Hearth and Home Technologies Ventilation Hood HRV200PLUS User Manual |
INSTALLATION & OPERATING
INSTRUCTIONS
HRV200PLUS
HEAT RECOVERY VENTILATOR
DESIGNED TO OPERATE WITH THE FOLLOWING FRESH AIR FIREPLACES:
Æ
HEATILATOR CNXT70IPLUS SERIES & NB4236IPLUS SERIES
Æ
HEAT-N-GLO 6000PLUS SERIES & 6100PLUS SERIES
Æ Note: The Caliber NXT Plus gas appliance (CNXT70IPLUS Series)
and the 6100 PLUS (6100PLUS Series) CANNOT be installed at an
elevation above 6,200 ft. (1,890m).
IMPORTANT!
Before installation, the installer must give careful consider-
ation to how this HRV200PLUS system will operate if con-
nected to any other piece of mechanical air movement equip-
ment, i.e. a forced air furnace or air handler, operating at a
higher or lower static pressure.
Before the installation, the installer must assess any inter-
action between the HRV200PLUS and vented combustion
equipment, i.e. gas furnaces, oil furnaces, wood stoves, etc.,
and ensure the ability of the vented appliances to properly
vent is not compromised by the operation of the
CAUTION:
HRV200PLUS system.
Do not expose the appliance to the elements (such
as rain, etc.).
After installation, the installer must confirm the compatibil-
ity of the installed system by measuring both air flows of
the HRV200PLUS by using the balancing procedure found
in this manual and evaluating the effects on any intercon-
nected equipment.
Note: An arrow (Æ) found in the text signifies change in
content.
NEVER install a ventilator in a situation where its normal
operation, lack of operation or partial failure may result in
the back drafting or improper functioning of vented com-
bustion equipment!!!
PLEASE RETAIN THIS MANUAL
FOR FUTURE REFERENCE
This appliance is certified to CSA22.2 and UL1812 standards
and also is performance tested to CSA439-00.
For assistance during installation contact your local dealer
or contact the Heatilator Technical Services Department,
Hearth & Home Technologies Inc., 1915 W. Saunders Street,
Mt. Pleasant, Iowa 52641, 1-877-IAQ-VENT
(1-877-427-8368).
HEATILATOR® is a registered trademark of Hearth & Home
Technologies Inc.
02/04
4034-102 Rev F
1
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
C. ENGINEERING DATA
Efficient, Patented Aluminum Core
The cross-flow heat recovery core transfers heat between the intake and exhaust airstreams. The core removes easily for cleaning
or service.
Diagnostic LED
A diagnostic LED mounted on the side of the HRV200PLUS cabinet indicates normal and abnormal operating modes for efficient
system evaluation without having to open the door.
Supply and Exhaust Air Blowers
The supply and exhaust air flows are supplied by two forward curved blower wheels driven by a common, double shaft PSC blower
motor. Four field selectable blower speeds – one high speed and three low speeds – are available to meet specific installation
needs. The blower motor is rated at 120VAC, 1.4 Amps.
Air Filters
Air filters are supplied in both the exhaust and supply air streams. The filters are washable and easily removed for cleaning.
Automatic Defrost System
The HRV200PLUS is equipped with an automatic defrost feature utilizing heat from the Fresh Air Fireplace to defrost the HRV core.
As a warning feature, the electric ember bed will light for 15 seconds prior to ignition. Alternatively, a field installed defrost system
using recirculated indoor air to remove frost is available as an option.
Cabinet
Painted twenty gauge galvanized steel outer shell and aluminized inner liner sandwich ¾” (19mm) insulation to provide strength,
reduce heat loss and insure a corrosion free life.
Mounting
The HRV200PLUS comes supplied with four reinforced polyester straps which attach to the threaded inserts at each corner of the
case for easy installation and quiet operation.
Installed Weight - 78 lbs. (35.4 kg)
Shipping Weight - 84 lbs. (38 kg)
02/04
4034-102 Rev F
3
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
HRV200PLUS Performance
HVI CERTIFIED
Maximum Temperature Recovery
70%
60%
Sensible Effectiveness
@149 cfm (70 L/s) (CSA C439M)
Sensible Efficiency
55%
53%
@149 cfm (70 L/s) 32°F (0°C)
Sensible Efficiency
@131 cfm (62 L/s) -13°F (-25°C)
VAC @ 60 Hz
120
87
WATTS (Low Speed)
WATTS (High Speed)
Amp Rating
164
1.4
HRV200PLUS Clearance to Combustibles
Surface
Top
1"
Sides
1"
Front
1"
Bottom
1"
Back
0"
Clearance
Appliance Dimensions
4
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
D. DEFROST OPTIONS
The HRV200PLUS performs as a whole house heat recovery ventilator during Fresh Air Fireplace operation and continuous ventilation
operation. When the Fresh Air Fireplace is in use, the HRV core temperature is elevated with no chance of frost or ice build-up at any
time. However, when the HRV200PLUS is operating in continuous ventilation mode, outdoor temperatures below 25°F can cause frost
to form on the core. This frost can reduce airflow through the HRV resulting in unbalanced operation and could inhibit Fresh Air
Fireplace operation.
The Caliber NXT Plus and 6100 PLUS Fresh Air Fireplace is an “open hearth” design using the draft created by the HRV200PLUS to
form an air curtain containing flue products in the hearth, as opposed to the typical glass front. The fronts for the Caliber NXT Plus and
6100 PLUS are shipped with fixed mesh screens to provide a barrier between the occupants and the fire.
Æ
Æ
WARNING!
Removing the DEFC1 jumper allows the HRV200PLUS to independently ignite the Fresh Air Fireplace.
WARNING!
Do not remove the fixed mesh screen or screen door retainers on the Caliber NXT Plus and the 6100 PLUS fronts unless:
1. Fresh Air Fireplace Defrost is disabled (DEFC1 jumper installed), and
2. Fresh Air Fireplace operation is supervised by an adult. Removing the fixed screen mesh or mesh door retainers could
result in injury, property damage or death.
Choose the defrost method best for your application:
•
•
•
No Defrost
Mild climates where defrost is not needed. Allows fixed mesh screens/screen door retainers to be removed on the Caliber NXT
Plus and the 6100 PLUS.
Æ
Room Air Defrost
Defrosts with indoor air using the Optional Defrost Kit. Does not cause unexpected Fresh Air Fireplace ignitions. Allows fixed
mesh screens/screen door retainers to be removed on the Caliber NXT Plus and the 6100 PLUS.
Æ
Fresh Air Fireplace Defrost
Defrosts with the heat from the Fresh Air Fireplace. Causes unexpected Fresh Air Fireplace ignitions. Fixed mesh screens/
Æ
screen door retainers must be used on the Caliber NXT Plus and the 6100 PLUS.
Note: When “No Defrost” or “Room Air Defrost” is selected for the defrost method, the fireplace will not be used for defrost cycles. Some
homeowners may elect to remove the fixed mesh screen or screen door retainers from the Caliber NXT Plus and the 6100 PLUS fronts for
true “open hearth” operation.
1. No Defrost
This option is not generally recommended but may be used under the following conditions:
a. The system is installed in an area with fewer than five days a year with an outside temperature below 25°F. These areas are
typically in the southern and coastal regions of the country.
b. The system will not be used for continuous ventilation. This application is for the installation where the HRV200PLUS is not the
primary ventilation means for the building and will only be used as a power vent/heat recovery device for the Fresh Air
Fireplace.
c. Setup for No Defrost Option
1) Install the HRV200PLUS and the Fresh Air Fireplace per the instructions in this manual.
2) Ensure the DEFC1 jumper is installed on the HRV control board. This jumper will disable the defrost logic in the
HRV200PLUS.
02/04
4034-102 Rev F
5
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
2. Room Air Defrost
a. When the HRV200PLUS system is installed in climates that normally have more than five days a year with an outside temperature
below 25°F, Room Air Defrost is the recommended defrost method for two reasons:
1) Unanticipated fireplace ignition due to the HRV200PLUS entering the defrost cycle is eliminated, and
2) This presents the opportunity for some homeowners to remove the fixed mesh screen or screen door retainers on the front
Æ
of the Caliber NXT Plus or the 6100 PLUS allowing true “open hearth” operation.
b. Setup for Room Air Defrost Option
1) Install the HRV200PLUS and the Fresh Air Fireplace per the instructions in this manual.
