Goodman Mfg Air Conditioner GPC 14 SEER R 410 Package Air Conditioners with R 410A User Manual

TECHNICAL MANUAL  
GPC 14 SEER R-410A  
Package Air Conditioners  
with R-410A  
Refer to Service Manual RS6300011 (Horizontal)  
for installation, operation, and troubleshooting information.  
All safety information must be followed as provided in the Service Manual.  
Refer to the appropriate Parts Catalog for part number information.  
Models listed on page 3.  
Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency**  
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and  
Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult  
a tax professional if they have questions about the applicability of these credits.  
RT6322007r6  
September2010  
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not  
assume any responsibility for property damage or personal injury due to improper service procedures or  
services performed by an unqualified person.  
Copyright © 2009 - 2010 Goodman Manufacturing Company, L.P.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT IDENTIFICATION  
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please  
use these numbers when requesting service or parts information.  
5mm  
GPC1424H41AA  
GPC1430H41AA  
GPC1436H41AA  
GPC1442H41AA  
GPC1448H41AA  
GPC1460H41AA  
GPC1424H41AB  
GPC1430H41AB  
GPC1436H41AB  
GPC1442H41AB  
GPC1448H41AB  
AB model specific  
5 mm information  
begins on page 28.  
Models qualify for the 2009 and 2010 Federal Tax Credits  
for Energy Efficiency**  
**Note that these tax credits are subject to specific requirements set forth in the American  
Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman  
recommends that consumers consult a tax professional if they have questions about the  
applicability of these credits.  
The United States Environmental Protection Agency (“EPA”) has issued various regulations re-  
garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow  
these regulations may harm the environment and can lead to the imposition of substantial fines.  
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.  
WARNING  
WARNING  
Do not connect or use any device  
To prevent the risk of property  
WARNING  
that is not design certified by  
damage, personal injury, or death,  
Goodman for use with this unit.  
do not store combustible materials or use gasoline or  
Serious property damage, personal injury, reduced unit  
performance and/or hazardous conditions may result  
from the use of such non-approved devices.  
other flammable liquids or vapors in the vicinity of this  
appliance.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
GPC Package Cooling Units are designed for outdoor instal-  
lations only in either residential or light commercial applica-  
tions.  
-
Due to their design Scroll Compressors are inherently  
more tolerant of liquid refrigerant. NOTE: Even though the  
compressor section of a Scroll compressor is more toler-  
ant of liquid refrigerant, continued floodback or flooded  
start conditions may wash oil from the bearing surfaces  
causing premature bearing failure.  
The connecting ductwork (Supply and Return) can be con-  
nected for either horizontal or vertical airflow. In the vertical  
application a matching Roof Curb is recommended.  
-
-
Scroll Compressors use white oil which is compatible  
with 3GS oil which may be used if additional oil is re-  
quired.  
A return air filter must be installed behind the return air grille(s)  
or provision must be made for a filter in an accessible loca-  
tion within the return air duct. The minimum filter area should  
not be less than those sizes listed in the Specification Sec-  
tion. Under no circumstances should the unit be operated  
without return air filters.  
Operating pressures and amp draws may differ from stan-  
dard reciprocating compressors. This information may be  
found in the "Cooling Performance Data" section.  
A 3/4” PVC pipe is provided for removal of condensate water  
from the indoor coil In order to provide proper condensate  
flow, a drain trap is supplied and shipped loose inside the  
unit for field installation. (Do not reduce the drain line size.)  
LocationandClearances  
NOTE: To ensure proper condensate drainage, unit must be  
installed in a level position.  
Refrigerant flow control is achieved by use of restrictor ori-  
fices. GPC units use the FasTest Access Fitting System  
with a saddle that is either soldered to the suction and liquid  
lines or is fastened with a locking nut to the access fitting  
box (core) and then screwed into the saddle. Do not re-  
move the core from the saddle until the refrigerant  
charge has been removed. Failure to do so could re-  
sult in property damage or personal injury.  
10"  
36"  
WALL  
The single phase units use permanent split capacitor (PSC)  
design compressors. Starting components are therefore not  
required for these units. A low microfarad run capacitor as-  
sists the compressor to start and remains in the circuit dur-  
ing operation.  
UNIT  
All GPC14 units have X-13 indoor blower motors that are en-  
ergized by a 24V signal from the thermostat and are con-  
stant torque motors with very low power consumption. The X-  
13 features an integral control module.  
36"  
Air for condensing (cooling cycle) is drawn through the out-  
door coil by a propeller fan, and is discharged vertically out  
the top of the unit. The outdoor coil is designed for .0 static.  
No additional restriction (ductwork) shall be applied.  
36"  
Conditioned air is drawn through the filter(s), field installed,  
across the coil and back into the conditioned space by the  
indoor blower.  
Outside Slab Installation - Horizontal (H)  
Minimumclearancesarerequiredtoavoidairrecirculationand  
keep the unit operating at peak efficiency.  
GPC1424-30H41* use Copeland Reciprocating Compressors.  
GPC1436-60H41* use Copeland Scroll Compressors. There  
are a number of design characteristics which are different  
from the traditional reciprocating compressor.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
In installations where the unit is installed above ground level  
and not serviceable from the ground (Example: Roof Top in-  
stallations), the installer must provide service platform for ser-  
vice person with rails or guards in accordance with local codes  
or ordinances or in their absence with the latest edition of the  
Uniform Mechanical Code Section 305.  
