Harman Stove Company Stove TL200 User Manual

Installation & Operating Manual  
The Harman Exception Wood Stove  
(Model TL200)  
R7  
SAFETY NOTICE  
PLEASE READ THIS ENTIRE MANUAL BEFORE YOUINSTALL AND USE YOURNEW ROOM HEATER. FAILURE TO  
FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTYDAMAGE, BODILYINJURY, OR EVEN DEATH.  
FOR USE IN THE U.S. AND CANADA SUITABLE FOR INSTALLATION IN MOBILE HOMES  
IF THIS HARMAN EXCEPTION MODEL TL200 STOVE IS NOT PROPERLY INSTALLED,AHOUSEFIREMAYRESULT.  
FORYOURSAFETY, FOLLOW INSTALLATIONDIRECTIONS.  
CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATIONINSPECTION  
REQUIREMENTS INYOUR AREA.  
CONTACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE  
PREVENTION BUREAU,ETC.) TO DETERMINE THENEED FORA PERMIT.  
CETTEGUIDE D'UTILISATIONEST DISPONIBLEENFRANCAIS.CHEZVOTRECONCESSIONNAIRE DEHARMANSTOVE  
COMPANY.  
SAVETHESEINSTRUCTIONS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Specifications  
3.5"  
3.75"  
Weight  
440 lbs  
6 inch  
Flue Size  
Log Length Recommended  
Heating Capacity  
18" with 20" Max  
1500 to 2800 sq. ft.  
4.4 Grams Per Hr.  
2.25 Grams Per Hr.  
Average Emissions  
Emissions on Low  
Blower Size (optional)  
Outside Air size  
105 cfm variable speed  
3 inch  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Specifications  
TopLoad Door  
TopLoad Opening  
FrontLoad Door  
Combination Top  
LoadDoorand  
Damper Arm  
Grates  
Side Shield  
Andirons  
FrontLoad  
Door Latch  
Ash Door  
AshDoor Latch  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Operation  
Alldoors must be closedwhile thestove is in normal  
operation, and the gaskets routinely examined for wear  
and replacedwhen necessary. The fuel door may be left  
General Considerations  
Draft  
Before you install and operate your Exception open andthe openingcoveredwitha screenwhen operat-  
ing asa fireplace. Gooddoor sealsare importantfor main-  
tainingcontrol of the stove. Operatingthe stove with the  
ash door open, or with a door inadequately sealed, could  
createa seriousoverfiring condition(discussedlaterinthis  
section).  
woodstove,please readthe entirecontents ofthis manual.  
Pay particularattention to the explanationof draft and its  
effect on stove performance in the venting section. By  
followingthe installationandoperating guidelines, youwill  
ensure proper draft and gain  
joyment fromyour stove.  
maximumefficiency anden-  
NEVEROPERATE WITHMORE THANONE DOOR  
OPEN AT A TIME  
Fuel  
Your Exceptionburns woodvery efficiently. Here  
are some guidelinesconcerningfirewoodthat willhelp you  
obtain the best performance.  
The glass used in your Exception is manufactured  
to exact standards to withstand the high heat of the fire,  
but like all glass, it must be treated with common sense  
and care. Never abuse the glass by slamming the door  
shut or strikingthe glass with a heavy object. If the glass  
is brokenor damaged, do not operate thestove untilit has  
been replaced(See instructions inthe Maintenance sec-  
tion.)  
Select hardwoods if possible,as they are heavier  
and containmore heatingcapacity (BTU’s) per load than  
do softwoods. Wood should be split and stored under  
coverfor “seasoning- ayear is recommended. Your stove  
is not an incinerator - do not burn garbage, painted or  
treated wood, plastic, or other debris.  
Keepthe area around thestove free from clutter.  
Keep all combustibles, including fuel, beyond the code-  
required clearance distance (48" or 1215 mm inthe U.S.,  
1525 mmor 60" in Canada). Neverstore fuelinfront of the  
stovewhereit couldinterfere withdoor operation,safeload-  
ing, andash removal.  
Grates  
The Harman Exception’s unique grate system con-  
sists of two flat bottom grates, and two front andirons.  
The bottom grates have slots which allow the ash to fall  
into theashpanby passinga poker back andforth across  
the grates. The andirons keep the fuel from coming in  
direct contact withthe glass, and keephot coals and em-  
bers from spilling out while reloading. Never build a fire  
directly against the glass.  
Andiron extensions (included with each stove) clip  
ontothe fixedandirons andserve toprotect theglass when  
top loading is used as the primary loading method. The  
extensions can be clipped on the outside or inside of the  
andirons.  
WARNINGS  
For use with solid wood fuel only.  
Do not burn garbage or flammable fluids such as  
gasoline, naptha, or engine oil.  
Do not burn any fuel other than wood, such as  
charcoal, which can cause increased carbon  
monoxide production or overfiring. Never use highly  
volatile substances in your stove, such as gasoline,  
which could cause an explosion.  
The Stove  
Doors  
The grates andandirons must remain inplace at all  
times. Do not tamper with or change the configuration of  
this grate system.  
Yourstove has a largeglass-paneleddoorfor load-  
ingandfireviewing, aseparatesmallerdoorforremovingashes  
and a top loading door. To open the glass door, turn the  
handle clockwise andpull out; to close the door, return the  
handle toanopen(9 o'clock)positionandpushinto engage  
the latch while turning the handle counterclockwise to the  
closed(6 o'clock)position. To openthe ashdoor, lift up the  
handle andpullout. Close the door by pushinginandpush-  
ing the handle allthe way down. To openthe top loaddoor  
move the woodenknoblocatedonthe leftside ofthe stove  
front and upward until it locks the topopen.  
If the latch in either of your Exception doors needs  
adjustment, followthe instructions giveninthe Maintenance  
section.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Operation  
Controls  
The Combustion Process  
Two important controls - the top loadingdoor handle  
andthe air controllever regulate the operationand output  
ofthe stove.  
