GEMINI™ SELECT
38APS025-050,38APD025-100
Commercial Air-Cooled Condensing Units
with COMFORTLINK™ Controls
50/60 Hz
Controls, Start-Up, Operation,
Service, and Troubleshooting
CONTENTS
Page
Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
• AMBIENT LIMITATIONS
Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . .1,2
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Conventions Used in This Manual. . . . . . . . . . . . . . . . 2
Display Module Usage . . . . . . . . . . . . . . . . . . . . . . . . . . 17
• SCROLLING MARQUEE DISPLAY
• ACCESSORY NAVIGATOR™ DISPLAY MODULE
Main Base Board (MBB). . . . . . . . . . . . . . . . . . . . . . . . . 18
Current Sensor Board (CSB) . . . . . . . . . . . . . . . . . . . . 18
Energy Management Module (EMM) . . . . . . . . . . . . . 18
Compressor Expansion Module (CXB) . . . . . . . . . . 19
AUX Board (AUX). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Enable/Off/Remote Contact Switch. . . . . . . . . . . . . . 19
Emergency On/Off Switch. . . . . . . . . . . . . . . . . . . . . . . 19
Board Addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Control Module Communication. . . . . . . . . . . . . . . . . 19
Carrier Comfort Network® (CCN) Interface. . . . . . . 20
OPERATING DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-33
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
• RETURN AIR TEMPERATURE (RAT) ACCESSORY
• SUPPLY AIR TEMPERATURE (SAT) ACCESSORY
• COMPRESSOR RETURN GAS TEMPERATURE
SENSOR (RGT)
• VOLTAGE (ALL UNITS)
Operation Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-59
Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . 49
• CONTROL COMPONENTS
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Pressure Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Condenser Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Motormaster® V Controller . . . . . . . . . . . . . . . . . . . . . . 54
• GENERAL OPERATION
• CONFIGURATION
• DRIVE PROGRAMMING
• EPM CHIP
• LOSS OF CCN COMMUNICATIONS
• TROUBLESHOOTING
• REPLACING DEFECTIVE MODULES
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59,60
Recommended Maintenance Schedule. . . . . . . . . . 59
Microchannel Heat Exchanger (MCHX) Condenser
Coil Maintenance and Cleaning
• OUTDOOR-AIR TEMPERATURE SENSOR (OAT)
• DISCHARGE TEMPERATURE THERMISTOR (DTT)
• SPACE TEMPERATURE SENSOR (SPT)
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 60-66
Complete Unit Stoppage and Restart. . . . . . . . . . . . 60
• GENERAL POWER FAILURE
• UNIT ENABLE-OFF-REMOTE CONTACT SWITCH
IS OFF
• FAN STATUS INPUT OPEN
• OPEN 24-V CONTROL CIRCUIT BREAKER(S)
• COOLING LOAD SATISFIED
• THERMISTOR FAILURE
• COMPRESSOR SAFETIES
Alarms and Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
APPENDIX A — DISPLAY TABLES . . . . . . . . . . . 67-78
APPENDIX B — CCN TABLES . . . . . . . . . . . . . . . . 79-84
START-UP CHECKLIST FOR 38AP SPLIT SYSTEM
CONDENSING UNIT. . . . . . . . . . . . . . . . . . . .CL-1-CL-5
Fan Status Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Thermostat Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Pressure Transducer Inputs. . . . . . . . . . . . . . . . . . . . . 23
Energy Management Module . . . . . . . . . . . . . . . . . . . . 23
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Service Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operating Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operation of Machine Based on Control
Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Set Point Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
• DEMAND LIMIT (2-Stage Switch Controlled)
• EXTERNALLY POWERED DEMAND LIMIT
(4 to 20 mA Controlled)
• DEMAND LIMIT (CCN Loadshed Controlled)
SAFETY CONSIDERATIONS
Cooling Set Point (4 to 20 mA) . . . . . . . . . . . . . . . . . . 32
Digital Scroll Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-49
Preliminary Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Adjust Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . 34
Check Compressor Oil Level . . . . . . . . . . . . . . . . . . . . 47
Final Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roof, elevated structures, mechanical
rooms, etc.). Only trained, qualified installers and service
mechanics should install, start up, and service this equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380003-01 Printed in U.S.A. Form 38AP-1T Pg 1 210 11-09 Replaces: New
LEGEND
AUX
C
—
Auxiliary
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Contactor
CB
Circuit Breaker
CCHR
CSB
EMM
EQUIP GND
FB
Crankcase Heater Relay
Current Sensor Board
Energy Management Module
Equipment Ground
Fuse Block
FC
Fan Contactor
LON
MBB
SW
Local Operating Network
Main Base Board
Switch
TB
Terminal Block
TRAN
UPC
Transformer
Unitary Protocol Converter
Fig. 1 — Component Arrangement — Unit Sizes 025-030
3
LEGEND
AUX
C
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Auxiliary
Contactor
CB
Circuit Breaker
CCH
CSB
EMM
EQUIP GND
FC
Crankcase Heater Relay
Current Sensor Board
Energy Management Module
Equipment Ground
Fan Contactor
FCB
LON
MBB
MM
Fan Circuit Breaker
Local Operating Network
Main Base Board
Motormaster®
SW
Switch
TB
Terminal Block
TRAN
UPC
Transformer
Unitary Protocol Converter
Fig. 2 — Component Arrangement — Unit Sizes 040-060
4
LEGEND
AUX
C
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Auxiliary
Contactor
CB
Circuit Breaker
CCH
CSB
CXB
EMM
EQUIP GND
FC
FCB
LON
MBB
SW
TB
TRAN
UPC
Crankcase Heater Relay
Current Sensor Board
Compressor Expansion Board
Energy Management Module
Equipment Ground
Fan Contactor
Fan Circuit Breaker
Local Operating Network
Main Base Board
Switch
Terminal Block
Transformer
Unitary Protocol Converter
Fig. 3 — Component Arrangement — Unit Sizes 070-100
5
Fig. 4 — Power Wiring Schematic — 38APS,APD025-030
6
Fig. 5 — Power Wiring Schematic — 38APS040,050
7
Fig. 6 — Power Wiring Schematic — 38APD040-060
8
Fig. 7 — Power Wiring Schematic — 38APD070-100
9
Fig. 8 — Control Wiring Schematic — 38APS025-050
10
Fig. 9 — Control Wiring Schematic — 38APD025-060
11
Fig. 10 — Control Wiring Schematic — 38APD070-100
12
Legend and Notes for Fig. 4-10
LEGEND
NOTES:
1. Factory wiring is in accordance with UL (Underwriters Labora-
ACCSY
ALM
AMPS
AUX
C
— Accessory
tories) 1995 standards. Any field modifications or additions
must be in compliance with all applicable codes.
2. Use 75 C minimum wire for field power supply.
3. All field interlock contacts must have a minimum rating of
2 amps at 24-vac sealed. See field interlock wiring.
4. Compressor and fan motors are thermally protected. Three-
phase motors protected against single-phase conditions.
5. Terminals 13 and 14 of LVT are for field connection of remote
on-off. The contact must be rated for dry circuit application
capable of handling a 5-vdc, 1 mA to 20 mA load.
6. For 500 series unit operation at 208-3-60 line voltage, TRAN1
primary connections must be moved to terminals H3 and H4.
7. For 575-3-60 units, fan circuit breakers FCB1 and FCB2 are
replaced with fuse blocks FB1 and FB2.
— Alarm
— Amperes
— Auxiliary
— Contactor
CB
— Circuit Breaker
CCB
CCH
CH
— Compressor Circuit Breaker
— Crankcase Heater Relay
— Crankcase Heater
— Compressor
COMP
CSB
CXB
DGS
DPT
DTT
DUS
EMM
— Current Sensor Board
— Compressor Expansion Module
— Digital Scroll
— Discharge Pressure Transducer
— Discharge Temperature Thermistor
— Digital Unloaded Solenoid
— Energy Management Module
8. For units with low ambient Motormaster® V factory-installed
option or field-installed acessory, fan contactors FC1 and FC2
are replaced with fan relays FR1 and FR2.
9. MP-A1 not used in the following units:
070-100: 400-v, 460-v units without digital scroll
10. MP-A2 not used in the following units:
070-100: 400-v, 460-v
EQUIP GND — Equipment Ground
FB
FC
— Fuse Block
— Fan Contactor
FCB
FIOP
FR
— Fan Circuit Breaker
— Factory-Installed Option
— Fan Relay
11. MP-B1 not used in the following units:
070: all units
FS
FU
— Fan Status
080-100: 400-v, 460-v
— Fuse
12. MP-B2 not used in the following units:
070: all units
GND
HPS
LLSV
LVT
MBB
MLV
MM
— Ground
— High Pressure Switch
— Liquid Line Solenoid Valve
— Low Voltage Terminal
— Main Base Board
— Minimum Load Valve
— Motormaster
080-100: 400-v, 460-v
13. MP-A3 not used in the following units:
090,100: 400-v, 460-v
14. MP-B3 not used in the following units:
070: all units
080-100: 400-v, 460-v
MP
— Modular Motor Protector
— National Electrical Code
— Outdoor Air Thermistor
— Outdoor Fan Motor
— Option
15. Jumper plug required when modular motor protector is not
used.
NEC
OAT
OFM
OPT
PL
— Plug
RAT
RGT
RLY
SAT
SEN
SET
SPT
SW
— Return Air Temperature
— Return Gas Temperature
— Relay
— Supply Air Temperature
— Sensor Terminal Block
— Set Point Terminal Block
— Suction Pressure Transducer
— Switch
TB
— Terminal Block
TEMP
TRAN
UPC
Y
— Temperature
— Transformer
— Unitary Protocol Converter
— Cool Stage
13
a38-7122
LEGEND
b. Incoming wire size range for terminal block with MCA from 175.1 amps to
420 amps is 2 AWG to 600 kcmil.
EQUIP GND
NEC
—
—
Equipment Ground
National Electrical Code
c. Incoming wire size range for non-fused disconnect with MCA up to
100 amps is 14 AWG to 1/0.
d. Incoming wire size range for non-fused disconnect with MCA from
100.1 amp to 200 amps is 6 AWG to 350 kcmil.
NOTES:
1. Factory wiring is in accordance with UL 1995 standards. Field modifications
or additions must be in compliance with all applicable codes.
2. All units or modules have single point primary power connection. Main
power must be supplied from a field or factory-supplied disconnect.
3. Wiring for main field supply must be rated 75 C. Use copper conductors only.
a. Incoming wire size range for terminal block with MCA (minimum circuit
amps) up to 175 amps is 14 AWG (American Wire Gage) to 2/0.
e. Incoming wire size range for non-fused disconnect with MCA from
200.1 amp to 450 amps is 3/0 to 500 kcmil.
4. Refer to certified dimensional drawings for exact locations of the main power
and control power entrance locations.
Fig. 11 — Field Power Wiring
RETURN
AIR
a38-7133
MAT/RAT
FS1*
SAT
OUTSIDE
AIR
DUCT
SUPPLY
FAN
LEGEND
FS1 — Fan Status Switch (24-v)
EVAPORATOR
COIL
MAT — Mixed Air Temperature Sensor
RAT — Return Air Temperature Sensor
SAT — Supply Air Temperature Sensor
*FS1 can be pressure differential switch (shown), motor current detection, or sail switch.
Fig. 12 — MAT/RAT and SAT Sensor Layout
14
LVT
TERMINAL
STRIP
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
REMOTE
ON/OFF
ALM
R
COOL 2
COOL 1
*Not required for single circuit units.
Fig. 13 — Constant Volume Application Wiring Diagram 2-Stage Thermostat Control, Sizes 025-030 —
without Digital Scroll Option
LVT
TERMINAL
STRIP
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
REMOTE
ON/OFF
ALM
R
COOL2
COOL 1
a38-7126
*See Fig. 12 for MAT/RAT and SAT location.
†Not required for single circuit units.
Fig. 14 — Constant Volume Application Wiring Diagram 2-Stage Thermostat Control —
with Digital Scroll Option, Sizes 025-030 or All Sizes 040-100
LVT
TERMINAL
STRIP
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
REMOTE
ON/OFF
ALM
R
SAT
*
a38-7127
*See Fig. 12 for MAT/RAT and SAT location.
†Not required for single circuit units.
Fig. 15 — Constant Volume Application Wiring Diagram Space Temperature Sensor Control, Sizes 025-100
15
LVT
TERMINAL
STRIP
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
REMOTE
ON/OFF
ALM
R
SAT
*
a38-7128
*See Fig. 12 for MAT/RAT and SAT location.
†Not required for single circuit units.
Fig. 16 — Variable Air Volume Application Wiring Diagram, Sizes 025-100
LVT
TERMINAL
STRIP
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
a38-7129
Fig. 17 — Optional Energy Management Module Wiring
Legend and Notes for Fig. 13-17
LEGEND
a. Incoming wire size range for terminal block with MCA (mini-
mum circuit amps) up to 175 amps is 14 AWG (American
Wire Gage) to 2/0.
ALM R
COOL1
COOL2
FS1
— Alarm Relay (24-v), 5-va Maximum
— Thermostat Stage 1 (24-v)
— Thermostat Stage 2 (24-v)
— Fan Status Switch (24-v)
b. Incoming wire size range for terminal block with MCA from
175.1 amps to 420 amps is 2 AWG to 600 kcmil.
c. Incoming wire size range for non-fused disconnect with MCA
up to 100 amps is 14 AWG to 1/0.
d. Incoming wire size range for non-fused disconnect with MCA
from 100.1 amp to 200 amps is 6 AWG to 350 kcmil.
e. Incoming wire size range for non-fused disconnect with MCA
from 200.1 amp to 450 amps is 3/0 to 500 kcmil.
LLSV
LVT
— Liquid Line Solenoid Valve
— Low Voltage Terminal
MAT
— Mixed Air Temperature Sensor
— Return Air Temperature Sensor
— Set Point Adjustment (T-56, T-59)
— Supply Air Temperature Sensor
— Space Temperature Sensor (T-55, T-56, T-59)
Field Control Wiring
RAT
SA
SAT
4. Terminals 1 and 2 of the LVT are for the alarm relay. The maxi-
mum load allowed for the alarm relay is 5-va sealed and 10-va
inrush at 24-v. Field power supply is not required.
SPT
5. Refer to certified dimensional drawings for exact locations of
the main power and control power entrance locations.
6. Terminals 24, 25, and 2 of the LVT are for the control of the
field-supplied LLSV. The maximum load allowed for the LLSV
is 15-va sealed and 30-va inrush at 24-v. Field power supply is
not required.
7. LLSV (24-v) should be 15-va maximum per valve as required.
8. Installation of fan status switch (FS1) is recommended.
9. The contacts for remote ON/OFF, fan status, and demand limit
options must be rated for dry circuit application capable of han-
dling a 24-vac load up to 50 mA.
NOTES:
1. Factory wiring is in accordance with UL 1995 standards. Field
modifications or additions must be in compliance with all appli-
cable codes.
2. All units or modules have single point primary power connec-
tion. Main power must be supplied from a field or factory-
supplied disconnect.
3. Wiring for main field supply must be rated 75 C. Use copper
conductors only.
16
Display Module Usage
Comf
o
SCROLLING MARQUEE DISPLAY — This device is the
keypad interface used for accessing unit information, reading
sensor values, and testing the unit. See Fig. 18. The scrolling
marquee display is a 4-key, 4-character, 16-segment LED
(light-emitting diode) display. Eleven mode LEDs are located
on the display as well as an Alarm Status LED. See Appendix
A — Display Tables for further details.
r
t
Link
M
O
D
E
Alar
R
m
Status
un
S
ta
tu
s
S
er
vic
pe
e
T
e
s
t
T
e
m
ra
tu
r
e
s
P
res
s
u
res
ints
S
e
tpo
Inp
u
ts
tpu
O
u
MODE
Run Status
Service Test
Temperature
ts
C
o
nfig
u
r
a
tio
n
T
im
e
C
lo
ck
ES
O
p
e
C
ra
tin
g
M
o
d
e
A
s
la
rm
s
Pressures
Setpoints
EN
TER
Alarm Status
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
ESCAPE ENTER
Fig. 18 — Scrolling Marquee Display
Fig. 19 — Accessory Navigator Display Module
The scrolling marquee display module provides the user in-
terface to the ComfortLink™ control system. The display has
Once within a Mode or sub-mode, a “>” indicates the cur-
rently selected item on the display screen. Pressing the
up and down arrow keys, an
key, and an
ENTER
ESCAPE
key. These keys are used to navigate through the different lev-
els of the display structure. See Table 2. Press the
and
keys simultaneously will put the Nav-
ESCAPE
ENTER
igator module into expanded text mode where the full meaning
of all sub-modes, items and their values can be displayed. Press-
ESCAPE
key until the display is blank to move through the top 11 mode
levels indicated by LEDs on the left side of the display.
ing the
and
keys when the display says
ESCAPE
ENTER
‘Select Menu Item’ (Mode LED level) will return the Navigator
module to its default menu of rotating display items (those items
in Run StatusVIEW). In addition, the password will be dis-
abled, requiring that it be entered again before changes can be
Pressing the
and
keys simultaneously
ENTER
ESCAPE
will scroll a clear language text description across the display
indicating the full meaning of each display acronym. Pressing
the
and
keys when the display is blank
ENTER
ESCAPE
made to password protected items. Press the
exit out of the expanded text mode.
key to
ESCAPE
(Mode LED level) will return the scrolling marquee display to
its default menu of rotating display items. In addition, the pass-
word will be disabled requiring that it be entered again before
changes can be made to password protected items. Clear lan-
guage descriptions will be displayed in English.
NOTE: When the Language Selection (Configuration
DISPLANG), variable is changed, all appropriate display
expansions will immediately change to the new language. No
power-off or control reset is required when reconfiguring
languages.
When a specific item is located, the item name appears on the
left of the display, the value will appear near the middle of the
display and the units (if any) will appear on the far right of the
When a specific item is located, the display will flash show-
ing the operator, the item, followed by the item value and then
followed by the item units (if any). Press the
stop the display at the item value. Items in the Configuration
and Service Test modes are password protected. The display
will flash PASS and WORD when required. Use the
key to
ENTER
display. Press the
key at a changeable item and the val-
ENTER
ue will begin to flash. Use the up and down arrow keys to change
the value, and confirm the value by pressing the key.
ENTER
and arrow keys to enter the 4 digits of the password. The
ENTER
default password is 1111.
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to
ENTER
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
change the value or state and press the
it. Press the
structure. Repeat the process as required for other items.
key to accept
to stop the display at the item value. Press the
ENTER
ENTER
key to return to the next higher level of
ESCAPE
key again so that the item value flashes. Use the
ENTER
arrow keys to change the value or state of an item and press the
key to accept it. Press the key and the
ENTER
ESCAPE
Items in the Configuration and Service Test modes are pass-
word protected. The words Enter Password will be displayed
when required, with 1111 also being displayed. The default
password is 0111. Use the arrow keys to change the number
item, value, or units display will resume. Repeat the process as
required for other items.
ACCESSORY NAVIGATOR™ DISPLAY MODULE —
The Navigator module provides a mobile user interface to the
ComfortLink™ control system, which is only available as a
and press
to enter the digit. Continue with the re-
ENTER
maining digits of the password. The password can only be
changed through CCN operator interface software such as
ComfortWORKS®, ComfortVIEW™ and Service Tool.
field-installed accessory. The display has up and down arrow
keys, an
key, and an
key. These keys are
ESCAPE
used to navigate through the different levels of the display
structure. Press the key until ‘Select a Menu Item’
ENTER
ESCAPE
is displayed to move through the top 11 mode levels indicated
by LEDs on the left side of the display. See Fig. 19.
17
Adjusting the Contrast — The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast of
view screen. Pressing the up and down arrow keys simultane-
ously allows the user to adjust the display brightness. Use the
up or down arrow keys to adjust screen brightness. Press
the Navigator module, press the
key until the dis-
ESCAPE
play reads, “Select a menu item.” Using the arrow keys move
to accept the change. The Navigator module will
ENTER
to the Configuration mode. Press
this mode. The display will read:
to obtain access to
keep this setting as long as it is plugged in to the LEN bus.
ENTER
Main Base Board (MBB) — See Fig. 20. The MBB is
the heart of the ComfortLink control system. It contains the
major portion of operating software and controls the operation
of the machine. The MBB continuously monitors input/output
channel information received from its inputs and from all other
modules. The MBB receives inputs from the discharge and
suction pressure transducers, current sensor boards (CSB) and
thermistors. See Table 3. The MBB also receives the discrete
inputs from the thermostat contacts and other status switches.
See Table 4. The MBB also controls several outputs. Informa-
tion is transmitted between modules via a 3-wire communica-
tion bus or LEN (Local Equipment Network). The CCN (Car-
rier Comfort Network®) bus is also supported. Connections to
both LEN and CCN buses are made at the LVT (low voltage
terminal) terminal strip.
> TEST OFF
METR OFF
LANG ENGLISH
Pressing
will cause the “OFF” to flash. Use the up
ENTER
or down arrow to change “OFF” to “ON”. Pressing
ENTER
will illuminate all LEDs and display all pixels in the view
screen. Pressing and simultaneously
ESCAPE
ENTER
allows the user to adjust the display contrast. Use the up or
down arrows to adjust the contrast. The screen’s contrast will
change with the adjustment. Press
change. The Navigator module will keep this setting as long as
it is plugged in to the LEN bus.
to accept the
ENTER
Adjusting the Backlight Brightness — The backlight of the
display can be adjusted to suit ambient conditions. The factory
default is set to the highest level. To adjust the backlight of the
Current Sensor Board (CSB) — The CSB is used to
monitor the status of the compressors by measuring current and
providing an analog input to the main base board (MBB) or
compressor expansion module (CXB).
Navigator module, press the
key until the display
ESCAPE
reads, “Select a menu item.” Using the arrow keys move to the
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a field-
installed accessory. The EMM module receives 4 to 20 mA
inputs for the percent capacity, temperature reset, cooling set
point, and demand limit functions. The EMM module also re-
ceives the switch inputs for the field-installed 2-stage demand
limit and when two thermostats are used for one unit. The
EMM module communicates the status of all inputs with the
MBB, and the MBB adjusts the control point, capacity limit,
and other functions according to the inputs received.
Configuration mode. Press
mode. The display will read:
> TEST OFF
to obtain access to this
ENTER
METR OFF
LANG ENGLISH
will cause the “OFF” to flash. Use the up
Pressing
ENTER
or down arrow keys to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the
ENTER
Table 2 — Scrolling Marquee Display Menu Structure*
RUN
STATUS
SERVICE
TEST
SET
POINTS
TIME
CLOCK
OPERATING
MODES
MODE
TEMPERATURES PRESSURES
INPUTS OUTPUTS CONFIGURATION
ALARMS
Manual
Mode
On/Off
(TEST)
Auto
Display
(VIEW)
Unit
Temperatures
(UNIT)
Ckt A
Pressures
(PRC.A)
Unit
Discrete
(GEN.I)
Unit
Discrete
(GEN.O)
Cooling
(COOL)
Display
(DISP)
Unit Time
(TIME)
Modes
(MODE)
Current
(CRNT)
Machine
Hours/Starts
(RUN)
Unit
Outputs
(OUTS)
Ckt A
Temperatures
(CIR.A)
Ckt B
Pressures
(PRC.B)
Head
Pressure
(HEAD)
Reset
Alarms
(RCRN)
Ckt A/B
(CRCT)
Ckt A
(CIR.A)
Unit Configuration
(UNIT)
Unit Date
(DATE)
Task State
(TSKS)
Daylight
Saving
Time
Compressor Ckt A Comp
Ckt B
Temperatures
(CIR.B)
Unit
Analog
(4-20)
Alarm
History
(HIST)
Ckt B
(CIR.B)
CCN Network
(CCN)
Run Hours
(HOUR)
Tests
(CMPA)
(DST)
Local
Holiday
Schedules
(HOL.L)
Compressor Ckt B Comp
Options 1
(OPT1)
Starts
Tests
(STRT)
(CMPB)
Preventive
Maintenance
(PM)
Schedule
Number
(SCH.N)
Options 2
(OPT2)
SUB-MODE
Local
Software
Version
(VERS)
Motormaster
(M.MST)
Schedule
Number
(SCH.L)
Reset Cool
Temperature
(RSET)
Schedule
Overide
(OVR)
Set Point Select
(SLCT)
Service
Configuration
(SERV)
Broadcast
Configuration
(BCST)
LEGEND
Ckt
—
Circuit
*Throughout this text, the location of items in the menu structure will be described in
the following format:
Item Expansion (Mode NameSub-mode NameITEM)
18
RED LED - STATUS
GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
YELLOW LED -
CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER
CEPL130346-01
K11
K10
K9
K5
K8
K6
K7
J1
STATUS
J2
J3
J10
LEN
J4
K1
K4
K3
K2
CCN
J5
J6
J7
J8
J9
Fig. 20 — Main Base Board
Table 3 — Thermistor Designations
positions, the unit is allowed to operate and respond to the
scheduling configuration, CCN configuration and set point
data. See Fig. 21.
THERMISTOR INPUT
Return Air (Accessory)
PIN CONNECTION POINT
MBB J8-11,12; LVT 19,20
MBB J8-12,13; LVT 11,19
Supply Air (Accessory)
Emergency On/Off Switch — The Emergency On/Off
switch should only be used when it is required to shut the
unit off immediately. Power to the MBB, CXB, AUX, EMM,
and scrolling marquee display is interrupted when this switch is
off and all outputs from these modules will be turned off.
Compressor Return Gas
Temperature A
MBB J8-1,2
Compressor Return Gas
Temperature B
MBB J8-3,4
MBB J8-7,8
Outdoor Air Temperature
Discharge Temperature
(Digital Option Only)
AUX J6-1,2
Board Addresses — The main base board (MBB) has a
3-position Instance jumper that must be set to ‘1.’ All other
boards have 4-position DIP switches. All switches are set to
‘On’ for all boards.
Space Temperature (Accessory)
MBB J8-5,6; LVT 21,22
Table 4 — Switch Inputs
SWITCH INPUT
Thermostat Y1 (Accessory)
Thermostat Y2 (Accessory)
Fan Status 1 (Accessory)
Fan Status 2 (Accessory)
Remote On/Off
PIN CONNECTION POINT
LVT 12,18
Control Module Communication
RED LED — Proper operation of the control boards can be
visually checked by looking at the red status LEDs
(light-emitting diodes). When operating correctly, the red status
LEDs should be blinking in unison at a rate of once every
2 seconds. If the red LEDs are not blinking in unison, verify
that correct power is being supplied to all modules. Be sure that
the main base board (MBB) is supplied with the current soft-
ware. If necessary, reload current software. If the problem still
persists, replace the MBB. A red LED that is lit continuously or
blinking at a rate of once per second or faster indicates that the
board should be replaced.
LVT 15,18
LVT 16,18
LVT 17,18
LVT 13,14
High Pressure Switch A
High Pressure Switch B
MBB J6-4
MBB J6-6
Compressor Expansion Module (CXB) — The
CXB is only used on unit sizes 070-100 to provide additional
inputs and outputs for fans and compressors when the unit has
more than 4 compressors.
AUX Board (AUX) — The AUX is used with the digital
scroll option and the low ambient head pressure option. It pro-
vides additional inputs and outputs for digital scroll control
along with analog outputs to control head pressure control fan
speeds.
GREEN LED — The MBB has one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. All other boards have a LEN LED
which should be blinking whenever power is on. Check LEN
connections for potential communication errors at the board J3
and/or J4 connectors. Communication between modules is
accomplished by a 3-wire sensor bus. These 3 wires run in
parallel from module to module. The J4 connector on the MBB
provides both power and communication directly to the
marquee display only.
Enable/Off/Remote Contact Switch — The Enable/
Off/Remote Contact switch is a 3-position switch used to
control the unit. When switched to the Enable position, the unit
is under its own control. Move the switch to the Off position to
shut the unit down. Move the switch to the Remote Contact po-
sition and a field-installed dry contact can be used to start the
unit. The contacts must be capable of handling a 24 vac, 50 mA
load. In the Enable and Remote Contact (dry contacts closed)
YELLOW LED — The MBB has one yellow LED. The
Carrier Comfort Network (CCN) LED will blink during times
of network communication.
19
SCROLLING MARQUEE
DISPLAY
CB1
CB2
CB3
REMOTE
CONTROL
OFF
ON
SW1 OFF
ENABLE
SW2
LEGEND
CB — Circuit Breaker
SW — Switch
ENABLE/OFF/REMOTE
CONTACT SWITCH
EMERGENCY
ON-OFF SWITCH
Fig. 21 — Scrolling Marquee, Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations
4. The RJ14 CCN connector on LVT can also be used, but is
Carrier Comfort Network® (CCN) Interface —
only intended for temporary connection (for example, a
The 38AP units can be connected to the CCN if desired. The
laptop computer running Service Tool).
communication bus wiring is a shielded, 3-conductor cable
with drain wire and is supplied and installed in the field. See
IMPORTANT: A shorted CCN bus cable will prevent some
Table 5. The system elements are connected to the communi-
routines from running and may prevent the unit from start-
cation bus in a daisy chain arrangement. The positive pin of
ing. If abnormal conditions occur, unplug the connector. If
each system element communication connector must be wired
conditions return to normal, check the CCN connector and
to the positive pins of the system elements on either side of it.
cable. Run new cable if necessary. A short in one section of
This is also required for the negative and signal ground pins of
the bus can cause problems with all system elements on the
each system element. Wiring connections for CCN should be
bus.
made at LVT. Consult the CCN Contractor’s Manual for fur-
ther information.
