Model:
Everest
Installers Guide
Underwriters
Laboratories Listed
READ THIS MANUAL BEFORE INSTALLING OR
OPERATING THIS APPLIANCE. THIS INSTALLERS
GUIDE MUST BE LEFT WITH APPLIANCE FOR
FUTURE REFERENCE.
WARNING: IMPROPER INSTALLA-
TION, ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN
CAUSE INJURY OR PROPERTY DAM-
AGE. REFER TO THIS MANUAL. FOR
ASSISTANCE OR ADDITIONAL INFOR-
MATION CONSULT A QUALIFIED IN-
STALLER, SERVICE AGENCY, OR THE
GAS SUPPLIER.
WARNING: IF THE INFORMATION
IN THESE INSTRUCTIONS IS NOT
FOLLOWED EXACTLY, A FIRE OR
EXPLOSION MAY RESULT CAUS-
ING PROPERTY DAMAGE, PER-
SONAL INJURY, OR DEATH.
1. This appliance may be installed in an af-
termarket, permanently located, manufac-
tured (mobile) home, where not prohibited
by local codes.
- Do not store or use gasoline or other flam-
mable vapors and liquids in the vicinity of this
or any other appliance.
-
What to do if you smell gas
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
2. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases, unless a certified kit is used.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the fire department.
In the Commonwealth of Massachusetts:
• installation must be performed by a licensed
plumber or gas fitter;
- Installation and service must be performed by a
qualified installer, service agency, or the gas
supplier.
• a CO detector shall be installed in the room
where the appliance is installed.
Printed in U.S.A. Copyright 2006
Please contact your Heat & Glo dealer with any
questions or concerns. For the number of your nearest
Heat & Glo dealer, please call 1-888-427-3973.
Heat & Glo, a brand of Hearth & Home Technologies Inc.
20802 Kensington Boulevard, Lakeville, MN 55044
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471,
5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195,
6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426,
6774802, 6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia)
780250, 780403, 1418504 or other U.S. and foreign patents pending.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Safety and Warning Information. ....................................2
Service Parts Lists. .........................................................4
Î
Section 1: Approvals and Codes. ...................................6
Appliance Certification........................................................6
Installation Codes...............................................................6
HighAltitude Installations ....................................................6
Section 2: Getting Started ..............................................7
Introducing the Heat & Glo Gas Fireplaces ........................7
Pre-installation Preparation ................................................7
Section 3: Installing the Fireplace. ................................9
Step 1 Locating the Fireplace .........................................9
Step 2 Framing the Fireplace .........................................9
Step 3 Installing the Vent System .................................10
A. Vent System Approvals ................................10
B. Installing Vent Components .........................15
C. Vent Termination ..........................................18
Step 4 Positioning, Leveling, and
Securing the Fireplace ......................................21
Step 5 The Gas Control Systems.................................21
Step 6 The Gas Supply Line .........................................22
Step 7 Gas Pressure Requirements ............................22
Step 8 Wiring the Fireplace ..........................................23
Step 9 Finishing ............................................................24
Step 10 Installing Trim, Logs, and Ember Material .........25
Installing the Trim ..............................................25
Positioning the Logs ..........................................25
Placing the Ember Material ...............................25
Step 11 Before Lighting the Fireplace.............................26
Step 12 Lighting the Fireplace ........................................26
After the Installation ..........................................................26
Battery Backup ..................................................................26
Section 4: Maintaining and Servicing
Your Fireplace. ............................................27
Î = Contains updated information.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
3
Download from Www.Somanuals.com. All Manuals Search And Download.
EVEREST
Beginning Manufacturing Date: 8-00
Ending Manufacturing Date: ______
Service Parts
(NG, LP) Exploded Parts Diagram
Î
2
19
5
6
9
1
18
21
10
8
22
23
7
11 Log Set Assembly
3
20
4
13
14
16
15
Part number list on following page.
17
12Back Log (not shown)
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
4
EVEREST
Service Parts List
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When ordering,
supply serial and model numbers to ensure correct service parts.
ITEM
IPI IGNITION
SERIAL #
PART NUMBER
PRE 5000
060-801
1
Log Burner Orifice NG (#53A)
Log Burner Orifice LP (#64A)
Main Burner Orifice NG (#45A)
Main Burner Orifice LP (#56)
POST 5000
PRE 5000
POST 5000
PRE 5000
POST 5000
PRE 5000
POST 5000
582-853
750-800
582-864
062-801
582-845
045-802
582-856
1
2
2
3
4
5
6
7
8
9
Glass Door Assembly
Standard Door
Burner NG, LP
GLA-Everest
DF-Everest
750-175A
Log Grate
750-360A
Refractory, Base
Refractory, Right Side
Refractory, Left Side
SRV750-733
SRV750-731
SRV750-730
SRV750-732
LOGS-Everest
SRV750-703
SRV750-701A
SRV750-702A
SRV750-705
SRV750-706
SRV750-704
10 Refractory, Back
11 Log Set Assembly
12 Log 1 Back Log
13 Log 2 Left Burner Log
14 Log 3 Right Burner Log
15 Log 4 Right Inside Log
16 Log 5 Small Log
17 Log 6 Left Inside Log
PRE 5000
POST 5000
060-522
750-500
Valve NG
PRE 5000
POST 5000
060-523
750-501
Valve LP
18 Junction Box
4021-013
PRE 5000
POST 5000
PRE 5000
POST 5000
PRE 7-1-03
POST 7-1-03
485-510A
593-512A
485-511A
593-513A
750-130
19 Pilot Assembly NG (must order whole assembly)
19 Pilot Assembly LP (must order whole assembly)
20 Surround
750-132
21 Flex Ball Valve Assembly
22 Flame Control Knob
23 ON/OFF Rocker Switch
Module
302-320A
571-531
060-511
593-592
593-590A
593-593A
Wire Assembly
3V Adaptor Plug
Battery Pack
Trim Door Mesh
ON/OFF Rocker Switch
Glass Latch Assembly
Mineral Wool Embers
Lava Rock Bag
593-594A
MESH-Everest
750-556A
386-122A
050-721
705-420
ACCESSORIES
Remote Control Kit
Remote Control Kit
Wall Switch Kit, Off White
Wall Switch Kit, White
RC-SMART-HNG
SMART-STAT-HNG
WSK-21
WSK-21-W
PRE 5000
POST 5000
PRE 5000
POST 5000
LPK-Everest
LPKP-Everest
NGK-Everest
NGKP-Everest
Conversion Kit LP SPI
Conversion Kit NG SPI
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Approvals and Codes
1
High Altitude Installations
Appliance Certification
U.L. Listed gas appliances are tested and approved with-
out requiring changes for elevations from 0 to 2,000 feet in
the U. S. A. and in Canada.
