OMNIZONE™
50BV020-064, 50XJ064-104
Indoor Self-Contained
Remote Air-Cooled and Water-Cooled, VAV Systems
18 to 100 Nominal Tons
Controls Operation and
Troubleshooting
When working on this equipment, observe precautions in
CONTENTS
the literature; on tags, stickers, and labels attached to the equip-
ment, and any other safety precautions that apply. Follow all
safety codes. Wear safety glasses and work gloves. Use care in
handling, rigging, and setting this equipment, and in handling
all electrical components.
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
MAJOR SYSTEM COMPONENTS . . . . . . . . . . . . . . . 1 -7
Comfort Controller Processor (PCB1) . . . . . . . . . . . . 1
Comfort Controller I/O Module (PCB2). . . . . . . . . . . . 2
Comfort Controller I/O Module (PCB3). . . . . . . . . . . . 2
Local Interface Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PCB Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Control Module Communication. . . . . . . . . . . . . . . . . . 2
Carrier Comfort Network Interface. . . . . . . . . . . . . . . . 4
Optional and Field-Installed
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation
and service. There may be more than one disconnect
switch. Tag all disconnect locations to alert others not to
restore power until work is completed.
Accessory Sensors/Devices . . . . . . . . . . . . . . . . . . . 4
Wiring Control Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CONTROLS AND FUNCTIONS. . . . . . . . . . . . . . . . . 8-15
Using the Local Interface Display . . . . . . . . . . . . . . . . 8
Automatic Run Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power Up the LID Display . . . . . . . . . . . . . . . . . . . . . . . 12
Log On to the LID Display . . . . . . . . . . . . . . . . . . . . . . . 12
Change the Default Password . . . . . . . . . . . . . . . . . . . 12
Set the Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Configure Schedules. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Program Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Check System Parameters . . . . . . . . . . . . . . . . . . . . . . 14
Display Alarm History . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Configure Custom Programming Selections . . . . 14
Set Controller Address . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Log Off from Controller . . . . . . . . . . . . . . . . . . . . . . . . . 15
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-26
Occupancy Determination. . . . . . . . . . . . . . . . . . . . . . . 16
Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Sequence of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . 16
Diagnostic Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
50XJ Variable Frequency Drive Control. . . . . . . . . . 19
50BV Variable Frequency Drive Control . . . . . . . . . 22
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from rec-
ommended procedures. Any short-to-ground of the con-
trol board or accompanying wiring may destroy the
electronic modules or electrical components.
GENERAL
This publication contains Start-Up, Controls Operation, and
Troubleshooting information for the 50BV,XJ units. These
OMNIZONE™ packaged units are self-contained, water-
cooled or remote air-cooled indoor units for use in VAV
(variable air volume) applications. Units are equipped with
Comfort Controller 6400 (CC6400) system controls. Refer to
the unit Installation Instructions for unit layout.
MAJOR SYSTEM COMPONENTS
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 27-29
Run Test Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . 27
Forcing and Clearing and Input or Output . . . . . . . 27
Standard Diagnostic Features,
Comfort Controller Processor (PCB1) —
The central processing unit for the OMNIZONE system
control is the Comfort Controller 6400. The Comfort Control-
ler provides general purpose HVAC (heating, ventilation and
air conditioning) control and monitoring capability in a stand-
alone or network environment using closed-loop, direct dig-
ital control. The Comfort Controller 6400 has been pre-pro-
grammed to work in either stand-alone or CCN (Carrier Com-
fort Network) system installations.
The CC6400 processor is designed to provide heating and
cooling control, loop control, scheduling, and custom program-
ming. The main processor provides 16 field points (8 input and
8 output). Additional points are provided by the I/O modules
described on page 2. Table 1 lists the control inputs and outputs
for all CC6400 modules.
Alarm and Warning Lights . . . . . . . . . . . . . . . . . . . . 28
APPENDIX A — WIRING DIAGRAMS . . . . . . . . . 30-42
APPENDIX B — CONTROL SCREENS . . . . . . . . 43-64
Display Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Configuration Screens . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Maintenance Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location. Only trained, qualified installers and
service mechanics should install, start up, and service this
equipment.
Specifications for the Comfort Controller 6400 may be
found in the Comfort Controller literature.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 535-00137 Printed in U.S.A. Form 50BV,XJ-2T Pg 1 2-04 Replaces: 50BV,XJ-1T
Book 1
1
Tab 2a 2b
Table 1 — Control Inputs and Outputs
CONTROLLER I/O NO.
DIP SWITCH SETTINGS
Switch No. and Position
DESCRIPTION
ABBREV.
TYPE
Water Econ. Units Air Econ.Units
Inputs
SW2
SW3
SW1
Addr = 1-16
Main Controller (PCB1)
Supply Air Temperature
VFD Duct Static Pressure
SAT
DSP
Analog; 10K MCI
4-20mA; Internally Powered
1
2
1
2
1
2
Up
Up
1
2
Down
Up
1
2
Up
Down
COL/Safeties —
(Comprs.Status; Resister Bd.)
CMP MUX Analog; 0-10VDC
3
3
3
Up
3
Down
3
Down
Fire Alarm/Shutdown
Condenser Waterflow Switch
Remote Occupancy
Duct High Static Limit Switch
Entering Water Temp. Sensor
I/O Board (PCB2)
FSD
Switch closure
Switch closure
Switch closure
Switch closure
Analog; 5K
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
Up
Up
Up
Up
Up
4
5
6
7
8
Down
Down
Down
Down
Down
4
5
6
7
8
Down
Down
Down
Up
CDWF
RMTOCC
DHS
EWT
Up
Addr = 17-32
Mixed/Return Air Sensor
Filter Status Switch
(Dirty Filter Detect)
MAT/RAT
FLTS
Analog; 10K MCI
Switch closure
1
2
1
2
1
2
Up
Up
1
2
Down
Down
1
Up
2
Down
Phase Loss Monitor
External reset
Water Econ. FreezeStat
Differential Enthalpy
Space Zone Sensor(s)
VFD Bypass Enable
PHASE
RESET
FREEZE
ENTH
SPT
BYPASS
Switch closure
0-10VDC Externally Powered
Switch closure
Switch closure
Analog; 10K MCI
Switch closure
3
4
5
—
6
7
3
4
—
5
6
7
3
4
5
5
6
7
Up
Up
Up
Up
Up
Up
3
4
5
5
6
7
Down
Down
Down
Down
Down
Down
3
4
5
6
7
8
Down
Down
Up
Down
Up
Up
Refrigerant Pressure
(Compr.#1)
PRES
4-20mA; Internally Powered
8
8
8
Up
8
Up
—
—
I/O Board (PCB3)
Tower Sump Temp.
Building Pressure
Leaving Water Temp.
Indoor Air Quality
Indoor relative Humidity
Outside Air Temp.
Unassigned
Addr = 33-48
TWRTEMP Analog; 10K MCI
1
2
3
—
—
—
—
—
1
2
3
4
5
6
—
—
1
2
3
4
5
6
—
—
Up
Up
Up
Up
Up
Up
—
1
2
3
4
5
6
—
—
Up
Down
Up
Down
Down
Up
1
2
3
4
5
6
7
8
Up
Down
Down
Down
Down
Up
BSP
LWT
IAQ
4-20mA; Internally Powered
Analog; 10K MCI
4-20mA; Internally Powered
IRH
OAT
4-20mA; Internally Powered
Analog; 10K MCI
—
—
—
—
—
—
Up
Up
Unassigned
—
CONTROLLER I/O NO.
DIP SWITCH SETTINGS
Switch No. and Position
DESCRIPTION
ABBREV.
TYPE
Water Econ. Units Air Econ.Units
Outputs
SW4
SW5
SW6
Main Controller (PCB1)
Compressor #1 Relay
Compressor #2 Relay
Compressor #3 Relay
Compressor #4 Relay
VFD On/Off
VFD Speed Control
Alarm Pending
Service Required
I/O Board (PCB2)
Ventilation Output
Terminals Occupied
CMP1
CMP2
CMP3
CMP4
SF
SPEED
ALARM1
ALARM2
24VDC Discrete
24VDC Discrete
24VDC Discrete
24VDC Discrete
24VDC Discrete
4-20mA modulating
24VDC Discrete
24VDC Discrete
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Either
Either
Either
Either
Either
Down
Either
Either
1
2
3
4
DO
—
DO
DO
DO
—
—
—
—
—
—
—
1
2
3
4
DO
AO
DO
DO
VENTOUT 24VDC Discrete
OCCTRM 24VDC Discrete
1
2
1
2
1
2
Either
Either
1
2
DO
DO
—
—
2-Position\
ECONO
ECONO
MODVLV
4-20mA modulating
4-20mA modulating
4-20mA modulating
3
—
4
3
3
4
Down
Down
Down
3
3
4
AO
AO
AO
—
—
—
Reverse Operation Valve
Economizer Damper
Modulating Valve Econ./
Head Pressure Control
3
4
Hot Water Coil Valve Control
Heat Interlock Relay
VFD Bypass Start
VAV Terminals Open
I/O Board (PCB3)
HWV
HIR
BPSS
4-20mA modulating
24VDC Discrete
24VDC Discrete
5
6
7
8
5
6
7
8
5
6
7
8
Down
Either
Either
Either
—
—
—
—
1
2
3
4
AO
DO
DO
DO
DAMPERS 24VDC Discrete
Electric Heat Control — Stage #1 HEAT1
Electric Heat Control — Stage #2 HEAT2
Electric Heat Control — Stage #3 HEAT3
Electric Heat Control — Stage #4 HEAT4
24VDC Discrete
24VDC Discrete
24VDC Discrete
24VDC Discrete
24VDC Discrete
24VDC Discrete
4-20mA modulating
24VDC Discrete
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Either
Either
Either
Either
Either
Either
Down
Either
1
2
3
4
DO
DO
DO
DO
—
—
—
—
Water Pump Request
Tower Request
Modulating Exhaust Fan
External Dehumidification
PUMP
TOWER
EXH
—
—
—
—
1
2
3
4
DO
DO
AO
DO
DEHUM
LEGEND
AO
—
—
—
—
—
Analog Output
DO
Discreet Output
MCI
VAV
VFD
Precon Type II Thermistor
Variable Air Volume
Variable Frequency Drive
3
Table 2 — Communication Cable Recommendations
MANUFACTURER
Alpha
PART NUMBER
2413 or 5463
A22503
STATUS
American
Belden
Columbia
8772
02525
RED
(POWER)
GREEN
(IO BUS
COMMUNICATIONS)
REMOTE OCCUPANCY CONTROL (PCB1) — This con-
trol is a field located switch, controller or timer input which,
when activated, tells system when to switch from Unoccupied
to Occupied mode.
YELLOW
(CNN BUS
COMMUNICATIONS)
When in Occupied mode, the unit turns on the supply fan
and controls supply fan speed to maintain a duct static set point
measured at the Duct Static Pressure Sensor (DSP). The unit
operates to provide conditioning to a set point. When in
Unoccupied mode, the unit provides no cooling/heating, or
controls to a ‘setback’ set point.
FIRE ALARM (PCB1) — The fire alarm is a control voltage
input to the 50XJ unit, which causes the controller to shut the
system down in the event of a fire.
CONDENSER WATER FLOW SWITCH (50XJ
PCB1) — This thermal dispersion type flow switch if factory
installed, is located in the unit waterline to ensure that there is
waterflow before allowing the unit to start the compressor(s). If
no flow is detected, then compressor operation and economizer
cooling is avoided until waterflow is again detected. An
warning light (yellow) is provided during this state.
HEAT INTERLOCK OUTPUT (50XJ PCB2) — This output
is activated whenever heating is activated, commanding the
VAV dampers to operate in heating control mode.
Fig. 1 — CC6400 Control Module LEDs
Carrier Comfort Network Interface — The 50BV,XJ
units can be connected to the CCN (Carrier Comfort Network)
if desired. System elements are connected to the communica-
tion bus in a daisy chain arrangement. The negative pin of
each system element’s communication connector must be
wired to the respective negative pins, and positive pins on each
component must be connected to respective positive pins. The
controller signal pins must be wired to the signal ground pins.
Wiring connections for CCN must be made at the 3-pin plug.
At any baud rate (9600, 19200, 38400 baud), the number of
controllers is limited to 239 devices maximum. Bus length may
not exceed 4000 ft, with no more than 60 total devices on
any 1000-ft section. Optically isolated RS-485 repeaters are
required every 1000 ft.
NOTE: In order to this output to function, the Terminal
Occupied output must also be on.
TERMINAL OCCUPIED (50XJ PCB2) — Terminal Occu-
pied is activated to command VAV dampers to control to the
cooling set point. Terminal Occupied must be on along with
Heat Interlock for heating set point control to function.
EXTERNAL RESET INPUT (50XJ PCB2) — This modu-
lating input (0 to 10 vdc) allows remote adjustment (upward) of
the Supply Air Temperature (SAT) sensor set point. The default
External Reset Input setting is 55 F. This variable input can
raise the set point by up to 20 F for a full-range input signal, or
to any point in between.
WATER ECONOMIZER COIL (50XJ PCB2) — This factory-
installed option contains a water-to-air coil, two (2) electronic
motorized water valves, and related piping. Control of the water
economizer also requires a Mixed/Return Air Temperature
Sensor, a Condenser Water Inlet Temperature Sensor and an
Economizer Freezestat safety switch.
The electronic motorized water valves are each controlled
by the unit controller via separate 4 to 20 mA variable signals
to define variable valve position.
The Mixed/Return Air Sensor (MA_RA) is an air
temperature sensor located in the unit, between economizer
coil and evaporator.
The Condenser Water Inlet Temperature Sensor (CWT) is
located at the unit water inlet connection. This sensor receives
input power from the unit main controller and provides a linear
variable 1 to 5 vdc signal back to the controller. The full
temperature range is 32 to120 F.
The 50XJ units can be connected to two types of building
water systems: variable and fixed or constant flow control. In
either case, the economizer water valves are opened whenever
there is a call for Cooling and the Inlet Water Temperature is
colder than the Econ Start Set Point in the custom configuration.
NOTE: Carrier device default is 9600 baud.
The CCN Communication Bus wiring is field-supplied and
field-installed. It consists of shielded three-conductor cable
with drain (ground) wire. The cable selected must be identical
to the CCN Communication Bus wire used for the entire
network. See Table 2 for cable recommendations.
NOTE: Conductors and drain wire must be at least 20 AWG
(American Wire Gage), stranded, and tinned copper.
Individual conductors must be insulated with PVC, PVC/
nylon, vinyl, Teflon, or polyethylene. An aluminum/
polyester 100% foil shield and an outer jacket of PVC,
PVC/nylon, chrome vinyl, or Teflon with a minimum
operating temperature range of –20 C to 60 C is required.
The communication bus shields must be tied together at
each system element. If the communication bus is entirely
within one building, the resulting continuous shield must be
connected to ground at only one single point. If the communi-
cation bus cable exits from one building and enters another
building, the shields must be connected to the grounds at a
lightning suppressor in each building (one point only).
Optional and Field-Installed Accessory Sensors/
Devices — The 50XJ unit can be ordered with options and
accessories that add functionality and control. These options
and accessories are controlled by the CC6400 system as
described below.
NOTE: The CC6400 Control software includes all PCB1
functions, and most of the sensors/devices associated with
those functions are factory installed. However, some PCB1
sensors/devices must be field-connected to the proper terminal.
PCB2 devices are field-installed accessories. The CC6400
software includes these functions, but the actual sensor/device
must be installed and wired in the field. PCB3 is an accessory
control module. All PCB3 sensors/devices and software are
field-installed.
4
Dependencies — Water Economizer option is enabled, and
Fan is On, and Inlet Water Temperature is below set point; or
from “Remote Scheduler,” or from “Remote Linkage.”
Economizer mode is switched to Off or no start if: there is
no condenser waterflow, Fire Input is On, Fan is not On, or Un-
occupied mode is On.
Variable Waterflow Systems — Whenever water economizer
is off, the economizer flow control valve is fully closed, and the
reverse flow valve directly to the condenser is fully open. Upon
engagement of the water economizer, the economizer flow con-
trol valve shall be controlled to maintain the MA_RA located
between the economizer coil and the DX cooling coil, at a tem-
perature near the supply air set point. The the reverse flow valve
will be controlled in reverse of the economizer flow control
valve’s position. The following formula is an example: Reverse/
Head Press Ctrl output = 100 – two-position/Econo output.
Constant Building Waterflow Systems — Constant waterflow
configurations use two (2) water valves, only one of which is
in the main water supply pipe. The second valve is located in a
bypass pipe to the main outlet water pipe branched off of the
supply pipe immediately ahead of the first valve. This valve is
same type, but normally closed and is controlled in unison with
the first valve, but opposite position, such that the total opening
of the 2 valves always equals 100%.
VFD BYPASS (50XJ PCB2) — The VFD Bypass option
provides backup for the VFD Drive in VAV units. It uses a
manually operated rotary switch, which includes a series of
high voltage contacts. The bypass is a direct input to the unit
controller, and will be activated via a switch on the unit front
panel. When manually activated, the rotary switch takes the
VFD out of the fan power circuit and provides the 3-phase
power directly to the fan motor, running it at constant speed. A
low voltage control circuit ensures that the unit controller pro-
vides a signal to allow all VAV dampers to open fully before
the fan is turned on (at constant/full speed). A blue indicator
light located on the front of the unit indicates that the VFD By-
pass is active. A High Duct Static Switch (HDS) shuts the fan
down if duct static exceeds a maximum setting.
When the unit is off, both valves are closed.
Constant Waterflow Systems — Control of the economizer
flow control valve is same as for variable waterflow systems.
Control of the reverse flow control valve position will inversely
track the economizer flow control valve, such that the total sum
of the two valves open positions always equals 100%. The only
difference between the variable waterflow system and the
constant waterflow system is that for the constant flow system
when the unit is off, the economizer valve will be closed and
the reverse flow control valve will be open.
WATER ECONOMIZER COIL (50BV) — For the 50BV
unit, this factory-installed option contains a water-to-air coil, a
two-position diverting valve, and related piping. The water econ-
omizer is controlled by an Aquastat and a return-air thermostat.
VENTILATION OUTPUT (50XJ PCB2) — The ventilation
output is controller output signal (available for field connection)
to a field-supplied ventilation damper(s). This signal is activated
whenever the unit is in the occupied mode.
SPACE TEMPERATURE SENSOR (50XJ PCB2) — A field-
supplied Carrier space temperature sensor is required to
maintain space temperature in sensor mode.
SUPPLY AIR RESET (50XJ PCB2) — Supply air temperature
set point may be reset using either the SPT or MA_RA.
HEATING COILS AND VALVE (50XJ PCB2) — Water or
steam heating options are factory installed. Each includes a
motorized, variable control water or steam flow control valve,
which can be factory supplied for field installation outside the
unit. Installed in the water or steam inlet pipe, this valve is
wired to the unit main controller and operates on a 4 to 20 mA
signal. A Heating mode PID control is needed to control the
valve position (i.e., coil heating capacity) variably between 10
and 100%. The PID will control a set point to + 1° F; for VAV
Units this set point is at the Supply Air Temperature Sensor, or
as communicated from a remote thermostat.
SUPPLY AIR RESET (50BV) — Reset is provided by a
field-installed temperature sensor.
EXHAUST FAN CONTROL OUTPUT (50XJ PCB2) — This
output is activated whenever the unit is in the Occupied mode.
This is a modulating output that controls based on the Building
Pressure Input set point.
CONDENSER WATER PUMP/WATER TOWER (50XJ
PCB2) — This output (provided for field connection) is used
to control condenser water flow. Either an On/Off signal or a
variable output may be required for this feature.
HEAD PRESSURE CONTROL (50XJ PCB2) — Head Pres-
sure Control is required for unit installations that will
experience entering condenser water temperatures of 55 F or
lower.
PHASE LOSS/REVERSAL PROTECTION SWITCH
(50XJ PCB2) — This switch monitors VFD/Fan Motor sup-
ply leads to detect phase loss or reversal. If the switch detects
improper phasing, an input is sent to the unit controller, which
shuts the unit down. After a time delay, the controller attempts
to restart the unit.
A phase loss/reversal switch may be installed in the unit to
detect over/under voltage conditions and phase loss or reversal.
When the switch opens, the controller outputs are forced to off
with Safety forces, the alarm output will close and the red
alarm light will be lit. A system alarm will be generated and
displayed on the unit keypad. Unit reset is automatic when the
voltage and power phases have been restored.
FREEZE THERMOSTAT (FREEZSTAT) (50XJ PCB2) — The
Economizer Freezestat, used in conjunction with an optional
water economizer coil or heating coil, is a factory installed
averaging (capillary tube) air temperature sensor positioned in
the unit inlet airstream.
If the freeze protection switch contacts open the ventilation
request output will be closed for 15 minutes and the warning
light will light. If the freeze protection switch contacts are still
open after 15 minutes the supply fan will be stopped, all
compressor cooling will stop, the economizer valve will open
to 100%, the pump request output will remain on, and the
alarm light will light. This will maintain condenser water flow
through the coil to prevent freezing the coil while stopping all
other operations that could have contributed or will be affected
NOTE: Head Pressure Control is not needed or used in
conjunction with a Water Economizer. A refrigerant pres-
sure transducer will monitor head pressure on compressor
circuit 1, allowing the unit main controller to regulate water
flow rate in the main water line entering the unit; i.e., flow
to all condensers. (Water header design to the condensers
will be optimized such as to provide relative flow rates to
each condenser based on its compressor capacity, enabling
successful waterflow control at the main entering pipe.)
There are two possible water valving configurations, as
outlined below.
Pressure transducer input is factory installed in the
discharge line of compressor circuit 1. It is provided 5 vdc by
the unit main controller and returns a signal 1 to 5 vdc linearly.
The sensor’s range is 0 to 550 psig.
Water Valve(s) Control
Variable Building Waterflow Systems — Variable waterflow
configurations use only one water valve in the main water
supply pipe. The factory installed valve is a normally open
motorized variable control type. The valve is controlled by a
4 to 20 mA signal from the main unit controller using the
Reverse/Head Press Ctrl output, which modulates to maintain
the head pressure set point (Setpoint 04).
5
by the freeze condition. Unit reset is automatic when the
contacts on the freeze protection switch close again. The
contacts on the freeze protection switch open below 37 F.
TOWER SUMP TEMPERATURE SENSOR (50XJ
PCB3) — This sensor is used for monitoring (only) the tower
sump temperature.
LEAVING WATER TEMPERATURE SENSOR (50XJ
PCB3) — This sensor is used for monitoring (only) the leav-
ing water temperature.
BUILDING STATIC PRESSURE SENSOR (50XJ
PCB3) — This sensor is used to control both the speed of the
building exhaust fan and the building static pressure.
INDOOR AIR QUALITY (CO2) SENSOR (50XJ
PCB3) — This sensor monitors CO2 levels.
INDOOR RELATIVE HUMIDITY SENSOR (50XJ
PCB3) — This sensor monitors and controls the humidity
control relay.
OUTDOOR AIR TEMPERATURE SENSOR (50XJ
PCB3) — This sensor is used to monitor outdoor air and
broadcast the value over the Carrier Comfort Network (CCN).
STAGE HEAT RELAYS (50XJ PCB3) — These relays con-
trol up to four stages of electric heat, or other heating methods.
Fig. 2A — Field Terminal Blocks for 50XJ Unit
PUMP REQUEST RELAY (50XJ PCB3) — This relay turns
on a tower pump when requested.
TOWER REQUEST/CONTROL RELAY (50XJ PCB3) —
This relay is used to activate a tower fan.
BUILDING EXHAUST FAN SPEED CONTROL (50XJ
PCB3) — This output controls building exhaust fan speed.
HUMIDITY CONTROL RELAY (50XJ PCB3) — This relay
controls a humidifier or dehumidification device.
Wiring Control Devices — Standard controls for the
50XJ require no field-wiring. Standard 50XJ controls include:
Supply Air Temperature (SAT), Duct Static Pressure (DSP),
Duct High Static Limit Switch (DHS), Filter Status Switch
(FLTS), Entering Water Temperature (EWT), Compressor Sta-
tus (CSMUX), Supply Fan Start/Stop (SF), Supply Fan Speed
(SPEED), and Mixed/Air Return/Air sensor (MA_RA).
Fig. 2B — Field Terminal Block for 50BV Unit
NOTE: The MA_RA sensor will be located in the return air
steam if the unit does not have a water economizer, and in
the mixed airstream if the unit is equipped with a water
economizer.
