®
Protector™
Series
Standby Generators
Diesel Engine
1 of 6
Not for sale outside of US/CA
INCLUDES:
Standby Power Rating
• Two Line LCD Multilingual Digital
Evolution™ Controller (English/Spanish/
French/Portuguese) with external viewing
window for easy indication of generator
status and breaker position.
Model RD015 (Gray) - 15 kW 60 Hz
Model RD020 (Gray) - 20 kW 60 Hz
Model RD030 (Gray) - 30 kW 60 Hz
Model RD048 (Gray) - 48 kW 60 Hz (single phase only)
Model RD050 (Gray) - 50 kW 60 Hz (three phase only)
• Isochronous Electronic Governor
• Sound Attenuated Enclosure
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• ±1% Voltage Regulation
• Integrated Base Tank Provides 24 Hour
Run Time Minimum at 1/2 Load
• 5 Year Limited Warranty
• UL/CUL2200/UL 142 Listed
• Meets code requirements for External
Vent and Fill
Meets EPA Emission Regulations
CA/MA Emissions Compliant
FEATURES
¡
INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it
doesn’t stop there. Total commitment to component testing, reliability
testing, environmental testing, destruction and life testing, plus testing
to applicable CSA, NEMA, EGSA, and other standards, allows you to
choose GENERAC POWER SYSTEMS with the confidence that these
systems will provide superior performance.
¡
SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
electronically torque-matching the surge loads to the engine. Digital
voltage regulation at ±1%.
¡
¡
SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
¡
TEST CRITERIA:
PROTOTYPE TESTED
SYSTEM TORSIONAL TESTED
NEMA MG1-22 EVALUATION
MOTOR STARTING ABILITY
GENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this
confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
Download from Www.Somanuals.com. All Manuals Search And Download.
®
15 • 20 • 30 • 48 • 50 kW
application & engineering data
ENGINE SPECIFICATIONS: 15 & 20 kW
ENGINE LUBRICATION SYSTEM
Make
Generac
Oil Pump Type
Gear
Model
In-line
Oil Filter Type
Full flow spin-on canister
Cylinders
4
6.87/6.5 - 15 & 20 kW
6.8/6.4 - 30 kW
3 of 6
Crankcase Capacity (quarts/liters)
Displacement (Liters)
Bore (in./mm)
Stroke (in./mm)
Compression Ratio
Intake Air System
Cylinder Head Type
Piston Type
2.28
7.4/7 - 48 & 50 kW
3.46/88
3.70/94
ENGINE COOLING SYSTEM
21.3:1
Pressurized radiator - 15 & 20 kW
Closed recovery - 30, 48 & 50 kW
Type
Naturally Aspirated
Cast Iron OHV
Aluminum
Emergency Stationary
Water Pump
Pre-lubed, self-seating
1800 - 15 & 20 kW
2061 - 30 kW
Fan Speed (rpm)
EPA Emissions Compliance
2029 - 48 & 50 kW
ENGINE SPECIFICATIONS: 30 kW
Make
18.11/460 (15 & 20 kW) or
22/559 (30, 48 & 50 kW)
Fan Diameter (in/mm)
Fan Mode
Generac
Model
In-line
Pusher
Cylinders
4
FUEL SYSTEM
Fuel Type
Displacement (Liters)
Bore (in/mm)
2.4
Ultra Low Sulfur Diesel Fuel
Mechanical Engine Driven Gear
Mechanical
3.54/90
Fuel Pump Type
Stroke (in/mm)
3.70/94
Injector Type
Compression Ratio
Intake Air System
Cylinder Head Type
Piston Type
21.3:1
Fuel Supply Line (mm/in)
Fuel Return Line (mm/in)
Fuel Specification
Fuel Filtering (microns)
7.94/0.31 (ID)
Turbocharged
Cast Iron OHV
Aluminum
Emergency Stationary
7.94/0.31(ID)
ASTM
5 (15, 20 & 30 kW)
or 10 (48 & 50 kW)
EPA Emissions Compliance
ENGINE SPECIFICATIONS: 48/50 kW
TANK SPECIFICATIONS
Make
Generac
Total Size (gallons/liters)
34/128.7 - 15 & 20 kW
Model
In-Line
62/234.7 - 30, 48 & 50 kW
Cylinders
4
Usable Size (gallons/liters)
Run Time @ 1/2 Load (hrs)
32/121.1 - 15 & 20 kW
Displacement (Liters)
Bore in/mm
3.4
57/215.8 - 30, 48 & 50 kW
3.86/98
38 - 15 kW
28.6 - 20 kW
Stroke in/mm
Compression Ratio
Intake Air System
Cylinder Head Type
Piston Type
4.45/113
36.7 - 30 kW
18.5:1
24 - 48 & 50 kW
Turbocharged/Aftercooled
Cast Iron OHV
Aluminum
Emergency Stationary
Listings
UL142
EPA Emissions Compliance
Download from Www.Somanuals.com. All Manuals Search And Download.
