Carrier 50HG014 028 User Manual

50HG014-028  
Single Package Rooftop Units  
Electric Cooling with Electric Heat Option  
Installation Instructions  
Follow all safety codes. Wear safety glasses and work  
gloves. Use quenching cloth for unbrazing operations. Have  
fire extinguishers available for all brazing operations.  
CONTENTS  
Page  
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23  
Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . . . 1  
• ROOF CURB  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit. Electrical shock  
could cause personal injury.  
• ALTERNATE UNIT SUPPORT  
Step 2 — Remove Shipping Rails . . . . . . . . . . . . . . . . 3  
Step 3 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 3  
• POSITIONING  
• ROOF MOUNT  
• INSTALLATION ONTO CURB  
IMPORTANT: Units have high ambient operating lim-  
its. If limits are exceeded, the units will automatically  
lock the compressor out of operation. Manual reset will  
be required to restart the compressor.  
Step 4 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 8  
Step 5 — Make Unit Duct Connections . . . . . . . . . . . 8  
Step 6 — Trap Condensate Drain. . . . . . . . . . . . . . . . . 9  
Step 7 — Make Electrical Connections . . . . . . . . . . . 9  
• FIELD POWER SUPPLY  
INSTALLATION  
Step 1 — Provide Unit Support  
• FIELD CONTROL WIRING  
ROOF CURB — Assemble or install accessory roof curb in  
accordance with instructions shipped with this accessory. See  
Fig. 1. Install insulation, cant strips, roofing, and counter flash-  
ing as shown. Ductwork can be installed to roof curb before  
unit is set in place. Curb must be level. This is necessary to  
permit unit drain to function properly. Unit leveling tolerance is  
Step 8 — Install Outdoor-Air Hood . . . . . . . . . . . . . . 20  
Step 9 — Position Optional Power Exhaust  
or Barometric Relief Damper Hood. . . . . . . . . . . . 22  
Step 10 — Non-Fused Disconnect. . . . . . . . . . . . . . . 22  
Step 11 — Install All Accessories . . . . . . . . . . . . . . . 23  
1
± /16 in. per linear ft in any direction. Refer to Accessory  
Roof Curb Installation Instructions for additional information  
as required. When accessory roof curb is used, unit may be  
installed on class A, B, or C roof covering material.  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical compo-  
nents. Only trained and qualified service personnel should  
install, repair, or service air-conditioning equipment.  
Untrained personnel can perform the basic maintenance  
functions of replacing filters. All other operations should  
be performed by trained service personnel. When working  
on air-conditioning equipment, observe precautions in the  
literature, tags and labels attached to the unit, and other safety  
precautions that may apply.  
IMPORTANT: The gasketing of the unit to the roof curb  
is critical for a watertight seal. Install gasket with the  
roof curb as shown in Fig. 1. Improperly applied gasket  
can also result in air leaks and poor unit performance.  
ALTERNATE UNIT SUPPORT — When a curb cannot be  
used, install unit on a noncombustible surface. Support unit  
with sleepers, using unit curb support area. If sleepers cannot  
be used, support long sides of unit with a minimum of 3 equal-  
ly spaced 4-in. x 4-in. pads on each side.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 535-00092 Printed in U.S.A. Form 50HG-7SI Pg 1 11-03 Replaces: 50HG-3SI  
Book 1  
4
Tab 1b 6b  
Four lifting holes are provided in the unit base rails as  
shown in Fig. 3. Refer to rigging instructions on unit.  
POSITIONING Maintain clearance, per Fig. 4, around and  
above unit to provide minimum distance from combustible  
materials, proper airflow, and service access.  
Step 2 Remove Shipping Rails Remove ship-  
ping rails prior to lowering unit onto roof curb. See Fig. 2. The  
rails are attached to the unit at both the return end and condens-  
er end. Remove the screws from both ends of each rail. Be  
careful not to drop the rails onto any surface that could be dam-  
aged. Discard the rails. It is important to replace the screws into  
the unit to avoid any air or water leakage.  
Do not install unit in an indoor location. Do not locate air  
inlets near exhaust vents or other sources of contaminated air.  
Although unit is weatherproof, guard against water from  
higher level runoff and overhangs.  
Do not allow the shipping rail to drop on the roof surface.  
Damage to the roof surface may result.  
ROOF MOUNT Check building codes for weight distribu-  
tion requirements. Unit operating weight is shown in Table 1.  
INSTALLATION ONTO CURB The 50HG units are  
designed to fit on either the accessory full perimeter curb or  
onto existing 48/50TJ,HJ or 48/50DP,DR curbs. In either case,  
correct placement of the unit onto the curb is critical to operat-  
ing performance. To aid in correct positioning, 3/8-in. diameter  
locating holes have been added to the unit base rails. When  
placing the unit, these holes should line up with the roof curb  
edge as shown in Fig. 5 and 6, to assure proper duct opening  
alignment. Select the alignment holes suited for the curb being  
used. For installation on the HJ/TJ/DP/DR curb use the align-  
ment holes located approximately 20 in. from the end of the  
base rail on the return end of the unit. For placement on the HG  
curb, use the alignment holes located approximately 2-in. from  
the end of the base rail on the return end of the unit. See labels  
on the side of the unit for more details.  
Step 3 Rig and Place Unit Inspect unit for trans-  
portation damage. See Table 1 for physical data. File any claim  
with transportation agency.  
All panels must be in place when rigging. Unit is not  
designed for handling by fork truck. Damage to unit can  
result.  
Do not drop unit; keep upright. Use spreader bars over unit  
to prevent sling or cable damage. Rollers may be used to move  
unit across a roof. Level by using unit frame as a reference;  
leveling tolerance is ± 1/16 in. per linear ft in any direction. See  
Fig. 3 for additional information. Unit rigging weight is shown  
in Fig. 3.  
SHIPPING RAILS  
Fig. 2 Shipping Rail Removal  
3
Fig. 3 Rigging Details  
4
Fig. 4 Base Unit Dimensions  
5
Table 1 Physical Data  
UNIT 50HG  
014  
016  
020  
208/230  
208/230  
and 460  
15  
208/230  
and 460  
17.5  
VOLTAGE  
575  
575  
15  
575  
and 460  
NOMINAL CAPACITY (Tons)  
12.5  
12.5  
17.5  
OPERATING WEIGHT (lb)  
50 SERIES (Cooling Only)  
2017  
2017  
2111  
2111  
2139  
2139  
COMPRESSOR  
Quantity  
2
2
3
3
3
3
3
3
3
Number of Refrigerant Circuits  
Oil (ounces) Ckt A...Ckt B...Ckt C  
2
2
3
72...72...NA  
72...72...NA  
68...68...68  
68...68...68  
68...68...72 68...68...72  
REFRIGERANT TYPE  
Expansion Device  
Operating Charge (lb)  
Circuit A  
R-22  
TXV  
TXV  
TXV  
TXV  
TXV  
TXV  
19.6  
18.3  
NA  
19.6  
18.3  
NA  
13.2  
12.2  
15.4  
13.2  
12.2  
15.4  
13.1  
12.7  
15.2  
13.1  
12.7  
15.2  
Circuit B  
Circuit C  
CONDENSER COIL  
Rows...Fins/inch  
Total Face area (sq. ft)  
2...17  
57.78  
2...17  
57.78  
2...17  
57.78  
2...17  
57.78  
2...17  
57.78  
2...17  
57.78  
CONDENSER FAN  
Nominal Cfm (Total, all fans)  
Quantity...Diameter (in.)  
