Heat Controller Heat Pump HTD User Manual

INSTALLATION, OPERATION  
& MAINTENANCE MANUAL  
HTV/HTD/HTH Series  
Two-Stage  
Geothermal Heat Pumps  
2 to 6 Tons  
Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Safety  
CAUTION: Indicates a potentially hazardous situation or an  
unsafe practice, which if not avoided could result in minor or  
moderate injury or product or property damage.  
Warnings, cautions and notices appear throughout this manual.  
Read these items carefully before attempting any installation,  
service, or troubleshooting of the equipment.  
NOTICE: Notication of installation, operation or maintenance  
information, which is important, but which is not hazard-related.  
DANGER: Indicates an immediate hazardous situation, which if  
not avoided will result in death or serious injury. DANGER labels  
on unit access panels must be observed.  
WARNING! ꢀ  
WARNING: Indicates a potentially hazardous situation, which if  
not avoided could result in death or serious injury.  
WARNING! All refrigerant discharged from this unit must be  
recovered WITHOUT EXCEPTION. Technicians must follow  
industry accepted guidelines and all local, state, and federal  
statutes for the recovery and disposal of refrigerants. If a  
compressor is removed from this unit, refrigerant circuit oil will  
remain in the compressor. To avoid leakage of compressor oil,  
refrigerant lines of the compressor must be sealed after it is  
removed.  
WARNING! ꢀ  
WARNING! To avoid the release of refrigerant into the  
atmosphere, the refrigerant circuit of this unit must be serviced  
only by technicians who meet local, state, and federal  
prociency requirements.  
CAUTION! ꢀ  
CAUTION! To avoid equipment damage, DO NOT use these  
units as a source of heating or cooling during the construction  
process. The mechanical components and lters will quickly  
become clogged with construction dirt and debris, which may  
cause system damage.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
General Information  
Inspection  
7. Locate and verify any hot water generator (HWG), hanger,  
or other accessory kit located in the compressor section or  
blower section.  
Upon receipt of the equipment, carefully check the shipment  
against the bill of lading. Make sure all units have been received.  
Inspect the packaging of each unit, and inspect each unit for  
damage. Insure that the carrier makes proper notation of any  
shortages or damage on all copies of the freight bill and completes  
a common carrier inspection report. Concealed damage not  
discovered during unloading must be reported to the carrier within  
15 days of receipt of shipment. If not led within 15 days, the  
freight company can deny the claim without recourse. Note: It is the  
responsibility of the purchaser to le all necessary claims with the  
carrier. Notify your equipment supplier of all damage within fteen  
(15) days of shipment.  
CAUTION! ꢀ  
CAUTION! DO NOT store or install units in corrosive  
environments or in locations subject to temperature or  
humidity extremes (e.g., attics, garages, rooftops, etc.).  
Corrosive conditions and high temperature or humidity can  
signicantly reduce performance, reliability, and service  
life. Always move and store units in an upright position.  
Tilting units on their sides may cause equipment damage.  
Storage  
Equipment should be stored in its original packaging in a clean,  
dry area. Store units in an upright position at all times. Stack units  
a maximum of 3 units high.  
CAUTION! ꢀ  
CAUTION! CUT HAZARD - Failure to follow this caution  
may result in personal injury. Sheet metal parts may have  
sharp edges or burrs. Use care and wear appropriate  
protective clothing, safety glasses and gloves when  
handling parts and servicing heat pumps.  
Unit Protection  
Cover units on the job site with either the original packaging or  
an equivalent protective covering. Cap the open ends of pipes  
stored on the job site. In areas where painting, plastering, and/  
or spraying has not been completed, all due precautions must be  
taken to avoid physical damage to the units and contamination  
by foreign material. Physical damage and contamination may  
prevent proper start-up and may result in costly equipment clean-  
up.  
Examine all pipes, ttings, and valves before installing any of the  
system components. Remove any dirt or debris found in or on  
these components.  
Pre-Installation  
Installation, Operation, and Maintenance instructions are  
provided with each unit. Horizontal equipment is designed for  
installation above false ceiling or in a ceiling plenum. Other unit  
congurations are typically installed in a mechanical room. The  
installation site chosen should include adequate service clearance  
around the unit. Before unit start-up, read all manuals and  
become familiar with the unit and its operation. Thoroughly check  
the system before operation.  
Prepare units for installation as follows:  
1. Compare the electrical data on the unit nameplate with  
ordering and shipping information to verify that the correct unit  
has been shipped.  
2. Keep the cabinet covered with the original packaging until  
installation is complete and all plastering, painting, etc. is  
nished.  
3. Verify refrigerant tubing is free of kinks or dents and that it  
does not touch other unit components.  
4. Inspect all electrical connections. Connections must be clean  
and tight at the terminals.  
5. Remove any blower support packaging (water-to-air units  
only).  
6. Loosen compressor bolts on units equipped with compressor  
grommet vibration isolation until the compressor rides freely  
on the grommets.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
General Information  
Mounting Horizontal Units  
Horizontal Unit Location  
Horizontal units have hanger kits pre-installed from the factory  
as shown in Figure 1. Figure 3 shows a typical horizontal unit  
installation.  
Units are not designed for outdoor installation. Locate the unit in  
an INDOOR area that allows enough space for service personnel  
to perform typical maintenance or repairs without removing unit  
from the ceiling. Horizontal units are typically installed above a  
false ceiling or in a ceiling plenum. Never install units in areas  
subject to freezing or where humidity levels could cause cabinet  
condensation (such as unconditioned spaces subject to 100%  
outside air). Consideration should be given to access for easy  
removal of the lter and access panels. Provide sufcient room to  
make water, electrical, and duct connection(s).  
Horizontal heat pumps are typically suspended above a ceiling or  
within a soffit using field supplied, threaded rods sized to support  
the weight of the unit.  
Use four (4) field supplied threaded rods and factory provided  
vibration isolators to suspend the unit. Hang the unit clear of the  
oor slab above and support the unit by the mounting bracket  
assemblies only. DO NOT attach the unit flush with the floor slab  
above.  
If the unit is located in a conned space, such as a closet,  
provisions must be made for return air to freely enter the space  
by means of a louvered door, etc. Any access panel screws that  
would be difcult to remove after the unit is installed should  
be removed prior to setting the unit. Refer to Figure 3 for an  
illustration of a typical installation. Refer to unit specications  
catalog for dimensional data.  
Pitch the unit toward the drain as shown in Figure 2 to improve  
the condensate drainage. On small units (less than 8.8kW) ensure  
that unit pitch does not cause condensate leaks inside the  
cabinet.  
Conform to the following guidelines when selecting  
unit location:  
Figure 1: Hanger Bracket  
1. Provide a hinged access door in concealed-spline or plaster  
ceilings. Provide removable ceiling tiles in T-bar or lay-in  
ceilings. Refer to horizontal unit dimensions for specic  
series and model in unit specications catalog. Size the  
access opening to accommodate the service technician  
during the removal or replacement of the compressor and  
the removal or installation of the unit itself.  
2. Provide access to hanger brackets, water valves and ttings.  
Provide screwdriver clearance to access panels, discharge  
collars and all electrical connections.  
ꢀꢁꢂꢃꢄ>ꢅꢆPP@ꢄ7KUHDGHG  
5RGꢄꢇE\ꢄRWKHUVꢈ  
9LEUDWLRQꢄ,VRODWRU  
ꢇIDFWRU\ꢄVXSSOLHGꢈ  
:DVKHU  
ꢇE\ꢄRWKHUVꢈ  
'RXEOHꢄ+H[ꢄ1XWV  
ꢇE\ꢄRWKHUVꢈ  
3. DO NOT obstruct the space beneath the unit with piping,  
electrical cables and other items that prohibit future removal  
of components or the unit itself.  
4. Use a manual portable jack/lift to lift and support the weight  
of the unit during installation and servicing.  
The installation of water source heat pump units and all  
associated components, parts and accessories which make  
up the installation shall be in accordance with the regulations  
of ALL authorities having jurisdiction and MUST conform to  
all applicable codes. It is the responsibility of the installing  
contractor to determine and comply with ALL applicable codes  
and regulations.  
Figure 2: Horizontal Unit Pitch  
1/4” (6.4mm) pitch  
per foot for drainage  
Drain  
Connection  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Horizontal Installation  
Figure 3: Typical Horizontal Unit Installation  
ꢇꢃꢈꢄꢀ>ꢉꢆPP@ꢀWKUHDGHGꢀURGV  
ꢀꢁE\ꢀRWKHUVꢂ  
2SWLRQDOꢀ/RZꢀ3UHVVXUHꢀ'URSꢀ:DWHU  
&RQWUROꢀ9DOYH  
ꢁFDQꢀEHꢀLQWHUQDOO\ꢀPRXQWHG  
RQꢀVRPHꢀPRGHOVꢂ  
5HWXUQꢀ$LU  
7KHUPRVWDW  
:LULQJ  
3RZHUꢀ:LULQJ  
6WDLQOHVVꢀVWHHOꢀEUDLGꢀꢀKRVH  
ZLWKꢀLQWHJUDOꢀꢄ-ꢄ ꢀVZLYHO  
6XSSO\ꢀ$LU  
2SWLRQDOꢀ%DODQFLQJꢀ9DOYH  
8QLWꢀ3RZHU  
%XLOGLQJ  
/RRS  
)OH[LEOHꢀ'XFW  
,QVXODWHGꢀVXSSO\ꢀGXFWꢀZLWK  
&RQQHFWRU  
DWꢀOHDVWꢀRQHꢀꢅꢆꢀGHJꢀHOERZ  
WRꢀUHGXFHꢀDLUꢀQRLVH  
8QLWꢀ3RZHU  
:DWHUꢀ2XW  
:DWHUꢀ,Q  
'LVFRQQHFW  
ꢀꢁE\ꢀRWKHUVꢂ  
%DOOꢀ9DOYHꢀZLWKꢀRSWLRQDO  
LQWHJUDOꢀ3ꢃ7ꢀSOXJ  
8QLWꢀ+DQJHU  
Air Coil - To obtain maximum performance, the air coil should be  
cleaned before start-up. A 10% solution of dishwasher detergent  
and water is recommended for both sides of the coil. A thorough  
water rinse should follow.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Field Conversion of Air Discharge  
Overview - Horizontal units can be eld converted between side  
Figure 4: Left Return Side to Back  
(straight) and back (end) discharge using the instructions below.  
Remove Screws  
Water  
Connection End  
Note: It is not possible to eld convert return air between left or  
right return models due to the necessity of refrigeration copper  
piping changes.  
Return Air  
Preparation - It is best to eld convert the unit on the ground  
before hanging. If the unit is already hung it should be taken down  
for the eld conversion.  
Side Discharge  
Side to Back Discharge Conversion  
1.  
Place unit in well lit area. Remove the screws as shown in  
Figure 4 to free top panel and discharge panel.  
Lift out the access panel and set aside. Lift and rotate the  
discharge panel to the other position as shown, being careful  
with the blower wiring.  
Water  
Connection End  
Rotate  
2.  
Return Air  
3.  
4.  
5.  
6.  
7.  
Check blower wire routing and connections for tension or  
contact with sheet metal edges. Reroute if necessary.  
Check refrigerant tubing for contact with  
other components.  
Reinstall top panel and screws noting that the location for  
some screws will have changed.  
Manually spin the fan wheel to ensure that the wheel is not  
rubbing or obstructed.  
Replace access panels.  
Move to Side  
Replace Screws  
Water  
Connection End  
Back to Side Discharge Conversion - If the discharge is changed  
from back to side, use above instruction noting that illustrations will  
be reversed.  
Return Air  
Drain  
Left vs. Right Return - It is not possible to eld convert return air  
between left or right return models due to the necessity of refrigera-  
tion copper piping changes. However, the conversion process of  
side to back or back to side discharge for either right or left return  
conguration is the same. In some cases, it may be possible to  
rotate the entire unit 180 degrees if the return air connection needs  
to be on the opposite side. Note that rotating the unit will move the  
piping to the other end of the unit.  
Discharge Air  
Back Discharge  
Figure 5: Right Return Side to Back  
Water  
Connection End  
Return Air  
Supply Duct  
Side Discharge  
Water  
Connection End  
Return Air  
Drain  
Back Discharge  
Discharge Air  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Horizontal Installation  
Condensate Piping  
Figure 6: Horizontal Condensate Connection  
Condensate Piping – Horizontal Units  
Pitch the unit toward the drain as shown in Figure 2 to improve  
the condensate drainage. On small units (less than 2.5 tons/8.8  
kW), insure that unit pitch does not cause condensate leaks  
inside the cabinet.  
ꢀರ  
ꢁꢄꢅರꢆ3HUꢆ  
)RRW  
Install condensate trap at each unit with the top of the trap  
positioned below the unit condensate drain connection as shown  
in Figure 6. Design the depth of the trap (water-seal) based  
upon the amount of ESP capability of the blower (where 2 inches  
[51mm] of ESP capability requires 2 inches [51mm] of trap depth).  
As a general rule, 1-1/2 inch [38mm] trap depth is the minimum.  
ꢁꢂꢃರ  
ꢁꢂꢃರ  
* Some units include a painted drain connection.  
Using a threaded pipe or similar device to clear  
any excess paint accumulated inside this fitting  
may ease final drain line installation.  
Each unit must be installed with its own individual trap and  
connection to the condensate line (main) or riser. Provide a  
means to ush or blow out the condensate line. DO NOT install  
units with a common trap and/or vent.  
Always vent the condensate line when dirt or air can collect in  
the line or a long horizontal drain line is required. Also vent when  
large units are working against higher external static pressure  
than other units connected to the same condensate main since  
this may cause poor drainage for all units on the line. WHEN A  
VENT IS INSTALLED IN THE DRAIN LINE, IT MUST BE LOCATED  
AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE  
FLOW.  
CAUTION! ꢀ  
CAUTION! Ensure condensate line is pitched toward drain  
1/8 inch per ft [11mm per m] of run.  
DUCT SYSTEM INSTALLATION  
Duct System Installation  
At least one 90° elbow should be included in the supply duct to  
reduce air noise. If air noise or excessive air ow is a problem,  
the blower speed can be changed. For airow charts, consult  
specications catalog for the series and model of the specic  
unit.  
The duct system should be sized to handle the design airow  
quietly. Refer to Figure 3 for horizontal duct system details or  
gure 8 for vertical duct system details. A exible connector is  
recommended for both discharge and return air duct connections  
on metal duct systems to eliminate the transfer of vibration to  
the duct system. To maximize sound attenuation of the unit  
blower, the supply and return plenums should include internal  
berglass duct liner or be constructed from ductboard for the  
rst few feet. Application of the unit to uninsulated ductwork  
in an unconditioned space is not recommended, as the unit’s  
performance will be adversely affected.  
If the unit is connected to existing ductwork, a previous check  
should have been made to insure that the ductwork has the  
capacity to handle the airow required for the unit. If ducting is  
too small, as in the replacement of a heating only system, larger  
ductwork should be installed. All existing ductwork should be  
checked for leaks and repaired as necessary.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Vertical Installation  
Figure 7: Vertical Unit Mounting  
Vertical Unit Location  
Units are not designed for outdoor installation. Locate the unit in  
an INDOOR area that allows enough space for service personnel  
to perform typical maintenance or repairs without removing unit  
from the mechanical room/closet. Vertical units are typically  
installed in a mechanical room or closet. Never install units in  
areas subject to freezing or where humidity levels could cause  
cabinet condensation (such as unconditioned spaces subject to  
100% outside air). Consideration should be given to access for  
easy removal of the lter and access panels. Provide sufcient  
room to make water, electrical, and duct connection(s).  
If the unit is located in a conned space, such as a closet,  
provisions must be made for return air to freely enter the space  
by means of a louvered door, etc. Any access panel screws that  
would be difcult to remove after the unit is installed should  
be removed prior to setting the unit. Refer to Figures 7 and 8  
for typical installation illustrations. Refer to unit specications  
catalog for dimensional data.  
$LUꢀ3DGꢀRUꢀH[WUXGHG  
SRO\VW\UHQHꢀLQVXODWLRQꢀERDUG  
1. Install the unit on a piece of rubber, neoprene or other  
mounting pad material for sound isolation. The pad should  
be at least 3/8” [10mm] to 1/2” [13mm] in thickness. Extend  
the pad beyond all four edges of the unit.  
2. Provide adequate clearance for lter replacement and drain  
pan cleaning. Do not block lter access with piping, conduit  
or other materials. Refer to unit specications for dimensional  
data.  
3. Provide access for fan and fan motor maintenance and for  
servicing the compressor and coils without removing the unit.  
4. Provide an unobstructed path to the unit within the closet  
or mechanical room. Space should be sufcient to allow  
removal of the unit, if necessary.  
Figure 8: Typical Vertical Unit Installation Using Ducted  
Return Air  
Internally insulate supply  
duct for first 1.2 m each way  
to reduce noise  
Use turning vanes in  
supply transition  
5. Provide access to water valves and ttings and screwdriver  
access to the unit side panels, discharge collar and all  
electrical connections.  
Flexible canvas duct  
connector to reduce  
noise and vibration  
Downow units may be installed directly on the oor. The  
optional internal electric heat is rated for zero clearance to  
combustible materials.  
Rounded return  
transition  
The installation of water source heat pump units and all  
associated components, parts and accessories which make  
up the installation shall be in accordance with the regulations  
of ALL authorities having jurisdiction and MUST conform to  
all applicable codes. It is the responsibility of the installing  
contractor to determine and comply with ALL applicable codes  
and regulations.  
Rev.: 6/2/09S  
Internally insulate return  
transition duct to reduce  
noise  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Vertical Installation  
Sound Attenuation for Vertical Units - Sound attenuation is  
achieved by enclosing the unit within a small mechanical room  
or a closet. Additional measures for sound control include the  
following:  
Condensate Piping for Vertical Units - Vertical units utilize a  
condensate hose inside the cabinet as a trapping loop; therefore  
an external trap is not necessary. Figure 10a shows typical  
condensate connections. Figure 10b illustrates the internal trap  
for a typical vertical heat pump. Each unit must be installed with  
its own individual vent (where necessary) and a means to ush  
or blow out the condensate drain line. Do not install units with a  
common trap and/or vent.  
1.  
Mount the unit so that the return air inlet is 90° to the  
return air grille. Refer to Figure 9. Install a sound bafe as  
illustrated to reduce line-of sight sound transmitted through  
return air grilles.  
2.  
Mount the unit on an Unit Isolation Pad to minimize vibration  
transmission to the building structure. For more information on  
Unit Isolation Pads, contact your distributor.  
Figure 10a: Vertical Condensate Drain  
Figure 9: Vertical Sound Attenuation  
ꢀರ  
ꢁꢄꢅರꢆ3HUꢆ  
)RRW  
ꢁꢂꢃರ  
ꢁꢂꢃರ  
Return  
Air Inlet  
* Some units include a painted drain connection.  
Using a threaded pipe or similar device to clear  
any excess paint accumulated inside this fitting  
may ease final drain line installation.  
Figure 10b: Vertical Internal Condensate Trap  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Water Connection Installation  
External Flow Controller Mounting  
The female locking ring is threaded onto the pipe threads which  
holds the male pipe end against the rubber gasket, and seals the  
joint. HAND TIGHTEN ONLY! DO NOT OVERTIGHTEN!  
The Flow Controller can be mounted beside the unit as shown  
in Figure 12. Review the Flow Controller installation manual for  
more details.  
Figure 11: Water Connections  
Water Connections-Residential (Distributor) Models  
Residential models utilize swivel piping ttings for water  
connections that are rated for 450 psi (3101 kPa) operating  
pressure. The connections have a rubber gasket seal similar to a  
garden hose gasket, which when mated to the ush end of most  
1” threaded male pipe ttings provides a leak-free seal without  
the need for thread sealing tape or joint compound. Check for  
burrs and ensure that the rubber seal is in the swivel connector  
prior to attempting any connection (rubber seals are shipped  
attached to the swivel connector). DO NOT OVER TIGHTEN or  
leaks may occur.  
Swivel Nut  
Hand Tighten  
Only!  
Do Not  
Overtighten!  
Stainless steel  
snap ring  
Gasket  
Brass Adaptor  
GROUND-LOOP HEAT PUMP APPLICATIONS  
Figure 12: Typical Ground-Loop Application  
Pre-Installation  
Prior to installation, locate and mark all existing underground  
utilities, piping, etc. Install loops for new construction before  
sidewalks, patios, driveways, and other construction has begun.  
During construction, accurately mark all ground loop piping on  
the plot plan as an aid in avoiding potential future damage to the  
installation.  
To Thermostat  
Piping Installation  
The typical closed loop ground source system is shown in Figure  
12. All earth loop piping materials should be limited to polyethylene  
fusion only for in-ground sections of the loop. Galvanized or steel  
ttings should not be used at any time due to their tendency to  
corrode. All plastic to metal threaded ttings should be avoided due  
to their potential to leak in earth coupled applications. A anged  
tting should be substituted. P/T plugs should be used so that  
ow can be measured using the pressure drop of the unit heat  
exchanger.  
High and  
Low Voltage  
Knockouts  
Vibration Isolation Pad  
Earth loop temperatures can range between 25 and 110°F [-4  
to 43°C]. Flow rates between 2.25 and 3 gpm per ton [2.41 to  
3.23 l/m per kW] of cooling capacity is recommended in these  
applications.  
CAUTION! ꢀ  
Test individual horizontal loop circuits before backlling. Test  
vertical U-bends and pond loop assemblies prior to installation.  
Pressures of at least 100 psi [689 kPa] should be used when  
testing. Do not exceed the pipe pressure rating. Test entire  
system when all loops are assembled.  
CAUTION! The following instructions represent industry  
accepted installation practices for closed loop earth coupled  
heat pump systems. Instructions are provided to assist the  
contractor in installing trouble free ground loops. These  
instructions are recommendations only. State/provincial  
and local codes MUST be followed and installation MUST  
conform to ALL applicable codes. It is the responsibility of  
the installing contractor to determine and comply with ALL  
applicable codes and regulations.  
Flushing the Earth Loop  
Once piping is completed between the unit, Flow Controller and  
the ground loop (Figure 12), the loop is ready for nal purging  
and charging. A ush cart with at least a 1.5 hp [1.1 kW] pump is  
required to achieve enough uid velocity in the loop piping system  
to purge air and dirt particles. An antifreeze solution is used in  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Ground-Loop Heat Pump Applications  
most areas to prevent freezing. All air and debris must be removed  
from the earth loop piping before operation. Flush the loop with a  
high volume of water at a minimum velocity of 2 fps (0.6 m/s) in all  
piping. The steps below must be followed for proper ushing.  
1. Fill loop with water from a garden hose through the ush cart  
before using the ush cart pump to insure an even ll.  
2. Once full, the ushing process can begin. Do not allow the  
water level in the ush cart tank to drop below the pump inlet  
line to avoid air being pumped back out to the earth loop.  
3. Try to maintain a uid level in the tank above the return tee  
so that air cannot be continuously mixed back into the uid.  
Surges of 50 psi (345 kPa) can be used to help purge air  
pockets by simply shutting off the return valve going into the  
ush cart reservoir. This dead heads” the pump to 50 psi (345  
kPa). To purge, dead head the pump until maximum pumping  
pressure is reached. Open the return valve and a pressure  
surge will be sent through the loop to help purge air pockets  
from the piping system.  
4. Notice the drop in uid level in the ush cart tank when the  
return valve is shut off. If air is adequately purged from the  
system, the level will drop only 1-2 inches (2.5 - 5 cm) in a  
10” (25 cm) diameter PVC ush tank (about a half gallon [2.3  
liters]), since liquids are incompressible. If the level drops  
more than this, ushing should continue since air is still  
being compressed in the loop uid. Perform the “dead head”  
procedure a number of times. Note: This uid level drop is  
your only indication of air in the loop.  
Low temperature protection should be maintained to 15°F [9°C]  
below the lowest expected entering loop temperature. For  
example, if 30°F [-1°C] is the minimum expected entering loop  
temperature, the leaving loop temperature would be 25 to 22°F  
[-4 to -6°C] and low temperature protection should be at 15°F  
[-10°C]. Calculation is as follows:  
30°F - 15°F = 15°F [-1°C - 9°C = -10°C].  
All alcohols should be premixed and pumped from a reservoir  
outside of the building when possible or introduced under the  
water level to prevent fumes. Calculate the total volume of  
uid in the piping system. Then use the percentage by volume  
shown in Table 2 for the amount of antifreeze needed. Antifreeze  
concentration should be checked from a well mixed sample  
using a hydrometer to measure specic gravity.  
Low Water Temperature Cutout Setting - CXM Control  
When antifreeze is selected, the FP1 jumper (JW3) should be  
clipped to select the low temperature (antifreeze 10°F [-12.2°C])  
set point and avoid nuisance faults (see “Low Water Temperature  
Cutout Selection” in this manual). Note: Low water temperature  
operation requires extended range equipment.  