For the 50BV unit, standard controls include: Duct Static
Pressure (DSP), Duct High Static Limit Switch (DHS), Com-
pressor Status (CSMUX), Supply Fan Start/Stop (SF), and
Supply Fan Speed (SPEED).
•
•
To determine the average temperature of the space being
served.
To determine supply-air temperature reset, occupied
heating, unoccupied heating and cooling (refer to
Sequence of Operation in the Start-Up section.).
To wire the sensor, perform the following (see Fig. 3).
Identify which cable is for the sensor wiring.
1. Strip back the jacket from the cable for at least
For the 50XJ unit, optional controls will be wired to the
field terminal blocks (TB5 and TB6) provided. Refer to
Fig. 2A and the descriptions below.
For the 50BV unit, optional controls are wired to field
terminal block TB2 as shown in Fig. 2B.
EXTERNAL 0 TO 10 VOLT DC RESET SIGNAL (RESET)
(50XJ PCB2) — This field-supplied 0 to 10 vdc signal is used
to reset the 50XJ supply-air temperature. The controller will
scale the signal to provide 0 reset at 0 volts and 20 degrees of
reset at 10 volts. Wire the positive of the signal to the RESET
terminal and the negative to the C or common terminal.
SUPPLY AIR RESET (50BV) — Use a 5k ohm sensor
installed at the Entering Water Temperature sensor (EWT)
location on PCB1. For space temperature averaging, two 10k
ohm Space Temperature Sensors (SPT) can be wired in parallel.
1
3 inches. Strip /4-in. of insulation from each conduc-
tor. Cut the shield and drain wire from the sensor end
of the cable.
2. Wire the sensor to the SPT and C terminals on the field
terminal block (TB5). A typical 10K thermistor such
as the 33ZCT55SPT sensor may be used. If the SPT
sensor is not installed and the MA_RA (mixed air/
return air) sensor is configured for return air, the 50XJ
unit will use this sensor to control supply air reset,
occupied heat, and unoccupied heating and cooling
See Fig. 4 for space temperature sensor averaging.
HOT WATER OR STEAM VALVE (HWV) (50XJ
PCB2) — The HWV terminal supplies the positive signal to
control a 4 to 20 mA hot water or steam valve for occupied and
unoccupied heat. Connect the common side of the valve to the
C terminal or an equipment ground.
SPACE TEMPERATURE SENSOR (50XJ PCB2) — The
space temperature sensor (33ZCT55SPT) is used in the follow-
ing cases:
•
When using the optional water economizer and not using
Carrier’s ComfortID™ System.
6
AIR TERMINALS AND FRESH AIR DAMPER (50XJ
PCB2) — The VAV Terminal Open (TRMOP), Ventilation
Output (VENTR), VAV Terminals Control (TRMCT), and
Heat Interlock Relay (HIR) terminals provide dry contacts to
command the VAV terminals open; a ventilation damper open;
VAV terminals to control to their cooling set points; and VAV
terminals to control to their heat set points, respectively.
REMOTE OCCUPANCY (ROCC) (TB2 50BV, TB6
50XJ) — The 50XJ,BV unit may be commanded by a remote
control system or a twist timer to become occupied and run
when a set of dry contacts close. In order for this to occur, wire
the contacts to ROCC and C.
1
2
4
5
6
3
RED(+)
WHT(GND)
CCN COM
BLK(-)
SEN
SW1
SMOKE DETECTOR/FIRE ALARM SHUTDOWN (FSD)
(TB2 50BV, TB6 50XJ) — To allow a smoke detector to shut
the 50XJ,BV unit down, remove the jumper from FSD to C
and wire these terminals to a set of normally closed contacts on
the smoke detector.
BRN (GND)
BLU (SPT)
SENSOR WIRING
ALARM (ALARM) AND WARNING (WARN) OUTPUTS
(TB2 50BV, TB6 50XJ) — Two dry contacts output a dis-
crete signal when the alarm and warning lights on the display
are lit. To pick up the alarm output signal, wire between the
ALARM and ALM-CM terminals. To pick up the warning
output signal, wire between the WARN and ALM-CM
terminals.
Fig. 3 — Space Temperature Sensor
Typical Wiring (33ZCT55SPT)
RED
BLK
RED
BLK
J6
6
RED
BLK
RED
BLK
RED
BLK
7
SENSOR 1
SENSOR 2
SENSOR 3
SENSOR 4
SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION
J6
6
RED
BLK
RED
RED
BLK
BLK
7
SENSOR 3
SENSOR 1
SENSOR 2
RED
BLK
RED
BLK
SENSOR 6
SENSOR 4
SENSOR 5
LEGEND
Field Wiring
RED
BLK
RED
BLK
SENSOR 8
SENSOR 9
SENSOR 7
SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION
Fig. 4 — Space Temperature Averaging
7
Table 4 — Operative Keys
CONTROLS AND FUNCTIONS
Using the Local Interface Display — The Local
Interface Device (LID) is a CCN operator interface that gives
the user the capability to view and modify all configuration and
service data for the CC6400 control system. The LID also
allows the user to override all point display and maintenance
data.
MENU STRUCTURE — The LID operates on a hierarchy of
four levels (menus).
The top level contains the LID’s major functions. Each
function has a corresponding key on the LID. For an explana-
tion of each function key, refer to Table 3.
The second level separates the major functions (items) into
types with corresponding type numbers that can be used for
quick access.
The third level gives the user the capability to access each
occurrence of an item. For example, the application may
require two DO (Discreet Output) — Analog Comparison
algorithms. Thus, the CC6400 Controller would have two
occurrences of the DO — Analog Comparison algorithm.
The fourth level gives the user the capability to access main-
tenance and configuration data associated with the selected
occurrence of the item.
DEFAULT SCREEN — Figure 5 shows the LID. The LID’s
screen provides the user with the 24-character controller name
and the controller’s current time, date, and alarm status. This
screen appears when the LID is powered up and communicat-
ing with the controller or there is no keyboard activity for
10 minutes.
OPERATIVE
KEYS
USE
Clear — performs three operations:
• Cancels a data entry before the user
presses Enter, thus leaving the current
value unchanged.
• Returns a forced point to automatic
control.
• Redisplays the previous menu level.
Enter — performs two operations:
• Selects the displayed item, thus displaying
either its maintenance or configuration
data, depending on whether the user is in
the Status mode or the Edit mode.
• Accepts the value entered in a configuration
decision as new configuration data or as a
force.
CLEAR
ENTER
Down arrow — displays the next configured
item or decision. When the last configured
item or decision is displayed, the LID
re-displays the first configured item or
decision. For example, when the user presses
the down arrow key while viewing the last
configuration decision of an algorithm, the LID
re-displays the first configuration decision.
Up arrow — Displays the previous configured
item or decision.
Table 5 — Numeric Keys
OPERATIVE
KEYS
USE
-
Numeric keys
Performs two operations:
• Separates items, such as an algorithm from
its occurrence or hours from minutes.
• Serves as a decimal point in numeric values.
KEYPAD AND DISPLAY — The LID consists of a keypad
with 8 function keys, 4 operative keys, 12 numeric keys (0 to
9,., and -) and a two-line, alphanumeric liquid crystal display
(LCD). Each line on the LCD can display up to 24 characters.
See Fig. 5. Table 4 defines the purpose of the LID’s operative
keys. Table 5 defines the purpose of the LID’s numeric keys.
Performs two operations:
• Negates the value of numeric keys.
• Clears current data entry value any time it is
not the first key pressed during the data
entry sequence.
Table 3 — LID Function Keys
VIEWING MODES — The user can view items in either the
Status (maintenance) mode or the Edit (configuration) mode.
OPERATIVE
USE
KEYS
Status Mode — When the user first powers up the LID, it
displays the CC6400 controller items in Status (maintenance)
mode. The user may view the current value or status of an item
in Status mode without actually logging on to the Controller.
Knowing the current values or status of items can be useful
when troubleshooting. For example, the user could determine
if a point was forced.
Status — gives access to maintenance
values and configuration data for points.
Alarm — gives access to maintenance
and configuration data for alarms.
History — gives access to maintenance
and configuration data for history system
functions.
NOTE: Not all items have maintenance data. If the item you
select does not have maintenance data, the LID will display
“No maintenance.”
Accessing Items in Status Mode — The user can access
maintenance data in Status mode in two ways:
Service — gives access to maintenance
and configuration data for service system
functions.
Setup — gives access to configuration
data for setup system functions.
Schedule — gives access to maintenance
and configuration data for schedules.
Algorithm — gives access to maintenance
and configuration data for AO, DO, and global
algorithms. It also gives access to BEST ++™
custom programs.
•
Pressing the appropriate function key (i.e.,
)
ALRM
once to access a category (i.e., alarms) and then continu-
ing to press that key ( ) to scroll through all the
ALRM
items in that category (i.e., Limit Alarm, Set point
Alarm, Discrete Alarm, First Out Alarm, Runtime
Edit — gives the capability to switch from
Status mode to Edit (configuration) mode for
the selected item.
Alarm, and Number of Starts Alarm). Press
display the first maintenance decision.
to
ENTER
LEGEND
AO
—
Analog Output
NOTE: Scrolling by repeatedly pressing the function key
displays the name of all the items in that category, whether
or not they are actually configured. Scrolling by pressing
the up or down arrow displays only the configured items
within that category.
DO — Digital/Discreet Output
8
•
Pressing the appropriate LID numeric key (i.e., 2) and
the appropriate function key (i.e., ALRM ) to directly
access an item without having to scroll through all the
Set point Alarm, Discrete Alarm, First Out Alarm,
Runtime Alarm, and Number of Starts Alarm).
NOTE: Scrolling by repeatedly pressing the function key
displays the name of all the items in that category, whether
or not they are actually configured. Scrolling by pressing
the up or down arrow displays only the configured items
within that category.
items in that category. Press
maintenance decision.
to display the first
ENTER
Edit Mode — Because the LID first displays items in Status
mode when it is powered up, the user must log on to the con-
nected CC6400 Controller and press the
switch to Edit mode.
•
Pressing the appropriate LID numeric key (i.e., 2),
key to
EXPN/EDIT
the appropriate function key (i.e.,
EXPN/EDIT
to scroll through all the items in that category.
), and
ALRM
to directly access an item without having
While in Edit mode, the user can change the configuration
of items. For example, the user could change the value of an al-
gorithm’s configuration decision.
NOTE: Not all items have configuration data. If the item
selected does not have configuration data, pressing the
EXPN/EDIT
“No configuration.”
QUICK ACCESS IN EITHER STATUS OR EDIT
MODE — Use Table 6 as a reference to directly access
CC6400 Controller items using a LID in either Status or Edit
mods. For example, to access maintenance data for the AO —
key will have no effect. The LID will display
Heating VAV algorithm, press
,
, and
. To
ENTER
6
ALGO
access configuration data for the AO (Analog Output) —
Heating VAV algorithm, press ,
Accessing Items in Edit Mode — The two ways to access
items in Edit mode are the same as in Status mode, except for
,
,
6
ALGO EXPN/EDIT
and
. If the database consisted of two AO — Heating
ENTER
VAV algorithms, to access the second one, press
an additional step — pressing the
key.
EXPN/EDIT
The user can access configuration data in Edit mode in two
ways:
,
(deci-
6
.
mal),
,
,
, and
ENTER
.
2
ALGO EXPN/EDIT
•
Pressing the appropriate function key (i.e.,
to access a category (i.e., alarms), pressing
and then continuing to press that key (
ALRM
through all the items in that category (i.e., Limit Alarm,
) once
ALRM
EXPN/EDIT
) to scroll
OMNIZONE VPAC
12:00
02-06-04
EXPN
EDIT
TEST
SRVC
STAT
SET
2
5
8
0
3
6
1
4
7
–
ALRM
FUNCTION
KEYS
FUNCTION
KEYS
HIST
ALGO
SCHD
CLEAR
9
.
OPERATIVE
KEYS
OPERATIVE
KEYS
ENTER
NUMERIC KEYS
Fig. 5 — Local Interface Display (LID)
9
Table 6 — Quick Access Chart
LID FUNCTION KEYS
History
(HIST)
LID
NUM.
KEY
Algorithms
(ALGO)
Status
(STAT)
Service
(SRVC)
Alarm
(ALRM)
Setup
(SET)
Schedules
(SCHD)
1
2
AO—Adaptive Control
AO—Cooling CV
Hardware Points
Alarm History
Function Definition Limit
Set Clock
Real Time Clock
Occupancy
Setpoint
Software Points
Analog Point Trace
Channel Definition Setpoint
3
4
5
AO—Cooling VAV
Temperature Input
Discrete Point Trace
System Definition
Setpoint Definition First out
Database Control Runtime
Comfort Controller # of starts
Discrete
Controller Password Holiday
S/W Setpoint
AO—Fan Tracking
Milliamp Input
Consumable Channel
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
AO—Heating CV
Custom Milliamp Input
Internal Consumable
Network Time
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
6
7
8
AO—Heating VAV
Voltage Input
Runtime Channel
N/A
AO—Humidity Control
AO—Mixed Air CV w/IAQ
AO—Mixed Air VAV w/IAQ
AO—Permissive Interlock
AO—Reset
Custom Voltage Input
CCN Control
LID Preferences
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Sensed Discrete Input
N/A
9
Latched Discrete Input
N/A
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Pulsed Discrete Input
N/A
N/A
Milliamp Output
N/A
N/A
AO—Shared Transducer
AO—Static Pressure
DO—Analog
Custom Milliamp Output
N/A
N/A
Voltage Output
N/A
N/A
Custom Voltage Output
N/A
N/A
DO—DX-Staging VAV
DO—Electric Heat CV
DO—Electric Heat VAV
DO—Enthalpy Comparison
DO—Interlock
Discrete Output
N/A
N/A
Stepper Motor Output
N/A
N/A
Discrete Software Point
N/A
N/A
Analog Software Point
N/A
N/A
Network Data Out
N/A
N/A
DO—Lighting Control
DO—Permissive Interlock
DO—Pump Control
DO—Prop Thermo
DO—Prop Thermo 2 Pipe
DO—Prop Thermo 4 Pipe
DO—Staged Thermostat
DO—Staging Control
DO—Time Clock
Network Data In
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
DO—Time Clock w/Check
AOSS Schedule
N/A
N/A
N/A
N/A
N/A
N/A
Network Broadcast
Linkage/AOSS Schedule
NTFC w/Enthalpy Check
Sensor Group
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
WSM Air Source
N/A
N/A
N/A
WSM Cool Source
N/A
N/A
N/A
Custom Program
N/A
N/A
N/A
LEGEND
NOTES:
1. To change from Edit mode to Status mode, press
CLEAR
or press
AO
—
Analog Output
Adaptive Optimal Start/Stop
Constant Volume
Digital Output
Indoor Air Quality
Not Available
AOSS
CV
—
—
—
—
—
—
—
—
EXPN/EDIT
again.
2. Not all available selections will have items to select in sublevels.
DO
IAQ
N/A
NTFC
VAV
WSM
Nighttime Free Cooling
Variable Air Volume
Water System Manager
begins. The run test will complete and then the supply will
automatically restart.
NOTE: If the Local/Off/Remote switch is in the OFF posi-
tion, it is normal for the red alarm light on the display panel
to be lit, indicating that the unit is disabled.
NOTE: If the red light stays on when the switch is moved to
REMOTE, or if any other problems occur during the run
test, refer to the Troubleshooting section of this manual.
To perform the Run Test:
1. Turn unit power on.
Automatic Run Test — The 50BV,XJ unit controls are
programmed with an automatic run test that checks connection
and operation of major components. To perform the run test:
Verify that the control display (LID device/System Monitor)
interface cable is connected to internal jack on main controller;
that the fire alarm/shutdown switch input (FSD) has a factory
jumper or field input; that Bypass (if installed) is set in the
DRIVE position; and that the Local/Off/Remote switch is set to
the REMOTE position.
NOTE: When the Local/Off/Remote switch is in the
REMOTE position, the controller time schedule is pre-set
(from the factory) as unoccupied. This means that the unit
will not turn on until the run test is enabled. However, if the
controller schedule has already been modified in the field,
and the current time of day is occupied, then the supply fan
will start. The run test will shut the fan down when it
The LID display will show the controller identifica-
tion, time and date (Fig. 5):
OMNIZONE VPAC
hh:mm mm-dd-yy
10
2. Press 3 and then
. The LID display will show:
If the control does not receive open/open/closed/
in range/in range/in range, the red alarm LED will go
on and the test will stop.
If the inputs are OK, the red alarm LED blinks once
and the test continues.
SET
Controller Password
3. Press
. The LID display will show:
ENTER
Log in to Controller
Enter Password
NOTE: The LID display has two modes: Edit mode and
Status/Maintenance mode. If the LID display is in Edit
mode, then the display will only show the word “pass-
12. Next, the control forces the Supply Fan (SF) and all of the
Compressors (COMP) off, and waits 15 seconds.
For the 50XJ unit, if the REMOTE LED and AUTO
LED on the VFD display are on, the red LED blinks
once and the test continues.
NOTE: For the 50XJ unit, if the controller is config-
ured with a water Economizer, the delay is 2 min. and
both valves are commanded to 0%. Both water valves
will close.
word.” Press the
mode.
key to toggle to the Status
EXPN/EDIT
Press the
to display:
EXPN/EDIT
Log in to Controller
Enter Password
13. The control forces SF on and SPEED to 20 percent and
then waits 30 seconds.
4. Key in the password and press
.
ENTER
If the VFD display shows “10.6 Hz,” the Remote and
Auto LEDs blink, and the fan goes on, then the red LED
on the control module blinks once and the test continues.
NOTE: For the 50XJ unit, if the controller is config-
ured with a water Economizer the delay is 2 min. and
Econo valve is commanded to 100%. The economizer
valve will open and the RVS/HD (reverse/head
pressure) valve will remain closed.
NOTE: The default password is 1111.
5. The LID display will show:
Log in to Controller
Logged In
NOTE: At this point, for the 50BV unit only, the run
test will follow these steps:
a. Press 37
. The display will show:
ALGO
Custom Program
b. Press . The display will show:
14. The control forces SF on and SPEED to 35 percent and
then waits 30 seconds.
If the VFD display shows “20.0 Hz,” the Remote and
Auto LEDs blink, and the fan goes on, then the red LED
on the control module blinks once and the test continues.
NOTE: For the 50XJ unit, if the controller is configured
with a water Economizer the delay is 2 min. and RVS/
HD valve is commanded to 100%. The economizer valve
is commanded to 0% and the RVS/HD valve will open.
ENTER
2.0 Global Dictionary
OMNIZONE
c. Press
(NOTE: Display will flash,
EXPN/EDIT
indicating that the device is now in edit mode.)
The display will show:
2.0 Global Dictionary
OMNIZONE
15. The control forces SF off then waits 15 seconds.
If the VFD display shows “Off,” the Remote and Auto
LEDs are off, and the fan goes off, then the red LED on
the control module blinks once and the test continues.
NOTE: For the 50XJ unit, if the controller is configured
with a water Economizer both valves are commanded
to 0%. The economizer valve and RVS/HD will close.
NOTE: For the 50BV unit, the steps below (16-24)
will be completed for the number of compressors
configured.
d. Press
. The display will show:
ENTER
Compressor Stages
4.00
NOTE: A 50BV unit with only 2 compressors will
display 2.00. Skip to Step 6.
e. Input 2.00 and Press
Compressor Stages
2.00
. The display will show:
ENTER
16. The control forces CMP1 (compressor 1) on then waits
5 seconds.
STAT
6. Press
. The LID display will show:
If CSMUX is not in range the red LED will go on and
the test will stop.
If CSMUX is in range, the red LED blinks once and
the test continues.
Hardware Points
7. Press STAT again. The LID display will show:
Software Points
8. Press
. The LID display will show:
17. The control forces CMP1 off.
18. The control forces CMP2 (compressor 2) on then waits
5 seconds.
ENTER
Compressor 1 Status
9. Press 6 times. The LID display will show:
If CSMUX is not in range the red LED will go on and
the test will stop.
If CSMUX is in range, the red LED blinks once and
the test continues.
Factory/Field Test
Stop
10. Press 1 then
, The LID display will show:
ENTER
Factory/Field Test
Start
NOTE: At this point, the yellow warning light on the
display panel will be lit and will stay on throughout the
run test. After each successful step, the red alarm light
will blink once.
19. The control forces CMP2 off.
20. The control forces CMP3 (compressor 3) on, if config-
ured, then waits 5 seconds.
If CSMUX is not in range the red LED will go on and
the test will stop.
If CSMUX is in range, the red LED blinks once and
the test continues.
11. The control module will now check if there is input from
BYPAS (50XJ), DHS, FSD, SAT, DSP, and CSMUX.
21. The control forces CMP3 off.
11
22. The control forces CMP4 (compressor 4) on, if config-
ured, then waits 5 seconds.
4. The LID display will show:
Log in to Controller
Logged In
The LID display shows:
Factory/Field Test
Stop
NOTE: The user will be automatically logged off after
15 min. of non-use.
The yellow LED will go off, and the red LED will go
off.
23. The control forces CMP4 off.
24. The run test is complete.
Change the Default Password — To change the
default password, perform the following procedure:
NOTE: The password must have already been entered to
perform this procedure.
1. Press 3 and then
. The LID display will show:
SET
Controller Password
2. Press . The LID display will show:
Power Up the LID Display — After completing the
automatic run test, perform the following procedures to change
the controller password, set the controller clock, configure
schedules, set parameters, view settings, and view alarm
history.
1. Set the Remote/Local/Off switch on the front of the unit to
the OFF position. This prevents operation of the fan and
compressors while still providing power to the unit controls.
ENTER
Log in to Controller
Logged in
3. Press
. The LID display will show:
EXPN/EDIT
Password
NOTE: When the switch is in the OFF position, the red
alarm LED will be lit; this is normal. The bypass point
will also indicate OK.
1111 (default password, or previous password entered)
4. Enter the new password (up to 6 digits) and press
. The LID display will show:
ENTER
2. If the unit access panel (for power and controls) is still on
the unit, remove it in order to view the control modules
during start-up.
Password
(password just entered)
NOTE: Remember this password; write it down.
3. Switch the main unit power disconnect to ON.
5. Press CLEAR twice to leave the password screen and re-
turn to the default display screen.
When power is applied to the OMNIZONE™ System
Control panel, the red LED on the top front of the processor
module will flash at a rapid pace (about twice a second) for the
first 30 to 60 seconds. This rapid flash will then be replaced by
a slower paced flash (about once per second).
The green LED below the red LED will start flashing. This
LED indicates input/output communications for accessory
input output modules and the LID display.
Set the Clock — The user must be logged in to set the
clock. To set the clock, perform the following procedure:
1. Press 1 and then
Set Clock
. The LID display will show:
SET
2. Press
. The LID display will show:
ENTER
The yellow LED will flash when the controller is broadcast-
ing CCN messages to a laptop or other computer.
The third LED from the bottom of the controller (PCB1)
will light.
The LID display will show the controller identification,
time and date as shown below.
No Maintenance
NOTE: There is no maintenance information regarding
setting the clock.
3. Press
Time
. The LID display will show:
EXPN/EDIT
00:00
OMNIZONE VPAC
hh:mm mm-dd-yy
4. Enter the time. The time is entered in military time (for
example 14.59 for 2.59 pm). Press then press
ENTER
button. The LID display will show:
Log On to the LID Display — To Log On to the LID
the
display, perform the following procedure:
Day of Week
1
1. Press 3 and then
. The LID display will show:
SET
Controller Password
5. Enter the day of week. The numbers 1 through 7 corre-
spond to the days of the week (1 = MON, 2 = TUE,
3 = WED, 4 = THUR, 5 = FRI, 6 = SAT, 7 = SUN). Press
2. Press
. The LID display will show:
ENTER
Log in to Controller
Enter Password
NOTE: The LID display has two modes: Edit mode and
Status/Maintenance mode. Edit mode allows the user to
change settings on the configurations screens. Status/
Maintenance mode only allows the user to look at the
settings.
then press
. The LID display will show:
ENTER
Month
1
6. Enter the number of the corresponding month (1 through
12). Press
will show:
then press
. The LID display
ENTER
If the LID display is in Edit mode, then the display will
only show the word “password.” Press the
Day
1
key to toggle to the Status mode. Make
sure the LID display shows:
Log in to Controller
EXPN/EDIT
7. Enter the day of the month. Press
. The LID display will show:
then press
ENTER
Enter Password
Year
95
3. Key in the password and press
.
