Generac Portable Generator 004692 2 User Manual

CENTURION  
®
Installation and  
Owner’s Manual  
Air-cooled, Prepackaged  
Automatic Standby Generators  
Models:  
004692-2 (8.5 kW)  
CENTURION  
®
*This manual should remain with the unit.*  
Not intended for use as Primary Power in place of utility or  
!
!
in life-support applications.  
DANGER  
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!!  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Air-cooled 8.5 kW Generator  
3.2.2 “Off Position....................................14  
3.2.3 “Manual” Position ............................14  
3.3 Automatic Transfer Operation ....................14  
3.4 Sequence of Automatic Operation................14  
3.5 Manual Transfer Operation ........................14  
Introduction ........................Inside Front Cover  
Read This Manual Thoroughly ........................IFC  
Contents ..........................................................IFC  
Operation and Maintenance ............................IFC  
How to Obtain Service ....................................IFC  
Authorized Dealer Locator Number ................IFC  
3.5.1 Transfer to Generator  
Safety Rules ........................................................2  
Standards Index..................................................3  
Section 1 – General Information ..................4  
1.1 Unpacking/Inspection ....................................4  
1.2 Protection Systems ........................................4  
Power Source......................................14  
3.5.2 Transfer Back to Utility  
Power Source......................................15  
3.6 Setting the Exercise Timer ..........................15  
3.7 Protection Systems ......................................16  
3.7.1 Low Oil Pressure Switch ..................16  
3.7.2 High Temperature Switch ................16  
3.7.3 Overcrank ........................................16  
3.7.4 Overspeed ........................................16  
1.3 NEC Requirement for Arc Fault Circuit  
Interruption Breaker for Bedrooms ..............4  
1.3.1 Section 210.12 Arc Fault Circuit  
Interrupter Protection ........................4  
1.4 The Generator ..............................................5  
1.5 Specifications ................................................6  
1.5.1 Generator ..........................................6  
1.5.2 Engine ................................................6  
1.6 System Set LED ............................................7  
1.7 Fuel Requirements and Recommendations....7  
1.8 Fuel Consumption ........................................7  
1.9 Reconfiguring the Fuel System ......................7  
1.10 Location ........................................................8  
1.10.1 Generator ..........................................8  
1.10.2 Transfer Switch..................................8  
1.11 Battery Installation ........................................8  
1.12 The Battery....................................................9  
Section 2 – Post Installation Start-up  
Section 4 – Maintenance ..............................16  
4.1 Fuse ............................................................16  
4.2 Checking the Engine Oil Level ....................16  
4.3 Changing the Engine Oil ..............................17  
4.3.1 Engine Oil Recommendations ..........17  
4.3.2 Oil Change Procedure ......................17  
4.4 Changing the Oil Filter ................................17  
4.5 Changing the Engine Air Cleaner ................17  
4.5.1 8.5kW Generators ............................17  
4.6 Spark Plug(s) ..............................................18  
4.7 Battery Maintenance....................................18  
4.8 Adjusting Valve Clearance............................19  
4.9 Cooling System............................................19  
4.10 Attention After Submersion ........................20  
4.11 Out of Service Procedure ............................20  
4.11.1 Removal From Service......................20  
4.11.2 Return to Service..............................20  
4.12 Corrosion Protection ..................................20  
4.13 Service Schedule ........................................21  
and Adjustments ......................10  
2.1 Before Initial Startup ..................................10  
2.2 Check Transfer Switch Operation................10  
2.3 Electrical Checks ........................................10  
2.4 Generator Tests Under Load ......................11  
2.5 Checking Automatic Operation....................11  
Section 5 – Troubleshooting ........................22  
2.6 Adjusting the Regulator  
5.1 Troubleshooting Guide................................22  
(Natural Gas Only)........................................11  
Section 6 – Mounting Dimensions..............23  
Section 7 – Electrical Data............................24  
Section 8 – Exploded Views and  
Parts Lists....................................32  
Section 9 – Notes............................................46  
Section 10 – Warranty....................................48  
2.7 Engine Governor Adjustment ......................12  
2.7.1 Additional Corrosion Protection ......13  
2.8 Voltage Regulator Adjustment......................13  
Section 3 – Operation ....................................13  
3.1 Break-in Procedure......................................13  
3.2 Using the AUTO/OFF/MANUAL Switch ........13  
3.2.1 Auto” Position..................................13  
®
Generac Power Systems, Inc.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
Air-cooled 8.5 kW Generator  
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe  
operation be copied and posted near the unit’s installation site. Safety should be stressed to  
all operators and potential operators of this equipment.  
!
!
!
!
!
!
GENERAL HAZARDS  
WARNING:  
The engine exhaust from this product  
contains chemicals known to the state  
of California to cause cancer, birth  
defects or other reproductive harm.  
For safety reasons, Generac recommends that the  
installation, initial start-up and maintenance of  
this equipment is carried out by a Generac  
Authorized Dealer.  
• The engine exhaust fumes contain carbon monox-  
ide, which can be DEADLY. This dangerous gas, if  
breathed in sufficient concentrations, can cause  
unconsciousness or even death. This exhaust sys-  
tem must be installed properly, in strict compli-  
ance with applicable codes and standards.  
Following installation, do nothing that might ren-  
der the system unsafe or in noncompliance with  
such codes and standards.  
• Keep hands, feet, clothing, etc., away from drive  
belts, fans, and other moving or hot parts. Never  
remove any drive belt or fan guard while the unit is  
operating.  
• Adequate, unobstructed flow of cooling and venti-  
lating air is critical to correct generator operation.  
Do not alter the installation or permit even partial  
blockage of ventilation provisions, as this can seri-  
ously affect safe operation of the generator. The  
generator MUST be installed outdoors.  
• When working on this equipment, remain alert at  
all times. Never work on the equipment when  
physically or mentally fatigued.  
• Inspect the generator regularly, and contact the  
nearest Generac Authorized Dealer for parts need-  
ing repair or replacement.  
• Before performing any maintenance on the genera-  
tor, disconnect its battery cables to prevent acci-  
dental start up. Disconnect the cable from the bat-  
tery post indicated by a NEGATIVE, NEG or (–)  
first. Reconnect that cable last.  
• Never use the generator or any of its parts as a  
step. Stepping on the unit can stress and break  
parts, and may result in dangerous operating con-  
ditions from leaking exhaust gases, fuel leakage,  
oil leakage, etc.  
!
!
WARNING:  
This product contains or emits chemicals  
known to the state of California to cause  
cancer, birth defects or other reproductive harm.  
Study these SAFETY RULES carefully before  
installing, operating or servicing this equipment.  
Become familiar with this Owner’s Manual and with  
the unit. The generator can operate safely, efficiently  
and reliably only if it is properly installed, operated  
and maintained. Many accidents are caused by failing  
to follow simple and fundamental rules or precau-  
tions.  
Generac cannot possibly anticipate every possible  
circumstance that might involve a hazard. The warn-  
ings in this manual, and on tags and decals  
affixed to the unit are, therefore, not all-inclusive. If  
using a procedure, work method or operating tech-  
nique Generac does not specifically recommend, sat-  
isfy yourself that it is safe for others. Also make sure  
the procedure, work method or operating technique  
choosen does not render the generator unsafe.  
DANGER  
Despite the safe design of this generator,  
!
operating this equipment imprudently, neglecting  
its maintenance or being careless can cause  
possible injury or death. Permit only responsible  
and capable persons to operate or maintain this  
equipment.  
Potentially lethal voltages are generated by  
these machines. Ensure all steps are taken to  
render the machine safe before attempting to  
work on the generator.  
Parts of the generator are rotating and/or hot  
during operation. Exercise care near running  
!
generators.  
®
2
Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
Air-cooled 8.5 kW Generator  
• Keep a fire extinguisher near the generator at all  
times. Extinguishers rated ABC” by the National  
Fire Protection Association are appropriate for use  
on the standby electric system. Keep the extin-  
guisher properly charged and be familiar with its  
use. If there are any questions pertaining to fire  
extinguishers, consult the local fire department.  
ELECTRICAL HAZARDS  
• All generators covered by this manual produce  
dangerous electrical voltages and can cause fatal  
electrical shock. Utility power delivers extremely  
high and dangerous voltages to the transfer switch  
as does the standby generator when it is in opera-  
tion. Avoid contact with bare wires, terminals, con-  
nections, etc., while the unit is running. Ensure all  
appropriate covers, guards and barriers are in  
place before operating the generator. If work must  
be done around an operating unit, stand on an  
insulated, dry surface to reduce shock hazard.  
• Do not handle any kind of electrical device while  
standing in water, while barefoot, or while hands  
or feet are wet. DANGEROUS ELECTRICAL  
SHOCK MAY RESULT.  
• The National Electrical Code (NEC) requires the  
frame and external electrically conductive parts of  
the generator to be connected to an approved earth  
ground. Local electrical codes also may require  
proper grounding of the generator electrical system.  
• After installing this home standby electrical sys-  
tem, the generator may crank and start at any time  
without warning. When this occurs, load circuits  
are transferred to the STANDBY (generator) power  
source. To prevent possible injury if such a start  
and transfer occur, always set the generator’s  
AUTO/OFF/MANUAL switch to its OFF position  
before working on equipment and remove the fuse.  
• In case of accident caused by electric shock, imme-  
diately shut down the source of electrical power. If  
this is not possible, attempt to free the victim from  
the live conductor. AVOID DIRECT CONTACT WITH  
THE VICTIM. Use a nonconducting implement,  
such as a rope or board, to free the victim from the  
live conductor. If the victim is unconscious, apply  
first aid and get immediate medical help.  
EXPLOSION HAZARDS  
• Do not smoke around the generator. Wipe up any  
fuel or oil spills immediately. Ensure that no com-  
bustible materials are left in the generator com-  
partment, or on or near the generator, as FIRE or  
EXPLOSION may result. Keep the area surround-  
ing the generator clean and free from debris.  
• Gaseous fluids such as natural gas and liquid  
propane (LP) gas are extremely EXPLOSIVE.  
Install the fuel supply system according to applica-  
ble fuel-gas codes. Before placing the home stand-  
by electric system into service, fuel system lines  
must be properly purged and leak tested according  
to applicable code. After installation, inspect the  
fuel system periodically for leaks. No leakage is  
permitted.  
STANDARDS INDEX  
In the absence of pertinent standards, codes, regula-  
tions and laws, the published information listed  
below may be used as installation guide for this  
equipment.  
1. NFPA No. 37, STATIONARY COMBUSTION  
ENGINES AND GAS TURBINES, available from  
the National Fire Protection Association, 470  
Atlantic Avenue, Boston, MA 02210.  
2. NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-  
TEMS FOR HEALTH CARE FACILITIES, avail-  
able same as Item 1.  
• Never wear jewelry when working on this equip-  
ment. Jewelry can conduct electricity resulting in  
electric shock, or may get caught in moving com-  
ponents causing injury.  
3. NFPA No. 54, NATIONAL FUEL GAS CODE,  
available same as Item 1.  
4. NFPA No. 58, AMERICAN NATIONAL STANDARD  
FOR STORAGE AND HANDLING OF LIQUEFIED  
PETROLEUM GAS, available same as Item 1.  
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL  
ELECTRIC CODE, available same as Item 1.  
6. Article X, NATIONAL BUILDING CODE, available  
from the American Insurance Association, 85  
John Street, New York, N.Y. 10038.  
7. AGRICULTURAL WIRING HANDBOOK, available  
from the Food and Energy Council, 909  
University Avenue, Columbia, MO 65201.  
8. ASAE EP-3634, INSTALLATION AND MAINTE-  
NANCE OF FARM STANDBY ELECTRICAL SYS-  
TEMS, available from the American Society of  
Agricultural Engineers, 2950 Niles Road, St.  
Joseph, MI 49085.  
FIRE HAZARDS  
For fire safety, the generator must be installed and  
maintained properly. Installation always must  
comply with applicable codes, standards, laws and  
regulations. Adhere strictly to local, state and  
national electrical and building codes. Comply  
with regulations the Occupational Safety and  
Health Administration (OSHA) has established.  
Also, ensure that the generator is installed in  
accordance with the manufacturer’s instructions  
and recommendations. Following proper installa-  
tion, do nothing that might alter a safe installation  
and render the unit in noncompliance with the  
aforementioned codes, standards, laws and regu-  
lations.  
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE  
LIQUIDS CODE, available same as Item 1.  
®
Generac Power Systems, Inc.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 8.5 kW Generator  
There are LED readouts on the control panel to noti-  
fy personnel that one of these faults has occurred.  
DANGER  
Only qualified electricians or contractors should  
attempt such installations, which must comply  
strictly with applicable codes, standards and  
regulations.  
!
1.3 NEC REQUIREMENT FOR ARC  
FAULT CIRCUIT INTERRUPTION  
BREAKER FOR BEDROOMS  
The 2002 National Electric Code (NEC) introduced a  
requirement for new construction. This new require-  
ment indicates the need for Arc Fault Circuit  
Interrupters to be used to protect the complete  
branch circuit that feeds a dwelling bedroom. The  
actual NEC requirement is indicated below.  
1.1 UNPACKING/INSPECTION  
After unpacking, carefully inspect the contents  
for damage.  
• This standby generator set has been factory sup-  
plied with a weather protective enclosure that is  
intended for outdoor installation only.  
• This standby generator set is packaged with an  
automatic transfer switch with built in load center.  
The combination transfer switch and load center is  
pre-wired with a 2 foot and 30 foot conduit. Circuit  
breakers for emergency circuit connections are  
included.  
• This UL listed, NEMA 1, 2-pole switch is rated at  
100 AC amperes at 250 volts maximum. This  
transfer switch is for indoor use only.  
1.3.1 SECTION 210.12 ARC FAULT CIRCUIT  
INTERRUPTER PROTECTION  
1. Definition: An arc fault circuit interrupter is a  
device intended to provide protection from the  
effects of arc faults by recognizing characteristics  
unique to arcing and by functioning to de-ener-  
gize the circuit when an arc fault is detected.  
2. Dwelling Unit Bedrooms: All branch circuits that  
supply 125 volt, single-phase, 15 and 20 ampere  
outlets installed in dwelling unit bedrooms shall  
be protected by an arc fault circuit interrupter  
listed to provide protection of the entire branch  
circuit.  
Section 210.12 requires that AFCI protection be pro-  
vided on branch circuits that supply outlets (recepta-  
cle, lighting, etc.) in dwelling bedrooms. The require-  
ment is limited to 15 and 20 ampere, 125 volt cir-  
cuits. There is no prohibition against providing AFCI  
protection on other circuits or in locations other than  
bedrooms. Because circuits are often shared between  
a bedroom and other areas such as closets and hall-  
ways, providing AFCI protection on the complete cir-  
cuit would comply with 210.12.  
If this generator is used to power electrical load  
circuits normally powered by a utility power  
source, it is required by code to install a trans-  
fer switch. The transfer switch must effectively  
isolate the electrical system from the utility dis-  
tribution system when the generator is operat-  
ing (NEC 700, 701, and 702). Failure to isolate  
an electrical system by such means will result in  
damage to the generator and also may result in  
injury or death to utility power workers due to  
backfeed of electrical energy.  
