Carrier T 298 User Manual

Transport Air Conditioning  
R
2P  
1
BLK  
BLU  
BRN  
WHT  
2
GRN/YEL  
F
WHT  
C
H
EVAP.  
RED RED  
BLU  
WHT  
R
YEL  
1
2
C
PTC  
BLU  
S
SERVICE MANUAL  
for  
MODEL AirV  
Rooftop Air Conditioning Systems  
T--298 Rev D  
SAFETY SUMMARY  
GENERAL SAFETY NOTICES  
The following general safety notices supplement the specific warnings and cautions appearing elsewhere in  
this manual. They are recommended precautions that must be understood and applied during operation and  
maintenance of the equipment covered herein. The general safety notices are presented in the following three  
sections labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific  
warnings and cautions appearing elsewhere in the manual follows the general safety notices.  
FIRST AID  
An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention  
immediately.  
OPERATING PRECAUTIONS  
Always wear safety glasses.  
Keep hands clear of the evaporator blower and condenser fan.  
No work should be performed on the unit until all circuit breakers and start--stop switches are turned off, and  
power supply is disconnected.  
Always work in pairs. Never work alone.  
In case of severe vibration or unusual noise, stop the unit and investigate.  
MAINTENANCE PRECAUTIONS  
Beware of unannounced starting of the evaporator blower & condenser fan. Do not remove the ceiling grill  
assembly or the upper unit cover assembly before turning the power off, and disconnecting the power supply.  
Before disconnecting, discharge capacitors by shorting across the capacitors terminals. (See Paragraph  
3.5.8)  
When disassembling wiring, use numbered stickers to identify wire leads and terminals. This aids in quick,  
accurate reassembly.  
Be sure power is turned off before working on motors, controllers, or electrical control switches. Tag any circuit  
breakers and power supply to prevent accidental energizing of circuits.  
Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires.  
Problems with the system should be diagnosed and any necessary repairs must be performed by qualified  
service personnel.  
In case of electrical fire, open circuit switch and extinguish with CO2 (never use water).  
Use dry nitrogen to pressurize the system for leak checking. Be careful not to exceed 150 psig test pressure in  
the hermetic compressor.  
Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury.  
Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when  
brazing, and keep brazing cloth and fire extinguisher handy for emergency use.  
Disconnect power to the AirV unit before checking the capacitor.  
T-298  
Safety-- i  
SPECIFIC WARNING AND CAUTION STATEMENTS  
The statements listed below are applicable to the refrigeration unit and appear elsewhere in this manual.  
These recommended precautions must be understood and applied during operation and maintenance of the  
equipment covered herein.  
SPECIFIC WARNINGS AND CAUTIONS  
WARNING  
Be sure to observe warnings listed in the safety summary in the front of this manual before  
performing maintenance on the AirV system  
WARNING  
Before working on the unit be sure to first disconnect all electric power to the unitto avoid the  
possibility of electrical shock and personal injury. Before disconnecting, discharge capaci-  
tors by shorting across the capacitors terminals (Refer to paragraph 3.5.8)  
WARNING  
Shield coils with cardboard to protect hands against injury from sharp metal edges when re-  
moving compressor and other components.  
WARNING  
Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise ex-  
treme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency  
use.  
WARNING  
Disconnect power to the AirV unit before checking the capacitor.  
WARNING  
Do not touch the metal of the screwdriver when discharging the capacitor. You could receive  
a shock.  
WARNING  
Before installing thermostat, turn off all power to unit. There may be more than one power  
disconnect. Electrical shock can cause personal injury or death.  
CAUTION  
Do not use carbon tetrachloride, solvents, or waxes containing solvents to clean plastic sec-  
tions.  
T--298  
Safety-- ii  
CAUTION  
Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal  
injury.  
CAUTION  
The change from Fahrenheit to Celsius will be permanent. It cannot be changed back to Fahr-  
enheit.  
CAUTION  
When re--assembling, ensure the battery springs are correctly placed in the battery spring  
holders.  
CAUTION  
Improper wiring or installation may damage thermostat. Wiring must conform to local and  
national electrical codes.  
T-298  
Safety--iii  
TABLE OF CONTENTS  
PARAGRAPH NUMBER  
Page  
1-1  
1-1  
1-1  
1-1  
1-9  
1-9  
1-9  
1-9  
1-9  
1-9  
1-9  
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.2 SERIAL NUMBER IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.3 DESIGN CHANGE DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.4 AirV SYSTEM COMPONENT SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.4.1 Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.4.2 Compressor - 115 Volts, 60 Cycles, 1 Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.4.3 Compressor - 220 Volts, 50 Cycles, 1 Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.4.4 Thermostat Range (All Free Blow Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.5 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.6 REFRIGERANT CYCLE-STANDARD SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1.7 REFRIGERANT CYCLE - HEAT PUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10  
1.7.1 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10  
1.7.2 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.1 NO POWER TO UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.2 DUCTED UNIT WILL NOT OPERATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.3 DUCTED UNIT WILL NOT COOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.4 COMPRESSOR POWER SUPPLY OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.5 COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY . . . . . . . . . . . . . . . . . . . .  
2.6 CYCLES ON COMPRESSOR OVERLOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.7 INSUFFICIENT COOLING, COOLING AIR NOT ADEQUATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.8 CONDENSER AIR NOT ADEQUATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.9 INSUFFICIENT COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.10 COMPRESSOR FLOODING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.11 HEATER CYCLES ON LIMIT SWITCH (HEAT/ COOL VERSION ONLY) . . . . . . . . . . . . . . . . . . . . .  
2.12 AIR SWEEP NOT WORKING (FREE BLOW VERSION ONLY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.13 WATER LEAKAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.14 INADEQUATE HEAT (FREE-BLOW HEAT ONLY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2.15 INADEQUATE HEAT (HEAT-PUMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Clearing Diagnostic Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SERVICE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.1 PREVENTATIVE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.2 SERVICE - GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3 CEILING UNIT - FREE BLOW SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3.1 Filter Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3.2 Ceiling Grill Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3.3 Ceiling Panel Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3.4 Master Control Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3.5 Air Sweep Switch Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3.6 Indoor Thermostat Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3.7 Air Sweep Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.3.8 Heat Strip Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2-1  
2-1  
2-1  
2-1  
2-1  
2-1  
2-2  
2-2  
2-2  
2-2  
2-2  
2-2  
2-2  
2-2  
2-3  
2-3  
2-3  
3-1  
3-1  
3-1  
3-1  
3-1  
3-1  
3-2  
3-2  
3-2  
3-3  
3-3  
3-3  
T--298  
i
TABLE OF CONTENTS - Continued  
3.4 CEILING UNIT - DUCTED SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.4.1 Filter Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.4.2 Ceiling Grill Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.4.3 Control Box Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.4.4 Main PCB Board Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.4.5 PCB Display Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.4.6 Fuse Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5 SERVICE - UPPER UNIT - STANDARD, HC & HP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.1 Exterior Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.2 Compressor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.3 Control Box Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.4 Upper Scroll Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.5 Motor Assembly and Condenser Fan Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.6 Evaporator Blower Wheel Adjustment or Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.7 Air Handling System Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.8 Capacitor Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.9 Capacitor Testing and Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.5.10 Positive Temperature Coefficient Thermister (PTC) (Start Thermistor) Troubleshooting . . . . .  
3.5.11 Line Voltage - 10% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3-4  
3-4  
3-4  
3-4  
3-5  
3-5  
3-5  
3-5  
3-5  
3-6  
3-6  
3-7  
3-7  
3-8  
3-8  
3-9  
3-9  
3-9  
3-9  
3.6 SERVICE - UPPER UNIT - LOW PROFILE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10  
3.6.1 Exterior Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10  
3.6.2 Upper Scroll Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10  
3.6.3 Condenser Fan Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11  
3.6.4 Condenser Motor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12  
3.6.5 Evaporator Motor/Blower Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12  
3.6.6 Compressor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13  
3.6.7 Capacitor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13  
3.6.8 Remote Control (Fahrenheit to Celsius) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13  
3.7 THERMOSTAT INSTALLATION AND START-UP INSTRUCTIONS (WALL MOUNTED) . . . . . . . . 3-15  
3.7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.7.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.7.3 Thermostat Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.7.4 Install Thermostat - 12VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.8 LCD DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.8.1 Cool Only Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.8.2 Heat/Cool Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.9 SET THERMOSTAT CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.9.1 Enter Configuration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15  
3.10 CHECK THERMOSTAT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16  
3.10.1 Fan Operation (Cool Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16  
3.10.2 Fan Operation (Heat/Cool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16  
3.10.3 Cooling Operation (Cool Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16  
3.10.4 Cooling Operation (Heat/Cool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16  
3.10.5 Heating Operation (Heat/Cool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16  
T--298  
ii  
TABLE OF CONTENTS - Continued  
3.11 CHECK THERMOSTAT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16  
3.11.1 Temperature Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16  
3.11.2 Timeguard Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17  
3.11.3 Cycle Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17  
3.11.4 Minimum On Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17  
3.11.5 Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17  
WIRING SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
4-1  
4.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
4-1  
LIST OF FIGURES  
FIGURE NUMBER  
Page  
1-1  
1-3  
1-4  
1-5  
1-6  
1-7  
1-8  
1-9  
1-10  
1-11  
3-1  
3-2  
3-2  
3-2  
3-2  
3-3  
3-3  
3-3  
3-4  
3-4  
3-4  
3-5  
3-5  
3-5  
3-6  
3-6  
3-6  
3-7  
3-7  
3-7  
3-7  
3-8  
3-8  
3-8  
3-9  
Figure 1-1 Model/Serial Number Plate (Typical) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-2 Roof Unit Component Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-3 Ceiling Unit Component Identification (Free-Blow) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-4 Component Identification - Low Profile - Upper Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-5 Component Listing-Ceiling Unit For Ducted Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-6 Ducted System Air Flow Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-7 Serial Number Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-8 Refrigerant Flow Schematic (Standard System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-9 Refrigerant Flow Schematic - Heat Pump - (Cool Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 1-10 Refrigerant Flow Schematic - Heat Pump - (Heat Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-1 Filter Removal - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-2 Ceiling Grill - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-3 Ceiling Panel Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-4 Ceiling Panel With Heat Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-5 Control Box Assembly - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-6 Indoor Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-7 Air sweep motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-8 Heat Strip Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-9 Filter Removal - Ducted Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-10 Ceiling Grill - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-11 Control Box & PCB Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-12 Control Box Assembly - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-13 Main/Display PCB’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-14 Cover Assembly - Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-15 Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-16 Control Box Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-17 Water Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-18 Upper Scroll Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-19 Motor Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-20 Spring Clamp Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-21 Motor Clip Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-22 Condenser Fan Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-23 Blower Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-24 Condenser With Motor Assembly & Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-25 Set-Up For Discharging a Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
T--298  
iii  
LIST OF FIGURES  
Figure 3-26 Cover Assembly - Low Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-27 Upper Scroll Assembly Locking Tabs (b.) & Screw Locations (c.) . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-28 Upper Scroll Assembly Keeper Tab Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-29 Upper Scroll & Control Box Cover Removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-30 Condenser Fan Assembly & Retaining Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-31 Condenser Fan Motor & Fan Assembly Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-32 Condenser Fan Motor & Fan Assembly Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-33 Condenser Motor Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-34 Evaporator Motor Locking Tabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-35 Evaporator Motor/Blower Assembly In Cradle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-36 Evaporator Blower Wheel (Flush With End Of Motor Shaft) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-37 Control Box Assembly With Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-38 Remote Control Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-39 Remote Control PCB (FR9 Location) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-40 Wall Thermostat Wiring Diagram - Cool Only Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3-41 Wall Thermostat Wiring Diagram - Heat/Cool Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-1 Upper Unit Schematic - Standard & HC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-2 Upper Unit Schematic - Low Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-3 Ceiling Unit Schematic - Cooling Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-4 Ceiling Unit Schematic - Heat/Cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-5 Ceiling Unit, Standard - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-6 Heat Pump - Upper Unit - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-7 Heat Pump - Ceiling Unit - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-8 Heat Pump - Upper Unit - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4-9 Heat Pump - Ceiling Unit - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
LIST OF TABLES  
3-10  
3-10  
3-10  
3-11  
3-11  
3-11  
3-11  
3-12  
3-12  
3-12  
3-13  
3-13  
3-14  
3-14  
3-17  
3-18  
4-1  
4-1  
4-2  
4-2  
4-2  
4-3  
4-3  
4-4  
4-4  
TABLE NUMBER  
Page  
1-2  
Table 1-1 Model Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 1-2 Additional Support Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 2-1 System Self-diagnostics Function (Ducted Remote) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1-3  
2-4  
T--298  
iv  
SECTION 1  
DESCRIPTION  
1.1 INTRODUCTION  
MODEL No.  
