Graco Heat Pump 3A2527E User Manual

Instructions - Parts  
24P822 E-Flo® DC Control  
Module Kit  
3A2527E  
EN  
User Interface for E-Flo® DC Pumps with an Advanced Motor.  
For professional use only.  
Important Safety Instructions  
Read all warnings and instructions in this manual, the supplied  
ADCM manual, and the E-Flo DC manuals.  
Save these instructions.  
See the separate manual (supplied)  
for complete warnings and approvals  
information about the 24L097 Advanced  
Display Control Module (ADCM).  
PROVEN QUALITY. LEADING TECHNOLOGY.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Module  
The Control Module provides the interface for users  
to enter selections and view information related to  
setup and operation.  
4. Install the module (1) in the bracket (6a), making  
sure the tabs at the bottom of the bracket engage  
the slots in the module, and the lip at the top of  
the bracket holds the module securely in place.  
The screen backlight is factory set to remain on,  
even without screen activity. See Setup Screen 4  
to set the backlight timer to your preference. Press  
any key to restore.  
5. Connect the accessory cable (C), using the  
tie (12) as a strain relief as shown. See  
6. Restore power to the motor.  
Keys are used to input numerical data, enter setup  
screens, navigate within a screen, scroll through  
screens, and select setup values.  
Installation  
Install the Control Module  
1. Shut off and lock out power to the motor.  
2. Install the jumper connector (5) over the top two  
terminals of the motor, using the screw (5a).  
NOTE: To connect up to 8 motors together, see  
Appendix A in the E-Flo DC Motor Manual, where  
the control module is the referenced intrinsically  
safe (IS) apparatus.  
3. Assemble the bracket kit (6a-6f) and the holder  
and tie (11, 12) as shown.  
Figure 1 Install the Control Module  
3A2527E  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Install Optional Accessory Kits  
Optional accessory kits are available for purchase  
separately, including a pressure transducer kit (PN  
24R050 for 4–ball pumps; PN 24Y245 for 2–ball  
pumps), a start/stop switch kit (PN 16U729), and a  
controller kit (24V001 ) for a back pressure regulator.  
BPR Controller  
The BPR (back pressure regulator) controller enables  
the user to control the back fluid pressure from the  
control module.  
1. Mount the BPR controller using the bracket  
provided.  
Pressure Transducer Kit  
1. To measure fluid pressure, install the pressure  
transducer in the fluid line with a tee fitting.  
2. Connect a supply air line to the BPR controller  
air inlet (105).  
Option  
Description  
NOTICE  
Closed Loop Control  
Enabled  
If closed loop control  
is enabled on Setup  
Screen 8 (transducer  
1) or Setup Screen 9  
(transducer 2), install  
the transducer near the  
pump outlet, not near  
the end of the circulation  
line.  
To prevent equipment damage, always apply  
air pressure to the BPR controller before  
applying power to the system.  
3. Connect an air line from the BPR controller air  
output (108) to the BPR.  
4. Connect the BPR controller input cable (102) to  
Port 8 on the control module.  
Closed Loop Control  
Not Enabled  
Install the transducer  
where needed.  
2. Connect the transducer cable to Port 7  
(transducer 1) or Port 10 (transducer 2) on the  
control module.  
Start/Stop Switch Kit  
1. Mount the switch near the control module, using  
the bracket provided.  
2. Connect the switch cable to Port 4 on the control  
module.  
4
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Cable Connection  
Order an accessory cable (C) from Table 1. Connect the cable to Port 3 on the bottom of the control module  
(see Fig. 2). Connect the other end to the power terminal (PT) on the motor (see Fig. 3). Connect other  
cables as described in Table 2.  
Table 1 CAN Cables  
Cable Part  
No.  
Description  
16P911  
Intrinsically safe CAN cable, female  
x female, 3 ft (1 m)  
16P912  
Intrinsically safe CAN cable, female  
x female, 25 ft (8 m)  
Figure 2 ADCM Connectors  
Table 2 ADCM Cable Connections  
ADCM Port  
Number  
Connector Purpose  
1
Fiber Optic RX - to PLC  
Fiber Optic TX - to PLC  
Power and CAN communication  
Start/stop input  
2
3
4
5
Fiber Optic RX - to next ADCM  
Fiber Optic TX - tos next ADCM  
Pressure transducer 1  
BPR control 4-20mA output  
Not used  
6
7
8
9
10  
Pressure transducer 2  
Figure 3 Motor Power Terminal  
3A2527E  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Module Screens  
Module Keys  
The Control Module has two sets of screens:  
Run and Setup. For detailed information see  
Fig. 4 is a view of the control module display and  
keys. Table 2 explains the function of the membrane  
keys on the control module. As you move through  
the screens, you will notice that most information  
is communicated using icons rather than words  
to simplify global communication. The detailed  
screen descriptions in Run Screens, page 12, and  
Setup Screens, page 16, explain what each icon  
represents. The two softkeys are membrane buttons  
whose function correlates with the screen content to  
the immediate left of the button.  
Press  
to toggle between the Run screens and  
the Setup screens.  
NOTICE  
To prevent damage to the softkey buttons, do not  
press the buttons with sharp objects such as pens,  
plastic cards, or fingernails.  
Figure 4 Control Module Keypad and Display  
6
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Table 3 Module Keys  
Membrane Keys  
Softkeys  
Enter Screen. Highlight data that can be edited.  
Also changes the function of the Up/Down  
arrows so they move between data fields on  
the screen, rather than between screens.  
Press to toggle between Run screens  
and Setup screens.  
Error Reset: Use to clear alarm after cause  
has been fixed. When there is no alarm to  
clear, this key will set the active pump’s  
profile to Stop. Also used to cancel data  
entered and return to original data.  
Exit Screen. Exit data editing.  
Up/Down Arrows: Use to move between  
screens or fields on a screen, or to increment  
or decrement the digits in a settable field.  
Enter. Press to activate a field for editing or to accept  
the highlighted selection on a dropdown menu.  
