| HomeSeer Technologies Single Package Air Conditioner 13 SEER User Manual | 
| USER’S MANUAL AND INSTALLATION   INSTRUCTIONS   13 SEER   Single Package Air Conditioner   Single Package Air Conditioner   IMPORTANT   Read this owner information to become familiar with the capabilities and use   of your appliance. Keep this with literature on other appliances where you   have easy access to it in the future. If a problem occurs, check the instructions   and follow recommendations given. If these suggestions don’t eliminate your   problem, call your installing contractor or distributor in your area.   INTRODUCTION   Mostanyairconditionerwillkeepyoucool.Ourairconditionerwasdesignedtodo   it efficiently. Efficiency means less cost to you while keeping you comfortable.   WHYYOUR AIR CONDITIONER WORKS SO WELL, SO QUIETLY   1. Air is cooled by a large evaporator coil. Moisture is also removed from the air by   this same coil.   2. Air is then delivered through the main duct, via registers, into your home.   3. Return air is drawn through the return register.   4. This air enters the unit, passes through the evaporator coil, is cooled and dehumidi-   fied. Then the cycle begins again.   is any question concerning the power supply,   contact the local power company.   SECTION 2.   INSTALLER INFORMATION   Inspecting Equipment: All units are securely   packedatthetimeofshipmentand,uponarrival,   shouldbecarefullyinspectedfordamage.Claims   for damage (apparent or concealed) should be   filed immediately with the carrier.   GENERAL   Read the following instructions completely   before performing the installation.   These instructions are for the use of qualified   personnel specially trained and experienced   in the installation of this type of equipment   and related system components. Some states   require installation and service personnel to   be licensed. Unqualified individuals should not   attempt to interpret these instructions or install   this equipment.   INSTALLATION   1. SELECTTHE BEST LOCATION FORTHE   AIR CONDITIONING UNIT   IMPORTANT: DO NOT PLACE UNIT UNDER   THE HOME.   The single packaged air conditioners are de-   signed for outdoor installation only and can be   readilyconnectedintothehighstaticductsystem   of a home. The only connections needed for   installation are the supply and return ducts, the   line voltage, and thermostat wiring.A complete   air conditioning system typically consists of:   • Select a solid, level position, preferably on a   concrete slab, slightly above the grade level,   and parallel to the home.   • The hot condenser air must be discharged   up and away from the home, and if possible,   in a direction with the prevailing wind.   • Do not place the unit in a confined space.   • If practical, place the air conditioner where it   and the ducts will be shaded from the after-   noon sun when the heat load is greatest.   • Try to select a site for the unit that is as close   as possible to the proposed return grille loca-   tion.   • Single Package Air Conditioner   • Home Fittings Kit   • Unit Fittings Kit   • Thermostat   Thesinglepackageairconditioneriscompletely   assembled,factorywired,andfactoryruntested.   The units are ready for easy and immediate   installation.   • Keep in mind that the length of the supply and   returnductsshouldbekepttoaminimumwith   no sharp radiused bends.   2. UNPACK THE UNIT   It is recommended that the unit be unpacked   at the installation site to minimize damage due   to handling.   PRE-INSTALLATION CHECK   Before any installation is attempted, the cool-   ing load of the area to be conditioned must be   calculated and a system of the proper capacity   selected. It is recommended that the area to   be conditioned be completely insulated and   vapor sealed.   CAUTION:   Do not tip the unit on its side. Oil   may enter the compressor cylinders   and cause starting trouble. If unit has   been set on its side,restore to upright   position and do not run for several   hours.Thenrununitforafewseconds.   Do this three or four times with five   minutes between runs.   The installer should comply with all local codes   and regulations which govern the installation   of this type of equipment. Local codes and   regulations take precedence over any recom-   mendations contained in these instructions.   Consult local building codes and the National   ElectricalCode(ANSICI)forspecialinstallation   requirements.   The electrical supply should be checked to de-   termine if adequate power is available. If there   a. Remove the bands from around the unit.   b. Unfold the top and bottom cap flanges.   