Heat Controller Inc Air Conditioner R 410A User Manual

HEAT CONTROLLER  
INSTALLATION INSTRUCTIONS  
HIGH-EFFICIENCY CONDENSING UNITS FEATURING  
e a r t h f r i e n d l y r e f r i g e r a n t  
EARTH-FRIENDLY R-410A REFRIGERANT  
RSG - 612 & 712 TON  
WARNING  
92-42665-14-01  
SUPERSEDES 92-42665-14-00  
[ ] INDICATES METRIC CONVERSIONS  
1.0 SAFETY INFORMATION  
WARNING  
IMPORTANT: ALL MANUFACTUR-  
ER PRODUCTS MEET CURRENT  
FEDERAL OSHA GUIDELINES FOR  
SAFETY. CALIFORNIA  
PROPOSITION 65 WARNINGS ARE  
REQUIRED FOR CERTAIN PROD-  
UCTS, WHICH ARE NOT COVERED  
BY THE OSHA STANDARDS.  
!
! WARNING  
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED  
LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION,  
ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUC-  
TIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERA-  
TION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN  
IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE  
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAM-  
AGE, PERSONAL INJURY OR DEATH.  
CALIFORNIA'S PROPOSITION 65  
REQUIRES WARNINGS FOR PROD-  
UCTS SOLD IN CALIFORNIA THAT  
CONTAIN, OR PRODUCE, ANY OF  
OVER 600 LISTED CHEMICALS  
KNOWN TO THE STATE OF  
CALIFORNIA TO CAUSE CANCER  
OR BIRTH DEFECTS SUCH AS  
FIBERGLASS INSULATION, LEAD  
IN BRASS, AND COMBUSTION  
PRODUCTS FROM NATURAL GAS.  
WARNING  
!
DISCONNECT ALL POWER TO THE UNIT BEFORE STARTING MAINTENANCE.  
FAILURE TO DO SO CAN RESULT IN SEVERE ELECTRICAL SHOCK OR  
DEATH.  
ALL “NEW EQUIPMENT” SHIPPED  
FOR SALE IN CALIFORNIA WILL  
HAVE LABELS STATING THAT THE  
PRODUCT CONTAINS AND/OR  
PRODUCES PROPOSITION 65  
CHEMICALS. ALTHOUGH WE HAVE  
NOT CHANGED OUR PROCESSES,  
HAVING THE SAME LABEL ON ALL  
OUR PRODUCTS FACILITATES  
MANUFACTURING AND SHIPPING.  
WE CANNOT ALWAYS KNOW  
“WHEN, OR IF” PRODUCTS WILL  
BE SOLD IN THE CALIFORNIA  
MARKET.  
WARNING  
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURE SYSTEM FOR  
LEAK TEST. OXYGEN REACTS VIOLENTLY WITH OIL, WHICH CAN  
CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR  
DEATH.  
WARNING  
!
AFTER COMPLETION OF WIRING CHECK ALL ELECTRICAL CONNEC-  
TIONS, INCLUDING FACTORY WIRING WITHIN THE UNIT, AND MAKE  
SURE ALL CONNECTIONS ARE TIGHT, REPLACE AND SECURE ALL  
ELECTRICAL BOX COVERS AND ACCESS DOORS BEFORE LEAVING  
UNIT OR TURNING ON POWER TO CIRCUIT SUPPLY UNIT. FAILURE TO  
DO SO CAN CAUSE A FIRE OR ELECTRICAL SHOCK RESULTING IN  
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
YOU MAY RECEIVE INQUIRIES  
FROM CUSTOMERS ABOUT CHEMI-  
CALS FOUND IN, OR PRODUCED  
BY, SOME OF OUR HEATING AND  
AIR-CONDITIONING EQUIPMENT,  
OR FOUND IN NATURAL GAS USED  
WITH SOME OF OUR PRODUCTS.  
LISTED BELOW ARE THOSE CHEM-  
ICALS AND SUBSTANCES COM-  
MONLY ASSOCIATED WITH SIMI-  
LAR EQUIPMENT IN OUR INDUS-  
TRY AND OTHER MANUFACTUR-  
ERS.  
WARNING  
!
THIS UNIT MUST BE PERMANENTLY GROUNDED. A GROUND LUG IS  
PROVIDED NEAR THE CONTACTOR FOR A GROUND WIRE. FAILURE TO  
DO SO CAN CAUSE A FIRE OR ELECTRICAL SHOCK RESULTING IN  
PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.  
• GLASS WOOL (FIBERGLASS)  
INSULATION  
• CARBON MONOXIDE (CO)  
• FORMALDEHYDE  
• BENZENE  
MORE DETAILS ARE AVAILABLE  
AT THE WEBSITES FOR OSHA  
(OCCUPATIONAL SAFETY AND  
HEALTH ADMINISTRATION), AT  
WWW.OSHA.GOV AND THE STATE  
OF CALIFORNIA'S OEHHA (OFFICE  
OF ENVIRONMENTAL HEALTH  
HAZARD ASSESSMENT), AT  
WWW.OEHHA.ORG. CONSUMER  
EDUCATION IS IMPORTANT SINCE  
THE CHEMICALS AND SUB-  
STANCES ON THE LIST ARE  
FOUND IN OUR DAILY LIVES. MOST  
CONSUMERS ARE AWARE THAT  
PRODUCTS PRESENT SAFETY AND  
HEALTH RISKS, WHEN IMPROPER-  
LY USED, HANDLED AND MAIN-  
TAINED.  
CAUTION  
!
R-410A systems operate at higher pressures than R-22 systems. Do not use  
R-22 service equipment or components on R-410A equipment.  
CAUTION  
!
Only use evaporators approved for use on R-410A systems. Use of existing R-22  
evaporators can introduce mineral oil to the R-410A refrigerant forming two differ-  
ent liquids and decreasing oil return to the compressor. This can result in com-  
pressor failure.  
3
II. INTRODUCTION  
This booklet contains the installation and operating instructions for your self-contained  
air conditioner. There are a few precautions that should be taken to derive maximum  
satisfaction from it. Improper installation can result in unsatisfactory operation or danger-  
ous conditions.  