The Heat & Glo fireplace model discussed in this Installers
Guide have been tested to certification standards and listed
by the applicable laboratories.
When installing this appliance at an elevation above 2,000
feet, it may be necessary to decrease the input rating by
changing the existing burner orifice to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above a
2000 foot elevation in the U.S.A. or 10% for elevations
between 2000 and 4500 feet in Canada. If the heating value
of the gas has been reduced, these rules do not apply. To
identify the proper orifice size, check with the local gas
utility.
Certification
MODEL: EVEREST
LABORATORY: Underwriters Laboratories
TYPE: Direct Vent Gas Fireplace Heater
STANDARD: ANSIZ21.88-1998/CSA2.33-M98•UL307B
Installation Codes
If installing this appliance at an elevation above 4,500 feet
(in Canada), check with local authorities.
The fireplace installation must conform to local codes. Before
installing the fireplace, consult the local building code
agency to ensure that you are in compliance with all
applicable codes, including permits and inspections.
In the absence of local codes, the fireplace installation must
conform to the National Fuel Gas Code ANSI Z223.1 (in
the United States) or the CAN/CGA-B149 Installation Codes
(in Canada). The appliance must be electrically grounded
in accordance with local codes or, in the absence of local
codes with the National Electric Code ANSI/NFPA No. 70
(in the United States), or to the CSAC22.1Canadian Electric
Code (in Canada).
These models may be installed in a bedroom or bed-sitting
room in the U.S.A. and Canada.
Heat & Glo Quality Systems
registered by SGS ICS
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Getting Started
2
Introducing the Heat & Glo Gas Fireplaces
Warranty
Heat & Glo direct vent gas fireplaces are designed to oper-
ate with all combustion air siphoned from outside of the
building and all exhaust gases expelled to the outside.
The Heat & Glo Warranty will be voided by, and Heat & Glo
disclaims any responsibility for, the following actions:
• Installation of any damaged fireplace or vent system com-
ponent.
The information contained in this Installers Guide, unless
noted otherwise, applies to all models and gas control
systems. Gas fireplace diagrams, including the dimensions,
are shown in this section.
• Modification of the fireplace or direct vent system.
• Installation other than as instructed by Heat & Glo.
• Improper positioning of the gas logs or the glass door.
Pre-install Preparation
This gas fireplace and its components are tested and safe
when installed in accordance with this Installers Guide.
Report to your dealer any parts damaged in shipment,
particularly the condition of the glass. Do not install any
unit with damaged, incomplete, or substitute parts.
• Installation and/or use of any component part not manu-
factured and approved by Heat & Glo, not withstanding
any independent testing laboratory or other party approval
of such component part or accessory.
ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE
HAZARD.
The vent system components and trim doors are shipped
in separate packages. The gas logs may be packaged
separately and must be field installed.
Read all of the instructions before starting the
installation. Follow these instructions carefully during
the installation to ensure maximum safety and benefit.
Failure to follow these instructions will void the
owner’s warranty and may present a fire hazard.
When planning a fireplace installation, it’s necessary to
determine:
• Where the unit is to be installed.
• The vent system configuration to be used.
• Gas supply piping.
• Electrical wiring.
• Framing and finishing details.
• Whether optional accessories devices such as a fan,
wall switch, or remote control are desired.
If the fireplace is to be installed on carpeting or tile, or on
any combustible material other than wood flooring, the
fireplace should be installed on a metal or wood panel that
extends the full width and depth of the fireplace.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
7
8-15/16
(227mm)
8
(203mm)
20-7/8
(531mm)
Ø8
(203.1)
54-1/2
(1384mm)
49-7/8
(1266mm)
47-7/16
(1205mm)
45-7/16
(1154mm)
36-1/8
(918mm)
ELECTRICAL
ACCESS
2-18
(55mm)
4-11/16
(118mm)
2-5/16
(59mm)
23-3/8
(593mm)
GAS LINE
ACCESS
4-11/16
(119mm)
5-12
(139mm)
28-13/16
(732mm)
34-1/8
(866mm)
TOP VENT COLLARS
TOP STANDOFFS
TRIM DOOR
RATING PLATE
AND LABELS
GAS LINE
ACCESS
GAS CONTROLS
ELECTRICAL
ACCESS
Figure 1. Diagram of the Everest
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
8
Minimum Clearances
from the Vent Pipe to Combustible Materials
Inches
mm
Vertical Sections. ............. 1 ................ 25
Installing the Fireplace
Horizontal Sections
3
Top ..................................... 3 ................ 75
Bottom ............................... 1 ................ 25
Sides ................................. 1 ................ 25
Step 1.