ENTER
NOTE: The default password is 1111.
12
8. Enter the last two digits of the current year. Press
then press . The LID display will show:
4. If “No maintenance” is displayed, press
to
EXPN/EDIT
ENTER
view the set point information. The LID display will
show:
Update Clock
No
Occupied Lo Set point
0.30 ″ H2O
This is the pressure set point below which the fan is
considered to be off.
9. Press 1 and then
to cause the controller to
ENTER
update the clock. The LID display will flash. Press
CLEAR
twice to view the default display and the clock
should update to the input time and date.
5. Press
. The LID display will show:
Occupied Hi Set point
0.40 ″ H2O
This is the pressure set point above which the fan is
considered to be on.
Configure Schedules — Schedules are one method of
starting and stopping the unit at specified intervals. To config-
ure the schedules, perform the following procedure:
1. Press 1 and then
. The LID display will show:
SCHD
Occupancy Algorithm
The down or up arrow will also display the Unoccu-
pied Low and High Temperature set points. These
values should be kept the same as the occupied values.
2. Press
. The LID display will show:
ENTER
Time Schedule
Enter to select
6. Setpoint 02 internally coordinates the supply air set point
reset in several of the algorithms and can not be modified.
3. Press
. If the LID display shows “MODE 0” then
ENTER
Setpoint 03 is used for comparison by the unit to return
air, Space temperature or Average space temperature
through linkage to determine when to start reset of the
supply air when occupied, when to turn on heat and
disable cooling when occupied and when to bring the unit
on for unoccupied heating or cooling.
Setpoint 04 is used to set the head pressure set point if
the unit is ordered with the head pressure control
option. Only the Occupied Low set point may be
modified the other values will change to the Occupied
low valued shortly after it is modified so that all the
values remain the same.
the user is in Maintenance mode and the LID display is
showing the maintenance information for the occupancy
schedule. Press
to enter the configuration
EXPN/EDIT
mode. The LID display will show:
Manual Override Hours
0 hours
This is the first configuration for each occupancy
algorithm and is used to put the schedule in or out of
occupancy override for the number of hours entered.
4. Press
. The LID display will show:
Setpoint 05 is used to set the supply air static pressure the
unit should maintain. Only the Occupied Low set point
may be modified the other values will change to the
Occupied low value shortly after it is modified so that all
the values remain the same. The set point in the static
pressure control algorithm will also follow and cannot be
modified in the algorithm configuration screens.
Setpoint 06 is the Supply air temperature set point.
Only the Occupied Low set point may be modified the
other values will change to the Occupied low value
shortly after it is modified so that all the values remain
the same. The set point in DX VAV staging and some
of the other algorithms will also follow and cannot be
modified in the algorithm configuration screens.
Period 1: Day of week
00000000
The eight digits represent if this period should apply to
certain days of the week or holidays. The digits repre-
sent M, Tu, W, Th, F, Sa, Su, and Hol, respectively.
Enter a series of 0s or 1s with a 1 corresponding to the
days that this period should apply to and a 0 for the
days that this schedule should not apply to. As an
example, entering 11111000 would make the schedule
apply to days Monday through Friday and not apply to
Saturday, Sunday, or Holidays.
5. Press the
button. The LID display will show:
Period 1 occupied from
Setpoint 07 is the building pressure set point for the
building pressure control of a variable speed exhaust
fan from a field-supplied module. Only the Occupied
Low set point may be modified the other values will
change to the Occupied low value shortly after it is
modified so that all the values remain the same.
Setpoint 08 is the raw milliamp set point for the build-
ing pressure control and is tied to Setpoint 07 for the
sensor range selected in the custom programming
configuration. Several choices of building static
pressure sensors may be purchased and supplied for
building pressure control.
Setpoint 09 is used for the humidification/dehumidification
output from a field-supplied module. This set point may be
modified to enable the Humidity output to either humidify
or dehumidify when the indoor relative humidity (IRH)
exceeds the set point.
Table 7 lists the available controller set points and their
default values.
00:00
6. Input the Occupancy Start time for this period.
NOTE: 12.00 represents 12:00 pm.
7. Press the
8. Input the days and times for periods 2 through 8 as
required.
9. Press clear to leave the occupancy programming.
to input the Occupied To time for period 1.
Program Set Points — To program the set points,
perform the following procedure:
1. Press 2 and then
. The LID display will show:
SCHD
Set point Schedule
2. Press
. The LID display will show:
ENTER
Supply Fan Status
SETPT01
3. Press
.
ENTER
7. Pressing the CLEAR button will take the user out of the
set point configuration mode.
13
Table 7 — Controller Set Points
pressing the HIST button. The LID display will show “Alarm
History.” Press . The LID display will show the date
ENTER
and type of alarm.
DESCRIPTION
DISPLAY
VALUE UNITS STATUS FORCE
NAME
SCREENS
As an example, if the LID display shows:
ALARM — 10:55 11-27-02
SFS
OMNIZONE::SETPT01:
Supply fan Status
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
0.3 in H2O
0.4 in H2O
0.3 in H2O
0.4 in H2O
OccLow
OccHgh
UnOccLow
UnOccHgh
That display indicates that on 11/27/02 at 10:55 A.M. the
system Supply Fan was either on when it had not been
commanded on or was off when it was commanded on.
The user can view other stored alarms by pressing the up
and down arrows. The twenty-four most recent alarms are
stored.
OMNIZONE::SETPT02:
VAVRESETbaseline
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
0
0
0
0
dF
dF
dF
dF
OccLow
OccHgh
UnOccLow
UnOccHgh
OMNIZONE::SETPT03:
Heat\Cool Mode & Reset
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
Configure Custom Programming Selections —
To configure the custom programming selections, perform the
following procedure:
70
74
55
85
dF
dF
dF
dF
OccLow
OccHgh
UnOccLow
UnOccHgh
1. Press 37
. The LID display will show:
ALGO
Custom Program
2. Press . The LID display will show:
OMNIZONE::SETPT04:
Head Pressure Control
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
225 PSIG
225 PSIG
225 PSIG
225 PSIG
OccLow
OccHgh
UnOccLow
UnOccHgh
ENTER
2.0 Global Dictionary
OMNIZONE
OMNIZONE::SETPT05:
Supply Static Pressure
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
3. Press
. The display indicates “No Data.”
ENTER
CLEAR
1.5 in H2O
1.5 in H2O
1.5 in H2O
1.5 in H2O
OccLow
OccHgh
UnOccLow
UnOccHgh
Press
then press
.
Press
EXPN/EDIT
again. The LID display should now show:
ENTER
Compressor Stages
4.00
OMNIZONE::SETPT06:
Supply Air Temperature
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
55
55
55
55
dF
dF
dF
dF
OccLow
OccHgh
UnOccLow
UnOccHgh
4. Press 4 and then
are installed.
to indicate that 4 compressors
ENTER
5. Use the down and up arrows to select the other configura-
tion parameters as required. See Table 10 for a list of con-
figuration parameters.
6. A field-supplied 0 to 10 vdc signal to the 50XJ unit may
be used to reset the supply-air temperature.
OMNIZONE::SETPT07:
Building Static Pressure
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
0.02 in H2O
0.02 in H2O
0.02 in H2O
0.02 in H2O
OccLow
OccHgh
UnOccLow
UnOccHgh
OMNIZONE::SETPT08:
BSP raw control
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
The reset will be taken off the supply air set point
configured in the controller. The reset range can be
changed by adjusting the High Conversion Endpoint
value of the custom voltage input to a value other than
20. For example for 10 degrees of reset change the Hi
input value to 10. This may be found by pressing 7
12.32
12.32
12.32
12.32
ma
ma
ma
ma
OccLow
OccHgh
UnOccLow
UnOccHgh
OMNIZONE::SETPT09:
Humidity Control
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
0
%RH
OccLow
OccHgh
UnOccLow
UnOccHgh
99 %RH
0
%RH
STAT
from the Keypad. RESET will be the second
99 %RH
custom voltage input point in the controller. The first
will be CSMUX, which is the compressor status multi-
LEGEND
BSP
RH
—
—
Building Static Pressure
Relative Humidity
plexed input. Press
LID display:
to see the following in the
Ext. Supply Air Reset
RESET
Check System Parameters — To check system
parameters, press the STAT button. The LID display will
show: “Hardware Points Table 1.” Press
hardware points. The user can navigate up and down through
the points with the up and down arrows.
to view the
Press
. If the LID display shows:
ENTER
ENTER
System Value
Press
. The LID display will show:
EXPN/EDIT
STAT
Press 2 and
to display the software points. The user
Low Input Endpoint
2.0 Volts
can navigate up and down through the points with the up and
down arrows.
Press
three times to get to the High Conversion
Endpoint. The user must be logged in to be able to change this
otherwise you can only view it. See the start up section for how
to log into the controller.
Refer to Tables 8 and 9 for hardware and software points.
Display Alarm History — If the controller is indicating
there are alarms, the user can view the alarm history by
Configuration parameters are shown in Table 10.
14
Table 8 — Controller Hardware Points
Table 9 — Software Points
DESCRIPTION
DESCRIPTION
DISPLAY
VALUE UNITS STATUS FORCE NAME
DISPLAY
VALUE UNITS STATUS FORCE
NAME
SCREENS
SCREENS
OMNIZONE::HWP01-32:
Hardware points Table 1
Supply Air Temperature
Duct Static Pressure
Comp. Status MUX
OMNIZONE::SWP65-96:
Software Points
67
dF
in H2O
Volts
SAT
Compressor 1 Status
Compressor 2 Status
Compressor 3 Status
Compressor 4 Status
Off
Off
Off
Off
CLO1
0.2
DSP
CLO2
1.86
Enable
Yes
CSMUX
FSD
CLO3
CLO4
Fire Alarm/ShutDown
Cond. Water Flow Switch
Remote Occupancy
Duct High Press. Switch
Entering Water Temp.
Compressor 1 Relay
Compressor 2 Relay
Compressor 3 Relay
Compressor 4 Relay
Supply Fan/VFD
CDWF
ROCC
DHS
Bypass Acc Panel Secure No
BP_SAFE
VAVRESET
FLDTST
BSP_IN
TIMCLOCK
COOLOK
Disable
Normal
69.9
Stop
Stop
Stop
Stop
Stop
0
Off
Off
77.2
Clean
Normal
0
DX VAVRESET control
Factory/Field Test
Building Static Pressure
Time Clock
0
dF
Stop
0.03
Off
dF
EWT
in H2O
CMP1
CMP2
CMP3
CMP4
SF
Cooling
Supply Fan Status
Ok to run Fan
Disable
Off
No
FALSE
FALSE
Cool
Control SFS
OKFAN
OK Fan + Sup. Fan Stat
Fan + Cond. Water Flow
Equipment Mode
SF_SFS
VFD Speed Signal
%
SPEED
WARN
ALARM
MA_RA
FLTS
PHASE
RESET
FREEZ
SPT
FAN_CDWF
Non Critical Fault
Control MODE
Critical Fault
Activate Evacuation Mode Disable
EVAC
CTRLPT
Mixed/Return Air Temp
Dirty Filter Status
dF
Space Control Point
Mod. Econ Enabled
Head Pressure Control
74
No
Disable
dF
dF
Control ECON_OK
Control HEAD
ECONPT
Phase Loss Protection
Ext. Supply Air Reset
Water Econ. FreezeStat
Space_Reset Sensor
VFD Bypass Enable
Head Pressure(Comp1)
Ventilation Request
VAV Terminals Control
2-position/Econo Valve
Reverse/Head Press Ctrl
Hot Water Valve
dF
dF
Economizer Control Temp. 77.22
Normal
79.2
Disable
118.76
Close
No
Compressor Cooling
Duct Static Failure
Disable
Normal
Normal
Normal
Normal
Normal
COMPRES
DSP_ALM
BYPAS
PRES
VENTR
TRMCT
ECONO
Compressor 1 Alarm
Compressor 2 Alarm
Compressor 3 Alarm
Compressor 4 Alarm
C1_ALM
PSIG
C2_ALM
C3_ALM
C4_ALM
0
%
%
%
Cond. Flow Alarm Status Disable
Control CDWF_ST
100
Control MVLV
0
HWV
HIR
Table 10 — Configuration Parameters
Heat Interlock Relay
Bypass Start_Stop
VAV Terminals Open MAX
Off
Stop
Close
BPS_S
TRMOP
DESCRIPTION
VALUE
UNITS
NAME
Compressor Stages
Reset Ratio
2.00
3.00
0.00
0.00
1.00
0.00
0.00
2.00
0.00
0.00
68.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.00
–0.50
NUM_CMP
RSET_RTO
CDFW_SWT
EWT_SNS
EWT_RST
MOD_ECON
FLOW_TYP
MARA_SNS
PHAS_SWT
FREZ_SWT
ECON_SET
SPT_SNS
PRES_SNS
TWR_SNS
LWT_SNS
IAQ_SNS
IRH_SNS
BSP_SNS
OMNIZONE::HWP33-64:
Hardware points table 2
dF
CDWF 0=NO,1=YES
ECON 0=NO,1=YES
EWT Reset 0=NO,1=YES
MOD.VLV 0=NO,1=YES
0=CONST.,1=VARIABLE
0=RAT,1=MAT 2=NONE
PHASE 0=NO,1=YES
FREEZ 0=NO,1=YES
ENABLE ECON.
Cooling Tower Sump Temp. 57.5
dF
ma
dF
TWR
Building Static Milliamp
12.51
BSP
Condenser Leaving Water 70.3
LWT
Indoor Air Quality
Indoor Relative Humidity
Outdoor Air Temp.
Heat Stage 1
587.21
IAQ
49.7
76.1
Off
Off
Off
Off
Off
Off
0
%
dF
IRH
OAT
HEAT1
HEAT2
HEAT3
HEAT4
PUMP
TOWER
EXH
Heat Stage 2
dF
Heat Stage 3
SPT 0=NO,1=YES
PRES 0=NO,1=YES
TWR 0=NO,1=YES
LWT 0=NO,1=YES
IAQ 0=NO,1=YES
Heat Stage 4
Pump Request
Cooling Tower Request
Exhaust Fan
%
Ext. Dehumidification
Stop
DEHUM
IRH 0=NO,1=YES
BSP 0=NO,1=YES
BSP Range
in H2O BSP_RNG
in H2O BSP_LOW
BSP LOW VALUE
LEGEND
BSP
CDWF
ECON
EWT
IAQ
—
—
—
—
—
—
—
—
—
—
Building Static Pressure
Condenser Water Flow
Economizer
Entering Water Temperature
Indoor Air Quality
IRH
Indoor Relative Humidity
Leaving Water Temperature
Mixed Air Temperature
Return Air Temperature
Space Temperature
LWT
MAT
RAT
SPT
1. Press
. The display should show:
ENTER
Set Controller Address — To set the address of the
OMNIZONE™ System Control panel controller, perform the
following procedure:
Log in to Controller
Logged in
If this is not displayed, Press
displayed.
1. Press 7 and then
EXPN/EDIT
2. Type in the CCN element number and press
. Press
and then
ENTER
SRVC
until it is
EXPN/EDIT
.
.
ENTER
2. Press the
Log out of Controller
Press 1. Press
button. The LID display will show:
3. Press the
press
button. Type in the CCN bus number and
.
ENTER
to log off.
ENTER
Log Off from Controller — To log off from the
OMNIZONE System controller Press 3 and then
controller password will be displayed.
. The
SET
15
sensors installed and the configuration of these sensors in the
custom configuration, or the status of linkage.
OPERATION
Occupancy Determination — The OMNIZONE™
controller can determine occupancy in many ways. Local occu-
pancy is determined by either a local schedule contained in the
CC6400 controller, the use of the ROCC discrete input point or
by setting the Local/Off/Remote switch to Local. In order for
the CC6400 schedule or ROCC point to function the Local/
Off/Remote switch must be set to Remote.
When the OMNIZONE unit is connected to a Carrier
Comfort Network and the Local/Off/Remote switch is set to
Remote, the controller occupancy can be determined by a
Network Group schedule, a Network Global schedule, or via
Linkage from a linkage device such as a ComfortID™ linkage
master.
If the Return/Mixed air sensor is in the mixed airstream and
configured as such and there is no Space temperature sensor
installed and no Linkage, the Space Control Point will display
a default value of 75 F, which is above the default occupied
cooling set point and below the unoccupied cooling set point.
If this condition exists, supply air reset from a sensor and
unoccupied unit operation will not occur.
If the unit is configured to use a sensor for the Space
Control Point or if Linkage is active and the space has
unoccupied demand, the software point OKFAN will turn on
followed by the points TRMCT for air terminal control and
PUMP and TOWER to request condenser water flow and
temperature control. Approximately 20 to 30 seconds later the
SF point will turn ON and then the VFD output SPEED will
increase. If unoccupied demand is the reason the fan is on, a
control force will appear next to the OKFAN point. Otherwise
there should not be a force on that point.
If the fan is running due to unoccupied heating or cooling
demand, either the space temperature (if installed), return air
temperature or average linkage temperature must rise or drop
to within half way between the occupied and unoccupied set
points in order for the fan to turn back off.
Enabled by Switching to Local Mode — When the switch is
placed in the local mode the ROCC point will indicate enable.
If ROCC is ENABLED a software routine will override the
occupancy schedule so that TIMECLOCK will also turn on.
When ROCC is turned off the TIMECLOCK point will turn
off within 60 seconds.
Supply Fan Shutdown — If the unoccupied demand is satis-
fied and TIMECLOCK and ROCC are off and disabled,
OKFAN will turn off, SF_SFS will turn off, Tower and PUMP
will turn off, and then 5 minutes later the SF point will turn off
and the VFD speed will go to 0%.
During the 5-minute delay, the cooling and heating routines
become disabled. This delay allows a compressor that may
have just started to run for its 5-minute minimum on time with
the supply fan on. For example, if the staging routine had just
started Compressor 3 at the time the OK_FAN point changed
to OFF, the cooling routine would become disabled and com-
pressors 1 and 2 would shut off right away. Compressor three
would continue to run for its minimum on time of 5 minutes.
The fan continues running until all compressors meet the
minimum on time and run with a load, preventing them from
shutting down due to a safety.
Fan Control — All Variable Air Volume (VAV) units have
a Variable Frequency Drive (VFD) to provide variable fan
motor speed and thus variable airflow. Fan control turns the fan
on and off based on unit operating mode, and controls fan
speed to maintain a particular duct static pressure at a Duct
Static Pressure Sensor (DSP). The objective is to maintain a
reasonably constant supply-air exit velocity at VAV system
outlet grilles, regardless of damper opening positions. The duct
2
static pressure sensor is field-installed about /3 of the way
toward the “far end” of the ductwork. A High Duct Static
Switch (HDS) provides protection by shutting the fan down if
the duct static pressure exceeds a maximum setting.
For the 50XJ unit, a VFD interface display is mounted in
the front of the unit. A number of user-adjustable features can
be entered/changed using the keypad on the display. These
features described in detail in the Variable Frequency Drive
Control section.
Sequence of Operation — The following control
sequence of operation for the 50XJ,BV unit describes the
various sequences that occur depending upon the way an
operation is triggered and which software control points are
involved.
SUPPLY FAN — The Supply fan can be activated in any of
the following ways:
•
•
•
•
•
Unoccupied space or return air temperature demand.
Unoccupied Linkage demand.
Local Time Schedule (TIMCLOCK software point).
Remote Occupancy (ROCC software point).
By placing the remote-off-local switch in the local
mode.
•
Enabled by Schedule.
Supply Fan operation with Optional Bypass (50XJ) — If the
optional VFD Bypass is installed and the Bypass switch has
been turned to Bypass, and the access panel is in place, the
software point Bypass access panel secure BB_SAFE has been
turned to ON, and the unit operation switch has been placed
back in local or remote, then the bypass start stop point BPS_S
will follow the SF point when it turns on and off. The terminal
open point TRMOP will go on with the TRMCT point before
the fan starts.
COMPRESSOR COOLING — If the fan is on and there is no
demand for Heat, the equipment mode (MODE) will be
COOL, and Cooling (COOLOK) will switch to ENABLE.
If the unit is configured for variable flow the Reverse/Head
Pressure CTRL valve will open (otherwise it will already be
open), and if there is condenser water flow (CDWF is YES),
then the Fan + Condenser water flow point will become TRUE
and the Compressor Cooling (COMRES) point will switch to
Enable.
Once one of the above conditions exists, either TIME-
CLOCK or ROCC indicates ON or Enable. The software point
OKFAN will turn on followed by the points TRMCT for air
terminal control and PUMP and TOWER to request condenser
water flow and temperature control. Approximately 20 to
30 seconds later the supply fan (SF) point will turn ON and the
VFD output SPEED will increase. The SPEED point will
output a signal, determined by a PID calculation, based on the
duct static pressure DSP input and the Supply Static Pressure
set point in SETPT05.
Once the supply fan is running and the static pressure
increases above the Supply fan status set point in SETPT01, the
supply fan status point (SFS) will indicate ON and the software
point SF_SFS will indicate TRUE.
Enabled By Unoccupied Demand — A software point “Space
Control Point” will display the current value of the sensor used
to determine unoccupied demand. The EWT sensor provides
this function for the 50BV unit. The display is based on the
16
COMRES triggers the compressor staging routine that
controls the number of compressors energized. Units are
equipped with 4 compressors piped in separate refrigerant
circuits, and staged On/Off in a fixed sequential manner
(compressor no. 1 through compressor no. 4). The compressor
control routine uses a PID calculation to determine the percent-
age of cooling required, from 1 to 100%. Demand for the PID
calculation is determined from the supply air temperature and
the supply air set point (SETPT06).
NOTE: The reset from all methods may be limited to 10 F
or 15 F by changing the high end point of the custom
voltage input from the default (20 F) to 15 F or 10 F.
Either the return air or a space temperature sensor will be
used as the space control point. If this variable goes below the
Occupied High set point in the HEAT/COOL MODE AND
RESET set point (SETPT03), then for each degree that the
Space control point is below the set point value the supply air
set point will be reset by the value configured in the custom
configuration RESET RATIO.
If Linkage is active, for each degree that the average
occupied space temperature is below the average occupied cool
set point, the supply air set point will be reset by the amount
configured in the RESET RATIO. Reset will be limited to the
maximum value the custom voltage input RESET can display.
COOLING RESET (50BV) — The 5k ohm temperature sen-
sor will be used as the space control point. If this variable goes
below the Occupied High set point in the HEAT/COOL
MODE AND RESET set point (SETPT03), then for each
degree that the Space control point is below the set point value
the supply air set point will be reset by the value configured in
the custom configuration RESET RATIO.
Compressor cooling (COMPRES) will be turned off for any
of the following reasons:
•
•
There is no condenser water flow (CDWF is Off).
Economizer Freezestat (FREEZ) has been in alarm for
more than 15 minutes.
•
•
•
MODE changes to heat.
OK-FAN turns off during normal shut down.
During normal compressor operation the minimum on
time is 5 minutes and the minimum off time is 5 min.
ECONOMIZER COOLING (50XJ) — The unit diverts con-
denser inlet water flow through an optional economizer coil to
precool evaporator entering airflow. This occurs when there is
demand for the cooling, and the temperature at an Entering
Water Temperature (EWT) thermistor is colder than the
economizer start set point. Waterflow is controlled via two
electronic water flow valves. This option also incorporates an
Economizer Freeze Switch (EFS), located at the inlet of the
economizer coil.
Economizer water flow is in series with the condensers
allowing compressor operation while the economizer is
operating.
If the Fan is on, and there is no demand for heat then the
equipment mode (MODE) will be COOL and Cooling
(COOLOK) will switch to ENABLE.
HEATING (50XJ) — The controller is configured to control
two types of heat:
•
A modulating 4 to 20 mA output Hot Water Valve
(HWV) in the base unit, wired to the second module.
Four stages of staged heat wired to a third, accessory
module (PCB3).
•
For either method of heat to function, a space control point
must be configured in the custom configuration. This control
point comes from a return air sensor or space sensor, or from
the average space temperature received through linkage.
Whenever the space control point is below the occupied or
unoccupied heat set point the mode will change to heat and if
unoccupied the fan will be started. For linkage, this occurs if
the average space temperature is below the appropriate average
heat set point.
If the unit is configured for variable flow the Reverse/Head
Pressure CTRL valve will open (otherwise it will already be
open), and if there is condenser water flow (CDWF is YES)
then the Fan + Condenser water flow point will become TRUE.
