| 	
		 PN 452413   
					® 
					Canopy Type Kitchen Hoods   
					Installation, Operation and Maintenance Manual   
					Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the   
					product described. Protect yourself and others by observing all safety information. Failure to comply with instructions   
					could result in personal injury and/or property damage! Retain instructions for future reference.   
					Please record the Serial, Model #, and Mark for the hood and other equipment for future reference.   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Serial #: _______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Model #: ______________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Mark: _________________   
					Canopy Hood   
					1 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Table of Contents   
					Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32   
					Grease Grabber™ Cleaning and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 - 34   
					Filter Cleaning Frequency Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35   
					Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 - 37   
					Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 - 39   
					Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40   
					Canopy Hood   
					3 
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Receiving and Handling   
					Upon receiving the equipment, check for both obvious and hidden damage. If damage is found, record all   
					necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of   
					the shipment, including accessories, are accounted for.   
					STORAGE   
					If a kitchen hood must be stored prior to installation it must be protected from dirt and moisture. Indoor storage   
					is recommended. For outdoor storage, cover the hood with a tarp to keep it clean, dry, and protected from UV   
					(Ultra Violet) Radiation damage.   
					Improper storage which results in damage to the unit will void the warranty.   
					HOOD DEPTH (MULTIPLY BY LENGTH) FOR HOOD WEIGHT   
					HOOD   
					MODEL   
					3 ft.   
					3.5 ft   
					4 ft   
					4.5 ft   
					5 ft   
					5.5 ft   
					6.5 ft   
					7 ft   
					7.5 ft   
					6 ft   
					1.8288 m   
					.914 m   
					30 lbs/ ft.   
					1.067 m 1.2192 m 1.3716 m 1.524 m 1.6764 m   
					1.9812 m 2.1336 m 2.286 m   
					32 lbs/ft   
					35 lbs/ft   
					38 lbs/ft   
					40 lbs/ft   
					GH, GK,   
					GXEW   
					44.64   
					kg/m   
					47.62   
					kg/m   
					52.08   
					kg/m   
					56.54   
					kg/m   
					59.52   
					kg/m   
					36 lbs/ft   
					38 lbs/ft   
					41 lbs/ft   
					44 lbs/ft   
					46 lbs/ft   
					GH, GX,   
					GXDW   
					53.57   
					kg/m   
					56.44   
					kg/m   
					61.01   
					kg/m   
					65.47   
					kg/m   
					68.45   
					kg/m   
					40 lbs/ft   
					44 lbs/ft   
					48 lbs/ft   
					52 lbs/ft   
					GH, GK,   
					GXFW   
					59.52   
					kg/m   
					65.47   
					kg/m   
					71.42   
					kg/m   
					77.38   
					kg/m   
					48 lbs/ft   
					51 lbs/ft   
					54 lbs/ft   
					57 lbs/ft   
					GH, GK,   
					GXCW   
					71.42   
					kg/m   
					71.89   
					kg/m   
					81.35   
					kg/m   
					84.82   
					kg/m   
					44 lbs/ft   
					48 lbs/ft   
					52 lbs/ft   
					56 lbs/ft   
					GH, GK,   
					GXSW   
					65.47   
					kg/m   
					71.42   
					kg/m   
					77.38   
					kg/m   
					83.33   
					kg/m   
					39 lbs/ft   
					41 lbs/ft   
					44 lbs/ft   
					47 lbs/ft   
					49 lbs/ft   
					GGEW   
					GGDW   
					GGFW   
					GGCW   
					GGSW   
					58.03   
					kg/m   
					61.01   
					kg/m   
					65.47   
					kg/m   
					69.94   
					kg/m   
					72.91   
					kg/m   
					45 lbs/ft   
					47 lbs/ft   
					50 lbs/ft   
					53 lbs/ft   
					55 lbs/ft   
					66.96   
					kg/m   
					69.94   
					kg/m   
					74.40   
					kg/m   
					78.86   
					kg/m   
					81.84   
					kg/m   
					49 lbs/ft   
					53 lbs/ft   
					57 lbs/ft   
					61 lbs/ft   
					72.91   
					kg/m   
					78.86   
					kg/m   
					84.82   
					kg/m   
					90.77   
					kg/m   
					57 lbs/ft   
					60 lb/ft   
					63 lbs/ft   
					66 lbs/ft   
					84.82   
					kg/m   
					89.28   
					kg/m   
					93.74   
					kg/m   
					98.21   
					kg/m   
					53 lbs/ft   
					57 lbs/ft   
					61 lbs/ft   
					65 lbs/ft   
					78.86   
					kg/m   
					84.82   
					kg/m   
					90.77   
					kg/m   
					96.72   
					kg/m   
					52 lbs/ft   
					54 lbs/ft   
					56 lbs/ft   
					58 lbs/ft   
					61 lbs/ft   
					63 lbs/ft   
					GH, GK,   
					GXEV   
					77.38   
					kg/m   
					81.35   
					kg/m   
					83.33   
					kg/m   
					86.30   
					kg/m   
					90.77   
					kg/m   
					93.74   
					kg/m   
					61 lbs/ft   
					66 lbs/ft   
					68 lbs/ft   
					72 lbs/ft   
					75 lbs/ft   
					79 lbs/ft   
					GH, GK,   
					GXFV   
					90.77   
					kg/m   
					98.21   
					kg/m   
					101.18   
					kg/m   
					107.14   
					kg/m   
					111.6   
					kg/m   
					117.55   
					kg/m   
					81 lbs/ft   
					84 lbs/ft   
					87 lbs/ft   
					90 lbs/ft   
					GH, GK,   
					GXCV   
					120.53   
					kg/m   
					124.99   
					kg/m   
					129.46   
					kg/m   
					133.92   
					kg/m   
					66 lbs/ft   
					69 lbs/ft   
					72 lbs/ft   
					76 lbs/ft   
					79 lbs/ft   
					GH, GK,   
					GXSV   
					98.21   
					kg/m   
					102.67   
					kg/m   
					107.14   
					kg/m   
					113.09   
					kg/m   
					117.55   
					kg/m   
					Canopy Hood   
					4 
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation   
					NOTE: If you have a Back   
					Supply Plenum (BSP), this must   
					be installed before the hood.   
					Please see Page 10.   
					Fig. 1   
					For Wall/Single Island Style   
					Hoods, prior to installation,   
					check with local authorities   
					having jurisdiction on clearances   
					to combustible surfaces, etc.   
					Bottom   
					With the hood still inside its   
					packing crate, position the unit   
					beneath its installation location.   
					Carefully remove the packing   
					crate. Place some protective   
					material on the floor next to   
					Pallet   
					Protective Material   
					the crate to avoid damaging the hood as it is tipped on its side; Fig. 1. Tip the hood carefully onto the   
					protective material. If you have filler panels, install them now; Fig. 2. If you have integral filler panels,   
					no additional installation is needed.   
					Hood Installation Overview   
					If a Back Supply Plenum is provided, install first. Before raising hood, insert 1/2 in. (12.7 mm) diameter   
					threaded rod (by others) into hanger brackets on hood top. Check the engineering drawings or UL   
					label located on the inside of the hood for proper hood height above finished floor. Install filler panels   
					if needed. Raise and hang hood from adequate roof or ceiling supports All hanger brackets must be   
					used and the hood must be properly supported while lifting to prevent damage or distortion to the   
					hood. The hood must be hung level to operate properly. After hood is secured, make the exhaust duct   
					connections. The fire system distributor must be contacted at this time. After the fire system has been   
					installed, mount the enclosures, then the supply plenums. If an Horizontal Supply Plenum is provided,   
					it should be installed before the enclosures. The hood and accessories are now installed. Finally, make   
					the electrical connections from switches to fans and complete the fire system circuits as required by   
					the job specification.   
					Filler Panel Installation Instructions   
					1. Uncrate the hood and lay it on the floor   
					HOOD   
					with protective material between the hood   
					and the floor. (Fig. 1)   
					2. Bolt the filler panels together with 5/16 in.   
					HOOD   
					bolts provided in the hardware package.   
					HOOD   
					3. Position the filler panels to the hood back,   
					and tack-weld them into place. (Fig. 2)   
					T A CK-WELDED TO   
					HOOD BACK   
					4. To allow for ease of cleaning, caulk   
					the external seams with NSF Approved   
					5/16 IN. X 3/4 IN. BOL T S   
					WITH WASHERS & NUTS   
					RIGHT FILLER P A NEL   
					silicone caulk (GE SCS1009, or its   
					equivalent). The caulk is not provided.   
					BOTTOM FILLER P A NEL   
					Fig. 2   
					Canopy Hood   
					5 
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Hood Hanging Height   
					The hood hanging height is critical, hanging the hood at the incorrect height may significantly reduce   
					the ability for the hood to function properly and may be in violation of codes. The hood hanging height   
					(typically, 78 in. (198.12 cm) above the finished floor) is given on the UL label located on the inside of   
					the hood on the end panel. The hood must be hung level to operate properly. The grease trough is   
					pitched to drain into the grease container.   
					Double Island Style Hoods   
					Before hanging the hoods, please verify the hood marks to make sure the correct hood is   
					hung on the correct side.   
					A double island hood is created by installing two wall style hoods back to back. Use the installation   
					procedure described on page 5 for single island hoods; install and level both hoods. After leveling,   
					secure the hoods together by tack-welding and/or bolting the rear mounting brackets. Caulk this joint   
					with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.   
					Continuous Capture Plenum Hoods   
					Remove the support angles on the open end panels. (see   
					Fig. 3   
					Fig. 3) Use the installation procedure described on page   
					4 for single island hoods; install and level both hoods.   
					After leveling, secure the hoods together by tack-welding   
					and/or bolting the top angles. Fasten the hoods together   
					using u-clips and bolts, (see Fig. 4). Caulk this joint   
					with NSF Approved silicone caulk (GE SCS1009 or its   
					HOOD FRONT   
					HOOD   
					equivalent). The caulk is not provided.   
					CAULK   
					BOLT   
					ACORN NUT   
					U-CLIP   
					Fig. 4   
					Installing U-Channel Strip   
					1. After the hood is hung in position and   
					leveled, apply caulk to the inside edge   
					of the double island clip. (Fig. 5)   
					Fig. 5   
					2. Position and install the clip by tapping   
					into position along clip (friction fit).   
					3. Caulk edges to seal out grease and   
					allow for ease of cleaning. Caulk with   
					NSF Approved silicone caulk   
					HOOD-1A   
					HOOD-1B   
					(GE SCS1009 or its equivalent). The   
					caulk is not provided.   
					SILICONE CAULK   
					(GE SCS1009)   
					DOUBLE ISLAND CLIP   
					DOUBLE ISLAND CLIP   
					DETAIL A   
					Canopy Hood   
					6 
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Note: The installation of the canopy hoods shall be in accordance with NFPA 96 (latest edition),   
					Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations.   
					After the hood is installed, remove all protective plastic.   
					Note: Greenheck does not recommend walking or standing on the hood top as damage can result. If   
					you must walk on the hood top, protect the hood with additional support or planks for flooring.   