Read this booklet and any instructions packaged with separate equipment required to  
make up the system prior to installation. Give this booklet to the owner and explain its  
provisions. The owner should retain this booklet for future reference.  
III. CHECKING PRODUCT RECEIVED  
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage,  
either shipping or concealed, should be filed immediately with the shipping company.  
Check the unit model number, electrical characteristics, and accessories to determine if  
they are correct.  
IV. EQUIPMENT PROTECTION FROM THE  
ENVIRONMENT  
The metal parts of this unit may be subject to rust or deterioration in adverse environ-  
mental conditions. This oxidation could shorten the equipment’s useful life. Salt spray,  
fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and vari-  
ous chemical contaminants from industries such as paper mills and petroleum refineries  
are especially corrosive.  
If the unit is to be installed in an area where contaminants are likely to be a prob-  
lem, special attention should be given to the equipment location and exposure.  
1. Avoid having lawn sprinkler heads spray directly on the unit cabinet.  
2. In coastal areas, locate the unit on the side of the building away from the waterfront.  
3. Shielding provided by a fence or shrubs may give some protection.  
4. Elevating the unit off its slab or base enough to allow air circulation will help avoid  
holding water against the basepan.  
Regular maintenance will reduce the buildup of contaminants and help to protect  
the unit’s finish.  
WARNING  
!
DISCONNECT ALL POWER TO THE UNIT BEFORE STARTING MAINTENANCE.  
FAILURE TO DO SO CAN RESULT IN SEVERE ELECTRICAL SHOCK OR  
DEATH.  
1. Frequent washing of the cabinet, fan blade and coil with fresh water will remove  
most of the salt or other contaminants that build up on the unit.  
2. Regular cleaning and waxing of the cabinet with an automobile polish will provide  
some protection.  
3. A liquid cleaner may be used several times a year to remove matter that will not  
wash off with water.  
Several different types of protective coatings are offered in some areas. These coatings  
may provide some benefit, but the effectiveness of such coating materials cannot be ver-  
ified by the equipment manufacturer.  
The best protection is frequent cleaning, maintenance and minimal exposure to  
contaminants.  
4
V. WHY USE AN AIR COOLED SPLIT SYSTEM?  
With an air cooled system, you have no water or sewer connections to make, and  
no troublesome and costly water treatment problems.  
Since the condensing unit is located outside the building, and the low profile air han-  
dling unit can be installed in the drop ceiling or in the conditioned space, you will not  
need a separate equipment room which takes up valuable building space.  
Because of the simple design of the condensing unit, installation is quick and sim-  
ple, and very little maintenance is required.  
The size ranges offered allow you to mix or match components to meet actual job  
requirements, thus eliminating the need to use oversized or undersized equipment.  
Equipment sized to meet the actual load will provide better operating economy, bet-  
ter humidity control, and longer equipment life.  
Remote mounting of the already quiet condensing unit keeps the compressor and  
condenser fan noise outside, and the vertical discharge fans carry the sound up and  
away from the surrounding area.  
TABLE 1  
CORNER WEIGHTS (Pounds)  
Corner Weights, Lbs. [kg]  
Unit  
Model  
Total Weight  
Lbs. [kg]  
A
B
C
D
264  
283  
RSG078  
RSG090  
45 [20.41]  
47 [21.3]  
66 [29.91]  
75 [34.0]  
63 [28.6]  
63 [28.6]  
90 [40.8]  
98 [44.5]  
FIGURE 1  
UNIT DIMENSIONS — 612 & 712 TON  
C
424364"  
31116"  
325364"  
A
D
SUCTION  
LINE 118"  
211116"  
24316"  
LIQUID  
LINE 12"  
261116"  
28716"  
HIGH VOLTAGE - 134" HOLE  
B
LOW VOLTAGE - 78" HOLE  
5
VI. STANDARD UNIT FEATURES — 612 AND 712  
CABINET — Galvanized steel with a durable powder coat paint finish. The cabinet front  
and sides are formed into a one piece unitized design with stamped louvers to provide  
protection for the condenser coils.  
SERVICE ACCESS — Control box with separation between line and control voltages,  
as well as compressor and other refrigerant controls are accessible through removable  
top and side panels (without affecting normal operation of unit).  
Condenser fan motors are mounted on removable top panels which bring the motors out  
to you and expose entire condenser coil for cleaning.  
COMPRESSOR — Hermetically sealed with internal high temperature protection and  
durable insulation on motor windings. The compressor is mounted on rubber grommets  
to reduce vibration and noise.  
CONDENSER COILS — Constructed with copper tubes and aluminum fins mechanical-  
ly bonded to tubes for maximum heat transfer capabilities. All coil assemblies are leak  
tested.  
REFRIGERANT CONNECTIONS — All field sweat joints are made external of the unit  
and are located close to the ground for a neat looking installation.  
LOW AMBIENT CONTROL — A pressure sensitive fan cycling control allows operation  
of units down to to 0°F.  
HIGH PRESSURE CONTROL Manual reset control deactivates system if abnormally  
high pressure occurs.  
LOW PRESSURE CONTROL — Automatic reset control deactivates system if abnor-  
mally low pressure or refrigerant loss occurs.  
SERVICE VALVES Standard on liquid line and suction line. Allows outdoor section  
to be isolated from indoor coil.  
FILTER DRIER — Standard, field installed. Helps maintain system cleanliness.  
CONDENSER FAN MOTORS — Direct-drive, PSC single-phase motors.  
TRANSFORMER — Step down type, from Line to 24 volts. (Refer to Figure 2.)  
CONTACTOR — (Refer to Figure 2.) The contactor is an electrical switch which oper-  
ates the compressor and condenser fans. Its 24 volt coil is activated through the High  
Pressure Control and Low Pressure Control on a call for cooling.  
CAPACITORS — Help provide starting torque necessary to boost the condenser fan  
motors to operating speed by directing their stored energy to the starter winding in step  
with the running winding.  
EQUIPMENT GROUND — Lug for field connection of ground wire.  
TESTING — All units are run tested at the factory prior to shipment.  
