Harman Stove Company Furnace PF 100 User Manual

Installation & Operating Manual  
The Harman PF 100 Pellet Pro Furnace  
“Ce manuel est disponible en Français sur demande”  
R7  
SAFETY NOTICE  
PLEASE READ THIS ENTIRE MANUALBEFOREYOU INSTALLAND USEYOUR NEW ROOM HEATER. FAILURE TO  
FOLLOW INSTRUCTIONS MAYRESULT IN PROPERTYDAMAGE, BODILYINJURY, OR EVEN DEATH.  
FOR USE IN THE U.S.AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES  
IF THIS HARMAN PELLET FURNACE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR  
SAFETY, FOLLOW INSTALLATION DIRECTIONS.  
CONTACT LOCALBUILDING ORFIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATION INSPECTION  
REQUIREMENTSINYOURAREA.  
CONTACT YOUR LOCALAUTHORITY (SUCHAS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE  
PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FORAPERMIT.  
CETTEGUIDED'UTILISATIONEST DISPONIBLEENFRANCAIS.CHEZVOTRECONCESSIONNAIREDEHARMANSTOVE  
COMPANY.  
SAVETHESEINSTRUCTIONS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Assembly  
4
Venting  
10  
15  
21  
Installation  
Operation  
Maintenance  
29  
34  
Troubleshooting  
Feeder Parts  
35  
36  
37  
38  
39  
40  
Specifications  
Wiring Diagram  
Parts List & Options  
Warranty  
Testing Label  
Quick Reference Start-Up 41  
Please read this entire manual before you install and use your new  
furnace. Failure to follow instructions may result in  
property damage, bodily injury, or even death.  
DO NOT INSTALL IN A MOBILE HOME.  
SAVE THESE INSTRUCTIONS  
Harman Stove Company  
352 Mountain House Road  
Halifax, PA17032  
PF100 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Assembly  
Design  
The first thing that needs to be done is deciding  
where andhow the furnace willbe installed.  
Things that need to be takeninto considerationare  
VENTING, SUPPLY&RETURN DUCTING, ELEC-  
TRICAL, and Condensation drainage (if A/C is in-  
stalled). Don’t forget access to the furnace for service.  
Whenthereturnairinlet positionisknownthefilter  
boxand distribution blower can be installed. See pages  
5, 6, 7, 8.  
When the furnace is set into place venting can be  
done.  
Fig. 1  
Venting  
Use 4” pellet vent pipe to vent your PF 100.  
A combustionblower is used to extract the com-  
bustion gases fromthe firebox. This creates a negative  
pressure in the firebox and a positive pressure in the  
venting system as shown in fig. 2. The longer the vent  
pipe and more elbows used in the system, the greater  
the flow resistance. Because ofthese facts we recom-  
mend using as few elbows as possible and 30 feet or  
less ofvent pipe. The maximumhorizontal run should  
not exceed 18 feet.  
Be sure to use wall and ceiling pass through  
fittings (which are approved for pellet vent pipe )  
when going through combustible materials.Besure  
to usea startingcollartoattachtheventingsystemto the  
stove. The starting collar must be sealed to the  
stove flue collar with high temp silicone caulking  
or aluminumtape, and screwed into the stove flue  
collar at least three (3) places.  
Fig. 2  
Vent Pipe  
Clearances and Venting  
4” pellet venting pipe ( also known as PL vent ) is  
constructed of two layers with air space between the  
layers. This air space acts as an insulator and reduces  
the outsidesurface temperature to allowa clearance to  
combustibles of only2 inches. This 2 inch clearance is  
also approved by the pipe manufacturers. See images  
on left. See page 14 (Fig. 24 and 26) for larger images.  
The sections ofpipe lock together to form an air  
tight seal in most cases; however, in some cases a per-  
fect seal is not achieved. For this reason and the fact  
that the PF100 operates with a positive vent pressure,  
wespecify that alljoints withinthe structure should  
also be sealed with clear silicone.  
The shaded areas are the clear-  
ances for the PL vent pipe that must  
be maintained at 3”. After the vent-  
ing leaves the shaded area it may be  
installed at 2” to combustibles.  
(Only UL listed wall pass-throughs  
and fire stops must be used.)  
See NOTES:  
on page 12  
NOTE:Use only 4” diameter type “L” or “PL”  
venting system. Be sure to inspect and clean  
exhaust venting system frequently.  
4
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Assembly  
Filter Box  
(Cold Air Return)  
Top (same as bottom)  
Solid Side Panel  
Switch  
Blower access Panel  
Filter Frame Panel  
Blower access  
Panel Cover  
Bottom (same as  
top)  
Fig. 3  
NOTE:Read and follow all of the vent pipe  
manufacturers’ instructions on the proper  
installation andsupport ofthe vent pipe. Adhere to  
all clearances.  
Assembling Filter Box  
Tek screw from outside  
Solid Side Panel  
The cold air return filter boxcan be assembled  
with the filter frame on either side or the back, pro-  
vided there is access to the combustionblower and flue  
area.  
It isnotrecomendedthat the filterframebeinstalled  
on the same side as the ash door due to the need to  
access the combustion blower, filter, and flue pipe for  
service.  
Bottom  
1. Place the bottomon the floor. The edge closest  
to the knockouts will be the edge towards the furnace.  
See Fig. 4.  
Knockouts  
2. Place the desired vertical panelinside the bot-  
tom trayand hold into place with one Tek screw in the  
bottommiddle hole. (solid panelshown) See Fig 4.  
PF100 5  
This Edge Toward  
Furnace  
Fig. 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Assembly  
Filter Frame Panel  
Assembling Filter Box, Cont’d  
3. Place the filter frame panelinside the bottom  
and inside the solid panelcorner. See Fig. 6 for corner  
detail. Make surethat the filter opening isup.See Fig. 5  
Hold thefilter panelto thesolid panelwith aTek screw  
inthemiddle hole ofthesolid panel, and oneinthe bot-  
tommiddle holeunder the filter opening.  
Filter opening must be up  
NOTE: Do notput anyscrewsinto anyofthetop  
holes at this time.  
Fig. 5  
Fig. 6  
Open Side Panel  
4. Place the remaining panel, (in this case the  
blower access panel) in the bottompaneland into the  
corner ofthe solid panel. SeeFig. 7. Make surethat the  
panelisintheuprightposition.Therearenocovermount-  
ingholesinthe bottomedgeofthispanel. Holdthepanel  
into place with one Tek screw in the middle holeofthe  
solid panel and one in the bottom middle hole of the  
blower access panel.  
Fig. 7  
6
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Assembly  
Assembling Filter Box, Cont’d  
5. Placethetoponthefilterboxasshowninfigure8. At  
this time allTek screws canbe insertedaround the filter  
box.  
Top  
Note: Except for the (6) screws that attach the  
blower access panelin place. There should not be any  
screws protruding fromthe box on the side toward the  
furnace. Also DO NOT put a screw into the top center  
ofthefilter panelas ascrewinthis locationwillinterfere  
withthefilter access cover.  
6. Pryout the two knockouts inthe topofthe box  
and installtheflexconnector and the switch. See Fig. 9.  
Note: Don’t forget the HI-MED-LO switchlabel  
onthe switchbefore the locknut.Make surethat the set-  
screw on the flex connector is not pointing toward the  
furnace end of the box when the locknut is fully  
tightened.The filter boxis now readyto installonto the  
furnace.  
Fig. 8  
3 Speed Switch  
Follow the Blower mounting instructions onpage  
8 before continuingto step #7.  
Note: The blower should be mounted onthe fur-  
nace before thefilter boxfor easeofdistributionblower  
installation.  
Flex connector  
Note: It is best to wait untilthe blower , filter box,  
and cold air return duct work isinstalled before install-  
ing the filter and side panel.  
Access Panel  
Cover opening  
7. After the Filter Box is installed on the furnace  
the electricalwiring to the three speed switch needs to  
be completed. WHITE to WHITE, VIOLET to the  
center terminalof the switch, and the BLACK, RED,  
BLUE to the terminals shown.  
Fig. 9  
Note: Theoptional1500 CFM blower is a single  
speed blower, therefore the three speed switch willnot  
be used. The optional 2000CFM blower is a 4 speed,  
only hook up the three colors shown and tape off the  
orange wire. See Fig. 10.  
Yellow on 2000 CFM motor  
8. Installtheaccess panelcover byhooking the lip  
at thebottomofthe coverover theedge inthe filterbox.  
Use 6 Tek screws to secure the access panel.  
Violet 120VAC  
9. To installthe filter, insert the filterinto the filter  
slot and slide completely into the frame. Take note to  
the air flowarrow on the filter when installing.Slide the  
filteraccesscoverovertheopeningwiththeupright angle  
toward the filter box. If aTek was put into the middle  
hole bymistake, remove the screw to allow the access  
Fig. 10  
cover to fit properly.  
PF100 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Assembly  
Blower Assembly  
Installtheblowermountingbrackets onthe blower  
as shown in Fig. 11.  
