GE Network Router EX2100 User Manual

GEH-6632  
g
GE Industrial Systems  
EX2100Excitation Control  
User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
g
GE Industrial Systems  
Document:  
Issue Date:  
GEH-6632  
2000-09-30  
EX2100Excitation Control  
User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© 2000 General Electric Company, USA.  
All rights reserved.  
Printed in the United States of America.  
These instructions do not purport to cover all details or variations in equipment, nor to  
provide for every possible contingency to be met during installation, operation, and  
maintenance. If further information is desired or if particular problems arise that are not  
covered sufficiently for the purchaser’s purpose, the matter should be referred to GE  
Industrial Systems, Salem, Virginia, USA.  
This document contains proprietary information of General Electric Company, USA and  
is furnished to its customer solely to assist that customer in the installation, testing,  
operation, and/or maintenance of the equipment described. This document shall not be  
reproduced in whole or in part nor shall its contents be disclosed to any third party  
without the written approval of GE Industrial Systems.  
Document Identification: GEH-6632  
EX2100 is a trademark of General Electric Company, USA.  
Cimplicity® is a registered trademark of GE Fanuc Automation North America, Inc.  
Ethernet™ is a trademark of Xerox Corporation.  
Mate-N-Lok® is a registered trademark of Amp Incorporated.  
Windows NT® is a registered trademark of Microsoft Corporation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Symbol Legend  
Indicates a procedure, condition, or statement that, if not  
strictly observed, could result in personal injury or death.  
Indicates a procedure, condition, or statement that, if not  
strictly observed, could result in damage to or destruction of  
equipment.  
Note Indicates an essential or important procedure, condition, or statement.  
EX2100 User's Guide GEH-6632  
Safety Symbol Legend a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This equipment contains a potential hazard of electric shock  
or burn. Only personnel who are adequately trained and  
thoroughly familiar with the equipment and the instructions  
should install, operate, or maintain this equipment.  
Isolation of test equipment from the equipment under test  
presents potential electrical hazards. If the test equipment  
cannot be grounded to the equipment under test, the test  
equipment’s case must be shielded to prevent contact by  
personnel.  
To minimize hazard of electrical shock or burn, approved  
grounding practices and procedures must be strictly followed.  
To prevent personal injury or equipment damage caused by  
equipment malfunction, only adequately trained personnel  
should modify any programmable machine.  
b Safety Symbol Legend  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To:  
GE Industrial Systems  
Documentation Design, Rm. 291  
1501 Roanoke Blvd.  
g
Reader Comments  
General Electric Company  
Salem, VA 24153-6492 USA  
Fax: 1-540-387-8651  
(GE Internal DC 8-278-8651)  
We welcome comments and suggestions to make this publication more useful.  
Your Name  
Todays Date  
If needed, how can we contact you?  
Fax No.  
Phone No.  
E-mail  
Your Companys Name and Address  
Job Site  
GE Requisition No.  
Publication No.  
Your Job Function / How You Use This Publication  
Address  
Publication Issue/Revision Date  
General Rating  
Excellent Good Fair Poor Additional Comments  
Contents  
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
_____________________________________________________________  
_____________________________________________________________  
_____________________________________________________________  
_____________________________________________________________  
_____________________________________________________________  
_____________________________________________________________  
_____________________________________________________________  
_____________________________________________________________  
_____________________________________________________________  
Organization  
Technical Accuracy  
Clarity  
Completeness  
Drawings / Figures  
Tables  
Referencing  
Readability  
Specific Suggestions (Corrections, information that could be expanded on, and such.)  
Page No. Comments  
______  
______  
______  
______  
______  
______  
__________________________________________________________________________________  
__________________________________________________________________________________  
__________________________________________________________________________________  
__________________________________________________________________________________  
__________________________________________________________________________________  
__________________________________________________________________________________  
Other Comments (What you like, what could be added, how to improve, and such.) ________________________________________________  
___________________________________________________________________________________________  
___________________________________________________________________________________________  
___________________________________________________________________________________________  
___________________________________________________________________________________________  
___________________________________________________________________________________________  
___________________________________________________________________________________________  
Overall grade (Compared to publications from other manufacturers of similar products, how do you rate this publication?)  
¡ Superior  
¡ Comparable  
¡ Inferior  
¡ Do not know  
Comment ____________________________________________  
Detach and fax or mail to the address noted above.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
.........................................................................Fold here and close with staple or tape ..........................................................................................  
Place  
stamp  
____________________________  
____________________________  
____________________________  
here.  
GE Industrial Systems  
Documentation Design, Rm. 291  
1501 Roanoke Blvd.  
Salem, VA 24153-6492 USA  
...........................................................................................Fold here first.........................................................................................................  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Chapter 1 Equipment Overview  
1-1  
Introduction............................................................................................................................ 1-1  
System Overview ................................................................................................................... 1-2  
Hardware Overview ............................................................................................................... 1-5  
Software Overview................................................................................................................. 1-6  
Technical Characteristics ....................................................................................................... 1-6  
How to Get Help .................................................................................................................... 1-8  
Related Documents ................................................................................................................ 1-8  
Document Distribution............................................................................................. 1-8  
Chapter 2 Functional Description  
2-1  
Introduction............................................................................................................................ 2-1  
Exciter Hardware ................................................................................................................... 2-2  
Exciter Configurations ........................................................................................................... 2-3  
Power Conversion Cabinet..................................................................................................... 2-5  
Manual Ac Disconnect (Optional)........................................................................... 2-5  
Power Conversion Module (PCM)............................................................................. 2-5  
Gate Pulse Amplifiers (EGPA Board) ..................................................................... 2-6  
Main Dc Contactors. 41A or 41A/41B (Optional)................................................... 2-7  
Free Wheeling Diode De-excitation ........................................................................ 2-7  
Auxiliary Cabinet................................................................................................................... 2-8  
Ac Line-to-Line Filters ............................................................................................ 2-8  
De-excitation Module (EDEX)................................................................................ 2-8  
Shaft Voltage Suppressor......................................................................................... 2-9  
Field Flashing Module............................................................................................. 2-9  
Field Ground Detector (EXAM and EGDM)........................................................... 2-9  
High Voltage Interface – HVI.................................................................................. 2-9  
Control Cabinet.................................................................................................................... 2-10  
Diagnostic Interface (Keypad)............................................................................... 2-10  
Control Module...................................................................................................... 2-11  
Simplex Control System ........................................................................................ 2-12  
Redundant Control System .................................................................................... 2-13  
Control Power Supplies ......................................................................................... 2-14  
Exciter Software................................................................................................................... 2-17  
Auto Reference – AUTO REF............................................................................... 2-20  
AVR Setpoint – EXASP........................................................................................ 2-20  
Automatic Voltage Regulator – AVR.................................................................... 2-20  
Manual Reference – MANUAL REF .................................................................... 2-21  
Field Voltage and Current Regulators - FVR & FCR............................................ 2-21  
Under Excitation Limiter – UEL ........................................................................... 2-22  
Power System Stabilizer – PSS.............................................................................. 2-22  
Operator Interface ................................................................................................................ 2-23  
Turbine Control HMI............................................................................................. 2-23  
Control System Toolbox (toolbox)........................................................................ 2-23  
EX2100 User’s Guide GEH-6632  
Contents i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Printed Wiring Boards Overview  
3-1  
Introduction............................................................................................................................ 3-1  
Control Boards....................................................................................................................... 3-2  
Exciter Backplane (EBKP) ...................................................................................... 3-2  
Digital Signal Processor Board (DSPX).................................................................. 3-2  
ACLA Board............................................................................................................ 3-4  
EISB Board.............................................................................................................. 3-4  
EMIO Board ............................................................................................................ 3-4  
ESEL Board............................................................................................................. 3-5  
I/O Terminal Boards .............................................................................................................. 3-5  
EPCT Board............................................................................................................. 3-5  
ECTB Board ............................................................................................................ 3-6  
EXTB Board ............................................................................................................ 3-6  
EDCF Board ............................................................................................................ 3-6  
EACF Board ............................................................................................................ 3-7  
Bridge and Protection Boards and Modules........................................................................... 3-7  
EGPA Board ............................................................................................................ 3-7  
EXCS Board ............................................................................................................ 3-7  
EDEX Board............................................................................................................ 3-8  
EGDM Module ........................................................................................................ 3-8  
EXAM Module ........................................................................................................ 3-9  
Power Supply Boards............................................................................................................. 3-9  
EPDM Module......................................................................................................... 3-9  
EPBP Backplane...................................................................................................... 3-9  
EPSM Module ....................................................................................................... 3-11  
DACA – Ac to Dc Converter................................................................................. 3-11  
Related Board Publications.................................................................................................. 3-11  
Chapter 4 Terminal Board I/O and Equipment Connections  
4-1  
Introduction............................................................................................................................ 4-1  
Power Connections and Analog I/O....................................................................................... 4-2  
Power Potential Transformer Inputs ........................................................................ 4-3  
Potential and Current Transformer Inputs................................................................ 4-3  
Analog Input ............................................................................................................ 4-3  
Customer Contact I/O ............................................................................................................ 4-4  
Power Supply Inputs .............................................................................................................. 4-6  
Line Filter Connections.......................................................................................................... 4-7  
Exciter Internal I/O ................................................................................................................ 4-8  
Exciter AC Feedback............................................................................................... 4-8  
Exciter DC Feedback............................................................................................... 4-8  
De-Excitation ....................................................................................................................... 4-11  
Crowbar................................................................................................................................ 4-14  
Field Ground Detector.......................................................................................................... 4-14  
Field Flashing....................................................................................................................... 4-16  
Dc Field Flashing Settings..................................................................................... 4-16  
Flashing Control Sequence .................................................................................... 4-16  
Shaft Voltage Suppressor..................................................................................................... 4-18  
Data Highway Connections.................................................................................................. 4-19  
Control System Toolbox Connection................................................................................... 4-20  
Chapter 5 Diagnostic Interface-Keypad  
5-1  
Introduction............................................................................................................................ 5-1  
Using the Pushbuttons............................................................................................................ 5-2  
Reading the Display............................................................................................................... 5-5  
ii Contents  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Changing Display Units........................................................................................... 5-7  
Adjusting Display Contrast...................................................................................... 5-7  
Status Screen.......................................................................................................................... 5-8  
Reading the Meters .................................................................................................. 5-8  
Alternate Status Screen (Display I/O).................................................................................... 5-8  
Using the Menus .................................................................................................................... 5-9  
Viewing and Resetting Faults ................................................................................................ 5-9  
Editing Parameters ............................................................................................................... 5-10  
Parameter Backup.................................................................................................. 5-11  
Firmware and Hardware Information................................................................................... 5-13  
Protecting the Keypad.......................................................................................................... 5-14  
Modifying the Protections...................................................................................... 5-14  
Appendix A Warranty and Renewal Parts  
A-1  
Introduction........................................................................................................................... A-1  
Identifying the Part................................................................................................................ A-2  
Renewal Parts List .................................................................................................. A-2  
Part Number Structure ............................................................................................ A-2  
Warranty Terms .................................................................................................................... A-4  
How to Order Parts ............................................................................................................... A-5  
Data Nameplate....................................................................................................... A-5  
ML Number ............................................................................................................ A-5  
Appendix B Ratings and Specifications  
B-1  
Glossary of Terms  
Index  
EX2100 User’s Guide GEH-6632  
Contents iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
iv Contents  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1 Equipment Overview  
Introduction  
The EX2100ä Excitation Control (EX2100 or exciter) produces the field excitation  
current to control generator ac terminal voltage and/or the reactive volt-amperes. It is  
a full static excitation system designed for generators on both new and retrofit steam,  
gas, and hydro turbines.  
This chapter introduces the exciter and defines the document contents. Its purpose is  
to present a general product overview as follows:  
Section/Topic  
Page  
System Overview..................................................................................................... 1-2  
Hardware Overview................................................................................................. 1-5  
Software Overview .................................................................................................. 1-6  
Technical Characteristics......................................................................................... 1-6  
How to Get Help...................................................................................................... 1-8  
Related Documents.................................................................................................. 1-8  
Document Distribution ..................................................................................... 1-8  
Chapter 2  
Chapter 3  
Chapter 4  
Chapter 5  
Appendix A  
Appendix B  
Glossary  
Functional Description  
Printed Wiring Boards Overview  
Terminal Boards I/O and Equipment Connections  
Diagnostic Interface (Keypad)  
Warranty and Renewal Parts  
Ratings and Specifications  
EX2100 User’s Guide GEH-6632  
Chapter 1 Equipment Overview 1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Overview  
The exciter is a flexible modular system that can be assembled to provide a range of  
available output currents and several levels of system redundancy. These options  
include power from a potential, compound, or auxiliary source. Single or multiple  
bridges, warm backup bridges, and simplex or redundant controls are available. An  
overview of the turbine generator excitation system is shown in Figure 1-1.  
Power for the exciter is drawn from a power potential transformer connected to the  
generator terminals, or from an excitation transformer connected to an auxiliary bus.  
Generator line current and stator output voltage are the primary feedbacks to the  
exciter, and dc voltage and current is the controlled output to the exciter field.  
The architecture supports Ethernet LAN (Unit Data Highway) communication with  
other GE equipment including the GE Control System Toolbox (toolbox) for  
configuration, the turbine control, the LCI Static Starter, and the HMI (operator  
interface).  
Figure 1-2 is a simplified one line diagram of the exciter showing the power source,  
generator current and voltage measurements, control module, power conversion  
module (PCM), and protection circuits. In the potential source system, the secondary  
of the PPT is connected to the input of a 3-phase full-wave inverting thyristor bridge.  
The inverting bridge provides both positive and negative forcing voltage for  
optimum performance. Negative forcing provides fast response for load rejection and  
de-excitation.  
Excitation control results from phase controlling the output of the SCR bridge  
circuit. The SCR firing signals are generated by digital regulators in the controller.  
In the redundant control option (Figure 1-2), either M1 or M2 can be the active  
master control, while C monitors both to determine which should be the active and  
which the standby controller. Dual independent firing circuits and automatic tracking  
is used to ensure a smooth transfer to the standby controller.  
Either simplex or redundant  
control is available.  
1-2 Chapter 1 Equipment Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Transmission Line  
Step-up Transformer  
Air Circuit Breaker (52G)  
Current Transformers (CTs)  
Potential  
Transformers  
(PTs)  
Exciter Power  
Potential  
Transformer (PPT)  
Turbine  
Generator  
Controlled  
dc to Field  
Power Conversion  
Module (Bridge)  
EX2100  
Exciter  
Ac Source  
Control,  
Sequencing,  
Protection  
Data Highway to Turbine  
Control, HMI, & DCS  
Instrumentation  
Figure 1-1 Overview of Generator and Exciter System  
EX2100 User’s Guide GEH-6632  
Chapter 1 Equipment Overview 1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC DC  
Control  
AC  
Load  
Diagnostic  
Interface  
(Keypad)  
Unit  
Data  
Highway  
Power  
Supplies  
Customer I/O  
Current  
CT  
I/O  
PT  
Voltage  
Bridge I/O  
AC CB  
AC  
Aux  
Generator  
Source  
Control  
M1  
Control  
C
Control  
M2  
PPT  
PCT (3)  
Compound  
Source only  
Linear  
Reactors  
(3)  
Gating Selector  
AC CB or  
Disconnect  
Line Filter  
Power  
Conversion  
Modules  
(Bridge)  
AC  
DC  
Flashing  
Control  
DC CB or  
Contactor  
Shunt  
Active Field  
Ground Detector  
PT: Potential Transformer  
CT: Current Transformer  
CB: Circuit Breaker  
I/O: Input/Output  
PCT: Power Current Transformer  
PPT: Power Potential Transformer  
Deexcitation  
Crowbar  
Shaft Voltage Suppression  
Figure 1-2. Exciter One Line Diagram  
1-4 Chapter 1 Equipment Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware Overview  
The EX2100 hardware is contained in three cabinets as follows:  
control cabinet for the control, communication, and I/O boards  
auxiliary cabinet for field flashing and protection circuits such as de-excitation  
and shaft voltage suppression  
power conversion cabinet for the power SCR cells, cooling fans, dc contactors,  
and ac disconnect  
The exciter's power converter consists of bridge rectifiers, resistor/capacitor filter  
configurations, and control circuitry. An outside view of the cabinets is shown in  
Figure 1-3. The components and bridge size vary for different excitation systems and  
for the power output required.  
Control  
Cabinet  
Auxiliary  
Cabinet  
Contactors &  
Disconnects  
Fan  
Drawers  
Power  
Conversion  
Cabinet  
Keypads  
Figure 1-3. Exciter Cabinets  
EX2100 User’s Guide GEH-6632  
Chapter 1 Equipment Overview 1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Software Overview  
Microprocessor-based controllers (ACLA and DSPX) execute the exciter control  
code. The software consists of modules (blocks) combined to create the required  
system functionality. Block definitions and configuration parameters are stored in  
flash memory, while variables are stored in random-access memory (RAM).  
The exciter application software emulates traditional analog controls. It uses an open  
architecture system, with a library of existing software blocks configured from the  
toolbox. The blocks individually perform specific functions, such as logic gates,  
proportional integral (P.I.) regulators, function generators, and signal level detectors.  
The control selects one of two modes, either generator voltage regulation (Auto  
Regulation), or direct control (voltage or current, depending upon the application).  
Generator protection functions are integrated into the control, including over and  
under-excitation limiting, power system stabilization, and V/Hz limiting.  
The blocks can be interrogated while the exciter is running by using the toolbox. The  
dynamically changing I/O values of each block can be observed in operation, which  
is valuable during startup or troubleshooting.  
Technical Characteristics  
Summary characteristics for the EX2100 are as follows; for further details refer to  
Appendix B.  
Unit Specific ratings are provided on equipment nameplate and  
supercede all information herein.  
EX2100 Characteristics  
Description  
Power Converter Module (PCM)  
Single bridge rating  
1,000 and 2,000 A dc at up to 1,000 V ac  
Parallel bridge rating  
8,000 A dc at up to 1,500 V ac; with up to 6 bridges  
150% of design Amperes (EDA) for 30 s at 40 ºC  
Forcing requirements  
Power Sources  
Power for the PCM – Voltage source  
Auxiliary bus  
Generator terminals  
Compound source  
600 or 1,000 V ac versions  
Power Input for the PCM - VA  
3251 kVA (1,000 V version)  
Power for the PCM - Frequency  
Flashing power  
3-phase 50/60 Hz  
Battery source 125 V dc or 250 V dc, with up to 200 A for at least 10 s  
240 or 480 V ac, 50/60 Hz single-phase auxiliary source  
For two ac sources, or one ac and one dc source:  
Control power  
Nominal 120 V ac ±15%, with 1 DACA, 10 A rms max.  
Battery source, 125 V dc, range 80 – 140 V dc, 10.6 A dc max.  
1-6 Chapter 1 Equipment Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input/Output  
QTY  
Potential transformers (PTs)  
2
3-phase standard, single phase available  
120 V ac nominal  
1 VA nominal burden  
Current transformers (CTs, 1 or 5 A)  
2
Any two phases, single phase available  
1 VA nominal burden  
86G dedicated contact input  
52G dedicated contact input  
Trip rated contact outputs  
1
1
2
open for trip  
closed for online  
At 125 V dc with relay break characteristics:  
Resistive load 0.5 A  
Inductive load 0.2 A  
General Purpose contact inputs  
6
4
Customer contacts, 70 V dc supplied by ECTB  
General Purpose Form C contact outputs  
At 125 V dc with relay break characteristics:  
Resistive load 0.5 A  
Inductive load 0.1 A  
± 10 V differential amplifier input  
Thermal  
1
Base controls cabinet  
Continuous operation in a 0 to 40 ºC ambient environment, with 5 to  
95% humidity, non-condensing  
Base power conversion and auxiliary  
cabinet  
Continuous operation in a 0 to 40 ºC ambient environment, with 5 to  
95% humidity, non-condensing  
Cabinet Dimensions & Weight  
Redundant control with dual PCM  
redundant converter in a three-cabinet  
lineup  
Width 141.74 in (3600 mm)  
Height 104.32 in (2650 mm)  
Depth  
31.5 in (800 mm)  
Weight of Converter cabinet  
3,600 lbs  
5,600 lbs  
Weight of Total Lineup (Converter,  
Control, and Auxiliary cabinets)  
Cabinet type, control & auxiliary  
enclosures  
NEMA 1 (IEC IP 20), convection cooled  
Cabinet type, power conversion  
Power and Control Cable Access  
NEMA 1 (IEC IP 20), forced air cooled  
Entrances from the top and/or bottom  
EX2100 User’s Guide GEH-6632  
Chapter 1 Equipment Overview 1-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
How to Get Help  
If help is needed beyond the instructions provided in the drive system  
documentation, contact GE as follows:  
“+” indicates the  
international access code  
required when calling from  
outside of the USA.  
