SERVICE MANUAL R410A
MODEL : ARNU Series
URNU Series
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Download from Www.Somanuals.com. All Manuals Search And Download.
Part 1
General Information
1. Model Names .............................................4
2. External Appearance .................................5
3. Nomenclature .............................................6
- 3 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Model Names
1. Model Names
Capacity(Btu/h(kW))
18k 24k 28k 36k
(5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28)
Category
Chassis
Name
7k
9k
12k
15k
42k
48k
76k 96k
(2.2) (2.8) (3.6) (4.5)
ARNU07 ARNU09 ARNU12 ARNU15
SE
S5
SE
Wall Mounted
(General)
GSE*2
GSE*2
GSE*2
GSE*2
ARNU18G ARNU24G
S5*2
S5*2
ARNU07 ARNU09 ARNU12 ARNU15
GSE*2 GSE*2 GSE*2 GSE*2
Mirror
ARNU18 ARNU24
GS3*2 GS3*2
ART COOL
S3
SF
TJ
ART Cool
Gallery
ARNU07 ARNU09 ARNU12
GSF*2 GSF*2 GSF*2
ARNU07 ARNU09 ARNU12
GTJ*2 GTJ*2 GTJ*2
1 Way
2 Way
ARNU18 ARNU24
TL
GTL*2
ARNU07 ARNU09 ARNU12 ARNU15 ARNU18
GTE*2 GTE*2 GTE*2 GTE*2 GTE*2
GTL*2
TE
TP
TN
TM
BH
BG
BR
B8
B1
Ceiling
ARNU24G ARNU28G
TP*2
Cassette
TP*2
4 Way
ARNU36
GTN*2
ARNU42G ARNU48G
TM*2
TM*2
ARNU07 ARNU09 ARNU12 ARNU15 ARNU18 ARNU24
GBHA2 GBHA2 GBHA2 GBHA2 GBHA2 GBHA2
ARNU28 ARNU36 ARNU42
GBGA2 GBGA2 GBGA2
High
ARNU48
GBRA2
Static
URNU76 URNU96
GB8A2 GB8A2
Ceiling
Concealed
Duct
ARNU07 ARNU09 ARNU12 ARNU15
GB1G2 GB1G2 GB1G2 GB1G2
Low Static
Built In
ARNU18 ARNU24
GB2G2 GB2G2
B2
B3
ARNU07 ARNU09 ARNU12 ARNU15
GB3G2 GB3G2 GB3G2 GB3G2
B4
ARNU18 ARNU24
GB4G2 GB4G2
ARNU09G ARNU12G
VEA2 VEA2
Ceiling & Floor
VE
VJ
ARNU18 ARNU24
GVJA2 GVJA2
Ceiling Suspended
ARNU07 ARNU09 ARNU12 ARNU15
GCEA2 GCEA2 GCEA2 GCEA2
CE
CF
With Case
ARNU18 ARNU24
GCFA2 GCFA2
Floor
ARNU07 ARNU09 ARNU12 ARNU15
GCEU2 GCEU2 GCEU2 GCEU2
Standing
CE
CF
Without
Case
ARNU18 ARNU24
GCFU2 GCFU2
❈ *ART COOL- B: Blue, M:Metal, D:Wood, R:Mirror, W:White Wood, V:Silver, E:Red, G:Gold, 1: Kiss (Photo changeable)
*Wall Mounted- A: Basic, L:Plasma
*Ceiling Cassette- A: Basic, C:Plasma
- 4 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
External Appearance
2. External Appearance
Ceiling Cassette- 1Way
ARNU07GTJ*2
ARNU09GTJ*2
ARNU12GTJ*2
Ceiling Cassette -2Way
ARNU18GTL*2
ARNU24GTL*2
* A:Basic, C:Plasma
* A:Basic, C:Plasma
Ceiling Cassette- 4Way
Ceiling Concealed Duct - High Static
ARNU07GTE*2
ARNU09GTE*2
ARNU12GTE*2
ARNU15GTE*2
ARNU18GTE*2
ARNU24GTP*2
ARNU28GTP*2
ARNU36GTN*2
ARNU42GTM*2
ARNU48GTM*2
ARNU07GBHA2
ARNU09GBHA2
ARNU12GBHA2
ARNU15GBHA2
ARNU18GBHA2
ARNU24GBHA2
ARNU28GBGA2
ARNU36GBGA2
ARNU42GBGA2
ARNU48GBRA2
URNU76GB8A2
URNU96GB8A2
* A:Basic, C:Plasma
Ceiling Concealed Duct - Low Static
ARNU07GB1G2 ARNU15GB1G2
ARNU09GB1G2 ARNU18GB2G2
ARNU12GB1G2 ARNU24GB2G2
Wall Mounted
ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2
ARNU18GS5*2
ARNU24GS5*2
* A:Basic, L:Plasma
ART COOL Gallery
Ceiling Concealed Duct – Built-in
ARNU07GSF*2
ARNU09GSF*2
ARNU12GSF*2
ARNU07GB3G2
ARNU09GB3G2
ARNU12GB3G2
ARNU15GB3G2
ARNU18GB4G2
ARNU24GB4G2
* E:Red V:Silver
G:Gold 1: Kiss (Photo changeable)
ART COOL Mirror
Floor Standing
With case
S3: * B : Blue SE: * R:Mirror
ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2
ARNU18GS3*2
ARNU24GS3*2
M : Metal
D : Wood
R : Mirror
W : White Wood
V:Silver
B : Blue
ARNU07GCEA2
ARNU09GCEA2
ARNU12GCEA2
ARNU15GCEA2
ARNU18GCFA2
ARNU24GCFA2
Ceiling & Floor
ARNU09GVEA2
ARNU12GVEA2
Without case
ARNU07GCEU2
ARNU09GCEU2
ARNU12GCEU2
ARNU15GCEU2
ARNU18GCFU2
ARNU24GCFU2
Ceiling Suspended
ARNU18GVJA2
ARNU24GVJA2
- 5 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Nomenclature
3. Nomenclature
ARN
U
07
G
TJ
A
2
Serial Number
Combinations of functions
A:Basic function
L:Neo Plasma(Wall Mounted)
C:Plasma(Ceiling Cassette)
G: Low Static
ART COOL Type Panel Color
B:Blue D:Wood M:Metal R:Mirror W:White Wood
V: Silver E:Red G:Gold 1: Kiss (Photo changeable)
Chassis Name
Electrical Ratings
1:1Ø, 115V, 60Hz
2: 1Ø, 220V, 60Hz
6:1Ø, 220 ~ 240V, 50Hz 7: 1Ø, 100V, 50/60Hz
G:1Ø, 220 ~ 240V, 50Hz / 220V 60Hz
Total Cooling Capacity in Btu/h
EX) 5,000 Btu/h©'05' 18,000 Btu/h©'18'
Combination of Inverter Type and
Cooling Only or Heat Pump
N: AC Inverter and H/P V: AC Inverter and C/O
U: DC Inverter and H/P and C/O
System with
Indoor Unit using R410A
❈ LGETA:U Ex) URN
- 6 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Part 2
Indoor Units
Ceiling Cassette
1 Way.................................................................................8
2 Way...............................................................................13
4 Way(1)...........................................................................20
4 Way(2)...........................................................................23
Art Cool Series
ART COOL Miror .............................................................30
ART COOL Gallery ..........................................................41
Ceiling Concealed Duct
Low Static ........................................................................51
Built In..............................................................................57
High Static........................................................................63
Wall Mounted(General)
Wall Mounted ...................................................................72
Ceiling & Floor
Ceiling & Floor
Ceiling Suspended...........................................................83
Floor Standing
Floor Standing..................................................................90
- 7 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Ceiling Mounted Cassette Type (1Way)
1. Functions ......................................................................................9
2. Operation Details........................................................................10
3. Dimensions .................................................................................12
- 8 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Specification
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• Jet, High, Med, Low, Lolow
• Intermittent operation of fan at low speed.