If any loss or damage is noted at time of delivery, have  
the person(s) making the delivery note all damage on  
the freight bill or affix his or her signature under the  
consignor's memo of loss or damage.  
If during the installation of the Guardian Home  
Standby system the decision is made to provide back  
up power to a bedroom branch circuit, then the cir-  
cuit breaker in the Guardian Transfer Switch should  
be replaced with an Arc Fault Circuit Interrupter.  
If a loss or damage is discovered after delivery, sepa-  
rate the damaged materials and contact the carrier  
for claim procedures.  
It is most important that breakers only be switched  
like for like. For instance, if replacing a 15A breaker,  
it MUST be replaced with a 15A AFCI breaker.  
Likewise, a 20A breaker MUST be replaced with a  
20A AFCI.  
“Concealed damage” is understood to mean damage  
to the contents of a package that is not in evidence at  
the time of delivery, but is discovered later.  
1.2 PROTECTION SYSTEMS  
These AFCI breakers are available at the nearest  
hardware store.  
Unlike an automobile engine, the generator may have  
to run for long periods of time with no operator pres-  
ent to monitor engine conditions. For that reason, the  
engine is equipped with the following systems that  
protect it against potentially damaging conditions:  
Siemens Item #  
Q115AF  
Description  
15A Single Pole AFCI  
20A Single Pole AFCI  
Q120AF  
1. Low Oil Pressure Sensor  
2. High Temperature Sensor  
3. Overcrank  
4. Overspeed  
®
4
Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 8.5 kW Generator  
1.4 THE GENERATOR  
Figure 1.1 – 8.5 kW, V-Twin GT-990/760 Engine  
Data  
Decal  
Control  
Panel  
Oil Dipstick  
Air Filter  
Exhaust  
Enclosure  
Fuel Regulator  
Fuel Inlet  
Battery Compartment  
Oil Filter  
®
Generac Power Systems, Inc.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 8.5 kW Generator  
1.5 SPECIFICATIONS  
1.5.1 GENERATOR  
Model 004692  
8,500 NG/8,500 LP  
120/240  
Rated Max. Continuous Power Capacity (Watts*)  
Rated Voltage  
Rated Max. Continuous Load Current (Amps)  
120 Volts  
70.8 NG/70.8 LP  
240 Volts  
35.4 NG/35.4 LP  
Main Line Circuit Breaker  
Phase  
Number of Rotor Poles  
Rated AC Frequency  
Power Factor  
40 Amp  
1
2
60 Hz  
1
Battery Requirement  
at -17.8° C (0° F)  
Group 26/26R 12 Volts and 525  
Cold-cranking Amperes Minimum  
Weight  
Output Sound Level  
Normal Operating Range  
470 Pounds  
68 db (A)  
-20°F (28.8°C to 104°F (40°C)  
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power  
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60° F) ambient temperature.  
1.5.2 ENGINE  
Model 004692  
GT-990/760  
Type of Engine  
Number of Cylinders  
Rated Horsepower  
Displacement  
2
26 @ 3,600 rpm  
992cc  
Cylinder Block  
Valve Arrangement  
Ignition System  
Recommended Spark Plug  
Spark Plug Gap  
Compression Ratio  
Starter  
Aluminum w/Cast Iron Sleeve  
Overhead Valves  
Solid-state w/Magneto  
RC12YC  
0.50 mm (0.020 inch)  
9.5:1  
12 Vdc  
Oil Capacity Including Filter  
Recommended Oil Filter  
Recommended Air Filter  
Operating RPM  
Approx. 1.7 Qts  
Generac Part # 70185  
Generac Part # 0C8127  
3,600  
®
6
Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 8.5 kW Generator  
1.6 SYSTEM SET LED  
The “System Set” LED is lit when all of the following  
conditions are true:  
Gaseous fuels such as natural gas and liquid  
propane (LP) gas are highly explosive. Even the  
slightest spark can ignite such fuels and cause  
an explosion. No leakage of fuel is permitted.  
Natural gas, which is lighter than air, tends to  
collect in high areas. LP gas is heavier than air  
and tends to settle in low areas.  
1. The AUTO/OFF/MANUAL switch is set to the  
AUTO position.  
2. The UTILITY voltage being supplied to the unit is  
being sensed by the PCB. If the UTILITY sense  
voltage is not connected to the unit or if it is  
below 168 volts AC, then the System Set light will  
flash rapidly. This indicates that if the  
AUTO/OFF/MANUAL switch is placed in the Auto  
position , the generator will start.  
1.9 RECONFIGURING THE  
FUEL SYSTEM  
To reconfigure the fuel system from NG to LP,  
3. The “Not In Auto” dip switch is set to the OFF  
follow these steps:  
position on the control board.  
NOTE:  
4. No alarms are present, for example, low oil pres-  
sure, high temperature, etc.  
The primary regulator for the propane supply is  
NOT INCLUDED with the generator. A fuel pres-  
sure of 11 to 14 inches of water column (0.4 to 0.5  
psi) to the fuel inlet of the generator MUST BE  
SUPPLIED.  
1.7 FUEL REQUIREMENTS  
AND RECOMMENDATIONS  
With LP gas, use only the vapor withdrawal  
system. This type of system uses the vapors formed  
above the liquid fuel in the storage tank.  
1. Turn off the gas supply. (if connected)  
2. Open the roof and remove the door.  
3. Remove the battery. (if installed)  
The engine has been fitted with a fuel carburetion  
system that meets the specifications of the 1997  
California Air Resources Board for tamper-proof dual  
fuel systems. The unit will run on natural gas or LP  
gas, but it has been factory set to run on natural gas.  
Should the primary fuel need to be changed to LP  
gas, the fuel system needs to be reconfigured. See  
Section 1.9 for instructions on reconfiguration of the  
fuel system.  
4. Remove the engine air in baffle located on the left-  
hand side of the battery compartment. Two M6  
screws are located on top of the baffle and two  
M6 screws are located on the inside of the baffle  
towards the back.  
5. Remove the small hose clamp and hose from the  
fuel regulator. It may be necessary to pry the hose  
off of the brass fitting using a screwdriver to gen-  
tly lift up the hose edge.  
6. Remove the small brass hose fitting from the reg-  
Recommended fuels should have a Btu content of at  
least 1,000 Btus per cubic foot for natural gas; or at  
least 2,520 Btus per cubic foot for LP gas. Ask the  
fuel supplier for the Btu content of the fuel.  
ulator casting.  
7. Place the small fuel jet, thread side first, into the  
threaded hole originally occupied by the brass  
hose fitting (Figure 1.4).  
8. Using a short No. 2 Phillips screw driver, thread  
the small fuel jet into the regulator casting. Do  
not over tighten.  
Required fuel pressure for natural gas is 5 inches to  
7 inches water colum (0.18 to 0.25 psi); and for  
liquid propane, 11 inches to 14 inches of water  
column (0.4 to 0.5 psi).  
NOTE:  
Figure 1.4 - Demand Regulator  
Any piping used to connect the generator to the  
fuel supply should be of adequate size to ensure  
the fuel pressure NEVER drops below 4 inches  
water colum for natural gas or 10 inches water col-  
umn for liquid propane for all load ranges.  
OUTLET PORTS  
FUEL HOSE  
BRASS HOSE  
FITTING  
IDLE CIRCUIT  
PORT  
BRASS HOSE  
FITTING  
SMALL  
FUEL JET  
1
NP  
REGULATOR  
HOUSING PORT  
1.8 FUEL CONSUMPTION  
ADJUSTER  
SCREWS  
Model #  
Nat. Gas (*)  
LP Vapor (**)  
1/2 Load Full Load 1/2 Load  
Full Load  
1.98/72.5  
004692-1  
114  
170  
1.33/45.8  
* Natural gas is in cubic feet per hour.  
** LP is in gallons per hour/cubic feet per hour.  
®
Generac Power Systems, Inc.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 8.5 kW Generator  
9. Apply thread sealant to the threads of the hose fit-  
ting and replace it into the regulator body.  
10. Re-attach the small hose and hose clamp and  
tighten as necessary.  
1.10.2 TRANSFER SWITCH  
The transfer switch shipped with this generator is  
rated 100 amps maximum at 120/240 volts AC single  
phase. The enclosure of the transfer switch is NEMA  
1. This type of enclosure is intended for indoor use  
only. Follow these rules:  
11. Replace the engine air in baffle using the four M6  
screws.  
12. Identify both brass adjustment screws on the reg-  
ulator.  
• Install the transfer switch indoors on a firm, stur-  
dy supporting structure.  
NOTE:  
To prevent switch distortion, level the switch if nec-  
essary. This can be done by placing washers  
between the switch enclosure and mounting surface.  
• Never install the switch where water or any corro-  
sive substance might drip onto the enclosure.  
• Protect the switch at all times against excessive  
moisture, dust, dirt, lint, construction grit and cor-  
rosive vapors.  
One adjustment screw can be accessed from the  
front of the unit and the second can be accessed  
from the back of the unit enclosure by removing  
the plastic hole plug. The screw can be turned  
with a long flat blade screwdriver.  
13. To adjust the system to run on LP fuel, turn  
BOTH adjuster screws 1/2 TURN CLOCKWISE.  
The system should now be set for maximum  
power and best perfomance. DO NOT, UNDER  
ANY CIRCUMSTANCES, REMOVE THE SET  
PINS FROM THE REGULATOR HOUSING.  
THIS WILL VOID THE WARRANTY.  
1.11 BATTERY INSTALLATION  
Fill the battery with the proper electrolyte fluid if nec-  
essary and have the battery fully charged before  
installing it.  
14. It may be necessary to make minor adjustments  
to the preset adjustment screw settings to achieve  
maximum power, particularly at higher altitudes.  
If experiencing problems with the unit producing  
maximum power, follow the procedure in Section  
2.6 (Adjusting the Fuel Regulator).  
Before installing and connecting the battery, complete  
the following steps:  
1. Set the generator's AUTO/OFF/MANUAL switch to  
OFF.  
2. Turn off utility power supply to the transfer  
switch.  
1.10 LOCATION  
DANGER  
1.10.1 GENERATOR  
If the AUTO/OFF/MANUAL switch is not set to  
its OFF position, the generator can crank and  
start as soon as the battery cables are connect-  
ed. If the utility power supply is not turned off,  
sparking can occur at the battery posts and  
cause an explosion.  
Install the generator set, in its protective enclosure,  
outdoors, where adequate cooling and ventilating air  
is always available. Consider these factors:  
• Install the unit where air inlet and outlet openings  
will not become obstructed by leaves, grass, snow,  
etc. If prevailing winds will cause blowing or drift-  
ing, consider using a windbreak to protect the unit.  
• Install the generator on high ground where water  
levels will not rise and endanger it.  
• Allow sufficient room on all sides of the generator  
for maintenance and servicing. A good rule is to  
allow three feet of space on all sides.  
Battery cables were factory connected at the genera-  
tor (Figure 1.5). Connect cables to battery posts as  
follows:  
3. Connect the red battery cable (from starter con-  
tactor) to the battery post indicated by a positive,  
POS or (+).  
4. Connect the black battery cable (from frame  
ground) to the battery post indicated by a nega-  
tive, NEG or (—).  
• Where strong prevailing winds blow from one  
direction, face the generator air inlet openings to  
the prevailing winds.  
NOTE:  
• Install the generator as close as possible to the fuel  
Damage will result if battery connections are made  
in reverse.  
supply, to reduce the length of piping.  
• Install the generator as close as possible to the  
transfer switch. HOWEVER, REMEMBER THAT  
LAWS OR CODES MAY REGULATE THE DIS-  
TANCE.  
®
8
Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 8.5 kW Generator  
• Remove watches, rings or other metal objects;  
• Use tools with insulated handles;  
• Wear rubber gloves and boots;  
Figure 1.5 – Battery Cable Connections  
• Do not lay tools or metal parts on top of the  
battery; and  
• Disconnect charging source prior to connecting or dis-  
connecting battery terminals.  
Do not open or mutilate the battery. Released  
electrolyte has been known to be harmful to  
!
the skin and eyes, and to be toxic.  
The electrolyte is a dilute sulfuric acid that is  
harmful to the skin and eyes. It is electrically  
!
conductive and corrosive. The following  
procedures are to be observed:  
• Wear full eye protection and protective clothing;  
• Where electrolyte contacts the skin, wash it off  
immediately with water;  
• Where electrolyte contacts the eyes, flush  
thoroughly and immediately with water and seek  
medical attention; and  
• Spilled electrolyte is to be washed down with an  
acid neutralizing agent. A common practice is to  
use a solution of 1 pound (500 grams) bicarbonate  
of soda to 1 gallon (4 liters) or water. The bicar-  
bonate of soda solution is to be added until the  
evidence of reaction (foaming) has ceased. The  
resulting liquid is to be flushed with water and the  
area dried.  
NOTE:  
The generator is equipped with a battery trickle  
charger that is active when the unit is set up for  
automatic operation. With the battery installed  
and utility power source voltage available to the  
transfer switch, the battery receives a trickle  
charge while the engine is not running, to prevent  
self-discharge. The trickle charger is designed to  
help extend the life of the battery by maintaining  
the battery when the unit is not running. The  
trickle charge feature cannot be used to recharge  
a discharged battery.  
Lead-acid batteries present a risk of fire  
because they generate hydrogen gas. The  
following procedures are to be followed:  
1.12 THE BATTERY  
Servicing of the battery is to be performed or super-  
vised by personnel knowledgeable of batteries and  
the required precautions. Keep unauthorized person-  
nel away from batteries.  
• DO NOT SMOKE when near the battery;  
• DO NOT cause flame or spark in battery area; and  
• Discharge static electricity from body before touch-  
ing the battery by first touching a grounded metal  
surface.  
When replacing the battery, use the following type of  
battery: Group 26/26R 12VDC, 525 cold-cranking  
amps for 8.5 kW at -17.8º C (0º F) minimum. When  
using a maintenance-free battery, it is not necessary  
to check the specific gravity or electrolyte level. Have  
these procedures performed at the intervals specified  
in the “Service Schedule.” A negative ground system  
is used. Battery connections are shown on the wiring  
diagrams. Make sure the battery is correctly connect-  
ed and terminals are tight. Observe battery polarity  
when connecting the battery to the generator set.  
Be sure the AUTO/OFF/MANUAL switch is set to  
the OFF position before connecting the battery  
cables. If the switch is set to AUTO or MANUAL,  
the generator can crank and start as soon as  
the battery cables are connected.  
!
Be sure the utility power supply is turned off,  
or sparking may occur at the battery posts as  
the cables are attached and cause an explosion.  
DANGER  
Do not dispose of the battery in a fire. The  
battery is capable of exploding.  
A battery presents a risk of electrical shock  
and high short circuit current. The following  
precautions are to be observed when working  
on batteries:  
®
Generac Power Systems, Inc.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Post Installation Start-up and Adjustments  
Air-cooled 8.5 kW Generator  
4. Use an accurate AC voltmeter to check UTILITY  
2.1 BEFORE INITIAL START-UP  
power source voltage across transfer switch ter-  
minals N1 and N2. Nominal line-to-line voltage  
should be 240 volts AC.  