®
15 • 20 • 30 • 48 • 50 kW
operating data
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW (Standby)
Amp (Standby)
CB Size
70
120/240 V, 1Ø, 1.0 pf
15
15
15
20
20
20
30
30
30
30
48
50
50
50
62
52
RD015
RD020
120/208 V, 3Ø, 0.8 pf
120/240 V, 3Ø, 0.8 pf
120/240 V, 1Ø, 1.0 pf
120/208 V, 3Ø, 0.8 pf
120/240 V, 3Ø, 0.8 pf
120/240 V, 1Ø, 1.0 pf
120/208 V, 3Ø, 0.8 pf
120/240 V, 3Ø, 0.8 pf
277/480 V, 3Ø, 0.8 pf
120/240 V, 1Ø, 1.0 pf
120/208 V, 3Ø, 0.8 pf
120/240 V, 3Ø, 0.8 pf
277/480 V, 3Ø, 0.8 pf
60
45
50
83
100
80
4 of 6
69
60
70
125
104
90
150
125
100
50
RD030
45
200
173
150
75
200
200
175
90
RD048/RD050
SURGE CAPACITY IN AMPS
ENGINE FUEL CONSUMPTION
Voltage Dip @ < .4 pf
gal/hr
0.51
0.79
1.14
1.48
0.67
1.05
1.52
1.98
0.92
1.45
1.96
2.74
1.35
2.15
3.06
3.98
L/hr
1.93
2.99
4.31
5.58
2.6
15%
53
37
32
87
59
51
66
59
51
26
69
90
78
36
30%
129
90
25% of rated load
120/240 V, 1Ø
50% of rated load
RD015
RD015
RD020
120/208 V, 3Ø
120/240 V, 3Ø
120/240 V, 1Ø
120/208 V, 3Ø
120/240 V, 3Ø
120/240 V, 1Ø
120/208 V, 3Ø
120/240 V, 3Ø
277/480 V, 3Ø
120/240 V, 1Ø
120/208 V, 3Ø
120/240 V, 3Ø
277/480 V, 3Ø
75% of rated load
78
100% of rated load
25% of rated load
211
143
124
168
144
125
64
50% of rated load
RD020
3.97
5.32
7.48
3.5
75% of rated load
100% of rated load
25% of rated load
RD030
50% of rated load
RD030
5.5
75% of rated load
7.4
189
218
189
87
100% of rated load
25% of rated load
10.4
4.92
8.71
12.5
16.36
RD048/RD050
50% of rated load
RD048/RD050
75% of rated load
100% of rated load
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
®
15 • 20 • 30 • 48 • 50 kW
operating data
ENGINE COOLING
15 kW
2824/80
2.8/10.6
63,535/67
20 kW
2824/80
2.8/10.6
63,535/67
30 kW
48/50 kW
Air flow (inlet air including alternator and combustion air in cfm/cmm)
System coolant capacity (gal/liters)
3038/86
2.8/10.6
2824/80
2.8/10.6
5 of 6
Heat rejection to coolant (BTU per hr/MJ per hr)
Maximum operation air temperature on radiator (°C/°F)
Maximum ambient temperature (°C/°F)
111,000/117.1
135,900/143.4
50/122
50/122
COMBUSTION REQUIREMENTS
Flow at rated power (cfm/cmm)
190/5.38
190/5.38
190/2.55
190/5.38
SOUND EMISSIONS
Exercising at 7 meters/23 feet (dB(A))
65
70
Normal operation at 7 meters/23 feet (dB(A))
*Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters.
EXHAUST
Exhaust flow at rated output (cfm/cmm)
Exhaust temperature at rated output (°C/°F)
448/12.7
448/12.7
230/6.51
448/12.7
604.4/1120
604.4/1120
454.4/850
604.4/1120
ENGINE PARAMETERS
Rated Synchronous RPM
HP at rated kW
1800
26.4
33.5
49
85
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration .................................................................................................................3% for every 5 °C above 25 °C or 1.7% for every 5 °F above 77 °F
Altitude Deration (15, 30, 48 & 50 kW) .............................................................................1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ft
Altitude Deration (20 kW) ................................................................................................ 1% for every 100 m above 305 m or 3% for every 1000 ft above 1000 ft
CONTROLLER FEATURES
2-Line Plain Text Multilingual LCD Display.....................................................................................................................Simple user interface for ease of operation.
Mode Buttons: Auto............................................................................................................................................Automatic Start on Utility failure. 7 day exerciser.
Manual....................................................................................... Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Off.........................................................................................................................Stops unit. Power is removed. Control and charger still operate.
Ready to Run/Maintenance Messages ................................................................................................................................................................................Standard
Engine Run Hours Indication..............................................................................................................................................................................................Standard
Programmable start delay between 2-1500 seconds .........................................................................................................Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility Adjustable ....................................................................................................................................From 140-171 V/190-216 V
Future Set Capable Exerciser/Exercise Set Error Warning....................................................................................................................................................Standard
Run/Alarm/Maintenance Logs .................................................................................................................................................................................50 Events Each
Engine Start Sequence ................................................................................................................... Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration).
