GE Yard Vacuum DEH 211 User Manual

POWER LEADER TM  
PMCS 6.9  
Read-This-Book-First  
Installation Guide  
DEH-211  
GE Power Management Control System 6.9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Contents  
Introduction  
3
Welcome ....................................................................................................................................3  
How to Use this Book ................................................................................................................3  
About CIMPLICITY PMCS Version 6.9...................................................................................4  
Performance.................................................................................................................4  
Features........................................................................................................................4  
Supported Devices .......................................................................................................6  
Getting Started  
8
First Steps...................................................................................................................................8  
Understanding Terminology ........................................................................................8  
System Requirements.................................................................................................11  
Where to Get Help.....................................................................................................11  
What’s next? ..............................................................................................................12  
Installing the Software  
14  
Computer Preparation ..............................................................................................................14  
Installing CIMPLICITY.............................................................................................14  
Installing Additional Software ...................................................................................15  
Installing Additional Software ...................................................................................18  
Installing the EPM Software Components .................................................................18  
Installing the PMCS software...................................................................................................19  
eLicensing PMCS software........................................................................................19  
License by Phone .......................................................................................................21  
Host PC Installation...................................................................................................21  
Viewer Workstation Installation ................................................................................21  
PMCS Installation Steps ............................................................................................22  
PQ Analyst Installation Steps.....................................................................................37  
Un-elicensing PMCS..................................................................................................40  
Uninstalling PMCS ....................................................................................................41  
Reinstallation Steps....................................................................................................43  
Upgrading from previous versions to PMCS 6.9 .......................................................44  
CIMPLICITY PMCS Read-This-Book-First  
Back to Main Page i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuring the Software  
45  
Organize Your Information....................................................................................... 45  
Configuration Procedure........................................................................................... 47  
EPM Device- Special Considerations  
49  
Introduction............................................................................................................................. 49  
EPM Software Components .................................................................................................... 50  
Network Builder: Building the Network Configuration File..................................... 50  
ION Designer: Programming Devices and Software Nodes...................................... 50  
Communications Server: System Communications................................................... 50  
ION_LINK DDE Server: Communication with Windows Applications................... 50  
Workstation Configuration Guidelines.................................................................................... 51  
Configuring the EPM Device Network ................................................................................... 52  
Running Network Builder ......................................................................................... 52  
Building the Power-Monitoring Network in NetBuilder........................................... 53  
Adding Devices (Meters) .......................................................................................... 57  
Saving and Exiting.................................................................................................... 57  
Using MMS Servers with PMCS  
59  
What is an MMS Server? ........................................................................................................ 59  
System Requirements................................................................................................ 59  
Installation for Windows NT 4.0............................................................................................. 60  
Preparing the MMS Server for use with PMCS ...................................................................... 61  
Index  
66  
ii Contents  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Welcome  
Hello and welcome to the POWER LEADER Power Management Control System  
for CIMPLICITY® HMI. You are about to begin using your computer in an exciting  
new way—as a tool to help you increase productivity while reducing downtime and  
energy costs.  
This book is for anyone getting started with CIMPLICITY PMCS. It contains the  
information you need to install and begin using PMCS effectively.  
Chapter 2, Getting Started, explains the terminology of power-  
management systems, describes each of your PMCS items, outlines the  
minimum system requirements, and lists methods of getting GE  
Technical Support.  
Chapter 3, Installing the Software, explains how to prepare your system  
and install all of the PMCS software. Any special installation steps are  
outlined for each software module.  
Chapter 4, Configuring the Software, describes how to efficiently  
configure PMCS to get up and running in the shortest time.  
Chapter 5, EPM Device Special Considerations, details the additional  
configuration required to use EPM 7700, EPM 7600 and EPM 7500  
meters in a PMCS network.  
How to Use this Book  
You will find this book easy to use if you look for these simple conventions:  
Boldface type indicates the name of an item you need to select.  
Monospace type indicates an example or text that is displayed on the  
screen.  
UPPERCASE type indicates a file name, command name, or acronym.  
CIMPLICITY PMCS Read-This-Book-First  
Introduction 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About CIMPLICITY PMCS Version 6.9  
CIMPLICITY PMCS Version 6.9 is the latest Power Management Control System in  
the robust line of POWER LEADER power-management products from GE  
Industrial Systems. CIMPLICITY PMCS seamlessly integrates the comprehensive  
line of POWER LEADER devices, as well as many new Modbus RTU devices and  
systems. PMCS comes with built-in Ethernet compatibility and is optimized for the  
Windows NT 4.0 operating system. All of this adds up to the most flexible, high-  
performance, open-architecture power-management system available. PMCS  
software is the backbone of your new power management system, with state-of-the-  
art graphics and features designed to maximize productivity and minimize downtime  
and energy costs.  
Performance  
With built-in Modbus RTU and Ethernet compatibility, PMCS delivers critical  
power-management information faster than ever. PMCS supports baud rates of up to  
38.4 kbps on a Modbus RTU network and 10 Mbps on an Ethernet TCP/IP network.  
This results in near “real-time” screen refresh rates and immediate access to critical  
event and alarm data.  
Features  
PMCS comes with the following features that make the system more powerful and  
easy to use:  
Compatible with industry-standard third-party SCADA platforms.  
Built-in Modbus RTU network compatibility for an open network  
architecture and high-speed communications.  
Built-in Ethernet TCP/IP network compatibility for very high-speed  
communications and reduced wiring costs.  
Built-in support for the comprehensive line of POWER LEADER  
power-management devices, as well as additional GE meters and relays,  
Fanuc 90/30 and 90/70 programmable logic controllers, plus support  
for third-party meters and relays.  
3D virtual-device interaction with accurately reproduced device look  
and feel.  
Improved waveform capture, including extensive analysis tools.  
Comprehensive alarm and event reporting for immediate diagnosis of  
electrical system problems.  
Multiple Viewer Workstation support for seamless access and sharing  
of power-management data across your existing LAN.  
Configurable password protection and user-activity logging for  
improved security and restriction of setup or control operations.  
PMCS option modules are available to further increase productivity and reduce  
energy costs. Your system may include one or more of the following modules:  
4 Introduction  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CIMPLICITY PMCS Interface Toolkit with tools to quickly create  
accurate, intelligent floorplans, one-line diagrams, and elevation views.  
System Test Simulator to design and test PMCS systems without  
connection to real networks or devices.  
CIMPLICITY PMCS Read-This-Book-First  
Introduction 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Supported Devices  
CIMPLICITY PMCS 6.9 supports the following devices. Firmware revisions other  
than those listed may not be compatible with PMCS. Contact your GE Sales  
Representative or the GE Resolution Center, at 1-888-GE-RESOLV for more  
information.  
Device  
Firmware Revision Supported  
POWER LEADER EPM (commnet communications option)  
(Modbus communications option)  
1.06  
3.4  
POWER LEADER Meter  
2.00  
3.0.1.1.b  
1.5.1.0  
3.2  
EPM 3710 Electronic Power Meter  
EPM 3720 Electronic Power Meter  
Power Quality Meter (PQM)  
POWER LEADER MDP Overcurrent Relay  
(commnet communications option)  
(Modbus communications option)  
1.0  
3.4  
Spectra MicroVersaTrip™  
5.16  
4.13  
Enhanced MicroVersaTrip™ C  
Enhanced MicroVersaTrip™ D  
Spectra ECM Electronic Control Module  
239 Motor Protection Relay  
4.13  
7.2  
2.4  
269 Plus Motor Management Relay  
369 Motor Management Relay  
SR469 Motor Management Relay  
SR489 Generator Management Relay  
565 Feeder Management Relay  
735 Feeder Relay  
D.6.0.4  
1.45  
30D261A8.000  
1.41  
VE2.71  
25D152D1.000  
2.50  
SR745 Transformer Management Relay  
SR750 Feeder Management Relay  
SR760 Feeder Management Relay  
POWER LEADER Modbus Concentrator  
4.0  
3.60  
Main Firmware 2.2  
Segment Firmware 2.12  
POWER LEADER Modbus Monitor  
GE Fanuc MicroPLC Programmable Logic Controller  
ALPS Advanced Line Protection System  
LPS Line Protection System  
2.0  
n/a  
V0004.00AA15  
V0004.00AA15  
4.4  
DFP100 Digital Feeder Relay  
DFP200 Digital Feeder Relay  
EPM 7300 Meter  
2.01  
1.33  
EPM7500 Meter  
2.05  
EPM7600 Meter  
2.01  
EPM7700 Meter  
2.0  
Schweitzer Engineering Laboratories SEL-251 Distribution Relay  
R406  
Schweitzer Engineering Laboratories SEL-321 Phase and Ground Distance Relay,  
Directional Overcurrent Relay and Fault Locator  
R500  
Schweitzer Engineering Laboratories SEL-351 Directional Overcurrent Relay,  
Reclosing Relay and Fault Locator  
R103  
Schweitzer Engineering Laboratories SEL-587 Current Differential Relay  
System Monitor SM-3 Voltage Regulator  
Universal Relay  
R503  
0309B  
2.42  
6 Introduction  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Device  
Firmware Revision Supported  
Motor Manager II  
4.02  
CIMPLICITY PMCS Read-This-Book-First  
Introduction 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
First Steps  
If you are already familiar with PMCS, simply review the system requirements and  
skip ahead to Chapter 3.  
