Solid State Economizer System
(CONSISTING OF: C7046C DISCHARGE AIR SENSOR OR C7150B MIXED AIR SENSOR, C7400A
SOLID STATE ENTHALPY SENSOR OR C7650A SOLID STATE TEMPERATURE SENSOR, M7415
OR M8405 DAMPER ACTUATORS OR MODULATING DIRECT COUPLED ACTUATORS (MS7505),
T6031H THERMOSTAT AND W7459 OR W7212 SOLID STATE ECONOMIZER LOGIC MODULE)
PRODUCT DATA
FEATURES
C7046C Discharge Air Sensors have probe lengths of 8 in.
(203 mm) and nominal sensor resistance of 3000 ohms at
C7046C
77°F (25°C).
•
•
•
•
No setting or calibration required.
Solid state components not affected by dust or dirt.
Fast reacting.
M7415/M8405
Rugged aluminum insertion probe.
C7150B Mixed Air Sensor is used with the W7212/W7459
Economizer Module to sense mixed or discharged air in roof-
top packaged air conditioning equipment.
C7150B
W7459A,C
•
No setting or calibration required.
C7400A Solid State Enthalpy Sensor and C7650A Solid State
Temperature Sensors are used with the W7212/W7459 Solid
State Economizer Logic Module to sense outdoor and return
air enthalpy or temperature.
W7212
•
C7400A senses and combines temperature and
humidity (enthalpy) of outdoor air (heat index).
T6031H
C7400A/C7650A
•
•
C7650A senses temperature only.
When enthalpy/temperature of outdoor air increases,
the outdoor air damper closes to a preset minimum
position.
APPLICATION
•
•
When enthalpy/temperature of outdoor air is low, the
outdoor air damper opens to reduce the building
cooling load.
The Solid State Economizer System provides an economical
method of providing cooling air by incorporating outdoor air in
the first stage of cooling in heating, ventilating and air
conditioning (HVAC) systems. The Solid State Economizer
System consists of the C7046C Discharge Air Sensor or
C7150B Mixed Air Sensor, C7400A Solid State Enthalpy
Sensor or C7650A Solid State Temperature Sensor, M7415
or M8405 Damper Actuators or Modulating Direct Coupled
Actuators (MS7505), T6031H Thermostat and W7212 or
W7459A,C Solid State Economizer Logic Module.
Additional economizer savings are achieved when two
C7400A Solid State Enthalpy Sensors are connected to
one Logic Module for differential enthalpy changeover
control.
Contents
Ordering Information ........................................................
2
63-2484-2
SOLID STATE ECONOMIZER SYSTEM
Mounting Arrangement:
Integral mounting flange that requires two no. 8 screws (not
provided).
MS7505 Spring Return Direct Coupled Actuator
The MS7505 Series Spring Return Direct Coupled Actuators
(DCA) are control actuators that provide proportioning control
for valves and dampers. They accept a voltage signal from an
economizer to position a damper or valve at any chosen point
between fully open and fully closed.
Maximum Ambient Temperature:
250°F (121°C).
Operating Temperature Range:
40°F to 150°F (4°C to 66°C).
•
Control for air damper applications with up to 12.5 sq ft
assuming 3.5 in.-lb per sq ft of damper area, velocity
independent.
Wiring Connections:
•
•
•
•
•
•
•
Brushless DC submotor with electronic stall protection.
Patented self-centering shaft adapter.
Access cover to facilitate connectivity.
Metal housing with mechanical end limits.
Field-installable auxiliary switches.
6 in. (152 mm) leadwires.
Dimensions:
See Fig. 1.
C7150B Mixed Air Sensor
Used to sense mixed air in rooftop packaged air conditioning
equipment.
Spring return direction field-selectable.
Hub includes position indicator.
Resistance/Temperature (NTC):
Nominal Resistance: 3000 ohms at 77°F (24°C). Nominal Sen-
sitivity: 70 ohms per degree F (124 ohms per degree C) at
midrange.
SPECIFICATIONS
IMPORTANT
Maximum Ambient Temperature:
250°F (121°C).
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
these units may not exactly match the specifications
listed. Also, these products are tested and calibrated
under closely controlled conditions and some minor
differences in performance can be expected if these
conditions are changed.
Operating Temperature Range:
-40°F to +110°F (-40°C to +44°C).
Dimensions:
See Fig. 2.
Models:
C7400A Solid State Enthalpy Sensor/C7650A Solid
State Temperature Sensor
Senses enthalpy or temperature of outdoor and return air.
Specifications for each model are listed separately.
C7046 Discharge Air Sensors
Intended for use as a discharge sensor in rooftop applications.
Temperature Sensing Element:
Thermistor.
Sensing Element:
Carbon type, thermistor-resistor element.
Output Signal:
4 to 20 mA current signal; increases from 4 mA to 20 mA as
Performance Characteristics:
Reaction Time Constant with Air Approach Velocity of 8.33 ft/
enthalpy decreases.
sec (2.54 m/sec): 60 seconds.
Ambient Operating Temperature Range:
-40°F to +125°F (-40°C to +52°C).
Resistance/Temperature (NTC):
Nominal Resistance: 3000 ohms at 77°F (24°C). Nominal Sen-
sitivity: 70 ohms per degree F (124 ohms per degree C) at
midrange.
Approval:
Underwriters Laboratories Inc. Flammability Rating: UL94-5V.
Dimensions:
See Fig. 3.
1/2 (13)
DIAMETER
3/8 (10)
DIAMETER
7/8
(22)
1/4 (6)
DIAMETER
3/4 (19)
9/16
IMMERSION LENGTH: 8 (203)
(2)
(14)
1-1/2 (38)
M9087
Fig. 1. Approximate dimensions of C7046C Air Temperature Sensor in in. (mm).
3
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
Terminal Connections:
1/4 in. (6 mm) male quick connect terminals mounted on actua-
tor. Terminal arrangement is dependent on actuator model.
3/4
(19)
Ambient Operating Temperature Range:
-40°F to +125°F (-40°C to +52°C).
Voltage and Timing:
See Table 1.
3/16 (5) DIAMETER
Dimensions:
See Fig. 4.
Shaft:
Single-ended drive shaft with crank arm supplied.
Flammability Rating:
Underwriters Laboratories Inc. UL94-5V.
2
(51)
Approval:
Underwriters Laboratories Inc. Component Recognized: File
No. E4436, Guide No. XAPX2, Vol. 9, Section 1, 7-25-83.
SPECIFICATIONS: M7215
Models: ML7215: 25 lb-in. (2.8 Nm) torque, foot-mounted
spring-return damper motor with 2-10 Vdc feedback signal.
Accepts 2-10 Vdc control signal.
2-1/2 (64)
M9084
Fig. 2. Approximate dimensions of C7150B Mixed/
Discharge Air Sensor in in. (mm).
Dimensions: See Fig. 4.
Electrical Ratings:
Supply Voltage: 24 ±6 Vac 50/60 Hz.
Power Consumption: 24 Vac, 60 Hz: 8.7 VA. 24 Vac, 50 Hz: 8.4
5/16 (8)
VA.
Torque:
3-5/32
Lift and Hold: 25 lb-in. (2.8 Nm). Spring Return: 25 lb-in. (2.8
Nm). Breakaway: 40 lb-in. (4.5 Nm).
+
(80)
S
2-3/4
IMPORTANT
(70)
Never use motor continuously at the breakaway
torque rating.
NOTE: Breakaway torque available to overcome occasional
large loads such as a seized damper.
9/16
(14)
3-7/8 (96)
7/32
(6)
1 (25)
M9096
Stroke:
Travel: 90°.
Timing:
Fig. 3. Approximate dimensions of C7400A Solid State
Enthalpy Sensor/C7650A Solid State Temperature Sensor
in in. (mm).
Driving: 86 ±5 seconds.
Spring Return: 13 ±5 seconds.
Motor Rotation (Viewed From Shaft End):
Closed Position: Limit of clockwise rotation.
Open Position: Limit of counterclockwise rotation.
Crank Arm Rotation Limits: See Fig. 8.
M7415A, M8405A Damper Actuators
Provides control of economizer systems on HVAC equipment.
Actuator Rotation:
Shipped with shaft in closed position.
Closed position is the limit of clockwise rotation; open position
is the limit of counterclockwise rotation as viewed from the
shaft end of the motor.
Ambient Ratings:
Temperature:
Operating: -25°F to +125°F (-32°C to +52°C).
Storage: -30°F to +150°F (-34°C to +66°C).
Humidity: 5 to 95 percent RH, noncondensing.
Auxiliary Switch Rating (M8405A only):
24 Vac, 20 VA inrush, 20 VA run.
Terminal Connections: 1/4 in. (6 mm) quick-connect termi-
nals mounted on motor.
63-2484—2
4
SOLID STATE ECONOMIZER SYSTEM
Shaft: Single-ended drive shaft with crank arm supplied.
Approvals:
Underwriters Laboratory Inc.: Flammability Rating: UL94-5V.
Component Recognized: File No. E4436, Guide No.
XAPX2, Vol. 9, Section 1, 7-25-83.
Reliability:
Full-Stroke Cycles: 60,000. Repositions: 1,500,000.
4-1/2 (114)
1/4 (6)
1-3/8 (35)
3-1/8 (79)
4-1/32
(102)
4-1/2
(114)
4-1/2
(114)
5
(127)
2-1/4 (57)
3-1/2 (89)
7/16
(11)
1-1/4
(32)
5-3/16 (132)
TOP VIEW
SIDE VIEW
POWER END VIEW
M3851
Fig. 4. M7215, M7415A, and M8405A Damper Motor dimensions in in. (mm).
Table 1. M7415A/M7405A Actuator Specifications.
Power (Vac)
Torque
Timing
Voltage (Vac)
50/60 Hz
Stroke
(°)
Open Rotation
(lb-in.) (Nm) (Shaft End View) (Shaft End View)
Spring Return
a
Model Number
(Drive) (Hold) (sec)
b,c
24
24
24
24
24
8
5
3
5
5
5
90
90
90
90
90
90
90
90
90
90
25
25
25
25
44
2.8
2.8
2.8
2.8
5
ccw
cw
M7415A
b,d
7
ccw
cw
M8405A
b,c
8
cw
ccw
cw
M7415B
b,c
8
ccw
M7215A
a,b,c,e
13
cw/ccw
cw/ccw
MS7505
a
Timing with 60 Hz power.
Spring return.
b
c
d
e
Modulating.
Three-position with field adjustable minimum position control.
Mounts directly on damper shaft.
Control Range, Element Temperature and Differential:
See Table 2.
T6031H Thermostat
A standard spdt switch, without a case, that acts as a
changeover thermostat.
Approval:
Underwriters Laboratories Inc. Listed:
File E4436, Vol. 4, Guide No. XAPX2.
