40RM007-034
40RMQ008-028
40RMS008-034
Packaged Air-Handling Units
50/60 Hz
Installation, Start-Up and
Service Instructions
Recognize safety information. This is the safety-alert sym-
bol ( ). When you see this symbol on the unit and in instruc-
tions or manuals, be alert to the potential for personal injury.
CONTENTS
Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
Understand the signal words — DANGER, WARNING,
and CAUTION. These words are used with the safety-alert
symbol. Danger identifies the most serious hazards which will
result in severe personal injury or death. Warning indicates a
condition that could result in personal injury. Caution is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components and
equipment location (elevated structures, etc.).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment.
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils, and cleaning and replacing filters.
All other operations should be performed by trained service
personnel.
PRE-INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
Moving and Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Isolation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant and Chilled Water
Piping Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Power Supply and Wiring . . . . . . . . . . . . . . . . . . . . . . . 21
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Return-Air Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
•
•
•
Follow all safety codes.
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-45
Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Motor Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Shaft Bearings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fan Shaft Position Adjustment . . . . . . . . . . . . . . . . . . 26
Individual Fan Wheel Adjustment . . . . . . . . . . . . . . . 26
Fan Belts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Pulley and Drive Adjustment . . . . . . . . . . . . . . . . . . . . 27
Condensate Drains. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Return-Air Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Chilled Water Coil Freeze Protection . . . . . . . . . . . . 27
Coil Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Wear safety glasses and work gloves.
Use care in handling, rigging, and setting bulky
equipment.
Be sure all power to equipment is shut off before perform-
ing maintenance or service. More than one disconnect may
be present. Failure to do so may result in personal injury or
damage to the unit.
PRE-INSTALLATION
1. The power supply (v, ph, and Hz) must correspond to that
specified on unit rating plate.
2. The electrical supply provided by the utility must be suf-
ficient to handle load imposed by this unit.
3. Refer to Installation, General section (page 2) and
Fig. 1A-1C for locations of electrical inlets, condensate
drain, duct connections, and required clearances before
setting unit in place.
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . CL-1,CL-2
SAFETY CONSIDERATIONS
4. This installation must conform with local building codes
and with the NEC (National Electrical Code) or ANSI
(American National Standards Institute)/NFPA (National
Fire Protection Association) latest revision. Refer to
provincial and local plumbing or wastewater codes and
other applicable local codes.
Improper installation, adjustment, alteration, service, main-
tenance, or use can cause explosion, fire, electric shock, or
other occurrences which may injure you or damage your
property. Consult qualified installer or service agency for
information or assistance. The qualified installer or agency
must use only factory-authorized kits or accessories when
modifying this product.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-00003 Printed in U.S.A. Form 40RM-23SI Pg 1 12-04 Replaces: 40RM-22SI
Book 1
4
Tab 3c 2e
Table 1A — 40RM Physical Data, English — Cooling Units
UNIT 40RM
NOMINAL CAPACITY (Tons)
007
6
008
012
10
014
016
15
024
20
028
25
034
30
1
1
7 /
12 /
2
2
OPERATING WEIGHT (lb)
Base Unit with TXV
Plenum
381
175
385
175
405
175
670
225
685
225
690
225
1020
325
1030
325
FANS
Qty...Diam. (in.)
Nominal Airflow (cfm)
1...15
2400
1800-
3000
1...15
3000
2250-
3750
1...15
4000
3000-
5000
2...15
5000
3750-
6250
2...15
6000
4500-
7500
2...15
8,000
6,000-
10,000
2...18
10,000
7,500-
12,500
2...18
12,000
9,000-
15,000
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)
208/230-1-60
1.3
2.4
1.0
2.4
2.4
2.4
2.0
2.4
—
—
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
2.4
2.0
2.9
2.9
3.0
2.9
3.7
3.0
2.9
5.0
5.0
5.0
7.5
7.5
7.5
10.0
10.0
10.0
230-3-50, 400-3-50
Motor Speed (rpm)
208/230-1-60
1725
1725
1725
1425
1725
1725
1725
1425
—
—
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
230-3-50, 400-3-50
1725
1725
1425
1725
1725
1425
1725
1725
1425
1745
1745
1425
1745
1755
1425
1745
1755
1425
REFRIGERANT
Operating charge (lb)
(approx per circuit)*
R-22
2.5/2.5
3.0
3.0
1.5/1.5
2.0/2.0
3.5/3.5
4.5/4.5
5.0/5.0
DIRECT-EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
6.67
1
12/12
—
15
8.33
1
15/15
—
15
10.0
2
13.25
2
17.67
2
19.88
2
24.86
2
29.83
2
No. of Splits
No. of Circuits per Split (3 Row/4 Row)
Split Type...Percentage
Fins/in.
9/9
9/12
12/16
13/18
15/20
18/24
Face...50/50
17
15
15
17
15
15
STEAM COIL
Max Working Pressure (psig at 260 F)
Total Face Area (sq ft)
Rows...Fins/in.
20
6.67
1...9
6.67
1...9
6.67
1...9
13.33
1...10
13.33
1...10
13.33
1...10
15.0
1...10
15.0
1...10
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
150
6.67
2...8.5
6.67
2...8.5
6.67
2...8.5
13.33
2...8.5
13.33
2...8.5
13.33
2...8.5
15.0
2...12.5
15.0
2...12.5
Water Volume
(gal)
8.3
1.1
13.9
1.85
14.3
1.90
3
(ft )
PIPING CONNECTIONS,
Quantity...Size (in.)
1
1
1
1
1
1
3
3
DX Coil — Suction (ODF)
1...1 /
1...1 /
2...1 /
2...1 /
2...1 /
2...1 /
2...1 /
2...1 /
8
8
8
8
8
8
8
8
5
5
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1... /
2... /
8
8
1
1
1...2 /
1...2 /
2
2
2
1
1
1... /
1...1 /
2
1
1
1
1...1 /
1...1 /
1...2
1...2
2
2
2
2
1
1...1 /
1...1 /
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...16 x 20 x 2
4...20 x 24 x 2
4...20 x 25 x 2
Quantity...Size (in.)
Access Location
4...16 x 24 x 2
4...16 x 24 x 2
Either Side
LEGEND
DX
—
Direct Expansion
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
3
Table 1B — 40RMQ Physical Data, English — Heat Pump Units
UNIT 40RMQ
NOMINAL CAPACITY (Tons)
008
012
10
016
15
024
20
028
25
1
7 /
2
OPERATING WEIGHT (lb)
Base Unit with TXV
Plenum
385
175
427
175
713
225
720
140
1050
180
FANS
Qty...Diam. (in.)
1...15
3000
1...15
4000
2...15
6000
2...15
8000
2...18
10,000
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)
208/230-1-60
2250-3750
3000-5000
4500-7500
6000-10,000
7500-12,500
2.4
2.4
2.0
2.4
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
2.4
2.0
2.9
3.7
3.0
2.9
5.0
5.0
5.0
7.5
7.5
7.5
230-3-50, 400-3-50
Motor Speed (rpm)
208/230-1-60
1725
1725
1725
1425
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
1725
1725
1425
1725
1725
1425
1745
1745
1425
1745
1755
1425
230-3-50, 400-3-50
REFRIGERANT
Operating charge (lb)
(approx per circuit)*
R-22
3.0
2.0/2.0
3.0/3.0
3.5/3.5
4.5/4.5
DIRECT-EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
8.33
1
10.0
2
9
19.88
19.88
2
18
24.86
2
No. of Splits
2
18
No. of Circuits per Split
Split Type...Percentage
Rows...Fins/in.
15
24/16
—
3...15
Face...50/50
4...15
Face...60/40
4...15
4...15
4...15
STEAM COIL
Max Working Pressure (psig at 260 F)
Total Face Area (sq ft)
Rows...Fins/in.
20
13.33
1...10
6.67
1...9
6.67
1...9
13.33
1...10
15.0
1...10
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
150
13.33
2...8.5
6.67
2...8.5
6.67
2...8.5
13.33
15.0
2...12.5
2...8.5
Water Volume
(gal)
8.3
1.1
13.9
1.85
3
(ft )
PIPING CONNECTIONS,
Quantity...Size (in.)
1
1
1
1
3
DX Coil — Vapor (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
1...1 /
2...1 /
2...1 /
2...1 /
2...1 /
8
8
8
8
8
5
5
5
5
1... /
2... /
2... /
2... /
1...2 /
8
8
8
8
1
1
1
1...2 /
1...2 /
2
2
2
2
2
2
2
2
1
1
1
1...1 /
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...1 /
1...1 /
1
1
1...1 /
1...1 /
1...2
1...2
1...2
1...2
2
2
1
1
1...1 /
1...1 /
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...16 x 20 x 2
Quantity...Size (in.)
4...20 x 24 x 2
4...20 x 25 x 2
Right or Left Side
4...16 x 24 x 2
Either Side
4...16 x 24 x 2
Access Location
LEGEND
DX
— Direct Expansion
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
4
Table 1C — 40RMS Physical Data, English — Chilled Water Units
UNIT 40RMS
NOMINAL CAPACITY (Tons)
008
010
012
10
014
016
15
024
20
028
25
034
30
1
1
1
7 /
8 /
12 /
2
2
2
OPERATING WEIGHT (lb)
Base Unit
Plenum
390
175
391
175
391
175
661
225
677
225
683
225
1035
325
1042
325
FANS
Qty...Diam. (in.)
1...15
3000
1...15
3400
1...15
4000
2...15
5000
2...15
6000
2...15
8000
2...18
2...18
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp
(Standard Motor)
208/230-1-60
10,000
12,000
2250-3750 2250-4250 3000-5000 3750-6250
4500-7500
6000-10,000 7500-12,500 9000-15,000
2.4
2.4
2.0
2.4
2.4
2.4
2.0
2.4
—
—
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
2.4
2.0
2.9
2.9
3.0
2.9
3.7
3.0
2.9
5.0
5.0
5.0
7.5
7.5
7.5
10.0
10.0
10.0
230-3-50 and 400-3-50
Motor Speed (rpm)
208/230-1-60
1725
1725
1725
1425
1725
1725
1725
1425
—
—
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
230-3-50 and 400-3-50
1725
1725
1425
1725
1725
1425
1725
1725
1425
1745
1745
1425
1745
1755
1425
1745
1755
1425
CHILLED WATER COIL
Max Working Pressure (psig)
Face Area (sq ft) — Upper
Face Area (sq ft) — Lower
Rows...Fins/in.
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
8.3
—
9.0
—
9.9
—
8.3
5.5
8.3
8.3
11.0
8.3
12.4
12.4
15.5
12.4
3...15
20
STEAM COIL
Max Working Pressure
(psig at 260 F)
Total Face Area (sq ft)
Rows...Fins/in.
6.67
1...9
6.67
1...9
6.67
1...9
13.33
1...10
13.33
1...10
13.33
1...10
15.0
1...10
15.0
1...10
HOT WATER COIL
Max Working Pressure
(in. wg)
150
Total Face Area (sq ft)
Rows...Fins/in.
Water Volume
(gal)
6.67
2...8.5
6.67
6.67
2...8.5
13.33
2...8.5
13.33
13.33
2...8.5
15.0
2...12.5
15.0
2...12.5
2...8.5
2...8.5
8.3
1.1
13.9
1.85
14.3
1.90
3
(ft )
PIPING CONNECTIONS,
Quantity...Size (in.)
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
1
Chilled Water — In
1...1 / O D F 1...1 / ODF 2...1 / ODF 2...1 / ODM 2...1 / ODM 2...1 / ODM 2...2 / ODM 2...2 / ODM
8
8
8
8
8
8
8
8
Chilled Water — Out
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...1 / O D F 1...1 / ODF 2...1 / ODF 2...1 / ODM 2...1 / ODM 2...1 / ODM 2...2 / ODM 2...2 / ODM
8
8
8
8
8
8
8
8
1
1
1...2 /
1...2 /
2
2
2
2
2
2
1
1
1...1 /
1...1 /
1
1
1
1...1 /
1...1 /
1...1 /
1...2
1...2
2
2
1
1...1 /
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...16 x 20 x 2
Quantity...Size (in.)
4...20 x 24 x 2
4...20 x 25 x 2
4...16 x 24 x 2
4...16 x 24 x 2
Access Location
Either Side
5
Table 1D — 40RM Physical Data, SI — Cooling Units
UNIT 40RM
007
008
012
014
016
024
028
034
NOMINAL CAPACITY (kW)
21
26
35
43
52
70
87
105
OPERATING WEIGHT (kg)
Base Unit with TXV
Plenum
173
80
175
80
184
80
304
102
311
102
313
102
463
148
467
148
FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
208/230-1-60
1...381
1133
1...381
1604
1...381
1888
2...381
2360
2...381
2831
2...381
3775
2...457
4719
2...457
5663
850-1416 1203-2006 1416-2360 1770-2949 2124-3539 2831-4719 3539-5899 4247-7079
0.97
1.79
0.75
1.79
1.79
1.79
1.49
1.79
—
—
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
1.79
1.49
2.16
2.16
2.24
2.16
2.76
2.24
2.16
3.73
3.73
3.73
5.60
5.60
5.60
7.46
7.46
7.46
230-3-50, 400-3-50
Motor Speed (r/s)
208/230-1-60
28.8
28.8
28.8
23.8
28.8
28.8
28.8
23.8
—
—
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
230-3-50, 400-3-50
28.8
28.8
23.8
28.8
28.8
23.8
28.8
28.8
23.8
29.1
29.1
23.8
29.1
29.3
23.8
29.1
29.3
23.8
REFRIGERANT
Operating charge (kg)
(approx per circuit)*
R-22
1.13/1.13
1.36
1.36
0.68/0.68
0.90/0.90
1.59/1.59
2.04/2.04
2.27/2.27
DIRECT-EXPANSION COIL
Max Working Pressure (kPag)
Face Area (sq m)
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
2999
0.62
1
12/12
—
591
0.77
1
15/15
—
591
0.93
2
9/9
0.93
2
9/12
1.64
2
1.85
2
2.30
2
2.77
2
No. of Splits
No. of Circuits per Split (3 Row/4 Row)
Split Type...Percentage
Fins/m
12/16
13/18
15/20
18/24
Face...50/50
670
591
591
670
591
591
STEAM COIL
Max Working Pressure (kPag at 126 C)
Total Face Area (sq m)
Rows...Fins/m
138
0.62
1...355
0.62
1...355
0.62
1...355
1.24
1...394
1.24
1...394
1.24
1...394
1.39
1...394
1.39
1...394
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
1034
0.62
2...335
0.62
0.62
2...335
1.24
2...335
1.24
1.24
2...335
1.39
2...493
1.39
2...493
2...335
2...335
Water Volume
(L)
31.4
0.031
52.6
0.052
54.1
0.054
3
(m )
PIPING CONNECTIONS,
Quantity...Size (in.)
1
1
1
1
1
1
3
3
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
1...1 /
1...1 /
8
2...1 /
2...1 /
2...1 /
2...1 /
2...1 /
2...1 /
8
8
8
8
8
8
8
8
5
5
1... /
2... /
8
1
1
1...2 /
1...2 /
2
2
2
2
2
2
1
1
1
1
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...1 /
1...1 /
1
1...1 /
1...1 /
1...1 /
1...2
1...2
2
2
1
1...1 /
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
Either Side
Quantity...Size
4...508 x 610 x 51
4...508 x 635 x 51
4...406 x 610 x 51
Access Location
LEGEND
DX
—
Direct Expansion
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
6
Table 1E — 40RMQ Physical Data, SI — Heat Pump Units
UNIT 40RMQ
008
012
016
024
028
NOMINAL CAPACITY (kW)
26
35
52
70
87
OPERATING WEIGHT (kg)
Base Unit with TXV
Plenum
175
80
194
80
323
102
326
44
477
44
FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
208/230-1-60
1...381
1604
1...381
1888
2...381
2831
2...381
3775
2...457
4719
1203-2006
1416-2360
2124-3539
2831-4719
3539-5899
1.79
1.79
1.49
1.79
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
1.79
1.49
2.16
2.76
2.24
2.16
3.73
3.73
3.73
5.60
5.60
5.60
230-3-50, 400-3-50
Motor Speed (r/s)
208/230-1-60
28.8
28.8
28.8
23.8
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
28.8
28.8
23.8
28.8
28.8
23.8
29.1
29.1
23.8
29.1
29.3
23.8
230-3-50, 400-3-50
REFRIGERANT
Operating charge (kg)
(approx per circuit)*
R-22
1.36
0.91/0.91
1.36/1.36
1.59/1.59
2.04/2.04
DIRECT-EXPANSION COIL
Max Working Pressure (kPag)
Face Area (sq m)
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
2999
0.77
1
0.93
2
9
1.85
2
18
1.85
2
18
2.30
2
No. of Splits
No. of Circuits per Split
Split Type...Percentage
Rows...Fins/m
15
24/16
—
3...591
Face...50/50
4...591
Face...60/40
4...591
4...591
4...591
STEAM COIL
Max Working Pressure (kPag at 126 C)
Total Face Area (sq m)
Rows...Fins/m
138
1.24
1...394
0.62
1...355
0.62
1...355
1.24
1...394
1.39
1...394
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
1034
1.24
2...335
0.62
2...335
0.62
2...335
1.24
1.39
2...493
2...335
Water Volume
(L)
31.4
0.031
52.6
0.052
3
(m )
PIPING CONNECTIONS,
Quantity...Size (in.)