Motor Hp...Rpm  
14,000  
4...22  
14,000  
4...22  
14,000  
4...22  
14,000  
4...22  
14,000  
4...22  
14,000  
4...22  
1/4...1100  
1400  
1/4...1100  
1400  
1/4...1100  
1400  
1/4...1100  
1400  
1/4...1100  
1400  
1/4...1100  
1400  
Watts input (Total)  
EVAPORATOR COIL  
Rows...Fins/inch  
Total Face area (sq. ft)  
Face Split  
3...15  
23.33  
3...15  
23.33  
3...15  
23.33  
3...15  
23.33  
3...15  
23.33  
3...15  
23.33  
EVAPORATOR FAN  
Quantity...Size  
2...15x11  
Belt  
2...15x11  
Belt  
2...15x11  
Belt  
2...15x11  
Belt  
2...15x11  
Belt  
2...15x11  
Belt  
Type Drive  
Nominal Cfm  
5000  
5000  
6000  
6000  
7000  
7000  
Std Motor Hp  
3.7  
3
5
3.7  
3
5
5
5
Alt Motor Hp  
5
5
71/2  
71/2  
Motor Nominal Rpm  
Std Maximum Continuous Bhp  
Std Maximum Continuous Watts  
Alt Maximum Continuous Bhp  
Alt Maximum Continuous Watts  
Motor Frame Size  
1725  
1725  
1725  
1725  
1725  
1725  
4.25  
3.45  
4.25  
3.45  
5.75  
5.75  
3171  
2574  
3171  
2574  
4290  
4290  
5.75  
5.75  
5.75  
5.75  
8.63  
8.63  
4290  
4290  
4290  
4290  
6438  
6438  
Standard  
56HZ  
S184T  
485-613  
618-789  
778-1021  
1000-1227  
Ball  
56H  
56HZ  
S184T  
618-789  
485-613  
778-1021  
1000-1227  
Ball  
56H  
S184T  
S213T  
658-808  
794-974  
949-1145  
1126-1328  
Ball  
184T  
Motor Frame Size  
Fan Drive Rpm Range  
Alternate  
184T  
184T  
S213T  
658-808  
794-974  
949-1145  
1126-1328  
Ball  
Std motor/Std drive  
Std motor/Alt drive  
Alt motor/Std drive  
Alt motor/Alt drive  
472-619  
609-778  
778-1021  
1000-1227  
Ball  
609-778  
472-619  
778-1021  
1000-1227  
Ball  
Motor Bearing Type  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter  
1400  
1400  
1400  
1400  
1400  
1400  
Std motor/Std drive  
Std motor/Alt drive  
Alt motor/Std drive  
Alt motor/Alt drive  
Standard  
3.7-4.7  
3.4-4.4  
3.1-4.1  
3.1-4.1  
3.4-4.4  
3.1-4.1  
3.4-4.4  
3.7-4.7  
3.1-4.1  
3.4-4.4  
3.1-4.1  
3.1-4.1  
4.3-5.3  
4.3-5.3  
5.4-6.6  
5.5-6.5  
11/8  
4.3-5.3  
4.3-5.3  
5.4-6.6  
5.5-6.5  
11/8  
4.3-5.3  
4.3-5.3  
4.3-5.3  
4.3-5.3  
7
7
7
7
Motor Shaft Diameter (in.)  
Motor Shaft Diameter (in.)  
Belt, Quantity...Type...Length (in.)  
/
/
/
/
8
8
8
8
Alternate  
11/8  
11/8  
11/8  
11/8  
13/8  
13/8  
Std motor/Std drive  
Std motor/Alt drive  
Alt motor/Std drive  
Alt motor/Alt drive  
1...BX...51  
1...A...45  
1...BX...38  
1...B...38  
11.3-12.3  
1...BX...48  
1...A...45  
1...BX...38  
1...B...38  
11.3-12.3  
1...A...45  
1...BX...51  
1...BX...38  
1...B...38  
11.3-12.3  
1...A...45  
1...BX...48  
1...BX...38  
1...B...38  
11.3-12.3  
1...BX...46  
1...BX...42  
1...BX...46  
1...BX...42  
10.0-12.2  
1...BX...46  
1...BX...42  
1...BX...46  
1...BX...42  
10.0-12.2  
Pulley center line distance (in.)  
Speed change per full turn of moveable  
pulley flange (rpm)  
Std motor/Std drive  
Std motor/Alt drive  
Alt motor/Std drive  
Alt motor/Alt drive  
21  
29  
41  
38  
6
25  
28  
41  
38  
6
29  
21  
41  
38  
6
28  
25  
41  
38  
6
25  
30  
33  
34  
6
25  
30  
33  
34  
6
Moveable pulley maximum (full turns  
from closed position)  
Factory Pulley Setting  
(turns from closed position)  
Fan Shaft Diameter (in.)  
3
3
3
3
3
3
13/16  
549  
13/16  
546  
13/16  
704  
13/16  
694  
13/16  
733  
13/16  
733  
Factory Speed Setting (rpm)  
HIGH PRESSURE SWITCHES (psig)  
Cutout  
426  
320  
426  
320  
426  
320  
426  
320  
426  
320  
426  
320  
Reset (Auto)  
OUTDOOR AIR INLET SCREENS  
Quantity...Size (in.)  
RETURN AIR FILTERS  
Quantity...Size (in.)  
3...20x25  
9...16x25  
3...20x25  
9...16x25  
3...20x25  
9...16x25  
3...20x25  
9...16x25  
3...20x25  
9...16x25  
3...20x25  
9...16x25  
LEGEND  
Bhp  
TXV  
Brake Horsepower  
Thermostatic Expansion Valve  
6
Table 1 Physical Data (cont)  
UNIT 50HG  
024  
028  
ALL  
25  
208/230  
and 460  
20  
VOLTAGE  
575  
20  
NOMINAL CAPACITY (Tons)  
OPERATING WEIGHT (lb)  
50 SERIES (Cooling Only)  
2187  
2187  
2446  
COMPRESSOR  
Quantity  
3
3
2
Number of Refrigerant Circuits  
Oil (ounces) Ckt A...Ckt B...Ckt C  
3
3
2
72...72...72  
72...72...72  
110...110...NA  
REFRIGERANT TYPE  
Expansion Device  
Operating Charge (lb)  
Circuit A  
R-22  
TXV  
TXV  
TXV  
13.8  
13.9  
15.5  
13.8  
13.9  
15.5  
23.9  
21.5  
NA  
Circuit B  
Circuit C  
CONDENSER COIL  
Rows...Fins/inch  
Total Face Area (sq. ft)  
2...17  
57.78  
2...17  
57.78  
2...17  
66.67  
CONDENSER FAN  
Nominal Cfm (Total, all fans)  
Quantity...Diameter (in.)  
Motor Hp...Rpm  
14,000  
4...22  
14,000  
4...22  
21,000  
6...22  
1/4...1100  
1400  
1/4...1100  
1400  
1/4...1100  
2100  
Watts input (Total)  
EVAPORATOR COIL  
Rows...Fins/inch  
Total Face Area (sq. ft)  
Face Split  
4...15  
23.33  
4...15  
23.33  
4...15  
27.22  
EVAPORATOR FAN  
Quantity...Size  
2...15x11  
Belt  
2...15x11  
Belt  
2...15x11  
Belt  
Type Drive  
Nominal Cfm  
8000  
8000  
10,000  
Std Motor Hp  
5
5
71/2  
Alt Motor Hp  
71/2  
71/2  
10  
Motor Nominal Rpm  
Std Maximum Continuous Bhp  
Std Maximum Continuous Watts  
Alt Maximum Continuous Bhp  
Alt Maximum Continuous Watts  
Motor Frame Size  
1725  
1725  
1725  
5.75  
5.75  
8.63  
4290  
4290  
6438  
8.63  
8.63  
11.50  
6438  
6438  
8579  
Standard  
S184T  
S213T  
658-808  
794-974  
949-1145  
1126-1328  
Ball  
184T  
S213T  
S215T  
799-965  
939-1152  
945-1187  
1152-1366  
Ball  
Motor Frame Size  
Fan Drive Rpm Range  
Alternate  
S213T  
658-808  
794-974  
949-1145  
1126-1328  
Ball  
Std motor/Std drive  
Std motor/Alt drive  
Alt motor/Std drive  
Alt motor/Alt drive  
Motor Bearing Type  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter  
1400  
1400  
1400  
Std motor/Std drive  
Std motor/Alt drive  
Alt motor/Std drive  
Alt motor/Alt drive  
Standard  
4.3-5.3  
4.3-5.3  
5.4-6.6  
5.5-6.5  
11/8  
4.3-5.3  
4.3-5.3  
5.4-6.6  
5.5-6.5  
11/8  
5.4-6.6  
4.2-5.2  
4.2-5.2  
5.2-6.2  
13/8  
Motor Shaft Diameter (in.)  
Motor Shaft Diameter (in.)  
Belt, Quantity...Type...Length (in.)  
Alternate  
13/8  
13/8  
13/8  
Std motor/Std drive  
Std motor/Alt drive  
Alt motor/Std drive  
Alt motor/Alt drive  
1...BX...46  
1...BX...42  
1...BX...46  
1...BX...42  
10.0-12.2  
1...BX...46  
1...BX...42  
1...BX...46  
1...BX...42  
10.0-12.2  
1...BX...50  
2...AX...38  
2...BX...38  
2...BX...38  
9.6-12.0  
Pulley center line distance (in.)  
Speed change per full turn of moveable  
pulley flange (rpm)  
Std motor/Std drive  
Std motor/Alt drive  
Alt motor/Std drive  
Alt motor/Alt drive  
25  
30  
33  
34  
6
25  
30  
33  
34  
6
28  
36  
40  
36  
6
Moveable pulley maximum (full turns  
from closed position)  
Factory Pulley Setting  
(turns from closed position)  
Fan Shaft Diameter (in.)  