					Electrical Connections   
					Access for wiring the hood control panel (when applicable) is provided by a junction box located on   
					top of the hood when the control panel is mounted in the hood, or by the switch junction box when the   
					control panel is mounted in the fire protection cabinet. The box is labeled “Control Voltage Wiring to   
					Roof Top Fan Package”. Use minimum 14 AWG copper wire. After all the wiring is completed, install   
					the light bulbs (light bulbs not provided; standard light bulbs up to 100 watt may be used).   
					Caution: For multiple hood systems that have more than 14 lights total (incandescent or fluorescent),   
					the hood lights must be wired to multiple circuits. Each circuit must have less than 14 lights total.   
					Standard Greenheck light switches shipped on hoods are rated for 15 amps and shall not have more   
					than 14 lights connected to them. Higher amperage switches are available upon special request.   
					Ductwork   
					Exhaust   
					As specified in NFPA 96, Ch. 7.5 (latest edition), exhaust duct systems must be constructed in the   
					following manner:   
					Materials. Ducts shall be constructed of and supported by carbon steel not less than 1.37 mm   
					(0.054 in.) (No. 16 MSG) in thickness or stainless steel not less than 1.09 mm (0.043 in.) (No. 18 MSG)   
					in thickness.   
					Installation: All seams, joints, penetrations, and duct to hood collar connections shall have a   
					liquid-tight external weld. If you have an Automatic Fire Damper please refer to that manual for   
					installation instructions now.   
					Supply   
					Supply ductwork (where applicable) should be connected to the hood in a manner approved by the   
					local code authorities.   
					Note: For hoods with fire dampers in the exhaust and supply duct collars, an access panel for cleaning   
					and inspection shall be provided in the duct. This panel shall be as close to the hood as possible but   
					should not exceed 18 in. (45.72 cm).   
					For proper installation of duct collars when they are shipped unattached, see page 16.   
					Canopy Hood   
					7 
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installing External Supply Plenums   
					Using the Supply Plenum Clip   
					Fig. 6   
					OPTION #2   
					Note: The supply plenum is provided with   
					plenum clips that assist in hanging the plenum.   
					The plenum should not be hung only with the   
					plenum clips, threaded rod or uni-strut must   
					also be used.   
					UNI-STRUT SUPPLIED BY OTHERS   
					ROD   
					Y OTHERS   
					TOP VIEW   
					HOOD   
					OPTION #1   
					FOR PLENUMS <= 96"   
					2 CLIPS ARE NEEDED   
					1. Bolt the hanging clip to the supply plenum.   
					Two clips are needed for plenums less than   
					96 in. (243.84 cm) long and three for plenums   
					greater than 96 in. (243.84 cm). The third clip   
					is located in the center of the plenum length.   
					If there is a utility cabinet, the hanging clip   
					should be 23.5 in. (59.69 cm) from the end to   
					the hood.   
					FOR PLENUMS > 96"   
					3 CLIPS ARE NEEDED   
					THE THIRD CLIP IS LOCATED   
					IN THE CENTER OF THE PLENUM   
					LENGTH   
					OPTION #1   
					ATTACH HANGING CLIP TO   
					HOOD STANDING SEAM WITH   
					THE SUPPLIED "C" CLAMPS   
					(OPTIONAL: DRILL AND BOLT A   
					1/4-20 SS BOLT THROUGH   
					THE CLIP AND HOOD STANDING   
					SEAM)   
					2. Using the c-clamps provided, clamp the   
					supply plenum hanging clip to the hood   
					standing seam. Option: Drill and bolt a   
					1/4-20 SS bolt through the clip and hood   
					standing seam.   
					11.5   
					23.5   
					TOP VIEW   
					SUPPLY PLENUM   
					HANGER BRACKET   
					OPTION #1   
					HANGING CLIP COULD BE 23.5" FROM   
					END IF THERE IS A UTILITY CABINET   
					ON THE END OF THE HOOD   
					"C" CLAMP   
					OPTION #1   
					HOOD STANDING SEAM   
					HANGING CLIP   
					HANGING CLIP BOLTED TO PLENUM SHELL   
					HANGING CLIP   
					SUPPLY PLENUM SHELL   
					HOOD FRONT   
					Supply Plenum Clip   
					Fig. 7   
					OPTION #3   
					THREADED ROD   
					SUPPLIED BY OTHERS   
					THREADED ROD   
					Using the Uni-strut   
					1. The uni-strut (supplied by others) that holds   
					the hood up cantilevers over the end of the   
					hood and is mounted to the supply plenum   
					hanger brackets.   
					OPTION #2   
					THE UNI-STRUT (U-CHANNEL) THAT HOLDS THE   
					HOOD UP CANTILEVERS OVER THE END OF   
					THE HOOD AND IS MOUNTED TO THE ASP   
					HANGER BRACKETS   
					END VIEW   
					HOOD   
					Fig. 8   
					Canopy Hood   
					8 
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by others) into   
					hanger brackets on the supply plenum top. Raise and hang   
					the external supply plenum from adequate roof or ceiling   
					supports.   
					Fig. 9   
					2. The external supply plenum should be resting lightly against   
					the hood. The hood is used to position the plenum only, it is   
					not intended to support the plenum. All hanger brackets must   
					be used and the plenum must be properly supported while   
					lifting to prevent damage or distortion. The supply plenum   
					must be hung level to operate properly.   
					ASP - Air Curtain Supply Plenum   
					(Optional fastening of supply plenum to hood. See directions   
					below).   
					3. It is recommended that caulk be applied at the mating seams   
					and surfaces of the plenum, the hood, and the wall. If the   
					supply plenum is next to a wall, you will also need to caulk   
					around the surface next to the wall. Caulk the joints with NSF   
					Approved silicone caulk (GE SCS1009, or its equivalent). The   
					caulk is not provided.   
					Fig. 10   
					Installing the Supply Duct Collar to the Plenum   
					1. Place the duct collar(s) over the opening, fastening with tack-   
					welds at 1 to 2 in. (2.54 to 5.08 cm) intervals, or sheet metal   
					screws at 3 to 6 in. (7.62 to 15.24 cm) intervals.   
					HSP or VSP - Variable Supply Plenum   
					External Supply Plenum Weights, Dimensions, and Supply Rates   
					Length per   
					Weight   
					Width   
					(mm)   
					Height   
					(in) (mm)   
					section   
					External Supply   
					Plenum Type   
					Recommended   
					Supply Rate   
					(lbs/ft)   
					(kg/ft)   
					(in)   
					(ft)   
					(m)   
					.91 to   
					4.88   
					145 cfm/ft   
					35.0   
					9.5   
					15.878   
					6 
					152.4   
					355.6   
					609.6   
					Variable Variable   
					3 to 16   
					Back Supply   
					(246.36 m3/hr)   
					Air Curtain Supply   
					• 14 inch   
					.91 to   
					4.88   
					110 cfm/ft   
					4.31   
					5.67   
					14   
					24   
					10   
					10   
					254   
					254   
					3 to 16   
					3 to 16   
					(186.89 m3/hr)   
					Air Curtain Supply   
					• 24 inch   
					.91 to   
					4.88   
					145 cfm/ft   
					12.5   
					(246.36 m3/hr)   
					0-80 cfm/ft   
					curtain   
					face   
					(0-135.92 m3/hr)   
					.91 to   
					4.88   
					16.0   
					14.0   
					7.26   
					6.35   
					12   
					12   
					304.8   
					304.8   
					18   
					18   
					457.20   
					457.20   
					3 to 16   
					3 to 16   
					Variable Supply   
					80-160 cfm/ft   
					(135.92 -271.84 m3/hr)   
					.91 to   
					4.88   
					150 cfm/ft   
					Horizontal Supply   
					(254.85 m3/hr)   
					Using the UL Listed Fastener Provided   
					HOOD   
					1. Drill a 9/32 in. hole for the 1/4 in. bolt from the inside of the supply plenum to   
					inside the hood. Fasteners are to be located max. 6 in. (15.24 cm) from the   
					end of the hood with max. spacing between bolts 36 in. (91.44 cm)   
					1/4 - 20 UNC - 2A   
					SS BOLT   
					1/4 IN. SS NUT   
					DO NOT i N c l u D e u T i l i T y c a b i N e T s O r f i l l e r s w h e N figuriNg b O l T p l a c e m e N T .   
					DO NOT b O l T T h e s u p p l y p l e N u m T O a f i r e /u T i l i T y c a b i N e T .   
					2. Push bolt through hole, attach the washer and nut.   
					SS FLAT WASHER   
					3. Hand tighten, then use a wrench until fully tightened. Caulk around bolts   
					from inside of hood as necessary.   
					Fig. 11   
					Canopy Hood   
					9 
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installing the Back Supply Plenum   
					Installing the Supply Duct Collar   
					1. Find the center of the back supply plenum.   
					L (MODULE LENGTH)   
					2. If the back supply plenum is less than 9 ft. 10 in. (299.72 cm) long,   
					cut opening at the suggested location, centering the opening over   
					the center of the back supply plenum. (Fig. 12)   
					L/2   
					L/2   
					3. If the back supply plenum is greater than 9 ft. 10 in. (299.72 cm)   
					long, divide the length of the back supply by four. This will give you   
					the center of each half. Cut openings at the suggested location,   
					centering the duct collar over the center measurement of each half.   
					(Fig. 13)   
					4. Place the duct collar(s) over the opening, fastening with screws or   
					tack-welds every 4 to 6 in. (10.16 to 15.24 cm). (Fig. 14)   
					Fig. 12   
					• 
					The 4 in. (10.16 cm)   
					high duct collar is to   
					be attached to the   
					back supply.   
					L (MODULE LENGTH)   
					L/2   
					L/4   
					L/4   
					Fig. 14   
					Fig. 13   
					Hanging the Back Supply Plenum   
					5. Hang the back supply plenum from the ceiling.   
					(The back supply plenum needs to be mounted 31.25 in. (79.375 cm) above the floor (based upon a   
					canopy hood that will be hung at 78 in. (198.12 cm) above the finished floor. This is measured from   
					the lowest rear edge of the back supply plenum to the finished floor. Leave 6 to 10 in. (15.24 to   
					25.4 cm) of space below the plenum for access to the air diffusers.)   
					6. Fasten the Back Supply to the wall, going through the lower Back Supply wall. (Fig. 15)   
					• 
					These fasteners are to help maintain the location of the Back Supply, and are not intended to   
					hold the weight of the Back Supply Unit.   
					• 
					• 
					The fasteners should not interfere with the removable air diffusers.   
					The 31.25 in. (79.375 cm) height is based upon the canopy hood hanging height of 78 in.   
					(198.12 cm) from the finished floor to the bottom of the hood.   
					Canopy Hood   
					10   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Hanging the Hood   
					Before hanging the hood according to the   
					hood installation instructions, please check the   
					following:   
					Fig. 15   
					1. Make sure the back supply plenum is   
					properly secured, as described in steps 5   
					and 6, page 10.   
					2. If the ductwork for the back supply will not   
					interfere with the hood installation, it should   
					be connected now.   
					3. Any filler panels should be attached to the   
					hood before the hood installation.   
					See page 5 for instructions.   