1
1
1
3
DX Coil — Vapor (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
1...1 /
2...1 /
2...1 /
2...1 /
8
8
8
8
5
5
5
1... /
2... /
2... /
8
8
8
1
1
1
1...2 /
1...2 /
1...2 /
2
2
2
2
2
2
2
2
2
2
1
1
1
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (Male PVC)
1...1 /
1...1 /
1...1 /
1
1
1...1 /
1...1 /
1...2
1...2
1
1
1...1 /
1...1 /
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
Quantity...Size
4...406 x 508 x 51 4...406 x 610 x 51 4...406 x 610 x 51
4...406 x 610 x 51 4...406 x 508 x 51 4...508 x 635 x 51
Right or Left Side
4...406 x 610 x 51
Either Side
Access Location
LEGEND
DX
—
Direct Expansion
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
7
Table 1F — 40RMS Physical Data, SI — Chilled Water Units
UNIT 40RMS
008
010
012
014
016
024
028
034
NOMINAL CAPACITY (kW)
26
29
35
43
52
70
87
105
OPERATING WEIGHT (kg)
Base Unit
Plenum
177
80
177
80
177
80
300
102
307
102
310
102
469
148
473
148
FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW
(Standard Motor)
208/230-1-60
1...381
1416
1...381
1605
1...381
1888
2...381
2360
2...381
2831
2...381
3775
2...457
4719
2...457
5663
1062-1770 1204-2006 1416-2360
1770-2949
2124-3539
2831-4719
3539-5899
4247-7079
1.79
1.79
1.49
1.79
1.79
1.79
1.49
1.79
—
—
—
—
—
—
208/230-3-60, 460-3-60
575-3-60
1.79
1.49
2.16
1.79
1.49
2.16
2.76
2.24
2.16
3.73
3.73
3.73
5.60
5.60
5.60
7.46
7.46
7.46
230-3-50, 400-3-50
Motor Speed (r/s)
208/230-1-60
28.8
28.8
28.8
23.8
28.8
28.8
28.8
23.8
—
—
—
—
—
—
208/230-3-60, 460-3-60
575-3-60
230-3-50, 400-3-50
28.8
28.8
23.8
28.8
28.8
23.8
28.8
28.8
23.8
29.1
29.1
23.8
29.1
29.3
23.8
29.1
29.3
23.8
CHILLED WATER COIL
Max Working Pressure (kPag)
Face Area (sq m) — Upper
Face Area (sq m) — Lower
Rows...Fins/m
Enhanced Copper Tubes, Aluminum Sine-Waves
2999
0.77
—
3...591
0.84
—
3...591
0.91
—
0.77
0.51
0.77
0.77
1.02
0.77
1.15
1.15
3...591
1.44
1.15
3...591
3...591
3...591
3...591
3...591
STEAM COIL
Max Working Pressure
(kPag at 126 C)
Total Face Area (sq m)
Rows...Fins/m
138
0.62
1...355
0.62
1...355
0.62
1...355
1.24
1...355
1.24
1...394
1.24
1...394
1.39
1...394
1.39
1...394
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
1034
0.62
2...335
0.62
0.62
2...335
1.24
2...335
1.24
1.24
2...335
1.39
2...493
1.39
2...493
2...335
2...335
Water Volume
(L)
31.4
0.031
52.6
0.052
54.1
0.054
3
(m )
PIPING CONNECTIONS,
Quantity...Size (in.)
3
3
3
1...1 /
ODF
1...1 /
ODF
2...1 /
ODF
8
8
8
3
3
3
1
1
Chilled Water — In
2...1 / ODM 2...1 / ODM 2...1 / ODM 2...2 / ODM 2...2 / ODM
8
8
8
8
8
3
3
3
1...1 /
1...1 /
2...1 /
8
8
8
3
3
3
1
1
Chilled Water — Out
2...1 / ODM 2...1 / ODM 2...1 / ODM 2...2 / ODM 2...2 / ODM
8
8
8
8
8
ODF
ODF
ODF
1
1
1
1
1
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...2 /
1...2 /
2
2
2
2
2
2
1
1...1 /
1...1 /
1
1...1 /
1...1 /
1...1 /
1...2
1...2
2
2
1
1...1 /
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
Either Side
Quantity...Size (mm)
4...508 x 610 x 51
4...508 x 635 x 51
4...406 x 610 x 51
Access Location
8
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMS units may require alternate or addi-
tional field-fabricated piping access holes.
UNIT WEIGHT
UNIT
lb (kg)
40RM007
40RM008
40RM012
40RMQ008
40RMQ012
40RMS008
40RMS010
40RMS012
381 (173)
385 (175)
405 (184)
385 (175)
427 (194)
390 (177)
391 (177)
391 (177)
Fig. 1A — Dimensions — Sizes 007-012
9
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory-supplied and
field-installed.
6. 40RMQ016,024 and 40RMS units may
require alternate or additional field-
fabricated piping access holes.
UNIT WEIGHT
UNIT
lb (kg)
40RM014
40RM016
40RM024
40RMQ016
40RMQ024
40RMS014
40RMS016
40RMS024
670 (304)
685 (311)
690 (313)
713 (323)
720 (326)
661 (300)
677 (307)
683 (310)
Fig. 1B — Dimensions — Sizes 014-024
10
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory-supplied and
field-installed.
6. 40RMQ028 and 40RMS may require
alternate or additional field fabricated pip-
ing access holes.
UNIT WEIGHT
UNIT
lb (kg)
40RM028
40RM034
40RMQ028
40RMS028
40RMS034
1020 (463)
1030 (467)
1050 (477)
1035 (469)
1042 (473)
Fig. 1C — Dimensions — Sizes 028,034
11
40RM
–
016 – –
B
5
0
1
GC
Factory-Installed Options
GC – Unpainted, Standard Motor,
and Standard Drive
40RM – Commercial Packaged
Air Handler
HC – Unpainted, Standard Motor,
and Medium-Static Drive
(Not available for 60 Hz 028 size
or 50 Hz 016-028 sizes)
TC – Unpainted, Alternate Motor,
and Medium-Static Drive
(60 Hz 028 size and
Cooling Coil
– – Direct Expansion
Q – Direct Expansion for Heat Pump Duty
S – Chilled Water
Nominal Capacity – Tons (kW)
50 Hz 016-028 sizes)
007 – 6 (21)
016 – 15 (52)
024 – 20 (70)
028 – 25 (87)
034 – 30 (105)
YC – Unpainted, Alternate Motor, and
008 – 7-1/2 (26)
010 – 8-1/2 (29)
012 – 10 (35)
High-Static Drive*
ED – Painted, Standard Motor, and
Standard Drive
014 – 12-1/2 (43)
FD – Painted, Standard Motor, and
Not Used
Medium-Static Drive
(Not available for 60 Hz 028 size
or 50 Hz 016-028 sizes)
RD – Painted, Alternate Motor, and
Expansion Device
–
– None (40RMS)
Medium-Static Drive
(60 Hz 028 size and
50 Hz 016-028 sizes)
B – Thermostatic Expansion Valves (40RM, 40RMQ)
H – TXV with High Capacity, 4 Row Coil
WD – Painted, Alternate Motor,
and High-Static Drive*
Voltage Designation (V-Ph-Hz)
1 – 575-3-60
8 – 230-3-50
9 – 400-3-50
3 – 208/230-1-60
Packaging
1 – Standard Domestic
3 – Standard Export
(007-010 sizes only)
5 – 208/230-3-60
6 – 208/230/460-3-60 (all sizes 007-014;
size 016 except YC and WD options)
460-3-60 (sizes 016 with YC or WD options
and all size 024-034 units)
Revision Number
0 – Original
LEGEND
TXV — Thermostat Expansion Valve
*YC and WD option codes for all 034 size units and 008, 010 size units with 208/230-1-60
power designate standard motor and high-static drive.
NOTE: See the following table for the sizes available for each unit.
UNIT
40RM
007
X
008
X
010
012
X
014
X
016
X
024
X
028
X
034
X
40RMQ
40RMS
X
X
X
X
X
X
X
X
X
X
X
X
X
Fig. 2 — Model Number Nomenclature
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 3 — Foam Block Location
12
Unit Positioning — The unit can be mounted on the
floor for vertical application with return air entering the face of
the unit and supply air discharging vertically through the top of
the unit. The unit can also be applied in a horizontal arrange-
ment with return air entering horizontally and the supply air
discharging horizontally. When applying the unit in a horizon-
tal arrangement, ensure the condensate drain pan is located at
the bottom center of the unit for adequate condensate disposal.
See Fig. 4 for condensate connections for each unit position.
Typical positioning and alternate return air locations are
shown in Fig. 4. Alternate return air locations can be used by
moving the unit panel from the alternate return air location to
the standard return air location. Refer to overhead suspension
accessory drawing (Fig. 5) for preferred suspension technique.
The unit needs support underneath to prevent sagging.
LEGEND
Accessory Line
Alternate Air Intake and Discharge
Air Intake and Discharge
Fig. 4 — Typical Unit Positioning
IMPORTANT: Do NOT attempt to install unit with return
air entering top panel of unit. Condensate will not drain
from unit.
The 40RM Series evaporator coils have a face-split design.
Ensure that lower circuit of coil is first on/last off when
connected to the condensing unit and/or system controls. See
Fig. 8.
External TXV equalizer connections are provided and
factory-brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction line
at least 45 degrees above bottom, at approximately the
4 o’clock or 8 o’clock position. See Fig. 9.
Unit Isolation — Where extremely quiet operation is
essential, install isolators between floor and base of unit, or
between ceiling and top section of unit.
Be sure that unit is level and adequately supported. Use
channels at front and sides of unit for reference points when
leveling.
NOTE: The 40RMQ units are supplied with factory-installed
thermostatic expansion valves and check valve bypasses. No
extra piping connections or kits are required to install the
40RMQ with a 38AQ, 38ARQ, or 38AQS condensing unit in a
heat pump system, however, some field-supplied components
may be required. See the following two sections.
HEAT PUMP SYSTEM PIPING — Addition of a liquid so-
lenoid valve (LLSV) is recommended. The LLSV must be a
bi-flow type suited for use in heat pump systems. Refer to the
38AQ, ARQ, AQS literature for recommended component
part numbers. Wire the solenoid valve in parallel with the com-
pressor contactor coil.
The LLSV must be installed at the outdoor unit with the
flow arrow pointed toward the outdoor unit (in-flow direction
for the heating mode.)
38ARQ DUPLEX/40RMQ024 HEAT PUMP SYSTEM
PIPING — Two 38ARQ012 heat pump condensing units may
be connected in a duplex arrangement with the 40RMQ024.
See Fig. 10. Ensure that the lower circuit of the 40RMQ coil is
the first on/last off by connecting to the “A” condensing unit
and by configuring the controls so that the “A” condensing unit
is the first on/last off.
38ARQ012/38AQS016 DUPLEX/40RMQ028 HEAT PUMP
SYSTEM PIPING — One 38ARQ012 and one 38AQS016
heat pump condensing unit may be connected in a duplex
arrangement with the 40RMQ028. See Fig. 10. The
40RMQ028 has a 60/40 face split coil. Ensure that the larger
coil section (connection “B”, Fig. 8) is connected to the
38QAS016 and the smaller coil section is connected to the
38AQS012. In addition, ensure that the lower circuit of the
40RMQ coil is the first on/last off by connecting to the “A”
condensing unit and by configuring (see 38ARQ,AQS installa-
tion instructions for more information) the controls so that the
“A” condensing unit is the first on/last off.
FILTER DRIER REQUIREMENTS FOR HEAT PUMP
SYSTEMS — The 38ARQ and 38AQS units do not include
filter driers. Filter driers must be field-supplied and field-
installed. The filter driers used with these systems must be
bi-flow types suited for use in heat pump applications. Refer to
the 38AQ,ARQ,AQS literature for recommended component
part numbers. See Fig. 11 for filter drier quantity and location
information.
Refrigerant and Chilled Water Piping
Access — The 40RM Series units come with standard
knockouts for refrigerant and chilled water piping. These
knockouts are located on both sides of the unit for installation
flexibility. The standard knockouts provide sufficient access to
the unit’s coils for all 40RM and some 40RMQ units, however,
for 40RMQ016,028 and 40RMS units, additional holes must
be field-fabricated to accommodate the piping. See Fig. 6 for
the positions and dimensions of the additional access holes re-
quired for these units, including hole diameters and drilling
dimensions. Recommended access hole use is also listed for all
units. Note that Fig. 6 shows the access holes on the control-
box side of the unit; this is the side of the unit with the coil
headers, so it is used most often for piping access.
IMPORTANT: Do not bury refrigerant piping
underground.
Refrigerant Piping — See Tables 1A, 1B, 1D, 1E for
refrigerant pipe connection sizes. For ease in brazing, it is rec-
ommended that all internal solder joints be made before unit is
placed in final position.
The 40RM and 40RMQ direct-expansion units have inter-
nal factory-installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R-22. See Table 2 for part
numbers. Knockouts are provided in the unit corner posts for
40RM and 40RMQ008 and 012 refrigerant piping. The
40RMQ016,024 and 028 units requires additional field-
fabricated piping access holes. See Fig. 6, which also lists rec-
ommended knockouts and access holes to use for each 40RM
and 40RMQ unit size. Recommended fittings are listed in
Table 3.
The sensor bulb capillary tubes must be routed from the
TXVs inside the unit through one of the piping access holes.
Clamp the TXV sensor bulb on a vertical portion of the suction
line, outside the unit. See Fig. 7.
NOTE: Be sure to remove the styrofoam shipping pad from
the TXV. Verify that it has been removed. See Fig. 3.
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped portion
of the suction line.
13
OVERHEAD SUSPENSION ACCESSORY
UNIT SIZES 007-012
UNIT SIZES 014-024
UNIT SIZES 028,034
NOTE: Dimensions in [ ] are millimeters.
Fig. 5 — Preferred Suspension Technique
14
FIELD-FABRICATED HOLE DIAMETERS,
in. (mm)
FIELD-FABRICATED HOLE POSITION
DIMENSIONS, in. (mm)
USE HOLE
NUMBERS
UNIT
No. 5
No. 6
No. 7
No. 8
A
B
C
D
40RM007,008
40RMQ008
1, 3
—
—
—
—
—
—
—
—
40RM012-034
40RMQ012
40RMS008-012
40RMS014-024
40RMQ016,024,028
40RMS028,034
1, 2, 3, 4
—
—
—
—
—
—
—
—
—
—
—
—
3
4, 5
1 / (44.5)
4
—
—
—
6.25 (158.8)
3.0 (76.2)
3.25 (82.6)
—
3
3
3
4, 5, 6, 7
3*, 5, 6, 7
5, 6, 7, 8
1 / (44.5) 1 / (44.5) 1 / (44.5)
6.0 (152.4) 10.5 (266.7)
6.125 (155.6) 10.38 (263.7)
9.625 (244.5) 13.38 (339.9)
—
—
4
4
4
1
1
3
1 / (28.6) 1 / (28.6) 1 / (44.5)
8
8
4
1
1
1
1
2 / (63.5) 2 / (63.5) 2 / (63.5) 2 / (63.5) 6.0 (152.4)
17.0 (431.8)
2
2
2
2
1
3
*Must be enlarged from 1 / in. to 1 / inches.
