GM Oxygen Equipment MANTS420 User Manual

Model TS420  
Oxygen Deficiency Detector  
The information and technical data disclosed in this  
document may be used and disseminated only for the  
purposes and to the extent specifically authorized in  
writing by General Monitors.  
Instruction Manual  
11/00  
General Monitors reserves the right to change  
published specifications and designs without prior  
notice.  
*MANTS420*  
Part No.  
Revision  
MANTS420  
B/11-00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
System Integrity Verification  
General Monitors mission is to benefit society by providing solutions through industry leading  
safety products, services and systems that save lives and protect capital resources from the  
dangers of hazardous flames, gases and vapors.  
The safety products you have purchased should be handled carefully and installed, calibrated  
and maintained in accordance with the respective product instruction manual. Remember  
these products are for your safety.  
To ensure operation at optimum performance General Monitors recommends that certain  
maintenance items are performed.  
Commissioning Safety Systems  
Before power up, verify wiring, terminal connections and stability of mounting for all integral  
safety equipment including, but not limited to:  
!
!
!
!
!
Power supplies  
Control modules  
Field detection devices  
Signaling / output devices  
Accessories connected to field and signaling devices  
After the initial application of power (and any factory specifies warm-up period) to the safety  
system, verify that all signal outputs, to and from devices and modules, are within the  
manufacturers’ specifications. Initial calibration / calibration checking / testing should be  
performed per the manufacturers’ recommendations and instructions.  
Proper system operation should be verified by performing a full, functional test of all component  
devices of the safety system, ensuring that the proper levels of alarming occur.  
Proper system operation should be verifies by performing a full, functional test of all component  
devices of the safety system, ensuring that the proper levels of alarming occur.  
Fault/Malfunction circuit operation should be verified.  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Periodic Testing/Calibration of Field Devices  
Periodic testing/calibrating should be performed per the manufacturers’ recommendations and  
instructions. Testing/Calibrating procedures should include, but not be limited to:  
!
!
Verify zero reading  
Apply a known concentration of gas, or a simulated test device provided by the  
manufacturer  
!
!
Verify integrity of all optical surfaces and devices  
For flame detectors, use the appropriate test lamp  
When testing produces results outside of the manufacturers’ specifications, re-calibration or  
repair/replacement of the suspect device(s) should be performed as necessary. Calibration  
intervals should be independently established through a documented procedure, including a  
calibration log maintained by plant personnel or third party testing services.  
Periodic System Verification  
The following system verifications should be performed at least annually:  
Verify wiring, terminal connections and stability of mounting for all integral safety equipment  
including, but not limited to:  
!
!
!
!
!
Power supplies  
Control modules  
Field detection devices  
Signaling / output devices  
Accessories connected to field and signaling devices  
Proper system operation should be verified by performing a full, functional test of all component  
devices of the safety system, ensuring that the proper levels of alarming occur.  
Fault/Malfunction circuit operation should be verified.  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Quick Start Guide  
1. Mount and Wire the Detector (pages 5 through 9)  
There are no standard rules for detector placement since the optimum sensor location is  
different for each application. The customer must evaluate conditions at the facility to make this  
determination. Generally, the TS420 should be easily accessible for calibration checks. The  
TS420 should be mounted pointing down to prevent water build-up on the detector head. The  
detector assembly should not be placed where it may be coated by contaminating substances.  
Although the Model TS420 is RFI resistant, it should not be mounted in close proximity to radio  
transmitters or similar equipment.  
Some general guidelines for sensor location:  
!
The TS420 should be used in locations that are tightly enclosed with poor or no  
ventilation, such as utility tunnels or underground storage areas. These areas are likely  
to have dangerously low oxygen concentrations.  
!
Observe the TS420’s environmental specifications when locating the unit.  
The environmental specifications covering the electrochemical cell are found in the Appendix,  
Section 5.1.4.  
Detectors should be mounted in an area that is as free from wind, dust, water, shock and  
vibration as possible.  
WARNING - Operation above or below temperature limits will provide unstable readings, which  
may cause false alarms or failure to alarm. See Section 5.1.4 for guidelines.  
General Monitors discourages painting of detector assemblies. If the detector head is painted  
over, the gas will not be able to diffuse into the sensor. If the TS420 body is painted over, the  
LCD display cannot be read.  
The TS420 is shipped without the sensor installed. The sensor must be installed into the  
detector and calibrated for proper operation. See Sections 3.3 and 3.4 for installation  
instructions and Section 4.3 for calibration instructions.  
Once correctly installed, the TS420 requires little or no maintenance other than periodic  
calibration checks to ensure system integrity. General Monitors recommends a calibration  
check schedule be established and that the complete system, including all alarm circuitry, be  
tested at least annually.  
The overall and mounting dimensions for the TS420 (Figure Q-A) should be used when making  
installation determinations. Mechanical specifications can be found in the Appendix, Section  
5.1.2.  
4.50"  
3/4 NPT  
LOOP+ (RED)  
LOOP- (WHITE)  
Ø1.75"  
FRAME GROUND  
(GREEN/YELLOW)  
1 1/2-20 UN-2A  
Figure Q-A Outline and Dimensional Drawing  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Quick Start Guide  
Intrinsically Safe Barriers  
In order for the TS420 to be used with classified equipment inside of the hazardous area, it is  
necessary for the customer to purchase either a Galvanic or Zener Diode Barrier, which should  
be mounted in the non-classified area between the TS420 and the facilities’ control room. A list  
of recommended manufacturers and part numbers follows for galvanic barriers:  
Stahl - 9303/11-22-11  
MTL - MTL7206 or MTL5041  
Pepperl+Fuchs - KFD2-CR-EX1.30-300  
Elcon - mD323 or mD325  
Turck - mk33-Li-ExO  
These are recommended active type barriers for intrinsically safe applications. Each application  
is different and it is the ultimate decision of the user to determine the appropriate I/S barrier for  
their application.  