GE Industrial Systems  
Product Service Engineering  
1501 Roanoke Blvd.  
Salem, VA 24153-6492 USA  
Phone: + 1 888 GE4 SERV (888 434 7378, United States)  
+ 1 540 378 3280 (International)  
Fax:  
+ 1 540 387 8606 (All)  
Related Documents  
The following documents also apply to the exciter and may assist in understanding  
the system.  
GEI-100256C EX2100 Receiving, Storage, & Handling  
GEH-6631 EX2100 Installation and Startup Guide  
GEH-6633 EX2100 Troubleshooting, Preventive and Online Maintenance  
GEH-6403 Control System Toolbox for Mark VI Turbine Controller  
Printed Wiring Board (GEI) publications, refer to Chapter 3.  
Document Distribution  
GE Industrial Systems supplies product documents to its customers to support the  
equipment provided for each requisition. The contract documents define the terms of  
the document distribution.  
If provided (per contract) the following documents contain requisition information  
about the drive system.  
Requisition drawings, including outlines, layouts, and elementary diagrams  
Renewal parts listing  
Note If differences exist between the general product documentation and the  
requisition documentation, the requisition documentation should be considered the  
more exact representation of your equipment or system configuration.  
1-8 Chapter 1 Equipment Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Functional Description  
Introduction  
This chapter describes the function of the EX2100 static exciter and the individual  
control and protection circuits. Power supplies and the distribution of power is also  
covered. The functional description information is organized as follows:  
Section  
Page  
Exciter Hardware ..................................................................................................... 2-2  
Exciter Configurations............................................................................................. 2-3  
Power Conversion Cabinet ...................................................................................... 2-5  
Manual Ac Disconnect (Optional).................................................................... 2-5  
Power Converter Module (PCM)...................................................................... 2-5  
Gate Pulse Amplifiers (EGPA Board).............................................................. 2-6  
Main Dc Contactors. 41A or 41A/41B (Optional)............................................ 2-7  
Free Wheeling Diode De-excitation ................................................................. 2-7  
Auxiliary Cabinet..................................................................................................... 2-8  
Ac Line-to-Line Filters..................................................................................... 2-8  
De-excitation Module (EDEX)......................................................................... 2-8  
Shaft Voltage Suppressor.................................................................................. 2-9  
Field Flashing Module...................................................................................... 2-9  
Field Ground Detector (EXAM and EGDM) ................................................... 2-9  
High Voltage Interface – HVI .......................................................................... 2-9  
Control Cabinet...................................................................................................... 2-10  
Diagnostic Interface (Keyad).......................................................................... 2-10  
Control Module............................................................................................... 2-11  
Simplex Control System................................................................................. 2-12  
Redundant Control System............................................................................. 2-13  
Control Power Supplies .................................................................................. 2-14  
Exciter Software .................................................................................................... 2-17  
Auto Reference – AUTO REF........................................................................ 2-20  
AVR Setpoint – EXASP................................................................................. 2-20  
Automatic Voltage Regulator – AVR............................................................. 2-20  
Manual Reference – MANUAL REF ............................................................. 2-21  
Field Voltage and Current Regulators - FVR & FCR..................................... 2-21  
Under Excitation Limiter – UEL .................................................................... 2-22  
Power System Stabilizer – PSS ...................................................................... 2-22  
Human Machine Interface (HMI) .......................................................................... 2-23  
Mark VI HMI.................................................................................................. 2-23  
Toolbox........................................................................................................... 2-23  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exciter Hardware  
The EX2100 exciter consists of the following basic components.  
Power Conversion Module (PCM) and cooling fans  
Power potential transformer (PPT) (mounted separate from exciter)  
Line-to-line filters  
Shaft voltage suppressor  
De-excitation module  
Diagnostic Interface (keypad)  
Controllers and I/O boards  
Control power supplies  
Optional components that can be added to the exciter are:  
Warm backup bridge configuration  
Multibridge configuration for high current requirements  
Compound power source (separate from exciter)  
Auxiliary power source (bus-fed)  
Crowbar module (for hydro and other special applications)  
Dc Disconnect  
Field ground detector  
Redundant ac source for power supply  
Ac disconnect  
Field flashing module  
Redundant controllers providing a Triple Modular Redundant (TMR) system  
GE Control System Toolbox (toolbox) for configuration  
The control hardware is basically the same for the different types of excitation. The  
power conversion hardware is defined by application requirements, which therefore  
determines the exciter bridge size.  
2-2 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exciter Configurations  
EX2100 Exciters can be supplied with single or redundant control, and with single or  
redundant bridges. Variations of the single control type are shown in Figure 2-1.  
Simplex Control with  
Single PCM  
Simplex Control with  
Parallel PCMs  
PCM PCM PCM PCM PCM PCM  
Control with  
I/O and  
Operator  
Keypad  
Control with  
I/O and  
Operator  
Keypad  
PCM  
1
2
3
4
5
6
Figure 2-1. Simplex Control Configurations  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exciters with dual (redundant) control are shown in Figure 2-2. Multiple PCMs can  
be supplied in simplex, warm backup, or redundant n+1 or n+2 modes (with n+1 or  
n+2 equal to 6).  
Dual Control with  
Single PCM  
Dual Control with  
Warm Backup PCMs  
M1 Control,  
M1 Control,  
I/O and  
Operator  
Keypad  
I/O and  
Operator  
Keypad  
PCM  
PCM  
PCM  
M2 Control,  
I/O and  
Operator  
Keypad  
M2 Control,  
I/O and  
Operator  
Keypad  
C Control  
Selection  
Logic &  
C Control  
Selection  
Logic &  
Protection  
Protection  
Dual Control with Parallel PCMs  
M1 Control,  
I/O and  
Operator  
Keypad  
PCM  
1
PCM  
2
PCM  
3
PCM  
4
PCM  
5
PCM  
6
M2 Control,  
I/O and  
Operator  
Keypad  
C Control  
Selection  
Logic &  
Protection  
Figure 2-2. Dual Control System Configurations  
2-4 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Conversion Cabinet  
The Power Conversion cabinet contains the Power Conversion Module (PCM), the  
Exciter Gate Pulse Amplifier (EGPA) board, ac circuit breaker, and the dc circuit  
contactor. Three-phase power for the PCM comes from a PPT external to the exciter.  
The ac supply comes into the cabinet through the ac circuit breaker (if supplied), and  
is filtered by 3-phase line filters in the auxiliary cabinet.  
Manual Ac Disconnect (Optional)  
The manual ac disconnect switch serves as a disconnect device between the  
secondary of the power potential transformer and the static exciter. It is a molded  
case, 3-phase, non-automatic, panel-mounted switch, which is manually operated for  
isolating the ac input supply. It is a no-load disconnect device.  
Power Conversion Module (PCM)  
The exciter PCM includes the bridge rectifiers, dc leg fuses, thyristor protection  
circuitry (for example, snubbers, filters, and fuses) and leg reactor assemblies. The  
components vary for different bridge ratings based on the power output required.  
Bridge Rectifier  
Each bridge rectifier is a 3-phase full-wave thyristor bridge The bridge has six SCRs  
(thyristors) controlled by the Exciter Gate Pulse Amplifier board (EGPA) as shown  
in Figure 2-3. Heat is dissipated through large aluminum cooling fins and forced air  
flow from overhead fans.  
Leg Reactors and Cell Snubbers  
The commutating reactors are located in the ac legs feeding the SCRs, and the  
snubbers are an RC circuit from the anode to the cathode of each SCR. The cell  
snubbers, line-to-line snubbers and line reactors together perform the following  
functions to prevent misoperation of the SCRs.  
Limit the rate of change of current through the SCRs and provide a current dump  
to aid in starting conduction.  
Limit the rate of change in voltage across the cell and, during cell commutation,  
limit the reverse voltage that occurs across the cell.  
The SCR snubbers include PRV resistors to limit the peak reverse voltage. These  
resistors can be removed if required.  
Three-phase input power is fed to the bridge from the secondary of the PPT, either  
directly or through an ac breaker or disconnect, and a line-to-line filter. With  
inverting bridge designs, the bridge is capable of negative forcing voltage, which  
provides fast response for load rejection and de-excitation. The dc current output of  
the bridge is fed through a shunt, and on some designs a contactor (41A or both 41A  
and 41B) to the generator field. The bridge design utilizes dc leg fuses to protect the  
SCRs from overcurrrent.  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Current Shunt  
A dc shunt provides the bridge output current feedback signal. The mV output signal  
is input to a differential amplifier on the EDCF board. The amplifier output voltage  
controls the frequency of an oscillator, which generates a fiber-optic signal sent to  
the control module. The bridge output voltage feedback signal is generated in a  
similar way.  
EDCF provides dc current  
and voltage feedback  
To dc Breaker,  
Shunt, and  
Generator Field +  
FU3A  
FU3B  
FU1A  
FU1B  
FU2A  
FU2B  
SCR1  
SCR2  
SCR3  
Ac power  
Input  
Snubber 1  
Snubber 4  
Snubber 3  
Snubber 6  
Snubber 2  
Snubber 5  
SCR4  
FU4A  
SCR5  
SCR6  
FU6A  
FU6B  
FU4B  
FU5A  
FU5B  
Gen. Field -  
J3  
J1  
J4  
J6  
J2  
J5  
Gate Driver Inputs from EGPA Board  
Figure 2-3. Power Bridge  
Gate Pulse Amplifiers (EGPA Board)  
The EGPA board interfaces the control to the Power Bridge. EGPA takes the gate  
commands from the ESEL board in the controller, and generates the gate firing  
pulses for six SCRs (Silicon Controlled Rectifiers). It is also the interface for current  
conduction feedback, and bridge airflow and temperature monitoring.  
The gate pulse amplifiers  
directly control the SCRs.  
On a new exciter, an RTD is used to monitor the temperature and generate alarms  
instead of the Klixon switches. Additional switches actuated by fan rotation monitor  
cooling air flow across the bridge. On an exciter controls only retrofit, the exciter  
may have provisions for accepting feedback from two thermal switches mounted  
on the SCR heatsink assemblies. One thermal switch opens at the alarm level  
(170 °F (76 °C)) and the other at the trip level (190 °F (87 °C)). These switches  
are wired to the EGPA board and may require retrofitting into the existing bridge. If  
either switch opens, a bridge overtemperature alarm is generated. If both switches  
open, a fault and a trip are generated.  
2-6 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cooling Fan Assembly  
The SCR bridge assembly is cooled with forced air. From two to six overhead fans  
are used, depending on the bridge rating and redundancy requirements. The fans are  
powered by single-phase 115 V ac supplied by the customer. In redundant  
applications, a fan may be replaced while the exciter is running.  
Main Dc Contactors. 41A or 41A/41B (Optional)  
The main dc contactor (at the output of the power conversion module) provides a  
disconnect between the power conversion module and the generator field. The  
contactor picks up when the running mode is selected and no fault exists in the  
excitation. The contactors are normally actuated using pilot relays on the EXTB  
board driven by the controller. The auxiliary contacts from the contactor are routed  
back through the EXTB board as feedback signals.  
Free Wheeling Diode De-excitation  
De-excitation, the dissipation of the field current after the dc contactor opens, can be  
done with a free wheeling diode. This diode is connected from the generator field  
negative lead (anode) to the positive lead (cathode). The reverse voltage causes  
current to flow through the diode, and the field resistance causes the current decay.  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auxiliary Cabinet  
The auxiliary cabinet is located next to the power conversion cabinet and contains  
modules to protect the generator and provide startup dc power. Modules for filtering  
the incoming ac power, for de-excitation, shaft voltage suppression, and field  
flashing are mounted in this cabinet.  
Ac Line-to-Line Filters  
Fuse protected line-to-line series RC filter circuits (snubbers) are provided to damp  
the ac system to prevent voltage spikes at the completion of SCR commutation.  
There are two styles of filters employed depending on the voltage. The 600 V filter  
uses RC circuits and MOVs. The 1000 V filter uses the 600 V version with  
additional RC circuits. Refer to Chapter 4 for details and connections.  
De-excitation Module (EDEX)  
During any shutdown, the energy stored in the generator field must be dissipated. In  
a normal shutdown, a stop is initiated by an operator. The bridge is fired at retard  
limit and sufficient time is allowed for the field to decay before the field contactors  
are opened. During an abort stop (trip), the field contactors are opened immediately.  
The stored field energy must be dissipated through some other means.  
SCR De-excitation Module (EDEX)  
For customers requiring a rapid de-excitation, an SCR de-excitation module is  
provided. In the EDEX module, an SCR is fired to provide a conduction path  
through the field discharge resistor (or inductor) for the field current to flow and  
dissipate the field energy.  
The de-excitation module has dual independent firing control circuits. Each is  
activated by a parallel combination of auxiliary contacts representing the status of  
the field contactor(s), bridge ac supply breaker, and exciter bridge operating state.  
Any one of these paths can gate the de-excitation SCR which does not conduct  
unless the field voltage is inverted. If neither firing control circuit can fire the SCR, it  
is fired on overvoltage when the anode to gate voltage on the SCR exceeds the break  
over voltage of the breakover diode string connected between the anode and gate.  
De-excitation modules can be paralleled for larger excitation systems.  
Thyrite  
In systems that do not use the standard de-excitation module, a thyrite is connected  
across the dc output buses of the thyristor bridge. This protects the thyristors from  
high peak inverse voltages, which may occur as a result of abnormal generator  
operation. These are typically only supplied on salient pole generators.  
2-8 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Shaft Voltage Suppressor  
Excitation systems, which produce a dc voltage from ac through a solid state  
rectification process, produce ripple and spike voltages at the exciter output. Due to  
their rapid rise and decay times, these voltages are capacitively coupled from the  
field winding to the rotor body. This creates a voltage on the shaft relative to ground.  
Shaft voltage, if not effectively controlled, can be damaging to both journals and  
bearings. The shaft voltage suppressor is a filter that conducts the high frequency  
components of the induced voltages to ground. (This filter is shipped loose in some  
cases, otherwise it is part of the lineup).  
The Shaft Voltage Suppressor  
protects the shaft bearings.  
Field Flashing Module  
The field flashing module is provided on generator terminal fed excitation systems. It  
supplies initial exciter current and builds generator voltage, supplying approximately  
10% - 15% of no-load field current from the station batteries during the startup  
sequence. If large machines require ac field flashing, the ac power is supplied  
through an isolation transformer. Both designs require customer supplied power.  
Field Ground Detector (EXAM and EGDM)  
The generator field winding is electrically isolated from ground. The existence of  
one ground usually does not damage the rotor. However, the presence of two or  
more grounds in the field winding path causes magnetic and thermal imbalances and  
localized heating, which may damage the rotor forging or other metallic parts.  
The field ground detector  
protects the generator shaft.  
The function of the field ground detector is to detect a ground path from any exciter  
component connected to and including the main field windings.  
The Exciter Attenuator Module (EXAM) drives the electrical center of the field  
winding with a low frequency ac voltage relative to ground. To detect the current  
flow, the voltage across a sensing resistor is picked up by EXAM and measured by  
the EGDM module. This signal is sent over a fiber-optic link to the controller where  
it is monitored and alarmed. The EGDM boards (1 for simplex and 3 for redundant)  
are mounted in the control power supply module located in the control cabinet.  
High Voltage Interface – HVI  
The HVI contains the ac and dc bus, plus the line filter fuses. It also contains two  
terminal boards providing bridge feedback to the control and the EXAM board. The  
EACF board accepts incoming PPT ac voltage and air core CT current signals. It has  
transformers to isolate the voltages and produce low level signals. The EDCF board  
measures the bridge dc current and voltage, and sends it over fiber-optics to the  
control.  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Cabinet  
The control cabinet contains the keypad control rack, control power distribution  
module and supplies, and I/O terminal boards.  
Diagnostic Interface (Keypad)  
The keypad is a local operator interface that is mounted on the control cabinet door.  
Refer to Figure 2-4 for a view of the keypad and a summary of the operator and  
maintenance functions available. Chapter 5 describes the keypad in detail.  
A second keypad is provided  
for redundant controls.  
EX2100 Excitation Control  
g
Exciter Health  
& State Icons  
FVR Feedback  
0.0 Volts  
FldCurrAmps  
0.00 Amps  
0%  
0%  
100% 150%  
100% 150%  
-30%  
-30%  
Vmag  
Imag  
Watts  
0.00  
Freq_Hz  
0.00  
Balance Meter  
0.00  
Vars  
60.00  
0.00  
0.00  
On  
Off  
Exciter Control  
Navigation  
Run (Green)  
Stop (Red)  
Reset  
Auto  
Status  
Faults  
Command  
Man  
Menu  
Menu  
Voltage Level  
Escape  
Enter  
Display:  
Pushbuttons:  
Status screens provide analog and digital  
Organized into functional groups:  
representation of exciter functions and values.  
Navigation buttons for using the menu  
Exciter Control buttons  
Menu screens provide text-based access to  
parameters, wizards, and faults.  
Run and Stop buttons  
Figure 2-4. Diagnostic Interface – Keypad  
Start/stop commands, regulator transfer commands, and regulator activation  
commands can be issued from the keypad. The keypad also includes meter displays  
indicating system conditions such as generator MW and MVARs, field current and  
voltage, and regulator balance. Diagnostic displays such as the alarm history display  
provide system information for maintenance and troubleshooting.  
2-10 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Module  
The control module is a VME-style rack with boards cable connected to the I/O  
terminal boards. This rack is divided into three independently powered sections for  
the M1, M2, and C controllers. Each controller consists of control and I/O processor  
boards. If the rack contains only the M1 controller then it is a simplex control  
system; if the rack contains all three controllers then it is a redundant control system.  
The control and I/O processor boards are as follows:  
Microprocessor-based Application Control Layer Module (ACLA) controller,  
with LAN Ethernet port  
Microprocessor-based Digital Signal Processor (DSPX) controller  
Exciter ISBus Board (EISB), with fiber-optic communication with the bridge  
feedback board  
Exciter Main I/O Board (EMIO), with control of pilot relays and gating  
commands to the ESEL board  
Exciter Selector Board (ESEL), with gate pulse distribution from the active  
controller to the EGPA.  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Simplex Control System  
The interconnections between the simplex control and the terminal boards,  
generator protection modules, and power supply are shown in Figure 2-5. Only one  
EPSM power supply is used but this can have both ac and dc supplies for increased  
reliability.  