2) Install the Optional Defrost Kit (part # HRV99DEFKIT). The Optional Defrost Assembly is microprocessor controlled to
efficiently perform all defrost functions independently of the HRV200PLUS.
3) Ensure the DEFC1 jumper is installed on the HRV control board. This jumper will disable the defrost logic in the
HRV200PLUS.
3. Fresh Air Fireplace Defrost
When the HRV200PLUS system is installed in climates that normally have more than five days a year with outside temperatures
below 25°F, Fresh Air Fireplace Defrost is a desirable defrost method because it utilizes the heat from the Fresh Air Fireplace to
clear any frost build-up on the heat recovery core. However, the following precautions should be noted:
a. This method does allow the HRV200PLUS to independently ignite the Fresh Air Fireplace which may result in unexpected
fireplace operation.
b. The fixed mesh screen or screen door retainers on the Caliber NXT Plus and the 6100 PLUS fronts must not be removed
Æ
when using the Fresh Air Fireplace Defrost option.
c. Setup for Fresh Air Fireplace Defrost Option
1) Install the HRV200PLUS and the Fresh Air Fireplace per the instructions in this manual.
2) Remove the DEFC12 jumper on the HRV control board. Removing this jumper will allow the HRV200PLUS to control the
Fresh Air Fireplace for defrost cycles.
6
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
E. INSTALLATION DIAGRAMS
Note: Minimum and maximum clearances must be maintained at all times. Illustrations throughout these instructions reflect
typical installations and are for design purposes only. Actual installation may vary slightly due to individual design preferences.
The illustrations and diagrams used throughout these installation instructions are not drawn to scale.
1. Simplified Installation (Supply/Return Method)
•
•
HRV must be balanced.
It is recommended that the furnace blower run continuously or HRV operation be
interlocked with the furnace blower (refer to Section “L. Wiring”).
•
Check local codes/authority having jurisdiction for acceptance.
02/04
4034-102 Rev F
7
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
X
2. Partially Dedicated Installation
a. Exhaust Air
•
Stale air drawn from key areas of the home (bathroom,
kitchen, laundry).
•
•
Fresh air supplied to supply air duct of furnace.
HRV must be balanced.
b. Fresh Air
•
Fresh air supplied to main living areas of
the home (bedroom, family room).
Stale air drawn from furnace return.
HRV must be balanced.
•
•
8
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
3. Fully Dedicated Installation
x
•
Stale air drawn from key areas of the home (bathroom,
kitchen, laundry).
•
•
Fresh air supplied to main living areas.
HRV must be balanced.
02/04
4034-102 Rev F
9
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
F. INSTALLING THE VENTILATOR
1. Location
The HRV200PLUS must be located in a heated space where it will be possible to conveniently service the ventilator. Typically the
HRV200PLUS would be located in the mechanical room or an area close to the outside wall where the weather hoods will be
mounted. If a basement area is not convenient, a utility or laundry room may be used.
Attic installations are not normally recommended due to:
a. The complexity of work to install.
b. Freezing conditions in the attic.
c. Difficulty of access for service and cleaning.
Sufficient clearance at the front of the access door is required for servicing the air filters and core. A minimum of 25” (635mm)
clearance is recommended so the door can be opened. Four PVC reinforced polyester hanging straps are provided for hanging the
HRV200PLUS from the basement floor joists.
2. Mounting
The hanging straps should be attached to the ventilator at the top end corners (mounting screws are already located on the
ventilator case). Securely fasten the other end of the straps to the floor joists with wide head nails (not supplied), making sure the
ventilator is level. The straps are designed to reduce the chance of noise, resonance or harmonics; therefore using the full length
of the strap between the HRV200PLUS and the floor joists is recommended.
3. Electrical
The HRV200PLUS should be plugged into a standard designated (120VAC) electrical outlet with ground. The HRV200PLUS is
equipped with a 3 foot electrical cord so it should be located within 3 feet from electrical service. It is not recommended that an
extension cord be used for this appliance. If further wiring is required, then a licensed electrician should make all electrical connections.
It is recommended that a separate 15 amp/120 volt circuit be used.
WARNING!
In order to prevent electric shock when cleaning or servicing the HRV200PLUS, it is extremely important to confirm the
polarity of the power line that is switched by the safety (disconnect) switch. The hot line (black) is the proper line to be
switched. To confirm the proper polarity, use a voltmeter or test lamp to ensure there is no power after the switch when the
door is open. Check between that point and ground (on the cabinet). This must be done as dwellings are occasionally
wired improperly. Always make sure that the HRV200PLUS is properly grounded.
4. Installing the Drain Line and P-Trap
When defrosting, the HRV200PLUS may produce some condensation. This water should flow into a nearby drain or be taken away
by a condensate pump. The ventilator and all condensate lines must be installed in a space where the temperature is maintained
above the freezing point.
Construct a P-Trap using the plastic tee connector. Cut two lengths of
hose and connect each piece to an end of the “T” fitting, then connect
the other ends to the two drain spouts. Allow the “T” fitting to point
upwards. Connect to the drain line. Tape or fasten the base to avoid
any kinks. This creates a trap which will hold some condensate and
prevent odors from being drawn up the hose and into the fresh air supply
of the HRV200PLUS. See Figure 1.
WARNING!
Improperly installed water drain lines could result in property dam-
age.
Figure 1
10
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
G. VENT AND DUCT INSTALLATION
WARNING! - CONNECTING APPLIANCES TO THE HRV200PLUS
Do not connect any of the following appliances to the HRV200PLUS because lint, dust and/or grease will collect in the HRV,
damaging the ventilator:
• clothes dryer
• range top
• stove top fan
• gas furnace
• B-vented gas fireplace
• solid fuel fireplace or heater
• gas water heater
• direct vent gas fireplace
• central vacuum system
Connecting any of these appliances to the HRV200PLUS will void the warranty.
The HRV200PLUS (HRV) not only serves as the fresh air ventilator for the home, but is also the power venting device for the Fresh Air
Fireplace (FAF). The conduits from the FAF to the HRV and from the HRV to the exhaust termination remove both stale air from the
home and the products of combustion from the FAF. Thus the exhaust air conduit acts as the chimney for your fireplace!
The HRV200PLUS requires four standard and one optional vent/duct connections:
Standard
1. Fresh Air Supply - Fresh air from the Fresh Air Inlet to the HRV.
2. Warmside Air Supply - Heated fresh air from the HRV into the living area.
3. Fresh Air Fireplace Exhaust - Stale air/combustion products from the FAF to the HRV.
4. HRV Exhaust - Stale air/combustion products from the HRV to the Flue Exhaust.
Optional - Alternate Exhaust Damper Assembly
Alternate Exhaust - Stale air from the living area to the HRV.
Note: Each of these connections has specific requirements for safe
system operation, comfort and optimum efficiency. Always try to mini-
mize duct run length and follow the manufacturer’s installation in-
structions. Always follow specific code requirements.
1. Fresh Air From the Outdoor Intake to the HRV (Fresh Air Supply)
Duct Materials:
Fresh Air Inlet - 6” Outside Weatherhood (Part #HRV99189)
Insulated Air Duct - rigid or flexible
CoolVent™ Flexible Pipe may be used.
a. Locate the Fresh Air Inlet
See Figure 7 for more detailed instructions.
•
•
•
Must take air directly from outdoors.
Should be located upstream (if there are prevailing winds) from the exhaust outlet.
At least 3’ (.9m) below when within 10’ (3m) of the exhaust weatherhood, dryer vents or furnace exhaust
(medium or high efficiency furnaces).
•
A minimum of at least 10’ (3m) from driveways, oil fill pipes, gas meters, garbage containers or any other
know sources of contamination.
•
•
•
•
•
•
At least 18” (457mm) above the ground or above the depth of expected snow accumulation.
At least 3’ (1m) from the corner of the building.
Do not locate in a garage, attic or crawl space, adjacent dwelling units or other indoor spaces.
Cap with the included plastic weatherhood.
Must be clear of future obstructions such as plants, snow, etc.
Must be readily accessible for clearing of debris and obstructions.
02/04
4034-102 Rev F
11
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
b. Install Fresh Air Supply Ducting
The inner and outer liners of the insulated duct must be clamped
to the sleeve of the weatherhood as close to the outside as
possible and to the plastic inlet port on the HRV200PLUS. It is
very important that the fresh air intake line be given special
attention to make sure it is well sealed. A good bead (½”) of
high quality caulking (preferably acoustical sealant) will seal the
inner duct to both the HRV port and the weatherhood prior to
clamping.