8
4
NOTE: Access hole knockouts 1-4 are factory-supplied.
Fig. 6 — Refrigerant and Chilled Water Piping Access Holes
FIRST ON/LAST OFF = B
VERTICAL INSTALLATION
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: Component location arrangement shown for field installation of
sight glasses, solenoid valves, filter driers, and TXV sensing bulbs. The
TXVs and equalizer lines are factory installed.
FIRST ON/LAST OFF = A
HORIZONTAL INSTALLATION
Fig. 7 — Face-Split Coil Suction and
Liquid Line Piping (Typical)
Fig. 8 — Typical Evaporator Coil Connections
(40RM, 40RMQ)
15
UNIT
QUANTITY REQUIRED
FIGURE REFERENCE
38ARQ008,012
38AQS016
38ARQ012 (2)
38ARQ012,
AQS016
1
2
2
B
A
A
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: The 8 o’clock position is shown above.
2
A
Fig. 9 — TXV Sensing Bulb Location
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 11 — Filter Drier Quantity and Location
DISCONNECT
PER NEC
ELECTRIC
HEATER
ACCESSORY
24 V
CONTROL
WIRE
FUSED
DISCONNECT
SWITCH*
CONDENSING
UNIT B
BULB CAPILLARY
TUBES
40RMQ024
UNIT
RETURN
AIR
8 DIAMS
MIN
SIGHT
GLASS*
FILTER
DRIER*
SUBBASE
ACCESSORY
INSULATED
VAPOR LINE
15 DIAMS
MIN
10 DIAMS
MIN
LIQUID
LINE
FUSED
DISCONNECT
SWITCH*
CONDENSATE
DRAIN
CONDENSING
UNIT A
LEGEND
INSULATED
VAPOR LINE
NEC — National Electrical Code
TXV — Thermostatic Expansion Valve
Piping
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to
Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only
and are not intended for, or to include all details for, a specific installation.
4. Filter driers must be bi-flow type suited for heat pump duty.
5. Condensing unit A should be the first on and last off and be connected to
the lower half of the coil.
LIQUID
LINE
6. Internal factory-supplied TXVs not shown.
Fig. 10 — Typical Installation — 40RMQ024,028
16
Table 2 — Factory-Installed Nozzle and Distributor Data
FEEDER TUBES
PER DISTRIBUTOR*
Qty...Size (in.)
1
COIL
TYPE
TXV
DISTRIBUTOR
Qty...Part No.
NOZZLE
UNIT
Qty...Part No.
Qty...Part No.
40RM007
40RM008
40RMQ008
40RM012
40RMQ012
3, 4 Row
3, 4 Row
—
1...TDEBX8
1...TDEBX8
1...TDEBX8
2...TDEX6
2...TDEX4
1...1116
1...1126
1...1657
2...1115
2...1655
12... /
1...E5
1...C6
1...C6
2...E4
2...E4
4
4
4
4
4
1
15... /
1
15... /
1
3, 4 Row
—
9... /
1
9... /
1
3 Row
4 Row
2...TDEBX8
2...TDEBX8
9... /
4
4
40RM014
2...1115
2...E5
1
6... /
1
3 Row
4 Row
2...TDEBX8
2...TDEBX8
2...1116
2...1126
12... /
2...E6
2...C6
4
4
40RM016
40RMQ016
40RM024
40RMQ024
40RM028
40RMQ028
40RM034
1
16... /
1
—
2...TDEBX8
2...1657
16... /
2...C6
4
1
3 Row
4 Row
2...TDEBX11
2...TDEBX11
2...1116
2...1126
13... /
2...E8
2...C8
4
16
3
18... /
3
—
2...TDEBX11
2...1655
18... /
2...E8
16
1
3 Row
4 Row
2...TDEBX11
2...TDEBX11
2...1126
2...1126
15... /
2...C10
2...C15
4
16
3
20... /
3
—
2...TDEBX11
2...1655
20... /
2...E15
16
1
3 Row
4 Row
2...TDEBX16
2...TDEBX16
2...1126
2...1126
18... /
2...C12
2...C17
4
16
3
24... /
1
*Feeder tube size is / in. (6.35 mm).
4
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.
Table 3 — Fitting Requirements
ACCESS
HOLE NO.*
CONNECTION
FITTINGS REQUIRED†
(in.)
UNIT
CIRCUIT
TYPE
1
1
1 / Street Elbow
8
5
1
3
1
3
Suction
—
—
—
—
1 / Nipple, 10 / L
8
8
1
1 / Long Radius Elbow
40RM
007
8
5
5
5
/ Street Elbow
8
5
Liquid
Suction
Liquid
/ Nipple, 8 / L
8
8
8
/ Long Radius Elbow
1
1
1
1 / Street Elbow
8
8
8
5
1 / Nipple, 8 / L
8
40RM
40RMQ
008
1 / Long Radius Elbow
5
5
5
/ Street Elbow
8
8
5
/ Nipple, 8 / L
8
/ Long Radius Elbow
8
3
3
3
3
1 / Nipple, 4 /
8
8
8
L
8
8
1 / Long Radius Elbow
4
Return
—
3
1 / Nipple, 7 /
8
L
40RMS
008-012
3
1 / Long Radius Elbow
3
3
5
1 / Nipple, 6 /
8
L
8
8
5
1
Supply
Suction
—
1 / Long Radius Elbow
1
Lower
(2) 1 / Street Elbow
8
5
5
5
/ Street Elbow
8
1
2
3
Liquid
Liquid
Lower
Upper
/ Nipple, 8 / L
8
2
/ Long Radius Elbow
8
5
5
5
/ Street Elbow
8
40RM
012
1
/ Nipple, 13 /
L
8
2
/ Long Radius Elbow
8
1
1
1
3
1 / Nipple, 5 /
8
8
8
L
8
4
1 / Long Radius Elbow
4
Suction
Upper
1 / Nipple, 12 L
1
1 / Long Radius Elbow
1
1
2
Suction
Liquid
Lower
Lower
(2) 1 / Street Elbow
8
5
5
5
/ Street Elbow
8
8
8
1
/ Nipple, 5 / L
2
/ Long Radius Elbow
5
5
5
/ Street Elbow
8
40RMQ
012
1
3
4
Liquid
Upper
Upper
/ Nipple, 10 /
L
8
8
2
/ Long Radius Elbow
1
1
1
1
5
1 / Nipple, 5 /
L
8
8
8
8
8
1 / Long Radius Elbow
Suction
1 / Nipple, 12 L
1 / Long Radius Elbow
*See Fig. 6 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
17
Table 3 — Fitting Requirements (cont)
ACCESS
HOLE NO.*
CONNECTION
CIRCUIT
FITTINGS REQUIRED†
(in.)
UNIT
TYPE
1
1
1 / Street Elbow
8
5
1
2
3
Suction
Liquid
Liquid
Lower
Lower
Upper
1 / Nipple, 7 /
L
8
8
1
1 / Long Radius Elbow
8
5
5
5
/ Street Elbow
8
7
/ Nipple, 1 /
L
8
8
16
/ Long Radius Elbow
40RM
014
5
5
5
/ Street Elbow
8
8
1
/ Nipple, 11 /
L
2
/ Long Radius Elbow
8
1
1
1
5
1 / Nipple, 5 /
8
8
8
L
8
8
1 / Long Radius Elbow
4
Suction
Upper
1 / Nipple, 13 L
1
1 / Long Radius Elbow
3
3
1 / Long Radius Elbow
8
3
4
5
6
7
1
2
3
Supply
Return
Return
Supply
Suction
Liquid
Lower
Lower
Upper
Upper
Lower
Lower
Upper
1 / Nipple, 3 /
L
8
4
3
1 / Long Radius Elbow
8
3
3
1 / Long Radius Elbow
8
3
1 / Nipple, 3 /
L
8
8
3
1 / Long Radius Elbow
40RMS
8
3
3
014-024
1 / Long Radius Elbow
8
8
8
1 / Nipple, 7 L
3
1 / Long Radius Elbow
3
3
1 / Long Radius Elbow
8
8
3
1 / Nipple, 11 /
L
4
3
1 / Long Radius Elbow
8
1
1 / Street Elbow
8
8
1
3
1 / Nipple, 2 /
L
4
1
1 / Long Radius Elbow
8
5
5
5
/ Street Elbow
8
3
/ Nipple, 1 / L
8
8
/ Long Radius Elbow
8
40RM
016
5
5
5
/ Street Elbow
8
1
Liquid
/ Nipple, 11 /
L
8
2
/ Long Radius Elbow
8
1
1
1
5
1 / Nipple, 5 /
8
8
8
L
8
8
1 / Long Radius Elbow
4
3
5
Suction
Suction
Suction
Upper
Lower
Lower
1 / Nipple, 13 L
1
1 / Long Radius Elbow
1
1
1 / Nipple, 3 L
8
8
1 / Long Radius Elbow
5
5
5
5
7
/ Nipple, 2 / L
8
8
/ 45° Elbow
8
5
/ Nipple, 1 / L
8
8
/ Long Radius Elbow
8
5
5
5
5
7
40RMQ016,
024,028
/ Nipple, 2 / L
8
8
8
/ 45° Elbow
6
7
Liquid
Upper
Upper
1
/ Nipple, 4 / L
8
4
/ Long Radius Elbow
8
1
1
1
1
1 / Nipple, 5 L
8
8
8
8
1 / 45° Elbow
Suction
3
1 / Nipple, 8 /
L
4
1 / Long Radius Elbow
1
1
1 / Street Elbow
8
5
1
2
3
Suction
Liquid
Liquid
Lower
Lower
Upper
1 / Nipple, 7 /
L
8
8
1
1 / Long Radius Elbow
8
5
5
5
/ Street Elbow
8
1
/ Nipple, 6 /
L
8
8
2
/ Long Radius Elbow
40RM
024
5
5
5
/ Street Elbow
8
8
1
/ Nipple, 9 /
L
2
/ Long Radius Elbow
8
1
1
1
5
1 / Nipple, 5 /
8
8
8
L
8
8
1 / Long Radius Elbow
4
Suction
Upper
1 / Nipple, 11 L
1
1 / Long Radius Elbow
3
3
1 / Street Elbow
8
8
8
1
2
3
Suction
Liquid
Liquid
Lower
Lower
Upper
1 / Nipple, 11 L
3
1 / Long Radius Elbow
5
5
5
/ Street Elbow
8
1
/ Nipple, 1 /
L
8
8
2
/ Long Radius Elbow
40RM
028
5
5
5
/ Street Elbow
8
8
3
/ Nipple, 19 /
L
4
/ Long Radius Elbow
8
3
3
3
3
1 / Nipple, 4 /
L
8
16
1 / Long Radius Elbow
8
8
4
Suction
Upper
1
1 / Nipple, 23 /
L
4
3
1 / Long Radius Elbow
8
*See Fig. 6 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
18
Table 3 — Fitting Requirements (cont)
ACCESS
HOLE NO.*
CONNECTION
CIRCUIT
FITTINGS REQUIRED†
(in.)
UNIT
TYPE
1
1
2 / Long Radius Elbow
8
1
5
6
7
8
1
2
3
Supply
Return
Return
Supply
Suction
Liquid
Lower
Lower
Upper
Upper
Lower
Lower
Upper
2 / Nipple, 3 /
L
8
2
1
2 / Long Radius Elbow
8
1
1
2 / Long Radius Elbow
8
8
8
2 / Nipple, 3 L
1
2 / Long Radius Elbow
40RMS
1
1
028, 034
2 / Long Radius Elbow
8
8
7
2 / Nipple, 6 /
L
8
1
2 / Long Radius Elbow
8
1
1
2 / Long Radius Elbow
8
8
7
2 / Nipple, 11 / L
8
1
2 / Long Radius Elbow
8
3
1 / Street Elbow
8
8
8
3
1 / Nipple, 3 L
3
1 / Long Radius Elbow
5
/ Street Elbow
8
5
5
3
/ Nipple, 7 / L
8
4
/ Long Radius Elbow
8
40RM
034
5
5
5
/ Street Elbow
8
1
Liquid
/ Nipple, 18 /
L
8
2
/ Long Radius Elbow
8
3
3
3
3
1 / Nipple, 4 /
L
8
16
1 / Long Radius Elbow
8
8
4
Suction
Upper
1
1 / Nipple, 19 /
L
4
3
1 / Long Radius Elbow
8
*See Fig. 6 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
To size, design, and install chilled water piping, consult the
Carrier System Design manual. See Fig. 12 for an example of a
typical installation. Recommended fittings are listed in Table 3.
To access 40RMS coil vents and drains, remove the unit
side panel over the coil header. Vent and drain plugs are on the
top and bottom of header, respectively. See the Service section
for information on preventing coil freeze-up during winter.
Chilled Water Piping — See Tables 1C and 1F for
chilled water connection sizes. For ease in brazing, it is recom-
mended that all internal solder joints be made before unit is
placed in final position.
Knockouts are provided in the unit corner posts for 40RM
and 40RMQ refrigerant piping; additional field-fabricated ac-
cess holes are required for 40RMS chilled water piping. See
Fig. 6, which lists recommended knockouts and access holes to
use for each 40RMS unit size.
Fig. 12 — Typical 40RMS Chilled Water Piping
19
See Fig. 14. Loosen the 2 screws next to the drain outlet at both
ends of the unit, push drain pan down in the slots near the drain
connection, and up in the slots on the opposite end. Retighten
screws. The pan should have a pitch of at least 1/4-in. over its
length toward the drain connection.
Condensate Drain — Install a trapped condensate drain
line to unit connection as shown in Fig. 13. The unit drain con-
nection is a PVC stub. See Fig. 14. Some areas may require an
adapter to connect to either galvanized steel or copper pipe.
For these applications, install a field-supplied threaded PVC
adapter.
NOTE: A trap must be installed in the condensate drain line to
ensure that the static pressure of fans is balanced with the
water column in the drain line and that condensate can drain
completely from pan. Without a trap, air can be drawn up drain
line until water level in condensate pan becomes equal to static
pressure created by fans, preventing complete drainage. Condi-
tions will worsen as filters become dirty.
Install clean-out plugs in trap. Pitch drain line downward to
an open floor drain or sump. Provide service clearance around
drain line to permit removal of unit panels. Observe all local
sanitary codes.
As shipped, the unit’s condensate drain pan is NOT sloped
towards the drain connection. The pan slope must be changed
to pitch towards the side of the unit with the drain connection.
Fan Motors and Drives — Motor and drive packages
are factory installed in all units. The standard motor and drive
packages consist of the following items:
1 — fan motor
1 — adjustable motor pulley
1 — fan pulley
1 — fan
belt
(40RM007-012,
40RMQ008-012,
40RMS008-012 units)
2 — matched fan belts (40RM014-034, 40RMS014-034,
40RMQ014-028 units)
For instructions on changing fan rotation, changing drive
speeds and adjusting drives, see Pulley and Drive Adjustment
in the Service section.
Fig. 14 — Drain Pan Slope Adjustment
OTE: Dimensions in [ ] are in millimeters.
Fig. 13 — Condensate Drains
20
460-v, 3-ph, 60 Hz operation can be field-converted to
208/230-v, 3-ph, 60 Hz operation. Rewire the motor according
to the diagram plate on the motor. After reconfiguring the mo-
tor, mark the motor specifying 208-v or 230-v operation replac-
ing the 460-v sticker information on the units’ corner post.
Power Supply and Wiring — Check the unit data
plate to ensure that available power supply matches electrical
characteristics of the unit. Provide a disconnect switch of size
required to provide adequate fan motor starting current. See
Tables 4-6 for unit electrical data.
Fan motors are factory-installed on all units. Indoor-fan
contactors are located in the fan contactor box behind the side
access panel (see Fig. 15 and 16). Wire the thermostat to the
24-v control circuit terminal block located in the side of the fan
contactor control box, according to Fig. 17 or the unit label
diagram. If the air handler is part of a split system, complete the
wiring from the condensing unit to the thermostat shown in
Fig. 17.