If the entering-water temperature is below the Economizer
start set point in the configuration parameters table (Table 10),
then the Mod. Econ Enabled point (ECONOK) will change to
enable and the Economizer valve will modulate open to lower
the Economizer control temp to the supply air set point
(SETPT06) temperature. The economizer modulation is
controlled by a PID loop and the Reverse/Head pressure
control valve will modulate in reverse of the Economizer valve
using the formula MVLV = 100 – ECONO.
ECONOMIZER COOLING (50BV) — The unit diverts con-
denser inlet waterflow through an optional economizer coil to
precool evaporator entering airflow. If the entering-water
temperature is colder than the setting on the Aquastat, and the
return-air temperature is warmer than the setting on the return
air thermostat, the two-position diverting valve will direct
water to the economizer coil.
Both heat control routines use a PID to calculate a supply air
set point that will satisfy the heat demand in the space. The
modulating output and the staged outputs will both operate at
the same time to control an attached heat source, such as steam
valves or electric heaters, to provide the supply-air temperature
required.
The heat mode changes back to cool when the space control
point is back above the occupied heat set point. For linkage, the
mode changes back to cool when the average space tempera-
ture is back above the average occupied heat set point.
When unoccupied heat is enabled the fan will be stopped
and the heat turned off when the space control temperature is
more than halfway above the difference between the occupied
heat set point and the unoccupied heat set point. For example,
if the occupied heat set point is 70 and the unoccupied heat set
point is 60 the unit will come on for unoccupied heating below
60 F and turn off again above 65 F. The average occupied and
unoccupied set points are used when linkage is active.
HEAD PRESSURE CONTROL (HPC) (50XJ) — In instal-
lations where entering water temperature can fall below 55 F,
where a water economizer (described above) is not installed,
the HPC provides 1 or 2 electronic water flow control valves to
vary flow to the condensers. Controlling the water flow
maintains compressor discharge pressure above a minimum
value, ensuring sufficient refrigerant flow out of the condenser
and throughout the refrigerant circuit. Refrigerant pressure is
measured at compressor circuit no. 1 by a Discharge Pressure
Sensor (DPS).
Economizer water flow is in series with the condensers
allowing compressor operation while the economizer is
operating.
COOLING RESET (50XJ) — The controller can reset the
supply air set point using these three methods:
•
•
•
An external 0 to 10 volt input RESET
The value of the space control point
Linkage
The external 0 to 10 volt input reset is configured to produce
a 0 to 20 degree supply air reset over the 2 to 10 volt range. If
more than 1.8 volts is sensed on the input, this method of reset
takes priority over other methods.
17
Units not equipped with a water economizer can be ordered
with the reverse/head pressure control valve factory installed
and a pressure transducer located in the discharge line of
compressor no. 1.
When the condenser water temperature gets low enough to
cause the head pressure to drop, the valve will be modulated to
control the head pressure of all four compressors by varying
the water flow through the condensers.
When the unit is operating and the COOLOK software
point is enabled and the EWT gets below 60 F, the Head
software point will become enabled and the head pressure
control valve will modulate to keep the head pressure at the
head pressure set point (SETPT04). The default set point is
225 PSI and may be set from 200 to 250 PSI. The minimum
output value for the head pressure control algorithm is 40% in
order to maintain a minimum flow through the condensers. The
valve will modulate between 40 and 100%. Do not set the
minimum lower than 40% or the compressors may shut down
due to low flow, resulting in the high-pressure switch tripping.
VENTILATION REQUEST (50XJ) — The ventilation request
output will close a set of relay contacts to activate a ventilation
damper whenever the supply fan and supply fan status are both
true and the TIMECLOCK software point is on.
VAV TERMINAL OPERATION OUTPUT (50XJ) — The
VAV terminal control output (TRMCT) closes a set of relay
contacts to indicate to non-Carrier air terminals that the fan is
either forced on or is going to turn on. This signals the
terminals to open and start controlling to the desired CFM and
Temperature set points.
VAV TERMINAL OPEN OUTPUT (50XJ) — The VAV ter-
minal open output (TRMOP) closes a set of relay contacts to
command the air terminals to open to maximum CFM at times
when the fan is operating on the VFD Bypass.
PUMP AND TOWER OUTPUTS (50XJ) — The pump and
Tower outputs close a set of relay contacts to indicate that the
50XJ unit is in operation and may require condenser water
flow through the unit.
FIRE INPUT (FSD) — This is a normally closed input, which
when opened, deenergizes an isolation relay in the unit, opening
the input to the controller. When this input turns On, all control
outputs are immediately turned Off, including the fan. Unit
reset requires manual resetting at the main controller keypad.
DUCT HIGH STATIC INPUT (DHS) — This air switch
provides backup protection for the ductwork. It is factory
installed in the unit, wired to the unit main controller to receive
5 vdc. It is a normally open discreet switch, with adjustable
manual setting at the switch (range is 1 to 5 in. wg). Upon
switch closure, the controller immediately turns all outputs Off,
including fan, and then indicates an alarm both by turning On
its Alarm Output, Red Alarm light and via communications.
DIRTY FILTERS SWITCH (DFLTS) (50XJ) — This switch
measures the change (delta) in air pressure across the filters.
When the delta increases beyond the preset setting, a yellow
warning light will be lit, indicating that the filters need cleaning
or replacement.
The switch receives 5 vdc from the unit controller and
monitors air pressure delta across the return air filters. Switch is
normally open, with manually adjustable setting at the switch
between 0.5 and 1.5 in. wg. Upon closure, controller should
wait to assure closure for minimum 1 minute, then indicate an
alert via its non-critical alert output and via communications.
All other unit operation should remain normal.
COMPRESSOR OVERLOAD (COL)/SAFETIES — Each
compressor circuit is provided with a temperature overload
board (Copeland Protector Bd.), a Current Overload/Sensor
Board (COL), High Pressure Switch (HPS), Low Pressure
Switch (LPS), and Evaporator Freeze Switch (EFS). These
devices are wired in series to the contactor for each compressor.
Each such circuit is then wired through a common resistor board;
such that any one or more input(s) to the main controller allows it
to discern which compressor is not operating when it should be.
The Current Overload Board (COL) is located in the unit
control box, wired in the control power line for the compressor
pilot relay (which drives the compressor contactor), and
incorporates a current loop which monitors one leg of the
compressor power leads. This board is powered along with the
related compressor contactor.
Whenever the compressor current falls below a threshold
level (i.e., compressor not operating), it activates an on-board
relay which opens power to the compressor pilot relay (i.e.,
compressor contactor), and turns On a control power feedback
line to the unit controller, via the resistor board (described
above). Any one of the safety switches described herein will
cause this event. In the event this occurs, the controller shall
turn OFF this compressor, and start the next compressor in
sequence. After a 5-minute period, the controller shall restart
this compressor, and turn the other one off, as cooling demand
requires. If the ‘problem’ compressor then operates for 10 min-
utes of run time normally, the unit reverts to normal operation
and compressor sequencing. If not, and the same error occurs
again, this compressor shall be shut down and replaced with
the next compressor, as before, and held off for 10 minutes. It
shall then be restarted and the other compressor shut down, as
before. If it does not run successfully for 10 minutes of normal
run time again, it is shut down and replaced a third time. This
time it is held off for 15 minutes. If the “problem” compressor
does not operate successfully for the 10 minutes of normal run
time this third time, this compressor ONLY is shut down and
locked out for servicing. Alarm output (Red light) flashes and
then remains on.
BUILDING PRESSURE CONTROL (50XJ) — The building
pressure control output provides an analog 4 to 20 mA signal to
control return fan or exhaust fan speed. Fan speed is modulated
to maintain the building static pressure set point (SETPT07).
The control parameters for the building pressure set point
and building pressure are read and controlled in milliamps but
are converted to inches of water for ease of setting and display.
The range and low start values of the sensor selected should be
configured in the custom configurations screen. The raw sensor
value in milliamps will be displayed on the hardware point
BSP. The converted sensor reading in inches of H2O will be
displayed at the software point BSP_IN. The set point input in
SETPT07 in inches of H2O is converted to a raw milliamp set
point in SETPT08. The algorithm controls to the milliamp
values since the math required for control using the static
pressure in inches generates numbers too small to be used
given the range of the controller configuration parameters.
Diagnostic Features — The CC6400 provides a number
of features to help protect the unit and allow problem
diagnosis.
CRITICAL FAULT — The controller provides an output
(for field connection) to signal an external building systems
monitor or control that the unit is not operating properly and
has shut down. A red light mounted on the front of the unit
provides visual indication of this alarm condition.
NOTE: If the Local/Off/Remote switch is in the OFF
position, it is normal for the red alarm light on the display
panel to be lit, indicating that the unit is disabled.
NON-CRITICAL FAULT — The controller provides an
output for a yellow light, mounted on the front of the unit, that
indicates the need for minor maintenance or service.
HIGH-PRESSURE SWITCH (HPS) — This switch is located
in the discharge refrigerant line of each compressor, and is set
to open at pressures above 360 psig. It is wired in the 115 vac
control power line of the compressor contactor (in series with
the LPS and EFS), and activates the COL board (above) when
it opens.
18
LOW-PRESSURE SWITCH (LPS) — The Low-Pressure
Switch is located in the suction refrigerant line of each
compressor, and is set to open at pressures below 27 psig. It is
wired in the 115 vac control power line of the compressor
contactor (in series with the HPS and EFS), and activates the
COL board (above) when it opens.
EVAPORATOR FREEZE SWITCH (EFS) — This is a thermal
disk type switch, mounted on a return bend of the evaporator,
refrigerant circuit for which corresponds to each respective
compressor, and is set to open at temperatures below 28 F. It is
wired in the 115 vac control power line of the compressor
contactor (in series with the HPS, and activates the COL board
(above) when it opens.
The 7-character LED displays various values, depending
upon what mode is running.
•
In Standard Monitor mode: the LED displays the current
output frequency.
In Status Monitor mode: monitors the status conditions
and frequency command value setting.
In Setup mode: displays setup parameter titles and values.
In Program mode: displays parameter group titles, indi-
vidual parameter names, and parameter values.
During a trip: displays the trip title.
•
•
•
•
The appropriate local/remote LED, which is inset into the
speed control key, is lit when the unit is in Local or Remote
mode.
COPELAND PROTECTOR BOARD — This board is pro-
vided with each compressor, installed in the terminal box, since
these compressors do not have internal current protection. This
board activates at an overtemperature setting, and locks out
operation of the compressor for 30 minutes; there is no method
to over-ride or reset this timer. Due to this timing function,
please note that the compressor will not attempt to restart until
the third attempt described above.
ALARMS — Alarms can be provided via 4 methods; Unit
mounted Alarm Light (Red and Yellow), Keypad Display,
Network Communications, or a discreet Alarm Output to the
Field Low Voltage Terminal Strip. This field output circuit
includes an isolation relay and dry contacts. Alarms are
covered in detail in the Troubleshooting section.
The appropriate manual/auto LED, which is inset into the
run mode key, is lit when the unit is Manual or Auto mode.
When numeric data is shown on the LED display, the corre-
sponding unit indication LED will be lit. If no unit indication
LED is lit, the current data has no unit or the corresponding
unit does not exist on the display panel.
KEY FUNCTIONS — Refer to Table 11 for the functions of
each key on the keypad.
NON-TRIP MESSAGES — Non-trip messages are those that
may be displayed but do not cause a trip and are not recorded in
the fault history. Table 12 lists the non-trip messages with their
explanations.
TRIP MESSAGES — Trip messages and their causes are
shown in Table 13.
CLEARING A TRIP — A trip clear can be performed after
the cause of the trip has been removed. To perform a trip clear,
either switch off power to the inverter or use the following
procedure:
Press Stop/Reset. The display will show: CLr. Press Stop/Re-
set again. The display will show: 0.0, indicating that the trip is
cleared and the display will return to Standard Monitor mode.
If any key other than the STOP/RESET key is pressed at the
trip clear command prompt, the trip clear command is aborted
and the display returns to Standard Monitor mode (where the
trip title will be displayed flashing).The trip clear command
does not clear the recorded past faults.
50XJ Variable Frequency Drive Control — The
variable frequency drive is factory wired and programmed for
proper operation with the unit controls; no installation or
service adjustments are normally required. There is an interface
display for the VFD, independent of the main control display,
mounted on the front of the 50XJ unit.
The VFD default conditions at unit power up are: “AUTO”
run mode, “REMOTE” speed control, and “OFF” in the LED
display. When the fan is operating, the LED displays the output
frequency in Hz.
OPERATING KEYPAD — The keypad allows users to en-
able or disable the keypad, input commands from the keypad,
and monitor drive operation. Fig. 6 shows the operating panel
keypad layout and the locations of the keys and display LEDs.
UNITS LED (TYPICAL 4)
7-CHARACTER LED
DISPLAY AREA
HZ
PERCENT
SECONDS
KW/AMPS/VOLTS
KEYS (TYPICAL 8)
SETUP
PROGRAM
MONITOR
RUN
READ
STOP
WRITE RESET
LOCAL/REMOTE LEDS
MANUAL/AUTO LEDS
LOCAL/REMOTE
MANUAL/AUTO
SPEED CTRL
RUN MODE
Fig. 6 — 50XJ VFD Display Keypad
19
STATUS MONITOR MODE — In Status Monitor mode, it is
possible to monitor the VFD status (frequency command, output
voltage, current, terminal information, etc.). Status monitor
mode is entered by pressing the Setup/Program/Monitor key,
then selecting MON at the mode selection menu and pressing
the Read/Write key. Table 11 details the procedure for entering
status monitor mode (from standard monitor mode) and viewing
all the monitored status variables. The present output frequency
(which, just after power is applied, is 0.0) is displayed. (If the ST-
CC terminals are not shorted, OFF will be displayed).
If either
or
is pressed continuously, every 0.5 sec
the next/previous item will be displayed. As optional points,
RUN, STOP, displaying the frequency status, and switching to
local/remote and manual/auto modes can be performed.
MANUAL MODE — To override the automatic unit controls
and manually operate the fan from the VFD display, press keys
for “MANUAL” run mode, “LOCAL” speed control, and
press the Up or Down arrow keys to increase or decrease
output frequency.
Table 11 — Keys and Functions for 50XJ VFD
KEY
FUNCTION
Local/Remote Key
LOCAL/REMOTE
Switches the source of frequency command information from panel/terminal
block. The appropriate LED is lit to indicate local or remote frequency command.
SPEED CTRL
Manual/Auto Key
MANUAL/AUTO
Switches the source of run/stop command information from panel/terminal block.
The appropriate LED is lit to indicate manual or auto run/stop command.
RUN MODE
SETUP
Setup/Program/Monitor Key
Toggles between Setup, Program, Monitor, and Frequency Mode.
PROGRAM
MONITOR
Read/Write Key
READ
Mode, group, parameter, data, and frequency selection key. This key is used to
select or enter a parameter value, a frequency command, or a group name.
WRITE
Up Key
Scrolls up the setting of the currently displayed parameter. If the key is held
down, the scrolling speed gradually increases. Only RAM values are changed.
Also toggles to other function group entries. Pushing Read/Write key saves the setting.
Down Key
Scrolls down the setting of the currently displayed parameter. If the key is held
down, the scrolling speed gradually increases. Only RAM values are changed.
Also toggles to other function group entries. Pushing Read/Write key saves the setting.
Run Key
RUN
This key is used to start a RUN command (only valid when in manual control mode).
Stop/Reset Key
STOP
RESET
Functions as the STOP key and emergency stop key during local operation.
Functions as the RESET key when an inverter trip occurs. In all other modes,
emergency off is engaged when this key is pressed twice.
Table 12 — VFD Non-Trip Messages for 50XJ Unit
LED MESSAGE
OFF
EXPLANATION
Displayed whenever the ST-CC connection is open.
pOFF
nOFF
Displayed when the VFD control power supply voltage is too low.
Displayed when the VFD’s main DC bus voltage is low.
rtrY
Auto-restart message: alternately displayed with the output frequency whenever the
VFD tries to automatically restart after a non-critical trip.
Err1
CLr
Displayed when 2 frequency points (F-P1,F-P2,etc.) are set too close to each other.
Displayed during a pending clear command (after the STOP/RESET key has been
pressed ONCE after a trip).
EOFF
CtrL
HI
Displayed during a pending emergency off command (after the STOP/RESET key has
been pressed ONCE when in terminal control mode).
Displayed during a pending coast stop command (after the Local/Remote key has
been pressed once when in local control mode while the VFD is running).
This maximum value warning message “HI” will be alternately displayed in the data
field of a parameter when an attempt is made to increase the setting value greater than
the parameter’s maximum value.
LO
This minimum value warning message “LO” will be alternately displayed in the data
field of a parameter when an attempt is made to decrease the setting value less than
the parameter’s minimum value.
PASS
Err
Displayed if the correct password is entered at the password prompt.
Displayed if an incorrect password is entered at the password prompt.
E1
Displayed when the VFD attempts to display a number that exceeds four
numerical digits.
db
dbon
FJOG
rJOG
L
Displayed when DC injection braking is being executed.
Displayed when motor shaft stationary control is being executed.
Displayed when in forward JOG mode.
Displayed when in reverse JOG mode.
VFD/motor overload pre-alarm display.
C
Overcurrent pre-alarm display.
P
Overvoltage pre-alarm display.
H
Overheat pre-alarm display.
t
Option board communication alarm display.
Displayed when the VFD is initializing values during resetting/power-up.
InIt
20
Table 13 — VFD Trip Messages for 50XJ Unit
LED MESSAGE
nErr
EXPLANATION
Displayed in the trip history in standard monitor mode when no trip has been recorded
since the last VFD reset or trip clear.
OC1
OC2
OC3
OC1P
OC2P
OC3P
OCL
OCA1
OCA2
OCA3
OP1
OP2
OP3
OLIn
OLnt
OCr
Overcurrent during acceleration trip
Overcurrent during deceleration trip
Overcurrent during normal (constant speed) run trip
Overcurrent in DC section during acceleration trip
Overcurrent in DC section during deceleration trip
Overcurrent in DC section during normal (constant speed) run trip
Load end over current trip detected at start-up (output terminals, motor wiring, etc.)
U-phase short circuit trip detected at start-up
V-phase short circuit trip detected at start-up
W-phase short circuit trip detected at start-up
Overvoltage during acceleration trip
Overvoltage during deceleration trip
Overvoltage during normal (constant speed) run trip
VFD overloaded trip
Motor overloaded trip
Dynamic braking resistor overcurrent trip
Dynamic braking resistor overload trip
OLr
OH
Inverter overheat trip
E
Emergency off trip message. Displayed after the STOP/RESET key has been pressed
once when in Auto Control mode, or press STOP/RESET key twice within one second
in Manual control mode.
EEP1
EEP2
Err2
Err3
Err4
Err5
Err6
Err7
Err8
Err9
UC
EEPROM failure during write cycle
EEPROM abnormality during initial reading
RAM error
ROM error
CPU error
Communication interruption error
Gate array error
Output current detection circuit error
Option PCB error trip
Option ROM error
Low operating current trip
Main circuit undervoltage trip
Overtorque trip
UP1
Ot
EF1
EF2
Etn
Software detected earth fault trip
Hardware detected earth fault trip
Auto-tuning error
EtYP
dANP
Inverter typeform and EEPROM typeform mismatch error
Damper trip. When damper function is selected, and damper is closed while the motor
is running.
LOSS
IV analog input loss. Valid when LA15 = 3 and frequency command is selected from
IV analog input terminal.
LEGEND
CPU
—
—
—
—
—
—
—
—
Central Processing Unit
Analog Input Terminal
IV
PCB
Printed Circuit Board
Random Access Memory
Read-Only Memory
Phase 1 Output (T1)
Phase 2 Output (T2)
Phase 3 Output (T3)
RAM
ROM
U-phase
V-phase
W-phase
21
Table 14 — VFD Mode Summary for 50XJ Unit
KEY OPERATON
LED MESSAGE
EXPLANATION
—
0.0
SEtP
PrG
non
Standard monitor mode
Switch to mode selection menu.
Program mode.
Select Status Monitor mode title with U/D keys.
Enter Status Monitor mode by pressing R/W. First monitor
item (motor run direction) is displayed.
S/P/M
S/P/M
S/P/M
R/W
Fr-F
DOWN
60.0
Pressing UP/DOWN views next/previous status variable.
Frequency command value displayed (monitor #1)
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
C 0
Y 228
P 0
A....
b....
O....
t0.00
OC1
OC2
OC3
nErr
Fr-F
Load current (%) monitor (monitor #2)
Input voltage (V) monitor (monitor #3)
Output voltage (V) monitor (monitor #4)
Input terminal status monitor
Input terminal status monitor
Output terminal status monitor
Total RUN time monitor
Past trip #1 monitor
Past trip #2 monitor
Past trip #3 monitor
Past trip #4 monitor
Return to the top menu item
TRIP MESSAGES — Trip messages and their causes are
shown in Table 16.
CLEARING A TRIP — A trip clear can be performed after
the cause of the trip has been removed. To perform a trip clear,
either switch off power to the inverter (keep VFD off until
charge LED turns off) or use the following procedure:
Press STOP. The display will show: CLr. Press STOP again.
The display will show: 0.0, indicating that the trip is cleared
and the display will return to Standard Monitor mode.
If any key other than the STOP key is pressed at the trip
clear command prompt, the trip clear command is aborted and
the display returns to Standard Monitor mode (where the trip
title will be displayed flashing). The trip clear command does
not clear the recorded past faults.
STATUS MONITOR MODE — In Status Monitor mode, it is
possible to monitor the inverter status (frequency command,
output voltage, current, terminal information, etc.). Status
monitor mode is entered by pressing the MON key until the
monitor LED is lit. The present output frequency (which, just
after power is applied, is 0.0) is displayed. (If the ST-CC
terminals are not shorted, OFF will be displayed.)
50BV Variable Frequency Drive Control — The
variable frequency drive is factory wired and programmed for
proper operation with the unit controls; no installation or
service adjustments are normally required.
The VFD default conditions at unit power up are: “0.0 Hz”
in the LED display. When the fan is operating, the LED
displays the output frequency in Hz.
OPERATING KEYPAD — The keypad allows users to en-
able or disable the keypad, input commands from the keypad,
and monitor drive operation. Fig. 7 shows the operating panel
keypad layout and the locations of the keys and display LEDs.
The 4-character LED displays various values, depending
upon what mode is running.
•
In Standard Monitor mode: the LED displays the current
output frequency.
•
In Status Monitor mode: monitors the status conditions
and frequency command value setting.
•
•
In Setup mode: displays setup parameter titles and values.
During a trip: displays the trip title.
The appropriate local/remote LED, which is inset into the
speed control key, is lit when the unit is in local or remote
mode.
KEY FUNCTIONS — Refer to Fig. 8 for the functions of
each key on the keypad.
NON-TRIP MESSAGES — Non-trip messages are those that
may be displayed but do not cause a trip and are not recorded in
the fault history. Table 15 lists the non-trip messages with their
explanations.
If either
or
is pressed continuously, every 0.5 sec
the next/previous item will be displayed. As optional points,
RUN, STOP, displaying the frequency status, and switching to
local/remote and manual/auto modes can be performed.
22
VEC lamp
RUN lamp
MON lamp
PRG lamp
Lights when the inverter is
operating. Blinks when the
automatic acceleration/deceleration
is operating
Lights when the
inverter is in
monitor mode.
Lights when the inverter is
in parameter setting mode.
Lights when sensorless
vector operation control
is running.
ECN lamp
Monitor key
Lights whenenergy-saving
mode is in operation.
Displays operation
frequency, parameters,
and error causes.
Charge Lamp
CHARGE
Indicates that high voltage is
still present within the inverter.
Do not open the terminal
board cover while this is lit.
Built-in
potentiometer lamp
MON ENT
Built-in potentiometer
Operation frequency can
be changed when the
built-in potentiometer lamp
is lit.
RUN
STOP
Up/down key lamp
Pressing up or down
key when this lamp
is lit allows the
Enter key
Down key
setting of operation
frequency.
STOP key
RUN key
RUN key lamp
Every pressing of this key
while the RUN key lamp is
lit will cause a slowdown
stop.
Pressing this key
while the RUN key
lamp is lighted
Lights when the
RUN key is
enabled.
Up key
starts operations.