NOTE: Conductors and drain wire must be 20 AWG (Ameri-
can Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of
–20 C to 60 C is required. Wire manufactured by Alpha (2413
or 5463), American (A22503), Belden (8772), or Columbia
(02525) meets the above mentioned requirements.
Table 5 — CCN Communication Bus Wiring
PART NO.
Regular Wiring
1895
MANUFACTURER
Plenum Wiring
Alpha
—
A48301
884421
—
M64430
—
American
Belden
Columbia
Manhattan
Quabik
A21451
8205
D6451
M13402
6130
It is important when connecting to a CCN communication
bus that a color coding scheme be used for the entire network
to simplify the installation. It is recommended that red be used
for the signal positive, black for the signal negative, and white
for the signal ground. Use a similar scheme for cables contain-
ing different colored wires.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to a ground at one point only. If the commu-
nication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only). To connect the unit to
the network:
OPERATING DATA
Sensors — The electronic control uses 3 to 7 thermistors to
sense temperatures for controlling unit operation. See Table 3.
These sensors are outlined below. Three different thermistor
curves are utilized depending on the thermistor and the config-
uration of the input. The three different types are 5 kat 77 F
(25 C), 10 kat 77 F (25 C), and 86 k at 77 F (25 C). See
Thermistors section on page 49 for additional information.
RETURN AIR TEMPERATURE (RAT) ACCESSORY
(Part No. 33ZCSENSAT) — A return air temperature sensor
is required for unit sizes 040-100 and all units equipped with
the digital scroll option. The sensor is field installed in the
indoor unit and wired to the LVT of the unit to measure the air
temperature entering the evaporator coil. The sensor should be
located directly in front of the evaporator coil after an outside
air intake.
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (–) conductors. (Substitute appropri-
ate colors for different colored cables.)
3. Connect the red wire to (+) terminal on LVT of the plug,
the white wire to COM terminal, and the black wire to the
(–) terminal.
The RAT sensor consists of a thermistor encased within a
stainless steel probe. See Fig. 22. The sensor probe is 6 in.
nominal length with 114 in. of unshielded, 2-conductor
18 AWG twisted-pair cables. The sensor temperature range is
–40 to 245 F with a nominal resistance of 10,000 ohms at 77 F.
The sensor has with an accuracy of ±0.36 F.
20
3.90
3.00
1
2
4
5
6
3
RED(+)
.175 DIA
x .600
WHT(GND)
CCN COM
BLK(-)
SEN
.08
SW1
.39
BRN (GND)
BLU (SPT)
SENSOR WIRING
FOAM GASKET
.40'' O.D.
.250 .01 Dia
5.5 .5
NOTE: All dimensions
shown in inches.
PLENUM RATED CABLE
114''
Fig. 23 — Space Temperature Sensor
Typical Wiring (33ZCT55SPT)
6
Fig. 22 — 33ZCSENSAT Sensor
SUPPLY AIR TEMPERATURE (SAT) ACCESSORY
(33ZCSENSAT) — A supply air temperature sensor is
required for unit sizes 040-100 and all units equipped with the
digital scroll option. The SAT sensor consists of a thermistor
encased within a stainless steel probe. See Fig. 22. The SAT
sensor probe is 6 in. nominal length with 114 in. of unshielded,
2-conductor 18 AWG twisted-pair cables. The sensor tempera-
ture range is –40 to 245 F with a nominal resistance of
10,000 ohms at 77 F. The sensor has an accuracy of ±0.36 F.
1
2
4
5
6
3
RED(+)
WHT(GND)
CCN COM
BLK(-)
SET
SEN
NOTE: The sensor must be mounted in the discharge of the
unit, downstream of the cooling coil and before any heating
coil or heat exchanger if reheat is utilized. Be sure the probe tip
does not come in contact with any of the unit surfaces.
SW1
BLK
(T56)
BRN (GND)
BLU (SPT)
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
COMPRESSOR RETURN GAS TEMPERATURE SEN-
SOR (RGT) — These sensors are factory installed in a fric-
tion fit well located in the suction line of each circuit. They are
a 5 k thermistor connected to the main base board.
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) —
This sensor is factory installed on a bracket which is inserted
through the base pan of the unit on the unit sizes 025-060 and
mounted to the back of the control box on the unit sizes 070-
100. This sensor is a 5 k thermistor connected to the main
base board.
Cool
Warm
Fig. 24 — Space Temperature Sensor
Typical Wiring (33ZCT56SPT)
The sensor should be mounted approximately 5 ft from the
floor in an area representing the average temperature in the
space. Allow at least 4 ft between the sensor and any corner.
Mount the sensor at least 2 ft from an open doorway.
DISCHARGE
TEMPERATURE
THERMISTOR
(DTT) — This sensor is only used on units with a digital
compressor. The sensor is mounted on the discharge line close
to the discharge of the digital compressor. It attaches to the dis-
charge line using a spring clip and protects the system from
high discharge gas temperature when the digital compressor is
used. This sensor is a 86 k thermistor connected to the AUX
board.
To connect the space temperature sensor (Fig. 25):
1. Use a 20 gage wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three-conductor shielded cable for the sensor and set
point adjustment connections. The standard CCN
communication cable may be used. If the set point
adjustment (slidebar) is not required, then an unshielded,
18 or 20 gage, two-conductor, twisted pair cable may be
used. Connect one wire of the twisted pair to one SEN
terminal and connect the other wire to the other SEN ter-
minal located under the cover of the space temperature
sensor.
SPACE TEMPERATURE SENSOR (SPT) — The space
temperature sensors are used to measure the interior
temperature of a building. The following three types of SPT
sensors are available:
• Space temperature sensor (33ZCT55SPT) with timed
override button (see Fig. 23)
• Space temperature sensor (33ZCT56SPT) with timed
override button and set point adjustment (see Fig. 24)
• Space temperature sensor (33ZCT59SPT) with occu-
pancy override button, set point adjustment slidebar, and
LCD (liquid crystal display) display
2. Connect the other ends of the wires to terminals 21 and
22 on LVT located in the unit control box.
3. Connect the T56 set point adjustment between the SET
terminal and LVT terminal 23.
21
Units on the CCN can be monitored from the space using
the RJ11 connector provided with the space sensor, if desired.
To wire the RJ11 connector into the CCN (Fig. 26):
SPT
SENSOR
IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the CCN communication bus
wire used for the entire network. Refer to Table 5 for
acceptable wiring.
LVT
21
SEN
SEN
SET
22
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black (–) conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)
23
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of
the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the
space temperature sensor.
Fig. 25 — Typical SPT Wiring
T-55 SPACE
SENSOR
6
5
4
3
2
1
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus.
NOTE: See Fig. 27 for space temperature averaging.
CCN+
TO CCN
CCN GND
COMM 1
BUS (PLUG)
AT UNIT
CCN-
Fig. 26 — CCN Communications Bus Wiring to
Optimal Space Sensor RJ11 Connector
RED
BLK
RED
BLK
J6
6
RED
BLK
RED
BLK
RED
BLK
7
SENSOR 1
SENSOR 2
SENSOR 3
SENSOR 4
SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION
J6
6
RED
BLK
RED
BLK
RED
BLK
7
SENSOR 3
SENSOR 1
SENSOR 2
RED
BLK
RED
BLK
SENSOR 6
SENSOR 4
SENSOR 5
RED
BLK
RED
BLK
LEGEND
Factory Wiring
Field Wiring
SENSOR 8
SENSOR 9
SENSOR 7
SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION
Fig. 27 — Space Temperature Averaging
22
See VAV Supply Air Temperature Reset and Demand Limit
sections on pages 29 and 31 for further details.
Fan Status Input — A proof-of-fan operation is recom-
mended and needs to be field installed in the indoor unit. Sev-
eral different types of switches can be utilized, such as a differ-
ential pressure switch located across the indoor fan or auxiliary
contacts on an indoor fan contactor.
CAUTION
Care should be taken when interfacing with other manufac-
turer’s control systems due to possible power supply
differences, full wave bridge versus half wave rectification.
The two different power supplies cannot be mixed.
ComfortLink™ controls use half wave rectification. A
signal isolation device should be utilized if a full wave
bridge signal generating device is used.
Thermostat Input — A two-stage thermostat can be
used for constant volume applications to provide Y1 and Y2
cooling inputs.
Pressure Transducer Inputs — Each refrigerant cir-
cuit is equipped with a suction and discharge pressure trans-
ducer. The suction pressure transducers have a yellow body
with a pressure range of -6.7 to 420 psig while the discharge
transducers have a red body with a pressure range of 14.5 to
667 psig. These inputs connect to the MBB (main base board)
and are used to monitor the status of the unit and to ensure the
unit operates within the compressor envelope. The transducers
are used to protect the compressor from operating at too low or
too high of a pressure condition. In some cases, the unit may
not be able to run at full capacity. The MBB will automatically
reduce the capacity of a circuit as needed to maintain specified
maximum/minimum operating pressures.
Control — When mechanical cooling is required, the MBB
has the capability to control the unit capacity by staging multi-
ple scroll compressors and controlling the digital scroll com-
pressor operation. The control also checks on various other op-
eration parameters in the unit to make sure that safeties are not
exceeded and the compressors are reliably operated.
The ComfortLink™ control system offers two basic control
approaches to mechanical cooling; constant volume operation
for 2 stages of cooling or VAV operation for multiple stages
of cooling. In addition to these methods of control, the
ComfortLink control offers the ability to run multiple stages of
cooling for either a space temperature sensor or thermostat
control by controlling the unit to either a low or high cool set
point. The control type ConfigurationOPT2C.TYP de-
termines the selection of the type of cooling control as well as
the method for selecting a cooling mode.
Energy Management Module (Fig. 28) — The
energy management module (EMM) is a factory-installed op-
tion (FIOP) or field-installed accessory used for the following
types of temperature reset, demand limit, and capacity control
features:
•
•
•
•
•
4 to 20 mA temperature reset
4 to 20 mA cooling set point
SETTING UP THE SYSTEM
4 to 20 mA desired capacity set point
4 to 20 mA demand limit
Machine Control Type (ConfigurationOPT2 C.TYP)
— The most important cooling control configuration is located
under Configuration OPT2. This configuration defines the
method and control source responsible for selecting a cooling
mode. The configuration also determines the method by which
compressors are staged. Control types are:
Discrete inputs for 2-step demand limit (requires field-
supplied dry contacts capable of handling a 24 vac,
50 mA load)
•
Discrete inputs for units with dual thermostats
NOTE: A field-supplied 4 to 20 mA signal generator is re-
quired for use with the EMM.
• C.TYP = 1 (VAV-RAT) configuration refers to standard
VAV operation.
CEBD430351-0396-01C
J1
J2
LEN
J4
J3
STATUS
J5
J7
J6
TEST 2
GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS
DIP SWITCH
RED LED - STATUS
Fig. 28 — Energy Management Module
23
• C.TYP = 3 (TSTAT-MULTI) configuration will force
the MBB to monitor the thermostat inputs to make a
determination of mode. Unlike traditional 2-stage ther-
mostat control, the unit is allowed to use multiple stages
of cooling control and perform VAV style operation. The
control will be able to call out a low set point or a high
set point to maintain supply air temperature. (Required
for 025-030 units with digital scroll option and 040-100
units with two-stage thermostat control.)
supply air depending on space temperature vs space
temperature set point. The control uses SPS.P, LC.ON,
HC.ON, and LC.OF to determine the leaving set point.
LC.ON and HC.ON are added to the space temperature
set point to determine when cooling mode will begin and
when CSP1 and CSP2 will be used for leaving set point.
Based on LC.OF, the control point transitions between
CSP1 and CSP2. LC.OF is used to calculate the space tem-
perature at which control point is raised based on space tem-
perature vs space temperature set point (SPS.P) plus
LC.ON minus LC.OF. The control point transition from
CSP2 to CSP1 occurs when space temperature is below
LC.OF divided by 2.
• C.TYP = 4 (TSTAT-2STG) configuration will force the
MBB to monitor the thermostat inputs to make a deter-
mination of mode.
• C.TYP = 5 (SPT-MULTI) configuration will force the
MBB to monitor a space temperature sensor to make a
determination of mode. Unlike traditional 2-stage space
temperature control, the unit is allowed to use multiple
stages of cooling control and perform VAV style opera-
tion. The control will be able to call out a low set point or
a high set point to maintain supply air temperature.
• C.TYP = 7 (% CAPACITY) configuration will force the
MBB to monitor the 4-20 cooling demand CL.MA input
and translate this into desired % capacity for the unit.
• C.TYP = 9 (VAV-SETPOINT) configuration will force
the MBB to monitor the 4-20 cooling demand CL.MA
input. This value will be translated into a desired leav-
ing-air set point ranging from 40 to 80 F. The control will
translate the input linearly with 4 ma equal to 40 F set
point and 20 mA equal to 80 F set point.
For example (see Fig. 29):
Given: SPS.P = 72 F, LC.ON = 1, HC.ON = 3,
LC.OF = 2 F, CSP1 = 60 F, and CSP2 = 55 F
If space temperature equals 73 F (72+1) (Low Cool)
cooling will begin and control set point equals 60 F
(CSP1).
If space temperature is greater than 76 F (72+1+3 = 76)
(High Cool), control point set point would equal 55 F
(CSP2).
If space temperature falls below 72 F (73-2/2) (Low
Cool minus LC.OF/2), control point transitions back to
60 F CSP1 if space continues to fall below 71 F (73-2)
(Low Cool minus LC.OF), the unit is shut off.
Unit Capacity Control Based on Unit Type — The MBB
uses several set points to control capacity depending on unit
type. The set points are located in the set point area of the dis-
play SetPointsCOOL. Refer to Table 6 and the following
descriptions.
76 F
Hi Cool Start
H.C.ON
73 F
Lo Cool Start
Table 6 — Unit Capacity Control
L.C. OF L.C. OF/2
ITEM
DESCRIPTION
RANGE UNITS DEFAULT
L.C.ON
CSP1 Cooling Set Point 1
CSP2 Cooling Set Point 2
40-80
40-80
65-80
F
F
F
65
55
74
72 F
Hi Cool End 72 F
A48-7701
SPS.P Space Temperature Cooling Set
Point
Cooling Setpoint
L.C.ON Demand Level Low Cool On
H.C.ON Demand Level (+) High Cool On 0.5-20.0
L.C.OF Demand Level (–) Low Cool Off 0.5-2
–1-2
^F
^F
^F
1.5
0.5
1
Lo Cool End 71 F
• C.TYP = 1 (VAV-RAT) is a capacity control routine that
controls compressor capacity to supply air temperature.
The MBB will attempt to control leaving temperature to
the control point (CTPT) which equals CSP1 plus any
reset which is being applied.
• C.TYP = 3 (TSTAT-MULTI) configuration will force the
MBB to monitor the thermostat inputs to make a deter-
mination of control point (CTPT). The control will vary
the control point based on Y1 and Y2 inputs. When Y1 is
closed CSP1 will be used and when Y2 is closed CSP2
will be used as the supply air temperature set point.
CSP1 should be greater than CSP2.
• C.TYP = 4 (TSTAT-2STG) configuration will force the
MBB to monitor the thermostat inputs to make a deter-
mination of mode and capacity. If Y1 input is closed,
50% of the unit capacity will be energized and if Y2 is
closed, 100% of the unit capacity will be energized.
Fig. 29 — Space Temperature vs.
Space Temperature Set Point
• C.TYP = 7 (% CAPACITY) configuration will force the
MBB to monitor the input 4-20 cooling demand CL.MA
and translate this into desired % capacity for the unit.
The control will attempt to match the desired capacity
insuring the unit operates the compressor within com-
pressor safeties and timeguards. (Requires the EMM
option or accessory.)
• C.TYP = 9 (VAV-SETPOINT) configuration will force
the MBB to operate as a VAV unit and control capacity to
meet supply air temperature. The control point is devel-
oped from the 4-20 cooling demand CL.MA input value.
The 4 to 20 mA input will be translated into a desired
control point ranging from 40 to 80 F. The control will
translate the input linearly with 4 mA equal to 40 F set
point and 20 mA equal to 80 F set point. (Requires the
EMM option or accessory.)
NOTE: This is not a preferred method of control for units
with greater than 2 stages of capacity
• C.TYP = 5 (SPT-MULTI) configuration will force the
MBB to monitor the thermostat inputs to determine
mode and cooling set point as the unit is controlled by
space temperature vs space temperature set point SPS.P.
Unlike traditional 2-stage thermostat control, the unit is
allowed to use multiple stages of cooling control and per-
form VAV style operation. The control will be able to call
out a low set point (CSP1) or high set point (CSP2) for
Capacity Control Logic when Control is Controlling to Sup-
ply Temperature — The control system cycles compressors,
hot gas bypass and the digital compressor to maintain the sup-
ply temperature at or close to the control point of the unit. The
SAT and RAT sensors are used by the main base board (MBB)
to determine the temperature drop across the evaporator and
are used in determining the optimum time to add or subtract ca-
pacity stages. The CSP set points can be automatically reset by
24
the return temperature, space, or outdoor-air temperature reset
features. It can also be reset from an external 4 to 20 mA signal
(requires energy management module factory-installed option
or field-installed accessory).
The control has an automatic lead-lag feature built in which
determines the wear factor (combination of starts and run
hours) for each compressor. If all compressors are off and less
than 30 minutes has elapsed since the last compressor was
turned off, the wear factor is used to determine which compres-
sor to start next. As additional stages of compression are re-
quired, the processor control will add them. If a circuit is to be
stopped, the compressor with the lowest wear factor will be
shut off first. See Table 7 for compressor size information and
Table 8 for compressor loading sequence.
The capacity control algorithm runs every 30 seconds. The
algorithm attempts to maintain the control point at the desired
set point. Each time it runs, the control reads the entering and
leaving temperatures. The control determines the rate at which
conditions are changing and calculates 2 variables based on
these conditions. Next, a capacity ratio is calculated using the
2 variables to determine whether or not to make any changes to
the current stages of capacity. This ratio value ranges from
–100 to +100%. If the next stage of capacity is a compressor,
the control starts (stops) a compressor when the ratio reaches
+100% (-100%). A delay of 90 seconds occurs after each ca-
pacity step change. Refer to Table 8.
Table 7 — Compressor Size Information
CIRCUIT A (Nominal hp)
CIRCUIT B (Nominal hp)
UNIT SIZE
Compressor A1
Compressor A2
Compressor A3
Compressor B1
Compressor B2
Compressor B3
38APS025
38APD025
38APS027
38APD027
38APS030
38APD030
38APS040
38APD040
38APS050
38APD050
38APD060
38APD070
38APD080
38APD090
38APD100
11
11
13
13
15
15
13
10
15
12
13
15
15
13
15
11
—
13
—
15
—
13
10
15
12
13
15
15
13
15
—
—
—
—
—
—
13
—
15
—
—
—
—
13
15
—
11
—
13
—
15
—
9
—
—
—
—
—
—
—
9
—
—
—
—
—
—
—
—
—
—
—
11
15
15
15
—
13
15
11
15
15
15
—
13
15
11
15
15
15
Table 8 — Part Load Data Percent
LOADING SEQUENCE A
LOADING SEQUENCE B
CONTROL
STEPS
38AP UNIT SIZE
% Displacement
Compressor
% Displacement
Compressor
1
2
50
A1
—
—
—
—
38APS025-030
38APD025-030
100
A1,A2
1
2
50
100
A1
A1, B1
50
100
B1
A1,B1
1
2
3
33
67
A1
—
—
—
—
—
—
38APS040,050
38APD040
A1,A2
100
A1,A2,A3
1
2
3
4
27
50
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
23
50
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
77
73
100
100
1
2
3
4
23
50
A1
27
50
B1
A1,B1
A1,B1
38APD050,060
38APD070
73
A1,A2,B1
A1,A2,B1,B2
77
A1,B1,B2
A1,A2,B1,B2
100
100
1
2
3
4
5
15
42
A1
15
42
B1
A1,B1
A1,B1
57
A1,A2,B1
57
A1,B1,B2
85
A1,A2,B1,B2
A1,A2,B1,B2,B3
85
A1,A2,B1,B2
A1,A2,B1,B2,B3
100
100
1
2
3
4
5
20
40
A1
20
40
B1
A1,B1
A1,B1
38APD080
38APD090
60
A1,A2,B1
A1,A2,B1,B2
A1,A2,B1,B2,B3
60
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
80
100
80
100
1
2
3
4
5
6
15
32
A1
18
32
B1
A1,B1
A1,B1
48
A1,A2,B1
51
A1,B1,B2
66
A1,A2,B1,B2
A1,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
66
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
82
85
100
100
1
2
3
4
5
6
17
33
A1
17
33
B1
A1,B1
A1,B1
50
A1,A2,B1
50
A1,B1,B2
38APD100
67
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
67
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
83
83
100
100
NOTES:
2. When unit is equiped with digital scroll option, sequence A is always
used.
1. These capacity steps may vary due to different capacity staging
sequences.
25
MINUTES LEFT FOR START — This value is displayed
only in the network display tables (using Service Tool,
ComfortVIEW™ or ComfortWORKS® software) and
represents the amount of time to elapse before the unit will start
its initialization routine. This value can be zero without the
machine running in many situations. This can include being
unoccupied, ENABLE/OFF/REMOTE CONTACT switch in
the OFF position, CCN not allowing unit to start, Demand
Limit in effect, no call for cooling due to no load, and alarm or
alert conditions present. If the machine should be running and
none of the above are true, a minimum off time (DELY, see
below) may be in effect. The machine should start normally
once the time limit has expired.
close to the set point (within an adjustable deadband) and mov-
ing toward the set point.
Ramp Loading — The ramp loading control (Configuration
SLCTCRMP) limits the rate of change of supply temper-
ature. If the unit is in a Cooling mode and configured for Ramp
Loading, the control makes 2 comparisons before deciding to
change stages of capacity. The control calculates a temperature
difference between the control point and supply temperature. If
the difference is greater than 4° F (2.2° C) and the rate of
change (°F or °C per minute) is more than the configured Cool-
ing Ramp Loading value (CRMP), the control does not allow
any changes to the current stage of capacity.
Minimum Load Control — If equipped, the minimum load
control valve is energized only when one compressor on the
circuit is running and the unit is unloading.
Low Saturated Suction Protection — The control will try to
prevent shutting a circuit down due to low saturated suction
conditions by removing stages of capacity. See Alerts section.
MINUTES
OFF
TIME
(ConfigurationOPT2
DELY) — This user-configurable time period is used by
the control to determine how long unit operation is delayed
after power is applied/restored to the unit. Typically, this time
period is configured when multiple machines are located on a
single site. For example, this gives the user the ability to pre-
vent all the units from restarting at once after a power failure.
A value of zero for this variable does not mean that the unit
should be running.
Head Pressure Control — The main base board
(MBB) controls the condenser fans to maintain the lowest
condensing temperature possible, and thus the highest unit
efficiency. The MBB uses the saturated condensing tempera-
ture input from the discharge pressure transducer and outside
air temperature sensor to control the fans. If OAT is greater
than 70 F before a circuit is starting, then all condenser fan
stages will be energized. A fan stage is increased based on
SCT. When the highest SCT of both circuits is greater than fan
on set point, then an additional stage of fan will be added to the
current fan stage. Fan On Set Point (F.ON) equals Head Set
Point ON (115 F) except after a fan stage increase when Head
Set Point is increased by Fan Stage Delta (10 F). A fan stage is
decreased when the SCTs of both circuits are less than fan off
set point for two minutes. Fan Off Set Point (F.OFF) equals
Head Set Point OFF (–72 F). Table 9 shows the number of fan
stages, contactors energized and the fans that are on during the
fan stage. Unit sizes 025 to 060 have common fan control. Unit
sizes 070 to 100 have some fans that are common and some
that are controlled individually. Figure 30 shows the location
of each fan and compressor within the unit.
MOTORMASTER® V OPTION — For low-ambient opera-
tion, the first stage of fans is equipped with the Motormaster V
head pressure controller option or accessory. For units with
common fans, the control will control the Head Pressure Set-
point (–10 F) and the highest SCT to try to maintain it at 100 F.
Unit sizes 070 to 100 have one Motormaster V for each circuit
and the control tries to maintain SCT at 100 F for the circuit.
The controller is given an ON command with the first stage of
fan and adjusts fan speed.
NOTE: If the unit has digital scroll or hot gas bypass, circuit A
is always lead.
LEAD/LAG DETERMINATION — This is a configurable
choice and is factory set to be automatic for all units. The value
can be changed to Circuit A or Circuit B leading as desired. Set
at automatic, the control will sum the current number of logged
circuit starts and one-quarter of the current operating hours for
each circuit. The circuit with the lowest sum is started first.
Changes to which circuit is the lead circuit and which is the lag
are also made when total machine capacity is at 100% or when
there is a change in the direction of capacity (increase or
decrease) and each circuit’s capacity is equal.
CAPACITY CONTROL OVERRIDES — The following over-
rides will modify the normal operation of the routine.
Deadband Multiplier — The user configurable deadband mul-
tiplier (ConfigurationSLCTZ.GN) has a default value of
1.0. The range is from 1.0 to 4.0. When set to other than 1.0,
this factor is applied to the capacity Load/Unload Factor. The
larger this value is set, the longer the control will delay between
adding or removing stages of capacity.
First Stage Override — If the current capacity stage is zero,
the control will modify the routine with a 1.2 factor on adding
the first stage to reduce cycling. This factor is also applied
when the control is attempting to remove the last stage of
capacity.
Slow Change Override — This control prevents the capacity
stages from being changed when the supply temperature is
Table 9 — Fan Stages
CIRCUIT A STAGES/COMMON FAN STAGES
CIRCUIT B FAN STAGES
Contactor Energized
38AP UNIT SIZE
Fan Stage
Contactor Energized
Fans Operating
Fan Stage
Fans Operating
Stage 1
Stage 2
Stage 1
Stage 2
Stage 3
Stage 1
Stage 2
Stage 3
Stage 4
FC1
OFM1
025-030
040,050
—
—
—
FC1,2
OFM1,2
FC1
FC2
FC1,2
FC1
FC2
FC1,2
FC1,2,3
OFM3
OFM1,2
OFM1,2,3
OFM3
OFM1,2
OFM1,2,3
OFM1,2,3,4
—
—
—
—
—
060
—
Stage 1*
Stage 2
Stage 3
Stage 1
Stage 2
FC2,4
FC1
OFM1,2
OFM3
Stage 1*
Stage 2
Stage 3
Stage 1
Stage 2
Stage 3
FC1,3
FC2
OFM3,4
OFM1
070
080
FC1,3
OFM3,4
FC2,4
OFM1,2
FC1
FC1,3
OFM5
OFM5,6,(2)
FC4
OFM3
OFM3,2,(6)
OFM3,1,2,(6)
FC3,4
FC2,3,4
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
FC4
FC1
FC4,1
FC4,3
FC1,3
FC4,1,3
OFM3
OFM5
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
FC4
FC2
FC4,2
FC4,3
FC2,3
FC4,2,3
OFM3
OFM1
OFM3,5
OFM3,1
090,100
OFM3,(2),4,6
OFM5,(2),4,6
OFM3,5,(2),4,6
OFM3,2,4,(6)
OFM1,2,4,(6)
OFM3,1,2,4,(6)
* Fan Stage 1 on unit size 070 is used only when ambient temperature is less than 32 F.
26
Outdoor Fan Layout – Top View
OFM1
OFM1
OFM2
OFM1
OFM2
OFM3
OFM3
OFM2
OFM4
Sizes 025-030
OFM1
Sizes 040, 050
OFM5
Sizes 060, 070
OFM1
OFM2
OFM3
OFM5
OFM3
OFM2
OFM6
OFM4
OFM6
Size 080
Sizes 090, 100
Compressor Layout Dual Circuit – Top View
A1
B1
A2
B2
B1
A2
A1
A1
B3
B2
Sizes 040-060
B1
Sizes 025-030
Sizes 070, 080
A3
A2
A1
B1
B2
B3
Sizes 090, 100
Compressor Layout Single Circuit – Top View
A1
A2
A1
A2
A3
Sizes 025-030
Sizes 040, 050
Fig. 30 — Compressor and Fan Location
27
demand limit control option. Because of this limitation, the unit
may not be able to produce the desired supply fluid tempera-
ture. Demand limit can be controlled by switch inputs or a 4 to
20 mA signal.
LOW TEMPERATURE COOLING (MD17) — Unit is in
Cooling mode and the rate of change of the supply fluid is neg-
ative and decreasing faster than -0.5° F per minute. Error be-
tween supply fluid and control point exceeds fixed amount.
Control will automatically unload the unit if necessary.
HIGH TEMPERATURE COOLING (MD18) — Unit is in
Cooling mode and the rate of change of the supply fluid is pos-
itive and increasing. Error between supply fluid and control
point exceeds fixed amount. Control will automatically load
the unit if necessary to better match the increasing load.