					Fasteners holding the   
					back supply to the wall   
					4. Lift the hood, and position it so the filler   
					panels are resting lightly on the top outside   
					edges of the back supply. The back supply   
					is used to position the hood only, it is not   
					intended to hold any hood weight. (Fig. 16)   
					31.25 in.   
					Critical   
					Dimension   
					5. Connect the remaining ductwork for the   
					back supply and the hood. It is recommended   
					that caulk be applied at the mating seams   
					and surfaces of the back supply, the hood,   
					and the wall.   
					Fig. 16   
					Air Diffusers   
					The air diffusers, located at the bottom of the back   
					supply (Fig. 17), will need to be cleaned as often as the   
					application dictates. Inspect periodically to determine   
					the cleaning schedule.   
					Fig. 17   
					1. To clean the air diffusers, unfasten the screws.   
					Remove the air diffusers from the Back Supply   
					Unit, and wash in the sink or dishwasher.   
					2. Insert the air diffusers at an angle from the bottom,   
					and rotate so the forms are downward. Rest the   
					diffuser on the internal angles. (Fig. 18)   
					Removable Air Diffusers   
					3. Refasten with the stainless steel screws.   
					Fig. 18   
					Canopy Hood   
					11   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installing Enclosure Panels   
					Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork   
					attached and electrical connections completed.   
					Fig. 19   
					1. Position the end enclosure panels on the hood, and clamp into place with clamps provided or tack-   
					weld the panels into place (Fig 19).   
					2. Fasten the end enclosure panels to the wall, method depends on wall construction. (fasteners are   
					not provided)   
					If the hood is a double island, bolt the end enclosure panels together. (fasteners are not provided)   
					3. Position the front enclosure panel(s) on the hood, and bolt to the end enclosure panels with the   
					5/16 in. bolts provided in the hardware package.   
					4. Tack-weld or clamp the front enclosure panel(s) to the hood. If clamps are used, they must be   
					positioned 4 in. (100 mm) from the ends, and in the center of the front enclosure panel.   
					5. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk   
					(GE SCS1009, or its equivalent). The caulk is not provided.   
					6. Installation instructions may not be applicable for concrete ceilings.   
					Canopy Hood   
					12   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installing End Skirts   
					. 
					Fig. 20   
					1. After the hood is hung in position, slide the hemmed form on top of the end skirt onto the end   
					panels of the hood.   
					2. Drill a hole in the hood end panel to line up with the hole in the end skirt. Attach the end skirt with   
					a 1/4 in. bolt and cap nut to the inside of the hood, or tack-weld the end skirt to the hood.   
					3. Position the end skirt against the wall and attach. The method depends on the wall construction.   
					(fasteners for this are not provided)   
					4. Caulk the internal joint formed by the end skirt and the hood end panel with NSF Approved silicone   
					caulk (GE SCS1009 or its equivalent). The caulk is not provided.   
					5. To allow for ease in cleaning, also caulk all the external seams.   
					Canopy Hood   
					13   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installing Backsplash Panels   
					FLAT BACKSPLASH PANEL   
					MATERIAL GAUGE — STAINLESS   
					LENGTH   
					QTY   
					WALL   
					Inches   
					<= 48   
					Millimeters   
					<= 1219.2   
					1 
					2 
					3 
					4 
					5 
					>48<=94   
					>94<=141   
					>1219.2<=2387.6   
					>2387.6<=3581.4   
					HEIGHT   
					>141<=188 >3581.4<=4775.2   
					>188<=235 >4775.2<=5969   
					LENGTH   
					NOTE: PANELS UP TO 48 IN. (1219.2 MM) WIDE SHIP IN ONE PIECE; OVER 48 IN. (1219.2 MM) IN MULTIPLE PIECES.   
					Fig. 21   
					1 IN. (25.4 MM)   
					INSULATED BACKSPLASH PANEL   
					MATERIAL GAUGE — STAINLESS   
					INSULATION — 1 IN. (25.4 MM)   
					WALL   
					LENGTH   
					QTY   
					Inches   
					<= 46   
					Millimeters   
					<= 1168.4   
					1 
					2 
					3 
					4 
					5 
					>46<=91   
					>91<=136   
					>1168.4<=2311.4   
					>2311.4<=3454.4   
					HEIGHT   
					>136<=181 >3454.4<=4597.4   
					>181<=226 >4597.4<=5740.4   
					LENGTH   
					NOTE: PANELS UP TO 46 IN. (1168.4 MM) WIDE SHIP IN ONE PIECE; OVER 46 IN. (1168.4 MM) IN MULTIPLE PIECES.   
					Fig. 22   
					Canopy Hood   
					14   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installing Backsplash Panels   
					SLIDE FLANGE   
					BEHIND BACK   
					OF THE HOOD   
					SECTION VIEW   
					OF BACKSPLASH   
					PANEL OVERLAP   
					HOLES SHOULD BE SPACED TO   
					ADEQUATELY SECURE THE PANEL   
					TO THE WALL STUDS (HOLE SPACING   
					AND FASTENERS PROVIDED BY OTHERS)   
					Fig. 23   
					1. After the hood is hung in position, slide the flat flange of the backsplash panel behind the back of   
					the hood.   
					Note: If the backsplash panel length is greater than 46 in. (116.84 cm), it will be shipped in multiple   
					pieces.   
					2. After the backsplash panel has been positioned, drill holes in the panel and fasten to the wall.   
					(fasteners provided by others).   
					Note: The holes should be spaced to adequately secure the panel to the wall.   
					3. Caulk the joints between the hood and the backsplash panel with NSF Approved silicone caulk   
					(GE SCS1009, or its equivalent). The caulk is not provided.   
					4. Caulk the joint between the backsplash panels when multiple panels are required, with NSF   
					Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.   
					Canopy Hood   
					15   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installing Duct Collars   
					1. The exhaust duct   
					connection needs to   
					be located within 48 in.   
					(121.92 cm) from the   
					center of the hood   
					length to the center of   
					the duct connection.   
					(see Fig. 24, back view   
					Fig. 25)   
					Hanger Bracket   
					Exhaust Plenum   
					3.00   
					14.00   
					Duct Cut Out Area   
					Hood Width   
					16.00   
					2. The exhaust duct   
					connection is to be   
					a continuous liquid-   
					tight weld. Weld with   
					a non-ferrous filler   
					wire, such as silicon   
					bronze or stainless   
					steel filler wire. Protect   
					all stainless steel areas   
					from weld splatter.   
					Supply Plenum   
					Hood Length   
					3.00   
					Front of Hood   
					8.00   
					8.00   
					Top View of the Hood   
					Fig. 24   
					8.00   
					8.00   
					Hood Top   
					1.00   
					3. The supply duct   
					connection is tack-   
					welded at 1 to 2 in.   
					(2.54 to 5.08 cm)   
					Exhaust Plenum   
					12.00   
					Duct Cut Out Area   
					intervals, or sheet metal   
					screws at 3 to 6 in.   
					(7.62 cm to 15.24 cm)   
					spacing to the hood.   
					(Fig. 26)   
					Back View of the Hood   
					Fig 25   
					SUPPLY   
					INTERNAL   
					SUPPLY   
					CHAMBER   
					FIRE DAMPER   
					4. The deflector is   
					centered under the   
					supply duct collar.   
					(Fig. 28)   
					S 
					C 
					UPP   
					L 
					E 
					Y 
					DUC   
					T 
					ONN   
					CT   
					IO   
					N 
					HOOD   
					S 
					1 
					6 
					UPP   
					L 
					2 
					Y 
					" 
					DUC   
					T 
					S 
					C 
					O 
					O 
					R 
					NN   
					S 
					E 
					H 
					C 
					EE   
					T 
					I 
					T 
					O 
					M 
					N 
					T 
					O 
					A 
					B 
					L 
					E 
					S 
					T 
					A 
					C 
					K 
					WELDED WITH   
					" 
					T 
					O 
					T 
					A 
					CK   
					E 
					T 
					CR   
					E 
					W 
					S 
					AT   
					3 
					" 
					TO   
					5. For hoods that are   
					insulated, the edges of   
					the insulation need to   
					be taped after the hole   
					is cut, (the insulation   
					tape is to be provided   
					by others).   
					" 
					S 
					PACING   
					TO   
					HOOD.   
					INSULATED   
					SUPPLY PLENUM   
					EXHAUST   
					CAPTURE   
					Fig. 26   
					Fig. 27   
					Fig. 28   
					6. On combination hoods,   
					make sure the fire   
					Note: UL listed hood   
					assembly to be used   
					only with Greenheck   
					Fan Corp. labeled   
					subassembly for   
					exhaust hood without   
					exhaust damper part   
					Number DC.   
					damper is located over   
					the internal supply   
					chamber. (Fig. 29)   
					DEFLECTOR TO BE PLACED CENTERED   
					UNDER THE SUPPLY DUCT COLLAR   
					Canopy Hood   
					16   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Exhaust Air Balancing Baffles (EABB)   
					This is a guide to assist in determining if multiple hoods on one fan can be balanced to have equal   
					static pressure. For multiple hoods on one fan to achieve their designed exhaust flow, all of the hoods   
					must have equal static pressure at their designed exhaust flow.   
					The laws of physics force the static pressure for each branch of a duct system on one fan to always be   
					equal. This will happen by the flow rate increasing in low static branches and decreasing in high static   
					branches until the static pressure is equal in all branches.   
					Checking for Balance   
					Every hood with Exhaust Air Balancing Baffles (EABB) has a range for its static pressure. The low   
					number in this range is given by the standard calculation for hood static. (Static that is printed with   
					the CAPS submittal). The maximum increase above the low number can be calculated from the duct   
					velocity at the low static, (also given on CAPS submittal). This is then added to the low number to get   
					the highest static pressure possible with an EABB.   
					The maximum potential increase in static is given in the graph, or can be calculated from:   
					2 
					Max. Increase = 0.00000036 x (Duct velocity)   
					Maximum Increase in Static Pressure for Exhaust Air Balancing Baffle   
					(Fully Closed)   
					4.5   
					After the range for each hood is calculated,   
					it should be compared to the hood with the   
					4 
					highest static pressure. If the highest hood   
					3.5   
					falls inside of the range, then the hoods can be   
					3 
					balanced with the EABB. If it is higher than the   
					2.5   
					range, the hoods cannot be balanced.   
					2 
					Example 1:   
					Hood 1:   
					1.5   
					1 
					Ps = 0.58 in. wg   
					0.5   
					0 
					Duct Velocity = 1900 FPM   
					Ps = 0.44 in. wg   
					500   
					1000   
					1500   
					2000   
					2500   
					3000   
					3500   
					Duct Velocity FPM   
					Hood 2:   
					Duct Velocity = 1800 FPM   
					Hood 2 has the lower Ps, at 1800 FPM the maximum increase in Ps is 1.17. The range for Hood 2 is   
					0.44 to 1.61. Hood 1 is less than 1.61 so these hoods can be balanced.   
					Example 2:   
					Hood 3:   
					Hood 4:   
					Ps = 2.00 in. wg   
					Duct Velocity = 2000 FPM   
					Ps = 0.44 in. wg   
					Duct Velocity = 1500 FPM   
					Hood 4 has the lower Ps, at 1500 FPM the maximum increase in Ps is .81. The range for Hood 4 is 0.44   
					to 1.25. Hood 3 is higher than 1.25 so these hoods cannot be balanced.   