FIGURE 2  
LOW AMBIENT  
CAPACITOR  
CONTROL  
612 & 712 TON FEATURES  
CONTROL  
BOX  
LOW VOLTAGE  
CONNECTION  
HIGH VOLTAGE  
ENTRY  
LOW VOLTAGE  
ENTRY  
LIQUID  
VALVE  
COMPRESSOR CONTACTOR  
CRANKCASE  
HEATER  
SUCTION  
VALVE  
LOW  
CONTROL TRANSFORMER  
SCROLL  
COMPRESSOR  
HIGH PRESSURE  
SWITCH  
PRESSURE  
SWITCH  
6
TABLE 2  
PHYSICAL AND ELECTRICAL DATA TABLE (RSG)  
Condensing Unit  
078  
090  
Operating Weight (lbs.) [kg]  
Shipping Weight (lbs.) [kg]  
264 [119.8]  
283 [128.9]  
287 [130.2]  
306 [138.8]  
COMPRESSOR:  
Quantity  
1
1
Type  
RPM  
Scroll  
3500  
CONDENSER FANS:  
Quantity  
1
1
CFM [L/s]  
4700 [2218]  
24 [610]  
13 [249]  
PSC  
4700 [2218]  
24 [610]  
13 [249]  
PSC  
Diameter (in.) [mm]  
Motor Horsepower (ea.) [W]  
Type  
RPM  
1075  
1075  
CONDENSER COIL:  
Quantity  
1
112  
1
2
Rows  
Fins per Inch  
20  
22  
Square Feet [m2]  
Fins/Tubes  
22.2 [3]  
22.2 [3]  
Aluminum/Copper  
Tube Size, O.D. (in.) [mm]  
38 [10]  
38 [10]  
ELECTRICAL DATA TABLE (RSG)  
MODEL NO. RSG  
078A3  
078A4  
078A5  
090A3  
090A4  
090A5  
COMPRESSOR MOTOR:  
Electrical Characteristics  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
OPERATING CURRENT:  
Rated Load Amps  
22.4/22.4  
149  
10.6  
75  
7.0  
54  
25/25  
164  
12.2  
100  
9.0  
78  
Locked Rotor Amps  
CONDENSER FAN MOTORS:  
Volts & Phase  
208/230-1  
2.2  
460-1  
1.3  
575-1  
1.0  
208/230-1  
2.2  
460-1  
1.3  
575-1  
1.0  
Full Load Amps (each)  
SYSTEM CHARACTERISTICS:  
Unit FLA  
25.0  
12  
15  
8.0  
28.0  
14.0  
17  
10.0  
13  
Minimum Circuit Ampacity  
31/31  
11.0  
34/34  
Max. Fuse Size or HACR  
Circuit Breaker Ampacity  
50/50  
60  
25  
30  
15  
30  
50/50  
60  
25  
30  
20  
30  
Disconnect Size  
NOTE: N.E.C., C.E.C. and local codes take precedence over suggested wire and fuse sizes.  
[ ] Designates Metric Conversion  
VII. INSTALLATION  
A. IMPORTANT MESSAGE TO OWNER  
The manufacturer assumes no responsibility for equipment installed in violation of any  
code or regulation. The operation portion of this manual gives instructions as to the ser-  
vice and care of the unit. It is recommended that the installer go over the operational  
portion of this manual with the owner so that there is a full understanding of the equip-  
ment and how it is intended to function.  
These instructions should be read and kept for future reference. It is suggested that this  
booklet be affixed to or adjacent to the indoor equipment. It is addressed to your dealer  
and serviceman, but we highly recommend that you read it—paying particular attention  
to the section titled “MAINTENANCE.”  
B. INSPECTION AND HANDLING  
Inspect exterior of unit for evidence of rough handling in shipment. If damage is found,  
enter claim at once. Unpack carefully after moving unit to approximate location. Any  
damage should be reported immediately to the transportation company.  
Material in this shipment was inspected at the factory and released to the common carri-  
er with no known damage.  
7
C. ORDER PARTS  
When reporting shortages or damaged parts, or when ordering repair parts, give the  
complete unit model and serial numbers which are stamped on the Unit Rating Plate.  
D. STANDARD ITEMS  
The condensing unit consists of a completely assembled package which includes a com-  
pressor, a condenser coil, fan, fan motors, outdoor control box, factory wiring, factory  
tubing and fittings.  
E. INSTALLATION GENERAL  
NOTE: These units must be installed outdoors. No ductwork can be attached, or  
other modifications made, to the discharge grille. Modifications will affect perfor-  
mance or operation.  
The condensing unit should be installed outdoors. It should be located as near as possi-  
ble to the evaporator section to keep connecting refrigerant tubing lengths to a minimum.  
The unit must be installed to allow a free air flow to the condenser coils.  
If several units are installed adjacent to each other, care must be taken to avoid recircu-  
lation of air from one condenser to another. In all installations, adequate space must be  
provided for installation and servicing.  
FIGURE 3  
CLEARANCES  
36” min. [914 mm]  
Condensing Unit  
Condensing Unit  
Control Box End  
24” min.  
[610 mm]  
24” min.  
[610 mm]  
Control Box End  
36” min. [914 mm]  
The unit must not be connected to any duct work. Do not locate unit under a roof drip; if  
necessary, install gutters, etc., to prevent water run-off from hitting the unit. To prevent  
air recirculation, it is recommended that the unit not be installed under an overhang, but  
if necessary allow a minimum of 60 inches above the unit for air discharge.  
NOTE: To prevent the possibility of freeze damage, you can install an air proving switch  
in the air handler supply duct wired in series with the compressor contactor coil (24V)  
which would lock out the compressor in the event of air flow failure.  
F. ROOFTOP INSTALLATION (REFER TO FIGURE 4)  
If rooftop installation is required, make certain that the building construction is adequate  
for the weight of the unit. (Refer to physical data chart.) Before placing the unit on the  
roof, make certain that the nylon rigging slings are of sufficient length to maintain equilib-  
rium of the unit when lifting. Under no circumstances should the unit be lifted by only one  
corner for rooftop installation.  
G. SLAB INSTALLATION  
Condensing units should be set on a solid level foundation. When installed at ground  
level, the unit should be placed on a 6 inch cement slab. If the pad is formed at the  
installation site, do not pour the pad tight against the structure, otherwise vibration will  
be transmitted from the unit through the pad.  