NOTE - To maintain intrinsic safety, wire length and gauge are limited by the capacitance and  
inductance of the wire, Ci and Li of the TS420, and the barrier ratings. See Section 5.1.5 for  
instructions on calculating these values.  
Align the TS420 so that the LCD display is easily viewed. Teflon tape may be used on the  
TS420’s threads.  
The two wires at the base of the TS420 provide a 4-20mA loop-powered output. The red wire  
is the “loop +” lead and the white wire is the “loop -” lead (Figure Q-B). A third green/yellow  
wire is provided for frame ground.  
JUNCTION BOX  
LOOP + (RED)  
RED  
CONTROL  
WHITE  
TS420  
ROOM  
GRN/YEL  
LOOP - (WHITE)  
Figure Q-B Wiring Diagram  
It is recommended that a two wire, shielded cable be used for making power and output signal  
connections on the TS420.  
Connect the green/yellow frame ground wire to the grounding terminal or lug inside the junction  
box being used with the TS420.  
Ensure the junction box frame is connected to frame ground or connected to the cable shield,  
which is connected to frame ground at the controller.  
Connect the red wire to the +24VDC terminal. Connect the white wire to the signal input  
terminal on the readout/relay display module, FMD Field Mounted Display, S4100E smart  
sensor, industrial analog to digital converter, computer-based monitor, PLC, DCS, etc.  
Since the TS420 is designed to operate continuously, a power switch is not included, in order to  
prevent accidental system shutdown.  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Quick Start Guide  
NOTE - Power must remain disconnected until all wiring connections are made.  
The absolute maximum distance between the TS420 and the power supply is 8000 feet (2438  
meters). Depending on the application, general purpose or intrinsically safe, the cable length  
will depend on the intrinsically safe barrier chosen and the cable used. See the Appendix,  
Section 5.1.5, for the intrinsically safe system requirements. In addition, cable length  
specifications can also be found in the Appendix, Section 5.1.3. In all cases, the cable run  
should be as short as possible.  
2. Apply power to the detector.  
Before applying power to the system for the first time, all wiring connections should be checked  
for correctness. The sensor should be allowed to stabilize prior to calibration. The stabilization  
time should be one (1) hour for all sensors.  
Initial Power-up  
The TS420 has been shipped un-calibrated, therefore, the first time power is applied, the  
TS420 will enter Start-up mode (3.6mA) for a short interval, then may transition to fault mode  
(flashing MODE LCD with the CAL LCD off and the analog output current at 3.5mA) until  
calibrated (See Section 4.3 for Calibration Procedure).  
After calibration is complete, the TS420 will proceed to Operate mode (17.38mA = 20.9% V/V  
O2) where any detected oxygen will show as a proportional analog output current between 4  
and 20mA (4mA = 0% V/V O2, 20mA = 25% V/V O2). The MODE LCD will be on steady and the  
CAL LCD off with normal atmosphere and both the MODE and CAL LCD's will flash when  
oxygen deficiency is detected. (O2 level < 19%).  
General Monitors recommends the TS420 be calibrated again within the first twenty-four (24)  
hours after the initial calibration. Calibrations should be performed with new units and units that  
have been off power for more than one (1) week. See “Calibration”, Section 4.3, for more  
details.  
Power-up After Initial Calibration  
When the TS420 is powered up, after it has been previously calibrated, the unit will enter a  
Start-up mode (3.6mA) for approximately 50 seconds, which allows the sensor to stabilize  
before proceeding to the Operate mode (17.38mA). During Start-up, the “MODE” LCD will  
flash, the “CAL” LCD will be off and the analog output current will be 3.6mA.  
OPERATING MODES  
INDICATOR  
ANALOG OUTPUT  
3.6mA  
CAL  
MODE  
START-UP  
OPERATE  
AMBIENT O2 = 20.9%  
DEFICIENT ATMOSPHERE, O2< 19%1  
17.38mA  
4.0-16.16mA  
FAULT  
NO POWER  
SYSTEM  
0.0mA  
3.5mA  
Figure Q-C Operating Modes, Indicators and Outputs  
1. Segment may flash Synchronously or alternating.  
Perform a calibration and the TS420 will return to operate mode (17.38mA).  
NOTE - The TS420 will not allow you to enter calibration mode during Start-up mode (3.6mA).  
vi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Quick Start Guide  
3. Calibrate the Detector.  
Activating the “CAL” switch will automatically disable the external alarm circuits by fixing the  
analog output current to 3.75mA.  
General Monitors recommends that the TS420 be calibrated within the first twenty-four (24)  
hours after initial start-up, and that calibration be checked at least every ninety (90) days to  
ensure the integrity of the system.  
NOTE: A calibration check consists of applying a 20.9% V/V O2 (“normal” ambient air) of full-  
scale concentration of gas to the sensor and observing the reading on the display device being  
used.  
General Monitors is not implying that the customer should expect problems with sensor life or  
stability. “Frequent” calibration checks merely ensure the integrity of the life protecting  
equipment, and are recommended for problem environments (i.e. sensors accidentally being  
painted over, etc, see Appendix 5.4).  
A calibration schedule should be established and followed. A logbook should also be kept  
showing calibration dates and dates of sensor replacement.  
Calibration Procedure:  
1. If it is suspected that the air is not at “normal” levels (20.9% O2), it will be necessary to  
calibrate the sensor with clean air. The 20.9% O2 gas cylinder (GMI P/N 1400262-11) can be  
used. Apply the clean air source prior to entering calibration mode and allow the sensor to  
stabilize for at least one (1) minute before proceeding.  
2. Place the magnet over the GMI Logo on the body of the unit and hold it there until the “CAL”  
LCD indicator appears, then remove the magnet. The analog output current will drop to  
3.75mA.  