• The louver can be set at swing up and down automatically.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
• The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.
Hot-start Control (Heating)
Compact and light design
• To install a unit is very convenient because of smaller
size than textile.
• The most advanced low-noise design.
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
Low noise
• Long life wrinkle(type) and washable and anti-bacteria
filter is adopted.
Long life filter
• Built-in drain pump automatically drains water.
• A standard drain-head height of up to 700mm is possible.
High head Drain pump
High-Ceiling corresponding Function
• According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
•
It is operating individually or totally by central control function.
Central Control(Optional)
- 9 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Detail
2. Operation Detail
(1) The function of main control
I Auto Swing Control
• This function is to swing the louver up and down automatically.
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
Intake Air Temperature
Thermo. ON
(SET TEMPERATURE +0.5°C)
Thermo. OFF
(SET TEMPERATURE -0.5°C)
More than
3 minutes
More than
3 minutes
Selected
Speed
Selected
Speed
Selected
Speed
INDOOR FAN
Low
Low
Thermal ON
ST+0.5
Thermal OFF
ST-0.5
Indoor Unit mode
To be selected higher temperature
contrast Indoor Unit and Remo.
ST+0.5
To be selected higher temperature
contrast Indoor Unit and Remo.
ST-0.5
2TH (Remo.+Indoor)
Remo. Mode
- 10 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Detail
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor pipe
Temperature
36(42)°C
33(39)°C
25°C
22(20)°C
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Indoor fan
4 Way
Stop Low Low
Low
Low Stop Stop Low
ON
Thermal ON
ST+2
Thermal OFF
ST+4
Indoor Unit mode
2TH
(Remo.+Indoor)
To be selected lower temperature
contrast Indoor Unit and Remo.
To be selected lower temperature
contrast Indoor Unit and Remo.
Remo. mode
ST+0
ST+2
I Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.
Pipe
temperature
35 °C
30 °C
27 °C
25 °C
22 °C
LO
LOW
Indoor fan
SELECTED
LOW
OFF
LOW
LOLOW
FAN
speed
COMP
ON
- 11 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
5 6
1 0 0
1 5 1
1 7 3
2 4 2 . 5
16.4
110
3 4 4 . 4
4 1 0
4 8 0
- 12 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Ceiling Mounted Cassette Type (2Way)
1. Functions ....................................................................................14
2. Operation Details........................................................................15
3. Dimensions .................................................................................17
- 13 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• Jet, High, Med, Low, Lolow
• Intermittent operation of fan at low speed.
• The louver can be set at swing up and down automatically.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
• The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.
Hot-start Control (Heating)
Compact and light design
• To install a unit is very convenient because of smaller
size than textile.
• The most advanced low-noise design.
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
Low noise
• Long life wrinkle(type) and washable and anti-bacteria
filter is adopted.
Long life filter
• Built-in drain pump automatically drains water.
• A standard drain-head height of up to 700mm is possible.
High head Drain pump
High-Ceiling corresponding Function
• According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
•
It is operating individually or totally by central control function.
Central Control(Optional)
- 14 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Detail
2. Operation Detail
(1) The function of main control
I Auto Swing Control
• This function is to swing the louver up and down automatically.
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
Intake Air Temperature
Thermo. ON
(SET TEMPERATURE +0.5°C)
Thermo. OFF
(SET TEMPERATURE -0.5°C)
More than
3 minutes
More than
3 minutes
Selected
Speed
Selected
Speed
Selected
Speed
INDOOR FAN
Low
Low
Thermal ON
ST+0.5
Thermal OFF
ST-0.5
Indoor Unit mode
To be selected higher temperature
contrast Indoor Unit and Remo.
ST+0.5
To be selected higher temperature
contrast Indoor Unit and Remo.
ST-0.5
2TH (Remo.+Indoor)
Remo. Mode
- 15 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Detail
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor pipe
Temperature
36(42)°C
33(39)°C
25°C
22(20)°C
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Indoor fan
4 Way
Stop Low Low
Low
Low Stop Stop Low
ON
Thermal ON
ST+2
Thermal OFF
ST+4
Indoor Unit mode
2TH
(Remo.+Indoor)
To be selected lower temperature
contrast Indoor Unit and Remo.
To be selected lower temperature
contrast Indoor Unit and Remo.
Remo. mode
ST+0
ST+2
I Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.
Pipe
temperature
35 °C
30 °C
27 °C
25 °C
22 °C
LO
LOW
Indoor fan
SELECTED
LOW
OFF
LOW
LOLOW
FAN
speed
COMP
ON
- 16 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
5 5 0
6 4 0
6 9 . 5
2 7 5
- 17 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Ceiling Mounted Cassette Type (4Way) (1)
1. Functions ....................................................................................19
2. Operation Details........................................................................20
3. Dimensions .................................................................................22
- 18 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• Jet, High, Med, Low, Lolow
• Intermittent operation of fan at low speed.
• The louver can be set at swing up and down automatically.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
• The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.
Hot-start Control (Heating)
Compact and light design
• To install a unit is very convenient because of smaller
size than textile.
• The most advanced low-noise design.
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
Low noise
• Long life wrinkle(type) and washable and anti-bacteria
filter is adopted.
Long life filter
• Built-in drain pump automatically drains water.
• A standard drain-head height of up to 700mm is possible.
High head Drain pump
High-Ceiling corresponding Function
• According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
•
•
It is operating individually or totally by central control function.
It is operating swirl swing
Central Control(Optional)
Swirl Swing Control
- 19 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Detail
2. Operation Detail
(1) The function of main control
I Auto Swing Control
• This function is to swing the louver up and down automatically.
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
Intake Air Temperature
Thermo. ON
(SET TEMPERATURE +0.5°C)
Thermo. OFF
(SET TEMPERATURE -0.5°C)
More than
3 minutes
More than
3 minutes
Selected
Speed
Selected
Speed
Selected
Speed
INDOOR FAN
Low
Low
Thermal ON
ST+0.5
Thermal OFF
ST-0.5
Indoor Unit mode
To be selected higher temperature
contrast Indoor Unit and Remo.
ST+0.5
To be selected higher temperature
contrast Indoor Unit and Remo.
