| 
		 Lenox Air Conditioner Elite Series XP16 Units Heat Pumps User Manual  | 
	
| 	
		 INSTALLATION   
					INSTRUCTIONS   
					E20 Lennox Industries Inc.   
					Dallas, Texas, USA   
					Elite® Series XP16 Units   
					HEAT PUMPS   
					506640−01   
					12/10   
					These instructions are intended as a   
					Litho U.S.A.   
					general guide and do not supersede   
					local codes in any way. Consult   
					authorities having jurisdiction before   
					installation.   
					Supersedes 11/10   
					TABLE OF CONTENTS   
					Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . .   
					
					Model Number Identification . . . . . . . . . . . . . . . . . . . .   
					Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					Typical Parts Arrangement . . . . . . . . . . . . . . . . . . . . . .   
					Caps and Fasteners Torque Requirements . . . . . . . .   
					Operating Gauge Set and Service Valves . . . . . . . . .   
					Recovering Refrigerant from Existing System . . . . .   
					New Outdoor Unit Placement . . . . . . . . . . . . . . . . . . .   
					Removing and Installing Panels . . . . . . . . . . . . . . . . .   
					Line Set Requirements . . . . . . . . . . . . . . . . . . . . . . . . .   
					
					
					
					
					
					
					
					
					
					
					
					RETAIN THESE INSTRUCTIONS FOR FUTURE   
					REFERENCE   
					NOTICE TO INSTALLER   
					BRAZING LINE SET TO SERVICE VALVES   
					It is imperative to follow the brazing technique illustrated starting on   
					
					
					Indoor Refrigerant Metering Device Removal and   
					
					WARNING   
					Improper installation, adjustment, alteration, service or   
					maintenance can cause personal injury, loss of life, or   
					damage to property.   
					
					
					
					
					
					Installation and service must be performed by a licensed   
					professional installer (or equivalent) or a service agency.   
					Servicing and Weighing In Refrigerant for Units   
					
					IMPORTANT   
					
					
					
					
					
					
					The Clean Air Act of 1990 bans the intentional venting of   
					refrigerant (CFCs, HFCs, and HCFCs) as of July 1,   
					1992. Approved methods of recovery, recycling or   
					reclaiming must be followed. Fines and/or incarceration   
					may be levied for noncompliance.   
					Shipping and Packing List   
					IMPORTANT   
					This unit must be matched with an indoor coil as   
					specified in Lennox XP16 Engineering Handbook.   
					Coils previously charged with HCFC−22 must be   
					flushed.   
					Check unit for shipping damage. Consult last carrier   
					immediately if damage is found.   
					1 − Assembled outdoor unit   
					General   
					The XP16 outdoor unit uses HFC−410A refrigerant. This   
					unit must be installed with a matching indoor blower coil   
					and line set as outlined in the XP16 Lennox Engineering   
					Handbook. Elite® Series outdoor units are designed for   
					use in check / expansion valve (CTXV) systems only and   
					are not to be used with other refrigerant flow control   
					devices. An indoor coil check / expansion valve approved   
					for use with HFC−410A must be ordered separately and   
					installed prior to operating the unit.   
					CAUTION   
					Physical contact with metal edges and corners while   
					applying excessive force or rapid motion can result in   
					personal injury. Be aware of, and use caution when   
					working near these areas during installation or while   
					servicing this equipment.   
					12/10   
					506640−01   
					Page 1   
					*2P1210*   
					*P506640-01*   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Typical Unit Parts Arrangement   
					FOR COIL SENSOR (RT21)   
					LOCATION SEE DETAIL A   
					COMPRESSOR   
					DUAL RUN CAPACITOR (C12)   
					(−024, −036 AND −048 ONLY)   
					SINGLE RUN CAPACITOR (C1)   
					(−060 ONLY)   
					DEMAND DEFROST   
					CONTROL (A108)   
					DISCHARGE LINE   
					SENSOR (RT28)   
					REVERSING   
					VALVE (L1)   
					TRUE SUCTION   
					PORT   
					HIGH PRESSURE   
					SWITCH (S4)   
					EXPANSION VALVE   
					SENSING BULB   
					CHECK /   
					EXPANSION   
					VALVE   
					LIQUID VALVE AND GAUGE   
					PORT / LIQUID LINE   
					CONNECTIONS   
					LIQUID LINE   
					BI−FLOW FILTER   
					DRIER   
					GROUND   
					LUG   
					LOW PRESSURE   
					SWITCH (S87)   
					SINGLE POLE   
					CONTACTOR   
					(K1)   
					AMBIENT   
					TEMPERATURE   
					SENSOR (RT13)   
					VAPOR VALVE AND GAUGE PORT /   
					SUCTION LINE CONNECTIONS   
					DETAIL A   
					XP16−048   
					COIL SENSOR − EIGHT HAIRPIN   
					UP FROM THE BOTTOM ON   
					INSIDE ROW.   
					XP16−036   
					XP16−060   
					COIL SENSOR −   
					SIXTH HAIRPIN UP   
					FROM THE BOTTOM   
					COIL SENSOR − NINTH   
					HAIRPIN UP FROM THE   
					BOTTOM ON INSIDE   
					ROW.   
					ON INSIDE ROW.   
					XP16−024   
					COIL SENSOR −THIRD   
					HAIRPIN DOWN FROM   
					THE TOP ON INSIDE   
					ROW.   
					Figure 1. Unit Parts Arrangement   
					Caps and Fasteners Torque Requirements   
					When servicing or repairing HVAC equipment and   
					components, ensure the fasteners are appropriately   
					
					fasteners.   
					IMPORTANT   
					Only use Allen wrenches of sufficient hardness (50Rc −   
					Rockwell Harness Scale minimum). Fully insert the   
					wrench into the valve stem recess.   
					Table 1. Torque Requirements   
					Parts   
					Recommended Torque   
					Service valve stems are factory−torqued (from 9 ft−lbs for   
					small valves, to 25 ft−lbs for large valves) to prevent   
					refrigerant loss during shipping and handling. Using an   
					Allen wrench rated at less than 50Rc risks rounding or   
					breaking off the wrench, or stripping the valve stem   
					recess.   
					Service valve cap   
					Sheet metal screws   
					Machine screws #10   
					Compressor bolts   
					Gauge port seal cap   
					8 ft.− lb.   
					11 NM   
					2 NM   
					16 in.− lb.   
					28 in.− lb.   
					90 in.− lb.   
					8 ft.− lb.   
					3 NM   
					10 NM   
					11 NM   
					See the Lennox Service and Application Notes   
					Corp.0807−L5 (C−08−1) for further details and   
					information.   
					Page 3   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Operating Gauge Set and Service Valves   
					USING MANIFOLD GAUGE SET   
					IMPORTANT   
					To prevent stripping of the various caps used, the   
					appropriately sized wrench should be used and fitted   
					snugly over the cap before tightening.   
					When checking the system charge, only use a manifold   
					gauge set that features low−loss anti−blow back fittings.   
					Manifold gauge set used for HFC−410A refrigerant   
					systems must be capable of handling the higher system   
					operating pressures. The manifold gauges should be rated   
					for:   
					OPERATING SERVICE VALVES   
					The liquid and vapor line service valves are used for   
					refrigerant recovery, flushing, leak testing, evacuating,   
					weighing in refrigerant and optimizing system charge.   
					S 
					S 
					S 
					High side ꢀ Pressure range of 0 − 800 pound−force per   
					square inch gauge (psig)   
					Low side ꢀ Use with 30" vacuum to 250 psig with   
					dampened speed to 500 psig   
					Each valve is equipped with a service port which has a   
					factory−installed valve core. Figure 2 provides information   
					on how to access and operate both angle− and ball−type   
					service valves.   
					Manifold gauge set hoses must be rated for use to 800   
					psig of pressure with a 4000 psig burst rating.   
					Operating Angle−Type Service Valve:   
					1. Remove stem cap with an appropriately sized wrench.   
					INSERT HEX−HEAD   
					EXTENSION HERE   
					2 
					2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16"   
					for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open   
					the service valve.   
					SERVICE PORT CAP   
					TO INDOOR   
					UNIT   
					SERVICE PORT CORE   
					TO OUTDOOR   
					UNIT   
					SERVICE PORT   
					CORE   
					(VALVE STEM SHOWN OPEN)   
					INSERT HEX WRENCH HERE   
					VALVE STEM   
					SHOWN   
					CLOSED   
					TO INDOOR   
					UNIT   
					REMOVE   
					STEM CAP   
					1 
					When service valve stem is in the CLOSED position,   
					the service port is open to the line set and indoor unit.   
					STEM CAP   
					TO OUTDOOR UNIT   
					To Access Service Port:   
					When service valve is OPEN, the service port is open to line set,   
					indoor and outdoor unit.   
					1/6 TURN   
					A service port cap protects the service port core from   
					contaminationand serves as the primary leak seal.   
					Operating Ball−Type Service Valve:   
					12   
					6 
					1 
					5 
					11   
					10   
					1. Remove service port cap with an appropriately sized   
					wrench.   
					2 
					1. Remove stem cap with an appropriately sized wrench.   
					2. Use an appropriately sized wrenched to open.   
					9 
					3 
					2. Connect gauge set to service port.   
					4 
					8 
					7 
					A 
					To open rotate stem   
					counterclockwise   
					90°.   
					3. When testing is completed, replace service port cap and   
					tighten as follows:   
					TO INDOOR UNIT   
					S 
					
					B 
					To close rotate stem   
					clockwise 90°.   
					S 
					Reinstall Stem Cap:   
					Without torque wrench: Finger tighten and use an appropriately sized   
					wrench to turn an additional 1/6 turn clockwise.   
					1/12 TURN   
					BALL (SHOWN CLOSED)   
					VALVE STEM   
					2 
					Stem cap protects the valve stem from damage and   
					serves as the primary seal. Replace the stem cap and   
					tighten as follows:   
					12   
					1 
					5 
					11   
					10   
					SERVICE PORT   
					2 
					SERVICE PORT CORE   
					SERVICE PORT CAP   
					9 
					3 
					S 
					S 
					With Torque Wrench: Finger tighten and then   
					
					4 
					8 
					7 
					6 
					Without Torque Wrench: Finger tighten and use an   
					REMOVE   
					STEM CAP   
					TO OUTDOOR UNIT   
					appropriatelysized wrench to turn an additional 1/12 turn clockwise.   
					1 
					NOTE ꢀ A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.   
					Figure 2. Angle and Ball−Type Service Valves   
					Page 4   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Recovering Refrigerant from Existing System   
					CONNECT MANIFOLD GAUGE SET   
					DISCONNECT POWER   
					Connect a manifold gauge set, clean recovery cylinder and a   
					recovery machine to the service ports of the existing unit..   
					Disconnect all power to the existing outdoor unit at the disconnect   
					switch and/or main fuse box/breaker panel.   
					2 
					1 
					NOTE ꢀ Use the recovery machine instructions to make   
					the correct manifold gauge set connections for recovery   
					refrigerant.The illustration below is a typical connection.   
					MAIN FUSE   
					BOX/BREAKER   
					PANEL   
					MANIFOLD GAUGES   
					DISCONNECT   
					SWITCH   
					RECOVERY MACHINE   
					LOW   
					HIGH   
					OUTDOOR UNIT   
					CLEAN RECOVERY   
					CYLINDER   
					RECOVERING REFRIGERANT   
					3 
					Remove existing HCFC−22 refrigerant using one of the following procedures:   
					METHOD 2 LIMITATIONS   
					METHOD 1:   
					Use Method 1 if the existing outdoor unit is not equipped with shut−off valves, or   
					if the unit is not operational and you plan to use the existing HCFC−22 to flush   
					the system.   
					NOTE ꢀ When using Method 2, the listed devices   
					below could prevent full system charge recovery into   
					the outdoor unit:   
					Recover all HCFC−22 refrigerant from the existing system using a recovery   
					machine and clean recovery cylinder. Check gauges after shutdown to confirm   
					that the entire system is completely void of refrigerant.   
					S 
					Outdoor unit’s high or low−pressure switches (if   
					applicable) when tripped can cycle the   
					compressor OFF.   
					S 
					S 
					Compressor can stop pumping due to tripped   
					internal pressure relief valve.   
					METHOD 2:   
					Use Method 2 if the existing outdoor unit is equipped with manual shut−off valves,   
					and you plan to use new HCFC−22 refrigerant to flush the system.   
					Compressor has internal vacuum protection that   
					is designed to unload the scrolls (compressor   
					stops pumping) when the pressure ratio meets a   
					certain value or when the suction pressure is as   
					high as 20 psig. (Compressor suction   
					pressuresshould never be allowed to go into   
					a vacuum. Prolonged operation at low suction   
					pressures will result in overheating of the   
					scrolls and permanent damage to the scroll   
					tips, drive bearings and internal seals.)   
					Perform the following task:   
					A 
					Start the existing HCFC−22 system in the cooling mode and close the liquid line   
					valve.   
					B 
					Use the compressor to pump as much of the existing HCFC−22 refrigerant into   
					the outdoor unit until the outdoor system is full. Turn the outdoor unit main power   
					OFF and use a recovery machine to remove the remaining refrigerant from the   
					system.   
					NOTE ꢀ It may be necessary to bypass the low pressure switches (if equipped) to   
					ensure complete refrigerant evacuation.   
					Once the compressor can not pump down to a lower   
					pressure due to any of the above mentioned system   
					conditions, shut off the vapor valve. Turn OFF the main   
					power to unit and use a recovery machine to recover   
					any refrigerant left in the indoor coil and line set.   
					C 
					D 
					When the low side system pressures reach 0 psig, close the vapor line valve.   
					Check gauges after shutdown to confirm that the valves are not allowing   
					refrigerantto flow back into the low side of the system.   
					Figure 3. Refrigerant Recovery   
					IMPORTANT   
					The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance,   
					service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.   
					WARNING   
					Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.   
					Failure to follow this warning may result in personal injury or death.   
					Page 5   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				New Outdoor Unit Placement   
					If additional elevation is necessary, raise the unit by   
					extending the height of the unit support feet. This may be   
					achieved by using a 2 inch (50.8mm) schedule 40 female   
					threaded adapter.   
					CAUTION   
					In order to avoid injury, take proper precaution when lift-   
					ing heavy objects.   
					The specified coupling will fit snuggly into the recessed   
					portion of the feet. Use additional 2 inch (50.8mm)   
					Schedule 40 male threaded adaptors which can be   
					threaded into the female threaded adaptors to make   
					additional adjustments to the level of the unit.   
					Remove existing outdoor unit prior to placement of new   
					
					mounting slab, platforms or supports. Refer to figure 4 for   
					mandatory installation clearance requirements.   
					NOTE ꢀ Keep the height of extenders short enough to   
					ensure a sturdy installation. If it is necessary to extend   
					further, consider a different type of field−fabricated   
					framework that is sturdy enough for greater heights.   
					POSITIONING CONSIDERATIONS   
					Consider the following when positioning the unit:   
					S 
					Some localities are adopting sound ordinances based   
					on the unit’s sound level registered from the adjacent   
					property, not from the installation property. Install the   
					unit as far as possible from the property line.   
					ROOF MOUNTING   
					Install the unit a minimum of 6 inches (152 mm) above the   
					roof surface to avoid ice build−up around the unit. Locate   
					the unit above a load bearing wall or area of the roof that   
					can adequately support the unit. Consult local codes for   
					
					mounting considerations.   
					S 
					When possible, do not install the unit directly outside   
					a window. Glass has a very high level of sound   
					transmission. For proper placement of unit in relation   
					to a window see the provided illustration in figure 5,   
					detail A.   
					PLACING UNIT ON SLAB   
					When installing unit at grade level, the top of the slab   
					should be high enough above grade so that water from   
					higher ground will not collect around the unit. The slab   
					should have a slope tolerance as described in figure 5,   
					detail B.   
					NOTICE   
					Roof Damage!   
					This system contains both refrigerant and oil. Some   
					rubber roofing material may absorb oil and cause the   
					rubber to swell when it comes into contact with oil. The   
					rubber will then bubble and could cause leaks. Protect   
					the roof surface to avoid exposure to refrigerant and oil   
					during service and installation. Failure to follow this   
					notice could result in damage to roof surface.   
					NOTE ꢀ If necessary for stability, anchor unit to slab as   
					
					ELEVATING THE UNIT   
					Units are outfitted with elongated support feet as illustrated   
					