Locating the Fireplace
At Wall Firestops
The diagram below shows space and clearance require-
ments for locating a fireplace within a room.
Top ..................................... 3 ................ 76
Bottom ............................... 1 ................ 25
Sides ................................. 1 ................ 25
4” (102mm)
For minimum clearances, see the direct vent termination
clearance diagrams on pages 20 and 21 in this manual.
B
The distance from the unit to combustible construction
is to be measured from the unit outer wrap surface to
the combustible construction, NOT from the screw
heads that secure the unit together.
A
Step 2. Framing the Fireplace
Fireplace framing can be built before or after the fireplace is
set in place. Framing should be positioned to accommo-
date wall coverings and fireplace facing material. The dia-
gram below shows framing reference dimensions.
E
D
CAUTION: MEASURE FIREPLACE DIMENSIONS, AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS, BEFORE FRAMING.
C
1/2” (13mm)
Shows center of
10” x 12” vent framing
holes for venting.
A
B
C
D
E
35 1/2”
21 3/4”
30 1/2”
43 1/4”
61 3/16”
(902mm) (552mm) (775mm) (1099mm) (1554mm)
Figure 2. Fireplace Dimensions, Locations,
and Space Requirements
Clearance Requirements
The top, back, and sides of the fireplace are defined by
stand-offs. The minimum clearance to a perpendicular wall
extending past the face of the fireplace is 4 inches (102mm).
The back of the fireplace may be recessed 23 (584mm)
inches (546mm) into combustible construction.
D
Minimum Clearances
from the Fireplace to Combustible Materials
Inches
mm
Framing should be
constructed of 2 X 4
lumber or heavier.
Glass Front........................ 36 .............. 914
Floor
Rear
Sides
Top
............................ 0 ................. 0
...........................1/2 ............... 13
...........................1/2 ............... 13
......................... 4 1/2 ............ 114
C
B
A. ..... 35 1/8” (892mm)
B. ..... 50 1/2” (1283mm)
C. ..... 21 3/8” (542mm)
D. ..... 55 1/2” (1372mm)
Ceiling* ........................... 31 .............. 787
* The clearance to the ceiling is measured from the
top of the unit, excluding the stand-offs and collar.
See Figure 24 for further details.
(Center of 12 x 10)
A
Figure 3. Framing Dimensions
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
9
Step 3. Installing the Vent System
A. Vent System Approvals
4
6
These models are approved to use DVP-series direct
vent pipe components and terminations.Approved vent
system components are labeled for identification. This
pipe is tested and listed as an approved component of
the fireplace. The pipe is tested to be run inside an
enclosed wall. There is no requirement for inspection
openings at each joint within the wall. There is no re-
quired pitch for horizontal vent runs. NO OTHER VENT-
ING SYSTEMS OR COMPONENTS MAYBE USED.
12
DVP4
DVP6
DVP12
14-1/4
12-3/16
MAX.
2
MIN.
Detailed installation instructions are included with
each vent termination kit and should be used in
conjunction with this Installers Guide. The draw-
ing below shows vent system components and ter-
minations.
24
36
DVP12A
48
The flame and ember appearance may vary based
on the type of fuel burned and the venting configura-
tion used.
9-7/8
DVP24
45.0O
10-1/4
DVP45
Identifying Vent Components
DVP36
The vent systems installed on this gas fireplace may
include one, two, or three 90°elbow assemblies. The
relationships of vertical rise to horizontal run in vent
configurations using 90° elbows MUST BE strictly
adhered to. The rise to run relationships are shown
in the venting drawings and tables. Refer to the dia-
grams on the next several pages.
11-1/4
7-1/4
1-1/4 TYP
DVP48
8-9/16
1/2 TYP
12-9/16
NOTE: PIPES OVERLAP 1-1/4
INCHES (31.8mm)ATEACH JOINT.
DVP90ST
NOTE: Two 45° elbows may be used in place of one
90° elbow. rise to run ratios in the vent system must be
followed if 45° elbows are used.
Figure 4. DVP-Series Direct Vent Component Specifications
(5-inch inner pipe / 8-inch outer pipe)
Vent system components
VERTICAL
TERMINATION
STORM COLLAR
ROOF FLASHING
Vent system
termination kits
HORIZONTAL
TERMINATION
PIPE LENGTH
DVP-TVHW
DVP-TRAP
WALL FIRESTOP
CEILING
FIRESTOP
90 DEGREE
ELBOW
DVP-TV
Figure 5. Vent Components and Terminations
To Unit
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
10
CAP
STRAIGHT UP
VERTICAL VENTING
V (FT.)
40' MAX. (12.4 M)
Figure 6. Straight Up Vertical Venting
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
11
VENTING WITH ONE (1) 90° ELBOW
H
V
V
H
1' MIN. (305mm)
2' MIN. (610mm)
4' MIN. (1.22m)
10' MAX. (3.1m)
15' MAX. (4.65m)
20' MAX. (6.2m)
V+H= 40’ MAX. (12.4MM) H = 20' MAX. (6.2m)
NOTE: If a 90o elbow is first attached to the unit, the
maximum horizontal run is 3-feet (914mm).
H
V
NOTE: For corner installations:A6-inch (152mm) section of straight
pipe may need to be attached to the fireplace before a 90o elbow,
to allow the vent pipe to clear the top standoffs.