c. Carefully remove the top cap and tube.   3 RETURN DUCT   6 ft.   Align the 14” return duct slots with the holes in   the collar and install two screws. Position the   collarovertheopeningandalignthefournotches   in the collar with the four dimples in the panel.   Using self-drilling screws (10-16x.5) attach the   collar to the rear panel.   24"   4. LOCATING AND INSTALLING THE RE-   TURN AIR ASSEMBLY   To avoid complications, locate and install the   return air assembly first. The return air box   with grille and filter (Figure 4) should not be   located in heavy traffic areas like hallways or   center of rooms. A good spot is in a corner or   under a table, if a minimum two inch clearance   is available. If desired, the return opening can   be located inside a closet with louvered doors   that have an open area equal to or greater than   the 12”x 20”grille furnished.The return air grille   can be placed in the wall of a closet and the air   ductedintothefilterboxthroughaboxed-inarea   at the closet floor level. Make sure the filter is   readily accessible.   12"   12"   Figure 2. Minimum Unit Clearances   3. INSTALLTHERETURNANDSUPPLYAIR   FITTINGS ON THE UNIT   The supply and return fittings are included with   select models. If supplied, the duct fittings are   shippedinthesupplyduct.Theyattachtotheunit   openings with a flange and bead arrangement,   secured with two sheet metal screws. Note: For   ease of access, install fitting before positioning   unit in final location.   After determining the location of the return air   opening, start the installation from under the   home by cutting a small hole in the fiber under-   board to determine how the floor joist location   willaffectcuttingtheopeningneededforthebox.   Floorjoistsgenerallyarelocatedon16”centers,   leaving 14-3/8” between joists. After measuring   the return air box (approximately 12-1/4” x 14-   1/4”), cut the hole through the floor so that the   box will fit between the floor joists. Care should   betakenwhencuttingthroughcarpetingtoavoid   snags.Inmostinstallationsitwillbenecessaryto   cut a similar hole in the fiberboard directly under   the hole in the floor.However, if the floor is more   SUPPLY DUCT   Positionthesupplyductcollar, ifsupplied, sothe   edge of the unit opening fits between the flange   andthebead.Overlapthecollarendskeepingthe   smallscrewholesunderneath.Aligntheholesin   the crimped area and install one screw.   Note: It may be necessary to loosen the four   screws that hold the transition duct in order to   install the supply fitting. Re-tighten when instal-   lation is complete.   Tap collar as necessary to ensure engagement   with unit opening and install second screw.   Tighten first screw. Rotate collar clockwise so   joint is near three o’clock position.   Transition Duct Screws   14” Duct Dimples   Supply Air   Return Air   Figure 3. Return and Supply Air Fittings   Figure 4. Return Air Box   4 than ten inches deep, it will only be necessary   to cut a hole for the collar on the return air box   or for the insulated duct.   Set the box into the opening and fasten with   screws or nails. Put the filter and return air   grille in place.   5. LOCATING AND INSTALLING THE   SUPPLY DAMPER(S)   Figure 5. Supply Damper   over all tabs flat on the inside of the heat duct.   Seal the opening between the fiberboard and   damper or flexible duct.   CAUTION:   When a home is not equipped with a   make-ready kit means must be pro-   vided to prevent simultaneous opera-   tion of the heating and cooling units.   Aheat/coolthermostatisavailablefor   this purpose.   DUCTING SYSTEM   DUCT REQUIREMENTS   The supply duct system, including the number   and type of registers, will have much more ef-   fect on the performance of an air conditioning   system than any other factor.The duct must be   sufficientlylargetoconductanadequateamount   of air to each register.   When installing this air conditioning   system in conjunction with a furnace,   a damper must be installed in the fur-   nace base assembly to prevent cold   air being discharged around the heat   exchanger. Damage to the heat ex-   changer and asphyxiation may occur   if a damper is not installed.if the damp   THE AIR CONDITIONING OUTPUT OF THE   SYSTEMWILL NOT COOLTHE HOME IFTHE   AIR IS LOST TO THE OUTSIDE THROUGH   LEAKSINTHEDUCTSYSTEM.ALSO,DUCTS   WHICH ARE COLLAPSED OR RESTRICTED   BY FOREIGN OBJECTS WILL PREVENT   ADEQUATE AIR FLOW.   Check with the furnace manufacturer   for damper requirements. Failure to   install the required furnace damper   mayinvalidatecodeagencylistingand   limited warranty on the furnace.   