Fig. 7 — 50BV VFD Display
ALL OF THE BASIC PARAMETERS CAN BE SET BY THE SAME
STEP PROCEDURES.
[STEPS IN KEY ENTRY FOR BASIC PARAMETERS]
SWITCHES TO THE SETTING MONITOR MODE.
SELECTS PARAMETER TO BE CHANGED.
MON
READS THE PROGRAMMED PARAMETER
SETTING.
ENT
CHANGES THE PARAMETER SETTING.
SAVES THE CHANGED VALUE OF THE
PARAMETER SETTING.
ENT
Fig. 8 — 50BV VFD Display Function Keys
23
Table 15 — Non-Trip Messages for the 50BV VFD
ERROR
CODE
PROBLEM
POSSIBLE CAUSES
REMEDIES
OFF (Note 1) ST terminal OFF
• The ST-CC circuit is opened.
• Close the ST-CC circuit.
NOFF
Undervoltage in main
circuit
• The supply voltage between R, S and T is
under voltage.
• Measure the main circuit supply voltage.
If the voltage is at a normal level, the
inverter requires repairing.
rtrY
Retry in process
• The inverter is in the process of retry.
• A momentary stop occurred.
• The inverter is normal if it restarts after
several tens of seconds.
The inverter restarts automatically. Be careful of the
machine because it may suddenly restart.
Err1
CLr
Frequency point
setting error
Clear command
acceptable
• The frequency setting signals at points 1
and 2 are set too close to each other.
• This message is displayed when pressing
the STOP key while an error code is displayed.
• Set the frequency setting signals at points
1 and 2 apart from each other.
• Press the STOP key again to clear the
trip.
EOFF
Emergency stop
command acceptable
• The operation panel is used to stop the
operation in automatic control or remote
control mode.
• Press the STOP key for an emergency stop.
To cancel the emergency stop, press any other key.
HI/LO
Setting error alarm /
An error code and
data are displayed
alternately twice each.
• An error is found in a setting when data is
reading or writing.
• Check whether the setting is made
correctly.
db
DC braking
• DC braking in process
• Normal if the message disappears after
several tens of seconds. (See Note 2.)
In It
Parameters in the
process of initialization
• Parameters are being initialized to default
values.
• Normal if the message disappears after a
while (several seconds to several tens of seconds).
Setup parameters in
• Setup parameters are in the process of
• Normal if the message disappears after a
while (several seconds to several tens of seconds).
the process of being set being set.
Atn
Auto-tuning in process
• Auto-tuning is in process.
• Normal if the message disappears after
several seconds.
NOTES:
1. ST : Terminal of stand by function.
2. When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter, you can judge
the inverter to be normal if “db” disappears when opening the circuit between the terminal and CC.
Table 16 — Trip Messages for 50BV VFD
ERROR COMMUNICATION
PROBLEM
POSSIBLE CAUSES
REMEDIES
CODE
OC1
NO.
1
Overcurrent during
acceleration
• The acceleration time ACC is too short.
• The V/F setting is improper.
• A restart signal is input to the rotating
motor after a momentary stop, etc.
• A special motor (e.g. motor with a small
impedance) is used.
• Increase the acceleration time ACC.
• Check the V/F parameter.
• Use F301 (auto-restart) and F302
(ride-through control).
• Increase the carrier frequency F300.
OC2
OC3
OCR
OCL
2
3
5
4
Overcurrent during
deceleration
Overcurrent during
operation
Arm overcurrent at
start-up
Overcurrent (An
overcurrent on the
load side at start-up) • The motor has too small impedance.
• The deceleration time dEC is too short.
(During deceleration)
• The load fluctuates abruptly.
• The load is in an abnormal condition.
• Increase the deceleration time dEC.
• Reduce the load fluctuation.
• Check the load (operated machine).
• Make a service call.
• A main circuit element is defective.
• The insulation of the output main circuit or • Check the cables and wires for defective
motor is defective.
insulation.
OP1
A
Overvoltage during
acceleration
• The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
• Insert a suitable input reactor.
(3) A system using a thyristor is connected
to the same power distribution line.
• A restart signal is input to the rotating
motor after a momentary stop, etc.
• Use F301 (auto-restart) and F302
(ride-through control).
OP2
B
Overvoltage during
deceleration
• The deceleration time dEC is too short.
(Regenerative energy is too large.)
• F304 (dynamic braking resistor
activation) is off.
• F305 (overvoltage limit operation) is off.
(1) The input voltage fluctuates abnormally.
The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyristor is connected
to the same power distribution line.
• Increase the deceleration time dEC.
• Install a suitable dynamic braking resistor.
• Enable F304 (dynamic braking selection).
• Enable F305 (overvoltage limit operation).
• Insert a suitable input reactor.
24
Table 16 — Trip Messages for 50BV VFD (cont)
ERROR COMMUNICATION
PROBLEM
POSSIBLE CAUSES
REMEDIES
CODE
OP3
NO.
C
Overvoltage during
constant-speed
operation
• The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
• Insert a suitable input reactor.
(3) A system using a thyristor is connected
to the same power distribution line.
• The motor is in a regenerative state
because the load causes the motor to run at
a frequency higher than the inverter
output frequency.
• Install a dynamic braking resistor.
OL1
OL2
D
E
Inverter overload
Motor overload
• The acceleration ACC time is too short.
• The DC braking amount is too large.
• The V/F setting is improper.
• A restart signal is input to the rotating
motor after a momentary stop, etc.
• The load is too large.
• Increase the acceleration time ACC.
• Reduce the DC braking amount F251
and the DC braking time F252.
• Check the V/F parameter setting.
• Use F301 (auto-restart) and F302
(ride-through control).
• Use an inverter with a larger rating.
• The V/F setting is improper.
• The motor is locked up.
• Low-speed operation is performed
continuously.
• An excessive load is applied to the motor
during operation.
• Check the V/F parameter setting.
• Check the load (operated machine).
• Adjust OLN to the overload that the
motor can withstand during operation in a
low speed range.
*EPHO
*EPH1
9
8
Output phase failure • A phase failure occurred in the output line
of the main circuit.
• Check the main circuit output line, motor,
etc., for phase failure.
• Enable F605 (Output phase failure
detection).
Input phase failure
• A phase failure occurred in the input line
of the main circuit.
• Check the main circuit input line for phase
failure.
• Enable F608 (input phase failure
detection).
OH2
*Ot
2Eh
20h
External thermal trip • A thermal trip command is entered from
an external input device.
• Check the external input device.
Over-torque trip
• The load torque rises up to the over-torque • Enable F615 (Over-torque trip selection)
detection level during operation
• Check whether the system is in a normal
condition.
OLr
OH
F
Dynamic braking
• The deceleration time is too short.
• Increase the deceleration time dEC.
• Use a dynamic resistor with a larger
capacity (W) and adjust F308 (PBR
capacity parameter) accordingly.
resistor overload trip • The dynamic braking amount is too large.
10h
Overheat
• The cooling fan does not rotate.
• The ambient temperature is too high.
• The vent is blocked up.
• A heat generating device is installed close
to the inverter.
• The thermistor in the unit is broken.
• Restart the operation by resetting the
inverter after it has cooled down enough.
• The fan requires replacement if it does
not rotate during operation.
• Secure sufficient space around the
inverter.
• Do not place any heat-generating device
near the inverter.
• Make a service call.
*UP1
1E
Undervoltage trip
(main circuit)
• The input voltage (in the main circuit) is
too low.
• Check the input voltage.
• Enable F627 (undervoltage trip
selection).
• To cope with a momentary stop due to
undervoltage, enable F302 (ride-through
control) and F301 (auto-restart).
25
Table 16 — Trip Messages for 50BV VFD (cont)
ERROR COMMUNICATION
PROBLEM
POSSIBLE CAUSES
REMEDIES
CODE
*UC
NO.
1D
Small-current
operation trip
• The output current falls to the low-current
detection level during operation.
• Enable F610 (low-current detection
parameter).
• Check whether the detection level is set
properly to the system.
(F611 and F612)
• If no error is found in the setting, make a
service call.
EF2
E
22h
11h
Ground fault trip
Emergency stop
• A ground fault occurs in the output cable
or the motor.
• During automatic operation or remote
operation, a stop command is entered from
the operation panel or a remote input device.
• Check the cable and the motor for ground
faults.
• Reset the inverter.
Err2
Err3
Err4
Err5
15h
16h
17h
18h
Main unit RAM fault • The control RAM is defective.
Main unit ROM fault • The control ROM is defective.
• Make a service call.
• Make a service call.
• Make a service call.
• Check the remote control device,
cables, etc.
CPU fault trip
• The control CPU is defective.
Remote control
error
• An error arises during remote operation.
EtYP
EEP1
29h
12h
Inverter type error
• The control circuit board (main circuit
board or drive circuit board) is replaced.
• A data writing error occurs.
• Make a service call.
EEPROM fault
• Turn off the inverter, then turn it on again.
If it does not recover from the error, make
a service call.
Etn
28h
Auto-tuning error
• Check the settings of the motor parameters F401to F408
• Check that the motor is not two or more sizes smaller in capacity than the inverter.
• Check that the inverter output cable is not too thin.
• Check that the motor is not running.
• Check that the motor is a three-phase inductive motor.
*With a parameter, you can choose between trip-on and -off.
NOTES:
1. During operation, the following alarms may be displayed, which have the same meaning as previously defined alarms.
• C (overcurrent alarm) — same as OC
• P (overvoltage alarm) — same as OP
• L (overload alarm) — same as OL1/OL2
• H (overheat alarm) — same as OH
2. If two or more problems arise simultaneously, one of the following alarms appears and blinks.
CP, PL, CPL
The blinking alarms, C, P, L, H are displayed in this order from left to right.
26
TROUBLESHOOTING
Refer to Tables 17-21 for troubleshooting information.
Run Test Troubleshooting — The automatic run test
is a diagnostic tool used during unit start-up. Table 17
describes troubleshooting specifically for the automated run
test.
Table 17 — Run Test Troubleshooting
PROBLEM
Control modules do not have lights when unit power on.
Control display does not light up when unit power on.
Run test will not start.
POSSIBLE CAUSE
Transformer open. Circuit breaker open. Power wiring open. Module failure.
Connection location. Interface cable open. Display failure.
Pre-existing ALARM (red)? Not “Logged in” with password.
Switch not in Local.
WARN (yel) does not light during run test.
ALARM (red) does not light during run test.
Wiring open. Lamp failure. Control module failure.
Wiring open. Lamp open. Control module failure.
Run test stops, ALARM (red) light is lit after it blinks once.
Bypass switch to LINE. Mode switch to OFF. Duct high
pressure switch open. Fire shutdown input or jumper open.
Supply air temp out of range. Duct static pressure sensor out of range.
Compressor resistor board wiring error or failure.
Fan does not start/ALARM (red) blinks 2 times.
Fan relay failure.
Run test stop, ALARM (red) light is lit after blinking 3 times.
Wiring open. VFD connection error. VFD setup error. Fan relay failure.
Current isolator failure. Control module failure.
Run test stop, ALARM (red) is lit after it blinks 4 times.
Fan does not increase speed.
VFD connection error. VFD setup error.
Current isolator load adjustment too low.
Fan does not stop after ALARM (red) blinks 5 times.
Fan rotation is backwards.
Fan relay failure.
VFD to motor wiring sequence error. VFD setup error.
Run test stop, ALARM (red) is lit after blinking 6 times.
Compressor 1 does not start.
Wiring open. Compressor resistor board wiring error or failure.
High-pressure switch, low-pressure switch, coil frost switch,
or compressor protection module open. Compressor relay failure.
Contactor failure. Control module failure. No refrigerant charge.
Run test stop, ALARM (red) is lit after blinking 7 times.
Compressor 2 does not start.
Wiring open. Compressor resistor board wiring error or failure.
High-pressure switch, low-pressure switch, coil frost switch,
or compressor protection module open. Compressor relay failure.
Contactor failure. Control module failure. No refrigerant charge.
Run test stop, ALARM (red) is lit after blinking 8 times.
Compressor 3 does not start.
Wiring open. Compressor resistor board wiring error or failure.
High-pressure switch, low-pressure switch, coil frost switch,
or compressor protection module open. Compressor relay failure.
Contactor failure. Control module failure. No refrigerant charge.
Run test stop, ALARM (red) is lit after blinking 9 times.
Compressor 4 does not start.
Wiring open. Compressor resistor board wiring error or failure.
High-pressure switch, low-pressure switch, coil frost switch,
or compressor protection module open. Compressor relay failure.
Contactor failure. Control module failure. No refrigerant charge.
Compressor rotation is backwards.
“C” message in I/O status display.
Field power wiring sequence error. Compressor power wiring sequence error.
No input signal/communication failure.
“Service” message in I/O status display.
“Supervisor” message in I/O status display.
ALARM (red) always on, will not enter run test.
Value is forced from 6400 keypad entry.
Value is forced from network communication (i.e., PC).
SAT, DSP, CSMUX, DHS, or PHASE input values out of range. Mode switch OFF.
Forcing and Clearing an Input or Output — Dur-
ing unit operation and/or troubleshooting, it may be necessary
or desirable to clear an input or output. Tables 18 and 19
describe the procedure for clearing inputs and outputs.
Table 18 — Forcing an Input or Output
STEP # INSTRUCTION/ACTION
1. Press 3, SET, ENTER
RESULT
“Controller Password”
2. Press ENTER
3. Press 1111, ENTER
4. Press STAT
“Log in to Controller” “Enter Password”
“Log in to Controller” “Logged in”
“Hardware Points”
5. Press ENTER
“Supply Air Temperature”
6. Press down arrow to obtain desired item
(NOTE: order is PCB1 I/O, PCB2 I/O, PCB3 I/O)
7. Key in force value (1=on/start, 0 = off/stop), ENTER
force value/status “Service”
Table 19 — Clearing a Forced Input or Output
STEP # INSTRUCTION/ACTION
RESULT
1. Press 3, SET, ENTER
2. Press ENTER
3. Press 1111, ENTER
4. Press STAT
“Controller Password”
“Log in to Controller” “Enter Password”
“Log in to Controller” “Logged in”
“Hardware Points”
5. Press ENTER
“Supply Air Temperature”
6. Press down arrow to obtain desired item
7. Press CLEAR, ENTER
(NOTE: order is PCB1 I/O, PCB2 I/O, PCB3 I/O)
auto value/status (NOTE “Service” must be gone)
27
Table 20 — Alarms Displayed at Unit LID
FUNCTION ALARM MESSAGE (Actual Text)
CAUSE
UNIT RESPONSE (See Notes)
RESET
SAT xx.x dF outside
limit of xxx.x dF
SAT reads out of prescribed range
for 5 sec. during operation
Unit shuts down and
indicates alarm
Automatic
SAT
Duct Static Sensor Failure
Duct Pressure Sensor reading is out of
range (i.e., likely faulty sensor or circuit).
External Fire Alarm input opens for 5 sec.
Pressure rises above 3.0 in.H2O during
operation. Set point adjustable on the switch.
Used for Off position of switch on smaller
units with one controller
Unit shuts down, indicates alarm
Automatic
DSP_ALM
FSD
Fire Shutdown
Duct High Static Pressure
Unit shuts down, indicates alarm
Unit shuts down, indicates alarm
Automatic
Automatic
DHS
CSMUX x.xx Volts outside
limit of x.xx Volts
Compressor safety circuit Resistor Board
reads out of prescribed range for 5 sec.
during operation
Unit shuts down and indicates
alarm
Automatic
CSMUX
Check Condenser Water Flow
Change Filters
Waterflow Switch contacts are open at startup, Compressor Cooling shuts down, Automatic
CDWF
FLTS
or go open for 5 sec. during operation.
locks out and indicates warning
Filter pressure drop exceeds Filter Pressure
Switch setting (and contacts open) for 5 sec.
Unit operates normally,
but still indicates Warning
Automatic
Economizer Freeze Condition
Economizer Freeze Switch contacts for 5 sec. Warning indicated for 15 minutes Automatic
open during operation.
turns off ventilation request, then
unit shuts down and Econo valve
opens, pump request stays on,
and Alarm indicated
FREEZ
C1_ALM
C2_ALM
C3_ALM
C4_ALM
Compressor 1 Fault
Compressor 2 Fault
Compressor 3 Fault
Compressor 4 Fault
Compressor safety circuit opens for 2 sec.
Unit shuts that compressor down, Automatic
and indicates Warning, but retries
2 more times before locking it out.
Check Supply Fan
Duct Pressure Sensor reading is below .3 in.
H2O at 10 sec. after starting fan, or during
operation, or reads above .3″ when fan is
supposed to be Off.
If on but indicates off cooling,
and heating will be disabled
warning light will be on
Automatic
SFS
EWT xx.x dF outside
limit of xxx.x dF
MA_RA xx.x dF outside
limit of xxx.x dF
EWT reads out of prescribed range for 5 sec.
or more
ma_ra reads out of prescribed range for 5 sec. Indicates warning
or more
Phase monitor activates (see “Phase
Loss/Reversal Protection Switch” on page 5)
for 5 sec. during operation.
Indicates warning
Automatic
Automatic
Automatic
EWT
MA_RA
Phase Loss
Unit shuts down, indicates alarm
PHASE
BYPAS switch in Bypass position or Off,
local remote in Off position
BYPAS
NOTES:
1. Unit display will indicate alarm by displaying “There is 1 Alarm” or
“There are X alarms”, for the active alarms in the controller.
2. Red light on, indicating alarm.
3. Yellow light is on, indicating a warning.
again. A system alarm will be generated and displayed at the
keypad.
Standard Diagnostic Features, Alarm and
Warning Lights
DUCT HIGH STATIC INPUT (DHS) — This air switch
provides over pressurization protection for the ductwork. It is
factory installed in the unit. The switch is a normally open
switch, with adjustable manual setting (range is 1 to 5 in. wg
default setting is 3.0 in. wg). Upon switch closure, the control-
ler outputs will be forced to off with safety forces, the alarm
output will close and the red Alarm light will be lit. A system
alarm will be generated and displayed on the unit keypad. Unit
reset is automatic when the duct pressure is again below the
switch setting minus the device hysteresis.
COMPRESSOR MULTIPLEX (MUX) BOARD — A re-
sistance board is used to generate a variable voltage input to the
controller to determine compressor status. If the voltage output
from this board gets out of the acceptable range the controller
outputs will be forced to off with safety forces, the alarm
output will close and the red Alarm light will be lit. A system
alarm will be generated and displayed on the unit keypad. Unit
reset is automatic when the Mux board has a valid reading
again. The valid range is between 1.5 and 10 vdc. The table
below indicates what voltages correspond to the compressor
status indicated in the controller.
SUPPLY AIR TEMPERATURE SENSOR FAILURE — If
the supply air temperature sensor fails and indicates either
245 F from a short or -40.0 F from and open sensor the control-
ler outputs will be forced to off with safety forces, the alarm
output will close and the red Alarm light will be lit. A system
alarm will be generated and displayed on the unit keypad. Unit
reset is automatic when the supply air sensor has a valid
reading again.
DUCT STATIC PRESSURE SENSOR FAILURE — If the
duct static pressure sensor fails and indicates either 5.0 inches
from a short or 0.0 inches from and open sensor the controller
outputs will be forced to off with safety forces, the alarm
output will close and the red Alarm light will be lit. A system
alarm will be generated and displayed on the unit keypad. Unit
reset is automatic when the supply air sensor has a valid
reading again.
FIRE/SHUTDOWN INPUT (FSD) — This is a normally
closed input, which when opened, deenergizes an isolation
relay in the unit, opening the input to the controller. When this
input turns opens, all control outputs are immediately turned
off, including the fan. Fire forces will be displayed on the
outputs. Unit reset is automatic when the FSD input is closed
28
Table 21 — Compressor MUX Board Voltages
A phase loss reversal switch may be installed in the unit to
detect over, under voltage conditions and phase loss or reversal.
Upon switch opening, the controller outputs will be forced to off
with safety forces, the alarm output will close and the red Alarm
light will be lit. A system alarm will be generated and displayed
on the unit keypad. Unit reset is automatic when the voltage and
power phases have been restored.
ECONOMIZER COIL FREEZE PROTECTION SWITCH —
This switch is installed in the 50XJ unit when the economizer
coil is provided. In the event the freeze protection switch
contacts open, the ventilation request output will be closed for
15 minutes and the Warning light will light. If the freeze
protection switch contacts are still open after 15 minutes, the
supply fan will be stopped, all compressor cooling will stop,
the economizer valve will open to 100%, the pump request
output will remain on, and the Alarm light will light. This will
maintain condenser water flow through the coil to prevent
freezing the coil while stopping all other operations that could
have contributed or will be affected by the freeze condition.
Unit reset is automatic when the contacts on the freeze
protection switch close again. The contacts on the freeze
protection switch open below 37 F.
COMP
None
VOLTS
1.86
RANGE
1.50 < V < .95
1
2
1,2
3
2.88
3.59
4.44
5.13
last val < = V < 2.95
last val < = V < 3.68
last val < = V < 4.55
last val < = V < 5.25
last val < = V < 5.85
and CMP4 is on
4
5.71
1,3
1,4
5.85
6.39
last val < = V < 5.99
last val < = V < 6.51
and CMP4 is on
2,3
2,4
6.36
6.87
last val < = V < 6.54
last val < = V < 7.03
and CMP4 is on
1,2,3
1,2,4
3,4
1,3,4
2,3,4
1,2,3,4
6.99
7.46
7.94
8.45
8.81
9.26
last val < = V < 7.15
last val < = V < 7.63
last val < = V < 8.11
last val < = V < 8.58
last val < = V < 8.99
V > 8.99
SUPPLY FAN STATUS — Supply fan status is determined
by the duct static pressure sensor. If the fan is operating and a
fan speed signal is sent to the variable frequency drive, the duct
static pressure must become greater than the supply fan status
high set point (SETPT01) for the supply fan status software
point to turn on. When the duct static pressure becomes lower
than the supply fan status low set point, the supply fan status
will indicate OFF. If at any time the commanded state of the
supply fan does not agree with the supply fan status for more
than a minute, a supply fan status warning will be issued and
the warning light will be lit.
COMPRESSOR STATUS — Compressor status is determined
from the compressor MUX voltage input to the OMNIZONE
controller. If at any time the compressor status indicates off for
more than 30 seconds when the compressor commanded state
is on, the compressor will be turned off with a safety force and
the controller will try to start the compressor after five minutes.
If the compressor status does not indicate on for more than
30 seconds then the compressor will be turned off again with a
safety force for ten minutes. The controller will then try to
restart the compressor a second time. If the compressor status
does not come on within 30 seconds the compressor will be
turned off for 15-minutes this time. After the 15-minute delay
the controller will try to restart the compressor for a third time.
If the compressor does not start it will be locked out for this
operating cycle and will not be restarted until the OMNIZONE
controller goes through an off cycle where the cooling and
supply fan are shut down. When the compressor is going
through the three restarts or when it is locked out the Warning
light will be lit and the specific compressor alarm will be
indicated on the display and via communications. The three
strikes compressor test is reset automatically if the compressor
status comes on while the compressor is on.
CONDENSER WATER FLOW — This is an optional
switch that can be used with the OMNIZONE™ controller. A
thermal dispersion flow switch detects water flowing past the
sensor element and closes normally open contacts that energize
a relay with normally open contacts to the unit controller. If no
flow switch is installed, a jumper must be in place to indicate
that there is water flow all the time in order for the economizer
and compressors to operate. A configuration decision is used to
indicate if a flow switch is installed and disable alarms from the
flow switch. When the flow switch is installed, the controller
will check for water flow when flow is requested for unit
operation. The controller will also test or to see if there is water
flow when the unit is not operating. If there is no flow when
the unit is operating or if there is flow when the unit is not
operating, the warning relay will energize and the yellow light
will be lit. If only loss of flow indication is desired, the
configuration for the flow switch may be set to no and the
controller will only energize the warning relay and turn on the
yellow light if there is a loss of flow while the unit is in
operation.
DIRTY FILTERS INPUT — This air pressure delta switch is
factory installed in the 50XJ unit. It receives 5 vdc from the
unit controller and monitors air pressure delta across the return
air filters. Switch is normally open, with manually adjustable
setting at the switch between 0.5 to 1.5 in. wg. Upon closure,
controller should wait to assure closure for minimum 1 minute,
and then indicate an alarm both via its Alarm Output and via
communications. However, all other unit operation should
remain normal.
