INTELLIKNIGHT®
5820XL
Addressable Fire System
Installation and
Operations Manual
Part Number 151209 Rev R
ECN 09- 570 08/27/09
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Procedure
Adherence to the following will aid in problem-free installation with long-term reliability:
Installation Precautions - Adherence to the following will aid in problem-free installation
with long-term reliability: WARNING - Several different sources of power can be connected
to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit
and associated equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt to install, service, or operate
this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after
Software Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or change in site-specific
software. Re-acceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or wiring. All
components, circuits, system operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified. This
system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or
humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful
life of the system's standby batteries and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it is recommended that this system
and its peripherals be installed in an environment with a normal room temperature of 15-27º
C/60-80º F. Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged
when subjected to lightning induced transients. Although no system is completely immune
from lightning transients and interference, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical Services Department if any problems are
anticipated or encountered. Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits. Remove all electronic
assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible,
make all cable entries from the sides or rear. Before making modifications, verify that they
will not interfere with battery, transformer, or printed circuit board location. Do not tighten
screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with screw terminal removal. Silent Knight
fire alarm control panels contain static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic assemblies removed from the
unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated equipment.
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Manual
FACP operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a
substitute for fire insurance! An automatic fire alarm system - typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm
control with remote notification capability - can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or loss of life
resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke
detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in
walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire
on another level or floor of a building. A second floor detector, for example, may not sense a
first floor or basement fire. Furthermore, all types of smoke detectors, including ionization
and photoelectric types, have sensing limitations. No type of smoke detector can sense every
kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical circuits, children
playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and
in rooms used by the system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are not so located, a developing fire
may damage the alarm system, crippling its ability to report a fire. Audible warning devices
such as bells may not alert people if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building. A fire alarm system will not
operate without any electrical power. If AC power fails, the system will operate from standby
batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist. Equipment used in the system
may not be technically compatible with the control. It is essential to use only equipment listed
for service with your control panel. Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service or temporarily disabled. The
most common cause of fire alarm malfunctions, however, is inadequate maintenance. All
devices and system wiring should be tested and maintained by professional fire alarm
installers following written procedures supplied with each device. System inspection and
testing should be scheduled monthly or as required by National and/or local fire codes.
Adequate written records of all inspections should be kept.
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Section 1
Introduction .............................................................................................................................................. 1-1
1.1 Overview of Basic System ....................................................................................................................... 1-1
1.1.1 Hardware Features ............................................................................................................................ 1-1
1.1.2 Software Features ............................................................................................................................. 1-2
1.2 About this Manual .................................................................................................................................... 1-2
1.2.1 Terms Used in this Manual ............................................................................................................... 1-2
1.3 Compatible Products ................................................................................................................................ 1-3
1.4 How to Contact Silent Knight .................................................................................................................. 1-4
Requirements and recommendations for proper use of fire alarm systems including smoke
detectors and other fire alarm devices: .................................................................................. 1-7
Section 2
2.1 Federal Communications Commission (FCC) ......................................................................................... 2-1
2.2 Underwriters Laboratories (UL) .............................................................................................................. 2-2
2.2.1 Requirements for All Installations .................................................................................................... 2-2
2.2.2 Requirements for Central Station Fire Alarm Systems .................................................................... 2-3
2.2.3 Requirements for Local Protected Fire Alarm Systems ................................................................... 2-3
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems - Digital Alarm Communicator
Transmitter (DACT) 2-3
Section 3
Before You Begin Installing ............................................................................................... 3-1
3.1 What’s in the Box? ................................................................................................................................... 3-1
3.2 Environmental Specifications .................................................................................................................. 3-1
3.3 Electrical Specifications ........................................................................................................................... 3-2
3.4 Wiring Specifications ............................................................................................................................... 3-3
3.5 Board Assembly Diagram ........................................................................................................................ 3-5
3.6 Calculating Current Draw and Standby Battery ...................................................................................... 3-6
3.6.1 Current Draw Worksheet Requirements ........................................................................................... 3-6
3.6.2 Current Draw Worksheet for SK SLC Devices ................................................................................ 3-7
3.6.3 Current Draw Worksheet for Hochiki SLC Devices ...................................................................... 3-10
3.6.4 Maximum Battery Standby Load .................................................................................................... 3-12
151209
1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Section 4
Control Panel Installation ...................................................................................................... 4-1
4.1 Mounting the Control Panel Cabinet ....................................................................................................... 4-1
4.1.1 Preventing Water Damage ................................................................................................................ 4-1
4.1.2 Removing the 5820XL Assembly from the Housing ....................................................................... 4-1
4.2 AC Connection ......................................................................................................................................... 4-2
4.3 Battery Connection .................................................................................................................................. 4-3
4.3.1 RBB Accessory Cabinet ................................................................................................................... 4-4
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries ............................................................. 4-4
4.4 SBUS Wiring ........................................................................................................................................... 4-6
4.4.1 Calculating Wiring distance for SBUS modules .............................................................................. 4-6
Wiring Distance calculation example: ................................................................................... 4-8
4.4.2 Wiring Configurations ...................................................................................................................... 4-9
4.5 Remote Annunciator 5860 Installation .................................................................................................. 4-10
4.5.1 Mounting the 5860 .......................................................................................................................... 4-11
4.5.1.1 Flush Mounting .................................................................................................................... 4-12
Flush Mounting with an Electrical Box ............................................................................... 4-13
Flush Mounting Steps .......................................................................................................... 4-13
4.5.1.2 Surface Mounting ................................................................................................................. 4-14
4.5.2 Model 5860 Connection to the Panel .............................................................................................. 4-15
4.6 5815XL Installation ............................................................................................................................... 4-16
4.6.1 5815XL Connection to the Panel .................................................................................................... 4-17
4.7 5824 Serial/Parallel Interface Module Installation ................................................................................ 4-18
4.7.1 Selecting 5824 Options ................................................................................................................... 4-19
4.8 5880 LED I/O Module ........................................................................................................................... 4-21
4.8.1 5880 Board Layout ......................................................................................................................... 4-21
4.8.2 FACP Connection ........................................................................................................................... 4-22
4.8.3 LED Wiring .................................................................................................................................... 4-23
4.8.4 Dry Contact Wiring ........................................................................................................................ 4-24
4.9 5865-3 / 5865-4 LED Annunciator Installation ..................................................................................... 4-25
4.9.1 FACP Connection ........................................................................................................................... 4-26
4.9.2 5865 Mounting ................................................................................................................................ 4-27
4.10 Configuring Modules ............................................................................................................................. 4-28
4.11 Telephone Connection ........................................................................................................................... 4-29
4.12 5211 Ground Start Relay ........................................................................................................................ 4-29
™
4.13 Flexputs I/O Circuits ........................................................................................................................... 4-30
4.13.1 Conventional Notification Appliance ............................................................................................. 4-30
4.13.1.1 Regulated Class B Notification Wiring ............................................................................... 4-30
4.13.1.2 Class A Notification Wiring ................................................................................................ 4-32
4.13.2.1 Class B Inputs ...................................................................................................................... 4-33
4.13.3.1 Installing 2-Wire Class B Smoke Detectors ........................................................................ 4-35
4.13.4.1 Installing a Class B 4-Wire Smoke Detector ....................................................................... 4-37
4.13.4.2 Installing 4-Wire Class A Smoke Detectors ........................................................................ 4-38
2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
4.13.5.2 Constant Power .................................................................................................................... 4-39
4.14 On-Board Relays (Conventional) ........................................................................................................... 4-40
4.14.1 Trouble Relay ................................................................................................................................. 4-40
4.14.2 Programmable Relays ..................................................................................................................... 4-40
4.15 Remote Station Applications ................................................................................................................. 4-41
4.15.5 Using a MR-201/T Control Relay From Air Products ................................................................... 4-46
Section 5
Hochiki and SK SLC Device Installation ........................................................... 5-1
5.1 List of SK SLC Devices ........................................................................................................................... 5-1
5.2 List of Hochiki SLC Devices ................................................................................................................... 5-2
5.3 Maximum Number of Devices ................................................................................................................. 5-3
5.4 Wiring Requirements for SLC Devices ................................................................................................... 5-3
5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration ......................................................................... 5-3
5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration .................................................................. 5-5
5.5 Wiring SK SLC Detectors ........................................................................................................................ 5-6
5.6 Addressing SK SLC Devices ................................................................................................................... 5-7
5.7 Hochiki Detector Installation ................................................................................................................... 5-8
5.7.1 Wiring Hochiki Detectors ................................................................................................................. 5-8
5.8 Addressing Hochiki Devices .................................................................................................................... 5-9
5.8.1 SD505-APS, SD505-AHS, & SD505-AIS ....................................................................................... 5-9
5.8.2 SLC Devices with Dip Switches ..................................................................................................... 5-10
Section 6
Programming Overview ........................................................................................................... 6-1
6.1 JumpStart Autoprogramming ................................................................................................................... 6-1
6.1.1 Input Points ....................................................................................................................................... 6-2
6.1.2 Output Points .................................................................................................................................... 6-2
6.1.3 Running JumpStart ........................................................................................................................... 6-2
6.2 Mapping Overview .................................................................................................................................. 6-4
6.2.1 Input Point Mapping ......................................................................................................................... 6-5
6.2.2 Output Circuit Mapping .................................................................................................................... 6-6
6.2.3 Zone Event Mapping ........................................................................................................................ 6-7
6.2.4 Mapping LED Points ........................................................................................................................ 6-9
6.3 Programming Using the 5660 Silent Knight Software Suite ................................................................. 6-10
6.4 Programming Using an Annunciator ..................................................................................................... 6-10
151209
3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
6.4.1 Entering & Exiting the Program Menu ........................................................................................... 6-11
6.4.1.1 Moving through the Menus .................................................................................................. 6-11
6.4.1.2 Selecting Options and Entering Data ................................................................................... 6-12
6.4.1.3 Editing Keys ......................................................................................................................... 6-12
6.5 Programming Menu Quick Reference ................................................................................................... 6-13
Section 7
Programming ......................................................................................................................................... 7-1
7.1 UL 864 Programming Requirements ....................................................................................................... 7-1
7.2 SLC Family .............................................................................................................................................. 7-2
7.3 Modules .................................................................................................................................................... 7-2
7.3.1 Edit Modules ..................................................................................................................................... 7-3
7.3.1.1 Naming Modules .................................................................................................................... 7-3
7.3.1.2 Setting the 5815XL Wiring Class .......................................................................................... 7-4
7.3.2 Adding a Module .............................................................................................................................. 7-4
7.3.3 Deleting a Module ............................................................................................................................ 7-5
7.4 Zone ......................................................................................................................................................... 7-5
7.4.1 Edit Zone ........................................................................................................................................... 7-5
7.4.1.1 Edit Zone Name ..................................................................................................................... 7-6
7.4.1.2 Edit Zone Properties ............................................................................................................... 7-6
Heat Temperature Setting ...................................................................................................... 7-7
7.4.1.3 Zone Outputs .......................................................................................................................... 7-8
7.4.1.4 Cadence Patterns .................................................................................................................. 7-11
7.4.1.5 Zone Accessory Options ...................................................................................................... 7-11
7.4.2 Add Zone ........................................................................................................................................ 7-12
7.4.3 Delete Zone ..................................................................................................................................... 7-12
7.4.4 View Zone Points ............................................................................................................................ 7-13
7.5 Group ..................................................................................................................................................... 7-14
7.5.1 Edit Group ....................................................................................................................................... 7-14
7.5.1.1 Edit Group Name ................................................................................................................. 7-14
7.5.1.2 Edit Group Properties ........................................................................................................... 7-15
7.5.2 Add Group ...................................................................................................................................... 7-17
7.5.3 Delete Group ................................................................................................................................... 7-17
7.5.4 View Group Points .......................................................................................................................... 7-18
7.5.5 Edit Output Group Templates ......................................................................................................... 7-18
7.6 Point ....................................................................................................................................................... 7-19
7.6.1 Point Programming For 5815XL Module ....................................................................................... 7-19
7.6.2 Point Programming For Internal or External Power Module (5895XL) ........................................ 7-24
4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
7.6.3.1 Assigning a Name to Points ................................................................................................. 7-27
7.7 System Options ...................................................................................................................................... 7-27
7.7.1 Reporting Account .......................................................................................................................... 7-28
7.7.1.1 Edit Accounts ....................................................................................................................... 7-29
Select Account (ID) ............................................................................................................. 7-29
Edit Account Number .......................................................................................................... 7-29
Select Reporting Format ...................................................................................................... 7-29
Selecting Primary and Secondary Phone Lines ................................................................... 7-30
7.7.1.2 Auto Test Time .................................................................................................................... 7-32
7.7.2 Phone Lines ..................................................................................................................................... 7-32
7.7.2.1 Dialing Prefix ....................................................................................................................... 7-33
7.7.2.2 Number of Answer Rings .................................................................................................... 7-34
7.7.2.3 Dial Option (TouchTone or Pulse) ....................................................................................... 7-34
7.7.2.4 Rotary Format ...................................................................................................................... 7-34
7.7.2.5 Line Monitor ........................................................................................................................ 7-34
7.7.2.6 Ground Start Relay ............................................................................................................... 7-34
7.7.2.7 Answering Machine Bypass ................................................................................................. 7-35
7.7.3 Sys. Event Outputs .......................................................................................................................... 7-35
7.7.3.1 Trouble Events ..................................................................................................................... 7-36
7.7.3.2 System Alarm Cadence ........................................................................................................ 7-37
7.7.4 Miscellaneous Options 1 ................................................................................................................. 7-38
7.7.4.1 Water Flow Delay ................................................................................................................ 7-38
7.7.4.2 Low AC Report Delay ......................................................................................................... 7-40
7.7.4.3 Automatic Daylight Savings Adjustment ............................................................................ 7-40
7.7.4.4 Clock Display Format (AM/PM or Military) ....................................................................... 7-40
7.7.4.5 Change AC Line Frequency ................................................................................................. 7-40
7.7.5 Miscellaneous Options 2 ................................................................................................................. 7-41
7.7.5.1 Synchronize Strobes Active During Silence ........................................................................ 7-41
7.7.5.2 Auto Display Oldest Event .................................................................................................. 7-41
7.7.5.3 Report by Zone or by Point .................................................................................................. 7-41
7.7.6 Miscellaneous Options 3 ................................................................................................................. 7-42
7.7.6.1 Alarm Verification Time ...................................................................................................... 7-42
7.7.6.2 Plex Door Option ................................................................................................................. 7-42
7.7.6.3 Daylight Saving Time Start and End ................................................................................... 7-43
7.7.7 Edit Banner Message ...................................................................................................................... 7-44
7.8 JumpStart Autoprogramming ................................................................................................................. 7-45
7.9 Computer Account ................................................................................................................................. 7-46
151209
5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.10 Access Codes ......................................................................................................................................... 7-47
7.10.1.1 Edit Name ............................................................................................................................ 7-48
Section 8
System Operation ............................................................................................................................ 8-1
8.1 User and Installer Default Codes ............................................................................................................. 8-1
8.2 Annunciator Description .......................................................................................................................... 8-1
8.2.1 LCD Displays ................................................................................................................................... 8-2
8.2.2 Banner ............................................................................................................................................... 8-2
8.3 Key Operation .......................................................................................................................................... 8-2
8.4 Menu System ............................................................................................................................................ 8-3
8.4.1 Main Menu Overview ....................................................................................................................... 8-3
8.4.2 Using the Menus ............................................................................................................................... 8-4
8.5 Basic Operation ........................................................................................................................................ 8-4
8.5.1 Setting Time and Date ...................................................................................................................... 8-4
8.5.2 Disable / Enable a Point .................................................................................................................... 8-4
8.5.3 Disable / Enable NACs by Group ..................................................................................................... 8-4
8.5.4 View Event History .......................................................................................................................... 8-5
8.5.4.1 To clear the event history ....................................................................................................... 8-5
8.5.5 Conduct a Fire Drill .......................................................................................................................... 8-5
8.5.6 Conduct an Indicator Test ................................................................................................................. 8-5
8.5.7 Conduct a Walk Test ......................................................................................................................... 8-6
8.5.8 Conduct a Dialer Test ....................................................................................................................... 8-6
8.5.9 Silence alarms or troubles ................................................................................................................. 8-7
8.5.11 Check Detector Through Point Status .............................................................................................. 8-7
8.5.12 View Status of a Point ...................................................................................................................... 8-8
8.5.13 View Alarms or Troubles ................................................................................................................. 8-8
8.5.15 Reset dialer ....................................................................................................................................... 8-8
8.5.16 Communicating with a Remote Computer ....................................................................................... 8-9
8.5.17 Working with a Printer ................................................................................................................... 8-10
8.6 Operation Mode Behavior ...................................................................................................................... 8-11
8.7 Releasing Operations ............................................................................................................................. 8-14
8.7.1 Single Interlock Zone Releasing ..................................................................................................... 8-15
Conditions Required for an Pre-Alert Output Activation .................................................... 8-15
Conditions required for an General Alarm and Release Output Activation ........................ 8-15
6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
8.7.2 Double Interlock Zone Releasing ................................................................................................... 8-16
Conditions Required for a Pre-Alert Output Activation ...................................................... 8-16
Conditions Required for a General Alarm Output Activation ............................................. 8-16
8.8 Smoke Alarm Verification ..................................................................................................................... 8-17
Section 9
Reporting ..................................................................................................................................................... 9-1
9.1 Receivers Compatible with the Control Panel ......................................................................................... 9-1
9.2 Reporting Formats Dialer Outputs ......................................................................................................... 9-1
Section 10
Testing and Troubleshooting ......................................................................................... 10-1
10.1 Troubleshooting ..................................................................................................................................... 10-1
10.2 Common Problems ................................................................................................................................. 10-1
10.2.1 Periodic Testing And Maintenance .................................................................................. 10-2
10.2.2 Event History .................................................................................................................................. 10-3
10.3 Built-in Troubleshooting and Testing Tools .......................................................................................... 10-4
10.3.1 SLC Device Locator ....................................................................................................................... 10-4
10.3.3 I/O Point Control ............................................................................................................................ 10-6
10.3.4 Earth Fault Resistance .................................................................................................................... 10-7
Section 11
Installation Records .................................................................................................................... 11-1
11.1 SLC Point Record .................................................................................................................................. 11-1
11.2 Conventional Output Point Record ........................................................................................................ 11-8
Appendix A
Compatible Devices ..................................................................................................................... A-1
A.1 Notification Appliances .......................................................................................................................... A-1
A.2 Two-Wire Smoke Detectors .................................................................................................................. A-12
Appendix B
Special Characters Lists .........................................................................................................B-1
B.1 Characters used for Naming .....................................................................................................................B-1
151209
7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1
Introduction
The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control
system that meets the requirements of UL 864.
1.1 Overview of Basic System
The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit boards
mounted to an aluminum housing.
1.1.1 Hardware Features
•
The IntelliKnight 5820XL panel has one signaling line circuit (SLC). Up to three
additional SLC loops can be added using the 5815XL SLC expander. The SLC(s) support
the SK series addressable detectors and modules or Hochiki protocol detectors and
modules.
•
•
Each SLC supports up to 99 detectors and 99 modules for a total of 396 detectors and 396
modules per 5820XL panel when using SK series devices. Alternatively, each SLC
supports up to 127 Hochiki devices for a total of 508 devices per 5820XL panel.
6.0A of output power is available through 6 sets of terminals for notification and auxiliary
applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total
output power for all 6 circuits must not exceed 6.0A).
•
•
•
•
•
•
•
Built-in dual phone line, digital alarm communicator/transmitter (DACT).
Reports events to central station by point or by zone.
UL Listed for pre-action and deluge releasing systems.
Dedicated Form C trouble relay and two general purpose Form C programmable relays.
Basic system operation can be performed using a key or a user code.
Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).
Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on
one control panel. See sections 4.8 and 4.9 for additional information on these models.
•
Printing of detector status, event history, and real time event log available through the
Model 5824 Serial/Parallel Printer Interface Module (sold separately).
•
•
Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.
Add 6 Flexput™ circuits with each 5895XL Intelligent Power Module (up to 8 5895XLs
per system). See note below.
•
Add 4 notification/auxiliary power circuits with each 5496 Intelligent Power Module. See
note below.
Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any
combination.
151209
1-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
1.1.2 Software Features
•
•
125 software zones, 250 output groups.
Advanced smoke detector features:
Automatic drift compensation
Maintenance alert region
Point status eliminates calibrated smoke test requirements for NFPA 72
•
•
•
“JumpStart” feature for easy programming
Non-volatile event history stores 1000 events
A choice of output patterns available for notification outputs, including ANSI 3.41
temporal signal
®
•
Built-in synchronization appliance support for AMSECO, Faraday, Gentex , System
®
®
Sensor , and Wheelock .
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for
the 5820XL. Please let us know if the manual does not meet your needs in any way. We value
your feedback!
1.2.1 Terms Used in this Manual
The following terminology is used with the IntelliKnight 5820XL system:
Table 1-1 Manual Terminology
Term
Description
SLC
Signaling line circuit
Module
The term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the 5820XL
panel itself and the built-in 5897 power supply. It also refers to any
(optional) 5815XL SLC expansion modules.
Input Point
An addressable sensing device, such as a smoke or heat detector or a contact
monitor device.
Input Zone
A protected area made up of input points.
Output Point
(or Output Circuit)
A notification point or circuit for notification appliances. Relay circuits and
auxiliary power circuits are also considered output points.
Group (or “Output Group”)
A group of output points. Operating characteristics are common to all
output points in the group.
Output (or “Cadence”) Pattern
Mapping
The pattern that the output will use, for example, Constant, March Code,
ANSI 3.41. Applies to zones and special system events. See Section 7.7.3.2
for additional information.
Mapping is the process of specifying which outputs are activated when
1-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
1.3 Compatible Products
Table 1-2 lists the products available from Silent Knight for use with the IntelliKnight
5820XL.
Table 1-2: 5820XL Compatible Products
Type of
Device
Model
Description
SLC Devices
Other
Modules
5815XL SLC Expander
Allows an additional 127 Hochiki SLC devices, or 99 SK detectors and 99 SK modules
to be added to the system. Up to three 5815XLs per system.
5211 Ground Start Relay
For use with ground start telephone network. (Do not use in UL installations.)
5824 Serial/Parallel Printer
Interface Module
Allows a printer to be attached for the system for on-site event logging, detector status
and event history reports. Two maximum per system.
5895XL Intelligent Power
Module
Provides additional power, six Flexput™ circuits, and two 5895XLs and 5496s can be
Form C relays. Max. 8 per system see Model 5895
Installation Instructions P/N 151024.
used in any combination,
up to a total of eight
devices on one system.
5496 Intelligent Power
Module
Provides 4 additional Notification Appliance Circuits/
Auxiliary power. (Up to 8 per system.)
5860 and 5860R Remote Fire Same operation, similar appearance as on-board
Alarm Annunciator
annunciator. Up to 8 5860s per system. 5860 is gray; 5860R
is red.
5860TG and 5860TR Trim
Ring Kit
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray; 5860TR is
red.
5865-3 and 5865-4 LED
Annunciator
LED annunciator can display up to 30 LEDs (15 red and 15
yellow). 5865-4 has key switches for silence and reset, and
a system trouble LED.
5865-3, 5865-4, and 5880
can be used in any
combination, up to a total
5880 LED I/O Module
Driver for up to 40 LEDs. Interfaces with customized
of eight devices on one
annunciator boards. In addition the 5880 has eight generic
panel.
switch input points.
5883 General Purpose Relay Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be
Module
used with each 5880 module.
Misc.
7860 Telephone Cord
RJ31X cord for connecting phone line to the 5820XL.
5660 Silent Knight Software For communication and panel programming with a Windows-based computer and
Suite (SKSS)
remote viewing of detector status and event history.
5670 Silent Knight Software Facility management software. For remote viewing of detector status and event history.
Suite (SKSS)
Requires a modem (not sold by Silent Knight).
RBB
Remote Battery Box for mounting backup batteries that are too large to fit into the main
control panel cabinet.
Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
Note: Models SD500-FRCM, and SD500-FRCM-4 are no longer manufactured, but they are still compatible with
the IntelliKnight system. Contact Silent Knight if you need information about these modules.
151209
1-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
The following modems have been tested by Silent Knight for compatibility with the 5820XL
and the Silent Knight Software Suite software packages:
Table 1-3: Compatible Modems
Manufacturer
US Robotics
Model
28.8
LifeStyle
Motorola
28.8, 3400 series
Premier 33.6
MultiTech
MT19321ZDX
1.4 How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent
Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Customer Service at 800-328-0103 or in Connecticut
203-484-7161.
®
IntelliKnight is a registered trademarks of Silent Knight. Flexput™ is a trademark of Silent
Knight.
1-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected
premise following the recommendations of the current edition of the National Fire Protection
Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes,
and the recommendations contained in Guide for the Proper Use of System Smoke Detectors,
which is made available at no charge to all installing dealers. A study by the Federal
Emergency Management Agency (an agency of the United States government) indicated that
smoke detectors may not go off or give early warning in as many as 35% of all fires. While
fire alarm systems are designed to provide warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons. For example:
•
Particles of combustion or smoke from a developing fire may not reach the sensing
chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or
smoke flow.
Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where
detectors are located.
Smoke particles may be blown away from detectors by air outlets
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires
developing on another level.
•
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke
detectors are designed to alarm at various levels of smoke density. If such density levels
are not created by a developing fire at the location of detectors, the detectors will not go
into alarm.
•
Smoke detectors, even when working properly, have sensing limitations. Detectors that
have photoelectronic sensing chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers
tend to detect fast flaming fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide adequate warning of a fire.
•
•
Smoke detectors are subject to false alarms and nuisance alarms and may have been
disconnected by users. For example, a smoke detector located in or near a kitchen may go
into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or
steamy environments may cause a smoke detector to falsely alarm. If the location of a
smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect
the smoke detector; call a professional to analyze the situation and recommend a solution.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson,
children playing with matches (especially within bedrooms), smoking in bed, violent
explosions (caused by escaping gas, improper storage of flammable materials, etc.).
151209
1-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
•
•
Heat detectors do not sense particles of combustion and are designed to alarm only when
heat on their sensors increases at a predetermined rate or reaches a predetermined level.
Heat detectors are designed to protect property, not life.
Warning devices (including horns, sirens, and bells) may not alert people or wake up
sleepers who are located on the other side of closed or partially open doors. A warning
device that activates on a different floor or level of a dwelling or structure is less likely to
awaken or alert people. Even persons who are awake may not notice the warning if the
alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by
passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or
other devices should be provided to warn these people). Any warning device may fail to
alert people with a disability, deep sleepers, people who have recently used alcohol or
drugs, or people on medication or sleeping pills.
Please note that:
i) Strobes can, under certain circumstances, cause seizures in people with conditions
such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not
respond or comprehend the meaning of the signal. It is the property owner’s responsi-
bility to conduct fire drills and other training exercises to make people aware of fire
alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent
hearing loss.
•
•
Telephone lines needed to transmit alarm signals from a premises to a central station may
be out of service or temporarily out of service. For added protection against telephone line
failure, backup radio transmission systems are recommended.
System components, though designed to last many years, can fail at any time. As a
precautionary measure, it is recommended that smoke detectors be checked, maintained,
and replaced per manufacturer’s recommendations.
•
•
System components will not work without electrical power. If system batteries are not
serviced or replaced regularly, they may not provide battery backup when AC power fails.
Environments with high air velocity or that are dusty or dirty require more frequent
maintenance.
In general, fire alarm systems and devices will not work without power and will not function
properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate,
an alarm system is not a substitute for insurance. Property owners should continue to act
prudently in protecting the premises and the people in their premises and should properly
insure life and property and buy sufficient amounts of liability insurance to meet their needs.