ST-0.5
2TH (Remo.+Indoor)
Remo. Mode
I Swirl Swing Control
Vane 2
Vane 2, 4 is almost vane closed while vane1, 3 is opened.
Vane 1, 3 and vane 2,4 turn over minutely
Vane 1
Vane 3
Vane 4
- 20 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Detail
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor pipe
Temperature
36(42)°C
33(39)°C
25°C
22(20)°C
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Indoor fan
4 Way
Stop Low Low
Low
Low Stop Stop Low
ON
Thermal ON
ST+2
Thermal OFF
ST+4
Indoor Unit mode
2TH
(Remo.+Indoor)
To be selected lower temperature
contrast Indoor Unit and Remo.
To be selected lower temperature
contrast Indoor Unit and Remo.
Remo. mode
ST+0
ST+2
I Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.
Pipe
temperature
35 °C
30 °C
27 °C
25 °C
22 °C
LO
LOW
Indoor fan
SELECTED
LOW
OFF
LOW
LOLOW
FAN
speed
COMP
ON
- 21 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
9 0
9 0
5 2 1
5 7 0
3 0
1 2 0 . 4
2 6 9
3 0
6 7 0
- 22 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Ceiling Mounted Cassette Type (4Way) (2)
1. Functions ....................................................................................24
2. Operation Details........................................................................25
3. Dimensions .................................................................................27
- 23 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• Jet, High, Med, Low, Lolow
• Intermittent operation of fan at low speed.
• The louver can be set at swing up and down automatically.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
• The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.
Hot-start Control (Heating)
Compact and light design
• To install a unit is very convenient because of smaller
size than textile.
• The most advanced low-noise design.
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
Low noise
• Long life wrinkle(type) and washable and anti-bacteria
filter is adopted.
Long life filter
• Built-in drain pump automatically drains water.
• A standard drain-head height of up to 700mm is possible.
High head Drain pump
High-Ceiling corresponding Function
• According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
•
•
It is operating individually or totally by central control function.
It is operating swirl swing
Central Control(Optional)
Swirl Swing Control
- 24 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Detail
2. Operation Detail
(1) The function of main control
I Auto Swing Control
• This function is to swing the louver up and down automatically.
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
Intake Air Temperature
Thermo. ON
(SET TEMPERATURE +0.5°C)
Thermo. OFF
(SET TEMPERATURE -0.5°C)
More than
3 minutes
More than
3 minutes
Selected
Speed
Selected
Speed
Selected
Speed
INDOOR FAN
Low
Low
Thermal ON
ST+0.5
Thermal OFF
ST-0.5
Indoor Unit mode
To be selected higher temperature
contrast Indoor Unit and Remo.
ST+0.5
To be selected higher temperature
contrast Indoor Unit and Remo.
ST-0.5
2TH (Remo.+Indoor)
Remo. Mode
I Swirl Swing Control
Vane 2
Vane 2, 4 is almost vane closed while vane1, 3 is opened.
Vane 1, 3 and vane 2,4 turn over minutely
Vane 1
Vane 3
Vane 4
- 25 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Detail
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor pipe
Temperature
36(42)°C
33(39)°C
25°C
22(20)°C
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Indoor fan
4 Way
Stop Low Low
Low
Low Stop Stop Low
ON
Thermal ON
ST+2
Thermal OFF
ST+4
Indoor Unit mode
2TH
(Remo.+Indoor)
To be selected lower temperature
contrast Indoor Unit and Remo.
To be selected lower temperature
contrast Indoor Unit and Remo.
Remo. mode
ST+0
ST+2
I Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.
Pipe
temperature
35 °C
30 °C
27 °C
25 °C
22 °C
LO
LOW
Indoor fan
SELECTED
LOW
OFF
LOW
LOLOW
FAN
speed
COMP
ON
- 26 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
126
2 0 4
9 9
8 2
6 0
8 4 0
6 8 4
A direction View
1 5 4
2 0 4
6 7 1
9 5 0
6 1 8
5 0 0 ( A i r o u t l e t h o l e )
- 27 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
126
A direction View
1 9 5
2 4 6
- 28 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
126
A direction View
2 3 7
2 8 8
- 29 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Art Cool Type(Mirror)
1. Functions ....................................................................................31
2. Operation Details........................................................................32
3. Dimensions .................................................................................39
- 30 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (THERMISTOR)
Room temperature control
• Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
• Indoor fan is delayed for 5 sec at the starting.
Indoor Fan Speed Control
• High, Med, Low, CHAOS
Operation indication Lamps (LED)
Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off
: Lights up during the system operation.
Sleep Mode
Timer
: Lights up during Sleep Mode Auto operation.
: Lights up during Timer operation.
Defrost Mode
: Lights up during Defrost Mode or Hot Start operation.
Soft Dry Operation Mode
• Intermittent operation of fan at low speed.
Sleep Mode Auto Control
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic
• Both the indoor and outdoor fan stops dur-
ing defrosting.
• The fan is switched to intermittent or irregular operation
•
The fan speed is automatically switched from high to low speed.
Hot-start Control (Heating)
• The indoor fan does not rotate until the
evaporator pipe temperature will be reached
at 28°C.
Airflow Direction Control
• The louver can be set at the desired position or swing
up and down automatically.
- 31 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
I Cooling Mode Operation
•
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.
- 32 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Healthy Dehumidification Mode
• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp < 26°C => Intake Air Temp-1°C
18°C ≤ Intake Air Temp < 24°C => Intake Air Temp-0.5°C
Intake Air Temp < 18°C
=> 18°C
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C
Compressor OFF Temp. => Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
I Heating Mode Operation
• When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.
When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2˚C
Themo OFF Temp. => Setting Temp.+4°C
• While in compressor on, when above 38°C, it operates with setting airflow speed (while in sleep mode, with
the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C , when above 35°C , it
operates with the low airflow speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.
I Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.
I Fuzzy Operation (Outdoor unit C/O Model)
• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp<18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-
ature
- 33 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Fuzzy Operation (Outdoor unit H/P Model)
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp
21°C ≤ Inatake Air Temp<24°C => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C => Fuzzy Operation for Heating
=> Fuzzy Operation for Cooling
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
- 34 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp + 2°C
Compressor OFF Temp => Setting Temp + 4°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
20°C ≤ Intake Air Temp => Intake Air Temp + 0.5°C
Intake Air Temp < 20°C => 20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
I Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.
I On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
I Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
- 35 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation
is carried out according to the set time.
I Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.
I Chaos Swing Mode
• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.
I Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.”
I Jet Cool Mode Operation (Outdoor unit C/O Model)
• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
I Jet Cool Mode Operation (Outdoor unit H/P Model)
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
I Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory
- 36 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
I Forced Operation (Outdoor unit C/O Model)
• To operate the appliance by force in case that the remote controller is lost, the forced operation button is on
the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of
airflow.
I Forced Operation (Outdoor unit H/P Model)
• To operate the appliance by force in case that the remote controller is lost, the forced operation selection
switch is on the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation
condition is set according to the intake air temperature as follows.