Right. Move to the right when editing number fields. Press  
again to accept the entry when all digits are correct.  
Softkeys: Use varies by screen.  
See columns at right.  
Reset. Reset totalizer to zero.  
Activate Profile. This softkey is disabled by  
default, and only appears if the “Profile Lock”  
box is checked on Setup Screen 15, page 29.  
Press to activate the profile just edited.  
Search. Press in Run Screen 1 to make the  
active pump blink for identification.  
3A2527E  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Icons  
As you move through the screens, you will notice that most information is communicated using icons rather  
than words to simplify global communication. The detailed screen descriptions in Run Screens, page 12, and  
Setup Screens, page 16, explain what each icon represents.  
Screen Icons  
Screen Icons  
Jog Mode  
Profile Number  
Jog Up/Down  
Pump Number  
Speed  
Cycles  
Cycles Total  
Maintenance  
Volume  
Units  
Pump Pressure  
Flow Rate  
Target  
Pressure Transducer Off  
Zero Offset  
Transducer  
Calibration Scale  
Serial Number  
Pressure  
In Setup Mode  
Mode Select  
Flow Mode  
Control Location  
Pressure Mode  
Lower Size  
Local Control  
Modbus Device  
Serial Port  
PLC/Remote Control  
Modbus Address  
Back Pressure  
Regulator  
Serial Baudrate  
Maximum  
Limit  
Minimum  
Limit  
Calendar  
Clock  
Maximum and  
Minimum Limits  
Deviation Enable  
Lock Profile  
Password  
Alarm Enable  
8
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Screen Navigation and Editing  
Refer to this section if you have questions about  
screen navigation or about how to enter information  
and make selections.  
Reset Field  
The reset field is used for totalizers. Press  
reset the field to zero.  
to  
All Screens  
When all data is correct, press  
to exit the screen.  
1. Use  
to move between screens.  
Then use  
to move to a new screen, or  
to move between Setup screens and Run screens.  
2. Press  
to enter a screen. The first data field  
on the screen will highlight.  
Initial Setup  
3. Use  
change.  
to highlight the data you wish to  
NOTE: Before creating the pump profiles in Setup  
Screens 1 through 4, you must set up the system  
parameters in Setup Screens 5 through 15, as  
follows.  
4. Press  
to edit.  
Drop Down Field  
1. Press  
to enter the Setup screens. Setup  
1. Use  
to highlight the correct choice from  
Screen 1 will appear.  
the dropdown menu.  
2. Scroll to Setup Screen 5.  
2. Press  
to select.  
to cancel.  
3. Press  
Number Field  
1. The first digit will be highlighted. Use  
to change the number.  
3. See Setup Screen 5, page 22, and select the  
lower used in your system.  
2. Press  
to move to the next digit.  
4. Continue setting the system parameters  
3. When all digits are correct, press  
accept.  
again to  
4. Press  
to cancel.  
5. Scroll to Setup Screen 1. Establish  
the profiles for each pump. See  
Check Box Field  
A check box field is used to enable or disable features  
in the software.  
1. Press  
box.  
to toggle between  
and an empty  
2. The feature is enabled if a  
is in the box.  
3A2527E  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
INITIAL SETUP  
(Setup Screens 5–14)  
SETUP AND EDIT PROFILES  
(Setup Screens 1–4)  
RUN  
(Run Screens 1–8)  
3A2527E  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Run Screens  
Run Screen 1 Key  
Enter the screen.  
The Run screens display current target values and  
performance for a selected pump and profile. Any  
alarms will display in the sidebar at the right of the  
screen. Screens 5–8 display a log of the last 20  
alarms for the active pump.  
For systems with multiple pumps and  
one display, select the desired pump (1  
to 8), using the pull-down menu.  
Select the desired profile (1 to 4), using  
the pull-down menu.  
Select from the profile drop-down menu  
to stop the pump.  
Displays current pump speed in cycles  
per minute.  
Information displayed on the Run screens  
corresponds to the Modbus Registers. See  
The active pump and profile may be changed in Run  
Screens 1, 2, and 3.  
Run Screen 1  
Displays current pump pressure as a  
percentage. If a transducer is used, this  
icon is replaced by the pressure icon.  
Displays current flow rate, in units as  
selected in Setup Screen 13, page 27.  
This screen displays information for a selected  
pump and profile. A box around an icon indicates  
which mode the active pump and profile is running  
(pressure or flow).  
Exit the screen.  
Signals the active pump to blink code 9  
for identification.  
Figure 5 Run Screen 1  
Figure 6 Select a Pump  
Figure 7 Select a Profile  
12  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Run Screen 2  
Run Screen 3  
This screen displays pressure settings for the active  
pump and profile.  
This screen displays fluid flow settings for the active  
pump and profile.  
NOTE: Some fields are grayed out, depending on  
setup selections.  
NOTE: Some fields are grayed out, depending on  
setup selections.  
Figure 8 Run Screen 2, in Pressure Mode  
Figure 10 Run Screen 3, in Pressure Mode  
Figure 9 Run Screen 2, in Flow Mode  
Figure 11 Run Screen 3, in Flow Mode  
Run Screen 2 Key  
Enter the screen.  
Run Screen 3 Key  
Enter the screen.  
For systems with multiple pumps and  
one display, select the desired pump (1  
to 8), using the pull-down menu.  
For systems with multiple pumps and  
one display, select the desired pump (1  
to 8), using the pull-down menu.  
Select the desired profile (1 to 4), using  
the pull-down menu.  
Select the desired profile (1 to 4), using  
the pull-down menu.  
Select from the profile drop-down menu  
to stop the pump.  
Select from the profile drop-down menu  
to stop the pump.  
Displays pressure maximum (first data  
field), target (second data field), and  
minimum (third data field), as selected  
disable the pressure alarms.  