1-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
Requirements and recommendations for proper use of fire alarm systems in-
cluding smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection
equipment in all rooms and areas of the house or building in accordance with the requirements
and recommendations of the current edition of the National Fire Protection Association
Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations,
State and local codes and the recommendations contained in Guide for the Proper Use of
System Smoke Detectors, which is made available at no charge to all installing dealers. For
specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for
fire protection systems.
Requirements and Recommendations include:
•
•
•
•
Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing construction.
It is recommended that more than one smoke detector shall be installed in a hallway if it is
more than 30 feet long.
It is recommended that there shall never be less then two smoke detectors per apartment or
residence.
It is recommended that smoke detectors be located in any room where an alarm control is
located, or in any room where alarm control connections to an AC source or phone lines
are made. If detectors are not so located, a fire within the room could prevent the control
from reporting a fire.
•
All fire alarm systems require notification devices, including sirens, bells, horns, and/or
strobes. In residential applications, each automatic alarm initiating device when activated
shall cause the operation of an alarm notification device that shall be clearly audible in all
bedrooms over ambient or background noise levels (at least 15dB above noise) with all
intervening doors closed.
•
•
It is recommended that a smoke detector with an integral sounder (smoke alarm) be
located in every bedroom and an additional notification device be located on each level of
a residence.
To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards. At a
minimum the requirements of Chapter 7 of NFPA 72 shall be followed. A maintenance
agreement should be arranged through the local manufacturer’s representative.
Maintenance should be performed annually by authorized personnel only.
•
The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to make sure
all sensors and transmitters are working properly.
151209
1-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
1-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2
Agency Listings, Approvals, and Requirements
2.1 Federal Communications Commission (FCC)
1. The following information must be provided to the telephone company before the
IntelliKnight 5820XL can be connected to the phone lines:
A
B
C
Manufacturer:
Silent Knight
IntelliKnight 5820XL
AC6USA-23901-AL-E
0.8B
Model Number:
FCC registration number:
Ringer equivalence:
Type of jack:
D
E
RJ31X
Facility Interface Codes:
Loop Start: 02LS2
Ground Start: 02GS2
F
Service Order Code:
9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted by
ACTA. On the inside cover of this equipment is a label that contains, among other
information, a product identifier. If requested, this information must be provided to the
telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network
must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA.
A compliant telephone cord (not provided) and modular jack must be utilized with this
product. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine
the number of devices that may be connected to the public switched telephone network. This
number must not exceed 5.0. Since this product has an REN of 1.0, the number of devices is
limited. The REN number is imbedded in the FCC registration number as 10B.
If the 5820XL causes harm to the telephone network, the telephone company will notify you
in advance that the temporarily discontinuance of service may be required. But if advance
notice is not practical, the telephone company will notify the customer as soon as possible.
Also, you will be advised of your right to file a complaint with the FCC if you believe it is
necessary.
The telephone company may make changes in its facilities, equipment, operations or
procedures that could affect the operation of the equipment. If this happens the telephone
company will provide advance notice in order for you to make necessary modifications to
maintain uninterrupted service.
If trouble is experienced with the 5820XL, for repair or warranty information, please contact
Silent Knight at 1-800-328-0103 or www.silentknight.com. If the equipment is causing harm
to the telephone network, the telephone company may request that you disconnect the
5820XL until the problem has been resolved.
151209
2-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
This product cannot be adjusted or repaired in the field. It must be returned to the factory for
service.
This equipment is not designed for use with party line service. Connection to party line
service is subject to state tariffs. You may contact the state public utility commission, public
service commission or corporation commission for information.
Since the 5820XL is a commercial fire alarm panel, it must be connected upstream of all other
equipment utilizing the phone lines. If you have questions about the installation, contact your
telephone company or a qualified installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions:
(1) This device may not cause radio interference, and (2) This device must accept any interference received,
including interference that may cause undesired operation.
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer
to the specific section of the manual for additional requirements. The following subsections
list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 8.7 for
information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
ventional detectors listed in the compatibility chart. (See Appendix A.)
3. Use UL listed notification appliances compatible with the 5820XL from those specified in
the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
2-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Agency Listings, Approvals, and Requirements
Restricted Options:
•
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 -
30 hours. For UL certified installations this number must be set from 1 to 3 hours.
•
The system allows the use of non-latching spot type smoke detectors. This feature may not
be used in commercial applications whereby a general alarm is sounded. It is intended for
elevator recall, door holding applications, and hotel/motel room applications.
•
The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL
certified installations the setting must be a minimum of 60 seconds.
•
•
Call forwarding shall not be used.
When two count is used detector spacing shall be cut in half, you shall not use the alarm
verification feature, and no delay shall be used.
•
P.A.S feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5820XL sends an automatic
daily test to the central station.
3. Do not use the ground start option.
4. The AC Loss Hours option must be set from 1-3 hours.
5. The Attempts to Report option must be set for 5.
2.2.3 Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire
Alarm Systems - Digital Alarm Communicator
Transmitter (DACT)
2. The AC Loss Hours option must be set from 15-30 hours.
151209
2-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
2-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3
Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth
installation. Please read this section thoroughly, especially if you are installing a 5820XL
panel for the first time.
3.1 What’s in the Box?
The IntelliKnight 5820XL ships with the following hardware:
•
•
•
A cabinet with all hardware assembled
Two keys for the front door
Two keys for user operation of the on-board annunciator (installer operations require the
Installer’s Code)
•
•
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series
3.2 Environmental Specifications
It is important to protect the 5820XL control panel from water. To prevent water damage, the
following conditions should be AVOIDED when installing the units:
•
•
•
•
•
•
Intended for indoor use in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the 5820XL control panel, the unit should be mounted
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity not exceeding 93% noncondensing.
151209
3-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
3.3 Electrical Specifications
Rating
EarthGround
Faults
Terminal # and Label
Description
AC input (hot)
Voltage
120 VAC, 60 Hz 2.5 A
N/A N/A
120 VAC 60 Hz 2.5 A
Current
1
2
3
L
N/A
N/A
N/A
Earth ground
N
AC input (neutral)
3.0 Amp Notification and
Aux power Circuits
4
5
6
7
8
9
X
*I/O 6
Flexput™ Circuits
Flexput™ Circuits
Flexput™ Circuits
Flexput™ Circuits
Flexput™ Circuits
Flexput™ Circuits
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
O
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
X
*I/O 5
O
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
X
*I/O 4
O
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
10
11
12
13
14
X
O
X
O
X
*I/O 3
*I/O 2
*I/O 1
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and
Aux power Circuits
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
O
100 mA for initiation circuits
B
SBUS communication
SBUS power
5 VDC
100 mA
A
SBUS OUT
SBUS IN
0Ω
0Ω
+
24 VDC
1.0 A
-
B
A
Used for Class A installations
+
-
N.C.
C
RELAY 2
RELAY 1
General Purpose Relay 2
General Purpose Relay 1
24 VDC
24 VDC
2.5 A, resistive
2.5 A, resistive
N/A
N/A
N/A
N.O.
N.C.
C
N.O.
N.C.
C
TROUBLE Trouble Relay
24 VDC
32 VDC
2.5 A, resistive
150 mA
N.O.
SC-
SC+
SC-
SC+
L1
SLC terminals
SLC OUT
0Ω
0Ω
L2
Used for Class A installations
SLC IN
*
Regulated/Special application when used for releasing.
3-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Before You Begin Installing
Rating
EarthGround
Faults
Terminal # and Label
Description
Voltage
Current
37
Ring
Tip
Phone Line 1 Telco Ring
Phone Line 1 Telco Tip
38
39
40
41
42
43
44
45
46
N/A
N/A
0Ω
Ring
Tip
Phone Line 1 Premises Ring
Phone Line 1 Premises Tip
Phone Line 2 Telco Ring
Phone Line 2 Telco Tip
Ring
Tip
0Ω
0Ω
Ring
Tip
Phone Line 2 Premises Ring
Phone Line 2 Premises Tip
SC-
SC+
SLC Programming Terminal ( - ) 32 VDC
SLC Programming Terminal ( + ) 32 VDC
150 mA
150 mA
3.4 Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with
telephone communication or cause false alarms. To avoid induced noise, follow these
guidelines:
•
Isolate input wiring from high current output and power wiring. Do not pull one multi-
conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltage
SLC loops
AC power, Terminals 1-3
Terminals 33-36
Audio input/output
Phone line circuits, Terminals
37-44
Notification circuits
SBUS
Terminals 4-15
Terminals 16-23
Terminals 24-32
Relay circuits
•
•
•
Do not pull wires from different groups through the same conduit. If you must run them
together, do so for as short a distance as possible or use shielded cable. Connect the shield
to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit
board where it could induce noise into the sensitive microelectronics or pick up unwanted
RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or
bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it
around a ferrite toroid.
151209
3-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Before You Begin Installing
3.5 Board Assembly Diagram
On-board Annunciator
To AC
Chassis
Mounting
Nuts
Chassis
Mounting
Nuts
Key Switch
Input
Ground Start
Relay Socket
Programming
Ports
Figure 3-2 Model 5820XL Assembly
Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL
assembly to the cabinet. If you should need to remove the board assembly for repair, remove
the four mounting nuts which hold the assembly in the cabinet. Then lift the entire assembly
out of the cabinet. Do not attempt to remove the circuit boards from the metal bracket.
151209
3-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
3.6 Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs for your
installation.
3.6.1 Current Draw Worksheet Requirements
The following steps must be taken when determining 5820XL current draw and standby
battery requirements.
1. You will use the Current Draw Worksheet to determine current draw and standby battery
Hochiki SLC Devices. For the 5820XL, the worst case current draw is listed for the panel,
addressable devices, and all SBUS expanders. Fill in the number of addressable devices
and expanders that will be used in the system and compute the current draw requirements
for alarm and standby. Record this information in the Current Draw Worksheet on Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the
device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself,
does not exceed 6.0 A. This is the maximum alarm current for the 5820XL control panel.
If the current is above 6.0 A you will need to use a notification power expander(s) such as
the Silent Knight 5495 or the 5895XL intelligent power expander, to distribute the power
loads so that the 5820XL or the power expanders do not exceed their power rating. Refer
to the current draw worksheets provided with the 5495 or the 5895XL manuals so you do
not exceed their power requirements.
6. Complete the remaining instructions in the appropriate Current Draw Worksheet for deter-
mining battery size requirements.
3-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Before You Begin Installing
3.6.2 Current Draw Worksheet for SK SLC Devices
Use Table 3-1 to determine current requirements during alarm/battery standby operation when
SK SLC devices are installed. You can install up 99 SK detectors per loop (396 max per
panel) and 99 SK modules per loop (396 max per panel). Copy this section if additional space
is required.
Table 3-1: Current Draw Worksheet for SK SLC Devices
Standby
Current
Alarm
Current
Device
# of Devices
Current per Device
For each device use this formula: This column
X
This column
=
Current per number of devices.
Standby:
215 mA
385 mA
215 mA
Fire Panel (Current draw from
battery)
1
Alarm:
385 mA
Addressable SLC Detectors
SK-Photo
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
SK-Photo-T
SK-Ion
Standby/Alarm:
0.27 mA
SK-Heat
SK-Heat-HT
Standby/
SLC
Aux. Pwr
SLC
Alarm:
Standby:
Alarm:
2 mA
2 mA
SK-Beam (without integral test)
(99 max/loop
mA
& 396 max/
panel)
8.5 mA
mA
1
Standby/
Alarm:
2 mA
2 mA
5
SK-Beam-T (with integral test)
Standby:
Alarm:
mA
mA
Aux. Pwr
SLC
8.5 mA
mA
mA
Standby/
Alarm:
6
SK-Duct
0.27 mA
0.3 mA
SK-Acclimate
SK-Heat-ROR
mA
mA
mA
mA
Standby/Alarm:
151209
3-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Standby
Current
Alarm
Current
Device
# of Devices
Current per Device
Addressable SLC Modules
Standby/ 0.375mA
mA
SLC
Alarm
0.375mA
1.7mA
7mA
mA
SK-Control
Standby/
Alarm:
mA
Aux Pwr
mA
mA
mA
mA
SK-Monitor
SK-Minimon
SK-Pull-SA
SK-Pull-DA
SK-Monitor-2
SK-Mon10
mA
mA
mA
Standby/Alarm:
0.375 mA
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
0.75 mA
3.5 mA
1.45 mA
2.25 mA
2.25 mA
1.7 mA
20 mA
mA
mA
mA
mA
mA
mA
mA
SK-Relay-6
(99 max/loop
& 396 max/
Standby/
SLC
1
panel)
Alarm:
Standby/
Alarm:
SK-Control-6
SK-Relay
mA
Aux Pwr
mA
mA
Standby/Alarm:
0.255 mA
12 mA
mA
mA
Standby
Aux Pwr
SLC
Alarm
90 mA
mA
mA
SK-Zone
Standby/
Alarm
mA
mA
0.27mA
50 mA
Standby
Alarm
Aux Pwr
SLC
SK-Zone-6
270 mA
mA
mA
Standby/Alarm 2 mA
mA
mA
SLC Accessories
B501BHT-2 Sounder Base
Standby:
Alarm:
Alarm:
1 mA
15 mA
0.7 mA
0.5 mA
7.5 mA
10 mA
Aux Pwr
SLC
(99 max/loop
& 396 max/
panel)
mA
mA
mA
mA
mA
B224RB Relay Base
RTS151/151 KEY
RA100Z
Standby/Alarm:
Alarm:
mA
Alarm:
SLC Isolator Devices
SK-Iso (Isolator Module)
(100 max/loop Standby/Alarm:
&400 max/
Standby/Alarm:
panel)
0.45 mA
0.5 mA
mA
mA
mA
mA
B224BI Isolator Base
Accessories Modules
5815XL SLC Expander
(3 max.)
(8 max)
Standby/Alarm:
Standby:
55 mA
20 mA
25 mA
45 mA
mA
mA
mA
5860 Remote Fire Alarm
Annunciator
Alarm:
mA
mA
5824 Serial/Parallel Printer
Interface Module
Standby/Alarm:
mA
mA
(2 max.)
(8 max.)
5496 Intelligent Power Module
Standby/Alarm:
Standby/Alarm:
10 mA
10 mA
5895XL IntelliKnight Power
Module
mA
3-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Before You Begin Installing
Standby
Current
Alarm
Current
Device
# of Devices
Current per Device
Standby:
35 mA
145 mA
35 mA
145 mA
35 mA
200 mA
0 mA
mA
5865-4 LED Annunciator
(with reset and silence switches)
Alarm:
mA
Standby:
Alarm:
mA
mA
mA
5865-3 LED Annunciator
5880 I/O Module
(8 max.)
mA
mA
mA
Standby:
Alarm:
Standby:
Alarm:
5883 Relay Interface
(32 max.)
220mA
(22 mA per relay)
A
B
Total System Current
3
Refer to devices manual for current rating.
Auxiliary Devices
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
Auxiliary Devices Current
Notification Appliance Circuits
Refer to device manual for current rating.
Alarm:
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
Alarm:
Alarm:
Alarm:
C
D
E
F
G
H
I
Notification Appliances Current
Total current ratings of all devices in system (line A + line B + C)
Total current ratings converted to amperes (line D x .001):
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):
Multiply lines E and F.
mA
A
H
Total standby AH
AH
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
H
Multiply lines E and H.
Total alarm AH
AH
J
Total ampere hours
required
AH
4
Add lines G and I.
1. Total does not include isolator devices or accessory bases.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. SK-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be
considered when determining auxiliary power capacity but not calculated into current requirements for day to day
operation.
6. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is
calculated by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.
151209
3-9
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
3.6.3 Current Draw Worksheet for Hochiki SLC Devices
Use Table 3-2 to determine current requirements during alarm/battery standby operation when
Hochiki SLC devices are installed. You can install up 127 Hochiki devices per loop (508 max
per panel). Copy this section if additional space is required.
Table 3-2: Current Draw Worksheet for Hochiki SLC Devices
Standby
Current
Alarm
Current
Device
# of Devices
This column
Current per Device
For each device use this formula:
X
This column
Standby:
Alarm:
=
Current per number of devices.
215 mA
385 mA
215 mA
IntelliKnight 5820XL Fire Panel
(Current draw from battery)
1
385 mA
Addressable SLC Devices
SD500-AIM
SD500-MIM
SD500-PS
mA
mA
mA
mA
1
SD500-ARM
SD505-AHS
SD505-AIS
Standby/Alarm:
0.55 mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
(508 max.)
SD505-APS
Standby:
Alarm:
8 mA
60 mA
Aux. Pwr
mA
mA
1
1
SD500-ANM
SD500-SDM
(508 max.)
(508 max.)
Standby/
Alarm:
Standby/
Alarm:
SLC
SLC
mA
.55 mA
mA
mA
mA
mA
.55 mA
20 mA
106 mA
10 mA
220 mA
10 mA
Standby:
Alarm:
Aux. Pwr
Standby:
Aux. Pwr Alarm:
LED:
mA
mA
mA
1
SD500-LED
(100 max.)
mA
mA
Standby/
Alarm:
SLC
mA
0.55 mA
SLC Accessory Bases
SD505-6RB
(508 max.)
(508 max.)
Standby/Alram:
.082 mA
1 mA
32 mA
mA
mA
mA
Standby:
Aux. Pwr
Alarm:
mA
mA
SD505-6SB
Standby/
Alarm:
SLC
mA
mA
.082 mA
2
Standby:
Aux. Pwr
35 mA
SD505-ADHR
SD505-DUCTR
2
mA
mA
Alarm:
75 mA
(508 max.)
Standby/
Alarm:
SLC
mA
.082 mA
SD505-DTS
SD505-DTS-K
SD505-ADH
None, included with SD505-ADHR worst case.
(508 max.)
(508 max.)
None, included with detector current.
SD505-DUCT
SLC Isolator Devices
SD500-LIM
SD505-6IB
(1024 max.)
(508 max.)
Standby/Alarm
0.092 mA
mA
mA
Accessories Modules
5815XL SLC Expander
(3 max.)
(8 max.)
Standby/Alarm:
Standby:
Alarm:
55 mA
20 mA
25 mA
mA
mA
mA
mA
5860 Remote Fire Alarm Annun.
3-10
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Before You Begin Installing
Standby
Current
Alarm
Current
Device
# of Devices
Current per Device
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
5824 Serial/Parallel Printer Interface
5895XL IntelliKnight Power Expander
5496 Intelligent Power Module
5865-4 LED Annunciator
(2 max.)
(8 max.)
45 mA
10 mA
10 mA
35 mA
145 mA
35 mA
145 mA
35 mA
200 mA
0 mA
mA
mA
mA
mA
mA
mA
mA
(with reset and silence switches)
mA
mA
mA
mA
mA
mA
mA
5865-3 LED Annunciator
5880 LED I/O Module
(8 max.)
Standby:
Alarm:
5883 Relay Interface
(32 max.)
220mA
(22 mA per relay)
A
B
Total System Current
3
Refer to devices manual for current rating.
Auxiliary Devices
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
Auxiliary Devices Current
Alarm:
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
Alarm:
Alarm:
Alarm:
C
D
E
F
G
H
I
Notification Appliances Current
Total current ratings of all devices in system (line A + line B + C)
Total current ratings converted to amperes (line D x .001):
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):
Multiply lines E and F.
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
Multiply lines E and H.
mA
A
H
Total standby AH
Total alarm AH
AH
H
AH
J
Total ampere hours
required
AH
4
Add lines G and I.
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or
240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
151209
3-11
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
3.6.4 Maximum Battery Standby Load
Table 3-3 shows the maximum battery standby load for the 5820XL based on 24 and 60 hours
of standby. The standby load calculations of line D in the Current Draw Calculation
* 33AH max battery size for FM (Factory Mutual) installations..
Table 3-3: Maximum Battery Standby Load
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
Rechargeable Battery Size
7 AH
12 AH
18 AH
35 AH
270 mA
475 mA
685 mA
1.3 A
105 mA
190 mA
270 mA
540 mA
*
Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter
(DACT).
Warning!
Silent Knight does not support the use of batteries smaller than those listed in Table 3-3. If you use a battery
too small for the installation, the system could overload the battery resulting in the installation having less than
the required 24 hours standby power. Use Table 3-3 to calculate the correct battery amperes/hour rating needed
for your installation.
3.7 Installation Tasks Overview
This section provides a chart listing tasks that need to be performed when installing the
IntelliKnight 5820XL system. The chart is intended to be a handy way for you to make sure
you have completed all necessary tasks. Unless noted, these tasks do not have to be performed
in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart.
See Sec.
(for more info.)
Task
Main Panel Hardware Installation
U
U
U
U
Mount the control panel cabinet.
Connect AC.
Connect phone lines.
Install 5815XL SLC expander modules (if needed). Required if more than
127 SLC devices are used.
U
U
U
U
U
U
U
Install 5860 Remote Fire Alarm Annunciator modules if used.
Install 5865 or LED Annunciator modules if used.
Install 5880 LED I/O module if customized LED annunciation will be used.
Install notification appliances.
Install auxiliary power devices (if used).
If using a printer, install the 5824 Serial/Parallel Printer Interface Module.
Connect batteries (typically last step).
3-12
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Before You Begin Installing
See Sec.
(for more info.)
Task
SLC Device Hardware Installation
Perform these steps before running JumpStart.
U
U
U
Connect device bases to the loop.
Set device addresses.
Physically connect detectors to their bases. Connect relay and contact
monitor modules.
5.4 & see device
install instructions
JumpStart
JumpStart is for initial system programming. JumpStart automatically selects
some options for SLC devices. See “Input Point Configuration” section of this
chart for other options.
JumpStart makes selections for the following options. You can customize
options, if necessary.
Device type (detector or switch) configured by JumpStart.
Program type of detector (heat, photoelectric, or ionization) selected by
JumpStart.
System Software Configuration
U
U
U
U
U
U
U
U
Select low AC hours report time (6 hours by default).
Select Auto Test Time (2:00 AM by default).
Enable/disable automatic DST adjustment feature (enabled by default).
Change clock display format (12-hour with AM/PM by default).
Set up reporting accounts.
Select options for phone lines.
Select system-wide response to trouble conditions, if desired.
Select system-wide cadence patterns for special conditions (fire drill, Aux1
and Aux2 alarms) if desired.
U
Customize banner message (message that displays on LCD in normal
mode) if desired.
Input Point (SLC Device) Configuration
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart).
You can change options selected by JumpStart, if necessary and further customize input point options.
U
U
U
Select device type (SK or Hochiki). Only one device type can be used per
control panel.
Program type of switch (manual pull, fire drill, and so on), if necessary.
(JumpStart assigns all switches as Manual Pull type.)
If the installation includes duct detectors, program detector type.
(JumpStart does not distinguish duct detectors from ordinary smoke
detectors.)
U
U
Assign a name (or description) to the point.
Assign input points to zones, if necessary. (JumpStart assigns all input
points to Zone 1.)
Zone Configuration
U
Add the zone to the system if it does not already exist. (Zone 1 created by
JumpStart.)
U
Program a name (or description) for the zone.
151209
3-13
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
See Sec.
(for more info.)
Task
U
U
Select alarm delay options (detection characteristics) for zone.
Select heat detector trip temperature. (JumpStart selects 150°F for heat
detectors.)
Output Point Configuration
Conventional notification circuits (circuits 1-6):
U
Enable circuits used for notification appliances through programming, if
necessary. (JumpStart enables circuits 1-6 as Notification.)
Conventional relay circuits (circuits 7-8):
U
Select options for relay circuits, if desired. Note: Relay circuits will always
output continuously (constant pattern), even if assigned to an Output Group
that uses a different output pattern.
Auxiliary power circuits (circuits 1-6):
U
U
Enable any circuit used for auxiliary power devices through programming.
Select type of power (door holder, constant, or resettable)
Addressable relay modules
U
Assign addressable relay modules to output groups through programming.
(JumpStart assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming.
All output circuits (1-8):
U
U
Disable (set to UNUSED) any unused circuits. If you do not disable unused
output circuits, they will cause a trouble condition (unless an EOL resistor
is used).
U
Select a name for the point, if desired.
Output Group Configuration
U
U
U
Add the group to the system if it does not already exist.
Assign output points to the group.
Program a name (or description) for the group, if desired.
Select “group properties” (see below).
U
U
U
U
U
Latching / non-latching
Silencing option
Select options for activation with system switches.
Map zones to output groups that will activate when zone goes into alarm.
Select a cadence pattern for outputs in the zone.
3-14
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4
Control Panel Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while
installing or servicing.
4.1 Mounting the Control Panel Cabinet
Read the environmental specifications in Section 3.2 before mounting the control panel
cabinet. This will ensure that you select a suitable location.
The panel should be accessible to main drop wiring runs. It should be mounted as close to the
center of the building as possible and located within a secured area, but should be accessible
for testing and service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When mounting on
concrete, especially when moisture is expected, attach a piece of 3/4-inch plywood to the
concrete surface and then attach the cabinet to the plywood. Also mount any other modules to
the plywood.
The cabinet can be surface- or flush-mounted. If you will be flush-mounting the cabinet, the
hole for the enclosure should be 14.75" W x 25" H x 4" D. Do NOT flush-mount in a wall
designated as a fire break.
4.1.1 Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the
conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause
water problems. Installers should take reasonable precautions to prevent water from entering
the cabinet. Water damage is not covered under warranty.
4.1.2 Removing the 5820XL Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for
repair, do so by unscrewing the nuts that connect the control panel assembly to the cabinet. Do
not attempt to disassemble the circuit boards. See Section 3.5 for location of the nuts.
151209
4-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.2 AC Connection
At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may
be necessary for a professional electrician to make this connection.
The AC terminals are rated at 120 VAC, 50 or 60 Hz, 2.5A.
Figure 4-1 120 VAC Power Connection
4-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.3 Battery Connection
The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH
rating. Determine the correct AH rating as per your current load calculation (see Section 3.6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating. It is recommended that you replace batteries every five years.
To Control Panel
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
UL Listed 12V Battery
UL Listed 12V Battery
Figure 4-2 Battery Connection
151209
4-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.3.1 RBB Accessory Cabinet
The Model RBB Accessory cabinet can be used when your backup batteries requirements use
backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet
holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64
cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
•
•
•
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch ply-
wood. This is necessary because the weight of the batteries inside the accessory cabi-
net could cause the cabinet to pull away from the drywall.
When mounting on concrete, especially when moisture is expected, attach a piece of
3/4-inch plywood to the concrete surface and then attach the RBB cabinet to the ply-
wood.
If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no
more than 18" away from the main control panel cabinet. This will ensure that the bat-
tery cables reach the battery terminals.
Cabinet
Mounting Holes
Figure 4-3 RBB Cabinet Mounting Holes
2. Connect the main control panel battery cables to the battery cable extenders as shown in
Figure 4-4 Splicing Control panel Battery Cable to RBB Battery Cable Extenders
4-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet.
RBB Cabinet
Cover Screws
Conduit
Coupler
Conduit
-
+
+
-
RBB Cabinet
Cover Screws
Figure 4-5 Battery Connections in the RBB Cabinet
Note: Figure 4-5 is an example of how the wire connections can be routed. However, any other cabinet knock-
outs (on either the main control panel or the RBB cabinet), that are not previously being used may be uti-
lized to connect conduit between the two cabinets.
Observe the proper polarity to prevent damage to the batteries or the control panel.
Screw the cover screw 3/4 of the way into the cover mounting hole.
Cover Plate
Mounting Keyholes
Figure 4-6 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
151209
4-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.4 SBUS Wiring
This section contains information on calculating SBUS wire distances and the types of wiring
configurations (Class A and B).