Ethernet Data Highway to  
Mark VI, LCI, and HMI  
Control Module M1  
Keypad  
To Flashing  
Computer (Tool)  
EXTB  
panel  
3-phase  
Voltage  
Sensing  
53A  
pilot  
41  
close  
PT  
PT  
PT  
PT  
41 Device  
De-  
excitation  
3-phase  
Current  
Sensing  
53B 41  
pilot trip  
Crowbar  
CT  
CT  
70 V dc  
125 Vdc  
De-ex  
pilot  
EPCT  
Contact  
Inputs  
TRIP  
86  
2nd  
TRIP  
Gate Pulse Amplifier  
Contact  
Outputs  
EGPA  
70 Vdc  
To SCRs  
125Vdc  
Field Current  
& Voltage  
Fiber-optic Feedback  
5 Vdc  
EDCF  
ECTB  
70 Vdc  
EPSM  
EGDM  
PPT and air  
core CT  
ac feedbacks  
15 Vdc  
24 Vdc  
Power  
Supply  
Field  
Ground  
Detector  
EACF  
EXAM  
De-  
excitation  
EDEX  
GPA power  
Coil Power  
EPDM  
125 Vdc  
Option:  
DACA  
Rectified ac  
125 V dc  
Battery  
Optional:  
Crowbar  
Figure 2-5. Simplex Control and Cabling to Terminal Boards  
2-12 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Redundant Control System  
A redundant control system has three controllers and three redundant power supplies,  
one for each controller. The power supply rack also holds three ground detector  
modules. Figure 2-6 shows three EDCF boards, and there can be three EPCT boards,  
if required.  
Up to two Ethernet cables are connected to the ACLA controllers (one to M1 and  
one to M2) for redundant communication with the turbine control and HMIs. Two  
keypads are shown connected to M1 and M2. Both keypads have access to the  
information in controller C.  
Ethernet Data Highway to Turbine Control and HMI  
Keypad  
M1  
Keypad  
C
EBKP  
Backplane  
PT PT  
PT PT  
M2  
EXTB  
To Flashing  
panel  
53A  
41  
pilot close  
Fan-out  
circuits  
41 Device  
41  
close  
53A  
pilot  
De-  
53A  
41  
excitation  
CT  
pilot close  
53B  
pilot  
41  
trip  
CT  
Crowbar  
-125Vdc  
53B  
pilot  
41  
trip  
De-ex  
pilot  
EPCT  
70V  
70V  
41  
trip  
53B  
pilot  
TRIP  
86  
Tool  
Gate Pulse Amplifiers  
2nd  
TRIP  
EGPA  
125Vdc  
EGPA  
125Vdc  
EDCF  
70V  
Fiber-optic Field  
V & I feedback  
ECTB  
EDCF  
EDCF  
P24V  
P24V  
70V  
P24V  
PN24V  
70V  
70V  
PN24V  
PN24V  
E
E
E
G
D
M
G
D
M
G
D
M
PPT and air core CT  
(AC) Feedbacks  
EPSM  
EPSM  
Power  
Supply  
EPSM  
Power  
Supply  
Power  
Supply  
EACF  
EDEX  
De-excitation  
125 Vdc  
Coil Power  
EPBP  
back  
plane  
EPDM  
EXAM  
Attenuator  
GPA power  
Field  
Optional:  
Crowbar  
125 V dc  
Battery  
Ground  
Detector  
EGDM  
Option:  
DACA  
Rectified ac  
Figure 2-6. Redundant Control System Cabling  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controller C  
Controller C is only used with redundant systems. It is mounted in the control rack  
and is physically similar to the M1 and M2 controllers, however, C is not responsible  
for bridge firing and therefore does not contain an ESEL, or ACLA board.  
Controller C receives the same feedback voltage and current inputs as the other  
controllers and contains similar software. Its purpose is to monitor the active and  
backup controllers (M1 or M2) and initiate appropriate protective responses in the  
event the system conditions exceed the defined regulation boundaries. Input and  
output signal voting takes place in all three controllers, which are linked in a Triple  
Modular Redundant (TMR) controller configuration.  
Each controller contains up to six boards, interconnected through the backplane as  
shown in the simplified diagram of Figure 2-7.  
Ethernet Data Highway (EGD, Modbus)  
To plant controls  
Serial  
Serial  
Modbus  
Modbus  
ACLA  
M1  
DSPX  
M1  
DSPX  
M2  
ACLA  
M2  
DSPX  
C
I/O  
I/O  
I/O  
DPM  
DPM  
Communication  
across backplane  
ISBus  
Figure 2-7. Communication between Redundant Control Boards  
Control Power Supplies  
Power for the controls come from the Exciter Power Distribution Module (EPDM).  
This is supplied by a 125 V dc source and one or two 115 V ac sources. The ac  
source is passed through an ac/dc converter (DACA) as shown in Figure 2-8. The  
resulting 125 V dc is diode coupled with the other dc sources to create a dc bus that  
feeds the control modules and gate pulse amplifier boards. Fused outputs from the  
EPDM feed power to the EGPA boards, EXTB, and the Exciter Power Backplane  
(EPBP). Each output has an LED indication and an on/off isolation switch.  
Redundant supplies provide  
high reliability.  
The EPDM mounts on the left side of the Exciter Power Supply rack. Up to three  
Exciter Power Supply Modules (EPSM) mount in the EPBP backplane and provide  
logic level power to the controller(s). The EPSMs are fed by 125 V dc from the  
EPDM, and generate supply voltages of +5 V dc, ±15 V dc, and +24 V dc. In  
2-14 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
addition there is an isolated 70 V dc output for use by EXTB and ECTB for contact  
wetting.  
Up to three ground detection modules (EGDM) are also mounted in the EPBP, as  
shown in Figure 2-9. These communicate with the EXAM module, which is located  
in the auxiliary cabinet.  
Exciter Power Distribution Module (EPDM)  
N125V  
P125V  
TB1  
1
J8A  
J8B  
FU1  
3.15A  
2
3
4
5
6
1
2
P125  
DS1  
G
To  
EGPA1  
SW1  
FU2  
3.15A  
125  
V dc  
Filter  
FU3  
3.15A  
1
2
DS2  
G
To  
EGPA2  
SW2  
FU4  
3.15A  
N125  
FU5  
3.15A  
J8C1  
115 Vac DACA #1  
7
JDACA1  
DS3  
G
7
JDACA1  
15  
16  
AC1 Hot  
SW3  
To  
EGPA3  
FU6  
3.15A  
2
1
1
10  
9
10  
9
115  
Vac  
Filter  
17  
18  
12  
12  
J91  
3
3
To  
EXTB  
DS4  
G
AC1 Neu.  
AC2 Hot  
3
J1M1  
FU7  
8A  
115 Vac DACA #2  
7
2
JDACA2  
21  
22  
JDACA2  
7
To  
EPSM1  
DS5  
G
SW4  
SW5  
SW6  
FU8  
8A  
1
1
1
10  
10  
9
J1M22  
DS6  
G
FU9  
8A  
9
115  
Vac  
To  
EPSM2  
Filter  
FU10  
8A  
1
23  
24  
J1C  
12  
FU11  
8A  
12  
2
1
3
3
To  
EPSM3  
DS7  
G
FU12  
8A  
AC2 Neu.  
BJS jumper is supplied for  
R1  
R2  
isolation of ground reference  
on systems with external  
reference  
BJS  
Chassis  
Ground  
Figure 2-8. Exciter Power Distribution Module  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power to Exciter Backplane  
EBKP (Control Rack)  
To M1  
To M2 To C  
M2  
M1  
C
EDEX EDCF  
EDEX EDCF  
EDEX EDCF  
CONTROL  
J602  
CONTROL  
J602  
CONTROL  
EDEX  
EETB  
ECTB  
EDEX  
EETB  
ECTB  
EDEX  
EETB  
J602  
ECTB  
EXTB  
EXTB  
EXTB  
Exciter Power  
Distribution  
Module  
EDEX  
CROWBAR  
EGDM FAN MEDIA  
EDEX EGDM FAN MEDIA  
EDEX EGDM FAN MEDIA  
CONV  
CROWBAR  
CONV  
CONV  
CROWBAR  
EPDM  
Fan  
Fan  
Fan  
EPSM  
EGDM  
Ground  
Detector  
M1  
EPSM  
Power  
Supply  
M2  
EGDM  
EPSM  
Power  
Supply  
C
EGDM  
Ground  
Detector  
C
Blank  
plate  
Power  
Supply  
M1  
Ground  
Detector  
M2  
J1_M2  
J1_C  
J2C  
J1_M1  
GROUND  
DETECT  
To J1M1  
To J1M2  
To J1C  
125 V dc  
115 V ac  
Supplies  
Figure 2-9. Exciter Power Backplane (EPBP) with EPDM, Power Supplies & Ground  
Detector Modules  
2-16 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exciter Software  
The exciter software is configured and loaded from the toolbox, and resides in the  
controllers. The software is represented on the toolbox screen by control blocks  
linked together to show the signal flow. Figure 2-10 is a simplified overview of the  
exciter control system displaying the main control functions. Both the generator field  
and stator currents and voltages are measured and input to the control system. In  
normal operation the ac regulator is selected. Figure 2-11 is the simplified software  
block diagram displaying the main control blocks.  
The generator voltages and currents from the PTs and CTs are wired to the EPCT  
board, which acts as a signal conditioner to isolate and scale the signals. The  
conditioned signals are then fed to the controller. Software conversion algorithms  
use these signals to calculate system variables for use by the regulator, limiter, and  
protection functions. The outputs from these software calculations include the  
following:  
Generator voltage magnitude and generator frequency derived from the PTs  
The magnitude of generator current derived from the CTs  
Generator power, P  
Generator reactive volt amperes (VARs), Q  
Change in rotor speed calculated from the integral of accelerating power that is  
normally used as the input to the optional Power System Stabilizer (PSS)  
Generator active and reactive current  
Magnitude of generator flux (VHz)  
Line voltage derived from the PTs  
Line frequency derived from line PTs  
Phase angle correlation between the generator and line, derived from generator  
and line PTs  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Voltage/Current  
Sensing  
DC  
Regulator  
DC Voltage  
adjust  
Exciter  
Bridge  
Generator  
AC  
Regulator  
AC  
Voltage  
adjust  
Exciter System  
Stabilizer Circuits  
Over-excitation  
Limiter  
Under-excitation  
Limiter  
V/Hz Limiter &  
Protection  
VAR/Power Factor  
Control  
Voltage Sensing &  
Load Compensation  
Power System  
Stabilizer  
Figure 2-10. Control Scheme  
2-18 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reactive  
Current  
External  
Raise/  
Lower  
AUTO  
REF  
EXASP  
Setpoint  
Exciter AVR  
Setpoint.  
Watts  
Slip  
PSS  
V/Hz Limit;  
Reactive  
Current  
Compen-  
sation.  
AVR  
Setpoint  
and  
Power  
System  
Stabilizer  
Tracking  
Frequency  
VMAG  
Watts  
VARs  
AVR  
UEL  
Automatic  
Voltage  
Regulator  
Under  
Excitation  
Limit  
FVR  
Generator  
Terminal  
Voltage  
VMAG  
Track  
Value  
Setpoint  
(VMAG)  
FVR  
Field Voltage Regulator Setpoint  
External  
Raise/  
Lower  
Field  
Voltage  
Regulator  
MANUAL  
REF  
Firing  
Commd  
to  
Bridge  
Min.  
FCR Setpoint  
(User Input)  
Field Volts from Bridge Output  
FCR  
Field  
Current  
Regulator  
Field Current from Bridge DC Shunt  
Figure 2-11. Software Block Diagram  
The output of the control software is the firing command, which is sent to the bridge  
to generate the field current. The individual function blocks are discussed in the  
following sections.  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auto Reference – AUTO REF  
The AUTOREF block generates an auto (or Auto Control (AC)) setpoint for the  
Automatic Voltage Regulator (AVR) based on user-supplied parameters and  
conditions. Raise/lower inputs to AUTO REF come in from the other devices on the  
Data Highway such as the turbine control or HMI. A variable rate integrator  
generates the output setpoint within preset limits. The setpoint is combined with  
other auxiliary stabilizing and protective signals in the EXASP block to form the  
reference to the AVR block.  
AVR Setpoint – EXASP  
The EXASP block combines a number of functions to produce the setpoint  
(reference input) to the AVR, and the AVR tracking value. The EXASP inputs are as  
follows:  
Stabilizing signal from the PSS block  
Output from the AUTOREF block  
External test signal  
Protective signal generated by the UEL block  
Reactive current input (feedback)  
Voltage magnitude input (feedback)  
Frequency input (feedback)  
The outputs to the AVR block are the AVR setpoint and tracking value.  
Automatic Voltage Regulator – AVR  
The AVR block maintains the generator terminal voltage. The setpoint (reference)  
comes from the EXASP block, and the feedback is the generator voltage. The error  
value is input to a proportional plus integral (PI) regulator with integrator windup  
protection, which produces an output signal. Figure 2-12 shows the block diagram.  
When the AVR is enabled, the AVR output is passed through directly from the track  
input to the output of the Field Voltage Regulator (FVR).  
Generator terminal voltage is  
controlled by the AVR.  
2-20 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preset Condition  
Preset State True  
Q
S
R
Q
Preset Not True  
a
0.05  
a>b?  
b
Software  
Software  
Q
Jumper 0 Jumper 1  
Proportional Gain  
Output Value  
Enable  
1
Gain  
Scaling  
Positive  
Limit  
Integration  
Output  
Tracking  
Control  
Preset  
State  
Integral Gain  
AVR  
Setpoint  
Error  
+
+
1
s
Σ
Σ
+
Output  
-
Negative  
Limit  
Generator  
Voltage  
Integrator  
Tracking Input  
+
Σ
Tracking  
Gain r/s  
-
AVR  
Status  
Preset  
Value  
Status of  
Regulators  
Anti-  
windup  
+
Σ
-
Figure 2-12. Automatic Voltage Regulator Block  
Manual Reference – MANUAL REF  
The MANUAL REF block generates a manual setpoint for the FVR or FCR based on  
user-supplied parameters and conditions. Raise/Lower inputs to MANUAL REF  
come in from other control devices on the Data Highway such as the turbine control  
or HMI.  
Field Voltage and Current Regulators - FVR & FCR  
The Field Voltage Regulator (FVR) is the typical manual regulator supplied on most  
applications and uses the generator field voltage as the feedback input. While FVR  
does permit the current to vary as a function of the field resistance, the FVR makes  
the manual regulator completely independent from the over excitation limiter. FVR  
uses the voltage from the generator field as feedback, with a setpoint from the  
MANUAL REF block. A PI regulator with integral windup protection generates the  
output. During operation in AVR mode, the output of the AVR is passed directly to  
the FVR output with no signal conditioning. On units that operate with an inner field  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
voltage regulator loop such as compound exciters and some high ceiling exciters, the  
FVR uses a setpoint from either the AVR or the MANUAL REF block, and is  
always operational whether in manual or automatic operation.  
The Field Current Regulator (FCR) is a special application of the manual regulator  
and uses the generator field current as the feedback input. The current setpoint is  
generally switched between a high level and lower level to provide transient forcing  
capability as well as steady state operation within the capability of the generator.  
Generally the setpoint is larger than expected field currents and the integral preset is  
operational. The FCR output is held at positive ceiling until enable becomes true  
which allows the output to follow the P+I regulator. The bridge firing command is  
the smaller of the FVR and FCR outputs. While it does regulate constant field  
current over varying field temperature, FCR is not the standard manual regulator.  
Under Excitation Limiter – UEL  
The UEL block is an auxiliary control to limit the automatic voltage regulator  
demand for underexcited reactive current (or reactive power). UEL prevents  
reduction of the generator excitation to a level where the small-signal (steady state)  
stability limit, or the stator core end-region heating limit is exceeded. Performance is  
specified by identifying the region of limiter action on the generator capability curve.  
There is both a setpoint section and regulator section of the UEL. The two key inputs  
are generator terminal voltage and real power.  
Power System Stabilizer – PSS  
The PSS block provides an additional input to the automatic regulator to improve  
power system dynamic performance. A number of different quantities may be used  
as inputs to the PSS, such as shaft speed, frequency, synchronous machine electrical  
power, accelerating power, or some combination of the above. The PSS used with  
the exciter is multi-input using a combination of synchronous machine electrical  
power and internal frequency (which approximates rotor speed) to arrive at a signal  
proportional to rotor speed. This comes from the integral of accelerating power, but  
with shaft torsional signals greatly attenuated. The input signal is derived entirely  
from generator terminal quantities without the need for shaft speed transducers. No  
additional external hardware is required.  
2-22 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operator Interface  
Operator and engineering work stations such as the HMI (Human Machine Interface)  
The HMI contains exciter and  
turbine graphic displays.  
and the toolbox communicate with the exciter. This allows operator monitoring and  
control of the exciter, and engineering access to system diagnostics and control  
block configuration  
Turbine Control HMI  
On turbine generator sets that include Mark VI turbine controls, the exciter shares  
the HMI. The HMI is Windows NT® based with CIMPLICITY operator display  
software and communication drivers for the data highways. From the HMI, the  
operator can initiate commands and view real-time data and alarms on the  
CIMPLICITY graphic displays. An HMI can be configured as a server or viewer,  
and can contain tools and utility programs.  
An HMI can be mounted in a  
control console or on a  
tabletop.  
The Unit Data Highway (UDH) connects the exciter with the HMI or HMI/Data  
Server. The network is 10BaseT Ethernet, and uses separately powered network  
switches. For longer runs, fiber-optic cables can be used.  
Redundant cable operation is  
optional and, if supplied,  
operation continues even if  
one cable is faulted.  
Control System Toolbox (toolbox)  
The toolbox is used to configure and maintain the exciter. Control blocks and  
diagrams can be modified by configuration and loaded into the control. With the  
exciter online, real-time data is available on the toolbox screen, including control  
system diagnostics for troubleshooting. The toolbox software runs on an HMI server  
or a separate PC on the UDH. Direct connection to the controller DSPX board is also  
possible through the Tool port on the control rack backplane.  
EX2100 User’s Guide GEH-6632  
Chapter 2 Functional Description 2-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
2-24 Chapter 2 Functional Description  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Printed Wiring Boards  
Overview  
Introduction  
This chapter describes the EX2100 printed wiring boards and their operation. These  
boards fall into four functional groups; control rack boards including controller  
boards and I/O processors, I/O terminal boards, bridge control and protection  
modules, and power supply boards. This chapter is organized as follows:  
Section  
Page  
Control Boards......................................................................................................... 3-2  
EBKP Backplane .............................................................................................. 3-2  
DSPX Board ..................................................................................................... 3-2  
ACLA Board..................................................................................................... 3-4  
EISB Board....................................................................................................... 3-4  
EMIO Board ..................................................................................................... 3-4  
ESEL Board...................................................................................................... 3-4  
I/O Terminal Boards ................................................................................................ 3-5  
EPCT Board...................................................................................................... 3-5  
ECTB Board ..................................................................................................... 3-5  
EXTB Board..................................................................................................... 3-5  
EDCF Board ..................................................................................................... 3-6  
EACF Board ..................................................................................................... 3-6  
Bridge and Protection Boards and Modules............................................................. 3-7  
EGPA Board..................................................................................................... 3-7  
EXCS Board ..................................................................................................... 3-7  
EDEX Board..................................................................................................... 3-7  
EGDM Module................................................................................................. 3-7  
EXAM Module................................................................................................. 3-8  
Power Supply Boards............................................................................................... 3-9  
EPDM Module.................................................................................................. 3-9  
EPBP Backplane............................................................................................... 3-9  
EPSM Module .................................................................................................. 3-9  
DACA – Ac to Dc Converter.......................................................................... 3-10  
Related Board Publications.................................................................................... 3-11  
EX2100 User’s Guide GEH-6632  
Chapter 3 Printed Wiring Boards Overview 3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Boards  
The control boards are located in the control module. This module consists of the  
exciter backplane (EBKP) and the metal chassis that holds the boards (refer to Figure  
3-1). The control boards are as follows:  
IS200DSPX Digital Signal Processor control board (DSPX)  
IS215ACLA Application Control Layer Module (ACLA)  
IS200EISB Exciter ISBus Board (EISB)  
IS200EMIO Exciter Main I/O board (EMIO)  
IS200ESEL Exciter Selector board (ESEL)  
EBKP Backplane  
The EBKP provides the backplane for the control boards and the connectors for the  
I/O terminal board cables. EBKP has three sections for controllers M1, M2, and C.  