The first line displays the maximum  
flow rate and maximum cycle rate  
(displayed as a cpm conversion of the  
maximum flow setting). The second  
line displays the target flow rate. The  
third line displays the minimum flow  
rate. See Setup Screen 3, page 19 to  
establish these settings. See  
Exit the screen.  
disable the flow alarms.  
Exit the screen.  
3A2527E  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Run Screen 4  
Run Screens 5–8  
This screen displays the current pressure readings of  
transducers 1 and 2. Pressure can be displayed as  
psi, bar, or MPa. See Setup Screen 13, page 27.  
Run Screens 5–8 display a log of the last 20 alarms,  
with date and time. The currently active pump is  
displayed in a box at the top left of the screen.  
Figure 12 Run Screen 4  
Figure 13 Run Screens 5–8 (Screen 5 shown)  
14  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Notes  
3A2527E  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Setup Screens  
Setup Screen 1 Key  
Enter the screen.  
Use the Setup screens to set control  
parameters for the motor. See  
information on how to make selections and enter  
data.  
Pump selection — See Step 1.  
Profile selection — See Step 2.  
Inactive fields are grayed-out on a screen.  
Information displayed on the Setup screens  
corresponds to the Modbus Registers. See  
Pressure mode or Flow mode — See  
Step 3  
NOTE: Before setting up profiles on Setup Screens  
1–4, do the initial setup on Setup Screens 5–15.  
Screens 5–15 establish the configuration for your  
system and affect the displayed data.  
Setting for Back Pressure Regulator —  
See Step 4.  
Press to accept the selections.  
Setup Screen 1  
This softkey is disabled by default, and  
only appears if the “Profile Lock” box is  
Press to activate the profile just edited.  
Use this screen to set the operating mode for a  
selected pump and profile.  
Exit the screen.  
Figure 14 Setup Screen 1  
16  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
1. For systems with multiple pumps and one  
display, select the desired pump (1 to 8), using  
the pull-down menu.  
In flow mode, the motor will maintain a  
constant speed to maintain the target flow rate  
set on Setup Screen 3, regardless of the fluid  
pressure, up to the pump’s maximum working  
pressure.  
Figure 15 Select Pump Number  
Figure 17 Select Mode (Pressure Mode Shown)  
2. Select the desired profile (1 to 4), using the  
pull-down menu.  
4. If the system is equipped with a back pressure  
regulator (BPR), set the target air pressure to the  
BPR from 0 to 100 percent (approximately 1 to  
100 psi). Leave the field set to 000 for a system  
with no BPR. See manual 332142 for information  
on the BPR control kit.  
Figure 16 Select Profile Number  
3. Select the desired operating mode (pressure or  
flow), using the pull-down menu.  
In pressure mode, the motor will adjust the  
pump speed to maintain the fluid pressure  
percentage set on Setup Screen 2. If the flow  
limit is reached before the target pressure, the  
unit will stop driving to the pressure (if set as  
an alarm).  
Figure 18 Set Back Pressure Regulator  
3A2527E  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Setup Screen 2  
Use this screen to set the maximum, target, and  
minimum fluid pressure for a selected pump and  
profile. In pressure mode, you will set a target fluid  
pressure. In flow mode, you will set a maximum  
fluid pressure. In either pressure or flow mode,  
a minimum pressure may be set if desired. See  
Setup Screen 4, page 20, to specify how the system  
will respond if the pump begins to operate outside of  
the set boundaries.  
1. For systems with multiple pumps and one  
display, select the desired pump (1 to 8), using  
the pull-down menu.  
2. Select the desired profile (1 to 4), using the  
pull-down menu.  
3. In flow mode, set the desired maximum pump  
fluid pressure, as a percentage of the maximum  
pressure of your pump. NOTE: The motor will  
not run if the profile does not have a maximum  
pressure setting. This field is not used in  
pressure mode.  
Setup Screen 2 Key  
Enter the screen.  
Pump selection — See Step 1.  
Profile selection — See Step 2.  
Fluid pressure maximum— See Step 3.  
Fluid pressure target — See Step 4.  
4. In pressure mode, set the desired fluid pressure  
target as a percentage of the maximum pressure  
of your pump. This field is not used in flow mode.  
Fluid pressure minimum — See Step 5.  
Press to accept the selections.  
This softkey is disabled by default, and  
only appears if the “Profile Lock” box is  
Press to activate the profile just edited.  
Exit the screen.  
NOTE: If closed loop pressure is enabled, the  
target pressure will be displayed as a pressure  
value rather than a percentage of maximum  
enable closed loop pressure control.  
5. If desired, set a minimum pump fluid pressure,  
as a percentage of the maximum fluid pressure  
of your pump.  
18  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Screen 3  
Use this screen to set your flow rate settings for a  
selected pump and profile. In pressure mode, you  
will set a maximum flow rate. In flow mode, you  
will set a target flow rate. In either pressure or flow  
mode, a minimum flow rate may be set if desired.  
See Setup Screen 4 to specify how the system will  
respond if the pump begins to operate outside of the  
set boundaries.  
1. For systems with multiple pumps and one  
display, select the desired pump (1 to 8), using  
the pull-down menu.  
2. Select the desired profile (1 to 4), using the  
pull-down menu.  
3. In flow mode, set a target flow rate. This field is  
not used in pressure mode.  
Setup Screen 3 Key  
Enter the screen to set or change  
preferences.  
Pump selection — See Step 1.  
Figure 19 Flow Mode: Flow Rate Settings  
Profile selection — See Step 2.  
4. In pressure mode, set the maximum flow rate.The  
software will calculate the number of pump cycles  
needed to achieve that flow rate. This field is not  
used in flow mode.  
Flow rate maximum— See Step 3.  
Flow rate target— See Step 4.  
Flow rate minimum — See Step 5.  
Press to accept the selections.  
NOTE: The motor will not run if the profile does  
not have a maximum flow rate setting.  
This softkey is disabled by default, and  
only appears if the “Profile Lock” box is  
Press to activate the profile just edited.  
Exit data editing.  
