Carrier 48HJ004 014 User Manual

48HJ004-014  
Single-Package Rooftop  
Heating/Cooling Units  
User’s Information Manual  
NOTE TO INSTALLER:  
TO LIGHT UNIT  
This manual should be left with the equipment owner.  
1. Do not turn off the electrical power to unit without  
first turning off the gas supply.  
2. Before attempting to start the gas heating section,  
familiarize yourself with all the procedures that must  
be followed.  
WARNING: If the information in this manual is  
not followed exactly, a fire or explosion may  
result causing property damage, personal  
injury or loss of life.  
— Do not store or use gasoline or other flam-  
mable vapors and liquids in the vicinity of  
this or any other appliance.  
If you do not follow these instructions exactly, a fire or  
explosion may result. Property damage, injury, or loss of  
life could occur.  
— WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
See Fig. 1A and 1B for location of gas valve. Refer to Fig. 2  
while proceeding with the following steps.  
• Do not touch any electrical switch; do  
not use any phone in your building.  
Step 1 — Set room thermostat to the lowest temperature  
setting and set SYSTEM switch to HEAT or AUTO. position.  
• Immediately call your gas supplier from a  
neighbor’sphone. Followthegassupplier’s  
instructions.  
• If you cannot reach your gas supplier,  
call the fire department.  
Step 2 — Close the manual gas valve.  
Step 3 — Turn off the electrical supply to the unit, tag  
disconnect.  
Step 4 — Remove the compressor access panel.  
— Installation and service must be performed  
by a qualified installer, service agency or the  
gas supplier.  
Step 5 — Move the gas valve switch to the OFF position  
and wait 5 minutes.  
Step 6 — Move the gas valve switch to the ON position.  
Step 7 — Replace the compressor access panel.  
Step 8 — Turn on the electrical supply to unit.  
Step 9 — Open the manual gas valve.  
Improper installation, adjustment, alteration, ser-  
vice or maintenance can cause property damage,  
serious injury or death. Refer to this manual. For  
assistance or additional information consult a  
qualified installer, service agency, or the gas  
supplier.  
Step 10 — Set room thermostat selector slightly above  
room temperature to start unit. The induced-draft combustion  
air fan will start. Main gas valve will open and main burners  
should ignite within 5 seconds. If the burners do not light, there  
is a 22-second delay before another 5-second try. If the burner  
still does not light, the time delay is repeated. If the burner does  
not light within 15 minutes, there is a lockout. To reset the con-  
trol, break the 24-v power to W1. Repeat Steps 1-10. If burners  
still do not light, call for service.  
Before performing recommended maintenance, be sure  
main power switch to unit is turned off. Electrical shock  
could cause serious injury or death.  
Step 11 — Set the temperature selector on room thermostat  
to desired setting.  
Your rooftop combination heating/cooling unit is equipped  
with an automatic direct spark ignition and induced-draft com-  
bustion blower.  
If the main burners fail to light, or the blower fails to come  
on, shut down gas heating section and call your dealer for  
service. Failure to follow these requirements could result in  
serious injury or death.  
Do not attempt to light by hand; serious injury or death  
may result.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 534-80017 Printed in U.S.A. Form 48HJ-2SO Pg 1 11-00 Replaces: 48GJ,HJ-1SO  
Book 1  
4
Tab 1a 6a  
MAIN  
ON  
OFF  
LOCK-OUT  
G
TA  
STEP 1  
STEP 2  
STEP 3  
SINGLE-STAGE GAS  
VALVE  
2-STAGE GAS VALVE  
W R  
STEP 4  
SINGLE-STAGE GAS  
VALVE  
2-STAGE GAS VALVE  
48HJD005,006*  
48HJE004-006*  
48HJF004-006*  
48HJD007-014  
48HJE007-014  
48HJF007-014  
48HJD005,006†  
48HJE004-006†  
48HJF004-006†  
48HJG005,006  
48HJH004-006  
48HJK004-006  
48HJL005,006  
48HJM004-006  
48HJN004-006  
W R  
STEP 5  
48HJD005,006†  
48HJE004-006†  
48HJF004-006†  
48HJG005,006  
48HJH004-006  
48HJK004-006  
48HJL005,006  
48HJM004-006  
48HJN004-006  
48HJD005,006*  
48HJE004-006*  
48HJF004-006*  
48HJD007-014  
48HJE007-014  
48HJF007-014  
STEP 6  
STEP 7  
STEP 10  
STEP 9  
STEP 8  
*3-phase units only.  