29
APPENDIX A — WIRING DIAGRAMS
VFD2
( C )
C O M M O N
VFD1
( R ) A C 2 4 V
1
2
3
CSMUX
30
31
ECONO MBV
24VAC
VFD2
Close
Open
( C )
C O M M O N
VFD1
( R ) A C 2 4 V
CSMUX
32
33
1
2
3
1
2
4
34
VFD2
( C )
C O M M O N
VFD1
( R ) A C 2 4 V
CSMUX
35
VFD2
( C )
C O M M O N
VFD1
( R ) A C 2 4 V
CSMUX
36
LEGEND AND NOTES FOR ALL 50BV WIRING DIAGRAMS
LEGEND
ECONO — Economizer Valve/Damper Control
ALARM — Unit Alarm Relay (Critical Fault)
ALM-CM— Alarm/Warning Relay Common
RESET
ROCC
SAT
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
External Reset
EWT
FLTS
— Entering Water Temp. Sensor
— Filter Status Switch
Remote Occupancy
Supply Air Temp. Sensor
Space/Zone Temperature Sensor
Supply Fan Start/Stop Relay
0-10 VDC Signal Isolator for VFD
Switch
AO
— Analog Output
FREEZ — Freeze Thermostat
AQUA — Aquastat
SPT
(Water Economizer)
BM
— Blower Motor
SF
FRZ
FSD
GND
HIR
— Freeze Thermostat (DX Circuit)
BPS_S — Fan Start/Stop Relay
(VFD Bypass Mode)
SPEED
SW
— Fire Alarm/Shutdown
— Ground
BR
— Blower Relay
T
TB2
Transformer
Terminal Block for Field Connections
Transformer
VAV Terminals Control
VAV Terminals Open
Ventilation Output
Variable Frequency Drive
Unit Warning Relay
(Non-Critical Fault)
— Heat Interlock Relay
— High Refrigerant Pressure Switch
— Hot Water Valve
BYPAS — VFD Bypass Control
HPS
HWV
LPS
CBR
CC
— Circuit Breaker
— Compressor Contactor
TRANS
TRMCT
TRMOP
VENTR
VFD
— Low Refrigerant Pressure Switch
CDWF — Condenser Waterflow Relay
CDWFS — Condenser Waterflow Switch
MA_RA — Mixed/Return Air Temp. Sensor
MBVR — Motorized Ball Valve Relay
CLO
CMP
— Compressor Lockout Control
— Compressor Control Relay
MSR
OLR
PCB1
— Local/Remote Control Relays
— Compressor Motor Protector
— Unit Control Board
WARN
COMPR — Compressor
CSMUX — Signal Multiplexer-Comp Status
DEHUM — External Dehumidification
Unit Wire
PCB2,3 — I/O Expansion Board
PHASE — Phase/Rotation Monitor
PHASER— Phase Monitor Relay
DHS
DO
DSP
— Duct High Static Limit Switch
— Digital Output
— Duct Static Pressure Transducer
Field Wiring
RAT
— Return Air Thermostat
NOTES:
1. Partial wiring shown on both power and control diagrams.
2. Class 2 transformer TRANS-1 is wired into separate circuit. Do not interconnect other
transformers or circuits; circuit separation or compressor transformers from low voltage
control panel transformers shall be maintained.
3. Shielded wire shall have drain wire connected to VFD ground screw. The floating end
of the drain wire shall be insulated.
4. Shielded wire shall have drain wire connected to the control panel, adjacent to the
PCB. The floating end of the drain wire shall be insulated.
37
TB4
N
NOTE 1
GRN
T1
GRN
PCB1
1
2
3
CB1
J2
503/BRN
502/RED
HRN5
HRN5
2
24 V
502
1
501
500
504
X1
X2
RED
RED
ORN
BRN
503/BRN
16
15
14
13
12
11
10
9
8
7
6
5
510/WHT
NOTE 4
511
505
512/YEL
592/BRN
514/BLK
RED
WHT
BRN
SPEED
IN OUT
VFD
CC
592
700
GRN
-
-
510
621
BRN
0
ALARM 1
WHT
BRN
515/WHT
516/GRA
529/YEL
532/PNK
612/BLU
514
701
+
+
J4
IV
BLK
WHT
SW1
1
0
1 2 3 4 5 6 7 8
GRD
513
YEL
SF
SW2
1 2 3 4 5 6 7 8
YEL
INT
703/BLK
702/RED
4
2
ST
CC
F
EXT
4
3
2
1
SW3
1 2 3 4 5 6 7 8
512
507
4-20mA
OTHER
0
WARN 1
YEL
BRN
SW4
1 2 3 4 5 6 7 8
0-10VDC
4-20mA
CSMUX
V
HRN4
5
SW5
712/RED
536/RED
704/BLK
705/RED
710/GRN
711/WHT
550/BRN
551/BLU
587/BRN
588/ORN
552/BRN
553/BLK
18
17
16
15
14
13
12
11
10
9
8
7
6
5
DO
AO
1
2
3
3
4
4
537
538
S4
RED
RED
SW6
DO
AO
1
2
509
509
BRN
EWT
DHS
C
4
3
2
1
S
BRN
542
543
4
3
2
1
6
6
6
6
8
8
8
8
CMP4
CMP3
CMP2
CMP1
GRA
GRA
0
0
SF
1
1
515/WHT
506/BRN
541
540
539
544
545
2
2
2
4
4
4
ROCC
CDWF
FSD
YEL
YEL
HRN3
1
HRN4
6
J3
546
547
516
517
518
520
BRN
519
CMP4
2
2
2
2
3
1
PNK
PNK
GRA
GRA
GRA
BRN
CLO4
LOGIC
HRN3
12
548
549
525
524
BRN
BLU
BLU
BRN
554/VIO
HRN3
2
+
712/RED
DSP
4
3
2
1
529
530
531
0
0
0
CMP3
1
713/BLK
714/GRN
715/WHT
-
3
1
YEL
YEL
YEL
J7
2
CLO3
LOGIC
3
3
1
1
SAT
526
BRN
NOTE 5
HRN3
3
532
533
534
CMP2
1
1
3
1
PNK
PNK
PNK
GRN
CLO2
LOGIC
1
2
3
2
527
561/BRN
557/RED
BRN
J7
J2
PCB2
16
15
14
13
12
11
10
9
8
7
6
5
HRN3
4
612
613
535
CMP1
T2
564/YEL
3
1
BLU
BLU
BLU
CLO1
LOGIC
528
BRN
623/WHT
567/PNK
609/ORN
610/VIO
568/BLU
622/BLK
561/BRN
GRN
CB2
HRN5
3
HRN5
X2
4
J4
24 V
635
556
555
560
X1
RED
RED
ORN
BRN
SW1
1 2 3 4 5 6 7 8
1
0
SW2
1 2 3 4 5 6 7 8
INT
EXT
4
3
2
1
SW3
1 2 3 4 5 6 7 8
4-20mA
OTHER
SW4
1 2 3 4 5 6 7 8
0-10VDC
4-20mA
565/BRN
508/BRN
623
0
HIR
1
1
1
1
3
18
17
16
15
14
13
12
11
10
9
8
7
6
5
SW5
WHT
DO
AO
1
2
3
3
4
4
SW6
564
DO
AO
1
2
0
0
0
1
TRMOP
TRMCT
VENTR
CDWF
620/BRN
566/BRN
506/BRN
599/BRN
YEL
569/GRA
568
BLU
570/BLU
727/GRN
728/WHT
J3
622
FREEZ
BLK
571/YEL
WHT
CDWFS
CB3
BRN
WHT
BLK
600/RED
558/RED
1
2
4
716/GRN
717/WHT
724/GRN
725/WHT
4
3
2
1
BLU
FLTS
MA_RA
3
T3
24 V
GRN
HRN5
HRN5
6
604
603
602
BRN
5
X1
X2
RED
ORN
NOTE 5
607/BRN
MVLV
W1
RA (CCW)
633/BRN
634/RED
609/ORN
COMMON
24 VAC
605/RED
W2
4-20mA
0-20 mA
ECONO
W1
RA (CCW)
608/BRN
606/RED
COMMON
24 VAC
W2
610/VIO
0-20 mA
4-20mA
580/BRN
1
1
FSD
3
3
558/RED
559/RED
581/PNK
573/YEL
598/YEL
LOCAL
OFF
ROCC
MODE
SW
574
BRN
569/GRA
REMOTE
575/
BRN
BLK
J1
50XJ Low Voltage Control Wiring
38
H4 H3 H2 H1
TB3
N
T4
6
TB2
115 V
Bussman MDQ5
5 A, 250 V
301
300
302
302
FU27
X1
X2
115 V
BLK
BLK
WHT
WHT
HRN1
HRN1
306
307
BLK
309
308
1
1
6
BLK
WHT
WHT
CMP1
HRN1
310
BLK
311
312
BLU
2
4
2
2
BLK
T1
T2
OLR1
HRN1
LPS1
HPS1
FRZ1
312
313
314
315
316
318
320
M1
M2
3
3
A
C1
B
BLU
BLU
BLU
BLU
BLU
BLU
WHT
CMP2
HRN1
322
323
2
4
4
4
BLK
PNK
T1
T2
OLR2
HRN1
LPS2
HPS2
FRZ2
323
324
325
326
327
329
M1
M2
5
5
A
C2
B
PNK
PNK
PNK
PNK
PNK
PNK
HRN2
HRN2
332
BLK
333
BLK
335
334
WHT
1
1
6
6
WHT
CMP3
HRN2
337
338
2
4
2
2
BLK
YEL
T1
T2
OLR3
HRN2
HPS3
LPS3
FRZ3
338
339
340
341
342
YEL
344
M1
M2
3
3
A
C3
B
YEL
YEL
YEL
YEL
YEL
CMP4
HRN2
348
349
2
4
4
4
BLK
GRA
T1
T2
OLR4
HRN2
LPS4
HPS4
FRZ4
349
350
351
352
353
GRA
355
M1
M2
5
5
A
C4
B
GRA
GRA
GRA
GRA
GRA
BYPAS*
10
BPS_S*
359
361
2
4
9
BLK
WHT
NOTE 1
CUVL*
UVC
DS1*
362
BLK
363
VIO
364
BLK
WHT
WHT
SWITCH SETTINGS
Open
ID
Close
45 +/- 6 °F
FRZ1-4
HPS1-4
LPS1-4
30 +/- 5 °F
360 +/- 10 PSIG
264 +/- 15 PSIG
27 +/- 4 PSIG
67 +/- 7 PSIG
50XJ 115V Control Wiring
39
USE COPPER SUPPLY WIRES.
POWER WIRING
50XJ - 460 V Unit
DISC1*
TB1
VFD
IFM
2
206/BLK
103
104
107
100/BLK
L1
FU1
FU2
FU3
R
S
T
U
V
BLK
BLK
BLK
207/BLK
108
109
112
101/BLK
L2
1
YEL
YEL
YEL
208/BLK
113
114
117
102/BLK
L3
W
3
BLU
BLU
BLU
GRN
GRN
GRN
GND
E
I
GND
5
PHASE*
1
SW1
Phase rotation
sequence is
ABC (L1-L2-L3).
201
V
10
BLK
Note 1
202
2
YEL
203
3
BLU
Note 1
Current Loop
of CLO1
COMP1
C1
127
128
129
BLK
132
YEL
135
BLU
FU7
FU8
FU9
L1
T1
1
2
3
BLK
BLK
GRN
CH1
130
131
YEL
L2
L3
T2
T3
YEL
133
134
BLU
BLU
136/BLK
137/BLK
Current Loop
of CLO2
C2
C3
C4
COMP2
138
139
140
FU10
FU11
FU12
L1
L2
L3
T1
T2
T3
1
2
3
BLK
BLK
BLK
GRN
CH2
141
142
YEL
143
YEL
YEL
144
145
146
BLU
BLU
BLU
147/BLK
148/BLK
Current Loop
of CLO3
COMP3
149
150
151
FU13
FU14
FU15
L1
L2
L3
T1
T2
T3
1
2
3
BLK
BLK
BLK
GRN
CH3
152
153
YEL
154
YEL
YEL
155
156
157
BLU
BLU
BLU
158/BLK
159/BLK
Current Loop
of CLO4
COMP4
160
161
162
FU16
FU17
FU18
L1
L2
L3
T1
T2
T3
1
2
3
BLK
BLK
BLK
GRN
CH4
163
164
YEL
165
YEL
YEL
166
167
BLU
168
BLU
BLU
169/BLK
170/BLK
T1
193
YEL-COM
RED-200V
ORN-230V
BLK-460V
X2
BLK
Note 1
Note 2
194
X1
X2
BLU
T2
195
YEL-COM
RED-200V
ORN-230V
BLK-460V
BLK
Note 1
Note 2
196
X1
X2
BLU
T3*
204
YEL-COM
RED-200V
ORN-230V
BLK-460V
BLK
Note 1
Note 2
FUSES 1-18 ARE 600 V, CLASS RK-5 FUSES.
FUSES 25-26 ARE 600 V, CLASS CC FUSES.
205
X1
X2
BLU
460 V
15 HP 35 A
20 HP 40 A
25 HP 60 A
30 HP 80 A
40 HP 80 A
50 HP 100 A
FUSE
USAGE
T4
197
198
Com
H1
FU25
BLK
BLK
200V
H2
FU1-3
Note 1
230V
H3
199
200
460V
FU26
H4
X1
BLU
BLU
10 Ton Compressor 30 A
13 Ton Compressor 40 A
15 Ton Compressor 40 A
20 Ton Compressor 50 A
25 Ton Compressor 60 A
3 A
FU 7-18
FU 25-26
50XJ Power Wiring
40
J7
2
3
3
1
1
GRN
PCB3
1
2
3
2
TRAN
24 V
GRN
J7
CB
J2
X1
X2
16
15
14
13
12
11
10
9
J4
DEHUM
0
1
Exhaust
Fan Control
4-20 mA
SW1
1 2 3 4 5 6 7 8
+
-
1
0
TOWER
PUMP
0
0
0
0
0
0
1
1
1
1
1
1
SW2
1 2 3 4 5 6 7 8
INT
EXT
8
HEAT
4
SW3
1 2 3 4 5 6 7 8
7
6
4-20 mA
OTHER
HEAT
3
5
4
SW4
1 2 3 4 5 6 7 8
HEAT
2
3
0-10 VDC
4-20 mA
2
HEAT
1
1
SW5
18
17
16
15
14
13
12
11
10
9
1
2
2
3
3
4
4
DO
AO
SW6
1
DO
AO
Outdoor Air Temperature
Indoor Relative Humidity
J3
+
-
-
8
+
7
Indoor Air Quality
6
Leaving Water Temp
5
4
+
-
3
Building Pressure
Tower Sump Temp
2
1
50BV,XJ Accessory Control Module (PCB3) Schematic
41
LEGEND AND NOTES FOR ALL 50XJ WIRING DIAGRAMS
LEGEND
SAT
SPT
SF
—
—
—
—
—
—
—
—
—
—
Supply Air Temp. Sensor
Space/Zone Temperature Sensor
Supply Fan Start/Stop Relay
0-10 VDC Signal Isolator for VFD
Switch
FREEZ — Freeze Thermostat
ALARM — Unit Alarm Relay (Critical Fault)
ALM-CM— Alarm/Warning Relay Common
BPS_S — Fan Start/Stop Relay
(VFD Bypass Mode)
(Water Economizer)
FRZ
FSD
FU
— Freeze Thermostat (DX Circuit)
SPEED
SW
— Fire Alarm/Shutdown
— Fuse
BYPAS — VFD Bypass Control
GND — Ground
T
Transformer
C
— Compressor Contactor
— Circuit Breaker
TB1
TB2
TB3
TB5-7
Power Distribution Terminal Block
120 V-Hot Terminal Block
120 V-Neutral Terminal Block
Terminal Blocks for
Field Connections
Tower Request
HEAT — Electric Heat Stage Control
CB
HIR
HPS
— Heat Interlock Relay
— High Refrigerant Pressure Switch
CDWF — Condenser Waterflow Relay
CDWFS — Condenser Waterflow Switch
HRN — Harness
CH
CLO
CMP
— Crankcase Heater
— Compressor Lockout Control
— Compressor Control Relay
HWV — Hot Water Valve
IFM
J
LPS
— Indoor Fan Motor
TOWE
R
—
— Jumper Wire
COMP — Compressor
TRMCT
TRMOP
VENTR
VFD
—
—
—
—
—
VAV Terminals Control
VAV Terminals Open
Ventilation Output
Variable Frequency Drive
Unit Warning Relay
(Non-Critical Fault)
— Low Refrigerant Pressure Switch
CSMUX — Signal Multiplexer-Comp Status
CUVL — UVC Light For Indoor Coil Area
DEHUM — External Dehumidification
MA_RA— Mixed/Return Air Temp. Sensor
MVLV — Modulating Valve (Econ)/
Heat Pres. Ctl.
DHS
— Duct High Static Limit Switch
OLR — Compressor Motor Protector
PCB1 — Unit Control Board
PCB2,3— I/O Expansion Board
PHASE— Phase/Rotation Monitor
PUMP — Water Pump Request
RESET — External Reset
WARN
DISC1 — Disconnect Switch
DS
DSP
— Door Switch
— Duct Static Pressure Transducer
Optional Wiring
(Optional Items Noted With “*”)
ECONO — Economizer Valve/Damper
Control
— —
Field Wiring
EWT
FLTS
— Entering Water Temp. Sensor
— Filter Status Switch
ROCC — Remote Occupancy
NOTES:
1. Partial wiring shown on both power and control diagrams.
2. All class 2 transformers are wired into separate circuits. Do not interconnect these
transformers or circuits; circuit separation shall be maintained.
3. On 200/240 v units, the transformers are factory wired for 240 v. For 200 v applica-
tions, move the blue wire to the 200 v tap of each transformer.
4. Shielded wire shall have drain wire connected to VFD ground screw. The floating end
of the drain wire shall be insulated.
5. Shielded wire shall have drain wire connected to the control panel, adjacent to the
PCB. The floating end of the drain wire shall be insulated.
42
APPENDIX B — CONTROL SCREENS
Display Screens
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
OMNIZONE::HWP01-32:Hardware points Table 1
Supply Air Temperature
Duct Static Pressure
Comp. Status MUX
67
dF
SAT
0.2
in H2O
Volts
DSP
1.86
Enable
Yes
CSMUX
FSD
Fire Alarm/Shut Down
Cond. Water Flow Switch
Remote Occupancy
Duct High Press. Switch
Entering Water Temp.
Compressor 1 Relay
Compressor 2 Relay
Compressor 3 Relay
Compressor 4 Relay
Supply Fan/VFD
CDWF
ROCC
DHS
Disable
Normal
69.9
Stop
Stop
Stop
Stop
Stop
0
Off
Off
77.2
Clean
Normal
0
dF
EWT
CMP1
CMP2
CMP3
CMP4
SF
VFD Speed Signal
%
SPEED
WARN
ALARM
MA_RA
FLTS
PHASE
RESET
FREEZ
SPT
BYPAS
PRES
VENTR
TRMCT
ECONO
MVLV
HWV
Non Critical Fault
Critical Fault
Mixed/Return Air Temp
Dirty Filter Status
dF
Phase Loss Protection
Ext. Supply Air Reset
Water Econ. FreezeStat
Space_Reset Sensor
VFD Bypass Enable
Head Pressure(Comp1)
Ventilation Request
dF
Normal
79.2
Disable
118.76
Close
No
dF
PSIG
VAV Terminals Control
2-position/Econo Valve
Reverse/Head Press Ctrl
Hot Water Valve
Heat Interlock Relay
Bypass Start_Stop
VAV Terminals Open MAX
0
%
%
%
100
Control
0
Off
HIR
BPS_S
TRMOP
Stop
Close
OMNIZONE::HWP33-64: Hardware points table 2
Cooling Tower Sump Temp.
Building Static Milliamp
Condenser Leaving Water
Indoor Air Quality
57.5
12.51
70.3
587.21
49.7
76.1
Off
dF
ma
dF
TWR
BSP
LWT
IAQ
Indoor Relative Humidity
Outdoor Air Temp.
%
dF
IRH
OAT
Heat Stage 1
HEAT1
HEAT2
HEAT3
HEAT4
PUMP
TOWER
EXH
Heat Stage 2
Off
Heat Stage 3
Off
Heat Stage 4
Off
Pump Request
Off
Cooling Tower Request
Exhaust Fan
Off
0
%
Ext. Dehumidification
Stop
DEHUM
OMNIZONE::SWP65-96:Software Points
Compressor 1 Status
Compressor 2 Status
Compressor 3 Status
Compressor 4 Status
Bypass Acc Panel Secure
DX VAV RESET Control
Factory/Field Test
Off
CLO1
CLO2
CLO3
CLO4
BP_SAFE
VAVRESET
FLDTST
BSP_IN
Off
Off
Off
No
0
dF
Stop
Building Static Pressure
Time Clock
0.03
in H2O
Off
TIMCLOCK
COOLOK
SFS
Cooling
Disable
Off
Supply Fan Status
Control
Control
Ok to run Fan
No
OKFAN
OK Fan + Sup. Fan Stat
Fan + Cond. Water Flow
Equipment Mode
FALSE
FALSE
Cool
SF_SFS
FAN_CDWF
MODE
Activate Evacuation Mode
Space Control Point
Mod. Econ Enabled
Head Pressure Control
Economizer Control Temp.
Compressor Cooling
Duct Static Failure
Compressor 1 Alarm
Compressor 2 Alarm
Compressor 3 Alarm
Compressor 4 Alarm
Cond. Flow Alarm Status
Disable
74
No
EVAC
dF
dF
CTRLPT
ECON_OK
HEAD
Control
Control
Disable
77.22
Disable
Normal
Normal
Normal
Normal
Normal
Disable
ECONPT
COMPRES
DSP_ALM
C1_ALM
C2_ALM
C3_ALM
C4_ALM
CDWF_ST
Control
43
Display Screens (cont)
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
OMNIZONE:Custom Configuration
Compressor Stages
Reset Ratio
2
3
0
0
1
0
0
2
0
0
NUM_CMP
RSET_RTO
CDFW_SWT
EWT_SNS
EWT_RST
MOD_ECON
FLOW_TYP
MARA_SNS
PHAS_SWT
FREZ_SWT
ECON_SET
SPT_SNS
dF
CDWF 0=NO,1=YES
ECON 0=NO,1=YES
EWT Reset 0=NO,1=YES
MOD.VLV 0=NO,1=YES
0=CONST.,1=VARIABLE
0=RAT,1=MAT,2=NONE
PHASE 0=NO,1=YES
FREEZ 0=NO,1=YES
ENABLE ECON.
