Greenheck Fan Ventilation Hood Outdoor Air Ventilator User Manual

Part # 457502  
Installation, Operation and Maintenance Instructions  
for Neutralizer 100% Outdoor Air Ventilators  
WARNING:  
Improper installation, adjustment, alteration, service or maintenance can cause property damage,  
injury or death. Read the installation, operating, and maintenance instructions thoroughly before  
installing or servicing this equipment.  
This manual is the property of the owner, and is required for future maintenance.  
Please leave it with the owner when you complete the job.  
GREENHECK  
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410  
PH. 715-359-6171  
Download from Www.Somanuals.com. All Manuals Search And Download.  
June 1998  
®
Installation Instructions for:  
NV-45 w/Horizontal Discharge  
A -Equip. Support C  
L
441/4"  
Step 1 Mounting the Unit  
Equipment  
Support  
Footprint  
Arrangement HZ can be mounted on a curb  
with an equipment support (see curb inst.) or  
on three equipment supports (figs.1&4).  
Arrangement HZ can also be used for indoor  
applications mounted hanging (fig. 5), inline  
as part of an air handling system, or base  
mounted. Mounting hardware to be provided  
by others.  
C
L
A
A
C
L
(fig.1)  
C
L
In any case, adequate support of the unit is  
required.  
Step 2 Attach Ductwork to Unit Discharge  
Chart and drawing (fig.2) below shows opening size (ID)  
and location for a discharge collar. Also included is the  
recommended straight duct length for optimal  
performance. Greenheck recommends attaching  
ductwork to collar using a rubber duct section at the  
unit to eliminate vibration.  
Step 3 Attach Ductwork to Unit Intake  
For non-weatherhood installations, fig. 3 below shows  
dimensions for supply opening (ID). Attach ductwork to  
perimeter flange using a rubber duct section at the unit  
to eliminate vibration. Design the remaining ductwork  
for minimal losses to allow the unit to operate properly.  
16  
48  
23  
Recommended Duct Size/Location  
and Intake Dimensions  
Minimum Straight Duct Length - 54”  
43  
16  
12  
(fig.2)  
(fig.3)  
Typical Installations  
DISCHARGE  
DISCHARGE  
INT  
AKE  
INT  
AKE  
(fig.4)  
(fig.5)  
Roof mounted arrangement HZ  
with weatherhood, mounted on three equipment supports.  
Ductwork is attached to discharge collar with rubber  
boot transition.  
Arrangement HZ shown as an indoor  
hanging installation with intake and  
discharge ductwork installed.  
(Hanging support structure for unit is by others).  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Instructions for:  
NV-45 w/Downblast Discharge  
Before beginning this installation:  
Step 1 Roof Opening  
Make sure that there is room to access the unit from all sides.  
Make sure inlet of unit is located well away from any exhaust fans.  
Determine the center of the supply duct roof  
opening. The chart below shows the maximum  
recommended roof opening dimensions. These  
sizes can be smaller based on codes and  
ductwork sizes.  
For Installations using rectangular curb  
Roof  
Opening  
A
Rectangular  
Curb  
Footprint  
A/2  
A - Max Roof Open. Sq.  
Supply Duct C to  
47"  
L
B -  
881/2"  
Equip. Support C  
L
C*  
A
C*  
A/2  
C*  
C
L
B
C
L
*C- Determine equal dimension for these 3 locations  
C
L
Step 2 Install Roof Curb and  
Equipment Support  
For rectangular curbs, center curb on 3 sides of roof opening, as shown in above installation diagram, by  
determining C dimension (varies per unit/curb size). For either installation, level the curb and shim if necessary.  
Attach curb to roof and flash in place.  
If equipment support is needed, refer to chart in step 1 for dimensional location based on NV unit size. Attach to  
roof in the same manner as the curb. Remove metal cover, flash to wooden nailer, and reinstall cover.  