8
FIGURE 4  
ROOFTOP INSTALLATION  
NYLON SLINGS  
SPREADER BARS  
VIII. REFRIGERANT PIPING DATA  
CONDENSING UNITS ARE SHIPPED WITH A NITROGEN HOLDING CHARGE.  
EVACUATE CONDENSING UNIT BEFORE CHARGING WITH REFRIGERANT.  
TABLE 3  
REFRIGERANT PIPING DATA  
Equivalent Length (ft.) [m] of straight type “L” tubing for non-ferrous valves and fittings (brazed).  
Tee,  
Branch Flow  
Tube Size,  
O.D.  
Solenoid  
Valve  
Angle  
Valve  
Short Radius  
Ell  
Long Radius  
Ell  
Tee,  
Line flow  
1/2  
5/8  
70  
[21.3]  
[21.9]  
[22.9]  
[23.8]  
8.3  
[2.5]  
[3.2]  
[3.8]  
[4.4]  
[5.7]  
[7.0]  
[8.3]  
1.6  
1.9  
2.1  
2.4  
3.0  
3.6  
4.2  
5.3  
[0.5]  
1.0  
1.2  
1.4  
1.6  
2.0  
2.4  
2.8  
3.5  
[0.3]  
1.0  
[0.3]  
[0.4]  
[0.4]  
[0.5]  
[0.6]  
[0.7]  
[0.8]  
[1.1]  
3.1  
3.6  
4.2  
4.8  
6.0  
7.2  
8.4  
10.7  
[0.9]  
72  
75  
78  
10.4  
12.5  
14.6  
18.8  
22.9  
27.1  
35.4  
[0.6]  
[0.7]  
[0.7]  
[0.9]  
[1.1]  
[1.3]  
[1.6]  
[0.4]  
[0.4]  
[0.5]  
[0.6]  
[0.7]  
[0.8]  
[1.1]  
1.2  
1.4  
1.6  
2.0  
2.4  
2.8  
3.5  
[1.1]  
[1.3]  
[1.5]  
[1.8]  
[2.2]  
[2.6]  
[3.3]  
3/4  
7/8  
1 1/8  
1 3/8  
1 5/8  
2 1/8  
[10.8]  
9
WARNING  
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURE SYSTEM FOR  
LEAK TEST. OXYGEN REACTS VIOLENTLY WITH OIL, WHICH CAN  
CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR  
DEATH.  
FIGURE 5  
LIQUID LINE PRESSURE DROP PER 100 FEET EQUIVALENT LENGTH  
(TYPE L COPPER TUBING)  
NOTES:  
1. When evaporator coil is above condenser, the pressure drop due to vertical lift (.5  
PSIG per foot of lift) must be added to the pressure drop derived from this curve.  
2. Size liquid line for no more than 10°F loss (approximately 50 PSIG total pressure  
drop).  
3. Do not oversize liquid line. Oversized liquid lines add significantly to the amount of  
refrigerant required to charge the system.  
4. The maximum recommended velocity with solenoid valves or other quick closing  
devices in the liquid line is 300 FPM.  
A. INSTALLATION OF PIPING  
Once located, the condensing unit is ready to be interconnected with the evaporator  
using ONLY refrigeration grade dehydrated tubing. The following should be considered  
when connecting the tubing.  
1
1. Pitch the suction line toward the compressor approximately ⁄  
2
inch every 10 feet to  
facilitate oil return.  
2. It is recommended that the sight glass, filter drier and liquid line solenoid valve be  
installed in the liquid line just prior to the evaporator.  
3. Silver solder (such as silfos, Easy Flow, etc.) should be used for all refrigerant joints.  
4. Thoroughly clean all joints before fluxing. DO NOT USE ACID FLUX.  
5. When fluxing, limit the application of paste to the minimum and always apply flux to  
the male portion of the connection.  
6. Suction lines should be insulated to prevent condensate drip. Use insulation of at  
3
least ⁄  
8
inch wall thickness. The insulation should be installed on the tubing prior to  
making the sweat connections.  
10  
7. Insulate the liquid line whenever the heat pick-up or transfer can affect the sub-cool-  
ing.  
8. Care should be taken to avoid transmission of noise or vibration to building structure.  
FIGURE 6  
SUCTION LINE SYSTEM CAPACITY LOSS IN PERCENT PER 100 FEET EQUIVALENT LENGTH  
(TYPE L COPPER TUBING)  
NOTES:  
1. The minimum velocity line (700 fpm) is recommended for cooling only units with verti-  
cal or horizontal run refrigerant lines.  
2. For suction pressure drop (PSIG), multiply percent (%) loss by 1.18.  
B. TYPICAL PIPING RECOMMENDATIONS  
REFRIGERANT PIPING:  
The following will be of help in accomplishing a successful installation.  
1. Size liquid line for no more than 10°F loss which corresponds to approximately 50  
PSIG pressure drop.  
2. Size suction lines for no more than 2°F loss which corresponds to approximately 5  
PSIG pressure drop.  
3. Install sight glass, filter drier and solenoid valve in liquid line adjacent to evaporator.  
Filter drier should be between the condensing unit and sight glass.  
4. Pitch all horizontal suction lines downward in the direction of flow. (12" to 10 ft. run)  
11  
5. When making up refrigerant piping, take every precaution to prevent dirt and moisture  
from entering the piping.  
6. Locate the condensing unit and evaporator(s) as close together as possible to mini-  
mize piping runs.  
7. Liquid or suction lifts not to exceed 60 ft.  
TABLE 4  
RECOMMENDED VAPOR AND LIQUID LINE SIZES FOR VARIOUS  
LENGTHS OF RUN  
RECOMMENDED VAPOR AND LIQUID LINE  
SIZES FOR VARIOUS LENGTHS OF RUN  
EQUIVALENT  
LENGTH TO  
EVAPORATOR  
(FEET)  
LIQUID LINE O.D.  
VAPOR LINE O.D.  