24°C ≤ Intake Air Temp
=> Cooling Mode Operation, 22°C, High Speed
21°C ≤ Intake Air Temp < 24°C => Dehumidification Operation, 23°C, High Speed
Intake Air Temp < 21°C
=> Heating Mode Operation, 24°C, High Speed
I Test Operation Control
• To check the condition of the installation when installing the appliance, the appliance is operated at cooling
mode, high speed of airflow, compressor-on for 18 min without controlling the room temperature.
• After supplying power to the main body, keep pressing the forced operation button for about 3 seconds.
• While in test operation, a key can be input by the remote controller.
When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, Jet
Cool) is input by the remote controller, the test operation is canceled and the appliance is operated according
to the setting by the remote controller.
I Protection of the evaporator pipe from frosting
• In the temperrature of the indoor pipe is below 0°C after 7 minutes from starting the compressor, the compres-
sor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the temperature of
the indoor pipe is over 7°C, the compressor and the outdoor fan are reoperated.
• Outdoor fan motor stops when indoor pipe temperature is blow 3°C and restarts at the pipe temperature above
6°C or after 90 seconds, if the pipe temperature does not rise to 6°C, outdoor fan motor runs continuously at
even below 3°C.
- 37 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Buzzer Sounding Operation
• When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds.
• When the appliance-pause key is input by the remote controller, the long “beep—” sounds.
I Air Cleaner Operation
• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.
- 38 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
2 8 2
5 3
2 6 5
1 6 5
2 8 2
- 39 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3 0 4
3 1 5
1 7 3
- 40 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
ArtCoolGallery
1. Functions ....................................................................................42
2. Operation Details........................................................................43
3. Dimensions .................................................................................50
- 41 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (THERMISTOR)
Room temperature control
• Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
• Indoor fan is delayed for 5 sec at the starting.
Indoor Fan Speed Control
• High, Med, Low, CHAOS
Operation indication Lamps (LED)
Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off
: Lights up during the system operation.
Sleep Mode
Timer
: Lights up during Sleep Mode Auto operation.
: Lights up during Timer operation.
Defrost Mode
: Lights up during Defrost Mode or Hot Start operation.
Soft Dry Operation Mode
• Intermittent operation of fan at low speed.
Sleep Mode Auto Control
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic
• Both the indoor and outdoor fan stops dur-
ing defrosting.
• The fan is switched to intermittent or irregular operation
•
The fan speed is automatically switched from high to low speed.
Hot-start Control (Heating)
• The indoor fan does not rotate until the
evaporator pipe temperature will be reached
at 28°C.
Airflow Direction Control
• The louver can be set at the desired position or swing
up and down automatically.
- 42 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
I Cooling Mode Operation
•
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.
- 43 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Healthy Dehumidification Mode
• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp < 26°C => Intake Air Temp-1°C
18°C ≤ Intake Air Temp < 24°C => Intake Air Temp-0.5°C
Intake Air Temp < 18°C
=> 18°C
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C
Compressor OFF Temp. => Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
I Heating Mode Operation
• When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.
When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2˚C
Themo OFF Temp. => Setting Temp.+4°C
• While in compressor on, when above 38°C, it operates with setting airflow speed (while in sleep mode, with
the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C , when above 35°C , it
operates with the low airflow speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.
I Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.
I Fuzzy Operation (Outdoor unit C/O Model)
• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp<18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-
ature
- 44 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Fuzzy Operation (Outdoor unit H/P Model)
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp
21°C ≤ Inatake Air Temp<24°C => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C => Fuzzy Operation for Heating
=> Fuzzy Operation for Cooling
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
- 45 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp + 2°C
Compressor OFF Temp => Setting Temp + 4°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
20°C ≤ Intake Air Temp => Intake Air Temp + 0.5°C
Intake Air Temp < 20°C => 20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
I Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.
I On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
I Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
- 46 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation
is carried out according to the set time.
I Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.
I Chaos Swing Mode
• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.
I Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.”
I Jet Cool Mode Operation (Outdoor unit C/O Model)
• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
I Jet Cool Mode Operation (Outdoor unit H/P Model)
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
I Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory
- 47 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
I Forced Operation (Outdoor unit C/O Model)
• To operate the appliance by force in case that the remote controller is lost, the forced operation button is on
the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of
airflow.
I Forced Operation (Outdoor unit H/P Model)
• To operate the appliance by force in case that the remote controller is lost, the forced operation selection
switch is on the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation
condition is set according to the intake air temperature as follows.
24°C ≤ Intake Air Temp
=> Cooling Mode Operation, 22°C, High Speed
21°C ≤ Intake Air Temp < 24°C => Dehumidification Operation, 23°C, High Speed
Intake Air Temp < 21°C
=> Heating Mode Operation, 24°C, High Speed
I Test Operation Control
• To check the condition of the installation when installing the appliance, the appliance is operated at cooling
mode, high speed of airflow, compressor-on for 18 min without controlling the room temperature.
• After supplying power to the main body, keep pressing the forced operation button for about 3 seconds.
• While in test operation, a key can be input by the remote controller.
When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, Jet
Cool) is input by the remote controller, the test operation is canceled and the appliance is operated according
to the setting by the remote controller.
I Protection of the evaporator pipe from frosting
• In the temperrature of the indoor pipe is below 0°C after 7 minutes from starting the compressor, the compres-
sor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the temperature of
the indoor pipe is over 7°C, the compressor and the outdoor fan are reoperated.
• Outdoor fan motor stops when indoor pipe temperature is blow 3°C and restarts at the pipe temperature above
6°C or after 90 seconds, if the pipe temperature does not rise to 6°C, outdoor fan motor runs continuously at
even below 3°C.
- 48 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Buzzer Sounding Operation
• When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds.
• When the appliance-pause key is input by the remote controller, the long “beep—” sounds.
I Air Cleaner Operation
• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.
- 49 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
5 2 5
- 50 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Ceiling Concealed Duct Type (Low static)
1. Funtions ......................................................................................52
2. Operation Details........................................................................53
3. Dimensions .................................................................................56
- 51 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• High, Med, Low
• Intermittent operation of fan at low speed.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
Hot-start Control (Heating)
• The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C.
High head height Drain pump
• A standard drain-head height of up to 700mm is possible.
•
It is operating individually or totally by central control function.
Central Control(Optional)
- 52 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
2. Operation Details
(1) The function of main control
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.
Intake Air Temperature
SET TEMPERATURE +0.5°C
(Thermo. ON)
SET TEMPERATURE -0.5°C
(Thermo. OFF)
More than
3 minutes
More than
3 minutes
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
INDOOR FAN
Low
OFF
Low
OFF
COMPRESSOR
ON
ON
ON
Thermal ON
ST+0.5
Thermal OFF
ST-0.5
Indoor Unit mode
To be selected higher temperature
contrast Indoor Unit and Remo.
ST+0.5
To be selected higher temperature
contrast Indoor Unit and Remo.