4.4.1 Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the maximum
wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel,
it is necessary to calculate the total worst case current draw for all modules on a single 4-
conductor bus. The total worst case current draw is calculated by adding the individual worst
case currents for each module. The individual worst case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of accessory mod-
ules are required, and the worst case current draw will exceed the 1 amp limit, then the current draw must
be distributed using 5895XL Power Expanders. Each 5895XL Power Expander provides an additional
SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are done separately for
each 5895XL, and separately for the control panel itself.
Model Number
5860 Fire Annunciator
Worst Case Current Draw
.100 amps
5824 Serial/Parallel Printer Interface Module .040 amps
5880 LED I/O Module
.250 amps
.200 amps
.010 amps
.010 amps
5865 LED Fire Annunciator
5895XL Intelligent Power Supply
5496 Intelligent Power Supply
the modules can be located from the panel on a single wire run. The table insures 6.0 volts of
line drop maximum. In general, the wire length is limited by resistance, but for heavier wire
gauges, capacitance is the limiting factor.
4-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
These cases are marked in the chart with an asterisk (*). Maximum length can never be more
than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in
the note below).
Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
22 Gauge
18 Gauge
16 Gauge
14 Gauge
0.100
0.200
1852 ft.
926 ft.
617 ft.
463 ft.
370 ft.
309 ft.
265 ft.
231 ft.
206 ft.
185 ft.
4688 ft.
2344 ft.
1563 ft.
1172 ft.
938 ft.
781 ft.
670 ft.
586 ft.
521 ft.
469 ft.
* 6000 ft.
3731 ft.
2488 ft.
1866 ft.
1493 ft.
1244 ft.
1066 ft.
933 ft.
* 6000 ft.
5906 ft.
3937 ft.
2953 ft.
2362 ft.
1969 ft.
1687 ft.
1476 ft.
1312 ft.
1181 ft.
0.300
0.400
0.500
0.600
0.700
0.800
0.900
829 ft.
1.000 (Max)
746 ft.
Note: The following formulas were used to generate the wire distance chart:
6.0 Volts
Maximum Resistance (Ohms) =
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
Rpu
Maximum Wire Length (Feet) =
(6000 feet maximum)
* 500
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)
Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire
Wire Gauge
Ohms per 1000 feet (Rpu)
22
18
16
14
16.2
6.4
4.02
2.54
151209
4-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules:
2 - Module 5860 Fire Annunciator
1 - 5895XL Intelligent Power Expander
1 - 5865 LED Fire Annunciator
1 - 5824 Serial/Parallel Interface Module
The total worst case current is calculated as follows:
5860 Current Draw
= 2 x .100 amps
= 1 x .010 amps
= 1 x .200 amps
= 1 x .040 amps
= .200 amps
= .010 amps
= .200 amps
= .040 amps
= .450 amps
5895XL Current Draw
5865 Current Draw
5824 Current Draw
Total Worst Case Current Draw
Using this value, and referring to the Wiring Distance table, it can be found that the available
options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
4-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.4.2 Wiring Configurations
configuration.
Supervised
Power Limited
Caution
For proper system supervision do not use looped wire
under terminals marked A, B, +, and - of the SBUS
device connectors. Break wire runs to provide
supervision of connections.
Figure 4-7 SBUS Class A Wiring
Supervised
Power Limited
Figure 4-8 SBUS Class B Wiring
151209
4-9
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.5 Remote Annunciator 5860 Installation
The optional Model 5860 Remote Annunciator, shown in Figure 4-9, performs the same
functions as the on-board annunciator. Operation is identical. Up to 8 annunciators can be
added to the IntelliKnight 5820XL system.
Figure 4-9 Model 5860 Remote Annunciator, Front View
5860 installation involves the following steps:
1. Make sure power is off at the panel.
5. The new 5860 module must be added to the system through programming. JumpStart will
4-10
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.5.1 Mounting the 5860
This section of the manual describes mounting the remote annunciator. The annunciator can
be flush- or surface-mounted.
Figure 4-10 shows the parts of the annunciator. Instructions for disassembling and mounting
appear on the following pages.
Figure 4-10 Annunciator Parts
151209
4-11
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To
disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the
bottom of the annunciator bezel. (See Figure 4-11 for location of the set screws.)
Figure 4-11 Annunciator Back Box and Bezel Details
4.5.1.1 Flush Mounting
This section of the manual describes flush mounting. You can flush-mount with or without an
electrical box.
4-12
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
Flush Mounting with an Electrical Box
The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-
gang, and double-gang.
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to
accommodate the annunciator. Studs used with an electrical box must be two by fours (or
larger).
Figure 4-12 Placement of Electrical Box for Flush Mounting
Flush Mounting Steps
1. Cut a hole in the sheet rock to the following dimensions: 8-1/4” w x 6-5/8” h. If an electri-
cal box is used, the box must be 1-3/8” back from face of wall to accommodate the annun-
2. Remove knockout holes as needed for wires.
3. Fit the annunciator back box into the hole and stabilize with mounting wires. Angle the
mounting wires into the first hole past the sheet rock. Secure the wires behind the screws
as shown in Figure 4-13. When all four wires are in place, the back box should fit snugly
into the hole in the sheet rock.
151209
4-13
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
replace the electronic assembly in the back box. Place the bezel over the back box and
tighten the set screws on the bezel.
Figure 4-13 Flush Mounting the Back Box
4.5.1.2 Surface Mounting
The 5860 can be mounted directly to a surface or can be attached to a single, double, or four-
square electrical box. The Model 5860TG/TR trim ring kit is available for use when surface
mounting.
1. Drill holes in the surface to match the screw holes on the back box.
2. Fit the trim ring over the back box.
3. Attach the back box to the surface using screws provided.
replace the electronic assembly in the back box. Place the bezel over the back box and
tighten the set screws on the bezel.
4-14
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.6 5815XL Installation
The 5815XL SLC expander lets you add 127 addressable devices. Up to three 5815XLs
(adding 381 SLC devices for a total of 508 points) can be used with the system.
To install the 5815XL:
1. Make sure power is off at the panel.
2. Mount the 5815XL in the 5820XL, the 5895XL cabinet, or the 5815RMK remote mount-
ing kit. Use the standoffs located under the control panel board assembly and secure with
screws provided with the 5815XL. See also Model 5895XL Installation Instructions (P/N
151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
5. The new 5815XL module must be added to the system through programming. JumpStart
Figure 4-15 is a drawing of the 5815XL board, showing the location of terminals and
dipswitches.
Figure 4-15 5815XL Board
4-16
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.6.1 5815XL Connection to the Panel
Connect the 5815XL to the control panel as shown in Figure 4-16. After the 5815XL is
connected to the panel, it must be added to the system. This programming step is described in
Supervised
Power Limited
Figure 4-16 5815XL Connection to Main Panel Assembly
151209
4-17
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.7 5824 Serial/Parallel Interface Module
Installation
The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you
can print a real-time log of system events, a report of detector status, and event history.
Instructions for installing the 5824 appear below. The 5824 is for ancillary use only.
5824 installation involves the following steps:
1. Make sure power is off at the panel.
Note: Two 5824s per panel maximum.
3. Use the dipswitches on the back of the 5824 board to assign an ID# to the 5824 (see Sec-
Supervised
Power Limited
Figure 4-17 5824 Connection to the Panel
4-18
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
Model 5824 (with housing)
To Parallel Printer
To Serial Printer
Figure 4-18 Printer Connection
4.7.1 Selecting 5824 Options
Configuring the 5824 includes the following steps:
•
Add the module to the system. JumpStart will add the module automatically (see Section
•
•
Select a name, if desired (see Section 7.3.1.1).
Select options for the printer and the output port. See below.
151209
4-19
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Printer and Output Port Options
7
1. From the Installer Main Menu, select for Program Menu.
1
2. Select for Module.
1
3. Select for Edit Module.
4. From the list that displays, select the 5824 module you want to configure.
ENTER ENTER
5. Press
to bypass the next two screens. A screen similar to the one shown in
Figure 4-19 Selecting Printer and Output Port Options
6. Select options for the printer as needed for your installation. Most printers are parallel.
7. If you are using a serial printer, use the next screen to select serial port options as required
for your printer. Refer to your printer manual if you need more information.
Option
Choices
Baud Rate:
Data Bits:
Stop Bits:
Parity:
75 - 19200
5 - 8
.5, 1, 2
None, Even, Odd
4-20
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.8 5880 LED I/O Module
The 5880 is an LED driver board that can be used in a wide variety of applications, including
as an interface with most customized floor plan annunciator boards. The 5880 can drive up to
40 LEDs and has one PZT controller. The 5880 also has eight inputs for
monitoring. The following sub-sections describe hardware installation. Refer to Section 6 for
programming information.
4.8.1 5880 Board Layout
Figure 4-20 is a picture of the 5880 board showing locations of screw terminals for connection
to the panel and contact monitor wiring; pin connectors for connecting LEDs; and the
dipswitch for selecting an SBUS ID number.
Dry Contact Inputs
SBUS Address
DIPs
SBUS Connection
Figure 4-20 5880 Board Layout
151209
4-21
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.8.2 FACP Connection
The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-21.
After the 5880 is connected to the panel, it must be added to the system. This programming
Supervised
Power Limited
Figure 4-21 5880 Connection to Main Control Panel Assembly
4-22
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.8.3 LED Wiring
There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its
power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current
for each LED, no series resistors are required. LED outputs can be mapped to output circuits.
See Section 6 for programming details.
On connector P1, Pin 12 is an open collector output for controlling a PZT. If used, the 5880
PZT will match the PZT pattern of the on-board (or 5860) annunciator.
Note: The circuit connected to “Open Collector Output” (last pin on P1) must be current limited so that no more
than 100 mA of current is allowed to flow into the open collector transistor.
5880 LED Outputs
1
P1
2
3
4
5
6
7
8
9
10
Cathode
LEDs
Anode
LED Power
Programmable Open Collector Output
Not mappable.
Matches PZT pattern
on on-board
11
P2
12
13
14
15
16
17
18
19
20
annunciator
Cathode
LEDs
Anode
LED Power
no connection
Connectors P3 and P4 wired same as P2.
Figure 4-22 5880 Board Layout
151209
4-23
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.8.4 Dry Contact Wiring
The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch
supported by the control panel can be used with the 5880. For example, you can use a 5880 to
monitor pull stations, water flow, tamper, reset, or silence switches.
shared by two inputs.
Supervised
Model 7628
Figure 4-23 Dry Contact Wiring
4-24
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.9 5865-3 / 5865-4 LED Annunciator Installation
The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote
silence and reset key switches, and a general system trouble LED. The 5865-3 has 30
mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and
yellow (typically used for trouble) LEDs.
Installation of the 5865-5 and 5865-4 is identical. The key switches and the trouble LED
follow the behavior of other system annunciators and do not require any installation steps. The
following sub-sections describe how to install the 5865-3 and 5865-4 hardware. Refer to
Section 6 for programming information.
Note: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common to both
models.
Figure 4-24 5865-3 and 5865-4 Assembly (front view)
151209
4-25
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.9.1 FACP Connection
The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-25.
After the 5865 is connected to the panel, it must be added to the system. This programming
Supervised
Power Limited
Figure 4-25 5865 Connection to the FACP
4-26
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.9.2 5865 Mounting
Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang
Figure 4-26 5865 Mounting Example
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board
assembly. These labels can be used in a typewriter or can be written on by hand. Slide the
when illuminated.
Figure 4-27 Inserting Zone Description Labels
151209
4-27
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.10 Configuring Modules
This section describes how to configure any system hardware modules that have been added
to the system.
4.10.1 Assigning Module IDs
When installing a hardware module (such as, 5815XL, 5824, 5860, 5895XL, 5865-3 or 5865-
4), you must use the dipswitches on the module to assign an ID# to the module.
Figure 4-28 shows all possible dipswitch positions and their correlation to a numerical ID. For
example, to select ID 2, place dipswitch 2 in the up position.
Figure 4-28 Possible module addresses
Refer to Section 6. to edit, add, delete, and view module list.
4-28
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.11 Telephone Connection
from Silent Knight for this purpose.
A number of programmable options are available for customizing telephone lines. These
5211 Ground
Start Relay Socket
Figure 4-29 Connection of Telephone Lines
4.12 5211 Ground Start Relay
Note: Do not use ground start in UL installations.
If connecting the control panel to a ground start telephone network, you must use the 5211
ground start relay (order separately).
To install the 5211:
2. Enable ground start through the ground start programming option as described in Section
151209
4-29
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.13 Flexputs™ I/O Circuits
The six Flexput™ circuits are an innovative and versatile feature of the control panel. They
can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4
wire detectors), or as auxiliary power (resettable, continuous, or door holder).
The polarity of the Flexput terminals differs depending on whether the circuit is programmed
as an input or and output circuit. If the circuit is programmed as an input circuit (for a detector
or normally open contact) the X terminal is negative and O terminal is positive. If the circuit is
programmed as an output circuit (Aux power or NAC) then the X terminal is positive and the
O terminal is negative.
This section of the manual explains how to install conventional notification appliances and
initiating devices to be used with the system.
4.13.1 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for
Class A (Style Z) and Class B (Style Y) configurations.
4.13.1.1 Regulated Class B Notification Wiring
back of this manual.
To install a circuit:
4-30
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
Alarm
Polarity
Notification Wiring
Supervised
Power Limited
UL Listed EOL
Model 7628
4.7 kΩ
Max. Impedance: 1.5Ω
Regulated 24 VDC Full Wave Rectified
27.4 VDC, 3A per Circuit, 6A max Combined
Figure 4-30 Class B Notification Appliance Circuit Wiring
151209
4-31
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.13.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix at the back
of this manual.
To install a Class A notification appliance circuit:
Caution
For proper system supervision do not use looped wire under terminals marked O and X of the Flexput
connectors. Break wire runs to provide supervision of connections.
Supervised
Power Limited
Regulated 24 VDC Full Wave Rectified
27.4 VDC, 3A per Circuit, 6A max Combined
Figure 4-31 Class A Notification Appliance Circuit Configuration
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-31 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
4-32
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.13.2 Conventional Input Switch Circuits
This section of the manual explains how to install conventional initiating devices for Class A
(Style D) or Class B (Style B) configurations.
4.13.2.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations,
directly to the Flexput circuits of the control panel.
To install a Class B switch:
Supervised
Power Limited
UL Listed EOL
Model 7628
4.7 kΩ
Figure 4-32 Class B Input Switches
151209
4-33
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.13.2.2 Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations,
directly to the Flexput circuits of the control panel.
To install a Class A switch:
Supervised
Power Limited
Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.
Figure 4-33 Class A initiating Switches
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-33 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
4-34
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.13.3 Installing 2-Wire Smoke Detectors
Any compatible U.L. listed two-wire smoke detector can be used with the control panel (see
how to connect a UL listed 2-wire detector to the control panel.
4.13.3.1 Installing 2-Wire Class B Smoke Detectors
To install a Class B two-wire smoke detector, wire as shown in Figure 4-34.
Supervised
Power Limited
UL Listed EOL
Model 7628
Note:
Flexput circuit 5
4.7 kΩ
used as an example.
Any Flexput circuit
could be used.
Figure 4-34 Two-Wire Class B Smoke Detector
151209
4-35
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.13.3.2 Installing 2-Wire Class A Smoke Detector
To install a Class A two-wire smoke detector, wire as shown in Figure 4-35.
Supervised
Power Limited
Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.
Figure 4-35 Two-Wire Class A Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-35 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
4-36
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.13.4 Installing 4-Wire Smoke Detectors
Any compatible U.L. listed four-wire smoke detector can be used with the control panel (see
how to connect a UL listed four-wire detector to the control panel.
4.13.4.1 Installing a Class B 4-Wire Smoke Detector
Figure 4-36 illustrates how to install a 4-wire Class B smoke detector.
Conventions used for wiring 4-wire Class B loops:
1. Up to three Class B 4-wire smoke detector loops can be connected to the control panel at
once.
3. Each loop gets smoke power from the even numbered Flexput circuit and the contact input
is connected to the odd numbered Flexput circuit.
Supervised
Power Limited
UL Listed
EOL Resistor
Model 7628
Air Products
PAM-2
Note:
Model 160150
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.
Supervision
Module
ESL 449CT
Figure 4-36 Class B 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-36 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
151209
4-37
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.13.4.2 Installing 4-Wire Class A Smoke Detectors
Figure 4-37 illustrates how to install 4-wire Class A detectors.
Conventions used for wiring 4-wire Class A loops:
1. Up to two Class A 4-wire loops can be connected to the control panel at once.
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
Supervised
Power Limited
Figure 4-37 Class A 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput
circuit number used. For example, Figure 4-37 uses Flexput circuits 1, 2, 3 together and 4, 5, 6 together.
In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.
4-38
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.13.5 Auxiliary Power Installation
Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The three
types of auxiliary power available are:
•
•
•
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for
all Flexput circuits must not exceed 6.0 A).
To install an auxiliary power circuit:
tion of Flexput circuits.
Figure 4-38 Flexput Circuit Location
4.13.5.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the
system and the panel has AC power, door holder circuits have 24-volt power present at their
terminals. Any alarm will cause power to disconnect. Power will be re-applied when the
system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power
will be disconnected to conserve the battery backup. When AC power is restored, power is
immediately restored to the door holder circuits.
Use a UL listed door holder ESL DHX-1224, for this application.
4.13.5.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is
always present at Constant circuits.
151209
4-39
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.13.5.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional
4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at
the terminals unless a system reset occurs. If a system reset occurs, power is disconnected
from the terminals for 30 seconds, then re-applied.
4.14 On-Board Relays (Conventional)
The control panel has two built-in programmable relays and a built-in trouble relay. All relays
are Form C rated at 2.5 A @ 24 VDC.
Figure 4-39 Location of Conventional Relay Circuits
4.14.1 Trouble Relay
The control panel has a dedicated Form C trouble relay built into terminals 30-32. The relay
provides a normally open and a normally closed contact. The trouble relay will deactivate
under any trouble condition.
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no trouble con-
ditions.
4.14.2 Programmable Relays
The control panel has two Form C programmable relays built into terminals 24-29. Each relay
provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
tion of the relay terminals.
4-40
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.15 Remote Station Applications
4.15.1 Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for direct connection to a
Keltron receiver. The 3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation
instructions for complete information.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3. Program control panel Relay 1 for alarm.
4. Program Flexput circuit 5 for alarm.
5. Program Flexput circuit 6 for supervisory non latching.
Table 4-3: Keltron 3158 to Control Panel Connections
Terminal #
3158 Term. 1
Connects To
Terminal #
3158 Term. 8
Connects To
To Keltron receiving equipment
To Keltron receiving equipment
Earth ground
Control panel Term. 28
Control panel Term. 5
Control panel Term. 4
3158 Term. 2
3158 Term. 3
3158 Term. 4
3158 Term. 5
3158 Term. 6
3158 Term. 7
3158 Term. 9
3158 Term. 10
Not used; no connection.
Control panel Term. 18
Control panel Term. 19
Control panel Term. 7
Control panel Term. 6 Control panel Term. 29
Control panel Term. 28 Control panel Term. 31
Control panel Term. 29 Control panel Term. 30
Not suitable for remote station
protected premise service
where separate transmission
circuits are required for fire
supervisory (if applicable), and
trouble signals.
Example
Intended for connection to a
polarity reversal circuit of a
remote station receiving unit
having compatible ratings.
Figure 4-40 Keltron 3158 Connection to Control Panel
151209
4-41
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.15.2 City Box Connection Using the 5220 Module
This section describes how to connect the control panel to a local energy municipal fire alarm
box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire
alarm service. The city (master) box is an enclosure that contains a manually operated
transmitter used to send an alarm to the municipal communication center which houses the
central operating part of the fire alarm system.
City Box Standby Current:
0 (Notification supervision current
accounted for in control panel draw.)
Alarm Current:
1 Amp for 1 second
27.2 VDC max
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a
short piece of conduit (must not exceed 20 feet in length).
to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resis-
tor in the terminals of the Flexput circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the Flexput circuit used as a notification circuit, continuous and non-silencing.
It is not possible to reset the remote indication until you clear the condition and reset the
control panel.
Note:
Flexput Circuit 1 Used
as an example.
Any Flexput circuit
could be used.
All circuits non-power-limited.
All wiring non-supervised.
Figure 4-41 City Box Connection
4-42
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.15.3 NFPA 72 Polarity Reversal
Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having
compatible rating.
4.15.3.1 Using the 5220 Module
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble
events to a remote site. Alarms will override trouble conditions and it will not be possible to
reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Standby Current:
Alarm:
100 mA, 24 VDC
100 mA, 24 VDC
To install the 5220 for polarity reversal, follow the steps below:
1. Locate the knockout on the right side of the control panel cabinet to connect the 5220
using a short piece of conduit (must not exceed 20 feet in length).
4-42. This diagram also shows how to connect the 5220 to the remote indicator. Do not
install an EOL resistor in the terminals of the Flexput circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the Flexput circuit used as a notification circuit, continuous and non-silencing.
5. If necessary, adjust loop current using the potentiometer (R10) on the 5220 board . Normal
loop current is 2-to-8 mA with a 1k ohm remote station receiving unit. Maximum loop
resistance is 3k ohm.
Note:
Flexput circuit 1 and Relay 1
used as examples. Any
Flexput circuit and either
relay 1 or relay 2 could
be used.
All circuits power-limited.
All wiring supervised.
Jumper these terminals
when City Box is not used.
Intended for connection to a Polarity Reversal
circuit of a Remote Station receiving unit having
compatible ratings.
Figure 4-42 Polarity Reversal Connection Using the 5220 Module
151209
4-43
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.15.3.2 Using the 7644 Module
When the 7644 is used for polarity reversal, it allows alarm and trouble events to be reported
to a remote site. Alarms will override trouble conditions and it will not be possible to reset the
remote indicator until the condition is cleared and the control panel is reset.
To install the 7644 for polarity reversal:
1. Wire the 7644 to the control panel as shown in Figure 4-43. Do not install an EOL resistor
on the terminals of the Flexput circuit used.
Note: Use only Flexput circuits on the control panel for reverse polarity.
4. Program the output group characteristics as non-silenceable and reverse polarity. See Sec-
Figure 4-43 Polarity Reversal Connection Using the 7644
4-44
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.15.4 Using the SD500-ARM Addressable Relay Module
When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a
remote site. Alarms will override trouble conditions and it will not be possible to reset the
remote indicator until the condition is cleared and the control panel is reset.
1 kΩ
Intended for Connection to a
Polarity Reversal Circuit of A
Remote Station Receiving Unit
Having Compatible Rating.
To City Box
UL Listed
Model 7642
Must be installed
in City Box enclosure
Figure 4-44 Polarity Reversal Connection Using the SD500-ARM Module
151209
4-45
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4.15.5 Using a MR-201/T Control Relay From Air Products
When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble
events to a remote site. Alarms will override trouble conditions and it will not be possible to
reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Current:
15 mA max.
24 VDC nominal
4 KΩ
Operating Voltage:
Resistance:
To install the MR-201/T for polarity reversal, follow the steps below:
Intended for Connection
to a Polarity Reversal
Circuit of A Remote
Station Receiving Unit
Having Compatible
Rating.
Figure 4-45 Wiring the MR-201/T
4-46
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel Installation
4.15.6 Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the
5820XL FACP dry contacts. The FACP contacts must be supervised by the remote station
transmitter module using end-of-line resistors (ELRs) with a value determined by the
transmitter manufacturer. Power is also provided by the remote station transmitter
manufacturer. Refer to the remote station transmitter manufacturer’s manual for details.
151209
4-47
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
4-48
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5
Hochiki and SK SLC Device Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the
control panel while installing or servicing.
5.1 List of SK SLC Devices
The following SK SLC devices can be used with the control panel. See the device installation
instructions for more information (packaged with the device).
Note: The control panel supports the use of either SK SLC devices or Hochiki SLC devices. You cannot install
both SLC device types on the control panel.
SK
Section/ Install
Sheet PN
Model Name/Description
Part Number
SK-Photo
Photoelectric smoke detector
SK-Photo-T
SK-Acclimate
SK-Beam
Photoelectric smoke detector with thermal (135°F)
Multicriteria photoelectric smoke detector with thermal (135°F)
Reflected beam smoke detector without test feature
Reflected beam smoke detector with test feature
Ionization smoke detector
I56-3426-001
I56-3433-001
SK-Beam-T
SK-Ion
I56-3428-001
I56-3432-000
SK-Duct
Photoelectric duct smoke detector with extended air speed range
Fixed temperature thermal detector (135°F)
Rate-of-rise thermal detector with 135° fixed temperature
Fixed high temperature thermal detector (190°F)
Addressable single action pull station
Addressable dual action pull station
Fault isolator module
SK-Heat
SK-Heat-ROR
SK-Heat-HT
SK-Pull-SA
SK-Pull-DA
SK-Iso
I56-3429-000
I56-3446-001
I56-3447-001
I56-3445-000
I56-3442-000
I56-3444-000
I56-3435-000
I56-3443-000
I56-3438-000
I56-3439-000
I56-3440-000
I56-3441-000
I56-3436-000
I56-3437-000
K200-07-00
D450-15-00
D450-16-01
D550-06-00
D550-02-00
SK-Monitor
SK-Minimon
SK-Monitor-2
SK-Mon-10
SK-Relay
Monitor module
Mini monitor module
Dual input monitor module
10 input monitor module
Addressable relay module
SK-Relay-6
SK-Zone
Six relay control module
Addressable zone interface module
Six zone interface module
SK-Zone-6
SK-Control
SK-Control-6
B201LP
Supervised control module
Six circuit supervised control module
6" mounting base
B224BI
6" isolator base
B224RB
6" relay base
B501BHT-2
B501
6" temporal sounder base
4" mounting base
151209
5-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
5.2 List of Hochiki SLC Devices
The following Hochiki SLC devices can be used with the control panel. See the appropriate
section number in this manual or the device installation instructions (packaged with the
device) for more information.
Note: The control panel supports the use of either Hochiki SLC devices or SK SLC devices. You cannot install
both SLC device types on this control panel.
Section No./
Model Number
Model Name/Description
Installation
Instructions PN
SD505-APS
Photoelectric smoke detector.
Ionization smoke detector
Section 5.7
SD505-AIS
SD505-AHS
SD505-6AB
SD505-6IB
SD505-6RB
SD505-6SB
Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).
6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS.
150955
151175
151192
151191
6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and SD505-APS
6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS
6" sounder base for use with the SD505-AHS, SD505-AIS, and
SD505-APS SLC devices
SD505-DUCT
Duct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric Smoke
Sensor. Intake tubing for duct available in three lengths:
1700-09882
SD505-T2.5 (2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot)
SD505-DUCTR
SD505-ADH
Duct Detector housing with relay base. Duct housing with relay base including SD505-APS
Analog Photoelectric Smoke detector pre-installed
1700-09882
151040
Duct Detector Housing for use with the SD505-AIS or SD505-APS smoke detectors. Intake
tubing for duct available in three lengths:
STS-2.5: Duct widths 1.0’ to 2.5’; STS-5.0: Duct widths 2.5’ to 5.0’; STS-10.0: Duct widths
5.0’ to 10.0’ When ordering SD505-ADH, specify intake tubing size and order the appropriate
smoke detector (if needed).
SD505-ADHR
SD500-PS/-PSDA
SD500-AIM
Duct detector housing with relay (for use with SD505-AIS or SD505-APS smoke detectors)
Single or dual action addressable pull station
151126
151177
151071
Addressable input module (switch input), standard size, dipswitch configurable
SD500-MIM
Mini input monitor module (switch input), small size, dipswitch configurable. Fits in single-
gang box with manual pull station switch.
151071
SD500-ANM
SD500ARM
SD500-SDM
Addressable notification module
151109
151091
151193
Addressable relay module dipswitch configurable.