Getting started with PMCS is easy. This chapter explains power management and  
leads you through the steps to take prior to installing your PMCS software. If you  
need help with your PMCS system, the GE Technical Support telephone number is  
given at the end of this chapter.  
Understanding Terminology  
Power-management system terminology can be intimidating to new PMCS users. The  
list below defines many of the important terms and acronyms used in this guide and  
other PMCS manuals. Refer back to this list as new terms are presented later.  
Baud rate: A measurement of a communication channel's signaling rate or  
information-carrying capacity. Communicating devices typically have configurable  
baud rates to provide compatibility with various speed communication networks.  
Higher baud rates generally provide faster data-refresh times.  
CIMPLICITY HMI: An industry-standard SCADA software package providing  
flexible, accurate, and easy-to-use graphics. CIMPLICITY HMI is based on a client-  
server architecture, consisting of Servers and Viewer Workstations. Servers are  
responsible for the collection and distribution of data. Viewer Workstations connect  
into Servers and have full access to the collected data for viewing and control  
actions. Servers and Viewer Workstations can be easily networked together to  
seamlessly share data without the need to replicate your point database from node to  
node.  
CIMPLICITY HMI Server Development: CIMPLICITY HMI Server Development  
allows you to create new projects and can also function as a runtime system.  
CIMPLICITY HMI Server Runtime: CIMPLICITY HMI Server Runtime systems do  
not support project configuration. They may be used as runtime systems only.  
CIMPLICITY HMI Viewer Runtime: CIMPLICITY HMI Viewer Runtime connects  
to Servers for viewing data and controlling actions.  
Commnet: A GE Industrial Systems standard for device communications that  
specifies the communication protocol and the communication network.  
Communication network: A physical standard for wiring and interconnection of  
communicating devices. A communication network standard usually includes  
specifications of voltages, maximum cable-run lengths, shielding, termination, and  
8 Getting Started  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
cable requirements. RS485 and Ethernet are examples of communication-network  
standards.  
Communication protocol: A language or convention used for reliable transmission  
and reception of binary data. A communication protocol is often independent of the  
physical method or network used for transmission. Modbus RTU and TCP/IP are  
examples of communication protocol standards.  
DDE Server: A software application that typically runs in the background, gathering  
information from the network and providing the information in DDE format for use  
by one or more applications. The PMCS DDE Server is included in the PMCS  
Network & Device Configurator and comes in versions optimized for Ethernet  
TCP/IP or RS485 Modbus RTU networks.  
DDE: Dynamic Data Exchange. A Microsoft Windows standard for efficient sharing  
of data between applications on the same PC. See also NetDDE.  
Ethernet Gateway: A POWER LEADER device used to connect four RS485 Modbus  
RTU networks to an Ethernet TCP/IP network. The Gateway increases performance  
of a PMCS system through multiple Modbus networks and reduces overall wiring  
costs through reuse of existing Ethernet LAN wiring.  
Ethernet: An industry-standard communication network commonly used for local-  
area networks (LANs) of PCs. Ethernet PMCS systems provide very high-speed,  
reliable communications at 10 megabits per second.  
Event Logger: A standard PMCS application that efficiently analyzes, sorts, and logs  
unusual system behavior such as circuit breaker trips, undervoltages, and  
overcurrents. Extensive data-logging capabilities make it a useful tool for analyzing  
and predicting system maintenance patterns.  
Host PC: The PC running the PMCS DDE Server is referred to as the Host PC. All  
other PCs running PMCS client programs are referred to as Viewer Workstations or  
networked PCs.  
Interface Toolkit: An optional PMCS tool used to quickly generate accurate and  
friendly graphical user interfaces. The Interface Toolkit provides dozens of wizards  
to efficiently create intelligent one-line diagrams, equipment elevation views, floor  
plans, 3D virtual-faceplate views, and tabular displays.  
Modbus Concentrator: A POWER LEADER device used to connect eight commnet  
networks to an RS485 Modbus RTU network. The Concentrator provides full  
compatibility between the PMCS software and the extensive line of POWER  
LEADER devices with commnet communications, as well as simple expansion of a  
RS485 Modbus RTU network to up to 247 devices.  
Modbus RTU: An industry-standard, nonproprietary communications protocol  
typically used in medium-speed networks (up to 38.4 kpbs) on RS485.  
NetBEUI: A network protocol usually used in small, department-size local-area  
networks of 1 to 200 clients.  
NetDDE: A version of Dynamic Data Exchange (DDE) that allows communications  
between applications running on different PCs over network connections.  
NT Service: A designated piece of software which runs in the background of  
Windows NT and can be set to automatically start when the machine is booted up.  
For example, the PMCS DDE Server can be set to operate as a Windows NT Service,  
rather than a manually-launched application. Another advantage of NT Services is  
that they are persistent across multiple user logins and logouts; that is, PMCS DDE  
CIMPLICITY PMCS Read-This-Book-First  
Getting Started 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Server when operating as a Windows NT Service will not shut down when a user logs  
off.  
ODBC: Open Database Connectivity. An inter-application communication protocol  
required for certain PMCS client applications to share data. Automatically installed  
and configured as part of the PMCS installation routine.  
PMCS: Power Management Control System. GE’s high-performance power-  
management system for Windows NT, including open network protocols, waveform  
capture and analysis, event logging, and several optional modules.  
POWER LEADER: The family of GE power-management devices, including meters,  
relays, trip units, and software.  
RS485: An industry-standard communication network supporting up to 32 networked  
devices. RS485 provides medium-speed, reliable communication transport through  
shielding, balanced transmission voltages, and termination.  
SCADA: Supervisory Control and Data Acquisition. A category of systems that  
primarily acquires data for logging and analysis, as well as providing supervisory  
control in applications without time-critical requirements. Power-management  
systems are a direct application of SCADA technology.  
TCP/IP: Transmission Control Protocol / Internet Protocol. An industry-standard  
protocol typically used on Ethernet or Token-Ring local-area networks (LANs).  
Waveform Capture: A standard PMCS application that provides a window into  
power-quality data in an electrical system. Waveform Capture is used to view  
snapshots of voltage and current waveforms from various points in an electrical  
system to analyze harmonics and unusual system behavior.  
10 Getting Started  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Requirements  
The following table shows the minimum and recommended PC system configuration  
for running PMCS Version 6.9. Note that regardless of configuration, the PC system  
must be Windows NT-certified according to the Microsoft Windows NT 4.0  
addition to the requirements described below, setting up PMCS and EPM 7700  
workstations will require Windows NT Administrator-level authority privileges.  
Minimum  
Recommended  
Pentium II processor, 300 MHz  
Pentium III processor, 600 MHz  
Microsoft Windows NT 4.0 Workstation,  
Service Pack 6, Windows 2000 Professional  
Microsoft Windows NT 4.0 Workstation or  
Server, Service Pack 6, Windows 2000  
Professional, Cimplicity version 4.01 Service  
Pack 9 or Cimplicity version 5.0 Service Pack 1  
Cimplicity version 4.01 Service Pack 9 or  
Cimplicity version 5.0 Service Pack 1  
128 megabytes of RAM  
512K cache  
256 megabytes of RAM  
512K cache  
4-gigabyte hard disk  
CD-ROM drive  
10-gigabyte hard disk  
CD-ROM drive  
Note: For systems using MMS technology, refer to Using MMS Servers with PMCS  
for minimum system requirements.  