Install disconnect switch and power wiring in accordance
with all applicable local codes. See Fig. 15-17 and the unit
label diagram. For units with motor sizes less than 5 Hp
(3.7 kW), connect power wiring to unit with no. 10 ring termi-
nal. For units with motor sizes of 5 Hp (3.7 kW) or more, con-
nect power wiring with 1/4-in. ring terminal.
The 40RM, 40RMQ and 40RMS size 007-016 units (except
40RM016 with YC or WD option) that have motors wired for
FAN SCROLL
FAN
CONTACTOR
BOX
MOTOR
AND DRIVE
WIRE
ACCESS
FAN DRIVE
PULLEY
CONDENSATE
DRAIN
CONNECTION
(HORIZONTAL)
W
COIL
FILTER
ELEMENTS
TXV BULB
ACCESS
FAN
CONTACTOR
REFRIGERANT/
CHILLED WATER
PIPING ACCESS
24V
TERMINAL
BLOCK
FILTER
RETAINER
CLIP
CONDENSATE
DRAIN
CONNNECTION
(VERTICAL)
POWER
WIRING
KNOCKOUT
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 16 — Fan Contactor Box and Terminal Block
(Cover Removed) (Typical)
Fig. 15 — Wiring and Service Access
(Side Panel Removed)
21
Table 4 — Electrical Data, Standard Motors
FAN MOTOR
VOLTAGE
POWER SUPPLY
UNIT
V*-PH-Hz
Minimum
Circuit Amps
9.5
LIMITS
Hp (kW)
FLA
MOCP
208/230-1-60
208/230-3-60
460-3-60
187-253
187-253
414-506
518-632
207-253
360-440
187-253
187-253
414-506
518-632
207-253
360-440
187-253
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
1.3 (0.97)
2.4 (1.79)
2.4 (1.79)
1.0 (0.75)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.9 (2.16)
2.9 (2.16)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
2.9 (2.16)
2.9 (2.16)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
2.9 (2.16)
2.9 (2.16)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
7.6
5.8
15
15
15
15
15
15
20
15
15
15
15
15
20
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
20
15
15
15
15
30/25
15
15
30
15
45/40
20
15
50
25
60/60
30
20
70
30
7.3
2.6
3.3
40RM
007
575-3-60
1.4
1.7
230-3-50
5.2
6.5
400-3-50
2.6
3.3
208/230-1-60
208/230-3-60
460-3-60
11.0
5.8
13.8
7.3
40RM
40RMQ
40RMS
008
2.6
3.3
575-3-60
2.4
8.0
230-3-50
5.2
6.5
400-3-50
2.6
3.3
208/230-1-60
208/230-3-60
460-3-60
11.0
5.2
13.8
6.5
2.6
3.3
40RMS
010
575-3-60
2.3
2.9
230-3-50
5.2
6.5
400-3-50
2.6
3.3
208/230-3-60
460-3-60
5.8
7.5
40RM
40RMQ
40RMS
012
2.6
3.3
575-3-60
2.4
3.0
230-3-50
7.5
9.4
400-3-50
3.4
4.3
208/230-3-60
460-3-60
7.5
9.4
3.4
4.3
40RM
40RMS
014
575-3-60
3.8
4.8
230-3-50
7.5
9.4
400-3-50
3.4
4.3
208/230-3-60
460-3-60
10.6
4.8
13.3
6.0
40RM
40RMQ
40RMS
016
575-3-60
3.8
4.8
230-3-50
7.5
9.4
400-3-50
3.4
4.3
208/230-3-60
460-3-60
14.6/12.8
6.4
18.3/16.0
8.0
40RM
40RMQ
40RMS
024
575-3-60
5.1
6.4
230-3-50
15.2
7.6
19.0
9.5
400-3-50
208/230-3-60
460-3-60
21.4/19.4
9.7
26.9/24.3
12.1
9.8
40RM
40RMQ
40RMS
028
575-3-60
7.8
230-3-50
22.8
11.4
28.2/26.8
13.4
10.3
32.2
16.1
28.5
14.3
35.3/33.5
16.8
12.9
40.3
20.1
400-3-50
208/230-3-60
460-3-60
40RM
40RMS
034
575-3-60
230-3-50
400-3-50
See Legend and Notes on page 23.
22
Table 5 — Electrical Data, Alternate Motors
FAN MOTOR
VOLTAGE
POWER SUPPLY
UNIT
V*-PH-Hz
Minimum
LIMITS
Hp (kW)
FLA
MOCP
Circuit Amps
13.8/13.8
9.4
208/230-1-60
208/230-3-60
460-3-60
575-3-60
230-3-50
187-253
187-253
414-506
518-632
207-253
360-440
187-253
187-253
414-506
518-632
207-253
360-440
187-253
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
2.0 (1.49)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
2.9 (2.16)
2.9 (2.16)
2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
2.9 (2.16)
2.9 (2.16)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
5.0 (3.73)
5.0 (3.73)
3.7 (2.76)
3.7 (2.76)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
11.0/11.0
7.5
20
15
15
15
15
15
15
15
15
15
15
15
20
15
15
15
15
15
20
15
15
30
15
20
15
3.4
2.4
5.2
2.6
11.0
7.5/7.5
3.4
3.8
7.5
3.4
11.0
7.5
3.4
3.8
7.5
3.4
10.5/10.5
4.8
3.8
15.2
7.6
10.2
4.8
5.1
15.2
7.6
14.6/12.8
6.4
5.1
15.2
7.6
4.3
3.0
6.5
3.3
13.8
9.4/9.4
4.3
4.8
9.4
4.3
13.8
9.4
4.3
4.8
9.4
4.3
13.3/13.3
6.0
40RM
007
400-3-50
208/230-1-60
208/230-3-60
460-3-60
575-3-60
230-3-50
40RM
40RMQ
40RMS
008
400-3-50
208/230-1-60
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
40RMS
010
40RM
40RMQ
40RMS
012
4.8
19.0
9.5
12.7
6.0
6.4
40RM
40RMS
014
15
30
15
19.0
9.5
18.3/16.0
8.0
30/25
15
40RM
40RMQ
40RMS
016
6.4
19.0
9.5
15
30
15
21.5/19.4
9.7
26.9/24.3
12.1
9.8
45/40
20
40RM
40RMQ
40RMS
024
7.8
15
50
25
22.8
11.4
28.2/26.8
13.4
10.3
32.2
16.1
28.5
14.3
35.3/33.5
16.8
12.9
40.3
20.1
60/60
30
40RM
40RMQ
40RMS
028
20
60
30
400-3-50
Legend and Notes For Tables 4 and 5
LEGEND
Full Load Amps
Maximum Overcurrent Protection
Determine maximum deviation from average voltage.
FLA
—
—
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
MOCP
*Motors are designed for satisfactory operation within 10% of nominal volt-
ages shown. Voltages should not exceed the limits shown in the Voltage Lim-
its column.
Maximum deviation is 6 v.
Determine percent voltage imbalance.
NOTES:
6
% Voltage Imbalance = 100 x
397
1. Minimum circuit amps (MCA) and MOCP values are calculated in accor-
dance with NEC (National Electrical Code), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters’
Laboratories) Standard 1995.
= 1.5%
3. Unbalanced 3-Phase Supply Voltage
This amount of phase imbalance is satisfactory because it is below the maxi-
mum allowable 2%.
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percentage of
voltage imbalance.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
393 + 403 + 396
Average Voltage =
3
1192
=
3
=
397
23
LEGEND
EQUIP — Equipment
GND
HC
HTR
IFC
IFM
TB
— Ground
— Heating Contactor
— Electric Heater
— Indoor-Fan Contactor
— Indoor-Fan Motor
— Terminal Block
T’STAT — Thermostat
Factory Wiring
Field Control Wiring
NOTE: Use copper conductors only.
Fig. 17 — Unit Wiring
Table 6 — Fan Contactor Coil Data
Return-Air Filters — Type and size of filters are shown
in Tables 1A-1F and are factory-supplied and factory-installed.
In all units with 2 fans, a filter replacement tool (hook) is
shipped inside the unit for field use when replacing filters.
See the Service section for instructions on filter element
replacement.
UNIT
40RM, 40RMQ
40RMS
MAXIMUM
HOLDING
VA
VOLTAGE
(vac)
007-034
24
10
Connecting Ductwork — Refer to the Carrier System
Design Manual for the recommended design and layout of
ductwork. Figure 18 shows recommended duct connection to
units with 2 fans.
Do not operate unit without ductwork or discharge plenum
unless fan speed has been adjusted for external static pres-
sure of zero in. wg. Failure to do so may result in motor
overload.
DISCHARGE CONNECTIONS — Duct
flanges
are
factory-supplied; they are shipped inside the unit attached to
the hairpin end of the coil tube sheet for field installation. Us-
ing the existing screws, install the duct flanges on the unit’s fan
deck. Each fan discharge requires 2 flanges; each flange must
be bent in the middle to conform to the discharge opening. See
Fig. 19. After flanges are installed, connect them to the supply
duct using a canvas connection to prevent vibration. It is im-
portant that this connection be properly fabricated to prevent
high air friction losses and air noise.
RETURN CONNECTION — When using return-air duct-
work, route return-air duct to the unit’s return air inlet near the
filter rack, using a canvas connection to prevent transmission
of unit vibration. If the duct blocks off the unit’s access panel,
provide a slip joint in the ductwork to permit removal for
servicing.
OUTDOOR-AIR INLET CONNECTION — Connect outdoor-
air inlet to field-installed accessory economizer. Refer to
Economizer Installation Instructions.
Fig. 18 — Typical Fan Discharge Connections
for Multiple Fan Units
24
Fig. 19 — Duct Flange Installation
START-UP
Fan Shaft Bearings — Bearings on size 007-012 units
are sealed, permanently lubricated bearings that require no
further lubrication. Size 014-034 units have pillow-block bear-
ings (Fig. 20) that must be lubricated with suitable bearing
grease approximately every 3 months. See Table 7 for suitable
lubricants.
Before starting unit, check the following and correct as nec-
essary:
•
•
•
•
•
•
Is unit solidly supported?
Is fan adjusted for speed and pulley alignment?
Are pulleys, motor, and bearings securely mounted?
Are there any loose parts that will rattle or vibrate?
Is condensate drain pan pitched for correct drainage?
Are coil baffle plates tight against coil to prevent air
bypass?
Table 7 — Lubricant Data
MANUFACTURER
LUBRICANT
Mobil
Mobilplex EP No. 2
Prestige 42
Sunoco
Texaco
Texaco
•
•
Are all panels securely fastened?
Are all electrical connections correct and tight?
Multifak 2
Regal AFB-2*
Also refer to condensing unit instructions before starting a
split system. A split system start-up checklist is provided at the
end of these instructions.
*Preferred lubricant because it contains rust and oxidation inhibitors.
SERVICE
Inspection and maintenance should be performed at regular
intervals and should include the following:
•
Complete cleaning of cabinet, fan wheel, cooling coil,
condensate pan and drain, heating coils, and return-air
grille (if present).
Inspection of panels and sealing of unit against air
leakage.
•
•
•
•
•
Adjustment of fan motor, belt, bearings, and wheels.
Cleaning or replacement of filters.
Testing for cooling/heating system leaks.
Checking of all electrical connections.
Most unit service can be performed by removing one or
both of the unit’s side panels. Coil cleaning or removal or insu-
lation cleaning may require removal of a rear, top, or bottom
panel, depending on the unit’s orientation. When service is
completed, replace unit panels.
Panels — Panels are fastened to unit frame with sheet metal
screws. Fan and coil compartment must be sealed tightly after
service to prevent air from bypassing the cooling coil.
Fig. 20 — Fan Shaft, Bearings, and Fan Wheel
(Typical)
Fan Motor Lubrication — Fan motor supplied with
unit is permanently lubricated and requires no further
lubrication.
25
Centering Fan Wheel — If fan and fan shaft assembly
are not properly centered, blades may scrape against scroll or
may create an objectionable whistling noise. It may be neces-
sary to adjust individual fan wheels or move entire fan shaft.
See the following two sections.
Individual Fan Wheel Adjustment — Loosen the
2 locking bolts holding fan wheel hub to shaft. See Fig. 20.
Position fan wheel in center of the fan housing and tighten
locking bolts. Clearance between wheel and housing should be
the same on both sides.
Fan Shaft Position Adjustment — Loosen set-
screw or locking collar of each fan shaft bearing. Slide shaft
into correct position and replace locking collar (Fig. 21). To re-
place locking collar, push collar up against inner face of bear-
ing. Turn collar in direction of fan rotation until tight, and tight-
en setscrew. Tightening locking collar in direction of fan rota-
tion results in further tightening of collar should setscrew work
itself loose.
Fan Belts — Motor mounting plate and motor support an-
gles are slotted to permit both vertical and horizontal adjust-
ment. Adjust belt(s) for correct deflection by loosening motor
plate mounting bolts, moving motor/plate assembly forward or
back, and retightening bolts. Press down on belt with one fin-
ger midway between fan and motor pulleys to check deflection.
For units with motor sizes up to and including 3.7 Hp
3
(2.76 kW), correct deflection is /16-in. (4.8 mm). For larger
motor sizes, correct deflection is 1/8-in. (3.2 mm). See Fig. 22.
NOTE: The 028 and 034 size units with 60 Hz motors
(standard or medium static drive) are shipped with an extra set
of belts. Use the preinstalled belts or extra belts depending on
the adjustable pulley setting.
If complete belt replacement is required during servicing,
loosen the motor plate mounting bolts (Fig. 22), move motor/
plate assembly towards fan pulley, and pull belt(s) off pulleys.
Reverse the procedure with new bolts and readjust deflection.
Fan Rotation — Correct fan rotation with respect to fan
outlet is shown in Fig. 23.
To reverse the direction of rotation of a 3-phase fan motor,
reverse any 2 of the power leads. Refer to the connection dia-
gram on the inside of motor terminal box cover for proper re-
versing procedure of single-phase motor.
Fig. 21 — Fan Shaft Bearing
Fig. 22 — Fan Motor Mounting
26
Fig. 23 — Fan Rotation
Fan Pulley Alignment — Align as follows:
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan pulley
to lock it in place.
3. Use the methods shown in Fig. 24 to check proper pulley
alignment.
Fig. 24 — Fan Pulley Adjustments
4. If pulleys are not in correct alignment, loosen the motor
holddown bolts and slide the motor axially until the pul-
leys are aligned.
5. Tighten motor holddown bolts.
Alternative freeze protection methods follow:
•
•
Circulate hot water within the water coil’s supply main
or supplementary space heating.
Close off supply lines to unit and open a union or field-
supplied drain valve in the return line.
Pulley and Drive Adjustment — To obtain desired
fan speed, refer to the fan motor and drive data in Tables 8A-
11D and adjust fan motor pulley as follows:
1. Remove belt from fan motor pulley after loosening motor
from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw
moveable flange toward fixed flange to increase the fan
speed and away from fixed flange to reduce speed. Be-
fore tightening setscrew, make certain that setscrew is
over nearest flat surface of pulley hub (Fig. 24).
IMPORTANT: Draining from return line will not com-
pletely drain water from coils.
•
•
After draining as much water as possible from coils, add
sufficient antifreeze to prevent residual water in the coil
from freezing.
Add a sufficient quantity of non-corrosive antifreeze to
the entire system to prevent all water within the system
from freezing.
Increasing fan speed produces a greater load on motor. Do
not exceed rated capacity of motor.
Coil Removal — Remove unit panels and corner posts as
required. Disconnect coil connections and remove fastening
screws. Remove coil through end or side sections of unit.
Condensate Drains — Keep condensate drains free of
dirt and foreign matter.
Cleaning Cooling Coil — Remove return-air filters.
Remove any heavy dirt that may have accumulated on under-
side of coil. Coil can be cleaned more easily with a stiff brush,
vacuum cleaner, or compressed air when coil is dry. If coil is
wet or if water is to be used for cleaning, guard against splash-
ing water on electrical components or damaging surrounding
area. Clean coil baffles as applicable and check for tight fit to
be sure air does not bypass coil.
Return-Air Filters — Refer to Replacing Filters section
for filter accessibility and removal. Replace with clean filters of
the sizes listed in Tables 1A-1F.
