Honeywell Smoke Alarm 5820XL User Manual

INTELLIKNIGHT®  
5820XL  
Addressable Fire System  
Installation and  
Operations Manual  
Part Number 151209 Rev R  
ECN 09- 570 08/27/09  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Procedure  
Adherence to the following will aid in problem-free installation with long-term reliability:  
Installation Precautions - Adherence to the following will aid in problem-free installation  
with long-term reliability: WARNING - Several different sources of power can be connected  
to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit  
and associated equipment may be damaged by removing and/or inserting cards, modules, or  
interconnecting cables while the unit is energized. Do not attempt to install, service, or operate  
this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after  
Software Changes: To ensure proper system operation, this product must be tested in  
accordance with NFPA 72 after any programming operation or change in site-specific  
software. Re-acceptance testing is required after any change, addition or deletion of system  
components, or after any modification, repair or adjustment to system hardware or wiring. All  
components, circuits, system operations, or software functions known to be affected by a  
change must be 100% tested. In addition, to ensure that other operations are not inadvertently  
affected, at least 10% of initiating devices that are not directly affected by the change, up to a  
maximum of 50 devices, must also be tested and proper system operation verified. This  
system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or  
humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful  
life of the system's standby batteries and the electronic components may be adversely affected  
by extreme temperature ranges and humidity. Therefore, it is recommended that this system  
and its peripherals be installed in an environment with a normal room temperature of 15-27º  
C/60-80º F. Verify that wire sizes are adequate for all initiating and indicating device loops.  
Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.  
Like all solid state electronic devices, this system may operate erratically or can be damaged  
when subjected to lightning induced transients. Although no system is completely immune  
from lightning transients and interference, proper grounding will reduce susceptibility.  
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to  
nearby lightning strikes. Consult with the Technical Services Department if any problems are  
anticipated or encountered. Disconnect AC power and batteries prior to removing or  
inserting circuit boards. Failure to do so can damage circuits. Remove all electronic  
assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible,  
make all cable entries from the sides or rear. Before making modifications, verify that they  
will not interfere with battery, transformer, or printed circuit board location. Do not tighten  
screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in  
reduced terminal contact pressure and difficulty with screw terminal removal. Silent Knight  
fire alarm control panels contain static-sensitive components. Always ground yourself with a  
proper wrist strap before handling any circuits so that static charges are removed from the  
body. Use static suppressive packaging to protect electronic assemblies removed from the  
unit.  
Follow the instructions in the installation, operating, and programming manuals. These  
instructions must be followed to avoid damage to the control panel and associated equipment.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Manual  
FACP operation and reliability depend upon proper installation.  
While installing a fire alarm system may make lower insurance rates possible, it is not a  
substitute for fire insurance! An automatic fire alarm system - typically made up of smoke  
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm  
control with remote notification capability - can provide early warning of a developing fire.  
Such a system, however, does not assure protection against property damage or loss of life  
resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke  
detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in  
walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire  
on another level or floor of a building. A second floor detector, for example, may not sense a  
first floor or basement fire. Furthermore, all types of smoke detectors, including ionization  
and photoelectric types, have sensing limitations. No type of smoke detector can sense every  
kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions,  
escaping gas, improper storage of flammable materials, overloaded electrical circuits, children  
playing with matches, or arson.  
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and  
in rooms used by the system for the connection of alarm transmission wiring,  
communications, signaling, and/or power. If detectors are not so located, a developing fire  
may damage the alarm system, crippling its ability to report a fire. Audible warning devices  
such as bells may not alert people if these devices are located on the other side of closed or  
partly open doors or are located on another floor of a building. A fire alarm system will not  
operate without any electrical power. If AC power fails, the system will operate from standby  
batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced  
sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested  
at least once per year by a qualified fire protection specialist. Equipment used in the system  
may not be technically compatible with the control. It is essential to use only equipment listed  
for service with your control panel. Telephone lines needed to transmit alarm signals from a  
premise to a central monitoring station may be out of service or temporarily disabled. The  
most common cause of fire alarm malfunctions, however, is inadequate maintenance. All  
devices and system wiring should be tested and maintained by professional fire alarm  
installers following written procedures supplied with each device. System inspection and  
testing should be scheduled monthly or as required by National and/or local fire codes.  
Adequate written records of all inspections should be kept.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Section 1  
Requirements and recommendations for proper use of fire alarm systems including smoke  
detectors and other fire alarm devices: .................................................................................. 1-7  
Section 2  
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems - Digital Alarm Communicator  
Transmitter (DACT) 2-3  
Section 3  
151209  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Section 4  
4.13 Flexputs I/O Circuits ........................................................................................................................... 4-30  
2
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Section 5  
Section 6  
151209  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Section 7  
4
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
151209  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Section 8  
6
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Section 9  
Section 10  
Section 11  
Appendix A  
Appendix B  
151209  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
8
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
Introduction  
The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control  
system that meets the requirements of UL 864.  
1.1 Overview of Basic System  
The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit boards  
mounted to an aluminum housing.  
1.1.1 Hardware Features  
The IntelliKnight 5820XL panel has one signaling line circuit (SLC). Up to three  
additional SLC loops can be added using the 5815XL SLC expander. The SLC(s) support  
the SK series addressable detectors and modules or Hochiki protocol detectors and  
modules.  
Each SLC supports up to 99 detectors and 99 modules for a total of 396 detectors and 396  
modules per 5820XL panel when using SK series devices. Alternatively, each SLC  
supports up to 127 Hochiki devices for a total of 508 devices per 5820XL panel.  
6.0A of output power is available through 6 sets of terminals for notification and auxiliary  
applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total  
output power for all 6 circuits must not exceed 6.0A).  
Built-in dual phone line, digital alarm communicator/transmitter (DACT).  
Reports events to central station by point or by zone.  
UL Listed for pre-action and deluge releasing systems.  
Dedicated Form C trouble relay and two general purpose Form C programmable relays.  
Basic system operation can be performed using a key or a user code.  
Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).  
Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on  
one control panel. See sections 4.8 and 4.9 for additional information on these models.  
Printing of detector status, event history, and real time event log available through the  
Model 5824 Serial/Parallel Printer Interface Module (sold separately).  
Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.  
Add 6 Flexput™ circuits with each 5895XL Intelligent Power Module (up to 8 5895XLs  
per system). See note below.  
Add 4 notification/auxiliary power circuits with each 5496 Intelligent Power Module. See  
note below.  
Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any  
combination.  
151209  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
1.1.2 Software Features  
125 software zones, 250 output groups.  
Advanced smoke detector features:  
Automatic drift compensation  
Maintenance alert region  
Point status eliminates calibrated smoke test requirements for NFPA 72  
“JumpStart” feature for easy programming  
Non-volatile event history stores 1000 events  
A choice of output patterns available for notification outputs, including ANSI 3.41  
temporal signal  
®
Built-in synchronization appliance support for AMSECO, Faraday, Gentex , System  
®
®
Sensor , and Wheelock .  
1.2 About this Manual  
This manual is intended to be a complete reference for all installation and operation tasks for  
the 5820XL. Please let us know if the manual does not meet your needs in any way. We value  
your feedback!  
1.2.1 Terms Used in this Manual  
The following terminology is used with the IntelliKnight 5820XL system:  
Table 1-1 Manual Terminology  
Term  
Description  
SLC  
Signaling line circuit  
Module  
The term module is used for all hardware devices except for SLC  
addressable devices and notification appliances. This includes the 5820XL  
panel itself and the built-in 5897 power supply. It also refers to any  
(optional) 5815XL SLC expansion modules.  
Input Point  
An addressable sensing device, such as a smoke or heat detector or a contact  
monitor device.  
Input Zone  
A protected area made up of input points.  
Output Point  
(or Output Circuit)  
A notification point or circuit for notification appliances. Relay circuits and  
auxiliary power circuits are also considered output points.  
Group (or “Output Group”)  
A group of output points. Operating characteristics are common to all  
output points in the group.  
Output (or “Cadence”) Pattern  
Mapping  
The pattern that the output will use, for example, Constant, March Code,  
ANSI 3.41. Applies to zones and special system events. See Section 7.7.3.2  
for additional information.  
Mapping is the process of specifying which outputs are activated when  
certain events occur in the system. Section 6.2 explains mapping in detail.  
1-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Introduction  
1.3 Compatible Products  
Table 1-2 lists the products available from Silent Knight for use with the IntelliKnight  
5820XL.  
Table 1-2: 5820XL Compatible Products  
Type of  
Device  
Model  
Description  
Addressable See Section 5.2 for a list of compatible devices.  
SLC Devices  
Other  
Modules  
5815XL SLC Expander  
Allows an additional 127 Hochiki SLC devices, or 99 SK detectors and 99 SK modules  
to be added to the system. Up to three 5815XLs per system.  
5211 Ground Start Relay  
For use with ground start telephone network. (Do not use in UL installations.)  
5824 Serial/Parallel Printer  
Interface Module  
Allows a printer to be attached for the system for on-site event logging, detector status  
and event history reports. Two maximum per system.  
5895XL Intelligent Power  
Module  
Provides additional power, six Flexput™ circuits, and two 5895XLs and 5496s can be  
Form C relays. Max. 8 per system see Model 5895  
Installation Instructions P/N 151024.  
used in any combination,  
up to a total of eight  
devices on one system.  
5496 Intelligent Power  
Module  
Provides 4 additional Notification Appliance Circuits/  
Auxiliary power. (Up to 8 per system.)  
5860 and 5860R Remote Fire Same operation, similar appearance as on-board  
Alarm Annunciator  
annunciator. Up to 8 5860s per system. 5860 is gray; 5860R  
is red.  
5860TG and 5860TR Trim  
Ring Kit  
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray; 5860TR is  
red.  
5865-3 and 5865-4 LED  
Annunciator  
LED annunciator can display up to 30 LEDs (15 red and 15  
yellow). 5865-4 has key switches for silence and reset, and  
a system trouble LED.  
5865-3, 5865-4, and 5880  
can be used in any  
combination, up to a total  
5880 LED I/O Module  
Driver for up to 40 LEDs. Interfaces with customized  
of eight devices on one  
annunciator boards. In addition the 5880 has eight generic  
panel.  
switch input points.  
5883 General Purpose Relay Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be  
Module  
used with each 5880 module.  
Misc.  
7860 Telephone Cord  
RJ31X cord for connecting phone line to the 5820XL.  
5660 Silent Knight Software For communication and panel programming with a Windows-based computer and  
Suite (SKSS)  
*modem (not sold by Silent Knight, see Table 1-3 for compatible modems). Enables  
remote viewing of detector status and event history.  
5670 Silent Knight Software Facility management software. For remote viewing of detector status and event history.  
Suite (SKSS)  
Requires a modem (not sold by Silent Knight).  
RBB  
Remote Battery Box for mounting backup batteries that are too large to fit into the main  
control panel cabinet.  
Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)  
Note: Models SD500-FRCM, and SD500-FRCM-4 are no longer manufactured, but they are still compatible with  
the IntelliKnight system. Contact Silent Knight if you need information about these modules.  
151209  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
The following modems have been tested by Silent Knight for compatibility with the 5820XL  
and the Silent Knight Software Suite software packages:  
Table 1-3: Compatible Modems  
Manufacturer  
US Robotics  
Model  
28.8  
LifeStyle  
Motorola  
28.8, 3400 series  
Premier 33.6  
MultiTech  
MT19321ZDX  
1.4 How to Contact Silent Knight  
If you have a question or encounter a problem not covered in this manual, contact Silent  
Knight Technical Support at 800-446-6444.  
To order parts, contact Silent Knight Customer Service at 800-328-0103 or in Connecticut  
203-484-7161.  
®
IntelliKnight is a registered trademarks of Silent Knight. Flexput™ is a trademark of Silent  
Knight.  
1-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
Limitations of Fire Alarm Systems  
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected  
premise following the recommendations of the current edition of the National Fire Protection  
Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes,  
and the recommendations contained in Guide for the Proper Use of System Smoke Detectors,  
which is made available at no charge to all installing dealers. A study by the Federal  
Emergency Management Agency (an agency of the United States government) indicated that  
smoke detectors may not go off or give early warning in as many as 35% of all fires. While  
fire alarm systems are designed to provide warning against fire, they do not guarantee warning  
or protection against fire. A fire alarm system may not provide timely or adequate warning, or  
simply may not function, for a variety of reasons. For example:  
Particles of combustion or smoke from a developing fire may not reach the sensing  
chambers of smoke detectors because:  
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or  
smoke flow.  
Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where  
detectors are located.  
Smoke particles may be blown away from detectors by air outlets  
Smoke particles may be drawn into air returns before reaching the detector.  
In general, smoke detectors on one level of a structure cannot be expected to sense fires  
developing on another level.  
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke  
detectors are designed to alarm at various levels of smoke density. If such density levels  
are not created by a developing fire at the location of detectors, the detectors will not go  
into alarm.  
Smoke detectors, even when working properly, have sensing limitations. Detectors that  
have photoelectronic sensing chambers tend to detect smoldering fires better than flaming  
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers  
tend to detect fast flaming fires better than smoldering fires. Because fires develop in  
different ways and are often unpredictable in their growth, neither type of detector is  
necessarily best and a given type of detector may not provide adequate warning of a fire.  
Smoke detectors are subject to false alarms and nuisance alarms and may have been  
disconnected by users. For example, a smoke detector located in or near a kitchen may go  
into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or  
steamy environments may cause a smoke detector to falsely alarm. If the location of a  
smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect  
the smoke detector; call a professional to analyze the situation and recommend a solution.  
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson,  
children playing with matches (especially within bedrooms), smoking in bed, violent  
explosions (caused by escaping gas, improper storage of flammable materials, etc.).  
151209  
1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
Heat detectors do not sense particles of combustion and are designed to alarm only when  
heat on their sensors increases at a predetermined rate or reaches a predetermined level.  
Heat detectors are designed to protect property, not life.  
Warning devices (including horns, sirens, and bells) may not alert people or wake up  
sleepers who are located on the other side of closed or partially open doors. A warning  
device that activates on a different floor or level of a dwelling or structure is less likely to  
awaken or alert people. Even persons who are awake may not notice the warning if the  
alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by  
passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or  
other devices should be provided to warn these people). Any warning device may fail to  
alert people with a disability, deep sleepers, people who have recently used alcohol or  
drugs, or people on medication or sleeping pills.  
Please note that:  
i) Strobes can, under certain circumstances, cause seizures in people with conditions  
such as epilepsy.  
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not  
respond or comprehend the meaning of the signal. It is the property owner’s responsi-  
bility to conduct fire drills and other training exercises to make people aware of fire  
alarm signals and instruct on the proper reaction to alarm signals.  
iii) In rare instances, the sounding of a warning device can cause temporary or permanent  
hearing loss.  
Telephone lines needed to transmit alarm signals from a premises to a central station may  
be out of service or temporarily out of service. For added protection against telephone line  
failure, backup radio transmission systems are recommended.  
System components, though designed to last many years, can fail at any time. As a  
precautionary measure, it is recommended that smoke detectors be checked, maintained,  
and replaced per manufacturer’s recommendations.  
System components will not work without electrical power. If system batteries are not  
serviced or replaced regularly, they may not provide battery backup when AC power fails.  
Environments with high air velocity or that are dusty or dirty require more frequent  
maintenance.  
In general, fire alarm systems and devices will not work without power and will not function  
properly unless they are maintained and tested regularly.  
While installing a fire alarm system may make the owner eligible for a lower insurance rate,  
an alarm system is not a substitute for insurance. Property owners should continue to act  
prudently in protecting the premises and the people in their premises and should properly  
insure life and property and buy sufficient amounts of liability insurance to meet their needs.  
1-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Requirements and recommendations for proper use of fire alarm systems in-  
cluding smoke detectors and other fire alarm devices:  
Early fire detection is best achieved by the installation and maintenance of fire detection  
equipment in all rooms and areas of the house or building in accordance with the requirements  
and recommendations of the current edition of the National Fire Protection Association  
Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations,  
State and local codes and the recommendations contained in Guide for the Proper Use of  
System Smoke Detectors, which is made available at no charge to all installing dealers. For  
specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for  
fire protection systems.  
Requirements and Recommendations include:  
Smoke Detectors shall be installed in sleeping rooms in new construction and it is  
recommended that they shall also be installed in sleeping rooms in existing construction.  
It is recommended that more than one smoke detector shall be installed in a hallway if it is  
more than 30 feet long.  
It is recommended that there shall never be less then two smoke detectors per apartment or  
residence.  
It is recommended that smoke detectors be located in any room where an alarm control is  
located, or in any room where alarm control connections to an AC source or phone lines  
are made. If detectors are not so located, a fire within the room could prevent the control  
from reporting a fire.  
All fire alarm systems require notification devices, including sirens, bells, horns, and/or  
strobes. In residential applications, each automatic alarm initiating device when activated  
shall cause the operation of an alarm notification device that shall be clearly audible in all  
bedrooms over ambient or background noise levels (at least 15dB above noise) with all  
intervening doors closed.  
It is recommended that a smoke detector with an integral sounder (smoke alarm) be  
located in every bedroom and an additional notification device be located on each level of  
a residence.  
To keep your fire alarm system in excellent working order, ongoing maintenance is  
required per the manufacturer’s recommendations and UL and NFPA standards. At a  
minimum the requirements of Chapter 7 of NFPA 72 shall be followed. A maintenance  
agreement should be arranged through the local manufacturer’s representative.  
Maintenance should be performed annually by authorized personnel only.  
The most common cause of an alarm system not functioning when a fire occurs is  
inadequate maintenance. As such, the alarm system should be tested weekly to make sure  
all sensors and transmitters are working properly.  
151209  
1-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
1-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
Agency Listings, Approvals, and Requirements  
2.1 Federal Communications Commission (FCC)  
1. The following information must be provided to the telephone company before the  
IntelliKnight 5820XL can be connected to the phone lines:  
A
B
C
Manufacturer:  
Silent Knight  
IntelliKnight 5820XL  
AC6USA-23901-AL-E  
0.8B  
Model Number:  
FCC registration number:  
Ringer equivalence:  
Type of jack:  
D
E
RJ31X  
Facility Interface Codes:  
Loop Start: 02LS2  
Ground Start: 02GS2  
F
Service Order Code:  
9.0F  
This equipment complies with Part 68 of the FCC rules and the requirements adopted by  
ACTA. On the inside cover of this equipment is a label that contains, among other  
information, a product identifier. If requested, this information must be provided to the  
telephone company.  
A plug and jack used to connect this equipment to the premises wiring and telephone network  
must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA.  
A compliant telephone cord (not provided) and modular jack must be utilized with this  
product. It is designed to be used with a modular jack that is also compliant.  
The REN (ringer equivalence number) provided on this installation sheet is used to determine  
the number of devices that may be connected to the public switched telephone network. This  
number must not exceed 5.0. Since this product has an REN of 1.0, the number of devices is  
limited. The REN number is imbedded in the FCC registration number as 10B.  
If the 5820XL causes harm to the telephone network, the telephone company will notify you  
in advance that the temporarily discontinuance of service may be required. But if advance  
notice is not practical, the telephone company will notify the customer as soon as possible.  
Also, you will be advised of your right to file a complaint with the FCC if you believe it is  
necessary.  
The telephone company may make changes in its facilities, equipment, operations or  
procedures that could affect the operation of the equipment. If this happens the telephone  
company will provide advance notice in order for you to make necessary modifications to  
maintain uninterrupted service.  
If trouble is experienced with the 5820XL, for repair or warranty information, please contact  
Silent Knight at 1-800-328-0103 or www.silentknight.com. If the equipment is causing harm  
to the telephone network, the telephone company may request that you disconnect the  
5820XL until the problem has been resolved.  
151209  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
This product cannot be adjusted or repaired in the field. It must be returned to the factory for  
service.  
This equipment is not designed for use with party line service. Connection to party line  
service is subject to state tariffs. You may contact the state public utility commission, public  
service commission or corporation commission for information.  
Since the 5820XL is a commercial fire alarm panel, it must be connected upstream of all other  
equipment utilizing the phone lines. If you have questions about the installation, contact your  
telephone company or a qualified installer.  
Warning  
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions:  
(1) This device may not cause radio interference, and (2) This device must accept any interference received,  
including interference that may cause undesired operation.  
2.2 Underwriters Laboratories (UL)  
2.2.1 Requirements for All Installations  
General requirements are described in this section. When installing an individual device, refer  
to the specific section of the manual for additional requirements. The following subsections  
list specific requirements for each type of installation (for example, Central Station Fire  
Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 8.7 for  
information on releasing operation.  
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.  
2. Use the addressable smoke detectors specified in Section 5.2 of this manual and or con-  
ventional detectors listed in the compatibility chart. (See Appendix A.)  
3. Use UL listed notification appliances compatible with the 5820XL from those specified in  
the Appendix at the back of this manual.  
4. A full system checkout must be performed any time the panel is programmed.  
2-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Agency Listings, Approvals, and Requirements  
Restricted Options:  
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 -  
30 hours. For UL certified installations this number must be set from 1 to 3 hours.  
The system allows the use of non-latching spot type smoke detectors. This feature may not  
be used in commercial applications whereby a general alarm is sounded. It is intended for  
elevator recall, door holding applications, and hotel/motel room applications.  
The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL  
certified installations the setting must be a minimum of 60 seconds.  
Call forwarding shall not be used.  
When two count is used detector spacing shall be cut in half, you shall not use the alarm  
verification feature, and no delay shall be used.  
P.A.S feature shall be used only with automatic detectors.  
2.2.2 Requirements for Central Station Fire Alarm  
Systems  
1. Use both phone lines. Enable phone line monitors for both lines.  
2. You must program a phone number and a test time so that the 5820XL sends an automatic  
daily test to the central station.  
3. Do not use the ground start option.  
4. The AC Loss Hours option must be set from 1-3 hours.  
5. The Attempts to Report option must be set for 5.  
2.2.3 Requirements for Local Protected Fire Alarm  
Systems  
At least one UL listed supervised notification appliance must be used.  
2.2.4 Requirements for Remote Station Protected Fire  
Alarm Systems - Digital Alarm Communicator  
Transmitter (DACT)  
1. Do not exceed the current load restrictions shown in Section 3.6.  
2. The AC Loss Hours option must be set from 15-30 hours.  
151209  
2-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
2-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
Before You Begin Installing  
This section of the manual is intended to help you plan your tasks to facilitate a smooth  
installation. Please read this section thoroughly, especially if you are installing a 5820XL  
panel for the first time.  
3.1 What’s in the Box?  
The IntelliKnight 5820XL ships with the following hardware:  
A cabinet with all hardware assembled  
Two keys for the front door  
Two keys for user operation of the on-board annunciator (installer operations require the  
Installer’s Code)  
Ten 4.7K ohm end-of-line resistors  
A battery cable for batteries wired in series  
3.2 Environmental Specifications  
It is important to protect the 5820XL control panel from water. To prevent water damage, the  
following conditions should be AVOIDED when installing the units:  
Intended for indoor use in dry locations only  
Do not mount directly on exterior walls, especially masonry walls (condensation)  
Do not mount directly on exterior walls below grade (condensation)  
Protect from plumbing leaks  
Protect from splash caused by sprinkler system inspection ports  
Do not mount in areas with humidity-generating equipment (such as dryers, production  
machinery)  
When selecting a location to mount the 5820XL control panel, the unit should be mounted  
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or  
humidity not exceeding 93% noncondensing.  
151209  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
3.3 Electrical Specifications  
Rating  
EarthGround  
Faults  
Terminal # and Label  
Description  
AC input (hot)  
Voltage  
120 VAC, 60 Hz 2.5 A  
N/A N/A  
120 VAC 60 Hz 2.5 A  
Current  
1
2
3
L
N/A  
N/A  
N/A  
Earth ground  
N
AC input (neutral)  
3.0 Amp Notification and  
Aux power Circuits  
4
5
6
7
8
9
X
*I/O 6  
Flexput™ Circuits  
Flexput™ Circuits  
Flexput™ Circuits  
Flexput™ Circuits  
Flexput™ Circuits  
Flexput™ Circuits  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
0Ω  
0Ω  
0Ω  
0Ω  
0Ω  
0Ω  
O
100 mA for initiation circuits  
3.0 Amp Notification and  
Aux power Circuits  
X
*I/O 5  
O
100 mA for initiation circuits  
3.0 Amp Notification and  
Aux power Circuits  
X
*I/O 4  
O
100 mA for initiation circuits  
3.0 Amp Notification and  
Aux power Circuits  
10  
11  
12  
13  
14  
X
O
X
O
X
*I/O 3  
*I/O 2  
*I/O 1  
100 mA for initiation circuits  
3.0 Amp Notification and  
Aux power Circuits  
100 mA for initiation circuits  
3.0 Amp Notification and  
Aux power Circuits  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
O
100 mA for initiation circuits  
B
SBUS communication  
SBUS power  
5 VDC  
100 mA  
A
SBUS OUT  
SBUS IN  
0Ω  
0Ω  
+
24 VDC  
1.0 A  
-
B
A
Used for Class A installations  
+
-
N.C.  
C
RELAY 2  
RELAY 1  
General Purpose Relay 2  
General Purpose Relay 1  
24 VDC  
24 VDC  
2.5 A, resistive  
2.5 A, resistive  
N/A  
N/A  
N/A  
N.O.  
N.C.  
C
N.O.  
N.C.  
C
TROUBLE Trouble Relay  
24 VDC  
32 VDC  
2.5 A, resistive  
150 mA  
N.O.  
SC-  
SC+  
SC-  
SC+  
L1  
SLC terminals  
SLC OUT  
0Ω  
0Ω  
L2  
Used for Class A installations  
SLC IN  
*
Regulated/Special application when used for releasing.  
3-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Before You Begin Installing  
Rating  
EarthGround  
Faults  
Terminal # and Label  
Description  
Voltage  
Current  
37  
Ring  
Tip  
Phone Line 1 Telco Ring  
Phone Line 1 Telco Tip  
38  
39  
40  
41  
42  
43  
44  
45  
46  
N/A  
N/A  
0Ω  
Ring  
Tip  
Phone Line 1 Premises Ring  
Phone Line 1 Premises Tip  
Phone Line 2 Telco Ring  
Phone Line 2 Telco Tip  
Ring  
Tip  
0Ω  
0Ω  
Ring  
Tip  
Phone Line 2 Premises Ring  
Phone Line 2 Premises Tip  
SC-  
SC+  
SLC Programming Terminal ( - ) 32 VDC  
SLC Programming Terminal ( + ) 32 VDC  
150 mA  
150 mA  
3.4 Wiring Specifications  
Induced noise (transfer of electrical energy from one wire to another) can interfere with  
telephone communication or cause false alarms. To avoid induced noise, follow these  
guidelines:  
Isolate input wiring from high current output and power wiring. Do not pull one multi-  
conductor cable for the entire panel. Instead, separate the wiring as follows:  
High voltage  
SLC loops  
AC power, Terminals 1-3  
Terminals 33-36  
Audio input/output  
Phone line circuits, Terminals  
37-44  
Notification circuits  
SBUS  
Terminals 4-15  
Terminals 16-23  
Terminals 24-32  
Relay circuits  
Do not pull wires from different groups through the same conduit. If you must run them  
together, do so for as short a distance as possible or use shielded cable. Connect the shield  
to earth ground at the panel. You must route high and low voltages separately.  
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit  
board where it could induce noise into the sensitive microelectronics or pick up unwanted  
RF noise from the high speed circuits. See Figure 3-1 for an example.  
High frequency noise, such as that produced by the inductive reactance of a speaker or  
bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it  
around a ferrite toroid.  
151209  
3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
Figure 3-1 Wire Routing Example  
3-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Before You Begin Installing  
3.5 Board Assembly Diagram  
On-board Annunciator  
To AC  
Chassis  
Mounting  
Nuts  
Chassis  
Mounting  
Nuts  
Key Switch  
Input  
Ground Start  
Relay Socket  
Programming  
Ports  
Figure 3-2 Model 5820XL Assembly  
Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL  
assembly to the cabinet. If you should need to remove the board assembly for repair, remove  
the four mounting nuts which hold the assembly in the cabinet. Then lift the entire assembly  
out of the cabinet. Do not attempt to remove the circuit boards from the metal bracket.  
151209  
3-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
3.6 Calculating Current Draw and Standby Battery  
This section is for helping you determine the current draw and standby battery needs for your  
installation.  
3.6.1 Current Draw Worksheet Requirements  
The following steps must be taken when determining 5820XL current draw and standby  
battery requirements.  
1. You will use the Current Draw Worksheet to determine current draw and standby battery  
Hochiki SLC Devices. For the 5820XL, the worst case current draw is listed for the panel,  
addressable devices, and all SBUS expanders. Fill in the number of addressable devices  
and expanders that will be used in the system and compute the current draw requirements  
for alarm and standby. Record this information in the Current Draw Worksheet on Line A.  
2. Add up the current draw for all auxiliary devices and record in the table at Line B.  
3. Add up all notification appliance loads and record in the table at Line C.  
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the  
device manual for the current ratings.  
5. Make sure that the total alarm current you calculated, including current for the panel itself,  
does not exceed 6.0 A. This is the maximum alarm current for the 5820XL control panel.  
If the current is above 6.0 A you will need to use a notification power expander(s) such as  
the Silent Knight 5495 or the 5895XL intelligent power expander, to distribute the power  
loads so that the 5820XL or the power expanders do not exceed their power rating. Refer  
to the current draw worksheets provided with the 5495 or the 5895XL manuals so you do  
not exceed their power requirements.  
6. Complete the remaining instructions in the appropriate Current Draw Worksheet for deter-  
mining battery size requirements.  
3-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Before You Begin Installing  
3.6.2 Current Draw Worksheet for SK SLC Devices  
Use Table 3-1 to determine current requirements during alarm/battery standby operation when  
SK SLC devices are installed. You can install up 99 SK detectors per loop (396 max per  
panel) and 99 SK modules per loop (396 max per panel). Copy this section if additional space  
is required.  
Table 3-1: Current Draw Worksheet for SK SLC Devices  
Standby  
Current  
Alarm  
Current  
Device  
# of Devices  
Current per Device  
For each device use this formula: This column  
X
This column  
=
Current per number of devices.  