Additional hard disk space is recommended for increased storage of log and trend  
data. Also recommended are an uninterruptable power supply (UPS), 17” or larger  
monitor, tape drive or other backup mechanism, and (if Remote Access technical  
support is desired) a 28.8 Kbps or faster modem.  
The version of CIMPLICITY installed must be 4.01 or greater, and HMI Service  
Pack 9 must be installed. Also, the "Advanced DDE Communications" option must  
be installed.  
Microsoft Internet Explorer 3.02 or later is required to run the EPM 7700 component  
help system. To take advantage of all available .HTML help features, Internet  
Explorer version 4.0 or higher must be installed. (The latest version of Internet  
Explorer is available at www.microsoft.com.)  
Please note that the host PC requirements are directly tied to the complexity of your  
PMCS system. The minimum requirements will suffice for a simple PMCS system.  
However, as the number and complexity of your power management device grows,  
and you add more complex software requirements such as custom interfaces designed  
with third-party HMI tools, your PC requirements increase as well. A faster processor  
and more memory provide better performance for your PMCS system.  
Where to Get Help  
The GE Industrial Systems Resolution Center is available at 1-888-GE-RESOLV to  
answer your questions about installing or using PMCS. Please have your product  
serial number(s) ready when calling.  
Also, technical notes are available on the Internet at:  
CIMPLICITY PMCS Read-This-Book-First  
Getting Started 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
What’s next?  
The following chapters discuss the details of installing and getting quick results from  
your new PMCS software. Set aside at least an hour and be sure to follow the  
procedures carefully to guarantee correct installation of your PMCS software.  
12 Getting Started  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This page left blank intentionally.)  
CIMPLICITY PMCS Read-This-Book-First  
Getting Started 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Software  
Computer Preparation  
PMCS must be installed on a PC running Windows NT Workstation 4.0. This host  
PC must be dedicated to the PMCS system. Performance and data integrity cannot be  
predicted unless the PC is configured solely for the purpose of running PMCS.  
The Windows NT System control panel offers a Performance tab that allows you to  
boost performance for the foreground application. For PMCS, must be changed to No  
Performance Boost for Foreground Application (default is Maximum), as shown  
below:  
The Virtual Memory setting may be left at the Windows NT defaults.  
Make sure your system meets these requirements before proceeding with the  
remaining installation steps. PMCS will not run correctly unless these requirements  
are satisfied.  
Installing CIMPLICITY  
If CIMPLICITY HMI was provided with your PMCS software, you must install it  
before proceeding. If your computer already has CIMPLICITY HMI installed, make  
sure the following requirements are met.  
14 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CIMPLICITY HMI for Windows NT (Intel) Version 4.01 with HMI Service  
Pack 9 or CIMPLICITY HMI for Windows NT (Intel) Version 5.00 with HMI  
Service Pack 1is required. Other versions of CIMPLICITY may not be  
compatible with PMCS.  
If you are installing CIMPLICITY HMI, follow the directions provided with the  
software (inside the CD jewel case). Choose CIMPLICITY HMI as the product to  
install, then select either the HMI Server or Viewer as the product option to install,  
and C:\CIMPLICITY\HMI as the installation directory. If you install the Server  
option, also install Server Option - Communications - Advanced DDE/DDE  
Client.  
Installing Additional Software  
Install any additional software, such as Microsoft Excel, at this point in the  
procedure. Follow the instruction procedures provided by the manufacturer.  
For instructions on installing SISCO Systems' MMS Server for use with PMCS, refer  
to the section titled Using MMS Servers with PMCS.  
RS485 PMCS Network Interfaces  
If you are using an RS485 interface card to connect to the PMCS network, install the  
card following the manufacturer’s installation instructions. Be sure to install any  
Windows NT drivers provided by the interface-card vendor. Typically, drivers are  
installed at Control Panel>Network>Adapters>Add Adapter by following the  
instructions. You may be prompted to insert the manufacturer’s disk into the A:  
drive.  
From the Network  
control panel, select  
the Adapters tab,  
then click Add.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Select the appropriate network adapter from the list and click Have Disk…. Follow  
the instructions provided on the screen to complete the network card installation.  
For PMCS systems using one or more GE Multilin RS232 to RS485 converters (or  
equivalent), no additional drivers are required.  
Ethernet PMCS Network Interfaces  
If you are using an Ethernet interface card to connect to the PMCS network through  
one or more Ethernet Gateways or directly to a network of Universal Relays (Modbus  
TCP/IP), follow the manufacturer’s installation instructions and be sure to install the  
provided Windows NT drivers using Control Panel>Network>Adapters>Add  
Adapter. Refer to the screen shots above for an example, though the selections will  
differ based on the hardware you are installing.  
Ethernet requires the TCP/IP protocol for compatibility with the Ethernet Gateway or  
Universal Relays. TCP/IP should have been installed with Windows NT Workstation  
4.0; you can check this using Control Panel>Network>Protocols. The screen shot  
below shows a system with TCP/IP installed. If TCP/IP is not installed on your  
system, refer to the Windows NT documentation for installation instructions.  
16 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ethernet users:  
Check the  
Protocols tab of the  
Network control panel  
for TCP/IP Protocol.  
Local Area Network (LAN) Interfaces  
PMCS supports multiple Viewer Workstations through links over a local area  
network. Thus, in addition to the PMCS network interface, the Host PC may also  
have a LAN interface.  
A Host PC with an Ethernet PMCS network interface may use either the same  
Ethernet card as the LAN interface or a separate LAN interface card. A Host PC with  
an RS485 PMCS network interface requires an additional LAN interface card to  
support Viewer Workstations.  
Typical LAN interface cards include Ethernet and Token Ring. Any LAN interface  
card should be installed according to the manufacturer’s instructions.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Additional Software  
Install any additional software, such as Microsoft Excel or COMTRADE file  
browsers for analyzing waveform files, at this point in the procedure. Follow the  
instruction procedures provided by the manufacturer.  
Installing the EPM Software Components  
The EPM 7700, EPM 7600 and EPM 7500 Meters require additional software to  
operate with PMCS client software such as the Event Logger, Waveform Capture  
Module, or CIMPLICITY Wizards. This is because the EPM 7700, EPM 7600 and  
EPM 7500 are not compatible with the standard PMCS DDE Server. Instead, a  
separate DDE Server called the 7700 Gateway Server must be installed, along with a  
pair of ‘helper’ applications, the Communications Server and the ION_Link Server.  
The Communications Server processes all communications between the Gateway  
Server and/or the ION_Link and the Ethernet-based EPM 7700, EPM 7600 and EPM  
7500 meters.  
The EPM 7700 software may be selected during the standard PMCS installation  
routine. If you are not using any EPM devices in your PMCS setup, you do not need  
to install the EPM options during PMCS installation.  
The EPM software components do require some special configuration beyond that  
required for other PMCS components. Refer to the section titled EPM Device Special  
Considerations for details after running the installation routine described in this  
section.  
18 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the PMCS software  
Once you have set up Windows NT and any third-party software (if appropriate) you  
are ready to install the PMCS software. PMCS should be installed last, after all other  
software installations are completed. Your PMCS software is provided on a CD-  
ROM.  
The diagram below depicts the relationship of the Host PC and any optional Viewer  
Workstations in your system. Follow the specific instructions below for software  
installation on Host PCs and Viewer Workstations.  
View  
Node  
View  
Node  
Host  
PC  
PMCS  
..N..e.tw..o.r.k.(.s.)...
LAN  
View  
View  
Node  
Node  
eLicensing PMCS software  
General Electric Industrial Systems has added security technology that requires your  
PMCS software to be licensed in order to run. A separate license is required for each  
computer that will receive PMCS. Each eLicense Order ID that is sent with your  
order corresponds to one license.  
You license your software as part of the automated PMCS installation process.  
When you launch the installation process the first screen that will appear will be your  
eLicense Option screen (see below). This screen allows you to either trial or fully  
license your PMCS software.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30 Day Trial  
You have the option to Trial PMCS for 30 days through the 30-Day Trial  
selection on this screen. All functionality of PMCS is available to trial users  
and all configurations made for the software will be maintained from one  
use to the next. A single trial is registered to each PC and may not be  
uninstalled and re-installed for another trial.  
Licensing via the Web  
Choose the Web License option if you have a working internet connection  
on your PMCS computer. This option will automatically connect you to  
General Electric Industrial Systems’ eLicense distribution system. Once  
connected, an automated process will retrieve your unique PMCS eLicense  
key.  
