hp Modular Power Distribution Units
(Zero-U/1U Modular PDUs)
QuickSpecs
MODELS
Low Voltage Modular PDU Model, 100 – 127 VAC
24A Model – mPDU, 24A, Low
252663-D71 (NA/LA/JPN)
High Voltage Modular PDU Model(s), 200 – 240 VAC
16A Model – mPDU, 16A, High
252663-B24 (WW)
24A Model – mPDU, 24A, High
252663-D72 (NA/LA/JPN)
32A Model – mPDU, 32A, High
252663-B31 (INT’L)
40A Model – mPDU, 40A, High
252663-B21 (WW)
Feature List
•
•
•
•
•
Single input power distribution units with a unique modular design architecture
Up to 32 outlet receptacles
Zero-U/1U dense rack form factor
Easily accessible outlet receptacles and improved cable management
Models range from 16A-40A
DA-11041
World Wide — Version 3 — December 11, 2002
Download from Www.Somanuals.com. All Manuals Search And Download.
1
hp Modular Power Distribution Units
(Zero-U/1U Modular PDUs)
QuickSpecs
PRODUCT HIGHLIGHTS (continued)
Consolidate and Maximize Cord Management
When you have the power to choose where to mount the Extension Bars, you have the option of mounting the bars closer to where your specific servers
are located; so you don’t have to use long power cords running down the entire length of your rack – you can now get smaller cords plugging-in to a
nearby Extension Bar.
Shorter jumper cords (4.5ft) are offered as optional kits (PN 142257-006, quantity 1; PN 142257-007, quantity 15). Two short jumper cords ship with every
high voltage model of the mPDU. Additional shorter cords, if needed, have to be ordered (typically most devices ship with a 12ft – 8ft long jumper cord).
For more information on IEC320 -C14 to IEC 320 -C13 jumper cords, please refer the PDU cable section at the end of this document.
For low voltage applications (100 – 127V), typically most devices ship with a NEMA 5-15 cable (which plugs-into the NEMA 5-15R outlets on the low volt
Extension Bar). However, some devices with IEC320-C13 inlet may not ship with a NEMA cable. In such cases, a cable IEC320-C14 to NEMA 5-15P (PN
e7743a) will have to be ordered.
Easily Accessible Outlet Receptacles
Because you have the flexibility to decide how you want to configure your Modular PDU, you can now choose to mount the Extension Bars such that the
outlet receptacles are easily accessible, allowing you to easily plug-in and plug-out devices.
Current Ratings from 16A to 40A
Modular PDUs are available in a wide range, including four high volt models ranging from 16A to 40A current ratings; and one low voltage 24A model.
Compatibility
Ideal for use with the HP 9000 and 10000 Series Racks, the Modular PDUs are largely designed for the dense rack environment. These Modular PDUs
connect directly to the facility input power.
In addition, the low voltage model also connects to the low voltage UPS R3000 XR. The 40A model may be hardwired to a UPS as well. And the recently
announced 16A high voltage model will also connect to the high voltage UPS models of the R3000 XR and R6000.
Note: Control unit of the Modular PDUs may be mounted in a 1U configuration in most standard racks. To mount the Extension Bars in a rack other than
the HP 9000 and 10000 series racks, an optional kit PN 310777-B21 is offered. This kit allows mounting the Extension Bars in most third party racks
which use a standard EIA19″ vertical rail.
SERVICE & SUPPORT, CAREPAQ AND WARRANTY INFORMATION
Warranty Upgrade Options
HP Modular PDUs are backed by a limited 3-year warranty.
When used in the HP 9000 and 10000 Series Racks, HP PDUs assume the warranty of theHP Rack in which they’re installed. HP CarePaq services
bought for the HP Rack also extend towards the HP Modular PDU if it is being used inside the HP rack.
FM-CBXHW-36 – 9x5 Next-Business-Day On-Site Coverage, 3 Years
FM-CB4HR-36 – 9x5 4-Hour Response On-Site Coverage, 3 Years
FM-CB724-36 – 24x7, 4-Hour Response On-Site Coverage, 3 Years
CarePaq Information
For CarePaq (hardware & software) information, as well as orderable part numbers, please refer to the URL listed below:
DA-11041
World Wide — Version 3 — December 11, 2002
Download from Www.Somanuals.com. All Manuals Search And Download.