Standby:  
215 mA  
385 mA  
215 mA  
Fire Panel (Current draw from  
battery)  
1
Alarm:  
385 mA  
Addressable SLC Detectors  
SK-Photo  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
SK-Photo-T  
SK-Ion  
Standby/Alarm:  
0.27 mA  
SK-Heat  
SK-Heat-HT  
Standby/  
SLC  
Aux. Pwr  
SLC  
Alarm:  
Standby:  
Alarm:  
2 mA  
2 mA  
SK-Beam (without integral test)  
(99 max/loop  
mA  
& 396 max/  
panel)  
8.5 mA  
mA  
1
Standby/  
Alarm:  
2 mA  
2 mA  
5
SK-Beam-T (with integral test)  
Standby:  
Alarm:  
mA  
mA  
Aux. Pwr  
SLC  
8.5 mA  
mA  
mA  
Standby/  
Alarm:  
6
SK-Duct  
0.27 mA  
0.3 mA  
SK-Acclimate  
SK-Heat-ROR  
mA  
mA  
mA  
mA  
Standby/Alarm:  
151209  
3-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
Standby  
Current  
Alarm  
Current  
Device  
# of Devices  
Current per Device  
Addressable SLC Modules  
Standby/ 0.375mA  
mA  
SLC  
Alarm  
0.375mA  
1.7mA  
7mA  
mA  
SK-Control  
Standby/  
Alarm:  
mA  
Aux Pwr  
mA  
mA  
mA  
mA  
SK-Monitor  
SK-Minimon  
SK-Pull-SA  
SK-Pull-DA  
SK-Monitor-2  
SK-Mon10  
mA  
mA  
mA  
Standby/Alarm:  
0.375 mA  
Standby/Alarm:  
Standby/Alarm:  
Standby/Alarm:  
0.75 mA  
3.5 mA  
1.45 mA  
2.25 mA  
2.25 mA  
1.7 mA  
20 mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
SK-Relay-6  
(99 max/loop  
& 396 max/  
Standby/  
SLC  
1
panel)  
Alarm:  
Standby/  
Alarm:  
SK-Control-6  
SK-Relay  
mA  
Aux Pwr  
mA  
mA  
Standby/Alarm:  
0.255 mA  
12 mA  
mA  
mA  
Standby  
Aux Pwr  
SLC  
Alarm  
90 mA  
mA  
mA  
SK-Zone  
Standby/  
Alarm  
mA  
mA  
0.27mA  
50 mA  
Standby  
Alarm  
Aux Pwr  
SLC  
SK-Zone-6  
270 mA  
mA  
mA  
Standby/Alarm 2 mA  
mA  
mA  
SLC Accessories  
B501BHT-2 Sounder Base  
Standby:  
Alarm:  
Alarm:  
1 mA  
15 mA  
0.7 mA  
0.5 mA  
7.5 mA  
10 mA  
Aux Pwr  
SLC  
(99 max/loop  
& 396 max/  
panel)  
mA  
mA  
mA  
mA  
mA  
B224RB Relay Base  
RTS151/151 KEY  
RA100Z  
Standby/Alarm:  
Alarm:  
mA  
Alarm:  
SLC Isolator Devices  
SK-Iso (Isolator Module)  
(100 max/loop Standby/Alarm:  
&400 max/  
Standby/Alarm:  
panel)  
0.45 mA  
0.5 mA  
mA  
mA  
mA  
mA  
B224BI Isolator Base  
Accessories Modules  
5815XL SLC Expander  
(3 max.)  
(8 max)  
Standby/Alarm:  
Standby:  
55 mA  
20 mA  
25 mA  
45 mA  
mA  
mA  
mA  
5860 Remote Fire Alarm  
Annunciator  
Alarm:  
mA  
mA  
5824 Serial/Parallel Printer  
Interface Module  
Standby/Alarm:  
mA  
mA  
(2 max.)  
(8 max.)  
5496 Intelligent Power Module  
Standby/Alarm:  
Standby/Alarm:  
10 mA  
10 mA  
5895XL IntelliKnight Power  
Module  
mA  
3-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Before You Begin Installing  
Standby  
Current  
Alarm  
Current  
Device  
# of Devices  
Current per Device  
Standby:  
35 mA  
145 mA  
35 mA  
145 mA  
35 mA  
200 mA  
0 mA  
mA  
5865-4 LED Annunciator  
(with reset and silence switches)  
Alarm:  
mA  
Standby:  
Alarm:  
mA  
mA  
mA  
5865-3 LED Annunciator  
5880 I/O Module  
(8 max.)  
mA  
mA  
mA  
Standby:  
Alarm:  
Standby:  
Alarm:  
5883 Relay Interface  
(32 max.)  
220mA  
(22 mA per relay)  
A
B
Total System Current  
3
Refer to devices manual for current rating.  
Auxiliary Devices  
Alarm/Standby:  
Alarm/Standby:  
Alarm/Standby:  
Alarm/Standby:  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
Auxiliary Devices Current  
Notification Appliance Circuits  
Refer to device manual for current rating.  
Alarm:  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
A
Alarm:  
Alarm:  
Alarm:  
C
D
E
F
G
H
I
Notification Appliances Current  
Total current ratings of all devices in system (line A + line B + C)  
Total current ratings converted to amperes (line D x .001):  
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):  
Multiply lines E and F.  
mA  
A
H
Total standby AH  
AH  
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)  
H
Multiply lines E and H.  
Total alarm AH  
AH  
J
Total ampere hours  
required  
AH  
4
Add lines G and I.  
1. Total does not include isolator devices or accessory bases.  
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is  
removed during that time. However, during normal operation, door holders draw current and must be included in the  
6.0A total current that can be drawn from the panel.  
4. Use next size battery with capacity greater than required.  
5. SK-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be  
considered when determining auxiliary power capacity but not calculated into current requirements for day to day  
operation.  
6. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is  
calculated by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.  
151209  
3-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
3.6.3 Current Draw Worksheet for Hochiki SLC Devices  
Use Table 3-2 to determine current requirements during alarm/battery standby operation when  
Hochiki SLC devices are installed. You can install up 127 Hochiki devices per loop (508 max  
per panel). Copy this section if additional space is required.  
Table 3-2: Current Draw Worksheet for Hochiki SLC Devices  
Standby  
Current  
Alarm  
Current  
Device  
# of Devices  
This column  
Current per Device  
For each device use this formula:  
X
This column  
Standby:  
Alarm:  
=
Current per number of devices.  
215 mA  
385 mA  
215 mA  
IntelliKnight 5820XL Fire Panel  
(Current draw from battery)  
1
385 mA  
Addressable SLC Devices  
SD500-AIM  
SD500-MIM  
SD500-PS  
mA  
mA  
mA  
mA  
1
SD500-ARM  
SD505-AHS  
SD505-AIS  
Standby/Alarm:  
0.55 mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
(508 max.)  
SD505-APS  
Standby:  
Alarm:  
8 mA  
60 mA  
Aux. Pwr  
mA  
mA  
1
1
SD500-ANM  
SD500-SDM  
(508 max.)  
(508 max.)  
Standby/  
Alarm:  
Standby/  
Alarm:  
SLC  
SLC  
mA  
.55 mA  
mA  
mA  
mA  
mA  
.55 mA  
20 mA  
106 mA  
10 mA  
220 mA  
10 mA  
Standby:  
Alarm:  
Aux. Pwr  
Standby:  
Aux. Pwr Alarm:  
LED:  
mA  
mA  
mA  
1
SD500-LED  
(100 max.)  
mA  
mA  
Standby/  
Alarm:  
SLC  
mA  
0.55 mA  
SLC Accessory Bases  
SD505-6RB  
(508 max.)  
(508 max.)  
Standby/Alram:  
.082 mA  
1 mA  
32 mA  
mA  
mA  
mA  
Standby:  
Aux. Pwr  
Alarm:  
mA  
mA  
SD505-6SB  
Standby/  
Alarm:  
SLC  
mA  
mA  
.082 mA  
2
Standby:  
Aux. Pwr  
35 mA  
SD505-ADHR  
SD505-DUCTR  
2
mA  
mA  
Alarm:  
75 mA  
(508 max.)  
Standby/  
Alarm:  
SLC  
mA  
.082 mA  
SD505-DTS  
SD505-DTS-K  
SD505-ADH  
None, included with SD505-ADHR worst case.  
(508 max.)  
(508 max.)  
None, included with detector current.  
SD505-DUCT  
SLC Isolator Devices  
SD500-LIM  
SD505-6IB  
(1024 max.)  
(508 max.)  
Standby/Alarm  
0.092 mA  
mA  
mA  
Accessories Modules  
5815XL SLC Expander  
(3 max.)  
(8 max.)  
Standby/Alarm:  
Standby:  
Alarm:  
55 mA  
20 mA  
25 mA  
mA  
mA  
mA  
mA  
5860 Remote Fire Alarm Annun.  
3-10  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Before You Begin Installing  
Standby  
Current  
Alarm  
Current  
Device  
# of Devices  
Current per Device  
Standby/Alarm:  
Standby/Alarm:  
Standby/Alarm:  
Standby:  
Alarm:  
Standby:  
Alarm:  
Standby:  
Alarm:  
5824 Serial/Parallel Printer Interface  
5895XL IntelliKnight Power Expander  
5496 Intelligent Power Module  
5865-4 LED Annunciator  
(2 max.)  
(8 max.)  
45 mA  
10 mA  
10 mA  
35 mA  
145 mA  
35 mA  
145 mA  
35 mA  
200 mA  
0 mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
(with reset and silence switches)  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
5865-3 LED Annunciator  
5880 LED I/O Module  
(8 max.)  
Standby:  
Alarm:  
5883 Relay Interface  
(32 max.)  
220mA  
(22 mA per relay)  
A
B
Total System Current  
3
Refer to devices manual for current rating.  
Auxiliary Devices  
Alarm/Standby:  
Alarm/Standby:  
Alarm/Standby:  
Alarm/Standby:  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
Auxiliary Devices Current  
Alarm:  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
mA  
A
Alarm:  
Alarm:  
Alarm:  
C
D
E
F
G
H
I
Notification Appliances Current  
Total current ratings of all devices in system (line A + line B + C)  
Total current ratings converted to amperes (line D x .001):  
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):  
Multiply lines E and F.  
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)  
Multiply lines E and H.  
mA  
A
H
Total standby AH  
Total alarm AH  
AH  
H
AH  
J
Total ampere hours  
required  
AH  
4
Add lines G and I.  
1. Total does not include isolator devices or accessory bases.  
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or  
240 VAC.  
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is  
removed during that time. However, during normal operation, door holders draw current and must be included in the  
6.0A total current that can be drawn from the panel.  
4. Use next size battery with capacity greater than required.  
151209  
3-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
3.6.4 Maximum Battery Standby Load  
Table 3-3 shows the maximum battery standby load for the 5820XL based on 24 and 60 hours  
of standby. The standby load calculations of line D in the Current Draw Calculation  
number shown in Table 3-3 for the battery size used and standby hours required  
* 33AH max battery size for FM (Factory Mutual) installations..  
Table 3-3: Maximum Battery Standby Load  
Max. Load for 24 hrs.  
Standby, 5 mins. Alarm  
*Max. Load for 60 hrs.  
Standby, 5 mins. Alarm  
Rechargeable Battery Size  
7 AH  
12 AH  
18 AH  
35 AH  
270 mA  
475 mA  
685 mA  
1.3 A  
105 mA  
190 mA  
270 mA  
540 mA  
*
Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote  
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter  
(DACT).  
Warning!  
Silent Knight does not support the use of batteries smaller than those listed in Table 3-3. If you use a battery  
too small for the installation, the system could overload the battery resulting in the installation having less than  
the required 24 hours standby power. Use Table 3-3 to calculate the correct battery amperes/hour rating needed  
for your installation.  
3.7 Installation Tasks Overview  
This section provides a chart listing tasks that need to be performed when installing the  
IntelliKnight 5820XL system. The chart is intended to be a handy way for you to make sure  
you have completed all necessary tasks. Unless noted, these tasks do not have to be performed  
in the order they are listed here.  
Important: Connect and address SLC devices before running JumpStart.  
See Sec.  
(for more info.)  
Task  
Main Panel Hardware Installation  
U
U
U
U
Mount the control panel cabinet.  
Connect AC.  
Connect phone lines.  
Install 5815XL SLC expander modules (if needed). Required if more than  
127 SLC devices are used.  
U
U
U
U
U
U
U
Install 5860 Remote Fire Alarm Annunciator modules if used.  
Install 5865 or LED Annunciator modules if used.  
Install 5880 LED I/O module if customized LED annunciation will be used.  
Install notification appliances.  
Install auxiliary power devices (if used).  
If using a printer, install the 5824 Serial/Parallel Printer Interface Module.  
Connect batteries (typically last step).  
3-12  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Before You Begin Installing  
See Sec.  
(for more info.)  
Task  
SLC Device Hardware Installation  
Perform these steps before running JumpStart.  
U
U
U
Connect device bases to the loop.  
Set device addresses.  
Physically connect detectors to their bases. Connect relay and contact  
monitor modules.  
5.4 & see device  
install instructions  
JumpStart  
JumpStart is for initial system programming. JumpStart automatically selects  
some options for SLC devices. See “Input Point Configuration” section of this  
chart for other options.  
JumpStart makes selections for the following options. You can customize  
options, if necessary.  
Device type (detector or switch) configured by JumpStart.  
Program type of detector (heat, photoelectric, or ionization) selected by  
JumpStart.  
System Software Configuration  
U
U
U
U
U
U
U
U
Select low AC hours report time (6 hours by default).  
Select Auto Test Time (2:00 AM by default).  
Enable/disable automatic DST adjustment feature (enabled by default).  
Change clock display format (12-hour with AM/PM by default).  
Set up reporting accounts.  
Select options for phone lines.  
Select system-wide response to trouble conditions, if desired.  
Select system-wide cadence patterns for special conditions (fire drill, Aux1  
and Aux2 alarms) if desired.  
U
Customize banner message (message that displays on LCD in normal  
mode) if desired.  
Input Point (SLC Device) Configuration  
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart).  
You can change options selected by JumpStart, if necessary and further customize input point options.  
U
U
U
Select device type (SK or Hochiki). Only one device type can be used per  
control panel.  
Program type of switch (manual pull, fire drill, and so on), if necessary.  
(JumpStart assigns all switches as Manual Pull type.)  
If the installation includes duct detectors, program detector type.  
(JumpStart does not distinguish duct detectors from ordinary smoke  
detectors.)  
U
U
Assign a name (or description) to the point.  
Assign input points to zones, if necessary. (JumpStart assigns all input  
points to Zone 1.)  
Zone Configuration  
U
Add the zone to the system if it does not already exist. (Zone 1 created by  
JumpStart.)  
U
Program a name (or description) for the zone.  
151209  
3-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
See Sec.  
(for more info.)  
Task  
U
U
Select alarm delay options (detection characteristics) for zone.  
Select heat detector trip temperature. (JumpStart selects 150°F for heat  
detectors.)  
Output Point Configuration  
Conventional notification circuits (circuits 1-6):  
U
Enable circuits used for notification appliances through programming, if  
necessary. (JumpStart enables circuits 1-6 as Notification.)  
Conventional relay circuits (circuits 7-8):  
U
Select options for relay circuits, if desired. Note: Relay circuits will always  
output continuously (constant pattern), even if assigned to an Output Group  
that uses a different output pattern.  
Auxiliary power circuits (circuits 1-6):  
U
U
Enable any circuit used for auxiliary power devices through programming.  
Select type of power (door holder, constant, or resettable)  
Addressable relay modules  
U
Assign addressable relay modules to output groups through programming.  
(JumpStart assigns all relay modules to Group 1.)  
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)  
Assign LED modules to output groups through programming.  
All output circuits (1-8):  
U
U
Disable (set to UNUSED) any unused circuits. If you do not disable unused  
output circuits, they will cause a trouble condition (unless an EOL resistor  
is used).  
U
Select a name for the point, if desired.  
Output Group Configuration  
U
U
U
Add the group to the system if it does not already exist.  
Assign output points to the group.  
Program a name (or description) for the group, if desired.  
Select “group properties” (see below).  
U
U
U
U
U
Latching / non-latching  
Silencing option  
Select options for activation with system switches.  
Map zones to output groups that will activate when zone goes into alarm.  
Select a cadence pattern for outputs in the zone.  
3-14  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4  
Control Panel Installation  
Caution!  
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while  
installing or servicing.  
4.1 Mounting the Control Panel Cabinet  
Read the environmental specifications in Section 3.2 before mounting the control panel  
cabinet. This will ensure that you select a suitable location.  
The panel should be accessible to main drop wiring runs. It should be mounted as close to the  
center of the building as possible and located within a secured area, but should be accessible  
for testing and service.  
Mount the control panel cabinet so it is firmly secured to the wall surface. When mounting on  
concrete, especially when moisture is expected, attach a piece of 3/4-inch plywood to the  
concrete surface and then attach the cabinet to the plywood. Also mount any other modules to  
the plywood.  
The cabinet can be surface- or flush-mounted. If you will be flush-mounting the cabinet, the  
hole for the enclosure should be 14.75" W x 25" H x 4" D. Do NOT flush-mount in a wall  
designated as a fire break.  
4.1.1 Preventing Water Damage  
Water damage to the fire system can be caused by moisture entering the cabinet through the  
conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause  
water problems. Installers should take reasonable precautions to prevent water from entering  
the cabinet. Water damage is not covered under warranty.  
4.1.2 Removing the 5820XL Assembly from the Housing  
If it should ever be necessary to remove the control panel assembly from the cabinet for  
repair, do so by unscrewing the nuts that connect the control panel assembly to the cabinet. Do  
not attempt to disassemble the circuit boards. See Section 3.5 for location of the nuts.  
151209  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
IntelliKnight 5820XL Installation Manual  
4.2 AC Connection  
At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may  
be necessary for a professional electrician to make this connection.  
The AC terminals are rated at 120 VAC, 50 or 60 Hz, 2.5A.  
Figure 4-1 120 VAC Power Connection  
4-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Control Panel Installation  
4.3 Battery Connection  
The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH  
rating. Determine the correct AH rating as per your current load calculation (see Section 3.6).  
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase  
the AH rating. It is recommended that you replace batteries every five years.  
To Control Panel  
Red  
Black  
Battery Jumper  
(P/N 140694)  
Shipped With Panel  
UL Listed 12V Battery  
UL Listed 12V Battery  
Figure 4-2 Battery Connection  
151209  
4-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
4.3.1 RBB Accessory Cabinet  
The Model RBB Accessory cabinet can be used when your backup batteries requirements use  
backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet  
holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64  
cm W x 25.4 cm H x 15.24 cm D).  
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries  
To properly install the accessory cabinet and backup batteries, follow these steps:  
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch ply-  
wood. This is necessary because the weight of the batteries inside the accessory cabi-  
net could cause the cabinet to pull away from the drywall.  
When mounting on concrete, especially when moisture is expected, attach a piece of  
3/4-inch plywood to the concrete surface and then attach the RBB cabinet to the ply-  
wood.  
If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no  
more than 18" away from the main control panel cabinet. This will ensure that the bat-  
tery cables reach the battery terminals.  
Cabinet  
Mounting Holes  
Figure 4-3 RBB Cabinet Mounting Holes  
2. Connect the main control panel battery cables to the battery cable extenders as shown in  
Figure 4-4 Splicing Control panel Battery Cable to RBB Battery Cable Extenders  
4-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Control Panel Installation  
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet.  
RBB Cabinet  
Cover Screws  
Conduit  
Coupler  
Conduit  
-
+
+
-
RBB Cabinet  
Cover Screws  
Figure 4-5 Battery Connections in the RBB Cabinet  
Note: Figure 4-5 is an example of how the wire connections can be routed. However, any other cabinet knock-  
outs (on either the main control panel or the RBB cabinet), that are not previously being used may be uti-  
lized to connect conduit between the two cabinets.  
4. Connect battery leads to the backup battery terminals. See Figure 4-5.  
Observe the proper polarity to prevent damage to the batteries or the control panel.  
5. Insert the RBB cover screws into the cover mounting holes (see Figure 4-5).  
Screw the cover screw 3/4 of the way into the cover mounting hole.  
6. Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4-6.  
Cover Plate  
Mounting Keyholes  
Figure 4-6 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment  
7. Slide the cover into place and tighten the cover mounting screws. See Figure 4-6  
151209  
4-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
4.4 SBUS Wiring  
This section contains information on calculating SBUS wire distances and the types of wiring  
configurations (Class A and B).  
4.4.1 Calculating Wiring distance for SBUS modules  
The following instructions will guide you in determining the type of wire and the maximum  
wiring distance that can be used with control panel SBUS accessory modules.  
To calculate the wire gauge that must be used to connect SBUS modules to the control panel,  
it is necessary to calculate the total worst case current draw for all modules on a single 4-  
conductor bus. The total worst case current draw is calculated by adding the individual worst  
case currents for each module. The individual worst case values are shown in the table below.  
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of accessory mod-  
ules are required, and the worst case current draw will exceed the 1 amp limit, then the current draw must  
be distributed using 5895XL Power Expanders. Each 5895XL Power Expander provides an additional  
SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are done separately for  
each 5895XL, and separately for the control panel itself.  
Model Number  
5860 Fire Annunciator  
Worst Case Current Draw  
.100 amps  
5824 Serial/Parallel Printer Interface Module .040 amps  
5880 LED I/O Module  
.250 amps  
.200 amps  
.010 amps  
.010 amps  
5865 LED Fire Annunciator  
5895XL Intelligent Power Supply  
5496 Intelligent Power Supply  
Note: Refer to Table 3-2 for maximum number of each type of device that can be used per system.  
After calculating the total worst case current draw, Table 4-1 specifies the maximum distance  
the modules can be located from the panel on a single wire run. The table insures 6.0 volts of  
line drop maximum. In general, the wire length is limited by resistance, but for heavier wire  
gauges, capacitance is the limiting factor.  
4-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
These cases are marked in the chart with an asterisk (*). Maximum length can never be more  
than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in  
the note below).  
Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire  
Wiring Distance: SBUS Modules to Panel  
Total Worst Case  
Current Draw (amps)  
22 Gauge  
18 Gauge  
16 Gauge  
14 Gauge  
0.100  
0.200  
1852 ft.  
926 ft.  
617 ft.  
463 ft.  
370 ft.  
309 ft.  
265 ft.  
231 ft.  
206 ft.  
185 ft.  
4688 ft.  
2344 ft.  
1563 ft.  
1172 ft.  
938 ft.  
781 ft.  
670 ft.  
586 ft.  
521 ft.  
469 ft.  
* 6000 ft.  
3731 ft.  
2488 ft.  
1866 ft.  
1493 ft.  
1244 ft.  
1066 ft.  
933 ft.  
* 6000 ft.  
5906 ft.  
3937 ft.  
2953 ft.  
2362 ft.  
1969 ft.  
1687 ft.  
1476 ft.  
1312 ft.  
1181 ft.  
0.300  
0.400  
0.500  
0.600  
0.700  
0.800  
0.900  
829 ft.  
1.000 (Max)  
746 ft.  
Note: The following formulas were used to generate the wire distance chart:  
6.0 Volts  
Maximum Resistance (Ohms) =  
Total Worst Case Current Draw (amps)  
Maximum Resistance (Ohms)  
Rpu  
Maximum Wire Length (Feet) =  
(6000 feet maximum)  
* 500  
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)  
Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire  
Wire Gauge  
Ohms per 1000 feet (Rpu)  
22  
18  
16  
14  
16.2  
6.4  
4.02  
2.54  
151209  
4-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
Wiring Distance calculation example:  
Suppose a system is configured with the following SBUS modules:  
2 - Module 5860 Fire Annunciator  
1 - 5895XL Intelligent Power Expander  
1 - 5865 LED Fire Annunciator  
1 - 5824 Serial/Parallel Interface Module  
The total worst case current is calculated as follows:  
5860 Current Draw  
= 2 x .100 amps  
= 1 x .010 amps  
= 1 x .200 amps  
= 1 x .040 amps  
= .200 amps  
= .010 amps  
= .200 amps  
= .040 amps  
= .450 amps  
5895XL Current Draw  
5865 Current Draw  
5824 Current Draw  
Total Worst Case Current Draw  
Using this value, and referring to the Wiring Distance table, it can be found that the available  
options are:  
370 feet maximum using 22 Gauge wire  
938 feet maximum using 18 Gauge wire  
1493 feet maximum using 16 Gauge wire  
2362 feet maximum using 14 Gauge wire  
4-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Control Panel Installation  
4.4.2 Wiring Configurations  
configuration.  
Supervised  
Power Limited  
Caution  
For proper system supervision do not use looped wire  
under terminals marked A, B, +, and - of the SBUS  
device connectors. Break wire runs to provide  
supervision of connections.  
Figure 4-7 SBUS Class A Wiring  
Supervised  
Power Limited  
Figure 4-8 SBUS Class B Wiring  
151209  
4-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
4.5 Remote Annunciator 5860 Installation  
The optional Model 5860 Remote Annunciator, shown in Figure 4-9, performs the same  
functions as the on-board annunciator. Operation is identical. Up to 8 annunciators can be  
added to the IntelliKnight 5820XL system.  
Figure 4-9 Model 5860 Remote Annunciator, Front View  
5860 installation involves the following steps:  
1. Make sure power is off at the panel.  
2. Mount the 5860 in the desired location (see Section 4.5.1).  
5. The new 5860 module must be added to the system through programming. JumpStart will  
add the module automatically (see Section 6.1). You can also add it manually (see Section  
4-10  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Control Panel Installation  
4.5.1 Mounting the 5860  
This section of the manual describes mounting the remote annunciator. The annunciator can  
be flush- or surface-mounted.  
Figure 4-10 shows the parts of the annunciator. Instructions for disassembling and mounting  
appear on the following pages.  
Figure 4-10 Annunciator Parts  
151209  
4-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To  
disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the  
bottom of the annunciator bezel. (See Figure 4-11 for location of the set screws.)  
Figure 4-11 Annunciator Back Box and Bezel Details  
4.5.1.1 Flush Mounting  
This section of the manual describes flush mounting. You can flush-mount with or without an  
electrical box.  
4-12  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
Flush Mounting with an Electrical Box  
The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-  
gang, and double-gang.  
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to  
accommodate the annunciator. Studs used with an electrical box must be two by fours (or  
larger).  
Figure 4-12 Placement of Electrical Box for Flush Mounting  
Flush Mounting Steps  
1. Cut a hole in the sheet rock to the following dimensions: 8-1/4” w x 6-5/8” h. If an electri-  
cal box is used, the box must be 1-3/8” back from face of wall to accommodate the annun-  
2. Remove knockout holes as needed for wires.  
3. Fit the annunciator back box into the hole and stabilize with mounting wires. Angle the  
mounting wires into the first hole past the sheet rock. Secure the wires behind the screws  
as shown in Figure 4-13. When all four wires are in place, the back box should fit snugly  
into the hole in the sheet rock.  
151209  
4-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
replace the electronic assembly in the back box. Place the bezel over the back box and  
tighten the set screws on the bezel.  
Figure 4-13 Flush Mounting the Back Box  
4.5.1.2 Surface Mounting  
The 5860 can be mounted directly to a surface or can be attached to a single, double, or four-  
square electrical box. The Model 5860TG/TR trim ring kit is available for use when surface  
mounting.  
1. Drill holes in the surface to match the screw holes on the back box.  
2. Fit the trim ring over the back box.  
3. Attach the back box to the surface using screws provided.  
replace the electronic assembly in the back box. Place the bezel over the back box and  
tighten the set screws on the bezel.  
4-14  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.5.2 Model 5860 Connection to the Panel  
Supervised  
Power Limited  
Figure 4-14 Model 5860 Connection to the Panel  
151209  
4-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
4.6 5815XL Installation  
The 5815XL SLC expander lets you add 127 addressable devices. Up to three 5815XLs  
(adding 381 SLC devices for a total of 508 points) can be used with the system.  
To install the 5815XL:  
1. Make sure power is off at the panel.  
2. Mount the 5815XL in the 5820XL, the 5895XL cabinet, or the 5815RMK remote mount-  
ing kit. Use the standoffs located under the control panel board assembly and secure with  
screws provided with the 5815XL. See also Model 5895XL Installation Instructions (P/N  
151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).  
4. Use on-board dipswitches to select an ID#. (See Section 4.10.1.)  
5. The new 5815XL module must be added to the system through programming. JumpStart  
will add the module automatically (see Section 6.1). You can also add it manually (see  
6. You are now ready to connect SLC devices to the 5815XL (see Section 5.4).  
Figure 4-15 is a drawing of the 5815XL board, showing the location of terminals and  
dipswitches.  
Figure 4-15 5815XL Board  
4-16  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Control Panel Installation  
4.6.1 5815XL Connection to the Panel  
Connect the 5815XL to the control panel as shown in Figure 4-16. After the 5815XL is  
connected to the panel, it must be added to the system. This programming step is described in  
Supervised  
Power Limited  
Figure 4-16 5815XL Connection to Main Panel Assembly  
151209  
4-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
4.7 5824 Serial/Parallel Interface Module  
Installation  
The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you  
can print a real-time log of system events, a report of detector status, and event history.  
Instructions for installing the 5824 appear below. The 5824 is for ancillary use only.  
5824 installation involves the following steps:  
1. Make sure power is off at the panel.  
Note: Two 5824s per panel maximum.  
3. Use the dipswitches on the back of the 5824 board to assign an ID# to the 5824 (see Sec-  
4. Configure the 5824 device through programming. See Section 4.7.1.  
Supervised  
Power Limited  
Figure 4-17 5824 Connection to the Panel  
4-18  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Control Panel Installation  
Model 5824 (with housing)  
To Parallel Printer  
To Serial Printer  
Figure 4-18 Printer Connection  
4.7.1 Selecting 5824 Options  
Configuring the 5824 includes the following steps:  
Add the module to the system. JumpStart will add the module automatically (see Section  
Select a name, if desired (see Section 7.3.1.1).  
Select options for the printer and the output port. See below.  
151209  
4-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
Printer and Output Port Options  
7
1. From the Installer Main Menu, select for Program Menu.  
1
2. Select for Module.  
1
3. Select for Edit Module.  
4. From the list that displays, select the 5824 module you want to configure.  
ENTER ENTER  
5. Press  
to bypass the next two screens. A screen similar to the one shown in  
Figure 4-19 Selecting Printer and Output Port Options  
6. Select options for the printer as needed for your installation. Most printers are parallel.  
7. If you are using a serial printer, use the next screen to select serial port options as required  
for your printer. Refer to your printer manual if you need more information.  
Option  
Choices  
Baud Rate:  
Data Bits:  
Stop Bits:  
Parity:  
75 - 19200  
5 - 8  
.5, 1, 2  
None, Even, Odd  
4-20  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.8 5880 LED I/O Module  
The 5880 is an LED driver board that can be used in a wide variety of applications, including  
as an interface with most customized floor plan annunciator boards. The 5880 can drive up to  
40 LEDs and has one PZT controller. The 5880 also has eight inputs for  
monitoring. The following sub-sections describe hardware installation. Refer to Section 6 for  
programming information.  
