GE Power Supply DEH 40417 User Manual

DEH-40417  
g
ASTAT ®-IBP Plus Solid State Starters  
Service Instructions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEH-40417  
WARNINGS, CAUTIONS, AND NOTES  
AS USED IN THIS PUBLICATION  
WARNINGS  
Warning notices are used in this publication to emphasize that hazardous voltages, currents, or  
other conditions that could cause personal injury are present in this equipment or may be  
associated with its use.  
Warning notices are also used for situations in which inattention or lack of equipment knowledge  
could cause either personal injury or damage to equipment.  
CAUTIONS  
NOTES  
Caution notices are used for situations in which equipment might be damaged if care is not taken.  
Notes call attention to information that is especially significant to understanding and operating  
the equipment.  
This document is based on information available at the time of its publication. While efforts have  
been made to ensure accuracy, the information contained herein does not cover all details or  
variations in hardware and software, nor does it provide for every possible contingency in  
connection with installation, operation, and maintenance. Features may be described herein that  
are not present in all hardware and software systems. GE Electrical Distribution & Control  
assumes no obligation of notice to holders of this document with respect to changes subsequently  
made.  
GE Electrical Distribution & Control makes no representation or warranty, expressed, implied, or  
statutory, with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency,  
or usefulness of the information contained herein. No warrantees of merchantability or fitness for  
purpose shall apply.  
The following are trademarks of GE Company:  
ASTAT®-IBP Plus  
©Copyright 2001 GE Company  
All Rights Reserved  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
Table of Contents  
Cover Removal and Replacement ............................................................................................1  
Logic Board Replacement .......................................................................................................2  
Power Supply Board Replacement ...........................................................................................3  
Protection Board Replacement ................................................................................................5  
SCR Module Replacement (Sizes K, L, and Y) ...........................................................................6  
SCR Module Replacement (Sizes M, Z, and N) ..........................................................................7  
SCR Module Replacement (Sizes P, Q, and R) ..........................................................................8  
SCR Module Replacement (Size S)...........................................................................................9  
Trouble-Shooting Guide........................................................................................................ 11  
Renewal Parts List................................................................................................................. 12  
ii  
Prices and data subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
WARNING: Power must be removed from the ASTAT-  
IBP before any servicing operation.  
AVERTISSEMENT: Le courant doit être enlevé du  
ASTAT-IBP avant de procéder à toute opération de  
service.  
Terminal Connector  
Cover Rem oval and Replacem ent  
1. Remove the two 12-point terminal connectors by  
inserting  
a
flat-head screwdriver between the  
terminal connector and the ASTAT-IBP cover, as  
illustrated in Figure 1.  
Cover  
Figure 1. Removing the terminal connectors.  
Do not remove the wiring from the terminal  
connectors.  
Carefully release the terminal connector from the  
pins. Carefully pull the terminal connectors, with  
the wiring, straight off the ASTAT-IBP starter.  
2. Remove the plastic cover by pressing and releasing  
the plastic tab on each side of the cover with a flat-  
head screwdriver, as illustrated in Figure 2.  
3. To reattach the cover, lower it over the circuit  
boards. Carefully push down on the cover until the  
two tabs snap into place. It may be necessary to push  
in slightly on the outside of the lower plastic  
housing.  
Figure 2. Removing the cover.  
4. Replace the terminal connectors through the plastic  
cover onto the connector strips. Ensure that the  
terminal connectors snap into place.  
Prices and data subject to change without notice.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
Logic Board Replacem ent  
Logic Board  
Screws  
CAUTION: Always handle circuit boards by their edges  
and do not distort the parts on the circuit boards.  
ATTENTION: Il faut toujours manipuler les plaques de  
circuits par leurs côtés et ne pas déformer les pièces sur  
les plaques de circuits.  
1. Remove the ASTAT-IBP cover as described in steps  
1–2 of Cover Removal and Replacement.  
2. Unplug the two ribbon cables from the Logic Board,  
as shown in Figure 3.  
Unplug Cable  
Ribbon  
Power Supply  
Board  
3. Remove the four corner screws holding the Logic  
Board to the stand-offs below the Logic Board. Lift  
the Logic Board straight up to remove it, as  
illustrated in Figure 4.  
Figure 3. Logic board and part locations.  
