Addressable Fire Alarm Control Panel
MS-9600LS/MS-9600LSE
MS-9600UDLS/MS-9600UDLSE
MS-9600LSC
Manual
Document 52646
2/12/2010
P/N 52646:B2
Rev:
B2
ECN 10-098
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software. Re-
acceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation.
©Tuesday, August 14, 2012 9:31 am by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
4
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Section 1: Product Description .............................................................................................13
1.6.1: Intelligent Addressable Detectors: Newer Series..............................................................................20
1.6.4: Addressable Device Accessories.......................................................................................................20
ANN-BUS Wiring................................................................................................................................23
ANN-I/O LED Driver Module*...........................................................................................................32
ANN-LED Annunciator Module*........................................................................................................34
1.8.7: Legacy ACS Annunciators................................................................................................................40
Section 2: Installation.............................................................................................................42
2.4: Notification Appliance Circuits...................................................................................................................47
2.6.1: DACT-UD2 Installation ...................................................................................................................52
2.6.2: 4XTMF Transmitter Module Installation..........................................................................................55
2.6.4: SLC-2LS Expander Module..............................................................................................................57
Legacy ACM-8RF Relay Control Module...........................................................................................59
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
3.2: User Programming.......................................................................................................................................62
3.5: Programming and Passwords.......................................................................................................................63
3.6.3: Zone Setup.........................................................................................................................................95
Disable..................................................................................................................................................96
Zones Available....................................................................................................................................99
Loop Selection......................................................................................................................................99
Time-Date...........................................................................................................................................103
Timers.................................................................................................................................................105
Canadian Option.................................................................................................................................113
3.6.6: Verify Loops....................................................................................................................................114
3.6.9: Option Modules ..............................................................................................................................117
3.6.11: Clear Program................................................................................................................................136
3.7.6: Zone Setup.......................................................................................................................................144
Zones Available..................................................................................................................................148
Zone Message.....................................................................................................................................149
6
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Section 4: Operating Instructions .......................................................................................150
4.6: Supervisory Operation...............................................................................................................................154
4.7: Process Monitor Operation........................................................................................................................155
4.9: Medical Alert Condition Operation...........................................................................................................156
4.11: Disable/Enable Operation........................................................................................................................156
4.12: Waterflow Circuits Operation..................................................................................................................156
4.15: NAC Operation........................................................................................................................................157
4.16: Synchronized NAC Operation.................................................................................................................157
4.17: Coded Operation......................................................................................................................................157
4.19: Positive Alarm Sequence.........................................................................................................................158
4.20.1: Silence Inhibit Timer.....................................................................................................................159
4.22.1: System Point..................................................................................................................................162
4.22.3: Power.............................................................................................................................................164
4.22.12: Central Station.............................................................................................................................169
Section 5: Power Supply Calculations................................................................................174
5.4.1: NFPA Battery Requirements...........................................................................................................177
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Appendix A: Software Zones............................................................................................... 178
A.1: Correlations...............................................................................................................................................178
Appendix B: Default Programming.....................................................................................186
C.1: Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts....................................193
C.2: MBT-1 Municipal Box Trip - Silenceable.................................................................................................194
Appendix D: FACP with Keltron.......................................................................................... 195
Appendix E: Wire Requirements......................................................................................... 196
Appendix F: HVAC Control.................................................................................................. 198
F.1: Control Module Operation.........................................................................................................................198
F.2.1: HVAC RESTART...........................................................................................................................198
F.2.2: HVAC OVRRIDE...........................................................................................................................199
Appendix G: Canadian Application.....................................................................................200
8
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•
•
•
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
ANSI/UL 864, Control Units and Accessories for Fire Alarm Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2017 General-Purpose Signaling Devices and System
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
CAN\ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
CAN\ULC - S561-03 Installation and Services for Fire Signal Receiving Centers and Systems
Note: MS-9600LSE/MS-9600UDLSE is not ULC listed for Canadian applications
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
FM Approved to ANSI/UL 864
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility
SLC Wiring Manual
Document #15384
Document #51309
Document #51480
Document #50759
Document #51073
Document #50888
Document #51315
Document #50055
Document #51338
Document #50362
Document #53037
Document #53109
Document #52749
Document #53032
Document #151416
Document #53033
Document #151417
Document #51889
ACS Series Annunciators
411UD Communicator/Transmitter
411UDAC Communicator/Transmitter
CHG-120F Battery Charger
CHG-75 Battery Charger
LDM Series Lamp Driver Modules
LCD-80F Remote Fire Annunciator
ACM-8RF Relay Control Module
DACT-UD2 Manual
IDACT Communicator/Transmitter
ANN-80 Installation Document
ANN-(R)LED Installation Document
ANN-I/O Installation Document
ANN-RLY Installation Document
ANN-S/PG Installation Document
ACC-25/50(ZS/T) Manual
This product has been certified to comply with the requirements in the ANSI/UL 864, Standard for Control
Units and Accessories for Fire Alarm Systems, 9th Edition. Operation of this product with products not tested
for ANSI/UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local
Authority Having Jurisdiction (AHJ).
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
9
Download from Www.Somanuals.com. All Manuals Search And Download.
10
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Peripheral Devices and Their Documents:
Audio Control for ACC-25/50(ZS/T) Audio-Command-Center Doc. #51889
ANN-(R)LED
LED Display
Doc. #53032
ANN-I/O
LED Driver
Doc. #151416
ANN-80
Text Annunciator
Doc. #52749
ANN-S/PG
Printer Driver
Doc. #151417
ANN-RLY
Form-C Relay Card
Doc. #53033
IPDACT
Internet Communicator
Doc. # 53109
ANN (EIA-485) TB6
DACT-UD2
Communicator
Doc. # 53037
J2 Connector
4XTMF
Reverse Polarity
module
J10, J11 Connectors
SLC Loop
Addressable Devices and SLC Wiring
Doc. # 51309
Battery Connector TB2
CHG-75 Charger
Doc. # 51315
CHG-120F Charger
Doc. # 50888
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
12
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1: Product Description
The MS-9600LS and MS-9600UDLS are compact, cost effective, intelligent addressable FACPs
(Fire Alarm Control Panels) with an extensive list of powerful features. The combination of
Fire•Lite’s newer series devices and legacy 300 Series devices, along with the MS-9600LS or MS-
9600UDLS FACP, offer the latest in fire protection technology. The FLPS-7 power supply is a sep-
arate board while all other electronics are contained on a single main circuit board. Both boards are
mounted to a chassis and housed in a metal cabinet, providing a complete fire control system for
most applications. Optional modules, which plug into the main circuit board, are available for spe-
cial functions. Available accessories include LED, graphic and LCD annunciators, reverse polar-
ity/city box transmitter, digital alarm communicator/transmitter, SLC expansion module, local and
remote upload/download software and remote power expansion.
The MS-9600UDLS includes a factory installed DACT-UD2 Digital Alarm Communicator Trans-
#53037, which is supplied with the FACP, for DACT wiring and programming information. The
DACT transmits system status (alarm, troubles, AC loss, etc.) to a Central Station via the public
switched telephone network. It also allows remote programming or interrogation of the control
panel using the PS-Tools Upload/Download utility via the public switched telephone network.
Local programming and interrogation is also possible for the MS-9600UDLS using the PS-Tools
and the USB port J4 on the DACT-UD2. The MS-9600LS can be programmed and interrogated
locally using the serial port at TB7. Any personal computer with Windows® XP or greater and
compatible modem with a speed of 2400 baud or faster and PS-Tools software may serve as a Ser-
vice Terminal. This allows download of the entire program or upload of the entire program, history
file, walktest data, current status and system voltages.
The MS-9600LSC is a ULC approved Canadian version of the FACP which offers the same fea-
Option” on page 113 for a full description.
The MS-9600LSE and MS-9600UDLSE offer the same features as the MS-9600LS and MS-
9600UDLS but allow connection to 220/240 VAC input.
NOTE: Unless otherwise specified, the terms FACP, MS-9600LS and MS-9600UDLS are used
in this manual to refer to all versions of the FACPs.
1.1 Inventory
When the FACP shipment is received, check to make certain that all parts have been included in the
shipment. The FACP shipment should consist of one of each of the following:
•
•
•
•
•
•
main circuit board with display
FLPS-7 Power Supply
chassis (with main circuit board and power supply mounted)
backbox with door and dress panel
plastic bag containing screws, cables, key, etc.
manual
1.2 Features and Options
•
New LiteSpeed™ polling protocol for faster SLC response time
•
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire or
3,000 ft (900 m) with untwisted, unshielded wire
•
Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Features and Options
Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7
•
•
requirements
318 addressable device capacity for each SLC loop (159 detectors and 159 control/monitor
modules)
•
•
99 software zones
Up to four onboard NACs (Notification Appliance Circuits):
four Style Y (Class B) or two Style Z (Class A)
•
•
•
•
•
•
•
•
Additional NAC capability using control modules
7.0 amps total power for NACs and 24 VDC auxiliary power outputs in alarm
Two programmable relay outputs and one fixed trouble relay
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
• Automatic drift compensation
• Maintenance alert
• Detector sensitivity test capability (NFPA 72 compliant)
• Automatic device type-code verification
• Point trouble identification
•
•
•
•
•
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
New ANN-BUS Annunciators/Modules (ACS annunciators cannot be used when ANN-BUS
annunciators/modules are connected)
• ANN-80 Remote Liquid Crystal Display point annunciator
• ANN-I/O LED Driver Module
• ANN-LED Alarm, Trouble, Supervisory Annunciator (minimum of one required for
Canadian applications)
• ANN-RLED Alarm Annunciator
• ANN-S/PG Serial/Parallel Printer Module
• ANN-RLY Form-C Relay Module
• Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center
•
Legacy ACS/Term Annunciators: (ANN-BUS annunciator/modules cannot be used when
ACS/Term annunciators are connected)
• ACM Series-LED Zone Annunciators
• LDM Graphic Annunciator Series
• LCD-80F Liquid Crystal Display point annunciator (LCD-80FC for Canadian applications)
• ACM-8RF Relay Module
•
•
•
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two-
stage capability
•
•
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, legacy ACS
annunciators or ANN-80 Remote annunciator
14
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Product Description
•
Auto-program (learn mode) reduces installation time. Reports two devices set to the same
address
•
•
•
•
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or keyboard or local PC
Compatible with Fire•Lite’s newer series addressable devices (LiteSpeed and CLIP Mode) -
Refer to SLC Wiring Manual for listing of all compatible addressable devices
•
Compatible with legacy Fire•Lite’s 300 Series devices (CLIP Mode only) - Refer to SLC
Wiring Manual for listing of all compatible addressable devices
•
•
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Optional DACT-UD2 Digital Alarm Communicator Transmitter, reports up to 99 zones or 636
points (all devices) to a UL listed Central Station. The DACT-UD2 is supplied standard with
the MS-9600UDLS/E
•
•
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of program
and data.
Optional DP-9692 dress panel (required for Canadian applications)
1.3 Specifications
AC Power - TB1 of Power Supply Board
MS-9600LS(C) & MS-9600UDLS: 120 VAC, 50/60 Hz, 3.0 amps (L1=Hot, L2=Neutral)
MS-9600LSE & MS-9600UDLSE: 240 VAC, 50 Hz, 1.5 amps (L1=Hot Leg 1, L2=Hot Leg 2)
Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation
Battery (Sealed Lead Acid Only) - TB2
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp
Maximum Battery Size: 26 Amp Hour
Minimum Battery Size: 12 Amp Hour
(FACP cabinet holds maximum of two 18 Amp Hour batteries. For greater than 18 Amp Hour up
to 26 Amp Hour batteries, use BB26 Battery Box)
For greater than 26 Amp Hour up to 75 Amp Hour batteries, use the CHG-75 Battery Charger and
BB26 or BB-55F Battery Box. For greater than 75 Amp Hour up to 120 Amp Hour batteries, use
the CHG-120F Battery Charger and BB-55F Battery Box.
Jumper JP3, on the FACP main circuit board, must be removed to disable the FACP battery char-
ger when using the CHG-75 or CHG-120F.
Communication Loop - (Standard ) TB8 and (Optional SLC Expander Module) J3
24 VDC nominal, 27.6 VDC maximum
Maximum length - refer to “Wire Requirements” on page 196
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited
Refer to SLC Wiring Manual for wiring information
NOTE: When installing SLC wiring in conduit, each loop must be installed in separate conduit.
Notification Appliance Circuits - TB4
Special Application power
Power-limited circuitry, supervised
NAC wiring requirements, refer to “NAC Wiring” on page 197
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Specifications
Maximum signaling current per circuit: 3.00 amps (see Figure 1.1 on page 17)
End-of-Line Resistor: 4.7 k, ½ watt (P/N 71252 UL listed) for NACs
Refer to Device Compatibility Document for listed compatible devices
Two Programmable and One Fixed Output Relay - TB1 & TB5
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Four-Wire Resettable Special Application Smoke Detector Power (24 VDC nominal) -
TB3, Terminals 1 (+) & 2 (-)
Maximum ripple voltage: 10 mVRMS
Power-limited circuit, nonsupervised
Refer to Device Compatibility Document for listed compatible devices
Nonresettable Special Application Power #1 (24 VDC Nominal) -
TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10mVRMS
Total DC current available from each output is up to 1.5 amps (see Figure 1.1)
Power-limited circuit, nonsupervised
Nonresettable Special Application Power #2 (24 VDC Nominal) -
TB3, Terminals 5 (+) & 6 (-)
Maximum ripple voltage: 10mVRMS
Total DC current available from each output is up to 1.5 amps (see Figure 1.1)
Power-limited circuit, nonsupervised
EIA-485 (ACS/ANN-BUS) - TB6
ACS/ANN annunciator connector, Terminal 1 (+) and Terminal 2 (-)
EIA-485 (TERM) - TB7
Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -)
Supervised, power-limited.
EIA-232 Serial - TB7
Local serial PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground)
Non-supervised, power-limited.
16
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
Product Description
1.3.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit and the
total current available from the FACP power supply.
TB3
Resettable Special
Application Power
1
1.5 amps max
per circuit
for 4-wire smoke detectors
2
3
4
5
6
Standby
1.5 Amps Max*
per panel
Resettable Special
Application Power
Power #1
1.5 amps max
per circuit
Resettable Special
Application Power
Power #2
1.5 amps max
per circuit
Alarm
7 Amps Max
per panel
1
NAC 1
Style Y or Z
3 amps max
per circuit
2
3
4
5
6
7
8
NAC 3
Style Y only
3 amps max
per circuit
NAC 2
Style Y or Z
3 amps max
per circuit
NAC 4
Style Y only
3 amps max
per circuit
TB4
*The combined output current of all Special Applications Power circuits cannot exceed 1.5 amps in standby. Each
circuit is capable of delivering the full 1.5 amps individually.
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability
1.4 Controls and Indicators
LCD Display
HONEYWELL
LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 020102
The FACP uses an 80-character (4 lines X 20
characters) high viewing angle LCD display.
The display includes a long life LED backlight
that remains illuminated. If AC power is lost and
the system is not in alarm, the LED backlight will
turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
•
•
•
•
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Circuits
•
•
•
•
•
Maintenance/presignal (yellow)
Alarm Silenced signals (yellow)
Disabled (yellow)
Battery fault (yellow)
Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
•
•
•
•
Acknowledge/Step
Alarm Silence
Drill
Reset (lamp test)
Service/program keys:
•
•
•
•
•
•
•
•
•
•
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Figure 1.2 Membrane/Display Panel
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi-
tions.
1.5 Circuits
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. A second SLC loop is avail-
able by plugging the optional SLC module into connector J3 on the main circuit board. SLC loops,
configurable for NFPA Style 4, 6 or 7, provide communication to addressable detectors, monitor
(initiating device) and control (output device) modules. Refer to the SLC Wiring Manual for infor-
mation on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
•
•
Special Application Power
• 24 VDC Resettable (smoke detector power) output - 1.5 amps maximum
• 24 VDC Nonresettable power output #1 - 1.5 amps maximum
• 24 VDC Nonresettable power output #2 - 1.5 amps maximum
24 VDC Battery Charger (up to 26 AH batteries)
18
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Components
Product Description
NAC (Notification Appliance Circuits)
Up to four NACs are provided with various programmable features:
•
four Style Y (Class B) NACs
OR
•
two Style Z (Class A) NACs
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe
relay monitors system trouble and the two programmable relays are factory default programmed for
system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5
amps @ 30 VAC (resistive). The programmable relays can be programmed for the following oper-
ations:
•
•
•
•
•
•
•
•
•
•
fire alarm
trouble
supervisory
supervisory auto-resettable
DACT communication failure
process monitor
process monitor auto-resettable
hazard alert
medical alert
AC loss
Auxiliary Trouble Inputs
Auxiliary Trouble Inputs can be connected to trouble bus outputs from auxiliary equipment, such as
power supplies or normally-open dry contacts of a trouble relay to allow monitoring by the FACP.
1.6 Components
Main Circuit Board
The main circuit board contains the system’s CPU and other primary components and wiring inter-
face connectors. Optional modules plug in and are mounted to the main circuit board. The circuit
board is delivered mounted to a chassis which must be mounted to the backbox. Refer to the circuit
board illustration on Page 10.
FLPS-7 Power Supply
The FLPS-7 Power Supply is provided as a separate module which is delivered mounted to a chas-
sis which must be mounted to the backbox and connected to the main circuit board.
Cabinet
The FACP cabinet is red with a navy blue front overlay.
The backbox provides space for two batteries (up to 18 Amp Hour).
Ample knockouts are provided for system wiring. Also available is an
optional dress panel DP-9692, which mounts to the inside of the cabinet
(required by ULC for Canadian applications).
Batteries
Batteries must be sealed lead acid type. The FACP cabinet provides space for two batteries (up to
18 Amp Hour). Batteries larger than 18 Amp Hour up to 26 Amp Hour require use of the BB-26 or
similar UL listed battery cabinet. The CHG-75 can be used for charging 26 to 75 AH batteries and
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Components
the BB-26 can be used for housing the batteries. The CHG-120F can be used for charging 26 to 120
AH batteries and the BB-55F can be used for housing the batteries. Batteries must be ordered sep-
arately.
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling
Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wir-
ing and operation). This allows the control panel to continually process the information to deter-
mine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to
an SLC address that is set in the detector head using built-in rotary decimal switches with the abil-
ity to select up to 159 addresses. Note that a blinking LED on an intelligent detector indicates com-
munication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or
LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series
devices. If a mix of old and new series devices are installed on the same loop, that loop must be
programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a complete list of com-
patible addressable detectors.
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface between the con-
trol panel and conventional notification and initiating devices. Each module can be set to respond
to an address with built-in rotary switches with the ability to select up to 159 addresses (a tab on the
address switch must be broken off to use addresses 100-159). A blinking LED on a monitor mod-
ule indicates communication between the module and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or
LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series
devices. If a mix of old and new series devices are installed on the same loop, the loop must be pro-
grammed to operate in CLIP mode. Refer to the SLC Wiring Manual for a complete list of compat-
ible addressable modules. Refer to the Device Compatibility Document for a list of approved
notification and initiating devices.
1.6.3 300 Series Intelligent Addressable Devices
Fire•Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9600LS
FACP. The FACP must be configured for CLIP Mode operation if the control panel is installed in
an existing system with 300 Series devices. The address of 300 Series devices cannot be set above
99. Refer to the SLC Wiring Manual for a complete list of compatible addressable devices.
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly P/N R-47K
The 47 K End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the MMF-300,
MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 K End-of-Line Resistor assembly
is used to supervise the MMF-302 module circuit. The resistors are included with each module.
Power Supervision Relay
The UL listed End-of-Line power supervision relay (P/N: EOLR-1) is used to supervise the power
to 4-wire smoke detectors and notification appliances.
20
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules
Product Description
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An ELR,
which is supplied with each module and fire alarm control panel, is mounted to the ELR plate.
Resistors mounted to the N-ELR plate can be used for the supervision of a monitor and control
module circuit.
1.7 Optional Modules
The FACP main circuit board includes option module connectors for the following modules:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the
module is used to select an option which allows the reverse polarity circuit to open with a system
trouble condition if no alarm condition exists. The module plugs into connectors J10 and J11
which are located near the top left of the main circuit board. When the 4XTMF module is installed,
Jumper JP6, on the main circuit board, must be cut to allow supervision of the module.
SLC-2LS Expander Module
The SLC-2LS Expander Module allows expansion of the FACP from one SLC circuit to two SLC
circuits. The module plugs into connector J3 which is located in the lower right corner of the main
circuit board. The wiring for the second SLC connects to terminals located on the expander mod-
ule.
DACT-UD2 Digital Alarm Communicator/Transmitter
The DACT-UD2 is used to transmit system status to UL-listed Central Station receivers via the
public switched telephone network. All circuitry and connectors are contained on a compact mod-
ule which plugs into connector J2, which is located near the bottom center of the main circuit
board.
DACT-UD2 wiring and programming information.
IPDACT - Internet Protocol DACT
The IPDACT is a compact, Internet Protocol Digital Alarm Communicator/Transmitter designed to
allow FACP status communication to a Central Station via the internet. No telephone lines are
required when using the IPDACT. Using Contact ID protocol from the FACP, the IPDACT con-
verts the standard DACT phone communication to a protocol that can be transmitted and received
via the internet. It also checks connectivity between the FACP and Central Station. Refer to the
IPDACT Product Installation Document P/N 53109 for additional information.
1.8 Accessories
1.8.1 PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly
from most IBM compatible computers (PC), running Windows™ XP or newer. FACP program
files can also be created and stored on the PC and then downloaded later to the control panel. The
P/N: PK-CD Kit includes the FACP Windows-based Programming Utility software on CD-ROM
with on-line help file. A standard USB cable with male-A to male-B connectors, which must be
purchased separately, is required by the MS-9600UDLS for local connection of the PC to the USB
port J4 on the DACT-UD2. The MS-9600LS requires connection to the Serial Port on FACP con-
nector TB7. Remote programming requires that the PC have a 2400 baud or faster modem.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Accessories
Important: Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to the DACT-UD2 manual). Remote interrogation of panel programming,
history logs, detector status, etc., is possible without enabling the remote download option.
1.8.2 Dress Panel: DP-9692
A DP-9692 dress panel is available for the FACP (required for Canadian installations). The dress
panel restricts access to the system wiring while allowing access to the key panel.
The MS-9600LSC has received ULC approval. ULC approval is contingent on the proper installa-
tion of the dress panel which is provided with the FACP
1.8.3 TR-CE Trim Ring
An optional TR-CE trim ring is available for semi-flush mounting the FACP backbox.
1.8.4 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery
Charger. The battery box is red and is provided with knockouts.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one
100 AH battery. When the CHG-120 is mounted in the BB-55F, two 26 AH or one 60 AH battery
may also be housed in the battery box.
1.8.5 Battery Charger
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS-9600LS FACP.
The FACP battery charger must be disabled when using the CHG-75. The charger and up to 26 AH
batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in
the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to
the CHG-75 Manual for additional information.
CHG-120 Battery Charger
The CHG-120 is capable of charging up to 120 AH lead-acid batteries with the FACP. The FACP
battery charger must be disabled when using the CHG-120. The batteries and charger can be
housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel.
Note that when using the BB-55F for housing the charger and batteries greater than 26AH, multiple
BB-55Fs are required. Refer to the CHG-120 Manual for additional information.
22
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
1.8.6 New ANN-BUS Annunciators/Devices
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
!
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due
to incompatible serial communication protocols.
A variety of optional devices can be connected to the FACP EIA-485 ANN-BUS communication
circuit. Compatible devices include:
•
•
•
•
•
•
ANN-80 LCD Annunciator
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)
ANN-RLED Annunciator Module (red alarm LEDs only)
ANN-RLY Relay Module
ANN-BUS Wiring
This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).
Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the maximum
wiring distance that can be used with FACP ANN-BUS accessory modules.
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is nec-
essary to calculate the total worst case current draw for all modules on a single 4-conductor bus.
The total worst case current draw is calculated by adding the individual worst case currents for each
module. The individual worst case values are shown in the following table:
Worst Case Current Draw1
Model Number
ANN-80 LCD Annunciator
0.040 amps
0.040 amps
0.200 amps
0.068 amps
0.075 amps
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-(R)LED Annunciator Module
ANN-RLY Relay Module
1 Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp. If
current draw exceeds 0.5 amps, refer to “Powering ANN-BUS Devices from
Auxiliary Power Supply” on page 26.
After calculating the total worst case current draw, Table 1.1 specifies the maximum distance the
modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line
drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges,
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Accessories
capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maxi-
mum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. The formula
used to generate this chart is shown in the note below.
Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case Current
22 Gauge
18 Gauge
16 Gauge
14 Gauge
Draw (amps)
0.100
1,852 ft.
926 ft.
617 ft.
463 ft.
370 ft.
4,688 ft.
2,344 ft.
1,563 ft.
1,172 ft.
938 ft.
* 6,000 ft.
3,731 ft.
2,488 ft.
1,866 ft.
1,493 ft.
*6,000 ft.
5,906 ft.
3,937 ft.
2,953 ft.
2,362 ft.
0.200
0.300
0.400
0.500
Table 1.1 Wiring Distances
The following formulas were used to generate the wire distance chart:
6.0 volts
Maximum Resistance (Ohms)
=
=
Total Worst Case Current Draw (amps)
Maximum Wire Length (feet)
(6,000 feet maximum)
Maximum Resistance (Ohms)
Rpu
*500
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire Gauge
Ohms per 1,000 feet (Rpu)
22
18
16
14
16.2
6.4
4.02
2.54
Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:
Wire Gauge
Maximum Wire Length
312 feet
18
16
14
12
497 feet
787 feet
1,250 feet
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
•
•
•
3 ANN-80 Remote Fire Annunciators
1 ANN-S/PG Serial/Parallel Printer Interface Module
1 ANN-I/O LED Driver Module
24
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
The total worst case current is calculated as follows:
ANN-80 Current Draw
= 3 X 0.040 amps
= 1 X.0.040 amps
= 1 X.0.200 amps
= 0.120 amps
= 0.040 amps
= 0.200 amps
= 0.360 amp
ANN-S/PG Current Draw
ANN-I/O Current Draw
Total Worst Case Current Draw
Using this value and referring to the Wiring Distance Table 1.1 on page 24, it can be found that the
available options are:
•
•
•
•
463 feet maximum using 22 Gauge wire
1,172 feet maximum using 18 Gauge wire
1,866 feet maximum using 16 Gauge wire
2,953 feet maximum using 14 Gauge wire
Wiring Configuration
Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices.
ANN-BUS and power wiring are
supervised and power-limited
B
4
A
(+) (-)
TB1
3
2
1
ANN-BUS/
ACS BUS
ANN-BUS Device
24 VDC
nonresettable
TB1
TB5
A B
TB6 + -
TB3 + - + - + -
TB4
JP8
JP5
FACP
Figure 1.3 FACP wiring to ANN-BUS Device
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Powering ANN-BUS Devices from Auxiliary Power Supply
Accessories
Figure 1.4 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as
the FCPS-24FS6/8, when the total ANN-BUS power requirement exceeds the capability of the
FACP’s DC Power Output circuit.
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
ANN-BUS and power wiring are
supervised and power-limited
-24 VDC
ANN-80
ANN-BUS
+24 VDC
nonresettable
ANN-BUS/
ACS BUS
FCPS-24FS6/8
FACP
Figure 1.4 Powering ANN-BUS Devices from FCPS-24FS6/8
ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
NOTE: Address (ID Number) DIP switches on some devices may have more than 5 switch
positions. Unless otherwise specified in the documentation supplied with each device, switch
positions 6 and above must be set to OFF.
26
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
Switch 51
OFF
Address
Switch 4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Switch 3
OFF
OFF
OFF
OFF
ON
Switch 2
OFF
OFF
ON
Switch 1
not valid
01
OFF
ON
OFF
02
OFF
OFF
ON
03
OFF
ON
04
OFF
OFF
OFF
ON
OFF
ON
05
OFF
ON
06
OFF
ON
OFF
ON
07
OFF
ON
ON
08
OFF
OFF
OFF
OFF
1 Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
ANN-80 Remote Fire Annunciator
The ANN-80(-W) Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It
mimics the display on the control panel and will annunciate device type, point alarm, trouble or
supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP.
The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervi-
sory and Alarm Silenced conditions. Additionally, the annunciator is capable of remotely perform-
ing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication
between the ANN-80 and FACP is accomplished over a two wire RS-485 serial interface employ-
ing the ANN-BUS communication format. The devices are powered, via two additional wires,
from either the host FACP or remote UL-listed, filtered, power supply.
The function buttons, keyswitch and piezo sounder may be individually enabled and disabled
feature and programming information.
Note that if the keyswitch is enabled and remains in the unlocked position for more than two min-
utes without any buttons being pressed on the annunciator, a trouble indication will be annunciated.
Specifications
•
•
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
• Normal/Standby (no activity): 37.0 mA
• Trouble: 39.0 mA
• Alarm: 40.0 mA
• AC Fail ( not backlit): 15.0 mA
•
For use indoors in a dry location
Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the annunci-
ator.
Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the termi-
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise.
2. Push in the snap latch located on the right side of the unit while pulling the cover open.
3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut.
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Accessories
Annunciator backplate
Annunciator cover
with LCD display
Press in latch
and
Pull annunciator
cover open
Key switch shown in OFF/Locked position
Figure 1.5 ANN-80
Mounting
TheANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical box.
Select and remove the appropriate knockout(s), pull the necessary wires through the knockouts and
mount the annunciator in or on the wall depending on the type of installation desired.
The ANN-SB80KIT(-R/-B/-W) is an available mounting kit for the ANN-80 annunciator. The kit
comes with a surface backbox and surface wedge for angled viewing. The two pieces can be used
separately or can be stacked together.
The ANN-80 cover must be attached to the annunciator backplate before mounting the annunciator
to the electrical box/wall. The cover cannot be reattached or removed after the annunciator has
been mounted.
Annunciator mounted on
surface wedge from the
ANN-SB80KIT
Annunciator mounted on
surface backbox from the
ANN-SB80KIT
Annunciator mounted on stacked
surface wedge and backbox from
the ANN-SB80KIT
28
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator. Make certain all power has
been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal
block TB1.
wiring channel
wires
TB1
2. Remove appropriate amount of wire insulation.
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B.
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals
3 & 4. Make certain to connect A to A and B to B.
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+).
Make certain to observe proper polarity.
6. If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity.
7. After all connections are made, remove extra wire from inside of annunciator by dressing it
neatly through wire channel, with any excess wire pushed back through hole into electrical
box.
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS
B
4
A
(+) (-)
TB1
24 VDC
nonresettable
3
2
1
ANN-BUS/
ACS BUS
ANN-80
TB1
TB5
A B
TB6 + -
TB3 + - + - + -
TB4
JP8
JP5
FACP
Figure 1.6 ANN-80 Wiring to FACP
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
The following table shows the ANN-80 connections to the FACP
Accessories
FACP
ANN-80 (TB1)
Terminal GND (-) on TB3
Terminal PWR (+)TB3
Terminal ACS on TB6
Terminal ACS on TB6
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
option for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus
Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of an ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address correspond-
ing to the address set on the ANN-80 at the FACP.