Electrical Rating:
0.25A at 1/.4V to 12 Vdc inductive load.
Dimensions:
See Fig. 5.
5
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
3/4 (19)
MOUNTING
1
HOLES
4-1/16
(103)
4-3/16
(106)
OVERALL LENGTH: 5 (127)
2-3/16
(56)
OVERALL DEPTH LESS
ADJUSTING DIAL SHAFT:
2-1/8 (54)
ON THE 114496 BRACKET, THE MOUNTING HOLES ARE TWO
1
NO. 8-32 TAPPED HOLES. THE 107940 BRACKET IS MOUNTED
WITH A 5/32 (4) DIAMETER HOLE AT THE TOP AND A VERTICAL
5/32 X 5/16 (4 X 8) SLOT AT THE BOTTOM.
M9090
Fig. 5. Approximate dimensions of back mounting bracket
for T6031H in in. (mm).
7/8 (22)
W7459A,C Solid State Economizer Logic Module
Used with C7400 Sensor or C7650A Sensor and M7415 or
M8405 Actuator to proportion outdoor and return air dampers
for economizer control in commercial HVAC equipment.
2-13/16 (71)
1-1/4
(32)
Electrical Ratings:
Input Voltage: 24 Vac, 50/60 Hz.
Power Consumption: 5.5 VA.
5/8
(16)
Relay Contact Rating at 24 Vac: 1.5A run, 3.5A inrush.
Temperature Ratings:
-25°F to +125°F (-32°C to +52°C).
M9085A
Fig. 6. Approximate dimensions of W7459 Solid State
Economizer Logic Module in in. (mm).
Approval:
Underwriters Laboratories Inc.: Flammability Rating: UL94V-5V.
Specifications:
See Table 3.
SPECIFICATIONS: W7212A LOGIC MODULE
Dimensions:
See Fig. 6.
Models: W7212A, W7213A, W7214A Logic Modules: for use
with any Honeywell 2-10 Vdc actuator; includes DCV input;
adjustable exhaust fan setpoint.
NOTES:
—
All models include a minimum damper position
potentiometer, and setpoints for: occupied/unoccu-
pied control, DCV operation, and DCV maximum.
Occupied/Unoccupied overrides minimum damper
position setting when building is unoccupied.
—
Dimensions: See Fig. 7.
Electrical Ratings:
Input Voltage: 24 Vac ±20%; 50/60 Hz (Class 2). Nominal
Power Consumption (at 24 Vac, 60 Hz): 11.5 VA.
Relay Contact Rating at 30 Vac (maximum power from class 2
input only): 1.5A run, 3.5A inrush.
63-2484—2
6
SOLID STATE ECONOMIZER SYSTEM
IMPORTANT
All inputs and outputs must be 24 Vac Class 2.
C7400 Solid State Enthalpy Sensor.
C7650 Dry Bulb Temperature Sensor.
S963B1128 Remote Potentiometer to provide remote control of
damper minimum position.
Ambient Ratings:
Temperature: -40°F to +149°F (-40°C to +65°C). Humidity: 5 to
95 percent RH (noncondensing).
ST6008 Energy Management Timer for occupied/unoccupied
control.
Inputs:
4-3/8 (112)
Enthalpy (C7400)
Dry Bulb Temperature (C7650)
Discharge Air (C7046)
Mixed Air (C7150)
DCV Sensor (C7232): 0/2-10 Vdc control signal;
100K ohm input impedance.
1-5/8
(41)
Outputs:
Actuator Signal: 2-10 Vdc. Minimum Actuator Impedance: 1K
ohm.
2-1/16
(53)
Exhaust Fan: Contact closure.
24 Vac Out: 25 VA maximum.
1-15/16
(49)
Approvals:
Underwriters Laboratories Inc.: UL873 listed.
Flammability Rating: UL94-5VB.
4-1/8
(104)
Plenum Rated.
CE.
C-tick.
Accessories:
4074EJM Bag Assembly. Consists of: Checkout jumper, 620
ohm, 1.2K ohm, 5.6K ohm, and 6.8K ohm checkout resis-
tors.
1/8 (4)
2-5/8 (66)
M20578B
C7046A Discharge Air Temperature Sensor. C7150B Mixed Air
Temperature Sensor.
C7232A,B Carbon Dioxide Sensors.
Fig. 7. Logic module dimensions in in. (mm).
Table 2. T6031H Thermostat Specifications.
Max Element
Temperature
Control Range
Differential
°F °C
2°
Capillary Length
ft
Bulb Size
mm
3/8 x 3-1/2 10 x 89
Model
Number
Type of
Mounting
°F
°C
°F
°C
66°
m
in.
T6031H
0° to 95°
-18° to +35° 150°
3°
Back
2
0.6
Table 3. W7459A,C,D Specifications.
Discharge Air Minimum Position
For Use with
Actuator
Terminals for Remote
Output
Model
Temperature Input Potentiometer Adjustment Minimum Damper Position Relays
W7459A M7415
W7459C M8405
Thermistor Sensor
Spst control
Yes
Yes
No
2 spdt
2 spdt
No. Minimum position
adjustment is built into
M8405 Actuator
W7212A M7215
MS7505
Thermistor sensor
Yes
Yes
2 spdt
4. After installation is complete, check out product opera-
INSTALLATION: M7215, M7415, M8405
tion as provided in these instructions.
When Installing this Product...
CAUTION
1. Read instructions carefully. Failure to follow them could
damage the product or cause a hazardous condition.
2. Check ratings and description given in the specifications
to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
7
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
WIRING: M7215, M7415, M8405
CAUTION
Spring-return assembly can release.
Leave end covers attached to the motor.
Personal Injury Hazard.
All wiring must comply with applicable codes and ordinances.
Refer to Fig. 9 for typical hookup.
Location and Mounting
M7215
L1
L2
TR
Locate motor as close as possible to the equipment to be
controlled. Refer to Fig. 4 for mounting dimensions.
TR1
IN+
2-10
+
–
1. Mount motor with the shaft horizontal to ensure maxi-
VDC
CONTROL
mum life.
IN–
NOTE: Operation in other positions is possible when required
by the application.
OUT
–
1
OUT
+
METER INDICATING
MOTOR POSITION
(2-10 VDC)
2. Remove crank arm (secured with two screws) from the
motor hub.
1
DOTTED LINE REPRESENTS INTERNAL
IMPORTANT
CONNECTIONS OF THE M7215 ACTUATOR.
M17365
Position crank arm on hub so it does not strike motor
mounting surface during any portion of full stroke.
See Fig. 8.
Fig. 9. Typical M7215 wiring.
3. Reposition the crank arm to accommodate specific
C7046C Discharge Air Temperature Sensor
damper requirements.
The sensor assembly consists of an aluminum sensor probe
(element housed internally) with attached flange that can be
mounted on a flat duct or plenum surface, or in a 2 in. by 4 in.
(51 by 102 mm) junction box, using two no. 8 screws.
Connections to the sensor are made through two 6 in. (152
mm) leadwires.
NOTE: Crank arm position is adjustable in eight degree
increments.
4. Reconnect crank arm to the motor hub.
5. If there is an excess length of linkage rod, cut it to size.
Make necessary minor adjustments until desired opera-
tion is obtained.
Location
6. Tighten all nuts and set screws.
Locate the sensor in the air duct or plenum where it can
sample average air temperature. Avoid locations where air
stratification can cause sensing errors.
Mounting
To mount the C7046C Sensor on a flat duct or plenum surface
(see Fig. 10):
MAXIMUM
OPEN
MAXIMUM
CLOSED
1. Cut a 1/2 in. (13 mm) hole in the duct or plenum surface
at the desired location.
1
POSITION
POSITION
2. Insert the sensor probe into the duct or plenum hole until
the flange rests against the duct or plenum wall.
3. If necessary, use the flange as a template to mark and
drill two holes for no. 8 mounting screws.
4. Fasten the sensor to the duct or plenum surface with the
two no. 8 sheet metal screws (not provided).
MOTOR MOUNTING SURFACE
CRANK ARM FIELD ADJUSTABLE IN 7.5 DEGREE INCREMENTS.
1
M3850
Fig. 8. Limits of crank arm rotation.
63-2484—2
8
SOLID STATE ECONOMIZER SYSTEM
To mount the C7046C Sensor in a junction box (see Fig. 11):
SYSTEM DUCT OR PLENUM
1. Cut a 1/2 in. (13 mm) hole in the duct or plenum surface
at the desired location.
2. Remove the center rear knockout from the junction box
and insert the sensor probe through the knockout with
the flange flat against the junction box.
3. Using the flange as a template, mark and drill two holes
in the junction box and the duct or plenum surface for no.
8 mounting screws.
NO. 8
MOUNTING
SCREWS (2)
FLANGE
SENSOR PROBE
4. Insert the sensor probe through both the junction box
knockout and the 1/2 in. (13 mm) hole drilled in the duct
or plenum and fasten the junction box and sensor to the
duct or plenum surface with the two no. 8 sheet metal
screws (not provided).
1
TO APPROPRIATE
SYSTEM COMPONENTS
(SEE WIRING DIAGRAM)
SENSOR WIRES WITH
2 SOLDERLESS
CONNECTORS
1
SCREWS NOT PROVIDED.
M9086
Fig. 10. Mounting C7046C Air Temperature Sensor on duct
or plenum.
STANDARD 2 X 4 (51 X 102)
OUTLET BOX (OPTIONAL)
SENSOR PROBE
FLANGE
CONNECTOR
AND
LOCKNUT
BLANK
FACEPLATE
(OPTIONAL)
TO APPROPRIATE
SYSTEM COMPONENTS
(SEE WIRING DIAGRAM)
1
SENSOR WIRES WITH 2
SOLDERLESS CONNECTORS
1
SCREWS NOT PROVIDED.
SYSTEM DUCT OR PLENUM
M9088
Fig. 11. Mounting C7046C Discharge Air Temperature Sensor in junction box.
Wiring
CAUTION
Can Cause Electrical Shock or Equipment Damage.
Disconnect the power supply before connecting the
wiring.
Connect low voltage wiring from the sensor to the appropriate
system component terminals using solderless connectors as
shown in Fig. 10 and 11.
Make sure wiring complies with applicable local codes,
ordinances and regulations.
9
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
IMPORTANT
Dimensions, Approximate 9.72 in. high x 3.94 in. wide x 2.95
in. deep (247 mm high x 100 mm wide x 75 mm deep)
Fail Safe Mode Spring Return
Electrical Connections Enclosed screw terminal strip (22 to
14 AWG) (Enclosed screw terminal strip [0.324 to 2.08 sq
mm])
Failure to follow these wiring practices can introduce
electrical interference (noise) that can cause erratic
system operation:
a. Keep wiring at least one foot away from large induc-
tive loads such as motors, line starters, lighting bal-
lasts, and large power distribution panels.
b. Shielded cable is required in installations where
these guidelines cannot be met.
c. Ground shield only to grounded controller case.
d. Make good physical wiring connections to ensure
good electrical connections.
