| 	
		 GEH-6385   
					g 
					GE Industrial Systems   
					ACMVAC2-G   
					™ 
					Innovation Series   
					Medium Voltage – GP Type G Drives   
					Reference and Troubleshooting   
					2300 V Drives   
				g 
					GE Industrial Systems   
					Publication: GEH-6385   
					Issued: 2000-06-29   
					ACMVAC2-G   
					™ 
					Innovation Series   
					Medium Voltage – GP Type G Drives   
					Reference and Troubleshooting   
					2300 V Drives   
				© 2000 General Electric Company, USA.   
					All rights reserved.   
					Printed in the United States of America.   
					These instructions do not purport to cover all details or variations in equipment, nor to   
					provide every possible contingency to be met during installation, operation, and   
					maintenance. If further information is desired or if particular problems arise that are not   
					covered sufficiently for the purchaser’s purpose, the matter should be referred to GE   
					Industrial Systems, Salem, Virginia, USA.   
					This document contains proprietary information of General Electric Company, USA and is   
					furnished to its customer solely to assist that customer in the installation, testing,   
					operation, and/or maintenance of the equipment described. This document shall not be   
					reproduced in whole or in part nor shall its contents be disclosed to any third party without   
					the written approval of GE Industrial Systems.   
					Document Identification: GEH-6385, original release   
					Technical Writer/Editor: Teresa Davidson   
					The Innovation Series is a trademark of the General Electric Company, USA.   
					Microsoft is a registered trademark of the Microsoft Corporation.   
					Windows is a registered trademark of the Microsoft Corporation.   
					Modbus is a trademark of Modicon.   
					Profibus is trademark of Profibus International   
					Genius is a registered trademark of GE Fanuc Automation North America, Inc.   
				Safety Symbol Legend   
					Indicates a procedure, condition, or statement that, if not   
					strictly observed, could result in personal injury or death.   
					Indicates a procedure, condition, or statement that, if not   
					strictly observed, could result in damage to or destruction of   
					equipment.   
					Note Indicates an essential or important procedure, condition, or statement.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Safety Symbol Legend • a   
				This equipment contains a potential hazard of electric shock   
					or burn. Only personnel who are adequately trained and   
					thoroughly familiar with the equipment and the instructions   
					should install, operate, or maintain this equipment.   
					Isolation of test equipment from the equipment under test   
					presents potential electrical hazards. If the test equipment   
					cannot be grounded to the equipment under test, the test   
					equipment’s case must be shielded to prevent contact by   
					personnel.   
					To minimize hazard of electrical shock or burn, approved   
					grounding practices and procedures must be strictly followed.   
					To prevent personal injury or equipment damage caused by   
					equipment malfunction, only adequately trained personnel   
					should modify any programmable machine.   
					b • Safety Symbol Legend   
					Innovation Series Medium Voltage GP – Type G Drives GEH-6385   
				Contents   
					Chapter 1 Overview   
					1-1   
					Introduction...................................................................................................................... 1-1   
					Using Toolbox Help for Reference and Troubleshooting ................................................... 1-2   
					Related Documents........................................................................................................... 1-3   
					How to Get Help............................................................................................................... 1-3   
					Chapter 2 Faults and Troubleshooting   
					2-1   
					Introduction...................................................................................................................... 2-1   
					Types of Faults................................................................................................................. 2-2   
					Fault Indication................................................................................................................. 2-2   
					Fault Descriptions............................................................................................................. 2-3   
					Chapter 3 Paramters/Functions   
					3-1   
					Introduction...................................................................................................................... 3-1   
					Diagnostic and Utility Functions....................................................................................... 3-4   
					Diagnostic and Utility Overview ................................................................................ 3-4   
					Capture Buffer ........................................................................................................... 3-4   
					General Purpose Constants........................................................................................3-10   
					General Purpose Filters.............................................................................................3-11   
					Oscillator..................................................................................................................3-12   
					Position Feedback.....................................................................................................3-13   
					Predefined Constants.................................................................................................3-14   
					Signal Level Detector (SLD).....................................................................................3-15   
					Simulator..................................................................................................................3-18   
					Control Diagnostic Variables.....................................................................................3-19   
					Line Simulator..........................................................................................................3-19   
					Drive Configuration Functions.........................................................................................3-20   
					Intelligent Part Number (IPN) ...................................................................................3-20   
					Primary Motor & Application Data ...........................................................................3-21   
					General Setup Functions ..................................................................................................3-24   
					Keypad Overview .....................................................................................................3-24   
					Keypad Contrast Adjustment.....................................................................................3-25   
					Keypad Meter Configuration.....................................................................................3-25   
					Keypad Security Configuration .................................................................................3-27   
					Language and Units Presentation...............................................................................3-28   
					Language Display .....................................................................................................3-29   
					I/O Functions...................................................................................................................3-30   
					Analog and Digital I/O Testing .................................................................................3-30   
					Analog Inputs/Outputs and Mapping .........................................................................3-32   
					Digital Inputs/Outputs and Mapping..........................................................................3-33   
					LAN Functions................................................................................................................3-34   
					LAN Overview .........................................................................................................3-34   
					Frame Phaselock Loop..............................................................................................3-34   
					LAN Configuration and Health .................................................................................3-35   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Contents • i   
				LAN Signal Map.......................................................................................................3-38   
					Motor Control Functions..................................................................................................3-44   
					Motor Control Overview...........................................................................................3-44   
					Flux Curve................................................................................................................3-45   
					Leakage Inductance Curve ........................................................................................3-46   
					Line Transfer ............................................................................................................3-46   
					Motor Equivalent Circuit...........................................................................................3-48   
					Motor Temperature Estimation..................................................................................3-49   
					Power Dip Protection................................................................................................3-49   
					Tach Loss Detection..................................................................................................3-50   
					Protective Functions ........................................................................................................3-52   
					Custom User Faults...................................................................................................3-52   
					DC Link Protection...................................................................................................3-52   
					Ground Fault Protection (Fast) ..................................................................................3-54   
					Hardware Fault Strings .............................................................................................3-55   
					Heatsink Thermal Protection .....................................................................................3-56   
					Line-Line Voltage Protection ....................................................................................3-58   
					Motor Overtemperature Detection .............................................................................3-59   
					Phase Current Protection...........................................................................................3-60   
					Timed Overcurrent Detection....................................................................................3-61   
					Transformer Overtemperature Detection....................................................................3-65   
					Motor Ground Protection ..........................................................................................3-66   
					Phase Imbalance Monitor..........................................................................................3-68   
					Line Monitor.............................................................................................................3-70   
					Phase Lock Loop ......................................................................................................3-72   
					Sequencer Functions........................................................................................................3-74   
					Sequencer Overview .................................................................................................3-74   
					Fault Reset Logic......................................................................................................3-74   
					Sequencer Permissives ..............................................................................................3-76   
					Stopping Commands and Modes ...............................................................................3-78   
					Sequencer Commands...............................................................................................3-82   
					Sequencer Status.......................................................................................................3-85   
					Main Contactor Configuration...................................................................................3-87   
					Speed Reference Functions ..............................................................................................3-89   
					Critical Speed Avoidance..........................................................................................3-89   
					Local Speed Reference..............................................................................................3-90   
					Minimum Speed Limit..............................................................................................3-91   
					Remote Speed Reference...........................................................................................3-92   
					Speed Reference Generation .....................................................................................3-93   
					Speed Reference Ramp .............................................................................................3-94   
					Speed Reference Reverse ..........................................................................................3-97   
					Speed/Torque Control Functions......................................................................................3-99   
					Droop .......................................................................................................................3-99   
					Motor Control Interface...........................................................................................3-100   
					Speed Control Fault Check......................................................................................3-103   
					Speed Feedback Calculation....................................................................................3-105   
					Speed/Torque Overview..........................................................................................3-106   
					Speed/Torque Regulator..........................................................................................3-107   
					System Data Parameters.................................................................................................3-112   
					Exec time/Chop freq ...............................................................................................3-112   
					Motor ctrl alg sel.....................................................................................................3-112   
					Motor efficiency .....................................................................................................3-113   
					Motor service factor................................................................................................3-114   
					Motor winding cfg ..................................................................................................3-114   
					Preflux Forcing.......................................................................................................3-114   
					ii • Contents   
					Innovation Series Medium Voltage GP Type – G Drives GEH-6385   
				Chapter 4 Wizards   
					4-1   
					Introduction...................................................................................................................... 4-1   
					Cell Test Wizard............................................................................................................... 4-4   
					Cell Test Options....................................................................................................... 4-4   
					Running the Fiber-Optic Test ..................................................................................... 4-5   
					Running the Bridge Cell Test ..................................................................................... 4-8   
					DAC Setup......................................................................................................................4-10   
					Drive Commissioning......................................................................................................4-11   
					Drive Commissioning: Overview...............................................................................4-11   
					Drive Commissioning: Intelligent Part Number .........................................................4-11   
					Drive Commissioning: Drive Units............................................................................4-11   
					Drive Commissioning: AC Source Selection..............................................................4-12   
					Drive Commissioning: Motor Nameplate Data ..........................................................4-12   
					Drive Commissioning: Motor Crossover Voltage.......................................................4-13   
					Drive Commissioning: Motor Protection Class ..........................................................4-13   
					Drive Commissioning: Motor Poles...........................................................................4-13   
					Drive Commissioning: Motor Data Sheet ..................................................................4-13   
					Drive Commissioning: Motor Data Sheet - Equivalent Circuit Data ...........................4-14   
					Drive Commissioning: Motor Data Sheet - Flux Curve ..............................................4-15   
					Drive Commissioning: Motor and Process Speed Referencing ...................................4-15   
					Drive Commissioning: Tachometer Support ..............................................................4-16   
					Drive Commissioning: Tachometer Pulses Per Revolution.........................................4-16   
					Drive Commissioning: Tachometer Loss Protection...................................................4-16   
					Drive Commissioning: Stopping Configuration .........................................................4-17   
					Drive Commissioning: Flying Restart........................................................................4-17   
					Drive Commissioning: X-Stop Configuration ............................................................4-18   
					Drive Commissioning: X-Stop Ramp Time ...............................................................4-18   
					Drive Commissioning: Run Ready Permissive String.................................................4-19   
					Drive Commissioning: Starting and Stopping the Drive .............................................4-19   
					Drive Commissioning: Manual Reference..................................................................4-19   
					Drive Commissioning: Maximum Speed References..................................................4-20   
					Drive Commissioning: Jog Speed Setpoints...............................................................4-20   
					Drive Commissioning: Reference Ramp Bypass ........................................................4-20   
					Drive Commissioning: Reference Ramp Mode ..........................................................4-20   
					Drive Commissioning: Reference Ramp Speed Independent Rates.............................4-21   
					Drive Commissioning: Reference Ramp Speed Independent Rate Set Selection .........4-21   
					Drive Commissioning: Reference Ramp Programmed Acceleration Rates..................4-22   
					Drive Commissioning: Reference Ramp Programmed Acceleration Speeds................4-22   
					Drive Commissioning: Reference Ramp Programmed Deceleration Rates..................4-22   
					Drive Commissioning: Reference Ramp Programmed Deceleration Speeds................4-23   
					Drive Commissioning: DDI Increment and Decrement Rates (Local Mode) ...............4-23   
					Drive Commissioning: Speed/Torque Regulator Configuration..................................4-23   
					Drive Commissioning: Speed/Torque Regulator Modes.............................................4-23   
					Drive Commissioning: Torque Regulator Reference and Output ................................4-24   
					Drive Commissioning: Torque with Speed Override Reference and Output................4-24   
					Drive Commissioning: Torque with Speed Override Speed Error...............................4-24   
					Drive Commissioning: Torque with Speed Override Stopping Behavior.....................4-25   
					Drive Commissioning: Torque and Current Limits.....................................................4-25   
					Drive Commissioning: Torque and Current Limits Uniform.......................................4-25   
					Drive Commissioning: Failed Calculation .................................................................4-26   
					Drive Commissioning: Torque and Current Limit Selection.......................................4-26   
					Drive Commissioning: Normal Torque and Current Limits........................................4-26   
					Drive Commissioning: Alternate Torque and Current Limits......................................4-26   
					Drive Commissioning: Motoring Torque Limits ........................................................4-26   
					Drive Commissioning: Generating Torque Limits......................................................4-26   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Contents • iii   
				Drive Commissioning: Current Limits.......................................................................4-27   
					Drive Commissioning: Power Dip Ride-Through.......................................................4-27   
					Drive Commissioning: Parameter Calculation............................................................4-27   
					Drive Commissioning: Simulator Mode.....................................................................4-27   
					Drive Commissioning: Hardware Fault Strings in Simulator Mode ............................4-27   
					Drive Commissioning: Simulator Mechanical Configuration......................................4-27   
					Drive Commissioning: Exit Reminder .......................................................................4-28   
					Drive Commissioning: Conclusion............................................................................4-28   
					Line Transfer Tuneup ......................................................................................................4-28   
					Line Transfer Tuneup: Overview...............................................................................4-28   
					Line Transfer Tuneup: Motor Transfer Data ..............................................................4-28   
					Line Transfer Tuneup: Motor Capture Data ...............................................................4-29   
					Line Transfer Tuneup: Operation ..............................................................................4-29   
					Motor Control Tuneup.....................................................................................................4-31   
					Motor Control Tuneup: Equivalent Circuit ................................................................4-31   
					Motor Control Tuneup: Measurements ......................................................................4-32   
					Motor Control Tuneup: Operation .............................................................................4-32   
					Panel Meter Setup............................................................................................................4-32   
					Per Unit Setup .................................................................................................................4-32   
					Line Protection Setup.......................................................................................................4-33   
					Line Protection: Introduction.....................................................................................4-33   
					Line Protection: Default Settings...............................................................................4-33   
					Line Protection: Overvoltage.....................................................................................4-33   
					Line Protection: Undervoltage...................................................................................4-33   
					Line Protection: Overfrequency.................................................................................4-34   
					Line Protection: Underfrequency...............................................................................4-34   
					Line Protection: Conclusion ......................................................................................4-34   
					Pulse Test........................................................................................................................4-34   
					Pulse Test: Introduction ............................................................................................4-34   
					Pulse Test: Analog Output Configuration ..................................................................4-35   
					Pulse Test: Bridge State Configuration ......................................................................4-35   
					Pulse Test: Timer Configuration................................................................................4-37   
					Pulse Test: Operation................................................................................................4-37   
					Remaining Parameter Setup .............................................................................................4-37   
					Simulator Setup...............................................................................................................4-38   
					Simulator Setup: Introduction....................................................................................4-38   
					Simulator Setup: Simulator Mode..............................................................................4-38   
					Simulator Setup: Hardware Fault String Override......................................................4-38   
					Simulator Setup: Simulator Mechanical Configuration...............................................4-38   
					Simulator Setup: Conclusion .....................................................................................4-38   
					Speed Regulator Tuneup..................................................................................................4-39   
					Speed Regulator Tuneup: Model ...............................................................................4-39   
					Speed Regulator Tuneup: System Inertia ...................................................................4-39   
					Speed Regulator Tuneup: Inertia Measurement Command.........................................4-39   
					Speed Regulator Tuneup: Speed Regulator Mode ......................................................4-40   
					Speed Regulator Tuneup: Manual Regulator Tuneup .................................................4-40   
					Speed Regulator Tuneup: 1st Order Response............................................................4-40   
					Speed Regulator Tuneup: 2nd Order Response ..........................................................4-40   
					Speed Regulator Tuneup: 2nd Order Response with Stiffness Filter ...........................4-41   
					Speed Regulator Tuneup: Calculate Speed Regulator Gains Command ......................4-41   
					iv • Contents   
					Innovation Series Medium Voltage GP Type – G Drives GEH-6385   
				Chapter 5 Signal Mapping   
					5-1   
					Introduction...................................................................................................................... 5-1   
					LAN Interfaces................................................................................................................. 5-2   
					Parameter Configuration for Signal Mapping .................................................................... 5-3   
					Variable Mapping............................................................................................................. 5-4   
					Applying the LAN Heartbeat Echo Feature ....................................................................... 5-5   
					Application of Feedback Signals....................................................................................... 5-6   
					Variable Maps .................................................................................................................. 5-6   
					Real Variable Map..................................................................................................... 5-7   
					Boolean Variable Map ............................................................................................... 5-8   
					Appendix A Function Block Diagrams   
					A-1   
					Introduction......................................................................................................................A-1   
					Index   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Contents • v   
				Chapter 1 Overview   
					Introduction   
					This document provides reference and troubleshooting information for the 2300 V   
					model of the Innovation Series™ Medium Voltage – GP Type G drives. The purpose   
					of the document is to assist installation and maintenance technicians in   
					understanding the drive’s diagnostic and configuration software, as well as using   
					fault codes to troubleshoot drive problems.   
					Chapter 1 defines the document contents. Its purpose is to present a general product   
					overview for the reader, as follows:   
					Section   
					Page   
					Introduction ........................................................................................................ 1-1   
					Using Toolbox Help for Reference and Troubleshooting...................................... 1-2   
					Related Documents ............................................................................................. 1-3   
					How to Get Help ................................................................................................. 1-3   
					Notes .................................................................................................................. 1-4   
					Chapter 2, Faults and Troubleshooting, lists and defines drive fault messages,   
					with troubleshooting suggestions if a fault occurs.   
					Chapter 3, Functions/Parameters, lists and describes the drive application program   
					functions, including input parameters, output variables, and configuration.   
					Chapter 4, Wizards, describes in detail the automated Windows-based “forms” that   
					guide the user through drive configuration and tuneup.   
					Chapter 5, Signal Mapping, describes LAN interfaces and parameter configuration   
					for variable signal mapping.   
					Note The information in Chapters 2, 3, and 4 is duplicated from the GE Control   
					System Toolbox’s online Help files. This document, GEH-6385, is provided as   
					assistance when the toolbox is not available or was not purchased with the drive   
					system. (Refer to Using Toolbox Help for Reference and Troubleshooting in this   
					chapter.)   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 1 Overview • 1-1   
				Using Toolbox Help for Reference and Troubleshooting   
					The GE Control System Toolbox is an optionally purchased drive configuration   
					program used to tune and commission the drive as needed for each application. The   
					toolbox provides Microsoft® Windows®-based menus, block diagrams, dialog   
					boxes, and wizards on a PC-based drive interface.   
					GE document GEH-6401   
					describes toolbox features   
					and use.   
					When you choose Help on the toolbox main menu bar, a drop-down menu provides   
					several options for finding information.   
					Organized Help topics, a Help Index tab,   
					and a Find tab for searching the Help   
					database.   
					Send a toolbox "bug" report or   
					enhancement request directly to GE   
					(requires that e-mail is installed).   
					How to find information in Help and how to   
					customize the toolbox Help features.   
					Additional information about the toolbox   
					and GE contacts (requires access to the   
					GE intranet).   
					Information about faults, functions, wizards,   
					and special messages.   
					Information about the drive and toolbox   
					version, installation notes (compatibilities),   
					and requirements.   
					Identifies toolbox release, version, and   
					platform information.   
					From that menu, select Product Help to access online help files that contain the   
					fault, function, and wizard information provided in this manual.   
					Help Topics: Innovation Series ACMVAC4-G Help   
					Drive firmware and associated   
					reference files may change with   
					product upgrades and revisions.   
					The information provided in this   
					document, GEH-6385, is current   
					at the time of its issue. However,   
					the toolbox Help files provided   
					with your drive may be a more   
					current representation of your   
					drive configuration.   
					1-2 • Chapter 1 Overview   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Related Documents   
					If needed for supplementary information, refer to the following documents for the   
					Innovation Series Medium Voltage – GP Type G drives, as applicable:   
					GEH-6381, Installation and Startup   
					GEH-6382, User’s Guide   
					GEH-6401, Control System Toolbox   
					How to Get Help   
					If help is needed beyond the instructions provided in the documentation, contact GE   
					as follows:   
					GE Industrial Systems   
					Product Service Engineering   
					1501 Roanoke Blvd.   
					Salem, VA 24153-6492 USA   
					“+” indicates the   
					Phone: + 1 800 533 5885 (United States, Canada, Mexico)   
					+ 1 540 378 3280 (International)   
					international access code   
					required when calling from   
					outside of the USA.   
					Fax:   
					+ 1 540 387 8606 (All)   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 1 Overview • 1-3   
				Notes   
					1-4 • Chapter 1 Overview   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Chapter 2 Faults and Troubleshooting   
					Introduction   
					The drive software includes selftest diagnostics to aid in troubleshooting. When   
					these tests detect an unfavorable condition, they output fault indications to the   
					drive’s operator interfaces: the door-mounted Drive Diagnostic Interface (DDI,   
					referred to as the keypad) or a connected PC running the GE Control System   
					Toolbox (the toolbox). An operator can then use either interface to examine the fault   
					and clear it, as applicable.   
					For information on using the   
					keypad refer to the drive   
					User's Guide, GEH-6382.   
					GEH-6401 describes the   
					toolbox.   
					This chapter lists and defines the relevant fault messages for the drive, with   
					troubleshooting suggestions. It is organized as follows:   
					Section   
					Page   
					Introduction ........................................................................................................ 2-1   
					Types of Faults ................................................................................................... 2-2   
					Fault Indication................................................................................................... 2-2   
					Fault Descriptions ............................................................................................... 2-3   
					This equipment contains a potential hazard of electric shock   
					or burn. Only adequately trained persons who are   
					thoroughly familiar with the equipment and the instructions   
					should maintain this equipment.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-1   
				Types of Faults   
					There are currently two types of fault conditions:   
					• 
					Alarm faults indicate conditions that you should note, but that are not serious   
					enough to automatically shut down or trip the drive. If the condition goes away,   
					some alarm faults clear themselves and the display then identifies the alarm as   
					brief. Otherwise, you must stop the drive to clear this type of fault.   