Step 3 Install Ductwork  
Recommended Supply  
Ductwork Sizes  
The chart shows at left shows the duct  
sizes and straight lengths recommended  
Straight  
Duct  
Size  
Duct  
for optimal performance (AMCA Publication  
201-90). Using duct sizes less then  
recommended lengths will affect fan  
performance. Good duct installation  
practices should be followed for the  
remaining ductwork. The use of a duct  
adapter with the supply duct is strongly  
recommended to properly align the  
ductwork with the supply fan discharge.  
The duct adaptor is only a guide and is not  
intended to be used as support for the  
ductwork.  
Length  
Supply  
Ductwork  
by Others  
16 x 16  
54"  
Duct Adaptor  
Ductwork  
Sealant  
Step 4 Apply Sealant  
Before installing unit apply a sealant or a  
gasket around the perimeter of the supply  
duct adaptor to isolate the fan and  
minimize vibration.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Step 5 Install Supply Unit  
Use a crane and a spreader bar  
hooked to the factory lifting lugs  
(as shown in the diagram) to lift  
and center the NV unit on the  
curb and equipment support. Use  
self-tapping sheet metal screws  
to fasten unit to the curb and  
equipment support through holes  
provided.  
Lifting Lugs  
(4 places)  
Model TSU  
Supply Unit  
Electrical and pipes connections  
can be made at this time.  
Complete Installation  
Illustration shows the complete  
installation of downblast NV with  
filter section and weatherhood.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
GREENHECK  
Installation Instructions for:  
SLAB, RAIL, AND CURB MOUNTING  
NV-90 and NV-120  
®
w/Horizontal Discharge  
Before beginning this installation:  
Make sure that there is room to access the unit from all sides.  
Make sure inlet of unit is located well away from any  
exhaust fans.  
1a. Slab Construction  
Recommended Size: 1ft. wider and  
longer than total unit size.  
Recommended Material: Concrete at  
least 4" thick.  
Slab should be set and leveled on a  
sufficient bed of gravel for proper  
drainage.  
Spreader Bar  
1b. Install Unit  
Use a crane and spreader bar to  
prevent damage to unit. Lifting lugs are  
provided as shown in illustration.  
Its is highly recommended that all  
accessory items be lifted separately  
and attached after the NV unit is in  
place.  
NV Unit  
Intake  
Unit may be fastened to slab through  
lifting lugs.  
Lifting Lugs (4)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. Rail Mounting  
Rails extends 6" from  
discharge end of unit  
Rails located 6-12" in  
from sides of unit.  
For proper support, rails should be located  
6-12" in from sides of unit and should  
extend at least 6" beyond both discharge  
end of unit and filter section.  
Rails extend 6" from  
end of filter section  
Spreader Bar  
3. Curb Mounting  
(See page 9 for curb assembly)  
Install unit on curb using a crane and  
spreader bar to prevent damage to unit.  
Lifting lugs are provided as shown in  
illustration.  
It is highly recommended that all accessory  
items be lifted separately and attached  
after the unit is set in place.  
Lifting Lugs (4)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Optional Up-stream Heating Coil  
If an optional up-stream heating coil is provided with the unit an additional equipment support may be required. If  
filters only are provided in this section, additional support is not needed. Follow the guidelines below for  
requirements.  
Slab/Rail Mount  
Curb Mount  
Curb Height  
Equipment Support Requirements:  
NV-90  
None  
12”  
NV-120  
Curb Height + 12”  
Coil Section  
Typical NV-120 installation  
on cement slab with  
optional up-stream heating  
coil section .  
See page 10 for attachment  
instructions.  
Equipment Support  
Cement Slab  
5. Attach Ductwork to Unit Discharge  
Chart and drawing below show opening size (ID) and location for discharge collar. Also included is the  
recommended straight duct lengths for optimal performance. Greenheck recommends attaching  
ductwork using a rubber duct section at the unit to eliminate vibration.  