Table 1: Approximate Fluid Volume (gal.) per 100' of Pipe  
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)  
Pipe  
Size  
1”  
Volume (gal) [liters]  
4.1 [15.3]  
Antifreeze may be added before, during or after the ushing  
procedure. However, depending upon which time is chosen,  
antifreeze could be wasted when emptying the ush cart tank.  
See antifreeze section for more details.  
Copper  
1.25”  
6.4 [23.8]  
2.5”  
9.2 [34.3]  
Rubber Hose  
1”  
3.9 [14.6]  
3/4” IPS SDR11  
1” iPS SDR11  
1.25” IPS SDR11  
1.5” IPS SDR11  
2” IPS SDR11  
1.25” IPS SCH40  
1.5” IPS SCH40  
2” IPS SCH40  
Typical  
2.8 [10.4]  
Loop static pressure will uctuate with the seasons. Pressures  
will be higher in the winter months than during the cooling  
season. This uctuation is normal and should be considered  
when charging the system initially. Run the unit in either heating  
or cooling for a number of minutes to condition the loop to a  
homogenous temperature. This is a good time for tool cleanup,  
piping insulation, etc. Then, perform nal ush and pressurize  
the loop to a static pressure of 50-75 psi [345-517 kPa] (winter)  
or 35-40 psi [241-276 kPa] (summer). After pressurization, be  
sure to loosen the plug at the end of the Grundfos loop pump  
motor(s) to allow trapped air to be discharged and to insure the  
motor housing has been ooded. This is not required for Taco  
circulators. Insure that the Flow Controller provides adequate  
ow through the unit by checking pressure drop across the heat  
exchanger and compare to the pressure drop tables at the back  
of the manual.  
4.5 [16.7]  
8.0 [29.8]  
10.9 [40.7]  
18.0 [67.0]  
8.3 [30.9]  
Polyethylene  
10.9 [40.7]  
17.0 [63.4]  
1.0 [3.8]  
Unit Heat Exchanger  
Flush Cart Tank  
10” Dia x 3ft tall  
[254mm x 91.4cm tall]  
10 [37.9]  
Antifreeze  
In areas where minimum entering loop temperatures drop below  
40°F [5°C] or where piping will be routed through areas subject  
to freezing, antifreeze is required. Alcohols and glycols are  
commonly used as antifreeze; however your local sales manager  
should be consulted for the antifreeze best suited to your area.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Ground-Loop Heat Pump Applications  
Table 2: Antifreeze Percentages by Volume  
Minimum Temperature  
for Low Temperature Protection  
Type  
10°F  
15°F  
20°F  
25°F  
[-12.2°C] [-9.4°C]  
[-6.7°C]  
[-3.9°C]  
Methanol  
Propylene Glycol  
Ethanol*  
21%  
29%  
23%  
17%  
24%  
20%  
13%  
18%  
16%  
8%  
12%  
11%  
* Must not be denatured with any petroleum based product  
GROUND-WATER HEAT PUMP APPLICATIONS  
Open Loop - Ground Water Systems  
Pressure Tank and Pump  
Typical open loop piping is shown in Figure 13. Shut off valves  
should be included for ease of servicing. Boiler drains or other  
valves should be tee’d” into the lines to allow acid ushing of the  
heat exchanger. Shut off valves should be positioned to allow ow  
Use a closed, bladder-type pressure tank to minimize mineral  
formation due to air exposure. The pressure tank should be  
sized to provide at least one minute continuous run time of the  
pump using its drawdown capacity rating to prevent pump short  
through the coax via the boiler drains without allowing ow into the cycling. Discharge water from the unit is not contaminated in any  
piping system. P/T plugs should be used so that pressure drop  
and temperature can be measured. Piping materials should be  
limited to copper or PVC SCH80. Note: Due to the pressure and  
temperature extremes, PVC SCH40 is not recommended.  
manner and can be disposed of in various ways, depending on  
local building codes (e.g. recharge well, storm sewer, drain eld,  
adjacent stream or pond, etc.). Most local codes forbid the use  
of sanitary sewer for disposal. Consult your local building and  
zoning department to assure compliance in your area.  
The pump should be sized to handle the home’s domestic water  
load (typically 5-9 gpm [23-41 l/m]) plus the ow rate required  
for the heat pump. Pump sizing and expansion tank must be  
chosen as complimentary items. For example, an expansion  
tank that is too small can causing premature pump failure due  
to short cycling. Variable speed pumping applications should be  
considered for the inherent energy savings and smaller pressure  
tank requirements.  
Water quantity should be plentiful and of good quality. Consult  
table 3 for water quality guidelines. The unit can be ordered with  
either a copper or cupro-nickel water heat exchanger. Consult  
table 3 for recommendations. Copper is recommended for  
closed loop systems and open loop ground water systems that  
are not high in mineral content or corrosiveness. In conditions  
anticipating heavy scale formation or in brackish water, a cupro-  
nickel heat exchanger is recommended. In ground water situations  
where scaling could be heavy or where biological growth such  
as iron bacteria will be present, an open loop system is not  
recommended. Heat exchanger coils may over time lose heat  
exchange capabilities due to build up of mineral deposits. Heat  
exchangers must only be serviced by a qualied technician, as  
acid and special pumping equipment is required. Desuperheater  
coils can likewise become scaled and possibly plugged. In areas  
with extremely hard water, the owner should be informed that the  
heat exchanger may require occasional acid ushing. In some  
cases, the desuperheater option should not be recommended due  
to hard water conditions and additional maintenance required.  
Water Control Valve  
Note the placement of the water control valve in gure 13. Always  
maintain water pressure in the heat exchanger by placing the  
water control valve(s) on the discharge line to prevent mineral  
precipitation during the off-cycle. Pilot operated slow closing  
valves are recommended to reduce water hammer. If water  
hammer persists, a mini-expansion tank can be mounted on the  
piping to help absorb the excess hammer shock. Insure that the  
total ‘VA’ draw of the valve can be supplied by the unit transformer.  
For instance, a slow closing valve can draw up to 35VA. This  
can overload smaller 40 or 50 VA transformers depending on the  
other controls in the circuit. A typical pilot operated solenoid valve  
draws approximately 15VA (see Figure 22). Note the special wiring  
diagrams for slow closing valves (Figures 23 & 24).  
Water Quality Standards  
Table 3 should be consulted for water quality requirements.  
Scaling potential should be assessed using the pH/Calcium  
hardness method. If the pH <7.5 and the Calcium hardness is  
less than 100 ppm, scaling potential is low. If this method yields  
numbers out of range of those listed, the Ryznar Stability and  
Langelier Saturation indecies should be calculated. Use the  
appropriate scaling surface temperature for the application,  
150°F [66°C] for direct use (well water/open loop) and DHW  
(desuperheater); 90°F [32°F] for indirect use. A monitoring plan  
should be implemented in these probable scaling situations. Other  
water quality issues such as iron fouling, corrosion prevention and  
erosion and clogging should be referenced in Table 3.  
Flow Regulation  
Flow regulation can be accomplished by two methods. One method  
of ow regulation involves simply adjusting the ball valve or water  
control valve on the discharge line. Measure the pressure drop  
through the unit heat exchanger, and determine ow rate from  
tables 9a through 9c. Since the pressure is constantly varying, two  
pressure gauges may be needed. Adjust the valve until the desired  
ow of 1.5 to 2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved.  
A second method of ow control requires a ow control device  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Ground-Water Heat Pump Applications  
mounted on the outlet of the water control valve. The device is  
typically a brass tting with an orice of rubber or plastic material  
that is designed to allow a specied ow rate. On occasion, ow  
control devices may produce velocity noise that can be reduced  
by applying some back pressure from the ball valve located on the  
discharge line. Slightly closing the valve will spread the pressure  
drop over both devices, lessening the velocity noise. NOTE: When  
EWT is below 50°F [10°C], a minimum of 2 gpm per ton (2.6 l/m  
per kW) is required.  
CAUTION! ꢀ  
CAUTION! Refrigerant pressure activated water regulating  
valves should never be used with this equipment.  
Water Coil Low Temperature Limit Setting  
For all open loop systems the 30°F [-1.1°C] FP1 setting (factory  
setting-water) should be used to avoid freeze damage to the unit.  
See Low Water Temperature Cutout Selection” in this manual for  
details on the low limit setting.  
Figure 13: Typical Open Loop/Well Application  
8QLWꢀ3RZHU  
'LVFRQQHFW  
)ORZ  
5HJXODWRU  
:DWHU  
&RQWURO  
9DOYH  
3UHVVXUH  
7D Q N  
:DWHUꢀ2XW  
:DWHUꢀ,Q  
6KXWꢁ2II  
9DOYH  
$LUꢀ3DGꢀRU  
([WUXGHG  
SRO\VW\UHQH  
LQVXODWLRQꢀERDUG  
7KHUPRVWDW  
:LULQJ  
2SWLRQDO  
)LOWHU  
%RLOHU  
'UDLQV  
3ꢂ7ꢀ3OXJV  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Water Quality Standards  
Table 3: Water Quality Standards  
Water Quality  
Parameter  
HX  
Material  
Closed  
Recirculating  
Open Loop and Recirculating Well  
Scaling Potential - Primary Measurement  
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below  
pH/Calcium Hardness  
Method  
-
All  
pH < 7.5 and Ca Hardness <100ppm  
Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)  
Scaling indexes should be calculated at 66°C for direct use and HWG applications, and at 32°C for indirect HX use.  
A monitoring plan should be implemented.  
Ryznar  
Stability Index  
-
6.0 - 7.5  
If >7.5 minimize steel pipe use.  
All  
All  
-
-0.5 to +0.5  
Langelier  
Saturation Index  
If <-0.5 minimize steel pipe use. Based upon 66°C HWG and  
Direct well, 29°C Indirect Well HX  
Iron Fouling  
Iron Fe (Ferrous)  
2+  
-
-
<0.2 ppm (Ferrous)  
If Fe2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.  
All  
All  
(Bacterial Iron potential)  
<0.5 ppm of Oxygen  
Above this level deposition will occur.  
Iron Fouling  
Corrosion Prevention  
6 - 8.5  
6 - 8.5  
pH  
All  
All  
Monitor/treat as  
needed  
Minimize steel pipe below 7 and no open tanks with pH <8  
-
<0.5 ppm  
At H S>0.2 ppm, avoid use of copper and copper nickel piping or HX's.  
2
Hydrogen Sulfide (H S)  
2
Rotten egg smell appears at 0.5 ppm level.  
Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.  
Ammonia ion as hydroxide, chloride,  
nitrate and sulfate compounds  
-
<0.5 ppm  
All  
Maximum Allowable at maximum water temperature.  
10$C  
<20ppm  
24$C  
NR  
38 C  
NR  
Copper  
Cupronickel  
-
-
-
-
-
Maximum  
<150 ppm  
<400 ppm  
<1000 ppm  
>1000 ppm  
NR  
NR  
Chloride Levels  
304 S  
316 S  
S
S
<250 ppm  
<550 ppm  
>550 ppm  
<150 ppm  
< 375 ppm  
>375 ppm  
Titanium  
All  
Erosion and Clogging  
<10 ppm of particles  
and a maximum  
velocity of 1.8 m/s  
Filtered for maximum  
841 micron [0.84 mm,  
20 mesh] size.  
<10 ppm (<1 ppm "sandfree” for reinjection) of particles and a maximum  
velocity of 1.8 m/s. Filtered for maximum 841 micron 0.84 mm,  
20 mesh] size. Any particulate that is not removed can potentially  
clog components.  
Particulate Size and  
Erosion  
Rev.: 3/22/2012  
Manufacturer  
The Water Quality Table provides water quality requirements for Manufacturercoaxial heat exchangers. When water properties are outside of those  
requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the  
warranty for the coaxial heat exchanger.  
Notes:  
‡ꢀ&ORVHGꢀ5HFLUFXODWLQJꢀV\VWHPꢀLVꢀLGHQWLILHGꢀE\ꢀDꢀclosed pressurized piping system.  
‡ꢀ5HFLUFXODWLQJꢀRSHQꢀZHOOVꢀVKRXOGꢀREVHUYHꢀWKHꢀRSHQꢀUHFLUFXODWLQJꢀGHVLJQꢀFRQVLGHUDWLRQVꢃ  
‡ꢀ15ꢀꢁꢀApplication not recommended.  
‡ꢀꢂꢁꢂꢀ1RꢀGHVLJQꢀ0D[LPXPꢃ  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Hot Water Generator  
The HWG (Hot Water Generator) or desuperheater option  
provides considerable operating cost savings by utilizing excess  
heat energy from the heat pump to help satisfy domestic hot  
water requirements. The HWG is active throughout the year,  
providing virtually free hot water when the heat pump operates  
in the cooling mode or hot water at the COP of the heat pump  
during operation in the heating mode. Actual HWG water  
heating capacities are provided in the appropriate heat pump  
performance data.  
Electric water heaters are recommended. If a gas, propane, or  
oil water heater is used, a second preheat tank must be installed  
(Figure 15). If the electric water heater has only a single center  
element, the dual tank system is recommended to insure a usable  
entering water temperature for the HWG.  
Typically a single tank of at least 52 gallons (235 liters) is used to  
limit installation costs and space. However, a dual tank, as shown  
in Figure 15, is the most efcient system, providing the maximum  
storage and temperate source water to the HWG.  
Heat pumps equipped with the HWG option include a built-in  
water to refrigerant heat exchanger that eliminates the need to  
tie into the heat pump refrigerant circuit in the eld. The control  
circuit and pump are also built in for residential equipment. Figure  
14 shows a typical example of HWG water piping connections on  
a unit with built-in circulating pump. This piping layout reduces  
scaling potential.  
It is always advisable to use water softening equipment on  
domestic water systems to reduce the scaling potential and  
lengthen equipment life. In extreme water conditions, it may be  
necessary to avoid the use of the HWG option since the potential  
cost of frequent maintenance may offset or exceed any savings.  
Consult Table 3 for scaling potential tests.  
The temperature set point of the HWG is eld selectable to 125°F  
or 150°F . The 150°F set point allows more heat storage from  
the HWG. For example, consider the amount of heat that can be  
generated by the HWG when using the 125°F set point, versus  
the amount of heat that can be generated by the HWG when  
using the 150°F set point.  
Figure 14: Typical HWG Installation  
Cold  
Inlet  
Hot Outlet  
to home  
Shut Off  
Valve #1  
Shut Off  
Valve #4  
Upper  
In a typical 50 gallon two-element electric water heater the lower  
element should be turned down to 100°F, or the lowest setting,  
to get the most from the HWG. The tank will eventually stratify  
so that the lower 80% of the tank, or 40 gallons, becomes 100°F  
(controlled by the lower element). The upper 20% of the tank, or  
10 gallons, will be maintained at 125°F (controlled by the upper  
element).  
element to  
120 - 130°F  
[49 - 54°C]  
Lower  
element to  
Powered  
Water  
Heater  
100 - 110°F  
[38 - 43°C]  
Shut-off  
Valve #3  
Using a 125°F set point, the HWG can heat the lower 40 gallons  
of water from 100°F to 125°F, providing up to 8,330 btu’s of heat.  
Using the 150°F set point, the HWG can heat the same 40 gallons  
of water from 100°F to 150°F and the remaining 10 gallons of  
water from 125°F to 150°F, providing a total of up to 18,743 btu’s  
of heat, or more than twice as much heat as when using the  
125°F set point.  
Shut Off  
Valve #2  
Field supplied 3/4’ brass nipple and ‘T’  
Insulated water lines -  
5/8” OD, 50 ft maximum (one way)  
[16mm OD, 15 meters maximum]  
Figure 15: HWG Double Tank Installation  
This example ignored standby losses of the tank. When those  
losses are considered the additional savings are even greater.  
Hot Outlet to  
house  
Cold Inlet  
Cold Inlet from  
Domestic supply  
Hot Outlet  
Upper element to 130°F [54°C]  
(or owner preference)  
Shut-off  
WARNING! ꢀ  
Valve #1  
Shut-off  
WARNING! A 150°F SETPOINT MAY LEAD TO  
SCALDING OR BURNS. THE 150°F SET POINT MUST  
ONLY BE USED ON SYSTEMS THAT EMPLOY AN  
APPROVED ANTI-SCALD VALVE.  
Valve #4  
Powered  
Water Heater  
Lower element to 120°F [49°C]  
Unpowered  
Water Heater  
Shut-off  
Valve #3  
Shut Off  
Valve #2  
Field Supplied 3/4” brass nipple and “T”  
Insulated water lines - 5/8” OD, 50 ft maximum (one way)  
[16mm OD, 15 meters maximum]  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Hot Water Generator  
ANTI-SCALD  
VALVE PIPING  
CONNECTIONS  
Installation  
COLD WATER  
SUPPLY  
The HWG is controlled by two sensors and a microprocessor  
control. One sensor is located on the compressor discharge  
line to sense the discharge refrigerant temperature. The  
other sensor is located on the HWG heat exchanger’s “Water  
In” line to sense the potable water temperature.  
CHECK VALVE  
ANTI-SCALD  
VALVE  
ѥꢀWARNING! ѥ  
C
WARNING! UNDER NO CIRCUMSTANCES SHOULD  
THE SENSORS BE DISCONNECTED OR REMOVED  
AS FULL LOAD CONDITIONS CAN DRIVE HOT  
WATER TANK TEMPERATURES FAR ABOVE SAFE  
TEMPERATURE LEVELS IF SENSORS HAVE BEEN  
DISCONNECTED OR REMOVED.  
HOT WATER  
TO HOUSE  
M
H
The microprocessor control monitors the refrigerant and  
water temperatures to determine when to operate the HWG.  
The HWG will operate any time the refrigerant temperature  
is sufÄciently above the water temperature. Once the  
HWG has satisÄed the water heating demand during a  
heat pump run cycle, the controller will cycle the pump at  
regular Intervals to determine if an additional HWG cycle  
can be utilized. The microprocessor control Includes 3 DIP  
switches, SW10 (HWG PUMP TEST), SW11 (HWG TEMP),  
and SW12 (HWG STATUS).  
WATER HEATER  
SW10 HWG PUMP TEST. When this switch is in the “ON”  
position, the HWG pump is forced to operate even if there  
is no call for the HWG. This mode may be beneÄcial to  
assist in purging the system of air during Initial start up.  
When SW10 is in the OFF” position, the HWG will operate  
normally. This switch is shipped from the factory in the  
OFF” (normal) position. NOTE; If left in the On” position for  
5 minutes, the pump control will revert to normal operation.  
125°F. This switch Is shipped from the factory in the “OFF”  
(125°F) position.  
SW12 HWG STATUS. This switch controls operation of  
the HWG. When SW12 is in the ON” position the HWG is  
disabled and will not operate. When SW12 is in the “OFF”  
position the HWG is in the enabled mode and will operate  
normally. This switch is shipped from the factory in the  
ON” (disabled) position. CAUTION: DO NOT PLACE THIS  
SWITCH IN THE ENABLED POSITION UNITL THE HWG  
PIPING IS CONNECTED, FILLED WITH WATER, AND  
PURGED OR PUMP DAMAGE WILL OCCUR.  
SW11 HWG TEMP. The control setpoint of the HWG can  
be set to either of two temperatures, 125°F or 150°F. When  
SW11 is in the ON” position the HWG setpoint is 150°F.  
When SW11 is in the OFF” position the HWG setpoint is  
When the control is powered and the HWG pump output  
is not active, the status LED (AN1) will be “On”. When the  
HWG pump output is active for water temperature sampling  
or HWG operation, the status LED will slowly Åash (On 1  
second, Off 1 second).  
ѥꢀWARNING! ѥ  
WARNING! USING A 150°F SETPOINT ON THE  
HWG WILL RESULT IN WATER TEMPERATURES  
SUFFICIENT TO CAUSE SEVERE PHYSICAL INJURY  
IN THE FORM OF SCALDING OR BURNS, EVEN  
WHEN THE HOT WATER TANK TEMPERATURE  
SETTING IS VISIBLY SET BELOW 150°F. THE 150°F  
HWG SETPOINT MUST ONLY BE USED ON SYSTEMS  
THAT EMPLOY AN APPROVED ANTI-SCALD VALVE  
(PART NUMBER AVAS4) AT THE HOT WATER  
STORAGE TANK WITH SUCH VALVE PROPERLY  
SET TO CONTROL WATER TEMPERATURES  
DISTRIBUTED TO ALL HOT WATER OUTLETS AT A  
TEMPERATURE LEVEL THAT PREVENTS SCALDING  
OR BURNS!  
If the control has detected a fault, the status LED will Åash a  
numeric fault code as follows:  
Hot Water Sensor Fault  
1 Åash  
Compressor Discharge sensor fault  
High Water Temperature (>160ºF)  
Control Logic Error  
2 Åashes  
3 Åashes  
4 Åashes  
Fault code Åashes have a duration of 0.4 seconds with  
a 3 second pause between fault codes. For example, a  
Compressor Discharge sensor fault” will be four Åashes  
0.4 seconds long, then a 3 second pause, then four Åashes  
again, etc.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Hot Water Generator  
insure maximum utilization of the heat available from the  
Warning! The HWG pump Is fully wired from the factory. Use  
extreme caution when working around the microprocessor  
control as it contains line voltage connections that presents  
a shock hazard that can cause severe injury or death!  
refrigeration system and conserve the most energy. On tanks  
with both upper and lower elements and thermostats, the  
lower element should be turned down to 100°F [38°C] or  
the lowest setting; the upper element should be adjusted to  
120-130°F [49-54°C]. Depending upon the specic needs  
of the customer, you may want to adjust the upper element  
differently. On tanks with a single thermostat, a preheat tank  
should be used (Fig 15).  
The heat pump, water piping, pump, and hot water tank should  
be located where the ambient temperature does not fall below  
50°F [10°C]. Keep water piping lengths at a minimum. DO NOT  
use a one way length greater than 50 ft. (one way) [15 m]. See  
Table 7 for recommended piping sizes and maximum lengths.  
6. Replace access cover(s) and restore power or  
fuel supply.  
All installations must be in accordance with local codes. The  
installer is responsible for knowing the local requirements, and  
for performing the installation accordingly. DO NOT connect the  
pump wiring until “Initial Start-Up” section, below. Powering the  
pump before all installation steps are completed may damage the  
pump.  
Initial Start-Up  
1. Make sure all valves in the HWG water circuit are  
fully open.  
2. Turn on the heat pump and allow it to run for  
10-15 minutes.  
3. Set SW12 to the OFF” position (enabled) to engage the  
HWG.  
Water Tank Preparation  
4. The HWG pump should not run if the compressor is not  
running.  
5. The temperature difference between the water entering and  
leaving the HWG coil should be approximately 5-10°F [3-  
6°C].  
1. Turn off power or fuel supply to the hot water tank.  
2. Connect a hose to the drain valve on the water tank.  
3. Shut off the cold water supply to the water tank.  
4. Open the drain valve and open the pressure relief valve or a  
hot water faucet to drain tank.  
6. Allow the unit to operate for 20 to 30 minutes to insure that it  
is functioning properly.  
5. When using an existing tank, it should be ushed with cold  
water after it is drained until the water leaving the drain hose  
is clear and free of sediment.  
6. Close all valves and remove the drain hose.  
7. Install HWG water piping.  
HWG Water Piping  
Table 7: HWG Water Piping Sizes and Length  
1. Using at least 5/8” [16mm] O.D. copper, route and install the  
water piping and valves as shown in Figures 14 or 15. Install  
an approved anti-scald valve if the 150°F HWG setpoint is or  
will be selected. An appropriate method must be employed  
to purge air from the HWG piping. This may be accomplished  
by ushing water through the HWG (as In Figures 14 and  
15) or by Installing an air vent at the high point of the HWG  
piping system.  
2. Insulate all HWG water piping with no less than 3/8” [10mm]  
wall closed cell insulation.  
3. Open both shut off valves and make sure the tank drain valve  
is closed.  
Unit  
Nominal  
1/2" Copper  
(max length*) (max length*)  
3/4" Copper  
Nominal HWG Flow  
Tonnage  
1.5  
(gpm)  
0.6  
50  
50  
50  
50  
50  
45  
25  
10  
-
-
2.0  
0.8  
2.5  
1.0  
-
3.0  
1.2  
-
3.5  
1.4  
-
4.0  
1.6  
50  
50  
50  
5.0  
2.0  
6.0  
2.4  
Water Tank Rell  
1. Close valve #4. Ensure that the HWG valves (valves #2 and  
#3) are open. Open the cold water supply (valve #1) to ll the  
tank through the HWG piping. This will purge air from the  
HWG piping.  
*Maximum length is equivalent length (in feet) one way of type L copper.  
2. Open a hot water faucet to vent air from the system until  
water ows from faucet; turn off faucet. Open valve #4.  
3. Depress the hot water tank pressure relief valve handle to  
ensure that there is no air remaining in the tank.  