Each section has its own independent power supply. Controllers M1 and M2 have  
the ACLA, DSPX, EISB, EMIO, and ESEL boards. Section C only has the DSPX,  
EISB, and EMIO. Two overhead fans cool the controllers.  
The upper part of the backplane contains DIN connectors for the plug-in control  
boards. The lower part of the backplane contains D-SUB connectors for I/O interface  
cables, and circular DIN connectors for keypad interface cables, power supply plugs,  
and test rings. Labels on the connectors in Figure 3-1 refer to the boards and devices  
to which the cables are connected. For more information refer to Chapter 4 and GEI-  
100460.  
DSPX Board  
The DSPX board is the main controller and shares control responsibility with the  
ACLA. It is a single-slot, 3U high module located in the control rack next to the  
ACLA. It provides functions including the bridge firing circuit control, I/O  
processing, and inner loop regulation as follows:  
The DSPX performs most of  
the I/O interface and inner  
loop bridge control and  
protection functions  
Field Voltage Regulator (FVR)  
Field Current Regulator (FCR)  
SCR gating signals to the ESEL board  
Start-stop function  
Field flashing control  
Alarms and trip logic  
Generator instrumentation processing  
Generator simulator  
For more information refer to Chapter 4 and GEI-100267.  
3-2 Chapter 3 Printed Wiring Boards Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fan  
Fan  
RST  
RST  
OK  
OK  
ACTIVE  
ENET  
FLASH  
ACTIVE  
ENET  
FLASH  
S
T
A
T
U
S
S
T
A
T
U
S
ACLA  
DSPX  
DSPX ACLA  
DSPX  
EISB  
EMIO ESEL ESEL EMIO  
EISB  
EISB  
EMIO  
J304 J305 J306 J307 J308 J309  
J314 J315  
E
P
C
T
E
P
C
T
E
P
C
T
E
G
P
A
1
E
G
P
A
2
Keypad  
M1  
Keypad  
M2  
Keypad  
C
Tool M1  
Tool M2  
Tool C  
J404 J405 J406 J407 J408 J409  
J414 J415  
E
G
P
A
3
E
G
P
A
4
E
C
T
E
C
T
E
C
T
Test Rings M1  
Test Rings M2 Test Rings C  
B
B
B
M1-Fan Pwr  
J502  
M2-Fan Pwr C-Fan Pwr  
J504 J505 J506 J507 J508 J509 J510  
J512  
J514 J515  
2
1
2
1
2
1
E
A
C
F
E
A
C
F
E
A
C
F
E
X
T
B
E
X
T
B
E
X
T
B
E
G
P
A
5
E
G
P
A
6
4
3
4
3
4
3
J602  
J610  
J612  
M1  
M2  
C
Power  
Power  
Power  
IS200EBKPG1AAA  
Figure 3-1. Control Module  
EX2100 User’s Guide GEH-6632  
Chapter 3 Printed Wiring Boards Overview 3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACLA Board  
The ACLA board is a double-slot, 3U high module located next to the DSPX. ACLA  
provides Ethernet communications with the turbine control, LCI, and HMI, and runs  
outer loop control functions including the following:  
ACLA handles network  
communications and outer  
loop functions.  
Automatic Voltage Regulator (AVR)  
Power System Stabilizer (PSS)  
Under Excitation Limit control (UEL)  
VAR/power factor regulator (VAR/PF)  
For more information refer to Chapter 4 and GEI-100434.  
EISB Board  
The Exciter ISBus Board (EISB) is a special communication interface board for the  
M1, M2, and C control modules. ISBus is a proprietary, high-speed communication  
bus used in many GE systems. The EISB is used to provide communication among  
the 3 DSPSs in M1, M2, and C. EISB receives and transmits fiber-optic feedback  
signals through the backplane connector. It transmits them over the control  
backplane to the DSPX controller and also communicates between the DSPX and the  
tool and keypad ports using RS-232C. EISB is a single-slot, 3U high module that is  
located in the control rack under the DSPX. From six fiber-optic connectors on the  
front panel it accepts current and voltage signals from the generator field (and from  
the exciter if required) using EDCF boards, and receives and transmits signals to the  
Ground Detection Module (EGDM). For more information refer to Chapter 4 and  
GEI-100454.  
EISB manages all the fiber-  
optic communication in the  
cabinets.  
EMIO Board  
The EMIO is a single slot, double height VME style board, that manages the I/O  
from the EPCT, ECTB, EACF, and EXTB terminal boards. The I/O include PT and  
CT signals, contact inputs, output relay drivers, and pilot trip relay drivers. It also  
sends logic level gate pulse signals over the backplane to the ESEL board, which  
sends them to EGPA in the power conversion cabinet. For more information refer to  
Chapter 4 and GEI-100453.  
ESEL Board  
The Exciter Selector board receives six logic level gate pulse signals from its  
corresponding EMIO. These pulse signals drive up to six sets of cables which are  
distributed to the exciter gate pulse amplifier (EGPA) boards. The EGPA boards are  
mounted in the power conversion cabinet. If there are redundant controls, two ESEL  
are used, one driven by M1 and the other by M2. The active ESEL, selected by  
controller C, sends the necessary control signals to the EGPA boards.  
Three groups of ESEL boards are available supporting increasing redundancy levels;  
ESELH1 contains a single bridge driver, ESELH2 contains three bridge drivers, and  
ESELH3 contains six bridge drivers. For more information refer to Chapter 4 and  
GEI-100456.  
3-4 Chapter 3 Printed Wiring Boards Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O Terminal Boards  
The exciter terminal boards are as follows:  
IS200EPCT Exciter PT/CT board (EPCT)  
IS200ECTB Exciter Contact Terminal Board (ECTB)  
IS200EXTB Exciter Terminal Board (EXTB)  
IS200EDCF Exciter Dc Feedback board (EDCF)  
IS200EACF Exciter Ac Feedback board (EACF)  
EPCT Board  
The EPCT contains isolation transformers for critical generator voltage and current  
measurements. Two three-phase generator PT voltage inputs are input to EPCT. Two  
generator CT current inputs, with current levels of 1 A or 5 A, are input. In addition,  
one analog input, which can be either 0-10 V or 4-20 mA, is brought into EPCT. All  
the signals are interfaced to the EMIO board. For more information refer to Chapter  
4 and GEI-100459.  
EPCT receives and conditions  
generator PT and CT  
feedbacks.  
ECTB Board  
The ECTB board supports excitation contact outputs and contact inputs. There are  
two versions; the ECTBG1 board which is only used in the redundant mode, and the  
ECTBG2 board which is only used in the simplex mode. Each board contains two  
trip contact outputs driving a customer lockout, and four general purpose Form-C  
relay contact outputs, controlled by the EMIO board. Six auxiliary contact inputs are  
powered (wetted) with 70 V dc by ECTB. Also, the 52G and 86 G contact inputs are  
powered and monitored by ECTB. In the redundant case, power comes from the M1  
and M2 power supplies. For more information refer to Chapter 4 and GEI-100457.  
EXTB Board  
The EXTB board supports pilot relay contact outputs, contact inputs, and signal  
conditioning circuits. EXTB cables to the EMIO board through the EBKP  
backplane.  
EXTB handles field flashing  
and protection functions.  
Pilot relays for the breaker/contactor close 41, and flashing contactors 53A, and 53B  
are located on the board, plus pilot relays for the trip relay 41T and the de-excitation  
relay KDEP. Crowbar status signals and de-excitation status signals from the EDEX  
board are conditioned on EXTB and sent to EMIO. Three contact inputs from 41,  
53A, and 53B are powered (wetted) by 70 V dc on EXTB. Power for the contacts is  
from the M1 and M2 power supplies (redundantly), and the resulting status signals  
are sent to EMIO in the control rack. Different groups of EXTB are available for  
controlling either a field breaker or a contactor in the field circuit. These groups are  
defined in Table 3-1. For more information refer to GEI-100458.  
Table 3-1. EXTB Board Groups  
Trip Relay  
41T used  
Close Relay  
41 used  
Type of Redundancy  
Board  
Control Mode  
Contactor Mode  
Breaker Mode  
Contactor Mode  
Breaker Mode  
Redundant control  
Redundant control  
Simplex control  
Simplex control  
EXTB G1  
EXTB G3  
EXTB G2  
EXTB G4  
No  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
EX2100 User’s Guide GEH-6632  
Chapter 3 Printed Wiring Boards Overview 3-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EDCF Board  
The EDCF board measures field current and field voltage at the SCR bridge, and  
interfaces to the EISB board in the control panel over a high-speed fiber-optic link.  
The fiber-optics provides voltage isolation between the two boards, and high noise  
immunity. Field current is measured using a shunt in the dc field circuit. The field  
voltage feedback circuit provides seven selector settings to scale down the bridge  
voltage, depending on the type of bridge application. For more information refer to  
Chapter 4 and GEI-100464.  
EDCF handles bridge dc  
voltage and current feedback.  
EACF Board  
The EACF board measures the exciter PPT ac supply voltage and current. The  
EACF terminal board contains transformers for a 3-phase voltage measurement, and  
terminals for two Flux/Air core coils. The outputs of the voltage and current circuits  
are fanned out to three DB9 connectors for cables to controllers M1, M2, and C.  
These cables can be up to 90 m in length. There are two versions of this board,  
EACFG1 is for inputs up to 480 V rms, and EACFG2 is for inputs up to 1000 V rms.  
For more information refer to Chapter 4 and GEI-100465.  
EACF handles bridge ac  
voltage and current feedback.  
3-6 Chapter 3 Printed Wiring Boards Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Bridge and Protection Boards and Modules  
The exciter bridge and protection boards are as follows:  
IS200EGPA Exciter Gate Pulse Amplifier board (EGPA)  
IS200EXCS Conduction Sensor board (EXCS)  
IS200EDEX Exciter De-Excitation board (EDEX)  
IS200EGDM Exciter Field Ground Detector Module (EGDM)  
IS200EXAM Exciter Attenuator Module (EXAM)  
Crowbar module  
EGPA Board  
The EGPA board interfaces the control to the power bridge. EGPA takes the six gate  
commands from the ESEL and controls the gate firing of up to six SCRs on the  
bridge. It is also the interface for current conduction feedback, and the bridge airflow  
and temperature monitoring.  
Bridge control passes through  
EGPA. One EGPA is required  
per PCM.  
A nominal 125 V dc power source from EPDM supplies an on-board dc/dc converter  
that provides power for SCR gating over the full range of input supply voltage. LEDs  
provide visual indication of the status of the output firing, currents into the bridge,  
gate power supply, line filter, cooling fan rotation, and bridge temperature and alarm  
or fault conditions. For more information refer to Chapter 4 and GEI-100461.  
EXCS Board  
The EXCS board has four conduction sensors. It is used to detect the presence of  
current in the bus. The output is a logic signal.  
EDEX Board  
The EDEX board is the main board in the de-excitation module. EDEX provides de-  
excitation SCR firing, conduction sense feedback, and voltage retention to ensure  
operation in the event of a power failure. EMIO initiates de-excitation on the EXTB  
board. The EXTB board opens the 41 dc contactor (41A/41B) or breaker, and then  
transfers de-excitation signals from the auxiliary contacts to SCR firing circuits on  
the EDEX. There are two types of EDEX. Group 1 board is designed for SCR de-  
excitation, Group 2 is designed for diode de-excitation. For more information refer  
to Chapter 4 and GEI-100466.  
EDEX is usually controlled by  
EXTB, but can initiate de-  
excitation if control fails.  
EGDM Module  
The EGDM is a double slot, double height (6U) form factor board that mounts in the  
Exciter Power Backplane rack (EPBP). A simplex system has one EGDM, while a  
redundant system has three. EGDM detects field leakage resistance from any point  
in the field circuit of the generator to ground, either on the ac or dc side. The field  
ground detector applies a low frequency square wave to the sense resistor connected  
to the field circuit. EXAM, the attenuator module located in the Auxiliary Panel,  
senses the voltage across the ground resistor and sends the signal to the EGDM  
through a nine-conductor cable.  
EGDM and EXAM work  
together to detect field ground  
leakage current.  
EX2100 User’s Guide GEH-6632  
Chapter 3 Printed Wiring Boards Overview 3-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
In a redundant system, the set of three EGDM boards are configured as a Controller  
(C), Master 1 (M1) and Master 2 (M2). The configuration for each EGDM is  
controlled by a set of program pins on the P2 connector. The C controller receives  
information from the active DSPX on which EGDM master should provide the drive  
signal to the sense resistor in the Attenuator Module. The active master receives an  
Oscillator Signal over the fiber optic link that it converts to a ±50 V signal. This is  
applied to one end of the sense resistor in the Attenuator Module.  
The signal conditioner receives an attenuated (10:1) differential signal from the  
Sense Resistor. This is a simple unity gain differential amplifier with a high  
common-mode rejection ratio followed by an A-to-D converter (Voltage Controlled  
Oscillator VCO). This feeds a fiber-optic transmitter that is cabled to EISB. The  
signal conditioner circuitry is powered by an isolated power supply to maintain  
personnel and equipment safety due to the high common-mode voltage at the Sense  
Resistor. For more information refer to Chapter 4 and GEI-100467.  
EXAM Module  
The EXAM mounts in the auxiliary cabinet and contains a sense resistor connected  
to a resistor network across the field. EXAM applies the low frequency ±50 V  
square-wave signal, supplied from the EGDM, to one end of the sense resistor. The  
resulting current generates a voltage across the resistor, that is sent back to the  
EGDM.  
In a redundant system, the test signal can come from either, M1 or M2. EXAM has a  
relay that switches between the two under the control of controller C. A single cable  
carries the control and sense signals between the EGDM and EXAM modules. For  
more information refer to Chapter 4 and GEI-100467.  
3-8 Chapter 3 Printed Wiring Boards Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Supply Boards  
The exciter power supply boards are as follows:  
IS200EPDM Exciter Power Distribution Module (EPDM)  
IS200EPBP Exciter Power Backplane (EPBP)  
IS200EPSM Exciter Power Supply Module (EPSM)  
DACA Module  
EPDM Module  
The EPDM provides the power for the control, I/O, and protection boards. It is  
mounted on the side of the EPBP and accepts a 125 V dc supply from the station  
battery, and one or two 115 V ac supplies. All supply inputs are filtered. Each ac  
supply is rectified to 125 V dc in an ac to dc converter (DACA). The resulting two or  
three dc voltages are diode coupled together to create the dc source supply,  
designated as P125V and N125V. With the center grounded, these voltages are  
nominally +62.5 V and –62.5 V to ground.  
Individual supply outputs to the exciter boards are fused. They have an on/off toggle  
switch, and a green LED indicator to display supply power availability. These  
outputs supply up to three EGPA boards, the EXTB board, and three EPSM modules  
serving the three controllers. Outputs are wired to the EPBP for distribution. For  
more information refer to Chapter 4.  
Any of the exciter power  
supply modules can be  
switched off from the EPDM.  
EPBP Backplane  
The EPBP holds three electrically isolated power supplies (EPSM) that supply power  
to the M1, M2, and C controllers. It also holds three EGDM. EPBP accepts 125 V dc  
from the adjacent EPDM, and distributes logic level power from the three EPSM to  
the three controllers. Each power supply has an independent ON-OFF switch on the  
EPDM. The EPSM modules interface to the backplane through DIN connectors. 70  
V dc and 24 V dc power is distributed from the locking connectors at the top of the  
backplane to the terminal boards. Refer to Figure 3-2. For more information refer to  
Chapter 4 and GEI-100463.  
EPSM Module  
The EPSM converts 125 V dc from the EPDM into the voltages required for the  
control system. There are three independent power supplies that supply power to  
each of the controllers M1, M2, and C. These supplies are located in the power  
supply module mounted below the control rack in the control cabinet.  
The EPSM supplies +5 V dc, ±15 V dc, and +24 V dc to the controller. Power is also  
supplied to modules external to the control rack as follows:  
±24 V dc to power the EDEX de-excitation module, crowbar module, EGDM,  
and EDCF  
Isolated +70 V dc for contact wetting to the EXTB and ECTB boards  
For more information refer to Chapter 4 and GEI-100462.  
EX2100 User’s Guide GEH-6632  
Chapter 3 Printed Wiring Boards Overview 3-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M2  
M1  
C
EDEX EDCF  
EDEXEDCF  
EDEXEDCF  
CONTROL  
CONTROL  
CONTROL  
J17  
M2  
J16  
M2  
J17  
C
J16  
C
J17  
M1  
J16  
M1  
J15M1  
J14M1  
J13M1  
J15M2  
J14M2  
J13M2  
J15C  
J14C  
J13C  
EDEX  
EDEX  
EDEX  
J602  
J602  
J602  
EETB  
ECTB  
EETB  
ECTB  
EETB  
ECTB  
EXTB  
J18  
M1  
J18  
M2  
J18  
C
J19  
M1  
J19  
M2  
J19  
C
J20  
M1  
J20  
M2  
J20  
C
J21M2  
J21M1  
J21C  
J12M1  
J12M2  
J12C  
EXTB  
EXTB  
MEDIA  
CONV  
FAN MEDIA  
CONV  
EDEX EGDM  
CROW  
BAR  
EDEX  
CROW  
BAR  
FAN  
EGDM  
EDEX EGDM  
CROW  
BAR  
MEDIA  
FAN  
CONV  
Blank plate  
EPSM  
EGDM  
EPSM  
EGDM  
EPSM  
EGDM  
J2C  
GROUND  
DETECT  
J1_M1  
J1_M2 BARCODE  
J1_C  
IS200EPBPG1  
Figure 3-2. Exciter Power Backplane  
DACA – Ac to Dc Converter  
The DACA is an ac to dc converter that is powered by a 115 V ac source and  
produces 125 V dc. The DACA and battery source provide a redundant 125 V dc  
supply for the EPDM. Two DACAs can be connected to the EPDM if required for  
greater power supply reliability.  
3-10 Chapter 3 Printed Wiring Boards Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Related Board Publications  
For a more detailed description of each board's circuitry and application data, refer to  
the following documents:  
GEI-100460 IS200EBKP Exciter Backplane  
GEI-100267 IS200DSPX Digital Signal Processor Board  
GEI-100434 IS215ACLAH1 Application Control Layer Board  
GEI-100454 IS200EISB Exciter ISBus board  
GEI-100453 IS200EMIO Exciter Main I/O board  
GEI-100456 IS200ESEL Exciter Selector board  
GEI-100459 IS200EPCT Exciter PT/CT board  
GEI-100457 IS200ECTB Exciter Contact Terminal Board  
GEI-100458 IS200EXTB Exciter Terminal Board  
GEI-100464 IS200EDCF Exciter DC Feedback board  
GEI-100465 IS200EACF Exciter AC Feedback board  
GEI-100461 IS200EGPA Exciter Gate Pulse Amplifier board  
GEI-100466 IS200EDEX Exciter De-Excitation board  
GEI-100467 IS200EGDM Exciter Ground Detector Module  
GEI-100463 IS200EPBP Exciter Power Backplane  
GEI-100462 IS200EPSM Exciter Power Supply Module  
EX2100 User’s Guide GEH-6632  
Chapter 3 Printed Wiring Boards Overview 3-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
3-12 Chapter 3 Printed Wiring Boards Overview  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4 Terminal Board I/O and  
Equipment Connections  
Introduction  
This chapter describes the customer's equipment connections, and inputs and outputs  
(I/O) available through terminal board wiring. System cabling to provide desired  
functionality is also defined. The information is organized as follows:  
Section  
Page  
Power Connections and Analog I/O......................................................................... 4-2  
Power Potential Transformer Inputs................................................................. 4-3  
Potential and Current Transformer Inputs ........................................................ 4-3  
Analog Input..................................................................................................... 4-3  
Customer Contact I/O .............................................................................................. 4-4  
Power Supply Inputs................................................................................................ 4-6  
Line Filter Connections............................................................................................ 4-7  
Exciter Internal I/O .................................................................................................. 4-8  
Exciter AC Feedback........................................................................................ 4-8  
Exciter DC Feedback........................................................................................ 4-8  
De-Excitation......................................................................................................... 4-11  
Crowbar ................................................................................................................. 4-14  
Field Ground Detector ........................................................................................... 4-14  
Field Flashing ........................................................................................................ 4-16  
Dc Field Flashing Settings.............................................................................. 4-16  
Flashing Control Sequence............................................................................. 4-16  
Shaft Voltage Suppressor....................................................................................... 4-18  
Data Highway Connections ................................................................................... 4-19  
Control System Toolbox Connection..................................................................... 4-20  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Connections and Analog I/O  
Figure 4-1 displays a typical connection diagram of the common power and analog  
I/O for an excitation system.  
