Honeywell Blood Pressure Monitor 40002083 User Manual

Airport Systems  
Installation and Operation Guide  
for  
Programmable Logic Controller  
Health Monitoring System  
Model 40002083  
Manual Number EPM40002083-001  
Honeywell Airport Systems  
550 State Route  
Urbana, OH 43078  
Phone (937) 484-2000  
Fax (937) 484-2101  
Copyright 2007 Honeywell International  
All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
DISCLAIMERS  
This manual could contain technical inaccuracies or typographical errors. Honeywell  
reserves the right to revise this manual from time to time of the contents thereof without  
obligation of Honeywell to notify any person of such revision or change. Details and  
values given in this manual are average values and have been compiled with care. They  
are not binding, however, and Honeywell disclaims any liability for damages or  
detriments suffered as a result of reliance on the information given herein or the use of  
product, processes or equipment to which this manual refers. No warranty is made that  
the use of the information or of the products processes or equipment to which this  
manual refers will not infringe any third party’s patents or rights. The information given  
does not release the buyers from making their own experiments and tests.  
PLC Health Monitoring & Reporting Sys  
ii  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
TABLE OF CONTENTS  
1.1  
LIMITED WARRANTY .................................................................................................................. I  
SAFETY INFORMATION................................................................................................V  
SECTION 2. GENERAL INFORMATION.....................................................................2-1  
2.1  
2.2  
SCOPE .......................................................................................................................................2-1  
GENERAL DESCRIPTION...............................................................................................................2-1  
2.2.1 PLCHMR System Module......................................................................................................2-1  
2.2.2 Model SGC-60 Master Controller replacement Micro-Controller Unit....................................2-1  
2.2.3 Model SGF-60-E Flash-head replacement Micro-Controller Unit..........................................2-2  
SAFETY PRECAUTIONS .............................................................................................................................2-6  
2.3  
SPECIFICATIONS .........................................................................................................................2-9  
SECTION 3. INSTALLATION & POWER UP..............................................................3-1  
3.1  
3.2  
UNPACKING ................................................................................................................................3-1  
USER SUPPLIED TOOLS...............................................................................................................3-1  
3.2.1 Master Controls Switch Setting For Installation ...................................................................3-1  
3.2.2 Power Configuration.............................................................................................................3-2  
3.3  
INSTALLATION .............................................................................................................................3-2  
3.3.1 Installation Overview ............................................................................................................3-2  
3.3.2 SGC-60 Master Controller MCU Upgrade ...........................................................................3-2  
3.3.3 PLCHMR Module Installation...............................................................................................3-5  
3.3.4 SGF-60-E Flash-head Digital Controller MCU Upgrade......................................................3-8  
3.4  
3.5  
FLASH HEAD STATUS REPORTING RELAY INSTALLATION WIRING .................................................3-11  
FINAL INSTALLATION CHECK ......................................................................................................3-13  
3.5.1 Preliminary..........................................................................................................................3-13  
3.5.2 Verify Correct Wiring from the PLCHMR Module to Master Controller..............................3-13  
3.6  
POWER UP AND SYSTEM TESTS.................................................................................................3-13  
3.6.1 PLCHMR Status Indicators ................................................................................................3-13  
3.6.2 System Power Up...............................................................................................................3-13  
3.7  
PLCHMR SYSTEM MAINTENANCE AND CONFIGURATION MENUS ...................................................3-16  
3.7.1 PLCHMR System Maintenance & Configuration Menus Overview ...................................3-16  
3.7.2 HMS Maintenance Menu Login..........................................................................................3-18  
3.7.3 HMS Light Configuration Menu..........................................................................................3-19  
3.7.4 PLCHMR Report Configuration Menu................................................................................3-21  
3.7.5 PLCHMR Facility Configuration Menu ...............................................................................3-22  
3.7.6 Verify Local Mode Operation..............................................................................................3-23  
SECTION 4. PRINCIPLES OF OPERATION...............................................................4-1  
4.1  
OVERALL DESCRIPTION...............................................................................................................4-1  
SECTION 5. MAINTENANCE......................................................................................5-1  
5.1  
PLCHMR MODULE.....................................................................................................................5-1  
SECTION 6. REPLACEMENT PARTS........................................................................6-1  
SECTION 7. APPENDIX A – EXAMPLES...................................................................7-1  
7.1  
LIGHT CONFIGURATION EXAMPLES...............................................................................................7-1  
PLC Health Monitoring & Reporting Sys  
iii  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
TABLE OF FIGURES  
Figure 2.2-1 PLCHMR Module.....................................................................................2-3  
Figure 2.2-2 Master Controller with PLCHMR Module Installed...................................2-4  
Figure 2.2-3: Model SGF-60E Flash Head...................................................................2-5  
Figure 3.3-1 Model SGC-60 Master Controller with MCU High-lighted .......................3-4  
Figure 3.3-2 PLCHMR Module Mounted on and Wired to Master Controller................3-6  
Figure 3.3-3 Terminal Block- 8 +16V - Red and GND –Black Wire Connections .........3-7  
Figure 3.3-4 StrobeGuard Control & Status Network Wiring Connections ...................3-8  
Figure 3.3-5 MCU Location on Flash Head Digital Logic Controler............................3-10  
Figure 3.4-1 PLCHMR's Output Relay connection Diagram.......................................3-12  
Figure 3.6-1 Master Controller Circuit Board..............................................................3-15  
Figure 3.7-1 PC to PLCHMR RS-232 Serial Port Interface Cable Connections.........3-17  
Figure 3.7-2 HMS Maintenance Menu Hierarchy .......................................................3-18  
Figure 3.7-3 HMS Maintenance Menu........................................................................3-19  
Figure 3.7-4 HMS Light Configuration Menu..............................................................3-20  
Figure 3.7-5 HMS Modify Light Menu.........................................................................3-21  
Figure 3.7-6 HMS Report Confguration Menu............................................................3-22  
Figure 3.7-7 HMS Facility Conguration Menu ............................................................3-22  
Figure 7.1-1 Tower Example with 9 Flash Heads on Three Physical Tiers ..................7-2  
Figure 7.1-2 Light Configuration Menus Settings for 9 Lights and 7 Relay Outputs.....7-3  
Figure 7.1-3 System Configuration with 9 Flash Heads using 7 relays ........................7-4  
Figure 7.1-4 Light Configuration Menus Settings for 24 Light and 8 Relay Outputs.....7-5  
Figure 7.1-5 System Configuration with 24 Flash Heads using 8 relays ......................7-6  
PLC Health Monitoring & Reporting Sys  
iv  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
SAFETY INFORMATION  
This section contains general safety instructions for using your Honeywell equipment. Task  
and equipment-specific Warnings are included in other sections of this manual where  
appropriate. Read all Warnings and follow all instructions carefully. Failure to do so may  
result in personal injury, death, or property damage. To use this equipment safely, refer to  
the following:  
1. Refer to the FAA Advisory Circular AC 150/5340-26, Maintenance of Airport Visual  
Aids Facilities, for instructions on safety precautions.  
2. Observe all safety regulations. To avoid injuries, always remove power prior to  
making any wire connections and/or touching any parts. Refer to FAA Advisory  
Circular AC 150/5340-26.  
3. Read and become familiar with the general safety instructions provided in this section  
of the manual before installing, operating, maintaining, or repairing this equipment.  
4. Read and carefully follow the instructions given throughout this manual before  
performing specific tasks and working with specific equipment.  
5. Store this manual within easy reach of personnel installing, operating, maintaining, or  
repairing this equipment.  
6. Follow all applicable safety procedures required by your company, industry standards,  
and government or other regulatory agencies.  
7. Obtain and read Material Safety Data Sheets (MSDS) for all materials used.  
SAFETY AND WORKMANSHIP ALERTS  
This manual uses two types of markings when giving instructions requiring special  
attention. The markings will be followed by indented text:  
WARNING!  
The WARNING sign in this manual denotes a hazard. The WARNING  
calls attention to a procedure or practice which, if not correctly  
performed or adhered to, could result in property damage, injury or  
death. Do not proceed beyond a WARNING sign until the indicated  
conditions are fully understood and met.  