ST-0.5
2TH (Remo.+Indoor)
Remo. Mode
- 53 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor unit
Heat-Exchanger
40°C
temperature
T ST
A
T LT
T Off
T On
Intake Air Temperature
3min
Low fan during 10sec
B
Setting Temperature
+3°C
(Thermal OFF)
Setting Temperature
(Thermal ON)
Minimum
3min
1min
1min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
C
Setting
fan
Setting
fan
Setting
fan
Indoor fan
4way valve
Off Low Low
Low
Low Off
Off Low
spped
spped
spped
ON
• Compressor-off interval : -
While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
A
-
-
For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
B
C
To be operated "Low" except initial Hotstart operation
High Static
Low Static
B2 CE
Convertible
VE
Chassis
BH
BG
BR
B1
CF
VJ
Hotstart On
Hotstart Off
T On
T Off
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C 19°C 19°C 19°C
22°C 22°C 22°C 22°C
25°C 25°C 25°C 25°C
27°C 27°C 27°C 27°C
26°C
27°C
28°C
30°C
26°C
27°C
28°C
30°C
Low temperature T LT
Setting Temperature T ST
- 54 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C.
• The operation diagram is as following.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min
Low
1 min
Low
Thermal
Outdoor fan
ON
ON
Setting fan
speed
Setting fan
speed
Indoor fan
Off
Off
ON
4way Valve
• Initial Hotstart On state
➀ Power Off ➠ On
➁ Operation Off ➠ On
➂ Cooling operation ➠ Heating operation
➃ Defrost operation
- 55 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
2 1 6
2 7 7
2 4
1 6 1
1 4
3 8 3
5 7 5
1 8
1 5 4
1 9 0
- 56 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Ceiling Concealed Duct Type (Built in)
1. Funtions ......................................................................................58
2. Operation Details........................................................................59
3. Dimensions .................................................................................62
- 57 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• High, Med, Low
• Intermittent operation of fan at low speed.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
Hot-start Control (Heating)
• The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C.
High head height Drain pump
• A standard drain-head height of up to 700mm is possible.
•
It is operating individually or totally by central control function.
Central Control(Optional)
- 58 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
2. Operation Details
(1) The function of main control
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.
Intake Air Temperature
SET TEMPERATURE +0.5°C
(Thermo. ON)
SET TEMPERATURE -0.5°C
(Thermo. OFF)
More than
3 minutes
More than
3 minutes
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
INDOOR FAN
Low
OFF
Low
OFF
COMPRESSOR
ON
ON
ON
Thermal ON
ST+0.5
Thermal OFF
ST-0.5
Indoor Unit mode
To be selected higher temperature
contrast Indoor Unit and Remo.
ST+0.5
To be selected higher temperature
contrast Indoor Unit and Remo.
ST-0.5
2TH (Remo.+Indoor)
Remo. Mode
- 59 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor unit
Heat-Exchanger
40°C
temperature
T ST
A
T LT
T Off
T On
Intake Air Temperature
3min
Low fan during 10sec
B
Setting Temperature
+3°C
(Thermal OFF)
Setting Temperature
(Thermal ON)
Minimum
3min
1min
1min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
C
Setting
fan
Setting
fan
Setting
fan
Indoor fan
4way valve
Off Low Low
Low
Low Off
Off Low
spped
spped
spped
ON
• Compressor-off interval : -
While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
A
-
-
For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
B
C
To be operated "Low" except initial Hotstart operation
High Static
Low Static
B2 CE
Convertible
VE
Chassis
Hotstart On
Hotstart Off
BH
BG
BR
B1
CF
VJ
T On
T Off
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C 19°C 19°C 19°C
22°C 22°C 22°C 22°C
25°C 25°C 25°C 25°C
27°C 27°C 27°C 27°C
26°C
27°C
28°C
30°C
26°C
27°C
28°C
30°C
Low temperature T LT
Setting Temperature T ST
- 60 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C.
• The operation diagram is as following.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min
Low
1 min
Low
Thermal
Outdoor fan
ON
ON
Setting fan
speed
Setting fan
speed
Indoor fan
Off
Off
ON
4way Valve
• Initial Hotstart On state
➀ Power Off ➠ On
➁ Operation Off ➠ On
➂ Cooling operation ➠ Heating operation
➃ Defrost operation
- 61 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
2 1 6
2 7 7
2 4
3 8 8
6 1 8
3 8 8
5 7 5
1 9 0
2 5 0
1 9 0
5 0 0 ( M a x )
- 62 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Ceiling Concealed Duct Type (High Static)
1. Funtions ......................................................................................64
2. Operation Details........................................................................65
3. Dimensions .................................................................................68
- 63 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Funtion
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• High, Med, Low
• Intermittent operation of fan at low speed.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
Hot-start Control (Heating)
• The indoor fan does not rotate until the evaporator piping
temperature reaches 30°C.
High head height Drain pump
• A standard drain-head height of up to 700mm is possible.
•
It is operating individually or totally by central control function.
Central Control(Optional)
- 64 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
2. Operation Details
(1) The function of main control
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.
Intake Air Temperature
SET TEMPERATURE +0.5°C
(Thermo. ON)
SET TEMPERATURE -0.5°C
(Thermo. OFF)
More than
3 minutes
More than
3 minutes
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
INDOOR FAN
Low
OFF
Low
OFF
COMPRESSOR
ON
ON
ON
- 65 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor unit
Heat-Exchanger
40°C
temperature
T ST
A
T LT
T Off
T On
Intake Air Temperature
3min
Low fan during 10sec
B
Setting Temperature
+3°C
(Thermal OFF)
Setting Temperature
(Thermal ON)
Minimum
3min
1min
1min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
C
Setting
fan
Setting
fan
Setting
fan
Indoor fan
4way valve
Off Low Low
Low
Low Off
Off Low
spped
spped
spped
ON
• Compressor-off interval : -
While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
A
-
-
For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
B
C
To be operated "Low" except initial Hotstart operation
High Static
Low Static
B2 CE
Convertible
VE
Chassis
BH
BG
BR
B1
CF
VJ
Hotstart On
Hotstart Off
T On
T Off
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C 19°C 19°C 19°C
22°C 22°C 22°C 22°C
25°C 25°C 25°C 25°C
27°C 27°C 27°C 27°C
26°C
27°C
28°C
30°C
26°C
27°C
28°C
30°C
Low temperature T LT
Setting Temperature T ST
- 66 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 22°C.