Single-phase units only.  
Fig. 2 — To Light Unit  
3
MAIN  
ON  
OFF  
LOCK-OUT  
G
TA  
STEP 3  
STEP 1  
STEP 2  
STEP 4  
SINGLE-STAGE GAS  
VALVE  
2-STAGE GAS VALVE  
W R  
48HJD005,006*  
48HJE004-006*  
48HJF004-006*  
48HJD007-014  
48HJE007-014  
48HJF007-014  
48HJD005,006†  
48HJE004-006†  
48HJF004-006†  
48HJG005,006  
48HJH004-006  
48HJK004-006  
48HJL005,006  
48HJM004-006  
48HJN004-006  
*3-phase units only.  
Single-phase units only.  
STEP 5  
STEP 6  
STEP 7  
Fig. 3 — To Shut Unit Off  
4
Units with outdoor air capability have a cleanable filter for  
the outdoor air. This filter should be checked semi-annually  
and cleaned as necessary with steam or hot water and a mild  
detergent. Do not use throwaway filters in place of cleanable  
ROUTINE MAINTENANCE AND CARE  
FOR THE EQUIPMENT OWNER  
Consider the following information before maintaining or  
servicing equipment:  
filters.  
.
1. TURN OFF GAS SUPPLY AND THEN ELECTRI-  
CAL POWER TO YOUR UNIT AND INSTALL  
LOCKOUT TAG BEFORE SERVICING OR PER-  
FORMING MAINTENANCE.  
2. Do not turn off electrical power to this unit without  
first turning off the gas supply.  
Never operate your unit without filters in place. Failure to  
heed this warning may result in damage to the blower  
motor, compressor and/or evaporator coil. An accumula-  
tion of dust and lint on internal parts of your unit can cause  
loss of efficiency and, in some cases, fire that could result  
in serious injury or death.  
3. When removing access panels or performing mainte-  
nance functions inside your unit, be aware of sharp  
sheet metal parts and screws. Although special care  
has been taken to reduce sharp edges inside the unit,  
be extremely careful when handling parts or reaching  
into the unit.  
Table 1 — Indoor-Air Filter Data for 48HJ  
INDOOR-AIR FILTERS  
UNIT SIZE  
48HJ  
(Throwaway Fiberglass)  
Quantity  
Size (in.)  
16 x 25 x 2  
16 x 25 x 2  
20 x 20 x 2  
004-007  
008,009  
012,014  
2
4
4
4. Failure to follow these instructions could result in  
serious injury or death.  
NOTE: Replacement filters should be UL (UnderwritersLaborato-  
Air Filter(s) — Air filter(s) should be checked at least  
every 3 or 4 weeks and changed or cleaned when necessary.  
Table 1 indicates the correct filter size for your unit. See Fig. 4  
for filter access panel location.  
ries) certified or equivalent.  
FILTER ACCESS PANEL  
1. Lift up and remove filter access panel.  
2. While holding filter, tilt upper filter rack.  
3. Remove filters by pulling up and out toward you from the  
track.  
4. Inspect or replace filters.  
5. Return filters t filter tracks. Note direction of airflow ar-  
rows on filter frame.  
6. Reinstall filter access panel.  
If you have difficulty in locating your air filter or if you  
have questions concerning proper filter maintenance, contact  
your dealer for instructions. When replacing your unit filters,  
always use the same size and type of filter that was originally  
supplied by the installer.  