.
CAUTION  
Failure to obey the instructions following a CAUTION marking may  
result in equipment damage.  
PLC Health Monitoring & Reporting Sys  
v
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
QUALIFIED PERSONNEL  
The term “qualified personnelis defined here as individuals who thoroughly understand  
the equipment and its safe operation, maintenance, and repair. Qualified personnel are  
physically capable of performing the required tasks, familiar with all relevant safety rules  
and regulations and have been trained to safely install, operate, maintain, and repair the  
equipment. It is the responsibility of the company operating this equipment to see that  
its personnel meet these requirements.  
INTERLOCKS  
This equipment contains interlocks for your protection. To ensure safety, always  
remove power from the equipment prior to opening access panels or doors if possible.  
Do not depend on the interlocks or door switches when working with the equipment. Do  
not short-circuit or tamper with any access gate, door or other safety interlock switch.  
Discharge capacitors with an approved insulated grounding rod prior to touching any  
part. When it is absolutely mandatory that an interlock be bypassed for the purpose of  
tracing or correcting a malfunction, authorized maintenance personnel may perform the  
bypass for the specific test to be made. Immediately after completing the test, restore  
the interlock to working condition.  
WARNING!  
INTENDED USE  
HONEYWELL IS NOT RESPONSIBLE FOR INJURIES OR DAMAGES  
RESULTING FROM NONSTANDARD, UNINTENDED APPLICATIONS OF  
ITS EQUIPMENT. THIS EQUIPMENT IS DESIGNED AND INTENDED  
ONLY FOR THE PURPOSE DESCRIBED IN THIS MANUAL. USES NOT  
DESCRIBED IN THIS MANUAL ARE CONSIDERED UNINTENDED USES  
AND MAY RESULT IN SERIOUS PERSONAL INJURY, DEATH OR  
PROPERTY DAMAGE. UNINTENDED USES MAY RESULT FROM  
TAKING ANY OF THE ACTIONS LISTED BELOW.  
1. Making changes to the equipment that have not been recommended  
or described in this manual, or using parts that are not genuine  
Honeywell replacement parts.  
2. Failing to make sure that auxiliary equipment complies with  
approval agency requirements, local codes, and all applicable  
safety standards.  
3. Using materials or auxiliary equipment that are inappropriate or  
incompatible with your Honeywell equipment.  
4. Allowing unqualified personnel to perform any task.  
PLC Health Monitoring & Reporting Sys  
vi  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
WARNING!  
KEEP AWAY FROM LIVE CIRCUITS. OPERATION AND MAINTENANCE  
PERSONNEL MUST OBSERVE ALL SAFETY REGULATIONS AT ALL  
TIMES.  
DO NOT CHANGE PLUG-IN COMPONENTS OR MAKE  
ADJUSTMENTS INSIDE EQUIPMENT WITH THE HIGH VOLTAGE  
SUPPLY ON. UNDER CERTAIN CONDITIONS, THERE IS A POTENTIAL  
FOR SERIOUS INJURY FROM CIRCUITS WITH POWER CONTROLS IN  
THE OFF POSITION. THIS IS DUE TO CHARGES RETAINED BY THE  
CAPACITORS. TO AVOID SERIOUS INJURY, ALWAYS DISCONNECT  
POWER, THEN DISCHARGE CAPACITORS BY USING AN APPROVED  
GROUNDING ROD PRIOR TO TOUCHING ANY PART.  
RESUSCITATION. MAINTENANCE PERSONNEL SHOULD BE TRAINED  
IN CARDIOPULMONARY RESUSCITATION (CPR).  
CAUTION  
This equipment contains static sensitive semiconductor devices and  
integrated circuits that may be damaged by Electro-Static Discharge  
(ESD). Take the necessary precautions before attempting service.  
Any replacement circuit boards should be kept in metallized anti-static  
bags until immediately before installation. Ground yourself (touch the  
outside of a grounded metal enclosure) before removing circuit boards  
from their protective bags. Avoid touching components when handling  
the boards.  
PLC Health Monitoring & Reporting Sys  
vii  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
SECTION 2. GENERAL INFORMATION  
2.1  
Scope  
This manual provides information about the installation, operation, and maintenance of  
the Programmable Logic Controller Health Monitoring and Reporting (PLCHMR) System  
manufactured by Honeywell.  
2.2  
General Description  
The PLCHMR system is a retrofitable health monitoring and reporting system for  
Honeywell’s high intensity flashing white obstruction lighting system. A majority of the  
system’s functionality is contributed by the PLCHMR module. It is designed for use with  
the StrobeGuard, Model SG-60E High Intensity Obstruction Lighting System. The  
system is designed and manufactured in compliance with Federal Aviation  
Administration Advisory Circular 150/5345-43E. The PLCHMR system will monitor and  
report on up to 24 flash-heads controlled by a single controller at distances up to 2500  
feet.  
The PLCHMR System module is shown in Figure 2.2-1. The major components of the  
retrofit kit consist of the following:  
PLCHMR System Module P/N 40002083-001  
Model SGC-60 Master Controller replacement Micro-Controller Unit (MCU P/N  
40002085-001)  
Model SGF-60 Flash-head replacement micro-controller units (one for every flash  
head P/N 40002084-001)  
2.2.1 PLCHMR System Module  
The PLCHMR module (see Figure 2.2-1) is a configurable microprocessor-based  
system that monitors a StrobeGuard, Model SG-60E High Intensity Obstruction  
Lighting system via the RS485 control and status network. The PLCHMR outputs alarm  
status via dry contact relays to a remote alarm monitoring system. The PLCHMR  
module is preassembled and consists of three circuit card assemblies affixed to  
mounting plate. The module provides 2 wiring harnesses that must be attached to two  
terminal connectors located on the Model SGC-60 Master Controller (See Figure 2.2-2).  
2.2.2 Model SGC-60 Master Controller replacement Micro-Controller Unit  
The Master Controller (see Figure 3.3-1) is a micro-controller based system that  
controls the flash interval and timing, flash intensity, and monitors the complete  
StrobeGuardsystem via the StrobeGuardRS485 control and status network  
(SCSN). The MCU must be replaced during the installation process in order for the  
PLCHMR to monitor the SCSN. Software in the new micro controller changes the baud  
rate of the SCSN from 300 to 9600 baud. A replacement MCU is provided as part of the  
upgrade kit (P/N 40002085-001 and replaces P/N40000328-001).  
PLC Health Monitoring & Reporting Sys  
2-1  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
2.2.3 Model SGF-60-E Flash-head replacement Micro-Controller Unit  
The SGF-60E Flash-head (see Figure 2.2-3) is a micro-controller based system that is  
designed to control a capacitor discharge xenon flash tube unit. The Flash-head  
receives its flash interval, timing, flash intensity commands from, and returns status to  
the Master Controller via the SCSM. Replacement MCUs are provided as part of the  
upgrade kit (P/N 40002084-001 and replaces old MCU P/N40000324-001).  
PLC Health Monitoring & Reporting Sys  
2-2  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
PLCHMR  
Configuration  
Serial Port  
Power On LED  
Power Supply  
Single Board  
Computer  
Top view  
Side view  
Relay Interface  
Card  
StrobeGuard  
Control and  
Status Network  
wiring.  
Mounting Plate  
Figure 2.2-1 PLCHMR Module  
PLC Health Monitoring & Reporting Sys  
2-3  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Figure 2.2-2 Master Controller with PLCHMR Module Installed  
PLC Health Monitoring & Reporting Sys  
2-4  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
N O  
N O  
N C  
N C  
C
C
N O  
N C  
+
AC  
C
-
AC  
Figure 2.2-3: Model SGF-60E Flash Head  
PLC Health Monitoring & Reporting Sys  
2-5  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Safety Precautions  
The following general safety precautions must be observed during all phases of operation,  
service, and repair of this equipment. Failure to comply with these precautions or with  
specific warnings elsewhere in this manual violates safety standards of design,  
manufacture, and intended use of this equipment. Honeywell assumes no liability for the  
customer’s failure to comply with these requirements, as listed below.  