3. The CAL” and “MODE” LCD indicator will flash, indicating that the unit is now calibrating.  
4. After approximately 30 seconds, the display will change from a flashing “CAL” and “MODE”  
LCD to a solid “MODE” LCD, indicating that the calibration is complete and the unit has re-  
entered “OPERATE” mode. Remove any calibration gas.  
6. The unit is now calibrated and the new values have been stored in the NOVRAM (non-  
volatile memory).  
Figure Q-D shows a flow diagram of the codes that will appear in the display window during the  
calibration procedure.  
If there is a problem and the TS420 cannot complete the calibration sequence, a fault indicator  
will be displayed, and the analog output current will drop to 3.5mA.  
CALIBRATION  
INDICATOR  
CAL  
MODE  
Magnet Applied  
Magnet Recognized  
Cal Proceeding  
Figure Q-D Flow Diagram  
vii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Quick Start Guide  
NOTE - If the unit fails to calibrate a flashing “MODE” LCD will be displayed. The sensor must  
see “clean” air for at least fifteen (15) minutes before a second calibration is attempted by  
reapplying the magnet.  
The instrument is now ready to operate! Please consult the manual for more information  
on the instrument’s many features.  
If you have any problems in the set-up or testing of the detector, please refer to the “Trouble  
Shooting Section”, or call the factory direct.  
Worldwide Service is available by calling:  
Lake Forest, California  
(24 hr. service)  
Phone: +1-949-581-4464  
Fax: +1-949-581-1151  
Houston, Texas  
Ireland  
Phone: +1-281-855-6000  
Fax: +1-281-855-3290  
Phone: +1-353-91-751175  
Fax: +1-353-91-751317  
Singapore  
Phone: +1-65-748-3488  
Fax: +1-65-748-1911  
United Arab Emirates  
United Kingdom  
Phone: +1-971-4-8815751  
Fax: +1-971-4-8817927  
Phone: +1-44-1625-619-583  
Fax: +1-44-1625-619-098  
viii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Table of Contents  
WARRANTY STATEMENT  
..........................................................................................i  
System Integrity Verification .........................................................................................ii  
Commissioning Safety Systems......................................................................................ii  
Periodic Testing/Calibration of Field Devices ...............................................................iii  
Periodic System Verification ........................................................................................iii  
Table of Contents  
Table of Figures  
........................................................................................ix  
.........................................................................................x  
1.0  
Introduction  
.........................................................................................1  
1.1  
1.2  
1.3  
General Description...................................................................................1  
Features and Benefits ...............................................................................1  
Applications  
.........................................................................................1  
2.0  
3.0  
Detector Assembly  
.........................................................................................3  
2.1  
2.2  
Sensor Assembly.......................................................................................3  
Control Electronics ....................................................................................4  
Installation  
.........................................................................................5  
3.1  
3.2  
3.3  
Receipt of Equipment ................................................................................5  
Detector Location Considerations .............................................................5  
Installation Instructions..............................................................................6  
3.3.1 Intrinsically Safe Barriers..............................................................6  
3.3.2 Maintenance.................................................................................6  
Wiring Connections ...................................................................................7  
3.4  
4.0  
5.0  
Operation  
.........................................................................................8  
4.1  
4.2  
4.3  
4.4  
4.5  
4.6  
Applying Power .........................................................................................8  
Operating Modes.......................................................................................9  
Calibration  
Calibration Equipment .............................................................................10  
Sensor Replacement Procedure .............................................................11  
Sensor Care and Maintenance................................................................13  
.........................................................................................9  
Appendix  
.......................................................................................14  
5.1  
Specifications .......................................................................................14  
5.1.1 System Specifications ................................................................14  
5.1.2 Mechanical Specifications..........................................................14  
5.1.3 Electrical Specifications..............................................................14  
5.1.4 Environmental Specifications .....................................................15  
5.1.5 Intrinsically Safe System Requirements.....................................16  
5.1.6 Sample Calculation.....................................................................16  
Engineering Documentation....................................................................17  
5.2.1 Outline & Dimensional Drawing..................................................17  
5.2.2 Control Drawing..........................................................................18  
5.2.3 Sample Installation .....................................................................19  
5.2.4 Junction Boxes ...........................................................................20  
5.2.5 Splash-Guards............................................................................21  
5.2.6 Accessories ................................................................................22  
5.2.7 Calibration Accessories..............................................................22  
Ordering Information................................................................................23  
Calibration Schedule for Problem Environments.....................................24  
Spare Parts & Accessories......................................................................25  
5.2  
5.3  
5.4  
5.5  
ix  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Table of Figures  
Page  
Figure Q-A  
Figure Q-B  
Figure Q-C  
Figure Q-D  
Figure 1  
Figure 2  
Figure 3  
Figure 4  
Figure 5  
Figure 6  
Figure 7  
Figure 8  
Figure 9  
Outline and Dimensional Drawing......................................................................iv  
Wiring Diagram................................................................................................... v  
Operating Modes, Indicators and Outputs..........................................................vi  
Flow Diagram ....................................................................................................vii  
Model TS420 ...................................................................................................... 1  
Oxygen Deficiency Sensor Assembly ................................................................ 3  
LCD Display Location......................................................................................... 4  
Wiring Diagram................................................................................................... 7  
Operating Modes, Indicators and Outputs.......................................................... 8  
Flow Diagram ................................................................................................... 10  
Calibration Cup................................................................................................. 10  
Calibration Plug ................................................................................................ 10  
Change in % Oxygen in the atmosphere  
with Relative Humidity at constant Temperature................................. 11  
Sensor Alignment ............................................................................................. 12  
Calibration Kit with Bottle.................................................................................. 13  
Outline and Dimensional Drawing.................................................................... 17  
Control Drawing................................................................................................ 18  
Sample Installation ........................................................................................... 19  
10252 Round Aluminum Junction Box............................................................. 20  
31305-2 Aluminum Junction Box...................................................................... 20  
45160-1 Plastic Junction Box, NPT; 45160-2 Plastic Junction Box, M20........ 21  
70631-2 Splash - Guard................................................................................... 21  
45170-1 Flow Block.......................................................................................... 22  
45147-1 Flow Block Retainer ........................................................................... 22  
914-152 Calibration Plug.................................................................................. 22  
1400152-1 Calibration Cup .............................................................................. 22  
Figure 10  
Figure 11  
Figure 12  
Figure 13  
Figure 14  
Figure 15  
Figure 16  
Figure 17  
Figure 18  
Figure 19  
Figure 20  
Figure 21  
Figure 22  
Calibration Schedule for Problem Environments........................................................................ 24  
x
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
1.0 Introduction  
1.1 General Description  
The Model TS420 is a 4-20mA, loop-powered Oxygen Deficiency detector used for monitoring  
Oxygen levels. The micro-processor based electronics process information at the sensor site  
and are contained within a corrosion and solvent resistant plastic housing. An LCD display  
provides status indications that can be viewed through a window in the housing. The analog  
signal (0 to 25% V/V O2 full scale) provides remote and/or discrete indications of the sensor’s  
operation.  