					• 
					Trip faults indicate a more serious condition that needs to be corrected.   
					Therefore, it trips the drive. The drive should not be restarted until the condition   
					is corrected.   
					You can clear most faults by selecting Clear Faults on the drive’s keypad or in the   
					(optional) toolbox program.   
					Fault Indication   
					The drive indicates a fault condition on the keypad, toolbox display, and on the   
					DSPX board.   
					The DSPX board is the   
					IS200DSPX Digital Signal   
					Processor, located in the   
					drive control rack.   
					On the keypad, a fault icon appears in the right side of the display: The operator can   
					then use the keypad to access the fault/alarm description (see Figure 5-1) and to clear   
					the fault.   
					Abbreviated Description   
					Fault No.   
					ACTIVE FAULT   
					Fault Icon:   
					50 Trip   
					108 Brief   
					12 Trip   
					HtSink temp low,   
					DC bus voltage   
					Gnd flt,   
					Flashing = fault   
					Not flashing (on steady) = alarm   
					113 Trip   
					Invalid board   
					--- RESET FAULTS NOW --   
					Fault Behavior   
					Figure 2-1. Sample Fault Display Screen on Keypad   
					The toolbox uses a Windows -based PC display. When a fault occurs, the word   
					Alarm or Trip appears in the lower right corner of the screen. You can view a   
					description and clear the fault using the toolbox functions. (GE publication GEH-   
					6401 describes these tools and this feature.)   
					The DSPX Fault LED displays at the front of the drive’s control rack. This red   
					indicator is on solid for a fault and flashes for an alarm.   
					A fault is identified by an assigned number and abbreviated description. Both of   
					these are displayed when an operator examines a fault using the keypad (see Figure   
					2-1) or the toolbox.   
					Table 2-1 lists the drive faults and their probable cause.   
					2-2 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Fault Descriptions   
					Note When troubleshooting leads to a hardware inspection or component   
					replacement, be sure to follow the procedures described in the drive User’s Guide,   
					GEH-6382. This will help ensure that the equipment operates correctly.   
					When troubleshooting leads to a hardware inspection or   
					component replacement, be sure to follow the procedures   
					described in the drive User’s Guide, GEH-6382. This will help   
					prevent damage caused by incorrect installation and ensure   
					that the equipment operates correctly.   
					Table 2-1. Fault Definitions and Probable Cause   
					No. Name   
					1 CPFP isolation lost   
					Type Description   
					Trip   
					The CPFP isolation lost trip fault is hardware generated. The CPFP power   
					supply isolation card is indicating that power supply isolation to the phase   
					modules has been compromised. The CPFP card is designed to provide   
					control power to circuit cards in the high voltage compartment. This card has   
					a double voltage barrier that isolates the phases from each other and from the   
					control. This fault indicates that one of these voltage barriers has failed. This   
					is a dangerous situation since failure of the second barrier could cause   
					dangerous voltages to conduct into the control cabinet or cause a phase-   
					phase short on the CPFP card. The fault is generated when the status light   
					conducted via fiber from the CPFP goes out. The fiber connects CPFP (PWR   
					OK) to FOSA (SPARE-R). Check that the fiber is installed correctly.   
					Disconnect the fiber from FOSA and look for the status light traveling up the   
					fiber. If you do not see a light then the problem is on CPFP. If there is light   
					then the problem is on FOSA or BICM.   
					Primary causes:   
					CPFP power supply failure   
					Fiber not connected   
					Possible board failures:   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Power distribution wiring to CPFP.   
					2 
					Illegal seq state   
					Trip   
					The Illegal seq state trip fault occurs when the sequencer state (variable   
					Sequencer state) is unrecognized. This trip may occur during system   
					development but should not occur in the field.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-3   
				No. Name   
					Type Description   
					The Cont failed to close trip fault occurs when contactor A is commanded to   
					3 Cont failed to close Trip   
					open or close and fails to do so within the allowed time (defined by parameter   
					MA pickup time).   
					Primary causes:   
					The contactor A feedback is missing or bad.   
					Possible configuration faults:   
					The allowed time for contactor A to open and close is too short. The allowed   
					time is represented by parameter MA pickup time.   
					Contactor A feedback is enabled when no contactor is present in the system.   
					In the absence of the contactor, parameter MA contactor fbk should be set   
					equal to Disable.   
					Related functions:   
					Main Contactor Configuration   
					4 
					Local flt   
					Trip   
					Trip   
					The Local flt trip fault occurs when the local permissive circuit is open and a   
					Run request, Jog request, Full flux request, or diagnostic test (cell test, pulse   
					test, autotune) request is issued.   
					Possible wiring faults:   
					The connections to ATBA terminal board locations 8 (L115), 10 (L24), and 12   
					(LCOM) are missing or damaged.   
					The connection to backplane connector J2 is missing or damaged.   
					5 
					6 
					Tool requested trip   
					The Tool requested trip trip fault is generated from the engineering monitor   
					issuing the “uf” command. It is for test purposes only.   
					Run cmd during init Alarm   
					The Run cmd during init alarm occurs when a Run request, Jog request, Full   
					flux request, or diagnostic test (cell test, pulse test, autotune) request is issued   
					during drive initialization. When the alarm occurs, the request to perform a   
					drive action is ignored.   
					Primary causes:   
					The external application layer issues a request to perform a drive action during   
					drive initialization.   
					An external input (i.e. digital input) used to request a drive action was high   
					during drive initialization.   
					7 
					Over speed   
					Trip   
					The Over speed trip fault occurs when the magnitude of speed (variable   
					Speed reg fbk) is greater than the over speed threshold (parameter Over   
					speed flt level).   
					Primary causes:   
					Motor speed is too high.   
					Possible configuration faults:   
					Parameter Over speed flt level is set too low.   
					Related functions:   
					Speed Control Fault Check   
					8 
					9 
					Timed over current   
					EE flash corrupted   
					Trip   
					Trip   
					The Timed over current trip fault occurs when one of the squared phase   
					currents (variables Ia^2 filtered, Ib^2 filtered, and Ic^2 filtered) in the timed   
					over current detection model exceeds the timed over current threshold level.   
					This fault indicates that the motor has exceeded its thermal limit.   
					The EE flash corrupted trip fault occurs when the memory containing the drive   
					parameters is determined to be bad during drive initialization.   
					EE flash corrupted requires a hard reset to clear.   
					Possible board failures:   
					DSPX   
					2-4 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					Alarm   
					10   
					Run cmd w high   
					flux   
					The Run cmd w high flux alarm occurs when a Run request, Jog request, Full   
					flux request, or diagnostic test (cell test, pulse test, autotune) request is issued   
					and the variable Flux reference is greater than 2 percent rated flux (100%   
					Flux).   
					Primary causes:   
					An attempt is made to restart the drive quickly. Normally four rotor time   
					constants are required to allow the flux to decay after the drive stops running.   
					Related functions:   
					Sequencer Permissives   
					11   
					EE erase failed   
					Alarm   
					The EE erase failed trip fault occurs when the preparation of memory for the   
					next parameter save operation fails to happen satisfactorily. The next   
					parameter save operation is expected to be invalid, and the integrity of future   
					parameter save operations are in doubt.   
					EE erase failed requires a hard reset to clear.   
					Possible board failures:   
					DSPX   
					12   
					13   
					Gnd flt, coarse   
					Trip   
					The Gnd flt, coarse trip fault occurs when a large ground current is detected.   
					The trip fault occurs when the magnitude of the sum of the three phase   
					currents is too large.   
					Vdc Fbk voltage   
					trim   
					Alarm   
					The Vdc Fbk voltage trim alarm occurs when the automatic Vdc feedback trim   
					function on the BICM is not functioning correctly. You will not receive this   
					warning unless you are using drive firmware version V02.21.00B or higher   
					AND you have a BICMH1AB version card or higher. Older versions of   
					software and hardware suffer from Vdc feedback inaccuracy, which can lead   
					to problems in some circumstances. Getting the trim function to operate   
					properly is important to optimum performance of the drive. There are several   
					situations that can lead to this alarm.   
					First, make sure you have run the Cell Test Wizard (either fiber optic test or   
					bridge cell test) at least once when the DC link is fully discharged (<100V).   
					This wizard calibrates the DC bus feedback and saves a parameter in the   
					drive. This procedure does not need to be repeated unless hardware has   
					changed in the drive or the previously saved parameter was overwritten by a   
					parameter downloaded from the toolbox. If this procedure has not been   
					performed then this alarm is generated.   
					Second, make sure that JP1 on the BICMH1AB card has been moved to the   
					non-default position. This jumper enables the circuit that this alarm is   
					concerned with. The jumper JP1 being in the dashed-box indicates the non-   
					default position. The jumper being in the solid box indicates the default   
					position. The default position is used only when the card is placed in drives   
					that have software versions prior to V02.21.00B   
					If both if these steps fail to clear this alarm then your BICM card may be   
					defective.   
					Primary board failures   
					BICM   
					14   
					Cap buff init failed   
					Alarm   
					The capture buffer initialization has failed to allocate enough memory to run   
					the capture buffer. The capture buffer has been disabled and will not run.   
					However the drive should operate normally.   
					A new version of firmware is required to correct this problem.   
					15   
					MA cont not closed Trip   
					The MA cont not closed trip fault occurs when the MA feedback indicates that   
					the MA contactor is open when it is commanded to close.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-5   
				No. Name   
					Type Description   
					16   
					Illegal req for xfer   
					Alarm   
					The Illegal req for xfer alarm occurs when a motor transfer command is issued   
					and a trip fault is present in the drive. The alarm may also occur when a motor   
					transfer command is issued at the same time a diagnostic test (cell test, pulse   
					test, autotune) is active.   
					Primary causes:   
					The external application layer issues an inappropriate motor transfer request.   
					17   
					Transfer req   
					aborted   
					Trip   
					Trip   
					The Transfer req aborted trip fault occurs when the motor control is unable to   
					synchronize to the utility line in the allotted time in response to a motor transfer   
					request.   
					18   
					Tune up failed   
					The Tune up failed trip fault occurs when an attempt to run the motor control   
					tune up or the speed regulator tune up fails.   
					Primary causes:   
					The external application layer issues an inappropriate motor control tune up   
					request or speed regulator tune up request.   
					An attempt by the motor control tune up or the speed regulator tune up to   
					initialize the diagnostic message stack fails.   
					19   
					20   
					Ext ref out of range Alarm   
					The Ext ref out of range alarm occurs when the external line reference voltage   
					is outside of the allowable range.   
					TOC pending   
					Alarm   
					The TOC pending alarm occurs when one of the squared phase currents   
					(variables Ia^2 filtered, Ib^2 filtered, and Ic^2 filtered) in the timed over current   
					detection model exceeds the timed over current alarm level.   
					This alarm indicates that the motor is nearing its thermal limit.   
					21   
					System flt   
					Trip   
					The System flt trip fault occurs when the system permissive circuit is open and   
					a Run request, Jog request, Full flux request, or diagnostic test (cell test, pulse   
					test, autotune) request is issued.   
					Possible wiring faults:   
					The connections to ATBA terminal board locations 2 (S115), 4 (S24), and 6   
					(SCOM) are missing or damaged..   
					22   
					23   
					Trip   
					Trip   
					Run before MA   
					closed   
					The Run before MA closed trip fault occurs when a Run request, Jog request,   
					or Full flux request is issued to the motor control sequencer before contactor A   
					is closed.   
					Related functions:   
					Sequencer Permissives   
					Main Contactor Configuration   
					Flying restrt disabl   
					The Flying restrt disabl trip fault occurs when a Run request, Jog request, Full   
					flux request, or diagnostic test (cell test, pulse test, autotune) request is issued   
					when the motor is not at zero speed.   
					Flying restrt disabl can be turned off and the drive allowed to start when the   
					motor is not at zero speed by placing the drive in flying restart mode. Flying   
					restart mode is enabled by setting parameter Flying restart equal to Enable fly   
					restart.   
					Related functions:   
					Sequencer Permissives   
					2-6 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					24   
					Power dip   
					Trip   
					The Power dip trip fault occurs when the DC link voltage feedback (variable   
					DC bus voltage) falls below the power dip level and remains below the power   
					dip level longer than the power dip time.   
					The power dip time is configurable through parameter Power dip control.   
					If the DC link voltage feedback is at some moments below the power dip level   
					and at some moments above the power dip level, the trip fault can occur. If   
					over any time interval the DC link feedback spends more time below the power   
					dip level than above the power dip level, and the time difference is greater   
					than the power dip time, Power dip occurs.   
					Possible configuration faults:   
					Power dip functionality is disabled because parameter Power dip control is set   
					incorrectly. To enable power dip functionality parameter Power dip control   
					should be set equal to 0.500 sec (Enable).   
					Related functions:   
					Power Dip Protection   
					25   
					Cur reg in limit   
					Alarm   
					The Cur reg in limit alarm occurs when the X and/or Y current regulator output   
					enter limits for more than 1 sec. It is cleared when the X and/or Y current   
					regulator come out of limit for more than of equal to 1 sec.   
					Primary causes:   
					The tachometer feedback is bad.   
					Large motor parameters errors.   
					Motor inverter connection opens while running.   
					Power dip.   
					Loss of current feedback.   
					26   
					Volt reg in limit   
					Alarm   
					The Volt reg in limit alarm occurs when the X and/or Y voltage regulator output   
					enter limits for more than 1 sec. It is cleared when the X and/or Y voltage   
					regulator come out of limit for more than of equal to 1 sec.   
					Primary causes:   
					Motor inverter connection opens while running.   
					Power dip.   
					Loss of voltage feedback.   
					28   
					29   
					R1 meas in limit   
					R2 meas in limit   
					Alarm   
					Alarm   
					The R1 meas in limit alarm occurs when the total primary resistance measured   
					during drive pre-flux is outside of a reasonable bound. The total primary   
					resistance consists of the stator and cable resistances. When the fault   
					condition is present, the motor control does not use the resistance   
					measurement.   
					The R2 meas in limit alarm occurs when the online calculation of rotor   
					resistance exceeds the positive or negative saturation level. The saturation   
					levels are 80 percent and -40 percent.   
					Primary causes:   
					The rotor resistance calculation is incorrect due a large error in motor   
					parameters.   
					30   
					Tach loss trip   
					Trip   
					The Tach loss trip fault occurs when the difference between the tachometer   
					feedback (variable Motor speed) and the estimated speed (variable Calculated   
					speed) is too large.   
					The trip fault can be disabled by setting parameter Tach loss fault mode equal   
					to Trip.   
					Primary causes:   
					The tachometer feedback is bad.   
					The estimated speed is incorrect due to large errors in motor parameters.   
					Related functions:   
					Tach Loss Detection   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-7   
				No. Name   
					Tach loss alarm   
					Type Description   
					31   
					32   
					33   
					34   
					Alarm   
					The Tach loss alarm occurs when the difference between the tachometer   
					feedback (variable Motor speed) and the estimated speed (variable Calculated   
					speed) is too large.   
					When the alarm occurs, the drive dynamically switches to tachless control   
					mode. The drive continues tachless operation until the fault is cleared by an   
					operator.   
					Tach loss fault mode can be used to change the fault behavior to trip if   
					required.   
					Primary causes:   
					The tachometer feedback is bad.   
					The estimated speed is incorrect due to large errors in motor parameters.   
					Related functions:   
					Tach Loss Detection   
					IOC phase A   
					IOC phase B   
					IOC phase C   
					Trip   
					The IOC phase A trip fault is hardware generated. The trip fault occurs when   
					the current measured by the phase A shunt exceeds the instantaneous   
					overcurrent threshold, which is positive or negative 250 percent rated shunt   
					current. It also occurs within 25 microseconds when the phase A current   
					experiences a step change of 100 percent rated shunt. When either condition   
					is detected, the power bridge IGBT gating is disabled immediately.   
					Possible board failures:   
					SHCA   
					FOSA   
					BICM   
					HFPA (FU4)   
					Possible wiring faults:   
					Connections between FOSA and SHCA.   
					Trip   
					The IOC phase B trip fault is hardware generated. The trip fault occurs when   
					the current measured by the phase B shunt exceeds the instantaneous   
					overcurrent threshold, which is positive or negative 250 percent rated shunt   
					current. It also occurs within 25 microseconds when the phase B current   
					experiences a step change of 100 percent rated shunt. When either condition   
					is detected, the power bridge IGBT gating is disabled immediately.   
					Possible board failures:   
					SHCA   
					FOSA   
					BICM   
					HFPA (FU4)   
					Possible wiring faults:   
					Connections between FOSA and SHCA.   
					Trip   
					The IOC phase C trip fault is hardware generated. The trip fault occurs when   
					the current measured by the phase C shunt exceeds the instantaneous   
					overcurrent threshold, which is positive or negative 250 percent rated shunt   
					current. It also occurs within 25 microseconds when the phase C current   
					experiences a step change of 100 percent rated shunt. When either condition   
					is detected, the power bridge IGBT gating is disabled immediately.   
					Possible board failures:   
					SHCA   
					FOSA   
					BICM   
					HFPA (FU4)   
					Possible wiring faults:   
					Connections between FOSA and SHCA.   
					2-8 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					Trip   
					36   
					BICM card clock   
					fail   
					The BICM card clock fail   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-9   
				No. Name   
					Type Description   
					Trip   
					46   
					X stop   
					The X stop trip fault occurs when the X stop circuit is open and when X stop is   
					configured as a trip fault. X stop is configured as a trip fault when parameter X   
					stop mode is set equal to Trip flt stop. Any other setting for parameter X stop   
					mode disables the X stop trip fault.   
					The state of the X stop circuit is determined by the value of the variable to   
					which parameter X stop request sel points. The X stop trip fault can be   
					disabled, along with all other X stop behavior, by setting parameter X stop   
					request sel equal to Unused.   
					Related functions:   
					Stopping Commands and Modes   
					47   
					Trip   
					Run req & xstop   
					open   
					The Run req & xstop open trip fault occurs when the X stop circuit is open, the   
					drive is stopped, and one of the following requests is issued: Run request, Jog   
					request, or Full flux request.   
					The state of the X stop circuit is determined by the value of the variable to   
					which parameter X stop request sel points. The trip fault can be disabled,   
					along with all other X stop behavior, by setting parameter X stop request sel   
					equal to Unused.   
					Related functions:   
					Sequencer Permissives   
					Stopping Commands and Modes   
					48   
					BICM card temp   
					low   
					Trip   
					The BICM card temp low trip fault occurs when the sensor on BICM measures   
					a temperature that is –20C or below.   
					BIC ambient temp is the variable being monitored to generate this fault.   
					Primary causes:   
					Failed thermal sensor on BICM.   
					Ambient temperature is too low.   
					Possible board failures:   
					BICM   
					49   
					HtSink DB temp   
					low   
					Trip   
					The HtSink DB temp low trip fault occurs when the dynamic brake heatsink   
					temperature (variable DB heat sink temp) is too low.   
					The main purpose of this trip fault is to detect the absence of the thermal   
					sensor input from the heatsink.   
					Primary causes:   
					The DB heatsink thermal sensor input is not present.   
					No power to TFBA card or TFBA card failure.   
					Possible board failures:   
					BICM   
					TFBA   
					CPFP   
					Possible wiring faults:   
					Thermal sensor input to TFBA is missing or damaged.   
					Related functions:   
					Heatsink Thermal Protection   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-11   
				No. Name   
					Type Description   
					50   
					Trip   
					HtSink DS temp   
					low   
					The HtSink DS temp low trip fault occurs when the diode source heatsink   
					temperature (variable DS heat sink temp) is too low.   
					The main purpose of the fault is to detect the absence of the thermal sensor   
					input from the heatsink.   
					Primary causes:   
					The DS heatsink thermal sensor input is not present.   
					No power to TFBA card or TFBA card failure.   
					Possible board failures:   
					BICM   
					TFBA   
					CPFP   
					Possible wiring faults:   
					Thermal sensor input to TFBA is missing or damaged   
					Related functions:   
					Heatsink Thermal Protection   
					51   
					52   
					53   
					54   
					HtSink A temp low   
					HtSink B temp low   
					HtSink C temp low   
					Ambient temp low   
					Trip   
					Trip   
					Trip   
					Trip   
					The HtSink A temp low trip fault occurs when heatsink A temperature (variable   
					Heat sink A temp) is too low.   
					Related functions:   
					Heatsink Thermal Protection   
					The HtSink B temp low trip fault occurs when when heatsink B temperature   
					(variable Heat sink B temp) is too low.   
					Related functions:   
					Heatsink Thermal Protection   
					The HtSink C temp low trip fault occurs when when heatsink C temperature   
					(variable Heat sink C temp) is too low.   
					Related functions:   
					Heatsink Thermal Protection   
					The Ambient temp low trip fault occurs when the ambient temperature   
					(variable Bridge ambient temp) is too low.   
					The main purpose of the trip fault is to detect the absence of the ambient   
					thermal sensor input.   
					Primary causes:   
					The ambient thermal sensor input is not present.   
					Possible board failures:   
					BICM   
					Possible wiring faults:   
					The thermal sensor input to backplane connector J4 pins 7 and 8 is missing or   
					damaged.   