1. Any interruption of the protective grounding conductor (inside or  
outside the instrument) or disconnecting the protective earth ground  
terminal is likely to make this equipment dangerous. Intentional  
interruption is prohibited.  
2. Whenever it is likely that the ground protection has been impaired, the  
equipment must be made inoperative by removing AC line power, and  
then shall be secured against any unintended operation.  
3. Ensure that only fuse / Breakers with the required rated current and of  
the specified type (normal blow, time delay, etc.) are used for  
replacement. The use of repaired fuses and the short-circuiting of fuse  
holders must be avoided.  
4. Electrical energy available at many points may result in personal injury  
or death if touched. Any adjustment, maintenance, and repair of the  
opened equipment while power is applied shall be avoided as much as  
possible, however some maintenance described in this manual is  
performed with power supplied to the equipment while protective  
covers are removed. When repair with power applied is unavoidable,  
only a skilled person who is aware of the hazard involved shall carry  
out maintenance. Do not attempt internal service or adjustment unless  
another person, capable of rendering first aid and resuscitation, is  
present.  
5. Do not install, substitute parts or perform any unauthorized  
modification to the equipment.  
6. Make sure the input voltage selection on the Ferroresonant  
transformer assembly matches the line voltage before applying power  
to the unit.  
Capacitors inside the equipment may still be charged after the equipment has  
been disconnected from its power source, even though the equipment was  
designed to drain charge from the capacitors when power is removed. Do not put  
hands or tools in the Flash-head if the High Voltage Indicator neon lamp NE1 is  
ON, which is located on the High Voltage Circuit Board. (Refer to Figure 2.2-3)  
7. Do not confuse the High Voltage Indicator NE1, with the POWER ON  
Indicator located on the Ferro resonant Transformer Assembly. It is  
possible for the High Voltage Indicator NE1 to be ON After the main  
AC power to the unit is turned OFF (POWER ON Indicator is OFF). If  
this happens, the energy stored in the capacitor Assembly must be  
discharged before performing maintenance.  
PLC Health Monitoring & Reporting Sys  
2-6  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
8. Capacitor Discharge Procedure. Attach one end of the capacitor  
discharge tool to chassis ground first, then the other end to any of the  
relay terminals. Hold for 3 seconds, or until the indicator turns off.  
PLC Health Monitoring & Reporting Sys  
2-7  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
WARNING!  
This system uses lethal voltages in the Flash-head. Unless absolutely  
necessary, do not attempt to service or adjust the equipment with AC  
line power applied.  
Safety interlock switches are provided in the Flash-head enclosure to  
interrupt main AC power to the power supply. These interlock switches  
are activated when the Flash-head door is opened in a conventional  
manner. No interlock is provided when other means of access are  
used. Do not tamper with the interlocks by opening or shorting the  
terminals.  
The POWER ON Indicator is ON when the Ferroresonant Transformer is  
powered. If the POWER ON Indicator is OFF, Line input AC power may  
still be present in the system.  
AC LINE VOLTAGE IS STILL PRESENT WHEN INTERLOCKS ARE  
ACTIVATED. DISCONNECT POWER AT THE MAIN AC CIRCUIT  
BREAKERS BEFORE INSPECTING OR SERVICING, UNLESS  
ABSOLUTELY NECESSARY TO PERFORM MAINTENANCE WITH  
POWER ON.  
WARNING!  
Flash tubes in this lighting system produce brilliant flashes of light  
containing some ultraviolet radiation that can cause temporary or  
permanent eye damage.  
DO NOT LOOK DIRECTLY AT THE FLASH-HEAD WHILE IT IS IN  
OPERATION.  
PLC Health Monitoring & Reporting Sys  
2-8  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
2.3  
Specifications  
Electrical Input:  
PLCHMR Module .................................................................................... 3 Watts. 5 VDC.  
Mechanical Properties:  
PLCHMR Module  
Weight.............................................................................................2 pounds (4.4 kg)  
Dimensions ......................................5.6"w (142mm) x 5.7"h (145mm) x 2"d (51mm)  
Operating Environment:  
Operating Temperature.............................................................................-55ºC to +55ºC  
Humidity...........................................................................................95% relative humidity  
System Operating Status Indicators:  
PLCHMR, DC line power present .............................. Green LED POWER ON Indicator  
PLC Health Monitoring & Reporting Sys  
2-9  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
SECTION 3. INSTALLATION & POWER UP  
WARNING!  
Modifications to the Power Supply are required for certain applications.  
Remove input power at circuit breakers and discharge capacitors with  
an approved grounding rod before attempting any necessary  
modifications.  
3.1  
Unpacking  
Carefully unpack each item and remove any internal packing material from the  
PLCHMR. Carefully check the supplied materials with the PLCHMR bill of materials.  
There are many small items that should be supplied inside clear plastic bags, verify  
each of these bags contain the proper amount of parts per the bill of materials. Report  
any shortages of materials immediately to the Honeywell Technical Support.  
Examine each item for obvious physical damage. Report any claims to the carrier  
immediately.  
Pertinent information such as installation drawings, schematics,  
interconnection drawings, and operation manuals are included in the carton. The  
upgraded 8051 micro-controllers (MCU) replacements for the master control and each  
flash head are in a separate package(s) inside the carton. Do not remove 8051 MCUs  
from their respective packaging until you are ready to install them.  
3.2  
User Supplied Tools  
PC computer with RS232 serial port,  
Serial port parameters: 115200 baud, 8 data bits, no parity, 1 stop bit.  
Terminal Emulator – MS Windows Hyper Terminal, Tera Term  
Screwdriver ¼:” slot-type  
Screwdriver 1/16” slot-type  
Small Phillips screwdriver  
DB9 to DB9 Female/Female RS2232 Null Modem Serial Interface Cable (Radio  
Shack Model 03044 Catalog # 55010600 or equivalent)  
3.2.1 Master Controls Switch Setting For Installation  
Set Master Controller switches (Shown in Figure 2.2-2) as follows:  
POWER SWITCH --------------------------------------------------------------------------- OFF  
LOCAL / REMOTE Switch ------------------------------------------------------------ LOCAL  
MODE Switch -------------------------------------------------------------------------------- DAY  
The Master Controller has the following control switches (Figure 2.2-2):  
PLC Health Monitoring & Reporting Sys  
3-1  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
POWER SWITCH: Toggle switch that turns input AC line power on/off in the Master  
Controller. Does not affect AC power to the Flash-heads. Input voltage is present  
at terminal block PB1, even with the power switch turned off.  
RESET Switch: Momentary pushbutton that resets the Master Controller. Switch  
must be held for about one second to activate.  
REMOTE / LOCAL Mode Switch: Two-position toggle switch that permits manual  
(local) selection of the flash intensity level using the DAY / TWILIGHT / NIGHT  
rotary switch. In normal (remote) operation, permits automatic operation controlled  
by the Ambient Light Sensor photocell.  
DAY / TWILIGHT / NIGHT Switch: Three-position rotary switch that allows manual  
selection of three light intensities of the system (DAY = high, TWILIGHT =  
intermediate, and NIGHT = low). The REMOTE / LOCAL Mode Switch must be in  
the LOCAL position to use this switch.  
3.2.2  
Power Configuration  
The PLCHMR input voltage selection is set at the factory prior to shipping.  
3.3  
Installation  
3.3.1  
Installation Overview  
The installation has four major activities:  
First, replace the Master controller’s MCU with the one MCU provided by the kit  
Second, mount and wire the PLCHMR module.  
Third, replace the MCU in each Flash-head’s digital control board with the MCU  
provided by the kit.  
Fourth, the PLCHMR’s site specific configuration table must be edited to match  
the configuration of the high intensity strobe system; this activity is described in  
Section 3.7.  
The following sub-sections feature detailed instructions for completing the installation  
outlined above.  