SIZES (INCHES)  
SIZES (INCHES)  
078  
090  
078  
11⁄  
11⁄  
11⁄  
13⁄  
090  
11⁄  
11⁄  
13⁄  
13⁄  
1
1
8
8
0' to 15'  
16' to 50'  
2  
2  
1
1
1
1
1
1
2
2
8
8
51' to 100'  
101' to 150'  
2  
2  
8
8
2  
2  
8
8
NOTE: Runs between condenser and evaporator not to  
exceed 150' linear equivalent length.  
FIGURE 7  
COIL BELOW CONDENSING UNIT  
TX VALVE  
SOLENOID  
VALVE  
LIQUID  
LINE  
NOTE: PIPING  
SIGHT GLASS  
ACCESSORIES SHOWN  
SHOULD BE MOUNTED  
AS CLOSE TO AIR  
HANDLER UNIT AS  
POSSIBLE  
SUCTION  
LINE  
FIGURE 8  
COIL ABOVE CONDENSING UNIT  
LIQUID  
LINE  
SUCTION  
LINE  
12  
VIX. WIRING  
NOTE: Field wiring must comply with the National Electric Code (CEC in Canada) and  
any local ordinance that may apply.  
X. ELECTRICAL POWER  
It is important that proper electrical power is available at the unit. Voltage must not vary  
more than 10% of that stamped on the rating plate. (See Electrical Data Table for mini-  
mum and maximum voltage.) Interphase voltage variation on three-phase units must not  
be more than 3%. Contact local power company for correction of improper voltage or  
phase unbalance.  
IMPORTANT: Models equipped with scroll compressors must be phased correctly for  
proper compressor rotation. If the compressor is noisy or if suction and discharge pres-  
sures do not appear normal, reverse any two power leads to the unit. Extended run time in  
reverse rotation will damage the compressor and lead to premature failure.  
XI. POWER WIRING  
Power wiring must be run in grounded rain-tight conduit. Power wiring must comply with  
the National Electric Code (C.E.C. in Canada) and any applicable local code.  
XII. WIRE ROUTING  
POWER WIRING MUST BE RUN IN CONDUIT. Conduit must be run through the con-  
nector panel below the service cover and attached to the bottom of the control box.  
If low (extra-low in Canada) voltage control wire is run in conduit with power supply,  
Class I insulation is required. If run separate, Class II is required. Low voltage wiring  
may be run through the insulated bushing provided in the 7/8 " hole in the connector  
panel then routed to the control box.  
WARNING  
!
AFTER COMPLETION OF WIRING CHECK ALL ELECTRICAL CONNEC-  
TIONS, INCLUDING FACTORY WIRING WITHIN THE UNIT, AND MAKE  
SURE ALL CONNECTIONS ARE TIGHT, REPLACE AND SECURE ALL  
ELECTRICAL BOX COVERS AND ACCESS DOORS BEFORE LEAVING  
UNIT OR TURNING ON POWER TO CIRCUIT SUPPLY UNIT. FAILURE TO  
DO SO CAN CAUSE A FIRE OR ELECTRICAL SHOCK RESULTING IN  
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
XIII. GROUNDING  
WARNING  
!
A grounding lug is provided in control box for a ground wire.  
Grounding may be accomplished by grounding the power line conduit to the unit.  
THIS UNIT MUST BE PERMA-  
NENTLY GROUNDED. A GROUND  
LUG IS PROVIDED NEAR THE  
CONTACTOR FOR A GROUND  
WIRE. FAILURE TO DO SO CAN  
CAUSE A FIRE OR ELECTRICAL  
SHOCK RESULTING IN PROPER-  
TY DAMAGE, SEVERE PERSON-  
AL INJURY OR DEATH.  
XIV. THERMOSTAT — 612 AND 712 TON  
A single-stage cooling, two-stage heating (if heating is used) thermostat should be  
mounted on an inside wall about four to five feet above the floor in a location where it will  
not be affected by the sun or drafts, from open doors or other sources. Install, level, and  
after installation check the thermostat calibration and recalibrate if necessary.  
XV. LEAK TESTING  
Pressure line set and coil through service fittings with dry nitrogen to 150 psig maximum.  
Leak test all joints using liquid detergent. If a leak is found, relieve pressure, repair and  
retest.  
13  
XVI. R-410A REFRIGERANT  
A. TOOLS REQUIRED FOR INSTALLING & SERVICING R-410A MODELS  
Manifold Sets:  
-Up to 800 PSIG High Side  
-Up to 250 PSIG Low Side  
-550 PSIG Low Side Retard  
Manifold Hoses:  
-Service Pressure Rating of 800 PSIG  
Recovery Cylinders:  
-400 PSIG Pressure Rating  
-Dept. of Transportation 4BA400 or 4BW400  
!
CAUTION  
R-410A systems operate at higher pressures than R-22 systems. Do not use  
R-22 service equipment or components on R-410A equipment.  
B. SPECIFICATION OF R-410A:  
Application: R-410A is not a drop-in replacement for R-22; equipment designs must  
accommodate its higher pressures It cannot be retrofitted into R-22 condensing units.  
Physical Properties: R-410A has an atmospheric boiling point of -62.9°F and its satu-  
ration pressure at 77°F is 224.5 psig.  
Composition: R-410A is an azeotropic mixture of 50% by weight difluoromethane  
(HFC-32) and 50% by weight pentafluoroethane (HFC-125).  
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22.  
Recovery and recycle equipment, pumps, hoses and the like need to have design pres-  
sure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig high-  
side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a ser-  
vice pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service  
pressure rating. DOT 4BA400 or DOT 4BW400.  
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can  
become combustible. R-410A and air should never be mixed in tanks or supply  
lines, or be allowed to accumulate in storage tanks. Leak checking should never  
be done with a mixture of R-410A and air. Leak checking can be performed safely  
with nitrogen or a mixture of R-410A and nitrogen.  
C. QUICK REFERENCE GUIDE FOR R-410A  
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than  
R-22. Ensure that servicing equipment is designed to operate with R-410A.  
• R-410A refrigerant cylinders are pink in color.  
• R-410A, as with other HFC’s, is only compatible with POE oils.  
• Vacuum pumps will not remove moisture from oil.  
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999,  
R-410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for  
equipment charging. Post March 1999 cylinders do not have a dip tube and should be  
inverted to ensure liquid charging of the equipment.  