Part No.  
VOLTS  
ph  
68RV14102A  
This manual contains service instructions and electrical  
data for the AirV, Carrier Transport Air Conditioning’s  
Recreational Vehicle air conditioning unit.  
99--00468--01  
115  
V
The AirV units are two piece systems, consisting of the  
Upper Unit and the Ceiling unit. The Upper Unit contains  
the refrigeration system while the Ceiling Unit contains  
the controls and vents. The Ceiling Units are available in  
a free--blow or ducted configuration.  
hz  
13,500  
1
60  
Btu/h  
W
Carrier  
Air Conditioning  
C
Division of Carrier Corporation  
CAPACITY  
3,955  
13.5  
A
AMPS  
DATE OF Mfg  
SERIAL No.  
USE 20 AMP  
TIME DELAY FUSE OR  
CIRCUIT BREAKER  
The free--blow units (see Figure 1-2) deliver air to the  
vehicle by means of front and rear end vents and one  
downward vent (air shower). The vents may all be  
opened or closed to direct air as desired. The front and  
rear vents are fitted with motorized dampers that  
oscillates to produce an “air--sweep” effect. These units  
may be fitted with optional electric heat.  
05/03  
1303Y12345  
DESIGN PSIG HIGH 350 LO 150  
oz  
15.9  
R--22  
kg  
0.45  
The ducted units (see Figure 1-5 and Figure 1-6) deliver  
air through ducting built in the vehicle ceiling. These  
units are fitted with a 12 VDC microprocessor control  
system, a display panel (PCB display) and a remote  
controller. These units may be wired to provide  
thermostatic control of the vehicle furnace.  
RLA  
12.5  
COMPRESSOR  
FAN MOTOR  
FLA  
2.58  
99--00469--01  
USE CEILING ASSY/ANY  
Figure 1-1 Model/Serial Number Plate (Typical)  
1.3 DESIGN CHANGE DESCRIPTIONS  
Carrier’s AirV air conditioning models include cooling  
only units, heating/cooling units, and heat pump units.  
The cooling only units are available with free blow or  
ducted air delivery. Cooling units with heat strips are  
available for free blow only.  
The following list provides a description of changes in  
design and serial number breaks for those changes.  
Operation of the AirV units is controlled automatically by  
the temperature controller (thermostat), which  
maintains the vehicle’s interior temperature at the  
desired set point. Free Blow, cool--only units are  
available with a wall mounted thermostat.  
1400Y A diode was added to the Ducted Ceiling  
assembly control board to stop DC ripple from the  
converters,  
2900Y Cover screw coating was changed in order to  
eliminate corrosion.  
Table 1-1 lists model numbers and descriptions of the  
AirV units, and Table 1-2 lists additional support  
manuals that are available.  
3400Y The plastic shroud was modified to improve  
drainage.  
5100Y A new compressor and capacitor is introduced,  
improving stability and increasing capacity.  
1.2 SERIAL NUMBER IDENTIFICATION  
1201Y The temperature sensor was moved to the grill  
Separate part numbers and serial numbers areprovided  
for the upper and lower unit assemblies The numbers  
may be found on a plate readable from inside the  
vehicle, See Figure 1-7.  
to improve temperature sensing during furnace mode,  
2501Y The dual air sweep was added.  
4501Y A switch was added to skip compressor  
malfunction test.  
The first two numbers of the serial number, see  
Figure 3-22, is the week the unit was manufactured. For  
example, 01 would designate the first week of the year  
and 52 would designate the last week of the year.  
4601Y Change in material was made in order to  
strengthen the fan propeller.  
4901Y The mounting bolt lengths were increased 3/4  
inch.  
The third and fourth numbers designate the year in  
which the unit was manufactured. For example, 99  
would represent the year 1999, 00 the year 2000, and  
so on.  
4901Y The polar white ducted ceiling color was cut--in.  
0703Y & 1903Y New style PCB -- Cool Mode -- Control  
& Power Assembly (Fans shut off in auto mode).  
The letter Y and all the numbers after it designates the  
unit serial number. Example: Y43210  
0803Y & 2603Y New style PCB -- Heat Pump -- Control  
& Power Assembly (Fans shut off in auto mode).  
A serial number of 1303Y12345 designates that the unit  
was manufactured the 13th week of 2003 and the serial  
number is Y12345.  
4204Y Minimum furnace setpoint lowered from 63°F to  
45°F.  
1-1  
T--298  
Table 1-1. Model Chart  
UPPER UNIT (ROOF)  
Model Number  
Part Number  
Voltage  
115/1/60  
115/1/60  
220/1/50  
220/1/50  
115/1/60  
115/1/60  
Amps  
12.8  
Color  
White  
Ivory  
99--00468--00  
99--00468--01  
99--00468--02  
99--00468--03  
99--00468--08  
99--00468--09  
115V Standard System  
68RV14102A  
12.8  
White  
Ivory  
220V Standard System  
68RV11302A  
5.3 Cool  
6.7 Heat  
14.5  
14.5  
White  
Ivory  
High Capacity  
68RV15102A  
99--00468--04  
(Free Blow)  
12.7 Cool  
10.9 Heat  
115/1/60  
115/1/60  
115/1/60  
115/1/60  
115/1/60  
115/1/60  
White  
Ivory  
99--00468--05  
(Free Blow)  
12.7 Cool  
10.9 Heat  
Heat Pump  
Systems  
68RV14112A  
99--00468--06  
(Ducted)  
12.7 Cool  
10.9 Heat  
White  
Ivory  
99--00468--07  
(Ducted)  
12.7 Cool  
10.9 Heat  
LOW PROFILE  
68RV15103A  
99--00468--10  
(Free Blow -- High Capacity)  
15.1 Cool  
13.8 Heat  
White  
White  
LOW PROFILE  
68RV14103A  
99--00468--12  
(Free Blow -- Standard)  
15.0 Cool  
13.7 Heat  
CEILING UNIT  
Model Number  
Part Number  
Voltage  
115/1/60  
Color  
White  
Ivory  
Options  
Interface  
99--00469--00  
99--00469--01  
99--00469--02  
99--00469--03  
99--00469--06  
99--00469--04  
99--00469--05  
99--00469--08  
99--00469--10  
99--00469--11  
99--00469--12  
99--00469--13  
99--00469--23  
99--00469--24  
99--00469--25  
99--00469--26  
Cool Only  
Cool Only  
Heat/Cool  
Heat/Cool  
Cool Only  
Cool Only  
Cool Only  
Heat/Cool  
Cool Only  
Heat Pump  
Heat Pump  
Heat Pump  
Cool Only  
Cool Only  
Heat/Cool  
Heat/Cool  
Free Blow  
Free Blow  
Free Blow  
Free Blow  
Ducted  
68RV0010AA  
115/1/60  
115/1/60  
White  
Ivory  
68RV0010BA  
68RV0010KA  
68RV0030AA  
115/1/60  
115/1/60 (12VDC)  
220/1/50  
White  
White  
Ivory  
Free Blow  
Free Blow  
Free Blow  
Ducted  
220/1/50  
68RV0030BA  
68RV0030KA  
220/1/50  
White  
White  
White  
Ivory  
220/1/50  
115/1/60  
Free Blow  
Free Blow  
Ducted  
68RV0012CA  
115/1/60  
68RV0011LA  
68RV0010AB  
68RV0010AB  
68RV0010BB  
68RV0010BB  
115/1/60 (12VDC)  
115/1/60  
White  
White  
Ivory  
Free Blow  
Free Blow  
Free Blow  
Free Blow  
115/1/60  
115/1/60  
White  
Ivory  
115/1/60  
Ducted  
68RV0040MA  
68RV0010DB  
99--00469--22  
99--00469--29  
115/1/60  
115/1/60  
White  
White  
Cool Only  
Cool Only  
Wall Thermostat  
Free Blow  
Wall Thermostat  
1-2  
T--298  
Table 1-2 Additional Support Manuals  
MANUAL--FORM NO.  
EQUIPMENT COVERED  
TYPE OF MANUAL (For) PART NO.  
99--00469--00  
99--00469--01  
99--00469--02  
99--00469--03  
71LC6A54310  
AirV 115 Volts--Free Blow (Cool Only)  
Owner’s Guide  
71LH6A54070  
71LD6A54070  
71LH6A54070  
AirV 115 Volts--Free Blow (Heat--Cool)  
AirV 115 Volts--Ducted (Cool Only)  
AirV 220 Volts--Free Blow (Heat--Cool)  
Owner’s Guide  
Owner’s Guide  
Owner’s Guide  
99--00469--06  
99--00469--08  
99--00469--09  
99--00469--11  
99--00469--12  
71RQ6A5401A  
AirV 115 Volts--Free Blow (Heat Pump)  
Owner’s Guide  
99--00469--13  
99--00469--22  
71DQ6A5401A  
71DW6A54070  
AirV 115 Volts--Ducted (Heat Pump)  
Owner’s Guide  
Owner’s Guide  
AirV 115 Volts--Ducted Wired Thermostat  
99--00469--23  
99--00469--24  
99--00469--25  
99--00469--26  
71LC6A54310  
71LH6A54070  
AirV 115 Volts--Free Blow (Cool Only)  
AirV 115 Volts--Free Blow (Heat--Cool)  
Owner’s Guide  
Owner’s Guide  
99--00469--29  
ALL  
71RW6A54310  
T--298PL  
AirV 115 Volts--Free Blow Wired Thermostat  
Owner’s Guide  
Service Parts  
AirV  
62--50455--00  
Basic refrigeration  
Service Training  
ALL  
1
2
3
4
5
1. Cover  
2. Condenser  
3. Evaporator  
4. Compressor  
5. Base Pan  
Figure 1-2 Roof Unit Component Identification  
1-3  
T--298  
1
2
3
4
1. Ceiling Panel Assembly  
2. Control Box Cover  
3. Control Assembly  
4. Ceiling Grill Assembly  
Figure 1-3 Ceiling Unit Component Identification (Free--Blow)  
1-4  
T--298  
1
2
3
4
5
9
6
7
8
10  
11  
1. Cover Assembly  
7. Condenser Coil  
2. Scroll Assembly -- Upper  
3. Condenser Fan  
8. Scroll Assembly -- Lower  
9. Evaporator Coil  
4. Condenser Motor  
5. Evaporator Motor  
6. Evaporator Blower Wheel  
10. Compressor  
11. Base Pan Assembly  
See Figure 1-3 for Ceiling Package (Free--Blow)  
Figure 1-4 Component Identification -- Low Profile -- Upper Unit  
1-5  
T--298  
1
2
3
12  
11  
10  
4
5
6
7
8
9
1. Telescoping Divider (3 different sizes available)  
2. Divider Assembly  
7. Remote Control Assembly  
8. Remote Control Bracket Assembly  
9. Filter Assemblies (2)  
10. PCB Cover  
11. PCB Main Assembly  
12. PCB Display  
3. Frame Panel, Insulation Assembly  
4. Control Box Assembly  
5. Control Box Cover  
6. Suction Packing Assembly  
Figure 1-5 Component Listing--Ceiling Unit For Ducted Systems  
1-6  
T--298  
1
2
3
4
5
SCHEMATIC VIEW  
1
SUPPLY AIR  
5
2
1
3
SUPPLY AIR  
4
RETURN AIR  
INSTALLED VIEW  
1. Vehicle Duct System (Connection)  
2. Telescoping Divider (3 different sizes available)  
3. Return Air Suction Area  
4. Control Box Assembly  
5. Supply Air Discharge Area  
Figure 1-6 Ducted System Air Flow Arrangement  
1-7  
T--298  
Serial number  
of Upper Unit  
Upper Unit  
Serial Number  
of Ceiling Unit  
Ceiling Unit  
(Cover Removed)  
Free Blow Type  
Serial Number of  
Ceiling Unit  
(Side of Control Box)  
Ceiling Assembly Frame  
Bottom of  
Upper Unit  
Serial Number  
of Upper Unit  
Bottom View After Installation  
(With Grille Removed)  
Ducted Type  
Figure 1-7 Serial Number Locations  
1-8  
T--298  
1.4 AirV SYSTEM COMPONENT SPECIFI-  
CATIONS  
d. Fully Loaded Amps -- High Capacity  
Cooling -- Approx. 14.5 AMPS  
Heating -- Approx. 11 AMPS  
1.4.1 Refrigerant Charge  
Standard -- High Capacity -- Heat Pump  
R--22 -- 15.9 Ounces  
e. Fully Loaded Amps -- Low Profile  
Cooling -- Approx. 14.1 AMPS  
Heating -- Approx. 13.8 AMPS  
Low Profile (All)  
f. Fully Loaded Amps -- Heat Pump  
Cooling -- Approx. 12.8 AMPS  
Heating -- Approx. 11 AMPS  
R--22 -- 16.9 Ounces  
1.4.2 Compressor -- 115 Volts, 60 Cycles, 1 Phase  
1.4.3 Compressor -- 220 Volts, 50 Cycles, 1 Phase  
a. Locked Rotor Amps  
a. Locked Rotor Amps -- Standard -- High  
Capacity -- Heat Pump  
64.5 AMPS6  
23.6 AMPS  
b. Locked Rotor Amps -- Low Profile  
High Capacity  
1.4.4 Thermostat Range (All Free Blow Units)  
61° F (16° C) to 89° F (32° C)  
59.0 AMPS  
1.5 START--UP  
c. Fully Loaded Amps -- Standard  
Cooling -- Approximate 12.8 AMPS  
Heating -- N/A  
Refer to operating instructions in Owners Guide (see  
Table 1-2) packaged with the vehicle system.  