					MINIMUM CLEARANCE   
					ABOVE UNIT   
					CLEARANCE ON ALL SIDES ꢀ INCHES (MILLIMETERS)   
					6 (152)   
					ACCESS PANEL   
					NOTES:   
					S 
					S 
					Clearance to one of the other three   
					sides must be 36 inches (914mm).   
					30 (762)   
					48 (1219)   
					12 (305)   
					Clearance to one of the remaining   
					two sides may be 12 inches   
					(305mm) and the final side may be   
					6 inches (152mm).   
					LINE SET   
					CONNECTIONS   
					36 (914)   
					MINIMUM CLEARANCE BETWEEN TWO UNITS   
					24   
					(610)   
					Figure 4. Installation Clearances   
					Page 6   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				ꢀ Outside Unit Placement   
					DETAIL A   
					Install unit away from windows.   
					ꢀ Slab Mounting at Ground Level   
					DETAIL B   
					Install unit level or, if on a slope, maintain slope tolerance of two (2)   
					degrees (or two inches per five feet [50 mm per 1.5 m]) away from   
					building structure.   
					BUILDING   
					STRUCTURE   
					MOUNTING   
					SLAB   
					GROUND LEVEL   
					TWO 90° ELBOWS INSTALLED IN LINE SET WILL   
					REDUCE LINE SET VIBRATION.   
					Elevated Slab Mounting   
					DETAIL C ꢀ   
					ꢀ Slab Side Mounting   
					DETAIL D   
					using Feet Extenders   
					#10 1/2" LONG SELF−DRILLING   
					SHEET METAL SCREWS   
					COIL   
					STABILIZING BRACKET (18 GAUGE   
					METAL ꢀ 2" WIDTH; HEIGHT AS   
					REQUIRED)   
					BASE PAN   
					#10 1−1/4" LONG HEX HD SCREW   
					AND FLAT WASHER   
					CORNER POST   
					Concrete slab ꢀ use two plastic anchors (hole   
					drill 1/4")   
					BASE   
					Wood or plastic slab ꢀ no plastic anchor (hole   
					drill 1/8")   
					Stabilizing bracket (18 gauge metal ꢀ 2" (50.8mm) width; height as required); bend to form   
					right angle as exampled below.   
					LEG DETAIL   
					2" (50.8MM) SCH 40   
					FEMALE THREADED   
					ADAPTER   
					ꢀ Roof Top Mounting   
					DETAIL F   
					If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be   
					constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24   
					inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated.   
					2" (50.8MM) SCH 40   
					MALE THREADED   
					ADAPTER   
					PREVAILING WINTER WINDS   
					Use additional 2" SCH 40 male threaded adapters which   
					can be threaded into the female threaded adapters to   
					make additional adjustments to the level of the unit.   
					WIND BARRIER   
					INLET AIR   
					ꢀ Deck Top Mounting   
					DETAIL E   
					MINIMUM ONE   
					PER SIDE   
					One bracket per side   
					(minimum). For extra   
					INLET AIR   
					INLET AIR   
					stability, two brackets per   
					side, two inches (51mm)   
					from each corner.   
					SAME FASTENERS AS   
					SLAB SIDE MOUNTING.   
					FOR EXTRA   
					STABILITY   
					INLET AIR   
					Figure 5. Placement, Slab Mounting and Stabilizing Unit   
					Page 7   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Removing and Installing Panels   
					LOUVERED PANEL REMOVAL   
					Remove the louvered panels as follows:   
					IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR   
					ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.   
					1. Remove two screws, allowing the panel to swing open   
					slightly.   
					PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR   
					ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.   
					2. Hold the panel firmly throughout this procedure. Rotate   
					bottom corner of panel away from hinged corner post until   
					lower three tabs clear the slots as illustrated in detail B.   
					SCREW   
					HOLES   
					3. Move panel down until lip of upper tab clears the top slot in   
					corner post as illustrated in detail A.   
					LIP   
					LOUVERED PANEL INSTALLATION   
					Position the panel almost parallel with the unit as illustrated in   
					detail D with the screw side as close to the unit as possible.   
					Then, in a continuous motion:   
					Detail A   
					Detail B   
					1. Slightly rotate and guide the lip of top tab inward as   
					illustrated in detail A and C; then upward into the top   
					slot of the hinge corner post.   
					2. Rotate panel to vertical to fully engage all tabs.   
					3. Holding the panel’s hinged side firmly in place, close   
					the right−hand side of the panel, aligning the screw   
					holes.   
					4. When panel is correctly positioned and aligned, insert   
					the screws and tighten.   
					ROTATE IN THIS DIRECTION;   
					THEN DOWN TO REMOVE   
					PANEL   
					HOLD DOOR FIRMLY TO THE HINGED   
					SIDE TO MAINTAIN   
					FULLY−ENGAGED TABS   
					ANGLE MAY BE TOO   
					EXTREME   
					Detail C   
					PREFERRED ANGLE   
					FOR INSTALLATION   
					Detail D   
					MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO   
					PARALLEL WITH THE UNIT AS POSSIBLE) WHILE   
					INSTALLING PANEL.   
					Figure 6. Removing and Installing Panels   
					WARNING   
					To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:   
					While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause   
					injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g.,   
					being bent or scratched).   
					While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause   
					panels to be blown around and battered.   
					Page 8   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Line Set Requirements   
					This section provides information on: installation of new or   
					replacement line set.   
					S 
					S 
					Model (XP16) and size of unit (e.g. −036).   
					Line set diameters for the unit being installed as listed   
					
					S 
					S 
					S 
					Adding Polyol ester oil requirements   
					New or replacement line set installation   
					Using existing line set.   
					S 
					Number of elbows vertical rise or drop in the piping.   
					USING EXISTING LINE SET   
					ADDING POLYOL ESTER OIL REQUIREMENTS   
					Things to consider:   
					S 
					S 
					S 
					Liquid line that meter the refrigerant, such as RFC1   
					liquid line, must not be used in this application.   
					IMPORTANT   
					Mineral oils are not compatible with HFC−410A. If oil   
					must be added, it must be a Polyol Ester oil.   
					Existing line set of proper size as listed in table 2 may   
					be reused.   
					If system was previously charged with HCFC−22   
					refrigerant, then existing line set must be flushed (see   
					
					The compressor is charged with sufficient Polyol Ester oil   
					(POE) for line set lengths up to 50 feet. Recommend   
					adding oil to system based on the amount of refrigerant   
					charge in the system. Systems with 20 pounds or less of   
					refrigerant required no oil to be added.   
					If existing line set is being used, then proceed to Brazing   
					
					For systems over 20 pounds − add one ounce for every five   
					(5) pounds of HFC−410A refrigerant.   
					IMPORTANT   
					Recommended topping−off POE oils are Mobil EAL   
					ARCTIC 22 CC or ICI EMKARATEt RL32CF.   
					Lennox highly recommends changing line set when   
					converting the existing system from HCFC−22 to   
					HFC−410A. If that is not possible and the line set is the   
					proper size as reference in table 2, use the procedure   
					outlined under Flushing Line Set and Indoor Coil on page   
					13.   
					NEW OR REPLACEMENT LINE SET INSTALLATION   
					Field refrigerant piping consists of both liquid and vapor   
					lines from the outdoor unit to the indoor coil. Use Lennox   
					L15 (sweat, non−flare) series line set, or field−fabricated   
					refrigerant line sizes as specified in table 2.   
					IMPORTANT   
					If refrigerant lines are routed through a wall, then seal and   
					isolate the opening so vibration is not transmitted to the   
					building. Pay close attention to line set isolation during   
					installation of any HVAC system. When properly isolated   
					from building structures (walls, ceilings. floors), the   
					refrigerant lines will not create unnecessary vibration and   
					subsequent sounds. See figure 7 for recommended   
					installation practices.   
					If this unit is being matched with an approved line set   
					or indoor unit coil which was previously charged with   
					mineral oil, or if it is being matched with a coil which   
					was manufactured before January of 1999, the coil   
					and line set must be flushed prior to installation. Take   
					care to empty all existing traps. Polyol ester (POE) oils   
					are used in Lennox units charged with HFC−410A   
					refrigerant. Residual mineral oil can act as an   
					insulator, preventing proper heat transfer. It can also   
					clog the expansion device, and reduce the system   
					performance and capacity.   
					NOTE ꢀ When installing refrigerant lines longer than 50   
					feet, see the Lennox Refrigerant Piping Design and   
					Fabrication Guidelines, CORP. 9351−L9, or contact   
					Lennox Technical Support Product Applications for   
					assistance. To obtain the correct information from Lennox,   
					be sure to communicate the following information:   
					Failure to properly flush the system per the   
					instructions below will void the warranty.   
					Table 2. Refrigerant Line Set ꢀ Inches (mm)   
					Field Connections   
					Recommended Line Set   
					Model   
					Liquid Line   
					Suction Line   
					Liquid Line   
					Suction Line   
					L15 Line Set   
					XP16−024−230   
					XP16−036−230   
					XP16−048−230   
					XP16−060−230   
					3/8" (10 mm)   
					3/8" (10 mm)   
					3/8" (10 mm)   
					3/4" (19 mm)   
					3/8" (10 mm)   
					3/4" (19 mm)   
					L15−41 ꢀ 15 ft. − 50 ft. (4.6m − 15 m)   
					7/8" (22 mm)   
					3/8" (10 mm)   
					3/8" (10 mm)   
					7/8" (22 mm)   
					L15−65 ꢀ 15 ft. − 50 ft. (4.6 m − 15 m)   
					Field Fabricated   
					1−1/8" (29 mm)   
					1−1/8" (29 mm)   
					NOTE ꢀ Some applications may required a field provided 7/8" to 1−1/8" adapter   
					Page 9   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Line Set Isolation ꢀ The following illustrations are examples of proper refrigerant line set isolation:   
					REFRIGERANT LINE SET ꢀ INSTALLING   
					VERTICAL RUNS (NEW CONSTRUCTION SHOWN)   
					REFRIGERANT LINE SET ꢀ TRANSITION   
					FROM VERTICAL TO HORIZONTAL   
					NOTE ꢀ Insulate liquid line when it is routed through areas where the   
					surrounding ambient temperature could become higher than the   
					temperatureof the liquid line or when pressure drop is equal to or greater   
					than 20 psig.   
					ANCHORED HEAVY NYLON   
					WIRE TIE OR AUTOMOTIVE   
					AUTOMOTIVE   
					MUFFLER-TYPE HANGER   
					MUFFLER-TYPE HANGER   
					OUTSIDE WALL   
					LIQUID LINE   
					VAPOR LINE   
					WALL   
					STUD   
					WIRE TIE   
					INSIDE WALL   
					STRAP   
					WOOD BLOCK   
					BETWEEN STUDS   
					STRAP LIQUID LINE TO   
					VAPOR LINE   
					NON−CORROSIVE   
					METAL SLEEVE   
					WIRE TIE   
					LIQUID LINE   
					NON−CORROSIVE   
					METAL SLEEVE   
					WOOD BLOCK   
					WIRE TIE   
					VAPOR LINE − WRAPPED   
					IN ARMAFLEX   
					STRAP   
					REFRIGERANT LINE SET ꢀ INSTALLING   
					HORIZONTAL RUNS   
					SLEEVE   
					To hang line set from joist or rafter, use either metal strapping material   
					or anchored heavy nylon wire ties.   
					WIRE TIE (AROUND   
					VAPOR LINE ONLY)   
					VAPOR LINE WRAPPED   
					WITH ARMAFLEX   
					8 FEET (2.43 METERS)   
					OUTSIDE   
					WALL   
					STRAPPING   
					MATERIAL (AROUND   
					VAPOR LINE ONLY)   
					FLOOR JOIST OR   
					LIQUID   
					LINE   
					ROOF RAFTER   
					TAPE OR   
					WIRE TIE   
					8 FEET (2.43 METERS)   
					PVC   
					PIPE   
					CAULK   
					NON−CORROSIVE   
					METAL SLEEVE   
					FIBERGLASS   
					INSULATION   
					STRAP THE VAPOR LINE TO THE JOIST   
					OR RAFTER AT 8 FEET (2.43 METERS)   
					INTERVALS THEN STRAP THE LIQUID   
					LINE TO THE VAPOR LINE.   
					TAPE OR   
					WIRE TIE   
					NOTE ꢀ Similar installation practices should be used if line set is   
					to be installed on exterior of outside wall.   
					FLOOR JOIST OR   
					ROOF RAFTER   
					Figure 7. Line Set Installation   
					Page 10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Brazing Connections   
					
