TECHNICAL MANUAL
GPC 14 SEER R-410A
Package Air Conditioners
with R-410A
•
Refer to Service Manual RS6300011 (Horizontal)
for installation, operation, and troubleshooting information.
All safety information must be followed as provided in the Service Manual.
•
•
•
•
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency**
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and
Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult
a tax professional if they have questions about the applicability of these credits.
RT6322007r6
September2010
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not
assume any responsibility for property damage or personal injury due to improper service procedures or
services performed by an unqualified person.
Copyright © 2009 - 2010 Goodman Manufacturing Company, L.P.
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please
use these numbers when requesting service or parts information.
5mm
GPC1424H41AA
GPC1430H41AA
GPC1436H41AA
GPC1442H41AA
GPC1448H41AA
GPC1460H41AA
GPC1424H41AB
GPC1430H41AB
GPC1436H41AB
GPC1442H41AB
GPC1448H41AB
AB model specific
5 mm information
begins on page 28.
Models qualify for the 2009 and 2010 Federal Tax Credits
for Energy Efficiency**
**Note that these tax credits are subject to specific requirements set forth in the American
Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman
recommends that consumers consult a tax professional if they have questions about the
applicability of these credits.
The United States Environmental Protection Agency (“EPA”) has issued various regulations re-
garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
WARNING
WARNING
Do not connect or use any device
To prevent the risk of property
WARNING
that is not design certified by
damage, personal injury, or death,
Goodman for use with this unit.
do not store combustible materials or use gasoline or
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
other flammable liquids or vapors in the vicinity of this
appliance.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DESIGN
GPC Package Cooling Units are designed for outdoor instal-
lations only in either residential or light commercial applica-
tions.
-
Due to their design Scroll Compressors are inherently
more tolerant of liquid refrigerant. NOTE: Even though the
compressor section of a Scroll compressor is more toler-
ant of liquid refrigerant, continued floodback or flooded
start conditions may wash oil from the bearing surfaces
causing premature bearing failure.
The connecting ductwork (Supply and Return) can be con-
nected for either horizontal or vertical airflow. In the vertical
application a matching Roof Curb is recommended.
-
-
Scroll Compressors use white oil which is compatible
with 3GS oil which may be used if additional oil is re-
quired.
A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible loca-
tion within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Sec-
tion. Under no circumstances should the unit be operated
without return air filters.
Operating pressures and amp draws may differ from stan-
dard reciprocating compressors. This information may be
found in the "Cooling Performance Data" section.
A 3/4” PVC pipe is provided for removal of condensate water
from the indoor coil In order to provide proper condensate
flow, a drain trap is supplied and shipped loose inside the
unit for field installation. (Do not reduce the drain line size.)
LocationandClearances
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
Refrigerant flow control is achieved by use of restrictor ori-
fices. GPC units use the FasTest Access Fitting System
with a saddle that is either soldered to the suction and liquid
lines or is fastened with a locking nut to the access fitting
box (core) and then screwed into the saddle. Do not re-
move the core from the saddle until the refrigerant
charge has been removed. Failure to do so could re-
sult in property damage or personal injury.
10"
36"
WALL
The single phase units use permanent split capacitor (PSC)
design compressors. Starting components are therefore not
required for these units. A low microfarad run capacitor as-
sists the compressor to start and remains in the circuit dur-
ing operation.
UNIT
All GPC14 units have X-13 indoor blower motors that are en-
ergized by a 24V signal from the thermostat and are con-
stant torque motors with very low power consumption. The X-
13 features an integral control module.
36"
Air for condensing (cooling cycle) is drawn through the out-
door coil by a propeller fan, and is discharged vertically out
the top of the unit. The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.
36"
Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.
Outside Slab Installation - Horizontal (H)
Minimumclearancesarerequiredtoavoidairrecirculationand
keep the unit operating at peak efficiency.
GPC1424-30H41* use Copeland Reciprocating Compressors.
GPC1436-60H41* use Copeland Scroll Compressors. There
are a number of design characteristics which are different
from the traditional reciprocating compressor.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DESIGN
In installations where the unit is installed above ground level
and not serviceable from the ground (Example: Roof Top in-
stallations), the installer must provide service platform for ser-
vice person with rails or guards in accordance with local codes
or ordinances or in their absence with the latest edition of the
Uniform Mechanical Code Section 305.
36"
NOTE: Unit can also use roof curb.