3
3
3
13/16  
733  
13/16  
733  
13/16  
882  
Factory Speed Setting (rpm)  
HIGH PRESSURE SWITCHES (psig)  
Cutout  
426  
320  
426  
320  
426  
320  
Reset (Auto)  
OUTDOOR AIR INLET SCREENS  
Quantity...Size (in.)  
RETURN AIR FILTERS  
Quantity...Size (in.)  
3...20x25  
9...16x25  
3...20x25  
9...16x25  
3...20x25  
9...20x25  
LEGEND  
Bhp  
TXV  
Brake Horsepower  
Thermostatic Expansion Valve  
7
HORIZONTAL APPLICATIONS Horizontal units are  
shipped with outer panels that allow for side by side horizontal  
duct connections. If specified during ordering, the unit will be  
shipped with the vertical duct openings blocked off from the  
factory, ready for side supply installation. If the horizontal  
option was not specified at time of ordering the unit, a field-  
installed accessory kit is required to convert the vertical unit  
into a horizontal supply configuration.  
Installation of the duct block-off covers should be complet-  
ed prior to placing the unit unless sufficient side clearance is  
available. A minimum of 66-in. is required between the unit  
and any obstruction to install the duct block-off covers. Side  
supply duct dimensions and locations are shown on Fig. 4.  
Connect ductwork to horizontal duct flange connections on  
side of unit.  
ALIGNMENT  
HOLE  
(IN BASE RAIL)  
ALIGNMENT  
HOLE SHOULD  
LINE UP WITH  
ROOF CURB  
EDGE FLANGE  
EDGE FLANGE  
Fig. 5 Alignment Hole Details  
ALIGNMENT  
HOLES FOR  
HJ, TJ, DP, DR  
CURB-BOTH  
SIDES  
ECONOMIZER  
SUPPLY  
OPENING  
RETURN  
OPENING  
CURB  
RETURN  
OPENING  
CURB  
SUPPLY  
OPENING  
ALIGNMENT  
HOLES FOR HG  
CURB-BOTH  
SIDES  
SEE  
NOTE  
SEE  
NOTE  
ROOF CURB  
Fig. 6 Alignment Hole Location  
AIR  
IN  
AIR  
OUT  
Step 4 Field Fabricate Ductwork Secure all  
ducts to building structure. Use flexible duct connectors be-  
tween unit and ducts as required. Insulate and weatherproof all  
external ductwork, joints, and roof openings with counter  
flashing and mastic in accordance with applicable codes.  
NOTE: Do not drill in this area; damage to basepan may result in  
water leak.  
Fig. 7 Air Distribution —  
Vertical Supply and Return  
Ducts passing through an unconditioned space must be in-  
sulated and covered with a vapor barrier.  
Step 5 Make Unit Duct Connections  
ECONOMIZER  
VERTICAL CONFIGURATION Unit is shipped for thru-  
the-bottom duct connections. Ductwork openings are shown in  
Fig. 1 and 4. Duct connections for vertical supply and return  
configuration are shown in Fig. 7. Field fabricated concentric  
ductwork may be connected as shown in Fig. 8 and 9. The unit  
is designed to attach the ductwork to the roof curb. Do not  
attach duct directly to the unit basepans.  
Unit basepans must be supported under the unit and around  
duct openings in order to prevent air leakage.  
SEE  
NOTE  
SEE  
NOTE  
For vertical supply and return units, tools or parts could  
drop into ductwork and cause an injury. Install a 90-degree  
turn in the return ductwork between the unit and the condi-  
tioned space. If a 90-degree elbow cannot be installed, then  
a grille of sufficient strength and density should be installed  
to prevent objects from falling into the conditioned space.  
AIR OUT  
AIR OUT  
AIR IN  
NOTE: Do not drill in this area; damage to basepan may result in  
water leak.  
Units with electric heat require a 1-in. clearance for the first  
24 in. of ductwork. Outlet grilles must not lie directly below  
unit discharge.  
Fig. 8 Air Distribution Concentric Duct  
NOTE: A 90-degree elbow must be provided in the supply  
ductwork to comply with UL (UnderwritersLaboratories)  
codes for use with electric heat.  
8
Operating voltage to compressor must be within voltage  
range indicated on unit nameplate. On 3-phase units, voltages  
between phases must be balanced within 2%.  
Unit failure as a result of operation on improper line voltage  
or excessive phase imbalance constitutes abuse and may cause  
damage to electrical components.  
FIELD CONTROL WIRING Unit can be controlled with  
either a Carrier-approved accessory thermostat or a Carrier-  
approved space temperature sensor. Install thermostat accord-  
ing to the installation instructions included with accessory.  
Locate thermostat assembly or space temperature sensor on a  
solid interior wall in the conditioned space to sense average  
temperature.  
Route thermostat or space temperature sensor cable or  
equivalent single leads of colored wire from subbase terminals  
through conduit into unit to low-voltage connections as shown  
on unit label wiring diagram and in Fig. 13 or 14.  
NOTE: Dimensions A, A, B, and Bare obtained from field-supplied  
ceiling diffuser.  
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American  
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,  
use no. 16 AWG insulated wire (35 C minimum). For over  
75 ft, use no. 14 AWG insulated wire (35 C Minimum). All  
wire larger than no. 18 AWG cannot be directly connected at  
the thermostat and will require a junction box and splice at the  
thermostat.  
Shaded areas indicate block-off pans.  
Fig. 9 Concentric Duct Details  
Step 6 Trap Condensate Drain See Fig. 10  
for drain location. One 3/4-in. half coupling is provided outside  
unit evaporator section for condensate drain connection. A trap  
at least 4-in. deep must be used. See Fig. 11.  
Step 7 Make Electrical Connections  
FIELD POWER SUPPLY Unit is factory wired for volt-  
age shown on unit nameplate.  
When installing units, provide disconnect per NEC (Nation-  
al Electrical Code) of adequate size (MOCP [Maximum  
Overcurrent protection] of unit is on the informative plate). See  
Tables 2A and 2B. All field wiring must comply with NEC and  
local codes. Size wire based on MCA (Minimum Circuit  
Amps) on the unit informative plate. See Fig. 12 for power  
wiring connections to the unit power terminal block and  
equipment grounds.  
Route power and ground lines through control box end pan-  
el or unit basepan (see Fig. 4) to connections as shown on unit  
wiring diagram and Fig. 12.  
Fig. 10 Condensate Drain Details  
The correct power phasing is critical to the operation of the  
scroll compressors. An incorrect phasing will result in an  
alarm being generated and compressor operation lockout.  
Should this occur, power phase correction must be made to  
the incoming power.  
The unit must be electrically grounded in accordance with  
local codes and NEC ANSI/NFPA 70 (American National  
Standards Institute/National Fire Protection Association).  
Field wiring must conform to temperature limitations for  
type Twire. All field wiring must comply with NEC and  
local requirements.  
NOTE: Dimensions in [] are in millimeters.  
Fig. 11 Condensate Drain Piping Details  
9
Table 2A Electrical Data (Units Without Optional Convenience Outlet)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
60/ 59  
72/ 71  
66/ 64  
78/ 76  
60/ 60  
72/ 74  
66/ 67  
78/ 81  
78/ 87  
70/ 70  
90/ 80  
80/ 80  
90/ 90  
70/ 70  
90/ 80  
80/ 80  
90/ 90  
80/ 90  
70/ 70  
80/ 80  
80/ 70  
90/ 90  
70/ 70  
80/ 80  
80/ 70  
90/ 90  
80/ 90  
90/100  
80/ 90  
100/110  
150/150  
150/175  
150/175  
175/175  
35  
40  
35  
45  
35  
40  
35  
45  
45  
50  
45  
60  
80  
90  
80  
90  
30  
35  
30  
35  
30  
35  
30  
35  
35  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6 /9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
1.0 5.9  
1.0 5.9  
1.0 5.9  
1.0 5.9  
1.0 5.9  
1.0 5.9  
1.0 5.9  
1.0 5.9  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
1.0 3.1  
12/16  
19/25  
33/ 38  
1
208/230  
187 253 19.2 146.0 19.2 146.0  
4.0  
4.0  
4.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
93/102 100/110  
86/ 94 90/100  
52/ 60  
101/109 110/110  
143/132 150/150  
158/147 175/150  
151/139 175/150  
166/154 175/175  
38/50 104/120  
29  
35  
32  
38  
29  
36  
32  
40  
44  
51  
47  
55  
66  
74  
70  
77  
24  
30  
26  
32  
24  
31  
26  
34  
35  
43  
38  
45  
62  
70  
65  
73  
35  
40  
40  
45  
35  
40  
40  
45  
45  
60  
50  
60  
80  
80  
80  
80  
30  
35  
30  
35  
30  
35  
30  
35  
35  
45  
40  
50  
70  
80  
70  
80  
3.7  
5.0  
3.7  
5.0  
3.7  
5.0  
3.7  
5.0  
3.0  
5.0  
3.0  
5.0  
3.0  
5.0  
3.0  
5.0  
4.8  
7.6  
4.8  
7.6  
4.8  
7.6  
4.8  
7.6  
3.9  
6.1  
3.9  
6.1  
3.9  
6.1  
3.9  
6.1  
15  
25  
50  
16  
25  
48  
18  
30  
60  
15  
24  
46  
1
014  
460  
414 506  
9.5  
73.0  
9.5  
73.0  
1
575  
518 633  
7.6  
58.4  
7.6  
58.4  
40  
35  
45  
60  
70  
60  
70  
LEGEND AND NOTES FOR TABLES 2A AND 2B  
LEGEND  
MCA  
Heating, Air Conditioning and MOCP  
Refrigeration NEC  
Indoor (Evaporator) Fan Motor OFM  
Locked Rotor Amps RLA  
Determine maximum deviation from average voltage.  