• Do not install a suction line filter drier in the liquid line.  
• A liquid line filter drier is standard with every unit. Only manufacturer approved liquid  
line filter driers can be used. These filter driers are rated for minimum working pres-  
sure of 600 psig.  
• Desiccant (drying agent) must be compatible for POE oils and R-410A.  
14  
D. REPLACEMENT UNITS  
To prevent failure of a new condensing unit, the existing evaporator tubing system must  
be correctly sized and cleaned or replaced. Care must be exercised that the expansion  
device is not plugged. For new and replacement units, a liquid line filter drier should be  
installed and refrigerant tubing should be properly sized. Test the oil for acid. If positive,  
a suction line filter drier is mandatory.  
IMPORTANT: WHEN REPLACING AN R-22 UNIT WITH AN R-410A UNIT, EITHER  
REPLACE THE LINE SET OR ENSURE THAT THE EXISTING LINE SET IS THOR-  
OUGHLY CLEANED OF ANY OLD OIL OR DEBRIS.  
CAUTION  
!
Only use evaporators approved for use on R-410A systems. Use of existing R-22  
evaporators can introduce mineral oil to the R-410A refrigerant forming two differ-  
ent liquids and decreasing oil return to the compressor. This can result in com-  
pressor failure.  
E. EVAPORATOR COIL  
REFER TO EVAPORATOR COIL MANUFACTURER’S INSTALLATION INSTRUC-  
TIONS:  
IMPORTANT: The manufacturer is not responsible for the performance and operation of  
a mismatched system, or for a match listed with another manufacturer’s coil.  
XVII. EVACUATION AND CHARGING  
The evacuation of any system component that has been exposed to atmosphere or lost  
its charge is essential before charging. Never attempt to operate a system while it is  
under a vacuum.  
FIGURE 9  
TYPICAL FIELD WIRING CONNECTIONS — 612 AND 712 TON  
15  
TABLE 5  
FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS  
SOLID COPPER WIRE - AWG  
3.0  
2.5  
2.0  
16  
16  
18  
14  
14  
16  
12  
12  
14  
10  
12  
12  
10  
10  
12  
10  
10  
10  
50  
100  
150  
200  
250  
300  
Length of Run - Feet (1)  
(1) Wire length equals twice the run distance.  
NOTE: The condensing unit is shipped with a holding charge of dry nitrogen  
which must be purged from the unit before evacuation.  
1. Since the condensing unit itself must be evacuated, open the suction, discharge and  
liquid shut-off valves.  
2. Use a refrigeration type vacuum pump capable of evacuation in the 500 micron  
range.  
3. Connect the vacuum pump to the service manifold assembly with a pressure gauge  
that will read 30 inches vacuum. Connect the service manifold to the suction line  
schrader valve port.  
1
4. With an accurate scale, ⁄  
2
oz., set refrigerant tank up so its weight can be measured  
while in a position to charge liquid. (Unit must be off.) Energize liquid line solenoid  
valve by wiring valve to 24V power supply (or open by manual stem if applicable).  
5. Connect to the liquid shut-off valve port. Shut off tank and evacuate the system. The  
pressure gauge should read at least 29.5" of vacuum.  
6. Triple evacuate the system.  
7. The refrigerant system will now be free of noncondensables.  
8. Remove vacuum pump from 3-way valve.  
9. Before tightening, purge tank and service valve hose.  
CHARGING HINTS  
SYMPTOM  
POSSIBLE CAUSE  
REMEDY  
High head pressure  
a. Air flow to or from condenser restricted or  
dirty condenser  
b. Faulty condenser fan or motor.  
c. Overcharge of refrigerant  
d. Air in system.  
a. Remove obstruction, relocate condensing unit,  
if necessary clean condenser.  
b. Replace.  
c. Reduce charge.  
d. Evacuate and recharge.  
Low head pressure  
a. Short of refrigerant.  
b. Low evaporator air flow.  
a. Check for leak, add charge.  
b. Increase blower speed, check filters.  
Low vapor &  
hot compressor  
a. Short of refrigerant.  
a. Check for leak—add refrigerant.  
Excessive sweating  
a. Low indoor airflow  
b. Excess refrigerant  
a. Increase speed of air handler blower or reduce  
restriction—replace air filter.  
b. Slowly reduce charge.  
10. Note weight of refrigerant tank.  
11. De-energize liquid line solenoid valve. Open refrigerant tank valve. Allow pressure in  
tank and unit to equalize.  
12. Close off service valve to liquid port and note weight of refrigerant tank.  
13. Re-wire liquid line solenoid to thermostat control. Close main disconnect switch and  
turn thermostat to lowest setting.  
14. Charge unit per chart.  
16  
TABLE 6  
REQUIRED OZS. R-410A PER FT. OF TUBING  
Tube Size  
O.D., In.  
Liquid  
Vapor  
oz/ft  
oz/ft  
1.06  
1.65  
2.46  
3.28  
1/2  
5/8  
0.04  
0.07  
0.10  
0.13  
0.22  
0.34  
0.48  
0.84  
3/4  
7/8  
1 1/8  
1 3/8  
1 5/8  
2 1/8  
Quantities based on 110°F liquid and 45°F vapor.  
BASIC SYSTEM CHARGE*  
Unit  
Model  
Basic System  
Charge, Oz. [g] *  
RSG078  
178 [5046]  
242 [6861]  
RSG090  
*-System with 0 Feet [0] of tubing.  
15. Note weight of refrigerant tank.  
16. When system has stabilized, check superheat at the suction line service valve. The  
actual line temperature should be 15° to 25°F higher than the saturation temperature  
corresponding to the suction pressure. If superheat is measured at evaporator, the  
actual line temperature should be 15° to 20° higher than the saturation temperature  
corresponding to the suction pressure.  
17. Close service ports on suction and liquid valves. Remove service gauges.  
18. Replace service port caps and valve stem caps. These caps must be replaced to  
prevent leaks.  