Logic Board  
4. Reassemble the Logic Board to the starter. With the  
display on the Logic Board at the upper left corner,  
place the board on the stand-offs. Reattach the four  
screws holding the Logic Board to the stand-offs.  
5. Reattach the two ribbon cables. Ensure that the  
ribbon cable at the bottom of the ASTAT-IBP is fully  
seated on both circuit boards and that the ribbon  
cable does not interfere with or touch the cover.  
6. Reinstall the plastic cover and the terminal  
connectors as described in steps 3–4 of Cover Removal  
and Replacement.  
Cable Ribbon  
Figure 4. Removing the Logic Board.  
2
Prices and data subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
Pow er Supply Board Replacem ent  
Power Supply Board  
Ribbon Cable  
The Power Supply Board is located as shown in Figure 5.  
It contains gray and orange transformers visible from the  
sides.  
1. Remove the following components:  
a. The cover, as described in steps 1–2 of Cover  
Removal and Replacement.  
b. The Logic Board, as described in steps 2–3 of  
Logic Board Replacement.  
2. Remove the four screws holding the Power Supply  
Board to the black plastic housing, as shown in  
Figure 6.  
3. If a yellow-green wire is connected to the bottom of  
the Power Supply Board, it must be disconnected.  
Lower the top of the Power Supply Board to view the  
red and white gate leads to the SCRs, as shown in  
Figure 7.  
Figure 5. Location of the Power Supply Board.  
Screw  
NOTE: Check the red and white gate wires for a marked  
number before removing these wires. Each gate wire  
must have a number corresponding to the terminal  
numbers (1–12) on the Power Supply Board to facilitate  
reassembly.  
NOTE: Vérifier les chiffres sur les fils de porte avant  
denlever ceux-ci. Chaque fil de porte doit avoir un  
chiffre correspondant aux chiffres de la borne (1–12)  
sur la plaque de la boîte d’alimentation pour faciliter le  
réassemblage.  
Figure 6. Removing the screws holding the Power Supply Board  
to the housing.  
4. With a small screwdriver, remove the red and white  
gate wires from the small four-point gate Terminal  
Boards, one on the component side and two on the  
solder side of the Power Supply Board.  
Protection Board  
Gate Leads  
These wires must be reconnected to the new Power  
Supply Board at the proper number terminals for  
proper operation of the starter.  
5. Lift off the Power Supply Board. Remove and save  
the hex stand-offs, nuts, and washers from the Power  
Supply Board for use on the replacement board.  
6. Attach the stand-offs to the new Power Supply Board.  
Place the new Board in position in the ASTAT-IBP.  
Bottom of Power  
Supply Board  
Gate Terminal  
Board  
Figure 7. Gate leads, Power Supply Board, and Protection Board.  
Prices and data subject to change without notice.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
7. Reconnect the red and white gate wires to the four-  
point Terminal Boards, one on the component side  
and two on the solder side of the Power Supply  
Board, as illustrated in Figures 8, 9, and 10.  
8. Secure the Power Supply Board with the four screws  
removed earlier.  
9. Reinstall the following components:  
a. The Logic Board, as described in steps 4–5 of  
Logic Board Replacement.  
d. The cover, as described in steps 3–4 of Cover  
Removal and Replacement.  
Figure 9. Gate lead connections for sizes M, Z, and N.  
Figure 8. Gate lead connections for sizes K, L, and Y.  
Figure 10. Gate lead connections for sizes P, Q, R, and S.  
4
Prices and data subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
Protection Board Replacem ent  
Six-Point  
Terminal Board  
1. Remove the following components:  
a. The cover, as described in steps 1–2 of Cover  
Removal and Replacement.  
b. The Logic Board, as described in steps 2–3 of  
Logic Board Replacement.  
Protection Board  
Wire Connectors  
c. The Power Supply Board, as described in steps 2–  
5 of Power Supply Board Replacement.  
2. Remove the six wire connectors from the Protection  
Board, as shown in Figure 11. Note the locations of  
these terminals for reassembly.  
Mounting Screw  
3. Disconnect the four leads from the two current  
transformers and the two leads from the thermostat  
connecting to the six-point Terminal Board, located  
at the top-right edge of the Protection Board. Label  
these leads to ensure that they are connected to the  
same terminals on the new Protection Board.  
Figure 11. Removing the wire connectors from the Protection  
Board.  