Fig. 4 — Typical Filter Access Panel Location  
(48HJ008-014 Shown)  
5
Heat Exchanger  
Combustion Area and Vent System — The com-  
bustion area and vent system should be visually inspected be-  
fore each heating season. The normal accumulation of dirt,  
soot, rust, and scale can result in loss of efficiency and improp-  
er performance if allowed to build up.  
NOTE: To ensure dependable and efficient heating operation,  
the heat exchanger should be checked by a qualified mainte-  
nance person before each heating season, and cleaned when  
necessary.  
If your unit makes any unusual or especially loud noises  
during heating, shut down the heating section and call your  
qualified Carrier service technician.  
This checkout should not be attempted by anyone not hav-  
ing the required expertise and equipment to do the job  
properly.  
See Fig. 1A, 1B, and 5 and proceed as follows to inspect the  
combustion area and power-venting system of your unit.  
1. Turn off gas supply to your unit.  
2. Turn off electrical power to your unit; install lockout tag.  
3. Remove compressor access panel.  
4. Using a flashlight, carefully inspect the burner areas for  
dirt, soot, or scale.  
Checking and/or cleaning the heat exchanger involves  
removing the gas controls assembly and the flue collector box  
cover. When finished, the gas controls must be reinstalled for  
proper operation. Also, the flue collector box cover must be  
replaced correctly so that a proper seal is maintained. Contact  
your dealer for the required periodic maintenance. At the  
beginning of each cooling/heating season and as conditions  
require.  
Fans and Belts, and Fan Motor — Periodically check  
the condition of fan wheels and housings, belt tension and fan  
motor shaft bearings. No lubrication of condenser or evapora-  
tor fan bearings or motors is required or recommended.  
If dirt, soot, rust or scale accumulations are found, call your  
dealer and do not operate your heating section.  
Evaporator and Condenser Coils — Cleaning of  
the coils should be done by qualified service personnel. Con-  
tact you dealer for the required annual maintenance.  
5. When you have completed your inspection, follow the  
start-up procedures in this manual to restore your unit to  
operation.  
Condensate Drain — The drain pan and condensate  
drain line should be checked and cleaned at the same time the  
cooling coils are checked by your dealer.  
6. Observe unit heating operation.  
Compressor — All compressors are factory supplied with  
a normal charge of the correct type refrigeration-grade oil in  
them and should not require additional oil.  
Components in heat section may be hot after unit has been  
started up. When observing flame, be careful not to get  
close to or touch heating components. Serious injury could  
result.  
Condenser Fan  
Watch the burner flame to see if it is bright blue. If you  
observe a suspected malfunction or that the burner flame  
is not bright blue, call your dealer.  
Do not poke sticks, screwdrivers, or any other object into  
revolving fan blades. Severe bodily injury could result.  
7. Replace compressor access panel.  
The fan must be kept free of all obstructions to ensure prop-  
er cooling. Contact your dealer for any required service.  
Unit Panels — After performing any maintenance or  
service on the unit, be sure all panels are securely fastened in  
place to prevent rain from entering unit cabinet and to prevent  
disruption of the correct unit airflow pattern.  
ElectricalControlsandWiring — Ensure wires do  
not contact refrigerant tubing or sharp edges. Electrical con-  
trols are difficult to check without proper instrumentation. If in-  
adequate cooling is suspected, contact your qualified local  
dealer for service.  
6
2. Inspection of all combustion- and ventilation-air passages  
and openings.  
3. Close inspection of all gas pipes leading to and inside  
your unit.  
4. Inspection and if required, cleaning of the condenser and  
evaporator coils.  
5. Inspection, and if required, cleaning of the condensate  
drain pan.  
6. Inspection and cleaning of blower wheel housing and  
motor.  
7. Inspection of all supply- and return-air ducts for leaks,  
obstructions, and insulation integrity. Any problems  
found should be resolved at the time of inspection.  
8. Inspection of the unit base for cracks, gaps, etc., which  
may cause a hazardous condition.  