CAPILLARY  
TUBE  
DISCHARGE  
LIQUID  
EVAPORATOR  
SUCTION  
ACCUMULATOR  
STRAINER  
CONDENSER  
COMPRESSOR  
Figure 1-8 Refrigerant Flow Schematic (Standard System)  
1.6 REFRIGERANT CYCLE--STANDARD SYSTEM  
The evaporator blower (fan) pulls vehicle air through the  
filters, which remove particulate matter, and then pass  
the cleaned air through the evaporator coil.  
The cooling cycle is energized when the thermostat,  
located on the ceiling unit, calls for cooling. The main  
components of the system are the compressor,  
air-cooled condenser coil, strainer, capillary tube,  
evaporator coil and accumulator.  
The low pressure, low temperature liquid that flows into  
the evaporator coil tubes is colder than the air that is  
circulated over the tubes. Heat transfer is established  
from the vehicle air (flowing over the tubes) to the  
refrigerant (flowing inside the tubes). The evaporator  
coil tubes have aluminum fins to increase heat transfer  
from the air to the refrigerant; therefore the cooler air is  
circulated to the interior of the vehicle.  
The compressor raises the pressure and the  
temperature of the refrigerant and forces it through the  
discharge line into the condenser coil. (See Figure 1-8.)  
The condenser fan circulates surrounding air (which is  
at a temperature lower than the refrigerant) over the  
outside of the coil tubes. Heat transfer is established  
from the refrigerant (inside the tubes) to the air (flowing  
over the tubes). The tubes have fins designed to  
improve the transfer of heat from the refrigerant gas to  
the air. This removal of heat causes the refrigerant to  
liquefy, thus liquid refrigerant leaves the coil and flows  
through a strainer to the capillary tube. The strainer  
removes any impurities within the refrigerant system.  
The transfer of heat from the air to the low temperature  
liquid refrigerant in the indoor coil causes the liquid to  
vaporize. This low temperature, low pressure vapor  
passes into the accumulator. The accumulator is  
designed with the inlet tube delivering refrigerant to the  
bottom of the tank and the outlet tube taking refrigerant  
form the top of the tank. This arrangement ensures that  
only vapor refrigerant is returned to the compressor,  
where the cycle repeats.  
The capillary tube meters the flow of liquid refrigerant to  
the evaporator coil. As the refrigerant flows through the  
capillary tube, there is a reduction in pressure and  
temperature.  
When ventilation only is selected, the indoor fan  
functions to circulate air throughout the vehicle. The  
refrigerant cycle will remain off.  
1-9  
T--298  
1.7 REFRIGERANT CYCLE -- HEAT PUMP  
DISCHARGE  
LIQUID  
CAPILLARY  
TUBE  
INDOOR COIL  
SUCTION  
STRAINER  
REVERSING VALVE  
ACCUMULATOR  
COMPRESSOR  
OUTDOOR COIL  
Figure 1-9 Refrigerant Flow Schematic -- Heat Pump -- (Cool Mode)  
1.7.1 Cooling  
capillary tube, there is a reduction in pressure and  
temperature.  
The cooling cycle is energized when the thermostat,  
located in the ceiling unit, calls for cooling The system  
controls are positioned for “normal” refrigerant flow, with  
the compressor discharge delivered to the outdoor coil  
and liquid delivered to the indoor coil. (See Figure 1-9.)  
The indoor blower (fan) pulls inside air through the  
filters, which remove particulate matter, and then pass  
the cleaned air through the indoor coil.  
The low pressure, low temperature liquid that flows into  
the indoor coil tubes is colder than the air that is  
circulated over the tubes. Heat transfer is established  
from the indoor air (flowing over the tubes) to the  
refrigerant (flowing inside the tubes). The indoor coil  
tubes have aluminum fins to increase heat transfer from  
the air to the refrigerant; therefore the cooler air is  
circulated to the interior of the vehicle.  
The main components of the system are the  
compressor, reversing valve, air-cooled outdoor coil,  
strainer, capillary tube, indoor coil, and the accumulator.  
The compressor raises the pressure and the  
temperature of the refrigerant and forces it through the  
discharge line and reversing valve into the outdoor coil.  
The outdoor fan circulates surrounding air (which is at a  
temperature lower than the refrigerant) over the outside  
of the coil tubes. Heat transfer is established from the  
refrigerant (inside the tubes) to the outdoor air (flowing  
over the tubes). The tubes have fins designed to  
improve the transfer of heat from the refrigerant gas to  
the air; this removal of heat causes the refrigerant to  
liquefy, thus liquid refrigerant leaves the coil and flows  
through the strainer to the capillary tube. The strainer  
removes any impurities within the refrigerant system.  
The transfer of heat from the air to the low temperature  
liquid refrigerant in the indoor coil causes the liquid to  
vaporize. This low temperature, low pressure vapor  
passes into the accumulator. The accumulator is  
designed with the inlet tube delivering refrigerant to the  
bottom of the tank and the outlet tube taking refrigerant  
form the top of the tank. This arrangement ensures that  
only vapor refrigerant is returned to the compressor,  
where the cycle repeats.  
When ventilation only is selected, the indoor fan  
functions to circulate air throughout the vehicle. The  
refrigerant cycle will remain off.  
The capillary tube meters the flow of liquid refrigerant to  
the indoor coil. As the refrigerant flows through the  
1-10  
T--298  
CAPILLARY  
TUBE  
DISCHARGE  
LIQUID  
INDOOR COIL  
SUCTION  
STRAINER  
REVERSING VALVE  
ACCUMULATOR  
COMPRESSOR  
OUTDOOR COIL  
Figure 1-10 Refrigerant Flow Schematic -- Heat Pump -- (Heat Mode)  
1.7.2 Heating  
outdoor coil. The strainer removes any impurities within  
the refrigerant system.  
The heating cycle is energized when the thermostat,  
located in the ceiling unit, calls for heat The system  
controls are positioned for “reverse” refrigerant flow,  
with the compressor discharge delivered to the indoor  
coil and liquid delivered to the outdoor coil. (See  
Figure 1-10.)  
The capillary tube meters the flow of liquid refrigerant to  
the outdoor coil. As the refrigerant flows through the  
capillary tube, there is a reduction in pressure and  
temperature.  
The low pressure, low temperature liquid that flows into  
the outdoor coil tubes is colder than the outdoor air that  
is circulated over the tubes. Heat transfer is established  
from the outdoor air (flowing over the tubes) to the  
refrigerant (flowing inside the tubes). The outdoor coil  
tubes have aluminum fins to increase heat transfer from  
the air to the refrigerant.  
The main components of the system are the  
compressor, reversing valve, indoor coil, capillary tube,  
strainer, air-cooled outdoor coil, and the accumulator.  
The compressor raises the pressure and the  
temperature of the refrigerant and forces it through the  
discharge line and reversing valve into the indoor coil.  
The transfer of heat from the air to the low temperature  
liquid refrigerant in the outdoor coil causes the liquid to  
vaporize. This low temperature, low pressure vapor  
passes into the accumulator. The accumulator is  
designed with the inlet tube delivering refrigerant to the  
bottom of the tank and the outlet tube taking refrigerant  
form the top of the tank. This arrangement ensures that  
only vapor refrigerant is returned to the compressor,  
where the cycle repeats.  
The indoor blower (fan) pulls inside air through the  
filters, which remove particulate matter, and then pass  
the cleaned air through the indoor coil.  
The vehicle air (which is at a temperature lower than the  
refrigerant) passes over the outside of the coil tubes.  
Heat transfer is established from the refrigerant (inside  
the tubes) to the vehicle air (flowing over the tubes). The  
tubes have fins designed to improve the transfer of heat  
from the refrigerant gas to the air; this removal of heat  
causes the refrigerant to liquefy, thus liquid refrigerant  
leaves the coil and flows through the strainer to the  
When ventilation only is selected, the indoor fan  
functions to circulate air throughout the vehicle. The  
refrigerant cycle will remain off.  
1-11  
T--298  
SECTION 2  
TROUBLESHOOTING  
For ducted units, the green operation indicator LED (SeeFigure 3-9) will flash if there is a problem.  
Refer to Table 2--1 for diagnostic information.  
SYMPTOM AND PROBABLE CAUSE  
2.1 NO POWER TO UNIT  
PROBABLE REMEDY  
1. Master switch off  
1. Reset master switch  
2. Open circuit breaker  
2. Reset circuit breaker  
3. Replace wiring  
3. Defective wiring  
4. Loose electrical connections  
5. Faulty switches, thermostat, or fan  
6. 12 VDC not connected (Ducted System)  
7. 12 VDC in--line fuse open (Ducted)  
2.2 DUCTED UNIT WILL NOT OPERATE  
1. Display not illuminated  
4. Tighten connections  
5. Replace defective components  
6. Connect to 12 VDC power source  
7. Replace fuse  
1. Check 12 Volt DC in--line fuse  
2. Check 115 Volt AC Connections  
2. Display illuminated  
2.3 DUCTED UNIT WILL NOT COOL  
1. Green LED light flashes 5 times  
1. Check 115 volt AC power source  
Momentarily disconnect 12 VDC power source  
Disable compressor malfunction test switch.  
Check AMP draw.  
Check T  
2. Unit cools for a few moments then stops cooling  
2. Remove grill, verify evaporator coil probe is  
inserted into coil.  
Check AMP draw.  
Check T  
Replace unit  
2.4 COMPRESSOR POWER SUPPLY OPEN  
1. Loose leads at compressor terminals  
2. Defective motor overload switch  
3. Defective capacitor  
4. Open compressor windings  
5. Seized compressor  
1. Tighten leads  
2. Replace switch  
3. Replace capacitor -- Refer to Paragraph 3.5.8  
4. Replace compressor  
5. Replace compressor  
6. Capacitor incorrectly wired  
6. Verify capacitor wiring (Refer to wiring diagram)  
2.5 COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY  
1. Loose lead at fan motor  
1. Tighten lead.  
2. Defective or burned out motor  
3. Outdoor air restricted or recirculating  
2. Replace motor.  
3. Check for dirty condenser coil, proper clearance  
around unit, remove any obstructions.  
4. Overcharge or noncondensables in system  
5. Restricted discharge line  
4. Check AMP draw  
5. Check for obstruction in line.  
Check T.  
Replace unit.  