TIME GUARD ACTIVE (MDTG) — Compressor time
guard is active, preventing the compressor from starting.
HIGH SCT CIRCUIT A (MD21) — Unit is in a Cooling
mode and the saturated condensing temperature (SCT) is great-
er than the calculated maximum limit. No additional stages of
capacity will be added. Unit capacity may be reduced if SCT
continues to rise to avoid high-pressure switch trips by reduc-
ing condensing temperature.
HIGH SCT CIRCUIT B (MD22) — Unit is in a Cooling
mode and the saturated condensing temperature (SCT) is great-
er than the calculated maximum limit. No additional stages of
capacity will be added. Unit capacity may be reduced if SCT
continues to rise to avoid high-pressure switch trips by reduc-
ing condensing temperature.
Service Test — Both main power and control circuit
power must be on.
The Service Test function should be used to verify proper
operation of condenser fan(s), compressors, minimum load
valve solenoid (if installed), liquid line solenoid valve (if
installed), and remote alarm relay. To use the Service Test
mode, the Enable/Off/Remote Contact switch must be in the
OFF position. Use the display keys and Service Test Mode and
Sub-Mode Directory table in Appendix A to enter the mode
and display TEST. Press
twice so that OFF flashes.
ENTER
Enter the password if required. Use either arrow key to change
the TEST value to the ON position and press . Place
ENTER
the Enable/Off/Remote Contact switch in the ENABLE posi-
tion. The Service Test mode is now enabled. Press
ESCAPE
down key to enter the OUTS, COMPA or COMPB
and the
sub-mode.
Test the condenser fans, liquid line solenoid and alarm re-
lay by changing the item values from OFF to ON. These dis-
crete outputs are then turned off if there is no keypad activity
for 10 minutes. When testing the digital output the display can
be changed from 1 to 15 by using either the up or down arrow;
the number represents the cycle rate out of a 15 second duty cy-
cle that the output will be energized. If the cycle is set for 7, the
output will be energized 7 seconds out of every 15 seconds.
Test the compressor and minimum load valve solenoid (if in-
stalled) outputs in a similar manner. The minimum load valve
solenoids will be turned off if there is no keypad activity for
10 minutes. Compressors will stay on until they are turned off
by the operator. The Service Test mode will remain enabled for
as long as there is one or more compressors running. All safe-
ties are monitored during this test and they will turn a compres-
sor, circuit or the machine off if required. Any other mode or
sub-mode can be accessed, viewed, or changed during the
TEST mode. The STAT item (Run/StatusVIEW) will dis-
play "0" as long as the Service mode is enabled. The TEST
sub-mode value must be changed back to OFF before the unit
can be switched to Enable or Remote contact for normal
operation.
MINIMUM COMP ON TIME (MD23) — Cooling load
may be satisfied, however control continues to operate com-
pressor to ensure proper oil return. This may be an indication of
oversized application, low fluid flow rate or low loop volume.
LOW SOUND MODE (MD25) — Not applicable.
Operation of Machine Based on Control
Method — Machine On/Off control is determined by
the
configuration
of
the
control
method
(ConfigurationOPT2CTRL). With the control method
set to 0, simply switching the Enable/Off/Remote Contact
switch to the Enable or Remote Contact position (external con-
tacts closed) will put the unit in an occupied state. The control
mode (Operating ModesMODE) will be 1 (OFF LOCAL)
when the switch is Off and will be 5 (ON LOCAL) when in the
Enable position or Remote Contact position with external con-
tacts closed.
Operating Modes
RAMP LOAD LIMITED (MD05) — Ramp load (pull-
down) limiting is in effect. In this mode, the rate at which sup-
ply fluid temperature is dropped is limited to a predetermined
value to prevent compressor overloading. See Cooling Ramp
Loading (ConfigurationSLCTCRMP). The pull-down
limit can be modified, if desired, to any rate from 0.2 to 2° F
(0.1 to 1° C) per minute.
TIMED OVERRIDE IN EFFECT (MD06) — Timed over-
ride is in effect. This is a 1 to 4 hour temporary override of the
programmed schedule, forcing unit to Occupied mode. Over-
ride can be implemented with unit under Local (Enable) or
CCN (Carrier Comfort Network®) control. Override expires af-
ter each use.
SLOW CHANGE OVERRIDE (MD09) — Slow change
override is in effect. The supply fluid temperature is close to
and moving towards the control point.
MINIMUM OFF TIME ACTIVE (MD10) — Unit is being
held off by Minutes Off Time (Configuration
OPT2DELY).
Two other control methods are available for Machine On/
Off control:
OCCUPANCY SCHEDULE (CTRL=2) — The main base
board will use the operating schedules as defined under the
Time Clock mode in the scrolling marquee display. These
schedules are identical. The schedule number must be set to 1
for local schedule.
The schedule number can be set anywhere from 65 to 99
for operation under a CCN global schedule. The Enable/Off/
Remote Contact must be in the Enable or Remote Contact posi-
tion. The control mode (Operating ModesMODE) will be 1
when the switch is Off. The control mode will be 3 when the
Enable/Off/Remote Contact switch input is On and the time of
day is during an unoccupied period. Similarly, the control
mode will be 7 when the time of day is during an occupied
period.
TEMPERATURE RESET (MD14) — Temperature reset is
in effect. In this mode, unit is using temperature reset to adjust
supply fluid set point upward and is currently controlling to the
modified set point. The set point can be modified based on re-
turn fluid, outdoor-air-temperature, space temperature, or 4 to
20 mA signal.
CCN SCHEDULE (CTRL=3) — An external CCN device
controls the On/Off state of the machine. This CCN device
forces the variable 'CHIL_S_S' between Start/Stop to control
the unit. The control mode (Operating ModesMODE) will
be 1 when the switch is Off. The control mode will be 2 when
the Enable/Off/Remote Contact switch input is On and the
DEMAND LIMITED (MD15) — Demand limit is in effect.
This indicates that the capacity of the unit is being limited by
28
CHIL_S_S variable is 'Stop.' Similarly, the control mode will
be 6 when the CHIL_S_S variable is 'Start.'
be set to the temperature difference where the maximum reset
should occur. The variable RM.DG should be set to the
maximum amount of reset desired. To verify that reset is func-
tioning correctly proceed to Run Status mode, sub-mode
VIEW, and subtract the active set point (SETP) from the con-
trol point (CTPT) to determine the degrees reset. Under normal
operation, the unit will maintain a constant leaving temperature
approximately equal to the cooling set point. As the unit load
varies, the return air temperature will change in proportion to
the load. Usually the unit size and supply air temperature set
point are selected based on a full-load condition. At part load,
the air temperature set point may be colder than required. If the
leaving air temperature was allowed to increase at part load, the
efficiency of the machine would increase.
Set Point Adjustment
CV SET POINT ADJUSTMENT — If the unit is configured
for control type SPT MULTI (C.TYP =5) and the Space Tem-
perature Offset Sensor is enabled. (SP.O.S) set to enable
[ConfigurationOPT1]. Space temperature offset corre-
sponds to a slider on a T56 sensor that allows the occupant to
adjust the space temperature by a configured range during an
occupied period. The space temperature offset range (SP.O.R)
value is either added or subtracted from the space temperature
cool set point. Example SPS.P equals 72 F and SP.O.R equals
5 then the cooling set point can be adjusted from 68 to 77 F by
adjusting the T56 slider.
Return temperature reset allows for the leaving temperature
set point to be reset upward as a function of the return air tem-
perature or, in effect, the building load.
Figures 31 and 32 are examples of outdoor air and space
temperature reset.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
Space Temp
Offset Sensor
Enable/
Disable
SP.O.S
SPTOSENS
Space Temp
Offset Range
SP.O.R
1-10
SPTO_RNG
17.8
16.7
15.6
14.4
13.3
12.2
11.1
64
62
60
58
56
54
52
VAV SUPPLY AIR TEMPERATURE RESET — The con-
trol system is capable of changing the controlling set point
based on several different methods. The methods are return
temperature, space temperature (SPT), outside air temperature
(OAT) and from an externally powered 4 to 20 mA signal. Re-
turn air is a measure of the building load. The return tempera-
ture reset is in effect an average building load reset method. An
accessory sensor must be used for SPT reset; either a T55, T56,
or T59 sensor can be used. The energy management module
(EMM) must be used for temperature reset using a 4 to 20 mA
signal. To use 4 to 20 mA reset, one variable must be config-
ured MA.DG, which is the amount of reset desired with a
20 mA signal. The control will interpolate between 0 degrees
reset at 4 mA and the value entered for MA.DG at 20 mA. See
Table 10 for an example of 4 to 20 mA reset.
CHANGE IN
RESET TEMPERATURE
CHANGE
IN SAT
SET POINT
MAXIMUM RESET
CHILLED SET POINT
RESET SET POINT
40
45
50 55 60 65 70 75
80
85 90
OUTSIDE TEMPERATURE (F)
4.4 7.2 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2
OUTSIDE TEMPERATURE (C)
LEGEND
SAT — Supply Air Temperature
CAUTION
Care should be taken when interfacing with other control
systems due to possible power supply differences; full
wave bridge versus half wave rectification. Connection of
control devices with different power supplies may result in
permanent equipment damage. ComfortLink™ controls
incorporate power supplies with half wave rectification. A
signal isolation device should be utilized if the signal gen-
erator incorporates a full wave bridge rectifier.
Fig. 31 — Outdoor-Air Temperature Reset
17.8
16.7
15.6
14.4
13.3
12.2
11.1
64
62
60
58
56
54
52
CHANGE IN
RESET TEMPERATURE
CHANGE
IN SAT
SET POINT
MAXIMUM RESET
To use Outdoor Air or Space Temperature reset, four vari-
ables must be configured. In the Configuration mode under the
sub-mode RSET, items CRST, RM.NO, RM.F and RT.DG
must be properly set. See Table 11. The outdoor air reset exam-
ple provides 0° F (0° C) reset to the active set point at 85 F
(29.4 C) outdoor-air temperature and 6 F (3.3 C) reset at 55 F
(12.8 C) outdoor-air temperature. See Fig 31. The space tem-
perature reset example provides 0° F (0° C) reset to the active
set point at 72 F (22.2 C) space temperature and 6 F (3.3 C) re-
set at 68 F (20.0 C) space temperature. See Fig 32. The variable
CRST should be configured for the type of reset desired. The
variable RM.NO should be set to the temperature that no reset
should occur. The variable RM.F should be set to the tempera-
ture that maximum reset is to occur. The variable RM.DG
should be set to the maximum amount of reset desired.
CHILLED SET POINT
RESET SET POINT
65
66 67 68 69 70 71
SPACE TEMPERATURE (F)
72
73 74
18.3 18.9 19.4 20.0 20.6 21.1 21.7 22.2 22.8 23.3
SPACE TEMPERATURE (C)
LEGEND
SAT — Supply Air Temperature
Fig. 32 — Space Temperature Reset
To use Return reset, four variables must be configured. In
the Configuration mode under the sub-mode RSET, items
CRST, RT.NO, RT.F and RT.DG must be properly set. See
Table 12.
This example provides 5 F (2.8 C) active set point reset at
2 F (1.1 C) T and 0° F (0° C) reset at 10 F (5.6 C) T. The
variable RT.NO should be set to the air temperature difference
(T) where no reset should occur. The variable RT.F should
29
Table 10 — 4 to 20 mA Reset
KEYPAD
ENTRY
ITEM
DISPLAY
SUB-MODE
RSET
ITEM
COMMENT
EXPANSION
0 = no reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temp
3 = Return Fluid
COOLING RESET
ENTER
CRST
1
TYPE
4 = Space Temperature
5.0 F
Default: 0° F (0° C) Reset at 20 mA
Range: –30 to 30 F (–16.7 to 16.7 C)
MA.DG
4-20 mA DEGREES RESET
(2.8 C)
NOTE: The example above shows how to configure the unit for 4 to
20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F reset
will occur at 20.0 mA. An energy management module is required.
Table 11 — Configuring Outdoor Air and Space Temperature Reset
DISPLAY
MODE
(RED LED)
KEYPAD
ENTRY
SUB-
MODE
KEYPAD
ENTRY
ITEM
EXPANSION
ITEM
COMMENT
Outdoor
Space
Air
ENTER
DISP
UNIT
OPT1
OPT2
M.MST
2 = Outdoor-Air Temperature
4 = Space Temperature
(Connect to LTV-21,22)
ENTER
COOLING RESET
TYPE
CONFIGURATION
RSET
CRST
RM.NO*
RM.F
2
4
Default: 125.0 F (51.7 C)
Range: 0° to125 F
(-17.7 to 51.7 C)
REMOTE - NO
RESET TEMP
85 °F
55 °F
15 °F
72 °F
68 °F
6 °F
Default: 0.0° F (-17.7 C)
Range: 0° to 125 F
(-17.7 to 51.7 C)
REMOTE - FULL
RESET TEMP
Default: 0° F (0° C)
Range: –30 to 30 F
(–34.4 to -1.1 °C)
REMOTE - DEGREES
RESET
RM.DG
*1 item skipped in this example.
Table 12 — Configuring Return Temperature Reset
MODE
(RED LED)
KEYPAD
ENTRY
KEYPAD
ENTRY
ITEM
EXPANSION
SUB-MODE
DISP
ITEM DISPLAY
COMMENT
ENTER
UNIT
CNN
OPT1
OPT2
M.MST
CONFIGURATION
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
2 = Outdoor-Air Temperature
3 = Return Air Temperature
4 = Space Temperature
COOLING
RESET TYPE
ENTER
RSET
CRST*
3
RETURN - NO
RESET TEMP
Default: 10° F (5.6° C)
RT.NO*
RT.F
10° F
0° F
5° F
Range: 0° to 30 F T (-17.7 to 16.7 C)
RETURN - FULL
RESET TEMP
Default: 0° F (–17.8° C)
Range: 0° to 10 F T (-17.7 to –12.2 C)
RETURN - DEGREES Default: 0° F (0° C)
RESET Range: –30 to 30°F (–16.7 to 16.7 C)
RT.DG
*4 items skipped in this example.
30
from exceeding the capacity entered as Demand Limit Switch
2 set point. The demand limit stage that is set to the lowest
demand takes priority if both demand limit inputs are closed. If
the demand limit percentage does not match unit staging, the
unit will limit capacity to the closest capacity stage.
To disable demand limit, configure the DMDC to 0. See
Table 13.
EXTERNALLY POWERED DEMAND LIMIT (4 to
20 mA Controlled) — To configure Demand Limit for 4 to
20 mA control, set the Demand Limit Select (Configura-
tionRSETDMDC) to 2. Then configure the Demand
Limit at 20 mA (ConfigurationRSETDM20) to the
maximum loadshed value desired. Connect the output from an
externally powered 4 to 20 mA signal to terminal block LVT
strip terminals 7 and 8. Refer to the unit wiring diagram for
these connections to the optional/accessory energy manage-
ment module and terminal block. The control will reduce al-
lowable capacity to this level for the 20 mA signal. See Table
13 and Fig. 33.
Demand Limit — Demand Limit is a feature that allows
the unit capacity to be limited during periods of peak energy
usage. There are 3 types of demand limiting that can be
configured. The first type is through 2-stage switch control,
which will reduce the maximum capacity to 2 user-configu-
rable percentages. The second type is by 4 to 20 mA signal in-
put which will reduce the maximum capacity linearly between
100% at a 4 mA input signal (no reduction) down to the user-
configurable level at a 20 mA input signal. The third type uses
the CCN loadshed module and has the ability to limit the cur-
rent operating capacity to maximum and further reduce the ca-
pacity if required.
NOTE: The 2-stage switch control and 4 to 20 mA input signal
types of demand limiting require the energy management
module (EMM).
To use Demand Limit, select the type of demand limiting to
use. Then configure the Demand Limit set points based on the
type selected.
DEMAND LIMIT (2-Stage Switch Controlled) — To con-
figure Demand Limit for 2-stage switch control, set the Demand
Limit Select (ConfigurationRSETDMDC) to 1. Then
CAUTION
configure the
2
Demand Limit Switch points
Care should be taken when interfacing with other manufac-
turer’s control systems, due to possible power supply dif-
ferences, full wave bridge versus half wave rectification.
The two different power supplies cannot be mixed. Com-
fortLink™ controls use half wave rectification. A signal
isolation device should be utilized if a full wave bridge
signal generating device is used. Failure to comply could
result in possible equipment damage.
(ConfigurationRSETDLS1 and DLS2) to the desired ca-
pacity limit. See Table 13. Capacity steps are controlled by 2 re-
lay switch inputs field wired to low voltage terminal (LVT) strip
terminal 3-6. Refer to the unit wiring diagram for these connec-
tions.
For Demand Limit by 2-stage switch control, closing the
first stage demand limit contact will put the unit on the first de-
mand limit level. The unit will not exceed the percentage of ca-
pacity entered as Demand Limit Switch 1 set point. Closing
contacts on the second demand limit switch prevents the unit
Table 13 — Configuring Demand Limit
KEYPAD
ENTRY
KEYPAD
ENTRY
MODE
SUB-MODE
DISP
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
CONFIGURATION
ENTER
UNIT
CCN
OPT1
OPT2
M.MST
RSET
ENTER
CRST
X
X
Cooling Reset Type
Demand Limit Select
Default: 0
0 = None
DMDC*
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
DM20
SHNM
SHDL
SHTM
DLS1
DLS2
XXX %
XXX
Demand Limit at 20 mA
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Switch 1
Demand Limit Switch 2
Range: 0 to 100
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
XXX%
XXX MIN
XXX %
XXX %
Default: 60 min.
Range: 0 to 120 min.
Default: 80%
Range: 0 to 100%
Default: 50%
Range: 0 to 100%
*Seven items skipped in this example.
31
100
50% CAPACITY AT 20 mA
80
60
DM20 = 50
100% CAPACITY AT 4mA
40
20
0
75% CAPACITY AT 12 mA
50% CAPACITY AT 12 mA
DM20 = 0
20
0
2
6
8
12
16
18
4
10
14
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT
Fig. 33 — 4 to 20 mA Demand Limiting — Demand Limit Select (DMDC = 2)
DEMAND LIMIT (CCN Loadshed Controlled) — To con-
figure Demand Limit for CCN Loadshed control, set the De-
mand Limit Select (ConfigurationRSETDMDC) to 3.
Then configure the Loadshed Group Number (Configura-
tionRSETSHNM), Loadshed Demand Delta (Configu-
rationRSETSHDL), and Maximum Loadshed Time
(ConfigurationRSETSHTM). See Table 13.
The Loadshed Group number is established by the CCN
system designer. The ComfortLink controls will respond to a
Redline command from the Loadshed control. When the Red-
line command is received, the current stage of capacity is set to
the maximum stages available. Should the loadshed control
send a Loadshed command, the ComfortLink controls will re-
duce the current stages by the value entered for Loadshed De-
mand delta. The maximum loadshed time is the maximum
length of time that a loadshed condition is allowed to exist. The
control will disable the Redline/Loadshed command if no Can-
cel command has been received within the configured maxi-
mum loadshed time limit.
compressor is always installed in the A1 compressor location.
When a digital compressor is installed, a digital unloader sole-
noid (DUS) is used on the digital compressor.
DIGITAL SCROLL OPERATION — A digital scroll oper-
ates in two stages - the "loaded state" when the solenoid valve
is normally closed and the "unloaded state" when the solenoid
valve is open. During the loaded state, the compressor operates
like a standard scroll and delivers full capacity and mass flow.
However, during the unloaded state, there is no capacity
and no mass flow through the compressor. The capacity of the
system is varied by varying the time the compressor operates
in an unloaded and loaded state during a 15-second period. If
the DUS is energized for 7.5 seconds, the compressor will be
operating at 50% capacity. If the DUS is energized for 11 sec-
onds, the compressor will be operating at approximately 25%
of its capacity. Capacity is the time averaged summation of
loaded and unloaded states, and its range is continuous from
10% to 100%. Regardless of capacity, the compressor always
rotates with constant speed. As the compressor transitions from
a loaded to unloaded state, the discharge and suction pressures
will fluctuate and the compressor sound will change.
The ComfortLink controller controls and integrates the op-
eration of the DUS into the compressor staging routine to
maintain temperature control. When a digital compressor is in-
stalled, an additional discharge gas thermistor (DTT) is in-
stalled along with the AUX board for control of the DUS.
DIGITAL COMPRESSOR CONFIGURATION — When a
digital compressor is installed, the configuration parameter
ConfigurationUnitA1.TY is configured to YES. There is
also a maximum unload time configuration, Configuration
UnitMAX.T, that is set to 7 seconds, which indicates the
maximum unloading for the digital compressor is 50%. This is
done to optimize efficiency of the system.
Cooling Set Point (4 to 20 mA) — A field supplied
and generated, externally powered 4 to 20 mA signal can be
used to provide the leaving temperature set point. The energy
management module (EMM) must be used for cooling set
point control using a 4 to 20 mA signal. To use the 4 to 20 mA
set point, the unit type must be configured for control type VAV
set point (ConfigurationOPT2C.TYP = 9). Once config-
ured, the control will translate the input linearly with 4 mA
equal to 40 F set point and 20 mA equal to 80 F set point. Con-
nect the signal to LVT strip terminal 10,8 (+,-). See Table 14
for instructions to enable the function. Figure 34 shows how
the 4 to 20 mA signal is linearly calculated.
Digital Scroll Option — The 38AP units have
a
factory-installed option for a digital scroll compressor which
provides additional stages of unloading for the unit. The digital
Table 14 — Configuration VAV 4 to 20 mA Set Point
MODE
KEYPAD
ENTRY
KEYPAD
ENTRY
SUB-MODE
DISP
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
(RED LED)
CONFIGURATION
ENTER
UNIT
CCN
OPT1
ENTER
ENTER
OPT2
C.TYP
C.TYP
4
9
Unit Options 2 Controls
Machine Control Type
1 = VAV
3 = Tstat Multi
4 = Tstat 2 Stage
5 = SPT Multi
7 = PCT CAP
8 = Dual Stat
9 = VAV Set Point
32
(C) (F)
32.2 90
26.7 80
21.1 70
15.6 60
10.0 50
4.4 40
-1.1 30
-6.7 20
-12.2 10
-17.8
0
0
5
10
15
20
SETPOINT SIGNAL – 4-20 mA INPUT
Fig. 34 — 4 to 20 mA Supply Set Point
With the unit in deep vacuum (500 microns or less), isolate
the vacuum pump from the system. Observe the rate-of-rise of
the vacuum in the system. If the vacuum rises by more than
50 microns in a 30-minute time period, then continue the dehy-
dration process. Maintain a vacuum on the system until the
standing vacuum requirement is met. This will ensure a dry
system.
PRE-START-UP
IMPORTANT: Before beginning Pre-Start-Up or Start-Up,
review Start-Up Checklist at the back of this publication.
The checklist assures proper start-up of a unit and provides
a record of unit condition, application requirements, system
information, and operation at initial start-up.
By following these evacuation and dehydration procedures,
the amount of moisture present in the system will be mini-
mized. It is required that liquid line filter driers be installed
between the condenser(s) and the expansion devices to capture
any foreign debris and provide additional moisture removal
capacity.
Do not attempt to start the air-conditioning system until the
following checks have been completed.
System Check
1. Check all system components, including the air-handling
equipment. Consult manufacturer's instructions. If the
unit has field-installed accessories, be sure all are proper-
ly installed and wired correctly. Refer to unit wiring
diagrams.
2. Open liquid line and suction line service valves.
3. Check tightness of all electrical connections.
4. Oil should be visible in the compressor sight glasses. An
acceptable oil level in the compressor is from 1/8 to 3/8 of
sight glass. Adjust the oil level as required. No oil should
be removed unless the crankcase heater has been ener-
gized for at least 24 hours. See Add Oil section on
page 47, for Carrier-approved oils.
5. Electrical power source must agree with unit nameplate.
6. Crankcase heaters must be firmly attached to compres-
sors, and must be on for 24 hours prior to start-up.
7. Fan motors are 3-phase. Check rotation of fans during
first start-up check.
START-UP
IMPORTANT: Before beginning Pre-Start-Up or Start-Up,
review Start-Up Checklist at the back of this publication.
The checklist assures proper start-up of a unit and provides
a record of unit condition, application requirements, system
information, and operation at initial start-up.
CAUTION
Crankcase heaters on all units are wired into the control cir-
cuit, so they are always operable as long as the main power
supply disconnect is on (closed), even if any safety device
is open. Compressor heaters must be on for 24 hours prior
to the start-up of any compressor. Equipment damage
could result if heaters are not energized for at least 24 hours
prior to compressor start-up.
EVACUATION AND DEHYDRATION — Because the
38AP systems use polyolester (POE) oil, which can absorb
moisture, it is important to minimize the amount of time that
the system interior is left exposed to the atmosphere. Minimiz-
ing the exposure time of the oil to the atmosphere will mini-
mize the amount of moisture that needs to be removed during
evacuation.
Once all of the piping connections are complete, leak test
the unit and then pull a deep dehydration vacuum. Connect the
vacuum pump to the charging valve in the suction line and to
the liquid line service valve. For best results, it is recommended
that a vacuum of at least 500 microns (0.5 mm Hg) be ob-
tained. Afterwards, to ensure that no moisture is present in the
system, perform a standing vacuum-rise test.
Compressor crankcase heaters must be on for 24 hours be-
fore start-up. To energize the crankcase heaters, close the field
disconnect and turn on the fan circuit breakers. Leave the com-
pressor circuit breakers off/open. The crankcase heaters are
now energized.
Preliminary Charge — Refer to GTAC II (General
Training Air Conditioning), Module 5, Charging, Recovery,
Recycling, and Reclamation for charging procedures. Using
the liquid charging method and charging by weight procedure,
charge each circuit with the amount of Puron® refrigerant
(R-410A) listed in Table 15.
33
Table 15 — Preliminary Puron Refrigerant (R-410A)
Charge, lb (kg)
CAUTION
38AP UNIT SIZE
38APS025
38APD025
38APS027
38APD027
38APS030
38APD030
38APS040
38APD040
38APS050
38APD050
38APD060
38APD070
38APD080
38APD090
38APD100
CIRCUIT A
24 (10.9)
12 (5.6)
CIRCUIT B
—
Charging procedures for MCHX (microchannel heat
exchanger) units require very accurate measurement tech-
niques. Charge should be added in small increments. Using
cooling charging charts provided, add or remove refriger-
ant until conditions of the chart are met. As conditions get
close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on
and all compressors are running when using charging
charts. Failure to comply may result in equipment damage.
12 (5.6)
—
26 (11.6)
13 (6.0)
13 (6.0)
—
29 (12.9)
14 (6.5)
14 (6.5)
—
39 (17.7)
21 (9.5)
17 (7.8)
—
48 (21.5)
22 (9.9)
26 (11.6)
29 (12.9)
33 (15.1)
46 (20.7)
46 (20.7)
46 (20.7)
Due to the compact design of microchannel heat exchang-
ers, refrigerant charge is reduced significantly. As a result,
charging procedures for MCHX units require very accurate
measurement techniques. Charge should be added in small
increments. Using cooling charging charts provided, add or
remove refrigerant until conditions of the chart are met. As
conditions get close to the point on the chart, add or remove
charge in 1/4 lb increments until complete. Ensure that all fans
are on and all compressors are running when using charging
charts. If charging at low outdoor ambient, the condenser coil
can be partially blocked in order to increase head pressure.
With all fans operating and all compressors on the circuit
being serviced operating at full capacity, adjust the refrigerant
charge in accordance with the unit charging charts in Fig. 35-
56. Charge vapor into compressor low-side service port located
on the suction service valve. Measure pressure at the liquid line
service valve, making sure a Schrader depressor is used. Also,
measure liquid line temperature as close to the liquid service
valve as possible. Add charge until the pressure and tempera-
ture conditions of the charging chart curve are met. If liquid
pressure and temperature point fall above curve, add charge. If
liquid pressure and temperature point fall below curve, reduce
the charge until the conditions match the curve.
27 (12.1)
29 (12.9)
29 (12.9)
39 (17.7)
46 (20.7)
NOTES:
1. Preliminary charge is based on 25 ft (7.6 m) of interconnecting liquid line
piping between indoor and outdoor units.
2. For liquid line piping longer than 25 ft (7.6 m), use the following
information:
1/2 in. (12.7 mm) liquid line — 0.6 lb per 10 linear ft (0.27 kg per 3 m)
5/8 in. (15.9 mm) liquid line — 1.0 lb per 10 linear ft (0.45 kg per 3 m)
7/8 in. (22.2 mm) liquid line — 2.0 lb per 10 linear ft (0.91 kg per 3 m)
11/8 in. (28.6 mm) liquid line — 3.5 lb per 10 linear ft (1.59 kg per 3 m)
Adjust Refrigerant Charge
CAUTION
Never charge liquid into the low pressure side of system.
Do not overcharge. During charging or removal of refriger-
ation, be sure indoor fan system is operating. Failure
to comply could result in personal injury or equipment
damage.
If the sight glass is cloudy, check refrigerant charge again.