Before starting, complete the following:  
1. Set the generator's AUTO/OFF/MANUAL switch to  
the OFF position.  
2. Turn OFF the utility power supply to the transfer  
switch using the means provided (such as the  
utility main line circuit breaker).  
5. Check UTILITY power source voltage across ter-  
minals N1 and the transfer switch neutral lug;  
then across terminal N2 and neutral. Nominal  
line-to-neutral voltage should be 120 volts AC.  
6. When certain that UTILITY supply voltage is com-  
patible with transfer switch and load circuit rat-  
ings, turn OFF the UTILITY power supply to the  
transfer switch.  
7. On the generator panel, set the AUTO/OFF/MAN-  
UAL switch to MANUAL. The engine should crank  
and start.  
8. Let the engine warm up for about five minutes to  
allow internal temperatures to stabilize. Then, set  
the generator’s main circuit breaker to its ON (or  
closed) position.  
3. Turn OFF all loads connected to the tranfer  
switch terminals T1 and T2.  
4. Check the engine crankcase oil level and, if nec-  
essary, fill to the dipstick FULL mark with the  
recommended oil. Do not fill above the FULL  
mark.  
5. Check the fuel supply. Gaseous fuel lines must  
have been properly purged and leak tested in  
accordance with applicable fuel-gas codes. All  
fuel shutoff valves in the fuel supply lines must be  
open.  
DANGER  
Never operate the engine with the oil level  
below the “Add” mark on the dipstick. Doing  
this could damage the engine.  
Proceed with caution! Generator power voltage  
is now supplied to the transfer switch. Contact  
with live transfer switch parts will result in  
dangerous and possibly fatal electrical shock.  
!
2.2 CHECK TRANSFER SWITCH  
9. Connect an accurate AC voltmeter and a frequen-  
cy meter across transfer switch terminal lugs E1  
and E2. Voltage should be 242-252 volts; fre-  
quency should read about 61-63 Hertz.  
10. Connect the AC voltmeter test leads across termi-  
nal lug E1 and neutral; then across E2 and neu-  
tral. In both cases, voltage reading should be 121-  
126 volts AC.  
11. Set the generator’s main circuit breaker to its  
OFF (or open) position. Let the engine run at no-  
load for a few minutes to stabilize internal engine  
generator temperatures.  
OPERATION  
Refer to Section 3.5, of the owner’s manual for man-  
ual operation procedures.  
Do not attempt manual transfer switch opera-  
tion until all power voltage supplies to the  
transfer switch have been positively turned off.  
Failure to turn off all power voltage supplies  
will result in extremely hazardous and possibly  
fatal electrical shock.  
12. Set the generator's AUTO/OFF/MANUAL switch to  
OFF. The engine should shut down.  
2.3 ELECTRICAL CHECKS  
NOTE:  
Complete electrical checks as follows:  
It is important not to proceed until certain that  
generator AC voltage and frequency are correct  
and within the stated limits. Generally, if both AC  
frequency and voltage are high or low, the engine  
governor requires adjustment. If frequency is cor-  
rect, but voltage is high or low, the generator’s  
voltage regulator requires adjustment.  
1. Set the generator's main circuit breaker to its  
OFF (or open) position.  
2. Turn OFF all loads connected to the transfer  
switch terminals T1 and T2.  
3. Turn on the UTILITY power supply to the trans-  
fer switch using the means provided (such as a  
utility main line circuit breaker).  
DANGER  
The transfer switch is now electrically “hot.”  
Contact with “hot” parts will result in extreme-  
ly hazardous and possibly fatal electrical shock.  
Proceed with caution.  
®
10 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Post Installation Start-up and Adjustments  
Air-cooled 8.5 kW Generator  
2.4 GENERATOR TESTS UNDER LOAD  
2.5 CHECKING AUTOMATIC  
To test the generator set with electrical loads applied,  
proceed as follows:  
OPERATION  
To check the system for proper automatic operation,  
proceed as follows:  
1. Set generator’s main circuit breaker to its OFF  
(or open) position.  
1. Check that the AUTO/OFF/MANUAL switch is set  
to OFF.  
2. Turn OFF the UTILITY power supply to the trans-  
fer switch, using the means provided (such as a  
UTILITY main line circuit breaker).  
3. Manually set the transfer switch to the UTILITY  
position, i.e., load terminals connected to the  
UTILITY power source side.  
2. Turn OFF all loads connected to the transfer  
switch terminals T1 and T2.  
3. Set the generator's AUTO/OFF/MANUAL  
switch to OFF.  
4. Turn OFF the UTILITY power supply to the trans-  
fer switch, using the means provided (such as a  
utility main line circuit breaker).  
4. Turn ON the UTILITY power supply to the trans-  
fer switch, using the means provided (such as a  
UTILITY main line circuit breaker).  
5. Set the AUTO/OFF/MANUAL switch to AUTO. The  
system is now ready for automatic operation.  
6. Turn OFF the UTILITY power supply to the trans-  
fer switch.  
With the AUTO/OFF/MANUAL switch at AUTO, the  
engine should crank and start when the utility source  
power is turned OFF. After starting, the transfer  
switch should connect load circuits to the standby  
side. Let the system go through its entire automatic  
sequence of operation.  
DANGER  
Do not attempt manual transfer switch opera-  
tion until all power voltage supplies to the  
transfer switch have been positively turned off.  
Failure to turn off all power voltage supplies  
will result in extremely hazardous and possibly  
fatal electrical shock.  
5. Manually set the transfer switch to the STANDBY  
position, i.e., load terminals connected to the  
generator's E1/E2 terminals. The transfer switch  
operating lever should be down.  
6. Set the generator's AUTO/OFF/MANUAL switch to  
MANUAL. The engine should crank and start  
immediately.  
With the generator running and loads powered by  
generator AC output, turn ON the UTILITY power  
supply to the transfer switch. The following should  
occur:  
7. Let the engine stabilize and warm up for a few  
minutes.  
8. Set the generator’s main circuit breaker to its ON  
(or closed) position. Loads are now powered by  
the standby generator.  
9. Turn ON electrical loads connected to transfer  
switch terminals T1 and T2. Apply an electrical  
load equal to the full rated wattage/amperage  
capacity of the installed generator.  
10. Connect an accurate AC voltmeter and a frequen-  
cy meter across terminal lugs E1 and E2. Voltage  
should be greater than 230 volts; frequency  
should be greater than 58 Hertz.  
11. Let the generator run at full rated load for 20-30  
minutes. Listen for unusual noises, vibration or  
other indications of abnormal operation. Check  
for oil leaks, evidence of overheating, etc.  
12. When testing under load is complete, turn OFF  
electrical loads.  
• After about six seconds, the switch should transfer  
loads back to the UTILITY power source.  
• About one minute after retransfer, the engine  
should shut down.  
2.6 ADJUSTING THE REGULATOR  
(NATURAL GAS ONLY)  
Although the generator has been factory set to pro-  
vide maximum power, it may be necessary in some  
areas to adjust this setting. Because natural gas has  
different BTU or power content across the country  
the engine may not perform as designed.  
If experiencing engine problems at high or full load  
conditions follow these steps. It will require a fre-  
quency meter to perform this procedure.  
1. Turn off UTILITY power to the main distribution  
panel in the house. This can be done by switching  
the service main breaker to the off or open posi-  
tion.  
2. Allow the generator to start. Before loading the  
generator, confirm that the no load frequency  
,with the roof open and door off, is set at 63-63.5  
Hz. Transfer load to emergency circuits.  
13. Set the generator's main circuit breaker to its  
OFF (or open) position.  
14. Let the engine run at no-load for a few minutes.  
15. Set the AUTO/OFF/MANUAL switch to OFF. The  
engine should shut down.  
®
Generac Power Systems, Inc. 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Post Installation Start-up and Adjustments  
Air-cooled 8.5 kW Generator  
3. Turn on appliances, lights, pumps, etc., that are  
on the emergency circuits in an attempt to fully  
load the generator. Be cautious not to overload  
the generator. Use the following chart as a guide:  
Do not make any unnecessary adjustments.  
Factory settings are correct for most applica-  
tions. However, when making adjustments, be  
careful to avoid overspeeding the engine.  
!
Unit  
120 Volts  
70.8 amps  
240 Volts  
35.4 amps  
8.5 kW  
If this procedure or equipment are not available,  
locate the nearest Generac Dealer and they can per-  
form the adjustments.  
4. When full load has been achieved. Connect a fre-  
quency meter to the output lugs of the generator’s  
main line circuit breaker.  
5. The fuel regulator is fitted with two adjustment  
screws. While watching the frequency meter,  
slowly turn the adjustment screws clockwise or  
counterclockwise one at a time until the highest  
frequency is read on the meter. (Figures 2.1 and  
2.2).  
NOTE:  
A service fee may be charged for this adjustment.  
2.7 ENGINE GOVERNOR ADJUSTMENT  
If both AC frequency and voltage are correspondingly  
high or low, adjust the engine governor as follows:  
Figure 2.1 — Dual Fuel Regulators  
1. Loosen governor clamp bolt (Figure 2.3).  
V-twin  
Figure 2.3 — V-twin Engine Governor  
Adjustment  
Idle Spring  
Governor  
Adjustment  
Screw  
(Both Sides)  
Shaft  
(Rotate  
Clockwise)  
Set Pin  
(Both Sides)  
6. When the highest frequency is reached maximum  
power has been set. From this point, turn both  
adjustment screws 1/4 turn clockwise. The regu-  
lator is now set.  
No Load Idle  
Adjustment Screw  
Governor Clamp Bolt  
Figure 2.2 — Placement of Regulator  
2. Completely remove the idle spring.  
3. With governor arm at wide open throttle position,  
rotate governor shaft fully clockwise. Tighten  
clamp bolt to 84 inch-pounds.  
4. Start unit and apply full load. Use full load speed  
adjust screw (Figure 2.4) to adjust frequency to  
58 Hz.  
5. Remove load, stop engine, loosen the idle adjust  
screw and reconnect the idle spring.  
6. Using a hand, push the governor arm to the  
closed throttle position. Make sure the idle spring  
does not stretch at all.  
7. Restart the unit.  
Adjustment Screw  
8. Slowly turn the idle adjust screw to adjust the no-  
load idle frequency to 63-63.5 Hz.  
9. The governor is now set.  
7. Turn UTILITY power to the main distribution  
panel back on. This can be done by switching the  
service main breaker to the on or closed position.  
Allow the generator to shut down.  
®
12 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 — Operation  
Air-cooled 8.5 kW Generator  
Figure 2.4 — Full Load Speed Adjust Screw  
3.1 BREAK-IN PROCEDURE  
Once the unit has been installed and all electrical  
checks have been made, it is strongly recommended  
that the following “Break-in Procedure” be completed  
to ensure correct generator operation in the future.  
Full Load Speed Adjust Screw  
1. Set the generator’s AUTO/OFF/MANUAL switch to  
AUTO.  
2. Turn OFF the UTILITY power supply to the trans-  
fer switch using the means provided (such as a  
utility main line circuit breaker).  
3. The unit will start, and the transfer switch will  
transfer to standby.  
4. Using the transfer switch’s built-in emergency  
load center, turn on circuits to load the generator  
to approximately 25% rated load and run the unit  
for one hour.  
2.7.1 ADDITIONAL CORROSION  
PROTECTION  
Periodically spray all engine linkage parts and brack-  
ets with corrosion inhibiting spray such as WD-40 or  
a comparable product.  
5. Run the unit for one hour at 50% rated load.  
6. Run the unit for one hour at 75% rated load.  
7. Run the unit for one hour at 100% rated load.  
8. Turn ON the UTILITY power supply to the trans-  
fer switch, which will allow the transfer switch to  
transfer back to UTILITY power. The unit will  
continue to run for one minute and then shut  
down.  
2.8 VOLTAGE REGULATOR  
9. Allow the unit to cool.  
ADJUSTMENT  
With the frequency between 62-63 Hertz, slowly turn  
the slotted potentiometer (Figure 2.5) until line volt-  
age reads 244-252 volts.  
10. Drain the oil and remove the oil filter. Replace the  
oil filter according to Section 4.4, “Changing the  
Oil Filter”. Replace the oil with synthetic oil as  
recommended in Section 4.3, “Changing the  
Engine Oil”.  
NOTE:  
The access panel on top of the control panel must  
be removed to adjust the voltage regulator.  
11. The generator is now ready for service.  
3.2 USING THE AUTO/OFF/MANUAL  
SWITCH (FIGURE 3.1)  
NOTE:  
The voltage regulator is housed above the genera-  
tor's control panel. The regulator maintains a volt-  
age in direct proportion to frequency at a 2-to-1  
ratio. For example, at 62 Hertz, line-to-neutral  
voltage will be 124 volts.  
3.2.1 “AUTO” POSITION  
Selecting this switch position activates fully automat-  
ic system operation. It also permits starting and exer-  
cising the engine every seven days with the setting of  
the exercise timer (see Section 3.6). This position  
also is used for remote starting, when it is set up.  
Figure 2.5 – Voltage Adjustment Potentiometer  
Figure 3.1 – Generator Control Panel  
FUSE  
R
L o c a t  
e
y o u r n e a r e s t  
d e a le r a t  
:
R
POWER SYSTEMS, INC.  
5A  
AUTO OFF MAN.  
SYSTEM SET  
LOW OIL  
HIGH TEMP.  
OVER SPEED  
OVER CRANK  
FUSE  
F L  
4
A
S
H
IN  
N
H
G
O
IN  
G R E E N L E D  
=
SET  
EXERCISE  
TIME  
15A  
U
G
T
IL IT  
E D L E D  
IS E R  
Y
S
E N  
S
=
E
F L  
A
S
R
S
T
E X E R  
C
N
O
S
E T  
®
Generac Power Systems, Inc. 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 — Operation  
Air-cooled 8.5 kW Generator  
Upon restoration of utility source voltage above a pre-  
set level, generator circuit board action signals the  
transfer switch to transfer loads back to that power  
supply. After retransfer, the engine is signalled to shut  
down.  
3.2.2 “OFF” POSITION  
This switch position shuts down the engine. This  
position also prevents automatic operation.  
3.2.3 “MANUAL POSITION  
Set the switch to Manual to crank and start the  
engine. Transfer to standby power will not occur  
unless there is a utility failure.  
The actual sequence of operation is controlled by  
sensors and timers on a control logic circuit board,  
as follows:  
A.Utility Voltage Dropout Sensor  
• This sensor monitors UTILITY source voltage.  
• If utility source voltage drops below about 60 per-  
cent of the nominal supply voltage, the sensor  
energizes a 15-second timer.  
• Once the timer has expired, the engine will crank  
and start.  
With the switch set to AUTO, the engine may  
crank and start at any time without warning.  
!
Such automatic starting normally occurs when  
utility power source voltage drops below a pre-  
set level or during the normal exercise cycle. To  
prevent possible injury that might be caused by  
such sudden starts, always set the switch to  
OFF and remove the fuse before working on or  
around the generator or transfer switch. Then,  
place a “Do Not Operate” tag on the generator  
panel and on the transfer switch.  