Customer Supplied  
+
Generator Field +  
To Bridge 1  
-
Control Cabinet  
Generator Field -  
PT1  
PTSW1  
PTSW2  
(O  
1
2
3
X1  
X2  
X3  
H1  
P
RI  
VA  
C :  
14  
40  
0
SE PNE  
C
VA  
C : O  
12  
0
2
4
6
1
3
5
TB1  
O
R
G
R
1
3
5
7
H2  
H3  
PT  
PT  
PT  
PT  
2
4
6
U
N
D
E
D
To  
8
10  
9
11  
EMIO  
(M1)  
J3  
05  
12  
14  
16  
18  
20  
22  
24  
PT2  
13  
15  
17  
19  
21  
23  
(O  
H1  
X1  
X2  
X3  
SE PNE  
C
VA  
C : O  
12  
0
P
RI  
VA  
C :  
14  
40  
0
1
3
5
2
4
6
O
R
G
R
H2  
H3  
To  
EMIO  
(M2)  
Fa  
n-  
ou  
t
cir  
cui  
ts  
U
N
D
E
J3  
08  
Power  
Flow  
D
To  
EMIO  
(C)  
TB2  
1
CTSW1  
5H  
2
1
J3  
15  
5L  
2
3
4
CT  
4
3
1H  
1L  
TB3  
1
CTSW3  
5H  
2
1
3
5L  
2
3
4
CT  
1H  
4
1L  
EPCT  
PPT  
41AC1  
Power Conversion Cabinet  
X1  
SE  
H1  
H2  
H3  
K1  
K2  
K3  
L1  
L2  
L3  
P
RI  
C
X2  
KV  
VA  
C :  
12  
47  
0
To  
Bridge 1  
VA  
C :  
A
12  
80  
X3  
65  
0
Phase Rotation  
3
Note: Circuits shown  
external to the exciter  
are for reference only.  
1
2
Figure 4-1. Exciter AC Power Supply and PT/CT Wiring  
4-2 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Potential Transformer Inputs  
In the EX2100 excitation system, a 3-phase source of ac power is converted to a  
controlled dc output. This ac input can be from one of several sources. Most  
common is a generator terminal connected Y-Delta power potential transformer. The  
primary and secondary voltages as well as kVA ratings are sized for the particular  
application. An auxiliary bus fed PPT is also commonly used. In industrial  
applications where forcing is needed for large motor starting a compound source  
(current and voltage) input can be used. This ac input is connected to the bus in the  
bridge cabinet and can be isolated by the 41AC1 device for maintenance. It is  
monitored by the controls through the EACF board.  
Potential and Current Transformer Inputs  
A redundant PT input for PT  
failure detection is possible, and  
single-phase sensing can be  
supported.  
Customer supplied 3-phase PT and CT are wired to switches in the control cabinet as  
shown in Figure 4-1. The switches are wired to the EPCT. High frequency noise  
suppression near the point of signal entry is provided on all input signals to EPCT.  
On the board, the two 3-phase generator voltage inputs, nominal 115 V ac, are  
brought into PT transformers. Two generator CTs (phases A and C), with either 1 A  
or 5 A secondaries, are brought into CT transformers. The resulting low voltage  
transformer output signals are cabled to the EMIO board in the control rack.  
Generator Voltage Measurement  
The cable lengths from the generator PTs can be up to 1000 ft of #12 AWG wire.  
The PT secondary outputs are nominally 115 V rms at 50/60 Hz and are fused. On  
EPCT, the two transformers make a three-wire open delta voltage measurement,  
yielding 1.533 V rms for a 115 V rms input.  
In the case of a simplex system the voltage signals are sent through the J305  
connector to the EMIO board in the M1 controller. In the case of a redundant system,  
the signals are fanned to connectors J305, J308, and J315, and sent to controllers M1,  
M2, and C.  
Item  
PT Inputs  
CT Inputs  
Number of Inputs  
Volts or Current  
2, 3 phases each  
2, Phases A and C  
10-200 V rms, 115 V rms nominal  
0-2 A, nominal 1A, or  
0-10 A, nominal 5 A  
Frequency  
Burden  
50/60 Hz nominal  
Less than 1 VA  
50/60 Hz nominal  
Circuit loading 6.25 VA nominal  
Generator Current Measurement  
Two generator current inputs from the CTs are wired to non-pluggable terminal  
blocks, TB2 and TB3 that support ring terminals. The CTs do not have fused  
secondaries. There is a choice of a 0-1 A rms CT input, or a 0-5 A rms CT input. The  
cable length from the CT to the EPCT board can be up to 1000 ft., and the wire gage  
can be up to #10 AWG. The resulting signals are sent to the EMIO board through the  
same connectors as the voltage signals.  
Analog Input  
The EPCT board provides an analog input for customer use. This input is jumper  
selectable for either ± 10 V dc or 4-20 mA. The EMIO samples the input at 2000  
samples per second, and the accuracy is better than 1% full scale.  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Customer Contact I/O  
Customer contact inputs and relay contact outputs are wired to the ECTB board.  
In addition to six general purpose contact inputs, there are two dedicated contact  
inputs, wetted by 70 V dc from the exciter, as follows:  
86G contact input used as a lockout during normal operation  
52G contact input gives the online status of the generator  
ECTB provides four general purpose Form C contact outputs controlled by EMIO.  
These are used for 94EX and 30EX and other outputs. For each relay, the coil current  
and the status of a relay auxiliary contact is monitored. These feedbacks are cabled to  
EMIO in the controller. Refer to Figure 4-2 and Table 4-1.  
Table 4-1. General Purpose Relay Contact Characteristics:  
Item  
Description  
Customer Power  
Relay break characteristic  
125 V dc nominal (24 V dc min)  
Resistive load  
2 A  
28 V dc  
125 V dc  
28 V dc  
125 V dc  
0.5 A  
1 A  
Inductive  
0.007 s (L/R)  
0.007 s (L/R)  
0.1 A  
Suppression  
External suppression supplied by customer on induction loads  
ECTBG1 is the redundant control version of the ECTB. This fans inputs to three  
connectors J405, J408, and J418 that are cabled to the three controllers. For relay  
control, the board does two-out-of three voting, and the 70 V dc and 24 V dc inputs  
are redundant.  
4-4 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
J13M1  
J405  
ECTBG2 (Simplex)  
P70 V dc  
P24D  
From M1  
TB1  
18  
P24M1  
NO  
COM  
NC  
Customer  
P24D  
19 Power to  
Contacts  
Relay  
Driver  
Coil  
K#GP  
125 V dc  
20  
From M1  
(EMIO)  
Ex. Fault  
to Mark VI  
Four General Purpose Relay Outputs as Above  
P24M1  
1
M1  
Relay  
Driver  
Coil  
K#M1  
Customer  
Power to  
Contacts  
M1  
125 V dc  
5
Two Trip Relay Outputs as Above  
Term. 1&5  
Ex. trip to  
Customer  
86  
Auxiliary  
P70Vdc  
Contact  
Input  
Red LED  
33  
34  
Current Limit  
Circuit  
Six Circuits as Above  
P70Vdc  
52G  
Contact  
Red LED  
45  
(Closed  
online)  
46  
Current Limit  
Circuit  
P70Vdc  
86G  
Contact  
47  
48  
(Open  
for Trip)  
To Optocoupler on M1 (EMIO)  
Current Limit  
TB2  
Figure 4-2. Customer I/O wired to ECTBG2 Simplex Board  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Supply Inputs  
The customer’s ac and dc power inputs are wired to the exciter’s Power Distribution  
Module (EPDM), which is located on the left hand side of the exciter power  
backplane rack. Figure 4-3 shows the screw terminals for the 125 V dc battery  
source, and the 115 V ac suply, AC1. A second ac supply, AC2, can also be  
connected.  
EPDM Exciter Power Distribution Module  
1
SPARE  
SW7  
2
1
J1C  
J1M2  
J1M1  
J8C  
SW6  
SW5  
SW4  
SW3  
SW2  
SW1  
2
1
2
1
2
1
2
TB1  
x
1
2
J8B  
x
1
3
P125Vdc  
P125Vdc  
P125Vdc  
x
x
x
x
x
x
x
x
x
x
x
x
2
4
N125Vdc  
N125Vdc  
N125Vdc  
125 V dc  
from battery  
x
x
x
x
x
x
x
x
x
x
x
5
6
1
2
7
8
J8A  
9
10  
12  
14  
16  
18  
20  
22  
24  
x
11  
13  
15  
17  
19  
21  
23  
115 V ac  
supply #1  
AC1H  
AC1H  
AC1N  
AC1N  
AC2H  
AC2H  
1
J9  
3
10  
JDACA1  
1
115 V ac  
supply #2  
AC2N  
AC2N  
3
1
12  
10  
JDACA2  
3
12  
Figure 4-3. Power Wiring Connections to EPDM.  
4-6 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Line Filter Connections  
The 600 V filter is connected to fuse board LFU1. The 1000 V filter has two filter  
circuits and is connected to fuse boards LFU1 and LFU2. The filters are located at  
the top of the auxiliary cabinet. Connections to the line filter are shown in Figure 4-  
4.  
Auxiliary Enclosure  
EACF1  
Control  
Enclosure  
Linefilter  
EKBP  
Rack  
TB4  
Coil1_H  
Coil1_L  
Coil2_H  
Coil2_L  
1
2
J5  
04  
J5  
04  
3
4
EMIO M1  
From PPT  
L1 L2 L3  
L1  
L2  
L3  
TB1  
J5  
09  
J5  
09  
EMIO M2  
EMIO C  
DISC 1  
TB2  
J5  
14  
J5  
14  
L1  
L2  
L3  
TB3  
480V : 1.6V  
LFU1  
LFU2  
2
4
6
2
4
6
F
U3  
F
U3  
F
F
F
U1  
F
U2  
GND  
U1 U2  
To Warm  
Backup Bridge B2  
GND on  
1
3
5
1
3
5
Aux Panel  
B-L1  
B-L2  
B-L3  
Figure 4-4. AC Feedback and Line Filters  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exciter Internal I/O  
Exciter AC Feedback  
The EACF board measures the exciter ac supply voltage and current. The terminal  
board contains transformers for a 3-phase voltage measurement, and terminals for  
two flux/air core coils. The cable between EACF and the EBKP control backplane  
can be up to 90 m in length. Cable shield terminal screws attached to chassis ground  
are located within three inches of the input screws where applicable. There are two  
versions of the circuit board, EACFG1 for up to 480 V rms inputs, and EACFG2 for  
up to 1000 V rms inputs. Refer to Figure 4-4.  
Exciter DC Feedback  
The EDCF board measures field current and field voltage at the SCR bridge, and  
interfaces to the EISB board in the controller over a high-speed fiber-optic link. The  
fiber optics provides voltage isolation between the two boards, and high noise  
immunity. For a circuit block diagram, refer to Figure 4-5. The field voltage  
feedback circuit provides seven selector settings to scale down the bridge voltages  
appropriate to the application.  
EDCF DC Feedback Board  
+/-24Vdc  
from  
External  
Source  
+ 24 V dc  
- 24 V dc  
1
DC/AC  
Inverter  
AC/DC Converter  
& Power Supplies  
2
+ 15 V dc  
+24V  
-24V  
3
4
- 15 V dc  
+ 5 V dc  
J16  
SCR Bridge  
COM  
30 Vdc  
max.  
+
Shunt  
mV  
input  
-
Field Current  
Amplifier  
+
DC  
Shunt  
To  
EISB  
board  
I feedbk  
Tx1  
Tx2  
-
Fiber Optic Link  
ACOMH  
V feedbk  
Field  
scale 7  
JP7  
scale 1  
JP1  
Field Voltage  
Amplifier  
+
-
Voltage  
Isolation  
Barrier  
R 9  
Ra  
R1  
Stab-on  
ACOMH  
Figure 4-5. Field Voltage and Current Measurement  
4-8 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Field Current Feedback  
The field current is measured across a dc shunt at the SCR bridge. This generates a  
nominal 100 mV signal, which is input to a differential amplifier. The output voltage  
from the amplifier ranges from –5 V to +5 V. A VCO produces a linear proportional  
frequency of 0 to 2 MHz with an accuracy of 1% of full scale reading. These pulses  
drive the LED in the optical isolator coupled to the fiber-optic cable.  
Field Voltage Feedback  
The bridge voltage is measured across the negative terminal of the bridge and the  
positive terminal of the current shunt. After scaling the voltage with the jumpered  
resistors, the signals are input into a differential amplifier which controls the voltage-  
controlled oscillator (VCO). The VCO produces a linear proportional frequency of 0  
to 2 MHz with an accuracy of 1% of full-scale reading. The pulses drive the LED in  
the optical isolator coupled to the fiber-optic cable.  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auxiliary Cabinet  
Control Cabinet  
EISB M1  
EDCF-1  
E1  
P1  
VCO  
Duplex Fiber-  
Optic Link  
Voltage  
VFOF  
Volts  
Current  
CFOF  
PPT  
Scaling  
Generator  
Field  
P2  
1
1
BK  
PSM1  
+
2
2
VCO  
WH  
BK  
-
Current  
P24VDC  
Dc  
Shunt  
Shunt (mv)  
To Bridge 2  
41A  
Generator  
Field +  
+
-
2
1
BK WH  
Auxiliary Cabinet  
HS +  
De-Excit.  
FDI-1  
SCR1  
SCR3  
SCR2  
53B (W)  
Field  
L1  
L2  
L3  
53B (Y) Flash  
TB1-1  
Shaft  
TB1-2 Voltage  
SCR4  
J4  
SCR5  
J5  
SCR6  
J6  
41B  
J1  
J3  
J2  
Generator Field -  
Control Cabinet  
To Bridge 2  
J2/3M  
EXTB  
K41_M1 K41_M2  
1
41B  
41A  
3
3
J6  
K41_C  
K41_M2  
K41_C  
1
4
4
9
2
K41_M1  
P125  
N125  
P70V  
J505  
Control Rack  
J505  
2
3
EMIO  
M1  
J508  
J515  
J508  
70V  
Return  
EMIO M2  
Feedback  
J515  
EMIO  
C
Figure 4-6. DC Field Circuit Contactor and Control Board  
4-10 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
De-Excitation  
During shutdown of the generator, the stored energy of the generator field inductance  
must be dissipated. In the EX2100 exciter, this is the function of the EDEX  
de-excitation module and field discharge resistor or inductor (when supplied).  
Standard de-excitation is provided by a freewheeling diode. For higher performance  
applications, the de-excitation module consists of a thyristor (53 mm or 77 mm cell  
size) mounted in a large heatsink assembly with attached snubber network.  
The EDEX board contains Hall effect conduction sensors. The sensors are mounted  
in the air gap of a circular steel core attached to the board. They sense the magnetic  
field produced by the field discharge current flowing through the thyristor. Two  
independent sensor circuits are used. The EDEX fires the SCR when either of two  
control inputs is true or when the anode to cathode voltage of the SCR exceeds a  
certain value. The two firing control circuits on the board are powered from separate  
power supplies and use separate conduction sensors making them mutually  
independent.  
The actual control logic inputs used are dependent on the application. When the  
exciter shuts down, a P24 V firing control signal is sent to both de-excitation module  
firing control circuits. Both firing control circuits send gate pulses to fire the de-  
excitation SCR. At this point, the main field polarity reversal has occurred making  
the SCR anode positive with respect to the cathode. Therefore the SCR conducts and  
dissipates the stored energy of the generator field through the field discharge device.  
Feedback from either conduction sensor verifies that the discharge circuit has  
operated successfully. If both independent firing control circuits fail to fire, the SCR  
is fired by the anode firing circuit when the anode to cathode voltage has exceeded  
the selected level.  
For large exciters, it is possible to connect multiple de-excitation modules together  
with one EDEX board configured to be the Master and the other boards configured  
to be Slaves. In this case, a firing control signal sent to the Master is relayed to the  
Slave modules, firing all modules simultaneously.  
EXTB controls the main breaker or contactor in the field circuit. When this opens,  
the auxiliary contacts cause an immediate de-excitation commanded by EDEX. De-  
excitation controlled by EXTB in both the contactor and breaker mode is shown in  
Figures 4-7, and 4-8.  
Location of the 41A dc contactor in the field circuit is shown in Figure 4-6.  
Contactor 41B is optional. Both contactors are located in the Power Conversion  
Cabinet, and are driven from the 41 Close pilot on the EXTB board. Several  
auxiliary contacts are used to provide status feedback to the control, and firing  
commands to the de-excitation board, EDEX.  
An alternative to an 41A and 41B contactor is to use a breaker in the excitation ac  
supply or dc field circuit. Normally, the breaker would be a dc field breaker that  
ccould break the output while inserting a discharge resistor with the normally open  
contact. But, an ac break with the SCR based de-excitation module could also be  
applied. The breaker has two coils, 41 Close and 41 Trip, and auxiliary contacts for  
de-excitation. Figure 4-8 shows how the breaker interfaces with the EXTB control  
board and EDEX.  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Cabinet  
Converter Cabinet  
Auxiliary Cabinet  
De-Excitation  
EXTB G1 - Contactor Mode  
Generator  
Field +  
Generator  
Field -  
(Simplex version is G2)  
J505  
To  
M1  
FDI  
J508  
J515  
HS+  
HS-  
2
1
To  
M2  
Conduction  
DEPL  
EDEX  
To  
C
M1  
Status  
Sense Circuit  
M1 De-Excit.  
Status  
J8  
J8  
Status  
Feedback  
2
2
J6  
3
5
5
3
M2 De-Excit.  
Status  
M2  
Status  
4
3
70V Ret  
P70V  
Self Firing  
2
4
4
P24V  
P24V  
M2 Firing  
Command  
1
1
7
8
7
8
Bkr  
Bkr  
Ct  
Ct  
3
4
7
5
3
4
N24  
M1 Firing  
Command  
1
2
1
2
8
6
6
N24  
41 Trip Relays  
not present on  
6
G1 and G2 boards  
M1 M2  
P24  
COM  
N24  
P24  
1
2
3
1
2
3
M2  
C
C
1
9
41 Close  
P125  
A
B
A
COM  
N24  
M1  
B
Bkr.  
Ct.  
41A  
41B  
N125  
To EPBP  
J17M2  
To EPBP  
J17M1  
KDEP  
N125  
P70Vdc  
2 1  
J9  
J12M2 J12M1  
Figure 4-7. DC Contactor Control and Wiring to De-Excitation Board  
4-12 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auxiliary Cabinet  
Control Cabinet  
De-Excitation  
EXTB G3 - Breaker Mode  
Generator  
Field +  
Generator  
Field -  
Customer  
Breaker  
(Simplex version is G4)  
J505  
J508  
J515  
To M1  
To M2  
FDI  
HS+  
HS-  
1
2
2
Conduction  
Sense Circuit  
M1 De-  
EDEX  
DEPL  
To C  
CTB  
J8  
2
M1  
Status  
J8  
Status  
Feedback  
2
J6  
3
Exc Status  
5
5
M2 De-  
Exc Status  
M2  
Status  
70V Ret  
P70V  
2
4
Self Firing  
P24V  
P24V  
M2 Firing  
Command  
1
1
Ct  
Ct  
Bkr  
Bkr  
7
5
3
4
3
4
M1 Firing  
Command  
N24V  
N24V  
8
6
6
M1 M2  
M2 C  
C M1  
6
41 Trip  
P125  
M1 M2  
41  
P24  
P24  
1
2
3
1
M2 C  
C M1  
1
9
Breaker  
41 Close  
P125  
A
A
2
3
COM  
N24  
COM  
N24  
B
B
Bkr Ct  
N125  
Close  
Trip  
To EPBP To EPBP  
J17M1  
J17M2  
KDEP  
N125  
P70Vdc  
1
2 3  
J9  
J12M2 J12M1  
Figure 4-8. Ac or Dc Breaker Control and Wiring to De-Excitation Board  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Crowbar  
The optional crowbar subsystem limits high negative voltages that can be induced  
into the PCM during a pole slip (loss of synchronization) event. Like the de-  
excitation module, the crowbar will self-fire based on selective field voltage limits. It  
includes a discharge resistor, which may be shared with the de-excitation function  
when the two are supplied together. This is typically only provided on generators  
with salient poles (hydro applications).  