To minimize air flow restriction, the flexible insulated duct (if
used) that connects the outside weatherhood to the
HRV200PLUS should be stretched tightly and be as short as
possible.
Twisting or folding the duct will severely restrict air flow. See
Figure 2 for the recommended connection of insulated ducts to
the outside weatherhood and the HRV200PLUS.
Ducting must be installed in accordance with local codes.
2. Warmside Air Supply - Heated fresh air from the HRV into the
living area
Duct Materials: Insulated Metal Air Duct - rigid or flexible, 200°F rated
CoolVent™ Flexible Pipe may be used.
Figure 2
Duct Adapter - (Simplified Installation)
Diffusers or Grilles - 200°F rated (Dedicated Installation)
Note: Due to elevated temperatures in the fresh air supply duct:
• Use only ducting materials rated for use at or above 200°F
• Do not use plastic duct or terminations rated below 200°F.
• Do not connect fresh air supply duct into the return duct work of the furnace. Hot air stream could damage exposed
components in the furnace return cabinet.
• WHEN USING THE EXISTING DUCT WORK FOR AIR DISTRIBUTION, ALWAYS CONNECT TO THE SUPPLY DUCT
WORK DOWNSTREAM OF THE CENTRAL FURNACE OR AIR HANDLER.
a. Duct the Warmside Air Supply
The HRV200PLUS recovers heat from the fireplace normally wasted in the flue. This means that the temperatures achieved
in the fresh air stream to the home will typically be 100°F hotter than the outdoor ambient temperature. Under some operating
conditions, the temperature inside the fresh air supply duct could be as high as 200°F.
The fresh air should be supplied to all living areas and bedrooms, excluding bathrooms, kitchens and utility areas.
The fresh air supply may be delivered to the home through a dedicated duct system when:
1) No central forced air system exists,
2) The HRV200PLUS is not in close proximity to the central supply air ducts or
3) Heating load design factors favor dedicated supply registers.
When dedicated supply grilles are used, grilles that diffuse the air comfortably from high wall or ceiling locations are
recommended.
In homes with a forced air distribution system, direct connection to the furnace supply duct work is the preferred method for
supplying fresh air from the HRV200PLUS. This will ensure fresh air is delivered evenly throughout the house and utilizes the
existing duct work infrastructure.
When connected to the furnace supply air duct work, the duct adapter should be installed to insure reliable air flow and stable
operation of the HRV200PLUS. The duct adapter is designed to minimize the effects of static pressure in the duct regardless
of the furnace blower speed selection and allows for fast, easy and airtight connections.
Remember to check the air flow balance of the HRV200PLUS with the furnace fan both on and off to determine that it does not
imbalance the ventilator more than 10%.
12
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
Note: When using the existing furnace duct work for air distribu-
tion, the furnace blower must be set to run continuously or inter-
locked with the HRV200PLUS. The interlock may be easily
achieved using the Furnace Interface Relay terminals on the
HRV200PLUS control board. These terminals interface directly with
the furnace control board using low voltage wiring. See wiring dia-
gram in Section “L. WIRING” for details.
b. Warmside Ducting Guidelines
To maximize air flow in the duct work system, all ducts should be kept short and have as few bends or elbows as possible. 45°
elbows are preferred to 90° elbows. Use “Y” tees instead of 90° tees whenever possible.
All duct joints must be fastened with screws, rivets or duct sealant and wrapped with a quality duct tape to prevent leakage. We
recommend aluminum foil duct tape or tape and mastic.
Galvanized ducting from the HRV200PLUS to the living areas in the house is recommended whenever possible, although
flexible duct can be used in moderation if necessary.
The main supply and return lines to and from the HRV200PLUS must be 6” (150mm) minimum. Branch lines to the individual
rooms may be as small as 4” (100mm), but 5” (125mm) lines are preferred.
All ducts running through attics, crawl spaces or other unconditioned spaces must be sealed and insulated to code.
c. Dampers and Grilles
The use of balancing dampers and/or adjustable grilles to balance the flow rates into various rooms is recommended.
We recommend the use of high mounted wall returns with grilles. The exhaust air duct from the kitchen should never be
connected to a range hood. Instead, the exhaust grille should be mounted high on the wall at least 4’ (1.2m) horizontally away
from the stove. A “flip-up”, 6” x 10” (150 x 250mm) rectangular kitchen grille with removable grease filter is recommended.
See Figure 3.
Dampers should be located just prior to the HRV200PLUS to balance the stale air exhausted out of the house with a fresh air
supply entering the house.
Figure 3
Recommended Exhaust Grille for Kitchen
CAUTION:
Check temperature specifications of hoods and
grilles before installation to avoid possible damage
to them by the flow of warm/hot air. Hoods and grilles
should be rated for use at or above 200°F.
02/04
4034-102 Rev F
13
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
3. Fresh Air Fireplace Exhaust - Stale air/combustion products from the FAF to the HRV
Duct Materials: CoolVent™ Flexible Pipe (1” air clearance to combustible materials)
Firestops, Hangers and Accessories as Required
a. Fresh Air Fireplace Exhaust Guidelines
1) FAF must be vented with CoolVent™ flexible insulated vent pipe, maintaining 1” (25.4mm) clearance to combustible
surfaces.
Note: 1” (25.4mm) air clearance to combustibles must be maintained
when using CoolVent™ in this portion of the venting system.
2) The total combined length of the CoolVent™ run for the Fireplace Exhaust and the HRV Exhaust must not exceed the
maximum lengths shown in the following table:
3) Direction of flow may include any combination horizontal, vertical up or vertical down.
Æ
Æ
4) The entire vent run must be contained within an area which will not experience temperatures below 40°F.
WARNING!
The maximum TOTAL EXHAUST vent run is measured from the flue collar of the Fresh Air Fire-
place, through the HRV, to the outside termination. DO NOT EXCEED MAXIMUM VENTING LENGTHS!
b. Attaching the CoolVent™ to the Fresh Air Fireplace Flue Collar
1) Secure a CoolVent™ appliance connector to the CoolVent™ insulated flexible pipe per the manufacturer’s instructions.
2) Apply a generous bead (1/2 inch) of RTV high temperature silicone to the flue collar and attach the appliance adaptor.
c. Assembling the Vent Pipe Sections
1) When it is necessary to connect two or more lengths of CoolVent™ insulated flexible pipe in a vent run, use a universal
connector at each joint.
2) Always support CoolVent™ insulated flexible pipe every three feet.
WARNING!
When vent sections exceed three feet (.9m) in length ensure minimum clearances are
maintained. Structural support must be provided to reduce off-center loading. Follow
manufacturer installation instructions..
14
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
4. HRV Exhaust - Stale air/combustion products from the HRV to the Flue Exhaust
Duct Materials:
CoolVent™ Flexible Pipe - Zero Clearance to Combustible Materials
Horizontal Terminations: CoolVent™ Termination Cap
Vertical Terminations:
CoolVent™ Universal Adapter
B-Vent Roof Support
B-Vent Pipe Sections
B-Vent Termination Cap
a. HRV Plus Exhaust Guidelines
1) HRV must be vented with CoolVent™ flexible insulated vent pipe. The CoolVent™ flexible pipe can be installed with zero
clearance to combustible materials when used as the HRV Exhaust.
2) The total combined length of the CoolVent™ vent run for the Fresh Air Fireplace Exhaust the HRV Exhaust must not
exceed the maximum lengths in the following table:
Æ
WARNING!
The maximum TOTAL EXHAUST vent run is measured from the flue collar of the Fresh Air Fire-
place, through the HRV, to the outside termination. DO NOT EXCEED MAXIMUM VENTING LENGTHS!
3) Direction of flow may include any combination horizontal, vertical up or vertical down, but must not form a trap for
condensation to collect.
4) Refer to Figures 7-9 for horizontal termination locations.
b. Assembling the Vent Pipe Sections
1) When it is necessary to connect two or more lengths of CoolVent™ insulated flexible pipe in a vent run, use a universal
connector at each joint.
2) Always support CoolVent™ insulated flexible pipe every three feet.
WARNING!
When vent pipe sections exceed three feet (.9m) in length, structural support must be provided to
reduce off-center loading and insure minimum clearances are maintained. Follow manufacturer’s
installation instructions.