4. Loosen the four screws holding the Protection Board  
to the housing. Remove the Protection Board from  
the ASTAT-IBP.  
5. Place the new Protection Board in position in the  
ASTAT-IBP and secure it with the four mounting  
screws to the housing.  
6. Attach the four current transformer leads and the  
two thermostat leads to the six-point Terminal  
Board.  
7. Attach the six push-on wire connectors to the  
Protection Board.  
8. Reinstall the following components:  
a. The Power Supply Board, as described in steps 6–  
9 of Power Supply Board Replacement.  
b. The Logic Board, as described in steps 4–5 of  
Logic Board Replacement.  
c. The cover, as described in steps 3–4 of Cover  
Removal and Replacement.  
Prices and data subject to change without notice.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
SCR Module Replacem ent (Sizes K, L,  
and Y)  
This procedure requires the following tools and  
materials:  
• #2 Philips-head screwdriver, 3/ 16" Allen wrench,  
torque wrench  
• Scotchbrite or equivalent abrasive  
• Mild solvent to clean mounting surfaces  
• Electrolube 2GX or equivalent thermal grease  
1. Loosen the screws holding the MOVs and bus bars  
to the SCR Module to be replaced, as illustrated in  
Figure 12, and remove the MOVs and bus bars.  
2. Remove the mounting screws at each end of the SCR  
Module, as shown in Figure 13, then lift out the  
Module. Retain all the parts and hardware removed  
from the SCR Module for reassembly with the  
replacement Module.  
Figure 12. Removing the MOVs and bus bars from an SCR to be  
replaced.  
3. Clean the heat sink surface of the replacement  
Module with a fine abrasive, such as Scotchbrite.  
Remove all particles from the heat sink surface and  
wipe the SCR mounting surface with a mild solvent.  
Apply a light coat of thermal grease, such as  
Electrolube 2GX to both the SCR and heat sink  
surfaces.  
4. Place the contact face of the SCR Module on the  
mating heat sink surface. Move the Module back  
and forth several times to distribute the thermal  
grease evenly over the contact surfaces.  
5. Attach the SCR Module to the heat sink with the  
screws removed earlier. Tighten the screws to 44 in-  
lb.  
6. Reattach the bus bars and MOVs to the SCR Module  
with the screws removed earlier. Tighten the screws  
to 26 in-lb.  
Figure 13. Removing the SCR module.  
6
Prices and data subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
SCR Module Replacem ent (Sizes M, Z,  
and N)  
This procedure requires the following tools and  
materials:  
• #2 Philips-head screwdriver, 3/ 16" Allen wrench,  
torque wrench  
• Scotchbrite or equivalent abrasive  
• Mild solvent to clean mounting surfaces  
• Electrolube 2GX or equivalent thermal grease  
1. Loosen the screws holding the MOVs and bus bars  
to the SCR Module to be replaced, shown in Figure  
14, and remove the MOVs and bus bars.  
Figure 14. Location of SCRs on size M, Z, N ASTAT-IBP.  
2. Remove the mounting screws at each end of the SCR  
Module, then lift out the Module. Retain all parts  
and hardware removed from the SCR Module for  
reassembly with the replacement Module.  
3. Clean the heat sink surface of the replacement  
Module with a fine abrasive, such as Scotchbrite.  
Remove all particles from the heat sink surface and  
wipe the SCR mounting surface with a mild solvent.  
Apply a light coat of thermal grease, such as  
Electrolube 2GX to both the SCR and heat sink  
surfaces.  
4. Place the contact face of the SCR Module on the  
mating heat sink surface. Move the Module back  
and forth several times to distribute the thermal  
grease evenly over the contact surfaces.  
5. Attach the SCR Module to the heat sink with the  
screws removed earlier. Tighten the screws to 44 in-  
lb.  
6. Reattach the bus bars and MOVs to the SCR Module  
with the screws removed earlier. Tighten the screws  
to 80 in-lb.  
Prices and data subject to change without notice.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
SCR Module Replacem ent (Sizes P, Q,  
and R)  
This procedure requires the following tools and  
materials:  
3
1/ 2" wrench, / 16" Allen wrench, torque wrench  
• Scotchbrite or equivalent abrasive  
• Mild solvent to clean mounting surfaces  
• Electrolube 2GX or equivalent thermal grease  
1. Disconnect the control wiring harness for the SCRs  
to be replaced. If necessary, disconnect the wiring  
harness of the CTs.  