CombustioninyourHarmanExceptionis controlled  
very precisely. Duringa woodfire, primarycombustion air  
enters the bottomof the stove, is directed upto thetop of  
the loaddoor and thendown past the glass, finally enter-  
ing the combustion chamber. Secondary combustion air  
enters the bottomof the stove andis delivereddirectly to  
the afterburner behind the firebox, where it provides the  
additional oxygen required for clean burning  
During combustion, burning proceeds through  
severalstages - aninitialevaporationstage, where mois-  
tureis releasedfromthewood;astage wherevolatilegases  
containing much of the wood’s heating capacity are re-  
leased and burned; and a charcoal stage, where the re-  
mainingcharcoalburns to releasethe additionalheat avail-  
able. What is left after this final stage is ash. Within the  
firebox, two or moreof these stages are generally occur-  
ringat once.  
Top loading door handle/damper interlock.The  
top loading door handle is linked to the bypass damper  
and serves two purposes. Move the handle forward one  
position (approximately 3") and the handle automatically  
opens the bypass damper. In this mode of operation the  
combustion gases go directly from the main combustion  
chamber to the flue collar and exit into the chimney.  
Continue moving and liftingthe handle and it opens  
the toploadingdoor.  
NOTE: The bypass damper must be open for  
smokeless loading. This is particularly important to re-  
member whenloadingwoodthroughthefront doorsince the  
front door andthe bypassdamper arenot interlockedinthe  
same way that the toploading door is interlockedwith the  
bypass damper. Open the bypass damper by moving the  
topdoorhandleforwardonepositionbeforeopeningtheloading  
door.  
Damper Open  
Damper Closed  
Top Load Door Open and Locked  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Operation  
Air Control  
Building and Maintaining the Fire  
The air control lever is locateddirectly below the ash  
TheHarman Exceptionwas testedwiththe fuel door  
lipof the stove. Usingthis lever youwillbe able tovary the open andclosed. If youoperate under normalconditions  
amount ofair deliveredto thefire, creatinga rangeof heat keepdoor closed.  
Set theair controllever at the maximumheat output  
setting, allthe way to the right. Open the bypass damper  
by movingthe toploadinghandleforward one position (ap-  
proximately3"). The convectionblower, if installed, should  
be off for the first five minutes after a reload.  
outputs. The low heat output setting is to the left, and  
high is to the far right. Do not, under any circumstances,  
alter the configurationor operation of the air controllever.  
Never use gasoline, gasoline-type lantern fuel,  
kerosene, charcoal lighter fluid, or similar liquids to  
start or “freshen up” a fire in this heater. Keep all  
such liquids well away from the heater while it is in  
use.  
Build a bed of paper and kindling; place several 1  
" - 2" (25 mm - 50 mm) split pieces of dry wood on top,  
followed by a few 2" - 3" (50 mm - 80 mm) split pieces.  
Ignite the paper and close the door.  
Allow the fire to burn until a good charcoal bed, 2" -  
3" (50 mm - 80 mm) is formed; close the bypass damper  
by pushingthe toploading handle all the way back until it  
locks closed. (Youmay needto leave the loaddoor open  
a crack to getthe blaze goingproperly, but neverleave the  
stove unattendedwithdoor open.) Addmore woodto cre-  
ate a deeper charcoal base (3" - 4", or 80 mm - 100 mm  
thick); remember to open the bypass damper if you are  
loadingfromthe front. Thiswillallowthe exhaust gases to  
pass directly into the flue outlet and reduce smoke spill-  
ageduring refueling.  
Once the charcoal bed is established you may add  
a full load of dry wood. After adding the fuel, leave the  
damper open and the air setting at maximum for 5 to 15  
minutes; close the damper and allow the air setting to  
remain on high for an additional 5 to 10 minutes. Then  
adjust the air lever andblower speedfor the desired heat  
output.  
Less  
More  
Belowthis setting, run the optional blower on "low"  
or "OFF". Higher air movement cools the  
secondary combustionarea whichcan leadto poor  
combustion and lower efficiency.  
Reloading  
Onceyouhavepreparedandmaintainedathick char-  
coal bed, you should be able to reload the stove, allow  
some open damper burning at the maximum air setting,  
close the damper and reset the air control in about five  
minutes.  
Blower  
To regulate the speed of the optional convection  
blower, adjust the control from low to high by turning the  
knob locatedon the blower. The blower speedshould be  
matchedto the air controllever setting.  
When the air setting is low, the blower should al-  
ways beat the minimum setting(corresponding toa blower  
speed of 750 RPM.) At higher settings, above first notch  
on the air control, the blower may be set to your desired  
comfort level. Be sure that the blower cord does not run  
7
under, over, above or infront ofthe stove.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Operation  
As you begin to operate your stove at higher tem-  
Operating as a Fireplace  
peratures, youwill notice a “hot” or unpleasant smell; this  
is just the paint goingthrough the curing process, and will  
disappear after afew fires.  
The followingguidelines for air settings canbe used  
for woodburning; as you become familiar withyour stove,  
you will know which settings best heat your home.  
• Minimum burn rate - air control fully to left.  
Medium low burn rate - air control moved 1" to right.  
• High burn rate - air control fully to the right.  
Note: At minimum burnrates the glass may get dirty  
but will cleanoff againat higher burn rates.  
The TL200 is testedandapprovedto beburned with  
the front loaddoor openandthe damperopen. Inthis mode  
of operation you get a true fire sound as well as appear-  
ance. Due to the cracklingand poppingof burningwood it  
is necessary to place the optional screen over the door  
opening. This prevents sparks fromentering the roomjust  
like ascreen over a fireplace.  
CAUTION  
The stove is hot while in operation. Keep children,  
clothing and furniture away. Contact may cause skin  
burns.  
Afterburner Viewport  
Overfiring  
This is a small ceramic window in the back of the  
firebox. Thiswindowallows youtoseetheAfterburner Com-  
bustion System in action. This glass may smoke up un-  
der some conditions but will burnoff again. It is OK if this  
glass is not totally clean.  