3
hp Modular Power Distribution Units
(Zero-U/1U Modular PDUs)
QuickSpecs
HP MODULAR PDU SPECIFICATIONS
Mechanical Dimensions (WxHxD) 17.5 x 1.62 x 5.6 in/44.45 x 4.11 x 14.22 cm
Unit Weight
18 lb/8.16 kg
Shipping Dimensions (WxHxD)
Shipping Weight
21.5 x 12.25 x 13.0 in/54.61 x 31.12 x 33.02 cm
20.2 lb/9.16 kg
Operating Temperature
Operating Relative Humidity (%)
Operating Elevation
50° to 122°F/10° to 50°C
10% to 90%
0 to 10,000 ft/0 to 3048 m
–4° to 140°F/–20° to 60°C
5% to 95%
Storage Temperature
Storage Relative Humidity (%)
Storage Elevation
0 to 30,000 ft/0 to 9144 m
Conformance Standards
UL, CUL, CE, NOM, D - 16A and 40A models
UL, CUL, NOM – 24A High and Low voltage models
CE, D - 32A model
Kit Contents
24-40A Modular PDUs ship with x1 Control Unit and x4 Extension Bars
16A Modular PDU ship with x1 Control Unit and x2 Extension Bars
All models ship with:
0U/1U Mounting brackets/hardware for Control Unit
Mounting brackets for Extension Bars
Cord Retention bracket for the Control Unit
Tie wraps
Install Card
High voltage models ship with two 10A, IEC320 -C14 to IEC 320 -C13 jumper cables, each 4.5ft/1.37m long. In
addition, the 16A model ships with one 16A, IEC 320-C19 to IEC 320-C20 jumper cord, 8.2ft/2.5m long.
DA-11041
World Wide — Version 3 — December 11, 2002
4
Download from Www.Somanuals.com. All Manuals Search And Download.
hp Modular Power Distribution Units
(Zero-U/1U Modular PDUs)
QuickSpecs
ADDITIONAL SPECIFICATIONS
Low Voltage 24A
High Voltage 16A
High Voltage 24A
High Voltage 32A
High Voltage 40A
(NA/JPN/LA)
(WW)
252663-B24
16A
(NA/JPN/LA)
(INTL)
(WW)
Part Number
252663-D71
24A
252663-D72
24A
252663-B31
32A
252663-B21
40A
Current (max)
AC Voltage Range
Frequency (Hertz)
Load Capacity (VA)
100-127V
50/60Hz
200-240V
50/60Hz
200-240V
50/60Hz
200-240V
50/60Hz
200-240V
50/60Hz
2880 (@120V)
4x15A
3680 (@230V)
2X10A
4992 (@208V)
4x15A
7360 (@230V
4x15A
9200 (@230V)
4x15A
Output Circuit
Breakers
Overload Protection
Indicator Lights
Yes
Yes
Yes
Yes
Yes
Indicator light on each of the Extension Bars; and a main AC pilot light on the Control Unit
Plugs and Cables
Control Unit (x1)
Input: 3.6m attached
cable with L5-30P
Input: Detachable
input power cord
Input: 3.6m attached
cable with L6-30P
Input: 3.6m attached
cable with IEC309-32A
Input: Hardwire
(country specific) with
a IEC 320-C20 inlet
Output: Four IEC320-
C19 (12A ea)
Output: Four IEC320-
C19 (12A ea)
Output: Four IEC320-
C19 (12A ea)
Output: Four IEC320-
C19 (12A ea)
Output: Two IEC320-
C19 (8A ea)
Note: Manual ON/Off control provided for each load group; switch guards provided to prevent inadvertent power Off. The Control unit for the 16A model
has 2 outputs while the Control Unit for all other Modular PDUs has 4 outputs. The Extension Bars plug directly into the output-ends of the Control
Unit.