36"  
NOTE: Unit can also use roof curb.  
24"  
WARNING  
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE  
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION  
DURING ALL RIGGING AND MOVING OPERATIONS.  
TO FACILITATE LIFTING AND MOVING IF A CRANE  
IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE  
SLING.  
36"  
Refer to Roof Curb Installation Instructions for proper curb  
installation. Curbing must be installed in compliance with  
the National Roofing Contractors Association Manual.  
Rooftop Installation - Horizontal (H)  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DIMENSIONS  
GPC14[24-60]H41A*  
A
14.000  
4.512  
4.500  
14.000  
SUPPLY  
6.500  
14.000  
RETURN  
BACK VIEW  
(DUCT OPENINGS)  
66.542  
B
34.075  
Chassis  
Model  
A
B
GPC1424  
GPC1430  
GPC1436  
GPC1442  
GPC1448  
GPC1460  
33  
33  
33  
33  
33  
33  
30½  
30½  
35½  
35½  
38½  
38½  
Small  
Medium  
Large  
Dimensions in inches  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
GPC14[24-60]H41A*  
HKR ELECTRICAL DATA  
Circuit #1  
Circuit #2  
Maximum  
Overcurrent  
Protection (amps)  
at 208 / 240V  
Maximum  
Actual  
kW & BTU  
at 240V  
Minimum Circuit  
Ampacity  
at 208 / 240V  
Minimum Circuit  
Ampacity  
at 208 / 240V  
Model and Heat Kit Usage  
Overcurrent  
Protection (amps)  
at 208 / 240V  
GPH1424H41A*  
HKR05*,C*  
24 / 27  
33 / 28  
45 / 51  
30 / 30  
40 / 40  
60 / 60  
----  
----  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
HKR08*,C*  
HKR10*,C*  
GPH1430H41A*  
HKR05*,C*  
24 / 27  
34 / 39  
45 / 52  
45 / 52  
30 / 30  
40 / 40  
60 / 60  
60 / 60  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
14.25 / 48,600  
HKR08*,C*  
HKR10*,C*  
HKR15*,C*  
GPH1436H41A*  
HKR05*,C*  
HKR08*,C*  
HKR10*,C*  
HKR15*,C*  
GPH1442H41A*  
HKR05*,C*  
HKR08*,C*  
HKR10*,C*  
HKR15*,C*  
HKR20*,C*  
GPH1448H41A*  
HKR05*,C*  
HKR08*,C*  
HKR10*,C*  
HKR15*,C*  
HKR20*,C*  
----  
----  
22 / 25  
30 / 30  
24 / 27  
34 / 39  
45 / 52  
45 / 52  
30 / 30  
40 / 40  
60 / 60  
60 / 60  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
14.25 / 48,600  
----  
22 / 25  
----  
30 / 30  
25 / 27  
34 / 39  
46 / 52  
46 / 52  
46 / 52  
30 / 30  
40 / 40  
60 / 60  
60 / 60  
60 / 60  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
14.25 / 48,600  
19.50 / 66,500  
----  
----  
22 / 25  
43 / 49  
30 / 30  
60 / 60  
25 / 28  
34 / 40  
30 / 30  
40 / 40  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
46 / 53  
46 / 52  
46 / 52  
60 / 60  
60 / 60  
60 / 60  
----  
----  
9.50 / 32,400  
14.25 / 48,600  
19.50 / 66,500  
22 / 25  
43 / 49  
30 / 30  
60 / 60  
GPH1460H41A*  
HKR05*,C*  
HKR08*,C*  
HKR10*,C*  
HKR15*,C*  
HKR20*,C*  
26 / 30  
36 / 40  
48 / 54  
30 / 30  
40 / 40  
60 / 60  
----  
----  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
48 / 54  
48 / 54  
60 / 60  
60 / 60  
22 / 25  
43 / 49  
30 / 30  
60 / 60  
14.25 / 48,600  
19.50 / 66,500  
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.  
All wires and overcurrent protection devices are sized for use with electric heaters only and without  
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See  
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent  
protection during refrigeration cycle.  