Note:For highly resistive duct systems it may be   necessarytoaddanadditionalreturnairductand   orsupplytoachievemaximumperformanceand   prevent coil icing and refrigerant flood back.   CONNECTING THE RETURN AND SUPPLY   AIR FLEXIBLE DUCTS   When locating the supply damper(s), carefully   check floor joists and frame members that could   interfere with the installation of the damper or   flexible duct. Ideally, the damper should be   located in the bottom of the main duct, forward   of center of the home, at least three feet from   the nearest register.The round supply opening   in the slanted side of the damper should face   the side of the home where the air conditioner   is located.To locate the center of the heat duct,   first cut a small hole in the fiberboard below the   duct at the desired location. After locating the   duct center, cut a hole approximately 3/4”larger   than the damper opening in the fiberboard. Cut   a 9-1/8” x 13-1/8” hole in the duct and bend   over all tabs flat on the inside of the heat duct.   After inserting the damper into the duct, bend   a. The supply duct for all units is twelve inches   in diameter.The return duct is 14” diameter   for all air conditioning units.   b. The flexible ducts can be connected to the   corresponding fittings with the clamps pro-   vided with the ducts. Note: All connections   should be leak tight or a loss in cooling   capacity will result.   c. Theflexibleductsmaybecuttotherequired   length, see instructions packed with duct.   Keep all ducts as short and straight as pos-   sible. Avoid sharp bends.   d. Ducts may be spliced with sheet metal   sleeves and clamps. (See Ducting Instal-   lation Accessories below.)   5 TYPICAL APPLICATIONS   4 4 6 4 3 2 3 2 6 6 7 1 1 5 5 SINGLE DUCT APPLICATION   MULTIPLE DUCT APPLICATION   Ref. No.   Description   12” x 20” Return Air   16” x 20” Air Filter   12” x 20” Grille   1 2 3 4 5 6 7 Supply Damper   14” Diameter Flex Return Duct   12” Diameter Flex Supply Duct   12” x 12” x 12” “Y” Fitting   Figure 6. Typical Applications   e. Once the inner duct is connected to the   proper fitting, the insulation and plastic   sleeveshouldbepulledovertheconnection   and clamped.   f. For homes with multiple supply ducts or for   special applications, aY fitting is available   to divide the supply air so it can be ducted   to different areas of the home for more   efficient cooling. Note:TheY fitting should   be insulated for maximum performance.   If Standard Motor:   1. Disconnect all electrical power to the   unit and remove the service panel.   2. Remove the motor lead from terminal #4 of   the blower relay. Cut the wire tie holding the   motor lead bundle. The motor leads are   color coded as shown in Figure 7.   3. Ifthedesiredheatingblowerspeedisdifferent   than the cooling speed, remove and discard   the jumper wire between terminals #6 and   #4. on the blower relay. Place the desired   heating blower speed lead on terminal #6   and the desired cooling blower speed   lead on terminal #4 of the blower relay. Use   another wire tie (field supplied) to bundle the   remaining motor leads.   Blower Speed — For optimum system   performance and comfort, it may be necessary   to change the factory set speed. See table 1 for   factory settings. To change the blower speed:   6 If Fixed Torque Motor:   1. Disconnect all electrical power to the unit   and remove the blower panel.   Check all factory wiring per the unit wiring   diagram and inspect the factory wiring connec-   tions to be sure none loosened during shipping   or installation.   2. Locate the orange and red wires terminated   totheblowermotor. Theorangewirecontrols   coolingoperationwhiletheredwirecontrols   heating operation.   3. Verify the required speed from the airflow   datafoundinfigure7.Placeappropriatewire   on the appropriate motor speed tap for the   required airflow point.   CAUTION:   To avoid personal injury or property   damage, make certain that the motor   leads cannot come into contact with   any uninsulated metal components   of the unit.   Note:If the same speed is required for both   heating and cooling, remove either the red   or orange wire from the blower motor. Next,   obtainthejumperwirefromthehomeowners   packet and connect it to the blower relays   at the coils on the blue wire and red wire   side.   Check all factory wiring per the unit wiring   diagram and inspect the factory wiring connec-   tions to be sure none loosened during shipping   or installation.   