The TS420 is entity-approved as intrinsically safe for use in Class I, Divisions 1 & 2, Groups A,  
B, C and D, Class II, Groups E, F and G & Class III hazardous areas. It can also be used in  
general-purpose (non-hazardous) applications.  
NOTE - Intrinsically safe applications require an I/S barrier mounted in a safe area. See  
Section 3.3.1 for guidelines.  
1.2 Features and Benefits  
Microprocessor-Based Electronics: monitors for fault conditions, processes input signals  
from the sensor and provides outputs in the form of display codes and an analog signal.  
One Person Adjustment-Free Calibration: initiate the calibration sequence with a magnet,  
apply 20.9% V/V O2, and wait for the display to indicate that the unit has completed the  
calibration. No user adjustments are required.  
Two Segment LCD: indicates gas presence, operational modes, fault codes and calibration  
cues.  
4 to 20 mA Output: transmits fault, calibration, and gas concentration levels to a remote  
display, computer or other device.  
1.3 Applications  
This is a partial listing of applications.  
!
!
!
!
!
!
!
!
Wastewater Treatment Plants  
Chemical and Petrochemical Plants  
Refineries  
Pulp & Paper Plants  
Micro-chip Manufacturing  
Pharmaceuticals  
Food & Beverage  
Utilities  
Figure 1 Model TS420  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
This page left intentionally blank  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
2.0 Detector Assembly  
2.1 Sensor Assembly  
General Monitors uses a two-electrode electrochemical cell (Figure 2) to provide a stable and  
accurate gas detector.  
Remove paper liner from gasket, if present.  
Figure 2 Oxygen Deficiency Sensor Assembly  
The oxygen sensor is of the self-powered, diffusion limited, metal air battery type. It contains an  
anode, electrolyte and an air cathode to which the diffusion of oxygen is severely restricted by a  
diffusion barrier. At the air cathode, oxygen is reduced to hydroxyl ions, which in turn oxidize  
the metal anode. This action produces a current that is proportional to the rate of consumption  
of oxygen.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
2.2 Control Electronics  
The Model TS420’s electronics are contained within a plastic housing so that sensor  
information can be processed at the point of detection. The Model TS420 provides a 4-20 mA  
output signal proportional to 0 to 25% V/V O2 full-scale gas concentration at the detector.  
Ambient Air is approximate 20.9% V/V O2. This level equals 17.38 mA. As the oxygen level  
decreases the 4-20 mA signal decreases.  
The TS420 provides a two-digit LCD (Liquid Crystal Display). This display (Figure 3) provides  
status such as gas present, fault and calibration cues to the operator. The MODE LCD is on  
steady during normal operation to show that the sensor is functioning properly.  
Monitored faults are: data memory failure, failed to calibrate and sensor removed.  
Engineering specifications covering the sensor cell and control electronics are found in the  
Appendix, Section 5.1.  
DISPLAY  
Figure 3 LCD Display Location  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
3.0 Installation  
3.1 Receipt of Equipment  
All equipment shipped by General Monitors is packed in shock absorbing containers, which  
provide considerable protection against physical damage. The contents should be carefully  
removed and checked against the packing slip. If any damage has occurred or if there is any  
discrepancy in the order, notify General Monitors as soon as possible. All subsequent  
correspondence with General Monitors must specify the equipment part number and serial  
number.  
Each TS420 is thoroughly checked by the factory. However, a complete check-out and initial  
calibration is necessary upon initial installation and start up to ensure system integrity.  
3.2 Detector Location Considerations  
There are no standard rules for detector placement since the optimum sensor location is  
different for each application. The customer must evaluate conditions at the facility to make this  
determination. Generally, the TS420 should be easily accessible for calibration checks. The  
TS420 should be mounted pointing down to prevent water build-up on the detector head. The  
detector assembly should not be placed where it may be coated by contaminating substances.  
Although the Model TS420 is RFI resistant, it should not be mounted in close proximity to radio  
transmitters or similar equipment.  
Some general guidelines for sensor location:  
!
The TS420 should be used in locations that are tightly enclosed with poor or no  
ventilation, such as utility tunnels or underground storage areas. These areas are likely  
to have dangerously low oxygen concentrations.  
!
Observe the TS420’s environmental specifications when locating the unit.  
The environmental specifications covering the electrochemical cell are found in the Appendix,  
Section 5.1.4.  
Detectors should be mounted in an area that is as free from wind, dust, water, shock and  
vibration as possible.  
WARNING - Operation above or below temperature limits will provide unstable readings, which  
may cause false alarms or failure to alarm. See Section 5.1.4 for guidelines.  