Frequency 60 Hz
Manual operation Manual Crank
Spring Return Direction By orientation
Rotational Stroke 95 ±3 degrees
Rotational Stroke Adjustment Mechanically limited 5 degree
increments
Shaft Adapter Type Self-centering clamping
Compatible Damper Shafts 3/8 to 1.06 round or 3/8 to 11/16
square (10 to 27 round or 10 to 18 square)
Mounting Direct Coupled
e. Make sure that building earth ground connections
are not intermittent or missing.
f. Mount sensor only in recommended environment.
External Auxiliary Switches Available Yes
Rated Torque (44 lb-in. (5 Nm)
MS7505 Damper Actuators
Maximum Stall Torque 75 lb-in. (8.5 Nm)
Spring Return Torque 44 lb-in. (5 Nm)
Maximum Noise Rating, Holding (dBA @ 1m) 20 (no audi-
ble noise)
Location and Mounting
Maximum Noise Rating, Driving (dBA @ 1m) 40
Environmental Rating NEMA2
Ambient Temperature Range -40°F to +140°F (-40°C to
+60°C)
LOCATION
Locate the actuator as close as possible to the equipment to
be controlled. Refer to Fig. 12 for mounting dimensions.
Storage Temperature Range -40°F to +158°F (-40°C to
+70°C)
Operating Humidity Range (% RH) 5 to 95% RH, non-con-
Wiring
Disconnect power supply before connecting wiring to prevent
electrical shock or equipment damage. All wiring must comply
with applicable local codes and ordinances.
densing
Materials Aluminum housing, Plenum rated plastic access
cover
Weight 6 lb (2.72 kg)
Approvals: CE: 89/336/ECC, 73/23/EEC
C-Tick N314
Canadian Underwriters Laboratories, Inc. cUL C22.2 No.
24-93
Underwriters Laboratories, Inc. UL873, Plenum Rated
Includes Mounting Bracket, Self-Centering Shaft Adapter,
3mm crank
3-15/16 (100)
1-9/16
(40)
1-9/16
(40)
3 (76)
MIN.
2-1/2
(64)
FROM
SHAFT
END
MIN.
1-9/16
(40)
T6031H THERMOSTAT
Location and Mounting
9-3/4
(247)
6-1/8
(156)
The T6031H Thermostat mounts either vertically or horizontally
on a wall or panel. Locate the remote bulb as far from the
controller as capillary tubing allows.
Mounting Sensing Elements
T6031H: Install the bulb in the return airflow where air of
average temperature can circulate around it.
IMPORTANT
2-15/16 (75)
Do not overtighten clamps to the point of distorting
the sensor bulb because overtightening causes a sig-
nificant shift in bulb calibration.
1/4 (6)
3 (76)
MIN.
Mounting Thermostat
Mount the thermostat using the back mounting plate as shown
in Fig. 5.
M20952
Fig. 12. MS7505 Dimensions Diagram.
63-2484—2
10
SOLID STATE ECONOMIZER SYSTEM
dimensions). Mount device in a location protected from rain,
snow and direct sunlight. Secure device to sheet metal using
the two supplied mounting screws.
Wiring
CAUTION
Disconnect power supply before connecting wiring.
Can Cause Electrical Shock or Equipment Damage.
CAUTION
Equipment Damage Hazard.
Mounting screws longer than 5/8 in. can damage
internal motor components.
When mounting the module to an M7215 use only the
included #6 5/8 in. thread-forming screw.
Disconnect the power supply before connecting wiring to
prevent electrical shock and equipment damage. All wiring
must comply with applicable local codes and ordinances.
Refer to Fig. 13 and the wiring diagrams furnished with the
system equipment to complete the wiring.
M7415, M7405 OR
M8405 ACTUATOR
TEMPERATURE
RISE
SETPOINT
SWITCH
BREAKS R-B;
MAKES R-W
ON RISE
DIFFERENTIAL
SETPOINT
FOR T6031H
MAKES R-B;
BREAKS R-W
ON FALL
W
B
R
W7459
ECONOMIZER PACKAGE
M9091
Fig. 14. Mounting W7459 on M7415 or M8405 Damper
Actuator.
R AND W LOCATIONS
DEPEND ON MODEL
AND CONSTRUCTION
M9089
Fig. 13. T6031H switch terminal arrangement and
switching.
M7215 DAMPER MOTOR
W7459A,C AND W7212 Solid State
Economizer Logic Module
ECONOMIZER
LOGIC MODULE
Location and Mounting W7459 Economizer
Logic Module
Mount the W7459 Economizer Logic Module on the side of the
M7415 or M8405 Damper Actuator. When planning the
installation, allow enough clearance for maintenance and
service. Install the W7459 Economizer Logic Module where it
is protected from rain and snow. One mounting screw is
supplied to secure the W7459 to the actuator (after the
actuator is mounted). See Fig. 14.
5/8 INCH SCREW INCLUDED WITH LOGIC MODULE. M20717B
Location and Mounting W7212
The logic modules mount on an M7215 or a sheet metal duct
or panel. When planning the installation, allow enough
clearance for maintenance and service (see Fig. 15 and 16 for
Fig. 15. Direct mounting of module.
11
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
4500
4000
3500
3000
2500
2000
1500
1000
3,000 OHMS AT
77F (25C)
55
60
15
65
70
75
80
85
30
90
95
35
100
F
20
25
C
TEMPERATURE (DEGREES)
M20601
M9099
Fig. 16. Mounting the W7212 module on sheet metal.
Fig. 17. C7046C and C7150B Air Temperature Sensors
resistance versus temperature.
C7400 Enthalpy Sensor and C7650A
C7400A Solid State Enthalpy Sensor
Temperature Sensor Location and Mounting
The C7400A Solid State Enthalpy Sensor is used with a solid
state economizer control and damper actuator to proportion an
outdoor air damper in a ventilation system.
Outdoor air sensing: Mount the C7400 Enthalpy Sensor or
C7650A Temperature Sensor in any orientation where it is
exposed to freely circulating air but protected from rain, snow
and direct sunlight.
Figure 18 is a partial psychometric chart with single C7400A
Sensor and W7459A Economizer Logic Module performance
curves. The curves illustrate the reset in the temperature
control point due to changes in relative humidity.
Return air sensing: For differential enthalpy or temperature
control, a second C7400 Enthalpy Sensor or C7650A
Temperature Sensor is connected to the W7459 or W7212.
Mount the second sensor in the return air duct as far as
possible from the outdoor air sensor.
The enthalpy control setpoint A,B,C or D combines
temperature and humidity conditions, resulting in the control
curve shown in Fig. 18. When the enthalpy or outdoor air is
below (left of) the appropriate curve, the outdoor air damper
can proportion open on a call for cooling. If outdoor air enthalpy
rises above (to the right of) the control curve, the outdoor air
damper closes to the minimum position.
Wiring
For differential enthalpy, turn the control setpoint to D (fully
clockwise). If outdoor air enthalpy is lower than return air enthalpy,
the outdoor air damper proportions open on a call for cooling.
CAUTION
Can Cause Electrical Shock or Equipment Damage.
Disconnect power supply before connecting wiring.
If outdoor air is higher enthalpy than return air enthalpy, the
outdoor air damper closes to minimum position. Differential
enthalpy control provides energy savings and increased
comfort by using the air with the lowest enthalpy.
Disconnect the power supply before connecting wiring to
prevent electrical shock or equipment damage. All wiring must
comply with applicable local codes, ordinances and
regulations.
If outdoor air enthalpy and return air enthalpy are equal, the
outdoor air damper proportions open on a call for cooling.
The relationship between the C7400A Sensor output current
and relative humidity is shown in Fig. 19.
OPERATION AND CHECKOUT
C7046C (Discharge) and C7150B (Mixed) Air Sensors
C7650A Solid State Temperature Sensor
The C7046C discharge air sensor is applied following the coils
in the supply air to the conditioned space. The C7150B mixed
air sensor is mounted in the mixing box, where the “best”
combination of outdoor and return air temperature can be
measured. Use either a discharge or a mixed air sensor to
provide input to the economizer module through T and T1
Terminals.
The C7650A Solid State Temperature Sensor is used with a
solid state economizer control and damper actuator to
proportion an outdoor air damper in a ventilation system.
When outdoor air temperature is higher than return air
temperature, the outdoor air damper closes to the minimum
position. When the outdoor air temperature and the return air
temperature are equal, the outdoor air damper proportions
open on a call for cooling.
The relationship between the C7650A Sensor output current
and the air temperature is shown in Fig. 20.
63-2484—2
12
SOLID STATE ECONOMIZER SYSTEM
85
90
95 100 105 110
(29) (32) (35) (38) (41) (43)
CONTROL CONTROL POINT
CURVE
APPROX. °F (°C)
AT 50% RH
80
(27)
A
B
C
D
73 (23)
70 (21)
67 (19)
63 (17)
75
(24)
70
(21)
65
(18)
60
(16)
A
55
(13)
B
50
(10)
C
45
(7)
D
40
(4)
35
(2)
1
A
B
C
D
35
(2)
40
45
50
55
60
65
70
75
80
85
90
95 100 105 110
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
HIGH LIMIT CURVE FOR W7210D, W7212, W7213, W7214, W7340B.
M11160C
1
Fig. 18. Partial psychrometric chart with single C7400A Solid State Enthalpy Sensor and W7212 or W7459 Solid State
Economizer Logic Module performance curves.
C7400A OUTPUT CURRENT
100
19
LED ON
18
17
16
15
14
90
80
70
60
D
LED ON
LED OFF
C
LED ON
LED OFF
B
13
12
50
40
LED ON
LED OFF
A
11
10
9
30
20
10
LED OFF
95
85 90
F
100
40
60
65
45
50
55
70
75
80
NOTE: A,B,C,D ARE W7459 SWITCHING SETPOINTS.
40
(4)
50
(10)
60
(16)
70
(21)
80
(27)
90
(32)
100
(38)
M7578A
TEMPERATURE F (C)
M9101
Fig. 20. C7650A Solid State Temperature Sensor output
current vs. temperature.
Fig. 19. C7400A Sensor output current vs. relative
humidity.
13
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
The economizer functions as a true first stage of cooling and
provides maximum fuel economy during the cooling cycle. The
economizer is automatically locked out during heating. It holds
the outdoor air damper at the minimum position setting. On a
call for cooling by the space thermostat, the system operates
as follows:
M7415 Damper Actuator
Single M7415 Damper Actuator accepts thermistor sensor
input from a C7046A or a C7150B Mixed Air Sensor mounted
in discharge or mixed air duct. See Fig. 27.