19. Record total charge quantity on rating plate.  
XVIII. SEQUENCE OF OPERATION — 612  
XVIII. AND 712 TON  
1. When the room temperature is higher than the thermostat setting, the thermostat con-  
tacts close and energize the compressor contactor (CC) through the high pressure,  
and low pressure controls. If the unit has “short cycled” and the optional anti-short  
cycle timer (TDC) has been supplied, the contactor coil (CC) will remain de-energized  
for up to five (5) minutes.  
2. The system will continue cooling operation, as long as the contacts of all safety  
devices are closed and until the thermostat is satisfied.  
3. When the thermostat is satisfied, compressor or contactor (CC) is de-energized.  
XIX. ACCESSORIES  
A. ANTI-SHORT CYCLE TIMER  
ANTI-SHORT-CYCLE TIMER — Prevents restarting of unit for five minutes if shut down  
for any reason. (See wiring diagram and schematic in this manual for proper location  
and installation; item TDC.)  
17  
FIGURE 10  
ANTI-SHORT CYCLE TIMER  
B. LIQUID PRESSURE CONTROL  
Outdoor fan motor speed control designed to regulate condenser head pressure at low  
ambients by varying the air volume through the condenser. Has been tested and is avail-  
able through the parts department.  
C. LIQUID LINE SOLENOID VALVE  
LIQUID LINE SOLENOID VALVE (24V) — Recommended for all split system applica-  
tions, to prevent refrigerant migration during off cycles. See wiring connection (See  
Figure 11). Solenoid to be located in liquid line close to air handler.  
FIGURE 11  
LIQUID LINE SOLENOID VALVE  
D. SIGHT GLASS / MOISTURE INDICATOR  
SIGHT GLASS — Allows viewing of the refrigerant. Bubbles may indicate a shortage of  
refrigerant or a restriction in the liquid line. The color indicator shows relative moisture  
saturation of the refrigerant. Its inclusion in the refrigerant piping is recommended. A  
minimum of 12 hours after installation is required before attempting to determine if a  
moisture condition within the system exists.  
18  
XX. MISCELLANEOUS  
A. CHARGE CHARTS  
FIGURE 12  
RSG078  
SYSTEM CHARGE CHART  
1
6 ⁄  
2
TON CONDENSER  
6-1/2 TON CONDENSING UNIT 60HZ.  
REFRIGERANT R-410A  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
110  
105  
100  
95  
90  
85  
80  
75  
70  
65  
60  
55  
100 105 110 115 120 125 130 135 140 145 150 155 160 165  
Pressure at Suction Service Port (psig)  
REQUIRED OUNCES R-410A  
CHARGE PER FOOT OF TUBING  
VAPOR  
LINE  
TUBE SIZE  
O.D. IN.  
LIQUID  
LINE  
1/2  
5/8  
1.06  
1.65  
1-1/8  
1-3/8  
.22  
.34  
REFRIGERANT REQUIRED: 178 OZ. WITH 0 FT. OF SUCTION AND LIQUID LINE.  
CAUTION: BEFORE FINAL REFRIGERANT CHECK, INDOOR AIR TEMPERATURE SHOULD BE AT COMFORT CONDITIONS  
FOR MOST ACCURATE RESULTS.  
INSTRUCTIONS:  
1. CONNECT PRESSURE GUAGES TO SUCTION AND LIQUID PORTS ON UNIT.  
2. MEASURE AIR TEMPERATURE TO OUTDOOR COIL.  
3. PLACE AN "X" ON THE APPROPRIATE CHART WHERE THE SUCTION AND LIQUID PRESSURES CROSS.  
4. IF "X" IS BELOW AMBIENT TEMPERATURE LINE, ADD CHARGE AND REPEAT STEP 3.  
5. IF "X" IS ABOVE AMBIENT TEMPERATURE LINE, RECOVER EXCESS CHARGE AND REPEAT STEP 3.  
6. IF CONDENSER FANS ARE NOT RUNNING, THE HEAD PRESSURE CONTROL MAY REQUIRE JUMPERING.  
92-102644-01-01  
19  
FIGURE 13  
RSG090  
SYSTEM CHARGE CHART  
TON CONDENSER WITH 10 TON EVAPORATOR  
1
7 ⁄  
2
7-1/2 TON CONDENSING UNIT 60HZ.  
REFRIGERANT R-410A  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
110  
105  
100  
95  
90  
85  
80  
75  
70  
65  
60  
55  
100 105 110 115 120 125 130 135 140 145 150 155 160 165  
Pressure at Suction Service Port (psig)  
REQUIRED OUNCES R-410A  
CHARGE PER FOOT OF TUBING  
VAPOR  
LINE  
TUBE SIZE  
O.D. IN.  
LIQUID  
LINE  
1/2  
5/8  
1.06  
1.65  
1-1/8  
1-3/8  
.22  
.34  
REFRIGERANT REQUIRED: 239 OZ. WITH 0 FT. OF SUCTION AND LIQUID LINE  
CAUTION: BEFORE FINAL REFRIGERANT CHECK, INDOOR AIR TEMPERATURE SHOULD BE AT COMFORT CONDITIONS  
FOR MOST ACCURATE RESULTS.  
INSTRUCTIONS:  
1. CONNECT PRESSURE GUAGES TO SUCTION AND LIQUID PORTS ON UNIT.  
2. MEASURE AIR TEMPERATURE TO OUTDOOR COIL.  
3. PLACE AN "X" ON THE APPROPRIATE CHART WHERE THE SUCTION AND LIQUID PRESSURES CROSS.  
4. IF "X" IS BELOW AMBIENT TEMPERATURE LINE, ADD CHARGE AND REPEAT STEP 3.  
5. IF "X" IS ABOVE AMBIENT TEMPERATURE LINE, RECOVER EXCESS CHARGE AND REPEAT STEP 3.  
6. IF CONDENSER FANS ARE NOT RUNNING, THE HEAD PRESSURE CONTROL MAY REQUIRE JUMPERING.  
92-102644-03-01  
20  
B. MAINTENANCE AND OPERATION  
1. All access panels must be in place when unit is in operation.  
2. For maximum efficiency, the condenser coil must be kept clean. Periodic inspections,  
depending on local conditions are recommended. If it is necessary to clean the con-  
denser coil, use a common garden hose.  