If the Keyswitch on the ANN-80 is left in the unlocked position for more than 2 minutes, a trouble
condition will be indicated at the FACP.
ANN-S/PG Serial/Parallel Interface Installation
The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel
printer to the FACP for a real-time log of system events, detector status reports and event history.
The module is provided with a plastic enclosure for surface mounting. Proceed with the installation
as described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 1.7.
Parallel
ANN-BUS and power wiring are
supervised and power-limited
(-)
Cable Connectors for
connection to printer
(+)
A
B
Serial
ANN-S/PG Module
ANN-BUS/
24 VDC
ACS BUS
nonresettable
TB1
TB5
+ - + - + -
+ -
A B
TB3
TB4
JP8
TB6
FACP
JP5
Figure 1.7 ANN-S/PG Connection to FACP
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)
to the module.
30
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
4. Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to “ANN-BUS Options” on page 121).
Note that the Auto-configure feature allows the programmer to quickly bring all installed
5. Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 1.7). Only
one printer can be connected.
Specifications
•
•
•
•
•
•
•
Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32oF to 120oF (0oC to 49oC)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
PRN 6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the event
occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section con-
tains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm system configu-
ration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power
source (battery backup). Since a secondary power source is not provided as a standard feature, a
separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency
power supply may be used, as long as it meets the power continuity requirements of NFPA 72.
Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable.
One end of the cable will plug into the DB-25 connector on the PRN printer and the other end plugs
into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9 port on the ANN-
S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer
cable. Connect either a serial or parallel printer, but not both at the same time.
Setting Printer Options
Refer to the documentation supplied with the PRN-6F printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
Option
Setting
HS Draft
Option
Setting
Font
LPI
CPI
10CPI
0.5
6 LPI
Skip
ESC Character
Bidirectional Copy
CG-TAB
ESC
Emulate
I/O
Epson FX-850
ON
Graphic
E-US ASCII
OFF
Buffer
Serial
Baud
40K
Country
Auto CR
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Color Option
Formien
Not Installed
Format
Protocol
Lines
6LPI=60
Character Set
Standard
Table 1.2 PRN-6F Setup Options
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Accessories
Standard
Exec 10.5
SI.Zero
Auto LF
PAPER
BIN 1
On
On
12/72”
12/72”
12/72”
12/72”
12/72”
12/72”
BIN 2
SINGLE
PUSH TRA
PULL TRA
PAP ROLL
Table 1.2 PRN-6F Setup Options
ANN-I/O LED Driver Module*
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs
The module is provided with a plastic enclosure for mounting inside the annunciator or accessory
Options” on page 121 for programming information.
*In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervi-
sory, burglary or trouble signals. Green indicates the presence of power or an activated output.
ANN-I/O Board Layout
Figure 1.8 illustrates the ANN-I/O board showing locations of screw terminals for connection to
the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID
number.
Terminals not used (future)
ANN-BUS (ID#)
Address DIP
switch
ANN-BUS Connector
Figure 1.8 ANN-I/O Board Layout
32
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
Specifications
•
•
Max. ANN-BUS Voltage: 28 VDC
Max. Current:
• Alarm: 200 mA
• Standby: 35 mA
• Each LED: 10 mA
•
•
Operating Temperature: 32oF to 120oF (0oC to 49oC)
For indoor use in a dry location only
ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 1.9. After the
ANN-I/O is connected to the panel, it must be added to the system via FACP programming. Refer
to the section titled “ANN-I/O Options” on page 123.
P1
P2
P3
P4
21
30
11
31
40
1
10
20
ANN-I/O Module
24 VDC
nonresettable
ANN-BUS/
ACS BUS
ANN-BUS and power wiring are
supervised and power-limited
TB1
+ -
TB3 + - + - + -
A B
TB5
TB4
JP8
TB6
JP5
FACP
Figure 1.9 ANN-I/O Connection to FACP
ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized so
that there is approximately 10 mA of current for each LED. No series resistors are required. Refer
The LEDs are wired as illustrated in Figure 1.10. Note that the illustration depicts only connectors
P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Accessories
Figure 1.10 ANN-I/O Board Layout
ANN-LED Annunciator Module*
The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general sys-
tem faults and input zones/points when used with a compatible FACP. The ANN-LED module pro-
vides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or
addressable points. The ANN-LEDR provides alarm (red) indication for up to 30 input zones or
addressable points. Multiple ANN-(R)LED modules may be used for full system coverage.
34
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
*In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervi-
sory, burglary or trouble signals. Green indicates the presence of power or an activated output.
Figure 1.11 ANN-LEDs (shown in possible stacked configuration)
Specifications
•
•
Max. ANN-BUS Voltage: 24 VDC
Max. Current:
• Alarm: 68 mA
• Standby: 28 mA
o
o
o
o
•
•
Operating Temperature: 32 F to 120 F (0 C to 49 C)
For indoor use in a dry location only
Mounting/Installation
Refer to the documentation supplied with the ANN-LED module for mounting information.
Figure 1.12 Exploded View of ANN-LED
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
ANN-LED Board Layout and Connection to FACP
Accessories
Figure 1.13 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
1
2
3
4
5
6
7
8
Address DIP switch
ANN-BUS
TB1
ANN-BUS and power wiring are
supervised and power-limited
ANN-LED
ANN-BUS/
ACS BUS
+24 VDC
-24 VDC
TB1
TB5
TB3 + - + - + -
+ -
A B
TB4
JP8
TB6
JP5
FACP
Figure 1.13 ANN-LED Connection to FACP
ANN-RLY Annunciator Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
Specifications
•
•
•
•
•
•
•
•
•
Operating Voltage: 24 VDC
Max. Current:
Alarm: 75 mA
Standby: 15 mA
Relay Contact Ratings
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
o
o
o
o
Operating Temperature: 32 F to 120 F (0 C to 49 C)
For indoor use in a dry location only
36
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
Mounting/Installation
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis or inside
the ROME Series enclosure. Refer to the ANN-RLY Installation Document #53033 for instructions
on chassis mounting or to the ROME Series Installation Document #53530 for mounting in the sep-
arate backbox.
FACP Chassis Installation
mounting holes
mounting hooks through
mounting slots
FACP Backbox Installation
using ANN-MBRLY mounting bracket
grounding wire
mounting holes
ANN-MBRLY
mounting bracket
ANN-RLY
mounting holes
mounting holes
ROME Series Installation
using ANN-MBRLY mounting bracket
ANN-RLY on ANN-
MBRLY mounting
bracket
mounting holes
Figure 1.14 ANN-RLY Mounting Options
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Accessories
ANN-RLY Board Layout and Connection to FACP
the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
Ground Wire
ANN-RLY
attaches to chassis
(see documentation
supplied with module)
ANN-BUS
+24 VDC
-24 VDC
FACP
Figure 1.15 ANN-RLY Board Layout and Connection to FACP
ANN-BUS Audio Panel Control
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
!
The FACP is capable of providing automated activation of the ACC-25/50(ZS/T) zoned system
speaker circuits. To do this, the FACP must be enabled to communicate with the ACC-25/50ZS
plished by programming the Audio Panel ANN-BUS address into the FACP (refer to “Modules
panel, refer to the ACC-25/50ZS Series Audio Panel manual (document #51889).
The ACC-25/50ZS Series audio panel connects to the FACP via the ACS/ANN-BUS communica-
tion circuit. Zones 33 - 56 on the FACP correspond to the ACC-25/50ZS Series audio circuits
1 - 24. Zone 32 on the FACP serves as the All-Call zone and will activate all audio panel output
circuits. The programmer can select which of the five audio messages at the audio panel will play
will play over the corresponding audio panel output circuit.
38
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Product Description
Examples:
•
FACP Input programmed to Zone 33 goes into alarm, the programmed message for Zone 33
[Message 1, 2, 3, 4 or 5] will play over the ACC-25/50ZS Series output circuit 1 which
corresponds to FACP Zone 33.
•
FACP Input programmed to Zone 1 and Zone 34 (Zone 1 is programmed for a Message [1, 2,
3, 4 or 5] and Zone 34 is programmed for No Message) goes into alarm, the programmed
message for Zone 1 will play over the ACC-25/50ZS Series output circuit 2 which corresponds
to FACP Zone 34.
•
•
If two or more input zones are active at the same time, the highest priority message will turn on
(Message 1 is highest priority and Message 5 is lowest) and play over the corresponding audio
panel output circuit(s).
Zone 32 is an All-Call zone. All audio panel output circuits will turn on if Zone 32 is activated
and its programmed message will play (or the highest priority message currently being
played).
A fault at the ACC-25/50ZS Series panel will cause the FACP to indicate a System Trouble and the
display will indicate a Voice Evac Fault.
The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair of commu-
nication wires connected between the A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals
2 & 3 of the ACC-ZPMK module on the audio panel.
ACC-ZPMK
on ACC-25/50ZS Series
A (+)
B (-)
ANN-BUS
FACP
Figure 1.16 FACP Connection to ACC-25/50ZS Series Audio Panel
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Getting Started
1.8.7 Legacy ACS Annunciators
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
!
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due
to incompatible serial communication protocols.
ACM Series LED Zone Type Annunciators
The ACM Series Annunciators remotely display alarm and trouble status as well as system status.
For more detailed information, refer to the appropriate annunciator manual. Following is a list of
annunciators which can be used with the FACP.
•
ACM-16ATF - Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs
and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power
LED and a local piezo sounder. *In Canada, this module must be used to annunciate the fire
alarm input points/zones only.
•
•
AEM-16ATF - Annunciator Expander Module annunciates 16 zones with 16 red alarm LEDs
and 16 yellow trouble LEDs. *In Canada, this module must be used to annunciate the fire
alarm input points/zones only.
ACM-32A - Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In
addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It
also has a switch for local piezo silence. *In Canada, this module must be used to annunciate
the fire alarm input points/zones only.
•
AEM-32AF - Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs.
*In Canada, this module must be used to annunciate the fire alarm input points/zones only.
LCD-80F Remote Fire Annunciator
The LCD-80F annunciator is an 80-character backlit LCD remote fire annunciator that is capable of
displaying English language text. Tactile switches provide remote system Acknowledge, Silence,
Drill and Reset functions. A keyswitch allows enabling/disabling of the tactile switches. Commu-
nications between the control panel and the annunciator is accomplished over a serial interface
employing the EIA-485 communication standard. Up to 32 LCD-80F annunciators may be con-
nected to the EIA-485 circuit. The annunciators may be powered from the host FACP or a remote
UL listed filtered power supply such as the FCPS Series. For more detailed information, refer to
the LCD-80F manual.
The LCD-80F is not for use in Canadian applications.
LCD-80FC Remote Fire Annunciator (for use in Canadian applications)
The LCD-80FC is identical to the LCD-80F except for the tactile switches and keyswitch. There is
no keyswitch, and tactile switches are provided for local silence and lamp test only. No remote sys-
tem functions can be performed from the LCD-80FC annunciator.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F
expander modules, are used to provide an interface to a custom graphic LED annunciator.
1.9 Getting Started
The following is a brief summary of the minimal steps involved in bringing an MS-9600LS/MS-
9600UDLS on-line:
•
•
Address and Install Intelligent Devices (refer to the SLC Wiring Manual).
40
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Getting Started
Product Description
•
•
•
Resolve Programming Conflicts.
right and left arrow keys to navigate between devices.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2: Installation
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using key slots and
two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of
the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi-
net approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the
number of conductors required for the devices to be installed. Sufficient knockouts are provided
for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box.
All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.1 Mounting
The circuit board contains static-sensitive components. Always ground yourself with a proper
wrist strap before handling any boards so that static charges are removed from the body. Use static
suppressive packaging to protect electronic assemblies.
•
Mark and predrill holes in the wall for the center top keyhole mounting bolt using the dimen-
sions illustrated in Figure 2.2 on page 44.
•
•
•
Install center top fastener in the wall with the screw head protruding.
Place backbox over the top screw, level, and secure.
Mark and drill the left and right upper and lower mounting holes.
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
•
•
•
Install remaining fasteners and tighten.
Attach solid earth ground wire to grounding stud as indicated in Figure 2.1.
When the location is dry and free of construction dust, install the main circuit board chassis by
positioning the two mounting tab holes on the top of the chassis over the mounting studs in the
top of the backbox and sliding the mounting tabs at the bottom of the chassis into the mounting
slots in the bottom of the backbox as illustrated below.
•
Secure the chassis to the mounting studs with the supplied nuts.
42
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting
Installation
Main Circuit Board on Chassis
mounting tab holes
mounting studs
mounting tabs
grounding stud:
attach solid earth
ground wire (refer to
“AC Power and
mounting slots
Connection” on
FACP Backbox
Figure 2.1 FACP Main Circuit Board Installation
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Mounting
3.37 cm
1.325“
3.37 cm
1.325“
5.1 cm
2.00“
2.00“
2.00“
2.00“
2.00“
2.00“
2.00“
1.625“ (4.128 cm)
Semi-Flush Mounting
Do not recess box
more than 3.875” into
wall to avoid covering
venting holes on top of
box.
Hinge Slot for
optional Dress Panel
4.13 cm
16.65“ (42.29 cm)
12.00“ (30.48 cm)
4.1 cm
1.625“
2.325“ (5.91 cm)
1.625“
4.13 cm
1.625“
4.1cm
1.625“
1.25“ (3.2 cm)
7.0 cm
2.75“
12.13cm
4.775"
12.13 cm
4.775“
6.0“
15.24 cm
16.0“
40.64 cm
29.95 cm
11.792“
15.0“
38.1 cm
48.37cm
19.0“
17.83cm
7.02“
38.1 cm
15.00“
4.45cm
1.75“
Mounting
slots for
optional
Trim Ring
4.45cm
1.75“
Semi-flush
mounting
hole
16.00“ (40.64 cm)
2.00“
4.128 cm
5.207“
13.23 cm
Hinge Slot for
optional Dress Panel
13.23 cm
5.207“
4.535“
11.52 cm
1.00“ (2.54 cm)
1.30“
3.30 cm
Figure 2.2 FACP Cabinet Mounting
44
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting
Installation
Top
Depth
= 5.207" (13.23 cm)
Depth =
Door
= 16.821" (42.73 cm)
Backbox
5.325"
(13.526 cm)
= 16.65" (42.29 cm)
Door
= 19.26" (48.92 cm)
Backbox
= 19.0" (48.26 cm)
Left Side
Right Side
Bottom
Figure 2.3 FACP Cabinet Dimensions
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Power
2.2 Power
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
!
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCON-
NECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED
EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR
INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
2.2.1 AC Power and Earth Ground Connection
Primary power required for the FACP is 120 VAC, 60 Hz, 3.0 amps for
the MS-9600LS(C) and MS-9600UDLS or 240 VAC, 50 Hz, 1.5 amps
for the MS-9600LSE and MS-9600UDLSE. Overcurrent protection for
this circuit must comply with Article 760 of the National Electrical
Code (NEC) and/or local codes. Use 14 AWG (2.00 mm2) or larger
wire with 600 volt insulation rating. Make certain that the AC mains
circuit breaker is off before wiring any connections between the mains
and the control panel. Connect wiring from the AC mains to TB1 on
the FLPS-7 Power Supply, being careful to observe proper connections.
120 VAC
Hot L1
EARTH
Neut L2
Illustration depicts connection of 120 VAC to TB1. Note that the FLPS-7 Power Supply is con-
nected to the main circuit board by a cable connected to J1. Ensure that this cable is connected.
Connect a wire from the grounding stud in the cabinet to a known solid earth ground (refer to Fig-
ure 2.1 on page 43). This connection is vital for maintaining the control panel’s immunity to
unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the
panel only after the system is completely installed and visually checked. Note that AC power must
be applied to the panel before installing the battery interconnect cable (refer to the following sec-
tion).
2.2.2 Battery Power
Before connecting the batteries to the FACP, make certain that
the interconnect cable between the batteries is not connected.
Do not connect the interconnect cable until the system is com-
pletely installed. Observe polarity when connecting the batter-
ies. Connect the battery cable to TB2 on the main circuit board.
of the correct battery rating.
Interconnect
Cable
WARNING: RISK OF PERSONAL INJURY
!
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN
AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID,
IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK
IMMEDIATE MEDICAL ATTENTION.
46
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Relays
Installation
2.2.3 Special Application DC Power Output Connection
All Special Application DC power outputs are power-limited.
Power-limited Resettable Power
Power-limited Nonresettable Power #1
1.5 amperes max., 24 VDC nominal
filtered, nonresettable power can be
drawn from TB3 Terminals 3(+) and 4(-)
Power-limited Nonresettable Power #2
1.5 amperes max., 24 VDC nominal
filtered, resettable power can be drawn
from TB3 Terminals 1(+) and 2(-)
1.5 amperes max. , 24 VDC nominal
filtered, nonresettable power can be drawn
from TB3 Terminals 5(+) and 6(-)
1
2
3
4
5
6
Figure 2.4 Special Application Power Outputs - 24 VDC
2.3 Relays
The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble
relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).
The Alarm and Supervisory silk-screen labels reflect the factory default programming for the two
programmable relays.
Note that relay connections must be power-limited. Refer to Power-limited wiring requirements.
Note that the relays labeled as Alarm
Relay (Relay 1) and Supervisory Relay
(Relay 3) reflect the factory default
programming for these relays which are
programmable.
TB1
TB5
The relay labeled Trouble Relay (Relay 2)
is fixed and cannot be changed. It is a fail-
safe relay which will transfer on any trouble
or total power failure.
Relay contacts shown with power applied to panel
and no active troubles, alarms or supervisories
Figure 2.5 Relay Terminals
2.4 Notification Appliance Circuits
The control panel provides four Style Y/Class B or two Style Z/Class A NACs (Notification Appli-
ance Circuits). Each circuit is capable of 3.0 amps of current. Total system current in alarm cannot
VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Device
Compatibility Document for a listing of compatible notification appliances. The NACs, which are
located on the main circuit board, may be expanded via the FCPS Series field charger/power sup-
plies.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Notification Appliance Circuits
The following sections describe the configuration and wiring of Style Y and Style Z Notification
Appliance Circuits on the FACP main circuit board. The NACs are configured for Style Y (Class
NAC configuration to Style Z (Class A) and preparing the NACKEY configuration card located in
JP8, when installing a 4XTMF Transmitter Module.
2.4.1 Configuring NACs
The Notification Appliance Circuits on the main circuit board are configured for Style Y or Style Z
by properly orienting the NACKEY card in JP8 which is located at the top of the main circuit board
near the NAC Terminal TB4. The default configuration is for Style Y (Class B). Refer to Figure
2.6 for information on installing the NACKEY card.
NACKEY Card
• Style Z (Class A) - install NACKEY into JP8
C P A - E Y
N A C K
with Class A pointing down toward circuit board
as illustrated to the right.
• Style Y (Class B) - install NACKEY into JP8
with Class B pointing down toward circuit board .
B
C L A S S
scored mark
CLASS A
NACKEY -PCA
Key
Key-slot
NACKEY must be inserted with text side facing
in toward center of main circuit board and key
into key-slot as illustrated to the right. It is keyed
to prevent incorrect insertion.
JP8
Top edge of FACP
Main Circuit Board
If the 4XTMF Option Module is to be installed in
connectors J10 and J11, the NACKEY card must be
carefully separated at the scored mark and only the
required half installed into JP8. This will allow room
for the 4XTMF module.
TB4
JP8
NACKEY card slot
4XTMF OPT BD
4XTMF Module connectors
J11
J10
connectors for 4XTMF option module
Figure 2.6 NAC Configuration Using NACKEY
48
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Notification Appliance Circuits
Installation
2.4.2 Style Y (Class B) NAC Wiring
4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7K ohm, ½ watt P/N:71252 UL-listed
NAC 1
NAC 3
NAC 4
NAC 2
Polarized Bells
Polarized Bells
Polarized Strobes
Polarized Horns
Polarized Strobes
Polarized Horns
Notification Appliance Circuit
polarity shown in alarm state
Dummy Load all unused circuit
circuit number
TB4
Figure 2.7 NAC Style Y (Class B) Wiring
2.4.3 Style Z (Class A) NAC Wiring
2 Style Z (Class A) Notification Appliance
Circuits, supervised and power-limited
Polarized Bell
Polarized Bell
Polarized Strobe
Polarized Horn
Polarized Strobe
Polarized Horn
Notification Appliance Circuit
polarity shown in alarm state
NAC 1
NAC 2
Figure 2.8 NAC Style Z (Class A) Wiring
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Power-limited Wiring Requirements
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-lim-
ited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through dif-
ferent knockouts and/or conduits. A typical wiring diagram for the FACP is shown below.
4XTMF
SLC-2LS
Figure 2.9 Typical Power-limited Wiring Requirements
50
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules and Devices
Installation
2.6 Optional Modules and Devices
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
!
FACP Keypad/Display Removal
Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to
replace the keypad/display, access the auxiliary trouble bus connectors at J16 and J17 or install the
DACT-UD2 option module on J2, the Keypad/Display can be removed by inserting a Phillips
screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and
loosening the three mounting screws. Note that it is not necessary to disconnect the cables between
the Keypad/Display and the main circuit board unless the unit itself is being replaced. Carefully lift
the Keypad/Display and rest the unit at the bottom of the main circuit board.
NOTE: When installing the DACT-UD2, the main motherboard must be removed from the
chassis. Unplug the power supply cable from J1 before proceeding.
Keypad/DisplayMounting
Screw Access Hole
screw
standoff
standoff
screw
screw
screw
screw
screw
Keypad/Display Mounting
Screw Access Holes
Figure 2.10 Keypad/Display Removal
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Optional Modules and Devices
2.6.1 DACT-UD2 Installation
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
!
The DACT-UD2 Digital Alarm Communicator/Transmitter, which is supplied standard with the
MS-9600UDLS/E, transmits system status to UL listed Central Station receivers via the public
switched telephone network. It is capable of reporting up to 99 software zones or up to 636
addressable points. Two modular phone jacks, labeled PRI for Primary phone line and SEC for
Secondary phone line, allow easy connection of two independent telephone lines to the DACT-
UD2. The following functions have been incorporated into the DACT-UD2:
•
•
•
•
•
Line Seizure - takes control of phone lines disconnecting any premises phones
Off/On Hook - performs on and off-hook status to the phone lines
Listen for dial tone - 440 hertz tone typical in most networks
Dialing Central Station(s) number - default is Touch-Tone®, programmable to rotary
For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and ‘Kissoff’
tone(s) - the frequency and time duration of the tone(s) varies with the transmission format.
The control panel will adjust accordingly
•
Communicate in the following formats:
• Ademco Contact ID
• SIA
The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.
PRI
SEC
Primary Phone Line
Secondary Phone Line
J5 Connector (located on
back of module) plugs into J2
on FACP main circuit board
J4
USB Port
Figure 2.11 DACT-UD2 Module
52
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules and Devices
Installation
The following steps must be followed when installing the DACT-UD2 module:
1. Remove all power (AC and DC) from FACP before proceeding with installation
2. Remove all main circuit board mounting screws (6 locations) and the 4XTMF module
standoffs (2 locations), unplug the power supply cable from J1 and lift the main circuit board
assembly off the chassis (refer to Figure 2.10)
3. Remove the Keypad/Display from the main circuit board as described in the beginning of this
section
4. Remove and discard the Keypad/Display support standoff that presently occupies DACT-UD2
standoff location #3 (refer to Figure 2.12)
5. Install the supplied DACT-UD2 female/female standoffs in the three locations shown in Figure
2.12 and secure with the three supplied screws, inserted from the bottom side of the main
circuit board. Be sure to tighten them fully.
6. Carefully plug connector J5 on back of the DACT-UD2 module into connector J2 on the FACP
main circuit board, being careful not to bend any pins
7. Align the mounting holes in the DACT-UD2 module with the newly installed standoffs on the
FACP main circuit board
Standoff 1
Standoff 2
Standoff 3
J5
J2
J1 Connector located on
back of DACT-UD2 module
Figure 2.12 DACT-UD2 J1 Connector to FACP J2 Connector
Secure the module to the standoffs on the main circuit board with two of the screws supplied with the DACT-UD2 and the supplied male/female standoff which becomes the new Keypad/Display support in that location see Figure 2.13)
(
NOTE: It is important that the supplied hardware be used to secure the module in order to help
protect against electrical transients.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Optional Modules and Devices
Mounting Screw
Mounting Screw
male/female standoff
Figure 2.13 DACT-UD2 Installation on Standoffs
8. Reinstall Keypad/Display on the main circuit board by positioning the unit over the
appropriate standoffs and securing with screws which were loosened in step 3
9. Remount the main circuit board assembly to the chassis using screws and standoffs in their
original locations. Plug in the power supply cable at J1 on the main circuit board
10. Make certain to program the control panel for DACT-UD2 operation
11. Refer to the Telephone Requirement and Warnings section of the DACT-UD2 Installation and
Programming Manual Document #53037, before proceeding with this step. Connect the
premises primary and secondary phone lines to the DACT-UD2 as illustrated in Figure 2.14
and test the system for correct operation
54
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules and Devices
Installation
Primary Lines
Secondary Lines
Incoming Telco Phone
Lines
Incoming Telco
Phone Lines
Green Wire
Red Wire
Ring
Tip
Green Wire
Red Wire
Tip
Ring
To premises phones
Tip
Ring
To premises phones
Ring
Tip
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
Secondary Phone Line SEC
7 foot cable
(MCBL-7)
Primary Phone Line PRI
order separately
Male Plug
Connectors
CAUTION: It is critical that the
DACT-UD2 be located as the first
device on the incoming telephone
circuit to properly function
Female
Connectors
DACT-UD2
Figure 2.14 Wiring Phone Jacks
2.6.2 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition
to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open
with a system trouble condition if no alarm condition exists. A disable switch allows disabling of
the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Optional Modules and Devices
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connec-
tion to a polarity reversal circuit or a Remote Station receiving unit having compatible rat-
ings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the right (disconnect) position to pre-
vent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after
the module is installed in the FACP. In addition, the System Trouble LED will turn on to indicate
the Disconnect condition.
Note: 4XTMF Module is not suitable for transmitting reverse
polarity supervisory signal.
Remote Alarm (power-limited)*
* Wiring from these terminals
can exit the protected
premises. Dummy load
terminals 6 and 7 (4.7K, ¼
watt resistor) if Municipal Box
Remote Trouble (power-limited)*
No connection
is not connected.
Municipal Box (nonpower-limited)*
+ - + -
+ -
Polarities are shown for module activation
Disconnect LED
1 2 3 4 5 6 7
Disconnect Switch
shown in disconnect
position
TBL Jumper
Connect to FACP J10 & J11
Figure 2.15 4XTMF Transmitter Module
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (AC and DC) from the FACP before installing 4XTMF
2. Cut jumper JP6 on the main circuit board to allow the control panel to supervise the 4XTMF
module
3. The NACKEY Card must be separated at the score mark to allow connection of the 4XTMF
module (refer to Figure 2.6 on page 48 for complete information)
4. Carefully plug the connectors on the 4XTMF module into connectors J10 and J11 on the FACP
main circuit board, being careful not to bend any pins
5. Secure 4XTMF module to standoffs with supplied screws.
6. Reapply power to the FACP
7. For proper 4XTMF operation, the output relays must be programmed for the factory default
settings as shown on the PC board silkscreen: Alarm Relay, Trouble Relay and Supervisory
Relay
56
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules and Devices
Installation
8. When the installation has been complete, enable the 4XTMF module by sliding the disconnect
switch to the left
9. Test system for proper operation
Standoff
Standoff
Cut Jumper JP6
J10 & J11 Connectors
4XTMF
FACP
Figure 2.16 4XTMF Connectors to FACP Connectors
NOTE: Jumper JP5 on the FACP main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. The supervisory relay must be
programmed as shown on the main circuit board silk-screen (TB5, Terminals 4, 5 & 6).
Cutting JP5 will allow the 4XTMF to generate a trouble if the supervisory contact opens
Leaving JP5 in will prevent generation of a trouble if the supervisory contact opens
2.6.3 Auxiliary Trouble Input (J16 & J17)
Auxiliary Trouble Inputs 1 (J17) and 2 (J16), which are located on the FACP main circuit board,
can be used to monitor for trouble conditions on auxiliary equipment such as power supplies. J16
and/or J17 can be connected to any open collector trouble output on the auxiliary equipment. The
control panel will indicate a trouble condition if a trouble is sensed at the Auxiliary Trouble Inputs.
If the 4XTMF Module is installed and FACP jumper JP6 has been cut to supervise it, Auxiliary
Trouble Input 1 (J17) will monitor the 4XTMF for trouble conditions.
2.6.4 SLC-2LS Expander Module
The optional SLC-2LS Expander Module provides a second SLC loop for the FACP control panel.
This allows connection of an additional 318 addressable devices, bringing the total to 636 address-
able devices which can be connected to the FACP. Refer to the SLC Wiring Manual for informa-
tion on connecting devices to the SLC.
IMPORTANT! When SLC wiring is run in conduit, each SLC loop must be installed in separate
conduit.
The following steps must be followed when installing the SLC-2LS Expander Module:
1. Remove all power (AC and DC) from the FACP before installing the SLC-2LS module
2. Remove four screws from main FACP motherboard, from locations indicated in following
illustration, and replace with four supplied metal standoffs
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Optional Modules and Devices
3. Carefully plug connector J3 on the SLC-2LS module into connector J3 on the
MS-9600LS/MS-9600UDLS main circuit board, being careful not to bend any pins
4. Secure the SLC-2LS Expander Module to the four standoffs installed in step 2 with the four
supplied screws (or the screws removed in step 2)
5. Connect the SLC wiring and devices to TB8 on the SLC Expander Module. Refer to the SLC
Wiring Manual for wiring information
6. Reapply power to the control panel
7. Program the addressable devices connected to the SLC-2LS Expander Module as detailed in
8. Test the system for proper operation
SLC Loop 1
SLC Loop 2
Shield B
Shield A
SLC A-
Shield B
Shield A
SLC A-
SLC B-
SLC A+
SLC B+
SLC B-
SLC A+
SLC B+
Remove four screws and replace
with four supplied metal standoffs
SLC-2LS Expander Module
FACP
Figure 2.17 SLC-2LS Expander Module Installation
2.6.5 Printer/PC
A serial printer or a PC (personal computer) may be connected to TB7 Terminals 1 - 4 on the FACP.
The printer can be used to provide a hard-copy printout of real-time events, history file and walktest
data. An IBM compatible PC can be connected to provide local FACP programming capabilities
using the PS-Tools programming utility. Installation of either device requires panel programming
to allow the FACP to communicate with the device.
A parallel printer may also be connected to the FACP using the optional ANN-S/PG Serial/Parallel
58
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules and Devices
CAUTION: POSSIBLE EQUIPMENT DAMAGE
Installation
!
DO NOT CONNECT A PRINTER OR PC TO THE FACP IF A GROUND FAULT (ZERO IMPED-
ANCE TO GROUND) EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE MAY RESULT.
REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY WIRING.
Installation
Remote printers and PCs require separate primary power. Also required is the PRT/PK-CABLE
which is an interface cable prewired to a DB9F connector. Wire the PRT/PK-CABLE to TB7 Ter-
minals 1 - 4 as illustrated in the following figure. Connect the DB9F connector to the printer or PC
serial EIA-232 port. If a nine-pin serial connector is not available on the printer or PC, use a DB25
adapter. Make certain that the DB25 adapter does not swap the Transmit and Receive lines. Apply
power to the FACP and printer or PC. Note that a ground fault (zero impedance to ground) may
occur on the FACP, dependent on the printer or PC being used, due to this connection. For this rea-
son, it is important that there be no preexisting ground fault on the panel.
Note that the printer may or may not be supervised as determined by user programming. Refer to
Red
5
4
3
2
1
White
Green
Black
9
8
7
6
PRT/PK-CABLE
TX
RCV
DTR
GRND
RS-232 PC/PRINTER
XMT RCV DTR GRND
SLC
SLC
ACS
COMM
SHIELD
1
2
B+ A+ B- A-
B
A
T
B
6
T
B
8
T
B
7
Figure 2.18 Serial Printer and Computer Connections
Printer Configuration
Refer to the documentation supplied with the printer for pertinent information about printer setup.
Set the printer’s options as listed in the following table:
COMMUNICATION SETUP
BUFFER:
DATA BITS:
LARGE
7
EVEN
PARITY:
STOP BIT:
1 STOP
2400/4800/9600
NO
BAUD RATE:
AUTOMATIC LINE FEED
AUTOMATIC CARRIAGE RETURN
NO
PC Configuration
The Windows-based PK-CD Programming Utility Kit contains a CD-ROM with on-line help file.
2.6.6 Annunciators
Legacy ACM-8RF Relay Control Module
The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Optional Modules and Devices
Legacy ACM Series Annunciators
ACM and AFM Series Annunciators provide visual indications of FACP status in remote locations.
Refer to the appropriate annunciator manual for information on installation, wiring and operation.
60
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3: Programming
3.1 Programming Data Entry
Programming can be accomplished using the FACP keypad or by connecting an optional standard
computer keyboard. The keyboard can be connected to the PS-2 connector J7 on the control panel
main circuit board.
Local or remote programming and editing can also be accomplished using the DACT-UD2 Digital
Alarm Communicator/Transmitter which is optional for the MS-9600LS and supplied standard
with the MS-9600UDLS. Refer to the DACT-UD2 Manual P/N 53037 for detailed information.
The information presented in this section refers to programming the FACP via the onboard keypad.
If an optional computer keyboard is connected to the FACP main circuit board, the following table
describes the keyboard keys which correspond to the onboard keypad keys.
Keypad Keys
Computer Keyboard Keys
1st Event
Home
Delete
Esc
Insert
*
CLR
ESC
RECALL
*
#
#
A - Z
A - Z
0 - 9
Space bar
—
0 - 9
(on QZ key)
—
/
/
•
•
ENTER
ACK/STEP
SILENCE
DRILL
RESET
Enter
F1
F2
F3
F4
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
User Programming
3.2 User Programming
The FACP is completely field programmable and requires no special software skills. While pro-
gramming the FACP, the fire protection capabilities of the control panel are enabled. Program-
ming mode will time-out following 10 minutes of inactivity.
Site-specific programming may be accomplished in three ways:
•
Autoprogramming Feature - This is a convenient method for quickly bringing the FACP
addressable SLC devices on-line without the necessity of programming each device
Autoprogramming
•
•
Manual programming or editing, using the FACP keypad or a PC keyboard
Remote Programming and Editing Feature - allows creation and editing of site-specific custom
programs using a Windows-based computer and modem. For programs requiring a large
amount of data entry, this method may be preferred. A PK-CD programming CD-ROM can be
ordered for this purpose
•
Local Programming and Editing Feature - allows creation and editing of site-specific custom
programs using a Windows-based computer and the DACT-UD2 USB connection on the
MS-9600UDLS or Serial Port connection on TB7 of the MS-9600LS. For programs requiring
a large amount of data entry, this method may be preferred. A PK-CD programming CD-ROM
can be ordered for this purpose
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
SYSTEM ALL NORMAL
10:00A 010807
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or super-
visory event exists at the panel, the event must be cleared before entering Programming mode. To
access any of the programming or read status features, the Enter or Mode key must be pressed,
which will cause the LCD to display the following:
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Sta-
tus feature which allows the user to view the programmed features and status of the control panel
detailed description of this feature.
Pressing 2 will select user Programming which may only be accomplished by an authorized person.
After pressing 2, a screen will prompt for a password. After entering the correct password, the user
may select from a list of programming options.
Pressing 3 will select Remote Download which allows the user to enable the remote programming
option. Refer to the DACT-UD2 manual P/N 53037.
62
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Initial Power-up
Programming
Exit Programming or Read Status
The programmer can exit Read Status or Programming mode by repeatedly pressing the keypad
ESC (Escape) key until the display reads System All Normal. Ten minutes of inactivity will also
cause the FACP to exit Programming mode. Note that the data which is entered during Program-
ming mode is not saved until the programmer exits this mode by repeatedly pressing the ‘ESC’ key.
If the Reset key is pressed or power is lost before exiting Programming mode, all data which was
just entered will be lost.
User Programming Levels
There are two user programming levels:
•
User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
•
User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.
3.3 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of addressable devices to the SLC, apply power to the control panel. If
the addressable devices have not yet been programmed into the FACP, their LEDs will not flash and
the following trouble message will be displayed.
TROUBL IN SYSTEM
NO DEVICES INSTALLED
09:03A 020410
3.4 Programming Screens Description
The main options available when the Enter key is pressed are: Read Status, Programming Mode.
Each option has multiple functions or features which may be chosen. To view all of the choices, it
is necessary that the programmer scroll through a number of additional subscreens. These selec-
tions are displayed on multiple screens to make them more readable for the programmer. Refer to
“Master Programming Level” on page 65, for additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the pro-
grammer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed in
the upper right corner of the screen being viewed. The programmer can then press the keypad Up
or Down arrow key to view the new subscreen. To select one of the choices in a screen, the pro-
grammer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is followed to view all option choices.
3.5 Programming and Passwords
There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in non-
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Programming and Passwords
Change” on page 135. If an invalid password is entered, the blinking cursor will return to the first
password character position. To exit Programming or Read Status mode at any time, press the ESC
(Escape) key repeatedly. Note that Programming mode must be exited using the ESC key in order
to store the program data entered during this mode. If the Reset key is pressed or power is lost
before exiting Programming mode, the data just entered will not be saved.
To access user Programming mode, press the Enter or Mode key. The LCD will display the follow-
ing:
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
To enter the user Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
*****
Entering the Master level password (default 00000) will cause the following screen to appear:
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
If the Maintenance level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.
64
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
3.6 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user Program-
ming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the sys-
tem Trouble LED flashes until Programming mode is exited. The following display will appear:
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the dis-
play, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated
below while pressing the ‘up’ arrow key will display the previous screen.
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOPS
Programming Screen #2
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
3.6.1 Autoprogram
PROGRAMMING
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which
prompts the control panel to poll all devices installed on one or both SLC loops. The primary pur-
pose of autoprogramming is to allow the installer a fast and easy way to bring the system on-line as
quickly as possible. The first time the system is powered-up, it should be autoprogrammed.
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
If the system is already programmed and Autoprogram is initiated, the system will only add default
values for newly installed devices.
When Autoprogram is selected, the programmer is given the option of autoprogramming all loops,
only loop 1 or only loop 2. The following will be displayed on the LCD:
AUTOPROGRAM
1=LOOP 1
2=LOOP 2
3=ALL LOOPS
Autoprogram Loop Select Screen
After selecting one of the Autoprogram options, the control panel will begin autoprogramming the
system by communicating with each addressable device installed on one or both loops. While auto-
programming, the panel will display the following:
AUTOPROGRAM
AUTOPROGRAMMING!
PLEASE WAIT
Autoprogram Progress Screen
When Autoprogramming is completed, the control panel will display the type and quantity of each
device installed on the SLC loop(s) similar to the following display:
# OF DET LOOP1 055
# OF MON LOOP1 035
# OF CON LOOP1 030
Autoprogram Result Screen #1
# OF DET LOOP2 000
# OF MON LOOP2 000
# OF CON LOOP2 000
Autoprogram Result Screen #2
In the preceding example, the first display indicates that Loop 1 has 55 addressable detectors, 35
monitor modules and 30 control modules installed. The second display indicates that Loop 2 has
no devices installed.
66
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
3.6.2 Point Program
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
The Point Program option allows the programmer to add a new addressable device to an SLC loop,
delete an existing device from a loop or change the programming for an existing device. Pressing
2, while viewing Programming Screen #1, will select the Point Program option and display the fol-
lowing screen:
Programming Screen #1
POINT PROGRAM
SELECT LOOP
1=LOOP 1
2=LOOP 2
Point Program Screen #1
The programmer selects the desired SLC loop by pressing 1 or 2 in Point Program Screen #1,
which causes the panel to display the following screen:
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
Detector Programming
Pressing 1, while viewing Point Program Screen #2, will allow the programmer to add, delete or
change the programming of an addressable detector. The following screen will be displayed by the
control panel:
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the
programmer to add a new detector address to programming:
ADD DETECTOR
ENTER DETECTOR#
***
Add Detector Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
Press the down arrow key to view additional choices. Press the number corresponding to the
desired selection to program that type to the newly added detector.
When the type has been selected, the following screen will be displayed:
ADD DETECTOR
DETECTOR#
IS ADDED
005
The programmer can continue adding detectors by pressing the ESC or left arrow key which will
return the display to the Add Detector Screen.
Delete Detector
Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the pro-
grammer to delete a specific detector:
DETECTOR
1=ADD
2=DELETE
3=EDIT
DELETE DETECTOR
ENTER DETECTOR#
***
Detector Screen
Delete Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 005. When the last digit is keyed-in, the following screen
will be displayed:
DELETE DETECTOR
DETECTOR#
IS DELETED
005
The programmer can continue deleting detectors by pressing the ESC or left arrow key which will
return the display to the Delete Detector Screen.
68
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Edit Detector
Programming
The programmer can change a detectors existing or factory default programming by pressing 3 in
the Detector Screen. The following screen will be displayed:
EDIT DETECTOR
ENTER POINT ADDRESS
***
Edit Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 017.
When the last digit is keyed-in, if the selected address has not been added to programming, a screen
showing information about a device that is installed with a lower address, closest to the selected
address, will be displayed.
If no detectors have been installed on the loop, the following will be displayed:
NO DETECTOR
INSTALLED
Edit Detector Screen #1
If the selected address has been added to programming, device summary screens will be displayed.
These screens allow the programmer to view all device settings at a single glance. Pressing the left
or right arrow keys will allow the programmer to rapidly view the devices at the previous or next
address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not physically installed
on the SLC or has a communication fault but the address is programmed in the system, the follow-
ing screen will be displayed:
TROUBL SMOKE(PHOTO)
********************
ZNNN
* 1D017
Edit Detector Screen #1
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
69
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
If the selected address has been added to programming and a detector (such as a photoelectric
detector) with the selected address is physically installed on the SLC and is communicating with
the control panel, the following will be displayed:
NORMAL SMOKE (PHOTO)
*********************
ZNNN
V 1D017
Edit Detector Screen #1
To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to
view the Edit Detector screens.
In the preceding example:
• Normal - indicates that the detector with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
• <ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device
• ZNNN - represents the first of five possible software zones that the detector is assigned to
(NNN = the three digit zone number from 000 - 099)
• V or * - indicates whether or not alarm verification is enabled (V = alarm verification
enabled and * = alarm verification disabled)
• 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop 1, D=Detector
and 017 = Detector Address 017)
70
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
The following examples show the editing of a photoelectric smoke detector with address 017,
located on the first SLC loop:
EDIT DETECTOR 1D017
1=ENABLED YES
2=TYPE SMOKE(PHOTO)
3=VERIFICATION OFF
Edit Detector Screen #2
EDIT DETECTOR 1D017
1=WALKTEST
2=PAS
3=PRE-SIGNAL
NO
NO
NO
Edit Detector Screen #3
EDIT DETECTOR 1D017
1=ZONE ASSIGNMENT
00 ** ** ** **
Edit Detector Screen #4
EDIT DETECTOR 1D017
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Detector Screen #5
Enable/Disable Detector
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is
selected, the detector will not be polled by the control panel, preventing the detector from reporting
alarms and troubles to the panel. The control panel will display the device type and address which
has been disabled and will turn on the Trouble LED and Disable LED.
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector
Screen #2. This will cause the control panel to display the following Detector Type Screens:
DETECTOR TYPE
1=SMOKE PHOTO
2=USER DEFINED-1
3=SMOKE (ION)
Detector Type Screen #1
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
71
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Pressing the down arrow key will display additional detector types as indicated in the following
table:
Detector Type
Smoke Photo
User-Defined-1
Smoke Ion
Action When Activated
Fire Alarm
same as previous (Smoke Photo)
Fire Alarm
User-Defined-2
Heat Detect
same as previous (Smoke Ion)
Fire Alarm
User-Defined-3
Smoke DuctP
User-Defined-4
Photo w/Heat
User-Defined-5
Duct-Superv
User-Defined-6
Photo-SupervAR
User-Defined-7
ADAPT
same as previous (Heat Detect)
Fire Alarm
same as previous (Smoke DuctP)
Fire Alarm
same as previous (Photo w/Heat)
Supervisory, latching
same as previous (Superv DuctP)
Supervisory, nonlatching (works only in LiteSpeed)
same as previous (Photo-SupervAR)
Fire Alarm
User-Defined-8
Beam
same as previous (ADAPT)
Fire Alarm
User-Defined-9
same as previous (Beam)
While viewing any Detector Type screen, select the type of detector being programmed by pressing
the corresponding keyboard number key. The display will return to Edit Detector Screen #2 and
indicate the selection next to the Type option.
NOTE: If a detector is selected as a SUPERV DUCTP type, it will function like a supervisory point,
not a fire alarm point. The supervisory LED and supervisory relay will activate, not the fire alarm LED
or alarm relay, if smoke is sensed.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and
not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2
so that the display reads Verification On. Each time the 3 key is pressed, the display will toggle
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable a device for the Walktest feature,
press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes. Each press
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time of
up to 3 minutes. Zone 97, however, will activate immediately and may be used to connect a signal-
ing device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose).
To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until the display reads
PAS Yes. Each press of the 2 key will cause the display to toggle between PAS Yes and PAS No.
For example, if a detector with address 005 is to be configured for PAS operation:
• Select PAS Yes when editing the detector set to address 005
72
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
• Program the desired zone or zones to be activated by this detector, in this example Z001
• Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001
• Program an output, such as a control module, for PAS activation by assigning zone Z97 to it.
This control module may be connected to a signaling device used to indicate a PAS
condition (do not use a Notification Appliance Circuit for this purpose)
• Enable zones Z001 and Special Purpose Zone PAS 97 and set the PAS delay timer to some
value
With the preceding program settings, when the detector with address 005 is activated, zone Z97
will cause its associated control module to activate immediately, sounding the connected PAS sig-
naling device. Following the PAS delay time, zone Z001 will cause its associated control module
to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a preprogrammed time
delay of up to three minutes while allowing for visual verification by a person. Note that the alarm
relay and communicator will respond to the initial alarm immediately. In addition, Zone 98 will
activate. This zone can be programmed to a control module which may be used to activate a
sounder or indicator which the installer designates as a Presignal indication (do not use a Notifica-
tion Appliance Circuit for this purpose). To enable the Pre-signal feature, press 3 while viewing
Edit Detector Screen #3 until the display reads Pre-signal Yes. Each press of the 3 key will cause
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
For example, if a detector with address 005 is to be configured for Pre-Signal operation:
• Select Pre-signal Yes when editing the detector set to address 005.
• Program the desired zone or zones to be activated by this detector, in this example Z001.
• Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001.
• Program an output, such as a control module, for Pre-signal activation by assigning zone
Z98 to it. This control module may be connected to a signaling device used to indicate a
Pre-signal condition (do not use a Notification Appliance Circuit for this purpose).
• Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Pre-signal delay
timer to some value.
With the preceding program settings, when the detector with address 005 is activated, zone Z98
will cause its associated control module to activate immediately, sounding the connected signaling
device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone Z001 will
cause its associated control module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
Zone Assignment
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while view-
ing Edit Detector Screen #4 displays the following screen:
EDIT DETECTOR
1=ZONE ASSIGNMENT
00 ** ** ** **
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Edit Detector Screen #4
Zone Assignment Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
73
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zone Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate
through the zones and the CLEAR key can be used to quickly clear a zone.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the detec-
tor currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will cause the
following screen to be displayed:
EDIT DETECTOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Detector Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
74
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be dis-
played. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
Press the number corresponding to the adjective that is to be used as a descriptor for the location of
the detector currently being programmed. When an adjective has been selected, it will appear at the
top of the display as indicated by the asterisks.
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
**********************
1=WEST
2=FRONT
**********************
1=NORTH
2=SOUTH
3=EAST
3=CENTER
Adjective Screen #2
Adjective Screen #1
*********************
1=MAIN
2=FIRST
**********************
1=REAR
2=UPPER
3=2ND
3=LOWER
Adjective Screen #4
Adjective Screen #3
**********************
1=3RD
2=4TH
**********************
1=FLOOR1
2=FLOOR2
3=5TH
3=FLOOR3
Adjective Screen #5
Adjective Screen #6
**********************
1=FLOOR4
2=FLOOR5
3=ROOM
Adjective Screen #7
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be dis-
played. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press
the number corresponding to the noun that is to be used as a descriptor for the location of the detec-
tor currently being programmed. When a noun has been selected, it will appear at the top of the
display as indicated by the asterisks.
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
**********************
1=CLOSET
2=CORRIDOR
**********************
1=BASEMENT
2=BOILER RM
3=CLASSROOM
3=ELECTRIC RM
Noun Screen #2
Noun Screen #1
**********************
1=ELEVATOR
2=ENTRANCE
3=FLOOR
**********************
1=GARAGE
2=HALLWAY
3=HVAC RM
Noun Screen #3
Noun Screen #4
**********************
1=KITCHEN
2=LOBBY
**********************
1=PATIENT
2=RESTROOM
3=ROOM
3=OFFICE
Noun Screen #5
Noun Screen #6
**********************
1=STAIRWAY
2=STOREROOM
3=WING
**********************
1=ZONE
Noun Screen #8
Noun Screen #7
76
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previ-
ous Adjective and Noun Screens. The new screens will list custom Adjectives and Nouns which
have been programmed into the control panel using the PS-Tools programming kit. These descrip-
tors are selected as described in the previous sections.
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
Description
EDIT DETECTOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
The Description selection allows the programmer to enter additional information about the detector
currently being programmed. This information will be displayed as part of the device label on the
display. Pressing 2 while viewing Edit Detector Screen #5 will cause the following screen to be
displayed:
Edit Detector Screen #5
DESCRIPTION 1D002
NOUN/ADJECTIVE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional
descriptive information about the device being programmed. This information will appear on the
display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters
from the keypad, repeatedly press the appropriate key until the desired character is displayed in the
first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle
through the characters 2, A, and B. Press the right arrow key to move the cursor one position to the
right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four
times until a blank appears in the desired position. When all characters have been entered, press the
Enter key to store the information. The display will return to the Edit Detector Screen #5, display-
ing the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the
first letter of the Description, Adjective or Noun field as follows:
•
•
If the zero key is pressed, a 0 is placed in the first letter position.
If the zero key is then pressed a second time with no intervening key actions, the entire field is
replaced with the field entered for the previous device programmed, and the cursor moves to
the last character of the field (Recall function). The Recalled Adjective or Noun field may
now be changed letter-by-letter.
•
•
If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character is 9 it goes to 0.
The above increment function may be repeated with each press of the zero key.
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
77
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
4. Press the right arrow key to advance the zone field.
5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01
through Z99 may be selected to link software zones.
Module Programming
Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or
change the programming of an addressable module. The following screen will be displayed by the
control panel:
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
Add Module
Pressing 1 while viewing the Modules Screen will display the following screen which allows the
programmer to add a new module address to programming:
ADD MODULE
ENTER MODULE#
***
Add Module Screen #1
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit module address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
ADD MODULE
1=CONTROL
2=MONITOR
Add Module Screen #2
78
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Pressing 1 for Control Module or 2 for Monitor Module will cause the following screen to be dis-
played:
ADD MODULE
MODULE#
IS ADDED
005
Add Module Screen #3
The programmer can continue adding modules by pressing the ESC or left arrow key which will
return the display to the Add Module Screen #1.
Delete Module
Pressing 2 in the Modules Screen will display the Delete Module Screen which allows the program-
mer to delete a specific module:
MODULES
1=ADD
2=DELETE
3=EDIT
DELETE MODULE
ENTER MODULE#
***
Modules Screen
Delete Module Screen
A flashing cursor will appear in the position of the first asterisk to the left. Using the panel keypad,
key in the module address such as 005. When the last digit is keyed in, the following confirmation
that the module has been deleted will be displayed:
DELETE MODULE
MODULE#
IS DELETED
005
Edit Module Screen for Monitor Module
The programmer can change a modules existing or factory default programming by pressing 3 in
the Modules Screen. The following screen will be displayed:
EDIT MODULE
ENTER MODULE ADDRESS
***
Edit Module Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
79
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit module address, such as 012. When the last digit is keyed-in, if the selected address
has not been added to programming, a screen showing information about a device that is installed
with a lower address, closest to the selected address, will be displayed. If no modules are installed
on the loop, the following screen will be displayed:
NO MODULE
INSTALLED
Edit Module Screen
If the selected address has been added to programming but a module (such as a monitor module)
with the selected address is not physically installed on the SLC or has a communication fault, the
following screen will be displayed:
TROUBL MONITOR
<ADJ><NOUN>
ZNNN
1M012
If the selected address has been added to programming and a module (such as a monitor module)
with the selected address is physically installed on the SLC and is communicating with the control
panel, the following screen will be displayed:
NORMAL MONITOR
<ADJ><NOUN>
ZNNN
1M012
To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Monitor screens. In the preceding example:
• Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled).
• <ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device.
• ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the two digit zone number from 000 - 099).
• 1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module
and 012 = Module Address 012).
If the selected address corresponds to a control module, a screen displaying information about the
control module with the selected address will be displayed as shown in “Edit Module Screen for
Control Modules” on page 88.
80
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
If the selected address corresponds to a monitor module, a screen displaying information about the
module with the selected address will be displayed as illustrated in the following:
NORMAL MONITOR
<ADJ><NOUN>
ZNNN
1M012
EDIT MONITOR 1M012
1=ENABLED
2=TYPE MONITOR
YES
Edit Monitor Screen #2
EDIT MONITOR 1M012
1=PRE-SIGNAL NO
Edit Monitor Screen #3
EDIT MONITOR 1M012
1=WALKTEST
YES
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Monitor Screen #4
EDIT MONITOR 1M012
1=ADJECTIVE/NOUN
2=DESCRIPTION
********************
Edit Monitor Screen #5
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing the Edit Module Screen
#2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled
No is selected, the module will not be polled by the control panel, preventing the module from
reporting alarms and troubles to the panel. The control panel will indicate a system trouble condi-
tion and the Disable LED with turn on if any devices are disabled.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
81
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Type Monitor
EDIT MONITOR
1=ENABLED
The FACP response to the activation of a user-defined type is the same as most previous standard
types in the list, thus allowing a variety of user-defined types and responses. To select the type of
monitor module being programmed, press the 2 key while viewing the Edit Monitor Screen #2.
This will cause the control panel to display the following Monitor Type Screens:
2=TYPE MONITOR
Edit Monitor Screen #2
MONITOR TYPE
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
Monitor Type Screen #1
Pressing the down arrow key will display additional Monitor Type screens. While viewing one of
the Monitor Type screens, select the type of monitor module being programmed by pressing the
corresponding keypad number key. The display will return to the Edit Monitor Screen #2 which
will show the new type selection.
Table 3.1 lists the Monitor Types and their respective functions.
82
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Monitor module type selection will affect the function of the point as follows:
Programming
Monitor Type
Action When Activated
Fire Alarm
Pull-Station
User-Defined-1
Waterflow
same as previous (Pull-Station)
Fire Alarm Delayed
User-Defined-2
Monitor
same as previous (Waterflow)
Fire Alarm
User-Defined-3
Future
same as previous (Monitor)
not used
Future
not used
Smoke-Conventional1
User-Defined-5
Heat-Conventional
User-Defined-6
Medic-Alert2
Fire Alarm
same as previous (Smoke-Conventional)
Fire Alarm
same as previous (Heat-Detector)
Supervisory, latching
User-Defined-7
Hazard-Alert2
User-Defined-8
User-Defined-9
Phone
same as previous (Medic-Alert)
Supervisory, latching
same as previous (Hazard-Alert)
Supervisory, latching
same as previous (Tornado-Alert)
Active Phone (LCD display only)
same as previous (Phone)
Supervisory, nonlatching (tracking)
same as previous (Tamper)
Supervisory, latching
User-Defined-10
Tamper
User-Defined-11
Supervisory
User-Defined-12
Supervisory-AR3
User-Defined-13
HVAC OVRRIDE4
Power-Monitor
User-Defined-14
Trouble-Monitor
User-Defined-15
Process-Monitor2
User-Defined 16
Process-Monitor-AR2, 3
User-Defined-17
Future
same as previous (Supervisory)
Supervisory, nonlatching (tracking)
same as previous (Supervisory-AR)
Switch Supervisory, nonlatching (tracking)
Power Fault
same as previous (Power Monitor)
Trouble
same as previous (Trouble Monitor)
Piezo
same as previous (Process-Monitor)
Piezo, nonlatching (tracking)
same as previous (Process-Monitor-AR)
not used
Future
not used
Ack-Switch
Acts like panel Acknowledge Key
Acts like panel Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
Sil-Switch
Reset-Switch
Drill-Switch
PAS-Bypass
HVAC RESTART4
Drill-Switch-AR3
Switch
Drill Switch, nonlatching (tracking)
Table 3.1 Monitor Types
1 Conventional 2-wire smoke detectors may be powered using an external power supply
with an SLC Control Relay Module programmed for Resettable Power operation (refer
to note 1 on page page 89).
2 Combination systems employing these non-fire monitor types require the SLC loop to
be programmed by the installer for Style 4 operation and isolator modules must be
employed on each non-fire branch of the SLC as per Figure 13 in the Fire-Lite SLC
Wiring Manual (document number 51309). Fire and non-fire devices must not be used
on the same SLC branch.
3 For all entries ending in AR, AR refers to AutoResettable.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
83
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Pre-signal
EDIT MONITOR
1=PRE-SIGNAL
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display
reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal
Edit Monitor Screen #3
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Monitor Screen #4
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2
while viewing Edit Monitor Screen #4 displays the following screen:
MON ZONE ASSIGN
Z00 Z** Z** Z** Z**
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zones Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Monitor Screen #4.
Noun/Adjective
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
The Noun/Adjective selection allows the programmer to enter specific descriptors about the moni-
tor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will
cause the following screen to be displayed:
Edit Monitor Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
84
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be dis-
played. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
Press the number corresponding to the adjective that is to be used as a descriptor for the location of
the monitor module currently being programmed.
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
**********************
1=WEST
2=FRONT
**********************
1=NORTH
2=SOUTH
3=EAST
3=CENTER
Adjective Screen #2
Adjective Screen #1
**********************
1=MAIN
2=FIRST
**********************
1=REAR
2=UPPER
3=2ND
3=LOWER
Adjective Screen #4
Adjective Screen #3
**********************
1=3RD
2=4TH
**********************
1=FLOOR 1
2=FLOOR 2
3=5TH
3=FLOOR 3
Adjective Screen #5
Adjective Screen #6
**********************
1=FLOOR 4
2=FLOOR 5
3=ROOM
Adjective Screen #7
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
85
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be dis-
played. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press
the number corresponding to the noun that is to be used as a descriptor for the location of the mon-
itor module currently being programmed.
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
**********************
1=CLOSET
2=CORRIDOR
**********************
1=BASEMENT
2=BOILER RM
3=CLASSROOM
3=ELECTRIC RM
Noun Screen #2
Noun Screen #1
**********************
1=GARAGE
2=HALLWAY
**********************
1=ELEVATOR
2=ENTRANCE
3=FLOOR
3=HVAC RM
Noun Screen #4
Noun Screen #3
**********************
1=KITCHEN
2=LOBBY
**********************
1=PATIENT
2=RESTROOM
3=ROOM
3=OFFICE
Noun Screen #5
Noun Screen #6
**********************
1=STAIRWAY
2=STOREROOM
3=WING
**********************
1=ZONE
Noun Screen #8
Noun Screen #7
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previ-
ous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which
have been programmed into the control panel using the PS-Tools programming kit.
86
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Description
Programming
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
The Description selection allows the programmer to enter additional information about the monitor
module currently being programmed. This information will be displayed as part of the device label
on the LCD display. Pressing 2 while viewing Edit Monitor Screen #5 will cause the following
screen to be displayed:
Edit Monitor Screen #5
DESCRIPTION 1M012
NOUN/ADJECTIVE
********************
Noun/Adjective Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional
descriptive information about the device being programmed. This information will appear on the
LCD display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters
from the keypad, repeatedly press the appropriate key until the desired character is displayed in the
first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle
through the characters 2, A, and B. Press the right arrow key to move the cursor one position to the
right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four
times until a blank appears in the desired position. When all characters have been entered, press the
Enter key to store the information. The display will return to the Edit Monitor Screen #4, display-
ing the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the
first letter of the Adjective or Noun field as follows:
•
•
If the zero key is pressed, a 0 is placed in the first letter position.
If the zero key is then pressed a second time with no intervening key actions, the entire
Adjective field is replaced with the field entered for the previous device programmed, and the
cursor moves to the last character of the field (Recall function). The Recalled Adjective or
Noun field may now be changed letter-by-letter.
•
•
If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character is 9 it goes to 0.
The above increment function may be repeated with each press of the zero key.
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field.
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
4. Press the right arrow key to advance the zone field.
5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01
through Z99 may be selected to link software zones.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
87
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Edit Module Screen for Control Modules
The programmer can change a module’s existing or factory default programming by pressing 3 in
MODULES
1=ADD
the Modules Screen. The following screen will be displayed:
2=DELETE
3=EDIT
EDIT MODULE
ENTER MODULE ADDRESS
***
Modules Screen
Edit Module Screen
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as 002. When the last digit is keyed
in, if the selected address corresponds to a control module, a screen displaying information about
the control module with the selected address will be displayed as illustrated in the following:
NORMAL
CONTROL
<ADJ><NOUN>
SW ZNNN
1M002
Edit Control Screen #1
In the preceding example:
•
Normal - indicates that the module with the selected address is physically installed on the SLC
and communicating with the control panel (enabled).
•
<ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device.
•
•
•
Control - indicates that the selected module is a control module.
S or * - represents Silenceable (S) or Nonsilenceable (*).