6. Defective motor overload switch  
6. Replace switch.  
2-1  
T--298  
SYSTEM AND PROBABLE CAUSE  
2.6 CYCLES ON COMPRESSOR OVERLOAD  
1. Defective run capacitor  
PROBABLE REMEDY  
1. Replace capacitor -- Refer to Paragraph 3.5.8  
2. Replace unit.  
2. Defective compressor bearings or valves  
3. Greatly restricted evaporator air, iced evaporator  
coil.  
3. Defrost evaporator coil.  
4. Low refrigerant charge  
5. Evaporator capillary restricted  
6. Liquid line restricted  
7. Compressor hot  
4. Replace unit.  
5. Replace unit.  
6. Replace unit.  
7. Verify refrigerant charge.  
Check AMP draw.  
Check T.  
8. Weak or inconsistent line power  
8. Check line voltage at time of compressor start--up.  
2.7 INSUFFICIENT COOLING, COOLING AIR NOT ADEQUATE  
1. Dirty evaporator coil  
1. Clean as required.  
2. Iced evaporator coil, slightly low refrigerant charge  
3. Improper fan operation  
4. Defective fan motor  
2. Defrost or Recharge.  
3. Verify fan rotation (Refer to wiring diagram)  
4. Replace fan motor.  
5. Return air filter is dirty  
5. Remove and clean filters (Refer to paragraphs 3.3.1  
& 3.4.1)  
2.8 CONDENSER AIR NOT ADEQUATE  
1. Outside Air Restricted  
2. Dirty coil  
1. Check for obstruction at coil. Remedy as required.  
2. Clean coil.  
3. Defective fan motor  
3. Replace fan motor.  
2.9 INSUFFICIENT COOLING  
1. Unit undersized  
2. Capillary restricted  
1. Re--evaluate unit for proper capacity.  
2. Check AMP draw.  
Check T.  
Replace unit.  
2.10 COMPRESSOR FLOODING  
1. Unit overcharged  
1. Check AMP draw.  
Check T.  
Replace unit.  
2. Low evaporator airflow  
2. Clean filter and/or evaporator coil.  
3. Defective electrical connections  
3. Check connections per wiring diagram and tighten  
any loose connections.  
2.11 HEATER CYCLES ON LIMIT SWITCH (HEAT/ COOL VERSION ONLY)  
1. Dirty filter  
1. Clean or replace filter.  
2. Blocked evaporator air inlet (indoor)  
3. Low airflow due to fan motor speed  
2. Remove blockage.  
3. Check fan motor. Repair or replace as necessary.  
2.12 AIR SWEEP NOT WORKING (FREE BLOW VERSION ONLY)  
1. Ceiling grill not properly aligned  
2. Linkage in upper control box stuck  
3. Air sweep motor failure  
1. Align ceiling grill.  
2. Align and lubricate linkage.  
3. Replace motor.  
2.13 WATER LEAKAGE  
1. Water dripping from ceiling unit.  
1. Verify vehicle is level  
Tighten unit mounting bolts evenly or replace unit  
gasket.  
2-2  
T--298  
SYSTEM AND PROBABLE CAUSE  
2.14 INADEQUATE HEAT (FREE--BLOW HEAT ONLY)  
1. No heat from heat strip.  
PROBABLE REMEDY  
1. Verify AMP draw . ( 13.8 AMP)  
Verify resistance through heating element. (9 OHM)  
Check bi--metal switch. If open, replace switch.  
2.15 INADEQUATE HEAT (HEAT--PUMP)  
NOTE: Allow unit to operate 15 minutes after switch-  
ing from cooling mode.  
1. Reversing valve not operating  
1. Check for 115 volts at reversing valve coil  
Check for reversing valve restriction  
Verify compressor operation  
2. Outdoor coil icing.  
2. Check outdoor coil sensor  
Clearing Diagnostic Alarms  
When a repair has been accomplished due to a corresponding alarm, the alarm must be cleared. This is done by  
disconnecting the 12 VDC power to the ducted ceiling assembly for one or two seconds. Once the 12 VDC power is  
reconnected, the alarm should have been cleared.  
2-3  
T--298  
Table 2--1 System Self--diagnostics Function (Ducted Remote)  
Flashes  
Error Codes  
Error Contents  
Display Pattern  
Allowed Modes  
(Priority)  
(Malfunction)  
1
2
3
4
5
6
ROOM AIR THERM-  
ISTOR FAILURE  
FAN Mode  
2
0.5 sec.  
(Twice)  
3sec  
3sec  
.
.
0.5 sec (3  
Times)  
3
4
5
6
1
INDOOR COIL  
THERMISTOR FAIL-  
URE  
FAN Mode  
FURNACE Mode  
3sec.  
3sec  
.
0.5 sec. (4  
Times)  
OUTDOOR COIL  
THERMISTOR  
FAILURE  
FAN Mode  
FURNACE Mode  
3sec.  
3sec  
.
COMPRESSOR  
DRIVE  
MALFUNCTION  
FAN Mode  
FURNACE Mode  
0.5 sec. (5  
Times)  
3sec  
3sec  
.
.
REVERSING VALVE  
DRIVE MAL--  
FAN Mode  
FURNACE Mode  
0.5 sec.  
(6Times)  
FUNCTION  
3sec  
3sec  
.
.
DISCHARGE AIR  
THERMISTOR FAIL-  
URE  
FAN Mode  
FURNACE Mode  
0.5 sec.  
(Once)  
3sec  
.
3sec  
.
Continuous  
7
THERMISTOR  
WIRING WRONG  
(only in cooling  
test mode)  
FAN Mode  
0.5 sec. (Continu-  
ous)  
3sec  
.
NOTE:  
If more than two errors occur, the highest ranked code is displayed. If the highest ranked error is cleared, the  
next highest ranked error code is displayed.  
2-4  
T--298  
SECTION 3  
SERVICE AND MAINTENANCE  
3.1 PREVENTATIVE MAINTENANCE  
WARNING  
Cleaning--Clean evaporator coil and condenser coil.  
Hold flashlight behind coil to see if all spaces are clear.  
Dust accumulation obstructs or reduces airflow and  
results in loss of cooling capacity. Both coils may be  
vacuumed when dry. Coils may also be brushed with a  
stiff brush and then blown out with compressed air.  
Before working on the unit be sure to first  
disconnect all electric power to the unit to  
avoid the possibility of electrical shock and  
personal injury. Before disconnecting, dis-  
charge capacitors by shorting across the  
capacitors terminals (Refer to paragraph  
3.5.8)  
Thoroughly clean base pan, motors, fan wheels, and  
other components.  
Clean cover and ceiling grill. Mild detergents reduce  
electrostatic charges on plastic sections of the grill and  
are good cleaners.  
WARNING  
Shield coils with cardboard to protect  
hands against injury from sharp metal  
edges when removing compressor and oth-  
er components.  
CAUTION  
Do not use carbon tetrachloride, solvents,  
or waxes containing solvents to clean plas-  
tic sections.  
3.3 CEILING UNIT -- FREE BLOW SYSTEMS  
3.3.1 Filter Removal  
Painting--Paint any parts that show evidence of rust  
with a good rust--prevention paint.  
The filters (Figure 3-1) are located in the ceiling grill. To  
remove the filters, do the following:  
Wiring-- Check all wiring for deterioration and all  
electrical contacts for tightness or corrosion.  
a. Grasp the edge of the filter at recess in the end of the  
ceiling grill.  
Mounting--Make sure unit is secure on roof according  
to installation instructions provided in Owner’s Guide.  
Check fans to insure that they are correctly positioned in  
the center of the orifice, and tight on the shaft.  
b. Pull filter completely out of the filter slot.  
c. Vacuum filter or wash filter in luke--warm water.  
Shake off excess water and dry thoroughly.  
Leaks--Check any connections that show evidence of  
oil or leaks. When unit is properly installed (refer to  
Owner’s Guide) check gaskets for possible air leakage.  
d. Replace filter by sliding the filter into the filter slot in  
the ceiling grill until the filter frame is flush with the in-  
terior grill.  
Controls--Check unit to ensure all controls are  
functioning correctly and unit operation is normal.  
Vibrations can cause unwanted noise.  
Filters  
NOTE  
Check to ensure that piping is not vibrating  
against side of the unit.  
NOTE  
For proper cleaning and flushing, use a UL  
approved refrigerant recovery/recycling  
system.  
NOTE  
Figure 3-1 Filter Removal -- Free Blow  
Refrigerant removal must always include  
recovering the refrigerant, not allowing it to  
escape to the atmosphere.  
3.3.2 Ceiling Grill Removal  
To remove the ceiling grill (Figure 3-2) do the following:  
a. Before working on unit place the master switch in the  
OFF position and disconnect all electrical power.  
3.2 SERVICE -- GENERAL  
General Notes—These Service Instructions are  
provided to assist the trained and qualified Carrier  
service technician in repairing or replacing components  
of the AirV units.  
b. Remove 4 screws located on the ceiling grill, making  
sure to support the weight of the grill.  
c. Lower the ceiling grill from the ceiling panel.  
3-1  
T--298  
d. To replace the grill, place the grill up against the ceil-  
ing panel and align the screw holes in the grill with the  
ceiling panel.  
Heat Strip  
Connection  
e. Replace 4 screws.  
Heater Assembly  
Option  
Mounting  
Screws  
Figure 3-4 Ceiling Panel With Heat Option  
3.3.4 Master Control Switch  
To remove the master control switch, do the following:  
a. Remove ceiling grill. (Refer to paragraph 3.3.2.)  
b. Remove 5 screws that secure the control assembly  
(Item 2, Figure 1-3) to the control box cover.  
Figure 3-2 Ceiling Grill -- Free Blow  
3.3.3 Ceiling Panel Removal  
c. Remove the master control switch knob by grabbing  
the outside edge of the knob and pulling it off of the  
switch stem.  
To remove the ceiling panel (Figure 3-3) do the  
following:  
d. Remove 2 screws securing the master control switch  
to the control assembly.  
a. Remove the ceiling grill. (Refer to paragraph 3.3.2.)  
e. Carefully disconnect wires from the master control  
switch. Label wires to aid in reassembly.  
b. Remove 5 screws securing the duct plate to the ceil-  
ing panel.  
f. Reverse above procedure for reassembly.  
c. Remove 4 mounting bolts making sure to support the  
weight of the ceiling panel.  
Junction Box  
With Cover  
Air Sweep Switch  
d. Disconnect the unit harnesses and main power wires  
from the ceiling panel.  
e. Lower the ceiling panel from the air conditioning unit.  
f. Reverse above procedure for reassembly.  
Air Sweep Cam  
Thermostat  
Master Control  
Switch  
Serial/Model  
Number Tag  
Duct Plate &  
Mounting Holes  
Figure 3-5 Control Box Assembly -- Free Blow  
3.3.5 Air Sweep Switch Removal  
To remove the air sweep switch, do the following:  
a. Remove ceiling grill. (Refer to paragraph 3.3.2.)  
Mounting Bolts  
Junction Box  
b. Remove 5 screws securing the control assembly  
(Item 2, Figure 1-3) to the control box cover.  
c. Disconnect wires from the air sweep switch.  
d. Pinch tabs on either end of the switch and slide out of  
lower control box cover.  
Figure 3-3 Ceiling Panel Assembly  
e. Reverse above procedure for reassembly.  
3-2  
T--298  
3.3.6 Indoor Thermostat Removal  
To remove the indoor thermostat (Figure 3-6) do the  
following:  
Air Sweep Motor  
a. Remove ceiling grille. (Refer to paragraph 3.3.2.)  
b. Remove 5 screws securing the control assembly  
(item 3, Figure 1-3) to the control box cover.  
c. Remove the indoor thermostat knob by grabbing the  
outside edge of the knob and pulling it off of the ther-  
mostat stem.  
d.Remove 2 screws that secure the indoor thermostat to  
the lower control box cover.  
e. Carefully disconnect the 2 wires from the indoor ther-  
mostat.  
f. Remove the sensing bulb from the plastic clip.  
g. Carefully slide the sensing bulb through the rubber  
grommet.  
Figure 3-7 Air sweep motor  
h. Remove the thermostat from the control assembly.  
i. Reverse above procedure for reassembly.  