					Note 1: For many systems, an EABB may not be needed on the hood that has the highest static pressure. The   
					exception to this is if the individual ductwork has uneven static pressures.   
					Note 2: When sizing the fan, use the static pressure from the highest hood and sum the CFM from all the hoods.   
					Canopy Hood   
					17   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Balancing the Kitchen Exhaust System   
					A. To determine the proper dining room air balance:   
					1. Refer to engineering drawings to determine total exhaust CFM from dining areas.   
					(Exhaust fans, heating and air conditioning units, restrooms, etc.)   
					2. Determine the total CFM of make-up air supplied to dining area.   
					3. Subtract #1 from #2 above. If the result is a negative number, a negative pressure is present   
					in the dining area. In this case, kitchen exhaust odors could be drawn from the kitchen to the   
					dining area. Therefore, exhaust or supply air should be adjusted to provide a slight positive   
					pressure in the dining area.   
					B. To determine proper kitchen air balance:   
					1. Refer to engineering drawings to determine total exhaust from the kitchen area.   
					(Exhaust hoods, dishwasher hoods, etc.)   
					2. Determine total CFM of make-up air supplied to kitchen area.   
					(Make-up air hoods, heating and air conditioning units, etc.)   
					3. Subtract #1 from #2 above. The result should be a negative number. If the result is a positive   
					number, a positive pressure is present in the kitchen area. Kitchen odors could be forced into   
					the dining area. Also, a positively balanced kitchen area can adversely affect the performance   
					of the exhaust hood.   
					Caution: According to NFPA 96, Ch. 8-3 Replacement Air: Replacement air quantity shall be adequate   
					to prevent negative pressures in the commercial cooking area(s) from exceeding 4.98 kPa (0.02 in.   
					water column).   
					Testing Hood Air Volume   
					Baffle Filter Style Hoods   
					Nominal Filter Size   
					A. Exhaust:   
					With all the filters in place, determine   
					H/4   
					the total hood exhaust volume with a   
					rotating vane anemometer as follows:   
					x 
					x 
					1. All cooking equipment should   
					be on.   
					H 
					x 
					2. Measure the velocities   
					H/2   
					x 
					x 
					H/4   
					Velocity measurements should   
					be taken at five locations per   
					filter. These must be over a filter   
					slot as in Fig. 29.   
					Fig. 29   
					Canopy Hood   
					18   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Measure the velocity of each location.   
					A digital 2.75 in. (70 mm) rotating   
					vane anemometer or equivalent   
					is suggested. The center of the   
					anemometer should be held 2 in.   
					(50 mm) from the face of the filters as   
					shown in Fig. 30. It is helpful to make   
					a bracket to keep the anemometer   
					at the 2 in. (50 mm) distance and   
					parallel to the filter. Both squareness   
					and distance are very important for   
					accuracy.   
					Rotating Vane Anemometer   
					2 in.   
					Fig. 30   
					Calculate the average velocity for the filter.   
					3. Determine the filter’s conversion factor from the table.   
					4. Calculate the filter’s volume in CFM (m3/hr) by multiplying the average velocity by the   
					conversion factor.   
					5. Calculate the hood’s volume by repeating the process for the remaining filters and summing the   
					individual filter volumes.   
					Nominal Filter Size (H x L)   
					Imperial   
					Metric   
					Conversion Factor   
					Conversion Factor   
					Inches   
					Millimeters   
					400 x 400   
					500 x 400   
					400 x 500   
					500 x 500   
					16 x 16   
					16 x 20   
					20 x 16   
					20 x 20   
					1.63   
					2.13   
					1.90   
					2.48   
					.157   
					.198   
					.177   
					.230   
					Example: Exhaust Only Hood with three 20 x 16 Filters   
					Measured velocities in fpm for one 20 x 16 Filter   
					Sum of Velocity Readings   
					250   
					255   
					(4572 m/h)   
					(4663.44 m/h)   
					256   
					(4681.73 m/h)   
					Average Velocity   
					= 
					= 
					= 
					Number of Readings   
					248   
					240   
					(4535.42 m/h)   
					(4389.12 m/h)   
					255 + 250 + 256 + 248 + 240   
					5 
					(Imperial)   
					= 249.8 fpm   
					4663 + 4572 + 4681 + 4535 + 4389   
					5 
					(Metric)   
					= 4568 m/hr   
					For a nominal filter size of 20 x 16, the conversion factor is 1.90 Imperial (.177 Metric)   
					Volume for one filter = Conversion Factor x Average Velocity   
					= 
					= 
					1.90   
					.177   
					x 
					x 
					249.8 fpm   
					4568 m/hr   
					= 
					= 
					474.6 cfm   
					809 m3/hr   
					Total hood volume   
					= (Filter 1 Volume) + (Filter 2 Volume) + (Filter 3 Volume)   
					= 
					= 
					474.6   
					809   
					+ 
					+ 
					455.4   
					880   
					+ 
					+ 
					470.1   
					799   
					= 1400.1 cfm   
					= 2488 m3/hr   
					Canopy Hood   
					19   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				B. Supply (If Applicable):   
					Example for Perforated Face Supply   
					1. Hood set up   
					If the make-up air unit has a temperature control, it should be used to keep the supply air at the   
					desired room discharge air temperature.   
					2. Measure Velocities   
					Divide the perforated face panel into a grid of equal areas, each approximately 4 in. (100 mm)   
					square.   
					Measure the velocity at the center of each grid area. A digital 2.75 in. (70 mm) rotating vane   
					anemometer or equivalent is suggested. The center of the anemometer should be held tight to   
					the face of the panel, and parallel to the filter. Both squareness and distance are important for   
					accuracy. Calculate the average velocity of the panel.   
					3. Measure the length, height, and width of the perforated face panel.   
					4. Calculate the perforated face panel volume in CFM by using the following formula:   
					Volume   
					Volume   
					= 
					= 
					Avg. Velocity   
					Avg. Velocity   
					Length (in.)   
					Length (m)   
					Height (in.) 0.005   
					* 
					* 
					* 
					* 
					* 
					Height (m)   
					0.72   
					* 
					5. Calculate the system’s volume by repeating the process for the remaining panels and adding   
					the individual panel volumes together.   
					Filter Readings (fpm)   
					Filter Readings (m/hr)   
					260 250 255 260 250 255 265   
					270 275 270 280 265 265 270   
					290 285 280 280 275 290 295   
					285 275 280 260 270 265 260   
					4755 4572 4663 4755 4572 4663 4846   
					4938 5029 4938 5121 4846 4846 4938   
					5304 5212 5121 5121 5029 5304 5395   
					5212 5029 5121 4755 4938 4846 4755   
					Example: Face Supply Hood with three 28 in. (.711 m) Perforated Panels   
					Measured velocities in FPM for one perforated panel   
					Sum of Velocity Readings   
					Average Velocity   
					= 
					= 
					= 
					Number of Readings   
					260 + 250 + … + 265 + 260   
					28   
					(Imperial)   
					= 270.7 fpm   
					4755 + 4572 + … + 4846 + 4755   
					28   
					(Metric)   
					= 4951 m/hr   
					Measure Length and Height = 28 in. (.711 m) long perforated panels x 16 in. (.406 m) high   
					Average   
					Velocity   
					Conversion   
					Factor   
					Volume for one panel =   
					x 
					x Length x Height   
					= 
					= 
					0.005   
					0.72   
					x 
					x 
					270.7 fpm   
					4951 m/hr   
					x 
					x 
					28   
					x 
					x 
					16   
					= 
					= 
					606.4 cfm   
					1029 m3/hr   
					.711   
					.406   
					Total system volume = (Panel 1 Volume) + (Panel 2 Volume) + (Panel 3 Volume)   
					= 
					= 
					606.4   
					1029   
					+ 
					+ 
					614.3   
					1044   
					+ 
					+ 
					593.8   
					1009   
					= 
					1814.5 cfm   
					3082 m3/hr   
					= 
					Canopy Hood   
					20   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Testing Hood Air Volume   
					Baffle Filters Style Hoods with the Shortridge Meter   
					A. Exhaust   
					With all the filters in place, determine the total hood exhaust   
					volume with a Shortridge meter as follows:   
					1. All cooking equipment should be on. If the hood has   
					internal short circuit make-up air, it should be turned off.   
					2. Measuring Velocities   
					• Set up the Shortridge meter.   
					• For 20 in. (500 mm) wide filters, position the grid as   
					shown in Fig. 32 and 33. Average two measurements.   
					• For 16 in. (400 mm) wide filters position the grid as   
					shown in Fig. 34.   
					• Take velocity readings for each filter.   
					3. *Calculate each filter’s volumetric flow rate by summing   
					the flow rate of each individual filter in the hood.   
					4. *Calculate the total hood’s volumetric flow rate by   
					summing the flow rate of each individual filter in the hood.   
					*Note: For best accuracy multiply the velocity of each filter by its   
					conversion factor and sum the flow rates. Averaging the velocity   
					measured for all filters may cause error.   
					Fig. 31   
					Nominal Filter Size (H x L)   
					Imperial   
					Metric   
					Conversion Factor   
					Conversion Factor   
					Inches   
					Millimeters   
					400 x 400   
					400 x 500   
					500 x 400   
					500 x 500   
					16 x 16   
					16 x 20   
					20 x 16   
					20 x 20   
					1.66   
					2.10   
					1.96   
					2.40   
					.154   
					.195   
					.182   
					.223   
					14 in.   
					2.75 in.   
					10 in.   
					Example: Measured velocities for 20 x 20 filter = 185 and 189 fpm   
					Fig. 32   
					Fig. 33   
					Fig. 34   
					Sum of Velocity Readings   
					Average Velocity   
					(Imperial)   
					= 
					= 
					= 
					17.25 in.   
					Number of Readings   
					6 in.   
					185 + 189   
					= 187.0 fpm   
					2 
					10 in.   
					3383 + 3456   
					2 
					= 
					(Metric)   
					3420 m/hr   
					Conversion   
					Average   
					Velocity   
					Flow rate for one filter =   
					x 
					Factor   
					14 in.   
					= 
					= 
					2.40   
					x 
					x 
					187.0 fpm   
					3420 m/hr   
					= 
					= 
					448.8 cfm   
					763 m3/hr   
					2.75 in.   
					.223   
					10 in.   
					(Filter 1   
					Flow Rate)   
					(Filter X   
					Flow Rate)   
					Total hood flow rate   
					= 
					+ … +   
					= 448.8 + 457.8 + 437.5 + 444.8 = 1788.9 cfm   
					= 763 + 778 + 743 + 756   
					= 3040 m3/hr   
					Canopy Hood   
					21   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				High Velocity Cartridge Filters   
					A. Exhaust   
					1/2 Width   
					1/4 Width   
					1/4 Width   
					With all the filters in place, determine the total hood exhaust   
					volume with a rotating vane anemometer as follows:   
					1. All cooking equipment should be on. If the hood has   
					internal short circuit make-up air, it should be turned off.   
					2. Measuring Velocities   
					Fig. 35   
					• Velocity measurement should be taken at three locations per filter.   
					2 in.   
					These must be over the inlet opening as shown in Fig. 35.   