During the occupied period, on a call for cooling, when outdoor
air temperature or enthalpy conditions are low, the M7415
Actuator proportions to maintain between 50°F (10°C) and
56°F (13°C) at the thermistor sensor.
When the enthalpy or temperature of the outdoor air is below
the setpoint, the outdoor air damper is proportioned open (and
the return air damper is proportioned closed) to maintain
between 50°F and 56°F (10°C and 13°C) at the mixed/
discharge air sensor. During economizer operation, the
mechanical cooling is operated by stage 2 cooling on the
space thermostat.
If the mixed or discharge temperature is above 56°F (13°C),
the M7415 Actuator opens to admit additional outdoor air until
the temperature returns to the 50°F (10°C) to 56°F (13°C)
range. If the mixed or discharge air temperature is below 50°F
(10°C), the actuator proportions closed, shutting the outdoor
air damper until the temperature returns to the 50°F (10°C) to
56°F (13°C) range. During the occupied period, the actuator
does not close past the minimum position.
When the enthalpy or temperature of the outdoor air is above
the setpoint, the outdoor air damper closes to its minimum
position. A call for cooling from the space thermostat turns on
the mechanical cooling.
If the fully open M7415 Actuator cannot satisfy the space
demand, mechanical cooling is sequenced on.
During the unoccupied period, the M7415 Damper Actuator
spring-returns the outdoor air damper to the fully closed
position.
During the unoccupied period, the M7415 Actuator overrides
the minimum position setting and drives fully closed. On a loss
of power, the actuator spring-returns fully closed.
W7212A Economizer Logic Module
W7212A economizer logic module used with C7400 enthalpy
If terminals P and P1 are jumpered, the M7415 drives fully
open; however, if terminals P and P1 are left open, the M7415
drives fully closed. The M7415 minimum position adjustment
drives the motor open when the resistance across P and P1 is
minimal. Increasing the amount of resistance across these
terminals drives the actuator closed.
sensors, M7215 or MS7505 damper actuators and C7232 CO
sensors to proportion outdoor and return air dampers from
economizer and demand control ventilation in commercial
HVAC equipment.
2
W7212A Optional Applications
M8405 Damper Actuator
HEAT PUMP CHANGEOVER (W7213, W7214 ONLY)
In heat pump applications, the controller must have control of
the changeover valve. To provide the logic module with the
An spst low-voltage controller is used to control the M8405
Actuator as follows:
information necessary for proper information, there must be a
connection to the logic module O/B terminal. This terminal
alerts the logic module as to when the system operates in
cooling (the only time the economizer is used).
a. Fully open—when the controller circuit closes to pro-
vide 24 Vac to terminals D and T, the actuator is
energized and runs fully open.
b. Fully closed—when the controller circuit opens,
power is removed from terminals D and T, and the
actuator spring-returns to the fully closed position.
c. Mid-position—when the controller circuit closes to
provide 24 Vac to terminals T and X, the actuator is
energized to run to the adjustable mid-position (mini-
mum position).
W7213 (CHANGEOVER TERMINAL B)
Connect the B terminal according to the following details:
— 24V power to B: System is in heating mode.
— No power to B: System is in cooling mode.
W7214 (CHANGEOVER TERMINAL O)
Adjustable minimum position can be reached from either the
fully closed or fully open position. From fully closed, the
actuator drives open to the minimum position; from fully open,
the actuator spring-returns to minimum position.
Connect the O terminal according to the following details:
— 24V power to O: System is in cooling mode.
— No power to O: System is in heating mode.
SETTINGS AND ADJUSTMENTS
W7459A,C Solid State Economizer Logic
Module
Adjusting Minimum Damper Position
The purpose of an economizer is to use outdoor air for cooling
whenever possible, to reduce air conditioner compressor
operation. The W7459 Economizer System, when wired as
shown in Fig. 27, responds to a signal from the cooling
thermostat. This system uses a C7400 Enthalpy Sensor or a
C7650A Temperature Sensor. It responds to both dry bulb
temperature and humidity, allowing the use of outdoor air at
higher temperatures for free cooling when the humidity is low.
The minimum position potentiometer keeps the outdoor air
damper from completely closing during system operation to
allow ventilation.
63-2484—2
14
SOLID STATE ECONOMIZER SYSTEM
M7415 and M8405 Damper Actuators
W7459A,C Solid State Economizer Logic
Module
Adjusting Minimum Position (Ventilation)
The M7415 Damper Actuator is adjusted for desired minimum
position using a Q709 Actuator Mounted Minimum Position
Potentiometer and/or a remote S963B1136 Manual
Potentiometer. The M8405 Damper Actuator has an integral
thumbwheel for minimum position adjustment.
Two potentiometers with small screwdriver slots for adjustment
are located on the face of the module.
Minimum Position Adjustment
W7459A ECONOMIZER LOGIC MODULE
M7415 Minimum Position Adjustment
1. Make sure the factory-installed jumper is in place
across terminals P and P1 (terminals T and T1 are
disconnected.
2. Connect 24 Vac at terminals TR and TR1 and adjust the
potentiometer on the face of the W7459A with a small
screwdriver for desired minimum position.
1. Run actuator to fully closed position and disconnect 24
Vac from terminals TR and TR1.
2. Connect minimum position potentiometer to terminals P
and P1 (T and T1 are disconnected).
3. Reconnect 24 Vac to terminals TR and TR1 and adjust
the potentiometer for the desired minimum position.
4. When the Q709 Actuator Mounted Minimum Position
Potentiometer is used and a remote potentiometer is not
connected in series, jumper terminals P and P1 on the
Q709A.
W7459C ECONOMIZER LOGIC MODULE
1. Connect 24 Vac at terminals TR and X (D is not connected).
2. Adjust thumbwheel on motor for desired minimum position.
M8405 Minimum Position Adjustment
Enthalpy Changeover Setpoint
1. Connect the 24 Vac to the actuator at terminals T and X
(D is not connected).
Single enthalpy: the enthalpy changeover setpoint is set to
return the outdoor air damper to the minimum position when
the enthalpy rises above its setpoint. The enthalpy setpoint
scale markings, located on the W7459, are A, B, C, D; see Fig.
18 for the corresponding control point. The factory-installed
2. Adjust the thumbwheel on the actuator for desired
minimum position.
Discharge Air Temperature Setpoint
Adjustment—M7415 Only
620-ohm jumper must be in place across terminals + and S .
R
This temperature range can be adjusted either up or down by
wiring a resistor in series (to increase the setpoint) or in parallel
(to decrease the setpoint) with the C7150B, depending on the
application. See Fig. 21 and 22 for explanation.
ENTHALPY
CHANGEOVER
SETPOINT
R
T
C7150
T1
M7415
MINIMUM
DAMPER
RESISTOR VALUE (OHMS)
C7150B SETPOINT °F (°C)
POSITION
SETTING
1
681
2760
54.5—61.5 (12.5—16.4)
68.4—80.1 (20.3—26.8)
87.4—110.3 (30.8—45.5)
104.7—150 (40.4—65.5)
116—194 (46.7—90)
120—300 (49—149)
3650
LED LIGHTS
4420
WHEN OUTDOOR
AIR IS SUITABLE
FOR FREE COOLING
4750
4870
NO RESISTOR
50—56 (10—13.3)
USE 1%, 1/8 W OR HIGHER RESISTOR
M1544C
Fig. 21. Increasing C7150B setpoint.
1
MINIMUM DAMPER POSITION ADJUSTMENT
IS PRESENT ONLY ON W7459A,D MODELS.
M9098B
T
R
Fig. 23. Location of enthalpy setpoint potentiometer,
minimum position potentiometer and LED.
C7150
T1
M7415
Differential Enthalpy Changeover Setting
RESISTOR VALUE (OHMS)
C7150B SETPOINT °F (°C)
18.2K
24K
36—44 (2.2—6.7)
39.5—47 (4.0—8.3)
42—49 (5.6—9.4)
50—56 (10—13.3)
(USE THIS OPTION ONLY WITH TWO-STAGE COOLING
THERMOSTATS.)
Differential enthalpy control uses two C7400 Enthalpy Sensors
or two C7650A Temperature Sensors connected to one W7459
Solid State Economizer Logic Module.
30K
NO RESISTOR
USE 1%, 1/8 W OR HIGHER RESISTOR
M1545C
Fig. 22. Decreasing C7150B setpoint.
15
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
The setpoint scale markings, located on the W7459, are A,B,C
and D. Turn the setpoint potentiometer fully clockwise to the D
setting. The economizer selects the air that has lower enthalpy
or temperature for cooling; for example, if outdoor air has lower
enthalpy or temperature than return air, the outdoor air damper
is opened to bring in outdoor air for free cooling.
3.
a. On the standard (non-differential) economizers, the
logic module checks the outdoor air C7400 Enthalpy
Sensor or C7650 Temperature Sensor to determine if
the enthalpy or temperature is below the setpoint.
b. On the differential economizers, the logic module
checks to determine if the outdoor air temperature is
below the return air temperature.
Remote Minimum Position Control
4. If the logic module uses the outside air for cooling, the
mixed air sensor prevents the entering air from going
below 50°F (10°C).
Remote control of outdoor air dampers is desirable when
requiring temporary additional ventilation. The addition of a
S963B1128 Remote Potentiometer allows occupants to open
or close the dampers beyond minimum position for modified
ventilation.
a. On the modulating system, the control closes the
outside air damper and opens the return air damper
to mix the outside air and return air to maintain 50°–
55°F (10°–13°C).
b. On the three-position system, the mixed air sensor
switch opens, closing the fresh air damper until the
mixed air sensor temperature returns above 55°F
(13°C), closing the switch and re-opening the outside
air damper.
SEQUENCE OF OPERATION
Economizer Sequence of Operation
5.
a. If the logic module senses that the outside air is not
suitable for cooling, the air conditioning unit com-
pressor is energized and the space is cooled with
refrigerated air.
(WITH AND WITHOUT DIFFERENTIAL ENTHALPY)
The economizer operating sequence for both the modulating
and the three-position control systems are identical when the
outdoor enthalpy temperature is above the mixed air setpoint
of 55°F (13°C). The operating sequence for both, using a
standard two-stage thermostat is:
b. On the two-stage thermostat, the economizer is the
first stage if the outside air temperature is suitable for
cooling. The compressor on the unit is energized if
the second stage of the thermostat is energized,
thereby creating an integrated economizer.
6. Refer to Table 4 for further information on outside air
damper positions.
1. The first stage of the thermostat signals a need for
cooling.
2. The W7459 Solid State Economizer Logic Module
begins to make decisions regarding the unit/
economizer operation.