B.Engine Warm-up Time Delay  
• This mechanism lets the engine warm up for  
about 10 seconds before the load is transferred  
to a standby source.  
C.Standby Voltage Sensor  
• This sensor monitors generator AC output volt-  
age. When the voltage has reached 50 percent of  
the nominal rated voltage, transfer to standby  
can occur.  
3.3 AUTOMATIC TRANSFER  
D.Utility Voltage Pickup Sensor  
OPERATION  
To select automatic operation, do the following:  
• This sensor monitors UTILITY power supply  
voltage. When that voltage is restored above 80  
percent of the nominal source voltage, a retrans-  
fer time delay starts timing.  
1. Make sure the transfer switch main contacts are  
set to their UTILITY position, i.e., loads connect-  
ed to the UTILITY power source (Figure 3.2).  
2. Be sure that normal UTILITY power source volt-  
age is available to transfer switch terminal lugs  
N1 and N2.  
E.Retransfer Time Delay  
• This timer runs for about 15 seconds.  
• At end of a 15-second delay, circuit board action  
de-energizes transfer relay in the transfer switch.  
• Retransfer to UTILITY power source then occurs.  
F. Engine Cool-down Timer  
• When the load is transferred back to UTILITY  
power source, the engine cool-down timer starts  
timing.  
3. Set the generator’s AUTO/OFF/MANUAL switch to  
AUTO.  
4. Set the generator’s main circuit breaker to its ON  
(or closed) position.  
With the preceding steps complete, the generator will  
start automatically when utility source voltage drops  
below a preset level. After the unit starts, loads are  
transferred to the standby power source. Refer to  
Section 3.4, “Sequence of Automatic Operation”.  
• The timer will run for about one minute, and the  
generator will then shut down.  
3.5 MANUAL TRANSFER OPERATION  
3.4 SEQUENCE OF AUTOMATIC  
3.5.1 TRANSFER TO GENERATOR  
POWER SOURCE  
OPERATION  
The generator’s control panel houses a control logic  
circuit board. This board constantly monitors utility  
power source voltage. Should that voltage drop below  
a preset level, circuit board action will signal the  
engine to crank and start. After the engine starts, the  
circuit board signals the transfer switch to activate  
and connect load circuits to the standby power sup-  
ply (load terminal lugs T1/T2 connect to terminal  
lugs E1/E2).  
To start the generator and activate the transfer switch  
manually, proceed as follows:  
1. Set the generator’s AUTO/OFF/MANUAL switch  
to OFF.  
2. Set the generator’s main circuit breaker to its  
OFF (or open) position.  
3. Turn OFF the utility power supply to the transfer  
switch using the means provided (such as a  
utility main line circuit breaker).  
®
14 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 — Operation  
Air-cooled 8.5 kW Generator  
DANGER  
DANGER  
Do not attempt to activate the transfer switch  
manually until all power voltage supplies to  
the switch have been positively turned off.  
Failure to turn off all power voltage supplies  
may result in extremely hazardous and possibly  
fatal electrical shock.  
Do not attempt to activate the transfer switch  
manually until all power voltage supplies  
to the switch have been positively turned off.  
Failure to turn off all power voltage supplies  
may result in extremely hazardous and possibly  
fatal electrical shock.  
4. Use the manual transfer handle inside the trans-  
fer switch to move the main contacts to their  
“Standby” position, i.e., loads connected to the  
standby power source (Figure 3.2).  
5. Use the manual transfer handle inside the trans-  
fer switch to move the main contacts back to their  
UTILITY position, i.e., loads connected to the  
UTILITY power source (Figure 3.2).  
5. To crank and start the engine, set the  
AUTO/OFF/MANUAL switch to MANUAL.  
6. Let the engine stabilize and warm up for a few  
minutes.  
6. Turn ON the UTILITY power supply to the trans-  
fer switch using the means provided.  
7. Set the system to automatic operation as outlined  
in Automatic Transfer Operation,” Section 3.3.  
7. Set the generator’s main circuit breaker to its ON  
(or closed) position. The standby power source  
now powers the loads.  
3.6 SETTING THE EXERCISE TIMER  
The generator is equipped with an exercise timer.  
Once it is set, the generator will start and exercise  
once every seven days, on the day of the week and at  
the time of day the following sequence is completed.  
During this exercise period, the unit runs for approx-  
imately 12 minutes and then shuts down. Transfer of  
loads to the generator output does not occur during  
the exercise cycle.  
Figure 3.2 – Manual Transfer Switch Operation  
A switch on the control panel (see Figure 3.1) permits  
selection of the day and time for system exercise. To  
select the desired day and time of day, the following  
sequence must be performed at that time.  
1. Verify that the AUTO/OFF/MANUAL switch is set  
to AUTO.  
2. Hold down the “Set Exercise Time Switch” until  
the generator starts (approximately 10 seconds)  
and then release. During this time all the red  
LEDs on the control panel will flash to indicate  
board is resetting itself.  
3. The generator will start and run for approximately  
12 minutes and then shut down on its own. The  
exerciser will then be set to run at that time of day  
every week.  
3.5.2 TRANSFER BACK TO UTILITY POWER  
SOURCE  
NOTE:  
When utility power has been restored, transfer back  
to that source and shut down the generator. This can  
be accomplished as follows:  
The exerciser will only work in the AUTO mode  
and will not work correctly unless this procedure  
is performed. The exerciser will need to be reset  
every time the 12-volt battery is disconnected and  
then reconnected. The exerciser WILL NOT work  
if dip switch 2 on the controller printed circuit  
board (“Remote Not Auto”) is ON.  
1. Set the generator’s main circuit breaker to its  
OFF (or open) position.  
2. Let the engine run for a minute or two at no-load  
to stabilize the internal temperatures.  
3. Set the generator’s AUTO/OFF/MANUAL switch to  
its OFF (or open) position. The engine should  
shut down.  
If the exerciser is not set using the “Set Exercise  
Time Switch”, the generator will automatically  
exercise 7 days after the battery connection was  
made.  
4. Check that UTILITY power supply to the transfer  
switch is turned OFF.  
®
Generac Power Systems, Inc. 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Air-cooled 8.5 kW Generator  
3.7.3.1 Approximate Crank Cycle Times  
• 15 seconds ON  
• 7 seconds OFF  
3.7 PROTECTION SYSTEMS  
3.7.1 LOW OIL PRESSURE SWITCH  
• 7 seconds ON  
• 7 seconds OFF  
• Repeat for 45 seconds  
Approximately 90 seconds total  
This switch (Figure 3.3) has normally closed contacts  
that are held open by engine oil pressure during  
cranking and operating. Should oil pressure drop  
below the 8 psi range, switch contacts close, and the  
engine shuts down. The unit should not be restarted  
until oil is added. The AUTO/OFF/MANUAL switch  
must then be turned to OFF and then back to AUTO.  
3.7.4 OVERSPEED  
This feature protects the generator from damage by  
shutting it down if it happens to run faster than the  
preset limit. This protection also prevents the gener-  
ator from supplying an output that could potentially  
damage appliances connected to the generator cir-  
cuit. Contact the nearest Generac Authorized Dealer  
if this failure occurs.  
3.7.2 HIGH TEMPERATURE SWITCH  
This switch’s (Figure 3.3) contacts close if the tem-  
perature should exceed approximately 140º C (284º  
F), initiating an engine shutdown. The generator will  
automatically restart and the LED on the generator  
control panel will reset once the temperature has  
returned to a safe operating level.  
4.1 FUSE  
Figure 3.3 – Low Oil Pressure and  
High Temperature Switches  
The generator panel’s 15 amp fuse (Figure 4.1) pro-  
tects the DC control circuit against overload. The fuse  
is wired in series with the battery output lead to the  
panel. If the fuse element has melted open, the engine  
will not crank or start. Replace the fuse using only an  
identical 15-amp replacement.  
Low Oil Switch  
High Temp Switch  
The generator panel’s 5 amp fuse protects the battery  
charge circuit against overload. If the fuse element  
has melted open, battery charging capabilities will  
not be possible. Replace the fuse using only an iden-  
tical 5 amp replacement. To remove fuse, push cap  
down and rotate counterclockwise.  
Figure 4.1 – Generator Control Panel  
Oil  
Drain  
Hose  
FUSE  
R
L o c a t  
e
y o u r n e a r e s t  
d e a le r a t  
:
R
Oil Filter  
POWER SYSTEMS, INC.  
5A  
AUTO OFF MAN.  
SYSTEM SET  
LOW OIL  
HIGH TEMP.  
OVER SPEED  
OVER CRANK  
FUSE  
3.7.3 OVERCRANK  
This feature prevents the generator from damaging  
itself when it continually attempts to start and anoth-  
er problem, such as no fuel supply, prevents it from  
starting. The unit will crank and rest for a preset time  
limit. Then, it will stop cranking, and the LED on the  
generator control panel will light indicating an over-  
crank failure. The AUTO/OFF/MANUAL switch will  
need to be set to OFF and then back to AUTO to reset  
the generator control board.  
F L  
4
A
S
H
IN  
N
H
G
O
IN  
G R E E N L E D  
=
SET  
EXERCISE  
TIME  
15A  
U
G
T
IL IT  
E D L E D  
IS E R  
Y
S
E N  
S
=
E
F L  
A
S
R
S
T
E X E R  
C
N
O
S
E T  
4.2 CHECKING THE ENGINE  
OIL LEVEL  
For oil capacities, see “Specifications,” Section 1.5.  
For engine oil recommendations, see Section 4.3.1.  
To check the engine oil level, proceed as follows  
(Figure 4.2):  
NOTE:  
If the fault is not repaired, the overcrank feature  
will continue to activate.  
1. Start the generator by moving the Auto/  
Off/Manual switch to the MANUAL position. Allow  
it to run for a short while and then shut it down  
by moving the switch to the OFF position.  
®
16 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Air-cooled 8.5 kW Generator  
2. Remove the dipstick and wipe it dry with a  
clean cloth.  
3. Install the dipstick; then, remove it again. The oil  
level should be at the dipstick “Full” mark. If nec-  
essary, add oil to the “Full” mark only. DO NOT  
FILL ABOVE THE “FULLMARK.  
2. Immediately after the engine shuts OFF, pull the  
oil drain hose (Figure 4.3) free of its retaining  
clip. Remove the cap from the hose and drain the  
oil into a suitable container.  
3. After the oil has drained, replace the cap onto the  
end of the oil drain hose. Retain the hose in the clip.  
4. Refill with the proper recommended oil (see  
Section 4.3.1). See Section 1.5.2 for oil capaci-  
ties.  
Never operate the engine with the oil level  
below the “Add” mark on the dipstick. Doing  
!
Figure 4.3 – Oil Drain Hose and Filter  
this could damage the engine.  
4. Install the dipstick.  
5. Reset the AUTO/OFF/MANUAL switch to its origi-  
nal position.  
Figure 4.2 — Oil Dipstick and Fill, 8.5 kW  
Oil Dipstick  
Oil  
Drain  
Hose  
Oil Fill  
Oil Filter  
4.4 CHANGING THE OIL FILTER  
Change the engine oil filter as follows:  
1. With the oil drained, remove the old oil filter by  
turning it counterclockwise.  
2. Apply a light coating of clean engine oil to the gas-  
ket of the new filter. See Section 1.5.1 for recom-  
mended filter.  
4.3 CHANGING THE ENGINE OIL  
3. Screw the new filter on by hand until its gasket  
lightly contacts the oil filter adapter. Then, tighten  
the filter an additional 3/4 to one turn (Figure 4.3).  
4. Refill with the proper recommended oil (see  
Section 4.3.1). See Section 1.5.2 for oil capaci-  
ties.  
4.3.1 ENGINE OIL RECOMMENDATIONS  
Use oil of American Petroleum Institute (API) Service  
Class SG, SH or SJ. Use all season SAE 5W-30  
Synthetic oil. Organic break-in oil is required before  
using synthetic oil.  
NOTE:  
5. Start the engine and check for leaks.  
The unit is supplied with “break-in” oil. See the  
“Break-in Procedure,” Section 3.1, for the first  
required oil change.  
4.5 CHANGING THE ENGINE  
AIR CLEANER  
4.5.1 8.5 KW GENERATORS  
See Figure 1.1, for the location of the air cleaner. Use  
the following procedure:  
Any attempt to crank or start the engine before  
it has been properly serviced with the recom-  
mended oil may result in an engine failure.  
!
1. Turn the two screws counterclockwise to loosen  
(Figure 4.4).  
2. Remove the cover and air filter.  
3. Wipe away dust or debris from inside of the air  
box and around edges.  
4.3.2 OIL CHANGE PROCEDURE  
To change the oil, proceed as follows:  
1. Run the engine until it is thoroughly warmed up  
then shut OFF the engine.  
4. Install the new air cleaner into the air box.  
®
Generac Power Systems, Inc. 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Air-cooled 8.5 kW Generator  
5. Install the cover. Turn the two cover screws clock-  
wise to tighten.  
See the “Service Schedule,” Section 4.11 for air  
cleaner maintenance. See Section 1.5.1 for air filter  
replacement part number.  
4.7 BATTERY MAINTENANCE  
The battery should be inspected per the “Service  
Schedule,” Section 4.11. The following procedure  
should be followed for inspection:  
1. Inspect the battery posts and cables for tightness  
and corrosion. Tighten and clean as necessary.  
2. Check the battery fluid level of unsealed batteries  
and, if necessary, fill with DISTILLED WATER  
ONLY. DO NOT USE TAP WATER IN BATTERIES.  
3. Have the state of charge and condition checked.  
This should be done with an automotive-type bat-  
tery hydrometer.  
Figure 4.4 — V-twin Engine Air Cleaner  
Screw  
DANGER  
Do not dispose of the battery in a fire. The  
battery is capable of exploding.  
Cover  
Filter  
A battery presents a risk of electrical shock  
and high short circuit current. The following  
precautions are to be observed when working  
on batteries:  
• Remove watches, rings or other metal objects;  
• Use tools with insulated handles;  
• Wear rubber gloves and boots;  
• Do not lay tools or metal parts on top of the  
battery; and  
• Disconnect charging source prior to connecting or dis-  
connecting battery terminals.  
4.6 SPARK PLUG(S)  
Reset the spark plug(s) gap or replace the spark  
plug(s) as necessary. See Section 4.11 for mainte-  
nance requirements.  
Do not open or mutilate the battery. Released  
electrolyte has been known to be harmful to  
!
1. Clean the area around the base of the spark  
plug(s) to keep dirt and debris out of the engine.  
Clean by scraping or washing using a wire brush  
and commercial solvent. Do not blast the spark  
plug(s) to clean.  
2. Remove the spark plug(s) and check the condi-  
tion. Replace the spark plug(s) if worn or if reuse  
is questionable. See Section 4.11 for recom-  
mended inspection.  
the skin and eyes, and to be toxic.  
The electrolyte is a dilute sulfuric acid that is  
harmful to the skin and eyes. It is electrically  
!
conductive and corrosive. The following  
procedures are to be observed:  
• Wear full eye protection and protective clothing;  
• Where electrolyte contacts the skin, wash it off  
immediately with water;  
• Where electrolyte contacts the eyes, flush  
thoroughly and immediately with water and seek  
medical attention; and  
3. Check the spark plug gap using a wire feeler  
gauge, carefully bending the ground electrode  
(Figure 4.5).  