4. Inspect all work for leaks.  
5. Before restoring power or fuel supply to the water heater,  
adjust the temperature setting on the tank thermostat(s) to  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Electrical - Line Voltage  
WARNING! ꢀ  
CAUTION! ꢀ  
WARNING! To avoid possible injury or death due to electrical  
shock, open the power supply disconnect switch and secure it  
in an open position during installation.  
CAUTION! Use only copper conductors for eld installed  
electrical wiring. Unit terminals are not designed to accept other  
types of conductors.  
Table 4a: HT Series Electrical Data  
All HTUnits with Emerson ECM Fan Motor  
HT Units (ECM) Standard  
Ext  
Max  
Compressor  
HWG  
Pump  
FLA  
Fan  
Motor  
FLA  
Total  
Unit  
FLA  
Min  
Circuit  
Amps  
Loop  
Pump  
FLA  
Fuse/  
HACR  
(2)  
Model  
RLA  
LRA  
Qty  
11.7  
15.3  
58.3  
83.0  
1
1
1
1
1
0.5  
0.5  
0.5  
0.5  
0.5  
1.7  
1.7  
1.7  
1.7  
1.7  
3.9  
3.9  
6.9  
6.9  
6.9  
16.1  
19.7  
28.6  
34.5  
37.1  
19.0  
23.5  
33.9  
41.2  
44.5  
30  
35  
50  
60  
70  
024  
036  
048  
21.2 104.0  
27.1 152.9  
29.7 179.2  
060  
070  
Rated Voltage of 208-230/60/1  
HACR circuit breaker in USA only  
Min/Max Voltage of 197/254  
All fuses Class RK-5  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Electrical - Line Voltage  
Figure 16: HT Single Phase Line Voltage  
Field Wiring  
WARNING! ꢀ  
WARNING! Disconnect electrical power source to prevent  
injury or death from electrical shock.  
CAUTION! ꢀ  
CAUTION! Use only copper conductors for eld installed  
electrical wiring. Unit terminals are not designed to accept  
other types of conductors.  
Electrical - Line Voltage  
All eld installed wiring, including electrical ground, must comply  
with the National Electrical Code as well as all applicable local  
codes. Refer to the unit electrical data for fuse sizes. Consult  
wiring diagram for eld connections that must be made by the  
installing (or electrical) contractor.  
All nal electrical connections must be made with a length of  
exible conduit to minimize vibration and sound transmission to  
the building.  
General Line Voltage Wiring  
Unit Power Supply  
(see electrical table for wire  
and breaker size)  
Be sure the available power is the same voltage and phase shown  
on the unit serial plate. Line and low voltage wiring must be done  
in accordance with local codes or the National Electric Code,  
whichever is applicable.  
Special Note for AHRI Testing: To achieve rated airow for  
AHRI testing purposes on all PSC products, it is necessary to  
change the fan speed to “HI” speed. When the heat pump has  
experienced less than 100 operational hours and the coil has  
not had sufcient time to be “seasoned”, it is necessary to clean  
the coil with a mild surfactant such as Calgon to remove the oils  
left by manufacturing processes and enable the condensate to  
properly “sheet” off of the coil.  
Power Connection  
Line voltage connection is made by connecting the incoming line  
voltage wires to the “L” side of the contactor as shown in Figure  
16. Consult Tables 4a through 4b for correct fuse size.  
208 Volt Operation  
All residential 208-230 Volt units are factory wired for 230 Volt  
operation. The transformer may be switched to the 208V tap as  
illustrated on the wiring diagram by switching the red (208V) and  
the orange (230V) wires at the contactor terminal.  
Figure 17: PSC Motor Speed Selection  
Connect the blue wire to:  
H for High speed fan  
M for Medium speed fan  
L for Low speed fan  
Blower Speed Selection – Units with PSC Motor  
PSC (Permanent Split Capacitor) blower fan speed can be  
changed by moving the blue wire on the fan motor terminal  
block to the desired speed as shown in Figure 17. Optional ECM  
motor speeds are set via low voltage controls (see “ECM Blower  
Control”). Most units are shipped on the medium speed tap.  
Consult specications catalog for specic unit airow tables.  
Typical unit design delivers rated airow at nominal static (0.15 in.  
w.g. [37Pa]) on medium speed and rated airow at a higher static  
(0.4 to 0.5 in. w.g. [100 to 125 Pa]) on high speed for applications  
where higher static is required. Low speed will deliver  
Medium is factory setting  
Fan Motor  
HWG Wiring (Split Units Only)  
The hot water generator pump power wiring is disabled at the  
factory to prevent operating the HWG pump “dry.” After all HWG  
piping is completed and air purged from the water piping, the  
pump power wires should be applied to terminals on the HWG  
power block PB2 as shown in the unit wiring diagram. This  
connection can also serve as a HWG disable when servicing the  
unit.  
approximately 85% of rated airow at 0.10 in. w.g. [25 Pa].  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Electrical - Low Voltage Wiring  
Thermostat Connections  
Low Water Temperature Cutout Selection  
The thermostat should be wired directly to the CXM board  
(units with PSC fan). Units with optional ECM motor include  
factory wiring from the CXM board to the ECM interface  
board. Thermostat wiring for these units should be connected  
to the ECM interface board. Figure 18 shows wiring for
The CXM control allows the Äeld selection of low water (or  
water-antifreeze solution) temperature limit by clipping jumper  
JW3, which changes the sensing temperature associated with  
thermistor FP1. Note that the FP1 thermistor is located on  
the refrigerant line between the coaxial heat exchanger and  
expansion device (TXV). Therefore, FP1 is sensing refrigerant  
temperature, not water temperature, which is a better indication  
of how water Åow rate/temperature is affecting the refrigeration  
circuit.  
units with PSC or optional ECM motor. See Electrical –  
HT  
Thermostat” for speciÄc terminal connections.  
Figure 18:
HT Low Voltage Field Wiring  
The factory setting for FP1 is for systems using water (30°F  
[-1.1°C] refrigerant temperature). In low water temperature  
(extended range) applications with antifreeze (most ground  
loops), jumper JW3 should be clipped as shown in Figure  
19 to change the setting to 10°F [-12.2°C] refrigerant  
temperature, a more suitable temperature when using  
an antifreeze solution. All residential units include water/  
refrigerant circuit insulation to prevent internal condensation,  
which is required when operating with entering water  
temperatures below 59°F [15°C].  
Low voltage  
Äeld wiring  
for units with  
PSC FAN  
(ECM board  
will not be  
present)  
Figure 19: FP1 Limit Setting  
Low voltage Äeld wiring for units with ECM fan  
JW3-FP1  
jumper should  
be clipped for  
low temperature  
operation  
CXM PCB  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Electrical - Low Voltage Wiring  
Accessory Connections  
Figure 23 illustrates piping for two-stage solenoid valves. Review  
gures 20-22 for wiring of stage one valve. Stage two valve should  
be wired between terminal “Y2” (ECM board) and terminal “C.”  
A terminal paralleling the compressor contactor coil has been  
provided on the CXM control. Terminal “A” is designed to control  
accessory devices, such as water valves. Note: This terminal  
should be used only with 24 Volt signals and not line voltage.  
Terminal “A” is energized with the compressor contactor. See  
Figure 20 or the specic unit wiring diagram for details.  
Note: When EWT is below 50°F [10°C], a minimum of 2 gpm per  
ton (2.6 l/m per kW) is required.  
Figure 21: AVM Valve Wiring  
Figure 20: Accessory Wiring  
2
AVM  
Taco Valve  
3
1
Heater Switch  
Water Solenoid Valves  
An external solenoid valve(s) should be used on ground water  
installations to shut off ow to the unit when the compressor  
is not operating. A slow closing valve may be required to help  
reduce water hammer. Figure 20 shows typical wiring for a  
24VAC external solenoid valve. Figures 21 and 22 illustrate  
typical slow closing water control valve wiring for Taco 500 series  
(Manufacturer P/N AVM...) and Taco SBV series valves. Slow  
closing valves take approximately 60 seconds to open (very little  
water will ow before 45 seconds). Once fully open, an end switch  
allows the compressor to be energized. Only relay or triac based  
electronic thermostats should be used with slow closing valves.  
When wired as shown, the slow closing valve will operate properly  
with the following notations:  
Thermostat  
Figure 22: Taco SBV Valve Wiring  
1. The valve will remain open during a unit lockout.  
2. The valve will draw approximately 25-35 VA through the “Y”  
signal of the thermostat. Note: This valve can overheat the  
anticipator of an electromechanical thermostat. Therefore,  
only relay or triac based thermostats should be used.  
Two-stage Units  
Figure 23: Two-Stage Piping  
HT two-stage units should be designed with two parallel valves  
for ground water applications to limit water use during rst stage  
operation. For example, at 1.5 gpm/ ton [2.0 l/m per kW], a 048  
unit requires 6 gpm [23 l/m] for full load (2nd stage) operation,  
but only 4 gpm [15 l/m] during 1st stage operation. Since the unit  
will operate on rst stage 80-90% of the time, signicant water  
savings can be realized by using two parallel solenoid valves with  
two ow regulators. In the example above, stage one solenoid  
would be installed with a 4 gpm [15 l/m] ow regulator on the  
outlet, while stage two would utilize a 2 gpm [8 l/m] ow regulator.  
When stage one is operating, the second solenoid valve will be  
closed. When stage two is operating, both valves will be open,  
allowing full load ow rate.  
Solenoid  
Valve  
Flow  
Regulator  
Stage 2  
To Discharge  
OUT  
IN  
Stage 1  
From Water Source  
NOTE: Shut-off valves, strainers and  
other required components not shown.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Electrical - Thermostat Wiring  
Figure 24: Units With Optional ECM Fan.  
ѥꢀCAUTION! ѥ  
Connection to ECM Control  
Thermostat  
CAUTION! Many units are installed with a factory or ¿eld  
supplied manual or electric shut-off valve. DAMAGE  
WILL OCCUR if shut-off valve is closed during unit  
operation. A high pressure switch must be installed on  
the heat pump side of any ¿eld provided shut-off valves  
and connected to the heat pump controls in series with  
the built-in refrigerant circuit high pressure switch to  
disable compressor operation if water pressure exceeds  
pressure switch setting. The ¿eld installed high pressure  
switch shall have a cut-out pressure of 300 psig and a  
cut-in pressure of 250 psig. This pressure switch can  
ECM  
Board  
Y1  
Y2  
W
Compressor  
Compressor Stage 2  
Auxiliary Heat  
Y1  
Y2  
W
Dehumidification DH  
DH  
O
Reversing Valve  
Fan  
O
G
R
C
L
G
R
24Vac Hot  
24Vac Common  
Fault LED  
be ordered from with a 1/4” internal Àare  
Manufacturer  
C
connection as part number 39B0005N02.  
AL1  
ѥꢀCAUTION! ѥ  
Units with CXM or DXM board and ECM fan motor, utilizing ECM dehumidication mode  
CAUTION! Refrigerant pressure activated water regulating  
Notes:  
Manufacturer  
valves should never be used with
equipment.  
1) ECM dehumidication mode slows down fan speed in the cooling mode when  
dehumidication output from thermostat is active. Normal heating and cooling fan  
speeds are not affected.  
2) ECM board DIP switch SW9 must be in dehumid. mode for ECM dehumidication mode.  
Thermostat Installation  
The thermostat should be located on an interior wall in a  
larger room, away from supply duct drafts. DO NOT locate  
the thermostat in areas subject to sunlight, drafts or on  
external walls. The wire access hole behind the thermostat  
may in certain cases need to be sealed to prevent erroneous  
temperature measurement. Position the thermostat back  
plate against the wall so that it appears level and so the  
thermostat wires protrude through the middle of the back  
plate. Mark the position of the back plate mounting holes  
and drill holes with a 3/16” (5mm) bit. Install supplied  
anchors and secure plate to the wall. Thermostat wire must  
be 18 AWG wire. Wire the appropriate thermostat as shown  
in Figures 24 and 25 to the low voltage terminal strip on the  
CXM (units with PSC motor) or ECM control board (units  
with ECM motor). Practically any heat pump thermostat will  
work with these units, provided it has the correct number of  
heating and cooling stages.  
Figure 25: Typical Thermostat 2 Heat/1 Cool (PSC Fan)  
Connection to CXM Control  
1 Thermostat  
CXM  
Y
Y2/W  
O
Y
W
O
Compressor  
Heating Stage 2  
Reversing Valve  
Fan  
G
G
24Vac Hot  
R
R
24Vac Common  
Fault LED  
C
C
L
AL1  
NOTICE: Units with ClimaDry whole house dehumidiÄcation  
option require a separate humidistat or thermostat part  
number ATP32U04 (See ClimaDry AOM for more details).  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
ECM Blower Control  
The ECM fan is controlled by an interface board that converts  
thermostat inputs and eld selectable CFM settings to signals  
used by the ECM motor controller. Units manufactured before  
July 2005 have version I (P/N 69243707). Units manufactured  
after July 2005 have version II (P/N 17B0019N01). Fan speeds  
are selected with jumpers for version I or via a nine position DIP  
switch for version II. To take full advantage of the ECM motor  
features, a multi-stage thermostat should be used (2-stage  
heat/2-stage cool or 3-stage heat/2-stage cool).  
operating in the normal mode, the cooling airow settings  
are determined by the cooling tap setting above. When  
dehumidication is enabled there is a reduction in airow  
in cooling to increase the moisture removal of the heat pump.  
Consult submittal data or specications catalog for the specic  
unit series and model to correlate speed tap to airow in CFM.  
The dehumidication mode can be enabled in two ways.  
1. Constant Dehumidication Mode: When the dehumidication  
mode is selected (via DIP switch or jumper setting), the ECM  
motor will operate with a multiplier applied to the cooling  
CFM settings (approx. 20-25% lower airow). Any time the  
unit is running in the cooling mode, it will operate at the lower  
airow to improve latent capacity. The “DEHUM” LED will be  
illuminated at all times. Heating airow is not affected. NOTE:  
Do not select dehumidication mode if cooling setting is tap 1.  
HFC-410A packaged units built after May 2009 have ECM  
controller version III (P/N 17B0034N01). This controller includes  
logic and a relay to control the HWG functions.  
Note: Power must be off to the unit for at least three seconds  
before the ECM motor will recognize a speed change. The motor  
will recognize a change in the CFM Adjust or dehumidication  
mode settings while the unit is powered.  
2. Automatic (Humidistat-controlled) Dehumidication Mode:  
When the dehumidication mode is selected (via DIP switch  
or jumper setting) AND a humidistat is connected to terminal  
DH (version II) or HUM (version I), the cooling airow will  
only be reduced when the humidistat senses that additional  
dehumidication is required. The DH (or HUM) terminal is  
reverse logic. Therefore, a humidistat (not dehumidistat) is  
required. The “DEHUM” LED will be illuminated only when  
the humidistat is calling for dehumidication mode. Heating  
airow is not affected. NOTE: Do not select dehumidication  
mode if cooling setting is tap 1.  
There are four different airow settings from lowest airow rate  
(speed tap 1) to the highest airow rate (speed tap 4). The charts  
below indicate settings for both versions of the ECM interface  
board, followed by detailed information for each setting.  
Cooling Settings: The cooling setting determines the cooling  
(normal) CFM for all units with ECM motor. Cooling (normal)  
setting is used when the unit is not in dehumidication mode.  
Tap 1 is the lowest CFM setting, while tap 4 is the highest CFM  
setting. To avoid air coil freeze-up, tap 1 may not  
be used if the dehumidication mode is selected. Consult  
submittal data or specications catalog for the specic unit series  
and model to correlate speed tap setting to airow in CFM.  
Heating Settings: The heating setting determines the heating  
CFM for HT units. Tap 1 is the lowest CFM setting, while tap 4 is  
the highest CFM setting. Consult submittal data or specications  
catalog for the specic unit series and model to correlate speed  
tap setting to airow in CFM.  
Auxiliary/Emergency Heat Settings: The auxiliary/emergency  
heat setting determines the CFM when the unit is in auxiliary  
heat or emergency heat mode. This setting is used for residential  
units with internal electric heat. When auxiliary electric heat is  
energized (i.e. compressor and electric heat), the greater of the  
auxiliary/emergency or heating setting will be used. A “G” (fan)  
signal must be present from the thermostat for electric heat to  
operate. Consult the submittal data or specications catalog for  
the specic unit series and model to correlate speed tap setting to  
airow in CFM.  
CFM Adjust Settings: The CFM adjust setting allows four  
selections. The NORM setting is the factory default position. The  
+ or – settings adjust the airow by +/- 15%. The +/- settings are  
used to “ne tune” airow adjustments. The TEST setting runs the  
ECM motor at 70% torque, which causes the motor to operate like  
a standard PSC motor, and disables the CFM counter.  
Dehumidication Mode Settings: The dehumidication mode  
setting provides eld selection of humidity control. When  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
ECM Blower Control  
Table 5: ECM Board Tap Settings  
Cooling settings:
Heating settings:
Aux/Emerg Heat settings:
HT Units  
HT Units  
HT Units  
Version I  
69243707  
Version I  
69243707  
Version I  
69243707  
Version II and III  
Version II and III  
Version II and III  
(17B0019N01 & 17B0034N01)  
(17B0019N01 & 17B0034N01)  
(17B0019N01 & 17B0034N01)  
Tap  
HP CFM  
DIP Switch  
Tap  
DIP Switch  
Tap  
AUX CFM  
DIP Switch  
DELAY  
Setting  
Jumper  
SW1  
ON  
ON  
OFF  
OFF  
SW2  
ON  
OFF  
ON  
Setting  
Jumper  
SW3  
ON  
ON  
OFF  
OFF  
SW4  
ON  
OFF  
ON  
Setting  
Jumper  
SW5  
ON  
ON  
OFF  
OFF  
SW6  
ON  
OFF  
ON  
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
OFF  
OFF  
OFF  
*Residential Units  
CFM Adjust settings:
Dehum Mode settings:
HT Units  
HT Units  
Version I  
69243707  
CFM Adj  
Jumper  
Version I  
69243707  
Dehumid  
Jumper  
pins 1,2  
Version II and III  
Version II and III  
(17B0019N01 & 17B0034N01)  
(17B0019N01 & 17B0034N01)  
Tap  
Setting  
TEST  
-
+
DIP Switch  
Tap  
DIP Switch  
SW9  
SW7  
SW8  
Setting  
NORM  
Dehumid  
1
2
3
4
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
OFF  
ON  
OFF  
pins 2,3  
NORM  
Figure 26a: ECM Version II Interface Layout  
Figure 26b: ECM Version I Interface Layout  
1/4" Spade  
Connections  
to CXM or  
DXM Board  
1/4" Spade  
Connections  
to CXM or  
Thermostat  
Input LEDs  
G
G
G
G
R
A
L
DXM Board  
Thermostat  
Input LEDs  
G
Y1 Y2  
O
W1 EM  
C
R
CFM Counter  
1 flash per 100CF  
CFM Counter  
1 flash per 100 CFM  
LED's  
CFM  
Thermostat  
Thermostat  
Connections  
Connections  
Y
ECM Motor  
Low Voltage  
Connector  
ECM Motor  
Low Voltage  
Connector  
J01  
G
Dehumidification  
LED  
Dehumidification  
LED  
Fan Speed Selection DIP Switch  
Fan Speed Selection Jumpers  
Figure 26c: ECM Version III Interface Layout  
&RPSUHVVRU  
'LVFKDUJHꢀ6HQVRU  
'HKXPLGLILFDWLRQ  
+RWꢀ:DWHUꢀ6HQVRU /('  
+:*ꢀ/('  
ꢁꢂꢃꢄꢀ6SDGH  
&RQQHFWLRQV  
WRꢀ&;0ꢀRU  
&&  
(&0ꢀ0RWRU  
/RZ 9ROWDJH  
&RQQHFWRU  
';0ꢀ%RDUG  
5
&
*
:
2
5
*
*
*
*
+:*ꢀ3XPS  
5HOD\  
<ꢀ  
<ꢁ  
*
<
*
<ꢀ <ꢁ  
',3ꢀ6ZLWFKHV  
*
2
:
&
5
'+ $/ꢁ $  
$/ꢀ  
$
7KHUPRVWDW  
&RQQHFWLRQV  
&)0ꢀ&RXQWHU  
ꢁꢀIODVKꢀSHUꢀꢁꢅꢅꢀ&)0  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
HT Series ECM Blower Performance Data  
Residential  
Units Only  
Airow in CFM with wet coil and clean air lter  
Dehumid  
Mode  
Cooling Mode  
Heating Mode  
Max  
ESP  
(in. wg)  
Fan  
Motor  
(hp)  
Fan  
Only  
Mode  
Aux/  
Emerg  
Mode  
Model  
Range  
Stg 1 Stg 2 Stg 1 Stg 2 Stg 1 Stg 2  
Default  
Maximum  
Minimum  
Default  
700  
1000  
600  
525  
800  
550  
800  
425  
600  
750  
1000  
600  
600  
850  
350  
1000  
300  
850  
024  
1.0  
0.9  
1.0  
0.7  
0.7  
1/2  
1/2  
1
1000  
700  
450  
550  
400  
450  
1050  
1500  
900  
800  
850  
650  
1100  
1500  
900  
850  
550  
1350  
1500  
1350  
1500  
2000  
1350  
1875  
2300  
1500  
2000  
2300  
1800  
036  
Maximum  
Minimum  
Default  
1100  
600  
1200  
825  
900  
1100  
600  
1500  
450  
550  
1400  
2000  
1200  
1750  
2300  
1500  
1900  
2300  
1800  
1050  
1500  
900  
1100  
1600  
1100  
1400  
2000  
1375  
1650  
2000  
1650  
850  
1500  
2000  
1200  
1875  
2300  
1500  
2000  
2300  
1800  
1150  
1500  
900  
700  
048  
Maximum  
Minimum  
Default  
1200  
825  
2000  
600  
1300  
1900  
1100  
1450  
2200  
1350  
1050  
1500  
1000  
1250  
1800  
1250  
1450  
1900  
1100  
1650  
2200  
1350  
875  
060  
1
Maximum  
Minimum  
Default  
2300  
750  
950  
070  
1
Maximum  
Minimum  
2300  
900  
During Auxiliary operation (residential units only) the CFM will run at the higher if the heating (delay jumper) or AUX settings  
Airow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1” berglass lter  
Do not select Dehumidication mode if HP CFM is on setting 1  
All units AHRI/ISO/ASHRAE 13256-1 rated HP (Cooling) Delay (Heating) CFM Setting 3  
Note: See the ECM Blower Control section for information on setting taps.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
CXM Controls  
CXM Control  
On = EH2 Normal. Off = DDC Output at EH2.  
For detailed control information, see CXM Application, Operation  
and Maintenance (AOM) manual (part #97B0003N12).  
NOTE: Some CXM controls only have a 2 position DIP switch  
package. If this is the case, this option can be selected by  
clipping the jumper which is in position 4  
Field Selectable Inputs  
of SW1.  
Test mode: Test mode allows the service technician to check  
the operation of the control in a timely manner. By momentarily  
shorting the test terminals, the CXM control enters a 20 minute  
test mode period in which all time delays are sped up 15 times.  
Upon entering test mode, the status LED will ash a code  
representing the last fault. For diagnostic ease at the thermostat,  
the alarm relay will also cycle during test mode. The alarm relay  
will cycle on and off similar to the status LED to indicate a code  
representing the last fault, at the thermostat. Test mode can be  
exited by shorting the test terminals for 3 seconds.  
Jumper not clipped = EH2 Normal. Jumper clipped = DDC  
Output at EH2.  
DIP switch 5: Factory Setting - Normal position is “On.” Do not  
change selection unless instructed to do so by the factory.  
Table 6a: CXM LED And Alarm Relay Operations  
Description of Operation  
Normal Mode  
LED  
On  
Alarm Relay  
Open  
Normal Mode with UPS Warning  
CXM is non-functional  
Fault Retry  
On  
Cycle (closed 5 sec., Open 25 sec.)  
Off  
Open  
Slow Flash  
Fast Flash  
Slow Flash  
Open  
Closed  
Retry Mode: If the control is attempting a retry of a fault,  
the status LED will slow ash (slow ash = one ash every 2  
seconds) to indicate the control is in the process of retrying.  
Lockout  
Over/Under Voltage Shutdown  
Open (Closed after 15 minutes)  
Test Mode - No fault in memory Flashing Code 1  
Test Mode - HP Fault in memory Flashing Code 2  
Test Mode - LP Fault in memory Flashing Code 3  
Test Mode - FP1 Fault in memory Flashing Code 4  
Test Mode - FP2 Fault in memory Flashing Code 5  
Test Mode - CO Fault in memory Flashing Code 6  
Cycling Code 1  
Cycling Code 2  
Cycling Code 3  
Cycling Code 4  
Cycling Code 5  
Cycling Code 6  
Cycling Code 7  
Field Conguration Options  
Note: In the following eld conguration options, jumper wires  
should be clipped ONLY when power is removed from the CXM  
control.  