					55   
					56   
					AC line fuse blown   
					Trip   
					Trip   
					The AC line fuse blown trip fault occurs when one of the fuses feeding the   
					diode source assembly opens.   
					Primary causes:   
					Loss of I24 supply on CTBC feeding this string .   
					Shorted diode in source bridge.   
					DB resistor   
					overload   
					The DB resistor overload trip fault occurs when the dynamic braking resistor   
					thermal model indicates that the dynamic braking package has exceeded its   
					rating.   
					Primary causes:   
					Incorrect configuration of DB thermal model.   
					DB resistor package has not been sized correctly for application.   
					2-12 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					57   
					DB resistor hot   
					Alarm   
					The DB resistor hot alarm occurs when the dynamic braking resistor thermal   
					model indicates that the dynamic braking package is approaching its rating.   
					Primary causes:   
					Incorrect configuration of DB thermal model.   
					DB resistor package is marginal for application.   
					58   
					Motor reac parms   
					bad   
					Trip   
					The Motor reac parms bad trip fault occurs when the primary motor reactance   
					parameters have values that are not appropriate relative to one another.   
					Primary causes:   
					Internal calculations are performed using Starting react Xst, Magnetizing react   
					Xm, Stator lkg react X1,and Rotor lkg react X2. The relationship between   
					these parameters should be: (Rotor lkg react X2 || Magnetizing react Xm) +   
					Stator lkg react X1 > Starting react Xst.   
					This should be corrected before attempting to run the drive.   
					63   
					BICM card over   
					temp   
					Fault   
					The BICM card over temp trip fault occurs when the sensor on BICM   
					measures a temperature above 60C. The drive control electronics cannot   
					operate reliably above this temperature. Reset the fault after the temperature   
					drops below 60C.   
					BIC ambient temp is the variable being monitored to generate this fault.   
					Primary causes:   
					Blocked air flow to control rack.   
					Control rack cooling fan failure.   
					Ambient temperature is too high.   
					Possible board failures:   
					BICM   
					64   
					65   
					Trip   
					Trip   
					HtSink DB over   
					temp   
					The HtSink DB over temp trip fault occurs when the dynamic brake heatsink   
					temperature (variable DB heat sink temp) is too high.   
					Related functions:   
					Heatsink Thermal Protection   
					HtSink DS over   
					temp   
					The HtSink DS over temp trip fault occurs when the diode source heatsink   
					temperature (variable DS heat sink temp) is too high.   
					The bridge turns off in response to the fault to protect the IGBTs from thermal   
					damage.   
					Primary causes:   
					Airflow to the heatsink is not sufficient.   
					Blower is not operating correctly.   
					Possible board failures:   
					BICM   
					Related functions:   
					Heatsink Thermal Protection   
					66   
					67   
					HtSink A over temp Trip   
					The HtSink A over temp trip fault occurs when heatsink A temperature   
					(variable Heat sink A temp) is too high.   
					Related functions:   
					Heatsink Thermal Protection   
					HtSink B over temp Trip   
					The HtSink B over temp trip fault occurs when heatsink B temperature   
					(variable Heat sink B temp) is too high.   
					Related functions:   
					Heatsink Thermal Protection   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-13   
				No. Name   
					Type Description   
					68   
					HtSink C over temp Trip   
					The HtSink C over temp trip fault occurs when heatsink C temperature   
					(variable Heat sink C temp) is too high.   
					Related functions:   
					Heatsink Thermal Protection   
					69   
					BICM card hot   
					Alarm   
					The BICM card hot alarm occurs when the sensor on BICM measures a   
					temperature that is hot. The sensed temperature is above 55C and the control   
					electronics are operating outside of their design parameters. If the   
					temperature continues to rise and exceeds 60C, the drive will trip. This   
					warning is generated in order to allow time for corrective action to be taken.   
					BIC ambient temp is the variable being monitored to generate this alarm.   
					Primary causes:   
					Blocked air flow to control rack.   
					Control rack cooling fan failure.   
					Ambient temperature is too high.   
					Possible board failures:   
					BICM   
					70   
					71   
					72   
					73   
					74   
					75   
					HtSink DB temp hot Alarm   
					The HtSink DB temp hot alarm occurs when the dynamic brake heatsink   
					temperature (variable DB heat sink temp) is high.   
					Related functions:   
					Heatsink Thermal Protection   
					HtSink DS temp hot Alarm   
					The HtSink DS temp hot alarm occurs when the diode source heatsink   
					temperature (variable DS heat sink temp) is high.   
					Related functions:   
					Heatsink Thermal Protection   
					HtSink A temp hot   
					HtSink B temp hot   
					HtSink C temp hot   
					Alarm   
					Alarm   
					Alarm   
					Alarm   
					The HtSink A temp hot alarm occurs when heatsink A temperature (variable   
					Heat sink A temp) is high.   
					Related functions:   
					Heatsink Thermal Protection   
					The HtSink B temp hot alarm occurs when heatsink B temperature (variable   
					Heat sink B temp) is high.   
					Related functions:   
					Heatsink Thermal Protection   
					The HtSink C temp hot alarm occurs when heatsink C temperature (variable   
					Heat sink C temp) is high.   
					Related functions:   
					Heatsink Thermal Protection   
					Switchgear not   
					ready   
					The Switchgear not ready alarm occurs when the permissive string to close   
					the main switchgear is not present. This permissive string ends at BTBH(8)   
					and includes customer contacts used to open the main. The primary purpose   
					of the alarm is to prevent charging of the DC bus until the switchgear is ready   
					to close.   
					Primary causes:   
					Switchgear not racked in.   
					Customer switchgear permissive not met.   
					76   
					HtSink DB rise high Alarm   
					The HtSink DB rise high alarm occurs when the dynamic brake heatsink   
					temperature (variable DB heat sink temp) is too far above the ambient   
					temperature (variable Bridge ambient temp).   
					Related functions:   
					Heatsink Thermal Protection   
					2-14 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					The HtSink DS rise high alarm occurs when the diode source heatsink   
					77   
					78   
					79   
					80   
					81   
					HtSink DS rise high Alarm   
					temperature (variable DS heat sink temp) is too far above the ambient   
					temperature (variable Bridge ambient temp).   
					Related functions:   
					Heatsink Thermal Protection   
					HtSink A rise high   
					HtSink B rise high   
					HtSink C rise high   
					Alarm   
					Alarm   
					Alarm   
					Trip   
					The HtSink A rise high alarm occurs when heatsink A temperature (variable   
					Heat sink A temp) is too far above the ambient temperature (variable Bridge   
					ambient temp).   
					Related functions:   
					Heatsink Thermal Protection   
					The HtSink B rise high alarm occurs when heatsink B temperature (variable   
					Heat sink B temp) is too far above above the ambient temperature (variable   
					Bridge ambient temp).   
					Related functions:   
					Heatsink Thermal Protection   
					The HtSink C rise high alarm occurs when heatsink A temperature (variable   
					Heat sink C temp) is too far above above the ambient temperature (variable   
					Bridge ambient temp).   
					Related functions:   
					Heatsink Thermal Protection   
					HtSink temp   
					imbalanc   
					The HtSink temp imbalanc trip fault occurs when two of the measured heatsink   
					temperatures differ by an amount exceeding heatsink imbalance fault level.   
					The main purpose of the trip fault is to detect the absence of a thermal sensor   
					input from the heatsink, the failure of the sensor itself or heat pipe failure.   
					Primary causes:   
					A heatsink thermal sensor input is not present.   
					A heatsink thermal sensor is defective   
					The heatpipe system is defective.   
					Possible board failures:   
					BICM   
					Related functions:   
					Heatsink Thermal Protection   
					82   
					Trip   
					HtSink blower   
					failed   
					The HtSink blower failed trip fault occurs when the drive is running and the   
					cooling fans are not operating.   
					Primary causes:   
					Blower starter tripped due to blower motor overload or failure.   
					Related functions:   
					Heatsink Thermal Protection   
					83   
					84   
					Run permissive lost Alarm   
					The Run permissive lost alarm occurs when the run permissive circuit is open.   
					The state of the run permissive circuit is determined by the value of the   
					variable to which parameter Run permissive sel points. The alarm can be   
					disabled by setting parameter Run permissive sel equal to Unused.   
					Related functions:   
					Sequencer Permissives   
					Cont req while flt   
					Alarm   
					The Cont req while flt alarm occurs when contactor A is commanded to close   
					and a trip fault is present in the drive.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-15   
				No. Name   
					Type Description   
					85   
					Flux req while flt   
					Alarm   
					The Flux req while flt alarm occurs when a flux command is issued and a trip   
					fault is present in the drive. The alarm may also occur when a flux command   
					is issued at the same time a diagnostic test (cell test, pulse test, autotune) is   
					active.   
					Primary causes:   
					The external application layer issues an inappropriate flux enable request.   
					86   
					AC line over   
					voltage   
					Trip   
					The AC line over voltage trip fault occurs when the control firmware detects   
					that the magnitude of the AC line is above the value of Line OV fault level,   
					which has a suggested value of 117% of nominal.   
					The voltage magnitude used for this comparison is a processed by a low-pass   
					filter. This filter is set to 1.2 rad/sec as a default, so transient over-voltages   
					are allowed above the threshold value without causing this trip fault.   
					Primary causes:   
					AC line voltage is excessive.   
					Possible configuration faults:   
					Source has been applied at a voltage other than that set by the factory.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					87   
					AC line voltage   
					high   
					Alarm   
					The AC line voltage high alarm occurs when the control firmware detects that   
					the magnitude of the AC line is above the value of Line OV alarm level, which   
					has a suggested value of 112% of nominal.   
					The voltage magnitude used for this comparison is a low-pass filtered version   
					of the fastest version. The filter is set to 1.2 rad/sec as a default, so transient   
					voltage above the alarm turn-on value can occur without causing this alarm.   
					This alarm will cease once the filtered value of voltage magnitude has   
					decreased to below Line OV alarm clear, which has a suggested value of   
					110% of nominal.   
					Primary causes:   
					AC line voltage is marginally excessive.   
					Possible configuration faults:   
					Source has been applied at a voltage other than that set by the factory.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					2-16 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					88 AC line under volt   
					Type Description   
					Trip   
					The AC line under volt trip fault occurs when the control firmware detects that   
					the magnitude of the ac line is below the value of Line UV fault level, which   
					has a suggested value of 50% of the nominal ac line input.   
					The voltage magnitude used for this comparison is a low-pass filtered version   
					of the signal. The filter is set to 1.2 rad/sec as a default, so transient voltages   
					below the alarm turn-on value can occur without causing this trip fault.   
					Primary causes:   
					AC line voltage too low.   
					Possible configuration faults:   
					Source has been applied at a voltage other than that set by the factory.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					89   
					AC line volts low   
					Alarm   
					The AC line volts low alarm occurs when the control firmware detects that the   
					magnitude of the ac line is below the value of Line UV alarm level, which has a   
					suggested value of 88% of nominal.   
					The voltage magnitude used for this comparison is a low-pass filtered version   
					of the fastest version. The filter is set to 1.2 rad/sec as a default, so transient   
					voltage above the alarm turn-on value can occur without causing this alarm.   
					This alarm will cease once the filtered value of voltage magnitude has   
					increased to above the value of Line UV alarm clear, which has a suggested   
					value of 90% of nominal.   
					Primary causes:   
					AC line voltage is marginally low.   
					Possible configuration faults:   
					Source has been applied at a voltage other than that set by the factory.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					90   
					AC line over freq   
					Trip   
					The AC line over freq trip fault occurs when the control firmware detects that   
					the frequency of the AC line is above the value of Over freq flt level, which   
					has a suggested value of 125% of nominal.   
					The frequency value used for this comparison is a low-pass filtered version of   
					the fastest version. The filter is set to .2 rad/sec as a default, so transient   
					over-frequency values are allowed above the threshold value without causing   
					this trip fault.   
					Primary causes:   
					AC line frequency is excessive.   
					Possible configuration faults:   
					Source has been applied at a 60hz while the factory setup value, AC grid   
					frequency was at 50hz.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-17   
				No. Name   
					91 AC line freq high   
					Type Description   
					Alarm   
					The AC line freq high alarm occurs when the control firmware detects that the   
					frequency of the AC line is above the value of Over freq alm level, which has   
					a suggested value of nominal frequency plus 17.3 rad/sec.   
					The frequency value used for this comparison is a low-pass filtered version of   
					the fastest version. The filter is set to .2 rad/sec as a default, so transient   
					over-frequency values are allowed above the threshold value without causing   
					this alarm.   
					This alarm will cease once the filtered value of filtered frequency has   
					decreased to below the value of Over freq alm clear, which has a suggested   
					value of nominal frequency plus 15.7rad/sec.   
					Primary causes:   
					AC line frequency is marginally excessive.   
					Possible configuration faults:   
					Source has been applied 60hz while the factory setup value, AC grid   
					frequency was at 50hz.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					92   
					AC line under freq   
					Trip   
					The AC line under freq trip fault occurs when the control firmware detects that   
					the frequency of the AC line is below the value of Under freq flt level, which   
					has a suggested value of nominal of 50% of nominal.   
					The frequency value used for this comparison is a low-pass filtered version of   
					the fastest version. The filter is set to .2 rad/sec as a default, so transient   
					under-frequency values are allowed below the threshold value without   
					causing this trip fault.   
					Primary causes:   
					AC line frequency is low.   
					Possible configuration faults:   
					Source has been applied at 50hz while the factory setup value, AC grid   
					frequency was at 60hz.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					2-18 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					93 AC line freq low   
					Type Description   
					Alarm   
					The AC line freq low alarm occurs when the control firmware detects that the   
					frequency of the AC line is below the value of Under freq alm level, which has   
					a suggested value of nominal minus 17.3rad/sec.   
					The frequency value used for this comparison is a low-pass filtered version of   
					the fastest version. The filter is set to .2 rad/sec as a default, so transient   
					under-frequency values are allowed below the threshold value without   
					causing this alarm.   
					This alarm will cease once the filtered value of filtered frequency has   
					increased to a value above below the value of Under freq alarm clr, which has   
					a suggested value of nominal frequency minus 15.7rad/sec.   
					Primary causes:   
					AC line frequency is transiently low.   
					Possible configuration faults:   
					Source has been applied at 50hz while the factory setup value, AC grid   
					frequency was at 60hz.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					94   
					Stat charger   
					timeout   
					Trip   
					The Stat charger timeout trip fault occurs when the static charger is unable to   
					completely charge the DC bus. Normal charge operation terminates when the   
					DC bus reaches 90% of its nominal level. At this point the charger is turned   
					off and the switch gear is closed. If after around 70 seconds of charging the   
					DC bus does not reach this threshold then the trip fault is generated and the   
					charging sequence is aborted.   
					Primary causes:   
					Static charger failure.   
					DC bus capacitor defective.   
					95   
					96   
					Stat charger failed   
					Switchgear failure   
					Trip   
					Trip   
					The Stat charger failed trip fault occurs when the static charger reports a fault   
					during its operation. The DC bus charging procedure stops when the trip fault   
					occurs.   
					Primary causes:   
					Static charger failure.   
					The Switchgear failure trip fault occurs when the AC line switchgear does not   
					close in response to a close command during the bus charging sequence.   
					The trip fault also occurs when the switchgear opens unexpectedly during   
					drive operation.   
					Primary causes:   
					Switchgear defective.   
					Switchgear opened via external command.   
					Switchgear tripped.   
					97   
					Vdc <200v after   
					5sec   
					Trip   
					The Vdc <200v after 5sec trip fault occurs when the static charger fails to   
					charge the DC bus voltage to 200 volts within 5 seconds. The DC bus   
					charging procedure stops when the trip fault occurs.   
					Primary causes:   
					Static charger failure.   
					Local Fault or System Fault Active   
					DC bus shorted.   
					DC feedback not working.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-19   
				No. Name   
					98 Ambient over temp   
					Type Description   
					Trip   
					The Ambient over temp trip fault occurs when the ambient temperature   
					(variable Bridge ambient temp) is too high.   
					The main purpose of the trip fault is to use the ambient temperature   
					measurement to detect a condition which could endanger the power bridge.   
					Primary causes:   
					The bridge environment and running conditions cause the ambient   
					temperature to rise above a safe operating level.   
					Possible board failures:   
					BICM   
					Possible wiring faults:   
					The thermal sensor input to backplane connector J4 pins 7 and 8 is damaged.   
					99   
					Ambient temp hot   
					Alarm   
					The Ambient temp hot alarm occurs when the ambient temperature (variable   
					Bridge ambient temp) is too high.   
					The main purpose of the alarm is to use the ambient temperature   
					measurement to detect a condition which could endanger the power bridge.   
					Primary causes:   
					The bridge environment and running conditions cause the ambient   
					temperature to rise above a safe operating level.   
					Possible board failures:   
					BICM   
					Possible wiring faults:   
					The thermal sensor input to backplane connector J4 pins 7 and 8 is damaged.   
					100 Phase A cur offset   
					101 Phase B cur offset   
					102 Phase C cur offset   
					Trip   
					Trip   
					Trip   
					The Phase A cur offset trip fault occurs when the phase A current offset   
					(variable Phs A current offset) is too large. The current offset threshold level is   
					1 percent of the rated shunt current (parameter IPN shunt size).   
					Phs A current offset is the output of an automatic current offset calculation.   
					The trip fault only occurs when the offset calculation is not active.   
					Phase A cur offset evaluates phase A current feedback information collected   
					while the power bridge is turned off, when current feedbacks should be zero.   
					It uses the information to detect power bridge and feedback circuitry problems.   
					The Phase B cur offset trip fault occurs when the phase B current offset   
					(variable Phs B current offset) is too large. The current offset threshold level is   
					1 percent of the rated shunt current (parameter IPN shunt size).   
					Phs B current offset is the output of an automatic current offset calculation.   
					The trip fault only occurs when the offset calculation is not active.   
					Phase B cur offset evaluates phase B current feedback information collected   
					while the power bridge is turned off, when current feedbacks should be zero.   
					It uses the information to detect power bridge and feedback circuitry problems.   
					The Phase C cur offset trip fault occurs when the phase C current offset   
					(variable Phs C current offset) is too large. The current offset threshold level   
					is 1 percent of the rated shunt current, represented by parameter IPN shunt   
					size.   
					Phs C current offset is the output of an automatic current offset calculation.   
					The trip fault only occurs when the offset calculation is not active.   
					Phase C cur offset evaluates phase C current feedback information collected   
					while the power bridge is turned off, when current feedbacks should be zero.   
					It uses the information to detect power bridge and feedback circuitry problems.   
					2-20 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					103 A-B voltage offset   
					Trip   
					The A-B voltage offset trip fault occurs when the A-B line-line voltage offset   
					(variable A-B, Voltage offset) is too large.   
					A-B, Voltage offset is the output of an automatic voltage offset calculation.   
					The trip fault only occurs when the offset calculation is not active.   
					A-B voltage offset evaluates A-B voltage feedback information collected while   
					the power bridge is turned off, when voltage feedbacks should be zero. It   
					uses the information to detect power bridge and feedback circuitry problems.   
					104 B-C voltage offset   
					Trip   
					The B-C voltage offset trip fault occurs when the B-C line-line voltage offset   
					(variable B-C, Voltage offset) is too large.   
					B-C, Voltage offset is the output of an automatic voltage offset calculation.   
					The trip fault only occurs when the offset calculation is not active.   
					B-C voltage offset evaluates B-C voltage feedback information collected while   
					the power bridge is turned off, when voltage feedbacks should be zero. It   
					uses the information to detect power bridge and feedback circuitry problems.   
					105 Pulse tst config bad Trip   
					The Pulse tst config bad trip fault occurs when the pulse test configuration   
					parameters are invalid and the pulse test is invoked. The purpose of the fault   
					is to prevent the pulse test from running under poorly defined conditions.   
					Primary causes:   
					One or more of the following parameters is negative: Pulse 1 on time, Mid   
					pulse off time, Pulse 2 on time, Post pulse off time.   
					106 Ckt board list fail   
					Trip   
					The Ckt board list fail trip fault occurs when the electronic board ID   
					interrogation which happens during drive initialization fails. Each circuit board   
					in the rack has an electronic ID.   
					Ckt board list fail requires a hard reset to clear.   
					Primary causes:   
					A circuit board is not seated properly in its backplane sockets.   
					The electronic ID part on a circuit board has experienced a failure.   
					107 Motor volt offs high   
					Alarm   
					The Motor volt offs high alarm occurs when the line-line voltage offset   
					measurements are invalid when the drive is started. Generally the alarm   
					occurs when the drive is stopped and quickly started again.   
					The voltage offsets are represented by variables A-B, Voltage offset and B-C,   
					Voltage offset. They are the outputs of automatic voltage offset   
					measurements. They are valid for a certain length of time after the   
					measurements are performed.   
					The voltage offset measurements are performed when the drive is started and   
					enough time has elapsed to cause the previous voltage offset measurements   
					to be invalid. However, there is an exception to this statement. The offset   
					measurements are not performed during the flux decay time, which begins   
					when the drive is stopped and continues for 8 rotor time constants.   
					When the drive is started during the flux decay time, and the previous offset   
					measurements are invalid because too much time has elapsed since they   
					were performed, the Motor volt offs high alarm occurs.   
					Related functions:   
					Line-Line Voltage Protection   
					108 DC bus voltage low Alarm   
					The DC bus voltage low alarm occurs when the DC link voltage feedback   
					(variable DC bus voltage) is too low.   