Figure 7. Venting with One 90° Elbow
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
12
VENTING WITH TWO (2) 90° ELBOWS
H
V
1
H
V
1
V
V
H + H1
H
1' MIN. (305mm)
2' MIN. (610mm)
4' MIN. (1.22m)
10' MAX. (3.1m)
15' MAX. (4.65m)
20' MAX. (6.2m)
V+H+H1= 40' MAX.(12.4m) H+H1 = 20´ MAX. (6.2m)
V+V1+H= 40' MAX.(12.4m)
Figure 8. Venting with Two 90° Elbows
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
13
VENTING WITH THREE (3) 90° ELBOWS
H
1
V
1
V
H
V + V1
H + H1
1' MIN. (305mm)
2' MIN. (610mm)
4' MIN. (1.22m)
10' MAX. (3.1m)
15' MAX. (4.65m)
20' MAX. (6.2m)
NOTE: H + H = 20' MAX. (6.2m)
V + V11+ H + H1= 40' MAX. (12.4m)
V
1
H
1
V
H
Figure 9.
Venting with three 90° elbows
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
14
B. Installing Vent Components
1. Attach the First Vent Component to the
Starting Collars
If your vertical vent component is over 10 feet, you may
want to install the included vertical baffle to improve flame
appearance. Vertical baffle is located in the bag containing
the instruction manual. Center the vertical baffle on the five
inch flue being used, and with self tapping screws secure
the baffle to the inside of the firebox (see Figure 10).
To attach the first vent component to the starting collars
of the fireplace:
•
Make sure that the fireplace gasket supplied with the
fireplace seals between the first component and the out-
er fireplace wrap.
With vent runs of 30 feet or more without elbows, an
additional baffle (SRV750-152) is to be used with the
supplied baffle. This is a service part and is to be purchased
separately.
•
Refer to Cinch Pipe and Termination Cap installation in-
structions.
2. Assembling Vent Sections
Refer to Cinch Pipe and Termination Cap installation in-
structions.
VERTICAL
BAFFLE
5” EXHAUST
PIPE
WARNING: ENSURE THAT THE FIBERGLASS
GASKET SUPPLIED WITH THE FIREPLACE
!
SEALS BETWEEN THE FIRST VENT COMPONENT
AND THE OUTER FIREPLACE WRAP.
If the installation is for a termination cap attached directly
to the fireplace, skip to the sections, Install Firestops and
Vent Termination.
Figure 10. Vertical Baffle
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
15
• 90° elbows may be installed and rotated to any point around
the preceding component’s vertical axis. For elbows that
are changing the vent direction, one screw minimum
should be put in the outer flue at the joint to prevent the
elbow from rotating.
WARNING: INSTALLATION OF THIS FIRE-
PLACE REQUIRES THE USE OF HEAT
!
SHIELD 570-290 ABOVE THE FIRST 900 ELBOW IN
THE VENTING SYSTEM.
To Install the Heat Shield:
COMBUSTIBLE
SURFACE
1. Determine if the heat shield is required. Do so by mea-
suring the vertical distance between the top horizontal
surface of the elbow to any combustible surface above. If
the distance is more than 4 inches, the heat shield is
NOT required. If it is 4 inches or less, the heat shield IS
REQUIRED. Install per the following steps. See Figure 11.
3“ MIN.
(76MM)
HEAT
SHIELD
2. Fasten the shield in place using the four pilot holes pro-
vided in the part. The shield should be oriented such that
the 13 1/8 inch dimension (longest dimension) is run-
ning in the same direction the elbow is pointing. The
shield should be centered directly above the elbow, and
positioned so that it creates a 1/2 inch airspace between
the shield and the combustible surface. See Figure 12.
Refer to Cinch Pipe and Termination Cap installation in-
structions.
Figure 11
• Continue adding vent components, locking each succeed-
ing component into place.
3. Install Support Brackets
• Ensure that each succeeding vent component is secure-
ly fitted and locked into the preceding component in the
vent system.
Refer to Cinch Pipe and Termination Cap installation in-
structions.
CORRECT
INCORRECT
Figure 12
4. Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.
NOTE: Model DVP-TRAP does not need an exterior
firestop on an exterior combustible wall.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
16
To install firestops for horizontal runs that pass through
either interior or exterior walls:
10" (254 mm)
10" (254mm)
•
Cut a 12-inch by 10-inch (305mm X 254mm) hole through
the wall. The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.
•
•
Position the firestops on both sides of the hole previ-
ously cut and secure the firestops with nails or screws.
CHIMNEY
HOLE
The pipe opening of the firestops MUST be placed to-
wards the bottom of the fireplace.
EXISTING CEILING
JOISTS
NEW
FRAMING
MEMBERS
NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.
CEILING
Figure 14. 10" x 10" Hole & New Framing Members
If the area above the ceiling is NOT an attic, position and
secure the ceiling firestop on the ceiling side of the previously
cut and framed hole.
10"
INTERIOR
WALL SHIELD
This shows a ceiling installation.
12"
JOIST
Figure 13. 10" x 12" Hole and Vent Pipe
CEILING
NAILS (4 REQUIRED)
CEILING FIRESTOP
For Vertical Runs - One ceiling firestop is REQUIRED
at the hole in each ceiling through which the vent passes.
Figure 15. Ceiling Firestop (Ceiling Side)
To install firestops for vertical runs that pass through ceilings:
If the area above the ceiling IS an attic, position and secure
the firestop on top of the previously framed hole.
• Position a plumb bob directly over the center of the verti-
cal vent component.
This shows an attic installation. Keep insulation away from
the vent pipe at least 1 inch (25mm).
• Mark the ceiling to establish the centerpoint of the vent.
• Drill a hole or drive a nail through this centerpoint.
NAILS (4 REQUIRED)
• Check the floor above for any obstructions, such as wir-
ing or plumbing runs.