3.3.8 Heat Strip Assembly Removal  
To remove the heat strip assembly (Figure 3-8) do the  
following:  
Thermostat  
a. Remove ceiling grille. (Refer to paragraph 3.3.2.)  
b. Unplug electrical connection at air sweep motor as-  
sembly.  
c. Remove two screws securing heat strip assembly to  
the ceiling panel assembly.  
d. Slide heat strip assembly away from air sweep motor  
assembly and pull down, easing the the electrical  
connection through the access hole.  
e. Reverse the procedures for reassembly.  
Sensing Bulb  
Figure 3-6 Indoor Thermostat  
3.3.7 Air Sweep Removal  
To remove the air sweep, do the following:  
a. Remove ceiling grille. (Refer to paragraph 3.3.2.)  
Heat Strip  
b. Remove cam (See Figure 3-3) from air sweep motor  
shaft.  
c. Remove 4 screws securing air sweep motor bracket  
to the ceiling panel assembly.  
d. Carefully disconnect air sweep motor wire termina-  
tions.  
e. Remove 2 screws securing air sweep motor  
(Figure 3-7) to control box and remove motor.  
f. Reverse above procedure for reassembly.  
Figure 3-8 Heat Strip Assembly  
3-3  
T--298  
3.4 CEILING UNIT -- DUCTED SYSTEMS  
3.4.1 Filter Removal  
c. Remove two screws securing control box cover to  
control box assembly. See Figure 3-11.  
d. Remove control box assembly cover.  
The filters (Figure 3-9) are located in the ceiling grill. To  
remove the filters, do the following:  
a. Grasp the edge of the filter at recess in the end of the  
ceiling grill.  
b. Pull filter completely out of the filter slot.  
c. Vacuum filter or wash filter in luke--warm water.  
Shake off excess water and dry thoroughly.  
d. Replace filter by sliding the filter into the filter slot in  
the ceiling grill until the filter frame is flush with the in-  
terior grill.  
Mounting Screws  
Filters  
Figure 3-10 Ceiling Grill -- Ducted  
e. Disconnect blue furnace wires.  
f. Unplug two connectors from upper unit.  
g. Unplug DC power plug #1 (red/yellow/black wires)  
See Figure 3-12  
h. Unplug relay signal plug #2 (brown/red/orange/  
yellow wires). See Figure 3-12  
Operation Indicators  
i. While supporting control box assembly remove two  
screws securing control box assembly to ducted ceil-  
ing unit.  
Figure 3-9 Filter Removal -- Ducted Unit  
3.4.2 Ceiling Grill Removal  
j. Pull control box assembly from the ducted ceilingunit.  
k. Reverse above procedure to reassemble.  
To remove the ceiling grill (Figure 3--10) do the following:  
a. Before working on unit place the master switch in the  
OFF position and disconnect all electrical power.  
Control Box  
b. Remove filters (Refer to paragraph 3.4.1).  
Control Box  
Cover Screws  
c. Remove 4 screws located on the ceiling grill, (two are  
under the filters) making sure to support the weight of  
the grill.  
Fuse  
d. Lower the ceiling grill from the ceiling panel.  
e. To replace the grill, place the grill up against the ceil-  
ing panel and align the screw holes in the grill with the  
ceiling panel.  
f. Replace 4 screws and 2 filters.  
3.4.3 Control Box Assembly Removal  
PCB Cover  
To remove the control box assembly (Figure 3-11 &  
Figure 3-12) do the following:  
PCB Cover  
Screws  
a. Remove ceiling grill. Refer to paragraph 3.4.2.  
b. Disconnect 115 volt (AC) and 12 volt (DC) power  
wires.  
Figure 3-11 Control Box & PCB Cover  
3-4  
T--298  
3.4.5 PCB Display Removal  
115V AC  
To remove the PCB display assembly (Figure 3-13) do  
the following.  
12V DC  
a. Remove ceiling grill. Refer to paragraph 3.4.2.  
b. Push large clip away from PCB display assembly.  
c. Push center clip towards large clip.  
#1  
Fuse  
d. Pull PCB display assembly from PCB cover.  
e. Unplug display wiring from PCB main assembly.  
f. Reverse above procedures of reassembly.  
3.4.6 Fuse Removal  
Upper Unit  
Connectors  
Furnace  
Wires (blue)  
#2  
To remove the fuse (Figure 3-11) do the following:  
a. Remove ceiling grill. Refer to paragraph 3.4.2.  
Figure 3-12 Control Box Assembly -- Ducted  
3.4.4 Main PCB Board Removal  
b. Turn fuse holder in direction of arrow (counter-- clock--  
wise).  
To remove the Main PCB board (Figure 3-13) do the  
following:  
c. Pull fuse from fuse holder.  
a. Remove ceiling grill. Refer to paragraph 3.4.2.  
d. Test and/or replace.  
b. Remove three screws securing the PCB cover to the  
ducted ceiling unit.  
e. Reverse above procedures for reassembly.  
c. Carefully turn over the PCB cover exposing the PCB  
main and the PCB display assemblies.  
3.5 SERVICE -- UPPER UNIT -- STANDARD,  
HC & HP  
d. Gently push holding clip away from PCB mainassem-  
bly.  
3.5.1 Exterior Cover Removal  
e. Lift PCB main assembly from PCB cover assembly.  
f. Unplug display wiring plug #4. Figure 3-13  
CAUTION  
g. Unplug thermistor/thermostat wiring plug #3.  
Figure 3-13  
Coil fins are sharp. Use care when removing  
the cover form the base pan to avoid per-  
sonal injury.  
h. Unplug power wiring plug #1. Figure 3-12  
i. Unplug signal wiring plug #2. Figure 3-12  
j. Reverse above procedures for reassembly.  
To remove the exterior cover, do the following:  
a. Before working on unit place the master switch in the  
OFF position and disconnect all electrical power.  
b. Remove 15 screws securing the unit cover to the  
base pan assembly. See Figure 3-14.  
Holding Clips  
PCB Display  
c. Carefully lift the exterior cover off of the unit base pan  
assembly.  
d. Reverse above procedure for reassembly.  
PCB Main  
#4  
#3  
Cover Screws  
Figure 3-13 Main/Display PCB’s  
Figure 3-14 Cover Assembly -- Standard  
3-5  
T--298  
3.5.2 Compressor Replacement  
Observe the same procedures for rotary compressors  
as for reciprocating compressors.  
a. Follow all safety codes. Reminder: use protective  
goggles, work gloves, and water soaked quenching  
cloth.  
b. Remove exterior cover. refer to paragraph 3.5.1. Dis-  
connect all wiring from the compressor.  
c. Apply field--supplied, line--tap--valves to the suction  
and discharge lines as close to the compressor as  
possible.  
Control Box  
Screws  
d. Recover the refrigerant charge from the unit. After re-  
covering, cut the discharge and suction line process  
tubes below the tube crimps. If you choose a good  
tubing location for cutting the refrigeration lines ini-  
tially, the location is easily accessible when making  
the final joints.  
Figure 3-15 Control Box  
WARNING  
Oil vapor in piping stubs can ignite from  
torch flame and cause serious injury. Exer-  
cise extreme care when brazing, and keep  
brazing cloth and fire extinguisher handy  
for emergency use.  
Water  
Cover  
e. Connect a nitrogen supply to the unit at one of the line  
--tap--valve connectors (5--psig maximum flow), leav-  
ing the other connector open to the atmosphere.  
Braze angle valves with stubs to each process tube.  
Figure 3-16 Control Box Removal  
c. Slide control box out of the lower scroll assembly.  
(See Figure 3-16.)  
f. Remove compressor from unit (3 bolts).  
d. To open control box remove 2 screws securing the  
water cover to the control box cover.  
g. Remove line--tap--valves from suction and discharge  
lines. Carefully braze the holes closed from where the  
line--tap--valves were removed.  
e. Gently lift the water cover off of the control box. (See  
Figure 3-17.)  
h. Clean system: add or replace liquid line filter drier. For  
proper cleaning and flushing use a UL approved re-  
frigerant recycling system.  
f. Reverse above procedure for reassembly.  
i. Install new compressor and braze into place with  
field--supplied copper slip couplings.  
j.Connect wiring: replace wire terminals if necessary.  
k. Proceed with evacuation and charging (15.9 OZ. --  
.45 KG R22). Pinch off lines where angle valves were  
added. Cut off angle valves above pinch--off , and  
braze tubes.  
l. Start up unit.  
3.5.3 Control Box Assembly Removal  
To remove the control box assembly, do the following:  
Control Box  
Cover  
a. Remove exterior cover assembly. Refer to paragraph  
3.5.1.  
b. Remove 2 screws securing control box assembly to  
the lower scroll assembly. (SeeFigure 3-15.)  
Figure 3-17 Water Cover Removal  
3-6  
T--298  
3.5.4 Upper Scroll Assembly Removal  
i. Remove condenser fan from motor shaft and lift fan  
out through the top of the condenser orifice. (See  
Figure 3-22)  
a. Remove exterior cover assembly. Refer to paragraph  
3.5.1.  
j. Remove motor assembly.  
b. Remove 4 screws securing upper scroll assembly to  
the lower scroll assembly. (See Figure 3-18)  
k.Reverse above procedure for reassembly.  
c. Gently pry 4 snap clips open and lift the upper scroll  
assembly off of the lower scroll assembly.  
d. Reverse above procedure for reassembly.  
Screws  
4 Places  
Ground screw  
Motor Ground  
Lead  
Figure 3-19 Motor Assembly  
Spring Clamp  
Snap Clip  
4 Places  
Figure 3-18 Upper Scroll Assembly  
Figure 3-20 Spring Clamp Removal  
3.5.5 Motor Assembly and Condenser Fan  
Removal  
a. Remove exterior cover assembly. Refer to paragraph  
3.5.1.  
b. Remove control box assembly. Refer to paragraph  
3.5.3.  
Motor Clip  
c. Remove upper scroll assembly. Refer to paragraph  
3.5.4.  
d. Remove 4 screws securing the condenser cover to  
the condenser orifice. (See Figure 3-24.)  
e. Carefully disconnect motor wire terminations from  
within the control box.  
f. Remove 1 screw securing the motor ground lead to  
the motor bracket assembly. (See Figure 3-19)  
g. Using flat--nosed pliers, depress the motor spring  
clamp and slide it off of the condenser fan (See  
Figure 3-20).  
h. Lift and slide motor towards evaporator coil to remove  
condenser fan from the motor shaft.  
Figure 3-21 Motor Clip Removal  
3-7  
T--298  
3.5.7 Air Handling System Removal  
a. Remove exterior cover assembly. Refer to paragraph  
3.5.1.  
b. Remove control box assembly. Refer to paragraph  
3.5.3.  
c. Remove upper scroll assembly. Refer to paragraph  
3.5.4.  
d. Remove motor assembly. Refer to paragraph 3.5.5.  
e. Remove 8 screws securing lower scroll assembly to  
the base pan assembly.  
f. Remove 1 screw from clamp securing suction tube to  
the base pan assembly.  
Condenser Fan  
g. Remove 3 nuts securing the compressor to the base  
pan assembly.  
h. Remove 2 screws securing the condenser orifice to  
the base pan assembly.  
i. Remove 2 screws securing the condenser coil as-  
sembly to the base pan assembly.  
Figure 3-22 Condenser Fan Removal  
3.5.6 Evaporator Blower Wheel Adjustment or  
Removal  
j. Carefully lift the entire assembly off of the base pan  
assembly.  
a. Remove exterior cover assembly. Refer to Exterior  
Cover Assembly Removal instructions 3.5.1  
k. Reverse the above procedure for reassembly, ensur-  
ing that the air handling system is positioned correct-  
ly. Tighten all screws.  
b. Remove control box assembly. Refer to Control Box  
Assembly Removal instructions 3.5.3  
c. Remove upper scroll assembly. Refer to Upper Scroll  
Assembly Removal instructions 3.5.4  
d. Loosen motor assembly. Refer to Motor Assembly  
Removal instructions 3.5.5.  
Compressor  
e. Mark shaft at a point where wheel hub and motor  
shaft meet to aid in reassembly.(See Figure 3-23.)  
Condenser Cover  
f. Remove 1 set screw holding the blower wheel to the  
motor shaft. (See Figure 3-23)  
g. Slide off blower wheel from motor shaft  
h. Reverse above procedure for reassembly.  