					• Measure the velocity of each location. A digital 2.75 in. (70 mm)   
					rotating vane anemometer or its equivalent is suggested. The center   
					of the anemometer should be held 2 in. (50 mm) from the face of   
					the filters as in Fig. 31. It is helpful to make brackets to keep the   
					anemometer at the 2 in. (50 mm) distance and parallel to the filter.   
					Both squareness and distance are important for accuracy.   
					Rotation Vane   
					Anemometer   
					3. Calculate the average slot velocity.   
					4. Calculate the CFM per linear foot by dividing the average velocity by a   
					conversion factor listed in the following table.   
					5. Calculate the hood’s exhaust volume by multiplying the CFM per linear   
					foot by the length of hood.   
					Fig. 36   
					Imperial   
					Cartridge Filter Size   
					Metric   
					Conversion Factor   
					Conversion Factor   
					3 
					3 
					16 in. (400 mm) high with 4 in. (100 mm) high inlet   
					20 in. (500 mm) high with 4 in. (100 mm) high inlet   
					16 in. (400 mm) high with 7 in. (120 mm) high inlet   
					20 in. (500 mm) high with 7 in. (120 mm) high inlet   
					1.63 1/ft   
					2.15 1/ft   
					1.24 1/ft   
					1.58 1/ft   
					5.35 1/m   
					3 
					3 
					3 
					3 
					7.05 1/m   
					3 
					4.07 1/m   
					3 
					5.18 1/m   
					Example:   
					Measure the slot velocities in fpm for a 9 ft. (2.74 m) hood with four 20 x 20 in. (500 x 500 mm)   
					filters with standard opening, three readings per filter.   
					Filter Readings (fpm)   
					Sum of Velocity Readings   
					Average slot velocity   
					(Imperial)   
					= 
					470   
					482   
					455   
					399   
					440   
					430   
					431   
					439   
					425   
					453   
					441   
					465   
					Number of Readings   
					5330   
					= 
					= 
					= 444.2 fpm   
					12   
					97474   
					Filter Readings (m/hr)   
					(Metric)   
					= 8123 m/hr   
					12   
					8595   
					8047   
					7864   
					7882   
					8028   
					7772   
					8815   
					8321   
					7297   
					8284   
					8065   
					8504   
					Average Slot Velocity   
					Conversion Factor   
					444.2 fpm   
					CFM per linear foot   
					= 
					= 
					= 
					= 206.6 cfm/linear foot   
					2.15   
					8123 m/hr   
					7.05   
					1152 m3/hr   
					= 
					Hood exhaust volume   
					= 
					= 
					= 
					CFM/linear foot (m3/hr / m)   
					x 
					x 
					x 
					Hood Length   
					206.6   
					1152   
					9 ft.   
					2.74 m   
					= 1859.4 cfm   
					= 3156 m3/hr   
					Canopy Hood   
					22   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				High Velocity Cartridge Filters   
					A. Exhaust   
					With all the filters in place, determine the total hood exhaust   
					volume with a Shortridge meter as follows:   
					1. All cooking equipment should be on. If the hood has   
					internal short circuit make-up air, it should be turned off.   
					2. Measuring Velocities   
					• Set up the Shortridge meter. Leave all holes of   
					Velgrid open. Do NOT tape over holes that are not   
					over openings. The conversion factor takes this into   
					account.   
					• Position the grid over each filter as shown.   
					• Take velocity readings for each filter.   
					3. *Calculate each filter’s volumetric flow rate by summing   
					the flow rate of each individual filter in the hood.   
					4. *Calculate the total hood’s volumetric flow rate by   
					summing the flow rate of each individual filter in the   
					hood.   
					Fig. 37   
					*Note: For best accuracy multiply the velocity of each filter   
					by its conversion factor and sum the flow rates. Averaging the   
					velocity measured for all filters may cause error.   
					Nominal Filter Size (H x L)   
					Imperial   
					Metric   
					Conversion Factor   
					Conversion Factor   
					Inches   
					Millimeters   
					400 x 400   
					400 x 500   
					500 x 400   
					500 x 500   
					2 
					2 
					16 x 16   
					16 x 20   
					20 x 16   
					20 x 20   
					1.22 ft   
					.113 m   
					2 
					2 
					1.67 ft   
					.155 m   
					2 
					2 
					1.21 ft   
					.112 m   
					2 
					2 
					1.50 ft   
					.139 m   
					1/2 width   
					Example: Measured velocities for 20 x 20 filter = 282 fpm (5157 m/hr)   
					1/2 height   
					Conversion   
					Factor   
					Average   
					Velocity   
					Flow rate for one filter   
					= 
					x 
					x 
					(Imperial)   
					(Metric)   
					= 
					= 
					1.50   
					.139   
					282 fpm   
					= 
					423.0 cfm   
					717 m3/hr   
					x 5157 m/hr =   
					Total hood flow rate = (Filter 1 Flow Rate) + … + (Filter X Flow Rate)   
					= 423.0 + 421.8 + 420.7 + 418.2 = 1683.7 cfm   
					Fig. 38   
					= 717 + 717 + 715 + 711   
					= 2860 m3/hr   
					Canopy Hood   
					23   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Grease-X-Tractor™ High Efficiency Filters or Grease Grabber™ Multi-Filtration System   
					A. Exhaust   
					1/2 Width   
					With all the filters in place, determine the total hood exhaust   
					volume with a rotating vane anemometer as follows:   
					1/4 Width   
					1/4 Width   
					1. All cooking equipment should be off. If the hood has internal   
					1/2 Height   
					short circuit make-up air, it should be turned off.   
					2. Measuring Velocities   
					• Measurement should be taken at six locations per filter.   
					They must be over the inlet opening as shown in Fig. 39.   
					• Measure the velocity of each location. A digital 2.75 in.   
					Fig. 39   
					(70 mm) rotating vane anemometer or its equivalent is   
					suggested. The center of the anemometer should be held 2 in. (50 mm) from the face of the   
					filters as in Fig. 40. It is helpful to make brackets to keep the anemometer at the 2 in. (50 mm)   
					distance and parallel to the filter. Both squareness and distance are important for accuracy.   
					2 in.   
					3. Calculate the average velocity for the filter.   
					4. Determine the filter’s conversion factor from the table.   
					Rotating Vane   
					Anemometer   
					5. Calculate each filters volume in CFM by multiplying the average   
					velocity by the conversion factor.   
					Nominal Filter Size (H x L)   
					Imperial   
					Metric   
					Conversion Factor   
					Conversion Factor   
					Inches   
					Millimeters   
					400 x 400   
					400 x 500   
					500 x 400   
					500 x 500   
					2 
					2 
					16 x 16   
					16 x 20   
					20 x 16   
					20 x 20   
					1.31 ft   
					.122 m   
					Fig. 40   
					2 
					2 
					1.65 ft   
					.153 m   
					2 
					2 
					1.23 ft   
					.114 m   
					2 
					2 
					1.65 ft   
					.153 m   
					Example: (Imperial)   
					Example: (Metric)   
					Hood Length = 7 feet 0 inches with four 20 x 20 filters.   
					Hood Length = 2.13 meters, with four 500 x 500 mm filters.   
					Measure the velocities in fpm for each 20 x 20 filter   
					(six readings per filter)   
					Measure the velocities in m/hr for each 500 x 500 mm filter   
					(six readings per filter)   
					225   
					210   
					228   
					237   
					230   
					250   
					225   
					245   
					201   
					238   
					222   
					240   
					245   
					223   
					265   
					221   
					187   
					197   
					226   
					220   
					240   
					219   
					219   
					200   
					4114.80   
					3840.48   
					4169.66   
					4334.26   
					4420.12   
					4572.00   
					4114.80   
					4480.56   
					3675.88   
					4352.54   
					4059.94   
					4389.21   
					4480.56   
					4078.22   
					4846.52   
					4041.65   
					3419.86   
					3602.74   
					4133.08   
					4023.36   
					4389.12   
					4005.07   
					4005.07   
					3657.60   
					Filter 1   
					Filter 2   
					Filter 3   
					Filter 4   
					Filter 1   
					Filter 2   
					Filter 3   
					Filter 4   
					Sum of Velocity Readings   
					Number of Readings   
					1258   
					Sum of Velocity Readings   
					Number of Readings   
					23006   
					Average slot velocity for Filter 1   
					= 
					= 
					Average slot velocity for Filter 1   
					= 
					= 
					= 
					209.7 fpm   
					= 
					3834 m/hr   
					6 
					6 
					(repeat for each filter)   
					(repeat for each filter)   
					For a nominal filter size of 20 x 20, the conversion factor is 1.65   
					Volume for Filter 1 = Conversion Factor x Average Velocity   
					For a nominal filter size of 500 x 500, the conversion factor is .153   
					Volume for Filter 1 = Conversion Factor x Average Velocity   
					= 
					1.65 ft2   
					= 346.0 cfm (repeat for each filter)   
					x 
					209.7 ft./min.   
					= 
					.153 m2   
					= 586.7 m3/hr (repeat for each filter)   
					x 
					3834 m/hr   
					Total hood volume   
					Total hood volume   
					Filter 1   
					Volume   
					346.0   
					Filter 2   
					Volume   
					377.6   
					Filter 3   
					Volume   
					386.9   
					Filter 4   
					Volume   
					378.1   
					Filter 1   
					Volume   
					587   
					Filter 2   
					Volume   
					642   
					Filter 3   
					Volume   
					657   
					Filter 4   
					Volume   
					642   
					= 
					= 
					+ 
					+ 
					+ 
					+ 
					+ 
					+ 
					= 
					= 
					+ 
					+ 
					+ 
					+ 
					+ 
					+ 
					= 
					1488.6 cfm   
					= 
					2528 m3/hr   
					Canopy Hood   
					24   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Grease-X-Tractor™ High Efficiency Filters or Grease Grabber™ Multi-Filtration System   
					A. Exhaust   
					With all the filters in place, determine the total hood exhaust   
					volume with a Shortridge meter as follows:   
					1. All cooking equipment should be on. If the hood has   
					internal short circuit make-up air, it should be turned off.   
					2. Measuring Velocities   
					• Set up the Shortridge meter. Leave all holes of   
					Velgrid open. Do NOT tape over holes that are not   
					over openings. The conversion factor takes this into   
					account.   
					• For 20 in. (500 mm) high filters, position the grid   
					as shown in Fig. 42 and 43. Average the two   
					measurements.   
					• For 16 in. (400 mm) high filters position the grid as   
					shown in Fig. 44.   
					• For 20 in. (500 mm) wide filters, position the grid over   
					the left and right side of the filter. Average the two   
					Fig. 41   
					measurements.   
					• Take velocity readings for each filter.   
					3. *Calculate each filter’s volumetric flow rate by summing   
					the flow rate of each individual filter in the hood.   
					4. *Calculate the total hood’s volumetric flow rate by summing   
					the flow rate of each individual filter in the hood.   
					*Note: For best accuracy multiply the velocity of each filter by its   
					conversion factor and sum the flow rates. Averaging the velocity   
					measured for all filters may cause error.   
					Nominal Filter Size (H x L)   
					Imperial   
					Conversion Factor   
					Metric   
					Conversion Factor   
					14.25 in.   