General Monitors discourages painting of detector assemblies. If the detector head is painted  
over, the gas will not be able to diffuse into the sensor. If the TS420 body is painted over, the  
LCD display cannot be read.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
3.3 Installation Instructions  
The TS420 is shipped without the sensor installed. The sensor must be installed into the  
detector and calibrated for proper operation. See Section 4.5 for installation instructions and  
Section 4.3 for calibration instructions.  
Once correctly installed, the TS420 requires little or no maintenance other than periodic  
calibration checks to ensure system integrity. General Monitors recommends a calibration  
check schedule be established and that the complete system, including all alarm circuitry, be  
tested at least annually.  
The overall and mounting dimensions for the TS420 (Figure 12) should be used when making  
installation determinations. Mechanical specifications can be found in the Appendix, Section  
5.1.2.  
3.3.1 Intrinsically Safe Barriers  
In order for the TS420 to be used with classified equipment inside of the hazardous area, it is  
necessary for the customer to purchase either a Galvanic or Zener Diode Barrier, which should  
be mounted in the non-classified area between the TS420 and the facilities’ control room. A list  
of recommended manufacturers and part numbers follows for galvanic barriers:  
Stahl - 9303/11-22-11  
MTL - MTL7206 or MTL5041  
Pepperl+Fuchs - KFD2-CR-EX1.30-300  
Elcon - mD323 or mD325  
Turck - mk33-Li-ExO  
These are recommended active type barriers for intrinsically safe applications. Each application  
is different and it is the ultimate decision of the user to determine the appropriate I/S barrier for  
their application.  
NOTE - To maintain intrinsic safety, wire length and gauge are limited by the capacitance and  
inductance of the wire, Ci and Li of the TS420, and the barrier ratings. See Section 5.1.5 for  
instructions on calculating these values.  
Align the TS420 so that the LCD display is easily viewed. Teflon tape may be used on the  
TS420’s threads.  
3.3.2 Maintenance  
The removal of particulate matter from sensor accessories may be done through the use of  
clean water only. Solvents should not be used. The accessories should be thoroughly dried,  
with compressed air if necessary, before refitting to the sensor body. Do not apply compressed  
air directly to the sensor.  
Some typical items to check during maintenance examinations are:  
!
!
!
!
The sensor mounting, to see it is secure.  
The sensor, to see it is clear of oil, water, dust or paint which might clog it.  
The cable connections for tightness and possible damage.  
All detector placements are up-to-date with the layout of the plant, e.g. modifications to  
the plant.  
!
The complete system, to see it has a back up supply for the full-prescribed time.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
3.4 Wiring Connections  
The two wires at the base of the TS420 provide a 4-20mA loop-powered output. The red wire  
is the “loop +” lead and the white wire is the “loop -” lead (Figure 4). A third green/yellow wire is  
provided for frame ground.  
It is recommended that a two wire, shielded cable be used for making power and output signal  
connections on the TS420.  
Connect the green/yellow frame ground wire to the grounding terminal or lug inside the junction  
box being used with the TS420.  
Ensure the junction box frame is connected to frame ground or connected to the cable shield,  
which is connected to frame ground at the controller.  
Connect the red wire to the +24VDC terminal. Connect the white wire to the signal input  
terminal on the readout/relay display module, FMD Field Mounted Display, S4100E smart  
sensor, industrial analog to digital converter, computer-based monitor, PLC, DCS, etc.  
Since the TS420 is designed to operate continuously, a power switch is not included, in order to  
prevent accidental system shutdown.  
NOTE - Power must remain disconnected until all wiring connections are made.  
The absolute maximum distance between the TS420 and the power supply is 8000 feet (2438  
meters). Depending on the application, general purpose or intrinsically safe, the cable length  
will depend on the intrinsically safe barrier chosen and the cable used. See the Appendix,  
Section 5.1.5, for the intrinsically safe system requirements. In addition, cable length  
specifications can also be found in the Appendix, Section 5.1.3. In all cases, the cable run  
should be as short as possible.  
JUNCTION BOX  
LOOP + (RED)  
RED  
CONTROL  
WHITE  
TS420  
ROOM  
GRN/YEL  
LOOP - (WHITE)  
Figure 4 Wiring Diagram  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
4.0 Operation  
4.1 Applying Power  
Before applying power to the system for the first time, all wiring connections should be checked  
for correctness. The sensor should be allowed to stabilize prior to calibration. The stabilization  
time should be one (1) hour for all sensors.  
Initial Power-up  
The TS420 has been shipped un-calibrated, therefore, the first time power is applied, the  
TS420 will enter Start-up mode (3.6mA) for a short interval, then may transition to fault mode  
(flashing MODE LCD with the CAL LCD off and the analog output current at 3.5mA) until  
calibrated (See Section 4.3 for Calibration Procedure).  
After calibration is complete, the TS420 will proceed to Operate mode (17.38mA = 20.9% V/V  
O2) where any detected oxygen will show as a proportional analog output current between 4  
and 20mA (4mA = 0% V/V O2 , 20mA = 25% V/V O2). The MODE LCD will be on steady and  
the CAL LCD off with normal atmosphere and both the MODE and CAL LCD's will flash when  
oxygen deficiency is detected. (O2 level < 19%).  
General Monitors recommends the TS420 be calibrated again within the first twenty-four (24)  
hours after the initial calibration. Calibrations should be performed with new units and units that  
have been off power for more than one (1) week. See “Calibration”, Section 4.3, for more  
details.  
Power-up After Initial Calibration  
When the TS420 is powered up, after it has been previously calibrated, the unit will enter a  
Start-up mode (3.6mA) for approximately 50 seconds, which allows the sensor to stabilize  
before proceeding to the Operate mode (17.38mA). During Start-up, the MODE LCD will flash,  
the CAL LCD will be off and the analog output current will be 3.6mA.  