WARNING  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPC14[24-60]H41A*  
ACCESSORIES  
Part Number  
OT18-60A  
Description  
Outdoor Thermostat Kit w/Lockout Stat  
Emergency Heat Relay Kit  
Electric Heat Kit  
OT/EHR18-60  
HKR  
PCCP101-103  
PCP101-103  
PCP101-103R8  
GPCED101-103  
GPHED101-103  
GPCEH101-103  
GPHEH101-103  
PCMD101-103  
PCMDM101-103  
GPHMD101-103  
SQRPCH101  
SQRPCH102-103  
SQRPC101  
Roof Curb  
Downflow Plenum Kit  
Downflow Plenum Kit w/ R-8 Insulation  
Downflow Economizer for GPC-(H) A/C - To Be Used With PCP101-103  
Downflow Economizer for GPH-(H) Heat Pump - To Be Used With PCP101-103  
Horizontal Economizer for GPC-(H) A/C  
Horizontal Economizer for GPH-(H) Heat Pump  
Manual Damper - To Be Used With PCP101-103  
Motorized Damper - To Be Used With PCP101-103  
Manual Damper for Horizontal Applications  
Square to Round Adapters 16"&14"  
Square to Round Adapters 18"&14"  
Square to Round Adapter - For Use With PCCP101-103 Curb 16" Rounds  
Square to Round Adapter For Use With PCCP101-103 Curb 18" Rounds  
External Horizontal Filter Rack  
SQRPC102-103  
PCFR101-103  
PCEF101-103  
CDK36  
Elbow & Flashing w/ R-8 Liner  
Flush Mount Concentric Duct Kit  
CDK36515  
Flush Mount Concentric Duct Kit w/ Filter  
CDK36530  
Step Down Concentric Duct Kit  
CDK36535  
Step Down Concentric Duct Kit w/ Filter  
CDK4872  
Flush Mount Concentric Duct Kit  
CDK4872515  
CDK4872530  
CDK4872535  
Flush Mount Concentric Duct Kit w/ Filter  
Step Down Concentric Duct Kit  
Step Down Concentric Duct Kit w/ Filter  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPC14[24-60]H41A*  
BLOWER PERFORMANCE DATA  
Dry Coil Data  
E.S.P (In. of H2O)  
Model  
Speed  
Volts  
CFM  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
934  
759  
755  
638  
581  
489  
-
-
T1  
230  
230  
230  
WATTS  
CFM  
95  
77  
76  
73  
83  
90  
652  
133  
-
-
601  
142  
-
-
-
990  
837  
801  
744  
696  
119  
876  
169  
797  
144  
937  
185  
1124  
257  
933  
179  
1099  
213  
1181  
247  
1055  
211  
1147  
245  
1336  
303  
1275  
299  
1510  
455  
1590  
550  
1510  
T2,T3  
T4, T5  
WATTS 107  
CFM 1061  
WATTS 126  
CFM 1022  
WATTS 116  
CFM 1103  
WATTS 142  
CFM 1285  
WATTS 205  
CFM 1234  
WATTS 144  
CFM 1287  
WATTS 162  
CFM 1381  
WATTS 195  
CFM 1272  
WATTS 160  
CFM 1357  
WATTS 188  
CFM 1537  
WATTS 244  
CFM 1418  
WATTS 242  
CFM 1175  
WATTS 395  
CFM 1845  
WATTS 490  
CFM 1775  
WATTS 395  
CFM 2025  
WATTS 575  
94  
105  
110  
-
989  
947  
925  
-
134  
146  
158  
-
-
-
929  
894  
829  
748  
156  
-
695  
168  
-
643  
173  
-
T1  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
114  
126  
134  
1063  
154  
1012  
165  
962  
T2,T3  
T4, T5  
T1  
173  
-
-
-
1240  
218  
1202  
231  
1163  
244  
1076  
268  
922  
183  
1053  
221  
1144  
258  
998  
220  
1099  
255  
1293  
317  
1228  
308  
1450  
465  
1580  
560  
1450  
1046  
280  
-
1003  
288  
-
1111  
140  
1071  
152  
1024  
164  
-
-
1232  
175  
1186  
187  
1133  
201  
-
-
T2,T3  
T4, T5  
T1  
-
-
1325  
203  
1277  
217  
1233  
233  
-
-
-
-
1197  
168  
1145  
183  
1106  
191  
947  
230  
1049  
267  
1253  
329  
1178  
320  
1430  
470  
1530  
570  
1430  
906  
243  
1008  
284  
1208  
341  
1141  
338  
1400  
475  
1500  
575  
1400  
1297  
202  
1244  
213  
1194  
228  
T2,T3  
T4, T5  
T1  
1478  
258  
1431  
274  
1386  
288  
1383  
258  
1349  
273  
1312  
282  
1635  
420  
1645  
435  
1515  
445  
T2,T3  
T4, T5  
1790  
505  
1715  
520  
1685  
535  
1635  
1645  
1515  
T1, T2, T3 230  
420  
1900  
595  
435  
1840  
620  
445  
1780  
630  
455  
1725  
645  
465  
1650  
655  
470  
1620  
660  
475  
1580  
670  
T4, T5  
230  
NOTES:  
1. Data shown is dry coil. Wet coil pressure drop is approx.  
2. 0.1" H2O, for 2 row indoor coil; 0.2” H2O, for 3 row indoor coil; and 0.3” H2O, for 4 row indoor coil.  
3. Data shown does not include filter pressure drop, approx. 0.08” H2O.  
4. Reduce airflow by 2% for 208V operation.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA  
S E R E I R U  
M P T E E R A T  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE COOLING SPECIFICATIONS  
GPC14[24-30]H41AA  
GPC1424H41*  
GPC1430H41*  
COOLING  
COOLING CAPACITY, BTUH  
SEER / EER  
24,600  
14.5 / 12.1  
208-230/1/60  
10.5  
12.5  
20  
28,400  
14.0 / 12.1  
208-230/1/60  
13.16  
15.6  
25  
CAPACITY  
UNIT  
VOLTAGE (NAMEPLATE)  
AMPS (TOTAL)  
ELECTRICAL  
SPECIFICATION  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM OVERCURRENT PROTECTION (1)  
COMPRESSOR  
TYPE  
RECIP  
7.9  
RECIP  
9.8  
RATED LOAD AMPS  
LOCKED ROTOR AMPS  
HORSEPOWER  
41  
55  
CONDENSER  
FAN MOTOR  
1/6  
1/4  
RPM  
815  
830  
FULL LOAD AMPS  
1.1  
1.5  
LOCKED ROTOR AMPS  
BLADE DIAMETER (INCHES) / # OF BLADES  
FACE AREA - SQ. FT.  