68
0
dF
SPT 0=NO,1=YES
PRES 0=NO,1=YES
TWR 0=NO,1=YES
LWT 0=NO,1=YES
IAQ 0=NO,1=YES
IRH 0=NO,1=YES
BSP 0=NO,1=YES
BSP Range
0
SPT_SNS
0
TWR_SNS
LWT_SNS
IAQ_SNS
0
0
0
IRH_SNS
0
BSP_SNS
BSP_RNG
BSP_LOW
1.00
-0.5
in H2O
in H2O
BSP LOW VALUE
Setpoints
OMNIZONE::SETPT01: Supply fan Status
Occupied Lo Setpoint
0.3
0.4
0.3
0.4
in H2O
in H2O
in H2O
in H2O
OccLow
Occupied Hi Setpoint
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
OMNIZONE::SETPT02: VAVRESETbaseline
Occupied Lo Setpoint
0
0
0
0
dF
dF
dF
dF
OccLow
Occupied Hi Setpoint
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
OMNIZONE::SETPT03: Heat\Cool Mode & Reset
Occupied Lo Setpoint
70
74
55
85
dF
dF
dF
dF
OccLow
Occupied Hi Setpoint
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
OMNIZONE::SETPT04: Head Pressure Control
Occupied Lo Setpoint
225
225
225
225
PSIG
PSIG
PSIG
PSIG
OccLow
Occupied Hi Setpoint
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
OMNIZONE::SETPT05: Supply Static Pressure
Occupied Lo Setpoint
1.5
1.5
1.5
1.5
in H2O
in H2O
in H2O
in H2O
OccLow
Occupied Hi Setpoint
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
OMNIZONE::SETPT06: Supply Air Temperature
Occupied Lo Setpoint
55
55
55
55
dF
dF
dF
dF
OccLow
Occupied Hi Setpoint
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
OMNIZONE::SETPT07: Building Static Pressure
Occupied Lo Setpoint
0.02
0.02
0.02
0.02
in H2O
in H2O
in H2O
in H2O
OccLow
Occupied Hi Setpoint
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
OMNIZONE::SETPT08: BSP raw control
Occupied Lo Setpoint
12.32
12.32
12.32
12.32
ma
ma
ma
ma
OccLow
Occupied Hi Setpoint
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
OMNIZONE::SETPT09: Humidity Control
Occupied Lo Setpoint
0
%RH
%RH
%RH
%RH
OccLow
Occupied Hi Setpoint
99
0
OccHgh
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
UnOccLow
UnOccHgh
99
44
Configuration Screens
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::CC6400:Controller Identification
Description:
OMNIZONE VPAC
Test Version 0.009
CEPP-130124-07
6400
DevDesc
Location
PartNum
ModelNum
SerialNo
RefNum
Location:
Software Part Number:
Model Number:
Serial Number:
Reference Number:
Version 1.6
OMNIZONE::ADAPT01: VAVRESET Software point con-
trol
Analog Output Point
Status Point
VAVRESET
COOLOK
LINK_01
Name
Name
Name
Name
Name
Time Schedule
Setpoint Schedule
Reset Point
SETPT02
TEMP_I00
Reset
Start Reset Value
Stop Reset Value
Control Point
-40
dF
dF
StrtRst
StopRst
Name
245
RESET
PID_Master_Loop
Proportional Gain
Integral Gain
1
KP
0
KI
Derivative Gain
0
KD
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
Block Iteration Rate
Power on Delay
0
%
DsblOut
MinOut
MaxOut
StartVal
BlkRate
PowerUp
0
%
20
20
10
0
%
%
sec
sec
OMNIZONE::ADAPT02: Head Pressure control
Analog Output Point
Status Point
MVLV
Name
Name
Name
Name
Name
HEAD
Time Schedule
LINK_01
SETPT04
TEMP_I00
Setpoint Schedule
Reset Point
Reset
Start Reset Value
Stop Reset Value
Control Point
-40
PSIG
PSIG
StrtRst
StopRst
Name
245
PRES
PID_Master_Loop
Proportional Gain
Integral Gain
-0.2
-0.1
-0.1
0
KP
KI
Derivative Gain
KD
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
Block Iteration Rate
Power on Delay
%
DsblOut
MinOut
MaxOut
StartVal
BlkRate
PowerUp
40
%
100
100
10
%
%
sec
sec
0
OMNIZONE::ADAPT03: Building Pressure Ctrl.
Analog Output Point
Status Point
EXH
Name
Name
Name
Name
Name
OKFAN
LINK_01
SETPT08
TEMP_I00
Time Schedule
Setpoint Schedule
Reset Point
Reset
Start Reset Value
Stop Reset Value
Control Point
-40
245
BSP
ma
ma
StrtRst
StopRst
Name
PID_Master_Loop
Proportional Gain
Integral Gain
-20
-10
0
KP
KI
Derivative Gain
KD
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
Block Iteration Rate
Power on Delay
0
%
DsblOut
MinOut
MaxOut
StartVal
BlkRate
PowerUp
0
%
100
40
10
0
%
%
sec
sec
OMNIZONE::ANCTL01: Supply Fan Status
Discrete Output Point
Sensor Group/SPT Sensor
Time Schedule
SFS
Name
Name
Name
Name
DSP
OCCPC01
SETPT01
Setpoint Schedule
Analog
Hysteresis
Block Iteration Rate
Power on Delay
0
30
0
in H2O
sec
sec
Hyst
BlkRate
PowerUp
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuation information.
45
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::DOPI_01: Supply Fan Status
Discrete Output Point
Time Schedule
SFS
Name
Name
Name
OCCPC01
SETPT01
Setpoint Schedule
Permissive Interlock
Control Point Type
Occ Discrete State
Unocc Discrete State
Occ Analog Test
Analog
On
On
Type
OccSt
UnoccSt
OAnlgTst
UAnlgTst
Ovrd
Low
Low
0
Unocc Analog Test
Override Value
Hysteresis
0.2
in H2O
sec
Hyst
Persistence Time
0
Persist
Name
Analog Control Point
Discrete Control Point
Power on Delay
DSP
PNT_NAME
0
Name
sec
PowerUp
OMNIZONE::ANCTL02: Humidity Control
Discrete Output Point
Sensor Group/SPT Sensor
Time Schedule
DEHUM
IRH
Name
Name
Name
Name
LINK_01
SETPT09
Setpoint Schedule
Analog
Hysteresis
Block Iteration Rate
Power on Delay
10
60
0
%RH
sec
sec
Hyst
BlkRate
PowerUp
OMNIZONE::CCVAV01: Modulating Economizer Control
Cooling Coil Valve
Fan Status Point
ECONO
Name
Name
Name
Name
Name
Name
Name
Name
ECON_OK
VAVRESET
LINK_01
Sensor Group/SPT Sensor
Time Schedule
Setpoint Schedule
High Humidity Switch
Humidity Setpoint
High Humidity Sensor
VAV Setpoint Reset
Supply Air Setpoint
Reset Ratio
Start Reset
Maximum Reset
Supply Air Temperature
PID_Master_Loop
Proportional Gain
Integral Gain
Derivative Gain
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
Block Iteration Rate
Power on Delay
SETPT02
SENSDI00
SETPT00
MAMP_I00
53
dF
^F
dF
^F
Setpt
1
RstRat
StrtRst
MaxReset
Name
20
20
ECONPT
-4
-2
0
0
0
100
30
30
0
KP
KI
KD
%
DsblOut
MinOut
MaxOut
StartVal
BlkRate
PowerUp
%
%
%
sec
sec
OMNIZONE::BSP: Building Static Milliamp
Low Input Endpoint
4
ma
ma
ma
ma
ma
ma
LowRange
HighRng
LowConv
HighConv
LowFlt
High Input Endpoint
20
4
Low Conversion Endpoint
High Conversion Endpoint
Low Input Fault
High Input Fault
Externally Powered
20
4
20
No
HighFlt
ExtPower
OMNIZONE::IAQ: Indoor Air Quality
Low Input Endpoint
4
ma
ma
LowRange
HighRng
LowConv
HighConv
LowFlt
High Input Endpoint
20
0
Low Conversion Endpoint
High Conversion Endpoint
Low Input Fault
High Input Fault
Externally Powered
2000
4
20
Yes
ma
ma
HighFlt
ExtPower
OMNIZONE::CSMUX: Comp. Status MUX
Low Input Endpoint
0
Volts
Volts
Volts
Volts
Volts
Volts
LowRange
HighRng
LowConv
HighConv
LowFlt
High Input Endpoint
11
0
Low Conversion Endpoint
High Conversion Endpoint
Low Input Fault
11
1
10.5
High Input Fault
HighFlt
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
46
Configuration Screens (cont)
DESCRIPTION
OMNIZONE::PRES: Head Pressure(Comp1)
Low Input Endpoint
VALUE*
UNITS
NAME
LowRange
0.6
4
6.23
309.77
0.3
5
Volts
Volts
PSIG
PSIG
Volts
Volts
High Input Endpoint
HighRng
LowConv
HighConv
LowFlt
Low Conversion Endpoint
High Conversion Endpoint
Low Input Fault
High Input Fault
HighFlt
OMNIZONE::RESET: Ext. Supply Air Reset
Low Input Endpoint
2
Volts
Volts
dF
LowRange
HighRng
LowConv
HighConv
LowFlt
High Input Endpoint
10
0
Low Conversion Endpoint
High Conversion Endpoint
Low Input Fault
20
0
10
dF
Volts
Volts
High Input Fault
HighFlt
OMNIZONE::ALARM: Critical Fault
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
4
sec
sec
sec
Minimum On Time
Delay Time
4
10
OMNIZONE::BPS_S: Bypass Start_Stop
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
60
60
5
sec
sec
sec
Minimum On Time
Delay Time
OMNIZONE::CMP1: Compressor 1 Relay
Output Logic Type
Normal
300
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
sec
sec
sec
Minimum On Time
Delay Time
300
30
OMNIZONE::CMP2: Compressor 2 Relay
Output Logic Type
Normal
300
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
sec
sec
sec
Minimum On Time
Delay Time
300
30
OMNIZONE::CMP3: Compressor 3 Relay
Output Logic Type
Normal
300
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
sec
sec
sec
Minimum On Time
Delay Time
300
30
OMNIZONE::CMP4: Compressor 4 Relay
Output Logic Type
Normal
300
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
sec
sec
sec
Minimum On Time
Delay Time
300
30
OMNIZONE::DEHUM: Ext. Dehumidification
Output Logic Type
Normal
60
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
sec
sec
sec
Minimum On Time
Delay Time
60
10
OMNIZONE::HEAT1: Heat Stage 1
Output Logic Type
Minimum Off Time
Minimum On Time
Delay Time
Normal
60
LogType
MinOff
MinOn
DlyTim
sec
sec
sec
60
10
OMNIZONE::HEAT2: Heat Stage 2
Output Logic Type
Minimum Off Time
Minimum On Time
Delay Time
Normal
60
LogType
MinOff
MinOn
DlyTim
sec
sec
sec
60
10
OMNIZONE::HEAT3: Heat Stage 3
Output Logic Type
Minimum Off Time
Minimum On Time
Delay Time
Normal
60
LogType
MinOff
MinOn
DlyTim
sec
sec
sec
60
10
OMNIZONE::HEAT4: Heat Stage 4
Output Logic Type
Minimum Off Time
Minimum On Time
Delay Time
Normal
60
LogType
MinOff
MinOn
DlyTim
sec
sec
sec
60
10
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
47
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::HIR: Heat Interlock Relay
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
60
60
5
sec
sec
sec
Minimum On Time
Delay Time
OMNIZONE::PUMP: Pump Request
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
5
5
5
sec
sec
sec
Minimum On Time
Delay Time
OMNIZONE::SF: Supply Fan/VFD
Output Logic Type
Minimum Off Time
Minimum On Time
Delay Time
Normal
30
LogType
MinOff
MinOn
DlyTim
sec
sec
sec
60
10
OMNIZONE::TOWER: Cooling Tower Request
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
5
5
5
sec
sec
sec
Minimum On Time
Delay Time
OMNIZONE::TRMCT: VAV Terminals Control
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
60
60
5
sec
sec
sec
Minimum On Time
Delay Time
OMNIZONE::TRMOP: VAV Terminals Open MAX
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
5
5
5
sec
sec
sec
Minimum On Time
Delay Time
OMNIZONE::VENTR: Ventilation Request
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
3
3
5
sec
sec
sec
Minimum On Time
Delay Time
OMNIZONE::WARN: Non Critical Fault
Output Logic Type
Normal
LogType
MinOff
MinOn
DlyTim
Minimum Off Time
4
sec
sec
sec
Minimum On Time
Delay Time
4
10
OMNIZONE::DSALM01: Duct High Pressure
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Discrete Check
DHS
Name
Name
Name
SENSDI00
SENSDI00
Alarm Logic
Normal
15
10
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
1
Alarm Source
Alarm Routing
5
11010000
0
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
Duct High Static
Pressure
0
sec
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
48
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::DSALM02: Phase Protection
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Discrete Check
PHASE
Name
Name
Name
SENSDI00
SENSDI00
Alarm Logic
Normal
15
10
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Re-Alarm Interval
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
0
min
Alarm=1 or Alert=0
Alarm Level
1
1
Alarm Source
5
Alarm Routing
11010000
0
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
Phase Loss
0
sec
OMNIZONE::DSALM03: Freeze Protection
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Discrete Check
FREEZ
Name
Name
Name
SENSDI00
SENSDI00
Alarm Logic
Normal
15
900
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
1
Alarm Source
5
Alarm Routing
11010000
0
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
Economizer Freez
e Condition
0
sec
OMNIZONE::DSALM04: Duct Static Failure
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Discrete Check
DSP_ALM
SENSDI00
SENSDI00
Name
Name
Name
Alarm Logic
Normal
10
10
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
1
Alarm Source
5
Alarm Routing
11010000
0
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
Duct Static Sens
or Failure
0
sec
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
49
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::DSALM05: Fire alarm
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Discrete Check
FSD
Name
Name
Name
SENSDI00
SENSDI00
Alarm Logic
Invert
10
10
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
Alarm Processor
Alarm Processing
Re-Alarm Interval
Alarm=1 or Alert=0
Alarm Level
Alarm Source
Alarm Routing
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
sec
sec
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
0
min
1
0
5
11010000
0
Fire Shutdown
0
sec
OMNIZONE::DSALM06: Condenser Water Flow
Monitored Input Point
Comparison Point
CDWF
Name
Name
Name
COOLOK
CDWF_ST
Alarm Inhibit Point
Discrete Check
Alarm Logic
Normal
120
120
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
2
Alarm Source
5
Alarm Routing
11010000
0
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
Check Condenser
Water Flow
0
sec
OMNIZONE::DSALM07: Filter Alarm
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Discrete Check
FLTS
Name
Name
Name
SENSDI00
SENSDI00
Alarm Logic
Normal
10
20
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
Alarm Processor
Alarm Processing
Re-Alarm Interval
Alarm=1 or Alert=0
Alarm Level
Alarm Source
Alarm Routing
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
sec
sec
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
0
min
1
2
5
11010000
0
Change Filters
0
sec
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
50
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::DSALM08: Compressor 1 Alarm
Monitored Input Point
Comparison Point
C1_ALM
Name
Name
Name
SENSDI00
SENSDI00
Alarm Inhibit Point
Discrete Check
Alarm Logic
Normal
10
10
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
2
Alarm Source
5
Alarm Routing
11010000
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
0
Compressor 1 fau
lt
0
sec
OMNIZONE::DSALM09: Compressor 2 Alarm
Monitored Input Point
Comparison Point
C2_ALM
Name
Name
Name
SENSDI00
SENSDI00
Alarm Inhibit Point
Discrete Check
Alarm Logic
Normal
10
10
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
2
Alarm Source
5
Alarm Routing
11010000
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
0
Compressor 2 Fau
lt
0
sec
OMNIZONE::DSALM10: Compressor 3 Alarm
Monitored Input Point
Comparison Point
C3_ALM
Name
Name
Name
SENSDI00
SENSDI00
Alarm Inhibit Point
Discrete Check
Alarm Logic
Normal
10
10
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
2
Alarm Source
5
Alarm Routing
11010000
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
0
Compressor 3 Fau
lt
0
sec
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
51
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::DSALM11: Compressor 4 Alarm
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Discrete Check
C4_ALM
Name
Name
Name
SENSDI00
SENSDI00
Alarm Logic
Normal
10
10
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
2
Alarm Source
5
Alarm Routing
11010000
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
0
Compressor 4 Fau
lt
0
sec
OMNIZONE::DSALM12: Supply Fan Alarm
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Discrete Check
SFS
Name
Name
Name
SF
SENSDI00
Alarm Logic
Normal
120
120
AlmLogic
DlyTim
Persist
Enable Delay Time
Persistence Time
sec
sec
Alarm Processor
Alarm Processing
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
Re-Alarm Interval
0
min
Alarm=1 or Alert=0
Alarm Level
1
2
Alarm Source
5
Alarm Routing
11010000
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
0
Check Supply Fan
0
sec
OMNIZONE::DXVAV01: Compressor Staging
Discrete Output Point 1
Discrete Output Point 2
Discrete Output Point 3
Discrete Output Point 4
Discrete Output Point 5
Discrete Output Point 6
Fan Status Point
CMP1
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
CMP2
CMP3
CMP4
DISCRO00
DISCRO00
COMPRES
VAVRESET
LINK_01
SETPT02
SENSDI00
SETPT00
IRH
Sensor Group/SPT Sensor
Time Schedule
Setpoint Schedule
High Humidity Switch
Humidity Setpoint
High Humidity Sensor
VAV Setpoint Reset
Supply Air Setpoint
Reset Ratio
Start Reset
Maximum Reset
Supply Air Temperature
PID_Master_Loop
Proportional Gain
Integral Gain
Derivative Gain
57
1
20
20
SAT
dF
^F
dF
^F
SetPT
RstRat
StrtRst
MaxReset
Name
-1
KP
-0.4
-0.7
0
KI
KD
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
%
DsblOut
MinOut
MaxOut
StartVal
BlkRate
0
%
100
0
%
%
Block Iteration Rate
Staging Control
30
sec
Total Number of Stages
On Time Delay
4
2
1
0
TotalStg
OnDelay
OffDelay
PowerUp
min
min
sec
Off Time Delay
Power on Delay
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
52
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::EHVAV01: DO - Elec Heat VAV 01
Discrete Output Point 1
Discrete Output Point 2
Discrete Output Point 3
Discrete Output Point 4
Discrete Output Point 5
Discrete Output Point 6
Fan Status Point
HEAT1
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
Name
Value
OccHeat
HEAT2
HEAT3
HEAT4
DISCRO00
DISCRO00
MODE
LINK_09
LINK_01
LINK_01
SENSDI00
SETPT00
IRH
SAT
150
Yes
Sensor Group/SPT Sensor
Time Schedule
Setpoint Schedule
High Humidity Switch
Humidity Setpoint
High Humidity Sensor
Duct Temperature
Duct High Limit
dF
Occupied Heating
PID_Master_Loop
Proportional Gain
5
KP
Integral Gain
2.5
0
KI
Derivative Gain
KD
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
0
0
%
DdblOut
MinOut
MaxOut
StartVAl
BlkRate
Value
%
100
0
%
%
Block Iteration Rate
Heating Setpoint Offset
Staging Control
Total Number of Stages
On Time Delay
Off Time Delay
Power on Delay
15
3
sec
^F
4
3
1
0
TotalStg
OnDelay
OffDelay
PowerUp
min
min
sec
OMNIZONE::HCVAV01: AO - Heating VAV 01
Heating Coil Valve
HWV
Name
Name
Name
Name
Name
Value
Name
Name
Name
OccHeat
Fan Status Point
MODE
LINK_09
LINK_01
LINK_01
3
Sensor Group/SPT Sensor
Time Schedule
Setpoint Schedule
Heating Setpoint Offset
High Humidity Switch
Humidity Setpoint
^F
SENSDI00
SETPT00
IRH
High Humidity Sensor
Occupied Heating
Yes
PID_Master_Loop
Proportional Gain
3
1.5
0
KP
Integral Gain
KI
Derivative Gain
KD
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
Block Iteration Rate
Supply Air Temperature
P_Submaster_Loop
Proportional Gain
Disabled Output Value
Minimum Output Value
Maximum Output Value
Center Value
Block Iteration Rate
Power on Delay
35
40
140
80
15
SAT
dF
dF
dF
dF
sec
DsblOut
MinOut
MaxOut
StartVal
BlkRate
Name
3
KP
0
%
FanOff
MinOut
MaxOut
Center
BlkRate
PowerUp
0
%
100
30
2
%
%
sec
sec
0
OMNIZONE::INTLK01: OK to run Fan
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
OKFAN
Name
Name
Name
TIMCLOCK
ROCC
Input 1 Comparison
Input 2 Comparison
Off Persistence Time
On Persistence Time
Output Logic Type
Off
Off
5
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
sec
sec
5
Invert
5
Power on Delay
sec
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
53
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::INTLK02: Ok to Cool
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
COOLOK
MODE
Name
Name
Name
SF_SFS
Input 1 Comparison
Input 2 Comparison
Off Persistence Time
On Persistence Time
Output Logic Type
Off
On
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
3
sec
sec
10
Normal
0
Power on Delay
sec
OMNIZONE::INTLK03: OK Fan + Sup. Fan Stat
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
SF_SFS
OKFAN
SFS
Name
Name
Name
Input 1 Comparison
On
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
Input 2 Comparison
On
Off Persistence Time
On Persistence Time
Output Logic Type
2
sec
sec
2
Normal
0
Power on Delay
sec
OMNIZONE::INTLK04: Supply Fan Delays
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
SF
Name
Name
Name
OKFAN
SENSDI00
Input 1 Comparison
On
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
Input 2 Comparison
Off
Off Persistence Time
On Persistence Time
Output Logic Type
300
20
sec
sec
Normal
0
Power on Delay
sec
OMNIZONE::INTLK05: Dis. Cool befor SF delay
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
FAN_CDWF
CDWF
Name
Name
Name
OKFAN
Input 1 Comparison
On
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
Input 2 Comparison
On
Off Persistence Time
On Persistence Time
Output Logic Type
3
sec
sec
3
Normal
0
Power on Delay
sec
OMNIZONE::INTLK06: Activate VAV Terminals
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
TRMCT
OKFAN
SF
Name
Name
Name
Input 1 Comparison
Off
Off
1
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
Input 2 Comparison
Off Persistence Time
On Persistence Time
Output Logic Type
sec
sec
1
Invert
1
Power on Delay
sec
OMNIZONE::INTLK07: Ventilation Request
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
VENTR
Name
Name
Name
TIMCLOCK
SF_SFS
Input 1 Comparison
On
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
Input 2 Comparison
On
Off Persistence Time
On Persistence Time
Output Logic Type
1
sec
sec
1
Normal
1
Power on Delay
sec
OMNIZONE::INTLK08: Heat Interlock Relay
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
HIR
Name
Name
Name
MODE
SF_SFS
Input 1 Comparison
On
On
30
30
Normal
5
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
Input 2 Comparison
Off Persistence Time
On Persistence Time
Output Logic Type
sec
sec
Power on Delay
sec
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
54
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::INTLK09: Condenser Pump
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
PUMP
Name
Name
Name
COOLOK
SENSDI00
Input 1 Comparison
Input 2 Comparison
Off Persistence Time
On Persistence Time
Output Logic Type
On
Off
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
30
sec
sec
2
Normal
0
Power on Delay
sec
OMNIZONE::INTLK10: Tower Request
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
TOWER
Name
Name
Name
COOLOK
SENSDI00
Input 1 Comparison
Input 2 Comparison
Off Persistence Time
On Persistence Time
Output Logic Type
On
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
Off
30
sec
sec
2
Normal
0
Power on Delay
sec
OMNIZONE::INTLK11: Compressor Cooling
Discrete Output Point
Discrete Input Point 1
Discrete Input Point 2
Discrete Interlock
COMPRES
COOLOK
Name
Name
Name
FAN_CDWF
Input 1 Comparison
On
Sns1Sta
Sns2Sta
OffPrst
OnPrst
LogType
PowerUp
Input 2 Comparison
On
Off Persistence Time
On Persistence Time
Output Logic Type
2
sec
sec
30
Normal
0
Power on Delay
sec
OMNIZONE::LINK_01: Linkage/AOSS Schedule 01
Setpoint Bias
Setpoint Schedule
Adaptive Optimal Start
AO Start Enable
Building Insulation
Unoccupied 24hr Factor
Offset Low Value
VOLT_I00
SETPT03
Name
Name
Disable
30
Enable
BldInsul
UnOccFct
Value
15
0
^F
^F
Offset High Value
Sensor Group/SPT Sensor
Time Schedule
0
Value
CTRLPT
OCCPC01
OAT
Name
Name
Name
Name
Name
Name
Name
Outside Air Temp
NTFC Algorithm
NTFC_00
HCVAV01
SAT
Heating Algorithm
Supply Air Temp
Fan Status
SF_SFS
Adaptive Optimal Stop
AO Stop Enable
Disable
60
Enable
MaxStop
SPBias
PowerUp
Evacuate
Pressure
Maximum Stop Time
Setpoint Bias
min
^F
sec
2
0
Power on Delay
Evacuation
EVAC
TRMOP
Pressurization
OMNIZONE::LMALM01: Supply air Sensor
Monitored Input Point
Alarm Inhibit Point
Limit Check
SAT
Name
Name
SENSDI00
Low Limit
25
150
15
10
5
dF
LowLim
HighLim
DlyTim
Persist
Hyst
High Limit
dF
Enable Delay Time
Persistence Time
Hysteresis
sec
sec
^F
Alarm Processor
Alarm Processing
Re-Alarm Interval
Alarm=1 or Alert=0
Alarm Level
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
0
min
1
1
Alarm Source
Alarm Routing
5
11010000
7
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
0
sec
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
55
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::LMALM02: Entering WaterTemp.