4.8.1 5880 Board Layout  
Figure 4-20 is a picture of the 5880 board showing locations of screw terminals for connection  
to the panel and contact monitor wiring; pin connectors for connecting LEDs; and the  
dipswitch for selecting an SBUS ID number.  
Dry Contact Inputs  
SBUS Address  
DIPs  
SBUS Connection  
Figure 4-20 5880 Board Layout  
151209  
4-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
4.8.2 FACP Connection  
The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-21.  
After the 5880 is connected to the panel, it must be added to the system. This programming  
Supervised  
Power Limited  
Figure 4-21 5880 Connection to Main Control Panel Assembly  
4-22  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.8.3 LED Wiring  
There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its  
power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current  
for each LED, no series resistors are required. LED outputs can be mapped to output circuits.  
See Section 6 for programming details.  
On connector P1, Pin 12 is an open collector output for controlling a PZT. If used, the 5880  
PZT will match the PZT pattern of the on-board (or 5860) annunciator.  
Note: The circuit connected to “Open Collector Output” (last pin on P1) must be current limited so that no more  
than 100 mA of current is allowed to flow into the open collector transistor.  
5880 LED Outputs  
1
P1  
2
3
4
5
6
7
8
9
10  
Cathode  
LEDs  
Anode  
LED Power  
Programmable Open Collector Output  
Not mappable.  
Matches PZT pattern  
on on-board  
11  
P2  
12  
13  
14  
15  
16  
17  
18  
19  
20  
annunciator  
Cathode  
LEDs  
Anode  
LED Power  
no connection  
Connectors P3 and P4 wired same as P2.  
Figure 4-22 5880 Board Layout  
151209  
4-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
4.8.4 Dry Contact Wiring  
The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch  
supported by the control panel can be used with the 5880. For example, you can use a 5880 to  
monitor pull stations, water flow, tamper, reset, or silence switches.  
Wire dry contacts as shown in Figure 4-23. Notice grouping of terminals; power terminals are  
shared by two inputs.  
Supervised  
Model 7628  
Figure 4-23 Dry Contact Wiring  
4-24  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.9 5865-3 / 5865-4 LED Annunciator Installation  
The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote  
silence and reset key switches, and a general system trouble LED. The 5865-3 has 30  
mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and  
yellow (typically used for trouble) LEDs.  
Installation of the 5865-5 and 5865-4 is identical. The key switches and the trouble LED  
follow the behavior of other system annunciators and do not require any installation steps. The  
following sub-sections describe how to install the 5865-3 and 5865-4 hardware. Refer to  
Section 6 for programming information.  
Note: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common to both  
models.  
Figure 4-24 5865-3 and 5865-4 Assembly (front view)  
151209  
4-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
4.9.1 FACP Connection  
The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-25.  
After the 5865 is connected to the panel, it must be added to the system. This programming  
Supervised  
Power Limited  
Figure 4-25 5865 Connection to the FACP  
4-26  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.9.2 5865 Mounting  
Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang  
Figure 4-26 5865 Mounting Example  
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board  
assembly. These labels can be used in a typewriter or can be written on by hand. Slide the  
when illuminated.  
Figure 4-27 Inserting Zone Description Labels  
151209  
4-27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
4.10 Configuring Modules  
This section describes how to configure any system hardware modules that have been added  
to the system.  
4.10.1 Assigning Module IDs  
When installing a hardware module (such as, 5815XL, 5824, 5860, 5895XL, 5865-3 or 5865-  
4), you must use the dipswitches on the module to assign an ID# to the module.  
Figure 4-28 shows all possible dipswitch positions and their correlation to a numerical ID. For  
example, to select ID 2, place dipswitch 2 in the up position.  
Figure 4-28 Possible module addresses  
Refer to Section 6. to edit, add, delete, and view module list.  
4-28  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Control Panel Installation  
4.11 Telephone Connection  
from Silent Knight for this purpose.  
A number of programmable options are available for customizing telephone lines. These  
5211 Ground  
Start Relay Socket  
Figure 4-29 Connection of Telephone Lines  
4.12 5211 Ground Start Relay  
Note: Do not use ground start in UL installations.  
If connecting the control panel to a ground start telephone network, you must use the 5211  
ground start relay (order separately).  
To install the 5211:  
2. Enable ground start through the ground start programming option as described in Section  
151209  
4-29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
IntelliKnight 5820XL Installation Manual  
4.13 FlexputsI/O Circuits  
The six Flexput™ circuits are an innovative and versatile feature of the control panel. They  
can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4  
wire detectors), or as auxiliary power (resettable, continuous, or door holder).  
The polarity of the Flexput terminals differs depending on whether the circuit is programmed  
as an input or and output circuit. If the circuit is programmed as an input circuit (for a detector  
or normally open contact) the X terminal is negative and O terminal is positive. If the circuit is  
programmed as an output circuit (Aux power or NAC) then the X terminal is positive and the  
O terminal is negative.  
This section of the manual explains how to install conventional notification appliances and  
initiating devices to be used with the system.  
4.13.1 Conventional Notification Appliance  
This sub-section of the manual explains how to install conventional notification appliances for  
Class A (Style Z) and Class B (Style Y) configurations.  
4.13.1.1 Regulated Class B Notification Wiring  
You must use an appliance from the list of compatible appliances in the Appendix A at the  
back of this manual.  
To install a circuit:  
1. Wire Class B Notification appliances as shown in Figure 4-30.  
4-30  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Control Panel Installation  
2. Configure the circuit through programming (see Section 7.6).  
Alarm  
Polarity  
Notification Wiring  
Supervised  
Power Limited  
UL Listed EOL  
Model 7628  
4.7 kΩ  
Max. Impedance: 1.5Ω  
Regulated 24 VDC Full Wave Rectified  
27.4 VDC, 3A per Circuit, 6A max Combined  
Figure 4-30 Class B Notification Appliance Circuit Wiring  
151209  
4-31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
4.13.1.2 Class A Notification Wiring  
You must use an appliance from the list of compatible appliances in the Appendix at the back  
of this manual.  
To install a Class A notification appliance circuit:  
1. Wire the Class A notification appliances as shown in Figure 4-31.  
Caution  
For proper system supervision do not use looped wire under terminals marked O and X of the Flexput  
connectors. Break wire runs to provide supervision of connections.  
2. Configure the circuit for Class A in programming (see Section 7.6).  
Supervised  
Power Limited  
Regulated 24 VDC Full Wave Rectified  
27.4 VDC, 3A per Circuit, 6A max Combined  
Figure 4-31 Class A Notification Appliance Circuit Configuration  
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to  
refer to the circuit pair. For example, Figure 4-31 uses both Flexput circuit 5 and 6, so in programming it  
would be referred to as point 5.  
4-32  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.13.2 Conventional Input Switch Circuits  
This section of the manual explains how to install conventional initiating devices for Class A  
(Style D) or Class B (Style B) configurations.  
4.13.2.1 Class B Inputs  
You can connect conventional Class B switches, such as waterflow switches and pull stations,  
directly to the Flexput circuits of the control panel.  
To install a Class B switch:  
1. Wire the Class B switch as shown in Figure 4-32.  
2. Configure the circuit through programming (see Section 7.6).  
Supervised  
Power Limited  
UL Listed EOL  
Model 7628  
4.7 kΩ  
Figure 4-32 Class B Input Switches  
151209  
4-33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
4.13.2.2 Class A Inputs  
You can connect conventional Class A switches, such as waterflow switches and pull stations,  
directly to the Flexput circuits of the control panel.  
To install a Class A switch:  
1. Wire the Class A switch as shown in Figure 4-33.  
2. Configure the circuit through programming (see Section 7.6).  
Supervised  
Power Limited  
Note:  
Flexput circuit 5 and 6  
used as an example.  
Any Flexput point pairing  
could be used.  
Figure 4-33 Class A initiating Switches  
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to  
refer to the circuit pair. For example, Figure 4-33 uses both Flexput circuit 5 and 6, so in programming it  
would be referred to as point 5.  
4-34  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.13.3 Installing 2-Wire Smoke Detectors  
Any compatible U.L. listed two-wire smoke detector can be used with the control panel (see  
how to connect a UL listed 2-wire detector to the control panel.  
4.13.3.1 Installing 2-Wire Class B Smoke Detectors  
To install a Class B two-wire smoke detector, wire as shown in Figure 4-34.  
Supervised  
Power Limited  
UL Listed EOL  
Model 7628  
Note:  
Flexput circuit 5  
4.7 kΩ  
used as an example.  
Any Flexput circuit  
could be used.  
Figure 4-34 Two-Wire Class B Smoke Detector  
151209  
4-35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
4.13.3.2 Installing 2-Wire Class A Smoke Detector  
To install a Class A two-wire smoke detector, wire as shown in Figure 4-35.  
Supervised  
Power Limited  
Note:  
Flexput circuit 5 and 6  
used as an example.  
Any Flexput point pairing  
could be used.  
Figure 4-35 Two-Wire Class A Smoke Detector Connections  
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to  
refer to the circuit pair. For example, Figure 4-35 uses both Flexput circuit 5 and 6, so in programming it  
would be referred to as point 5.  
4-36  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.13.4 Installing 4-Wire Smoke Detectors  
Any compatible U.L. listed four-wire smoke detector can be used with the control panel (see  
how to connect a UL listed four-wire detector to the control panel.  
4.13.4.1 Installing a Class B 4-Wire Smoke Detector  
Figure 4-36 illustrates how to install a 4-wire Class B smoke detector.  
Conventions used for wiring 4-wire Class B loops:  
1. Up to three Class B 4-wire smoke detector loops can be connected to the control panel at  
once.  
2. Each Class B loop input is paired with a unique power source as shown in Figure 4-36.  
3. Each loop gets smoke power from the even numbered Flexput circuit and the contact input  
is connected to the odd numbered Flexput circuit.  
Supervised  
Power Limited  
UL Listed  
EOL Resistor  
Model 7628  
Air Products  
PAM-2  
Note:  
Model 160150  
Flexput circuit 5 and 6  
used as an example.  
Any Flexput point pairing  
could be used.  
Supervision  
Module  
ESL 449CT  
Figure 4-36 Class B 4-Wire Smoke Detector Connections  
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to  
refer to the circuit pair. For example, Figure 4-36 uses both Flexput circuit 5 and 6, so in programming it  
would be referred to as point 5.  
151209  
4-37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
4.13.4.2 Installing 4-Wire Class A Smoke Detectors  
Figure 4-37 illustrates how to install 4-wire Class A detectors.  
Conventions used for wiring 4-wire Class A loops:  
1. Up to two Class A 4-wire loops can be connected to the control panel at once.  
2. Smoke power is supplied to each Class A loop as shown in Figure 4-37.  
Air Products  
PAM-2  
Model 160150  
Supervision  
Module  
Air Products  
PAM-2  
Model 160150  
Supervision  
Module  
Supervised  
Power Limited  
Figure 4-37 Class A 4-Wire Smoke Detector Connections  
Note: In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput  
circuit number used. For example, Figure 4-37 uses Flexput circuits 1, 2, 3 together and 4, 5, 6 together.  
In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.  
4-38  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.13.5 Auxiliary Power Installation  
Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The three  
types of auxiliary power available are:  
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for  
all Flexput circuits must not exceed 6.0 A).  
To install an auxiliary power circuit:  
1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 4-38 for loca-  
tion of Flexput circuits.  
2. Configure the auxiliary power output through programming (see Section 7.6).  
Figure 4-38 Flexput Circuit Location  
4.13.5.1 Door Holder Power  
Door holder power is intended for fire door applications. When there are no alarms in the  
system and the panel has AC power, door holder circuits have 24-volt power present at their  
terminals. Any alarm will cause power to disconnect. Power will be re-applied when the  
system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power  
will be disconnected to conserve the battery backup. When AC power is restored, power is  
immediately restored to the door holder circuits.  
Use a UL listed door holder ESL DHX-1224, for this application.  
4.13.5.2 Constant Power  
Use constant power for applications that require a constant auxiliary power source. Power is  
always present at Constant circuits.  
151209  
4-39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
IntelliKnight 5820XL Installation Manual  
4.13.5.3 Resettable Power  
Resettable power is typically used to power beam detectors, flame detectors and conventional  
4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at  
the terminals unless a system reset occurs. If a system reset occurs, power is disconnected  
from the terminals for 30 seconds, then re-applied.  
4.14 On-Board Relays (Conventional)  
The control panel has two built-in programmable relays and a built-in trouble relay. All relays  
are Form C rated at 2.5 A @ 24 VDC.  
Figure 4-39 Location of Conventional Relay Circuits  
4.14.1 Trouble Relay  
The control panel has a dedicated Form C trouble relay built into terminals 30-32. The relay  
provides a normally open and a normally closed contact. The trouble relay will deactivate  
under any trouble condition.  
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no trouble con-  
ditions.  
4.14.2 Programmable Relays  
The control panel has two Form C programmable relays built into terminals 24-29. Each relay  
provides a normally open and a normally closed contact.  
To install one or two programmable relays, follow these steps.  
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-39 for the loca-  
tion of the relay terminals.  
2. Configure the relay through programming (see Section 7.6).  
4-40  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Control Panel Installation  
4.15 Remote Station Applications  
4.15.1 Keltron Model 3158 Installation  
The control panel is compatible with Keltron Model 3158, used for direct connection to a  
Keltron receiver. The 3158 reports alarms, supervisories, and troubles.  
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation  
instructions for complete information.  
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-40.  
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.  
3. Program control panel Relay 1 for alarm.  
4. Program Flexput circuit 5 for alarm.  
5. Program Flexput circuit 6 for supervisory non latching.  
Table 4-3: Keltron 3158 to Control Panel Connections  
Terminal #  
3158 Term. 1  
Connects To  
Terminal #  
3158 Term. 8  
Connects To  
To Keltron receiving equipment  
To Keltron receiving equipment  
Earth ground  
Control panel Term. 28  
Control panel Term. 5  
Control panel Term. 4  
3158 Term. 2  
3158 Term. 3  
3158 Term. 4  
3158 Term. 5  
3158 Term. 6  
3158 Term. 7  
3158 Term. 9  
3158 Term. 10  
Not used; no connection.  
Control panel Term. 18  
Control panel Term. 19  
Control panel Term. 7  
Control panel Term. 6 Control panel Term. 29  
Control panel Term. 28 Control panel Term. 31  
Control panel Term. 29 Control panel Term. 30  
Not suitable for remote station  
protected premise service  
where separate transmission  
circuits are required for fire  
supervisory (if applicable), and  
trouble signals.  
Example  
Intended for connection to a  
polarity reversal circuit of a  
remote station receiving unit  
having compatible ratings.  
Figure 4-40 Keltron 3158 Connection to Control Panel  
151209  
4-41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
4.15.2 City Box Connection Using the 5220 Module  
This section describes how to connect the control panel to a local energy municipal fire alarm  
box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire  
alarm service. The city (master) box is an enclosure that contains a manually operated  
transmitter used to send an alarm to the municipal communication center which houses the  
central operating part of the fire alarm system.  
City Box Standby Current:  
0 (Notification supervision current  
accounted for in control panel draw.)  
Alarm Current:  
1 Amp for 1 second  
27.2 VDC max  
The maximum coil and wire resistance (combined) must not exceed 30 ohms.  
To install the 5220 for city box connection:  
1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a  
short piece of conduit (must not exceed 20 feet in length).  
2. Wire the 5220 to the control panel as shown in Figure 4-41. This drawing also shows how  
to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resis-  
tor in the terminals of the Flexput circuit used for this application.  
3. Connect earth ground wire to the 5220 chassis with mounting screw.  
4. Program the Flexput circuit used as a notification circuit, continuous and non-silencing.  
It is not possible to reset the remote indication until you clear the condition and reset the  
control panel.  
Note:  
Flexput Circuit 1 Used  
as an example.  
Any Flexput circuit  
could be used.  
All circuits non-power-limited.  
All wiring non-supervised.  
Figure 4-41 City Box Connection  
4-42  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.15.3 NFPA 72 Polarity Reversal  
Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having  
compatible rating.  
4.15.3.1 Using the 5220 Module  
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble  
events to a remote site. Alarms will override trouble conditions and it will not be possible to  
reset the remote indicator until the condition is cleared and the control panel is reset.  
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.  
Standby Current:  
Alarm:  
100 mA, 24 VDC  
100 mA, 24 VDC  
To install the 5220 for polarity reversal, follow the steps below:  
1. Locate the knockout on the right side of the control panel cabinet to connect the 5220  
using a short piece of conduit (must not exceed 20 feet in length).  
2. Wire the 5220 to the control panel using the four-wire pigtail provided as shown in Figure  
4-42. This diagram also shows how to connect the 5220 to the remote indicator. Do not  
install an EOL resistor in the terminals of the Flexput circuit used for this application.  
3. Connect earth ground wire to the 5220 chassis with mounting screw.  
4. Program the Flexput circuit used as a notification circuit, continuous and non-silencing.  
5. If necessary, adjust loop current using the potentiometer (R10) on the 5220 board . Normal  
loop current is 2-to-8 mA with a 1k ohm remote station receiving unit. Maximum loop  
resistance is 3k ohm.  
Note:  
Flexput circuit 1 and Relay 1  
used as examples. Any  
Flexput circuit and either  
relay 1 or relay 2 could  
be used.  
All circuits power-limited.  
All wiring supervised.  
Jumper these terminals  
when City Box is not used.  
Intended for connection to a Polarity Reversal  
circuit of a Remote Station receiving unit having  
compatible ratings.  
Figure 4-42 Polarity Reversal Connection Using the 5220 Module  
151209  
4-43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
4.15.3.2 Using the 7644 Module  
When the 7644 is used for polarity reversal, it allows alarm and trouble events to be reported  
to a remote site. Alarms will override trouble conditions and it will not be possible to reset the  
remote indicator until the condition is cleared and the control panel is reset.  
To install the 7644 for polarity reversal:  
1. Wire the 7644 to the control panel as shown in Figure 4-43. Do not install an EOL resistor  
on the terminals of the Flexput circuit used.  
Note: Use only Flexput circuits on the control panel for reverse polarity.  
2. Program the Flexput circuit as a notification circuit. See Section 7.6.2.  
3. Map the group to activate constant on from the zone event. See Section 7.4.1.3.  
4. Program the output group characteristics as non-silenceable and reverse polarity. See Sec-  
Figure 4-43 Polarity Reversal Connection Using the 7644  
4-44  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.15.4 Using the SD500-ARM Addressable Relay Module  
When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a  
remote site. Alarms will override trouble conditions and it will not be possible to reset the  
remote indicator until the condition is cleared and the control panel is reset.  
1 kΩ  
Intended for Connection to a  
Polarity Reversal Circuit of A  
Remote Station Receiving Unit  
Having Compatible Rating.  
To City Box  
UL Listed  
Model 7642  
Must be installed  
in City Box enclosure  
Figure 4-44 Polarity Reversal Connection Using the SD500-ARM Module  
151209  
4-45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
4.15.5 Using a MR-201/T Control Relay From Air Products  
When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble  
events to a remote site. Alarms will override trouble conditions and it will not be possible to  
reset the remote indicator until the condition is cleared and the control panel is reset.  
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.  
Current:  
15 mA max.  
24 VDC nominal  
4 KΩ  
Operating Voltage:  
Resistance:  
To install the MR-201/T for polarity reversal, follow the steps below:  
Intended for Connection  
to a Polarity Reversal  
Circuit of A Remote  
Station Receiving Unit  
Having Compatible  
Rating.  
Figure 4-45 Wiring the MR-201/T  
2. Program the Flexput circuit for non silence NAC circuit (see Section 7.6).  
4-46  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control Panel Installation  
4.15.6 Transmitter Activated by Dry Contacts  
This section describes the connection of a UL 864 listed remote station transmitter to the  
5820XL FACP dry contacts. The FACP contacts must be supervised by the remote station  
transmitter module using end-of-line resistors (ELRs) with a value determined by the  
transmitter manufacturer. Power is also provided by the remote station transmitter  
manufacturer. Refer to the remote station transmitter manufacturer’s manual for details.  
151209  
4-47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
4-48  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5  
Hochiki and SK SLC Device Installation  
Caution!  
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the  
control panel while installing or servicing.  
5.1 List of SK SLC Devices  
The following SK SLC devices can be used with the control panel. See the device installation  
instructions for more information (packaged with the device).  
Note: The control panel supports the use of either SK SLC devices or Hochiki SLC devices. You cannot install  
both SLC device types on the control panel.  
SK  
Section/ Install  
Sheet PN  
Model Name/Description  
Part Number  
SK-Photo  
Photoelectric smoke detector  
SK-Photo-T  
SK-Acclimate  
SK-Beam  
Photoelectric smoke detector with thermal (135°F)  
Multicriteria photoelectric smoke detector with thermal (135°F)  
Reflected beam smoke detector without test feature  
Reflected beam smoke detector with test feature  
Ionization smoke detector  
I56-3426-001  
I56-3433-001  
SK-Beam-T  
SK-Ion  
I56-3428-001  
I56-3432-000  
SK-Duct  
Photoelectric duct smoke detector with extended air speed range  
Fixed temperature thermal detector (135°F)  
Rate-of-rise thermal detector with 135° fixed temperature  
Fixed high temperature thermal detector (190°F)  
Addressable single action pull station  
Addressable dual action pull station  
Fault isolator module  
SK-Heat  
SK-Heat-ROR  
SK-Heat-HT  
SK-Pull-SA  
SK-Pull-DA  
SK-Iso  
I56-3429-000  
I56-3446-001  
I56-3447-001  
I56-3445-000  
I56-3442-000  
I56-3444-000  
I56-3435-000  
I56-3443-000  
I56-3438-000  
I56-3439-000  
I56-3440-000  
I56-3441-000  
I56-3436-000  
I56-3437-000  
K200-07-00  
D450-15-00  
D450-16-01  
D550-06-00  
D550-02-00  
SK-Monitor  
SK-Minimon  
SK-Monitor-2  
SK-Mon-10  
SK-Relay  
Monitor module  
Mini monitor module  
Dual input monitor module  
10 input monitor module  
Addressable relay module  
SK-Relay-6  
SK-Zone  
Six relay control module  
Addressable zone interface module  
Six zone interface module  
SK-Zone-6  
SK-Control  
SK-Control-6  
B201LP  
Supervised control module  
Six circuit supervised control module  
6" mounting base  
B224BI  
6" isolator base  
B224RB  
6" relay base  
B501BHT-2  
B501  
6" temporal sounder base  
4" mounting base  
151209  
5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
5.2 List of Hochiki SLC Devices  
The following Hochiki SLC devices can be used with the control panel. See the appropriate  
section number in this manual or the device installation instructions (packaged with the  
device) for more information.  
Note: The control panel supports the use of either Hochiki SLC devices or SK SLC devices. You cannot install  
both SLC device types on this control panel.  
Section No./  
Model Number  
Model Name/Description  
Installation  
Instructions PN  
SD505-APS  
Photoelectric smoke detector.  
Ionization smoke detector  
Section 5.7  
SD505-AIS  
SD505-AHS  
SD505-6AB  
SD505-6IB  
SD505-6RB  
SD505-6SB  
Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).  
6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS.  
150955  
151175  
151192  
151191  
6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and SD505-APS  
6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS  
6" sounder base for use with the SD505-AHS, SD505-AIS, and  
SD505-APS SLC devices  
SD505-DUCT  
Duct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric Smoke  
Sensor. Intake tubing for duct available in three lengths:  
1700-09882  
SD505-T2.5 (2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot)  
SD505-DUCTR  
SD505-ADH  
Duct Detector housing with relay base. Duct housing with relay base including SD505-APS  
Analog Photoelectric Smoke detector pre-installed  
1700-09882  
151040  
Duct Detector Housing for use with the SD505-AIS or SD505-APS smoke detectors. Intake  
tubing for duct available in three lengths:  
STS-2.5: Duct widths 1.0’ to 2.5’; STS-5.0: Duct widths 2.5’ to 5.0’; STS-10.0: Duct widths  
5.0’ to 10.0’ When ordering SD505-ADH, specify intake tubing size and order the appropriate  
smoke detector (if needed).  
SD505-ADHR  
SD500-PS/-PSDA  
SD500-AIM  
Duct detector housing with relay (for use with SD505-AIS or SD505-APS smoke detectors)  
Single or dual action addressable pull station  
151126  
151177  
151071  
Addressable input module (switch input), standard size, dipswitch configurable  
SD500-MIM  
Mini input monitor module (switch input), small size, dipswitch configurable. Fits in single-  
gang box with manual pull station switch.  
151071  
SD500-ANM  
SD500ARM  
SD500-SDM  
Addressable notification module  
151109  
151091  
151193  
Addressable relay module dipswitch configurable.  
Addressable smoke detector module. Use to assign an address to a loop of conventional  
devices.  
SD500-LIM  
SD500-LED  
Line isolator module. Fits in a double gang box.  
151125  
151232  
Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-LED  
Driver Modules can be used per SLC loop.  
SD505-DTS, SD505-DTS-K Remote test switch & LED indicator for the SD505-ADHR and SD505-DUCTR  
151126  
5-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Hochiki and SK SLC Device Installation  
5.3 Maximum Number of Devices  
The 5820XL supports SK or Hochiki devices on one 5820XL system. The maximum number  
of devices per system varies depending on device protocol and the number of 5815XL  
signaling circuit loop (SLC) expanders added to the system. Device support is as follows:  
SK Devices–A 5820XL system can support a total of 396 SK detectors and 396 SK  
modules. 99 detectors and 99 modules can be connected to the built-in SLC loop. Each  
optional 5815XL adds another 99 detectors and 99 modules. Add up to three 5815XLs to a  
system to achieve the maximum number of devices on the system.  
OR  
Hochiki Devices–A 5820XL system can support a total of 508 Hochiki SLC detectors and  
modules, in any combination. 127 devices can be connected to the built-in SLC loop. Each  
optional 5815XL adds another 127 devices.  
5.4 Wiring Requirements for SLC Devices  
The following information applies to all SLC devices. Refer to the section that describes the  
type of device you are installing for details.  
5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration  
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid  
or stranded as long as it meets the National Electric Code 760-51 requirements for power  
limited fire protective signaling cables. Wire distances are computed using copper wire.  
Maximum wiring resistance is 40 ohms for SK devices and 50 ohms for Hochiki devices.  
Maximum loop length depends on the wire gauge. See Table 5-1 for SK and Table 5-2 for  
Hochiki.  
Table 5-1 Maximum wiring distance for SK modules  
Wire Gauge  
MAx. Distance for SK  
1200 feet  
22 AWG  
18 AWG  
16 AWG  
14 AWG  
12 AWG  
3100 feet  
4900 feet  
7900 feet  
10,000 feet  
Table 5-2 Maximum wiring distance for Hochiki devices  
Wire Gauge  
Max. Distance for Hochiki  
22 AWG  
18 AWG  
16 AWG  
14 AWG  
1500 feet  
3900 feet  
6200 feet  
10,000 feet  
151209  
5-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
IntelliKnight 5820XL Installation Manual  
Figure 5-1 and Figure 5-2 show how wire length is determined for out-and-back tap and T-tap  
style wiring.  
Figure 5-1 Calculating wire run length for a simple out and back tap  
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet.  
This requirement must be met in addition to the maximum distance requirements for the  
various wire gauges.  
Figure 5-2 Calculating Wire Run Length for a T-tap  
5-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hochiki and SK SLC Device Installation  
5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration  
Figure 5-3 illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations.  
Note: Style 6 does not use short circuit isolator devices.  
Figure 5-3 Class A SLC Configuration  
Note: No t-taps allowed on class A SLC loops.  
Caution  
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors.  
Break wire runs to provide supervision of connections.  
151209  
5-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
5.5 Wiring SK SLC Detectors  
This section describes how to install SK heat and smoke detectors. All detectors ship with  
installation instructions. Refer to the detector’s installation instructions for more detailed  
information.  
This information applies to the following SK models:  
SK-Photo Photoelectric Smoke Detector  
SK-Photo-T Photoelectric Smoke Detector with Thermal  
SK-Acclimate Photoelectric Smoke Detector with Thermal  
SK-Heat Fixed Temperature Detector  
SK-Heat-T High Temperature Thermal Detector  
SK-Heat-ROR Rate-of-Rise Thermal Detector  
SK-Ion Ionization Smoke Detector  
To wire SK detectors:  
1. Wire device bases as shown in Figure 5-4.  
2. Set the address for each device as described in Section 5.6.  
Caution: Do not loop wire under Terminal 1 or 2.  
Break wire run to provide supervision of connections.  
...............  
Class A wiring:  
Class B wiring:  
Figure 5-4 Heat and Smoke Detector Connection to the Panel.  
5-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Hochiki and SK SLC Device Installation  
5.6 Addressing SK SLC Devices  
All SK devices are addressed using the two rotary dials that appear on the device board. Use  
the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS  
rotary dial to set the tens place in a two digit number.  
SK device addresses are handled differently than Hochiki device addresses. The control panel  
recognizes when an SK detector or SK module is installed. For this reason, SK detectors can  
be assigned any unique address from 1 to 99, and SK modules can be assigned any unique  
address from 1 to 99. Unlike Hochiki detectors and modules which share addresses 1 through  
99, there can be an SK detector using address 1 and an SK module using address 1. 0 is an  
invalid address.  
Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS rotary  
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary  
All dials labeled for ONES  
or TENS position.  
Example 1: Device Set to 01.  
Example 2: Device Set to 42.  
Figure 5-5 SK SLC Device Addressing Using Rotary Dials  
151209  
5-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
5.7 Hochiki Detector Installation  
The information in this section applies to the following Hochiki models: SD505-AHS Heat  
Detector, SD505-AIS Ionization Smoke Detector, and SD505-APS Photoelectric Smoke  
Detector.  
Also see Section 5.8 for information on how to address the detectors.  
5.7.1 Wiring Hochiki Detectors  
1. Wire device bases as shown in Figure 5-6.  
2. Set the address for each device as described in Section 5.8.  
3. If you are connecting to the main panel, do not connect any devices to terminals 35 and  
36. If you are connecting to the 5815XL, do not connect any devices to “SLC IN”.  
Figure 5-6 Heat or Smoke Detector Connection to the FACP (Class B)  
5-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Hochiki and SK SLC Device Installation  
5.8 Addressing Hochiki Devices  
This section tells how to address detectors and modules.  