• Reposition the fireplace and vent system, if necessary,
to accommodate the ceiling joists and/or obstructions.
RAFTER
• Cut a 10-inch x 10-inch (254mm x 254mm) hole through
the ceiling, using the centerpoint previously marked.
• Frame the hole with framing lumber the same size as the
ceiling joists.
CEILING
CEILING FIRESTOP
NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.
Figure 16. Attic Firestop
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
17
C. Vent Termination
Refer to Cinch Pipe and Termination Cap installation in-
structions.
WARNING: THE TERMINATION CAP MUST BE
POSITIONED SO THAT THEARROW IS POINT-
ING UP.
!
WARNING: VENTING TERMINALS SHALL
NOT BE RECESSED INTO AWALL OR SID-
!
ING. VENT TERMINATION CLEARANCES MUST
BE FOLLOWED TO AVOID FIRE DANGER. SEE
VENT TERMINATION MINIMUM CLEARANCES DI-
AGRAM ON FOLLOWING PAGE.
7 1/4"
(184mm)
Figure 17. Trapezoid Termination Cap
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
18
M
N
P
G
R
v
A
H
D
Q
(See Note 2)
v
V
B
L
U.S.
(3 FT)
B
T
v
v
v
B
v
S
S
Electrical
Service
V
V
F
v
M
I
D*
V
v
X
A
J or K
X
= VENT TERMINAL
=AIR SUPPLY INLET
= AREA WHERE TERMINAL IS NOT PERMITTED
V
K
= 3 ft. (U.S.A.)
A = 12 inches ................ clearances above grade, veran-
6 ft. (Canada) ......... clearance to a mechanical
(powered) air supply inlet
(See Note 1)
da, porch, deck or balcony
B = 12 inches ................ clearances to window or door
that may be opened, or to per-
manently closed window.
(Glass)
L** = 7 ft. ......................... clearance above paved side-
(See Note 1)
walk or a paved driveway lo-
cated on public property
M*** = 18 inches .............. clearance under veranda, porch,
deck, balcony or overhang
D* = 18 inches ................ vertical clearance to unventilat-
ed soffit or to ventilated soffit lo-
42 inches .............. vinyl
cated above the terminal
Alcove Applications
*30 inches ................ for vinyl clad soffits and below
electrical service
N
= 6 inches ................ non-vinyl sidewalls
12 inches .............. vinyl sidewalls
F
=
9 inches ................. clearance to outside corner
P
= 8 ft.
G = 6 inches .................. clearance to inside corner
______________________________Q___M_I_N___________________________________
_____1___c__a_p__________________3___f_e_e__t_________________2__x__Q____A_C_T_U_A_L____
______2__c__a_p__s________________6___f_e_e__t_________________1__x__Q____A_C_T_U_A_L____
______3__c__a_p__s_________________9__f_e_e__t_______________2_/_3__x___Q___A_C_T_U_A__L___
4 caps 12 feet 1/2 x Q ACTUAL
RMAX
H = 3 ft. (Canada) .......... not to be installed above a gas
meter/regulator assembly within
3 feet (90cm) horizontally from the
center-line of the regulator
I
=
=
3 ft. (U.S.A.)
6 ft. (Canada) .......... clearance to gas service regu-
lator vent outlet
9 inches (U.S.A.)
QMIN = # termination caps x 3
RMAX = (2 / # termination caps) x QACTUAL
J
12 inches(Canada) clearance to non-mechanical air
supply inlet to building or the
combustion air inlet to any other
appliance
S = 6 inches ................. clearance from sides of
electrical service
(See Note 5)
T
= 12 inches ................ clearance above electrical
service
(See Note 5)
** a vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings
and serves both dwellings.
NOTE 3: Local codes or regulations may require different
clearances.
NOTE 4: Termination caps may be hot. Consider their proximity to
doors or other traffic areas.
*** only permitted if veranda, porch, deck or balcony is fully open on
a minimum of 2 sides beneath the floor, or meets Note 2.
NOTE 5: Location of the vent termination must not interfere with
NOTE 1: On private property where termination is less than 7 feet
above a sidewalk, driveway, deck, porch, veranda or balcony, use of
a listed cap shield is suggested. (See vents components page)
access to the electrical service.
WARNING: In the U.S: Vent system termination is NOT permitted
in screened porches. You must follow side wall, overhang and
ground clearances as stated in the instructions.
NOTE 2: Termination in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum
between termination caps. 2. All mechanical air intakes within 10 feet
of a termination cap must be a minimum of 3 feet below the termination
cap. 3. All gravity air intakes within 3 feet of a termination cap must be
a minimum of 1 foot below the termination cap.
In Canada: Vent system termination is NOT permitted in screened
porches. Vent system termination is permitted in porch areas
with two or more sides open. You must follow all side walls,
overhang and ground clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper perfor-
mance of the appliance when the venting system does not meet
these requirements.
Î
Figure 18. Vent Termination Minimum Clearances
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
19
To seal the roof hole, and to divert rain and snow from the
vent system:
For Vertical Terminations - To locate the vent and
install the vent sections:
• Locate and mark the vent centerpoint on the underside
of the roof, and drive a nail through the centerpoint.
• Attach a flashing to the roof using nails, and use a non-
hardening mastic around the edges of the flashing base
where it meets the roof.
• Make the outline of the roof hole around the centerpoint
nail.
• Attach a storm collar over the flashing joint to form a
water-tight seal. Place non-hardening mastic around the
joint, between the storm collar and the vertical pipe.