D
C
Discharge Opening Sizes  
Straight  
Duct Length  
A
B
C
D
B
A
NV-90 161/4 24 34 1/2 223/8  
NV-120 161/4 251/2 34 231/4  
81  
96  
Back View  
NV-90 and NV-120  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Instructions for:  
CURB MOUNTING*  
NV-90 and NV-120  
*For installations using Greenheck's  
optional roof curb.  
1. Assemble Roof Curb  
Curbs are shipped knockdown and require assembly  
by others. Assembly instructions are also included  
with curb.  
Assemble curb sections as shown using hex bolts and  
lock nuts supplied with curb.  
Detail shown is typical for all four corners.  
Roof Curb  
41/2  
241/4  
2. Locate and Cut Roof Opening  
When locating unit, make sure there is room to access unit  
from all sides. Make sure inlet of this unit is located well  
away from exhaust fans.  
Recommended  
405/8  
Roof Opening  
(36"x36")  
Roof Opening for NV-120 and NV-90 = (A) 36" x (B) 36"  
1031/2  
3. Install Curb  
Located curb over roof opening with dimensions shown to  
the right and fasten in place.  
431/4  
Check that diagonal dimensions are within  
1/8" of each other and adjust as necessary. Shim as  
required to level.  
3
81 /16  
A
B
4. Install Ductwork  
D
The following chart shows the duct sizes and straight  
lengths recommended for optimal performance (AMCA  
Publication 201-90). Using duct sizes less than  
recommended lengths will affect fan performance. Good  
duct installation practices should be followed for the  
remaining ductwork.  
Roof Opening  
Ductwork  
by Others  
C
Roof Curb  
Duct Locations:  
Straight  
Duct Length  
A
B
C
D
NV-90  
24  
93/8  
91/2  
24 301/4  
26 291/4  
81  
96  
NV-120 26  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5. Install Unit.  
Use a crane and spreader bar to prevent damage  
to unit. Lifting lugs are provided as shown in  
illustration.  
It is highly recommended that all accessory items  
be lifted separately and attached after the unit is  
in place.  
Electrical and pipe connections can be made at  
this time.  
6. Attach Filter/Coil Section (if included)  
Use a crane and spreader bar hooked to factory  
lifting lugs (as shown in diagram) to lift and center the filter section on the NV unit. Note that the top U-  
shaped flange on the filter section fits over the vertical flange of the NV unit (see detail A). Use sheet metal  
screws to fasten the filter section to NV unit. Mounting holes are prepunched, see diagram for approximate  
hole locations.  
Filters ship separately. To install, remove side panel on filter section and slide into filter channels. Note  
arrows on filters for correct orientation.  
Note:  
If the optional up-stream heating coil  
section is included with the unit, special  
Spreader Bar  
support for this section is required. See  
page 8 for requirements.  
Lifting Lugs (2)  
Detail A  
Filter /Coil section fastener locations  
typical for entire section.  
Top fasteners are accessed from  
outside, side fasteners are accessed  
from inside, bottom fasteners are  
accessed from underneath filter section  
(Note: bottom fasteners are not required  
for slab mounted units).  
Fasten through  
both flanges.  
KSU Unit  
Filter/Coil Section  
Butt units together  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7. Attach Weatherhood  
Use a crane and spreader bar hooked  
to factory lifting lugs (as shown in  
diagram) to lift and center the  
weatherhood on the filter section (same  
procedure as shown in previous step).  
If there is no filter section, the  
weatherhood attaches directly to NV  
unit in same manner. Fastener  
instructions are same as Step 6.  
Spreader Bar  
Lifting Lugs (2)  
8. Attach Support Legs  
Support Legs are required  
Weatherhood fastener locations  
typical for entire section.  
Top fasteners are accessed from  
outside, side and bottom fasteners  
are accessed from inside.  
on weatherhood section.  
Attach through pre-  
punched holes in  
weatherhood using  
supplied fasteners.  