02/04
4034-102 Rev F
15
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
5. Stale Air from the Living Area to the HRV (Alternate Exhaust)
Duct Materials:
Alternate Exhaust Damper Assembly
Air Duct - flexible or rigid, insulation optional
Alternate Exhaust Port
The alternate exhaust port is used to draw air from the points in the house where the worst air quality problems occur, when the
fireplace is not in operation. It is recommended that return air ducts are installed in the bathroom, kitchen and laundry room.
Additional return air ducts from strategic locations (i.e. greenhouse, atrium, swimming pool, sauna, etc.) may be installed.
Also, the furnace return duct may be used for exhaust. In this method, the exhaust air is not ducted back to the HRV200PLUS
with dedicated lines from bathrooms, kitchens, etc. Instead, the exhaust air is drawn out of the cold air return of the forced air
furnace. This method has become popular and provides good ventilation when installed in accordance with the instructions.
The furnace blower must be running when the ventilator is operating for this system to be effective.
The HRV200PLUS comes factory wired ready to allow installation and operation of the Alternate Exhaust Damper Assembly
(Figure 4). The Alternate Exhaust Damper Assembly should be professionally installed by a trained service technician. The
installation instructions are supplied with the assembly.
Figure 4 - Alternate Exhaust Damper
H. EXHAUST TERMINATION
1. Horizontal Exhaust Terminations (see Figures 5-9)
a. Cut a 9” (229mm) diameter hole in the outside wall of the structure to allow the CoolVent™ Flexible Pipe to protrude.
b. Apply a generous bead (½”) of RTV around the perimeter of the collar/adapter 2” - 3” (51mm - 76mm) from the open end.
c. Slide the CoolVent™ Flexible Pipe over the termination collar about 1” (25.4mm) beyond the RTV bead.
d. Tighten the hose clamp around the flexible pipe approximately 1” (25.4mm) from the end of the pipe.
e. Carefully apply pressure to the termination cap, compressing the flexible pipe until the cap is flush with the siding.
f. Secure the termination cap in place with four screws, one in each corner of the termination cap base. Caulk the perimeter of
the base to form an air and moisture proof seal.
16
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
Figure 5
Horizontal Termination
Figure 6 - Typical Horizontal Termination
02/04
4034-102 Rev F
17
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
2. Horizontal Termination Locations (flue exhaust and fresh air inlets)
Figure 7 - Termination Cap Locations
Figure 8 - Alcove Clearances
9 - Electrical Service Clearances
18
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
Dimension Descriptions
A
B
Clearance above the ground, a veranda, porch, deck or balcony - 12 inches (30 cm) minimum. *
Clearance to window or door that may be opened – 10,000 BTUs or less, 6 inches (15 cm) minimum; 10,000-50,000 BTUs, 9 inches (23 cm)
minimum; over 50,000 BTUs, 12 inches (30 cm) minimum. *
C
D
Clearance to permanently closed window – 12 inches (30 cm) minimum - recommended to prevent condensation on window.
Vertical clearance to ventilated soffit located above the termination within a horizontal distance of 2 feet (60 cm) from the centerline of the
termination – 18 inches (46 cm) minimum. **
E
F
G
H
I
Vertical clearance to unventilated soffit - 12 inches (30 cm) minimum. **
Clearance to outside corner - 6 inches (15 cm) minimum.
Clearance to inside corner - 6 inches (15 cm) minimum.
Not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally* from the center line of the regulator (Canada only)
Clearance to service regulator vent outlet – 3 feet (.91 m) U.S. minimum and 6 feet (1.8 m) Canada minimum. *
J
Clearance to non-mechanical air supply inlet into building or the combustion air inlet to any other appliance – 9” (23 cm) U.S. minimum and 12
inches (30 cm) Canada minimum. *
K
L
Clearance to mechanical air supply inlet - 3 feet (.91 m) U.S. minimum and 6 feet (1.8 m) Canada minimum. *
Clearance above a paved sidewalk or paved driveway located on public property - 7 feet (2.1 m) minimum.
A vent may not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both
dwellings.
M
Clearance under veranda, porch, deck or balcony - 12 inches (30 cm) minimum. * Recommended 30 inches (76 cm) for vinyl or plastic.
Only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor. *
N
O
P
Vertical clearance between two horizontal termination caps – 12 inches (30 cm) minimum.
Horizontal clearance between two horizontal termination caps – 12 inches (30 cm) minimum.
6” - Non-vinyl sidewalls
12” – Vinyl sidewalls
Q
R
18” – Non-vinyl soffit and overhang
42” – Vinyl soffit and overhang
8 ft.
U
6” min. – Clearance from sides of electrical service.
12” min. – Clearance above electrical service.
W
*
As specified in CGA B149 Installation Codes
Note: Local codes or regulations may require different clearances.
** Clearance required to vinyl soffit material – 30 inches (76 cm) minimum.
Note: Location of the vent termination must not interfere with access to the electrical service.
WARNING!
In the U.S.: Vent system termination is NOT permitted in screened porches. You must follow side wall, overhang and ground clearances as stated
in the instructions.
In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more
sides open. You must follow all side wall, overhang and ground clearances as stated in the instructions.
Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet
these requirements.
02/04
4034-102 Rev F
19
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
3. Vertical Termination (see Figure 11)
a. Install the B-Vent roof support per the manufacturer’s installation instructions. Insure proper use of necessary flashing and
firestop spacers as required by the vent manufacturer.
b. Install a CoolVent™ Universal Adapter to the end of the flexible pipe as described in Step 4b, page 15.
c. Install an adequate length of rigid B-Vent pipe into the roof support to provide the minimum height from the roof to the bottom
of the cap as shown in Figure 12 and Table 1. Secure the rigid pipe in the roof support.
d. Place a ½” bead of RTV in the receiving end of the appliance adapter and insert the end of the rigid B-Vent pipe. Secure the
hose clamp to the pipe. Reference Figure 5 and inset in Figure 10 for RTV and hose clamp placement.
e. Use aluminum duct tape to seal all seams of the rigid B-Vent exposed below the roof line.
f. Typical Vertical Termination (see Figure 10)
•
•
•
•
•
•
At least 10’ (3m) from the ventilation air intake.
At least 18” (457mm) above the roof line or above the depth of expected snow accumulation.
At least 3’ (1m) away from the corner of the building.
Not near a gas meter, electric meter or a walkway where fog or ice could create a hazard.
Not into a garage, workshop or other enclosed space.
When installing the termination cap, its outside perimeter must be sealed with exterior caulking.
Figure 10
20
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
Figure 11
Typical Vertical Termination
02/04
4034-102 Rev F
21
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
4. Chase/Termination Installation
Figure 12 and Table 1 specify minimum vent heights
for various pitched roofs.
Table 1
Roof Pitch
H (Min.) Ft.
These vent heights are necessary for safety and do
not ensure draft-free operation. Trees, buildings,
adjoining roof lines, adverse conditions, etc. may create
a need for a taller vent should down drafting occur.
Flat to 6/12................................................ 1.0
6/12 to 7/12............................................... 1.25
Over 7/12 to 8/12 ...................................... 1.5
Over 8/12 to 9/12 ...................................... 2.0
Over 9/12 to 10/12.................................... 2.5
Over 10/12 to 11/12 .................................. 3.25
Over 11/12 to 12/12 .................................. 4.0
Over 12/12 to 14/12.................................. 5.0
Over 14/12 to 16/12.................................. 6.0
Over 16/12 to 18/12.................................. 7.0
Over 18/12 to 20/12.................................. 7.5
Over 20/12 to 21/12.................................. 8.0
Vent Height
Figure 12 - Vent Height for Vertical Termination
22
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
WARNING - RISK OF FIRE!
Always maintain minimum clearances or greater around
the vent system. Do not pack air spaces with insulation
or other material. The flow of combustion and ventilation
air must not be obstructed.
5. Firestop Spacer/Vent Installation
Following code requirements, frame an opening and install
a firestop spacer whenever the vent penetrates a ceiling,
wall or floor area, as shown in Figure 13. Frame the opening
with the same sized lumber as used in the ceiling/floor joist.
DO NOT pack insulation around the vent. Assemble vent
sections with three screws per joint.