Starter Lock-out ...............................................................................................................................Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger .......................................................................................................................................................................................................Standard
Charger Fault/Missing AC Warning.....................................................................................................................................................................................Standard
Low Battery/Battery Problem Protection and Battery Condition Indication ........................................................................................................................... Standard
Automatic Voltage Regulation with Over and Under Voltage Protection ............................................................................................................................... Standard
Under-Frequency/Overload/Stepper Overcurrent Protection.................................................................................................................................................Standard
Safety Fused/Fuse Problem Protection...............................................................................................................................................................................Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown .............................................................................................................................................Standard
Overcrank/Overspeed (@ 72 Hz)/RPM Sense Loss Shutdown ...........................................................................................................................................Standard
High Engine Temperature Shutdown ..................................................................................................................................................................................Standard
Internal Fault/Incorrect Wiring Protection ...........................................................................................................................................................................Standard
Common External Fault Capability .....................................................................................................................................................................................Standard
Field Upgradable Firmware ................................................................................................................................................................................................Standard
Download from Www.Somanuals.com. All Manuals Search And Download.
®
15 • 20 • 30 • 48 • 50 kW
available accessories
Model #
Product
Description
The 5-gallon spill box screws into the existing fuel fill port of the base tank. It captures and
contains fuel if over fueling or spilling occurs during the fill process.
006502-0
Spill Box
The 90% fuel level alarm alerts the fuel fill operator when the tank reaches a 90% fill level by
sounding an audible alarm and triggering an LED warning light.
006504-0
90% Fuel Level Alarm
Tank Risers
6 of 6
006505-0 - 15 & 20 kW
006506-0 - 30 & 50 kW
Tank risers are required in some municipalities to help avoid potential base tank corrosion
caused by mounting on rough surfaces.
A powder coat painted, steel fuel fill drop tube is required in some municipalities to prevent
sparking due to static electricity buildup, which can be caused by the fuel dropping into the
tank from the fill area. Using a drop tube also results in submerged filling, which increases
the fuel delivery flow rate and reduces vapors, foam and potential tank evaporation.
006507-0
Fuel Fill Drop Tube
006513-0 - 15 & 20 kW
006517-0 - 30 kW
006516-0 - 50 kW
Some municipalities require the use of stainless steel fuel lines instead of the standard hoses
Stainless Steel Fuel Lines provided with the diesel generator products. These stainless steel lines are fire resistant for
additional safety.
E-stop allows for immediate fuel shutoff and generator shutdown in the event of an
emergency.
006510-0
006511-0
006512-0
E-Stop
The spill box drainback kit allows fuel that was captured in the 5-gallon spill box to be drained
directly back into the fuel tank to avoid vapors.
Spill Box Drainback Kit
The cast iron, lockable fuel cap provides the ability to lock the fuel system to prevent
unwanted fuel tampering or fuel siphoning.
Lockable Fuel Cap
006572-0 - 15 & 20 kW
006571-0 - 30 kW
006570-0 - 50 kW
The Protector Maintenance Kits offer all the hardware necessary to perform complete
maintenance on Generac Protector generators.
Maintenance Kits
006560-0 - 15 & 20 kW
006559-0 - 30 kW
006558-0 - 50 kW
Recommended for generators installed in regions where the temperature regularly falls below
32 °F (0 °C). The Cold Weather Kits consist of a block heater with all necessary mounting
hardware and a battery warmer with a thermostat built into the battery wrap.
Cold Weather Kits
Fuel Maintenance Kit
Paint Kit
The Fuel Maintenance Kit contains everything needed to maintain and clean a diesel fuel
system
006576-0
If the generator enclosure is scratched or damaged, it is important to touch-up the paint to
protect from future corrosion. The paint kit includes the necessary paint to properly maintain
or touch-up a generator enclosure.
005704-0
Completely wireless and battery powered, Generac's wireless remote monitor provides you
with instant status information without ever leaving the house.
005928-0
005951-0
Basic Wireless Remote
Advanced Wireless
Remote
Remotely control generator functions with the advanced model's LCD display. In addition to
remote testing of the generator, set the exercise cycle and maintenance interval reminders.
The PMM Starter Kit consists of a 24 VAC, field installed transformer that enables the use
of the 24 VAC Power Management Modules (PMMs) and one PMM. The standard controller
(without starter kit) can control two HVAC loads with no additional hardware. Not compatible
with pre-wired switches.
006199-0
006186-0
PMM Starter Kit
Power Management Modules are used in conjunction with the Smart Switch to increase its
power management capabilities. It gives the Smart Switch additional power management
flexibility not found in any other transfer switch. Not compatible with pre-wired switches.
Note: PMM Starter Kit required.
Power Management
Module (50 Amps)
Generac's Mobile Link allows you to check the status of your generator from
anywhere that you have access to an Internet connection from a PC or with any
smart device. You will even be notified when a change in the generator’s status
occurs via e-mail or text message. Note: Harness Adapter Kit required.
006463-0
006478-0
Mobile Link™
The Harness Adapter Kit is required to make liquid-cooled units compatible with
Mobile Link™.
Harness Adapter Kit
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2013 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0K4729-A Printed in U.S.A. 07/19/13
Download from Www.Somanuals.com. All Manuals Search And Download.
|