• The size of the roof hole framing dimensions depend on the
pitch of the roof. There MUST BE a 1-inch (25.4mm) clear-
ance from the vertical vent pipe to combustible materials.
• Slide the termination cap over the end of the vent pipe
and snap into place.
• Mark the roof hole accordingly.
• Cover the opening of the installed vent pipes.
• Cut and frame the roof hole.
HORIZONTAL
OVERHANG
• Use framing lumber the same size as the roof rafters
and install the frame securely. Flashing anchored to the
frame must withstand heavy winds.
2 FT.
MIN.
20 INCH MIN.
VERTICAL
WALL
LOWEST
DISCHARGE
OPENING
• Continue to install concentric vent sections up through
the roof hole (for inside vent installations) or up past the
roof line until you reach the appropriate distance above
the roof (for outside terminations).
TERMINATION
CAP
X
12
ROOF PITCH
IS X/ 12
WARNING: MAJOR U.S. BUILDING CODES
!
SPECIFY MINIMUM CHIMNEY AND/OR
VENT HEIGHTABOVE THE ROOF TOP. THESE MIN-
IMUM HEIGHTS ARE NECESSARY IN THE INTER-
EST OF SAFETY. SEE THE FOLLOWING DIAGRAM
FOR MINIMUM HEIGHTS, PROVIDED THE TERMI-
NATION CAP ISAT LEAST TWENTY INCHES FROM
A VERTICAL WALL AND 2-FEET BELOW A HORI-
ZONTAL OVERHANG.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Roof Pitch
H (min.) ft.
flat to 6/12
6/12 to 7/12
1.0
1.25
1.5
2.0
2.5
3.25
4.0
5.0
6.0
7.0
7.5
8.0
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
NOTE: This also pertains to vertical vent systems in-
stalled on the outside of the building.
Figure 19. Minimum Height from Roof to
Lowest Discharge Opening
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
20
Step 5. The Gas Control Systems
Step 4. Positioning, Leveling, and
Securing the Fireplace
WARNING: THIS UNIT IS NOT FOR USE WITH
!
The diagram below shows how to properly position, level,
and secure the fireplace.
SOLID FUEL.
Intermittent Pilot Ignition (IPI) System
The gas control system used with this model is Intermittent
Pilot Ignition (IPI). This system includes a 3V control valve,
electronic module, and intermittent pilot.
WARNING: CONTINUOUS 110-120 VAC SER-
VICE MUST BE WIRED TO THE FIREPLACE
!
JUNCTION BOX.
WARNING: DIRECT VENT PROPANE MODELS
WITH IPI CONTROL SYSTEMS CANNOT BE
!
USED IN CANADA.
NAILING TABS
(BOTH SIDES)
Figure 20. Proper Positioning, Leveling, and
Securing of a Fireplace
1. Place the fireplace into position.
2. Level the fireplace from side to side and from front to
back.
Figure 21. Intermittent Pilot Ignition
3. Shim the fireplace with non-combustible material, such
as sheet metal, as necessary.
4. Secure the fireplace to the framing by nailing or screwing.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
21
Step 6. The Gas Supply Line
USE A WRENCH
ON SHUT-OFF
VALVE WHEN
TIGHTENING
GAS LINE
NOTE: Have the gas supply line installed in accordance
with local building codes by a qualified installer
approved and/or licensed as required by the locality.
(In the Commonwealth of Massachusetts installation
must be performed by a licensed plumber or gas fitter).
GAS
VALVE
NOTE: Before the first firing of the fireplace, the gas
supply line should be purged of any trapped air.
FLEX
NOTE: Consult local building codes to properly size
the gas supply line leading to the 1/2 inch
(13 mm) hook-up at the unit.
CONNECTOR
GAS LINE
ACCESS
HOLE
CONTROL
VALVE
MANUAL
SHUT-OFF VALVE
This gas fireplace is designed to accept a 1/2 inch
(13 mm) gas supply line.
To install the gas supply line:
Figure 22. Gas Supply Line
• A listed (and Commonwealth of Massachusetts approved)
1/2 inch (13mm) tee-handle manual shut-off valve and a
listed flexible gas connector are connected to the 1/2
inch (13mm) inlet of the control valve. NOTE: If substi-
tuting for these components, please consult local codes
for compliance.
Step 7. Gas Pressure Requirements
Pressure requirements for Heat & Glo gas fireplaces
are shown in the table below.
• Locate the gas line access hole in the outer casing of
the fireplace.
Pressure
Natural Gas
Propane
Minimum
Inlet Pressure
5.0 inches
w.c.
11.0 inches
w.c.
• The gas line may be run from either side of the fireplace
provided the hole in the outer wrap does not exceed 2 1/2”
in diameter and it does not penetrate the actual firebox.
Maximum Inlet
Gas Pressure
14.0 inches
w.c.
14.0 inches
w.c.
• The gap between the supply piping and gas access hole
can be plugged with non-combustible insulation to pre-
vent cold air infiltration.
Manifold
Pressure
3.5 inches
w.c.
10.0 inches
w.c.
• Open the fireplace lower grille, insert the gas supply line
through the gas line hole, and connect it to the shut-off
valve.
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
provided on the inlet and outlet side of the gas control for a
test gauge connection to measure the manifold pressure.
Use a small flat blade screwdriver to crack open the screw
in the center of the tap. Position a rubber hose over the tap
to obtain the pressure reading.
• When attaching the pipe, support the control so that the
lines are not bent or torn.
• After the gas line installation is complete, use a soap
solution to carefully check all gas connections for leaks.
The fireplace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of one-half (1/2) psig (3.5 kPa).
WARNING: DO NOT USE AN OPEN FLAME
TO CHECK FOR GAS LEAKS.