					The alarm clears when the DC link voltage feedback rises to an acceptable   
					voltage, which is the under voltage threshold plus a hysteresis voltage.   
					DC bus voltage low only occurs when the drive is stopped.   
					Possible board failures:   
					FOSA   
					DSPX   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-21   
				No. Name   
					Type Description   
					109   
					Alarm   
					Task 1 exec   
					overrun   
					The Task 1 exec overrun alarm occurs when Task 1 exceeds its allotted CPU   
					execution time. This alarm may occur during system development but should   
					not occur in the field.   
					Primary causes:   
					Task 1 contains too much functionality to complete in the specified execution   
					time.   
					Possible board failures:   
					DSPX   
					110   
					Alarm   
					Task 2 exec   
					overrun   
					The Task 2 exec overrun alarm occurs when Task 2 exceeds its allotted CPU   
					execution time. This alarm may occur during system development but should   
					not occur in the field.   
					Primary causes:   
					Task 2 contains too much functionality to complete in the specified execution   
					time.   
					Task 1 contains too much functionality. Although it completes in its specified   
					execution time, it does not allow Task 2 to run to completion.   
					Possible board failures:   
					DSPX   
					111   
					Alarm   
					Task 3 exec   
					overrun   
					The Task 3 exec overrun alarm occurs when Task 3 exceeds its allotted CPU   
					execution time. This alarm may occur during system development but should   
					not occur in the field.   
					Primary causes:   
					Task 3 contains too much functionality to complete in the specified execution   
					time.   
					Task 1 and Task 2 contain too much functionality. Although they complete in   
					their specified execution time, they do not allow Task 3 to run to completion.   
					Possible board failures:   
					DSPX   
					112 ADL msg stack fail   
					Alarm   
					The ADL msg stack fail alarm occurs when an attempt by autotune or cell test   
					to allocate or free message stack memory fails. The purpose of the alarm is to   
					indicate failure in the use of dynamic memory with asynchronous drive   
					language functionality. This alarm may occur during system development but   
					should not occur in the field.   
					Primary causes:   
					An attempt to allocate or free memory on behalf of the ADL message stack   
					failed.   
					113 Invalid board set   
					Trip   
					The Invalid board set trip fault occurs when the electronic board ID   
					interrogation which happens during initialization does not produce the   
					expected set of circuit boards. Each circuit board in the rack has an electronic   
					ID which contains board type and revision information. Each Innovation   
					Series product has an expected set of circuit boards. If any of the expected   
					boards is missing, or if incorrect boards are present, the drive cannot operate   
					properly.   
					The circuit boards that the drive has identified can be obtained by making the   
					following GE Control System Toolbox menu selections: View, Reports, Drive   
					Version and Hardware Info.   
					Primary causes:   
					A circuit board which is required for the drive to operate properly is not   
					present.   
					A circuit board which should not be used in the drive is present.   
					A circuit board is not seated properly in its backplane socket.   
					The electronic ID part on a circuit board has experienced a failure.   
					2-22 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					114 Ain 1 signal alarm   
					Alarm   
					The Ain 1 signal alarm occurs when the level of analog input number 1   
					(variable Analog input 1) is too low. The alarm level is specified by parameter   
					Analog in 1 flt lev.   
					The alarm can occur only when parameter Analog in 1 flt mode is set equal to   
					Low level alarm. The alarm is disabled for any other setting for parameter   
					Analog in 1 flt mode.   
					The main purpose of Ain 1 signal alarm is to detect a low 4-20 mA signal. The   
					low level may indicate that a signal is missing which is required for the drive to   
					operate properly.   
					Primary causes:   
					The analog input number 1 signal source is absent or unhealthy.   
					Possible configuration faults:   
					The analog input 1 alarm level, represented by parameter Analog in 1 flt lev, is   
					set incorrectly.   
					The analog input number 1 gain, represented by parameter Analog in 1 gain,   
					is set incorrectly.   
					The analog input number 1 offset, represented by parameter Analog in 1   
					offset, is set incorrectly.   
					The analog input number in 1 flt mode, represented by parameter Analog in 1   
					flt mode, is set incorrectly.   
					Possible wiring faults:   
					The connections between the analog signal source and ATBA terminal board   
					locations 38 (AI1P) and 40 (AI1N) are missing or damaged.   
					115 Ain 1 signal trip   
					Trip   
					The Ain 1 signal trip fault occurs when the level of analog input number 1   
					(variable Analog input 1) is too low. The trip fault level is specified by   
					parameter Analog in 1 flt lev.   
					The trip fault can occur only when parameter Analog in 1 flt mode is set equal   
					to Low level trip. The trip fault is disabled for any other setting for parameter   
					Analog in 1 flt mode.   
					The main purpose of Ain 1 signal trip is to detect a low 4-20 mA signal. The   
					low level may indicate that a signal is missing which is required for the drive to   
					operate properly.   
					Primary causes:   
					The analog input number 1 signal source is absent or unhealthy.   
					Possible configuration faults:   
					The analog input 1 trip fault level, represented by parameter Analog in 1 flt lev,   
					is set incorrectly.   
					The analog input number 1 gain, represented by parameter Analog in 1 gain,   
					is set incorrectly.   
					The analog input number 1 offset, represented by parameter Analog in 1   
					offset, is set incorrectly.   
					The analog input number in 1 flt mode, represented by parameter Analog in 1   
					flt mode, is set incorrectly.   
					Possible wiring faults:   
					The connections between the analog signal source and ATBA terminal board   
					locations 38 (AI1P) and 40 (AI1N) are missing or damaged.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-23   
				No. Name   
					Type Description   
					116 Ain 2 signal alarm   
					Alarm   
					The Ain 2 signal alarm occurs when the level of analog input number 2   
					(variable Analog input 2) is too low. The alarm level is specified by parameter   
					Analog in 2 flt lev.   
					The alarm can occur only when parameter Analog in 2 flt mode is set equal to   
					Low level alarm. The fault is disabled for any other setting for parameter   
					Analog in 2 flt mode.   
					The main purpose of Ain 2 signal alarm is to detect a low 4-20 mA signal. The   
					low level may indicate that a signal is missing which is required for the drive to   
					operate properly.   
					Primary causes:   
					The analog input number 2 signal source is absent or unhealthy.   
					Possible configuration faults:   
					The analog input 2 alarm level, represented by parameter Analog in 2 flt lev, is   
					set incorrectly.   
					The analog input number 2 gain, represented by parameter Analog in 2 gain,   
					is set incorrectly.   
					The analog input number 2 offset, represented by parameter Analog in 2   
					offset, is set incorrectly.   
					The analog input number in 2 flt mode, represented by parameter Analog in 2   
					flt mode, is set incorrectly.   
					Possible wiring faults:   
					The connections between the analog signal source and ATBA terminal board   
					locations 44 (AI2P) and 46 (AI2N) are missing or damaged.   
					117 Ain 2 signal trip   
					Trip   
					The Ain 2 signal trip fault occurs when the level of analog input number 2   
					(variable Analog input 2) is too low. The trip fault level is specified by   
					parameter Analog in 2 flt lev.   
					The trip fault can occur only when parameter Analog in 2 flt mode is set equal   
					to Low level trip. The trip fault is disabled for any other setting for parameter   
					Analog in 2 flt mode.   
					The main purpose of Ain 2 signal trip is to detect a low 4-20 mA signal. The   
					low level may indicate that a signal is missing which is required for the drive to   
					operate properly.   
					Primary causes:   
					The analog input number 2 signal source is absent or unhealthy.   
					Possible configuration faults:   
					The analog input 2 trip fault level, represented by parameter Analog in 2 flt lev,   
					is set incorrectly.   
					The analog input number 2 gain, represented by parameter Analog in 2 gain,   
					is set incorrectly.   
					The analog input number 2 offset, represented by parameter Analog in 2   
					offset, is set incorrectly.   
					The analog input number in 2 flt mode, represented by parameter Analog in 2   
					flt mode, is set incorrectly.   
					Possible wiring faults:   
					The connections between the analog signal source and ATBA terminal board   
					locations 44 (AI2P) and 46 (AI2N) are missing or damaged.   
					118 Illegal req for sby   
					Alarm   
					The Illegal req for sby alarm occurs when a Standby command is issued and a   
					trip fault is present in the drive. The alarm may also occur when a Standby   
					command is issued at the same time a diagnostic test (cell test, pulse test,   
					autotune) is active.   
					Primary causes:   
					The external application layer issues an inappropriate standby request.   
					2-24 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					Alarm   
					119   
					Start permissive   
					bad   
					The Start permissive bad alarm occurs when the start permissive circuit is   
					open and the drive is stopped. The state of the start permissive circuit is   
					determined by the value of the variable which parameter Start permissive sel   
					selects. The alarm can be disabled by setting parameter Start permissive sel   
					equal to Unused.   
					Related functions:   
					Sequencer Permissives   
					121 DBS1 IGDM card flt Trip   
					The DBS1 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					122 DBS2 IGDM card flt Trip   
					The DBS2 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-25   
				No. Name   
					Type Description   
					Trip   
					123 AS1 IGDM card flt   
					The AS1 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					124 AS2 IGDM card flt   
					Trip   
					The AS2 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					2-26 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					Trip   
					125 AS3 IGDM card flt   
					The AS3 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					126 AS4 IGDM card flt   
					Trip   
					The AS4 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-27   
				No. Name   
					Type Description   
					Trip   
					127 BS1 IGDM card flt   
					The BS1 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					128 BS2 IGDM card flt   
					Trip   
					The BS2 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					2-28 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					Trip   
					129 BS3 IGDM card flt   
					The BS3 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					130 BS4 IGDM card flt   
					Trip   
					The BS4 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-29   
				No. Name   
					Type Description   
					Trip   
					131 CS1 IGDM card flt   
					The CS1 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					132 CS2 IGDM card flt   
					Trip   
					The CS2 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					2-30 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					Trip   
					133 CS3 IGDM card flt   
					The CS3 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					134 CS4 IGDM card flt   
					Trip   
					The CS4 IGDM card flt trip fault is hardware generated. The trip fault occurs   
					when the bridge control has lost communication with the indicated IGDM   
					module. This communication occurs via fiber optic cable between the FOSA   
					and the IGDM. During normal operation the IGDM transmits continuous light   
					back to FOSA. Any loss of this signal triggers this trip fault.   
					Several unrelated situations can cause the light to stop transmitting. Run the   
					Cell Test Wizard to identify any failed devices.   
					Primary causes:   
					CPFP power supply failure   
					IGDM failure   
					A desat fault on the indicated IGBT was detected.   
					Possible board failures:   
					IGDM   
					CPFP   
					FOSA   
					BICM   
					Possible wiring faults:   
					Fiber optic connection between FOSA and IGDM   
					Power distribution wiring from CPFP.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-31   
				No. Name   
					Type Description   
					135 AC line transient   
					Alarm   
					The AC line transient alarm occurs as a result of significant phase lock loop   
					error or significant phase imbalance.   
					A phase imbalance signal is calculated by subtracting a control calculated   
					threshold from a filtered signal which is formed by filtering the sum of two   
					signals. One of these signals is the phase lock loop error and the other is the   
					error between the demodulated real component of line voltage and the   
					measured magnitude of the line.   
					The calculated threshold phase imbalance level which is computed by the   
					control is based on the magnitude of the input line voltage. This calculated   
					phase imbalance threshold represents a phase imbalance of about 18% or a   
					phase lock loop error of about 6.7 degrees. The phase imbalance signal   
					which is a result of the previously mentioned subtraction is equal to about   
					18% imbalance when it becomes positive.   
					The phase imbalance signal feeds an integrator designed to cause the AC line   
					transient alarm when the threshold has been exceeded for a very short time.   
					That amount of time is dependent upon the amount of the phase imbalance,   
					but the alarm will occur eventually if the imbalance signal remains positive.   
					Primary causes:   
					AC line disturbances.   
					Transient phase imbalances.   
					Weak control of frequency on diesel generator sets or gas turbine generator   
					sets.   
					Very fast voltage magnitude changes.   
					Damaged reactor or transformer   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					2-32 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					Trip   
					136 AC line watchdog   
					The AC line watchdog trip fault will occur when the AC line transient alarm   
					persists for about one second. Both the trip fault and the alarm are a result of   
					significant phase lock loop error or significant phase imbalance.   
					A phase imbalance signal is calculated by subtracting a control calculated   
					threshold from a filtered signal which is formed by filtering the sum of two   
					signals. One of these signals is the phase lock loop error and the other is the   
					error between the demodulated real component of line voltage and the   
					measured magnitude of the line.   
					The calculated threshold phase imbalance level which is computed by the   
					control is based on the magnitude of the input line voltage. This calculated   
					phase imbalance threshold represents a phase imbalance of about 18% or a   
					phase lock loop error of about 6.7 degrees. The phase imbalance signal   
					which is a result of the previously mentioned subtraction is equal to about   
					18% imbalance when it becomes positive.   
					The phase imbalance signal feeds an integrator designed to cause the AC line   
					transient alarm when the threshold has been exceeded for a very short time.   
					That amount of time is dependent upon the amount of the phase imbalance,   
					but the alarm will occur eventually if the imbalance signal remains positive. If   
					the alarm persists continuously for about one second, the AC line watchdog   
					trip fault will occur.   
					Primary causes:   
					AC line disturbances.   
					Transient phase imbalances.   
					Weak control of frequency on diesel generator sets or gas turbine generator   
					sets.   
					Very fast voltage magnitude changes.   
					Damaged reactor or transformer   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					137 AC line rev phs seq Trip   
					The AC line rev phs seq trip fault occurs when the control senses that the   
					rotation of the AC line is opposite of what is expected. This condition is   
					checked only one time after the control is powered up. When the phase lock   
					loop locks for the first time, just after the charging sequence has begun, the   
					sign of PLL frequency is checked against the expected sign. The expected   
					sign is determined by the setting of Phase rotation req. If Forward sequence   
					is selected, the sign of PLL frequency is expected to be positive, otherwise, it   
					must be negative. If the expected sign is not found, the trip fault is given. AC   
					line rev phs seq requires a hard reset to clear.   
					Before changing Phase rotation req, review the rotation of any AC cooling   
					pumps or blowers in the drive. Incorrect phase sequence can lead to   
					ineffective air or water flow in the cooling system.   
					Primary causes:   
					Control senses wrong phase sequence.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					Possible wiring faults:   
					Main AC input lines to source are not in correct phase sequence.   
					Sensing wires to FOSA are in wrong sequence.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-33   
				No. Name   
					Type Description   
					Trip   
					138 AC line vfb offset   
					The AC line vfb offset trip fault occurs when the voltage feedback offset being   
					calculated for line voltage feedbacks is above the allowable threshold. The   
					system integrates the voltages seen on the AC input terminals. The results of   
					this integration should be near zero since the input waveform is a sine wave.   
					If the input line-line voltages integrate to a non-zero value above a predefined   
					threshold this trip fault is generated.   
					Primary causes:   
					Bad VCO Circuit.   
					Incorrect sensor wiring.   
					Large DC current component through transformer.   
					Possible board failures:   
					VATF-SRC   
					FOSA   
					BICM   
					DSPX   
					Possible wiring faults:   
					Check wiring of VATF-SRC sensor inputs to phase leg.   
					139 AC line failed   
					Trip   
					The AC line failed trip fault occurs when the phase lock loop fails to   
					synchronize during the start up sequence.   
					Primary causes:   
					The AC line is missing.   
					There is a large AC line imbalance.   
					There is a blown fuse.   
					140 Xfrmr over temp   
					141 Xfrmr temp hot   
					142 Motor over temp   
					Trip   
					The Xfrmr over temp trip occurs when the transformer over temperature circuit   
					is open. The control input which points to the over temperature circuit is   
					selected by parameter Xfrmr OT fault sel.   
					Xfrmr over temp can be disabled by setting parameter Xfrmr OT fault sel equal   
					to Unused.   
					Alarm   
					Trip   
					The Xfrmr temp hot alarm occurs when the transformer over temperature   
					circuit is open. The control input which points to the over temperature circuit is   
					selected by parameter Xfrmr OT fault sel.   
					Xfrmr temp hot can be disabled by setting parameter Xfrmr OT fault sel equal   
					to Unused.   
					The Motor over temp trip fault occurs when the motor overtemperature circuit   
					is open. The state of the motor overtemperature circuit is selected by   
					parameter Motor OT fault sel.   
					Motor over temp can be disabled by setting parameter Motor OT fault sel   
					equal to Unused.   
					Related functions:   
					Motor Overtemperature Detection   
					143 Motor temp hot   
					Alarm   
					The Motor temp hot trip fault occurs when the motor overtemperature circuit is   
					open. The state of the motor overtemperature circuit is selected by parameter   
					Motor OT fault sel.   
					Motor temp hot can be disabled by setting parameter Motor OT fault sel equal   
					to Unused.   
					Related functions:   
					Motor Overtemperature Detection   
					144 Unrecognized IPN   
					Trip   
					The Unrecognized IPN trip fault occurs when the specified Intelligent Part   
					Number (IPN) is not a valid combination of fields for the Innovation Series   
					product. The IPN should correspond to the drive nameplate.   
					Unrecognized IPN requires a hard reset to clear.   
					2-34 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					145   
					Trip   
					Customer use NC   
					flt   
					The Customer use NC flt trip fault occurs when the customer normally closed   
					circuit is open. The state of the normally closed circuit is selected by   
					parameter User NC fault sel.   
					146 Customer use NC   
					Alarm   
					Trip   
					The Customer use NC alm alarm occurs when the customer normally closed   
					circuit is open. The state of the normally closed circuit is selected by   
					parameter User NC fault sel.   
					alm   
					147   
					148   
					Customer use NO   
					flt   
					The Customer use NO flt trip fault occurs when the customer normally open   
					circuit is closed. The state of the normally open circuit is selected by   
					parameter User NO fault sel.   
					Alarm   
					Trip   
					Customer use NO   
					alm   
					The Customer use NO alm alarm occurs when the customer normally open   
					circuit is closed. The state of the normally open circuit is selected by   
					parameter User NO fault sel.   
					149 Sat curve data bad   
					The Sat curve data bad trip fault occurs when the flux saturation curve is not   
					monotonic.   
					Primary causes:   
					The saturation curve data entered by the operator is bad.   
					The saturation curve data calculated by autotune is bad.   
					Possible configuration faults:   
					One or more of the saturation curve parameters is bad. The saturation curve   
					parameters are Flux curve amps 1, Flux curve amps 2, Flux curve amps 3,   
					Flux curve amps 4, Flux curve amps 5, Flux curve voltage 1, Flux curve   
					voltage 2, Flux curve voltage 3, Flux curve voltage 4, and Flux curve voltage 5.   
					150 Rated flux data bad Trip   
					The Rated flux data bad trip fault occurs when the motor control calculation of   
					rated flux (variable 100% Flux) does not converge to a stable value.   
					151 Leakage curve bad Trip   
					The Leakage curve bad trip fault occurs when the leakage flux curve is not   
					monotonic (i.e. Point 1 < point 2 < point 3 < point 4 < point 5).   
					Primary causes:   
					The calculated leakage curve has been derived from bad motor reactance   
					data.   
					The leakage curve data entered by the operator is bad.   
					The leakage curve data calculated by autotune is bad.   
					Possible configuration faults:   
					When the leakage curve is not entered specifically point-by-point (see below)   
					one is calculated from Starting react Xst, Magnetizing react Xm, Stator lkg   
					react X1, and Rotor lkg react X2. The relationship between these parameters   
					should be: (Rotor lkg react X2 || Magnetizing react Xm) + Stator lkg react X1   
					> Starting react Xst. If Motor reac parms bad fault is also present, this is the   
					likely cause.   
					When the leakage curve is not entered specifically point-by-point, one or more   
					of the leakage curve parameters is bad. The leakage curve parameters are   
					Lkg flux current 1, Lkg flux current 2, Lkg flux current 3, Lkg flux current 4, Lkg   
					flux current 5, Lkg flux voltage 1, Lkg flux voltage 2, Lkg flux voltage 3, Lkg flux   
					voltage 4, and Lkg flux voltage 5. If the leakage parameters are not set, the   
					leakage curve is determined as above, or as the results of autotune.   
					152 Invalid Time Base   
					Trip   
					The Invalid Time Base trip fault occurs when the execution time base is   
					invalid. Parameter Exec time/Chop freq contains valid choices for the time   
					base.   
					Invalid Time Base requires a hard reset to clear.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-35   
				No. Name   
					Type Description   
					153 DSPx Watchdog   
					Trip   
					The DSPx Watchdog trip fault occurs when the DSPX EPLD stops seeing a   
					Locke watchdog toggle bit from the processor. A hard reset occurs and the fault is   
					d 
					declared at initialization.   
					DSPx Watchdog requires a hard reset to clear.   
					Possible board failures:   
					DSPX   
					154 Reverse rotation   
					155 Failure to rotate   
					156 Loss of spd control   
					157 Bic Watchdog   
					Trip   
					Trip   
					Alarm   
					Trip   
					The Reverse rotation trip fault occurs when the motor shaft is rotating opposite   
					to the requested direction.   
					Related functions:   
					Speed Control Fault Check   
					The Failure to rotate trip fault occurs when speed regulator error grows large   
					while the speed feedback is small.   
					Related functions:   
					Speed Control Fault Check   
					The Loss of spd control trip fault occurs when the speed regulator error is too   
					large.   