Support Legs (2)  
9. Install Birdscreen or Optional Weatherhood Filters  
Birdscreens simply slide up and into  
opening, resting on channels. Install side  
screens first and slide to edges of unit.  
Install center screen last. No fasteners  
are required.  
Install 1st-  
slide to side  
Install 2nd-  
slide to side  
Install last  
Filters simply side down into filter tracks  
as shown. No fasteners are required.  
Note arrows on filters for correct airflow.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Instructions  
Before connecting power to the unit, read and  
CAUTION !  
understand the following instructions and  
wiring diagrams. Complete wiring diagrams  
are attached inside the door(s) of the unit.  
If any of the original wire must be replaced,  
the replacement wire must have a temperature  
rating of at least 105°C, except for energy cut-off  
or sensor lead wire which must be 150°C.  
All wiring should be done in accordance with  
the National Electrical Code ANSI/NFPA 70-  
latest edition and any local codes that may  
apply. In Canada, wiring should be done in  
accordance with the Canadian Electrical  
Code. The equipment must be properly  
grounded.  
DANGER !  
High voltage electrical input is needed for this  
equipment. This work should be performed by a  
qualified electrician.  
Electrical Controls Door  
Electrical Location  
Electrical Power  
Connection  
Electrical Power Connection  
Electrical Controls Door  
NV-45  
NV-90-120  
NOTE: Any wiring running through the NV unit in the airstream must be protected by  
flexible metal conduit, metal clad cable, or raceways.  
Sequence for wiring NV unit:  
For units without control centers:  
The motor nameplate is to be used for determining the voltage and amperage required by  
the unit.  
For units with control centers:  
1. The unit’s nameplate states the voltage and total amperage required.  
The main feeder supplying power to the unit should be sized for the label’s voltage and amperage.  
2. The main power line should be connected to the disconnect switch.  
Make sure that the disconnect lugs are securely tightened.  
3. Connect control panel wiring to terminal strip in the control center.  
Greenheck’s standard control voltage is 120/60/1.  
4. When an optional convenience outlet is provided, a separate power supply must be provided to  
the receptacle. This circuit must be on a ground fault breaker.  
CAUTION  
Any wiring deviations may result in personal injury or property damage. Greenheck is not  
responsible for any damage to, or failure of the NV unit caused by incorrect final wiring.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SYSTEM STARTUP  
For proper unit function and safety, follow everything in this startup procedure in the order presented. This is to  
be done after the electrical connections are complete.  
• Voltage meter  
• Incline manometer or equivalent  
Special Tools Required • Tachometer  
• Thermometer  
• Amperage meter  
1. Check Voltage  
Before starting the unit compare the supplied voltage with the unit’s nameplate voltage and the motor  
voltage.  
2. Check Blower Rotation  
First hand rotate the blower to ensure that the wheel is not rubbing against  
the scroll. If the blower is rotating in the wrong direction, the unit will move  
Blower  
Housing  
some air but not perform properly. To check the rotation, open the blower  
access door and run the blower momentarily to determine the rotation. To  
reverse the rotation, turn the power off and use the following procedure:  
• For single phase units, rewire the motor per the instructions on  
the motor.  
• For three phase units, interchange any two power leads.  
This can be done at the motor starter.  
3. Air Volume Check and Measurement  
Along with the building balance, the units air volume (cfm) should be measured and compared with its rated air  
volume. This unit is flexible for varying air volume (units above 15 Hp may have fixed drives), but the actual air  
volume should be known for making final adjustments.  
The most accurate way to measure the air volume is by using the pitot traverse method in the ductwork away  
from the blower. Other methods can be used but should be proven and accurate.  
To adjust the air volume, change the fan RPM or the system losses. See Trouble Shooting Section in this  
guide.  
4. Measure Motor Voltage, Amperage and Fan RPM  
All access doors must be installed except the control center door. Measure and record the input voltage and  
motor amperage(s).  