5.8.1 SD505-APS, SD505-AHS, & SD505-AIS  
The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS  
ionization smoke detector are easily addressed at the FACP. The Installer Code is required to  
perform this task.  
To address a SD505-APS, SD505-AHS, or SD505-AIS:  
1. Connect a detector base temporarily to the programming terminals as shown in  
Figure 5-7. (You can use the same base for each detector.)  
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing  
ENTER  
2. Enter the Installer code, then press  
.
2
3. Select for Point Functions.  
3
4. Select for Set SLC Dev Addr.  
ENTER  
5. Select Yes” by pressing the  
up arrow, then press  
. (The panel will go into  
SILENCE  
trouble at this point. You can use the  
key to stop the PZT. The trouble will clear  
automatically when the panel re initializes when you finish programming.)  
6. When the wait message clears, the following options display:  
1
for Read Address. Use to read (or check) a single detector’s address.  
2
for Write Address. Use to program a single detector’s address.  
3
for Seq. Programming. Use to program more than one detector in sequential order.  
7. If you are changing addresses, write the programmed address on the back of the device.  
8. To exit press  
left arrow until fully exited.  
151209  
5-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
5.8.2 SLC Devices with Dip Switches  
Input and relay module addresses are set using the dip switches on the module board. The  
chart below shows the available addresses. For example, to select address 3, place dip  
switches 1 and 2 in the up position. The range of valid addresses is 1-127. 0 is an invalid  
address.  
Figure 5-8 Hochiki SLC Device Addressing Using Dip Switches  
5-10  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Section 6  
Programming Overview  
This section of the manual is intended to give you an overview of the programming process.  
Please read this section of the manual carefully, especially if you are programming the control  
panel for the first time.  
The JumpStart feature automates many programming tasks and selects default options for the  
system. You will run JumpStart at least once when you are installing the system. See Section  
6.1 for details. After you run JumpStart, you may need to do some additional programming  
in detail.  
Programming the panel can be thought of as a three part process. You must program:  
System options. These are options that affect general operation of the panel (see Section  
Options for input points and zones. These are primarily options that control detection  
behavior of devices (see Section 7.6 for details).  
Options for output points and groups. This includes selecting characteristics for output  
groups and mapping output circuits to output groups (see Section 7.6 for details).  
6.1 JumpStart Autoprogramming  
The JumpStart feature allows for faster system setup. When you run JumpStart (immediately  
after addressing SLC devices), the system scans devices on all SLC loops and determines  
device type (for example, ionization smoke detector or heat sensor) and selects some system  
options based on the device type. This saves the installer from having to program options for  
each device. Depending on the application, the installer may need to make some changes after  
JumpStart completes.  
See Section 6.1.3 for complete details about running JumpStart.  
IMPORTANT  
JumpStart is intended to be run one time only, immediately after SLC devices have been addressed and connected.  
JumpStart will reset all manually programmed options to default settings. Do not run JumpStart after you have  
configured the system.  
151209  
6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
6.1.1 Input Points  
JumpStart will determine the number and type of input points (detectors or contact monitor  
modules) on each SLC loop. JumpStart assigns the correct detector type (heat, ionization or  
photoelectric), so the installer does not need to edit device type for detectors. Any contact  
monitor modules on the system will be assigned type "Manual Pull." The installer will need to  
manually change the switch type if manual pull is not correct.  
JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped  
to Output Group 1. After JumpStart completes, you can re-map to configure a multiple zone/  
output group system (see Section 7.4.1.3). For a general explanation of mapping, see Section  
6.1.2 Output Points  
JumpStart creates three output groups and assigns output circuits as follows:  
Circuits 1-6:  
Configured as Notification and assigned to Group 1. JumpStart automatically programs Zone  
1 to activate Group 1 using constant on output.  
Circuit 7 (Relay 1):  
Assigned to Group 249. JumpStart automatically programs Zone 1 to activate Group 249  
using constant on output when a supervisory condition occurs.  
Circuit 8 (Relay 2):  
Assigned to Group 250. JumpStart automatically programs Zone 1 to activate Group 250  
using constant on output when an alarm occurs.  
Addressable output points (Relay modules, NAC Modules, Sounder Bases, Relay Bases):  
All addressable relay devices will be configured as “Output Pt” (general purpose output point)  
and assigned to Group 1.  
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.  
6.1.3 Running JumpStart  
Run JumpStart immediately after you have addressed and connected all input devices  
(detectors, pull stations, and so on) and output devices (notification appliances, relays, and so  
on).  
Note: If you need to install a few devices after you have run JumpStart, you can install them manually. Follow  
instructions in Section 8 for configuration.  
To run JumpStart, follow these steps.  
1. Press  
to view Main Menu.  
7
2. Select for Program Menu.  
6-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Programming Overview  
6
3. From the next menu, select for JumpStart.  
4. The message "WARNING Will DELETE all system options" displays on the LCD. Select  
Yes to continue. A series of messages displays for the next several seconds. JumpStart  
scans the SLC loops for devices. This can take several minutes, depending on the number  
of devices attached.  
5. When the message, "SLC FAMILY HOCHIKI" flashes. Press  
installing, or press to display SK and press to accept SK.  
to accept Hochiki if  
6. When the message “Configuring System Done” displays, press any key to continue.  
7. Select one of the following options from the menu that displays.  
1
2
3
1
2
- Review System  
Press  
Press  
if you need to review the JumpStart configuration.  
if you need to rerun JumpStart for any reason.  
- Repeat JumpStart  
- Accept Configuration  
3
1. If you are ready to make the JumpStart configuration permanent, select  
.
2. The system will ask you if the installation contains duct detectors. If there  
2
are none, select  
detectors, select  
for No and skip to Step 8. If the system contains duct  
for Yes and continue with Step 3.  
1
3. From the list that displays, select the 5815XL device that contains the duct  
detectors.  
4. The first photoelectric or ionization detector on the system will display.  
1
2
Select  
for DUCT and  
for NonDUCT.  
1
2
5. Press  
to select the next detector. Select  
for DUCT and  
for Non-  
DUCT. Continue until all duct detectors have been selected. (Note: You can  
move backwards through the list with .)  
6. When you reach the last detector on this device, press  
.
7. The system will ask you if there are more duct detectors in the system. If  
1
there are, select  
for Yes and repeat from Step 3. If there are no more  
2
duct detectors, select  
for No and continue with Step 8.  
1
8. The system will restart in 10 seconds. You can press  
to restart immedi-  
2
ately. Do not select  
for System Diagnostics. (This feature is for use in  
testing at the factory.)  
9. After the system resets, it will use the new JumpStart configuration.  
If you want to go directly to Program Mode to configure any devices, press  
4
- Enter Programming  
4
. The Programming Menu appears and you can begin programming.  
151209  
6-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
6.2 Mapping Overview  
This section of the manual is an overview of mapping. Details about how to select mapping  
options appear in the appropriate subsections in Section 7.  
Mapping is an important concept with the control panel. In general terms, mapping is  
assigning or linking events to outputs that should activate when events occur. You do this by  
assigning input points to input zones, output points to output groups and then linking or  
mapping zones and output groups.  
Figure 6-1 is a brief overview of the concept of mapping. The next several pages of the  
manual show these subjects in detail.  
Figure 6-1 Mapping Overview  
6-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Programming Overview  
6.2.1 Input Point Mapping  
Input points are assigned to input zones. Any input point can be assigned to any input zone.  
(Input points can be assigned to one zone only. An input point can be designated as “Unused,”  
which means it has not been assigned to a zone.)  
Figure 6-2 Input Point Assignment Example  
151209  
6-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
6.2.2 Output Circuit Mapping  
Figure 6-3 is a simple example showing how to assign notification and relay output circuits to  
groups. For an example of a simple floor above/floor below application, see Figure 6-5.  
Figure 6-3 Assigning Output Circuits to Groups (Example)  
6-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Programming Overview  
6.2.3 Zone Event Mapping  
There are 8 types of events that can occur in zones (see below). For each event type, you can  
activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output  
groups, an output group template may be used (see Section 7.5.5 for information on output  
group templates). Event types are:  
Manual Pull Alarm  
Water Flow Alarm  
Detector Alarm (heat or smoke detectors)  
Aux 1 and Aux 2 Alarm (user-specified alarm types)  
Pre-alarm  
Supervisory  
Trouble  
Figure 6-4 Example of Zone Events Mapped to Output Groups and Patterns  
151209  
6-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns  
6-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Programming Overview  
6.2.4 Mapping LED Points  
Figure 6-6 is a simple example showing how LED points are mapped to zones and output  
groups. Typically you would create two output groups for each zone, one for alarms and one  
for troubles. (LED points are available when Models 5865-3/4 and/or 5880 are used with the  
system.)  
Figure 6-6 Example of LED Points Mapped to Output Groups  
(applies to Models 5865-3/4 and 5880)  
151209  
6-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
6.3 Programming Using the 5660 Silent Knight  
Software Suite  
You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel  
onsite or remotely. SKSS is an optional software package that lets you easily program the  
control panel using a Windows-based computer and a modem* (not sold by Silent Knight).  
When using SKSS, you can set up the programming options for the panel, save the options in  
a file, then download the file to the panel. You connect to the control panel directly using the  
control panel’s onboard USB or serial port or remotely using a modem. If you need to connect  
to an older control panel that does not have a USB port, and your laptop does not have a serial  
port, use a USB to serial converter. SKSS includes an online help system and a manual. See  
the SKSS manual (PN 151240) for more information.  
*
See Section 1.3 for a list of modems that have been tested for compatibility with the control panel and SKSS.  
6.4 Programming Using an Annunciator  
You can program the control panel from a system annunciator, using either the control panel’s  
on-board annunciator or a Model 5860 Remote Annunciator.  
The following subsections describe programming basics, including a description of editing  
keys available for programming and how to move through programming menus. Section 7  
contains specific information about individual programming options.  
6-10  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Programming Overview  
6.4.1 Entering & Exiting the Program Menu  
To enter Program Mode:  
1. Enter the Installer Code (factory programmed default code is 5820).  
2. The display prompts you to press the  
or  
key to bring up the Main Menu (see Figure  
Figure 6-7 Keypad Enabled Screen  
7
3. Then press . The menu option displays. See Section 7 for detailed menu information and  
Section 6.5 for a quick reference listing all programmable options and JumpStart defaults.  
To exit Program Mode:  
When you have completed working with the menus, press (left arrow) several times until  
you are exited from programming mode. Two prompts will display. The first prompt is to  
make sure you intended to leave the Program Menu (select Yes or No as appropriate). The  
second prompt is for accepting all changes. If you select No, any changes you have made  
since you entered the Program Menu will have no effect.  
6.4.1.1 Moving through the Menus  
Figure 6-8 shows how to move through Program Menu screens, using the System Options  
screen as an example.  
Figure 6-8 Moving through Program Menu  
(System Options Sub-Menu Used as an Example)  
151209  
6-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
6.4.1.2 Selecting Options and Entering Data  
There are several ways to make programming selections using the control panel depending on  
which screen you are currently using. The chart below is a generic explanation.  
To  
Press  
Select from a menu.  
Enter the number of the option.  
Enter numeric data.  
Press the appropriate number on the annunciator.  
Enter text (alphanumeric data).  
Enter each letter individually by pressing and holding any numeric key until the  
one you wish to select displays. Then press  
Section 6.4 for complete information.  
(right arrow) to select the letter. See  
Select from a scrolling list.  
Use  
(up arrow) and  
(down arrow) to move through a list of available  
options. When the option you want to select is displayed, press  
.
6.4.1.3 Editing Keys  
The keys shown in Figure 6-9 are available for use when you are in the Program Menu.  
Figure 6-9 Editing Keys Available from Program Menu  
6-12  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Programming Overview  
6.5 Programming Menu Quick Reference  
This section of the manual lists all Program Menu options in the order they appear on the sub-  
menus. Default settings are indicated in text or marked with an asterisk. The comments  
column provide quick information and a reference to a section (if applicable) which has more  
detailed information.  
Menu  
Options/Defaults  
Comments  
Hochiki  
SK  
SLC  
Section 7.2  
Family  
Module  
Edit Module  
Select Module  
5815XL-SLC  
Enter Module Name Select Class  
Section 7.3.1  
5860-Keystation  
5824-Ser/Par/IO  
Add Module  
5895XL-io/Pwr Sup  
5496 NAC Expand  
5880-LED/IO Dev  
5865-LED Annunc  
List of Modules  
Delete Module  
View Module List List of Modules  
Enter Name1  
Enter Number1  
Enter Name2  
Enter Number2  
Edit Zone Name  
Zone Properties  
*1 Count  
2 Count  
Alarm Ver.  
PAS  
Verification Type  
SNGL ILOCK  
DBL ILOCK  
Heat Temp Set 135° to 150°F Section 7.4.1.2  
Manual Pull  
Edit Zone  
Select Zone to Edit  
(MP)  
(Groups 01 &  
Zone  
Water Flow  
(WF)  
250, Pattern  
00)  
Detector Alarm  
Aux 1  
Zone Outputs  
Aux 2  
no group  
Pre-alarm (PRE)  
Supervisory  
(SUP)  
(Group 249,  
Pattern 00)  
Trouble (TRB) no group  
Cadence  
00-20  
Zone Accessory Opt  
Local Zone  
Yes or No  
Add Zone  
Adds next available zone number.  
Select Zone to be Deleted  
Section 7.4.3  
Section 7.4.4  
Delete Zone  
View Zone Points List of all points in selected zone.  
151209  
6-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
Menu  
Options/Defaults  
Comments  
Enter Name1  
Enter Number1  
Enter Name2  
Enter Number2  
Group Name  
Latching  
Options  
*Non-  
Latching  
Latching  
*SILENCE  
Silenceable  
NON-SIL  
Non-Silenceable  
Auto  
Auto Un-silenced  
Silencing  
Options  
Unsilence  
SIL-INHIB  
Silence after inhib  
delay. Section  
Edit Group  
Select Group  
SHUT-  
DOWN  
Automatic  
Shutdown  
Group Properties  
Group  
*No.  
1
Group  
Activates for Section 7.5.1.2  
all Man. Pull  
Group  
*Yes.  
Activates for Section 7.5.1.2  
Fire Drill  
Group Active  
With:  
Group  
*No.  
Activates for Section 7.5.1.2  
Aux 1  
Group  
*No  
Activates for Section 7.5.1.2  
Aux 2  
Ignore Global *No  
Cadence  
Section 7.5.3  
Section 7.5.5  
Add Group  
Delete Group  
Select Group to Delete  
View Group Points Select Group  
Select Group  
Yes  
No  
Select Template  
Edit OPG Template  
Number  
Include in template  
Select Pattern  
0-16  
6-14  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming Overview  
Menu  
Options/Defaults  
Comments  
UNUSED  
PHOTO  
ION  
Select  
Latching  
HEAT  
DETECTOR  
SUP DET  
PHOT DUCT  
ION DUCT  
2WIRE SMK  
SUP PHOTO  
SUP ION  
MAN_PULL  
Section 7.6  
Select  
Latching  
LATCH  
WATERFLOW  
SUPERVSY  
NLATCH  
LATCH  
NLATCH  
FIREDRILL  
SILENCE  
RESET  
PAS_ACK  
LATCH  
ZN_AUX1  
ZN_AUX2  
SYS_AUX1  
Internal and  
External 5815XL  
Point  
Enter Pt  
NLATCH  
LATCH  
SWITCH  
Section 7.6  
NLATCH  
LATCH  
NLATCH  
LATCH  
SYS_AUX2  
DETECT SW  
TAMPER  
NLATCH  
LATCH  
NLATCH  
MAN REL  
ILOCK  
OUTPUT PT  
AUX CONST  
AUX RESET  
AUX DOOR  
OUTPUT PT  
AUX RESET  
AUX DOOR  
Select Group  
Select Group  
NOTIF  
Section 7.6  
Section 7.6  
RELAY  
SLC LED  
LED No. 01 - 80 Select Group Section 7.6  
151209  
6-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Menu  
Options/Defaults  
Comments  
Enter Pt  
Input Point Type  
(detector/switch)  
Select Function  
Select Group  
Per JumpStart  
UNUSED  
B NOTIF  
A NOTIF  
Select Type  
CONSTANT  
RESETABLE  
DOOR  
AUX PWR  
MAN PULL  
Select zone  
Latch and Non-  
latch feature only  
appear for  
WATERFLOW Select zone  
SUPERVSY  
TAMPER  
Select zone  
Select zone  
waterfowl,  
supervisory,  
tamper, zone  
aux1, zone aux2,  
system aux1, and  
system aux2.  
DETECT SW  
FIREDRILL  
SILENCE  
RESET  
Section 7.6.  
B SWITCH  
PAS_ACK  
ZN_AUX1  
ZN_AUX2  
SYS_AUX1  
SYS_AUX2  
MAN REL  
ILOCK  
Select zone  
Select zone  
Select zone  
Internal Pwr and  
External Power  
Point  
(cont.)  
Section 7.6  
Section 7.6  
A SWITCH  
Same as B SWITCH  
2-WIRE SMK  
4-WIRE SMK  
2-WIRE SMK  
4-WIRE SMK  
B DETECTOR  
A DETECTOR  
Select Group or  
Zone Number  
Group or Zone  
selection will  
appear depending  
on the type  
selected.  
Section 7.6  
Edit Name  
Enter Name  
NOTIF  
Enter Point #  
UNUSED  
5880  
Select Group #  
Edit Name  
Enter Name  
NOTIF  
Enter Point #  
UNUSED  
5865  
Select Group #  
Edit Name  
Enter Name  
6-16  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming Overview  
Menu  
Options/Defaults  
Comments  
For each account (1-4), select:  
*123456  
Edit Account #  
Account # (6-digit  
number, identifies  
account to central  
station)  
Edit Format  
*Contact ID Reporting Format  
(SIA, S20,  
Contact ID)  
Y (Yes)  
N (No)  
*Yes  
*No  
Section 7.7.1  
Report Alarms  
M (Must)  
Y (Yes)  
Rep. Alarm Restore N (No)  
M (Must)  
Y (Yes)  
N (No)  
Report Troubles  
Edit Acct.  
M (Must)  
Y (Yes)  
System  
Options  
Reporting  
Accounts  
Report Ena/Disable N (No)  
M (Must)  
Y (Yes)  
N (No)  
M (Must)  
Y (Yes)  
N (No)  
M (Must)  
1 - 5  
Report Test  
Report Resets  
Switch attempts  
Fail attempts  
*5  
Section 7.7.1  
1 - 15  
*10  
Primary Phone Line 1 or 2  
*Line 1  
*Line 2  
Secondary Phone  
Line  
1 or 2  
Edit Phone #1  
Set the Hour  
up to 40 digits  
blank  
Auto Test Time  
Set the Minutes  
Select AM/PM  
*02:00 AM  
151209  
6-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Menu  
Options/Defaults  
Comments  
For each phone line (1 & 2), select:  
Dialing Prefix  
Up to 9 digits  
none  
06  
Section 7.7.2.1  
# of Answer Rings Range: 00-15  
Number of rings  
before panel  
answers a call  
from a computer  
TT  
Touch Tone  
TT/PL  
Select Dialing  
Option  
TouchTone  
alternating with  
pulse see Section  
TouchTone  
Phone Lines  
Select Phone Line  
PULSE  
Pulse dialing  
U = 60/40  
Rotary Pulse Format  
E = 66/34  
*U  
Yes  
*Yes  
Line Monitor  
No  
Yes = enabled  
Ground Start  
*N = Disabled  
*Y = Enabled  
None selected  
None selected  
None selected  
No = disabled  
Answering Machine Yes = enabled  
Bypass  
No = disabled  
System  
Options  
(cont.)  
Select Group  
System Trouble  
Select Cadence  
Alarm Silence  
Select Group  
Select Cadence  
Select Group  
Select Cadence  
Group Tr  
Trbl Silence  
SBUS Com  
SBUS Pwr  
SLC Loop  
AC Loss  
Trouble Events  
Select Group  
System Event  
Outputs  
Battery  
User Selected  
Gnd Flt  
Phone Ln  
Account  
Select  
Cadence  
Printer  
Aux Pwr  
Sys Sw  
Fire Drill  
Sys Alarm Cadence System Aux1  
System Aux2  
Select Cadence Constant  
6-18  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming Overview  
Menu  
Options/Defaults  
Comments  
0 - 90 Seconds  
*30 sec  
*3 hrs  
Water Flow delay  
is the number of  
sec. before water  
flow alarm is  
Water Flow Delay  
generated. Section  
0 - 30 hours  
Low AC Report  
Delay. Section  
Low AC Delay  
DST  
Y (Enabled)  
N (Disabled)  
Automatic Daylight Saving Time  
enable or disable. Section 7.7.4.3  
and 7.7.6.3. See also DST settings  
in Misc. Option 3, below.  
Misc. Options 1  
*Enabled  
*AM/PM  
AM/PM  
MIL  
System Clock  
Format (AM/PM  
or military).  
CLK  
50 Hz  
Section 7.7.4.5  
AC Freq:  
60 Hz  
System  
Options  
(cont.)  
Neither  
Y (Enabled)  
N (Disabled)  
Y (Enabled)  
SYNC Strbs w/ Sil  
*Disabled  
*Disabled  
Misc. Options 2  
Auto Display Oldest  
Report By  
N (Disabled)  
Zone  
*Zone  
Point  
Alarm Verification Enter time from 1 to  
*60 Seconds  
*Disabled  
time  
250 seconds  
Y (Enabled)  
N (Disabled)  
Plex Door  
DST Start  
Misc. Options 3  
also DST settings  
in Misc. Options  
1, above.  
Select week: 1st,  
Select month  
2nd, 3rd, 4th or Last  
DST End  
Internal Message  
Custom Message  
Edit Banner  
Edit Line 1  
Edit Line 2  
No  
Section 7.8  
Section 7.9  
JumpStart  
AutoPrg  
Yes  
Computer Account  
#
*5820  
*0  
Computer  
Account  
Computer Access  
Code  
Computer Phone # Up to 40 digits  
151209  
6-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Menu  
Options/Defaults  
Comments  
Edit Name  
Edit Access Code  
System Reset  
System Silence  
System Event Ack.  
Fire Drill Key  
System Tests  
Fire Drill Menu  
Indicator Test  
Walk Test no-Report  
Walk Test w/Report  
Dialer Test  
Profile 1 is the profile that dictates  
what functions the Firefighter Key  
has access to. Because this is the  
profile for a key the user name  
and the access code can not be  
edited for this profile.  
Profile 2 is the profile for the  
installer and is referred to as the  
"Installer Code". This profile’s  
user name and panel functions can  
not be edited.  
Clear History Buffer  
Point Functions  
Disable/Enable Point  
Point Status  
Access  
Codes  
Select Profile  
(01 - 20)  
Edit Panel Functions Set SLC Device Address  
SLC Device Locator  
SLC Multi-Device Locator  
I/O Point Control  
Event History  
Set Time & Date  
Printer Options  
Event Logging  
Print Event History  
Print Detector Status  
Print System Config  
Reset Dialer  
Program Menu  
System Information  
Upload/Download  
1. Use of multiple notification groups may not synchronize with each other.  
6-20  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7  
Programming  
This section of the manual describes how to manually program the control panel from the  
built-in annunciator. Each subsection discusses these menu options in detail. All options  
described in this section can be performed using the 5660 Silent Knight Software Suite  
(SKSS).  
Important!  
Before any customized programming is done, JumpStart should be run first. After  
JumpStart is run, thoroughly test the system. The reason the system should be tested  
after JumpStart is because Jumpstart automatically programs the system, searching for  
and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm  
the integrity of the installation prior to performing any custom programming. After  
determining that the hardware is properly installed, custom programming can be  
7.1 UL 864 Programming Requirements  
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND  
OTHER INVOLVED PARTIES: This product incorporates field programmable software. In  
order for the product to comply with the requirements in the Standard for Control Units and  
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be  
limited to specific values or not used at all as indicated below.  
Permitted in  
UL 864 (Y/N)  
Possible  
Settings  
Settings Permitted in  
UL 864  
Programming Option  
Menu Item  
Phone Lines  
Enable Gnd Start  
No  
Yes & No  
No  
Misc Options 1  
Low AC Report Delay  
Yes  
0–30 hours  
1–3  
151209  
7-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
7.2 SLC Family  
The 5820XL supports Hochiki protocol SLC devices or SK series SLC devices. You must  
configure the 5820XL to accept the protocol of the devices you are installing. You cannot mix  
SLC devices of different protocols.  
1. Press or  
to display the main menu.  
2. Enter the installer code if requested.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
0
4. Press to enter module menu.  
5. Press  
6. Press  
to select the desired SLC device type.  
to accept the displayed SLC device type.  
7.3 Modules  
This section lists the options available under the module option in the program menu. The  
following modules are available for the control panel: 5815XL SLC expander, 5860 remote  
fire alarm annunciator, 5824 serial/parallel printer interface module, 5496 intelligent power  
module, 5895XL intelligent power module, 5880 LED I/O module, and 5865 LED  
annunciator.  
7-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Programming  
7.3.1 Edit Modules  
The features that can be edited when this option is selected are module name and class of  
wiring (Class A or Class B), or features that are specific to the module to be edited.  
To edit an existing module:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
1
4. Press to enter module menu.  
1
5. Press to edit a module.  
6. Use the  
or  
arrow to select the module you wish to edit.  
7.3.1.1 Naming Modules  
You can assign an English name to a system hardware module to make it easier to recognize  
on a display.  
7. If you wish to edit the modules name press the  
or  
arrow to select each character  
for the modules name (or press to bypass name edit).  
Press the to move to the next character.  
Figure 7-1 Edit module Name Programming Screen Example  
151209  
7-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
7.3.1.2 Setting the 5815XL Wiring Class  
8. Choose the class of wiring you wish to use for this module by pressing the  
or  
arrow, then press  
.
7.3.2 Adding a Module  
If you need to add a new hardware module to the system, follow these steps.  
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
1
4. Press to enter module menu.  
2
5. Press to add a module.  
6. From the next screen, select the number that corresponds to the type of module you are  
adding from the <New Module Type> screen.  
The screen will display “Adding module [#]...” for a few moments. You will be returned to  
the <New Module Type> screen where you can select another module if desired.  
You must save changes when you exit the Program Menu or the new module will not be  
added.  
Note: If you Add a Module that has not been physically connected, the panel will go into trouble after it  
reinitializes (when you exit the Program Menu). When the new module is attached, the trouble will correct  
itself automatically the next time you power up the system.  
7-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Programming  
7.3.3 Deleting a Module  
If you ever need to delete a module, follow these steps.  
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
1
4. Press to enter module menu.  
3
5. Press to delete a module.  
6. A warning screen will display. If you want to proceed with deleting the module, select  
Yes. To cancel, select No.  
7.4 Zone  
Through the zone option in the program menu you can edit, add, delete, and view zone points.  
Selections made here affect all detectors and switches in the zone. Up to 125 zones can be  
used in the system.  
7.4.1 Edit Zone  
Features that can be edited through the edit zone option are, edit zone name, zone properties  
(which includes, zone type, and detector sensitivity), and zone output mapping.  
To edit a zone, follow these steps:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
2
4. Press to enter zone menu.  
1
5. Press to edit a zone.  
6. Enter the zone number, then press  
.
151209  
7-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
IntelliKnight 5820XL Installation Manual  
7.4.1.1 Edit Zone Name  
1
7. Press to edit the selected zone’s name.  
A screen similar to the one shown in Figure 7-2 displays.  
Figure 7-2 Selecting Character for Zone Name  
8. Select the characters for the zone name by pressing the  
or  
arrow until the desired  
character is shown then press  
OR  
.
Enter the Numerical Designator for the character you want, then press . See Appendix B for  
a list of available characters and their numeric designators.  
9. Repeat step 8 until the name is complete.  
10. Press  
when the name is complete.  
7.4.1.2 Edit Zone Properties  
Zone properties consist of alarm delay characteristics, and heat detector sensitivity.  
2
2. Press to edit the properties of the selected zone.  
Detection type also selected from this screen  
7-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Programming  
Alarm Delay Characteristics  
3. Select the alarm delay characteristics (see Table 7-1) by pressing the  
or  
arrow.  
Table 7-1: Alarm Delay Characteristics  
Type of Delay  
Description  
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device  
of any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is  
considered the most typical operation and is the default for all zones.  
1-Count  
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order  
for the zone to report an alarm. Switches of type manual pull, water flow, Aux1 and Aux2 are an  
exception; they will cause an alarm when only one switch is in alarm.  
2-Count  
When a single detector is in alarm in a 2-Count zone, the system enters a prealarm condition. In a  
prealarm condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has  
occurred. If the zone has been mapped to an output group for the prealarm event, the output group will  
activate. The prealarm will not be reported to the central station.  
Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by  
resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has completed,  
the detector will go into alarm. If the detector is no longer in alarm, no report will go to the central  
station. The alarm verification sequence is ignored if the zone is already in alarm.  
Alarm Ver.  
This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds,  
giving on-site personnel a chance to investigate the alarm. If the acknowledge switch is not activated  
within 15 seconds, an alarm occurs automatically.  
If this option is enabled for a zone, the zone will respond to an alarm condition as follows:  
• The zone will not go into alarm for 15 seconds to allow an on-site operator to activate the acknowl-  
edge switch.  
PAS  
• If the operator does not press the acknowledge switch within 15 seconds, the zone will go into  
alarm.  
• If the operator presses the acknowledge switch within 15 seconds, a 180-second time-frame will  
begin counting down. This time-frame allows the operator to investigate the cause of the alarm.  
If the operator performs a reset within 180 seconds, the alarm will not occur. If the operator does  
not perform a reset within 180 seconds, an alarm will occur automatically.  
• The P.A.S. feature will be overridden if another alarm occurs.  
See Section 8.7.1 for single interlock releasing operation.  
See Section 8.7.2 for double interlock releasing operation.  
SNGL ILOCK  
DBL ILOCK  
4. Press  
.
Heat Temperature Setting  
Use this feature to set the temperature at which heat detectors will respond. The range is 135°  
to 150° F. All detectors in the zone will respond in the same way.  
The Model SD505-AHS Heat Detector is an absolute temperature device. This means that it  
responds to an alarm immediately if the temperature in the zone goes above the programmed  
temperature.  
5. Enter the temperature at which the heat detector will respond.  
Or  
Use the  
on the annunciator, then press  
6. Use the or keys to scroll through the range or enter directly from the number keys  
on the annunciator.  
or  
keys to scroll through the range or enter directly from the number keys  
.
151209  
7-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
7. Then press  
.