See Fig. 57 and 58. Ensure all fans and compressors on the cir-
cuit being serviced are operating. Also ensure maximum allow-
able liquid lift has not been exceeded. If the sight glass is
cloudy, a restriction could exist in the liquid line. Check for a
plugged filter drier or partially open solenoid valve. Replace or
repair, as needed.
34
Circuit A or B
130
120
110
100
90
50 SST
40 SST
50
30 SST
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7169
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 35 — Charging Chart — 38APD025, 50/60 Hz
Single Circuit
130
50 SST
40 SST
120
110
100
90
50
30 SST
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7170
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
Saturated Suction Temperature
4000
2000
2500
3000
3500
LEGEND
SST
—
LIQUID PRESSURE AT LIQUID VALVE (kPag)
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 36 — Charging Chart — 38APS025, 50/60 Hz
35
Circuit A or B
130
120
110
100
90
50 SST
40 SST
50
30 SST
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7171
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 37 — Charging Chart — 38APD027, 50/60 Hz
Single Circuit
130
50 SST
40 SST
120
110
100
90
50
30 SST
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7172
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
SST
—
LIQUID PRESSURE AT LIQUID VALVE (kPag)
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 38 — Charging Chart — 38APS027, 50/60 Hz
36
Circuit A or B
130
120
110
100
90
50 SST
40 SST
30 SST
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
a38-7173
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 39 — Charging Chart — 38APD030, 50/60 Hz
Single Circuit
130
50 SST
40 SST
30 SST
120
110
100
90
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7174
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 40 — Charging Chart — 38APS030, 50/60 Hz
37
Circuit A
130
120
110
100
90
50 SST
40 SST
30 SST
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
a38-7175
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 41 — Charging Chart — 38APD040 — Circuit A, 50/60 Hz
Circuit B
130
50 SST
40 SST
30 SST
50
120
110
100
90
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
a38-7176
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 42 — Charging Chart — 38APD040 — Circuit B, 50/60 Hz
38
Single Circuit
130.0
120.0
110.0
100.0
90.0
50 SST
40 SST
30 SST
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80.0
70.0
a38-7177
60.0
200.0
250.0
300.0
350.0
400.0
450.0
500.0
550.0
600.0
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
LEGEND
Saturated Suction Temperature
2000
2500
3000
3500
SST
—
LIQUID PRESSURE AT LIQUID VALVE (kPag)
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 43 — Charging Chart — 38APS040, 50/60 Hz
Circuit A
130
50 SST
40 SST
30 SST
50
120
110
100
90
ADD CHARGE IF ABOVE CURVE
40
30
20
80
REDUCE CHARGE IF BELOW CURVE
70
60
200
250
300
350
400
450
500
550
600
a38-7178
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
LEGEND
Saturated Suction Temperature
1500
4000
2000
2500
3000
3500
SST
—
LIQUID PRESSURE AT LIQUID VALVE (kPag)
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 44 — Charging Chart — 38APD050 — Circuit A, 50/60 Hz
39
Circuit B
130
120
110
100
90
50 SST
40 SST
30 SST
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
a38-7179
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
SST
—
LIQUID PRESSURE AT LIQUID VALVE (kPag)
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 45 — Charging Chart — 38APD050 — Circuit B, 50/60 Hz
Single Circuit
130
50 SST
40 SST
30 SST
50
120
110
100
90
ADD CHARGE IF ABOVE CURVE
40
30
20
80
REDUCE CHARGE IF BELOW CURVE
70
60
200
250
300
350
400
450
500
550
600
a38-7180
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 46 — Charging Chart — 38APS050, 50/60 Hz
40
Circuit A
130.0
120.0
110.0
100.0
90.0
50 SST
40 SST
30 SST
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80.0
70.0
60.0
200.0
250.0
300.0
350.0
400.0
450.0
500.0
550.0
600.0
a38-7181
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
LEGEND
Saturated Suction Temperature
2000
2500
3000
3500
SST
—
LIQUID PRESSURE AT LIQUID VALVE (kPag)
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 47 — Charging Chart — 38APD060 — Circuit A, 50/60 Hz
Circuit B
130.0
50 SST
40 SST
50
120.0
110.0
100.0
90.0
30 SST
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80.0
70.0
60.0
200.0
250.0
300.0
350.0
400.0
450.0
500.0
550.0
600.0
a38-7182
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
LEGEND
Saturated Suction Temperature
1500
4000
2000
2500
3000
3500
SST
—
LIQUID PRESSURE AT LIQUID VALVE (kPag)
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 48 — Charging Chart — 38APD060 — Circuit B, 50/60 Hz
41
Circuit A
130
120
110
100
90
50 SST
40 SST
50
30 SST
ADD CHARGE IF ABOVE CURVE
40
30
20
80
REDUCE CHARGE IF BELOW CURVE
70
60
200
250
300
350
400
450
500
550
600
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
a38-7183
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 49 — Charging Chart — 38APD070 — Circuit A, 50/60 Hz
Circuit B
130
50 SST
40 SST
50
120
110
100
90
30 SST
ADD CHARGE IF ABOVE CURVE
40
30
20
80
REDUCE CHARGE IF BELOW CURVE
70
60
200
250
300
350
400
450
500
550
600
a38-7184
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
Saturated Suction Temperature
4000
2000
2500
3000
3500
LEGEND
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 50 — Charging Chart — 38APD070 — Circuit B, 50/60 Hz
42
Circuit A
130
120
110
100
90
50 SST
40 SST
30 SST
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7185
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 51 — Charging Chart — 38APD080 — Circuit A, 50/60 Hz
Circuit B
130
50 SST
40 SST
30 SST
50
120
110
100
90
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7186
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 52 — Charging Chart — 38APD080 — Circuit B, 50/60 Hz
43
Circuit A
130
120
110
100
90
50 SST
40 SST
30 SST
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
a38-7187
1500
4000
2000
2500
3000
3500
LEGEND
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
Saturated Suction Temperature
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 53 — Charging Chart — 38APD090 — Circuit A, 50/60 Hz
Circuit B
130
50 SST
40 SST
30 SST
50
120
110
100
90
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7188
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 54 — Charging Chart — 38APD090 — Circuit B, 50/60 Hz
44
Circuit A
130
120
110
100
90
50 SST
40 SST
30 SST
50
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
a38-7189
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 55 — Charging Chart — 38APD100 — Circuit A, 50/60 Hz
Circuit B
130
50 SST
40 SST
30 SST
50
120
110
100
90
ADD CHARGE IF ABOVE CURVE
40
30
20
REDUCE CHARGE IF BELOW CURVE
80
70
60
200
250
300
350
400
450
500
550
600
a38-7190
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1500
4000
2000
2500
3000
3500
LEGEND
Saturated Suction Temperature
LIQUID PRESSURE AT LIQUID VALVE (kPag)
SST
—
NOTE: Charging procedures for MCHX units require very accurate measurement techniques. Charge should be added in small increments. Using cooling
charging charts provided, add or remove refrigerant until conditions of the chart are met. As conditions get close to the point on the chart, add or remove charge in
1/4 lb increments until complete. Ensure that all fans are on and all compressors are running when using charging charts.
Fig. 56 — Charging Chart — 38APD100 — Circuit B, 50/60 Hz
45
a38-7117
†
†
LEGEND
LLS — Liquid Line Solenoid
TXV — Thermostatic Expansion Valve
*Field-supplied.
†Field-supplied when required. Must be controlled by 38AP unit control.
Fig. 57 — Required Location of Solenoid Valves and Recommended Filter Drier and
Sight Glass Locations for 38APD025-100 Dual-Circuit Units
a38-7118
SECTION 1
LIQUID
LINE
SECTION 2
SOLENOID VALVE†
SECTION 1
LIQUID
LINE
SECTION 2
SOLENOID VALVE†
*Field-supplied.
†Field-supplied when required. Must be controlled by 38AP unit control.
Fig. 58 — Required Location of Solenoid Valves and Recommended Filter Drier and
Sight Glass Locations for 38APS025-050 Single-Circuit Units
46
SUCTION
SCHRADER B
RGT B SPT B
Check Compressor Oil Level — After adjusting the
refrigerant charge, allow each circuit to run fully loaded for
20 minutes. Stop the compressors and check the oil level. Oil
level should be 1/8 to 3/8 up on the sight glass.
SPT A
RGT A
SUCTION
SCHRADER A
IMPORTANT: Oil level should only be checked when the
compressors are off.
Add oil only if necessary to bring the oil into view in the
sight glass. If oil is added, run the circuit for an additional
10 minutes, then stop and check oil level. If the level remains
low, check the piping system for proper design for oil return;
also, check the system for leaks. If checking the oil level with
unit running in part load, let unit run one hour, then run at full
load for 10 minutes. If oil does not return to acceptable sight
glass levels, check for correct suction piping and line sizing.
HPS A
DPT A
HPS B
DPT B
DTT A
Final Checks — Ensure all safety controls are operating,
control panel covers are on, and the service panels are in place.
Oil Charge
CAUTION
OIL SIGHT
GLASS
LEGEND
The compressor in a Puron® refigerant (R-410A) system
uses a polyol ester (POE) oil. This is extremely hygro-
scopic, meaning it absorbs water readily. POE oils can
absorb 15 times as much water as other oils designed for
HCFC and CFC refrigerants. Take all necessary precau-
tions to avoid exposure of the oil to the atmosphere. Failure
to do so could result in possible equipment damage.
DPT
DTT
HPS
RGT
SPT
—
—
—
—
—
Discharge Pressure Transducer
Discharge Temperature Thermistor
High Pressure Switch
Return Gas Temperature Sensor
Space Temperature Sensor
Fig. 59 — Typical Tandem Compressor Assembly
RGT A
SPT A
Puron systems use a polyol ester (POE) oil. Use only Carri-
er approved compressor oil. Oil should be visible in compres-
sor oil sight glass. An acceptable oil level is from 1/8 to 3/8 of
sight glass. All compressors must be off when checking oil lev-
el. Recommended oil level adjustment method is as follows:
SUCTION
SCHRADER A
ADD OIL — Recover charge from the outdoor section of the
unit and isolate the condensing unit using the liquid and suction
service valves. Add oil to suction line Schrader valve on tan-
dem compressors sets and the compressor Schrader on the trio
and single compressor circuits. (See Fig. 59 and 60.) When oil
can be seen at the bottom of the sight glass, add oil in 5 oz in-
crements which is approximately 1/8 in oil level. Run all com-
pressors for 20 minutes then shut off to check oil level. Repeat
procedure until acceptable oil level is present.
HPS A
DPT A
DTT A
OIL ADD
LOCATION
NOTE: Use only Carrier approved compressor oil. Approved
sources are:
Totaline . . . . . . . . . . . . . . . . . . . . . . .3MAF POE P903-1601
Mobil. . . . . . . . . . . . . . . . . . . . . . . . . . .EAL Arctic 32-3MA
Uniqema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RL32-3MAF
OIL SIGHT
GLASS
Do not reuse oil that has been drained out, or oil that has
been exposed to atmosphere.
Actual Start-Up
NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-5.
Actual start-up should be done only under supervision of a
qualified refrigeration mechanic.
LEGEND
DPT
DTT
HPS
RGT
SPT
—
—
—
—
—
Discharge Pressure Transducer
Discharge Temperature Thermistor
High Pressure Switch
Return Gas Temperature Sensor
Space Temperature Sensor
VAV APPLICATIONS — C.TYP = 1 and 9
1. Start indoor fan motor.
Fig. 60 — Typical Trio Compressor Assembly
2. Fan status switch input should close. Note the unit will
not start unless the Fan Status input is closed.
3. Unit C.TYP = 1: Using the scrolling marquee display,
set leaving set point (Set PointCOOLCSP.1). Unit
C.TYP = 9: Using the 4 to 20mA input, set the control
point (Run StatusVIEWCTPT) for leaving set
point.
4. Turn ENABLE/OFF/REMOTE CONTACT switch to
ENABLE position.
5. If supply air temperature is greater than the control point
the unit will start to stage up.
CV APPLICATION — C.TYP = 4
1. Start indoor fan motor.
47
2. Fan status switch input should close. Note the unit will
not start unless the fan status input is closed.
3. Close Y1 input unit will stage up to 50 % capacity with
1 minute between stages.
4. Close Y2 input the unit will stage up to 100% capacity
with 1 minute between stages.
CV APPLICATION — C.TYP = 3
The maximum voltage deviation is the largest difference
between a voltage measurement across 2 legs and the average
across all 3 legs.
Example: Supply voltage is 240-3-60.
AB = 243 v
BC = 236 v
AC = 238 v
1. Start indoor fan motor.
2. Fan status switch input should close. Note the unit will
not start unless the fan status input is closed.
1. Determine average voltage:
3. Close Y1 input unit. The control will control supply-air
243 + 236 + 238
Averagevoltage =
3
temperature to CSP1 and stage capacity as required.
4. Close Y2 input. The unit will control supply-air tempera-
717
ture to CSP2 and stage capacity as required.
=
3
CV APPLICATION — C.TYP = 5
= 239
1. Start indoor fan motor.
2. Determine maximum deviation from average voltage:
2. Fan status switch input should close. Note the unit will
not start unless the fan status input is closed.
3. The control will use space temperature (Temperatures
SPT) vs space temperature set point (Set Point
COOLSPS.P) to decide to whether to control supply-
air temperature to CSP1 or CSP2, and will stage capacity
as required.
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v.
3. Determine percent voltage imbalance:
4
% Voltage Imbalance = 100 x
239
% CAPACITY INPUT — C.TYP = 7
1. Start indoor fan motor.
2. Fan status switch input should close. Note the unit will
not start unless the fan status input is closed.
= 1.7%
This voltage imbalance is satisfactory as it is below the
maximum allowable of 2%.
3. The control will adjust unit capacity based on the 4 to
20mA Cool mA (INPUTS4-20CL.MA).
4. Actual capacity and desired capacity may be different due
to unit diagnostics.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately. Do not operate unit until imbalance condition
is corrected.
OPERATION
Operating Limitations
AMBIENT LMITATIONS — See Table 16 for ambient
limitations.
Control Circuit Power — Power for the control circuit is
supplied from the main incoming power through a factory-
installed control power transformer (TRAN1) for all models.
Field wiring connections are made to LVT terminal board.
Table 16 — 38AP Unit Ambient Limitations
Single Circuit
Operation Sequence — During unit off cycle, if power
is maintained to the unit and the EMERGENCY ON/OFF
switch is left in the OFF position, the compressor crankcase
heaters will be energized.
38APS
UNIT
SIZE
MINIMUM LOW
AMBIENT
(Standard Unit)
MINIMUM LOW AMBIENT
MOTORMASTER®
CONTROL*
MAXIMUM
AMBIENT†
The unit is started by putting the ENABLE/OFF/REMOTE
CONTACT switch in the ENABLE or REMOTE CONTACT
position. When the unit receives a call to run (either from the
internal control, or CCN network command or remote contact
closure), the unit stages up in capacity to maintain either supply
air temperature or space temperature. The first compressor
starts 11/2 to 3 minutes after the call for cooling.
The lead circuit can be specifically designated on all models
or selected based on compressor run hours and starts depend-
ing on field configuration. The unit control will override this
selection under certain starting conditions to properly maintain
oil return to the compressors. The MBB controls fan stages to
maintain the head pressure set point and will automatically ad-
just unit capacity as required to keep compressors from operat-
ing outside of the specified envelope. There are no pumpout or
pumpdown sequences on these units.
025-050
45 F (7.2 C)
–20 F (–28.9 C)
122 F (50 C)
Dual Circuit
38APD
UNIT
SIZE
025-040
050-060
070-100
MINIMUM LOW
AMBIENT
(Standard Unit)
32 F (0 C)
25 F (–3.9 C)
32 F (0 C)
MINIMUM LOW AMBIENT
MOTORMASTER
CONTROL*
MAXIMUM
AMBIENT†
–20 F (–28.9 C)
–20 F (–28.9 C)
–20 F(–28.9 C)
122 F (50 C)
122 F (50 C)
122 F (50 C)
* Factory-installed option or field-installed accessory.
†Operation above listed temperature depends on the saturated suction tem-
perature the unit is operating at. Refer to ECAT for exact limitations.
VOLTAGE (ALL UNITS)
Main Power Supply — Minimum and maximum acceptable
supply voltages are listed in the Installation Instructions.
Unbalanced 3-Phase Supply Voltage — Never operate a motor
where a phase imbalance between phases is greater than 2%.
To determine percent voltage imbalance:
The liquid line solenoid valve is energized anytime a com-
pressor is operating in the circuit and also when the circuit is
OFF and the OAT is less than the SST. The liquid line solenoid
valve is de-energized 5 seconds after the circuit stops and also
when the circuit is OFF and the OAT is greater than the SST
plus 2° F. Each circuit operates independently.
max voltage deviation
from avg voltage
% Voltage Imbalance = 100 x
average voltage
48
For all units, if temperature reset is used, the unit controls to
a higher leaving temperature as the building load reduces. If
demand limit is used, the unit may temporarily be unable to
maintain the desired leaving-air temperature because of im-
posed power limitations. Loading sequence for compressors is
shown in Table 8.
(SPT), supply air temperature (SAT) and return air temperature
(RAT/EAT) thermistors.
SPACE TEMPERATURE THERMISTOR (SPT) — This
sensor is a field-supplied accessory and is part of the T55 or
T56 sensor package that can be used to control space tempera-
ture on constant volume (CV) units. The sensor is connected to
the LVT. The SPT has a 10 k input channel and has a differ-
ent set of temperature vs. resistance and voltage drop perfor-
mance than the 5 k thermistors.
SERVICE
WARNING
SUPPLY AIR THERMISTOR (SAT) — This sensor is field
supplied and is used to measure the supply air temperature of
the unit. The SAT thermistor is configurable to be either a 5 k
or 10 k thermistor. Care should be taken to ensure the config-
uration matches the type of thermistor which is installed. This
is configured under the Configuration menu OPT1, SAT.T and
by selecting 0 for 5 k or 1 for 10 k or 2 for none. The proper
temperature vs. resistance and voltage drop performance tables
should be followed based on the configuration.
ELECTRIC SHOCK HAZARD: Turn off all power to unit
before servicing. The ENABLE/OFF/REMOTE CON-
TACT switch on control panel does not shut off control
power; use field disconnect. Failure to do so could result in
personal injury.
Electronic Components
RETURN AIR OR EVAPORATOR AIR THERMISTOR
(RAT) — This sensor is field supplied and should be located
directly upstream of the evaporator. The RAT is used to mea-
sure the evaporator entering or return air temperature of the
unit. The RAT thermistor is configurable to be either a 5 k
or 10 k thermistor. Care should be taken to ensure the
configuration matches the type of thermistor which is installed.
This is configured under the Configuration menu OPT1,
RAT.T and by selecting 0 for 5 k or 1 for 10 k or 2 for none.
The proper temperature vs. resistance and voltage drop perfor-
mance tables should be followed based on configuration.
CONTROL COMPONENTS — Unit uses an advanced elec-
tronic control system that normally does not require service.
For details on controls refer to Operating Data section.
Access to the compressors is through latched panels from
beneath the control box on the unit sizes 025-060 and on each
end of the unit on sizes 070-100. The front door(s) provide
access to the compressor(s) and all components of the
refrigeration system. For unit sizes 025-030, access to the
controls is through the upper latched outer door above the com-
pressor access door. Similarly, the upper center latched door on
sizes 040-060 gives access to the controls. Inner panels are se-
cured in place and should not be removed unless all power to
the unit is off.
See Table 3 for thermistor pin connection points.
THERMISTOR/TEMPERATURE SENSOR CHECK — A
high quality digital volt-ohmmeter is required to perform this
check.
1. Connect the digital voltmeter across the appropriate the-
mistor terminals at the J8 terminal strip on the main base
board (see Fig. 61).
Thermistors — Electronic control uses up to 7 thermistors
to sense temperatures used to control operation of the unit. The
standard unit comes with return gas temperature (RGT) and
outside air temperature (OAT) thermistors. These thermistors
are 5 k thermistors, identical in their temperature and voltage
drop performance. Resistance at various temperatures is listed
in Tables 17-21.
2. Using the voltage reading obtained, read the sensor tem-
perature from Tables 17-21.
3. To check thermistor accuracy, measure temperature at
probe location with an accurate thermocouple-type tem-
perature measuring instrument. Insulate thermocouple to
avoid ambient temperatures from influencing reading.
Temperature measured by thermocouple and temperature
determined from thermistor voltage reading should be
close, ± 5° F (3° C) if care was taken in applying thermo-
couple and taking readings.
DISCHARGE
TEMPERATURE
THERMISTOR
(DTT) — This sensor is only used on units with a digital
compressor. The sensor is mounted on the discharge line close
to the discharge of the digital compressor. It attaches to the dis-
charge line using a spring clip and protects the system from
high discharge gas temperature when the digital compressor is
used. This sensor is a 86 k thermistor connected to the AUX
board.
If a more accurate check is required, unit must be shut down
and thermistor removed and checked at a known temperature
(freezing point or boiling point of water) using either voltage
drop measured across thermistor at the J8 terminal, by deter-
mining the resistance with unit shut down and thermistor
disconnected from J8. Compare the values determined with the
value read by the control in the Temperatures mode using the
scrolling marquee display.
RETURN GAS THERMISTORS (RGTA,B) — The
RGTA,B thermistors are located in the suction line of the re-
spective circuits and are used to monitor superheat entering the
compressor and generate low superheat alarms.
OUTSIDE AIR THERMISTOR (OAT) — The OAT is lo-
cated inside the base rail on unit sizes 025-060 and on the back
of the control box on sizes 070-100. It is used to control fan cy-
cling on the unit.
REPLACING
RETURN
GAS
THERMISTORS
The remaining thermistors are installed in either the space,
ductwork or air handler. These include the space temperature
(RGTA,B) — Add a small amount of thermal conductive
grease to the thermistor well and end of probe. Tighten the re-
taining nut 1/4 turn past finger tight.