To measure the fan RPM, the blower door will need to be removed. Minimize measurement time because the  
motor may over amp with the door removed.  
With blower door in place compare measured amps to the motor nameplate full load amps and correct if  
overamping. See the trouble shooting section in this guide.  
5. Settings for Optional Components  
Freeze Protection:  
This de-energizes the blower if the output temperature is below the set point. A timer allows the blower to  
operate during startup. This will reset when turned off.  
Typical settings are:  
°
Discharge temperature = 35 F  
Timer = 5 minutes  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Instructions for Coils  
Steam Coils  
Application Recommendations:  
Satisfactory operation and service life are best ensured when coils are installed with proper piping, trap, and  
and operation.  
General:  
1. Provide separate supports and hangers for the unit and the piping.  
2. Be certain that adequate piping flexibility is provided. Stresses resulting form expansion of closely  
coupled piping and coil arrangement can cause serious damage.  
3. Standard steam coils are pitched in the casings when installed for horizontal air flow. The CASING MUST  
BE LEVEL after the unit is installed for proper condensate drainage. If condensate is not removed the coil  
will suffer from water hammering and will have a shortened life. On vertical air flow applications, the coils  
must be pitched when installed.  
4. Do not reduce pipe size at the coil return connection. Carry return connection size through the dirt pocket,  
making the reduction at the branch leading to the trap.  
5. It is recommended that vacuum breakers be installed on all applications to prevent retaining condensate  
in the coil. Generally, the vacuum breaker is to be connected between the coil inlet and the return main.  
The vacuum breaker should be open to the atmosphere and the trap design should allow venting of large  
quantities of air.  
6. Do not drip supply mains through the coil.  
7. Do not attempt to lift condensate when using modulating or on-off control.  
8. Do not reduce the pipe size leaving the coil.  
Traps:  
1. Size traps in accordance with the manufacturer’s recommendations. Be certain that the required pressure  
differential will always be available. DO NOT UNDERSIZE.  
2. Float and thermostatic or bucket traps are recommended for low pressure steam. On high pressure  
systems, bucket traps are normally recommended. The thermostatic traps should be used only for air  
venting.  
3. Bucket traps are recommended for use with on-off control only.  
4. Locate traps at least 12 inches below the coil return connection.  
Controls:  
1. On high pressure installations, a two-position steam valve with a face and bypass  
arrangement is preferred where modulating control is required.  
2. Modulating valves must be size properly. DO NOT UNDERSIZE.  
o
Freezing Conditions (Entering air below 35 F):  
1. 5 PSI steam must be supplied to the coil at all times.  
2. Provision should always be made to thoroughly mix fresh air and return air before it enters the coil on  
return air units. Also, temperature control elements must be properly located to obtain true air mixture  
temperatures.  
3. As additional protection against freeze-up, the trap should be installed sufficiently far below the coil to  
provide an adequate hydrostatic head to ensure removal of condensate during an interruption in the steam  
pressure. Estimate 3 feet for each 1 PSI of trap differential required.  
4. On start up, admit steam to coil ten minutes before admitting outdoor air.  
5. Provision must be made to close fresh air dampers if steam supply pressure falls below minimum  
specified.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Gate Valve  
Control Valve, Modulating  
Two-Position  
Check Valve-Vacuum Breaker  
Float and Thermostat Trap  
Strainer  
Greenheck does not  
supply coil controls, all  
control elements shown  
are supplied by others.  
Retur  
n Main  
Figure 1  
Recommended Steam Coil Piping  
Direct Expansion Coils  
Application Recommendations:  
1. Piping should be in accordance with accepted industry standards.  
2. The condensate drain pipe should be sized adequately to ensure the condensate  
drains properly. The bottom of the drain pan should be twice the distance of the internal static pressure  
water column above the exit of the trap.  
3. When connecting suction and liquid connections make sure the coil is free from all foreign material. Make  
sure all joints are tight and free of leakage.  