Figure 20 Pressure Mode: Flow Rate Settingss  
5. If desired, set a minimum flow rate.  
NOTE: With flow rate units of cc/min, the maximum  
value that can be displayed is 9999. If the field  
displays ####, the saved value is out of range. Go to  
Setup Screen 13, page 27 and change the flow rate  
to a larger unit. Return to this screen and reduce the  
setting to a lower value that will be within the display’s  
range, then reset the flow rate units to cc/min.  
3A2527E  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Screen 4  
Setup Screen 4 Key  
Enter the screen to set or change  
preferences.  
Use this screen to specify how the system will  
respond if the pump begins to operate outside of  
the pressure and flow settings established on Setup  
Screen 2 and Setup Screen 3. The operating mode  
(pressure or flow, set on Setup Screen 1) determines  
which fields are active.  
Pressure Alarm Enable  
Line 1 (Pressure Maximum): use  
dropdown menu to set as Limit,  
Deviation, or Alarm.  
Line 2 (Pressure Minimum): use  
dropdown menu to set as Limit,  
Deviation, or Alarm.  
Flow Rate Alarm Enable  
Figure 21 Alarm Preference Menu  
Line 3 (Flow Maximum): use dropdown  
menu to set as Limit, Deviation, or Alarm.  
/
Limit: The pump continues to run and issues  
no alert.  
Line 4 (Flow Minimum): use dropdown  
menu to set as Limit, Deviation, or Alarm.  
Press to accept the selections.  
– Maximum pressure set to Limit: The system  
reduces the flow if necessary to prevent the  
pressure from exceeding the limit.  
This softkey is disabled by default, and  
only appears if the “Profile Lock” box is  
Press to activate the profile just edited.  
– Maximum flow set to Limit: The system reduces  
the pressure if necessary to prevent the flow  
from exceeding the limit.  
– Minimum pressure or flow set to Limit: The  
system takes no action. Use this setting if no  
minimum pressure or flow setting is desired.  
Exit data editing.  
Deviation: The system alerts you to the  
problem, but the pump may continue to run  
past the maximum or minimum settings until the  
system’s absolute pressure or flow boundaries are  
reached.  
Alarm: The system alerts you to the alarm  
cause and shuts down the pump.  
Figure 22 Setup Screen 4 (In Pressure Mode)  
Figure 23 Setup Screen 4 (In Flow Mode)  
20  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Pressure Mode Examples  
Flow Mode Examples  
Runaway Control: The user may choose to set the  
maximum flow to Alarm. If the flow rate exceeds  
the maximum entered on Setup Screen 3, an Alarm  
Runaway Control: The user may choose to set  
the minimum pressure to Alarm. If a hose bursts,  
the pump will not change speed, but the back  
pressure will fall. When the pressure falls below  
the minimum entered on Setup Screen 2, an Alarm  
symbol  
shut down.  
will show on screen and the pump will  
symbol  
shut down.  
will show on screen and the pump will  
Detect a Plugged Filter or Pipe: The user may  
choose to set the minimum flow to Deviation. If  
the flow rate drops below the minimum entered on  
Protect Connected Equipment: The user may  
choose to set the maximum pressure to Limit to  
prevent the connected equipment from excessive  
pressure.  
Setup Screen 3, a Deviation symbol  
will show  
on screen to warn the user that action should be  
taken. The pump continues to run.  
Detect a Plugged Filter or Pipe: The user may  
choose to set the maximum pressure to Deviation.  
When the pressure exceeds the maximum entered  
on Setup Screen 2, a Deviation symbol  
will  
show on screen to warn the user that action should  
be taken. The pump continues to run.  
3A2527E  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Setup Screen 5  
Use this screen to set the lower pump size (cc) of  
each pump. The default is blank; select the correct  
lower size, or custom. If custom is selected, enter the  
size of the lower in cc. This screen also activates jog  
mode, allowing you to position the motor/pump shaft  
for connection or disconnection.  
Figure 27 Select a Custom Lower  
NOTE: The motor will limit its pressure output when  
the selected lower is 750cc, to prevent exceeding the  
pressure rating of the lower.  
Setup Screen 5 Key  
Enter the screen.  
For systems with multiple pumps and  
one display, select the desired pump (1  
to 8), using the pull-down menu.  
Select to enable jog mode. Use the  
arrow keys to move the motor/pump  
shaft up or down.  
Select the correct pump lower size from  
the drop-down menu. The default is  
blank. If custom is selected, a field will  
open to input the size of the lower in cc.  
Figure 24 Setup Screen 5  
Figure 25 Select Jog Mode  
Figure 26 Select Pump Lower  
Press to accept the selections.  
Exit the screen.  
22  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Setup Screen 6  
Setup Screen 7  
Use this screen to view the grand totalizer value and  
set or reset the batch totalizer.  
Use this screen to set the desired maintenance  
interval (in cycles) for each pump. The screen also  
displays the current cycle count. An Advisory is  
issued when the counter reaches 0 (zero).  
Figure 28 Setup Screen 6  
Figure 30 Setup Screen 7  
Setup Screen 7 Key  
Enter the screen.  
For systems with multiple pumps and  
one display, select the desired pump (1  
to 8), using the pull-down menu.  
Set the desired maintenance interval (in  
cycles) for each pump.  
Figure 29 Reset the Totalizer  
Setup Screen 6 Key  
Enter the screen to set or change  
preferences.  
Press to accept the selections.  
Grand Totalizer - displays the current  
grand total of pump cycles. Not  
resettable.  
Exit the screen.  
Batch Totalizer - displays the batch total  
in selected volume units.  
Reset Batch Totalizer - resets the batch  
totalizer to zero.  
Press to accept the selections.  
Exit data editing.  
3A2527E  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Screens 8 and 9  
Use these screens to set up the pressure transducers.  
The screens are identical, except Screen 8 is for  
transducer 1 and Screen 9 is for transducer 2.  
Selecting a transducer and a pump activates closed  
loop pressure control.  