3.3.2  
SGC-60 Master Controller MCU Upgrade  
The installation kit provides one new MCU P/N 40002085-001 to replace the old MCU  
P/N 40000328-001. It is important to install the MCU with the proper orientation since,  
more often than not installing a MCU backwards will result in damage to the chip and/or  
surrounding circuitry. First note the location of pin 1. To find pin 1 look for a small  
rectangular notch on one of its short ends this denotes the top side of MCU; the first pin  
counter-clockwise from this notch is pin 1. The MCU is pressed into a socket. The  
PLC Health Monitoring & Reporting Sys  
3-2  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
MCU’s socket has a notch along the outside edge on one of the short sides this is the  
top side of the socket.  
CAUTION!  
Do not use excessive force when you remove or install the chip  
from/into its socket. Excessive force can bend or damage the MCU  
Pins or the socket.  
Step 1  
Gently remove the old MCU using a small flat head screwdriver to pry it free of its  
socket. Set aside the old MCU.  
Step 2  
Carefully place the new MCU in the empty socket with top of the MCU and pin 1  
in the same locations as noted earlier. Inspect all of MCU’s pins checking that  
each pin is inserted into its respective contact and that none of the pins of have  
"roll under" or "bend out" of the socket.  
Step 3  
Carefully press the new MCU into the empty socket until it is firmly seated on the  
socket.  
Step 4  
Place the old MCU into the new MCUs empty shipping container.  
A detailed drawing showing the location of the MCU in the Master Controller is shown in  
Figure 3.3-1.  
PLC Health Monitoring & Reporting Sys  
3-3  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Replace existing  
MCU PN-  
40000328 with  
new MCU PN-  
40002085  
Location of 4  
Screws to be  
removed for the  
PLCHMR Module  
Standoffs  
Figure 3.3-1 Model SGC-60 Master Controller with MCU High-lighted  
PLC Health Monitoring & Reporting Sys  
3-4  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
3.3.3  
PLCHMR Module Installation  
The installation kit provides a PLCHMR module P/N 40002083 that is mounted inside  
the Master Controller Enclosure. This module is mounted to four 2.5” high standoffs  
and has five (5) wires to connect to the Master Controller board.  
3.3.3.1  
PLCHMR Module 2.5” Standoff Installation  
Remove and save the four (4) 6-32 screws that secure the Master Controller to the enclosure’s  
bottom panel (Refer to Figure 3.3-1 for exact screw locations). The four saved screws will be  
used in a later step to secure the PLCHMR module mounting plate to the standoffs.  
3.3.3.2  
PLCHMR Module Power Supply Connections  
The PLCHMR module receives 16VDC power from Terminal Block-8 located on the top left  
hand corner of the Master Controller PCB as shown in Figure 3.3-2. Note the orientation and  
locations of the two positions on the plug-in terminal with respect to the +16 and GND Labels  
shown on the Master Controller PCB. Remove the two position plug-in terminal and loosen both  
of the plug-in terminal’s screw sufficiently to install the PLCHMR module’s red and black wires.  
The red wire should be inserted into the screw terminal position labeled #2 as shown Figure  
3.3-3 which connects to the +16 contact on the Master Controller PCB. The black wire should  
be inserted into the screw terminal position labeled #1 as shown Figure 3.3-3 which connects  
to the GND contact on the Master Controller PCB.  
PLC Health Monitoring & Reporting Sys  
3-5  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
TB8  
Red  
PLCHMR  
Module  
Output Relay  
Terminal Blocks  
Black  
TB-5  
Figure 3.3-2 PLCHMR Module Mounted on and Wired to Master Controller  
PLC Health Monitoring & Reporting Sys  
3-6  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Black Wire  
Red Wire  
Figure 3.3-3 Terminal Block- 8 +16V - Red and GND –Black Wire Connections  
3.3.3.3 PLCHMR Module Mount  
The PLCHMR module mounts to the four 2.5” high standoffs that were installed per directions in  
Section 3.3.3.1. Note the location and orientation of the PLCHMR module as shown in Figure  
3.3-2 relative to the Master Controller. Oriented the PLCHMR module and place it  
approximately as shown per Figure 3.3-2 on the 2.5” high standoffs. Then re-connect the two  
position PLCHMR power supply plug-in with its mating header block on the Master Controller.  
Carefully position the PLCHMR module so that the four (4) mounting plate holes line-up with  
four tapped bores in the 2.5” standoff. Secure the mounting plate to the standoff by installing  
the four (4) 6-32 screws removed during the Section 3.3.3.1 activities.  
3.3.3.4  
PLCHMR Module StrobeGuard Control and Status Network Connections  
The PLCHMR module connects to the StrobeGuard Control and Status Network via  
Terminal Block-5 which is located near the bottom center of the Master Controller PCB as  
shown in Figure 3.3-2. Before starting this task, note any existing wiring connections along  
with their orientation and locations relative to the four position plug-in terminal connected to the  
Master Controller. Remove the four position plug-in terminal. Install the White, Blue, and Black  
PLCHMR’s network wires as directed:  
a) Loosen the plug-in terminal’s screw labeled #1 as shown in Figure 3.3-4 sufficiently to  
insert the PLCHMR module’s White wire into terminal position along with maintaining  
any existing wiring connections.  
PLC Health Monitoring & Reporting Sys  
3-7  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
b) Next, loosen the plug-in terminal’s screw labeled #2 as shown in Figure 3.3-4  
sufficiently to insert the PLCHMR module’s Blue wire into this terminal position along  
with maintaining any existing wiring connections.  
c) Finally, sufficiently loosen the plug-in terminal’s screw labeled #4 as shown in Figure  
3.3-4 and insert the PLCHMR module’s Black wire into the terminal position while  
maintaining any existing wiring connections.  
Reinstall the plug-in terminal onto its corresponding fixed mating header located on the Master  
Controller.  
1 2 3 4  
White Wire  
Blue Wire  
Black Wire  
Figure 3.3-4 StrobeGuard Control & Status Network Wiring Connections  
3.3.4  
SGF-60-E Flash-head Digital Controller MCU Upgrade  
The installation kit provides new MCUs P/N 40002084-001 to replace all existing old  
MCUs P/N 40000324-001 in Flash Head Logic Control Board. See Figure 2.2-3 for the  
location of Logic Control Board in the Flash Head Enclosure. It is important to install the  
MCU with the proper orientation since more often than not installing a MCU backwards  
will result in damage to the chip and/or surrounding circuitry. First note the location of  
pin 1. To find pin 1 look for a small rectangular notch on one of its short ends this  
denotes the top side of MCU; the first pin counter-clockwise from this notch is pin 1.  
PLC Health Monitoring & Reporting Sys  
3-8  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
The MCU is pressed into a rectangular socket. This socket has a notch along the  
outside edge on one of the short sides this is the top side of the socket.  
CAUTION!  
Do not use excessive force when you remove or install the chip  
from/into its socket. Excessive force can bend or damage the MCU  
Pins or the socket.  
Step 1  
Gently remove the old MCU using a small flat head screwdriver to pry it free of its  
socket. Set aside the old MCU.  
Step 2  
Carefully place the new MCU in the empty socket with top of the MCU and pin 1  
in the same locations as noted earlier. Inspect all of MCU’s pins checking that  
each pin is inserted into its respective contact and that none of the pins of have  
been "rolled under" or "bent out" of the socket.  
Step 3  
Carefully press the new MCU into the empty socket until it is firmly seated on the  
socket.  
Step 4  
Place the old MCU into its replacement’s empty shipping container.  
A detailed drawing showing the location of the MCU in the Flash-Head’s Digital Master  
Controller is shown in Figure 3.3-5.  
PLC Health Monitoring & Reporting Sys  
3-9  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Figure 3.3-5 MCU Location on Flash Head Digital Logic Controler  
PLC Health Monitoring & Reporting Sys  
3-10  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
3.4  
Flash Head Status Reporting Relay Installation Wiring  
The PLCHMR features eight (8) configurable status reporting outputs. Each output  
connects to a form-c relay via three screw terminal connections. Each screw terminal  
connection is uniquely tied to one of the relay’s contacts. In accordance with Figure  
3.4-1:  
1) Terminal labeled #1 connects to the normally-open contact  
2) Terminal labeled #2 connects to the common contact  
3) Terminal labeled #3 connects to the normally-closed contact,  
Typically each discrete alarm reporting connections is made to the site’s alarm  
monitoring system uses terminals 1 & 2. Using the typical connection ensures that a  
fail/fault indication is reported in the event that power is interrupted to the SG-60 High  
Intensity Strobe Light System.  