4. Greenheck does not supply compressor or condensing units, for further instruction on DX coil installation  
and operation contact your compressor and/or condenser manufacturer.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Water Coils  
Application Recommendations:  
1. Piping should be in accordance with accepted industry standards.  
2. Connect the WATER SUPPLY TO THE BOTTOM CONNECTION on the air leaving side and the WATER  
RETURN TO THE TOP CONNECTION on the air entering side. The extra bottom connection can be used for  
an auxiliary manual drain connection, and the extra top connection can be used for an automatic air vent or  
the extra connections can be capped. Connecting the supply and/or return in any other manner will result  
in very poor performance.  
3. The air vent at the uppermost point should be temporarily opened during system start-up to release all  
of the air from the coil. To maintain heat transfer capacity, periodically vent any air in coil.  
4. Water coils are not normally recommended for use with entering air temperatures below 40oF; however,  
special high pressure water coils have been used successfully on high temperature hot water jobs with low  
entering air temperatures when correctly controlled. No control system can be depended on to be 100%  
safe against freeze-up with water coils. Glycol solutions or brines are the only safe media for operation of  
water coils with low entering air conditions.  
5. When fresh and return air are to be heated by a hot water coil, care should be used in the design of the  
duct work to ensure thorough mixing before the air enters the coil. The return air should always enter the  
bottom of the duct and the fresh air should enter the top of the duct. The greater the distance between the  
mixing point and the entrance to the coil, the better the application. Temperature control elements should  
be located to sense the lowest temperature air that will enter the coil. Always install gasketed fresh air  
dampers which are automatically controlled to close whenever the water leaving the coil is too cool, or the  
fan stops. Care should be used in designing fresh air intake to prevent stack effect (or wind) from forcing  
cold air through the coils when the fan is shut down. Two sets of dampers are frequently required.  
CONTINUOUS WATER CIRCULATION THROUGH THE COIL AT ALL TIMES IS HIGHLY RECOMMENDED.  
6. Pipe sizes for the system must be selected on the basis of the head (pressure) available from the  
circulation pump. The velocity should not exceed 8 feet per second and the friction loss should be  
approximately 3 feet of water column per 100 feet of pipe.  
7. For chilled water coils, the condensate drain pipe should be sized adequately to ensure the condensate  
drains properly.  
Coil Maintenance  
Filters:  
Filters upstream of the coil should be checked regularly for dirtiness and clogging. If the filters are dirty, they  
should be cleaned or replaced. It is important that the coils stay clean to maintain maximum heat transfer  
capability.  
WARNING: Biological Hazard! All drain pans and coils should be cleaned on a regular  
schedule by qualified personnel to prevent the growth of bacteria.  
Cleaning:  
1. Coils must be clean to obtain maximum performance. Soiled fins reduce the capacity of the coil, demand  
more energy from the fan, and create a medium for order and bacteria to grow and spread through the  
conditioned zone. High pressure water (700 Psi or less) may be used to clean coils with fin thickness over  
.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the fins will  
withstand the spray pressure. For coils with fragile fins or high fin density, foaming chemical sprays and  
washes air available. Many coil cleaners contain harsh chemicals, so they must be used with caution by  
qualified personnel only. Care must be taken not to damage the coils. FINS ARE SHARP! Use caution when  
working with coils.  
2. Drain pans in any air conditioning unit will contain moisture; therefore, algae and other organisms will grow  
due to airborne spores and bacteria. Scheduled cleaning is necessary to prevent build-up from clogging the  
drain. The drain pans should also be kept clean to prevent growth of bacteria and the spread of disease.  