Model   Wire Color /   Speed Tap   Motor   Speed   Air Flow   (0.3 In. WC)   P3RD   CONDENSATE DRAIN   Red   Black   Red   Low   High   760   2 Ton   A 3/4”condensate fitting extends out of the side   oftheunit.Thedraintrap,shippedintheelectrical   compartment,mustbeinstalledtopreventwater   from collecting inside the unit.Thread the elbow   provided with the unit into the drain connection   until hand tight.Install the trap into the fitting and   seal the joint. Make sure it is level. Route the   condensatefromthetraptoasuitabledrain.Any   connecting tubing or hose must have the outlet   below the trap level for proper drainage.   1000   760   Low   2.5 Ton   3 Ton   Black   Red   High   1000   760   Low   Black   T1   High   1000   750   Low   T2   Med/Low   Medium   Med/High   High   1,000   1,140   1,300   1,350   1,340   1,450   1,650   1,750   1,965   1,340   1,450   1,650   1,750   1,965   3.5 Ton   4 Ton   Orange / T3   Red / T4   T5   T1   Low   Orange / T2   Red / T3   T4   Med/Low   Medium   Med/High   High   WARNING:   T5   Turnoffelectricalpowerbeforeservic-   ing controls. Severe electrical shock   may result unless power is turned off.   Unit must be installed in compliance   withtheNationalElectricalCode(NEC)   and local codes.   T1   Low   T2   Med/Low   Medium   Med/High   High   5 Ton   Orange / T3   Red / T4   T5   Figure 7. Standard Motor Lead Connection   Elbow   High Voltage   Low Voltage   P-Trap   Figure 8. Drain Trap   Figure 9. Power Entry   7 Y terminals respectively on the thermostat   subbase. Connect the green wire to the   yellow wire at the unit. See the instruction   sheetpackedwiththethermostatfordetailed   methods of mounting.   ELECTRICAL CONNECTIONS   1. ELECTRICAL SERVICE   High Voltage   a. Install a branch circuit disconnect of ad-   equatesizeperNEC.Locatethedisconnect   within sight of the unit.   b. Extend leads through power wiring hole   provided.Connect L1 and L2 directly to the   contactor. (See Figure 9).   Note:The cooling-only thermostat must be   connected to an interlock switch to prevent   simultaneous operation of the furnace and   the air conditioner. (See Figure 1, Page   2.)   c. Ground the air conditioning unit using the   green grounding screw provided in the   control panel.   b. Connect the Heat-CoolThermostat: The   heat-cool thermostat is equipped with a   systemHEAT-COOLswitch,whichprovides   a positive means of preventing simultane-   ous operation of the heating and cooling   units.The thermostat is also equipped with   an ON-AUTO fan switch which allows the   home owner to operate the indoor blower   when air circulation is desired.   Low Voltage   a. Route24vcontrolwiresthroughthesealing   grommet near the power entrance.   b. Connect the control wires to the leads in   the low voltage area. (See Figure 10).   2. OVERCURRENT PROTECTION   Connect the red, yellow, green and brown   low voltage wires to the R or RC, Y, G and   W terminals respectively on the thermostat   base.The black wire is the 24 volt common   required on some thermostats. See ther-   mostat instruction sheet for more detailed   information.   In general, the best fuse or breaker for any air   conditioner is the smallest size that will permit   the equipment to run under normal use and   service without nuisance trips. Such a device,   sized properly, gives maximum equipment   protection. The principal reason for specifying   a time delay type is to prevent nuisance trips   when the unit starts.   Refer to furnace installation instructions   for required connections and proper heat   anticipator setting when installing unit with   an external furnace.   In the event that a fuse does blow or a breaker   trips, always determine the reason. Do not arbi-   trarily put in a larger fuse or breaker and do not,   in any case, exceed the maximum size listed on   the data label of the unit.   c. If two stage heating is desired, an   optional outdoor thermostat may be   installed: Connect the thermostat to the   orange low voltage wire and theW terminal   on the indoor thermostat base (See Figure   10). See the thermostat instructions for   details on setting the outdoor thermostat.   3. LOCATING THE THERMOSTAT   Locate the thermostat away from drafts and   slammingdoorsandplaceitwherethereisafree   flowofair.Mountonaninsidewallapproximately   five feet from the floor.   4. ELECTRIC HEAT PACKAGE (OP-   TIONAL)   Do not locate near a lamp, kitchen range, direct   sunlight, or in line with air flow from supply   registers.   The air conditioner is shipped without an auxil-   iary electric heat kit installed. If electric heat is   desired, an accessory Heater Kit must be field   installed.See Specifications Sheet for available   kits and their applications.   