Field Ground Detector  
The generator field is an ungrounded system. The field ground detector (EGDM)  
The EGDM is an active  
system that applies a voltage  
to the field circuit.  
detects field leakage resistance between any point in the field circuit of the generator  
and ground. The active detection system shown in Figure 4-9 applies a low  
frequency square wave voltage with respect to ground, and monitors for current flow  
through a high impedance ground resistor. The square wave is ±50 V dc at 0.2 Hz  
frequency. If PRV resistors are present, grounds anywhere in the system can be  
detected even while the exciter is not being fired, from the PPT secondary to any  
point in the generator field.  
The ground detector feedback voltage is sent over a fiber-optic link to the DSPX  
where it is monitored and alarmed. The DSPX controls the oscillator voltage over an  
adjacent fiber-optic link. In the case of redundant control, if the M1 controller fails,  
the oscillator in the M2 channel takes over, as commanded by controller C.  
One or three EGDMs are mounted next to the power supplies in the power  
backplane.  
4-14 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Cabinet  
Auxiliary Cabinet  
Generator  
Field +  
Generator  
Field -  
From  
Flashing  
53B  
Power  
Backplane  
EPBP  
Control  
Backplane  
EBKP  
Ground Detector Attenuator  
Module EXAM  
J2  
EISB - M1  
Ground  
Detector  
Voltage  
EGDM -M1  
To DSPX  
Counters  
Optical  
Receiver  
VCO  
Oscillator  
control  
Oscillator 1  
Optical  
Transmitter  
To DSPX  
Counters  
M2  
M2  
Optical  
Receiver  
VCO  
Oscillator  
control  
Oscillator 2  
Optical  
Transmitter  
C
To DSPX  
Counters  
C
Optical  
Receiver  
VCO  
Master  
Select  
Control  
Optical  
Transmitter  
+/-65 Vdc +5V +/-15V  
Power Supply  
P24 V  
Figure 4-9. Field Ground Detector  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Field Flashing  
Field flashing relays 53A and 53B are controlled from drivers on the EMIO board,  
through pilot relays on EXTB. In redundant control, the three driver signals actuate  
pilot relays on EXTB that are contact voted to output a single voltage. These outputs  
actuate the 53A and 53B relays in the Auxiliary Cabinet. The 53A and 53B contacts  
put dc voltage from the station battery across the generator field, as shown in Figure  
4-10. The field flashing module supplies approximately 15 to 20% of AFNL to the  
generator field during the startup sequence.  
The station battery is used to  
initiate the field current. An  
auxiliary ac source can also  
be used.  
For ac field flashing, the ac voltage is rectified by a diode bridge and filtered. The  
startup sequences and logic are the same.  
Dc Field Flashing Settings  
Field flashing panels are used to supply a wide range of flashing currents. This  
happens if the flashing control fails, leaving the flashing current on continuously.  
The flashing current magnitude required for a generator is set by configuring a  
maximum and minimum allowable value in the control module.  
The current values are preset in the factory based on information supplied. These  
values define the envelope in which the hysteretic flashing control holds the field  
current during the flashing sequence.  
Flashing Control Sequence  
A start request is issued by the operator. The optional field contactor(s) closes,  
followed by contactor 53B, then 53A. When the field current reaches the maximum  
allowable field flash value (typically 15 - 20% of AFNL), contactor 53A opens and  
the field current decays through the freewheeling diodes. If the control has not taken  
over before the current decays to the minimum field flash current setting, typically  
10% AFNL, the sequence is repeated. If the current magnitude exceeds  
approximately 25% AFNL, or the control has not taken over after a fixed time delay,  
the startup is stopped and a diagnostic alarm is issued.  
Flashing current flow is  
monitored by the control  
through the field shunt.  
4-16 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
From  
Shunt1 +  
Generator  
Field -  
Station Battery  
125 Vdc  
Auxiliary Panel  
Flashing  
1
2
PTB-1  
-
+
Shaft Voltage  
Suppresser  
53B  
53A  
53B  
x
w
v
x
Y
Y
EXAM  
J1  
1
53B  
TB1  
1
2
3
J1  
Aux  
3
2
1
7
2
3
8
FBK1  
5
6
1
2
3
4
EXTB  
4
M1 53B  
M2 53B  
Current  
Limit  
Circuit  
C 53B  
P70Vdc  
J5M1  
J5M2  
J5C  
J7  
J7  
M1-EMIO  
(J5)  
4
4
10  
6
M1  
M2  
1
2
M2 C  
10  
6
M2-EMIO  
(J5)  
C M1  
53B  
B
A
K53B relay  
contacts  
SUP  
C-EMIO  
(J5)  
53A  
A
SUP  
M1  
M2  
9
2
9
2
B
M2  
C
1
C M1  
5
5
53A2  
K53A relay  
contacts  
Aux  
3
4
12  
3
12  
3
P70Vdc  
M1 53A  
Current  
Limit  
Circuit  
M2 53A  
C 53A  
P70VDC  
Figure 4-10. Field Flashing Control from EMIO and EXTB  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Shaft Voltage Suppressor  
Excitation systems, which produce a dc voltage from an ac supply through a solid  
state rectification process, cause ripple and spike voltages at the exciter output. Due  
to their rapid rise and decay times these voltages are capacitively coupled from the  
field winding to the rotor body. This creates a voltage on the shaft relative to ground  
that, if not effectively controlled, can damage both journals and bearings. The shaft  
voltage suppressor is a filter that conducts the high frequency components of the  
induced voltages to ground and limits shaft voltage caused by thyristor commutation  
to less than 7 V zero to peak. For the connections to the field, refer to Figure 4-11.  
Generator Field -  
Generator Field +  
Shaft Voltage Suppressor  
C1  
C2  
R5  
R6  
TB1-2  
TB1-1  
R1  
R2  
R3  
R4  
TB1-3  
Field  
Flashing  
J1-1  
J1-2  
7
8
53B  
AUX  
Thyrite  
TH1  
TH2  
Crowbar  
CBRO  
HSA  
HSC  
1
2
Heatsink  
JCY  
JCX  
DEPL  
EPL1  
EPL2  
Figure 4-11 Shaft Voltage Suppressor, Thyrite, and Crowbar  
4-18 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Data Highway Connections  
The EX2100 exciter communicates over the same data highway as the Mark VI  
The Data Highway integrates  
several different single  
control systems.  
turbine control and the HMI. A typical exciter connection to the redundant Unit Data  
Highway (UDH) network is shown in Figure 4-12. This shows redundant control  
with two ACLAs. The UDH is implemented using commercially available fast  
Ethernet switches.  
10Base-T cabling is used for short distances between the controller and the T-switch,  
and any local HMI. The 10BaseT ports in the ACLA and the T-switch are for RJ-45  
connectors. The maximum distance for local traffic at 10 Mbps using unshielded  
twisted pair cable is 100 m.  
100Base-FX fiber optics can be used for longer distance communication between the  
local controllers and the central control room. The 100BaseFX ports in the T-switch  
and the Ethernet switch are for SC type fiber-optic connectors. The maximum  
distance at 100 Mbps using 100BaseFX fiber-optic cables is 2 km. Redundancy can  
be obtained by using two T-switches with an interconnecting cable.  
Central Control Room  
Fast  
Fast  
Ethernet  
Switch B  
Ethernet  
Switch A  
From other Units  
From other Units  
100Base-FX  
connections  
T-Switch A  
T-Switch B  
To local HMI  
Viewer,  
10Base-T  
10Base-T  
connections  
From other Controllers  
From other Controllers  
Local Control Area  
Exciter Control  
Cabinet  
Industrial  
Systems  
Industrial  
GE  
Systems  
GE  
g
g
S
T
A
T
U
S
S
T
A
T
U
S
Ethernet Port,  
RJ-45  
ACLA  
H1A  
ACLA  
H1A  
Figure 4-12. Unit Data Highway Connections  
EX2100 User’s Guide GEH-6632  
Chapter 4 Terminal Board I/O and Equipment Connections 4-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control System Toolbox Connection  
The toolbox connector on the exciter backplane supports an RS-232C cable, which  
connects an external computer to the DSPX board. This connection is for  
maintenance purposes. There are three 9-pin connectors located at J303B, J310B,  
and J313B to support communication with controllers M1, M2, and C. (Refer to  
Figure 4-13).  
The UDH can also provide a toolbox interface using the Ethernet port on the ACLA.  
This is a 10BaseT port and uses an RJ-45 connector for unshielded twisted pair  
cable.  
UDH Ethernet Data  
Highway to Toolbox  
and HMI  
ACLA  
DSPX  
DSPX ACLA  
DSPX  
EISB  
EMIO ESEL ESEL EMIO  
EISB  
EISB  
EMIO  
Toolbox RS-232C  
Computer Cable  
Connections  
J304 J305 J306 J307 J308 J309  
J314 J315  
E
P
C
T
E
G
P
A
1
E
G
P
A
2
E
P
C
T
E
P
C
T
Key Pad  
M1  
Key Pad  
M2  
Key Pad  
C
J404 J405 J406 J407 J408 J409  
J414 J415  
E
G
P
A
3
E
G
P
A
4
E
C
T
E
C
T
B
E
C
T
B
Tool M1  
Tool M2 Tool C  
Test Rings M1  
Test Rings M2 Test Rings C  
B
J504 J505 J506 J507 J508 J509  
J514 J515  
E
E
A
C
F
E
A
C
F
E
X
T
B
E
G
P
A
5
E
G
P
A
6
E
X
T
B
E
A
X
T
B
C
F
J602  
J610  
J612  
M1  
Power  
M2  
Power  
C
Powr  
IS200EBKP  
Figure 4-13. Toolbox Connections  
4-20 Chapter 4 Terminal Board I/O and Equipment Connections  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 5 Diagnostic Interface-Keypad  
Introduction  
This chapter provides operating guidelines for the Diagnostic Interface, more  
commonly called the keypad. The keypad is a door-mounted, local control unit that  
enables you to:  
Monitor frequency, current, power, and voltage  
Start and stop the exciter  
Set and adjust configuration parameters  
Examine and reset fault conditions  
This chapter is organized as follows:  
Section  
Page  
Using the Pushbuttons.............................................................................................. 5-2  
Reading the Display................................................................................................. 5-5  
Changing Display Units.................................................................................... 5-7  
Adjusting Display Contrast............................................................................... 5-7  
Status Screen............................................................................................................ 5-8  
Reading the Meters........................................................................................... 5-8  
Alternate Status Screen (Display I/O)...................................................................... 5-8  
Using the Menus ...................................................................................................... 5-9  
Viewing and Resetting Faults .................................................................................. 5-9  
Editing Parameters................................................................................................. 5-10  
Parameter Backup........................................................................................... 5-11  
Firmware and Hardware Information..................................................................... 5-13  
Protecting the Keypad............................................................................................ 5-14  
Modifying the Protections .............................................................................. 5-14  
EX2100 User’s Guide GEH-6632  
Chapter 5 Diagnostic Interface-Keypad 5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Using the Pushbuttons  
The keypad includes membrane-type pushbuttons to access exciter values and to  
control the exciter. Tables 5-1 and 5-2 define the pushbutton functions for menu  
navigation and exciter control (see Figure 5-1).  
EX2100 Excitation Control  
g
Exciter Health  
& State Icons  
FVR Feedback  
0.0 Volts  
FldCurrAmps  
0.00 Amps  
0%  
0%  
100% 150%  
100% 150%  
-30%  
-30%  
Vmag  
Imag  
Watts  
0.00  
0.00  
0.00  
Freq_Hz  
Balance Meter  
Vars  
60.00  
0.00  
0.00  
On  
Exciter Control  
Navigation  
Run (Green)  
Stop (Red)  
Reset  
Auto  
Status  
Faults  
Command  
Man  
Menu  
Menu  
Voltage Level  
Off  
Escape  
Enter  
Display:  
Pushbuttons:  
Status screens provide analog and digital  
Organized into functional groups:  
representation of exciter functions and values.  
Navigation buttons for using the menu  
Exciter Control buttons  
Menu screens provide text-based access to  
parameters, wizards, and faults.  
Run and Stop buttons  
Figure 5-1. Diagnostic Interface - Keypad  
5-2 Chapter 5 Diagnostic Interface-Keypad  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5-1. Navigation Pushbuttons  
Button  
Function  
Displays the default Status Screen, which shows eight parameters as numbers or  
bargraphs. A set of Health icons (displayed at all times; see Exciter Health and State  
Icons) provides additional exciter status information.  
Status  
If pressed while displaying a Menu screen (see Menu Selections), displays the Main  
Menu.If pressed while displaying a Status screen, displays the last Menu screen. If held  
down, the up and down arrow keys adjust screen contrast  
Menu  
Menu Navigation: Used to highlight (reverse image) an item in a menu of options.  
Adjust Contrast, if menu key is held down.  
Entry of Numeric Parameter: Used to index through numbers (0-9, ., -) when editing a  
parameter.  
Entry of Option Parameter: Used to index through 1 – n choices.  
(See Parameter Configuration.)  
Menu Navigation: Right Arrow button displays the next selected level down in a menu  
tree. Left Arrow button displays next level up in menu tree.  
Entry of Numeric Parameter: Used to select a digit when editing a parameter.  
Entry of Option Parameter or Command Execution: Not functional.  
Menu Navigation: Displays the next level up in menu tree.  
Entry of Parameter: Displays the parameter list.  
Escape  
Enter  
Menu Navigation: Displays the next level down in menu tree.  
Entry of Parameter: Accepts editing of parameter.  
EX2100 User’s Guide GEH-6632  
Chapter 5 Diagnostic Interface-Keypad 5-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5-2. Exciter Control Pushbuttons  
Button  
Function  
Reset  
Faults  
Resets faults.  
Command  
Menu  
Quick access to a list of commonly used commands  
Selects Auto mode (AC regulator or AVR)  
Selects Manual mode (DC regulator or FVR)  
Increase voltage, VARS, PF  
Auto  
Man  
Decrease voltage, VARS, PF  
Run  
Stop  
5-4 Chapter 5 Diagnostic Interface-Keypad  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reading the Display  
The keypad displays information as both text and animated graphics. There are two  
types of content screens, selected by pressing the corresponding Navigation button:  
Status and Menu.  
The Status Screen (Figure 5-2) is the default screen that displays after exciter  
startup, following an initialization screen. It uses animated meters with associated  
text to present exciter performance data. An alternate Status Screen can also be  
accessed (see Status Screen).  
Heartbeat  
Fault State  
Limiter  
Text Identifying  
Exciter Variable  
Animated  
Meters  
FVR Feedback  
0.0 Volts  
FldCurrAmps  
0.00 Amps  
0%  
0%  
100% 150%  
100% 150%  
-30%  
-30%  
Auto Mode  
Running  
Online  
Vmag  
Imag  
Watts  
0.00  
Vars  
0.00  
0.00  
Freq_Hz  
60.00  
0.00  
Balance Meter  
0.00  
Figure 5-2. Status Screen Example  
The Menu Screen (see Figure 5-3) lists and provides access to menu-based  
functions for adjusting parameters, running wizards, and viewing faults (see Menu  
Selections).  
Main Menu  
Fault List  
Alarms  
Alarm String  
Application data  
Diagnostic and utility functions  
General setup  
I/O interface  
Figure 5-3. Menu Screen Example  
The Exciter Health and State Icons continually show on the right hand side of all  
display screens. They indicate if the exciter is functioning correctly and show its  
running state. These icons are displayed in five functional groups, as shown below.  
You can change the display units and adjust the display contrast, if needed.  
EX2100 User’s Guide GEH-6632  
Chapter 5 Diagnostic Interface-Keypad 5-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5-3. Exciter Health and State Icons  
Group  
Icon  
Indication  
Description  
Communications  
OK  
Animated line (its center raises and lowers) shows that there is  
communication between the keypad and the exciter.  
Heartbeat  
Communications  
not established  
Animated metronome icon shows that the keypad is attempting to  
establish communication with the exciter, but cannot.  
Auto mode  
Regulates terminal voltage.  
Regulates field voltage.  
Control  
Manual mode  
Test Mode  
Exciter OK  
The exciter is performing a diagnostic test.  
Blank  
When no icon displays, the exciter is operating correctly.  
Abnormal  
Displayed when there are over-ridden parameters.  
Displayed when an alarm condition occurs.  
Fault State  
Alarm state  
Trip fault  
Displayed when a fault state occurs.  
blinking  
Stopped  
Running  
Limiting  
Exciter is stopped.  
Exciter is running.  
o
Status  
Field voltage regulator output is greater than field current regulator  
or V/Hz or UEL limits are active.  
Offline  
Online  
Exciter is offline.  
Exciter is online.  
5-6 Chapter 5 Diagnostic Interface-Keypad  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Shortcut – Press and hold the  
Menu key. Press the Up and  
Down arrows to adjust the  
display contrast.  
                                                                          
                                                                          
Changing Display Units  
Ø
To change the type of measurement units displayed  
1. From the Main Menu, select General Setup.  
2. Select Display Units.  
3. Select the display units parameter to edit it (see below).  
4. Highlight, then select the preferred display units.  
Press ENTER to accept, ESC to leave  
Display units  
New Value  
= Metric (SI)  
Present Value = Metric (SI)  
Adjusting Display Contrast  
Ø
To adjust the display contrast  
1. From the Main Menu, select General Setup.  
2. Then select:  
a. Keypad  
b. Keypad Functions  
c. Adjust Screen Contrast  
This displays the following screen.  
- CONTRAST ADJUSTMENT -  
HOLD UP ARROW TO INCREASE  
HOLD DOWN ARROW TO DECREASE  
Press ESCAPE to Continue  
3. Press the Escape button to save the contrast value and return to the previous  
menu.  
EX2100 User’s Guide GEH-6632  
Chapter 5 Diagnostic Interface-Keypad 5-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Status Screen  
The Status screen displays up to eight variables (parameters). The first two  
parameters are displayed both in text and animated meters. Table 5-4 defines the  
characteristics of the bar graphs for these parameters.  
Reading the Meters  
A variable shown as a bar graph is over range when it is either greater than + 100%  
or less than –100%. The over range mark is shown with a vertical bar through the bar  
graph at the +100% and the –100% marks.  
Not Over Range  
+100%  
-100%  
Over  
Range  
Table 5-4. Animated Meter Characteristics (Default) for Status Screen  
Bar Graph  
Variable  
Numeric Display  
Units in Bar Graph  
DC bus voltage  
AC line current  
Magnitude of dc bus voltage (FVR feedback)  
Magnitude of ac line current (I_Mag_Fil)  
Percentage of dc per unit volts (VDC_PU)  
Percentage of source top-rated current (I_PU)  
Alternate Status Screen (Display I/O)  
The keypad has an alternate Status screen that displays the status of the general  
purpose inputs and outputs. To toggle between the Meter Status Screen and the I/O  
Status Screen, press any of the Arrow buttons.  