Set Screw  
Motor Assembly  
Condenser  
Cover Screws  
Base Pan  
Base Pan  
Figure 3-24 Condenser With Motor Assembly &  
Compressor  
Figure 3-23 Blower Wheel  
3-8  
T--298  
3.5.8 Capacitor Troubleshooting  
WARNING  
Do not touch the metal of the screwdriver  
when discharging the capacitor. You could  
receive a shock.  
WARNING  
Disconnect power to the AirV unit before  
checking the capacitor.  
b. After the capacitor has been discharged and all wires  
removed from the capacitor terminals, use an ohm--  
meter to test its resistance.  
To test capacitor to determine if good, open or shorted,  
an ohm meter can be used. To determine a capacitor’s  
capacitance, a capacitor meter is required.  
c. Set the scale to R x 1K or 10K ohm and place the  
ohmmeter leads across the capacitor terminals.  
Capacitors showing signs of leaks or bulging should be  
replaced immediately.  
d. If the ohmmeter first reads 0, then rises toward infinity  
or some higher resistance, the capacitor is good.  
3.5.9 Capacitor Testing and Replacement  
e. If the ohmmeter goes to 0 or a low resistance and  
stays there, the capacitor is shorted and needs to be  
replaced.  
Capacitors must be discharged properly before testing.  
a. Place a 20,000 ohm, 2 watt resistor across the termi-  
nals of the capacitor for approximately 30 seconds  
(See Figure 3-25 for a suggested tool).  
f. If the ohmmeter reads infinity (OL) the capacitor is  
open and needs to be replaced.  
INSULATED SCREWDRIVER  
20,000 -- OHM  
2 -- WATT RESISTOR  
ATTACH TO CLEAN UNPAINTED  
METAL PART OF UNIT FRAME  
CLIP TO  
SCREWDRIVER  
TOUCH TO CAPACITOR TERMINALS  
TO DISCHARGE CAPACITOR  
Figure 3-25 Set--Up For Discharging a Capacitor  
3.5.10 Positive Temperature Coefficient Thermister  
(PTC) (Start Thermistor) Troubleshooting  
When the compressor starts, an amp draw will be  
indicated for almost a second.  
a. Disconnect power from the AirV unit.  
b. Disconnect the wires to the PTC.  
If no amp draw is indicated or if the amp draw occurs for  
much longer than a second, the PTC is defective and  
must be replaced.  
c. Using an ohm meter, check for continuity across the  
PTC.  
3.5.11 Line Voltage -- 10%  
Line voltage should be checked during peak electrical  
load periods.  
If the PTC does not have continuity, it must be replaced.  
If continuity exists, reconnect the wires to the PTC.  
d. Reconnect power to the AirV unit.  
With the AirV unit on and the compressor operating, use  
a voltmeter to check the voltage being supplied to the  
AirV unit. The voltage must be within 10% of the units  
required voltage. A voltage drop greater than 10% will  
cause a premature compressor failure and needs to be  
corrected immediately.  
e. Turn on the AirV unit to start.  
f. Use a clamp--on amp probe to monitor the amp draw  
of the compressor during its start--up.  
3-9  
T--298  
3.6 SERVICE -- UPPER UNIT -- LOW PROFILE  
3.6.1 Exterior Cover Removal  
b.  
b.  
CAUTION  
b.  
Coil fins are sharp. Use care when removing  
the cover form the base pan to avoid per-  
sonal injury.  
b.  
To remove the exterior cover, do the following:  
a. Before working on unit place the master switch in the  
OFF position and disconnect all electrical power.  
c.  
b. Remove (8) screws securing the unit cover to the  
base pan assembly. See Figure 3-26.  
b.  
b.  
c. Carefully lift the exterior cover off of the unit base pan  
assembly.  
d. Reverse above procedure for reassembly.  
Figure 3-27 Upper Scroll Assembly  
Locking Tabs (b.) & Screw Locations (c.)  
Screws  
Screws  
Figure 3-26 Cover Assembly -- Low Profile  
3.6.2 Upper Scroll Assembly Removal  
To remove the upper scroll assembly, do the following:  
a. Remove exterior cover assembly. Refer to paragraph  
3.6.1.  
b. Release the (2) front, (2) rear, (1) left side and (1) right  
side locking tabs (See Figure 3-27) by pulling back on  
the tabs (See Figure 3-28).  
c. Remove the screw (1) from the control box cover  
(See Figure 3-27).  
d. With all (6) locking tabs released and control box  
screw removed, lift the upper scroll assembly off of  
the lower scroll assembly.  
e. Reverse above procedure for reassembly. Ensure all  
(6) locking tabs snap shut & lock.  
Figure 3-28 Upper Scroll Assembly  
Keeper Tab Release  
3-10  
T--298  
Evaporator Coil  
Retaining  
Ring  
Figure 3-30 Condenser Fan Assembly  
& Retaining Ring  
Fan Stop  
Condenser Coil  
Condenser Motor  
13MM  
Bolt  
13MM  
Bolt  
Grommet  
Figure 3-29 Upper Scroll & Control Box  
Cover Removed  
Figure 3-31 Condenser Fan Motor  
& Fan Assembly Stop  
3.6.3 Condenser Fan Assembly Removal  
To remove condenser fan assembly, do the following:  
a. Perform steps outlined in Section 3.6.2.  
b. Depress and remove Retaining Ring (See  
Figure 3-30).  
Tab  
c. Using both hands, carefully pull up on fan assembly  
until it is free of the motor shaft.  
d. When replacing the fan assembly make sure the fan  
assembly is against the stop on the shaft (See  
Figure 3-31)  
e. Push back on tab to allow fan assembly to rest  
against stop (See Figure 3-32). Fan assembly will  
now be flush with the end of the motor shaft.  
Figure 3-32 Condenser Fan Motor  
& Fan Assembly Tab  
f. Reverse above procedure for reassembly.  
3-11  
T--298  
3.6.4 Condenser Motor Removal  
To remove condenser fan motor, do the following:  
a. Perform steps outlined in Section 3.6.2.  
b. Remove (3) 13MM bolts (See Figure 3-31).  
c. Remove (3) Grommets. Inspect, replace or reuse.  
Blower Side Locking Tabs  
d. Cut Tie--Wraps & discard (2 locations). When re-  
assembling, tie--wrap at same 2 locations.  
e. Remove ground wire from compressor bracket (See  
Figure 3-33).  
f. Un--plug (yellow/brown/white) from control box as-  
sembly.  
g. Reverse above procedure for reassembly.  
Cond. Motor  
Ground Screw  
Outside Locking Tabs  
Comp. Mounting Bolt  
Figure 3-33 Condenser Motor Ground  
Figure 3-34 Evaporator Motor Locking Tabs  
3.6.5 Evaporator Motor/Blower Assembly  
Removal  
To remove the evaporator motor, do the following:  
a. Perform steps outlined in Section 3.6.2.  
Lower Scroll  
Assembly  
b. Pull back on and release the (4) locking tabs. There  
are 2 on each side of the control box assembly. (See  
Figure 3-34).  
Capacitor  
c. Lift control box assembly from lower scroll assembly,  
exposing evaporator motor.  
d. Un--plug (black/blue/white/brown) evaporator motor  
from control box assembly.  
e. Remove ground wire (green/yellow) from motor  
housing.  
Cradle  
f. Lift motor/blower assembly from lower scroll assem-  
bly cradle.  
g. Carefully remove the blower wheel from the evapora-  
tor motor shaft by pushing out from the motor side.  
Figure 3-35 Evaporator Motor/Blower Assembly  
In Cradle  
3-12  
T--298  
NOTE  
NOTE  
When reassembling the blower wheel on to  
the motor shaft ensure that the blower  
wheel is flush with the end of the motor  
shaft (SeeFigure 3-36).  
When placing the evaporator motor/blower  
assembly back into the lower scroll assem-  
bly cradle, make sure that the assembly is  
seated securely in the cradle.  
(See Figure 3-35).  
h. Reverse above procedure for reassembly.  
3.6.6 Compressor Replacement  
Perform the procedures outlined in Section 3.5.2  
There are 4 bolts with the Low Profile Compressor.  
The system charge for the Low Profile unit is 16.9 OZ.  
3.6.7 Capacitor Removal  
To remove the capacitor, do the following:  
a. Perform steps a., b. & c. as outlined in Section 3.6.5.  
b. Perform steps outlined in Sections 3.5.8 & 3.5.9.  
Wheel Flush With Motor Shaft  
c. The Low Profile Capacitor is removed from the con-  
trol box assembly by pushing on the capacitor from  
under the control box assembly (See Figure 3-35).  
Figure 3-36 Evaporator Blower Wheel  
(Flush With End Of Motor Shaft)  
Control Box Assembly  
Upper Scroll Assembly  
Capacitor  
Terminal Block  
Figure 3-37 Control Box Assembly With Capacitor  
3.6.8 Remote Control (Fahrenheit to Celsius)  
CAUTION  
All Remote Control Assemblies in the United States are  
pre--set to display in Fahrenheit degrees (see  
Figure 3-38). To change from a Fahrenheit display to a  
Celsius display do the following:  
The change from Fahrenheit to Celsius will  
be permanent. It cannot be changed back to  
Fahrenheit.  
3-13  
T--298  
a. Remove the batteries from the remote control.  
f. Carefully cut the FR9 jumper wire.  
b. Carefully remove the remote cover by inserting a nar-  
row flat object between the cover and remote body  
and prying apart.  
g. Reverse above procedure for reassembly.  
c. Remove the brass screw holding the PCB in place.  
CAUTION  
d. Carefully remove the PCB board from the remote  
body, making sure the battery springs release from  
their holders.  
When re--assembling, ensure the battery  
springs are correctly placed in the battery  
spring holders.  
e. Locate FR9 on the PCB board (see Figure 3-39).  
Spring Holders  
Battery Springs  
PCB  
BATTERIES  
&
COVER  
COVER  
BODY  
Figure 3-38 Remote Control Components  
PCB  
FR9  
Figure 3-39 Remote Control PCB (FR9 Location)  
3-14  
T--298  
3.7 THERMOSTAT INSTALLATION AND START--  
UP INSTRUCTIONS (WALL MOUNTED)  
2.Disconnect wires from existing thermostat, one at  
a time. Be careful not to allow wires to fall back into  
the wall.  
3.7.1 Introduction  
3.As each wire is disconnected, record wire color  
and terminal marking.  
The thermostat is a wall mounted, low--voltage  
thermostat which maintains room temperature by  
4.Discard or recycle old thermostat.  
controlling the operation of  
a
heating and air  
conditioning system. Batteries are not required;  
temperature and mode settings are preserved with the  
power off.  
NOTE  
Mercury is a hazardous waste and must be des-  
posed of properly.  
c. Seperate the front and back pieces of plastic.  
CAUTION  
d. Route thermostat wires through hole in back piece of  
plastic. Level plastic against wall (for aesthetic value  
only -- thermostat need not be leveled for proper op-  
eration) and mark wall through 2 mounting holes.  
Improper wiring or installation may damage  
thermostat. Wiring must conform to local  
and national electrical codes.  
e. Drill two 3/16 inch mounting holes in wall where  
marked.  
WARNING  
NOTE  
Mounting holes on thermostat are designed to  
fit on a horizontal J--Box.  
Before installing thermostat, turn off all  
power to unit. There may be more than one  
power disconnect. Electrical shock can  
cause personal injury or death.  
f. Secure back plastic to wall with 2 anchors and screws  
provided, making sure all wires extend through holein  
plastic.  
3.7.2 Installation  
g. Connect wires to proper terminal of the connector  
block in the front piece of plastic.  
NOTE  
h. Pusr any excess wire back into wall. Excess wire in-  
side the thermostat plastic case can interfere with  
proper air flow across the temperature sensor. Seal  
hole in wall to prevent air leaks. Leaks can effect op-  
eration.  
Read all instructions before starting the installa-  
tion.  
NOTE  
i. Snap front and back pieces of plastic together.  
j. Turn on power to the unit.  
The thermostat requires no batteries. The ther-  
mostat is not a power stealing device and  
MUST have both R and C connected.  