					WARNING   
					IMPORTANT   
					Polyol Ester (POE) oils used with HFC−410A   
					refrigerant absorb moisture very quickly. It is very   
					important that the refrigerant system be kept closed   
					as much as possible. DO NOT remove line set caps   
					or service valve stub caps until you are ready to make   
					connections.   
					Allow braze joint to cool before removing the wet rag   
					from the service valve. Temperatures above 250ºF can   
					damage valve seals.   
					IMPORTANT   
					Use silver alloy brazing rods with 5% minimum silver   
					alloy for copper−to−copper brazing. Use 45% minimum   
					alloy for copper−to−brass and copper−to−steel brazing.   
					WARNING   
					Danger of fire. Bleeding the refrigerant   
					charge from only the high side may result   
					in pressurization of the low side shell and   
					suction tubing. Application of a brazing   
					torch to a pressurized system may result   
					in ignition of the refrigerant and oil   
					mixture − Check the high and low   
					pressures before applying heat.   
					WARNING   
					Fire, Explosion and Personal Safety   
					Hazard.   
					Failure to follow this warning could   
					result in damage, personal injury or   
					death.   
					Never use oxygen to pressurize or   
					purge refrigeration lines. Oxygen,   
					when exposed to a spark or open   
					flame, can cause fire and/or an ex-   
					plosion, that could result in property   
					damage, personal injury or death.   
					WARNING   
					When using a high pressure gas such as   
					dry nitrogen to pressurize a refrigeration   
					or air conditioning system, use a   
					regulator that can control the pressure   
					down to 1 or 2 psig (6.9 to 13.8 kPa).   
					CAUTION   
					Brazing alloys and flux contain materials which are   
					hazardous to your health.   
					Avoid breathing vapors or fumes from brazing   
					operations. Perform operations only in well−ventilated   
					areas.   
					Wear gloves and protective goggles or face shield to   
					protect against burns.   
					Wash hands with soap and water after handling brazing   
					alloys and flux.   
					Page 11   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				CAP AND CORE REMOVAL   
					CUT AND DEBUR   
					Cut ends of the refrigerant lines square (free from nicks or dents)   
					and debur the ends. The pipe must remain round. Do not crimp end   
					of the line.   
					Remove service cap and core from   
					both the suction / vapor and liquid line   
					service ports.   
					2 
					1 
					CUT AND DEBUR   
					SERVICE PORT   
					CAP   
					SERVICE   
					PORT   
					CORE   
					LINE SET SIZE MATCHES   
					SERVICE VALVE CONNECTION   
					SERVICE   
					PORT   
					CORE   
					SERVICE VALVE   
					CONNECTION   
					SERVICE   
					PORT CAP   
					COPPER TUBE   
					STUB   
					LIQUID LINE SERVICE   
					VALVE   
					SUCTION / VAPOR LINE   
					SERVICE VALVE   
					REDUCER   
					LINE SET SIZE IS SMALLER   
					THAN CONNECTION   
					DO NOT CRIMP SERVICE VALVE   
					CONNECTOR WHEN PIPE IS   
					SMALLER THAN CONNECTION   
					REFRIGERANT LINE   
					ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE   
					VALVES   
					3 
					Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction /   
					vapor line service port valve.   
					A 
					B 
					C 
					Connect gauge set low pressure side to   
					liquid line service valve (service port).   
					USE REGULATOR TO FLOW   
					NITROGEN AT 1 TO 2 PSIG.   
					LOW   
					HIGH   
					Connect gauge set center port to bottle of   
					nitrogenwith regulator.   
					Remove core from valve in suction / vapor   
					line service port to allow nitrogen to escape.   
					ATTACH   
					GAUGES   
					B 
					SUCTION / VAPOR SERVICE PORT MUST BE   
					OPEN TO ALLOW EXIT POINT FOR NITROGEN   
					SUCTION /   
					VAPOR LINE   
					SERVICE   
					VALVE   
					C 
					VAPOR LINE   
					OUTDOOR   
					UNIT   
					INDOOR   
					UNIT   
					NITROGEN   
					LIQUID LINE SERVICE   
					VALVE   
					WHEN BRAZING LINE SET TO   
					SERVICE VALVES, POINT FLAME   
					AWAY FROM SERVICE VALVE.   
					LIQUID LINE   
					A 
					Figure 8. Brazing Procedures   
					WARNING   
					When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning   
					system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).   
					Page 12   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				WRAP SERVICE VALVES   
					To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use   
					additionalwater saturated cloths underneath the valve body to protect the base paint.   
					4 
					FLOW NITROGEN   
					Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and   
					out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections   
					5 
					6 
					BRAZE LINE SET   
					Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water   
					saturated cloths must remain water saturated throughout the brazing and cool−down process.   
					LIQUID LINE SERVICE VALVE   
					WHEN BRAZING LINE SET TO   
					SERVICE VALVES, POINT FLAME   
					AWAY FROM SERVICE VALVE.   
					IMPORTANT ꢀ Allow braze joint to cool. Apply   
					additional water saturated cloths to help cool brazed   
					joint. Do not remove water saturated cloths until piping   
					has cooled. Temperatures above 250ºF will damage   
					valve seals.   
					WATER SATURATED   
					CLOTH   
					LIQUID LINE   
					WARNING   
					SUCTION / VAPOR LINE   
					SERVICE VALVE   
					1. FIRE, PERSONAL INJURY, OR PROPERTY   
					DAMAGE may result if you do not wrap a water   
					saturated cloth around both liquid and suction line   
					service valve bodies and copper tube stub while   
					brazing in the line set! The braze, when complete,   
					must be quenched with water to absorb any residual   
					heat.   
					WHEN BRAZING LINE SET TO   
					SERVICE VALVES, POINT FLAME   
					AWAY FROM SERVICE VALVE.   
					2. Do not open service valves until refrigerant lines and   
					indoor coil have been leak−tested and evacuated.   
					Refer to procedures provided in this supplement.   
					SUCTION / VAPOR LINE   
					WATER SATURATED   
					CLOTH   
					PREPARATION FOR NEXT STEP   
					After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both   
					service valves to cool piping. Once piping is cool, remove all water saturated cloths.   
					7 
					Figure 9. Brazing Procedures (continued)   
					Page 13   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil   
					Flushing is only required when the existing system used HCFC−22 refrigerant. If the existing system used HFC−410a, then   
					remove the original indoor coil metering device and proceed to Installing New Indoor Metering Device on page 15.   
					TYPICAL EXISTING FIXED ORIFICE   
					REMOVAL PROCEDURE (UNCASED   
					COIL SHOWN)   
					TYPICAL EXISTING EXPANSION VALVE REMOVAL   
					PROCEDURE (UNCASED COIL SHOWN)   
					OR   
					1B   
					1A   
					STUB END   
					TWO PIECE PATCH PLATE   
					(UNCASED COIL ONLY)   
					LIQUID LINE   
					ORIFICE   
					HOUSING   
					CHECK   
					EXPANSION   
					VALVE   
					DISTRIBUTOR TUBES   
					LIQUID LINE ORIFICE HOUSING   
					DISTRIBUTOR   
					TUBES   
					® 
					TEFLON   
					RING   
					® 
					TEFLON RING   
					FIXED ORIFICE   
					BRASS NUT   
					® 
					TEFLON   
					RING   
					SENSING   
					LINE   
					DISTRIBUTOR   
					ASSEMBLY   
					DISTRIBUTOR   
					ASSEMBLY   
					EQUALIZER   
					LINE   
					REMOVE AND DISCARD   
					® 
					WHITE TEFLON SEAL   
					(IF PRESENT)   
					LIQUID LINE ASSEMBLY   
					(INCLUDES STRAINER)   
					LIQUID LINE   
					ASSEMBLY WITH   
					BRASS NUT   
					A 
					B 
					On fully cased coils, remove the coil access and plumbing panels.   
					Remove any shipping clamps holding the liquid line and distributor as-   
					sembly.   
					MALE EQUALIZER   
					LINE FITTING   
					VAPOR   
					LINE   
					C 
					Using two wrenches, disconnect liquid line from liquid line orifice hous-   
					ing. Take care not to twist or damage distributor tubes during this pro-   
					cess.   
					LIQUID   
					LINE   
					SENSING BULB   
					A 
					B 
					On fully cased coils, remove the coil access and plumbing panels.   
					D 
					E 
					Remove and discard fixed orifice, valve stem assembly if present and   
					® 
					Teflon washer as illustrated above.   
					Remove any shipping clamps holding the liquid line and distributor   
					assembly.   
					Use a field−provided fitting to temporary reconnect the liquid line to the   
					indoor unit’s liquid line orifice housing.   
					C 
					Disconnect the equalizer line from the check expansion valve   
					equalizer line fitting on the vapor line.   
					D 
					E 
					Remove the vapor line sensing bulb.   
					CONNECT GAUGES AND EQUIPMENT FOR   
					FLUSHING PROCEDURE   
					Disconnect the liquid line from the check expansion valve at the liquid   
					line assembly.   
					2 
					INVERTED HCFC−22   
					GAUGE   
					MANIFOLD   
					F 
					Disconnect the check expansion valve from the liquid line orifice   
					housing.Take care not to twist or damage distributor tubes during this   
					process.   
					CYLINDER CONTAINS   
					CLEAN HCFC−22 TO BE   
					USED FOR FLUSHING.   
					A 
					® 
					G 
					H 
					Remove and discard check expansion valve and the two Teflon rings.   
					LOW   
					HIGH   
					1 
					Use a field−provided fitting to temporary reconnect the liquid line to the   
					indoor unit’s liquid line orifice housing.   
					NEW   
					OUTDOOR   
					UNIT   
					VAPOR LINE   
					SERVICE VALVE   
					FLUSHING LINE SET   
					OPENED   
					CLOSED   
					The line set and indoor unit coil must be flushed with at least the   
					same amount of clean refrigerant that previously charged the   
					system. Check the charge in the flushing cylinder before   
					proceeding.   
					EXISTING   
					INDOOR   
					UNIT   
					3 
					B 
					LIQUID LINE SERVICE   
					VALVE   
					A 
					Set the recovery machine for liquid recovery and start the   
					recovery machine. Open the gauge set valves to allow the   
					RECOVERY   
					CYLINDER   
					TANK   
					RETURN   
					rBecovery machine to pull a vacuum on the existing system line   
					set and indoor unit coil.   
					C 
					B 
					Invert the cylinder of clean HCFC−22 and open its valve to allow   
					liquid refrigerant to flow into the system through the vapor line   
					valve. Allow the refrigerant to pass from the cylinder and through   
					the line set and the indoor unit coil before it enters the recovery   
					machine.   
					INLET   
					D 
					DISCHARGE   
					RECOVERY MACHINE   
					A 
					Inverted HCFC−22 cylinder with clean refrigerant to the vapor service   
					valve.   
					C 
					D 
					After all of the liquid refrigerant has been recovered, switch the   
					recovery machine to vapor recovery so that all of the HCFC−22   
					vapor is recovered. Allow the recovery machine to pull down to 0   
					the system.   
					B 
					C 
					HCFC−22 gauge set (low side) to the liquid line valve.   
					HCFC−22 gauge set center port to inlet on the recovery machine with an   
					empty recovery tank to the gauge set.   
					Close the valve on the inverted HCFC−22 drum and the gauge   
					set valves. Pump the remaining refrigerant out of the recovery   
					machine and turn the machine off.   
					D 
					Connect recovery tank to recovery machines per machine instructions.   
					Figure 10. Removing Indoor Refrigerate Metering Device and Flushing Procedures   
					Page 14   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Installing New Indoor Metering Device   
					This outdoor unit is designed for use in HFC−410A systems that use a check / expansion valve metering device (purchased   
					separately) at the indoor coil.   
					See the Lennox XP16 Engineering Handbook for approved check / expansion valve kit match−ups. The check / expansion   
					valve device can be installed either internal or external to the indoor coil. In applications where an uncased coil is being   
					installed in a field−provided plenum, install the check / expansion valve in a manner that will provide access for field servicing   
					
					1/2 Turn   
					A 
					B 
					Remove the field−provided fitting that temporarily   
					reconnectedthe liquid line to the indoor unit’s distributor   
					assembly.   
					INDOOR EXPANSION VALVE INSTALLATION   
					TWO PIECE   
					12   
					PATCH PLATE   
					(Uncased Coil Shown)   
					1 
					11   
					10   
					® 
					(UNCASED   
					STUB   
					END   
					2 
					Install one of the provided Teflon rings around the   
					stubbed end of the check / expansion valve and lightly   
					lubricate the connector threads and expose surface of   
					LIQUID LINE   
					ORIFICE   
					COIL ONLY)   
					9 
					3 
					CHECK /   
					EXPANSION   
					VALVE   
					4 
					8 
					HOUSING   
					5 
					7 
					® 
					6 
					DISTRIBUTOR   
					TUBES   
					the Teflon ring with refrigerant oil.   
					® 
					TEFLON   
					RING   
					C 
					D 
					E 
					Attach the stubbed end of the expansion valve to the   
					liquid line orifice housing. Finger tighten and use an   
					appropriatelysized wrench to turn an additional 1/2 turn   
					clockwise as illustrated in the figure above, or 20 ft−lb.   
					® 
					® 
					Place the remaining Teflon washer around the other   
					end of the check / expansion valve. Lightly lubricate   
					TEFLON   
					RING   
					SENSING   
					LINE   
					® 
					connector threads and expose surface of the Teflon   
					ring with refrigerant oil.   
					DISTRIBUTOR   
					ASSEMBLY   
					EQUALIZER   
					LINE   
					Attach the liquid line assembly to the check / expansion   
					valve. Finger tighten and use an appropriately sized   
					wrench to turn an additional 1/2 turn clockwise as   
					illustratedin the figure above or 20 ft−lb.   
					LIQUID LINE   
					ASSEMBLY WITH   
					BRASS NUT   
					SENSING BULB INSTALLATION   
					A 
					Attach the vapor line sensing bulb in the proper   
					orientationas illustrated to the right using the clamp and   
					screws provided.   
					1/8 Turn   
					MALE EQUALIZER LINE   
					FITTING (SEE   
					VAPOR   
					LINE   
					EQUALIZER LINE   
					INSTALLATION FOR   
					FURTHER DETAILS)   
					NOTE ꢀ Confirm proper thermal contact between vapor line   
					and expansion bulb before insulating the sensing bulb once   
					installed.   
					12   
					1 
					5 
					11   
					10   
					2 
					LIQUID LINE   
					9 
					3 
					4 
					8 
					B 
					Connect the equalizer line from the check / expansion   
					valve to the equalizer vapor port on the vapor line. Finger   
					tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated   
					below.   
					7 
					Sensing bulb insulation is   
					required if mounted external to   
					the coil casing.   
					6 
					ON LINES SMALLER THAN   
					7/8", MOUNT SENSING   
					BULB AT EITHER THE 3 OR   
					9 O’CLOCK POSITION.   
					VAPOR LINE   
					EQUALIZER LINE INSTALLATION   
					Remove and discard either the flare seal cap or flare nut with   
					copper flare seal bonnet from the equalizer line port on the vapor   
					line as illustrated in the figure to the right.   
					12   
					BULB   
					BULB   
					FLARE SEAL CAP   
					FLARE NUT   
					VAPOR LINE   
					ON 7/8" AND LARGER LINES,   
					MOUNT SENSING BULB AT   
					EITHER THE 4 OR 8 O’CLOCK   
					POSITION. NEVER MOUNT ON   
					BOTTOM OF LINE.   
					COPPER FLARE   
					SEAL BONNET   
					OR   
					12   
					MALE BRASS EQUALIZER   
					LINE FITTING   
					BULB   
					BULB   
					NOTE ꢀ NEVER MOUNT ON BOTTOM OF LINE.   
					VAPOR LINE   
					Figure 11. Installing Indoor Check / Expansion Valve   
					Page 15   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Leak Test Line Set and Indoor Coil   
					IMPORTANT   
					Leak detector must be capable of sensing HFC refrigerant.   
					CONNECT GAUGE SET   
					A 
					Connect an HFC−410A manifold gauge set high pressure hose to the   
					vapor valve service port.   
					LOW   
					HIGH   
					MANIFOLD GAUGE SET   
					NOTE ꢀ Normally, the high pressure hose is connected to the liquid   
					line port. However, connecting it to the vapor port better protects the   
					manifoldgauge set from high pressure damage.   
					B 
					With both manifold valves closed, connect the cylinder of HFC−410A   
					refrigerantto the center port of the manifold gauge set.   
					OUTDOOR UNIT   
					NOTE ꢀ Later in the procedure, the   
					HFC−410A container will be replaced by   
					the nitrogen container.   
					A 
					B 
					TO VAPOR   
					SERVICE VALVE   
					NITROGEN   
					HFC−410A   
					Figure 12. Manifold Gauge Set Connections for Leak Testing   
					TEST FOR LEAKS   
					side of the manifold gauge set. Disconnect the   
					HFC−410A cylinder.   
					After the line set has been connected to the indoor and   
					outdoor units, check the line set connections and indoor   
					unit for leaks. Use the following procedure to test for leaks:   
					3. Connect a cylinder of dry nitrogen with a pressure   
					regulating valve to the center port of the manifold   
					gauge set.   
					1. With both manifold valves closed, connect the cylinder   
					of HFC−410A refrigerant to the center port of the   
					manifold gauge set. Open the valve on the HFC−410A   
					cylinder (vapor only).   
					4. Adjust dry nitrogen pressure to 150 psig (1034 kPa).   
					Open the valve on the high side of the manifold gauge   
					set in order to pressurize the line set and the indoor unit.   
					2. Open the high pressure side of the manifold to allow   
					HFC−410A into the line set and indoor unit. Weigh in   
					a trace amount of HFC−410A. [A trace amount is a   
					maximum of two ounces (57 g) refrigerant or three   
					pounds (31 kPa) pressure]. Close the valve on the   
					HFC−410A cylinder and the valve on the high pressure   
					5. After a few minutes, open one of the service valve   
					ports and verify that the refrigerant added to the   
					system earlier is measurable with a leak detector.   
					6. After leak testing disconnect gauges from service   
					ports.   
					Page 16   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Evacuating Line Set and Indoor Coil   
					Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any   
					gas that will not condense under temperatures and pressures present during operation of an air conditioning system.   
					Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and   
					compressor parts.   
					CONNECT GAUGE SET   
					NOTE ꢀ Remove cores from service valves (if not already done).   
					LOW   
					HIGH   
					1 
					A 
					Connect low side of manifold gauge set   
					with 1/4 SAE in−line tee to vapor line   
					service valve   
					B 
					C 
					D 
					Connect high side of manifold gauge   
					set to liquid line service valve   
					OUTDOOR   
					UNIT   
					MANIFOLD   
					GAUGE SET   
					A34000 1/4 SAE TEE WITH   
					SWIVEL COUPLER   
					Connect micron gauge available   
					connector on the 1/4 SAE in−line tee.   
					Connect the vacuum pump (with   
					vacuum gauge) to the center port of the   
					manifold gauge set. The center port   
					line will be used later for both the   
					HFC−410A and nitrogen containers.   
					A 
					500   
					MICRON   
					GAUGE   
					C 
					TO VAPOR   
					SERVICE VALVE   
					NITROGEN   
					HFC−410A   
					B 
					VACUUM PUMP   
					TO LIQUID LINE   
					SERVICE VALVE   
					D 
					EVACUATE THE SYSTEM   
					RECOMMEND   
					MINIMUM 3/8" HOSE   
					A 
					B 
					Open both manifold valves and start the vacuum pump.   
					Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).   
					2 
					NOTE ꢀ During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure   
					indicates a relatively large leak. If this occurs, repeat the leak testing procedure.   
					NOTE ꢀ The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of   
					pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.   
					C 
					When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:   
					S 
					S 
					S 
					S 
					S 
					S 
					Close manifold gauge valves   
					Close valve on vacuum pump and turn off vacuum pump   
					Disconnect manifold gauge center port hose from vacuum pump   
					Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.   
					Open manifold gauge valves to break the vacuum in the line set and indoor unit.   
					Close manifold gauge valves.   
					D 
					E 
					Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the   
					dry nitrogen from the line set and indoor unit.   
					Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the   
					absolutepressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump   
					and closing the manifold gauge valves.   
					F 
					When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an   
					upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and   
					indoor unit.   
					1/6 TURN   
					G 
					Perform the following:   
					S 
					S 
					S 
					S 
					Close manifold gauge valves.   
					Shut off HFC−410A cylinder.   
					12   
					1 
					5 
					11   
					7 
					2 
					4 
					10   
					Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core   
					tool while maintaining a positive system pressure.   
					9 
					3 
					8 
					Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.   
					6 
					Figure 13. Evacuating Line Set and Indoor Coil   
					Page 17   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Electrical Connections   
					IMPORTANT   
					Use a thermocouple or thermistor electronic vacuum   
					gauge that is calibrated in microns. Use an instrument   
					capable of accurately measuring down to 50 microns.   
					In the U.S.A., wiring must conform with current local codes   
					and the current National Electric Code (NEC). In Canada,   
					wiring must conform with current local codes and the current   
					Canadian Electrical Code (CEC).   
					Refer to the furnace or air handler installation instructions   
					for additional wiring application diagrams and refer to unit   
					nameplate for minimum circuit ampacity and maximum   
					overcurrent protection size.   
					WARNING   
					Danger of Equipment Damage. Avoid deep vacuum   
					operation. Do not use compressors to evacuate a   
					system. Extremely low vacuums can cause internal   
					arcing and compressor failure. Damage caused by   
					deep vacuum operation will void warranty.   
					24VAC TRANSFORMER   
					Use the transformer provided with the furnace or air   
					handler for low-voltage control power (24VAC − 40 VA   
					minimum)   
					INSTALL THERMOSTAT   
					SIZE CIRCUIT AND INSTALL DISCONNECT   
					SWITCH   
					Install room thermostat (ordered separately) on an inside wall   
					2approximately in the center of the conditioned area and 5 feet   
					(1.5m) from the floor. It should not be installed on an outside wall   
					or where it can be affected by sunlight or drafts.   
					1 
					Refer to the unit nameplate for minimum circuit ampacity, and   
					maximum fuse or circuit breaker (HACR per NEC). Install power   
					wiring and properly sized disconnect switch.   
					THERMOSTAT   
					MAIN FUSE BOX/   
					BREAKER PANEL   
					DISCONNECT   
					SWITCH   
					5 FEET   
					(1.5M)   
					NOTE ꢀ 24VAC, Class II circuit connections are made in the control   
					panel.   
					NOTE ꢀ Units are approved for use only with copper conductors.   
					Ground unit at disconnect switch or to an earth ground.   
					WARNING   
					Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and   
					local codes.   
					Line voltage is present at all components when unit is not in operation on units with single-pole contactors.   
					Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power   
					supplies.   
					Page 18   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				HIGH VOLTAGE FIELD WIRING   
					LOW VOLTAGE CONNECTIONS   
					LOW VOLTAGE (24V) FIELD WIRING   
					3 
					WIRE RUN LENGTH   
					AWG# INSULATION TYPE   
					LESS THAN 100’ (30 METERS)   
					MORE THAN 100’ (30 METERS)   
					18   
					16   
					TEMPERATURE RATING   
					35ºC MINIMUM.   
					NOTE − For proper voltages, select thermostat wire (control wires)   
					gauge per table above.   
					NOTE − Do not bundle any excess 24VAC control wires inside   
					control box.   
					C 
					A 
					B 
					C 
					D 
					Run 24VAC control wires through cutout with grommet.   
					Run 24VAC control wires through wire tie.   
					Make 24VAC control wire connections.   
					Tighten wire tie to security 24V control wiring.   
					NOTE − Wire tie provides low voltage wire strain relief and to maintain   
					separation of field installed low and high voltage circuits.   
					CUTOUT WITH   
					A 
					GROMMET   
					TIGHTEN WIRE TIE   
					24V CONTROL WIRES   
					D 
					B 
					Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated. See figures 14 and 15 for typical field   
					connections when connecting unit to either a CBX32MV or CBX40UHV in non−communicating mode. For connections to other Lennox air handlers   
					or furnaces, see the ComfortSense® 7000 installation instruction for further match component wiring illustrations.   
					HIGH VOLTAGE POWER SUPPLY CONNECTIONS   
					OUTDOOR UNIT   
					CONTROL BOX   
					4 
					GROUND   
					G 
					NOTE − Any excess high voltage field wiring   
					should be trimmed and secured away from   
					any low voltage field wiring.   
					L1   
					L2   
					NOTE − To facilitate a conduit, a cutout is lo-   
					cated in the bottom of the control box. Connect   
					conduit to the control box using a proper con-   
					duit fitting.   
					CONDUIT   
					CUTOUT   
					CONDUIT   
					Page 19   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CBX32MV   
					OR   
					CBX40UHV   
					COMFORTSENSET   
					HEAT PUMP UNIT   
					(TWO−STAGE)   
					7000   
					X2658 OUTDOOR SENSOR IS REQUIRED FOR OUTDOOR   
					TEMPERATURE DISPLAY, DEW POINT CONTROL, HEAT PUMP AND   
					DUAL FUEL BALANCE POINTS.   
					1 
					R 
					R 
					R 
					CONNECTED ON UNIT WITH LSOM. RESISTOR KIT (CAT # 47W97)   
					IS REQUIRED WHEN CONNECTING THE COMFORTSENSE 7000   
					WITH THE LSOM 2.   
					2 
					W3   
					H 
					W2   
					W2   
					W1   
					O 
					3 
					FIELD PROVIDED JUMPER BETWEEN Y2 OUT BL ON HEAT PUMP   
					TO Y2 ON CBX40UHV.   
					1 
					W1   
					W1   
					O. D.   
					SENSOR   
					(X2658)   
					AIR   
					HANDLER   
					CONTROL   
					O 
					O 
					L 
					2 
					L 
					IMPORTANT − USE CARE WHEN CUTTING LINKS TO   
					PREVENT DAMAGE TO CONTROL. SEE CBX40UHV   
					INSTALLATION INSTRUCTION FOR FURTHER DETAILS.   
					Y1   
					Y1   
					Y2   
					Y1   
					Y2   
					G 
					Y1−Y2   
					2−STAGE   
					COMPR   
					CUT ON−BOARD LINK Y1−Y2 FOR TWO−STAGE HP   
					CUT ON−BOARD LINK R −O.   
					G 
					Y2   
					OUT   
					BL   
					D 
					DS   
					Y2   
					3 
					R−O   
					HEAT   
					PUMP   
					T 
					T 
					B 
					C 
					R−DS   
					DEHUM   
					OR   
					C 
					C 
					CUT ON−BOARD LINK R−DS WHEN DEHUMIDIFICATION TERMINAL IS USED.   
					HARMONY   
					Figure 14. Typical Field Wiring ꢀ Heat Pump Application with CBX32MV or CBX40UHV   
					CBX32MV OR   
					CBX40UHV   
					COMFORTSENSEt   
					OUTDOOR UNIT   
					7000 THERMOSTAT   
					RED   
					RED   
					OUTDOOR   
					SENSOR   
					FAN RELAY (NOT REQUIRED   
					WITH SINGLE−SPEED   
					OUTDOOR FAN)   
					BLACK   
					PURPLE   
					T 
					T 
					PURPLE   
					(X2658)   
					BLACK   
					YELLOW   
					BLUE   
					BROWN (NOT USED FOR APPLICATIONS WITHOUT LSOM   
					BLUE (NOT REQUIRED FOR SINGLE STAGE)   
					AIR   
					HANDLER   
					CONTROL   
					IMPORTANT − USE CARE WHEN CUTTING LINKS TO   
					PREVENT DAMAGE TO CONTROL. SEE CBX40UHV   
					INSTALLATION INSTRUCTION FOR FURTHER DETAILS.   
					Y1−Y2   
					2−STAGE   
					COMPR   
					RESISTOR KIT (CAT # 47W97) IS REQUIRED   
					WHEN CONNECTING THE COMFORTSENSE   
					7000 WITH THE LSOM 2.   
					CUT ON−BOARD LINK Y1−Y2 FOR TWO−STAGE A/C ONLY   
					CUT ON−BOARD LINK R −O.   
					R−O   
					HEAT   
					PUMP   
					R−DS   
					DEHUM   
					OR   
					CUT ON−BOARD LINK R−DS WHEN DEHUMIDIFICATION   
					TERMINAL IS USED.   
					HARMONY   
					® 
					Figure 15. Heat Pump Application ꢀ Humiditrol and Second−Stage Outdoor Fan Relay Wiring with   
					CBX32MV or CBX40UHV   
					Page 20   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Figure 16. Typical Unit Wiring Diagram (−024, −036 and −048 Only)   
					Page 21   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Figure 17. Typical Unit Wiring Diagram (−060 Only)   
					Page 22   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Figure 18. Typical Factory Wiring Diagram (No Field Modifications)   
					have consulted with the power company and the   
					voltage condition has been corrected.   
					Unit Start−Up   
					6. Open both the liquid and vapor line service valves to   
					release the refrigerant charge contained in outdoor   
					unit into the system.   
					IMPORTANT   
					If unit is equipped with a crankcase heater, it should be   
					energized 24 hours before unit start−up to prevent   
					compressor damage as a result of slugging.   
					