Table 4. Outdoor air damper positions.
Standard Economizer Damper Position
Differential Enthalpy Damper Position
Return
Outside
1
2
2
1
2,3
2,3
Temperature
Modulating
Closed
3-Position
Closed
Temperature
80
Modulating
Closed
3-Position
Closed
80
85
75
80
75
Open
Closed
Open
Open
Open
Closed
Open
Open
75
Closed
Closed
70
Open
Open
Open
Open
Open
65
Open
60
Open
75
75
75
Open
Open
Open
55
Open
Open
54 and down
Modulating
Opening/Closing
Modulating
Opening/Closing
1
2
3
Standard economizer position based on enthalpy control set on the A setting and 50% relative humidity.
Closed position is either the minimum position or fully closed, depending on the job setting.
Opening/closing is dependent on the mixed air temperature.
63-2484—2
16
SOLID STATE ECONOMIZER SYSTEM
Dry Bulb Temperature Sensor(s). The C7400 responds to both
dry bulb temperature and humidity, allowing use of outdoor air
at higher temperatures for free cooling when humidity is low.
The C7650 responds only to dry bulb temperature; use only in
dry, arid climates.
OPERATION: W7212
The purpose of the economizer is to use outdoor air for
cooling, whenever possible, to reduce compressor operation.
Power at the N terminal determines the Occupied/Unoccupied
setting:
The logic module functions as a true first stage of cooling
providing maximum energy economy during the cooling cycle.
It automatically locks out free cooling during heating; holding
the outdoor air damper at the minimum position setting.
— W7212:
•
24 Vac (Occupied).
The logic module can operate as either a basic free cooling
controller, or it can incorporate additional functions. Table 5
details the input/output (I/O) logic of the module.
•
No power (Unoccupied).
— W7213,W7214:
•
W7213 (CHANGEOVER TERMINAL B)
— 24V power to B: System is in heating mode.
— No power to B: System is in cooling mode.
W7214 (CHANGEOVER TERMINAL O)
— 24V power to O: System is in cooling mode.
— No power to O: System is in heating mode.
•
S963B1128 REMOTE
POTENTIOMETER
MINIMUM
R
CW
CLOSE
POSITION
P1
ADJUSTMENT
NOTE: When module is operating in Occupied mode, the
minimum position is defined by the potentiometer.
When the module is operating in Unoccupied mode,
and there is no call for cooling, the damper drives fully
closed.
P
B
W
CW
ECONOMIZER
M20603A
When wired as shown in Fig. 28–33, the logic module
responds to the cooling thermostat signal. The system uses
C7400 Solid State Enthalpy Changeover Sensor(s) or C7650
Fig. 24. S963B1128 Remote Potentiometer used with logic
module for remote damper control.
Table 5. W7212 Economizer I/O Logic.
INPUTS
Enthalpy
OUTPUTS
a
b
Compressor
N Terminal
b
b
Occupied
Unoccupied
Demand Control
Ventilation (DCV)
Outdoor
High (Free
Cooling LED Off)
Return
Y1
On
Y2 Stage 1 Stage 2
Damper
Closed
Below set (DCV
LED Off)
Low
On
Off
Off
On
Off
On
On
Off
On
Off
On
Off
Off
Off
Off
Minimum position
On
Off
On
On
c
c
Low (Free
Cooling LED On)
High
Modulating (between Modulating (between
min. position and full- closed and full-open)
open)
Off
On
On
Off
On
On
Off
Off
On
Off
Off
On
Off
Off
Off
On
On
Off
On
Off
Off
Off
On
Off
Off
Off
Off
Off
Minimum position
Closed
d
d
Above set (DCV
LED On)
High (Free
Cooling LED Off)
Low
Modulating (between Modulating (between
min. position and DCV closed and DCV
maximum)
maximum)
e
f
Low (Free
Cooling LED On)
High
Modulating
Modulating
a
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
b
Power at N terminal determines Occupied/Unoccupied setting:
• W7212: 24 Vac (Occupied), no power (Unoccupied).
• W7213,W7214: No power (Occupied), 24 Vac (Unoccupied).
c
d
e
Modulation is based on the mixed air sensor signal.
Modulation is based on the DCV signal.
Modulation is based on the greater of DCV and mixed air sensor signals, between minimum position and either maximum posi-
tion (DCV) or fully open (mixed air signal).
f
Modulation is based on the greater of DCV and mixed air sensor signals, between closed and either maximum position (DCV) or
fully open (mixed air signal).
17
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
NOTES:
—
—
DCV and Free Cooling have setpoints and LED indications.
For models with a B terminal (W7213):
No power to B: cooling mode, free cool enabled. Module follows logic detailed above.
24V power to B: heating mode, free cool disabled. Actuator drives to minimum position (closed when Unoccupied).
For models with an O terminal (W7214):
—
24V power to O: cooling mode, free cool enabled. Module follows logic detailed above.
No power to O: heating mode, free cool disabled. Actuator drives to minimum position (closed when Unoccupied).
limit the amount of outdoor air flow into the building when the
SETTINGS AND ADJUSTMENTS: W7212
DCV overrides the mixed air sensor and allows the proper
ventilation based on occupancy. Setting the DCV maximum
position of the damper prevents the introduction of large
amounts of hot or cold air into the space by preventing the
dampers from opening 100%. Set the DCV maximum position
at the maximum design occupancy.
CAUTION
Equipment Damage Hazard.
Excessive force can damage potentiometer
controls.
Use a small screwdriver when adjusting enthalpy
IMPORTANT
With the DCV maximum position set below the mini-
mum position, the minimum position overrides the
maximum position (negating most DCV functions of
the logic module, as the damper cannot move).
changeover and minimum damper position controls.
Potentiometers with small screwdriver adjustment slots,
located on device face, provide adjustments for several
parameters (see Fig. 25 for locations on device):
NOTES:
—
When the mixed air sensor takes control based on
an increased requirement for cooling, it overrides
the DCV maximum position potentiometer and can
drive the damper full-open.
If the mixed air temperature drops to 45°F, the
mixed air sensor overrides the DCV and fully
closes the damper to protect from freezing the hot
or chilled water coils. Control returns to normal
once the mixed air temperature rises to 48°F.
— DCV setpoint.
— Minimum damper position.
— DCV maximum damper position.
— Enthalpy changeover.
— Exhaust setpoint.
—
EXHAUST
FAN SETPOINT
EXH
N1
LED LIGHTS
Set
N
2V
10V
WHEN EXHAUST
CONTACT IS MADE
Minimum Position Adjustment
EXH
P1
T1
MINIMUM DAMPER
POSITION SETTING
For detailed assistance in minimum position selection
reference the Economizer Application Guide (form 63-8594)
Ventilation section. The following provides basic guidelines for
minimum position selection and adjustment:
P
T
Min
Pos
MAXIMUM DAMPER
DEMAND CONTROL
VENTILATION SETPOINT
Open
DCV
Max
LED LIGHTS WHEN
DEMAND CONTROL
VENTILAION INPUT
IS ABOVE SETPOINT
2V
10V
AQ1
IMPORTANT
DCV
AQ
SO+
SO
SR+
SR
DCV
Set
10V
•
Adjust the minimum position potentiometer to allow
the minimum amount of outdoor air for building efflu-
ents, as required by local codes, to enter the building.
This procedure requires use of a quality thermometer
capable of reading to 0.5°F (0.25°C).
2V
DEMAND CONTROL
VENTILAION SETPOINT
Free
Cool
•
B
C
D
LED LIGHTS WHEN
OUTDOOR AIR IS
SUITABLE FOR
A
NOTE: Make minimum position adjustments with at least a
10°F (6°C) temperature difference between outdoor
and return air.
FREE COOLING
ENTHALPY
M20604
CHANGEOVER SETPOINT
Fig. 25. Potentiometer and LED locations (W7212 shown).
1. Calculate the appropriate mixed air temperature. See
Equation 1.
2. Disconnect mixed air sensor from terminals T and T1.
3. Place a jumper across terminals T and T1.
4. Ensure that either the factory-installed jumper is in place
across terminals P and P1 or, if remote damper position
is required, that it is wired according to Fig. 24 and
turned fully clockwise.
Demand Control Ventilation Setpoint
The logic module modulates the outdoor damper to provide
ventilation based on the 0/2-10 Vdc DCV. With no cooling
signal, the DCV overrides the outdoor air damper when
ventilation requires additional outdoor air.
5. Connect 24 Vac across terminals TR and TR1.
6. Carefully adjust the potentiometer on the face of the
device with a small screwdriver until the mixed air tem-
perature reaches the calculated value.
Adjusting Minimum and Maximum Positions
The minimum position potentiometer maintains the minimum
outdoor air flow into the building during the occupied period.
The minimum position allows for the building effluents. The
DCV maximum position potentiometer allows the installer to
NOTE: Ensure that the sensed air is well-mixed.
63-2484—2
18
SOLID STATE ECONOMIZER SYSTEM
7. If all minimum and maximum position adjustments are
complete, remove the T-T1 jumper and reconnect the
mixed air sensor.
NOTE: Turn the enthalpy setpoint potentiometer fully clock-
wise to the D setting.
The logic module selects the lower enthalpy air (return or
outdoor) for cooling. For example, when outdoor air has lower
enthalpy than return air, the module calls to open the outdoor
air damper to bring in outdoor air for free cooling.
EQUATION 1. FORMULA TO AID MINIMUM POSITION ADJUSTMENT.
(T × OA)+(T × RA)= T
O
R
M
Where:
= Outdoor air temperature
OA = Percent of outdoor air
T
O
Exhaust Setpoint
T = Return air temperature
The exhaust setpoint determines when the exhaust fan runs
based on damper position. When the exhaust fan call is made,
the module provides a 60 ±30 second delay before exhaust fan
activation. This delay allows the damper to reach the
R
RA = Percent of return air
T
= Resulting mixed air temperature
M
NOTE: The following sample calculation uses only Fahren-
heit temperature.
appropriate position to avoid unnecessary fan overload.
NOTES:
EXAMPLE: Assume local codes require 10% outdoor air dur-
ing occupied conditions, outdoor air is 60°F and
return air is 75°F. Under these conditions, what is
the temperature of the mixed air?
—
EF and EF1 are 24V dry contacts only. An external
line voltage contactor is required to operate the
exhaust fan.
When the exhaust fan is deactivated the EF and
EF1 contacts open immediately.
—
(0.1 × 60°F)+(0.9 × 75°F)=6.0°F + 67.5°F=73.5°F
Mixed air will be 73.5°F when OA is 60°F and RA is 75°F with
10 percent outdoor air entering the building.
CHECKOUT AND TROUBLESHOOTING
Tables 6 through 10 provide step-by-step economizer checkout
and troubleshooting steps. See Fig. 23 and 25 for enthalpy
setpoint potentiometer, minimum position potentiometer and
LED locations.