					Related functions:   
					Speed Control Fault Check   
					The Bic Watchdog trip fault occurs when the BICM stops seeing a watchdog   
					toggle bit from the DSPX. When the drive is running, BICM monitors a toggle   
					bit being manipulated by DSPX. If DSPX does not toggle the bit on BICM   
					within a predefined time interval, the BICM declares a fault and disables the   
					bridge. This indicates that the processor cannot communicate reliably with the   
					bridge interface card.   
					Bic Watchdog requires a hard reset to clear.   
					Possible configuration faults:   
					The connected drive is a simulator but Simulate mode act is equal to False.   
					Set Simulate mode equal to Yes to correct the problem.   
					Possible board failures:   
					BICM   
					DSPX   
					CABP (backplane)   
					158 Bic watchdog echo   
					Trip   
					The Bic watchdog echo trip fault occurs when the DSPX stops seeing the echo   
					of the watchdog toggle bit that it writes to the BICM. This indicates that the   
					processor cannot communicate reliably with the bridge interface card.   
					Primary Causes:   
					Bent backplane connector pins or poorly seated cards.   
					Possible board failures:   
					BICM   
					DSPX   
					CABP (backplane)   
					160 LAN trip request   
					Trip   
					The LAN trip request trip fault occurs when a request for a trip fault is received   
					from the LAN by assertion of the reference Boolean signal Trip request, lan.   
					161 LAN alarm request   
					Alarm   
					The LAN alarm request alarm occurs when a request for an alarm is received   
					from the LAN by assertion of the reference Boolean signal Alarm request, lan.   
					2-36 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				No. Name   
					Type Description   
					162   
					Alarm   
					LAN watchdog   
					alarm   
					The LAN watchdog alarm occurs when the connection between DSPX and the   
					Application/LAN interface becomes invalid. This includes one of the following   
					conditions, depending upon the selection of Network interface:   
					The Application/LAN interface Dual-Port RAM watchdog stops.   
					The ISBus frames stop.   
					The alarm is declared after the condition persists for several hundred   
					microseconds.   
					163   
					Alarm   
					Restrictd fcn   
					enabld   
					The Restrictd fcn enabld alarm occurs when the selected execution time base   
					in the parameter Exec time/Chop freq restricts certain drive functionality due to   
					timing limitations, or the ISBus network is selected by the Network interface   
					parameter and the DSPX hardware does not support ISBus. Certain functions   
					that are presently enabled will not run.   
					Possible configuration faults:   
					Execution time base is too low. Select alternate time base in parameter Exec   
					time/Chop freq.   
					LAN is enabled, but will not operate. Disable LAN by setting parameter   
					Network interface to None.   
					ISBus is selected, but will not operate. Deselect ISBus by setting parameter   
					Network interface, or replace the DSPX HIA with a DSPX H1B.   
					164 LAN heartbeat trip   
					Trip   
					The LAN heartbeat trip occurs when all of the following conditions are present:   
					Non-zero value is entered in Parameter LAN heartbeat time.   
					The signal (Heartbeat ref, lan) fails to transition within in that time.   
					The trip behavior is enabled by Parameter LAN trips inhibit.   
					The LAN connection ok condition was previously detected.   
					165   
					166   
					Alarm   
					LAN heartbeat   
					alarm   
					The LAN heartbeat alarm occurs when all of the following conditions are   
					present:   
					Non-zero value is entered in Parameter LAN heartbeat time.   
					The signal (Heartbeat ref, lan) fails to transition within in that time.   
					Either the trip behavior is inhibited by Parameter LAN trips inhibit, or the trip   
					behavior is enabled but the LAN connection ok condition was not previously   
					detected.   
					Trip   
					Requird Parm   
					Missing   
					The Requird Parm Missing trip fault occurs when one of the required   
					parameters either is not entered, “No Value” or has a value of zero. Check the   
					following values, which can be found in the commissioning wizard.   
					Primary causes:   
					Motor rated voltage, Not entered   
					Motor rated freq, Not entered   
					Motor rated current, Not entered   
					Motor rated rpm, Not entered   
					Motor rated power, Not entered   
					Motor service factor, Not entered   
					167 Version mismatch   
					Trip   
					The Version mismatch trip fault occurs at initialization when the drive pattern   
					detects a product or version mismatch with the parameters stored in non-   
					volatile RAM. Download parameters to fix.   
					168 System ISBus error Alarm   
					The System ISBus error alarm occurs when an ISBus fault is detected in the   
					DSPX control. The variable Sys ISBus error reg contains the bit-coded value   
					of the last ISBus fault detected; each bit indicates a particular ISBus fault seen   
					by the control. The variable Sys ISBus error cnt increments upon fault   
					detection.   
					Record the value of Sys ISBus error reg to assist factory troubleshooting   
					efforts. Monitor the progression of Sys ISBus error cnt to obtain an indication   
					of the rate of occurrence of fault conditions.   
					Transient occurrence of this alarm upon initialization of the interface is   
					expected.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 2 Faults and Troubleshooting • 2-37   
				No. Name   
					Type Description   
					Alarm   
					169 Frame PLL not OK   
					The Frame PLL not OK alarm occurs when phase-lock between the DSPX   
					control and the System ISBus or (local ACL) is not assured. Detection of the   
					fault is enabled when the parameter Network interface is configured to select   
					an interface for which synchronized operation is supported. The presence of   
					this alarm indicates that data coherency is compromised.   
					Verify the integrity of IsBus connections and configurations. If this alarm   
					persists in the absence of any other interface faults, then verify that LAN frame   
					time is consistent with that of the host, and confirm the absence of overrides,   
					particularly regarding the Frame phaselock loop and DSPX timebase.   
					Transient occurrence of this alarm upon initialization of the interface is   
					expected.   
					2-38 • Chapter 2 Faults and Troubleshooting   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Chapter 3 Paramters/Functions   
					Introduction   
					Application firmware consists of coordinated blocks of code called functions. Each   
					Chapter 4 describes wizards.   
					function performs a specific task in controlling the drive. Parameters are adjustable   
					values within a function that allow you to configure and adjust the drive behavior.   
					Parameters can be set and modified using wizards within the keypad and the optional   
					toolbox.   
					The following is a list of the drive parameters and functionsIt is organized as   
					follows:   
					Section   
					Page   
					Introduction ........................................................................................................ 3-1   
					Diagnostic and Utility Functions ......................................................................... 3-4   
					Diagnostic and Utility Overview................................................................... 3-4   
					Capture Buffer ............................................................................................. 3-4   
					General Purpose Constants ..........................................................................3-10   
					General Purpose Filters ...............................................................................3-11   
					Oscillator ....................................................................................................3-12   
					Position Feedback .......................................................................................3-13   
					Predefined Constants...................................................................................3-14   
					Signal Level Detector (SLD) .......................................................................3-15   
					Simulator ....................................................................................................3-18   
					Control Diagnostic Variables.......................................................................3-19   
					Line Simulator ............................................................................................3-19   
					Drive Configuration Functions ...........................................................................3-20   
					Intelligent Part Number (IPN)......................................................................3-20   
					Primary Motor & Application Data..............................................................3-21   
					General Setup Functions.....................................................................................3-24   
					Keypad Overview........................................................................................3-24   
					Keypad Contrast Adjustment.......................................................................3-25   
					Keypad Meter Configuration .......................................................................3-25   
					Keypad Security Configuration....................................................................3-27   
					Language and Units Presentation.................................................................3-28   
					Language Display........................................................................................3-29   
					I/O Functions.....................................................................................................3-30   
					Analog and Digital I/O Testing....................................................................3-30   
					Analog Inputs/Outputs and Mapping............................................................3-32   
					Digital Inputs/Outputs and Mapping ............................................................3-33   
					LAN Functions ..................................................................................................3-34   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-1   
				LAN Overview............................................................................................3-34   
					Frame Phaselock Loop ................................................................................3-34   
					LAN Configuration and Health....................................................................3-35   
					LAN Signal Map.........................................................................................3-38   
					Motor Control Functions ....................................................................................3-44   
					Motor Control Overview .............................................................................3-44   
					Flux Curve ..................................................................................................3-45   
					Leakage Inductance Curve...........................................................................3-46   
					Line Transfer ..............................................................................................3-46   
					Motor Equivalent Circuit.............................................................................3-48   
					Motor Temperature Estimation ....................................................................3-49   
					Power Dip Protection ..................................................................................3-49   
					Tach Loss Detection....................................................................................3-50   
					Protective Functions...........................................................................................3-52   
					Custom User Faults.....................................................................................3-52   
					DC Link Protection .....................................................................................3-52   
					Ground Fault Protection (Fast).....................................................................3-54   
					Hardware Fault Strings................................................................................3-55   
					Heatsink Thermal Protection .......................................................................3-56   
					Line-Line Voltage Protection.......................................................................3-58   
					Motor Overtemperature Detection ...............................................................3-59   
					Phase Current Protection .............................................................................3-60   
					Timed Overcurrent Detection ......................................................................3-61   
					Transformer Overtemperature Detection......................................................3-65   
					Motor Ground Protection.............................................................................3-66   
					Phase Imbalance Monitor ............................................................................3-68   
					Line Monitor...............................................................................................3-70   
					Phase Lock Loop.........................................................................................3-72   
					Sequencer Functions ..........................................................................................3-74   
					Sequencer Overview....................................................................................3-74   
					Fault Reset Logic ........................................................................................3-74   
					Sequencer Permissives.................................................................................3-76   
					Stopping Commands and Modes..................................................................3-78   
					Sequencer Commands .................................................................................3-82   
					Sequencer Status .........................................................................................3-85   
					Main Contactor Configuration .....................................................................3-87   
					Speed Reference Functions.................................................................................3-89   
					Critical Speed Avoidance ............................................................................3-89   
					Local Speed Reference ................................................................................3-90   
					Minimum Speed Limit ................................................................................3-91   
					Remote Speed Reference.............................................................................3-92   
					Speed Reference Generation........................................................................3-93   
					Speed Reference Ramp................................................................................3-94   
					Speed Reference Reverse.............................................................................3-97   
					Speed/Torque Control Functions ........................................................................3-99   
					Droop..........................................................................................................3-99   
					Motor Control Interface.............................................................................3-100   
					Speed Control Fault Check........................................................................3-103   
					Speed Feedback Calculation ......................................................................3-105   
					Speed/Torque Overview ............................................................................3-106   
					Speed/Torque Regulator ............................................................................3-107   
					System Data Parameters...................................................................................3-112   
					Exec time/Chop freq..................................................................................3-112   
					Motor ctrl alg sel.......................................................................................3-112   
					Motor efficiency........................................................................................3-113   
					Motor service factor ..................................................................................3-114   
					3-2 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Motor winding cfg.....................................................................................3-114   
					Preflux Forcing .........................................................................................3-114   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-3   
				Diagnostic and Utility Functions   
					Diagnostic and Utility Overview   
					The Innovation Series products contain a number of diagnostic functions. More   
					information is available for the following topics.   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Capture Buffer   
					General Purpose Constants   
					General Purpose Filters   
					Oscillator   
					Position Feedback   
					Predefined Constants   
					Signal Level Detector (SLD)   
					Simulator   
					Capture Buffer   
					The Innovation Series capture buffer is used to collect coherent data at a specified   
					rate in the drive. The capture buffer is circular, and will collect a fixed number of   
					samples of each data channel before overwriting the oldest data. The capture buffer   
					can be triggered on any available variable signal in the drive by using a Boolean   
					trigger mode or comparison to a value. The capture buffer will also trigger on a Trip   
					fault. It is useful for capturing drive variables for troubleshooting field problems and   
					capturing specific drive events. The Trend Recorder can display the capture buffer   
					output.   
					Function Inputs   
					The following table specifies the input parameters to the Capture Buffer function.   
					Parameter   
					Description   
					Capture ch1 select   
					Capture ch2 select   
					Capture ch3 select   
					Selects capture buffer channel #1 variable.   
					Selects capture buffer channel #2 variable.   
					Selects capture buffer channel #3 variable.   
					Channels 3 & 4 are active when Capture buff   
					config is set to either 4 channels enabled or 8   
					channels enabled.   
					Capture ch4 select   
					Capture ch5 select   
					Selects capture buffer channel #4 variable.   
					Selects capture buffer channel #5 variable.   
					Channels 5, 6, 7, & 8 are active when Capture   
					buff config is set to 8 channels enabled.   
					Capture ch6 select   
					Capture ch7 select   
					Capture ch8 select   
					Selects capture buffer channel #6 variable.   
					Selects capture buffer channel #7 variable.   
					Selects capture buffer channel #8 variable.   
					3-4 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				The following variable is also an input to the Capture Buffer function.   
					Variable   
					Description   
					Capture buffer ready   
					Enables or disables the capture buffer data   
					collection.   
					Function Outputs   
					The following table specifies the status variables of the Capture Buffer function.   
					Variable   
					Description   
					Capture buffer stat   
					Indicates the status of the capture buffer. Possible   
					values are:   
					Complete - Capture buffer has completed its   
					collection of data and is disabled.   
					Wait for trigger - The capture buffer is waiting for the   
					evaluation of the trigger condition to go True.   
					Post trigger capt – Capture buffer has been triggered   
					and is collecting post trigger data.   
					Capture triggered   
					Indicates if the capture buffer has been triggered.   
					True/False   
					Number of channels   
					Indicates the number of channels that the capture   
					buffer is configured to collect based on the setting of   
					Capture buff config.   
					Capture buffer depth   
					Capture samp period   
					Total capture time   
					Indicates the depth (i.e. number of samples) of the   
					capture buffer. Capture buffer depth is inversely   
					proportional to the number of channels collected.   
					Indicates the interval at which the capture buffer   
					collects data based on the values of the parameters   
					Capture period and Capture period gain. Seconds   
					Indicates the total time that a full buffer would collect   
					based on the values of Capture buffer depth,   
					Capture period, and Capture period gain.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-5   
				Function Configuration   
					The following table specifies the parameters that configure the size and execution   
					rate of the capture buffer.   
					Parameter   
					Description   
					Capture buff config   
					Specifies the number of channels to collect. The depth   
					of the capture buffer is inversely proportional to the   
					number of channels collected. Possible values are:   
					2 channels enabled   
					4 channels enabled   
					8 channels enabled   
					Note Whenever this parameter is modified, the   
					capture buffer must be re-enabled to collect data with   
					the new channel configuration.   
					Capture period   
					Determines the rate at which the capture buffer collects   
					data. Each rate in the enumeration list is based on a   
					particular execution rate in the processor. Actual   
					execution rates vary between each Innovation Series   
					product. Possible values are:   
					Disable - Disables the capture buffer from collecting   
					data.   
					Task 1 rate - Collects data at the fastest execution rate   
					of the processor.   
					Task 2 rate - Collects data at n times slower than Task   
					1 rate. (n Task 1’s are executed every 1 Task 2).   
					Task 3 rate - Collects data at m times slower than Task   
					2 rate. (m Task 2’s are executed every 1 Task 3).   
					Note Whenever this parameter is modified, the   
					capture buffer must be re-enabled to collect data at the   
					new rate.   
					Capture period gain   
					Cap re-enable delay   
					Increases the collection period of the capture buffer   
					(data is collected at a slower rate). For an integer   
					value, n (>1), the capture buffer would collect data   
					every nth execution of the Capture period.   
					Controls an auto re-enable function for the capture   
					buffer. This parameter sets the delay from when the   
					capture buffer has completed its collection to when the   
					capture buffer is re-enabled automatically. Minutes.   
					The capture buffer will only re-enable when the drive is   
					not stopped (Stopped is False). If Cap re-enable delay   
					expires when the drive is stopped, the capture buffer   
					will not re-enable until the drive is running again.   
					Note A value of –1 disables the auto re-enable   
					function.   
					3-6 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				The following table specifies the parameters that configure the capture buffer trigger   
					control. The capture buffer will also automatically trigger on the rising edge of Trip   
					fault active.   
					Parameter   
					Description   
					Capture pre trigger   
					Specifies the portion of the capture buffer that will be   
					collected before the trigger occurs. Percent.   
					Capture trig select   
					Selects capture buffer trigger variable. The capture   
					buffer will also automatically trigger on the rising edge   
					of Trip fault active.   
					Capture trigger mode   
					Specifies the type of comparison against the variable   
					selected in Capture trig select. Possible values are:   
					Boolean - Triggers when variable is a 1. Variable in   
					Capture trig select must be of Boolean type.   
					Inverted boolean - Triggers when variable is a 0.   
					Variable in Capture trig select must be of Boolean   
					type.   
					Equal to level - Triggers when variable is equal to   
					value in Capture trig level.   
					Not equal to level - Triggers when variable is not   
					equal to value in Capture trig level.   
					Greater than level - Triggers when variable is greater   
					than value in Capture trig level.   
					Less than level - Triggers when variable is equal to   
					value in Capture trig level.   
					Capture trigger type   
					Specifies the behavior of the configurable trigger.   
					Possible values are:   
					Level Trigger - Will trigger when the comparison   
					specified by Capture trigger mode has been satisfied.   
					If the trigger condition is satisfied when the capture   
					buffer is enabled, it will trigger immediately and collect   
					post-trigger data.   
					Edge Trigger - Will trigger on the rising edge of the   
					trigger condition specified by Capture trigger mode.   
					Capture trig level   
					Specifies the threshold level for level-based trigger   
					comparisons.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-7   
				Function description   
					The capture buffer can be accessed from the Trend Recorder in the Control System   
					Toolbox. To enable the Trend Recorder:   
					• 
					From the View menu, select Trend Recorder OR select the Trend Recorder   
					button on the toolbar:   
					. 
					To enable the Innovation Series capture buffer from the Trend Recorder:   
					1. From the Edit menu, select Configure OR select the Configure button from the   
					Trend Recorder toolbar:   
					2. Select the Block Collected tab on the Trend Recorder Configuration dialog box   
					and click OK.   
					This enables the Upload   
					and Edit Block   
					buttons on the Trend   
					Recorder toolbar.   
					3. Select the Edit Block button from the toolbar, which brings up a block diagram   
					that allows you to configure the capture buffer parameters described in the   
					Function Input and Function Configuration sections. All of the parameter   
					values must be sent to the drive for the capture buffer to work correctly.   
					4. Go back to the Trend Recorder and select the Record   
					button to enable the   
					capture buffer. The toolbox status bar should change from a “Stopped”   
					indicationto a waiting indication, as follows:   
					This indicates that the capture buffer is collecting data and waiting for the trigger.   
					To upload the capture buffer data into the Trend Recorder, select the Upload button   
					from the Trend Recorder toolbar.   
					3-8 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Capture Buffer Compatible Behavior   
					To view more than 4 channels or more than 512 samples, the Capture Buffer   
					function should be used with a GE Control System Toolbox with a release of at least   
					V6.1. Toolbox version prior to the V6.1 release can handle a maximum capture   
					buffer size of 4 channels x 512 samples.   
					The capture buffer will present the collected data in a backward compatible format if   
					used in conjunction with an older Toolbox release, however, because the capture   
					buffer size has increased, only a sub-set of the data will be presented when viewed   
					with an older Toolbox.   
					Related diagrams   
					• 
					Capture Buffer Configuration (Capture)   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-9   
				General Purpose Constants   
					Each Innovation Series product provides three general purpose constants. The   
					general purpose constants allow users to place constant values in device variables.   
					The general purpose constants are particularly useful in configuring diagnostic   
					functions.   
					Function inputs   
					The following table specifies the input parameters of the General Purpose Constants   
					function.   
					Parameter   
					Description   
					GP Constant 1   
					GP Constant 2   
					GP Constant 3   
					User defined constant 1   
					User defined constant 2   
					User defined constant 3   
					Function outputs   
					The following table specifies the output variables of the General Purpose Constants   
					function.   
					Variable   
					Description   
					GP Constant 1   
					GP Constant 2   
					GP Constant 3   
					User defined constant 1   
					User defined constant 2   
					User defined constant 3   
					Function description   
					The General Purpose Constants function sets the general purpose constant output   
					variables equal to the general purpose constant input parameters:   
					GP Constant 1 = GP Constant 1   
					GP Constant 2 = GP Constant 2   
					GP Constant 3 = GP Constant 3   
					The units of the general purpose constants are determined by their use. For example,   
					if one of the constants is used as a comparison level in a diagnostic function such as   
					an SLD, the implied units of the constant are the internal control units of the signal   
					against which the comparison is made. The units of the general purpose constant are   
					not necessarily the display units of the comparison signal. For more information on   
					the difference between display units and internal control units, see the Language and   
					Units Presentation function help.   
					Related diagrams   
					• 
					Diagnostic & Utility Functions (Diag_Util)   
					3-10 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				General Purpose Filters   
					Each Innovation Series product contains four general purpose filters. The general   
					purpose filters allow users to filter signals with a specified bandwidth.   
					Function inputs   
					The following table specifies the input parameters of the General Purpose Filters   
					function.   
					Parameter   
					Description   
					GP filter 1 sel   
					GP filter 2 sel   
					GP filter 3 sel   
					GP filter 4 sel   
					Selects input to general purpose filter 1   
					Selects input to general purpose filter 2   
					Selects input to general purpose filter 3   
					Selects input to general purpose filter 4   
					Function outputs   
					The following table specifies the output variables of the General Purpose Filters   
					function.   
					Variable   
					Description   
					GP filter 1 output   
					GP filter 2 output   
					GP filter 3 output   
					GP filter 4 output   
					General purpose filter 1 output   
					General purpose filter 2 output   
					General purpose filter 3 output   
					General purpose filter 4 output   
					Function configuration   
					The following table specifies the configuration parameters of the General Purpose   
					Filters function.   