(AB) 457 – 452 = 5 v  
(BC) 464 – 457 = 7 v  
(AC) 457 – 455 = 2 v  
FLA  
Full Load Amps  
Minimum Circuit Amps  
HACR  
Maximum Overcurrent Protection  
National Electrical Code  
IFM  
LRA  
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
*Fuse or HACR circuit breaker.  
% Voltage Imbalance = 100 x  
†208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the  
branch circuit values for the refrigeration part of the system. The following two tables list  
the branch circuit values for the electric heat and values for a feeder circuit for both branch  
circuits.  
457  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the maximum allowable  
2%.  
NOTES:  
1. In compliance with NEC requirements for multimotor and combination load equipment  
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall  
be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.  
2. Unbalanced 3-Phase Supply Voltage  
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your  
local electric utility company immediately.  
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.  
Use the following formula to determine the percent of voltage imbalance.  
3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired sepa-  
rately in the field.  
4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v  
units, respectively.  
5. The FLA load amps provided in the table for electric heaters are based on 208/240, 480  
and 600v.  
6. MCA calculation for 50HG014-028 units with electric heaters over 50 kW is = 1.25 x  
(IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA).  
% Voltage Imbalance  
max voltage deviation from average voltage  
= 100 x  
average voltage  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
452 + 464 + 455  
Average Voltage =  
3
1371  
3
=
=
457  
10  
Table 2A Electrical Data (Units Without Optional Convenience Outlet) (cont)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
71/ 70  
83/ 82  
80/ 80  
90/ 90  
80/ 80  
100/ 90  
90/ 90  
100/100  
80/ 90  
100/100  
90/ 90  
100/110  
150/150  
150/175  
150/175  
175/175  
80/ 80†  
100/ 90†  
90/ 90†  
100/100†  
40  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
1.0 5.9  
2
77/ 75  
89/ 87  
90/ 90  
100/100  
80/ 90  
1.0 5.9  
2
78/ 87  
1.0 5.9  
93/102  
100/110  
90/100  
19/25  
52/ 60  
2
86/ 94  
1.0 5.9  
101/109  
143/132  
158/147  
151/139  
166/154  
71/ 70†  
83/ 82†  
77/ 75†  
110/110  
150/150  
175/150  
175/150  
175/175  
80/ 80†  
90/ 90†  
90/ 90†  
1
208/230  
187 253 16.7 130.0 16.7 130.0 16.7 130.0 4.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
1.0 5.9  
56/75156/180  
2
1.0 5.9  
89/ 87100/100†  
2
37  
43  
40  
46  
44  
51  
47  
55  
66  
74  
70  
77  
96  
104  
100  
107  
29  
36  
32  
38  
35  
43  
38  
45  
62  
70  
65  
73  
80  
88  
83  
90  
45  
50  
3.7  
5.0  
3.7  
5.0  
3.7  
5.0  
3.7  
5.0  
3.0  
5.0  
3.0  
5.0  
3.0  
5.0  
3.0  
5.0  
4.8  
7.6  
4.8  
7.6  
4.8  
7.6  
4.8  
7.6  
3.9  
6.1  
3.9  
6.1  
3.9  
6.1  
3.9  
6.1  
1.0 3.1  
50  
25  
50  
75  
25  
48  
78  
30  
60  
90  
24  
46  
75  
2
45  
45  
1.0 3.1  
50  
60  
2
45  
60  
45  
50  
1.0 3.1  
2
50  
45  
1.0 3.1  
60  
60  
1
016  
460  
414 506  
9.0  
70.0  
9.0  
70.0  
9.0  
70.0 4.0  
2
80  
80  
1.0 3.1  
80  
90  
2
80  
80  
80  
90  
1.0 3.1  
2
110  
110  
110  
125  
35  
110  
1.0 3.1  
125  
2
125  
1.0 3.1  
125  
2
35  
40  
1.0 3.1  
40  
2
35  
35  
1.0 3.1  
40  
45  
2
35  
35  
1.0 3.1  
45  
40  
2
2
40  
35  
1.0 3.1  
50  
70  
45  
60  
1
575  
518 633  
7.0  
55.0  
7.0  
55.0  
7.0  
55.0 4.0  
1.0 3.1  
80  
70  
2
70  
60  
1.0 3.1  
80  
70  
2
2
90  
100  
1.0 3.1  
100  
90  
100  
100  
1.0 3.1  
100  
110  
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp FLA Qty Hp  
MCA  
MOCP*  
FLA  
016  
208/240  
187 253  
NA  
NA  
NA  
NA  
NA  
NA  
NA NA  
NA  
56/75 156/180 NA NA NA NA  
NA  
156/180 175/200  
200/225  
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
169/192 200/225  
200/225  
225/250  
200/225  
225/250  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
1.0 5.9 184/207 200/225  
177/199 200/225  
1.0 5.9 192/214 200/225  
1
016  
208/230  
187 253 16.7 130.0 16.7 130.0 16.7 130.0 4.0  
/
4
1.5 56/75 156/180  
2
See Legend and Notes on page 10.  
11  
Table 2A Electrical Data (Units Without Optional Convenience Outlet) (cont)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
84/ 83  
96/ 94  
100/100  
110/110  
110/110  
125/110  
100/100  
110/110  
110/110  
125/125  
175/150  
175/175  
175/150  
200/175  
100/ 90  
110/110  
100/100  
125/110  
100/ 90  
110/110  
100/100  
125/110  
150/175  
175/175  
150/175  
175/200  
100/ 90†  
110/110†  
100/100†  
125/110†  
45  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
1.0 5.9  
2
92/ 89  
104/101  
86/ 94  
1.0 5.9  
2
1.0 5.9  
101/109  
95/103  
19/25  
52/ 60  
2
1.0 5.9  
110/117  
151/139  
166/154  
160/148  
175/162  
1
208/230  
187 253 16.7 130.0 16.7 130.0 22.4 184.0 4.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
84/ 83100/100†  
96/ 94110/110†  
92/ 89110/110†  
104/101125/110†  
1.0 5.9  
56/75156/180  
2
1.0 5.9  
2
42  
48  
45  
51  
47  
55  
51  
59  
70  
77  
74  
82  
100  
107  
104  
112  
35  
41  
37  
44  
38  
45  
41  
49  
65  
73  
69  
77  
83  
90  
86  
94  
50  
50  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
7.6  
11.0  
7.6  
1.0 3.1  
60  
25  
50  
75  
25  
48  
78  
30  
60  
90  
24  
46  
75  
2
50  
50  
1.0 3.1  
60  
60  
2
50  
60  
45  
60  
1.0 3.1  
2
60  
50  
11.0  
7.6  
1.0 3.1  
60  
60  
1
020  
460  
414 506  
9.0  
70.0  
9.0  
70.0 10.7  
90.0 4.0  
2
80  
80  
1.0 3.1  
80  
90  
2
80  
90  
90  
90  
11.0  
7.6  
1.0 3.1  
2
110  
125  
125  
125  
40  
125  
1.0 3.1  
125  
2
125  
11.0  
6.1  
1.0 3.1  
125  
2
40  
45  
1.0 3.1  
50  
2
45  
45  
9.0  
1.0 3.1  
50  
50  
2
40  
40  
6.1  
1.0 3.1  
50  
45  
2
2
45  
45  
9.0  
1.0 3.1  
50  
70  
50  
60  
1
575  
518 633  
7.0  
55.0  
7.0  
55.0  
9.3  
73.0 4.0  
6.1  
1.0 3.1  
80  
70  
2
70  
70  
9.0  
1.0 3.1  
80  
80  
2
2
90  
100  
6.1  
1.0 3.1  
100  
100  
100  
110  
100  
9.0  
1.0 3.1  
110  
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp FLA Qty Hp  
MCA  
MOCP*  
FLA  
020  
208/240  
187 253  
NA  
NA  
NA  
NA  
NA  
NA  
NA NA  
NA  
56/75 156/180 NA NA NA NA  
NA  
156/180 175/200  
200/225  
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
177/199 200/225  
200/225  
225/250  
225/250  
225/250  
5.0 16.7/15.2  
7.5 24.2/22.0  
1.0 5.9 192/214 200/225  
186/208 200/225  
1.0 5.9 201/222 225/225  
1
020  
208/230  
187 253 16.7 130.0 16.7 130.0 22.4 184.0 4.0  
/
4
1.5 56/75 156/180  
2
See Legend and Notes on page 10.  