Chilled Water Coil Freeze Protection — Shut off
water supply to unit. Remove side panel of unit and remove
vent and drain plugs in top and bottom of coil header. Drain
coil and blow out remaining water. Reinstall plugs and side
panel.
Cleaning Insulation — The insulation contains an im-
mobilized antimicrobial agent that helps prevent the growth of
bacteria and fungi. Clean the inner surface of the insulation
according to the separate maintenance instructions shipped
with the unit.
27
Replacing Filters — Filters can be removed and in-
stalled from either side of the unit. Install new filters in units
that have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 25).
3. Remove old filters by lifting and tilting them out of the
filter track. See Fig. 15 and 26.
4. Reverse the procedure to install new filters.
To install new filters in larger units that have 2 fans, follow
the preceding steps, but use the factory-supplied filter hook to
slide filters within reach for removal. The filter hook is shipped
inside the unit in the filter track.
Do not operate unit without air filters.
Fig. 26 — Filter Removal/Replacement
FILTER
RETAINER
CLIP
SLIDE
Fig. 25 — Remove Filter Retainer Clip
28
Table 8A — Fan Motor Data, Standard Motor — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
208/230-1-60
Speed (rpm)
Hp
1725
1.3
1725
2.4
1725
2.4
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Frame (NEMA)
Shaft Dia (in.)
208/230-3-60 and 460-3-60
Speed (rpm)
Hp
56Y
56Y
56Y
5
5
5
/
8
/
8
/
8
1725
2.4
1725
2.4
1725
2.4
1725
2.4
1725
2.9
1725
3.7
1745
5.0
1745
7.5
1745
10.0
Frame (NEMA)
Shaft Dia (in.)
575-3-60
56Y
56Y
56Y
56Y
56Y
56Y
S184T
S213T
S215T
5
5
5
5
7
7
1
3
3
/
8
/
8
/
8
/
8
/
8
/
8
1 /
1 /
1 /
8
8
8
Speed (rpm)
Hp
1725
1.0
1725
2.0
1725
2.0
1725
2.0
1725
3.0
1725
3.0
1745
5.0
1755
7.5
1755
10.0
Frame (NEMA)
Shaft Dia (in.)
230-3-50 and 400-3-50
Speed (rpm)
Hp
56
56HZ
56HZ
56HZ
56HZ
56HZ
184T
S213T
D215T
5
7
7
7
7
7
1
3
3
/
8
/
8
/
8
/
8
/
8
/
8
1 /
1 /
1 /
8
8
8
1425
2.4
1425
2.4
1425
2.4
1425
2.9
1425
2.9
1425
2.9
1425
5.0
1425
7.5
1425
10.0
Frame (NEMA)
Shaft Dia (in.)
56Y
56Y
56Y
56Y
56Y
56Y
184T
S213T
S215T
5
5
5
7
7
7
1
3
3
/
8
/
8
/
8
/
8
/
8
/
8
1 /
1 /
1 /
8
8
8
LEGEND
NEMA — National Electrical Manufacturers Association
Table 8B — Fan Motor Data, Alternate Motor — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RM
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
007
40RMS
010
40RMQ
40RMS
016
40RMQ
40RMS
024
UNIT
208/230-1-60
Speed (rpm)
Hp
1725
2.4
1725
2.4
1725
2.4
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Frame (NEMA)
Shaft Dia (in.)
208/230-3-60 and 460-3-60
Speed (rpm)
Hp
56Y
56Y
56Y
5
5
5
/
8
/
8
/
8
1725
2.9
1725
2.9
1725
2.9
1725
3.7
1725
3.7
1725
5.0
1745
7.5
1745
10.0
Frame (NEMA)
Shaft Dia (in.)
575-3-60
56Y
56Y
56Y
Y56Y
Y56Y
S184T
S213T
S215T
7
7
7
7
7
1
3
3
/
8
/
8
/
8
/
8
/
8
1 /
1 /
1 /
8
8
8
Speed (rpm)
Hp
1725
2.0
1725
3.0
1725
3.0
1725
3.0
1745
5.0
1745
5.0
1755
7.5
1750
10.0
Frame (NEMA)
Shaft Dia (in.)
230-3-50 and 400-3-50
Speed (rpm)
Hp
56HZ
56HZ
56HZ
56HZ
184T
184T
S213T
D215T
7
7
7
7
1
1
3
3
/
8
/
8
/
8
/
8
1 /
1 /
1 /
1 /
8
8
8
8
1425
2.4
1425
2.9
1425
2.9
1425
5.0
1425
5.0
1425
5.0
1425
7.5
1425
10.0
Frame (NEMA)
Shaft Dia (in.)
56Y
56Y
56Y
S184T
S184T
S184T
S213T
S215T
7
7
7
7
1
1
3
3
/
8
/
8
/
8
/
8
1 /
1 /
1 /
1 /
8
8
8
8
LEGEND
NEMA — National Electrical Manufacturers Association
29
Table 8C — Fan Motor Data, Standard Motor — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
208/230-1-60
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
208/230-3-60 and 460-3-60
Speed (r/s)
28.75
0.97
56Y
28.75
1.79
56Y
28.75
1.79
56Y
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
15.9
15.9
15.9
28.75
1.79
56Y
28.75
1.79
56Y
28.75
1.79
56Y
28.75
1.79
56Y
28.75
2.16
56Y
28.75
2.76
56Y
29.08
3.73
29.08
5.60
29.08
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
575-3-60
S184T
28.6
S213T
34.9
S215T
34.9
15.9
15.9
15.9
15.9
22.2
22.2
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
230-3-50 and 400-3-50
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
28.75
0.746
56
28.75
1.49
28.75
1.49
28.75
1.49
28.75
2.24
28.75
2.24
29.08
3.73
29.25
5.60
29.25
7.46
56HZ
22.2
56HZ
22.2
56HZ
22.2
56HZ
22.2
56HZ
22.2
184T
28.6
S213T
34.9
S215T
34.9
15.9
23.75
1.79
56Y
23.75
1.79
56Y
23.75
1.79
56Y
23.75
2.16
56Y
23.75
2.16
56Y
23.75
2.16
56Y
23.75
3.73
23.75
5.60
23.75
7.46
184T
28.6
S213T
34.9
S215T
34.9
15.9
15.9
15.9
22.2
22.2
22.2
LEGEND
NEMA — National Electrical Manufacturers Association
Table 8D — Fan Motor Data, Alternate Motor — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
007
40RMS
010
40RMQ
40RMS
016
UNIT
208/230-1-60
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
208/230-3-60 and 460-3-60
Speed (r/s)
28.75
1.79
56Y
28.75
1.79
56Y
28.75
1.79
56Y
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
15.9
15.9
15.9
28.75
2.16
56Y
28.75
2.16
56Y
28.75
2.16
56Y
28.75
2.76
28.75
2.76
29.08
3.73
29.08
5.60
29.17
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
575-3-60
Y56Y
22.2
Y56Y
22.2
S184T
28.6
S213T
34.9
S215T
34.9
22.2
22.2
22.2
Speed (r/s)
Shaft kW
28.75
1.49
28.75
2.24
28.75
2.24
28.75
2.24
29.08
3.73
29.08
3.73
29.25
5.60
29.17
7.46
Frame (NEMA)
Shaft Dia (mm)
230-3-50 and 400-3-50
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
56HZ
22.2
56HZ
22.2
56HZ
22.2
56HZ
22.2
184T
28.6
184T
28.6
S213T
34.9
D215T
34.9
23.75
1.79
56Y
23.75
2.16
56Y
23.75
2.16
56Y
23.75
3.73
23.75
3.73
23.75
3.73
23.75
5.60
23.75
7.46
S184T
22.2
S184T
28.6
S184T
28.6
S213T
34.9
S215T
34.9
22.2
22.2
22.2
LEGEND
NEMA — National Electrical Manufacturers Association
30
Table 9A — Standard Drive Data, 60 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
2.4-3.4
2.5
2.8-3.8
2.5
2.8-3.8
2.5
3.4-4.4
2.5
2.8-3.8
2.5
2.8-3.8
2.5
3.7-4.7
3.0
4.3-5.3
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
8.8
1
8.8
1
8.8
1
8.8
1
9.0
9.0
9.4
11.0
11.0
7
7
7
15
15
1 /
1 /
1 /
1
/
1
/
16
16
16
16
16
1—A
1—A
1—A
1—A
1—A
1—A
2—B
2—B*
2—B*
(2) 42.8
(2) 43.8
(2) 42.8
(2) 43.8
40.3
41.3
41.3
42.3
42.3
42.3
41.8
FAN SPEEDS (rpm)
Factory Setting
Range
568
470-666
1200
647
549-745
1200
647
549-745
1200
764
666-863
1200
632
537-728
1200
632
537-728
1200
771
679-863
1200
752
682-841
1100
752
674-831
1100
Max Allowable Speed (rpm)
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
19.6
19.6
19.6
19.7
19.1
19.1
15.3
13.1
13.1
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
5
6
6
6
SHAFTS CENTER DISTANCE (in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.12-
10.99
6.67-
9.43
6.67-
9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
Table 9B — Medium-Static Drive Data, 60 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.7-4.7
3.0
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
8.8
1
8.0
1
8.0
1
8.0
1
8.2
8.6
9.4
9.4
9.4
7
7
7
15
15
1 /
1 /
1 /
1
/
1
/
16
16
16
16
16
1—A
1—A
1—A
1—A
1—A
1—B
1—B
2—B*
2—B*
(2) 38.8
(2) 39.8
(2) 38.8
(2) 39.8
42.3
40.3
40.3
40.3
41.3
41.8
41.8
FAN SPEEDS (rpm)
Factory Setting
Range
764
666-863
1200
841
733-949
1200
841
733-949
1200
841
733-949
1200
820
715-926
1200
842
742-943
1200
881
798-984
1200
881
798-984
1100
881
798-984
1100
Max Allowable Speed (rpm)
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
19.7
21.6
21.6
21.6
21.1
16.7
15.3
15.3
15.3
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
6
6
6
SHAFTS CENTER DISTANCE (in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.16-
10.99
6.67-
9.43
6.67-
9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
31
Table 9C — High-Static Drive Data, 60 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.7-4.7
3.0
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
7.0
1
6.0*
1
6.0
1
6.0
1
7.4
7.9
7.4
8.6
8.6
7
7
7
15
15
1 /
1 /
1 /
1
/
1
/
16
16
16
16
16
1—A
41.3
1—A
37.3
1—A
37.3
1—A
37.3
1—B
39.8
1—B
39.8
2—B
36.8
2—B
37.8
2—B
37.8
961
1121
1121
1121
979
1060
1118
1024
1024
838-
1084
978-
1200*†
978-
1200†
978-
1200†
873-
1096
950-
1171
1014-
1200†
873-
1075
873-
1075
Max Allowable Speed (rpm)
1200
24.6
1200
28.7
1200
28.7
1200
28.7
1200
19.4
1200
18.4
1200
1100
16.7
1100
16.7
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
19.4
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
6
6
6
6
6
SHAFTS CENTER DISTANCE (in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32**
9.16-
10.99
8.16-
10.02
6.67-
9.43
6.67-
9.43
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in. and result-
ing fan speed is 837-1096 rpm.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed
1200 rpm.
**575-v unit has a center distance of 9.16-10.99.
Table 9D — Standard Drive Data, 60 Hz — SI
40RM
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMQ 40RMS
UNIT
40RMS
008
010
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
61.0-
86.4
71.1-
96.5
71.1-
96.5
86.4-
111.8
71.1-
96.5
71.1-
96.5
94.0-
119.4
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
224
25.4
1—A
224
25.4
1—A
224
25.4
1—A
224
25.4
1—A
229
36.5
1—A
229
36.5
1—A
239
36.5
2—B
279
49.2
279
49.2
2—B*
2—B*
(2) 1087
(2) 1113
(2) 1087
(2) 1113
1024
1049
1049
1074
1074
1074
1062
FAN SPEEDS (r/s)
Factory Setting
Range
9.5
10.8
10.8
12.7
10.5
10.5
12.9
12.5
12.5
7.8-11.1 9.2-12.4 9.2-12.4 11.1-14.4 9.0-12.1 9.0-12.1 11.3-14.4 11.4-14.0 11.2-13.9
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per / Turn of
2
Moveable Motor Pulley
Flange
0.327
0.327
0.327
0.328
0.318
0.318
0.255
0.218
0.218
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
5
6
6
6
SHAFTS CENTER DISTANCE (mm)
265-313 265-313 265-313 265-313 265-313 265-313 232-279
169-240
169-240
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
32
Table 9E — Medium-Static Drive Data, 60 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
94.0-
119.4
109.2-
134.6
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
224
25.4
1—A
203
25.4
1—A
203
25.4
1—A
203
25.4
1—A
208
36.5
1—A
218
36.5
1—B
239
36.5
1—B
239
49.2
239
49.2
2—B*
2—B*
(2) 986
(2) 1011
(2) 986
(2) 1011
1074
1024
1024
1024
1049
1062
1062
FAN SPEEDS (r/s)
Factory Setting
Range
12.7
14.0
14.0
14.0
13.7
14.0
14.7
14.7
14.7
11.1-14.4 12.2-15.8 12.2-15.8 12.2-15.8 11.9-15.4 12.4-15.7 13.3-16.4 13.3-16.4 13.3-16.4
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per / Turn of
2
Moveable Motor Pulley
Flange
0.328
0.360
0.360
0.360
0.352
0.278
0.255
0.255
0.255
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
6
6
6
SHAFTS CENTER DISTANCE (mm)
265-313
265-313
265-313
265-313
265-313
265-313
232-279
169-240
169-240
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
Table 9F — High-Static Drive Data, 60 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
94.0-
119.4
109.2-
134.6
109.2-
134.6
109.2
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
178
25.4
1—A
1049
152*
25.4
1—A
947
152
25.4
1—A
947
152
25.4
1—A
947
188
36.5
1—B
1011
201
36.5
1—B
1011
188
36.5
2—B
935
203
49.2
2—B
935
203
49.2
2—B
960
16.0
18.7
18.7
18.7
16.3
17.7
18.6
17.1
17.1
14.0-
18.1
16.3-
20.0*†
16.3-
20.0†
16.3-
20.0†
14.4-
18.3
15.8-
19.5
16.9-
20.0†
14.6-
17.9
14.6-
17.9
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
0.410
0.478
0.478
0.478
0.323
0.307
0.323
0.278
0.278
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
6
6
6
6
6
SHAFTS CENTER DISTANCE (mm)
265-313
265-313
265-313
265-313 265-313** 232-279
207-255
169-240
169-240
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 178 mm and
resulting fan speed is 14.0-18.3 r/s.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed
20 r/s.