					preparation.   
					OPEN BOTH VAPOR AND LIQUID SERVICE   
					VALVE STEMS TO RELEASE   
					REFRIGERANT FROM OUTDOOR UNIT TO   
					SYSTEM.   
					UNIT START−UP   
					1. Rotate fan to check for binding.   
					2. Inspect all factory− and field−installed wiring for loose   
					connections.   
					3. Verify that the manifold gauge set is connected as   
					
					positioned near the liquid line service port as illustrated   
					
					subcooling method for optimizing the system   
					refrigerant charge.   
					NO   
					YES   
					GO TO SERVICE AND WEIGH   
					IN REFRIGERANT CHARGE   
					FOR OUTDOOR UNITS   
					DELIVERED VOID OF CHARGE   
					
					GO TO OPTIMIZING SYSTEM   
					REFRIGERANT CHARGE ON   
					
					4. Replace the stem caps and tighten to the value listed   
					in table 1.   
					5. Check voltage supply at the disconnect switch. The   
					voltage must be within the range listed on the unit’s   
					nameplate. If not, do not start the equipment until you   
					Figure 19. Outdoor Unit Factory Charge   
					Page 23   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Service and Weigh In Refrigerant for Outdoor Units Delivered Void of Charge   
					The following procedures are only required if it has been determine that the new outdoor unit is void of charge. Skip to the   
					next section if refrigerant charge is present.   
					LEAK CHECK, REPAIR AND EVACUATE   
					2. Connect the manifold gauge set’s low pressure side to   
					the true suction port.   
					If the outdoor unit is void of refrigerant, clean the system   
					using the procedure described below.   
					3. Connect the manifold gauge set’s high pressure side   
					to the liquid line service port.   
					1. Leak check system using procedures provided on   
					
					4. Connect the center hose of the gauge set to acylinder   
					of HFC−410A and purge the hose. Then, place the   
					cylinder upside down on a scale.   
					2. Evacuate the system using procedure provided in   
					
					5. Check that fan rotates freely.   
					3. Use nitrogen to break the vacuum and install a new   
					filter drier in the system.   
					6. Inspect all factory− and field−installed wiring for loose   
					connections.   
					4. Evacuate the system again using procedure in figure   
					12.   
					7. Open the high side manifold gauge valve and weigh in   
					liquid refrigerant. Use figure 20 in calculating the   
					correct weigh−in charge.   
					CONNECT MANIFOLD GAUGE SET AND WEIGH IN   
					CHARGE   
					8. Close manifold gauge valves.   
					9. Monitor the system to determine the amount of   
					moisture remaining in the oil. It may be necessary to   
					replace the bi−flow filter drier several times to achieve   
					the required dryness level. If system dryness is not   
					verified, the compressor will fail in the future.   
					After the evacuation procedure, reconnect the manifold   
					
					
					required for initial system weigh in charging.   
					1. Close manifold gauge set valves and connect the   
					center hose to a cylinder of HFC−410A. Set for liquid   
					phase charging.   
					10. Continue to Optimizing System Refrigerant Charge   
					
					subcooling method.   
					WEIGH−IN CHARGING   
					CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE   
					If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total   
					refrigerantcharge:   
					Additional charge specified per indoor   
					
					Adjust amount. for variation in line set   
					length listed on line set length table below.   
					Amount specified on   
					nameplate   
					Total Charge   
					+ 
					= 
					+ 
					Refrigerant Charge per Line Set Length   
					OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET   
					(4.6 M) LINE SET*   
					LIQUID LINE SET DIAMETER   
					3/8" (9.5 MM)   
					3 OUNCE PER 5’ (85 G PER 1.5 M)   
					*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract   
					this amount.   
					NOTE ꢀ Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature   
					of the liquid line or when pressure drop is equal to or greater than 20 psig.   
					NOTE ꢀ The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.   
					Figure 20. Using HFC−410A Weigh In Method   
					Page 24   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				MANIFOLD GAUGE SET   
					HIGH   
					LOW   
					GAUGE SET   
					B 
					CONNECTIONS FOR OPTIMIZING SYSTEM CHARGE   
					TRUE SUCTION PORT   
					CONNECTION   
					OUTDOOR UNIT   
					NOTE ꢀ Refrigerant tank should be   
					turned right−side−up to deliver vapor   
					during charge optimizing procedure.   
					REFRIGERANT   
					TANK   
					A 
					CHARGE IN   
					LIQUID PHASE   
					DIGITAL SCALE   
					TO LIQUID   
					LINE SERVICE   
					VALVE   
					TEMPERATURE SENSOR   
					(LIQUID LINE)   
					C 
					D 
					TEMPERATURE SENSOR (USE FOR   
					SUBCOOLING METHOD)   
					A 
					B 
					C 
					D 
					Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.   
					Connect the manifold gauge set’s low pressure side to the true suction port.   
					INSIDE OUTDOOR UNIT   
					Connect the manifold gauge set’s high pressure side to the liquid line service port.   
					Position temperature sensor on liquid line near liquid line service port (use only for subcooling method).   
					Figure 21. Gauge Set Connections for Adding Refrigerant   
					DISTRIBUTOR   
					OUTDOOR UNIT   
					NOTE − ARROWS INDICATE DIRECTION   
					OF REFRIGERANT FLOW   
					REVERSING VALVE   
					CHECK / EXPANSION   
					VALVE   
					OUTDOOR   
					COIL   
					INDOOR UNIT   
					BI−FLOW FILTER / DRIER   
					MUFFLER   
					TRUE SUCTION   
					PORT   
					VAPOR   
					SERVICE   
					PORT   
					LIQUID LINE   
					SERVICE PORT   
					COMPRESSOR   
					CHECK / EXPANSION VALVE   
					INDOOR   
					COIL   
					NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and   
					indoor coil. Use true suction port to measure vapor pressure during charging.   
					Figure 22. Heat Pump Cooling Cycle   
					Page 25   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Optimizing System Refrigerant Charge   
					This section provides instructions on optimizing the   
					system charge. This section includes:   
					efficiency. Make any air flow adjustments before   
					continuing with the optimizing procedure.   
					S 
					S 
					S 
					S 
					Optimizing procedure   
					Adjusting indoor airflow   
					Using subcooling method   
					5. Use subcooling method to optimize the system   
					
					ADJUSTING INDOOR AIRFLOW   
					Approved matched components, targeted subcooling   
					(SC) values and add charge values   
					Heating Mode Indoor Airflow Check   
					(Only use when indoor unit has electric heat)   
					S 
					Normal operating pressures   
					Temperature pressures   
					S 
					Indoor blower airflow (CFM) may be calculated by   
					energizing electric heat and measuring:   
					OPTIMIZING PROCEDURE   
					S 
					S 
					Temperature rise between the return air and supply air   
					temperatures at the indoor coil blower unit,   
					1. Move the low−side manifold gauge hose from the   
					vapor line service valve to the true suction port (see   
					
					Measuring voltage supplied to the unit,   
					S 
					Measuring amperage being drawn by the heat unit(s).   
					2. Set the thermostat for either cooling or heating   
					demand. Turn on power to the indoor unit and close   
					the outdoor unit disconnect switch to start the unit.   
					Then, apply the measurements taken in the following   
					formula to determine CFM:   
					Amps x Volts x 3.41   
					CFM =   
					1.08 x Temperature rise (F)   
					3. Allow unit to run for five minutes to allow pressures to   
					stabilize.   
					Cooling Mode Indoor Airflow Check   
					Check airflow using the Delta−T (DT) process using figure   
					23.   
					4. Check the airflow as instructed under Adjusting Indoor   
					Airflow to verify or adjust indoor airflow for maximum   
					ADJUSTING INDOOR AIRFLOW   
					DT   
					Temp.   
					of air   
					entering   
					indoor   
					coil ºF   
					1. Determine the desired DTꢀMeasure entering air temper-   
					ature using dry bulb (A) and wet bulb (B). DT is the intersect-   
					ing value of A and B in the table (see triangle).   
					80 24 24 24 23 23 22 22 22 20 19 18 17 16 15   
					78 23 23 23 22 22 21 21 20 19 18 17 16 15 14   
					76 22 22 22 21 21 20 19 19 18 17 16 15 14 13   
					74 21 21 21 20 19 19 18 17 16 16 15 14 13 12   
					72 20 20 19 18 17 17 16 15 15 14 13 12 11 10   
					70 19 19 18 18 17 17 16 15 15 14 13 12 11 10   
					2. Find temperature drop across coilꢀMeasure the coil’s dry   
					bulb entering and leaving air temperatures (A and C). Tem-   
					A 
					perature Drop Formula: (T   
					) = A minus C.   
					Drop   
					Wet−bulb ºF   
					57 58 59 60 61 62 63 64 65 66 67 68 69 70   
					B 
					3. Determine if fan needs adjustmentꢀIf the difference between   
					the measured T and the desired DT (T –DT) is within   
					Drop   
					Drop   
					+3º, no adjustment is needed. See examples: Assume DT =   
					15 and A temp. = 72º, these C temperatures would necessi-   
					tate stated actions:   
					A 
					T 
					Drop   
					C 
					72º   
					19º   
					53º   
					Cº   
					T 
					– 
					DT   
					= 
					ºF ACTION   
					Drop   
					19   
					B 
					air flow   
					air flow   
					53º   
					58º   
					62º   
					– 
					– 
					– 
					15   
					15   
					15   
					= 
					= 
					= 
					4 
					Increase the airflow   
					DRY   
					BULB   
					DRY   
					BULB   
					64º   
					14   
					−1 (within +3º range) no change   
					10   
					−5 Decrease the airflow   
					WET   
					BULB   
					INDOOR   
					COIL   
					All temperatures are   
					expressed in ºF   
					4. Adjust the fan speedꢀSee indoor unit instructions to in-   
					crease/decrease fan speed.   
					Changing air flow affects all temperatures; recheck tempera-   
					tures to confirm that the temperature drop and DT are within   
					+3º.   
					Figure 23. Checking Airflow over Indoor Coil Using Delta−T Formula   
					Page 26   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				OPTIMIZE CHARGE USING SUBCOOLING METHOD   
					1. Check liquid and vapor line pressures. Compare pressures with either second−stage   
					
					guide and expect minor pressures variations. Significant pressure differences may   
					indicate improper charge or other system problem.   
					2. Decide whether to use cooling or heating mode based on current outdoor ambient   
					temperature:   
					USE   
					COOLING   
					MODE   
					A 
					Use COOLING MODE when:   
					60ºF   
					(15ºC)   
					S 
					S 
					Outdoor ambient temperature is 60°F (15.5°C) and above.   
					USE   
					HEATING   
					MODE   
					Indoor return air temperature range is between 70 to 80°F (21−27°C). This   
					temperature range is what the target subcooling values are base upon in   
					