9. Inspection of the unit casing for signs of deterioration.  
10. Inspection of all electrical wiring and components to  
ensure proper connection.  
11. Inspection for leaks in the refrigerant circuit. Pressure-  
check to determine appropriate refrigerant charge  
12. Inspection of fan wheels and housings, belt tension, and  
fan motor shaft bearings.  
13. Operational check of the unit to determine working con-  
ditions. Repair or adjustment should be made at the time  
of inspection.  
Fig. 5 — Typical Heat Section Detail  
REGULAR DEALER MAINTENANCE  
Your servicing dealer may offer an economical service  
contract that covers seasonal inspections. Ask for further  
details.  
In addition to the type of routine maintenance you might be  
willing to perform, your unit should be inspected regularly by a  
properly trained and qualified Carrier service technician. An  
inspection (preferably each heating/cooling season, but at least  
every year) should include the following:  
Complete service instructions can be found in the unit  
Installation, Start-Up and Service Instructions.  
1. Inspection of all flue product passages — including the  
burners, heat exchanger, and flue collector box.  
7
NOTE: Before proceeding with the next check, turn OFF the  
electrical power supply to the unit. Remove the control access  
door.  
BEFORE YOU CALL FOR SERVICE,  
CHECK FOR PROBLEMS  
THAT CAN BE EASILY SOLVED  
(
) During the heating season, check the control switch on  
If insufficient heating or cooling is suspected:  
) Check for sufficient airflow. Check the air filter for dirt.  
Check for blocked return- or supply-air grilles. Be sure they  
are open and unobstructed. If these checks do not reveal the  
cause, call your servicing dealer.  
If your unit is not operating at all, check the following list  
for easy solutions:  
the gas valve. Is it in the ON position? If it is not, be sure it has  
not been turned off for the purpose of safety. If no safety haz-  
ards are present, follow the start-up procedures in this manual.  
(
(
) If your unit still fails to operate, call your servicing dealer  
for troubleshooting and repairs. Specify the model and serial  
numbers of your unit. (Record them in this manual in the space  
provided.) If the dealer knows exactly which unit you have, he  
may be able to offer suggestions over the phone, or save valu-  
able time through knowledgeable preparation for the service  
call.  
(
) Check to be sure that your thermostat temperature selec-  
tor is set above the indoor temperature during the heating sea-  
son, or below the indoor temperature during the cooling  
season. Be sure the SYSTEM switch in the proper HEAT or  
COOL position and not in the OFF position.  
IN CASE OF TROUBLE  
(
) Is the electrical supply switch ON? Are any fuses blown,  
or has the circuit breaker tripped?  
) During the heating season, check the external manual  
shutoff valve. Is this lever parallel with the pipe, indicating that  
the valve is open? Or is the lever at the right angle, indicating  
that the valve is closed? If closed, has the gas been shut off for  
safety reasons? Otherwise, you may open the valve and follow  
the start-up procedures listed in this manual.  
If, after performing the above checks, unit performance is  
unsatisfactory, shut off the unit and call your dealer.  
(
Dealer’s Name _____________________________________  
Telephone No.______________________________________  
Unit Model ________________________________________  
Unit Serial Number _________________________________  
Copyright 2000 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 534-80017 Printed in U.S.A. Form 48HJ-2SO Pg 8 11-00 Replaces: 48GJ,HJ-1SO  
Book 1  
4
Tab 1a 6a  

Canon PIXMA MX350 User Manual
Energizer Battery Charger CHFC User Manual
Epson AcuLaser CX11NF User Manual
Eveready Battery Charger EV2PC2 User Manual
Friedrich CP12F10 User Manual
GE Zoneline AZ6100 User Manual
Graco Baby Monitor 2791 User Manual
Harbor Freight Tools BOTTLE JACK 93376 User Manual
HoMedics Shiatsu and Vibration Massaging Cussion MCS300HW User Manual
HP Hewlett Packard AFICIO SP 8100DN User Manual