1.7  
3.0  
22 / 3  
13.4  
1
22 / 3  
13.4  
1
CONDENSER FAN  
CONDENSER  
COIL  
NUMBER OF ROWS  
FINS PER INCH  
24  
24  
EVAPORATOR  
BLOWER  
HORSEPOWER - NO. OF SPEEDS  
FULL LOAD AMPS  
1/2 - 5  
1.5  
1/2 - 5  
1.86  
NA  
MOTOR  
LOCKED ROTOR AMPS  
MOTOR SPEED TAP - COOLING  
RPM  
NA  
T2  
T2  
1050  
10 X 8  
850  
1050  
10 X 8  
1,050  
NA  
DIAMETER X WIDTH (INCHES)  
HI EFFICIENCY COOLING CFM  
5 TON NOMINAL COOLING CFM  
FAN ONLY COOLING CFM  
MAX EXTERNAL STATIC PRESS ("w.c.)  
FACE AREA - SQ. FT.  
EVAPORATOR  
BLOWER  
NA  
800  
950  
0.5  
0.5  
EVAPORATOR  
COIL  
5.25  
3
5.25  
3
NUMBER OF ROWS  
FINS PER INCH  
16  
16  
FILTER SIZE - SQ. FT. *  
DRAIN SIZE (INCHES)  
20 x 20 x 1  
3/4"  
20 x 25 x 1  
3/4"  
GENERAL  
INFORMATION  
EXPANSION DEVICE  
ORIFICE (0.057) ORIFICE (0.060)  
REFRIGERANT CHARGE R-410A (Oz.)  
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN  
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)  
SHIPPING WEIGHT LBS.  
OPERATING WEIGHT LBS.  
83  
3/4, 1, 1-1/4  
1/2  
78  
3/4, 1, 1-1/4  
1/2  
310  
310  
300  
300  
(1)  
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
Calculated external filter size based on air velocity of 300 ft/min.  
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers  
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE COOLING SPECIFICATIONS GPC14[36-42]H41AA  
GPC1436H41*  
GPC1442H41*  
COOLING CAPACITY, BTUH  
SEER / EER  
35,600  
14.0 / 12.0  
208-230/1/60  
20.06  
24.2  
40  
40,000  
14.2/ 12.0  
208-230/1/60  
22.2  
COOLING  
CAPACITY  
UNIT  
VOLTAGE (NAMEPLATE)  
AMPS (TOTAL)  
ELECTRICAL  
SPECIFICATION  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM OVERCURRENT PROTECTION (1)  
TYPE  
26.6  
40  
COMPRESSOR  
SCROLL  
16.7  
79  
SCROLL  
17.9  
RATED LOAD AMPS  
LOCKED ROTOR AMPS  
HORSEPOWER  
112  
CONDENSER  
FAN MOTOR  
1/4  
1/4  
RPM  
830  
1075  
1.4  
FULL LOAD AMPS  
1.5  
LOCKED ROTOR AMPS  
BLADE DIAMETER (INCHES) / # OF BLADES  
FACE AREA - SQ. FT.  
3.0  
2.9  
22 / 3  
13.4  
1
22 / 4  
17.0  
CONDENSER FAN  
CONDENSER  
COIL  
NUMBER OF ROWS  
1
FINS PER INCH  
24  
24  
HORSEPOWER - NO. OF SPEEDS  
FULL LOAD AMPS  
1/2 - 5  
1.86  
NA  
1/2 - 5  
2.9  
EVAPORATOR  
BLOWER  
MOTOR  
LOCKED ROTOR AMPS  
MOTOR SPEED TAP - COOLING  
RPM  
NA  
T2  
T2  
1050  
10 X 8  
1,200  
NA  
1050  
10 x 8  
1,300  
NA  
EVAPORATOR  
BLOWER  
DIAMETER X WIDTH (INCHES)  
HI EFFICIENCY COOLING CFM  
5 TON NOMINAL COOLING CFM  
FAN ONLY COOLING CFM  
MAX EXTERNAL STATIC PRESS ("w.c.)  
FACE AREA - SQ. FT.  
1,100  
0.5  
1,200  
0.5  
EVAPORATOR  
COIL  
5.2  
6.2  
NUMBER OF ROWS  
3
4
FINS PER INCH  
14  
14  
GENERAL  
FILTER SIZE - SQ. FT. *  
DRAIN SIZE (INCHES)  
25 x 25 x 1  
3/4"  
(2) 20 x 20 x 1  
3/4"  
INFORMATION  
EXPANSION DEVICE  
ORIFICE (0.065) ORIFICE (0.072)  
REFRIGERANT CHARGE R-410A (Oz.)  
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN  
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)  
SHIPPING WEIGHT LBS.  
OPERATING WEIGHT LBS.  
80  
3/4, 1, 1-1/4  
1/2  
118  
3/4, 1, 1-1/4  
1/2  
370  
370  
360  
360  
(1)  
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
Calculated external filter size based on air velocity of 300 ft/min.  