7.4.1.3 Zone Outputs  
Output groups and cadence patterns are mapped to events. They can be programmed to output  
when an event occurs in a zone. Some system trouble events can be mapped for the entire  
system. Section 6.2 of this manual contains a general explanation of mapping. The following  
sections explain how to select mapping options.  
Note: Use of multiple notification groups may not synchronize with each other.  
Mapping to Zone Events  
Eight types of events can occur in zones. For each event type, you can activate up to 8 output  
groups or output group template, specifying a pattern for each. The following is a list of all  
event types:  
Note: Abbreviations in the parenthesizes are the characters that are displayed in programming (see  
Manual Pull Alarm (MP)  
Water Flow Alarm (WF)  
Detector Alarm (DE). This applies to heat or smoke detectors.  
Aux 1 and Aux 2 Alarm (A1 or A2). User-specified alarm types.  
Pre-alarm (PR)  
Supervisory (SU)  
Trouble (TR)  
To map zone events to outputs:  
7
1. From the Installer Main Menu, select for Program Menu.  
2
2. From the Program Menu, select for Zone.  
1
3. From the next menu, select for Edit Zone.  
4. Enter the zone number you wish to edit.  
3
5. From the next menu, select for Zone Outputs.  
6. From the next screen, a list of 8 event types will display. Select the event type you want to  
program. A screen similar to the one shown in Figure 7-3 will display. Press  
7. Press the or key to toggle the group letter to either G = Group or T = output group  
template depending on want you need for this zone. Press  
.
.
7-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Programming  
8. Select options for each event that could occur in this zone. Figure 7-3 is a complete exam-  
ple of how you might map a zone.  
Indicates output group 1, cadence  
pattern 00 has been selected. 00 is  
a constant output cadence.  
Indicates type of event (in  
this case, Manual Pull alarm).  
See Section 6.5 for choices.  
“T” Indicates output group  
template 1. See Section 7.5.5 for  
more information on output group  
templates.  
Figure 7-3 Selecting Output Groups/templates and Cadence Patterns for a Zone Event  
Zone Mapping Example  
Suppose you want to program Zone 1 so that:  
Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the  
ANSI cadence pattern.  
Manual pull alarm would activate Output Group 3 using constant output.  
Troubles would activate Output Group 2 using the zone-coded cadence pattern.  
To accomplish this you need to access the screen for each event and then select your output  
151209  
7-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
groups. Figure 7-4 shows how you would program this application.  
Figure 7-4 Zone Mapping Example  
7-10  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Programming  
7.4.1.4 Cadence Patterns  
The cadence patterns shown in Figure 7-5 are available for use with the control panel.  
Cadence patterns can be selected by event type for each zone or for the entire system. Special  
cadence patterns can be selected for fire drills and any auxiliary system switches used with the  
system.  
Figure 7-5 Cadence Patterns Available with the Control Panel  
7.4.1.5 Zone Accessory Options  
This option applies to detectors that are used with SD505-6SB, SD505-6RB, and  
SD505-ADHRs.  
Single or Multi-station cadence pattern (choose from Patterns 00 to 21).  
Local Zone (choose Y or N, for Yes or No).  
151209  
7-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
IntelliKnight 5820XL Installation Manual  
7.4.2 Add Zone  
To add a zone, follow these steps:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
2
4. Press to enter zone menu.  
2
5. Press to add a zone.  
A zone will be added. The system will assign the next available zone number. Options for  
this zone can now be programmed through the Zone Edit sub-menu. Up to 125 zones can  
be used.  
7.4.3 Delete Zone  
To delete a zone, follow these steps:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
2
4. Press to enter zone menu.  
3
5. Press to delete a zone.  
A warning screen will display. If you want to proceed with deleting the zone, select Yes.  
To cancel, select No.  
7-12  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Programming  
7.4.4 View Zone Points  
To view the points in a zone, follow these steps:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
2
4. Press to enter zone menu.  
4
5. Press to view zone points.  
6. Enter the number of the zone you wish to view, then press  
.
Zone Number  
Module or  
Device Address  
Point Number  
Total Number of  
Points in the Zone  
Figure 7-6 View Zone Points Screen  
151209  
7-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
7.5 Group  
An output group is made up of output points that have been programmed to respond in the  
same way. Output groups simplify programming because you have to program the output  
characteristics that are common to all of the group points once, instead of programming each  
individual point. Once you have defined the characteristics of output groups, you can assign  
each point to the appropriate group. All valid output points are assigned to only one output  
group. Unused points are not assigned to any output group. Up to 250 output groups can be  
defined.  
7.5.1 Edit Group  
In the edit group option you can program the name of an output group (Section 7.5.1.1) and  
change the properties (Section 7.5.1.2) of that group.  
To edit a group, follow these steps:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
3
4. Press to enter group menu.  
1
5. Press to edit group.  
6. Enter the number of the group you wish to edit, then press  
.
7.5.1.1 Edit Group Name  
1
7. To edit the group name, press  
.
A screen similar to the one shown in Figure 7-2 displays.  
Figure 7-7 Selecting Character for Zone Name  
7-14  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Programming  
8. Select the characters for the zone name by pressing the  
or  
arrow until the desired  
character is shown then press  
OR  
.
Enter the Numerical Designator for the character you want, then press . See Appendix B  
of this manual for a list of available characters and their numeric designators.  
9. Repeat step 8 until the name is complete.  
10. Press  
when the name is complete.  
7.5.1.2 Edit Group Properties  
The Edit Group Menu allows you to select options for each group for the following items:  
Latching or non-latching outputs.  
Silencing operation.  
Operation with system switches.  
Figure 7-8 Group Properties Screen Programming Options  
Latching / Non-latching Outputs  
Outputs that are programmed as Latching remain active until the system has been manually  
reset. Non-latching outputs stop activating automatically when the condition clears.  
Silencing Options  
The following silencing options are available for each output group.  
Table 7-2: Silencing Options  
Option  
SILENCE  
Description  
SILENCE  
Silenceable. The output group can be silenced through the  
key.  
SILENCE  
NON-SIL  
Not silenceable. The output group cannot be silenced. Activation of the  
ignored for this output group.  
key will be  
151209  
7-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
IntelliKnight 5820XL Installation Manual  
Table 7-2: Silencing Options  
Option  
Description  
AUT UNSIL  
Auto Unsilenced. If this option is selected, the output group can be silenced for a programmed time-  
frame. If the condition that caused the output to activate has not cleared during the time-frame, the  
output reactivates. If you select this option, select the time-frame in the DLY: field. Range is 00-60  
minutes. (See Figure 7-8 for location of field.)  
SIL-INHIB  
Timed Silence after Inhibit. If this option is selected, the output group must be audible for a  
programmed number of minutes before it can be silenced. If the condition that caused the output to  
activate has not cleared during the time-frame, the output can be silenced. If you select this option,  
select the timeframe in the DLY: field. Range is 00-60 minutes. (See Figure 7-8 for location of field.)  
SHUT-DOWN  
If this option is selected, the output group will automatically silence (shut down) after the  
programmed time period. If you select this option, select the timeframe in the DLY: field. Range is  
01-60 minutes. (See Figure 7-8 for location of field.)  
Response with System-Wide Conditions  
You can select whether an output group will respond to various system-wide occurrences.  
Table 7-3: Output Group Response Choices  
Option  
Description  
ManPull  
Manual Pull Activation. Select Yes if you want this group to activate for all manual pull  
alarms that occur in the system.  
Note: Even though manual pull switches are assigned to zones, activation  
selected here for manual pull will override zone-programmed activation.  
Fire Drill  
Fire Drill Activation. Select Yes if you want this group to activate for fire drills.  
Sys Aux1 and Sys Aux2  
Ignore Global Cad  
Select Yes if you want this output group to activate for system-wide Aux1 and Aux2  
alarms.  
(Aux 1 and Aux 2 alarm types are for auxiliary alarm conditions. For example, you  
might want to use Aux 1 to provide a unique alarm type.)  
Ignore Global Cadence. If you want to create an output group that can never be  
overridden, you can select Yes for this option. Selecting No means that system-wide  
events that have been assigned an output pattern could override the pattern for the  
output group.  
For example, suppose you had assigned a set of strobes to Output Group 3. You would  
never want these strobes to output in a pattern under any circumstances. To make sure  
this happens, select Yes for Ignore Global Cadence for Output Group 3.  
Reverse Polarity  
This option programs the output group for reverse polarity operation. Selecting Reverse  
Polarity–Troubles will cause the output group to be de-energized for any system  
trouble. Selecting Reverse Polarity–No Troubles will cause system troubles to be  
ignored. Activation is accomplished through standard mapping methods. Use with the  
7644 assembly to implement reverse polarity. See Section 4.15.3.2 for more  
information on the 7644.  
11. To get to this menu item repeat steps 1 through 6 of Section 7.5.1.  
2
12. To edit group properties, press  
.
13. Press the  
or  
or  
arrows to select the desired latching option.  
14. Press  
.
15. Press the  
7-16  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Programming  
16. Press  
.
select Y (yes) or N (no).  
or  
arrows to  
18. Press  
.
19. Repeat steps 14 and 15 for all the activation options.  
7.5.2 Add Group  
To add a group:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
3
4. Press to enter group menu.  
2
5. Press to add a group.  
The system will assign the next available group number. Properties for the new group can  
now be edited if desired (see Section 7.5.1.2). A total of 250 output groups can be defined.  
7.5.3 Delete Group  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
3
4. Press to enter group menu.  
3
5. Press to delete a group.  
A warning screen will display. If you want to proceed with deleting the group, select Yes.  
To cancel, select No.  
151209  
7-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
7.5.4 View Group Points  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
3
4. Press to enter group menu.  
4
5. Press to view group points.  
6. Enter the group number, then press  
.
7.5.5 Edit Output Group Templates  
Some installations may require that zones be mapped to more than 8 output groups. With  
output group templates you can combine one or all output groups into one template, which can  
be used when the same combination of outputs are used for several zones.  
For example, lets say an installation has five zones (See Table 7-4). The check mark indicates  
what output groups are mapped to each zone. You will notice that every zone is mapped to  
outputs 1 and 2. As an alternative you can create a template that combines output group 1 and  
2 as one choice.  
Table 7-4: Zone Group Example  
Group Number  
Zone  
1
2
3
4
5
6
7
8
1st Floor Smoke Detectors  
2nd Floor Smoke Detectors  
3rd Floor smoke Detectors  
Manual Fire Pull Stations  
Water Flow Switches  
This can be done by creating a template which includes output groups 1 and 2. Then you can  
map all the zones to the template you created. This will free up output group assignments that  
are common to several zones. This is very useful when you need to map zones to more than  
7-18  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Programming  
eight output groups.  
To create Output Group Templates:  
7
1. From the Main Menu, select for Program Menu.  
3
2. From the Program Menu, select for Group.  
5
3. At the next screen, select for Edit OPG Template.  
4. Select the template number (01 - 08).  
5. Select output group number. See Figure 7-9.  
Yes = Include the selected  
output group in this template  
Output  
Group #  
No = Do Not include output  
group in this template  
Select the  
Cadence Pattern  
Figure 7-9 Output Group Template Programming Screen  
7.6 Point  
You may need to change characteristics of individual input points (detectors and switches)  
even after using JumpStart. This section explains how to change options for: type of input  
point; latching/non-latching status (switches); and name and zone assignment of a point.  
7.6.1 Point Programming For 5815XL Module  
To program for an 5815XL Module points, follow these steps:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
4
4. Press to enter point menu.  
5. Press the  
or  
arrows to select the desired module. Refer to Section 6.5 Quick Refer-  
ence Table for available choices.  
6. Press  
.
7. Enter the number of the point you wish to edit.  
151209  
7-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
IntelliKnight 5820XL Installation Manual  
8. Press  
.
9. Select the type of device by pressing the or  
umn heading “Type Selection” for a list of choices.  
Table 7-5: Point Programming Options for 5815XL Modules  
Type  
Selection  
Latching  
Option  
Function  
Comments  
UNUSED  
PHOTO  
ION  
HEAT  
PHOT DUCT  
ION DUCT  
2WIRE SMK  
SUP PHOTO  
SUP ION  
DETECTOR  
SUP DET  
Latching  
Non Latching  
7-20  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Programming  
Table 7-5: Point Programming Options for 5815XL Modules  
Latching  
Type  
Selection  
Function  
Comments  
Option  
Use this switch type for manual pull stations. This input is always latched.  
The switch can clear only when an alarm is reset. This switch type has the  
highest priority; it overrides any other type of alarm.  
MAN_PULL  
Latching  
Use this switch type for monitoring water flow in a sprinkler system. Switch  
closure will cause a sprinkler alarm. Water flow switches can be  
programmed as latching or non-latching.  
You can program a delay of up to 90 seconds to be used with a water flow  
switch. The delay allows for normal, brief changes in sprinkler system water  
pressure. The water flow alarm will not activate unless the switch is active  
for the programmed delay time.  
WATERFLOW  
Non Latching  
If a delay is used, the system begins counting down when the switch closes.  
If the switch opens (restores) before the timer expires, a water flow alarm is  
not generated. If the water flow switch remains closed after the timer  
expires, a water flow alarm will be generated.  
Latching  
Use this switch type for tamper monitoring of sprinklers and other fire  
protection devices. If a contact closes, a sprinkler supervisory event will be  
generated. Supervisory switches can be latching or non-latching.  
SUPERVISY  
FIREDRILL  
Non Latching  
SWITCH  
System-level, non latching switch. This switch is an alternative way of  
causing a fire drill. It has the same operation as the fire drill option available  
from the annunciator. When the switch is activated, a fire drill begins; when  
the switch is de-activated, the fire drill ends.  
This system-level switch is an alternative way to silence the system. It has  
SILENCE  
RESET  
SILENCE  
the same effect as pressing the  
This system-level switch is an alternative way to reset the system. It has the  
RESET  
key.  
same effect as pressing the  
key.  
Positive acknowledge switch. This switch must be used in zones  
programmed as Positive Alarm Sequence (see Table 7-1).  
If an acknowledge switch closes when an alarm or trouble condition is not  
already in progress, a trouble will occur.  
PAS_ACK  
You must use a UL listed normally open, momentary switch type. The  
switch must be rated at 5V, 100 mA (minimum) and be used with an EOL  
resistor for supervision.  
151209  
7-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Table 7-5: Point Programming Options for 5815XL Modules  
Type  
Selection  
Latching  
Option  
Function  
Comments  
Latching  
Use these switch types if you want to monitor special zone-level conditions  
(such as operation of a fan or damper).  
ZN_AUX1  
ZN_AUX2  
SYS_AUX1  
SYS_AUX2  
DETECT SW  
TAMPER  
Non Latching  
Latching  
Non Latching  
Latching  
Use these switch types if you want to monitor special system-wide  
conditions (such as operation of a fan or damper).  
Non Latching  
Latching  
SWITCH  
(cont.)  
Non Latching  
Used to monitor conventional 4-wire detectors, a contact closure will  
generate a detector alarm event.  
Latching  
Performs identically to a supervisory switch, but will be indicated as a  
tamper switch on the LCD annunciator.  
Non Latching  
Latching  
Manual release switch, typically a pull station.  
MAN REL  
Non Latching  
Latching  
Interlock release switch input.  
ILOCK  
Non Latching  
Output Point, a general use notification type. Use for driving standard  
notification appliances.  
OUTPUT PT  
AUX CONST  
AUX RESET  
Select Group  
Use constant power for applications that require a constant auxiliary power  
source. Power is always present at Constant circuits.  
NOTIF  
Use for auxiliary power, resettable applications. See Section 4.13.5.3 for a  
description of how this option operates.  
Use for auxiliary power, door holder applications. For example, if you were  
using an auxiliary power supply for door holders, you would use this option.  
See Section 4.13.5.1 for a description of how this option operates.  
AUX DOOR  
Output Point, a general use relay type. Use for applications requiring a relay,  
such as fan shutdown, elevator recall, and so on.  
OUTPUT PT  
AUX RESET  
Select Group  
Select Group  
Use for auxiliary power, resettable applications. See Section 4.13.5.3 for a  
description of how this option operates.  
RELAY  
Use for auxiliary power, door holder applications. For example, if you were  
using an auxiliary power supply for door holders, you would use this option.  
See Section 4.13.5.1 for a description of how this option operates.  
AUX DOOR  
Select Group  
7-22  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming  
Table 7-5: Point Programming Options for 5815XL Modules  
Latching  
Type  
Selection  
Function  
Comments  
Option  
Select LED No.  
01 -80  
SLC LED  
Select Group  
151209  
7-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
7.6.2 Point Programming For Internal or External Power  
Module (5895XL)  
To program for an internal or external power module points:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
4
4. Press to enter point menu.  
5. Press the  
choices.  
or  
arrows to select the desired module. Refer to Section 6.5 for available  
6. Press  
.
7. Enter the number of the circuit or point you wish to edit. Refer to Table 7-6 for available  
selections.  
8. Press  
.
9. Select the type by pressing the  
or  
arrows.  
10. Press  
.
11. Select the function by pressing the  
or  
arrows.  
12. Press  
.
13. Select the zone by pressing the  
or  
arrows.  
14. Press  
.
7-24  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Programming  
Or  
Press to skip point name edit.  
16. Repeat Steps 1 through 15 for all circuits.  
Table 7-6: Menu choices for Internal/External Power Module  
Function  
Selections for  
each Type  
Choices  
Type Selections  
Comments  
Enter Point or Circuit  
UNUSED  
B NOTIF  
A NOTIF  
CONSTANT  
RESETTABLE  
DOOR  
Constant auxiliary power.  
Resettable auxiliary power.  
Door holder auxiliary power.  
Refer to comments column of  
AUX PWR  
MAN PULL  
WATERFLOW  
SUPERVSY  
TAMPER  
Table 7-5 for description of these  
options.  
Latch or Non-latching feature only  
appears for waterflow, supervisory,  
tamper, zone aux1, zone aux2, system  
aux1, and system aux2.  
FIREDRILL  
SILENCE  
Select Type  
RESET  
B SWITCH  
PAS_ACK  
ZN_AUX1  
ZN_AUX2  
SYS_AUX1  
SYS_AUX2  
MAN REL  
ILOCK  
A SWITCH  
Same as B SWITCH Used for  
2-WIRE SMK  
4-WIRE SMK  
2-WIRE SMK  
4-WIRE SMK  
Used for Class B, 2-wire detectors.  
B DETECTOR  
Used for Class B, 4-wire detectors.  
Used for Class A, 2-wire detectors.  
Used for Class A, 4-wire detectors.  
A DETECTOR  
Select Zone/Group  
Edit Name  
Group or Zone selection will appear  
depending on the type selected.  
See Section 7.3.1.1.  
151209  
7-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
7.6.3 Point Programming For 5880 and 5865 Modules  
To program 5880 or 5865 module points:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
4
4. Press to enter point menu.  
5. Press the  
choices.  
or  
arrows to select the desired module. Refer to Section 6.5 for available  
6. Press  
.
Figure 7-10 Programming Points Screen for 5880 and 5865 Modules  
7. Enter the point number.  
8. Press  
.
.
.
9. Press the  
or  
or  
arrows to select the type (Notification or unused).  
arrows to select the desired Group.  
10. Press  
11. Press the  
12. Press  
Or  
Press to skip module name edit.  
7-26  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Programming  
14. Repeat Steps 1 through 13 for all points.  
7.6.3.1 Assigning a Name to Points  
You can assign a name to a point to make it easier to recognize on a display.  
To edit a point name:  
2. Using the  
or  
arrow, select the module of the point you want to edit, press  
.
3. Enter the point number.  
4. Press until the module name is blinking.  
5. Press  
.
A screen similar to the one shown in Figure 7-2 displays.  
Figure 7-11 Selecting Character for Zone Name  
6. Select the characters for the point name by pressing the  
or  
arrow until the desired  
character is shown then press  
OR  
.
Enter the Numerical Designator for the character you want, then press . See Appendix B  
for a list of available characters and their numeric designators.  
7. Repeat step 6 until the name is complete.  
8. Press  
when the name is complete.  
7.7 System Options  
This section of the manual explains how to customize software options that affect general  
operation of the system. This includes such items as: AC loss hours, system clock options,  
holidays schedule, telephone and reporting account options. Refer to each individual  
subsection for complete instructions.  
151209  
7-27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
7.7.1 Reporting Account  
Up to four reporting accounts can be used with the control panel. Events in accounts are  
reported by zone.  
Each account is assigned an up-to-6-digit account number. Each account is also assigned a  
unique ID (1-4) which determines the priority for reporting ("1" has the highest priority; "4"  
has the lowest).  
Disable any unused accounts by selecting “N” for all events (see Figure 7-12). If the system is  
local only (does not connect to a central station), disable all events for all four reporting  
accounts.  
Options for each account can be customized. These options appear on the Reporting Accounts  
screen. Some related options appear on the Phone Lines screen (see Section 7.7.2).  
To access the Reporting Accounts screen:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
3. Select for Program Menu.  
Display reads: Initializing  
7
Please wait . . .  
5
4. From the Program Menu, select for System Options.  
0
5. From the next menu, select for Reporting Accounts.  
7-28  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Programming  
7.7.1.1 Edit Accounts  
1
6. From the next menu, select for Edit Account.  
A screen similar to one shown in Figure 7-12 will display. The following subsections  
describe the options on each field.  
Figure 7-12 Reporting Account Editing Screen  
Select Account (ID)  
The control panel provides up to 4 reporting accounts. The priority of an account is based on  
its account ID. Account 1 is highest priority; Account 4 is lowest. Use Account 1 to report the  
highest priority events.  
7. Press the  
or  
arrow to select account ID number, then press  
.
Edit Account Number  
Enter an up-to-6-digit number for each account to identify the account to the central station.  
See Figure 7-12 for location of this option on the screen. The account number should be  
compatible with the reporting format used. For example, the Contact ID format transmits up  
to four digits only.  
8. Enter the desired account number (up to 6-digits), then press  
.
Select Reporting Format  
Select a reporting format for each account. Options are:  
SIA  
CID  
S20  
SIA format. 8 events per call.  
Ademco’s Contact ID format  
Same as SIA but limits events reported to 20 events per phone call.  
9. Press the  
or  
arrow to select the reporting format, then press  
.
151209  
7-29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
IntelliKnight 5820XL Installation Manual  
Events to Report  
The next six options select which types of events (or event families) will be reported to this  
account. (See Figure 7-12 for location of these options on the screen.) Events are reported by  
zone.  
Event Family  
Events Included in this Family  
Alarms  
All alarms (Water Flow, Manual Pull, Detectors, Auxiliary Switches)  
All alarm restores.  
Alarm Restore  
Supervisory/Trouble  
Enable/Disable Point  
Service/Test  
All trouble and supervisory conditions and trouble and supervisory restores.  
Enabling and disabling of input and output points.  
Fire drill, walk test, dialer test, automatic test, all programming sessions.  
All system resets.  
System Reset  
10. Press the  
or  
arrow to select Must, Yes, or No (see table below), then press  
.
11. Repeat step 10 for all six event report options.  
For each event family, select M, Y, or N.  
M(ust)  
Must Report. Selecting "M" makes this a primary reporting account for this family of events. The dialer  
MUST report events in this family to this account.  
Selecting Must makes an account a primary reporting account. The dialer will try to report the event to  
the primary account until it exceeds the "Switch Attempts" value. When the dialer has exceeded the  
Switch Attempt retry limit, it will switch to a backup account (a "Can Report" or "Yes" account, see  
below). If the dialer cannot report the event to any of the backup accounts, it will return to the primary  
account and repeat the process until it exceeds the "Fail Attempts" value. If the Fail Attempts limit is  
exceeded, an Account Trouble condition is generated and a local trouble will sound.  
Y(es)  
N(o)  
Can Report. Selecting Y makes this a backup account for this event family. The dialer will report to this  
account only if it was previously unable to report the event to a Must account.  
No events in this family will ever be reported to this account.  
Switch Attempts  
Specify the number of times the dialer should attempt to report to this account before  
switching to the next account. Range is 01-15.  
12. Enter the number of switch attempts (or press the  
or  
arrow), then press  
.
Fail Attempts  
This feature specifies the number of times the dialer should attempt to perform the dial/switch  
sequence before issuing an account trouble condition. Range is 01 - 15 (Default = 10).  
13. Enter the number of fail attempts (or press the  
or  
arrow), then press  
.
Selecting Primary and Secondary Phone Lines  
For each account, select which phone line (Line 1 or Line 2) is primary. See Figure 7-12 for an  
example of how to make this selection.  
14. Press the  
or  
arrow to select line 1 or 2 as primary phone line, then press  
.
7-30  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Programming  
15. Repeat step 14 for the secondary phone line.  
Telephone Number  
Enter up to 40 characters for phone number for this account.  
The following special characters are available:  
Table 7-7: Special Character for Dialing  
#
*
,
Pound (or number) key on the telephone  
Star key on the telephone  
Comma (character for 2-second pause)  
Use the number buttons on the annunciator or the up- and down-arrow keys to select special  
characters. Characters begin displaying after “9”. See Figure 7-12 for an example.  
151209  
7-31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
7.7.1.2 Auto Test Time  
To access the automatic dialer test time screen:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
3. Select for Program Menu.  
Display reads: Initializing  
7
Please wait . . .  
5
4. From the Program Menu, select for System Options.  
0
5. From the next menu, select for Reporting Account.  
2
6. From the next menu, select for auto test time.  
7. Enter the hour you desire the control panel to send an automatic test report (or press the  
or  
arrow), then press  
.
8. Enter the minutes (or press the  
9. Select AM or PM by pressing the  
or  
arrow), then press  
arrow, then press  
.
or  
.
7.7.2 Phone Lines  
To access the phone lines screen:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
3. Select for Program Menu.  
Display reads: Initializing  
Please wait . . .  
7
5
4. From the Program Menu, select for System Options.  
1
5. Select for the phone lines menu.  
7-32  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Programming  
6. Select the phone line to be edited (1 or 2) by pressing the  
or  
arrow, then press  
.
Figure 7-13 Phone Lines Editing Screen  
7.7.2.1 Dialing Prefix  
Enter up to 8 characters to be used for such things as PBX dial-out codes, a pause, and so on.  
The following special characters are available:  
#
*
,
Pound (or number) key on the telephone  
Star key on the telephone  
Comma (character for 2-second pause)  
Use the number buttons on the annunciator or the up- and down-arrow keys to select special  
characters. Characters begin displaying after “9”. See Figure 7-13 for an example.  
7. Enter a dialing prefix (if needed), then press  
Or  
.
Press to bypass the dialing prefix option.  
151209  
7-33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
7.7.2.2 Number of Answer Rings  
This option is used in conjunction with the 5660 SKSS. Use the option to determine the  
number of rings before the panel answers a call from the computer. Range is 00-15 rings. This  
option is factory-programmed as 06 rings, which should be compatible for most installations  
where the answering machine bypass feature is used. You may need to adjust it depending on  
the installation’s telephone system.  
The selection made here must match the programming for this option in the Communication  
Configuration dialog box of the 5660 SKSS. See the software manual for more information  
(PN 151240).  
8. Enter the desired number of answer rings, then press  
.
7.7.2.3 Dial Option (TouchTone or Pulse)  
9. Press the  
or  
arrow to select the dial option, then press  
.
Dial Option  
Description  
PULSE  
TT  
If this option is selected, only pulse dialing will be used for this phone line.  
TouchTone dialing. If this option is selected, only TouchTone dialing will be used for this  
phone line.  
TouchTone alternating with pulse. If this option is selected, the dialer will first attempt to  
use TouchTone. It will switch to pulse if TouchTone is not successful on the first attempt.  
It will continue to alternate between TT and pulse for additional attempts.  
TT/PL  
7.7.2.4 Rotary Format  
10. Press the  
.
or  
arrow to select the pulse ratio for rotary dialing option, then press  
Options are:  
U
E
U.S. standard format. Uses the 60 msec / 40 msec make/break ratio.  
European format. Uses the 66 msec / 34 msec make/break ratio.  
7.7.2.5 Line Monitor  
Enable the line monitor for each phone line that will be used. See Figure 7-13 for location of  
this field on the phone lines screen. When the phone line monitor has been enabled for a  
phone line, a trouble condition will occur if the line is not connected. If a phone line will not  
be used, it must be disabled.  
11. Select Y (monitor line) or N (don’t monitor line) by pressing the  
press  
or  
arrow, then  
.
7.7.2.6 Ground Start Relay  
If using the 5211 ground start relay, you must enable the ground start relay programming  
option. See Figure 7-13 for the location of this field on the phone lines screen. This option is  
7-34  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                   
Programming  
disabled by default. For 5211 installation, see Section 4.12.  
Note: Ground start cannot be used in UL installations.  
12. Select Y (ground start used monitor line) or N (ground start not used don’t monitor line)  
by pressing the or arrow, then press  
.
7.7.2.7 Answering Machine Bypass  
This option is used in conjunction with the 5660 SKSS. This feature ensures that an answering  
machine will not interfere with communication between the panel and the computer. If an  
answering machine is used at the panel site, enable this feature; if an answering machine is not  
used, disable the feature.  
This option is factory-programmed as Yes (enabled).  
The selection made here must match the programming for this option in the Communication  
Configuration dialog box of the 5660 SKSS. See the 5660 SKSS manual for more information  
(PN 151240).  
13. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled)  
by pressing the  
or  
arrow, then press  
.
7.7.3 Sys. Event Outputs  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
3. Select for Program Menu.  
Display reads: Initializing  
7
Please wait . . .  
5
4. From the Program Menu, select for System Options.  
2
5. From the System Options Menu, select for Sys. Event Outputs.  
151209  
7-35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
7.7.3.1 Trouble Events  
You can map certain system trouble events to an output group. To access the screen for  
selecting output groups and cadence patterns for system trouble events.  
1
6. Press for Trouble Events. A screen similar to the one in Figure 7-14 will display. Select  
a group and a cadence pattern for each event as needed for your application. The U: field  
is for a user-specified trouble condition. You can program an output group and cadence  
pattern for any of the following events:  
Battery  
Low battery condition.  
Gnd Flt  
Ground fault.  
Phone Ln  
Account  
Printer  
Phone Line 1 or 2 trouble.  
Account trouble; cannot report to account.  
Printer trouble. (Currently not supported; do not select.)  
Auxiliary power trouble.  
Aux Pwr  
Sys Sw  
Trouble with a system switch.  
Trouble with an output group.  
SBUS communication trouble.  
SBUS power trouble.  
Group Tr  
SBUS Com  
SBUS Pwr  
SLC Loop  
AC Loss  
Trouble on the SLC loop.  
AC power lost.  