Addressable smoke detector module. Use to assign an address to a loop of conventional
devices.
SD500-LIM
SD500-LED
Line isolator module. Fits in a double gang box.
151125
151232
Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-LED
Driver Modules can be used per SLC loop.
SD505-DTS, SD505-DTS-K Remote test switch & LED indicator for the SD505-ADHR and SD505-DUCTR
151126
5-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Hochiki and SK SLC Device Installation
5.3 Maximum Number of Devices
The 5820XL supports SK or Hochiki devices on one 5820XL system. The maximum number
of devices per system varies depending on device protocol and the number of 5815XL
signaling circuit loop (SLC) expanders added to the system. Device support is as follows:
•
SK Devices–A 5820XL system can support a total of 396 SK detectors and 396 SK
modules. 99 detectors and 99 modules can be connected to the built-in SLC loop. Each
optional 5815XL adds another 99 detectors and 99 modules. Add up to three 5815XLs to a
system to achieve the maximum number of devices on the system.
OR
•
Hochiki Devices–A 5820XL system can support a total of 508 Hochiki SLC detectors and
modules, in any combination. 127 devices can be connected to the built-in SLC loop. Each
optional 5815XL adds another 127 devices.
5.4 Wiring Requirements for SLC Devices
The following information applies to all SLC devices. Refer to the section that describes the
type of device you are installing for details.
5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid
or stranded as long as it meets the National Electric Code 760-51 requirements for power
limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms for SK devices and 50 ohms for Hochiki devices.
Hochiki.
Table 5-1 Maximum wiring distance for SK modules
Wire Gauge
MAx. Distance for SK
1200 feet
22 AWG
18 AWG
16 AWG
14 AWG
12 AWG
3100 feet
4900 feet
7900 feet
10,000 feet
Table 5-2 Maximum wiring distance for Hochiki devices
Wire Gauge
Max. Distance for Hochiki
22 AWG
18 AWG
16 AWG
14 AWG
1500 feet
3900 feet
6200 feet
10,000 feet
151209
5-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Figure 5-1 and Figure 5-2 show how wire length is determined for out-and-back tap and T-tap
style wiring.
Figure 5-1 Calculating wire run length for a simple out and back tap
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet.
This requirement must be met in addition to the maximum distance requirements for the
various wire gauges.
Figure 5-2 Calculating Wire Run Length for a T-tap
5-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Hochiki and SK SLC Device Installation
5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration
Figure 5-3 illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations.
Note: Style 6 does not use short circuit isolator devices.
Figure 5-3 Class A SLC Configuration
Note: No t-taps allowed on class A SLC loops.
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors.
Break wire runs to provide supervision of connections.
151209
5-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
5.5 Wiring SK SLC Detectors
This section describes how to install SK heat and smoke detectors. All detectors ship with
installation instructions. Refer to the detector’s installation instructions for more detailed
information.
This information applies to the following SK models:
•
•
•
•
•
•
•
SK-Photo Photoelectric Smoke Detector
SK-Photo-T Photoelectric Smoke Detector with Thermal
SK-Acclimate Photoelectric Smoke Detector with Thermal
SK-Heat Fixed Temperature Detector
SK-Heat-T High Temperature Thermal Detector
SK-Heat-ROR Rate-of-Rise Thermal Detector
SK-Ion Ionization Smoke Detector
To wire SK detectors:
1. Wire device bases as shown in Figure 5-4.
Caution: Do not loop wire under Terminal 1 or 2.
Break wire run to provide supervision of connections.
...............
Class A wiring:
Class B wiring:
Figure 5-4 Heat and Smoke Detector Connection to the Panel.
5-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Hochiki and SK SLC Device Installation
5.6 Addressing SK SLC Devices
All SK devices are addressed using the two rotary dials that appear on the device board. Use
the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS
rotary dial to set the tens place in a two digit number.
SK device addresses are handled differently than Hochiki device addresses. The control panel
recognizes when an SK detector or SK module is installed. For this reason, SK detectors can
be assigned any unique address from 1 to 99, and SK modules can be assigned any unique
address from 1 to 99. Unlike Hochiki detectors and modules which share addresses 1 through
99, there can be an SK detector using address 1 and an SK module using address 1. 0 is an
invalid address.
Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS rotary
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary
All dials labeled for ONES
or TENS position.
Example 1: Device Set to 01.
Example 2: Device Set to 42.
Figure 5-5 SK SLC Device Addressing Using Rotary Dials
151209
5-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
5.7 Hochiki Detector Installation
The information in this section applies to the following Hochiki models: SD505-AHS Heat
Detector, SD505-AIS Ionization Smoke Detector, and SD505-APS Photoelectric Smoke
Detector.
Also see Section 5.8 for information on how to address the detectors.
5.7.1 Wiring Hochiki Detectors
1. Wire device bases as shown in Figure 5-6.
3. If you are connecting to the main panel, do not connect any devices to terminals 35 and
36. If you are connecting to the 5815XL, do not connect any devices to “SLC IN”.
Figure 5-6 Heat or Smoke Detector Connection to the FACP (Class B)
5-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Hochiki and SK SLC Device Installation
5.8 Addressing Hochiki Devices
This section tells how to address detectors and modules.
5.8.1 SD505-APS, SD505-AHS, & SD505-AIS
The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS
ionization smoke detector are easily addressed at the FACP. The Installer Code is required to
perform this task.
To address a SD505-APS, SD505-AHS, or SD505-AIS:
1. Connect a detector base temporarily to the programming terminals as shown in
Figure 5-7. (You can use the same base for each detector.)
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing
ENTER
2. Enter the Installer code, then press
.
2
3. Select for Point Functions.
3
4. Select for Set SLC Dev Addr.
ENTER
5. Select “Yes” by pressing the
up arrow, then press
. (The panel will go into
SILENCE
trouble at this point. You can use the
key to stop the PZT. The trouble will clear
automatically when the panel re initializes when you finish programming.)
6. When the wait message clears, the following options display:
1
for Read Address. Use to read (or check) a single detector’s address.
2
for Write Address. Use to program a single detector’s address.
3
for Seq. Programming. Use to program more than one detector in sequential order.
7. If you are changing addresses, write the programmed address on the back of the device.
8. To exit press
left arrow until fully exited.
151209
5-9
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
5.8.2 SLC Devices with Dip Switches
Input and relay module addresses are set using the dip switches on the module board. The
chart below shows the available addresses. For example, to select address 3, place dip
switches 1 and 2 in the up position. The range of valid addresses is 1-127. 0 is an invalid
address.
Figure 5-8 Hochiki SLC Device Addressing Using Dip Switches
5-10
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6
Programming Overview
This section of the manual is intended to give you an overview of the programming process.
Please read this section of the manual carefully, especially if you are programming the control
panel for the first time.
The JumpStart feature automates many programming tasks and selects default options for the
system. You will run JumpStart at least once when you are installing the system. See Section
6.1 for details. After you run JumpStart, you may need to do some additional programming
depending on your installation. Section 7 of this manual covers manual programmable options
in detail.
Programming the panel can be thought of as a three part process. You must program:
•
•
•
System options. These are options that affect general operation of the panel (see Section
Options for input points and zones. These are primarily options that control detection
behavior of devices (see Section 7.6 for details).
Options for output points and groups. This includes selecting characteristics for output
groups and mapping output circuits to output groups (see Section 7.6 for details).
6.1 JumpStart Autoprogramming
The JumpStart feature allows for faster system setup. When you run JumpStart (immediately
after addressing SLC devices), the system scans devices on all SLC loops and determines
device type (for example, ionization smoke detector or heat sensor) and selects some system
options based on the device type. This saves the installer from having to program options for
each device. Depending on the application, the installer may need to make some changes after
JumpStart completes.
See Section 6.1.3 for complete details about running JumpStart.
IMPORTANT
JumpStart is intended to be run one time only, immediately after SLC devices have been addressed and connected.
JumpStart will reset all manually programmed options to default settings. Do not run JumpStart after you have
configured the system.
151209
6-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
6.1.1 Input Points
JumpStart will determine the number and type of input points (detectors or contact monitor
modules) on each SLC loop. JumpStart assigns the correct detector type (heat, ionization or
photoelectric), so the installer does not need to edit device type for detectors. Any contact
monitor modules on the system will be assigned type "Manual Pull." The installer will need to
manually change the switch type if manual pull is not correct.
JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped
to Output Group 1. After JumpStart completes, you can re-map to configure a multiple zone/
output group system (see Section 7.4.1.3). For a general explanation of mapping, see Section
6.1.2 Output Points
JumpStart creates three output groups and assigns output circuits as follows:
Circuits 1-6:
Configured as Notification and assigned to Group 1. JumpStart automatically programs Zone
1 to activate Group 1 using constant on output.
Circuit 7 (Relay 1):
Assigned to Group 249. JumpStart automatically programs Zone 1 to activate Group 249
using constant on output when a supervisory condition occurs.
Circuit 8 (Relay 2):
Assigned to Group 250. JumpStart automatically programs Zone 1 to activate Group 250
using constant on output when an alarm occurs.
Addressable output points (Relay modules, NAC Modules, Sounder Bases, Relay Bases):
All addressable relay devices will be configured as “Output Pt” (general purpose output point)
and assigned to Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
6.1.3 Running JumpStart
Run JumpStart immediately after you have addressed and connected all input devices
(detectors, pull stations, and so on) and output devices (notification appliances, relays, and so
on).
Note: If you need to install a few devices after you have run JumpStart, you can install them manually. Follow
instructions in Section 8 for configuration.
To run JumpStart, follow these steps.
1. Press
to view Main Menu.
7
2. Select for Program Menu.
6-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
6
3. From the next menu, select for JumpStart.
4. The message "WARNING Will DELETE all system options" displays on the LCD. Select
Yes to continue. A series of messages displays for the next several seconds. JumpStart
scans the SLC loops for devices. This can take several minutes, depending on the number
of devices attached.
5. When the message, "SLC FAMILY HOCHIKI" flashes. Press
installing, or press to display SK and press to accept SK.
to accept Hochiki if
6. When the message “Configuring System Done” displays, press any key to continue.
7. Select one of the following options from the menu that displays.
1
2
3
1
2
- Review System
Press
Press
if you need to review the JumpStart configuration.
if you need to rerun JumpStart for any reason.
- Repeat JumpStart
- Accept Configuration
3
1. If you are ready to make the JumpStart configuration permanent, select
.
2. The system will ask you if the installation contains duct detectors. If there
2
are none, select
detectors, select
for No and skip to Step 8. If the system contains duct
for Yes and continue with Step 3.
1
3. From the list that displays, select the 5815XL device that contains the duct
detectors.
4. The first photoelectric or ionization detector on the system will display.
1
2
Select
for DUCT and
for NonDUCT.
1
2
5. Press
to select the next detector. Select
for DUCT and
for Non-
DUCT. Continue until all duct detectors have been selected. (Note: You can
move backwards through the list with .)
6. When you reach the last detector on this device, press
.
7. The system will ask you if there are more duct detectors in the system. If
1
there are, select
for Yes and repeat from Step 3. If there are no more
2
duct detectors, select
for No and continue with Step 8.
1
8. The system will restart in 10 seconds. You can press
to restart immedi-
2
ately. Do not select
for System Diagnostics. (This feature is for use in
testing at the factory.)
9. After the system resets, it will use the new JumpStart configuration.
If you want to go directly to Program Mode to configure any devices, press
4
- Enter Programming
4
. The Programming Menu appears and you can begin programming.
151209
6-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
6.2 Mapping Overview
This section of the manual is an overview of mapping. Details about how to select mapping
options appear in the appropriate subsections in Section 7.
Mapping is an important concept with the control panel. In general terms, mapping is
assigning or linking events to outputs that should activate when events occur. You do this by
assigning input points to input zones, output points to output groups and then linking or
mapping zones and output groups.
Figure 6-1 is a brief overview of the concept of mapping. The next several pages of the
manual show these subjects in detail.
Figure 6-1 Mapping Overview
6-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
6.2.1 Input Point Mapping
Input points are assigned to input zones. Any input point can be assigned to any input zone.
(Input points can be assigned to one zone only. An input point can be designated as “Unused,”
which means it has not been assigned to a zone.)
Figure 6-2 Input Point Assignment Example
151209
6-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
6.2.2 Output Circuit Mapping
Figure 6-3 is a simple example showing how to assign notification and relay output circuits to
groups. For an example of a simple floor above/floor below application, see Figure 6-5.
Figure 6-3 Assigning Output Circuits to Groups (Example)
6-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
6.2.3 Zone Event Mapping
There are 8 types of events that can occur in zones (see below). For each event type, you can
activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output
groups, an output group template may be used (see Section 7.5.5 for information on output
group templates). Event types are:
•
•
•
•
•
•
•
Manual Pull Alarm
Water Flow Alarm
Detector Alarm (heat or smoke detectors)
Aux 1 and Aux 2 Alarm (user-specified alarm types)
Pre-alarm
Supervisory
Trouble
Figure 6-4 Example of Zone Events Mapped to Output Groups and Patterns
151209
6-7
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
6.2.4 Mapping LED Points
Figure 6-6 is a simple example showing how LED points are mapped to zones and output
groups. Typically you would create two output groups for each zone, one for alarms and one
for troubles. (LED points are available when Models 5865-3/4 and/or 5880 are used with the
system.)
Figure 6-6 Example of LED Points Mapped to Output Groups
(applies to Models 5865-3/4 and 5880)
151209
6-9
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
6.3 Programming Using the 5660 Silent Knight
Software Suite
You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel
onsite or remotely. SKSS is an optional software package that lets you easily program the
control panel using a Windows-based computer and a modem* (not sold by Silent Knight).
When using SKSS, you can set up the programming options for the panel, save the options in
a file, then download the file to the panel. You connect to the control panel directly using the
control panel’s onboard USB or serial port or remotely using a modem. If you need to connect
to an older control panel that does not have a USB port, and your laptop does not have a serial
port, use a USB to serial converter. SKSS includes an online help system and a manual. See
the SKSS manual (PN 151240) for more information.
*
See Section 1.3 for a list of modems that have been tested for compatibility with the control panel and SKSS.
6.4 Programming Using an Annunciator
You can program the control panel from a system annunciator, using either the control panel’s
on-board annunciator or a Model 5860 Remote Annunciator.
The following subsections describe programming basics, including a description of editing
keys available for programming and how to move through programming menus. Section 7
contains specific information about individual programming options.
6-10
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
6.4.1 Entering & Exiting the Program Menu
To enter Program Mode:
1. Enter the Installer Code (factory programmed default code is 5820).
2. The display prompts you to press the
or
key to bring up the Main Menu (see Figure
Figure 6-7 Keypad Enabled Screen
7
Section 6.5 for a quick reference listing all programmable options and JumpStart defaults.
To exit Program Mode:
When you have completed working with the menus, press (left arrow) several times until
you are exited from programming mode. Two prompts will display. The first prompt is to
make sure you intended to leave the Program Menu (select Yes or No as appropriate). The
second prompt is for accepting all changes. If you select No, any changes you have made
since you entered the Program Menu will have no effect.
6.4.1.1 Moving through the Menus
Figure 6-8 shows how to move through Program Menu screens, using the System Options
screen as an example.
Figure 6-8 Moving through Program Menu
(System Options Sub-Menu Used as an Example)
151209
6-11
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
6.4.1.2 Selecting Options and Entering Data
There are several ways to make programming selections using the control panel depending on
which screen you are currently using. The chart below is a generic explanation.
To
Press
Select from a menu.
Enter the number of the option.
Enter numeric data.
Press the appropriate number on the annunciator.
Enter text (alphanumeric data).
Enter each letter individually by pressing and holding any numeric key until the
one you wish to select displays. Then press
Section 6.4 for complete information.
(right arrow) to select the letter. See
Select from a scrolling list.
Use
(up arrow) and
(down arrow) to move through a list of available
options. When the option you want to select is displayed, press
.
6.4.1.3 Editing Keys
The keys shown in Figure 6-9 are available for use when you are in the Program Menu.
Figure 6-9 Editing Keys Available from Program Menu
6-12
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
6.5 Programming Menu Quick Reference
This section of the manual lists all Program Menu options in the order they appear on the sub-
menus. Default settings are indicated in text or marked with an asterisk. The comments
column provide quick information and a reference to a section (if applicable) which has more
detailed information.
Menu
Options/Defaults
Comments
Hochiki
SK
SLC
Section 7.2
Family
Module
Edit Module
Select Module
5815XL-SLC
Enter Module Name Select Class
Section 7.3.1
5860-Keystation
5824-Ser/Par/IO
Add Module
5895XL-io/Pwr Sup
5496 NAC Expand
5880-LED/IO Dev
5865-LED Annunc
List of Modules
Delete Module
Section 7.3.3
View Module List List of Modules
Enter Name1
Enter Number1
Enter Name2
Enter Number2
Section 7.4.1.1
Edit Zone Name
Zone Properties
*1 Count
2 Count
Section 7.4.1.2
Alarm Ver.
PAS
Verification Type
SNGL ILOCK
DBL ILOCK
Manual Pull
Edit Zone
Select Zone to Edit
(MP)
(Groups 01 &
Zone
Water Flow
(WF)
250, Pattern
00)
Detector Alarm
Aux 1
Zone Outputs
Section 7.4.1.3
Aux 2
no group
Pre-alarm (PRE)
Supervisory
(SUP)
(Group 249,
Pattern 00)
Trouble (TRB) no group
Cadence
00-20
Section 7.4.1.5
Zone Accessory Opt
Local Zone
Yes or No
Add Zone
Adds next available zone number.
Select Zone to be Deleted
Section 7.4.2
Section 7.4.3
Section 7.4.4
Delete Zone
View Zone Points List of all points in selected zone.
151209
6-13
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Menu
Options/Defaults
Comments
Enter Name1
Enter Number1
Enter Name2
Enter Number2
Group Name
Section 7.5.1.1
Section 7.5.1.2
Latching
Options
*Non-
Latching
Latching
*SILENCE
Silenceable
Section 7.5.1.2
NON-SIL
Non-Silenceable
Section 7.5.1.2
Auto
Auto Un-silenced
Section 7.5.1.2
Silencing
Options
Unsilence
SIL-INHIB
Silence after inhib
delay. Section
Edit Group
Select Group
SHUT-
DOWN
Automatic
Shutdown
Group Properties
Section 7.5.1.2
Group
*No.
1
Group
all Man. Pull
Group
*Yes.
Fire Drill
Group Active
With:
Group
*No.
Aux 1
Group
*No
Aux 2
Ignore Global *No
Cadence
Section 7.5.1.2
Section 7.5.2
Section 7.5.3
Section 7.5.4
Section 7.5.5
Add Group
Delete Group
Select Group to Delete
View Group Points Select Group
Select Group
Yes
No
Select Template
Edit OPG Template
Number
Include in template
Select Pattern
0-16
6-14
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
Menu
Options/Defaults
Comments
UNUSED
PHOTO
ION
Select
Latching
HEAT
DETECTOR
SUP DET
PHOT DUCT
ION DUCT
2WIRE SMK
SUP PHOTO
SUP ION
MAN_PULL
Section 7.6
Select
Latching
LATCH
WATERFLOW
SUPERVSY
NLATCH
LATCH
NLATCH
FIREDRILL
SILENCE
RESET
PAS_ACK
LATCH
ZN_AUX1
ZN_AUX2
SYS_AUX1
Internal and
External 5815XL
Point
Enter Pt
NLATCH
LATCH
SWITCH
Section 7.6
NLATCH
LATCH
NLATCH
LATCH
SYS_AUX2
DETECT SW
TAMPER
NLATCH
LATCH
NLATCH
MAN REL
ILOCK
OUTPUT PT
AUX CONST
AUX RESET
AUX DOOR
OUTPUT PT
AUX RESET
AUX DOOR
Select Group
Select Group
NOTIF
Section 7.6
Section 7.6
RELAY
SLC LED
151209
6-15
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Menu
Options/Defaults
Comments
Enter Pt
Input Point Type
(detector/switch)
Select Function
Select Group
Per JumpStart
UNUSED
B NOTIF
A NOTIF
Select Type
CONSTANT
RESETABLE
DOOR
AUX PWR
MAN PULL
Select zone
Latch and Non-
latch feature only
appear for
WATERFLOW Select zone
SUPERVSY
TAMPER
Select zone
Select zone
waterfowl,
supervisory,
tamper, zone
aux1, zone aux2,
system aux1, and
system aux2.
DETECT SW
FIREDRILL
SILENCE
RESET
Section 7.6.
B SWITCH
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
Select zone
Select zone
Select zone
Internal Pwr and
External Power
Point
(cont.)
Section 7.6
Section 7.6
A SWITCH
Same as B SWITCH
2-WIRE SMK
4-WIRE SMK
2-WIRE SMK
4-WIRE SMK
B DETECTOR
A DETECTOR
Select Group or
Zone Number
Group or Zone
selection will
appear depending
on the type
selected.
Section 7.6
Edit Name
Enter Name
NOTIF
Section 7.6.3
Enter Point #
UNUSED
5880
Select Group #
Edit Name
Enter Name
NOTIF
Section 7.6.3
Enter Point #
UNUSED
5865
Select Group #
Edit Name
Enter Name
6-16
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
Menu
Options/Defaults
Comments
For each account (1-4), select:
*123456
Edit Account #
Account # (6-digit
number, identifies
account to central
station)
Section 7.7.1
Edit Format
*Contact ID Reporting Format
(SIA, S20,
Contact ID)
Section 7.7.1
Y (Yes)
N (No)
*Yes
*No
Section 7.7.1
Report Alarms
M (Must)
Y (Yes)
Rep. Alarm Restore N (No)
M (Must)
Y (Yes)
N (No)
Report Troubles
Edit Acct.
M (Must)
Y (Yes)
System
Options
Reporting
Accounts
Report Ena/Disable N (No)
M (Must)
Y (Yes)
N (No)
M (Must)
Y (Yes)
N (No)
M (Must)
1 - 5
Report Test
Report Resets
Switch attempts
Fail attempts
*5
Section 7.7.1
1 - 15
*10
Primary Phone Line 1 or 2
*Line 1
*Line 2
Secondary Phone
Line
1 or 2
Edit Phone #1
Set the Hour
up to 40 digits
blank
Auto Test Time
Set the Minutes
Select AM/PM
*02:00 AM
151209
6-17
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Menu
Options/Defaults
Comments
For each phone line (1 & 2), select:
Dialing Prefix
Up to 9 digits
none
06
Section 7.7.2.1
# of Answer Rings Range: 00-15
Number of rings
before panel
answers a call
from a computer
Section 7.7.2.2
TT
Touch Tone
TT/PL
Select Dialing
Option
TouchTone
alternating with
pulse see Section
TouchTone
Phone Lines
Select Phone Line
PULSE
Pulse dialing
U = 60/40
Rotary Pulse Format
E = 66/34
Section 7.7.2.4
*U
Yes
*Yes
Section 7.7.2.5
Section 7.7.2.6
Section 7.7.2.7
Section 7.7.3.1
Line Monitor
No
Yes = enabled
Ground Start
*N = Disabled
*Y = Enabled
None selected
None selected
None selected
No = disabled
Answering Machine Yes = enabled
Bypass
No = disabled
System
Options
(cont.)
Select Group
System Trouble
Select Cadence
Alarm Silence
Select Group
Select Cadence
Select Group
Select Cadence
Group Tr
Trbl Silence
SBUS Com
SBUS Pwr
SLC Loop
AC Loss
Trouble Events
Select Group
System Event
Outputs
Battery
User Selected
Gnd Flt
Phone Ln
Account
Select
Cadence
Printer
Aux Pwr
Sys Sw
Fire Drill
Section 7.7.3.2
Sys Alarm Cadence System Aux1
System Aux2
Select Cadence Constant
6-18
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming Overview
Menu
Options/Defaults
Comments
0 - 90 Seconds
*30 sec
*3 hrs
Water Flow delay
is the number of
sec. before water
flow alarm is
Water Flow Delay
generated. Section
0 - 30 hours
Low AC Report
Delay. Section
Low AC Delay
DST
Y (Enabled)
N (Disabled)
Automatic Daylight Saving Time
enable or disable. Section 7.7.4.3
and 7.7.6.3. See also DST settings
in Misc. Option 3, below.
Misc. Options 1
*Enabled
*AM/PM
AM/PM
MIL
System Clock
Format (AM/PM
or military).
CLK
Section 7.7.4.4
50 Hz
Section 7.7.4.5
AC Freq:
60 Hz
System
Options
(cont.)
Neither
Y (Enabled)
N (Disabled)
Y (Enabled)
Section 7.7.5.1
Section 7.7.5.2
Section 7.7.5.3
Section 7.7.6
SYNC Strbs w/ Sil
*Disabled
*Disabled
Misc. Options 2
Auto Display Oldest
Report By
N (Disabled)
Zone
*Zone
Point
Alarm Verification Enter time from 1 to
*60 Seconds
*Disabled
time
250 seconds
Y (Enabled)
N (Disabled)
Plex Door
DST Start
Misc. Options 3
also DST settings
in Misc. Options
1, above.
Select week: 1st,
Select month
2nd, 3rd, 4th or Last
DST End
Internal Message
Custom Message
Section 7.7.7
Edit Banner
Edit Line 1
Edit Line 2
No
Section 7.8
Section 7.9
JumpStart
AutoPrg
Yes
Computer Account
#
*5820
*0
Computer
Account
Computer Access
Code
Computer Phone # Up to 40 digits
151209
6-19
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Menu
Options/Defaults
Comments
Edit Name
Edit Access Code
System Reset
System Silence
System Event Ack.
Fire Drill Key
System Tests
Fire Drill Menu
Indicator Test
Walk Test no-Report
Walk Test w/Report
Dialer Test
Profile 1 is the profile that dictates
what functions the Firefighter Key
has access to. Because this is the
profile for a key the user name
and the access code can not be
edited for this profile.
Profile 2 is the profile for the
installer and is referred to as the
"Installer Code". This profile’s
user name and panel functions can
not be edited.
Clear History Buffer
Point Functions
Disable/Enable Point
Point Status
Access
Codes
Select Profile
(01 - 20)
Edit Panel Functions Set SLC Device Address
SLC Device Locator
SLC Multi-Device Locator
I/O Point Control
Event History
Set Time & Date
Printer Options
Event Logging
Print Event History
Print Detector Status
Print System Config
Reset Dialer
Program Menu
System Information
Upload/Download
1. Use of multiple notification groups may not synchronize with each other.
6-20
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7
Programming
This section of the manual describes how to manually program the control panel from the
built-in annunciator. Each subsection discusses these menu options in detail. All options
described in this section can be performed using the 5660 Silent Knight Software Suite
(SKSS).
Important!
Before any customized programming is done, JumpStart should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested
after JumpStart is because Jumpstart automatically programs the system, searching for
and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm
the integrity of the installation prior to performing any custom programming. After
determining that the hardware is properly installed, custom programming can be
7.1 UL 864 Programming Requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES: This product incorporates field programmable software. In
order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings Permitted in
UL 864
Programming Option
Menu Item
Phone Lines
Enable Gnd Start
No
Yes & No
No
Misc Options 1
Low AC Report Delay
Yes
0–30 hours
1–3
151209
7-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.2 SLC Family
The 5820XL supports Hochiki protocol SLC devices or SK series SLC devices. You must
configure the 5820XL to accept the protocol of the devices you are installing. You cannot mix
SLC devices of different protocols.
1. Press or
to display the main menu.
2. Enter the installer code if requested.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
0
4. Press to enter module menu.
5. Press
6. Press
to select the desired SLC device type.
to accept the displayed SLC device type.