Selecting the Web License option from the License Option brings you to  
the Web License Screen. This screen requires you to enter your eLicense  
Order ID. This information is contained on the Order Confirmation Sheet  
that accompanied your PMCS software or it can be obtained from your  
Purchase Confirmation e-mail Enter the Order ID and click on Get License  
to initiate the Web connection to General Electric Industrial Systems’  
eLicense distribution system.  
20 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Similar to the trial, each eLicense is registered to the computer In which case, the  
eLicense Order ID can only be used for one computer The software must be  
unlicensed to be re-licensed with the same eLicense Order ID on another computer  
Select Launch from your License Installation Success Screen to continue installing  
PMCS.  
License by Phone  
If your PMCS computer does not have an internet connection you may license your  
PMCS software over the phone by selecting the By Phone option on the Licensing  
Option Page. This will bring you to a Phone License screen. This screen provides a  
Toll-Free Assistance Line 1-888-GE-4-SERV (international callers, please use 540-  
378-3888) that can be used to retrieve your unique eLicense key from a General  
Electric Industrial Systems customer support representative (please select Technical  
Support, then Software Licensing from the phone menu). You will be asked over the  
phone for your System Identifier, Version ID, and Order ID and in return you will  
be given your eLicense key. The eLicense Order ID from the License  
Confirmation sheet and the eLicense key given over the phone are required to Install  
the eLicense.  
Similar to the trial, each eLicense is registered to the computer In which case, the  
eLicense Order ID can only be used for one PMCS computer . The software must be  
unlicensed to be re-licensed with the same eLicense Order ID on another computer .  
Select Launch from your License Installation Success Screen to continue installing  
PMCS.  
Host PC Installation  
Every PMCS system requires one Host PC that is directly connected to the PMCS  
network and communicates with the power-management devices. The Host PC is also  
typically used to view and analyze data.  
If you are installing multiple PMCS catalog numbers on the Host PC, you will need  
the CD and serial number from each package. Follow the Installation Steps section  
below. If the Host PC will be providing data to View Nodes, be sure to refer to GEH-  
6510, Network and Device Configurator, to configure NetDDE for operation with the  
View Node PCs.  
Viewer Workstation Installation  
PMCS supports optional Viewer Workstations, which interact with the power-  
management network through NetDDE links to the Host PC. Viewer Workstations  
are not directly connected to the PMCS network but are connected via LAN to the  
Host PC. Viewer Workstations are not mandatory in a PMCS system because the  
data is available for display and analysis at the Host PC. When installing PMCS  
View Nodes, be sure to use only an appropriate catalog number for the installation.  
Do not install any other PMCS software on a PMCS Viewer Workstation.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: The EPM software differs from the standard PMCS usage of Viewer  
Workstations. Refer to the section titled EPM Device - Special Considerations for  
more details on EPM Workstations and View Nodes.  
PMCS Installation Steps  
Follow the procedure below to install each PMCS catalog number. Be sure the  
catalog numbers you are installing are appropriate for the destination PC (Host PC or  
View Node). Close any open applications before installation.  
1. Insert the PMCS Installation CD into the CD-ROM drive.  
2. Click the Start button from the Windows NT Task Bar and select Run.  
3. In the Run dialog box, enter X:\setup (where X is the appropriate CD-  
ROM drive designation).  
22 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. The GE PMCS 6.9 Setup screen appears as shown below. Read the general information  
and disclaimers shown on the screen, and click Next.  
When you select the Next button in the Welcome screen, the PMCS license agreement screen  
is shown. Please take a moment to read over the license agreement, then click Next.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. At the User Information screen shown below, enter your name, your company name, and  
the serial number for the PMCS component you are installing. Serial numbers for PMCS  
components are located on the PMCS CD-ROM jewel case. If you make an error in the  
serial number, the installation routine will prompt you for a correct PMCS serial number.  
When you have completed the registration information, click Next.  
When you select the Next button in the User Information screen, a registration confirmation  
screen prompts you to verify your entries. Ensure that you have made no mistakes in the  
User Information fields, then continue.  
24 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. At the Choose Destination Location dialog, specify a drive on which to install PMCS.  
Default is “C”. Click Next to continue.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. At the Setup Type screen, select either a Custom installation, standard PMCS  
installation, or PMCS with EPM 7700 Components. PMCS installation is recommended  
and will install all components for the PMCS catalog number you entered in the User  
Information screen. Select PMCS with EPM 7700 Components if you will be installing  
EPM 7700, EPM 7600 or EPM 7500 devices in your network. Select Custom if you wish  
to select specific PMCS software components to install. Click Next to continue.  
If you select PMCS with EPM 7700 Components, you may also be required to view an  
additional license agreement for MS Data Access components. This software is required  
by the EPM 7700 software. Take a moment to read the license agreement information,  
then continue.  
26 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box  
(Step 7), skip this step and proceed to Step 11.  
If you are installing the EPM 7700 Components, select whether this is to be a Primary node  
installation or Secondary node installation. You must install at least one Primary node on  
your PMCS network; it is recommended that you install the Primary node at the same  
machine as the PMCS DDE Server for convenience in configuration. Secondary nodes are  
akin to PMCS view nodes and may be installed on remote machines to access EPM 7700  
data from the Primary node. (For additional details on Primary and Secondary nodes, see  
the section on configuring EPM 7700 components later in this chapter.)  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box  
(Step 7) or if you selected “Primary Node Installation” in Step 8, skip this step and  
proceed to Step 11.  
If you selected Secondary Node installation in Step 8, the following dialog box appears  
prompting you to select either "Full Station" or "Stationless" node installation. If you are  
installing software on a computer that will service EPM 7700, EPM 7600 or EPM 7500  
IEDs directly, choose "Full Station". If you are installing software on a computer that will  
not be connected to IEDs but will be used to access data from other network workstations,  
choose "Stationless". For more details on EPM 7700 network configuration, refer to the  
EPM Device Special Considerations section later in this manual, or to DEH-40035, the  
GE 7700 Gateway User’s Guide.  
28 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box  
(Step 7), or if you selected “Primary Node Installation” in Step 8, skip this step and  
proceed to Step 11.  
If you selected Secondary Node installation in Step 9, the following dialog box appears  
prompting you for the name of the computer on which the Primary Node is installed.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. Select the Program Folder for PMCS installation. It is recommended that the default  
Program Folder be chosen. Click Next to continue.  
30 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12. If you chose the “PMCS” installation, you may be presented with one or more DDE  
Server selections depending upon the PMCS catalog number you entered in the User  
Information screen. Select only the DDE communications servers that you will be using  
in your system  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13. Next, the installer prompts you to choose how you wish to install the PMCS components.  
You may install them as standard applications which may be launched from the Start  
menu, or you may choose to install the PMCS components as Window NT Services. NT  
Services can be set to start automatically when the machine is powered up, and have the  
powerful advantage of running in the background with no regard to users' logon/logoff  
cycles. For example, the PMCS Waveform Server, when set to run as an NT Service,  
continues to collect waveform data whether or not a user is logged on. (For further  
information on NT Services, refer to your Windows NT documentation.)  
Choose whether to configure your PMCS components as NT Services, then select Next.  
32 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If you chose to configure NT Services, you'll also need to select the appropriate DDE Server.  
The Select DDE Sever Configuration dialog is displayed for this action. Select the DDE  
Server(s) you will be using with your application, then choose Next.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14. The Selected Components screen offers you the opportunity to verify the installation  
settings before any files are copied to your hard drive. Confirm that the installation  
settings are correct, then click Next. The installation program copies the appropriate files  
to your hard drive.  
If you have selected the EPM 7700 System Components (either manually when performing a  
Custom install or automatically when PMCS with EPM 7700 Components install is  
selected), the installer will check your system for a copy of Microsoft Internet Explorer,  
version 3.02 or higher. This is because the EPM 7700 software components use .html-  
format help files which require Internet Explorer to view. If Internet Explorer is not  
found, the following dialog box appears:  
If you wish to view the EPM 7700 software help files, you should separately install Microsoft  
Internet Explorer, version 3.02 or higher. (To take advantage of all available help system  
features, Internet Explorer version 4.0 or higher is required.) Internet Explorer is not  
included as part of PMCS. You may obtain the latest version of Internet Explorer by  
34 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15. After completing the selected PMCS installation, the installation program checks the host  
PC for an older version of the POWER LEADER Modbus Monitor Proxy software. If the  
installer locates the Proxy software, it prompts you to update the Proxy to the PCMS 6.x-  
compatible version before finishing the PMCS installation routine. (If your system does  
not use POWER LEADER Modbus Monitor devices or does not have the Monitor Proxy  
software installed, the PMCS installer will skip this step.)  