Overfiring  
Avoidoverfiring your stove, a potentially hazardous  
situation which can lead to overheating of combustible  
materials, damage to the stove, and in extreme cases,  
causea fire. Overfiringis causedby: 1. Too muchair flow-  
ing through the stove too quickly. 2. Improper positioning  
of the primary air controllevel too far to the right. 3. Inad-  
vertently leaving the damper open or 4. Not keeping up  
withroutinemaintenance, suchas checkingdoor gaskets  
for wear.  
Overfiringresults inexcessive fuelconsumption, and  
maycause parts of thestove orchimney connectorto glow  
red. If younotice signs of overfiring,reduce theair supply  
to the fire, and review the Maintenance section in this  
manual.  
Removing Ashes  
Some ashis goodfor proper burning. Too much ash  
cancause problems.  
Never letthe ashes in thefirebox buildup to over 2"  
in depth. Remove ashes periodically by raking a poker  
across the grates. Excessive ash build-up can prevent  
properventing of exhaust gases.  
Do notallow theashpanto overflow. This can cause  
damage to the grate. Empty the ash pan whenyou see it  
getting close to full. (Remember to close ash door while  
emptying the ash pan.)  
Disposal of Ashes  
Never leave the stove unattended if either the ash or  
load door is open. Overfiring may result.  
The Exception was designed to provide access to  
the ashpan without the need for opening the main door.  
Before opening the ash door and removing the ashpan,  
openthe bypass damper. Wearingheavyprotective gloves,  
open the ash door and remove the ashpan by pulling it  
forward by the handle. Close the ash door before taking  
the ashes outside forsafe disposal.  
A good time to empty the ashpan is before loading.  
This ensures that theashes willbe coldandsaferto handle  
than directly after poking the ashes down or tending the  
fire.  
In the event of a chimney fire, callyour localfire de-  
partment; make sure everyoneis safely out ofthe house.  
Reduce the air intake of the stove as much as possible  
using the air control lever; close the bypass damper to  
further restrict air flow. Do notthrow water on thefire; this  
cancausestove damage andcreateanevenmore danger-  
ous situation. Have your chimney professionally cleaned  
andinspectedbefore resumingburning inyour stove.  
WARNING: Ashes should be placed in a metal  
container with a tight fitting lid. The closed con-  
tainer of ashes should be placed on a noncombus-  
tible floor or on the ground, well away from all com-  
bustible materials, pending final disposal. If the  
ashes are disposed of by burialin soil or otherwise  
locally dispersed, they should be retained in the  
closed container until all cinders have thoroughly  
cooled.  
Never usethe ash disposal container for other  
trash. Wood ash can be added to your garden or  
compost.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Maintenance  
Like allfine equipment,your Exceptionrequires some  
routine maintenance and inspection. Follow the guide-  
lines inthissection toguarantee safe,efficient operation.  
The Fire Chamber  
The inside of the fire chamber should be exam-  
ined for damage to the refractory lining material, grates,  
castingorAfterburnerglass. If any bricks havebeen dam-  
aged, replacethemwithHarmanStove Company replace-  
ment parts.  
The Stove  
Surface  
The stove’sexterior surface shouldbe dusted pe-  
riodically with a soft cloth. For more thorough cleaning,  
wait until the stove is cool before using a damp cloth to  
cleanany blemishes.  
Glass - Replacement  
If thestove’s glassis crackedor broken, youmust  
replace it before operating your stove. Remove pieces  
carefully. Replace glass only with Harman Stove Com-  
pany replacement glass panels; do not use substitutes.  
To replace the glass panel, you will need to re-  
movethe door. To do this, open the door, lift it straight up  
andplace it ona soft surface.  
The Door  
If you have a gold plated front door it should never  
be buffed or polished. Abrasive cleaners and metal pol-  
ishes willremove theplatingandtherefore shouldnever be  
used. If the doorneeds to be cleaned, wait untilthe stove  
is completely cool, then usea sponge, soap andwater to  
gently removedirt andstains. Before relightingthe stove,  
remove all soapresidue andwipe dry.  
Carefully remove damaged glass, gasket material,  
and holddown clips (set aside).  
Referringto the diagram, note how thevarious com-  
ponents of the door systemfit together. Lay the load door  
facedownonthe softsurface,andinstalltheself adheasive  
1/4"” gasket material around the front face of the glass.  
Note: this glass hasa specialIRcoating onone side. This  
coating must be to the outside of the stove. The coated  
side has a label on it. Do not remove the label before in-  
stalling the glass. If labelis missing, check for continuity.  
Set the glass paneand gasket gently onto the door.  
Installthe holddown clips and tightenwith boltsas shown.  
Make sure there are no lumps in the gasket and tighten  
the screws atan evenamount. Reinstalldoor on  
stove.  
Controls  
To avoid a rust build-up on the inner surfaces of  
the controls,work thecontrols backandforthseveraltimes,  
during thesummer, or any prolongedperiod whenyouare  
not usingyour stove.  
Door  
Glass Gasket  
Glass  
Glass - Cleaning  
Sometimes itwill benecessary toclean ac-  
cumulated ash from the glass surface; allowing  
this ash to remain on the glass for long periods  
can result in “etching” due to the acidity of the  
ash. Thecreosote whichaccumulates ontheglass  
shouldburn off during yourhot fires.  
Never cleanthe glasswhile it is hot, anddo  
not use abrasive substances. Washthe surface  
with cool water, and rinse thoroughly. You may  
wish to use a non-abrasive cleaner specifically  
designed for use on stove glass. In any case,  
dry thoroughly before relightingyour stove.  
Hold Down Clips  
and Bolts  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Maintenance  
Gaskets  
The Chimney System  
Gaskets are used at strategic positions whenbuild-  
ing the Harman Exception for controlling the path that in-  
coming andoutgoingairandgasestake throughthe stove.  
You must check these gaskets from time to time, and  
replace themwhen necessary. The gaskets are made of  
fiberglass of different sizes (obtainable fromHarman Stove  
Company) and are fixed in place witha high temperature  
stove gasket cement. To change a gasket, first remove  
the wornfiberglass and cleanthe area with a wire brush.  