W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * =
Waterflow Timer Delay disabled).
•
•
ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the three digit zone number from 000 - 099).
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module
and 002 = Module Address 02).
88
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Control screens:
EDIT CONTROL
1=ENABLED
YES
2=TYPE CONTROL
3=SILENCEABLE YES
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
YES
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Control Screen #4
Enable/Disable Module
To Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2.
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No
is selected, the module will not be polled by the control panel, preventing the module from activat-
ing its output devices. The control panel will indicate a system trouble condition and the Disable
LED will turn on if any devices are disabled.
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
Type
To select the type of control module being programmed, press the 2 key while viewing the Edit
Control Screen #2. This will cause the control panel to display the following Control Type Screens.
Press the down arrow key to view additional screens and selections.
CONTROL TYPE
1=BLANK
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1
While viewing one of the Control Type screens, select the type of control module being pro-
grammed by pressing the corresponding keypad number key. The display will return to the Edit
Control Screen #2 and indicate the new type selection.
NOTE: A control relay module set to the Resettable Power type will follow the main circuit board
24 VDC resettable power unless the control relay module is disabled.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
89
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
The following table contains control module type codes and their functions which are displayed in
the Control Type screens:
Control Type
Bell Circuit
Special Function
NAC Type - supervised
NAC Type - supervised
NAC Type - supervised
Ignore Open Circuit
Horn Circuit
Sounders
Relay
Strobe Circuit
Control
NAC Type - supervised
NAC Type - supervised
Relay Type - Ignore Open Circuit
Relay Type - Ignore Open Circuit
Resettable Power1
HVAC SHUTDN 2
1 When using a control relay module to supply resettable power to conventional 2-
wire smoke detectors, the MMF-302 monitor module must be set for smoke-
conventional operation.
EDIT CONTROL
1=ENABLED
2=TYPE
Silenceable
3=SILENCEABLE
The Silenceable selection allows the programmer to select whether output devices connected to the
control module can be silenced, either by pressing the Alarm Silence key or by enabling Autosi-
lence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable feature
causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the display to
toggle between Silenceable Yes and Silenceable No.
Edit Control Screen #2
Note that nonsilenceable outputs will not be activated for Fire Drill.
Walktest
EDIT CONTROL
1=WALKTEST
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
Zone Assignment
A maximum of five zones can be programmed to each addressable control module. Pressing 2
while viewing Edit Control Screen #3 displays the following screen:
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
90
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
remaining zones can be left blank or programmed as general alarm zones Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Control Screen #3.
Noun/Adjective
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
The Noun/Adjective selection allows the programmer to enter specific descriptors about the control
module currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause
the following screen to be displayed:
Edit Control Screen #4
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
91
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be dis-
played. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
Press the number corresponding to the adjective that is to be used as a descriptor for the location of
the control module currently being programmed.
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
**********************
1=WEST
2=FRONT
**********************
1=NORTH
2=SOUTH
3=EAST
3=CENTER
Adjective Screen #2
Adjective Screen #1
**********************
1=MAIN
2=FIRST
**********************
1=REAR
2=UPPER
3=2ND
3=LOWER
Adjective Screen #4
Adjective Screen #3
**********************
1=3RD
2=4TH
**********************
1=FLOOR 1
2=FLOOR 2
3=5TH
3=FLOOR 3
Adjective Screen #5
Adjective Screen #6
**********************
1=FLOOR 4
2=FLOOR 5
3=ROOM
Adjective Screen #7
92
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be dis-
played. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press
the number corresponding to the noun that is to be used as a descriptor for the location of the con-
trol module currently being programmed.
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
**********************
1=CLOSET
2=CORRIDOR
**********************
1=BASEMENT
2=BOILER RM
3=CLASSROOM
3=ELECTRIC RM
Noun Screen #2
Noun Screen #1
**********************
1=GARAGE
2=HALLWAY
**********************
1=ELEVATOR
2=ENTRANCE
3=FLOOR
3=HVAC RM
Noun Screen #4
Noun Screen #3
**********************
1=KITCHEN
2=LOBBY
**********************
1=PATIENT
2=RESTROOM
3=ROOM
3=OFFICE
Noun Screen #5
Noun Screen #6
**********************
1=STAIRWAY
2=STOREROOM
3=WING
**********************
1=ZONE
Noun Screen #8
Noun Screen #7
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previ-
ous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which
have been programmed into the control panel using the PS-Tools programming kit.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
93
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Description
EDIT CONTROL
1=ADJECTIVE/NOUN
2=DESCRIPTION
The Description selection allows the programmer to enter additional information about the control
module currently being programmed. This information will be displayed as part of the device label
on the display. Pressing 2 while viewing Edit Control Screen #4 will cause the following screen to
be displayed:
Edit Control Screen #4
DESCRIPTION 1M002
NOUN/ADJECTIVE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional
descriptive information about the device being programmed. This information will appear on the
display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters
from the keypad, repeatedly press the appropriate key until the desired character is displayed in the
first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle
through the characters 1, A, and B. Press the right arrow key to move the cursor one position to the
right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four
times until a blank appears in the desired position. When all characters have been entered, press the
Enter key to store the information. The display will return to the Edit Control Screen #4, displaying
the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the
first letter of the Adjective or Noun field as follows:
•
•
If the zero key is pressed, a 0 is placed in the first letter position.
If the zero key is then pressed a second time with no intervening key actions, the entire
Adjective field is replaced with the field entered for the previous device programmed, and the
cursor moves to the last character of the field (Recall function). The Recalled Adjective or
Noun field may now be changed letter-by-letter.
•
•
If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character is 9 it goes to 0.
The above increment function may be repeated with each press of the zero key.
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field.
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
4. Press the right arrow key to advance the zone field.
5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01
through Z99 may be selected to link software zones.
94
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
3.6.3 Zone Setup
Pressing 3 while viewing Programming Screen #1 will access the Zone Setup screens as illustrated
below:
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
ZONE SETUP
1=ENABLE
2=DISABLE
Programming Screen #2
3=ZONE 97 98 99
Zone Setup Screen #1
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
Enable
ZONE SETUP
1=ENABLE
Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
ZONE TO ENABLE
Z
Enable Screen
This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z.
Another zone can then be enabled.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
95
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Disable
ZONE SETUP
1=ENABLE
Pressing 2 for Disable, while viewing Zone Setup Screen #1, will display the following screen:
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
ZONE TO DISABLE
Z
Disable Screen
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be disabled and the cursor will return to the original position next to
the Z. Another zone can then be disabled.
Zone 97, 98 and 99
Pressing 3 for Zone 97, 98 and 99, while viewing Zone Setup Screen #1, will display the following
screen:
SPEC PURPOSE ZONE
1=PAS 97
OFF
2=PRESIGNAL 98 OFF
3=TWO STAGE 99 OFF
Zone 97, 98 and 99 Screen
Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose applica-
tions. In the above illustration, the three zones are shown Off, which means they can be pro-
grammed to function in the same manner as all other zones, by assigning them to input and output
devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the
display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS
(Positive Alarm Sequence) activation of any detector will cause Zone 97 to activate. By assigning
Zone 97 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a PAS condition in the control panel. Do not
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condi-
tion.
Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is pro-
grammed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning
Zone 98 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a Pre-signal condition in the control panel. Do
not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal
condition.
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause
the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to “Two Stage Opera-
tion” on page 111 for a description of this feature.
96
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Zones Installed
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to
the following:
Zone Setup Screen #2
ZONES INSTALLED
00 01 02 03 04 05
Zones Installed Screen
This display will show all of the zones that have been programmed into the control panel. Note that
an up and/or down arrow may appear in the upper right corner of the display, indicating that addi-
tional screens of zone information exists. Press the up or down arrow keys to view the additional
zones.
Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to
the following:
ZONES ENABLED
00 01 02 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19 20 21
Zones Enabled Screen
This display will show all of the zones that are enabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.
Zones Disabled
Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar
to the following:
ZONES DISABLED
03
Zones Disabled Screen
This display will show all of the zones that are disabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
97
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Zone Type
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on
the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a
screen similar to the following:
Zone Setup Screen #3
ZONE TYPE PROG
1=Z00 MONITOR
2=Z01 MONITOR
3=Z02 MONITOR
Zones Installed Screen
This display will show the system zones (default and user programmed) and their associated types.
Note that an up and/or down arrow will appear in the upper right corner of the display, indicating
that additional screens of zone information exists. Press the up or down arrow keys to view zones
Z00 through Z99.
Zone types can be changed by pressing the keypad number key corresponding to the zone in each
Zones Installed Screen. Available zone types will be displayed in the resultant screens. For exam-
ple, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following
screens will be displayed:
ZONE TYPE PROG
1=MONITOR
ZONE TYPE PROG
1=HEAT
2=SMOKE PHOTO
3=WATERFLOW
2=PULL STATION
3=DUCT
Zone Type Program Screen #1
Zone Type Program Screen #2
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON
3=TAMPER
3=SMOKE ION
Zone Type Program Screen #4
Zone Type Program Screen #3
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Water-
flow silenceable zone type to the selected zone. Any signaling devices programmed to the same
zone can be silenced by pressing the Alarm Silence key or by using the auto-silence feature.
To program a waterflow circuit as nonsilenceable, refer to “System Setup” on page 100.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only
change how it is reported to the Central Station.
98
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Zones Available
ZONE SETUP
1=ZONE TYPES
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
ZONES AVAILABLE
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19
The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.
3.6.4 Loop Setup
Loop Setup allows the programmer to configure the SLC Loop(s) for NFPA Style 4, 6 or 7 wiring
and to select the protocol for each loop. Pressing 1 while viewing Programming Screen #2 will
cause the following screen to be displayed:
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOPS
LOOP SETUP
1=LOOP 1
2=LOOP 2
Programming Screen #2
3-PROTOCOL CLIP
Loop Selection Screen
Loop Selection
Press 1 while viewing the Loop Selection Screen to configure Loop1 or 2 to configure Loop 2. The
following screens will appear for each loop.
LOOP # SETUP
1=STYLE
4
Loop Setup Screen
Style
To program the SLC Style for the selected loop, press 1 for Style, while viewing Loop Setup
Screen. In the preceding example, the control panel is programmed for Style 4 SLC wiring as indi-
cated by the 4 to the right of Style in the display. To change the wiring style, press 1 to toggle the
display to read Style 6. Each press of the 1 key will cause the display to toggle between Style 4 and
Style 6. Note that, when programming the Loop Style, the programmer can only select between
Style 4 and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop
Setup for Style 6. Style 7 wiring is the same as Style 6 with the added requirement that each
addressable device on the loop must have a pair of isolator modules, one on each side.
Note on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for Style
6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the Reset
button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear
the SLC trouble.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
99
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Loop Protocol
Loop Protocol refers to the SLC loop mode of operation. Refer to “Wire Requirements” on
LiteSpeed and CLIP mode. CLIP mode (Classic Loop Interface Protocol) is used for the older leg-
acy addressable devices such as the M300 Series modules and detectors. LiteSpeed mode is used
for newer addressable devices such as the 350 series (or newer) for quicker response times. Note
that the legacy devices can operate only in CLIP mode while the newer devices are compatible with
both modes of operation. Pressing 3 while viewing the Loop Setup Screen will allow the program-
mer to select between CLIP and LiteSpeed mode. Each press of the 3 key will toggle the setting
between CLIP and LiteSpeed mode.
Device Addressing
It is important to note that the FACP addressable device capacity is 159 detectors and 159 con-
trol/monitor modules per SLC loop. Since older legacy addressable devices cannot be set to
addresses above 099, the newer series devices must be used when addresses 100 to 159 are to be
installed. It is permissible to mix old and new devices in the same panel, however, the FACP must
be programmed for CLIP mode.
3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
•
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during
a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will
continue to sound at these rates until the alarm or trouble condition is cleared. If the trouble
condition is not cleared within 24 hours, the panel will reactivate the trouble sounder and
retransmit the trouble condition to the central station if connected.
•
•
•
•
Banner: This option allows the user to change the top line of the LCD display from the blank
factory default readout to a user defined readout when the control panel is in Normal condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr),
date and daylight savings time feature into the FACP memory
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.
NACs: This feature allows the programmer to configure the control panel Notification
Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable,
autosilence, coding, silence inhibit, zone assignment and enable/disable.
•
•
Relays: This option allows programming of two onboard relays for activation by various
control panel events, such as alarm, trouble, supervisory, etc.
Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to “Canadian Option” on page 113).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.
•
Waterflow Silenceable: This option provides the ability to silence any output circuit activated
by a monitor module programmed as a waterflow type.
100
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOPS
SYSTEM SETUP
1=TROUBLE REM OFF
2=BANNER
Programming Screen #2
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
detailed description of this feature. Pressing 1 while viewing System Setup Screen #1 will cause
the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1 key will
cause the display to toggle between Trouble Rem On and Trouble Rem Off.
Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause
the following to be displayed:
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
101
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Pressing 1 while viewing the Banner Screen will select the blank factory default banner setting and
display the following screen:
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
FACTORY BANNER
Factory Banner Screen
Pressing the Enter key will store this selection in nonvolatile memory and return the display to the
Banner Screen.
Pressing 2 while viewing the Banner Screen will display the following screens :
USER DEFINED BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
USER BANNER - LINE 2
PRESS ENTER IF OK
************
User Defined Banner Screen #2
These screens allow the programmer to enter a two line custom banner. A flashing cursor will
appear in the bottom left corner of each display. A maximum of 20 characters (including spaces)
can be entered into each screen for a total of two lines with 40 characters. After entering up to 20
characters in the first screen, press Enter to view the second screen. Enter up to 20 characters in the
second screen in the same manner or just press Enter if a second banner line is not being entered.
To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the
desired character is displayed in the first position. For example, to enter the letter B, press the 2
(ABC) key three times to toggle through the characters 1, A, and B. Press the right arrow key to
move the cursor one position to the right and repeat the process to enter the next character. To enter
a space, press the * (QZ) key four times to place a blank in the desired position. When all charac-
ters have been entered, press Enter to store the information and return to the Banner Screen.
102
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Time-Date
SYSTEM SETUP
1=TROUBLE REM
2=BANNER
The control panel time and date can be changed by pressing 3 while viewing the System Setup
3=TIME-DATE
Screen #1. The following screen will be displayed:
System Setup Screen #1
TIME AND DATE
1=TIME 10:00 AM
2=DATE 02-04-2010
3=CLOCK FORMAT 12HR
Time-Date Screen #1
TIME AND DATE
1=DAYLIGHT SAVINGS
Time-Date Screen #2
Time
To change the time, press 1 while viewing the Time-Date Screen. The following screen will be dis-
played:
ENTER TIME
10:00 AM
1=AM
2=PM
Time Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current time.
To change the time, enter the two-digit hours followed by the two-digit minutes. The cursor will
move one position to the right each time a digit is entered. After the last minutes digit is entered,
the cursor will again move one position to the right. At this point enter 1 for AM or 2 for PM. The
display will then return to the Time-Date Screen which will show the new time entry. If an error is
made while entering a digit, press the CLR key to delete the entire entry and beginning again.
Date
To change the date, press 2 while viewing the Time-Date Screen. The following screen will be dis-
played:
ENTER DATE
MONTH DAY YEAR
02-04-2010
Date Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current date.
To change the date, enter the two-digit month followed by the two-digit day and then the two-digit
year (09 for 2009, 10 for 2010, etc.). The cursor will move one position to the right each time a
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
103
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
digit is entered. After the last year digit is entered, the display will return to the Time-Date Screen
which will show the new date entry. If an error is made while entering a digit, press the CLR key to
delete the entire entry and beginning again.
Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3
while viewing the Time-Date screen will cause the display to toggle between 12HR and 24HR.
Select 12HR for 12 hour display or 24HR for 24 hour display.
NOTE: If the clock is changed to 24 hour (military) format, the date will change to the European
standard of Day-Month-Year (for display purposes only).
Daylight Savings Time
TIME AND DATE
1=DAYLIGHT SAVINGS
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
Time & Date Screen #2
DAYLIGHT SAVINGS
1=ENABLED
YES
2=START MONTH MAR
3=START WEEK WEEK-2
Daylight Savings Screen #1
DAYLIGHT SAVINGS
1=END MONTH NOV
2=END WEEK WEEK-1
Daylight Savings Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the
programmer to select the month that daylight savings time will begin. In this sub-screen, pressing
1 will select March, 2 will select April, and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will begin. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select the
last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the
programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1
will select September, 2 will select October, and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will end. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the
last week of the selected month.
104
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Timers
SYSTEM SETUP
1=TIMERS
2=NAC
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while
3=RELAYS
viewing System Setup Screen #2. The following screen will be displayed:
System Setup Screen #2
TIMERS
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLOW
000
000
000
Timer Screen #1
TIMERS
1=AC LOSS DELAY 000
Timer Screen #2
PAS (Positive Alarm Sequence) Delay
TIMERS
1=PAS DELAY
000
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following dis-
play will appear:
2=PRE SIGNAL 000
3=WATERFLOW
000
Timer Screen #1
PAS DELAY
RANGE 0-180 SECONDS
PAS Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
105
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.
Note that the FACP can be programmed for either PAS or Pre-signal operation, not both. Refer to
“Edit Detector” on page 69 for programming details.
Waterflow Delay
TIMER
1=PAS DELAY
2=PRE SIGNAL 000
000
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:
3=WATERFLOW
000
Timer Screen #1
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.
AC Loss Delay
TIMER
1=AC LOSS DELAY
The reporting of a loss of AC power to a central station can be delayed by programming the length
of the desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2
to display the following:
Timer Screen #2
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss
report immediately to the central station.
106
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following screen:
Programming
AC LOSS DELAY
RANGE 00-23
AC Loss Delay Screen #2
A flashing cursor will appear in the lower left corner of the display. The factory default setting is
02 hours. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When the sec-
ond digit is entered, the display will return to AC Loss Delay Screen #1.
NAC (Notification Appliance Circuit)
SYSTEM SETUP
1=TIMERS
2=NAC
The options for the NACs on the control panel main circuit board can be set by pressing 2 while
3=RELAYS
viewing System Setup Screen #2. The following screens will be displayed:
System Setup Screen #2
NACS
1=NAC 1
2=NAC 2
3=NAC 3
4=NAC 4
NAC Selection Screen
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3, or 4 for NAC 4.
Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC option card is
installed, in JP8 of the main circuit board, for Class B operation.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
107
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
The following screens will be displayed for either selection:
NAC #
1=ENABLED
2=TYPE
YES
BELL
3=SILENCEABLE YES
NAC Screen #1
NAC #
1=AUTO SILENCE 00
2=CODING
TEMPORAL
NAC Screen #2
NAC #
1=ZONE
00 00 00 00 00
2=SIL INHIBITED NO
NAC Screen #3
NAC #
1=SYNC TYPE
S
NAC Screen #4
Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.
108
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Type
NAC #
1=ENABLED
2=TYPE
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1.
The following screen will be displayed. Press the down arrow key to view additional screens:
3=SILENCEABLE
NAC Screen #1
NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1
Select the NAC device type by pressing the number corresponding to the type in the appropriate
screen. When the selection is made, the display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
NAC Type Code
Bell
Special Function
None
Horn
None
Strobe
None
Synced Strobe
Strobe Sil Sync
Future Use
Future Use
Future Use
Blank
Synchronized to manufacturer
Same as Synced Strobe but Silence turns off audible & visual devices
None
None
None
None
Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This
will prevent the selected main circuit board NAC from being silenced by pressing the Alarm
Silence key or by the Auto Silence feature. Each press of the 3 key will cause the display to toggle
between Silenceable Yes and Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for silenceable and the Synced Strobe feature is selected, only the audible devices
will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to
operate. If the Strobe Sil Sync feature is selected, Silence will turn off both audible and visual
devices.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
109
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Auto Silence
NAC #
1=AUTO SILENCE
2=CODING
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following
screens will be displayed:
TEMPORAL
NAC Screen #2
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #3
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. When a time delay is selected, the information will be stored
in memory and the display will return to NAC Screen #2.
Coding
The Coding feature allows the programmer to select the type of output that the main circuit board
notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #2
will cause the following displays to appear:
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
Coding Screen #2
110
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
The programmer can select the notification appliance output by pressing the number corresponding
to the desired output. The coding selections are:
•
•
•
•
•
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off
Two Stage - refer to “Two Stage Operation” on page 111 for description
Selection of one of the above options will cause the control panel to store the information in mem-
ory and return the display to NAC Screen #2, which will display the new coding choice.
Two Stage Operation
Two Stage operation consists of the following:
•
•
1st stage output - 20 ppm (pulse-per-minute) coding
2nd stage output - Temporal coding as described above
If Two Stage operation is programmed as the Coding option, the following sequence of events will
occur during an alarm.
1. The on-board NACs which are programmed to General Alarm Zone 0 will activate with a 1st
stage output upon activation of any alarm point.
2. If the activated alarm point is directly mapped to a zone which is programmed to an on-board
NAC, that NAC will go directly to 2nd stage coding output. All other NACs not directly
mapped to the activated alarm point’s zone but assigned to Zone 0 will activate with a 1st stage
output.
3. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not been pressed,
all NACs presently in 1st stage activation will go to 2nd stage activation.
4. If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation will
remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already in 2nd
stage activation.
5. If another alarm point is activated and the countdown timer is counting, the alarm point will
have no effect on the NACs unless the alarm point’s zones are directly mapped to one of the
NACs, in which case it will follow the procedure outlined in step 2.
6. If another alarm point is activated and the countdown timer has stopped counting due to the
Acknowledge switch being pressed, the countdown timer will restart and the NACs will
respond as outlined in step 2. NACs already in 2nd stage activation will not be affected.
7. Any control modules assigned to special Zone 99 will be activated either by direct mapping of
an input device programmed to Zone 99 or if the timer counts down to zero and the NAC goes
into 2nd stage coding.
8. Control modules that are programmed to the same zone as the activated input device will not
be delayed for activation.
Zone
NAC #
1=ZONE
A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while
viewing NAC Screen #3 displays the following screen:
00 00 00 00 00
2=SIL INHIBITED NO
NAC Screen #3
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Zone Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
111
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Note that Z** represents the Zone Number(s) corresponding to the selected NAC. The factory
default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear
on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned
to this NAC. The cursor moves to the next Z** designation. Continue entering zone assignments
or the remaining zones can be left blank or programmed as general alarm zone Z00. When all
desired changes have been made, press the Enter key to store the zone assignments. The display
will return to the NAC Screen #3 which will show the zone assignments just entered.
Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board
NAC for a period of one minute. Pressing 2 while viewing NAC Screen #3 will cause the display
to change from the factory default of Silence Inhibit No to Silence Inhibit Yes. Each press of the 2
key will cause the display to toggle between the two options.
Synced Type
NAC #
1=SYNC TYPE
If synchronized strobes were selected as the Type of device installed, the type of synchronization
must be selected in this option. Pressing 1 while viewing NAC Screen #4 will cause the following
screen to be displayed:
NAC Screen #4
NAC SYNC TYPE
1=SYSTEM SENSOR
2=WHEELOCK
3=GENTEX
Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select Whee-
lock, and 3 will select Gentex.
Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 3.0 amps. Refer to
the manufacturer’s documentation supplied with the Strobes to determine the maximum current
draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can
be attached to each circuit. Following is a list of the strobes that have been tested with this FACP
and the maximum number that can be connected to each NAC. Make sure that the NAC maximum
current is not exceeded:
• System Sensor: 46 Strobes
• Wheelock: 42 Strobes
• Gentex: 39 Strobes
Relays
SYSTEM SETUP
1=TIMERS
2=NAC
Pressing 3 while viewing System Setup Screen #2 allows the programmer to configure two of the
3=RELAYS
main circuit board Form-C relays from the following screen:
System Setup Screen #2
RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
112
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that
Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The
following screen will appear for each relay to be programmed:
RELAY #
1=TYPE
ALARM
Relay Type Screen
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be dis-
played:
RELAY
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS MON
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
Relay Screen #2
RELAY
RELAY
1=MEDICAL
2=SILENCEABLE ALARM
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #4
Relay Screen #3
While viewing the selected screen, press the number corresponding to the desired relay type to pro-
gram the main circuit board relay. The choice will be stored in memory and the display will return
to the Relay Type Screen which will show the programmed type choice. Press the Escape key to
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Note the following:
1. AR (AutoResettable) in SUPERVISORY AR and PROCESS MON AR means that a relay with
the Supervisory and/or Process Monitor type code, when activated, will automatically reset
when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and
deactivate when the FACP Alarm Silenced LED is illuminated.
Canadian Option
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Cana-
dian requirements. The display will change to Canadian Opt. On. Each press of the 1 key will
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:
System Setup Screen #3
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
Important! For Canadian Applications, this option must be set to ON prior to any other panel pro-
gramming.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
113
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
The Canadian Options configures the FACP with the following as required by Canada:
•
The following monitor module type codes are not available:
• monitor
• non-latching supervisory
• non-latching drill
• non-latching process monitor
• process monitor
• hazard
• tornado
• medical alert
•
•
The auto-silence timer is fixed at 20 minutes and cannot be changed.
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications.
Waterflow Silenceable
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the sys-
tem for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the
display between Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all
output devices associated with a waterflow type input device, will be nonsilenceable. When Water-
flow Sil. Yes is selected, all output devices associated with a waterflow type input device, will be
silenceable.
3.6.6 Verify Loops
PROGRAMMING
1=LOOP SETUP
Pressing 3 while viewing Programming Screen #2, will select the Verify Loops option and display
2=SYSTEM SETUP
3=VERIFY LOOPS
the following screen:
VERIFY LOOPS
1=LOOP 1
2=LOOP 2
Programming Screen #2
3=BOTH LOOPS
Verify Loop Select Screen
During loop verification, the FACP polls each device on the selected SLC to determine if the device
is communicating and whether or not it responds with the proper type identification. The program-
mer can choose to verify one or both loops by pressing the number corresponding to the choices
shown above.
When the selection is made, the following screen will be displayed while verification is in progress:
VERIFYING LOOPS
PLEASE WAIT
Verification Progress Screen
When Loop verification has been completed, the display will indicate that the system is OK or, if
problems have been detected, any device type programming errors. Use the up and down arrow
keys to view all detected errors.
114
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
3.6.7 History
PROGRAMMING
1=HISTORY
2=WALKTEST
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 1 while viewing Programming Screen #3 will display the History options
as shown in the following display:
3=OPTION MODULES
Programming Screen #3
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
View Events
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as
illustrated in the following:
HISTORY
History Screen
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
View Events Screen
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms, or 3 to
view other events. Use the up and down arrow keys to scroll through all of the displayed events.
Erase History
The Erase History option allows a user to erase all events from the history file. This will provide a
clean slate in order to use the history file to track future events. Pressing 2 while viewing the His-
tory Screen will cause the following screen to be displayed:
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. Dur-
ing this process, the display will read as follows:
ERASING HISTORY
PLEASE WAIT
Erase History Wait Screen
After the History file has been erased, the display will return to the History Screen.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
115
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
3.6.8 Walktest
PROGRAMMING
1=HISTORY
2=WALKTEST
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Pressing 2 while viewing the Programming Screen #3 will cause
the following Walktest options to be displayed:
3=OPTION MODULES
Programming Screen #3
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the follow-
ing screen will be displayed::
UNIT IN WALKTEST
1=VIEW WALKTEST LOG
2=VIEW POINTS
3=VIEW SUMMARY
Unit In Walktest Screen
From this screen, it is possible to view the walktest log, untested system points or a summary of the
addressable devices tested during the current walktest. The user can select between any of these
screens without interrupting the current walktest session. The walktest session will not end until
the Unit In Walktest screen is exited by pressing the Escape key.
Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a screen sim-
ilar to one of the following two screens to be displayed:
ALARM: MONITOR
NO EVENTS IN
WALKTEST LOG
NORTH CLASSROOM
Z001
10*15A 020510 1M006
OR
If there are no events in the current walktest session, the first screen will be displayed, indicating no
events have been stored in the walktest log. If any events have been stored, a screen similar to the
second will be displayed indicating the latest event. As walktest events occur, the display will
change to indicate the latest event. All stored events can be scrolled on the screen by pressing the
up or down arrow keys. To return to the first event, press the 1st Event key.
116
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
Pressing 2 for View Points while viewing the Unit In Walktest screen will display one of the follow-
ing screens:
UNTESTED POINTS 010
NO POINTS IN
SYSTEM
1D001 SMOKE (PHOTO)
*********************
NOT TESTED
OR
If the system has no points installed, the first screen will be displayed. If points are installed, the
second screen will be displayed, which allows the viewing of all untested system points and their
status relating to the current walktest session. The up and down arrow keys will allow viewing of
all untested points. If a point is tested while it is being displayed, the screen will update and display
the next untested point. The first line indicates the total number of untested points. The second line
displays information about an untested point. A description on the bottom of the screen will indi-
cate if the displayed point has been disabled, if the Walktest option has been disabled for that point
or if the point is not yet tested. The up and down arrow keys allow the user to scroll through all
untested points.
Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a new screen
which will show a total of the tested detectors, tested modules, untested detectors and untested
modules for the current walktest session. If more than one SLC loop is installed on the FACP,
pressing the down arrow key will display the Walktest summary for each SLC loop.
The user can perform a one-person walktest by activating devices throughout the system. As each
device is activated, the information about the activated device is stored in the Walktest Log. The
information can be viewed by choosing one of the options from the Unit In Walktest screen.
To end the Walktest session, press the Escape key to return to the Walktest screen. Pressing 3 for
View Results while viewing the Walktest screen, after a walktest session has been completed, will
allow the operator to view the final results of the most recent walktest. The following screen will
be displayed:
WALKTEST RESULTS
View Result Screen
Use the up and down arrow keys to view all of the walktest results which will be displayed. Note
that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the
Walktest log information will be lost. This information is also overwritten when subsequent walk-
tests are performed.
3.6.9 Option Modules
PROGRAMMING
1=HISTORY
2=WALKTEST
Options available for the FACP include ACS, Graphic, LED, Relay and LCD annunciators, printer
connection for acquiring hardcopy printouts of panel data and PC (Personal Computer) connection
for uploading and downloading panel data.
3=OPTION MODULES
Programming Screen #3
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
117
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Pressing 3 while viewing Programming Screen #3 will display the following screen:
OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ONBOARD DACT
3=PRINTER/PC PR4800
Options Screen
Note that PR4800 in the display indicates that a supervised printer, configured for 4800 baud, has
been previously programmed into the system.
Annunciators/UDACT
Pressing 1 while viewing the Options Screen will cause the control panel to display the following
screens:
ANNUNCIATORS
1=TERM ENABLED
2=ACS OPTIONS
3=ANN-BUS OPTIONS
NO
Annunciator Screen
A Terminal Mode annunciator, ACS Mode annunciator or ANN-BUS annunciator/module can be
installed in the system. Do not use a mix of ACS annunciators and ANN annunciators since they
use different communication protocols. ACS or ANN annunciators use the same TB6 terminal
block connection. To install any of these devices, press the number corresponding to the desired
device shown in the Annunciator Screen.