OPERATING MODES  
INDICATOR  
ANALOG OUTPUT  
3.6mA  
CAL  
MODE  
START-UP  
OPERATE  
AMBIENT O2 = 20.9%  
DEFICIENT ATMOSPHERE, O2< 19%1  
FAULT  
17.38mA  
4.0-16.16mA  
NO POWER  
SYSTEM  
0.0mA  
3.5mA  
Figure 5 Operating Modes, Indicators and Outputs  
1.  
Segment may flash Synchronously or alternating.  
Perform a calibration and the TS420 will return to operate mode (17.38mA).  
NOTE - The TS420 will not allow you to enter calibration mode during Start-up mode (3.6mA).  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
4.2 Operating Modes  
The TS420 has four distinct operating modes: Start-up, Normal Operation, Calibration and  
Fault. The mode is indicated by both the analog output and the LCD display. See Figures 5  
and 6.  
4.3 Calibration  
Activating the “CAL” switch will automatically disable the external alarm circuits by fixing the  
analog output current to 3.75mA.  
General Monitors recommends that the TS420 be calibrated within the first twenty-four (24)  
hours after initial start-up, and that calibration be checked at least every ninety (90) days to  
ensure the integrity of the system.  
NOTE: A calibration check consists of applying a 20.9% V/V O2 (“normal” ambient air) of full-  
scale concentration of gas to the sensor and observing the reading on the display device being  
used.  
General Monitors is not implying that the customer should expect problems with sensor life or  
stability. “Frequent” calibration checks merely ensure the integrity of the life protecting  
equipment, and are recommended for problem environments (i.e. sensors accidentally being  
painted over, etc, see Appendix 5.4).  
A calibration schedule should be established and followed. A logbook should also be kept  
showing calibration dates and dates of sensor replacement.  
Calibration Procedure:  
1. If it is suspected that the air is not at “normal” levels (20.9% O2), it will be necessary to  
calibrate the sensor with clean air. The 20.9% O2 gas cylinder (GMI P/N 1400262-11) can be  
used. Apply the clean air source prior to entering calibration mode and allow the sensor to  
stabilize for at least one (1) minute before proceeding.  
2. Place the magnet over the GMI Logo on the body of the unit and hold it there until the “CAL”  
LCD indicator appears, then remove the magnet. The analog output current will drop to  
3.75mA.  
4. The “CAL” and “MODE” LCD indicator will flash, indicating that the unit is now calibrating.  
4. After approximately 30 seconds, the display will change from a flashing “CAL” and “MODE”  
LCD to a solid “MODE” LCD, indicating that the calibration is complete and the unit has re-  
entered “OPERATE” mode. Remove any calibration gas.  
6. The unit is now calibrated and the new values have been stored in the NOVRAM (non-  
volatile memory).  
Figure 6 shows a flow diagram of the codes that will appear in the display window during the  
calibration procedure.  
If there is a problem and the TS420 cannot complete the calibration sequence, a fault indicator  
will be displayed, and the analog output current will drop to 3.5mA.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
CALIBRATION  
INDICATOR  
CAL  
MODE  
Magnet Applied  
Magnet Recognized  
Cal Proceeding  
Figure 6 Flow Diagram  
NOTE - If the unit fails to calibrate a flashing “MODE” LCD will be displayed. The sensor must  
see “clean” air for at least fifteen (15) minutes before a second calibration is attempted by  
reapplying the magnet.  
4.4 Calibration Equipment  
General Monitors offers flow calibration kits as the method of introducing calibration gas to the  
TS420. (See Section 5.5).  
Calibration is performed with 20.9% V/V O2.  
NOTE - When removing regulator from gas cylinders, open value on regulator to ensure that  
gas is purged and pressure in the regulator is relieved. Be sure to follow this recommendation  
when switching cylinders.  
WARNING – Do not use a gas cylinder if the regulator gage shows the cylinder pressure in the  
black area just above 0 psi. Unstable calibration could result.  
If the TS420 is to be used with the optional Splash-Guard, all calibrations must be performed  
using the calibration cup (Figure 7) with the Splash-Guard installed onto the TS420. In addition,  
all gas checks must be performed using the calibration cup with the Splash-Guard installed.  
This performs two functions:  
1.  
2.  
It provides a more accurate representation of the amount of gas getting to the sensor.  
It checks that the Splash-Guard is not clogged and that gas can get to the sensor.  
Figure 7 Calibration Cup  
If the Splash-Guard will not be used, the TS420 must be calibrated and gas checked with the  
calibration plug (Figure 8)  
Figure 8 Calibration Plug  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
NOTE – Calibrating the TS420 in normal atmospheric air may introduce a considerable error  
due to the affects of temperature and humidity. Ambient temperature and humidity can affect  
the amount of oxygen in the atmosphere (see Figure 9).  
21.00  
20.50  
20.00  
19.50  
19.00  
0C  
20C  
40C  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
Relative Humidity (%)  
Figure 9 Change in % Oxygen in the atmosphere with Relative Humidity at constant Temperature  
4.5 Sensor Replacement Procedure  
The following is the procedure to replace a TS420 sensor.  
IMPORTANT - Each sensor is shipped in a plastic bottle. DO NOT remove the sensor until you  
are ready to apply power to the system. To ensure proper sensor response, each TS420 must  
be calibrated in the field upon initial installation.  
1.  
2.  
Unscrew the TS420 sensor cap.  
Pull sensor out of the TS420 using your fingers. The sensor is a plug-in type, and the  
sensor will have a snug fit.  
NOTE - The TS420 output will drop to 3.5mA when the sensor is removed, indicating a fault  
condition.  
3.  
If the new sensor is in a plastic storage container, then remove lid ring and uncap jar.  
Remove the sensor from the container. Save the storage container for later use.  