49
Table 17 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
59
60
1.982
1.956
1.930
1.905
1.879
1.854
1.829
1.804
1.779
1.754
1.729
1.705
1.681
1.656
1.632
1.609
1.585
1.562
1.538
1.516
1.493
1.470
1.448
1.426
1.404
1.382
1.361
1.340
1.319
1.298
1.278
1.257
1.237
1.217
1.198
1.179
1.160
1.141
1.122
1.104
1.086
1.068
1.051
1.033
1.016
0.999
0.983
0.966
0.950
0.934
0.918
0.903
0.888
0.873
0.858
0.843
0.829
0.815
0.801
0.787
0.774
0.761
0.748
0.735
0.723
0.710
0.698
0.686
0.674
0.663
0.651
0.640
0.629
0.618
0.608
0.597
0.587
0.577
0.567
0.557
0.548
0.538
0.529
0.520
7,686
7,665
7,468
7,277
7,091
6,911
6,735
6,564
6,399
6,238
6,081
5,929
5,781
5,637
5,497
5,361
5,229
5,101
4,976
4,855
4,737
4,622
4,511
4,403
4,298
4,196
4,096
4,000
3,906
3,814
3,726
3,640
3,556
3,474
3,395
3,318
3,243
3,170
3,099
3,031
2,964
2,898
2,835
2,773
2,713
2,655
2,597
2,542
2,488
2,436
2,385
2,335
2,286
2,239
2,192
2,147
2,103
2,060
2,018
1,977
1,937
1,898
1,860
1,822
1,786
1,750
1,715
1,680
1,647
1,614
1,582
1,550
1,519
1,489
1,459
1,430
1,401
1,373
1,345
1,318
1,291
1,265
1,240
1,214
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
0.511
0.502
0.494
0.485
0.477
0.469
0.461
0.453
0.445
0.438
0.430
0.423
0.416
0.408
0.402
0.395
0.388
0.381
0.375
0.369
0.362
0.356
0.350
0.344
0.339
0.333
0.327
0.322
0.317
0.311
0.306
0.301
0.296
0.291
0.286
0.282
0.277
0.272
0.268
0.264
0.259
0.255
0.251
0.247
0.243
0.239
0.235
0.231
0.228
0.224
0.220
0.217
0.213
0.210
0.206
0.203
0.200
0.197
0.194
0.191
0.188
0.185
0.182
0.179
0.176
0.173
0.171
0.168
0.165
0.163
0.160
0.158
0.155
0.153
0.151
0.148
0.146
0.144
0.142
0.140
0.138
0.135
0.133
1,190
1,165
1,141
1,118
1,095
1,072
1,050
1,029
1,007
986
965
945
925
906
887
868
850
832
815
798
782
765
750
734
719
705
690
677
663
650
638
626
614
602
591
581
570
561
551
542
533
524
516
508
501
494
487
480
473
467
461
456
450
445
439
434
429
424
419
415
410
405
401
396
391
386
382
377
372
367
361
356
350
344
338
332
325
318
311
304
297
289
282
–25
–24
–23
–22
–21
–20
–19
–18
–17
–16
–15
–14
–13
–12
–11
–10
–9
–8
–7
–6
–5
–4
–3
–2
–1
0
3.699
3.689
3.679
3.668
3.658
3.647
3.636
3.624
3.613
3.601
3.588
3.576
3.563
3.550
3.536
3.523
3.509
3.494
3.480
3.465
3.450
3.434
3.418
3.402
3.386
3.369
3.352
3.335
3.317
3.299
3.281
3.262
3.243
3.224
3.205
3.185
3.165
3.145
3.124
3.103
3.082
3.060
3.038
3.016
2.994
2.972
2.949
2.926
2.903
2.879
2.856
2.832
2.808
2.784
2.759
2.735
2.710
2.685
2.660
2.634
2.609
2.583
2.558
2.532
2.506
2.480
2.454
2.428
2.402
2.376
2.349
2.323
2.296
2.270
2.244
2.217
2.191
2.165
2.138
2.112
2.086
2.060
2.034
2.008
98,010
94,707
91,522
88,449
85,486
82,627
79,871
77,212
74,648
72,175
69,790
67,490
65,272
63,133
61,070
59,081
57,162
55,311
53,526
51,804
50,143
48,541
46,996
45,505
44,066
42,679
41,339
40,047
38,800
37,596
36,435
35,313
34,231
33,185
32,176
31,202
30,260
29,351
28,473
27,624
26,804
26,011
25,245
24,505
23,789
23,096
22,427
21,779
21,153
20,547
19,960
19,393
18,843
18,311
17,796
17,297
16,814
16,346
15,892
15,453
15,027
14,614
14,214
13,826
13,449
13,084
12,730
12,387
12,053
11,730
11,416
11,112
10,816
10,529
10,250
9,979
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
1
86
2
87
3
88
4
89
5
90
6
91
7
92
8
93
9
94
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
9,717
9,461
9,213
8,973
8,739
8,511
8,291
8,076
50
Table 18 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
TEMP
(C)
RESISTANCE
(Ohms)
TEMP
(C)
RESISTANCE
(Ohms)
TEMP
(C)
RESISTANCE
(Ohms)
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
1.982
1.935
1.889
1.844
1.799
1.754
1.710
1.666
1.623
1.580
1.538
1.497
1.457
1.417
1.378
1.340
1.302
1.265
1.229
1.194
1.160
1.126
1.093
1.061
1.030
0.999
0.969
0.940
0.912
0.885
0.858
0.832
0.807
0.782
0.758
0.735
0.713
0.691
0.669
0.649
0.629
0.610
0.591
0.573
0.555
0.538
0.522
7,855
7,499
7,161
6,840
6,536
6,246
5,971
5,710
5,461
5,225
5,000
4,786
4,583
4,389
4,204
4,028
3,861
3,701
3,549
3,404
3,266
3,134
3,008
2,888
2,773
2,663
2,559
2,459
2,363
2,272
2,184
2,101
2,021
1,944
1,871
1,801
1,734
1,670
1,609
1,550
1,493
1,439
1,387
1,337
1,290
1,244
1,200
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
0.506
0.490
0.475
0.461
0.447
0.433
0.420
0.407
0.395
0.383
0.371
0.360
0.349
0.339
0.329
0.319
0.309
0.300
0.291
0.283
0.274
0.266
0.258
0.251
0.244
0.237
0.230
0.223
0.217
0.211
0.204
0.199
0.193
0.188
0.182
0.177
0.172
0.168
0.163
0.158
0.154
0.150
0.146
0.142
0.138
0.134
1,158
1,118
1,079
1,041
1,006
971
938
906
876
836
805
775
747
719
693
669
645
623
602
583
564
547
531
516
502
489
477
466
456
446
436
427
419
410
402
393
385
376
367
357
346
335
324
312
299
285
–32
3.705
3.687
3.668
3.649
3.629
3.608
3.586
3.563
3.539
3.514
3.489
3.462
3.434
3.406
3.376
3.345
3.313
3.281
3.247
3.212
3.177
3.140
3.103
3.065
3.025
2.985
2.945
2.903
2.860
2.817
2.774
2.730
2.685
2.639
2.593
2.547
2.500
2.454
2.407
2.360
2.312
2.265
2.217
2.170
2.123
2.076
2.029
100,260
94,165
88,480
83,170
78,125
73,580
69,250
65,205
61,420
57,875
54,555
51,450
48,536
45,807
43,247
40,845
38,592
38,476
34,489
32,621
30,866
29,216
27,633
26,202
24,827
23,532
22,313
21,163
20,079
19,058
18,094
17,184
16,325
15,515
14,749
14,026
13,342
12,696
12,085
11,506
10,959
10,441
9,949
–31
–30
–29
–28
–27
–26
–25
–24
–23
–22
–21
–20
–19
–18
–17
–16
–15
–14
–13
–12
–11
–10
–9
–8
–7
–6
–5
–4
–3
–2
–1
0
1
2
3
4
5
6
7
8
9
10
11
9,485
12
9,044
13
8,627
14
8,231
51
Table 19 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
–25
–24
–23
–22
–21
–20
–19
–18
–17
–16
–15
–14
–13
–12
–11
–10
–9
–8
–7
–6
–5
–4
–3
–2
–1
0
4.758
4.750
4.741
4.733
4.724
4.715
4.705
4.696
4.686
4.676
4.665
4.655
4.644
4.633
4.621
4.609
4.597
4.585
4.572
4.560
4.546
4.533
4.519
4.505
4.490
4.476
4.461
4.445
4.429
4.413
4.397
4.380
4.363
4.346
4.328
4.310
4.292
4.273
4.254
4.235
4.215
4.195
4.174
4.153
4.132
4.111
4.089
4.067
4.044
4.021
3.998
3.975
3.951
3.927
3.903
3.878
3.853
3.828
3.802
3.776
3.750
3.723
3.697
3.670
3.654
3.615
3.587
3.559
3.531
3.503
3.474
3.445
3.416
3.387
3.357
3.328
3.298
3.268
3.238
3.208
3.178
3.147
3.117
3.086
3.056
3.025
196,453
189,692
183,300
177,000
171,079
165,238
159,717
154,344
149,194
144,250
139,443
134,891
130,402
126,183
122,018
118,076
114,236
110,549
107,006
103,558
100,287
97,060
94,020
91,019
88,171
85,396
82,729
80,162
77,662
75,286
72,940
70,727
68,542
66,465
64,439
62,491
60,612
58,781
57,039
55,319
53,693
52,086
50,557
49,065
47,627
46,240
44,888
43,598
42,324
41,118
39,926
38,790
37,681
36,610
35,577
34,569
33,606
32,654
31,752
30,860
30,009
29,177
28,373
27,597
26,838
26,113
25,396
24,715
24,042
23,399
22,770
22,161
21,573
20,998
20,447
19,903
19,386
18,874
18,384
17,904
17,441
16,991
16,552
16,131
15,714
15,317
61
62
2.994
2.963
2.932
2.901
2.870
2.839
2.808
2.777
2.746
2.715
2.684
2.653
2.622
2.592
2.561
2.530
2.500
2.470
2.439
2.409
2.379
2.349
2.319
2.290
2.260
2.231
2.202
2.173
2.144
2.115
2.087
2.059
2.030
2.003
1.975
1.948
1.921
1.894
1.867
1.841
1.815
1.789
1.763
1.738
1.713
1.688
1.663
1.639
1.615
1.591
1.567
1.544
1.521
1.498
1.475
1.453
1.431
1.409
1.387
1.366
1.345
1.324
1.304
1.284
1.264
1.244
1.225
1.206
1.187
1.168
1.150
1.132
1.114
1.096
1.079
1.062
1.045
1.028
1.012
0.996
0.980
0.965
0.949
0.934
0.919
0.905
14,925
14,549
14,180
13,824
13,478
13,139
12,814
12,493
12,187
11,884
11,593
11,308
11,031
10,764
10,501
10,249
10,000
9,762
9,526
9,300
9,078
8,862
8,653
8,448
8,251
8,056
7,869
7,685
7,507
7,333
7,165
6,999
6,838
6,683
6,530
6,383
6,238
6,098
5,961
5,827
5,698
5,571
5,449
5,327
5,210
5,095
4,984
4,876
4,769
4,666
4,564
4,467
4,370
4,277
4,185
4,096
4,008
3,923
3,840
3,759
3,681
3,603
3,529
3,455
3,383
3,313
3,244
3,178
3,112
3,049
2,986
2,926
2,866
2,809
2,752
2,697
2,643
2,590
2,539
2,488
2,439
2,391
2,343
2,297
2,253
2,209
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
0.890
0.876
0.862
0.848
0.835
0.821
0.808
0.795
0.782
0.770
0.758
0.745
0.733
0.722
0.710
0.699
0.687
0.676
0.666
0.655
0.645
0.634
0.624
0.614
0.604
0.595
0.585
0.576
0.567
0.558
0.549
0.540
0.532
0.523
0.515
0.507
0.499
0.491
0.483
0.476
0.468
0.461
0.454
0.447
0.440
0.433
0.426
0.419
0.413
0.407
0.400
0.394
0.388
0.382
0.376
0.370
0.365
0.359
0.354
0.349
0.343
0.338
0.333
0.328
0.323
0.318
0.314
0.309
0.305
0.300
0.296
0.292
0.288
0.284
0.279
0.275
0.272
0.268
0.264
2,166
2,124
2,083
2,043
2,003
1,966
1,928
1,891
1,855
1,820
1,786
1,752
1,719
1,687
1,656
1,625
1,594
1,565
1,536
1,508
1,480
1,453
1,426
1,400
1,375
1,350
1,326
1,302
1,278
1,255
1,233
1,211
1,190
1,169
1,148
1,128
1,108
1,089
1,070
1,052
1,033
1,016
998
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
1
87
2
88
3
89
4
90
5
91
6
92
7
93
8
94
9
95
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
981
964
947
931
915
900
885
870
855
841
827
814
800
787
774
762
749
737
725
714
702
691
680
670
659
649
639
629
620
610
601
592
583
574
566
557
52
Table 20 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
TEMP
(C)
RESISTANCE
(Ohms)
TEMP
(C)
RESISTANCE
(Ohms)
TEMP
(C)
RESISTANCE
(Ohms)
–32
–31
–30
–29
–28
–27
–26
–25
–24
–23
–22
–21
–20
–19
–18
–17
–16
–15
–14
–13
–12
–11
–10
–9
4.762
4.748
4.733
4.716
4.700
4.682
4.663
4.644
4.624
4.602
4.580
4.557
4.533
4.508
4.482
4.455
4.426
4.397
4.367
4.335
4.303
4.269
4.235
4.199
4.162
4.124
4.085
4.044
4.003
3.961
3.917
3.873
3.828
3.781
3.734
3.686
3.637
3.587
3.537
3.485
3.433
3.381
3.328
3.274
3.220
3.165
3.111
200,510
188,340
177,000
166,342
156,404
147,134
138,482
130,402
122,807
115,710
109,075
102,868
97,060
91,588
86,463
81,662
77,162
72,940
68,957
65,219
61,711
58,415
55,319
52,392
49,640
47,052
44,617
42,324
40,153
38,109
36,182
34,367
32,654
31,030
29,498
28,052
26,686
25,396
24,171
23,013
21,918
20,883
19,903
18,972
18,090
17,255
16,464
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
3.056
3.000
2.944
2.889
2.833
2.777
2.721
2.666
2.610
2.555
2.500
2.445
2.391
2.337
2.284
2.231
2.178
2.127
2.075
2.025
1.975
1.926
1.878
1.830
1.784
1.738
1.692
1.648
1.605
1.562
1.521
1.480
1.439
1.400
1.362
1.324
1.288
1.252
1.217
1.183
1.150
1.117
1.086
1.055
1.025
0.996
0.968
15,714
15,000
14,323
13,681
13,071
12,493
11,942
11,418
10,921
10,449
10,000
9,571
9,164
8,776
8,407
8,056
7,720
7,401
7,096
6,806
6,530
6,266
6,014
5,774
5,546
5,327
5,117
4,918
4,727
4,544
4,370
4,203
4,042
3,889
3,743
3,603
3,469
3,340
3,217
3,099
2,986
2,878
2,774
2,675
2,579
2,488
2,400
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
0.940
0.913
0.887
0.862
0.837
0.813
0.790
0.767
0.745
0.724
0.703
0.683
0.663
0.645
0.626
0.608
0.591
0.574
0.558
0.542
0.527
0.512
0.497
0.483
0.470
0.457
0.444
0.431
0.419
0.408
0.396
0.386
0.375
0.365
0.355
0.345
0.336
0.327
0.318
0.310
0.302
0.294
0.287
0.279
0.272
0.265
2,315
2,235
2,157
2,083
2,011
1,943
1,876
1,813
1,752
1,693
1,637
1,582
1,530
1,480
1,431
1,385
1,340
1,297
1,255
1,215
1,177
1,140
1,104
1,070
1,037
1,005
974
–8
–7
–6
–5
944
–4
915
–3
889
–2
861
–1
836
0
811
1
787
2
764
3
742
4
721
5
700
6
680
7
661
8
643
9
626
10
609
11
592
12
576
13
561
14
Table 21 — 86K Thermistor vs Resistance (DTT)
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
-40
-40
-31
-22
-13
-4
2,889,600
2,087,220
1,522,200
1,121,440
834,720
627,280
475,740
363,990
280,820
218,410
171,170
135,140
107,440
86,000
75
80
167
176
185
194
203
212
221
230
239
248
257
266
275
284
293
302
311
320
329
338
347
356
12,730
10,790
9,200
7,870
6,770
5,850
5,090
4,450
3,870
3,350
2,920
2,580
2,280
2,020
1,800
1,590
1,390
1,250
1,120
1,010
920
-35
-30
-25
-20
-15
-10
-5
85
90
95
5
100
105
110
115
120
125
130
135
140
145
150
155
160
165
170
175
180
14
23
0
5
32
41
10
15
20
25
30
35
40
45
50
55
60
70
50
59
68
77
86
69,280
95
56,160
104
113
122
131
140
158
45,810
37,580
30,990
25,680
21,400
15,070
830
53
Pressure Transducers — The suction and discharge
transducers are different part numbers and can be distinguished
by the color of the transducer body, suction (yellow) and dis-
charge (red). Figures 59 and 60 shows typical location of pres-
sure transducers on each circuit. No pressure transducer cali-
bration is required. The transducers operate on a 5 vdc supply,
which is generated by the main base board (MBB). See Fig. 61
for transducer connections to the J8 connector on the MBB.
fan height.eps in
job folder (WIP)
1
RGTA
RED
1
2
2
3
4
5
6
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
BLK
RED
Fig. 62 — Mounted Fan Position
RGTB
3
LVT
T55
4
BLK
BLU
BLU
RED
J12
3
IMPORTANT: Check for proper fan rotation (clockwise
when viewed from above). If necessary, switch any
2 power leads to reverse fan rotation.
5
23
22
T-55
ACCSY
SEN
6
4
OAT
7
SPACE TEMPERATURE
ACCESSORY OR
DUAL CHILLER LWT
LOW SOUND FAN — A shroud and a wire guard provide
protection from the rotating fan. The exposed end of the fan
motor shaft is protected from weather by grease. If fan motor
must be removed for service or replacement, be sure to re-
grease fan shaft and reinstall fan guard. The fan motor has a
step in the motor shaft. For proper performance, fan should be
positioned such that it is securely seated on this step. Tighten
the bolt to 15 ± 1 ft-lb (20 ± 1.3 N·m).
8
BLK
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
EVAPORATOR ENTERING
FLUID TEMP
RED
BLK
RED
EVAPORATOR LEAVING
FLUID TEMP
J8
BLK
RED
B
C
A
B
C
A
+
IMPORTANT: Check for proper fan rotation (counter-
clockwise when viewed from above). If necessary, switch
any 2 power leads to reverse fan rotation.
DPTB
SPTB
DPTA
GRN
BLK
RED
-
transducer.eps
in job folder (WIP)
+
Motormaster® V Controller — The optional or acces-
sory Motormaster V controller uses an input signal from the
AUX board. See Fig. 63. The controller is factory configured
and requires no field programming. If a situation arises where
the drive does not function properly, the information provided
below and in Table 22 can be used to troubleshoot the drive.
GRN
BLK
-
B
C
A
RED
+
8
GRN
BLK
9
-
10
B
C
A
RED
+
11
12
SPTA
GRN
BLK
WARNING
-
LEGEND
Hazard of electrical shock! Wait three minutes after discon-
necting incoming power before servicing drive. Capacitors
retain charge after power is removed. Drive assembly
includes externally mounted current limiting resistors. Use
extreme caution when servicing the drive. Failure to com-
ply could result in possible personal injury.
ACCSY
DPT
LVT
—
—
—
—
—
—
—
—
Accessory
Discharge Pressure Transducer
Low Voltage Terminal
LWT
OAT
Leaving Fluid Temperature
Outdoor Air Temperature Sensor
Return Gas Temperature Sensor
Sensor Terminal Block
RGT
SEN
SPT
Space Temperature Sensor
WARNING
Fig. 61 — Thermistor Connections to
Main Base Board, J8 Connector
When configured as shown below, this equipment is
designed to start when it receives line power. Ensure that
all personnel are clear of fans and guards are installed
before applying power. Failure to comply could result in
possible personal injury.
TROUBLESHOOTING — If a transducer is suspected of be-
ing faulty, first check supply voltage to the transducer. Supply
voltage should be 5 vdc ± 0.2 v. If supply voltage is correct,
compare pressure reading displayed on the scrolling marquee
display module against pressure shown on a calibrated pressure
gauge. Pressure readings should be within ± 15 psig. If the
two readings are not reasonably close, replace the pressure
transducer.
CAUTION
If input power has not been applied to the drive for a period
of time exceeding three years (due to storage, etc.), the
electrolytic DC bus capacitors within the drive can change
internally, resulting in excessive leakage current. This can
result in premature failure of the capacitors if the drive is
operated after such a long period of inactivity or storage. In
order to reform the capacitors and prepare the drive for
operation after a long period of inactivity, apply input
power to the drive for 8 hours prior to actually operating
the motor. Before attempting to operate the drive, motor,
and driven equipment, be sure all procedures pertaining to
installation and wiring have been properly followed. Fail-
ure to comply could result in equipment damage.
Condenser Fans — Each fan is supported by a formed
wire mount bolted to a fan deck and covered with a wire guard.
METAL FANS — The exposed end of fan motor shaft is pro-
tected from weather by grease and a rubber boot. If fan motor
must be removed for service or replacement, be sure to re-
grease fan shaft and reinstall fan guard. For proper perfor-
mance, fan web should be 0.32 in. (8 mm) below top of orifice
on the fan deck to top of the fan hub. (See Fig. 62.) Tighten set
screws to 15 ± 1 ft-lb (20 ± 1.3 N-m). Figure 62 shows the
proper position of mounted fan.
54
5. Press Mode to display present parameter number.
CAUTION
Upper right decimal point blinks.
Use the
and
buttons to scroll to the desired
DO NOT connect incoming AC power to output terminals
T1, T2, and T3! Severe damage to the drive will result. Do
not continuously cycle input power to the drive more than
once every two minutes. Damage to the drive will result.
parameter number.
Once the desired parameter number is found, press the
Mode button to display the present parameter setting. The up-
per right-hand decimal point will begin blinking, indicating
that the present parameter setting is being displayed, and that it
can be changed by using the up and down buttons. Use
GENERAL OPERATION — The speed varies in proportion
to a 4 to 20 mA signal produced by the ComfortLink™ con-
trols. The MMV output speed is displayed in Hz.
and
to change setting. Press Mode to store new setting.
The ComfortLink controls must be configured for MMV
operation in order for it to operate. This is configured under the
Configuration menu M.MASTMMR.S and selecting
“YES”. This configuration menu also contains the gains and
minimum speed for the motormaster control logic.
CONFIGURATION — The MMV is configured for 1 of 12
operation modes based on the inputs to the control terminal
block. The 38AP units use operating modes 5-8. In these con-
figurations, the MMV follows a 4 to 20 mA speed reference
signal present on terminals 25 (+) and 2 (-). One additional
jumper is required to configure the drive for 50/60 Hz opera-
tion and input voltage. See Table 23 for proper inputs. Once the
drive is powered, it will change to the mode selected according
to the inputs. See Fig. 64.
Pressing the Mode will store the new setting and also exit
the PROGRAM mode. To change another parameter, press the
Mode key again to re-enter the PROGRAM mode (the param-
eter menu will be accessed at the parameter that was last
viewed or changed before exiting). If the Mode key is pressed
within two minutes of exiting the PROGRAM mode, the pass-
word is not required to access the parameters. After two min-
utes, the password must be entered in order to access the pa-
rameters again.
To change password: first enter the current password then
change parameter P44 to the desired password.
To disable automatic control mode and enter manual speed
control mode:
1. Change P05 to ‘01- keypad’.
2. Push UP and DOWN arrow key to set manual speed.
DRIVE PROGRAMMING
3. Set P05 to ‘04 - 4-20mA control’ to restore 4 to 20 mA
control.
CAUTION
EPM CHIP — The drive uses a electronic programming mod-
ule (EPM) chip to store the program parameters. This is an
EEPROM memory chip and is accessible from the front of the
VFD. It should not be removed with power applied to the
VFD.
LOSS OF CCN COMMUNICATIONS — Carrier Comfort
Network® (CCN) communications with external control
systems can be affected by high frequency electrical noise gen-
erated by the Motormaster V control. Ensure unit is well
grounded to eliminate ground currents along communication
lines.
If communications are lost only while Motormaster V con-
trol is in operation, order a signal isolator (CEAS420876-2)
and power supplies (CEAS221045-01, 2 required) for the CCN
communication line.
Fault Codes — The drive is programmed to automatically re-
start after a fault and will attempt to restart three times after a
fault (the drive will not restart after CF, cF, GF, F1, F2-F9, or
Fo faults). If all three restart attempts are unsuccessful, the
drive will trip into FAULT LOCKOUT (LC), which requires a
manual reset.
It is strongly recommended that the user NOT change any
programming without consulting Carrier service personnel.
Unit damage may occur from improper programming.
To enter password and change program values:
1. Press Mode.
2. Upper right decimal point blinks.
3. Display reads “00”. To enter the PROGRAM mode to ac-
cess the parameters, press the Mode button. This will ac-
tivate the PASSWORD prompt (if the password has not
been disabled). The display will read “00” and the upper
right-hand decimal point will be blinking. (See Fig. 63.)
4. Use the
and
buttons to scroll to the password
value (the factory default password is “111”) and press
the Mode button. Once the correct password value is
entered, the display will read “P01”, which indicates that
the PROGRAM mode has been accessed at the beginning
of the parameter menu (P01 is the first parameter).
NOTE: If the display flashes “Er”, the password was incorrect,
and the process to enter the password must be repeated.
55
L1
L2
L3
Mode
DANGER
LEGEND
MMV
— Motormaster V Control
MMV
TERMINAL
BLOCK
T1
T3
B+
T2
B-
DISPLAY
BUTTONS
Mode
Fig. 63 — Motormaster® V Mode Buttons and Mode Display
Table 22 — Fault Codes
FAULT CODE
DESCRIPTION
SOLUTION
AF
CF
cF
High Temperature Fault: Ambient temperature is too high; Cooling
fan has failed (if equipped).
Check cooling fan operation
Control Fault: A blank EPM, or an EPM with corrupted data has
been installed.
Perform a factory reset using Parameter 48 —
PROGRAM SELECTION.
Incompatibility Fault: An EPM with an incompatible parameter ver-
sion has been installed.
Either remove the EPM or perform a factory reset
(Parameter 48) to change the parameter version of
the EPM to match the parameter version of the drive.
CL
CURRENT LIMIT: The output current has exceeded the CURRENT Check for loose electrical connections.
LIMIT setting (Parameter 25) and the drive is reducing the output
Check for faulty condenser fan motor.
frequency to reduce the output current. If the drive remains in CUR- Check Parameter P25 from Table 23 is set correctly.
RENT LIMIT too long, it can trip into a CURRENT OVERLOAD fault
(PF).
GF
HF
JF
Data Fault: User data and OEM defaults in the EPM are corrupted. Restore factory defaults P48, see section above. If
that does not work, replace EPM.
High DC Bus Voltage Fault: Line voltage is too high; Deceleration
rate is too fast; Overhauling load.
Check line voltage — set P01 appropriately
Serial Fault: The watchdog timer has timed out, indicating that the
serial link has been lost.
Check serial connection (computer)
Check settings for PXX.
Check settings in communication software to match
PXX.
LF
Low DC Bus Voltage Fault: Line voltage is too low.
Check line voltage — set P01 appropriately
OF
Output Transistor Fault: Phase to phase or phase to ground short
Reduce boost or increase acceleration values. If
circuit on the output; Failed output transistor; Boost settings are too unsuccessful, replace drive.
high; Acceleration rate is too fast.
Check for incorrect wiring T1, T2, T3.
PF
Current Overload Fault: VFD is undersized for the application;
Mechanical problem with the driven equipment.
Check line voltage — set P01 appropriately
Check for dirty coils
Check for motor bearing failure
SF
F1
Single-phase Fault: Single-phase input power has been applied to a Check input power phasing
three-phase drive.
EPM Fault: The EPM is missing or damaged.
F2-F9, Fo
Internal Faults: The control board has sensed a problem
Feedback signal is above set point
Consult factory
Drive display = 60.0 even though it is
cold outside and it should be running
slower
Check for proper set point
Check liquid line pressure
Drive display = ‘---’ even though drive
should be running
Start jumper is missing
Replace start jumper. See section above
Drive display = 8.0 even though fan
should be running faster
Feedback signal is below set point and fan is at minimum speed
Check for proper set point
Check liquid line pressure
VFD flashes 57 and LCS
Feedback or speed signal lost. Drive will operate at 57 Hz until reset In stand alone mode: Check transducer wiring and
or loss of start command. Resetting requires cycling start command feedback voltage. Feedback voltage displayed on
(or power).
P-69. Pin 6 should be 5 v output. Pin 5 (feedback)
should be somewhere between 0 and 5 v.
56
MOTORMASTER V TERMINAL BLOCK
2
5
6
11
12
2
14
13A
13B
13C
15
25
2
1
FR1
21
14
FR1
21
14
208/230, 460, 575 VOLT ONLY
208 VOLT ONLY
FR1
21
14
Y
T ONL
OL
400 V
LEGEND
Configuration Table
AUX — Auxiliary
CONTROL INPUT
(PINS 25, 2)
FB
FR
— Fuse Block
— Fan Relay
MODE
NOMINAL VOLTAGE
Hz
START JUMPER
MM — Motormaster
5
6
7
8
208/230/460/575*
208/380
60
60
50
50
External control 4-20 mA
External control 4-20 mA
External control 4-20 mA
External control 4-20 mA
TB1-TB2
TB13A-TB2
TB13B-TB2
TB13C-TB2
OFM — Outdoor Fan Motor
TB
— Terminal Block
230
380/415
*208-v can run in mode 5 or 6.
Fig. 64 — Typical Motormaster® Wiring
57
Table 23 — Motormaster® V Program Parameters for Operating Modes
PARAMETER
P01
P02
P03
P04
P05
P06
P08
P09
P10
P11
P12
P13
P14
P15
P16
P17
P19
P20
P21
P22
P23
P24
P25
P26
P27
P28
P29
P30
P31
P32
P33
P34
P35
P36
P37
P38
P39
P40
P41
P42
P43
P44
P45
P46
P47
P48
P61
P62
P63
P64
P65
P66
P67
P68
DESCRIPTION
Line Voltage: 01 = low line, 02 = high line
Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03=8 kHz
Start-up mode: flying restart
Stop mode: coast to stop
Standard Speed source: 04=4-20 mA, 05=R22, 06=R134a
TB-14 output: 01 = none
TB-30 output: 01 = none
MODE 5 MODE 6 MODE 7 MODE 8
01
01
06
01
04
01
01
01
01
01
01
01
01
02
02
01
10
10
0
02
01
06
01
04
01
01
01
01
01
01
01
01
02
02
01
10
10
0
01
01
06
01
04
01
01
01
01
01
01
01
01
02
02
01
10
10
0
02
01
06
01
04
01
01
01
01
01
01
01
01
02
02
01
10
10
0
TB-31 Output: 01 = none
TB-13A function sel: 01 = none
TB-13B function sel: 01 = none
TB-13C function sel: 01 = none
TB-15 output: 01 = none
Control: 01 = Terminal strip
Serial link: 02 = enabled 9600,8,N,2 with timer
Units editing: 02 = whole units
Rotation: 01 = forward only, 03 = reverse only
Acceleration time: 10 sec
Deceleration time: 10 sec
DC brake time: 0
DC BRAKE VOLTAGE 0%
Min freq = 8 Hz ~ 100 - 160 rpm
Max freq
Current limit:
Motor overload: 100
Base freq: 60 or 50 Hz
Fixed boost: 0.5% at low frequencies
Accel boost: 0%
Slip compensation: 0%
Preset spd #1: 0
Preset spd #2: 0
Preset spd #3: 0
0
0
0
0
8
8
8
8
60
125
100
60
0.5
0
60
125
100
60
0.5
0
50
110
100
50
0.5
0
50
110
100
50
0.5
0
0
0
0
0
57
0
57
0
47
0
47
0
0
0
0
0
Preset spd 4 default – R22 setpoint. TB12-2 open
Preset spd 5 default – R134a setpoint. TB12-2 closed
Preset spd 6 default
Preset spd 7 default
Skip bandwidth
18.0
12.6
0
18.0
12.6
0
18.0
12.6
0
18.0
12.6
0
0
0
0
0
0
0
0
0
Speed scaling
0
0
0
0
Frequency scaling 50 or 60 Hz
Load scaling: default (not used so NA)
Accel/decel #2: default (not used so NA)
Serial address
60
200
60
1
60
200
60
1
50
200
60
1
50
200
60
1
Password:111
111
8
111
8
111
8
111
8
Speed at min signal: 8 Hz used when PID disabled and 4-20 mA input
Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20 mA input
Clear history? 01 = maintain. (set to 00 to clear)
Program selection: Mode 1 – 12
PI Mode: 05= reverse, 0-5V, 01 = no PID
Min feedback = 0 (0V *10)
Max feedback = 50 (5V * 10)
Proportional gain = 4%
Integral gain = .2
60
01
05
01
0
60
01
06
01
0
50
01
07
01
0
50
01
08
01
0
50
4
50
4
50
4
50
4
.2
.2
.2
.2
PI accel/decel (setpoint change filter) = 5
Min alarm
Max alarm
5
5
5
5
0
0
0
0
0
0
0
0
LEGEND
NA — Not Applicable
PID — Proportional Integral Derivative
TB — Terminal Block
58
TROUBLESHOOTING — Troubleshooting the Motormas-
ter® V control requires a combination of observing system op-
eration and VFD display information. The MMV should fol-
low the 4 to 20 mA signal from the ComfortLink™ controls.
The speed command from the ComfortLink controls can be
monitored in 2 ways:
5. Mount the new module in the unit’s control box using a
Phillips screwdriver and the screws saved in Step 2.
6. Reinstall all module connectors. For accessory Naviga-
tor™ device replacement, make sure the plug is installed
at LVT in the LEN connector.
7. Carefully check all wiring connections before restoring
power.
8. Verify the ENABLE/OFF/REMOTE CONTACT switch
is in the OFF position.
9. Restore control power. Verify that all module red LEDs
blink in unison. Verify that all green LEDs are blinking
and that the scrolling marquee or Navigator display is
communicating correctly.
10. Verify all configuration information, settings, set points
and schedules. Return the ENABLE/OFF/REMOTE
CONTACT switch to its previous position.
1. Variables VH.PA, VH.PB in the "outputs" submenu of
ComfortLink - given as a percentage of 4 to 20 mA range.
2. P56 in Motormaster V shows 4-20 mA input in percent of
maximum input.
Refer to Table 24 for the variable definitions of each
controller.
Table 24 — Controller Cross-Reference
4-20 mA
CONTROL
SIGNAL
VH.PA, VH.PB
(COMFORTLINK)
VFD SPEED
(MOTORMASTER V)
INPUT (P56,
MOTORMASTER V)
4 mA
12 mA
20 mA
0%
50%
20%
60%
8 Hz
26 Hz
60 Hz
Table 25 — Replacement Modules
100%
100%
REPLACEMENT PART NO.
MODULE
(with Software)
The MMV also provides real time monitoring of key in-
puts and outputs. The collective group is displayed through pa-
rameters 50-56 and all values are read only.
• P50: FAULT HISTORY — Last 8 faults
• P51: SOFTWARE version
• P52: DC BUS VOLTAGE — in percent of nominal.
Usually rated input voltage x 1.4.
• P54: LOAD — in percent of drives rated output current
rating
Main Base Board (MBB)
38AP501672
HK50AA031
Scrolling Marquee Display
Energy Management
Module (EMM)
30GT515218
Navigator Display
Compressor Expansion Board
Auxiliary Board
HK50AA033
HK50AA027
32GB500442EE
Compressors
• P55: VDC INPUT — in percent of maximum input: 50
will indicate full scale which is 5 v
• P56: 4-20 mA INPUT — in percent of maximum input:
20% = 4 mA, 100% = 20 mA
WARNING
Do not supply power to unit with compressor cover
removed. Failure to follow this warning can cause a fire,
resulting in personal injury or death.
REPLACING DEFECTIVE MODULES — The Comfort-
Link™ replacement modules are shown in Table 25. If the main
base board (MBB) has been replaced, verify that all configura-
tion data is correct. Follow the Configuration mode table and
verify that all items under sub-modes UNIT, OPT1 and OPT2
are correct. Any additional field-installed accessories or op-
tions (RSET, SLCT sub-modes) should also be verified as well
as any specific time and maintenance schedules.