Each relay’s state is controlled uniquely by its software Tier Reporting Mechanism  
(TRM). The TRM is software configurable and enables the operator via a menu to  
combine tier related flash-heads into a group that can be associated with a TRM. (See  
Section 3.7.3 for additional details on software configuration)  
The two operating states (activated/deactivated) of each relay represent the state of its  
corresponding TRM. The TRM’s two states are Flash/OK and Fail/Fault. The TRM  
state FLASH/OK represents a normal operation alarm level and is indicated by an  
activated relay. The TRM state Fail/Fault represents an abnormal operation alarm level  
and is indicated by a deactivated relay.  
For example:  
Assume that all the flash-heads on tier #1 are operating normally when some event  
causes a tier’s flash-head to malfunction. While all of the flash-heads on tier 1 are ok,  
TRM #1 is set to FLASH/OK and relay #1 is activated. After the fault event occurs  
causing a flash-head on the tier to malfunction, then TRM #1 would automatically  
change to the Fail/Fault state which would de-activate relay #1.  
An activated relay cause the normally-open contact to be closed allowing any signal  
applied to the common contact(#2) to appear on the normally-open contact (#1). For a  
deactivated relay the normally-close contact is closed allowing any signal applied to the  
common contact (#2) to appear normally-closed contact (#3).  
PLC Health Monitoring & Reporting Sys  
3-11  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
1
Relay 1  
Relay 2  
Relay 3  
Relay 4  
2
3
1
2
3
1
2
3
1
2
3
Digital Inputs  
Do Not Use  
1
2
3
1
2
3
Relay 5  
Relay 6  
1
2
3
1
2
3
Relay 7  
Relay 8  
- V 2 0 8 R 9 1 6 0 4  
i - r M . c o m : / / w w h t w t p . T  
T r i - M E n g i n e e r i n g  
Figure 3.4-1 PLCHMR's Output Relay connection Diagram  
-
PLC Health Monitoring & Reporting Sys  
3-12  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
3.5  
Final Installation Check  
Before applying power to the equipment, perform the procedures in the following  
sections. If any test does not pass, please consult Sections 3.3.3.2 and 3.3.3.4 in this  
manual or call Honeywell Technical Support at (805) 581-5591.  
3.5.1  
Preliminary  
1.  
2.  
Verify that all AC input power circuit breakers are turned off.  
Check that the MCU on the Master Controller’s printed circuit boards is  
properly seated in its socket.  
3.  
4.  
Check that any user-installed wiring does not interfere with relay operation  
when covers are closed.  
Check that replacement MCUs have been installed in all Flash-heads.  
Check that all Flash-head covers are shut properly for a weather-tight seal  
with all latches closed.  
5.  
Set Master Controller switches as follows:  
POWER SWITCH ------------------------------------------------------------------ OFF  
LOCAL / REMOTE Switch --------------------------------------------------- LOCAL  
MODE Switch ----------------------------------------------------------------------- DAY  
3.5.2  
Verify Correct Wiring from the PLCHMR Module to Master Controller  
Check that power supply and StrobeGuard Network connectors on the printed circuit  
boards are properly seated in their sockets (Re-Verify that Sections 3.3.3.2 and 3.3.3.4  
were performed correctly).  
3.6  
Power Up and System Tests  
During the power up of the system, there are two LED lights, which will be checked to  
verify correct operation and installation. The following is a description of all the  
indicators on PLCHMR.  
3.6.1  
3.6.2  
PLCHMR Status Indicators  
Power Status Indicators (Figure 2.2-1)  
ƒ Red LED after power-up indicates Single Board Computer Fault  
ƒ Green LED indicates Power is OK  
System Power Up  
All switches and indicators listed in this section are in the Master Controller, except for  
the external system circuit breakers.  
PLC Health Monitoring & Reporting Sys  
3-13  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Verify POWER SWITCH is turned OFF.  
Verify LOCAL / REMOTE switch is set to LOCAL.  
Verify MODE switch is set to DAY.  
Turn on circuit breaker to apply power to Master Controller.  
Turn on circuit breaker to apply power to Flash-heads.  
Turn POWER SWITCH to ON.  
Verify that the Master Controller LED test sequence has started (See  
EPM-00001152 - Installation and Operating Guide for High Intensity  
Obstruction lighting). The test sequence will exercise every LED and relay  
(e.g. it will quickly sweep through the Flash-head Status LEDs in red and  
green mode).  
After the test sequence completes, the Flash-head status LEDs for the  
selected number of Flash-heads shall be lit red then change to green as  
the Flash-heads report (DS1 - DS24, Figure 3.6-1 Item 4).  
8.  
9.  
After 1 minute, verify the number of Flash-head status LEDs (DS1 - DS24,  
Figure 3.6-1 Item 4) that are lit green matches the total number of white  
Flash-head lights (including AOL) on the tower (if there are n Flash-heads  
on the tower, Flash-head status LEDs DS1 - DSn shall be lit green). Verify  
that the remaining unused Flash-head status LEDs (DSn+1 - DS24) are  
turned off.  
After all the flash-heads report good (green), check the Master Control  
board’s relay monitoring LEDs which should display following:  
i. DS29-DS32 GREEN,  
ii. DS33 OFF (DS29 - DS33, Figure 3.6-1 Item 5.) Verify Photocell  
status LED DS28 (Figure 3.6-1, Item 3) is lit green.  
iii. Verify Day Mode LED DS25 (Figure 3.6-1, Item 3) is lit red, and  
the Twilight and Night LEDs (DS26 and DS27 respectively Figure  
3.6-1, Item 3) are not lit.  
iv. Hold down the RESET switch for approximately 1 second and  
verify the LED test sequence has restarted.  
PLC Health Monitoring & Reporting Sys  
3-14  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Wait 1 minute and measure the voltage between TB1-1 and TB1-2 to verify the voltage  
is 12-18 VAC. Repeat steps 7 - 10 to assure proper recovery after reset.  
Figure 3.6-1 Master Controller Circuit Board  
PLC Health Monitoring & Reporting Sys  
3-15  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Note: Before performing any tests of the Flash Head  
Reporting Relay wiring the system must be configured  
using the PLCHMR System Maintenance and  
Configuration Menus.  
3.7  
PLCHMR System Maintenance and Configuration Menus  
3.7.1  
PLCHMR System Maintenance & Configuration Menus Overview  
The PLCHMR system must be configured as part of the on-site installation. The  
PLCHMR’s maintenance menus are used to view and modify the site specific  
configuration data. The maintenance menus use a text window interface along with a  
command entry prompt. The command entry prompt is posted at the bottom of terminal  
window and is marked with “maint>”. Configuration data in the maintenance menus  
contains information about the site’s lights, its reporting mechanism, and the facility  
information. The site’s light configuration data contains information on how many lights,  
which tiers the lights are located, and height above ground level. The reporting  
configuration will specify if the reports are to be made via Ethernet or relays. The facility  
information will include: the owner, contact number, address, FCC number, Altitude,  
Longitude, and Latitude.  
The maintenance menu system has a hierarchical structure which begins with the  
Health Monitoring System (HMS) home maintenance menu (see Figure 3.7-2). The  
home maintenance menu is the initial menu presented after the maintenance login is  
completed.  
The home maintenance menu can be recognized by the “HMS  
Maintenance Menu” title along with its four numbered menu items (See Figure 3.7-3).  