Figure 32 Select Pressure Transducer  
Figure 31 Setup Screens 8 and 9 (Screen 8 shown)  
Setup Screens 8 and 9 Key  
Figure 33 Select Pump, to Enable Closed Loop  
Pressure Control  
Select from the dropdown options to  
enable the transducer.  
For systems with multiple pumps and  
one display, select the desired pump (1  
to 8), using the pull-down menu. Enables  
closed loop pressure control and assigns  
the transducer to a pump.  
Enter the calibration scale factor from the  
transducer label.  
Figure 34 Enter Calibration Scale Factor  
Figure 35 Enter Calibration Offset Value  
Enter the calibration offset value from the  
transducer label.  
Displays the current transducer reading.  
Exit data editing.  
Move between Setup Screens, fields on  
a screen, or to increment/decrement the  
digits when editing number fields.  
24  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Screens 10 and 11  
These screens are auto-populated by the software.  
Screen 10 displays the serial numbers of motors 1–4,  
and Screen 11 displays the serial numbers of motors  
5–8.  
Figure 37 Select a Pump Number for Each Serial  
Number  
NOTE: Changing the pump order will shift every other  
pump up one position. For example, if AD00001 is  
changed to be pump 4, AD00002 will become pump  
1, AD00003 will become pump 2, and so on.  
Figure 36 Setup Screens 10 and 11 (Screen 10  
shown)  
3A2527E  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Screen 12  
Use this screen to set your modbus preferences.  
Figure 40 Set Modbus Node ID  
Figure 38 Setup Screen 12  
Setup Screen 12 Key  
Enter the screen.  
For systems with multiple pumps and  
one display, select the desired pump (1  
to 8), using the pull-down menu.  
Figure 41 Set Baud Rate (Bits Per Second)  
Control location. Select local  
or  
control from the dropdown  
remote  
NOTE:The following are fixed modbus settings,  
which cannot be set or changed by the user: 8 data  
bits, 2 stop bits, no parity.  
options. Setting applies to the selected  
pump only.  
Enter or change the Modbus node ID.  
Value is between 1 and 247. Each  
pump requires a unique node ID, which  
identifies that pump if more than one  
pump is connected to the display..  
Select serial port baud rate from the  
dropdown options: 57600 or 115200.  
This is a system-wide setting.  
Press to accept the selections.  
Exit data editing.  
Figure 39 Select Local or Remote Control  
26  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Screen 13  
Use this screen to set the desired units for pressure,  
totals, and flow.  
Figure 43 Select Desired Pressure Units  
Figure 42 Setup Screen 13  
Setup Screen 13 Key  
Select desired pressure units (psi, bar,  
or MPa)  
Figure 44 Select Desired Volume Units  
Select desired volume units (liters or  
gallons)  
Select desired flow rate units (L/min,  
gpm, cc/min, oz/min, or cycles/min)  
Exit data editing.  
Move between Setup Screens, fields on  
a screen, or to increment/decrement the  
digits when editing number fields.  
Figure 45 Select Desired Flow Rate Units  
3A2527E  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Screen 14  
Use this screen to set your date format, date, and  
time.  
Figure 47 Select the Date Format  
Figure 46 Setup Screen 14  
Setup Screen 14 Key  
Enter the screen to set or change  
preferences.  
Select your preferred date format from  
the dropdown menu.  
Figure 48 Set the Date  
MM/DD/YY  
DD/MM/YY  
YY/MM/DD  
Set the correct date.  
Set the correct time.  
Figure 49 Set the Time  
Press to accept the selections.  
Exit data editing.  
28  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Screen 15  
Use this screen to enter a password that will be  
required to access the Setup screens. This screen  
also displays the software version.  
Figure 51 Set the Password  
Figure 52 Disable the Password  
Figure 53 Lock the Profile  
Figure 50 Setup Screen 15  
Setup Screen 15 Key  
Enter the screen to set the password.  
When the top box of the screen is  
checked, the password is active. To  
temporarily disable the password,  
uncheck the box. The password field will  
be grayed-out.  
Enter the desired 4–digit password.  
Check the box to lock out the profile field  
in the Run screens.  
Exit data editing.  
3A2527E  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Error Code Troubleshooting  
Error codes can take three forms:  
NOTE: In the error codes listed below, an “X” means  
the code is associated with the display only.  
• Alarm  
: alerts you to the alarm cause and shuts  
down the pump.  
NOTE: In the e  
rror codes listed below, a “_” in the  
code is a placeholder for the number of the pump  
where the event occurred.  
• Deviation  
: alerts you to the problem, but pump  
may continue to run past the set limits until the  
system’s absolute limits are reached.  
NOTE: The blink code is displayed using the power  
indicator on the motor. The blink code given below  
indicates the sequence. For example, blink code 1–2  
indicates 1 blink, then 2 blinks; the sequence then  
repeats.  
• Advisory: information only. Pump will continue to  
operate.  
NOTE: On Advanced motors, flow (K codes) and  
pressure (P codes) can be designated as alarms or  
deviations. See Setup Screen 4, page 20.  
NOTE: A blink code of 9 is not an error code, but an  
indicator of which pump is active (  
softkey has  
been pushed, see Run Screen 1, page 12).  
Display  
Code  
Applicable  
Motor  
Blink  
Code  
Alarm or  
Deviation  
Description  
None  
Basic  
6
Alarm  
The Mode Select knob is set between Pressure  
and  
Flow  
. Set knob to the desired mode.  
None  
CAC_  
CAD_  
Basic and  
Advanced  
9
None  
Alarm  
Alarm  
A blink code of 9 is not an error code, but an indicator of  
which pump is active.  
Advanced  
None  
2–3  
Display detects a loss of CAN communication. Flashing  
alarm appears on the display, and the blink code occurs.  
Advanced  
Unit detects a loss of CAN communication. This alarm is only  
logged. No flashing alarm appears on the display, but the  
blink code does occur.  