**575-v unit has a center distance of 233-279.
33
Table 10A — Standard Drive Data, 50 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
2.4-3.4
2.5
2.8-3.8
2.5
2.8-3.8
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
8.0
1
8.0
1
8.0
1
8.0
1
9.0
9.0
8.6
11.0
11.0
7
7
7
15
15
1 /
1 /
1 /
1
/
1
/
16
16
16
16
16
1—A
39.3
1—A
39.3
1—A
39.3
1—A
40.3
1—A
42.3
1—A
42.3
1—B
41.8
2—B
43.8
2—B
43.8
517
428-606
1200
588
499-677
1200
588
449-677
1200
695
606-784
1200
618
538-697
1200
618
538-697
1200
795
713-878
1200
622
557-687
1100
622
557-687
1100
Max Allowable Speed (rpm)
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
17.8
17.8
17.8
17.8
15.9
15.9
13.8
10.8
10.8
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
5
6
6
6
SHAFTS CENTER DISTANCE (in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44
12.32-
9.12-
10.99
6.67-
9.43
6.67-
9.43
Table 10B — Medium-Static Drive Data, 50 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.7-4.7
3.0
4.0-5.0
2.5
4.3-5.3
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
8.0
1
7.0
1
7.0
1
6.0
1
7.5
7.9
7.0
9.4
9.4
7
7
7
15
15
1 /
1 /
1 /
1
/
1
/
16
16
16
16
16
1—A
40.3
1—A
41.3
1—A
41.3
1—A
37.3
1—A
39.3
1—B
39.8
2—A
36.8
2—B
39.8
2—B
39.8
695
794
794
926
741
756
916
728
728
606-784 692-896 692-896 808-1045 646-836 667-848 814-1018 652-803 652-803
Max Allowable Speed (rpm)
1200
1200
1200
1200
1200
1200
1200
1100
1100
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
17.8
20.4
20.4
23.7
19.0
15.1
20.4
12.6
12.6
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
5
6
6
SHAFTS CENTER DISTANCE (in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.16-
10.99
9.16-
10.99
6.67-
9.43
6.67-
9.43
34
Table 10C — High-Static Drive Data, 50 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
4.0-5.0
3.0
3.4-4.4
2.5
4.0-5.0
3.0
4.0-5.0
3.0
4.3-5.3
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
6.0
1
5.5
1
5.5
1
5.5
1
6.0
7.0
6.4
8.0
8.6
7
7
7
15
15
1 /
1 /
1 /
1
/
1
/
16
16
16
16
16
1—A
37.3
1—A
37.3
1—A
37.3
1—A
36.3
2—A
36.3
2—A
39.3
2—A
34.3
2—B
36.8
2—B
37.8
926
1010
1010
1166
926
916
1002
855
795
808-
1045
881-
1140
881-
1140
1036-
1200*
808-
1045
814-
1018
891-
1113
766-
944
713-
878
Max Allowable Speed (rpm)
1200
23.7
1200
25.9
1200
25.9
1200
1200
23.7
1200
17.0
1200
18.5
1100
1100
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
21.6
14.8
13.8
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
6
5
6
6
6
6
SHAFTS CENTER DISTANCE (in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.16-
10.99
9.16-
10.99
9.16-
10.99
8.16-
10.02
6.67-
9.43
6.67-
9.43
*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
Table 10D — Standard Drive Data, 50 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
61.0
86.4
71.1
96.5
71.1-
96.5
86.4-
111.8
86.4-
111.8
86.4-
111.8
109.2
134.6
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
203
25.4
1—A
998
203
25.4
1—A
998
203
25.4
1—A
998
203
25.4
1—A
1024
229
36.5
1—A
1074
229
36.5
1—A
1074
218
36.5
1—B
1062
279
49.2
2—B
1113
279
49.2
2—B
1113
8.6
9.8
9.8
11.6
10.3
10.3
13.3
10.4
10.4
7.1-10.1 8.3-11.3 8.3-11.3 10.1-13.1 9.0-11.6 9.0-11.6 11.9-14.6 9.3-11.5 9.3-11.5
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
0.297
0.297
0.297
0.297
0.265
0.265
0.230
0.180
0.180
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
5
6
6
6
SHAFTS CENTER DISTANCE (mm)
265-313 265-313 265-313 265-313 265-313 265-313 232-279 169-240 169-240
35
Table 10E — Medium-Static Drive Data, 50 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
86.4
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
94.0-
119.4
101.6-
127.0
109.2-
134.6
109.2
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
2.5
3.0
2.5
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
203
25.4
1—A
1024
178
25.4
1—A
1049
178
25.4
1—A
1049
152
25.4
1—A
947
191
36.5
1—A
998
201
36.5
1—B
1011
178
36.5
2—A
922
239
49.2
2—B
1011
239
49.2
2—B
1011
11.6
13.2
13.2
15.4
12.4
12.6
15.3
12.1
12.1
10.1-13.1 11.5-14.9 11.5-14.9 13.5-17.4 10.8-13.9 11.1-14.1 13.6-17.0 10.9-13.4 10.9-13.4
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
0.297
0.340
0.340
0.395
0.317
0.252
0.340
0.210
0.210
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
5
6
6
SHAFTS CENTER DISTANCE (mm)
265-313
265-313
265-313
265-313
265-313
232-279
232-279
169-240
169-240
Table 10F — High-Static Drive Data, 50 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMQ
40RMS
024
40RM
40RMQ
40RMS
028
40RM
40RMS
014
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
86.4-
111.8
86.4-
111.8
86.4-
111.8
101.6-
127.0
86.4-
111.8
101.6-
127.0
101.6-
127.0
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
3.0
2.5
3.0
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
152
25.4
1—A
947
140
25.4
1—A
947
140
25.4
1—A
947
140
25.4
1—A
922
152
36.5
2—A
922
178
36.5
2—A
998
163
36.5
2—A
871
203
49.2
2—B
935
218
49.2
2—B
960
15.4
16.8
16.8
19.4
15.4
15.3
16.7
14.3
13.3
13.5-17.4 14.7-19.0 14.7-19.0 17.3-20.0* 13.5-17.4 13.6-17.0 14.9-18.6 12.8-15.7 11.9-14.6
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
0.395
0.432
0.432
0.360
0.395
0.283
0.308
0.247
0.230
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
6
5
6
6
6
6
SHAFTS CENTER DISTANCE (mm)
265-313 265-313 265-313
234-279
232-279 232-279 207-255 169-240 169-240
*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 20 r/s.
36
Table 11A — 40RM,RMQ Standard Fan Performance Data —
0.0-2.4 in. wg External Static Pressure — English
EXTERNAL STATIC PRESSURE (in. wg)
UNIT
40RM,
RMQ
AIRFLOW
(Cfm)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1,800
2,100
2,400
2,700
3,000
2,250
2,600
3,000
3,400
3,750
3,000
3,500
4,000
4,500
5,000
3,750
4,300
5,000
5,700
6,250
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
399
446
498
544
594
0.19
0.28
0.40
0.55
0.73
454
497
541
588
635
0.24
0.34
0.47
0.63
0.82
548
583
622
663
707
0.35
0.46
0.60
0.78
0.99
634
660
693
730
770
0.47
0.59
0.74
0.93
1.15
713
733
760
792
828
0.60
0.73
0.89
1.09
1.32
785
802
824
851
883
0.74
0.88
1.05
1.26
1.50
850
867
885
909
937
0.89
1.05
1.22
1.44
1.69
007
008
012
014
016
024
273
322
552
615
671
0.08
0.15
0.65
0.91
1.20
493
540
595
653
706
0.37
0.52
0.73
1.01
1.31
580
622
673
726
773
0.49
0.66
0.91
1.21
1.53
656
693
740
789
834
0.62
0.81
1.07
1.40
1.74
727
757
800
846
889
0.76
0.96
1.24
1.59
1.95
794
819
856
899
940
0.92
1.12
1.41
1.78
2.16
858
878
910
950
988
1.08
1.29
1.60
1.97
2.37
399
604
680
756
834
0.29
0.92
1.33
1.86
2.51
573
641
713
787
861
0.69
1.02
1.45
1.99
2.67
654
714
778
845
914
0.86
1.22
1.68
2.26
2.96
722
780
839
901
966
1.03
1.42
1.91
2.52
784
838
896
955
1.19
1.61
2.14
2.78 1005
3.54 1064
841
892
947
1.37
1.81
2.36
3.03 1051
3.82 1109
896
942
995
1.55
2.01
2.58
3.28
4.11
3.25 1016
394
436
492
550
596
0.40
0.57
0.86
1.23
1.59
453
487
535
587
630
0.52
0.70
0.99
1.37
1.74
558
586
623
664
700
0.80
1.00
1.31
1.71
2.09
643
670
704
740
770
1.10
1.34
1.69
2.11
2.51
717
742
775
809
837
1.39
1.67
2.08
2.55
2.97
785
806
838
872
899
1.71
2.01
2.47
2.99
3.45
848
867
896
929
955
2.04
2.36
2.86
3.43
3.94
428
488
542
604
660
0.59
0.92
1.29
1.83
2.42
475
528
578
637
690
0.70
1.04
1.43
1.99
2.59
570
609
649
700
747
0.99
1.34
1.74
2.32
2.95
656
689
721
763
804
1.33
1.71
2.11
2.70
3.34
730
762
791
826
861
1.68
2.11
2.55
3.15
3.79
796
827
855
888
919
2.02
2.51
3.00
3.64
4.29
856
886
914
946
975
2.38
2.92
3.46
4.15
4.83
532
608
686
764
843
1.25
1.93
2.83
3.97
5.38
569
641
716
791
868
1.39
2.09
3.01
4.18
5.62
639
702
770
841
914
1.69
2.42
3.38
4.59
6.09
711
763
823
888
957
2.06
2.80
3.77
5.02
781
824
876
935
2.48
3.23
4.21
5.47
846
885
930
982
2.93
3.71
4.70
5.96 1030
7.53 1084
905
943
983
3.39
4.23
5.24
6.51
8.08
6.55 1000
7.02 1042
7,500
8,750
10,000
11,250
12,500
15,000
456
521
587
653
720
829
1.29
1.98
2.88
4.03
5.46
8.84
490
551
614
678
743
850
1.47
2.18
3.11
4.29
5.75
9.19
556
608
664
724
785
888
1.85
2.61
3.59
4.82
6.33
9.88
621
664
714
768
825
924
2.25
3.07
4.09
5.37
6.93
10.57
678
720
763
812
865
2.64
3.53
4.62
5.95
7.55
729
770
812
856
904
3.06
3.99
5.15
6.54
8.20
778
816
857
899
944
3.60
4.45
5.68
7.14
8.86
028
034
958 11.27
991 11.99 1024 12.73
9,000
10,500
12,000
13,500
15,000
521
596
673
751
829
1.99
3.16
4.63
6.51
8.84
550
623
698
773
850
2.25
3.40
4.90
6.82
9.19
616
672
743
815
888
2.77
3.89
5.45
7.44
9.88
676
720
785
853
924
3.23
4.40
731
767
826
890
3.72
4.94
6.62
8.71
782
814
867
927
4.20
5.50
7.23
9.38
829
859
908
4.70
6.05
7.87
6.02
8.06
10.57
963 10.07
958 11.27
991 11.99 1024 12.73
See Legend and Notes on page 45.
37
Table 11A — 40RM,RMQ Standard Fan Performance Data —
0.0-2.4 in. wg External Static Pressure — English (cont)
EXTERNAL STATIC PRESSURE (in. wg)
UNIT
40RM,
RMQ
AIRFLOW
(Cfm)
1.4
1.6
1.8
2.0
2.2
2.4
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1,800
2,100
2,400
2,700
3,000
2,250
2,600
3,000
3,400
3,750
3,000
3,500
4,000
4,500
5,000
3,750
4,300
5,000
5,700
6,250
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
910
927
944
964
989
1.04
1.21
1.41
1.63
1.89
965
983
1.20
1.38
1.59
1.82
2.10
1016
1035
1052
1069
1089
1.36
1.56
1.78
2.03
2.31
1065
1084
1101
1118
1136
1.52
1.74
1.98
2.24
2.53
1111
1131
1149
1165
1183
1.69
1.92
2.18
2.45
2.76
1155
1175
1193
—
1.86
2.11
2.38
—
007
008
012
014
016
024
999
1018
1039
—
—
918
936
1.26
1.48
1.79
2.18
2.58
975
991
1014
1045
1078
1.43
1.67
1.99
2.39
2.80
1029
1044
1064
1092
1122
1.62
1.87
2.20
2.61
3.03
1079
1094
1113
1137
1164
1.80
2.07
2.42
2.83
3.27
1126
1142
1159
1182
—
1.99
2.28
2.64
3.07
—
1172
1188
—
—
—
2.18
2.49
—
—
—
963
998
1034
949
990
1040
1094
1151
1.74
2.21
2.80
3.53
4.39
1000
1037
1084
1136
1191
1.93
2.42
3.03
3.78
4.66
1050
1083
1126
1176
—
2.14
2.64
3.26
4.03
—
1099
1128
1167
—
2.36
2.86
3.50
—
1147
1172
—
—
—
2.58
3.10
—
—
—
1192
—
2.81
—
—
—
—
—
—
—
—
—
909
925
2.37
2.73
3.26
3.88
4.42
968
980
1002
1031
1057
2.74
3.11
3.67
4.33
4.91
1026
1034
1052
1079
1103
3.12
3.52
4.09
4.79
5.40
1080
1084
1101
1125
1148
3.51
3.92
4.53
5.25
5.90
1131
1135
1148
1169
1191
3.92
4.35
4.98
5.73
6.40
1181
1184
1190
—
4.32
4.78
5.44
—
950
981
1007
—
—
912
940
968
1000
1028
2.75
3.33
3.92
4.67
5.39
967
992
1018
1050
1078
3.13
3.75
4.38
5.19
5.97
1019
1041
1066
1097
1125
3.52
4.18
4.85
5.71
6.54
1070
1088
1112
1142
1170
3.92
4.61
5.32
6.23
7.11
1120
1134
1156
1185
—
4.35
5.06
5.80
6.76
—
1168
1179
1198
—
4.79
5.52
6.29
—
—
—
954
990
1028
1073
1126
3.83
4.74
5.79
7.11
8.75
1005
1040
1078
1120
1166
4.27
5.24
6.38
7.72
9.37
1052
1090
1130
1169
—
4.72
5.80
7.00
8.37
—
1098
1135
1173
—
5.22
6.30
7.60
—
1142
1176
—
—
—
5.67
6.84
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7,500
8,750
10,000
11,250
12,500
15,000
831
859
4.41
4.97
6.20
7.73
9.53
13.49
870
901
5.10
5.59
913
944
976
1017
1058
—
5.90
6.42
7.33
8.90
10.84
—
950
980
1013
1052
1093
—
6.88
7.20
8.00
9.51
11.49
—
985
1020
1050
1086
—
7.70
8.10
8.82
10.16
—
—
—
—
—
—
—
—
—
—
—
—
—
900
939
6.74
028
034
941
980
1022
1090
8.32
10.19
14.28
984
1057
—
—
9,000
10,500
12,000
13,500
15,000
866
902
5.20
6.60
899
942
5.85
7.14
950
980
1026
1073
—
6.65
7.70
9.76
12.21
—
989
1016
1062
—
7.38
8.31
10.38
—
1029
1051
1095
—
8.32
8.99
11.01
—
1077
1085
—
9.74
9.77
—
949
8.50
988
9.14
1000
1057
10.78
13.49
1036
1090
11.49
14.28
—
—
—
—
—
—
—
—
See Legend and Notes on page 45.