					Parameter   
					Description   
					GP filter 1 bndwth   
					GP filter 2 bndwth   
					GP filter 3 bndwth   
					GP filter 4 bndwth   
					General purpose filter 1 bandwidth   
					General purpose filter 2 bandwidth   
					General purpose filter 3 bandwidth   
					General purpose filter 4 bandwidth   
					Function description   
					The operation of general purpose filter 1 is described here. Each of the four general   
					purpose filters behaves in the same manner.   
					The input, output, and bandwidth of general purpose filter 1 are defined as follows:   
					Input = Variable selected by GP filter 1 sel   
					Output = GP filter 1 output   
					Bandwidth = GP filter 1 bndwth   
					The transfer functions for general purpose filter 1 is defined as follows:   
					Bandwidth   
					Output =   
					× Input   
					s + Bandwidth   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-11   
				The general purpose filters run at the fastest execution rate available in the product.   
					This is the same rate at which bridge feedbacks are collected, the fastest regulators   
					are operated, and hardware commands are issued. The filter execution rate is   
					generally faster than the 1-millisecond rate at which the application functions and the   
					LAN communications occur.   
					Related diagrams   
					• 
					Diagnostic & Utility Functions (Diag_Util)   
					Oscillator   
					Each Innovation Series product contains a diagnostic oscillator. The oscillator   
					switches between a positive value and a negative value, spending the same amount   
					of time at each level. The oscillator can be used as a reference signal source for test   
					purposes.   
					Function outputs   
					The following table specifies the output variables of the Oscillator function.   
					Variable   
					Description   
					Sqr wave osc output   
					Oscillator square wave output   
					Function configuration   
					The following table specifies the configuration parameters of the Oscillator function.   
					Parameter   
					Description   
					Oscillator neg mag   
					Oscillator pos mag   
					Oscillator 1/2 cycle   
					Oscillator enable   
					Magnitude of the negative portion of oscillator output   
					Magnitude of the positive portion of oscillator output   
					Time that defines half of the oscillation period, sec   
					Enable oscillator   
					Function description   
					The Oscillator function produces a square wave output that switches between a   
					positive value and a negative value. The function can be enabled or disabled via the   
					parameter, Oscillator enable. The output levels and the period of the square wave are   
					configurable. The following diagram shows how the configuration parameters   
					generate the oscillator output.   
					Sqr wave osc output   
					Oscillator pos mag   
					0 
					Time   
					-Oscillator neg mag   
					Oscillator 1/2 cycle   
					Related diagrams   
					• 
					Diagnostic & Utility Functions (Diag_Util)   
					3-12 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Position Feedback   
					The Position Feedback function provides a set of position feedback signals in 22-bit   
					floating point format.   
					Function inputs   
					The following tachometer signals are inputs to the Position Feedback function.   
					• 
					• 
					• 
					Tachometer position: This signal is a 16-bit integer with units of A-quad-B   
					counts.   
					Marker count: This signal is a 16-bit integer that increments every time a marker   
					pulse is detected.   
					Marked tachometer position: This signal is a 16-bit integer with units of A-quad-   
					B counts. It equals the tachometer position at the instant the marker pulse is   
					detected.   
					The following table specifies the input parameters of the Position Feedback function.   
					Parameter   
					Description   
					Pos sample cmd sel   
					Selects the signal that specifies the sampling of   
					tachometer position.   
					Function outputs   
					The following table specifies the output variables of the Position Feedback function.   
					Variable   
					Description   
					Tachometer position extended to 22 bits and   
					converted to floating point format.   
					Position counter   
					Marked tachometer position extended to 22 bits and   
					converted to floating point format.   
					Pos cntr mark   
					Sampled version of Position counter, sampled on the   
					falling edge of the sample signal.   
					Pos down edge smp   
					Pos up edge sample   
					Sampled version of Position counter, sampled on the   
					rising edge of the sample signal.   
					Function description   
					The output signals Position counter and Pos cntr mark are the tachometer position   
					and the marked tachometer position extended from 16 to 22 bits. Position counter   
					and Pos cntr mark roll over to zero (0) at the maximum value that can be represented   
					in 22 bits (4,194,303). The transition happens in both the forward and backward   
					directions.   
					Position counter is sampled when the signal selected by Pos sample cmd sel   
					transitions between True and False. Pos up edge sample equals Position counter   
					when the signal selected by Pos sample cmd sel changes from False to True. Pos   
					down edge smp equals Position counter when the signal selected by Pos sample cmd   
					sel changes from True to False.   
					The Task Interval Strobe shown on the Position Feedback diagram represents   
					sampling of hardware that takes place at the Task 1 rate, the fastest execution rate   
					available to the control. The Task 1 rate is faster than the fastest rate at which   
					Position counter can be sampled.   
					Related diagrams   
					• 
					Position Feedback Instrument (PosFbk)   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-13   
				Predefined Constants   
					Each Innovation Series product contains a number of predefined constants. These   
					constants are available for use in a variety of functions. They are generally found on   
					the selection lists for parameters that select control signals.   
					Floating point constants   
					The following floating point constants are available.   
					• 
					• 
					• 
					Constant float 0.0   
					Constant float -1.0   
					Constant float 1.0   
					Integer constants   
					The following integer constants are available.   
					• 
					• 
					• 
					Constant integer0   
					Constant integer -1   
					Constant integer1   
					Boolean constants   
					The following Boolean constants are available.   
					• 
					• 
					Force True   
					Force False   
					Unused constants   
					The Unused category of constants can be used to turn off certain product behaviors.   
					See individual functional helps for information on how the Unused constants affect   
					those functions.   
					The following Unused constants are available.   
					• 
					• 
					• 
					Unused float   
					Unused integer   
					Unused boolean   
					3-14 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Signal Level Detector (SLD)   
					Each Innovation Series product supplies three SLD channels. Each SLD does a level   
					comparison on two inputs. The Boolean output of the SLD represents the status of   
					the comparison. The nature of the comparison is configurable.   
					Function inputs   
					The following table specifies the input parameters of the Signal Level Detector   
					(SLD) function.   
					Parameter   
					Description   
					SLD1 input 1 select   
					SLD1 input 2 select   
					SLD2 input 1 select   
					SLD2 input 2 select   
					SLD3 input 1 select   
					SLD3 input 2 select   
					Selects SLD1 input 1 value   
					Selects SLD1 input 2 value   
					Selects SLD2 input 1 value   
					Selects SLD2 input 2 value   
					Selects SLD3 input 1 value   
					Selects SLD3 input 2 value   
					Function outputs   
					The following table specifies the output variables of the Signal Level Detector (SLD)   
					function.   
					Variable   
					Description   
					SLD1 status   
					SLD2 status   
					SLD3 status   
					Status of SLD1 comparison   
					Status of SLD2 comparison   
					Status of SLD3 comparison   
					Function configuration   
					The following table specifies the configuration parameters of the Signal Level   
					Detector (SLD) function:   
					Parameter   
					Description   
					SLD1 compare mode   
					SLD1 sensitivity   
					Type of comparison that the SLD1 function performs   
					SLD1 comparison level   
					SLD1 hysteresis   
					SLD1 turn off deadband   
					SLD1 pick up delay   
					SLD1 drop out delay   
					SLD1 input 1 abs val   
					SLD2 compare mode   
					SLD2 sensitivity   
					SLD1 turn on time delay, Seconds   
					SLD1 turn off time delay, Seconds   
					SLD1 input 1 mode (allows the absolute value to be used)   
					Type of comparison that the SLD2 function performs   
					SLD2 comparison level   
					SLD2 hysteresis   
					SLD2 turn off deadband   
					SLD2 pick up delay   
					SLD2 drop out delay   
					SLD2 input 1 abs val   
					SLD3 compare mode   
					SLD3 sensitivity   
					SLD2 turn on time delay, Seconds   
					SLD2 turn off time delay, Seconds   
					SLD2 input 1 mode (allows the absolute value to be used)   
					Type of comparison that the SLD3 function performs   
					SLD3 comparison level   
					SLD3 hysteresis   
					SLD3 turn off deadband   
					SLD3 pick up delay   
					SLD3 drop out delay   
					SLD3 input 1 abs val   
					SLD3 turn on time delay, Seconds   
					SLD3 turn off time delay, Seconds   
					SLD3 input 1 mode (allows the absolute value to be used)   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-15   
				Function description   
					The following description explains the operation of SLD1. It also applies to SLD2   
					and SLD3.   
					Parameters SLD1 input 1 select and SLD1 input 2 select select device variables. They   
					define the inputs for SLD1. The following table specifies how the inputs are formed   
					based on the value of parameter SLD1 input 1 abs val.   
					SLD1 input 1 abs val   
					SLD1 Input Values   
					False   
					Input 1 = SLD1 input 1 select pointer value   
					Input 2 = SLD1 input 2 select pointer value   
					True   
					Input 1 = Absolute value of SLD1 input 1 select   
					pointer value   
					Input 2 = SLD1 input 2 select pointer value   
					The parameter SLD1 compare mode determines the type of comparison that is   
					performed on the two inputs. It determines how the configuration parameters SLD1   
					sensitivity, SLD1 hysteresis, SLD1 pick up delay, and SLD1 drop out delay are   
					interpreted. It determines how the output SLD1 status is formed. The following   
					tables specify the behavior of SLD1 for the different enumerations of SLD1 compare   
					mode.   
					SLD1 compare mode = In1-In2>Sen   
					Turn on condition   
					Turn on delay time   
					(Input 1 - Input 2) > SLD1 sensitivity   
					Turn on condition must remain valid for SLD1 pick up   
					delay. After the delay SLD1 status = True.   
					Turn off condition   
					Turn off delay time   
					(Input 1 - Input 2) <= (SLD1 sensitivity - SLD1   
					hysteresis)   
					Turn off condition must remain valid for SLD1 drop out   
					delay. After the delay SLD1 status = False.   
					SLD1 compare mode = In1-In2<Sen   
					Turn on condition   
					Turn on delay time   
					(Input 1 - Input 2) < SLD1 sensitivity   
					Turn on condition must remain valid for SLD1 pick up   
					delay. After the delay SLD1 status = True.   
					Turn off condition   
					Turn off delay time   
					(Input 1 - Input 2) >= (SLD1 sensitivity + SLD1   
					hysteresis)   
					Turn off condition must remain valid for SLD1 drop out   
					delay. After the delay SLD1 status = False.   
					SLD1 compare mode = In1<>In2   
					Turn on condition   
					Turn on delay time   
					Absolute value of (Input 1 - Input 2) > SLD1 sensitivity   
					Turn on condition must remain valid for SLD1 pick up   
					delay. After the delay SLD1 status = True.   
					Turn off condition   
					Turn off delay time   
					Absolute value of (Input 1 - Input 2) <=(SLD   
					sensitivity-SLD1 hysteresis)   
					Turn off condition must remain valid for SLD1 drop out   
					delay. After the delay SLD1 status = False.   
					3-16 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				SLD1 compare mode = In1=In2   
					Turn on condition   
					Turn on delay time   
					Turn off condition   
					Absolute value of (Input 1 - Input 2) <= SLD1   
					sensitivity   
					Turn on condition must remain valid for SLD1 pick up   
					delay. After the delay SLD1 status = True.   
					Absolute value of (Input 1 - Input 2) > (SLD1   
					sensitivity + SLD1 hysteresis)   
					Turn off delay time   
					Turn off condition must remain valid for SLD1 drop   
					out delay. After the delay SLD1 status = False.   
					SLD1 compare mode = In1-In2>Sen one shot   
					Turn on condition   
					Turn on delay time   
					(Input 1 - Input 2) > SLD1 sensitivity   
					After the turn on condition is met a timer begins. The   
					turn on condition does not need to remain valid while   
					the timer runs.   
					After SLD1 pick up delay expires SLD1 status = True.   
					After SLD1 status goes True a timer begins.   
					Turn off condition   
					Reset condition   
					After SLD1 drop out delay expires SLD1 status =   
					False.   
					The minimum time SLD1 status is True is   
					approximately 1 millisecond.   
					SLD 1 becomes active again when (Input 1 - Input 2)   
					<= (SLD1 sensitivity - SLD1 hysteresis)   
					SLD1 compare mode = In1-In2<Sen one shot   
					Turn on condition   
					Turn on delay time   
					(Input 1 - Input 2) < SLD1 sensitivity   
					After the turn on condition is met a timer begins. The   
					turn on condition does not need to remain valid while   
					the timer runs.   
					After SLD1 pick up delay expires SLD1 status = True.   
					After SLD1 status goes True a timer begins.   
					Turn off condition   
					After SLD1 drop out delay expires SLD1 status =   
					False.   
					The minimum time SLD1 status is True is   
					approximately 1 millisecond.   
					Reset condition   
					SLD 1 becomes active again when (Input 1 - Input 2)   
					>= (SLD1 sensitivity + SLD1 hysteresis)   
					Related diagrams   
					• 
					Signal Level Detection (SLD)   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-17   
				Simulator   
					The Simulator function allows the user to simulate the operation of the drive and   
					motor without applying power to the motor, power bridge, and other equipment.   
					Function inputs   
					The following table specifies the input parameters of the Simulator function.   
					Parameter   
					Description   
					Ext sim spd enb sel   
					Selects the signal that disables the calculated model   
					speed and allows the speed to be specified by another   
					source.   
					Ext sim spd sel   
					Ext sim trq sel   
					Selects the variable motor speed that overrides the speed   
					calculation. RPM   
					Selects the variable torque produced by an external load.   
					Newton-meters   
					Function outputs   
					The following table specifies the output variables of the Simulator function.   
					Variable   
					Description   
					Simulated speed   
					Motor speed. Radians/second   
					Function configuration   
					The following table specifies the configuration parameters of the Simulator function.   
					Parameter   
					Description   
					Simulate mode   
					Fixed ext sim spd   
					Enables drive and motor simulation.   
					Constant motor speed that overrides the speed   
					calculation. Radians/second.   
					Simulated load   
					Constant torque produced by an external load. Newton-   
					meters or Pound-feet.   
					Sim const friction   
					Simulated inertia   
					Constant friction. Newton-meters or Pound-feet   
					Inertia of motor and load. Kilogram-meters² or Pound-   
					feet²   
					Simulated stiction   
					Sim visc friction   
					Constant stiction. Newton-meters or Pound-feet   
					Viscous friction coefficient. Newton-meters/RPM or   
					Pound-feet/RPM   
					3-18 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Control Diagnostic Variables   
					The Control Diagnostic Variables function outputs filtered diagnostic variables that   
					are available to the user.   
					Function outputs   
					The following table specifies the output variables of the Control Diagnostic   
					Variables function.   
					Variable   
					Description   
					AC line voltage mag   
					Filtered ac line magnitude. A true magnitude calculation   
					of Vab and Vbc which is then filtered.   
					AC line frequency   
					Filtered ac line frequency produced by the phase lock   
					loop.   
					Line Simulator   
					The Line Simulator function allows the user to simulate the operation of the drive   
					and the ac line without applying power to the bridge.   
					Function inputs   
					The following table specifies the input parameters of the Line Simulator function.   
					Parameter   
					Description   
					Sim line frequency   
					AC line frequency in simulator mode. It is normally set   
					to, but not restricted to, 50 or 60 Hertz.   
					Sim freq slew rate   
					Sim A-N volt scale   
					Simulator frequency slew in radians/sec/sec. Setting   
					this value to a something other than zero causes the   
					frequency to slew continuously from (-)0.5 of nominal to   
					(+)0.25 of nominal and back. This exercises the entire   
					transient frequency range covered by the specification.   
					Sim A-N volt scale can be used to attenuate phase A   
					line to neutral voltage in order to simulate transient line   
					conditions. The line to neutral voltage for phase A will   
					be attenuated according to Sim A-N volt scale every   
					2.70046 Seconds. The duration of the transient is   
					specified by the parameter Volt short time. The 2.70046   
					Seconds period was chosen so that the transient   
					condition gradually walks through the sine wave. In   
					order to simulate an open on phase A, set Sim A-N volt   
					scale to 1.0, Sim B-N volt scale to 1.0, and Sim C-N volt   
					scale to 0.5.   
					Sim B-N volt scale   
					Sim C-N volt scale   
					A-B volt fault scale   
					Sim B-N volt scale behaves identically to Sim A-N volt   
					scale except that it affects phase B instead of phase A.   
					Sim C-N volt scale behaves identically to Sim A-N volt   
					scale except that it affects phase C instead of phase A.   
					A-B volt fault scale simulates a line to line fault   
					between phases A and B. The default for A-B volt fault   
					scale is 0, providing no attenuation.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-19   
				Function outputs   
					The following table specifies the output variables of the Line Simulator function.   
					Variable   
					Description   
					Simulate mode act   
					Sim A-B line voltage   
					Sim B-C line voltage   
					Sim A-N line voltage   
					Sim B-N line voltage   
					Sim C-N line voltage   
					Simulator mode   
					Simulator line to line voltage A-B   
					Simulator line to line voltage B-C   
					Simulator line to neutral voltage A   
					Simulator line to neutral voltage B   
					Simulator line to neutral voltage C   
					Function configuration   
					The following table specifies the configuration parameters of the Line Simulator   
					function.   
					Parameter   
					Description   
					Simulate mode   
					Enables simulation mode.   
					Drive Configuration Functions   
					Intelligent Part Number (IPN)   
					The Intelligent Part Number (IPN) specifies the Innovation Series product and the   
					basic configuration of the product. The IPN is the catalog number for the Innovation   
					Series product. It can be found on the inside of the cabinet door.   
					The IPN for the Innovation Series medium voltage drive with general industrial   
					application pattern takes the following form:   
					ACMVAC2-G-FRAM-VOLT-AMPS-xxxxxxxxx-xxx-xx   
					The IPN contains eight fields separated by dashes. The fields shown in italics are   
					user configurable.   
					Product field   
					The product field is designated by the characters ACMVAC2. The characters have   
					the following meaning:   
					AC   
					MV   
					AC   
					2 
					AC inverter drive   
					Medium voltage   
					AC fed   
					2300 volt   
					3-20 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Pattern field   
					The pattern field is designated by the character G. The character has the following   
					meaning:   
					G 
					General industrial application firmware pattern   
					Frame size field   
					The frame size field is designated by the characters FRAM. The designation has the   
					following meaning:   
					FRAM   
					Bridge frame size   
					The following medium voltage drive frame sizes are supported:   
					0700 (Eupec IGBTs)   
					0701 (Powerex IGBTs)   
					System voltage field   
					The system voltage field is designated by the characters VOLT. The designation has   
					the following meaning:   
					VOLT   
					Maximum lineup output AC voltage   
					The medium voltage drive supports the following system voltages:   
					2300   
					Shunt rating field   
					The shunt rating field is designated by the characters AMPS. The designation has the   
					following meaning:   
					AMPS   
					Total shunt amp rating per phase   
					The medium voltage drive supports the following shunt ratings:   
					0300, 0500, 0600, 0800, 1000   
					Primary Motor & Application Data   
					User entered parameters   
					Eight primary values define the motor load for the Innovation Series general   
					industrial application (GIA) pattern drive. The primary values include motor   
					nameplate data and application data. They are user-entered parameters that are   
					generally specified within the Drive Commissioning wizard. The primary values are   
					used to determine control and protective settings for the drive.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-21   
				The following table lists the user-entered parameters that specify the primary motor   
					and application data:   
					Parameter   
					Description   
					Motor rated current   
					Motor rated voltage   
					Crossover Voltage   
					Motor rated power   
					Motor rated freq   
					Motor rated rpm   
					Motor poles   
					Motor nameplate current. Amps   
					Motor nameplate voltage. Volts   
					Voltage at which field weakening begins. RMS volts   
					Motor nameplate power. Kilowatts or Horsepower   
					Motor nameplate frequency. Hertz   
					Motor nameplate speed. RPM   
					The number of magnetic poles in the motor. If this   
					parameter is left blank, the control determines the   
					number of poles from parameters Motor rated freq   
					and Motor rated rpm. In the case of some lower speed   
					motors (less than 900 rpm at 60 hz) with high slip, this   
					determination may not be accurate and parameter   
					Motor poles must have the correct value entered.   
					Unitless. Must be an even whole number.   
					Applied top RPM   
					Top application speed. RPM   
					Reflected indication variables   
					The Innovation Series drive contains a variable copy of some of the primary motor   
					and application parameters. The following table lists the variable reflections of the   
					primary value parameters:   
					Variable   
					Description   
					100% Motor current   
					100% Motor voltage   
					100% Motor power   
					100% Applied RPM   
					Motor nameplate current. RMS amps   
					Voltage at which field weakening begins. RMS volts   
					Motor nameplate power. Kilowatts or Horsepower   
					Top application speed used in overspeed fault   
					protection and other areas of motor control. RPM   
					3-22 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Calculated control variables   
					The Innovation Series drive contains a set of variables that are calculated from the   
					primary motor parameters but are not exact reflections of the primary parameters.   
					These calculated variables are used in motor control and protective functions. The   
					values of the variables are calculated at drive initialization after power up or a hard   
					reset.   
					The following table lists the variables calculated from the primary value parameters:   
					Parameter   
					Description   
					100% Motor torque   
					Motor torque at motor nameplate conditions. Newton-   
					meters or Pound-feet   
					100% Flux   
					Motor flux at motor nameplate conditions. Volts/hertz   
					100% Torque current   
					Motor torque current at motor nameplate conditions.   
					RMS amps   
					100% Flux current   
					100% Slip   
					Motor flux current at motor nameplate conditions.   