12  
Table 2A Electrical Data (Units Without Optional Convenience Outlet) (cont)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
96/ 94  
107/106  
104/101  
115/113  
96/ 94  
110/110  
125/125  
125/110  
125/125  
110/110  
125/125  
125/110  
125/125  
175/150  
175/175  
175/150  
200/175  
110/110  
125/125  
125/110  
150/125  
110/110  
125/125  
125/110  
150/125  
150/175  
175/175  
150/175  
175/200  
110/110†  
125/125†  
125/110†  
150/125†  
50  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
1.0 5.9  
2
1.0 5.9  
2
1.0 5.9  
107/109  
104/103  
115/117  
151/139  
166/154  
160/148  
175/162  
19/25  
52/ 60  
2
1.0 5.9  
1
208/230  
187 253 22.4 184.0 22.4 184.0 22.4 184.0 4.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
96/ 94110/110†  
107/106125/125†  
104/101125/110†  
115/113125/125†  
1.0 5.9  
56/75156/180  
2
1.0 5.9  
2
45  
51  
49  
55  
47  
55  
51  
59  
70  
77  
74  
82  
100  
107  
104  
112  
39  
45  
42  
48  
39  
45  
42  
49  
65  
73  
69  
77  
83  
90  
86  
94  
50  
60  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
7.6  
11.0  
7.6  
1.0 3.1  
60  
25  
50  
75  
25  
48  
78  
30  
60  
90  
24  
46  
75  
2
50  
60  
1.0 3.1  
60  
60  
2
50  
60  
50  
60  
1.0 3.1  
2
60  
60  
11.0  
7.6  
1.0 3.1  
60  
60  
1
024  
460  
414 506 10.7  
90.0 10.7  
90.0 10.7  
90.0 4.0  
2
80  
80  
1.0 3.1  
80  
90  
2
80  
90  
90  
90  
11.0  
7.6  
1.0 3.1  
2
110  
125  
125  
125  
45  
125  
1.0 3.1  
125  
2
125  
11.0  
6.1  
1.0 3.1  
125  
2
45  
50  
1.0 3.1  
50  
2
50  
50  
9.0  
1.0 3.1  
50  
60  
2
45  
45  
6.1  
1.0 3.1  
50  
50  
2
2
50  
50  
9.0  
1.0 3.1  
50  
70  
60  
60  
1
575  
518 633  
9.3  
73.0  
9.3  
73.0  
9.3  
73.0 4.0  
6.1  
1.0 3.1  
80  
70  
2
70  
70  
9.0  
1.0 3.1  
80  
80  
2
2
90  
100  
6.1  
1.0 3.1  
100  
100  
100  
110  
100  
9.0  
1.0 3.1  
110  
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp FLA Qty Hp  
MCA  
MOCP*  
FLA  
024  
208/240  
187 253  
NA  
NA  
NA  
NA  
NA  
NA  
NA NA  
NA  
56/75 156/180 NA NA NA NA  
NA  
156/180 175/200  
200/225  
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
5.0 16.7/15.2  
7.5 24.2/22  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
2
177/199 200/225  
200/225  
225/250  
225/250  
225/250  
1.0 5.9 192/214 200/225  
186/208 200/225  
1.0 5.9 201/222 225/225  
1
024  
208/230  
187 253 22.4 184.0 22.4 184.0 22.4 184.0 4.0  
/
4
1.5 56/75 156/180  
2
See Legend and Notes on page 10.  
13  
Table 2A Electrical Data (Units Without Optional Convenience Outlet) (cont)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
139/137  
151/149  
146/143  
158/155  
139/137  
151/149  
146/143  
158/155  
160/148  
175/162  
169/155  
183/170  
175/175  
175/175  
175/175  
200/200  
175/175  
175/175  
175/175  
200/200  
175/175  
200/175  
175/175  
200/200  
150/150  
175/175  
175/175  
175/175  
150/150  
175/175  
175/175  
175/175  
150/175  
175/200  
175/175  
175/200  
150/150†  
175/175†  
175/175†  
175/175†  
70  
7.5 24.2/22.0  
10.0 30.8/28.0  
7.5 24.2/22.0  
10.0 30.8/28.0  
7.5 24.2/22.0  
10.0 30.8/28.0  
7.5 24.2/22.0  
10.0 30.8/28.0  
1.0 5.9  
2
1.0 5.9  
2
1.0 5.9  
19/25  
52/ 60  
2
1.0 5.9  
1
208/230  
187 253 47.1 245.0 47.1 245.0  
414 506 19.6 125.0 19.6 125.0  
518 633 15.8 100.0 15.8 100.0  
6.0  
6.0  
6.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
139/137175/175†  
151/149175/175†  
146/143175/175†  
158/155200/200†  
1.0 5.9  
56/75156/180  
2
1.0 5.9  
2
59  
66  
62  
69  
59  
66  
62  
69  
74  
82  
78  
85  
104  
112  
108  
115  
49  
55  
51  
57  
49  
55  
51  
57  
69  
77  
71  
79  
86  
94  
89  
97  
70  
80  
7.5  
10.0  
7.5  
11.0  
14.0  
11.0  
14.0  
11.0  
14.0  
11.0  
14.0  
9.0  
1.0 3.1  
70  
25  
50  
75  
25  
48  
78  
30  
60  
90  
24  
46  
75  
2
80  
70  
1.0 3.1  
80  
80  
2
70  
80  
70  
70  
1.0 3.1  
2
80  
70  
10.0  
7.5  
1.0 3.1  
80  
80  
1
028  
460  
2
80  
90  
1.0 3.1  
90  
90  
2
90  
90  
90  
100  
10.0  
7.5  
1.0 3.1  
2
125  
125  
125  
125  
60  
125  
1.0 3.1  
125  
2
125  
10.0  
7.5  
1.0 3.1  
150  
2
60  
60  
1.0 3.1  
70  
2
60  
60  
10.0  
7.5  
11.0  
9.0  
1.0 3.1  
70  
70  
2
60  
60  
1.0 3.1  
70  
60  
2
2
60  
60  
10.0  
7.5  
11.0  
9.0  
1.0 3.1  
70  
70  
70  
70  
1
575  
1.0 3.1  
80  
80  
2
80  
70  
10.0  
7.5  
11.0  
9.0  
1.0 3.1  
80  
80  
2
2
100  
100  
100  
100  
100  
1.0 3.1  
110  
100  
10.0  
11.0  
1.0 3.1  
110  
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp FLA Qty Hp  
MCA  
MOCP*  
FLA  
028  
208/240  
187 253  
NA  
NA  
NA  
NA  
NA  
NA  
NA NA  
NA  
56/75 156/180 NA NA NA NA  
NA  
156/180 175/200  
200/225  
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
186/208 200/225  
225/250  
225/250  
225/250  
250/300  
7.5 24.2/22.0  
10.0 30.8/28.0  
1.0 5.9 201/222 225/225  
195/215 225/225  
1.0 5.9 209/230 225/250  
1
028  
208/230  
187 253 47.1 245.0 47.1 245.0  
6.0  
/
1.5 56/75 156/180  
4
2
See Legend and Notes on page 10.  