Figure 7-14 System Trouble Event Mapping Example  
7-36  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Programming  
7.7.3.2 System Alarm Cadence  
Fire drill and system auxiliary alarm events can have special cadence patterns to distinguish  
them from other types of alarms. See Section 7.4.1.4 for available cadence patterns.  
A typical use of the System Aux1 and Aux2 patterns is to distinguish fire emergencies from  
other types of emergencies. The System Aux1 and Aux2 alarms would be triggered by a  
system-wide switch.  
To access the screen for selecting output groups and cadence patterns for system trouble  
events:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
3. Select for Program Menu.  
Display reads: Initializing  
7
Please wait . . .  
5
4. From the Program Menu, select for System Options.  
2
5. From the System Options Menu, select for Sys. Event Outputs.  
2
6. Press for System Alarm Cadence.  
A screen similar to the one in Figure 7-15 will display. Select a cadence pattern for these  
special events if required for your application.  
Figure 7-15 Special Cadence Patterns for Fire Drill and Auxiliary Alarm Events  
151209  
7-37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
7.7.4 Miscellaneous Options 1  
Through this programming option you can set the water flow delay time, low AC report delay,  
enable or disable automatic daylight savings time adjustment, clock format, and AC clock  
frequency.  
7.7.4.1 Water Flow Delay  
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction  
with a water flow switch. The delay is system-wide. All water flow switches on the system  
will use the same delay period.  
To access the screen for programming water flow delay, follow these steps:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
5
4. Select for System Options.  
5
5. Select for Miscellaneous Options 1.  
A screen similar to the one shown in Figure 7-16 will display.  
Delay in seconds  
before waterflow  
alarm occurs.  
(00 - 90)  
Figure 7-16 Water Flow Delay Programming Screen  
7-38  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Programming  
6. Enter the number of seconds (0 to 90 ) to delay an a water flow switch alarm, then press  
.
151209  
7-39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
7.7.4.2 Low AC Report Delay  
Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations.  
You can adjust the number of hours before a Low AC report will be sent to the central station.  
To program low AC report delay, follow these steps:  
Note: Steps continued from step 6 of Section 7.7.4.1.  
Low AC Report  
Delay in Hours  
(00 - 30)  
Figure 7-17 Low AC Report Delay Programming Screen  
7. Enter the number of hours before a low AC report will be sent to the central station, then  
press  
7.7.4.3 Automatic Daylight Savings Adjustment  
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. Before  
January 2007, if this feature is enabled (set to Yes), the system clock will switch to DST on the  
first Sunday in April at 2:00 a.m. and revert to standard time on the last Sunday in October at  
2:00 a.m. After January 2007, if this feature is enabled, the system clock will start and end  
DST according to the settings made in Misc. Options 3 (see Section 7.7.6.3). If this feature is  
not enabled (set to No) the Daylight Saving Time change is not made to the system clock.  
To enable or disable DST adjustment continue programming form step 7 above:  
8. Select Y (enabled) or N (disabled) by pressing the  
or  
arrow, then press  
.
7.7.4.4 Clock Display Format (AM/PM or Military)  
To change the system clock display format, continue programming from step 8 above:  
9. Select AMPM (for AM/Pm display format) or MIL (for military or 24 hr display format)  
by pressing the or arrow, then press  
.
7.7.4.5 Change AC Line Frequency  
The panel’s AC line frequency is selectable for 50, 60 Hz, or Neither. AC Frequency feature  
dictates how the control panel will calculate time based on the AC line frequency used in the  
installation site. The "Neither" option can be used in areas where the AC line frequency is not  
dependable and you want the panel to calculate time from the internal crystal. The internal  
crystal is not as accurate as the AC power source and either 60 Hz or 50 Hz should normally  
selected. The panel defaults to the 60 Hz. selection  
To change the AC line frequency, continue programming from step 9 above:  
10. Select 50, 60 or Neither, by pressing the  
or  
arrow, then press  
.
7-40  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                 
Programming  
7.7.5 Miscellaneous Options 2  
Through this programming option you can turn the strobe synchronization during silence  
feature On or Off, and select the control panel to report events by zone or by point.  
To edit miscellaneous options 2:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
5
4. Select for System Options.  
6
5. Select for Miscellaneous Options 2.  
7.7.5.1 Synchronize Strobes Active During Silence  
When "SYNC Strbs w/ Sil:" is Selected as Y (Yes) then strobes will continue to flash when the  
system is silenced and will stop flashing when the system is reset.  
Note: The "SYNC Strbs w/ Sil:" only functions with outputs that use a synchronized output pattern.  
6. Press the  
7. Press  
or  
arrow to toggle this selection between Y (Yes) or N (No).  
or  
to make your selection and move to the next programming option.  
Note: See Section 7.4.1.4 for more information about Synchronization protocol choices.  
7.7.5.2 Auto Display Oldest Event  
When this feature is programmed Y (Yes) then the oldest un-acknowledge event will  
automatically display on the control panel and remote annunciators after there has been no  
activity on any system touchpad for two minutes.  
8. Press the  
9. Press  
or  
arrow to toggle this selection between Y (Yes) or N (No).  
or  
to make your selection and move to the next programming option.  
7.7.5.3 Report by Zone or by Point  
When the "Report by" option is set to Zone, then the control panel will report events by zone.  
If Point is selected then the control panel will report events by point.  
10. Press the  
or  
arrow to toggle this selection between Zone or Point.  
11. Then press  
or  
151209  
7-41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
IntelliKnight 5820XL Installation Manual  
7.7.6 Miscellaneous Options 3  
From Miscellaneous Options 3, you set the alarm verification time, turn the Plex Door option  
on/off, and set the start and end week and month of Daylight Saving Time.  
To edit Miscellaneous Options 3:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
4. Enter code if prompted.  
Display reads:  
Initializing  
Please wait . . .  
5
5. Select for System Options.  
7
6. Select for Miscellaneous Options 3.  
7.7.6.1 Alarm Verification Time  
You can set the alarm verification time from 1 to 250 seconds (default is 60 seconds).  
To set the alarm verification:  
7. Enter the desired number of seconds for the alarm verification time.  
8. Press  
or  
to make your selection and move to the next programming option.  
7.7.6.2 Plex Door Option  
If installing the plex door hardware (PN Plex-1), you must turn the Plex Door option On as  
described in this section.  
To turn the Plex Door option on/off:  
9. Press the  
or  
arrow to toggle this selection between Y (Yes) or N (No).  
10. Press  
or  
to make your selection and move to the next programming option.  
7-42  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Programming  
7.7.6.3 Daylight Saving Time Start and End  
This option lets you to adjust the week and month Daylight Saving Time (DST) starts and  
ends. For this feature to work, you must enable (set to Yes) the DST option under Misc.  
Options 1 (see Section 7.7.6.3). You can view and change the settings in this option anytime,  
however, settings will not take effect until 2007. The default values for the DST Start and End  
options reflect the August 8, 2005 DST law that goes into effect in 2007:  
DST Start: The second Sunday in March  
DST End: The first Sunday in November  
To set the start and end for Daylight Saving Time:  
11. Press the  
then press  
or  
arrow to select the week (1st, 2nd, etc.) Daylight Saving Time starts,  
to make your selection and move to the month setting.  
12. Press the  
or  
arrow to select the month (January – December) Daylight Saving Time  
starts, then press  
to make your selection and move to the DST End option.  
13. Press the  
or  
arrow to select the week (1st, 2nd, etc.) Daylight Saving Time ends,  
to make your selection and move to the month setting.  
then press  
14. Press the  
or  
arrow to select the month (January – December) Daylight Saving Time  
two times to make your selection and exit Misc. Options 3.  
ends, then press  
151209  
7-43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
7.7.7 Edit Banner Message  
The banner is the message that displays on the panel LCD when the system is normal, that is,  
when no alarms or troubles exist and no one is currently using system menus. You can create a  
customized message, which can be up to 40 characters, two lines of 20 characters each.  
If you do not create a customized message, the system will use the internal banner. You cannot  
change the internal banner.  
To customizing the banner display message:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
5
4. Select for System Options.  
8
5. Select for Edit Banner. A screen similar to the one shown in Figure 7-18 will display.  
Figure 7-18 Internal Banner Message  
6. Press the  
or  
arrow to select “Custom”, then press  
. A screen similar to the one  
Figure 7-19 Custom Banner Edit Screen  
7. Select each letter by pressing the  
acter.  
or  
arrow, then press  
to move to the next char-  
8. When done, press  
to move to line two of the custom banner. Repeat step 7 and 8.  
7-44  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Programming  
7.8 JumpStart Autoprogramming  
IMPORTANT!  
JumpStart is intended to be used prior to performing any custom programming. Each time  
JumpStart is executed, all options will be reset to their default values. Do not run  
JumpStart after you have configured the system through programming.  
To run JumpStart:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
6
4. Select for System Options.  
5. Press the  
6. Press  
or  
arrow to select "Yes" from the warning screen.  
.
151209  
7-45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
7.9 Computer Account  
An installer at the panel site can initiate communications between the panel and a computer  
running the 5660 SKSS (see also Section 8.5.16). In order for this communication to function  
properly both the computer (running the software) and the control panel must have matching  
computer account numbers and computer access codes.  
Before you program in this location you should know how your control panel will  
communicate with the downloading computer, either through direct connect (RS232) or via  
the phone lines (Internal Modem).  
If the panel initiates the call to a downloading computer, a phone number must be  
programmed in the computer accounts area. If the computer initiates the call, answering  
To program computer account information:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
7
3. Select for Program Menu.  
Display reads:  
Initializing  
Please wait . . .  
7
4. Select for System Options.  
5. Enter the computer account number, then press  
6. Enter the computer code (up to 7-digits), then press  
.
.
7. Enter the phone number the panel will dial to connect to a downloading computer (up to  
40-digits), then press . See Table 7-7 for special dialing characters.  
7-46  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Programming  
7.10 Access Codes  
Access codes provide the user access to the control panel functions. Each access code can be  
customized for each user. This allows some users the ability to access programming and other  
higher level panel functions, while other users may only need access to lower level functions  
such as preforming fire drills, or acknowledging trouble conditions.  
Profile 1 is the profile that dictates what functions the Fire Fighter Key has access to. Because  
this is the profile for a key the user name and the access code can not be edited for this profile.  
Profile 2 is the profile for the installer and is referred to as the "Installer Code". This profile’s  
user name and panel functions can not be edited.  
Table 7-8 lists the panel functions that can be selected for each user profile.  
Table 7-8: User Profile Selectable Panel Functions  
Type of Function  
Selectable Functions  
System Reset  
System Silence  
System Event Acknowledge  
Fire Drill Key  
Panel Operations  
System Test  
Fire Drill Menu  
Indicator Test  
Walk Test no Report  
Walk Test with Report  
Dialer Test  
Clear History Buffer  
Point Functions  
Disable/Enable Point  
Point Status  
Set SLC Device Address  
SLC Device Locator  
SLC Mult-Device Locator  
I/O Point Control  
Event History  
Panel Menus  
Set Time & Date  
Printer Options  
Event Logging  
Print Event History  
Print Detector Status  
Print System Configuration  
Reset Dialer  
Program Menu  
System Information  
Upload/Download  
To change an access code:  
1. Enter the installer code.  
2. Press  
or  
to display the main menu.  
3. Select for Program Menu.  
Display reads: Initializing  
7
151209  
7-47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
Please wait . . .  
4. Select for System Options.  
Display reads: Select Profile 01  
Fire Fighter’s Key  
8
5. Select the access code you wish to edit by pressing the  
6. Then press  
or  
arrow.  
.
7.10.1 Profile Edit Menu  
From the Profile Edit Menu you can change the users name, access code, and the panel  
functions that the user will have access to with their code.  
Note: Profile 1 (Fire Fighter’s Key) the user name and access code can not be edited. Profile 2 (Installer) the  
user name and panel functions can not be edited.  
7.10.1.1 Edit Name  
7. Select each character of a word by pressing the  
the next character.  
or  
arrow, then press  
to move to  
8. Repeat step 7 until user name is complete.  
9. Then press  
to finish.  
7.10.1.2 Edit Access Code  
10. Enter new access code (minimum of 4 digits, maximum of 7 digit)  
11. Press  
.
12. Enter code again.  
13. Press  
.
7.10.1.3 Panel Functions  
14. Press the  
15. Then press  
16. Press the  
or  
arrow to move through the list of available functions.  
to move to Y (yes) or N (no) selection column.  
or arrow to select Y or N.  
17. Press  
.
18. Repeat steps 14 through 17 until user profile is complete.  
7-48  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Section 8  
System Operation  
Operation of the control panel is simple. Menus guide you step-by-step through operations.  
This section of the manual is an overview of the operation menus. Please read this entire  
section carefully before operating the panel.  
Press  
to view Main Menu: Select the desired menu option. Enter your access code if  
prompted.  
Note: See Section 7.10 for information on how to modify user access code profiles.  
8.1 User and Installer Default Codes  
User Code (factory-programmed as 1111).  
Installer Code (factory-programmed as 5820).  
8.2 Annunciator Description  
Figure 8-1shows the annunciator that is part of the control panel board assembly.  
Figure 8-1 Control Panel Annunciator  
151209  
8-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
8.2.1 LCD Displays  
The control panel LCD displays system messages, annunciates alarms, supervisories and  
troubles; provides status information; and prompts for input. These messages can be up to 80  
characters, displaying over four lines of 20 characters each. Annunciator keys beep when they  
are pressed.  
8.2.2 Banner  
The banner is the message that displays on the control panel when the system is in normal  
mode (no alarm or trouble condition exists and menus are not in use). You can create a  
customized message that will display instead of the internal (default) message. See Section  
Figure 8-2 Banner Display Examples  
8.3 Key Operation  
The key on the control panel board assembly is for accessing the Main Menu. The key is  
activated when it is turned once to the right (clockwise). If the key has been used to activate  
the menu, it must be turned counter-clockwise to exit the menu.  
Figure 8-3 Using a Key to Access the Main Menu  
8-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Operation  
8.4 Menu System  
The control panel is easy to operate from Main Menu. To view the Main Menu press the  
or button on the control panel or remote annunciator, then turn the firefighter’s key  
clockwise or enter your access code. The Main Menu will appear as shown in Section 8.4.1.  
Select the desired option. If you have entered a code or firefighter’s key does not have access  
to the menu item you have selected the following display message will appear:  
-Access denied.-  
Entered PIN does not  
allow access to this  
function.  
You must enter an access code with the correct profile settings to gain access to that menu  
item.  
The control panel supports up to 20 access codes. The profile for each access code (or user)  
can be modified through the programming menu option (see Section 7.10 for access code  
programming).  
8.4.1 Main Menu Overview  
The chart below is a brief overview of the Main Menu. These options are described in greater  
detail throughout this section of the manual.  
Main Menu Options  
Description  
From here both menus can access Fire Drill and Indicator Test.  
1
2
3
4
5
System Tests  
From here both menus can enable / disable points.  
Display event history on the LCD. See Section 8.5.4 for more information.  
Set time and date for the system.  
Point Functions  
Event History  
Set Time and Date  
Printer Options  
Options for controlling a printer if attached to the system. If a printer is used,  
the Model 5824 serial/parallel interface module must be used.  
Cancel any attempt to call the central station. Any calls awaiting additional  
attempts will be aborted.  
6
7
8
9
Reset Dialer  
Program Menu  
System Info  
Brings up a set of menus for programming the panel, including changing  
access codes. These options are described in detail in Section 7.  
View system information, including model and serial numbers and revision  
number and date.  
Initiate communication from the panel site between the panel and a  
computer running the Silent Knight Software Suite.  
Up/Download  
151209  
8-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
8.4.2 Using the Menus  
To move through the menus:  
Use  
previous menu.  
and  
to move through the options in a menu. Use to move to a  
To select an option:  
Enter the number of the option.  
–OR–  
ENTER  
Press  
(Enter key) if the option appears at the top of the menu (= symbol  
displays after the option number in this case).  
8.5 Basic Operation  
8.5.1 Setting Time and Date  
4
1. From the Main Menu, select for Set Date and Time.  
2. Make changes in the fields on the screen. Use (right arrow) to move through the fields.  
Use the  
and  
to select options in the fields.  
ENTER  
3. When the date and time are correct, press  
.
8.5.2 Disable / Enable a Point  
2
1. From the Main Menu, select for Point Functions.  
1
2. Select for Disable/Enable Point. A list of modules displays.  
ENTER  
3. Use  
and  
to move through the list. Press  
to select the module where the  
point you want to disable/enable is located. A description of the point should display. The  
fourth line of the screen should show "NORMAL" (meaning that the point is currently  
enabled) or "DISABLED" (the point is currently disabled). Press to toggle between NOR-  
MAL and DISABLE.  
8.5.3 Disable / Enable NACs by Group  
2
1. From the Main Menu, select for point functions.  
1
2
2. Select to Disable NACs by group or to Enable NACs by group.  
ENTER  
3. Use  
lighted.  
and  
to move through the list of groups. Press  
to select the group high-  
8-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System Operation  
8.5.4 View Event History  
3
Use the View Event History feature to display events on LCD. From the Main Menu, press  
to select Event History. Events will begin displaying with most recent events first.  
The panel can store up to 1000 events. When it reaches its 1000-event capacity, it begins  
deleting, starting with the oldest events.  
If a printer is attached to the system (via a Module 5824 serial/parallel interface module), you  
can print event history (see Section 8.5.17).  
The 5660 SKSS or 5670 SKSS can be used to retain more than 1000 events and to create  
event history reports.  
8.5.4.1 To clear the event history  
1
6
From the Installer menu select for System Tests. From the test menu select Clear  
History Buffer.  
8.5.5 Conduct a Fire Drill  
1
1. From the Main Menu, press for System Tests.  
ENTER  
1
2. Press for Fire Drill. You will be prompted to press  
.
ENTER  
3. The drill will begin immediately after you press  
.
4. Press any key to end the drill. (If you do not press any key to end the fire drill manually, it  
will time out automatically after ten minutes.)  
If a fire drill switch has been installed, activating the switch will begin the drill; deactivating  
the switch will end the drill.  
8.5.6 Conduct an Indicator Test  
The indicator test checks the annunciator LEDs, PZT, and LCD display.  
1
1. From the Main Menu, press for System Tests.  
2
2. Press for Indicator Test. The system turns on each LED several times, beeping the PZT  
as it does so. At the same time it scrolls each available character across the LCD. A prob-  
lem is indicated if any of the following occurs:  
An LED does not turn on;  
You do not hear a beep;  
All four lines of the LCD are not full.  
This test takes approximately 15 seconds to complete. You can press any key to end manually  
while the test is still in progress. When the test ends, you will be returned to the <Test Menu>.  
151209  
8-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
8.5.7 Conduct a Walk Test  
1
1. From the Main Menu, press for System Tests.  
IMPORTANT!  
If any alarm verification zones are being used, the user will be asked if they  
wish to disable alarm verification during walk test. This occurs for either walk  
test option.  
3
2. Select for Walk Test-No Rpt. The LCD will display “WALK TEST STOPPED” on  
Line 1 and “ENTER = start test” on Line 2. If you select this option, central station report-  
ing will be disabled while the test is in progress.  
Or  
4
Select for Walk Test-with Rpt. The LCD will display “WALK TEST STOPPED” on  
Line 1 and “ENTER = start test” on Line 2. If you select this option, central station report-  
ing will occur as normal during the walk test.  
The panel generates a TEST report to the central station when the walk test begins. During  
a walk test, the panel’s normal fire alarm function is completely disabled, placing the  
panel in a local trouble condition. All zones respond as 1-Count zones (respond when a  
single detector is in alarm) during a walk test. Each alarm initiated during the walk test  
will be reported and stored in the event history buffer.  
ENTER  
3. Press  
to end the walk test. The system will reset. The panel will send a "TEST  
RESTORE" report to the central station.  
If you do not end the walk test manually within four hours, it will end automatically.  
If an alarm or pre-alarm condition is occurring in the system, you will not be able to enter the  
walk test.  
Note: the panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to  
normal, the panel is ready to go to the next device.  
8.5.8 Conduct a Dialer Test  
1
1. From the Main Menu, press for System Tests.  
5
2. Select for Dialer Test. The screen will display “Manual dialer test started”. When the  
test is completed, you will be returned to the <Test Menu>.  
8-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Operation  
8.5.9 Silence alarms or troubles  
SILENCE  
Press  
and enter your code or rotate the key at the prompt. If an external silence  
switch has been installed, activating the switch will silence alarms or troubles. If you are  
SILENCE  
already using system menus when you press  
rotate the key.  
, you will not need to enter your code or  
Note: Alarm and trouble signals that have been silenced but the detector remains un-restored will un-silence ev-  
ery 24 hours until it is restored.  
8.5.10 Reset alarms  
RESET  
Press  
and enter your code or rotate the key at the prompt. If an external reset switch  
has been installed, activating the switch will reset alarms. If you are already using system  
RESET  
menus when you press  
, you will not need to enter your code or rotate the key.  
8.5.11 Check Detector Through Point Status  
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in  
compliance with NFPA 72.  
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL  
TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an  
out of compliance condition (but is currently still in compliance).  
When a CAL TRBLE condition occurs, the central station receives a detector trouble report  
(“373” + Zone # for Contact ID format; “FT” + Zone # in SIA format).  
To check sensitivity for an individual detector, follow the steps below. Section 8.5.17 provides  
instructions for printing the status of all detectors in the system.  
2
1. From the Main Menu, press for Point Functions.  
2
2. Press for Point Status.  
3. Select the module where the point you want to check is located.  
ENTER  
4. Enter the number of the point you want to check and press  
.
151209  
8-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
5. A screen similar to those shown in Figure 8-4 will display.  
Figure 8-4 Checking Detector Sensitivity Compliance  
If a printer is attached to the system (via a Module 5824 serial/parallel interface module), you  
can print detector status (see Section 8.5.17).  
8.5.12 View Status of a Point  
2
1. From the Main Menu, select for Point Status.  
ENTER  
2. From the list that displays, press  
to select the module where this point is located.  
The screen that displays will show you if the point has a trouble and will provide sensitiv-  
ity compliance information. (See Section 8.5.11 for complete information about detector  
sensitivity compliance.)  
8.5.13 View Alarms or Troubles  
When the system is in alarm or trouble, you can press  
to view the location of an alarm or  
8.5.14 View System Information  
8
Press from the Main Menu to view the panel model and serial number and system version  
number and date. The information displays for several seconds then returns to the main menu.  
8.5.15 Reset dialer  
6
From the Main Menu, select . The LCD will display “Dialer reset in progress...” You will be  
returned to the Main Menu when the reset is completed.  
8-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System Operation  
8.5.16 Communicating with a Remote Computer  
An installer at the panel site can initiate communications between the panel and a computer  
running the SKSS 5660. You can use this feature to upload a panel configuration. For  
example, if you have made programming changes to an installation on site using an  
annunciator, you can send your changes to the computer, so that the central station will have  
the latest data about the installation. See the software manual for more information (PN  
151240).  
To initiate communication:  
9
1. From the Main Menu, select for Up/Download.  
2. From the next screen that displays, select the communication device. Options are:  
If you select this option, you will use the panel’s built-in modem to call  
the panel.  
1
2
= Internal Modem  
If you select this option, the panel and a computer are both on-site  
connected via a 9-pin straight-through serial cable.  
= RS232 connection  
3. If you are using the panel’s internal modem to communicate, you will be prompted to  
enter a phone number. If you are communicating via the RS232 connection, a phone num-  
ber is not needed and this step will be skipped.  
ENTER  
If the phone number you will be calling is already displayed, press  
Step 4.  
. Continue with  
If the phone number you will be calling is not already displayed, enter the number and press  
ENTER  
. A phone number can be up to 40 digits long and can contain the following special  
characters.  
#
*
,
Pound (or number) key on the telephone  
Star key on the telephone  
Comma (character for 2-second pause)  
Use the number buttons on the annunciator or the up- and down-arrow keys to select special  
characters. Characters begin displaying after “9”.  
4. You will be prompted to enter an account number. If the account number you want to use  
ENTER  
is already displayed, just press  
to begin communication.  
If the account number displayed is not the correct one, enter the account number and press  
ENTER  
to begin communication.  
5. The panel will attempt to communicate with the computer. If communication was estab-  
lished, the upload task you created will be placed in the SKSS 5660 job queue, awaiting  
processing. When processing is completed, an “Unsolicited Upload” task will appear in  
the queue.  
151209  
8-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
8.5.17 Working with a Printer  
If you are using the Model 5824 serial/parallel interface module, several printing options are  
available. See Section 4.7 for information about installing the 5824.  
5
1. From the Main Menu, select Printer Options.  
2. From the next screen, select the 5824 module where the printer is connected.  
3. If the printer is not currently busy printing another report, a screen with the following  
1
options will be available. If the printer is busy, a message will display. You can press to  
cancel the current print job. These options will then display.  
Enables event logging, which causes the printer to continuously print events as they occur. The  
date/time will print in 24-hour military format. Once event logging is enabled, it will remain  
enabled until canceled by the installer. If you need to disable event logging, return to this option  
1
= Event Logging  
1
and press  
to disable.  
EVENT LOG:  
STARTED: 02/17/97 02:23  
02/17/97 11:23 Event: System Silenced  
02/17/97 11:24 Event: System Reset  
02/17/97 14:30 Event: Local Programming Begin  
02/17/97 15:01 Event: Local Programming Ended Successfully  
Sample Event Log  
EVENT LOG:  
STOPPED: 02/17/97 15:02  
Prints the up-to-1000 events currently stored in the panel’s event history buffer. Events print  
starting with the newest. The date and time printed will be when the event actually occurred and  
will print in 24-hour military format.  
2
= Print Event History  
EVENT HISTORY:  
PRINTED: 02/28/97 13:35  
3 of 10: System Silenced  
2 of 10: System Reset  
4 of 10: Printer Off Line 4  
4 of 10: Printer On Line 4  
5 of 10: Local Programming Begin  
5 of 10: Local Programming Ended Successfully  
6 of 10: Walk Test Begin  
02/20/97 09:02 Event  
02/20/97 09:05 Event  
02/22/97 08:47 Event  
02/22/97 08:52 Event  
02/25/97 15:54 Event  
02/25/97 16:10 Event  
Sample Event  
History Print-Out  
02/28/97 12:50 Event  
02/28/97 13:31 Event  
2 of 10: Walk Test End  
.
.
.
Prints the current status of all detectors in the system. This is a method for finding out if any  
detectors are out of NFPA compliance or any detectors need maintenance (are approaching an  
out of compliance condition).  
3
= Print Detector  
Status  
Sample Detector  
Status Print-Out  
Note: Detector status can also be viewed and printed using the 5660 SKSS or 5670 SKSS (facility monitoring on-  
ly).  
8-10  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Operation  
8.6 Operation Mode Behavior  
The control panel can be in one of seven conditions at any given moment: Normal, Alarm,  
Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 8-1 describes the behavior of the  
panel in each of these modes.  
Table 8-1: Operation Mode Behavior  
Operation  
Mode  
Occurs When  
System Behavior  
In This Mode You Can  
Normal  
No alarm or  
trouble  
condition exists  
and menus are  
not in use.  
SYSTEM POWER LED is on.  
Enter the appropriate code to activate the User or  
Installer Menu, or rotate the key to activate the User  
Menu.  
The All Systems Normal display indicates  
that the system is in normal mode.  
The current date and time display on the  
last line of the LCD.  
Alarm  
A smoke  
The dialer seizes control of the phone line Press the down arrow to view the alarm. A screen  
detector goes  
into alarm or a  
pull station is  
activated.  
and calls the central station.  
similar to this one displays.  
The on-board annunciator sounds a loud,  
steady beep (any notification devices  
attached to the system will also sound).  
GENERAL ALARM LED flashes.  
The LCD displays a screen similar to this  
one.  
SILENCE  
Press  
and enter an access code (or  
activate the key) to silence the annunciator (and any  
notification devices attached to the system).  
RESET  
When the alarm condition clears, press  
and enter a code (or activate the key) to restore the  
panel to normal.  
151209  
8-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
Table 8-1: Operation Mode Behavior  
Operation  
Mode  
Occurs When  
System Behavior  
In This Mode You Can  
Supervisory  
The system  
detects a  
supervisory  
condition.  
The dialer seizes control of the phone line  
and calls the central station.  
Press  
(down arrow) to view the supervisory  
condition. A screen similar to this one displays.  
The on-board annunciator sounds a loud,  
pulsing beep in the sequence one second  
on, one second off.  
SUPERVISORY LED flashes.  
The LCD displays a screen similar to this  
one.  
SILENCE  
Press  
and enter an access code (or  
activate the key) to silence the annunciator.  
Once the supervisory condition has been corrected,  
the system will restore itself automatically.  
Trouble  
A system trouble The dialer seizes control of the phone line  
Press  
(down arrow) to view the trouble. A  
condition  
occurs.  
and calls the central station.  
screen similar to this one displays.  
The on-board annunciator sounds a loud,  
pulsing beep in the sequence one second  
on, nine seconds off.  
SYSTEM TROUBLE LED flashes.  
The LCD displays a screen similar to this  
one.  
SILENCE  
Press  
and enter an access code (or  
activate the key) to silence the annunciator.  
Once the trouble condition has been fixed, the  
system will restore itself automatically.  
8-12  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Operation  
Table 8-1: Operation Mode Behavior  
System Behavior  
Operation  
Mode  
Occurs When  
In This Mode You Can  
(down arrow) to view the prealarm. A  
Prealarm  
A single detector Touchpad PZT beeps.  
trips in a 2-  
Press  
The LCD displays a screen similar to this  
screen similar to this one displays.  
Count zone. (2-  
Count means  
two detectors  
must trip before  
an alarm is  
one.  
reported.)  
All system operations are available in this mode.  
Menus are not available during the reset process.  
Reset  
All LEDs are on briefly then the LCD  
displays "ALARM RESET IN  
PROGRESS". If the reset process  
completes normally, the date and time  
normal mode screen displays.  
RESET  
The  
button is pressed  
followed by a  
valid code or  
rotation of the  
key.  
Silenced  
An alarm or  
trouble  
condition has  
been silenced  
but still exists.  
To silence  
SYSTEM SILENCE LED is on. SYSTEM  
TROUBLE, SUPERVISORY or  
GENERAL ALARM LED (depending on  
condition) is on. The annunciator (and any  
notification devices attached to the  
system) will be silenced.  
Press  
(down arrow) to view the location of the  
alarm or trouble. When the condition no longer  
exists, the SYSTEM SILENCED and SYSTEM  
TROUBLE LED, SUPERVISORY or GENERAL  
ALARM LEDs turn off.  
alarms and  
troubles, press  
SILENCE  
followed by the  
Installer or User  
Code or rotate  
the key.  