1. Install(4)Tekscrewsoneachsidewhereshown  
in Fig. 11. Start with the two center screws.  
NOTE: There are two smallholesinthe discharge  
endofthe blower that matchthe two centerholesonthe  
small angle of the blower bracket. The two (2) outer  
holes are drilled bytheTek screws.  
Mounting Screws  
Fig. 11  
Fig. 12  
Fig. 13  
2. Mount blower with brackets installed on the  
furnace as shown in Fig. 12. Each side will require 6  
Tek screws.  
NOTE: Thefurnace blower opening ismade large  
enough for the use of a 1500 or 2000 CFM blower.  
The blowermounting bracketswillfit either blower. The  
inner hole patternis for the 1000 CFM blower and the  
outer pattern is for the 1500 or 2000 CFM blower.  
NOTE: These Blower Motors are not designed to  
be operated without any positive static back  
pressure. OPERATION WITHOUT SUPPLY  
DUCTWORK OR IN FREE AIR WILL CAUSE  
MOTOR OVERLOAD AND PREMATURE  
FAILURE.  
CAUTION: Regardless of the supply air duct size  
installed, the Distribution Blower Motor MUST be  
checked forrunning Amperage. Check themotor name  
plate for thefullload AMPS. Iftheamperage is running  
higher than that listed, a supplyair restricting damper  
mayberequired to increase the supplyplenumpositive  
static pressure.  
3. Mount the filter box on the furnace with ( 8 )  
10 x 3/4 Tek screws, 3 on each side. Visually locate  
these holes so you are familiar withtheirlocationonthe  
filter boxandthe furnace. Access to the mounting holes  
can be gained through the blower access panel cover  
and the filteropening. See Fig. 14.  
Note: Two pieces of 2x4 stacked laying flat on  
thefloor 12inchesfromthebloweropening willsupport  
thefilterboxduring installation.  
Fig. 14  
8
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Assembly  
Firebrick  
Firebrick installation-required  
The firebrick isshipped inthe ashpan. It willneed  
to be placed on the brick shelf as shown in Fig. 15. It  
can be installed with either face to the fire. Hold the  
brick longways and slide it down into the slot on the  
shelf. There is a stop at the rear ofthe shelfto stop the  
rearward travel.The brick just sits on the shelf in the  
uprightposition.  
Fig. 15  
Baffle installation  
The upper heat exchanger baffle comes shipped  
along sidetheashpan. Remove theashpanandthebaffle.  
This upperbaffle needs to be installed before operating  
the furnace.  
The baffle has a long 45 degree bend on the bot-  
tom ofthe firebox side. See Fig. 17.  
The top has a 90 degree bend on the same side to  
use as a handle.  
Onthe oppositeside there are fourhooks that will  
support the baffle.  
Fig. 16  
Baffle support bracket  
Onthe front and rear ofthe fireboxwalls there are  
brackets that these hooks fit into. See Fig. 16  
Slide the upper baffle down on to the brackets,  
whileyou holdthe baffleagainst theheat exchanger.You  
willnotice that the upper baffle willholdthe lower baffle  
plate into position. See Fig.17.  
Upper heat  
exchanger baffle  
Note how the upper and lower baffles are held  
into positionbecause theywillneed to be removed  
during heatexchanger cleaning.  
o
45 bend  
Fig. 17  
PF100 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
Venting  
NOTE: Use only 4” diameter type “L” or “PL”  
venting system. Be sure to inspect and clean  
exhaust venting system frequently.  
INSTALLATION IS TO BE PERFORMED BY A  
QUALIFIEDINSTALLER.  
4” Type “L” or  
“PL” Vent pipe  
DO NOT INSTALLA FLUE DAMPER IN THE  
EXHAUSTVENTINGSYSTEM OFTHIS UNIT.  
DO NOT CONNECT THIS UNIT TO A  
CHIMNEY FLUE SERVING ANOTHER  
APPLIANCE.  
Fig. 18  
Thisistheminimumventingconfiguration.  
NOTE: This would only be allowed with non-  
combustible walls.  
The minimumvent configurationisa 90o orTeeon  
a starter collar and a 24” lengthhorizontal through an  
exterior wall. A cap or other bird screen on the end  
should direct the flue gasses down and awayfromthe  
structure. See Fig. 18.  
INSTALL VENT WALL PASS-THROUGHS AT  
CLEARANCES SPECIFIED BY THE VENT  
MANUFACTURER  
NOTE: All installation clearnaces and restrictions  
must be adhered to.  
Themaximumhorizontallengthis18feet.The mini-  
mumterminationheight above the exteriorgrade is18”.  
Themaximumtotallengthofanyconfigurationis30feet*.  
* ( see venting graph on page 13 for exceptions )  
NOTE: CleanoutTee’s should always beused on  
the transitions to horizontal pipe to allow easyaccess  
for cleaning.  
NOTE: Read and follow all of the vent pipe  
manufacturers’ instructions on the proper  
installation andsupport ofthe vent pipe. Adhere to  
all clearances.  
WARNING  
The venting graghallows for (one) 90deg. or Tee  
fittinginanyconfiguration.  
Keep combustiblematerialssuchasgrass, leaves, etc.  
at least 3 feet awayfromthe point directlyunder the  
vent termination. (between the vent andthe ground)  
Ifmore 90’s,T’s, or45sare neededthetotallength  
must be adjusted to allow forthe added restriction.  
Up to four (4) additional90’s,Tee’s, or equivalent  
45’s can be added as long as the overall length is ad-  
justed inaccordance with the values listed below.  
( See the venting graph onpage 12.)  
WARNING  
DO NOT INSTALL IN SLEEPING ROOM  
EachVertical ---- 90 deg. or T subtract 2.5 feet  
Each Vertical ---- 45 deg.  
Each Horizontal- 90 deg. or T subtract 5.0 feet  
Each Horizontal - 45 deg. subtract 2.5 feet  
subtract 1.5 feet  
CAUTION  
KEEP COMBUSTIBLES AWAY  
FROM FLUE OUTLET.  
Anyexteriorventing (vent pipe exposedto out-  
side ambiant temperatures) should be kept to a  
minimum, due topotentialcondensation problems.  
This is especiallyimportant in highhumiditycold  
weather climates, such as maritime areas, lake shores,  
and low river valleys.  
10  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
PF100 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
Requirements forTerminating the Venting  
WARNING:Ventingterminalsmustnotberecessed  
into awallor siding.  
NOTE: OnlyPL vent pipe wallpass-throughs and  
fire stops should be used when venting through com-  
bustible materials.  
NOTE: Always take into considerationthe effect  
the prevailingwind directionor otherwind currents will  
cause withflyashand /or smoke whenplacing the termi-  
nation.  
H. Avent must not be installed within 3 feet (90  
cm) above a gas meter/regulator assemblywhen mea-  
sured fromthe horizontalcenter-line ofthe regulator.1  
I. The clearance to service regulator vent outlet  
must be aminimumof6 feet.1  
J. The clearance to a non-mechanical air supply  
inlet to the building or the combustion air inlet to any  
other appliance must be a minimumof48”.1  
K. The clearance to a mechanicalair supply inlet  
must be aminimumof10 feet.1  
In addition, the following must be observed:  
A. Theclearanceabove grade must be a minimum  
of18".1  
B. The clearance to a window or door that may  
be opened must be a minimumof48" to the side, 48"  
below the window/door, and 12" above the window/  
door.1  
(with outside air installed, 6 feet )  
L. The clearance above a paved sidewalk or a  
paved drivewaylocated on public propertymust be a  
minimumof 7 feet.1,2  
M. The clearance under a veranda, porch, deck  
or balconymust be a minimumof12 inches.1,3  
NOTE: The clearance to vegetation and other  
exterior combustiblessuchas mulchis36” as measured  
from the center of the outlet or cap. This 36” radius  
continues to grade or a minimum of 7 feet below the  
outlet.  
( with outside airinstalled, 18)  
C.A12" clearance to a permanentlyclosed win-  
dow is recommended to prevent condensation on the  
window.  
D. The verticalclearance to a ventilated soffit lo-  
cated abovethe terminalwithina horizontaldistance of  
2 feet (60 cm) fromthecenter-line ofthe terminal must  
be aminimumof18".  
E. The clearance to an unventilated soffit must be  
a minimumof12".  
F. The clearance to an outside corner is 11" from  
center ofpipe.  
1Certain Canadian and or Localcodes or regula-  
tions mayrequire different clearances.  
2A vent shall not terminate directlyabove a side-  
walk or paved drivewaywhich is located between two  
single familydwellingsand serves bothdwellings.  
3Only permitted if veranda, porch, deck, or bal-  
conyis fullyopen on aminimumof 2sides beneaththe  
floor.  