2. Remove the bolt holding the busbar to the line side  
of the SCR Module.  
Figure 15. Disconnecting the SCR load side..  
3. Remove the bolt holding the CT, spacer, and load-  
side busbar to the SCR Module, as shown in Figure  
15.  
4. Remove the four screws holding the SCR Module to  
the mounting plate, as shown in Figure 16.  
5. Lift out the SCR Module, as shown in Figure 17.  
Retain all parts and hardware for reassembly with  
the replacement Module.  
6. Remove the MOV by disconnecting it at the spade  
connectors. Attach the MOV to the replacement  
SCR Module in the same manner.  
7. Clean the heat sink surface of the replacement  
Module with a fine abrasive, such as Scotchbrite.  
Remove all particles from the heat sink surface and  
wipe the SCR mounting surface with a mild solvent.  
Apply a light coat of thermal grease, such as  
Electrolube 2GX to both the SCR and heat sink  
surfaces.  
Figure 16. Removing the SCR mounting screws.  
8. Place the new SCR Module in the proper position on  
the mounting surface. Move the Module back and  
forth several times to evenly distribute the grease on  
the plate.  
9. Secure the SCR Module to the mounting plate with  
the screws removed earlier. Tighten the screws to 44  
in-lb torque.  
10. Reattach the busbars, CT, and spacer to the SCR  
Module with the bolts removed earlier. Tighten the  
bolts to 150 in-lbs torque.  
11. Attach the wiring harness of the new SCR Module to  
its mating piece. Attach the wiring harness of the  
CTs, if necessary.  
Figure 17. Removing an SCR Module.  
8
Prices and data subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
SCR Module Replacem ent (Size S)  
This procedure requires the following tools and  
materials:  
9 / 16" wrench, 11/ 16" wrench, 3/ 16" Allen wrench,  
torque wrench  
• Scotchbrite or equivalent abrasive  
• Mild solvent to clean mounting surfaces  
• Electrolube 2GX or equivalent thermal grease  
1. Disconnect the control wiring harness for the SCRs  
to be replaced. If necessary, disconnect the wiring  
harness of the CTs.  
2. Remove the bolt holding the busbars connected to  
the blocks on the load and line sides of the SCR  
Module, as shown in Figure 18.  
Figure 18. Removing the busbar mounting bolt.  
3. Remove the bolt holding the CT, the threaded stud,  
and the load-side busbar from the Module.  
4. Remove the bolts holding the load-side lug in place.  
Remove the lug.  
5. Remove the L-shaped busbar and CT, if applicable,  
from the assembly, as shown in Figure 19.  
6. Remove the four screws holding the SCR Module to  
the mounting plate, as shown in Figure 20.  
Figure 19. Removing the L-shaped busbar.  
Figure 20. Removing the SCR mounting screws.  
Prices and data subject to change without notice.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
7. Lift out the SCR Module, as shown in Figure 21.  
Retain all parts and hardware for reassembly with  
the replacement Module.  
8. Remove the threaded stud from the SCR Module  
and attach it to the new Module. Tighten to 200 in-  
lb torque.  
9. Clean the heat sink surface of the replacement  
Module with a fine abrasive, such as Scotchbrite.  
Remove all particles from the heat sink surface and  
wipe the SCR mounting surface with a mild solvent.  
Apply a light coat of thermal grease, such as  
Electrolube 2GX to both the SCR and heat sink  
surfaces.  
10. Place the new SCR Module in the proper position on  
the mounting surface. Move the Module back and  
forth several times to evenly distribute the grease on  
the plate.  
Figure 21. Removing the SCR Module from the mounting plate..  
11. Secure the SCR Module to the mounting plate with  
the screws removed earlier. Tighten the screws to 44  
in-lb torque.  
12. Reattach the load-side lug, L-shaped busbar, and  
CT, if applicable. Tighten the mounting bolts to 200  
in-lb torque.  
13. Reattach the busbars to the SCR Module. Tighten  
the mounting bolts to 150 in-lb torque.  
14. Attach the wiring harness of the new SCR Module to  
its mating piece. Attach the harness of the CTs, if  
necessary.  