• Spilled electrolyte is to be washed down with an  
acid neutralizing agent. A common practice is to  
use a solution of 1 pound (500 grams) bicarbonate  
of soda to 1 gallon (4 liters) or water. The bicar-  
bonate of soda solution is to be added until the  
evidence of reaction (foaming) has ceased. The  
resulting liquid is to be flushed with water and the  
area dried.  
Figure 4.5 – Setting the Spark Plug Gap  
SET PLUG GAP AT 0.50 mm  
(0.020 inch)  
Lead-acid batteries present a risk of fire  
because they generate hydrogen gas. The  
following procedures are to be followed:  
®
18 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Air-cooled 8.5 kW Generator  
• DO NOT SMOKE when near the battery;  
• DO NOT cause flame or spark in battery area; and  
• Discharge static electricity from body before touch-  
ing the battery by first touching a grounded metal  
surface.  
Figure 4.6 - Valve Clearance Adjustment  
Rocker  
Arm  
Pivot Ball  
Stud  
Jam Nut  
Valve  
Stem  
Be sure the AUTO/OFF/MANUAL switch is set to  
!
the OFF position before connecting the battery  
cables. If the switch is set to AUTO or MANUAL,  
the generator can crank and start as soon as  
the battery cables are connected.  
Be sure the utility power supply is turned off,  
or sparking may occur at the battery posts as  
the cables are attached and cause an explosion.  
4.8 ADJUSTING VALVE CLEARANCE  
After the first 50 hours of operation, adjust the  
valve clearance in the engine.  
NOTE:  
Start all four screws before tightening or it will not  
be possible to get all the screws in place. Make  
sure the valve cover gasket is in place.  
Important: If feeling uncomfortable about doing this  
procedure or the proper tools are not available,  
please contact the Generac Authorized Dealer for  
service assistance. This is a very important step to  
insure the longest life for the engine.  
• Re-attach the spark plug wire to the spark plug.  
• Repeat the process for the other cylinder.  
To adjusting valve clearance:  
4.9 COOLING SYSTEM  
Air inlet and outlet openings in the generator com-  
partment must be open and unobstructed for contin-  
ued proper operation. This includes such obstruc-  
tions as high grass, weeds, brush, leaves and snow.  
• Make sure the engine is at room temperature.  
• Make sure that the spark plug wire is removed  
from the spark plug and out of the way.  
• Remove the four screws attaching the valve cover  
Without sufficient cooling and ventilating air flow, the  
engine/generator quickly overheats, which causes it to  
quickly shut down. (see Figure 4.7)  
with a #2 or #3 phillips screwdriver.  
• Make sure the piston is at Top Dead Center (TDC)  
of its compression stroke (both valves closed). To  
get the piston at TDC, remove the intake screen at  
the front of the engine to gain access to the flywheel  
nut. Use a large socket and socket wrench to rotate  
the nut and hence the engine. While watching the  
piston through the spark plug hole. The piston  
should move up and down. The piston is at TDC  
when it is up as high as it can go.  
Figure 4.7 – Cooling Vent Locations  
• Loosen the rocker jam nut. Use an 10mm allen  
wrench to turn the pivot ball stud while checking  
clearance between the rocker arm and the valve  
stem with a feeler gauge. Correct clearance is  
0.002-0.004 inch (0.05-0.1 mm).  
NOTE:  
The rocker arm jam nut must be held in place as  
the pivot ball stud is turned.  
When valve clearance is correct, hold the pivot ball  
stud in place with the allen wrench and tighten the  
rocker arm jam nut. Tighten the jam nut to 174  
in/lbs. torque. After tightening the jam nut, recheck  
valve clearance to make sure it did not change.  
The exhaust from this product gets extremely  
hot and remains hot after shutdown. High  
grass, weeds, brush, leaves, etc. must remain  
clear of the exhaust. Such materials may ignite  
and burn from the heat of the exhaust system.  
• Install new valve cover gasket.  
• Re-attach the valve cover.  
The maximum ambient temperature for the  
!
generator is 48.9° C (104° F).  
®
Generac Power Systems, Inc. 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Air-cooled 8.5 kW Generator  
4.11.2 RETURN TO SERVICE  
To return the unit to service after storage, proceed  
as follows:  
4.10 ATTENTION AFTER SUBMERSION  
If the generator has been submerged in water,  
it must not be started and operated. Following any  
submersion in water, have a Generac Authorized  
Dealer thoroughly clean and dry the generator.  
1. Verify that utility power is turned off and that the  
AUTO/OFF/MANUAL switch is set to OFF.  
2. Check the tag on the engine for oil viscosity and  
classification. Verify that the correct recommend-  
ed oil is used in the engine (see Section 4.3.1). If  
necessary, drain and refill with the proper oil.  
3. Check the state of the battery. Fill all cells of  
unsealed batteries to the proper level with dis-  
tilled water. DO NOT USE TAP WATER IN THE  
BATTERY. Recharge the battery to 100 percent  
state of charge, or, if defective, replace the battery.  
See “Specifications,” Section 1.5, for type and  
size.  
4.11 OUT OF SERVICE PROCEDURE  
4.11.1 REMOVAL FROM SERVICE  
If the generator cannot be exercised every seven days,  
and it is to be out of service longer than 90 days, pre-  
pare the generator for storage as follows:  
1. Start the engine and let it warm up.  
2. Close the fuel shutoff valve in the fuel supply line  
and allow the unit to shut down.  
3. Once the unit has shut down, it will signal a low  
4. Clean and wipe the entire generator.  
5. Reconnect the battery. Observe battery polarity.  
Damage may occur if the battery is connected  
incorrectly.  
oil fault.  
4. Set the AUTO/OFF/MANUAL switch to OFF and  
turn off the utility power to the transfer switch.  
5. While the engine is still warm from running,  
drain the oil completely. Refill the crankcase with  
oil. See ”Engine Oil Recommendations,” Section  
4.3.1.  
6. Open the fuel shutoff valve.  
7. Start the unit by moving the AUTO/OFF/MANUAL  
switch to MANUAL. Allow the unit to warm up  
thoroughly.  
6. Attach a tag to the engine indicating the viscosity  
and classification of the oil in the crankcase.  
7. Remove the spark plug(s) and spray fogging agent  
into the spark plug(s) threaded openings.  
Reinstall and tighten the spark plug(s).  
8. Remove the battery and store it in a cool, dry  
room on a wooden board. Never store the battery  
on any concrete or earthen floor.  
8. Stop the unit and set the AUTO/OFF/MANUAL  
switch to AUTO.  
9. Turn on the utility power to the transfer switch.  
10. The generator is now ready for service.  
NOTE:  
If the battery was dead or disconnected, the exer-  
cise timer must be reset.  
9. Clean and wipe the entire generator.  
4.12 CORROSION PROTECTION  
Periodically wash and wax the enclosure using auto-  
motive type products. Frequent washing is recom-  
mended in a salt water, coastal area. Spray engine  
linkages with a light oil such as WD-40.  
®
20 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Air-cooled 8.5 kW Generator  
4.13 SERVICE SCHEDULE  
ATTENTION: It is recommended that all service work  
be performed by the nearest Generac Authorized Dealer.  
SYSTEM/COMPONENT  
PROCEDURE  
FREQUENCY  
X = Action  
Inspect  
Change  
Clean  
W = Weekly  
M = Monthly  
Y = Yearly  
R = Replace as Necessary  
* = Notify Dealer  
if Repair is Needed.  
FUEL  
Fuel lines and connections*  
X
X
M
M
LUBRICATION  
Oil level  
Oil  
X
X
AFTER BREAK-IN  
AND Y  
Oil filter  
AFTER BREAK-IN  
AND Y  
COOLING  
Enclosure louvers  
BATTERY  
X
X
W
Remove corrosion,  
ensure dryness  
X
X
X
X
M
M
Clean and tighten  
battery terminals  
Check charge state  
X
X
R
R
EVERY 6 M  
EVERY 6 M  
Electrolyte level  
(unsealed batteries only)*  
ENGINE AND MOUNTING  
Air cleaner  
X
X
R
R
Y
Y
Spark plug(s)  
GENERAL CONDITION  
Vibration, Noise, Leakage,  
Temperature*  
X
M
Y
COMPLETE TUNE-UP*  
TO BE COMPLETED BY A GENERAC  
AUTHORIZED DEALER  
®
Generac Power Systems, Inc. 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Troubleshooting  
Air-cooled 8.5 kW Generator  
5.1 TROUBLESHOOTING GUIDE  
PROBLEM  
The engine will not crank.  
CAUSE  
CORRECTION  
1. Replace fuse.  
2. Tighten, clean or replace  
as necessary.  
1. Fuse blown  
2. Loose, corroded or defective  
battery cables  
3. Defective starter contactor  
4. Defective starter motor  
5. Dead Battery  
3. *  
4. *  
5. Charge or replace battery.  
The engine cranks but  
will not start.  
1. Out of fuel  
1. Replenish fuel.  
2. *  
3. *  
2. Defective fuel solenoid (FS)  
3. Open #14 wire from  
engine control board  
4. Defective spark plug(s)  
5. Valve Lash  
4. Clean, re-gap or replace plug(s).  
5. Reset Valve Lash.  
The engine starts hard  
and runs rough.  
1. Air cleaner  
1. Check, replace air cleaner.  
plugged or damaged  
2. Defective spark plug(s)  
3. Fuel regulator not set.  
4. Fuel pressure incorrect.  
2. Clean, re-gap or replace plug(s).  
3. Set fuel regulator.  
4. Confirm fuel pressure to regulator  
is 11-14” water column (0.4-0.5  
psi) for LP, and 5-7” water colum  
(0.18-0.25 psi) for natural gas.  
The AUTO/OFF/MANUAL switch  
is set to OFF, but the engine  
continues to run.  
1. Defective switch  
1. *  
2. *  
2. AUTO/OFF/MANUAL switch  
wired incorrectly  
3. Defective control board  
3. *  
There is no AC output from  
the generator.  
1. Main line circuit breaker open  
2. Generator internal failure  
1. Reset circuit breaker  
to ON (or closed).  
2. *  
There is no transfer to  
standby after utility  
source failure.  
1. Defective transfer switch coil  
2. Defective transfer relay  
3. Transfer relay circuit open  
4. Defective control logic board  
1. *  
2. *  
3. *  
4. *  
Unit consumes large  
amounts of oil.  
1. Break-in procedure  
1. *  
not followed (see Section 2.1)  
*Contact the nearest Generac Authorized Dealer for assistance.  