Refer to the Start-Up Checklist for 38AP units (completed
at time of original start-up) found in the job folder. This infor-
mation is needed later in this procedure. If the checklist does
not exist, fill out the current information in the Configuration
mode on a new checklist. Tailor the various options and config-
urations as needed for this particular installation.
WARNING
Exercise extreme caution when reading compressor cur-
rents when high-voltage power is on. Correct any of the
problems described below before installing and running a
replacement compressor. Wear safety glasses and gloves
when handling refrigerants. Failure to follow this warning
can cause fire, resulting in personl injury or death.
CAUTION
Do not manually operate contactors. Serious damage to the
machine may result.
CAUTION
Electrical shock can cause personal injury. Disconnect all
electrical power before servicing.
COMPRESSOR REPLACEMENT — To change out
a
faulty compressor, refer to the compressor replacement proce-
dure included with the new compressor.
1. Check that all power to unit is off. Carefully disconnect
all wires from the defective module by unplugging its
connectors.
2. Remove the defective module by removing its mounting
screws with a Phillips screwdriver, and removing the
module from the control box. Save the screws for later
use.
3. Verify that the instance jumper (MBB) or address switch-
es (all other modules) exactly match the settings of the
defective module.
OIL CHARGE — Compressors are factory charged with
110 oz of POE oil. Refer to Oil Charge section page 47 for
proper oil and charge procedure.
MAINTENANCE
Recommended Maintenance Schedule — The fol-
lowing are only recommended guidelines. Jobsite conditions
may dictate that maintenance schedule is performed more often
than recommended.
NOTE: Handle boards by mounting standoffs only to avoid
electrostatic discharge.
4. Package the defective module in the carton of the new
module for return to Carrier.
59
Every month:
TROUBLESHOOTING
• Check condenser coils for debris, clean as necessary.
• Check moisture indicating sight glass for possible refrig-
erant loss and presence of moisture.
Complete Unit Stoppage and Restart — Possi-
ble causes for unit stoppage and reset methods are shown be-
low. (See Table 26 also.) Refer to Fig. 1-3 and 8-17 for compo-
nent arrangement and control wiring diagrams.
Every 3 months:
• Check refrigerant charge.
• Check all refrigerant joints and valves for refrigerant
leaks, repair as necessary.
• Check fan status switch operation.
• Check condenser coils for debris.
• Check all condenser fans for proper operation.
• Check compressor oil level.
GENERAL POWER FAILURE — After power is restored,
restart is automatic through normal MBB start-up.
UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS
OFF — When the switch is OFF, the unit will stop immediate-
ly. Place the switch in the ENABLE position for local switch
control or in the REMOTE CONTACT position for control
through remote contact closure.
FAN STATUS INPUT OPEN — After the problem causing
the fan status input to be open has been corrected, reset is auto-
matic by closing the fan status input.
OPEN 24-V CONTROL CIRCUIT BREAKER(S) — De-
termine the cause of the failure and correct. Reset circuit break-
er(s). Restart is automatic after MBB start-up cycle is
complete.
COOLING LOAD SATISFIED — Unit shuts down when
cooling load has been satisfied. Unit restarts when required to
satisfy set point.
THERMISTOR FAILURE — If a thermistor fails in either an
open or shorted condition, the unit will be shut down. Replace
SAT or RAT as required. Unit restarts automatically, but must
be reset manually by resetting the alarm with the scrolling mar-
quee as shown in Table 27.
• Check crankcase heater operation.
Every 12 months:
• Check all electrical connections, tighten as necessary.
• Inspect all contactors and relays, replace as necessary.
• Check accuracy of thermistors, replace if greater than
± 2° F (1.2° C) variance from calibrated thermometer.
• Obtain and test an oil sample. Change oil only if
necessary.
• Check refrigerant filter driers for excessive pressure
drop, replace as necessary.
• Check condition of condenser fan blades and ensure they
are securely fastened to the motor shaft.
• Perform service test to confirm operation of all
components.
Microchannel Heat Exchanger (MCHX) Con-
denser Coil Maintenance and Cleaning
Recommendations
CAUTION
CAUTION
If unit stoppage occurs more than once as a result of any of
the safety devices listed, determine and correct cause
before attempting another restart.
Do not apply any chemical cleaners to MCHX condenser
coils. These cleaners can accelerate corrosion and damage
the coil.
COMPRESSOR SAFETIES — The 38AP units with Com-
fortLink™ controls include a compressor protection board that
protects the operation of each of the compressors. Each board
senses the presence or absence of current to each compressor.
If there is a command for a compressor to run and there is
no current, then one of the following safeties or conditions
have turned the compressor off:
Compressor Overcurrent — All compressors have internal
line breaks or a motor protection device located in the com-
pressor electrical box.
Compressor Short Circuit — There will not be current if the
compressor circuit breaker that provides short circuit protection
has tripped.
Routine cleaning of coil surfaces is essential to maintain
proper operation of the unit. Elimination of contamination and
removal of harmful residues will greatly increase the life of the
coil and extend the life of the unit. The following steps should
be taken to clean MCHX condenser coils:
1. Remove any foreign objects or debris attached to the
coreface or trapped within the mounting frame and
brackets.
2. Put on personal protective equipment including safety-
glasses and/or face shield, waterproof clothing and
gloves. It is recommended to use full coverage clothing.
3. Start high pressure water sprayer and purge any soap or
industrial cleaners from sprayer before cleaning condens-
er coils. Only clean, potable water is authorized for clean-
ing condenser coils.
Compressor Motor Over Temperature — The internal line-
break or over temperature switch has opened.
High-Pressure Switch Trip — The high pressure switch has
opened. Below are the factory settings for the fixed high pres-
sure switch.
4. Clean condenser face by spraying the core steady and
uniformly from top to bottom while directing the spray
straight toward the core. Do not exceed 900 psig or 30 de-
gree angle. The nozzle must be at least 12 in. from the
core face. Reduce pressure and use caution to prevent
damage to air centers.
CUTOUT
CUT-IN
38AP UNIT
SIZE
psig
kPa
psig
kPa
025-100
650
4482
500
3447
ASTP Protection Trip — All non-digital Copeland compres-
sors are equipped with an advanced scroll temperature protec-
tion (ASTP). A label located above the terminal box identifies
models that contain this technology. See Fig. 65.
CAUTION
Excessive water pressure will fracture the braze between
air centers and refrigerant tubes.
60
Low Saturated Suction — Several conditions can lead to low
saturated suction alarms. The controls have several override
modes built in which will attempt to keep the unit from
shutting down. Low airflow, low refrigerant charge and
plugged filter driers are the main causes for this condition. To
avoid permanent damage, do NOT repeatedly reset these alert
and/or alarm conditions without identifying and correcting the
cause(s).
Alarms and Alerts — These are warnings of abnormal
or fault conditions, and may cause either one circuit or the
whole unit to shut down. They are assigned code numbers as
described in Table 26.
Automatic alarms will reset without operator intervention if
the condition corrects itself. The following method must be
used to reset manual alarms (refer to Table 27):
Before resetting any alarm, first determine the cause of the
alarm and correct it. After determining and correcting the cause
of the alarm, enter the Alarm mode indicated by the LED on
Fig. 65 — Advanced Scroll Temperature
Protection Label
Advanced scroll temperature protection is a form of internal
discharge temperature protection that unloads the scroll com-
pressor when the internal temperature reaches approximately
300 F. At this temperature, an internal bi-metal disk valve
opens and causes the scroll elements to separate, which stops
compression. Suction and discharge pressures balance while
the motor continues to run. The longer the compressor runs un-
loaded, the longer it must cool before the bi-metal disk resets.
See Fig. 66 for approximate reset times.
To manually reset ASTP, the compressor should be stopped
and allowed to cool. If the compressor is not stopped, the motor
will run until the motor protector trips, which occurs up to
90 minutes later. Advanced scroll temperature protection will
reset automatically before the motor protector resets, which
may take up to 2 hours.
the side of the scrolling marquee display. Press
and
ENTER
until the sub-menu item RCRN “RESET ALL CURRENT
ALARMS” is displayed. Press . The control will
ENTER
prompt the user for a password, by displaying PASS and
WORD. Press to display the default password, 1111.
ENTER
for each character. If the password has been
Press
ENTER
changed, use the arrow keys to change each individual charac-
ter. Toggle the display to “YES” and press
alarms will be reset.
. The
ENTER
Compressor Time Guards — For compressors, the control
will use a Compressor Minimum OFF Time of 2 minutes or a
Compressor Minimum ON Time of 3 minutes.
High Discharge Gas Temperature Protection — Units
equipped with digital compressors have an additional thermis-
tor located on the discharge line, If discharge temperature ex-
ceeds 265 F (129.4 C), the digital compressor will be shut off.
Alarms will also occur if the current sensor board malfunc-
tions or is not properly connected to its assigned digital input. If
the compressor is commanded OFF and the current sensor
reads ON, an alert is generated. This will indicate that a com-
pressor contactor has failed closed. In this case, a special mode,
Compressor Stuck on Control, will be enabled and all other
compressors will be turned off. An alarm will then be enabled
to indicate that service is required. Outdoor fans will continue
to operate. The first outdoor fan stage is turned on immediately.
The other stages of fan will be turned on as required by SCT.
DIAGNOSTIC ALERT CODES AND POSSIBLE
CAUSES
T048 (Circuit A Compressor Availability Alert)
T049 (Circuit B Compressor Availability Alert)
—
Alert
codes 048 and 049 are for circuits A and B respectively. These
alerts occur when two compressors are unavailable to run on a
3 compressor circuit. This alert can only occur on single circuit
unit sizes 040-060 and three compressor circuit unit sizes 70-
100. The control ensures proper oil return by insuring a circuit
does not operate with one compressor for longer than one hour
of cumulative run time.
COMPRESSOR FAILURE ALERTS
T051, T052, T053 (Circuit A Compresser Failures)
T055, T056, T057 (Circuit B Compressor Failures) — Alert
codes 051, 052, 053, 55, 56 and 057 are for compressors A1,
A2, A3, B1, B2, and B3 respectively. These alerts occur when
the current sensor (CS) does not detect compressor current dur-
ing compressor operation. When this occurs, the control turns
off the compressor.
120
110
100
90
80
70
60
50
40
30
20
10
0
If the current sensor board reads OFF while the compressor
relay has been commanded ON, an alert is generated.
POSSIBLE CAUSES
Compressor Overload — Either the compressor internal over-
load protector is open or the external overload protector (Kri-
wan module) has activated. The external overload protector
modules are mounted in the compressor wiring junction box.
Temperature sensors embedded in the compressor motor wind-
ings are the inputs to the module. The module is powered with
24 vac from the units main control box. The module output is a
normally closed contact that is wired in series with the com-
pressor contactor coil. In a compressor motor overload condi-
tion, contact opens, deenergizing the compressor contactor.
Low Refrigerant Charge — If the compressor operates for an
extended period of time with low refrigerant charge, the com-
pressor ASTP device will open, which will cause the compres-
sor to trip on its overload protection device.
0
10
20
30
40
50
60
70
80
90
Compressor Unloaded Run Time (Minutes)
*Times are approximate.
NOTE: Various factors, including high humidity, high ambient temperature,
and the presence of a sound blanket will increase cool-down times.
Fig. 66 — Recommended Minimum Cool Down
Time After Compressor is Stopped*
Circuit Breaker Trip — The compressors are protected from
short circuit by a breaker in the control box.
61
Wiring Error — A wiring error might not allow the compres-
sor to start.
control, the supply-air temperature must be updated every
3 minutes. If it is not updated, then the alarm will be generated.
Failure of this thermistor will shut down the entire unit.
To check out alerts T051-T057:
A061 (Return Air Thermistor Failure) — If the unit is re-
quired to use the return air thermistor input (C.TYP 1, 3, 5, and
9) and the sensor reading is outside the range of –40 to 245 F
(–40 to118 C) then the alarm will occur. The cause of the alarm
is usually a faulty thermistor, a shorted or open thermistor
caused by a wiring error, or a loose connection. If the return
temperature is being written to by CCN or a third party control,
the return-air temperature must be updated every 3 minutes. If
it is not updated, then the alarm will be generated. Failure of
this thermistor will shut down the entire unit.
T068, T69 (Circuit A,B Compressor Return Gas Tempera-
ture Thermistor Failure) — This alert occurs when the com-
pressor return gas temperature sensor is outside the range of
–40 to 245 F (–40 to 118 C). Failure of this thermistor will dis-
able any elements of the control which requires its use.
T073 (Outside Air Temperature Thermistor Failure) — This
alert occurs when the outside air temperature sensor is outside
the range of –40 to 245 F (–40 to 118 C). Failure of this therm-
istor will disable any elements of the control which requires its
use.
T074 (Space Temperature Thermistor Failure) — This alert
occurs when the space temperature sensor is outside the range
of –40 to 245 F (–40 to 118 C). Failure of this thermistor will
disable any elements of the control which requires its use. If the
unit is configured for SPT 2 stage or SPT multi-stage operation
and the sensor fails, no cooling mode may be chosen. The
cause of the alert is usually a faulty thermistor in the T55, T56,
or T58 device, a shorted or open thermistor caused by a wiring
error, or a loose connection.
1. Turn on the compressor in question using Service Test
mode. If the compressor does not start, then most likely
the problem is one of the following: HPS open, open in-
ternal protection, circuit breaker trip, incorrect safety wir-
ing, or incorrect compressor wiring.
2. If the compressor does start, verify it is rotating in the cor-
rect direction.
IMPORTANT: Prolonged operation in the wrong direction
can damage the compressor. Correct rotation can be veri-
fied by a gage set and looking for a differential pressure
rise on start-up.
IMPORTANT: If the CS is always detecting current, verify
that the compressor is on. If the compressor is on, check
the contactor and the relay on the MBB. If the compressor
is off and there is no current, verify the CS wiring and
replace if necessary.
IMPORTANT: Return to Normal mode and observe com-
pressor operation to verify that compressor current sensor
is working and condenser fans are energized.
COMPRESSOR STUCK ON FAILURE ALARMS
Circuit A A051, A052, A053
Circuit B A055, A056, A057 — Alarm codes 051, 052, 053,
055, 056 and 057 are for compressors A1, A2, A3, B1, B2 and
B3. These alarms occur when the current sensor (CS) detects
current when the compressor should be off. When this occurs,
the control turns off the compressor.
T090 (Circuit A Discharge Pressure Transducer Failure)
T091 (Circuit B Discharge Pressure Transducer Failure) —
Alert codes 090 and 091 are for circuits A and B respectively.
These alerts occur when the pressure is outside the range of 0.0
to 667.0 psig. A circuit cannot run when this alert is active. Use
the scrolling marquee to reset the alert. The cause of the alert is
usually a faulty transducer, faulty 5-v power supply, or a loose
connection.
If the current sensor board reads ON while the compressor
relay has been commanded OFF for a period of 4 continuous
seconds, an alarm is generated. These alarms are only moni-
tored for a period of 10 seconds after the compressor relay has
been commanded OFF. This is done to facilitate a service tech-
nician forcing a relay to test a compressor.
In addition, if a compressor stuck failure occurs and the cur-
rent sensor board reports the compressor and the request off,
certain diagnostics will take place as follows:
T092 (Circuit A Suction Pressure Transducer Failure)
T093 (Circuit B Suction Pressure Transducer Failure)
—
Alert codes 092 and 093 are for circuits A and B respectively.
These alerts occur when the pressure is outside the range of 0.0
to 420.0 psig. A circuit cannot run when this alert is active. Use
the scrolling marquee to reset the alert. The cause of the alert is
usually a faulty transducer, faulty 5-v power supply, or a loose
connection.
T094 (Discharge Gas Thermistor Failure) — This alert oc-
curs for units which have the digital compressor installed on
circuit A. If discharge gas temperature is open or shorted, the
circuit will be shutoff. The alert will reset itself when discharge
temperature is less than 250 F (121.1 C). The cause of the alert
is usually low refrigerant charge or a faulty thermistor.
1. If any of the compressors are diagnosed as stuck on and
the current sensor board is on and the request is off, the
control will command the condenser fans to maintain
normal head pressure.
2. The control will shut off all other compressors.
The possible causes include welded contactor or frozen
compressor relay on the MBB.
To check out alarms A051-A057:
1. Place the unit in Service Test mode. All compressors
should be off.
2. Verify that there is not 24-v at the contactor coil. If there
is 24 v at the contactor, check relay on MBB and wiring.
T110 (Circuit A Loss of Charge)
T111 (Circuit B Loss of Charge) — Alert codes 110 and 111
are for circuits A and B respectively. These alerts occur when
the compressor is OFF and the suction pressure is less than
26 psig.
3. Check for welded contactor.
4. Verify CS wiring.
5. Return to Normal mode and observe compressor opera-
tion to verify that compressor current sensor is working
and condenser fans are energized.
A060 (Supply Air Thermistor Failure) — If the unit is re-
quired to use the supply air thermistor input (C.TYP 1, 3, 5, and
9) and the sensor reading is outside the range of –40 to 245 F
(–40 to 118 C) then the alarm will occur. The cause of the
alarm is usually a faulty thermistor, a shorted or open thermis-
tor caused by a wiring error, or a loose connection. If the sup-
ply temperature is being written to by CCN or a third party
T112 (Circuit A High Saturated Suction Temperature)
T113 (Circuit B High Saturated Suction Temperature)
—
Alert codes 112 and 113 occur when compressors in a circuit
have been running for at least 5 minutes and the circuit saturat-
ed suction temperature is greater than 70 F (21.1 C). The high
saturated suction alert is generated and the circuit is shut down.
62
T114 (Circuit A Low Superheat)
continues to rise to greater than 150 F (65.6 C), the alert will
occur and the circuit's remaining compressor will shut down.
The cause of the alarm is usually an overcharged system, high
outdoor ambient temperature coupled with dirty outdoor coil,
plugged filter drier, or a faulty high-pressure switch.
T115 (Circuit B Low Superheat) — Alert codes 114 and 115
occur when the superheat of a circuit is less than 5 F (2.8 C) for
5 continuous minutes. The low superheat alert is generated and
the circuit is shut down.
T118 (High Discharge Gas Temperature Alert)
A118 (High Discharge Gas Temperature Alarm)
A140 (Reverse Rotation Detected) — A test is made once, on
power up, for suction pressure change on the first activated cir-
cuit. The unit control determines failure as follows:
1. The suction pressure of both circuits is sampled 5 seconds
before the compressor is brought on, right when the com-
pressor is brought on and 5 seconds afterwards.
2. The rate of suction pressure change from 5 seconds be-
fore the compressor is brought on to when the compres-
sor is brought on is calculated.
3. The rate of suction pressure change from when the
compressor is brought on to 5 seconds afterwards is
calculated.
—
This
alert or alarm occurs for units which have the digital compres-
sor installed on circuit A. If discharge gas temperature is great-
er than 268 F (131.1 C), the circuit will be shut off. The alert
will reset itself when discharge temperature is less than 250 F
(121.1 C). If this alert occurs 3 times within a day, the A118
alarm will be generated and the alarm must be reset manually.
The cause of the alert is usually low refrigerant charge or a
faulty thermistor.
P120 (Circuit A Low Saturated Suction Temperature —
Compressor Shutdown)
T120 (Circuit A Low Saturated Suction Temperature Alert)
4. With the above information, the test for reverse rotation is
made. If the suction pressure change 5 seconds after com-
pression is greater than the suction pressure change 5 sec-
onds before compression – 1.25, then there is a reverse
rotation error.
A120 (Circuit A Low Saturated Suction Temperature
Alarm)
P121 (Circuit B Low Saturated Suction Temperature —
Compressor B2 Shutdown)
This alarm will disable mechanical cooling and will require
manual reset. This alarm may be disabled once the reverse ro-
tation check has been verified by setting REV.R = Yes.
A150 (Unit is in Emergency Stop) — If the CCN emergency
stop command is received, the alarm is generated and the unit
will be immediately stopped.
T121 (Circuit B Low Saturated Suction Temperature Alert)
A121 (Circuit B Low Saturated Suction Temperature
Alarm) — This alert or alarm is used to keep the evaporator
from freezing and the saturated suction temperature above the
low limit for the compressors.
When SSTA or SSTB is less than 20 F (–6.7 C) for 4 min-
utes, less than 10 F (–12.2 C) for 2 minutes, less than 0° F
(–17.8 C) for 1 minute, or less than –20 F (–28.9 C) for 20 sec-
onds continuously, one compressor of the affected circuit will
be shut down with a local alert (P120, P121) and a 10-minute
time guard will be added to the compressor. If saturated suction
temperature continues to be less than 20 F (–6.7 C) for 4 min-
utes, less than 10 F (–12.2 C) for 2 minutes, less than 0° F
(–17.8 C) for 1 minute, or less than –20 F (–28.9 C) for 20 sec-
onds continuously, then another compressor will be shut down
until the last compressor on the circuit is shut down at which
time an alert or alarm will be issued (T120, T121, A120,
A121).
This failure follows a 3 strike methodology whereby the
first two times a circuit goes down entirely, an alert will be gen-
erated (T120, T121) which keeps the circuit off for 15 minutes
before allowing the circuit to try again. The third time this hap-
pens, an alarm (A120, A121) will be generated which will ne-
cessitate a manual reset to get the circuit back running.
To recover from these alerts, a 10-minute hold off timer
must elapse and the saturated suction temperature must rise
above 29.32 F (–1.5 C). If recovery occurs, staging will be al-
lowed on the circuit again. Therefore, it is possible that multi-
ple P120 or P121 alerts may be stored in the alarm.
If there are 1 or 2 strikes on the circuit and the circuit
recovers for a period of time, it is possible to clear out the
strikes thereby resetting the strike counter automatically. The
control must have saturated suction temperature greater than or
equal to 34 F (1.1 C) for 60 minutes in order to reset the strike
counters.
If the CCN point name "EMSTOP" in the system table is set
to emergency stop, the unit will shut down immediately and
broadcast an alarm back to the CCN, indicating that the unit is
down. This alarm will clear when the variable is set back to
"enable."
A151 (Illegal Configuration) — An A151 alarm indicates an
invalid configuration has been entered. The following are ille-
gal configurations.
• Invalid unit size has been entered.
• Dual thermostat configured for single-circuit unit.
• Dual thermostat and switch demand limit configure
• AUX board incorrect revision.
• Unit configuration set to invalid type.
A152 (Unit Down Due to Failure) — Both circuits are off
due to alerts and/or alarms. Reset is automatic when all alarms
are cleared. This alarm indicates the unit is at 0% capacity.
T153 (Real Time Clock Hardware Failure) — A problem
has been detected with MBB real time clock hardware. Try re-
setting the power and check the indicator lights. If the alarm
continues, the board should be replaced.
A154 (Serial EEPROM Hardware Failure) — A problem
has been detected with the EEPROM on the MBB. Try reset-
ting the power and check the indicator lights. If the alarm con-
tinues, the board should be replaced.
T155 (Serial EEPROM Storage Failure Error) — A problem
has been detected with the EEPROM storage on the MBB. Try
resetting the power and check the indicator lights. If the alert
continues, the board should be replaced.
A156 (Critical Serial EEPROM Storage Failure Error) — A
problem has been detected with the EEPROM storage on the
MBB. Try resetting the power and check the indicator lights. If
the alarm continues, the board should be replaced.
A157 (A/D Hardware Failure) — A problem has been detect-
ed with A/D conversion on the boards. Try resetting the power
and check the indicator lights. If the alarm continues, the board
should be replaced.
T122 (Circuit A High Pressure Trip)
T123 (Circuit B High Pressure Trip) — Alert codes 122 and
123 are for circuits A and B respectively.
T126 (Circuit A High Head Pressure)
T127 (Circuit B High Head Pressure) — Alert codes 126 and
127 are for circuits A and B respectively. These alerts occur
when the appropriate saturated condensing temperature is
greater than 150 F (65.6 C). Prior to the alert, the control will
shut down one compressor on a circuit if that circuit's saturated
condensing temperature is greater than 145 F (62.8 C). If SCT
63
A170 (Loss of Communication with the Compressor
Expansion Module) — This alarm indicates that there are
communications problems with the compressor expansion,
which is required for unit sizes 070 to 100. The alarm will auto-
matically reset.
A173 (Energy Management Module Communication Fail-
ure) — This alarm indicates that there are communications
problems with the energy management. All functions per-
formed by the EMM will stop, which can include demand lim-
it, reset and capacity input. The alarm will automatically reset.
T174 (4 to 20 mA Cooling Set point Input Failure) — This
alert indicates a problem has been detected with cooling set
point 4 to 20 mA input. The input value is either less than 2 mA
or greater than 22 mA.
T176 (4 to 20 mA Reset Input Failure) — This alert indi-
cates a problem has been detected with reset 4 to 20 mA input.
The input value is either less than 2 mA or greater than 22 mA.
The reset function will be disabled when this occurs.
greater than 22 mA. The reset function will be disabled when
this occurs.
A200 (Fan Status Switch 1 Failure)
T201 (Fan Status Switch 1 Failure)
T202 (Fan Status Switch 2 Failure) — This alarm or alert in-
dicates the fan status input 1 or 2 is open when the unit is ON.
The unit will be in an alert condition until the fan status switch
is closed. The alarm or alert is an automatic reset when the fan
status switch closes. The A200 alarm is for single circuit units.
T303 (Condenser Coil Maintenance Due) — Coil Service
Countdown (C.L.DN) expired. Complete condenser coil clean-
ing and enter ‘YES’ for Coil Maintenance Done (C.L.MN)
item.
T500, T501, T502 (Current Sensor Board Failure — A xx
Circuit A)
T503, T504, T505 (Current Sensor Board Failure — B xx
Circuit B) — Alert codes 500, 501, 502, 503, 504, and 505 are
for compressors A1, A2, A3, B1, B2, and B3 respectively.
These alerts occur when the output of the current sensor (CS) is
a constant high value. These alerts reset automatically. If the
problem cannot be resolved, the CS board must be replaced.
T177 (4 to 20 mA Demand Limit Input Failure)
—
This
alert indicates a problem has been detected with demand limit
4 to 20 mA input. The input value is either less than 2 mA or
Table 26 — Alarm and Alert Codes
ALARM/
ALARM OR
ALERT
ACTION TAKEN
BY CONTROL
RESET
DESCRIPTION
WHY WAS THIS ALARM GENERATED?
Two compressors on circuit failed
Two compressors on circuit failed
ALERT CODE
METHOD
Circuit A Compressor
Availability Alert
Circuit B Compressor
Availability Alert
T048
T049
Alert
Alert
Circuit shut down
Circuit shut down
Manual
Manual
Circuit A
Compressor A1,A2,A3
Failure
Circuit B
Compressor B1,B2,B3
Failure
Circuit A
Compressor A1,A2,A3
Failure
Circuit B
Compressor B1,B2,B3
Failure
Respective current sensor board (CSB)
feedback signal does not match relay state
Respective compressor shut
down in Circuit A.
T051, T052, T053
T055, T056, T057
A051, A052, A053
A055, A056, A057
Alert
Alert
Manual
Manual
Manual
Manual
Respective current sensor board (CSB)
feedback signal does not match relay state
Respective compressor shut
down in Circuit B.
Respective current sensor board (CSB)
feedback signal is ON when the compressor
should be off
Respective current sensor board (CSB)
feedback signal is ON when the compressor
should be off
Alarm
Alarm
Unit shut down
Unit shut down
Supply Air
Thermistor outside range of –40 to 245 F
(–40 to 118 C)
A060
A060
A061
A061
T068
T069
Alarm
Alarm
Alarm
Alarm
Alert
Unit shut down
Unit shut down
Unit shut down
Unit shut down
Circuit shut down
Circuit shut down
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Thermistor Failure
Supply Air Temperature
Update not received
Return Air
Thermistor Failure
Return Air Temperature
Update not received
Circuit A Return Gas
Thermistor Failure
Circuit B Return Gas
Thermistor Failure
Temperature not updated during 3 minutes
Thermistor outside range of –40 to 245 F
(–40 to 118 C)
Temperature not updated during 3 minutes
Thermistor is outside range of –40 to 245 F
(–40 to 118 C)
Thermistor is outside range of –40 to 245 F
(–40 to 118 C)
Alert
Temperature reset disabled.
Unit runs under normal
control/set points.
Temperature reset disabled.
Unit runs under normal
control/set points.
Outside Air
Thermistor outside range of –40 to 245 F
(–40 to 118 C)
T073
T074
Alert
Alert
Automatic
Automatic
Thermistor Failure
Space Temperature
Thermistor Failure
Thermistor outside range of –40 to 245 F
(–40 to 118 C)
Circuit A Discharge Pres-
sure Transducer Failure
Circuit B Discharge Pres-
sure Transducer Failure
Circuit A Suction Pressure
Transducer Failure
Circuit B Suction Pressure
Transducer Failure
The pressure is outside the range of
0.0 to 667.0 psig
The pressure is outside the range of
0.0 to 667.0 psig
The pressure is outside the range of
0.0 to 420.0 psig
The pressure is outside the range of
0.0 to 420.0 psig
T090
T091
T092
T093
T094
Alert
Alert
Alert
Alert
Alert
Circuit A shut down
Circuit B shut down
Automatic
Automatic
Automatic
Automatic
Automatic
Circuit A shut down
Circuit B shut down
Discharge Gas
Thermistor Failure
Discharge thermistor (DTT) is
either open or shorted
Digital compressor shut down.