3.8 LCD DISPLAY  
3.8.1 Cool Only Thermostat (Part No. 1110--421)  
3.7.3 Thermostat Location  
On power up, the LCD readout will display C (Cool  
The thermostat should be mounted:  
Approximately 5 foot (1.5m) from the floor.  
Only).  
Close to or in a frequently used room, preferably on  
an inside partitioning wall.  
3.8.2 Heat/Cool Thermostat (Part No. 1110--420)  
On power up, the LCD readout will display HC (Heat/  
Cool).  
On a section of wall without pipes or duct work.  
The thermostat should NOT be mounted:  
Close to a window, or an outside wall, or next to a door  
leading to the outside.  
3.9 SET THERMOSTAT CONFIGURATION  
While in configuration mode, three option choices can be  
made.  
Exposed to direct light and heat from a lamp, sun, fire-  
place, or other temperature--radiating object which  
may cause a false reading.  
A - Anticipator Value Adjustment  
Close to or in direct airflow from supply registers and  
return--air grilles.  
d - Display Temperature Fahrenheit/Celcius Selection  
oF - Offset Adjustment For Room Temperature  
In areas with poor air circulation, such as behind a  
door or in an alcove.  
3.7.4 Install Thermostat -- 12VDC  
a. Turn off all power to unit.  
3.9.1 Enter Configuration Mode  
Enter and hold the FAN button for approximately 10 sec-  
b. If an existing thermostat is being replaced:  
1.Remove existing thermostat from wall.  
onds until room temperature disappears and the display  
reads A. You are now in the configuration mode.  
3-15  
T--298  
NOTE  
c. Press MODE button once to display offset value.  
If the FAN button is pressed again or if no button  
is pressed for two minutes, the thermostat will  
exit the configuration mode and return to nor-  
mal operation. To re--enter the configuration  
mode, the FAN button must be pressed and  
held for 10 seconds again.  
d. Use UP & DOWN buttons to select a value between  
--5 and 5.  
e. Press MODE buttonto return to oF. UP & DOWN  
buttons now move between option choices; or press  
FAN button to exit configuration mode.  
3.10 CHECK THERMOSTAT OPERATION  
3.10.1 Fan Operation (Cool Only)  
While in the configuration mode, the following options  
are available:  
A. ANTICIPATOR -- Value Adjustment  
1. Press FAN button, starting fan operation. FAN an-  
nunciator turns on; Lo is displayed in the room tem-  
perature area for 5 seconds indicating Fan Low  
Speed.  
This adjustment controls the sensitivity and cycle rate of  
the thermostst. Higher numbers decrease the  
sensitivity and slow the cycle rate. Lower numbers  
increase the sensitivity and increase the cycle rate.  
However, a limiting feature will not allow more than 4  
equipment cycles per hour, regardless of setting. Values  
can range from 1 to 3. Factory default setting is 2. This  
default selection will provide optimum performance in  
nearly all installations. Try it first. Do not change settings  
unless there is evidence of need to do so. Unlike  
conventional anticipators, this setting is not determined  
by current draw. There is no need to measure, know, or  
compensate for current.  
2. Press FAN button, FAN annunciator remains on; Hi  
is displayed in room temperature area for 5 seconds  
indicating Fan High Speed.  
3. Press FAN button, stopping fan operation. FAN an-  
nunciator turns off.  
3.10.2 Fan Operation (Heat/Cool)  
1. Press FAN button, starting low fan (Lo) operation.  
FAN annunciator turns on.  
To Adjust:  
2. Press FAN button, starting high fan (Hi) operation.  
FAN annunciator remains on.  
a. Enter configuration mode (if not already there).  
b. Use UP & DOWN buttons to display A.  
c. Press MODE button once to display current value.  
d. Use UP & DOWN buttons to move between values.  
3. Press FAN button, stopping fan operation. FAN an-  
nunciator turns off.  
3.10.3 Cooling Operation (Cool Only)  
e. Press MODE buttonto return to A. UP & DOWN  
buttons now move between option choices A, d, oF or  
press FAN button to exit configuration mode.  
1. Press and release MODE button until COOL is dis-  
played.  
2. Press DOWN button until LCD readout reads 10 de-  
grees below room temperature. Cooling and High  
Fan system should begin to operate within 5 min-  
utes.  
d. Fahrenheit/Celsius Selection  
This selection operates the thermostat in either  
Fahrenheit or Celsius.  
To Select:  
3.10.4 Cooling Operation (Heat/Cool)  
a. Enter configuration mode (if not already there).  
b. Use UP & DOWN buttons to display d.  
1. Press and release MODE button until COOL is dis-  
played.  
c. Press MODE button once to display current  
2. Press DOWN button until LCD readout reads 10 de-  
grees below room temperature. Cooling and High  
Fan system should begin to operate within 5 min-  
utes.  
selection of F or C.  
d. Use UP & DOWN buttons to change between F & C.  
e. Press MODE buttonto return to d. UP & DOWN  
buttons now move between option choices; or press  
FAN button to exit configuration mode.  
3.10.5 Heating Operation (Heat/Cool)  
1. Press and release MODE button until HEAT is dis-  
played.  
oF. Room Temperature Offset Adjust Selection  
The selected number is the number of degrees, plus or  
minus, which will be added to the actual temperature.  
The numbers can range between --5 and +5. Factory  
default is 0. This adjusted value will be used as actual  
temperature for both display and control action. The  
effect is that a positive number selection will make the  
room temperature lower, and vice versa. The  
thermostat is calibrated within an accuracy of plus or  
minus 2 degrees when shipped from the factory; this  
adjustment will provide the best accuracy when set to o.  
2. Press UP button until LCD readout reads 10 degrees  
above room temperature. Heating system should  
begin to operate within 1 minute.  
3.11 CHECK THERMOSTAT OPERATION  
3.11.1 Temperature Display  
The thermostat will display room temperature until the  
UP or DOWN button is pressed. The word SET appears  
when these buttons are pressed and the current set  
point is displayed. If no buttons are pressed for 5  
seconds, the display will change back to show room  
temperature.  
To Select:  
a. Enter configuration mode (if not already there).  
b. Use UP & DOWN buttons to display oF .  
3-16  
T--298  
3.11.2 Timeguard Timer  
minutes regardless of demand). However, pressing UP  
and FAN buttons simultaneously or changing the set  
point will override the timer for 1 cycle.  
A 3--minute timeguard is built into the thermostat  
immediately upon power up, and any time the  
compressor (output “Y”) turns off. The compressor will  
not turn on until the timeguard has expired. Pressing UP  
and FAN buttons simultaneously will override the  
timeguard for 1 cycle.  
3.11.4 Minimum On Timer  
Once the equipment has turned on, it will remain on for a  
minimum of 2 minutes regardless of demand. However,  
the equipment can turn off in less than 2 minutes if a  
change in set point, or a changein mode occurs.  
3.11.3 Cycle Timer  
3.11.5 Error Messages  
In normal cooling (and heating) operation the  
thermostat will not allow more than 4 equipment cycles  
per hour (or 1 cycle every 15 minutes). Both the “Y”  
(cooling) and “W” (heating) outputs have a 15--minute  
timer that starts counting down when the output is  
turned on, (e.g., if “Y” output is turned on for 9 minutes  
and then satisfies, it cannout turn back on for another 6  
E4 will be displayed if the thermostat has an internal  
memory failure. If E4 appears, replace the thermostat.  
---- (two dashes) will be displayed if the thermostat  
cannot properly read the room temperature. If ----  
appears, replace the thermostat.  
Factory Wiring  
UPPER UNIT  
Field Wiring  
Motor  
Comp.  
1 2 3 4  
2
1
115V AC High Voltage  
Power Supply  
1 2 3 4  
J
L
N2  
N1  
THERMOSTAT  
POWERBOX  
ASSEMBLY  
W
Y
1
2
3
4
5
COOL (Compressor)  
FAN (High)  
Y
GH  
GL  
C
GH  
12VDC LowVoltage  
Power Supply  
GL FAN (Low)  
R
C
CEILING UNIT  
Figure 3-40 Wall Thermostat Wiring Diagram -- Cool Only Model  
3-17  
T--298  
Factory Wiring  
Field Wiring  
UPPER UNIT  
Motor  
Comp.  
1 2 3 4  
2 1  
115V AC High Voltage  
Power Supply  
1 2 3 4  
J
L
N2  
N1  
THERMOSTAT  
POWERBOX  
ASSEMBLY  
W
Y
1
2
3
4
5
COOL (Compressor)  
FAN (High)  
Y
GH  
GL  
C
GH  
12VDC LowVoltage  
Power Supply  
GL FAN (Low)  
R
C
TB  
Blue  
Blue  
1
2
12 VDC (Gnd)  
+ 12VDC  
FURNACE  
CEILING UNIT  
Figure 3-41 Wall Thermostat Wiring Diagram -- Heat/Cool Model  
3-18  
T--298  
SECTION 4  
WIRING SCHEMATICS  
4.1 INTRODUCTION  
This Section contains wiring schematics for the AirV units.  
Figure 4--1 is the schematic for the standard upper unit assembly and it is applicable to all standard units.  
Figure 4--2 is the schematic for the Low Profile upper unit assembly.  
Figure 4--3 is the schematic for a free blow ceiling unit without heat while Figure 4--4 is a free blow unit with heat.  
Figure 4--5 is for a ducted unit with microprocessor control.  
Figure 4--6 is for an Upper Unit Heat Pump with free blow application and Figure 4--7 is the matching free blow ceiling  
unit.  
Figure 4--8 is for the Upper Unit Heat Pump ducted application and Figure 4--9 is the matching ducted ceiling unit.  
Note that the ducted units have 115 VAC power for the components and 12 VDC power for the microprocessor control  
system.  
Figure 4--10 is for the ducted or free blow application that uses a wall--mounted thermostat, with or without the furnace  
option.  
Where applicable, diagrams that designate 115 Volt, 60 H, 1 Phase, are also available using 220 Volts, 50 H, 1 Phase.  
Most noteably Figure 4--1 and Figure 4--5.  
FAN MOTOR  
4P  
1
2P  
1
BLK  
BLU  
BLK  
BLU  
BRN  
WHT  
GRN/YEL  
2
3
4
2
PLUG CONNECTS  
TO CEILING UNIT  
SEE FIG> 4--3  
OR 4--4  
F
WHT  
GRN/YEL  
GRN/YEL  
C
H
CAPACITOR  
CONTROL  
BOX  
EVAP.  