®
22 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 — Mounting Dimensions  
Air-cooled 8.5 kW Generator  
Drawing No. 0D3739-B  
®
Generac Power Systems, Inc. 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Electrical Data  
Air-cooled 8.5 kW Generator  
Wiring Diagram - Drawing No. 0D8500-B  
ENGINE WIRING  
DIAGRAM KEY  
3
2
1
BA - BRUSH ASSEMBLY  
BCR - BATTERY CHARGE RELAY  
BATTERY  
CHARGER  
CB1 - MAIN OUTPUT BREAKER  
CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATION  
14  
2
1
D
-
DIODE  
0
DSW - PCB MOUNTED DIP SWITCH  
FS - FUEL SOLENOID  
225B  
F1 - FUSE 15 AMP  
F2 - FUSE 5 AMP  
GRD - CONTROL PANEL GROUND  
HTO - HIGH OIL TEMPERATURE SWITCH  
IC - INLINE CONNECTOR  
ICT - INTERCONNECTION TERMINALS  
FS  
224B  
13A  
0
13A  
0
225B  
IM1 - IGNITION MODULE, CYLINDER #1  
IM2 - IGNITION MODULE, CYLINDER #2  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
0
224B  
SCR - STARTER CONTACTOR RELAY  
SP1, SP2 - SPARK PLUGS  
SW1 - AUTO / OFF / MANUAL SWITCH  
SW2 - SET EXERCISE SWITCH  
14  
0
0
14  
SM - STARTER MOTOR  
TB - INSULATED TERMINAL BLOCK  
TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)  
14  
IC  
TB  
D
SP1  
6
0
0
14  
IM1  
18  
85  
4
3
86  
13  
13  
16  
13  
13  
13  
D
1
IC  
IC  
SP2  
C1  
16  
SCR  
IM2  
13  
18  
351  
85  
A
B
86  
351  
HTO  
0
0
14  
86  
56  
18  
85  
56  
1
56  
16  
13  
18  
86  
2
3
4
5
J2  
56  
14  
4
LOP  
0
J1  
86  
23  
56  
14  
239  
17  
0
194  
18  
CONTROL  
PRINTED CIRCUIT BOARD  
66A  
15A  
15  
RED  
BLACK  
DSW  
225  
1 - 20 Vac Sense Transformer  
2 - Remote Not Auto  
3 - 50 Hz Operation  
4 - SPARE  
SM  
224  
-
+
12V  
BATTERY  
SC  
CUSTOMER SUPPLIED  
L.E.D - ALARM INDICATORS  
®
24 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Electrical Data  
Air-cooled 8.5 kW Generator  
Wiring Diagram - 8.5 kW – Drawing No. 0D8500-B  
CONTROL PANEL BOX  
225  
224  
224A  
225A  
224A  
225A  
CLOSEST TO BEARING  
TX  
BCR  
CB2  
1
4
7
3
6
9
4
0
N1 N2  
STATOR  
162  
2
66  
13A  
A
B
77  
0
225B  
225B  
4
10  
9
224B  
224B  
0
2
11  
6
66  
8
2
14  
55  
4
6
22  
0
6
5
66A  
11  
0
11  
11  
22  
22  
77  
11  
66  
66  
13A  
225  
22  
4
0
4
3
2
0
6
0
77  
6
44  
1
224  
162  
162  
55  
C2  
VOLTAGE  
REGULATOR  
66A  
0
0
0
33  
66A  
4
55  
22  
N2  
N1  
13  
13  
225  
GRD  
13  
351  
224  
194  
23  
N2  
4
23  
N1  
13  
44  
351  
11  
13  
13A  
351  
15A  
194  
N2  
22  
23  
13  
33  
194  
N1  
0
13  
66A  
F2  
F1  
239  
CB1  
0
15A  
17  
OFF  
17  
15  
13  
239  
17  
0
SW1  
225  
224  
15  
1a  
1
15  
1b  
SW2  
240V GENERATOR  
AUTO  
OUTPUT TO TRANSFER  
SWITCH CONTACTOR  
CUSTOMER  
CONNECTION  
MANUAL  
®
Generac Power Systems, Inc. 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Electrical Data  
Air-cooled 8.5 kW Generator  
Electrical Schematic - Drawing No. 0D8501-B  
11  
22  
225A  
3
2
1
225A  
224A  
224A  
BATTERY  
CHARGER  
225B  
F2  
225  
13A  
13  
224B  
13A  
2
1
224  
F1  
7
7
9
BCR  
6
3
4
11  
0
13A  
13  
77  
C2-1  
0
15  
77  
14  
BATTERY CHARGE  
WINDING  
66  
0
66  
C2-2  
22  
0
0
C2-4  
55  
HTO  
0
C2-11  
0
LOP  
11  
22  
ENGINE RUN  
WINDING  
BA  
FIELD  
SW2  
C1-4  
0
14  
(STATOR)  
15  
C1-3  
0
C2-9  
C2-3  
4
0
ELECTRONIC  
VOLTAGE  
REGULATOR  
C2-10  
4
4
66A  
0
85  
23  
194  
6
86  
162  
C1-6  
4
6
CB2  
0
351  
225  
14  
224  
C2-7  
C2-8  
66A  
2
(STATOR)  
1
2
3
4
5
15A  
J2  
239  
23  
18  
1
2
4
66A  
J1  
DIAGRAM KEY  
194  
86  
3
5
7
23  
194  
56  
BA - BRUSH ASSEMBLY  
BCR - BATTERY CHARGE RELAY  
CB1 - CIRCUIT BREAKER, MAIN OUTPUT  
CB2 - CIRCUIT BREAKER, ALT. EXCITATION  
D - DIODE  
FS - FUEL SOLENOID  
F1 - FUSE 15 AMP  
F2 - FUSE 5 AMP  
HTO - HIGH OIL TEMPERATURE SWITCH  
IM1 - IGNITION MODULE, CYLINDER #1  
IM2 - IGNITION MODULE, CYLINDER #2  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTER  
SCR - STARTER CONTACTOR RELAY  
SP1, SP2 - SPARK PLUGS  
SW1 - AUTO / OFF / MANUAL SWITCH  
SW2 - SET EXERCISE SWITCH  
SM - STARTER MOTOR  
14  
66A  
239  
15A  
17  
CONTROL  
PRINTED CIRCUIT  
BOARD  
9
10  
12  
14  
15  
0
225  
224  
16  
17  
TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)  
®
26 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Electrical Data  
Air-cooled 8.5 kW Generator  
Electrical Schematic - Drawing No. 0D8501-B  
11  
C2-6  
22  
C2-5  
TX  
240VAC  
UTILITY  
INPUT  
225A  
224A  
N2  
N1  
N2  
56VA  
1VA  
N2  
N1  
12Vdc  
TRANSFER  
RELAY  
225  
224  
23  
194  
COIL  
N1  
CUSTOMER  
CONNECTIONS  
13  
17  
11  
NEUTRAL  
23  
22  
33  
15A  
0
SW1  
194  
120V  
120V  
POWER  
WINDING  
(STATOR)  
15A  
239  
13  
15  
17  
44  
CB1  
23  
15  
194  
239  
11  
0
240V  
14  
15  
13  
RED  
0
C2-1  
13  
SC  
SCR  
15  
56  
16  
16  
0
14  
C1-1  
18  
BATTERY  
12V  
0
SC  
0
FS  
0
SM  
17  
BLACK  
15  
CUSTOMER  
SUPPLIED  
IM1  
IM2  
0
SP1  
18  
D
18  
C1-5  
D
SP2  
®
Generac Power Systems, Inc. 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Electrical Data  
Air-cooled 8.5 kW Generator  
Electrical Schematic - 12 Circuit Load Center - Drawing No. 0E7815  
E1  
N1A  
194  
23  
194  
23  
194  
23  
12Vdc TRANSER  
COIL  
194  
TR  
23  
A
B
7
7
9
9
E1  
TS TO  
GENERATOR  
CONTROL PANEL  
1
4
3
6
OPEN  
N2  
N1A  
F2  
N2  
126  
205  
240VAC  
OUTPUT  
N2A  
F1  
N1A  
N1A  
N1  
N1  
N1A  
E1  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
CIRCUIT BREAKER  
E2  
E1  
E2  
NEUTRAL (WHITE)  
NEUTRAL (WHITE)  
RED (MAIN 2)  
NEUTRAL  
CONNECTION  
INSIDE SWITCH  
B
N2A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
205  
B
N1A  
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
BLU/WHT  
ORG  
BLU  
20A/120V CIRCUIT 10  
15A/120V CIRCUIT 9  
20A/120V CIRCUIT 6  
15A/120V CIRCUIT 5  
20A/240V CIRCUIT 2  
30A/240V CIRCUIT 1  
30A/240V CIRCUIT 3  
20A/240V CIRCUIT 4  
15A/120V CIRCUIT 7  
20A/120V CIRCUIT 8  
15A/120V CIRCUIT 11  
15A/120V CIRCUIT 12  
E2  
E2  
B
VR2  
C2  
N2A  
VIO  
C1  
A
T1  
T2  
YEL  
ATS  
T1  
BRN  
N2A  
CUSTOMER  
CIRCUIT  
CONNECTION  
B
E2  
T2  
BRN/WHT  
YEL/WHT  
GRY  
B
E2  
LEGEND  
PNK  
ATS-AUTOMATIC TRANSFER SWITCH  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
TR-TRANSFER RELAY  
TS-TERMINAL STRIP  
VIO/WHT  
ORG/WHT  
LC  
XA,XB-LIMIT SWITCHES  
®
28 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Electrical Data  
Air-cooled 8.5 kW Generator  
Electrical Schematic - 12 Circuit Load Center - Drawing No. 0E7815  
E1  
N1A  
194  
23  
194  
23  
194  
23  
12Vdc TRANSER  
COIL  
194  
TR  
23  
A
B
7
7
9
9
E1  
TS TO  
GENERATOR  
CONTROL PANEL  
1
4
3
6
OPEN  
N2  
N1A  
F2  
N2  
126  
205  
240VAC  
OUTPUT  
N2A  
F1  
N1A  
N1A  
N1  
N1  
N1A  
E1  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
CIRCUIT BREAKER  
E2  
E1  
E2  
NEUTRAL (WHITE)  
NEUTRAL (WHITE)  
RED (MAIN 2)  
NEUTRAL  
CONNECTION  
INSIDE SWITCH  
B
N2A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
205  
B
N1A  
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
E2  
XB  
XA  
E2  
B
BLU  
VIO  
15A/120V CIRCUIT 6  
15A/120V CIRCUIT 5  
20A/120V CIRCUIT 2  
30A/240V CIRCUIT 1  
30A/240V CIRCUIT 3  
15A/120V CIRCUIT 4  
15A/120V CIRCUIT 7  
15A/120V CIRCUIT 8  
N2A  
T1  
T2  
YLW  
BRN  
ATS  
T1  
N2A  
CUSTOMER  
CIRCUIT  
CONNECTION  
B
E2  
T2  
BRN/WHT  
YLW/WHT  
GRY  
B
E2  
LEGEND  
ATS-AUTOMATIC TRANSFER SWITCH  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2-5A, 600V FUSE  
PNK  
LC-CIRCUIT BREAKER (LOADS)  
TR-TRANSFER RELAY  
TS-TERMINAL STRIP  
LC  
XA,XB-LIMIT SWITCHES  
®
Generac Power Systems, Inc. 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Electrical Data  
Air-cooled 8.5 kW Generator  
Wiring Diagram - 12 Circuit Load Center - Drawing No. 0E7687  
®
30 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Electrical Data  
Air-cooled 8.5 kW Generator  
Wiring Diagram - 12 Circuit Load Center - Drawing No. 0E7687  
®
Generac Power Systems, Inc. 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Enclosure – Drawing No. 0F0100-A  
76  
85  
44  
77  
71  
40  
68  
69  
80  
82  
41  
73  
48  
81  
30  
17  
79  
80  
72  
1
86  
72  
5
52  
18  
A
29  
12  
49  
44  
16  
19  
28  
55  
75  
89  
64  
47  
54  
50  
9
35  
46  
11  
49  
51  
25  
14  
8
74  
57  
35  
27  
56  
50  
22  
34  
49  
5
1
59  
49  
62  
13  
35  
59  
38  
26  
3
51  
39  
37  
42  
43  
36  
51  
21  
49  
43  
83  
33  
2
32  
10  
49  
50  
53  
52  
20  
4
15  
62  
63  
71  
69  
35  
25  
60  
68  
®
32 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Compartment – Drawing No. 0F0100-A  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
7
8
9
0D8312  
0C6735  
0F0063  
0C7062  
0F0066  
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
2
1
1
1
1
1
1
1
ASSEMBLY, ENCLOSURE BASE  
SUPPORT, ROOF FOLDING  
ENCLOSURE, FRONT  
ENCLOSURE, EXHAUST SIDE  
ENCLOSURE, SIDE & BACK  
ENCLOSURE, ROOF  
PANEL, ALTERNATOR DIVIDER  
PANEL, MUFFLER BOX SIDE  
COVER, MUFFLER BOX  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
0F0710  
047411  
043116  
0D3700  
0D4662  
090388  
092120  
0D1606  
0D3167  
0A3328  
055414  
092079  
0A1658  
0C3906  
045771  
0388040AJ0  
14  
14  
5
18  
11  
35  
2
1
1
1
1
RIVET POP 0.125" X 0.337"  
SCREW HHC M6-1.0 X 16 G8.8  
SCREW HHC M6-1.0 X 12 G8.8  
NUT, LOCKING FLANGE M6-1.0  
SCREW HHTT M8-1.2 X 20 BP  
SCREW TAPTITE M6-1.0 X 12 YC  
NUT LOCK TRIC M6 X 1.0 Y/ZNC  
HOUSING, FAN  
GASKET, BATTERY HOLD DOWN  
PLUG, PLASTIC 0.593"  
LUG SLDLSS #2-#8X17/64 CU  
SCREW TAPTITE M6-1.0X25 BP  
L/WASH SPECIAL ¼  
SELF-ALIGN SCREW M6 HH  
NUT HEX M8-1.25 G8 YC  
CABLE, #6 RED BATTERY 38.5" (NOT  
SHOWN)  
WASHER FLAT 5/16" ZINC  
WASHER LOCK 5/16  
SCREW TAPTITE M5-0.8 X 10 BP  
HARNESS, ENGINE  
BUSHING, SNAP SB-1000-12  
SCREW HHC M8-1.25 X 25 G8.8  
RIVET,1/8" X 0.126" - 0.375" LSH POP  
L/WASH SPECIAL #10  
ASSEMBLY,BASE/C-PNL GRND WIRE  
ASSEMBLY,BASE/DOOR GROUND WIRE  
PLUG PLASTIC 1.375  
GASKET, EXTRUDED TRIM  
PLATE, "HOT"  
GROMMET 2.75 X 1/16  
0E9873  
0D8333  
0C8101A  
0C8101B  
0C8283  
0C8284A  
0C8284B  
0C8284C  
0C8285  
0C8899A  
0D1128  
0E4244  
0D2538A  
0D1839  
0D1840  
0D2425  
0D2588  
0D2676  
0D2677  
0D2979B  
0D2979C  
0D2979D  
0E4245  
0E4245A  
0E4245B  
0D3057D  
0D3059A  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
GASKET, DOOR SEAL  
FOAM, BACK ENCLOSURE  
FOAM, ROOF ENCLOSURE  
FOAM, FRONT ENCLOSURE  
BRACKET, BATTERY SUPPORT  
PAD, 24"X48" WITH MOUNTING HOLES  
PANEL, ENGINE DIVIDER  
BAFFLE, INTAKE  
HINGE, LIFT OFF, TYPE B KNUCKLE  
BRACKET, TOP SUPPORT  
BRACKET, BOTTOM SUPPORT  
DUCT, BASE AIR  
GASKET, FRONT DIVIDER  
COVER, FRONT EXHAUST ENCLOSURE  
COVER, BACK EXHAUST ENCLOSURE  
CLOTH, HARDWARE 266.7mm x 146mm  
CLOTH, HARDWARE 543mm x 146mm  
CLOTH, HARDWARE 266.7mm x 387.4mm  
FOAM, FRONT INTAKE BAFFLE  
FOAM, TOP INTAKE BAFFLE  
FOAM, BACK INTAKE BAFFLE  
FOAM, BACK ENCL. STRIP  
FOAM, EXHAUST SIDE ENCLOSURE  
END  
1
2
2
4
1
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
022145  
022129  
074908  
10  
6
8
1
1
4
2
2
1
2
2
11  
1
1
1
1
1
0D2346  
023484F  
043107  
0A7836  
0A8475  
0912970069  
0912970070  
055450  
0E5968  
0D3701  
0D3472  
0C8742  
0C8911  
0D8442  
EXTERNAL CONNECTION BOX  
POWER BLOCK  
HARNESS GENERATOR TO EXTERNAL  
CONNECTION BOX  
33  
0D3059B  
1
FOAM, EXHAUST SIDE ENCLOSURE  
FRONT  
34  
35  
36  
0E2874  
0D7176  
0D3059D  
1
24  
1
SCREW HHTR 1/4-20 X 3/4  
WASHER, SELF LOCKING  
FOAM, FRONT EXHAUST ENCLOSURE  
COVER  
FOAM, BACK EXHAUST ENCLOSURE  
COVER  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
036937  
022152  
051713  
022158  
0D3059C  
026850  
049813  
0D2537A  
0E4321  
0E1330A  
2
5
2
5
1
1
1
1
1
1
SCREW PPHM #10-32 X 1  
WASHER LOCK #10  
WASHER FLAT M5  
NUT HEX #10-32 STEEL  
37  
0D3059E  
1
FOAM, EXHAUST FAN HOUSING  
WASHER SHAKPROOF EXT 1/4 STEEL  
NUT HEX M6-1.0 G8 YELLOW CHROME  
HINGE, LIFT OFF, TYPE A KNUCKLE  
PANEL, EXHAUST ALIGNMENT  
GROMMET, 38.1 CROSS SLIT WITH  
HOLE  
38  
39  
40  
41  
42  
43  
44  
45  
0C7781A  
0D3037  
0D2537  
0D2538  
0D3037A  
0A2115  
022097  
022473  
2
1
1
1
1
4
9
8
DOOR, PAWL  
LATCH, QUARTER TURN LOCKING  
HINGE, LIFT OFF, TYPE A PIN  
HINGE, LIFT OFF, TYPE B PIN  
LATCH, QUARTER TURN NON-LOCKING  
WASHER NYLON .250"  
89  
90  
0E9692  
042907  
1
2
BRACKET, REGULATOR MOUNTING  
SCREW HHC M8-1.25 X 16mm  
WASHER LOCK M6-1/4"  
WASHER FLAT ¼" ZINC  
®
Generac Power Systems, Inc. 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Engine & Alternator – Drawing No. 0D8446-C  
®
34 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Engine & Alternator – Drawing No. 0D8446-C  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
0C6934  
0D8062H  
0D8057H  
0C6043A  
0D8274  
0D6634A  
0D3220  
0D8314  
056482  
0C3168  
0D8313  
0D1846  
0C7038  
0D1647  
0D2558  
0C7038A  
0C7758  
0388050AD0  
0C2417A  
082121C  
066386  
029451  
049451  
022237  
022511  
022131  
039288  
022145  
049820  
045756  
022129  
022259  
059637  
0D4662  
074994  
057822  
0F0462  
0C2824  
025145  
0C4138  
048031C  
030340  
048031C  
030340  
1
1
1
1
1
1
1
1
1
3
1
4
1
1
1
1
ADAPTOR, ENGINE  
STATOR  
ROTOR  
CARRIER, REAR BEARING  
FAN, 12" CURVED BLADE  
MUFFLER  
TAIL PIPE, MUFFLER  
PANEL, MUFFLER BASE  
BEARING 1.1811-2.8346  
5/16 SPECIAL LOCK WASHER  
BOLT, HHCS 3/8"-24 x 14.2"  
BOLT, HHCS M8-1.25 x 345mm  
BRACKET, ALTERNATOR MOUNTING  
DUCT, ALTERNATOR AIR  
GASKET, ALTERNATOR AIR DUCT  
BRACKET, ENGINE MOUNTING  
RUBBER MOUNT  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
41  
42  
4
1
1
1
CABLE, #6 48" BLACK BATTERY  
EARTH STRAP 3/8X 3/8  
CLIP-J, VYNL COAT 0.625" ID  
ASSEMBLY BRUSH HOLDER  
TAPE ELEC UL FOAM 1/8 X 1/2  
WASHER FLAT .406ID X 1.62OD  
WASHER LOCK 3/8  
SCREW HHC 3/8-16 X 1-1/4 G5  
WASHER FLAT 3/8 ZINC  
SCREW HHC M8-1.25 x 55 G8.8  
WASHER FLAT 5/16 ZINC  
NUT LOCK HEX M8-1.25 NYL INSERT  
SCREW TAPTITE M6-1.0X10 BP  
WASHER LOCK M8-5/16  
NUT HEX 5/16-18 STEEL  
SCREW TAPTITE 3/8-16 X 3/4 BP  
SCREW 5/16-18X3/4" HH THD ROLL  
HOSE RES 1/2 LP GAS  
CLAMP HOSE #8 .53 - 1.00  
NUT HEX W/TOOTH WSHR M8-1.25  
SCREW TAP-R #10-32 x 9/16  
U-BOLT 5/16"-18 X 1.25" WITH SADDLE  
GASKET, EXHAUST PORT  
CLAMP HOSE BAND 1/4"  
HOSE 1/4" I.D.  