a. ConnectCoolingThermostat:Thecooling   thermostatavailableforusewiththissystem   is equipped with a selector switch. To shut   down the air conditioner, set the selector   switch to the OFF position.Connect the red   and yellow wires from the unit to the R and   • Select the correct size heat package for the   installation.   8 4 Wire Heat/Cool Thermostat   2 Wire Cooling Thermostat   Control Wire Legend   Green - Blower Relay   Single Stage Electric Heat   Red - Transformer   24V   RED   R RED   R Yellow - Cooling 1st   Stage   YELLOW   GREEN   Y YELLOW   GREEN   Y Brown - Heating 1st   Stage   G W Orange - Heating 2nd   Stage   BROWN   BROWN   ORANGE   Two Stage Electric Heat   RED   R Y YELLOW   GREEN   G W BROWN   ORANGE   Optional   Outdoor Thermostat   (Field Supplied)   Figure 10. Low Voltage Connections   • • Follow installation instructions provided   with each heater kit.   Installation is most easily accomplished   before making duct or electrical connec-   tions.   Is the thermostat wired correctly? Is it   installed in a proper location?   2. START-UP PROCEDURE   • The blower must be set to high speed for   electric heat operation.   a. Set the system switch to the OFF posi-   tion.   b. Dial thermostat setting as high as it will   go.   c. Turn on power supply at the disconnect   switch.   d. Set the system switch to ON or COOL.   Set the temperature setting to below room   temperature. Verify that the indoor blower,   outdoorfan, andcompressorareenergized   and the cooling function starts.   e. Verify that the discharge air grilles are   adjusted and the system is balanced.   f. Verify that there are no air leaks in the duct   work.   SYSTEM OPERATION   1. PRE-START CHECK LIST   The following check list should be observed   prior to starting the unit.   Is the unit level? It should be level or   slightly slanted toward the drain for proper   condensate drainage.   Is the unit installed with the proper clear-   ances (See Figure 2)?   g. Verify that the condensate drain is properly   installed and that it functions correctly.   h. Dial the thermostat higher than room tem-   perature. The unit should stop.   Isthewiringcorrectaccordingtothewiring   diagram and electrical codes?   i. Ifusingacombinationheating-coolingther-   mostat, set to the HEAT position. Proceed   to check for correct furnace operation.   j. Verify that the furnace controls and burners   or heating elements operate correctly.   k. Instruct the owner on unit operation, filter   servicing, and proper thermostat opera-   tion.   Areallthewiringconnectionstight?Check   the condenser fan to make sure it turns   freely.   Is the overcurrent protection properly   sized?   9 13 SEER - Charging Charts   OUTDOOR TEMPERATURE (°F)   85 90   2 TON   Suct. Dis.   70   75   80   95   100   Dis. Dis.   105   Dis. Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.   75   77   79   81   83   85   87   89   91   93   95   97   99   101   142   144   147   150   153   133   138   144   147   149   157   159   161   164   168   136   141   146   149   152   171   173   176   179   182   138   143   148   152   155   186   188   190   193   197   200   141   146   150   154   158   161   200   202   205   208   211   215   144   148   152   156   160   164   215   217   219   222   226   229   146   150   155   159   163   167   229   231   233   237   240   244   149   153   157   161   165   170   244   246   248   251   255   258   151   155   159   163   168   172   OUTDOOR TEMPERATURE (°F)   85 90   2-1/2   TON   Suct. Dis.   70   75   80   95   100   Dis.   105   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.   75   77   79   81   83   85   87   89   91   93   95   97   99   101   143   145   148   149   153   126   131   137   143   146   158   161   163   165   168   130   135   140   146   149   174   176   178   180   184   134   139   144   148   152   189   191   193   196   199   203   138   143   147   151   155   159   204   206   208   211   215   218   142   146   151   155   158   162   219   221   223   227   230   234   145   150   154   158   162   166   234   236   238   242   246   249   149   153   157   161   166   170   250   252   254   258   261   265   152   156   160   165   169   174   Refrigerant Charging Chart Legend for Cooling Mode of Operation   * Note: All pressures are listed in psig. and all temperatures in °F.   - Shaded Boxes indicate   flooded conditions   - Rated Design Values. Suction Pressure will be lower than design value if indoor air   flow, entering dry bulb, or entering wet bulb temperatures are lower than design.   - Discharge temperatures greater than charted   values indicate an undercharged system.   10   13 SEER - Charging Charts - Continued   OUTDOOR TEMPERATURE (°F)   3 TON   70   75   80   85   90   95   Dis.   100   Dis.   105   Dis.   Suct. Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.   69   71   73   75   77   79   81   83   85   87   89   91   93   95   147   149   152   152   156   140   145   150   159   161   163   166   168   169   173   144   149   154   160   163   180   182   184   186   189   147   152   157   162   166   196   198   200   203   206   210   151   155   160   165   168   172   212   215   217   219   223   226   154   159   163   167   171   175   229   231   233   236   240   243   157   161   166   170   174   178   245   247   249   253   256   260   160   164   168   172   177   181   261   263   265   270   273   276   163   167   170   175   180   184   OUTDOOR TEMPERATURE (°F)   3-1/2   TON   70   75   80   85   90   95   Dis.   100   Dis.   105   Dis.   Suct. Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.   72   74   76   78   80   82   84   86   88   90   92   94   96   98   162   164   167   167   170   127   133   138   148   150   179   182   184   184   188   135   140   145   152   155   196   199   201   202   206   141   146   151   157   160   213   216   218   220   223   227   148   153   157   162   166   169   230   232   235   237   241   244   154   159   163   167   171   175   247   249   251   255   258   262   161   165   169   173   177   181   264   266   268   272   276   279   167   171   175   179   183   188   281   283   285   290   293   297   172   176   180   185   189   194   Refrigerant Charging Chart Legend for Cooling Mode of Operation   * Note: All pressures are listed in psig. and all temperatures in °F.   - Shaded Boxes indicate   flooded conditions   - Rated Design Values. Suction Pressure will be lower than design value if indoor air   flow, entering dry bulb, or entering wet bulb temperatures are lower than design.   - Discharge temperatures greater than charted   values indicate an undercharged system.   11   13 SEER - Charging Charts - Continued   OUTDOOR TEMPERATURE (°F)   4 TON   70   75   80   85   90   95   Dis.   100   Dis.   105   Dis.   Suct. Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.   71   73   75   77   79   81   83   85   87   89   91   93   95   97   151   153   156   157   160   147   152   157   164   167   169   171   173   175   179   151   156   161   167   170   187   189   191   193   197   156   161   165   170   174   204   206   209   211   215   218   160   165   169   174   177   181   222   224   226   229   233   236   164   169   173   177   181   185   240   242   244   247   251   254   169   173   177   181   185   189   257   259   261   265   269   272   172   176   180   185   189   193   275   277   279   283   287   290   176   180   184   189   193   198   OUTDOOR TEMPERATURE (°F)   5 TON   70   75   80   85   90   95   Dis.   100   Dis.   105   Dis.   Suct. Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Dis.   Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.   68   70   72   74   76   78   80   82   84   86   88   90   92   94   151   154   156   157   161   151   156   162   168   171   168   170   172   174   178   155   160   165   171   174   184   186   189   191   194   159   164   169   173   177   201   203   205   208   211   215   163   168   172   176   180   184   217   219   221   224   228   231   167   171   175   179   183   187   234   236   238   241   244   248   170   174   179   183   187   191   250   252   254   258   261   265   173   177   182   186   190   194   266   268   270   274   278   281   177   181   184   189   194   198   Refrigerant Charging Chart Legend for Cooling Mode of Operation   * Note: All pressures are listed in psig. and all temperatures in °F.   - Shaded Boxes indicate   flooded conditions   - Rated Design Values. Suction Pressure will be lower than design value if indoor air   flow, entering dry bulb, or entering wet bulb temperatures are lower than design.   - Discharge temperatures greater than charted   values indicate an undercharged system.   12   710554   Figure 11. Wiring Diagram   13   K C B L A   710589A   Figure 12. Wiring Diagram   14   15   INSTALLER   PLEASE LEAVE THESE   INSTALLATION INSTRUCTIONS   WITH THE HOMEOWNER.   708548A (Replaces 7085480)   Specifications and illustrations subject   to change without notice and without   incurring obligations.   ¢708548L¤   O'Fallon, MO   Printed in U.S.A. (06/06)   708548A   |