14  
Table 2B Electrical Data (Units With Optional Convenience Outlet)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
65/ 64  
77/ 76  
71/ 69  
80/ 80  
90/ 90  
90/ 80  
70/ 70  
80/ 80  
80/ 70  
90/ 90  
70/ 70  
80/ 80  
80/ 70  
90/ 90  
80/ 90  
90/100  
80/ 90  
100/110  
150/150  
150/175  
150/175  
175/175  
35  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
1.0 5.9  
2
1.0 5.9  
83/ 81 100/100  
2
65/ 66  
77/ 81  
71/ 73  
80/ 80  
90/ 90  
90/ 80  
1.0 5.9  
12/16  
19/25  
33/ 38  
52/ 60  
2
1.0 5.9  
83/ 88 100/100  
85/ 93 90/100  
1
208/230  
187 253 19.2 146.0 19.2 146.0  
4.0  
4.0  
4.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
2
1.0 5.9  
99/108 100/110  
92/100 100/110  
107/115 110/125  
150/138 150/150  
164/153 175/175  
157/145 175/150  
172/160 175/175  
2
1.0 5.9  
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
32  
38  
35  
41  
32  
40  
36  
44  
47  
55  
51  
59  
70  
78  
73  
81  
27  
33  
29  
36  
27  
35  
30  
38  
39  
46  
41  
49  
66  
74  
69  
77  
40  
45  
40  
50  
40  
45  
40  
50  
50  
60  
60  
60  
80  
80  
80  
90  
30  
40  
35  
40  
30  
40  
35  
40  
40  
50  
45  
50  
70  
80  
70  
80  
3.7  
5.0  
3.7  
5.0  
3.7  
5.0  
3.7  
5.0  
3.0  
5.0  
3.0  
5.0  
3.0  
5.0  
3.0  
5.0  
4.8  
7.6  
4.8  
7.6  
4.8  
7.6  
4.8  
7.6  
3.9  
6.1  
3.9  
6.1  
3.9  
6.1  
3.9  
6.1  
1.0 3.1  
40  
15  
25  
50  
16  
25  
48  
18  
30  
60  
15  
24  
46  
2
35  
1.0 3.1  
45  
2
35  
40  
1.0 3.1  
2
35  
1.0 3.1  
45  
1
014  
460  
414 506  
9.5  
73.0  
9.5  
73.0  
2
45  
1.0 3.1  
50  
2
45  
60  
1.0 3.1  
2
80  
1.0 3.1  
90  
2
80  
1.0 3.1  
90  
2
30  
35  
1.0 3.1  
2
30  
1.0 3.1  
35  
2
30  
1.0 3.1  
35  
2
2
30  
1.0 3.1  
35  
35  
1
575  
518 633  
7.6  
58.4  
7.6  
58.4  
1.0 3.1  
40  
2
35  
1.0 3.1  
45  
2
2
60  
1.0 3.1  
70  
60  
1.0 3.1  
70  
See Legend and Notes on page 10.  
15  
Table 2B Electrical Data (Units With Optional Convenience Outlet) (cont)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
76/ 75  
88/ 87  
82/ 80  
94/ 92  
85/ 93  
99/108  
92/100  
107/115  
150/138  
164/153  
157/145  
172/160  
76/ 75†  
90/ 90  
100/100  
90/ 90  
110/100  
90/100  
80/ 80  
100/ 90  
90/ 90  
100/100  
80/ 90  
100/100  
90/ 90  
100/110  
150/150  
150/175  
150/175  
175/175  
80/ 80†  
100/ 90†  
90/ 90†  
100/100†  
40  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
1.0 5.9  
2
1.0 5.9  
2
1.0 5.9  
100/110  
100/110  
110/125  
150/150  
175/175  
175/150  
175/175  
90/ 90†  
19/25  
52/ 60  
2
1.0 5.9  
1
208/230  
187 253 16.7 130.0 16.7 130.0 16.7 130.0 4.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
1.0 5.9  
88/ 87100/100†  
82/ 8090/ 90†  
94/ 92110/100†  
56/75156/180  
2
1.0 5.9  
2
40  
46  
43  
49  
47  
55  
51  
59  
70  
78  
73  
81  
100  
108  
103  
111  
32  
39  
35  
41  
39  
46  
41  
49  
66  
74  
69  
77  
84  
91  
86  
94  
45  
50  
3.7  
5.0  
3.7  
5.0  
3.7  
5.0  
3.7  
5.0  
3.0  
5.0  
3.0  
5.0  
3.0  
5.0  
3.0  
5.0  
4.8  
7.6  
4.8  
7.6  
4.8  
7.6  
4.8  
7.6  
3.9  
6.1  
3.9  
6.1  
3.9  
6.1  
3.9  
6.1  
1.0 3.1  
50  
25  
50  
75  
25  
48  
78  
30  
60  
90  
24  
46  
75  
2
50  
45  
1.0 3.1  
50  
60  
2
50  
60  
45  
50  
1.0 3.1  
2
60  
45  
1.0 3.1  
60  
60  
1
016  
460  
414 506  
9.0  
70.0  
9.0  
70.0  
9.0  
70.0 4.0  
2
80  
80  
1.0 3.1  
80  
90  
2
80  
90  
80  
90  
1.0 3.1  
2
110  
125  
125  
125  
35  
110  
1.0 3.1  
125  
2
125  
1.0 3.1  
125  
2
35  
40  
1.0 3.1  
45  
2
40  
35  
1.0 3.1  
50  
45  
2
40  
35  
1.0 3.1  
50  
40  
2
2
45  
35  
1.0 3.1  
50  
70  
45  
60  
1
575  
518 633  
7.0  
55.0  
7.0  
55.0  
7.0  
55.0 4.0  
1.0 3.1  
80  
70  
2
70  
60  
1.0 3.1  
80  
70  
2
2
90  
100  
1.0 3.1  
100  
100  
100  
100  
100  
1.0 3.1  
110  
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp FLA Qty Hp  
MCA  
MOCP*  
FLA  
016  
208/240  
187 253  
NA  
NA  
NA  
NA  
NA  
NA  
NA NA  
NA  
56/75 156/180 NA NA NA NA  
NA  
156/180 175/200  
200/225  
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
176/198 200/225  
200/225  
225/250  
200/225  
225/250  
3.7 10.6/ 9.6  
5.0 16.7/15.2  
1.0 5.9 190/213 200/225  
183/205 200/225  
1.0 5.9 198/220 200/225  
016  
208/230  
187 253 16.7 130.0 16.7 130.0 16.7 130.0 4.0 1/4 1.5 56/75 156/180  
2
See Legend and Notes on page 10.  
16  
Table 2B Electrical Data (Units With Optional Convenience Outlet) (cont)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
89/ 88  
101/ 99  
97/ 94  
109/106  
92/100  
110/110  
110/110  
110/110  
125/125  
110/110  
110/125  
110/110  
125/125  
175/150  
175/175  
175/175  
200/175  
100/ 90  
110/110  
100/100  
125/110  
100/ 90  
110/110  
100/100  
125/110  
150/175  
175/175  
150/175  
175/200  
100/ 90†  
110/110†  
100/100†  
125/110†  
45  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
1.0 5.9  
2
1.0 5.9  
2
1.0 5.9  
107/115  
102/109  
116/124  
157/145  
172/160  
167/154  
181/169  
19/25  
52/ 60  
2
1.0 5.9  
1
208/230  
187 253 16.7 130.0 16.7 130.0 22.4 184.0 4.0  
/
1.5  
0.7  
0.7  
4
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
89/ 88110/110†  
101/ 99110/110†  
97/ 94110/110†  
109/106125/125†  
1.0 5.9  
56/75156/180  
2
1.0 5.9  
2
45  
51  
48  
54  
51  
59  
55  
63  
73  
81  
78  
85  
103  
111  
108  
115  
38  
44  
40  
47  
41  
49  
45  
53  
69  
77  
73  
80  
86  
94  
90  
98  
50  
60  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
7.6  
11.0  
7.6  
1.0 3.1  
60  
25  
50  
75  
25  
48  
78  
30  
60  
90  
24  
46  
75  
2
50  
50  
1.0 3.1  
60  
60  
2
60  
60  
45  
60  
1.0 3.1  
2
60  
50  
11.0  
7.6  
1.0 3.1  
70  
60  
1
020  
460  
414 506  
9.0 70.0  
9.0  
70.0 10.7  
90.0 4.0  
/
4
2
80  
80  
1.0 3.1  
90  
90  
2
80  
90  
90  
90  
11.0  
7.6  
1.0 3.1  
2
125  
125  
125  
125  
45  
125  
1.0 3.1  
125  
2
125  
11.0  
6.1  
1.0 3.1  
125  
2
40  
45  
1.0 3.1  
50  
2
45  
45  
9.0  
1.0 3.1  
50  
50  
2
45  
40  
6.1  
1.0 3.1  
50  
45  
2
2
45  
45  
9.0  
1.0 3.1  
60  
70  
50  
60  
1
575  
518 633  
7.0 55.0  
7.0  
55.0  
9.3  
73.0 4.0  
/
4
6.1  
1.0 3.1  
80  
70  
2
80  
70  
9.0  
1.0 3.1  
90  
80  
2
2
100  
100  
100  
100  
100  
6.1  
1.0 3.1  
110  
100  
9.0  
1.0 3.1  
110  
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp FLA Qty Hp  
MCA  
MOCP*  
FLA  
020  
208/240  
187 253  
NA  
NA  
NA  
NA  
NA  
NA  
NA NA  
NA  
56/75 156/180 NA NA NA NA  
NA  
156/180 175/200  
200/225  
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
183/205 200/225  
200/225  
225/250  
225/250  
225/250  
5.0 16.7/15.2  
7.5 24.2/22.0  
1.0 5.9 198/220 200/225  
193/214 200/225  
1.0 5.9 207/229 225/250  
1
020  
208/230  
187 253 16.7 130.0 16.7 130.0 22.4 184.0 4.0  
/
4
1.5 56/75 156/180  
2
See Legend and Notes on page 10.  