24"
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION
DURING ALL RIGGING AND MOVING OPERATIONS.
TO FACILITATE LIFTING AND MOVING IF A CRANE
IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE
SLING.
36"
Refer to Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with
the National Roofing Contractors Association Manual.
Rooftop Installation - Horizontal (H)
5
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DIMENSIONS
GPC14[24-60]H41A*
A
14.000
4.512
4.500
14.000
SUPPLY
6.500
14.000
RETURN
BACK VIEW
(DUCT OPENINGS)
66.542
B
34.075
Chassis
Model
A
B
GPC1424
GPC1430
GPC1436
GPC1442
GPC1448
GPC1460
33
33
33
33
33
33
30½
30½
35½
35½
38½
38½
Small
Medium
Large
Dimensions in inches
6
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DESIGN
GPC14[24-60]H41A*
HKR ELECTRICAL DATA
Circuit #1
Circuit #2
Maximum
Overcurrent
Protection (amps)
at 208 / 240V
Maximum
Actual
kW & BTU
at 240V
Minimum Circuit
Ampacity
at 208 / 240V
Minimum Circuit
Ampacity
at 208 / 240V
Model and Heat Kit Usage
Overcurrent
Protection (amps)
at 208 / 240V
GPH1424H41A*
HKR05*,C*
24 / 27
33 / 28
45 / 51
30 / 30
40 / 40
60 / 60
----
----
----
----
----
----
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
HKR08*,C*
HKR10*,C*
GPH1430H41A*
HKR05*,C*
24 / 27
34 / 39
45 / 52
45 / 52
30 / 30
40 / 40
60 / 60
60 / 60
----
----
----
----
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
14.25 / 48,600
HKR08*,C*
HKR10*,C*
HKR15*,C*
GPH1436H41A*
HKR05*,C*
HKR08*,C*
HKR10*,C*
HKR15*,C*
GPH1442H41A*
HKR05*,C*
HKR08*,C*
HKR10*,C*
HKR15*,C*
HKR20*,C*
GPH1448H41A*
HKR05*,C*
HKR08*,C*
HKR10*,C*
HKR15*,C*
HKR20*,C*
----
----
22 / 25
30 / 30
24 / 27
34 / 39
45 / 52
45 / 52
30 / 30
40 / 40
60 / 60
60 / 60
----
----
----
----
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
14.25 / 48,600
----
22 / 25
----
30 / 30
25 / 27
34 / 39
46 / 52
46 / 52
46 / 52
30 / 30
40 / 40
60 / 60
60 / 60
60 / 60
----
----
----
----
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
14.25 / 48,600
19.50 / 66,500
----
----
22 / 25
43 / 49
30 / 30
60 / 60
25 / 28
34 / 40
30 / 30
40 / 40
----
----
----
----
4.75 / 16,200
7.00 / 23,800
46 / 53
46 / 52
46 / 52
60 / 60
60 / 60
60 / 60
----
----
9.50 / 32,400
14.25 / 48,600
19.50 / 66,500
22 / 25
43 / 49
30 / 30
60 / 60
GPH1460H41A*
HKR05*,C*
HKR08*,C*
HKR10*,C*
HKR15*,C*
HKR20*,C*
26 / 30
36 / 40
48 / 54
30 / 30
40 / 40
60 / 60
----
----
----
----
----
----
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
48 / 54
48 / 54
60 / 60
60 / 60
22 / 25
43 / 49
30 / 30
60 / 60
14.25 / 48,600
19.50 / 66,500
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
All wires and overcurrent protection devices are sized for use with electric heaters only and without
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
WARNING
7
Download from Www.Somanuals.com. All Manuals Search And Download.