Water coil low temperature limit setting: Jumper 3 (JW3-FP1 Low  
Temp) provides eld selection of temperature  
limit setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant  
temperature).  
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].  
Air coil low temperature limit setting: Jumper 2 (JW2-FP2 Low  
Temp) provides eld selection of temperature limit setting for  
FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).  
Note: This jumper should only be clipped under extenuating  
circumstances, as recommended by  
Test Mode - Over/Under  
Flashing Code 7  
shutdown in memory  
Test Mode - UPS in memory  
Flashing Code 8  
Cycling Code 8  
Cycling Code 9  
Test Mode - Swapped Thermistor Flashing Code 9  
-Flash code 2 = 2 quick ashes, 10 second pause, 2 quick  
ashes, 10 second pause, etc.  
-On pulse 1/3 second; off pulse 1/3 second  
the factory.  
Figure 27: Test Mode Pins  
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].  
Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides eld  
selection of the alarm relay terminal AL2 to be jumpered to 24VAC  
or to be a dry contact (no connection).  
Short test pins  
together to enter Test  
Mode and speed-up  
timing and delays for  
20 minutes.  
Not Clipped = AL2 connected to R. Clipped = AL2 dry contact  
(no connection).  
DIP Switches  
Note: In the following eld conguration options, DIP switches  
should only be changed when power is removed from the CXM  
control.  
DIP switch 1: Unit Performance Sentinel Disable - provides eld  
selection to disable the UPS feature.  
On = Enabled. Off = Disabled.  
DIP switch 2: Stage 2 Selection - provides selection of whether  
compressor has an “on” delay. If set to stage 2, the compressor  
will have a 3 second delay before energizing. Also, if set for stage  
2, the alarm relay will NOT cycle during test mode.  
On = Stage 1. Off = Stage 2  
DIP switch 3: Not Used.  
DIP switch 4: DDC Output at EH2 - provides selection for DDC  
operation. If set to “DDC Output at EH2,” the EH2 terminal will  
continuously output the last fault code of the controller. If set to  
EH2 normal,” EH2 will operate as standard electric heat output.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
CXM Controls  
Safety Features – CXM Control  
fault. The FP2 input is bypassed for the initial 120 seconds of a  
compressor run cycle. FP2 is set at the factory for one try. Therefore,  
the control will go into lockout mode once the FP2 fault has occurred.  
FP2 lockout code = 5  
Condensate overow: The condensate overow sensor must  
sense overow level for 30 continuous seconds to be recognized  
as a CO fault. Condensate overow will be monitored at all times.  
CO lockout code = 6  
Over/under voltage shutdown: An over/under voltage condition  
exists when the control voltage is outside the range of 18VAC to  
31.5VAC. Over/under voltage shut down is a self-resetting safety.  
If the voltage comes back within range for at least 0.5 seconds,  
normal operation is restored. This is not considered a fault or  
lockout. If the CXM is in over/under voltage shutdown for 15  
minutes, the alarm relay will close.  
The safety features below are provided to protect the compressor,  
heat exchangers, wiring and other components from damage  
caused by operation outside of design conditions.  
Anti-short cycle protection: The control features a 5 minute anti-  
short cycle protection for the compressor.  
Note: The 5 minute anti-short cycle also occurs at power up.  
Random start: The control features a random start upon power up  
of 5-80 seconds.  
Fault Retry: In Fault Retry mode, the Status LED begins slowly  
ashing to signal that the control is trying to recover from a fault  
input. The control will stage off the outputs and then “try again”  
to satisfy the thermostat input call. Once the thermostat input call  
is satised, the control will continue on as if no fault occurred. If  
3 consecutive faults occur without satisfying the thermostat input  
call, the control will go into “lockout” mode. The last fault causing  
the lockout will be stored in memory and can be viewed by going  
into test mode. Note: FP1/FP2 faults are factory set at only one  
try.  
Over/under voltage shut down code = 7  
Unit Performance Sentinel-UPS (patent pending): The UPS feature  
indicates when the heat pump is operating inefciently. A UPS  
condition exists when:  
a) In heating mode with compressor energized, FP2 is greater  
than 125°F [52°C] for 30 continuous seconds, or:  
Lockout: In lockout mode, the status LED will begin fast ashing.  
The compressor relay is turned off immediately. Lockout mode can  
be “soft” reset by turning off the thermostat (or satisfying the call).  
A “soft” reset keeps the fault in memory but resets the control. A  
hard” reset (disconnecting power to the control) resets the control  
and erases fault memory.  
b) In cooling mode with compressor energized, FP1 is greater  
than 125°F [52°C] for 30 continuous seconds, or:  
c)  
In cooling mode with compressor energized, FP2 is less than  
40°F [4.5°C] for 30 continuous seconds. If a UPS condition  
occurs, the control will immediately go to UPS warning. The  
status LED will remain on as if the control is in normal mode.  
Outputs of the control, excluding LED and alarm relay, will NOT  
be affected by UPS. The UPS condition cannot occur during a  
compressor off cycle. During UPS warning, the alarm relay will  
cycle on and off. The cycle rate will be “on” for 5 seconds, “off”  
for 25 seconds, “on” for 5 seconds, “off” for 25 seconds, etc.  
Lockout with emergency heat: While in lockout mode, if W becomes  
active (CXM), emergency heat mode will occur.  
High pressure switch: When the high pressure switch opens due  
to high refrigerant pressures, the compressor relay is de-energized  
immediately since the high pressure switch is in series with the  
compressor contactor coil. The high pressure fault recognition is  
immediate (does not delay for 30 continuous seconds before de-  
energizing the compressor).  
High pressure lockout code = 2  
Example: 2 quick ashes, 10 sec pause, 2 quick ashes, 10 sec.  
pause, etc.  
Low pressure switch: The low pressure switch must be open and  
remain open for 30 continuous seconds during “on” cycle to be  
recognized as a low pressure fault. If the low pressure switch is open  
for 30 seconds prior to compressor power up it will be considered a  
low pressure (loss of charge) fault. The low pressure switch input is  
bypassed for the initial 60 seconds of a compressor run cycle.  
Low pressure lockout code = 3  
Water coil low temperature (FP1): The FP1 thermistor temperature  
must be below the selected low temperature limit setting for 30  
continuous seconds during a compressor run cycle to be recognized  
as a FP1 fault. The FP1 input is bypassed for the initial 120 seconds  
of a compressor run cycle. FP1 is set at the factory for one try.  
Therefore, the control will go into lockout mode once the FP1 fault  
has occurred.  
UPS warning code = 8  
Swapped FP1/FP2 thermistors: During test mode, the control  
monitors to see if the FP1 and FP2 thermistors are in the  
appropriate places. If the control is in test mode, the control will  
lockout, with code 9, after 30 seconds if:  
a) The compressor is on in the cooling mode and the FP1 sensor  
is colder than the FP2 sensor, or:  
b) The compressor is on in the heating mode and the FP2 sensor  
is colder than the FP1 sensor.  
Swapped FP1/FP2 thermistor code = 9.  
Diagnostic Features  
The LED on the CXM board advises the technician of the current  
status of the CXM control. The LED can display either the current  
CXM mode or the last fault in memory if in test mode. If there is no  
fault in memory, the LED will ash Code 1 (when in test mode).  
FP1 lockout code = 4  
Air coil low temperature (FP2): The FP2 thermistor temperature must  
be below the selected low temperature limit setting for 30 continuous  
seconds during a compressor run cycle to be recognized as a FP2  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
CXM Controls  
CXM Control Start-up Operation  
The control will not operate until all inputs and safety controls  
are checked for normal conditions. The compressor will have a  
5 minute anti-short cycle delay at power-up. The rst time after  
power-up that there is a call for compressor, the compressor will  
follow a 5 to 80 second random start delay. After the random start  
delay and anti-short cycle delay, the compressor relay will be  
energized. On all subsequent compressor calls, the random start  
delay is omitted.  
Table 6b: Unit Operation  
HT  
T-stat signal  
ECM fan  
G
Fan only  
G, Y or Y1  
G, Y1, Y2  
G, Y1, Y2, W  
G, W  
Stage 1 heating1  
Stage 2 heating1  
Stage 3 heating1  
Emergency heat  
Stage 1 cooling2  
Stage 2 cooling2  
G, Y or Y1, O  
G, Y1, Y2, O  
1
Stage 1 = 1st stage compressor, 1st stage fan operation  
Stage 2 = 2nd stage compressor, 2nd stage fan operation  
Stage 3 = 2nd stage compressor, auxiliary electric heat, 2nd  
or 3rd stage fan operation (depending on fan settings)  
2
3
Stage 1 = 1st stage compressor, 1st stage fan operation, reversing valve  
Stage 2 = 2nd stage compressor, 2nd stage fan operation, reversing valve  
Stage 1 = compressor, 1st stage fan operation  
Stage 2 = compressor, 2nd stage fan operation  
Stage 3 = compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings)  
Stage 1 = compressor, 1st stage fan operation, reversing valve  
Stage 2 = compressor, 2nd stage fan operation, reversing valve  
Stage 1 = compressor, fan  
Stage 2 = compressor, auxiliary electric heat, fan  
Cooling = compressor, fan, reversing valve  
4
5
6
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
CXM Controls  
Table 7: Nominal resistance at various temperatures  
CXM Thermostat Details  
Thermostat Compatibility - Most all heat pump thermostats can  
be used with the CXM control. However Heat/Cool stats are  
NOT compatible with the CXM.  
Resistance  
(kOhm)  
85.34  
84.00  
81.38  
61.70  
58.40  
55.30  
52.38  
49.64  
47.05  
44.61  
42.32  
40.15  
38.11  
36.18  
34.37  
32.65  
31.03  
29.50  
28.05  
26.69  
25.39  
24.17  
23.02  
21.92  
20.88  
19.90  
18.97  
18.09  
17.26  
16.46  
15.71  
15.00  
14.32  
13.68  
13.07  
12.49  
11.94  
11.42  
10.92  
10.45  
10.00  
9.57  
9.16  
8.78  
8.41  
8.06  
7.72  
7.40  
7.10  
6.81  
6.53  
6.27  
6.01  
5.77  
5.54  
5.33  
5.12  
4.92  
4.72  
4.54  
4.37  
4.20  
4.04  
3.89  
3.74  
3.60  
3.47  
3.34  
3.22  
3.10  
Resistance  
(kOhm)  
2.99  
2.88  
2.77  
2.67  
2.58  
2.49  
2.40  
2.32  
2.23  
2.16  
2.08  
2.01  
1.94  
1.88  
1.81  
1.75  
1.69  
1.64  
1.58  
1.53  
1.48  
1.43  
1.39  
1.34  
1.30  
1.26  
1.22  
1.18  
1.14  
1.10  
1.07  
1.04  
1.01  
0.97  
0.94  
0.92  
0.89  
0.86  
0.84  
0.81  
0.79  
0.76  
0.74  
0.72  
0.70  
0.68  
0.66  
0.64  
0.62  
0.60  
0.59  
0.57  
0.55  
0.54  
0.52  
0.51  
0.50  
0.48  
0.47  
0.46  
0.44  
0.43  
0.42  
0.41  
0.40  
0.39  
0.38  
0.37  
0.36  
Temp (ºC) Temp (ºF)  
Temp (ºC) Temp (ºF)  
-17.8  
-17.5  
-16.9  
-12  
-11  
-10  
-9  
0.0  
0.5  
1.5  
55  
56  
131.0  
132.8  
134.6  
136.4  
138.2  
140.0  
141.8  
143.6  
145.4  
147.2  
149.0  
150.8  
152.6  
154.4  
156.2  
158.0  
159.8  
161.6  
163.4  
165.2  
167.0  
168.8  
170.6  
172.4  
174.2  
176.0  
177.8  
179.6  
181.4  
183.2  
185.0  
186.8  
188.6  
190.4  
192.2  
194.0  
195.8  
197.6  
199.4  
201.2  
203.0  
204.8  
206.6  
208.4  
210.2  
212.0  
213.8  
215.6  
217.4  
219.2  
221.0  
222.8  
224.6  
226.4  
228.2  
230.0  
231.8  
233.6  
235.4  
237.2  
239.0  
240.8  
242.6  
244.4  
246.2  
248.0  
249.8  
251.6  
253.4  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
10.4  
12.2  
14.0  
15.8  
17.6  
19.4  
21.2  
23.0  
24.8  
26.6  
28.4  
30.2  
32.0  
33.8  
35.6  
37.4  
39.2  
41.0  
42.8  
44.6  
46.4  
48.2  
50.0  
51.8  
53.6  
55.4  
57.2  
59.0  
60.8  
62.6  
64.4  
66.2  
68.0  
69.8  
71.6  
73.4  
75.2  
77.0  
78.8  
80.6  
82.4  
84.2  
86.0  
87.8  
89.6  
91.4  
93.2  
95.0  
96.8  
98.6  
100.4  
102.2  
104.0  
105.8  
107.6  
109.4  
111.2  
113.0  
114.8  
116.6  
118.4  
120.2  
122.0  
123.8  
125.6  
127.4  
129.2  
Anticipation Leakage Current - Maximum leakage current for  
"Y" is 50 mA and for "W" is 20mA. Triacs can be used if leakage  
current is less than above. Thermostats with anticipators can be  
used if anticipation current is less than that specied above.  
-8  
-7  
-6  
-5  
-4  
-3  
-2  
-1  
0
1
2
3
4
5
6
7
Thermostat Signals -  
• "Y" and "W" have a 1 second recognition time when  
being activated or being removed.  
• "O" and "G" are direct pass through signals but are  
monitored by the micro processor.  
• "R" and "C" are from the transformer.  
• "AL1" and "AL2" originate from the alarm relay.  
• "A" is paralleled with the compressor output for use  
with well water solenoid valves.  
• The "Y" 1/4" quick connect is a connection point to the  
"Y" input terminal P1 for factory use. This "Y" terminal  
can be used to drive panel mounted relays such as the  
loop pump relay.  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Unit Commissioning And Operating Conditions  
Operating Limits  
Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels could  
cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).  
Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.  
Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water temperature, and 3)  
ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be at normal levels  
to insure proper unit operation. Extreme variations in temperature and humidity and/or corrosive water or air will adversely affect unit  
performance, reliability, and service life. Consult Table 8a for operating limits.  
Table 8a: Building Operating Limits  
UHnTit  
Operating Limits  
Cooling  
Heating  
Air Limits  
Min. ambient air, DB  
45ºF [7ºC]  
39ºF [4ºC]  
Rated ambient air, DB  
80.6ºF [27ºC]  
68ºF [20ºC]  
Max. ambient air, DB  
130ºF [54ºC]  
85ºF [29ºC]  
Min. entering air, DB/WB  
65/45ºF [18/7ºC]  
70/50ºF Reheat  
50ºF [10ºC]  
Rated entering air, DB/WB 80.6/66.2ºF [27/19ºC]  
68ºF [20ºC]  
100/75ºF [38/24ºC]  
80ºF [27ºC]  
Max. entering air, DB/WB  
Water Limits  
20ºF [-6.7ºC]  
Min. entering water  
20ºF [-6.7ºC]  
Normal entering water  
50-110ºF [10-43ºC]  
30-70ºF [-1 to 21ºC]  
Max. entering water  
120ºF [49ºC]  
120ºF [49ºC]  
[1.6 to 3.2 l/m per kW]  
1.5 to 3.0 gpm / ton  
Normal Water Flow  
Commissioning Conditions  
Consult Table 8b for the particular model. Starting conditions vary depending upon model and are based upon the following notes:  
Notes:  
1. Conditions in Table 8b are not normal or continuous operating conditions. Minimum/maximum limits are start-up conditions to bring  
the building space up to occupancy temperatures. Units are not designed to operate under these conditions on a regular basis.  
2. Voltage utilization range complies with AHRI Standard 110.  
Table 8b: Building Commissioning Limits  
H
T
Commissioning Limits  
Cooling  
Heating  
Air Limits  
Min. ambient air, DB  
Rated ambient air, DB  
Max. ambient air, DB  
Min. entering air, DB/WB  
Rated entering air, DB/WB 80.6/66.2ºF [27/19ºC]  
Max. entering air, DB/WB  
Water Limits  
45ºF [7ºC]  
80.6ºF [27ºC]  
130ºF [54ºC]  
60ºF [16ºC]  
39ºF [4ºC]  
68ºF [20ºC]  
85ºF [29ºC]  
40ºF [4.5ºC]  
68ºF [20ºC]  
80ºF [27ºC]  
110/83ºF [43/28ºC]  
Min. entering water  
Normal entering water  
Max. entering water  
20ºF [-6.7ºC]  
50-110ºF [10-43ºC]  
120ºF [49ºC]  
20ºF [-6.7ºC]  
30-70ºF [-1 to 21ºC]  
120ºF [49ºC]  
1.5 to 3.0 gpm / ton  
[1.6 to 3.2 l/m per kW]  
Normal Water Flow  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Unit Start-Up and Operating Conditions  
Low water temperature cutout: Verify that low water  
temperature cut-out controls are set properly  
(FP1 - JW3).  
Miscellaneous: Note any questionable aspects of  
the installation.  
Unit and System Checkout  
BEFORE POWERING SYSTEM, please check the following:  
UNIT CHECKOUT  
Balancing/shutoff valves: Insure that all isolation valves are  
open and water control valves are wired.  
Line voltage and wiring: Verify that voltage is within an  
acceptable range for the unit and wiring and fuses/breakers  
are properly sized. Verify that low voltage wiring is complete.  
Unit control transformer: Insure that transformer has the  
properly selected voltage tap. Residential 208-230V units are  
factory wired for 230V operation unless specied otherwise.  
Loop/water piping is complete and purged of air. Water/  
piping is clean.  
CAUTION! ꢀ  
CAUTION! Verify that ALL water control valves are open  
and allow water ow prior to engaging the compressor.  
Freezing of the coax or water lines can permanently  
damage the heat pump.  
CAUTION! ꢀ  
Antifreeze has been added if necessary.  
CAUTION! To avoid equipment damage, DO NOT  
leave system lled in a building without heat during the  
winter unless antifreeze is added to the water loop. Heat  
exchangers never fully drain by themselves and will  
freeze unless winterized with antifreeze.  
Entering water and air: Insure that entering water and air  
temperatures are within operating limits of Table 8.  
Low water temperature cutout: Verify that low water  
temperature cut-out on the CXM/CXM control is properly set.  
Unit fan: Manually rotate fan to verify free rotation and insure  
that blower wheel is secured to the motor shaft. Be sure to  
remove any shipping supports if needed. DO NOT oil motors  
upon start-up. Fan motors are pre-oiled at the factory.  
Check unit fan speed selection and compare to design  
requirements.  
Condensate line: Verify that condensate line is open and  
properly pitched toward drain.  
HWG pump is disconnected unless piping is completed and  
air has been purged from the system.  
Water ow balancing: Record inlet and outlet water  
temperatures for each heat pump upon startup. This check  
can eliminate nuisance trip outs and high velocity water ow  
that could erode heat exchangers.  
Unit air coil and lters: Insure that lter is clean and  
accessible. Clean air coil of all manufacturing oils.  
Unit controls: Verify that CXM eld selection options are  
properly set. Low voltage wiring is complete.  
Unit Start-up Procedure  
1. Turn the thermostat fan position to “ON.” Blower  
should start.  
2. Balance air ow at registers.  
3. Adjust all valves to their full open position. Turn on the line  
power to all heat pump units.  
4. Room temperature should be within the minimum-maximum  
ranges of Table 8b. During start-up checks, loop water  
temperature entering the heat pump should be between 30°F  
[-1°C] and 95°F [35°C].  
5. Two factors determine the operating limits of water source  
heat pumps, (a) return air temperature, and (b) water  
temperature. When any one of these factors is at a minimum  
or maximum level, the other factor must be at normal level to  
insure proper unit operation.  
a. Adjust the unit thermostat to the warmest setting. Place  
the thermostat mode switch in the “COOL” position.  
Slowly reduce thermostat setting until the compressor  
activates.  
Blower speed is set.  
Service/access panels are in place.  
SYSTEM CHECKOUT  
b. Check for cool air delivery at the unit grille within a few  
minutes after the unit has begun to operate.  
Note: Units have a ve minute time delay in the control  
circuit that can be bypassed on the CXM/CXM control  
board as shown below in Figure 27. See controls  
description for details.  
c. Verify that the compressor is on and that the water ow  
rate is correct by measuring pressure drop through the  
heat exchanger using the P/T plugs and comparing to  
Tables 9a through 9b.  
d. Check the elevation and cleanliness of the condensate  
lines. Dripping may be a sign of a blocked line. Check  
that the condensate trap is lled to provide a water seal.  
e. Refer to Table 10. Check the temperature of both entering  
and leaving water. If temperature is within range, proceed  
with the test. If temperature is outside of the operating  
range, check refrigerant pressures and compare to Tables  
11 through 12. Verify correct water ow by comparing unit  
System water temperature: Check water temperature for  
proper range and also verify heating and cooling set points  
for proper operation.  
System pH: Check and adjust water pH if necessary to  
maintain a level between 6 and 8.5. Proper pH promotes  
longevity of hoses and ttings (see Table 3).  
System ushing: Verify that all air is purged from the system.  
Air in the system can cause poor operation or system  
corrosion. Water used in the system must be potable quality  
initially and clean of dirt, piping slag, and strong chemical  
cleaning agents. Some antifreeze solutions may require  
distilled water.  
Flow Controller pump(s): Verify that the pump(s) is wired,  
purged of air, and in operating condition.  
System controls: Verify that system controls function and  
operate in the proper sequence.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Unit Start-Up Procedure  
pressure drop across the heat exchanger versus the data  
in Tables 9a through 9b. Heat of rejection (HR) can be  
calculated and compared to catalog data capacity pages.  
The formula for HR for systems with water is as follows:  
HR = TD x GPM x 500, where TD is the temperature  
difference between the entering and leaving water,  
and GPM is the ow rate in U.S. GPM, determined by  
comparing the pressure drop across the heat exchanger  
to Tables 9a through 9b.  
WARNING! ꢀ  
WARNING! When the disconnect switch is closed, high  
voltage is present in some areas of the electrical panel.  
Exercise caution when working with energized equipment.  
CAUTION! ꢀ  
CAUTION! Verify that ALL water control valves are open  
and allow water ow prior to engaging the compressor.  
Freezing of the coax or water lines can permanently  
damage the heat pump.  
f. Check air temperature drop across the air coil when  
compressor is operating. Air temperature drop should be  
between 15°F and 25°F [8°C and 14°C].  
g. Turn thermostat to “OFF” position. A hissing noise  
indicates proper functioning of the reversing valve.  
6. Allow ve (5) minutes between tests for pressure to equalize  
before beginning heating test.  
a. Adjust the thermostat to the lowest setting. Place the  
thermostat mode switch in the “HEAT” position.  
b. Slowly raise the thermostat to a higher temperature until  
the compressor activates.  
c. Check for warm air delivery within a few minutes after the  
unit has begun to operate.  
d. Refer to Table 10. Check the temperature of both entering  
and leaving water. If temperature is within range, proceed  
with the test. If temperature is outside of the operating  
range, check refrigerant pressures and compare to Tables  
11 through 12. Verify correct water ow by comparing  
unit pressure drop across the heat exchanger versus the  
data in Tables 9a through 9b. Heat of extraction (HE) can  
be calculated and compared to submittal data capacity  
pages. The formula for HE for systems with water is as  
follows:  
HE = TD x GPM x 500, where TD is the temperature  
difference between the entering and leaving water,  
and GPM is the ow rate in U.S. GPM, determined by  
comparing the pressure drop across the heat exchanger to  
Tables 9a through 9b.  
e. Check air temperature rise across the air coil when  
compressor is operating. Air temperature rise should be  
between 20°F and 30°F [11°C and 17°C].  
f. Check for vibration, noise, and water leaks.  
7. If unit fails to operate, perform troubleshooting analysis  
(see troubleshooting section). If the check described fails  
to reveal the problem and the unit still does not operate,  
contact a trained service technician to insure proper  
diagnosis and repair of the equipment.  
8. When testing is complete, set system to maintain desired  
comfort level.  
9. BE CERTAIN TO FILL OUT AND RETURN ALL WARRANTY  
REGISTRATION PAPERWORK.  
Note: If performance during any mode appears abnormal, refer  
to the CXM section or troubleshooting section of this manual.  