NOTE: Wherepassage through a wall, or partition  
of combustible construction is desired, the  
installation shallconformto CAN/CSA-B365. (if in  
Canada)  
G. The clearance to an inside corner is 12".  
Inside  
Corner  
Detail  
Fixed  
Closed  
Fixed  
Closed  
Openable  
Openable  
= Air supply inlet  
= Vent terminal  
Fig. 20  
= Area where terminal is not permitted  
A
V
PF100  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting and Clearances  
Clearances to combustibles  
Ifinstalling thefurnace in a roomseparated fromthe  
remainingliving spaces,theminimumsize oftheroommust  
be no smaller than 8’ x 8’. See Fig. 21. The reason for this  
is heat build-upand required space for service and normal  
operation.  
This isthe minimumsize ofthe roomeven ifit is built  
ofnon-combustible material.  
High and low air vents MUST be installed between  
the roomandthe remaining living space. Each vent should  
be at least 72 square inches in area. ( The vent size will  
need to be increased if there is no return air ducting sys-  
tem.)  
The stripedareasare theminimum clearancesto com-  
bustibles which is 36” from stove body, not hopper or  
blower.  
FloorProtector  
PF100  
Skidplate  
Footprint  
The shaded area indicates the required floor protec-  
tion area. The PF100 requires 48” x 52” offloor protec-  
tioncenteredaroundtheskidplatefootprint. Flooringshould  
be aminimumof 26 gauge sheet metalcoveringthe instal-  
lation clearance area and 18” in front of, and 8” to either  
side of the ash pan door.  
18”  
48” wide  
The 18” clearanceonthe hopper endis a manufactur-  
ers recommendationfor adding pellets andor servicing the  
feeder mechanism.  
Theminimumclearanceto thetopoftheplenumis4”.  
Note the minimumheight to the bottomofthe supply  
duct ifit crosses the hopper.  
Theminimumductconfigurationtoalivingspaceabove  
the furnace is as shown in below.An offset ofat least 24”  
MUST be installedbetweenthe plenumandthe floorregis-  
ter. The register size MUST have an area of at least 240  
square inches.  
Fig.21  
The minimum ceiling height is 6’6”. This is set by the  
clearance to combustibles ( 28” ) from the top of the  
of the furnace. See Fig. 22.  
NOTE: Install vent at clearances  
specified bythe vent manufacturer.  
CAUTION: When installing a floor  
register, the temperature of the  
discharge air MUST be taken into  
consideration (The discharge air  
temperature maybe high enough to  
cause burns ifnot properlyoperated  
andmaintained.)  
CAUTION: The Blower Motor full  
load AMPS MUST be checked.A  
plenum damper may be required to  
adjust themotor fullloadAMPSto the  
motor nameplate rating.  
Fig. 22  
PF100 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting and Installation  
The shaded areas are the clearances for the PL vent  
pipethat must be maintainedat3”. Afterthe venting leaves  
the shaded area it may be installed at 2” to combustibles.  
(Onlylisted4pellet vent wallpass-throughsand fire stops  
must be used.) See Fig. 23 & 25.  
181/8”  
181/8”  
See NOTES: on  
page 13  
Fig. 25  
The PF100 furnacemaybe used andinstalled into an  
Chimneys tallerthan20above theconnectionwillre- existing masonaryorClassAmetalchimney.  
Fig. 23  
quire a draft test to determineifthe draft istoo high.  
Note: The High Burn Draft should not exceed .85  
IWC. Someformofa restrictorplate maybe requiredat the  
top of high chimneys to reduce the draft. See page 20 for  
the Draft Test procedure.  
Certain Canadian and Local Codes may require that  
the chimney be fully relined. See Fig. 24.  
It Can Not be installed ina chimneyserving another  
appliance.  
The chimneyshould be cleaned andor inspected be-  
foreinstallation.  
Fig. 26  
Fig. 24  
Creosote - Formation and Need for Removal - When wood is burned slowly, it produces tar and other organic vapors,  
which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue  
of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an  
extremely hot fire. The pellet vent pipe should be inspected at least twice monthly during the heating season to determine  
if a creosote buildup has occurred. If creosote has accumulated it should be removed to reduce the risk of a chimney fire.  
Guidance on minimizing creosote formation and the need for periodic creosote removal: The chimney should be  
inspected during the heating season to determine if a creosote build-up has occurred. If a significant layer of creosote has  
accumulated (3mm or more) it should be removed to reduce the risk of a chimney fire.  
14  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Outside Air  
Outside airis optional, althoughit maybe required  
by some building codes. The benefit of outside air is  
higherefficiency andreducedventingrestrictionsmainly  
noticed insmalland verytight houses.  
To installoutsideair, use23/4”"I.D.galvinizedsteel  
flex pipe, part # 2-00-08544 ( 12’ 6” length) or part #  
2-00-08545 ( 25’ length). There is a break-away hole  
on the rear panel which must be removed before con-  
necting the flex pipe. See Fig. 28. The pipe should be  
run outside and terminate 3 feet or more below or 1  
foot or more to the side ofthe vent pipe outlet. Never  
terminate theoutsideair above the vent pipe outlet. The  
maximumlength ofthis pipe is 25 feet. Inlet cover part  
number 1-10-09542 should be used to keep birds, ro-  
dents etc.out ofthe inlet pipe. See Fig. 27.  
Inlet Cover part#  
1-10-09542  
Fig. 27  
Outside Air Pipe Knockout  
NOTE: Ifoutside air is installed, the inlet cover  
should not be placed in an area where drifting ofsnow  
or ice willbuild up, blocking the intake air supply.  
The OutsideAir knockout is located on the face  
of the Feeder Cover. It is pre-cut except for several  
small tabs. There is also a filler plate screwed to the  
inside to cover the top ofthe hole after the Outside Air  
Pipe has been installed. This will allow for removal of  
theFeederCoverwithout disconnectingtheOutsideAir  
Pipe. See Fig. 28.  
Only metal Intake Flex should be used for the  
Outside AirSupplyconnection.  
Fig. 28  
Onlya screened or rodent protected Outside Air  
Intakecovershouldbeusedas anoutsideweathercover.  
The Outside Air Intake Pipe is inside the Feeder  
Cover and to the right ofthe feeder motor. The 2 3/4”  
steelflexpipe ismade toslide over theoutsideoftheAir  
Intake Pipe. See Fig. 29. It should be held into place  
withsomesilicone, foiltape, ora hose clamp. (not sup-  
plied )  
Outside Air Inlet Pipe  
HRV  
Wheninstallingina house witha Heat Reclaiming  
VentilationSystem(HRV)besurethesystemis balanced  
and is not creating a negative pressure in the house.  
Note: Ifthefurnace is installed withthe outside air  
systemno adjustments to the HRVshould be necessary.  
Fig. 29  
PF100 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Wall Control Wiring  
The WallControlsends and receives it’s informa-  
tion fromthe control board through a 4 wire Datacom  
cable. There is a 100’ length ofthis cable supplied with  
the furnace. 100’ lengths of this cable can also be or-  
dered separately, part # 3-20-02583. Or anyDatacom  
cable -CAT 3 - 2 twisted pair 24ga solid wire can be  
acquiredat alocalelectricalsupplyhouse.Also anyCAT  
3- 24ga. solid wire 2, 3, or 4 pair cable can be used  
because theyallhave the samepair color combinations.  
The maximumlengthofwallcontrolwiringis 200 feet.  
The furnace connectingpoint is a 4pole screw ter-  
minal block on the side of the hopper just around the  
corner to the right of the control. Follow the wiring  
instructions on the label alongside the terminal block.  
See Fig. 31.  
70  
65  
60  
75  
80  
LOW  
FUEL  
Fig. 30  
CAUTION: Withthis smallofwire gauge, care  
must be taken not to overtighten the terminal screws,  
thus breakingthe wire.  
There are tie-wrap holes in the face ofthe hopper  
aprox. every6” to keep thecable secure and out ofthe  
way.  
TheWallControlis made to fit ona standard wall  
case electricalbox. It could also be mounted directlyto  
a stud using 2 drywallscrews. In either case the screws  
should be turned in and tested for a snug fit when the  
Wall Control is slid down over the screws. The Wall  
Controlonlyhangs onthe screwsso a good fit is impor-  
tant.  
Fig. 31  
Remove theWallControland make the Datacom  
cable connections with the UY auto splicers provided.  
DONOT STRIPTHE WIRES. Followingthewiring  
diagram on the inside of the Wall Control make each  
splice. SeeFig. 32. Insert the two matching color wires  
fullyinto the two holes ofone ofthe UY connectors. A  
pair of standard Channel-lock pliers works ideally to  
squeeze the raised button downinto the UY connector  
body. Extra UY connectors can be purchased.  
Part # 3-20-00200  
Datacom  
Cable  
Wall Control  
Red  
Orange -  
(+ LED )  
( Tstat )  
Orange/White - White or Black ( - LED)  
Blue - Blue ( Tstat )  
Blue/White - Blue  
NOTE: A pair of needle nose pliers maybe nec-  
essaryto insert theBLUE T-stat wires fullyinto thecon-  
nector. Visually inspect to see that the wires are fully  
inserted before squeezing the UYsplicer.  
Fig. 32  
NOTE: The PF100 furnace Can Not be  
installed with any other brand ortype of wall  
thermostat.  