GPC14[24-60]H41A*
ACCESSORIES
Part Number
OT18-60A
Description
Outdoor Thermostat Kit w/Lockout Stat
Emergency Heat Relay Kit
Electric Heat Kit
OT/EHR18-60
HKR
PCCP101-103
PCP101-103
PCP101-103R8
GPCED101-103
GPHED101-103
GPCEH101-103
GPHEH101-103
PCMD101-103
PCMDM101-103
GPHMD101-103
SQRPCH101
SQRPCH102-103
SQRPC101
Roof Curb
Downflow Plenum Kit
Downflow Plenum Kit w/ R-8 Insulation
Downflow Economizer for GPC-(H) A/C - To Be Used With PCP101-103
Downflow Economizer for GPH-(H) Heat Pump - To Be Used With PCP101-103
Horizontal Economizer for GPC-(H) A/C
Horizontal Economizer for GPH-(H) Heat Pump
Manual Damper - To Be Used With PCP101-103
Motorized Damper - To Be Used With PCP101-103
Manual Damper for Horizontal Applications
Square to Round Adapters 16"&14"
Square to Round Adapters 18"&14"
Square to Round Adapter - For Use With PCCP101-103 Curb 16" Rounds
Square to Round Adapter For Use With PCCP101-103 Curb 18" Rounds
External Horizontal Filter Rack
SQRPC102-103
PCFR101-103
PCEF101-103
CDK36
Elbow & Flashing w/ R-8 Liner
Flush Mount Concentric Duct Kit
CDK36515
Flush Mount Concentric Duct Kit w/ Filter
CDK36530
Step Down Concentric Duct Kit
CDK36535
Step Down Concentric Duct Kit w/ Filter
CDK4872
Flush Mount Concentric Duct Kit
CDK4872515
CDK4872530
CDK4872535
Flush Mount Concentric Duct Kit w/ Filter
Step Down Concentric Duct Kit
Step Down Concentric Duct Kit w/ Filter
8
Download from Www.Somanuals.com. All Manuals Search And Download.
GPC14[24-60]H41A*
BLOWER PERFORMANCE DATA
Dry Coil Data
E.S.P (In. of H2O)
Model
Speed
Volts
CFM
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
934
759
755
638
581
489
-
-
T1
230
230
230
WATTS
CFM
95
77
76
73
83
90
652
133
-
-
601
142
-
-
-
990
837
801
744
696
119
876
169
797
144
937
185
1124
257
933
179
1099
213
1181
247
1055
211
1147
245
1336
303
1275
299
1510
455
1590
550
1510
T2,T3
T4, T5
WATTS 107
CFM 1061
WATTS 126
CFM 1022
WATTS 116
CFM 1103
WATTS 142
CFM 1285
WATTS 205
CFM 1234
WATTS 144
CFM 1287
WATTS 162
CFM 1381
WATTS 195
CFM 1272
WATTS 160
CFM 1357
WATTS 188
CFM 1537
WATTS 244
CFM 1418
WATTS 242
CFM 1175
WATTS 395
CFM 1845
WATTS 490
CFM 1775
WATTS 395
CFM 2025
WATTS 575
94
105
110
-
989
947
925
-
134
146
158
-
-
-
929
894
829
748
156
-
695
168
-
643
173
-
T1
230
230
230
230
230
230
230
230
230
230
230
230
114
126
134
1063
154
1012
165
962
T2,T3
T4, T5
T1
173
-
-
-
1240
218
1202
231
1163
244
1076
268
922
183
1053
221
1144
258
998
220
1099
255
1293
317
1228
308
1450
465
1580
560
1450
1046
280
-
1003
288
-
1111
140
1071
152
1024
164
-
-
1232
175
1186
187
1133
201
-
-
T2,T3
T4, T5
T1
-
-
1325
203
1277
217
1233
233
-
-
-
-
1197
168
1145
183
1106
191
947
230
1049
267
1253
329
1178
320
1430
470
1530
570
1430
906
243
1008
284
1208
341
1141
338
1400
475
1500
575
1400
1297
202
1244
213
1194
228
T2,T3
T4, T5
T1
1478
258
1431
274
1386
288
1383
258
1349
273
1312
282
1635
420
1645
435
1515
445
T2,T3
T4, T5
1790
505
1715
520
1685
535
1635
1645
1515
T1, T2, T3 230
420
1900
595
435
1840
620
445
1780
630
455
1725
645
465
1650
655
470
1620
660
475
1580
670
T4, T5
230
NOTES:
1. Data shown is dry coil. Wet coil pressure drop is approx.
2. 0.1" H2O, for 2 row indoor coil; 0.2” H2O, for 3 row indoor coil; and 0.3” H2O, for 4 row indoor coil.