To obtain maximum performance, the air coil should be cleaned  
before start-up. A 10% solution of dishwasher detergent and  
water is recommended.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Unit Operating Conditions  
Table 9a: HT Coax Water Pressure Drop  
Pressure Drop (psi)  
Model  
GPM  
30°F  
50°F  
70°F  
90°F  
2.3  
3.0  
3.4  
4.5  
6.0  
0.7  
1.1  
1.3  
2.0  
3.1  
0.4  
0.7  
0.9  
1.4  
2.3  
0.4  
0.6  
0.8  
1.2  
1.9  
0.5  
0.7  
0.8  
1.2  
1.8  
024  
3.0  
4.5  
6.0  
6.8  
9.0  
1.5  
2.6  
3.8  
4.5  
6.9  
0.9  
1.7  
2.7  
3.2  
5.2  
0.8  
1.5  
2.3  
2.7  
4.4  
0.9  
1.5  
2.2  
2.6  
4.1  
036
4.5  
6.0  
6.8  
9.0  
12.0  
1.5  
2.6  
3.8  
4.5  
6.9  
0.6  
1.1  
1.4  
2.5  
4.2  
0.5  
1.0  
1.3  
2.3  
3.8  
0.3  
0.9  
1.2  
2.2  
3.5  
048  
6.0  
7.5  
9.0  
11.3  
12.0  
15.0  
0.9  
1.7  
2.5  
3.7  
4.1  
6.1  
0.2  
0.9  
1.5  
2.6  
3.0  
4.7  
0.2  
0.7  
1.3  
2.3  
2.6  
4.1  
0.3  
0.8  
1.4  
2.3  
2.6  
4.0  
060  
7.0  
8.5  
10.5  
12.8  
14.0  
17.0  
1.4  
2.2  
3.3  
4.6  
5.4  
7.6  
0.7  
1.3  
2.2  
3.4  
4.1  
6.0  
0.5  
1.1  
1.9  
3.0  
3.6  
5.4  
0.7  
1.2  
2.0  
2.9  
3.5  
5.2  
070  
Table 10: Water Temperature Change Through Heat Exchanger  
ꢅꢂꢃꢂꢇ  
ꢆꢂꢃꢂꢀꢇ  
ꢀꢁꢂꢃꢂꢄꢅ  
Antifreeze Correction Table  
Cooling  
Heating  
WPD  
Antifreeze  
Antifreeze Type  
%
EWT 90°F  
Sens Cap  
EWT 30°F  
Corr. Fct.  
EWT 30°F  
Total Cap  
Power  
Htg Cap  
Power  
0
1.000  
0.995  
0.986  
0.978  
0.997  
0.990  
0.982  
0.998  
0.994  
0.986  
0.998  
0.994  
0.988  
1.000  
0.995  
0.986  
0.978  
0.997  
0.990  
0.982  
0.998  
0.994  
0.986  
0.998  
0.994  
0.988  
1.000  
1.003  
1.009  
1.014  
1.002  
1.007  
1.012  
1.002  
1.005  
1.009  
1.002  
1.004  
1.008  
1.000  
0.989  
0.968  
0.947  
0.989  
0.968  
0.949  
0.981  
0.944  
0.917  
0.993  
0.980  
1.000  
0.997  
0.990  
0.983  
0.997  
0.990  
0.984  
0.994  
0.983  
0.974  
0.998  
0.994  
0.990  
1.000  
1.070  
1.210  
1.360  
1.070  
1.160  
1.220  
1.140  
1.300  
1.360  
1.040  
1.120  
1.200  
Water  
5
15  
25  
5
Propylene Glycol  
15  
25  
5
Methanol  
Ethanol  
15  
25  
5
15  
25  
Ethylene Glycol  
0.966  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Unit Operating Conditions  
Table 11: HT Series Typical Unit Operating Pressures and Temperatures  
HT024  
Full Load Cooling - without HWG active  
Water  
Full Load Heating - without HWG active  
Water  
Entering  
Air  
Temp  
Rise °F  
DB  
Water  
Flow  
Suction Discharge  
Air Temp Suction Discharge  
Drop °F Pressure Pressure Superheat Subcooling  
Water  
Temp  
°F  
Temp  
Rise  
°F  
Temp  
Drop  
°F  
Pressure Pressure Superheat Subcooling  
GPM/ton  
PSIG  
PSIG  
DB  
PSIG  
PSIG  
1.5  
2.25  
3
72-83  
75-85  
78-88  
273-293  
275-295  
277-297  
6-11  
6-11  
6-11  
3-8  
3-8  
3-8  
5.9-7.9  
4.2-6.2  
2.7-4.7  
16-22  
17-23  
18-24  
30*  
1.5  
2.25  
3
128-138  
128-138  
128-138  
186-206  
172-192  
158-178  
18-23  
18-23  
18-23  
8-13  
6-11  
6-11  
16.3-18.3  
12.1-14.1  
7.8-9.8  
19-25  
20-26  
20-26  
102-112  
106-116  
110-120  
302-322  
303-323  
305-325  
8-12  
8-12  
8-12  
6-11  
6-11  
6-11  
8.9-10.9  
6.7-8.7  
4.5-6.5  
22-28  
23-29  
23-29  
50  
70  
1.5  
2.25  
3
136-146  
136-146  
136-146  
281-301  
267-287  
253-273  
7-12  
7-12  
7-12  
7-12  
5-10  
4-9  
15.7-17.7  
11.6-13.6  
7.6-9.6  
19-25  
19-25  
19-25  
128-138  
134-144  
141-151  
330-350  
332-352  
334-354  
10-15  
10-15  
10-15  
8-13  
8-13  
8-13  
11.3-13.3  
8.5-10.5  
5.8-7.8  
27-34  
28-35  
28-35  
1.5  
2.25  
3
139-149  
139-149  
139-149  
368-388  
354-374  
340-360  
6-11  
6-11  
6-11  
7-12  
5-10  
5-10  
14.9-16.9  
11-13  
7.2-9.2  
18-24  
18-24  
18-24  
162-172  
166-176  
171-181  
367-387  
372-392  
377-397  
14-19  
15-20  
17-22  
10-15  
10-15  
10-15  
14.4-16.4  
10.8-12.8  
7.1-9.1  
33-41  
34-42  
34-42  
90  
1.5  
2.25  
3
143-153  
143-153  
143-153  
465-485  
450-470  
433-453  
6-11  
6-11  
6-11  
7-12  
5-10  
5-10  
13.9-15.9  
10.2-12.2  
6.5-8.5  
17-23  
17-23  
17-23  
110  
*Based on 15% Methanol antifreeze solution  
Full Load Cooling - without HWG active  
Full Load Heating - without HWG active  
HT036  
Entering  
Water  
Water  
Temp  
Drop  
°F  
Air  
Temp  
Rise °F  
DB  
Water  
Flow  
GPM/ton  
Suction Discharge  
Pressure Pressure Superheat Subcooling  
Air Temp  
Drop °F  
DB  
Suction Discharge  
Pressure Pressure Superheat Subcooling  
Water  
Temp  
°F  
Temp  
Rise  
°F  
PSIG  
PSIG  
PSIG  
PSIG  
1.5  
2.25  
3
69-79  
73-83  
76-86  
293-313  
297-317  
300-320  
7-12  
7-12  
7-12  
14-19  
14-19  
14-19  
8.9-10.9  
6.7-8.7  
4.5-6.5  
17-23  
18-24  
19-25  
30*  
50  
1.5  
2.25  
3
129-139  
128-138  
128-138  
225-245  
211-231  
197-217  
15-20  
15-20  
15-20  
10-15  
9-14  
9-14  
21.9-23.9  
16.1-18.1  
10.3-12.3  
18-24  
19-25  
19-25  
96-106  
100-110  
105-115  
322-342  
326-346  
331-351  
10-15  
10-15  
10-15  
17-22  
17-22  
17-22  
12.2-14.2  
9.3-11.3  
6.4-8.4  
23-29  
24-30  
24-30  
1.5  
2.25  
3
136-146  
135-145  
135-145  
302-322  
283-303  
265-285  
9-14  
9-14  
9-14  
13-18  
12-17  
12-17  
21.5-23.5  
15.8-17.8  
10-12  
18-24  
19-25  
19-25  
123-133  
129-139  
135-145  
352-372  
358-378  
364-384  
11-16  
11-16  
11-16  
19-24  
19-24  
19-24  
15-17  
11.6-13.6  
8.2-10.2  
28-35  
29-36  
30-37  
70  
1.5  
2.25  
3
140-150  
140-150  
140-150  
390-410  
369-389  
349-369  
7-12  
8-13  
8-13  
13-18  
8-13  
8-13  
20.5-22.5  
14.9-16.9  
9.3-11.3  
17-23  
17-23  
17-23  
157-167  
169-179  
181-191  
390-410  
399-419  
408-428  
13-18  
13-18  
14-19  
18-23  
16.5-21.5  
15-20  
21-23  
15.5-17.5  
10.5-12.5  
36-44  
37-45  
39-47  
90  
1.5  
2.25  
3
145-155  
145-155  
145-155  
488-508  
467-487  
447-467  
7-12  
8-13  
8-13  
13-18  
8-13  
8-13  
19-21  
14-16  
9-11  
17-23  
17-23  
17-23  
110  
*Based on 15% Methanol antifreeze solution  
HT048  
Full Load Cooling - without HWG active  
Full Load Heating - without HWG active  
Entering  
Water  
Water  
Temp  
Drop  
°F  
Air  
Temp  
Rise °F  
DB  
Water  
Flow  
GPM/ton  
Suction Discharge  
Pressure Pressure Superheat Subcooling  
Air Temp Suction Discharge  
Drop °F Pressure Pressure Superheat Subcooling  
Water  
Temp  
°F  
Temp  
Rise  
°F  
PSIG  
PSIG  
DB  
PSIG  
PSIG  
1.5  
2.25  
3
66-76  
69-79  
72-82  
286-306  
289-309  
292-312  
7-12  
7-12  
7-12  
8-13  
9-14  
9-14  
8-10  
6-8  
4-6  
18-24  
19-25  
19-25  
30*  
50  
1.5  
2.25  
3
125-135  
123-133  
122-132  
242-262  
224-244  
205-225  
13-18  
13-18  
14-19  
10-15  
9-14  
7-12  
20.9-22.9  
15.6-17.6  
10.2-12.2  
19-25  
19-25  
19-25  
93-103  
98-108  
103-113  
314-334  
320-340  
326-346  
8-13  
8-13  
8-13  
10-15  
10-15  
10-15  
11.5-13.5  
8.7-10.7  
5.9-7.9  
23-29  
24-30  
25-31  
1.5  
2.25  
3
133-143  
132-142  
131-141  
310-330  
290-310  
270-290  
8-13  
8-13  
9-14  
8-13  
7-12  
5-10  
20.5-22.5  
15.2-17.2  
9.9-11.9  
19-25  
19-25  
19-25  
123-133  
130-140  
137-147  
344-364  
354-374  
361-381  
9-14  
9-14  
9-14  
9-14  
9-14  
9-14  
15-17  
11.5-13.5  
7.9-9.9  
28-35  
29-36  
30-37  
70  
1.5  
2.25  
3
138-148  
137-147  
136-146  
396-416  
374-394  
352-372  
7-12  
7-12  
7-12  
7-12  
6-11  
4-9  
19.2-21.2  
14.3-16.3  
9.3-11.3  
18-24  
18-24  
18-24  
165-175  
175-185  
185-195  
390-410  
401-421  
413-433  
13-18  
15-20  
17-22  
8-13  
8-13  
8-13  
19.6-21.6  
15-17  
10.3-12.3  
37-45  
38-46  
39-47  
90  
1.5  
2.25  
3
144-154  
143-153  
142-152  
497-517  
472-492  
447-467  
7-12  
7-12  
7-12  
5-10  
4-9  
3-8  
18-20  
13.3-15.3  
8.5-10.5  
17-23  
17-23  
17-23  
110  
*Based on 15% Methanol antifreeze solution  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Unit Operating Conditions  
Table 11: HT Series Typical Unit Operating Pressures and Temperatures: Continued  
HT060  
Full Load Cooling - without HWG active  
Full Load Heating - without HWG active  
Water  
Temp  
Entering  
Water  
Air  
Temp  
Rise °F  
DB  
Water  
Flow  
Suction  
Pressure  
PSIG  
Discharge  
Air Temp Suction Discharge  
Drop °F Pressure Pressure Superheat Subcooling  
Water  
Temp  
°F  
Temp  
Rise  
°F  
Pressure Superheat Subcooling  
PSIG  
Drop  
°F  
GPM/ton  
DB  
PSIG  
PSIG  
1.5  
2.25  
3
66-76  
69-79  
72-82  
282-302  
285-305  
289-309  
10-16  
10-16  
10-16  
9-14  
9-14  
10-15  
8-10  
6-8  
4-6  
19-25  
19-25  
20-26  
30*  
50  
1.5  
2.25  
3
128-138  
126-136  
125-135  
238-258  
222-242  
205-225  
16-21  
21-26  
26-31  
14-19  
13-18  
12-17  
20.5-22.5  
14.9-16.9  
9.2-11.2  
21-27  
21-27  
21-27  
90-100  
95-105  
99-109  
310-330  
313-333  
316-336  
11-17  
11-17  
11-17  
12-17  
12-17  
12-17  
11.3-13.3  
8.5-10.5  
5.7-7.7  
24-30  
25-31  
26-32  
1.5  
2.25  
3
135-145  
134-144  
133-143  
315-335  
296-316  
276-296  
10-15  
12-17  
15-20  
14-19  
13-18  
11-16  
21-23  
15.5-17.5  
10-12  
22-28  
22-28  
22-28  
115-125  
120-130  
126-136  
337-357  
341-361  
345-365  
12-18  
12-18  
12-18  
14-19  
14-19  
15-20  
14-16  
10.6-12.6  
7.3-9.3  
28-35  
29-36  
30-37  
70  
1.5  
2.25  
3
139-149  
138-148  
138-148  
408-428  
386-406  
364-384  
10-15  
10-15  
10-15  
15-20  
13-18  
11-16  
20.1-22.1  
14.8-16.8  
9.5-11.5  
21-27  
21-27  
21-27  
157-167  
161-171  
166-176  
390-410  
394-414  
398-418  
15-20  
15-20  
15-20  
14-19  
14-19  
15-20  
18.2-20.2  
13.9-15.9  
9.6-11.6  
37-45  
38-46  
39-47  
90  
1.5  
2.25  
3
144-154  
143-153  
142-152  
515-535  
493-513  
469-489  
8-13  
8-13  
8-13  
14-19  
13-18  
12-17  
19-21  
14-16  
9-11  
20-26  
20-26  
20-26  
110  
*Based on 15% Methanol antifreeze solution  
HT070  
Full Load Cooling - without HWG active  
Full Load Heating - without HWG active  
Entering Water  
Water  
Air  
Temp  
Drop °F  
DB  
Water  
Temp Temp  
Drop  
°F  
Air  
Suction Discharge  
Pressure Pressure Superheat Subcooling  
Suction Discharge  
Pressure Pressure Superheat Subcooling  
Water  
Temp  
°F  
Flow  
GPM/  
ton  
Temp  
Rise  
°F  
Rise  
°F DB  
PSIG  
PSIG  
PSIG  
PSIG  
1.5  
2.25  
3
61-71  
65-75  
68-78  
292-312  
296-316  
300-320  
11-16  
11-16  
10-15  
13-18  
14-19  
15-20  
7.2-9.2  
5.4-7.4  
3.5-5.5  
19-25  
20-26  
21-27  
30*  
1.5  
2.25  
3
131-141  
130-140  
129-139  
210-230  
205-225  
200-220  
10-15  
11-16  
13-18  
12-17  
12-17  
12-17  
18.5-20.5  
14-16  
9.5-11.5  
22-28  
23-29  
24-30  
89-99  
98-108  
106-116  
327-347  
337-357  
348-368  
10-15  
10-15  
10-15  
19-24  
14-19  
9-14  
10.9-12.9 26-32  
8.3-10.3 28-34  
50  
5.7-7.7  
30-36  
1.5  
2.25  
3
135-145  
131-141  
128-138  
300-320  
295-315  
290-310  
10-15  
11-16  
13-18  
15-20  
14-19  
14-19  
17.6-19.6  
13.8-15.8  
10-12  
23-29  
23-29  
23-29  
119-129  
132-142  
144-154  
365-385  
380-400  
395-415  
10-15  
10-15  
10-15  
21-26  
16-21  
11-16  
14.7-16.7 33-39  
11.3-13.3 36-42  
70  
7.9-9.9  
38-44  
1.5  
2.25  
3
139-149  
137-147  
135-145  
390-410  
370-390  
350-370  
10-15  
10-15  
10-15  
16-21  
14-19  
13-18  
16.7-18.7  
12.6-14.6  
8.5-10.5  
22-28  
22-28  
22-28  
162-172  
172-182  
182-192  
418-438  
430-450  
444-464  
10-15  
10-15  
11-16  
19-24  
19-24  
19-24  
19.4-21.4 43-49  
14.7-16.7 45-51  
10.1-12.1 47-53  
90  
1.5  
2.25  
3
145-155  
145-155  
144-154  
490-510  
470-490  
452-472  
10-15  
10-15  
9-14  
16-21  
14-19  
13-18  
15.9-17.9  
11.7-13.7  
7.4-9  
20-27  
20-27  
20-27  
110  
*Based on 15% Methanol antifreeze solution  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Performance Data — HT 024 - Full Load  
850 CFM Nominal (ISO Rated) Airflow Cooling, 950 CFM Nominal (ISO Rated) Airflow Heating  
Performance capacities shown in thousands of Btuh  
Cooling - EAT 80/67°F  
Heating - EAT 70°F  
EWT  
WPD  
°F  
WPD  
PSI  
GPM  
CFM  
EER  
HR LWT HWC GPM  
CFM  
COP  
LAT LWT HWC  
TC SC kW  
HC kW  
HE  
PSI  
FT  
FT  
6.0  
6.0  
3.7  
3.7  
1.1  
1.1  
2.0  
2.0  
3.1  
3.1  
0.9  
0.9  
1.6  
1.6  
2.6  
2.6  
0.7  
0.7  
1.4  
1.4  
2.3  
2.3  
0.7  
0.7  
1.3  
1.3  
2.0  
2.0  
0.6  
0.6  
1.2  
1.2  
1.9  
1.9  
0.7  
0.7  
1.2  
1.2  
1.8  
1.8  
0.7  
0.7  
1.2  
1.2  
1.8  
1.8  
8.6  
8.6  
2.5  
2.5  
4.6  
4.6  
7.1  
7.1  
2.0  
2.0  
3.8  
3.8  
6.0  
6.0  
1.6  
1.6  
3.2  
3.2  
5.2  
5.2  
1.5  
1.5  
2.9  
2.9  
4.7  
4.7  
1.5  
1.5  
2.7  
2.7  
4.4  
4.4  
1.5  
1.5  
2.7  
2.7  
4.2  
4.2  
1.6  
1.6  
2.7  
2.7  
4.1  
4.1  
820 16.4 1.49  
950 16.6 1.44  
820 17.8 1.51  
950 18.1 1.47  
820 18.6 1.53  
950 18.9 1.48  
820 19.0 1.53  
950 19.3 1.49  
820 20.4 1.56  
950 20.7 1.51  
820 21.3 1.57  
950 21.7 1.53  
820 21.9 1.58  
950 22.2 1.53  
820 23.1 1.60  
950 23.4 1.55  
820 24.3 1.62  
950 24.6 1.57  
820 24.9 1.64  
950 25.3 1.59  
820 25.9 1.65  
950 26.3 1.60  
820 27.3 1.68  
950 27.7 1.63  
820 28.1 1.69  
950 28.5 1.64  
820 28.8 1.70  
950 29.2 1.65  
820 30.4 1.73  
950 30.8 1.68  
820 31.2 1.75  
950 31.7 1.70  
820 31.6 1.76  
950 32.1 1.70  
820 33.4 1.79  
950 33.9 1.74  
820 34.3 1.81  
950 34.9 1.76  
820 34.4 1.81  
950 35.0 1.76  
820 36.3 1.86  
950 36.9 1.80  
820 37.3 1.88  
950 37.9 1.82  
3.2  
3.4  
3.5  
3.6  
3.6  
3.7  
3.6  
3.8  
3.8  
4.0  
4.0  
4.2  
4.0  
4.2  
4.2  
4.4  
4.4  
4.6  
4.5  
4.7  
4.6  
4.8  
4.8  
5.0  
4.9  
5.1  
4.9  
5.2  
5.1  
5.4  
5.2  
5.5  
5.3  
5.5  
5.5  
5.7  
5.6  
5.8  
5.6  
5.8  
5.7  
6.0  
5.8  
6.1  
11.3 88.5  
11.7 86.2  
12.7 90.1  
13.1 87.6  
13.4 91.0  
13.8 88.4  
13.8 91.5  
14.2 88.8  
15.0 93.0  
15.5 90.1  
16.0 94.1  
16.5 91.1  
16.5 94.7  
17.0 91.6  
17.6 96.0  
18.1 92.8  
18.7 97.4  
19.3 94.0  
19.3 98.1  
19.9 94.7  
20.2 99.2  
20.8 95.6  
21.6 100.8 50.4  
22.2 97.0 9.9  
22.3 101.7 52.6  
22.9 97.8 7.6  
22.9 102.5 54.7  
23.6 98.5 15.7  
24.4 104.3 59.1  
25.1 100.0 11.2  
25.3 105.3 61.6  
16.2  
3.9  
21.6  
8.7  
24.1  
6.1  
25.4  
4.7  
30.0  
10.3  
32.9  
7.3  
34.5  
5.7  
38.3  
12.1  
41.7  
8.6  
43.6  
6.6  
1.6  
1.5  
1.8  
1.8  
1.9  
1.9  
2.0  
1.9  
2.2  
2.1  
2.3  
2.3  
2.4  
2.3  
2.6  
2.5  
2.7  
2.6  
2.8  
2.7  
2.9  
2.8  
3.1  
3.0  
3.2  
3.1  
3.3  
3.2  
3.5  
3.4  
3.6  
3.5  
3.6  
3.5  
3.8  
3.7  
3.9  
3.8  
3.9  
3.8  
4.2  
4.0  
4.3  
4.2  
20  
30  
Operation not recommended  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
1.1  
1.1  
2.0  
2.0  
3.1  
3.1  
0.9  
0.9  
1.6  
1.6  
2.6  
2.6  
0.7  
0.7  
1.4  
1.4  
2.3  
2.3  
0.7  
0.7  
1.3  
1.3  
2.0  
2.0  
0.6  
0.6  
1.2  
1.2  
1.9  
1.9  
0.7  
0.7  
1.2  
1.2  
1.8  
1.8  
0.7  
0.7  
1.2  
1.2  
1.8  
1.8  
0.7  
0.7  
1.2  
1.2  
1.8  
1.8  
0.7  
0.7  
1.1  
1.1  
1.7  
1.7  
0.5  
0.5  
1.0  
1.0  
1.7  
1.7  
2.5  
2.5  
4.6  
4.6  
7.1  
7.1  
2.0  
2.0  
3.8  
3.8  
6.0  
6.0  
1.6  
1.6  
3.2  
3.2  
5.2  
5.2  
1.5  
1.5  
2.9  
2.9  
4.7  
4.7  
1.5  
1.5  
2.7  
2.7  
4.4  
4.4  
1.5  
1.5  
2.7  
2.7  
4.2  
4.2  
1.6  
1.6  
2.7  
2.7  
4.1  
4.1  
1.6  
1.6  
2.7  
2.7  
4.1  
4.1  
1.5  
1.5  
2.6  
2.6  
4.0  
4.0  
1.2  
1.2  
2.4  
2.4  
3.9  
3.9  
730 30.2 20.2 0.95 31.9 33.4 22.7  
850 30.7 21.8 0.98 31.3 34.0 22.7  
730 30.2 20.2 0.88 34.2 33.2 15.1  
850 30.7 21.7 0.92 33.6 33.9 15.1  
730 30.1 20.1 0.86 35.2 33.0 11.2  
850 30.7 21.6 0.89 34.6 33.7 11.2  
730 29.6 20.1 1.04 28.4 33.2 22.5  
850 30.1 21.6 1.08 27.9 33.8 22.5  
730 30.1 20.2 0.97 31.0 33.4 15.1  
850 30.6 21.8 1.00 30.5 34.0 15.1  
730 30.2 20.2 0.93 32.3 33.4 11.3  
850 30.7 21.8 0.97 31.7 34.0 11.3  
730 28.7 19.7 1.15 24.9 32.7 22.2  
850 29.2 21.2 1.20 24.4 33.3 22.2  
730 29.4 20.0 1.07 27.5 33.1 15.0  
850 29.9 21.5 1.11 27.0 33.7 15.0  
730 29.7 20.1 1.03 28.9 33.2 11.3  
850 30.2 21.6 1.07 28.3 33.9 11.3  
730 27.5 19.2 1.28 21.5 31.9 21.7  
850 28.0 20.7 1.33 21.1 32.5 21.7  
730 28.4 19.6 1.19 24.0 32.5 14.7  
850 28.9 21.1 1.23 23.5 33.1 14.7  
730 28.8 19.8 1.14 25.3 32.7 11.1  
850 29.3 21.3 1.18 24.8 33.4 11.1  
730 26.1 18.7 1.42 18.4 31.0 21.1  
850 26.6 20.1 1.47 18.0 31.6 21.1  
730 27.1 19.1 1.32 20.6 31.6 14.3  
850 27.6 20.5 1.37 20.2 32.3 14.3  
730 27.6 19.3 1.27 21.8 32.0 10.9  
850 28.1 20.7 1.31 21.4 32.6 10.9  
730 24.6 18.0 1.58 15.6 30.0 20.4  
850 25.0 19.4 1.64 15.3 30.6 20.4  
730 25.7 18.5 1.47 17.5 30.7 13.9  
850 26.1 19.9 1.52 17.2 31.3 13.9  
730 26.2 18.7 1.41 18.5 31.0 10.6  
850 26.7 20.1 1.46 18.2 31.7 10.6  
730 23.0 17.4 1.76 13.1 29.0 19.8  
850 24.5 19.2 1.70 14.5 30.3 19.8  
730 24.1 17.8 1.64 14.7 29.7 13.5  
850 24.5 19.2 1.70 14.5 30.3 13.5  
730 24.6 18.0 1.58 15.6 30.0 10.2  
850 25.1 19.4 1.63 15.3 30.6 10.2  
730 21.5 16.9 1.95 11.0 28.1 19.2  
850 21.8 18.1 2.02 10.8 28.7 19.2  
730 22.5 17.2 1.82 12.3 28.7 13.0  
850 22.9 18.5 1.89 12.1 29.3 13.0  
0.8  
0.8  
0.7  
0.7  
0.6  
0.7  
1.1  
1.1  
0.9  
0.9  
0.8  
0.8  
1.4  
1.5  
1.2  
1.2  
1.0  
1.1  
1.9  
1.9  
1.5  
1.6  
1.4  
1.4  
2.4  
2.4  
2.0  
2.0  
1.8  
1.9  
3.0  
3.0  
2.5  
2.6  
2.3  
2.4  
3.6  
3.3  
3.2  
3.3  
3.0  
3.0  
4.4  
4.5  
3.9  
4.0  
3.7  
3.7  
5.3  
5.4  
4.7  
4.8  
4.5  
4.5  
6.3  
6.4  
5.6  
5.8  
5.3  
5.5  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
3.0  
3.0  
4.5  
4.5  
6.0  
6.0  
40  
50  
46.5  
13.9  
60  
70  
25.9 100.9  
8.6  
25.6 105.7 62.9  
26.3 101.3 17.5  
27.3 107.7 67.9  
28.0 103.0 12.4  
28.2 108.8 70.6  
80  
28.9 104.0  
9.6  
28.2 108.9 71.2  
29.0 104.1 19.3  
30.0 111.0 76.7  
30.7 105.9 13.7  
30.9 112.1 79.7  
31.6 106.9 10.5  
90  
100  
110  
120  
730 23.0 17.4 1.76 13.1 29.0  
850 23.4 18.7 1.82 12.8 29.6  
9.9  
9.9  
27.4 18.7  
28.0 18.7  
730 20.0 16.4 2.17  
850 20.3 17.7 2.25  
9.2  
9.0  
730 20.9 16.7 2.03 10.3 27.8 12.6  
850 21.3 17.9 2.10 10.1 28.5 12.6  
730 21.4 16.8 1.96 10.9 28.1  
850 21.8 18.1 2.03 10.7 28.7  
Operation not recommended  
9.6  
9.6  
26.9 18.3  
27.5 18.3  
27.2 12.3  
27.8 12.3  
730 18.7 16.2 2.41  
850 19.0 17.4 2.50  
730 19.5 16.3 2.26  
850 19.8 17.5 2.34  
730 19.9 16.4 2.18  
850 20.2 17.6 2.26  
7.7  
7.6  
8.6  
8.5  
9.1  
8.9  
27.3  
28.0  
9.3  
9.3  
Interpolation is permissible; extrapolation is not.  