					If indoor return air temperature is not within reference range, set thermostat to   
					cooling mode and a setpoint of 68ºF (20ºC). This should place the outdoor unit   
					into second−stage (high−capacity) cooling mode. When operating and   
					temperature pressures have stabilized, continue to step 3.   
					B 
					Use HEATING MODE when:   
					S 
					S 
					Outdoor ambient temperature is 59°F (15.0°C) and below.   
					Indoor return air temperature range is between 65−75°F (18−24°C). This   
					temperature range is what the target subcooling values are base upon in   
					
					If indoor return air temperature is not within reference range, set thermostat to   
					heating mode and a setpoint of 77ºF (25ºC). This should place the outdoor unit   
					into second−stage (high−capacity) heating mode. When operating and   
					temperature pressures have stabilized, continue to step 3.   
					3. Read the liquid line pressure; then find its corresponding temperature pressure listed   
					
					4. Read the liquid line temperature; record in the LIQº space to the left.   
					SATº   
					LIQº   
					SCº   
					5. Subtract LIQº temperature from SATº temperature to determine subcooling; record   
					it in SCº space to the left..   
					– 
					
					column), also consider any additional charge required for line set lengths longer than   
					15 feet and/or unit matched component combinations (Add Charge column).   
					= 
					7. If subcooling value is:   
					A 
					B 
					GREATER than shown for the applicable unit match component, REMOVE   
					refrigerant;   
					LESS than shown for the applicable unit match component, ADD refrigerant.   
					
					9. Close all manifold gauge set valves and disconnect gauge set from outdoor unit.   
					10. Replace the stem and service port caps and tighten as specified in Operating Service   
					
					11. Recheck voltage while the unit is running. Power must be within range shown on the   
					nameplate.   
					Figure 24. Using HFC−410A Subcooling Method ꢀ Second Stage (High Capacity)   
					Page 27   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				APPROVED MATCHED SYSTEM COMPONENTS, TARGETED SUBCOOLING (SC) VALUES AND   
					ADD CHARGE VALUES   
					Listed below are the approved matched system components (air handlers and indoor coils), targeted subcooling and   
					add charge values for the XP16. This information is also listed on the unit charging sticker located on the outdoor unit   
					access panel.   
					Subcooling values listed in the following tables are based   
					on outdoor ambient air temperature of:   
					Table 5. XP16−048−230   
					Heating   
					Mode   
					+5ºF   
					Cooling   
					Mode   
					+1ºF   
					*Add Charge   
					Indoor Air Handers   
					and Coils   
					S 
					S 
					60°F (15.5°C) and above for cooling mode   
					59°F (15.0°C) and below for heating mode.   
					Subcooling   
					lbs.   
					1 
					1 
					3 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					2 
					2 
					0 
					1 
					0 
					0 
					1 
					1 
					1 
					oz.   
					4 
					Table 3. XP16−024−230   
					CBX26UH−048−230   
					CBX27UH−048−230   
					CBX27UH−060−230   
					CBX32M−048   
					CBX32M−060   
					CBX32MV−048   
					CBX32MV−060   
					CBX32MV−068   
					CBX40UHV−048   
					CBX40UHV−060   
					CH23−68   
					10   
					19   
					13   
					19   
					14   
					19   
					14   
					9 
					8 
					9 
					Heating   
					Mode   
					+5ºF   
					Cooling   
					Mode   
					+1ºF   
					4 
					*Add Charge   
					Indoor Air Handers   
					and Coils   
					14   
					9 
					3 
					Subcooling   
					lb.   
					0 
					0 
					1 
					0 
					1 
					1 
					1 
					1 
					1 
					0 
					1 
					1 
					oz.   
					15   
					9 
					4 
					CBX26UH−024   
					CBX27UH−024−230   
					CBX27UH−030−230   
					CBX32MV−024/030   
					CBX32MV−036   
					CBX40UHV−024   
					CBX40UHV−030   
					CBX40UHV−036   
					CH33−31B   
					45   
					20   
					17   
					20   
					17   
					17   
					17   
					17   
					31   
					45   
					24   
					18   
					6 
					7 
					7 
					7 
					7 
					7 
					7 
					7 
					8 
					4 
					7 
					8 
					9 
					11   
					4 
					9 
					3 
					9 
					11   
					11   
					4 
					9 
					8 
					3 
					19   
					14   
					24   
					19   
					19   
					13   
					11   
					15   
					15   
					14   
					9 
					9 
					3 
					9 
					11   
					12   
					5 
					3 
					10   
					9 
					3 
					CH33−49C   
					12   
					0 
					CH33−50/60C   
					CH33−60D   
					9 
					5 
					CR33−30/36A/B/C   
					CX34−31A/B   
					8 
					0 
					11   
					10   
					CH33−62D   
					9 
					4 
					CX34−38A/B   
					CR33−50/60C   
					CR33−60D   
					7 
					10   
					10   
					0 
					Table 4. XP16−036−230   
					7 
					Heating   
					Mode   
					+5ºF   
					Cooling   
					Mode   
					+1ºF   
					CX34−60D   
					8 
					*Add Charge   
					Indoor Air Handers   
					and Coils   
					CX34−62D   
					9 
					6 
					Subcooling   
					lbs.   
					0 
					oz.   
					0 
					CX34−62C   
					8 
					9 
					9 
					CBX26UH−036   
					CBX27UH−036−230   
					CBX27UH−042−230   
					CBX32M−036   
					CBX32MV−036   
					CBX32MV−048   
					CBX40UHV−030   
					CBX40UHV−036   
					CBX40UHV−042   
					CBX40UHV−048   
					CH33−43B   
					50   
					22   
					24   
					22   
					22   
					24   
					22   
					22   
					24   
					24   
					13   
					37   
					37   
					49   
					29   
					29   
					5 
					7 
					Table 6. XP16−060−230   
					0 
					9 
					Heating   
					Mode   
					+5ºF   
					Cooling   
					Mode   
					+1ºF   
					*Add Charge   
					Indoor Air Handers   
					and Coils   
					11   
					7 
					3 
					0 
					0 
					9 
					Subcooling   
					lbs.   
					4 
					oz.   
					13   
					3 
					7 
					0 
					9 
					CBX26UH−060   
					CBX27UH−060−230   
					CBX32M−060   
					CBX32MV−060   
					CBX32MV−068   
					CBX40UHV−060   
					CH23−682   
					20   
					10   
					17   
					17   
					15   
					17   
					37   
					33   
					15   
					24   
					24   
					21   
					13   
					9 
					6 
					6 
					6 
					7 
					6 
					9 
					8 
					7 
					7 
					7 
					9 
					7 
					11   
					7 
					3 
					0 
					2 
					0 
					9 
					1 
					12   
					12   
					1 
					7 
					0 
					9 
					1 
					11   
					11   
					10   
					11   
					11   
					7 
					3 
					0 
					2 
					3 
					0 
					1 
					12   
					10   
					0 
					2 
					7 
					2 
					CH33−48C   
					2 
					11   
					11   
					9 
					CH33−50/60C   
					CH33−62D   
					1 
					CH33−43C   
					2 
					1 
					4 
					CR33−48B/C   
					0 
					CR33−50/60C   
					CR33−60D   
					0 
					0 
					CX34−43B/C   
					9 
					2 
					11   
					11   
					0 
					0 
					CX34−50/60C   
					9 
					2 
					CX34−62C   
					2 
					16   
					4 
					CX34−62D   
					1 
					*Amount of charge required in additional to charge shown on unit   
					nameplate. (Remember to consider line set length difference.)   
					Page 28   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				NORMAL OPERATING PRESSURES   
					TEMPERATURE PRESSURES   
					Use the following tables to perform maintenance checks; it   
					is not a procedure for charging the system. Minor   
					variations in these pressures may be due to differences in   
					installations. Significant deviations could mean that the   
					system is not properly charged or that a problem exists   
					with some component in the system.   
					Compute subcooling by determining saturated   
					condensing temperature from temperature pressure   
					chart. Subtract from liquid temperature entering TXV.   
					Table 8. HFC−410A Temperature (°F) −   
					Pressure (Psig)   
					°F   
					Psig   
					°F Psig   
					°F Psig   
					°F Psig   
					Typical pressures only, expressed in psig (liquid +/− 10   
					and vapor +/− 5 psig); matched indoor component (air   
					handler or coil), indoor air quality, and indoor load will   
					cause the pressures to vary.   
					32   
					33   
					34   
					35   
					100.8   
					102.9   
					105.0   
					107.1   
					63   
					64   
					65   
					66   
					178.5   
					181.6   
					184.3   
					187.7   
					94   
					95   
					96   
					97   
					290.8   
					295.1   
					299.4   
					303.8   
					125   
					126   
					127   
					128   
					445.9   
					451.8   
					457.6   
					463.5   
					Table 7. Normal Operating Pressures*   
					Normal Operating Pressures − Cooling   
					XP16   
					−024   
					Vap   
					First Stage (Low Capacity) Pressure   
					−036   
					−048   
					−060   
					Liq   
					36   
					37   
					38   
					39   
					40   
					41   
					42   
					43   
					44   
					45   
					46   
					47   
					48   
					49   
					50   
					51   
					52   
					53   
					54   
					55   
					56   
					57   
					58   
					59   
					60   
					61   
					62   
					109.2   
					111.4   
					113.6   
					115.8   
					118.0   
					120.3   
					122.6   
					125.0   
					127.3   
					129.7   
					132.2   
					134.6   
					137.1   
					139.6   
					142.2   
					144.8   
					147.4   
					150.1   
					152.8   
					155.5   
					158.2   
					161.0   
					163.9   
					166.7   
					169.6   
					172.6   
					175.4   
					67   
					68   
					69   
					70   
					71   
					72   
					73   
					74   
					75   
					76   
					77   
					78   
					79   
					80   
					81   
					82   
					83   
					84   
					85   
					86   
					87   
					88   
					89   
					90   
					91   
					92   
					93   
					190.9   
					194.1   
					197.3   
					200.6   
					203.9   
					207.2   
					210.6   
					214.0   
					217.4   
					220.9   
					224.4   
					228.0   
					231.6   
					235.3   
					239.0   
					242.7   
					246.5   
					250.3   
					254.1   
					258.0   
					262.0   
					266.0   
					270.0   
					274.1   
					278.2   
					282.3   
					286.5   
					98   
					308.2   
					312.7   
					317.2   
					321.8   
					326.4   
					331.0   
					335.7   
					340.5   
					345.3   
					350.1   
					355.0   
					360.0   
					365.0   
					370.0   
					375.1   
					380.2   
					385.4   
					390.7   
					396.0   
					401.3   
					406.7   
					412.2   
					417.7   
					423.2   
					428.8   
					434.5   
					440.2   
					129   
					130   
					131   
					132   
					133   
					134   
					135   
					136   
					137   
					138   
					139   
					140   
					141   
					142   
					143   
					144   
					145   
					146   
					147   
					148   
					149   
					150   
					151   
					152   
					153   
					154   
					155   
					469.5   
					475.6   
					481.6   
					487.8   
					494.0   
					500.2   
					506.5   
					512.9   
					519.3   
					525.8   
					532.4   
					539.0   
					545.6   
					552.3   
					559.1   
					565.9   
					572.8   
					579.8   
					586.8   
					593.8   
					601.0   
					608.1   
					615.4   
					622.7   
					630.1   
					637.5   
					645.0   
					F   
					(C)**   
					Liq   
					Liq   
					Vap   
					Liq Vap   
					Vap   
					99   
					100   
					101   
					102   
					103   
					104   
					105   
					106   
					107   
					108   
					109   
					110   
					111   
					112   
					113   
					114   
					115   
					116   
					117   
					118   
					119   
					120   
					121   
					122   
					123   
					124   
					65   
					(18.3)   
					226   
					260   
					301   
					346   
					396   
					451   
					144   
					145   
					148   
					151   
					153   
					156   
					220   
					254   
					295   
					340   
					389   
					444   
					141   
					144   
					148   
					150   
					153   
					156   
					224   
					259   
					302   
					346   
					396   
					450   
					143   
					143   
					147   
					149   
					152   
					155   
					230   
					267   
					311   
					357   
					398   
					453   
					137   
					139   
					141   
					144   
					147   
					149   
					75   
					(23.9)   
					85   
					(29.4)   
					95   
					(35.0)   
					105   
					(40.6)   
					115   
					(46.1)   
					Second Stage (High Capacity) Pressure   
					65   
					(18.3)   
					241   
					279   
					321   
					369   
					421   
					480   
					140   
					142   
					144   
					146   
					148   
					151   
					232   
					269   
					312   
					346   
					409   
					465   
					129   
					136   
					140   
					142   
					145   
					148   
					238   
					278   
					321   
					372   
					424   
					481   
					138   
					140   
					142   
					144   
					147   
					149   
					232   
					276   
					320   
					367   
					421   
					479   
					131   
					133   
					136   
					138   
					141   
					144   
					75   
					(23.9)   
					85   
					(29.4)   
					95   
					(35.0)   
					105   
					(40.6)   
					115   
					(46.1)   
					Normal Operating Pressures − Heating   
					First Stage (Low Capacity) Pressure   
					50   
					(10)   
					312   
					330   
					112   
					130   
					350   
					372   
					115   
					136   
					336   
					363   
					114   
					135   
					385   
					414   
					108   
					126   
					60   
					(15.5)   
					Second Stage (High Capacity) Pressure   
					20   
					(−7.0)   
					299   
					312   
					325   
					344   
					358   
					64   
					79   
					321   
					347   
					367   
					387   
					395   
					61   
					74   
					289   
					294   
					321   
					341   
					361   
					57   
					69   
					332   
					349   
					361   
					383   
					425   
					59   
					67   
					30   
					(−1.0)   
					40   
					(4.4)   
					93   
					90   
					80   
					75   
					50   
					(10)   
					110   
					128   
					110   
					131   
					110   
					128   
					85   
					60   
					(15.5)   
					122   
					** Temperature of air entering outdoor coil.   
					Page 29   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				UNIT COMPONENTS   
					Demand Defrost Control (A108)   
					System Operation   
					The demand defrost control measures differential   
					temperatures to detect when the system is performing   
					poorly because of ice build−up on the outdoor coil. The   
					controller self−calibrates when the defrost system starts   
					and after each system defrost cycle. The demand defrost   
					
					IMPORTANT   
					Some scroll compressor have internal vacuum protector   
					that will unload scrolls when suction pressure goes   
					below 20 psig. A hissing sound will be heard when the   
					compressor is running unloaded. Protector will reset   
					when low pressure in system is raised above 40 psig. DO   
					NOT REPLACE COMPRESSOR.   
					S 
					S 
					S 
					Demand defrost control connections, jumpers and   
					
					This section addresses:   
					Demand defrost control connections, jumpers and   
					LED descriptions are listed on table 9.   
					S 
					S 
					Unit components (sensors, temperature switch,   
					pressure switches and demand defrost control)   
					Demand defrost control status, fault and lockout LEDs   
					