16. At this point, the installation program copies the appropriate files to your hard drive.  
17. After the Setup program finishes installing the PMCS components you have selected, you  
will be prompted to install the Adobe Acrobat Reader software. If you do not have  
Acrobat Reader 3.0 or later installed on your PC, you may wish to install Acrobat Reader  
at this time. The PMCS CD-ROM includes a full complement of technical documentation  
in Acrobat PDF format which may be viewed with the Acrobat Reader program. The  
documentation is located in the TechDocs directory of the CD-ROM.  
18. After the installation of Acrobat Reader, you will be prompted to install Waveform  
Analyst software. Install Waveform Analyst application to browse a large amount of  
power quality survey data with ease, using a graphical interface on a Microsoft Windows  
platform  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19. When all the installations are complete, the Setup Complete dialog box, shown below,  
prompts you to restart your computer.  
After restarting your computer, be sure to view the ReadMe file to check any late-breaking  
information useful to the configuration or operation of your PMCS system.  
NOTE: Your computer MUST be restarted after installing PMCS software. This step is  
critical to proper operation of the software, as it enables the following to happen:  
The operating system will register the new software components.  
The MMS Server (if installed) will update its alias table.  
Initial network configurations for EPM7700, EPM 7600 and EPM 7500 devices will  
be created.  
36 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PQ Analyst Installation Steps  
Follow the procedure below to install each PMCS catalog number. Be sure the catalog  
numbers you are installing are appropriate for the destination PC (Host PC or View Node).  
Close any open applications before installation.  
Insert the PMCS Installation CD into the CD-ROM drive. If CD AutoStart is enabled, the  
PMCS installation routine will launch automatically. In this case, skip steps 2 and 3 and  
proceed directly to step 4.  
Click the Start button from the Windows NT Task Bar and select Run.  
1. In the Run dialog box, enter X:\setup (where X is the appropriate CD-ROM drive  
designation).  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. The GE PMCS 6.9 Setup screen appears as shown below. Read the general information  
and disclaimers shown on the screen, and click Next.  
When you select the Next button in the Welcome screen, the PMCS 6.9 license  
agreement screen is shown. Please take a moment to read over the license agreement, then  
click Next.  
3. At the User Information screen shown below, enter your name, your company name, and  
the serial number for the PMCS component you are installing. Serial numbers for PMCS  
components are located on the PMCS CD-ROM jewel case. If you make an error in the  
serial number, the installation routine will prompt you for a correct PMCS serial number.  
When you have completed the registration info,click Next.  
38 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. At the Choose Destination Location dialog, specify a drive on which to install PMCS.  
Default is “C”. Click Next to continue.  
5. Now PQ Analyst setup Dialog box appears. Click OK button to continue the PQ Analyst  
installation.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When all the installations are complete, the Setup Complete dialog box, shown below,  
prompts you to restart your computer.  
NOTE: Your computer must be restarted after installing PMCS software. This step is  
critical to proper operation of software.  
Un-elicensing PMCS  
In order to unlicense your software to use your eLicense Order ID for another computer  
– you must have an internet connection. To retrieve your license for use on another  
PMCS installation, simply right click on any PMCS executable on your desktop and  
select unlicense.  
The screen will request the eLicense Order ID to be entered.  
40 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A screen will appear to indicate that you have successfully un-eLicensed and you may  
now take the eLicense Order ID for use on another PMCS installation.  
* Please note that you can not retrieve an eLicense for re-use through the unlicense  
process past 3 years of initial Licensing.  
Uninstalling PMCS  
All PMCS software is provided with an uninstall utility to fully remove PMCS  
components from your system. Uninstalling PMCS will permanently delete any  
configuration information.  
NOTE: The Uninstaller may not delete some files such as error logs, system logs,  
and configuration records, which are created after the PMCS installation is complete.  
Since these files are not part of the initial installation, they will not be removed by the  
Uninstaller, and must be deleted manually.  
If you are uninstalling EPM 7700 components, be aware that the Pegasys System Log  
Service does not properly unregister itself as an NT Service. The following  
procedure will allow you to manually uninstall this component: the remaining PMCS  
software can then be uninstalled in the usual manner.  
Uninstalling the Pegasys System Log Service:  
1. Open a Command Prompt window.  
2. Make the C drive the current directory (assuming your Windows system files  
reside on the C drive).  
3. Type “slservice –e” EXACTLY as shown and hit enter.  
4. If the Pegasys System Log Service was installed and running you will receive the  
message “Pegasys System Log Service stopped”. If you do not receive this  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
message, the Log Service was not installed on your system. Exit the command  
prompt and continue uninstalling PMCS.  
5. If you received the correct message in step 4, uninstall the service. Type  
“slservice –u” EXACTLY as shown and hit enter. A message appears indicating  
“Pegasys System Log Service uninstalled”. Exit the command prompt and  
continue uninstalling PMCS.  
42 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reinstallation Steps  
Follow the procedure below to reinstall your PMCS software.  
1. If your system includes the PMCS Interface Toolkit, uninstall the CIMPLICITY  
Wizards from any third-party HMI tools.  
2. Close any open applications.  
3. Insert the PMCS Version 6.9 CD into the CD-ROM drive.  
4. From Start menu, select Run and enter X:\setup (where X is the appropriate  
CD-ROM drive designation).  
5. Read the general information and disclaimers shown on the screen and click  
Next.  
6. Enter your name, your company name, and the serial number located on the  
PMCS CD jewel case, then click Next. If you make an error in the serial number,  
the installation routine will prompt you for a correct PMCS serial number.  
7. Choose the installation type; either PMCS, PMCS with EPM 7700  
Components, or Custom installation. PMCS or PMCS with EPM 7700  
Components installation will reinstall all components of the appropriate PMCS  
catalog number. Select Custom if you wish to reinstall only selected PMCS  
software components.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Upgrading from previous versions to PMCS 6.9  
PMCS 6.9 provides an easy-to-use, automatic upgrade path from previous versions of  
PMCS. The software installer examines your hard drive and, if it locates any previous  
version of PMCS, it makes decisions on upgrading each component.  
Follow the procedure below to upgrade your currently installed PMCS version (such  
as 5.0, 5.1, or 6.0) to PMCS version 6.9. This procedure assumes you have an  
existing PMCS installation with configured ports, topics and (optionally) generic  
topics, and that CIMPLICITY Wizards are installed in the generic HMI application.  
WARNING: PMCS 5.1 and PMCS 5.1b Modbus DDE Server users only: Upgrading  
from PMCS 5.1 to PMCS 6.9 may cause the Modbus version of the DDE Server to  
lose its port configuration. You may need to reconfigure your communications ports  
from the PMCS DDE Server after upgrading. The Ethernet version of the DDE  
Server is not affected.  
PMCS 5.0 users: Port configuration is lost when a PMCS 5.0 configuration file is  
converted to a PMCS 5.1b configuration file. You will need to reconfigure your  
communications ports from the PMCS DDE Server. Refer to GEH-6510 for  
instructions. Also, any generic topics you may have configured at the PMCS DDE  
Server will be lost, and you will need to re-configure these generic topics.  
1. Close any open applications, and insert the PMCS 6.9 CD into the CD-ROM  
drive.  
2. From Start menu, select Run and enter X:\setup (where X is the appropriate CD-  
ROM drive designation).  
3. Read the general information and disclaimers shown, then click Next.  
4. Enter your name, your company name, and the serial number located on the  
PMCS CD jewel case, then click Next. If you make an error in the serial number,  
the installation routine prompts you for a correct PMCS serial number.  
5. Choose either PMCS, PMCS with EPM 7700 Components or Custom  
installation. PMCS or PMCS with EPM 7700 Components installation will  
reinstall all components of the appropriate PMCS catalog number. Select  
Custom if you wish to reinstall only selected PMCS software components.  
6. After upgrading, existing HMI applications that use PMCS wizards will continue  
to work. If you upgrade device firmware you will need to replace the old wizard  
screens with new screens to maintain compatibility between your application and  
the device. The old PMCS wizards will remain on your system unless you  
uninstall the previous version of PMCS. It is highly recommended that all new  
applications use PMCS 6.9 Advanced wizards exclusively.  