Advanced  
2–4  
3–6  
Alarm  
Alarm  
Alarm  
Display detects a loss of modbus communication when  
control access is set to modbus.  
CAG_  
CCN_  
Basic and  
Advanced  
Circuit board communication failure.  
Advanced  
Advanced  
Advanced  
1–2  
Flow is below minimum limit.  
K1D_  
K2D_  
K3D_  
None  
None  
Deviation Flow is below minimum limit.  
Deviation Flow exceeds maximum target; also indicates pump runaway  
condition exists.  
Basic and  
Advanced  
1
Alarm  
Flow exceeds maximum target; also indicates pump runaway  
condition exists.  
K4D_  
30  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Display  
Code  
Applicable  
Motor  
Blink  
Code  
Alarm or  
Deviation  
Description  
Advanced  
None  
Advisory Maintenance counter is enabled and countdown reached  
zero (0).  
MND_  
Advanced  
Advanced  
Advanced  
Advanced  
Advanced  
1–3  
None  
None  
1–4  
Alarm  
Pressure is below minimum limit.  
P1I_  
P2I_  
P3I_  
P4I_  
P5DX  
Deviation Pressure is below minimum limit.  
Deviation Pressure exceeds maximum target.  
Alarm  
Pressure exceeds maximum target.  
None  
Deviation More than one pump is assigned to a transducer. The  
assignment for that transducer is automatically cleared under  
this condition. User must reassign.  
Advanced  
Advanced  
None  
Deviation For units without closed loop pressure control: Transducer (A  
or B) is enabled but not detected.  
P6CA or  
P6CB  
1–6  
3–5  
5
Alarm  
For units with closed loop pressure control: Transducer is  
enabled but not detected.  
P6D_  
T2D_  
T3D_  
V1I_  
Basic and  
Advanced  
Alarm  
Internal thermistor disconnected.  
Basic and  
Advanced  
Deviation Over temperature.  
Basic and  
Advanced  
2
Alarm  
Alarm  
Alarm  
Alarm  
Alarm  
Brown out; voltage supplied to motor is too low.  
Basic and  
Advanced  
2–6  
3
AC power is lost.  
V1M_  
V4I_  
Basic and  
Advanced  
Voltage supplied to motor is too high.  
Internal software error.  
Basic and  
Advanced  
4–5  
3–4  
WMC_  
WNC_  
Basic and  
Advanced  
Software versions do not match.  
Advanced  
Advanced  
None  
1–5  
Deviation Profile is set to 0 pressure or 0 flow.  
WSC_  
WSD_  
Alarm  
Invalid lower size; occurs if the unit is operated before setting  
up the lower size.  
Basic and  
Advanced  
4
Alarm  
An internal circuit board hardware failure is detected.  
WXD_  
3A2527E  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts  
24P822 Control Module Kit  
Ref Part  
Description  
Qty  
1
Ref Part  
Description  
Qty  
1
— — —  
1
24P821  
DISPLAY KIT, control  
module; includes  
item 1a; see manual  
332013 for approvals  
information about the  
bare ADCM module  
LABEL, warning,  
English  
LABEL, warning,  
French  
LABEL, warning,  
Spanish (shipped  
loose)  
CONNECTOR,  
jumper; includes  
item 5a  
SCREW, cap, socket  
head; M5 x 40 mm  
BRACKET KIT,  
control module;  
includes items 6a-6f  
6a  
BRACKET, control  
module  
BRACKET, mounting  
LOCKWASHER,  
external tooth; M5  
WASHER; M5  
SCREW, cap, socket  
head; M5 x 12 mm  
KNOB; M5 x 0.8  
— — —  
— — —  
6b  
6c  
1
4
— — —  
— — —  
6d  
6e  
2
2
1a▲ 16P265  
1b▲ 16P265  
1c▲ 16P265  
1
1
1
— — —  
— — —  
— — —  
6f  
11  
12  
2
1
1
HOLDER, tie  
STRAP, tie  
5
24N910  
1
▲ Replacement Danger and Warning labels, tags,  
and cards are available at no cost.  
Items marked — — — are not available separately.  
— — —  
24P823  
5a  
6
1
1
Cable (C) is shown for reference but is not included  
in the kit. Order desired length separately. See  
32  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Accessory Kits  
BPR Controller Kit 24V001  
Ref Part  
Description  
Qty  
1
Ref Part  
Description  
ELBOW  
TEE  
Qty  
1
1
— — —  
101  
TRANSDUCER,  
miniature  
CABLE, F/C, I.S., 8 M  
GAUGE, pressure, air  
BUSHING  
ELBOW  
106 110207  
107 C19466  
108 198171  
— — —  
102  
1
1
1
1
ELBOW  
1
103 110436  
104 100030  
105 198178  
— — —  
Parts not sold separately.  
Start/Stop Switch Kit 16U729  
The kit includes the switch and enclosure, a mounting bracket, and cables. Parts are not sold separately.  
Pressure Transducer Kit 24R050 (for 4–Ball pumps)  
and Kit 24Y245 (for 2–Ball pumps)  
Each kit includes the fluid pressure sensor with cable, an adaptor, and an o-ring. Parts are not sold separately.  
3A2527E  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Appendix A - Modbus Variable Map  
To communicate through fiber optics with the E-Flo  
DC Control Module, reference the appropriate  
hardware as shown in manual 332356. That  
manual indicates various options for connecting  
fiber optic cables from the control module to the  
non-hazardous area. The following table lists  
Modbus registers available to a PC or PLC located in  
the non-hazardous area.  
Table 4 shows the registers needed for basic  
operation, monitoring, and alarm control features.  
Tables 5 and 6 provide bit definitions as needed for  
certain registers. Table 7 shows the units and how to  
convert the register value to a unit value.  
Reference the Modbus communication settings  
selected in Setup Screen 12, page 26.  