3. Never operate the unit without filters installed in the air handler.  
4. If a compressor crankcase heater is used, it must be turned on 12 hours prior to start-  
ing the compressor.  
1. CONTACTOR  
The contactor is an electrical switch which operates the compressor and condenser  
fans. Its 24 volt coil is activated either directly or indirectly by the room thermostat.  
2. HIGH PRESSURE SWITCH (HPC)  
Opens the contactor (24 volt) circuit on high refrigerant pressure—Manual Reset—check  
for cause of tripping before putting unit back in service.  
3. LOW PRESSURE SWITCH (LPC)  
Acts as safety against loss of refrigerant and low evaporator temperatures.  
4. PRE-START CHECK  
PRE-START CHECK  
10. Is refrigerant tubing neatly run and suction line thoroughly  
insulated?  
11. Is condensate drain line properly sized, run, trapped and  
pitched?  
12. Are refrigerant connections tight and leak tested?  
13. Is filter clean and in place?  
1. Is condensing unit properly located and level?  
2. Is air free to travel to and from condensing unit?  
3. Is the wiring correct and according to the unit wiring dia-  
gram?  
4. Are wiring connections tight? (Including those in unit and  
compressor electrical box.)  
14. Does the condenser fan turn free without rubbing?  
15. Is the fan tight on the fan shaft?  
16. Are all covers and access panels in place to prevent air  
loss?  
5. Is the unit properly grounded?  
6. Is circulating air blower correctly wired?  
7. Is condensing unit properly fused?  
8. Is the thermostat level, correctly wired and in a good loca-  
tion?  
17. Are refrigerant valves open for full flow?  
9. Is the ductwork correctly sized, run, taped and insulated?  
21  
C. TROUBLESHOOTING  
!
WARNING  
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE  
TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.  
SYMPTOM  
POSSIBLE CAUSE  
REMEDY  
Unit will not run  
• Power off or loose electrical connection  
• Thermostat out of calibration-set too high  
• Defective contactor  
• Check for correct voltage at compressor contactor in control box  
• Reset  
• Check for 24 volts at contactor coil - replace if contacts are  
open  
• Blown fuses  
• Transformer defective  
• High pressure control open (if provided)  
• Replace fuses  
• Check wiring-replace transformer  
• Reset-also see high head pressure remedy-The high pressure  
control opens at 610 PSIG  
• Interconnecting low voltage wiring damaged.  
• Replace thermostat wiring  
Condenser fan runs, compressor • Run or start capacitor defective (single phase only)  
• Replace  
• Replace  
doesn’t  
• Start relay defective (single phase only)  
• Loose connection  
• Check for correct voltage at compressor -  
check & tighten all connections  
• Wait at least 2 hours for overload to reset.  
If still open, replace the compressor.  
At compressor terminals, voltage must be within 10% of rating  
plate volts when unit is operating.  
• Add start kit components  
• Compressor stuck, grounded or open motor winding,  
open internal overload.  
• Low voltage condition  
Insufficient cooling  
• Improperly sized unit  
• Improper airflow  
• Incorrect refrigerant charge  
• Air, non-condensibles or moisture in system  
• Incorrect voltage  
• Recalculate load  
• Check - should be approximately 400 CFM per ton.  
• Charge per procedure attached to unit service panel  
• Recover refrigerant, evacuate & recharge, add filter drier  
• At compressor terminals, voltage must be within 10% of rating  
plate volts when unit is operating.  
Compressor short cycles  
• Incorrect voltage  
• At compressor terminals, voltage must be 10% of  
nameplate marking when unit is operating.  
• Replace - check for correct voltage  
• Add refrigerant  
• Defective overload protector  
• Refrigerant undercharge  
Registers sweat  
• Low evaporator airflow  
• Increase speed of blower or reduce restriction - replace air  
filter  
High head-low vapor pressures  
• Restriction in liquid line, expansion device or filter drier  
• Flow check piston size too small  
• Incorrect capillary tubes  
• Remove or replace defective component  
• Change to correct size piston  
• Change coil assembly  
• TXV does not open  
• Replace TXV  
High head-high or normal vapor  
pressure - Cooling mode  
• Dirty condenser coil  
• Clean coil  
• Correct system charge  
• Repair or replace  
• Refrigerant overcharge  
• Outdoor fan not running  
• Air or non-condensibles in system  
• Recover refrigerant, evacuate & recharge  
High head-high or normal vapor  
pressure - Heating mode  
• Low air flow - condenser coil  
• Refrigerant overcharge  
• Air or non-condensibles in system  
• Dirty condenser coil  
• Check filters - correct to speed  
• Correct system charge  
• Recover refrigerant, evacuate & recharge  
• Check filter - clean coil  
Low head-high vapor pressures  
• Defective Compressor valves  
• Defective TXV(s)  
• Replace compressor  
• Replace coil assembly  
Low vapor - cool compressor -  
iced evaporator coil  
• Low evaporator airflow  
• Operating below 65°F outdoors  
• Moisture in system  
• Increase speed of blower or reduce restriction - replace air filter  
• Add Low Ambient Kit  
• Recover refrigerant - evacuate & recharge - add filter drier  
High vapor pressure  
• Excessive load  
• Defective compressor  
• Recheck load calculation  
• Replace  
Fluctuating head & vapor  
pressure  
• TXV hunting  
• Check TXV bulb clamp - check air distribution on coil - replace  
TXV  
• Recover refrigerant, evacuate & recharge  
• Air or non-condensibles in system  
• Air or non-condensibles in system  
Gurgle or pulsing noise at  
• Recover refrigerant, evacuate & recharge  
expansion device or liquid line  
22  
23  
24  
CM 1208  

Canon Pixma MX452 Wlse All In One Printer Printer 6989B002 User Manual
Carrier 48HJ004 007 User Manual
Cornelius REMCOR 1550 User Manual
Cypress CY8C24794 User Manual
Dakota Digital VM 170 User Manual
Epson Printer RP U420 User Manual
Fisher Price R4743 User Manual
Ford LINCOLN 5L3Z 19G323 AAA User Manual
Heat Glo LifeStyle 6000G IPI User Manual
HP Hewlett Packard Officejet 5610 User Manual