Guardian Technologies Portable Generator 05324 User Manual

Liquid Cooled  
Gas Engine  
Generator Sets  
Standby Power Rating  
25 kW 60 Hz  
Model Number: 05324 (Tan - Steel)  
Whisper-Test™  
Low Speed Exercise  
62 dB(A) at 23 feet  
GENERAC 1.6L ENGINE  
Naturally Aspirated  
Gaseous Fueled  
UL 2200 Listed  
Transfer Switch is sold separately  
STANDARD EQUIPMENT  
UV/Ozone resistant hoses  
Watertight state of the art electrical connectors  
Mainline circuit breaker  
Radiator drain extension  
Battery charge alternator  
2 Amp static battery charger  
Battery rack and battery cables  
Fan and belt guards  
All input connections in one single area  
High coolant temperature shutdown  
Low oil pressure shutdown  
Low coolant level automatic shutdown  
Overspeed automatic shutdown  
Crank timer  
Exercise timer  
Oil drain extension  
Cool flow radiator  
Closed coolant recovery system  
Isochronous governor  
Flex fuel line pigtail  
FEATURES  
State of the art digital control system with R-Series digital control panel  
Watertight electrical connectors  
Rodent proof construction  
High efficiency, low distortion Generac designed alternator  
Vibration isolated from mounting base  
Matching Generac transfer switches engineered and tested to work as  
a system  
Innovative design and fully prototype tested  
UL 2200 Listed  
Solid state frequency compensated  
voltage regulator  
Dynamic and static battery charger  
Sound attenuated acoustically designed enclosure  
Whisper-Test™ feature for low noise level exercise  
Acoustically designed engine cooling system  
High flow low noise factory engineered exhaust system  
All components easily accessible for maintenance  
Electrostatically applied powder paint  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby 25 kW  
OPERATING DATA  
STANDBY 25 kW  
KW RATING  
25 LP / 24 NG  
ENGINE SIZE  
1.6 Liter 4 cyl. in-line  
GENERATOR OUTPUT VOLTAGE/KW - 60Hz  
120/240V, 1-phase, 1.0 pf  
120/208V, 3-phase, 0.8 pf  
KW  
25 LP/24 NG  
25  
AMP  
104.2 LP/100 NG  
87  
CB Size  
125  
100  
GENERATOR LOCKED ROTOR KVA  
AVAILABLE @ VOLTAGE DIP OF 35%  
Single phase  
34  
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)  
Natural Gas  
(ft3/hr.)  
60  
Propane  
(gal/hr.)  
cu ft/hr  
Exercise cycle  
0.65  
24  
64  
101  
138  
175  
25% of rated load  
50% of rated load  
75% of rated load  
100% of rated load  
161  
253  
345  
437  
1.76  
2.77  
3.79  
4.81  
ENGINE COOLING  
Air flow (inlet air including alternator and combustion air) ft3/min.  
1,528  
System coolant capacity  
Heat rejection to coolant  
Max. operating air temp. on radiator  
Max. ambient temperature  
US gal.  
BTU/hr.  
°C (°F)  
°C (°F)  
2.0  
110,000  
60 (150)  
50 (140)  
COMBUSTION AIR REQUIREMENTS  
Flow at rated power 60 Hz  
cfm  
90  
SOUND EMISSIONS IN DBA  
db(A) @ 23 feet in exercise mode  
db(A) @ 23 feet at normal operating load  
62  
74  
EXHAUST  
Exhaust flow at rated output 60 Hz  
Exhaust temp. at muffler outlet  
cfm  
°F  
249  
1015  
ENGINE PARAMETERS  
Rated synchronous RPM  
HP at rated KW  
60 Hz  
60 Hz  
3600  
45  
POWER ADJUSTMENT FOR AMBIENT CONDITIONS  
Temperature Deration  
3% for every 10 °C above - °C  
1.65% for every 10 °F above - °F  
Altitude Deration  
25  
77  
1% for every 100 m above - m  
3% for every 1000 ft. above - ft.  
183  
600  
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable  
utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1.  
Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuelBtu content, ambient temperature, altitude,  
engine power and condition, etc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTERCONNECTIONS  
Standby 25 kW  
INSTALLATION LAYOUT  
VISE ACTION LATCH,  
ONE PER DOOR, ONE LIFT-OFF  
DOOR PER SIDE OF GENERATOR  
CONTROL PANEL R TYPE  
BATTERY CHARGER IS  
ENCLOSED WITHIN  
62.2  
EXHAUST AND AIR DISCHARGE  
LOUVERS - FRONT AND SIDES  
46  
29  
DOOR TYP  
AUTO  
OFF  
OFF  
ON  
MANUAL  
SET  
EXERCISE  
TIME  
OVER CRANK  
OVER SPEED  
LOW COOLANT LEVEL  
HI COOLANT TEMPERATURE  
LOW OIL PRESSURE  
LOW BATTERY  
LOW FUEL PRESSURE  
SYSTEM READY  
27.4  
DANGER  
High voltage.  
FUSES  
LOCATED  
INSIDE  
Contact with terminals  
may result in personal  
injury or death.  
0F3215  
DOOR  
TYP  
33.5  
6
MIN.  
RIGHT SIDE VIEW  
CONCRETE BASE  
NOT INCLUDED  
FRONT VIEW  
30.7  
FUEL LINE CONNECTION  
3/4" NPT FEMALE COUPLING  
EXHAUST MUFFLERS  
ENCLOSED WITHIN,  
UNIT WEIGHT: Steel 875 lbs.  
®
GENERAC POWER SYSTEMS, INC. • P.O. BOX 297 • WHITEWATER, WI 53190  
Bulletin 0174530SBY / Printed in U.S.A. 05.07  
© 2007 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Baby Furniture PD241547B User Manual
Greenheck Fan Ventilation Hood APEX 200 User Manual
Grizzly Grinder G9928 User Manual
Haier Video Games Y 716 User Manual
Halsey Taylor Indoor Furnishings HRFG ERA User Manual
Hotpoint Refrigerator RLA 21 User Manual
Hotpoint Washer WMYF 862 User Manual
Husqvarna Blower 111750 HCS1372 User Manual
Husqvarna Trimmer 325RDX Series User Manual
Ice O Matic Ice Maker ICE0500 User Manual