17  
Table 2B Electrical Data (Units With Optional Convenience Outlet) (cont)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
101/ 99  
112/111  
109/106  
120/118  
101/100  
112/115  
109/109  
120/124  
157/145  
172/160  
167/154  
181/169  
110/110  
125/125  
125/125  
125/125  
110/110  
125/125  
125/125  
125/125  
175/150  
175/175  
175/175  
200/175  
110/110  
125/125  
125/110  
150/125  
110/110  
125/125  
125/110  
150/125  
150/175  
175/175  
150/175  
175/200  
110/110†  
125/125†  
125/110†  
150/125†  
50  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
5.0 16.7/15.2  
7.5 24.2/22.0  
1.0 5.9  
2
1.0 5.9  
2
1.0 5.9  
19/25  
52/ 60  
2
1.0 5.9  
1
208/230  
187 253 22.4 184.0 22.4 184.0 22.4 184.0 4.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
101/ 99110/110†  
112/111125/125†  
109/106125/125†  
120/118125/125†  
1.0 5.9  
56/75156/180  
2
1.0 5.9  
2
48  
54  
52  
58  
51  
59  
55  
63  
73  
81  
78  
85  
103  
111  
108  
115  
42  
48  
45  
51  
42  
49  
45  
53  
69  
77  
73  
80  
86  
94  
90  
98  
50  
60  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
5.0  
7.5  
7.6  
11.0  
7.6  
1.0 3.1  
60  
25  
50  
75  
25  
48  
78  
30  
60  
90  
24  
46  
75  
2
60  
60  
1.0 3.1  
60  
60  
2
60  
60  
50  
60  
1.0 3.1  
2
60  
60  
11.0  
7.6  
1.0 3.1  
70  
60  
1
024  
460  
414 506 10.7  
90.0 10.7  
90.0 10.7  
90.0 4.0  
2
80  
80  
1.0 3.1  
90  
90  
2
80  
90  
90  
90  
11.0  
7.6  
1.0 3.1  
2
125  
125  
125  
125  
50  
125  
1.0 3.1  
125  
2
125  
11.0  
6.1  
1.0 3.1  
125  
2
45  
50  
1.0 3.1  
50  
2
50  
50  
9.0  
1.0 3.1  
60  
60  
2
50  
45  
6.1  
1.0 3.1  
50  
50  
2
2
50  
50  
9.0  
1.0 3.1  
60  
70  
60  
60  
1
575  
518 633  
9.3  
73.0  
9.3  
73.0  
9.3  
73.0 4.0  
6.1  
1.0 3.1  
80  
70  
2
80  
70  
9.0  
1.0 3.1  
90  
80  
2
2
100  
100  
100  
100  
100  
6.1  
1.0 3.1  
110  
100  
9.0  
1.0 3.1  
110  
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp FLA Qty Hp  
MCA  
MOCP*  
FLA  
024  
208/240  
187 253  
NA  
NA  
NA  
NA  
NA  
NA  
NA NA  
NA  
56/75 156/180 NA NA NA NA  
NA  
156/180 175/200  
200/225  
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
183/205 200/225  
200/225  
225/250  
225/250  
225/250  
5.0 16.7/15.2  
7.5 24.2/22.0  
1.0 5.9 198/220 200/225  
193/214 200/225  
1.0 5.9 207/229 225/250  
1
024  
208/230  
187 253 22.4 184.0 22.4 184.0 22.4 184.0 4.0  
/
4
1.5 56/75 156/180  
2
See Legend and Notes on page 10.  
18  
Table 2B Electrical Data (Units With Optional Convenience Outlet) (cont)  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
144/142  
156/154  
151/148  
163/160  
144/142  
156/154  
151/148  
163/160  
167/154  
181/169  
175/161  
190/176  
175/175  
200/200  
175/175  
200/200  
175/175  
200/200  
175/175  
200/200  
175/175  
200/200  
175/175  
200/200  
150/150  
175/175  
175/175  
175/175  
150/150  
175/175  
175/175  
175/175  
150/175  
175/200  
175/175  
175/200  
150/150†  
175/175†  
175/175†  
175/175†  
70  
7.5 24.2/22.0  
10.0 30.8/28.0  
7.5 24.2/22.0  
10.0 30.8/28.0  
7.5 24.2/22.0  
10.0 30.8/28.0  
7.5 24.2/22.0  
10.0 30.8/28.0  
1.0 5.9  
2
1.0 5.9  
2
1.0 5.9  
19/25  
52/ 60  
2
1.0 5.9  
1
208/230  
187 253 47.1 245.0 47.1 245.0  
414 506 19.6 125.0 19.6 125.0  
518 633 15.8 100.0 15.8 100.0  
6.0  
6.0  
6.0  
/
/
/
1.5  
0.7  
0.7  
4
4
4
2
1.0 5.9  
38/50 104/120  
2
1.0 5.9  
2
144/142175/175†  
156/154200/200†  
151/148175/175†  
163/160200/200†  
1.0 5.9  
56/75156/180  
2
1.0 5.9  
2
62  
69  
65  
72  
62  
69  
65  
72  
78  
85  
81  
89  
108  
115  
111  
119  
52  
58  
54  
60  
52  
58  
54  
60  
73  
80  
75  
83  
90  
98  
93  
100  
80  
80  
7.5  
10.0  
7.5  
11.0  
14.0  
11.0  
14.0  
11.0  
14.0  
11.0  
14.0  
9.0  
1.0 3.1  
70  
25  
50  
75  
25  
48  
78  
30  
60  
90  
24  
46  
75  
2
80  
70  
1.0 3.1  
90  
80  
2
80  
80  
70  
70  
1.0 3.1  
2
80  
70  
10.0  
7.5  
1.0 3.1  
90  
80  
1
028  
460  
2
80  
90  
1.0 3.1  
90  
90  
2
90  
90  
100  
10.0  
7.5  
1.0 3.1  
100  
125  
125  
125  
125  
60  
2
125  
1.0 3.1  
125  
2
125  
10.0  
7.5  
1.0 3.1  
150  
2
60  
60  
1.0 3.1  
70  
2
60  
60  
10.0  
7.5  
11.0  
9.0  
1.0 3.1  
70  
70  
2
60  
60  
1.0 3.1  
70  
60  
2
2
60  
60  
10.0  
7.5  
11.0  
9.0  
1.0 3.1  
70  
80  
70  
70  
1
575  
1.0 3.1  
90  
80  
2
80  
70  
10.0  
7.5  
11.0  
9.0  
1.0 3.1  
90  
80  
2
2
100  
100  
100  
110  
100  
1.0 3.1  
110  
100  
10.0  
11.0  
1.0 3.1  
110  
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
(ea)  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp FLA Qty Hp  
MCA  
MOCP*  
FLA  
028  
208/240  
187 253  
NA  
NA  
NA  
NA  
NA  
NA  
NA NA  
NA  
56/75 156/180 NA NA NA NA  
NA  
156/180 175/200  
200/225  
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT  
COMPRESSOR  
No. 2  
VOLTAGE  
RANGE  
ELECTRIC  
HEAT  
POWER  
POWER  
SUPPLY  
DISCONNECT  
SIZE  
OFM  
IFM  
FLA  
UNIT  
SIZE  
NOMINAL  
VOLTAGE  
EXHAUST  
No. 1  
No. 3  
FLA  
(ea)  
FLA  
50HG (3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA RLA LRA Qty Hp  
kW  
FLA  
Hp  
Qty Hp  
MCA  
MOCP*  
FLA  
(ea)  
2
193/214 200/225  
225/250  
225/250  
225/250  
250/300  
7.5 24.2/22.0  
10.0 30.8/28.0  
1.0 5.9 207/229 225/250  
201/221 225/225  
1.0 5.9 216/236 225/250  
1
028  
208/230  
187 253 47.1 245.0 47.1 245.0  
6.0  
/
1.5 56/75 156/180  
4
2
See Legend and Notes on page 10.  
19  
3. Remove the bracket holding the bottom half of the hood  
in the shipping position. Remove the hood bottom half  
and filters (or manual dampers on units so equipped)  
from outdoor section.  
NOTE: On units without economizers, the components  
are attached to the unit basepan. To access the compo-  
nents, remove the panel below the outdoor air intake  
section.  
4. Remove inner filter track from shipping position in out-  
door section. Position inner filter track so the track is fac-  
ing outward from the unit. Install the filter track with  
4 screws provided.  
LEGEND  
5. Apply seal strip (provided) to back flange of both hood  
sides where hood side connects to the unit back panel.  