Term Options
While viewing the Annunciators Screen, each press of the 1 key for Term Options, will cause the
display to toggle between Term Enabled No and Term Enabled Yes.
NOTE: The LCD-80F is a Terminal Mode annunciator. To enable the FACP for LCD-80F
operation, press 1 for Term Enabled Yes.
118
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
ACS Options
Programming
ANNUNCIATORS
1=TERM OPTIONS
2=ACS OPTIONS
Pressing 2 for ACS Options while viewing the Annunciators screen, will display the following
screen:
3=ANN-BUS OPTIONS
Annunciator Screen
ACS OPTIONS
1=ACS ENABLED
2=ACS INSTALLED
3=UDACT
NO
NO
Pressing 1 while viewing the ACS Options screen will cause the display to toggle between ACS
Enabled Yes and ACS Enabled No. To install an ACS annunciator, the display must read ACS
Enabled Yes.
If ACS has been enabled, press 2 while viewing the ACS Options screen to select addresses for the
ACS annunciators. The following screen will be displayed:
ANNUNCIATOR
1=ADDRESS 1
2=ADDRESS 2
3=ADDRESS 3
YES
NO
NO
ACS Installed Screen
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 -31. Each screen will indicate if an address has been used for an installed ACS annun-
ciator. To select one or more addresses for the installed ACS annunciator(s), press the number key
corresponding to the address in each screen. The display for the selected address will change from
No to Yes. Each press of the number key will cause the display to toggle between No and Yes. The
address of each installed annunciator must be enabled to allow communication between the FACP
and annunciator.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
119
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Annunciator addressing is specific to the FACP control panel. The following table describes the
annunciator addresses and the corresponding addressable devices that will be annunciated at each
annunciator address.
ACS Annunciator Address
Annunciator Displays the Following Points
8 General System Status Points & Zones 1 - 56
Zones 57 - 99 & 4 NACs
1
2
3
Loop 1, Module Addresses 1 - 64
Loop 2, Module Addresses 1 - 64
Loop 1, Module Addresses 65 - 128
Loop 2, Module Addresses 65 - 128
Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159
Loop 1, Detector Addresses 1 - 64
Loop 2, Detector Addresses 1 - 64
Loop 1, Detector Addresses 65 - 128
Loop 2, Detector Addresses 65 - 128
Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159
not used
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
not used
not used
not used
not used
not used
not used
8 General System Status Points & Zones 1 - 56
Zones 57 - 99 & 4 NACs
Loop 1, Module Addresses 1 - 64
Loop 2, Module Addresses 1 - 64
Loop 1, Module Addresses 65 - 128
Loop 2, Module Addresses 65 - 128
Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159
Loop 1, Detector Addresses 1 - 64
Loop 2, Detector Addresses 1 - 64
Loop 1, Detector Addresses 65 - 128
Loop 2, Detector Addresses 65 - 128
Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159
not used
The 8 General System Status Points include the following:
•
•
•
•
•
•
•
•
General Alarm
General Trouble
General Supervisory
Alarm Silenced
System Off Normal
AC Loss
Battery Fault
NAC Fault
Pressing 3 while viewing the ACS Options screen will toggle the display between UDACT NO and
UDACT YES. This allows the connection of an external UDACT (Universal Digital Alarm Com-
municator/Transmitter).
120
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
ANN-BUS Options
Programming
ANNUNCIATORS
1=TERM OPTIONS
2=ACS OPTIONS
Pressing 3 for ANN-BUS Options, while viewing the Annunciators screen, will cause the following
screens to be displayed:.
3=ANN-BUS OPTIONS
Annunciator Screen
ANN-BUS
1=ENABLED
NO
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
ANN-BUS Screen #2
A printer module, graphic annunciator module, LCD annunciator module, LED annunciator mod-
ule and relay module can be programmed into the system. These devices communicate with the
FACP over the ANN-BUS terminals on the control panel.
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads
Enabled Yes. Each press of the 1 key will cause the display to toggle between Enabled Yes and
Enabled No.
Modules Installed
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN-
BUS addresses for the module(s). The following screen will be displayed.
ANN-BUS MODULES
1=ADDR. 1 NONE
2=ADDR. 2 NONE
3=ADDR. 3 NONE
ANN-BUS Modules Screen #1
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1-8. To program an ANN-BUS module to a specific address, press the number key cor-
responding to the desired address in each screen. The following screen will be displayed for each
address:
ANN-BUS MODULES
ANN-BUS ADDRESS #
1=TYPE
NONE
ANN-BUS Address Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
121
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
Pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80 MODULE
3=ANN-I/O MODULE
Module Type Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG MODULE
2=ANN-LED MODULE
3=ANN-RLY MODULE
Module Type Screen #2
ANN-BUS MODULE TYPE
1=ANN-AUDIO
Module Type Screen #3
Press the number corresponding to the module type that is installed with the selected address.
NOTE: If the module type selected is the ANN-80, ANN-S/PG, or ANN-AUDIO or if Not Installed
is selected, the ANN-BUS Address Screen shown on the previous page will be displayed following
the module selection. The options selected for each of these modules will be the same for all
modules of the same type (refer to “ANN-S/PG (Print) Options” on page 132 and “ANN-80
Options” on page 133).
If ANN-I/O, ANN-LED or ANN-RLY is the selected module type, the following ANN-BUS
Address Screen will be displayed:
ANN-BUS MODULES
ANN-BUS ADDRESS #
1=TYPE ANN-I/O
2=MODULE OPTIONS
ANN-BUS Address Screen
Since the options for each of these module types can be individually set, pressing 2 for Module
Options, while viewing the ANN-BUS Address Screen will display the available options as
described below.
122
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
ANN-I/O Options
Programming
Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-I/O
option is selected will display the following screen:
ANN-I/O ADDR #
SLC 1 MOD 001-030
ACTIVE LEDS ONLY
ANN-I/O Address Screen #1
ANN-I/O ADDR #
1=POINT/ZONE POINT
ANN-I/O Address Screen #2
ANN-I/O ADDR #
1=RANGE
2=DET/MOD
3=SLC LOOP #
PT001-030
MOD
2
ANN-I/O Address Screen #3
The first screen indicates that the ANN-I/O at the selected ANN-BUS address is programmed to
annunciate SLC Loop #1 addressable modules with addresses 1 through 30. The programming can
be changed using ANN-I/O Address Screens 2 and 3.
Pressing 1 while viewing ANN-I/O Address Screen #2 will program the annunciator module to
annunciate either Point (addressable device address) information or Zone information.
Pressing 1 while viewing ANN-I/O Address Screen #3 will select the Point or Zone range to be
annunciated (refer to the tables in “ANN-I/O Zone Option” on page 123 and “ANN-I/O Point
Option” on page 125).
Pressing 2 while viewing ANN-I/O Address Screen #3 will select either addressable detectors or
addressable modules to be annunciated.
Pressing 3 while viewing ANN-I/O Address Screen #3 will select the SLC loop with the address-
able devices to be annunciated.
ANN-I/O Zone Option
If Zone is selected as the module option, the first ten LEDs on the first ANN-I/O module will dis-
play the system status information. The remaining 30 LEDs on the first module and 40 LEDs on
the remaining modules will display the active/alarm status of each zone in the Zone Range pro-
grammed for that particular module. The LED assignments for each ANN-I/O module will be as
follows.
ANN-I/O Module #1
Function
ANN-I/O Module #2
Function
ANN-I/O Module #3
Function
Module LED
1
2
3
AC Fault
Fire Alarm
Supervisory
Zone 30
Zone 31
Zone 32
Zone 70
Zone 71
Zone 72
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
123
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
4
Trouble
Alarm Silenced
Earth Fault
Battery Fault
Charger Fault
NAC Fault
Disabled
Zone 00
Zone 01
Zone 02
Zone 03
Zone 04
Zone 05
Zone 06
Zone 07
Zone 08
Zone 09
Zone 10
Zone 11
Zone 33
Zone 34
Zone 35
Zone 36
Zone 37
Zone 38
Zone 39
Zone 40
Zone 41
Zone 42
Zone 43
Zone 44
Zone 45
Zone 46
Zone 47
Zone 48
Zone 49
Zone 50
Zone 51
Zone 52
Zone 53
Zone 54
Zone 55
Zone 56
Zone 57
Zone 58
Zone 59
Zone 60
Zone 61
Zone 62
Zone 63
Zone 64
Zone 65
Zone 66
Zone 67
Zone 68
Zone 69
Zone 73
Zone 74
Zone 75
Zone 76
Zone 77
Zone 78
Zone 79
Zone 80
Zone 81
Zone 82
Zone 83
Zone 84
Zone 85
Zone 86
Zone 87
Zone 88
Zone 89
Zone 90
Zone 91
Zone 92
Zone 93
Zone 94
Zone 95
Zone 96
Zone 97
Zone 98
Zone 99
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Zone 20
Zone 21
Zone 22
Zone 23
Zone 24
Zone 25
Zone 26
Zone 27
Zone 28
Zone 29
124
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
ANN-I/O Point Option
Programming
If Point is selected as the module option, the first ten LEDs on the first ANN-I/O module will
display the system status information. The remaining 30 LEDs on the first module and 40 LEDs on
each additional module will display the active/alarm status of each point in the Point Range
programmed for that particular module. The points that will be annunciated on a particular ANN-
I/O module depend on the programming options selected as far as which SLC loop and the device
type (detector or module) to be annunciated. The LED assignments for each ANN-I/O module will
be as follows.
ANN-I/O
Module #1
Function
ANN-I/O
Module #2
Function
ANN-I/O
Module #3
Function
ANN-I/O
Module #4
Function
ANN-I/O
Module #5
Function
Module LED
1
AC Fault
Fire Alarm
Supervisory
Trouble
Point 31
Point 32
Point 33
Point 34
Point 35
Point 36
Point 37
Point 38
Point 39
Point 40
Point 41
Point 42
Point 43
Point 44
Point 45
Point 46
Point 47
Point 48
Point 49
Point 50
Point 51
Point 52
Point 53
Point 54
Point 55
Point 56
Point 57
Point 58
Point 59
Point 60
Point 61
Point 62
Point 63
Point 64
Point 65
Point 66
Point 67
Point 68
Point 69
Point 70
Point 71
Point 72
Point 73
Point 74
Point 75
Point 76
Point 77
Point 78
Point 79
Point 80
Point 81
Point 82
Point 83
Point 84
Point 85
Point 86
Point 87
Point 88
Point 89
Point 90
Point 91
Point 92
Point 93
Point 94
Point 95
Point 96
Point 97
Point 98
Point 99
Point 100
Point 101
Point 102
Point 103
Point 104
Point 105
Point 106
Point 107
Point 108
Point 109
Point 110
Point 111
Point 112
Point 113
Point 114
Point 115
Point 116
Point 117
Point 118
Point 119
Point 120
Point 121
Point 122
Point 123
Point 124
Point 125
Point 126
Point 127
Point 128
Point 129
Point 130
Point 131
Point 132
Point 133
Point 134
Point 135
Point 136
Point 137
Point 138
Point 139
Point 140
Point 141
Point 142
Point 143
Point 144
Point 145
Point 146
Point 147
Point 148
Point 149
Point 150
Point 151
Point 152
Point 153
Point 154
Point 155
Point 156
Point 157
Point 158
Point 159
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
2
3
4
5
Alarm Silenced
Earth Fault
Battery Fault
Charger Fault
NAC Fault
Disabled
Point 01
Point 02
Point 03
Point 04
Point 05
Point 06
Point 07
Point 08
Point 09
Point 10
Point 11
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Point 12
Point 13
Point 14
Point 15
Point 16
Point 17
Point 18
Point 19
Point 20
Point 21
Point 22
Point 23
Point 24
Point 25
Point 26
Point 27
Point 28
Point 29
Point 30
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
125
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
ANN-LED Options
Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-LED
option is selected will display the following screen:
ANN-LED ADDR #
LOOP1 DET 1-10
ALARM,SUPERV,TBL
ANN-LED Address Screen #1
ANN-LED ADDR #
1=POINT/ZONE
2=ALARM/ATS
ANN-LED Address Screen #2
ANN-LED ADDR #
1=RANGE
2=DET/MOD
3=LOOP#
ANN-LED Address Screen #3
The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed to
annunciate Alarms, Supervisories and Troubles for SLC Loop #1 addressable Detectors with
addresses 1 through 10. The programming can be changed using ANN-LED Address Screens 2
and 3.
Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate either Point (addressable device address) information or Zone information.
Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate only Alarms for addressable device addresses 1-30 or Alarms, Supervisories and Trou-
bles for addressable device addresses 1-10.
Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be
annunciated (refer to the tables in “ANN-LED Zone Option - Alarm Only (for use with ANN-
Pressing 2 while viewing ANN-LED Address Screen #3 will select either addressable detectors or
addressable modules to be annunciated.
Pressing 3 while viewing ANN-LED Address Screen #3 will select the SLC loop with the address-
able devices to be annunciated.
126
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
ANN-LED Zone Option - Alarm Only (for use with ANN-RLED module)
Programming
If Zone is selected as the module option, and the module is programmed to annunciate alarms only,
the first ten LEDs on the first ANN-LED module will display the system status information. The
remaining 30 LEDs on the first module and the last 30 LEDs on the remaining modules will display
the active/alarm status of each zone in the Zone Range programmed for that particular module. The
LED assignments for each ANN-LED module will be as follows.
Alarm Silenced
Earth Fault
NAC 1 Fault
Battery Fault
NAC 2 Fault
NAC 3 Fault
Disabled
NAC 4 Fault
Maintenance
Charger Fault
Zone 00
Zone 01
Zone 02
Zone 03
Zone 04
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 05
Zone 06
Zone 07
Zone 08
Zone 09
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Active/Alarm
Active/Alarm
Active/Alarm
Active Alarm
Active/Alarm
Zone 20
Zone 21
Zone 22
Zone 23
Zone 24
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 25
Zone 26
Zone 27
Zone 28
Zone 29
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
ANN-RLED Module #1
Not Used
Not Used
Not Used
Not Used
Zone 31
Not Used
Not Used
Zone 32
Not Used
Not Used
Not Used
Not Used
Zone 30
Zone 33
Zone 34
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 35
Zone 36
Zone 37
Zone 38
Zone 39
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 40
Zone 41
Zone 42
Zone 43
Zone 44
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 45
Zone 46
Zone 47
Zone 48
Zone 49
Active/Alarm
Active/Alarm
Active/Alarm
Active Alarm
Active/Alarm
Zone 50
Zone 51
Zone 52
Zone 53
Zone 54
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 55
Zone 56
Zone 57
Zone 58
Zone 59
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
ANN-RLED Module #2
The LED assignments for the modules annunciating Zone Ranges 60 - 89 and 90 - 99, will follow
the same pattern as the second ANN-RLED module.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
127
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
ANN-LED Zone Option - Alarm, Trouble and Supervisory
If Zone is selected as the module option, and the module is programmed to annunciate alarms,
troubles and supervisories, the first ten LEDs on the first ANN-LED module will display the sys-
tem status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the
remaining modules will display the alarm, trouble and supervisory status for each of the ten zones
in the Zone Range programmed for that particular module. The LED assignments for each ANN-
LED module will be as follows.
Alarm Silenced
Earth Fault
NAC 1 Fault
Battery Fault
NAC 2 Fault
NAC 3 Fault
Disabled
NAC 4 Fault
Maintenance
Charger Fault
Zone 00
Zone 01
Zone 02
Zone 03
Zone 04
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 00
Trouble
Zone 01
Trouble
Zone 02
Trouble
Zone 03
Trouble
Zone 04
Trouble
Zone 00
Zone 01
Zone 02
Zone 13
Zone 04
Supervisory
Supervisory
Supervisory
Supervisory
Supervisory
Zone 05
Zone 06
Zone 07
Zone 08
Zone 09
Active/Alarm
Active/Alarm
Active/Alarm
Active Alarm
Active/Alarm
Zone 05
Trouble
Zone 06
Trouble
Zone 07
Trouble
Zone 08
Trouble
Zone 09
Trouble
Zone 05
Zone 06
Zone 07
Zone 08
Zone 09
Supervisory
Supervisory
Supervisory
Supervisory
Supervisory
ANN-LED Module #1
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 10
Trouble
Zone 11
Trouble
Zone 12
Trouble
Zone 13
Trouble
Zone 14
Trouble
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Supervisory
Supervisory
Supervisory
Supervisory
Supervisory
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Zone 15
Trouble
Zone 16
Trouble
Zone 17
Trouble
Zone 18
Trouble
Zone 19
Trouble
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Supervisory
Supervisory
Supervisory
Supervisory
Supervisory
ANN-LED Module #2
The LED assignments for the modules annunciating Zone Ranges 20 - 29, 30 - 39, 40 - 49, 50 - 59,
60 - 69, 70 - 79, 80 - 89 and 90 - 99, will follow the same pattern as the second ANN-LED module.
128
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
ANN-LED Point Option - Alarm Only (for use with ANN-RLED module)
Programming
If Point is selected as the module option and the module is programmed to annunciate alarms only,
the first ten LEDs on the first ANN-LED module will display the system status information. The
remaining 30 LEDs on the first module and the last 30 LEDs on each additional module will dis-
play the active/alarm status of each point in the Point Range programmed for that particular mod-
ule. The points that will be annunciated on a particular ANN-LED module depend on the
programming options selected as far a which SLC loop and the device type (detector or module) to
be annunciated. The LED assignments for each ANN-LED module will be as follows.
Alarm Silenced
Earth Fault
NAC 1 Fault
Battery Fault
NAC 2 Fault
NAC 3 Fault
Disabled
NAC 4 Fault
Maintenance
Charger Fault
Point 01
Point 02
Point 03
Point 04
Point 05
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 06
Point 07
Point 08
Point 09
Point 10
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 11
Point 12
Point 13
Point 14
Point 15
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 16
Point 17
Point 18
Point 19
Point 20
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 21
Point 22
Point 23
Point 24
Point 25
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 26
Point 27
Point 28
Point 29
Point 30
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
ANN-RLED Module #1 (Point Range 01 - 30)
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Point 31
Point 32
Point 33
Point 34
Point 35
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 36
Point 37
Point 38
Point 39
Point 40
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 41
Point 42
Point 43
Point 44
Point 45
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 46
Point 47
Point 48
Point 49
Point 50
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 51
Point 52
Point 53
Point 64
Point 55
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 56
Point 57
Point 58
Point 59
Point 60
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
ANN-RLED Module #2 (Point Range 31 - 60)
The LED assignments for the modules annunciating Point Ranges 61 - 90, 91 - 120, 121 - 150, and
151 - 159, will follow the same pattern as the second ANN-RLED module.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
129
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
ANN-LED Point Option - Alarm, Trouble and Supervisory
If Point is selected as the module option, and the module is programmed to annunciate alarms,
troubles and supervisories, the first ten LEDs on the first ANN-LED module will display the sys-
tem status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the
remaining modules will display the alarm, trouble and supervisory status for each of the ten zones
in the Point Range programmed for that particular module. The LED assignments for each ANN-
LED module will be as follows.
Alarm Silenced
Earth Fault
NAC 1 Fault
Battery Fault
NAC 2 Fault
NAC 3 Fault
Disabled
NAC 4 Fault
Maintenance
Charger Fault
Point 01
Point 02
Point 03
Point 04
Point 05
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 01
Trouble
Point 02
Trouble
Point 03
Trouble
Point 04
Trouble
Point 05
Trouble
Point 01
Point 02
Point 03
Point 04
Point 05
Supervisory
Supervisory
Supervisory
Supervisory
Supervisory
Point 06
Point 07
Point 08
Point 09
Point 10
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 06
Trouble
Point 07
Trouble
Point 08
Trouble
Point 09
Trouble
Point 10
Trouble
Point 06
Point 07
Point 08
Point 09
Point 10
Supervisory
Supervisory
Supervisory
Supervisory
Supervisory
ANN-LED Module #1 (Point Range 01 - 10)
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Point 11
Point 12
Point 13
Point 14
Point 15
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 11
Trouble
Point 12
Trouble
Point 13
Trouble
Point 14
Trouble
Point 15
Trouble
Point 11
Point 12
Point 13
Point 14
Point 15
Supervisory
Supervisory
Supervisory
Supervisory
Supervisory
Point 16
Point 17
Point 18
Point 19
Point 20
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Active/Alarm
Point 16
Trouble
Point 17
Trouble
Point 18
Trouble
Point 19
Trouble
Point 20
Trouble
Point 16
Point 17
Point 18
Point 19
Point 20
Supervisory
Supervisory
Supervisory
Supervisory
Supervisory
ANN-LED Module #2 (Point Range 11 - 20)
The LED assignments for the modules annunciating Point Ranges 21 - 30, 31 - 40 and 41 - 50, 51 -
60, 61 - 70, 71 - 80, 81 - 90, 91 - 100, 101 - 110, 111, 120, 121 - 130, 131 - 140, 141 - 150 and
151 - 159, will follow the same pattern as the second ANN-LED Module.
130
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
ANN-RLY Options
Programming
Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-RLY
option is selected will cause the following screen to be displayed:
ANN-RLY - ADDR. #
1=RELAY 1
2=RELAY 2
3=RELAY 3
ZONE 00
ZONE 01
ZONE 02
ANN-RLY Options Screen
The ANN-RLY module provides ten Form-C relays which can be programmed for various func-
tions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will display the
remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen,
press the number key corresponding to the relay to be programmed. Following is a list of the avail-
able programming options for each relay:
•
•
•
•
•
•
•
•
•
•
•
•
Alarm
Supervisory
Supervisory AR
Trouble
Comm Fail
Process Mon
Process Mon AR
AC Loss
Hazard
Medical
Silenceable Alarm
Zone Active XX
Auto-Configure
ANN-BUS
1=ANN ENABLED
2=OPTIONS INSTALLED
3=AUTO-CONFIGURE
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and automatically
program the device type and address into the system. The ANN-BUS must be enabled for the Auto-
Configure feature to work.
ANN-BUS Screen #1
Pressing 3 while viewing ANN-BUS Screen #1 will begin the Auto-Configure process and cause
the following screen to be displayed:
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
131
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
ANN-S/PG (Print) Options
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
The Print option allows the programmer to configure the optional printer. Pressing 1 while viewing
ANN-BUS screen #2 will display the following screens:
ANN-BUS Screen #2
ANN-S/PG OPTIONS
1=PORT
PAR
2=PRINTER SUPV NO
3=OFFLINE TIMER 60
ANN-S/PG Options Screen #1
ANN-S/PG OPTIONS
1=BAUD RATE
2=DATA BITS
3=PARITY
N/A
N/A
N/A
ANN-S/PG Options Screen #2
ANN-S/PG OPTIONS
1=STOP BITS
N/A
ANN-S/PG Options Screen #3
Pressing 1 for Port while viewing ANN-S/PG Options screen #1 will allow the programmer to
select between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause
the display to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that
the interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select an
offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print Options
screen #1. Each press of the 2 key will cause the display to toggle between Printer Supv NO for no
supervision and Printer Supv YES for printer supervision. Note that this option is not selectable if
the Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an Offline Timer by pressing
3 while viewing Print Options screen #1. The resultant screen allows the programmer to program
the Offline Timer for a delay of between 0 and 255 seconds before loss of printer supervision is
reported as a trouble.
If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be available.
The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the Serial Port
option has been selected.
Pressing 1 for Baud Rate while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of 19200, 9600, or 2400.
Pressing 2 for Data Bits while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allows the user to select 7 or 8 Data Bits.
Pressing 3 for Parity while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allows the user to select between No Parity, Even Parity, or Odd Parity.
Pressing 1 for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to appear
which allows the user to select between 1.0 or 2.0 Stop Bits.
132
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
ANN-80 Options
Programming
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
Pressing 2 while viewing ANN-BUS screen #2 will display the following screen:
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-BUS Screen #2
ANN-80 Options Screen #1
ANN-80 OPTIONS
1=SIL BTN ENABLE
2=RST BTN ENABLE
3=DRL BTN ENABLE
ANN-80 Options Screen #2
The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options Screen
#1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not any installed ANN-80
annunciator must be unlocked by its key before any annunciator key presses will function. Pressing
2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Lock Enable
Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock position is
ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 annunciator will function normally or
always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display to
toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No
(Ack/Step button never functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the
Silence button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Sil
Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence button never
functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the
Reset button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Rst
Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never func-
tions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the
Drill button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Drl
Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never func-
tions).
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
133
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
On Board DACT
OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ON BOARD DACT
The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a
Central Station. Pressing 2 while viewing the Option Module Screen will allow programming of
the Onboard DACT. Refer to the DACT-UD2 Installation and Programming Manual Document
#53037 for detailed information on installing and programming this option.
3=PRINTER/PC
NO
Option Module Screen
Printer/PC
A Printer or a PC can be connected to the control panel. Pressing 3 while viewing the Option Mod-
ule Screen will cause the following screen to appear:
PRINTER-PC
1=PRINTER NO SU NO
2=PRINTER SU YES
3=PC
NO
Printer-PC Screen
Pressing 1 while viewing the Printer-PC Screen will program the control panel for an unsupervised
(NO SU) printer. The display will change to the Printer Baud Rate Screen as shown below.
Pressing 2 while viewing the Printer-PC Screen will program the control panel for a supervised
(SU) printer. Printer supervision, when enabled, will typically detect the removal of the printer
cable and will detect when the printer power has been turned off. Depending upon the brand of
printer, other errors such as paper empty or printer off-line may be detected.
Enabling either printer option will cause the following screen to appear, which allows the program-
mer to select the baud rate for the printer communication:
PRINTER BAUD RATE
1=2400 BAUD
2=4800 BAUD
3=9600 BAUD
Printer Baud Rate Screen
Pressing the number key corresponding to the desired baud rate (2 for 4800 Baud for example) will
program the control panel for the selected baud rate and return the display to the Option Module
Screen which will indicate Printer/PC PR4800 for a supervised printer installed at 4800 baud rate.
Pressing 3 while viewing the Printer-PC Screen will program the control panel for a PC connection.
The display will return to the Option Module Screen which will indicate Printer/PC PC for per-
sonal computer installed.
134
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
3.6.10 Password Change
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing 1 while viewing Programming Screen #4 will
cause the following screen to be displayed:
Programming Screen #4
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
3=REMOTE DOWNLOAD
Password Change Screen
Press 1 to change the Master Programming Level password, 2 to change the Maintenance Level
password, or 3 to change the Remote Download password. Note that the passwords will not be dis-
played on LCD annunciators.
The following screen will appear when either change option is selected:
ENTER NEW FIVE DIGIT
PASSWORD
Enter Password Screen
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
VERIFY NEW
PASSWORD
Password Change Screen
Re-enter the new password to accept the change. The display will return to the initial Password
Change Screen.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
135
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Master Programming Level
3.6.11 Clear Program
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Pressing 2 while viewing Programming Screen #4, will select the Clear Program option. This will
cause the LCD to display the following screens:
Programming Screen #4
CLEAR PROGRAM
1=WHOLE SYSTEM
2=ALL LOOPS
3=LOOP1
Clear Program Screen #1
CLEAR PROGRAM
1=LOOP2
Clear Program Screen #2
Pressing 1, for Whole System while viewing the Clear Program Screen #1, will clear all general
system programming options and all programmed addressable devices from the nonvolatile mem-
ory of the FACP. This function is useful when the control panel is first installed, prior to autopro-
gramming. Note that it is necessary to autoprogram after using the Clear Whole System function.
Pressing 2, for All Loops while viewing the Clear Program Screen #1, will clear all programming
related to all SLC loops and connected addressable devices.
Pressing 3, for Loop 1 while viewing the Clear Program Screen #1, will clear only the program-
ming related to SLC Loop 1 and the connected addressable devices.
Pressing 1, for Loop 2 while viewing the Clear Program Screen #2, will clear only the program-
ming related to SLC Loop 2 and the connected addressable devices.
Before executing any of the Clear commands listed above, the control panel will provide a warning
to the user by prompting with the following display:
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES
2=NO
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will pre-
vent programming from being cleared.
136
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Master Programming Level
Programming
3.6.12 Program Check
PROGRAMMING
The Program Check feature allows the programmer to view the zones which have been pro-
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
grammed to the Notification Appliance Circuits on the control panel but have not been pro-
grammed to Initiating Devices as well as other circuits with no input or output correlations.
Pressing 3 while viewing Programming Screen #4 will cause the following screen to be displayed:
Programming Screen #4
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Pressing 1 while viewing the Program Check screen will display an NAC screen similar to the fol-
lowing.
Program Check Screen
NACS NO INPUT
NAC 1
25 31 44 55 67
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for NAC 1, NAC 2, NAC 3, and NAC 4.
NOTE: If the NACs have been configured for Class Ain the setup option, only NAC1 and NAC2 will
display test information. NAC3 and NAC4 will display asterisks (*) and will not be included in the test.
Pressing 2 while viewing the Program Check screen will display a screen similar to the following:
ZONES NO INPUT
05 07 09 10 11 1M001
The Zone No Input screen allows the programmer to view the zones which have not been pro-
grammed to at least one input device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able module (control module in this example) with an address of 001 on loop 1 but have not been
programmed to any input devices. Use the up and down arrow keys to view all the zones without
input assignments.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
137
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Maintenance Programming Level
Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be
displayed:
ZONES NO OUTPUT
05 07 09 10 11 1D001
The Zone No Output feature allows the programmer to view the zones which have not been pro-
grammed to at least one output device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able detector with an address of 001 on loop 1 but have not been programmed to any output
devices. Use the up and down arrow keys to view all the zones without output assignments.
3.7 Maintenance Programming Level
To access Maintenance Programming mode, press the Enter key. The LCD will display the follow-
ing:
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
To enter the Maintenance Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
When the Maintenance level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
138
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Programming Level
Programming
Note that in the preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key, as shown in the following screen.
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
3.7.1 Disable Point
Pressing 1 for Point Program, while viewing Maintenance Screen #1 will cause the following
screens to be displayed:
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
POINT PROGRAM
1=LOOP 1
2=LOOP 2
Maintenance Screen #1
Loop Select Screen
Select the Loop, containing the device to be disabled, by pressing 1 for Loop 1 or 2 for Loop 2. A
screen will then be displayed, allowing the operator to select the type of addressable device to be
disabled as shown in the following display:
POINT PROGRAM
1=DETECTOR
2=MODULE
Device Select Screen
Select the device type by pressing 1 for an addressable detector or 2 for an addressable module.
The operator will be prompted to enter the three digit device address as shown in the following
example for a detector:
EDIT DETECTOR
ENTER POINT ADDRESS
***
Address Select Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
139
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Maintenance Programming Level
A flashing cursor will appear in the bottom left corner of the display, prompting for the three digit
device address. When the third digit is enter, 001 for example, a screen will appear which will
allow enabling or disabling of the selected point, as illustrated in the following example:
EDIT DETECTOR 1D001
1=ENABLED
YES
Enable/Disable Select Screen
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.