					Second−stage operation   
					TEST PINS (P1)   
					LOW AMBIENT   
					THERMOSTAT PINS   
					(P3)   
					DEFROST TERMINATION   
					PIN SETTINGS (P1)   
					SENSOR PLUG IN   
					(COIL AND   
					AMBIENT   
					SENSORS) (P4)   
					DIAGNOSTIC LEDS   
					(DS1 AND DS2)   
					DELAY PINS   
					(P5)   
					24V TERMINAL STRIP   
					CONNECTIONS (P2)   
					REVERSING VALVE   
					(O OUT)   
					PRESSURE SWITCH   
					CIRCUIT   
					CONNECTIONS   
					Note − Component locations vary by board manufacturer.   
					Figure 25. Demand Defrost Control (A108)   
					Page 30   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Table 9. Demand Defrost Control (A108) Inputs, Outputs and Configurable Settings   
					Control Control Label or   
					Locations Description   
					Purpose   
					Function   
					P1   
					P1   
					TEST   
					Test Mode   
					See Test Mode on page 39 for further details.   
					
					which are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt   
					terminationpin is factory set at 50°F (10°C). If the temperature shunt is   
					not installed, the default termination temperature is 90°F (32°C).   
					Defrost Temperature   
					Termination Shunt (Jumper)   
					Pins   
					50, 70, 90, 100   
					24VAC Thermostat Input /   
					Output   
					W1   
					24VAC input / output from indoor thermostat to indoor unit.   
					C 
					24VAC Common   
					Thermostat Service Light   
					24VAC   
					24VAC common   
					L 
					Thermostat service light connection.   
					24VAC   
					P2   
					R 
					Y2   
					O 
					Thermostat Input   
					Thermostat Input   
					Thermostat Input   
					Controls the second stage operation of the unit.   
					Reversing valve solenoid.   
					Controls the operation of the unit.   
					Y1   
					Low Ambient Thermostat Provides selection of the Y2 compressor lock−in temperature. Valid   
					options are 40, 45, 50 and 55 degrees Fahrenheit.   
					P3   
					P4   
					55, 50, 45, 40   
					DIS−YEL   
					Pins   
					(P4−5) Ground connection for outdoor coil temperature sensor.   
					(P4−6) Connection for outdoor coil temperature sensor.   
					Coil Sensor   
					(P4−3) Ground connection for outdoor ambient temperature sensor.   
					(P4−4) Connection for outdoor ambient temperature sensor.   
					AMB−BLACK   
					Ambient Sensor   
					COIL−BROWN   
					Discharge Sensor   
					No discharge sensor is used; replaced by 10K resistor.   
					The demand defrost control has a field−selectable function to reduce   
					occasional sounds that may occur while the unit is cycling in and out of   
					the defrost mode. When a jumper is installed on the DELAY pins, the   
					compressor will be cycled off for 30 seconds going in and out of the   
					defrost mode. Units are shipped with jumper installed on DELAY pins.   
					P5   
					DELAY   
					Delay Mode   
					NOTE − The 30 second off cycle is NOT functional when TEST pins on   
					P1 are jumpered.   
					P6   
					TST, PS DF, C, R, O, Y1, Y2   
					RED LED   
					Factory Test Connectors   
					Diagnostic LED   
					No field use.   
					DS1   
					Valid states for demand defrost control two LEDs are OFF, ON and   
					FLASHING which indicate diagnostics conditions that are described in   
					
					DS2   
					GREEN LED   
					TWO CONNECTORS   
					O OUT   
					FAN   
					Condenser Fan Operation   
					24 VAC output   
					These two connections provide power for the condenser fan.   
					24 VAC output connection for reversing valve.   
					O OUT   
					When the low pressure switch trips, the demand defrost control will cycle   
					off the compressor, and the strike counter in the demand defrost control   
					will count one strike. The low pressure switch is ignored under the   
					following conditions:   
					S 
					during the defrost cycle and 90 seconds after the termination of   
					defrost   
					LO−PS   
					LO−PS   
					Low−Pressure Switch   
					S 
					S 
					S 
					when the average ambient sensor temperature is below 0°F (−18°C)   
					for 90 seconds following the start up of the compressor   
					during TEST mode   
					Y2 OUT   
					Y1 OUT   
					Y2 OUT   
					Y1 OUT   
					24 VAC Output   
					24 VAC output for second stage compressor solenoid.   
					24 VAC Common Output   
					24 VAC common output, switched for enabling compressor contactor.   
					When the high pressure switch trips, the demand defrost control will cycle   
					off the compressor, and the strike counter in the demand defrost control   
					will count one strike.   
					HS−PS   
					HS−PS   
					High−Pressure Switch   
					L 
					L 
					Service Light Output   
					24 Volt output   
					24VAC service light output.   
					24VAC typically used to supply power to the Lennox System Operation   
					Monitor (LSOM). Not used in this system.   
					24V   
					24V   
					Page 31   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				DEMAND DEFROST CONTROL (A108) DIAGNOSTIC LEDS   
					The state (Off, On, Flashing) of two LEDs on the demand defrost control (DS1 [Red] and DS2 [Green]) indicate diagnostics   
					
					Table 10. Demand Defrost Control (A108) Diagnostic LEDs   
					DS1 and DS2 System Status, Fault and Lockout Codes   
					DS2   
					Green   
					DS1   
					Red   
					Condition/Code   
					Possible Cause(s)   
					Solution   
					Type   
					1 
					Check control transformer power (24V).   
					If power is available to demand defrost con-   
					No power (24V) to demand   
					defrost control terminals R and C   
					or demand defrost control failure.   
					2 
					OFF   
					OFF   
					Status   
					Power problem   
					trol and LED(s) do not light, replace demand   
					defrost control.   
					Simultaneous   
					SLOW Flash   
					Unit operating normally or in   
					standby mode.   
					Status   
					Status   
					Normal operation   
					None required.   
					Alternating SLOW   
					Flash   
					Initial power up, safety trip, end of   
					room thermostat demand.   
					5−minuteanti−short cycle delay   
					None required (jumper TEST pins to override)   
					Sensor being detected open or shorted or out of temperature range. Demand defrost   
					control will revert to time/temperature defrost operation. (System will still heat or   
					cool).   
					Simultaneous   
					FAST Flash   
					Fault   
					Fault   
					Fault   
					Ambient Sensor Problem   
					Coil Sensor Problem   
					Sensor being detected open or shorted or out of temperature range. Demand defrost   
					control will not perform demand or time/temperature defrost operation. (System will   
					still heat or cool).   
					Alternating   
					FAST Flash   
					Indicates that demand defrost control has internal component failure. Cycle 24VAC   
					power to demand defrost control. If code does not clear, replace demand defrost   
					control.   
					Demand Defrost Control   
					Failure   
					ON   
					ON   
					1 
					Remove any blockages or restrictions from   
					coils and/or fans. Check indoor and outdoor   
					fan motor for proper current draws.   
					SLOW   
					Flash   
					1 
					OFF   
					OFF   
					Fault   
					Low Pressure Fault   
					Low Pressure Lockout   
					High Pressure Fault   
					High Pressure Lockout   
					Restricted air flow over indoor or   
					outdoor coil.   
					2 
					3 
					2 
					3 
					Improper refrigerant charge in   
					system.   
					Check system charge using subcooling   
					method.   
					ON   
					Lockout   
					Fault   
					Improper metering device   
					installed or incorrect operation   
					of metering device.   
					Check system operating pressures and   
					compare to unit subcooling tables in this   
					instruction or located on unit access panel.   
					SLOW   
					Flash   
					OFF   
					4 
					4 
					Incorrect or improper sensor   
					location or connection to   
					system.   
					Make sure all pressure switches and sensors   
					have secure connections to system to prevent   
					refrigerant leaks or errors in pressure and   
					temperaturemeasurements.   
					ON   
					OFF   
					ON   
					Lockout   
					Fault   
					SLOW   
					Flash   
					Discharge Line Temperature   
					Fault   
					This code detects shorted sensor or high discharge temperatures. If the discharge   
					line temperature exceeds a temperature of 285ºF (140ºC) during compressor   
					operation, the demand defrost control will de−energize the compressor contactor   
					output (and the defrost output if active). The compressor will remain off until the   
					discharge temperature has dropped below 225ºF (107ºC).   
					FAST   
					Flash   
					Discharge Line Temperature   
					Lockout   
					ON   
					Lockout   
					Fault   
					Fast   
					Flash   
					The demand defrost control detects open sensor or out of temperature sensor range.   
					This fault is detected by allowing the unit to run for 90 seconds before checking   
					sensor resistance. If the sensor resistance is not within range after 90 seconds, the   
					demanddefrost control will count one fault. After 5 faults, the demand defrost control   
					will lockout.   
					OFF   
					Discharge Sensor Fault   
					Fast   
					Flash   
					Discharge Sensor Lockout   
					OFF   
					Lockout   
					(Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)   
					Page 32   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				High Pressure Switch (S4)   
					2. If the demand defrost control recognizes five   
					temperature sensor range faults during a single (Y1)   
					compressor demand, it reverts to a lockout mode and   
					displays the appropriate code. The demand defrost   
					control detects open sensor or out-of-temperature   
					sensor range. This fault is detected by allowing the unit   
					to run for 90 seconds before checking sensor   
					resistance. If the sensor resistance is not within range   
					after 90 seconds, the demand defrost control will count   
					one fault. After five faults, the demand defrost control   
					will lockout. Code on demand defrost control is   
					Discharge Sensor Fault and Lockout.   
					When the high pressure switch trips, the demand defrost   
					control will cycle off the compressor, and the strike counter   
					in the demand defrost control will count one strike. High   
					Pressure (auto reset) − trip at 590 psig, reset at 418.   
					Low Pressure Switch (S87)   
					When the low pressure switch trips, the demand defrost   
					control will cycle off the compressor, and the strike counter   
					in the demand defrost control will count one strike. Low   
					pressure switch (auto reset) − trip at 25 psig, reset at 40   
					psig.   
					The low pressure switch is ignored under the following   
					conditions:   
					The discharge line sensor, which covers a range of 150°F   
					(65°C) to 350°F (176°C), is designed to mount on a ½"   
					refrigerant discharge line.   
					S 
					S 
					S 
					S 
					During the defrost cycle and 90 seconds after the   
					termination of defrost   
					NOTE − Within a single room thermostat demand, if   
					5−strikes occur, the demand defrost control will lockout the   
					unit. demand defrost control 24 volt power R must be   
					cycled OFF or the TEST pins on demand defrost control   
					must be shorted between 1 to 2 seconds to reset the   
					demand defrost control.   
					When the average ambient sensor temperature is   
					below 15° F (−9°C)   
					For 90 seconds following the start up of the   
					compressor   
					During test mode   
					Crankcase Heater (HR1) and Crankcase Thermostat   
					Switch (S40)   
					Ambient Sensor (RT13)   
					The ambient sensor considers outdoor temperatures   
					below −35°F (−37°C) or above 120°F (48°C) as a fault. If the   
					ambient sensor is detected as being open, shorted or out   
					of the temperature range of the sensor, the demand   
					defrost control will not perform demand defrost operation.   
					The demand defrost control will revert to time/temperature   
					defrost operation and will display the appropriate fault   
					code. Heating and cooling operation will be allowed in this   
					fault condition.   
					The reference models are equipped with a 70 watt, belly   
					band type crankcase heater. HR1 prevents liquid from   
					accumulating in the compressor. HR1 is controlled by a   
					thermostat located on the liquid line. When liquid line   
					temperature drops below 50° F the thermostat closes   
					energizing HR1. The thermostat will open, de−energizing   
					HR1 once liquid line temperature reaches 70° F .   
					Liquid Line Bi−Flow Filter Drier   
					The unit is equipped with a large−capacity biflow filter drier   
					which keeps the system clean and dry. If replacement is   
					necessary, order another of like design and capacity. The   
					replacement filter drier must be suitable for use with   
					HFC−410A refrigerant.   
					Coil Sensor (RT21)   
					Coil SensorꢀThe coil temperature sensor considers   
					outdoor temperatures below −35°F (−37°C) or above 120°F   
					(48°C) as a fault. If the coil temperature sensor is detected   
					as being open, shorted or out of the temperature range of   
					the sensor, the demand defrost control will not perform   
					demand or time/temperature defrost operation and will   
					display the appropriate fault code. Heating and cooling   
					operation will be allowed in this fault condition.   
					The replacement filter drier must be suitable for use with   
					HFC−410A refrigerant.   
					SECOND−STAGE OPERATION   
					If the demand defrost control (A108) receives a call for   
					second−stage compressor operation Y2 in heating or   
					cooling mode and the first-stage compressor output is   
					active, the second-stage compressor solenoid output will   
					be energized.   
					High Discharge Temperature Sensor (RT28)   
					If the discharge line temperature exceeds a temperature of   
					285°F (140°C) during compressor operation, the demand   
					defrost control will de−energize the compressor contactor   
					output (and the defrost output, if active). The compressor   
					will remain off until the discharge temperature has dropped   
					below 225°F (107°C) and the 5-minute anti−short cycle   
					delay has been satisfied. This sensor has two fault and   
					lockout codes:   
					If first-stage compressor output is active in heating mode   
					and the outdoor ambient temperature is below the selected   
					compressor lock−in temperature, the second-stage   
					compressor solenoid output will be energized without the   
					Y2 input. If the jumper is not connected to one of the   
					temperature selection pins on P3 (40, 45, 50, 55°F), the   
					default lock−in temperature of 40°F (4.5°C) will be used.   
					1. If the demand defrost control recognizes five high   
					discharge line temperature faults during a single (Y1)   
					compressor demand, it reverts to a lockout mode and   
					displays the appropriate code. This code detects   
					shorted sensor or high discharge temperatures. Code   
					on demand defrost control is Discharge Line   
					Temperature Fault and Lockout.   
					The demand defrost control de−energizes the   
					second-stage compressor solenoid output immediately   
					when the Y2 signal is removed or the outdoor ambient   
					temperature is 5°F above the selected compressor lock−in   
					temperature, or the first-stage compressor output is   
					de−energized for any reason.   
					Page 33   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				If a pressure switch opens while the Y1 Out line is   
					engaged, a 5−minute short cycle will occur after the switch   
					closes.   
					Defrost System   
					This section addresses:   
					S 
					S 
					S 
					Emergency Heat   
					Demand Defrost Control Pressure Switch   
					Connections   
					Defrost System Overview   
					The unit’s automatic reset pressure switches (LO PS − S87   
					and HI PS − S4) are factory−wired into the demand defrost   
					control on the LO−PS and HI−PS terminals, respectively.   
					Defrost Control Connections, Jumper Settings and   
					Features   
					S 
					S 
					Operational Mode Overview (Calibration, Normal and   
					Defrost)   
					Demand Defrost Control Sensors   
					Sensors connect to the demand defrost control through a   
					field-replaceable harness assembly that plugs into the   
					
					the sensors, the demand defrost control detects outdoor   
					ambient, coil, and discharge temperature fault conditions.   
					As the detected temperature changes, the resistance   
					across the sensor changes.   
					Defrost Cycle Actuation   
					EMERGENCY HEAT (AMBER LIGHT)   
					An emergency heat function is designed into some room   
					thermostats. This feature is applicable when isolation of the   
					outdoor unit is required, or when auxiliary electric heat is   
					staged by outdoor thermostats. When the room thermostat is   
					placed in the emergency heat position, the outdoor unit   
					control circuit is isolated from power and field-provided relays   
					bypass the outdoor thermostats. An amber indicating light   
					simultaneously comes on to remind the homeowner that he   
					is operating in the emergency heat mode.   
					Testing Demand Defrost Control Sensors   
					Sensor resistance values can be checked by ohming   
					
					Table 11. Sensor Temperature /Resistance Range   
					Emergency heat is usually used during an outdoor unit   
					shutdown, but it should also be used following a power   
					outage if power has been off for over an hour and the   
					outdoor temperature is below 50°F (10°C). System should   
					be left in the emergency heat mode at least six hours to   
					allow the crankcase heater sufficient time to prevent   
					compressor slugging.   
					Pins/W   
					ire   
					Color   
					Temperature   
					Range °F (°C)   
					Resistance values   
					range (ohms)   
					Sensor   
					Outdoor   
					−35 (−37) to 120 (48) 280,000 to 3750   
					3 & 4   
					(Black)   
					Coil   
					−35 (−37) to 120 (48) 280,000 to 3750   
					5 & 6   
					(Brown)   
					DEFROST SYSTEM OVERVIEW   
					Discharge (if 24 (−4) to 350 (176) 41,000 to 103   
					applicable)   
					1 & 2   
					(Yellow)   
					The control monitors ambient temperature, outdoor coil   
					temperature, and total run time to determine when a   
					defrost cycle is required. The coil temperature probe is   
					designed withaspringcliptoallowmountingto theoutside   
					coil tubing. The location of the coil sensor is important for   
					proper defrost operation.   
					Note: Sensor resistance increases as sensed temperature decreases.   
					