DCV Maximum Position Adjustment
1. Disconnect mixed air sensor from terminals T and T1
and short terminals T and T1.
2. Connect a jumper between terminals AQ and AQ1.
3. Connect 24 Vac across terminals TR and TR1.
4. Adjust the potentiometer on the face of the device with a
small screwdriver for desired maximum position.
5. If all minimum and maximum position adjustments are
complete, remove the T-T1 jumper and reconnect the
mixed air sensor.
ENTHALPY CHANGEOVER
SETPOINT
W7459
TR1
TR
+
B
C
1
+
+
S
O
R
S
+
D
A
C7400
DC
MILLIAMMETER
S
2
620 OHM
JUMPER
Enthalpy Changeover Setpoint
Outdoor Enthalpy Changeover Setpoint
(Single Enthalpy)
The outdoor enthalpy changeover setpoint returns the outdoor
air damper to minimum position when enthalpy rises above its
setpoint. Enthalpy setpoint scale markings, located in the
device, are A, B, C and D. See Fig. 18 for the corresponding
control point. The factory-installed 620-ohm jumper must be in
place across terminals SR and SR+. Temperature and humidity
points to the left of the selected curve will allow the dampers to
open for free cooling.
LED LIGHTS WHEN
OUTDOOR AIR IS SUITABLE
FOR FREE COOLING
1
2
INSERT DC MILLIAMMETER BETWEEN S AND S FOR CHECKOUT
O
AND TROUBLESHOOTING.
M9097
JUMPER USED FOR SINGLE ENTHALPY CONTROL.
Differential Enthalpy Changeover Setting
Differential enthalpy control uses two C7400 Enthalpy Sensors
connected to one logic module. The logic module compares
outdoor air to return air.
Fig. 26. Meter location for checkout and troubleshooting.
19
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
W7459C ECONOMIZER PACKAGE
M8405 ACTUATOR
T
M8405
MAX
T
TR
TR1
SW
SET
APPLY
24VAC T-X
MIN
FOR MIN POSN
C7400
+
T-D FOR
OUTDOOR
MAX POSN
SENSOR
+
S
O
S
X
D
S
R
+
5
C7400
S
RETURN
SENSOR
5
1K
4
+
1
3
2
4
UNOCCUPIED
2K
ST6008
TIMER
X
D
X
D
OCCUPIED
T675/T6031 MIXED
AIR CONTROL
6
55¡ F SETPOINT
W
R
C
COOL 1
COOL 2
Y1
Y2
W2
W1
Y1
Y2
W
T6031 AMBIENT
LOCKOUT CONTROL
50¡ F SETPOINT
R
HEAT 2
HEAT 1
W2
W1
X
FAN
6
DELAY
RELAY
FDR
G
G
1
3
FAN
RH
RC
L2
FDR
2
R
L1
(HOT)
T7300 OR T874
THERMOSTAT
HVAC EQUIPMENT
TERMINAL STRIP
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
MOTOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
3
4
5
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY IF A C7400 ENTHALPY SENSOR
M3865B
IS ADDED TO S AND + FOR DIFFERENTIAL ENTHALPY.
R
6
FOR T7300 ONLY.
Fig. 27. M8405A Damper Actuator used in two-stage cooling system with differential enthalpy changeover and W7459C
Economizer.
63-2484—2
20
SOLID STATE ECONOMIZER SYSTEM
W7459A ECONOMIZER PACKAGE
M7415 ACTUATOR
TR
24 VAC
TR1
TR
TR1
C7400
+
OUTDOOR
AIR
+
+
S
S
O
R
ENTHALPY
SENSOR
S
620 OHM
RESISTOR
6
5
2
1K
5
1
3
1S
2K
4
4
T
MIXED
AIR
T1
T
P
T1
P1
SENSOR
1S1
C7150B MIXED
AIR OR
P1
P
C7046A
MINIMUM POSITION
ADJUSTMENT
MINIMUM
POSITION
UNOCCUPIED
8
DISCHARGE
AIR SENSOR
ST6008
TIMER
OCCUPIED
C
M7415
TR
COOL 1
COOL 2
HEAT 2
HEAT 1
W
Y1
Y2
W2
W1
24 VAC
Y1
Y2
TR1
T6031 AMBIENT
LOCKOUT
R
CONTROL
SENSOR
T
50 F SETPOINT
T1
W2
P1
P
MIN
POS
W1
FAN
G
X
DELAY
RELAY
7
FDR
G
1
3
FAN
RH
L2
FDR
2
R
RC
L1
(HOT)
T7300 OR T874
THERMOSTAT
HVAC EQUIPMENT
TERMINAL STRIP
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
MOTOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
2
3
4
5
6
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY IF A C7400 ENTHALPY SENSOR
IS ADDED TO S AND + FOR DIFFERENTIAL ENTHALPY.
R
7
8
FOR T7300 ONLY.
M10115A
WITH T7300, USE CONTACTS A AND A INSTEAD OF S7005 TIMER.
1
2
Fig. 28. W7459A/C7400 used in two-stage cooling system with single enthalpy changeover and with M7415 Actuator.
21
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
TR
TR1
N1
N
24 VAC HOT
24 VAC COM
MINIMUM POSITION
ADJUSTMENT
24
Vac
24 Vac
COM
P1
T1
HOT
P
T
C7150B MIXED
AIR OR C7046A
DISCHARGE
AIR SENSOR
+
–
2-10 VDC CONTROL
SIGNAL INPUT
1
2
5
AQ1
–
+
0/2-10 VDC
INDOOR AIR
SENSOR
AQ
SO+
SO
SR+
3
4
EF
EF1
SR
M7215
C7400
W7212
5
OUTDOOR
AIR
+
3
620 OHM
L1
ENTHALPY
SENSOR
S
RESISTOR
(HOT)
L2
EXHAUST
FAN
Y1
Y2
C
COOL 1
COOL 2
Y1
Y2
W2
W1
A2
HEAT 2
HEAT 1
W2
W1
4
A1
G
A2
A1
G
RH
FAN
2
L2
RC
X
1
R
L1
(HOT)
HVAC EQUIPMENT
TERMINAL STRIP
T7300/Q7300
THERMOSTAT
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR. USE THE SAME
TRANSFORMER FOR T7300 AND ECONOMIZER.
3
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
4
5
T7300 TERMINALS A1 AND A2 ARE CONNECTED WHEN THERMOSTAT IS IN THE OCCUPIED MODE.
M20716D
EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.
Fig. 29. W7212 used with M7215 Damper Motor and T7300 Thermostat.
63-2484—2
22
SOLID STATE ECONOMIZER SYSTEM
TR
TR1
N1
N
24 VAC HOT
24 VAC COM
MINIMUM POSITION
ADJUSTMENT
24
Vac
24 Vac
COM
P1
T1
HOT
P
T
C7150B MIXED
AIR OR C7046A
DISCHARGE
+
–
2-10 VDC CONTROL
SIGNAL INPUT
AIR SENSOR
1
2
5
AQ1
–
+
0/2-10 VDC
INDOOR AIR
SENSOR
AQ
SO+
SO
SR+
3
4
EF
EF1
SR
M7215
C7400
W7212
5
OUTDOOR
AIR
+
4
620 OHM
L1
ENTHALPY
SENSOR
S
RESISTOR
(HOT)
L2
EXHAUST
FAN
Y1
Y2
C
COOL 1
COOL 2
Y1
Y2
W2
W1
HEAT 2
HEAT 1
W2
3
AUX
W1
A2
G
RH
RC
G
R
FAN
2
L2
1
X
L1
(HOT)
HVAC EQUIPMENT
TERMINAL STRIP
T7350
THERMOSTAT
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
THE SAME TRANSFORMER CAN BE USED FOR THE THERMOSTAT AND ACTUATOR.
IF SEPARATE HEATING AND COOLING TRANSFORMERS ARE USED, REMOVE JUMPER AT THERMOSTAT.
T7350 - TERMINAL “AUX” IS POWERED BY THE HEATING TRANSFORMER (RH).
3
IF POWERING THE ECONOMIZER TERMINAL “N” WITH THE THERMOSTAT TERMINAL “AUX”, BE SURE THE ECONOMIZER IS POWERED BY THE
SAME TRANSFORMER AS TERMINAL “AUX”. IF NOT, USE AN ISOLATION RELAY TO POWER “N”.
4
5
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.
M13657
Fig. 30. W7212 used with M7215 Damper Motor and T7350 Thermostat.
23
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
TR
TR1
N1
N
24 VAC HOT
24 VAC COM
MINIMUM POSITION
ADJUSTMENT
24
Vac
24 Vac
COM
P1
T1
HOT
P
T
C7150B MIXED
AIR OR C7046A
DISCHARGE
AIR SENSOR
+
–
2-10 VDC CONTROL
SIGNAL INPUT
1
2
5
AQ1
–
+
0/2-10 VDC
INDOOR AIR
SENSOR
AQ
SO+
SO
SR+
3
4
EF
EF1
SR
M7215
C7400
W7212
5
OUTDOOR
AIR
+
4
620 OHM
L1
ENTHALPY
SENSOR
S
RESISTOR
(HOT)
L2
EXHAUST
FAN
Y1
Y2
C
COOL 1
COOL 2
Y1
Y2
W2
W1
A
HEAT 2
HEAT 1
W2
3
W1
A
G
R
G
R
FAN
2
L2
RC
X
1
L1
(HOT)
HVAC EQUIPMENT
TERMINAL STRIP
TB7220 OR TB8220
THERMOSTAT
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
THE SAME TRANSFORMER CAN BE USED FOR THE THERMOSTAT AND ACTUATOR.
IF SEPARATE HEATING AND COOLING TRANSFORMERS ARE USED, REMOVE JUMPER AT THERMOSTAT.
TB7220 - TERMINAL “A” IS POWERED BY THE COOLING TRANSFORMER (RC).
TB8220 - TERMINAL “A” IS POWERED BY THE HEATING TRANSFORMER (R).
3
IF POWERING THE ECONOMIZER TERMINAL “N” WITH THE THERMOSTAT TERMINAL “A”, BE SURE THE ECONOMIZER IS POWERED BY THE
SAME TRANSFORMER AS TERMINAL “A”. IF NOT, USE AN ISOLATION RELAY TO POWER “N”.
4
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
M13658
5
EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.
Fig. 31. W7212 used with M7215 Damper Motor and TB7220 or TB8220 Thermostats.