Also cleanany other surfaces that come into contact with  
the gasket. Place a small bead of cement in the area  
under the gasket, thenpress new gasket materialinto the  
channel; do not overlap the ends of the gasket. Seat the  
gasket firmly by applying pressure when possible; for ex-  
ample,after changingthe doorgasket, closethe door. Allow  
the cement to dry before usingyour stove.  
Creosote  
Whenwoodis burnedslowly, it produces tar and  
other organic vapors, as well as soot, whichcombine with  
expelled moistureto formcreosote . The creosote vapors  
condense inthe relatively cool chimney flue (associated  
with a slow burning fire). As a result, creosote accumu-  
lates on the flue lining. When ignited, this creosote can  
result in anextremely hot fire.  
The Afterburner on the Exception cuts creosote to  
almost nothing when properly burned with dry seasoned  
wood.  
The chimney should be inspected at least once  
every two months duringthe heating seasonto see if any  
creosote build-up has occurred. Checking your chimney  
andchimney connector more frequently, especially while  
you are gettingused to your stove, is recommended. To  
inspect this system, let the stove cool. Usinga flashlight  
and mirror, check the interior of the chimney connector,  
andthe chimney itself. If a significant layer of creosote or  
soot as accumulated(1/8"” or 3 mm)it shouldbe removed  
to reduce the risk of a chimney fire.  
Gaskets arelocated:  
Onthe doors to provide airtight closure.  
Between the damper and the damper frame.  
Handle  
Toclean depositsfromthesurface ofthe connec-  
tor, use a stiff wire brush after dismantling the connector  
assembly. To cleanthe chimney, use aspecially designed  
brush sized to fit your particular flue opening, or call an  
established chimney cleaningservice.  
At the end of the heatingseason, performa thor-  
ough examination of your chimney system, and have it  
repairedif necessary.  
The handle on the front door of your Exception is  
attached to a threaded shaft. After a period of time, you  
may find that the front door does not close as firmly as  
when your stove was new. This is due to a natural com-  
pression of the gaskets. To tighten the seal, open the  
door and rotate the handle one fullturn counterclockwise  
or bendthe latchplate onthe stove.  
Blower  
The optional blower on your Harman Exception  
stove requires very little maintenance. Youshould, how-  
ever, keep the air inlet and the motor free of dust and dirt.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Installation  
DO NOT INSTALL IN A SLEEPING ROOM  
Outside Air (optional)  
Assembly  
Blower (optional)  
The Exception is designed to accommodate the  
use of outside air introduced directly to the stove. The  
opening is located at the back of the stove behind the  
pedestal. An outside air connector plate attaches over  
this opening, usingtwo 1/4-20 x 1/2"” hex head bolts.  
Outside air is always required wheninstalling the  
Exception in a mobile home, and is requiredfor every in-  
stallation by certainlocalbuilding codes. Checkwith your  
local building inspector to find out requirements. Some  
signsto watchfor thatindicate a possible needfor outside  
air: poor performance ofother heatersor ofthe Exception,  
including smoke roll-out and odor; the disappearance of  
the same symptoms when a window is opened near the  
stove; andcondensation onwindows inthe winter. Mod-  
ern homes with tight windows and doors, vapor barriers,  
and particularly with exhaust systems are the most likely  
to requireoutside air.  
Bolt the mounting plate to the bottom rear of the  
stove withfour 1/4-20 bolts. Put the blowerinplaceonthe  
bracket and bolt fast. Tighten the bolts, but do not over-  
tighten.  
Thepower cordfor theblower must be connected  
toa groundedoutlet, andmay notbe routedabove, under,  
over oraroundthestove itself.  
An outside air duct less than 5' (1525 mm) long  
Blower Variable  
Speed knob  
may be 3" [80mm] in diameter, and be made of masonry  
tile, 26 gauge (0.019)galvanizedsteel, or other noncom-  
bustiblematerial; itshould have a 1" (25 mm)clearance to  
combustibles. Systems longerthan5'(1525 mm), or con-  
tainingmore thantwo elbows, should have a 4" (100 mm)  
diameter duct to provide anadequate flowof combustion  
air. Any system must have a damper that is capable of  
fully closing.The airduct must terminate outsidethe dwell-  
ingand be screened to keep debris, birds or animals out.  
3" Outside Air  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Installation  
Parallel versus Corner Installations  
Floor Protection  
Inall installations, the area under andaround the  
A parallel installation is one in which the back  
stove must be protected from falling ash and live coals. and sides of the stove are parallel to the walls behind and  
Theareaunderahorizontal runofchimneyconnector must to the side of the stove. A corner installation is one in  
also beprotected . This protector must be of noncombus- which theback ofthe stoveis positioneddiagonally across  
tible material, and positioned as shown in the accompa- a corner of the room. Each installation requires its own  
nying illustration. The guidelines for floor protection are: setof clearances.  
1) completely under the stove and any horizontal runs of  
For parallel installations, the required clearance  
connector; 2) 8"(200mm) inback of the stove; 3) 8"(200 distances from the stove are: 1) to the side wall, 20"  
mm) to each side; 4) U.S. 16"(405 mm) in front of the (450mm); 2) to the back wall, 14" (360 mm). From the  
doors; Canada 18" (450 mm) in front of the doors; 5) 2" chimney connector to the wall, 18"(360 mm) and to the  
(50 mm) to each side of any horizontal runs of chimney ceiling, 18"(450 mm). NOTE: For a verticalchimney con-  
connector.  
nector ina parallelinstallation the distance of the connec-  
tor to the side wall must be 32"(720 mm), due to the re-  
quired side clearance ofthe stove itself. Fireplace instal-  
lations must meet these same clearance requirements;  
specifically follow these guidelines for mantel and trim  
clearances.  
Forcorner installations,the clearancedistances from  
the stove are 14"(360 mm) from eachcorner of the stove  
measured straight back to the nearest combustible mate-  
rial, and 22" 360 mm from the chimney connector to the  
walls.  