7. After upgrading, launch the PMCS DDE Server. The Server will convert your  
previous PMCS configuration to a PMCS 6.9 configuration.  
WARNING: Event Logger users only: Upgrading your EventServer or Eventlogger  
application will result in the loss of all device configurations and annunciator panel  
items. Make a list of these items so that they may be reconstructed in the new  
application. Existing database files will be backed up by the installation program, but  
they cannot be viewed with the PMCS 6.9 EventViewer. To view databases created  
with earlier editions of PMCS, use Microsoft Access to open the .mdb files.  
44 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuring the Software  
To get the most out of your new PMCS system, follow the directions below to  
configure your system.  
Organize Your Information  
Host PC  
You need the following information to properly configure the PMCS software for the  
Host PC. This information is used throughout the configuration process and you  
should archive it for any future maintenance of your system.  
For RS485 PMCS network interfaces, you need to list all devices in the power-  
management network (including Modbus Concentrators) with associated device  
types, Modbus RTU addresses, and COM ports. Assign names of less than 20  
characters (no spaces) to these devices.  
For example, in a simple system with four devices (and one Modbus Concentrator),  
you may have a table similar to the following.  
COM port  
Modbus RTU Address  
Device Type  
MODCONC  
E3720  
Device (Topic) Name  
MCI  
1
1
1
1
2
2
12  
33  
61  
210  
Main_Meter  
Mfg_Meter  
PLEPM  
MVT  
Mfg_Breaker  
Mill_Relay  
ML269  
For an Ethernet PMCS network interface (Ethernet Gateway), you must list all  
devices in the power-management network, including the device types and Modbus  
RTU addresses. You need to know the appropriate Ethernet Gateway IP address and  
COM port (1–4) to which each device is connected. Assign names of less than 20  
characters (no spaces) to these devices.  
For example, in a simple system with 10 devices, you may have a table similar to the  
following (this system uses one Ethernet Gateway and three Modbus Concentrators).  
CIMPLICITY PMCS Read-This-Book-First  
Configuring the Software 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ethernet Gateway COM  
Modbus RTU  
Address  
IP Address  
port  
Device Type  
MODCONC  
E3720  
Device (Topic) Name  
MC1  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
1
2
1
12  
Main_Meter  
Mfg_Meter  
1
33  
PLEPM  
PLEPM  
MODCONC  
PLEPM  
PLM  
1
61  
Plating_Meter  
MC2  
2
12  
2
66  
Office1_Meter  
Office2_Meter  
Feeder1_Relay  
Mfg_Breaker  
Mill_Relay  
2
80  
2
90  
MDP  
2
100  
200  
21  
MVT  
3
ML269  
4
MODCONC  
MVT  
MC3  
4
201  
210  
Plating_Breaker  
Office_Breaker  
4
MVT  
View Node  
You should configure View Nodes after you have configured and tested the Host PC  
to ensure all functions are operating. View Nodes require a copy of the network  
architecture list used above. Refer to GEH-6510, Network and Device Configurator,  
for complete configuration instructions.  
46 Configuring the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Procedure  
Follow the procedure below to efficiently configure your system and minimize your  
time to startup.  
Host PC Configuration  
1. Configure the DDE Server. Your Host PC will likely have several versions of  
the DDE Server installed (RS485-Modbus, TCP/IP Modbus, TCP/IP  
Encapsulated Modbus and Ethernet-TCP/IP). Configure only the server  
appropriate for your PMCS network interface (GE32MODB, GE32MTCP,  
GE32GTWY or GE32ENET). See GEH-6510, Network and Device  
Configurator, for complete details.  
2. EPM 7700, EPM 7600 and EPM 7500 users only (all others proceed to step  
3): Configure the Communications Server and GE 7700 Gateway Server. If you  
installed the EPM software options and you are going to use EPM 7700, EPM  
7600 or EPM 7500 devices in your PMCS network, you will need to configure  
both the Communications Server and the GE 7700 Gateway Server. For Comm  
Server configuration instructions, refer to EPM Software Components  
Configuration later in this guide. For GE 7700 Gateway Server configuration  
instructions, refer to DEH-40035, the GE 7700 Gateway Server User’s Guide.  
3. Configure the user interface. If your system was provided with a generic HMI  
software application, either load or create the custom HMI (using the Interface  
Toolkit wizards, if appropriate; see DEH-210, CIMPLICITY PMCS Interface  
Toolkit or refer to the HMI software’s documentation.  
4. Configure the applications. As appropriate, configure the following application  
modules, referring to the instruction manuals provided.  
Event Logger, GEH-6512  
Waveform Capture, GEH-6511  
5. Test the applications. Test the functioning of all applications to ensure proper  
Host PC operation. Do not proceed to step 5 until you are sure the Host PC  
operates as expected.  
6. Set up NetDDE. If your system has one or more View Nodes, set up NetDDE  
shares and trusts in the Host PC, following the procedures in GEH-6510,  
Network & Device Configurator and the CIMPLICITY HMI documentation.  
7. Set up NetDDE. If your system uses the PMCS Waveform Capture client, and  
you intend to access waveform data from View Nodes, set up NetDDE shares  
and trusts for the PMCS Waveform Server following the procedures in GEH-  
6511, PMCS Waveform Capture Module.  
Viewer Workstation Configuration  
1. Configure the user interface. Load the custom MMI. Refer to the CIMPLICITY  
HMI documentation as appropriate.  
2. Configure the applications. As appropriate, configure the application modules,  
referring to the instruction manuals provided. See step 3 of the Host PC  
Configuration for the appropriate instruction manual numbers.  
CIMPLICITY PMCS Read-This-Book-First  
Configuring the Software 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EPM Software Components Configuration  
The EPM 7700, EPM 7600 and EPM 7500 requires several separate software  
components which are installed during the PMCS setup. This section provides a brief  
overview of the steps required to configure these components; the following section  
describes the EPM software components in greater detail.  
For details of using the NetBuilder software, refer to the Configuring the EPM 7700  
Device Network section of this manual, and to DEH-440035, the GE 7700 Gateway  
User’s Guide.  
1. Launch the NetBuilder application. From the Start menu, select  
Programs>Power Management Ltd>Utilities>Network Builder.  
2. Insert a workstation(s). Normally all the workstations in a PMCS network are  
automatically configured during the installation of the software – these  
instructions are provided in case you need to enter the information manually.  
Select the Items menu from NetBuilder, and choose Workstation to insert a  
workstation. Name the workstation (up to 15 alphanumeric characters, the first  
character must be alphabetic), and choose OK. Repeat this step for each  
workstation (computer) in your network.  
3. Insert Ethernet Sites. Select Items>Insert>Ethernet Site to insert an Ethernet site.  
Set the proper time synchronization options, then choose OK. Repeat this step to  
add additional sites to the workstation if necessary.  
4. Insert devices to the site. Select Items>Insert>Device, and complete the dialog  
box with the proper device type, Group, Ethernet address and name for an  
Ethernet device (EPM 7700, EPM 7600 or EPM 7500). The device name may  
be no more than eight alphanumeric characters, and the first character must be  
alphabetic. The IP service port field must be "7700" for any device connected to  
the Ethernet, and "7800" for any additional device connected through an EPM  
7700’s RS485 port. Choose OK to close the Insert Device dialog box. Repeat  
this step as necessary to add additional devices to the site.  
5. Save and exit. When all workstations, sites, and devices have been added, select  
the save icon and then exit.  
48 Configuring the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EPM Device-  
Special Considerations  
Introduction  
The GE EPM 7700, EPM 7600 and EPM 7500 devices add new level of power  
management capabilities to PMCS. These EPM devices also require some special  
configuration which is not necessary for other PMCS-compatible devices. This  
section describes the additional requirements and configuration steps necessary to use  
the EPM 7700, EPM 7600 and EPM 7500 in conjunction with PMCS.  
NOTE: If you are not using the EPM 7700, EPM 7600 or EPM 7500 meters in your  
PMCS network, it is not necessary to read this section of the manual.  