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.  
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.  
See performance correction tables for operating conditions other than those listed above.  
For operation in the shaded areas, please see the Performance Data Selection Notes.  
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.  
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.  
Table does not reect fan or pump power corrections for AHRI/ISO conditions.  
All performance is based upon the lower voltage of dual voltage rated units.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Performance Data — HT 036 - Full Load  
1250 CFM Nominal (ISO Rated) Airflow Cooling, 1250 CFM Nominal (ISO Rated) Airflow Heating  
Performance capacities shown in thousands of Btuh  
Cooling - EAT 80/67°F  
Heating - EAT 70°F  
EWT  
WPD  
°F  
WPD  
PSI  
GPM  
CFM  
EER  
HR LWT HWC GPM  
CFM  
COP  
LAT LWT HWC  
TC SC kW  
HC kW  
HE  
PSI  
FT  
FT  
9.0  
9.0  
8.3 19.1 1080 25.6 2.09  
8.3 19.1 1250 26.0 2.02  
3.6  
3.8  
3.9  
4.0  
4.0  
4.2  
4.1  
4.3  
4.3  
4.5  
4.4  
4.6  
4.5  
4.7  
4.6  
4.9  
4.8  
5.0  
4.9  
5.1  
5.0  
5.2  
5.1  
5.4  
5.2  
5.4  
5.2  
5.5  
5.4  
5.6  
5.5  
5.7  
5.5  
5.7  
5.6  
5.9  
5.7  
6.0  
5.7  
6.0  
5.9  
6.1  
5.9  
6.2  
18.5 91.9  
19.1 89.2  
20.7 93.9  
21.3 91.0  
21.9 95.1  
22.6 92.0  
22.6 95.7  
23.3 92.5  
24.4 97.3  
25.2 94.0  
25.9 98.7  
26.7 95.2  
26.7 99.5  
27.5 95.8  
28.2 100.8 37.5  
29.0 97.0 12.9  
29.9 102.4 41.1  
30.7 98.4 9.1  
30.8 103.3 43.1  
31.7 99.2 7.0  
15.9  
4.2  
20.8  
9.5  
23.5  
6.7  
25.0  
5.2  
29.1  
11.2  
32.3  
7.9  
34.1  
6.1  
2.1  
2.1  
2.4  
2.4  
2.6  
2.5  
2.7  
2.6  
2.9  
2.9  
3.1  
3.0  
3.2  
3.2  
3.4  
3.3  
3.7  
3.6  
3.8  
3.7  
3.9  
3.8  
4.2  
4.1  
4.3  
4.2  
4.4  
4.3  
4.7  
4.5  
4.8  
4.7  
4.9  
4.7  
5.2  
5.0  
5.3  
5.2  
5.3  
5.2  
5.6  
5.5  
5.8  
5.6  
20  
30  
Operation not recommended  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
2.6  
2.6  
6.0 1080 44.8 27.6 1.44 31.1 49.7 22.5  
6.0 1250 45.6 29.7 1.49 30.5 50.6 22.5  
4.5 10.5 1080 44.2 27.4 1.39 31.8 48.9 14.8  
4.5 10.5 1250 44.9 29.5 1.44 31.2 49.9 14.8  
6.9 16.0 1080 43.6 27.3 1.38 31.7 48.3 10.9  
6.9 16.0 1250 44.4 29.3 1.43 31.1 49.3 10.9  
1.1  
1.1  
0.9  
0.9  
0.8  
0.8  
1.4  
1.5  
1.1  
1.2  
1.0  
1.0  
1.9  
2.0  
1.5  
1.6  
1.4  
1.4  
2.6  
2.7  
2.1  
2.1  
1.9  
1.9  
3.4  
3.5  
2.8  
2.9  
2.5  
2.6  
4.3  
4.4  
3.6  
3.7  
3.3  
3.4  
5.3  
4.7  
4.6  
4.7  
4.3  
4.3  
6.5  
6.7  
5.7  
5.8  
5.3  
5.4  
7.9  
8.0  
7.0  
7.1  
6.6  
6.7  
9.4  
9.6  
8.4  
8.6  
7.9  
8.1  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
4.5  
4.5  
6.8  
6.8  
9.0  
9.0  
2.6  
2.6  
6.0 1080 27.9 2.12  
6.0 1250 28.3 2.05  
4.5 10.5 1080 29.2 2.14  
4.5 10.5 1250 29.7 2.07  
6.9 16.0 1080 30.0 2.15  
6.9 16.0 1250 30.4 2.08  
2.0  
2.0  
3.8  
3.8  
4.7 1080 44.7 27.6 1.54 28.9 49.9 22.6  
4.7 1250 45.4 29.6 1.60 28.4 50.9 22.6  
8.7 1080 44.8 27.6 1.46 30.7 49.8 15.0  
8.7 1250 45.6 29.7 1.51 30.1 50.8 15.0  
2.0  
2.0  
3.8  
3.8  
4.7 1080 31.9 2.18  
4.7 1250 32.4 2.12  
8.7 1080 33.5 2.22  
8.7 1250 34.0 2.15  
40  
50  
5.9 13.6 1080 44.7 27.6 1.43 31.3 49.6 11.2  
5.9 13.6 1250 45.5 29.7 1.48 30.7 50.5 11.2  
5.9 13.6 1080 34.4 2.23  
5.9 13.6 1250 34.9 2.16  
1.7  
1.7  
3.2  
3.2  
3.9 1080 43.7 27.3 1.68 26.0 49.5 22.4  
3.9 1250 44.5 29.3 1.75 25.5 50.4 22.4  
7.5 1080 44.5 27.5 1.57 28.3 49.9 15.1  
7.5 1250 45.3 29.6 1.63 27.7 50.8 15.1  
1.7  
1.7  
3.2  
3.2  
3.9 1080 35.9 2.27  
3.9 1250 36.5 2.20  
7.5 1080 37.8 2.31  
7.5 1250 38.4 2.24  
5.2 11.9 1080 44.7 27.6 1.53 29.3 49.9 11.3  
5.2 11.9 1250 45.5 29.7 1.58 28.8 50.9 11.3  
5.2 11.9 1080 38.8 2.33  
5.2 11.9 1250 39.4 2.26  
1.5  
1.5  
2.9  
2.9  
3.5 1080 42.2 26.8 1.86 22.7 48.5 22.0  
3.5 1250 42.9 28.8 1.93 22.3 49.5 22.0  
6.7 1080 43.4 27.2 1.73 25.1 49.3 14.9  
6.7 1250 44.1 29.2 1.79 24.7 50.2 14.9  
1.5  
1.5  
2.9  
2.9  
3.5 1080 40.0 2.36  
3.5 1250 40.6 2.29  
6.7 1080 42.1 2.42  
6.7 1250 42.8 2.34  
31.9 104.3 45.8  
32.8 100.1 14.6  
33.9 106.1 50.0  
34.8 101.7 10.3  
34.9 107.1 52.2  
60  
4.7 10.8 1080 43.9 27.3 1.67 26.3 49.6 11.2  
4.7 10.8 1250 44.6 29.4 1.73 25.9 50.5 11.2  
4.7 10.8 1080 43.3 2.44  
4.7 10.8 1250 43.9 2.37  
35.8 102.5  
8.0  
1.5  
1.5  
2.7  
2.7  
3.4 1080 40.2 26.0 2.06 19.5 47.3 21.4  
3.4 1250 40.9 28.0 2.14 19.2 48.2 21.4  
6.3 1080 41.7 26.6 1.91 21.8 48.2 14.6  
6.3 1250 42.4 28.6 1.98 21.4 49.2 14.6  
1.5  
1.5  
2.7  
2.7  
3.4 1080 44.1 2.47  
3.4 1250 44.8 2.39  
6.3 1080 46.5 2.53  
6.3 1250 47.2 2.45  
35.7 107.8 54.1  
36.6 103.2 16.3  
37.8 109.8 58.8  
38.8 104.9 11.5  
39.0 111.0 61.3  
70  
4.4 10.1 1080 42.4 26.8 1.84 23.0 48.6 11.0  
4.4 10.1 1250 43.1 28.8 1.91 22.6 49.6 11.0  
4.4 10.1 1080 47.8 2.56  
4.4 10.1 1250 48.5 2.48  
40.0 105.9  
8.9  
1.5  
1.5  
2.7  
2.7  
4.2  
4.2  
1.5  
1.5  
2.6  
2.6  
4.1  
4.1  
1.5  
1.5  
2.6  
2.6  
4.1  
4.1  
1.4  
1.4  
2.5  
2.5  
4.0  
4.0  
1.1  
1.1  
2.4  
2.4  
3.9  
3.9  
3.4 1080 38.0 25.2 2.29 16.6 45.8 20.8  
3.4 1250 38.6 27.1 2.37 16.3 46.7 20.8  
6.2 1080 39.6 25.8 2.13 18.6 46.8 14.2  
6.2 1250 40.3 27.7 2.20 18.3 47.8 14.2  
9.7 1080 40.4 26.1 2.05 19.7 47.4 10.7  
9.7 1250 41.1 28.1 2.12 19.4 48.3 10.7  
3.5 1080 35.6 24.1 2.54 14.0 44.3 20.1  
3.5 1250 37.9 26.7 2.45 15.4 46.2 20.1  
6.1 1080 37.2 24.9 2.37 15.7 45.3 13.7  
6.1 1250 37.9 26.7 2.45 15.4 46.2 13.7  
9.5 1080 38.1 25.2 2.28 16.7 45.9 10.4  
9.5 1250 38.7 27.1 2.36 16.4 46.8 10.4  
3.5 1080 33.2 23.0 2.82 11.8 42.8 19.4  
3.5 1250 33.7 24.8 2.92 11.6 43.7 19.4  
6.1 1080 34.8 23.8 2.63 13.2 43.7 13.2  
6.1 1250 35.4 25.6 2.73 13.0 44.7 13.2  
9.4 1080 35.6 24.1 2.54 14.0 44.3 10.0  
9.4 1250 36.2 26.0 2.63 13.7 45.2 10.0  
1.5  
1.5  
2.7  
2.7  
4.2  
4.2  
1.5  
1.5  
2.6  
2.6  
4.1  
4.1  
3.4 1080 48.2 2.58  
3.4 1250 49.0 2.50  
6.2 1080 50.9 2.65  
6.2 1250 51.6 2.56  
9.7 1080 52.3 2.69  
9.7 1250 53.1 2.60  
3.5 1080 52.4 2.69  
3.5 1250 53.2 2.60  
6.1 1080 55.3 2.76  
6.1 1250 56.1 2.68  
9.5 1080 56.8 2.81  
9.5 1250 57.7 2.72  
39.4 111.3 62.5  
40.4 106.3 18.0  
41.8 113.6 67.6  
42.9 108.2 12.7  
43.1 114.8 70.4  
80  
44.2 109.3  
9.8  
43.2 114.9 70.8  
44.3 109.4 19.7  
45.8 117.4 76.4  
47.0 111.6 13.9  
47.3 118.7 79.5  
48.4 112.7 10.8  
90  
100  
110  
120  
3.2 1080 30.8 21.9 3.11  
3.2 1250 31.4 23.5 3.23  
9.9  
9.7  
41.5 18.8  
42.4 18.8  
Operation not recommended  
5.9 1080 32.3 22.6 2.92 11.1 42.3 12.8  
5.9 1250 32.9 24.3 3.03 10.9 43.2 12.8  
9.2 1080 33.1 23.0 2.83 11.7 42.7  
9.2 1250 33.7 24.7 2.93 11.5 43.6  
9.7  
9.7  
40.4 18.4  
41.4 18.4  
41.0 12.4  
41.9 12.4  
2.6 1080 28.7 20.8 3.43  
2.6 1250 29.2 22.3 3.55  
5.4 1080 30.0 21.4 3.23  
5.4 1250 30.5 23.1 3.35  
8.9 1080 30.7 21.8 3.13  
8.9 1250 31.2 23.4 3.25  
8.4  
8.2  
9.3  
9.1  
9.8  
9.6  
41.4  
42.3  
9.4  
9.4  
Interpolation is permissible; extrapolation is not.  
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.  
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.  
See performance correction tables for operating conditions other than those listed above.  
For operation in the shaded areas, please see the Performance Data Selection Notes.  
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.  
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.  
Table does not reect fan or pump power corrections for AHRI/ISO conditions.  
All performance is based upon the lower voltage of dual voltage rated units.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Performance Data — HT 048 - Full Load  
1550 CFM Nominal (ISO Rated) Airflow Cooling, 1650 CFM Nominal (ISO Rated) Airflow Heating  
Performance capacities shown in thousands of Btuh  
Cooling - EAT 80/67°F  
Heating - EAT 70°F  
EWT  
WPD  
°F  
WPD  
PSI  
GPM  
CFM  
EER  
HR LWT HWC GPM  
CFM  
COP  
LAT LWT HWC  
TC SC kW  
HC kW  
HE  
PSI  
FT  
FT  
12.0  
12.0  
6.0  
6.0  
9.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
5.2 12.1 1430 33.0 2.94  
5.2 12.1 1650 33.5 2.85  
3.3  
3.4  
3.4  
3.6  
3.5  
3.7  
3.6  
3.7  
3.7  
3.9  
3.8  
4.0  
3.9  
4.1  
4.0  
4.2  
4.2  
4.4  
4.3  
4.5  
4.4  
4.6  
4.5  
4.7  
4.6  
4.8  
4.7  
4.9  
4.8  
5.0  
4.9  
5.1  
4.9  
5.2  
5.1  
5.3  
5.1  
5.4  
5.1  
5.4  
5.2  
5.5  
5.3  
5.5  
23.0 91.4  
23.8 88.8  
25.2 93.0  
26.1 90.3  
26.5 93.9  
27.3 91.0  
27.1 94.4  
28.1 91.5  
29.5 96.1  
30.4 93.0  
31.2 97.3  
32.1 94.0  
32.1 97.9  
33.1 94.6  
34.3 99.5  
35.3 95.9  
36.4 101.0 41.9  
37.5 97.2 8.3  
37.5 101.8 43.7  
38.7 98.0 6.4  
39.4 103.1 46.9  
40.5 99.1 13.5  
41.9 104.9 50.7  
43.1 100.7 9.6  
43.3 105.9 52.8  
44.5 101.5 7.4  
16.2  
4.0  
21.6  
8.7  
24.1  
6.1  
25.5  
4.7  
30.2  
10.1  
33.1  
7.1  
34.7  
5.5  
3.4  
3.3  
3.6  
3.5  
3.6  
3.5  
3.7  
3.6  
3.8  
3.7  
3.9  
3.8  
4.0  
3.9  
4.1  
4.0  
4.3  
4.1  
4.3  
4.2  
4.5  
4.3  
4.7  
4.5  
4.8  
4.6  
4.9  
4.7  
5.1  
5.0  
5.2  
5.1  
5.3  
5.2  
5.6  
5.4  
5.8  
5.6  
5.8  
5.6  
6.2  
6.0  
6.4  
6.2  
20  
30  
Operation not recommended  
6.0  
6.0  
9.0  
1.2  
1.2  
2.7  
2.7  
2.8 1330 58.6 39.7 1.89 31.0 65.0 22.1  
2.8 1550 59.6 42.6 1.96 30.4 66.3 22.1  
6.4 1330 58.4 40.7 1.78 32.8 64.5 14.6  
6.4 1550 59.4 43.8 1.85 32.2 65.7 14.6  
1.8  
1.8  
1.8  
1.8  
1.8  
1.9  
2.0  
2.0  
1.8  
1.9  
1.8  
1.8  
2.3  
2.4  
2.0  
2.1  
1.9  
2.0  
2.9  
2.9  
2.5  
2.5  
2.3  
2.3  
3.6  
3.7  
3.1  
3.1  
2.8  
2.9  
4.5  
4.5  
3.8  
3.9  
3.6  
3.6  
5.5  
4.9  
4.8  
4.9  
4.5  
4.6  
6.7  
6.9  
5.9  
6.1  
5.6  
5.7  
8.2  
8.4  
7.3  
7.4  
6.8  
7.0  
9.9  
10.1  
8.8  
9.0  
8.3  
8.5  
1.2  
1.2  
2.7  
2.7  
2.8 1430 35.6 3.03  
2.8 1650 36.1 2.94  
6.4 1430 36.9 3.07  
6.4 1650 37.5 2.98  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
4.7 10.8 1330 58.0 41.3 1.73 33.5 64.0 10.9  
4.7 10.8 1550 59.0 44.4 1.80 32.9 65.2 10.9  
4.7 10.8 1430 37.7 3.10  
4.7 10.8 1650 38.3 3.00  
1.0  
1.0  
2.4  
2.4  
4.2  
4.2  
0.9  
0.9  
2.2  
2.2  
3.9  
3.9  
0.8  
0.8  
2.0  
2.0  
3.6  
3.6  
0.8  
0.8  
2.0  
2.0  
3.5  
3.5  
0.8  
0.8  
1.9  
1.9  
3.4  
3.4  
0.8  
0.8  
1.9  
1.9  
3.3  
3.3  
0.8  
0.8  
1.9  
1.9  
3.3  
3.3  
0.8  
0.8  
1.8  
1.8  
3.3  
3.3  
0.7  
0.7  
1.8  
1.8  
3.2  
3.2  
2.3 1330 57.8 38.4 2.06 28.1 64.8 22.0  
2.3 1550 58.8 41.3 2.13 27.6 66.1 22.0  
5.6 1330 58.5 39.3 1.93 30.3 65.1 14.7  
5.6 1550 59.5 42.3 2.00 29.7 66.3 14.7  
9.7 1330 58.6 39.8 1.87 31.3 65.0 11.0  
9.7 1550 59.6 42.8 1.94 30.7 66.2 11.0  
2.0 1330 56.1 37.4 2.25 24.9 63.8 21.7  
2.0 1550 57.1 40.2 2.33 24.4 65.0 21.7  
5.1 1330 57.4 38.1 2.11 27.2 64.6 14.6  
5.1 1550 58.4 41.0 2.18 26.7 65.9 14.6  
9.0 1330 57.9 38.5 2.04 28.4 64.9 11.0  
9.0 1550 58.9 41.4 2.11 27.9 66.1 11.0  
1.9 1330 53.7 36.5 2.48 21.7 62.2 21.1  
1.9 1550 54.7 39.2 2.57 21.3 63.4 21.1  
4.7 1330 55.5 37.1 2.31 24.0 63.4 14.4  
4.7 1550 56.4 39.9 2.40 23.6 64.6 14.4  
8.4 1330 56.3 37.5 2.24 25.2 63.9 10.9  
8.4 1550 57.2 40.3 2.32 24.7 65.1 10.9  
1.8 1330 51.0 35.6 2.73 18.7 60.3 20.5  
1.8 1550 51.8 38.2 2.83 18.3 61.5 20.5  
4.5 1330 52.9 36.2 2.55 20.8 61.6 14.0  
4.5 1550 53.9 38.9 2.64 20.4 62.9 14.0  
8.1 1330 53.9 36.5 2.46 21.9 62.3 10.6  
8.1 1550 54.8 39.3 2.55 21.5 63.5 10.6  
1.8 1330 47.9 34.6 3.02 15.8 58.2 19.8  
1.8 1550 48.7 37.2 3.13 15.5 59.4 19.8  
4.4 1330 50.0 35.3 2.82 17.7 59.6 13.5  
4.4 1550 50.8 37.9 2.92 17.4 60.8 13.5  
7.8 1330 51.0 35.6 2.72 18.7 60.3 10.3  
7.8 1550 51.9 38.3 2.82 18.4 61.5 10.3  
1.9 1330 44.7 33.4 3.36 13.3 56.2 19.1  
1.9 1550 47.6 36.8 3.25 14.6 58.7 19.1  
4.4 1330 46.8 34.2 3.14 14.9 57.5 13.0  
4.4 1550 47.6 36.8 3.25 14.6 58.7 13.0  
1.0  
1.0  
2.4  
2.4  
4.2  
4.2  
0.9  
0.9  
2.2  
2.2  
3.9  
3.9  
0.8  
0.8  
2.0  
2.0  
3.6  
3.6  
0.8  
0.8  
2.0  
2.0  
3.5  
3.5  
0.8  
0.8  
1.9  
1.9  
3.4  
3.4  
0.8  
0.8  
1.9  
1.9  
3.3  
3.3  
2.3 1430 40.3 3.17  
2.3 1650 40.9 3.07  
5.6 1430 42.1 3.21  
5.6 1650 42.8 3.11  
9.7 1430 43.1 3.24  
9.7 1650 43.8 3.14  
2.0 1430 45.5 3.30  
2.0 1650 46.2 3.20  
5.1 1430 47.8 3.35  
5.1 1650 48.5 3.25  
9.0 1430 49.1 3.38  
9.0 1650 49.8 3.28  
1.9 1430 51.1 3.43  
1.9 1650 51.9 3.33  
4.7 1430 53.8 3.50  
4.7 1650 54.7 3.39  
8.4 1430 55.4 3.54  
8.4 1650 56.2 3.43  
1.8 1430 56.9 3.57  
1.8 1650 57.7 3.46  
4.5 1430 60.0 3.66  
4.5 1650 61.0 3.54  
8.1 1430 61.8 3.71  
8.1 1650 62.7 3.59  
1.8 1430 62.7 3.73  
1.8 1650 63.7 3.62  
4.4 1430 66.2 3.84  
4.4 1650 67.2 3.72  
7.8 1430 68.1 3.90  
7.8 1650 69.2 3.78  
1.9 1430 68.5 3.91  
1.9 1650 69.5 3.79  
4.4 1430 72.2 4.05  
4.4 1650 73.3 3.92  
7.7 1430 74.2 4.13  
7.7 1650 75.4 4.00  
40  
50  
9.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
38.6  
11.8  
9.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
60  
9.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
44.7 106.8 55.1  
45.9 102.4 15.3  
47.6 108.9 59.4  
48.9 104.2 10.9  
49.1 110.0 61.8  
70  
9.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
50.5 105.2  
8.4  
50.0 110.6 63.3  
51.3 105.7 17.1  
53.1 112.9 68.2  
54.5 107.7 12.1  
54.8 114.1 70.9  
80  
9.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
9.0  
12.0  
12.0  
56.3 108.8  
9.4  
55.1 114.3 71.6  
56.6 109.0 18.9  
58.4 116.8 77.0  
60.0 111.2 13.3  
60.1 118.1 80.0  
61.7 112.3 10.3  
90  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
7.7 1330 47.9 34.6 3.03 15.8 58.2  
7.7 1550 48.7 37.2 3.14 15.5 59.4  
1.9 1330 41.6 32.2 3.75 11.1 54.4 18.5  
1.9 1550 42.4 34.6 3.88 10.9 55.6 18.5  
4.3 1330 43.6 33.0 3.50 12.5 55.5 12.6  
4.3 1550 44.3 35.5 3.62 12.2 56.7 12.6  
9.9  
9.9  
100  
110  
120  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
7.6 1330 44.6 33.4 3.38 13.2 56.1  
7.6 1550 45.4 35.9 3.50 13.0 57.3  
9.6  
9.6  
53.1 18.1  
54.3 18.1  
1.8 1330 38.8 30.9 4.19  
1.8 1550 39.5 33.2 4.35  
9.2  
9.1  
4.3 1330 40.5 31.7 3.91 10.3 53.8 12.2  
4.3 1550 41.2 34.1 4.06 10.2 55.0 12.2  
7.5 1330 41.4 32.1 3.78 11.0 54.3  
7.5 1550 42.1 34.5 3.92 10.8 55.5  
Operation not recommended  
9.0  
12.0  
12.0  
6.0  
6.0  
9.0  
9.0  
12.0  
12.0  
9.2  
9.2  
52.5 17.9  
53.7 17.9  
52.7 12.0  
53.9 12.0  
1.6 1330 36.4 29.6 4.71  
1.6 1550 37.0 31.8 4.88  
4.1 1330 37.8 30.4 4.39  
4.1 1550 38.4 32.6 4.55  
7.4 1330 38.5 30.8 4.24  
7.4 1550 39.2 33.1 4.39  
7.7  
7.6  
8.6  
8.4  
9.1  
8.9  
53.0  
54.2  
9.0  
9.0  
Interpolation is permissible; extrapolation is not.  