PLC Health Monitoring & Reporting Sys  
3-16  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Figure 3.7-1 PC to PLCHMR RS-232 Serial Port Interface Cable Connections  
PLC Health Monitoring & Reporting Sys  
3-17  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
HMS Maintenance Menu  
1) Light Configuration  
2) Report Configuration  
3) Facility Information  
4) Exit  
Press 1  
Press 3  
Press 9  
Press 25  
Press 2  
Press 5  
HMS Report Configuration Menu  
Current Report Method: Relays + ETHERNET  
1) NONE – Change report method to none  
HMS Facility Configuration Menu  
1) OWNER  
2) Relays – Change report method to relays  
3) ETHERNET – Change report to ethernet  
2) CONTACT NUMBER  
3) ADDRESS LINE 1  
4) FCC NUMBER  
5) Altitude  
4) Relays & ETHERNET – Change report method to include both  
5) Exit  
7) Longitude  
HMS Light Configuration Menu  
8) Latitude  
Lamp_ID Tier_Lvl Height Facing_Dir Priority  
9) Exit  
Press 1  
1)  
2)  
3)  
1
1
1
1
151  
152  
151  
NW  
SE  
1
2
1
1
1
SW  
25) Exit  
HMS Modify Light Menu  
1) Lamp ID: 1  
2) Tier Level: 1  
3) Height : 151 Feet AGL  
4) Direction: NW  
6 Clear All fields  
7)Exit  
Press 7  
maint>1  
Figure 3.7-2 HMS Maintenance Menu Hierarchy  
The following is a detailed set of instructions for navigating and utilizing PLCHMR’s  
maintenance menu system.  
3.7.2  
HMS Maintenance Menu Login  
Access to the Maintenance Mode menus is restricted. A login id and password are  
used to control access to the Maintenance Mode Menus. To gain access to the  
maintenance mode menu use the following steps:  
a) Connect one of the PC/Laptop’s serial ports to the PLCHMR’s serial port using a  
female/female null modem serial interface cable as shown in Figure 3.7-1 (Radio  
Shack Model 03044 Catalog # 55010600 or equivalent). The PLCHMR’s serial  
port connection requires a DB-9 female connector.  
b) On the PC/Laptop start a terminal emulator. Either HyperTerminal or Tera Term  
is a suitable terminal emulator.  
c) Configure the PC/Laptop’s terminal emulator’s serial port parameters to:  
i) 115200 baud,  
ii) 8 data bits,  
PLC Health Monitoring & Reporting Sys  
3-18  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
iii) no parity,  
iv) 1 stop bit.  
d) Apply power and wait for login prompt. If power is already applied and a login  
prompt is not shown press the enter key.  
e) After the login prompt “login >” is displayed then type “maint” and wait for the  
password prompt.  
f) At the password prompt “password>” type “grimes” and wait for Home  
Maintenance Window to be displayed (See Figure 3.7-3 ).  
HMS Maintenance Menu  
Menu Title  
1) Light Configuration  
Menu Item  
2) Report Configuration  
3) Facility Information  
4) Exit Maintenance Mode  
maint>  
Command  
Prompt  
Figure 3.7-3 HMS Maintenance Menu  
3.7.3  
HMS Light Configuration Menu  
The Light Configuration menu displays the current light configuration and allows the  
user to modify the configuration lines by selecting a line number at the User Prompt  
(See Figure 3.7-4). The Light Configuration menu can be recognized by the “HMS Light  
Configuration Menu” title along with its 24 numbered rows of light data. The light  
configuration menu is a table with six columns and 25 rows. The first column contains  
the row number the remaining five columns have a unique heading. Each row  
represents the location, orientation and priority data for a particular Flash head as  
identified by the number in the Lamp Id column its row.  
The column heading definitions are:  
i.  
Lamp_ID – The unique address or ID# as set on Flash Head’s digital logic  
board SW3. The maximum value for this entry is 24.  
ii.  
Tier_Lvl – The tier or level number for the Flash Head defined s. Typically the  
top tier of flash heads is numbered 1. The maximum value for this entry is 8.  
Each Tier_Lvl is associated with a Tier Report Mechanism (TRM) which  
controls the state of its reporting relay. The status of Tier_Lvl #1 is reported  
via relay #1. Up to 24 flash heads could be assigned to one tier. Typically 3-  
PLC Health Monitoring & Reporting Sys  
3-19  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
4 flash heads are assigned to a tier as this would represent the physical  
installation of the flash heads on one tier of a tower.  
iii. Height – The height as measured from ground level of the obstruction/tower.  
iv. Facing_Dir – Nearest facing cardinal compass direction of the Flash Head.  
System defines eight (8) valid cardinal directions and they are:  
i.  
N
ii.  
iii.  
NW  
E
iv. SE  
v.  
vi.  
S
S
vii. SW  
viii. W  
ix. NW  
v. Priority – Maintenance Priority associated with Flash Head. The range of  
valid values is 0-25. Typically a value of 1 is used to represent the highest  
priority maintenance issue.  
HMS Light Configuration Menu  
Lamp_ID  
Tier_Lvl  
Height  
Facing_Dir  
Priority  
1)  
2)  
3)  
4)  
5)  
6)  
7)  
8)  
1
2
3
4
0
0
0
0
0
1
2
2
3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
151  
152  
153  
164  
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
NW  
SE  
SW  
N
1
2
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
9)  
10)  
11)  
12)  
13)  
14)  
15)  
16)  
17)  
18)  
19)  
20)  
21)  
22)  
23)  
24)  
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
25) Exit  
maint>  
Figure 3.7-4 HMS Light Configuration Menu  
To edit the contents of a specific row in the HMS Light Configuration Menu, enter the  
row number and press the enter key. This action will bring up the HMS Modify Light  
PLC Health Monitoring & Reporting Sys  
3-20  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Menu (see Figure 3.7-5. Once in the Modify Light Menus select the menu item to edit  
by entering the row number of the menu item and pressing enter.  
To erase all configuration data for a specific light listed in the HMS Light Configuration  
Menu enter the row number of the light. This action brings up the HMS Modify Light  
Menu. Next input the number 6 followed by the “Enter” key. After clearing all data  
values input the number 7 along with an “Enter” key to exit to the HMS Light  
Configuration Menu. Selecting the “Exit” menu option commits any changes made in  
that menu to memory.  
HMS Modify Light Menu  
1) Lamp ID:  
2) Tier Level:  
3) Height:  
1
1
151 Feet AGL  
4) Direction:  
5) Priority:  
6) Clear all fields  
7) Exit  
NW  
1
maint>l  
Figure 3.7-5 HMS Modify Light Menu  
3.7.4  
PLCHMR Report Configuration Menu  
The Report Configuration Menu displays the current reporting configuration and allows  
the user to select one of four reporting methods (See Figure 3.7-6). Do not change this  
setting.  
PLC Health Monitoring & Reporting Sys  
3-21  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
HMS Report Configuration Menu  
Current Report Method: RELAYS + ETHERNET  
1) NONE - Change Report method to none.  
2) RELAYS - Change Report method to relays.  
3) ETHERNET - Change Report method to ethernet.  
4) RELAYS+ETHERNET - Change Report method to include both.  
5) Exit  
maint>  
Figure 3.7-6 HMS Report Confguration Menu  
3.7.5  
PLCHMR Facility Configuration Menu  
The Facility Configuration menu displays data about the facility’s operator and its  
location. With this menu the user may edit any data line by selecting its line number at  
the User Prompt and pressing the enter key (See Figure 3.7-7). The Facility  
Configuration menu can be recognized by the “HMS Facility Configuration Menu” title  
along with its 9 numbered rows of facility data.  
HMS Facility Configuration Menu  
1) OWNER:  
Obstruction Lighting  
937-484-2000  
550 State Route 55  
Urbana Oh 43078  
10108227  
2) CONTACT NUMBER:  
3) ADDRESS LINE 1:  
4) ADDRESS LINE 2:  
5) FCC NUMBER:  
6) Altitude:  
1500.00  
7) Longitude:  
40.16  
8) Latitude:  
-83.8  
9) Exit  
maint>  
Figure 3.7-7 HMS Facility Conguration Menu  
PLC Health Monitoring & Reporting Sys  
3-22  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
3.7.6  
Verify Local Mode Operation  
All switches and indicators listed in this section are in the Master Controller.  
3.7.6.1  
Day Mode:  
1.  
2.  
3.  
Verify MODE Switch is set to DAY.  
Verify Day mode LED DS25 (Figure 3.6-1, Item 3) is lit red.  
After about 6 seconds, verify all Flash-heads are flashing in sync and in  
Day mode (maximum brightness).  
4.  