7.3 Modules
This section lists the options available under the module option in the program menu. The
following modules are available for the control panel: 5815XL SLC expander, 5860 remote
fire alarm annunciator, 5824 serial/parallel printer interface module, 5496 intelligent power
module, 5895XL intelligent power module, 5880 LED I/O module, and 5865 LED
annunciator.
7-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.3.1 Edit Modules
The features that can be edited when this option is selected are module name and class of
wiring (Class A or Class B), or features that are specific to the module to be edited.
To edit an existing module:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
1
4. Press to enter module menu.
1
5. Press to edit a module.
6. Use the
or
arrow to select the module you wish to edit.
7.3.1.1 Naming Modules
You can assign an English name to a system hardware module to make it easier to recognize
on a display.
7. If you wish to edit the modules name press the
or
arrow to select each character
for the modules name (or press to bypass name edit).
Press the to move to the next character.
Figure 7-1 Edit module Name Programming Screen Example
151209
7-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.3.1.2 Setting the 5815XL Wiring Class
8. Choose the class of wiring you wish to use for this module by pressing the
or
arrow, then press
.
7.3.2 Adding a Module
If you need to add a new hardware module to the system, follow these steps.
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
1
4. Press to enter module menu.
2
5. Press to add a module.
6. From the next screen, select the number that corresponds to the type of module you are
adding from the <New Module Type> screen.
The screen will display “Adding module [#]...” for a few moments. You will be returned to
the <New Module Type> screen where you can select another module if desired.
You must save changes when you exit the Program Menu or the new module will not be
added.
Note: If you Add a Module that has not been physically connected, the panel will go into trouble after it
reinitializes (when you exit the Program Menu). When the new module is attached, the trouble will correct
itself automatically the next time you power up the system.
7-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.3.3 Deleting a Module
If you ever need to delete a module, follow these steps.
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
1
4. Press to enter module menu.
3
5. Press to delete a module.
6. A warning screen will display. If you want to proceed with deleting the module, select
Yes. To cancel, select No.
7.4 Zone
Through the zone option in the program menu you can edit, add, delete, and view zone points.
Selections made here affect all detectors and switches in the zone. Up to 125 zones can be
used in the system.
7.4.1 Edit Zone
Features that can be edited through the edit zone option are, edit zone name, zone properties
(which includes, zone type, and detector sensitivity), and zone output mapping.
To edit a zone, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
2
4. Press to enter zone menu.
1
5. Press to edit a zone.
6. Enter the zone number, then press
.
151209
7-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.4.1.1 Edit Zone Name
1
7. Press to edit the selected zone’s name.
A screen similar to the one shown in Figure 7-2 displays.
Figure 7-2 Selecting Character for Zone Name
8. Select the characters for the zone name by pressing the
or
arrow until the desired
character is shown then press
OR
.
a list of available characters and their numeric designators.
9. Repeat step 8 until the name is complete.
10. Press
when the name is complete.
7.4.1.2 Edit Zone Properties
Zone properties consist of alarm delay characteristics, and heat detector sensitivity.
2
2. Press to edit the properties of the selected zone.
Detection type also selected from this screen
(see Table 7-1).
7-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Alarm Delay Characteristics
or
arrow.
Table 7-1: Alarm Delay Characteristics
Type of Delay
Description
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device
of any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is
considered the most typical operation and is the default for all zones.
1-Count
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order
for the zone to report an alarm. Switches of type manual pull, water flow, Aux1 and Aux2 are an
exception; they will cause an alarm when only one switch is in alarm.
2-Count
When a single detector is in alarm in a 2-Count zone, the system enters a prealarm condition. In a
prealarm condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has
occurred. If the zone has been mapped to an output group for the prealarm event, the output group will
activate. The prealarm will not be reported to the central station.
Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by
resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has completed,
the detector will go into alarm. If the detector is no longer in alarm, no report will go to the central
station. The alarm verification sequence is ignored if the zone is already in alarm.
Alarm Ver.
This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds,
giving on-site personnel a chance to investigate the alarm. If the acknowledge switch is not activated
within 15 seconds, an alarm occurs automatically.
If this option is enabled for a zone, the zone will respond to an alarm condition as follows:
• The zone will not go into alarm for 15 seconds to allow an on-site operator to activate the acknowl-
edge switch.
PAS
• If the operator does not press the acknowledge switch within 15 seconds, the zone will go into
alarm.
• If the operator presses the acknowledge switch within 15 seconds, a 180-second time-frame will
begin counting down. This time-frame allows the operator to investigate the cause of the alarm.
If the operator performs a reset within 180 seconds, the alarm will not occur. If the operator does
not perform a reset within 180 seconds, an alarm will occur automatically.
• The P.A.S. feature will be overridden if another alarm occurs.
See Section 8.7.1 for single interlock releasing operation.
See Section 8.7.2 for double interlock releasing operation.
SNGL ILOCK
DBL ILOCK
4. Press
.
Heat Temperature Setting
Use this feature to set the temperature at which heat detectors will respond. The range is 135°
to 150° F. All detectors in the zone will respond in the same way.
The Model SD505-AHS Heat Detector is an absolute temperature device. This means that it
responds to an alarm immediately if the temperature in the zone goes above the programmed
temperature.
5. Enter the temperature at which the heat detector will respond.
Or
Use the
on the annunciator, then press
6. Use the or keys to scroll through the range or enter directly from the number keys
on the annunciator.
or
keys to scroll through the range or enter directly from the number keys
.
151209
7-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7. Then press
.
7.4.1.3 Zone Outputs
Output groups and cadence patterns are mapped to events. They can be programmed to output
when an event occurs in a zone. Some system trouble events can be mapped for the entire
system. Section 6.2 of this manual contains a general explanation of mapping. The following
sections explain how to select mapping options.
Note: Use of multiple notification groups may not synchronize with each other.
Mapping to Zone Events
Eight types of events can occur in zones. For each event type, you can activate up to 8 output
groups or output group template, specifying a pattern for each. The following is a list of all
event types:
Note: Abbreviations in the parenthesizes are the characters that are displayed in programming (see
•
•
•
•
•
•
•
Manual Pull Alarm (MP)
Water Flow Alarm (WF)
Detector Alarm (DE). This applies to heat or smoke detectors.
Aux 1 and Aux 2 Alarm (A1 or A2). User-specified alarm types.
Pre-alarm (PR)
Supervisory (SU)
Trouble (TR)
To map zone events to outputs:
7
1. From the Installer Main Menu, select for Program Menu.
2
2. From the Program Menu, select for Zone.
1
3. From the next menu, select for Edit Zone.
4. Enter the zone number you wish to edit.
3
5. From the next menu, select for Zone Outputs.
6. From the next screen, a list of 8 event types will display. Select the event type you want to
7. Press the or key to toggle the group letter to either G = Group or T = output group
template depending on want you need for this zone. Press
.
.
7-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
ple of how you might map a zone.
Indicates output group 1, cadence
pattern 00 has been selected. 00 is
a constant output cadence.
Indicates type of event (in
this case, Manual Pull alarm).
“T” Indicates output group
more information on output group
templates.
Figure 7-3 Selecting Output Groups/templates and Cadence Patterns for a Zone Event
Zone Mapping Example
Suppose you want to program Zone 1 so that:
•
Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the
ANSI cadence pattern.
•
•
Manual pull alarm would activate Output Group 3 using constant output.
Troubles would activate Output Group 2 using the zone-coded cadence pattern.
To accomplish this you need to access the screen for each event and then select your output
151209
7-9
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
groups. Figure 7-4 shows how you would program this application.
Figure 7-4 Zone Mapping Example
7-10
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.4.1.4 Cadence Patterns
The cadence patterns shown in Figure 7-5 are available for use with the control panel.
Cadence patterns can be selected by event type for each zone or for the entire system. Special
cadence patterns can be selected for fire drills and any auxiliary system switches used with the
system.
Figure 7-5 Cadence Patterns Available with the Control Panel
7.4.1.5 Zone Accessory Options
This option applies to detectors that are used with SD505-6SB, SD505-6RB, and
SD505-ADHRs.
Single or Multi-station cadence pattern (choose from Patterns 00 to 21).
Local Zone (choose Y or N, for Yes or No).
151209
7-11
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.4.2 Add Zone
To add a zone, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
2
4. Press to enter zone menu.
2
5. Press to add a zone.
A zone will be added. The system will assign the next available zone number. Options for
this zone can now be programmed through the Zone Edit sub-menu. Up to 125 zones can
be used.
7.4.3 Delete Zone
To delete a zone, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
2
4. Press to enter zone menu.
3
5. Press to delete a zone.
A warning screen will display. If you want to proceed with deleting the zone, select Yes.
To cancel, select No.
7-12
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.4.4 View Zone Points
To view the points in a zone, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
2
4. Press to enter zone menu.
4
5. Press to view zone points.
6. Enter the number of the zone you wish to view, then press
.
Zone Number
Module or
Device Address
Point Number
Total Number of
Points in the Zone
Figure 7-6 View Zone Points Screen
151209
7-13
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.5 Group
An output group is made up of output points that have been programmed to respond in the
same way. Output groups simplify programming because you have to program the output
characteristics that are common to all of the group points once, instead of programming each
individual point. Once you have defined the characteristics of output groups, you can assign
each point to the appropriate group. All valid output points are assigned to only one output
group. Unused points are not assigned to any output group. Up to 250 output groups can be
defined.
7.5.1 Edit Group
In the edit group option you can program the name of an output group (Section 7.5.1.1) and
change the properties (Section 7.5.1.2) of that group.
To edit a group, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
3
4. Press to enter group menu.
1
5. Press to edit group.
6. Enter the number of the group you wish to edit, then press
.
7.5.1.1 Edit Group Name
1
7. To edit the group name, press
.
A screen similar to the one shown in Figure 7-2 displays.
Figure 7-7 Selecting Character for Zone Name
7-14
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
8. Select the characters for the zone name by pressing the
or
arrow until the desired
character is shown then press
OR
.
of this manual for a list of available characters and their numeric designators.
9. Repeat step 8 until the name is complete.
10. Press
when the name is complete.
7.5.1.2 Edit Group Properties
The Edit Group Menu allows you to select options for each group for the following items:
•
•
•
Latching or non-latching outputs.
Silencing operation.
Operation with system switches.
Figure 7-8 Group Properties Screen Programming Options
Latching / Non-latching Outputs
Outputs that are programmed as Latching remain active until the system has been manually
reset. Non-latching outputs stop activating automatically when the condition clears.
Silencing Options
The following silencing options are available for each output group.
Table 7-2: Silencing Options
Option
SILENCE
Description
SILENCE
Silenceable. The output group can be silenced through the
key.
SILENCE
NON-SIL
Not silenceable. The output group cannot be silenced. Activation of the
ignored for this output group.
key will be
151209
7-15
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table 7-2: Silencing Options
Option
Description
AUT UNSIL
Auto Unsilenced. If this option is selected, the output group can be silenced for a programmed time-
frame. If the condition that caused the output to activate has not cleared during the time-frame, the
output reactivates. If you select this option, select the time-frame in the DLY: field. Range is 00-60
SIL-INHIB
Timed Silence after Inhibit. If this option is selected, the output group must be audible for a
programmed number of minutes before it can be silenced. If the condition that caused the output to
activate has not cleared during the time-frame, the output can be silenced. If you select this option,
select the timeframe in the DLY: field. Range is 00-60 minutes. (See Figure 7-8 for location of field.)
SHUT-DOWN
If this option is selected, the output group will automatically silence (shut down) after the
programmed time period. If you select this option, select the timeframe in the DLY: field. Range is
Response with System-Wide Conditions
You can select whether an output group will respond to various system-wide occurrences.
Table 7-3: Output Group Response Choices
Option
Description
ManPull
Manual Pull Activation. Select Yes if you want this group to activate for all manual pull
alarms that occur in the system.
Note: Even though manual pull switches are assigned to zones, activation
selected here for manual pull will override zone-programmed activation.
Fire Drill
Fire Drill Activation. Select Yes if you want this group to activate for fire drills.
Sys Aux1 and Sys Aux2
Ignore Global Cad
Select Yes if you want this output group to activate for system-wide Aux1 and Aux2
alarms.
(Aux 1 and Aux 2 alarm types are for auxiliary alarm conditions. For example, you
might want to use Aux 1 to provide a unique alarm type.)
Ignore Global Cadence. If you want to create an output group that can never be
overridden, you can select Yes for this option. Selecting No means that system-wide
events that have been assigned an output pattern could override the pattern for the
output group.
For example, suppose you had assigned a set of strobes to Output Group 3. You would
never want these strobes to output in a pattern under any circumstances. To make sure
this happens, select Yes for Ignore Global Cadence for Output Group 3.
Reverse Polarity
This option programs the output group for reverse polarity operation. Selecting Reverse
Polarity–Troubles will cause the output group to be de-energized for any system
trouble. Selecting Reverse Polarity–No Troubles will cause system troubles to be
ignored. Activation is accomplished through standard mapping methods. Use with the
information on the 7644.
11. To get to this menu item repeat steps 1 through 6 of Section 7.5.1.
2
12. To edit group properties, press
.
13. Press the
or
or
arrows to select the desired latching option.
14. Press
.
15. Press the
arrows to select the desired silencing option. Refer to Table 7-2.
7-16
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
16. Press
.
select Y (yes) or N (no).
or
arrows to
18. Press
.
19. Repeat steps 14 and 15 for all the activation options.
7.5.2 Add Group
To add a group:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
3
4. Press to enter group menu.
2
5. Press to add a group.
The system will assign the next available group number. Properties for the new group can
7.5.3 Delete Group
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
3
4. Press to enter group menu.
3
5. Press to delete a group.
A warning screen will display. If you want to proceed with deleting the group, select Yes.
To cancel, select No.
151209
7-17
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.5.4 View Group Points
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
3
4. Press to enter group menu.
4
5. Press to view group points.
6. Enter the group number, then press
.
7.5.5 Edit Output Group Templates
Some installations may require that zones be mapped to more than 8 output groups. With
output group templates you can combine one or all output groups into one template, which can
be used when the same combination of outputs are used for several zones.
what output groups are mapped to each zone. You will notice that every zone is mapped to
outputs 1 and 2. As an alternative you can create a template that combines output group 1 and
2 as one choice.
Table 7-4: Zone Group Example
Group Number
Zone
1
2
3
4
5
6
7
8
1st Floor Smoke Detectors
2nd Floor Smoke Detectors
3rd Floor smoke Detectors
Manual Fire Pull Stations
Water Flow Switches
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
This can be done by creating a template which includes output groups 1 and 2. Then you can
map all the zones to the template you created. This will free up output group assignments that
are common to several zones. This is very useful when you need to map zones to more than
7-18
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
eight output groups.
To create Output Group Templates:
7
1. From the Main Menu, select for Program Menu.
3
2. From the Program Menu, select for Group.
5
3. At the next screen, select for Edit OPG Template.
4. Select the template number (01 - 08).
Yes = Include the selected
output group in this template
Output
Group #
No = Do Not include output
group in this template
Select the
Cadence Pattern
Figure 7-9 Output Group Template Programming Screen
7.6 Point
You may need to change characteristics of individual input points (detectors and switches)
even after using JumpStart. This section explains how to change options for: type of input
point; latching/non-latching status (switches); and name and zone assignment of a point.
7.6.1 Point Programming For 5815XL Module
To program for an 5815XL Module points, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
4
4. Press to enter point menu.
5. Press the
or
ence Table for available choices.
6. Press
.
7. Enter the number of the point you wish to edit.
151209
7-19
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8. Press
.
9. Select the type of device by pressing the or
umn heading “Type Selection” for a list of choices.
Table 7-5: Point Programming Options for 5815XL Modules
Type
Selection
Latching
Option
Function
Comments
UNUSED
PHOTO
ION
HEAT
PHOT DUCT
ION DUCT
2WIRE SMK
SUP PHOTO
SUP ION
DETECTOR
SUP DET
Latching
Non Latching
7-20
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Table 7-5: Point Programming Options for 5815XL Modules
Latching
Type
Selection
Function
Comments
Option
Use this switch type for manual pull stations. This input is always latched.
The switch can clear only when an alarm is reset. This switch type has the
highest priority; it overrides any other type of alarm.
MAN_PULL
Latching
Use this switch type for monitoring water flow in a sprinkler system. Switch
closure will cause a sprinkler alarm. Water flow switches can be
programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with a water flow
switch. The delay allows for normal, brief changes in sprinkler system water
pressure. The water flow alarm will not activate unless the switch is active
for the programmed delay time.
WATERFLOW
Non Latching
If a delay is used, the system begins counting down when the switch closes.
If the switch opens (restores) before the timer expires, a water flow alarm is
not generated. If the water flow switch remains closed after the timer
expires, a water flow alarm will be generated.
Latching
Use this switch type for tamper monitoring of sprinklers and other fire
protection devices. If a contact closes, a sprinkler supervisory event will be
generated. Supervisory switches can be latching or non-latching.
SUPERVISY
FIREDRILL
Non Latching
SWITCH
System-level, non latching switch. This switch is an alternative way of
causing a fire drill. It has the same operation as the fire drill option available
from the annunciator. When the switch is activated, a fire drill begins; when
the switch is de-activated, the fire drill ends.
This system-level switch is an alternative way to silence the system. It has
SILENCE
RESET
SILENCE
the same effect as pressing the
This system-level switch is an alternative way to reset the system. It has the
RESET
key.
same effect as pressing the
key.
Positive acknowledge switch. This switch must be used in zones
programmed as Positive Alarm Sequence (see Table 7-1).
If an acknowledge switch closes when an alarm or trouble condition is not
already in progress, a trouble will occur.
PAS_ACK
You must use a UL listed normally open, momentary switch type. The
switch must be rated at 5V, 100 mA (minimum) and be used with an EOL
resistor for supervision.
151209
7-21
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table 7-5: Point Programming Options for 5815XL Modules
Type
Selection
Latching
Option
Function
Comments
Latching
Use these switch types if you want to monitor special zone-level conditions
(such as operation of a fan or damper).
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
DETECT SW
TAMPER
Non Latching
Latching
Non Latching
Latching
Use these switch types if you want to monitor special system-wide
conditions (such as operation of a fan or damper).
Non Latching
Latching
SWITCH
(cont.)
Non Latching
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
Latching
Performs identically to a supervisory switch, but will be indicated as a
tamper switch on the LCD annunciator.
Non Latching
Latching
Manual release switch, typically a pull station.
MAN REL
Non Latching
Latching
Interlock release switch input.
ILOCK
Non Latching
Output Point, a general use notification type. Use for driving standard
notification appliances.
OUTPUT PT
AUX CONST
AUX RESET
Select Group
Use constant power for applications that require a constant auxiliary power
source. Power is always present at Constant circuits.
NOTIF
description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
AUX DOOR
Output Point, a general use relay type. Use for applications requiring a relay,
such as fan shutdown, elevator recall, and so on.
OUTPUT PT
AUX RESET
Select Group
Select Group
description of how this option operates.
RELAY
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
AUX DOOR
Select Group
7-22
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Table 7-5: Point Programming Options for 5815XL Modules
Latching
Type
Selection
Function
Comments
Option
Select LED No.
01 -80
SLC LED
Select Group
151209
7-23
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.6.2 Point Programming For Internal or External Power
Module (5895XL)
To program for an internal or external power module points:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
4
4. Press to enter point menu.
5. Press the
choices.
or
arrows to select the desired module. Refer to Section 6.5 for available
6. Press
.
selections.
8. Press
.
9. Select the type by pressing the
or
arrows.
10. Press
.
11. Select the function by pressing the
or
arrows.
12. Press
.
13. Select the zone by pressing the
or
arrows.
14. Press
.
7-24
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
Or
Press to skip point name edit.
16. Repeat Steps 1 through 15 for all circuits.
Table 7-6: Menu choices for Internal/External Power Module
Function
Selections for
each Type
Choices
Type Selections
Comments
Enter Point or Circuit
UNUSED
B NOTIF
A NOTIF
CONSTANT
RESETTABLE
DOOR
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Refer to comments column of
AUX PWR
MAN PULL
WATERFLOW
SUPERVSY
TAMPER
Table 7-5 for description of these
options.
Latch or Non-latching feature only
appears for waterflow, supervisory,
tamper, zone aux1, zone aux2, system
aux1, and system aux2.
FIREDRILL
SILENCE
Select Type
RESET
B SWITCH
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
A SWITCH
Same as B SWITCH Used for
2-WIRE SMK
4-WIRE SMK
2-WIRE SMK
4-WIRE SMK
Used for Class B, 2-wire detectors.
B DETECTOR
Used for Class B, 4-wire detectors.
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
A DETECTOR
Select Zone/Group
Edit Name
Group or Zone selection will appear
depending on the type selected.
See Section 7.3.1.1.
151209
7-25
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.6.3 Point Programming For 5880 and 5865 Modules
To program 5880 or 5865 module points:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
4
4. Press to enter point menu.
5. Press the
choices.
or
arrows to select the desired module. Refer to Section 6.5 for available
6. Press
.
Figure 7-10 Programming Points Screen for 5880 and 5865 Modules
7. Enter the point number.
8. Press
.
.
.
9. Press the
or
or
arrows to select the type (Notification or unused).
arrows to select the desired Group.
10. Press
11. Press the
12. Press
Or
Press to skip module name edit.
7-26
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
14. Repeat Steps 1 through 13 for all points.
7.6.3.1 Assigning a Name to Points
You can assign a name to a point to make it easier to recognize on a display.
To edit a point name:
2. Using the
or
arrow, select the module of the point you want to edit, press
.
3. Enter the point number.
4. Press until the module name is blinking.
5. Press
.
A screen similar to the one shown in Figure 7-2 displays.
Figure 7-11 Selecting Character for Zone Name
6. Select the characters for the point name by pressing the
or
arrow until the desired
character is shown then press
OR
.
for a list of available characters and their numeric designators.
7. Repeat step 6 until the name is complete.
8. Press
when the name is complete.
7.7 System Options
This section of the manual explains how to customize software options that affect general
operation of the system. This includes such items as: AC loss hours, system clock options,
holidays schedule, telephone and reporting account options. Refer to each individual
subsection for complete instructions.
151209
7-27
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.7.1 Reporting Account
Up to four reporting accounts can be used with the control panel. Events in accounts are
reported by zone.
Each account is assigned an up-to-6-digit account number. Each account is also assigned a
unique ID (1-4) which determines the priority for reporting ("1" has the highest priority; "4"
has the lowest).
Disable any unused accounts by selecting “N” for all events (see Figure 7-12). If the system is
local only (does not connect to a central station), disable all events for all four reporting
accounts.
Options for each account can be customized. These options appear on the Reporting Accounts
screen. Some related options appear on the Phone Lines screen (see Section 7.7.2).
To access the Reporting Accounts screen:
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select for Program Menu.
Display reads: Initializing
7
Please wait . . .
5
4. From the Program Menu, select for System Options.
0
5. From the next menu, select for Reporting Accounts.
7-28
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.7.1.1 Edit Accounts
1
6. From the next menu, select for Edit Account.
describe the options on each field.
Figure 7-12 Reporting Account Editing Screen
Select Account (ID)
The control panel provides up to 4 reporting accounts. The priority of an account is based on
its account ID. Account 1 is highest priority; Account 4 is lowest. Use Account 1 to report the
highest priority events.
7. Press the
or
arrow to select account ID number, then press
.
Edit Account Number
Enter an up-to-6-digit number for each account to identify the account to the central station.
See Figure 7-12 for location of this option on the screen. The account number should be
compatible with the reporting format used. For example, the Contact ID format transmits up
to four digits only.
8. Enter the desired account number (up to 6-digits), then press
.
Select Reporting Format
Select a reporting format for each account. Options are:
SIA
CID
S20
SIA format. 8 events per call.
Ademco’s Contact ID format
Same as SIA but limits events reported to 20 events per phone call.
9. Press the
or
arrow to select the reporting format, then press
.
151209
7-29
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Events to Report
The next six options select which types of events (or event families) will be reported to this
account. (See Figure 7-12 for location of these options on the screen.) Events are reported by
zone.
Event Family
Events Included in this Family
Alarms
All alarms (Water Flow, Manual Pull, Detectors, Auxiliary Switches)
All alarm restores.
Alarm Restore
Supervisory/Trouble
Enable/Disable Point
Service/Test
All trouble and supervisory conditions and trouble and supervisory restores.
Enabling and disabling of input and output points.
Fire drill, walk test, dialer test, automatic test, all programming sessions.
All system resets.
System Reset
10. Press the
or
arrow to select Must, Yes, or No (see table below), then press
.
11. Repeat step 10 for all six event report options.
For each event family, select M, Y, or N.
M(ust)
Must Report. Selecting "M" makes this a primary reporting account for this family of events. The dialer
MUST report events in this family to this account.
Selecting Must makes an account a primary reporting account. The dialer will try to report the event to
the primary account until it exceeds the "Switch Attempts" value. When the dialer has exceeded the
Switch Attempt retry limit, it will switch to a backup account (a "Can Report" or "Yes" account, see
below). If the dialer cannot report the event to any of the backup accounts, it will return to the primary
account and repeat the process until it exceeds the "Fail Attempts" value. If the Fail Attempts limit is
exceeded, an Account Trouble condition is generated and a local trouble will sound.
Y(es)
N(o)
Can Report. Selecting Y makes this a backup account for this event family. The dialer will report to this
account only if it was previously unable to report the event to a Must account.
No events in this family will ever be reported to this account.
Switch Attempts
Specify the number of times the dialer should attempt to report to this account before
switching to the next account. Range is 01-15.
12. Enter the number of switch attempts (or press the
or
arrow), then press
.
Fail Attempts
This feature specifies the number of times the dialer should attempt to perform the dial/switch
sequence before issuing an account trouble condition. Range is 01 - 15 (Default = 10).
13. Enter the number of fail attempts (or press the
or
arrow), then press
.
Selecting Primary and Secondary Phone Lines
For each account, select which phone line (Line 1 or Line 2) is primary. See Figure 7-12 for an
example of how to make this selection.
14. Press the
or
arrow to select line 1 or 2 as primary phone line, then press
.
7-30
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
15. Repeat step 14 for the secondary phone line.
Telephone Number
Enter up to 40 characters for phone number for this account.
The following special characters are available:
Table 7-7: Special Character for Dialing
#
*
,
Pound (or number) key on the telephone
Star key on the telephone
Comma (character for 2-second pause)
Use the number buttons on the annunciator or the up- and down-arrow keys to select special
characters. Characters begin displaying after “9”. See Figure 7-12 for an example.
151209
7-31
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.7.1.2 Auto Test Time
To access the automatic dialer test time screen:
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select for Program Menu.
Display reads: Initializing
7
Please wait . . .
5
4. From the Program Menu, select for System Options.
0
5. From the next menu, select for Reporting Account.
2
6. From the next menu, select for auto test time.
7. Enter the hour you desire the control panel to send an automatic test report (or press the
or
arrow), then press
.
8. Enter the minutes (or press the
9. Select AM or PM by pressing the
or
arrow), then press
arrow, then press
.
or
.
7.7.2 Phone Lines
To access the phone lines screen:
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select for Program Menu.
Display reads: Initializing
Please wait . . .
7
5
4. From the Program Menu, select for System Options.
1
5. Select for the phone lines menu.
7-32
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
6. Select the phone line to be edited (1 or 2) by pressing the
or
arrow, then press
.
Figure 7-13 Phone Lines Editing Screen
7.7.2.1 Dialing Prefix
Enter up to 8 characters to be used for such things as PBX dial-out codes, a pause, and so on.
The following special characters are available:
#
*
,
Pound (or number) key on the telephone
Star key on the telephone
Comma (character for 2-second pause)
Use the number buttons on the annunciator or the up- and down-arrow keys to select special
characters. Characters begin displaying after “9”. See Figure 7-13 for an example.