Figure 13 - Installing the Firestop Spacer
02/04
4034-102 Rev F
23
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
I. SELECTING BLOWER SPEEDS
The HRV200PLUS’ versatile design allows flexibility for a variety of installations by providing one high blower speed option and three
low blower speed options:
Table 2
Æ
Net Air Flow (sCFM)
External Static
0.10
0.20
0.30
0.40
0.50
High
Speeds
Med
224
155
127
98
219
155
119
85
209
145
105
70
194
120
91
174
89
Low
Med Low
Low
64
Speeds
54
37
24
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
J. BALANCING
1. Balancing Collar Instructions
WARNING!
Risk of carbon
m o n o x i d e !
Negative air
pressure may
cause
back
drafting of gas
a p p l i a n c e s .
Proper balanc-
ing of the HRV
is required.
Figure 14
2. Air Flow Balancing
Æ
Note: When installing the Caliber NXT Plus or 6100 PLUS with the HRV200PLUS, a minimum of 130 CFM must be maintained
for fireplace operation. The Caliber NXT Plus or 6100 PLUS will fail to operate when the Fresh Air Fireplace exhaust air flow is
less than 130 CFM! Always perform balancing procedures with the fireplace off!
It is necessary to have balanced air flows in an HRV200PLUS. The volume of air brought in from the outside must equal the
volume of air exhausted by the ventilator. If the air flows are not properly balanced, then:
•
•
•
•
The HRV200PLUS may not operate at its maximum efficiency.
A negative or positive air pressure may occur in the house.
The ventilator may not defrost properly.
Failure to balance HRV200PLUS properly may void warranty.
Excessive positive pressure may drive moist indoor air into the external walls of the building where it may condense (in cold
weather) and degrade structural components. It may also cause key holes to freeze up.
Excessive negative pressure may have several undesirable effects. In some geographic locations, soil gases such as methane
and radon gas may be drawn into the home through basement/ground contact areas. Excessive negative pressure may also cause
the back drafting of vented combustion equipment.
Read the Application Warning on the front of this manual!
Prior to balancing, ensure that:
•
•
•
•
•
All sealing of the duct work system has been completed.
All of the HRV200PLUS’ components are in place and functioning properly.
Balancing dampers are fully open.
Ventilator is on HIGH speed.
Air flows in branch lines to specific areas of the house should be adjusted first prior to balancing the ventilator. A smoke pencil
used at the grilles is a good indicator of each branch line’s relative air flow.
•
•
After taking readings of both the stale air to the HRV200PLUS duct and fresh air to the house duct, the duct with the lower
CFM ([L/s] velocity) reading should be left alone, while the duct with the higher reading should be dampered back to match the
lower reading.
Return the ventilator to the appropriate fan speed for normal operation.
02/04
4034-102 Rev F
25
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
3. Pitot Tube Balancing Procedure (see Figure 16)
The following is a method of field balancing an HRV200PLUS using a pitot tube, advantageous in situations when flow
stations are not installed in the duct work. The procedure should be performed with the HRV200PLUS on high speed.
The first step is to operate all mechanical systems that have an influence on the ventilation system (i.e. the HRV itself and the
forced air furnace or air handler if applicable) on high speed. This will provide the maximum pressure that the HRV200PLUS will
need to overcome and allow for a more accurate balance of the ventilator.
Drill a small hole in the duct (about 3/16”), 3 feet downstream of any elbows or bends, and one foot upstream of any elbows or
bends. These are recommended distances but the actual installation may limit the amount of straight duct.
The pitot tube should be connected to a magnehelic gauge or other manometer capable of reading from 0 to 0.25 in. (0 - 62 PA) of
water, preferably to three digits of resolution. The tube coming out of the top of the pitot is connected to the high pressure side of
the gauge. The tube coming out of the side of the pitot is connected to the low pressure or reference side of the gauge.
Insert the pitot tube into the duct; pointing the tip into the air flow. See Figure 15.
For general balancing it is sufficient to move the pitot tube around in the duct and take an average or typical reading. Repeat this
procedure in the other (supply or return) duct. Determine which duct has the highest air flow (highest reading on the gauge). Then
damper that air flow back to match the lower reading from the other duct. The flows should now be balanced. Actual air flow can be
determined from the gauge reading. The value read on the gauge is called the velocity pressure. The pitot tube comes with a chart
that will give the air flow velocity based on the velocity pressure indicated by the gauge. This velocity will be in either feet per
minute or meters per second. To determine the actual air flow, the velocity is multiplied by the cross sectional area of the duct being
measured.
This is an example of determining the air flow in a 6” duct. The pitot tube reading was 0.025 inches of water. From the chart, this
is 640 feet per minute.
The 6” duct has a cross sectional area of = [3.14 x (6” ÷ 12)² ÷ 4 = 0.2 square feet
The air flow is then: 640 ft./min. x 0.2 square feet = 128 cfm
For your convenience, the cross sectional area of some common round duct is listed below:
The accuracy of the air flow reading will be affected by how close to any elbows or bends the readings are taken. Accuracy
can be increased by taking an average of multiple readings as outlined in the literature supplied with the pitot tube. See
Figure 16.
If the ALTERNATE 5TH PORT is used for alternative exhaust, both the fireplace and exhaust air streams must be balanced
individually with the incoming fresh air stream. Individually, each exhaust stream needs to be within 10% of the incoming air
stream.
WARNING!
DO NOT penetrate the HRV exhaust duct for pitot tube balancing. This duct is under positive pressure during normal
operation and cannot be properly patched once penetrated!
Note: Always seal the pitot tube access hole in the Fresh Air
Fireplace duct with aluminum tape or the equivalent.
Figure 15
26
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
Figure 16 - Pitot Tube Balancing
02/04
4034-102 Rev F
27
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
4. Flow Station Balancing Procedure (see Figure 17)
The following is a method of field balancing an HRV using a flow station. The procedure should be performed with the
HRV200PLUS on high speed.
The first step is to operate all mechanical systems on high speed, which have an influence on the ventilation system, i.e. the HRV
itself and the forced air furnace or air handler if applicable. This will provide the maximum pressure that the HRV200PLUS will need
to overcome, and allow for a more accurate balance of the ventilator.
Note: Always balance the system using the FRESH AIR FIREPLACE EXHAUST duct and the WARMSIDE AIR SUPPLY duct.
Install the flow station 18” downstream of any elbows or bends, and one foot upstream of any elbows or bends. These are
recommended distances but the actual installation may limit the amount of straight duct.
The flow station should be connected to a magnehelic gauge or other manometer capable of reading from 0 to 0.25 in. (0 - 62 PA)
of water, preferably to three digits of resolution.
Take readings from both exhaust ducts and the warmside air supply. Determine which duct has the highest air flow (highest reading
on the gauge). Then damper that air flow back to match the lower reading from the other duct. The flows should now be balanced.
See Figure 17. Actual air flow can be determined from the gauge reading. The value read on the gauge is called the velocity
pressure. The flow station comes with a chart that will give the air flow velocity based on the velocity pressure indicated by the
gauge. This velocity will be in either feet per minute or meters per second.
The accuracy of the air flow reading will be affected by how close to any elbows or bends the readings are taken. See Figure 17.
If the ALTERNATE 5TH PORT is used for alternative exhaust, both the fireplace and exhaust air streams must be balanced
individually with the incoming fresh air stream. Individually, each exhaust stream needs to be within 10% of the incoming air
stream.
Figure 17 - Flow Station Balancing
28
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
K. OPERATING MODES
The operating mode of the HRV200PLUS is determined by the status of the control inputs:
1. Fireplace Control Input Group
Connector P9
Connector P6
Connector P1
Connector P3
LO, HI, 12V, COM, C1, C2, R2, R1
2. Thermostat Control Inputs
TCOM, TSTAT
3. Ventilation Control Input Group
R, B, O, W, G
4. Furnace Interface Control Group
FNC, FCOM, FNO
The Fireplace Control Input Group represents the home owner’s desire for fireplace operation and are considered first priority by the
HRV200PLUS controller. These inputs include signals from the fireplace dashboard controls, fireplace remote controls and dedicated
hearth room thermostats. Inputs to activate the fireplace from this control group are processed with no regard to the other two input
groups.
The Thermostat Control Inputs are used to couple the HRV200PLUS to the primary heating system to provide comfort heating when the
temperature at the main thermostat falls below the set point. The Thermostat Control will not shut off the Fresh Air Fireplace if there is
an input from the Fireplace Control Input Group.
