HAZARDGARD
HAZARDOUS DUTY AIR CONDITIONERS
advanced features for safety and durability
Permanent split capacitor and totally enclosed fan motor to ensure
efficient operation– even under adverse electrical conditions.
Enclosed fan motor has hermetically sealed overload for arc-free
operation.
Hermetically sealed refrigeration system.
Environmentally sealed on/off switch and gold plated contacts in
thermostat for corrosion resistance.
Solid-state control relays for compressor and fan operation.
Hot gas bypass allows the air conditioner to operate at low ambient
conditions without freezing at outdoor ambient temperatures as
low as 45° F.
ideal applications
Offshore oil rigs, on-shore oil
company offices and refineries
Petrochemical sites and propane
fill-up stations
built tough
Paint and varnish storage or
processing plants
rugged, commercial grade components.
heavy gauge steel cabinets.
Grain alcohol processors or
storage sites
state-of-the-art manufacturing.
engineered to perform better and last longer.
Plant areas using strong
solvents or chemicals
Munitions plants or armories
PVC or plastics plants and
processing points
Durable, commercial grade quality that lasts
Friedrich air conditioners are a SUPERIOR PRODUCT built from high grade
materials and components that deliver DEPENDABLE OPERATION for years
after your purchase.
Recycling plants
Furniture refinishing/stripping
workshops
Fertilizer plants
Trusted performance from a trusted company
Friedrich air conditioners can be found in some of the world’s toughest
locations. Oil companies rely on us to cool offshore oil rigs in the most
extreme conditions, and military bases and government offices all over the
world choose Friedrich. Industrial and high tech leaders also trust Friedrich
commercial grade products for their applications. If we can handle all of
these jobs, just think how we’ll perform for yours.
Office complexes where methane
is a by-product
Hazardous materials storage
QUALITY
Specifications
Energy Efficiency
Ratio AHAM
Moisture
Removal
(Pints/ Hr.)
Air Direction
Controls
Room Side Air
Circulation
CFM
Cooling Capacity
(BTU/Hr.- AHAM)
Electrical Characteristics (60 Hertz)
Model
Volts Rated
Amps AHAM
Watts
EER
SH15L30
SH20L30
15000/15000
19800/19500
230/208
230/208
7.9/8.7
10.0/10.9
1765/1765
2200/2167
8.5/8.5
9.0/9.0
4.0
5.7
8-way
8-way
375
375
Installation Information
Circuit Rating
Window Width Thru-The-Wall Finished Breaker or
Weight
(Lbs.)
Dimensions (Inches)
(Inches)
Hole (Inches)
T - D Fuse
Minimum Minimum
Depth Depth Hood Extension Extension
Model
Height
Width
Overall to Louvers Into Room
Outside
Min. Max.
Height
Width
Volts - Amps
Net
Shipping
3
7
3
3
15 15 16
/
17 15 16
/
25 15 16
/
25 15 16
/
27
27
8
9 316
/
9 316
/
3 1 16
/
3 1 16
/
16 1516
/
16 1516
/
27
27
8
42
42
16 16
26 /16
250V - 15A
250V - 15A
140
166
152
179
/
/
/
SH15L30
SH20L30
3
/
7
/
3
/
3
8
8
18 16
26 /16
Due to continuing engineering research and technology, specifications are subject to change without notice. Manufactured under U.S. Design
Patent DES 368, 306 decorative front; Utility Patent 5, 622, 058. MAXIMUM outdoor ambient operating temperature is 130°F. MAXIMUM
TEMPERATURE RATING FOR CLASS I, DIVISION 2, GROUPS A,B,C,D.
OPERATING TEMPERATURE CODE T3B
Friedrich Air Conditioning Co. | P.O. Box 1540 | San Antonio, TX 78295-1540 | (800) 541-6645 | fax (210) 357-4480 | www.friedrich.com
HG-08