LEGEND
CCN
CSB
CXB
DTT
—
—
—
—
Carrier Comfort Network®
LWT
MBB
SCT
SST
— Leaving Fluid Temperature
— Main Base Board
Current Sensor Board
Compressor Expansion Module
Discharge Temperature Thermistor
— Saturated Condensing Temperature
— Saturated Suction Temperature
EEPROM — Electrically Erasable Programmable
TSTAT — Thermostat
Read-Only Memory
EMM
—
Energy Management Module
64
Table 26 — Alarm and Alert Codes (cont)
ALARM/
ALERT CODE
ALARM OR
ALERT
ACTION TAKEN
BY CONTROL
RESET
METHOD
DESCRIPTION
WHY WAS THIS ALARM GENERATED?
If the compressors are off and discharge pressure
reading is less than 26 psig for 30 sec.
If the compressors are off and discharge pressure
reading is less than 26 psig for 30 sec.
Circuit is on and saturated suction temperature is
greater than 70 F (15.6 C) for 5 minutes
Circuit is on and saturated suction temperature is
greater than 70 F (15.6 C) for 5 minutes
T110
T111
T112
T113
Alert
Alert
Alert
Alert
Circuit A Loss of Charge
Circuit B Loss of Charge
Circuit not allowed to start.
Circuit not allowed to start.
Circuit shut down
Manual
Manual
Manual
Manual
Circuit A High Saturated
Suction Temperature
Circuit B High Saturated
Suction Temperature
Circuit shut down
Automatic after first
daily occurance,
manual
Circuit A Low Suction
Superheat
Suction superheat is less than 5 F (2.8 C)
for 5 minutes.
Circuit A is shut down after
pumpdown complete.
T114
T115
Alert
Alert
thereafter
Automatic after first
daily occurance,
manual
Circuit B Low Suction
Superheat
Suction superheat is less than 5 F (2.8 C)
for 5 minutes.
Circuit B is shut down after
pumpdown complete.
thereafter
High Discharge
Discharge Thermistor (DTT) reading is
greater than 250 F
3 Discharge Gas Temperature alarms
occur within a day
T118
A118
Alert
Compressor A1 shut down
Compressor A1 shut down
Automatic
Manual
Gas Temperature
High Discharge
Gas Temperature
Alarm
SSTA is less than 20 F for 4 minutes, less than
10 F for 2 minutes, less than 0° F for 1 minute or
less than –20 F for 20 seconds continuously
SSTA is less than 20 F for 4 minutes, less than
10 F for 2 minutes, less than 0° F for 1 minute or
less than –20 F for 20 seconds continuously
SSTA is less than 20 F for 4 minutes, less than
10 F for 2 minutes, less than 0° F for 1 minute or
less than –20 F for 20 seconds continuously and
only one compressor running
SSTB is less than 20 F for 4 minutes, less than
10 F for 2 minutes, less than 0° F for 1 minute or
less than –20 F for 20 seconds continuously
SSTB is less than 20 F for 4 minutes, less than
10 F for 2 minutes, less than 0° F for 1 minute or
less than –20 F for 20 seconds continuously and
only one compressor running
SSTB is less than 20 F for 4 minutes, less than
10 F for 2 minutes, less than 0° F for 1 minute or
less than –20 F for 20 seconds continuously and
only one compressor running
Circuit A Low
Circuit A will remove one
compressor stage.
P120
T120
Alert
Alert
Automatic
Saturated Suction
Automatic
unless
3rd strike.
Circuit A Low
Saturated Suction
Circuit A shut down
Circuit A shut down
Circuit A Low
Saturated Suction
A120
P121
T121
Alarm
Alert
Alert
Manual
Circuit A Low
Saturated Suction
Circuit B will remove one
compressor stage.
Automatic
Automatic
unless
3rd strike.
Circuit B Low
Saturated Suction
Circuit B shut down
Circuit B shut down
Circuit B Low
Saturated Suction
A121
Alarm
Manual
High Pressure Switch
Trip Circuit A
High Pressure Switch
Trip Circuit B
T122
T123
Alert
Alert
High Pressure A Switch Input opento MBB
High Pressure B Switch Input open to MBB
Circuit shut down
Circuit shut down
Manual
Manual
Automatic, only
after first 3 daily
occurrences.
Circuit A High
T126
A126
T127
Alert
Alarm
Alert
SCTA >150 F
SCTA >150 F
SCTB >150 F
Circuit shut down
Circuit shut down
Circuit shut down
Discharge Pressure
Circuit A High
Discharge Pressure
Manual
Automatic, only
after first 3 daily
occurrences
Circuit B High
Discharge Pressure
Circuit B High
A127
A140
Alarm
Alarm
SCTB >150 F
Circuit shut down
Unit shut down.
Manual
Discharge Pressure
Reverse Rotation Detected
Incoming unit power leads not phased correctly
Manual
Automatic once
Unit shutdown without going CCN command for
A150
A151
Alarm
Alarm
Emergency Stop
CCN emergency stop command received
One or more illegal configurations exists.
through pumpdown.
EMSTOP returns
to normal
Manual once
Unit is not allowed to start. configuration errors
are corrected
Illegal Configuration
Automatic once
alarms/alerts are
cleared that prevent
the chiller from
starting.
A152
Alarm
Unit Down Due to Failure
LEGEND
Both circuits are down due to alarms/alerts.
Unit is unable to run.
CCN
CSB
CXB
DTT
—
—
—
—
Carrier Comfort Network®
LWT
MBB
SCT
SST
— Leaving Fluid Temperature
— Main Base Board
Current Sensor Board
Compressor Expansion Module
Discharge Temperature Thermistor
— Saturated Condensing Temperature
— Saturated Suction Temperature
EEPROM — Electrically Erasable Programmable
TSTAT — Thermostat
Read-Only Memory
EMM
—
Energy Management Module
65
Table 26 — Alarm and Alert Codes (cont)
ALARM/
ALERT CODE
ALARM OR
ALERT
ACTION TAKEN
BY CONTROL
RESET
METHOD
DESCRIPTION
WHY WAS THIS ALARM GENERATED?
Occupancy schedule will not
be used. Unit defaults to
Local On mode.
Automatic when
correct clock
control restarts.
Real Time Clock
Hardware Failure
T153
Alert
Internal clock on MBB fails
Serial EEPROM
Hardware Failure
Serial EEPROM
Storage Failure
A154
T155
Alarm
Alert
Hardware failure with MBB
Unit is unable to run.
No action
Manual
Manual
Configuration/storage failure with MBB
Critical Serial EEPROM
Storage Failure
A/D Hardware Failure
Loss of Communication
with CXB
A156
A157
A170
Alarm
Alarm
Alarm
Configuration/storage failure with MBB
Hardware failure with peripheral device
MBB loses communication with CXB
Unit is not allowed to run.
Unit is not allowed to run.
CXB functions disabled
Manual
Manual
Automatic
4 to 20 mA temperature
reset disabled. Demand Limit
set to 100%. 4 to 20 mA
set point disabled.
Loss of Communication
with EMM
A173
Alarm
MBB loses communication with EMM
Automatic
4 to 20 mA Cooling Set
Point/Desired % Capacity
Input Failure
If configured with EMM and input less than
2 mA or greater than 22 mA
Set point function/%
T174
T176
Alert
Alert
Automatic
Automatic
capacity function disabled.
Reset function disabled.
Unit returns to normal
set point control.
4 to 20 mA Temperature
Reset Input Failure
If configured with EMM and input less than
2 mA or greater than 22 mA
Demand limit function
disabled. Unit returns to
100% demand limit control.
4 to 20 mA Demand Limit
Input Failure
If configured with EMM and input less than
2 mA or greater than 22 mA
T177
A200
T201
Alert
Alarm
Alert
Automatic
Automatic
Automatic
Fan Status
Switch 1 Open
Fan Status Switch 1
is open with Dual TSTAT
configuration
Alarm is generated when fan status switch 1
is open when the unit is in an ON state
Unit not allowed to start
Alert is generated when fan status switch 1
is open when Y1 or Y2 are closed
Circuit A is not allowed to run
Fan Status Switch 2
is open with Dual TSTAT
configuration
Alert is generated when fan status switch 1
is open when Y3 or Y4 are closed
T202
T303
Alert
Alert
Circuit B is not allowed to run
None
Automatic
Automatic
Coil Service Countdown (C.L.DN) expired.
Complete condenser coil cleaning and enter ‘YES’
for Coil Maintenance Done (C.L.MN) item.
Condenser Coil
Maintenance Due
Current Sensor Board
A1 Failure
Current Sensor Board
A2 Failure
Current Sensor Board
A3 Failure
Current Sensor Board
B1 Failure
Current Sensor Board
B2 Failure
Current Sensor Board
B3 Failure
Alert occurs when CSB output
is a constant high value
Alert occurs when CSB output
is a constant high value
Alert occurs when CSB output
is a constant high value
Alert occurs when CSB output
is a constant high value
Alert occurs when CSB output
is a constant high value
Alert occurs when CSB output
is a constant high value
T500
T501
T502
T503
T504
T505
Alert
Alert
Alert
Alert
Alert
Alert
Compressor A1 shut down
Compressor A2 shut down
Compressor A3 shut down
Compressor B1 shut down
Compressor B2 shut down
Compressor B3 shut down
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
LEGEND
CCN
CSB
CXB
DTT
—
—
—
—
Carrier Comfort Network®
LWT
MBB
SCT
SST
— Leaving Fluid Temperature
— Main Base Board
Current Sensor Board
Compressor Expansion Module
Discharge Temperature Thermistor
— Saturated Condensing Temperature
— Saturated Suction Temperature
EEPROM — Electrically Erasable Programmable
TSTAT — Thermostat
Read-Only Memory
EMM
—
Energy Management Module
Table 27 — Example of Reading and Clearing Alarms
KEYPAD
ENTRY
SUB-MODE
CRNT
ITEM
ITEM EXPANSION
COMMENT
ACTIVE ALARMS (AXXX) OR
ALERTS (TXXX) DISPLAYED.
ENTER
AXXX or TXXX
CURRENTLY ACTIVE ALARMS
ESCAPE
CRNT
NO
NO
Use to clear active alarms/alerts
NO Flashes
ENTER
ENTER
RCRN
YES
NO
Select YES
Alarms/alerts clear, YES changes to NO
66
APPENDIX A — DISPLAY TABLES
Run Status Mode and Sub-Mode Directory
SUB-MODE
VIEW
ITEM
RAT
SAT
SETP
CTPT
LOD.F
DISPLAY
xxx.x ºF
xxx.x ºF
xxx.x ºF
xxx.x ºF
xxx
ITEM DESCRIPTION
COMMENT
Return Air Temperature
Supply Air Temperature
Active Set Point
Control Point
Load/Unload Factor
0=Service Test
1=Off Local
2=Off CCN
3=Off Time
4=Off Emrgcy
5=On Local
6=On CCN
7=On Time
STAT
Control Mode
0=COOL OFF
1=LO COOL
2=HI COOL
3=COOL ON
SPT.M
Space Temp Control Mode
OCC
MODE
CAP
STGE
ALRM
TIME
YES/NO
YES/NO
xxx
x
xxx
Occupied
Override Modes in Effect
Percent Total Capacity
Requested Stage
Current Alarms & Alerts
Time of Day
xx.xx
00:00-23:59
1 - 12 (1 = January,
2 = February, etc.)
MNTH
xx
Month of Year
DATE
YEAR
xx
xx
Day of Month
Year of Century
01-31
UNIT RUN HOUR AND START
RUN
HRS.U
STR.U
xxxx HRS
XXXX
Machine Operating Hours
Machine Starts
CIRC AND COMP RUN HOURS
HRS.A
HRS.B
HR.A1
HR.A2
HR.A3
HR.B1
HR.B2
HR.B3
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
Circuit A Run Hours
Circuit B Run Hours
Compressor A1 Run Hours
Compressor A2 Run Hours
Compressor A3 Run Hours
Compressor B1 Run Hours
Compressor B2 Run Hours
Compressor B3 Run Hours
HOUR
67
APPENDIX A — DISPLAY TABLES (cont)
Run Status Mode and Sub-Mode Directory (cont)
SUB-MODE
STRT
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
COMPRESSOR STARTS
ST.A1
ST.A2
ST.A3
ST.B1
ST.B2
ST.B3
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
Compressor A1 Starts
Compressor A2 Starts
Compressor A3 Starts
Compressor B1 Starts
Compressor B2 Starts
Compressor B3 Starts
PREVENTIVE MAINTENANCE
COIL
SI.CL
COIL MAINTENANCE
Coil Cleaning Srvc Int
Coil Service Countdown
Coil Cleaning Maint.Done
COIL MAINTENANCE DATES
MM/DD/YY HH:MM
xxxx HRS
xxxx HRS
YES/NO
C.L.DN
C.L.MN
CL.DT
C.L.M0
C.L.M1
C.L.M2
C.L.M3
C.L.M4
User Entry
PM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
SOFTWARE VERSION NUMBERS
CESR131279-XXXXX
MBB
AUX
CXB
EMM
MARQ
NAVI
CESR131333-XXXXX
CESR131173-XXXXX
CESR131174-XXXXX
CESR131171-XXXXX
CESR130227-XXXXX
VERS
Service Test Mode and Sub-Mode Directory
SUB-MODE
TEST
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
To enable Service Test mode, move
Enable/Off/Remote contact switch to
OFF. Change TEST to ON.
Service Test Mode
Move switch to ENABLE
OUTPUTS
Fan 1 Relay
Fan 2 Relay
Fan 3 Relay
Fan 4 Relay
FAN1
FAN2
FAN3
FAN4
FAN5
V.HPA
V.HPB
DIG.P
LSV.A
LSV.B
RMT.A
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
xx
xx
xx
ON/OFF
ON/OFF
ON/OFF
Fan 5 Relay
OUTS
Var Head Press % Cir A
Var Head Press % Cir B
Comp A1 Load Percent
Liquid Line Solenoid A
Liquid Line Solenoid B
Remote Alarm Relay
CIRCUIT A COMPRESSOR TEST
Compressor A1 Relay
Comp A1 Unload Time
Compressor A2 Relay
Compressor A3 Relay
Minimum Load Valve Relay
CIRCUIT B COMPRESSOR TEST
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
CC.A1
UL.TM
CC.A2
CC.A3
MLV
ON/OFF
xx
ON/OFF
ON/OFF
ON/OFF
CMPA
CMPB
CC.B1
CC.B2
CC.B3
ON/OFF
ON/OFF
ON/OFF
68
APPENDIX A — DISPLAY TABLES (cont)
Temperature Mode and Sub-Mode Directory
SUB-MODE
UNIT
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
ENTERING AND LEAVING UNIT TEMPERATURES
RAT
SAT
OAT
SPT
SCT.D
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x ΔF
Return Air Temperature
Supply Air Temperature
Outside Air Temperature
Space Temperature
Circuit SCT Difference
TEMPERATURES CIRCUIT A
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Discharge Gas Temp
Suction Superheat Temp
TEMPERATURES CIRCUIT B
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Suction Superheat Temp
SCT.A
SST.A
RGT.A
D.GAS
SH.A
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x ΔF
CIR.A
CIR.B
SCT.B
SST.B
RGT.B
SH.B
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x ΔF
Pressures Mode and Sub-Mode Directory
SUB-MODE
PRC.A
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
PRESSURES CIRCUIT A
XXX.XPSIG
XXX.XPSIG
DP.A
SP.A
Discharge Pressure
Suction Pressure
PRESSURES CIRCUIT B
PRC.B
DP.B
SP.B
XXX.XPSIG
XXX.XPSIG
Discharge Pressure
Suction Pressure
Set Points Mode and Sub-Mode Directory
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COOLING SET POINTS
Cooling Set Point 1
RANGE
COMMENT
CSP.1
CSP.2
SPS.P
SPT.O
STP.O
P.CAP
LCON
HCON
LCOF
xxx.x °F
xxx.x °F
xxx.x °F
xx.x ΔF
xxx.x °F
XXX
xx.x ΔF
xx.x ΔF
xx.x ΔF
40 to 80
40 to 80
65 to 80
Default: 55 F
Default: 50 F
Default: 78 F
Cooling Set Point 2
Space T Cool Set Point
Space Temperature Offset
Space T SP Plus Offset
Percent CAP Requested
Lo Cool On Set Point
HI Cool On Set Point
Lo Cool Off Set Point
HEAD PRESSURE SET POINTS
Head Set Point ON
COOL
–1 to 2
0.5 to 20
0.5 to 2
Default: 1
Default: 3
Default: 0.5
H.SP
HSPF
F.ON
F.OFF
F.DLT
F.TME
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
XX.X
85 to 120
45 to 90
Default: 110 F
Default: 72 F
Head Set Point OFF
Fan On Set Point
Fan Off Set Point
Fan Stage Delta
Fan Delta Active Time
HEAD
0 to 50
0 to 300
XXX
69
APPENDIX A — DISPLAY TABLES (cont)
Inputs Mode and Sub-Mode Directory
SUB-MODE
GEN.I
ITEM
DISPLAY
ITEM DESCRIPTION
GENERAL INPUTS
Start/Stop Switch
COMMENT
STST
IDFA
Y.1
Y.2
IDFB
Y.3
Y.4
DLS1
DLS2
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Indoor Fan Status-CIRA
Y1 Thermostat Input
Y2 Thermostat Input
Indoor Fan Status-CIRB
Y3 Thermostat Input
Y4 Thermostat Input
Demand Limit Switch 1
Demand Limit Switch 2
CIRCUIT INPUTS
FKA1
FKA2
FKA3
HPSA
FKB1
FKB2
FKB3
HPSB
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Compressor A1 Feedback
Compressor A2 Feedback
Compressor A3 Feedback
High Pressure Switch A
Compressor B1 Feedback
Compressor B2 Feedback
Compressor B3 Feedback
High Pressure Switch B
CRCT
4-20
4-20 MA INPUTS
DMND
RSET
CL.MA
XX.X
XX.X
XX.X
4-20 ma Demand Signal
4-20 ma Reset Signal
4-20 Cooling Demand
Outputs Mode and Sub-Mode Directory
SUB-MODE
GEN.O
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
GENERAL OUTPUTS
FAN1
FAN2
FAN3
FAN4
FAN5
MLV.R
V.HPA
V.HPB
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
XXX
Fan 1 Relay
Fan 2 Relay
Fan 3 Relay
Fan 4 Relay
Fan 5 Relay
Minimum Load Valve Relay
Var Head Press Out Cir A
Var Head Press Out Cir B
XXX
OUTPUTS CIRCUIT A
CC.A1
DPE.R
D.SOL
CC.A2
CC.A3
LSV.A
ON/OFF
XXX
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Compressor A1 Relay
Comp A1 Load Percent
Digital Scroll Solenoid
Compressor A2 Relay
Compressor A3 Relay
Liquid Line Solenoid A
CIR.A
CIR.B
OUTPUTS CIRCUIT B
CC.B1
CC.B2
CC.B3
LSV.B
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Liquid Line Solenoid B
70
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory
SUB-MODE
DISP
ITEM
DISPLAY
ITEM DESCRIPTION
DISPLAY CONFIGURATION
Test Display LEDs
COMMENT
TEST
METR
ON/OFF
ON/OFF
Metric Display
Off = English On = Metric
Default: 0
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
LANG
X
Language Selection
PAS.E
PASS
ENBL/DSBL
XXXX
Password Enable
Service Password
UNIT CONFIGURATION
Unit Size
SIZE
NCKT
SZ.A1
SZ.A2
SZ.A3
SZ.B1
SZ.B2
SZ.B3
FAN.S
A1.TY
MAX.T
X
XX
XX
XX
XX
XX
XX
XX
YES/NO
XX
Number of Refrigerant Circuits
Compressor A1 Size
Compressor A2 Size
Compressor A3 Size
Compressor B1 Size
Compressor B2 Size
Compressor B3 Size
Fan Sequence Number
Compressor A1 Digital
Maximum A1 Unload Time
CCN NETWORK CONFIGS
UNIT
Default: 1
CCNA
CCNB
XXX
XXX
CCN Address
Range: 0 to 239
Default: 1
Range: 0 to 239
CCN Bus Number
CCN
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400
BAUD
X
CCN Baud Rate
UNIT OPTIONS 1 HARDWARE
Minimum Load Valve Select
CSB Boards Enable
MLV.S
CSB.E
SPT.S
SPOS
SPOR
YES/NO
ENBL/DSBL
ENBL/DSBL
ENBL/DSBL
XX
Space Temp Sensor
Space Temp Offset Enable
Space Temp Offset Range 1 to 10
Default: 0
0 = 5 K
1 = 10 K
2 = None
Default: 0
0 = 5 K
1 = 10 K
2 = None
OPT1
RAT.T
X
RAT Thermistor Type
SAT Thermistor Type
SAT.T
EMM
X
YES/NO
EMM Module installed
UNIT OPTIONS 2 CONTROLS
Default: 4
1 = VAV
2 = Invalid
3 = TSTAT MULTI
4 = TSTAT 2 STG
5 = SPT MULTI
6 = Invalid
C.TYP
X
Machine Control Type
7 = PCT CAP
8 = DUAL TSTAT
9 = VAV SETPOINT
Default: 0
0 = Enable/Off/Remote Switch
1 = Occupancy
OPT2
CTRL
LOAD
X
X
Control Method
2 = CCN Control
Default: 1
1 = Equal
2 = Staged
Loading Sequence Select
Default: 1
1 = Automatic
LLCS
DELY
X
Lead/Lag Circuit Select
Minutes Off Time
2 = Circuit A Leads
3 = Circuit B Leads
Default: 0
Range: 0 to 15 Minutes
XX
71
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
M.MST
ITEM
DISPLAY
ITEM DESCRIPTION
MOTORMASTER
COMMENT
MMR.S
P.GAN
YES/NO
XX
Motormaster Select
Default: 1
Range: 1 to 4
Default: 0.1
Range: -20 to 20
Head Pressure P Gain
I.GAN
XX.X
Head Pressure I Gain
Default: 0.0
Range: -20 to 20
D.GAN
MIN.S
XX.X
XX
Head Pressure D Gain
Minimum Fan Speed
RESET COOL TEMP
Default: 0
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Temperature
4 = Space Temperature
CRST
X
Cooling Reset Type
Default: 0.0 ΔF
MA.DG
RM.NO
RM.F
XX.XΔF
XXX.X °F
XXX.X °F
XX.X °F
XXX.XΔF
XXX.XΔF
XX.X °F
4-20 - Degrees Reset
Remote - No Reset Temp
Remote - Full Reset Temp
Remote - Degrees Reset
Return - No Reset Temp
Return - Full Reset Temp
Return - Degrees Reset
Range: -30 to 30 ΔF
Default: 125 F
Range: 0º to125 F
Default: 0 F
Range: 0º to125 F
Default: 0.0 ΔF
Range: -30 to 30 ΔF
Default: 10.0 ΔF
Range: 0º to125 F
Default: 0 ΔF
Range: 0º to125 F
Default: 0.0 ΔF
Range: -30 to 30 ΔF
RM.DG
RT.NO
RT.F
RSET
RT.DG
Default: 0
0 = None
DMDC
X
Demand Limit Select
1 = Switch
2 - 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
DM20
SHNM
SHDL
SHTM
DLS1
DLS2
XXX%
XXX
Demand Limit at 20 mA
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Switch 1
Demand Limit Switch 2
Range: 0 to 100%
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
XXX%
XXX
Default: 60 minutes
Range: 0 to 120 minutes
Default: 80%
Range: 0 to 100%
Default: 50%
Range: 0 to 100%
XXX%
XXX%
SETPOINT AND RAMP LOAD
Ramp Load Select
RL.S
ENBL/DSBL
ENBL/DSBL
Default: Enable
Default: 1.0
Range: 0.3 to 2
Default: 1
Range: 1 to 99
Default: 1
Range: 1 to 4
CRMP
Cooling Ramp Loading
Schedule Number
SLCT
SCHD
Z.GN
XX
X.X
Deadband Multiplier
SERVICE CONFIGURATION
Enable Compressor A1
Enable Compressor A2
Enable Compressor A3
Enable Compressor B1
Enable Compressor B2
Enable Compressor B3
Enable Compressor FBack
Reverse Rotation Enable
EN.A1
EN.A2
EN.A3
EN.B1
EN.B2
EN.B3
EN.FB
REV.R
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
SERV
BCST
BROADCAST CONFIGURATION
CCN Time/Date Broadcast
CCN OAT Broadcast
T.D.B
OAT.B
G.S.B
BC.AK
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Global Schedule Broadcst
CCN Broadcast Ack'er
72
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory
SUB-MODE
TIME
ITEM
DISPLAY
ITEM DESCRIPTION
TIME OF DAY
Hour and Minute
COMMENT
HH.MM
XX.XX
Military (00:00 - 23:59)
MONTH, DATE, DAY, AND YEAR
1 - 12 (1 = January,
2 = February, etc.)
Range: 01 -31
1 - 7 (1 = Sunday,
2 = Monday, etc.)