Clearances  
Clearance is the empty space required between  
the stove or chimney connector to the nearest combus-  
tible surface or object, such as walls,ceilings, floors, or  
furniture. Clearance distances may only be reduced by  
usingmethods approvedby eithertheCAN/CSAB365 stan-  
dard (Canada) or NFPA211 (U.S.) Contact your building  
authority for information if you are interested in reducing  
clearancedistances otherthan thosepresented here.  
Fromthe frontof thestove, clearanceto combus-  
tible materials such as furniture, curtains, fuel, etc., is:  
48"(1215 mm) in the  
U.S.  
and  
60"  
(1525 mm) in Canada.  
14"  
8"  
22"  
14"  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Door Assembly/Installation Tips  
Door Glass  
Paw Bolt  
Be sure that the door glass is installed in the door with  
the label, located onthe glass, on the external side of the  
door.  
The paw bolt should be turned into the door from the  
inside approximately 14 turns.  
Withthe setscrew removed, turn the brass elbowonto  
the paw bolt approximately 5 turns, or until a 1/16"  
clearance is achieved between the elbow and the door  
face (make sure to stop onthe flat spot of the paw bolt).  
The set screw on the brass elbow must be aligned to  
contact the flat spot on the paw bolt, thentightenusing a  
5/32"Allen wrench.  
Rope the glass carefully to insure proper sealing.  
Apply the rope exactly along the edge of the external  
face of the glass, not overhanging or pressed too far in  
fromthe edge.  
Make sharp 90o turns at the corners.  
Overlap the ends of the rope at the upper left or right  
After attaching the door handle, close and latch the  
door by turning the handle to the six o'clock position.  
Duringthis process observe to see that the door rope is  
beingcompressedproperly.  
corners.  
Glass Retainer Clips  
If it does not compress, loosen the set screw and turn  
the paw bolt one additional turn into the door. Repeat as  
requiredto ensure a tight seal.  
Use the glass retainer clips and screws suppliedin the  
door kit.  
Use a 1/8" Allen wrench to tighten the glass clips to  
cast door with 10-24 x 3/8" screws supplied.  
HINGE PINS  
DOOR  
BRASS HANDLE  
HANDLE  
BOLT  
SET  
SCREW  
PAW BOLT  
GLASS  
WOOD  
HANDLE  
GLASS GASKET  
4 GLASS  
RETAINER  
CLIPS  
4 GLASS  
RETAINER  
BOLTS  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Exception Linkage Installation  
Beforeside shield  
is in place.  
Step 1: Remove left side shield  
The side shield has tabs on it that latch into holes on the  
side of the stove. This makes removing the side shield  
easy.  
Lift up on the side shield then pull out.  
slots for  
side  
shield  
tabs  
Step 2: Install the drive arm  
Withleft hand, slide new drive armthrough hole in side  
of stove. Withright hand,take 1/4x 20grade 8 bolt along  
with washer and insert through hole from insideof stove.  
Tightensnugly usinga 7/16" wrench.(Shown inFig. 2)  
Figure 1  
Figure 3  
DriveArmAssembly  
Heavy Washer  
1/4 x 20 x 1/2" Bolt  
Figure 2  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Exception Linkage Installation, cont'd  
Beforeside shield  
is in place.  
Step 3: Install the top lift arm  
Tightenthe 1/4-20 x 5/8 button headallenbolt. Bolt into  
the tab on the underside of the top lid. This bolt can be  
tightened fully. (See Fig. 6 & 7)  
slots for  
side  
shield  
tabs  
Slide the top lift arm onto the shoulder pin on the drive  
arm. Check positioning of toplift arm. (See Fig. 5)  
Using the 1/4-20 lock nut, secure the top lift arm to the  
lid. NOTE: The top lift armneeds to move onthe bolt. Do  
not tighten the lock nut. Youcanturn it snug thenback off  
1/2 turn.  
Operatethe complete linkage usingthe drivearmhandle.  
You'll knowif your bolts are too loose or too tight.  
Step4: Re-attachleftsideshield.
Place side shield under top load door arm  
Place tabs in slots andpress down to lock into position.  
Things to Check  
Makesure the toploaddoor (lid)is centeredfrom left to  
right. It is possible for it to get bumped off center during  
shipping and installation. This lid can be recentered by  
tapping inthe proper direction witha block of wood.  
Inextreme cases the lift lug(Fig 7)canget bent. Check  
to see that it is 90o fromthe lid.If adjustment is necessary  
the lugcan be straightenedwitha largeadjustable wrench.  
Side Shield  
After side shield is in place.  
Figure 4  
Self-LockingNut  
Self-LockingNut  
Before tightening  
the nut be sure  
the bolt is tight  
in the lid.  
Figure 6  
Figure 5  
Shoulder Pin  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Exception Linkage Installation, cont'd  
1/4 x 20" Self Locking Nut  
TopLift Arm  
Lift Lug  
1/4 x 20"  
Button  
head  
Allenbolt  
DriveArm  
Assembly  
Outside  
Damper Arm  
Shoulder Pin  
PivotArm  
Figure 7  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Venting  
The Harman Exception may be installed with a  
minimum of (150 mm) 24 gauge chimney connector  
pipe. Size of the connector should correspond to the  
Chimney Connectors and Chimneys  
Draft  
Draft is widely misunderstood. It is important that size of the flue collar opening. Do not use makeshift  
you, the stoveoperator, realize that draftis a variable ef- compromises. No partof thechimney connectormay pass  
through anattic or roof space, closet or other concealed  
space, or through a floor or ceiling. Whenever possible,  
avoidpassing theconnector througha combustiblewall; if  
you must, use anapproved wallpass-through, described  
later inthis section.  
fect, not a given quantity. Stoves and chimneys do not  
have draft, yetdraft isthe key to yourstove’s performance.  
Draft is a force, produced by an operating stove  
and the chimney to which it is attached. It is created by  
hot gases rising up the chimney, creating a pressure dif-  
ference betweenthe inside of yourhome andthe outside  
air. Itcontinually movesfreshcombustionair intothe stove,  
andhot exhaust gases out of the stove; without this con-  
stant flow, the fire willgo out.  