Remove paper liner on sensor gasket if present.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
4.  
5.  
Examine the sensor and ensure that it is the correct gas type for your application.  
Align the arrow on the sensor label with the notch on the TS420 body. Install the  
sensor by pushing sensor’s pins into pin sockets on the TS420, see Figure 10.  
Figure 10 Sensor Alignment  
Remove paper  
liner from  
gasket, if  
present  
CALIBRATION  
PLUG  
CALIBRATION  
CUP  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Figure 11, Calibration Kit with Bottle  
Screw on TS420 sensor cap.  
6.  
7.  
Apply power to the unit and allow the sensor to stabilize prior to initial calibration. The  
stabilization time should be at least one (1) hour for all sensors.  
8.  
Calibrate new sensor (see Section 4.3).  
NOTE - The TS420 will stay in fault anytime the sensor is removed. Calibration is required to  
reset the TS420.  
4.6 Sensor Care and Maintenance  
If power is removed from the TS420 for periods greater than one hour, the sensor should be  
removed from the TS420 and placed in the original storage container shipped with the sensor.  
Storage of the sensor in the original container guards against sensor contamination from  
solvents, lubricant humidity, etc.  
NOTE - Do not short the sensor pins.  
In the case of long intervals of non-use, the sensors should be stored as described above in a  
cool, dry place, preferably refrigerated between 0 and 20°C.  
In all cases, after the sensor has been removed from the TS420, the cap should be replaced on  
to the TS420 body and the gas port taped off to prevent any corrosion damage to the exposed  
socket pins.  
4.7 Fault Codes & The Remedies  
The TS420 has self-diagnostics incorporated into the microprocessor program. If a fault is  
detected, the output signal will drop to 3.5mA and the MODE LCD will be flashing to indicate  
the fault.  
When a calibration fault has occurred and has been corrected, the unit will stay in fault until it  
has been successfully calibrated.  
The Fault Codes are:  
Fault (No Power): Neither LCD will be on. Output signal will be 0.0mA.  
Remedy: Check wiring, ensure power is applied to unit.  
Fault (System): The “MODE” LCD will be flashing. Output signal will be 3.5mA.  
Remedy: Attempt recalibrating the detector. If the fault persists, replace the sensor and after  
sensor has stabilized (one (1) hour minimum). Recalibrate. If fault still persists, contact factory  
or your sales representative.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.0 Appendix  
5.1 Specifications  
5.1.1 System Specifications  
Sensor Type:  
Electrochemical cell  
Typical Life (sensing element):  
2 years in normal air  
Warranty:  
Two years for the electronics  
One year for the sensor cell  
Malfunctions Monitored:  
Calibration Errors  
Data Memory Errors  
Measuring Range:  
Oxygen 0-25% V/V O2  
Response Time:  
T90 < 15 sec  
Repeatability:  
+ 1 % full scale  
Approvals:  
UL, CUL, CSA, CENELEC and CE approved.  
NOTE - Not approved for use in atmospheres > 21%V/V O2.  
5.1.2 Mechanical Specifications  
Weight (approx.):  
Length:  
Diameter:  
Mounting:  
Housing:  
0.5 lbs. (0.23 kg)  
4.5" (114 mm)  
1.75"(44 mm)  
3/4" NPT  
Plastic  
5.1.3 Electrical Specifications  
Recommend two wire 14, 16 or 18 AWG shielded cable.  
General Purpose Installations  
Maximum distance between the TS420 and the power source @ 24VDC nominal (600 load  
resistor maximum) is 8000 feet (2438 meters).  
Intrinsically Safe Installations  
See Sections 5.1.5 through 5.1.7.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Intrinsically Safe Parameters  
Ui /VMAX  
Ii /IMAX  
Ci =  
=
=
35VDC  
100mA  
0
Li =  
500 µH  
Input Power:  
10 to 35VDC range; 3.5 to 22mA loop powered  
Output Current:  
(600 max. @ 24VDC) (120 max. @ 10VDC)  
Signal Range  
Fault  
3.5 to 22mA  
3.5mA  
Start-up  
3.6mA  
Calibration  
Detection Range  
Over-range  
3.75mA  
4 to 20mA  
22mA  
Electrical Classification:  
Class I, Divisions 1 & 2, Groups A, B, C & D;  
Class I, Zone 0, AEx ia IIC T6; EX ia IIC T6; Eex ia IIC T6  
Class II, Groups E, F & G,  
Class III,  
IP67, Type 4X  
RFI/EMI Protection:  
Complies with EN50081-2, EN50082-2  
Status Indicator:  
Liquid Crystal Display with Normal, Fault, and Calibration cues  
5.1.4 Environmental Specifications  
Operating Temperature Range:  
-4°F to +122°F  
(-20°C to +50°C)  
Storage Temperature Range:  
-4°F to +122°F  
(-20°C to +50°C)  
Humidity Range:  
0 to 99% relative humidity non-condensing  
Pressure Range:  
Atmosphere ± 10%  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.1.5 Intrinsically Safe System Requirements  
NOTE - Refer to control drawing 45217 Rev A. (Section 5.2.2)  
The TS420 is approved as intrinsically safe on its own (entity approved). However, when  
installing the TS420 into a system, there are requirements, which must be strictly followed to  
maintain the intrinsic safety of the system. These requirements are:  
1. Ui/VMAX of the field device (TS420) must be less than or equal to UMAX of barrier.  
2. Ii/IMAX of the field device (TS420) must be greater than or equal to IMAX of the barrier.  
3. The inductance of the cable and the TS420 (Li) must be less than the barrier’s maximum  
inductance rating (La).  
4. The capacitance of the cable and the TS420 (Ci) must be less than the barrier’s maximum  
capacitance rating (Ca).  
To calculate maximum cable length, use the following formulas, and use the shorter of the two  
calculations.  