63-2484—2
24
SOLID STATE ECONOMIZER SYSTEM
TR
TR1
N1
N
~
+
1
2
3
4
5
MINIMUM POSITION
ADJUSTMENT
24
Vac
24 Vac
COM
P1
T1
HOT
P
T
C7150B MIXED
AIR OR C7046A
DISCHARGE
+
–
F
AIR SENSOR
1
2
5
AQ1
–
+
0/2-10 VDC
INDOOR AIR
SENSOR
MS7XXX
HONEYWELL
ACTUATOR
AQ
SO+
SO
SR+
3
4
EF
EF1
SR
4
W7212
3
C7400
620 OHM
OUTDOOR
AIR
+
RESISTOR
ENTHALPY
SENSOR
S
C
L1
(HOT)
L2
COOL 1
Y1
Y1
Y2
EXHAUST
FAN
5
HEAT 2
W2
W1
W2
UNOCCUPIED
HEAT 1
ST6008
TIMER
W1
G
6
FAN
OCCUPIED
DELAY
RELAY
RH
FDR
G
R
FAN
2
L2
RC
X
FDR
1
L1
(HOT)
HVAC EQUIPMENT
TERMINAL STRIP
THERMOSTAT
1
2
3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
4
5
EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.
M24219
SEE WIRING DIAGRAMS FOR T7350 AND TB7220/TB8220.
TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE THERMOSTAT.
6
Fig. 32. W7212A used in single-stage cooling system with single enthalpy changeover and Honeywell actuator and time
clock for occupancy.
25
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
TR
TR1
N1
N
~
1
MINIMUM POSITION
ADJUSTMENT
2
24
Vac
24 Vac
COM
P1
T1
HOT
3
P
T
+
C7150B MIXED
AIR OR C7046A
+
–
4
DISCHARGE
AIR SENSOR
F
5
1K
1S
1
2
5
3
AQ1
2K
–
+
0/2-10 VDC
INDOOR AIR
SENSOR
MS7XXX
HONEYWELL
ACTUATOR
AQ
SO+
SO
SR+
3
4
1S1
EF
EF1
SR
W7212
C7400
7
5
OUTDOOR
AIR
+
620 OHM
ENTHALPY
SENSOR
RESISTOR
S
C
L1
(HOT)
L2
COOL 1
COOL 2
HEAT 2
HEAT 1
Y1
Y2
Y1
Y2
T6031 AMBIENT
LOCKOUT
W
R
EXHAUST
FAN
CONTROL
50 F SETPOINT
W2
W1
W2
UNOCCUPIED
8
6
W1
G
ST6008
TIMER
FAN
9
DELAY
RELAY
OCCUPIED
RH
FDR
FDR
G
R
FAN
2
RC
X
L2
4
1
L1
(HOT)
HVAC EQUIPMENT
TERMINAL STRIP
T7300 OR T874
THERMOSTAT
1
2
3
6
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
USE THE FOLLOWING CONTACTS INSTEAD OF TIMER
FOR T7300, USE A1 AND A2 TERMINALS.
FOR T7350 USE AUX TERMINAL.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA
LOAD OF THE ECONOMIZER AND ACTUATOR.
FOR TB7220 OR TB8220 USE A TERMINAL
THE TERMINALS ARE CONNECTED WHEN THERMOSTAT IS IN THE OCCUPIED MODE.
7
8
9
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED
BY A 24 VAC INPUT.
EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.
SEE WIRING DIAGRAMS FOR T7350 AND TB7220/TB8220.
4
5
FOR T7300 ONLY
TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE THERMOSTAT.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE
REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO
SR AND SR+ FOR DIFFERENTIAL ENTHALPY.
M24220
Fig. 33. W7212A used in two-stage cooling system with Honeywell Series 72 Actuator and time clock for occupancy.
63-2484—2
26
SOLID STATE ECONOMIZER SYSTEM
1
2
L2
L1
(HOT)
~
+
1
2
3
4
5
TR
TR1
N1
N
MINIMUM POSITION
ADJUSTMENT
24
Vac
24 Vac
COM
F
P1
T1
HOT
P
T
MS7XXX
HONEYWELL
ACTUATOR
C7150B MIXED
AIR OR C7046A
DISCHARGE
+
–
AIR SENSOR
1
2
5
~
1
2
AQ1
–
+
0/2-10 VDC
INDOOR AIR
SENSOR
3
AQ
SO+
SO
SR+
+
3
4
4
F
5
EF
EF1
MS7XXX
HONEYWELL
ACTUATOR
SR
W7212
4
620 OHM
C7400
5
UNOCCUPIED
3
RESISTOR
OUTDOOR
+
ST6008
AIR
7
TIMER
ENTHALPY
SENSOR
S
L1
(HOT)
OCCUPIED
L2
1
C
COOL 1
Y1
Y2
Y1
Y2
L1
(HOT)
COOL 2
HEAT 2
HEAT 1
L2
1
2
3
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
EXHAUST
FAN
W2
W1
W2
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE
THE LOAD OF ALL ACTUATORS.
W1
G
USE THE FOLLOWING CONTACTS INSTEAD OF TIMER
FOR T7300, USE A1 AND A2 TERMINALS.
FOR T7350 USE AUX TERMINAL.
FAN
DELAY
RELAY
FOR TB7220 OR TB8220 USE A TERMINAL
THE TERMINALS ARE CONNECTED WHEN THERMOSTAT
IS IN THE OCCUPIED MODE.
RH
FDR
FDR
G
R
FAN
RC
X
L2
L1
4
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR
SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY
SENSOR IS ADDED TO SR AND SR+ FOR DIFFERENTIAL
ENTHALPY.
1
(HOT)
THERMOSTAT
6
HVAC EQUIPMENT
TERMINAL STRIP
EF AND EF1 ARE DRY CONTACTS IN THE
LOGIC MODULE.
5
6
SEE WIRING DIAGRAMS FOR T7350
AND TB7220/TB8220.
M24221
7
TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS
ON THE THERMOSTAT.
Fig. 34. W7212 controlling parallel-wired Honeywell Series 72 Actuators and time clock for occupancy.
27
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
~
1
2
TR
TR1
O
5
3
+
N
4
MINIMUM POSITION
ADJUSTMENT
24
Vac
24 Vac
COM
P1
T1
F
5
HOT
P
T
+
–
C7150B
DISCHARGE
AIR SENSOR
MS7XXX
1
2
4
HONEYWELL
ACTUATOR
AQ1
–
+
0/2-10 VDC
INDOOR AIR
SENSOR
AQ
SO+
SO
SR+
3
5
EF
EF1
SR
W7214
2
3
620 OHM
C7400
RESISTOR
OUTDOOR
AIR
+
ENTHALPY
SENSOR
S
A3
A2
Y1
Y2
4
C
COOL 1
Y1
Y2
L1
(HOT)
COOL 2
HEAT 2
HEAT 1
FAN
L2
EXHAUST
FAN
W2
W2
W1
G
W1
G
RH
L2
L1
1
R
O
RC
X
(HOT)
5
O
HVAC EQUIPMENT
TERMINAL STRIP
T7300
THERMOSTAT
1
2
3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A
C7400 ENTHALPY SENSOR IS ADDED TO SR AND SR+ FOR DIFFERENTIAL ENTHALPY.
4
5
T7300 TERMINALS A2 AND A3 ARE CONNECTED WHEN THERMOSTAT IS IN THE UNOCCUPIED MODE.
SEE WIRING DIAGRAMS FOR T7350 AND TB7220/TB8220.
W7213: B TERMINAL
W7214: O TERMINAL
M24222
Fig. 35. W7213, W7214 controlling heat pump system.
63-2484—2
28
SOLID STATE ECONOMIZER SYSTEM
Table 6. Troubleshooting modulating economizer—outdoor enthalpy above setpoint.
Condition on Logic Module Should Be
1. Red LED not lighted.
Condition Not Met
1. If the LED glows, the Logic Module recognizes conditions are good for free cool-
ing. Verify that conditions are above the enthalpy setpoint, see Note 2. Check wir-
ing to Enthalpy Control for a short from {SO} and {+}.
2. 24 Vac to terminals {TR} and {TR1}.
3. 24 Vac to terminals {1} and {TR1}.
4. 24 Vac to terminals {2} and {TR1}.
2. Check the wiring from [G] and [C] on the unit low voltage terminal strip. {TR} and
{TR1} power the actuator.
3. Verify that there is a call for cooling from the thermostat. Without a call for cooling,
the compressor can not be in the normal air conditioning mode.
4. If 24 Vac is not on {2} and {TR1}, the internal switch is not set correctly. Remove
the {SO} wire from the module. If 24 Vac is on {2} and {TR1}, the enthalpy control
is bad or the {SO} and {+} wires are shorted together. If no voltage to {2} and
{TR1}, the module is bad.
5. Continuity on terminals {1} and {2}, {3} 5. If there is not continuity for terminals {1} and {2}, the internal switch is not in the
and {4}.
correct position and the module is defective. If there is continuity from terminals
{1} and {2}, the red LED should not be lighted. If there is continuity on terminals
{3} and {4}, the internal switch is correctly energized. The damper actuator should
be in a min. position.
6. Compressor does not operate with all 6. Check the wiring from {2} to Y1 on the unit low voltage control board. If the LED is
above conditions correct.
not lighted, check 24 Vac from {2} to Y1.
Second Stage
7. 24 Vac to terminals {3} and {TR1}.
8. 24 Vac to terminals {4} and {TR1}.
7. Verify that you have a two-stage thermostat. Check for a call for a second stage
cooling. If 24 Vac is not on {3} and {TR1}, check wiring from Y2 on the thermostat
to the module.
8. If {4} and {TR1} do not have 24 Vac, and {3} and {TR1} have 24 Vac, the internal
switch is not in the correct position. The module is defective.
9. Compressor does not operate with
9. If all other functions are correct, check wiring from {4} to Y2 on the unit low voltage
second stage conditions met.
terminal board.
Table 7. Troubleshooting modulating economizer—outdoor enthalpy below setpoint.
Condition on Logic Module Should Be
Conditions Not Met
1. Red LED lighted.
1. Jumper terminals {SO} and {+}. If the LED lights, the module is okay, see Note 2.
Check wiring to enthalpy control.
2. 24 Vac to terminals {TR} and {TR1}.
3. 24 Vac to terminals {1} and {TR1}.
2. Check the wiring from [G] and [C] on the unit low voltage terminal strip. {TR} and
{TR1} power the actuator.
3. Verify there is a call for cooling from the thermostat. Without a call for cooling, the
motor can not be in the economizer mode.
4. No continuity on terminals {1} and {2}. 4. If there is continuity from terminals {1} and {2}, the red LED should not be lighted. If
there is continuity and the LED glows, the module is defective.
5. Continuity on terminals {3} and {5}.
5. If there is continuity on terminals {3} and {5}, the internal switch is correctly ener-
gized. Damper motor should be in a modulating mode.