Verify that the Flash-head Status LED for each Flash-head on the tower is  
lit green (including any AOL). Unused Flash-head status LEDs shall be  
off. (DS1 - DS24: Figure 3.6-1, Item 4)  
5.  
6.  
Verify relay status LEDs DS29-DS32 are lit green, and DS33 is OFF.  
(Figure 3.6-1, Item 5)  
If you have a Dual (Red/White) System, the Red Lights should be OFF.  
3.7.6.2  
Twilight Mode:  
1.  
2.  
Set MODE Switch to TWILIGHT.  
Verify Day and Night mode LEDs (DS25 and DS27 respectively Figure  
3.6-1, Item 3) are unlit and the Twilight mode LED DS26 is lit red.  
3.  
4.  
After 6 seconds, Verify all Flash-heads are flashing in sync and in Twilight  
mode (medium brightness).  
Verify that the Flash-head Status LED for each Flash-head on the tower is  
lit green (including any AOL). Unused Flash-head status LEDs shall be  
off. (DS1 - DS24: Figure 3.6-1, Item 4)  
5.  
6.  
Verify relay status LEDs DS29 - DS32 are lit green, and DS33 is off.  
(Figure 3.6-1, Item 5)  
If you have a Dual (Red/White) System, the Red Lights should be OFF.  
3.7.6.3  
1.  
Night Mode  
Set MODE Switch to NIGHT.  
2.  
3.  
Verify Day and Twilight mode LEDs (DS25 and DS26 respectively (Figure  
3.6-1, Item 3) are unlit and Night mode LED DS27 is lit red.  
4.  
Verify that the Flash-head Status LED for each Flash-head on the tower is  
lit green (including any AOL). Unused Flash-head status LEDs shall be  
off. (DS1 - DS24: Figure 3.6-1, Item 4)  
PLC Health Monitoring & Reporting Sys  
3-23  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
5.  
6.  
Verify relay status LEDs DS29-DS31 are lit green, and DS32 and DS33  
are off. (DS29 - DS33: Figure 3.6-1, Item, 5,)  
If you have a White-Only System: After 6 seconds, Verify all Flash-heads  
are flashing in sync and in Night mode (lowest brightness, ~1/8 second  
duration bursts at 40 bursts per minute).  
7.  
If you have a Dual (Red/White) System: Verify normal red night mode  
operation.  
(a)  
(b)  
Verify that all Flash-heads are OFF  
Verify that all Red Lights are ON and flashing properly, and the Red  
Light Controller does not indicate any alarms in the top-most Red  
Beacons.  
(c)  
Verify that LED DS36 (EXT RED READY) is lit green (See Item 10,  
Figure 3.6-1).  
8.  
If you have a Dual (Red/White) System: Perform the following steps to  
check white night backup operation.  
(a)  
Simulate a Top Red Beacon failure.  
On a Honeywell 9LCA Series Control, this may be done with the B1  
circuit breaker in the Control. Turn the B1 breaker off to activate  
the 9LCA Beacon Failure Alarm, or toggle the breaker momentarily  
to activate the 9LCA Flasher Bypass Alarm.  
Other Redlight systems have different controls, and may require  
removing Red Beacon power at the input power circuit breakers.  
(b)  
(c)  
(d)  
(e)  
(f)  
Verify that the DS36 (External Red Ready) LED is OFF.  
Verify that the DS32 (Night/Red) LED is ON  
Verify that the DS33 (Backup) LED is ON  
Verify that all the Red Lights are OFF  
Verify that all Flash-heads are flashing in sync and in Night mode  
(lowest brightness, ~1/8 second duration bursts at 40 bursts per  
minute).  
(g)  
(h)  
(i)  
Repair the simulated Red Beacon failure.  
Verify that DS36 (External Red Ready) LED is ON.  
Verify that the lighting system is still operating white strobes, and  
not red-lights.  
(j)  
Set the MODE switch to DAY. Wait for the Flash-heads to switch to  
DAY mode (about 6 seconds). Set the MODE switch back to  
NIGHT. Wait for the Flash-heads to switch to OFF mode (about 6  
seconds).  
(k)  
Verify normal red night mode operation per Step 6 above.  
PLC Health Monitoring & Reporting Sys  
3-24  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
(l)  
If you have more than one Red Beacon at the top level, repeat the  
simulated failure test for each Red Beacon.  
PLC Health Monitoring & Reporting Sys  
3-25  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
SECTION 4. PRINCIPLES OF OPERATION  
4.1  
The PLCHMR is a product that consists of hardware and software to provide health  
monitoring and remote reporting services. PLCHMR is integrated into the  
Overall Description  
StrobeGuard® System. The PLCHMR uses a single board computer; manufactured by  
a respected industrial supplier of single board computers (SBC). The SBC provides  
sufficient processor bandwidth and memory support the intended health monitoring and  
reporting tasks. The SBC has an industry standard PC/104 bus to provide a common  
interface bus for a variety of off-the-shelf daughter boards. Industry standard daughter  
boards have been selected to provide the required input/output interfaces consistent  
with the demand of customer provided monitoring systems. In addition the SBC  
provides a 10/100 Ethernet interface and an RS-485 serial port interface. The PLCHMR  
will use its RS-485 serial network connection to receive and process health status data  
from the SGC-60. The RS-485 serial network bus will be referred to as the  
StrobeGuard Control and Status Network (SCSN). SCSN will be used to send  
commands and collect status data from each SGF-60 Flash Head connected to the RS-  
485 network. The PLCHMR is collocated within the SGC-60 Master Controller  
enclosure.  
The PLCHMR reports each flash heads’ health status via discrete outputs. Each flash  
heads’ discretely reported status data will be a Flash/Fail report. PLCHMR System  
uses a uniquely configured relay output daughter board. This daughter board drives  
logic inputs provide by the customer at the remote facility. The relay output daughter  
board will provides 8 Form C relays to report the system’s status. Screw terminals on  
the relay output board will enable setting the relay’s output voltage. The normally  
closed relay contact will be used to report the fail condition.  
The PLCHMR provides an interactive character based menu -oriented Maintenance  
Mode Service (MMS). The MMS is accessed via the SBC’s Serial RS232 interface.  
The MMS is an interactive character-oriented communications session. A PC based  
client terminal service initiates a MMS session by logging onto the system as the “maint”  
user. The MMS validates the “maint” user via a password; it proceeds to establish a  
session with the client terminal service by initially presenting the Maintenance Mode  
menu.  
4.1.1.1  
Power Supply  
The PLCHMR receive 16VDC power from the Master Controllers TB8 terminal  
connector. The 16VDC power is fed to a single output DC/DC Converter which  
produces 5VDC for the SBC.  
4.1.1.2  
Communications  
The PLCHMR monitors commands from the Master Controller and Flash Head status  
reports via the RS485 serial link.  
PLC Health Monitoring & Reporting Sys  
4-1  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
SECTION 5. MAINTENANCE  
5.1  
PLCHMR Module  
The PLCHMR module requires no periodic maintenance.  
PLC Health Monitoring & Reporting Sys  
5-1  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
SECTION 6. REPLACEMENT PARTS  
Description  
Part Number  
SGC-60 Master Controller  
Master Controller Replacement MCU-------------------- 40002085-001  
SGF-60-E Flash-head  
Digital Controller, Replacement MCU-------------------- 40002084-001  
PLCHMR Module  
Module, Assembly -------------------------------------------- 40002083-001  
PLC Health Monitoring & Reporting Sys  
6-1  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
SECTION 7. APPENDIX A – EXAMPLES  
7.1  
Light Configuration Examples  
The HMS Light Configuration Menu provides the flexibility and configurability to address  
most field installations. This section provides specific examples that demonstrate some  
possible configuration values that are the results of choices made in the Light  
Configuration Menu. The PLCHMR system has eight (8) relays that can report the  
status of up to 24 Flash Heads. The Light Configuration menu enables the user to map  
the status reporting from any combination of Flash Heads to any one or all 8 of the  
relays. In section 3.4 it was declared that the relay’s state is controlled by the software  
configured Tier Reporting Mechanism (TRM). Section 3.4 also indicated the TRM has  
two states FLASH/OK and FAIL/FAULT. Software configuration of the TRM is  
performed through the HMS Light Configuration Menu. Each TRM can be assigned  
from zero to 24 Flash Heads. A Flash Head is assigned to a specific TRM via a  
numeric entry in its corresponding Tier_Lvl column in the Light Configuration Menu. For  
a TRM to activate its relay the status reported of all Flash Heads assigned to that tier  
must be FLASH/OK. The TRM will deactivate its relay if any Flash Head assigned to it  
reports a FAIL/FAULT status.  