3. Data shown does not include filter pressure drop, approx. 0.08” H2O.
4. Reduce airflow by 2% for 208V operation.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
BLOWER PERFORMANCE DATA
S E R E I R U
M P T E E R A T
10
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGE COOLING SPECIFICATIONS
GPC14[24-30]H41AA
GPC1424H41*
GPC1430H41*
COOLING
COOLING CAPACITY, BTUH
SEER / EER
24,600
14.5 / 12.1
208-230/1/60
10.5
12.5
20
28,400
14.0 / 12.1
208-230/1/60
13.16
15.6
25
CAPACITY
UNIT
VOLTAGE (NAMEPLATE)
AMPS (TOTAL)
ELECTRICAL
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
MAXIMUM OVERCURRENT PROTECTION (1)
COMPRESSOR
TYPE
RECIP
7.9
RECIP
9.8
RATED LOAD AMPS
LOCKED ROTOR AMPS
HORSEPOWER
41
55
CONDENSER
FAN MOTOR
1/6
1/4
RPM
815
830
FULL LOAD AMPS
1.1
1.5
LOCKED ROTOR AMPS
BLADE DIAMETER (INCHES) / # OF BLADES
FACE AREA - SQ. FT.
1.7
3.0
22 / 3
13.4
1
22 / 3
13.4
1
CONDENSER FAN
CONDENSER
COIL
NUMBER OF ROWS
FINS PER INCH
24
24
EVAPORATOR
BLOWER
HORSEPOWER - NO. OF SPEEDS
FULL LOAD AMPS
1/2 - 5
1.5
1/2 - 5
1.86
NA
MOTOR
LOCKED ROTOR AMPS
MOTOR SPEED TAP - COOLING
RPM
NA
T2
T2
1050
10 X 8
850
1050
10 X 8
1,050
NA
DIAMETER X WIDTH (INCHES)
HI EFFICIENCY COOLING CFM
5 TON NOMINAL COOLING CFM
FAN ONLY COOLING CFM
MAX EXTERNAL STATIC PRESS ("w.c.)
FACE AREA - SQ. FT.
EVAPORATOR
BLOWER
NA
800
950
0.5
0.5
EVAPORATOR
COIL
5.25
3
5.25
3
NUMBER OF ROWS
FINS PER INCH
16
16
FILTER SIZE - SQ. FT. *
DRAIN SIZE (INCHES)
20 x 20 x 1
3/4"
20 x 25 x 1
3/4"
GENERAL
INFORMATION
EXPANSION DEVICE
ORIFICE (0.057) ORIFICE (0.060)
REFRIGERANT CHARGE R-410A (Oz.)
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)
SHIPPING WEIGHT LBS.
OPERATING WEIGHT LBS.
83
3/4, 1, 1-1/4
1/2
78
3/4, 1, 1-1/4
1/2
310
310
300
300
(1)
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGE COOLING SPECIFICATIONS GPC14[36-42]H41AA
GPC1436H41*
GPC1442H41*
COOLING CAPACITY, BTUH
SEER / EER
35,600
14.0 / 12.0
208-230/1/60
20.06
24.2
40
40,000
14.2/ 12.0
208-230/1/60
22.2
COOLING
CAPACITY
UNIT
VOLTAGE (NAMEPLATE)
AMPS (TOTAL)
ELECTRICAL
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
MAXIMUM OVERCURRENT PROTECTION (1)
TYPE
26.6
40
COMPRESSOR
SCROLL
16.7
79
SCROLL
17.9
RATED LOAD AMPS
LOCKED ROTOR AMPS
HORSEPOWER
112
CONDENSER
FAN MOTOR
1/4
1/4
RPM
830
1075
1.4
FULL LOAD AMPS
1.5
LOCKED ROTOR AMPS
BLADE DIAMETER (INCHES) / # OF BLADES
FACE AREA - SQ. FT.
3.0
2.9
22 / 3
13.4
1
22 / 4
17.0
CONDENSER FAN
CONDENSER
COIL
NUMBER OF ROWS
1
FINS PER INCH
24
24
HORSEPOWER - NO. OF SPEEDS
FULL LOAD AMPS
1/2 - 5
1.86
NA
1/2 - 5
2.9
EVAPORATOR
BLOWER
MOTOR
LOCKED ROTOR AMPS
MOTOR SPEED TAP - COOLING
RPM
NA
T2
T2
1050
10 X 8
1,200
NA
1050
10 x 8
1,300
NA
EVAPORATOR
BLOWER
DIAMETER X WIDTH (INCHES)
HI EFFICIENCY COOLING CFM
5 TON NOMINAL COOLING CFM
FAN ONLY COOLING CFM
MAX EXTERNAL STATIC PRESS ("w.c.)
FACE AREA - SQ. FT.