!
• At the gas line access hole, use insulation to re-pack
the space around the gas pipe.
The fireplace must be isolated from the gas supply piping
system by closing its individual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than one-half (1/2) psig (3.5 kPa).
• Insert insulation from the outside of the fireplace and
pack the insulation tightly to totally seal between the
pipe and the outer casing.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
22
INTERMITTENT
PILOT
IGNITION MODULE
3 VAC
PLUG-IN
3V TRANSFORMER
IGNITOR
ON/OFF
WALL
SWITCH
FLAME SPARKER/
SENSOR
IGNITION
MODULE
(3V)
ORG
WHT
LOW VOLTAGE
SEE NOTE 1
VALVE
GROUND TO
FIREPLACE
CHASSIS
GROUND
REMOTE
CONTROL
HOT
NEUTRAL
WHITE WIRE
CAN BE
PLUGGED
INTO ANY
OF #1-#5
LOCATIONS
ON THE
BLACK WIRE CAN BE
PLUGGED INTO ANY OF
#1 - #5 LOCATIONS
ON THE HOT SIDE
PIGGYBACK
ON/OFF SWITCH
NEUTRAL SIDE
TRANSFORMER
3 VAC
PLUG IN
VALVE
Figure 23. Intermittent Pilot Ignition (IPI) Wiring Diagram
Optional Accessories
Step 8. Wiring the Fireplace
Optional remote control kits require that 110-120 VAC be
wired to the factory installed junction box before the fire-
place is permanently installed.
NOTE: Electrical wiring must be installed by a licensed
electrician.
CAUTION: DISCONNECT REMOTE CONTROLS IF YOU
ARE ABSENT FOR EXTENDED TIME PERIODS. THIS
WILL PREVENTACCIDENTAL FIREPLACE OPERATION.
Wall Switch
Position the wall switch in the desired position on the wall.
An assembly of 18 ft of 20 AWG is provided with the fire-
place to connect the wall switch to the appliance. Instead of
the supplied assembly, wire with a length of 25 ft or less and
a gauge of 20 AWG through 14 AWG is acceptable. The
wire needs a jacket with a temperature rating of 140oF (60oC)
or higher. At the appliance connect the wire to the ON/OFF
switch pigtails.
Intermittent Pilot Ignition (IPI) Wiring
Appliance Requirements
This appliance requires that 110-120 VAC be wired to the
factory installed junction box. Maintain correct polarity when
wiring the junction box.
WARNING: DO NOT CONNECT 110-120 VAC
TO THE WALL SWITCH OR THE CONTROL
VALVE WILL BE DESTROYED.
WARNING: DO NOT CONNECT 110-120 VAC
TO THE GAS CONTROL VALVE OR THE AP-
PLIANCE WILL MALFUNCTION AND THE
!
!
VALVE WILL BE DESTROYED.
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-
TION WHEN SERVICING CONTROLS. WIRING ERRORS
CAN CAUSE IMPROPER AND DANGEROUS OPERA-
TION. VERIFYPROPER OPERATIONAFTER SERVICING.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
23
CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS
AND THE FIREPLACE SURROUND (TOP AND SIDES)
ARE SEALED, A 300° F. MINIMUM SEALANT MATE-
RIAL MUST BE USED. THESE JOINTS ARE NOT RE-
QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE
MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF
NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-
PLACE SURROUND. SEE THE DIAGRAM BELOW.
Step 9. Finishing
The following diagram shows the minimum vertical and
corresponding maximum horizontal dimensions of fireplace
mantels or other combustible projections above the top front
edge of the fireplace. See Figures 2 and 3 for other fireplace
clearances.
Only non-combustible materials may be used to cover the
black fireplace front.
WARNING: WHEN FINISHING THE FIREPLACE,
NEVER OBSTRUCT OR MODIFY THE AIR IN-
FINISH WALL MATERIAL MAY BE COMBUSTIBLE
- TOP AND SIDES
!
LET/OUTLET GRILLES IN ANY MANNER.
0”
CEILING
12"
11"
10"
31”
9"
8"
HIGH TEMPERATURE
(3000F. / 149 0C. MIN.)
TOP & SIDE
7"
6"
12”
5"
11”
SEAL JOINT
10”
4"
2”
9”
8”
3"
7”
6”
2"
5”
4"
3”
1/2”
1/2”
Figure 25. Sealant Material
TOP FRONT EDGE
OF FIREPLACE
Hearth Extensions
A hearth extension may be desirable for aesthetic reasons.
However,ANSI or CAN/CGAtesting standards do not require
hearth extensions for gas fireplace appliances.
Figure 24.
Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles above Fireplace
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
24
Step 10. Installing Trim, Logs and
Ember Material
Installing the Trim
Combustible materials may be brought up to the specified
clearances on the side and top front edges of the fireplace,
but MUST NEVER overlap onto the front face. The joints
between the finished wall and the fireplace top and sides
can only be sealed with a 300° F. (149° C) minimum sealant.
LATCHES
Install optional marble and brass trim surround kits as
desired. Marble, brass, brick, tile, or other non-combustible
materials can be used to cover up the gap between the
sheet rock and the fireplace.
GLASS
ASSEMBLY
Positioning the Logs
If the gas logs have been factory installed they should not
need to be positioned. If the logs have been packaged
separately, refer to the instructions that accompany the
logs. Save the log instructions with this manual.
Figure 26. Glass Assembly
Glass Specifications: CERAMIC
If sooting occurs, the logs might need to be repositioned
slightly to avoid excessive flame impingement.
Placing the Rock
A bag of rock is shipped with this fireplace. Refer to the
placement instructions on the back of the log placement
instructions.