Capacitance:  
Max. Cable Length = CMAX(Barrier) - Ci(TS420) (ft)  
Wire Capacitance/Ft  
Inductance:  
Max. Cable Length =  
L
MAX(Barrier - Li(TS420) (ft)  
Wire Inductance/Ft  
5.1.6 Sample Calculation  
What is the maximum allowable cable length when using an MTL 7206 barrier and BELDEN  
8760 2-conductor shielded cable?  
BELDEN 8760 Parameters: C/ft = 24 pF/ft, L/ft: not available  
MTL 7206:  
TS420:  
CMAX = 0.12 µf  
LMAX = 4.0 mH  
Ui/VMAX = 35V  
Ii/IMAX = 93mA  
Ci = 0 µf  
Li = 500 µH  
Ui/VMAX = 35V  
Ii/IMAX = 100mA  
1. Ui/VMAX (TS420) Ui/VMAX (MTL 7206)  
35VDC 35VDC  
2. Ii/IMAX (TS420) Ii/IMAX (MTL 7206)  
100mA  
93mA  
3. Cable inductance not available.  
4. Max. cable length = CMAX (MTL 7206) - Ci (TS420)  
C/L (Belden 8760)  
= 0.12µf - 0µf  
24pF/ft  
Max. Cable length = 5000 feet  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.2 Engineering Documentation  
5.2.1 Outline & Dimensional Drawing  
4.50"  
3/4 NPT  
LOOP+ (RED)  
LOOP- (WHITE)  
Ø1.75"  
FRAME GROUND  
(GREEN/YELLOW)  
1 1/2-20 UN-2A  
Figure 12 Outline and Dimensional Drawing  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.2.2 Control Drawing  
Figure 13 Control Drawing  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.2.3 Sample Installation  
Figure 14 Sample Installation  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.2.4 Junction Boxes  
Figure 15 10252 Round Aluminum Junction Box  
Figure 16 31305-2 Aluminum Junction Box  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
Figure 17 45160-1 Plastic Junction Box, NPT; 45160-2 Plastic Junction Box, M20  
5.2.5 Splash-Guard  
Figure 18 70631-2 Splash - Guard  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.2.6 Accessories  
Figure 19 45170-1 Flow Block  
Figure 20 45147-1 Flow Block Retainer  
5.2.7 Calibration Accessories  
Figure 21 914-152 Calibration Plug  
Figure 22 1400152-1 Calibration Cup  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.3 Ordering Information  
TS420 - 3 0 0 - 101 - 1 0  
Junction Box:  
0 = None  
1 = 45160-1 Junction Box – Plastic NPT  
3 = 10252 Junction Box – Round, Aluminum  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.4 Calibration Schedule for Problem Environments  
Detector Serial Number:________________________ Location:_____________________  
1)  
Installation and preliminary calibration. Record date after preliminary calibration is  
performed:  
Date:_______________  
2)  
3)  
24-hour calibration. Record date after 24-hour calibration is performed:  
Date:_______________  
7 day calibration check (Record date and reading of calibration check. Repeat after 7  
days if reading deviates more than ±10%. Otherwise go to step 4).  
Date  
Reading  
Date  
Reading  
Date  
Reading  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
4)  
5)  
6)  
7)  
14 day calibration check (Record date and reading of calibration check. Repeat after  
14 days if reading deviates more than ±10%. Otherwise go to step 5).  
Date  
Reading  
Date  
Reading  
Date  
Reading  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
30 day calibration check (Record date and reading of calibration check. Repeat after  
30 days if reading deviates more than ±10%. Otherwise go to step 6).  
Date  
Reading  
Date  
Reading  
Date  
Reading  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
60 day calibration check (Record date and reading of calibration check. Repeat after  
60 days if reading deviates more than ±10%. Otherwise go to step 7).  
Date  
Reading  
Date  
Reading  
Date  
Reading  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
90 day calibration check:  
Date  
Reading  
Date  
Reading  
Date  
Reading  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
________ ________  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model TS420  
5.5 Spare Parts & Accessories  
TS420 Spare Parts  
The Model TS420 has potted electronics, therefore, there are no replacement boards available  
for this unit. The part numbers of the TS420 itself are:  
TS420  
Oxygen Deficiency  
Sensor Cap  
45200-1  
45103-1  
Replacement Sensors  
Oxygen Deficiency Sensor  
45213-1  
TS420 Mounting Accessories  
Splash-Guard (Standard)  
Flow Block (Incl. Ret./Cal Plug)  
Retainer, Flow Block  
Alum. Junction Box (Small)  
Alum. Junction Box (Large)  
Plastic Junction Box (3/4” NPT)  
Plastic Junction Box (M20)  
Cable Grip  
70631-2  
45170-1  
45147-1  
10252  
31305-2  
45160-1  
45160-2  
961-008  
961-009  
961-007  
961-006  
¾” NPT, Adapter, Plastic  
¾” NPT Adapter, Steel  
20 mm x ¾” NPT Adapter, Brass  
TS420 Calibration Accessories  
Tubing  
Regulator (500ml/Min)  
Calibration Plug  
931-085  
922-023  
914-152  
1400152-1  
Calibration Cup  
Calibration Kits (cylinder, regulator & tubing)  
O2 20.9%  
1400263-11  
Spare Cylinders  
O2 20.9%  
1400262-11  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Electro Voice Microphone 603 A User Manual
Extron electronic Cable Box VSC 500 User Manual
Fender Musical Toy Instrument Brown Derby User Manual
Fisher Projector PLC XU100 User Manual
Frigidaire Cooktop FGGC3645K User Manual
Furuno SONAR F 851SD User Manual
Fusion Car Amplifier CP AW1120 User Manual
Garland Oven CPO ED 12H User Manual
Giant Septic System P420 User Manual
Global Machinery Company Cordless Drill DP250LS User Manual