1,100
0.5
1,200
0.5
EVAPORATOR
COIL
5.2
6.2
NUMBER OF ROWS
3
4
FINS PER INCH
14
14
GENERAL
FILTER SIZE - SQ. FT. *
DRAIN SIZE (INCHES)
25 x 25 x 1
3/4"
(2) 20 x 20 x 1
3/4"
INFORMATION
EXPANSION DEVICE
ORIFICE (0.065) ORIFICE (0.072)
REFRIGERANT CHARGE R-410A (Oz.)
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)
SHIPPING WEIGHT LBS.
OPERATING WEIGHT LBS.
80
3/4, 1, 1-1/4
1/2
118
3/4, 1, 1-1/4
1/2
370
370
360
360
(1)
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGE COOLING SPECIFICATIONS
GPC14[48-60]H41AA
GPC1448H41*
GPC1460H41*
COOLING CAPACITY, BTUH
SEER / EER
46,500
14.5 / 12.0
208-230/1/60
24.2
57,500
14.5 / 12.0
208-230/1/60
30.7
COOLING
CAPACITY
UNIT
VOLTAGE (NAMEPLATE)
AMPS (TOTAL)
ELECTRICAL
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
29.1
37.3
MAXIMUM OVERCURRENT PROTECTION (1)
TYPE
45
60
SCROLL
19.9
SCROLL
26.4
COMPRESSOR
RATED LOAD AMPS
LOCKED ROTOR AMPS
HORSEPOWER
109
134
CONDENSER
FAN MOTOR
1/4
1/4
RPM
1075
1.4
1075
1.4
FULL LOAD AMPS
LOCKED ROTOR AMPS
BLADE DIAMETER (INCHES) / # OF BLADES
FACE AREA - SQ. FT.
2.9
2.9
22 / 4
19.1
22 / 4
19.1
CONDENSER FAN
CONDENSER
COIL
NUMBER OF ROWS
1
2
FINS PER INCH
21
16
EVAPORATOR
BLOWER
HORSEPOWER - NO. OF SPEEDS
FULL LOAD AMPS
3/4 - 5
2.9
3/4 - 5
2.9
LOCKED ROTOR AMPS
MOTOR SPEED TAP - COOLING
RPM
NA
NA
MOTOR
T2
T2
1050
10 x 8
1,600
NA
1050
11 x 8
1,600
1,800
1,600
0.5
DIAMETER X WIDTH (INCHES)
HI EFFICIENCY COOLING CFM
5 TON NOMINAL COOLING CFM
FAN ONLY COOLING CFM
MAX EXTERNAL STATIC PRESS ("w.c.)
FACE AREA - SQ. FT.
EVAPORATOR
BLOWER
1,400
0.5
6.2
7.0
EVAPORATOR
COIL
NUMBER OF ROWS
4
4
FINS PER INCH
14
14
GENERAL
FILTER SIZE - SQ. FT. *
DRAIN SIZE (INCHES)
(2) 20 x 20 x 1
3/4"
(2) 20 x 25 x 1
3/4"
INFORMATION
EXPANSION DEVICE
ORIFICE (0.076) ORIFICE (0.088)
REFRIGERANT CHARGE R-410A (Oz.)
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)
SHIPPING WEIGHT LBS.
OPERATING WEIGHT LBS.
123
3/4, 1, 1-1/4
1/2
188
3/4, 1, 1-1/4
1/2
400
400
390
390
(1)
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1424H41AA
14
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1424H41AA
15
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1430H41AA
16
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1430H41AA
17
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1436H41AA
18
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1436H41AA
19
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1442H41AA
20
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1442H41AA
21
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1448H41AA
22
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1448H41AA
23
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1460H41AA
24
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPC1460H41AA
25
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING DIAGRAMS
GPC14[24-60]H41AA
PU
NOTE #3
PU
BK
2
BK
PU
1
3
240
BL
C
208
BK
2
0
8
-
2
4
0
/
BL
L2
C
T2
T1
RD
24V
RD
BL
SEE NOTE 5
L1
BK
BK
RD
1
/
YL
GND
GR
BK
60
RD
RD
YL
PU
LVJB
YL
H
T
H
E
R
M
O
S
T
WH
WH
RD
C
BR
F
YL
RD
GR
Y
R
G
GR
BL
PLF
3
6
5
4
9
8
7
W1
WH
YL
RCCF
BL
GR
2
1
BR
BR
BL
W2
C
A
T
++
PU
BR
RD
BK
BK
SA
(IF USED) SEE NOTE 4
CONTROL
BOX
RD
C
BK
YL
PU BR
CM
YL
GR
WH
S
R
C
L
2
G
3
N
4
1
5
HPS
COMP
WH
EM
SEE NOTE 2
L1
L2
COMPONENT LEGEND
CONTACTOR
FACTORY WIRING
SUPPLY VOLTAGE
208-240/1/60
LINE VOLTAGE
LOW VOLTAGE
OPTINAL HIGH
VOLTAGE
C
CM
CONDENSER MOTOR
COMP
COMPRESSOR
EM
EVAPORATOR MOTOR
EQUIPMENT GROUND
LOW VOLTAGE JUNCTION BOX
FEMALE PLUG / CONNECTOR
RUN CAPACITOR FOR
COMPRESSOR AND FAN
START ASSIST
T2
C
GND
LVJB
PLF
R
COMP
C
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
T1
C
C
RCCF
S
H
RCCF
F
S.A.