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers  
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE COOLING SPECIFICATIONS  
GPC14[48-60]H41AA  
GPC1448H41*  
GPC1460H41*  
COOLING CAPACITY, BTUH  
SEER / EER  
46,500  
14.5 / 12.0  
208-230/1/60  
24.2  
57,500  
14.5 / 12.0  
208-230/1/60  
30.7  
COOLING  
CAPACITY  
UNIT  
VOLTAGE (NAMEPLATE)  
AMPS (TOTAL)  
ELECTRICAL  
SPECIFICATION  
MINIMUM CIRCUIT AMPACITY  
29.1  
37.3  
MAXIMUM OVERCURRENT PROTECTION (1)  
TYPE  
45  
60  
SCROLL  
19.9  
SCROLL  
26.4  
COMPRESSOR  
RATED LOAD AMPS  
LOCKED ROTOR AMPS  
HORSEPOWER  
109  
134  
CONDENSER  
FAN MOTOR  
1/4  
1/4  
RPM  
1075  
1.4  
1075  
1.4  
FULL LOAD AMPS  
LOCKED ROTOR AMPS  
BLADE DIAMETER (INCHES) / # OF BLADES  
FACE AREA - SQ. FT.  
2.9  
2.9  
22 / 4  
19.1  
22 / 4  
19.1  
CONDENSER FAN  
CONDENSER  
COIL  
NUMBER OF ROWS  
1
2
FINS PER INCH  
21  
16  
EVAPORATOR  
BLOWER  
HORSEPOWER - NO. OF SPEEDS  
FULL LOAD AMPS  
3/4 - 5  
2.9  
3/4 - 5  
2.9  
LOCKED ROTOR AMPS  
MOTOR SPEED TAP - COOLING  
RPM  
NA  
NA  
MOTOR  
T2  
T2  
1050  
10 x 8  
1,600  
NA  
1050  
11 x 8  
1,600  
1,800  
1,600  
0.5  
DIAMETER X WIDTH (INCHES)  
HI EFFICIENCY COOLING CFM  
5 TON NOMINAL COOLING CFM  
FAN ONLY COOLING CFM  
MAX EXTERNAL STATIC PRESS ("w.c.)  
FACE AREA - SQ. FT.  
EVAPORATOR  
BLOWER  
1,400  
0.5  
6.2  
7.0  
EVAPORATOR  
COIL  
NUMBER OF ROWS  
4
4
FINS PER INCH  
14  
14  
GENERAL  
FILTER SIZE - SQ. FT. *  
DRAIN SIZE (INCHES)  
(2) 20 x 20 x 1  
3/4"  
(2) 20 x 25 x 1  
3/4"  
INFORMATION  
EXPANSION DEVICE  
ORIFICE (0.076) ORIFICE (0.088)  
REFRIGERANT CHARGE R-410A (Oz.)  
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)  
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)  
SHIPPING WEIGHT LBS.  
OPERATING WEIGHT LBS.  
123  
3/4, 1, 1-1/4  
1/2  
188  
3/4, 1, 1-1/4  
1/2  
400  
400  
390  
390  
(1)  
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
Calculated external filter size based on air velocity of 300 ft/min.  
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers  
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1424H41AA  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1424H41AA  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1430H41AA  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1430H41AA  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1436H41AA  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1436H41AA  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1442H41AA  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1442H41AA  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1448H41AA  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1448H41AA  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1460H41AA  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPC1460H41AA  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
PERFORMANCE TEST  
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor  
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:  
If conditions vary from this, results will change as follows:  
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low  
and high side pressures and power will not change.  
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will  
occur in low and high side pressures and power.  
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.  
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.  
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.  
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAMS  
GPC14[24-60]H41AA  
PU  
NOTE #3  
PU  
BK  
2
BK  
PU  
1
3
240  
BL  
C
208  
BK  
2
0
8
-
2
4
0
/
BL  
L2  
C
T2  
T1  
RD  
24V  
RD  
BL  
SEE NOTE 5  
L1  
BK  
BK  
RD  
1
/
YL  
GND  
GR  
BK  
60  
RD  
RD  
YL  
PU  
LVJB  
YL  
H
T
H
E
R
M
O
S
T
WH  
WH  
RD  
C
BR  
F
YL  
RD  
GR  
Y
R
G
GR  
BL  
PLF  
3
6
5
4
9
8
7
W1  
WH  
YL  
RCCF  
BL  
GR  
2
1
BR  
BR  
BL  
W2  
C
A
T
++  
PU  
BR  
RD  
BK  
BK  
SA  
(IF USED) SEE NOTE 4  
CONTROL  
BOX  
RD  
C
BK  
YL  
PU BR  
CM  
YL  
GR  
WH  
S
R
C
L
2
G
3
N
4
1
5
HPS  
COMP  
WH  
EM  
SEE NOTE 2  
L1  
L2  
COMPONENT LEGEND  
CONTACTOR  
FACTORY WIRING  
SUPPLY VOLTAGE  
208-240/1/60  
LINE VOLTAGE  
LOW VOLTAGE  
OPTINAL HIGH  
VOLTAGE  
C
CM  
CONDENSER MOTOR  
COMP  
COMPRESSOR  
EM  
EVAPORATOR MOTOR  
EQUIPMENT GROUND  
LOW VOLTAGE JUNCTION BOX  
FEMALE PLUG / CONNECTOR  
RUN CAPACITOR FOR  
COMPRESSOR AND FAN  
START ASSIST  
T2  
C
GND  
LVJB  
PLF  
R
COMP  
C
FIELD WIRING  
HIGH VOLTAGE  
LOW VOLTAGE  
T1  
C
C
RCCF  
S
H
RCCF  
F
S.A.  