					temperature changes for various types of sensors.   
					NOTE − When checking the ohms across a sensor, be   
					aware that a sensor showing a resistance value that is not   
					
					designed. However, if a shorted or open circuit is detected,   
					then the sensor may be faulty and the sensor harness will   
					need to be replaced.   
					NOTE − The demand defrost control accurately measures   
					the performance of the system as frost accumulates on the   
					outdoor coil. This typically will translate into longer running   
					time between defrost cycles as more frost accumulates on   
					the outdoor coil before the demand defrost control initiates   
					defrost cycles.   
					Defrost Temperature Termination Jumper   
					Settings (P1)   
					DEFROST CONTROL CONNECTIONS, JUMPERS   
					SETTINGS AND FEATURES   
					The demand defrost control selections are: 50, 70, 90, and   
					100°F (10, 21, 32 and 38°C). The shunt termination pin is   
					factory set at 50°F (10°C). If temperature shunt is not   
					installed, default termination temperature is 90°F (32°C).   
					Pressure Switch 5−Strike Lockout   
					The internal control logic of the demand defrost control   
					counts the pressure switch trips only while the Y1 (Input)   
					line is active. If a pressure switch opens and closes four   
					times during a Y1 (Input), the control logic will reset the   
					pressure switch trip counter to zero at the end of the Y1   
					(Input). If the pressure switch opens for a fifth time during   
					the current Y1 (Input), the control will enter a lockout   
					condition.   
					Test Pins (P1) Function   
					Placing the jumper on the field test pins (P1) allows the   
					technician to:   
					S 
					S 
					S 
					S 
					Clear short cycle lockout   
					Clear five−strike fault lockout   
					The 5−strike pressure switch lockout condition can be reset   
					by cycling OFF the 24−volt power to the demand defrost   
					control or by shorting the TEST pins between 1 to 2   
					seconds. All timer functions (run times) will also be reset.   
					Cycle the unit in and out of defrost mode   
					Place the unit in defrost mode to clear the coil   
					
					Page 34   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Compressor Delay Mode (P5)   
					1. Frost Detection ꢀ If the compressor runs longer than   
					30 minutes and the actual difference between the clear   
					coil and frosted coil temperatures exceeds the   
					maximum difference allowed by the demand defrost   
					control, a defrost cycle will be initiated.   
					The demand defrost control has a field−selectable function   
					to reduce occasional sounds that may occur while the unit   
					is cycling in and out of the defrost mode. When a jumper is   
					installed on the DELAY pins, the compressor will be cycled   
					off for 30 seconds going in and out of the defrost mode.   
					Units are shipped with jumper installed on DELAY pins.   
					2. Time ꢀ If six hours of heating mode compressor run   
					time has elapsed since the last defrost cycle while the   
					coil temperature remains below 35°F (2°C), the   
					demand defrost control will initiate a defrost cycle.   
					NOTE − The 30 second off cycle is NOT functional when   
					jumpering the TEST pins.   
					OPERATIONAL MODE OVERVIEW   
					The demand defrost control has three basic operational   
					modes. Those modes are:   
					Actuation   
					When the reversing valve is de−energized, the Y1 circuit is   
					energized, and the coil temperature is below 35°F (2°C),   
					the demand defrost control logs the compressor run time.   
					If the demand defrost control is not calibrated, a defrost   
					cycle will be initiated after 30 minutes of heating mode   
					compressor run time. The control will attempt to   
					self−calibrate after this (and all other) defrost cycle(s).   
					1. Calibration Mode ꢀ The demand defrost control is   
					considered uncalibrated when power is applied to the   
					demand defrost control, after cool mode operation, or   
					if the coil temperature exceeds the termination   
					
					further details).   
					Calibration success depends on stable system   
					temperatures during the 20−minute calibration period. If   
					the demand defrost control fails to calibrate, another   
					defrost cycle will be initiated after 45 minutes of heating   
					mode compressor run time. Once the demand defrost   
					control is calibrated, it initiates a demand defrost cycle   
					when the difference between the clear coil and frosted coil   
					temperatures exceeds the maximum difference allowed   
					by the control or after six hours of heating mode   
					compressor run time has been logged since the last   
					defrost cycle.   
					2. Normal Mode ꢀ The demand defrost control   
					monitors the O line, to determine the system operating   
					mode (heat/cool), outdoor ambient temperature, coil   
					temperature (outdoor coil) and compressor run time to   
					determine when a defrost cycle is required.   
					Calibration of the demand defrost control occurs after   
					a defrost cycle to ensure that there is no ice on the coil.   
					During calibration, the temperature of both the coil and   
					the ambient sensor are measured to establish the   
					temperature differential which is required to allow a   
					defrost cycle.   
					Termination   
					3. Defrost Mode ꢀ The following paragraphs provide a   
					detailed description of the defrost system operation.   
					The defrost cycle ends when the coil temperature exceeds   
					the termination temperature or after 14 minutes of defrost   
					operation. If the defrost is terminated by the 14−minute   
					timer, another defrost cycle will be initiated after 30   
					minutes of run time.   
					DEFROST CYCLE ACTUATION   
					The demand defrost control initiates a defrost cycle based   
					on either frost detection or time.   
					Page 35   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				DEFROST CONTROL (A108) CALIBRATION MODE SEQUENCE   
					Occurs after power up and cooling operation, or if the coil temperature exceeds   
					the termination temperature while in Heat Mode.   
					Demand defrost control defaults to 30 minute ꢀ Time / Temperature Mode   
					Reset Compressor Runtime / Reset Three / Five Strike Counter   
					DEMAND MODE   
					THIRTY (30) MINUTE TIME /   
					TEMPERATURE MODE   
					45 MINUTE   
					TIME/TEMPERATURE MODE   
					Accumulate compressor runtime of   
					more than 30 minutes while coil   
					temperature is below 35° F (2°C).   
					When the accumulated compressor   
					time exceeds six (6) hours or if the   
					coil sensor indicates frost is present   
					on coil, go to Defrost.   
					Accumulate compressor runtime   
					while coil temperature is below 35° F   
					(2°C). When the accumulated   
					compressor time exceeds 30 minutes   
					go to Defrost.   
					Accumulate compressor runtime   
					while coil temperature is below 35°   
					F (2°C). When the accumulated   
					compressor time exceeds 45   
					minutes go to Defrost.   
					DEFROST   
					S 
					S 
					S 
					Outdoor Fan OFF   
					Reversing Valve ON   
					W1 line ON   
					Monitor coil temperature and   
					time in defrost mode.   
					HOW DID DEFROST TERMINATE?   
					Defrosted for 14−minute without the coil temperature   
					going above 35°F (2°C) for four (4) minutes and coil   
					did not reach termination temperature.   
					Coil temperature was above 35°F (2°C) for four (4)   
					minutes. of the 14−minute defrost OR reached   
					defrost termination temperature.   
					DEFROST TERMINATION   
					DEFROST TERMINATION   
					S 
					S 
					S 
					S 
					Compressor runtime counter RESET   
					Outdoor Fan ON   
					S 
					S 
					S 
					S 
					Compressor runtime counter RESET   
					Outdoor Fan ON   
					Reversing Valve OFF   
					W1 line OFF   
					Reversing Valve OFF   
					W1 line OFF   
					Attempt to Calibration ꢀ Temperature measurements are not taken for the first few minutes of each heat demand. This is   
					to allow coil temperatures to stabilize. demand defrost control has a maximum of 20 minutes of accumulated compressor   
					runtime in heat mode to calibrate demand defrost control This may involve more than one heating demand.   
					NO ꢀ Demand defrost control   
					reverts to 45 minute time   
					temperature.   
					Was stable coil temperature attained   
					within 20 minutes?   
					/ 
					YES ꢀ Calibration occurred   
					Figure 26. Defrost Calibration   
					Page 36   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Table 12. Ambient (RT13) and Coil (RT21) Sensors Temperature / Resistance Range   
					Degrees   
					Fahrenheit   
					Degrees   
					Fahrenheit   
					Degrees   
					Fahrenheit   
					Degrees   
					Fahrenheit   
					Resistance   
					Resistance   
					Resistance   
					Resistance   
					136.3   
					133.1   
					130.1   
					127.3   
					124.7   
					122.1   
					119.7   
					117.5   
					115.3   
					113.2   
					111.2   
					109.3   
					107.4   
					105.6   
					103.9   
					102.3   
					100.6   
					99.1   
					97.6   
					96.1   
					94.7   
					93.3   
					92.0   
					90.6   
					89.4   
					88.1   
					86.9   
					85.7   
					84.5   
					83.4   
					82.3   
					81.2   
					80.1   
					79.0   
					78.0   
					77.0   
					76.0   
					75.0   
					74.1   
					73.1   
					72.2   
					71.3   
					70.4   
					69.5   
					68.6   
					67.7   
					66.9   
					66.0   
					65.2   
					64.4   
					63.6   
					62.8   
					62.0   
					61.2   
					60.5   
					59.7   
					59.0   
					58.2   
					57.5   
					2680   
					2859   
					56.8   
					56.0   
					55.3   
					54.6   
					53.9   
					53.2   
					52.5   
					51.9   
					51.2   
					50.5   
					49.9   
					49.2   
					48.5   
					47.9   
					47.3   
					46.6   
					46.0   
					45.4   
					44.7   
					44.1   
					43.5   
					42.9   
					42.3   
					41.7   
					41.1   
					40.5   
					39.9   
					39.3   
					38.7   
					38.1   
					37.5   
					37.0   
					36.4   
					35.8   
					35.2   
					34.7   
					34.1   
					33.5   
					33.0   
					32.4   
					31.9   
					31.3   
					30.7   
					30.2   
					29.6   
					29.1   
					28.6   
					28.0   
					27.5   
					26.9   
					26.4   
					25.8   
					25.3   
					24.8   
					24.2   
					23.7   
					23.2   
					22.6   
					22.1   
					16657   
					16973   
					17293   
					17616   
					17942   
					18273   
					18607   
					18945   
					19287   
					19633   
					19982   
					20336   
					20695   
					21057   
					21424   
					21795   
					22171   
					22551   
					22936   
					23326   
					23720   
					24120   
					24525   
					24934   
					25349   
					25769   
					26195   
					26626   
					27063   
					27505   
					27954   
					28408   
					28868   
					29335   
					29808   
					30288   
					30774   
					31267   
					31766   
					32273   
					32787   
					33309   
					33837   
					34374   
					34918   
					35471   
					36031   
					36600   
					37177   
					37764   
					38359   
					38963   
					39577   
					40200   
					40833   
					41476   
					42130   
					42794   
					43468   
					21.6   
					21.0   
					20.5   
					20.0   
					19.4   
					18.9   
					18.4   
					17.8   
					17.3   
					16.8   
					16.3   
					15.7   
					15.2   
					14.7   
					14.1   
					13.6   
					13.1   
					12.5   
					12.0   
					11.5   
					11.0   
					10.4   
					9.9   
					44154   
					44851   
					45560   
					46281   
					47014   
					47759   
					48517   
					49289   
					50074   
					50873   
					51686   
					52514   
					53356   
					54215   
					55089   
					55979   
					56887   
					57811   
					58754   
					59715   
					60694   
					61693   
					62712   
					63752   
					64812   
					65895   
					67000   
					68128   
					69281   
					70458   
					71661   
					72890   
					74147   
					75431   
					76745   
					78090   
					79465   
					80873   
					82314   
					83790   
					85302   
					86852   
					88440   
					90068   
					91738   
					93452   
					95211   
					97016   
					98870   
					100775   
					102733   
					104746   
					106817   
					108948   
					111141   
					113400   
					115727   
					118126   
					120600   
					−11.3   
					−11.9   
					−12.6   
					−13.2   
					−13.9   
					−14.5   
					−15.2   
					−15.9   
					−16.5   
					−17.2   
					−17.9   
					−18.6   
					−19.3   
					−20.1   
					−20.8   
					−21.5   
					−22.3   
					−23.0   
					−23.8   
					−24.6   
					−25.4   
					−26.2   
					−27.0   
					−27.8   
					−28.7   
					−29.5   
					−30.4   
					−31.3   
					−32.2   
					−33.2   
					−34.1   
					−35.1   
					−36.1   
					−37.1   
					−38.2   
					−39.2   
					123152   
					125787   
					128508   
					131320   
					134227   
					137234   
					140347   
					143571   
					146913   
					150378   
					153974   
					157708   
					161588   
					165624   
					169824   
					174200   
					178762   
					183522   
					188493   
					193691   
					199130   
					204829   
					210805   
					217080   
					223677   
					230621   
					237941   
					245667   
					253834   
					262482   
					271655   
					281400   
					291774   
					302840   
					314669   
					327343   
					3040   
					3223   
					3407   
					3592   
					3779   
					3968   
					4159   
					4351   
					4544   
					4740   
					4937   
					5136   
					5336   
					5539   
					5743   
					5949   
					6157   
					6367   
					6578   
					6792   
					7007   
					7225   
					9.3   
					7444   
					8.8   
					7666   
					8.3   
					7890   
					7.7   
					8115   
					7.2   
					8343   
					6.7   
					8573   
					6.1   
					8806   
					5.6   
					9040   
					5.0   
					9277   
					4.5   
					9516   
					3.9   
					9757   
					3.4   
					10001   
					10247   
					10496   
					10747   
					11000   
					11256   
					11515   
					11776   
					12040   
					12306   
					12575   
					12847   
					13122   
					13400   
					13681   
					13964   
					14251   
					14540   
					14833   
					15129   
					15428   
					15730   
					16036   
					16345   
					2.8   
					2.3   
					1.7   
					1.2   
					0.6   
					0.0   
					−0.5   
					−1.1   
					−1.7   
					−2.2   
					−2.8   
					−3.4   
					−4.0   
					−4.6   
					−5.2   
					−5.7   
					−6.3   
					−6.9   
					−7.5   
					−8.2   
					−8.8   
					−9.4   
					−10.0   
					−10.6   
					Page 37   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Table 13. High Discharge Sensor (RT28) Temperature / Resistance Range   
					Degrees   
					Fahrenheit   
					Degrees   
					Fahrenheit   
					Degrees   
					Fahrenheit   
					Degrees   
					Fahrenheit   
					Resistance   
					Resistance   
					Resistance   
					Resistance   
					303.1   
					298.1   
					293.4   
					289.0   
					284.8   
					280.9   
					277.1   
					273.6   
					270.2   
					267.0   
					263.9   
					260.9   
					258.1   
					255.3   
					252.7   
					250.1   
					247.7   
					245.3   
					243.0   
					240.8   
					238.6   
					236.5   
					234.4   
					232.4   
					230.5   
					228.6   
					226.7   
					224.9   
					223.2   
					221.5   
					219.8   
					218.1   
					216.5   
					214.9   
					213.4   
					211.9   
					210.4   
					208.9   
					207.5   
					206.0   
					204.6   
					203.3   
					201.9   
					200.6   
					199.3   
					198.0   
					196.8   
					195.5   
					194.3   
					193.1   
					191.9   
					190.7   
					189.5   
					188.4   
					187.2   
					183   
					195   
					207   
					220   
					232   
					245   
					258   
					270   
					283   
					297   
					310   
					323   
					336   
					350   
					364   
					378   
					391   
					405   
					420   
					434   
					448   
					463   
					478   
					492   
					507   
					523   
					538   
					553   
					569   
					584   
					600   
					616   
					632   
					649   
					665   
					682   
					698   
					715   
					732   
					750   
					767   
					785   
					803   
					821   
					839   
					857   
					876   
					894   
					913   
					932   
					952   
					971   
					991   
					1011   
					1031   
					186.1   
					185.0   
					183.9   
					182.8   
					181.8   
					180.7   
					179.6   
					178.6   
					177.6   
					176.6   
					175.5   
					174.6   
					173.6   
					172.6   
					171.6   
					170.6   
					169.7   
					168.7   
					167.8   
					166.9   
					165.9   
					165.0   
					164.1   
					163.2   
					162.3   
					161.4   
					160.5   
					159.7   
					158.8   
					157.9   
					157.1   
					156.2   
					155.3   
					154.5   
					153.6   
					152.8   
					152.0   
					151.1   
					150.3   
					149.5   
					148.7   
					147.9   
					147.1   
					146.2   
					145.4   
					144.6   
					143.8   
					143.0   
					142.3   
					141.5   
					140.7   
					139.9   
					139.1   
					138.3   
					137.6   
					1052   
					1072   
					1093   
					1114   
					1135   
					1157   
					1179   
					1201   
					1223   
					1245   
					1268   
					1291   
					1315   
					1338   
					1362   
					1386   
					1411   
					1435   
					1460   
					1486   
					1511   
					1537   
					1563   
					1590   
					1617   
					1644   
					1672   
					1699   
					1728   
					1756   
					1785   
					1815   
					1845   
					1875   
					1905   
					1936   
					1968   
					1999   
					2032   
					2064   
					2098   
					2131   
					2165   
					2200   
					2235   
					2270   
					2306   
					2343   
					2380   
					2418   
					2456   
					2495   
					2534   
					2574   
					2615   
					136.8   
					136.0   
					135.2   
					134.5   
					133.7   
					132.9   
					132.2   
					131.4   
					130.6   
					129.9   
					129.1   
					128.4   
					127.6   
					126.8   
					126.1   
					125.3   
					124.6   
					123.8   
					123.1   
					122.3   
					121.6   
					120.8   
					120.1   
					119.3   
					118.5   
					117.8   
					117.0   
					116.3   
					115.5   
					114.8   
					114.0   
					113.2   
					112.5   
					111.7   
					111.0   
					110.2   
					109.4   
					108.7   
					107.9   
					107.1   
					106.4   
					105.6   
					104.8   
					104.0   
					103.3   
					102.5   
					101.7   
					100.9   
					100.1   
					99.3   
					2656   
					2698   
					2740   
					2783   
					2827   
					2872   
					2917   
					2963   
					3010   
					3057   
					3105   
					3154   
					3204   
					3255   
					3307   
					3359   
					3413   
					3467   
					3523   
					3579   
					3637   
					3695   
					3755   
					3816   
					3877   
					3940   
					4005   
					4070   
					4137   
					4205   
					4274   
					4345   
					4418   
					4491   
					4567   
					4644   
					4722   
					4802   
					4884   
					4968   
					5054   
					5141   
					5231   
					5323   
					5416   
					5512   
					5610   
					5711   
					5814   
					5920   
					6028   
					6139   
					6253   
					6370   
					6489   
					94.5   
					93.6   
					92.8   
					92.0   
					91.2   
					90.3   
					89.5   
					88.6   
					87.8   
					86.9   
					86.0   
					85.2   
					84.3   
					83.4   
					82.5   
					81.6   
					80.7   
					79.8   
					78.8   
					77.9   
					76.9   
					76.0   
					75.0   
					74.1   
					73.1   
					72.1   
					71.1   
					70.0   
					69.0   
					68.0   
					66.9   
					65.8   
					64.7   
					63.6   
					62.5   
					61.3   
					60.2   
					59.0   
					57.8   
					56.6   
					55.3   
					54.0   
					52.7   
					51.4   
					50.0   
					48.6   
					47.2   
					45.7   
					6613   
					6739   
					6869   
					7002   
					7139   
					7281   
					7426   
					7575   
					7729   
					7888   
					8051   
					8220   
					8394   
					8574   
					8759   
					8951   
					9149   
					9354   
					9566   
					9786   
					10013   
					10250   
					10495   
					10749   
					11014   
					11289   
					11575   
					11873   
					12184   
					12509   
					12848   
					13202   
					13573   
					13961   
					14368   
					14796   
					15246   
					15719   
					16218   
					16744   
					17301   
					17891   
					18516   
					19180   
					19887   
					20641   
					21448   
					22311   
					98.5   
					97.7   
					96.9   
					96.1   
					95.3   
					Page 38   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				TEST   
					PSlacing the jumper on the field test pins (P1) allows the technician to:   
					Clear short cycle lockout   
					S 
					S 
					S 
					Clear five−strike fault lockout   
					Cycle the unit in and out of defrost mode   
					Place the unit in defrost mode to clear the coil   
					WhenY1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2 to   
					5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal   
					operation.   
					The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one   
					second and then reapplied.   
					Y1 Active   
					Place a jumper on TEST pins for   
					longer than one second but less   
					than two seconds.   
					Place a jumper on TEST pins for   
					more than two seconds.   
					Clears any short cycle lockout and   
					five strike fault lockout function, if   
					applicable.   
					Clears any short cycle lockout and   
					five strike fault lockout function, if   
					applicable.No other functions will be   
					executed and unit will continue in the   
					mode it was operating.   
					ACTIVE   
					INACTIVE   
					O Line Status   
					If in HEATING Mode   
					If in COOLING Mode   
					If in DEFROST Mode   
					The unit will terminate defrost and   
					enter HEAT MODE uncalibrated   
					with defrost timer set for 45 minute   
					test.   
					No further test mode operation will be   
					executed until the jumper is removed   
					from the TEST pins and reapplied.   
					If no ambient or coil sensor fault   
					exist, unit will go into DEFROST   
					MODE.   
					If ambient or coil faults exist (open or   
					shorted), unit will remain in HEAT   
					MODE.   
					If jumper on TEST pins remains in   
					place for more than five seconds.   
					If jumper on TEST pins is removed   
					before a maximum of five seconds.   
					NOTE ꢀ Placing a jumper on the TEST pins will not bring the unit   
					out of inactive mode. The only way manually activate the heat   
					pump from an inactive mode is to cycle the 24VAC power to the   
					Control.   
					The unit will remain in DEFROST   
					MODE until termination on time or   
					temperature.   
					The unit will return to HEAT MODE   
					un−calibrated with defrost timer set   
					for 34 minutes.   
					Figure 27. Test Pin (P1) Functions   
					Page 39   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				12. After testing is complete, return unit to original set up.   
					Two−Stage Modulation Compressors   
					Checks   
					Maintenance   
					DEALER   
					Maintenance and service must be performed by a qualified   
					installer or service agency. At the beginning of each   
					cooling season, the system should be checked as follows:   
					