CM
SA
TR
NOTE #4
TRANSFORMER
WIRE CODE
BK BLACK
BL BLUE
HPS
HIGH PRESSURE SWITCH
IF USED
NOTE #2
EM
BR BROWN
GR GREEN
OR ORANGE
PU PURPLE
RD RED
L
N
3
G
1
2
WH WHITE
YL YELLOW
208-240
2
NOTE #4
3
1
TR
24V
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW
LEADS FROM EM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE
ENERGIZED, THE HIGHER SPEED SETTING IS USED.
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED
5. USE COPPER CONDUCTORS ONLY.
C
1
2
EM
SEE NOTE #2
3
++ USE N.E.C. CLASS 2 WIRE
4
5
6
PLF
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
C
HPS
R
W2
W1
Y
G
C
THERMOSTAT
208-240/1/60 0140G00871 REV. B
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
GPC 14 SEER R-410A
5mm Package Air Conditioners
GPC1424H41AB GPC1442H41AB
GPC1430H41AB GPC1448H41AB
GPC1436H41AB
PRODUCT DESIGN
GPC Package Cooling Units are designed for outdoor instal-
lations only in either residential or light commercial applica-
tions.
Air for condensing (cooling cycle) is drawn through the out-
door coil by a propeller fan, and is discharged vertically out
the top of the unit. The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.
The connecting ductwork (Supply and Return) can be con-
nected for either horizontal or vertical airflow. In the vertical
application a matching Roof Curb is recommended.
Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.
A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible loca-
tion within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Sec-
tion. Under no circumstances should the unit be operated
without return air filters.
GPC1424-60H41AB models use Copeland Scroll Compres-
sors. There are a number of design characteristics which
are different from the traditional reciprocating compressor.
-
Due to their design Scroll Compressors are inherently
more tolerant of liquid refrigerant. NOTE: Even though
the compressor section of a Scroll compressor is more
tolerant of liquid refrigerant, continued floodback or
flooded start conditions may wash oil from the bearing
surfaces causing premature bearing failure.
A 3/4” PVC pipe is provided for removal of condensate water
from the indoor coil In order to provide proper condensate
flow, a drain trap is supplied and shipped loose inside the
unit for field installation. (Do not reduce the drain line size.)
Refrigerant flow control is achieved by use of restrictor ori-
fices. GPC units use the FasTest Access Fitting System
with a saddle that is either soldered to the suction and liquid
lines or is fastened with a locking nut to the access fitting
box (core) and then screwed into the saddle. Do not re-
move the core from the saddle until the refrigerant
charge has been removed. Failure to do so could re-
sult in property damage or personal injury.
-
-
Scroll Compressors use white oil which is compatible
with 3GS oil which may be used if additional oil is re-
quired.
Operating pressures and amp draws may differ from
standard reciprocating compressors. This information
may be found in the "Cooling Performance Data" sec-
tion.
The single phase units use permanent split capacitor (PSC)
design compressors. Starting components are therefore not
required for these units. A low microfarad run capacitor as-
sists the compressor to start and remains in the circuit dur-
ing operation.
All GPC14 units have X-13 indoor blower motors that are en-
ergized by a 24V signal from the thermostat and are con-
stant torque motors with very low power consumption. The X-
13 features an integral control module.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DESIGN
In installations where the unit is installed above ground level
and not serviceable from the ground (Example: Roof Top in-
stallations), the installer must provide service platform for ser-
vice person with rails or guards in accordance with local codes
or ordinances or in their absence with the latest edition of the
Uniform Mechanical Code Section 305.