• The operation diagram is as following.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min
Low
1 min
Low
Thermal
Outdoor fan
ON
ON
Setting fan
speed
Setting fan
speed
Indoor fan
Off
Off
ON
4way Valve
• Initial Hotstart On state
➀ Power Off ➠ On
➁ Operation Off ➠ On
➂ Cooling operation ➠ Heating operation
➃ Defrost operation
- 67 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
4 5 0
1 3 3
3 5 5
1 7 5
2 0
1 5 8
2 6 0
3 5 5
4 5 0
4 5 0
2 2 4
- 68 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
4 5 0
3 5 5
1 5 8
1 1 3
1 8 6
2 9 8
4 5 0
2 2 0
2 0
2 2 4
- 69 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
2 2 1
1 2 3
7 2
1 4 4
1 2 2
9 0
5 9 0
4 7 7
1 6 8
1 8 5
5 6
5 9 0
1 4 0
3 8 0
3 2
3 0 3
2 5
3 1 2
- 70 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
1 4 0
9 9
6 0 1 2 2
7 0
6 4
6 8 8
5 6 0
3 0
2 9 0
1 6 1
6 4
4 4 0
2 0
3 1 8
4 6 0
6 8 8
- 71 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Wall Mountedd Type
1. Functions ....................................................................................73
2. Operation Details........................................................................74
3. Dimensions .................................................................................81
- 72 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (THERMISTOR)
Room temperature control
• Maintains the room temperature in accordance with the Setting temperature
Starting Current Control
• Indoor fan is delayed for 5 sec at the starting.
Indoor Fan Speed Control
• High, Med, Low, CHAOS
Operation indication Lamps (LED)
Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off
Sleep Mode
Timer
: Lights up during the system operation.
: Lights up during Sleep Mode Auto operation.
: Lights up during Timer operation.
Defrost Mode
Temperature
: Lights up during Defrost Mode or Hot Start operation.
: Indicate the setting temperature.
Soft Dry Operation Mode
• Intermittent operation of fan at low speed.
Sleep Mode Auto Control
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic
• Both the indoor and outdoor fan stops dur-
• The fan is switched to intermittent or irregular operation
ing defrosting.
•
The fan speed is automatically switched from high to low speed.
Hot-start Control (Heating)
• The indoor fan does not rotate until the
evaporator pipe temperature will be reached
at 28°C.
Airflow Direction Control
• The louver can be set at the desired position or swing
up and down automatically.
- 73 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
2. Operation Details
Function of Controls
DISPLAY
(1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer(on/off) and Sleep timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
I Cooling Mode Operation
•
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote controller. While in com-
pressor not running, operating with the low airflow speed regardless of the setting.
- 74 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Healthy Dehumidification Mode
• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp < 26°C => Intake Air Temp-1°C
18°C ≤ Intake Air Temp < 24°C => Intake Air Temp-0.5°C
Intake Air Temp < 18°C
=> 18°C
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C
Compressor OFF Temp. => Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
I Heating Mode Operation
• When the intake air temp reaches +3°Cabove the setting temp, the compressor is turned off. When below the
setting temp, the compressor is turned on.
Thermo ON Temp. => Setting Temp. +2°C
Thermo OFF Temp. => Setting Temp. +4°C
• While in compressor on, when above 38°C , it operates with or setting airflow speed (while in sleep mode, with
the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C , when above 35°C , it
operates with the low airflow speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.
I Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost the outdoor unit.
I Fuzzy Operation (Outdoor unit C/O Model)
• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
- 75 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp<18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-
ature
I Fuzzy Operation (Outdoor unit H/P Model)
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp
21°C ≤ Inatake Air Temp<24°C => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C => Fuzzy Operation for Heating
=> Fuzzy Operation for Cooling
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
- 76 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp
=> 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C
=> 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp. +2°C
Compressor OFF Temp => Setting Temp. +4°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C ≤ Intake Air Temp => Intake Air Temp + 0.5°C
Intake Air Temp < 20°C => 20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
I Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.
I On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
I Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
- 77 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation is
carried out according to the set time.
I Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.
I Chaos Swing Mode
• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.
I Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.”
I Jet Cool Mode Operation (Outdoor unit C/O Model)
• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• During the JET COOL function at any moment, the A/C starts to blow the cool air with side louvers closed at
extremely high speed for 30 minutes setting the room temp. automatically to 18°C.
I Jet Cool Mode Operation (Outdoor unit H/P Model)
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other
mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• During the JET HEAT function at any moment, the A/C starts to blow the hot air with side louvers closed at
extremely high speed for 60 minutes setting the room temp. automatically to 30°C.
I Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF
- 78 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
I Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.
Heat pump Model
Cooling Model
Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C
Operating mode
Indoor Fan Speed
Setting Temperature
Cooling
High
Cooling
High
Healthy Dehumidification
Heating
High
High
22°C
22°C
23°C
24°C
• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
I Test operation
•
•
•
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-
perature and resets in 18 1 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, Press and hold ON/OFF button 3~5 seconds, then the buzzer sound 1 "beep".
If you want to stop the operation, re-press the button.
I Protection of the evaporator pipe from frosting
• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool-
ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor
evaporator pipe from frosting.
• When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the
outdoor fan is turned on according to the condition of the room temperature.
I Buzzer Sounding Operation
• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
• When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the
remote control signal cannot be received.
- 79 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Air Cleaner Operation
• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.
- 80 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
2 8 2
2 6 5
1 6 5
- 81 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
2 8 1
3 0 0
- 82 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Ceiling & Floor
Ceiling Suspended
1. Funtions ......................................................................................84
2. Operation Details........................................................................85
3. Dimensions .................................................................................88
- 83 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Function
1. Function
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• High, Med, Low
• Intermittent operation of fan at low speed.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
• The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C.
Hot-start Control (Heating)
High head height Drain pump
Central Control(Optional)
• A standard drain-head height of up to 700mm is possible.
•
It is operating individually or totally by central control function.
- 84 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
2. Operation Details
(1) The function of main control
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.
Intake Air Temperature
SET TEMPERATURE +0.5°C
(Thermo. ON)
SET TEMPERATURE -0.5°C
(Thermo. OFF)
More than
3 minutes
More than
3 minutes
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
INDOOR FAN
Low
OFF
Low
OFF
COMPRESSOR
ON
ON
ON
Thermal ON
ST+0.5
Thermal OFF
ST-0.5
Indoor Unit mode
To be selected higher temperature
contrast Indoor Unit and Remo.
ST+0.5
To be selected higher temperature
contrast Indoor Unit and Remo.
ST-0.5
2TH (Remo.+Indoor)
Remo. Mode
- 85 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor unit
Heat-Exchanger
40°C
temperature
T ST
A
T LT
T Off
T On
Intake Air Temperature
3min
Low fan during 10sec
B
Setting Temperature
+3°C
(Thermal OFF)
Setting Temperature
(Thermal ON)
Minimum
3min
1min
1min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
C
Setting
fan
Setting
fan
Setting
fan
Indoor fan
4way valve
Off Low Low
Low
Low Off
Off Low
spped
spped
spped
ON
• Compressor-off interval : -
While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
A
-
-
For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
B
C
To be operated "Low" except initial Hotstart operation
High Static
Low Static
B2 CE
Convertible
VE
Chassis
BH
BG
BR
B1
CF
VJ
Hotstart On
Hotstart Off
T On
T Off
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C 19°C 19°C 19°C
22°C 22°C 22°C 22°C
25°C 25°C 25°C 25°C
27°C 27°C 27°C 27°C
26°C
27°C
28°C
30°C
26°C
27°C
28°C
30°C
Low temperature T LT
Setting Temperature T ST
- 86 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C.