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.  
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.  
See performance correction tables for operating conditions other than those listed above.  
For operation in the shaded areas, please see the Performance Data Selection Notes.  
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.  
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.  
Table does not reect fan or pump power corrections for AHRI/ISO conditions.  
All performance is based upon the lower voltage of dual voltage rated units.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Performance Data — HT 060 - Full Load  
1825 CFM Nominal (ISO Rated) Airflow Cooling, 2050 CFM Nominal (ISO Rated) Airflow Heating  
Performance capacities shown in thousands of Btuh  
Cooling - EAT 80/67°F  
Heating - EAT 70°F  
EWT  
WPD  
°F  
WPD  
PSI  
GPM  
CFM  
EER  
HR LWT HWC GPM  
CFM  
COP  
LAT LWT HWC  
TC SC kW  
HC kW  
HE  
PSI  
FT  
FT  
15.0  
15.0  
7.5  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
7.3 16.8 1750 42.8 3.89  
7.3 16.8 2050 43.4 3.77  
3.2  
3.4  
3.5  
3.6  
3.6  
3.8  
3.7  
3.9  
3.9  
4.1  
4.0  
4.2  
4.1  
4.3  
4.3  
4.5  
4.4  
4.6  
4.5  
4.7  
4.6  
4.8  
4.7  
5.0  
4.8  
5.1  
4.9  
5.1  
5.0  
5.3  
5.1  
5.3  
5.1  
5.4  
5.3  
5.5  
5.3  
5.6  
5.3  
5.6  
5.4  
5.7  
5.5  
5.8  
29.5 92.6  
30.6 89.6  
33.4 94.8  
34.5 91.5  
35.6 96.0  
36.7 92.5  
36.7 96.7  
37.9 93.1  
40.0 98.5  
41.3 94.7  
42.7 100.0 32.4  
44.0 96.0 7.8  
44.1 100.8 34.1  
45.5 96.7 6.1  
46.8 102.4 37.5  
48.2 98.0 12.8  
49.9 104.1 41.1  
51.3 99.6 9.1  
51.6 105.1 43.1  
53.0 100.4 7.1  
16.1  
4.1  
21.1  
9.2  
23.7  
6.5  
25.1  
5.1  
4.0  
3.8  
4.1  
4.0  
4.2  
4.1  
4.2  
4.1  
4.4  
4.2  
4.5  
4.4  
4.6  
4.4  
4.7  
4.6  
4.9  
4.7  
5.0  
4.8  
5.1  
5.0  
5.3  
5.2  
5.5  
5.3  
5.6  
5.4  
5.8  
5.7  
6.0  
5.8  
6.1  
5.9  
6.4  
6.2  
6.6  
6.4  
6.6  
6.4  
7.1  
6.9  
7.3  
7.1  
Operation not recommended  
20  
30  
7.5  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
1.7  
1.7  
3.7  
3.7  
3.9 1590 75.3 49.7 2.68 28.1 84.4 22.9  
3.9 1850 76.6 53.4 2.78 27.5 86.1 22.9  
8.6 1590 74.9 50.3 2.57 29.1 83.6 15.2  
8.6 1850 76.2 54.0 2.67 28.5 85.3 15.2  
1.9  
2.0  
1.8  
1.8  
1.8  
1.8  
2.3  
2.3  
2.0  
2.0  
1.9  
1.9  
2.8  
2.9  
2.4  
2.5  
2.2  
2.3  
3.5  
3.6  
3.0  
3.1  
2.8  
2.8  
4.4  
4.5  
3.8  
3.8  
3.5  
3.5  
5.5  
5.6  
4.7  
4.8  
4.3  
4.4  
6.7  
5.9  
5.8  
5.9  
5.4  
5.5  
8.1  
8.3  
7.1  
7.3  
6.7  
6.8  
9.8  
10.0  
8.7  
8.8  
8.2  
8.3  
11.7  
11.9  
10.4  
10.6  
9.8  
10.0  
1.7  
1.7  
3.7  
3.7  
3.9 1750 46.9 3.95  
3.9 2050 47.6 3.82  
8.6 1750 49.1 3.98  
8.6 2050 49.9 3.86  
6.1 14.1 1590 74.2 50.5 2.53 29.3 82.9 11.3  
6.1 14.1 1850 75.5 54.3 2.62 28.8 84.5 11.3  
6.1 14.1 1750 50.4 4.00  
6.1 14.1 2050 51.2 3.88  
1.2  
1.2  
3.0  
3.0  
2.7 1590 74.4 48.8 2.86 26.0 84.2 22.9  
2.7 1850 75.7 52.5 2.97 25.5 85.8 22.9  
7.0 1590 75.2 49.5 2.72 27.6 84.5 15.3  
7.0 1850 76.5 53.2 2.82 27.1 86.1 15.3  
1.2  
1.2  
3.0  
3.0  
2.7 1750 53.9 4.06  
2.7 2050 54.7 3.94  
7.0 1750 56.7 4.12  
7.0 2050 57.6 3.99  
29.3  
11.0  
7.5  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
40  
50  
5.3 12.2 1590 75.3 49.8 2.66 28.3 84.3 11.5  
5.3 12.2 1850 76.6 53.6 2.76 27.8 86.0 11.5  
5.3 12.2 1750 58.3 4.15  
5.3 12.2 2050 59.2 4.02  
0.9  
0.9  
2.6  
2.6  
2.0 1590 72.4 47.8 3.08 23.5 82.9 22.5  
2.0 1850 73.6 51.4 3.20 23.0 84.5 22.5  
6.0 1590 74.0 48.6 2.91 25.4 84.0 15.2  
6.0 1850 75.3 52.2 3.02 25.0 85.6 15.2  
0.9  
0.9  
2.6  
2.6  
2.0 1750 61.1 4.21  
2.0 2050 62.1 4.08  
6.0 1750 64.5 4.28  
6.0 2050 65.5 4.15  
7.5  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
4.7 10.8 1590 74.6 48.9 2.83 26.3 84.3 11.5  
4.7 10.8 1850 75.9 52.6 2.94 25.9 85.9 11.5  
4.7 10.8 1750 66.3 4.32  
4.7 10.8 2050 67.3 4.19  
0.7  
0.7  
2.4  
2.4  
1.7 1590 69.5 46.7 3.35 20.7 81.0 22.0  
1.7 1850 70.7 50.3 3.47 20.4 82.6 22.0  
5.4 1590 71.7 47.6 3.15 22.8 82.5 15.0  
5.4 1850 73.0 51.1 3.26 22.4 84.1 15.0  
0.7  
0.7  
2.4  
2.4  
1.7 1750 68.5 4.37  
1.7 2050 69.5 4.24  
5.4 1750 72.3 4.46  
5.4 2050 73.4 4.33  
53.6 106.2 45.7  
55.1 101.4 14.7  
57.1 108.3 49.9  
58.6 103.2 10.4  
59.0 109.4 52.1  
7.5  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
60  
4.3 10.0 1590 72.7 48.0 3.05 23.8 83.1 11.3  
4.3 10.0 1850 74.0 51.6 3.16 23.4 84.8 11.3  
4.3 10.0 1750 74.4 4.52  
4.3 10.0 2050 75.5 4.38  
60.6 104.1  
8.1  
0.7  
0.7  
2.3  
2.3  
4.1  
4.1  
0.8  
0.8  
2.2  
2.2  
4.1  
4.1  
0.8  
0.8  
2.3  
2.3  
4.0  
4.0  
0.9  
0.9  
2.3  
2.3  
4.0  
4.0  
0.8  
0.8  
2.2  
2.2  
4.0  
4.0  
0.6  
0.6  
2.0  
2.0  
3.8  
3.8  
1.7 1590 66.1 45.5 3.67 18.0 78.7 21.4  
1.7 1850 67.3 48.9 3.81 17.7 80.3 21.4  
5.2 1590 68.6 46.4 3.43 20.0 80.4 14.6  
5.2 1850 69.8 49.9 3.56 19.6 82.0 14.6  
9.5 1590 69.9 46.9 3.32 21.0 81.2 11.0  
9.5 1850 71.1 50.4 3.44 20.6 82.8 11.0  
1.8 1590 62.5 44.1 4.05 15.4 76.3 20.8  
1.8 1850 63.5 47.5 4.19 15.1 77.8 20.8  
5.2 1590 65.1 45.1 3.78 17.2 78.0 14.1  
5.2 1850 66.2 48.5 3.91 16.9 79.6 14.1  
9.4 1590 66.4 45.6 3.65 18.2 78.8 10.7  
9.4 1850 67.5 49.0 3.78 17.9 80.4 10.7  
2.0 1590 58.7 42.6 4.49 13.1 74.0 20.2  
2.0 1850 62.3 47.0 4.33 14.4 77.1 20.2  
5.2 1590 61.3 43.7 4.18 14.7 75.5 13.7  
5.2 1850 62.3 47.0 4.33 14.4 77.1 13.7  
9.3 1590 62.6 44.2 4.03 15.5 76.4 10.4  
9.3 1850 63.7 47.5 4.18 15.2 77.9 10.4  
2.0 1590 55.2 41.1 5.00 11.0 72.3 19.7  
2.0 1850 56.2 44.2 5.18 10.8 73.9 19.7  
5.2 1590 57.5 42.1 4.65 12.4 73.4 13.3  
5.2 1850 58.5 45.3 4.82 12.1 75.0 13.3  
9.3 1590 58.8 42.6 4.48 13.1 74.1 10.1  
9.3 1850 59.8 45.9 4.65 12.9 75.6 10.1  
0.7  
0.7  
2.3  
2.3  
4.1  
4.1  
0.8  
0.8  
2.2  
2.2  
4.1  
4.1  
0.8  
0.8  
2.3  
2.3  
4.0  
4.0  
1.7 1750 75.8 4.55  
1.7 2050 77.0 4.41  
5.2 1750 80.1 4.67  
5.2 2050 81.3 4.52  
9.5 1750 82.4 4.73  
9.5 2050 83.7 4.59  
1.8 1750 83.1 4.75  
1.8 2050 84.4 4.61  
5.2 1750 87.8 4.89  
5.2 2050 89.1 4.74  
9.4 1750 90.3 4.97  
9.4 2050 91.7 4.81  
2.0 1750 90.3 4.97  
2.0 2050 91.7 4.81  
5.2 1750 95.2 5.12  
5.2 2050 96.7 4.96  
9.3 1750 97.9 5.21  
9.3 2050 99.4 5.05  
60.3 110.1 53.9  
61.9 104.8 16.5  
64.2 112.4 58.6  
65.9 106.7 11.7  
66.3 113.6 61.2  
7.5  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
70  
68.0 107.8  
9.1  
66.9 114.0 62.2  
68.7 108.1 18.3  
71.1 116.4 67.4  
73.0 110.3 13.0  
73.4 117.8 70.2  
75.3 111.4 10.0  
73.3 117.8 70.4  
75.2 111.4 20.1  
77.8 120.4 76.2  
79.7 113.7 14.2  
80.1 121.8 79.3  
82.1 114.9 11.0  
7.5  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
80  
7.5  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
11.3  
11.3  
15.0  
15.0  
90  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
100  
110  
120  
1.8 1590 52.2 39.6 5.60  
1.8 1850 53.1 42.6 5.80  
9.3  
9.2  
71.3 19.4  
72.9 19.4  
7.5  
11.3  
11.3  
15.0  
15.0  
7.5  
5.1 1590 54.1 40.6 5.20 10.4 71.8 13.1  
5.1 1850 55.0 43.6 5.39 10.2 73.4 13.1  
9.2 1590 55.2 41.1 5.01 11.0 72.3  
9.2 1850 56.1 44.2 5.19 10.8 73.8  
Operation not recommended  
9.8  
9.8  
71.5 19.5  
73.1 19.5  
71.2 12.9  
72.8 12.9  
1.3 1590 50.0 38.5 6.30  
1.3 1850 50.8 41.4 6.53  
4.7 1590 51.3 39.2 5.83  
4.7 1850 52.2 42.1 6.04  
8.8 1590 52.1 39.6 5.62  
8.8 1850 53.0 42.6 5.82  
7.9  
7.8  
8.8  
8.6  
9.3  
9.1  
7.5  
11.3  
11.3  
15.0  
15.0  
71.3  
72.9  
9.7  
9.7  
Interpolation is permissible; extrapolation is not.  
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.  
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.  
See performance correction tables for operating conditions other than those listed above.  
For operation in the shaded areas, please see the Performance Data Selection Notes.  
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.  
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.  
Table does not reect fan or pump power corrections for AHRI/ISO conditions.  
All performance is based upon the lower voltage of dual voltage rated units.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Performance Data — HT 070 - Full Load  
1950 CFM Nominal (Rated) Airflow Cooling, 2100 CFM Nominal (Rated) Airflow Heating  
P erformance capacities shown in thousands of Btuh  
Cooling - EAT 80/67°F  
Heating - EAT 70°F  
EWT  
WPD  
°F  
WPD  
PSI  
GPM  
CFM  
EER  
HR LWT HWC GPM  
CFM  
COP  
LAT LWT HWC  
TC SC kW  
HC kW  
HE  
PSI  
FT  
FT  
17.0  
17.0  
8.5  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
8.9 20.6 1750 46.6 4.66  
8.9 20.6 2050 47.3 4.52  
2.9  
3.1  
3.2  
3.3  
3.3  
3.4  
3.3  
3.5  
3.5  
3.7  
3.6  
3.8  
3.7  
3.9  
3.8  
4.0  
3.9  
4.1  
4.0  
4.2  
4.1  
4.3  
4.2  
4.4  
4.3  
4.5  
4.3  
4.5  
4.4  
4.6  
4.5  
4.7  
4.5  
4.7  
4.6  
4.9  
4.7  
4.9  
4.7  
4.9  
4.8  
5.1  
4.9  
5.1  
30.7 94.7  
31.9 91.4  
35.3 97.3  
36.6 93.7  
37.5 98.6  
38.8 94.8  
38.7 99.2  
40.1 95.3  
42.4 101.4 30.0  
43.9 97.2 10.3  
45.0 102.9 32.9  
46.5 98.5 7.3  
46.4 103.7 34.5  
47.9 99.2 5.6  
49.4 105.4 38.4  
50.9 100.7 12.0  
52.3 107.1 41.8  
53.9 102.1  
53.8 108.0 43.7  
55.5 102.9 6.5  
56.2 109.4 46.8  
57.9 104.1 13.6  
59.4 111.3 50.7  
61.2 105.8  
61.2 112.3 52.8  
63.0 106.7 7.4  
62.9 113.3 55.2  
64.8 107.6 15.2  
66.6 115.5 59.6  
68.5 109.4 10.7  
68.6 116.7 61.9  
16.4  
3.8  
21.7  
8.6  
24.1  
6.1  
25.4  
4.7  
5.2  
5.0  
5.4  
5.2  
5.5  
5.4  
5.6  
5.5  
5.9  
5.7  
6.1  
5.9  
6.2  
6.1  
6.5  
6.3  
6.8  
6.6  
7.0  
6.8  
7.3  
7.1  
7.7  
7.4  
7.9  
7.7  
8.1  
7.9  
8.6  
8.4  
8.9  
8.7  
9.1  
8.8  
9.8  
9.5  
10.1  
9.8  
10.2  
9.9  
11.0  
10.7  
11.4  
11.1  
Operation not recommended  
20  
30  
8.5  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
2.2  
2.2  
5.1 1590 82.4 50.1 3.04 27.1 92.8 22.2  
5.1 1850 83.8 53.9 3.15 26.6 94.6 22.2  
4.6 10.6 1590 82.3 50.0 2.90 28.4 92.2 14.7  
4.6 10.6 1850 83.7 53.8 3.00 27.9 93.9 14.7  
7.6 17.6 1590 81.9 49.8 2.84 28.9 91.6 11.0  
7.6 17.6 1850 83.3 53.5 2.94 28.3 93.3 11.0  
3.6  
3.7  
3.6  
3.7  
3.6  
3.7  
3.9  
4.0  
3.6  
3.7  
3.6  
3.7  
4.5  
4.6  
4.0  
4.1  
3.8  
3.9  
5.4  
5.6  
4.7  
4.8  
4.4  
4.5  
6.7  
6.8  
5.8  
5.9  
5.4  
5.5  
8.2  
8.4  
7.1  
7.3  
6.6  
6.7  
10.0  
9.0  
8.8  
9.0  
8.2  
8.4  
12.2  
12.5  
10.8  
11.0  
10.1  
10.3  
14.7  
15.0  
13.1  
13.4  
12.3  
12.6  
17.6  
18.0  
15.8  
16.1  
14.9  
15.2  
2.2  
2.2  
5.1 1750 51.6 4.77  
5.1 2050 52.4 4.63  
4.6 10.6 1750 54.0 4.83  
4.6 10.6 2050 54.8 4.68  
7.6 17.6 1750 55.3 4.86  
7.6 17.6 2050 56.1 4.71  
1.6  
1.6  
3.9  
3.9  
3.8 1590 81.3 49.8 3.27 24.9 92.4 22.2  
3.8 1850 82.7 53.5 3.39 24.4 94.3 22.2  
8.9 1590 82.2 50.1 3.09 26.6 92.8 14.8  
8.9 1850 83.6 53.9 3.21 26.1 94.6 14.8  
1.6  
1.6  
3.9  
3.9  
3.8 1750 59.4 4.96  
3.8 2050 60.3 4.80  
8.9 1750 62.1 5.02  
8.9 2050 63.1 4.87  
8.5  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
40  
50  
6.7 15.5 1590 82.4 50.1 3.02 27.3 92.7 11.1  
6.7 15.5 1850 83.8 53.9 3.13 26.8 94.5 11.1  
6.7 15.5 1750 63.6 5.06  
6.7 15.5 2050 64.6 4.90  
1.3  
1.3  
3.4  
3.4  
3.0 1590 79.1 49.0 3.54 22.3 91.2 21.9  
3.0 1850 80.5 52.6 3.67 21.9 93.0 21.9  
7.8 1590 80.8 49.6 3.34 24.2 92.2 14.7  
7.8 1850 82.2 53.3 3.46 23.8 94.0 14.7  
1.3  
1.3  
3.4  
3.4  
3.0 1750 66.9 5.14  
3.0 2050 67.9 4.99  
7.8 1750 70.1 5.23  
7.8 2050 71.2 5.07  
8.5  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
8.5  
6.0 13.9 1590 81.5 49.8 3.24 25.1 92.5 11.1  
6.0 13.9 1850 82.9 53.6 3.36 24.7 94.3 11.1  
6.0 13.9 1750 71.8 5.27  
6.0 13.9 2050 72.9 5.11  
1.2  
1.2  
3.1  
3.1  
2.7 1590 76.1 47.8 3.87 19.6 89.3 21.4  
2.7 1850 77.4 51.4 4.01 19.3 91.1 21.4  
7.1 1590 78.3 48.7 3.63 21.6 90.7 14.5  
7.1 1850 79.7 52.3 3.76 21.2 92.5 14.5  
1.2  
1.2  
3.1  
3.1  
2.7 1750 74.4 5.34  
2.7 2050 75.5 5.18  
7.1 1750 78.0 5.44  
7.1 2050 79.2 5.28  
8.5  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
60  
9.6  
5.6 13.0 1590 79.3 49.1 3.52 22.6 91.3 11.0  
5.6 13.0 1850 80.7 52.7 3.64 22.2 93.1 11.0  
5.6 13.0 1750 80.0 5.50  
5.6 13.0 2050 81.2 5.33  
1.1  
1.1  
3.0  
3.0  
2.6 1590 72.4 46.3 4.26 17.0 87.0 20.9  
2.6 1850 73.7 49.8 4.42 16.7 88.7 20.9  
6.8 1590 75.0 47.4 3.98 18.9 88.6 14.2  
6.8 1850 76.3 50.9 4.12 18.5 90.4 14.2  
1.1  
1.1  
3.0  
3.0  
2.6 1750 81.9 5.56  
2.6 2050 83.2 5.38  
6.8 1750 86.0 5.68  
6.8 2050 87.3 5.50  
8.5  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
70  
5.4 12.4 1590 76.3 47.9 3.85 19.8 89.4 10.7  
5.4 12.4 1850 77.6 51.5 3.99 19.5 91.2 10.7  
5.4 12.4 1750 88.2 5.75  
5.4 12.4 2050 89.5 5.57  
70.5 110.4  
8.3  
1.2  
1.2  
2.9  
2.9  
2.7 1590 68.4 44.7 4.72 14.5 84.5 20.3  
2.7 1850 69.5 48.1 4.89 14.2 86.2 20.3  
6.7 1590 71.2 45.8 4.40 16.2 86.2 13.8  
6.7 1850 72.4 49.3 4.56 15.9 88.0 13.8  
1.2  
1.2  
2.9  
2.9  
2.7 1750 89.5 5.79  
2.7 2050 90.9 5.61  
6.7 1750 94.1 5.93  
6.7 2050 95.5 5.75  
69.8 117.4 63.6  
71.7 111.0 16.9  
73.9 119.8 68.4  
75.9 113.2 11.9  
76.1 121.1 71.0  
8.5  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
80  
5.2 12.1 1590 72.6 46.4 4.24 17.1 87.1 10.5  
5.2 12.1 1850 73.8 49.9 4.40 16.8 88.8 10.5  
5.2 12.1 1750 96.7 6.02  
5.2 12.1 2050 98.1 5.83  
78.2 114.3  
9.2  
1.2  
1.2  
2.9  
2.9  
2.8 1590 64.1 43.0 5.26 12.2 82.0 19.7  
2.8 1850 68.1 47.4 5.07 13.4 85.4 19.7  
6.7 1590 67.0 44.1 4.89 13.7 83.6 13.4  
6.7 1850 68.1 47.4 5.07 13.4 85.4 13.4  
1.2  
1.2  
2.9  
2.9  
2.8 1750 97.3 6.04  
2.8 2050 98.8 5.85  
6.7 1750 102.6 6.22  
6.7 2050 104.1 6.03  
76.7 121.5 72.0  
78.8 114.6 18.5  
81.3 124.3 77.2  
83.6 117.0 13.1  
83.9 125.8 80.1  
86.2 118.4 10.1  
8.5  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
12.8  
12.8  
17.0  
17.0  
90  
5.2 12.0 1590 68.4 44.7 4.71 14.5 84.5 10.1  
5.2 12.0 1850 69.6 48.1 4.88 14.2 86.3 10.1  
5.2 12.0 1750 105.5 6.32  
5.2 12.0 2050 107.1 6.12  
1.2  
1.2  
2.9  
2.9  
2.8 1590 59.8 41.2 5.88 10.2 79.9 19.2  
2.8 1850 60.9 44.3 6.09 10.0 81.6 19.2  
6.7 1590 62.6 42.3 5.46 11.5 81.2 13.0  
6.7 1850 63.7 45.5 5.66 11.2 83.0 13.0  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
100  
110  
120  
5.2 12.0 1590 64.0 42.9 5.27 12.2 82.0  
5.2 12.0 1850 65.1 46.2 5.46 11.9 83.8  
9.9  
9.9  
78.2 18.8  
80.0 18.8  
79.2 12.7  
81.0 12.7  
9.6  
9.6  
77.4 18.6  
79.2 18.6  
77.8 12.5  
79.6 12.5  
1.1  
1.1  
2.9  
2.9  
2.6 1590 55.7 39.5 6.61  
2.6 1850 56.7 42.5 6.85  
6.6 1590 58.3 40.6 6.13  
6.6 1850 59.3 43.6 6.36  
8.4  
8.3  
9.5  
9.3  
8.5  
12.8  
12.8  
17.0  
17.0  
8.5  
Operation not recommended  
5.1 11.8 1590 59.6 41.1 5.91 10.1 79.8  
5.1 11.8 1850 60.7 44.2 6.12  
9.9  
7.0  
6.8  
7.8  
7.7  
8.3  
8.2  
81.6  
0.9  
0.9  
2.7  
2.7  
2.1 1590 52.0 38.1 7.45  
2.1 1850 52.9 41.0 7.72  
6.2 1590 54.2 39.0 6.91  
6.2 1850 55.2 41.9 7.16  
8.5  
12.8  
12.8  
17.0  
17.0  
5.0 11.5 1590 55.5 39.4 6.65  
5.0 11.5 1850 56.4 42.4 6.90  
78.2  
80.0  
9.4  
9.4  
Interpolation is permissible; extrapolation is not.  