Extension Bars (x4)* Input: 2m attached
Input: 2m attached
Input: 2m attached
Input: 2m attached
Input: 2m attached
cord with IEC320-C20
cord with IEC320- C20 cord with IEC320- C20 cord with IEC320- C20 cord with IEC320- C20
*Except for the 16A
model, which has 2
Extension Bars
Output: Each Bar has
8 NEMA 5-15 outlets
Output: Each Bar has
8 C13 outlets
Output: Each Bar has
8 C13 outlets
Output: Each Bar has
8 C13 outlets
Output: 3 Bars each
with 8 C13 (10A max
per outlet, 12A max
per Bar); 1 Bar with 4
C19 (12A max per
outlet, 12A max per
Bar)
(12A max per outlet,
12A max per Bar)
(10A max per outlet,
12A max per Bar)
(10A max per outlet,
12A max per Bar)
(10A max per outlet,
12A max per Bar)
DA-11041
World Wide — Version 3 — December 11, 2002
Download from Www.Somanuals.com. All Manuals Search And Download.
5
hp Modular Power Distribution Units
(Zero-U/1U Modular PDUs)
QuickSpecs
MODULAR PDU FAMILY INFORMATION
MODEL SELECTION MATRIX
Low Voltage 24A
252663-D71
High Voltage 16A
High Voltage 24A
252663-D72
High Voltage 32A
252663-B31
High Voltage 40A
252663-B21
Part Number
252663-B24
Input Connection
(Single Input)
NEMA L5-30P
Detachable input power
cord with a IEC 320-C20
inlet
NEMA L6-30P
IEC 309-32A
Field Wired Terminal
Note: The 16A model with
the detachable cord can be
used only in applications
where the total leakage
current is less than 3.5 mA.
Output Connections (32) NEMA 5-15R
Note: The low volt Extension
(16) IEC 320 C-13
(32) IEC 320 C-13
(32) IEC 320 C-13
(24) IEC 320 C-13
(4) IEC 320 C-19
Note: The 16A model ships
with 2 Extension Bars, while
all other 24-40A models ship
with 4 Extension Bars.
Bars w/5-15 outlets should
be used ONLY with the low
volt Control Unit that is
shipped with the low volt
Modular PDU unit.
Applications
Connects to low voltage Connects to the high
models of the UPS R3000voltage models of the
XR (and may also be UPS R3000 XR and
connected directly into R6000
Designed to connect
directly into the facility directly into the facility
Designed to connect May be hardwired (Note:
Hardwiring needs to be done
by a certified on-site
electrician in accordance with
the local electrical installation
codes.) into the facility
input or to a high voltage
input
input
the facility input)
Note: Except for the UPS
R3000 XR, North America
high volt model, where an
additional cable option kit,
PN 340653-001 (IEC320-
C19 to L6-20P), is needed to
connect a 16A mPDU to the
NA high voltage model of the
UPS R3000 XR
UPS (R12000 XR)
Also connects directly into
the facility input
Note: You need to purchase
a cable PN 340653-001
(IEC320-C19 to L6-20P) for
North America. Other country
specific cables are managed
at the country level.
DA-11041
World Wide — Version 3 — December 11, 2002
Download from Www.Somanuals.com. All Manuals Search And Download.
6
hp Modular Power Distribution Units
(Zero-U/1U Modular PDUs)
QuickSpecs
ADDITIONAL PDU CABLES AVAILABLE
Product Part Number
Description
142257-002
8 ft/2.5 m, x1
10A, IEC320 -C14 to IEC 320 -C13 cables for connecting devices to the
power distribution unit.
142257-003
142257-006
10 ft/3.0 m, x1
4.5 ft/1.37 m, x1
142257-007
201493-001
4.5 ft/1.37 m, x15
High Volt, Y-cable for NA/LA, x1
Remote Insight Lights-Out Edition (RILOE) power Y-cable has been
designed for plugging into HP PDUs. One single Y-cable supports two
RILOE cards, which reduces the number of plugs required on the PDU for
connecting the RILOE cards.
201493-002
201493-B21
201493-B22
High Volt, Y-cables for NA/LA, x20
High Volt, Y-cable for INTL, x1
High Volt, Y-cables for INTL, x20
Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions.
© 2002 Hewlett-Packard Company
Hewlett-Packard, the Hewlett-Packard logo, CarePaq, ProLiant, and StorageWorks are trademarks of Hewlett-Packard Company in the U.S. and/or other
countries. All other product names mentioned herein may be trademarks of their respective companies.
Hewlett-Packard shall not be liable for technical or editorial errors or omissions contained herein. The information is provided "as is" without warranty of any
kind and is subject to change without notice. The warranties for Hewlett-Packard products are set forth in the express limited warranty statements
accompanying such products. Nothing herein should be construed as constituting an additional warranty.