Table 4 Modbus Registers  
Modbus  
Register  
Variable  
Register  
Access  
Size  
Notes/Units  
404100  
404101  
404102  
404103  
404104  
404105  
404106  
404107  
404108  
404109  
404110  
404111  
404112  
404113  
404114  
404115  
Pump Status Bits  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
16 Bit  
See Table 5 for bit definitions.  
Speed units, see Table 7.  
Flow units, see Table 7..  
Actual Pump Speed  
Actual Pump Flow Rate  
Actual Pump Pressure  
Transducer 1 Pressure  
Transducer 2 Pressure  
Batch Total High Word  
Batch Total Low Word  
Grand Total High Word  
Grand Total Low Word  
Maintenance Total High Word  
Maintenance Total Low Word  
Pump Alarms High Word  
Pump Alarms Low Word  
Display Alarms High Word  
Display Alarms Low Word  
Percent pressure, see Table 7.  
Pressure units, see Table 7.  
Pressure units, see Table 7.  
Volume units, see Table 7.  
Volume units, see Table 7.  
Pump cycles, see Table 7.  
Pump cycles, see Table 7.  
Pump cycles, see Table 7.  
Pump cycles, see Table 7.  
See Table 5 for bit definitions.  
See Table 5 for bit definitions.  
See Table 5 for bit definitions.  
See Table 5 for bit definitions.  
404200  
404201  
404202  
404203  
404204  
Local/Remote Control  
Read / Write 16 Bit  
Read / Write 16 Bit  
Read / Write 16 Bit  
Read / Write 16 Bit  
Read / Write 16 Bit  
0 = local, 1 = remote/PLC  
0 = stopped, 1, 2, 3, 4  
Active Profile Number  
Pump Control Bitfield  
See Table 5 for bit definitions.  
Pump cycles, see Table 7.  
Pump cycles, see Table 7.  
Maintenance Interval High Word  
Maintenance Interval Low Word  
403102  
Display seconds  
Read Only  
16 Bit  
Use as heartbeat.  
34  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NOTE: See Error Code Troubleshooting, page 30, for a description of each alarm.  
Table 5 Alarm Bits  
404112 - Pump Alarms Word 1  
Bit  
Event Type  
Deviation  
Alarm  
Event Code  
T3D_  
Event Name  
0
Over Temperature  
2
P6D_  
Pressure Transducer Missing  
Internal Software Error  
Maintenance Count  
AC Power Loss  
3
Deviation  
Advisory  
Alarm  
ERR_  
MND_  
V1M_  
4
5
6
Alarm  
T2D_  
Low Temperature  
7
Alarm  
Version Mismatch  
WNC_  
CCN_  
WMC_  
P5D_  
8
Alarm  
IPC Communication  
Internal software error  
Multiple Pumps Assigned to Transducer  
Zero setting on active profile  
Reserved  
9
Alarm  
10  
Deviation  
Deviation  
11  
WSC_  
others  
404113 - Pump Alarms Word 2  
Bit  
0
Event Type  
Alarm  
Event Code  
K1D_  
K2D_  
K4D_  
K3D_  
P1I_  
Event Name  
Minimum Speed  
Minimum Speed  
Maximum Speed  
Maximum Speed  
Minimum Pressure  
Minimum Pressure  
Maximum Pressure  
Maximum Pressure  
Under Voltage  
1
Deviation  
Alarm  
2
3
Deviation  
Alarm  
4
5
Deviation  
Alarm  
P2I_  
6
P4I_  
7
Deviation  
Alarm  
P3I_  
8
V1I_  
9
Alarm  
V4I_  
Over Voltage  
10  
11  
13  
14  
others  
Alarm  
V4I_  
High Pressure 120V  
CAN Communication Pump  
Board Hardware  
Invalid Lower Size  
Reserved  
Alarm  
CAD_  
WXD_  
WSD_  
Alarm  
Alarm  
3A2527E  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
404114 - Display Alarms Word 1  
Bit  
Event Type  
Deviation  
Event Code  
P6C_  
Event Name  
1
Pressure Transducer Missing  
Reserved  
others  
404115 - Display Alarms Word 2  
Bit  
Event Type  
Alarm  
Event Code  
CAG_  
Event Name  
12  
Modbus Communication  
CAN Communication Display  
Reserved  
15  
Alarm  
CAC_  
others  
Table 6 Pump Status and Control Bits  
404100 - Pump Status Bits  
Bit  
Meaning  
0
Reads 1 if the pump is trying to move  
1
Reads 1 if the pump is actually moving  
Reads 1 if there are any active alarms  
Reads 1 if there are any active deviations  
Reads 1 if there are any active advisories  
Reserved for future use  
2
3
4
others  
404202 - Pump Control Bits  
Bit  
Meaning  
0
Reads 0 for an active alarm or deviation. Reset to 1 to clear.  
Set to 1 to reset the batch total  
1
2
Set to 1 to reset the maintenance counter  
Reserved for future use - only write 0  
others  
36  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 Units  
Unit Type  
Selectable Units Units Register  
Converting registers to Register value for 1  
unit values  
unit  
Pressure  
Pressure  
Percent  
psi  
n/a  
Pressure = Register  
Pressure = Register  
1 = 1% Pressure  
1 = 1 psi  
403208 = 0  
403208 = 1  
403208 = 2  
Bar  
Pressure = Register/10 10 = 1.0 Bar  
MPa  
Pressure =  
Register/100  
100 = 1.00 Mpa  
Speed  
Flow  
Cycles/min  
Liters/min  
Gallons/min  
cc/min  
n/a  
Speed = Register/10  
Flow = Register/10  
Flow = Register/10  
Flow = Register  
10 = 1.0 cycle/min  
10 = 1.0 L/min  
10 = 1.0 Gal/min  
1 = 1 cc/min  
403210 = 0  
403210 = 1  
403210 = 2  
403210 = 3  
403210 = 4  
oz/min  
Flow = Register  
1 = 1 oz/min  
Cycles/min  
Flow = Register/10  
10 = 1.0 cycle/min  
Volume  
Cycles✝✝  
Liters  
403209 = 0  
403209 = 1  
n/a  
Volume = 1000*High + 0 (High) / 10 (Low) =  
Low/10 1.0 L  
Gallons  
Volume = 1000*High + 0 (High) / 10 (Low) =  
Low/10  
1.0 Gal  
Pump Cycles  
Cycles = 10000*High  
+ Low  
0 (High) / 1 (Low) = 1  
cycle  
Example of converting volume register reading to units: If the reading for register 404106 (volume high  
word) is 12, and the reading for register 404107 (volume low word) is 34, the volume is 12003.4 liters. 12 *  
1000 + 34/10 = 12003.4.  