LocationandClearances
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
NOTE: Unit can also use roof curb.
10"
WARNING
36"
WALL
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION
DURING ALL RIGGING AND MOVING OPERATIONS.
TO FACILITATE LIFTING AND MOVING IF A CRANE
IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE
SLING.
UNIT
Refer to Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with
the National Roofing Contractors Association Manual.
36"
36"
Outside Slab Installation - Horizontal (H)
Minimumclearancesarerequiredtoavoidairrecirculationand
keep the unit operating at peak efficiency.
36"
24"
36"
Rooftop Installation - Horizontal (H)
29
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGE COOLING SPECIFICATIONS GPC14[24-30]H41AB
GPC1424H41AB GPC1430H41AB
COOLING CAPACITY, BTUH
SEER / EER
24,600
28,400
COOLING
14.5 / 12.1
14.0 / 12.1
CAPACITY
UNIT
VOLTAGE (NAMEPLATE)
AMPS (TOTAL)
208-230/1/60
208-230/1/60
16.1
15.76
ELECTRICAL
SPECIFICATION
19.5
19
MINIMUM CIRCUIT AMPACITY
(1)
30
30
MAXIMUM OVERCURRENT PROTECTION
TYPE
SCROLL
SCROLL
COMPRESSOR
13.5
12.8
RATED LOAD AMPS
LOCKED ROTOR AMPS
HORSEPOWER
58.3
64
1/6
1/6
CONDENSER
FAN MOTOR
RPM
815
815
FULL LOAD AMPS
LOCKED ROTOR AMPS
1.1
1.1
1.7
1.7
BLADE DIAMETER (INCHES) / # OF BLADES
FACE AREA - SQ. FT.
22 / 2
22 / 2
CONDENSER FAN
CONDENSER
COIL
12.3
12.3
NUMBER OF ROWS
1
1
FINS PER INCH
26
26
1/2 - 5
1/2 - 5
EVAPORATOR
BLOWER
HORSEPOWER - NO. OF SPEEDS
FULL LOAD AMPS
1.5
1.86
LOCKED ROTOR AMPS
NA
NA
MOTOR
T2
T2
MOTOR SPEED TAP - COOLING
RPM
1050
1050
DIAMETER X WIDTH (INCHES)
HI EFFICIENCY COOLING CFM
FAN ONLY COOLING CFM
MAX EXTERNAL STATIC PRESS ("w.c.)
FACE AREA - SQ. FT.
10 X 8
10 X 8
EVAPORATOR
BLOWER
850
1,050
800
950
0.5
0.5
5.25
5.25
EVAPORATOR
COIL
NUMBER OF ROWS
3
3
16
16
FINS PER INCH
GENERAL
FILTER SIZE - SQ. FT. *
20 x 20 x 1
20 x 25 x 1
INFORMATION
DRAIN SIZE (INCHES)
3/4"
3/4"
EXPANSION DEVICE
ORIFICE (0.057)
ORIFICE (0.062)
REFRIGERANT CHARGE R-410A (Oz.)
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)
SHIPPING WEIGHT LBS.
59
3/4, 1, 1-1/4
1/2
53
3/4, 1, 1-1/4
1/2
290
290
280
280
OPERATING WEIGHT LBS.
(1)
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGE COOLING SPECIFICATIONS
GPC14[36-48]H41AB
GPC1436H41AB GPC1442H41AB GPC1448H41AB
COOLING
COOLING CAPACITY, BTUH
SEER / EER
35,600
14.0 / 12.0
208-230/1/60
20.06
24.2
40,000
14.2 / 12.0
208-230/1/60
22.2
46,500
14.5 / 12.0
208-230/1/60
24.2
CAPACITY
UNIT
VOLTAGE (NAMEPLATE)
AMPS (TOTAL)
ELECTRICAL
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
26.6
29.1
MAXIMUM OVERCURRENT PROTECTION (1)
TYPE
40
40
45
COMPRESSOR
SCROLL
16.7
SCROLL
17.9
SCROLL
19.9
RATED LOAD AMPS
LOCKED ROTOR AMPS
HORSEPOWER
79
112
109
CONDENSER
FAN MOTOR
1/4
1/4
1/4
RPM
830
1075
1.4
1075
1.4
FULL LOAD AMPS
LOCKED ROTOR AMPS
1.5
3.0
2.9
2.9
CONDENSER FAN BLADE DIAMETER (INCHES) / # OF BLADES
22 / 3
12.3
22 / 4
16.0
22 / 4
19.5
CONDENSER
COIL
FACE AREA - SQ. FT.