Monitored Input Point
Alarm Inhibit Point
Limit Check
EWT
Name
Name
SENSDI00
Low Limit
35
95
15
10
5
dF
LowLim
HighLim
DlyTim
Persist
Hyst
High Limit
dF
Enable Delay Time
Persistence Time
Hysteresis
sec
sec
^F
Alarm Processor
Alarm Processing
Re-Alarm Interval
Alarm=1 or Alert=0
Alarm Level
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
0
min
1
1
Alarm Source
Alarm Routing
5
11010000
7
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
0
sec
OMNIZONE::LMALM03: Compressor Mux
Monitored Input Point
Alarm Inhibit Point
Limit Check
CSMUX
Name
Name
SENSDI00
Low Limit
1.5
9.9
15
10
0.2
Volts
Volts
sec
LowLim
HighLim
DlyTim
Persist
Hyst
High Limit
Enable Delay Time
Persistence Time
Hysteresis
sec
Volts
Alarm Processor
Alarm Processing
Re-Alarm Interval
Alarm=1 or Alert=0
Alarm Level
Enable
AlmProc
ReAlmTim
Type
AlmLevel
AlmSrc
AlmRtg
AlmDesc
Message
Message
Message
Message
PowerUp
0
min
1
1
Alarm Source
Alarm Routing
5
11010000
7
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
0
sec
OMNIZONE::LMALM04: Mixed/Return Air
Monitored Input Point
Alarm Inhibit Point
Limit Check
MA_RA
Name
Name
SENSDI00
Low Limit
35
120
10
10
5
dF
LowLim
HighLim
DlyTim
Persist
Hyst
High Limit
dF
Enable Delay Time
Persistence Time
Hysteresis
sec
sec
^F
Alarm Processor
Alarm Processing
Re-Alarm Interval
Alarm=1 or Alert=0
Alarm Level
Enable
AlmProc
ReAlmTim
Type
0
min
1
2
AlmLevel
AlmSrc
Alarm Source
5
Alarm Routing
11010000
7
AlmRtg
Alarm Description Index
Alarm Message - Part 1
Alarm Message - Part 2
Alarm Message - Part 3
Alarm Message - Part 4
Power on Delay
AlmDesc
Message
Message
Message
Message
PowerUp
0
sec
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
56
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::OCCPC01: Occupancy 01
Time Schedule
Manual Override Hours
Period 1: Day of Week
Period 1: Occupied from
Period 1: Occupied to
Period 2: Day of Week
Period 2: Occupied from
Period 2: Occupied to
Period 3: Day of Week
Period 3: Occupied from
Period 3: Occupied to
Period 4: Day of Week
Period 4: Occupied from
Period 4: Occupied to
Period 5: Day of Week
Period 5: Occupied from
Period 5: Occupied to
Period 6: Day of Week
Period 6: Occupied from
Period 6: Occupied to
Period 7: Day of Week
Period 7: Occupied from
Period 7: Occupied to
Period 8: Day of Week
Period 8: Occupied from
Period 8: Occupied to
Push Button Override
Thermostat Override
Time Delay
0
hours
Ovrd
0
DOW1
Occ1
0:00
24:00:00
UnOcc1
DOW2
Occ2
UnOcc2
DOW3
Occ3
UnOcc3
DOW4
Occ4
UnOcc4
DOW5
Occ5
UnOcc5
DOW6
Occ6
UnOcc6
DOW7
Occ7
0
0:00
24:00:00
0
0:00
24:00:00
0
0:00
24:00:00
0
0:00
24:00:00
0
0:00
24:00:00
0
0:00
24:00:00
UnOcc7
DOW8
Occ8
0
0:00
24:00:00
UnOcc8
Name
LATCHI00
TEMP_I00
Name
5
5
0
min
min
sec
Value
Timed Override Duration
Power on Delay
Value
PowerUp
OMNIZONE::STPR_01: Supply Fan Speed
Analog Output Point
Fan Status Point
SPEED
SF
Duct Static Pressure
Static Pressure Setpoint
PID_Master_Loop
DSP
1.5
in H2O
Proportional Gain
8
Integral Gain
4
Derivative Gain
0
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
0
%
10
100
0
%
%
%
Block Iteration Rate
Power on Delay
10
0
sec
sec
OMNIZONE::TC01: DO - Time Clock 01
Discrete Output Point
Time Schedule
TIMCLOCK
LINK_01
Name
Name
Name
Loadshed
LDSHD00
Duty Cycle
Duty Cycle Enable
First Minute of Hour
Second Minute of Hour
Occupied Off Duration
Unoccupied Off Duration
Minimum Off Time
Redline Bias Time
Power on Delay
Disable
Enable
0
FirstOff
0
SecndOff
OccOff
0
min
min
min
min
sec
60
3
UnOccOff
MinOff
0
0
BiasTime
PowerUp
OMNIZONE::VPIOC: I/O & Faults
Compressor Status
Reschedule Rate
Power on Delay
1
sec
sec
RESCHRAT
RESCHPOR
10
Critical Fault
Reschedule Rate
Power on Delay
2
10
sec
sec
RESCHRAT
RESCHPOR
Fire Shutdown
Reschedule Rate
Power on Delay
2
10
sec
sec
RESCHRAT
RESCHPOR
Non Critical Fault
Reschedule Rate
Power on Delay
2
10
sec
sec
RESCHRAT
RESCHPOR
Compressor Fault/Test
Reschedule Rate
Power on Delay
10
30
sec
sec
RESCHRAT
RESCHPOR
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
57
Configuration Screens (cont)
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::VPTESTC: Field Test
Field Test
Reschedule Rate
5
40
sec
sec
RESCHRAT
RESCHPOR
Power on Delay
OMNIZONE::MODECTRC: Mode Control
Determines Heat
Reschedule Rate
10
30
sec
sec
RESCHRAT
RESCHPOR
Power on Delay
Run Fan in Bypass
Reschedule Rate
10
30
sec
sec
RESCHRAT
RESCHPOR
Power on Delay
Water Economizer Control
Reschedule Rate
10
30
sec
sec
RESCHRAT
RESCHPOR
Power on Delay
Mod Valve & Econo
Reschedule Rate
2
10
sec
sec
RESCHRAT
RESCHPOR
Power on Delay
OMNIZONE::SETSYNCC: Setpoint Synchronization
Setpoint Synch
Reschedule Rate
3
10
sec
sec
RESCHRAT
RESCHPOR
Power on Delay
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
Maintenance Screens
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
Value
Value
Status
Value
RefOut
Value
OMNIZONE::ADAPT01: VAVRESET Software point control
Analog Output Point
Status Point
0
%
Off
No
0
Occupied ?
Reset Point
dF
dF
dF
Controlling Setpoint
Control Point
0
0
PID_Master_Loop
Reference Output
Proportional Term
Integral Term
0
%
%
%
%
RefOut
PTerm
ITerm
0
0
0
100
6
Derivative Term
DTerm
Flags
Integrator Flags
Task Timer
OMNIZONE::ADAPT02: Head Pressure control
Analog Output Point
Status Point
Occupied ?
Reset Point
Controlling Setpoint
Control Point
sec
%
TaskTimr
100
Off
No
0
Control
Control
Value
Value
Status
Value
RefOut
Value
PSIG
PSIG
PSIG
0
117.72
PID_Master_Loop
Reference Output
Proportional Term
Integral Term
0
%
%
%
%
RefOut
PTerm
ITerm
0
0
0
100
2
Derivative Term
DTerm
Flags
Integrator Flags
Task Timer
OMNIZONE::ADAPT03: Building Pressure Ctrl.
Analog Output Point
Status Point
Occupied ?
Reset Point
Controlling Setpoint
Control Point
sec
%
TaskTimr
0
Value
Value
Status
Value
RefOut
Value
Off
No
0
ma
ma
ma
12.32
12.44
PID_Master_Loop
Reference Output
Proportional Term
Integral Term
0
%
%
%
%
RefOut
PTerm
ITerm
2
0
0
100
3
Derivative Term
DTerm
Flags
Integrator Flags
Task Timer
sec
TaskTimr
58
Maintenance Screens (cont)
DESCRIPTION
OMNIZONE::ANCTL01: Supply Fan Status
Discrete Output Point
Sensor Group/SPT Sensor
Occupied ?
Analog
Low Setpoint
Lo Setpoint + Hyst
Hi Setpoint - Hyst
High Setpoint
Reference Output
Task Timer
VALUE
UNITS
STATUS
FORCE
NAME
Off
0.17
No
Control
Value
in H2O
Value
Status
0.3
0
in H2O
in H2O
in H2O
in H2O
LowSP
ModLowSP
ModHghSP
HghSP
0
0.4
FALSE
47
RefOut
TaskTimr
sec
OMNIZONE::ANCTL02: Humidity Control
Discrete Output Point
Sensor Group/SPT Sensor
Occupied ?
Off
Value
Value
Status
49.56
No
%RH
Analog
Low Setpoint
0
%RH
%RH
%RH
%RH
LowSP
Lo Setpoint + Hyst
Hi Setpoint - Hyst
High Setpoint
10
ModLowSP
ModHghSP
HghSP
89
99
Reference Output
Task Timer
FALSE
25
RefOut
TaskTimr
sec
OMNIZONE::BSP_IN: Building Static Pressure (Typical Analog Software point)
System Value
Force
0.03
in H2O
Sysvalue
Force
0
Status
Alarm Status
0
Status
Normal
AlmStat
OMNIZONE::CCVAV01: Modulating Economizer Control
Cooling Coil Valve
Fan Status Point
0
%
Value
Value
Value
Status
Value
Value
Value
Off
0
Control
Sensor Group/SPT Sensor
Occupied ?
dF
No
Off
99
0
High Humidity Switch
High Humidity Setpoint
High Humidity Sensor
VAV Setpoint Reset
Setpoint
%RH
%RH
73
dF
^F
dF
dF
Setpoint
Offset
CCVVRF
Value
Setpoint Offset
20
CCV Supply Air Setpoint
Supply Air Temperature
PID_Master_Loop
Reference Output
73
77.19
0
%
%
%
%
RefOut
PTerm
ITerm
DTerm
Flags
TaskTimr
Proportional Term
0
Integral Term
0
Derivative Term
0
Integrator Flags
100
4
Task Timer
sec
ma
OMNIZONE::BSP: Building Static Milliamp
System Value
12.4
0
0
Sysvalue
Force
Force
Status
HwStat
Alarm Status
Normal
12.4
12.4
34
AlmStat
Sensor Value
ma
ma
SenValue
HwValue
ChanNum
AlgoName
AlmName
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
ADAPT03
OMNIZONE::IAQ: Indoor Air Quality
System Value
584.3
0
Sysvalue
Force
Force
Status
0
HwStat
Alarm Status
Normal
584.3
8.7
AlmStat
Sensor Value
SenValue
HwValue
ChanNum
AlgoName
AlmName
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
ma
36
OMNIZONE::CSMUX: Comp. Status MUX
System Value
1.83
0
Volts
Sysvalue
Force
Force
Status
0
HwStat
Alarm Status
Normal
1.83
1.8
3
AlmStat
Sensor Value
Volts
Volts
SenValue
HwValue
ChanNum
AlgoName
AlmName
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
LMALM03
59
Maintenance Screens (cont)
DESCRIPTION
OMNIZONE::PRES: Head Pressure(Comp1)
System Value
VALUE
UNITS
PSIG
STATUS
FORCE
NAME
118.76
0
Sysvalue
Force
Force
Status
0
HwStat
Alarm Status
Normal
118.76
1.9
24
ADAPT02
AlmStat
Sensor Value
PSIG
Volts
SenValue
HwValue
ChanNum
AlgoName
AlmName
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
OMNIZONE::RESET: Ext. Supply Air Reset
System Value
0
dF
Sysvalue
Force
Force
0
Status
0
HwStat
Alarm Status
Normal
AlmStat
Sensor Value
0
dF
Volts
SenValue
HwValue
ChanNum
AlgoName
AlmName
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
1.1
20
ADAPT01
OMNIZONE::UPDATEDB: Database Control
Database Error
No
DBError
EEError
RAMError
EEPROM
RAM
EEPROM Error
No
RAM Error
Available Program Bytes
Available Data Bytes
No
11130
14742
OMNIZONE::ALARM: Critical Fault (Typical Discrete Out)
System Value
Force
Off
SysVal
0
Force
Status
Alarm Status
Control Value
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
0
HwStat
Normal
Off
AlmStat
CtrValue
HdwValue
ChanNum
AlgoName
AlmName
Open
16
OMNIZONE::BP_SAFE: Bypass Acc Panel Secure (Typical Discrete Software)
System Value
Force
No
Sysvalue
Force
0
Status
Alarm Status
0
Status
Normal
AlmStat
OMNIZONE::DOPI_01: Supply Fan Status
Discrete Output Point
Occupied ?
Off
No
Control
Value
Status
Permissive Interlock
Reference Output
Perm Interlock Flag
Conditional
Modified Setpoint
Persistence Timer
Setpoint Limit
Analog Control Point
Discrete Control Point
Task Timer
0
RefOut
PIFlag
TRUE
Low
0.5
0
Condtion
ModStpt
PersTime
Value
in H2O
sec
0.3
0.17
Off
1
in H2O
in H2O
Value
Value
sec
TaskTimr
OMNIZONE::DSALM01: Duct High Pressure (Typical Discrete Alarm)
Monitored Input Point
Comparison Point
Alarm Inhibit Point
Alarm Status
Alarm Processor
Alarm Type
Time of Last Message
Month of Last Message
Day of Last Message
Year of Last Message
Task Timer
Off
Value
Value
Value
Status
Off
Off
Normal
0
0:00
0
0
0
2
AlmType
LastTime
LastDate
LastDate
LastDate
TaskTimr
sec
60
Maintenance Screens (cont)
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
Value
OMNIZONE::DXVAV01: Compressor Staging
Discrete Output Point 1
Discrete Output Point 2
Discrete Output Point 3
Discrete Output Point 4
Discrete Output Point 5
Discrete Output Point 6
Fan Status Point
Sensor Group/SPT Sensor
Occupied ?
High Humidity Switch
High Humidity Setpoint
High Humidity Sensor
VAV Setpoint Reset
Setpoint
Off
Off
Off
Off
Off
Off
Off
0
Value
Value
Value
Value
Value
Value
Value
Status
Value
Value
Value
dF
No
Off
99
%RH
%RH
49.56
75
dF
^F
dF
dF
Setpoint
Offset
DODXRF
Value
Setpoint Offset
20
DX Supply Air Setpoint
Supply Air Temperature
PID_Master_Loop
Reference Output
Proportional Term
Integral Term
75
66.97
0
%
%
%
%
RefOut
PTerm
ITerm
DTerm
Flags
11.9
0
Derivative Term
0
Integrator Flags
100
Staging Control
Number of Stages
Requested Stages
Delta Stages
0
NumStgs
ReqStgs
DltaStgs
DlyTimer
PIDClamp
TaskTimr
0
0
Delay Timer
0
min
sec
PID Integrator Clamp
Task Timer
Off
4
OMNIZONE::EHVAV01: DO - Elec Heat VAV 01
Discrete Output Point 1
Discrete Output Point 2
Discrete Output Point 3
Discrete Output Point 4
Discrete Output Point 5
Discrete Output Point 6
Fan Status Point
Off
Value
Value
Value
Value
Value
Value
Value
Value
Status
Value
Value
Value
Value
Value
Off
Off
Off
Off
Off
Off
Control
Sensor Group/SPT Sensor
Occupied ?
74
dF
No
High Humidity Switch
High Humidity Setpoint
High Humidity Sensor
Duct Temperature
Duct High Limit
Off
99
%RH
%RH
dF
49.71
66.97
150
dF
Morning Warm Up
Reference Output
Morning Warmup ?
PID_Master_Loop
Reference Output
Proportional Term
Integral Term
Off
RefOut
FALSE
HeatFlg
0
%
%
%
%
RefOut
PTerm
ITerm
DTerm
Flags
84.9
0
Derivative Term
0
Integrator Flags
100
55
Space Setpoint
dF
Value
Staging Control
Number of Stages
Requested Stages
Delta Stages
0
NumStgs
ReqStgs
DltaStgs
DlyTimer
PIDClamp
TaskTimr
0
0
Delay Timer
PID Integrator Clamp
Task Timer
0
min
sec
Off
7
61
Maintenance Screens (cont)
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
Value
Value
Value
Status
Value
Value
Value
Value
OMNIZONE::HCVAV01: AO - Heating VAV 01
Heating Coil Valve
Fan Status Point
0
%
Off
74
Control
Sensor Group/SPT Sensor
Occupied ?
dF
dF
No
55
Space Setpoint
High Humidity Switch
High Humidity Setpoint
High Humidity Sensor
Morning Warm Up
Reference Output
Morning Warmup ?
PID_Master_Loop
Reference Output
Proportional Term
Integral Term
Off
99
%RH
%RH
49.56
Off
FALSE
RefOut
HeatFlg
35
dF
^F
^F
^F
RefOut
PTerm
ITerm
DTerm
FLAGS
HCVVRF
Value
50.9
0
Derivative Term
Integrator Flags
0
100
35
66.99
HCV Supply Air Setpoint
Supply Air Temperature
P_Submaster_Loop
Reference Output
Proportional Term
Submaster Flags
dF
dF
0
%
%
RefOut
-96
1
PropTerm
SubmFlag
TaskTimr
Task Timer
1
sec
OMNIZONE::INTLK01: OK to run Fan (Typical Interlock)
Discrete Output Point
Off
Off
Off
On
1
Value
Discrete Input Point 1
Value
Discrete Input Point 2
Value
RefOut
TaskTimr
Reference Output
Task Timer
sec
OMNIZONE::LINK_01: Linkage/AOSS Schedule 01
Setpoint Bias
0
%
Value
Adaptive Optimal Start
Start Bias
0
10
5
min
StrtBias
CoolKFct
HeatKFct
StartDay
BiasTim
BiasOcc
CoolFlg
Value
Start Cool K Factor
Start Heat K Factor
Biased Start Day
Biased Start Time
Biased Occupied
Cool Flag
Sensor Group/SPT Sensor
Occupied ?
Outside Air Temp
Linkage Time Schedule
Mode
0:00
No
FALSE
74
dF
dF
No
76.1
Status
Value
0
0
Mode
Biased Occupied
Next Occupied Day
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Last Unoccupied Day
Last Unoccupied Time
Status
BiasFlag
NxtOcDay
NxtOccT
NxtUnDay
NxtUnoT
PrvUnDay
PrvUnoT
Status
0:00
0:00
Thu
15:04
0
Override is set
0
Override
Linkage Setpt Schedule
Occupied Lo Setpoint
Occupied Hi Setpoint
Unoccupied Lo Setpoint
Unoccupied Hi Setpoint
Linkage Space Temp
Supply Air Temp
70
dF
dF
dF
dF
dF
dF
OccLow
OccHgh
UnoccLow
UnoccHgh
Link
74
55
85
74
66.97
Off
Value
Fan Status
Value
Air Side Linkage
Linkage Status
1
LinkStat
Supe-Adr
Supe-Bus
BlockNum
OcLoStpt
OcHiStpt
UnLoStpt
UnHiStpt
AZT
Supervisory Element
Supervisory Bus
140
0
Supervisory Block No.
Avg Occ Heat Setpoint
Avg Occ Cool Setpoint
Avg Unocc Heat Setpoint
Avg Unocc Cool Setpoint
Avg Zone Temperature
Avg Occ Zone Temp
Adaptive Optimal Stop
Stop Bias
3
0
dF
dF
dF
dF
dF
dF
0
0
0
0
0
AOZT
0
min
StopBias
CoolKFct
HeatKFct
BiasLow
BiasHigh
AOStop
Stop Cool K Factor
Stop Heat K Factor
Biased Low Setpoint
Biased High Setpoint
Biased Stop
10
15
70
dF
dF
74
No
FALSE
Cool Flag
CoolFlg
Biased Stop Day
BiasDay
BiasTim
TaskTimr
Evacuate
Pressure
Biased Stop Time
Task Timer
0:00
9
Off
Off
sec
Evacuation
Pressurization
62
Maintenance Screens (cont)
DESCRIPTION
VALUE
UNITS
dF
STATUS
FORCE
NAME
OMNIZONE::LMALM01: Supply air Sensor (Typical Limit Alarm)
Monitored Input Point
Alarm Inhibit Point
66.97
Off
Value
Value
Limit Check
Alarm Status
Normal
Status
AlmValue
ExcdLim
Alarm Value
0
0
dF
dF
Exceeded Limit
Alarm Processor
Alarm Type
2
AlmType
LastTime
LastDate
LastDate
LastDate
TaskTimr
Time of Last Message
Month of Last Message
Day of Last Message
Year of Last Message
Task Timer
15:08
10
26
1
4
sec
OMNIZONE::DSP: Duct Static Pressure (Typical Milliamp Input)
System Value
Force
0.2
in H2O
Sysvalue
Force
0
Status
Alarm Status
Sensor Value
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
0
HwStat
Normal
0.2
AlmStat
in H2O
ma
SenValue
HdwValue
ChanNum
AlgoName
AlmName
4.5
2
ANCTL01
OMNIZONE::ECONO: 2-position/Econo Valve (Typical Milliamp Output)
System Value
Force
0
%
Sysvalue
Force
0
Status
Alarm Status
Control Value
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
0
HwStat
Normal
AlmStat
0
%
ma
CtrValue
HdwValue
ChanNum
AlgoName
AlmName
4
27
CCVAV01
OMNIZONE::OCCPC01: Occupancy 01
Time Schedule
Mode
0
Mode
Current Occupied Period
Override in Progress
Override Duration
0
Period
No
0
0:00
0:00
OverLast
OverDura
OccStart
UnStart
NxtOccD
NxtOccT
NxtUnOD
NxtUnOT
PrvUnOD
PrvUnOT
Value
min
Occupied Start Time
Unoccupied Start Time
Next Occupied Day
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Last Unoccupied Day
Last Unoccupied Time
Push Button Override
Thermostat Override
Task Timer
0:00
0:00
Thu
15:04
Off
0
dF
sec
Value
TaskTimr
1
OMNIZONE::BYPAS: VFD Bypass Enable (Typical)
System Value
Force
Disable
0
Sysvalue
Force
Status
Alarm Status
Sensor Value
Hardware Value
Channel Number
Control Algorithm Name
Alarm Algorithm Name
0
HwStat
Normal
Disable
Open
23
AlmStat
SenValue
HdwValue
ChanNum
AlgoName
AlmName
OMNIZONE::STPR_01: Supply Fan Speed
Analog Output Point
Fan Status Point
0
%
Value
Value
Value
Value
Off
0
Duct Static Pressure
Static Pressure Setpoint
PID_Master_Loop
Reference Output
Proportional Term
Integral Term
in H2O
in H2O
0
0
0
0
0
0
0
%
%
%
%
RefOut
PTerm
ITerm
DTerm
Flags
TaskTimr
Derivative Term
Integrator Flags
Task Timer
sec
63
Maintenance Screens (cont)
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
OMNIZONE::TC01: DO - Time Clock 01
Discrete Output Point
Occupied ?
Off
No
No
Value
Status
Status
Redline ?
Duty Cycle
Reference Output
Off Time Duration
Region of Hour
Task Timer
Off
0
RefOut
min
OffTime
Region
TaskTimr
0
22
sec
dF
OMNIZONE::EWT: Entering Water Temp.
System Value
69.9
0
0
Normal
69.9
8
Sysvalue
Force
HwStat
AlmStat
SenValue
Varnum
AlgoName
AlmName
Force
Status
Alarm Status
Sensor Value
dF
Channel Number
Control Algorithm Name
Alarm Algorithm Name
LMALM02
OMNIZONE::VPIOM: I/O & Faults (Typical BEST++ maintenance)
Compressor Status
Task State
RESCHED
TASKSTAT
TASKTIMR
EXETIME
Task Timer
1
sec
sec
Execution Time
Critical Fault
Task State
0.183
RESCHED
TASKSTAT
TASKTIMR
EXETIME
Task Timer
1
sec
sec
Execution Time
Fire Shutdown
Task State
0.111
RESCHED
TASKSTAT
TASKTIMR
EXETIME
Task Timer
1
sec
sec
Execution Time
Non Critical Fault
Task State
0.049
RESCHED
TASKSTAT
TASKTIMR
EXETIME
Task Timer
1
sec
sec
Execution Time
Compressor Fault/Test
Task State
0.113
RESCHED
TASKSTAT
TASKTIMR
EXETIME
Task Timer
Execution Time
1
sec
sec
0.046
Copyright 2004 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 535-00137 Printed in U.S.A. Form 50BV,XJ-2T Pg 64 2-04 Replaces: 50BV,XJ-1T
Book 1
1
Tab 2a 2b
|