Winterizing Coils:  
During any extended down time, all water should be drained from the coil. The coil should then be thoroughly  
flushed with a glycol solution to prevent freeze damage.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLE SHOOTING  
Blower Unit  
Symptom  
Possible Cause  
Corrective Action  
Blower fails  
to operate  
Blown fuse or open circuit breaker  
Replace fuse or reset circuit breaker and  
check amps  
Broken fan belt  
Replace  
Defective motor or capacitor  
Motor starter overloaded  
CFMs too high  
Replace  
Reset starter and check amps  
Check CFMs and adjust drives if needed  
Motor overamps  
Static pressures are higher or lower  
than design  
If higher, ductwork should be improved  
If lower, fan RPMs should be lower  
Blower rotation is incorrect  
Motor voltage incorrect  
Motor horsepower too low  
Check rotation and correct  
Check motor nameplate and supplied voltage  
See specifications and catalog for fan  
curves to determine if horsepower is sufficient.  
Shorted windings in motor  
Unit damper not fully open  
Replace motor.  
Insufficient airflow  
Adjust damper linkage or replace  
damper motor  
System static pressure too high  
Blower speed too low  
Improve ductwork to eliminate losses  
using good duct practices  
Check for correct drives and RPMs  
with catalog data  
Dampers or registers closed.  
Dirty or clogged filters  
Leaks in ductwork.  
Open and adjust  
Clean or replace  
Repair  
Elbows, or other obstructions  
may restrict fan outlet.  
Correct or improve ductwork  
Belt slippage  
Adjust belt tension  
Too much airflow  
Blower fan speed too high  
Filter(s) not in place.  
Check for correct fan RPM  
Install filters  
Insufficient static pressure (SP)  
(airflow resistance)  
Induce SP into system ductwork.  
Excessive noise  
or vibration  
Wheel rubbing on housing  
Loose wheel on shaft  
Loose motor or blower sheave  
Belts too loose  
Center wheel  
Tighten wheel setscrew  
Tighten sheave setscrew  
Adjust belt tension after 24 hours  
of operation  
Belts too tight  
Loosen to maintain 3/8” deflection  
per ft. of span between sheaves  
Worn belt  
Replace  
Motor base or blower loose  
Worn bearings  
Tighten mountings bolts  
Replace  
Bearing and drive alignment  
Motor out of balance  
Realign  
Replace  
Wheel out of balance  
Replace or rebalance  
Replace or rebalance  
Clean wheel and housing  
Sheaves eccentric or out of balance  
Accumulation of material on wheel  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Dimensions and Weights  
Optional Filters  
30  
128  
NV-45  
1680 lbs  
NV-45 w/Heating Coil  
NV-90  
1780 lbs  
46  
2650 lbs  
NV-120  
3150 lbs  
2870 lbs  
3370 lbs  
NV-90 w/Heating Coil  
NV-120 w/Heating Coil  
Optional Weatherhood  
Optional Motorized  
Damper  
ELEVATION VIEW  
NV-90/120  
Weatherhood  
250 lbs  
NV-90/120  
Filter Section  
200 lbs  
52  
NV-90/120  
Filter Section w/Coil  
420 lbs  
Optional Heating Coil  
Motor Control  
Center  
Optional  
Heating Coil  
Heat Pipe  
PLAN VIEW  
Cooling Coil  
461/4  
Optional Inlet  
Damper  
88  
17  
501/2 (NV-90)  
62 (NV-120)  
501/2  
Optional  
Weatherhood  
ELEVATION VIEW  
Optional  
Optional Curb  
or Support  
Blower/Motor  
Access Door  
Cooling Coil  
Optional Heating Coil  
Filter/Heating  
Section  
Motor  
Control  
Center  
1101/2  
Heat Pipe  
PLAN VIEW  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
 
Maintenance  
Greenheck recommends these procedures to insure trouble free operation of this unit. Most unit failures can be  
attributed to poor setup or poor maintenance.  
A record of maintenance performed on this unit should be kept. This information will provide essential information  
if problems are encountered. A section at the back of this manual is provided for recording the unit's maintenance  
history.  
Motor  
CAUTION: When performing any maintenance on this  
unit be sure that the power is disconnected and cannot  
Blower  
Housing  
be accidently turned on. The control center disconnect  
can be locked in the off position .  