See Fig. 16.  
6. Apply seal strip (provided) to top flange of both hood  
sides where hood sides connect to the hood top panels.  
See Fig. 16.  
7. Install hood sides to the back panels using the screws from  
Step 2. The sloped flanges point outward. The drip edges  
of the side panels should face outward as well. The filter  
guides should face inward to hold the filters in place. See  
Fig. 16.  
8. Apply seal strip along the entire length of the bottom  
flange of the hood top. See Fig. 16.  
EQUIP Equipment  
GND Ground  
NEC  
TB  
National Electrical Code  
Terminal Board  
NOTE: The maximum wire size for TB1 is 2/0.  
Fig. 12 Field Power Wiring Connections  
THERMOSTAT ASSEMBLY  
REMOVABLE JUMPER  
L
RH  
RC  
Y1  
Y2  
W1  
W2  
G
C
X
R
1
Y1  
2
Y2  
3
W1  
4
W2  
5
G
6
C
7
X
8
9. Install the bottom part of the hood top using 4 screws pro-  
vided. See Fig. 16.  
TB4  
10. Remove the packaging from filters (3) and install into the  
filter tracks. Slide the filters to the sides then place the last  
filter into the center of the filter track.  
Fig. 13 Field Control Thermostat Wiring  
NOTE: For units with manual dampers, replace the end filters  
with the manual dampers. Install the filter in the center  
between the manual dampers.  
T-55 SPT  
T1 T2  
T-56 SPT  
COM  
TH  
SN  
11. Install the filter retainer track along the bottom edge of the  
outdoor air hood using 4 screws provided. See Fig. 16.  
12. Install top section of the outdoor air hood using 9 screws  
provided. See Fig. 16. See Fig. 17 for a picture of the  
assembled outdoor air hood.  
TB3  
7
8
9
NOTE: For filter removal, remove the four screws holding the  
filter retainer. The filters can then be removed, cleaned, or  
replaced. Install the filters by reversing the procedure.  
SPT Space Temperature Sensor  
MANUAL DAMPER ASSEMBLY For units equipped  
with manual dampers, the assembly process is similar to the out-  
door air hood for units with economizers. There are two slide  
dampers shipped with the unit to allow for manual setting of the  
outside air volume. When assembling the hood, place one of the  
manual slide dampers in each of the end positions and the re-  
maining filter in the center position. The manual dampers can  
then be moved to the appropriate position and then locked into  
place using the screws mounted in the adjustment slots. See  
Fig. 18.  
Fig. 14 Field Control Space  
Temperature Sensor Wiring  
Set heat anticipator settings as shown inTable 3.  
Table 3 Heat Anticipator Settings  
STAGE 1  
(W1) ON  
Voltage  
STAGES 1 AND 2  
(W1 and W2) ON  
Voltage  
UNIT SIZE ELECTRIC  
50HG  
HEAT (kW)  
208/240 480 600 208/240 480 600  
15  
25  
50  
25  
50  
75  
0.2  
0.2  
0.4  
0.2  
0.4  
0.4  
0.2  
0.2  
0.2  
0.2  
0.2  
0.2  
0.2  
0.2  
0.2  
0.2  
0.2  
0.2  
0.2  
0.4  
0.8  
0.4  
0.8  
0.8  
0.2  
0.4  
0.4  
0.4  
0.4  
0.4  
0.2  
0.4  
0.4  
0.4  
0.4  
0.4  
HOOD  
SIDE  
HOOD TOP  
(BOTTOM HALF)  
014  
HOOD TOP  
(TOP HALF)  
HOOD  
SIDE  
016-028  
Settings may be changed slightly to provide a greater degree  
of comfort for a particular installation.  
RETURN AIR  
SECTION  
Step 8 Install Outdoor Air Hood Perform the  
following procedure to install the outdoor-air hood:  
1. Remove blank panel from return end of unit (hood sec-  
tion). Save the screws. See Fig. 15 for shipping location  
of components.  
2. Hood sides are fastened to sides of outdoor air opening.  
Remove the hood sides and save the screws (3 each side).  
Fig. 15 Outdoor-Air Hood Compartment  
Shipping Location  
20  
TOP HOOD  
SECTION  
ADD  
SEAL  
STRIP  
SEAL  
HOOD  
SIDE  
ADD  
SEAL  
STRIP  
STRIP  
LOCATION  
INNER  
FILTER  
TRACK  
BOTTOM  
HOOD  
SECTION  
ADD  
SEAL  
STRIP  
ADD  
SEAL  
STRIP  
FILTER  
GUIDE  
FILTER  
RETAINER  
FILTER  
GUIDE  
FILTER  
HOOD  
SIDE  
MANUAL  
DAMPER  
(IF EQUIPPED)  
UNIT  
BACK  
PANEL  
NOTE: Units with manual damper only use one filter.  
Fig. 16 Outdoor Air Hood Details  
LOCKING SCREW  
MOVEABLE DAMPER  
AIR FILTER POSITION  
MOVEABLE DAMPER  
Fig. 17 Outdoor Air Hood Assembled  
Fig. 18 Manual Damper Details  
21  
Step 9 Position Optional Power Exhaust or  
Barometric Relief Damper Hood The optional  
power exhaust or barometric relief dampers are shipped  
assembled and tilted back into the unit for shipping. Brack-  
ets and extra screws are shipped in shrink wrap around the  
dampers.  
BE SURE POWER IS SHUT OFF TO THE UNIT FROM  
THE BUILDING POWER SUPPLY.  
1. Open the control box access door.  
1. Remove 9 screws holding each damper assembly in  
place. See Fig. 19. Each damper assembly is secured with  
3 screws on each side and 3 screws along the bottom.  
Save screws.  
2. Remove the small cover plate located on the unit corner  
post near the control section.  
3. Remove the inner control box cover. The handle and shaft  
are located in a plastic bag at the bottom of the control  
box.  
4. Insert the square shaft into the disconnect with the pins  
vertical. On the 100 amp disconnect the shaft is keyed  
into the disconnect and can only be installed one way  
with the pins vertical.  
Be careful when tilting blower assembly. Hoods and blow-  
ers are heavy and can cause injury if dropped.  
2. Pivot the damper assembly outward until top edge of  
damper assembly rests against inside wall of unit.  
3. Secure each damper assembly to unit with 6 screws  
across top (3 screws provided) and bottom (3 screws  
from Step 1) of damper.  
4. With screws saved from Step 1, install brackets on each  
side of damper assembly. See Fig. 20.  
5. Remove tape from damper blades.  
5. Insert the handle through the corner post and onto the  
shaft with the handle positioned so that OFFis on top.  
6. Rotate the handle to the ONposition to lock the pins  
into the handle.  
7. From the inside of the corner post, attach the handle  
mounting screws to the handle. Slide the shaft fully into  
the handle and tighten the set screws(s) on the disconnect  
to lock the shaft. Tighten the screws that attach the handle  
to the corner post.  
8. Rotate the handle back to the OFFposition.  
9. Replace all panels and doors.  
Step 10 Non-Fused Disconnect The handle  
for the factory-installed non-fused disconnect is shipped inside  
the unit to prevent the handle from damage during shipping.  
Follow these steps to complete installation of the handle.  
10. Restore power to unit.  
Fig. 19 Power Exhaust or Barometric Relief Damper Mounting Details  
22  
Step 11 Install All Accessories After all of  
the factory-installed options have been adjusted, install all  
field-installed accessories. Refer to the accessory installation  
instructions included with each accessory. Consult the Carrier  
Price Pages for accessory package numbers for particular  
applications. The available field-installed accessories for the  
Centurion units are:  
economizer  
power exhaust  
barometric relief damper  
14-in. roof curb  
24-in. roof curb  
electric heaters  
enthalpy control  
differential enthalpy control  
plugged filter indicator  
carbon dioxide detector  
smoke detector  
filter status switch  
fan status switch  
condenser hail guard  
horizontal duct accessory  
thermostats  
two-position damper  
Fig. 20 Bracket and Hood Positioning  
23  
Copyright 2003 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 535-00092 Printed in U.S.A. Form 50HG-7SI Pg 24 11-03 Replaces: 50HG-3SI  
Book 1  
4
Tab 1b 6b  

AGE07 User Manual
Briggs Stratton 97000 User Manual
Briggs Stratton 401700 User Manual
Brother MFC J6910DW User Manual
Canon Pixma Mg5420 Inkjet Multifunction Printer 6225B002 User Manual
Friedrich Air Conditioner WS16 User Manual
Friedrich YQ07 User Manual
GE Zoneline AZ28E12EAC User Manual
Groupe SEB USA T FAL Digital Watch Babyphone Watch Babyphone 912471 User Manual
Heat Controller Inc Air Conditioner HDG60 User Manual