Assemble the connector beginningat theflue col-  
lar, with the crimped ends pointing towards the stove (to  
keep debris and creosoteflakes inside the system). Each  
joint, including the one to the stove’s flue collar and the  
one to the chimney itself should be secured with at least  
three sheet metalscrews. Screws may be a maximum of  
3 inches apart. A 1-1/4" (30 mm) overlap is required at  
each joint, including the flue collar attachment. No more  
than two 90 degree elbows should be used, and the total  
length of connector should not exceed 10 feet (3 m). All  
horizontal runs of connector must have a minimum up-  
wardslope of 1/4"(6 mm) per foot (20 mmper meter).  
Other factors, suchas barometric pressure, winds,  
the air tightness of the home, the total inside chim-  
ney volume, chimney height andthe presence of vent-  
ing devices such as exhaust fans also play a role in  
maintaining an adequate draft. Low barometric pres-  
sures, super insulated homes and exhaust fans can  
reduce draft; winds can play havoc with draft; and  
too large or too small a chimney volume can cause  
reduced draft due to the excessive cooling or not  
enough room to vent exhaust gases quickly.  
Introducing outside air directly to the stove may help  
remedy a low draft prblem. Some signs of inadequate  
draft are smoking, odor, difficulty in maintaining the  
fire, and low heat output. Overdraft can be caused  
by a very tall chimney even if it is the recommended  
size, and can cause overfiring of your stove. Signs  
of an overdraft include rapid fuel consumption, inabil-  
ity to slow the fire, and parts of the stove or chimney  
connector glowing red. It is important that you fol-  
low the chimney guidelines in this manual, including  
size, type, and height to avoid draft problems.  
Other causes of poor ventilation or draft are icing,  
exhaust fans, a blocked outside air inlet, and room air  
starvation. If your stove is sluggish and you get occa-  
sionalodor, check these possibilities and increase the air  
flow inyour home.  
Wall Pass-throughs  
Occasionally it is necessaryto pass the chimney  
connector through a combustible wall to reach the chim-  
ney. Dependingon yourlocalbuildingcodes, andthe per-  
tinentprovincialornationalcodes,there areseveralchoices  
for accomplishing this safely. Before beginning your in-  
stallation,contact localofficials, andalso thechimney con-  
nectorandchimney manufacturer forspecific requirements.  
Canada. Threemethods areapprovedbythe Cana-  
dianStandardsAssociation. Thediagramshowsone method  
requiringan18"(450 mm) airspace betweenthe connector  
andthewall. It allowsuse ofone ortwo covers as described  
in the diagram. The two other methods are described in  
detail in the current issue of CAN/CSA B365, the national  
standard.  
UnitedStates IntheU.S.,thenationalcodeis NFPA  
211. While many localities adopt this standard, be sure to  
check with local authorities before beginning your installa-  
tion.  
Wheninstalled andoperated accordingto this  
TheNFPA(NationalFireProtectionAssociation) per-  
mits four methods for passingthroughacombustible wall. A  
commonly usedmethodto pass througha walldirectly to a  
masonry chimney is toclear aminimum12"(300mm) around  
the entire chimney connector, andfill it with brick masonry  
which is at least 3.5"(90 mm) thick. A fireclay liner, mini-  
mum 3/8" (9 mm) wallthickness must runthrough the brick  
walltothe chimney liner (butnot beyondthe innersurface of  
the liner). It must be cemented in place withrefractory ce-  
ment. This method is illustrated. For details on the other  
three options, refer to the most recent edition of the NFPA  
211code.  
manual, the Exception will produce enoughhot gases to  
keep the chimney warmso that adequate draft is  
maintainedthroughout the burn cycle.  
Chimney Connectors  
In general, following these guidelines will en-  
sure compliance with allnational and provincial codes;  
prior to beginning your installation, check with your lo-  
cal building code official to check on additional local  
regulations which may influence the design and place-  
ment of your venting system.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Venting  
above the highest point with the 10 ft (3 m) radius top  
height. If there is not ten feet of clearancefrom thetop of  
the chimney, thenthe chimney must extend2 ft(6m) above  
the highest point within the 10 ft (3m) radius.  
The Chimney  
The Exception must be installed into a chimney  
approved for use with solid-fuel appliances. In the U.S.,  
the Exception must be connected to (1) a prefabricated  
chimneycomplyingwiththe requirementsfor TypeHTchim-  
neys in the Standard for Chimneys, Factory-Built, Resi-  
dential Type and BuildingHeatingAppliances, UL103, or  
(2)a code-approvedmasonry chimney with a flue liner. In  
Canada, the Exceptionis listedfor usewith prefabricated  
chimneys tested and listed to the high temperature (650  
degrees C) chimney standard, ULC S-629, or witha code  
approved masonry chimney. For mobile homes, the Ex-  
ception must only be installed withprefabricated chimney  
systems, including the installation components, tested to  
eitherUL 103or ULCS-629 whichhave beenapprovedfor  
use in mobile homes; the diameter should match the di-  
ameter of the flue collar opening.  
Do not connect this unit to a chimney flue servicing  
another appliance.  
NOTE: The restrictionof not venting more than one  
appliance to the sameflue applies to the U.S. specifically.  
Whileit is not recommendedthat youuse the same chim-  
ney for more than one appliance, in Canada certain ex-  
ceptions may be made. Be sure to contact your building  
code inspection official to see if this option is allowed in  
your area, and to find out the specific requirements for  
suchan installation.  
The minimum recommendedheight for any chim-  
ney is 16 ft (4.8 m) above flue collar height. For non-  
mobile home installations, a roundflue (either masonry or  
approvedprefabricated),of either6" (150mm), 7"(180 mm)  
or 8" (200 mm) may be used. For square or rectangular  
masonry chimneys, nominal sizes of 8" x 8" or 8"x 12"  
(200 mm x 200 mm, 200 mm x 300 mm) may be used.  