7. Enter a dialing prefix (if needed), then press
Or
.
Press to bypass the dialing prefix option.
151209
7-33
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.7.2.2 Number of Answer Rings
This option is used in conjunction with the 5660 SKSS. Use the option to determine the
number of rings before the panel answers a call from the computer. Range is 00-15 rings. This
option is factory-programmed as 06 rings, which should be compatible for most installations
where the answering machine bypass feature is used. You may need to adjust it depending on
the installation’s telephone system.
The selection made here must match the programming for this option in the Communication
Configuration dialog box of the 5660 SKSS. See the software manual for more information
(PN 151240).
8. Enter the desired number of answer rings, then press
.
7.7.2.3 Dial Option (TouchTone or Pulse)
9. Press the
or
arrow to select the dial option, then press
.
Dial Option
Description
PULSE
TT
If this option is selected, only pulse dialing will be used for this phone line.
TouchTone dialing. If this option is selected, only TouchTone dialing will be used for this
phone line.
TouchTone alternating with pulse. If this option is selected, the dialer will first attempt to
use TouchTone. It will switch to pulse if TouchTone is not successful on the first attempt.
It will continue to alternate between TT and pulse for additional attempts.
TT/PL
7.7.2.4 Rotary Format
10. Press the
.
or
arrow to select the pulse ratio for rotary dialing option, then press
Options are:
U
E
U.S. standard format. Uses the 60 msec / 40 msec make/break ratio.
European format. Uses the 66 msec / 34 msec make/break ratio.
7.7.2.5 Line Monitor
Enable the line monitor for each phone line that will be used. See Figure 7-13 for location of
this field on the phone lines screen. When the phone line monitor has been enabled for a
phone line, a trouble condition will occur if the line is not connected. If a phone line will not
be used, it must be disabled.
11. Select Y (monitor line) or N (don’t monitor line) by pressing the
press
or
arrow, then
.
7.7.2.6 Ground Start Relay
If using the 5211 ground start relay, you must enable the ground start relay programming
option. See Figure 7-13 for the location of this field on the phone lines screen. This option is
7-34
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
disabled by default. For 5211 installation, see Section 4.12.
Note: Ground start cannot be used in UL installations.
12. Select Y (ground start used monitor line) or N (ground start not used don’t monitor line)
by pressing the or arrow, then press
.
7.7.2.7 Answering Machine Bypass
This option is used in conjunction with the 5660 SKSS. This feature ensures that an answering
machine will not interfere with communication between the panel and the computer. If an
answering machine is used at the panel site, enable this feature; if an answering machine is not
used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication
Configuration dialog box of the 5660 SKSS. See the 5660 SKSS manual for more information
(PN 151240).
13. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled)
by pressing the
or
arrow, then press
.
7.7.3 Sys. Event Outputs
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select for Program Menu.
Display reads: Initializing
7
Please wait . . .
5
4. From the Program Menu, select for System Options.
2
5. From the System Options Menu, select for Sys. Event Outputs.
151209
7-35
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.7.3.1 Trouble Events
You can map certain system trouble events to an output group. To access the screen for
selecting output groups and cadence patterns for system trouble events.
1
a group and a cadence pattern for each event as needed for your application. The U: field
is for a user-specified trouble condition. You can program an output group and cadence
pattern for any of the following events:
Battery
Low battery condition.
Gnd Flt
Ground fault.
Phone Ln
Account
Printer
Phone Line 1 or 2 trouble.
Account trouble; cannot report to account.
Printer trouble. (Currently not supported; do not select.)
Auxiliary power trouble.
Aux Pwr
Sys Sw
Trouble with a system switch.
Trouble with an output group.
SBUS communication trouble.
SBUS power trouble.
Group Tr
SBUS Com
SBUS Pwr
SLC Loop
AC Loss
Trouble on the SLC loop.
AC power lost.
Figure 7-14 System Trouble Event Mapping Example
7-36
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.7.3.2 System Alarm Cadence
Fire drill and system auxiliary alarm events can have special cadence patterns to distinguish
A typical use of the System Aux1 and Aux2 patterns is to distinguish fire emergencies from
other types of emergencies. The System Aux1 and Aux2 alarms would be triggered by a
system-wide switch.
To access the screen for selecting output groups and cadence patterns for system trouble
events:
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select for Program Menu.
Display reads: Initializing
7
Please wait . . .
5
4. From the Program Menu, select for System Options.
2
5. From the System Options Menu, select for Sys. Event Outputs.
2
6. Press for System Alarm Cadence.
special events if required for your application.
Figure 7-15 Special Cadence Patterns for Fire Drill and Auxiliary Alarm Events
151209
7-37
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.7.4 Miscellaneous Options 1
Through this programming option you can set the water flow delay time, low AC report delay,
enable or disable automatic daylight savings time adjustment, clock format, and AC clock
frequency.
7.7.4.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction
with a water flow switch. The delay is system-wide. All water flow switches on the system
will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
5
4. Select for System Options.
5
5. Select for Miscellaneous Options 1.
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)
Figure 7-16 Water Flow Delay Programming Screen
7-38
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
6. Enter the number of seconds (0 to 90 ) to delay an a water flow switch alarm, then press
.
151209
7-39
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.7.4.2 Low AC Report Delay
Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a Low AC report will be sent to the central station.
To program low AC report delay, follow these steps:
Low AC Report
Delay in Hours
(00 - 30)
Figure 7-17 Low AC Report Delay Programming Screen
7. Enter the number of hours before a low AC report will be sent to the central station, then
press
7.7.4.3 Automatic Daylight Savings Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. Before
January 2007, if this feature is enabled (set to Yes), the system clock will switch to DST on the
first Sunday in April at 2:00 a.m. and revert to standard time on the last Sunday in October at
2:00 a.m. After January 2007, if this feature is enabled, the system clock will start and end
DST according to the settings made in Misc. Options 3 (see Section 7.7.6.3). If this feature is
not enabled (set to No) the Daylight Saving Time change is not made to the system clock.
To enable or disable DST adjustment continue programming form step 7 above:
8. Select Y (enabled) or N (disabled) by pressing the
or
arrow, then press
.
7.7.4.4 Clock Display Format (AM/PM or Military)
To change the system clock display format, continue programming from step 8 above:
9. Select AMPM (for AM/Pm display format) or MIL (for military or 24 hr display format)
by pressing the or arrow, then press
.
7.7.4.5 Change AC Line Frequency
The panel’s AC line frequency is selectable for 50, 60 Hz, or Neither. AC Frequency feature
dictates how the control panel will calculate time based on the AC line frequency used in the
installation site. The "Neither" option can be used in areas where the AC line frequency is not
dependable and you want the panel to calculate time from the internal crystal. The internal
crystal is not as accurate as the AC power source and either 60 Hz or 50 Hz should normally
selected. The panel defaults to the 60 Hz. selection
To change the AC line frequency, continue programming from step 9 above:
10. Select 50, 60 or Neither, by pressing the
or
arrow, then press
.
7-40
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.7.5 Miscellaneous Options 2
Through this programming option you can turn the strobe synchronization during silence
feature On or Off, and select the control panel to report events by zone or by point.
To edit miscellaneous options 2:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
5
4. Select for System Options.
6
5. Select for Miscellaneous Options 2.
7.7.5.1 Synchronize Strobes Active During Silence
When "SYNC Strbs w/ Sil:" is Selected as Y (Yes) then strobes will continue to flash when the
system is silenced and will stop flashing when the system is reset.
Note: The "SYNC Strbs w/ Sil:" only functions with outputs that use a synchronized output pattern.
6. Press the
7. Press
or
arrow to toggle this selection between Y (Yes) or N (No).
or
to make your selection and move to the next programming option.
7.7.5.2 Auto Display Oldest Event
When this feature is programmed Y (Yes) then the oldest un-acknowledge event will
automatically display on the control panel and remote annunciators after there has been no
activity on any system touchpad for two minutes.
8. Press the
9. Press
or
arrow to toggle this selection between Y (Yes) or N (No).
or
to make your selection and move to the next programming option.
7.7.5.3 Report by Zone or by Point
When the "Report by" option is set to Zone, then the control panel will report events by zone.
If Point is selected then the control panel will report events by point.
10. Press the
or
arrow to toggle this selection between Zone or Point.
11. Then press
or
151209
7-41
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.7.6 Miscellaneous Options 3
From Miscellaneous Options 3, you set the alarm verification time, turn the Plex Door option
on/off, and set the start and end week and month of Daylight Saving Time.
To edit Miscellaneous Options 3:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
4. Enter code if prompted.
Display reads:
Initializing
Please wait . . .
5
5. Select for System Options.
7
6. Select for Miscellaneous Options 3.
7.7.6.1 Alarm Verification Time
You can set the alarm verification time from 1 to 250 seconds (default is 60 seconds).
To set the alarm verification:
7. Enter the desired number of seconds for the alarm verification time.
8. Press
or
to make your selection and move to the next programming option.
7.7.6.2 Plex Door Option
If installing the plex door hardware (PN Plex-1), you must turn the Plex Door option On as
described in this section.
To turn the Plex Door option on/off:
9. Press the
or
arrow to toggle this selection between Y (Yes) or N (No).
10. Press
or
to make your selection and move to the next programming option.
7-42
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.7.6.3 Daylight Saving Time Start and End
This option lets you to adjust the week and month Daylight Saving Time (DST) starts and
ends. For this feature to work, you must enable (set to Yes) the DST option under Misc.
however, settings will not take effect until 2007. The default values for the DST Start and End
options reflect the August 8, 2005 DST law that goes into effect in 2007:
DST Start: The second Sunday in March
DST End: The first Sunday in November
To set the start and end for Daylight Saving Time:
11. Press the
then press
or
arrow to select the week (1st, 2nd, etc.) Daylight Saving Time starts,
to make your selection and move to the month setting.
12. Press the
or
arrow to select the month (January – December) Daylight Saving Time
starts, then press
to make your selection and move to the DST End option.
13. Press the
or
arrow to select the week (1st, 2nd, etc.) Daylight Saving Time ends,
to make your selection and move to the month setting.
then press
14. Press the
or
arrow to select the month (January – December) Daylight Saving Time
two times to make your selection and exit Misc. Options 3.
ends, then press
151209
7-43
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.7.7 Edit Banner Message
The banner is the message that displays on the panel LCD when the system is normal, that is,
when no alarms or troubles exist and no one is currently using system menus. You can create a
customized message, which can be up to 40 characters, two lines of 20 characters each.
If you do not create a customized message, the system will use the internal banner. You cannot
change the internal banner.
To customizing the banner display message:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
5
4. Select for System Options.
8
Figure 7-18 Internal Banner Message
6. Press the
or
arrow to select “Custom”, then press
. A screen similar to the one
Figure 7-19 Custom Banner Edit Screen
7. Select each letter by pressing the
acter.
or
arrow, then press
to move to the next char-
8. When done, press
to move to line two of the custom banner. Repeat step 7 and 8.
7-44
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.8 JumpStart Autoprogramming
IMPORTANT!
JumpStart is intended to be used prior to performing any custom programming. Each time
JumpStart is executed, all options will be reset to their default values. Do not run
JumpStart after you have configured the system through programming.
To run JumpStart:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
6
4. Select for System Options.
5. Press the
6. Press
or
arrow to select "Yes" from the warning screen.
.
151209
7-45
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
7.9 Computer Account
An installer at the panel site can initiate communications between the panel and a computer
running the 5660 SKSS (see also Section 8.5.16). In order for this communication to function
properly both the computer (running the software) and the control panel must have matching
computer account numbers and computer access codes.
Before you program in this location you should know how your control panel will
communicate with the downloading computer, either through direct connect (RS232) or via
the phone lines (Internal Modem).
If the panel initiates the call to a downloading computer, a phone number must be
programmed in the computer accounts area. If the computer initiates the call, answering
To program computer account information:
1. Enter the installer code.
2. Press
or
to display the main menu.
7
3. Select for Program Menu.
Display reads:
Initializing
Please wait . . .
7
4. Select for System Options.
5. Enter the computer account number, then press
6. Enter the computer code (up to 7-digits), then press
.
.
7. Enter the phone number the panel will dial to connect to a downloading computer (up to
7-46
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming
7.10 Access Codes
Access codes provide the user access to the control panel functions. Each access code can be
customized for each user. This allows some users the ability to access programming and other
higher level panel functions, while other users may only need access to lower level functions
such as preforming fire drills, or acknowledging trouble conditions.
Profile 1 is the profile that dictates what functions the Fire Fighter Key has access to. Because
this is the profile for a key the user name and the access code can not be edited for this profile.
Profile 2 is the profile for the installer and is referred to as the "Installer Code". This profile’s
user name and panel functions can not be edited.
Table 7-8 lists the panel functions that can be selected for each user profile.
Table 7-8: User Profile Selectable Panel Functions
Type of Function
Selectable Functions
System Reset
System Silence
System Event Acknowledge
Fire Drill Key
Panel Operations
System Test
Fire Drill Menu
Indicator Test
Walk Test no Report
Walk Test with Report
Dialer Test
Clear History Buffer
Point Functions
Disable/Enable Point
Point Status
Set SLC Device Address
SLC Device Locator
SLC Mult-Device Locator
I/O Point Control
Event History
Panel Menus
Set Time & Date
Printer Options
Event Logging
Print Event History
Print Detector Status
Print System Configuration
Reset Dialer
Program Menu
System Information
Upload/Download
To change an access code:
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select for Program Menu.
Display reads: Initializing
7
151209
7-47
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Please wait . . .
4. Select for System Options.
Display reads: Select Profile 01
Fire Fighter’s Key
8
5. Select the access code you wish to edit by pressing the
6. Then press
or
arrow.
.
7.10.1 Profile Edit Menu
From the Profile Edit Menu you can change the users name, access code, and the panel
functions that the user will have access to with their code.
Note: Profile 1 (Fire Fighter’s Key) the user name and access code can not be edited. Profile 2 (Installer) the
user name and panel functions can not be edited.
7.10.1.1 Edit Name
7. Select each character of a word by pressing the
the next character.
or
arrow, then press
to move to
8. Repeat step 7 until user name is complete.
9. Then press
to finish.
7.10.1.2 Edit Access Code
10. Enter new access code (minimum of 4 digits, maximum of 7 digit)
11. Press
.
12. Enter code again.
13. Press
.
7.10.1.3 Panel Functions
14. Press the
15. Then press
16. Press the
or
arrow to move through the list of available functions.
to move to Y (yes) or N (no) selection column.
or arrow to select Y or N.
17. Press
.
18. Repeat steps 14 through 17 until user profile is complete.
7-48
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8
System Operation
Operation of the control panel is simple. Menus guide you step-by-step through operations.
This section of the manual is an overview of the operation menus. Please read this entire
section carefully before operating the panel.
Press
to view Main Menu: Select the desired menu option. Enter your access code if
prompted.
8.1 User and Installer Default Codes
User Code (factory-programmed as 1111).
Installer Code (factory-programmed as 5820).
8.2 Annunciator Description
Figure 8-1shows the annunciator that is part of the control panel board assembly.
Figure 8-1 Control Panel Annunciator
151209
8-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8.2.1 LCD Displays
The control panel LCD displays system messages, annunciates alarms, supervisories and
troubles; provides status information; and prompts for input. These messages can be up to 80
characters, displaying over four lines of 20 characters each. Annunciator keys beep when they
are pressed.
8.2.2 Banner
The banner is the message that displays on the control panel when the system is in normal
mode (no alarm or trouble condition exists and menus are not in use). You can create a
customized message that will display instead of the internal (default) message. See Section
Figure 8-2 Banner Display Examples
8.3 Key Operation
The key on the control panel board assembly is for accessing the Main Menu. The key is
activated when it is turned once to the right (clockwise). If the key has been used to activate
the menu, it must be turned counter-clockwise to exit the menu.
Figure 8-3 Using a Key to Access the Main Menu
8-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
System Operation
8.4 Menu System
The control panel is easy to operate from Main Menu. To view the Main Menu press the
or button on the control panel or remote annunciator, then turn the firefighter’s key
clockwise or enter your access code. The Main Menu will appear as shown in Section 8.4.1.
Select the desired option. If you have entered a code or firefighter’s key does not have access
to the menu item you have selected the following display message will appear:
-Access denied.-
Entered PIN does not
allow access to this
function.
You must enter an access code with the correct profile settings to gain access to that menu
item.
The control panel supports up to 20 access codes. The profile for each access code (or user)
can be modified through the programming menu option (see Section 7.10 for access code
programming).
8.4.1 Main Menu Overview
The chart below is a brief overview of the Main Menu. These options are described in greater
detail throughout this section of the manual.
Main Menu Options
Description
From here both menus can access Fire Drill and Indicator Test.
1
2
3
4
5
System Tests
From here both menus can enable / disable points.
Set time and date for the system.
Point Functions
Event History
Set Time and Date
Printer Options
Options for controlling a printer if attached to the system. If a printer is used,
the Model 5824 serial/parallel interface module must be used.
Cancel any attempt to call the central station. Any calls awaiting additional
attempts will be aborted.
6
7
8
9
Reset Dialer
Program Menu
System Info
Brings up a set of menus for programming the panel, including changing
access codes. These options are described in detail in Section 7.
View system information, including model and serial numbers and revision
number and date.
Initiate communication from the panel site between the panel and a
computer running the Silent Knight Software Suite.
Up/Download
151209
8-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8.4.2 Using the Menus
To move through the menus:
Use
previous menu.
and
to move through the options in a menu. Use to move to a
To select an option:
Enter the number of the option.
–OR–
ENTER
Press
(Enter key) if the option appears at the top of the menu (= symbol
displays after the option number in this case).
8.5 Basic Operation
8.5.1 Setting Time and Date
4
1. From the Main Menu, select for Set Date and Time.
2. Make changes in the fields on the screen. Use (right arrow) to move through the fields.
Use the
and
to select options in the fields.
ENTER
3. When the date and time are correct, press
.
8.5.2 Disable / Enable a Point
2
1. From the Main Menu, select for Point Functions.
1
2. Select for Disable/Enable Point. A list of modules displays.
ENTER
3. Use
and
to move through the list. Press
to select the module where the
point you want to disable/enable is located. A description of the point should display. The
fourth line of the screen should show "NORMAL" (meaning that the point is currently
enabled) or "DISABLED" (the point is currently disabled). Press to toggle between NOR-
MAL and DISABLE.
8.5.3 Disable / Enable NACs by Group
2
1. From the Main Menu, select for point functions.
1
2
2. Select to Disable NACs by group or to Enable NACs by group.
ENTER
3. Use
lighted.
and
to move through the list of groups. Press
to select the group high-
8-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
System Operation
8.5.4 View Event History
3
Use the View Event History feature to display events on LCD. From the Main Menu, press
to select Event History. Events will begin displaying with most recent events first.
The panel can store up to 1000 events. When it reaches its 1000-event capacity, it begins
deleting, starting with the oldest events.
If a printer is attached to the system (via a Module 5824 serial/parallel interface module), you
can print event history (see Section 8.5.17).
The 5660 SKSS or 5670 SKSS can be used to retain more than 1000 events and to create
event history reports.
8.5.4.1 To clear the event history
1
6
From the Installer menu select for System Tests. From the test menu select Clear
History Buffer.
8.5.5 Conduct a Fire Drill
1
1. From the Main Menu, press for System Tests.
ENTER
1
2. Press for Fire Drill. You will be prompted to press
.
ENTER
3. The drill will begin immediately after you press
.
4. Press any key to end the drill. (If you do not press any key to end the fire drill manually, it
will time out automatically after ten minutes.)
If a fire drill switch has been installed, activating the switch will begin the drill; deactivating
the switch will end the drill.
8.5.6 Conduct an Indicator Test
The indicator test checks the annunciator LEDs, PZT, and LCD display.
1
1. From the Main Menu, press for System Tests.
2
2. Press for Indicator Test. The system turns on each LED several times, beeping the PZT
as it does so. At the same time it scrolls each available character across the LCD. A prob-
lem is indicated if any of the following occurs:
•
•
•
An LED does not turn on;
You do not hear a beep;
All four lines of the LCD are not full.
This test takes approximately 15 seconds to complete. You can press any key to end manually
while the test is still in progress. When the test ends, you will be returned to the <Test Menu>.
151209
8-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8.5.7 Conduct a Walk Test
1
1. From the Main Menu, press for System Tests.
IMPORTANT!
If any alarm verification zones are being used, the user will be asked if they
wish to disable alarm verification during walk test. This occurs for either walk
test option.
3
2. Select for Walk Test-No Rpt. The LCD will display “WALK TEST STOPPED” on
Line 1 and “ENTER = start test” on Line 2. If you select this option, central station report-
ing will be disabled while the test is in progress.
Or
4
Select for Walk Test-with Rpt. The LCD will display “WALK TEST STOPPED” on
Line 1 and “ENTER = start test” on Line 2. If you select this option, central station report-
ing will occur as normal during the walk test.
The panel generates a TEST report to the central station when the walk test begins. During
a walk test, the panel’s normal fire alarm function is completely disabled, placing the
panel in a local trouble condition. All zones respond as 1-Count zones (respond when a
single detector is in alarm) during a walk test. Each alarm initiated during the walk test
will be reported and stored in the event history buffer.
ENTER
3. Press
to end the walk test. The system will reset. The panel will send a "TEST
RESTORE" report to the central station.
If you do not end the walk test manually within four hours, it will end automatically.
If an alarm or pre-alarm condition is occurring in the system, you will not be able to enter the
walk test.
Note: the panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to
normal, the panel is ready to go to the next device.
8.5.8 Conduct a Dialer Test
1
1. From the Main Menu, press for System Tests.
5
2. Select for Dialer Test. The screen will display “Manual dialer test started”. When the
test is completed, you will be returned to the <Test Menu>.
8-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
System Operation
8.5.9 Silence alarms or troubles
SILENCE
Press
and enter your code or rotate the key at the prompt. If an external silence
switch has been installed, activating the switch will silence alarms or troubles. If you are
SILENCE
already using system menus when you press
rotate the key.
, you will not need to enter your code or
Note: Alarm and trouble signals that have been silenced but the detector remains un-restored will un-silence ev-
ery 24 hours until it is restored.
8.5.10 Reset alarms
RESET
Press
and enter your code or rotate the key at the prompt. If an external reset switch
has been installed, activating the switch will reset alarms. If you are already using system
RESET
menus when you press
, you will not need to enter your code or rotate the key.
8.5.11 Check Detector Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in
compliance with NFPA 72.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL
TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an
out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the central station receives a detector trouble report
(“373” + Zone # for Contact ID format; “FT” + Zone # in SIA format).
To check sensitivity for an individual detector, follow the steps below. Section 8.5.17 provides
instructions for printing the status of all detectors in the system.
2
1. From the Main Menu, press for Point Functions.
2
2. Press for Point Status.
3. Select the module where the point you want to check is located.
ENTER
4. Enter the number of the point you want to check and press
.
151209
8-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Figure 8-4 Checking Detector Sensitivity Compliance
If a printer is attached to the system (via a Module 5824 serial/parallel interface module), you
can print detector status (see Section 8.5.17).
8.5.12 View Status of a Point
2
1. From the Main Menu, select for Point Status.
ENTER
2. From the list that displays, press
to select the module where this point is located.
The screen that displays will show you if the point has a trouble and will provide sensitiv-
sensitivity compliance.)
8.5.13 View Alarms or Troubles
When the system is in alarm or trouble, you can press
to view the location of an alarm or
8.5.14 View System Information
8
Press from the Main Menu to view the panel model and serial number and system version
number and date. The information displays for several seconds then returns to the main menu.
8.5.15 Reset dialer
6
From the Main Menu, select . The LCD will display “Dialer reset in progress...” You will be
returned to the Main Menu when the reset is completed.
8-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
System Operation
8.5.16 Communicating with a Remote Computer
An installer at the panel site can initiate communications between the panel and a computer
running the SKSS 5660. You can use this feature to upload a panel configuration. For
example, if you have made programming changes to an installation on site using an
annunciator, you can send your changes to the computer, so that the central station will have
the latest data about the installation. See the software manual for more information (PN
151240).
To initiate communication:
9
1. From the Main Menu, select for Up/Download.
2. From the next screen that displays, select the communication device. Options are:
If you select this option, you will use the panel’s built-in modem to call
the panel.
1
2
= Internal Modem
If you select this option, the panel and a computer are both on-site
connected via a 9-pin straight-through serial cable.
= RS232 connection
3. If you are using the panel’s internal modem to communicate, you will be prompted to
enter a phone number. If you are communicating via the RS232 connection, a phone num-
ber is not needed and this step will be skipped.
ENTER
If the phone number you will be calling is already displayed, press
Step 4.
. Continue with
If the phone number you will be calling is not already displayed, enter the number and press
ENTER
. A phone number can be up to 40 digits long and can contain the following special
characters.
#
*
,
Pound (or number) key on the telephone
Star key on the telephone
Comma (character for 2-second pause)
Use the number buttons on the annunciator or the up- and down-arrow keys to select special
characters. Characters begin displaying after “9”.
4. You will be prompted to enter an account number. If the account number you want to use
ENTER
is already displayed, just press
to begin communication.
If the account number displayed is not the correct one, enter the account number and press
ENTER
to begin communication.
5. The panel will attempt to communicate with the computer. If communication was estab-
lished, the upload task you created will be placed in the SKSS 5660 job queue, awaiting
processing. When processing is completed, an “Unsolicited Upload” task will appear in
the queue.
151209
8-9
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8.5.17 Working with a Printer
If you are using the Model 5824 serial/parallel interface module, several printing options are
available. See Section 4.7 for information about installing the 5824.
5
1. From the Main Menu, select Printer Options.
2. From the next screen, select the 5824 module where the printer is connected.
3. If the printer is not currently busy printing another report, a screen with the following
1
options will be available. If the printer is busy, a message will display. You can press to
cancel the current print job. These options will then display.
Enables event logging, which causes the printer to continuously print events as they occur. The
date/time will print in 24-hour military format. Once event logging is enabled, it will remain
enabled until canceled by the installer. If you need to disable event logging, return to this option
1
= Event Logging
1
and press
to disable.
EVENT LOG:
STARTED: 02/17/97 02:23
02/17/97 11:23 Event: System Silenced
02/17/97 11:24 Event: System Reset
02/17/97 14:30 Event: Local Programming Begin
02/17/97 15:01 Event: Local Programming Ended Successfully
Sample Event Log
EVENT LOG:
STOPPED: 02/17/97 15:02
Prints the up-to-1000 events currently stored in the panel’s event history buffer. Events print
starting with the newest. The date and time printed will be when the event actually occurred and
will print in 24-hour military format.
2
= Print Event History
EVENT HISTORY:
PRINTED: 02/28/97 13:35
3 of 10: System Silenced
2 of 10: System Reset
4 of 10: Printer Off Line 4
4 of 10: Printer On Line 4
5 of 10: Local Programming Begin
5 of 10: Local Programming Ended Successfully
6 of 10: Walk Test Begin
02/20/97 09:02 Event
02/20/97 09:05 Event
02/22/97 08:47 Event
02/22/97 08:52 Event
02/25/97 15:54 Event
02/25/97 16:10 Event
Sample Event
History Print-Out
02/28/97 12:50 Event
02/28/97 13:31 Event
2 of 10: Walk Test End
.
.
.
Prints the current status of all detectors in the system. This is a method for finding out if any
detectors are out of NFPA compliance or any detectors need maintenance (are approaching an
out of compliance condition).
3
= Print Detector
Status
Sample Detector
Status Print-Out
Note: Detector status can also be viewed and printed using the 5660 SKSS or 5670 SKSS (facility monitoring on-
ly).
8-10
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
System Operation
8.6 Operation Mode Behavior
The control panel can be in one of seven conditions at any given moment: Normal, Alarm,
panel in each of these modes.