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.  
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.  
See performance correction tables for operating conditions other than those listed above.  
For operation in the shaded areas, please see the Performance Data Selection Notes.  
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.  
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.  
Table does not reect fan or pump power corrections for AHRI/ISO conditions.  
All performance is based upon the lower voltage of dual voltage rated units.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Preventive Maintenance  
Water Coil Maintenance  
months to minimize the problem. The condensate pan may also  
need to be cleaned periodically to insure indoor air quality. The  
condensate drain can pick up lint and dirt, especially with dirty  
lters. Inspect the drain twice a year to avoid the possibility of  
plugging and eventual overow.  
(Direct ground water applications only) - If the system is installed  
in an area with a known high mineral content (125 P.P.M. or  
greater) in the water, it is best to establish a periodic maintenance  
schedule with the owner so the coil can be checked regularly.  
Consult the well water applications section of this manual for a  
more detailed water coil material selection. Should periodic coil  
cleaning be necessary, use standard coil cleaning procedures,  
which are compatible with the heat exchanger material and  
copper water lines. Generally, the more water owing through  
the unit, the less chance for scaling. Therefore, 1.5 gpm per ton  
[2.0 l/m per kW] is recommended as a minimum ow. Minimum  
ow rate for entering water temperatures below 50°F [10°C] is 2.0  
gpm per ton [2.6 l/m per kW].  
Compressor  
Conduct annual amperage checks to insure that amp draw is no  
more than 10% greater than indicated on the serial plate data.  
Fan Motors  
All units have lubricated fan motors. Fan motors should never be  
lubricated unless obvious, dry operation is suspected. Periodic  
maintenance oiling is not recommended, as it will result in dirt  
accumulating in the excess oil and cause eventual motor failure.  
Conduct annual dry operation check and amperage check to  
insure amp draw is no more than 10% greater than indicated on  
serial plate data.  
Water Coil Maintenance  
(All other water loop applications)  
Generally water coil maintenance is not needed for closed loop  
systems. However, if the piping is known to have high dirt or  
debris content, it is best to establish a periodic maintenance  
schedule with the owner so the water coil can be checked  
regularly. Dirty installations are typically the result of deterioration  
of iron or galvanized piping or components in the system.  
Open cooling towers requiring heavy chemical treatment and  
mineral buildup through water use can also contribute to higher  
maintenance. Should periodic coil cleaning be necessary, use  
standard coil cleaning procedures, which are compatible with both  
the heat exchanger material and copper water lines. Generally,  
the more water owing through the unit, the less chance for  
scaling. However, ow rates over 3 gpm per ton (3.9 l/m per kW)  
can produce water (or debris) velocities that can erode the heat  
exchanger wall and ultimately produce leaks.  
Air Coil  
The air coil must be cleaned to obtain maximum performance.  
Check once a year under normal operating conditions and, if  
dirty, brush or vacuum clean. Care must be taken not to damage  
the aluminum ns while cleaning. CAUTION: Fin edges are sharp.  
Cabinet  
Do not allow water to stay in contact with the cabinet for long  
periods of time to prevent corrosion of the cabinet sheet metal.  
Generally, vertical cabinets are set up from the oor a few inches  
[7 - 8 cm] to prevent water from entering the cabinet. The cabinet  
can be cleaned using a mild detergent.  
Refrigerant System  
Hot Water Generator Coils  
To maintain sealed circuit integrity, do not install service gauges  
unless unit operation appears abnormal. Reference the operating  
charts for pressures and temperatures. Verify that air and water  
ow rates are at proper levels before servicing the refrigerant  
circuit.  
See water coil maintenance for ground water units. If the potable  
water is hard or not chemically softened, the high temperatures  
of the desuperheater will tend to scale even quicker than the  
water coil and may need more frequent inspections. In areas with  
extremely hard water, a HWG is not recommended.  
Filters  
Filters must be clean to obtain maximum performance. Filters  
should be inspected every month under normal operating  
conditions and be replaced when necessary. Units should never  
be operated without a lter.  
Washable, high efciency, electrostatic lters, when dirty, can  
exhibit a very high pressure drop for the fan motor and reduce  
air ow, resulting in poor performance. It is especially important  
to provide consistent washing of these lters (in the opposite  
direction of the normal air ow) once per month using a high  
pressure wash similar to those found at self-serve car washes.  
Condensate Drain  
In areas where airborne bacteria may produce a “slimy”  
substance in the drain pan, it may be necessary to treat the drain  
pan chemically with an algaecide approximately every three  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Troubleshooting  
CXM Troubleshooting Process Flowchart/Functional  
Troubleshooting Chart  
General  
If operational difculties are encountered, perform the preliminary  
checks below before referring to the troubleshooting charts.  
Verify that the unit is receiving electrical supply power.  
• Make sure the fuses in the fused disconnect switches  
are intact.  
After completing the preliminary checks described above,  
inspect for other obvious problems such as leaking connections,  
broken or disconnected wires, etc. If everything appears to  
be in order, but the unit still fails to operate properly, refer to  
the “CXM Troubleshooting Process Flowchart” or “Functional  
Troubleshooting Chart.”  
The CXM Functional Troubleshooting Process Flowchart”  
is a quick overview of how to start diagnosing a suspected  
problem, using the fault recognition features of the CXM board.  
The Functional Troubleshooting Chart” on the following page  
is a more comprehensive method for identifying a number of  
malfunctions that may occur, and is not limited to just the CXM  
controls. Within the chart are ve columns:  
• The Fault” column describes the symptoms.  
• Columns 2 and 3 identify in which mode the fault is likey to  
occur, heating or cooling.  
• The Possible Cause column” identies the most likely sources  
of the problem.  
• The Solution” column describes what should be done to  
correct the problem.  
CXM Board  
CXM board troubleshooting in general is best summarized as  
simply verifying inputs and outputs. After inputs and outputs  
have been veried, board operation is conrmed and the problem  
must be elsewhere. Below are some general guidelines for  
troubleshooting the CXM control.  
WARNING! ꢀ  
WARNING! HAZARDOUS VOLTAGE! DISCONNECT  
ALL ELECTRIC POWER INCLUDING REMOTE  
DISCONNECTS BEFORE SERVICING.  
Failure to disconnect power before servicing can cause  
severe personal injury or death.  
Field Inputs  
All inputs are 24VAC from the thermostat and can be veried  
using a volt meter between C and Y, G, O, W. 24VAC will be  
present at the terminal (for example, between Y” and C) if the  
thermostat is sending an input to the CXM board.  
Sensor Inputs  
All sensor inputs are ‘paired wires’ connecting each component to  
the board. Therefore, continuity on pressure switches, for example  
can be checked at the board connector.  
The thermistor resistance should be measured with the  
connector removed so that only the impedance of the thermistor  
is measured. If desired, this reading can be compared to the  
thermistor resistance chart shown in the CXM AOM manual. An  
ice bath can be used to check calibration of the thermistor.  
Outputs  
The compressor relay is 24VAC and can be veried using a  
voltmeter. The fan signal is passed through the board to the  
external fan relay (units with PSC motors only). The alarm relay  
can either be 24VAC as shipped or dry contacts for use with  
DDC controls by clipping the JW1 jumper. Electric heat outputs  
are 24VDC ground sinking” and require a volt meter set for DC  
to verify operation. The terminal marked “24VDC” is the 24VDC  
supply to the electric heat board; terminal “EH1” is stage 1 electric  
heat; terminal EH2” is stage 2 electric heat. When electric heat  
is energized (thermostat is sending a W” input to the CXM  
controller), there will be 24VDC between terminal 24VDC” and  
EH1” (stage 1 electric heat) and/or EH2” (stage 2 electric heat).  
A reading of 0VDC between 24VDC” and EH1” or EH2” will  
indicate that the CXM board is NOT sending an output signal to  
the electric heat board.  
Test Mode  
Test mode can be entered for 20 minutes by shorting the test  
pins. The CXM board will automatically exit test mode after 20  
minutes.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
CXM Process Flow Chart  
WARNING! ꢀ  
WARNING! HAZARDOUS VOLTAGE! DISCONNECT  
ALL ELECTRIC POWER INCLUDING REMOTE  
DISCONNECTS BEFORE SERVICING.  
Failure to disconnect power before servicing can cause  
severe personal injury or death.  
CXM Functional  
Troubleshooting Flow Chart  
Start  
Did Unit  
Attempt to  
Start?  
Check Main  
power (see power  
problems)  
No  
Yes  
Did Unit  
Lockout at  
Start-up?  
Yes  
Check fault LED code  
on control board  
No fault  
shown  
No  
See Unit  
short  
cycles”  
See  
LP/LOC  
Fault  
See FP1  
Fault  
Yes  
Yes  
Yes  
Unit Short  
Cycles?  
See HP  
Fault  
Replace  
CXM  
No  
See FP2  
Fault  
See  
See Over/  
Under  
Voltage  
See Only  
Fan Runs”  
Only Fan  
Runs?  
Condensate  
Fault  
No  
Only  
Compressor  
Runs?  
See Only  
Comp  
Runs”  
No  
Did unit lockout  
after a period of  
operation?  
Yes  
No  
Does unit  
operate in  
cooling?  
See Does  
not Operate  
in Clg”  
No  
Yes  
Unit is OK!  
‘See Performance  
Troubleshooting’ for  
further help  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Functional Troubleshooting  
Fault  
Htg Clg Possible Cause  
Solution  
Check line voltage circuit breaker and disconnect.  
Check for line voltage between L1 and L2 on the contactor.  
Check for 24VAC between R and C on CXM/DXM'  
Check primary/secondary voltage on transformer.  
Check pump operation or valve operation/setting.  
Check water ow adjust to proper ow rate.  
X
X
Green Status LED Off  
Main power problems  
X
X
Reduced or no water ow in cooling  
Water Temperature out of range in cooling  
Bring water temp within design parameters.  
Check for dirty air lter and clean or replace.  
Check fan motor operation and airow restrictions.  
Dirty Air Coil- construction dust etc.  
HP Fault  
Code 2  
X
Reduced or no air ow in heating  
High Pressure  
Too high of external static. Check static vs blower table.  
Bring return air temp within design parameters.  
Check superheat/subcooling vs typical operating condition table.  
Check switch continuity and operation. Replace.  
Check for refrigerant leaks  
X
X
X
X
Air temperature out of range in heating  
Overcharged with refrigerant  
Bad HP Switch  
X
X
X
Insufcient charge  
LP/LOC Fault  
Code 3  
X
X
Compressor pump down at start-up  
Check charge and start-up water ow.  
Low Pressure / Loss of Charge  
Check pump operation or water valve operation/setting.  
Plugged strainer or lter. Clean or replace..  
Check water ow adjust to proper ow rate.  
Check antifreeze density with hydrometer.  
Reduced or no water ow in heating  
LT1 Fault  
Code 4  
X
X
Inadequate antifreeze level  
Improper temperature limit setting (30°F vs  
10°F [-1°C vs -2°C])  
Clip JW3 jumper for antifreeze (10°F [-12°C]) use.  
Water coil low  
temperature limit  
X
X
Water Temperature out of range  
Bad thermistor  
Bring water temp within design parameters.  
X
X
Check temp and impedance correlation per chart  
Check for dirty air lter and clean or replace.  
Reduced or no air ow in cooling  
Check fan motor operation and airow restrictions.  
Too high of external static. Check static vs blower table.  
Too much cold vent air? Bring entering air temp within design parameters.  
LT2 Fault  
Code 5  
X
X
Air Temperature out of range  
Air coil low  
temperature limit  
Improper temperature limit setting (30°F vs  
10°F [-1°C vs -12°C])  
Normal airside applications will require 30°F [-1°C] only.  
X
X
X
X
X
X
Bad thermistor  
Blocked drain  
Improper trap  
Check temp and impedance correlation per chart.  
Check for blockage and clean drain.  
Check trap dimensions and location ahead of vent.  
Check for piping slope away from unit.  
Check slope of unit toward outlet.  
X
Poor drainage  
Condensate Fault  
Code 6  
Poor venting. Check vent location.  
X
X
X
Moisture on sensor  
Plugged air lter  
Check for moisture shorting to air coil.  
X
x
Replace air lter.  
Restricted Return Air Flow  
Find and eliminate restriction. Increase return duct and/or grille size.  
Check power supply and 24VAC voltage before and during operation.  
Check power supply wire size.  
Over/Under  
Voltage Code 7  
X
X
X
X
Under Voltage  
Check compressor starting. Need hard start kit?  
Check 24VAC and unit transformer tap for correct power supply voltage.  
Check power supply voltage and 24VAC before and during operation.  
Check 24VAC and unit transformer tap for correct power supply voltage.  
Check for poor air ow or overcharged unit.  
(Auto resetting)  
X
X
Over Voltage  
Heating mode FP2>125°F [52°C]  
Unit Performance Sentinel  
Code 8  
Cooling Mode FP1>125°F [52°C] OR FP2<  
40ºF [4ºC])  
Check for poor water ow, or air ow.  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
No compressor operation  
Compressor overload  
Control board  
See "Only Fan Operates".  
Check and replace if necessary.  
No Fault Code Shown  
Unit Short Cycles  
Reset power and check operation.  
Dirty air lter  
Check and clean air lter.  
Unit in "test mode"  
Unit selection  
Reset power or wait 20 minutes for auto exit.  
Unit may be oversized for space. Check sizing for actual load of space.  
Check and replace if necessary  
Compressor overload  
Thermostat position  
Unit locked out  
Ensure thermostat set for heating or cooling operation.  
Check for lockout codes. Reset power.  
Check compressor overload. Replace if necessary.  
Compressor Overload  
Only Fan Runs  
Check thermostat wiring at heat pump. Jumper Y and R for compressor operation  
in test mode.  
X
X
Thermostat wiring  
Thermostat wiring  
X
X
X
X
Check G wiring at heat pump. Jumper G and R for fan operation  
Jumper G and R for fan operation. Check for Line voltage across BR contacts.  
Fan motor relay  
Only Compressor Runs  
X
X
X
X
Check fan power enable relay operation (if present).  
Check for line voltage at motor. Check capacitor.  
Fan motor  
Check thermostat wiring at heat pump. Jumper Y and R for compressor operation  
in test mode  
X
X
Thermostat wiring  
Set for cooling demand and check 24VAC on RV coil and at CXM/DXM board.  
X
Reversing valve  
If RV is stuck, run high pressure up by reducing water ow and while operating  
engage and disengage RV coil voltage to push valve.  
X
X
Thermostat setup  
Thermostat wiring  
Check for ‘O’ RV setup not ‘B’.  
Unit Doesn’t Operate  
in Cooling  
Check O wiring at heat pump. Jumper O and R for RV coil ‘click’.  
Put thermostat in cooling mode. Check 24 VAC on O (check between C and  
O); check for 24 VAC on W (check between W and C). There should be voltage  
on O, but not on W. If voltage is present on W, thermostat may be bad or wired  
incorrectly.  
X
Thermostat wiring  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Performance Troubleshooting  
Performance Troubleshooting  
Htg Clg Possible Cause  
Solution  
X
X
Dirty lter  
Replace or clean.  
Check for dirty air lter and clean or replace.  
Check fan motor operation and airow restrictions.  
Too high of external static. Check static vs. blower table.  
Check for dirty air lter and clean or replace.  
Check fan motor operation and airow restrictions.  
Too high of external static. Check static vs. blower table.  
X
Reduced or no air ow in heating  
X
X
Reduced or no air ow in cooling  
Insufcient capacity/ Not  
Check supply and return air temperatures at the unit and at distant duct registers  
if signicantly different, duct leaks are present.  
X
Leaky duct work  
cooling or heating  
X
X
X
X
X
X
X
X
X
Low refrigerant charge  
Check superheat and subcooling per chart.  
Restricted metering device  
Defective reversing valve  
Thermostat improperly located  
Unit undersized  
Check superheat and subcooling per chart. Replace.  
Perform RV touch test.  
X
X
X
X
Check location and for air drafts behind stat.  
Recheck loads & sizing. Check sensible clg. load and heat pump capacity.  
Perform scaling check and clean if necessary.  
Check load, loop sizing, loop backll, ground moisture.  
Check for dirty air lter and clean or replace.  
Scaling in water heat exchanger  
Inlet water too hot or too cold  
X
Reduced or no air ow in heating  
Reduced or no water ow in cooling  
Check fan motor operation and air ow restrictions.  
Too high of external static. Check static vs. blower table.  
Check pump operation or valve operation/setting.  
Check water ow. Adjust to proper ow rate.  
X
X
High Head Pressure  
Inlet water too hot  
Check load, loop sizing, loop backll, ground moisture.  
Bring return air temperature within design parameters.  
Perform scaling check and clean if necessary.  
Check superheat and subcooling. Re-weigh in charge.  
Vacuum system and re-weigh in charge.  
X
Air temperature out of range in heating  
Scaling in water heat exchanger  
Unit overcharged  
X
X
X
X
X
X
X
Non-condensables in system  
Restricted metering device.  
Check superheat and subcooling per chart. Replace.  
Check pump operation or water valve operation/setting.  
Plugged strainer or lter. Clean or replace.  
X
X
Reduced water ow in heating.  
Water temperature out of range.  
Reduced air ow in cooling.  
Check water ow. Adjust to proper ow rate.  
Bring water temperature within design parameters.  
Check for dirty air lter and clean or replace.  
Low Suction Pressure  
X
Check fan motor operation and air ow restrictions.  
Too high of external static. Check static vs. blower table.  
Too much cold vent air? Bring entering air temperature within design parameters.  
Check for refrigerant leaks.  
X
X
Air temperature out of range  
Insufcient charge  
Too high of air ow  
Poor performance  
Too high of air ow  
Unit oversized  
X
X
X
Check fan motor speed selection and air ow chart.  
See ‘Insufcient Capacity’  
Low Discharge Air Temperature  
in Heating  
X
X
Check fan motor speed selection and airow chart.  
Recheck loads & sizing. Check sensible clg load and heat pump capacity.  
High humidity  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation, Operation & Maintenance  
HTV/HTD/HTH SERIES  
Heat Controller, Inc.  
Troubleshooting Form  
'DWHꢇꢀꢀBBBBBBBBBBBBBBBBBBBBBBBB  
$QWLIUHH]HꢇꢀꢀBBBBBBBBBBBBBBBBBBBBBBBB  
3DFNDJHGꢀ8QLWꢀ5HIULJHUDWLRQꢀ6FKHPDWLF  
&XVWRPHUꢇꢀꢀBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB  
0RGHOꢈꢇꢀꢀBBBBBBBBBBBBBBBBBBBBBBBBꢀꢀꢀ6HULDOꢈꢇꢀꢀBBBBBBBBBBBBBBBB /RRSꢀW\SHꢇꢀꢀBBBBBBBBBBBBBBB  
&RPSODLQWꢇ BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB  
+($7,1*ꢀ&<&/(ꢀ$1$/<6,6   
36,  
6$7  
$)  
$,5  
&2,/  
68&7,21  
$)  
$)  
&2035(6625  
',6&+$5*(  
(;3$16,21 ),/7(5  
&2$;  
9$/9(  
'5,(5ꢍ  
+:*  
$)  
$)  
$)  
$)  
36,  
6$7  
)/$6+  
)3ꢃꢇꢀ+($7,1*  
/,48,'ꢀ/,1(  
)3ꢂ  
6(1625  
$)  
36,  
:$7(5ꢀ,1  
$)  
36,  
:$7(5ꢀ287  
*$6ꢀ/,1(  
Look up pressure drop in  
I.O.M. or spec. catalog to  
determine flow rate.  
&22/,1*ꢀ&<&/(ꢀ$1$/<6,6   
5HIULJHUDQWꢀ7\SHꢇ  
36,  
6$7  
$)  
$,5  
&2,/  
+)&ꢉꢌꢂꢅ$  
68&7,21  
$)  
$)  
&2035(6625  
',6&+$5*(  
(;3$16,21 ),/7(5  
9$/9( '5,(5ꢍ  
&2$;  
+:*  
9ROWDJHꢇꢀꢀBBBBBBBB  
$)  
&RPSꢀ$PSVꢇꢀꢀBBBBBBB  
7RWDOꢀ$PSVꢇꢀꢀBBBBBBBB  
$)  
$)  
$)  
36,  
6$7  
$)  
36,  
:$7(5ꢀ,1  
$)  
36,  
:$7(5ꢀ287  
27+(5ꢀ6,'(  
2)ꢀ),/75ꢀ'5  
)3ꢃꢇꢀ)/$6+  
*$6ꢀ/,1(  
)3ꢂꢇꢀ&/*  
/,4ꢀ/,1(  
Look up pressure drop in  
I.O.M. or spec. catalog to  
determine flow rate.  
+HDWꢀRIꢀ([WUDFWLRQꢀꢎ$EVRUSWLRQꢏꢀRUꢀ+HDWꢀRIꢀ5HMHFWLRQꢀ  
________ IORZꢀUDWHꢀJSPꢏꢀꢀ[ꢀꢀBBBBBBBBꢀWHPSꢁGLIIꢁꢀꢎGHJꢁꢀ)ꢏꢀꢀ[ꢀꢀBBBBBBBBꢀIOXLG IDFWRU ꢀꢀ ꢀBBBBBBBBBBBBB  
ꢎ%WXꢄKUꢏ  
 
 
 
 
6XFWLRQꢀWHPSHUDWXUH ꢉꢀVXFWLRQꢀVDWXUDWLRQꢀWHPSꢁ  
'LVFKDUJHꢀVDWXUDWLRQꢀWHPSꢁ  OLTXLGꢀOLQHꢀWHPSꢁ  
6XSHUKHDW  
6XEFRROLQJ  
ꢎGHJꢀ)ꢏ  
ꢎGHJꢀ)ꢏ  
5HYꢁꢀꢂꢃꢄꢅꢆ  
8VHꢀꢊꢅꢅꢀIRUꢀZDWHUꢋꢀꢌꢆꢊꢀIRUꢀDQWLIUHH]Hꢁ  
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to determine water  
ow and temperature difference. If water-side analysis shows poor performance, refrigerant troubleshooting may be required. Connect  
refrigerant gauges as a last resort.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*97B00  
97B00???????  
*
01-2013  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Sander H8120 User Manual
Grundig Radio GUSR91DAB User Manual
Haier Water Heater FCD JTHA30 ET User Manual
Harbor Freight Tools Kitchen Utensil 66473 User Manual
Harman Kardon Speaker System SoundSticks III User Manual
Hasselblad Camera Lens CFE 56 250 User Manual
Hearth and Home Technologies Indoor Fireplace SL 350TRS D User Manual
Heath Zenith Door 595 5707 06 User Manual
Heath Zenith Work Light UT 9250 BZ User Manual
Honeywell Thermostat CT3500 User Manual