524J
PACKAGED AIR-HANDLING UNITS, 60 Hz
R
WITH PURON (R--410A) REFRIGERANT
SIZES: 16, 25, 28, 30
Electrical Data Supplement
NOTE: Read the entire instruction manual before starting the installation
th
This supplement only applies to 524J size 16, 25, 28 & 30 units when the 13 digit of the Model Number
is either a 1, 2, or 3 as shown in the Model Number Nomenclature diagram below. Check the Unit
th
Nameplate (see Figs. 1 & 2). If the digit in the 13 position is not either a 1, 2, or 3 discard this document.
MODEL NUMBER NOMENCLATURE
1
5
2
2
3
4
4
J
5
6
1
7
6
8
9
0
10 11 12 13 14 15 16 17
E
A
0
0
A
1
0
A
A
A
Model
Indoor Fan Options – Belt Drive
1 = Standard Motor/ Standard Drive
2 = Standard Motor / Medimum Drive
3 = High Motor / High Drive**
524J = Packaged Air-Handling Unit
Puron® R-410A Refirgerant
Voltage
T = 575-3-60l
J = 208/230-1-60
P = 208/230-3-60
E = 208/230/460-3-60*
Coil Options
A = Standard Aluminum Fin / Copper Tube
Factory Assigned
0 = Default
Cooling Tons
16 = 15 ton
25 = 20 ton
28 = 25 ton
30 = 30 ton
Factory Assigned
0 = Default
Factory Assigned
Type of Coil
A = Standard 4 Row DX Puron Coil
H = Heat Pump
0 = Default
* Size 16 units are triple voltage in the “E” configuration unless
the unit is equipped with the discrete 460-3-60 High Static motor option.
** Size 30 units - designate standard motor and high static drive.
C11002
MODEL
524JE16A000A10AAA
SERIAL
BRYANT
Test Pressure Gage
PSI ( kPa)
Compressors
(Factory Charged)
PH Hz RLA LRA
Refrigerant/System
Qty Volts AC
lbs
kg
R
—
1
2
Hi
Fan Motors
Qty Volts AC
PH Hz
FLA
HP
KW
Power
Max
Min
Supply Volts AC
PH Hz Volts Volts
MCA *
MOCP *
* MCA
=
Min Circuit Amps
(Fuse or HACR Bkr.)
* MOCP
=
Max Over Current Protective Device Amps
Test with External Static
in H 0
2
Part Number/Rev
99NA504644/2.0
Designed in U.S.A.
Assembled in Mexico
kPa
NOT Suitable for Outdoor Use
Charge System per Installation Instructions
Model Number
5 2 4 J E 1 6 A 0 0 0 A 1 0 AAA
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17
Position of Digit
C11004
Fig. 2 - Example of Nameplate with Model Number
Table 1 – Electrical Data, Standard Motors
FAN MOTOR
VOLTAGE
POWER SUPPLY
{
UNIT
V --- P H --- H z
Minimum
LIMITS
Hp (kW)
FLA
MOCP
Circuit Amps
208/230---3---60
4 6 0 --- 3 --- 6 0
187---253
414---506
518---632
187---253
414---506
518---632
187---253
414---506
518---632
187---253
414---506
518---632
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.6
4.6
13.3
6.0
20
15
524J*16A
524J*16H
5 7 5 --- 3 --- 6 0
3.8
4.8
15
208/230---3---60
4 6 0 --- 3 --- 6 0
14.6/12.8
6.4
18.3/16.0
8.0
30/25
15
524J*25A
524J*25H
5 7 5 --- 3 --- 6 0
5.1
6.4
15
208/230---3---60
4 6 0 --- 3 --- 6 0
21.4/19.4
9.7
26.9/24.3
12.1
45/40
20
524J*28A
524J*30A
5 7 5 --- 3 --- 6 0
7.8
9.8
15
208/230---3---60
4 6 0 --- 3 --- 6 0
28.2/26.8
13.4
35.3/33.5
16.8
60/60
30
5 7 5 --- 3 --- 6 0
10.3
12.9
20
NOTE: See page 5 for table legend and notes
3
Table 2 – Electrical Data, Alternate Motors
FAN MOTOR
VOLTAGE
POWER SUPPLY
{
UNIT
V --- P H --- H z
Minimum
LIMITS
Hp (kW)
FLA
MOCP
Circuit Amps
18.3/16.0
8.0
208/230---3---60
4 6 0 --- 3 --- 6 0
187---253
414---506
518---632
187---253
414---506
518---632
187---253
414---506
518---632
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
14.6/12.8
6.4
30/25
15
524J*16A
524J*16H
5 7 5 --- 3 --- 6 0
5.1
6.4
15
208/230---3---60
4 6 0 --- 3 --- 6 0
21.4/19.4
9.7
26.9/24.3
12.1
45/40
20
524J*25A
524J*25H
5 7 5 --- 3 --- 6 0
7.8
9.8
15
208/230---3---60
4 6 0 --- 3 --- 6 0
28.2/26.8
13.4
35.3/33.5
16.8
60/60
30
524J*28A
524J*30A
5 7 5 --- 3 --- 6 0
10.3
12.9
20
NOTE: See below for table legend and notes
Legend and Notes for Tables 1 and 2
LEGEND:
Example: Supply voltage is 230-3-60
F L A
--- Fu ll L o a d A m p s
max voltage deviation from average voltage
average voltage
MOCP --- Maximum Overcurrent Protection
% Voltage Imbalance = 100 x
{
Motors are designed for satisfactory operation within 10% of
normal voltage shown. Voltages should not exceed the limits
shown in the Voltage Limits column.
AB = 393 v
BC = 403 v
AC = 396 v
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calcu-
lated in accordance with The NEC. Article 440.
(393 + 403 + 396)
1192
3
Average Voltage =
=
=
2. Motor FLA values are established in accordance with Under-
writers’ Laboratories (UL). Standard 1995.
3
397
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the formula in the example
(see column to the right) to determine the percentage of volt-
age imbalance.
Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
4. Installation with Accessory Electric Heaters
Size the Field Power Wiring between the heater TB1 and the
40RU indoor fan motor per NEC Article 430---28 (1) or (2)
(depends on length of conduit between heater enclosure and
40RU power entry location). Install wires in field---installed
conduit.
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
6
% Voltage Imbalance
= 100 x
= 1.5%
397
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
Catalog No: SS524J---01
2011 Bryant Heating and Cooling Systems. D 7310 W. Morris St. D Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 01/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: New