6. Motor does not operate with all above 6. Jumper the mixed air sensor terminals {T} and {T1}. If the motor begins to operate,
conditions met.
check the wiring to the sensor. If correct, the temperature is below the sensor set-
point or it is defective. If the motor does not operate, and the wiring is correct and
the temperature is above the sensor setpoint, the motor is bad.
Second Stage
7. 24 Vac to terminals {3} and {TR1}.
7. Verify that you have a two-stage thermostat. Check for a call for a second stage
cooling. If 24 Vac is not on terminals {3} and {TR1}, check wiring from terminal Y2
on the thermostat to the module.
8. 24 Vac to terminals {5} and {TR1}.
8. If terminals {5} and {TR1} do not have 24 Vac, the internal switch is not in the cor-
rect position, assuming that terminals {3} and {TR1} have 24 Vac. The module is
defective.
9. Compressor does not operate with
9. If all other functions are correct, check the wiring from terminal {5} to Y2 on the unit
second stage conditions met.
low voltage terminal board.
29
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
Table 8. Troubleshooting three-position economizer—outdoor enthalpy above setpoint.
Condition on Logic Module Should Be
1. Red LED not lighted.
Conditions Not Met
1. If the LED glows, the module is in the economizer mode. Verify the conditions are
above the enthalpy setpoint, see Note 2. Check wiring to Enthalpy Control for a
short from {SO} and {+}.
2. 24 Vac to terminals {TR} and {TR1},
2. Check the wiring from [G] and [C] on the unit low voltage terminal strip. {TR} and
{X} and {TR}.
{TR1} power the actuator. {X} and {TR} provide power for minimum position.
3. 24 Vac to terminals {1} and {TR}.
3. Verify that there is a call for cooling from the thermostat. Without a call for cooling
the compressor can not be in the normal air conditioning mode.
4. 24 Vac to terminals {2} and {TR}.
4. If 24 Vac is not on {2} and {TR}, the internal contacts are not set correctly. Remove
the {SO} wire from the module. If 24 Vac is on {2} and {TR}, the enthalpy control is
bad or the {SO} and + wiring are shorted together. If no voltage to {2} and {TR}, the
module is bad.
5. Continuity on terminals {1} and {2}, {3} 5. If there is not continuity for {1} to {2}, the internal contacts are not in the correct
and {4}.
position, and either the module or the enthalpy control is defective. If there is conti-
nuity from terminals {1} and {2}, the red LED should not be lighted. If there is conti-
nuity and the LED glows, the module is defective. If there is continuity on terminals
{3} and {4}, the internal contacts are correctly energized. Damper motor should be
in the min. position.
6. Compressor does not operate with all 6. Check the wiring from {2} to Y1 on the unit low voltage control board. Verify that
above conditions correct.
there are not 24 Vac to Y1 and C on the unit.
Second Stage
7. 24 Vac to terminals {3} and {TR}.
8. 24 Vac to terminals {5} and {TR}.
7. Verify that the thermostat is two-stage. Check for a call for a second stage cooling.
If there are not 24 Vac on {3} and {TR}, check wiring from Y2 on the thermostat to
the module.
8. If {5} and {TR} do not have 24 Vac and {3} and {TR} have 24 Vac, the internal
switch 1S is not in the correct position. The module is defective.
9. Compressor does not operate with
9. If all other functions are correct, check the wiring from {5} to Y2 on the unit low volt-
second stage conditions met.
age terminal board.
Table 9. Troubleshooting three position economizer—outdoor enthalpy below setpoint.
Condition on Logic Module Should Be
Conditions Not Met
1. Red LED lighted.
1. Jumper terminals {SO} and {+}. If the LED glows, the module is okay, see Note 2.
Check wiring to enthalpy control.
2. 24 Vac to terminals {TR} and {TR1}.
3. 24 Vac to terminals {1} and {TR1}.
2. Check the wiring from [G] and [C] on the unit low voltage terminal strip. {TR} and
{TR1} power the actuator.
3. Verify there is a call for cooling from the thermostat. Without a call for cooling, the
motor can not be in the economizer mode.
4. No continuity on terminals {1} and {2}. 4. If there is continuity from terminals {1} and {2}, then the red LED cannot be lighted.
If there is continuity and the LED glows, the module is defective.
5. Continuity on terminals {3} and {5}.
5. If there is continuity on terminals {3} and {5}, the internal switch 1S is correctly
energized. Damper motor should be in a modulating mode.
6. Motor does not operate with all above 6. Jumper the mixed air sensor terminals {6} and {D}. If the motor begins to operate,
conditions met.
check the wiring to the sensor. If it is correct, the temperature is below the sensor
setpoint or the sensor is defective. If the motor does not operate, the wiring is cor-
rect, and the temperature is above the sensor setpoint, the motor is bad.
Second Stage
7. 24 Vac to terminals {3} and {TR}.
7. Verify that the thermostat is two-stage. Check for a call for a second stage cooling.
If 24 Vac is not on {3} and {TR}, check wiring from Y2 on the thermostat to the
module.
8. 24 Vac to terminals {5} and {TR}.
8. If {5} and {TR} do not have 24 Vac, and {3} and {TR} do have 24 Vac, then the
internal switch 1S is not in the correct position. The module is defective.
9. Compressor does not operate with
9. If all other functions are correct, check the wiring from {5} to Y2 on the unit low volt-
second stage conditions met.
age terminal board.
63-2484—2
30
SOLID STATE ECONOMIZER SYSTEM
CHECKOUT AND TROUBLESHOOTING:
W7212
W7212
EXH
N1
Set
10V
N
2V
Checkout requires a 9V battery, 620 ohm, 1.2K ohm, 5.6K
ohm, and 6.8K ohm resistors. Use Table 10 and Fig. 36 for
checkout.
EXH
P1
T1
P
T
Min
Pos
Open
1
DC VOLTMETER
DCV
Max
10V
+
–
2V
CAUTION
AQ1
DCV
Equipment Damage Hazard.
AQ
SO+
SO
SR+
SR
DCV
Set
10V
Excessive force can damage potentiometer
controls.
Use a small screwdriver when adjusting enthalpy
changeover and minimum damper position controls.
2V
S
C7400
+
Free
Cool
B
C
D
A
2
620 OHM RESISTOR
1
2
INSERT DC VOLTMETER BETWEEN AQ AND AQ1 FOR
CHECKOUT AND TROUBLESHOOTING.
JUMPER USED FOR SINGLE ENTHALPY CONTROL.
M20612
Fig. 36. Meter location for checkout and troubleshooting
(W7212 shown).
Table 10. Checkout for W7212, W7213, W7214 Economizers Connected to Honeywell Actuator.
Step
1.
Checkout Procedure
CHECKOUT PREPARATION
Proper Response
Disconnect power at TR and TR1.
Disconnect devices at P and P1.
Jumper P to P1.
All LED are off; Exhaust Fan contacts are open.
Place 5.6K ohm resistor across T and T1.
Jumper TR to 1.
W7212 only: Jumper TR to N.
If connected, remove C7400 Enthalpy Sensor from
terminals S and +.
O
Connect 1.2K ohm 4074EJM Checkout Resistor across
terminals S and +.
O
Put 620 ohm resistor across S and +.
R
Set minimum position, DCV setpoint, and Exhaust
potentiometers fully CCW.
Turn DCV maximum position potentiometer fully CW.
Set enthalpy potentiometer to D.
Apply power (24 Vac) to terminals TR and TR1.
DIFFERENTIAL ENTHALPY
2.
3.
Execute step one, Checkout Preparation.
–
–
Place 620 ohm resistor across S and +.
O
Place 1.2K ohm resistor across S and +.
Free cool LED turns on.
Free cool LED turns off.
R
Remove 620 ohm resistor from S and +.
O
SINGLE ENTHALPY
Execute step one, Checkout Preparation.
Set enthalpy potentiometer to A (fully CCW).
Set enthalpy potentiometer to D (fully CW).
–
Free cool LED turns on.
Free cool LED turns off.
31
63-2484—2
SOLID STATE ECONOMIZER SYSTEM
Table 10. Checkout for W7212, W7213, W7214 Economizers Connected to Honeywell Actuator. (Continued)
Step
4.
Checkout Procedure
DCV AND EXHAUST
Proper Response
Execute step one, Checkout Preparation.
Ensure terminals AQ and AQ1 are open.
–
LED for both DCV and Exhaust should be off.
Actuator drives fully closed.
Connect 9V battery positive to AQ and negative to AQ1.
LED for both DCV and Exhaust turn on.
Actuator drives to between 81 and 85 degrees open.
Turn Exhaust potentiometer CW until Exhaust LED turns
off.
Exhaust LED turns off with potentiometer approximately 90
percent CW. Actuator remains in position.
Turn DCV setpoint potentiometer CW.
DCV LED turns off with potentiometer at approximately 9V.
Actuator drives fully closed.
Turn DCV setpoint potentiometer CCW until Exhaust LED Exhaust contacts close 30-90 seconds after Exhaust LED
turns on.
turns on.
Turn DCV setpoint potentiometer CW.
Exhaust LED turns off with potentiometer indication at
approximately 9V.
Turn Exhaust potentiometer CCW until Exhaust LED turns Exhaust contacts close 30-90 seconds after Exhaust LED
on.
turns on.
5.
MINIMUM AND MAXIMUM POSITION
Execute step one, Checkout Preparation.
Connect 9V battery positive to AQ and negative to AQ1.
–
DCV LED turns on. Actuator drives to between 81 and 85
degrees open.
Turn DCV maximum position potentiometer to midpoint.
Turn DCV maximum position potentiometer to fully CCW.
Turn minimum position potentiometer to midpoint.
Turn minimum position potentiometer fully CW.
W7212: Remove jumper from TR and N.
MIXED AIR INPUT
Actuator drives to between 18 and 72 degrees open.
Actuator drives fully closed.
Actuator drives to between 18 and 72 degrees open.
Actuator drives fully open.
Actuator drives fully closed.
6.
7.
Execute step one, Checkout Preparation.
Set enthalpy potentiometer to A.
–
Free cool LED turns on.
Actuator drives to between 18 and 72 degrees open.
Remove 5.6K ohm resistor and jumper from T and T1.
Remove jumper from T and T1 and leave open.
HEAT PUMP INPUT - W7213, W7214 ONLY
Execute step one, Checkout Preparation.
Set enthalpy potentiometer to A.
Actuator drives fully open.
Actuator drives fully closed.
–
Free cool LED turns on.
Actuator drives to between 18 and 72 degrees open.
W7213: Jumper TR to B.
W7214: Remove jumper from TR and O.
Free cool LED turns off.
Actuator drives fully closed
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
® U.S. Registered Trademark
© 2005 Honeywell International Inc.
63-2484—2 M.S. Rev. 08-06
|