Although the EPM 7700, EPM 7600 and EPM 7500 meters are compatible with  
PMCS and its client applications (Waveform Capture, custom wizards, etc.), and  
EPM 7700, EPM 7600 and EPM 7500 meters may co-exist on the same Ethernet as  
other PMCS network segments, the EPM 7700, EPM 7600 and EPM 7500 use a  
slightly different metaphor than a straight PMCS network. An EPM device power-  
monitoring network is comprised of a number of nodes that are connected to the  
PMCS workstation through Ethernet links. Nodes in the power-monitoring network  
are IEDs such as the EPM 7700 meter (power meters are also referred to ‘meters’ or  
‘devices’). IEDs may be distributed across one or more networks as required to  
service the particular application.  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device- Special Considerations 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EPM Software Components  
There are four major components of the EPM software. The Network Builder, ION  
Designer, Communications Server, and ION_LINK DDE Server each interact to  
support the EPM 7700, EPM 7600 and EPM 7500 Meters. When you selected the  
“PMCS with EPM 7700 Components” selection during the PMCS installation  
routine, these software components were installed automatically. The four  
components and their functions are described below.  
Network Builder: Building the Network  
Configuration File  
The Network Builder presents a graphical view of the EPM 7700, EPM 7600 and  
EPM 7500 devices in your network, allowing you to easily add, remove or configure  
sites, services and meters. Network Builder creates a central network configuration  
file that holds information for the workstation, the network connections, and every  
connected device. You may want to restrict access to Network Builder or the  
network configuration file, since if the file is tampered with, EPM 7700, EPM 7600  
and EPM 7500 components may be rendered inoperable.  
ION Designer: Programming Devices and Software  
Nodes  
The ION Designer component allows you to customize the operation of an ION-  
compliant node, such as 7000-series meters and 3000-series meters. Be aware that  
misuse of ION Designer can adversely affect the operation of your meters.  
IMPORTANT: For purposes of PMCS network compatibility, it is CRITICAL that  
any EPM 7700, EPM 7600 and EPM 7500 meters be configured with the GE PMCS  
standard configuration. Using ION Designer to customize EPM 7700, EPM 7600 or  
EPM 7500 functionality can compromise compatibility with the PMCS client  
applications attempting to access the device.  
Communications Server: System Communications  
The Communications Server is the core communications component for EPM 7700,  
EPM 7600 and EPM 7500 meters. The Communications Server manages all  
communications between the meters connected to your network and the GE77GTWY  
and ION_Link DDE Server software applications.  
ION_LINK DDE Server: Communication with  
Windows Applications  
The ION_LINK DDE Server uses Dynamic Data Exchange to share information  
with applications such as Microsoft Excel or the CIMPLICITY Wizards.  
50 EPM Device- Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Workstation Configuration Guidelines  
If you are using the EPM 7700, EPM 7600 or EPM 7500 Meters in your PMCS  
network, the following guidelines in this section must be adhered to before  
continuing with the EPM configuration.  
NOTE: If you are adding a PMCS installation to an existing network, please refer  
your network administrator to GEH-6502, the PMCS Network Architecture Guide,  
for integration details.  
Each computer in the network must be assigned a Windows NT  
computer name. The name must be one to fifteen alphanumeric  
characters in length. Spaces may not be used, and the first character of  
the computer name may not be numeric.  
The System Control Panel should have the Performance Boost for  
Foreground Application value set to None, and a paging file should be  
created on the C: drive with the Initial and Maximum sizes set to twice  
the workstation’s installed RAM.  
The Network Control Panel’s Adapter tab should have the MS  
Loopback adapter installed if a physical network adapter is not installed  
in the workstation. Under the Protocols tab, TCP/IP or NetBEUI should  
be installed; if TCP/IP is installed, use IP address 192.168.100.xxx and  
subnet mask 255.255.255.0 unless your network administrator has  
assigned you an IP address. Under the Services tab, install Remote  
Access Server (RAS) and configure it by enabling NetBEUI (if using  
NetBEUI or, if TCP/IP is used, assign two or more IP addresses,  
starting at xxx.xxx.xxx.254 and working down. Set RAS to start  
automatically and set access to “entire network” (if available).  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device- Special Considerations 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuring the EPM Device Network  
The PMCS installation routine described earlier in this manual creates initial  
workstation and software node entries in the EPM 7700 network configuration file.  
After EPM 7700 software components are installed, the next step is to add Ethernet  
sites and devices to the PMCS power-monitoring network using Network Builder  
software.  
Running Network Builder  
Network Builder software presents your EPM power-monitoring network graphically,  
showing the installed components in a hierarchical tree. Network Builder allows you  
to edit the Network Configuration file— the file that identifies every node in the  
EPM power-monitoring network.  
The first step is to run Network Builder from the Start Menu: (Programs > Power  
Measurement Ltd > Utilities > Network Builder.)  
The following figure shows how Network Builder displays a system comprised of the  
basic EPM software components, a single EPM 7700 meter, a Primary Node and a  
Stationless Secondary node (also called a ‘view node’).  
Workstation: the network name of the  
Primary Node computer running the  
Communications Server and GE 7700.  
Software nodes: Stationless Secondary  
nodes appear here.  
Ethernet Site: Defines the Ethernet  
connection between the PMCS system  
and the connected device(s).  
Device: Name(s) of attached device(s).  
52 EPM Device- Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Building the Power-Monitoring Network in  
NetBuilder  
When Network Builder is running, you can begin configuring your EPM system by  
adding a site to the workstation, then adding devices to the site. For larger systems  
multiple sites are added; one for each network of devices monitored.  
NOTE: The PMCS installation wizard creates initial entries for the workstation and  
software nodes. If you do not need to make changes to the information provided  
during installation, skip this section and begin with the section title "Adding an  
Ethernet Site".  
Adding a Workstation  
When you use the PMCS installation wizard to install a Primary node or Full Station  
Secondary node, it creates a Workstation in the Network Configuration for you.  
Stationless Secondary nodes do not appear in the network configuration as  
workstations, but as software nodes under the Primary workstation. See the section  
on software nodes for more information.  
To add a new workstation, right click “System” and choose “Insert Workstation”  
from the pop-up menu. The “System – Add Workstation” dialog box appears as  
shown below. Type the network name of the computer in the “Name” field. (Use the  
default settings on the “Advanced” tab.) Click “OK, then proceed to “Adding  
Software Nodes” below.  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device- Special Considerations 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adding Software Nodes  
Software nodes identify the various software components in the network. Stationless  
Secondary nodes, although they are physically separate computers, do not run a  
Communications Server and are therefore not considered Workstations by Network  
Builder. Instead, Stationless Secondary nodes appear in the network diagram as  
software nodes under the Primary Workstation. Full Station Secondary nodes appear  
as Workstations because they do run an instance of the Communications Server.  
Acknowledging the Add Workstation dialog brings up a message box asking if you  
want to set up the default software nodes – choose Yes to display the software nodes  
dialog (shown below). Select only ION Designer and Pegasys ION_Link DDE Server  
as shown, then click OK to proceed. The other options are not supported in PMCS  
6.9.  
54 EPM Device- Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adding an Ethernet Site  
An Ethernet site defines the network connection between the devices and the  
Workstation(s). You add Ethernet sites to Workstations, then add devices to the sites.  
To add a new Ethernet site, right-click a Workstation name and choose “Insert:  
Ethernet site” from the pop-up menu – attach it to the current Workstation. Click OK  
to continue.  
An Add Ethernet Site dialog box (shown below) appears.  
Set the following communications parameters for the site.  
Enter the Transmit delay setting (in milliseconds). This setting determines  
the level of traffic on the network. If the PMCS system is the sole user of the  
network, set this value to 5 (or less) to maximize performance. Increase the  
transmit delay in situations where the network is shared with other users,  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device- Special Considerations 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
such as on a corporate LAN. Refer to the PMCS Network Architecture  
Guide for guidelines on setting this parameter for best system performance.  
Change the RX timeout delay from 10000 to 30000 on the Advanced tab.  
(See the following figure for Advanced tab.)  
All other parameters may be left at their default values for most applications. When  
you click OK in the Add Site dialog box, Network Builder will inform you if there is  
additional information you must enter.  
56 EPM Device- Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adding Devices (Meters)  
To add a meter, right-click on the Ethernet site you want to add the meter to, and  
select Insert Device… from the pop-up menu. The Add Ethernet Device dialog box  
appears (shown below).  
Enter the following information:  
Choose the meter type from the Type list (Power Measurement 7700 ION).  
Type a name in the Group box, or choose a Group from the list (by default  
the Group will be the name of the workstation).  
Enter a name for the meter (or accept the default). The meter name must  
begin with a letter.  