10  
Prices and data subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASTAT ®-IBP Plus Service Instructions  
Troubleshooting Guide  
This guide is provided for troubleshooting and isolating common problems. It does not cover every possible situation.  
Contact the Customer Support Center at 800-843-3742 if any problem is not resolved by these procedures.  
Sym p t o m o r Erro r & ( Erro r Co d e )  
P o s s ib le Ca u s e  
M e a s u re s t o B e Ta ke n  
Display OFF  
No control voltage.  
Check wire harness and control voltage  
Main breaker tripped or fuse blown  
F1 fuse blown on power supply PCB  
Bad connection of flat ribbon wire  
joining power supply PCB to control  
PCB  
Check and change.  
Verify connectors.  
Check power supply board and logic  
board for 5VDC. Use a DC voltmeter on  
the power supply board, (-) lead of  
voltmeter on the top lead of C6 (located  
next to the black heatsink on the right  
edge of the power supply board) and the  
(+) lead of voltmeter on top lead of Diode  
AD21 or R25 (located on the upper right  
corner of the power supply board.)  
Check and change.  
Equipment does not respond to STOP /  
START controls  
F2 fuse blown on power supply PCB  
Frequency error (admits  
45Hz £ f main £ 65Hz)  
No 1 L1 phase or frequence is out of  
(Ex10) range  
Check 1 L1 phase and/or mains  
frequence  
Overload trip  
(Ex11) Excessive load or excessive current  
during starting  
Verify overload conditions during starting  
time and steady state. Check settings in  
parameters "Nxxx", "Lxxx", and "oxxx"  
Check 1 L1 phase  
Check thyristor module.  
Check ground connections and voltage to  
ground.  
Synchronism loss  
Phase A, B, C thyristor  
(Ex13) Phase 1 L1 lost  
(Ex14) Short circuited thyristor  
(Ex15)  
(Ex16)  
Poor ribbon cable connection  
Check 2 T1 , 4 T2 and 6 T3 phases  
Check for adequate ventilation.  
Check thermostat and wiring  
Check thermistor and wiring, if no  
thermistor terminal 5 and 6 must be  
jumpered  
No output phases  
(Ex17) Heatsink thermostat tripped by  
overheating or defective  
Heatsink thermostat  
Motor thermistor(Ex18)  
Motor thermistor tripped by  
overheating or defective  
Phase A, B, C loss  
(Ex19) No input / output phases  
(Ex20)  
Check power wire harness for 1 L1 ,  
3 L2 , 5 L3 , 2 T1 , 4 T2 and 6 T3  
Verify gate and cathode wire harness.  
Verify thyristors  
(Ex21)  
Defective thyristor or ribbon wire  
harness loose or defective  
Stalled rotor  
Internal error  
(Ex22) Equipment detected stalled motor  
rotor  
Restart equipment and check for an  
appreciable loss in motor speed at any  
time  
Check IC1 and IC8 are correctly inserted  
in their sockets.  
(Ex23) Micro-controller malfunction  
Check for noise on control voltage power  
or line  
Long start time  
Lock-out  
(Ex25) Current limit condition present more  
than2 x ta sec. or 240 sec. (ta =  
acceleration ramp time)  
(Ex27) The time between startings is less  
Increase current limit and / or acceleration  
ramp time  
Check if settings are correct.  
that the adjusted in parameter "LKxx" This protection may be disabled  
(Ex28) The line voltage exceeds of limit set in Check if settings are correct.  
Undervoltage  
Overvoltage  
Undercurrent  
Overcurrent  
(Ex29) parameters "UVxx" or "OVxx"  
(Ex30) The motor current exceeds of limit set Check if settings are correct.  
(Ex31) in parameters "UCxx" or "OCxx" This protection may be disabled  
This protection may be disabled  
Prices and data subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
ASTAT ®-IBP Plus Service Instructions  
Renew al Parts List  
The following parts and assemblies are available as replacement parts for ASTAT-IBP Solid State Starters. Renewal  
parts as furnished may not be identical to the original parts since design changes may have been made in the interim.  
The parts supplied will, however, be interchangeable with the original parts.  
Ca t a lo g Nu m b e r  
Lis t  
P ric e ,  
GO -1 1 G  
$117.00  
117.00  
117.00  
430.00  
430.00  
430.00  
945.00  
945.00  
945.00  
1,512.00  
295.00À  
475.00À  
945.00À  
1800.00À  
2700.00  
140.00  
140.00  
140.00  
140.00  
140.00  
140.00  
140.00  
140.00  
140.00  
140.00  
650.00  
360.00  
40.00  
R e q .  