For instance consider the following example on how a system with 24 Flash Heads  
could be configured:  
In the following example consider a system with nine Flash Heads arrange on 3 physical  
tiers as shown in Figure 7.1-1.  
A typical configuration could use seven Tier Reporting Mechanisms TRMs. Each of the  
top six Flash Heads could be assigned to its own individual TRM. The three lowest  
Flash Heads would be assigned to one of the remaining TRMs. The Flash/Fail status  
for the top six Flash Head would be collected by their assigned TRM and then reported  
by a relay whose number identifies the tier or (TRM) number. This would result in the  
top six Flash Heads having individualized status reports and the bottom three flash  
Heads having a collective status report. The Light Configuration Menu setting would  
appear as shown in Figure 7.1-2. An alternative view is presented in Figure 7.1-3 which  
shows the individual groups Flash Head groups reporting status to their assigned TRM  
which is connected to the reporting relay.  
PLC Health Monitoring & Reporting Sys  
7-1  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Tier 1  
3
2
1
Flash Head Installation  
with 9 Flash Heads, installed on  
three tiers (levels). Each tier has  
three Flash Heads. Flash Heads  
numbers correspond to the unique  
ID or address set on the Flash  
Head’s digital logic board switch  
#3.  
Tier 2  
6
5
4
9
7
Tier 3  
8
Flash  
Head #  
Figure 7.1-1 Tower Example with 9 Flash Heads on Three Physical Tiers  
PLC Health Monitoring & Reporting Sys  
7-2  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
HMS Light Configuration Menu  
Lamp_ID Tier_Lvl Height Facing_Dir Priority  
1)  
2)  
3)  
4)  
5)  
6)  
7)  
8)  
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
7
7
151  
152  
153  
133  
133  
133  
113  
113  
113  
NW  
SE  
SW  
NW  
SE  
SW  
NW  
SE  
1
1
1
2
2
2
5
5
5
9)  
SW  
10)  
11)  
12)  
13)  
14)  
15)  
16)  
17)  
18)  
19)  
20)  
21)  
22)  
23)  
24)  
25) Exit  
maint>  
Figure 7.1-2 Light Configuration Menus Settings for 9 Lights and 7 Relay Outputs  
PLC Health Monitoring & Reporting Sys  
7-3  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
Relay #1  
TRM  
#1  
Relay  
State  
FLASH  
HEAD 1  
Flash/Fail Status  
Relay #2  
Relay #3  
TRM  
#2  
Relay  
State  
FLASH  
HEAD 2  
Flash/Fail Status  
Flash/Fail Status  
TRM  
#3  
Relay  
State  
FLASH  
HEAD 3  
Relay #4  
TRM  
#4  
Relay  
State  
FLASH  
HEAD 4  
Flash/Fail Status  
Relay #5  
Relay #6  
TRM  
#5  
Relay  
State  
FLASH  
HEAD 5  
Flash/Fail Status  
Flash/Fail Status  
TRM  
#6  
Relay  
State  
FLASH  
HEAD 6  
FLASH  
HEAD 7  
Flash/Fail Status  
Relay #7  
FLASH  
HEAD 8  
&
7
8
9
Relay  
State  
FLASH  
HEAD 9  
TRM #7  
Figure 7.1-3 System Configuration with 9 Flash Heads using 7 relays  
PLC Health Monitoring & Reporting Sys  
7-4  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
A typical configuration would be to create eight tiers (or groups). Each tier would be a  
collection of three Flash Heads. Each tier’s status would be collect by its assigned TRM  
and then reported by the relay whose number identifies the tier or (TRM) number. The  
Light Configuration Menu setting would appear as shown in Figure 7.1-4. An alternative  
view is presented in Figure 7.1-5 which shows the individual groups Flash Head groups  
reporting status to their assigned TRM which is connected to the reporting relay.  
HMS Light Configuration Menu  
Lamp_ID Tier_Lvl Height Facing_Dir Priority  
1)  
2)  
3)  
4)  
5)  
6)  
7)  
8)  
9)  
1
2
3
4
5
6
7
8
9
1
1
1
2
2
2
3
3
3
1510  
1520  
1530  
1330  
1330  
1330  
1130  
1130  
1130  
1030  
1030  
1030  
930  
930  
930  
830  
830  
830  
530  
530  
530  
NW  
SE  
SW  
Nw  
SE  
SW  
NW  
SE  
SW  
NW  
SE  
SW  
NW  
SE  
SW  
NW  
SE  
SW  
NW  
SE  
SW  
NW  
SE  
1
1
1
2
2
2
2
2
2
3
3
3
3
3
3
4
4
4
5
5
5
5
5
5
10) 10  
11) 11  
12) 12  
13) 13  
14) 14  
15) 15  
16) 16  
17) 17  
18) 18  
19) 19  
20) 20  
21) 21  
22) 22  
23) 23  
24) 24  
25) Exit  
maint>  
4
4
4
5
5
5
6
6
6
7
7
7
8
8
8
230  
230  
230  
SW  
Figure 7.1-4 Light Configuration Menus Settings for 24 Light and 8 Relay Outputs  
PLC Health Monitoring & Reporting Sys  
7-5  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airport Systems  
FLASH  
HEAD 1  
FLASH  
HEAD  
13  
Flash/Fail Status  
Flash/Fail Status  
Relay #1  
FLASH  
HEAD  
14  
FLASH  
HEAD 2  
Relay #5  
&
1
13  
14  
15  
&
Relay  
State  
2
3
0
Relay  
State  
FLASH  
HEAD  
15  
FLASH  
HEAD 3  
TRM #1  
TRM #5  
FLASH  
HEAD  
16  
FLASH  
HEAD 4  
Flash/Fail Status  
Flash/Fail Status  
FLASH  
HEAD  
17  
Relay #2  
Relay #6  
FLASH  
HEAD 5  
&
&
4
5
6
16  
17  
18  
Relay  
State  
Relay  
State  
FLASH  
HEAD  
18  
FLASH  
HEAD 6  
TRM #2  
TRM #6  
FLASH  
HEAD  
19  
FLASH  
HEAD7  
Flash/Fail Status  
Flash/Fail Status  
FLASH  
HEAD  
20  
Relay #3  
Relay #7  
FLASH  
HEAD 8  
&
&
7
8
9
19  
20  
21  
Relay  
State  
Relay  
State  
0
FLASH  
HEAD  
21  
FLASH  
HEAD 9  
TRM #3  
TRM #7  
FLASH  
HEAD  
10  
FLASH  
HEAD  
22  
Flash/Fail Status  
Flash/Fail Status  
FLASH  
HEAD  
11  
FLASH  
HEAD  
23  
Relay #4  
Relay #8  
&
&
10  
11  
12  
22  
23  
24  
Relay  
State  
Relay  
State  
0
0
FLASH  
HEAD  
12  
FLASH  
HEAD  
24  
TRM #4  
TRM #8  
Figure 7.1-5 System Configuration with 24 Flash Heads using 8 relays  
PLC Health Monitoring & Reporting Sys  
7-6  
Manual EPM40002083-001 Rev -  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Water Pump 3A0019J User Manual
Grizzly Paint Sprayer H8115 User Manual
Haier Saw HRF 220 User Manual
Heat Glo LifeStyle Electric Heater SUPREME N I30AU User Manual
Honeywell Air Cleaner F111 User Manual
Hubbell Switch LX3000 User Manual
Hunter Fan Fan 23347 User Manual
Hunter Fan Outdoor Ceiling Fan 20731 User Manual
Husqvarna Lawn Mower 435e User Manual
IBM Speaker 92P1956 User Manual