Placing the Ember Material
Ember material is shipped with this gas fireplace. The bag
labeled Glowing Ember (050-721) is standard glowing ember
material. To place the ember material:
EMBER
MATERIAL
• Pull the six glass latches out of the groove on the glass
frame. Remove the front trim door and the glass door
from the unit.
Figure 27. Placement of the Ember Material
• Cover the top of the burner with a single layer of ember
material. For best performance do not place embers di-
rectly on the ports. Save the remaining ember materials
for use during fireplace servicing.
• Replace the glass door and a front trim door on the unit
(see Service Parts List of this manual.)
• Pull out and latch the glass clips into the groove on the
glass frame.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
25
Step 12. Lighting the Fireplace
Step 11. Before Lighting the Fireplace
You’ve reviewed all safety warnings, you’ve checked the
fireplace for gas leaks, you know the vent system is
unobstructed, and you’ve checked for faulty components.
Now you’re ready to light the fireplace.
Before lighting the fireplace, be sure to do the following:
Remove all paperwork from underneath the fireplace.
Review safety warnings and cautions
• Read the Safety and Warning Information section at
the beginning of this Installers Guide.
WARNING: PLEASE REFER TO THE USER’S
MANUAL FORALL CAUTIONS, SAFETY, AND
!
Double-check for gas leaks
• Before lighting the fireplace, double-check the unit for
possible gas leaks.
WARNING INFORMATION PERTAINING TO THE
LIGHTING AND OPERATION OF THE FIREPLACE.
Double-check vent terminations and front grilles for
obstructions.
After the Installation
• Before lighting the fireplace, double-check the unit for
possible obstructions that could be blocking the vent ter-
minations or the front grilles.
LEAVE THIS INSTALLATION MANUAL WITH
!
THE APPLIANCE FOR FUTURE REFERENCE.
Double-check for faulty components
• Any component that is found to be faulty MUST BE re-
placed with an approved component. Tampering with the
fireplace components is DANGEROUS and voids all war-
ranties.
Battery Backup
This appliance may be operated on battery power in
the case of power outage. To operate the appliance
turn both the battery backup switch (right) and the main
on/off switch (left) to “on”. To conserve battery life,
turn the battery backup switch “off” when not in use.
A small amount of air will be in the gas supply lines. When
first lighting the fireplace, it will take a few minutes for the
lines to purge themselves of this air. Once the purging is
complete, the fireplace will light and will operate normally.
To replace the batteries, remove the screws holding
the control panel in place and pull it out. Be careful
not to disconnect any wires in the process.
Subsequent lightings of the fireplace will not require this
purging of air from the gas supply lines, unless the gas
valve has been turned to the OFF position, in which
case the air would have to be purged.
NOTE: Remotes or other powered options will not
function during a power outage.
NOTE: The fireplace should be run 3 to 4 hours on the initial
start-up. Turn it off and let it cool completely. Remove and
clean the glass. Replace the glass and run the fireplace for
an additional 8 hours. This will help to cure the products
used in the paint and logs.
During this break-in period it is recommended that some
windows in the house be opened for air circulation. This will
help avoid setting off smoke detectors, and help eliminate
any odors associated with the fireplace’s initial burning.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
26
Maintaining and Servicing
Your Fireplace
4
Fireplace Maintenance
Although the frequency of your fireplace servicing and main-
tenance will depend on use and the type of installation, you
should have a qualified service technician perform an appli-
ance check-up at the beginning of each heating season.
See the table below for specific guidelines regarding each
fireplace maintenance task.
IMPORTANT: TURN OFF THE GAS BEFORE SERVICING
YOUR FIREPLACE.
Figure 28.
Burner Flame Patterns
Replacing old ember material
Frequency: Once annually, during the checkup.
By: Qualified service technician.
Checking Flame Patterns, Flame Height
Frequency: Periodically.
Task: Brush away loose ember material near the burner.
Replace old ember material with new dime-size and shape
pieces of Golden Ember (DE-93) and Glowing Ember (050-
721). New ember material should be placed alternately on
top of the burner - a layer of Golden Ember, a layer of
Glowing Ember, and so on. Save the remaining ember
material and repeat this procedure at your next servicing.
For more information, see Placing Ember Material.
By: Qualified service technician/Home owner.
Task: Make a visual check of your fireplace’s flame patterns.
Make sure the flames are steady - not lifting or floating.
See Figure 28.
Checking Vent System
Frequency: Before initial use and at least annually
thereafter, more frequently if possible.
Cleaning Burner and Controls
Frequency: Once annually.
By: Qualified service technician/Home owner.
Task: Inspect the external vent cap on a regular basis to
ensure that no debris is interfering with the flow of air. Inspect
entire vent system for proper function.
By: Qualified service technician.
Task: Brush or vacuum the control compartment, fireplace
logs and burner areas surrounding the logs.
Cleaning Glass Door
Frequency: After the first 3 to 4 hours of use.As necessary
after initial cleaning.
Cleaning Flame Sensor Rod (IPI Systems)
Frequency: Periodically.
By: Home owner.
By: Qualified service technician.
Task: Clean as necessary, particularly after adding new ember
(flame colorant) material. Film deposits on the inside of the
glass door should be cleaned off using a household glass
cleaner. NOTE: DO NOT handle or attempt to clean the
door when it is hot and DO NOT use abrasive cleaners.
Task: Make a visual check of the straight flame sensor rod.
Use emery cloth to carefully remove any existing white
deposits.
Heat & Glo • Everest • 750-900 Rev. L • 1/06
Download from Www.Somanuals.com. All Manuals Search And Download.
27
|