MNTH
DOM
DAY
XX
XX
Month of Year
DATE
Day of Month
Day of Week
X
YEAR
XXXX
Year of Century
DAYLIGHT SAVINGS TIME
STR.M
STR.W
STR.D
MIN.A
STP.M
STP.W
STP.D
MIN.S
XX
X
X
XX
XX
XX
XX
XX
Month
Week
Day
Default: 4 Range 1- 12
Default: 1 Range 1- 5
Default: 7 Range 1- 7
Default: 60 Range 0 - 99
Default: 10 Range 1- 12
Default: 5 Range 1- 5
Default: 7 Range 1- 7
Default: 60 Range 0 - 99
DST
Minutes to Add
Month
Week
Day
Minutes to Subtract
HOL.L
HD.01
LOCAL HOLIDAY SCHEDULES
HOLIDAY SCHEDULE 01
MON
DAY
LEN
XX
XX
XX
Holiday Start Month
Start Day
Duration (days)
HOLIDAY SCHEDULE 02
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
HD.02
HD.03
HD.04
HD.05
HD.06
HD.07
HD.08
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 03
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 04
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 05
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 06
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 07
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 08
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
73
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE
HD.09
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
HOLIDAY SCHEDULE 09
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
HOLIDAY SCHEDULE 10
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
HD.10
HD.11
HD.12
HD.13
HD.14
HD.15
HD.16
HD.17
HD.18
HD.19
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 11
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 12
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 13
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 14
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 15
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 16
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 17
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 18
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 19
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
74
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE
HD.20
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
HOLIDAY SCHEDULE 20
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
HOLIDAY SCHEDULE 21
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
HD.21
HD.22
HD.23
HD.24
HD.25
HD.26
HD.27
HD.28
HD.29
HD.30
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 22
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 23
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 24
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 25
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 26
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 27
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 28
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 29
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 30
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
75
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE
SCH.N
ITEM
DISPLAY
ITEM DESCRIPTION
Schedule Number 0
COMMENT
SCH.L
LOCAL OCCUPANCY SCHEDULE
OCCUPANCY PERIOD 1
OCC.1
UNC.1
MON.1
TUE.1
WED.1
THU.1
FRI.1
SAT.1
SUN.1
HOL.1
XX:XX
XX:XX
Period Occupied Time
Military (00:00 - 23:59)
Military (00:00 - 23:59)
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
PER.1
PER.2
PER.3
PER.4
PER.5
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 2
XX:XX
XX:XX
OCC.2
UNC.2
MON.2
TUE.2
WED.2
THU.2
FRI.2
SAT.2
SUN.2
HOL.2
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 3
XX:XX
XX:XX
OCC.3
UNC.3
MON.3
TUE.3
WED.3
THU.3
FRI.3
SAT.3
SUN.3
HOL.3
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 4
XX:XX
XX:XX
OCC.4
UNC.4
MON.4
TUE.4
WED.4
THU.4
FRI.4
SAT.4
SUN.4
HOL.4
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 5
XX:XX
XX:XX
OCC.5
UNC.5
MON.5
TUE.5
WED.5
THU.5
FRI.5
SAT.5
SUN.5
HOL.5
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Saturday In Period
Sunday In Period
Holiday In Period
76
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
OCCUPANCY PERIOD 6
OCC.6
UNC.6
MON.6
TUE.6
WED.6
THU.6
FRI.6
SAT.6
SUN.6
HOL.6
XX:XX
XX:XX
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
PER.6
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 7
OCC.7
UNC.7
MON.7
TUE.7
WED.7
THU.7
FRI.7
SAT.7
SUN.7
HOL.7
XX:XX
XX:XX
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
PER.7
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 8
OCC.8
UNC.8
MON.8
TUE.8
WED.8
THU.8
FRI.8
SAT.8
SUN.8
HOL.8
XX:XX
XX:XX
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
PER.8
Saturday In Period
Sunday In Period
Holiday In Period
SCHEDULE OVERRIDE
OVR.T
OVR.L
SPT.O
T.OVR
X
X
Timed Override Hours
Override Time Limit
Space Temperature Offset
Timed Override
Default: 0 Range 0-4 hours
Default: 0 Range 0-4 hours
OVR
XX.X
YES/NO
User Entry
77
APPENDIX A — DISPLAY TABLES (cont)
Operating Mode and Sub-Mode Directory
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
MODES CONTROLLING UNIT
Ramp Load Limited
COMMENT
MD05
MD06
MD09
MD10
MD14
MD15
MD17
MD18
MDTG
MD21
MD22
MD23
MD25
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Timed Override in effect
Slow Change Override
Minimum OFF time active
Temperature Reset
Demand Limited
MODE
Low Temperature Cooling
High Temperature Cooling
Time Guard Active
High SCT Circuit A
High SCT Circuit B
Minimum Comp. On Time
Low Sound Mode
TASK STATES
0 = OFF
1 = ALLOW TO RUN
2 = PRE START
3 = STARTING
4 = RUNNING
TKCA
TKCB
X
X
Circuit A State
Circuit B State
5 = STOPPING
0 = OFF
1 = ALLOW TO RUN
2 = PRE START
3 = STARTING
4 = RUNNING
TSKS
5 = STOPPING
0 = OFF
1 = PRE-START DETERMINATION
2 = PRE START
TKFA
TKFB
X
X
Circuit A Fan State
Circuit B Fan State
3 = NORMAL
4 = STOPPING
0 = OFF
1 = PRE-START DETERMINATION
2 = PRE START
3 = NORMAL
4 = STOPPING
Alarms Mode and Sub-Mode Directory
SUB-MODE
CRNT
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
CURRENTLY ACTIVE ALARMS
AXXX
TXXX
PXXX
Alarms are hown as AXXX
Alerts are shown as TXXX
Current Alarms 1-25
RCRN
YES/NO
Reset All Current Alarms
ALARM HISTORY
AXXX
TXXX
PXXX
HIST
Alarms are shown as AXXX
Alerts are shown as TXXX
Alarm History 1-20
78
APPENDIX B — CCN TABLES
Status Tables
DESCRIPTION
TSTAT_IN (Thermostat Input)
Indoor Fan Status-CIRA
Y1 Thermostat Input
VALUE
UNITS
POINT NAME
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
IDFA_FS
Y1
Y2
IDFB_FS
Y3
Y2 Thermostat Input
Indoor Fan Status-CIRB
Y3 Thermostat Input
Y4 Thermostat Input
Y4
A_UNIT (General Unit Parameters)
Control Mode
10-char ASCII
N
STAT
SPTMODE
OCC
Space Temp Control Mode
Occupied
No/Yes
CCN Chiller
Alarm State
4-20 Cooling Demand
Active Demand Limit
Override Modes in Effect
Percent Total Capacity
Requested Stage
stop/start
6-char ASCII
NN.n
CHIL_S_S
ALM
COOL_MA
DEM_LIM
MODE
milliAmps
%
NNN
No/Yes
NNN
NN
%
CAP_T
STAGE
Active Set Point
Control Point
Return Air Temperature
Supply Air Temperature
Emergency Stop
NNN.n
NNN.n
NNN.n
NNN.n
degF
degF
degF
degF
SP
CTRL_PNT
RETURN_T
SUPPLY_T
EMSTOP
MIN_LEFT
Enable/EMStop
5-char ASCII
Minutes Left for Start
CIRCA_AN (Circuit A Analog Parameters)
Percent Total Capacity
Percent Available Capacity
Discharge Pressure
NNN
NNN
%
%
CAPA_T
CAPA_A
DP_A
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
PSIG
PSIG
degF
degF
degF
degF
%
degF
degF
deltaF
Suction Pressure
Head Set Point ON
Head Set Point OFF
SP_A
HSP_ON
HSP_OFF
SCTA
SSTA
VHPA_ACT
RGTA
Saturated Condensing Temperature
Saturated Suction Temperature
Variable Head Press Out Circuit A
Compressor Return Gas Temperature
Discharge Gas Temperature
Suction Superheat Temperature
CIRCADIO (Circuit A Discrete Inputs/Outputs)
CIRC.A DISCRETE OUTPUTS
Compressor A1 Relay
DIGCMPDT
SH_A
Off/On
NNN.n
Off/On
Off/On
Off/On
Off/On
K_A1_RLY
DIGITAL%
K_A2_RLY
K_A3_RLY
MLV_RLY
LLSV_A
Comp A1 Load Percent
Compressor A2 Relay
Compressor A3 Relay
Minimum Load Valve Relay
Liquid Line Solenoid A
CIRC.A DISCRETE INPUTS
Compressor A1 Feedback
Compressor A2 Feedback
Compressor A3 Feedback
High Pressure Switch A
%
Off/On
Off/On
Off/On
K_A1_FBK
K_A2_FBK
K_A3_FBK
HPSA
Open/Close
79
APPENDIX B — CCN TABLES (cont)
Status Tables (cont)
DESCRIPTION
CIRCB_AN (Circuit B Analog Parameters)
Percent Total Capacity
Percent Available Capacity
Discharge Pressure
VALUE
UNITS
POINT NAME
NNN
NNN
%
%
CAPB_T
CAPB_A
DP_B
SP_B
SCTB
SSTB
VHPB_ACT
RGTB
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
PSIG
PSIG
degF
degF
%
Suction Pressure
Saturated Condensing Temperature
Saturated Suction Temperature
Variable Head Press Out Circuit B
Compressor Return Gas Temperature
Suction Superheat Temperature
CIRCBDIO (Circuit B Discrete Inputs/Outputs)
CIRC.B DISCRETE OUTPUTS
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Minimum Load Valve Relay
Liquid Line Solenoid B
CIRC.B DISCRETE INPUTS
Compressor B1 Feedback
Compressor B2 Feedback
Compressor B3 Feedback
High Pressure Switch B
OPTIONS (Unit Parameters)
FANS
degF
deltaF
SH_B
Off/On
Off/On
Off/On
Off/On
Off/On
K_B1_RLY
K_B2_RLY
K_B3_RLY
MLV_RLY
LLSV_B
Off/On
Off/On
Off/On
K_B1_FBK
K_B2_FBK
K_B3_FBK
HPSB
Open/Close
Fan Stage Circuit A
Fan Stage Circuit B
NNN
NNN
FANSTGEA
FANSTGEB
FAN_1
FAN_2
FAN_3
Fan 1 Relay
Fan 2 Relay
Fan 3 Relay
Fan 4 Relay
Off/On
Off/On
Off/On
Off/On
Off/On
FAN_4
FAN_5
Fan 5 Relay
UNIT ANALOG VALUES
Return Air Temperature
Supply Air Temperature
Circuit SCT Difference
TEMPERATURE RESET
4-20 ma Reset Signal
NNN.n
NNN.n
NNN.n
degF
degF
deltaF
RETURN_T
SUPPLY_T
SCTDELTA
NN.n
NNN.n
NNN.n
milliAmps
degF
degF
RST_MA
OAT
SPT
Outside Air Temperature
Space Temperature
DEMAND LIMIT
4-20 ma Demand Signal
Demand Limit Switch 1
Demand Limit Switch 2
CCN Loadshed Signal
MISCELLANEOUS
NN.n
Off/On
Off/On
N
milliAmps
LMT_MA
DMD_SW1
DMD_SW2
DL_STAT
Supply Air Set Point
NNN.n
degF
SAT_SP
80
APPENDIX B — CCN TABLES (cont)
CCN Configuration Tables
DESCRIPTION
UNIT (Unit Configuration)
VALUE
UNITS
POINT NAME
Unit Size
Number of Refrig Ckts
Compressor A1 Size
Compressor A2 Size
Compressor A3 Size
Compressor B1 Size
Compressor B2 Size
Compressor B3 Size
NNN
N
tons
SIZE
NUMCKTS
SIZE_A1
SIZE_A2
SIZE_A3
SIZE_B1
SIZE_B2
SIZE_B3
NNN
NNN
NNN
NNN
NNN
NNN
N
tons
tons
tons
tons
tons
tons
Fan Sequence Number
Compressor A1 Digital
Maximum A1 Unload Time
OPTIONS1 (Options 1 Configuration)
Motormaster Select
FAN_TYPE
CPA1TYPE
MAXULTME
No/Yes
NN
secs
No/Yes
No/Yes
Disable/Enable
Disable/Enable
Disable/Enable
NN
MM_SLCT
MLV_FLG
CSB_ENA
SPTSENS
SPTOSENS
SPTO_RNG
RATTYPE
SATTYPE
EMM_BRD
Minimum Load Valve Select
CSB Boards Enable
Space Temperature Sensor
Space Temperature Offset Enable
Space Temperature Offset Range
RAT Thermistor Type
deltaF
N
N
SAT Thermistor Type
EMM Module Installed
No/Yes
OPTIONS2 (Options 2 Configuration)
Machine Control Type
N
N
N
CTRLTYPE
CONTROL
SEQ_TYPE
LEAD_TYP
RAMP_EBL
DELAY
Control Method
Loading Sequence Select
Lead/Lag Circuit Select
Ramp Load Select
N
Disable/Enable
NN
Minutes Off Time
mins
Deadband Multiplier
N.n
Z_GAIN
SCHEDOVR (Timed Override Set Up)
Schedule Number
NN
N
N
SCHEDNUM
OTL
OVR_EXT
TIMEOVER
Override Time Limit
Timed Override Hours
hours
hours
Timed Override
No/Yes
RESETCON (Temperature Reset and Demand Limit)
COOLING RESET
Cooling Reset Type
4-20 MA RESET
4-20 - Degrees Reset
N
CRST_TYP
420_DEG
NNN.n
deltaF
REMOTE RESET
Remote - No Reset Temperature
Remote - Full Reset Temperature
Remote - Degrees Reset
RETURN TEMPERATURE RESET
Return - No Reset Temperature
Return - Full Reset Temperature
Return - Degrees Reset
DEMAND LIMIT
NNN.n
NNN.n
NNN.n
degF
degF
deltaF
REM_NO
REM_FULL
REM_DEG
NNN.n
NNN.n
NNN.n
deltaF
deltaF
deltaF
RTN_NO
RTN_FULL
RTN_DEG
Demand Limit Select
N
NNN
NN
DMD_CTRL
DMT20MA
SHED_NUM
SHED_DEL
SHED_TIM
DLSWSP1
DLSWSP2
Demand Limit at 20 mA
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Switch 1
Demand Limit Switch 2
%
NN
%
mins
%
NNN
NNN
NNN
%
81
APPENDIX B — CCN TABLES (cont)
CCN Configuration Tables (cont)
DESCRIPTION
DISPLAY (Marquee Display Set Up)
Service Password
VALUE
UNITS
POINT NAME
NNNN
Disable/Enable
Off/On
PASSWORD
PASS_EBL
DISPUNIT
Password Enable
Metric Display
Language Selection
HPA (Head Pressure)
SCT Delta for Compressor A1
SCT Delta for Compressor A2
HPB (Head Pressure)
SCT Delta for Comp B1
SCT Delta for Comp B2
SERVICE
N
LANGUAGE
NNN.n
NNN.n
deltaF
deltaF
A1SCTDT
A2SCTDT
NNN.n
NNN.n
deltaF
deltaF
B1SCTDT
B2SCTDT
Enable Compressor A1
Enable Compressor A2
Enable Compressor A3
Enable Compressor B1
Enable Compressor B2
Enable Compressor B3
SET POINT
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
ENABLEA1
ENABLEA2
ENABLEA3
ENABLEB1
ENABLEB2
ENABLEB3
COOLING
Cooling Set Point 1
Cooling Set Point 2
NNN.n
NNN.n
NNN.n
NN.n
NN.n
NN.n
degF
degF
degF
deltaF
degF
deltaF
deltaF
deltaF
CSP1
CSP2
SPT_SP
SPTO
SPSP_PO
DMDLCON
DMDHCON
DMDLCOFF
Space T Cool Set Point
Space Temperature Offset
Space T SP Plus Offset
Lo Cool On Set Point
HI Cool On Set Point
Lo Cool Off Set Point
RAMP LOADING
NN.n
NN.n
Cooling Ramp Loading
Head Set Point ON
Head Set Point OFF
Fan On Set Point
Fan Off Set Point
Fan Stage Delta
Fan Delta Active Time
Unload Time Threshold
N.n
CRAMP
HSP_ON
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN
degF
degF
degF
degF
deltaF
secs
HSP_OFF
FANONSP
FANOFFSP
FSTGDLTA
FANDLTTM
UTTHRESH
NN
secs
CCN Maintenance Tables
DESCRIPTION
STRTHOUR (Maintenance Display)
Machine Operating Hours
Machine Starts
VALUE
UNITS
POINT NAME
NNNNNN
NNNNNN
NNNNNN
NNNNNN.n
NNNNNN.n
NNNNNN.n
NNNNNN
NNNNNN.n
NNNNNN.n
NNNNNN.n
NNNNNN
NNNNNN
NNNNNN
NNNNNN
NNNNNN
NNNNNN
NNNNNN
NNNNNN
hours
HR_MACH
CY_MACH
HR_CIRA
HR_A1
HR_A2
HR_A3
HR_CIRB
HR_B1
HR_B2
HR_B3
CY_CIRA
CY_A1
CY_A2
CY_A3
CY_CIRB
CY_B1
CY_B2
Circuit A Run Hours
hours
hours
hours
hours
hours
hours
hours
hours
Compressor A1 Run Hours
Compressor A2 Run Hours
Compressor A3 Run Hours
Circuit B Run Hours
Compressor B1 Run Hours
Compressor B2 Run Hours
Compressor B3 Run Hours
Circuit A Starts
Compressor A1 Starts
Compressor A2 Starts
Compressor A3 Starts
Circuit B Starts
Compressor B1 Starts
Compressor B2 Starts
Compressor B3 Starts
CY_B3
82
APPENDIX B — CCN TABLES (cont)
CCN Maintenance Tables (cont)
DESCRIPTION
CURRMODS (Maintenance Display)
Ramp Load Limited
Timed Override in effect
Slow Change Override
Minimum OFF time active
Temperature Reset
Demand Limited
VALUE
UNITS
POINT NAME
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
MODE_5
MODE_6
MODE_9
MODE_10
MODE_14
MODE_15
MODE_17
MODE_18
MODE_21
MODE_22
MODE_23
MODE_25
MODE_TG
Low Temperature Cooling
High Temperature Cooling
High SCT Circuit A
High SCT Circuit B
Minimum Comp. On Time
Low Sound Mode
Time Guard Active
Alarms (Maintenance Display)
Active Alarm #1
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
4-char ASCII
ALARM01C
ALARM02C
ALARM03C
ALARM04C
ALARM05C
ALARM06C
ALARM07C
ALARM08C
ALARM09C
ALARM10C
ALARM11C
ALARM12C
ALARM13C
ALARM14C
ALARM15C
ALARM16C
ALARM17C
ALARM18C
ALARM19C
ALARM20C
ALARM21C
ALARM22C
ALARM23C
ALARM24C
ALARM25C
Active Alarm #2
Active Alarm #3
Active Alarm #4
Active Alarm #5
Active Alarm #6
Active Alarm #7
Active Alarm #8
Active Alarm #9
Active Alarm #10
Active Alarm #11
Active Alarm #12
Active Alarm #13
Active Alarm #14
Active Alarm #15
Active Alarm #16
Active Alarm #17
Active Alarm #18
Active Alarm #19
Active Alarm #20
Active Alarm #21
Active Alarm #22
Active Alarm #23
Active Alarm #24
Active Alarm #25
Versions (Software Versions)
MBB CESR131279-
AUX CESR131333-
CXB CESR131173-
EMM CESR131174-
MARQUEE CESR131171-
NAVIGATOR CESR130227-
LOADFACT (Maintenance Display)
Load/Unload Factor
Control Point
Return Air Temperature
Supply Air Temperature
Ramp Load Limited
Slow Change Override
Low Temperature Cooling
High Temperature Cooling
Minimum Comp. On Time
LEARNFNS (Maintenance Display)
SCT Delta for Comp A1
SCT Delta for Comp A2
SCT Delta for Comp B1
SCT Delta for Comp B2
5-char ASCII
5-char ASCII
5-char ASCII
5-char ASCII
5-char ASCII
5-char ASCII
NNN
SMZ
NNN.n
NNN.n
NNN.n
Off/On
Off/On
Off/On
Off/On
Off/On
degF
degF
degF
CTRL_PNT
RETURN_T
SUPPLY_T
MODE_5
MODE_9
MODE_17
MODE_18
MODE_23
NNN.n
NNN.n
NNN.n
NNN.n
deltaF
deltaF
deltaF
deltaF
A1SCTDT
A2SCTDT
B1SCTDT
B2SCTDT
83
APPENDIX B — CCN TABLES (cont)
CCN Maintenance Tables (cont)
DESCRIPTION
PM-COIL (Maintenance Display)
Coil Cleaning Srvc Inter
Coil Service Countdown
Coil Cleaning Maint.Done
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
TESTMODE (Maintenance Display)
Service Test Mode
VALUE
UNITS
POINT NAME
NNNNN
NNNNN
No/Yes
15-char ASCII
15-char ASCII
15-char ASCII
15-char ASCII
15-char ASCII
hours
hours
SI_COIL
CL_CDOWN
CL_MAINT
COIL_PM0
COIL_PM1
COIL_PM2
COIL_PM3
COIL_PM4
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
NN
NET_CTRL
S_A1_RLY
S_A2_RLY
S_A3_RLY
S_B1_RLY
S_B2_RLY
S_B3_RLY
S_FAN_1
S_FAN_2
S_FAN_3
S_FAN_4
S_FAN_5
S_LLSV_A
S_LLSV_B
S_A1ULTM
S_MLV
Compressor A1 Relay
Compressor A2 Relay
Compressor A3 Relay
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Fan 1 Relay
Fan 2 Relay
Fan 3 Relay
Fan 4 Relay
Fan 5 Relay
Liquid Line Solenoid A
Liquid Line Solenoid B
Comp A1 Unload Time
Minimum Load Valve Relay
Remote Alarm Relay
secs
Off/On
Off/On
S_ALM
RUNTEST (Maintenance Display)
Percent Total Capacity
Percent Available Capacity
Discharge Pressure
NNN
NNN
%
%
CAPA_T
CAPA_A
DP_A
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
NNN
PSIG
PSIG
degF
degF
degF
degF
degF
degF
deltaF
Suction Pressure
Head Set Point ON
Head Set Point OFF
SP_A
HSP_ON
HSP_OFF
SCTA
SSTA
RGTA
Saturated Condensing Temperature
Saturated Suction Temperature
Compr Return Gas Temperature
Discharge Gas Temperature
Suction Superheat Temperature
Compressor A1 Relay
Compressor A2 Relay
Compressor A3 Relay
Minimum Load Valve Relay
Compressor A1 Feedback
Compressor A2 Feedback
Compressor A3 Feedback
Percent Total Capacity
Percent Available Capacity
Discharge Pressure
DIGCMPDT
SH_A
K_A1_RLY
K_A2_RLY
K_A3_RLY
MLV_RLY
K_A1_FBK
K_A2_FBK
K_A3_FBK
CAPB_T
CAPB_A
DP_B
%
%
NNN
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
NNN.n
Off/On
Off/On
Off/On
Off/On
PSIG
PSIG
degF
degF
degF
degF
degF
deltaF
Suction Pressure
Head Set Point ON
Head Set Point OFF
SP_B
HSP_ON
HSP_OFF
SCTB
Saturated Condensing Temperature
Saturated Suction Temperature
Compr Return Gas Temperature
Suction Superheat Temperature
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Minimum Load Valve Relay
SSTB
RGTB
SH_B
K_B1_RLY
K_B2_RLY
K_B3_RLY
MLV_RLY
84
Copyright 2009 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380003-01
Printed in U.S.A.
Form 38AP-1T
Pg 86
210
11-09
Replaces: New
START-UP CHECKLIST FOR 38AP SPLIT SYSTEM CONDENSING UNIT
(Remove and use for Job File)
I. Project Information
JOB NAME ______________________________________________________________________________
ADDRESS _______________________________________________________________________________
CITY ____________________________________________ STATE _______________ ZIP______________
INSTALLING CONTRACTOR ________________________________________________________________
SALES OFFICE ___________________________________________________________________________
START-UP PERFORMED BY ________________________________________________________________
Design Information
SUPPLY AIR
RETURN AIR
COIL SIZE
(sq ft)
COIL
CIRCUITING
CAPACITY
OAT
CFM
TEMPERATURE TEMPERATURE
ELEVATION DELTA
BETWEEN
INDOOR/OUTDOOR
SUCTION LINE
DIAMETER
LIQUID LINE
DIAMETER
DOUBLE RISER
CONTROL
TYPE (1-9)
LINE LENGTH
(Y/N)
CV/VAV
UNIT MODEL ______________________________ SERIAL ________________________________
II. Preliminary Equipment Check
IS THERE ANY PHYSICAL DAMAGE?
YES NO
DESCRIPTION ____________________________________________________________________________
________________________________________________________________________________________
1. UNIT IS INSTALLED LEVEL AS PER THE INSTALLATION INSTRUCTIONS.
2. POWER SUPPLY AGREES WITH THE UNIT NAMEPLATE.
3. ELECTRICAL POWER WIRING IS INSTALLED PROPERLY.
4. UNIT IS PROPERLY GROUNDED.
YES NO
YES NO
YES NO
YES NO
5. ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY. YES NO
6. ALL TERMINALS ARE TIGHT.
YES NO
YES NO
YES NO
YES NO
YES NO
YES NO
YES NO
7. ALL PLUG ASSEMBLIES ARE TIGHT.
8. ALL CABLES AND THERMISTORS HAVE BEEN INSPECTED FOR CROSSED WIRES.
9. ALL THERMISTORS ARE FULLY INSERTED INTO WELLS.
10. MOTORMASTER IS INSTALLED ON FAN 1.
11. SENSORS (RAT, SAT, SPT) FOR CONTROL TYPES 3, 4, AND 5 ARE INSTALLED.
12. LONG LINE OPTION KIT IS INSTALLED, IF NEED.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380003-01 Printed in U.S.A. Form 38AP-1T Pg CL-1 210 11-09 Replaces: New
Refrigeration System Check
1. ALL SERVICE VALVES ARE OPEN.
YES NO
YES NO
YES NO
YES NO
YES NO
YES NO
YES NO
YES NO
2. ONLY BLEED TXV(S) ARE INSTALLED.
3. ALL PIPING IS CONNECTED PROPERLY.
4. FILTER DRIERS AND SIGHT GLASSES ARE INSTALLED NEAR THE TXV(S).
5. THE SYSTEM HAS BEEN EVACUATED.
6. THE SYSTEM HAS BEEN CHARGED WITH THE APPROPRIATE INITIAL CHARGE.
7. EVAPORATOR FANS ARE TURNING IN THE CORRECT DIRECTION.
8. EVAPORATOR FAN STATUS SWITCH IS OPERATIONAL.
9. CRANKCASE HEATERS ARE OPERATIONAL AND HAVE BEEN ENERGIZED TO
REMOVE ANY LIQUID FROM THE COMPRESSORS.
YES NO
YES NO
YES NO
10. WATER HAS BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE.
11. THE PROPER FILTERS HAVE BEEN INSTALLED.
12. THE FAN AND MOTOR PULLEYS OF THE INDOOR FAN HAVE BEEN CHAECKED
FOR PROPER ALIGNMENT
YES NO
YES NO
13. THE INDOOR FAN BELTS HAVE THE PROPER TENSION.
14. THE CORRECT FAN ROTATION ON BOTH INDOOR AND OUTDOOR UNITS
HAS BEEND VERIFIED.
YES NO
YES NO
YES NO
15. THE LIQUID SOLENOID VALVES, IF INSTALLED, ARE NEAR THE EVAPORATOR.
16. THE PIPING HAS BEEN CHECKED FOR LEAKS WITH A LEAK DETECTOR.
LOCATE, REPAIR, AND REPORT ANY LEAKS________________________________________________
17. OIL IS VISABLE APPROXIMATELY 1/2 WAY IN THE SIGHT GLASS(ES)
OF THE COMPRESSOR.
YES NO
RECORD THE OIL LEVEL(S) ______________________________________________________________
III. Unit Start-Up
1. COMPRESSOR OIL LEVEL IS CORRECT.
YES NO
YES NO
YES NO
YES NO
YES NO
2. VERIFY COMPRESSOR MOUNTING BOLT TORQUE IS 10-14 FT-LB. (13.5-18.9 N-M).
3. LEAK CHECK UNIT. LOCATE, REPAIR AND REPORT ANY REFRIGERANT LEAKS.
4. VOLTAGE IS WITHIN UNIT NAMEPLATE RANGE.
5. CONTROL TRANSFORMER PRIMARY CONNECTION SET FOR PROPER VOLTAGE.
6. CONTROL TRANSFORMER SECONDARY VOLTAGE =
v
7. CHECK VOLTAGE IMBALANCE:
AVERAGE VOLTAGE =
A-B
A-C
(A-B + A-C + B-C)/3
B-C
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
VOLTAGE IMBALANCE = ____________% (MAX. DEVIATION/AVERAGE VOLTAGE) X 100
VOLTAGE IMBALANCE LESS THAN 2%.
(DO NOT START UNIT IF VOLTAGE IMBALANCE IS GREATER THAN 2%.
CONTACT LOCAL UTILITY FOR ASSISTANCE.)
YES NO
YES NO
8. VERIFY EVAPORATOR FAN CFM.
CL-2
Start and Operate Machine. Complete the Following:
1. COMPLETE COMPONENT TEST.
YES NO
YES NO
YES NO
YES NO
YES NO
YES NO
YES NO
2. CHECK REFRIGERANT AND OIL CHARGE.
3. FINISH CHARGING ACCORDING TO THE CHARGING CHART PROVIDED.
4. RECORD COMPRESSOR MOTOR CURRENT.
5. RECORD CONFIGURATION SETTINGS.
6. RECORD OPERATING TEMPERATURES AND PRESSURES.
7. PROVIDE OPERATING INSTRUCTIONS TO OWNER’S PERSONNEL.
Instruction Time ________ hours.
8. RECORD COMPRESSOR OIL LEVELS AFTER INITIAL RUN. ____________________________________
9. OIL LEVELS ARE STILL WITHIN SIGHT GLASS(ES).
YES NO
OPERATING DATA:
RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN
MACHINE IS IN A STABLE OPERATING CONDITION:
PRESSURE/TEMPERATURE
CIRCUIT A
CIRCUIT B
DISCHARGE PRESSURE
SUCTION PRESSURE
DP.A
DP.B
SP.A
SP.B
SATURATED CONDENSING TEMP
SATURATED SUCTION TEMP
LIQUID LINE TEMPERATURE*
LIQUID LINE PRESSURE
SCT.A
SST.A
SCT.B
SST.B
DISCHARGE LINE TEMPERATURE*
RETURN GAS TEMPERATURE
RETURN AIR TEMPERATURE*
SUPPLY AIR TEMPERATURE*
OUTDOOR-AIR TEMPERATURE
CONTROL POINT
RGT.A
RAT
RGT.B
SAT
OAT
CTPT
CAP.T
PERCENT TOTAL CAPACITY
*Readings taken with a digital thermometer.
CL-3
Compressor Running Current — All readings taken at full load.
COMPRESSOR MOTOR CURRENT
COMPRESSOR A1
L1
L1
L1
L2
L2
L2
L3
L3
L3
COMPRESSOR A2
COMPRESSOR A3
COMPRESSOR B1
COMPRESSOR B2
COMPRESSOR B3
CONDENSER FAN MOTOR CURRENT
FAN MOTOR 1
FAN MOTOR 2
FAN MOTOR 3
FAN MOTOR 4
FAN MOTOR 5
FAN MOTOR 6
EVAPORATOR MOTOR CURRENT
Record Software Versions
MODE — RUN STATUS
SUB-MODE ITEM
DISPLAY
ITEM
EXPANSION
VERS
MBB
MARQ
EMM
NAVI
AUX
CESR-131279- _ _-_ _
CESR-131171- _ _-_ _
CESR-131174- _ _-_ _
CESR-131227- _ _-_ _
CESR-131333- _ _-_ _
CESR-131173- _ _-_ _
CXB
(PRESS ENTER & ESCAPE SIMULTANEOUSLY TO OBTAIN SOFTWARE VERSIONS)
CL-4
COMMENTS:
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
SIGNATURES:
START-UP
CUSTOMER
TECHNICIAN ____________________________
REPRESENTATIVE ____________________________
DATE ___________________________________
DATE________________________________________
CL-5
Copyright 2009 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380003-01
Printed in U.S.A.
Form 38AP-1T
Pg CL-6
210 11-09
Replaces: New
|
Briggs Stratton 140297 User Manual
Canon PIXMA MX340 Office All In One Printer 4204B019 User Manual
Daewoo DWA 151C User Manual
Fedders R407C User Manual
Friedrich Air Conditioner WS12 User Manual
Friedrich MW12Y3FM User Manual
Fujitsu Air Conditioner AST12 User Manual
Havis Shields WBI F7 User Manual
HP Hewlett Packard OFFICEJET 7500A User Manual
Human Touch Automobile Accessories HT 100 User Manual