					RMS amps   
					Motor slip at motor nameplate conditions.   
					Radians/second   
					Display meter scaling parameters   
					The Innovation Series drive contains a set of parameters that specify the scaling for   
					the DDI and toolbox display meters. These parameters are calculated from the   
					primary motor and application parameters. They are calculated within the Drive   
					Commissioning wizard or the Per Unit Setup wizard. If any of the primary data   
					parameters is modified outside the Drive Commissioning wizard, the Per Unit Setup   
					wizard should be performed to update the display meter scaling parameters.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-23   
				General Setup Functions   
					Keypad Overview   
					The Drive Diagnostic Interface (DDI; also known as the keypad) is mounted on the   
					door of an Innovation Series drive. The DDI provides a simple, easily accessible   
					means for a user to set, monitor, and maintain the drive locally.   
					The DDI provides both analog and digital representations of drive functions and   
					values. Its keypad is logically organized into two functional groups: navigation keys   
					and drive control keys. The Run and Stop keys are set to the side for easy access.   
					The operator can use the DDI to perform the following common tasks:   
					• 
					• 
					• 
					• 
					• 
					Monitor speed / current / voltage / power   
					Start/Stop the drive   
					Adjust a configuration parameter   
					Reset a fault condition   
					Commission the drive through a wizard   
					Each drive has its own DDI for local control.   
					Related functions   
					Following are the DDI functions that can be modified from the toolbox:   
					• 
					• 
					• 
					• 
					Keypad Contrast Adjustment   
					Keypad Meter Configuration   
					Keypad Security Configuration   
					Language Display   
					3-24 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Keypad Contrast Adjustment   
					Normally the LCD contrast of the Drive Diagnostic Interface (DDI) should be   
					adjusted at the DDI or keypad. The user can modify the Keypad contrast adj   
					parameter under the General Setup -> Keypad -> Keypad Functions menu.   
					A special keypad key sequence is also available to make this adjustment and is   
					especially useful when the contrast is too light or too dark to navigate the menus.   
					The sequence is to hold down the Menu key and press either the up (darker) or down   
					(lighter) arrow keys until the contrast is acceptable.   
					If your DDI firmware version is prior to V02.01.03C and the DDI contrast is too   
					light or too dark to navigate through the menus you will need to use Toolbox to find   
					the Keypad contrast adj parameter and make the adjustment.   
					Function configuration   
					Parameter   
					Description   
					Keypad contrast adj   
					Adjusts the contrast of the DDI LCD screen. Values are   
					from 0 to 63 where 63 is the darkest contrast. Setting   
					Keypad contrast adj to 0 will cause the DDI to adjust the   
					contrast to a middle value.   
					Note Once Keypad contrast adj has been modified in   
					the toolbox and then saved in the drive, a hard reset   
					must be performed for the user to see their modification   
					to the contrast reflected in the DDI.   
					Keypad Meter Configuration   
					The DDI Status screen has four animated meters and associated text that display   
					drive performance information.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-25   
				The variables displayed by the meters and the meter ranges can be modified by   
					configuring the following parameters:   
					Function configuration   
					Parameter   
					Description   
					Keypad meter 1 sel   
					Selects a floating-point variable that is displayed in   
					Meter #1 on the DDI Status screen.   
					Keypad meter 2 sel   
					Keypad meter 3 sel   
					Keypad meter 4 sel   
					Keypad meter 1 range   
					Selects a floating-point variable that is displayed in   
					Meter #2 on the DDI Status screen.   
					Selects a floating-point variable that is displayed in   
					Meter #3 on the DDI Status screen.   
					Selects a floating-point variable that is displayed in   
					Meter #4 on the DDI Status screen.   
					Selects the bar graph meter scaling for Meter #1.   
					Possible values are as follows (note that all bar   
					graphs are scaled in percent (%)):   
					0 to +100   
					-100 to +100   
					0 to +150   
					-150 to +150   
					0 to +200   
					-200 to +200   
					0 to +300   
					-300 to +300   
					Keypad meter 2 range   
					Keypad meter 3 range   
					Keypad meter 4 range   
					Keypad meter 1 ref   
					Selects the bar graph meter scaling for Meter #2.   
					See Keypad meter 1 range for possible values.   
					Selects the bar graph meter scaling for Meter #3.   
					See Keypad meter 1 range for possible values.   
					Selects the bar graph meter scaling for Meter #4.   
					See Keypad meter 1 range for possible values.   
					Selects an optional reference display for Meter #1. If   
					selected, the bar graph for this reference signal will be   
					displayed just above the bar graph for the feedback   
					signal. Both graphs will be displayed in the Meter #1   
					area as a split screen. The reference signal will only   
					be displayed if local mode is enabled. Keypad meter 1   
					ref can be disabled from the pick list.   
					Note When changing DDI meter configuration from the toolbox, first save the   
					modified parameters to the drive. Press the Menu button and then the Status button   
					on the DDI. This will cause the meters on the Status screen to update.   
					3-26 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Keypad Security Configuration   
					The DDI contains security controls to keep unauthorized personnel from operating or   
					reconfiguring the drive. These security controls can be modified from the toolbox or   
					from the DDI. The controls are password protected in the DDI.   
					Function configuration   
					Parameter   
					Description   
					Keypad privilege   
					Selects the privilege level in the DDI. Possible levels are:   
					Read only - Disables both drive controls and configuration   
					functions. Allows user to view but not edit parameters.   
					Operate & read only – Enables drive controls, but disables   
					configuration functions. Allows user to view but not edit   
					parameters.   
					Configure & operate - Enables both drive controls and   
					configuration functions.   
					See below for full list of enabled functions for each level.   
					Keypad password   
					Sets the 5-digit password value for the DDI. When a user   
					attempts to modify the Keypad security configuration from   
					the DDI, he will be prompted to enter a password. If the   
					entered password does not match the value in Keypad   
					password, the user will not be permitted to modify the   
					security configuration (Keypad privilege and Keypad   
					password).   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-27   
				Function description   
					The following table displays a list of all DDI functions. Available functions for each   
					privilege level are marked with a check mark (ü).   
					Privilege Level   
					Operate &   
					read only   
					Cofigure &   
					operate   
					Keypad Function   
					Read Only   
					Drive control functions   
					Stop   
					Start   
					Reset faults   
					Change direction   
					Remote/Local   
					Jog   
					Speed Increment   
					Speed Decrement   
					Menu functions   
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					Status button   
					Menu button   
					Navigation buttons (Arrows, Esc, Enter)   
					Display Active Faults   
					Display Fault History   
					View Parameters   
					Edit Parameters   
					View Variables   
					Wizards   
					Adjust Screen Contrast   
					Display Firmware Version   
					Display Hardware Information   
					Save Parameters to Backup   
					Restore Parameters from Backup   
					Compare Current Parameters to Backup   
					View Overrides   
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					ü 
					Note When changing DDI security configuration from the toolbox, first save the   
					modified parameters to the drive. Then switch between the Menu and Status screens   
					for the password and privilege level to update.   
					Language and Units Presentation   
					The presentation of the Innovation Series product in the Control System Toolbox and   
					DDI (keypad) can be customized. The presentation can be configured using the   
					following parameters:   
					• 
					• 
					Language   
					Display units   
					In regions in which English is not the primary language, the Innovation Series   
					product provides a choice of two languages: English and the indigenous language.   
					The presentation is in English if parameter Language is set to English. The   
					presentation is in the indigenous language if Language is set to Native.Parameters   
					and variables in the Innovation Series product can be displayed in different unit   
					systems. The display units are chosen by parameter Display units.   
					3-28 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Three different unit systems are available:   
					• 
					• 
					• 
					Imperial (English)   
					Metric (SI)   
					Native (Platform)   
					If Display units is set to Native (Platform), then values are displayed in the same   
					units that the internal control uses. The following table specifies some of the unit   
					system differences.   
					Display units   
					Length   
					Power   
					Torque   
					Flux   
					Feet   
					Horsepower   
					Foot-pounds   
					Volts/hertz   
					Imperial   
					(English)   
					Metric (SI)   
					Meters   
					Meters   
					Kilowatts   
					Watts   
					Newton-meters   
					Newton-meters   
					Volts/hertz   
					Webers   
					Native (Platform)   
					Language Display   
					As long as the keypad has been configured correctly, the DDI can display its menu   
					and status information in an alternate language.   
					Note Presently this function is not yet operational.   
					Function configuration   
					Parameter   
					Description   
					Language   
					Selects the language in which to display all information in the DDI.   
					Possible selections are:   
					English - Displays DDI text in English.   
					Native - Displays DDI text in the native language that is specified   
					when DDI Menus are downloaded from the toolbox (see below).   
					Function description   
					To display the DDI text in a non-English language, the user must first download the   
					appropriate DDI Menus. The user can perform this operation from the toolbox by   
					selecting from the menu bar: Device > Download > DDI Menus.   
					The user will then be prompted to select an alternate language to download to the   
					DDI.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-29   
				The toolbox will then build the DDI Menu file and can be downloaded to the DDI.   
					Once the download is completed, the user can then modify the Language parameter   
					to the desired value. The DDI will display its text in the selected language the next   
					time its screen is updated   
					I/O Functions   
					Analog and Digital I/O Testing   
					The Analog and Digital I/O Testing function is intended for factory use only.   
					Function configuration   
					The following table specifies the configuration parameters for the Analog and   
					Digital I/O Testing function.   
					Parameter   
					Description   
					I/O test mode req   
					Simulate mode   
					Hardware I/O test request.   
					Simulator mode request.   
					Both I/O test mode req and Simulate mode must be True for the Analog and Digital   
					I/O Testing function to be active. I/O test mode is True when the function is active.   
					Analog inputs   
					The following table specifies the signals available for testing the analog inputs.   
					Variable   
					Description   
					Analog input 1 volts   
					Analog input 2 volts   
					Voltage of analog input 1 source. DC volts   
					Voltage of analog input 2 source. DC volts   
					3-30 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Digital inputs   
					The following table specifies the signals available for testing the digital inputs.   
					Variable   
					Description   
					Digital input 1 test   
					Digital input 2 test   
					Digital input 3 test   
					Digital input 4 test   
					Digital input 5 test   
					Digital input 6 test   
					Unfiltered value of digital input 1.   
					Unfiltered value of digital input 2.   
					Unfiltered value of digital input 3.   
					Unfiltered value of digital input 4.   
					Unfiltered value of digital input 5.   
					Unfiltered value of digital input 6.   
					Hi-fi counters   
					The following table specifies the signals available for testing the high fidelity VCO   
					counters.   
					Variable   
					Description   
					VCO 1 unfiltered   
					VCO 2 unfiltered   
					VCO 3 unfiltered   
					VCO 1 counter value.   
					VCO 1 counter value.   
					VCO 1 counter value.   
					Local and system fault strings   
					The following table specifies the signals available for testing the local and system   
					fault strings.   
					Variable   
					Description   
					Local fault test   
					System fault test   
					Unfiltered value of local fault string.   
					Unfiltered value of system fault string.   
					Contactor status   
					The following table specifies the signals available for testing the main contactor   
					status input.   
					Variable   
					Description   
					MA cont test mode   
					Unfiltered value of main contactor status.   
					DAC and meter outputs   
					The following table specifies the parameters that configure the analog output (DAC)   
					and meter output tests.   
					Parameter   
					Description   
					Analog out 1 test   
					Analog out 1 test   
					Analog out 1 test   
					Analog out 1 test   
					Analog meter 3 test   
					Analog meter 4 test   
					DAC 1 output voltage. DC volts   
					DAC 2 output voltage. DC volts   
					DAC 3 / Meter 1 output voltage. DC volts   
					DAC 4 / Meter 2 output voltage. DC volts   
					Meter 3 output voltage. DC volts   
					Meter 4 output voltage. DC volts   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-31   
				Relay outputs   
					The following table specifies the parameters that configure the relay output test.   
					Parameter   
					Description   
					Relay 1 test   
					Relay 1 output.   
					Relay 2 output.   
					Relay 3 output.   
					Relay 4 output.   
					Relay 2 test   
					Relay 3 test   
					SS relay driver test   
					Related diagrams   
					• 
					Analog and Digital I/O Testing (HWIO_Tst)   
					Analog Inputs/Outputs and Mapping   
					Analog Inputs   
					Two bipolar (±10 volts) analog inputs are available at the terminal board (ATB).   
					Jumpers on the BAIA board connect a burden resistor that allow these inputs to be   
					used for 4-20 ma references.   
					Analog in 1 offset and Analog in 2 offset provide a voltage offset adjustment. Analog   
					in 1 gain and Analog in 2 gain can be used to scale the inputs from volts to   
					appropriate application units. Analog in 1 filter and Analog in 2 filter provide first-   
					order signal softening at Analog input 1 and Analog input 2.   
					Loss of 4-20 ma signal can be configured by selecting a lower threshold Analog in 1   
					flt lev and Analog in 2 flt lev and then selecting the appropriate fault type, Analog in   
					1 flt mode and Analog in 2 flt mode.   
					Analog Outputs   
					Two bipolar (±10 volts) DAC outputs are available at the terminal board (ATB).   
					The signal to be output is selected by Analog out 1 select. This signal can be offset   
					by Analog out 1 offset using the same units as the signal to be output. The signal is   
					scaled for output by setting Analog out 1 scale to the value that will produce +10   
					volts. The second DAC is configured in a similar manner.   
					Meters   
					Four bipolar (±10 volts) meter drivers are available for use with the optional meter   
					assembly. This assembly is connected to the drive at connector J8 on the backplane.   
					The signal to be metered is selected by Analog meter 1 sel. This signal can be offset   
					by Meter 1 offset using the same units as the signal to be metered. The signal is   
					scaled for output by setting Analog meter 1 scale to the value which shall produce   
					+10 volts. Meter 1 mode is used to accommodate both 0 - +10 volt meters and -10 -   
					+10 volt meters. Analog meter 1 scale is unaffected by Meter 1 mode. The remaining   
					three meters are configured similarly.   
					Related diagrams   
					• 
					Analog Inputs / Outputs & Mapping (HWIO_Ana)   
					3-32 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Digital Inputs/Outputs and Mapping   
					Digital inputs and outputs provide an interface between the outside world and the   
					control. The ATB (terminal board) provides six general purpose digital inputs.   
					Three dry contact relays and one solid state relay driver are provided as outputs.   
					System and Local fault strings provide start and trip interlocks to the control.   
					Isolated digital inputs are listed with their associated terminal board points. A filter   
					debounces a noisy input signal. The filter should be set to zero in most instances,   
					since the hardware provides a level of debounce conditioning. The variables Digital   
					input 1 through Digital input 6 indicate the logical state of each digital input and are   
					used to interface to functions in the drive that require a Boolean signal.   
					Each relay output may be used by setting the parameters Relay 1 select through   
					Relay 3 select to the variables whose logical states are desired to drive the   
					corresponding relay. The associated terminal board points are shown for output   
					terminals of each relay. The variables Relay 1 state, Relay 2 state, and Relay 3 state   
					indicates whether the relay coils are energized.   
					Relay four is a solid-state relay driver that should be used for driving a 24 V dc, 10   
					mA relay. The relay driver output may be used by setting the parameter SS relay   
					driver sel to the variable whose logical state is desired to drive the relay. Solid state   
					relay indicates the status of the relay driver.   
					In addition to the four programmable outputs available on ATB, the drive provides 3   
					additional application outputs through the CTBC terminal board. The CTBC outputs   
					are not programmable but instead are mapped to some commonly used signals in the   
					drive. CTBC outputs are solid-state relay drivers that can be used for driving 24 V   
					dc, 10 mA relays. Signals available on CTBC are as follows:   
					CTBC Output   
					Pre-programmed function   
					D08 (pins 33 & 35)   
					D07 (pins 29 & 31)   
					D06 (pins 25 & 27)   
					Closed when No trip fault is True   
					Closed when Running is True   
					Closed when No faults active is True   
					A pilot relay controls a main contactor. Most applications do not require a contactor   
					(see MA contactor absent). This contactor is normally controlled through drive   
					sequencing, but it may be controlled alternately by MA close req sel. The contactor   
					cannot be energized if either the Local Fault String or the System Fault String are   
					open. If the contactor is closed and the Local Fault String or the System Fault String   
					open, the contactor will be de-energized.   
					Contactor status feedback is available (MA contactor closed). MA contactor fbk   
					determines if the drive sequencer requires MA contactor closed to be active in   
					response to a contactor close command.   
					Related diagrams   
					• 
					Digital Inputs / Outputs & Mapping (HWIO_Dig)   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-33   
				LAN Functions   
					LAN Overview   
					Information is available for the following LAN topics:   
					• 
					• 
					• 
					Frame Phaselock Loop   
					LAN Configuration and Health   
					LAN Signal Map   
					Frame Phaselock Loop   
					The Frame Phaselock Loop function can synchronize the execution of the Innovation   
					Series drive control firmware with the communication frame of the product   
					application interface. This feature is available only for those interface which support   
					synchronous communications, such as ISBus.   
					Function outputs   
					The following table specifies the published output variables of the Frame Phaselock   
					Loop function.   
					Variable   
					Description   
					Frame PLL OK status   
					Boolean signal indicating the lock status of the Frame   
					Phaselock Loop.   
					FPLL Phase error   
					FPLL Freq Output   
					Phase error signal for the Frame Phaselock Loop.   
					Scaling is per-unitized such that unity corresponds to the   
					full frame period; signal values range from minus one-   
					half to plus one-half.   
					Frequency adjustment output signal for the Frame   
					Phaselock Loop. Scaling is per-unitized such that unity   
					corresponds to the full frame period; signal values range   
					from minus output limit to plus output limit.   
					Function configuration   
					The following table specifies configuration parameters related to the Frame   
					Phaselock Loop function.   
					Parameter   
					Description   
					Network interface   
					Network interface type. Specifies one of the following   
					interface types:   
					No interface   
					ACL dual port memory (synchronous operation   
					supported)   
					ISBus (synchronous operation supported)   
					DRIVENET - Optional LAN modules such as Genius &   
					Profibus   
					LAN frame time   
					Expected communication frame period. Allowed frame   
					periods are 1, 2, 4, and 8 milliseconds.   
					3-34 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Function description   
					The product completely handles configuration of the Frame Phaselock Loop   
					function. Appropriate user selections of Network interface activate the function, and   
					user specification of LAN frame time sets the nominal period.   
					The Boolean variable Frame PLL OK status indicates the status of the Frame   
					Phaselock Loop. The asserted state indicates that the function has been activated and   
					that lock status has been validated. The unasserted state indicates that the function is   
					not activated or that lock status is not validated.   
					The FPLL Phase error signal reflects the phase error when valid phase information   
					has been extracted from the interface. A signal value of zero indicates either zero   
					phase error or invalid phase information. Scaling is such that one per-unit phase error   
					represents a full communication frame period.   
					The FPLL Freq Output signal is the frequency adjustment output of the function; the   
					authority of the function to modify away from nominal frequency is strictly limited.   
					When the function is not activated, the FPLL Freq Output signal is zero. When the   
					function is activated but no valid phase information is detected, then FPLL Freq   
					Output maintains its last valid calculated value.   
					When phaselock is achieved, Frame PLL OK status is asserted, FPLL Phase error is   
					at a zero-mean steady-state value, and FPLL Freq Output is at a non-zero, but very   
					small, steady-state value. When the Frame Phaselock Loop has been requested by   
					configuration but phaselock is not achieved, then Frame PLL not OK is shown.   
					LAN Configuration and Health   
					The following information describes the configuration of the primary signal interface   
					between the Innovation Series device and the application layer interface. The   
					application layer may consist of an embedded ACL card, a direct LAN interface   
					card, or an application-level ISBus serial bus.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-35   
				Configuration parameters   
					The following table specifies the configuration parameters of the LAN Configuration   
					and Health function.   
					Parameter   
					Description   
					Network interface   
					Network interface type. Specifies one of the following   
					interface types:   
					No interface   
					ACL dual port memory   
					ISBus   
					DRIVENET - Other optional LAN modules such as   
					Genius and Profibus   
					LAN frame time   
					LAN fbk avg time   
					Expected communication frame period. Allowed frame   
					periods are 1, 2, 4, and 8 milliseconds.   
					Period over which feedback signals are sequentially   
					averaged. The LAN Signal Map help topic describes   
					which feedback signals are averaged. If LAN fbk avg   
					time is zero, no averaging occurs.   
					LAN cmds inhibit   
					LAN trips inhibit   
					Disables LAN references, forcing the signal interface to   
					operate in feedback-only mode. Local images of   
					reference signals are set to zero (0.0) or False.   
					Disables LAN heartbeat trip fault (LAN heartbeat trip),   
					and enable the corresponding alarm (LAN heartbeat   
					alarm).   
					LAN heartbeat time   
					Sys ISBus node #   
					Period within which transition must be detected in the   
					LAN heartbeat signal (Heartbeat ref, lan) to satisfy the   
					local heartbeat timeout check.   
					ISBus node for the Innovation Series Drive device. Each   
					device on the ISBus bus should be assigned a unique   
					node between 1 and 31.   
					LAN parameter 1   
					through LAN   
					parameter 16   
					These parameters are used only by optional LAN   
					modules and are specific to those modules. Such items   
					as baud rate and device number are configured via these   
					parameters. Please see the documentation for the   
					specific LAN module for detailed information.   
					3-36 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Diagnostic variables   
					The following table specifies variables that indicate the LAN health and status for   
					the LAN Configuration and Health function.   