CM  
SA  
TR  
NOTE #4  
TRANSFORMER  
WIRE CODE  
BK BLACK  
BL BLUE  
HPS  
HIGH PRESSURE SWITCH  
IF USED  
NOTE #2  
EM  
BR BROWN  
GR GREEN  
OR ORANGE  
PU PURPLE  
RD RED  
L
N
3
G
1
2
WH WHITE  
YL YELLOW  
208-240  
2
NOTE #4  
3
1
TR  
24V  
NOTES:  
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS  
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.  
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW  
LEADS FROM EM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE  
ENERGIZED, THE HIGHER SPEED SETTING IS USED.  
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES  
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.  
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED  
5. USE COPPER CONDUCTORS ONLY.  
C
1
2
EM  
SEE NOTE #2  
3
++ USE N.E.C. CLASS 2 WIRE  
4
5
6
PLF  
SEE UNIT RATING PLATE FOR TYPE AND SIZE  
OF OVER CURRENT PROTECTION  
C
HPS  
R
W2  
W1  
Y
G
C
THERMOSTAT  
208-240/1/60 0140G00871 REV. B  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPC 14 SEER R-410A  
5mm Package Air Conditioners  
GPC1424H41AB GPC1442H41AB  
GPC1430H41AB GPC1448H41AB  
GPC1436H41AB  
PRODUCT DESIGN  
GPC Package Cooling Units are designed for outdoor instal-  
lations only in either residential or light commercial applica-  
tions.  
Air for condensing (cooling cycle) is drawn through the out-  
door coil by a propeller fan, and is discharged vertically out  
the top of the unit. The outdoor coil is designed for .0 static.  
No additional restriction (ductwork) shall be applied.  
The connecting ductwork (Supply and Return) can be con-  
nected for either horizontal or vertical airflow. In the vertical  
application a matching Roof Curb is recommended.  
Conditioned air is drawn through the filter(s), field installed,  
across the coil and back into the conditioned space by the  
indoor blower.  
A return air filter must be installed behind the return air grille(s)  
or provision must be made for a filter in an accessible loca-  
tion within the return air duct. The minimum filter area should  
not be less than those sizes listed in the Specification Sec-  
tion. Under no circumstances should the unit be operated  
without return air filters.  
GPC1424-60H41AB models use Copeland Scroll Compres-  
sors. There are a number of design characteristics which  
are different from the traditional reciprocating compressor.  
-
Due to their design Scroll Compressors are inherently  
more tolerant of liquid refrigerant. NOTE: Even though  
the compressor section of a Scroll compressor is more  
tolerant of liquid refrigerant, continued floodback or  
flooded start conditions may wash oil from the bearing  
surfaces causing premature bearing failure.  
A 3/4” PVC pipe is provided for removal of condensate water  
from the indoor coil In order to provide proper condensate  
flow, a drain trap is supplied and shipped loose inside the  
unit for field installation. (Do not reduce the drain line size.)  
Refrigerant flow control is achieved by use of restrictor ori-  
fices. GPC units use the FasTest Access Fitting System  
with a saddle that is either soldered to the suction and liquid  
lines or is fastened with a locking nut to the access fitting  
box (core) and then screwed into the saddle. Do not re-  
move the core from the saddle until the refrigerant  
charge has been removed. Failure to do so could re-  
sult in property damage or personal injury.  
-
-
Scroll Compressors use white oil which is compatible  
with 3GS oil which may be used if additional oil is re-  
quired.  
Operating pressures and amp draws may differ from  
standard reciprocating compressors. This information  
may be found in the "Cooling Performance Data" sec-  
tion.  
The single phase units use permanent split capacitor (PSC)  
design compressors. Starting components are therefore not  
required for these units. A low microfarad run capacitor as-  
sists the compressor to start and remains in the circuit dur-  
ing operation.  
All GPC14 units have X-13 indoor blower motors that are en-  
ergized by a 24V signal from the thermostat and are con-  
stant torque motors with very low power consumption. The X-  
13 features an integral control module.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
In installations where the unit is installed above ground level  
and not serviceable from the ground (Example: Roof Top in-  
stallations), the installer must provide service platform for ser-  
vice person with rails or guards in accordance with local codes  
or ordinances or in their absence with the latest edition of the  
Uniform Mechanical Code Section 305.  
LocationandClearances  
NOTE: To ensure proper condensate drainage, unit must be  
installed in a level position.  
NOTE: Unit can also use roof curb.  
10"  
WARNING  
36"  
WALL  
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE  
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION  
DURING ALL RIGGING AND MOVING OPERATIONS.  
TO FACILITATE LIFTING AND MOVING IF A CRANE  
IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE  
SLING.  
UNIT  
Refer to Roof Curb Installation Instructions for proper curb  
installation. Curbing must be installed in compliance with  
the National Roofing Contractors Association Manual.  
36"  
36"  
Outside Slab Installation - Horizontal (H)  
Minimumclearancesarerequiredtoavoidairrecirculationand  
keep the unit operating at peak efficiency.  
36"  
24"  
36"  
Rooftop Installation - Horizontal (H)  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE COOLING SPECIFICATIONS GPC14[24-30]H41AB  
GPC1424H41AB GPC1430H41AB  
COOLING CAPACITY, BTUH  
SEER / EER  
24,600  
28,400  
COOLING  
14.5 / 12.1  
14.0 / 12.1  
CAPACITY  
UNIT  
VOLTAGE (NAMEPLATE)  
AMPS (TOTAL)  
208-230/1/60  
208-230/1/60  
16.1  
15.76  
ELECTRICAL  
SPECIFICATION  
19.5  
19  
MINIMUM CIRCUIT AMPACITY  
(1)  
30  
30  
MAXIMUM OVERCURRENT PROTECTION  
TYPE  
SCROLL  
SCROLL  
COMPRESSOR  
13.5  
12.8  
RATED LOAD AMPS  
LOCKED ROTOR AMPS  
HORSEPOWER  
58.3  
64  
1/6  
1/6  
CONDENSER  
FAN MOTOR  
RPM  
815  
815  
FULL LOAD AMPS  
LOCKED ROTOR AMPS  
1.1  
1.1  
1.7  
1.7  
BLADE DIAMETER (INCHES) / # OF BLADES  
FACE AREA - SQ. FT.  
22 / 2  
22 / 2  
CONDENSER FAN  
CONDENSER  
COIL  
12.3  
12.3  
NUMBER OF ROWS  
1
1
FINS PER INCH  
26  
26  
1/2 - 5  
1/2 - 5  
EVAPORATOR  
BLOWER  
HORSEPOWER - NO. OF SPEEDS  
FULL LOAD AMPS  
1.5  
1.86  
LOCKED ROTOR AMPS  
NA  
NA  
MOTOR  
T2  
T2  
MOTOR SPEED TAP - COOLING  
RPM  
1050  
1050  
DIAMETER X WIDTH (INCHES)  
HI EFFICIENCY COOLING CFM  
FAN ONLY COOLING CFM  
MAX EXTERNAL STATIC PRESS ("w.c.)  
FACE AREA - SQ. FT.  
10 X 8  
10 X 8  
EVAPORATOR  
BLOWER  
850  
1,050  
800  
950  
0.5  
0.5  
5.25  
5.25  
EVAPORATOR  
COIL  
NUMBER OF ROWS  
3
3
16  
16  
FINS PER INCH  
GENERAL  
FILTER SIZE - SQ. FT. *  
20 x 20 x 1  
20 x 25 x 1  
INFORMATION  
DRAIN SIZE (INCHES)  
3/4"  
3/4"  
EXPANSION DEVICE  
ORIFICE (0.057)  
ORIFICE (0.062)  
REFRIGERANT CHARGE R-410A (Oz.)  
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)  
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)  
SHIPPING WEIGHT LBS.  
59  
3/4, 1, 1-1/4  
1/2  
53  
3/4, 1, 1-1/4  
1/2  
290  
290  
280  
280  
OPERATING WEIGHT LBS.  
(1)  
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
Calculated external filter size based on air velocity of 300 ft/min.  
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers  
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE COOLING SPECIFICATIONS  
GPC14[36-48]H41AB  
GPC1436H41AB GPC1442H41AB GPC1448H41AB  
COOLING  
COOLING CAPACITY, BTUH  
SEER / EER  
35,600  
14.0 / 12.0  
208-230/1/60  
20.06  
24.2  
40,000  
14.2 / 12.0  
208-230/1/60  
22.2  
46,500  
14.5 / 12.0  
208-230/1/60  
24.2  
CAPACITY  
UNIT  
VOLTAGE (NAMEPLATE)  
AMPS (TOTAL)  
ELECTRICAL  
SPECIFICATION  
MINIMUM CIRCUIT AMPACITY  
26.6  
29.1  
MAXIMUM OVERCURRENT PROTECTION (1)  
TYPE  
40  
40  
45  
COMPRESSOR  
SCROLL  
16.7  
SCROLL  
17.9  
SCROLL  
19.9  
RATED LOAD AMPS  
LOCKED ROTOR AMPS  
HORSEPOWER  
79  
112  
109  
CONDENSER  
FAN MOTOR  
1/4  
1/4  
1/4  
RPM  
830  
1075  
1.4  
1075  
1.4  
FULL LOAD AMPS  
LOCKED ROTOR AMPS  
1.5  
3.0  
2.9  
2.9  
CONDENSER FAN BLADE DIAMETER (INCHES) / # OF BLADES  
22 / 3  
12.3  
22 / 4  
16.0  
22 / 4  
19.5  
CONDENSER  
COIL  
FACE AREA - SQ. FT.  
NUMBER OF ROWS  
1
1
1
FINS PER INCH  
26  
28  
28  
EVAPORATOR  
BLOWER  
HORSEPOWER - NO. OF SPEEDS  
FULL LOAD AMPS  
1/2 - 5  
1.86  
1/2 - 5  
2.9  
3/4 - 5  
2.9  
MOTOR  
LOCKED ROTOR AMPS  
NA  
NA  
NA  
MOTOR SPEED TAP - COOLING  
RPM  
T2  
T2  
T2  
1050  
10 X 8  
1,200  
NA  
1050  
10 x 8  
1,300  
NA  
1050  
10 x 8  
1,600  
NA  
EVAPORATOR  
BLOWER  
DIAMETER X WIDTH (INCHES)  
HI EFFICIENCY COOLING CFM  
5 TON NOMINAL COOLING CFM  
FAN ONLY COOLING CFM  
MAX EXTERNAL STATIC PRESS ("w.c.)  
FACE AREA - SQ. FT.  
1,100  
0.5  
1,200  
0.5  
1,400  
0.5  
EVAPORATOR  
COIL  
5.2  
6.2  
6.2  
NUMBER OF ROWS  
3
4
4
FINS PER INCH  
14  
14  
14  
GENERAL  
FILTER SIZE - SQ. FT. *  
25 x 25 x 1  
3/4"  
(2) 20 x 20 x 1  
3/4"  
(2) 20 x 20 x 1  
3/4"  
INFORMATION  
DRAIN SIZE (INCHES)  
EXPANSION DEVICE  
ORIFICE (0.068) ORIFICE (0.072) ORIFICE (0.078)  
REFRIGERANT CHARGE R-410A (Oz.)  
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)  
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)  
SHIPPING WEIGHT LBS.  
OPERATING WEIGHT LBS.  
65  
3/4, 1, 1-1/4  
1/2  
94  
3/4, 1, 1-1/4  
1/2  
90  
3/4, 1, 1-1/4  
1/2  
370  
370  
400  
360  
360  
390  
(1)  
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
Calculated external filter size based on air velocity of 300 ft/min.  
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers  
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1424H41AB  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1424H41AB  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1430H41AB  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1430H41AB  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1436H41AB  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1436H41AB  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1442H41AB  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1442H41AB  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1448H41AB  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
COOLING PERFORMANCE DATA  
GPC1448H41AB  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
PERFORMANCE TEST  
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor  
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:  
If conditions vary from this, results will change as follows:  
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low  
and high side pressures and power will not change.  
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will  
occur in low and high side pressures and power.  
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.  
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.  
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.  
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5MM COILS  
WIRING DIAGRAMS  
GPC14[24-48]H41AB  
PU  
NOTE #3  
BK  
BK  
PU  
PU  
BL  
C
BK  
BL  
T2  
RD  
RD  
C
BL  
SEE NOTE 5  
T1  
BK  
BK  
/
/
RD  
GR  
YL  
GND  
BK  
RD  
RD  
YL  
PU  
LVJB  
YL  
WH  
RD  
C
BR  
H
E
R
M
O
S
WH  
YL  
RD  
GR  
Y
R
G
GR  
BL  
PLF  
W1  
WH  
YL  
H
RCCF  
BL  
BR  
BR  
BL  
W2  
C
GR  
A
PU  
++  
BR  
RD  
BK  
BK  
SA  
(IF USED) SEE NOTE 4  
RD  
BK  
CONTROL  
BOX  
YL  
PU BR  
YL  
GR  
WH  
S
C
R
C
G
N
CM  
COMP  
SEE NOTE 2  
EM  
L1  
L2  
COMPONENT LEGEND  
CONTACTOR  
FACTORY WIRING  
SUPPLY VOLTAGE  
208-240/1/60  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL HIGH  
VOLTAGE  
C
CM  
COMP  
EM  
GND  
LVJB  
PLF  
RCCF  
CONDENSER MOTOR  
COMPRESSOR  
EVAPORATOR MOTOR  
EQUIPMENT GROUND  
LOW VOLTAGE JUNCTION BOX  
FEMALE PLUG / CONNECTOR  
RUN CAPACITOR FOR^J  
COMPRESSOR AND FAN  
START ASSIST  
T2  
C
R
C
T1  
FIELD WIRING  
HIGH VOLTAGE  
LOW VOLTAGE  
C
COMP  
C
RCC  
F
S
H
F
S.A.  
CM  
SA  
TR  
NOTE #4  
TRANSFORMER  
WIRE CODE  
BK BLACK  
BL BLUE  
IF USED  
NOTE #2  
EM  
BR BROWN  
GR GREEN  
OR ORANGE  
PU PURPLE  
RD RED  
L
N
3
2
G
1
WH WHITE  
YL YELLOW  
208-240  
2
NOTE #4  
3
1
TR  
24V  
NOTES:  
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS  
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.  
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW  
LEADS FROM EM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE  
ENERGIZED, THE HIGHER SPEED SETTING IS USED.  
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES  
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.  
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED  
5. USE COPPER CONDUCTORS ONLY.  
C
EM  
SEE NOTE #2  
++ USE N.E.C. CLASS 2 WIRE  
4
5
6
SEE UNIT RATING PLATE FOR TYPE AND SIZE  
OF OVER CURRENT PROTECTION  
C
R
W2  
W1  
Y
G
C
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  

EdgeStar Ice Maker IP300P User Manual
Elation Professional Whiteboard Accessories SAT871 User Manual
Electro Voice Microphone RE90L User Manual
Extron electronic Stereo Receiver RGB 201 Rxi User Manual
Fujitsu Photo Scanner C150 E146 02EN User Manual
Furuno Radar Detector FR 1500 User Manual
Garmin Car Stereo System 695 User Manual
Garmin GPS Receiver 190 01117 02 User Manual
GE Freezer FUM5 FCM7 FCM15 FCM25 User Manual
Generac Switch 6378 User Manual