• The operation diagram is as following.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min
Low
1 min
Low
Thermal
Outdoor fan
ON
ON
Setting fan
speed
Setting fan
speed
Indoor fan
Off
Off
ON
4way Valve
• Initial Hotstart On state
➀ Power Off ➠ On
➁ Operation Off ➠ On
➂ Cooling operation ➠ Heating operation
➃ Defrost operation
- 87 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
2 7 3
2 4
4 9 0
- 88 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
6 5 0
- 89 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Floor Standing Type
1. Function ......................................................................................91
2. Operation Details........................................................................92
3. Dimensions .................................................................................95
- 90 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Function
1. Function
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• High, Med, Low
• Intermittent operation of fan at low speed.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Auto Restart
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
Deice (defrost) control (Heating)
• The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C.
Hot-start Control (Heating)
High head height Drain pump
Central Control(Optional)
• A standard drain-head height of up to 700mm is possible.
•
It is operating individually or totally by central control function.
- 91 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
2. Operation Details
(1) The function of main control
I Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
I Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.
Intake Air Temperature
SET TEMPERATURE +0.5°C
(Thermo. ON)
SET TEMPERATURE -0.5°C
(Thermo. OFF)
More than
3 minutes
More than
3 minutes
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
INDOOR FAN
Low
OFF
Low
OFF
COMPRESSOR
ON
ON
ON
Thermal ON
ST+0.5
Thermal OFF
ST-0.5
Indoor Unit mode
To be selected higher temperature
contrast Indoor Unit and Remo.
ST+0.5
To be selected higher temperature
contrast Indoor Unit and Remo.
ST-0.5
2TH (Remo.+Indoor)
Remo. Mode
- 92 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor unit
Heat-Exchanger
40°C
temperature
T ST
A
T LT
T Off
T On
Intake Air Temperature
3min
Low fan during 10sec
B
Setting Temperature
+3°C
(Thermal OFF)
Setting Temperature
(Thermal ON)
Minimum
3min
1min
1min
Thermal
ON
ON
OFF
OFF
ON
ON
Outdoor fan
C
Setting
fan
Setting
fan
Setting
fan
Indoor fan
4way valve
Off Low Low
Low
Low Off
Off Low
spped
spped
spped
ON
• Compressor-off interval : -
While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
A
-
-
For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
B
C
To be operated "Low" except initial Hotstart operation
High Static
Low Static
B2 CE
Convertible
VE
Chassis
BH
BG
BR
B1
CF
VJ
Hotstart On
Hotstart Off
T On
T Off
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C
22°C
25°C
27°C
19°C 19°C 19°C 19°C
22°C 22°C 22°C 22°C
25°C 25°C 25°C 25°C
27°C 27°C 27°C 27°C
26°C
27°C
28°C
30°C
26°C
27°C
28°C
30°C
Low temperature T LT
Setting Temperature T ST
- 93 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Details
I Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C.
• The operation diagram is as following.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min
Low
1 min
Low
Thermal
Outdoor fan
ON
ON
Setting fan
speed
Setting fan
speed
Indoor fan
Off
Off
ON
4way Valve
• Initial Hotstart On state
➀ Power Off ➠ On
➁ Operation Off ➠ On
➂ Cooling operation ➠ Heating operation
➃ Defrost operation
- 94 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
3. Dimensions
6 3 5
2 0 . 4
7 0
6 2 . 8
4 9
6 3 9
- 95 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
6 3 5
2 0 3
7 0
1 4 5
8 1 . 4
4 9 . 4
7 0
2 1 . 4
6 3 9
- 96 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Part 3
Trouble shooting guide
- 97 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Trouble shooting guide
Self-diagnosis function.....................................................................99
- 98 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
Self-diagnosis function
Self-Diagnosis Function
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
011 ¡ 051 : No.105 error of master unit
Display
Title
Cause of Error
0
1
2
-
Air temperature sensor of indoor unit is open or short
Inlet pipe temperature sensor of indoor unit is open or short
Failing to receive wired remote controller signal in indoor unit PCB
Air temperature sensor of indoor unit
Inlet pipe temperature sensor of indoor unit
0
0
0
0
-
-
-
-
Transmission error : wired remote controller
↔ indoor unit
3
4
5
Drain pump
Malfunction of drain pump
Transmission error : outdoor unit ↔ indoor
unit
Failing to receive outdoor unit signal in indoor unit PCB
0
0
6
7
-
-
Outlet pipe temperature sensor of indoor unit
Different operation mode
Serial No.
Outlet pipe temperature sensor of indoor unit is open or short
Operation mode between indoor unit and outdoor unit is different
In case when the serial number marked on
EEPROM of Indoor unit is 0 or FFFFFF
0
1
1
9
0
1
-
-
-
Poor fan motor operation
Disconnecting the fan motor connector/Failure of indoor fan motor
lock
Transmission error: indoor unit ¡ main PCB
of outdoor.
When the addressing signal doesn't respond for 3mins. suddenly,
while the indoor unit gets the calling signal from the outdoor unit,
- 99 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
Error
No.
Error Type
Error Point
Main Reasons
01
02
06
Indoor unit air sensor error
1. Indoor unit PCB wrong connection
2. Indoor unit PCB failure
Indoor unit sensor is
open/short
Indoor unit pipe inlet sensor error
Indoor unit pipe outlet sensor error
3. Sensor problem (main reason)
I Error diagnosis and countermeasure flow chart
No
Is sensor properly
Connect properly to PCB
connected to PCB?
Yes
No
Is the resistance value
of sensor normal?*
Change the sensor
Yes
Change the PCB
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature( 5% margin) ➔ Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ
CN-ROOM : Indoor air temp sensor
CN-PIPE2 : Pipe outlet temp sensor
CN-PIPE1 : Pipe inlet temp sensor
Measure the resistance of outlet pipe temp sensor.
- 100 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
Error
No.
Error Type
Error Point
Main Reasons
1. Remote controller fault
The remote controller
did not receive the sig-
nal from indoor unit
during specific time
2. Indoor unit PCB fault
03
No transmission between cabled
remote controller & indoor unit
3. Connector fault, Wrong connection
4. transmission cable problem
I Error diagnosis and countermeasure flow chart
Does the error happens
again if the remote
controller is replaced?*
No
Replace cabled remote
controller
Yes
Does the error occurred
when the cable of remote
controller is replaced?
No
Check connection &
transmission cable **
Yes
Replace indoor unit PCB ***
* If there is no remote controller to replace : Use another unit’s remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
➔ make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unit’s address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
: Remote controller connection
CN-REMO
❇ The PCB can differ from model to model.
Check from the right source.
Checking transmission cable connection status
- 101 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
Error
No.
Error Type
Error Point
Main Reasons
1. Drain pump/float switch fault
Float switch is open due to
rising of condensate water
level because of drain
pump fault or drain pipe
clogging
2. Improper drain pipe location, clog-
ging of drain pipe
04
Drain pump error
3. Indoor unit PCB fault
I Error diagnosis and countermeasure flow chart
Is the drain pan filled
Is Float switch short
On measuring its
resistance?