The Ventilation Control Input Group receives signals from the ventilation controls installed with the system to maintain desired fresh air
ventilation rates in the building envelope. Since the Fresh Air Fireplace operation requires continuous high speed ventilation, the
Ventilation Control Inputs are ignored unless the Fresh Air Fireplace in not in use.
The Furnace Interface Control Group consists of a single pole, double throw set of contacts to provide an interface with the furnace
control board and the main thermostat to enable furnace blower operation to distribute fresh air through the existing duct work.
1. Fireplace Operating Modes – Connector “P9”
a. OFF Mode
The HRV is idle until an input is sensed. This is the normal standby state when the HRV Plus is powered but not receiving any
command inputs.
b. Fireplace High Fire Mode
All fireplace demands for fireplace operation from the hearth room result in a 12VDC signal sent to the HRV controller “HI”
input terminal on the P9 connector strip. This includes the ON/OFF switch on the fireplace, demands from the fireplace remote
control and heating calls from a dedicated fireplace thermostat.
Fireplace High Fire Mode is activated when 12VDC is sensed at the “HI” input terminal. The HRV/Fresh Air Fireplace system
executes pre-purge and ignition processes as follow:
c. Caliber NXT Plus/6100 PLUS
1) Initiation
a) Blower motor on HIGH for system pre-purge.
b) C2 terminal is energized 12VDC activating the electric ember lights on the Fresh Air Fireplace.
c) Fifteen-second pre-purge timer activates while the HRV closes the alternate exhaust damper.
d) C1 terminal is energized 12VDC to override the pressure switch in the Fresh Air Fireplace.
e) R1 is energized 12VDC activating the IPI ignition circuit to initiate the fireplace ignition process. In the HRV, the R2
terminal must be jumpered to 12V to supply power to R1 at the Fresh Air Fireplace.
f) The thirty-second draft-proving delay timer activates.
g) The Fresh Air Fireplace lights.
h) The thirty-second draft-proving delay timer expires, C1 terminal is de-energized and the Fresh Air Fireplace pressure
switch is monitored for sufficient flow at the flue collar for proper operation. IF SUFFICIENT FLOW IS NOT SENSED
AT THE FLUE COLLAR OF THE FRESH AIR FIREPLACE AFTER THIRTY SECONDS OF OPERATION, THE FRESH
AIR FIREPLACE FLAMES WILL EXTINGUISH LEAVING THE ELECTRIC EMBERS ILLUMINATED ONLY. THE
FRESH AIR FIREPLACE WILL NOT SUSTAIN NORMAL OPERATION UNTIL THE LACK OF FLOW IS CORRECTED!
02/04
4034-102 Rev F
29
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
2) Termination
a) When the 12VDC signal is removed from the “HI” input terminal, R1 terminals is immediately de-energized shutting
down fireplace operation.
b) The blower motor remains on high speed for 20 seconds.
c) The C2 terminal is de-energized extinguishing the electric ember lights.
d) The blower motor remains on low speed for an additional five minutes.
e) The HRV returns to its previous state.
d. Novus Plus/6000 Plus
Æ
1) Initiation
a) Blower motor on high for system pre-purge.
b) Fifteen second delay timer activates while the HRV energizes the alternate exhaust damper to move closing off the
alternate exhaust port.
c) The K7 relay energizes making connection between the R1 and R2 terminals activating the IPI ignition circuit to
initiate the fireplace ignition process.
Once fireplace operation is no longer required, the system terminates the operation of the fireplace by deactivating
the ignition process and executing a post-purge as follows:
2) Termination
a) When the 12VDC signal is removed from the “HI” input terminal, the K7 relay is de-energized opening the connection
between R1 and R2 shutting down fireplace operation.
b) The blower motor remains on high for system post-purge - 20 seconds.
c) The HRV returns to its previous state.
2. HRV Defrost Mode
When the fireplace is not in use, the HRV200PLUS provides continuous ventilation for the whole house. During this normal
ventilation operation, the aluminum core of the HRV can develop frost when outdoor temperatures fall below 25°F. The Fresh Air
Fireplace is used as a source of heat to defrost the HRV200PLUS during cold weather ventilation operation. During HRV Defrost
Mode, the HRV will independently demand fireplace operation.
The HRV Defrost Mode sequence of operation is identical to Fireplace High Fire operation. This will include a pre-purge, ignition
process, burn time and post-purge.
HRV Defrost Mode is activated according to the following Table based on the Supply Air Temperature (SAT) sensor and terminates
based on the Exhaust Air Temperature (EAT) sensor.
WARNING!
The Fresh Air Fireplace is used by the HRV200PLUS
for normal defrosting of the aluminum core during
cold weather ventilation operation. This results in
fireplace operation independently initiated by the
HRV200PLUS.
The ON/OFF switch on the fireplace will not pre-
vent fireplace operation during HRV Defrost Mode.
Non-fireplace defrost may be achieved by install-
ing the optional defrost assembly HRV99DEFKIT.
30
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
3. Fireplace Control Terminals
Fireplace Control Terminals – Connector P9
Input
Function
Dry Contact Output to initiate the fireplace ignition process.
R1
Note: Caliber NXT Plus/6100 Plus Applications: R1 sends a 12 VDC
signal to the fireplace board to initiate the ignition process. R2 has a jumper
to 12V.
Dry Contact Output to initiate the fireplace ignition process.
R2
Note: Caliber NXT Plus/6100 Plus Applications: R2 has a jumper to 12V.
R1 sends a 12 VDC signal to the fireplace board to initiate the ignition
process.
12 VDC Output to energize the electric ember light relay on the
fireplace board.
C2**
12 VDC Output to override pressure switch operation during the first
thirty seconds of the ignition process.
C1**
12 VDC common output to the fireplace board.
Com**
12 VDC output to the fireplace ON/OFF switch for Novus Plus/6000
Plus applications or to the fireplace board for Caliber NXT
Plus/6100 Plus applications.
12V
Fireplace High Fire input to control - 12 VDC.
INPUT NOT USED
HI
LO
** These terminals used for Caliber NXT Plus/6100 Plus applications only.
See Figures 18-19 for wiring diagram.
4. Thermostat Operating Modes – Connector “P6”
a. OFF Mode
The HRV is idle until an input is sensed. This is the normal standby state when the HRV Plus is powered but not receiving any
command inputs.
b. Thermostat ON Mode
When 24VAC is sensed across the thermostat input terminals (“TSTAT” & “TCOM”), the HRV control executes Fireplace High
Fire Mode, as described above. When the 24VAC signal is removed from the Thermostat input terminals, the HRV returns to
its previous state.
02/04
4034-102 Rev F
31
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
5. Ventilation Operating Modes – Connector “P1”
a. OFF Mode
The HRV is idle until an input is sensed. This is the normal standby state when the HRV Plus is powered but not receiving any
command inputs.
b. Low Speed Ventilation Mode
Low Speed Ventilation Mode is activated when 12VDC is sensed at the “O” terminal. The HRV operates with blowers on low
speed and defrost control is active. High Speed Mode inputs override Low Speed inputs and place the unit in High Speed
Mode.
c. High Speed Ventilation Mode
The HRV is operating with blowers on high speed and defrost control is active. When 12VDC is sensed continuously at the “B”
terminal for more than 4½ seconds, the HRV will enter High Speed Ventilation Mode for as long as the override signal is
present, then return to its previous mode when the input is removed.
The dehumidistat on wall-mounted controls place the HRV into High Speed Ventilation Mode for moisture control. The
dehumidistat senses the humidity in the living area and activates high speed blower operation when the humidity level exceeds
the set point selected by the home owner. The HRV returns to its normal operating mode when the humidity level in the indoor
air stream falls below the set point.
d. High Speed Ventilation Mode – 20 Minute Timer
The HRV is operating with blowers on high speed and defrost control is active. When the override signal is sensed at the “B”
terminal for more than ½ second but less than 4 ½ seconds, the HRV will enter High Speed Mode for 20 minutes then return
to its normal mode.
e. Intermittent Ventilation Mode
Intermittent Ventilation Mode is activated when 12VDC is sensed at both the “W” and the “O” terminals. The HRV operates on
Low Speed Ventilation Mode for 20 minutes then is off for 40 minutes. High Speed Mode inputs override Intermittent Ventilation
Mode inputs and place the unit in High Speed Mode.