16  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Duct  
Installing Duct  
The HarmanPF100maybe connected to a gas or  
oil-firedcentralfurnace orheat pumpduct system. Prior  
to installation, determine whether all requirements for  
installationincluding allclearnaces canbe met.  
The PF100 warmair supplyand thecold air return  
must beinstalled ina parallelarrangement. EXAMPLE:  
The warmair supplyduct fromthe PF100 is to be con-  
nected to the warm air supply ofthe existing furnace.  
Also the coldair returnduct fromtheexisting furnace is  
to beconnected to the coldair returnduct ofthePF100.  
Isolationdampers(2)shouldbeinstalledintheductwork.  
(1) in the warmair supplyduct for the existing furnace  
and (1) in the warm air supply duct of the PF100 after  
or “downstream” of the high limit/fan control. These  
dampers can be manuallyoperated or fullyautomatic.  
In either case, the unit that is not being used must be  
prevented frombeing operated. (This also can be done  
manuallyor automatically.)NOTE:Anycontrolwiring,  
power wiring needed should be performed bya quali-  
fied installerand/or electrician.  
Fig. 33  
The warm-airsupplyoutlet ofthe PF100 shallnot  
be connected to the cold-air return inlet ofthe central  
furnace because a possibility exists ofcomponents of  
the centralfurnace overheating and causing the central  
furnace to operateother thanas intended.  
We recommendthat the warmair supplyplenum  
be constructed ofsheet metal.  
PF100 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Duct/Air Conditioning  
Installing Duct  
AddingAirConditioning to the PF100 furnace.  
Recommendations forSupplyAirand ReturnAir  
duct sizing.  
The speed or velocityofair moving through duct  
systems increases as the duct decreases insize with the  
same CFM blower. The sound of air flowing through  
the duct increases as the velocityincreases. Therefore  
the largest size duct practialshould be used.  
The velocityto sound levelmust betakeninto con-  
sideration whenconnecting this furnace into anexisting  
duct sustem.  
As a primary source furnace the duct systemcan  
be installed to fit the customers needs.  
These arerecommended SupplyAir duct sizes (in  
square inches)for the different CFM blowers that may  
be usedwith this furnace.  
An easy rule of thumb for A/C CFM blower size  
is, .75 to 1 CFM for each square foot of conditioned  
space. (std. 8ceiling height )  
The PF100 furnacecanbe fitted withanair condi-  
tioning coilmounted inthe supplyair plenum.  
The Harman Stove Co. is not responsable for  
sizing,duct placement, orinterconnections. Howeverwe  
have made adding A/C to the furnace easier with the  
informationlisted below.  
There is a factory installed junction box readyto  
accept yourA/C relay. TheA/C fancontrolcenter with  
40 va transformer must have a DPDT relay.  
STEVECO # 90-112 - Harman part # 3-20-38056  
Other brands are available at localsupplyhouses.  
The wiring shouldbe done as per Fig. 34. The low  
voltage wiring to the outside condensing unit and the  
cooling thermostat are not shown, see condensing unit  
diagramsforthat information.  
This style relayis used to lock out the feeder sys-  
temofthe furnace whentheA/C unit is callingfor cool-  
ing. This is a fail-safe against bothunitsoperating at the  
same time. See theNOTE inthe lower left corner.  
Velocity  
I.W.C.  
1000CFM  
1500CFM  
2000CFM  
500fpm 700fpm 900fpm Static  
.3 min. to .6 max.  
270sq.in 210sq.in. 160sq.in.  
360sq.in. 290sq.in. 220sq.in.  
470sq.in. 360sq.in. 290sq.in.  
(These duct sizes are onlyrecommendations. )  
TheReturnAirduct systemshouldbe sized aprox.  
10 percent larger for heating onlysystems and 20 per-  
cent larger ifairconditioningis installed.  
CAUTION: Regardless of the supply air duct  
size installed the DistributionBlower MotorMUSTbe  
checked forrunning Amperage. Check themotor name  
plate for thefullload AMPS. Iftheamperage is running  
higher than that listed, a supplyair restricting damper  
maybe required to increase the supplyplenumpositive  
static pressure.  
NOTE:  
It is highly recomended that the  
furnace control be turned to the  
“OFF” position whenever air  
conditioning is being used, whether  
or not it is interconnected.  
Fig.34  
18  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
FAN/HIGH LIMIT CONTROL  
Installation & Set-up  
High limit fan control  
1. The Fan Controlmust be placed in the discharge  
plenumapproximately11 inchesabovethedischargeopen-  
ing ofthe furnace as close to center as possible.  
Note: The best place is on the same side as the ash  
door because of ease of access. See Fig. 35.  
Note: Care must be taken when installing the Fan  
Controlwhenanair conditioning A Coilis used. The Fan  
Controlmust always be installed below the ACoilinlow  
plenuminstallations.  
2. Installthe flex and wiring.  
3. Make sure that the flue venting will not interfere  
withthe flexto the FanControl.  
4. Pry out one ofthe bottomknockouts ofthe Fan  
Control. Installthe 90 degree flex connector as shown in  
Fig. 36. One of the locknuts stays on the outside of the  
box and one goes on the inside to tighten the connector  
into place. This allows for maximum roomfor the wires  
around the switches.  
Fig. 35  
Fan Control  
Setpoint  
5. REMOVE THE COPPER JUMPER BE-  
TWEEN THE LIMIT AND CONTROL  
SWITCHES. (It is not needed.) Figure 36 shownwith  
copper jumper that has alreadybeen removed.  
High Limit  
Setpoint  
6. Connect the two VIOLET wires to the FAN  
CONTROL switch. ( It doesn’t matter which wire is on  
which screw). See Fig. 36.  
CONTROL  
LIMIT  
7. Connect the WHITE and SKY BLUE wires to  
the LIMIT switch. ( It doesn’t matter which wire is on  
which screw). See Fig. 36.  
8. Make sure that allofthe wires are out ofthe way  
whenclosing thecover. ( Excess twistingand pinching of  
the wires could cause a short circuit.)  
9. HIGH LIMIT setupis simple, just rotatethe high  
limit pointerclockwise untilit is against the tamper-proof  
screw. (Never adjust this screw)  
Fig. 36  
Locknuts outside and inside  
NOTE: KEEP THE FAN/LIMIT CONTROL  
INSTRUCTIONS WITH THE OWNERS  
MANUAL FOR FUTURE REFERENCE.  
10. FANCONTROLsetup: Moveboth fan control  
pointerstogetheruntiltheytouch, thenrotatebothpointers  
together until the gap between them is directly over the  
middle 0 of100. See Fig 36.  
Note: This is the best fan controlposition we have  
found during factorytesting. These fancontrollimits can  
NOTE: If fans are used in the fuel storage area,  
they should beinstalled so as notto create negative  
pressures in theroomwhere the solid-fuel-burning  
appliance is located.  
be adjusted if desired.  
PF100 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Installing Electrical Power:  
To installpowerto the furnace first remove the cover  
on the circuit breaker junctionbox shown.  
Inside youwillfind the mainterminalblock.(See wir-  
ing diagramonpage 36 for locationofmain terminalblock  
and proper powerconnections). Inthe bottomofthe boxa  
knockout holeis provided for the incoming wire.  
The minimumrecommended circuit is15 Amp 120  
V.A.C. 60 Hz. This furnace should be the onlyappliance  
onthe circuit.  
This furnace should neverbe poweredby the use  
of an extension cord.  
The recommended high and low voltages are, 130  
V.A.C. 60 Hz maximumhigh voltage, and 113 V.A.C. 60  
Hzminimumlowvoltage.  
The furnace will continue to operate at voltages as  
low as105 V.A.C. , although it can not be guaranteed that  
automatic ignitionwilloccur.Also there isthe possibilityof  
a distributionblower motor overload.  
Fig. 37  
NOTE: If other sources of electrical power are  
to be used ( such as a generator ) for normal opera-  
tion or emergency operation, this source should be  
checked before installation. Many generators and  
inverters may not supply 120V.A.C. 60Hz. power  
stable enough to operate the controlboard properly.  
(Controlboarddamage could occur). Checking& Re-  
cording the Low Draft:  
Draft meter bolt  
After the venting is completed, the firebox low draft  
will need to be checked and possibly adjusted. After re-  
moving the3/8” bolt fromthedraft hole showninFig. 38,  
insert the draft meter tube. The inner ash door and the  
hopper lid must be latched during this test. ( It is recom-  
mended that the draft meter have a scale of0 to 1” WC.)  
Turnthe FurnaceControlto “Test”. thiswillstart the  
combustionblower andallow you to check and record the  
High Draft ______ - IWC date _______ (There is no  
adjustment forthe HighDraft)  
Fig. 38  
Furnace Control  
After the first 60 seconds the “Testmode lowers the  
combustionblowervoltage to theLowBurnvoltage. (The  
“Test” mode cycles the voltage fromhigh to low every60  
seconds).During thisloweredvoltagecycle theLowBurn  
Draft must be checked and adjusted if necessary. The  
recommended low draft setting should be between -.25 &  
-.35IWC. Dependingonthe amount ofverticalrise, it may  
not be possible to get a low draft reading inthis range. In  
this case, a maximumlow draft of-.55 is acceptable.  