Enter the IP address for the meter.  
Enter the IP Service Port number (socket) for the meter. For a 7700, 7600  
and 7500 ION this number is 7700, for a 3720 ACM, 3721.  
Saving and Exiting  
Once you have added all of your sites and devices to the network tree, click the Save  
button (or choose Save from the File menu), and exit Network Builder. You have  
now configured your EPM 7700, EPM 7600 and EPM 7500 meters to operate with  
the PMCS, and you should be able to access EPM 7700, EPM 7600 and EPM 7700  
metering data from PMCS client applications.  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device- Special Considerations 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This page left blank intentionally.)  
58 EPM Device- Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Using MMS Servers with PMCS  
What is an MMS Server?  
PMCS is an extremely flexible system which supports generic DDE Servers. One such server  
is the SISCO AX-S4 MMS Server (MMS stands for Manfacturing Message Specification).  
AX-S4 MMS ("Access for MMS") is an easy to use tool that provides real-time data  
integration for Windows applications. PMCS applications can access data from MMS servers  
as well as the PMCS DDE Server. The MMS Server should only be used with PMCS when  
integrating devices that comply to the UCA/MMS 2.0 standard.  
For details on the SISCO AX-S4 MMS Server, refer to the AX-S4 MMS for Windows 95 and  
Windows NT User's Guide, which shipped with your MMS software product.  
For convenience, installation and setup instructions to prepare an MMS Server for access by  
PMCS applications are provided here.  
System Requirements  
The following table shows the minimum recommended PC system configuration for running  
the MMS Server and software with PMCS Version 6.9. Note that regardless of configuration,  
the PC system must be Windows NT-certified according to the Microsoft Windows NT 4.0  
the requirements described below, setting up PMCS and EPM7700 workstations will require  
Windows NT Administrator-level authority privileges, as described earlier in the Getting  
Started section.  
Minimum PC Requirements for using MMS Technology with PMCS  
Dual Pentium III processor, 500 MHz or better  
Microsoft Windows NT 4.0 Workstation, Service Pack 3 (SP5 recommended),  
Windows 2000 Professional, Cimplicity version 4.01 Service Pack 9 or  
Cimplicity version 5.0 Service Pack 1  
256 megabytes of RAM  
512K cache  
10-gigabyte hard disk  
Super VGA video adapter and monitor  
CD-ROM drive  
CIMPLICITY PMCS Read-This-Book-First  
Using MMS Servers with PMCS 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation for Windows NT 4.0  
The following installation procedures assume that you are familiar with Windows NT 4.0 and  
your computer.  
Carefully read the following notes that pertain to installing your AXS-MMS-132-095 product.  
Follow the steps below to install AX-S4 MMS for Windows NT on your system.  
1. Insert the AXS4-MMS-132-095 CD-ROM into the CD-ROM drive.  
2. If the Autorun feature is enabled on your computer, go to Step 3.  
Otherwise, click on Start, select Run and enter X:\disk1\setup (where X is the  
appropriate CD-ROM drive designation).  
3. When the AX-S4 MMS Setup initializes, you are presented with three installation  
choices: Typical, Minimal, and Custom. Typical (the recommended selection) will install  
the core AX-S4 MMS and SISCO OSI Stack components including AX-S4 MMS  
samples. Minimal will only install the AX-S4 MMS and SISCO OSI Stack components.  
Custom will allow you to select only those components that are required for your  
installation. When using this option, you may also choose to install the electronic copy of  
the AX-S4 MMS User's Guide.  
4. Follow the instructions on the screen to complete the AX-S4 MMS installation.  
Note: When the AX-S4 MMS Setup is complete you will be asked if you want to restart the  
computer. Select the option "No, I will restart my computer later." Click the Finish  
button.  
5. Install the OSI LLC Protocol Driver for Windows NT.  
Note: If you are replacing an existing version of the OSI LLC Protocol Driver, you need to  
remove the current version. Select the Services dialog tab, highlight the OSI LLC  
Protocol Driver and click the Remove button. Click on OK. Click the Close button and  
reboot your computer. When the system reboots, set the directory to the Windows System  
Drivers (System32\Drivers) and delete the file osillc.sys. The installation process will fail  
to load the correct OSILLC device driver if an older version of the device driver is  
present in the system directory.  
6. Click on Start > Settings > Control Panels. From the Control Panel folder, select the  
Network shortcut.  
7. Select the Protocols dialog tab and click the Add… button.  
8. From the Select Network Protocol dialog box, click the Have Disk… button.  
9. From the Insert Disk dialog box, type the path {d}:\osillc\winnt, where {d} designates  
the letter of your CD-ROM drive, and click on OK to accept the path.  
10. From the Select OEM Option dialog box, click on OK, then click the Close button and  
restart your computer.  
11. The following directory structure should now appear on your computer.  
<Drive>:\OSILL2  
All OSI Stack files  
<Drive>:\AXS4MMS  
All AX-S4 MMS files  
Note: If you are installing for both Windows 95 and Windows NT, you should install the  
product into the same directory. This will allow you to share the same configuration  
database between both platforms.  
60 Using MMS Servers with PMCS  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preparing the MMS Server for use with PMCS  
The following instructions describe how to set up your MMS Server for DDE access by  
PMCS applications such as Event Logger and Waveform Capture. Both MMS Server and  
PMCS must be properly installed before following these instructions.  
1. Launch the AX-S4 MMS Configuration Program (Start > Programs > Sisco > AXS4  
MMS > AXS4 MMS Configuration), and select Configure > Configuration > Network >  
Addressing. This displays the Network Addressing window, shown below.  
Choose New to start the wizard for creating a new host. The Host Name Wizard - Host Name  
dialog box is displayed.  
CIMPLICITY PMCS Read-This-Book-First  
Using MMS Servers with PMCS 61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Enter a name for the host you are creating, then choose Next to display the Host Name  
Wizard - Addressing dialog box:  
3. Complete the TCP/IP Network question by selecting the Yes checkbox and entering an IP  
address for the new host, then select Next.  
62 Using MMS Servers with PMCS  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. From the Host Name Wizard - Finished dialog box, select Add AR Names to display the  
AR Name Wizard - Host Name dialog box, below.  
5. Enter the Host Name of the AR Name being created, then choose Next.  
6. You may skip dialog boxes referring to Seletors by using the Next button until the AR  
Name Wizard - AR Name dialog box appears:  
CIMPLICITY PMCS Read-This-Book-First  
Using MMS Servers with PMCS 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Complete the AR Name configuration by entering an AR Name, entering a Comment  
(optional) and selecting TCP/IP Transport. Choose Next to complete the configuration.  
8. When the Finished dialog box appears, select Finished, then Finished again to complete  
and close the wizard.  
64 Using MMS Servers with PMCS  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This page left blank intentionally.)  
CIMPLICITY PMCS Read-This-Book-First  
Using MMS Servers with PMCS 65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
A
N
alarm, 4  
NetBuilder, 48  
AX-S4 MMS Server, 59  
Network Builder, 48  
D
E
O
P
DDE Server, 50  
option modules, 4  
Ethernet, 4, 9, 16, 17, 45, 47  
event, 4  
PEGASYS  
nodes, 49  
Performance, 4  
F
S
Fanuc, 4  
First Steps, 8  
servers  
DDE, 50  
I
T
Interface Toolkit, 5, 9, 43, 47  
TCP/IP, 4, 9, 10, 16, 47  
Technical Support, 3, 8, 11  
Terminology, 8  
M
minimum system requirements, 3  
MMS Server, 59  
Modbus Monitor Proxy, 35  
Modbus RTU, 4, 9, 45  
W
waveform capture, 4  
Windows NT, 4, 10, 14, 16, 19  
66 Index  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GE Industrial Systems  
General Electric Company  
41 Woodford Ave., Plainville, CT 06062  
DEH-211 R06 1000  
© 2001 General Electric Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Echo Chainsaw CS 355T User Manual
Everpure Water System EC110 User Manual
Exmark Lawn Mower Quest Bagger User Manual
Fitness Quest Home Gym Brutus 655 User Manual
Frigidaire Ventilation Hood HV2730B User Manual
Fujitsu Switch MB3788 User Manual
GE Monogram Microwave Oven JVM1540LNCS User Manual
GE Monogram Oven 30 Wall Oven User Manual
Generac Power Systems Portable Generator 004987 2 005396 0 User Manual
GE Washer S4200 User Manual