					2.75 in.   
					Fig. 42   
					Inches   
					Millimeters   
					400 x 400   
					400 x 500   
					500 x 400   
					500 x 500   
					2.75 in.   
					2 
					2 
					16 x 16   
					16 x 20   
					20 x 16   
					20 x 20   
					1.53 ft   
					.142 m   
					2 
					2 
					2.00 ft   
					.185 m   
					2 
					2 
					2.25 ft   
					.209 m   
					2 
					2 
					3.00 ft   
					.279 m   
					Example:   
					Fig. 43   
					Measured velocities for 20 x 20 in. (500 x 500 mm) filter.   
					Sum of Velocity Readings   
					Number of Readings   
					Average slot velocity   
					(Imperial)   
					= 
					198 + 205   
					= 
					= 
					= 201.5 fpm   
					2 
					2.5 in.   
					3.25 in.   
					14.75 in.   
					3021 + 3749   
					2 
					(Metric)   
					= 3385 m/hr   
					14.25 in.   
					2.75 in.   
					Flow rate for one filter   
					= 
					= 
					Conversion Factor   
					3.0   
					x 
					x 
					Average Velocity   
					Fig. 44   
					201.5 fpm   
					3385 m/hr   
					= 
					604.5 cfm   
					944 m3/hr   
					2.75 in.   
					= 
					.279   
					x 
					= 
					Filter 1   
					Flow Rate   
					Filter X   
					Flow Rate   
					Total hood flow rate   
					= 
					= 
					+ 
					… 
					+ 
					+ 
					604.5   
					+ 
					+ 
					600.3   
					1020   
					592.4   
					1006   
					+ 
					+ 
					2410.5 cfm   
					4012 m3/hr   
					613.3   
					1042   
					= 
					= 
					944   
					Canopy Hood   
					25   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Testing Hood Air Volume   
					Short Circuit Hoods   
					A. Supply   
					Fig. 45   
					All cooking equipment should be off. The hood   
					exhaust should also be off.   
					1. Measuring Velocities   
					• Velocity measurements should be made   
					with a digital 2.75 in. (70 mm) rotating vane   
					anemometer or its equivalent.   
					• One velocity measurement should be taken   
					for every 8 in. (200 mm) of short circuit   
					opening length, starting tight against one   
					edge of the opening, and finishing tight   
					against the other edge. The anemometer   
					should be placed at the bottom edge of the   
					opening, flush with the bottom lip as shown   
					in Fig. 45. Both squareness and placement   
					are important for accuracy.   
					2. Calculate the average slot velocity.   
					3. Calculate the CFM per linear foot by dividing   
					the average velocity by a conversion factor of   
					5.52 per ft. or 1.68 per m.   
					4. Calculate the hoods exhaust volume by   
					multiplying the CFM per linear foot by the total   
					hood length.   
					Example: 4 ft. (1.22 m) short circuit hood (36 in. (.914 m) short circuit opening):   
					Number of readings   
					Average slot velocity   
					= 36 in. / 8 in. => 6 readings   
					(.914 m / .2 m => 6 readings)   
					Sum of Velocity Readings   
					= 
					Number of Readings   
					786 + 900 + 1126 + 1048 + 1111 + 1115   
					6 
					6086   
					6 
					(Imperial)   
					(Metric)   
					= 
					= 
					= 
					= 
					= 1014.3 fpm   
					= 1723 m/hr   
					1335 + 1529 + 1913 + 1780 + 1888 + 1894   
					6 
					10339   
					6 
					Average Slot Velocity   
					Conversion Factor   
					CFM per linear foot   
					= 
					= 
					= 
					1014.3 fpm   
					= 183.8 cfm/linear foot   
					5.52   
					1723 m/hr   
					= 1026 m3/hr   
					1.68   
					3 
					Hood supply volume   
					= CFM/linear foot (or m /hr) x Total Hood Length   
					= 
					= 
					183.8   
					1026   
					x 
					x 
					4 ft.   
					1.22 m   
					= 735.2 cfm   
					= 1252 m3/hr   
					Canopy Hood   
					26   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Amerex Wiring Plan View   
					POWER SOURCE   
					MANUAL RESET RELAY   
					PRM   
					ELECTRIC GAS VALVE   
					MICROSWITCH   
					INSTALLER PROVIDED JUNCTION BOXES   
					BASIC WIRING DIAGRAM   
					POWER SOURCE   
					MANUAL RESET RELAY   
					RED (COMMON)   
					YELLOW (N.O)   
					BLACK (N.C.)   
					GAS VALVE   
					NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL   
					INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR   
					EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.   
					MICROSWITCH   
					BASIC WIRING DIAGRAM   
					MANUAL RESET RELAY   
					L1   
					RED (COMMON)   
					120V/60HZ   
					L2   
					K1   
					Ka   
					PUSHBUTTON SWITCH   
					YELLOW (N.O)   
					K1b   
					BLACK (N.C.)   
					MICROSWITCH   
					CURRENT DRAW MAX:   
					8A RESISTIVE   
					8A INDUCTIVE   
					120VAC   
					GAS VALVE   
					SEE NOTE 3   
					NOTES:   
					1.   
					2.   
					DENOTES FIELD INSTALLATION   
					DENOTES FACTORY INSTALLATION   
					3. GAS VALVE: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF   
					APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871,   
					12872, 12873, 12874, 12875 and 12876.   
					4. K1a and K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.   
					Fig. 46   
					Canopy Hood   
					27   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Ansul Wiring Plan View   
					2 Snap-Action Switches provided by Greenheck   
					may be wired as shown.   
					Option A   
					Relay Part No. 14702   
					Four typical examples shown   
					* K1a and K1b are N.O. when K1 is de-energized   
					Manual Reset Relay   
					L1   
					1 
					Equipment   
					Part No. 14702   
					Power to cooking   
					110V/60HZ   
					equipment   
					2 
					Black   
					Red   
					L2   
					K1*   
					3 
					Shunt Trip Breaker   
					NO   
					Brown   
					K1a   
					N.O.   
					Snap-Action Switch   
					Part No. 423878   
					5 
					6 
					120 VAC   
					Input   
					N 
					K1b N.O.   
					Push Button   
					Switch   
					Gas Valve   
					See Note 3   
					NC   
					7 
					8 
					Electric gas valve - If reset relay is   
					used, see option A or B at right.   
					Mechanical gas shut off valve does not   
					require electrical connection.   
					Alarms   
					NO   
					NO   
					Ansul Snap-Action Switch   
					(Switch contacts shown with Ansul   
					Automan in the cocked position)   
					Voltage Free   
					Option B   
					Relay Part No. 426151   
					Input   
					Contacts for   
					Building Alarm(s)   
					NC   
					Black   
					Red   
					Snap-Action Switch   
					Part No. 423878   
					NC   
					Reset   
					Power   
					Indicator   
					Brown   
					GND   
					Power to   
					Fan(s)   
					A 
					B 
					Screw 5   
					4 
					L2 Neutral   
					L1 Hot   
					Waterwash   
					Fan   
					Starter   
					Relay Coil   
					110 VAC/60HZ   
					3 
					6 
					9 
					3 
					4 
					3 
					2 
					1 
					NO   
					NC   
					4 
					7 
					1 
					Terminal strip in   
					Waterwash Control Panel   
					5 
					Manual Reset Relay   
					(Part No. 426151)   
					Electrical Rating   
					1/3 HP, 10 AMP, 120 VAC   
					1/2 HP, 10 AMP, 240 VAC   
					13 AMP, 28 VDC   
					Gas Valve   
					See Note 3   
					6 
					Fans   
					Note:   
					1.   
					2.   
					NO   
					NC   
					Denotes field installation.   
					Denotes factory installation.   
					120 VAC   
					N 
					Power to   
					3. Gas Valves: “UL Listed electrically-operated safety valve for natural or LP gas   
					as needed of appropriate pressure and temperature rating, 110V/60HZ”   
					or Ansul gas valves.   
					4. Do not use black wire on snap-action switch in normal installation. Black   
					wire may only be used for extraneous alarm, light circuits, etc.   
					Input   
					fan(s)   
					Fan Starter   
					Manual Switch   
					If prohibited by local codes, do not shut down   
					exhaust fans with this method of wiring.   
					Fig. 47   
					Canopy Hood   
					28   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Overall Wiring Plan View   
					C O N T R O L C E N T E R   
					T O M A K E - U P A I R   
					R 
					Y P O W S E U P P L   
					Fig. 48   
					Canopy Hood   
					29   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Wiring for Hood Switch Panels   
					The diagrams below show a typical hood switch panel remote mounted. For hood mounted switches   
					refer to the wiring connection decal on the cover of the junction box on the hood top.   
					The diagram below shows how to wire the exhaust and supply fans with a control panel to a fire   
					suppression contact (FSC1). When wired properly, the suppy fan will be turned off if the fire system is   
					activated and allow the exhaust fan to continue to operate.   
					The fire suppression contact (FSC1) is provided as part of the fire suppression system and is normally   
					mounted in the fire system control box.   
					COMBINED EXHAUST & SUPPLY SWITCHING   
					EXHAUST FAN CONTACT   
					OPTIONAL   
					SUP FAN   
					JUNCTION BOX   
					OL   
					FSC1   
					ON TOP OF HOOD   
					FOR FIELD   
					115VOLT   
					CONTROL   
					CONTROL   
					OL   
					EXH   
					FAN   
					STR   
					SUP   
					FAN   
					STR   
					SUP   
					HTR   
					CTRL   
					SUPPLY FAN CONTACT   
					CONNECTION OF   
					120 VOLT   
					VOLTAGE   
					SUPPLY POWER   
					HOOD SWITCH   
					PANEL DETAIL   
					HOOD   
					LIGHTS   
					LIGHT   
					SWITCH   
					EXHAUST & SUPPLY   
					SWITCH   
					HEATER   
					SWITCH   
					SEPARATE EXHAUST & SUPPLY SWITCHING   
					EXHAUST FAN CONTACT   
					OL   
					SUPPLY FAN CONTACT   
					OL   
					CONTROL   
					VOLTAGE   
					JUNCTION BOX   
					ON TOP OF HOOD   
					FOR FIELD   
					EXH   
					FAN   
					STR   
					SUP   
					FAN   
					STR   
					SUP   
					HTR   
					CTRL   
					H 
					N 
					CONNECTION OF   
					120 VOLT   
					SUPPLY POWER   
					HOOD SWITCH   
					PANEL DETAIL   
					LIGHT   
					SWITCH   
					EXHAUST   
					SWITCH   
					SUPPLY   
					SWITCH   
					HEATER   
					SWITCH   
					HOOD   
					LIGHTS   
					Fig. 49   
					Canopy Hood   
					30   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Circuit Diagrams   
					Single Pole   
					Double Pole   
					OFF   
					ON   
					OFF   
					ON   
					OFF   
					ON   
					OFF   
					ON   
					OFF   
					ON   
					OFF   
					ON   
					ON (NC)   
					ON (NC)   
					ON (NC)   
					ON (NO)   
					ON (NC)   
					ON (NO)   
					ON (NO)   
					ON (NC)   
					ON (NO)   
					ON (NC)   
					ON (NO)   
					ON (NO)   
					ON   
					OFF   
					ON   
					ON   
					ON   
					OFF   
					ON   
					OFF   
					ON   
					Series Circuit   
					Parallel Circuit   
					Off if both are not activated   
					Off if either are not activated   
					On if both are activated   
					Off if both are not activated   
					On if either is activated   
					On if both are activated   
					On if both are not activated   
					Off if either are not activated   
					Off if both are activated   
					On if either is activated   
					Off if either not activated   
					Off if both are activated   
					Fig. 50   
					Canopy Hood   
					31   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Maintenance   
					Daily Maintenance   
					1. Wipe grease from exposed metal surfaces on the hood interior using a clean, dry cloth.   
					2. Visually inspect the filters or cartridges for grease accumulation.   
					3. Remove grease cup, empty contents, and replace cup.   
					Weekly Maintenance   
					1. Remove the grease filters or cartridges and wash in dishwasher or pot sink.   
					Note: Filters installed over heavy grease producing equipment may require more frequent   
					cleaning. See filter cleaning schedule.   