The adjustment screwis throughthe smallholeto the  
right of the Igniter Light. See Fig. 39.Adjusted the Low  
Draft to __________ -IWC.  
“Test”  
LowDraft Adjustment Pot  
Fig.39  
Don’t forget to turn the control back to #4.  
20  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Fan Control  
Hopper Lid  
Latches  
Vent Pipe  
Hopper  
Combustion  
blower cover  
Heat Exchanger  
Shaker Handle  
Combustion  
Blower  
3 Speed Switch  
Control Cover  
Outer Door Latches  
Outer Door  
Viewing Glass  
Filter Box  
Fig. 40  
The Control  
The control can be covered as shown above, or  
uncovered asshown at left. There is a pair ofslots pro-  
vided for each position. Simplymove the cover to the  
desired position byplacing the tabs on the cover in the  
proper slots.  
CAUTION: Hot while in operation. Do  
not touch. Keep children, clothing,  
furniture, and other combustible material  
out of the installation clearance area.  
WARNING: Do not operate with fire  
chamber or ash removal doors open.  
WARNING: Do not store fuel or other  
combustible material within installation  
clearance area.  
Fig. 41  
PF100 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Feed adjuster  
Sets the maximum feed rate  
Power Light  
Indicates power to the  
control, and is also used  
during “Test” to check the  
Low Fuel Sensor operation.  
Test  
Runs all motors ** at full speed  
for one minute to check  
operation. After one minute the  
furnace will go to minimum  
burn and the combustion  
blower will alternate from high  
to low every minute to remind  
you that you are still in "Test  
Mode".  
Status Light  
Will be lit in either  
automatic or service mode  
when pointer is not within  
off position band except  
after normal shut down.It  
also blinks to indicate  
errors listed below.  
Lighting Mode Selector  
Switched between Auto and  
Manual lighting  
IGNITOR  
Low Fuel Light  
Indicates that fuel in the  
hopper is low and needs to be  
refilled.  
Combustion Blower Light  
Indicates Power to  
combustion blower  
Mode Selector  
See explanation below.  
Feed Motor LightIndicates  
Power to the feed motor.  
...  
...  
Dealer Diagnostic Port  
For dealer maintenance only.  
Requires special DDM monitor  
supplied to Harman Dealers  
exclusively.  
IgnitEr Light  
Indicates power to the  
ignitor  
Fig. 42  
Temp dial  
The “Temp Dial” should be in the “Normal Setting” position except when  
service work is being done. It also allows you to adjust the fire temperature  
when the “Mode Selector” is in “ Service Mode” using the scale marked  
from 1 to 7.  
Status light error messages:  
1 Blink: Indicates control board self diagnostic failure. This  
requires a manual reset*.  
3 Blinks: Indicates ESP (Exhaust Sensing Probe) failure. This  
requires a manual reset*.  
Mode Selector  
Allows you to choosebetweenAutomatic Mode, ServiceMode  
or OFF.  
4 Blinks: Can occur only in the Automatic Mode and  
indicates the Wall Control has failed or is not installed. If a  
Wall control is then installed thestatus light will automatically  
reset.(Note) only after the unit has warmed up.  
5 Blinks: (In Auto Light Mode Only)  
Automatic Mode  
Automatic mode switches operational control of the furnace  
to the wall mounted control. This is the mode to use whenever  
the furnace is burning in a normal heating application.  
Indicates that the igniter has failed to light the fire after 4  
consecutive 8 minute attempts. To reset - Turn the Mode  
Selector to OFF and then back to Automatic.  
Service Mode  
Service mode switches control of the furnace to the temp  
dial. The temp dial can be set from 1 to 7 to allow a steady  
furnace temperature at the desired level. The main purpose  
of this mode is to operate the furnace without having to go  
back to the wall mounted control.  
6 Blinks : Indicates that the control has calculated poor or  
incomplete combustion occurring for more than 50 minutes.  
A six blink status may be set if the stove is allowed to run out  
of pellets. To reset, turn mode selector to "OFF" then back  
on to the desired mode. If the unit was not out of pellets, see  
Troubleshooting section, Page 35, for more details.  
* Manual reset, disconnect power at the circut breaker for  
a few seconds and reconnect. If error still occurs call your  
Dealer.  
OFF Mode  
Turning the mode selector to OFF will shut down the furnace.  
**TheDistributionBlower is not controlled by theTest”  
operation. The Distribution Blower has it’s own Manual Test  
Switch on the Fan / High Limit Control cover.  
22  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Wall Control  
The wallcontrolacts like a thermostat, however,  
what is actuallygoing onis a thermister in thewallcon-  
trolis sending temperature information back to the mi-  
cro processor on the furnace. This information is used  
to increase or decrease the size ofthe fire according to  
the needs ofthe home.  
70  
Temperature Dial  
65  
60  
75  
80  
Setting The Room Temperature  
To set the roomtemperature, simplyturnthe tem-  
perature dialto the desired setting. The controland the  
furnace will then performto achieve the set tempera-  
ture.  
Note: Theminimumtemperature you canset with  
a full counter-clockwise knob position is 58 degrees.  
The maximumtemperatureyoucanset withafullclock-  
wise knob positionis 90 degrees.  
LOW  
FUEL  
Low Fuel Light  
WallControlcalibration:TheNormalSettingon  
theTemp Dialofthe Furnace Control(See Fig.44) cali-  
brates the WallControl temperature span.Ifthe Temp  
Dial is not pointing to the “NormalSetting”, the tem-  
perature span could varyby3 degrees up or down de-  
pending ontheTemp Dialknob setting.  
Fig. 43  
Low Fuel Sensor  
There is a low fuelsensor in the hopper that tells  
the controlthat the fuellevelin the hopper has dropped  
below the sensor.Whenthishappens, theLowFuellight  
on the WallControl will start to blink.You then know  
that it istime to fillthe hopper with pellets.  
Fig. 44  
Note: Testing the low fuelsensor can be done by  
turning the FEED ADJUSTER knob to “Test”. The  
POWER light willgo offwhen the sensor is uncovered  
and willlight whenthe sensor is covered again.  
Note: The LOWFUEL light ontheFurnace Con-  
trol will light at the same time. Only the LOW FUEL  
light ontheFurnaceControlwillremainlitforthreemin-  
utes after the sensor is covered with pellets. See Note  
below.  
Low Fuel  
Sensor  
Note: The Low Fuel light indicates that there is  
power going to the auxiliaryleads inthe circuit breaker  
junction box. (120 VAC 60 Hz Max. 1Amp.)  
The auxiliary power leads would be used if an  
optional bulk hopper and auger systemwere installed.  
(see wiring diagramon page 36)  
Type of Fuel  
Pelletized wood only. Note:The lower the ash  
content ofthepelletstheless cleaningthat willbe needed  
oftheheat exchangersurfaces. Thecleanerthesesurfaces  
Fig. 45  
are kept, the more efficient the furnace willbe.  
PF100 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Starting A Fire Automatically  
1. Turn Mode Selector to "OFF".  
This resets thecontrolinadditionto turning it off.  
Fig. 46  
2. Fill hopper with pellets.  
When filling the hopper check for excessive fines in  
thebottomofthehopper.Finesaresmallpiecesofbroken  
pellets(sawdust). Finesdo not floweasilyandoftenbuild  
up onthehopper funnelbottomangles. These fines can  
bepushedintothefeederopeningandthenfillthehopper  
with pellets. As the systemworks, theywillbe burned.  
Fig. 47  
3. Clean burnpot with scraper, if necessary.  
This is usuallya weekly maintenance procedure.  
Cleaningtheburnpotwiththescraperwithasmallamount  
ofnew fuelinthe bottomis not a problem. First, scrape  
the ashes on the front ofthe burn pot into the ash pan.  
Then scrape the hole grid surface downward into the  
burnpot. Whenthe stove is ignited these scrapings will  
be pushed out bythe feeder.  
Note: Ifthe DistributionBlower is running when  
the outer door is open, some air willescape around the  
door opening. Thisis not a problem, however, anydust  
that is caused in the process can potentially be blown  
around.  
Fig. 48  
24  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
4. If starting after an empty hopper, turn  
Feed Adjuster to "TEST" (for one 60  
second cycle). This will purge pellets into  
the auger tube and also allow you to check  
the motors for operation. NOTE: The auger  
motor will not operate with the ash door  
open.  
Fig. 49  
5. Turn Feed Adjuster to #4.  
If this is your first fire or you are trying  
different pellets, set the feed adjuster to #4,  
Fig. 50 This is a conservative number and  
will probably need to be increased if maxi-  
mum BTU output is desired. After you know  
a feed rate setting that works well for your  
application, use that setting. Remember, if  
your feed rate is too high you may waste fuel  
due to overshooting the Wall Control setting.  
Fig. 50  
6. Flip the Igniter Switch up into the  
"AUTO-LIGHT" position.  
Fig. 51  
7. Turn the Temperature Dial on the wall  
control to desired room temperature. Note:  
The set temperature on the dial must be higher  
than the room temperature for the fire to light.  
70  
65  
60  
75  
80  
WARNING: HOT WHILE IN OPERATION.  
KEEP CHILDREN, CLOTHING, AND  
FURNITURE AWAY. CONTACT MAY CAUSE  
SKIN BURNS.  
LOW  
FUEL  
Fig. 52  
PF100 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
8. Turn the Temperature Dialon the furnace  
control to “NORMAL SETTING”.  
Fig. 53  
9. Turn Mode Selector to “AUTOMATIC”  
This willstart the lighting process ifthe tempera-  
ture at the wall controlis less than the set temperature  
on the dial.  
The PF100is more thanjust an automatic ignition  
pellet furnace. The automatic systemwillallow the fire  
size to be adjusted to match the heating needs and even  
put the fire out if necessary. If heat is needed after the  
fire is out, the PF100 will automatically re-ignite and  
adjust thefire size to matchthe heating need.  
Fig. 54  
10. Fill hopper with pellets and remove  
ashes as required.  
Type of Fuel  
Use pelletizedwood only.Note:The lower the  
ash content ofthe pellets the less cleaning that will be  
needed oftheheat exchangersurfaces. Thecleanerthese  
surfaces are kept, the more efficient thefurnace willbe.  
NOTE: Do not burn garbage, gasoline, naphtha,  
engine oil, or other inappropriate materials in the  
PF100.  
...  
...  
Temp Dial  
Mode Selector  
This is the Control setting that will allow the Wall  
Control to function.  
Store pelletsinthe manufacturer’swrapping  
until needed to prevent pellets from absorbing  
moisture. Do not store fuel within the appliance  
installationclearances, orwithin thespace required  
for fueling, ash removal, and other routine  
maintenance operations.  
26  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Lighting A Fire Manually  
Lighting the fire manuallywillnot be necessaryunless  
the igniter inthe burnpot fails.  
Follow steps 1 through 5 of the instructions for  
automatic lighting.  
Fig. 55  
6. Flip the Igniter Switch Down into the  
"MANUAL-LIGHT" position. See Fig. 55.  
7. Open inner and outer ash doors as shown  
in figs. 63, 64, 65, on page 30.  
8. Fill burnpot with pellets as shown.  
See Fig. 57. Only fill level with the front  
edge. ( ------- DO NOT OVERFILL ------- )  
Fig. 56  
9. Have matches or other ignition source  
ready.  
10. Apply starting gel as shown in Fig. 58.  
NOTE: Stirring the starting gelinto thepellets usually  
allows the fire to become established quicker.  
CAUTION: A vapor flash could occur if too much  
time is allowedto pass before lightingthe starting gel.  
Fig. 57  
CAUTION:Caremust be takennot toget starting gel  
onyour handsor clothing. Serious burnscould occur during  
thelightingprocess.  
CAUTION:Never tryto applymore startinggelto an  
alreadyburningfire, or a fire withsmoldering pellets.  
"NEVER USE GASOLINE, GASOLINE-TYPE  
LANTERN FUEL, KEROSENE, CHARCOAL  
LIGHTER FLUID, OR SIMILAR LIQUIDS TO  
START OR "FRESHEN UP"AFIRE IN THIS FUR-  
NACE. KEEP ALL SUCH LIQUIDS WELL AWAY  
FROM THE FURNACE WHILE IN USE".  
Fig. 58  
PF100 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
11. Turn Mode Selector to “SERVICE”  
Thiswillstart thecombustionblowerand allow the  
ESPto controlthe fire inrelation to the TempDialset-  
ting 1 through 7. Once the fire is well established the  
Temp Dialcanremainonanynumber setting desired,or  
changed to the “AUTOMATIC”setting. Ifyou change  
to “AUTOMATICremember to set theTemp Dialto  
“ NormalSetting“ for proper WallControlcalibration.  
NOTE: When theSwitchis setto Manual-Lite in  
the “AUTOMATIC” mode, the WallControlwillfunc-  
tionasinAuto-Lite except thefire willnot beallowedto  
go out. It willonlybe allowed to go to a minimumburn  
rate between the times the Wall Control is calling for  
heat.This rate is about 1 pound offuelper hour.  
Fig. 59  
12. Light The Starting Gel With A Match.  
13. Close The Doors  
The fire willlight and the PF100 willadjust the fire  
to properlevelaccording to thetemperature dialsetting  
onthewallcontrol.  
14. Return air filter  
Check the condition of the return air filter  
periodicallyand replace as needed.  
Solid-fuelburning appliances need to be cleaned  
frequently because soot, creosote, and ash mayaccu-  
mulate. Ifyou suspect a chimney/vent pipe fire 1) Call  
the fire department. 2) Remove fuelfromthe burn pot  
usingthe burnpot scraping toolto scrapethe pelletsinto  
the ash pan. 3) Remove the ash pan from the unit and  
take outside. Do not place ash pan on a combustible  
material. 4) Turnoff circuit breaker at unit. 5) Do not  
use the unit untila qualified personhas inspected your  
appliance and venting.  
28  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Burnpot cleaning:  
The burnpot shouldbe cleaned no lessthanonce a  
week. Forbest operationthe burnpot should be cleaned  
everytime thehopper is filled withpellets. The fire does  
not have to be out to scrape the burnpot although it is  
recomended the furnacebeonminimumburnat the time  
ofcleaning.  
Note: The furnace can easily be turned to mini-  
mumburnregardless ofpresent operation. Simply turn  
the Mode Selector to SERVICE. Thenturn the Temp  
Dialto the #1 setting. Ifthis is done before starting to  
refillthehopperthefurnacewillnot beashotwhenscrap-  
ingtheburnpot. Whentheburnpot cleaningiscompleted  
don’t forget to turnthe controlback to theWallControl  
positions. See Fig. 61.  
Use the flat end ofthe scraper provided to scrape  
down over the holed surface ofthe burnpot grate. See  
Fig. 62. It is not necessary to clean out the scrapings  
fromthis cleaning because theywill be pushed out the  
next timethe auger operates.  
Note: Make a specialeffort to scrape the bottom  
inside corners ofthe burnpot where the auger tube en-  
ters theburnpot.Carbondepositscanbuildup over time  
in this area that may cause a restriction to the flow of  
pellets into the burnpot.  
Fines cleanout cover  
Fig. 60  
Note: Anold long shank screwdriver withthe end  
sharpenedisanidealaidintheremovalofthesedeposits.  
Cleaning the burnpot air chamber:  
This area onlyneeds to be cleaned twice a heating  
season, unlessexcessive buildup isnoticedduringsched-  
uled cleanings.  
There isa cover onthefront ofthe burnpot to gain  
access to the air chamber and igniter. The cover is held  
into place by two thumb screws. Loosen the thumb  
screwsand removethecover. SeeFig. 60.Theaircham-  
ber canbe cleaned ofanyashthat has fallenthrough the  
holes during operation and cleaning. Also at this time,  
remove thefeeder assemblycover andremove anyfines  
that mayhave accumulated.  
Possible pellet fines build up area.  
Fig. 61  
Scrape burnpot  
to remove any  
carbon build-up  
that may have  
occured.  
NOTE:ALWAYS REMEMBER TO CLOSE  
THE CLEANOUTCOVERAFTER CLEANING.  
Feeder Chamber (Fig. 61):  
This chamber mayget a buildup offinesfromthe feeder  
mechanismmovement. Thisareashould becheckedand  
cleaned at least once a year.  
To remove the feeder cover:  
• Remove the 5/16" wing nut.  
• Slide the cover off ofthe threaded stud.  
• Inspect and clean the inner chamber ifnecessary. See  
Fig. 61.  
• Reinstallthecover making certain it iscentered onthe  
feeder bodyand tighten as tightlyas you can byhand.  
Scraping can be done while in  
operation.  
Fig. 62  
PF100 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Ash Removal  
It is recommended to remove the ashes when the  
furnace is not in operation. This lessens the chances of  
coming in contact with hot surfaces. Ashes can be re-  
moved while inoperationbut, extra caremust be taken.  
Open Outer Ash Door  
Lift the two latches shown in figure 63 and open  
the outer dooras showninfigure 64. Ifthe Distribution  
Bloweris runningwhenthe outer door isopen, someair  
willescape aroundthe dooropening. This isnot a prob-  
lem, however anydust that is caused inthe ashremoval  
process can potentiallybe blown around.  
Outer Door  
Latches  
Fig. 63  
Open Inner Ash Door  
Lift latches shownin figure 64 and open the inner  
door as shownin figure 65.  
NOTE: Keep hopper lid and ash pan doors closed  
during operation and maintain all seals in good  
condition.  
Remove Ash Pan  
Always wear gloves to remove ashpan. Grab the  
ashpanbythe handle and pullit out ofthe furnace. Lift  
the handle and use it for carrying the ashpan.Close the  
inner door before disposing of the ashes.  
Inner Door Latches  
Disposal of Ashes  
Fig. 64  
Ashesshouldbeplaced inametalcontainerwith  
atight fittinglid. Theclosedcontainerofashesshouldbe  
placed on a non-combustible floor or on the ground,  
wellawayfromallcombustible materials, pending final  
disposal. If ashes are disposed of by burial in soil or  
otherwise locallydispersed, theyshould be retained in  
the closed container until all cinders have thoroughly  
cooled.  
Soot and Flyash: Formation and Need for  
Removal  
The products ofcombustion willcontain small  
particles offlyash. The flyashwillcollect in the exhaust  
venting system and restrict the flow ofthe flue gases.  
Incomplete combustion, suchas occurs during startup,  
shutdown, orincorrect operationoftheroomheater will  
lead to some soot formation which will collect in the  
exhaust venting system. The exhaust venting system  
should beinspected at least twicemonthlyto determine  
ifcleaningis necessary.  
Fig. 65  
30  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Cleaning the accordion heat exchanger/firebox:  
This cleaning shouldbe done after eachtonofpel-  
lets used. The frequencyofthis cleaningwillbe directly  
related to the quality and the ash content ofthe pellets  
being used. Keep in mind that the cleaner the heat ex-  
changer surface is kept, the higher theheat transfer effi-  
ciencywillbe.  
Upper Baffle  
Due to it’s ease of restarting it is recommended  
that the furnace be OFFand COOLbefore cleaning.  
Before starting to clean the inside of the firebox  
area it isrecomendedthat allofthebaffling beremoved.  
Start with the upper heat exchanger baffle. See Fig. 66.  
Pushstraight upwardonthe lowerashslide angleaprox.  
1/2”. This will release the baffle from the positioning  
brackets and allow it to be tilted toward the burnpot  
and removed fromthe furnace.  
Fig. 66  
Ash slide angle  
Note: Observe the positioning tabs and bracket  
system on the rear of the upper baffle as it is being  
removed, for easier replacement later.  
Remove the lower baffle plate. This baffle is a flat  
plate that sits on the furnace floor. Tip the top edge to-  
ward theburnpot andlift upand out ofthefurnace. Note  
how the bafflebottomedgesits behindtheashpanguide  
and against the heat exchanger. See Fig. 67.  
Lower  
Baffle  
Plate  
Fig. 67  
Ash Pan Guide  
With allofthe baffling removed, the entire firebox  
area and the accordion heat exchanger can be cleaned.  
Use the pointed end ofthe scraper suppliedto clean the  
accordion heat exchanger. A small wisp brush, wire  
brush, or anold stiffbristled paint brushworks best for  
cleaning the firebox walls. All of the fly ash removed  
duringcleaningwillfalltothebottomofthefurnacewhere  
there is an unobstructed access for cleaning. Even the  
bottom ends of the chains can be seen and accessed  
easilyfromthe door opening. See Fig. 68.  
CAUTION: Cleanout of the heat exchanger, flue  
pipe, chimney, andcombustion blowerfan housing,  
is especially important at the end of the heating  
season to minimize corrosion during the summer  
Fig. 68 months, caused by accumulated ash.  
Shaker Chain Ends  
PF100 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Combustion Blower Cleaning  
Remove the combustionblower heat shield.There  
are two latches that hold the shield inplace . See Fig. 69  
Flip the latches up and pull the shield away from the  
furnace. Itcannot befullyremoved, it canonlybemoved  
downover the wire untilit hangs onthe junctionbox.  
The furnace MUST be OFF and COOLbefore  
you shouldattempt to clean the combustion blower.  
The wire to the combustion blower doesn’t need  
to be disconnectedduring the cleaning process.  
Latch  
Loosen the three (3) thumb screws about 4 turns  
each. See Fig. 70. Hold the motor head with one hand  
and the blower plate handle with the other hand. Pull  
outwardontheplatehandleuntilthecompleteunit comes  
loose. Now rotate the plate counter-clockwise about  
1/8 turn. This will allow the complete assembly to be  
removed fromthe blower chamber.  
Fig. 69  
Clean the blower fan blades and the blower plate  
sealing overlap. See Fig. 71.  
Thumb Screws  
Note: Be carefullnot to bend the fan blades, this  
willthrow the fanblade out ofbalance or it mayrub the  
inner chamber, whichmayaffect theperformance ofthe  
furnace. Anyhorizontal and verticalflue pipe directly  
above the unit should be cleaned at this time.  
Note: The horizontalflue pipe directlyabove the  
furnace is the first place fly ash will settle, due to the  
slowing of flue gas velocity through horizontal pipe.  
Cleaning ofhorizontalventingpipes isveryimportant to  
the efficiencyofthis furnace.  
Fig. 70  
Sealing Overlap  
Fig. 71  
32  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Clean the flue outlet throat ( this is the hole that  
goes up into the flue pipe). See Fig. 72.  
Note: The ESP probe sensing tip extends into  
this same area. CARE MUSTBE TAKEN NOTTO  
DAMAGE THE ESP PROBEDURING CLEAN-  
ING. Bending ofthe ESP probe willmake it difficult to  
remove ifit should become necessary. See Fig. 72.  
ESP Probe  
Sealing overlap  
Cleantheinnerchamber oftheblower.SeeFig72.  
Clean the furnace blower plate, sealing overlap.  
See Fig 72. Inspect the tops oftheheat exchanger tubes  
wherethechainshakermechanismislocated. Makesure  
there are no fly ash buildups that may block the easy  
flowoffluegassesinto thecombustionblowerinlet hole.  
(Aflashlight may be necessary. )  
Fig.72  
Access to flue outlet throat  
Inspect the chain shaker mechanism for proper  
operation.  
Note: Flyash canbuild up to the top edges ofthe  
heat exchanger tubes without affecting operation. The  
chain shaker willcause anyexcess to falldown into the  
chamber under the tubes where it can be cleaned out  
throughthe fire box. See Fig. 73.  
CAUTION: Inspect flue pipes, flue pipe joints and  
flue pipe seals regularly to ensure that smoke and  
flue gases are not drawn into, and circulated by,  
the air-circulation system.  
Cleaning the Tube heat exchangers:  
The heatexchangerstubeshave anexternal handle  
that operatesthe cleaning mechanism. SeeFig. 74.  
This cleaning shouldbe done at least once a week,  
althoughit canbe done as oftenasdesired. The cleaner  
the heat exchangers are, the more efficient the furnace  
willbe. This cleaning canbe done at anytimeand inany  
mode ofoperation.  
Lower cleanout chamber  
Fig. 73  
Shaker  
handle  
Thehandlehastwo directions ofmovement, Right  
to Left and Inand Out.Allinside surfaces ofthese rect-  
angular tubes canbe cleaned with thisrange ofmotion.  
First, withthe handle pushed in, turnthe handle right to  
left, the full sweep, several strokes. Second, with the  
handlepointingstraight down, pullout and pushinward  
several strokes. Third, with the handle allthe wayout,  
turnthe handleright to left, the fullsweep, severaltimes.  
End withthe handle pushed inwardand pointing down.  
PF100 33  
Fig. 74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
FEEDER DOES NOT FEED  
1. No pellets in hopper.  
SMOKE IS VISIBLE COMING OUT OF VENT  
1. Air-fuel ratio is too rich.  
2. Firebox draft may be too low for low draft  
pressure switch in feeder circuit to operate.  
Check for closed doors, loose or missing  
gasket on doors or hopper lid, or a faulty pres-  
sure switch.  
3. Feed motor will not run until ESP  
senses 165 deg. F. Maybe you did not put  
enough pellets in the burn pot before lighting the  
fire manually.  
A. Feed rate too high.  
B. Draft too low caused by a gasket leak.  
LOW HEAT OUTPUT  
1. Feed rate too low  
2. Draft too low because of gasket leak.  
3. Poor quality or damp pellets  
4. Combination of 1 and 2.  
4. Something is restricting flow in the hopper or  
causing the slide plate to stick.  
Helpful Hints  
Cleaning Burn Pot  
Whenever your stove is not burning, take the  
opportunity to scrape the burn pot to remove  
carbon buildup. Avacuum cleaner is handy to  
remove the residue. Be sure the stove is cold if  
you use a vacuum.  
5. Feed motor has failed.  
PARTIALLY BURNED PELLETS  
1. Feed rate too high.  
2. Draft too low. (Check burn pot clean-out slide  
and door gasket).  
3. Burn pot or heat exchanger tubes may need  
to be cleaned.  
4. Combination of all the above.  
Carbon buildup can be scraped loose with  
the fire burning using the special tool provided  
with your stove. Scrape the floor and sides of the  
burn pot. The carbon will be pushed out by the  
incoming fuel. Always wear gloves to do this.  
5. #6 status blink:A 6 blink control board status  
indication is caused by poor or incomplete  
combustion. TheAutomatic Ignition circuit board  
has the ability to track the combustion through  
feed settings and ESP temperatures. When the  
control board has calculated poor or incomplete  
combustion, it will shut down the unit as a safety  
feature. (Poor or incomplete combustion is a  
contributer of creosote which may cause a  
chimney fire)  
A 6 blink status may be caused by several things:  
1. Blocked or partially blocked flue.  
2. Blocked or partially blocked inlet air.  
a. Backdraft damper on the inlet pipe may be  
stuck closed.  
Removing Ashes  
Turn the Temp Dial to number 1 approxi-  
mately 30 minutes before removing ashes. This  
will result in a cooler stove and ash pan.  
Maximum FeedAdjuster settings are not  
needed in most cases. Operating in the normal  
range (#4) is recommended when maximum heat  
output is not required. The ESP probe prevents  
the stove from being over-fired.  
Keep the stove free of dust and dirt.  
b. If outside air is installed, the inlet cover may  
be blocked.  
3. The air chamber under the burnpot may be  
filled with fines and small bits of ash.  
4. The holes in the burnpot may be getting filled  
with ash or carbon buildup.  
Fuel  
Pellet fuels are put into 3 categories in terms  
of ash content. Premium at 1% or less, Standard  
at 3% or less and all others at 3% or more.  
The P68 is capable of burning all 3 categories  
of pellets due to a patented feeder and burn pot  
system.  
It should be noted, however, that higher ash  
content will require more frequent ash removal,  
scraping of the burn pot, and may provide less  
BTU's per pound. Normally, standard and high ash  
pellets cost less than premium pellets and can be  
cost effective when burned in the P68.  
The moisture content must not exceed 8%.  
Higher moisture will rob BTU's and may not burn  
properly.  
5. Combustion blower fan blades may need  
cleaned.  
6. There is no fuel in the hopper.  
SMOKE SMELL  
Seal the vent pipe joints and connection to stove  
with silicone.  
FIRE HAS GONE OUT  
1. No pellets in hopper.  
2. Draft setting is too low.  
3. Something is restricting fuel flow.  
4. Feed motor or combustion blower has failed.  
5. Power failure or blown fuse.  
34  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Feeder Parts  
PF100 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
36  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagram  
Wiring Diagram  
PF100 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts List  
Rubber Grommet (7.5’) Hopper lid gasket 0-88-00248  
IgniterElementAssembly  
Burn Pot Weldment  
ExchangerBaffle-Top  
ExchangerBaffle-Bottom  
Arrow Scraper  
Flame Guide  
Flame Guide Insulator  
Thermister Probe  
1-10-06620  
1-10-73403  
2-00-73418  
2-00-73314  
2-00-773850  
3-00-08534  
3-44-35263  
3-20-00744  
3-20-08101  
3-20-03100  
3-20-9301  
Thermostat  
Circuit Board G4941  
DifferentialSwitch  
5” Single FanBlade (standard )  
1000 CFM Distribution Blower Motor  
1000 CFM DistributionBlower Complete  
Black ControlKnobs (2)  
3-20-40985  
3-20-36648  
1-10-01007  
3-31-00534  
White/Black ControlKnob  
ControlKnob Shaft  
12 X 6 X 1.25 Firebrick  
Glass WithGasket  
Ash Pan  
BurnPot Gasket  
WiringDiagram  
Owners Manual  
Hopper Lid Label  
Chain Shaker Gasket  
3-31-00968  
3-31-00982  
3-40-86125  
1-10-5555  
1-10-73351  
3-44-00409  
3-90-73370  
3-90-08101  
3-90-08415  
3-44-08100  
Low FuelSensor  
CombustionBlower  
4-20-03835  
3-21-08639  
2-00-00539  
3-20-04947  
3-20-334110  
3-20-04946  
3-20-70020  
3-40-20201  
3-20-03018  
3-20-04948  
3-20-23139  
3-20-02583  
InnerAshDoor Gasket  
Circuit Breaker Harness  
10Amp Circuit Breaker  
4 PoleThermostat Extension  
3 Speed Switch  
20 X 20 X 1Air filter  
3 PositionTerminalBlock  
JunctionBoxHarness  
FanLimit  
2 Pair Twisted Cat 3 Cable (100’)  
Options:  
5” Double Fan Blade ( high altitude )  
1500 CFM Blower  
2000 CFM Blower  
OutsideAirAssembly  
12-1/2’ FlexPipe 2-3/4” ID  
25’ Flex Pipe 2-3/4” ID  
3-20-502221  
1-00-00682  
3-21-52092  
1-10-09542  
2-00-08544  
2-00-08545  
38  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
HARMAN CENTRALHEAT WARRANTY  
5 YEAR LIMITED WARRANTY (Residential)  
1YEAR LIMITED WARRANTY(Commercial)  
Harman Stove Company warrants its central heat products to be free from defects in material or workmanship, in normal use and  
service, for a period of 5 years from the date of sales invoice and for mechanical and electrical failures, in normal use and service,  
for a period of 1 year from the date of sales invoice.  
If defective in material or workmanship, during the warranty period, Harman Stove Company will, at its option, repair or replace  
the product as described below.  
The warranty above constitutes the entire warranty with respect to Harman Stove Company. HARMAN STOVE COMPANY  
MAKESNO OTHERWARRANTY, EXPRESSED OR IMPLIED, INCLUDING “ANYWARRANTYOFMERCHANTABILITY,  
OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. No employee, agent, dealer, or other person is authorized to  
give any warranty on behalf of Harman Stove Company. This warranty does not apply if the product has been altered in any way  
after leaving the factory. Harman Stove Company and its agents assume no liability for “resultant damages of any kind” arising  
from the use of its products. In addition, the manufacturer and its warranty administrator shall be held free and harmless from  
liability from damage to property related to the operation, proper or improper, of the equipment.  
THEREARE NO WARRANTIES, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.  
THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the operators manual.  
THESE WARRANTIES WILL NOT APPLY if abuse, accident, improper installation, negligence, or use beyond rated capacity  
causes damage.  
HOW TO MAKE A CLAIM - any claim under this warranty should be made to the dealer from whom this appliance was  
purchased. Then contact is made with manufacturer, giving the model and serial numbers, the date of purchase, your dealer’s  
name and address, plus a simple explanation of the nature of the defect. Extra costs such as labor, mileage and overtime are not  
covered. Nuisance calls are not covered by these warranties.  
THISWARRANtYISLIMITEDTODEFECTIVEPARTS, REPAIRAND/ORREPLACEMENTATHARMANSTOVECOMPANY’S  
OPTIONAND EXCLUDESANYINCIDENTALAND CONSEQUENTIALDAMAGESCONNECTEDTHEREWITH.  
WARRANTY EXCLUSIONS: Failure due, but not limited to, fire, lightning, acts of god, power failures and/or surges, rust,  
corrosion and venting problems are not covered. Damage and/or repairs including but not limited to; filters, fuses, knobs, glass,  
door packing, paint, batteries or battery backup and related duct work are not covered. Also excluded from this warranty are  
consumable or normal wear items including but not limited to; grates, fire brick, gaskets. Additional or unusual utility bills incurred  
due to any malfunction or defect in equipment and the labor cost of gaining access to or removal of a unit that requires special  
tools or equipment are not covered. Maintenance needed to keep the stove in “good operating condition” is not covered. This  
includes, but is not limited to, cleaning, adjustment of customer controls and customer education. Labor, material, expenses and/  
or equipment needed to comply with law and/or regulations set forth by any governmental agencies are not covered.  
This warranty provides specific legal rights and the consumer may have other rights that vary from state to state.  
PLEASEREADLITERATURE BYTHEMANUFACTURERFORTHEVARIOUSACCESSORYDEVICES.THEMANUFACTURER  
WARRANTSTHESEACCESSORYDEVICES,NOTHARMAN STOVECOMPANYORTHEIRWARRANTYADMINISTRATOR.  
FURTHERMORE, THESE ACCESSORY DEVICES MUST BE INSTALLED AND USED ACCORDING TO THE  
RECOMMENDATIONSOFTHE MANUFACTURER.  
Remedies - The remedies set forth herein are exclusive and the liability of seller with respect to any contract or sale or anything  
done in connection therewith, whether in contract, in tort, under any warranty, or otherwise, shall not, except as herein expressly  
provided, exceed the price of the equipment or part of which such liability is based.  
CLARIFY - The above represents the complete warranty, which is given in connection with central heat, manufactured by  
Harman Stove Company. No other commitments, verbal or otherwise, shall apply except by a written addendum to this warranty.  
PF100 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Testing Label  
40  
PF100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Baby Swing 1761304 User Manual
Graco Marine Sanitation System 308550ZAD User Manual
Grizzly Saw G0668 User Manual
Grundig CRT Television Elegance 37 LXW 94 8616 Dolby User Manual
Harman Photo Printer MATT FB MP User Manual
Havis Shields Automobile Accessories KK C VAK User Manual
Hearth and Home Technologies Stove TIARA II User Manual
Hotpoint Clothes Dryer NVLR333 User Manual
Huey Chiao Bluetooth Headset HCB19 User Manual
Hypertec Carrying Case TSV12WFV2HY User Manual