					full-load capacity operation of two-stage modulation   
					compressors.   
					TOOLS REQUIRED   
					S 
					S 
					S 
					S 
					Refrigeration gauge set   
					Digital volt/amp meter   
					Outdoor Unit   
					1. Clean and inspect outdoor coil (may be flushed with a   
					water hose). Ensure power is off before cleaning.   
					Electronic temperature thermometer   
					On-off toggle switch   
					2. Outdoor unit fan motor is pre−lubricated and sealed.   
					No further lubrication is needed.   
					3. Visually inspect all connecting lines, joints and coils for   
					evidence of oil leaks.   
					IMPORTANT   
					4. Check all wiring for loose connections.   
					This performance check is ONLY valid on systems that   
					have clean indoor and outdoor coils, proper airflow over   
					coils, and correct system refrigerant charge. All   
					components in the system must be functioning proper to   
					correctly perform compressor modulation operational   
					check. (Accurate measurements are critical to this test   
					as indoor system loading and outdoor ambient can affect   
					variations between low and high capacity readings).   
					5. Check for correct voltage at unit (unit operating).   
					6. Check amp draw on outdoor fan motor.   
					Motor Nameplate:_________ Actual:__________.   
					7. Inspect drain holes in coil compartment base and   
					clean if necessary.   
					NOTE - If insufficient heating or cooling occurs, the unit   
					should be gauged and refrigerant charge should be   
					checked.   
					PROCEDURE   
					NOTE − Block outdoor coil to maintain a minimum of 375   
					psig during testing).   
					Outdoor Coil   
					It may be necessary to flush the outdoor coil more   
					frequently if it is exposed to substances which are   
					corrosive or which block airflow across the coil (e.g., pet   
					urine, cottonwood seeds, fertilizers, fluids that may contain   
					high levels of corrosive chemicals such as salts)   
					1. Turn main power OFF to outdoor unit.   
					2. Adjust room thermostat set point 5ºF above the room   
					temperature.   
					3. Remove control access panel. Install refrigeration   
					gauges on unit. Attach the amp meter to the common   
					(black wire) wire of the compressor harness. Attach   
					thermometer to discharge line as close as possible to   
					the compressor.   
					S 
					S 
					Outdoor Coil ꢀ The outdoor coil may be flushed with   
					a water hose.   
					Outdoor Coil (Sea Coast) ꢀ Moist air in ocean   
					locations can carry salt, which is corrosive to most   
					metal. Units that are located near the ocean require   
					frequent inspections and maintenance. These   
					inspections will determine the necessary need to wash   
					the unit including the outdoor coil. Consult your   
					installing contractor for proper intervals/procedures   
					for your geographic area or service contract.   
					4. Turn toggle switch OFF and install switch in series with   
					Y2 wire from room thermostat.   
					5. Cycle main power ON.   
					6. Allow pressures and temperatures to stabilize before   
					taking measurements (may take up to 10 minutes).   
					7. Record all of the readings for the Y1 demand.   
					Indoor Unit   
					1. Clean or change filters.   
					8. Close switch to energize Y2 demand. Verify power is   
					going to compressor solenoid.   
					2. Lennox blower motors are prelubricated and   
					permanently sealed. No more lubrication is needed.   
					9. Allow pressures and temperatures to stabilize before   
					taking measurements (may take up to 10 minutes).   
					3. Adjust blower speed for cooling. Measure the pressure   
					drop over the coil to determine the correct blower CFM.   
					Refer to the unit information service manual for pressure   
					drop tables and procedure.   
					10. Record all of the readings with the Y1 and Y2 demand.   
					11. If temperatures and pressures change in the direction   
					noted in Two−Stage Modulation Compressor Field   
					
					properly modulating from low to high capacity. (If no   
					amperage, pressures or temperature readings   
					change when this test is performed, the compressor   
					is not modulating between low and high capacity and   
					replacement is necessary).   
					4. Belt Drive Blowers − Check belt for wear and proper   
					tension.   
					5. Check all wiring for loose connections.   
					6. Check for correct voltage at unit. (blower operating)   
					7. Check amp draw on blower motor.   
					Motor Nameplate:_________ Actual:__________.   
					Page 40   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Indoor Coil   
					1. Clean coil if necessary.   
					filter to dry completely before returning it to the unit or   
					grille.   
					2. Check connecting lines, joints and coil for evidence of   
					oil leaks.   
					NOTE ꢀ The filter and all access panels must be in place   
					any time the unit is in operation.   
					4. Indoor Unit ꢀ The indoor unit’s evaporator coil is   
					equipped with a drain pan to collect condensate   
					formed as your system removes humidity from the   
					inside air. Have your dealer show you the location of   
					the drain line and how to check for obstructions. (This   
					would also apply to an auxiliary drain, if installed.)   
					3. Check condensate line and clean if necessary.   
					HOMEOWNER   
					Cleaning of the outdoor unit’s coil should be performed by   
					a trained service technician. Contact your dealer and set   
					up a schedule (preferably twice a year, but at least once a   
					year) to inspect and service your outdoor unit. The   
					following maintenance may be performed by the   
					homeowner.   
					Thermostat Operation   
					See the thermostat homeowner manual for instructions on   
					how to operate your thermostat.   
					Heat Pump Operation   
					Your new Lennox heat pump has several characteristics   
					that you should be aware of:   
					IMPORTANT   
					Sprinklers and soaker hoses should not be installed   
					where they could cause prolonged exposure to the   
					outdoor unit by treated water. Prolonged exposure of the   
					unit to treated water (i.e., sprinkler systems, soakers,   
					waste water, etc.) will corrode the surface of steel and   
					aluminum parts and diminish performance and longevity   
					of the unit.   
					S 
					Heat pumps satisfy heating demand by delivering   
					large amounts of warm air into the living space. This   
					is quite different from gas- or oil-fired furnaces or an   
					electric furnace which deliver lower volumes of   
					considerably hotter air to heat the space.   
					S 
					Do not be alarmed if you notice frost on the outdoor coil   
					in the winter months. Frost develops on the outdoor   
					coil during the heating cycle when temperatures are   
					below 45F (7C). An electronic control activates a   
					defrost cycle lasting 5 to 15 minutes at preset intervals   
					to clear the outdoor coil of the frost.   
					Outdoor Coil   
					The outdoor unit must be properly maintained to ensure its   
					proper operation.   
					S 
					S 
					S 
					Please contact your dealer to schedule proper   
					inspection and maintenance for your equipment.   
					S 
					During the defrost cycle, you may notice steam rising   
					from the outdoor unit. This is a normal occurrence. The   
					thermostat may engage auxiliary heat during the   
					defrost cycle to satisfy a heating demand; however,   
					the unit will return to normal operation at the   
					conclusion of the defrost cycle.   
					Make sure no obstructions restrict airflow to the   
					outdoor unit.   
					Grass clippings, leaves, or shrubs crowding the unit   
					can cause the unit to work harder and use more   
					energy.   
					Extended Power Outage   
					S 
					Keep shrubbery trimmed away from the unit and   
					periodically check for debris which collects around the   
					unit.   
					The heat pump is equipped with a compressor crankcase   
					heater which protects the compressor from refrigerant   
					slugging during cold weather operation.   
					Cleaning of the outdoor unit’s coil should be performed by   
					a trained service technician. Contact your dealer and set   
					up a schedule (preferably twice a year, but at least once a   
					year) to inspect and service your outdoor unit.   
					If power to your unit has been interrupted for several hours   
					or more, set the room thermostat selector to the   
					EMERGENCY HEAT setting to obtain temporary heat   
					without the risk of serious damage to the heat pump.   
					Routine Maintenance   
					In EMERGENCY HEAT mode, all heating demand is   
					satisfied by auxiliary heat; heat pump operation is locked   
					out. After a six-hour compressor crankcase warm-up   
					period, the thermostat can be switched to the HEAT setting   
					and normal heat pump operation may resume.   
					In order to ensure peak performance, your system must be   
					properly maintained. Clogged filters and blocked airflow   
					prevent your unit from operating at its most efficient level.   
					1. Air Filter ꢀ Ask your Lennox dealer to show you   
					where your indoor unit’s filter is located. It will be either   
					at the indoor unit (installed internal or external to the   
					cabinet) or behind a return air grille in the wall or   
					ceiling. Check the filter monthly and clean or replace   
					it as needed.   
					Preservice Check   
					If your system fails to operate, check the following before   
					calling for service:   
					S 
					S 
					S 
					S 
					S 
					S 
					Verify room thermostat settings are correct.   
					Verify that all electrical disconnect switches are ON.   
					Check for any blown fuses or tripped circuit breakers.   
					Verify unit access panels are in place.   
					2. Disposable Filter ꢀ Disposable filters should be   
					replaced with a filter of the same type and size.   
					NOTE ꢀ If you are unsure about the filter required for your   
					system, call your Lennox dealer for assistance.   
					Verify air filter is clean.   
					3. Reusable Filter ꢀ Many indoor units are equipped   
					with reusable foam filters. Clean foam filters with a   
					mild soap and water solution; rinse thoroughly; allow   
					If service is needed, locate and write down the unit   
					model number and have it handy before calling.   
					Page 41   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Accessories   
					S 
					S 
					S 
					Lennox XP16 Engineering Handbook   
					Lennox Product Catalog   
					For update−to−date information, see any of the following   
					publications:   
					Lennox Price Book   
					Checklists   
					Two−Stage Modulation Compressors Field Operational Checklist   
					Expected results during Y2 demand   
					(Toggle switch On)   
					Unit Readings   
					Y1 − First-Stage   
					Y2 − Second-Stage   
					COMPRESSOR   
					Voltage   
					Same   
					Amperage   
					Higher   
					OUTDOOR UNIT FAN MOTOR   
					Amperage   
					Same or Higher   
					TEMPERATURE   
					Ambient   
					Same   
					Higher   
					Higher   
					Same   
					Lower   
					Outdoor Coil Discharge Air   
					Compressor Discharge Line   
					Indoor Return Air   
					Indoor Coil Discharge Air   
					PRESSURES   
					Suction (Vapor)   
					Liquid   
					Lower   
					Higher   
					Page 42   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				XP16 Start−Up and Performance   
					Customer   
					Address   
					Serial   
					Indoor Unit Model   
					Outdoor Unit Model   
					Notes:   
					Serial   
					START UP CHECKS   
					RefrigerantType:   
					1st Stage: Rated Load Amps   
					2nd Stage: Rated Load Amps   
					Outdoor Unit Fan Full Load Amps   
					Actual Amps   
					Actual Amps   
					Rated Volts   
					Actual Volts   
					Actual Volts   
					2nd Stage   
					Rated Volts   
					1st Stage   
					Actual Amps:   
					COOLING MODE   
					Suction Pressure: 1st Stage:   
					Liquid Pressure: 1st Stage:   
					Supply Air Temperature: 1st Stage:   
					Temperature: Ambient:   
					2nd Stage:   
					2nd Stage:   
					2nd Stage:   
					Return Air:   
					System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach tempera-   
					tures.)   
					A 
					A 
					A 
					B 
					B 
					B 
					SUBCOOLING   
					Subcooling:   
					ꢀ 
					ꢀ 
					ꢀ 
					= 
					= 
					= 
					Saturated Condensing Temperature (A) minus Liquid   
					Line Temperature (B)   
					APPROACH   
					Approach:   
					Liquid Line Temperature (A) minus Outdoor Air   
					Temperature (B)   
					COIL TEMP DROP   
					Indoor Coil Temperature Drop (18 to 22°F)   
					Return Air Temperature (A) minus Supply Air   
					Temperature (B)   
					Page 43   
					XP16 SERIES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |