Protector™ Series
Owner’s Manual
For
Stationary Diesel Generators
Residential and Commercial
Model
RD015 -
RD020 -
RD030 -
RD048 -
RD050 -
15 kW 60 Hz
20 kW 60 Hz
30 kW 60 Hz
48 kW 60 Hz (Single Phase Only)
50 kW 60 Hz (Three Phase Only)
0066781 - 30 kW 60 Hz
NOT INTENDED FOR USE IN CRITICAL
LIFE SUPPORT APPLICATIONS.
*
*
ONLY QUALIFIED ELECTRICIANS OR
CONTRACTORS SHOULD ATTEMPT
INSTALLATION!
DEADLY EXHAUST FUMES! OUTDOOR
INSTALLATION ONLY!
*
This manual should remain with the unit.
This manual must be used in conjunction
with the appropriate installation manual.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Section 1 Safety
1.1 Introduction .......................................................................................................................... 1
1.2 Safety Information ................................................................................................................ 2
1.3 General Hazards ................................................................................................................... 2
1.4 Exhaust Hazards .................................................................................................................. 3
1.5 Electrical Hazards ................................................................................................................ 3
1.6 Fire Hazards .......................................................................................................................... 3
1.7 Explosion Hazards ............................................................................................................... 3
Section 2 Specifications
2.1 Emission Information .......................................................................................................... 5
2.1.1 Emissions Data Plate ....................................................................................................................5
2.2 Specifications ....................................................................................................................... 6
2.2.1 Engine ...........................................................................................................................................6
2.3 Engine Oil Recommendations ............................................................................................ 7
2.4 Coolant Water Treatment .................................................................................................... 7
2.5 Fuel Requirements ............................................................................................................... 7
2.5.1 Fuel Maintenance .........................................................................................................................8
2.5.2 Fuel Maintenance .........................................................................................................................8
2.6 Battery Requirements .......................................................................................................... 8
2.6.1 Battery Charger ............................................................................................................................8
2.7 Corrosion Protection ........................................................................................................... 8
2.8 Accessories .......................................................................................................................... 8
Section 3 Activation and Startup
3.1 Orientation .......................................................................................................................... 11
3.2 Remove Side Access Panels ............................................................................................ 11
3.3 Prime Fuel System ............................................................................................................. 12
3.4 Install Battery ..................................................................................................................... 12
3.5 Open Viewing Window ....................................................................................................... 13
3.6 Start and Run Engine ......................................................................................................... 13
3.7 Activate Unit ...................................................................................................................... 14
3.8 Operational Checks ........................................................................................................... 15
3.8.1 Self Test ......................................................................................................................................15
3.8.2 Check Manual Transfer Switch Operation ..................................................................................15
Owner’s Manual for Stationary Diesel Generators
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
3.8.3 Electrical Checks ........................................................................................................................16
3.8.4 Test Generator Under Load ........................................................................................................16
3.8.5 Check Automatic Operation ........................................................................................................17
3.9 Final Instructions ................................................................................................................17
Section 4 Operation
4.1 Control Panel ......................................................................................................................19
4.2 Auto/Manual/Off ..................................................................................................................19
4.3 Menu Navigation .................................................................................................................20
4.4 Alarm/Warning Conditions ................................................................................................22
4.5 Change Time and Date .......................................................................................................22
4.6 Programmable Timers ........................................................................................................22
4.6.1 Dealer Programmable ................................................................................................................22
4.6.1.1 Exercise Time ..................................................................................................................... 22
4.6.2 User Programmable ...................................................................................................................23
4.6.2.1 Start-Up Delay Timer .......................................................................................................... 23
4.6.2.2 Warm-Up Delay Timer ........................................................................................................ 23
4.7 USB Port for Firmware Updates ........................................................................................23
4.8 Battery Charger ..................................................................................................................23
4.9 Transfer Switch Automatic Operation ..............................................................................23
4.9.1 Automatic Sequence of Operation ..............................................................................................24
4.9.1.1 Utility Failure ....................................................................................................................... 24
4.9.1.2 Cranking.............................................................................................................................. 24
4.9.1.3 Load Transfer...................................................................................................................... 24
4.10 Transfer Switch Manual Operation .................................................................................24
4.10.1 Transfer to Generator Power ....................................................................................................25
4.10.2 Transfer Back to Utility Power ..................................................................................................25
Section 5 Maintenance
5.1 Component Locations ........................................................................................................27
5.2 Access Panels ....................................................................................................................29
5.2.1 Removal .....................................................................................................................................29
5.2.2 Installation ..................................................................................................................................29
5.3 Service Maintenance Intervals ..........................................................................................30
5.4 Remove From Service ........................................................................................................31
5.5 30 Hour Break-In .................................................................................................................31
iv
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
5.6 Daily Maintenance (If Running Continuously) ................................................................. 31
5.7 Schedule A Maintenance ................................................................................................... 32
5.7.1 Preliminary Instructions ..............................................................................................................32
5.7.2 Check Fuel Level and Fill ...........................................................................................................32
5.7.3 Drain Fuel Filter and Check Fuel Lines/Hoses ...........................................................................32
5.7.4 Check Coolant Level and Hoses ................................................................................................33
5.7.5 Check Radiator for Clogging .......................................................................................................34
5.7.6 Check Lubricating Oil Level ........................................................................................................34
5.7.7 Check Battery Condition/Fluid Level ...........................................................................................35
5.7.7.1 Check Condition and Clean ................................................................................................ 35
5.7.7.2 Check Fluid Level ............................................................................................................... 35
5.7.7.3 Check State of Charge........................................................................................................ 35
5.7.7.4 Battery Replacement .......................................................................................................... 35
5.7.8 Check and Adjust V-Belt .............................................................................................................37
5.7.8.1 Check.................................................................................................................................. 37
5.7.8.2 Adjust.................................................................................................................................. 38
5.7.9 Replace Air Filter Element ..........................................................................................................38
5.7.10 Drain Breather Canister and Replace Filter ..............................................................................38
5.7.11 Lubricate Governor Rod Linkage ..............................................................................................39
5.7.12 Final Instructions .......................................................................................................................39
5.8 Schedule B Maintenance ................................................................................................... 40
5.8.1 Replace Lubricating Oil and Oil Filter .........................................................................................40
5.8.2 Replace Fuel Filter ......................................................................................................................41
5.8.2.1 Prime Fuel System.............................................................................................................. 41
5.8.3 Drain/Flush Coolant System .......................................................................................................41
5.8.4 Final Instructions .........................................................................................................................42
5.9 Schedule C Maintenance ................................................................................................... 43
5.10 Return To Service ............................................................................................................ 43
Section 6 Troubleshooting
6.1 Engine Troubleshooting .................................................................................................... 45
6.2 Controller Troubleshooting ............................................................................................... 46
6.3 Removal From Service During Utility Outages ............................................................... 47
6.4 Storage ................................................................................................................................ 47
6.4.1 Prepare For Storage ...................................................................................................................47
6.4.2 Return From Storage ..................................................................................................................48
6.5 Attention After Submersion .............................................................................................. 49
6.6 Attention After Fuel Spillage ............................................................................................. 49
6.7 Contaminated Fuel Disposal ............................................................................................. 49
Owner’s Manual for Stationary Diesel Generators
v
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
WARNING
California Proposition 65. Engine exhaust and some of
its constituents are known to the state of California to
cause cancer, birth defects, and other reproductive
harm.
(000004)
WARNING
California Proposition 65. This product contains or
emits chemicals known to the state of California to
cause cancer, birth defects, and other reproductive
harm.
(000005)
vi
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1
Safety
1.1 — Introduction
Thank you for purchasing this stationary automatic standby generator set. Every effort was made to ensure that the
information in this manual was both accurate and complete at the time it was released. However, the manufacturer
reserves the right to change, alter or otherwise improve this product at any time without prior notice.
This generator is designed to automatically supply electrical power to operate critical loads during a utility power failure.
The unit is factory installed in an all-weather metal enclosure and is intended exclusively for outdoor installation
using only diesel fuel.
When properly sized, the generator is suitable for supplying typical residential/commercial loads, such as induction
motors (sump pumps, refrigerators, freezers, air conditioners, furnaces, etc.), electronic components (computers, mon-
itors, televisions, etc.), lighting, microwaves, and other residential and business loads.
READ THIS MANUAL THOROUGHLY: The operator is responsible for proper and safe use of this equipment. Read
and thoroughly understand the contents of this manual before attempting to use the equipment. If any portion of this
manual is not fully understood, contact the nearest Authorized Service Dealer for assistance.
SAVE THESE INSTRUCTIONS: The manufacturer suggests that this manual and the rules for safe operation be cop-
ied and posted near the generator installation site. Safety should be stressed to all operators and potential operators of
this equipment.
SAFETY: Throughout this manual, and on tags and decals affixed to the unit, DANGER, WARNING, CAUTION and
NOTE blocks are used to alert personnel to special instructions about a particular operation, function or service that
may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS
INJURY.
Indicates a hazardous situation or action which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTE: Notes contain additional information important to an operation or procedure.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of informa-
tion each indicates is as follows:
This symbol points out important Safety Information that, if not followed, could endanger personal safety and/or
property of others.
*
$
This symbol points out a potential Explosion Hazard.
This symbol points out a potential Fire Hazard.
!
+
This symbol points out a potential Electrical Shock Hazard.
These “Safety Alerts” cannot eliminate the hazards that they signal. Strict compliance with these special instructions,
plus common sense, are major accident prevention measures.
Owner’s Manual for Stationary Diesel Generators
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety
1.2 — Safety Information
Study these safety rules carefully before operating or servicing this equipment. Become familiar with this Owner’s Man-
ual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated
and maintained. Many accidents are caused by failing to follow simple rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this
manual, and on tags and decals affixed to the unit are not all-inclusive. If using a procedure, work method or operating
technique the manufacturer does not specifically recommend, ensure that it is safe for personnel. Also make sure the
procedure, work method or operating technique used does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its mainte-
nance or being careless can cause possible injury or death. Permit only responsible and capable per-
sons to install, operate and maintain this equipment.
*
Potentially lethal voltages are generated by these machines. Ensure steps are taken to make the
machine safe before attempting to work on the generator.
*
*
Parts of the generator are rotating and/or hot during operation. Exercise care near a running generator.
The installation of this generator must always comply with applicable codes, standards, laws and regu-
lations.
*
A running generator gives off DEADLY carbon monoxide, an odorless, colorless, poisonous gas.
Breathing carbon monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, head-
ache, vomiting, weakness, sleepiness, inability to think clearly, fainting, unconsciousness or even
death.
*
The control panel for this unit is intended to be operated by qualified service personnel only.
*
1.3 — General Hazards
• For safety reasons, this equipment should only be installed, serviced and repaired by a Service Dealer or other
competent, qualified electrician or installation technician who is familiar with applicable codes, standards, regula-
tions and product Installation Manual guidelines. The operator also must comply with all such codes, standards,
regulations and product Installation Manual guidelines.
• The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in
sufficient concentrations, can cause unconsciousness or even death. DO NOT alter or add to the exhaust system
or do anything that might render the system unsafe or in noncompliance with applicable codes and standards.
• Install a carbon monoxide alarm indoors, according to manufacturer’s instructions/recommendations.
• Adequate, unobstructed flow of cooling and ventilating air is critical for correct generator operation. Do not alter
the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation
of the generator. The generator MUST be installed and operated outdoors only.
• Keep hands, feet, clothing, etc. away from drive belts, fans, and other moving or hot parts. Never remove any
drive belt or fan guard while the unit is operating.
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or men-
tally fatigued.
• Inspect the generator regularly, and contact the nearest Dealer for parts needing repair or replacement.
• Before performing any maintenance on the generator, remove the control panel fuse and disconnect the Nega-
tive (-) battery cable to prevent accidental startup. When disconnecting battery cables always remove the NEGA-
TIVE (-) cable first. When reconnecting the cables, connect the POSITIVE (+) cable first.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may
result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
2
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety
1.4 — Exhaust Hazards
• Generator engine exhaust contains DEADLY carbon monoxide, an odorless, colorless, poisonous gas. Breathing
carbon monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting,
weakness, sleepiness, inability to think clearly, fainting, unconsciousness or even death. If any carbon monoxide
poisoning symptom is experienced, move into fresh air and immediately seek medical attention.
• This generator is designed for OUTDOOR installation ONLY. Never operate the generator inside any garage or
other enclosed space.
1.5 — Electrical Hazards
• All generators covered by this manual produce dangerous electrical voltages that can cause fatal electrical
shock. Utility power delivers extremely high and dangerous voltages to the transfer switch, as does the standby
generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc. while the unit is run-
ning. Ensure all appropriate covers, guards and barriers are in place, secured and/or locked before operating the
generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce potential
shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• The generator may crank and start at any time when utility power is lost. When this occurs, load circuits are
transferred to the STANDBY (generator) power source. Before working on the generator, always move the Main
Circuit Breaker switch on the control panel down to the OFF (Open) position, press the OFF key on the control
panel keypad, remove the 7.5 amp fuse, and disconnect the battery negative cable (black) from the battery neg-
ative (-) terminal.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not
possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use
a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is
unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock,
or may get caught in moving parts resulting in injury.
1.6 — Fire Hazards
• For fire safety, the generator must be installed and maintained properly. Installation MUST always comply with
applicable codes, standards, laws, regulations and product Installation Manual guidelines. Adhere strictly to
local, state, and national electrical and building codes. Comply with regulations of the Occupational Safety and
Health Administration (OSHA). Also, ensure that the generator is installed in accordance with the manufacturer’s
instructions and recommendations. Following proper installation, do nothing that might alter a safe installation
and render the unit in noncompliance with the aforementioned codes, standards, laws and regulations.
• Keep a fire extinguisher near the generator at all times. Extinguishers rated “ABC” by the National Fire Protection
Association are appropriate for use on the standby generator. Keep the extinguisher properly charged and be
familiar with its use. Consult the local fire department with any questions pertaining to fire extinguishers.
1.7 — Explosion Hazards
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible mate-
rials are left in the generator compartment, or on or near the generator as FIRE or EXPLOSION may result. Keep
the area surrounding the generator clean and free from debris.
If this generator is used to power electrical load circuits normally powered by a utility power source,
it is required by code to install a transfer switch. The transfer switch must effectively isolate the elec-
+
trical system from the utility distribution system when the generator is operating (NEC 702). Failure to
isolate an electrical system by such means will result in damage to the generator and also may result
in injury or death to utility power workers due to backfeed of electrical energy.
Owner’s Manual for Stationary Diesel Generators
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety
This page intentionally left blank.
4
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2
Specifications
2.1 — Emission Information
The U.S. Environmental Protection Agency (EPA) requires that the generator comply with exhaust emission standards.
The generator is certified to meet the applicable EPA emission levels, and is certified for use as a stationary engine for
standby power generation. Any other use may be a violation of federal and/or local laws. To ensure that the engine
complies with the applicable emission standards for the duration of the engine’s life, it is important to follow the mainte-
nance specifications in Section 5. This generator is certified to operate on Diesel Fuel No. 2 (KSM2610).
2.1.1— Emissions Data Plate
A data plate is riveted to the cylinder head cover to verify compliance with EPA emissions regulations.
Cylinder Head Cover
Figure 2-1. Emissions Data Plate (Sample)
Owner’s Manual for Stationary Diesel Generators
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
2.2 — Specifications
2.2.1— Engine
General
2.3L Engine
2.4L-49 Engine
3.4L Engine
Engine System
Type
4 cylinder, in-line, 4 cycle
Ultra Low Sulfur Diesel
5 Microns
4 cylinder, in-line, 4 cycle
Ultra Low Sulfur Diesel
5 Microns
4 cylinder, in-line, 4 cycle
Ultra Low Sulfur Diesel
10 Microns
Fuel Type
Fuel Filtering
3.46 in x 3.70 in
(88 mm x 94 mm)
3.54 in x 3.70 in
(90 mm x 94 mm)
3.86 in x 4.45 in
(98 mm x 113 mm)
Bore and Stroke
Displacement
139.5 cubic inches (2.286 liter)
1-3-4-2
146 cubic inches (2.392 liter)
1-3-4-2
208.3 cubic inches (3.41 liter)
1-3-4-2
Firing Order
Direction or Rotation
CCW - As Viewed From Flywheel
CCW - As Viewed From Flywheel
CCW - As Viewed From Flywheel
685 x 491 x 636 mm
(26.97 in x 19.33 in x 25.04 in)
677.1 x 497.8 x 721.3 mm
(26.66 in x 19.60 in x 28.40 in)
742 x 587 x 721 mm
(29.21 in x 23.11 in x 28.39 in)
Dimensions L x W x H
Dry Weight
441 lbs (200 kgs)
21.3 : 1
573 lbs (260 kgs)
21.3 : 1
551 lbs (250 kgs)
18.5 : 1
Compression Ratio
Cooling System
Water Pump
Drive
Pre-Lubed, Self-Sealing
Belt
Pre-Lubed, Self-Sealing
Belt
Pre-Lubed, Self-Sealing
Belt
Full Open Temperature:
185° F (85° C)
Full Open Temperature:
185° F (85° C)
Full Open Temperature:
185° F (85° C)
Thermostat
System Coolant Capacity
Coolant Flow Rate
Lubricating System
Oil Pump Type
2.8 gal (10.6 liter)
2.8 gal (10.6 liter)
2.8 gal (10.6 liter)
10 gal (38 liter)/min at 1800 RPM
10 gal (38 liter)/min at 1800 RPM
12.2 gal (46 liter)/min at 1800 RPM
Gear
Gear
Gear
Oil Filter Type
Full Flow Spin-On Canister
Not Applicable
6.87 qt. (6.5 liter)
15W-40
Full Flow Spin-On Canister
Installed
Full Flow Spin-On Canister
Installed
Oil Cooler
Crankcase Capacity
Lubricating Oil
6.8 qt. (6.4 liter)
15W-40
7.4 qt. (7.0 liter)
15W-40
Oil Fill Location
Filler Cap on Valve Cover and/or
Front Engine Cover
Filler Cap on Valve Cover and/or
Front Engine Cover
Filler Cap on Valve Cover and/or
Front Engine Cover
Oil Drain Location
Oil Pan, Bottom Side
Oil Pan, Bottom Side
Oil Pan, Front
Intake and Exhaust System
Intake Air System
Naturally Aspirated
Turbocharged
Turbocharged/Aftercooled
25 in. of Water (6.23 kPa)
Maximum Allowable
Intake Restriction
25 in. of Water (6.23 kPa)
25 in. of Water (6.23 kPa)
Maximum Allowable
Exhaust Back Pressure
23.6 in. of Water (5.88 kPa)
Closed Crankcase System
23.6 in. of Water (5.88 kPa)
Open Crankcase System
24 in of Water (5.98 kPa)
Open Crankcase System
Breather
Other Specifications
Operating Temperature Range
-20° F to 120° F (-29° C to 49° C)
-20° F to 120° F (-29° C to 49° C)
-20° F to 120° F (-29° C to 49° C)
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration........................................................................................3% for every 5 °C above 25 °C or 1.7% for every 5 °F above 77 °F
Altitude Deration (15, 30, 48 & 50 kW)...................................................... 1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ft
Altitude Deration (20 kW) ......................................................................... 1% for every 100 m above 305 m or 3% for every 1000 ft above 1000 ft
A complete specification sheet is included in the documentation provided with the unit at the time of purchase. For
additional copies, consult your local Authorized Service Dealer.
6
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
2.3 — Engine Oil Recommendations
To maintain the product warranty, use only genuine Generac replacement parts. Generac maintenance kits include
both the oil filter and air filter, and can be obtained through any Authorized Dealer.
All Generac maintenance kits meet minimum American Petroleum Institute (API) Service Class CD or better. Select the
appropriate viscosity oil grade according to the expected operating temperature. After break-in, synthetic oil also can
be used in the appropriate weight as standard. Once synthetic oil is used, it should be used for the life of the generator.
It is not recommended to go back to a mineral oil. Do not use special additives.
º C
º F
- 30 - 20 - 10
- 22 - 4 14
0
32
10
50
20
68
30
40
50
- 40
- 40
86 104 122
15W-40
All Seasons
10W-30
5W-30
Winter Conditions
Arctic Conditions
º C
º F
- 30 - 20 - 10
- 22 - 4 14
0
32
10
50
20
68
30
40
50
- 40
- 40
86 104 122
Figure 2-2. Lubricating Oil Recommendations
2.4 — Coolant Water Treatment
Use of improper coolants can damage the engine cooling system. Use demineralized water or distilled water for best
results. Hard water causes scale deposits, which reduces cooling efficiency and raises internal temperatures, possibly
leading to engine damage. Use an anti-corrosive to prevent rot in summer and anti-freeze to prevent freezing in winter.
Dilute the anti-freeze based on a theoretical temperature that is 9-18°F (5-10°C) below the lowest temperature
expected in the area. A ratio of 40-60% is most common range.
Freezing Point °F (°C)
Coolant (% Volume)
Water (% Volume)
-13 (-25)
40
-31 (-35)
50
-58 (-50)
60
60
50
40
NOTE: Use only Peak Fleet-Charge® 50/50 ethylene glycol type coolant (available from any authorized
dealer).
Do not use propylene glycol type coolant. Using the wrong coolant, mixing different types of coolant,
or even mixing different brands of the correct type of coolant, can produce unsatisfactory results, pos-
sibly leading to engine damage.
*
2.5 — Fuel Requirements
IMPORTANT! DO NOT use Home Heating Oil or Bio-Diesel Fuel.
Use No. 2D diesel fuel when temperatures are above freezing. When temperatures are below freezing, blend No.1D
diesel fuel and No. 2D diesel fuel together for a climate adjusted fuel ratio.
Starting October 1, 2010, diesel fuel must also meet the following requirements:
• Sulfur content of 15 parts per million (ppm) maximum.
• Minimum Cetane index of 40.
Owner’s Manual for Stationary Diesel Generators
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
NOTE: Low ambient temperatures as well as engine operation at high altitudes may require the use of fuels
with higher Cetane ratings.
Allow at least 5 percent of the tank capacity for fuel expansion. DO NOT OVERFILL!
2.5.1— Fuel Maintenance
Always treat diesel fuel for long term storage. Use the approved fuel additive and water abatement material. Test
stored fuel every 90 days and provide additional treatment if required. Periodically check and dry abatement material
as necessary.
2.5.2— Fuel Maintenance
Always treat diesel fuel for long term storage. Use the approved fuel additive and water abatement material. Test
stored fuel every 90 days and provide additional treatment if required. Periodically check and dry abatement material
as necessary.
2.6 — Battery Requirements
Group 27F, 12 Volt
2.3L Engine: For areas where temperatures regularly drop below 32° F (0° C).
NOTE: Battery dimensions (L x W x H) for Group 27F battery must not exceed 12-1/2" x 6-13/16" x 8-15/16"
(318 mm x 173 mm x 227 mm).
Group 31, 12 Volt
2.4L-49 Engine: For areas where temperatures regularly drop below 32° F (0° C).
NOTE: Battery dimensions (L x W x H) for Group 31 battery must not exceed 13" x 6-13/16" x 9-7/16"
(330 mm x 173 mm x 240 mm).
2.6.1— Battery Charger
The battery charger is integrated into the control panel module. It operates as a “Smart Charger” which ensures output
charging levels are safe and continuously optimized to promote maximum battery life.
2.7 — Corrosion Protection
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt
water/coastal areas.
2.8 — Accessories
The following product accessories are available. Contact a Dealer for additional information.
1. Scheduled Maintenance Kit (Part No. 006572-0; 15/20 kW)
2. Scheduled Maintenance Kit (Part No. 006571-0; 30 kW)
3. Scheduled Maintenance Kit (Part No. 006570-0; 50 kW)
8. Emergency Stop Switch (Part No. 006510-0)
9. Touch-Up Paint Kit (Part No. 005704-0)
10. Five Gallon Spill Box (Part No. 006502-0)
4. Cold Weather Kit (Part No. 006560-0: 15/20 kW; Part No.
006559-0: 30 kW; Part No. 006558-0: 50 kW)
11. Fuel Tank Risers (Part No. 006505-0: 15/20 kW; Part
No. 006506-0: 30/50 kW)
5. Vent Extension Support Kit (Part No. 006588-1)
6. Fuel Fill Drop Tube (Part No. 006507-0)
7. Lockable Fuel Fill Cap (Part No. 006512-0)
12. 90% Fuel Fill Level Alarm (Part No. 006504-0)
13. Spill Box Drain Back (Part No. 006511-0)
14. Stainless Steel Fuel Lines (Part No. 006513-0:15/20 kW;
Part No. 006517-0: 30 kW; Part No. 006516-0:
50 kW)
8
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
1.
2.
3.
5.
6.
4.
7.
8.
9.
10.
11.
12.
13.
14.
Figure 2-3. Product Accessories
Owner’s Manual for Stationary Diesel Generators
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
This page intentionally left blank.
10
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3
Activation and Startup
IMPORTANT NOTE: The unit fuel tank has been inspected by AHJ (authority having local jurisdiction) or fire
marshal and meets all requirements. Unit is fueled and the fuel is treated as per additive directions.
3.1 — Orientation
NOTE: The 3.4L engine is depicted in the artwork used in this manual. The location and appearance of some
components may vary between engine models.
The side of the enclosure with the viewing window is identified as the rear of the generator set. The right and left sides
are identified by standing at the rear and looking towards the front of the unit.
Fuel Priming
Pump
Viewing
Window
Battery
Figure 3-1. Enclosure (Rear Left View)
3.2 — Remove Side Access Panels
NOTE: Access panels are located at both the front and sides of the enclosure.
1. Insert key into latch and rotate counterclockwise 1/2 turn. See Figure 3-2.
2. Raise panel using thumb latch.
Key
Thumb Latch
Figure 3-2. Access Panel Key
Owner’s Manual for Stationary Diesel Generators
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Activation and Startup
3.3 — Prime Fuel System
1. See Figure 3-3. Loosen the air bleed screw and work priming pump until bubbles are observed. Place a shop rag
around the air bleed screw to catch any loss of fuel.
2. When all bubbles are purged and replaced by a solid stream of fuel, tighten the air bleed screw.
3. Check for leaks.
Priming
Pump
Air Bleed
Screw
Figure 3-3. Prime Fuel System
3.4 — Install Battery
CAUTION: Always connect the positive battery
$
cable first. If the positive cable should contact
ground with the negative cable installed, the result-
ing sparks may cause a battery explosion which
could result in serious injury.
2.4L/3.4L Models
NOTE: On 2.3L models, remove ten screws to release lou-
vered air intake panel on left side of enclosure.
1. Loosen two screws with nylon washers to release hold-
down clamp from battery tray.
2. Install battery onto tray.
3. Install two screws with nylon washers to secure hold-
Red Lead
From Starter
down clamp to battery tray.
4. Install battery positive cable (red) to battery positive (+)
terminal.
5. Install battery negative cable (black) to battery negative
(-) terminal.
NOTE: On 2.3L models, start ten screws to install louvered
air intake panel. Alternately tighten screws to 90 in-lbs (10
N-m) using a crosswise pattern.
Black Lead
To Frame
Battery
Figure 3-4. Battery Cable Connections
12
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Activation and Startup
3.5 — Open Viewing Window
1. Rotate viewing window upward to access control panel.
2. To hold viewing window in the open position, remove rod
from clip at back of window and insert into hole in frame.
See Figure 3-5.
Figure 3-5. Viewing Window
3.6 — Start and Run Engine
1. Pull up rubber flap covering fuse holder and verify installation of 7.5 amp fuse. See A of Figure 3-6.
2. Move the Main Circuit Breaker switch down to the OFF (Open) position. See B of Figure 3-6.
3. Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the
MANUAL mode. See C of Figure 3-6.
4. Allow the engine to run until it reaches normal operating temperature.
5. Press OFF on the control pad to stop the engine. A red LED illuminates to confirm that the system is in the OFF
mode.
7.5 Amp Fuse
and USB Port
A
B
LCD Screen
o
OFF
PUSH TO TRIP
Main Circuit Breaker
Control Pad
C
Figure 3-6. Generator Control Panel
Owner’s Manual for Stationary Diesel Generators
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Activation and Startup
3.7 — Activate Unit
Display Reads:
Generator Active is displayed on the
LCD screen when the unit is first
powered up. After displaying firmware
and hardware version codes, as well as
other system information, the Installation
Wizard is launched, and the Language
screen is displayed.
If the wrong language is selected, it may be changed
later using the Edit menu.
Up Arrow = (+)
Language
-
English
+
Use UP ARROW or DOWN ARROW to
scroll to desired language.
Press ENTER.
Down Arrow = (-)
Display Reads:
Press ENTER.
Press ESCAPE to abort the activation sequence. NOT
ACTIVATED is displayed and the generator will run in
manual mode only. Disconnect and reconnect the
negative battery cable to restart the activation routine.
If power is removed after a successful activation, no
data is lost, but the time and date must be updated.
Activate me (ENT) or
ESC to run in manual
888-9ACTIVATE (922-8482, US & CA
only) if activation passcode is not avail-
able.
Display Reads:
To Activate go to
If activation pass code is available, wait a
few seconds for the next display.
Display Reads:
Use UP ARROW or DOWN ARROW to
increment or decrement the digit to
correspond to the first number of the
pass code.
Press ESCAPE to return to preceding digits if a
correction becomes necessary.
SN 1234567890
If attempts to enter the activation code are
PASS CODE XXXXX
unsuccessful, check the number against the code
given on activategen.com. If it is correct, contact 1-888-
9ACTIVATE (922-8482, US & CA only).
Press ENTER.
Repeat step to enter remaining digits.
Display Reads:
Use UP ARROW or DOWN ARROW to
increment or decrement the hour. Press
ENTER.
Select Hour (0-23)
- 6 +
Use UP ARROW or DOWN ARROW to
increment or decrement the minute.
Press ENTER.
Use UP ARROW or DOWN ARROW to
select the month. Press ENTER.
Use UP ARROW or DOWN ARROW to
increment or decrement the date. Press
ENTER.
Use UP ARROW or DOWN ARROW to
increment or decrement the year. Press
ENTER.
14
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Activation and Startup
Display Reads:
Use UP ARROW or DOWN ARROW to
select either Yes or No.
Select YES to perform exercise at low speed. Select
NO to perform exercise at normal operating speed.
Quite Test Mode?
Yes No
Press ENTER.
Display Reads:
Set Exercise Time.
In the AUTO mode, the engine starts and runs once
each week at the time and day specified. During the
exercise cycle, the unit runs approximately 12 minutes
and then shuts down. Transfer of loads to the generator
does not occur unless utility power fails.
Use UP ARROW or DOWN ARROW to
increment or decrement the hour. Press
ENTER.
Select Hour (0-23)
- 1 +
Use UP ARROW or DOWN ARROW to
increment or decrement the minute.
Press ENTER.
Use UP ARROW or DOWN ARROW to
scroll to the day of the week. Press
ENTER.
3.8 — Operational Checks
The following procedures require special tools and skills. Contact a Generac Dealer or an authorized
service provider to perform these tasks.
+
3.8.1— Self Test
Upon power up, the controller goes through a system self test which checks for the presence of utility voltage on the
DC circuits. This is done to prevent damage if the installer mistakenly connects AC utility power sense wires into the
DC terminal block. If utility voltage is detected, the controller displays a warning message and locks out the generator,
thereby preventing damage to the controller. Remove power to the controller to clear this warning.
Utility voltage must be turned on and present at the N1 and N2 terminals inside the generator control panel for this test
to be performed and pass.
Before starting, complete the following:
1. Verify that the generator is OFF. A red LED on the control pad illuminates to confirm that the system is in the OFF
mode.
2. Verify that the Main Circuit Breaker switch on the generator control panel is in the OFF (Open) position.
3. Turn off all circuit breakers/electrical loads that will be powered by the generator.
4. Check the fuel level, coolant level, and engine lubricating oil level. See Subsections 5.7.2, 5.7.4, and 5.7.6,
respectively.
During initial start up only, the generator may exceed the normal number of start attempts and experience an “over
crank” fault. This is due to accumulated air in the fuel system during installation. Reset the control board and restart up
to two more times, if necessary. If unit fails to start, contact the local dealer for assistance.
3.8.2— Check Manual Transfer Switch Operation
Refer to the manufacturer’s instructions.
Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch
have been positively turned off. Failure to turn off all power voltage supplies will result in extremely
hazardous and possibly fatal electrical shock.
+
Owner’s Manual for Stationary Diesel Generators
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Activation and Startup
3.8.3— Electrical Checks
Complete electrical checks as follows:
1. Verify that the generator is OFF. A red LED on the control pad illuminates to confirm that the system is in the OFF
mode.
2. Verify that the Main Circuit Breaker switch on the generator control panel is in the OFF (Open) position.
3. Turn OFF all circuit breakers/electrical loads that will be powered by the generator.
4. Turn on the utility power supply to the transfer switch using the means provided (such as a utility main line circuit
breaker).
The transfer switch is now electrically “hot.” Contact with “hot” parts will result in extremely hazard-
ous and possibly fatal electrical shock.
+
5. Use an accurate AC voltmeter to check utility power source voltage across transfer switch terminals N1, N2, and
N3 (if three phase). Normal line-to-line voltage should be equivalent to rated unit voltage.
6. Check utility power source voltage across terminals N1, N2, and N3 (if three phase) and the transfer switch neu-
tral lug.
7. When certain that utility supply voltage is compatible with transfer switch and load circuit ratings, turn OFF the
utility power supply to the transfer switch.
8. Press MANUAL on the control pad to crank and start the engine.
9. Allow the engine to warm up for about five minutes. Move the Main Circuit Breaker switch on the generator con-
trol panel up to the ON (or closed) position.
Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts
will result in dangerous and possibly fatal electrical shock.
+
10. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal lugs E1, E2, and E3 (if
three phase).
11. Successively connect the AC voltmeter test leads across terminal lugs E1, E2, and E3 (if three phase) and neu-
tral; then across E2 and neutral. Voltage reading in each case should match utility voltage reading. If system is
three phase, verify that generator phase rotation matches utility phase rotation.
12. Move the Main Circuit Breaker switch on the generator control panel down to the OFF (Open) position.
13. Press OFF on the control pad to shut the engine down.
Do not proceed unless certain that generator AC voltage and frequency are correct and within the
stated limits.
+
3.8.4— Test Generator Under Load
To test the generator set with electrical loads applied, proceed as follows:
1. Verify that the generator is OFF. A red LED on the control pad illuminates to confirm that the system is in the OFF
mode.
2. Turn OFF all breakers/electrical loads that will be powered by the generator.
3. Turn OFF the utility power supply to the transfer switch, using the means provided (such as a utility main line cir-
cuit breaker).
Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch
have been positively turned off. Failure to turn off all power voltage supplies will result in extremely
hazardous and possibly fatal electrical shock.
+
4. Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator’s E1,
E2, and E3 (if three phase) terminals.
16
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Activation and Startup
5. Press MANUAL on the control pad. The engine will crank and start.
6. Allow the engine to warm up for a few minutes.
7. Move the Main Circuit Breaker switch on the generator control panel up to the ON (or closed) position. The
switch is now powered by the standby generator.
8. Turn ON the circuit breaker/electrical loads powered by the generator.
9. Connect a calibrated AC voltmeter and a frequency meter across terminal lugs E1, E2, and E3 (if three phase).
Voltage should be approximately unit rated voltage. Check with clamp on amp meter to ensure unit is not over-
loaded.
10. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications
of abnormal operation. Check for oil leaks, evidence of overheating, etc.
11. When testing under load is complete, turn OFF electrical loads.
12. Move the Main Circuit Breaker switch on the generator control panel up to the OFF (or open) position.
13. Allow the engine to run at no-load for 2-5 minutes.
14. Press OFF on the control pad to shut the engine down. A red LED illuminates to confirm that the system is in the
OFF mode.
3.8.5— Check Automatic Operation
To check the system for proper automatic operation, proceed as follows:
1. Verify that the generator is OFF. A red LED on the control pad illuminates to confirm that the system is in the OFF
mode.
2. Install front cover of the transfer switch.
3. Turn ON the utility power supply to the transfer switch, using the means provided (such as a utility main line cir-
cuit breaker).
NOTE: Transfer Switch will transfer back to utility position.
4. Move the Main Circuit Breaker switch on the generator control panel up to the ON (or closed) position.
5. Press AUTO on the control pad. The system is now ready for automatic operation.
6. Turn OFF the utility power supply to the transfer switch.
With the generator ready for automatic operation, the engine will crank and start when the utility source power is turned
OFF after a 10 second delay (factory default setting). After starting, the transfer switch connects load circuits to the
standby side. Let the system operate through its entire automatic sequence of operation.
With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer
switch. The system transfers back to the utility position and then runs through the cool down cycle and shuts down.
3.9 — Final Instructions
1. Use key to install side access panels.
2. Close viewing window.
NOTE: Obtain viewing window hasp, if not installed. See
Figure 3-7. With the retaining tab at the bottom, insert
square end of hasp into slot below viewing window.
Push on hasp until it snaps in place. Gently pull on hasp
to verify that it will not come free.
3. Install customer supplied padlock into hasp.
Figure 3-7. Install Viewing Window Hasp
Owner’s Manual for Stationary Diesel Generators
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Activation and Startup
This page intentionally left blank.
18
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4
Operation
4.1 — Control Panel
NOTE: The control panel is intended for use by qualified service personnel only.
The control panel is located behind the viewing window at the rear of the unit.
With the control pad set to AUTO, the engine may crank and start at any time without warning. Such
*
automatic starting occurs during the programmed exercise cycle or when utility power source voltage
drops below the configured level. To prevent possible injury that might occur during sudden starts,
always set the control pad to OFF and remove the 7.5 amp fuse before working on or around the gener-
ator or transfer switch. For added security, place a DO NOT OPERATE tag or placard on both the con-
trol panel and transfer switch.
7.5 Amp Fuse
and USB Port
LCD Screen
o
OFF
PUSH TO TRIP
AUTO
MANUAL
OFF
Main Circuit Breaker
ENTER
Control Pad
ESCAPE
Figure 4-1. Generator Control Panel
4.2 — Auto/Manual/Off
Feature
Description
Press to activate fully automatic operation. Green LED illuminates to confirm that system is in AUTO mode.
Transfer to standby power occurs if utility power fails.
AUTO
Functionality of exercise timer is enabled, if set.
Press to crank and start engine. Blue LED illuminates to confirm that system is in MANUAL mode.
Transfer to standby power occurs if utility power fails.
Functionality of exercise timer is disabled.
MANUAL
OFF
Press to shut down engine, if running. Red LED illuminates to confirm that system is in OFF mode.
Transfer to standby power does not occur if utility power fails.
Owner’s Manual for Stationary Diesel Generators
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
LCD Screen
UP ARROW
Green
LED
Blue
LED
Red
LED
ENTER
AUTO
MANUAL
OFF
DOWN ARROW
ESCAPE
Figure 4-2. Control Pad and LCD Screen
4.3 — Menu Navigation
See Figure 4-3.
Feature
Description
System Menus
The system returns to the Home screen if the control pad is not used for five minutes. The screen normally
displays a Status message, such as Ready to Run (Auto mode) or Switched to OFF (Off mode), and the
total Hours of Protection. If an active alarm/warning condition occurs, the associated Alarm/Warning mes-
sage is displayed. To clear the Alarm/Warning message, press OFF on the control pad followed by ENTER.
In the event of multiple Alarms/Warnings, the next message is then displayed. The highest priority alarm is
always displayed first.
HOME Screen
MAIN MENU
Enables the operator to navigate the software using UP ARROW, DOWN ARROW, ENTER and ESCAPE.
The Main Menu can be accessed from any sub menu by consecutively pressing ESCAPE. Each time
ESCAPE is pressed, the preceding menu is displayed. The Main Menu is reached when the System,
Date/Time, Battery, and Sub Menus are displayed.
Navigation
Used to abort a routine or back up to the preceding menu.
Used to make a selection or save an entry.
ESCAPE
ENTER
UP ARROW
DOWN ARROW
Used to move forward or backward from menu to menu or to scroll forward or backward (increment or dec-
rement) through available selections.
NOTE: Pressing the control pad illuminates the backlight for 30 seconds. The backlight also illuminates for 30 seconds when-
ever an active Alarm/Warning message is displayed.
20
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Switched to “OFF”
Hours of Protection
0 (H)
Home Screen
Up Arrow = (+)
Current Date/Time
02/14/13 07:40
ESC
Running Manual
Running-Utility Lost
Running-Remote Start
Running-2 Wire Start
Running - Exercise
Switched Off
ESC
ENTER
SYSTEM
DATE/TIME
Down Arrow = (-)
ENTER
Run Hours (H)
Battery Condition
ENTER
ESC
BATTERY
SUB MENUS
0.0
Stopped - Auto
Stopped - Alarm
“Good” “Inspect Battery” or “Check Battery”
Main Menu
ESC
ENTER
ENTER
ESC
ENTER
ENTER
MAINT:
Run Hrs
-
-
1 thru 50
1 thru 50
+
+
-
Run Log
+
“Run Log”
ESC
ENTER
HISTORY
MAINT
ESC
ESC
ENTER
ESC
“Alarm Log”
-
Alarm Log
+
Maint. Log
Scheduled
ENTER
ENTER
WARNING MESSAGE(S)
"Low Battery"
EDIT
DEALER
Access Requires Password
ENTER
ESC
ENTER
ESC
"Exercise Set Error"
"FIRMWARE ERROR-9"
“Schedule A Maint”
“Schedule B Maint”
“Schedule C Maint”
"Battery Problem"
"Charger Warning"
"Charger Missing AC"
"Overload Warning"
"Overload Cooldown"
"SEEPROM ABUSE"
"USB Warning"
ENTER
-
1 thru 50
+
"Schedule A Serviced"
"Schedule B Serviced"
"Schedule C Serviced"
"Maintenance Reset"
"Service Schedule A"
"Service Schedule B"
"Service Schedule C"
EXAMPLE:
“Inspect Battery 200 RnHr or 12/27/13”
“Service Schedule A, B or C”
Language
English
Language
Language
Espanol
Language
Francais
Language
+
+
-
+
-
+
ESC
ESC
“Next Maintenance 200 RnHr or 12/27/13”
Å
Æ
+
English
-
+
-
+
-
+
Portuguese
-
-
"Download Failure"
"Low Fuel (20%)"
"Stopping…"
ESC
ESC
ESC
ESC
ESC
ENTER
Current Date/Time
Select Hour (0-23)
Select Min (0-59)
Select Month (1-12)
Select Date (1-31)
Select Year (0-99)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ALARM MESSAGE(S)*
"High Engine Temp."
"Low Oil Pressure"
"Overcrank"
"Overspeed"
"RPM Sense Loss"
"Underspeed"
“Controller Fault"
"Ignition Fault Code"
"WIRING ERROR"
"Over Voltage"
"Under Voltage"
"Overload Remove Load"
"Canbus Error"
Å
9/12/13 12:22
Æ
-
14
+
-
0
+
-
2
+
-
13
+
-
13
+
ESC
ESC
ESC
ESC
Exercise Time
Quiet Test Mode ?
Select Hour (0-23)
Select Min (0-59)
Select Day
Wednesday
ENTER
ENTER
ENTER
ENTER
ESC
Å
14:00 Wednesday
Æ
-
YES or NO
+
-
14
+
-
0
+
-
+
*NOTE: Any key other than Enter will
force you out of Firmware Update
Select “Yes” then Press “Enter” to continue or Press
“ESCAPE” to escape out of updating.
Possible Message(s)
Corrupted File
Firmware Update
"Are You Sure?"
"- Yes or No +"
ENTER
ENTER
Firmware Update*
"Main V XXX To V XXX "
"GUI V XXX To XXX"
When the controller powers up the very first screen
displays the version number for a few seconds.
"Governor Fault"
"Missing Cam Pulse"
"Missing Crank Pulse"
"Ruptured Tank"
"Low Fuel (10%)"
"E-Stop"
Invalid File
ESC
Å
Insert USB
Æ
ESC
Å
Press Enter
Æ
File Not Found
Unsupported Device
Controller Fault
When update is complete remove Thumb Drive, then
follow the Install Wizard Menu.
Å
2-1500
Æ
Start up Delay (sec)
Warmup Time (sec)
ESC
ESC
Default: 10s
2.3L & 2.4L Units Only
"Fuse Problem"
-
5-30
+
*Note: E-Codes Not Shown
Pre Heat
Å
5-1500
Æ
Default: 5s
Default: 5s
ESC
Figure 4-3. Navigation Menu
Owner’s Manual for Stationary Diesel Generators
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.4 — Alarm/Warning Conditions
The owner/operator is alerted to Alarm and/or Warning conditions via the control panel LCD screen. All Alarm condi-
tions cause the generator to shut down. The Warning messages alert the operator to conditions that do not disable the
unit or require immediate correction.
The possible Alarm/Warning messages are listed below.
Alarm Messages
Warning Messages
• High Engine Temperature
• Low Oil Pressure
• Overcrank
• Low Battery
• Exercise Set Error
• FIRMWARE ERROR-9
• Schedule A Maintenance
• Schedule B Maintenance
• Schedule C Maintenance
• Battery Problem
• Overspeed
• RPM Sense Loss
• Underspeed
• Controller Fault
• Ignition Fault Code
• WIRING ERROR
• Over Voltage
• Charger Warning
• Charger Missing AC
• Overload Warning
• Overload Cooldown
• SEEPROM ABUSE
• USB Warning
• Under Voltage
• Overload Remove Load
• Canbus Error
• Governor Fault
• Missing Cam Pulse
• Missing Crank Pulse
• Ruptured Tank
• Low Fuel (10%)
• E-Stop
• Download Failure
• Low Fuel (20%)
• Stopping…
• Fuse Problem
NOTE: Unless properly trained to correct and clear Alarm/Warning conditions, contact an Authorized Dealer or trained
service technician.
4.5 — Change Time and Date
To change the time and date after activation, see the Navigation Menu in Figure 4-3. If power is lost (battery is discon-
nected/reconnected, control panel fuse is removed/installed, etc.), the display automatically prompts the user for the
Time and Date. All other information is retained in memory.
4.6 — Programmable Timers
4.6.1— Dealer Programmable
4.6.1.1—Exercise Time
A programmable exercise time is provided. In the AUTO mode, the engine starts and runs once each week at the time
and day specified. During the exercise cycle, the unit runs approximately 12 minutes and then shuts down. Transfer of
loads to the generator does not occur unless utility power fails.
NOTE: A Dealer password is required to change the Exercise time.
22
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.6.2— User Programmable
4.6.2.1—Start-Up Delay Timer
A programmable line interrupt delay (or Start-Up Delay) timer is provided. When utility voltage fails (falls below 60% of
nominal), the start-up delay timer is started. If the voltage rises above the Utility Volts Low threshold, the timer is reset.
If the utility voltage remains below the threshold during the duration of the timer, the unit cranks and starts.
NOTE: The factory default setting is five seconds, but is adjustable from 2 to 1500 seconds.
4.6.2.2—Warm-Up Delay Timer
A programmable Warm-Up Delay timer is provided. As soon as the generator starts, the warm-up timer is started.
When the warm-up timer expires, the control transfers load to the generator (through the transfer switch) if the utility
voltage is less than 80% of nominal. If utility voltage is greater than the threshold at expiration of the warm-up time, the
load is not transferred to the generator and a cool-down period begins. At the end of the cool-down period, the gener-
ator stops.
NOTE: The factory default setting is five seconds, but is adjustable from 5 to 1500 seconds.
4.7 — USB Port for Firmware Updates
A USB port is located beneath the rubber flap on the control panel, and is provided for firmware updates. Firmware
updates must be performed by an Authorized Service Dealer.
NOTE: The USB port is intended for use with a USB thumb drive only. The USB port is not intended for charging
devices such as phones or laptops. Do not connect any consumer electronics to the USB port.
4.8 — Battery Charger
NOTE: The battery charger is integrated into the control panel module.
The battery charger ensures:
• Output is continually optimized to promote maximum battery life.
• Charging levels are safe.
NOTE: A warning message is displayed on the LCD screen when the battery requires service.
4.9 — Transfer Switch Automatic Operation
In AUTO, the generator starts automatically when utility source voltage drops below the preset level. Once the unit
starts, loads are transferred to the standby power source.
To select automatic operation:
1. Verify that the transfer switch main contacts are set to the UTILITY position (loads connected to the utility power
source).
2. Verify that normal UTILITY power source voltage is available to transfer switch terminal lugs N1, N2 and N3 (if
three phase).
3. Move the Main Circuit Breaker switch on the control panel up to the ON (Closed) position.
4. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
Owner’s Manual for Stationary Diesel Generators
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.9.1— Automatic Sequence of Operation
4.9.1.1—Utility Failure
If the control pad is set to AUTO when the utility power fails (falls below 60% of nominal, dealer programmable), a ten
second Start-Up Delay timer is started (user programmable). If utility power is still absent when the time expires, the
engine cranks and starts.
Once started, a five second engine Warm-Up Delay timer starts (user programmable). When the time has elapsed, the
load is transferred to the generator. If utility power is restored (above 80% of nominal, dealer programmable) between
the time the engine is first started and expiration of the warm-up time, the controller completes the start cycle and then
runs through its normal cool-down cycle (while the load remains on the utility source throughout the episode).
4.9.1.2—Cranking
The cyclic cranking is controlled as follows:
Fifteen (15) seconds crank, seven (7) seconds rest, seven (7) seconds crank, seven (7) seconds rest; this sequence is
repeated for a total of six (6) crank cycles.
4.9.1.3—Load Transfer
With the generator running, the transfer of load is dependent upon the operating mode as follows:
• Starts and runs if utility power fails (falls below 60% of nominal) for five consecutive sec-
onds (adjustable).
• Starts a five second (adjustable) engine warm-up timer.
• Does not execute transfer if utility power returns before expiration of warm-up timer (but
finishes the warm-up and cool-down cycles).
• Transfers back to utility once utility power returns (above 80% of nominal) for fifteen
consecutive seconds.
• Only shuts down if OFF is pressed or an alarm shutdown occurs.
AUTO
• Once utility power returns, starts a cool-down cycle before it shuts down.
NOTE: Cool-down cycle is five minutes if turbocharger equipped, one minute if naturally
aspirated.
EXERCISE
• Only works in the AUTO mode.
• Does not exercise if generator is already running in AUTO.
• During exercise cycle, transfers only if utility power fails for ten consecutive seconds.
• Engine cranks and runs even if utility power is present, but does not transfer to generator.
• Transfers to generator if utility fails (falls below 60% of nominal) for ten consecutive sec-
MANUAL
onds.
• Transfers back to utility when utility returns for fifteen consecutive seconds. The engine
continues to run until the AUTO or OFF key is pressed.
4.10 — Transfer Switch Manual Operation
DO NOT attempt to activate the transfer switch manually until all power voltage supplies to the switch
have been completely turned off. Failure to turn off all power voltage supplies may result in extremely
hazardous and possibly fatal electrical shock.
Prior to automatic operation, manually exercise the transfer switch to verify that there is no binding or interference with
proper operation of the mechanism. Manual operation of the transfer switch is required if automatic operation fails.
24
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
IMPORTANT NOTE: Always use the applicable transfer switch owner's manual for actual manual transfer
switch operation instructions. The information presented here describes a typical V-style transfer switch,
which is not used for three phase applications.
4.10.1— Transfer to Generator Power
When utility power fails, manually transfer to standby power and start the generator as follows:
1. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.
2. Move the Main Circuit Breaker switch down to the OFF (Open) position.
3. Turn off the utility power supply to the transfer switch using the means provided (such as a utility main line circuit
breaker).
4. Use the manual transfer handle inside the transfer switch to move the main contacts to the STANDBY position
(loads connected to the standby power source).
5. Press MANUAL on the control pad. The engine cranks and starts.
6. Allow the engine to run for two minutes to bring it up to normal operating temperature.
7. Move the Main Circuit Breaker switch up to the ON (Closed) position.
Manual Transfer
Handle
Load Connected to Utility
Load Connected to Standby
Transfer Switch
Operating Lever
NOTE: V-style transfer switch not used for three phase applications.
Figure 4-4. Manual Transfer Switch Operation (Typical)
4.10.2— Transfer Back to Utility Power
When utility power is restored, manually transfer back to utility power and shut down the generator as follows:
NOTE: Verify that utility voltage has returned and is at the proper value.
1. Move the Main Circuit Breaker switch down to the OFF (Open) position.
2. Allow the engine to run for two minutes at no-load to bring it up to normal operating temperature.
3. Press OFF on the control pad to shut down the engine.
4. Verify that utility power supply to the transfer switch is turned off.
5. Use the manual transfer handle inside the transfer switch to move the main contacts to the UTILITY position
(loads connected to the utility power source).
6. Turn on the utility power supply to the transfer switch using the means provided.
7. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
Owner’s Manual for Stationary Diesel Generators
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
This page intentionally left blank.
26
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5
Maintenance
5.1 — Component Locations
The side of the enclosure with the viewing window is identified as the rear of the generator set. The right and left sides
are identified by standing at the rear and looking towards the front of the unit.
Viewing
Window
7.5 Amp Fuse
and USB Port
Main Circuit Breaker
Control Pad
and LCD Screen
Left Side
Right Side
Figure 5-1. Rear View
V-Belt
Air Filter
Oil Drain
Hose
Oil Filter Oil Level
Oil Fill Cap
Dipstick
Figure 5-2. Right Side View
Owner’s Manual for Stationary Diesel Generators
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Breather Canister
and Filter
Fuel Filter/Air Bleed
Fuel Return Hose
Fuel Supply Hose
Coolant
Drain Hose
Governor
Linkage
Coolant Overflow
Reservoir
Battery
Figure 5-3. Left Side View
Fuel Tank
Primary Vent
Emergency Vent
Primary Tank
Fuel Filler Spout
Emergency Vent
Secondary Tank
Fuel Level Gauge
Figure 5-4. Front View
NOTE: The 3.4L engine is depicted in the artwork used in this manual. The location and appearance of some
components may vary between engine models.
28
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.2 — Access Panels
Access panels are located at both the front and sides of the enclosure.
5.2.1— Removal
1. Insert key into latch and rotate counterclockwise 1/2 turn. See Figure 5-5.
2. Raise panel using thumb latch.
5.2.2— Installation
1. Lower panel into position using thumb latch.
2. Insert key into latch and rotate clockwise 1/2 turn.
Key
Thumb Latch
Figure 5-5. Access Panel Key
Owner’s Manual for Stationary Diesel Generators
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.3 — Service Maintenance Intervals
NOTE: Use only Genuine Generac parts to ensure warranty coverage.
All generator service must be performed by a qualified service person only.
*
It is important to perform all maintenance at the interval specified in the Service Maintenance Schedule. This
ensures safe and proper operation, as well as compliance with applicable emissions standards. Critical emissions
maintenance must be performed for the Emissions Warranty to remain valid. Service and repairs may be performed by
any qualified service technician or repair shop.
Observe the maintenance tasks and intervals shown in the table below.
Schedule A
Every
Schedule B
Every
Schedule C
Every
Daily If Running
Continuously
30 Hours
Engine Break In
Service
Year or
2 Years or
250 Hours
1000 Hours
125 Hours
Check Fuel Level and Fill
Drain Fuel Filter
Check Fuel Lines and Hoses
Check Coolant Level
Check Coolant Hoses
Check Radiator for Clogging
Check Lubricating Oil Level
Check Battery Condition/Fluid Level
Check/Adjust V-Belt Tension
Replace Air Filter Element
Drain Breather Canister and Replace Filter
Lubricate Governor Rod Linkage
Replace Lubricating Oil and Oil Filter
Replace Fuel Filter Element
Drain/Flush Coolant System
Inspect Fuel Tank
Check/Adjust Fuel Injection Valve
Pressure
Adjust Intake/Exhaust Valve Clearance
Check/Adjust Fuel Injection Pump Timing
Tighten Critical Fasteners
NOTE: If the unit reaches a Schedule A or Schedule B maintenance interval with 900 to 999 total hours, have
an authorized service provider perform the Schedule C maintenance tasks as well (and reset the A-B-C/Year
maintenance schedule counter).
30
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.4 — Remove From Service
To ensure safety, follow the steps below prior to inspection, maintenance or service.
IMPORTANT NOTE: If currently experiencing a utility outage, see Subsection 6.3 —Removal From Service
During Utility Outages for special instructions.
1. Open the viewing window. See Subsection 3.5 —Open Viewing Window.
2. Move the Main Circuit Breaker switch down to the OFF (Open) position. See A of Figure 5-6.
3. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode. See B of
Figure 5-6.
4. Remove T1 fuse from transfer switch.
5. Pull up rubber flap covering fuse holder and remove 7.5 amp fuse. See C of Figure 5-6.
6. Place a DO NOT OPERATE tag or placard on both the control panel and transfer switch.
7. If the unit has been running, wait five minutes for the engine to cool.
7.5 Amp Fuse
and USB Port
C
A
LCD Screen
o
OFF
PUSH TO TRIP
Main Circuit Breaker
Control Pad
B
Figure 5-6. Generator Control Panel
5.5 — 30 Hour Break-In
Perform the following task:
• Replace Lubricating Oil and Oil Filter
NOTE: See Subsection 5.8.1 under Schedule B Maintenance.
5.6 — Daily Maintenance (If Running Continuously)
Perform the following tasks:
• Check Fuel Level and Fill
• Drain Fuel Filter
• Check Coolant Hoses
• Check Radiator for Clogging
• Check Lubricating Oil Level
• Check Fuel Lines and Hoses
• Check Coolant Level
NOTE: See Subsection 5.7.1 through Subsection 5.7.6 under Schedule A Maintenance.
Owner’s Manual for Stationary Diesel Generators
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.7 — Schedule A Maintenance
NOTE: Perform Schedule A maintenance once each year or after 125 hours of service, whichever comes first.
5.7.1— Preliminary Instructions
1. See Subsection 5.4 —Remove From Service.
2. Remove access panels at the front and both sides of the enclosure. See Subsection 5.2 —Access Panels.
3. Remove battery negative cable (black) from battery negative (-) terminal.
NOTE: For general location of components, see Subsection 5.1 —Component Locations.
5.7.2— Check Fuel Level and Fill
1. Observe fuel gauge to note level of fuel in tank. See Figure 5-7.
2. Remove fuel fill cap from filler pipe.
3. Add fuel until needle on fuel gauge approaches the F(ull) mark.
4. Install fuel fill cap onto filler pipe.
Figure 5-7. Check Fuel Level Gauge and Fill
5.7.3— Drain Fuel Filter and Check Fuel Lines/Hoses
1. Slowly loosen water drain plug. See Figure 5-8.
2. Place a shop rag under the drain to catch any loss of water/fuel.
3. Work priming pump until water is drained and replaced by solid fuel. Tighten the water drain plug.
4. Check fuel filter and fuel lines/hoses for leaks. Tighten filter, fittings and hose clamps, if necessary.
5. Check hoses for nicks, cuts, tears or general deterioration. Replace as necessary.
32
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Priming
Pump
Fuel
Filter
Water
Drain Plug
Figure 5-8. Drain Water From Fuel Filter
5.7.4— Check Coolant Level and Hoses
Do not add coolant when the engine is hot. Steam and scalding fluids can cause severe burns.
*
NOTE: On 2.3L models, remove ten screws to release louvered air discharge panel on left side of enclosure.
1. Verify that the coolant level is between the HOT and COLD marks on the overflow reservoir. See Figure 5-9.
NOTE: Coolant expands when hot, so the level may be higher than the HOT mark. Do not add coolant higher
than the HOT mark.
2. If the coolant level is below the COLD mark, remove fill cap from overflow reservoir and add coolant. See Sub-
section 2.4 —Coolant Water Treatment.
3. Check coolant hoses for leaks. Tighten hose clamps, if necessary.
4. Check hoses for nicks, cuts, tears or general deterioration. Replace as necessary.
NOTE: On 2.3L models, install louvered air discharge panel. Alternately tighten ten screws to 90 in-lbs using a
crosswise pattern.
Drain Hose
Coolant
Reservoir
Figure 5-9. Coolant Overflow Reservoir and Drain Hose
Owner’s Manual for Stationary Diesel Generators
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.7.5— Check Radiator for Clogging
Direct beam of flashlight through openings in fan guard to inspect the radiator fins. Carefully look for debris, accumula-
tions of dirt or other deposits. If necessary, clean as follows:
1. On right side of enclosure, loosen two clamps at each end of turbocharger exhaust outlet pipe. Remove pipe,
clamps and rubber couplings from engine.
2. Remove oil drain hose from holding clamp.
3. Remove four screws with nylon washers to release fan guard from radiator shroud.
4. On left side of enclosure, loosen two clamps at each end of air intake pipe. Remove pipe, clamps and rubber
couplings from engine.
5. Remove coolant hoses from holding clamps.
6. Remove four screws with nylon washers to release fan guard from radiator shroud.
7. Carefully remove any debris from radiator fins. Use warm soapy water and a soft bristled brush to remove dirt
and other deposits, if necessary.
8. On left side of enclosure, install four screws with nylon washers to fasten fan guard to radiator shroud.
9. Install coolant hoses into holding clamps.
10. Install clamps and rubber couplings onto each end of air intake pipe. Install pipe to air heater and radiator shroud.
Tighten clamps.
11. On right side of enclosure, install four screws with nylon washers to fasten fan guard to radiator shroud.
12. Install oil drain hose into holding clamp.
13. Install clamps and rubber couplings onto each end of turbocharger exhaust outlet pipe. Install pipe to turbo-
charger outlet and radiator shroud. Tighten clamps.
5.7.6— Check Lubricating Oil Level
1. Remove dipstick and wipe with a clean cloth. See A of Figure 5-10.
2. Completely insert the dipstick and then remove it.
3. Verify that the oil level is at or near the H(igh) mark.
NOTE: Each hash mark or line below the H(igh) mark represents one liter. Add oil whenever the level is one
liter or more below the H(igh) mark.
4. If necessary, remove the oil fill cap and slowly add oil until the level is at the H(igh) mark. See B of Figure 5-10.
DO NOT OVERFILL.
5. Install dipstick and oil fill cap.
6. Check oil drain hose for leaks. Check hose for nicks, cuts, tears or general deterioration. Replace as necessary.
A
2.3 Liter
2.4 Liter
B
3.4 Liter
Figure 5-10. Oil Level Dipstick
34
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.7.7— Check Battery Condition/Fluid Level
5.7.7.1— Check Condition and Clean
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel on left side of enclosure.
1. Verify that top of battery is clean and dry. Dirt and electro-
lyte on top of the battery can cause battery to self-dis-
charge. Clean battery top with a solution of baking soda
(sodium bicarbonate) and water (5 teaspoons baking
soda per quart or liter of water). When solution stops bub-
bling, rinse off the battery with clean water.
2. Clean cable clamps and battery terminals using a wire
brush or sandpaper to remove any oxidation.
3. Inspect battery screws, clamps and cables for breakage,
loose connections and corrosion. Tighten and clean as
necessary.
4. Check the battery posts for melting or damage caused by
over tightening.
5. Inspect battery for discoloration, raised top or a warped
or distorted case, which might indicate that the battery
has been frozen, overheated or overcharged.
Red Lead
From Starter
6. Inspect the battery case for cracks or leaks.
7. Check the battery fluid level of unsealed batteries. See
Subsection 5.7.7.2—Check Fluid Level.
8. Check the battery state of charge. See Subsection
5.7.7.3—Check State of Charge.
Black Lead
To Frame
9. Replace battery if necessary. See Subsection 5.7.7.4—
Battery Replacement.
Battery
NOTE: On 2.3L models, start ten screws to install louvered
air intake panel. Alternately tighten screws to 90 in-lbs (10
N-m) using a crosswise pattern.
Figure 5-11. Battery Cable Connections
5.7.7.2— Check Fluid Level
Check the fluid level of unsealed batteries. If necessary, fill with
distilled water only. DO NOT use tap water.
5.7.7.3— Check State of Charge
Check the state of charge using a Digital Multimeter. Recharge and retest if state of charge is below manufacturer's
recommendations. Replace battery if necessary.
5.7.7.4— Battery Replacement
Removal
Always disconnect the negative battery cable first. If the positive cable should contact ground with the
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-
ous injury.
$
1. Remove battery negative cable (black) from battery negative (-) terminal.
2. Remove battery positive cable (red) from battery positive (+) terminal.
3. Install rubber protective cover over battery positive (+) terminal.
4. Loosen two screws with nylon washers to release battery hold-down clamp from battery tray.
5. Grasp battery strap next to battery positive (+) terminal, and lift battery.
6. When battery tilts sideways, remove from opening.
7. Remove rubber protective cover from battery positive (+) terminal.
Owner’s Manual for Stationary Diesel Generators
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Installation
Always connect the positive battery cable first. If the positive cable should contact ground with the
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-
ous injury.
$
1. Install rubber protective cover over battery posi-
tive (+) terminal. See A of Figure 5-12.
2. Grasp battery strap next to battery positive (+)
terminal, and lift battery.
3. When battery tilts sideways, insert into opening.
B
See B of Figure 5-12.
A
4. Return battery to the horizontal position while
sliding it onto battery tray.
5. Tighten two screws with nylon washers to
secure hold-down clamp to battery tray.
6. Remove rubber protective cover from battery
positive (+) terminal.
7. Install battery positive cable (red) to battery
positive (+) terminal.
8. Install battery negative cable (black) to battery
negative (-) terminal.
A = Protective Cover
B = Battery Strap
Figure 5-12. Install Battery (2.3L Models)
36
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.7.8— Check and Adjust V-Belt
5.7.8.1— Check
Check the V-belt deflection. Too little belt deflection accelerates belt wear, while too much deflection leaves the pulley
idle, overheats the engine, and no-load is generated. Adjust the belt deflection as follows:
1. On right side of enclosure, loosen two clamps at each end of turbocharger exhaust outlet pipe. Remove pipe,
clamps and rubber couplings from engine.
2. Remove oil drain hose from holding clamp.
3. Remove four screws with nylon washers to release fan guard from radiator shroud.
4. Perform visual inspection as follows:
• Inspect belt for cracks, fraying, excessive wear or other damage.
• Verify that belt is free of grease and oil. Replace belt if contaminated.
NOTE: Use a solution of soap and warm water to clean pulleys, if necessary. Avoid use of solvents, but if
used, always follow by a soap and water wash.
5. Using a suitable gauge, apply 22 Ibs (10 kgf) force midway between the crankshaft and alternator pulleys. See
Figure 5-13.
6. Take note of gauge reading. If belt deflection is not within specification, see Subsection 5.7.8.2—Adjust.
Belt Condition
New
Deflection
8-12 mm
Used
10-15 mm
7. Install four screws with nylon washers to fasten fan guard to radiator shroud.
8. Install oil drain hose into holding clamp.
9. Install clamps and rubber couplings onto each end of turbocharger exhaust outlet pipe. Install pipe to turbo-
charger outlet and radiator shroud. Tighten clamps.
Belt Deflection Gauge
Alternator Pulley
Crankshaft Pulley
Figure 5-13. Check V-Belt Deflection
Owner’s Manual for Stationary Diesel Generators
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.7.8.2— Adjust
1. Loosen tension adjuster screw (top). Loosen hex nut on pivot screw (bottom). Rotate alternator outward to
reduce belt deflection, rotate inward to increase belt deflection.
2. Tighten tension adjuster screw (top) to 17-22 ft-lbs (23-30 N-m). Tighten hex nut on pivot screw (bottom) to 33-43
ft-lbs (45-58 N-m).
3. Recheck belt deflection and repeat steps as necessary.
5.7.9— Replace Air Filter Element
1. Remove wing nut from threaded rod to release air cleaner cover. See Figure 5-14.
2. Remove the air filter element and discard.
3. Thoroughly clean air cleaner cover of any dust, dirt, or debris.
4. Place new air filter element against adapter flange.
NOTE: The air filter element is not directional.
5. Install air cleaner cover over threaded rod. Install wing nut and tighten until snug.
Element
Cover
Wing Nut
Figure 5-14. Air Cleaner Cover and Filter Element
5.7.10— Drain Breather Canister and Replace Filter
NOTE: This procedure only applies to turbocharged engines (2.4L/3.4L models).
1. Observe sight glass for level of oil in canister. See Figure 5-15.
2. When oil level approaches top of sight glass, remove plug at bottom of canister to drain oil.
3. Install drain plug at bottom of canister and tighten until snug.
4. Loosen clamp and remove filter element.
5. Install new filter element onto canister and tighten clamp.
6. Inspect hoses for nicks, cuts, tears or signs of deterioration. Replace as necessary.
7. Check for leakage. Tighten clamps if leaks are found.
NOTE: Dispose of used fuel filter at a proper collection center.
38
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Filter
Element
Clamp
Drain Plug
Sight
Glass
Figure 5-15. Drain Breather Canister and Replace Filter
5.7.11— Lubricate Governor Rod Linkage
1. Lubricate both ends of rod with a silicone spray. See Figure 5-16.
2. Verify that rod moves freely without binding.
Figure 5-16. Lubricate Governor Rod Ends
5.7.12— Final Instructions
1. Install battery negative cable (black) onto battery negative (-) terminal.
2. Install access panels at the front and both sides of the enclosure. See Subsection 5.2 —Access Panels.
3. See Subsection 5.10 —Return To Service.
Owner’s Manual for Stationary Diesel Generators
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.8 — Schedule B Maintenance
NOTE: Perform Schedule B maintenance every two years or after 250 hours of service, whichever comes first.
Before proceeding below, first perform all tasks listed under Schedule A Maintenance.
NOTE: For general location of components, see Subsection 5.1 —Component Locations.
5.8.1— Replace Lubricating Oil and Oil Filter
1. Remove oil drain hose from holding clamp. See Figure 5-17.
2. Use one wrench to hold hex on hose fitting (to prevent rotation), and use second wrench to remove drain plug.
3. Drain oil into a suitable container.
4. Install drain plug onto end of oil drain hose.
5. Install oil drain hose into holding clamp.
6. Rotate oil filter counterclockwise to remove from oil filter adapter.
7. Apply a light coat of clean engine oil to gasket of new oil filter.
8. Install oil filter by hand until gasket just contacts oil filter adapter. Tighten oil filter an additional 3/4 to one full turn.
9. Remove fill cap and fill engine with the recommended oil. See Subsection 2.3 —Engine Oil Recommendations.
10. Install fill cap.
11. Install battery negative cable (black) onto battery negative (-) terminal.
12. Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
13. Press MANUAL on the control pad to start the engine.
14. Allow the engine to run for one minute. Check for leaks while the engine is running.
15. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.
16. Wait a few minutes for the engine to cool and to allow oil to drain back to the oil pan.
17. Check oil level and add oil as necessary. DO NOT OVERFILL.
18. Install fill cap.
NOTE: Dispose of used oil and oil filter at a proper collection center.
Figure 5-17. Oil Fill Cap and Drain Hose
40
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.8.2— Replace Fuel Filter
1. Slowly loosen water drain plug. See Figure 5-18.
2. Rotate filter counterclockwise to remove from filter adapter.
3. Install new filter by hand until gasket just contacts filter adapter. Tighten filter an additional 3/4 to one full turn.
4. Tighten water drain plug.
NOTE: Dispose of used fuel filter at a proper collection center.
5. See Subsection 5.8.2.1—Prime Fuel System.
Priming
Pump
Fuel
Filter
Water
Drain Plug
Air Bleed
Screw
Figure 5-18. Prime Fuel System
5.8.2.1— Prime Fuel System
1. Place a shop rag near the air bleed screw to catch any loss of fuel.
2. Loosen the air bleed screw and work priming pump until bubbles are observed.
3. When all bubbles are purged and replaced by a solid stream of fuel, depress pump handle and tighten the air
bleed screw.
4. Check for leaks.
5.8.3— Drain/Flush Coolant System
NOTE: On 2.3L models, remove ten screws to release louvered air discharge panel on left side of enclosure.
1. Disconnect and empty coolant overflow reservoir.
2. Install and connect coolant overflow reservoir.
Verify that the engine is cool before removing the radiator cap. The cooling system is under pressure,
so steam and hot liquid can come out forcefully when the cap is loosened.
*
3. Slowly unscrew radiator cap.
4. Locate drain cock at bottom left side of radiator. Rotate hex fitting to open drain cock. See A of Figure 5-19.
Owner’s Manual for Stationary Diesel Generators
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5. Remove coolant drain hose from holding clamp.
6. Use wrench to hold hex on hose fitting (to prevent rotation), and use second wrench to remove drain plug.
7. Drain coolant into a suitable container.
8. Install plug at end of drain hose.
9. Install drain hose in holding clamp.
10. Rotate hex fitting to close radiator drain cock.
11. Obtain at least 2.8 gallons (10.6 liters) of coolant. See Subsection 2.4 —Coolant Water Treatment.
12. Rotate and remove plastic cover at top of enclosure and insert funnel into filler neck. See B of Figure 5-19.
13. Slowly pour coolant into filler neck until radiator is full.
14. Install radiator cap.
15. Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the
MANUAL mode.
16. Allow engine to run until the thermostat opens, as indicated by heating of the top radiator hose.
17. Check coolant hoses for leaks. Tighten clamps, if necessary.
18. Press OFF on the control pad to shut the engine down.
19. Wait five minutes for the engine to cool.
20. Repeat steps 4-20 to drain and refill cooling system.
21. Install plastic cover at top of enclosure and rotate until tight.
22. Check hoses for nicks, cuts, tears or general deterioration. Replace as necessary.
NOTE: On 2.3L models, start ten screws to install louvered air discharge panel. Alternately tighten screws to 90 in-lbs
using a crosswise pattern.
A
B
NOTE: Drain hose removed for
illustration purposes.
Figure 5-19. Drain/Fill Coolant System
5.8.4— Final Instructions
1. Install left and right side access panels. See Subsection 5.2 —Access Panels.
2. See Subsection 5.10 —Return To Service.
42
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.9 — Schedule C Maintenance
NOTE: Perform Schedule C maintenance after 1000 hours of service. Before proceeding below, first perform all
tasks listed under Schedule A Maintenance and Schedule B Maintenance.
The following procedures require special tools and skills. Contact a Generac Dealer or an authorized
service provider to perform these tasks.
*
• Inspect Fuel Tank
• Check/Adjust Fuel Injection Valve Pressure
• Check/Adjust Fuel Injection Pump Timing
• Adjust Intake/Exhaust Valve Clearance
• Tighten Critical Fasteners
NOTE: Reset the A-B-C/Year time maintenance schedule counter using the Dealer Sub Menu (password
required).
5.10 — Return To Service
After inspection, maintenance or service of the generator, return the unit to service following the steps below.
1. Pull up rubber flap covering fuse holder and install 7.5 amp fuse. See A of Figure 5-20.
2. Install T1 fuse in transfer switch.
3. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode. See B
of Figure 5-20.
4. Move the Main Circuit Breaker switch up to the ON (Closed) position. See C of Figure 5-20.
5. Close the viewing window.
6. Remove the DO NOT OPERATE tag or placard from both the control panel and transfer switch.
7. Reset the time and date.
7.5 Amp Fuse Holder
A
C
LCD Screen
o
OFF
PUSH TO TRIP
Main Circuit Breaker
Control Pad
B
Figure 5-20. Generator Control Panel
Owner’s Manual for Stationary Diesel Generators
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
This page intentionally left blank.
44
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6
Troubleshooting
6.1 — Engine Troubleshooting
Problem
Cause
Correction
Replace 7.5 amp fuse in generator con-
trol panel. Correct short circuit condi-
tion if fuse blows again.
Fuse blown.
Loose, corroded or defective bat-
tery cables.
Tighten, clean or replace as neces-
sary.*
The engine will not crank.
Tighten, clean or replace as neces-
sary.*
Defective starter contact.
Defective starter motor.
Tighten, clean or replace as neces-
sary.*
Dead Battery.
Charge or replace battery.
Out of fuel.
Replenish fuel. Turn on fuel valve.
*
Defective fuel solenoid.
The engine cranks but will not
start.
Replace F1 5 amp fuse if fuse blows
again.*
Open F1 5 amp fuse.
Defective fuel system.
No fuel to pump.
*
Prime fuel system.*
The engine starts hard and runs
rough.
Air cleaner plugged or damaged.
Check/replace air cleaner.
Defective keypad.
*
*
The generator is set to OFF, but
the engine continues to run.
Defective control board.
Main line circuit breaker is in the
OFF (OPEN) position.
Reset circuit breaker to ON (CLOSED)
position.
There is no AC output from the
generator.
Generator internal failure.
Defective transfer switch coil.
Defective transfer relay.
*
*
*
There is no transfer to standby
after utility source failure.
Transfer relay circuit open.
Defective control logic board.
Engine over filled with oil.
Engine breather defective.
Incorrect oil type or viscosity.
Damaged gasket, seal or hose.
*
*
Adjust oil to correct level.
*
Unit consumes large amounts of
oil.
See Engine Oil Recommendations.
Check for oil leaks.
* Contact an Authorized Service Dealer for assistance.
Owner’s Manual for Stationary Diesel Generators
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
6.2 — Controller Troubleshooting
Active Alarm
Problem
Solution
NOT ACTIVATED
Unit will not start in AUTO with utility loss.
Refer to activation section in Owner’s Manual.
Check MLCB. Contact servicing dealer if MLCB is in the ON
position.
NONE
NONE
Unit running in AUTO but no power in house.
Unit will not start in AUTO with utility loss.
Check screen for start delay countdown. If the start up delay is
greater than expected, contact servicing dealer to adjust from 2
to 1500 seconds.
HIGH
TEMPERATURE
Check ventilation around the intake, exhaust and rear of gener-
ator. Contact serving dealer if no obstruction is found.
Unit shuts down during operation.
Unit shuts down during operation.
Clear alarm and remove household loads from the generator.
Put back in AUTO and restart.
OVERLOAD
Clear alarm and remove household loads from the generator.
Put back in AUTO and restart. If problem returns, contact servic-
ing dealer to investigate possible fuel issue.
Unit was running and shuts down, attempts to
restart.
RPM SENSE LOSS
LOW OIL
PRESSURE
Check oil level. Add oil per Owner’s Manual. Contact servicing
dealer if oil level is correct.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Clear alarm. From the MAIN menu on the control panel, navi-
gate to the BATTERY MENU. Contact servicing dealer if battery
is GOOD. Replace battery If CHECK BATTERY is displayed.
RPM SENSE LOSS
OVERCRANK
Clear alarm. Attempt to start the unit in MANUAL. If it does not
start or starts and runs rough, contact servicing dealer.
Check ATO 7.5 amp fuse. Replace with same type fuse if bad.
Contact servicing dealer if fuse is good.
FUSE PROBLEM
OVERSPEED
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Contact servicing dealer.
Contact servicing dealer.
UNDER
VOLTAGE
UNDERSPEED
MISWIRE
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Contact servicing dealer.
Contact servicing dealer.
Contact servicing dealer.
OVERVOLTAGE
Clear alarm. From the MAIN menu on the control panel, navi-
gate to the BATTERY MENU. Contact servicing dealer if battery
is GOOD. Replace battery If CHECK BATTERY is displayed.
LOW BATTERY
Warning active.
BATTERY PROBLEM
CHARGER WARNING
Warning active.
Warning active.
Contact servicing dealer.
Contact servicing dealer
Perform SERVICE SCHEDULE A maintenance; press ENTER
to clear.
SERVICE SCHEDULE A
SERVICE SCHEDULE B
SERVICE SCHEDULE C
Warning active.
Warning active.
Warning active.
Perform SERVICE SCHEDULE B maintenance; press ENTER
to clear.
Perform SERVICE SCHEDULE C maintenance; press ENTER
to clear.
46
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
6.3 — Removal From Service During Utility Outages
If, during prolonged utility outages, the user wishes to remove the unit from service to conserve fuel, reduce run hours,
or to perform maintenance tasks, then complete the steps listed below.
IMPORTANT NOTE: Failure to abide by this procedure can result in equipment damage.
To remove the generator from service while running in AUTO and online, proceed as follows:
1. Turn the main utility disconnect to OFF (Open).
2. Open the viewing window. See Subsection 3.5 —Open Viewing Window.
3. Move the Main Circuit Breaker switch down to the OFF (Open) position.
4. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.
NOTE: If inspection and/or maintenance tasks are to be performed, complete the additional steps listed below.
5. Remove T1 fuse from transfer switch.
6. Pull up rubber flap covering fuse holder and remove 7.5 amp fuse.
7. Remove battery negative cable (black) from battery negative (-) terminal.
8. Place a DO NOT OPERATE tag or placard on both the control panel and transfer switch.
To return the generator to service, proceed as follows:
NOTE: If inspection and/or maintenance tasks were performed, start with step 1. If the unit was just shut down
to conserve fuel or to reduce run hours, start at step 5.
1. Install battery negative cable (black) onto battery negative (-) terminal.
2. Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
3. Install T1 fuse in transfer switch.
4. Remove the DO NOT OPERATE tag or placard from both the control panel and transfer switch.
5. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode. Allow
the generator to start and run for a few minutes.
6. Move the Main Circuit Breaker switch up to the ON (Closed) position.
7. Turn the main utility disconnect to ON (Closed).
8. Close the viewing window.
6.4 — Storage
6.4.1— Prepare For Storage
If the generator cannot be exercised every seven days and will be out of service longer than 90 days, prepare for stor-
age as follows:
1. Open the viewing window. See Subsection 3.5 —Open Viewing Window.
2. Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the
MANUAL mode.
3. Allow the engine to run until it reaches normal operating temperature.
4. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.
5. Move the Main Circuit Breaker switch on the control panel down to the OFF (Open) position.
6. Pull up rubber flap covering fuse holder and remove 7.5 amp fuse.
7. Turn off utility power to the transfer switch.
8. Place a DO NOT OPERATE tag or placard on both the control panel and transfer switch.
9. Wait five minutes for the engine to cool.
Owner’s Manual for Stationary Diesel Generators
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
10. Remove right side access panel. See Subsection 5.2 —Access Panels.
11. Remove oil drain hose from holding clamp.
12. Use one wrench to hold hex on hose fitting (to prevent rotation), and use second wrench to remove drain plug.
13. Drain oil into a suitable container.
14. Install drain plug onto end of oil drain hose.
15. Install oil drain hose into holding clamp.
16. Rotate oil filter counterclockwise to remove from oil filter adapter.
17. Apply a light coat of clean engine oil to gasket of new oil filter.
18. Install oil filter by hand until gasket just contacts oil filter adapter. Tighten oil filter an additional 3/4 to one full turn.
19. Remove oil fill cap and fill engine with the recommended oil. See Subsection 2.3 —Engine Oil Recommenda-
tions.
20. Install oil fill cap.
21. Install right side access panel. See Subsection 5.2 —Access Panels.
NOTE: Dispose of used oil and oil filter at a proper collection center.
22. Remove left side access panel. See Subsection 5.2 —Access Panels.
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel.
Always disconnect the negative battery cable first. If the positive cable should contact ground with the
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-
ous injury.
$
23. Remove battery negative cable (black) from battery negative (-) terminal.
24. Remove battery positive cable (red) from battery positive (+) terminal.
25. Remove two screws to release battery hold-down clamp from platform.
26. Remove battery and store on a wooden board in a cool, dry room. Do not store the battery on a concrete or
earthen floor.
27. Install left side access panel. See Subsection 5.2 —Access Panels.
NOTE: On 2.3L models, start ten screws to install louvered air intake panel. Alternately tighten screws to 90 in-
lbs.
28. Thoroughly clean and wipe down the generator. See Subsection 2.7 —Corrosion Protection.
6.4.2— Return From Storage
To return the unit to service after storage, proceed as follows:
1. Thoroughly clean and wipe down the generator. See Subsection 2.7 —Corrosion Protection.
2. Remove left side access panel. See Subsection 5.2 —Access Panels.
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel.
3. Install battery onto tray oriented with the negative (-) post toward the front of the enclosure.
4. Install two screws with nylon washers to secure battery hold-down clamp to tray.
5. Check battery. See Subsection 5.7.7—Check Battery Condition/Fluid Level..
Always connect the positive battery cable first. If the positive cable should contact ground with the
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-
ous injury.
$
6. Install battery positive cable (red) onto battery positive (+) terminal.
7. Install battery negative cable (black) onto battery negative (-) terminal.
48
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
8. Install left side access panel. See Subsection 5.2 —Access Panels.
NOTE: On 2.3L models, start ten screws to install louvered air intake panel. Alternately tighten screws to 90 in-
lbs.
9. Remove right side access panel. See Subsection 5.2 —Access Panels.
10. Check oil level and add oil as necessary. DO NOT OVERFILL.
11. Open the viewing window. See Subsection 3.5 —Open Viewing Window.
12. Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
13. Move the Main Circuit Breaker switch up to the ON (Closed) position.
14. Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the
MANUAL mode.
15. Allow the engine to run until it is reaches normal operating temperature. Check for leaks while the engine is run-
ning.
16. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.
17. Install right side access panel. See Subsection 5.2 —Access Panels.
18. Turn on utility power to the transfer switch.
19. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
20. Reset the time and date.
21. Close the viewing window.
6.5 — Attention After Submersion
Do NOT start and operate the generator if it has been submerged in water. Have a Dealer thoroughly clean, dry, and
inspect the generator following any submersion. If the structure (home) has been flooded, it should be inspected by a
certified electrician to ensure there won’t be any electrical problems during generator operation or when utility power is
returned.
6.6 — Attention After Fuel Spillage
Contact reputable local company that performs clean up and disposal services.
6.7 — Contaminated Fuel Disposal
Contact reputable local company that performs purging, burnishing and disposal services.
Owner’s Manual for Stationary Diesel Generators
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
This page intentionally left blank.
50
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
Owner’s Manual for Stationary Diesel Generators
51
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
52
Owner’s Manual for Stationary Diesel Generators
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Part No. 0K3220 Rev. J 05/07/2015 Printed in USA
© Generac Power Systems, Inc. All rights reserved
Specifications are subject to change without notice.
No reproduction allowed in any form without prior written
consent from Generac Power Systems, Inc.
Generac Power Systems, Inc.
S45 W29290 Hwy. 59
Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
generac.com
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Euro Pro Food Processor FP105B User Manual
Extron electronic Network Card RGB HDMI 300 User Manual
Fisher Projector PLC XU47 User Manual
Fostex Computer Monitor PM04 User Manual
Fujitsu Scanner 84 User Manual
Fundex Games Games Phase 10 Twist User Manual
GE Computer Monitor EPM 9650 9800 User Manual
Gemini Industries Switch UX 160 User Manual
GE Monogram Ventilation Hood ZV48RSFSS User Manual
Goodman Mfg Furnace GMS8 33 3 8 GAS FURNACE UNITS User Manual