Codes require that solid-fuel chimneys extend 3 ft  
(0.9 m) above the point at which they exit from the roof,  
provided that no part of any structure is within the top of  
the chimney, then the chimney must extend 2 ft (6 m)  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Venting  
Existing Masonry Chimneys  
If you planonusinga pre-existingmasonry chim-  
ney, have it thoroughly inspected andcleaned. Any faults  
which make the chimney unsafe and unusable must be  
repaired priorto use. These caninclude improper height,  
structuraldefects, blockages,inadequate clearanceto com-  
bustibles,unsealedopeningsinto otherrooms ofthe house,  
signs of creosote or smoke leakage, a loose or absent  
clean-outdoor, or absence of a liner.  
Do not connect to any air distribution duct or system.  
Venting to a Masonry Chimney  
Whenconnecting toa masonry chimney, several  
provisions are standard. First, whether thechimney con-  
nector is vented to the chimney through a thimble or a  
breech pipe, neither must pass beyond the inner surface  
of the chimney liner, andboth must be firmly cemented in  
place with refractory cement. (A thimble is a masonry  
pipe which is inserted through the chimney wall, and is  
frequently thepreferred method; a breechpipe is a piece  
of steel pipe used the same way.)In Canada, a breech  
pipe has redges or protrusions to lock it firmly into the  
refractory cement. In either case, the chimney connector  
vents to the chimney throught the thimble or breech pipe.  
Using a thimble, the connector slides completely  
inside the masonry to the inner adge of the flue liner, and  
may be easily removedforchimney andconnector inspec-  
tion. A breech pipe must extend at least 2" (50 mm) into  
the room, so the connector can be attached with  
sheetmetal screws.  
Installing to a Prefabricated Chimney  
When venting your Exception using a prefabri-  
cated chimney, be sure to contact local buildingcode au-  
thorities, andto follow the manufacturer’s instructions ex-  
actly. Useonly themanufacturer’s parts; do notuse make-  
shift installation techniques. All prefabricated chimneys  
must be tested to either the U.S. or Canadian high-tem-  
perature standards, UL 103or ULC-629.  
Venting to a Masonry Fireplace Chimney  
In some situations, a code compliant chimney  
originally used for a masonry fireplace may be used to  
installyour Exception. Inadditionto therequirements found  
inthe previous paragraphs, it is importantto beaware that  
allclearances must be met, includingthose fromthe chim-  
ney connector to combustibles — 18" (360 mm) to sides  
and18" (450 mm) to ceiling. Do not forget to include floor  
protectioninyour plans. (SeeClearances andFloor Pro-  
tection in this section.) Since many fireplaces have ex-  
posed woodenmantels andtrim, pay specialattention to  
the clearances necessary to these materials.  
Ifyour fireplacechimney isbehindacombustible wall,  
you must use an approved wall pass-through system to  
gain access to the masonry chimney. The chimney con-  
nector mustenter the chimney ata placewhere it is lined,  
andthe fireplace must be madeinoperable. For example,  
you might remove the damper, replacing it witha secure,  
airtight, noncombustible seal (removable for inspection);  
this also satisfies the requirement that no room air must  
be allowedto enter the chimney.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Venting - Mobile Homes  
Moblie Home Installations  
NOTE: When solid fuels are burned completely, they  
produce water andcarbon dioxide. However, in long  
slow burns, a substantialamount of carbon monoxide  
may be produced. If allowed to build up, carbon  
monoxide (which is odorless) can prove fatally  
poisonous. Proper ventilation and draft will prevent  
this from happening. If you smell smoke, turn up the  
air controllever setting, andthoroughly ventilate your  
dwelling. Duringfutureburns, becarefulnotto overload  
the stove with fuel, so you will not be tempted to  
constantly operate at a low air control setting.  
-
Mobile home installations must use approved fac  
tory-built chimneys testedand listedfor this specific use,  
to eitherof thehightemperature standards, ULC S-629 or  
UL 103. Any components used to install the chimney  
must be listed for this use and supplied by the chimney  
manufacturer. Do not substitute makeshift compromises.  
InCanada, chimney connectors mustbe testedandlisted  
tothe standardin CAN/ULC-641-M87.  
In addition to meeting the size and height require-  
ments detailedinthe Chimney section, the chimney must  
also beremovable tothe roof line area inorder toallow for  
transport. Whendesigning your system, consult with the  
chimney dealer to ensure that your system meets this  
requirement, and ask for specific details on how to re-  
move it.  
Follow allclearances, floor protection andother gen-  
eral guidelines in the Installation section when installing  
your Harman Exceptionin your mobile home.  
Other important Mobile Home guidelines:  
• The stove must be securely attached to the mobile  
home floor.  
• All stoves installedin mobile homes must have a direct  
outside air connection. (See Assembly Instructions.)  
Avapor barrier must be inplace where the approved  
chimney system exits the mobile home.  
Caution: The structural integrity of the mobile home  
floor, walls, and ceiling/roof must be maintained.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Exception Parts List  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
1-10-08074  
Damper linkage weldment  
Damper pivot arm weldment  
Top lift arm weldment  
Left side shield  
1-10-08075  
1-10-08127  
2-00-05204  
3-40-05228  
3-40-05171  
1-10-08058  
2-00-07071-1  
2-00-07071-2  
3-40-05180  
4-31-08078  
2-00-04174  
1-10-08076  
2-00-05205  
1-10-08073  
2-00-05169  
1-10-05146  
3-50-05229  
1-10-08077  
1-10-08057  
1-10-08059  
1-10-08200  
1-10-08111  
3-40-05174  
3-44-11862  
3-44-53500  
4-00-05165  
2-00-05202  
3-00-05165-4  
2-00-05222  
2-00-05147  
1-10-08133  
3-40-900450125  
4-40-08113  
4-40-08115  
4-31-08055  
3-40-00121  
3-40-00122  
1-10-08158  
2-00-05191  
2-00-05226  
1-10-05148  
3-40-05185  
2-00-05223  
Wooden knob  
Ceramic fiber afterburner  
Left side plate assy.  
Left glass retainer clip  
Right glass retainer clip  
Afterburner glass  
Brass plated hinge (2 per)  
Hinge plate (4 per) (not shown)  
Front top weldment  
Right side shield  
Ash door hinge weldment  
Airwash extension  
Airslide weldment  
Latch bushing  
9.  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
18.  