Q t y.  
De s c rip t io n  
W h e re Us e d  
P h a s e 1  
P h a s e 2  
P h a s e 3  
SCR Module  
QI3KDP  
QIX000111  
QIX000112  
QIX000113  
1/phase  
1/phase  
1/phase  
QI3LDP  
QI3YDP  
QI3MDP  
QI3ZDP  
QIX000114 QIX000115 QIX000116 1/phase  
QIX000117 QIX000118 QIX000119 1/phase  
QIX000120 QIX000121 QIX000122 1/phase  
QIX000123 QIX000124 QIX000125 1/phase  
QIX000126 QIX000127 QIX000128 1/phase  
QIX000129 QIX000130 QIX000131 1/phase  
QIX000132 QIX000133 QIX000134 1/phase  
QI3NDP  
QI3PDP  
QI3QDP  
QI3RDP  
QI3SDP  
Bypass Contactor  
QI3(K,L)DP  
QI3(Y,M)DP  
QI3(Z,N)DP  
QI3(P,Q,R)DP  
QI3SDP  
QIX000135  
QIX000136  
QIX000137  
QIX000138  
QIX000139  
QIX000140  
QIX000141  
QIX000142  
QIX000143  
QIX000144  
QIX000145  
QIX000146  
QIX000147  
QIX000148  
QIX000149  
QIX000150  
QIX000151  
QIX000154  
QIX000155  
QIX000156  
QIX000157  
QIX000158  
QIX000159  
QIX000160  
1
1
1
1
1
Protection Circuit Board  
QI3KDP  
1
QI3LDP  
1
QI3YDP  
1
QI3MDP  
QI3ZDP  
1
1
QI3NDP  
1
QI3PDP  
1
QI3QDP  
1
QI3RDP  
1
QI3SDP  
1
1
Logic Printed Circuit Board with EPROM  
Power Supply PCB  
ALL  
ALL  
1
Current Transformer  
QI3KDP  
1/phase  
1/phase  
2/phase  
2/phase  
2/phase  
1
ALL Others  
QI3(K,L,Y)DP  
QI3(M,Z,N)DP  
QI3(P,Q,R,S)DP  
All, 12-point  
All, 5-point  
120.00  
35.00  
MOV (with terminals and insulators)  
35.00  
35.00  
Terminal Strip (Logic P.C.B.)  
Terminal Strip (Control Power Input to  
ASTAT)  
16.00  
1
10.00  
Fuses on Power Supply Board (Bussman  
Type GMC, 250 Vac)  
F2, ALL, 500mA  
F1, ALL, 2A  
ALL  
QIX000161  
QIX000162  
QIX000163  
1
1
1
3.00  
3.00  
5.00  
Ribbon Cable, Top-Logic Board to Power  
Supply Board  
Ribbon Cable, Bottom-Logic Board to  
Protection Board  
ALL  
QIX000164  
1
6.00  
Thermostat  
QC2K,L,M  
ALL  
QIX000165  
QIX000166  
1
1
10.00  
30.00  
Plastic Cover-ASTAT-IBP Plus  
À List Price, GO-10C2.  
12  
Prices and data subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
These instructions do not cover all details or variations in equipment nor do they provide for every possible  
contingency that may be met in connection with installation, operation, or maintenance. Should further  
information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s  
purposes, the matter should be referred to the GE Company.  
g
GE Industrial System s  
General Electric Company  
41 Woodford Ave., Plainville, CT 06062  
DEH-40417 0901  
© 2001 General Electric Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Earlex Paint Sprayer ASG55 User Manual
Electro Voice Portable Speaker MTL 2B User Manual
Extron electronic Intercom System IPI204 User Manual
Fisher Price Baby Toy C5347 User Manual
Focal Car Speaker 13 WS Be User Manual
Franke Consumer Products Range FTU 3807 I User Manual
Fundex Games Board Games Tic Tac Toe User Manual
GE Clothes Dryer DCCD330EGWC User Manual
GE Noise Reduction Machine GFK 0787B User Manual
Global Upholstery Co High Chair Lounge Chair User Manual