Table 8-1: Operation Mode Behavior
Operation
Mode
Occurs When
System Behavior
In This Mode You Can
Normal
No alarm or
trouble
condition exists
and menus are
not in use.
SYSTEM POWER LED is on.
Enter the appropriate code to activate the User or
Installer Menu, or rotate the key to activate the User
Menu.
The All Systems Normal display indicates
that the system is in normal mode.
The current date and time display on the
last line of the LCD.
Alarm
A smoke
The dialer seizes control of the phone line Press the down arrow to view the alarm. A screen
detector goes
into alarm or a
pull station is
activated.
and calls the central station.
similar to this one displays.
The on-board annunciator sounds a loud,
steady beep (any notification devices
attached to the system will also sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this
one.
SILENCE
Press
and enter an access code (or
activate the key) to silence the annunciator (and any
notification devices attached to the system).
RESET
When the alarm condition clears, press
and enter a code (or activate the key) to restore the
panel to normal.
151209
8-11
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table 8-1: Operation Mode Behavior
Operation
Mode
Occurs When
System Behavior
In This Mode You Can
Supervisory
The system
detects a
supervisory
condition.
The dialer seizes control of the phone line
and calls the central station.
Press
(down arrow) to view the supervisory
condition. A screen similar to this one displays.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second
on, one second off.
SUPERVISORY LED flashes.
The LCD displays a screen similar to this
one.
SILENCE
Press
and enter an access code (or
activate the key) to silence the annunciator.
Once the supervisory condition has been corrected,
the system will restore itself automatically.
Trouble
A system trouble The dialer seizes control of the phone line
Press
(down arrow) to view the trouble. A
condition
occurs.
and calls the central station.
screen similar to this one displays.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second
on, nine seconds off.
SYSTEM TROUBLE LED flashes.
The LCD displays a screen similar to this
one.
SILENCE
Press
and enter an access code (or
activate the key) to silence the annunciator.
Once the trouble condition has been fixed, the
system will restore itself automatically.
8-12
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
System Operation
Table 8-1: Operation Mode Behavior
System Behavior
Operation
Mode
Occurs When
In This Mode You Can
(down arrow) to view the prealarm. A
Prealarm
A single detector Touchpad PZT beeps.
trips in a 2-
Press
The LCD displays a screen similar to this
screen similar to this one displays.
Count zone. (2-
Count means
two detectors
must trip before
an alarm is
one.
reported.)
All system operations are available in this mode.
Menus are not available during the reset process.
Reset
All LEDs are on briefly then the LCD
displays "ALARM RESET IN
PROGRESS". If the reset process
completes normally, the date and time
normal mode screen displays.
RESET
The
button is pressed
followed by a
valid code or
rotation of the
key.
Silenced
An alarm or
trouble
condition has
been silenced
but still exists.
To silence
SYSTEM SILENCE LED is on. SYSTEM
TROUBLE, SUPERVISORY or
GENERAL ALARM LED (depending on
condition) is on. The annunciator (and any
notification devices attached to the
system) will be silenced.
Press
(down arrow) to view the location of the
alarm or trouble. When the condition no longer
exists, the SYSTEM SILENCED and SYSTEM
TROUBLE LED, SUPERVISORY or GENERAL
ALARM LEDs turn off.
alarms and
troubles, press
SILENCE
followed by the
Installer or User
Code or rotate
the key.
151209
8-13
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8.7 Releasing Operations
This control panel supports two types of releasing, Double Interlock Zone, and Single
Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the
system, and the Single Interlock does not. An interlock switch is typically a dry-contact
pressure switch.
When a Single or Double Interlock Zone releasing is selected the system is will automatically
default the following system parameters:
Note: The defaults created can be modified through programming if desired.
•
•
•
Output Group 2 is created. Output Group 2 will be defaulted as an "Alarm" output group
for all releasing zones. NAC [34:001] is assigned to Output Group 2.
Output Group 3 is created. Output Group 3 will be defaulted as an "Pre-Alert" output
group for all releasing zones. NAC [34:002] is assigned to Output Group 3.
Output Group 4 is created. Output Group 4 will be defaulted as a "Release" output group
for all releasing zones. NAC circuit [34:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches, or inter-
lock/pressure switches.
Table 8-2: Approved Releasing Solenoids
Manufacturer
Asco
Part Number
T8210A107
8210G207
Rating
Current
Freq
24 VDC
24 VDC
3A max
3A max
0 Hz
0 Hz
Model 7641
Must Mounted
at the Solenoid
Figure 8-5 Wiring Configuration for Solenoid
Do not mix cross alarming zones with smoke verification zones. There must be at least two
automatic detection devices in each protected space. Spacing must be reduced to 0.7 times the
8-14
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
System Operation
8.7.1 Single Interlock Zone Releasing
A single interlock zone utilizes a minimum of two addressable detectors and a designated
manual release switch.
Important!
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Conditions Required for an Pre-Alert Output Activation
If any single addressable detector is activated, the “Pre-Alert” output will activate. This alerts
the user that the initial stages required for a release condition are present. (Also refer to Table
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the
Table 8-3: Single Interlock Zone Operation
Inputs
Output Results
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
1st Addressable Detector
2nd Addressable Detector
Manual Release Station
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
151209
8-15
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8.7.2 Double Interlock Zone Releasing
A Double Interlock Zone uses a minimum of two Addressable detectors, a designated manual
release switch, and an interlock switch input. An interlock switch is typically a dry-contact
pressure switch and will be referred to as an interlock/pressure switch in this document.
Important!
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Each Double Interlock Zone input requires at least one Interlock/pressure switch
Conditions Required for a Pre-Alert Output Activation
If any single addressable detector is activated, the “Pre-Alert” output will activate. This alerts
the user that the initial stages required for a release condition are present. (Also refer to Table
Conditions Required for a General Alarm Output Activation
If two addressable detectors, a manual release switch is activated, or an interlock switch is
active, the "Pre-Alert", and "General Alarm" outputs will activate.
Conditions Required for a Release Output Activation
Any release requires the activation of an interlock switch, and either a manual release switch
or 2 activated addressable detectors. When these conditions are met, the "Release" and
"General Alarm" outputs will activate, and the "Alert" outputs will deactivate.
Table 8-4: Double Interlock Zone Operation
Inputs
Output Results
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
4
4
4
4
4
4
4
1st Addressable Detector
2nd Addressable Detector
Manual Release Station
Interlock/Pressure Switch
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
4
4
4
ꢀ
4
4
4
4
ꢀ
ꢀ
4
8-16
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
System Operation
8.8 Smoke Alarm Verification
Figure 8-6 illustrates how the Smoke Alarm Verification cycle operates.
Figure 8-6 Smoke Verification Cycle
During the Confirmation Period if there is no alarm indication then the system will return to
normal operation.
151209
8-17
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
8-18
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 9
Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes sent
by the control panel for SIA and Contact ID formats.
9.1 Receivers Compatible with the Control Panel
Table 9-1 shows receivers compatible with the control panel.
Table 9-1: Receivers Compatible with the Control Panel
Manufacturer
Silent Knight
Model
Format
Model 9800
SIA and Contact ID
SIA
Model 9000 (SIA formats)
Model 685 (Contact ID )
SG-MLR2-DG (V. 1.64 or higher)
Quickalert
Ademco
Contact ID
Sur-Gard
SIA and Contact ID
SIA and Contact ID
Osborne Hoffman
9.2 Reporting Formats Dialer Outputs
SIA Reporting Format
Contact ID Reporting Format
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Event
Family
Parameter
(if any)
Event
Code
Group Contact
Event Description
Qualifier
#
#
Note:
Note: System events are reported when either "Report by Point" or "Report by
System Events
Zone" is selected.
AC power restore
Trouble System Event
Trouble System Event
Trouble System Event
Trouble System Event
Trouble System Event
AR
AT
ER
ER
ER
3
1
3
3
3
301
301
333
333
332
00
00
00
00
00
000
AC power lost
000
SBUS expander trouble restore
SBUS Class A supervision restore
Exp. ID
Exp. ID
Exp. ID
Exp. ID
Exp. ID
Exp. ID
Short circuit removed from SLC
communication loop
SLC Class A supervision restored
SBUS expander trouble
Trouble System Event
Trouble System Event
Trouble System Event
Trouble System Event
ER
ET
ET
ET
Exp. ID
Exp. ID
Exp. ID
Exp. ID
3
1
1
1
331
333
333
332
00
00
00
00
Exp. ID
Exp. ID
Exp. ID
Exp. ID
SBUS Class A supervision lost
Short circuit detected on SLC com-
munication loop
SLC Class A supervision lost
Fire drill has begun
Trouble System Event
ET
FI
Exp. ID
1
1
3
1
331
604
604
625
00
00
00
00
Exp. ID
000
Test
Test
System Event
System Event
Fire drill ended
FK
JD
000
Panel date has been changed
Trouble System Event
000
151209
9-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
SIA Reporting Format
Contact ID Reporting Format
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Event
Family
Parameter
(if any)
Event
Code
Group Contact
Event Description
Qualifier
#
#
Panel time has been changed
Local programming begin
Phone line 1 trouble restore
Phone line 2 trouble restore
Trouble System Event
Trouble System Event
Trouble System Event
Trouble System Event
JT
LB
LR
LR
LS
LT
LT
LU
1
1
3
3
1
1
1
1
625
627
351
352
628
351
352
628
00
00
00
00
00
00
00
00
000
000
001
002
000
001
002
000
1
2
Local programming ended normally Trouble System Event
Phone line 1 trouble detected
Phone line 2 trouble detected
Trouble System Event
Trouble System Event
1
2
Local programming aborted or ended Trouble System Event
with errors
Periodic test event – normal
Periodic test event – off normal
Initial power up
Test
Test
System Event
System Event
RP
RY
RR
RS
1
1
1
1
602
608
305
412
00
00
00
00
000
000
000
000
Trouble System Event
Trouble System Event
Remote programming ended nor-
mally
Unable to report to an account
Trouble System Event
Trouble System Event
RT
Acct #
1
1
354 Acct # Acct #
Remote programming aborted or
ended with errors
RU
413
00
000
User has initiated dialer test
Test
System Event
RX
SS
1
1
601
203
00
Water release circuit has been dis-
abled
Trouble System Event pi Exp. ID
Pnt #
Pnt #
Exp.
ID
Pnt #
Pnt #
Water release circuit has been re-
enabled
Trouble System Event pi Exp. ID
SR
3
203
Exp.
ID
Walk test end
Test
Test
System Event
System Event
TE
TE
3
3
607
607
00
00
000
000
SLC address programming ended;
system has been re-enabled.
Walk test begin
Test
Test
System Event
System Event
TS
TS
1
1
607
607
00
00
000
000
SLC address programming started;
system has been shut down.
Printer paper restore
Printer is out of paper
Printer back online
Printer offline
Trouble System Event
Trouble System Event
Trouble System Event
Trouble System Event
VI
VO
VY
VZ
YC
Exp ID
Exp ID
Exp ID
Exp ID
Line #
3
1
3
1
1
335
335
336
336
350
00
00
00
00
00
Exp. ID
Exp. ID
Exp. ID
Exp. ID
Line #
Auto dialer test communication trou- Trouble System Event
ble
Report to an account successful
Trouble System Event
YK
YK
Acct #
Line #
3
3
354 Acct # Acct #
Auto dialer test communication trou- Trouble System Event
ble restore
350
00
Line #
Ground fault condition detected
Ground fault condition restore
Battery voltage restore
Battery voltage low
Trouble System Event
Trouble System Event
Trouble System Event
Trouble System Event
YP
YQ
YR
YT
Exp. ID
Exp. ID
Exp. ID
Exp. ID
1
3
3
1
310
310
302
302
00
00
00
00
Exp. ID
Exp. ID
Exp. ID
Exp. ID
Note:
Note: Zone events are reported only when "Report by Zone" is selected.
Zone Events
9-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Reporting
SIA Reporting Format
Contact ID Reporting Format
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Event
Family
Parameter
(if any)
Event
Code
Group Contact
Event Description
Qualifier
#
#
SLC LED Module trouble restore
SLC LED Module trouble
Manual pull switch alarm
Detector alarm
Trouble
Trouble
Alarm
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
ER
ET
FA
FA
FH
FH
FJ
0000
0000
Zone
Zone
Zone
Zone
Zone
Zone
Zone
3
1
1
1
3
3
3
3
3
333
333
115
110
115
110
373
373
373
00
00
00
00
00
00
00
00
00
000
000
Zone
Zone
Zone
Zone
Zone
Zone
Zone
Alarm
Manual pull switch alarm restore
Detector alarm restore
Restore
Restore
Trouble
Trouble
Trouble
Manual pull switch trouble restore
Detector trouble restore
FJ
Positive Alarm Sequence acknowl-
edge switch trouble restore
FJ
Auxiliary power trouble restore
Notification output trouble restore
Trouble
Trouble
Zone Event
Zone Event
FJ
FJ
0000
3
3
320
320
00
00
000
1000+Gro
up #
Group #
Manual pull switch trouble
Detector trouble
Trouble
Trouble
Trouble
Zone Event
Zone Event
Zone Event
FT
FT
FT
Zone
Zone
Zone
1
1
1
373
373
373
00
00
00
Zone
Zone
Zone
Positive Alarm Sequence acknowl-
edge switch trouble
Auxiliary power trouble
Notification trouble
Trouble
Trouble
Zone Event
Zone Event
FT
FT
0000
1
1
320
320
00
00
000
1000+Gro
up#
Group #
User initiated a system reset
Water flow switch alarm
Reset
Alarm
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
OR
SA
SH
SJ
1
1
3
3
3
401
113
113
373
373
00
00
00
00
00
000
Zone
Zone
Zone
Zone
Zone
Zone
Zone
Zone
Water flow switch alarm restore
Water flow switch trouble restore
Restore
Trouble
Trouble
Supervisory/Tamper switch trouble
restore
SJ
Supervisory condition restore
Supervisory condition
Trouble
Trouble
Trouble
Trouble
Alarm
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
SR
SS
Zone
Zone
Zone
Zone
3
1
1
1
1
203
203
373
373
140
00
00
00
00
01
Zone
Zone
Zone
Zone
Zone
Water flow switch trouble
ST
ST
UA
Supervisory/Tamper switch trouble
Zone-based AUX1 switch alarm
1000+Zon
e
Zone-based AUX2 switch alarm
Alarm
Zone Event
UA
2000+Zon
e
1
140
02
Zone
System-based AUX1 switch alarm
System-based AUX2 switch alarm
Alarm
Alarm
Restore
Zone Event
Zone Event
Zone Event
UA
UA
UH
1000
2000
1
1
3
140
140
140
01
02
01
000
000
Zone-based AUX1 switch alarm
restore
1000+Zon
e
Zone
Zone-based AUX2 switch alarm
restore
Restore
Restore
Zone Event
Zone Event
UH
UH
2000+Zon
e
3
3
140
140
02
01
Zone
000
System-based AUX1 switch alarm
restore
1000
151209
9-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
SIA Reporting Format
Contact ID Reporting Format
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Event
Family
Parameter
(if any)
Event
Code
Group Contact
Event Description
Qualifier
#
#
System-based AUX2 switch alarm
restore
Restore
Trouble
Trouble
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
Zone Event
UH
UJ
UJ
UJ
UJ
UJ
UT
UT
2000
3
140
373
373
373
373
373
373
373
02
000
Zone-based AUX1 switch trouble
restore
1000+Zon
e
3
3
3
3
3
1
1
01
02
01
02
00
01
02
Zone
Zone
000
Zone-based AUX2 switch trouble
restore
2000+Zon
e
System-based AUX1 switch trouble Trouble
restore
1000
2000
0000
System-based AUX2 switch trouble Trouble
restore
000
External Reset/Silence/Fire Drill
switch trouble restore
Trouble
Trouble
Trouble
000
Zone-based AUX1 switch trouble
1000+Zon
e
Zone
Zone
Zone-based AUX2 switch trouble
2000+Zon
e
System-based AUX1 switch trouble Trouble
System-based AUX2 switch trouble Trouble
Zone Event
Zone Event
Zone Event
UT
UT
UT
1000
2000
0000
1
1
1
373
373
373
01
02
00
000
000
000
External Reset/Silence/Fire Drill
switch trouble
Trouble
Note: Note: Point events are reported only when "Report by Point" is selected.
Point Events
Manual pull switch alarm
Alarm
Alarm
Alarm
Alarm
Disable
Restore
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
FA
FA
FA
FA
FB
FH
FH
FH
FH
FJ
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
1
1
1
1
1
3
3
3
3
3
3
3
115
110
110
110
571
115
110
110
110
320
373
373
Exp.
ID
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Manual release switch alarm (Water
Release Zone)
Exp.
ID
Interlock switch alarm (Water
Release Zone)
Exp.
ID
Detector alarm
Exp.
ID
Point disabled
Exp.
ID
Manual pull switch alarm restore
Exp.
ID
Manual release switch alarm restore Restore
(Water Release Zone)
Exp.
ID
Interlock switch alarm restore (Water Restore
Release Zone)
Exp.
ID
Detector alarm restore
Restore
Trouble
Trouble
Exp.
ID
Notification output trouble restore
Manual pull switch trouble restore
Exp.
ID
FJ
Exp.
ID
Manual release switch trouble restore Trouble
(Water Release Zone)
FJ
Exp.
ID
9-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Reporting
SIA Reporting Format
Contact ID Reporting Format
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Event
Family
Parameter
(if any)
Event
Code
Group Contact
Event Description
Qualifier
#
#
Interlock switch trouble restore
(Water Release Zone)
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
FJ
FJ
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
3
373
373
373
320
320
373
373
373
373
373
320
571
113
571
571
113
373
373
Exp.
ID
Pnt #
Detector trouble restore
3
3
3
1
1
1
1
1
1
1
3
1
1
1
3
3
3
Exp.
ID
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Positive Alarm Sequence acknowl-
edge switch trouble restore
FJ
Exp.
ID
Aux power trouble restore
Notification output trouble
Manual pull switch trouble
FJ
Exp.
ID
FT
FT
FT
FT
FT
FT
FT
FU
SA
SB
SB
SH
SJ
Exp.
ID
Exp.
ID
Manual release switch trouble (Water Trouble
Release Zone)
Exp.
ID
Interlock switch trouble (Water
Release Zone)
Trouble
Trouble
Trouble
Trouble
Disable
Alarm
Exp.
ID
Detector trouble
Exp.
ID
Positive Alarm Sequence acknowl-
edge switch trouble
Exp.
ID
Auxiliary Power Trouble
Exp.
ID
Point Enabled
Exp.
ID
Water flow switch alarm
Water flow switch disabled
Exp.
ID
Disable
Disable
Restore
Trouble
Trouble
Exp.
ID
Supervisory/Tamper switch or
supervisory duct dectector disabled
Exp.
ID
Water flow switch alarm restore
Water flow switch trouble restore
Exp.
ID
Exp.
ID
Supervisory/Tamper switch or
supervisory duct dectector trouble
restore
SJ
Exp.
ID
Supervisory condition restore
Trouble
Trouble
Trouble
Trouble
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
SR
SS
ST
ST
Pnt #
Pnt #
Pnt #
Pnt #
3
1
1
1
203
203
373
373
Exp.
ID
Pnt #
Pnt #
Pnt #
Pnt #
Supervisory condition
Exp.
ID
Water flow switch trouble
Exp.
ID
Supervisory/Tamper switch or
supervisory duct dectector trouble
Exp.
ID
151209
9-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
SIA Reporting Format
Contact ID Reporting Format
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Event
Family
Parameter
(if any)
Event
Code
Group Contact
Event Description
Qualifier
#
#
Water flow switch re-enabled
Disable
Disable
Alarm
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
Point Event pi Exp. ID
SU
SU
UA
UA
UA
UA
UB
UH
UH
UH
UH
UJ
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
3
571
571
140
140
140
140
571
140
140
140
140
373
373
373
373
373
373
373
373
373
373
571
380
Exp.
ID
Pnt #
Supervisory/Tamper switch or
supervisory duct dectector re-enabled
3
1
1
1
1
1
3
3
3
3
3
3
3
3
3
1
1
1
1
1
3
1
Exp.
ID
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Pnt #
Zone-based AUX1 switch alarm
Zone-based AUX2 switch alarm
System-based AUX1 switch alarm
System-based AUX2 switch alarm
Auxiliary switch input disabled
Exp.
ID
Alarm
Exp.
ID
Alarm
Exp.
ID
Alarm
Exp.
ID
Disable
Restore
Restore
Restore
Restore
Trouble
Trouble
Trouble
Exp.
ID
Zone-based AUX1 switch alarm
restore
Exp.
ID
Zone-based AUX2 switch alarm
restore
Exp.
ID
System-based AUX1 switch alarm
restore
Exp.
ID
System-based AUX2 switch alarm
restore
Exp.
ID
Zone-based AUX1 switch trouble
restore
Exp.
ID
Zone-based AUX2 switch trouble
restore
UJ
Exp.
ID
External Reset/Silence/Fire Drill
switch trouble restore
UJ
Exp.
ID
System-based AUX1 switch trouble Trouble
restore
UJ
Exp.
ID
System-based AUX2 switch trouble Trouble
restore
UJ
Exp.
ID
Zone-based AUX1 switch trouble
Trouble
Trouble
Trouble
UT
UT
UT
UT
UT
UU
XE
Exp.
ID
Zone-based AUX2 switch trouble
Exp.
ID
External Reset/Silence/Fire Drill
switch trouble
Exp.
ID
System-based AUX1 switch trouble Trouble
Exp.
ID
System-based AUX2 switch trouble Trouble
Exp.
ID
Auxiliary switch input re-enabled
Disable
Exp.
ID
An unexpected SLC device has been Trouble
detected
Exp.
ID
9-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Reporting
SIA Reporting Format
Contact ID Reporting Format
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Event
Family
Parameter
(if any)
Event
Code
Group Contact
Event Description
Qualifier
#
#
An unexpected SLC device has been Trouble
removed
Point Event pi Exp. ID
XI
Pnt #
3
380
Exp.
ID
Pnt #
151209
9-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
9-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 10
Testing and Troubleshooting
10.1 Troubleshooting
This section of the manual offers suggestions for troubleshooting hardware problems. Please
read this section if you encounter a problem when installing the control panel. If these
suggestions do not solve your problem or if you encounter a problem that is not listed here,
contact Silent Knight Technical Support at 800-446-6444 for assistance.
10.2 Common Problems
Problem
Possible Cause / Suggested Actions
Trouble message "DBL ADDR" (Double An address has been assigned to more than one detector. Correct the address
Address) displays on LCD.
following the procedure described in Section 5.8.
Auxiliary power or notification circuits
have incorrect polarity.
Correct polarity. For notification and auxiliary power circuits: When in alarm
or powered, terminals labeled "X" are positive, terminals labeled "O" are
negative.
SLC devices are not being recognized
(trouble message "Missing" displays).
Check hardware connections.
If devices are physically connected, make sure wiring is correct (see Section
5.4). For the main panel, the positive side of device must be connected to
terminal 34; the negative side must be connected to Terminal 33. For 5815XL
devices, make sure the device connects to the 5815XL via the SLC OUT
terminals.
There can be only one SLC loop on the main panel and on each 5815XL
module. Do not connect devices to terminals labeled SLC IN.
Make sure SLC devices have been addressed properly following the
procedure described in Section 5.8.
For contact monitor modules, which are addressed using dip switches, the dip
switch must be set to the correct address before power is applied to the SLC
loop. If this procedure is not followed, the device will have an incorrect
address.
Make sure correct polarity has been observed for SLC device wiring. See
151209
10-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Problem
Possible Cause / Suggested Actions
SLC devices are not being recognized
(trouble message "Missing" displays on
the annunciator).
Check that SLC loop impedance is within the required range.
To measure impedance, use the following procedure.
1. Disconnect both wires from the terminal block at the panel (SLC devices
can remain connected).
2. Measure the impedance from positive to negative and from negative to
positive. Both measurements should be greater than 500 K ohms. If the
installation uses T-taps, test each T-tap individually.
3. Temporarily connect the positive wire to the negative wire of the SLC loop
at the point farthest from the panel (SLC devices can remain connected).
4. Measure the impedance from positive to negative and from negative to
positive. Both measurements must be less than 50 ohms.
The panel indicates a ground fault trouble An earth ground fault occurs when the panel senses an unexpected flow of
condition (trouble message "GROUND
FAULT" displays).
current from one or more of its terminals to the earth connection (Terminal 2).
Isolate the wiring that is causing the fault by removing wiring connections
one at a time until the earth fault is no longer present. Pause at least five
seconds after removing a wire before removing the next one.
The panel will also go into ground fault if a computer is connected to the
panel via a serial cable attached to the panel’s 9-pin connector. This is a
correct method for on-site communication between a panel and a computer.
Ignore the ground fault message in this case. The trouble will clear
automatically when you disconnect the computer from the cable
5815XL module that has been physically Check the status of the 5815XL green LED. If it flashes in the pattern .5 sec.
connected to the panel but is not being
recognized.
on / .5 sec. off, it is likely that the 5815XL has not been added to the system
through programming. JumpStart will add any 5815XLs connected to the
panel. If you have already run JumpStart, 5815XLs can be added manually
Check that the correct ID for the 5815XL module has been set through the
DIP switches. Assign ID#1 to the first 5815XL and ID#2 to the second
If the wiring between the 5815XL and the panel is correct, measure the
voltage from 5815XL Terminal (+) to Terminal (-). Voltage should be in the
range 27.2-27.4V when AC power is present.
If the green LED is not flashing, the likely cause is incorrect wiring from
10.2.1 Periodic Testing And Maintenance
To ensure proper and reliable operation, it is recommended that system inspection and testing
be scheduled monthly or as required by national and/or local fire codes. Testing should be
done by a qualified services representative if a malfunction is encountered.
Before testing:
1) Notify the fire department and/or central alarm receiving station if an alarm condition is
transmitted.
2) Notify facility personnel of a test so that alarm sounding devices are ignored during the test
period.
10-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing and Troubleshooting
3) When necessary, activation of Notification Appliances can be prevented by the DISABLE
function
Testing:
1) Activate a input via an alarm initiating device and check that the correct outputs activate
(Notification Appliances sound/flash, relays activate, alarm LED lights). Reset system.
Repeat for each alarm initiating device.
2) Momentarily open the following circuits one at a time and check for a trouble signal:
•
•
Notification Appliance (bell) Circuits.
Initiating devices
3) If new batteries were installed, wait 48 hours before completing this step. Remove AC
power, activate initiating device and check that:
•
•
The ALARM indicator lights.
All active Notification Appliances sound.
Measure battery voltage while the Notification Appliances are sounding. Replace any battery
with terminal voltage less than 85% of rating. Reapply AC power and RESET system.
10.2.2 Event History
The event history can be useful for tracking or recalling a trouble condition.
151209
10-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
10.3 Built-in Troubleshooting and Testing Tools
The fire control panel has several built-in testing and troubleshooting tools that can be utilized
to save time while testing and troubleshooting points and SLC devices.
10.3.1 SLC Device Locator
SLC device locator can be used to locate a device on a SLC loop.
Follow these steps to locate a particular SLC device:
2
1. Select (Point Functions) from the Main Menu.
4
2. Select (SLC Dev Locator).
Figure 10-1 Shut Down Warning
3. Press the
or
arrow to toggle NOto YES then press
.
If NOis chosen you will exit back to the Point Function menu.
If Yesis chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6. Press any key to exit SLC device locator function.
Note: Once you exit the system will resume normal operation.
10-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing and Troubleshooting
10.3.2 SLC Multi Locator
This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a
single search.