19.  
20.  
21.  
22.  
23.  
24.  
25.  
26.  
27.  
28.  
29.  
30.  
31.  
32.  
33.  
34.  
35.  
36.  
37.  
38.  
39.  
40.  
41.  
42.  
43.  
44.  
Damper weldment  
Damper frame assy.  
Right side plate assy.  
Afterburner hood weldment  
Ramp assy.  
IR glass  
1/4" OD rope 60" (not shown)  
1/2" door rope (66"per) (not shown)  
Cast door-machined  
Glass retainer clips (4 per)  
Gold plated cast door (optional, same as 27)  
Andiron (2 per)  
Grates (2 per)  
Grate support weldment  
Standard brick (4 per)  
Angle cut brick (2 per)  
Side cut brick (2 per)  
Paw bolt  
Brass elbow  
Wooden handle  
Ash door assy.  
Ash door latch  
Damper Clip (2 per)  
Ash pan assembly (not shown)  
Brick insulation (2 per) (not shown)  
Andiron extension (2 per) (not shown)  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Exception (TL200) Parts  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exception TL200 WoodStove  
Harman Gold Warranty  
HARMAN GOLD WARRANTY  
6 YEAR TRANSFERABLE LIMITED WARRANTY  
(Residential)  
1 YEAR LIMITED WARRANTY (Commercial)  
Harman Stove Company warrants its products to be free from defects in material or workmanship, in normal  
use and service, for a period of 6 years from the date of sales invoice and for mechanical and electrical failures, in  
normal use and service, for a period of 3 years from the date of sales invoice.  
If defective in material or workmanship, during the warranty period, Harman Stove Company will, at its option,  
repair or replace the product as described below.  
The warranty above constitutes the entire warranty with respect to Harman Stove Company products. HARMAN  
STOVE COMPANY MAKES NO OTHER WARRANTY, EXPRESSED OR IMPLIED, INCLUDING “ANY” WAR-  
RANTY OFMERCHANTABILITY, OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. No employee,  
agent, dealer, or other person is authorized to give any warranty on behalf of Harman Stove Company. This  
warranty does not apply if the product has been altered in any way after leaving the factory. Harman Stove Com-  
pany and its agents assume no liability for “resultant damages of any kind” arising from the use of its products. In  
addition, the manufacturer and its warranty administrator shall be held free and harmless from liability from damage  
to property related to the operation, proper or improper, of the equipment.  
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.  
THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the user’s  
manual.  
THESE WARRANTIES WILL NOT APPLY if abuse, accident, improper installation, negligence, or use beyond  
rated capacity causes damage.  
HOW TO MAKE A CLAIM - Any claim under this warranty should be made to the dealer from whom this  
appliance was purchased. Then contact is made with manufacturer, giving the model and serial numbers, the date  
of purchase, your dealer’s name and address, plus a simple explanation of the nature of the defect. Extra costs  
such as mileage and overtime are not covered. Nuisance calls are not covered by these warranties.  
THIS WARRANTY IS LIMITED TO DEFECTIVE PARTS - REPAIR AND/OR REPLACEMENT AT  
HARMAN STOVE COMPANY’S OPTION AND EXCLUDES ANY INCIDENTAL AND CONSEQUENTIAL  
DAMAGES CONNECTED THEREWITH.  
WARRANTY EXCLUSIONS: Failure due, but not limited to, fire, lightning, acts of God, power failures and/or  
surges, rust, corrosion and venting problems are not covered. Damage and/or repairs including but not limited to;  
remote controls, filters, fuses, knobs, glass, ceramic brick panels, ceramic fiber afterburners, door packing, tile,  
ceramic log sets, paint, batteries or battery back-up and related duct work are not covered. Also excluded from this  
warranty are consumable or normal wear items including but not limited to; flame guides, grates, coal bars, after-  
burner hoods, fire brick, gaskets. Additional or unusual utility bills incurred due to any malfunction or defect in  
equipment and the labor cost of gaining access to or removal of a unit that requires special tools or equipment are  
not covered. Maintenance needed to keep the stove in “good operating condition” is not covered. This includes,  
but is not limited to, cleaning, adjustment of customer controls and customer education. Labor, materials, expenses  
and/or equipment needed to comply with law and/or regulations set forth by any governmental agencies are not  
covered.  
This Warranty provides specific legal rights and the consumer may have other rights that vary from state to  
state.  
In the event of change in ownership, the remaining portion of this warranty may be transferred to the new  
owner by sending the new owner information to the Harman Stove Company.  
PLEASE READ THE LITERATURE BY THE MANUFACTURER FOR THE VARIOUS ACCESSORY DE-  
VICES. THE MANUFACTURER WARRANTS THESE ACCESSORY DEVICES, NOT HARMAN STOVE COM-  
PANY OR THEIRWARRANTY ADMINISTRATOR. FURTHERMORE, THESE ACCESSORY DEVICES MUST BE  
INSTALLED AND USEDACCORDING TO THE RECOMMENDATIONS OF THE MANUFACTURER.  
REMEDIES - The remedies set forth herein are exclusive and the liability of seller with respect to any contract  
or sale or anything done in connection therewith, whether in Contract, in tort, under any warranty, or otherwise, shall  
not, except as herein expressly provided, exceed the price of the equipment or part of which such liability is based.  
CLARIFY - The above represents the complete warranty, which is given in connection with stoves, manufac-  
tured by Harman Stove Company. No other commitments, verbal or otherwise, shall apply except by a written  
23  
addendum to this warranty.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Baby Playpen ISPP066AB User Manual
Grizzly Drill H7827 User Manual
Hotpoint Cooktop E6005 User Manual
Hotpoint Refrigerator BL31 User Manual
HP Hewlett Packard Personal Computer C5J37AWABA User Manual
HP Hewlett Packard Printer 2230 series User Manual
Humminbird Fish Finder Wide Vision User Manual
Husky Paint Sprayer HDS750 User Manual
Husqvarna Tiller CT20 User Manual
Husqvarna Trimmer 240RBD User Manual