NUMBER OF ROWS
1
1
1
FINS PER INCH
26
28
28
EVAPORATOR
BLOWER
HORSEPOWER - NO. OF SPEEDS
FULL LOAD AMPS
1/2 - 5
1.86
1/2 - 5
2.9
3/4 - 5
2.9
MOTOR
LOCKED ROTOR AMPS
NA
NA
NA
MOTOR SPEED TAP - COOLING
RPM
T2
T2
T2
1050
10 X 8
1,200
NA
1050
10 x 8
1,300
NA
1050
10 x 8
1,600
NA
EVAPORATOR
BLOWER
DIAMETER X WIDTH (INCHES)
HI EFFICIENCY COOLING CFM
5 TON NOMINAL COOLING CFM
FAN ONLY COOLING CFM
MAX EXTERNAL STATIC PRESS ("w.c.)
FACE AREA - SQ. FT.
1,100
0.5
1,200
0.5
1,400
0.5
EVAPORATOR
COIL
5.2
6.2
6.2
NUMBER OF ROWS
3
4
4
FINS PER INCH
14
14
14
GENERAL
FILTER SIZE - SQ. FT. *
25 x 25 x 1
3/4"
(2) 20 x 20 x 1
3/4"
(2) 20 x 20 x 1
3/4"
INFORMATION
DRAIN SIZE (INCHES)
EXPANSION DEVICE
ORIFICE (0.068) ORIFICE (0.072) ORIFICE (0.078)
REFRIGERANT CHARGE R-410A (Oz.)
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)
SHIPPING WEIGHT LBS.
OPERATING WEIGHT LBS.
65
3/4, 1, 1-1/4
1/2
94
3/4, 1, 1-1/4
1/2
90
3/4, 1, 1-1/4
1/2
370
370
400
360
360
390
(1)
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1424H41AB
32
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1424H41AB
33
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1430H41AB
34
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1430H41AB
35
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1436H41AB
36
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1436H41AB
37
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1442H41AB
38
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1442H41AB
39
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1448H41AB
40
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
COOLING PERFORMANCE DATA
GPC1448H41AB
41
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
5MM COILS
WIRING DIAGRAMS
GPC14[24-48]H41AB
PU
NOTE #3
BK
BK
PU
PU
BL
C
BK
BL
T2
RD
RD
C
BL
SEE NOTE 5
T1
BK
BK
/
/
RD
GR
YL
GND
BK
RD
RD
YL
PU
LVJB
YL
WH
RD
C
BR
H
E
R
M
O
S
WH
YL
RD
GR
Y
R
G
GR
BL
PLF
W1
WH
YL
H
RCCF
BL
BR
BR
BL
W2
C
GR
A
PU
++
BR
RD
BK
BK
SA
(IF USED) SEE NOTE 4
RD
BK
CONTROL
BOX
YL
PU BR
YL
GR
WH
S
C
R
C
G
N
CM
COMP
SEE NOTE 2
EM
L1
L2
COMPONENT LEGEND
CONTACTOR
FACTORY WIRING
SUPPLY VOLTAGE
208-240/1/60
LINE VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH
VOLTAGE
C
CM
COMP
EM
GND
LVJB
PLF
RCCF
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
EQUIPMENT GROUND
LOW VOLTAGE JUNCTION BOX
FEMALE PLUG / CONNECTOR
RUN CAPACITOR FOR^J
COMPRESSOR AND FAN
START ASSIST
T2
C
R
C
T1
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
C
COMP
C
RCC
F
S
H
F
S.A.
CM
SA
TR
NOTE #4
TRANSFORMER
WIRE CODE
BK BLACK
BL BLUE
IF USED
NOTE #2
EM
BR BROWN
GR GREEN
OR ORANGE
PU PURPLE
RD RED
L
N
3
2
G
1
WH WHITE
YL YELLOW
208-240
2
NOTE #4
3
1
TR
24V
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW
LEADS FROM EM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE
ENERGIZED, THE HIGHER SPEED SETTING IS USED.
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED
5. USE COPPER CONDUCTORS ONLY.
C
EM
SEE NOTE #2
++ USE N.E.C. CLASS 2 WIRE
4
5
6
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
C
R
W2
W1
Y
G
C
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
|