151209  
8-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
8.7 Releasing Operations  
This control panel supports two types of releasing, Double Interlock Zone, and Single  
Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the  
system, and the Single Interlock does not. An interlock switch is typically a dry-contact  
pressure switch.  
When a Single or Double Interlock Zone releasing is selected the system is will automatically  
default the following system parameters:  
Note: The defaults created can be modified through programming if desired.  
Output Group 2 is created. Output Group 2 will be defaulted as an "Alarm" output group  
for all releasing zones. NAC [34:001] is assigned to Output Group 2.  
Output Group 3 is created. Output Group 3 will be defaulted as an "Pre-Alert" output  
group for all releasing zones. NAC [34:002] is assigned to Output Group 3.  
Output Group 4 is created. Output Group 4 will be defaulted as a "Release" output group  
for all releasing zones. NAC circuit [34:003] is assigned to Output Group 4.  
Note: The installer must define which input points will be used for detectors, manual release switches, or inter-  
lock/pressure switches.  
Table 8-2: Approved Releasing Solenoids  
Manufacturer  
Asco  
Part Number  
T8210A107  
8210G207  
Rating  
Current  
Freq  
24 VDC  
24 VDC  
3A max  
3A max  
0 Hz  
0 Hz  
Model 7641  
Must Mounted  
at the Solenoid  
Figure 8-5 Wiring Configuration for Solenoid  
Do not mix cross alarming zones with smoke verification zones. There must be at least two  
automatic detection devices in each protected space. Spacing must be reduced to 0.7 times the  
linear spacing in accordance with NFPA 72. See Section 7.4 for zone option programming.  
8-14  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Operation  
8.7.1 Single Interlock Zone Releasing  
A single interlock zone utilizes a minimum of two addressable detectors and a designated  
manual release switch.  
Important!  
Only addressable detectors can be used. No conventional detectors can be used.  
Each Single Interlock Zone input requires at least one manual release switch.  
Conditions Required for an Pre-Alert Output Activation  
If any single addressable detector is activated, the “Pre-Alert” output will activate. This alerts  
the user that the initial stages required for a release condition are present. (Also refer to Table  
Conditions required for an General Alarm and Release Output Activation  
If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the  
Table 8-3: Single Interlock Zone Operation  
Inputs  
Output Results  
1st Addressable Detector  
2nd Addressable Detector  
Manual Release Station  
151209  
8-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
IntelliKnight 5820XL Installation Manual  
8.7.2 Double Interlock Zone Releasing  
A Double Interlock Zone uses a minimum of two Addressable detectors, a designated manual  
release switch, and an interlock switch input. An interlock switch is typically a dry-contact  
pressure switch and will be referred to as an interlock/pressure switch in this document.  
Important!  
Only addressable detectors can be used. No conventional detectors can be used.  
Each Single Interlock Zone input requires at least one manual release switch.  
Each Double Interlock Zone input requires at least one Interlock/pressure switch  
Conditions Required for a Pre-Alert Output Activation  
If any single addressable detector is activated, the “Pre-Alert” output will activate. This alerts  
the user that the initial stages required for a release condition are present. (Also refer to Table  
Conditions Required for a General Alarm Output Activation  
If two addressable detectors, a manual release switch is activated, or an interlock switch is  
active, the "Pre-Alert", and "General Alarm" outputs will activate.  
Conditions Required for a Release Output Activation  
Any release requires the activation of an interlock switch, and either a manual release switch  
or 2 activated addressable detectors. When these conditions are met, the "Release" and  
"General Alarm" outputs will activate, and the "Alert" outputs will deactivate.  
Table 8-4: Double Interlock Zone Operation  
Inputs  
Output Results  
4
4
4
4
4
4
4
1st Addressable Detector  
2nd Addressable Detector  
Manual Release Station  
Interlock/Pressure Switch  
4
4
4
4
4
4
4
4
8-16  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System Operation  
8.8 Smoke Alarm Verification  
Figure 8-6 illustrates how the Smoke Alarm Verification cycle operates.  
Figure 8-6 Smoke Verification Cycle  
During the Confirmation Period if there is no alarm indication then the system will return to  
normal operation.  
151209  
8-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
8-18  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9  
Reporting  
This section lists receivers that are compatible with this control panel, and the reporting codes sent  
by the control panel for SIA and Contact ID formats.  
9.1 Receivers Compatible with the Control Panel  
Table 9-1 shows receivers compatible with the control panel.  
Table 9-1: Receivers Compatible with the Control Panel  
Manufacturer  
Silent Knight  
Model  
Format  
Model 9800  
SIA and Contact ID  
SIA  
Model 9000 (SIA formats)  
Model 685 (Contact ID )  
SG-MLR2-DG (V. 1.64 or higher)  
Quickalert  
Ademco  
Contact ID  
Sur-Gard  
SIA and Contact ID  
SIA and Contact ID  
Osborne Hoffman  
9.2 Reporting Formats Dialer Outputs  
SIA Reporting Format  
Contact ID Reporting Format  
Event Class  
(System, Zone,  
or Point)  
Module  
ID #  
(if any)  
SIA  
Event  
Code  
Event  
Family  
Parameter  
(if any)  
Event  
Code  
Group Contact  
Event Description  
Qualifier  
#
#
Note:  
Note: System events are reported when either "Report by Point" or "Report by  
System Events  
Zone" is selected.  
AC power restore  
Trouble System Event  
Trouble System Event  
Trouble System Event  
Trouble System Event  
Trouble System Event  
AR  
AT  
ER  
ER  
ER  
3
1
3
3
3
301  
301  
333  
333  
332  
00  
00  
00  
00  
00  
000  
AC power lost  
000  
SBUS expander trouble restore  
SBUS Class A supervision restore  
Exp. ID  
Exp. ID  
Exp. ID  
Exp. ID  
Exp. ID  
Exp. ID  
Short circuit removed from SLC  
communication loop  
SLC Class A supervision restored  
SBUS expander trouble  
Trouble System Event  
Trouble System Event  
Trouble System Event  
Trouble System Event  
ER  
ET  
ET  
ET  
Exp. ID  
Exp. ID  
Exp. ID  
Exp. ID  
3
1
1
1
331  
333  
333  
332  
00  
00  
00  
00  
Exp. ID  
Exp. ID  
Exp. ID  
Exp. ID  
SBUS Class A supervision lost  
Short circuit detected on SLC com-  
munication loop  
SLC Class A supervision lost  
Fire drill has begun  
Trouble System Event  
ET  
FI  
Exp. ID  
1
1
3
1
331  
604  
604  
625  
00  
00  
00  
00  
Exp. ID  
000  
Test  
Test  
System Event  
System Event  
Fire drill ended  
FK  
JD  
000  
Panel date has been changed  
Trouble System Event  
000  
151209  
9-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
SIA Reporting Format  
Contact ID Reporting Format  
Event Class  
(System, Zone,  
or Point)  
Module  
ID #  
(if any)  
SIA  
Event  
Code  
Event  
Family  
Parameter  
(if any)  
Event  
Code  
Group Contact  
Event Description  
Qualifier  
#
#
Panel time has been changed  
Local programming begin  
Phone line 1 trouble restore  
Phone line 2 trouble restore  
Trouble System Event  
Trouble System Event  
Trouble System Event  
Trouble System Event  
JT  
LB  
LR  
LR  
LS  
LT  
LT  
LU  
1
1
3
3
1
1
1
1
625  
627  
351  
352  
628  
351  
352  
628  
00  
00  
00  
00  
00  
00  
00  
00  
000  
000  
001  
002  
000  
001  
002  
000  
1
2
Local programming ended normally Trouble System Event  
Phone line 1 trouble detected  
Phone line 2 trouble detected  
Trouble System Event  
Trouble System Event  
1
2
Local programming aborted or ended Trouble System Event  
with errors  
Periodic test event – normal  
Periodic test event – off normal  
Initial power up  
Test  
Test  
System Event  
System Event  
RP  
RY  
RR  
RS  
1
1
1
1
602  
608  
305  
412  
00  
00  
00  
00  
000  
000  
000  
000  
Trouble System Event  
Trouble System Event  
Remote programming ended nor-  
mally  
Unable to report to an account  
Trouble System Event  
Trouble System Event  
RT  
Acct #  
1
1
354 Acct # Acct #  
Remote programming aborted or  
ended with errors  
RU  
413  
00  
000  
User has initiated dialer test  
Test  
System Event  
RX  
SS  
1
1
601  
203  
00  
Water release circuit has been dis-  
abled  
Trouble System Event pi Exp. ID  
Pnt #  
Pnt #  
Exp.  
ID  
Pnt #  
Pnt #  
Water release circuit has been re-  
enabled  
Trouble System Event pi Exp. ID  
SR  
3
203  
Exp.  
ID  
Walk test end  
Test  
Test  
System Event  
System Event  
TE  
TE  
3
3
607  
607  
00  
00  
000  
000  
SLC address programming ended;  
system has been re-enabled.  
Walk test begin  
Test  
Test  
System Event  
System Event  
TS  
TS  
1
1
607  
607  
00  
00  
000  
000  
SLC address programming started;  
system has been shut down.  
Printer paper restore  
Printer is out of paper  
Printer back online  
Printer offline  
Trouble System Event  
Trouble System Event  
Trouble System Event  
Trouble System Event  
VI  
VO  
VY  
VZ  
YC  
Exp ID  
Exp ID  
Exp ID  
Exp ID  
Line #  
3
1
3
1
1
335  
335  
336  
336  
350  
00  
00  
00  
00  
00  
Exp. ID  
Exp. ID  
Exp. ID  
Exp. ID  
Line #  
Auto dialer test communication trou- Trouble System Event  
ble  
Report to an account successful  
Trouble System Event  
YK  
YK  
Acct #  
Line #  
3
3
354 Acct # Acct #  
Auto dialer test communication trou- Trouble System Event  
ble restore  
350  
00  
Line #  
Ground fault condition detected  
Ground fault condition restore  
Battery voltage restore  
Battery voltage low  
Trouble System Event  
Trouble System Event  
Trouble System Event  
Trouble System Event  
YP  
YQ  
YR  
YT  
Exp. ID  
Exp. ID  
Exp. ID  
Exp. ID  
1
3
3
1
310  
310  
302  
302  
00  
00  
00  
00  
Exp. ID  
Exp. ID  
Exp. ID  
Exp. ID  
Note:  
Note: Zone events are reported only when "Report by Zone" is selected.  
Zone Events  
9-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reporting  
SIA Reporting Format  
Contact ID Reporting Format  
Event Class  
(System, Zone,  
or Point)  
Module  
ID #  
(if any)  
SIA  
Event  
Code  
Event  
Family  
Parameter  
(if any)  
Event  
Code  
Group Contact  
Event Description  
Qualifier  
#
#
SLC LED Module trouble restore  
SLC LED Module trouble  
Manual pull switch alarm  
Detector alarm  
Trouble  
Trouble  
Alarm  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
ER  
ET  
FA  
FA  
FH  
FH  
FJ  
0000  
0000  
Zone  
Zone  
Zone  
Zone  
Zone  
Zone  
Zone  
3
1
1
1
3
3
3
3
3
333  
333  
115  
110  
115  
110  
373  
373  
373  
00  
00  
00  
00  
00  
00  
00  
00  
00  
000  
000  
Zone  
Zone  
Zone  
Zone  
Zone  
Zone  
Zone  
Alarm  
Manual pull switch alarm restore  
Detector alarm restore  
Restore  
Restore  
Trouble  
Trouble  
Trouble  
Manual pull switch trouble restore  
Detector trouble restore  
FJ  
Positive Alarm Sequence acknowl-  
edge switch trouble restore  
FJ  
Auxiliary power trouble restore  
Notification output trouble restore  
Trouble  
Trouble  
Zone Event  
Zone Event  
FJ  
FJ  
0000  
3
3
320  
320  
00  
00  
000  
1000+Gro  
up #  
Group #  
Manual pull switch trouble  
Detector trouble  
Trouble  
Trouble  
Trouble  
Zone Event  
Zone Event  
Zone Event  
FT  
FT  
FT  
Zone  
Zone  
Zone  
1
1
1
373  
373  
373  
00  
00  
00  
Zone  
Zone  
Zone  
Positive Alarm Sequence acknowl-  
edge switch trouble  
Auxiliary power trouble  
Notification trouble  
Trouble  
Trouble  
Zone Event  
Zone Event  
FT  
FT  
0000  
1
1
320  
320  
00  
00  
000  
1000+Gro  
up#  
Group #  
User initiated a system reset  
Water flow switch alarm  
Reset  
Alarm  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
OR  
SA  
SH  
SJ  
1
1
3
3
3
401  
113  
113  
373  
373  
00  
00  
00  
00  
00  
000  
Zone  
Zone  
Zone  
Zone  
Zone  
Zone  
Zone  
Zone  
Water flow switch alarm restore  
Water flow switch trouble restore  
Restore  
Trouble  
Trouble  
Supervisory/Tamper switch trouble  
restore  
SJ  
Supervisory condition restore  
Supervisory condition  
Trouble  
Trouble  
Trouble  
Trouble  
Alarm  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
SR  
SS  
Zone  
Zone  
Zone  
Zone  
3
1
1
1
1
203  
203  
373  
373  
140  
00  
00  
00  
00  
01  
Zone  
Zone  
Zone  
Zone  
Zone  
Water flow switch trouble  
ST  
ST  
UA  
Supervisory/Tamper switch trouble  
Zone-based AUX1 switch alarm  
1000+Zon  
e
Zone-based AUX2 switch alarm  
Alarm  
Zone Event  
UA  
2000+Zon  
e
1
140  
02  
Zone  
System-based AUX1 switch alarm  
System-based AUX2 switch alarm  
Alarm  
Alarm  
Restore  
Zone Event  
Zone Event  
Zone Event  
UA  
UA  
UH  
1000  
2000  
1
1
3
140  
140  
140  
01  
02  
01  
000  
000  
Zone-based AUX1 switch alarm  
restore  
1000+Zon  
e
Zone  
Zone-based AUX2 switch alarm  
restore  
Restore  
Restore  
Zone Event  
Zone Event  
UH  
UH  
2000+Zon  
e
3
3
140  
140  
02  
01  
Zone  
000  
System-based AUX1 switch alarm  
restore  
1000  
151209  
9-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
SIA Reporting Format  
Contact ID Reporting Format  
Event Class  
(System, Zone,  
or Point)  
Module  
ID #  
(if any)  
SIA  
Event  
Code  
Event  
Family  
Parameter  
(if any)  
Event  
Code  
Group Contact  
Event Description  
Qualifier  
#
#
System-based AUX2 switch alarm  
restore  
Restore  
Trouble  
Trouble  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
Zone Event  
UH  
UJ  
UJ  
UJ  
UJ  
UJ  
UT  
UT  
2000  
3
140  
373  
373  
373  
373  
373  
373  
373  
02  
000  
Zone-based AUX1 switch trouble  
restore  
1000+Zon  
e
3
3
3
3
3
1
1
01  
02  
01  
02  
00  
01  
02  
Zone  
Zone  
000  
Zone-based AUX2 switch trouble  
restore  
2000+Zon  
e
System-based AUX1 switch trouble Trouble  
restore  
1000  
2000  
0000  
System-based AUX2 switch trouble Trouble  
restore  
000  
External Reset/Silence/Fire Drill  
switch trouble restore  
Trouble  
Trouble  
Trouble  
000  
Zone-based AUX1 switch trouble  
1000+Zon  
e
Zone  
Zone  
Zone-based AUX2 switch trouble  
2000+Zon  
e
System-based AUX1 switch trouble Trouble  
System-based AUX2 switch trouble Trouble  
Zone Event  
Zone Event  
Zone Event  
UT  
UT  
UT  
1000  
2000  
0000  
1
1
1
373  
373  
373  
01  
02  
00  
000  
000  
000  
External Reset/Silence/Fire Drill  
switch trouble  
Trouble  
Note: Note: Point events are reported only when "Report by Point" is selected.  
Point Events  
Manual pull switch alarm  
Alarm  
Alarm  
Alarm  
Alarm  
Disable  
Restore  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
FA  
FA  
FA  
FA  
FB  
FH  
FH  
FH  
FH  
FJ  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
1
1
1
1
1
3
3
3
3
3
3
3
115  
110  
110  
110  
571  
115  
110  
110  
110  
320  
373  
373  
Exp.  
ID  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Manual release switch alarm (Water  
Release Zone)  
Exp.  
ID  
Interlock switch alarm (Water  
Release Zone)  
Exp.  
ID  
Detector alarm  
Exp.  
ID  
Point disabled  
Exp.  
ID  
Manual pull switch alarm restore  
Exp.  
ID  
Manual release switch alarm restore Restore  
(Water Release Zone)  
Exp.  
ID  
Interlock switch alarm restore (Water Restore  
Release Zone)  
Exp.  
ID  
Detector alarm restore  
Restore  
Trouble  
Trouble  
Exp.  
ID  
Notification output trouble restore  
Manual pull switch trouble restore  
Exp.  
ID  
FJ  
Exp.  
ID  
Manual release switch trouble restore Trouble  
(Water Release Zone)  
FJ  
Exp.  
ID  
9-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reporting  
SIA Reporting Format  
Contact ID Reporting Format  
Event Class  
(System, Zone,  
or Point)  
Module  
ID #  
(if any)  
SIA  
Event  
Code  
Event  
Family  
Parameter  
(if any)  
Event  
Code  
Group Contact  
Event Description  
Qualifier  
#
#
Interlock switch trouble restore  
(Water Release Zone)  
Trouble  
Trouble  
Trouble  
Trouble  
Trouble  
Trouble  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
FJ  
FJ  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
3
373  
373  
373  
320  
320  
373  
373  
373  
373  
373  
320  
571  
113  
571  
571  
113  
373  
373  
Exp.  
ID  
Pnt #  
Detector trouble restore  
3
3
3
1
1
1
1
1
1
1
3
1
1
1
3
3
3
Exp.  
ID  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Positive Alarm Sequence acknowl-  
edge switch trouble restore  
FJ  
Exp.  
ID  
Aux power trouble restore  
Notification output trouble  
Manual pull switch trouble  
FJ  
Exp.  
ID  
FT  
FT  
FT  
FT  
FT  
FT  
FT  
FU  
SA  
SB  
SB  
SH  
SJ  
Exp.  
ID  
Exp.  
ID  
Manual release switch trouble (Water Trouble  
Release Zone)  
Exp.  
ID  
Interlock switch trouble (Water  
Release Zone)  
Trouble  
Trouble  
Trouble  
Trouble  
Disable  
Alarm  
Exp.  
ID  
Detector trouble  
Exp.  
ID  
Positive Alarm Sequence acknowl-  
edge switch trouble  
Exp.  
ID  
Auxiliary Power Trouble  
Exp.  
ID  
Point Enabled  
Exp.  
ID  
Water flow switch alarm  
Water flow switch disabled  
Exp.  
ID  
Disable  
Disable  
Restore  
Trouble  
Trouble  
Exp.  
ID  
Supervisory/Tamper switch or  
supervisory duct dectector disabled  
Exp.  
ID  
Water flow switch alarm restore  
Water flow switch trouble restore  
Exp.  
ID  
Exp.  
ID  
Supervisory/Tamper switch or  
supervisory duct dectector trouble  
restore  
SJ  
Exp.  
ID  
Supervisory condition restore  
Trouble  
Trouble  
Trouble  
Trouble  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
SR  
SS  
ST  
ST  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
3
1
1
1
203  
203  
373  
373  
Exp.  
ID  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Supervisory condition  
Exp.  
ID  
Water flow switch trouble  
Exp.  
ID  
Supervisory/Tamper switch or  
supervisory duct dectector trouble  
Exp.  
ID  
151209  
9-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
SIA Reporting Format  
Contact ID Reporting Format  
Event Class  
(System, Zone,  
or Point)  
Module  
ID #  
(if any)  
SIA  
Event  
Code  
Event  
Family  
Parameter  
(if any)  
Event  
Code  
Group Contact  
Event Description  
Qualifier  
#
#
Water flow switch re-enabled  
Disable  
Disable  
Alarm  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
Point Event pi Exp. ID  
SU  
SU  
UA  
UA  
UA  
UA  
UB  
UH  
UH  
UH  
UH  
UJ  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
3
571  
571  
140  
140  
140  
140  
571  
140  
140  
140  
140  
373  
373  
373  
373  
373  
373  
373  
373  
373  
373  
571  
380  
Exp.  
ID  
Pnt #  
Supervisory/Tamper switch or  
supervisory duct dectector re-enabled  
3
1
1
1
1
1
3
3
3
3
3
3
3
3
3
1
1
1
1
1
3
1
Exp.  
ID  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Pnt #  
Zone-based AUX1 switch alarm  
Zone-based AUX2 switch alarm  
System-based AUX1 switch alarm  
System-based AUX2 switch alarm  
Auxiliary switch input disabled  
Exp.  
ID  
Alarm  
Exp.  
ID  
Alarm  
Exp.  
ID  
Alarm  
Exp.  
ID  
Disable  
Restore  
Restore  
Restore  
Restore  
Trouble  
Trouble  
Trouble  
Exp.  
ID  
Zone-based AUX1 switch alarm  
restore  
Exp.  
ID  
Zone-based AUX2 switch alarm  
restore  
Exp.  
ID  
System-based AUX1 switch alarm  
restore  
Exp.  
ID  
System-based AUX2 switch alarm  
restore  
Exp.  
ID  
Zone-based AUX1 switch trouble  
restore  
Exp.  
ID  
Zone-based AUX2 switch trouble  
restore  
UJ  
Exp.  
ID  
External Reset/Silence/Fire Drill  
switch trouble restore  
UJ  
Exp.  
ID  
System-based AUX1 switch trouble Trouble  
restore  
UJ  
Exp.  
ID  
System-based AUX2 switch trouble Trouble  
restore  
UJ  
Exp.  
ID  
Zone-based AUX1 switch trouble  
Trouble  
Trouble  
Trouble  
UT  
UT  
UT  
UT  
UT  
UU  
XE  
Exp.  
ID  
Zone-based AUX2 switch trouble  
Exp.  
ID  
External Reset/Silence/Fire Drill  
switch trouble  
Exp.  
ID  
System-based AUX1 switch trouble Trouble  
Exp.  
ID  
System-based AUX2 switch trouble Trouble  
Exp.  
ID  
Auxiliary switch input re-enabled  
Disable  
Exp.  
ID  
An unexpected SLC device has been Trouble  
detected  
Exp.  
ID  
9-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reporting  
SIA Reporting Format  
Contact ID Reporting Format  
Event Class  
(System, Zone,  
or Point)  
Module  
ID #  
(if any)  
SIA  
Event  
Code  
Event  
Family  
Parameter  
(if any)  
Event  
Code  
Group Contact  
Event Description  
Qualifier  
#
#
An unexpected SLC device has been Trouble  
removed  
Point Event pi Exp. ID  
XI  
Pnt #  
3
380  
Exp.  
ID  
Pnt #  
151209  
9-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
9-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10  
Testing and Troubleshooting  
10.1 Troubleshooting  
This section of the manual offers suggestions for troubleshooting hardware problems. Please  
read this section if you encounter a problem when installing the control panel. If these  
suggestions do not solve your problem or if you encounter a problem that is not listed here,  
contact Silent Knight Technical Support at 800-446-6444 for assistance.  
10.2 Common Problems  
Problem  
Possible Cause / Suggested Actions  
Trouble message "DBL ADDR" (Double An address has been assigned to more than one detector. Correct the address  
Address) displays on LCD.  
following the procedure described in Section 5.8.  
Auxiliary power or notification circuits  
have incorrect polarity.  
Correct polarity. For notification and auxiliary power circuits: When in alarm  
or powered, terminals labeled "X" are positive, terminals labeled "O" are  
negative.  
SLC devices are not being recognized  
(trouble message "Missing" displays).  
Check hardware connections.  
If devices are physically connected, make sure wiring is correct (see Section  
5.4). For the main panel, the positive side of device must be connected to  
terminal 34; the negative side must be connected to Terminal 33. For 5815XL  
devices, make sure the device connects to the 5815XL via the SLC OUT  
terminals.  
There can be only one SLC loop on the main panel and on each 5815XL  
module. Do not connect devices to terminals labeled SLC IN.  
Make sure SLC devices have been addressed properly following the  
procedure described in Section 5.8.  
For contact monitor modules, which are addressed using dip switches, the dip  
switch must be set to the correct address before power is applied to the SLC  
loop. If this procedure is not followed, the device will have an incorrect  
address.  
Make sure correct polarity has been observed for SLC device wiring. See  
151209  
10-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
Problem  
Possible Cause / Suggested Actions  
SLC devices are not being recognized  
(trouble message "Missing" displays on  
the annunciator).  
Check that SLC loop impedance is within the required range.  
To measure impedance, use the following procedure.  
1. Disconnect both wires from the terminal block at the panel (SLC devices  
can remain connected).  
2. Measure the impedance from positive to negative and from negative to  
positive. Both measurements should be greater than 500 K ohms. If the  
installation uses T-taps, test each T-tap individually.  
3. Temporarily connect the positive wire to the negative wire of the SLC loop  
at the point farthest from the panel (SLC devices can remain connected).  
4. Measure the impedance from positive to negative and from negative to  
positive. Both measurements must be less than 50 ohms.  
The panel indicates a ground fault trouble An earth ground fault occurs when the panel senses an unexpected flow of  
condition (trouble message "GROUND  
FAULT" displays).  
current from one or more of its terminals to the earth connection (Terminal 2).  
Isolate the wiring that is causing the fault by removing wiring connections  
one at a time until the earth fault is no longer present. Pause at least five  
seconds after removing a wire before removing the next one.  
The panel will also go into ground fault if a computer is connected to the  
panel via a serial cable attached to the panel’s 9-pin connector. This is a  
correct method for on-site communication between a panel and a computer.  
Ignore the ground fault message in this case. The trouble will clear  
automatically when you disconnect the computer from the cable  
5815XL module that has been physically Check the status of the 5815XL green LED. If it flashes in the pattern .5 sec.  
connected to the panel but is not being  
recognized.  
on / .5 sec. off, it is likely that the 5815XL has not been added to the system  
through programming. JumpStart will add any 5815XLs connected to the  
panel. If you have already run JumpStart, 5815XLs can be added manually  
(see Section 7.3.2).  
Check that the correct ID for the 5815XL module has been set through the  
DIP switches. Assign ID#1 to the first 5815XL and ID#2 to the second  
5815XL. See Section 4.10.1 for complete details.  
If the wiring between the 5815XL and the panel is correct, measure the  
voltage from 5815XL Terminal (+) to Terminal (-). Voltage should be in the  
range 27.2-27.4V when AC power is present.  
If the green LED is not flashing, the likely cause is incorrect wiring from  
between the 5815XL and the panel. See Section 4.6.1 for wiring details.  
10.2.1 Periodic Testing And Maintenance  
To ensure proper and reliable operation, it is recommended that system inspection and testing  
be scheduled monthly or as required by national and/or local fire codes. Testing should be  
done by a qualified services representative if a malfunction is encountered.  
Before testing:  
1) Notify the fire department and/or central alarm receiving station if an alarm condition is  
transmitted.  
2) Notify facility personnel of a test so that alarm sounding devices are ignored during the test  
period.  
10-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Testing and Troubleshooting  
3) When necessary, activation of Notification Appliances can be prevented by the DISABLE  
function  
Testing:  
1) Activate a input via an alarm initiating device and check that the correct outputs activate  
(Notification Appliances sound/flash, relays activate, alarm LED lights). Reset system.  
Repeat for each alarm initiating device.  
2) Momentarily open the following circuits one at a time and check for a trouble signal:  
Notification Appliance (bell) Circuits.  
Initiating devices  
3) If new batteries were installed, wait 48 hours before completing this step. Remove AC  
power, activate initiating device and check that:  
The ALARM indicator lights.  
All active Notification Appliances sound.  
Measure battery voltage while the Notification Appliances are sounding. Replace any battery  
with terminal voltage less than 85% of rating. Reapply AC power and RESET system.  
10.2.2 Event History  
The event history can be useful for tracking or recalling a trouble condition.  
151209  
10-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
10.3 Built-in Troubleshooting and Testing Tools  
The fire control panel has several built-in testing and troubleshooting tools that can be utilized  
to save time while testing and troubleshooting points and SLC devices.  
10.3.1 SLC Device Locator  
SLC device locator can be used to locate a device on a SLC loop.  
Follow these steps to locate a particular SLC device:  
2
1. Select (Point Functions) from the Main Menu.  
4
2. Select (SLC Dev Locator).  
A message similar to the one shown in Figure 10-1 will display.  
Figure 10-1 Shut Down Warning  
3. Press the  
or  
arrow to toggle NOto YES then press  
.
If NOis chosen you will exit back to the Point Function menu.  
If Yesis chosen the system will cease normal operation leaving the premise unprotected.  
4. Select the SLC loop.  
5. Enter the SLC address of the device you wish to locate.  
The LED on the selected device will start flashing.  
6. Press any key to exit SLC device locator function.  
Note: Once you exit the system will resume normal operation.  
10-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Testing and Troubleshooting  
10.3.2 SLC Multi Locator  
This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a  
single search.  
Follow these instructions to locate multiple SLC devices:  
2
1. Select (Point Functions) from the Main Menu.  
5
2. Select (SLC Dev Locator).  
A message similar to the one shown in Figure 10-1 will display.  
Figure 10-2 Shut Down Warning  
3. Press the  
or  
arrow to toggle NOto YES then press  
.
If NOis chosen you will exit back to the Point Function menu.  
If Yesis chosen the system will cease normal operation leaving the premise unprotected.  
4. Select the SLC loop.  
5. Enter up to 8 SLC addresses for the devices you wish to locate.  
The LEDs on the selected devices will start flashing.  
6. Press the to exit SLC multi-locator function.  
Note: Once you exit the system will resume normal operation.  
151209  
10-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IntelliKnight 5820XL Installation Manual  
10.3.3 I/O Point Control  
This feature allows you to toggle any output on or off and trip any input device. This can be  
useful to test a point’s output mapping.  
Follow these steps to control a I/O point:  
2
1. Select (Point Functions) from the Main Menu.  
6
2. Select (I/O Point Control).  
3. Select the Module the point is on.  
4. Enter the zone number , or press the  
then press  
or  
arrow to select the point you wish to test,  
.
5. Press  
to generate an alarm for an input point or activate an output point.  
6. To exit press  
.
10-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Testing and Troubleshooting  
10.3.4 Earth Fault Resistance  
Table 10-1 lists the earth fault resistance detection for each applicable terminal on the FACP.  