3.7.2 History
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
Pressing 2 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
3=PROGRAM CHECK
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
Maintenance Screen #1
History Screen
The History feature allows the operator to view control panel events which have been stored in a
history file in memory and erase the contents of the history file
Pressing 1 while viewing the History screen will cause the following screen to be displayed:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
Events Screen
To view all the events which have occurred in the control panel since the history file was last
erased, press 1 while viewing the Events screen. To view only alarms which have occurred, press 2
while viewing the Events screen. To view events other than alarms, press 3. The most recent event
will be displayed on the screen. To view all of the selected events, press the up or down arrow keys
to scroll through the list of events. If no events have occurred, the display will read NO EVENTS
IN HISTORY.
140
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Programming Level
Programming
Pressing 2 while viewing the History Screen will cause the following screen to be displayed:
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY,
PLEASE WAIT to be displayed. The display will then return to the History Screen. Pressing 2 will
cause the display to return to the History Screen without erasing the History file.
3.7.3 Program Check
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
3=PROGRAM CHECK
PROGRAM CHECK
1=NACS NO INPUT
Maintenance Screen #1
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen
The Program Check feature allows the programmer to view the zones which have been pro-
grammed to the Notification Appliance Circuits on the control panel but have not been pro-
grammed to Initiating Devices as well as other circuits with no input or output correlations.
Pressing 1 while viewing Program Check screen will cause a screen similar to the following to be
displayed.
NACS NO INPUT
NAC 1
25 31 44 55 67
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55, and 67 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for NAC1, NAC2, NAC3, and NAC4.
NOTE: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC2 will
display test information. NAC3 and NAC4 will display asterisks (*) and will not be included in the test.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
141
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Maintenance Programming Level
Pressing 2 while viewing the Program Check screen will display a screen similar to the following:
ZONES NO INPUT
05 07 09 10 11 1M001
The Zone No Input screen allows the programmer to view the zones which have not been pro-
grammed to at least one input device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able module (control module in this example) with an address of 001 on loop 1 but have not been
programmed to any input devices. Use the up and down arrow keys to view all the zones without
input assignments.
Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be
displayed:
ZONES NO OUTPUT
05 07 09 10 11 1D001
The Zone No Output feature allows the programmer to view the zones which have not been pro-
grammed to at least one output device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able detector with an address of 001 on loop 1 but have not been programmed to any output
devices. Use the up and down arrow keys to view all the zones without output assignments.
3.7.4 Walktest
PROGRAMMING
1=WALKTEST
2=SYSTEM
To perform a walktest, press 1 while viewing Maintenance Screen #2. The following screen will be
displayed:
3=ZONE SETUP
Maintenance Screen #2
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The dis-
play will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the
walktest.
142
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Programming Level
Programming
3.7.5 System
To program the time and date into the control panel, press 2 while viewing Maintenance Screen #2.
The following display will appear:
SYSTEMS
1=TIME/DATE
System Screen
Pressing 1 while viewing the System Screen will cause the following screen to be displayed:
TIME AND DATE
1=TIME 01:00 AM
2=DATE 01-01-2007
12HR
Time and Date Screen
To change the time, press 1 to display the following screen:
ENTER TIME
01:00 AM
1=AM
2=PM
Time Screen
A flashing cursor will appear on the left side of the display. Enter the four digit number corre-
sponding to the time (0000 - 1259). When the fourth digit is entered, the cursor will move one
position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display will
return to the Time and Date Screen displaying the new time.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
143
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Maintenance Programming Level
To change the date, press 2 while viewing the Time and Date Screen. The following screen will be
displayed:
ENTER DATE
MONTH DAY YEAR
01-01-2010
Date Screen
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit
day and four digit year. The cursor will move one position to the right after each entry. When the
fourth digit of the year has been entered, the display will return to the Time and Date Screen which
will show the new date.
3.7.6 Zone Setup
PROGRAMMING
1=WALKTEST
2=SYSTEM
Pressing 3 while viewing Maintenance Screen #2 will display the following screen:
3=ZONE SETUP
ZONE SETUP
1=ENABLE
2=DISABLE
Maintenance Screen #2
3=ZONE 97 98 99
Zone Setup Screen #1
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
144
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Programming Level
Pressing 1 while viewing Zone Setup screen #1 will display the following screen:
Programming
ZONE TO ENABLE
Z
Enable Screen
A flashing cursor appears to the right of the Z. To enable a zone, enter the two digit zone number
(00 - 99). After the second digit is entered, the zone will be enabled and the cursor will return to the
original position. The next zone to be enabled can then be entered. Press Esc (Escape) to return to
the previous screen.
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Pressing 2 while viewing Zone Setup screen #1 will display the following screen:
Zone Setup Screen #2
ZONE TO DISABLE
Z
Disable Screen
A flashing cursor appears to the right of the Z. To disable a zone, enter the two digit zone number
(00 - 99). After the second digit is entered, the zone will be disabled and the cursor will return to
the original position. The next zone to be disabled can then be entered. Press Esc (Escape) to
return to the previous screen.
Pressing 3 while viewing Zone Setup screen #1 will display the following screen:
SPEC PURPOSE ZONE
1=PAS 97
2=PRE-SIGNAL 98 OFF
OFF
3=FUTURE 99
OFF
Disable Screen
Zones 97, 98, and 99 can be programmed for normal zone operation or for special purpose applica-
tions. In the above illustration, the three zones are shown Off, which means they can be pro-
grammed to function in the same manner as all other zones, by assigning them to input and output
devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the
display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS
(Positive Alarm Sequence) activation of any detector will cause Zone 97 to activate. By assigning
Zone 97 to a control module in the Programming Zone Assignment Screen, an output device con-
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
145
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Maintenance Programming Level
nected to the control module can be used to indicate a PAS condition in the control panel. Do not
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condi-
tion.
Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is pro-
grammed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning
Zone 98 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a Pre-signal condition in the control panel. Do
not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal
condition.
Zone 99, in special purpose mode, is reserved for future use and has no effect.
Zones Installed
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to
the following:
Zone Setup Screen #2
ZONES INSTALLED
00 01 02 03 04 05
Zones Installed Screen
This display will show all of the zones that have been programmed into the control panel. Note that
an up and/or down arrow may appear in the upper right corner of the display, indicating that addi-
tional screens of zone information exists. Press the up or down arrow keys to view the additional
zones.
Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to
the following:
ZONES ENABLED
00 01 02 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19 20 21
Zones Enabled Screen
This display will show all of the zones that are enabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.
146
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Programming Level
Programming
Zones Disabled
Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar
to the following:
ZONES DISABLED
03
Zones Disabled Screen
This display will show all of the zones that are disabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.
Zone Type
ZONE SETUP
1=ZONE TYPES
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on
the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a
screen similar to the following:
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
ZONE TYPE PROG
1=Z00 MONITOR
2=Z01 MONITOR
3=Z02 MONITOR
Zones Installed Screen
This display will show the system zones (default and user programmed) and their associated types.
Note that an up and/or down arrow will appear in the upper right corner of the display, indicating
that additional screens of zone information exists. Press the up or down arrow keys to view zones
Z00 through Z99.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
147
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Maintenance Programming Level
Zone types can be changed by pressing the keypad number key corresponding to the zone in each
Zones Installed Screen. Available zone types will be displayed in the resultant screens. For exam-
ple, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following
screens will be displayed:
ZONE TYPE PROG
1=HEAT
ZONE TYPE PROG
1=MONITOR
2=PULL STATION
3=DUCT
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
Zone Type Program Screen #2
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON
3=TAMPER
3=SMOKE ION
Zone Type Program Screen #4
Zone Type Program Screen #3
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Water-
flow silenceable zone type to the selected zone. Any signaling devices programmed to the same
zone can be silenced by pressing the Alarm Silence key or by using the auto-silence feature.
To program a waterflow circuit as nonsilenceable, refer to “System Setup” on page 100.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only
change how it is reported to the Central Staion.
Zones Available
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
Zone Setup Screen #3
ZONES AVAILABLE
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19 20 21
The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.
148
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Programming Level
Programming
Zone Message
Pressing 3 while viewing Zone Setup Screen #3 will display the following screen:
ZONE MESSAGE
1=Z00
2=Z01
3=Z02
NO MESSAGE
MESSAGE 1
NO MESSAGE
Pressing the down arrow key will display additional screens for Zones up to Z99. Press the number
key corresponding to the Zone to be programmed. Screens will be displayed allowing the program-
mer to select Messages 1 through 5. When a message is selected, the display will return to the Zone
Message screen, showing the message selected for that particular zone. In the example above,
Zone 01 has been programmed for Message 1.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
149
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4: Operating Instructions
4.1 Panel Control Buttons
4.1.1 Acknowledge/Step
The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to
steady and also changes the status field on the LCD display from capital letters to small letters.
When the piezo is silenced, an acknowledge message is sent to the printer and the history file.
Acknowledge also sends a silence piezo command to the optional annunciators connected to the
FACP.
When more than one event exists, the first press of the Acknowledge/Step key functions as
described in the preceding paragraph. Subsequent pressing of the key steps through each off-nor-
mal active event, with alarm events having a higher priority than trouble and supervisory events.
4.1.2 Alarm Silence
The Alarm Silence key performs the same functions as Acknowledge/Step. In addition, if an alarm
exists, it turns off all silenceable NACs (Notification Appliance Circuits) and causes the Alarm
Silenced LED to turn on. It also sends an ‘alarm silenced’ message to the printer, history file and
optional annunciators. A subsequent new alarm will resound the system NACs. Note that the
Alarm Silenced LED is turned off by pressing the Reset key, the Drill key or subsequent activation
of the NACs.
4.1.3 Drill/Hold 2 Sec
When the Drill key is held for a minimum of two seconds (time required to prevent accidental acti-
vations), the FACP turns on all main panel NAC outputs and all silenceable circuits such as control
modules that are programmed as silenceable, and turns off the Alarm Silenced LED if it was previ-
ously on. The EVAC IN SYSTEM message is shown on the LCD display. The same message is sent
to the printer and history file. The Alarm Silence key can be used to turn off all silenceable NAC
outputs following activation by the Drill key.
4.1.4 Reset
Pressing and releasing the Reset key turns off all control modules and NACs, temporarily turns off
resettable power to 4-wire detectors, causes a RESET IN SYSTEM message to be displayed on the
LCD and sends the same message to the printer and history file. It also performs a lamp test by
turning on all LEDs (except the Ground LED), piezo sounder and LCD display segments after the
Reset key is released. Any alarm or trouble that exists after a reset will resound the system.
4.2 LED Indicators
The nine LED indicators, which are located on the front panel, operate as follows:
AC Power
This is a green LED which illuminates if AC power is applied to the FACP. A loss of AC power
will turn off this LED
Fire Alarm
This red LED flashes when one or more alarms occur. It illuminates steady when the Acknowl-
edge/Step or Alarm Silence key is pressed. The Fire Alarm LED turns off when the Reset key is
pressed. The LED will remain off if all alarms have been cleared.
150
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Normal Operation
Operating Instructions
Supervisory
This is a yellow LED that flashes when one or more supervisory conditions occur, such as a sprin-
kler valve tamper condition. It illuminates steady when the Acknowledge/Step or Alarm Silence
key is pressed. It turns off when the Reset key is pressed and remains off if all supervisory alarms
have been cleared.
Trouble
This is a yellow LED that flashes when one or more trouble conditions occur. It stays on steady
when the Acknowledge/Step or Alarm Silence key is pressed. The LED turns off when all trouble
conditions are cleared. This LED will also illuminate if the microprocessor watchdog circuit is
activated.
Maintenance
This is a yellow LED that flashes to indicate that a smoke detector requires cleaning or replacement
due to an invalid chamber reading or excessive drift.
Alarm Silenced
This is a yellow LED that turns on after the Alarm Silence key is pressed while an alarm condition
exists. It turns off when the Drill or Reset key is pressed.
Disabled
This is a yellow LED that flashes to indicate that a zone, NAC, detector or module has been tempo-
rarily disabled in programming by the user.
Battery
This is a yellow LED that flashes to indicate a low battery voltage condition.
Ground
This is a yellow LED that turns on steady to indicate a ground fault condition (zero impedance
between FACP and ground).
4.3 Normal Operation
With no alarms or troubles in the system, the display message is System All Normal along with the
current time and date as shown below. To set the time and date, refer to the appropriate section in
this manual.
HONEYWELL
LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 010810
The FACP performs the following functions at regular intervals while in Normal mode:
• Monitors AC input voltage and battery voltage
• Monitors and reports status of SLC loop(s), option cards and control panel
• Polls all devices on the SLC loop(s) and flashes each device LED while checking for valid
replies, alarms, troubles, etc.
• Refreshes LCD display and updates time
• Scans control panel keypad for key presses
• Performs autotest for all SLC devices
• Tests memory
• Updates and reads all communications busses (EIA-485, EIA-232, etc.)
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
151
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Trouble Operation
4.4 Trouble Operation
With no alarms in the system, the detection of a trouble will cause the following:
•
•
•
•
The piezo to pulse 1 second On and 1 second Off
The system Trouble LED to flash one second On and one second Off
The trouble relay to activate
TROUBL with device type, noun/adjective, address and trouble description will appear on the
LCD display
•
•
The same message, along with the time and date, is sent to the history buffer and optional
printer
Terminate upload or download communications
Note that specific troubles will initiate additional actions; for example, loss of AC power will turn
off the AC Power LED, a ground fault will turn on the Ground LED, etc.
Addressable Smoke Detectors, Monitor Modules and Control Modules
For addressable devices connected to the SLC loop, the following is a typical message that could
appear on the LCD display for a device trouble:
TROUBL SMOKE (PHOTO)
<ADJ> <NOUN>
INVREP
10:00A 010810 1D001
The information displayed in the above example provides the following information:
•
First line in display:
– The type of event; in this example TROUBL indicating a device trouble
– Device type identifier; in this example, SMOKE (PHOTO) indicates a Photoelectric smoke
detector. Other device type identifiers which can be displayed include SMOKE (ION) for
Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module and
Module Screen for Control Modules” on page 88 for information on additional device types.
•
•
Second line in display:
– <ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
– <NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
Third line in display: INVREP indicates an invalid reply from the addressable device. Other
possible troubles include:
SHORT - indicating a shorted circuit on an addressable device
OPEN - indicating an open circuit on an addressable device
DIRTY1 - maintenance alert indicating that a detector is near but below the allowed alarm
limit and is in need of maintenance before the performance is compromised
DIRTY2 - maintenance alert indicating that a detector needs immediate maintenance since it
has been within 80% of its alarm threshold for 24 hours
INVREP - maintenance alert indicating a hardware problem in the detector
TEST F - indicating a detector has failed the automatic test operation which functionally
checks its sensing chamber and electronics
152
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Alarm Operation
Operating Instructions
INV ID - indicating that an incorrect device code (Type ID) has been programmed for an
installed device (for example, Photo has been programmed but an Ion detector has been
installed)
SW TBL - indicating a module has failed the testing of its Class A switching relay
Fourth line in display:
•
– Time; the current time in this example is 10:00A which represents 10:00 AM
– Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of
the month, and 10 for the year 2010
– Device Address; 1D001 in this example 1 represents SLC Loop1, D represents a detector,
and 001 represents device address 001
Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to silence and the
system Trouble LED to change from flashing to on steady. This block acknowledgment occurs
regardless of the number of troubles, alarms and supervisory events active in the system. When the
Acknowledge/Step key is pressed and at least one new alarm or trouble exists in the system, the
‘acknowledge’ message is sent to the printer and history file. If the trouble clears, either before or
after the Acknowledge/Step key is pressed, the ‘clear trouble’ message is sent to the printer and his-
tory file.
If all troubles clear and there are no supervisory or fire conditions active in the system, the system
returns to normal mode operation and the System All Normal message is shown on the LCD display
and sent to the history and printer files. The auto-restore feature will restore cleared troubles even
if the troubles were never acknowledged. Note that pressing the Alarm Silence key when only trou-
bles exist in the system will have the same effect as pressing the Acknowledge/Step key.
If multiple trouble conditions exist in the system, they will be automatically scrolled on the LCD
display at a three second rate. If a combination of alarms, troubles and/or supervisory conditions
simultaneously occur in the system, only the alarms are scrolled on the display.
4.5 Alarm Operation
Alarm operation is similar to trouble operation with the following differences:
•
•
•
The piezo sounder produces a steady output as opposed to a pulsed output
The Fire Alarm LED flashes 1 second On and 1 second Off
The LCD displays Alarm along with the device name, type, address, adjective/noun, associated
zones and time/date
•
•
•
•
•
•
•
•
Alarms latch and are not allowed to clear automatically
Alarms activate software zones if so programmed
Timers for Silence Inhibit, Autosilence and Trouble Reminder are started
Alarms activate the general alarm relay and general alarm zone Z00
The trouble relay is not activated
Store event in history buffer
Terminate upload or download communications
Alarms must be Acknowledged before the FACP can be reset
A typical alarm display would be as illustrated below:
ALARM PULL STATION
<ADJ> <NOUN>
Z000
10:00A 010810 1M001
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
153
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Supervisory Operation
Note that the device type, which in this example is PULL STATION, can be any other programma-
ble alarm type.
The information displayed in the above example provides the following information:
•
First line in display:
– The type of event; in this example ALARM indicating an alarm condition
– Device type identifier; in this example, PULL STATION indicates a manual pull box. Other
device type identifiers which can be displayed include SMOKE (ION) for Ionization
Detector, HEAT for Heat Detector, CONTROL for Control Module and MONITOR for
for Control Modules” on page 88 for information on additional device types.
•
Second line in display:
– <ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
– <NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
•
•
Third line in display: Z000 indicates the zone programmed to this device which, in this
example, is general alarm Zone 000. Note that a single device can be programmed to five
different zones but only the first zone will be displayed.
Fourth line in display:
– Time; the current time in this example is 10:00A which represents 10:00 AM
– Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of
the month, and 10 for the year 2010
– Device Address; 1M001 in this example 1 represents SLC Loop1, M represents a module,
and 001 represents device address 001
4.6 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
•
•
•
The piezo sounder pulses ½ second On and ½ second Off
The Supervisory LED flashes ½ second On and ½ second Off
The LCD displays the status label Active Supervisory along with the device name, type,
address, adjective/noun, associated zones and time/date
•
•
•
•
•
•
•
The supervisory relay is activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Terminate upload or download communications
Supervisory condition must be Acknowledged before the FACP can be reset
154
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Process Monitor Operation
A typical Supervisory event would be displayed as illustrated in the following:
Operating Instructions
ACTIVE SUPERVISORY
<ADJ> <NOUN>
Z000
10:00A 010810 1M001
Note that, like alarms, supervisory signals latch (except when programmed for supervisory autore-
settable) and can be assigned to software zones. Supervisory alarms do not cause resound as do
other alarm conditions. Open circuits in supervisory wiring are processed by the control panel the
of the information displayed on the control panel LCD.
4.7 Process Monitor Operation
Process Monitor operation will initiate the following events:
•
•
The piezo sounder pulses ¼ second On and ¼ second Off
The LCD displays a process monitor message along with the device name, type, address,
adjective/noun, associated zones and time/date
•
•
•
•
•
•
Relays programmed for process monitoring will be activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Process Monitor condition must be Acknowledged before the FACP can be reset
Note that, like supervisories, process monitor signals latch (except when programmed for process
monitor autoresettable) and can be assigned to software zones.
4.8 Hazard Condition Operation
Hazard Condition operation will initiate the following events:
•
•
The piezo sounder turns on steady
The LCD displays a hazard message along with the device name, type, address,
adjective/noun, associated zones and time/date
•
•
•
•
•
•
Relays programmed for process monitoring will be activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Hazard condition must be Acknowledged before the FACP can be reset
Hazard conditions latch and will therefore clear only when the hazard condition is cleared and the
panel reset. They can be assigned to software zones.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
155
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Medical Alert Condition Operation
4.9 Medical Alert Condition Operation
Medical Alert Condition operation will initiate the following events:
•
•
The piezo sounder turns on steady
The LCD displays a medical alert message along with the device name, type, address,
adjective/noun, associated zones and time/date
•
•
•
•
•
•
Relays programmed for medical alert will be activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Medical Alert condition must be Acknowledged before the FACP can be reset
Medical alert conditions latch and will therefore clear only when the medical alert condition is
cleared and the panel reset. They can be assigned to software zones.
4.10 Programmed Zone Operation
Each addressable detector and monitor module can be assigned to a maximum of five software
alarm zones. A general alarm zone Z00 may be listed for output (control) points, but it is not nec-
essary to list Z00 for input points, since this is the default zone for all alarm input devices. Zone
Z00 is also activated by supervisory points.
When an input device alarms and is not disabled, it activates all software zones assigned to it. An
output device that is not disabled is turned on when any of the software zones to which it is pro-
grammed become active.
4.11 Disable/Enable Operation
Input points which are disabled do not cause an alarm or any zone activation. Disabled output
points are held in the off state. All disabled points are treated as if they were in trouble, with the
exception being the status label that will be displayed is DISABL.
4.12 Waterflow Circuits Operation
If an alarm exists from a monitor module point that has a waterflow type code and its mapped NAC
control module outputs are programmed for nonsilenceable operation, the Alarm Silence key will
not function.
4.13 Detector Functions
Maintenance Alert
Each addressable detector is monitored by the control panel for its maintenance status. If a detector
is near but below the allowed alarm limit, a ‘maintenance alert’ message will automatically be dis-
played, signaling that the detector is in need of servicing.
Automatic Test Operation
An automatic test of an addressable detector is performed each minute, resulting in a complete SLC
loop test in approximately 5 hours (if the loop has the maximum number of devices installed). The
detector’s sensing chamber and electronics are functionally tested for normal, safe operation. A
trouble message is displayed upon failure of this test. A System Reset will clear this trouble.
156
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Time Functions: Real-Time Clock
Type Code Supervision
Operating Instructions
The FACP monitors addressable hardware device codes at slow intervals. Mismatch of any type
code, compared to the system program, will cause a device trouble.
System Alarm Verification
The control panel may be programmed to perform alarm verification to help eliminate the nuisance
of false alarms. Alarm verification applies to smoke detectors only.
Smoke Detector Data
Smoke detector data is monitored by the FACP, eliminating the need to test the sensitivity of each
detector at its location. A printout of each detector’s data can be retrieved from the FACP using an
optional printer or Windows© HyperTerminal. Detector sensing ability can decrease with age and
should be monitored as part of a system’s routine maintenance.
4.14 Time Functions: Real-Time Clock
The FACP includes a crystal-based clock that provides time of day, date and day of week. Time is
displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time
change-over is programmable and automatic. If both AC and battery are lost, the time must be
reset.
4.15 NAC Operation
There are up to four programmable NACs (Notification Appliance Circuits) resident on the FACP
main circuit board. The NACs may be programmed as silenceable or nonsilenceable and may also
be programmed for steady or coded operation. Coded operation provides a choice between March
Time, Temporal, California coding and two-stage operation.
4.16 Synchronized NAC Operation
Synchronization is a panel feature that controls the activation of notification appliances in such a
way that all devices will turn on and off at exactly the same time. This is particularly critical when
activating strobes which must be synchronized to avoid random activation and a potential hazard or
confusion. The FACP can be programmed to operate with a variety of manufacturer’s devices.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for silenceable and the synchronization feature is selected, only the audible devices
will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to
operate.
4.17 Coded Operation
The NAC circuits resident on the control panel main circuit board can be programmed for coded
operation. The available pulse rates which can be programmed for coded operation are as follows:
•
•
•
Continuous:
Steady output with no pulsing
March Time:
Temporal Code:
Pulses at 120 ppm (pulses per minute)
Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off,
½ second On, 1½ second Off
•
•
California Code:
Two-Stage
10 seconds On, 5 seconds Off
Pulses at 20 ppm (pulses per minute) for 5 minutes and
then changes to Temporal
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
157
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Presignal
4.18 Presignal
Presignal option programs an initiating device to delay the activation of NACs and/or control mod-
ules while allowing visual verification by a person. Once a detector or monitor module triggers an
alarm, the onboard piezo sounds immediately, but the NACs are not activated for a user pro-
grammed time duration of up to three minutes. Note that the alarm relay and communicator will
respond to the initial alarm immediately. In addition, Zone 98 will activate. This zone can be pro-
grammed to a control module which may be used to activate a sounder or indicator which the
installer designates as a Presignal indication. Do not assign Zone 98 to a Notification Appliance
Circuit when using this zone to indicate a Pre-signal condition.
After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note
that if a second alarm occurs during the programmed time delay, the alarm will be processed imme-
diately, causing activation of the appropriate output zones. The events which occur upon Presignal
activation are as follows:
• onboard piezo sounds immediately
• control panel LCD display will indicate a presignal event and the active point
• control points programmed to Zone 98 will activate
• annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED
• outputs (NACs and control modules) of associated zones will be inhibited from activating
for a user programmed time delay of up to three minutes
• second alarm occurring anytime during the time delay will cause immediate activation of all
associated outputs
Presignal does not affect monitor modules programmed as waterflow, supervisory, process moni-
toring or remote switches. Presignal operation requires the approval of the local Authority Having
Jurisdiction.
4.19 Positive Alarm Sequence
PAS (Positive Alarm Sequence) option will program a smoke detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds. Zone 97, however, will acti-
vate immediately and may be used to connect a signaling device to indicate PAS activation. Do not
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condi-
tion.
When a detector triggers an alarm, the onboard piezo sounds immediately, but the NACs are pre-
vented from activating for 15 seconds. This inhibit time is factory set and cannot be changed.
Pressing the Alarm Silence or Acknowledge/Step key during the 15 second inhibit time will silence
the piezo sounder and start a timer which prevents activation of NACs for an additional time dura-
tion which can be user programmed for up to three minutes. After the programmed delay, the
NACs will activate if the source of the alarm is not cleared. Note that if a second alarm occurs dur-
ing either time delay, the alarm will be processed immediately, causing activation of the appropriate
output zones. The events which occur upon PAS activation are as follows:
• onboard piezo sounds immediately
• control panel LCD display will indicate a presignal event and the active point
• control points programmed to Zone 97 will activate
• ACS annunciators (if enabled) will pulse the Zone 97 PAS LED immediately upon PAS
activation. They will sound the local piezo, and pulse the alarm, associated zone and
detector address point LEDs after 15 seconds of an unacknowledged PAS activation. Note
that if the Alarm Silence or Acknowledge/Step button is pressed, the annunciators will be
inhibited from activating for an additional time delay
• outputs (NACs and control modules) of associated zones will be inhibited from activating
for a factory set duration of 15 seconds
158
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Special System Timers
Operating Instructions
• pressing the Alarm Silence or Acknowledge/Step key will start a timer which inhibits output
activation for additional time delay of up to three minutes which is user programmable
• second alarm occurring anytime during either time delay will cause immediate activation of
all associated outputs
PAS operation requires the approval of the local Authority Having Jurisdiction.
Note that the PAS BYPASS monitor type code, when activated, will inhibit the PAS capability until
the PAS BYPASS monitor is deactivated. While PAS is inhibited, signaling devices will immedi-
ately place the control panel into alarm. This feature may be employed by wiring a normally open
device, such as a switch, to a monitor module which has been programmed for PAS BYPASS.
4.20 Special System Timers
4.20.1 Silence Inhibit Timer
This option, if selected, prevents the Alarm Silence and Reset keys from functioning for 60 seconds
following an alarm. A second alarm during this 60 second period will not cause the timer to restart
with a new 60 seconds. Silence Inhibit operation requires the approval of the local Authority Hav-
ing Jurisdiction.
4.20.2 Autosilence Timer
If Autosilence is selected, the notification appliances, programmed as silenceable, will automati-
cally be silenced after a programmable duration of from 5 to 30 minutes. Pressing the Drill key
will restart the timer. Autosilence operation requires the approval of the local Authority Having
Jurisdiction.
4.20.3 Trouble Reminder
If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the
Alarm Silence key is pressed) and every two minutes during a trouble condition (after the Acknowl-
edge/Step or Alarm Silence key is pressed). The ‘beeps’ from the onboard piezo sounder will occur
until the alarm or fault is cleared.
Note that if the trouble is not cleared within 24 hours, the piezo will resound, indicating that the
trouble condition still exists.
4.20.4 Waterflow Retard Timer
If selected, this option will delay the activation of a waterflow type alarm for a programmable time
duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow
device. This feature requires the approval of the local Authority Having Jurisdiction.
4.20.5 Alarm Verification
If alarm verification is selected, an addressable smoke detector's alarm is ignored for a Retard time
of 13 seconds and the detector’s alarm condition is automatically reset. There will be no alarm
indication at the FACP during the Retard period. A Confirmation period of 60 seconds follows,
during which a subsequent alarm from the same detector will cause the panel to immediately acti-
vate the appropriate outputs and indicate the alarm condition at the FACP. If a different detector
alarms any time during the first detector's verification period, the panel will immediately activate
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
159
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Walktest
all appropriate outputs and indicate the alarm condition at the FACP. If no additional detector
alarms occur within 73 seconds of the first alarm (13 second Retard plus 60 second Confirmation),
the timer resets and the panel is ready to verify any new detector alarms which may occur.
13 sec.
73 sec.
0 sec.
RETARD
Detector Alarm
CONFIRMATION (60 seconds)
Verification (Retard +
Confirmation)
Alarm Ignored
Control Panel Processes Alarm if Same Detector is Still in Alarm
Detector Goes Into Alarm
Control Panel Immediately Processes Alarm
Different Detector Alarms
During First Detector's
Verification Period
NOTE: Alarm Verification is available only for addressable smoke detectors, not conventional
smoke detectors.
4.21 Walktest
Walktest is a feature which allows one person to test the fire alarm system. An audible walktest
will momentarily sound the Notification Appliance Circuits in the building and store the walktest
information in a file at the panel. A silent walktest will not sound the NACs but will store the walk-
test information in a file which can be viewed at the panel. Disabled NAC devices will not activate
during walktest.
Alarm/Shorted Condition
When in audible Walktest, the panel responds to each new alarm and activates its programmed con-
trol outputs for four seconds, if those outputs have been programmed for silenceable activation. It
also stores each alarm in the walktest history file which can be sent to an optional printer. The
stored display will be the same as if the device actually activated except the colon (:) in the time
stamp is replaced with an asterisk (*).
Open Condition
Addressable devices are monitored for fault conditions during Walktest mode. When a new trouble
condition occurs, the FACP will activate all NACs and control modules programmed for Walktest
and mapped to the faulted device, then shut them off after eight seconds.
While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of
the Program and status change operations). The alarm relay is not activated.
4.22 Read Status
Read Status functions do not require a password. The control panel will continue to provide fire
protection while in Read Status mode. This mode can be entered while the control panel is in alarm
or trouble. If a new alarm or trouble occurs during these functions, the Read Status is exited to pre-
vent confusion.
160
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Read Status
Operating Instructions
Read Status Entry
When the operator presses the control panel Enter key, the LCD will display the following:
1=READ STATUS
2=PROGRAMMING
3=REMOTE
DOWNLOAD
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Sta-
tus mode which allows the user to view and print the programmed features and status of the control
panel.