38
Table 11B — 40RM,RMQ Standard Fan Performance Data —
0-600 kPa External Static Pressure — SI
EXTERNAL STATIC PRESSURE (kPa)
UNIT
40RM,
RMQ
AIRFLOW
(L/s)
0
50
100
150
200
250
300
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
850
990
6.64
7.73
8.30
9.06
9.91
0.14
0.21
0.30
0.41
0.55
7.56
8.28
0.18
0.25
0.35
0.47
0.61
9.13
9.71
10.36
11.06
11.78
0.26
0.34
0.45
0.58
0.74
10.56
11.00
11.55
12.17
12.83
0.35
0.44
0.55
0.69
0.86
11.88
12.22
12.67
13.20
13.80
0.45
0.54
0.66
0.81
0.99
13.08
13.37
13.73
14.19
14.72
0.55
0.66
0.78
0.94
1.12
14.16
14.44
14.76
15.14
15.61
0.66
0.78
0.91
1.07
1.26
007
008
012
014
016
024
028
034
1130
1270
1420
9.02
9.79
10.58
1060
1230
1420
1600
1770
1420
1650
1890
2120
2360
1770
2030
2360
2690
2950
2120
2500
2830
3210
3540
2830
3300
3780
4250
4720
3540
4130
4720
5310
5900
4250
4960
5660
6370
7080
4.55
5.37
9.21
10.25
11.18
0.06
0.11
0.48
0.68
0.90
8.21
8.99
9.92
10.89
11.76
0.27
0.38
0.55
0.75
0.98
9.67
10.37
11.22
12.09
12.88
0.37
0.49
0.67
0.90
1.14
10.93
11.55
12.33
13.15
13.90
0.46
0.60
0.80
1.04
1.30
12.11
12.62
13.33
14.10
14.82
0.57
0.71
0.92
1.18
1.45
13.23
13.65
14.27
14.99
15.67
0.68
0.84
1.05
1.33
1.61
14.30
14.64
15.17
15.83
16.46
0.81
0.96
1.19
1.47
1.77
6.65
10.06
11.33
12.61
13.90
0.22
0.68
0.99
1.38
1.87
9.55
10.69
11.88
13.11
14.36
0.51
0.76
1.08
1.49
1.99
10.89
11.90
12.96
14.08
15.23
0.64
0.91
1.25
1.68
2.21
12.04
13.00
13.99
15.02
16.10
0.77
1.06
1.43
1.88
2.42
13.06
13.97
14.93
15.92
16.94
0.89
1.20
1.59
2.07
2.64
14.02
14.86
15.78
16.74
17.73
1.02
1.35
1.76
2.26
2.85
14.93
15.70
16.58
17.51
18.48
1.15
1.50
1.92
2.44
3.06
6.57
7.27
8.20
9.16
9.93
0.30
0.43
0.64
0.92
1.18
7.54
8.11
0.39
0.52
0.74
1.02
1.30
9.31
9.76
10.38
11.07
11.66
0.60
0.75
0.98
1.27
1.56
10.72
11.16
11.73
12.33
12.83
0.82
1.00
1.26
1.58
1.87
11.95
12.36
12.91
13.48
13.95
1.04
1.25
1.55
1.90
2.22
13.09
13.44
13.97
14.53
14.98
1.27
1.50
1.84
2.23
2.58
14.13
14.45
14.93
15.48
15.92
1.52
1.76
2.13
2.56
2.94
8.92
9.79
10.50
7.13
8.13
9.03
10.07
10.99
0.44
0.68
0.96
1.37
1.81
7.91
8.80
9.63
10.62
11.50
0.52
0.78
1.07
1.48
1.93
9.50
10.15
10.81
11.66
12.45
0.74
1.00
1.30
1.73
2.20
10.94
11.48
12.01
12.71
13.40
0.99
1.27
1.58
2.01
2.49
12.17
12.70
13.18
13.77
14.35
1.25
1.57
1.90
2.35
2.83
13.26
13.78
14.25
14.80
15.31
1.51
1.87
2.24
2.71
3.20
14.26
14.76
15.23
15.76
16.24
1.77
2.18
2.58
3.09
3.60
8.86
10.14
11.43
12.74
14.05
0.94
1.44
2.11
2.96
4.01
9.48
10.69
11.93
13.19
14.47
1.04
1.56
2.25
3.12
4.19
10.65
11.70
12.84
14.02
15.23
1.26
1.81
2.52
3.43
4.54
11.84
12.71
13.71
14.81
15.96
1.53
2.08
2.81
3.74
4.88
13.01
13.73
14.60
15.59
16.66
1.85
2.41
3.14
4.08
5.24
14.10
14.74
15.49
16.37
17.36
2.19
2.77
3.51
4.45
5.62
15.08
15.71
16.39
17.17
18.07
2.53
3.15
3.91
4.85
6.03
7.60
8.68
9.78
10.89
12.00
0.96
1.47
2.15
3.01
4.07
8.16
9.18
10.23
11.30
12.38
1.09
1.62
2.32
3.20
4.29
9.27
10.13
11.07
12.06
13.09
1.38
1.94
2.67
3.59
4.72
10.34
11.07
11.89
12.80
13.75
1.68
2.29
3.05
4.00
5.17
11.30
11.99
12.72
13.53
14.41
1.97
2.63
3.45
4.43
5.63
12.15
12.84
13.53
14.27
15.07
2.28
2.97
3.84
4.88
6.11
12.97
13.60
14.29
14.99
15.74
2.68
3.32
4.23
5.33
6.61
8.68
9.93
11.21
12.51
13.82
1.48
2.35
3.45
4.85
6.59
9.17
10.38
11.63
12.89
14.17
1.68
2.53
3.66
5.08
6.85
10.27
11.21
12.38
13.58
14.81
2.07
2.90
4.07
5.54
7.36
11.27
11.99
13.08
14.22
15.40
2.41
3.28
4.49
6.01
7.88
12.19
12.78
13.76
14.83
15.97
2.77
3.68
4.93
6.49
8.40
13.03
13.56
14.45
15.44
16.52
3.13
4.10
5.39
6.99
8.94
13.81
14.32
15.14
16.05
17.06
3.50
4.51
5.87
7.51
9.49
See Legend and Notes on page 45.
39
Table 11B — 40RM,RMQ Standard Fan Performance Data —
0-600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
UNIT
40RM,
RMQ
AIRFLOW
(L/s)
350
400
450
500
550
600
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
850
990
15.16
15.44
15.73
16.07
16.48
0.78
0.90
1.05
1.21
1.41
16.08
16.38
16.65
16.96
17.32
0.89
1.03
1.19
1.36
1.56
16.94
17.25
17.53
17.82
18.14
1.01
1.16
1.33
1.51
1.72
17.74
18.07
18.36
18.64
18.94
1.13
1.30
1.48
1.67
1.89
18.51
18.84
19.14
19.42
19.71
1.26
1.43
1.62
1.83
2.06
19.25
19.58
19.89
—
1.39
1.57
1.77
—
007
008
012
014
016
024
028
034
1130
1270
1420
—
—
1060
1230
1420
1600
1770
1420
1650
1890
2120
2360
1770
2030
2360
2690
2950
2120
2500
2830
3210
3540
2830
3300
3780
4250
4720
3540
4130
4720
5310
5900
4250
4960
5660
6370
7080
15.31
15.60
16.05
16.64
17.23
0.94
1.10
1.33
1.62
1.93
16.25
16.51
16.90
17.42
17.97
1.07
1.24
1.48
1.78
2.09
17.14
17.39
17.74
18.20
18.70
1.20
1.39
1.64
1.94
2.26
17.98
18.23
18.54
18.95
19.41
1.34
1.54
1.80
2.11
2.44
18.77
19.03
19.32
19.69
—
1.48
1.70
1.97
2.29
—
19.53
19.80
—
—
—
1.63
1.86
—
—
—
15.81
16.51
17.34
18.24
19.18
1.29
1.65
2.09
2.63
3.27
16.67
17.29
18.06
18.93
19.85
1.44
1.80
2.26
2.82
3.48
17.51
18.05
18.77
19.59
—
1.60
1.97
2.43
3.00
—
18.32
18.80
19.45
—
1.76
2.13
2.61
—
19.11
19.53
—
—
—
1.92
2.31
—
—
—
19.87
—
2.09
—
—
—
—
—
—
—
—
—
15.15
15.41
15.84
16.36
16.79
1.77
2.04
2.43
2.89
3.30
16.13
16.34
16.70
17.19
17.61
2.04
2.32
2.74
3.23
3.66
17.10
17.24
17.54
17.98
18.39
2.33
2.62
3.05
3.57
4.03
18.00
18.07
18.35
18.75
19.13
2.62
2.92
3.38
3.92
4.40
18.85
18.92
19.14
19.49
19.84
2.92
3.24
3.71
4.27
4.77
19.68
19.73
19.83
—
3.22
3.56
4.06
—
—
—
15.20
15.67
16.13
16.66
17.13
2.05
2.49
2.92
3.48
4.02
16.12
16.53
16.97
17.50
17.97
2.33
2.80
3.27
3.87
4.45
16.98
17.35
17.77
18.29
18.75
2.62
3.12
3.62
4.26
4.88
17.83
18.13
18.53
19.03
19.50
2.92
3.44
3.97
4.65
5.30
18.67
18.90
19.26
19.75
—
3.24
3.77
4.33
5.04
—
19.47
19.65
19.97
—
3.57
4.12
4.69
—
—
—
15.90
16.50
17.13
17.88
18.77
2.86
3.53
4.32
5.30
6.52
16.75
17.33
17.97
18.67
19.43
3.18
3.91
4.76
5.76
6.99
17.53
18.17
18.83
19.48
—
3.52
4.32
5.22
6.24
—
18.30
18.92
19.55
—
3.89
4.70
5.67
—
19.03
19.60
—
—
—
4.23
5.10
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
13.85
14.31
14.99
15.68
16.39
3.29
3.71
4.62
5.77
7.10
14.50
15.01
15.65
16.34
17.03
3.80
4.17
5.02
6.20
7.60
15.22
15.74
16.27
16.95
17.64
4.40
4.79
5.46
6.64
8.08
15.83
16.33
16.88
17.53
18.22
5.13
5.37
5.97
7.09
8.57
16.42
17.00
17.50
18.09
—
5.74
6.04
6.57
7.58
—
—
—
—
—
—
—
—
—
—
—
14.43
15.04
15.81
16.66
17.61
3.88
4.92
14.98
15.71
16.47
17.27
18.16
4.36
5.32
15.84
16.33
17.10
17.88
—
4.96
5.74
7.28
9.10
—
16.48
16.93
17.69
—
5.50
6.20
7.74
—
17.16
17.51
18.26
—
6.21
6.70
8.21
—
17.96
18.09
—
—
—
7.26
7.29
—
—
—
6.34
6.81
8.04
8.57
10.06
10.64
—
—
—
—
See Legend and Notes on page 45.
40
Table 11C — 40RM High-Capacity Fan Performance Data —
0.0-2.4 in. wg External Static Pressure — English
EXTERNAL STATIC PRESSURE (in. wg)
UNIT
40RM
AIRFLOW
(Cfm)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1,800
2,100
2,400
2,700
3,000
2,250
2,600
3,000
3,400
3,750
3,000
3,500
4,000
4,500
5,000
3,750
4,300
5,000
5,700
6,250
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
419
471
524
578
633
0.21
0.31
0.44
0.61
0.81
471
519
568
619
671
0.26
0.37
0.51
0.69
0.90
564
602
645
690
738
0.37
0.49
0.64
0.84
1.07
649
679
715
755
799
0.49
0.62
0.79
0.99
1.24
727
751
781
816
856
0.63
0.77
0.94
1.15
1.41
797
819
844
875
910
0.77
0.92
1.11
1.33
1.60
862
882
905
932
963
0.92
1.09
1.28
1.51
1.79
007
008
012
014
016
024
028
034
290
349
579
646
705
0.10
0.19
0.70
0.99
1.31
510
561
621
683
739
0.39
0.55
0.79
1.09
1.42
594
640
695
752
804
0.51
0.70
0.96
1.29
1.63
669
709
759
813
862
0.65
0.84
1.12
1.48
1.85
739
773
818
869
915
0.79
1.00
1.30
1.67
2.05
806
834
874
920
964
0.95
1.16
1.47
1.86
870
893
928
970
1.12
1.34
1.66
2.06
2.48
2.26 1011
421
626
706
786
867
0.35
0.98
1.42
1.99
2.70
592
664
738
815
893
0.73
1.08
1.54
2.12
2.84
670
735
803
873
946
0.90
1.28
1.77
2.39
3.14
737
798
862
929
997
1.06
1.48
2.00
2.65
797
855
917
980
1.23
1.67
2.23
2.90 1028
3.72 1092
854
908
967
1.41
1.87
2.45 1014
3.16 1073
4.00 1135
908
958
1.59
2.07
2.67
3.41
4.28
3.43 1046
410
455
514
575
624
0.43
0.62
0.92
1.32
1.71
467
504
556
612
657
0.55
0.74
1.06
1.47
1.87
567
599
641
686
725
0.83
1.05
1.39
1.82
2.24
649
679
718
759
793
1.12
1.38
1.76
2.23
2.66
721
748
786
825
856
1.41
1.70
2.14
2.66
3.12
788
811
847
884
915
1.72
2.04
2.52
3.09
3.59
851
871
903
939
969
2.05
2.39
2.91
3.52
4.06
437
499
555
620
677
0.61
0.95
1.34
1.91
2.52
483
538
590
651
706
0.72
1.07
1.48
2.06
2.69
576
617
659
712
761
1.01
1.37
1.79
2.39
3.04
660
696
730
774
817
1.35
1.74
2.17
2.78
3.44
732
767
798
836
873
1.69
2.13
2.59
3.22
3.89
797
830
860
896
929
2.03
2.53
3.04
3.71
4.39
856
888
918
952
984
2.38
2.94
3.49
4.21
4.93
542
620
700
781
862
1.29
1.99
2.92
4.10
5.56
577
652
728
806
885
1.42
2.15
3.10
4.30
5.79
646
711
781
854
929
1.72
2.48
3.46
4.71
6.24
716
771
833
900
971
2.09
2.85
3.85
5.13
785
831
885
946
2.51
3.28
4.29
5.58
849
890
938
993
2.95
3.76
4.78
6.08 1039
7.69 1096
907
947
990
3.40
4.27
5.32
6.62
8.24
6.70 1012
7.18 1054
476
545
615
685
756
1.39
2.14
3.12
4.37
5.92
510
574
641
709
778
1.58
2.35
3.36
4.64
6.22
579
633
692
754
819
1.99
2.81
3.87
5.20
6.83
644
691
743
800
860
2.40
3.29
4.41
5.79
7.47
701
747
794
845
901
2.81
3.77
4.96
6.40
8.14
752
797
843
891
942
3.29
4.25
5.51
7.02
8.83
804
842
888
935
983
3.96
4.76
6.05
7.64
9.52
9,000
10,500
12,000
13,500
15,000
539
620
701
783
865
2.18
3.37
4.94
6.95
9.45
569
646
724
804
884
2.39
3.62
5.22
7.27
9.81
626
695
769
844
921
2.85
4.13
5.80
7.91
683
744
811
883
956
3.34
4.68
6.40
8.57
739
793
854
920
3.83
5.25
7.04
9.26
791
842
897
958
4.32
5.83
7.69
9.97
837
888
940
4.82
6.41
8.36
996 10.71
10.52
11.24
991 11.98 1025 12.75 1059 13.54
See Legend and Notes on page 45.
41
Table 11C — 40RM High-Capacity Fan Performance Data —
0.0-2.4 in. wg External Static Pressure — English (cont)
EXTERNAL STATIC PRESSURE (in. wg)
UNIT
40RM
AIRFLOW
(Cfm)
1.4
1.6
1.8
2.0
2.2
2.4
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1,800
2,100
2,400
2,700
3,000
2,250
2,600
3,000
3,400
3,750
3,000
3,500
4,000
4,500
5,000
3,750
4,300
5,000
5,700
6,250
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
921
942
1.07
1.26
1.47
1.71
1.99
975
997
1017
1039
1065
1.23
1.43
1.66
1.91
2.20
1026
1048
1069
1090
1113
1.39
1.61
1.85
2.12
2.42
1074
1097
1118
1138
1161
1.55
1.79
2.05
2.33
2.65
1120
1143
1164
1185
—
1.72
1.97
2.25
2.55
—
1164
1186
—
1.90
2.16
—
007
008
012
014
016
024
028
034
963
987
1015
—
—
—
—
930
950
980
1018
1057
1.29
1.53
1.86
2.26
2.69
986
1005
1031
1065
1101
1.47
1.72
2.06
2.48
2.92
1039
1057
1081
1111
1144
1.65
1.92
2.27
2.70
3.15
1089
1107
1129
1156
1186
1.84
2.13
2.49
2.93
3.39
1136
1154
1175
—
2.03
2.33
2.72
—
1181
—
2.22
—
—
—
—
—
—
—
—
—
961
1005
1058
1116
1176
1.78
2.27
2.90
3.66
4.56
1012
1052
1101
1157
—
1.98
2.49
3.13
3.91
—
1062
1098
1143
1196
—
2.19
2.71
3.36
4.16
—
1111
1142
1184
—
2.41
2.94
3.60
—
1158
1186
—
—
—
2.64
3.18
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
912
928
2.39
2.75
3.30
3.96
4.54
971
982
1007
1039
1067
2.76
3.13
3.71
4.40
5.02
1028
1036
1056
1086
1112
3.14
3.53
4.13
4.85
5.50
1083
1087
1104
1130
1156
3.54
3.94
4.56
5.31
5.99
1135
1138
1151
1174
1198
3.95
4.37
5.00
5.78
6.49
1185
1187
1196
—
4.36
4.81
5.46
—
956
990
1019
—
—
912
942
971
1005
1036
2.75
3.34
3.95
4.72
5.48
967
992
1020
1054
1084
3.12
3.76
4.40
5.23
6.04
1019
1041
1067
1101
1131
3.52
4.18
4.86
5.75
6.61
1070
1088
1112
1145
1174
3.92
4.61
5.33
6.27
7.17
1120
1134
1156
1187
—
4.35
5.06
5.81
6.79
—
1168
1179
1198
—
4.79
5.52
6.29
—
—
—
961
1000
1041
1086
1138
3.86
4.79
5.88
7.21
8.83
1011
1050
1090
1133
1180
4.31
5.32
6.47
7.82
9.46
1058
1097
1137
1178
—
4.77
5.85
7.07
8.47
—
1104
1142
1181
—
5.24
6.38
7.67
—
1147
1184
—
—
—
5.71
6.91
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
874
886
5.33
5.36
897
930
969
1014
1061
5.91
6.13
940
982
1007
1051
1097
6.80
7.32
990
1020
1045
1086
—
7.50
8.10
8.71
10.17
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
930
6.60
7.20
7.89
976
8.25
8.86
9.49
1023
10.20
10.88
11.56
9,000
10,500
12,000
13,500
15,000
881
930
981
1035
1093
5.37
6.97
9.02
11.45
14.35
923
970
1021
1072
—
6.03
7.55
9.67
12.20
—
967
1008
1058
—
6.89
8.17
10.32
—
1020
1045
1094
—
8.25
8.86
10.97
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
See Legend and Notes on page 45.