Table 10-1: Earth Fault Resistance Values by Terminal  
Terminal Label  
Low Biased  
High Biased  
Terminal  
Number  
Function  
(Values in Ohms)  
High  
Trip  
High  
Restore  
Low  
Trip  
Low  
Restore  
Flexput™  
Notification  
Circuits  
4
X
O
X
O
X
O
X
O
X
O
X
O
B
A
+
I/O 6  
-
0
-
-
0
-
0
-
0
-
5
6
I/O 5  
0
-
0
-
7
0
-
0
-
8
I/O 4  
0
-
0
-
9
0
-
0
-
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
33  
34  
35  
36  
I/O 3  
0
-
0
-
0
-
0
-
I/O 2  
0
-
0
-
0
-
0
-
I/O 1  
0
-
0
-
0
-
0
-
SBUS  
Communication  
SBUS OUT  
0
0
-
0
0
-
-
-
SBUS Power  
0
-
0
-
-
0
0
0
-
0
0
0
-
SBUS  
Communication  
B
A
+
SBUS IN  
-
-
-
-
SBUS Power  
0
-
0
-
-
0
0
-
0
0
-
SLC Terminals  
SC-  
S+  
SLC OUT  
SLC IN  
-
-
0
-
0
-
SC-  
S+  
0
-
0
-
0
0
151209  
10-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
10-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 11  
Installation Records  
This section of the manual is for you to use if you wish to track of how points, zones, and  
groups have been programmed.  
11.1 SLC Point Record  
You can use the chart that begins below to keep track of SLC points.  
Default addresses for ID: On-board:  
= 33  
= 1  
= 2  
= 3  
5815-1:  
5815-2:  
5815-3  
Table 11-1: Installation Record  
Zone /  
Group  
Zone/  
Group  
Module Addr  
Description  
Module Addr  
Description  
On-board  
On-board  
On-board  
On-board  
On-board  
On-board  
On-board  
On-board  
On-board  
1
2
3
4
5
6
7
8
9
On-board 25  
On-board 26  
On-board 27  
On-board 28  
On-board 29  
On-board 30  
On-board 31  
On-board 32  
On-board 33  
On-board 34  
On-board 35  
On-board 36  
On-board 37  
On-board 38  
On-board 39  
On-board 40  
On-board 41  
On-board 42  
On-board 43  
On-board 44  
On-board 45  
On-board 46  
On-board 47  
On-board 48  
On-board 10  
On-board 11  
On-board 12  
On-board 13  
On-board 14  
On-board 15  
On-board 16  
On-board 17  
On-board 18  
On-board 19  
On-board 20  
On-board 21  
On-board 22  
On-board 23  
On-board 24  
151209  
11-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
IntelliKnight 5820XL Installation Manual  
Table 11-1: Installation Record  
Zone /  
Group  
Zone/  
Group  
Module Addr  
Description  
Module Addr  
Description  
On-board 49  
On-board 50  
On-board 51  
On-board 52  
On-board 53  
On-board 54  
On-board 55  
On-board 56  
On-board 57  
On-board 58  
On-board 59  
On-board 60  
On-board 61  
On-board 62  
On-board 63  
On-board 64  
On-board 65  
On-board 66  
On-board 67  
On-board 68  
On-board 69  
On-board 70  
On-board 71  
On-board 72  
On-board 73  
On-board 74  
On-board 75  
On-board 76  
On-board 77  
On-board 78  
On-board 79  
On-board 80  
On-board 81  
On-board 82  
On-board 83  
On-board 84  
On-board 85  
On-board 86  
On-board 87  
On-board 88  
On-board 89  
On-board 90  
On-board 91  
On-board 92  
On-board 93  
On-board 94  
On-board 95  
On-board 96  
On-board 97  
On-board 98  
On-board 99  
On-board 100  
On-board 101  
On-board 102  
On-board 103  
On-board 104  
On-board 105  
On-board 106  
On-board 107  
On-board 108  
On-board 109  
On-board 110  
On-board 111  
On-board 112  
On-board 113  
On-board 114  
On-board 115  
On-board 116  
On-board 117  
On-board 118  
On-board 119  
On-board 120  
On-board 121  
On-board 122  
On-board 123  
On-board 124  
On-board 125  
On-board 126  
On-board 127  
11-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Records  
Table 11-1: Installation Record  
Description Module Addr  
Zone /  
Group  
Zone/  
Group  
Module Addr  
Description  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
1
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
151209  
11-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Table 11-1: Installation Record  
Description Module Addr  
Zone /  
Group  
Zone/  
Group  
Module Addr  
Description  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
83  
5815-1  
5815-1  
5815-1  
5815-1  
5815-1  
123  
124  
125  
126  
127  
84  
85  
86  
87  
88  
89  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
1
90  
2
91  
3
92  
4
93  
5
94  
6
95  
7
96  
8
97  
9
98  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
11-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Records  
Table 11-1: Installation Record  
Description Module Addr  
Zone /  
Group  
Zone/  
Group  
Module Addr  
Description  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
151209  
11-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Table 11-1: Installation Record  
Description Module Addr  
Zone /  
Group  
Zone/  
Group  
Module Addr  
Description  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
5815-2  
115  
116  
117  
118  
119  
120  
122  
123  
124  
125  
126  
127  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
11-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Records  
Table 11-1: Installation Record  
Description Module Addr  
Zone /  
Group  
Zone/  
Group  
Module Addr  
Description  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
5815-1  
5815-3  
5815-3  
5815-3  
5815-3  
5815-3  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
Copy these pages if you additional sheets.  
151209  
11-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
11.2 Conventional Output Point Record  
This chart can be used to keep track of how conventional output points (circuits) have been  
configured.  
Point/Circuit  
Group  
Description  
1
2
3
4
5
6
7
8
11-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Appendix A  
Compatible Devices  
A.1  
Notification Appliances  
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL  
resistor on each loop. All supervised notification appliances used with the control panel must  
be polarized.  
Note:Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen  
will work with this feature. This control is UL listed for panel wide Synchronization.  
Table A-1 below lists notification appliances compatible with the fire alarm control panel.  
Appliances which can be synchronized indicate the type of snyc available in the columns  
marked Audio and/or Visual.  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Model  
SH24W-153075  
Audio  
Visual  
Type  
Horn/Strobe  
Strobe  
SAD24-153075  
SAD24-75110  
SL24W-75110  
SL24C-3075110  
SLB24-75  
Strobe  
Strobe  
Strobe  
Strobe  
RSD24-153075  
RSD24-75110  
SH24W-75110  
SH24W-3075110  
SHB24-75  
Strobe  
Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Chimes/Strobe  
Chimes/Strobe  
Chimes/Strobe  
Chimes/Strobe  
Horn  
AMSECO  
SCM24W-153075  
SCM24W-75110  
SCM24C-3075110  
SCM24C-177  
H24W  
H24R  
Horn  
151209  
A-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
IntelliKnight 5820XL Installation Manual  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Model  
Audio  
Visual  
Type  
446  
476  
477  
Vibrating Bell  
Vibrating Bell  
Single Stroke Bell  
Strobe  
2700 -M. -R, -T, -Y, -Z  
2701 Series  
2705 Series  
2820  
Strobe  
Strobe  
Snyc Temporal Horn/Strobe  
Snyc Temporal Horn/Strobe  
Horn Strobe  
2821  
2824  
5333  
Multi-Tone Horn)  
5336  
Multi-Tone Horn/Strobe  
Multi-Tone Horn/Strobe  
Multi-Tone Horn/Strobe  
Single Tone Horn/Strobe  
Electronic Horn with Strobe  
Electronic Horn with Strobe  
Single Tone Horn/Strobe  
8-Tone Horn/Strobe  
5337  
5338  
5343  
5346  
Faraday  
5347  
5348  
5373  
6321  
Sync Mini Horn/Strobe  
Mini Horn/Sync Strobe  
8-Tone Electronic Signal/Strobe  
8-Tone Horn/Strobe  
6322  
6380  
5376  
5377  
8-Tone Horn/Strobe  
5378  
8-Tone Horn/Strobe  
5383  
8-Tone Horn/Strobe with Sync Strobe  
8-Tone Horn/Strobe with Sync Strobe  
8-Tone Horn/Strobe with Sync Strobe  
8-Tone Horn/Strobe with Sync Strobe  
Single Gang Sync Strobe  
Strobe  
5386  
5387  
5388  
5508  
5509  
A-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compatible Devices  
Table A-1: Compatible Notification Appliances  
Model Audio Visual  
Manufacturer  
Type  
5510  
5511  
5512  
5516  
5517  
5518  
5519  
5521  
5522  
6120  
6140  
6223  
6226  
6227  
6228  
6243  
6244  
6245  
6246  
6247  
6248  
6300  
6301  
6302  
6310  
6311  
6312  
Strobe  
Strobe  
Strobe  
Strobe  
Strobe  
Strobe  
Strobe  
Faraday  
4” Square Sync Strobe  
4” Square Sync Strobe  
Horn  
Horn  
Horn  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Electron-Mechanical Horn  
Electron-Mechanical Horn  
Electron-Mechanical Horn  
Electron-Mechanical Horn/Strobe  
Electron-Mechanical Horn/Strobe  
Electron-Mechanical Horn/Strobe  
Mini-Horn  
Mini-Horn  
Mini-Horn  
Mini-Horn/Strobe  
Mini-Horn/Strobe  
Mini-Horn/Strobe  
6314 Series -M, -R, -T, -Y, -Z  
6320  
Strobe  
Sync Mini Horn/Strobe  
151209  
A-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Table A-1: Compatible Notification Appliances  
Model Audio Visual  
Manufacturer  
Type  
S2415-FC  
S241575-FC  
S2430-FC  
130-3117C  
130-3147C  
BLV-6  
Strobe  
Strobe  
Strobe  
Mini Horn  
Mini Horn  
Vibrating Bell  
Vibrating Bell  
Vibrating Chime  
Horn  
BLV-10  
FCI  
BLVCH  
H12/24-FC  
H12/24W-FC  
H12/24K-FC  
HC12/24-FC  
HC12/24W-FC  
HC12/24K-FC  
P2415-FC  
Horn  
Horn  
Horn  
Horn  
Horn  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Strobe  
FCI  
P2415W-FC  
P2415K-FC  
P241575-FC  
P241575W-FC  
P241575F-FC  
P241575K-FC  
P2430-FC  
P2430W-FC  
P2430K-FC  
P2475-FC  
P2475W-FC  
P2475K-FC  
P24110-FC  
P24110W-FC  
P24110K-FC  
S2430W-FC  
S2430K-FC  
S2475-FC  
Strobe  
Strobe  
S2475W-FC  
S2475K-FC  
S24110-FC  
S24110W-FC  
S24110K-FC  
450  
Strobe  
Strobe  
Strobe  
Strobe  
Strobe  
Horn  
Federal Signal  
VALS  
Horn/Strobe  
A-4  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compatible Devices  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Model  
Audio  
Visual  
Type  
GEC-24-15  
GEC-24-30  
GEC-24-60  
GEC-24-75  
Horn/Strobes  
Horn/Strobes  
Horn/Strobes  
Horn/Strobes  
Horn/Strobes  
Horn/Strobe  
Horn/Strobe  
Gentex  
GEC-24-177  
GEC-24-110  
GEC-24-15/75  
GX91  
MiniHorn Steady Tone  
GX93  
MiniHorn Temporal Tone  
HG124  
Horn  
Gentex  
HS24-15  
Horn/Strobe  
HS24-30  
Horn/Strobe  
HS24-60  
Horn/Strobe  
HS24-75  
Horn/Strobe  
HS24-110  
HS24-1575  
GCC24  
Horn/Strobe  
Horn/Strobe  
Multi Candella Horn/Strobe Ceiling Mount  
GCCR24  
Multi Candella Horn/Strobe Ceiling Mount  
GCS24  
Multi Candella Strobe Ceiling Mount  
GCSR24  
Multi Candella Strobe Ceiling Mount  
GECR-24  
GES24-15  
GES24-30  
GES24-60  
GES24-75  
GES24-110  
GES24-15/75  
GES24-177  
GES3-24  
Multi Candella Horn/Strobe  
Strobes  
Strobes  
Strobes  
Strobes  
Strobes  
Strobes  
Strobes  
Multi Candella Strobe  
Multi Candella Strobe  
Horn  
GESR-24  
GEH-24  
ST24-30  
Strobe  
ST24-60  
Strobe  
ST24-75  
Strobe  
ST24-110  
ST24-1575  
WGEC24-75W  
WGES24-75W  
WGMS-24-X  
Strobe  
Strobe  
Weatherproof Horn/Strobe  
Weatherproof Strobe  
Horn/Strobe  
151209  
A-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Model  
Audio  
Visual  
Type  
CHR  
Chime  
Chime  
CHW  
CHSR  
CHSW  
HR  
2-Wire Chime/Strobe  
2-Wire Chime/Strobe  
Horn  
HW  
Horn  
HRK  
Horn  
P2R  
2-Wire Horn/Strobe  
P2R-P  
PC2R  
2-Wire Horn/Strobe  
2-Wire Horn/Strobe  
PC2R-P  
P2RH  
2-Wire Horn/Strobe  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe  
P2RH-P  
PC2RH  
PC2RH-P  
P2W  
System Sensor  
P2W-P  
PC2W  
PC2W-P  
P2WH  
P2WH-P  
PC2WH  
PC2WH-P  
P2RK  
2-Wire Horn/Strobe  
2-Wire Horn/Strobe  
2-Wire Horn/Strobe  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe  
PC2RK  
P2RHK  
PC2RHK  
P4R  
2-Wire Horn/Strobe  
2-Wire Horn/Strobe High Candela  
2-Wire Horn/Strobe High Candela  
4-Wire Horn/Strobe  
PC4R  
4-Wire Horn/Strobe  
P4RH  
4-Wire Horn/Strobe High Candela  
4-Wire Horn/Strobe  
P4W  
A-6  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compatible Devices  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Model  
Audio  
Visual  
Type  
4-Wire Horn/Strobe  
PC4W  
P4WH  
PC4WH  
P4RK  
PC4RK  
P4RHK  
PC4RHK  
PC4RH  
SR  
System Sensor  
4-Wire Horn/Strobe High Candela  
4-Wire Horn/Strobe High Candela  
4-Wire Horn/Strobe  
4-Wire Horn/Strobe  
4-Wire Horn/Strobe High Candela  
4-Wire Horn/Strobe High Candela  
4-Wire Horn/Strobe High Candela  
Strobe  
SR-P  
Strobe  
SCR  
Strobe  
SCR-P  
SRH  
Strobe  
Strobe High Candela  
Strobe High Candela  
Strobe High Candela  
Strobe High Candela  
Strobe  
SRH-P  
SCRH  
SCRH-P  
SW  
SW-P  
Strobe  
SCW  
Strobe  
SCW-P  
SWH  
Strobe  
Strobe High Candela  
Strobe High Candela  
Strobe High Candela  
Strobe High Candela  
Strobe  
SWH-P  
SCWH  
SCWH-P  
SRK  
SCRK  
SRHK  
SCRHK  
Strobe  
Strobe High Candela  
Strobe High Candela  
151209  
A-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Model  
Audio  
Visual  
Type  
AH-12  
Horn  
Wheelock  
AH-24  
Horn  
AH-12WP  
AH-24WP  
Horn Weatherproof  
Horn Weatherproof  
AMT-241575W  
AMT-24MCW  
AMT-241575W-NYC  
AMT-12/24  
Multi-Tone Horn Strobe  
Mutli-Tone Horn Strobe  
Multi-Tone Horn Strobe  
Multi-tone Horn  
Multi-tone Horn  
Horn/Strobe  
AMT-12/24 NYC  
AS-121575W  
NH-12/24  
Horn  
AS-241575W  
AS-24MCC  
Horn/Strobe  
Horn/Strobe  
AS-24MCCH  
AS-24MCW  
Horn/Strobe  
Horn/Strobe  
AS-24MCWH  
ASWP-2475W  
ASWP-2475C  
ASWP-24MCWH  
ASWP-24MCCH  
CH-70  
Horn/Strobe  
Horn/Strobe Weatherproof  
Horn/Strobe Weatherproof  
Horn/Strobe  
Horn/Strobe  
Chime  
CH-90  
Chime  
CH70-241575W  
CH70-24MCW  
CH70-24MCWH  
CH90-24MCC  
Chime/Strobe  
Chime/Strobe  
Chime/Strobe  
Chime/Strobe  
A-8  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compatible Devices  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Wheelock  
Con’t  
Model  
CH90-24MCCH  
Audio  
Visual  
Type  
Chime/Strobe  
Horn  
HS-24  
HS4-241575W  
HS4-24MCW  
HS4-24MCWH  
HS4-24MCC  
MIZ-24S  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
Mini Horn Strobe  
MT-121575W  
MT-241575W  
MT-24MCW  
MTWP-2475W  
MTWP-2475C  
MTG-121575W  
MTR-121575W  
MTWPA-2475W  
MTWPB-2475W  
MTWPG-2475W  
MTWPR-2475W  
MTWPA-24MCCH  
ZNH  
MultitoneHorn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Multitone Horn Strobe  
Horn  
NS-121575W  
NS-241575W  
NS-24MCW  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
NS-24MCC  
Horn/Strobe  
NS-24MCCH  
ZNS-MCW  
Horn/Strobe  
Horn/Strobe  
ZNS-MCWH  
ZNS-24MCC  
ZNS-24MCCH  
Horn/Strobe  
Horn/Strobe  
Horn/Strobe  
151209  
A-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Model  
RSS-121575W  
Audio  
Visual  
Type  
Strobe  
Wheelock  
Con’t  
RSS-241575W  
RSS-24MCC  
Strobe  
Strobe  
RSS-24MCCR  
RSS-24MCCH  
RSS-24MCCHR  
RSS-24MCW  
Strobe  
Strobe  
Strobe  
Strobe  
RSS-24MCWH  
RSSP-121575W  
RSSP-241575W  
RSSR-2415W  
Strobe  
Strobe  
Strobe  
Strobe  
RSSR-2415C  
Strobe  
RSSR-2475W  
Strobe  
RSSR-2475C  
Strobe  
RSSR-24110C  
RSSA-24110W  
RSSB-24110W  
RSSG-24110W  
RSSR-24110W  
RSSA-24MCC  
RSSB-24MCC  
RSSG-24MCC  
RSSR-24MCC  
RSSWPA-2475W  
RSSWPA-24MCCH  
RSSWPG-24MCCH  
RSSWPR-24MCCH  
RSSWP-2475W  
RSSWP-2475C  
Strobe  
Strobe  
Strobe  
Strobe  
Strobe  
Multi-Cd Strobe  
Multi-Cd Strobe  
Multi-Cd Strobe  
Multi-Cd Strobe  
Strobe Weatherproof  
Strobe Weatherproof  
Strobe Weatherproof  
Strobe Weatherproof  
Strobe Weatherproof  
Strobe Weatherproof  
A-10  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compatible Devices  
Table A-1: Compatible Notification Appliances  
Manufacturer  
Wheelock  
con’t  
Model  
Audio  
Visual  
Type  
Strobe Weatherproof  
RSSWP-24MCWH  
ZRS-MCWH  
ZRS-24MCC  
ZRS-24MCCH  
MB-G6-24  
MB-G10-24  
MB-G6-12  
MB-G10-12  
MIZ-24-R  
MT-12/24-R  
MT4-12/24  
ZRS-MCW  
MTWPR-24MCCH  
NH-12/24R  
HSR  
Strobe  
Strobe  
Strobe  
Motor Bell  
Motor Bell  
Motor Bell  
Motor Bell  
Mini-Horn  
Multitone Horn  
Multitone Horn  
Strobe  
Multitone Horn Strobe  
Horn  
Horn/Strobe  
Horn/Strobe  
Strobe  
HSW  
STR  
STW  
Strobe  
HNR  
Horn  
HNW  
Horn  
151209  
A-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
A.2 Two-Wire Smoke Detectors  
Table A-2 lists two-wire smoke detectors that are compatible with the fire control panel. The  
table is organized by manufacturer. The columns show the number of detectors per loop that  
can be used.  
Table 1-1:  
5820XL  
24H  
Identifier  
18.5–27.4 VDC  
Operating Voltage Range  
Note: The maximum number of smoke detectors per zone is determined by both the current draw and the imped-  
ance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.  
Do not mix different models of detectors on any zone; false alarms could occur.  
Do not mix detectors of different models unless the system is specifically intended to be installed in that  
configuration.  
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum  
reset time of the smoke detector.  
Table A-2: Compatible Two-Wire Smoke Detectors  
Model Name or Number  
(Base model name or number  
in parentheses.)  
Compatibility ID  
Head Base  
Manufacturer  
# per Loop  
55000-350 (45681-200)  
55000-250 (45681-200)  
55000-225  
55000-350  
55000-250  
55000-225  
55000-226  
55000-227  
55000-325  
55000-328  
55000-326  
55000-327  
45681-200  
24 / loop  
24 / loop  
Apollo  
Apollo  
45681-200  
45681-255, 256,  
15 / loop for  
Ion Detectors  
55000-226  
55000-227  
15 / loop for  
Photo Electric  
Detectors  
45681-200, 220,  
230, 232, 251,252  
55000-325  
55000-328  
55000-326  
55000-327  
A-12  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Compatible Devices  
Table A-2: Compatible Two-Wire Smoke Detectors  
Model Name or Number  
(Base model name or number  
in parentheses.)  
Compatibility ID  
Head Base  
Manufacturer  
# per Loop  
429C (S10A)  
N/A  
N/A  
N/A  
N/A  
S10  
S10A  
30 / loop  
30 / loop  
30 / loop  
30 / loop  
40 / loop  
40 / loop  
40 / loop  
40 / loop  
40 / loop  
40 / loop  
40 / loop  
25 / loop  
25 / loop  
25 / loop  
25 / loop  
30 / loop  
30 / loop  
17 / loop  
17 / loop  
25 / loop  
429CRT (S11A)  
429CST (S11A)  
429CT (S10A)  
S11A  
S11A  
S10A  
609U01-11  
S00  
609U02-11  
S10  
S00/S03  
S00/S03  
S00/S03  
S00/S03  
S00/S03  
S00/S03  
S10A  
611U (601U or 602U)  
611UD (601U or 602U)  
611UT (601U or 602U)  
612U (601U or 602U)  
612UD (601U or 602U)  
711U (701E or 701U)  
712U (701E or 701U)  
713-5U (702E or 701U)  
713-6U (702E or 701U)  
721-U (S10A)  
S10  
S10  
ESL  
S10  
S10  
S10  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
FDT1  
FDT1  
HD-3  
S10A  
S10A  
S10A  
S10A  
721-UT (S10A)  
525  
S10A  
N/A  
Falcon  
525T  
N/A  
SIH-24F (HS-224D OR HSD-  
224)  
HB-5  
Hochiki  
SLK-24F (HS-224D)  
SLK-24FH (HS-224D)  
HD-3  
HD-3  
HB-5  
HB-5  
25 / loop  
25 / loop  
151209  
A-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliKnight 5820XL Installation Manual  
Table A-2: Compatible Two-Wire Smoke Detectors  
Model Name or Number Compatibility ID  
Manufacturer  
(Base model name or number  
in parentheses.)  
# per Loop  
Head  
Base  
1400  
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
N/A  
A
20 / loop  
20 / loop  
20 / loop  
20 / loop  
16 / loop  
16 / loop  
20 / loop  
20 / loop  
20 / loop  
20 / loop  
20 / loop  
20 / loop  
20 / loop  
20 / loop  
20 / loop  
20 / loop  
20 / loop  
16 / loop  
16 / loop  
16 / loop  
1451 (B401B)  
2100  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
2100T  
2151 (B401)  
2151T (B401)  
2300T  
2300  
2300TB  
2400  
System Sensor  
2400 (DH400)  
2400AIT  
2400AT  
2400TH  
2451 (B401B)  
2451DH (DH 400)  
2451TH (B401B)  
2W-B  
2WT-B  
2WTR-B  
A-14  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B  
Special Characters Lists  
This section contains tables of programmable characters that may be used for device, module,  
and zone names or phone numbers.  
B.1  
Characters used for Naming  
Table B-1 list the available character and their associated numeric designator. When  
programming these numbers can be entered as a short cut to using the up or down arrow keys,  
to select characters when naming a point or zone.  
Table B-1: Character Table  
000  
004  
008  
012  
016  
020  
024  
028  
032  
036  
040  
044  
048  
052  
056  
060  
064  
068  
A
E
I
001  
005  
009  
013  
017  
021  
025  
029  
033  
037  
041  
045  
049  
053  
057  
061  
065  
069  
B
F
J
002  
006  
010  
014  
018  
022  
026  
030  
034  
038  
042  
046  
050  
054  
058  
062  
066  
070  
C
G
K
O
S
W
a
003  
007  
011  
015  
019  
023  
027  
031  
035  
039  
043  
047  
051  
055  
059  
063  
067  
D
H
L
P
T
X
b
f
M
Q
U
Y
c
N
R
V
Z
d
h
l
e
g
i
j
k
m
q
n
r
o
p
t
s
u
v
z
w
x
0
4
8
_
*
y
1
2
6
:
3
7
5
9
-
.
,
&
#
151209  
B-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
IntelliKnight 5820XL Installation Manual  
B-2  
151209  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Silent Knight Fire Product Warranty and Return Policy  
General Terms and Conditions  
All new fire products manufactured by Silent Knight have a limited warranty period of  
36 months from the date of manufacture against defects in materials and workmanship.  
See limited warranty statement for details.  
This limited warranty does not apply to those products that are damaged due to misuse,  
abuse, negligence, exposer to adverse environmental conditions, or have been modified in  
any manner whatsoever.  
Repair and RA Procedure  
All products that are returned to Silent Knight for credit or repair require a RMA (Return  
Authorization) number. Call Silent Knight Customer Service at 800-328-0103 or  
203-484-7161 between 8:00 A.M. and 5:00 P.M. EST, Monday through Friday to obtain a  
return authorization number.  
Silent Knight Technical Support is available at 800-446-6444 between 8:00 A.M. and  
5:00 P.M. CST, Monday through Friday.  
All returns for credit are subject to inspection and testing at the factory before actual deter-  
mination is made to allow credit.  
RMA number must be prominently displayed on the outside of the shipping box. See  
return address example under Advanced Replacement Policy.  
Include a packing slip that has the RMA number, a content list, and a detailed description  
of the problem should be included with each return.  
All products returned to Silent Knight must be sent freight pre-paid. After product is pro-  
cessed, Silent Knight will pay for shipping product back to customer via UPS ground.  
Return the Silent Knight product circuit board only. Products that are returned in cabinets  
will be charged an additional $50 to cover the extra shipping and handling costs over  
board only returns. Do not return batteries. Silent Knight has the authority to determine  
if a product is repairable. Products that are deemed un-repairable will be returned to the  
customer.  
Product that is returned that has a board date code more than 36 months from date of man-  
ufacture will be repaired and the customer will be assessed the standard Silent Knight  
repair charge for that model.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Advanced Replacement Policy  
Silent Knight offers an option of advance replacement for fire product printed circuit  
boards that fail during the first 6 months of the warranty period. These items must be  
returned with transportation charges prepaid and must be accompanied by a return  
authorization.  
For advance replacement of a defective board contact your local Silent Knight Distributor  
or call Silent Knight at 203-484-7161 to obtain a RMA (Return Authorization) number  
and request advanced replacement,  
A new or refurbished board will be shipped to the customer. The customer will initially be  
billed for the replacement board but a credit will be issued after the repairable board is  
received at Silent Knight. All returned products must comply with the guidelines  
described under “General Terms and Conditions”.  
The defective board must be returned within 30 days of shipment of replacement board for  
customer to receive credit. No credit will be issued if the returned board was damaged due  
to misuse or abuse.  
Repairs and returns should be sent to:  
Silent Knight / Honeywell  
Attn: Repair Department  
12 Clintonville Road  
Northford, CT 06472  
USA  
RMA Number:___________________  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited Warranty  
SILENT KNIGHT warrants products manufactured by it to be free from defects in materials and  
workmanship for thirty-six (36) months from the date of manufacture, under normal use and service.  
Products are date stamped at time of manufacture. The sole and exclusive obligation of SILENT  
KNIGHT is to repair or replace, at its option, free of charge for parts and labor, any part that is  
defective in materials or workmanship under normal use and service. All returns for credit are  
subject to inspection and testing at the factory before actual determination is made to allow  
credit. SILENT KNIGHT does not warrant products not manufactured by it, but assigns to the  
purchaser any warranty extended by the manufacturer of such products. This warranty is void if the  
product is altered or repaired by anyone other than SILENT KNIGHT or as expressly authorized by  
SILENT KNIGHT in writing, or is serviced by anyone other than SILENT KNIGHT or its authorized  
distributors. This warranty is also void if there is a failure to maintain the products and systems in  
which they operate in a proper and workable manner. In case of defect, secure a Return Material  
Authorization form from our Return Authorization Department.  
This writing constitutes the only warranty made by SILENT KNIGHT, with respect to its  
products. SILENT KNIGHT, does not represent that its products will prevent any loss by  
fire or otherwise, or that its products will in all cases provide the protection for which they  
are installed or intended. Buyer acknowledges that SILENT KNIGHT is not an insurer and  
assumes no risk for loss or damages or the cost of any inconvenience, transportation  
damage, misuse, abuse, accident or similar incident.  
SILENT KNIGHT GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF  
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE  
WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO  
CIRCUMSTANCES SHALL SILENT KNIGHT BE LIABLE FOR ANY LOSS OF OR  
DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING  
OUT OF THE USE OF, OR INABILITY TO USE SILENT KNIGHT ALARM’S PRODUCTS.  
FURTHERMORE, SILENT KNIGHT SHALL NOT BE LIABLE FOR ANY PERSONAL  
INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,  
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS  
This warranty replaces all previous warranties and is the only warranty made by SILENT  
KNIGHT. No increase or alteration, written or verbal, of the obligation of this warranty is  
authorized.  
“SILENT KNIGHT” is a registered trademark.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Inc Pressure Washer 800 094 User Manual
Grizzly Guitar H8069 User Manual
Hans Grohe Plumbing Product 04066XX0 User Manual
Hasbro Motorized Toy Car 22613 User Manual
Healthrider Home Gym 831285770 User Manual
Honeywell Marine Radio MX7 Tecton User Manual
Hotpoint Microwave Oven HXC68AT User Manual
Hotpoint Refrigerator CTX18EACAA User Manual
HP Hewlett Packard Hearing Aid RM500SL User Manual
HP Hewlett Packard Server QW915A User Manual