The following screens will be displayed:
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
3=NACS
Read Status Screen #1
Read Status Screen #2
READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY
READ STATUS
1=ANNUNCIATORS
2=PHONE LINE
3=CENTRAL STATION
Read Status Screen #3
Read Status Screen #4
READ STATUS
1=SERVICE TERMINAL
2=PRINTER/PC
3=PRINT
READ STATUS
1=TIME-DATE
Read Status Screen #5
Read Status Screen #6
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
161
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Read Status
4.22.1 System Point
READ STATUS
1=SYSTEM POINT
2=ZONES
Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed:
3=POWER
READ SYSTEM POINT
SELECT LOOP
1=LOOP 1
Read Status Screen #1
2=LOOP 2
The operator selects the loop containing the device to be read by pressing 1 for Loop 1 or 2 for
Loop 2. The following screen will then be displayed:
READ SYSTEM POINT
SELECT TYPE
1=DETECTOR
2=MODULE
The operator now selects the type of device which is to be viewed by pressing 1 for Detector or 2
for Module. If 1 is pressed, the display will change to the following screen:
READ SYSTEM POINT
ENTER DETECTOR#
***
Entering the three digit detector address will cause the control panel to display the current status of
the selected device. For example, if a detector with address 001 on loop 1 is entered, a display sim-
ilar to the following will appear:
NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Z005
1D001
The information in the preceding display includes:
•
•
NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be
ION for ionization smoke detector)
•
•
•
NORTH CLASSROOM - the Adjective/Noun label for this device
Z005 - the first of five possible assigned software zones
1D001 - 1 = Loop 1, D = Detector, 001 = Address 001
162
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Read Status
Operating Instructions
Pressing the down arrow key, while viewing the screen shown on the previous page, will allow the
operator to view additional programming information about the selected device, such as:
•
•
•
•
•
•
•
•
•
•
Enable/Disable Status
Device Type
Alarm Verification On/Off
Walktest Yes/No
PAS (Positive Alarm Sequence) Yes/No
Pre-Signal Yes/No
Zone Assignments (five maximum)
Chamber Reading
Adjective/Noun descriptor
Silenceable Yes/No (for control modules)
4.22.2 Zones
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:
READ STATUS
1=SYSTEM POINT
2=ZONES
ZONES
3=POWER
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Read Status Screen #1
Zones Screen #1
ZONES
1=SPECIAL PURPOSE
2=ZONE TYPE
3=ZONE MESSAGE
Zones Screen #2
From the preceding screens, the control panel operator can view:
•
•
•
•
Zones Installed - all software zones programmed into the system (99 maximum)
Zones Enabled - all software zones that are enabled
Zones Disabled - all software zones that have been disabled
Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98
reserved for Pre-signal and 99 reserved for future use
•
•
Zone Type - the Type assigned to each installed zone (default is Alarm)
Zone Message - the message assigned to each installed zone
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
163
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Read Status
4.22.3 Power
Pressing 3 while viewing Read Status Screen #1 will display the following screens:
POWER
BATTERY
24 V RST
27.21V
25.31V
Zones Screen #1
POWER
CHARGER
NAC 1
NAC 2
28.36V
-2.39V
-2.39V
Zones Screen #2
POWER
NAC 3
NAC 4
-2.39V
-2.39V
Zones Screen #3
A real-time display of control panel voltages can be used to determine if system problems exist.
Note that Zones Screen #3 will only be displayed if the NACKEY NAC option card is installed, in
JP8 of the main circuit board, for Class B operation.
The following table lists the circuit being measured, possible conditions and their respective volt-
age ranges:
Circuit
Condition
Normal Battery (nominal)
Low Battery
No Battery
Normal
Voltage Range
27.05 to 28.15 VDC
20.0 to 20.8 VDC
0 to 18.36 VDC
Battery
24V Resettable
24V Nonresettable
Charger
21.25 to 27.50 VDC
21.25 to 27.50 VDC
27.05 to 28.15 VDC
-1.3 to -1.6 VDC
-2.3 to -2.5 VDC
0 to 1.0 VDC
Normal
Normal
Normal
NACs
Open Circuit
Short Circuit
164
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Read Status
Operating Instructions
4.22.4 Trouble Reminder
Pressing 1 while viewing Read Status Screen #2 will display the following screen:
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
TROUBLE REMINDER
TROUBLE REM
3=NACS
ON
Read Status Screen #2
The screen indicates whether the Trouble Reminder feature is On or Off.
4.22.5 Timers
Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be dis-
played:
TIMERS
PAS DELAY
PRE SIGNAL
WATERFLOW
000
000
000
TIMERS
AC LOSS DELAY
4
These screens indicate the delay time, in seconds, for each of four possible delay options.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
165
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Read Status
4.22.6 NAC
Pressing 3 while viewing Read Status Screen #2 will display the following screen:
NAC
1=NAC 1
2=NAC 2
3=NAC 3
4=NAC 4
Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC option card is
installed, in JP8 of the main circuit board, for Class B operation.
The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed
options for NAC 2, 3 to view the programmed options for NAC 3, or 4 to view the programmed
options for NAC 4. The resulting screens will display the following information:
•
•
•
•
•
•
•
•
Enable/Disable Status
Circuit Type (Bell, Strobe, etc.)
Silenceable/Nonsilenceable
Auto Silence Enable/Disable and time delay
Coding Selection (Temporal, Steady, etc.)
Zone Assignments
Silence Inhibit Enabled/Disabled
Synchronization Type (System Sensor, Wheelock or Gentex)
4.22.7 Relays
READ STATUS
1=RELAYS
Pressing 1 while viewing Read Status Screen #3 will display the following screen:
2=PROGRAM CHECK
3=HISTORY
Read Status Screen #3
RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
The operator can view the programmed option for each relay by pressing the corresponding number
key.
166
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Read Status
Operating Instructions
4.22.8 Program Check
Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be
displayed:
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Pressing 1 while viewing the Program Check screen will display a screen which will indicate if any
input zones have not been programmed to one of the Notification Appliance Circuits. Use the up
and down arrow keys to view all NACs.
Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any
output zones have not been programmed to at least one input zone. Use the up and down arrow
keys to view all zones.
Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any
input zones have not been programmed to at least one output zone. Use the up and down arrow
keys to view all zones.
4.22.9 History
Pressing 3 while viewing Read Status Screen #3 will display the following screen:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
The operator can view all events which have been stored in the history file, only alarms or other
events, such as troubles or supervisories, by pressing the corresponding number key.
4.22.10 Annunciators
Pressing 1 while viewing Read Status Screen #4 will display the following screens:
READ STATUS
1=ANNUNCIATORS
2=PHONE LINES
ANNUNCIATORS
TERM ENABLED
2=ACS OPTIONS
3=ANN-BUS OPTIONS
YES
3=CENTRAL STATION
Read Status Screen #4
Annunciator Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
167
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
The Annunciator Screen indicates if Terminal mode options are enabled or disabled.
Read Status
Pressing 2 for ACS Options while viewing the Annunciator Screen allows the operator to view the
ACS Options screen:
ACS OPTIONS
ACS ENABLED
NO
2=ACS ADDRESSES
UDACT ENABLED NO
ACS Options Screen
The ACS Options screen indicates if the ACS option has been enabled YES or disabled NO.
Pressing 2 for ACS Addresses while viewing the ACS Options screen will display screens with
ACS addresses 1 -31 and whether a device is installed at that address YES or not installed NO.
The ACS Options screen indicates if a UDACT is installed YES or if a UDACT is not installed NO.
Pressing 3 for ANN-BUS Options while viewing the Annunciator Screen will display the following
screens:
ANN-BUS
ENABLED
NO
2=MODULES INSTALLED
3=ANN-S/PG OPTIONS
ANN-BUS Screen #1
ANN-BUS
1=ANN-80 OPTIONS
ANN-BUS Screen #2
The ANN-BUS Screen #1 indicates if the ANN-BUS has been enabled YES or disabled NO.
Pressing 2 for Modules Installed while viewing ANN-BUS Screen #1 will display screens for
ANN-BUS Addresses 1 -8 and the devices installed at each address. Subscreen will display the
options that have been programmed for each device.
Pressing 3 for ANN-S/PG Options while viewing ANN-BUS Screen #1 will display the options
selected for the installed serial or parallel printer.
Pressing 1 for ANN-80 Options while viewing ANN-BUS Screen #2 will display the options
selected for the installed ANN-80 annunciators.
168
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Read Status
Operating Instructions
4.22.11 Phone Line
Pressing 2 while viewing Read Status Screen #4 will display the following screen:
PHONE LINE
PRIMARY TOUCHTONE
SECONDARY TOUCHTONE
3=SUPERV PHONE LINE
The second and third lines of this screen indicate that both the Primary and Secondary phone lines
have been configured for touchtone dialing operation.
Pressing 3 while viewing the Phone Line screen will cause the following screen to be displayed:
SUPERVISE PHONE LINE
PHONE LINE 2
NO
This screen indicates whether or not Phone Line 2 is being supervised. In this example, PHONE
LINE 2 NO indicates the phone line is not being supervised.
4.22.12 Central Station
READ STATUS
1=ANNUNCIATORS
2=PHONE LINE
Pressing 3 while viewing Read Status Screen #4 will display the following screens:
3=CENTRAL STATION
CENTRAL STATION
Read Status Screen #4
REPORTING
REPORT FIRST AVAIL
CALL LIMIT 10
ENABLED
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
REPORT STYLE
ZONE
Central Station Screen #2
Central Station Screen #1 indicates whether the Central Station Reporting is enabled or disabled, if
the Reports will be sent to the First Available or Backup Primary and Secondary Central Station
phone numbers and Call Limit for DACT trouble calls within a 24 hour period. Central Station
Screen #2 provides information on the Report Style (Zone or Point) as well as the Primary and Sec-
ondary Central Station programming which includes:
•
•
•
•
•
•
Test Time Interval
Account Code
24 Hour Test Time
Phone Number
Communication Format
Event Codes
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
169
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Read Status
4.22.13 Service Terminal
Pressing 1 while viewing Read Status Screen #5 will display the following screens:
READ STATUS
1=SERVICE TERMINAL
2=PRINTER/PC
3=PRINT
SERVICE TERMINAL
RING COUNT
05
Read Status Screen #5
Service Terminal Screen
The Ring Count is displayed in the Service Terminal Screen. A Ring Count value of 00 would indi-
cate that calling is disabled.
4.22.14 Printer/PC
Pressing 2 while viewing Read Status Screen #5 will display the following screen:
PRINTER PC
PRINTER PC PR4800
Printer/PC Screen
The display will inform the operator as to whether the control panel is configured for a printer or a
PC and if the printer is supervised. In the example above, PR4800 indicates that the panel is con-
figured for a printer with a baud rate of 4800 and PR indicates that the printer is being supervised.
If NS appeared in place of PR, it would indicate that the printer is not supervised.
170
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Read Status
Operating Instructions
4.22.15 Print
To print program data or control panel status, press 3 while viewing Read Status Screen #5. The
following screens will be displayed:
READ STATUS
1=SERVICE TERMINAL
2=PRINTER/PC
3=PRINT
PRINT
1=HISTORY
2=WALKTEST LOG
3=DETECTOR DATA
Read Status Screen #5
Print Screen #1
PRINT
1=EXIT PRINTING
Print Screen #2
Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail
all of the system activities since the file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail
all of the system activations during walktest since the log was last cleared. Refer to “Walktest” on
page 160 for additional information on the display.
Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each address-
able smoke detector connected to the system. A printout, similar to the following example, will be
generated if an optional printer is connected to the FACP.
DEVICE #
DEVICE TYPE
%DRIFT COMP
CHAMBER
1281
TIME/DATE
1D001
1D002
1D003
1D004
1D005
1D006
1D007
1D008
1D009
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
20
20
21
20
21
20
20
20
20
12:01AM 01-08-2001
12:01AM 01-08-2001
12:01AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
1281
1259
1309
1281
1322
1280
1215
1310
Chamber Value
The Chamber value should be within the indicated range for the following smoke detectors:
•
SD350(T), SD355(T), D350P(R), SD300(T), AD350 and AD355 Addressable Photoelectric
Smoke Detectors: 405 - 2100 (obscuration of 1.00%/ft to 3.66%/ft.)
•
CP350, CP355 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration
of 0.50%/ft. to 1.44%/ft.)
If the addressable smoke detector’s Chamber reading is not within the acceptable range, clean the
detector and check the Chamber value again. If the reading is still not within the acceptable range,
immediately replace the detector.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
171
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Drift Compensation
Read Status
Drift compensation uses software algorithms that identify and compensate for long-term changes in
the data readings from each addressable smoke detector. These long-term changes in detector data
readings are typically caused by dirt and dust accumulation inside the smoke chamber. Drift com-
pensation performs the following functions:
•
•
•
Samples each photoelectric smoke detector every 6 seconds and each ionization smoke
detector every 3 seconds
Allows a smoke detector to retain its original ability to detect actual smoke and resist false
alarms, even as dirt and dust accumulate
Reduces maintenance requirements by allowing the control panel to automatically perform the
periodic sensitivity measurements required by NFPA Standard 72
The FACP software also provides filters to remove transient noise signals, usually caused by elec-
trical interference.
Maintenance Alert
The software determines when the drift compensation for a detector reaches an unacceptable level
that can compromise detector performance. When a detector reaches an unacceptable level, the
control panel indicates a maintenance alert. Table 4.1 summarizes the three levels of maintenance
alert:
Maintenance Level
Low Chamber Value
Maintenance Alert
FACP Status Displays Indicates
INVREP
DIRTY1
A hardware problem in the detector
Dust accumulation that is near but below the allowed
limit. DIRTY 1 indicates the need for maintenance
before the performance of the detector is compromised
DIRTY2
Maintenance Urgent
Dust accumulation above the allowed limit.
Table 4.1 Maintenance Alert Levels
Figure 4.1 illustrates a graphic representation of the maintenance levels:
DIRTY
Maintenance
Urgent
Maintenance
Alert
Acceptable
Range
LowChamber
Reading
LOW
VALUE
Figure 4.1 Diagram of Maintenance Levels
172
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Read Status
Operating Instructions
4.22.16 Time-Date
The operator can view the daylight savings time and the month and week when daylight savings
time will begin and end. Pressing 1 while viewing Read Status Screen #6 will display the following
screens:
READ STATUS
1=TIME-DATE
Read Status Screen #6
DAYLIGHT SAVINGS
ENABLED
YES
MAR
START WEEK WEEK-2
START MONTH
DAYLIGHT SAVINGS
END MONTH
END WEEK
NOV
WEEK-1
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
173
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5: Power Supply Calculations
5.1 Overview
This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system
5.2 Calculating the AC Branch Circuit
The control panel requires connection to a separate, dedicated AC branch circuit, which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed
of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm
branch circuit. The branch circuit wire must run continuously, without any disconnect devices,
from the power source to the control panel. Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2)
wire with 600 volt insulation for this branch circuit.
Use Table 5.1, to determine the total amount of current, in AC amperes (A), that must be supplied
to the system.
Device Type
Number of
Devices
Current Draw
(AC amps)
Total Current per
Device
MS-9600LS(C)
MS-9600UDLS
or
3.0
or
1
X
=
MS-9600LSE
MS-9600UDLSE
1.5
2.0
CHG-120F
[
[
]
]
X
X
=
=
=
[
]
Sum Column for AC Branch Current Required
Table 5.1 AC Branch Circuit Requirements
5.3 Calculating the System Current Draw
5.3.1 Overview
The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 5.3 on page 176. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 5.3 on page 176. The secondary power
source (batteries) must be able to power the system during a primary power loss. To calculate the
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 5.3 on
page 176.
When calculating current draw and the battery size, note the following:
•
‘Primary’ refers to the main power source for the control panel
174
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Calculating the System Current Draw
Power Supply Calculations
•
•
‘Secondary’ refers to the control panel’s backup batteries
All currents are given in amperes (A). Table 5.2 shows how to convert milliamperes and
microamperes to full amperes.
To convert...
Multiply
Example
Milliamperes (mA) to
amperes (A)
mA x 0.001
3 mA x 0.001 = 0.003A
Microamperes (µA) to
amperes (A)
µA x 0.000001
300 µA x 0.000001 = 0.0003 A
Table 5.2 Converting to Full Amperes
5.3.2 How to Use Table 5.3 on page 176 to Calculate System
Current Draw
Use Table 5.3 on page 176 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns.
2. Enter the current draw where required. Refer to the Device Compatibility Document for
compatible devices and their current draw.
3. Calculate the current draws for each in all columns.
4. Sum the total current for each column.
5. Copy the totals from Column 2 and Column 3 to Table 5.4 on page 177.
Following are the types of current that can be entered into Table 5.3 on page 176:
Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.
Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
175
Download from Www.Somanuals.com. All Manuals Search And Download.
Power Supply Calculations
Calculating the System Current Draw
Table 5.3 contains columns for calculating current draws. For each column, calculate the current
and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation
Column 2 and Calculation Column 3 to Table 5.4 on page 177.
Calculation Column 1
Calculation Column 2
Calculation Column 3
Primary, Non-Fire Alarm Current (amps) Primary, Fire Alarm Current (amps)
Secondary, Non-Fire Alarm Current (amps)
Device Type
Qty
X[current draw]=
Total
Qty
X [current draw] =
Total
Qty
X[current draw]=
Total
Main Circuit Board
ANN-80
1
X[0.160]=
X[0.037]=
X[0.028]=
X[0.015]=
X[0.035]=
X[0.045]=
X[0.030]=
X[0.040]
0.160
1
X[0.253]=
X[0.040]=
X[0.068]=
X[0.075]=
X[0.200]=
X[0.045]=
0.253
1
X[0.103]=
X[0.015]=
X[0.028]=
X[0.015]=
X[0.035]=
X[0.045]=
X[0.030]=
X[0.040]=
0.103
[
[
[
[
[
[
[
]
]
]
]
]
]
]
[
[
[
[
[
[
[
]
]
]
]
]
]
]
[
[
[
[
[
[
[
]
]
]
]
]
]
]
ANN-(R)LED
ANN-RLY
ANN-I/O
ANN-S/PG
ACM-8RF
1
X[0.158] =
2
ACM-16ATF
ACM-32AF
X[0.056] =
2
AEM-16ATF
AEM-32AF
[
[
]
]
X[0.002]
X[0.040]
[
[
]
]
X[0.018] =
[
[
]
]
X[0.002]=
X[0.040]=
2
AFM-16ATF
AFM-32AF
X[0.056] =
2
AFM-16AF
DACT-UD2
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
X[0.025]
X[0.020]
X[0.040]
X[0.002]
X[0.064]
[
[
[
[
[
[
[
[
]
]
]
]
]
]
]
]
X[0.065] =
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
X[0.025]=
X[0.017]=
X[0.040]=
X[0.002]=
X[0.025]=
X[0.005]=
X[0.029]=
3
LDM-32F
X[0.056] =
LDM-E32F
X[0.018]=
X[0.064]=
LCD-80F & LCD-80FC
4XTMF
4
X[0.005]=
5
X[0.011] =
4-wire Detector Heads
Power Supervision Relays
SLC-2LS Expander
CP350 & CP355
SD350 & SD355
SD350T & SD355T
AD350 & AD355
H350 & H355
X[
] =
X[
]=
X[
]=
6
X[0.025]=
X[0.02500]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.001]=
X[0.025]=
X[0.025]=
X[0.01900]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.001]=
X[0.02600]=
H350R & H355R
H355HT
D350P & D350PL
D350RP & D350RPL
7
B501BH & B501BHT
maximum alarm draw
for all devices:
B224RB Relay Base
B224BI Isolator Base
MMF-300
X[0.00050]=
X[0.00045]=
X[0.00040]=
X[0.00350]=
X[0.00075]=
X[0.000375]=
X[0.00027]=
X[0.00200]=
X[0.00030]=
X[0.00039]=
X[0.00225]=
X[0.00027]=
X[0.00145]=
X[0.00040]=
X[0.00050]=
X[0.00045]=
X[0.00040]=
X[0.00350]=
X[0.00075]=
X[0.000375]=
X[0.00027]=
X[0.00200]=
X[0.00030]=
X[0.00039]=
X[0.00225]=
X[0.00027]=
X[0.00145]=
X[0.00040]=
with one (1) SLC Loop
with two (2) SLC Loops
0.400
0.800
MMF-300-10
MDF-300
MMF-301
MMF-302
MMF-302-6
BG-12LX
CMF-300
CMF-300-6
CRF-300
CRF-300-6
I300
8
NAC #1
[
[
[
[
[
]
]
]
]
]
X[
X[
X[
X[
[
]=
]=
]=
]=
NAC #2
NAC #3
NAC #4
Current Draw from TB3
[
]=
]=
[
]
[
]=
9
(nonalarm )
10
Sum each column for
totals
Primary Non-Alarm =
Primary Alarm =
Secondary Non-Alarm =
Table 5.3 System Current Draw Calculations
1 All eight ACM-8RF relays activated on a single module.
2 All annunciator LEDs on
3 LDM-32F with LEDs on
4 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
5 Refer to the Device Compatibility Document for standby current.
6 Must use compatible listed Power Supervision Relay.
7 Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
8 Current limitation of Terminal TB4 circuits is 3.00 amps per NAC.
9 The total standby current must include both the resettable (TB3 Terminals 1 & 2) and nonresettable (TB3 Terminals
3 & 4, 5 & 6) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not
exceed maximum ratings specified. Current limitations of TB3 circuits is 3.0 amps per output
10 Total current draw listed above cannot exceed 7.0 amps in alarm.
176
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Calculating the Battery Size
Power Supply Calculations
5.4 Calculating the Battery Size
Use Table 5.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load
determines the battery size (in AH), required to support the control panel under the loss of AC
power. Complete Table 5.4 as follows:
1. Enter the totals from Table 5.3 on page 176, Calculation Columns 2 and 3 where shown.
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below).
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere
hours.
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH).
5. Write the ampere hour requirements on the Protected Premises label located inside the cabinet
door.
Secondary Standby Load
(total from Table 5.3 Calculation
Column 3)
Required Standby Time
(24 hours)
[
]
X[
]
=
AH
Primary Alarm Load
(total from Table 5.3 Calculation
Column 2)
Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
[
]
X[
]
=
=
X
=
AH
AH
Sum of Standby and Alarm Ampere Hours
Multiply by the Derating Factor
1.2
Battery Size, Total Ampere Hours Required
AH
Table 5.4 Total Secondary Power Requirements at 24 VDC
5.4.1 NFPA Battery Requirements
•
NFPA 72 Local, Proprietary, Central, Auxiliary and Remote Station Fire Alarm Systems
require 24 hours of standby power followed by 5 minutes in alarm
•
NFPA requires 24 hours of standby plus 15 minutes activation for audio systems. The total
ampere hours required cannot exceed 26 AH with an internal charger
5.4.2 Selecting and Locating Batteries
Select sealed lead acid batteries that meet or exceed the total ampere hours calculated in Table 5.4.
The control panel can charge batteries in the 12 AH to 26 AH range. The control panel cabinet is
capable of housing batteries up to 18 AH. Batteries larger than 18 AH require the BB-26, BB-55F,
or other UL-listed external battery cabinet.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
177
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A: Software Zones
A.1 Correlations
Setup and configuration of an addressable system is different than a conventional system. In a
conventional system, assignment of input devices (smoke detectors, pull stations, heat detectors,
etc.) to zones is accomplished through wiring. The wiring is direct from clearly marked panel
terminals to any device assigned to a particular zone. Connection of output devices (horns, bells,
strobes, etc.) in a conventional system is accomplished by direct wiring of the output devices to
Notification Appliance Circuit terminals.
In an addressable system, a minimum of a single pair of wires (SLC communication loop) is used
to connect all addressable input and output devices. Communications between the FACP (Fire
Alarm Control Panel) and all addressable devices takes place over the wire pair which originates
from the FACP. Software programming is used to configure the system as opposed to direct wiring.
Zone assignments are created via software means, hence the term software zones.
Setup of an FACP software zone is accomplished by panel programming. Each addressable device
can be assigned to a maximum of five software zones. Each software zone, however, may have
1
from 1 to 99 addressable input devices assigned to it and from 1 to 99 addressable output devices
assigned to it.
Monitor and control modules comprise one group of 99 addresses, with each module having a
unique address from 1 to 99 . Detectors comprise a separate group of 99 addresses, each detector
having a unique address from 1 to 99 in its group. Be careful not to duplicate addresses within any
one group (modules and detectors). Refer to the following page for an example of zoning.
In the example on the following page:
•
Zone 01 has the following addressable devices assigned to it:
• SD350 smoke detectors with addresses 01 and 02
• MMF-300 monitor module with address 01
• MMF-302 monitor module with address 02 and 03
• CMF-300 control modules with addresses 05, 06, 07, 09, and 13
Zone 02 has the following addressable devices assigned to it:
• MMF-302 monitor module with addresses 02 and 03
• CP350 smoke detectors with addresses 03 and 04
• CMF-300 control modules with addresses 08, 09, and 10
Zone 03 has the following addressable devices assigned to it:
• SD350 smoke detectors with addresses 05, 06, and 07
• MMF-302 control module with address 04
•
•
• CMF-300 control modules with addresses 09, 11, and 12
The example points out some of the key assignment features of the FACP. Addresses of detectors
are not duplicated. Addresses of monitor and control modules are not duplicated. The control
module with address 09 is assigned to three software zones (providing floor above and floor
below). Be careful to properly plan the installation prior to installing any devices.
1. CLIP or Classic Loop Interface Protocol devices (modules and detectors) can only have
unique addresses of 1 to 99. Newer LiteSpeed devices (modules and detectors) can have
unique addresses of 1 to 159 which means each zone can have up to 159 input and output
devices assigned to it.
178
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Correlations
Software Zones
Correlation of Input and Output Zones
Input Devices
Zones
Output Devices
SD350
01
CMF-300
13
SD350
02
CMF-300
05
ZONE
01
MMF-300
01
CMF-300
06
MMF-302
02
CMF-300
07
CMF-300
09
MMF-302
03
CMF-300
08
CP350
03
ZONE
02
CMF-300
10
CP300
04
SD350
05
CMF-300
11
SD350
06
ZONE
03
SD350
07
CMF-300
12
MMF-302
04
The zone correlations which are shown graphically above are also presented in Table A.1 on
page 180 and Table A.2 on page 181.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
179
Download from Www.Somanuals.com. All Manuals Search And Download.
Software Zones
Correlations
DETECTOR ZONE ASSIGNMENT
Device
Type
Zone
Number
1
Device
Type
Zone
Number
Address
ADJ/NOUN
Address
ADJ/NOUN
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
SD350
FIRST HALL
ELEV. LOBBY
2ND FLOOR
ROOM 210
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
SD350
CP350
CP350
SD350
SD350
SD350
1
2
2
3
3
3
3RD FLOOR
MEZZANINE
MECH. ROOM
Table A.1 Detector Programming Sheet Example
180
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Correlations
Software Zones
MONITOR/CONTROL MODULE ZONE ASSIGNMENT
Zone
Number
Device
Type
Zone
Number
Address
Device Type
ADJ/NOUN
Address
ADJ/NOUN
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
MMF-300
MMF-302
MMF-302
MMF-302
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
CMF-300
1
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
1, 2
1, 2
3
1
1
1
2
1, 2, 3
2
3
3
1
Table A.2 Module Programming Sheet Example
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
181
Download from Www.Somanuals.com. All Manuals Search And Download.
Software Zones
Correlations
DETECTOR ZONE ASSIGNMENT
Device
Type
Zone
Number
Device
Type
Zone
Number
Address
ADJ/NOUN
Address
ADJ/NOUN
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
Table A.3 Blank Detector Programming Sheet - 1 of 2
182
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Correlations
Software Zones
DETECTOR ZONE ASSIGNMENT
Device
Type
Zone
Number
Device
Type
Zone
Number
Address
ADJ/NOUN
Address
ADJ/NOUN
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
Table A.4 Blank Detector Programming Sheet - 2 of 2
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
183
Download from Www.Somanuals.com. All Manuals Search And Download.
Software Zones
Correlations
MONITOR/CONTROL MODULE ZONE ASSIGNMENT
Device
Device
Type
Zone
Zone
Number
Address
ADJ/NOUN
Address
ADJ/NOUN
Number
Type
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
Table A.5 Blank Module Programming Sheet - 1 of 2
184
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Correlations
Software Zones
MONITOR/CONTROL MODULE ZONE ASSIGNMENT
Device
Device
Type
Zone
Zone
Number
Address
ADJ/NOUN
Address
ADJ/NOUN
Number
Type
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
Table A.6 Blank Module Programming Sheet - 2 of 2
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
185
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Default Programming
The following table provides a list of the programming options and their factory default settings.
Program Option
Master Password
Maintenance Password
Detector Programming
Detector Type
Factory Default
00000
Program Option
Factory Default
NAC Enable
Enabled
11111
NAC Silenceable
Yes
Not Installed
Smoke-Photo
Off
NAC Type
Bell
NAC Sync Type
System Sensor
Detector Verification
Detector Walktest
Detector PAS
NAC Autosilence
0
Yes
NAC Coding
Steady
Zone 000 only
0
No
NAC Zones
Detector Presignal
Detector Zone Assign.
Detector Adj/Noun
Module Programming
Module Type
No
NAC Silence Inhibit
Relay 1
000 only
none
Alarm
Trouble
Supervisory
No
Relay 2
Not Installed
Monitor
Yes
Relay 3
On Board DACT
Module Walktest
(not used)
Annunciator Terminal Mode
Annunciator ACS Mode
UDACT
No
No
Module Presignal
Module Zone Assign.
Module Adj/Noun
Zone 0 Enable
No
No
000 only
none
ACS Installed
No
Printer-PC
No
Enabled
Enabled
Enabled
Enabled
.....................
Enabled
Disabled
Monitor
Style 4
Printer Baud
9600
Off
Zone 1 Enable
Canadian Option
Zone 2 Enable
Waterflow Silenceable
ANN-BUS Enabled
Central Station Reporting
AC Loss Delay
No
Zone 3 Enable
No
.........................through..........
Zone 99 Enable
Disabled
2 Hours
First Available
By Point
No
Special Zones 97, 98 & 99
Zones 0 - 99 Type
Loop 1 & 2 Style
Loop 1 & 2 Protocol
Trouble Reminder
Banner
DACT Backup Reporting
DACT Report Style
ANN Enabled
LiteSpeed
Off
ANN-BUS Modules Addr. 1 - 8
ANN-S/PG Port
None
Parallel
9600
7
ANN-S/PG Baud
Time Format
12 Hr
ANN-S/PG Data Bits
ANN-S/PG Parity
Hours Setting
12
Even
1
Minutes Setting
00
ANN-S/PG Stop Bits
ANN-S/PG Offline Timer
ANN-S/PG Printer Supervision
ANN-80 Piezo Enabled
ANN-80 Lock Enabled
ANN-80 Acknowledge Button Enabled
ANN-80 Silence Button Enabled
ANN-80 Reset Button Enabled
ANN-80 Drill Button Enabled
ANN-I/O Point/Zone
ANN-I/O Range
Second Settings
AM-PM Setting
00
60
AM
No
Month Setting
01
Yes
Day Setting
01
Yes
Year Setting
00
Yes
PK-Plus Secret Code
Trouble Call Limit
Daylight Savings
Month Start Daylight Savings
Week Start Daylight Savings
Month End Daylight Savings
Week End Daylight
Verification
00000000
Yes
0
Yes
Yes
Yes
March
Zone
00-29
2nd Week
November
ANN-I/O Active LEDs Only
ANN-RLY Relay 1
................through.......................