Ventilation Jumper Table
To Achieve this Operating Mode:
1. Continuous Low Speed Ventilation
2. Continuous High Speed Ventilation
Place Jumper Between:
"R"
"R"
"R"
"O"
"B"
"W"
3. Intermittent Ventilation
20 min. on, 40 min. off
LowSpeed Ventilation only
4. Continuous Low Speed Intermittent Ventilation
"R"
"O" & "W"
6. Ventilation Control Terminals - Connector P1
Input
Function
High Speed Ventilation Mode input control - 12VDC input.
Dual Operating Modes:
B
1. 20 minute override if 12VDC signal duration is sensed between ½ second 4½ seconds.
2. ON/OFF override if 12VDC signal duration is sensed more than 4½ seconds.
High Speed Input overrides Low Speed Input.
R
O
W
G
Power supply out from control board - 12VDC output.
Low Speed Mode input to control - 12VDC input
Intermittent Ventilation Mode Input - 12VDC input
LED Output. This output is on anytime the HRV is operating in high speed.
32
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
7. Furnace Interface Operating Modes – Connector “P3”
See Section “L. WIRING” for wiring diagram, Figure 23.
a. OFF Mode
The furnace blower operates normally based on thermostat and furnace control board functionality.
b. Interlock Mode
The furnace interface relay provides connection between “R” and “G” on the furnace control board, creating demand for
continuous furnace blower operation.
8. Furnace Interface Terminals
Input
FNC
Function
Normally Closed Terminal - Dry Contacts
Common Terminal – Dry Contacts
Normally Open Terminal – Dry Contacts
FCOM
FNO
02/04
4034-102 Rev F
33
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
L. WIRING
1. Fireplace Control Wiring
(Caliber NXT Plus/6100 Plus)
Æ
Figure 18
Æ Caliber NXT Plus or 6100 Plus & HRV Wired Together
34
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
2. Fireplace Control Wiring
(Novus Plus/6000 Plus)
Æ
Figure 19 - Novus Plus Control Wiring
Æ
Figure 20 - 6000 Plus Control Wiring
Æ
02/04
4034-102 Rev F
35
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
3. HVAC System Thermostat Control Wiring
(use to interface HRV200PLUS with the central HVAC system)
Figure 21
Thermostat Control Wiring
(For integrated use with the central furnace and thermostat.)
36
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
4. Ventilation Control Wiring
(Controls may vary.)
Figure 22
Ventilation Control Wiring
02/04
4034-102 Rev F
37
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
5. Furnace Interface Wiring
Note: HRV board has a built-in isolation relay
to ensure thermostat compatibility.
Figure 23 - Furnace Interface Wiring
38
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
M. MAINTENANCE INSTRUCTIONS
Proper maintenance is critical to the proper operation of the HRV200PLUS. The following schedule should be followed:
1. Monthly Maintenance - Inspect Exterior Hoods
Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially
important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen).
WARNING!
Blockage of weather hoods may cause a pressure imbalance within the house. Severe blockage will cause intermittent
operation of the Fresh Air Fireplace!
2. Quarterly Maintenance
a. Clean Air Filters
The standard filters equipped with your HRV200PLUS are removable and washable.
1) Open the access door.
2) Carefully grip the end of the core and pull evenly outward until the core slides out one or two inches.
3) Remove the filter clips.
4) Once clips are removed, filters can be taken off the core and rinsed with water or a combination of mild soap and water.
Do not clean in the dishwasher.
5) To reassemble, place the clean filters (wet or dry) back into their positions against the core and return the clips to their
original position.
6) Slide the core back into its original position.
b. Check and Clean Drain Lines
3. Semi Annual Maintenance - Clean Core
a. Open the access door.
b. Carefully grip the ends of the core and pull evenly outward until core slides out. Core may be snug, but will slide out of the
channel.
c. Remove the filter clips and filters. Rinse filters with warm soapy water.
d. Wash the core in warm soapy water (do not use the dishwasher).
Note: Core installation label is on the outer end
of the core.
e. Install the clean core as follows:
1) Locate the filters on the core to cover the open surface and replace the filter clips.
2) Mount the bottom flange of the core guide into the H channel approximately 1/4” (6mm).
3) Mount the left or right flange of the core guide into the H channel approximately 1/4” (6mm) followed by the other side.
4) Mount the top flange of the core guide into the H channel approximately 1/4” (6mm).
5) With all four corners in place and the core straight and even, push firmly in the center of the core until the core stops on
the back of the cabinet.
Note: Core will appear to stick out from the cabinet
approximately 1/8” (3mm). This is designed this way so
the access door will fit tight against the core.
02/04
4034-102 Rev F
39
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
4. Annual Maintenance
a. Inspect and Clean Drain (condensate) Lines (if required)
Inspect the drain line, drain spout and P-trap for blockage, mold or kinks. Flush with warm soapy water. Replace if worn, bent
or if you are unable to clean.
b. Inspect and Clean Duct Work (if required)
The duct work running to and from the HRV200PLUS may accumulate dirt. Wipe and vacuum the duct once every year. You
may wish to contact a heating/ventilation company to do this.
c. Inspect and Clean the Fans (if required)
Note: Before attempting the following task, thought
should be given to having a qualified service technician
complete the service work.
Fans may accumulate dirt causing an imbalance and/or excessive vibration of the HRV200PLUS. A reduction in the air flow
may also occur. In new construction this may result within the first year due to heavy dust and may occur periodically over
time depending on the outdoor conditions.
1) Unplug the HRV200PLUS and open the service door.
2) Remove the core.
3) Remove the ducting (metal and/or flexible insulated type) from the black ports which are connected immediately inline
with the fan assembly.
4) Use a small brush, such as an old toothbrush or pipe cleaner and insert it:
a) Through the large opening of the fan assembly, and then
b) Through the smaller opening in the end of the fan assembly.
5) Scrub the individual fan blades until clean. Avoid moving or damaging balancing flat weight. The clip is usually found on
one or more of the fan blades.
6) Vacuum and wipe.
7) Reassemble making sure the ducting is reattached firmly and the insulation and moisture barrier are sealed and taped.
5. General Maintenance
Wipe down the inside of the cabinet with a damp cloth to remove dirt, bugs and debris that may be present.
40
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
N. LED DIAGNOSTICS
The HRV200PLUS comes equipped with a diagnostic LED mounted in the right side of the cabinet just below the power cord. This LED
indicates the state of the HRV - both normal operating modes as well as abnormal fault conditions. The LED response codes are
summarized in the following table:
02/04
4034-102 Rev F
41
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
O. TROUBLESHOOTING GUIDE
42
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
Æ
x
02/04
4034-102 Rev F
43
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
x
44
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
P. ACCESSORIES
9HQWLODWLRQ &RQWUROV
)ORZꢀ6WDWLRQ
9HQWLQJꢀ$FFHVVRULHV
+59ꢀꢁꢁꢂ3OXVꢂ$FFHVVRU\ꢂ.LWV
3LWRWꢀ7XEH
*ULOOHVꢀꢁ*UHDVHꢁ)LOWHUVꢁꢂꢁ:HDWKHUKRRGV
Installing Remote Controls
Optional wall-mounted remote controls can be connected to the ventilator for greater control of operation. Although the necessary
connections are low voltage, we recommend that a certified contractor make all connections.