					2. Before replacing filters, clean the interior plenum surfaces of any residual grease accumulations.   
					Periodic Maintenance   
					1. Painted hood exterior surfaces should be cleaned with a mild detergent solution.   
					2. Stainless steel hood exterior surfaces should be cleaned with a mild detergent and then polished   
					with a good grade stainless steel polish to preserve the original luster.   
					Note: Never use abrasive cleaners or chemicals on hood surfaces. Never use chlorine based   
					cleaners or iron wool pads to clean the hood. They may scratch or mar the material. Always rub   
					with the grain of the stainless.   
					3. To maintain optimum performance of your hood and fan, duct cleaning should be performed as   
					often as the application and code requires.   
					4. Re-caulk the hoods with an NSF Approved silicone caulk, (GE SCS1009 or its equivalent) as   
					needed.   
					Condensate Hood Baffle Installation   
					1. Grasp the baffle with drain holes facing   
					CORRECT   
					down and lift into the hood. For short hoods   
					with only one baffle it may be necessary to   
					turn the baffle slightly diagonal to fit it past   
					the drain channel.   
					UPPER HANGER   
					CONDENSATE   
					2. After the baffle clears the drain channel of   
					GUTTER   
					the hood, turn the baffle so it is lined up with   
					the upper hanger in the hood.   
					Fig. 51   
					3. Hook the upper channel of the baffle over   
					INCORRECT   
					the upper hanger of the hood and set the   
					lower edge of the baffle into the condensate   
					gutter. Repeat until all baffles are installed in   
					UPPER HANGER   
					the hood.   
					4. Center the baffle from side to side in the   
					CONDENSATE   
					GUTTER   
					hood.   
					Fig. 52   
					Canopy Hood   
					32   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Grease Grabber™ Filter Installation   
					NOTE: Never install the Second Stage filter in the front filter channel. The Second Stage filter   
					must be installed behind a UL Classified Grease-X-Tractor™ primary filter Model HE or GX.   
					1. Slide the top edge of the Second Stage filter into the top rear filter channel; Fig. 53.   
					2. Lifting the lower edge of the filter past the grease trough, continue to push the top of the filter into   
					the channel.   
					3. When the filter is even with the bottom rear filter channel, set the filter into the channel; Fig. 54.   
					4. Slide the filter to one end of the hood and repeat until all the filters are installed. Make sure the   
					filters are placed tightly together with no visible gaps.   
					5. Latch filters together by connecting hooks to handle on next filter; Fig. 55.   
					6. Install the Grease-X-Tractor™ primary filters in the same manner using the front filter channel.   
					Fig. 53   
					Fig. 54   
					Fig. 55   
					Canopy Hood   
					33   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Grease Grabber™ Filter Cleaning   
					Step 1 Remove the front GX filters: (1A) Remove middle filters first, (1B) slide ends toward middle and remove.   
					GG Filters, second row of filters   
					GX Filters, first row of filters   
					1A   
					1B   
					1C   
					Step 2 Release the hooks that hold the filters together. Slide the top hook upward and the bottom hook downward until the   
					hook releases. Do this to all filters.   
					Slide   
					hooks   
					2A   
					2B   
					2C   
					Step 3 Remove the GG filters, starting in the middle of the hood: (3A) Grab the handles on either side and lift the filter up,   
					(3B) pull the bottom of the filter toward yourself, (3C) lower the filter out of the hood. Repeat this process for each   
					filter. The filters that are on the ends will have to be slid toward the middle and then lifted out.   
					Pull filter down   
					Slide   
					filter up   
					Pull bottom of   
					filter towards yourself   
					3A   
					Step 4 Frequent Maintenance:   
					3B   
					3C   
					Note: Required washing frequency is dependent on type of cooking and quantity of food cooked.   
					- Remove filters from hood and place each filter in a whirlpool sink or dishwasher.   
					- If using a whirlpool sink, cycle for 10 minutes. Use standard dishwash soap. (4A)   
					- If using a dishwasher, cycle it three times to ensure all grease is removed. (4B)   
					- If using standard sink, cover with hot water and degreaser and soak for two hours. Rinse after soaking.   
					Note: For hoods with large quantities of filters, it is acceptable to wash 3 to 4 filters each day, cycling all of the filters in three days.   
					Note: The beads will discolor. Standard cooking will turn the beads yellow in color. Open flame cooking will cause the beads to   
					blacken. Neither affects the performance of the filters.   
					Periodic Inspection:   
					- Each filter may be soaked in hot soapy water for two hours once a month prior to washing if grease build-up is found.   
					- Inspect the filters by holding it up to a light. Light shining through more than six holes in a group indicates filter   
					damage.   
					- For filter replacement, call 1-800-337-7400   
					4A   
					4B   
					Step 5 Replace GG filters in hood. Do Step 3 in reverse order. (3C, then 3B, then 3A)   
					Step 6 Latch filters together by connecting the hooks to the handle on the next filter. Slide hook on from the top and bottom   
					of the handle. Do not try to snap the hooks into place. Do Step 2 in reverse.   
					Step 7 Replace the front GX filters. Do Step 1 in reverse. Be sure to install filters in the ends of the hood first, then install the   
					filters in the middle of the hood (1B, then 1A)   
					Caution: To prevent damage to filter media, do not wash second stage filters in detergents that contain   
					hydroxides such as sodium hydroxide or potassium hydroxide.   
					Canopy Hood   
					34   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Filter Washing Frequency Guide   
					NOTE: Standard cooking will turn the beads yellow in color. Open flame cooking will cause the beads to   
					blacken. Neither affects the performance of the beads.   
					Caution: To prevent damage to filter media, do not wash second stage filters in detergents that contain   
					hydroxides such as sodium hydroxide or potassium hydroxide.   
					Time   
					or   
					Cycles   
					Baffle Filter or   
					Grease-X-Tractor™   
					Wash Frequency   
					Washing Equipment   
					Cooking   
					Equipment   
					Frequency   
					Required   
					Preference   
					Chemical   
					Type   
					Temp   
					Every 3 days   
					2 Cycles   
					Twice a week   
					1 Cycle   
					Griddle   
					Fryer   
					Every 3 days   
					Weekly   
					Daily   
					2 Cycles   
					2 Cycles   
					Commercial   
					Grade Dish   
					Washer   
					Dish   
					Washer   
					Detergent   
					1 
					Best   
					180º F   
					Min   
					Daily   
					2 Cycles   
					Daily   
					Charbroiler   
					Wok   
					2 Cycles   
					Daily   
					2 Cycles   
					2 Cycles   
					Every 3 days   
					2 Cycles   
					Twice a week   
					2 Cycles   
					Daily   
					Griddle   
					Fryer   
					Every 3 days   
					Weekly   
					Daily   
					3 Cycles   
					Low Temp.   
					Dish Washer   
					(Chemical   
					Sanitizer)   
					3 Cycles   
					Dish   
					Washer   
					Detergent   
					2 
					3 
					4 
					140º F   
					Charbroiler   
					Wok   
					4 Cycles   
					2 Cycles   
					Daily   
					Daily   
					4 Cycles   
					2 Cycles   
					Every 3 days   
					5 minutes   
					Twice a week   
					5 minutes   
					Daily   
					Griddle   
					Fryer   
					Every 3 days   
					Weekly   
					Daily   
					10 Minutes   
					10 Minutes   
					15 Minutes   
					15 Minutes   
					15 Minutes   
					15 Minutes   
					25 Minutes   
					25 Minutes   
					Power   
					Wash Sink   
					(Whirlpool)   
					with Heater   
					180º F   
					Min   
					Pot & Pan   
					Detergent   
					Charbroiler   
					Wok   
					5 minutes   
					Daily   
					Daily   
					5 minutes   
					Daily   
					5 minutes   
					Twice a week   
					5 minutes   
					Daily   
					Griddle   
					Fryer   
					Every 3 days   
					Weekly   
					Daily   
					Power   
					Wash Sink   
					(Whirlpool)   
					no Heater   
					Pot & Pan   
					Detergent   
					140º F   
					Charbroiler   
					Wok   
					10 minutes   
					Daily   
					10 minutes   
					Daily   
					Daily   
					Griddle   
					Fryer   
					Every 2 days   
					Every 2 days   
					1 Hour   
					1 Hour   
					Soak 10 min., then scrub with   
					scour pad and bottle brush   
					Daily   
					Pot Sink   
					with Heater   
					Pot & Pan   
					Detergent   
					and/or   
					Soak 5 min., then scrub with   
					scour pad and bottle brush   
					5 
					180º F   
					(rinse with   
					sprayer after   
					soaking)   
					Degreaser   
					Charbroiler   
					Wok   
					Daily   
					Daily   
					2 Hours   
					2 Hours   
					Daily   
					Soak 10 min., then scrub with   
					scour pad and bottle brush   
					2 Hours   
					Griddle   
					Fryer   
					Daily   
					Change hot water   
					every 30 minutes   
					Pot Sink   
					Commercial   
					Grade   
					Kitchen   
					no Heater   
					2 Hours   
					Every 2 days Change hot water   
					every 30 minutes   
					Daily   
					6 
					140º F   
					Soak 10 minutes then scrub   
					with scour pad & bottle brush   
					(rinse with   
					sprayer after   
					soaking)   
					Worst   
					Degreaser   
					Charbroiler   
					Wok   
					Not Recommended   
					Not Recommended   
					Canopy Hood   
					35   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Troubleshooting   
					Problem: Exhaust fan is not operating or is not operating at design levels.   
					Is the fan receiving power?   
					Replace fuses, reset circuit breakers, check disconnect.   
					Is the belt loose or broken?   
					Replace or tighten belt.   
					Is the fan rotating in correct direction?   
					Have the electrician correctly wire the fan.   
					Problems with make-up air may interfere with the exhaust fan -   
					check the manufacturers installation manual.   
					Is the make-up air operating?   
					Does the airflow need to be increased?   
					Adjust or replace pulleys to increase fan RPM, install a larger motor.   
					Clean the fan wheel/blade, replace fan wheel if damaged, check for   
					loose bolts, check for broken or damaged components, check for   
					rags and other foreign objects.   