ANN-RLY Relay 10
ANN-LED Point/Zone
1st Week
Zone 1
............
Zone 10
Zone
No
0
Ring Count
PAS Timer
0
Presignal Timer
0
ANN-LED Alarms/ATS (Alarm, Trbl, Supv) ATS
ANN-LED Range 0 - 9
Waterflow Retard Timer
0
186
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix C: NFPA Standard-Specific Requirements
The FACP has been designed for use in commercial, industrial and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA)
Standards outlined in this Appendix. The minimum system components required for compliance
with the appropriate NFPA standard are listed below:
Fire Alarm Control Panel
Contains the main control board, cabinet (backbox and door), main power supply transformer and
power supply.
Batteries
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
The following additional equipment is needed for compliance with the NFPA 72 standards listed
below:
NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station
Service
411UDAC for connection to a compatible listed Central Station DACR or Protected Premises
OR
411UD may be installed as illustrated in Figure C.2, “FACP Connection to 411UD,” on page
189.
OR
4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver. See Figure
C.4, “Remote Station Connection Using 4XTMF Module,” on page 191, for installation
instructions for this unit.
NFPA 72 Auxiliary Fire Alarm System
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled “4XTMF Transmitter Module
Installation” on page 55 and as outlined in Figure C.3, “Municipal Box Connected to 4XTMF
Transmitter Module,” on page 190.
NFPA 72 Proprietary Fire Alarm System
FACP Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.5,
“Proprietary Protective Signaling System,” on page 192, for installation instructions for this unit.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
187
Download from Www.Somanuals.com. All Manuals Search And Download.
NFPA Standard-Specific Requirements
NFPA Signaling Systems for Central Station Service (Protected Premises
Unit)/Remote Station
The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UDAC. The relay contacts from the FACP may be used to trip any dialer UL listed for Central
Station/Remote Station Services.
Notes:
1. Reference the 411UDAC Manual for additional information
2. Program the 411UDAC for slave operation
3. The FACP must be programmed for AC Loss Reporting Delay This prevents the transmission
of a trouble on the loss of AC power
Program the 411UDAC as follows:
Channel 1 - Normally Open Contact
Device (alarm)
Channel 2 - Host Panel Trouble
Channel 3 - Supervisory
411UDAC Relay 2 Output (DACT Trouble)
Channel 2/Zone 2
Channel 1/Zone 1
2.2K
Monitor Module
ELR resistor
Channel 3/Zone 3
ELR
2.2K EOLR
Note: The Monitor Module input,
which is being used to monitor the
411UDAC Relay Output
1 2 3 4 5 6 7 8 9 10
programmed for DACT Trouble
(requires optional 411RK Relay Kit),
must be programmed as ‘Trouble’ at
the FACP. The 411UDAC must be
programmed as a Slave
Communicator (programming
address 64 set to 2).
411UDAC
Monitor Module Circuit Input
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion
charts for type V and type
H modules.
UL listed 2.2K ELRs (P/N 27070)
TB1
Monitor Module*
SLC Loop
AC wiring for
411UDAC/FACP must
be connected to the
same branch circuit.
123456
123
FACP
Figure C.1 Central Station Service Using 411UDAC
411UDAC
FACP
TB1-3
TB1-1
TB5-3
TB5-2
TB5-6
TB5-4
TB2-1
Alarm
TB2-2
TB2-3
Trouble
TB2-4
TB2-5
Supervisory
TB2-8
Table C.1 411UDAC Connections to FACP
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
188
Download from Www.Somanuals.com. All Manuals Search And Download.
NFPA Standard-Specific Requirements
The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the FACP may be used to trip any dialer UL listed for Central
Station/Remote Station Reporting Services.
Note: The Monitor Module input, which is being used to monitor
the 411UD Relay #2 Output (programmed for DACT Trouble),
must be programmed as ‘Trouble’ at FACP.
Channel1
1
Channel 4 (2.2K ELR)
2
Channel 2
3
4
Channel 3
5
6
Monitor Module ELR resistor
7
8
1
2
3
4
5
Relay Output (DACT Trouble)
6
7
8
9
411UD
FACP
J4 Not Installed
Supervisory Relay
Monitor Module Circuit Input
FACP
Trouble Relay
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion
charts for type V and type
H modules.
24 VDC
nonresettable
power
FACP
Alarm Relay
(2.2K ELRs
P/N 27070)
Monitor Module*
SLC Loop
+
-
1 2 3
1 2 3 4 5 6
FACP
Figure C.2 FACP Connection to 411UD
411UD
FACP
TB1-1
TB1-3
TB5-2
TB5-3
TB5-4
TB5-6
Alarm
Trouble
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
Supervisory
Table C.2 411-UD Connections to FACP
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
189
Download from Www.Somanuals.com. All Manuals Search And Download.
NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP6 on the FACP main circuit board to supervise placement of 4XTMF module and circuit.
3. Cut JP5 on the FACP main circuit board to enable FACP Supervisory relay.
FIRE
+
Municipal Box Circuit
-
Gamewell Model M34-56
Local Energy Municipal Box
Polarities shown in alarm condition
Nonpower-limited
-
+
4XTMF
Figure C.3 Municipal Box Connected to 4XTMF Transmitter Module
190
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
NFPA Standard-Specific Requirements
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP6 on the FACP main circuit board to supervise placement of the 4XTMF
module.
RS82 Remote Station Receiver UL listed.
Refer to Fire•Lite Alarms, Inc., Instruction Manual for Remote
Station Receiver Model RS82.
Polarity Shown is
Normal Standby
+
-
+
-
Power-limited
(Dummy load with a 4.7K, ¼ watt resistor
when no connection is made)
Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.
4XTMF Transmitter Module
Figure C.4 Remote Station Connection Using 4XTMF Module
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
191
Download from Www.Somanuals.com. All Manuals Search And Download.
NFPA Standard-Specific Requirements
NFPA 72 Proprietary Protective Signaling Systems
FACP Addressable Fire Control Panel
FACP Main Board
Form-C Alarm contact programmed to
activate on General Alarm.
Form-C Trouble contact which will automat-
ically activate on any Trouble condition.
Form-C relay contact programmed to
activate on Supervisory condition.
Notes:
1. Connection between the FACP and the
transmitter are supervised by the transmitter.
2. This FACP/Transmitter arrangement can be
employed for NFPA 72 Proprietary Protective
Signaling System.
3. Potter Electric Model EFT-C has not been
tested for UL 864 9th Edition and is for use in
retrofit applications only.
Figure C.5 Proprietary Protective Signaling System
192
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts
NFPA Standard-Specific Requirements
C.1 Central Station/Remote Station Transmitter: Connection
to FACP Dry Contacts
The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value
determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter
manufacturer’s manual for details.
Typical Central Station/Remote Station Transmitter Module
Typical Input Zone Triggers
*Note: The Trouble Relay is a fail-
safe relay. With power applied to
the FACP and no troubles in the
panel, the wiring should be
connected to the NO and C contacts
as indicated in the illustration.
FACP Main Circuit Board
Figure C.6 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
193
Download from Www.Somanuals.com. All Manuals Search And Download.
NFPA Standard-Specific Requirements
MBT-1 Municipal Box Trip - Silenceable
C.2 MBT-1 Municipal Box Trip - Silenceable
The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the
FACP and a Local Energy Municipal Box. The use of an addressable control module programmed
for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the
panel or box.
Connect wires to two
red terminals on box.
Note: 10 maximum loop
resistance due to wiring from
power supply to Municipal Box.
Gamewell Model
M34-56 Local Energy
Municipal Box
(All contacts shown in energized position)
white wire
MBT-1
- To next device
+ on SLC Loop
Braided-shield/Drain Wire
The CMF-300 must be
programmed as Silenceable
and General Alarm.
brown wire
black
EOLR-1 Power
Supervision Relay
red
Alarm polarity shown!
-
+
CMF-300
SLC Loop B+ -B
Shield
+
-
24 VDC, Nonresettable
FACP
194
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix D: FACP with Keltron
The following figure illustrates the connections between the FACP and Keltron
Receiver/Transmitter.
CAUTION:
POSSIBLE EQUIPMENT DAMAGE
!
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON
MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND MODULE
MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
Tip
Tip
Ring
Telephone Line
Ring
Earth
Earth
To Central/
Remote
Station
UL Listed
UL Listed
8th Edition Only
8th Edition Only
To Power
Supply
*Note: For more
information, refer to
Keltron manual.
Sprinkler
Supervisory Signal
Alarm/Trouble Signal
24 VDC
nonresettable power
4XTMF Module
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in their actual
positions in order to clarify wiring connections)
Figure D.1 Wiring to Keltron Printer
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
195
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix E: Wire Requirements
T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total
resistance of any branch cannot exceed 40 ohms. The total wire length of all branches cannot
exceed 10,000 feet (3,000 m).
Connecting external system accessories to the FACP main circuits must be carefully considered to
ensure proper operation. It is important to use the correct type of wire, wire gauge and wire run
length for each FACP circuit. Reference the chart below to specify wire requirements and
limitations for each FACP circuit.
Note:
1. If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of
encountering problems can be greatly reduced by exclusively employing electronic sounders
instead of more electronically noisy notification appliances such as electromechanical bells or
horns.
2. If two SLC loops are to be installed in conduit, each loop must be installed in separate conduit.
3. The SLC can be programmed to operate in LiteSpeed mode (factory default setting) for a
quicker device response time. While shielded wire is not required in LiteSpeed mode, it is
recommended that all SLC wiring be twisted-pair to minimize the effects of electrical
interference. Use the following table to determine the specific wiring requirements for the
SLC when unshielded wire is used:
CIRCUIT CONNECTIONS
WIRE REQUIREMENTS
Recommended Max.
Circuit Type
Circuit Function
Wire Type and Limitations
Distance
Wire Gauge and Compatible Brands
Feet (meters)
2
Connects to
Twisted, shielded pair
10,000 (3,000 m)
12 AWG (3.25 mm ): Genesis 4410,
Addressable Devices 40 ohms maximum per length
Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm ):Genesis 4408 & 4608
2
of Style 6 and 7 loops. 40 ohms 8,000 (2,400 m)
per branch maximum for Style 4
Signal 98430, Belden 9581, WPW995
2
CLIP MODE
loops
4,875 (1,450 m)
16 AWG (1.30 mm ): Genesis 4406 & 4606
Signal 98630, Belden 9575, WPW991
Direct Burial Cable Isotec NP713110VNQ-S
2
3,225 (980 m)
18 AWG (0.75 mm ): Genesis 4402 & 4602
Signal 98300, Belden 9574, WPW975
Direct Burial Cable Isotec NP714110VNQ-S
SLC loop
(power-limited)
2
Twisted, unshielded pair
10,000 (3,000 m)
12 AWG (3.25 mm ): Belden 5020UL &
40 ohms maximum per length
of Style 6 and 7 loops. 40 ohms 8,000 (2,400 m)
per branch maximum for Style 4
6020UL, Genesis WG-4315 & WG-4515
14 AWG (2.00 mm ):Belden 5120UL &
2
6120UL, Genesis WG-4313 & WG-4513
2
loops
4,875 (1,450 m)
16 AWG (1.30 mm ): Belden 5220UL &
LITESPEED MODE
Connects to
6220UL, Genesis WG-4311 & WG-4511
18 AWG (0.75 mm ): Belden 5320UL &
6320UL, Genesis WG-4306 & WG-4506
2
3,225 (980 m)
1
2
Untwisted, unshielded pair
3,000 (900 m)
12-18 AWG (3.25 - 0.75 mm ) using listed wire
2
ACS-BUS
Twisted pair with characteristic 6,000 (1,800 m)
12 AWG (3.25 mm )
(EIA-485)
annunciator modules impedance of 120 ohms
(power-limited)
ANN-BUS
(EIA-485)
(Power-limited)
Connects to
annunciator modules
Twisted pair
6,000 (1,800 m)
50 (15 m)
requirements.
2
EIA-232
(power-limited)
connects to remote
PC computer
Twisted, shielded pair
18 AWG (0.75 mm ) minimum
2
MMF-300 and
MMF-301
Initiating Device
Circuit
Maximum loop wire resistance 2,500 (760 m)
is 40 ohms for the MMF-300
12-18 AWG (3.25 - 0.75 mm )
(power-limited)
and 20 ohms for the MMF-301
2
MMF-302
(power-limited)
Initiating Device
Circuit
No more than a 2.4 volt drop
allowed at end of circuit.
Maximum loop wire resistance
is 25 ohms
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm )
2
CMF-300
Notification Appliance In alarm, no more than a 1.2
Distance limitation set 12-18 AWG (3.25 - 0.75 mm )
(power-limited)
Circuit
volt drop allowed at end of
circuit
by 1.2 volt maximum
line drop
Table E.1 FACP Wire Specifications
1
When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.
196
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
NAC Wiring
Wire Requirements
E.1 NAC Wiring
The following table lists NAC wiring requirements for the FACP.
CLASS-B
Max. allowable wire pair length
(feet)
CLASS-A
Max. allowable wire pair length
(feet)
Max.
allowable
total loop
resistance
(ohms)
NAC Load
(Amps)
AWG 12
solid
AWG 14
solid
AWG 16
solid
AWG 18
solid
AWG 12
solid
AWG 14
solid
AWG 16
solid
AWG 18
solid
0.25
0.5
0.75
1
12.72
6.36
4.24
3.18
2.54
2.12
1.82
1.59
1.41
1.27
3295
1648
1098
824
2072
1036
691
518
414
345
296
259
230
207
1301
650
434
325
260
217
186
163
145
130
819
409
273
205
164
136
117
102
91
1648
824
549
412
330
275
235
206
183
165
1036
518
345
259
207
173
148
129
115
104
650
325
217
163
130
108
93
409
205
136
102
82
1.25
1.5
1.75
2
659
549
68
471
58
412
81
511
45
2.25
2.5
366
72
330
82
65
41
Table E.2 NAC Wiring Requirements for FACP
Notes:
1. Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
197
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix F: HVAC Control
The FACP can be programmed to shut down a building’s HVAC fans in the event of a fire. The
fans cannot be restarted until the fire alarm condition has been cleared and the FACP has been reset
to a normal (non-alarm) condition.
IMPORTANT! This HVAC feature is not to be used for smoke control. It is only designed to shut
down fans during a fire alarm condition.
F.1 Control Module Operation
F.1.1 HVAC SHUTDN
The HVAC SHUTDN type code can be assigned to any addressable control relay module for the
purpose of shutting down HVAC fans during a fire alarm condition. Devices connected to a
module with this type code are unsupervised. To program this feature in the FACP:
•
•
•
Program the HVAC SHUTDN type code to the control module which will be used to shut
Program the control module to a software zone and program alarm input devices which, when
activated are to cause fan shutdown, to the same software zone (refer to Zone Assignment
Monitor the control module using an addressable monitor module programmed for Trouble
Monitor. The monitor module label should be programmed to indicate HVAC SHUTDOWN.
When the control module is active (HVAC SHUTDN), the monitor module will indicate a
trouble condition at the FACP and the display should indicate the HVAC is shut down.
Once activated, the HVAC SHUTDN control module remains activated, even if the FACP is
silenced or reset. After the alarm condition on the FACP has been cleared and the panel reset, the
HVAC SHUTDN control module remains activated and the fans remain off. The monitor module
programmed for Trouble Monitor which is being used to supervise the control module, will indicate
a trouble condition at the control panel and the LCD should display that the HVAC is shut down.
The fans can only be restarted when the HVAC SHUTDN control module is deactivated by the
HVAC RESTART module.
F.2 Monitor Module Operation
F.2.1 HVAC RESTART
The HVAC RESTART type code can be assigned to any addressable monitor module for the
purpose of resetting (deactivating) the HVAC SHUTDN control module and turning the fans back
on. The HVAC RESTART monitor module acts globally throughout the FACP system and
therefore is not programmed to a particular software zone. To program this feature in the FACP:
•
Program the HVAC RESTART type code to the monitor module which will be used to
deactivate the HVAC SHUTDN control module and restart the fans (refer to Type Monitor
under the section titled “Edit Module Screen for Monitor Module” on page 79).
The HVAC RESTART monitor module does not latch when activated. Pressing a switch connected
to the monitor module will deactivate the HVAC SHUTDN control relay module only if there are
no alarm conditions. The HVAC SHUTDN control relay module can be deactivated if trouble
conditions exist on the FACP.
198
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Monitor Module Operation
HVAC Control
F.2.2 HVAC OVRRIDE
The HVAC OVRRIDE type code can be assigned to any addressable monitor module for the
purpose of overriding or preventing the HVAC SHUTDN control modules from activating. The
HVAC OVRRIDE monitor module acts globally throughout the FACP system and therefore is not
programmed to a particular software zone. To program this feature in the FACP:
•
Program the HVAC OVRRIDE type code to the monitor module which will be used to
override the HVAC SHUTDN control module and prevent the fans from turning off (refer to
Type Monitor under the section titled “Edit Module Screen for Monitor Module” on page 79).
The HVAC OVRRIDE monitor module does not latch when activated. Activating a switch
connected to the monitor module will override all HVAC SHUTDN control relay modules in the
system, preventing the HVAC SHUTDN modules from activating and causing the FACP LCD to
display an active HVAC OVRRIDE module and turn on the Supervisory LED. Releasing the
switch will allow the HVAC SHUTDN control relay modules to activate with subsequent alarms,
turning off the fans.
As an example, pressing the HVAC OVRRIDE switch with no alarms in the system will prevent the
fans from being turned off when an alarm does occur. As long as the switch is activated, the fans
will not shutdown for any alarms. If the system is still in alarm when the switch is released, the
fans will not shutdown unless another alarm occurs after the switch is released.
Important! If an alarm exists in the system and HVAC Shutdown has already occurred, HVAC
OVRRIDE will have no effect on the HVAC SHUTDN control relay modules. HVAC OVRRIDE
will prevent HVAC Shutdown from occurring only if it is initiated prior to an alarm condition.
NOTE: Activation of the HVAC OVRRIDE module causes a supervisory event that will be
communicated to the Central Station if enabled.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
199
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix G: Canadian Application
•
•
The MS-9600LSC is supplied with the DP-9692 Dress Panel.
When installing and programming the FACP, the Canadian Option must be set to ON prior to
Section of this manual).
•
•
•
ACS Series annunciators are not compatible for Canadian applications.
The LCD-80FC annunciator can be used for optional ancillary annunciation.
The ANN-LED annunciator must be installed in the same room as the FACP. All wiring
between the FACP and ANN-LED must be in metal conduit no longer than 20 feet.
•
•
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
Label located on the FACP backbox door.
To comply with CAN/ULC - S559-04, the DACT-UD2 and 4XTMF must both be utilized.
ANN-LED annunciator must
be in same room as FACP
metal conduit
(max. 20 ft.)
ANN-LED Annunciator
FACP
Figure G.1 FACP Minimum Configuration - Single ANN-LED Annunciator
metal conduit
(max. 20 ft.)
ANN-LED annunciators must
be in same room as FACP
FACP
ANN-LED Annunciators
Figure G.2 FACP Maximum Configuration - Eight ANN-LED Annunciators
200
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
ANN-RLY Annunciator Module 36
ANN-SB80KIT Mounting Kit 28
annunciator 40
Numerics
coil resistance 55
ACM-8RF 14
current 55
installation 55
installation steps 56
voltage 55
annunciator addressing 120
annunciator, remote
see also LCD-80F 40
Auto Silence
NAC 110
A
Automatic Test Operation 156
auxiliary DC power 47
AC Branch Circuit
calculations 174
AC Loss Delay 106
AC Power 46
current 15
current, maximum 46
voltage 15
B
backbox 19
see also cabinet 45
Banner 100
Banner setting 101
battery 19
ACM LED annunciator 60
ACM Series
see also annunciator 40
ACM-16ATF Annunciator 40
ACM-32AF Annunciator 40
ACM-8RF 14
cable connection 46
charger capacity 15
charger, disable 15
charger, external 22
Charging Circuit 15
battery box 22
contact rating 59
see also Relay Control Module 59
ACS LED annunciator 14
add Detector 67
add Module 78
address range 20
baud rate 134
BB-55F
addressable 13
addressable detectors
see also detectors 15
addressable modules 20
see also modules 15
addressing
C
cabinet 19
mounting 42
annunciators 120
Calculate System Current Draw 175
Calculating the Battery Size 177
Central Station/Remote Station Reporting 189
CHG-120F
see also device addressing 100
see also module or detector addressing 20
Adjective
control module 92
monitor module 85
multiple entries 77
Adjective list 75
see also battery charger 22
see also remote battery charger 15
CHG-75
AEM-16ATF Annunciator 40
AEM-32AF Annunciator 40
Alarm 153
see also battery charger 22
see also remote battery charger 15
Class A 47
Class B 47
NAC wiring 49
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
201
Download from Www.Somanuals.com. All Manuals Search And Download.
D–E
Index
Classic Loop Interface Protocol 100
CLIP Mode
Detector
add 67
see also Classic Loop Interface Protocol
adding description 74
delete 68
Clock Format 104
Coded Operation 157
Coding
edit 69
enable/disable 71
screen display 70
type 71
NAC 110
coding
verification 72
two stage operation 111
control buttons 150
control module 20
description display 94
display 88
acceptable range 171
printout 171
Detector Programming 67
device addressing 100
Digital Alarm Communicator/Transmitter
see also DACT-UD2 21
dimensions
edit 88
enable/disable 89
noun 93
silenceable 90
cabinet 44
DIRTY1 172
type 89
DIRTY2 172
type codes 90
Disable 96
Correlations 178
current
Disable Point
Maintenance Level 139
definition 172
AC Power 46
availability 17
maximum 17
D
E
DACT 134
earth ground 46
DACT-UD2 15
edit
functions 52
installation 52
control module 88
detector 69
phone lines 54
see also Digital Alarm Communicator/
Transmitter 21
detector screens 70
module, monitor 79
EIA-232 59
for PC/Printer connection 16
see also Printer/PC interface 14
EIA-485
for ACS annunciators 16
for LCD-80F 16
Enable 95
data
see also detector data and sensitivity 157
values 14
Data Entry
via computer keyboard 61
via keypad 61
Enable/Disable
Date setting 103
Daylight Savings Time 104
DC power
control module 89
detector 71
module, monitor 81
End-of-Line Resistor Assembly 20
Enter key 64
nonresettable 47
resettable 47
see also auxiliary DC power 47
Default Programming 186
Delete Detector 68
Delete Module 79
Description
Erase History 115
exiting
Expander Module 57
see also SLC-2 21
control module 94
detector label 77
monitor module 87
202
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
F–N
Maintenance 151
see also Indicators 17
Supervisory 151
F
FACP
see also Fire Alarm Control Panel 13
Trouble 151
Features 13
LED annunciator 40
Local Energy Municipal Box Service 55
Local Programming 62
Loop Setup 99
Fire Alarm Control Panel
see also FACP 13
G
M
general alarm zone 84
see also zone Z00 74
ground fault 59
main circuit, mounting 42
levels 172
maintenance alert 172
Manual programming 62
Medical Alert 156
Mode key 64
H
Hazard Condition 155
History 115
erase 115
Maintenance Level 140
view events 115
Module
History file 14
add 78
HVAC Control 198
HVAC OVRRIDE 199
HVAC RESTART 198
HVAC SHUTDN 198
addressing 20
delete 79
edit monitor 79
enable/disable 81
see also addressable modules 20
Module Programming 78
Monitor module 20
adjective 85
I
Indicators 17
Installation 42
intelligent 13
Inventory 13
INVREP 172
enable/disable 81
noun 86
noun/adjective 84
type 82
type action 83
K
Type list 82
type selection 83
Mounting
Key Panel 18
function keys 18
cabinet 42
service/program keys 18
keyboard and keypad 61
Keypad/Display
main circuit board 42
municipal box transmitter
see also 4XTMF module 55
removal and installation 51
N
L
Auto Silence 110
coded 157
lamp test 18
LDM Series annunciator 40
LED
coding 110
current 16
End-of-Line Resistor 16
power 14
AC Power 150
silence inhibit 112
Alarm Silenced 151
Battery 151
Disabled 151
silenceable 109
Fire Alarm 150
Style configuration 48
Style Y wiring diagram 49
Ground 151
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
203
Download from Www.Somanuals.com. All Manuals Search And Download.
O–P
Index
synchronized 157
Output Circuits 18
voltage drop 15
voltage, operating 15
wiring Style 47
P
NAC enable/disable 108
NAC options 100
NAC type 109
PAS BYPASS 159
PAS timer 105
change 135
Master Level 1 64
PC (personal computer)
configuration 59
connection 58
ground fault 59
Phone Line 2
supervision 169
phone lines
DACT installation 54
Piezo
NACKEY card 48
N-ELR Mounting Plate 21
NFPA 72 Central Station Service (Protected
NFPA 72 Proprietary Fire Alarm System 187
NFPA 72 Proprietary Protective Signaling Sys-
tems 192
NFPA 72 Remote Station Protective Signaling
System 191
NFPA Battery Requirements 177
NFPA Signaling Systems for Central Station Ser-
vice (Protected Premises Unit)/Remote Station
see also sounder 18
Point Program 67
see also PAS 14
power
NFPA Standard 187
nonsilenceable
NAC 14
nonresettable 16
resettable 89
nonsilenceable waterflow 98
resettable smoke 16
power supply calculations 174
power-limited
relay connections 47
Power-up
first time 63
function 158
Noun
monitor module 86
multiple entries 77
Noun list 76
control module 91
monitor module 84
selection 84
primary power
see also AC Power 46
printer
O
Operating Instructions 150
Operation
alarm 153
disable/enable 156
hazard condition 155
medical alert 156
NAC 157
baud rate 134
configuration 59
connection 58
ground fault 59
setup 59
normal 151
process monitor 155
programmed zone 156
supervisory 154
trouble 152
Printer/PC interface 14
Process Monitor 155
PROCMON AR 113
Program
waterflow 156
check 137
annunciators/UDACT 118
Printer/PC 134
check correlations 137
clear 136
Program Check
Options 13
Maintenance Level 141
204
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
R–S
program keys
see also Key Panel 18
autoprogramming 62
exiting 63
current 47
see also Smoke Detector Power 16
factory default 186
Level 1 63
Level 2 63
manual 62
Master Level 1 65
S
Secondary Power Requirements 177
see also smoke detector sensitivity 157
Signal rate 14
modules 78
Signaling Line Circuit
see also SLC 15
silenceable
off-line computer 62
via computer keyboard 61
via panel keypad 61
Programming Levels 63
Programming Screens 63
Programming Utility
see also PS-Tools 21
PRT/PK-CABLE
control module 90
NAC 109
Silenceable Alarm Relay 113
silenceable circuits
synchronized signals 109
Silenceable waterflow 148
for PC/Printer connection 59
current 15
reference manual 15
resistance 15
see also Signaling Line Circuit 13
Style 18
R
exiting 63
history 167
voltage 15
NAC 166
power 164
Print 171
printer/PC 170
wiring length 15
SLC Loop Protocol 100
SLC loop selection 67
SLC Style 99
program check 167
relay 166
SLC-2 57
installation 57
system point 162
Time-Date 173
timers 165
wiring 58
SLC-2 Expander Module 21
smoke detector
trouble reminder 165
zones 163
Real-Time Clock 157
connections 47
chamber reading 171
sensitivity 157
Smoke Detector Power
current 16
sounder 18
fixed 47
programming 113
selections 113
Specifications 15
strobe synchronization 14
Style 13
Style Y 47
Relay Control Module
see also ACM-8RF 59
Relay options 100
Remote Programming 62
Remote Station Service 56
remote switch functions 14
NAC wiring 49
NC configuration 48
Style Z 47
NAC configuration 48
wiring 49
subscreen 63
supervise
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
205
Download from Www.Somanuals.com. All Manuals Search And Download.
T–Z
Index
Phone Line 2 169
Supervisory 154
measurements 164
ranges 164
SUPERVISORY AR 113
sync
W
programming 108
audible 116
see also synchronization 112
by manufacturer 112
programming 112
see also strobe synchronization 14
synchronized 157
Synchronized Signals 157
and silenceable circuits 109
System
Maintenance Level 143
System Point 162
Maintenance Level 142
operation 160
selection 84
silent 116
waterflow
Waterflow Retard Timer 159
Wire Requirements 196
wiring
System Setup 100
AC Power 46
earth ground 46
NAC Style Y 49
NAC Style Z 49
SLC-2 58
T
Time and Date
Maintenance Level 143
Time setting 103
Timers 100
wiring Style 13
Transmitter Module 55
see also 4XTMF module 21
TR-CE trim ring 22
Trouble 152
trouble display 152
trouble relay 14
trouble responses 152
Two Stage 96
two stage operation 111
Type
Z
Z97
PAS zone 73
Z98 73
Zone 97 96
Zone 98 96
control module 90
Zone Setup 95
Maintenance Level 144
Zone Z97 73
Zone Z98
control module 89
detector 71
monitor module 82
NAC 109
type code
pre-signal zone 73
see also software zones 14
zones per device 73
control module 90
supervision 157
verification 14
U
UL power-limited wiring requirements
see also power-limited and nonpower-lim-
ited 47
V
Verification
detector 72
Verify Loops 114
View Events 115
voltage
206
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Download from Www.Somanuals.com. All Manuals Search And Download.
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its
Northford, Connecticut facility and sold by it to its authorized
Distributors shall be free, under normal use and service, from defects
in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The
Products manufactured and sold by Manufacturer are date stamped at
the time of production. Manufacturer does not warrant Products that
are not manufactured by it in its Northford, Connecticut facility but
assigns to its Distributor, to the extent possible, any warranty offered
by the manufacturer of such product. This warranty shall be void if a
Product is altered, serviced or repaired by anyone other than
Manufacturer or its authorized Distributors. This warranty shall also
be void if there is a failure to maintain the Products and the systems in
which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND
DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER
EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,
TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY
MANUFACTURER
INCLUDING
WITHOUT
LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR
ANY PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE
LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY
ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer
with respect to its products and replaces all previous warranties and is
the only warranty made by Manufacturer. No increase or alteration,
written or verbal, of the obligation of this warranty is authorized.
Manufacturer does not represent that its products will prevent any loss
by fire or otherwise.
Warranty Claims.
Manufacturer shall replace or repair, at
Manufacturer's discretion, each part returned by its authorized
Distributor and acknowledged by Manufacturer to be defective,
provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed
Manufacturer's Return Material Authorization form. The replacement
part shall come from Manufacturer's stock and may be new or
refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND
EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.
Warn-HL-08-2009.fm
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
207
Download from Www.Somanuals.com. All Manuals Search And Download.
World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.firelite.com
Download from Www.Somanuals.com. All Manuals Search And Download.
|