02/04
4034-102 Rev F
45
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
Q. REPLACEMENT PARTS
46
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS INSTALLATION INSTRUCTIONS
INDEX
A
H
R
Duct Installation 11
Duct Work
Central Furnace 9
Ducting
Central Supply Air 12
Exhaust Air
Kitchen 13
Fresh Air Supply 12
Materials 12, 13, 14
Warmside 13
Warmside Air Supply 12
Ducting Materials 15, 16
Accessories 45
Adjustable Grilles 13
Heating Season 2
High Fire Mode
Fireplace 29
Horizontal Termination
Typical 17
Recommended Geographic
Locations 2
Remote Controls 45
Replacement Parts 46
Room Air Defrost 5, 6
ÆAiirr FFlioltewrsBa3lancing 25
Air Flows 1
Æ
Air Handler 1
Air Supply 11
Warmside 12
Alcove Clearances 18
Alternate Exhaust 16
Alternate Exhaust Port 16
Aluminum Core 3
Annual Maintenance 40
Automatic Defrost System 3
Horizontal Termination Locations
18
S
HRV Defrost Mode 30
HRV Exhaust 11, 15
HRV200PLUS Application 2
HVAC System Thermostat Control
Wiring 36
Safety 2
Æ
Semi Annual Maintenance 39
Simplified Installation 7
Stale Air 2, 16
Supply and Exhaust Air Blowers 3
E
I
T
Electrical Service Clearances 18
Elevation 1
Engineering Data 3
Excessive negative pressure 25
Excessive positive pressure 25
Exhaust 11, 15, 16
Exhaust Air Blowers 3
Exhaust Port 16
Installation 3
Termination
B
Drain Line and P-Trap 10
Fully Dedicated 9
Partially Dedicated 8
Simplified 7
Supply-Return Method 7
Vent & Duct 11
Horizontal Exhaust 16
Installation 22
Vertical 20, 21
Back Drafting 1
Balancing
Air Flow 25
Flow Station 28
Termination Cap Locations 18
Termination Installation 22
Thermostat Control 29
Pitot Tube 26
Balancing Collar Instructions 25
Balancing Dampers 13
Balancing Procedure 1
Ventilator 10
ÆTrhoeurbmleosshtaotoOtinpgerGatuinidgeM4o2d,es433, 144
Typical Horizontal Termination 17
Typical Vertical Termination 20
Exhaust Termination 16
Horizontal 16
Exterior Hoods 39
Installation Diagrams 7
L
Blower Speeds 24
Æ
LED 3
LED Diagnostics 41
F
C
V
ÆFireplace Control 29
Cabinet 3
Caliber NXT Plus/6100 Plus
Vent
Installation 11
Vent Height 22
Vent Height for Vertical Termina-
tion 22
Vent Pipe
Terminals 31
M
Æ
Fireplace Control Wiring
CaliberNXT Plus/6100 Plus 34
Novus Plus/6000 Plus 35
Firestop Spacer 23
Flow Rates 13
1, 2, 29, 34
Central Forced Air System 12
Central Furnace Ductwork 9
Central Supply Air Ducts 12
Chase/Termination Installation 22
Clearances
Alcove 18
Electrical Service 18
Climate 2
Control Terminals
Fireplace 31
CoolVent
Structural Support 15
CoolVent Support 14
Core 39
Maintenance 39
Monthly Maintenance 39
Mounting 3
N
Connections 14
Flow Station Balancing 28
Flue Collar 14
Flue Exhaust 18
Forced Air Furnace 1
Fresh Air 2
Inlet 11
Vented Combustion Equipment 1
Ventilation Control 29
Ventilation Control Wiring 37
Ventilation Operating Modes 32
Ventilator
Installation 10
Vertical Termination 20
Vertical Termination - Typical 21
Negative Air Pressure 25
No Defrost 5
Novus Plus/6000 Plus 30
Æ
O
Æ
ÆFresh Air Fireplace 2
Oil Furnace 1
Operating Modes 29
Fireplace 29
Defrost 5, 6
Exhaust 11, 14
Exhaust Guidelines 14
Flue Collar 14
Fresh Air Inlets 18
Fresh Air Supply 11
Fresh Air Supply Ducting
Install 12
Furnace Interface 33
Ventilation 32
W
Warmside Air Supply 12
Warmside Air Supply - 11
Wiring
D
P
Dampers and Grilles 13
Defrost
Fresh Air Fireplace 5, 6
No Defrost 5
Room Air 5, 6
Defrost Method 5
Defrost Mode 30
P-Trap 10
Partially Dedicated Installation 8
Performance 4
Pitot Tube Balancing 26
Power Ventilator 2
Fireplace Control
6000 Plus 35
Caliber NXT Plus/6100 Plus
34
Frost 5
Fully Dedicated Installation 9
Furnace Interface
Control 29
Operating Modes 33
Wiring 38
Novus Plus 35
Æ
Furnace Interface 38
HVAC System Thermostat
Control 36
Defrost Options 5
Æ
Q
Defrost System 3
Diagnostic LED 3
Diagnostics 41
Dimensions 4
Drain Line and P-Trap 10
Duct Adapter 12
Quarterly Maintenance 39
G
Ventilation Control 37
Wood Burning Fireplace 2
Wood Stove 1
Gas Fireplace 2
Gas Furnace 1
General Maintenance 40
02/04
4034-102 Rev F
47
Download from Www.Somanuals.com. All Manuals Search And Download.
HRV200PLUS GAS APPLIANCE
LIMITED WARRANTY
Hearth & Home Technologies Inc. (“HHT”) extends the following warranty for Heatilator Home Products® Heat Recovery
Ventilator Plus (HRV200PLUS) products installed in homes in the United States of America and Canada. Dealers and
employees of HHT have no authority to make any warranty or authorize any remedies in addition to or inconsistent with the
terms of this warranty. This warranty gives you specific legal rights. You may also have other rights, which vary from state to
state, regarding limitations on how long an implied warranty lasts, or that do not allow exclusion or limitation of incidental or
consequential damages.
Limited 5-Year Warranty
HHT warrants that all components of your HRV200PLUS, except for the heat recover core, will be free from defects in material
and workmanship for five years from the date of installation. The Limited 5-Year Warranty specified above is subject to the
conditions, exclusions and limitations listed below, is for the original user only, and is nontransferable.
Limited 20-Year Warranty
HHT warrants that the heat recovery core of your HRV200PLUS will be free from defects in material and workmanship for
twenty years from the date of installation. The Limited 20-Year Warranty specified above is subject to the conditions,
exclusions and limitations listed below, is for the original owner only, and is nontransferable.
Conditions, Exclusions, & Limitations of Liability
A. The Limited Warranties supplied by HHT apply only while the HRV200PLUS is in its location of original installation. These
Limited Warranties do not extend to defects caused by: (1) installation, operation or maintenance of the HRV200PLUS not
in accordance with the Installation Instructions, Operating Instructions, and the Listing Agent Identification Label furnished
with the HRV200PLUS; (2) installation which does not comply with local building codes; (3) shipping, improper handling,
improper operation, abuse, accident or unworkmanlike repairs; (4) environmental conditions, additional air handling
devices such as exhaust fans or forced air furnaces, or other causes; (5) interconnection with other appliances such as
central vacuums or clothes dryers; (6) installation or use of components not supplied with the HRV200PLUS or any other
components not expressly authorized and approved by HHT; and/or (7) modification of the HRV200PLUS not expressly
authorized and approved by HHT in writing. This warranty does not extend to products not manufactured or supplied by
HHT.
B. This warranty is limited to the replacement or repair of defective components or workmanship. Your sole remedy, and
HHT’s sole obligation under this warranty shall be HHT repairing or, at its discretion, replacing the defective components.
In no event shall HHT be liable for any incidental or consequential damages caused by your HRV200PLUS.
C. EXCEPT TO THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE
WARRANTIES SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF
THE WARRANTY OF THE APPLICABLE COMPONENTS SPECIFIED ABOVE. TO THE EXTENT PERMITTED BY LAW,
HHT DISCLAIMS ALL IMPLIED WARRANTIES, INCLUDING SPECIFICALLY THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
How to Obtain Service
To obtain service under this warranty you must:
1. Send written notice of the claimed condition to Heatilator Technical Service Department, Hearth & Home Technologies Inc.,
1915 W. Saunders Street, Mt. Pleasant, Iowa 52641-1563. You may also register your claim online at www.heatilator.com/
contact.asp.
2. Provide proof of purchase, proof of date of installation, model number and serial number to HHT.
3. Provide HHT reasonable opportunity to investigate the claim, including reasonable opportunity to inspect the
HRV200PLUS prior to any repair or replacement work and before the HRV200PLUS or any component of the
HRV200PLUS has been removed from the place of original installation.
4. Obtain HHT’s consent to any warranty work before the work is done.
Additional Information
If you would like information on current Heatilator products or want to locate a dealer in your area, call: 1-877-IAQ-VENT
(1-877-427-8368).
48
4034-102 Rev F
02/04
Download from Www.Somanuals.com. All Manuals Search And Download.
|
GPX Refrigerator 1536 0810 10 User Manual
Graham Field Blood Pressure Monitor 707A User Manual
Grizzly Biscuit Joiner T25688 User Manual
HANNspree Flat Panel Television DT12 10H1 User Manual
Harbor Freight Tools Lathe 95647 User Manual
Hayter Mowers Lawn Mower 41 Electric User Manual
Hearth and Home Technologies Indoor Fireplace ST 36TRB IPI User Manual
HP Hewlett Packard Computer Drive RDX160 User Manual
Hypertec Carrying Case 3107 User Manual
I Data Network Router ReRouter User Manual