Belt Tension  
Too Tight  
Adjustment  
Screw  
2 weeks after startup  
Too Loose  
Check belt tension - Belts tend to stretch after a period of  
time. They should be periodically checked for wear and  
3
tightness. Approximately /8" of deflection per ft. of span  
between sheaves is standard for belt tightness. When  
replacing belts, use the same type as supplied with the unit.  
Matched belts should always be used on units with  
multigroove pulleys.  
NOTE: For motors of 1 HP or less a smaller sliding base  
bracket is used to attach to blower.  
Replacement of belts - should be accomplished by loosening the tensioning device to the point where the belts  
can be removed by hand. Do not force belts on or off as this may cause breakage of cords leading to premature  
belt failure. Belts should be adjusted as shown above.  
Every 3 Months  
The filter in the unit should be inspected at least every 3 months. Depending on the environment filters could  
require changing or cleaning more or less often. The filters can be slid out of either side of the unit.  
If washable filters are installed, they can be washed in warm soapy water. An adhesive spray can be applied to  
increase filter efficiency.  
If disposable filters are installed, check by holding up to a light source. If light cannot pass through the filter, it  
should be replaced. Replacement filters should be of the same manufacturer and size.  
When reinstalling filters, be sure to install with the airflow in the correct direction indicated on the filter and with  
any factory spacers that came with the unit.  
Yearly  
All bearings on units 108 to 118 are permanently lubricated and require no further lubrication under normal use.  
Normal use being considered -20°F to 120°F and in a relatively clean environment. Units from sizes 120 to 220  
should be checked monthly for lubrication.  
Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be limited  
to the exterior surfaces only. Removing dust and grease buildup on motor housing assures proper motor cooling.  
Greasing of motors is intended only when grease fittings are provided. Many fractional motors are permanently  
lubricated and require no further lubrication. Motors supplied with grease fittings should be greased in  
accordance with manufacturer's recommendations. When motor temperature does not exceed 104°F (40°C), the  
grease should be replaced after 2000 hours of running time as a general rule.  
Wheels require very little attention when moving clean air. Occasionally oil and dust may accumulate on the wheel  
causing imbalance. When this occurs the wheel and housing should be cleaned to assure smooth and safe  
operation.  
Routinely check all fasteners for tightness.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance Documentation  
Job Information  
Job Name:________________________________________  
Address: _________________________________________  
City: ________________ State: ________ Zip: __________  
Phone: __________________ Fax: ____________________  
Contact Person:___________________________________  
Service Organization: ______________________________  
Address: _________________________________________  
City: ________________ State: ________ Zip: __________  
Phone: __________________ Fax: ____________________  
Work Done By: ____________________________________  
Name Plate Information  
Model: ___________________________________________  
Volts: ___________ Hertz: __________ Phase:__________  
Amps: __________________ Mark: ___________________  
Supply Hp: _______________________________________  
Serial Number: ____________________________________  
Field Start-Up Documentation  
Actual Voltage:  
Hertz:  
Phase:  
Motor Voltage:  
Motor Amperage:  
Fan RPM:  
Actual Amperage:  
Blower Rotation Correct  
Air Volume Design  
Actual  
CFM  
CFM  
Maintenance  
Date  
Time  
Notes:  
NV-IOM-R  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

Graco Automobile Parts 3A1323C User Manual
Haier Flat Panel Television LEC19B1320 User Manual
Hamilton Beach Blender 54615 User Manual
Hamilton Sundstrand Company Flat Panel Television SD 2006 02 User Manual
Hasselblad Power Supply Flextight 343 User Manual
HP Hewlett Packard All in One Printer 7130 printer User Manual
HP Hewlett Packard Stereo System HP 35660A User Manual
Huawei Cell Phone U8300 User Manual
Huffy Fitness Equipment M732211 User Manual
Husqvarna Lawn Mower 11 13 H User Manual