					Does the fan vibrate?   
					Problem: Hood is full of smoke. There is smoke coming out of the edges of the hood.   
					Is the fan operating at design levels?   
					See exhaust fan troubleshooting section.   
					Refer to test and balance report, design specifications and fan   
					curves; have an electrician check the motor amperage; try removing   
					the filter temporarily to see if capture improves. (Make sure to   
					replace filter to prevent risk of fire!); switch to different filters with   
					lower static pressure.   
					Is the fan correctly sized?   
					Are the filters in good condition?   
					Clean filters, replace damaged filters, properly position filters.   
					Is there sufficient make-up air?   
					(Kitchen should be in a slight negative   
					but not excessive. Check to see if there   
					is a strong draft through an open door).   
					Check make-up air unit, increase make-up air, make-up air should be   
					evenly distributed throughout the kitchen.   
					Does the current cooking equipment   
					match the original design?   
					Adjust or replace fan to match the cooking equipment load.   
					One hood may be over exhausting and the other hood not drawing   
					enough. Restrict second hood to help problem hood.   
					Are there multiple hoods on one fan?   
					Are there closed dampers in the duct?   
					Is the ductwork complex or to small?   
					Is the ductwork obstructed?   
					Open dampers.   
					Change to a higher static fan, modify the ductwork.   
					Clear obstruction.   
					Is this a short circuit hood?   
					Turn off or reduce the amount of air supplied to short circuit.   
					Problem: Smoke blows away before reaching the bottom of the hood.   
					Are there cooling fans directed at the   
					hood or cooking equipment?   
					Turn off or redirect fans.   
					Are there ceiling diffusers directing air at Move diffusers to more neutral area or replace with a diffuser that   
					the hood?   
					directs air away from the hood.   
					Are there open windows or doors?   
					Close windows and doors.   
					Find source of the draft and eliminate, add side skirts to hood (test   
					with cardboard – use stainless for permanent side skirts); increase   
					the amount of overhang on the spillage side; add a 6 in. lip around   
					the base of the hood (test with cardboard – use stainless for   
					permanent side skirts); make-up air should be spread out evenly   
					through the kitchen.   
					Are there cross drafts or other drafts in   
					the kitchen?   
					Add side skirts to hood (test with cardboard first); increase the   
					amount of overhang on spillage side.   
					Is the hood near a main walkway?   
					Canopy Hood   
					36   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Troubleshooting   
					Problem: Smoke blows away before reaching the bottom of the hood.   
					Are there pass-thru windows near   
					the hood?   
					Adjust amount and locations of make-up air to eliminate drafts   
					through the pass-thru windows.   
					Is this an air curtain hood?   
					Turn off or reduce the amount of make-up air.   
					Try turning off or reducing the amount of make-up air; block off   
					portions of the supply to direct air away from the problem area (test   
					with cardboard).   
					Is the make-up air part of the hood   
					or an attached plenum?   
					Problem: Pilot lights are being blown out or cooking equipment is being cooled by make-up air.   
					Try turning off or reducing the amount of make-up air; block off   
					portions of the supply to direct air away from the problem area (test   
					with cardboard first); remove any obstructions in front of supply that   
					Are there drafts from make-up air?   
					directs air toward cooking equipment.   
					Problem: Cold air can be felt by the cook at the hood.   
					Is this a short circuit hood?   
					Turn off or reduce the amount of air supplied to short circuit.   
					Turn off or reduce the amount of air supplied to the air curtain; heat   
					the supply air.   
					Is this an air curtain hood?   
					Is the make-up air part of the hood   
					or an attached plenum?   
					Try turning off or reducing the amount of make-up air; heat the   
					supply air.   
					Problem: The kitchen gets hot.   
					Is the hood capturing?   
					Hood is not drawing enough air, see sections above on fan   
					performance and hood capture.   
					Is this an air curtain hood?   
					Turn off or reduce the amount of air supplied to the air curtain.   
					Is the make-up air part of the hood   
					or an attached plenum?   
					Try turning off or reducing the amount of make-up air; cool the   
					supply air.   
					Problem: Cooking odors in the dining area.   
					Hood is not drawing enough air, see sections above on fan   
					performance and hood capture.   
					Is the hood capturing?   
					Is there a draft through doors between   
					the kitchen and dining area?   
					Decrease make-up air in the kitchen; increase exhaust air through   
					hood.   
					Problem: Grease is running off the hood.   
					Is there grease on top of the hood?   
					Is the caulk missing or damaged?   
					Is the grease cup inserted properly?   
					Exhaust duct is not correctly welded.   
					Clean problem area and re-caulk.   
					Put grease cup back in place.   
					Problem: Hood is noisy.   
					Is the fan running in the correct direction? See exhaust fan troubleshooting section.   
					Are the filters in place?   
					Replace missing filters.   
					Is the hood over exhausting?   
					Slow down fan (see exhaust fan troubleshooting section)   
					Canopy Hood   
					37   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Before calling your manufacturers representative to report a problem have the   
					following information available:   
					1. Review / summary of troubleshooting section in installation operation manual.   
					2. Hood model and serial number.   
					3. Current cooking equipment line-up.   
					4. Size of hood (length, width and height).   
					5. Island or wall configuration.   
					6. Multiple hoods on one fan.   
					7. Nature of spillage (one end; all around the edges).   
					8. Does the smoke make it to the hood?   
					9. Height hood is mounted above finished floor.   
					10. How make-up air is brought into the kitchen (hood, ceiling diffusers, separate plenum).   
					11. Is exhaust system controlled by a variable volume system?   
					12. Is the fan noisy?   
					Replacement Parts   
					GREENHECK   
					FILTER DESCRIPTION   
					PART NUMBER   
					(HEIGHT X WIDTH X DEPTH)   
					457626   
					457628   
					457632   
					457634   
					457627   
					457629   
					457633   
					457635   
					851656   
					851657   
					851659   
					851660   
					851703   
					851704   
					851706   
					851707   
					851709   
					851710   
					851712   
					851713   
					458763   
					458764   
					454878   
					454879   
					852208   
					852207   
					852388   
					852389   
					16 x 16 x 2 Aluminum Baffle Filter   
					16 x 20 x 2 Aluminum Baffle Filter   
					20 x 16 x 2 Aluminum Baffle Filter   
					20 x 20 x 2 Aluminum Baffle Filter   
					16 x 16 x 2 Stainless Steel Baffle Filter   
					16 x 20 x 2 Stainless Steel Baffle Filter   
					20 x 16 x 2 Stainless Steel Baffle Filter   
					20 x 20 x 2 Stainless Steel Baffle Filter   
					16 x 16 High Velocity Cartridge Filter   
					16 x 20 High Velocity Cartridge Filter   
					20 x 16 High Velocity Cartridge Filter   
					20 x 20 High Velocity Cartridge Filter   
					16 x 16 Grease-X-Tractor™ Aluminum Filter   
					16 x 20 Grease-X-Tractor™ Aluminum Filter   
					20 x 16 Grease-X-Tractor™ Aluminum Filter   
					20 x 20 Grease-X-Tractor™ Aluminum Filter   
					16 x 16 Grease-X-Tractor™ SS Filter   
					16 x 20 Grease-X-Tractor™ SS Filter   
					20 x 16 Grease-X-Tractor™ SS Filter   
					20 x 20 Grease-X-Tractor™ SS Filter   
					® 
					16 x 16 Flame Gard 1 Baffle Filter   
					® 
					16 x 20 Flame Gard 1 Baffle Filter   
					® 
					20 x 16 Flame Gard 1 Baffle Filter   
					® 
					20 x 20 Flame Gard 1 Baffle Filter   
					20 x 16 Grease Grabber™ Second Stage Filter   
					20 x 20 Grease Grabber™ Second Stage Filter   
					16 x 16 Grease Grabber™ Second Stage Filter   
					16 x 20 Grease Grabber™ Second Stage Filter   
					Canopy Hood   
					38   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Replacement Parts   
					GREENHECK   
					REGISTERS   
					PART NUMBER   
					452700   
					452701   
					452702   
					452703   
					453796   
					453797   
					453798   
					453799   
					452729   
					452730   
					452731   
					452732   
					452733   
					24 x 8 Aluminum Single Deflection H-OB   
					36 x 8 Aluminum Single Deflection H-OB   
					36 x 8 Aluminum Single Deflection H-OB   
					44 x 8 Aluminum Single Deflection H-OB   
					24 x 12 Aluminum Single Deflection H-OB   
					36 x 12 Aluminum Single Deflection H-OB   
					38 x 12 Aluminum Single Deflection H-OB   
					44 x 12 Aluminum Single Deflection H-OB   
					24 x 8 Aluminum 38° Fixed Blade RA-OB   
					30 x 8 Aluminum 38° Fixed Blade RA-OB   
					36 x 8 Aluminum 38° Fixed Blade RA-OB   
					38 x 8 Aluminum 38° Fixed Blade RA-OB   
					44 x 8 Aluminum 38° Fixed Blade RA-OB   
					GREENHECK   
					PART NUMBER   
					SWITCHES   
					850551   
					851776   
					851777   
					851778   
					851779   
					851780   
					851781   
					851782   
					851783   
					851784   
					851510   
					851511   
					851512   
					851618   
					Light Switch Only   
					Fan Switch Only   
					Light Switch & Fan Switch ( 2 switches)   
					Fan Switch & Heat Switch (2 switches)   
					Exhaust, Fan & Supply Switch (2 switches)   
					Light, Fan & Heat Switch (3 switches)   
					Light, Exhaust, Supply Separate Switch (3 switches)   
					Exhaust, Supply, Heat Separate Switch (3 switches)   
					Light, Exhaust, Supply, Heat Separate Switch (4 switches)   
					Fan Switch & Temper (3 position) (2 switches)   
					Light, Fans, & Temper (3 position) (3 switches)   
					Exhaust, Supply, & Temper (3 position) (3 switches)   
					Light, Exhaust, Supply, & Temper (3 position) (4 switches)   
					Automatic Fire Damper Test Switch   
					GREENHECK   
					PART NUMBER   
					MISCELLANEOUS   
					451131   
					453498   
					851744   
					851834   
					851747   
					Grease Cup   
					Glass Globes for hood lights (clear)   
					Grease Extractor Filter Removal Tool   
					Baffle Filter Removal Tool   
					High Velocity Cartridge Filter Removal Tool   
					Canopy Hood   
					39   
					® 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Warranty   
					Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from   
					the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option   
					when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of   
					one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the   
					nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.   
					As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications   
					without notice.   
					Contact Greenheck Fan Corporation:   
					Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com   
					® 
					452413 • Canopy Hood, Rev. 7, March 2008   
					Copyright 2008 © Greenheck Fan Corp.   
					40   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 | 
Grizzly Switch G8291 User Manual
Hamilton Beach Iron 840121300 User Manual
Hamilton Beach Stereo System 840095500 User Manual
Honeywell Beverage Dispenser 88080 User Manual
Honeywell Thermostat CT3451 User Manual
Hubbell Work Light UE28 User Manual
Husky Impact Driver HDT202 User Manual
IBM Computer Drive ATA 3 User Manual
iLive Clock Radio ICP310B User Manual
Image Treadmill IMTL079051 User Manual