No
No
half with condensate
water? (half level of
float switch)*
Replace float switch
Yes
Yes
Replace Indoor PCB or
reconnect the connector
In indoor unit PCB
Does the terminal voltage
for drain pump has
220V output?**
No
No
Is drain pump working?
(Sound/drain noise/
contact etc.)
Replace indoor unit PCB
Yes
Yes
Replace Drain Pump
N o
Drain pump blocked by
foreign particles?
Check the drain head height
and slope***
Checking float
sw itch
Yes
(Low position➠ short 0 ohm )
Remove it & clean the pump
* If the float goes up higher than a half of float
switch then the circuit is open & the unit is
stopped automatically.
float
(High position➠O pen)
Condensate w ater
- 102 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
float
*** Indoor PCB drain pump connector
A:Point to check rotating
(Check input of 220V)
(Marked as CN-DPUMP)
Float switch connector
Float switch Housing (CN-FLOAT)
[***] Standard of drain pipe head height / slope
MAX 450
- 103 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
Error
Error Type
No.
Error Point
Main Reasons
1. Auto addressing is not done
2. transmission cable is not connected
3. Short circuit of transmission cable
4. Indoor unit transmission circuit fault
5. Outdoor unit transmission circuit fault
6. Not enough distance between power and trans-
mission cable?
No signal transmission
between indoor & outdoor
units.
Indoor & Outdoor unit
05
transmission error
I Error diagnosis and countermeasure flow chart
Replace the PCB of indoor unit
No
No
displayed error
No
Is total number of indoor
units connected displayed
after auto addressing?
Does all the IDUs show
same error code CH05?
Re-connect after check the
transmission cable of indoor
unit displayed error**
Yes
END
Replace outdoor PCB after
checking
Check the main power
supply at the ODU
terminal block?
No
Is outdoor PCB LED
blinking?
Replace TRANS after checking
Yes
Yes
Check the insulation of inverter
/ constant compressor and replace
if required
No
Is main circuit breaker off?
Yes
Check the capacity of main circuit
breaker and replace if required
Improper connection of power supply cable
Main power supply problem
If all ok,
Turn on main circuit breaker
Check if the
transmission cable is
properly connected
to indoor / outdoor
terminal block?*
No
Re connect transmission cable
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking
* (Note1) Transmission from IDU is normal if voltage
fluctuation(-9V ~ +9V) exists when checking DC voltage
of communication terminal between IDU and ODU
* If the DC voltage between transmission terminal A, B
of indoor unit is fluctuate within (-9V~+9V) then
transmission from outdoor unit is normal
- 104 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
Error
No.
Error Type
Error Point
Main Reasons
Refer to CH02
Indoor unit outlet pipe
temperature sensor open
or short
Indoor unit outlet pipe
temperature sensor
error
06
Error
No.
Error Type
Error Point
Main Reasons
1. Indoor units are in different mode
2. PCB fault
3. cabled remote controller fault
❊ Checking ch07 method
The Indoor units started
later are operated in dif-
ferent mode from earlier
one.
All Indoor units are not
running in same mode
07
IDU doesn’t operate as Operation mode is
flickering at IDU wired remote controller and IDU
display window.
I Error diagnosis and countermeasure flow chart
Does error code
Is operation mode of
No
No
disappear
outdoor & Indoor units
after set operation
same?
Replace Indoor PCB***
mode same?**
Yes
Yes
END
Adjust outdoor main PCB
dip switch setting *
* Check mode selection setting of wired remote controller.
** Outdoor main PCB dip switch no.5 (Cooling) or no.6 (heating) is in On, different mode operation error
may occur because the operation mode is fixed by dip switch setting.
o Dip switch Setting o
ON
ON
1
1
2
2
3
3
4
4
5
5
6
6
7
7
1
8
2
9
3
4
5
6
7
10 11 12 13 14
ON
ON
1
1
2
2
3
3
4
4
5
5
6
6
7
7
1
8
2
9
3
4
5
6
7
10 11 12 13 14
*** Dissolution method CH07 with remote controller
1) Error removal method : Turn off remote controller by pressing the On/Off button on the cabled remote controller.
The error code will be removed automatically after few seconds.
With cableless remote controller: Turn off indoor unit, and then turn on by changing the operation
mode. The error will disappear.
- 105 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
LGE Internal Use Only
Only for training and service purposes
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
**** After replacing the indoor unit PCB, make sure to be done to do Auto addressing and input the address of central control
***** If ODU Dry Contact function is set , different mode operation error may be occurred because the operation mode is fixed.
Error
No.
Error Type
Error Point
Main Reasons
1. Error developed in transmission between the
micro- processor and the EEPROM on the sur-
face of the PCB.
Indoor unit EEPROM
error
09
2. ERROR due to the EEPROM damage
I Error diagnosis and countermeasure flow chart
- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control
- 106 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
Error
No.
Error Type
Error Point
Main Reasons
Indoor unit BLDC fan motor
failure
Indoor BLDC fan motor
feedback signal is absent
(for 50 sec.)
1. Motor connector connection fault
2. Indoor PCB fault
3. Motor fault
10
I Error diagnosis and countermeasure flow chart
Is connector
connection proper?
No
Connect properly
Yes
No
Is fan motor
normal?*
Replace indoor unit fan motor
Yes
Replace indoor unit PCB **
* It is normal when check hall sensor of indoor fan motor as shown below
Each termainl with the tester
Normal resistance( 10%)
Tester
+
-
TH chassis TD chassis
1
5
6
7
4
4
4
4
∞
∞
k
hundreds kΩ hundreds kΩ
∞
∞
hundreds kΩ hundreds kΩ
1
4
5
6
7
<Checking connection state of fan motor connector>
** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the
address of central control
(Notice: The connection of motor connector to PCB should be done under no power
supplying to PCB)
- 107 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnosis function
Error
No.
Error Type
Indoor unit transmission error
Error Point
Main Reasons
1. Indoor 485 transmission PCB fault
Indoor unit doesn’t get sig-
nal from ODU for 3 minutes
continuously
11
2. After PCB replacing, auto addressing
was not done
I Error diagnosis and countermeasure flow chart
After ODU main PCB
reset, error code
disappears?
No
No
After Auto addressing,
error code disappears?
Replace indoor unit 485
transmission PCB
Yes
Yes
END
- 108 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Download from Www.Somanuals.com. All Manuals Search And Download.
APRIL, 2008
P/NO : MFL50459501
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Grundig Flat Panel Television 40 VLE 8130 BG User Manual
Hasbro Robotics 83606 User Manual
Havis Shields Automobile Accessories WBI F7 User Manual
Heath Zenith Work Light 598 1189 01 User Manual
Hoshizaki Ice Maker B 1150SS User Manual
Hotpoint Washer WmAQL 721 User Manual
HP Hewlett Packard Computer Accessories ProLiant BL495c G6 User Manual
Hunter Fan Outdoor Ceiling Fan 42426 01 User Manual
Husqvarna Lawn Mower YTH2648TDRF User Manual
IBM Network Card CONNECTX 2 User Manual