1
1.8 FT  
1
5
4
4
4
14  
4
2
10  
8
2
4
3 FT  
4
4
3
1
2
2
1.33 FT  
2
1.33 FT  
CLAMP HOSE BAND 1/4"  
HOSE 1/4" I.D.  
®
Generac Power Systems, Inc. 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Engine – Drawing No. 0E8774-G Part 1  
®
36 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Engine – Drawing No. 0E8774-G Part 1  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
0C5729  
1
ASSEMBLY, CRANKCASE HOUSING  
WITH SLEEVE  
SEAL, 38 I.D. CRANKSHAFT  
SCREW, TAPTITE M6-1.0 X 12 YC  
ASSEMBLY, BREATHER  
GASKET, BREATHER COVER  
SEPARATOR, OIL BREATHER  
ASSEMBLY, HEAD #1 G&S  
RETAINER, PISTON PIN 20  
ROCKER, COVER NO OIL FILL  
STUD M8-1.25/10MM X 30 G5 ZINC  
PISTON, HC  
SET, PISTON RING 90MM  
PIN PISTON  
ASSEMBLY, CAMSHAFT & GEAR  
SHAFT, GOVERNOR  
ROLLER BEARING, GOVERNOR PLATE  
ROLLER BEARING, GOVERNOR  
ASSEMBLY,GOVERNOR GEAR  
SPOOL, GOVERNOR MACHINED  
GASKET, CRANK CASE  
SEAL, OIL PASSAGE  
ASSEMBLY, CRANKSHAFT HORIZONTAL  
DIRECT DRIVE  
ASSEMBLY, CONNECTING ROD  
SCREW SHC M6-1.0 X 50 G8.8  
SCREEN, OIL PICKUP  
ASSEMBLY, OIL PUMP  
SLEEVE, SEAMED DOWEL 10 DIA.  
COVER, OIL RELIEF  
SPRING, OIL RELIEF  
BALL, 1/2D OIL RELIEF  
37  
38  
39  
40  
41  
0C3971C  
0C5305  
0C3027  
0E9842  
0C5731  
1
1
1
1
1
ASSEMBLY, DIPSTICK WITH HANDLE  
TUBE, DIPSTICK  
O-RING, OIL CLR 3/8 X 1/2  
SEAL, 42 I.D. CRANKSHAFT  
ASSEMBLY, HOUSING COVER WITH  
SLEEVE  
SCREW, HHFC M10-1.5 X 55  
SCREW HHFC M6-1.0 X 25  
ASSEMBLY, OIL FILL CAP  
HOOK, LIFTING  
ROCKER, COVER WITH OIL FILL  
GASKET, VALVE COVER  
KEEPER, VALVE SPRING  
RETAINER, VALVE SPRING  
SPRING, VALVE  
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16A  
16B  
17  
18  
19  
20  
21  
0E9843  
090388  
1
3
1
1
3
1
4
1
4
2
2
2
1
1
2
1
1
1
1
1
1
0C5372  
0C3005  
0E3372B  
0D8067A  
071983  
0C2981C  
045761A  
0E2985  
021533  
0E1466  
0D4041  
0C2983  
0C2985A  
0C2985B  
0D4042  
0A7811  
0C2977  
0C5943  
0E4357E  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
0C3006  
080318  
093064  
0C8808  
0D2723B  
0C2979  
086515  
0D2274  
0D3867  
078672  
0C5371  
072694  
0D3998  
0C3027  
0D5313  
0D6024  
0C2976  
086516  
0C2229  
083897  
0D8067B  
0D9853D  
0C2978  
043790A  
9
8
1
2
1
2
8
4
4
2
4
4
4
2
4
2
12  
2
2
4
1
4
2
1
SEAL, VALVE STEM D7  
WASHER, VALVE SPRING  
STUD, ROCKER ARM PIVOT  
NUT HEX M8-1.0 G8 YEL CHR  
O-RING, 3/8" X 1/2"  
ROCKER ARM  
PLATE, PUSH ROD GUIDE  
SCREW HHFC M8-1.25 X 65  
VALVE, EXHAUST  
VALVE, INTAKE  
TAPPET, SOLID  
ASSEMBLY, HEAD #2 G&S  
PUSHROD, 147  
GASKET, HEAD  
BARBED ELBOW 90 3/8NPT X 3/8  
L0CKTITE  
KIT GASKET  
KIT PISTON & RINGS  
KIT BREATHER ASSEMBLY  
KIT GOVERNOR ASSEMBLY  
KIT HEAD ASSEMBLY CYLINDER 1  
KIT HEAD ASSEMBLY CYLINDER 2  
KIT OIL RELIEF  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
0E3223  
0D2157  
0E6098  
0D4123A  
078699E  
0C3011  
0C3009  
0C3010  
093873  
0C5315  
0C5998  
0D1667  
0C2991  
0C2988  
0C2992  
2
2
1
1
2
2
2
2
2
1
1
1
2
1
1
66  
67  
68  
69  
70  
71  
72  
73  
0D4010  
0D4011  
0D4012  
0D4013  
0D8675A  
0D8675B  
0D4015  
0D4016  
1
1
1
1
1
1
1
1
WASHER, LOCK RIB M6  
GEROTOR, OUTER  
CLAMP, OIL TUBE  
ARM, GOVERNOR  
E-RING, GOVERNOR ARM  
THRUST WASHER, GOVERNOR  
BUSHING, GOVERNOR LOWER  
KIT GEAR COVER  
®
Generac Power Systems, Inc. 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Engine – Drawing No. 0E8774-G Part 2  
74  
138  
75  
139  
135  
122  
124  
125  
123, 145  
125  
76  
77  
136  
137  
120  
79  
124  
133  
116  
134  
142  
78  
32  
119  
143  
80  
115  
127  
114  
11  
121  
118  
8
81  
29  
8
130  
126  
99  
96  
95  
83  
102  
84  
109  
103  
105  
86  
85  
88  
110  
99  
1
89  
90  
101  
89  
91  
107  
108  
112  
92  
112  
113  
111  
®
38 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Engine – Drawing No. 0E8774-G Part 2  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
74  
75  
76  
77  
78  
0C5136A  
0C3024  
0C3040  
0C8127  
0D8564A  
0D8564B  
0D2595  
0D4417  
0C3025  
0D3083  
0C7292  
070185B  
075281  
0F2094  
2
1
1
1
1
1
4
4
1
1
1
1
1
2
KNOB, AIR CLEANER  
COVER, AIRBOX NG/LP  
PRE-CLEANER,  
ELEMENT, AIR CLEANER  
ASSEMBLY, MIXER/AIRBOX 990  
ASSEMBLY, MIXER/AIRBOX 760  
SCREW SHOULDER (8MM) M6-1.0 X 18  
WASHER,RUBBER 1/4" X 1/8" THICK  
SWITCH, OIL PRESS  
ASSEMBLY, OIL DRAIN HOSE  
NIPPLE, 3/4"-16 UNF  
OIL FILTER  
SWITCH, THERMAL 284F  
SCREW, M3-0.5 X 6 SEMS  
110  
111  
112  
0C3022A  
0D1131  
045756  
1
1
25  
HOUSING, BLOWER NG COOLER  
GUARD, FAN  
SCREW TAPTITE M6-1X10 YELLOW  
CHROME  
NUT, GROMMET 1/4 PLUG  
HOSE, BREATHER  
WASHER FLAT 5/16-M8 ZINC  
WASHER LOCK M8-5/16  
WRAPPER, UPPER CYLINDER 1  
WRAPPER, LOWER CYLINDER 1  
WRAPPER, LOWER CYLINDER 2  
WRAPPER, UPPER CYLINDER 2  
SCREW TAPTITE M5-0.8 X 8 ZP  
ASSEMBLY, GROUND WIRE  
ASSY, IGN COIL W/DIODE NO ADV  
WASHER LOCK M6-1/4  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
0C9763  
0C3036A  
022145  
022129  
0C3018  
0C3019  
0D1142A  
0D1143  
0E6043  
0F1177  
0F1338B  
022097  
092079  
0E4271  
0D4529  
022129  
061906  
082774  
0E5343  
0C8468  
0C3048  
0D3754  
0D3742  
0C8482  
0E0486  
0D3743  
0D3705  
4
1
1
1
1
1
1
1
2
1
1
4
4
1
2
2
2
1
1
1
1
1
1
1
1
1
1
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
035461A  
2
BARBED STR 1/4NPT X 3/8 WITH VIBRA  
SEAL  
CLAMP HOSE .38-.87  
HOSE, 3/8" I.D. X 6" LONG  
COOLER, OIL  
PLASTITE,1/4-15 X 3/4  
GASKET, MANIFOLD / PORT  
MANIFOLD CYLINDER 2  
MANIFOLD CYLINDER 1  
SLEEVE, RUBBER  
WASHER FLAT M8 SS  
WASHER LOCK M8 SSTL  
SCREW SHC M8-1.25 X 20 G12.9  
PLATE, BACKING WITH OIL COOLER  
GROUND WIRE CONNECTOR  
FLYWHEEL ASSEMBLY  
FAN, NYLON  
SCREW TAPTITE M6-1.0 X 25 BP  
STARTER  
SPARKPLUG  
89  
90  
91  
92  
93  
94  
95  
96  
97  
0C7649  
0C9806  
0C3026  
0C9764  
0C3043  
0C7694  
0C7693  
0C3041A  
070008  
070006  
040976  
0C3016A  
0E4997  
0C3725B  
0C3031  
0C3032  
0A5992  
051754  
0C3033  
0C3034  
0C8549A  
4
2
1
4
2
1
1
2
4
4
4
1
1
1
1
1
2
2
1
1
1
WASHER LOCK M8-5/16  
SCREW HHC M8-1.25 X 85 G8.8  
KEY, WOODRFF 4 X 19D  
NUT HEX LOCK M10-1.50  
SPRING, ANTI-LASH  
ROD, GOVERNOR CONTROL  
ASSEMBLY, GOVERNOR LEVER  
SPRING, GOVERNOR  
ASSEMBLY, GOVERNOR ADJUSTER  
SCREW SHC M10-1.5 X 75 G10.9  
SPRING, GOVERNOR IDLE  
ASSEMBLY, GOVERNOR ADJUSTER  
BRACKET  
SEAL, GOVERNOR SHAFT  
NUT HEX M8-1.25 G8  
SCREW HHFC M6-1.0 X 10mm  
O-RING 0.49" I.D. X 0.07" THICK  
ASSY, IGN COIL W/DIODE NO ADV  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
PLATE, FAN  
140  
142  
143  
144  
145  
0C2993  
045771  
0D6147  
0E8152  
0F1338A  
1
1
7
1
1
WASHER SHAKEPROOF INT M8 SS  
SCREW HHC M8-1.25 X 12 G8.8  
WASHER, 25mm I.D.  