RED RED  
2P  
1
BLU  
WHT  
R
YEL  
YEL  
2
C
1
PTC  
2
BLU  
S
OVERLOAD PROTECTOR  
(If Used)  
COMPRESSOR  
Figure 4--1 Upper Unit Schematic -- Standard & HC  
(UNIT - 99 -00468 -10)  
INDOOR FAN MOTOR  
4P  
4P  
BLK  
BLU  
BLK  
BLU  
1
1
2
3
4
1
2
3
4
2
3
4
GRN/YEL  
WHT  
BRN  
WHT  
BRN  
WHT  
GRN/YEL  
FMC  
OUTDOOR FAN MOTOR  
3P  
1
YEL  
YEL  
1
2
3
WHT  
2
3
2P  
1
BRN  
WHT  
WHT  
YEL  
F
H
C
CAPACITOR  
BRN  
2
WHT  
RED  
BLU  
OLP  
(IF USED)  
RED  
BLU  
R
S
PTC  
(IF USED)  
YEL  
YEL  
LEGEND  
C
1
2
(3)  
OLP: OVERLOAD PROTECTION  
PTC: START THERMISTER  
JTB: JOINT TERMINAL BLOCK  
FMC: INDOOR FAN MOTOR CAPACITOR  
COMPRESSOR  
Figure 4--2 Upper Unit Schematic -- Low Profile  
4-1  
T--298  
BLK  
SWITCH  
4
2
6
8
CONTACTS MADE  
POSITION  
4P  
HIGH FAN  
LOW FAN  
1--4 . 1--6  
1--2 . 1--6  
NONE  
BLU  
1
OFF  
2
3
4
ASW  
LOW COOL  
HIGH COOL  
1--2 . 1--6 . 1--8  
1--4 . 1--6 . 1--8  
ORN  
ORN  
YEL  
WHT  
1
1
2
1
2
O (OFF)  
I (ON)  
2
2P  
BLK  
ASW  
2 -- 1  
ORN  
WHT  
L
C
GRN/YEL  
115 VAC  
SUPPLY  
WIRE  
LEGEND  
IT  
SW  
ASM  
2P  
1
ASM : AIR SWEEP MOTOR  
ASW : AIR SWEEP SWITCH  
SW : SWITCH  
WHT  
YEL  
{
2
GRN/YEL  
IT : INDOOR THERMOSTAT  
Figure 4--3 Ceiling Unit Schematic -- Cooling Only  
SWITCH  
POSITION  
4P  
SW  
CONTACTS MADE  
NONE  
BLK  
H
OFF  
1
L1--L . L1--A  
L1--H . L1--A  
LOW FAN  
HIGH FAN  
BLU  
2
3
4
L
L1  
WHT  
ORN  
ORN  
LOW COOL  
HIGH COOL  
HEAT  
L2--C . L1--L . L1--A . B--3  
L2--C . L1--H . L1--A . B--3  
A
2
1
BLK  
BLK  
1
2
2P  
YEL  
RED  
BLU  
BLK  
WHT  
IT  
ASW  
1
1
3
L2--HT . L1--L . L1--A . B--1  
ORN  
WHT  
GRN/YEL  
B
2
3
O (OFF)  
2
ASW  
2 -- 1  
ASM  
1 (ON)  
HEATER--ASSY  
HEATER  
HT  
BLK  
115 VAC  
SUPPLY  
WIRE  
LEGEND  
2
1
BT  
ASM AIR SWEEP MOTOR  
L2  
C
ASW AIR SWEEP SWITCH  
SW SWITCH  
IT INDOOR THERMOSTAT  
WHT  
2P  
2P  
WHT  
WHT  
GRN/YEL  
1
CEC CLOSED END CONNECTOR  
YEL  
CEC  
{
BT BIMETAL  
2
Figure 4--4 Ceiling Unit Schematic -- Heat/Cool  
LEGEND  
IDC Th : INDOoR COIL THERMISTER  
RA Th : ROOM AIR THERMISTER  
1
2
3
4
2
1
KY : RELAY  
DI : DIODE  
BLK  
WHT  
GRN/YEL  
BLU  
BLK  
WHT  
CN3  
3
2
1
Y
CN1  
RA Th  
CN4  
CN4  
RY1  
BLK  
1
2
3
4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
CONTROL  
PCB  
BLK  
BRN  
L
IDC Th  
RY3  
RY2  
N2  
N1  
115 VAC POWER  
WHT  
GRN/YEL  
ASS’Y  
FUSE  
D1  
RED  
BLK  
1
2
3
1
2
3
1
2
3
2
1
(+)  
(--)  
250V 3.15A  
RY4  
CN1  
12 VDC POWER  
1 2 3 4 5 6 7 8  
1 2 3 4 5 6 7 8  
CN9  
CN9  
1
2
CN2  
BLU  
BLU  
DISPLAY PCB AS  
Figure 4--5 Ceiling Unit, Standard -- Ducted  
4-2  
T--298  
FAN MOTOR  
OLP: OVERLOAD PROTECTION  
PTC: START THERMISTER  
RVC: REVERSING VALVE COIL  
4P  
4P  
1
BLK  
BLU  
1
2
3
4
1
BLK  
BLU  
WHT  
2
3
4
GRN/YEL  
2
3
4
WHT  
BRN  
GRN/YEL  
GRN/YEL  
BRN  
WHT  
EVAP.  
CONTROL  
BOX  
2P  
1
2P  
RVC  
BLK  
BRN  
1
2
1
F
BLK(BLU)  
C
CAPACITOR  
H
2
2
WHT  
WHT  
RED  
RED  
BLU  
2P  
1
OLP  
(IF USED)  
R
S
BLK  
RED  
YEL  
PTC  
C
1
2
(3)  
2
BLU  
FREEZE  
SWITCH  
COMPRESSOR  
Figure 4--6 Heat Pump -- Upper Unit -- Free Blow  
SW  
4P  
BLK  
BLU  
SWITCH  
POSITION  
H
1
2
CONTACTS MADE  
NONE  
OFF  
L
L1  
LOW FAN  
L1--L . L1--A  
L1--H . L1--A  
ORN  
ORN  
WHT  
A
2
1
3
4
HIGH FAN  
1
1
2
2
2P  
ASW  
LOW COOL  
BLK  
L2--C . L1--L . L1--A . B--3  
L2--C . L1--H . L1--A . B--3  
L2--HT . L1--L . L1--A . B--1  
HT  
C
BLK  
HIGH COOL  
HEATING  
ORN  
WHT  
GRN/YEL  
HEATER AS  
HEATER BT  
2P  
L2  
ASM  
BLK  
WHT  
O (OFF)  
1 (ON)  
2
1
2
1
2
2P  
1
ASW  
BLK  
BLK  
2 -- 1  
H
1
LEGEND  
BRN  
YEL  
115 VAC  
SUPPLY  
WIRE  
1
3
C
2
2
ASM: AIR SWEEP MOTOR  
ASW: AIR SWEEP SWITCH  
SW: SWITCH  
B
RED  
3
WHT  
YEL  
L
IT  
2P  
1
WHT  
WHT  
CEC  
IT: INDOOR THERMOSTAT  
{
CEC: CLOSED END CONNECTOR  
GRN/YEL  
2
BT: BIMETAL  
Figure 4--7 Heat Pump -- Ceiling Unit -- Free Blow  
4-3  
T--298  
1
2
3
LEGEND  
BRN  
BLK  
ODC Th  
ODA Th  
CN :HOUSING CONNECTOR  
PTC :START THERMISTOR  
OLP :OVERLOAD PROTECTOR  
RVC :REVERSING VALVE COIL  
FAN MOTOR  
CN  
BLK  
BLK  
BLU  
RED  
WHT  
1
2
3
4
1
BLU  
RED  
2
3
5
6
ODA Th :OUTDOOR AIR THERMISTOR  
ODC Th :OUTDOOR COIL THERMISTOR  
GRN/YEL  
GRN/YEL  
BRN  
BRN  
CONTROL EVAP.  
BOX  
WHT  
WHT  
F
C
H
CAPACITOR  
1
2
YEL  
COMPRESSOR  
RED  
BLU  
OLP  
RED  
R
1
2
(IF USED)  
1
YEL  
BLK(BLU)  
RVC  
C
2
PTC  
BLU  
(3)  
S
CN  
Figure 4--8 Heat Pump -- Upper Unit -- Ducted  
LEGEND  
PLUG CONNECTS TO UPPER UNIT.  
SEE DIAGRAM SUPPLIED WITH UPPER UNIT  
FOR ADDITIONAL WIRING.  
NOTE  
IDC Th: INDOOR COIL THERMISTER  
RA Th: ROOM AIR THERMISTER  
*
*
FACTORY WIRING  
ODC Th: OUTDOOR COIL THERMISTER  
FIELD WIRING  
(115VAC HIGH VOLT.)  
COMPRESSOR  
ODC ODA  
RVC  
MOTOR  
ODA Th :OUTDOOR AIR THERMISTOR  
RVC: REVERSING VALVE COIL  
1
2
3
1
2
1
2
3
4
2
1
*
FIELD WIRING  
GRN/YEL  
CN3  
(12VDC LOW VOLT.)  
WHT  
D1: DIODE  
K: RELAY  
BLK  
BLU  
WHT  
RED  
BLK  
BLK  
RED  
BLK  
BRN  
CN5  
1
2
1
2
3
4
Y
CN5  
1
2
3
CN1  
RA Th  
1
2
3
4
5
6
7
8
1
1
2
3
4
5
6
7
8
BLK  
BLK  
2
3
4
5
6
7
8
1
2
3
4
L
CONTROL PCB  
ASS’Y  
K1  
K7  
K2  
K3  
K4  
115VAC POWER  
N2  
N1  
WHT  
GRN/YEL  
IDC Th  
BRN  
POWER PCB ASS’Y  
CN4  
CN4  
CN6  
D1  
FUSE  
RED  
1
2
3
1
2
3
1
2
3
2
1
(+)  
(--)  
K6  
12VDC POWER  
250V 3.15A  
BLK  
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
CN1  
CN6  
CN9  
CN9  
1
2
CN2  
BLU  
BLU  
FURNACE SIGNAL  
DISPLAY PCB AS  
Figure 4--9 Heat Pump -- Ceiling Unit -- Ducted  
4-4  
T--298  
Figure 4--10 Ceiling Unit -- Wall Thermostat -- Ducted & Free Blow  
4.2 WALL MOUNTED THERMOSTATS  
For proper wiring of Wall Mounted Thermostats as an accessory, refer to Figure 3-40 (Wall Thermostat Wiring  
Diagram -- Cool Only Model) or Figure 3-41 (Wall Thermostat Wiring Diagram -- Heat/Cool Model).  
4-5  
T--298  
INDEX  
A
I
Indoor Thermostat , 3-3  
Air Handling System , 3-8  
Air Sweep Removal, 3-3  
Air Sweep Switch , 3-2  
INTRODUCTION, 1-1, 4-1  
L
LCD DISPLAY, 3-15, 3-16  
C
Leaks, 3-1  
Capacitor Testing, 3-9  
Capacitor Testing and Replacement, 3-9  
Ceiling Grill -- Ducted, 3-4  
Ceiling Grill -- Free Blow, 3-1  
Ceiling Panel -- Free Blow, 3-2  
CEILING UNIT -- DUCTED SYSTEMS, 3-4  
CEILING UNIT -- FREE BLOW , 3-1  
Cleaning, 3-1  
M
Main Pcb Board, 3-5  
Master Control Switch, 3-2  
Motor , 3-7  
Mounting, 3-1  
P
Compressor , 3-6, 3-13  
Painting, 3-1  
Condenser Fan, 3-7  
PCB Display , 3-5  
Control Box -- Ducted, 3-4  
Control Box -- Upper Unit, 3-6  
Controls, 3-1  
PREVENTATIVE MAINTENANCE, 3-1  
R
Cool Only Thermostat, 3-15  
REFRIGERANT CYCLE, 1-9, 1-10  
D
S
Design Change, 1-1  
Serial Number, 1-1  
SERVICE -- GENERAL, 3-1  
SERVICE -- UPPER UNIT -- LOW PROFILE, 3-10  
SERVICE AND MAINTENANCE, 3-1  
START--UP, 1-9  
E
Evaporator Blower Wheel, 3-8  
Exterior Cover, 3-5, 3-10, 3-15  
T
THERMOSTAT INSTALLATION AND START--UP IN-  
F
STRUCTIONS (WALL MOUNTED), 3-15  
Filter Removal -- Free Blow, 3-1  
Filter Removal -- Ducted, 3-4  
Fuse Removal -- Ducted, 3-5  
TROUBLESHOOTING, 2-1, 2-3  
U
Upper Scroll Assembly, 3-7, 3-10, 3-11, 3-12, 3-13  
H
W
Heat Strip, 3-3  
Heat/Cool Thermostat, 3-15  
WIRING SCHEMATICS, 4-1  
T--298  
Index -1  
Carrier Transport Air Conditioning  
50 Grumbacher Road  
York PA 17402 USA  
Tel: 1--800--673--2431  
Fax: 1--717--764--0401  
Carrier Transicold Division,  
Carrier Corporation  
Transport Air Conditioning Group  
P.O. Box 4805  
Syracuse, N.Y. 13221 U.S A  
A member of the United Technologies Corporation family. Stock symbol UTX  
©2006 Carrier Corporation D Printed in U. S. A. 0606  

Buhler I User Manual
Chauvet Baby Accessories MEGATRIX User Manual
Danby DPAC6507 User Manual
Danby SILHOUETTE DPAC120061 User Manual
Epson All in One Printer CX7000F User Manual
Goodman Mfg Co LP Air Conditioner RS6300011 User Manual
Hand Held Products Quick Check Bar Code Verifiers 800 User Manual
HP Hewlett Packard Hewlett Packard Printer X22LED User Manual
HP Hewlett Packard Hp Scanjet Enterprise Flow 7000 S2 Sheet Feed Scanner L2730BBGJ User Manual
HP Hewlett Packard LaserJet M5035x MFP User Manual