Follow these instructions to locate multiple SLC devices:
2
1. Select (Point Functions) from the Main Menu.
5
2. Select (SLC Dev Locator).
Figure 10-2 Shut Down Warning
3. Press the
or
arrow to toggle NOto YES then press
.
If NOis chosen you will exit back to the Point Function menu.
If Yesis chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter up to 8 SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6. Press the to exit SLC multi-locator function.
Note: Once you exit the system will resume normal operation.
151209
10-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
10.3.3 I/O Point Control
This feature allows you to toggle any output on or off and trip any input device. This can be
useful to test a point’s output mapping.
Follow these steps to control a I/O point:
2
1. Select (Point Functions) from the Main Menu.
6
2. Select (I/O Point Control).
3. Select the Module the point is on.
4. Enter the zone number , or press the
then press
or
arrow to select the point you wish to test,
.
5. Press
to generate an alarm for an input point or activate an output point.
6. To exit press
.
10-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing and Troubleshooting
10.3.4 Earth Fault Resistance
Table 10-1: Earth Fault Resistance Values by Terminal
Terminal Label
Low Biased
High Biased
Terminal
Number
Function
(Values in Ohms)
High
Trip
High
Restore
Low
Trip
Low
Restore
Flexput™
Notification
Circuits
4
X
O
X
O
X
O
X
O
X
O
X
O
B
A
+
I/O 6
-
0
-
-
0
-
0
-
0
-
5
6
I/O 5
0
-
0
-
7
0
-
0
-
8
I/O 4
0
-
0
-
9
0
-
0
-
10
11
12
13
14
15
16
17
18
19
20
21
22
23
33
34
35
36
I/O 3
0
-
0
-
0
-
0
-
I/O 2
0
-
0
-
0
-
0
-
I/O 1
0
-
0
-
0
-
0
-
SBUS
Communication
SBUS OUT
0
0
-
0
0
-
-
-
SBUS Power
0
-
0
-
-
0
0
0
-
0
0
0
-
SBUS
Communication
B
A
+
SBUS IN
-
-
-
-
SBUS Power
0
-
0
-
-
0
0
-
0
0
-
SLC Terminals
SC-
S+
SLC OUT
SLC IN
-
-
0
-
0
-
SC-
S+
0
-
0
-
0
0
151209
10-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
10-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 11
Installation Records
This section of the manual is for you to use if you wish to track of how points, zones, and
groups have been programmed.
11.1 SLC Point Record
You can use the chart that begins below to keep track of SLC points.
Default addresses for ID: On-board:
= 33
= 1
= 2
= 3
5815-1:
5815-2:
5815-3
Table 11-1: Installation Record
Zone /
Group
Zone/
Group
Module Addr
Description
Module Addr
Description
On-board
On-board
On-board
On-board
On-board
On-board
On-board
On-board
On-board
1
2
3
4
5
6
7
8
9
On-board 25
On-board 26
On-board 27
On-board 28
On-board 29
On-board 30
On-board 31
On-board 32
On-board 33
On-board 34
On-board 35
On-board 36
On-board 37
On-board 38
On-board 39
On-board 40
On-board 41
On-board 42
On-board 43
On-board 44
On-board 45
On-board 46
On-board 47
On-board 48
On-board 10
On-board 11
On-board 12
On-board 13
On-board 14
On-board 15
On-board 16
On-board 17
On-board 18
On-board 19
On-board 20
On-board 21
On-board 22
On-board 23
On-board 24
151209
11-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table 11-1: Installation Record
Zone /
Group
Zone/
Group
Module Addr
Description
Module Addr
Description
On-board 49
On-board 50
On-board 51
On-board 52
On-board 53
On-board 54
On-board 55
On-board 56
On-board 57
On-board 58
On-board 59
On-board 60
On-board 61
On-board 62
On-board 63
On-board 64
On-board 65
On-board 66
On-board 67
On-board 68
On-board 69
On-board 70
On-board 71
On-board 72
On-board 73
On-board 74
On-board 75
On-board 76
On-board 77
On-board 78
On-board 79
On-board 80
On-board 81
On-board 82
On-board 83
On-board 84
On-board 85
On-board 86
On-board 87
On-board 88
On-board 89
On-board 90
On-board 91
On-board 92
On-board 93
On-board 94
On-board 95
On-board 96
On-board 97
On-board 98
On-board 99
On-board 100
On-board 101
On-board 102
On-board 103
On-board 104
On-board 105
On-board 106
On-board 107
On-board 108
On-board 109
On-board 110
On-board 111
On-board 112
On-board 113
On-board 114
On-board 115
On-board 116
On-board 117
On-board 118
On-board 119
On-board 120
On-board 121
On-board 122
On-board 123
On-board 124
On-board 125
On-board 126
On-board 127
11-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Records
Table 11-1: Installation Record
Description Module Addr
Zone /
Group
Zone/
Group
Module Addr
Description
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
151209
11-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table 11-1: Installation Record
Description Module Addr
Zone /
Group
Zone/
Group
Module Addr
Description
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
5815-1
83
5815-1
5815-1
5815-1
5815-1
5815-1
123
124
125
126
127
84
85
86
87
88
89
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
1
90
2
91
3
92
4
93
5
94
6
95
7
96
8
97
9
98
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
11-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Records
Table 11-1: Installation Record
Description Module Addr
Zone /
Group
Zone/
Group
Module Addr
Description
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
151209
11-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table 11-1: Installation Record
Description Module Addr
Zone /
Group
Zone/
Group
Module Addr
Description
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
5815-2
115
116
117
118
119
120
122
123
124
125
126
127
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
11-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Records
Table 11-1: Installation Record
Description Module Addr
Zone /
Group
Zone/
Group
Module Addr
Description
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-3
5815-1
5815-3
5815-3
5815-3
5815-3
5815-3
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
Copy these pages if you additional sheets.
151209
11-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
11.2 Conventional Output Point Record
This chart can be used to keep track of how conventional output points (circuits) have been
configured.
Point/Circuit
Group
Description
1
2
3
4
5
6
7
8
11-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A
Compatible Devices
A.1
Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL
resistor on each loop. All supervised notification appliances used with the control panel must
be polarized.
Note:Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen
will work with this feature. This control is UL listed for panel wide Synchronization.
Table A-1 below lists notification appliances compatible with the fire alarm control panel.
Appliances which can be synchronized indicate the type of snyc available in the columns
marked Audio and/or Visual.
Table A-1: Compatible Notification Appliances
Manufacturer
Model
SH24W-153075
Audio
Visual
Type
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn/Strobe
Strobe
SAD24-153075
SAD24-75110
SL24W-75110
SL24C-3075110
SLB24-75
Strobe
Strobe
Strobe
Strobe
RSD24-153075
RSD24-75110
SH24W-75110
SH24W-3075110
SHB24-75
Strobe
Strobe
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn/Strobe
Horn/Strobe
Horn/Strobe
Chimes/Strobe
Chimes/Strobe
Chimes/Strobe
Chimes/Strobe
Horn
AMSECO
SCM24W-153075
SCM24W-75110
SCM24C-3075110
SCM24C-177
H24W
H24R
Horn
151209
A-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer
Model
Audio
Visual
Type
446
476
477
Vibrating Bell
Vibrating Bell
Single Stroke Bell
Strobe
2700 -M. -R, -T, -Y, -Z
2701 Series
2705 Series
2820
Strobe
Strobe
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Snyc Temporal Horn/Strobe
Snyc Temporal Horn/Strobe
Horn Strobe
2821
2824
5333
Multi-Tone Horn)
5336
Multi-Tone Horn/Strobe
Multi-Tone Horn/Strobe
Multi-Tone Horn/Strobe
Single Tone Horn/Strobe
Electronic Horn with Strobe
Electronic Horn with Strobe
Single Tone Horn/Strobe
8-Tone Horn/Strobe
5337
5338
5343
5346
Faraday
5347
5348
5373
6321
Sync Mini Horn/Strobe
Mini Horn/Sync Strobe
8-Tone Electronic Signal/Strobe
8-Tone Horn/Strobe
6322
6380
5376
5377
8-Tone Horn/Strobe
5378
8-Tone Horn/Strobe
5383
8-Tone Horn/Strobe with Sync Strobe
8-Tone Horn/Strobe with Sync Strobe
8-Tone Horn/Strobe with Sync Strobe
8-Tone Horn/Strobe with Sync Strobe
Single Gang Sync Strobe
Strobe
5386
5387
5388
5508
5509
A-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Compatible Devices
Table A-1: Compatible Notification Appliances
Model Audio Visual
Manufacturer
Type
5510
5511
5512
5516
5517
5518
5519
5521
5522
6120
6140
6223
6226
6227
6228
6243
6244
6245
6246
6247
6248
6300
6301
6302
6310
6311
6312
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Faraday
4” Square Sync Strobe
4” Square Sync Strobe
Horn
Horn
Horn
Horn/Strobe
Horn/Strobe
Horn/Strobe
Electron-Mechanical Horn
Electron-Mechanical Horn
Electron-Mechanical Horn
Electron-Mechanical Horn/Strobe
Electron-Mechanical Horn/Strobe
Electron-Mechanical Horn/Strobe
Mini-Horn
Mini-Horn
Mini-Horn
Mini-Horn/Strobe
Mini-Horn/Strobe
Mini-Horn/Strobe
6314 Series -M, -R, -T, -Y, -Z
6320
Strobe
Sync Mini Horn/Strobe
151209
A-3
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table A-1: Compatible Notification Appliances
Model Audio Visual
Manufacturer
Type
S2415-FC
S241575-FC
S2430-FC
130-3117C
130-3147C
BLV-6
Strobe
Strobe
Strobe
Mini Horn
Mini Horn
Vibrating Bell
Vibrating Bell
Vibrating Chime
Horn
BLV-10
FCI
BLVCH
H12/24-FC
H12/24W-FC
H12/24K-FC
HC12/24-FC
HC12/24W-FC
HC12/24K-FC
P2415-FC
Horn
Horn
Horn
Horn
Horn
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Strobe
FCI
P2415W-FC
P2415K-FC
P241575-FC
P241575W-FC
P241575F-FC
P241575K-FC
P2430-FC
P2430W-FC
P2430K-FC
P2475-FC
P2475W-FC
P2475K-FC
P24110-FC
P24110W-FC
P24110K-FC
S2430W-FC
S2430K-FC
S2475-FC
Strobe
Strobe
S2475W-FC
S2475K-FC
S24110-FC
S24110W-FC
S24110K-FC
450
Strobe
Strobe
Strobe
Strobe
Strobe
Horn
Federal Signal
VALS
Horn/Strobe
A-4
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Compatible Devices
Table A-1: Compatible Notification Appliances
Manufacturer
Model
Audio
Visual
Type
GEC-24-15
GEC-24-30
GEC-24-60
GEC-24-75
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn/Strobes
Horn/Strobes
Horn/Strobes
Horn/Strobes
Horn/Strobes
Horn/Strobe
Horn/Strobe
Gentex
GEC-24-177
GEC-24-110
GEC-24-15/75
GX91
MiniHorn Steady Tone
GX93
MiniHorn Temporal Tone
HG124
Horn
Gentex
HS24-15
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn/Strobe
HS24-30
Horn/Strobe
HS24-60
Horn/Strobe
HS24-75
Horn/Strobe
HS24-110
HS24-1575
GCC24
Horn/Strobe
Horn/Strobe
Multi Candella Horn/Strobe Ceiling Mount
GCCR24
Multi Candella Horn/Strobe Ceiling Mount
GCS24
Multi Candella Strobe Ceiling Mount
GCSR24
Multi Candella Strobe Ceiling Mount
GECR-24
GES24-15
GES24-30
GES24-60
GES24-75
GES24-110
GES24-15/75
GES24-177
GES3-24
ꢀ
Multi Candella Horn/Strobe
Strobes
Strobes
Strobes
Strobes
Strobes
Strobes
Strobes
Multi Candella Strobe
Multi Candella Strobe
Horn
GESR-24
GEH-24
ꢀ
ST24-30
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Strobe
ST24-60
Strobe
ST24-75
Strobe
ST24-110
ST24-1575
WGEC24-75W
WGES24-75W
WGMS-24-X
Strobe
Strobe
ꢀ
Weatherproof Horn/Strobe
Weatherproof Strobe
Horn/Strobe
151209
A-5
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer
Model
Audio
Visual
Type
CHR
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Chime
Chime
CHW
CHSR
CHSW
HR
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
2-Wire Chime/Strobe
2-Wire Chime/Strobe
Horn
HW
Horn
HRK
Horn
P2R
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
2-Wire Horn/Strobe
P2R-P
PC2R
2-Wire Horn/Strobe
2-Wire Horn/Strobe
PC2R-P
P2RH
2-Wire Horn/Strobe
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe
P2RH-P
PC2RH
PC2RH-P
P2W
System Sensor
P2W-P
PC2W
PC2W-P
P2WH
P2WH-P
PC2WH
PC2WH-P
P2RK
2-Wire Horn/Strobe
2-Wire Horn/Strobe
2-Wire Horn/Strobe
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe
PC2RK
P2RHK
PC2RHK
P4R
2-Wire Horn/Strobe
2-Wire Horn/Strobe High Candela
2-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe
PC4R
4-Wire Horn/Strobe
P4RH
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe
P4W
A-6
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Compatible Devices
Table A-1: Compatible Notification Appliances
Manufacturer
Model
Audio
Visual
Type
4-Wire Horn/Strobe
PC4W
P4WH
PC4WH
P4RK
PC4RK
P4RHK
PC4RHK
PC4RH
SR
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
System Sensor
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe
4-Wire Horn/Strobe
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
Strobe
SR-P
Strobe
SCR
Strobe
SCR-P
SRH
Strobe
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe
SRH-P
SCRH
SCRH-P
SW
SW-P
Strobe
SCW
Strobe
SCW-P
SWH
Strobe
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe
SWH-P
SCWH
SCWH-P
SRK
SCRK
SRHK
SCRHK
Strobe
Strobe High Candela
Strobe High Candela
151209
A-7
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer
Model
Audio
Visual
Type
AH-12
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn
Wheelock
AH-24
Horn
AH-12WP
AH-24WP
Horn Weatherproof
Horn Weatherproof
AMT-241575W
AMT-24MCW
AMT-241575W-NYC
AMT-12/24
ꢀ
ꢀ
ꢀ
Multi-Tone Horn Strobe
Mutli-Tone Horn Strobe
Multi-Tone Horn Strobe
Multi-tone Horn
Multi-tone Horn
Horn/Strobe
ꢀ
ꢀ
ꢀ
AMT-12/24 NYC
AS-121575W
NH-12/24
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn
AS-241575W
AS-24MCC
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn/Strobe
Horn/Strobe
AS-24MCCH
AS-24MCW
Horn/Strobe
Horn/Strobe
AS-24MCWH
ASWP-2475W
ASWP-2475C
ASWP-24MCWH
ASWP-24MCCH
CH-70
Horn/Strobe
Horn/Strobe Weatherproof
Horn/Strobe Weatherproof
Horn/Strobe
Horn/Strobe
Chime
CH-90
Chime
CH70-241575W
CH70-24MCW
CH70-24MCWH
CH90-24MCC
ꢀ
ꢀ
ꢀ
ꢀ
Chime/Strobe
Chime/Strobe
Chime/Strobe
Chime/Strobe
A-8
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Compatible Devices
Table A-1: Compatible Notification Appliances
Manufacturer
Wheelock
Con’t
Model
CH90-24MCCH
Audio
Visual
Type
ꢀ
Chime/Strobe
Horn
HS-24
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
HS4-241575W
HS4-24MCW
HS4-24MCWH
HS4-24MCC
MIZ-24S
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Mini Horn Strobe
MT-121575W
MT-241575W
MT-24MCW
MTWP-2475W
MTWP-2475C
MTG-121575W
MTR-121575W
MTWPA-2475W
MTWPB-2475W
MTWPG-2475W
MTWPR-2475W
MTWPA-24MCCH
ZNH
MultitoneHorn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Multitone Horn Strobe
Horn
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
NS-121575W
NS-241575W
NS-24MCW
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn/Strobe
Horn/Strobe
Horn/Strobe
NS-24MCC
Horn/Strobe
NS-24MCCH
ZNS-MCW
Horn/Strobe
Horn/Strobe
ZNS-MCWH
ZNS-24MCC
ZNS-24MCCH
Horn/Strobe
Horn/Strobe
Horn/Strobe
151209
A-9
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer
Model
RSS-121575W
Audio
Visual
Type
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Strobe
Wheelock
Con’t
RSS-241575W
RSS-24MCC
Strobe
Strobe
RSS-24MCCR
RSS-24MCCH
RSS-24MCCHR
RSS-24MCW
Strobe
Strobe
Strobe
Strobe
RSS-24MCWH
RSSP-121575W
RSSP-241575W
RSSR-2415W
Strobe
Strobe
Strobe
Strobe
RSSR-2415C
Strobe
RSSR-2475W
Strobe
RSSR-2475C
Strobe
RSSR-24110C
RSSA-24110W
RSSB-24110W
RSSG-24110W
RSSR-24110W
RSSA-24MCC
RSSB-24MCC
RSSG-24MCC
RSSR-24MCC
RSSWPA-2475W
RSSWPA-24MCCH
RSSWPG-24MCCH
RSSWPR-24MCCH
RSSWP-2475W
RSSWP-2475C
Strobe
Strobe
Strobe
Strobe
Strobe
Multi-Cd Strobe
Multi-Cd Strobe
Multi-Cd Strobe
Multi-Cd Strobe
Strobe Weatherproof
Strobe Weatherproof
Strobe Weatherproof
Strobe Weatherproof
Strobe Weatherproof
Strobe Weatherproof
A-10
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Compatible Devices
Table A-1: Compatible Notification Appliances
Manufacturer
Wheelock
con’t
Model
Audio
Visual
Type
Strobe Weatherproof
RSSWP-24MCWH
ZRS-MCWH
ZRS-24MCC
ZRS-24MCCH
MB-G6-24
MB-G10-24
MB-G6-12
MB-G10-12
MIZ-24-R
MT-12/24-R
MT4-12/24
ZRS-MCW
MTWPR-24MCCH
NH-12/24R
HSR
ꢀ
ꢀ
ꢀ
ꢀ
Strobe
Strobe
Strobe
Motor Bell
Motor Bell
Motor Bell
Motor Bell
Mini-Horn
Multitone Horn
Multitone Horn
Strobe
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Multitone Horn Strobe
Horn
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Horn/Strobe
Horn/Strobe
Strobe
HSW
STR
STW
Strobe
HNR
Horn
HNW
Horn
151209
A-11
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
A.2 Two-Wire Smoke Detectors
Table A-2 lists two-wire smoke detectors that are compatible with the fire control panel. The
table is organized by manufacturer. The columns show the number of detectors per loop that
can be used.
Table 1-1:
5820XL
24H
Identifier
18.5–27.4 VDC
Operating Voltage Range
Note: The maximum number of smoke detectors per zone is determined by both the current draw and the imped-
ance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Do not mix detectors of different models unless the system is specifically intended to be installed in that
configuration.
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum
reset time of the smoke detector.
Table A-2: Compatible Two-Wire Smoke Detectors
Model Name or Number
(Base model name or number
in parentheses.)
Compatibility ID
Head Base
Manufacturer
# per Loop
55000-350 (45681-200)
55000-250 (45681-200)
55000-225
55000-350
55000-250
55000-225
55000-226
55000-227
55000-325
55000-328
55000-326
55000-327
45681-200
24 / loop
24 / loop
Apollo
Apollo
45681-200
45681-255, 256,
15 / loop for
Ion Detectors
55000-226
55000-227
15 / loop for
Photo Electric
Detectors
45681-200, 220,
230, 232, 251,252
55000-325
55000-328
55000-326
55000-327
A-12
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Compatible Devices
Table A-2: Compatible Two-Wire Smoke Detectors
Model Name or Number
(Base model name or number
in parentheses.)
Compatibility ID
Head Base
Manufacturer
# per Loop
429C (S10A)
N/A
N/A
N/A
N/A
S10
S10A
30 / loop
30 / loop
30 / loop
30 / loop
40 / loop
40 / loop
40 / loop
40 / loop
40 / loop
40 / loop
40 / loop
25 / loop
25 / loop
25 / loop
25 / loop
30 / loop
30 / loop
17 / loop
17 / loop
25 / loop
429CRT (S11A)
429CST (S11A)
429CT (S10A)
S11A
S11A
S10A
609U01-11
S00
609U02-11
S10
S00/S03
S00/S03
S00/S03
S00/S03
S00/S03
S00/S03
S10A
611U (601U or 602U)
611UD (601U or 602U)
611UT (601U or 602U)
612U (601U or 602U)
612UD (601U or 602U)
711U (701E or 701U)
712U (701E or 701U)
713-5U (702E or 701U)
713-6U (702E or 701U)
721-U (S10A)
S10
S10
ESL
S10
S10
S10
N/A
N/A
N/A
N/A
N/A
N/A
FDT1
FDT1
HD-3
S10A
S10A
S10A
S10A
721-UT (S10A)
525
S10A
N/A
Falcon
525T
N/A
SIH-24F (HS-224D OR HSD-
224)
HB-5
Hochiki
SLK-24F (HS-224D)
SLK-24FH (HS-224D)
HD-3
HD-3
HB-5
HB-5
25 / loop
25 / loop
151209
A-13
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
Table A-2: Compatible Two-Wire Smoke Detectors
Model Name or Number Compatibility ID
Manufacturer
(Base model name or number
in parentheses.)
# per Loop
Head
Base
1400
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
N/A
A
20 / loop
20 / loop
20 / loop
20 / loop
16 / loop
16 / loop
20 / loop
20 / loop
20 / loop
20 / loop
20 / loop
20 / loop
20 / loop
20 / loop
20 / loop
20 / loop
20 / loop
16 / loop
16 / loop
16 / loop
1451 (B401B)
2100
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
2100T
2151 (B401)
2151T (B401)
2300T
2300
2300TB
2400
System Sensor
2400 (DH400)
2400AIT
2400AT
2400TH
2451 (B401B)
2451DH (DH 400)
2451TH (B401B)
2W-B
2WT-B
2WTR-B
A-14
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B
Special Characters Lists
This section contains tables of programmable characters that may be used for device, module,
and zone names or phone numbers.
B.1
Characters used for Naming
Table B-1 list the available character and their associated numeric designator. When
programming these numbers can be entered as a short cut to using the up or down arrow keys,
to select characters when naming a point or zone.
Table B-1: Character Table
000
004
008
012
016
020
024
028
032
036
040
044
048
052
056
060
064
068
A
E
I
001
005
009
013
017
021
025
029
033
037
041
045
049
053
057
061
065
069
B
F
J
002
006
010
014
018
022
026
030
034
038
042
046
050
054
058
062
066
070
C
G
K
O
S
W
a
003
007
011
015
019
023
027
031
035
039
043
047
051
055
059
063
067
D
H
L
P
T
X
b
f
M
Q
U
Y
c
N
R
V
Z
d
h
l
e
g
i
j
k
m
q
n
r
o
p
t
s
u
v
z
w
x
0
4
8
_
*
y
1
2
6
:
3
7
5
9
-
.
,
&
#
151209
B-1
Download from Www.Somanuals.com. All Manuals Search And Download.
IntelliKnight 5820XL Installation Manual
B-2
151209
Download from Www.Somanuals.com. All Manuals Search And Download.
Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
•
All new fire products manufactured by Silent Knight have a limited warranty period of
36 months from the date of manufacture against defects in materials and workmanship.
See limited warranty statement for details.
•
This limited warranty does not apply to those products that are damaged due to misuse,
abuse, negligence, exposer to adverse environmental conditions, or have been modified in
any manner whatsoever.
Repair and RA Procedure
•
All products that are returned to Silent Knight for credit or repair require a RMA (Return
Authorization) number. Call Silent Knight Customer Service at 800-328-0103 or
203-484-7161 between 8:00 A.M. and 5:00 P.M. EST, Monday through Friday to obtain a
return authorization number.
•
•
•
•
•
•
Silent Knight Technical Support is available at 800-446-6444 between 8:00 A.M. and
5:00 P.M. CST, Monday through Friday.
All returns for credit are subject to inspection and testing at the factory before actual deter-
mination is made to allow credit.
RMA number must be prominently displayed on the outside of the shipping box. See
return address example under Advanced Replacement Policy.
Include a packing slip that has the RMA number, a content list, and a detailed description
of the problem should be included with each return.
All products returned to Silent Knight must be sent freight pre-paid. After product is pro-
cessed, Silent Knight will pay for shipping product back to customer via UPS ground.
Return the Silent Knight product circuit board only. Products that are returned in cabinets
will be charged an additional $50 to cover the extra shipping and handling costs over
board only returns. Do not return batteries. Silent Knight has the authority to determine
if a product is repairable. Products that are deemed un-repairable will be returned to the
customer.
•
Product that is returned that has a board date code more than 36 months from date of man-
ufacture will be repaired and the customer will be assessed the standard Silent Knight
repair charge for that model.
Download from Www.Somanuals.com. All Manuals Search And Download.
Advanced Replacement Policy
•
Silent Knight offers an option of advance replacement for fire product printed circuit
boards that fail during the first 6 months of the warranty period. These items must be
returned with transportation charges prepaid and must be accompanied by a return
authorization.
•
•
For advance replacement of a defective board contact your local Silent Knight Distributor
or call Silent Knight at 203-484-7161 to obtain a RMA (Return Authorization) number
and request advanced replacement,
A new or refurbished board will be shipped to the customer. The customer will initially be
billed for the replacement board but a credit will be issued after the repairable board is
received at Silent Knight. All returned products must comply with the guidelines
described under “General Terms and Conditions”.
•
•
The defective board must be returned within 30 days of shipment of replacement board for
customer to receive credit. No credit will be issued if the returned board was damaged due
to misuse or abuse.
Repairs and returns should be sent to:
Silent Knight / Honeywell
Attn: Repair Department
12 Clintonville Road
Northford, CT 06472
USA
RMA Number:___________________
Download from Www.Somanuals.com. All Manuals Search And Download.
Limited Warranty
SILENT KNIGHT warrants products manufactured by it to be free from defects in materials and
workmanship for thirty-six (36) months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and exclusive obligation of SILENT
KNIGHT is to repair or replace, at its option, free of charge for parts and labor, any part that is
defective in materials or workmanship under normal use and service. All returns for credit are
subject to inspection and testing at the factory before actual determination is made to allow
credit. SILENT KNIGHT does not warrant products not manufactured by it, but assigns to the
purchaser any warranty extended by the manufacturer of such products. This warranty is void if the
product is altered or repaired by anyone other than SILENT KNIGHT or as expressly authorized by
SILENT KNIGHT in writing, or is serviced by anyone other than SILENT KNIGHT or its authorized
distributors. This warranty is also void if there is a failure to maintain the products and systems in
which they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our Return Authorization Department.
This writing constitutes the only warranty made by SILENT KNIGHT, with respect to its
products. SILENT KNIGHT, does not represent that its products will prevent any loss by
fire or otherwise, or that its products will in all cases provide the protection for which they
are installed or intended. Buyer acknowledges that SILENT KNIGHT is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience, transportation
damage, misuse, abuse, accident or similar incident.
SILENT KNIGHT GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL SILENT KNIGHT BE LIABLE FOR ANY LOSS OF OR
DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING
OUT OF THE USE OF, OR INABILITY TO USE SILENT KNIGHT ALARM’S PRODUCTS.
FURTHERMORE, SILENT KNIGHT SHALL NOT BE LIABLE FOR ANY PERSONAL
INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS
This warranty replaces all previous warranties and is the only warranty made by SILENT
KNIGHT. No increase or alteration, written or verbal, of the obligation of this warranty is
authorized.
“SILENT KNIGHT” is a registered trademark.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
|