NUT,HEX M24  
SNORKEL, AIR INTAKE  
®
Generac Power Systems, Inc. 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Control Panel Assembly – Drawing No. 0E7974-F  
®
40 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Control Panel Assembly – Drawing No. 0E7974-F  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
0E7886A  
0E7886C  
1
1
CIRCUIT BREAKER 30A X 2P 240V (7KW)  
CIRCUIT BREAKER 40A X 2P 240V  
(8.5KW)  
CIRCUIT BREAKER 45A X 2P 240V  
(11KW)  
CIRCUIT BREAKER 50A X 2P 240V  
(12KW)  
CIRCUIT BREAKER 60A X 2P 240V  
(13KW)  
CIRCUIT BREAKER 70A X 2P 240V  
(15KW)  
ASSEMBLY, BATTERY CHARGER  
ENGINE  
ASSEMBLY, POTTED REGULATOR  
RELAY, 12V 25A SPST  
BLOCK 1 POSITION  
22  
23  
0D5240  
0D9784  
0D9784  
1
6
4
SWITCH, SPST (ON)-ON N/O  
NUT HEX LOCK M3-0.5 NYLON INSERT  
NUT HEX LOCK M3-0.5 NYLON INSERT  
(7KW)  
NEUTRAL CONNECTOR  
HARNESS, CONTROL PANEL (NOT  
SHOWN)  
HARNESS, CONTROL PANEL WIRE (NOT  
SHOWN) (7KW)  
SCREW TAPTITE, M5-0.8 x 10 BP  
NUT HEX LOCK M5-0.8 NYLON INSERT  
TRANSFORMER  
SCREW HHC 1/4"-20 x 1/2"  
FUSE 5A X AGC5  
BLOCK TERMINAL STRIP 20A 4 X 6 X  
1100V  
RELAY PANEL 12VDC DPDT 10A 240VAC  
SCREW PPHM M4-0.7 x 10mm  
WASHER FLAT M4  
COVER, CONTROL PANEL COMPONENT  
COVER, CONTROL PANEL COMPONENT  
(7KW)  
SCREW PPHMS/LW #6-32 x 1/4"  
SCREW HHC M5-0.8 x10mm  
COVER, CONTROL PANEL  
COVER, CONTROL PANEL (7KW)  
NUT FLANGE M6-1.0 NYLOK  
ASSEMBLY, ROOF/DOOR GROUND WIRE  
SCREW HHTR 1/4"-20 X 3/4"  
WASHER LOCK SPECIAL 1/4"  
WASHER FLAT 1/4"-M6  
0E7886D  
0E7886E  
0E7886F  
0E7886G  
0A1801  
1
1
1
1
1
24  
26  
0D8502  
0D8441  
1
1
0E0120  
1
27  
29  
30  
31  
32  
33  
074908  
082025  
0C3910  
022507  
099727  
046689  
4
6
1
2
1
1
2
3
4
5
6
7
083049  
0C2174  
075210A  
0D3062  
0D8615  
1
1
1
4
1
HEX STAND-OFF #6-32 x 3/8"  
ASSEMBLY, HOME STANDBY  
CONTROLLER  
ASSEMBLY, HOME STANDBY  
CONTROLLER (7KW)  
34  
35  
36  
37  
063617  
075475  
043180  
0D8439  
0E0119  
1
4
2
1
1
0D8615A  
1
8
9
10  
11  
032300  
022676  
0E4494  
0E7890  
2
1
1
1
HOLDER, FUSE  
FUSE, 15AMP X AGC15  
SWITCH, ROCKER DPDT ON-OFF-ON  
CIRCUIT BREAKER MOUNTING  
BRACKET  
38  
39  
40  
092036  
045770  
0E7866  
0E7867  
0D3700  
0912970069  
0E2874  
0A1658  
022473  
038750  
022097  
049813  
031879  
031879  
023897  
8
2
1
1
8
1
1
2
3
1
3
1
6
4
2
12  
13  
15  
17  
18  
19  
023484E  
075476  
0E6480  
0C1085  
0D8443  
054502  
053623  
1
4
6
4
1
1
1
SNAP BUSHING  
41  
42  
43  
44  
45  
46  
47  
48  
49  
SCREW PPHM M4-0.7 x 16mm  
NUT HEX LOCK M4-0.7 NYLON INSERT  
SCREW PPHM M3-0.5 X 8mm  
DECAL, CONTROL PANEL (NOT SHOWN)  
CIRCUIT BREAKER 3 X 1 ETA 46-500-P  
CIRCUIT BREAKER 2.5 X 1 ETA 46-500-P  
(7KW)  
CONTROL, PANEL BOTTOM  
CONTROL, PANEL BOTTOM (7KW)  
SCREW HHC M5-0.8 x 30mm  
SCREW HHC M6-1.0 x 30mm  
WASHER LOCK M6-1/4"  
NUT HEX M6-1.0  
WASHER FLAT #4  
WASHER FLAT #4 (7KW)  
WASHER FLAT #10  
20  
21  
0E7870  
0E7871  
075235  
1
1
4
50  
®
Generac Power Systems, Inc. 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
GTS Load Center – Drawing No. 0E7973-B  
12  
31  
37  
7
9
6
11  
5
2
3A  
22  
3
39  
9
27  
36  
15  
24  
20  
10  
13  
1
19  
3B  
16  
22  
26  
17  
40  
21  
23  
18  
38  
14  
8
33  
32  
34  
38  
34  
®
42 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
GTS Load Center – Drawing No. 0E7973-B  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
3A  
3B  
3C  
3D  
4
5
6
7
8
0D3086  
0D3092  
0C2237  
077220  
077220A  
082574  
084464  
074908  
024912  
0A1658  
063617  
0E7889  
0A1495  
0A1661  
022473  
055450  
0D4684  
0E7900  
056326  
022152  
064526  
0E6155  
063378  
0D3094  
074138  
036933  
077033  
048850  
028739  
0A2110  
0D3191  
0D3088  
073591  
073590A  
040213B  
0E7888C  
0E7888  
0E7888B  
0E7888A  
0D3320  
0D3093  
0D8597  
075475  
0A7215  
0E6193  
1
1
1
1
1
1
1
6
1
1
1
1
4
2
1
1
1
BOX GTS LOAD CENTER  
COVER, 12 POSITION GTS LOAD CENTER  
TRANSFER SWITCH HOME STANDBY 100A 2P 250V  
COIL UTILITY  
COIL STANDBY  
INSULATOR-SIDEWALL (NOT SHOWN)  
LIMIT SWITCH OPERATION (NOT SHOWN)  
SCREW HHTT M5-0.8 X 10  
SCREW HHTT 1/4-20 X 5/8  
LOCK WASHER, SPECIAL-1/4"  
RELAY PANEL 12VDC DPDT 10A@240VAC  
12 CIRCUIT LOAD CENTER 125A/240V  
SCREW HHTT M4-0.7 X 10  
RIVET POP .156" X .675"  
WASHER FLAT 1/4-M6 ZINC  
PLUG PLASTIC 1.375  
HARNESS ADAPTER PLATE  
SUBPLATE, LOAD CENTER  
TRIM VINYL BLACK 1/8"GP  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
1
10.5"  
6
2
1
4
1
2
6
6
1
4
4
1
1
2
2
4
3
1
5
1
1
1
1
2
WASHER LOCK #10  
SCREW HWHS #6-25 X 3/8"  
ARM EXTENDER PIN  
HOLDER CABLE TIE  
HARNESS,GTS TO MAIN PANEL  
LUG QUICK DISCONNECT NI-S 10X45 DEG BRASS / TIN  
SCREW PPHM #10-32 X 3/8"  
LUG SLDLSS 1/0-#14X9/16 AL/CU  
BLOCK TERMINAL 20A 5 X 6 X 1100V  
TIE WRAP 3.9" X .10"  
SCREW SWAGE 1/4-20 X 1/2" ZINC  
COVER, RELAY & TERMINAL BLOCK  
WIRE HARNESS,GTS LOAD CENTER (NOT SHOWN FOR CLARITY)  
FUSE HOLDER  
FUSE 5A X BUSS  
PCB SUPPORT SNAP-IN 1-3/8"  
CIRCUIT BREAKER 20A 1P  
CIRCUIT BREAKER 20A 2P  
CIRCUIT BREAKER 15A 1P  
CIRCUIT BREAKER 30A 2P  
COVER - HARNESS ENTRY  
HARNESS, GTS TO EXT CONN BOX  
HARNESS, GTS TO EXT CONN BOX (8.5KW)  
SCREW PPHM M4-0.7 X 10  
SCREW SW 1/4"-20 X 5/8" WITH WASHER  
BRACKET, ARM EXTENDER  
38  
39  
40  
4
1
®
Generac Power Systems, Inc. 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Regulator – Drawing No. 0D8720-D  
®
44 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Exploded Views and Parts Lists  
Air-cooled 8.5 kW Generator  
Regulator – Drawing No. 0D8720-D  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
0D5694  
0F3154  
0C4647  
0D4166  
0C6070  
043180  
022264  
075475  
0C5760E  
0C6606  
097934  
0C4645  
0C5761  
0C5968  
0C6066  
0C5759  
0C5764  
0C5764A  
070728  
0C6069  
0C5762  
045764  
0C6731  
0C6067  
0C4706  
0C6068  
0C4643A  
026073  
026073  
0A4032  
0D3308  
024310  
028414A  
0D5698A  
0D3973  
1
1
1
1
1
4
4
4
1
2*  
2*  
2*  
2
2
2
2
2
2
4
2
2
16  
2
2
2
2
2
1
2
2*  
4
1
1
CASTING, TWIN REGULATOR HOUSING  
SOLENOID COIL, 12VDC  
GASKET , SOLENOID  
PLUNGER, LP REGULATOR ASSEMBLY  
SPRING-SOLENOID, PLUNGER  
WASHER, FLAT M4  
WASHER, LOCK M4  
SCREW PPHM M4-0.7 X 10  
JET, GN 410 ENGINE LP (7KW)  
BARBED STRAIGHT 1/2NPT x 1/2  
O-RING, CHECK VALVE  
ADJUSTER SCREW, TWIN REGULATOR  
LEVER, REGULATOR  
SUPPORT, INLET SEAL  
SEAL, INLET  
PIN, PIVOT ARM  
SPRING, REGULATOR  
SPRING, REGULATOR (7KW)  
SCREW, PFHMS M3-0.5 x 5  
GASKET, DIAPHRAGM  
COVER, TWIN REGULATOR  
SCREW, TAPTITE M4X8 BP  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
RIVET, POP .118 X .125  
SUPPORT, DIAPHRAGM  
DIAPHRAGM, TWIN REGULATOR  
CAP, D I APHRAGM SUPPORT  
INLET, TWIN REGULATOR 11.11 DIA.  
PLUG, STANDARD PIPE 1/8" STEEL SQUARE HEAD  
PLUG, STANDARD PIPE 1/8" STEEL SQUARE HEAD (7KW)  
PIN, LIMITED ADJUSTMENT  
WASHER, FLAT M3 X 10mm O.D.  
PLUG, STANDARD PIPE 1/2" STEEL SQUARE HEAD (7KW)  
BARBED STRAIGHT 1/8"NPT X 1/4"  
JET IDLE PRIMER PHILLIPS HD (V-TWIN ONLY)  
PLUG, EXPANSION 16mm  
28  
29  
30  
31  
32  
37  
1
1
* A QUANTITY OF 1 IS TO BE USED ON 7KW HOME STANDBY  
®
Generac Power Systems, Inc. 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Notes  
Air-cooled 8.5 kW Generator  
®
46 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Notes  
Air-cooled 8.5 kW Generator  
®
Generac Power Systems, Inc. 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Air-cooled 8.5 kW Generator  
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.  
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT  
YOUR WARRANTY RIGHTS AND OBLIGATIONS  
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission  
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be  
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control  
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modifi-  
cation or improper maintenance of your engine.  
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will  
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.  
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:  
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, dur-  
ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or  
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.  
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:  
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory  
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance  
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the  
completion of all scheduled maintenance.  
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or  
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unap-  
proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.  
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs. The  
warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.  
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.  
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:  
1-800-333-1322  
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System  
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited  
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by  
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms  
between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the  
Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe impor-  
tant rights and obligations with respect to your new engine.  
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty serv-  
ice, evidence must be presented showing the date of the sale to the original purchaser/owner.  
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the fol-  
lowing address:  
ATTENTION WARRANTY DEPARTMENT  
GENERAC POWER SYSTEMS, INC.  
P.O. BOX 297  
WHITEWATER, WI 53190  
Part 1  
®
48 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Air-cooled 8.5 kW Generator  
EMISSION CONTROL SYSTEM WARRANTY  
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:  
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on  
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con-  
tinue for 24 consecutive months thereafter.  
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or  
equipment and to each subsequent purchaser/owner that each of its engines is ...  
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its  
authority, and  
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-  
ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine man-  
ufacturer’s application for certification.  
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:  
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s  
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall  
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the  
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual  
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or  
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS  
Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s  
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part  
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection  
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the  
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.  
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no  
charge to the owner at a Generac Authorized Warranty Service Facility.  
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsi-  
ble for diagnostic costs if the repair is deemed warrantable.  
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused  
by a failure under warranty of any emission-related part covered by the ECS Warranty.  
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient  
to meet the expected demand for such emission-related parts.  
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS  
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac  
ECS Warranty obligations.  
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac  
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.  
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of  
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.  
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:  
1) Fuel Metering System:  
3) Ignition System including:  
a) Spark plug  
b) Ignition module  
1.2) LPG/Natural Gas carburetion assembly and its internal  
components.  
a) Fuel controller (if so equipped)  
4) Catalytic Muffler Assembly (if so equipped) including:  
a) Muffler gasket  
b) Exhaust manifold  
b) Mixer and its gaskets (if so equipped)  
c) Carburetor and its gaskets (if so equipped)  
d) Primary gas regulator (if so equipped)  
e) LP liquid vaporizer (if so equipped)  
5) Crankcase Breather Assembly including:  
a) Breather connection tube  
2) Air Induction System including:  
a) Intake pipe/manifold  
b) Air cleaner  
*Generac engine types covered by this warranty statement include the following:  
1) Prepackaged Standby Generator  
2) Auxiliary Power Unit (APU) Generator  
3) Standby Generator  
Part 2  
®
Generac Power Systems, Inc. 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Air-cooled 8.5 kW Generator  
GENERAC POWER SYSTEMS "TWO YEAR" LIMITED WARRANTY FOR CENTURION  
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"  
For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace  
any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to  
be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equipment that the pur-  
chaser/owner claims to be defective must be examined by the nearest Generac Authorized Warranty Service Dealer. All transportation  
costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies  
only to Generac Centurion prepackaged emergency automatic standby generators sold and rated for use in "Standby" applications.  
WARRANTY SCHEDULE  
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and main-  
tenance is required):  
• Engine - All Components  
Alternator - All Components  
Transfer System - All Components  
Steel enclosures are warranted against rusting for the first year of ownership only. Damage caused after receipt of generator is the  
responsibility of the owner and is not covered by this warranty. Nicks, srapes, dents or scratches to the painted enclosure should be  
repaired promptly by the owner.  
All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat Rate  
Manual.  
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:  
• Generac Centurion generators that utilize non-Generac replacement parts.  
• Generac Centurion generators utilizing non-Generac transfer switches.  
Repairs performed by individuals other than Centurion/Generac authorized dealers.  
Any Generac Centurion generators used as rental or trailer mounted applications.  
Air-cooled units used for prime power in place of existing utility power where utility power is present or in place of utility power  
where utility power service does not normally exist.  
Steel enclosures that are rusting due to the improper installation, location in a harsh or saltwater environment or scratched where  
integrity of paint applied is compromised.  
• Costs of normal maintenance, adjustments, installation and start-up.  
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.  
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all  
mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not  
cover repair when normal use has exhausted the life of a part(s) or engine.  
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freez-  
ing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.  
• Damage related to rodent and/or insect infestation.  
• Products that are modified or altered in a manner not authorized by Generac in writing.  
Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replace-  
ment of the defective part(s).  
• Failure due to misapplication.  
Telephone, cellular phone, facsimile, internet access or other communication expenses.  
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty  
period.  
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.  
Rental equipment used while warranty repairs are being performed.  
• Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e., cranes, hoists, lifts, etc,)  
• Overnight freight costs for replacement part(s).  
• Overtime labor.  
Starting batteries, fuses, light bulbs and engine fluids.  
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES  
NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not  
allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.  
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT  
SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A  
DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential  
damages, so the above limitation may not apply to you.  
This warranty gives you specific legal rights. You also have other rights from state to state.  
®
GENERAC POWER SYSTEMS, INC.  
P.O. BOX 297 • WHITEWATER, WI 53190  
Revision 10/01/04  
Part No. 0F0091  
Revision B (11/15/04)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Earthquake Sound Speaker MC6 User Manual
Elation Professional DJ Equipment OPTI 30 RGB User Manual
Fisher Price Baby Monitor M7933 User Manual
Frigidaire Microwave Oven CPLMV169 User Manual
Frymaster Fryer 8195915 User Manual
FujiFilm Camera Lens YF8A SA2B User Manual
Garmin GPS Receiver 1000 800 User Manual
GE Clothes Dryer DCCB330GG User Manual
GE Monogram Ventilation Hood ZV30 User Manual
Gianni Industries Door GK310 1224 User Manual