✝✝ Example of converting cycles register reading to units: If the reading for register 404108 (cycles high  
word) is 75, and the reading for register 404109 (cycles low word) is 8000, the volume is 758,000 cycles.  
75 * 10000 + 8000 = 758000.  
3A2527E  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B. Pump Control from a PLC  
This guide shows how to use the information in  
Appendix A to control a pump remotely from a PLC.  
The steps progress from basic pump control to more  
advanced monitoring and alarm control features.  
5. Monitor alarms and deviations: Read register  
404112 to 404115. Each bit in these registers  
corresponds to an alarm or deviation. See  
Appendix A, Table 5. I  
• Example 1: Pressure falls below the minimum  
setting entered on Setup Screen 2. It will show  
on bit 4 of register 404113 if minimum pressure  
is set to Alarm, and on bit 5 of register 404113  
if minimum pressure is set to Deviation.  
It is important that you first follow all directions in the  
Setup Screens to configure your system properly.  
Test that the pump operates correctly when controlled  
from the Display. Make sure the display, fiber optics,  
communication gateway, and PLC are connected  
properly. Refer to Communication KIt manual. Use  
Setup Screen 12 to enable remote control and set  
your modbus preferences.  
• Example 2: The system is set up for a  
pressure transducer on Setup Screen 8, but no  
transducer is detected. It will show on bit 1 of  
register 404114.  
1. Enable PLC control: Set register 404200 to 1.  
6. Monitor pump cycle rate, flow rate, and pressure:  
Read registers 404101 to 404105. Note that  
pressure is available only if a pressure transducer  
is connected to the display. Register 404104  
shows the pressure on transducer 1. Register  
404105 shows the pressure on transducer 2. See  
Appendix A, Table 7 for units for these registers.  
2. Run a pump: Set register 404201. Enter 0 for  
stopped,1 to 4 for the desired profile.  
3. View pump profile: Read register 404201. This  
register updates automatically to reflect the  
actual pump status. If the profile is changed from  
the display, this register changes as well. If the  
pump stops due to an alarm, this register will  
read 0.  
• Example 1: If register 404101 reads 75, the  
pump speed is 7.5 cycles/minute.  
4. View pump status: Read register 404100 to see  
the status of the pump. See Appendix A, Table  
6, for a description of each bit.  
• Example 2: If register 404103 reads 67, the  
pump is operating at 67 percent pressure.  
7. Reset active alarms and deviations: Clear the  
condition that caused the alarm. Set register  
404202, bit 0, to 1 to clear the alarm. The pump  
will be in profile 0 due to the alarm. Set 404201  
to the desired profile to run the pump again.  
• Example 1: Register 404100, bit 1, reads 1 if  
the pump is currently moving.  
• Example 2: Register 404100, bit 2 reads 1 if  
the pump has an active alarm.  
38  
3A2527E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Notes  
3A2527E  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Graco Standard Warranty  
Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its  
name to be free from defects in material and workmanship on the date of sale to the original purchaser for  
use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a  
period of twelve months from the date of sale, repair or replace any part of the equipment determined  
by Graco to be defective. This warranty applies only when the equipment is installed, operated and  
maintained in accordance with Graco’s written recommendations.  
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction,  
damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper  
maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall  
Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment  
with structures, accessories, equipment or materials not supplied by Graco, or the improper design,  
manufacture, installation, operation or maintenance of structures, accessories, equipment or materials  
not supplied by Graco.  
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an  
authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco  
will repair or replace free of charge any defective parts. The equipment will be returned to the original  
purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material  
or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of  
parts, labor, and transportation.  
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR  
IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY  
OF FITNESS FOR A PARTICULAR PURPOSE.  
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above.  
The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages  
for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall  
be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.  
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF  
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH  
ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY  
GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.),  
are subject to the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable  
assistance in making any claim for breach of these warranties.  
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from  
Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other  
goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or  
otherwise.  
FOR GRACO CANADA CUSTOMERS  
The Parties acknowledge that they have required that the present document, as well as all documents,  
notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or  
indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédaction du  
présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés,  
donnés ou intentés, à la suite de ou en rapport, directement ou indirectement, avec les procédures  
concernées.  
Graco Information  
To place an order, contact your Graco Distributor or call to identify the nearest distributor.  
Phone: 612-623-6921 or Toll Free: 1-800-328-0211 Fax: 612-378-3505  
All written and visual data contained in this document reflects the latest product information available at the time of publication. Graco  
reserves the right to make changes at any time without notice  
Original Instructions. This manual contains English. MM 3A2527  
Graco Headquarters: Minneapolis  
International Offices: Belgium, China, Japan, Korea  
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA  
Copyright 2013, Graco, Inc. All Graco manufacturing locations are registered to ISO 9001.  
Revision E, April 2015  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

Hamilton Beach Cooktop Meal Maker User Manual
HannsG Computer Monitor HW216 User Manual
Harbor Freight Tools Scale 95364 User Manual
Harman Kardon Home Theater System 950 0321 001 User Manual
HP Hewlett Packard Hunting Equipment HP54501A User Manual
HP Hewlett Packard Life Jacket tc3100 User Manual
Huffy Fitness Equipment 214946C User Manual
Hypertec Carrying Case N14628KHY User Manual
IDEAL INDUSTRIES Heat Gun Heat Gun User Manual
iHome Headphones IB24 User Manual