42
Table 11D — 40RM High-Capacity Fan Performance Data —
0-600 kPa External Static Pressure — SI
EXTERNAL STATIC PRESSURE (kPa)
UNIT
40RM
AIRFLOW
(L/s)
0
50
100
150
200
250
300
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
850
990
6.98
7.84
0.16
0.23
0.33
0.45
0.61
7.86
8.64
0.19
0.27
0.38
0.51
0.67
9.40
10.03
10.75
11.51
12.30
0.27
0.36
0.48
0.62
0.80
10.81
11.31
11.91
12.58
13.31
0.37
0.46
0.59
0.74
0.92
12.11
12.52
13.01
13.60
14.26
0.47
0.57
0.70
0.86
1.05
13.29
13.65
14.07
14.58
15.17
0.57
0.69
0.83
0.99
1.19
14.36
14.71
15.08
15.53
16.05
0.69
0.81
0.96
1.13
1.33
007
008
012
014
016
024
028
034
1130
1270
1420
8.73
9.46
9.63
10.55
10.31
11.18
1060
1230
1420
1600
1770
1420
1650
1890
2120
2360
1770
2030
2360
2690
2950
2120
2500
2830
3210
3540
2830
3300
3780
4250
4720
3540
4130
4720
5310
5900
4250
4960
5660
6370
7080
4.83
5.81
9.65
10.76
11.74
0.07
0.14
0.52
0.74
0.97
8.50
9.35
10.35
11.39
12.32
0.29
0.41
0.59
0.81
1.06
9.91
10.67
11.59
12.54
13.40
0.38
0.52
0.71
0.96
1.22
11.15
11.81
12.66
13.55
14.37
0.48
0.63
0.84
1.10
1.38
12.32
12.88
13.64
14.48
15.25
0.59
0.74
0.97
1.24
1.53
13.44
13.90
14.57
15.34
16.07
0.71
0.87
1.10
1.39
1.69
14.50
14.89
15.47
16.17
16.86
0.83
1.00
1.24
1.53
1.85
7.02
10.44
11.76
13.10
14.45
0.26
0.73
1.06
1.48
2.01
9.86
11.06
12.31
13.59
14.89
0.54
0.80
1.15
1.58
2.12
11.17
12.25
13.38
14.55
15.76
0.67
0.96
1.32
1.78
2.34
12.28
13.31
14.37
15.48
16.62
0.79
1.10
1.49
1.97
2.56
13.29
14.25
15.28
16.34
17.43
0.92
1.25
1.66
2.17
2.77
14.23
15.13
16.11
17.14
18.20
1.05
1.39
1.83
2.35
2.98
15.14
15.96
16.89
17.89
18.92
1.19
1.54
1.99
2.54
3.19
6.84
7.58
0.32
0.46
0.69
0.99
1.28
7.78
8.40
9.27
10.20
10.96
0.41
0.55
0.79
1.10
1.39
9.46
9.98
10.68
11.44
12.09
0.62
0.78
1.04
1.36
1.67
10.82
11.31
11.96
12.64
13.21
0.83
1.03
1.31
1.66
1.98
12.02
12.47
13.09
13.74
14.27
1.05
1.27
1.60
1.98
2.33
13.13
13.52
14.11
14.74
15.25
1.28
1.52
1.88
2.30
2.68
14.19
14.51
15.05
15.65
16.15
1.53
1.78
2.17
2.63
3.03
8.57
9.59
10.40
7.28
8.32
9.25
10.33
11.29
0.45
0.71
1.00
1.42
1.88
8.05
8.97
9.83
10.85
11.77
0.54
0.80
1.10
1.54
2.01
9.60
10.29
10.99
11.87
12.69
0.75
1.02
1.33
1.78
2.27
11.00
11.59
12.16
12.90
13.62
1.00
1.30
1.62
2.07
2.56
12.21
12.78
13.29
13.93
14.56
1.26
1.59
1.93
2.40
2.90
13.28
13.84
14.34
14.93
15.49
1.51
1.89
2.27
2.76
3.27
14.27
14.80
15.30
15.87
16.40
1.78
2.19
2.60
3.14
3.67
9.03
10.34
11.67
13.01
14.36
0.96
1.48
2.17
3.05
4.15
9.62
10.86
12.14
13.44
14.75
1.06
1.60
2.31
3.21
4.32
10.77
11.85
13.02
14.23
15.48
1.29
1.85
2.58
3.51
4.66
11.94
12.84
13.88
15.00
16.18
1.56
2.12
2.87
3.82
4.99
13.08
13.85
14.75
15.77
16.87
1.87
2.45
3.20
4.16
5.35
14.15
14.84
15.63
16.54
17.56
2.20
2.80
3.56
4.53
5.73
15.12
15.78
16.50
17.32
18.26
2.54
3.18
3.96
4.94
6.14
7.94
9.08
10.24
11.42
12.60
1.04
1.59
2.33
3.26
4.42
8.51
9.57
10.68
11.81
12.96
1.18
1.75
2.51
3.46
4.64
9.65
10.55
11.53
12.57
13.65
1.48
2.10
2.88
3.88
5.09
10.73
11.52
12.39
13.33
14.33
1.79
2.46
3.29
4.32
5.57
11.68
12.45
13.24
14.09
15.01
2.10
2.81
3.70
4.77
6.07
12.53
13.28
14.05
14.85
15.70
2.46
3.17
4.11
5.24
6.58
13.40
14.04
14.80
15.58
16.38
2.95
3.55
4.51
5.70
7.10
8.99
10.33
11.68
13.04
14.42
1.62
2.51
3.68
5.18
7.05
9.49
10.77
12.07
13.40
14.74
1.78
2.70
3.90
5.42
7.31
10.44
11.59
12.81
14.07
15.36
2.12
3.08
4.33
5.90
7.84
11.39
12.40
13.52
14.71
15.94
2.49
3.49
4.77
6.39
8.38
12.32
13.22
14.23
15.34
16.51
2.86
3.92
5.25
6.90
8.93
13.18
14.03
14.95
15.97
17.08
3.22
4.35
5.74
7.44
9.51
13.95
14.79
15.66
16.61
3.59
4.78
6.23
7.98
17.65 10.10
See Legend and Notes on page 45.
43
Table 11D — 40RM High-Capacity Fan Performance Data —
0-600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
UNIT
40RM
AIRFLOW
(L/s)
350
400
450
500
550
600
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
850
850
15.34
15.69
16.04
16.44
16.91
0.80
0.94
1.09
1.27
1.49
16.25
16.61
16.95
17.32
17.75
0.92
1.07
1.23
1.42
1.64
17.10
17.47
17.81
18.17
18.56
1.03
1.20
1.38
1.58
1.81
17.90
18.28
18.63
18.97
19.34
1.16
1.33
1.53
1.74
1.97
18.66
19.04
19.40
19.75
—
1.28
1.47
1.67
1.90
—
19.39
19.77
—
1.41
1.61
—
007
008
012
014
016
024
028
034
1130
1270
1420
—
—
—
—
1060
1230
1420
1600
1770
1420
1650
1890
2120
2360
1770
2030
2360
2690
2950
2120
2500
2830
3210
3540
2830
3300
3780
4250
4720
3540
4130
4720
5310
5900
4250
4960
5660
6370
7080
15.50
15.84
16.34
16.97
17.61
0.96
1.14
1.38
1.69
2.01
16.43
16.75
17.19
17.76
18.35
1.10
1.28
1.54
1.85
2.18
17.31
17.62
18.01
18.52
19.07
1.23
1.43
1.70
2.02
2.35
18.14
18.45
18.81
19.27
19.77
1.37
1.58
1.86
2.19
2.53
18.93
19.24
19.59
—
1.51
1.74
2.03
—
19.68
—
1.66
—
—
—
—
—
—
—
—
—
16.02
16.76
17.64
18.60
19.61
1.33
1.70
2.16
2.73
3.40
16.87
17.53
18.35
19.28
—
1.48
1.85
2.33
2.91
—
17.71
18.29
19.05
19.93
—
1.64
2.02
2.51
3.10
—
18.52
19.04
19.74
—
1.80
2.19
2.69
—
19.30
19.77
—
—
—
1.97
2.37
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
15.21
15.46
15.94
16.51
16.99
1.78
2.05
2.46
2.95
3.39
16.19
16.37
16.78
17.32
17.78
2.06
2.33
2.77
3.28
3.74
17.13
17.26
17.60
18.09
18.54
2.34
2.63
3.08
3.62
4.10
18.04
18.12
18.40
18.84
19.26
2.64
2.94
3.40
3.96
4.47
18.91
18.96
19.18
19.57
19.96
2.94
3.26
3.73
4.31
4.84
19.75
19.78
19.94
—
3.25
3.59
4.07
—
—
—
15.21
15.69
16.18
16.75
17.26
2.05
2.49
2.94
3.52
4.09
16.11
16.54
17.01
17.57
18.07
2.33
2.80
3.28
3.90
4.50
16.98
17.35
17.79
18.34
18.84
2.62
3.12
3.63
4.29
4.93
17.83
18.14
18.54
19.08
19.57
2.93
3.44
3.97
4.67
5.35
18.66
18.90
19.27
19.78
—
3.24
3.77
4.33
5.06
—
19.47
19.64
19.97
—
3.57
4.11
4.69
—
—
—
16.01
16.67
17.35
18.11
18.96
2.88
3.57
4.39
5.37
6.58
16.85
17.50
18.17
18.88
19.67
3.22
3.96
4.82
5.83
7.05
17.64
18.28
18.95
19.63
—
3.56
4.36
5.27
6.31
—
18.39
19.03
19.68
—
3.91
4.75
5.72
—
19.12
19.73
—
—
—
4.26
5.15
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
14.57
14.76
15.49
16.26
17.04
3.97
3.99
4.92
6.15
7.61
14.95
15.51
16.15
16.91
17.68
4.41
4.57
5.37
6.61
8.11
15.67
16.36
16.78
17.51
18.28
5.07
5.46
5.88
7.08
8.62
16.50
17.00
17.42
18.10
—
5.59
6.04
6.50
7.58
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
14.68
15.51
16.35
17.24
18.22
4.00
5.20
15.38
16.17
17.01
17.87
—
4.49
5.63
7.21
9.10
—
16.12
16.80
17.64
—
5.14
6.09
7.69
—
17.00
17.41
18.23
—
6.15
6.61
8.18
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
6.72
8.54
10.70
—
—
—
—
See Legend and Notes on page 45.
44
Legend and Notes for Tables 11A and 11C
LEGEND
FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
UNIT
NOTES:
1,800
2,400
3,000
0.05
0.08
0.11
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
40RM
007
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
40RM
40RMQ
40RMS
008
2,250
3,000
3,750
0.07
0.11
0.15
3. Refer to fan motor and drive tables for additional data.
2,550
3,400
4,250
0.09
0.13
0.18
40RMS
010
40RM
40RMQ
40RMS
012
3,000
4,000
5,000
0.11
0.17
0.23
40RM
40RMS
014
3,750
5,000
6,250
0.06
0.10
0.13
40RM
40RMQ
40RMS
016
4,500
6,000
7,500
0.08
0.12
0.17
40RM
40RMQ
40RMS
024
6,000
8,000
10,000
0.12
0.19
0.26
40RM
40RMQ
40RMS
028
7,500
10,000
12,500
0.15
0.22
0.30
40RM
40RMS
034
9,000
12,000
15,000
0.19
0.29
0.40
Legend and Notes for Tables 11B and 11D
FACTORY-SUPPLIED PRESSURE DROP — SI
LEGEND
ESP — External Static Pressure
AIRFLOW
(L/s)
850
1150
1450
PRESSURE DROP
(Pa)
UNIT
NOTES:
1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and
034; 20 r/s for all other sizes.
2. Fan performance is based on deductions for wet coil, clean
51-mm filters, and unit casing. See table at right for factory-sup-
plied filter pressure drop.
13
20
28
40RM
007
40RM
40RMQ
40RMS
008
17
27
38
1000
1400
1800
3. Refer to fan motor and drive tables for additional data.
1200
1600
2000
21
32
45
40RMS
010
40RM
40RMQ
40RMS
012
1450
1900
2350
28
42
56
40RM
40RMS
014
1750
2350
2950
15
24
33
40RM
40RMQ
40RMS
016
2100
2800
3500
20
30
42
40RM
40RMQ
40RMS
024
2900
3800
4700
32
47
64
40RM
40RMQ
40RMS
028
3500
4700
5900
36
55
76
40RM
40RMS
034
4250
5650
7050
47
71
98
45
Copyright 2004 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-00003 Printed in U.S.A. Form 40RM-23SI Pg 46 12-04 Replaces: 40RM-22SI
Book 1
4
Tab 3c 2e
START-UP CHECKLIST
(SPLIT SYSTEMS WITH 40RM,RMQ,RMS UNITS)
I. PRELIMINARY INFORMATION
OUTDOOR: MODEL NO. _________________________
SERIAL NO. ___________________________________
INDOOR: MODEL NO. ___________________________
SERIAL NO. ___________________________________
ADDITIONAL ACCESSORIES ______________________________________________________________________________
II. PRE-START-UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? _______________
(Y/N) ____
IF SO, WHERE: _________________________________________________________________________________________
_______________________________________________________________________________________________________
WILL THIS DAMAGE PREVENT UNIT START-UP?
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?
HAS THE GROUND WIRE BEEN CONNECTED?
(Y/N) _____
(Y/N) _____
(Y/N) _____
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?
(Y/N) _______
(Y/N) _______
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED?
CONTROLS
(Y/N) _____
ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED?
(Y/N) _____
ARE ALL WIRING TERMINALS (including main power supply) TIGHT?
(Y/N) _____
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS?
INDOOR UNIT
(Y/N) ______
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?
(Y/N) _____
ARE PROPER AIR FILTERS IN PLACE?
(Y/N) ______
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?
(Y/N) ______
DO THE FAN BELTS HAVE PROPER TENSION?
(Y/N) ______
PIPING
40RM,RMQ
HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)?
(Y/N) ______
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (40RM) OR OUTDOOR UNIT (40RMQ)
COILS AS REQUIRED? (Y/N) _________________________________________________________________
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR?
(Y/N) _____
LOCATE, REPAIR, AND REPORT ANY LEAKS. _______________________________________________________________
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS?
40RMS
(Y/N) _____
(Y/N) _____
HAS AIR BEEN BLED FROM SYSTEM?
(Y/N) _____
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, AND INDOOR COILS?
(Y/N) ______
LOCATE, REPAIR, AND REPORT ANY LEAKS. ________________________________________________________________
CL-1
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB ________ V
AC ______ V
BC ______ V
(AB + AC + BC)/3 = AVERAGE VOLTAGE = ________ V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = ________ V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = ___________ %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START-UP
CHECK INDOOR FAN MOTOR SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
COMP A1
COMP B1
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
OUTDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
INDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
INDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
COMPRESSOR AMPS (L1/L2/L3)
____/____/____
____/____/____
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING
1
1
OIL LEVEL AT / to / FULL?
(Y/N) ______
8
3
NOTES:
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
Copyright 2004 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
Tab
1
4
PC 111
Catalog No. 534-00003
Printed in U.S.A.
Form 40RM-23SI
Pg CL-2
12-04
Replaces: 40RM-22SI
3c 2e
|