					Variable   
					Description   
					LAN connection ok   
					Indicates that the health of the LAN connection is   
					good, such that the LAN watchdog function is   
					satisfied.   
					LAN commands OK   
					Heartbeat ref, lan   
					Indicates that the health of the LAN references is   
					good, based upon detection of two successive LAN   
					connection ok indications.   
					LAN heartbeat signal that proceeds from the   
					application layer to the local device, used locally for   
					LAN heartbeat trip) and LAN heartbeat alarm)   
					detection, and as the source of the reflected   
					Heartbeat fbk, lan signal.   
					Heartbeat fbk, lan   
					Sys ISBus error cnt   
					Sys ISBus error reg   
					Local device reflection of the Heartbeat ref, lan   
					signal that is sent back to the application layer.   
					Counter signal which provides an indication of the   
					rate of occurrence of ISBus fault conditions.   
					Bit-coded value of the last ISBus fault detected;   
					each bit indicates a particular ISBus fault seen by   
					the control.   
					Frame PLL OK status   
					FPLL Phase error   
					Boolean signal indicating the lock status of the   
					Frame Phaselock Loop.   
					Phase error signal for the Frame Phaselock Loop.   
					Scaling is per-unitized such that unity corresponds   
					to the full frame period; signal values range from   
					minus one-half to plus one-half.   
					FPLL Freq Output   
					Frequency adjustment output signal for the Frame   
					Phaselock Loop. Scaling is per-unitized such that   
					unity corresponds to the full frame period; signal   
					values range from minus output limit to plus output   
					limit.   
					Function description   
					Determining the integrity of the LAN interface involves several communication   
					layers, and may vary depending upon the specific communication options in use.   
					The Innovation Series Drive has two levels of validation available: LAN watchdog   
					and LAN heartbeat. Status information is conveyed to the user and/or application by   
					status signals and fault declarations.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-37   
				The LAN watchdog function describes the set of mechanisms the drive uses to   
					determine the status of the connection between DSPX and the module immediately   
					“above” the drive in the LAN hierarchy. For Dual-Port RAM interfaces, such as that   
					used for an embedded ACLA controller and for a direct LAN interface, the watchdog   
					takes the form of a handshake protocol. In this handshake protocol, the drive   
					determines the presence of a minimum level of intelligence on the host on the LAN   
					side of the shared memory. For ISBus interfaces, such as that used by a remote or   
					embedded ACLA controller, the watchdog reflects the reception of ISBus frame   
					synchronization codes. The watchdog function’s immediate authority is limited to   
					alarms and status variables, although the status information does play a functional   
					role in the interface management. Note that the watchdog does not offer information   
					about the LAN connection’s status which may be supported beyond the immediate   
					interface to DSPX. In fact, many device networks offer no means of determining   
					basic network health.   
					The LAN heartbeat function is visible to the user. The heartbeat function uses   
					published signal map channels, and is available for use by the application. It provides   
					a means to “loop back” a signal between the drive and any level in the LAN   
					hierarchy so a higher-level controller can validate the entire connection pathway,   
					including the drive itself. Locally, the drive can be configured to trigger a trip or   
					alarm if the heartbeat reference signal fails to transition within a configurable period   
					of time. The heartbeat offers the most robust validation options from a system   
					perspective, although it offers the least information about the detected problem’s   
					location.   
					The System ISBus error alarm occurs when an ISBus fault is detected in the DSPX   
					control. The variable Sys ISBus error reg contains the bit-coded value of the last   
					ISBus fault detected; each bit indicates a particular ISBus fault seen by the control.   
					The variable Sys ISBus error cnt increments upon fault detection. When initializing   
					the interface, the user should expect the alarm to signal intermittently.   
					The Frame PLL not OK alarm occurs when phase-lock between the DSPX control   
					and the System ISBus or (local ACL) is not assured. Detection of the fault is enabled   
					when the parameter Network interface is configured to select an interface for which   
					synchronized operation is supported. This alarm indicates that data coherency is   
					compromised. Status of the Frame Phaselock Loop function can be observed via the   
					signals Frame PLL OK status, FPLL Phase error, and FPLL Freq Output.   
					LAN Signal Map   
					The following information describes the primary signal interface between the   
					Innovation Series Drive and the product application layer interface. The application   
					layer may consist of an embedded ACL card, a direct LAN interface card, or an   
					application-level ISBus serial bus.   
					The LAN Signal Map is a fixed signal map that defines dedicated registered   
					communication channels for specific signals. It is defined in terms of paired   
					reference and feedback pages that are the same size physically. The internal data   
					organization of the reference and feedback pages may differ. The standard   
					Innovation Series signal map page consists of eight 32-bit elements.   
					3-38 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Each 32-bit element in the LAN Signal Map is assigned a data type. The following   
					data types are used.   
					• 
					Single precision floating point, IEEE 754 format (23-bit mantissa, 8-bit   
					exponent, 1-bit sign).   
					• 
					• 
					Two’s complement integer.   
					Individual 1-bit Boolean signals.   
					LAN References   
					The following table specifies the LAN Signal Map reference signals.   
					Page &   
					Element   
					Signal   
					Data   
					Type   
					Description   
					1 
					1 
					Boolea   
					n bits   
					Boolean requests. See table below for   
					definition of request bits.   
					1 
					2 
					Auto speed ref,   
					lan   
					Floating   
					point   
					Auto speed reference that can be used   
					in the Speed Reference Generation   
					function. RPM   
					1 
					1 
					3 
					4 
					Spd ref offset,   
					lan   
					Floating   
					point   
					Speed reference offset that can be   
					used prior to the Speed/Torque   
					Regulator function. RPM   
					Torque ref, lan   
					Floating   
					point   
					Torque reference that can be used in   
					the Speed/Torque Regulator function.   
					Newton-meters or Pound-feet   
					1 
					1 
					1 
					5 
					6 
					7 
					Unused   
					Unused   
					GP lan ref 1   
					Floating   
					point   
					General purpose reference that can be   
					used by a number of functions.   
					1 
					2 
					8 
					1 
					GP lan ref 2   
					Floating   
					point   
					General purpose reference that can be   
					used by a number of functions.   
					Torque fdfwd,   
					lan   
					Floating   
					point   
					Torque feed forward reference that can   
					be used in the Speed/Torque   
					Regulator function. Newton-meters or   
					Pound-feet   
					2 
					2 
					2 
					3 
					Flux reference,   
					lan   
					Floating   
					point   
					Flux scale that can be used in the   
					Motor Control Interface function.   
					Droop comp   
					ref, lan   
					Floating   
					point   
					Droop compensation reference that   
					can be used in the Droop function. Per   
					unit torque   
					2 
					2 
					2 
					2 
					4 
					5 
					6 
					7 
					Unused   
					Unused   
					Unused   
					GP lan ref 3   
					Floating   
					point   
					General purpose reference that can be   
					used by a number of functions.   
					2 
					8 
					GP lan ref 4   
					Floating   
					point   
					General purpose reference that can be   
					used by a number of functions.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-39   
				The following table specifies the LAN Signal Map request bits that appear in Page 1,   
					Element 1 of the reference signal map.   
					Bit   
					Signal   
					Description   
					0 
					Heartbeat ref,   
					lan   
					Heartbeat signal to validate LAN health.   
					1 
					2 
					3 
					Fault reset req,   
					lan   
					Request to reset drive faults. Functionality is always   
					enabled.   
					Trip request,   
					lan   
					Request to trip the drive. Functionality is always   
					enabled.   
					Alarm request,   
					lan   
					Request to declare an alarm in the drive. Functionality   
					is always enabled.   
					4-7   
					8 
					Unused   
					Run request,   
					lan   
					Request to run the drive. Functionality is always   
					enabled.   
					9 
					Jog request,   
					lan   
					Request to jog the drive. Functionality is always   
					enabled.   
					10   
					11   
					12   
					13   
					14   
					15   
					16   
					X stop request,   
					lan   
					Request to perform an X stop in the drive.   
					Functionality is always enabled.   
					Full flux req, lan   
					Request to flux the drive. Functionality is always   
					enabled.   
					Rev mode req,   
					lan   
					Request to reverse the direction of rotation that can be   
					used in the Speed Reference Generation function.   
					Torque mode   
					req, lan   
					Request to enable torque mode that can be used in the   
					Speed/Torque Regulator function.   
					Droop disab   
					req, lan   
					Request to inhibit droop functionality that can be used   
					in the Droop function.   
					Trq lim 2 sel,   
					lan   
					Request to choose between torque limits that can be   
					used in the Motor Control Interface function.   
					Ramp rate 2   
					sel, lan   
					Request to choose between ramp rates that can be   
					used in the Speed Reference Ramp function.   
					17   
					18   
					Unused   
					Auto mode req,   
					lan   
					Request to enable auto reference mode that can be   
					used in the Speed Reference Generation function.   
					19-23   
					24   
					Unused   
					GP lan req bit 1   
					General purpose request that can be used by a number   
					of functions.   
					25   
					26   
					27   
					28   
					29   
					30   
					31   
					GP lan req bit 2   
					GP lan req bit 3   
					GP lan req bit 4   
					GP lan req bit 5   
					GP lan req bit 6   
					GP lan req bit 7   
					GP lan req bit 8   
					General purpose request that can be used by a number   
					of functions.   
					General purpose request that can be used by a number   
					of functions.   
					General purpose request that can be used by a number   
					of functions.   
					General purpose request that can be used by a number   
					of functions.   
					General purpose request that can be used by a number   
					of functions.   
					General purpose request that can be used by a number   
					of functions.   
					General purpose request that can be used by a number   
					of functions.   
					3-40 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				LAN Feedbacks   
					Several LAN feedback signals are averaged versions of internal drive signals. The   
					signals that fall in this category appear in dedicated floating point feedback channels.   
					The averaging is sequential (not rolling), and the averaging time is specified by   
					parameter LAN fbk avg time.   
					The following table specifies the LAN Signal Map feedback signals.   
					Page &   
					Element   
					Data   
					Type   
					Signal   
					Description   
					1 
					1 
					Boolean   
					bits   
					Boolean feedbacks. See table   
					below for definition of feedback   
					bits.   
					1 
					2 
					Fault number   
					Integer   
					Number of active fault. Priority is   
					given to trip faults over alarms, and   
					to the earliest detected fault.   
					1 
					1 
					1 
					3 
					4 
					5 
					Averaged Speed reg fbk. RPM   
					Speed feedback,   
					lan   
					Floating   
					point   
					Motor torque, lan   
					Floating   
					point   
					Averaged Torque calced, unfil.   
					Newton-meters or Pound-feet   
					Motor current,   
					lan   
					Floating   
					point   
					Averaged Motor current, unfil x   
					2 . RMS amps   
					1 
					1 
					6 
					7 
					Unused   
					GP lan fbk reg 1   
					Floating   
					point   
					General purpose feedback   
					selected by GP lan fbk reg 1 sel.   
					1 
					2 
					2 
					8 
					1 
					2 
					GP lan fbk reg 2   
					Motor power, lan   
					Floating   
					point   
					General purpose feedback   
					selected by GP lan fbk reg 2 sel.   
					Floating   
					point   
					Averaged motor output power.   
					Kilowatts or Horsepower   
					Motor voltage,   
					lan   
					Floating   
					point   
					Averaged motor voltage. RMS   
					volts   
					2 
					2 
					3-6   
					7 
					Unused   
					GP lan fbk reg 3   
					Floating   
					point   
					General purpose feedback   
					selected by GP lan fbk reg 3 sel.   
					2 
					8 
					GP lan fbk reg 4   
					Floating   
					point   
					General purpose feedback   
					selected by GP lan fbk reg 4 sel.   
					The general purpose feedback signals GP lan fbk reg 1, …, GP lan fbk reg 4 are not   
					averaged. The following parameters are used to select the general purpose feedbacks.   
					• 
					• 
					• 
					• 
					GP lan fbk reg 1 sel   
					GP lan fbk reg 2 sel   
					GP lan fbk reg 3 sel   
					GP lan fbk reg 4 sel   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-41   
				The following table specifies the LAN Signal Map feedback bits that appear in Page   
					1, Element 1 of the feedback signal map.   
					Bit   
					Signal   
					Description   
					0 
					Heartbeat fbk, lan   
					No faults active   
					Trip fault active   
					Local fault string   
					Heartbeat signal to validate LAN health.   
					No trip faults or alarms are active in the drive.   
					Trip fault is active in the drive.   
					1 
					2 
					3 
					Local hardware permissive fault is active in the drive.   
					System fault   
					string   
					System hardware permissive fault is active in the   
					drive.   
					4 
					5 
					6 
					7 
					Ready to run   
					Bridge is on   
					Running   
					Drive is ready and will respond to a run request.   
					Bridge power is enabled.   
					Drive is running: References and regulators are   
					enabled.   
					8 
					Run active   
					Jog active   
					Drive is running in response to a run request.   
					Drive is running in response to a jog request.   
					Result of X stop requests.   
					9 
					10   
					11   
					X stop active   
					Flux enable   
					status   
					Net commanded flux is established.   
					12   
					13   
					14   
					Reverse mode   
					active   
					Result of reverse mode requests.   
					Torque mode   
					active   
					Speed/Torque Regulator function is regulating torque.   
					Speed/Torque Regulator function is regulating speed.   
					Inner torque regulator is in limit.   
					Speed mode   
					active   
					15   
					16   
					17   
					In cur or trq limit   
					Unused   
					MA cont enable   
					stat   
					Real or modeled contactor status.   
					18   
					19   
					Auto mode active   
					Zero speed active   
					Speed reference source is auto reference.   
					Speed feedback (Speed reg fbk) is below zero speed   
					level (Zero speed level).   
					20-22   
					23   
					Unused   
					Lan diag fbk bit 1   
					Drive has diagnostic information for the diagnostic   
					master.   
					24   
					25   
					26   
					27   
					28   
					29   
					30   
					31   
					GP lan fbk bit 1   
					GP lan fbk bit 2   
					GP lan fbk bit 3   
					GP lan fbk bit 4   
					GP lan fbk bit 5   
					GP lan fbk bit 6   
					GP lan fbk bit 7   
					GP lan fbk bit 8   
					General purpose feedback selected by GP lan fbk bit   
					1 sel.   
					General purpose feedback selected by GP lan fbk bit   
					2 sel.   
					General purpose feedback selected by GP lan fbk bit   
					3 sel.   
					General purpose feedback selected by GP lan fbk bit   
					4 sel.   
					General purpose feedback selected by GP lan fbk bit   
					5 sel.   
					General purpose feedback selected by GP lan fbk bit   
					6 sel.   
					General purpose feedback selected by GP lan fbk bit   
					7 sel.   
					General purpose feedback selected by GP lan fbk bit   
					8 sel.   
					3-42 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				The following parameters are used to select the general purpose feedback bits.   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					GP lan fbk bit 1 sel   
					GP lan fbk bit 2 sel   
					GP lan fbk bit 3 sel   
					GP lan fbk bit 4 sel   
					GP lan fbk bit 5 sel   
					GP lan fbk bit 6 sel   
					GP lan fbk bit 7 sel   
					GP lan fbk bit 8 sel   
					Related diagrams   
					• 
					• 
					• 
					Drive LAN Signal Map (SigMap_LAN)   
					Drive LAN Boolean Signals (bits 0-15) (SigMap_Bit1)   
					Drive LAN Boolean Signals (bits 16-31) (SigMap_Bit2)   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-43   
				Motor Control Functions   
					Motor Control Overview   
					The Innovation Induction motor control algorithm utilizes a Flux-Vector control   
					strategy. The motor control features include the following:   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Motor torque, flux and thermal models   
					Online motor parameters adaptation   
					Voltage and current regulators   
					Voltage feedback offset correction   
					Power-Dip ride through control   
					Tach and Tachless mode operation   
					Tach loss detection   
					Current limit and Motor pull-out limit   
					Automatic field-weakening control   
					Torque Compensation   
					Cross-over voltage control   
					Motor Equivalent Circuit parameter information is required for the motor controller.   
					These parameters can be obtained by running the Motor Control Tuneup wizard   
					during commissioning of the drive. The motor parameters will change due to motor   
					temperature variations; because of this, on-line parameter adaptation, motor thermal   
					model and torque compensation schemes (shown in diagram, Motor Control   
					(Ovr_MCtrl) are incorporated in the motor control to enable accurate tracking of   
					torque, flux and calculated speed.   
					Motor electrical models are used to form feedforward models, feedback torque, flux   
					and speed calculations.   
					The induction motor controller can be used with or without tachometer. It can also be   
					configured to operate in tachometer control mode with automatic switch over to   
					Tachless control upon detection of a Tach-loss situation (comparison between model   
					calculated speed and actual speed feedback signal).   
					Field flux control can be manipulated by Flux ref ratio (inputs to motor control   
					shown in the diagram, Motor Control (Ovr_MCtrl). However, if the inverter output   
					voltage approaches its limit (Crossover Voltage) by increasing speed, an automatic   
					field-weakening control will take action to limit the output voltage (by reducing flux   
					command) to the Crossover Voltage level.   
					Current limits in the drive are affected by motor Pull-out torque capability, Power   
					Dip Protection control, and user current limit setting (as shown in diagram Motor   
					Control Interface (Core)). Motor pullout limit normally occurs when a large torque is   
					demanded in deep field-weakening operating region.   
					Related diagrams   
					• 
					• 
					Motor Control Interface (Core)   
					Motor Control (Ovr_MCtrl)   
					3-44 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				Flux Curve   
					The Flux Curve describes the relationship between the induction motor voltage and   
					current. Specifically, each point of the curve specifies the voltage that is measured at   
					the motor terminals for a particular excitation current, under no load conditions at the   
					nameplate frequency.   
					Function configuration   
					The Flux Curve consists of five voltage and current points. Two parameters are   
					associated with each point. The following table lists the parameters that configure the   
					Flux Curve.   
					Parameter   
					Description   
					Flux curve voltage 1   
					Flux curve voltage 2   
					Flux curve voltage 3   
					Flux curve voltage 4   
					Flux curve voltage 5   
					Flux curve amps 1   
					Flux curve amps 2   
					Flux curve amps 3   
					Flux curve amps 4   
					Flux curve amps 5   
					No load voltage for data point 1. RMS volts   
					No load voltage for data point 2. RMS volts   
					No load voltage for data point 3. RMS volts   
					No load voltage for data point 4. RMS volts   
					No load voltage for data point 5. RMS volts   
					No load current for data point 1. RMS amps   
					No load current for data point 2. RMS amps   
					No load current for data point 3. RMS amps   
					No load current for data point 4. RMS amps   
					No load current for data point 5. RMS amps   
					The parameters listed above specify the curve if they contain meaningful values. If   
					all the parameters are set to <No Value>, then the control uses the curve measured   
					during Motor Control Tuneup.   
					Function description   
					Often the motor data sheet contains four or five voltage and current measurements   
					that specify the Flux Curve. The voltage points are generally labeled "VNL" and the   
					current points "INL".   
					If five data points are available on the motor data sheet, they can be entered directly   
					into the configuration parameters. Flux curve voltage 1 and Flux curve amps 1   
					represent the smallest voltage and current, and Flux curve voltage 5 and Flux curve   
					amps 5 represent the largest voltage and current.   
					If fewer than five data points are available on the motor data sheet, the highest data   
					points should contain meaningful values and the lowest data points should be set to   
					<No Value>. To reset one of the parameters to <No Value>, highlight the value and   
					press the Delete key.   
					If the curve data is not available, all the configuration parameters should be set to   
					<No Value>, and the Flux Curve should be determined using the Motor Control   
					Tuneup.   
					GEH-6385 Reference and Troubleshooting, 2300 V Drives   
					Chapter 3 Paramters/Functions • 3-45   
				Leakage Inductance Curve   
					The Leakage Inductance Curve describes the relationship between motor leakage   
					flux and torque current. The motor data sheet does not provide Leakage Inductance   
					Curve information. The characteristics of the curve can be obtained experimentally   
					or by running the Motor Control Tuneup.   
					Line Transfer   
					The Line Transfer function transfers a motor from the drive to the utility line and   
					captures a motor from the utility line to return control to the drive. In addition to the   
					parameters and variables documented here the Line Transfer Tuneup wizard is   
					provided to simplify and automate many of the tasks required to correctly   
					commission this function. To use this function you must have the necessary   
					contactors and operator interfaces as described in the "Innovation Series Line   
					Transfer Application Guide". The following figure summarizes the power one-line of   
					a basic line transfer application.   
					Utility   
					Customer's   
					Utiltiy Feed   
					Contactor   
					Motor   
					Drive Output   
					"MA" Contactor   
					Innovation Drive   
					& Transformer   
					Line   
					Reactor   
					Figure 1   
					General operation   
					The following table specifies the general configuration parameters for this function.   
					Parameter   
					Description   
					Selects the source of the utility line reference. The use of the   
					internal line reference (ILR) is encouraged unless conditions exist   
					such that it is not possible to accurately predict the utility phase and   
					magnitude at the motor from the source voltage applied to the drive.   
					See the "Innovation Series Line Transfer Application Guide" for a   
					complete discussion of issues related to line reference selection.   
					Line reference   
					The following table specifies the general status variables for this function.   
					Variable   
					Description   
					Line xfer enabled   
					Indicates that the line transfer function is enabled.   
					Transfer MA   
					request   
					Indicates that the transfer/capture sequence has requested the   
					MA contactor to close.   
					3-46 • Chapter 3 Paramters/Functions   
					Innovation Series Medium Voltage GP Type - G Drives GEH-6385   
				 |