The circle under each heading indicates the status of the corresponding I/O point, as  
follows:  
l = True  
¡ = False  
Display I/O Status  
1 2 3 4 5 6  
GP Inputs  
GP Outputs  
5-8 Chapter 5 Diagnostic Interface-Keypad  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Using the Menus  
The keypad’s Main Menu leads to other menu screens, where data can be reviewed  
and modified. The Main Menu can be accessed from any screen, as follows:  
If already in a Menu screen, press the Menu button.  
If in a Status screen, press the Menu button once or twice.  
Main Menu  
Fault List  
Alarms  
Alarm String  
Application data  
Diagnostic and utility  
General setup  
I/O interface  
Note The Main Menu selections may vary from product to product.  
Use the Navigation buttons to move through the menus, select items, and adjust  
values  
Press the Up or Down Arrow buttons to move through and highlight menu  
items.  
Press the Enter button to select a highlighted item  
To return to a previous menu screen, press the Escape button, Left Arrow  
button, or follow on-screen instructions.  
When a menu has more than one screen:  
Move to the next screen by highlighting the last item on the displayed  
screen, then press the Down Arrow button once more.  
If the last menu item is reached, then pressing the Down Arrow button will  
wrap back to the first item on that menu.  
Viewing and Resetting Faults  
When the display indicates either a Trip or an Alarm fault (refer to Reading the  
Display), you can view information and reset (clear) current faults, as follows:  
1. From the Main Menu, select Fault List, then select Display Active Faults.  
The following screen displays.  
Faults are displayed in order  
of occurrence with the most  
recent fault at the top.  
ACTIVE FAULT DISPLAY  
86 Trip  
115 Trip  
58 Brief  
95  
DC Over-current Trip  
Bridge 1 Fan 1 BAD  
Low AC V  
Field temp alarm  
--- RESET FAULTS NOW ---  
Refer to GEH-6633 Troubleshooting, Preventive and Online Maintenance, for a list  
of faults.  
EX2100 User’s Guide GEH-6632  
Chapter 5 Diagnostic Interface-Keypad 5-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. To view detail on a particular fault, select that fault (listed on the Active Fault  
Display screen). The following screen displays.  
SELECTED FAULT - PRESS  
Low AC V, B  
006:40:11.008  
Low AC input volts detected on  
the field exciter.  
3. Reset the faults either of two ways:  
- Select Reset Faults Now in the Fault Display screen.  
- Press the Reset Faults button.  
Ø
To view the exciter’s Fault History (a list of previously cleared faults  
and fault resets)  
This display list may be  
multiple screens long.  
From the Main Menu, select Fault List, then select Display Fault History.  
FAULT HISTORY DISPLAY  
0 Cleared  
86 Trip  
115 Trip  
Fault reset  
DC Over-current trip.  
Bridge 1 Fan 1 BAD  
58 Brief  
95  
Low AC V  
Field temp alarm  
--- RESET FAULTS NOW ---  
Editing Parameters  
There are two types of parameters that can be changed using the keypad:  
Option parameters lists items (options) for you to select. For example,  
True/False is an option parameter.  
Numeric parameters lists valid digits that you select to create a number.  
Ø
To edit a parameter  
1. From an exciter Parameters screen, select the parameter that is to be changed.  
Parameters  
GPT_Vrms  
VHiTripLev  
AFFL  
=
=
=
<No Value>  
1.2  
100  
Trip enabled  
100  
TripVHiTrip  
VFFL  
=
=
100.0  
This displays either an Option or Numeric parameter screen (see both below) with  
the New Value line highlighted.  
5-10 Chapter 5 Diagnostic Interface-Keypad  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. For an Option parameter:  
a. Use the Up or Down Arrow buttons to select a new parameter value.  
b. Press the Enter button to accept the change or Escape to exit and keep the  
present value.  
Press ENTER to accept, ESC to leave  
TripVHiTrip  
New Value  
= Trip disabled  
Present Value = Trip enabled  
3. For a Numeric parameter:  
a. Use the Left or Right Arrow buttons to highlight the digit to be changed.  
If you continue pressing the Left Arrow button after reaching the left-most  
digit of the edit field, the field fills with blanks. Pressing Enter when the  
entire number is blanked out saves a <No Value>.  
b. Use the Up and Down Arrow buttons to index through the valid digits (0, 1,  
2, 3, 4, 5, 6, 7, 8, 9, e, ., -).  
The e in the digit selection represents the start of the exponent in scientific  
notation. If the e is used, all digits to the right of the e make up the  
number’s exponent.  
Press ENTER to accept, ESC to leave  
VHiTripLev  
New Value  
=
1.3  
Present Value =  
1.2  
Low Limit  
High Limit  
=
=
0.0000000  
3.4028239e38  
4. When all of the digits have been changed, press Enter to accept the new value  
or press Escape to exit and keep the present value.  
Parameter Backup  
It is good practice to keep a backup copy of the exciter’s working parameter  
configuration. You can then restore this file, if needed, or compare it with a re-  
configured file to determine differences.  
Ø
To save active parameters  
1. From the Main Menu, select Parameter Backup Functions then select  
Save Parameters to Backup.  
Each new backup overwrites  
the previous backup copy,  
which cannot be restored.  
Save Parameters to Backup  
Save current parameter values.  
Press ENTER to continue. ESC cancels.  
EX2100 User’s Guide GEH-6632  
Chapter 5 Diagnostic Interface-Keypad 5-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Press Enter to make a backup copy of the parameters or Escape to cancel.  
To restore a parameter from backup  
Ø
1. Stop the exciter. (This function cannot be executed with the exciter running.)  
2. From the Main Menu, select Parameter Backup Functions then select Restore  
Parameters from Backup.  
Press to restore Parameters from Backup  
-- WARNING --  
The active parameter values will be  
replaced, and can not be recovered.  
Press ENTER to continue. ESC cancels.  
3. Press Enter to restore the backup parameters or Escape to cancel.  
Restoring parameters from a backup file overwrites the  
currently active parameter values, which cannot then be  
restored.  
Ø
To compare the active parameter set to the backup parameter set  
1. From the Main Menu, select Parameter Backup Functions then select  
Compare Current Parameters to Backup.  
BACKUP DIFFERENCES  
VHiTripLev = 1.3  
= 1.2  
<More >  
Backup value  
Backup value  
Backup value  
AFFL  
= 112.0  
= 100.0  
= 110.0  
= 100.0  
VFFL  
<More >  
2. Use the Up and Down Arrow buttons to scroll through the list of backup  
differences.  
3. Press Escape to return to the previous menu.  
5-12 Chapter 5 Diagnostic Interface-Keypad  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Firmware and Hardware Information  
Ø
To view the firmware versions for the DSPX board and the keypad  
From the Main Menu select:  
1. General Setup  
2. Firmware Version & Hardware Info  
3. Display Firmware Version  
The following screen displays:  
GE Generator Control  
EX2100  
DSPX Firmware Version:  
V02.06.00B  
DSPX Boot Monitor Version: V02.02.00C  
DDI Firmware Version:  
V02.00.00B  
Press ESC to exit  
Ø
To view exciter hardware information  
From the Main Menu select:  
1. General Setup  
2. Firmware Version & Hardware Info  
3. Display Hardware Information  
The following screen displays:  
GE Generator Control  
Hardware Information:  
IS200ESELH1APR 5473716  
IS215ACLAH1AL 8790070  
IS200DSPXH1CAA 7611193  
IS200EMIOH1APR 7360814  
IS200EISBH1APR 5673766  
ESC to exit  
<More >  
EX2100 User’s Guide GEH-6632  
Chapter 5 Diagnostic Interface-Keypad 5-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Protecting the Keypad  
To protect the exciter from unauthorized operation or reconfiguration, the keypad  
includes two security controls, Password and Privilege Level.  
The Password is a 5-digit number that protects the Password and Privilege Level  
from being changed by unauthorized personnel. The default Password is 00000.  
Privilege Level specifies which operational and configuration functions are disabled  
in the keypad. There are three levels:  
Read Only disables both the Exciter Control and the Configuration functions.  
An operator can view but not edit parameters.  
Operate & Read Only enables the Exciter Control function, but disables  
Configuration functions. An operator can view, but not edit parameters.  
Configure & Operate enables both the Exciter Control and the Configuration  
functions. This is the default setting.  
If you try to execute a function that is disabled in the active Privilege Level, the  
keypad displays the following error message.  
Incorrect password!  
Press Any Key to Continue  
Modifying the Protections  
Ø
To modify the Password and Privilege Levels  
1. From the Main Menu, select:  
a. General Setup  
b. Keypad  
c. Keypad Security  
The following screen displays:  
Press ENTER to accept, ESC to leave  
Enter Password: 00000  
5-14 Chapter 5 Diagnostic Interface-Keypad  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Enter the password as follows:  
a. Use the Up and Down Arrow buttons to index through the valid digits (0  
through 9).  
b. Use the Right and Left Arrow buttons to move the cursor to the digit to  
edit.  
-
-
Press Enter to accept the Password.  
If the password that was entered matches the saved Password value,  
you can then modify the Privilege Level or Password.  
Keypad Security  
Keypad privilege  
Keypad password  
=Configure &  
=
If it does not match, the keypad displays an error message.  
Incorrect password!  
Press Any Key to Continue  
3. Use the Up and Down Arrow buttons to select either the Privilege Level or  
Password.  
4. Press Enter to edit the parameter. (See Editing Parameters.)  
Note When you modify the keypad password, be sure to select Save Parameters To  
Backup. Otherwise, the password stored in the active parameter will not match the  
backup parameter set. That causes the Compare Current Parameters to Backup to  
identify the Keypad Password parameter as different.  
EX2100 User’s Guide GEH-6632  
Chapter 5 Diagnostic Interface-Keypad 5-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
5-16 Chapter 5 Diagnostic Interface-Keypad  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A Warranty and Renewal  
Parts  
Introduction  
When ordering a replacement part for a GE exciter, the customer needs to know:  
How to accurately identify the part  
If the part is under warranty  
How to place the order  
This information helps ensure that GE can process the order accurately and as soon  
as possible.  
To minimize system downtime if repair is needed, GE recommends that the customer  
keep a set of spare parts on hand. The Renewal Parts Quotation lists  
recommended spares.  
Appendix A of this manual provides information to help the user identify and obtain  
replacement parts. It is organized as follows:  
Section  
Page  
Identifying the Part ................................................................................................. A-2  
Renewal Parts List........................................................................................... A-2  
Part Number Structure ..................................................................................... A-2  
Warranty Terms ...................................................................................................... A-4  
How to Order Parts ................................................................................................. A-5  
Data Nameplate ............................................................................................... A-5  
ML Number ..................................................................................................... A-5  
EX2100 User’s Guide GEH-6632  
Appendix A Warranty and Renewal Parts A-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Identifying the Part  
An exciter component, or part, is identified by its assigned part number and  
description. The part number is normally found on a nameplate on the component.  
The description is included in the system renewal parts list.  
Renewal Parts List  
The Renewal Parts List is a separate document that lists the parts of a complete  
system. This list applies specifically to the equipment furnished on a customer’s  
particular application (requisition) at the time of shipment. It includes:  
Part numbers and descriptions  
Quantity used  
Recommended spares to keep onhand  
Normal delivery cycle for obtaining each part  
GE provides the Renewal Parts List with the exciter’s custom instructions. If this  
document is missing, contact the nearest GE sales office or service representative to  
obtain a replacement copy. You need to provide the following information (see  
Figure A-4) to correctly identify the system:  
Requisition number  
Model number  
Part Number Structure  
A GE part number is structured so that different portions of the number identify the  
type of equipment and location of manufacture. A part falls into one of four  
categories:  
Order-specific assemblies – Major assemblies or items that make up a specific  
exciter, constructed from common assemblies  
Common assemblies – Subassemblies used in many GE exciter products, not  
just a specific exciter  
Components – Individual parts that make up assemblies  
Printed wiring boards  
These categories and the makeup of their part numbers are defined under Order  
Specific Assemblies.  
A-2 Appendix A Warranty and Renewal Parts  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Order Specific Assemblies  
These parts make up the particular exciter. Other items obtained specifically for the  
order may also use a similar part number structure, which provides information about  
the equipment.  
3V AAA  
XX###  
123  
Unit & sequence number of  
Sequence/projec  
Unique  
to req'n  
Order  
product line  
Identifies manufacturer as GE  
Systems, Salem,  
Sample Part Number for Order-Specific Assembly  
Common Assemblies  
Common assemblies are subassemblies used as components of order-specific  
assemblies. Common assemblies are not designed for a particular exciter, but provide  
a function used in other GE products.  
For example, 36C774524AAG48 is the part number for a cable.  
Components  
Components are the basic parts that make up assemblies. They represent the  
lowest discrete level of a system. Component part numbers consist of a combination  
of alphanumeric characters that define the class and specific item. A sample number  
is shown below.  
104X 109 1ADO38  
Item or rating (500 V, 3.2 A FNQ)  
Component type (fuse)  
Component  
Sample Part Number for Component  
EX2100 User’s Guide GEH-6632  
Appendix A Warranty and Renewal Parts A-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Printed Wiring Boards  
A printed wiring board is identified by an alphanumeric part (catalog) number  
stamped near its edge. The structure of a board’s part number is described below.  
Note All digits are important when ordering or replacing any board.  
The factory may substitute later versions of boards based on availability and design  
enhancements. However, GE Industrial Systems ensures compatibility of  
replacement boards.  
IS 200 DSPX G# A A A  
Artwork revision1  
Functional revision1  
Functional revision2  
Group (variation, G or H)  
Functional acronym  
Assembly level3  
Manufacturer (DS & IS for GE in Salem, VA)  
1Backward compatible  
2Not backward compatible  
3200 indicates a base-level board; 215 indicates a  
higher-level assembly or added components (such  
as PROM)  
Sample Board Part Number  
Warranty Terms  
The GE Terms and Conditions brochure details product warranty information,  
including warranty period and parts and service coverage. The brochure is  
included with customer documentation. It may be obtained separately from the  
nearest GE Sales Office or authorized GE Sales Representative.  
Note Standard warranty is 18 months from shipment or 12 months from when  
power is first applied, whichever comes first.  
A-4 Appendix A Warranty and Renewal Parts  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
How to Order Parts  
Parts still under warranty may be obtained directly from the factory:  
GE Industrial Systems  
(“+” indicates the  
Product Service Engineering  
1501 Roanoke Blvd.  
Salem, VA 24153-6492 USA  
international access code  
required when calling from  
outside of the USA.)  
Phone:  
Fax:  
+ 1 800 533 5885 (United States, Canada, Mexico)  
+ 1 540 378 3280 (International)  
+ 1 540 387 8606 (All)  
Renewals (spares or those not under warranty) should be ordered by contacting the  
nearest GE Sales or Service Office. Be sure to include:  
Complete part number, located in the renewal parts list  
Part name  
Exciter model, located in it's nameplate  
Data Nameplate  
The data nameplate is located on the back of the cabinet door. It provides  
information needed when ordering parts or contacting GE for assistance.  
ML Number  
Each GE lineup, cabinet (panel)/case, and core unit has a unique identifying catalog  
number, also called the part or material list (ML) number. This number is  
structured to provide information about that equipment. The catalog number links the  
equipment to its requisition, drawings, components, materials, specification item,  
and shipping documents.  
3V AAA  
XX###  
123  
Unit & sequence number of components:  
CA## = Case assembly  
CD## = Core dc drive controller  
CI### = Core ac drive controller  
LU### = Lineup, multiple case  
assembly  
PN## = Panel assembly  
RL## = Requisition-level assembly  
Sequence/project  
Unique  
to req'n  
Order month/year/  
product line  
Identifies manufacturer as GE Industrial  
Systems, Salem, VA  
Sample Exciter ML (Catalog) Number  
EX2100 User’s Guide GEH-6632  
Appendix A Warranty and Renewal Parts A-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
A-6 Appendix A Warranty and Renewal Parts  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B Ratings and  
Specifications  
The actual equipment rating is on your exciter nameplate.  
This appendix indicates the range of possible product  
offerings but not necessarily the capability of your exciter.  
EX2100 Specification  
Power Conversion Module (PCM)  
Single bridge rating  
Description  
1,000 and 2,000 A dc at up to 1,000 V ac  
Parallel bridge rating  
8,000 A dc at up to 1,500 V ac, with up to 6 bridges  
150% of design Amperes (EDA) for 30 s at 40 ºC  
Forcing requirements  
Power Sources  
Power for the PCM – Voltage source  
Auxiliary bus  
Generator terminals  
Compound Source  
600 or 1,000 V versions  
Power for the PCM – VA (power)  
Power for the PCM - Frequency  
Power to the Cooling Fans (3)  
Flashing power  
3,251 KVA (1,000 V version)  
3-phase 50/60 Hz, ± 5%  
10 A rms, 125 V ac single source  
125-250 V dc battery source, with up to 200 A for at least 10 s  
380-480 V ac, 50/60 Hz single-phase auxiliary source  
For two ac sources, or one ac and one dc source  
Nominal 120 V ac ±15%, with 1 DACA, 10 A rms max.  
Battery source 125 V dc, range 80-140 V dc, 10.6 A dc max.  
10 KW for a 2000 A, 1,000 V ac PCM  
Control power (redundant with 2 bridges,  
warm backup}  
Heat loss in single PCM cabinet  
EX2100 User’s Guide GEH-6632  
Appendix B Ratings and Specifications B-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input/Output  
QTY  
Potential transformers (PTs)  
2
3-phase standard, single-phase available  
120 V ac nominal  
1 VA nominal burden  
Current transformers (CTs, 1 or 5 A)  
2
Any two phases, single phase is available  
1 VA nominal burden  
86G dedicated contact input  
52G dedicated contact input  
Trip rated contact outputs  
1
1
2
Open for trip  
Closed for online  
At 125 V dc the relay break characteristics are:  
Resistive load 0.5 A  
Inductive load 0.2 A  
General Purpose contact inputs  
6
4
Customer contact, 70 V dc supplied by ECTB  
At 125 V dc the relay break characteristics are:  
Resistive load 0.5 A  
General Purpose Form C contact outputs  
Inductive load 0.1 A  
± 10 V differential amplifier input  
Control  
1
Automatic ac Voltage Regulation  
Proportional + Integral, software implemented  
± 0.25 % over full voltage range  
Manual dc Voltage regulator  
Protection Features  
Proportional + Integral, software implemented  
± 2.0 % over full voltage range  
Under Excitation Limiter, (UEL)  
Over Excitation protection (76)  
Generator Field Ground detection (64F)  
Generator Overvoltage protection (24G)  
Loss of Excitation protection (40)  
V/Hz limit (24) and trip (24T)  
Bridge Over Temperature (26)  
Field Over Temperature (49)  
Phase Unbalance (22)  
PT Failure (60)  
Environmental Control & Protection  
Base controls cabinet  
Continuous operation in a 0 to 40 ºC ambient environment  
Base power bridge and auxiliary cabinet  
Continuous operation in a 0 to 40 ºC ambient environment, with 5 to 95%  
humidity, non-condensing  
Storage Temperature  
Humidity  
-40 ºC to +70 ºC  
5 to 95% humidity, non-condensing  
Altitude  
Normal operation at 0 to 1000 m. Derate 6% per 1000 m above 1000 m  
Forced air cooling required for PCM cabinet  
Reactive Sulfur, Reactive Chlorine, Hydrogen Sulfide  
Sulfur Dioxide, Chlorine Dioxide, Sulfuric Acid  
Hydrochloric Acid, Hydrogen Chloride, Ammonia  
Cooling  
Contaminants, withstand 10 PPB of  
these:  
Vibration  
Seismic  
Universal Building Code (UBC) – Seismic Code section 2312 Zone 4  
72 hours at 0.3 G rms between 4 to 16 Hz  
Shipping  
3 shocks of 15 G, 2 ms impulse for all three axes  
1.0 G Horizontal, 0.5 G vertical at 15 to 150 Hz  
Operating/Installed at Site  
B-2 Appendix B Ratings and Specifications  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cabinet Dimensions & Weight  
Redundant control with dual PCM  
redundant converter in a three-cabinet  
lineup  
Width 141.74 in (3600 mm)  
Height 104.32 in (2650 mm)  
Depth  
31.5 in (800 mm)  
Weight of Converter cabinet  
3,600 lbs.  
5,600 lbs.  
Weight of Total Lineup (Converter,  
Control, and Auxiliary cabinets)  
Cabinet type, control & auxiliary  
Cabinet type, power conversion  
Power and Control Cable Access  
Reliability  
NEMA 1 (IEC IP 20), convection cooled  
NEMA 1 (IEC IP 20), forced air cooled  
Entrances from the top and/or bottom  
MTBF - Mean Time Between Failures  
MTBF - Mean Time Between Failures  
MTTR - Mean Time to Repair  
Acoustic  
Simplex system 25,000 hrs  
Redundant system 175,000 hrs  
Any subsystem 4 hrs  
Generated Acoustic Noise (Preliminary)  
PCM cabinet approximately 75 dB  
Codes and Standards  
UL 508C  
Safety Standard Industrial Control Equipment  
Industrial Control Equipment  
CSA 22.2 No. 14  
UL 796  
Printed Wire Board Assemblies  
ANSI IPC  
Guidelines  
IEC 801-2:1991  
ENV 50140:1993  
EN 50082-2:1994  
IEC 801-4  
Electrostatic Discharge Susceptibility  
Radiated RF Immunity  
Generic Immunity Industrial Environment  
Electrical Fast Transient Susceptibility  
Surge Immunity  
IEC 1000-4-5  
IEC 1000-4-6  
ENV 55011:1991  
EN 61010-1  
Conducted RF Immunity  
ISM Equipment Emissions  
Safety of Electrical Equipment, Industrial Machines  
Intrusion Protection Codes/NEMA 1/IP 20  
Standard Definitions for Excitation Systems for Synchronous machines  
IEC 529  
IEEE 421.1  
IEEE 421.2  
Guide for Identification, Testing, and Evaluation of the Dynamic  
Performance of Excitation Control Systems  
IEEE 421.3  
IEEE 421.4  
IEEE 421.5  
High-Potential Test Requirements for Excitation Systems  
Guide for the preparation of Excitation Systems Specs  
Recommended Practice for Excitation Systems for Power Stability  
Studies  
EN50178/LVD/EMC  
IEEE C57.12.01  
IEEE C57.110  
CE Compliance  
General Requirements for Dry-Type Distribution & Power Transformers  
Recommended Practice for Establishing Transformer Capability when  
supplying Non-Sinusoidal Load Currents  
IEEE C57.116  
IEEE C37.90.1  
IEEE Guide for Transformers Directly Connected to Generators  
Surge Withstand Capability (SWC) tests for Protective Relays and Relay  
Systems  
IEEE C57.18.10  
Practices and Requirements for Semiconductor Power Rectifier  
Transformers  
EX2100 User’s Guide GEH-6632  
Appendix B Ratings and Specifications B-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
B-4 Appendix B Ratings and Specifications  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary of Terms  
6U  
Full height Versa Module Eurocard (VME) board  
application code  
Software that controls the machine or process, specific to the application.  
ASCII  
American Standard Code for Information Interchange. An 8-bit code used for data.  
auxiliary source  
A source of three-phase ac power for the exciter, but not from the generator being  
controlled.  
automatic voltage regulator (AVR)  
AVR is controller software that maintains the generator terminal voltage through the  
Field Voltage Regulator.  
baud  
A unit of data transmission. Baud rate is the number of bits per second transmitted.  
BIOS  
Basic input/output system. Performs the controller boot-up, which includes hardware  
self-tests and the file system loader.  
bit  
Binary Digit. The smallest unit of memory used to store only one piece of  
information with two states, such as One/Zero or On/Off.  
EX2100 User’s Guide GEH-6632  
Glossary of Terms i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
block  
Instruction blocks contain basic control functions, which are connected together  
during configuration to form the required machine or process control. Blocks can  
perform math computations, sequencing, or regulator (continuous) control.  
board  
Printed wiring board or card.  
bus  
Upper bar for power transfer, also an electrical path for transmitting and receiving  
data.  
bumpless  
No disruption to the exciter when transferring control.  
byte  
A group of binary digits (bits); a measure of data flow when bytes per second.  
CMOS  
Complementary metal-oxide semiconductor.  
COM port  
Serial controller communication ports (two). COM1 is reserved for diagnostic  
information and the Serial Loader. COM2 is used for I/O communication  
configure  
To select specific options, either by setting the location of hardware jumpers or  
loading software parameters into memory.  
crowbar  
The crowbar limits the high negative voltages that can be induced into the PCM  
during a pole slip (loss of synchronism) event. It includes a discharge resistor, and is  
self firing.  
CT  
Current Transformer, used to measure current in an ac power cable.  
DACA  
Ac to dc converter for power supply, produces 125 V dc.  
ii Glossary of Terms  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DCS (Distributed Control System)  
Control system, usually applied to control of boilers and other process equipment.  
de-excitation  
The de-excitation circuit provides a conduction path through a discharge resistor to  
dissipate the field current after a unit trip.  
device  
A configurable component of a control system.  
DRAM  
Dynamic Random Access Memory, used in microprocessor-based equipment.  
EGD  
Ethernet Global Data, a control network and protocol for the controller. Devices  
share data through EGD exchanges (pages).  
EMI  
Electro-magnetic interference; this can affect an electronic control system.  
EPBP Backplane  
Exciter Power Backplane holds power supply modules, ground detect modules, and  
connectors for power distribution.  
EPDM  
Exciter Power Distribution Module distributes 125 V dc to the power supplies.  
Ethernet  
LAN with a 10/100 M baud collision avoidance/collision detection system used to  
link one or more computers together. Basis for TCP/IP and I/O services layers that  
conform to the IEEE 802.3 standard.  
EX2100 Exciter  
GE static exciter; regulates the generator field current to control the generator output  
voltage.  
fanned input  
A termination board input that is connected to all three redundant controllers.  
EX2100 User’s Guide GEH-6632  
Glossary of Terms iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fault code  
A message from the controller to the HMI indicating a system warning or failure.  
field flashing  
The supply of initial exciter current during startup, usually from station batteries.  
field ground detector  
The field ground detector is an active circuit that detects a ground in either the ac or  
dc sections of the exciter and field wiring.  
field voltage regulator (FVR)  
FVR is controller software that maintains the generator terminal voltage using inputs  
from the Automatic Voltage Regulator (AVR) and the field voltage feedback.  
firmware  
The set of executable software that is stored in memory chips that hold their content  
without electrical power, such as EEPROM or Flash.  
flash  
A non-volatile programmable memory device.  
FVR  
Field Voltage Regulator, software controlling the voltage across the field.  
gating  
Controlling the conduction of the power SCRs with an input pulse train (or a  
voltage).  
health  
A term that defines whether a signal is functioning as expected.  
heartbeat  
A signal emitted at regular intervals by software to demonstrate that it is still active.  
HMI  
Human Machine Interface, usually a PC running Windows NT and CIMPLICITY  
HMI software.  
iv Glossary of Terms  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
hot backup  
Two bridges are used but only one is connected to the field, the other (the backup) is  
connected to a small dummy load. If the active bridge fails it is disconnected from  
the field by relays, and the backup is connected.  
ICS  
Integrated Control System. ICS combines various power plant controls into a single  
system.  
IEEE  
Institute of Electrical and Electronic Engineers. A United States-based society that  
develops standards.  
I/O  
Input/output interfaces that allow the flow of data into and out of a device.  
I/O drivers  
Software that interfaces the controller with input/output devices, such as  
communication networks, sensors, and solenoid valves.  
IP address  
The address assigned to a device on an Ethernet communication network.  
line filter  
Filter networks across the three-phase input lines to the exciter to minimize the  
voltage spikes that result from the abrupt decay of current during SCR  
commutations.  
LCI Static Starter  
Electric power device that runs the generator as a motor to bring a gas turbine up to  
starting speed.  
logical  
A statement of a true sense, such as a Boolean.  
Mark VI turbine controller  
A control system hosted in one or more VME racks that performs turbine-specific  
speed control, logic, and sequencing.  
EX2100 User’s Guide GEH-6632  
Glossary of Terms v  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Modbus  
A serial communication protocol developed by Modicon for use between PLCs and  
other computers.  
multiple bridges  
Several power producing bridges operate in parallel to produce a high field current.  
These share the exciter current load to provide redundancy and increased reliability.  
NEMA  
National Electrical Manufacturers Association; a U.S. standards organization.  
non-volatile  
Memory specially designed to store information even when the power is off, for  
example Flash memory.  
OLR  
On-Line Repair, capability provided by redundant control elements.  
over-excitation limiter (OEL)  
OEL software limits the excitation current to prevent overfluxing the generator  
power conversion module (PCM)  
The PCM or Bridge consists of six three-phase rectifiers, with associated protection  
and control devices, to generate the dc field current.  
power current transformer (PCT)  
A PCT can be attached to the generator line to provide a portion of the three-phase  
power for the exciter, part of a compound source.  
power distribution module (EPDM)  
The PDM distributes 125 V dc to the power supplies for the controllers and I/O  
termination boards.  
power potential transformer (PPT)  
A PPT is attached to the generator terminals to provide three-phase power for the  
exciter; referred to as a potential source.  
power system stabilizer (PSS)  
PSS software produces a damping torque on the generator to reduce generator  
oscillations.  
vi Glossary of Terms  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
product code (runtime)  
Software stored in the controller’s Flash memory that converts application code  
(pcode) to executable code.  
PRV  
Peak Reverse Voltage is limited with pole slip resistors, wired across the SCRs.  
PT  
Potential Transformer, used for measuring voltage in a power cable.  
real-time  
Immediate response, referring to control systems that must respond instantly to  
changing conditions.  
reboot  
To restart the controller or toolbox.  
Redundant  
A system consisting of duplicated components (boards or modules), which can  
transfer functionality from a failed component to one of the duplicate components  
without loss of the entire system’s functionality.  
relay ladder diagram (RLD)  
A ladder diagram represents a relay circuit. Power is considered to flow from the left  
rail through contacts to the coil connected at the right.  
RFI  
Radio Frequency Interference; this is high frequency electromagnetic energy which  
can affect the control system.  
RTD  
Resistance Temperature Device, used for measuring temperature.  
runtime  
See product code.  
runtime errors  
Controller problems indicated on the front panel by coded flashing LEDS, and also  
in the Log View of the toolbox.  
EX2100 User’s Guide GEH-6632  
Glossary of Terms vii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sampling rate  
The rate at which process signal samples are obtained, measured in samples/second.  
serial loader  
Connects the controller to the toolbox PC using the RS-232C COM ports. The Serial  
Loader initializes the controller flash file system and sets its TCP/IP address to allow  
it to communicate with the toolbox over Ethernet.  
server  
A PC, which gathers data over Ethernet from plant devices, and makes the data  
available to PC-based operator interfaces known as Viewers.  
shaft voltage suppressor  
The shaft voltage suppressor is a filter that conducts to ground the high frequency  
components of the induced voltages in the field current.  
signal  
The basic unit for variable information in the controller.  
simplex  
System with only one set of control and I/O boards. Contrast with redundant control  
systems.  
simulation  
Running the control system using a software model of the generator and exciter.  
SOE  
Sequence of Events, a high-speed record of contact closures taken during a plant  
upset to allow detailed analysis of the event.  
Static Exciter  
Produces a controlled dc field current without the use of a rotating generator.  
TCP/IP  
Communications protocols developed to inter-network dissimilar systems. It is a de  
facto UNIX standard, but is supported on almost all systems. TCP controls data  
transfer and IP provides the routing for functions.  
TMR  
Triple Modular Redundancy. An operation that uses three sets of control and I/O  
(channels M1, M2, and C) and votes the results.  
viii Glossary of Terms  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
toolbox  
A Windows NT -based software package used to configure the EX2100 and Mark VI  
turbine controller.  
under-excitation limit (UEL)  
UEL software functions to prevent generator over-heating caused by under  
excitation.  
unit data highway (UDH)  
Connects the EX2100, Mark VI turbine controllers, LCI, PLCs, and other GE  
provided equipment to the HMI Servers; runs at 10/100 Mbaud and supports Peer-to-  
Peer communications.  
V/Hz  
V/Hz is the ratio of generator voltage to the frequency; this is limited to prevent  
overfluxing the generator.  
VME board  
Versa Module Eurocard, a European standard for printed circuit boards and  
backplane.  
warm backup  
Two bridges are connected to the field but only one is actively producing power. The  
other bridge does not receive gating pulses until it is required to take over from the  
active bridge.  
Windows NT  
Advanced 32-bit PC operating system from Microsoft.  
EX2100 User’s Guide GEH-6632  
Glossary of Terms ix  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
x Glossary of Terms  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cell Snubbers 2-5  
communication 1-2, 1-5, 2-11, 2-13, 3-4, 4-19, 4-20,  
5-6  
Compound power source 2-2  
contact input 1-7, 3-4 – 3-6, 4-4, B-2  
contact output 1-7, 3-5, 3-6, 4-4, B-2  
control 1-1, 1-2, 1-5 – 1-7, 2-1 – 2-4, 2-6, 2-8 – 2-11,  
2-13, 2-14, 2-17, 2-19, 2-20, 2-21, 3-1, 3-2, 3-4 –  
3-9, 3-11, 4-3, 4-4, 4-8, 4-11, 4-14, 4-16, 4-19,  
5-1, 5-2, B-3  
Index  
Control Boards  
ACLA 1-6, 2-11, 2-13, 2-14, 3-1, 3-2, 3-4, 4-19, 4-20  
DSPX 1-6, 2-11, 3-1, 3-2, 3-4, 3-8, 4-14, 4-20, 5-13  
EBKP 3-1, 3-2, 3-6, 3-11, 4-8  
EISB 2-11, 3-1, 3-2, 3-4, 3-6, 3-8, 4-8  
EMIO 2-11, 3-1, 3-2, 3-4 – 3-6, 4-3, 4-4, 4-16, 4-17  
ESEL 2-6, 2-11, 2-14, 3-1, 3-2, 3-4, 3-5, 3-7  
control cabinet 1-5, 2-9, 2-10, 3-11, 4-3  
Control Cabinet 2-1, 2-10  
A
ac disconnect 1-5, 2-5  
Ac Line-to-Line Filters 2-1, 2-8  
Control Module 2-1, 2-11  
Ac to Dc Converter 1-6, 2-14, 3-1, 3-9, 3-11, B-1  
ACLA (see Application Control Layer Module)  
Analog I/O 4-1, 4-2  
Analog Input 4-1, 4-3  
Application Control Layer Module 1-6, 2-11, 2-13, 2-  
14, 3-1, 3-2, 3-4, 4-19, 4-20  
Control Power Supplies 2-1, 2-14  
Diagnostic Interface 1-1, 2-1, 2-2, 2-10, 5-1  
Redundant Control System 2-1, 2-13  
Simplex Control System 2-1, 2-12  
control module 1-2, 2-6, 2-11, 2-14, 3-4, 4-14, 4-16  
Control Module 2-1, 2-11  
AUTO REF (see Auto Reference)  
Auto Reference 2-1, 2-20  
Control power supplies 2-2  
Control Power Supplies 2-1, 2-14  
Control Scheme 2-18  
Control System Toolbox 1-2, 1-6, 1-8, 2-2, 2-17, 4-1,  
4-20  
Automatic Voltage Regulator 2-1, 2-20, 2-21, 3-4  
auxiliary cabinet 1-5, 1-7, 2-5, 2-8, 2-15, 4-7, B-2  
Auxiliary Cabinet 2-1, 2-8, 3-9, 4-16  
Ac Line-to-Line Filters 2-1, 2-8  
Connection 4-1, 4-20  
Controller  
De-excitation Module 2-1, 2-8, 3-1, 3-6 – 3-8, 3-10,  
3-11, 4-11  
C 1-2, 2-11, 2-13, 2-14, 3-2, 3-4, 3-5, 3-7 – 3-9, 3-11,  
4-3, 4-14, 4-20,  
M1 1-2, 2-11, 2-13, 2-14, 3-2, 3-4, 3-5 – 3-9, 3-11,  
4-3, 4-14, 4-20  
M2 1-2, 2-11, 2-13, 2-14, 3-2, 3-4, 3-5 – 3-9, 3-11,  
4-3, 4-14, 4-20  
cooling fans 1-5, 2-2, 3-9  
Field Flashing Module 2-1, 2-9  
Field Ground Detector 2-1, 2-9, 3-7, 4-1, 4-14, 4-15  
High Voltage Interface 2-1, 2-9  
Shaft Voltage Suppressor 2-1, 2-9, 4-1, 4-18  
Auxiliary power source 2-2  
AVR (see Automatic Voltage Regulator)  
AVR Setpoint 2-1, 2-20  
Crowbar 2-2, 3-6, 3-7, 3-10, 3-11, 4-1, 4-14, 4-18  
Crowbar module 2-2, 3-7, 3-11  
Current Shunt 2-6  
B
bridge 1-2, 1-5, 1-6, 2-2, 2-5 – 2-9, 2-11, 2-14, 2-19,  
3-1, 3-2, 3-5 –3-7, 4-3, 4-8, 4-9, 4-16, B-1, B-2  
Bridge and Protection Boards and Modules  
EDEX 2-1, 2-8, 3-1, 3-6 – 3-8, 3-10, 3-11, 4-11  
EGDM 2-1, 2-9, 2-15, 3-1, 3-4, 3-7 – 3-11, 4-14  
EGPA 2-1, 2-5, 2-6, 2-11, 2-14, 3-1, 3-4, 3-5, 3-7, 3-9  
EXAM 2-1, 2-9, 2-15, 3-1, 3-7 – 3-10  
EXCS 3-1, 3-7  
Current transformers 1-7, B-2  
Customer Contact I/O 4-1, 4-4  
D
DACA (see Ac to Dc Converter)  
Data Highway Connections 4-1, 4-19  
dc contactors 1-5  
Dc Field Flashing  
Bridge Rectifier 2-5  
Settings 4-1, 4-16  
de-excitation 1-2, 1-5, 2-5, 2-8, 3-4 – 3-6, 3-8, 3-11,  
4-11, 4-14  
C
Cabinet Dimensions & Weight 1-7, B-3  
De-excitation 2-1, 2-2, 2-7, 2-8, 4-11  
EX2100 User’s Guide GEH-6632  
Index i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
De-Excitation 3-7, 3-11, 4-1, 4-11 – 4-13  
Crowbar 2-2, 3-6, 3-7, 3-10, 3-11, 4-1, 4-14, 4-18  
Field Flashing 2-1, 2-9, 3-2, 4-1, 4-16, 4-17  
Field Ground Detector 2-1, 2-9, 3-7, 4-1, 4-14, 4-15  
Shaft Voltage Suppressor 2-1, 2-9, 4-1, 4-18  
De-excitation module 2-2, 2-8  
Exciter Contact Terminal Board 1-7, 2-15, 3-1, 3-4 –  
3-6, 3-10, 3-11, 4-4, B-2  
Exciter DC Feedback 3-5, 3-6, 3-11, 4-1, 4-8  
Exciter DC Feedback Board 2-6, 2-9, 2-13, 3-1, 3-4 –  
3-6, 3-10, 3-11, 4-8  
Exciter Gate Pulse Amplifier Board 2-1, 2-5, 2-6, 2-11,  
2-14, 3-1, 3-4, 3-5, 3-7, 3-9  
Exciter Internal I/O 4-1, 4-8  
De-excitation Module 2-1, 2-8, 3-1, 3-6 – 3-8, 3-10,  
3-11, 4-11  
Diagnostic Interface 1-1, 2-1, 2-2, 2-10, 5-1  
Alternate Status Screen 5-1, 5-8  
Changing Display 5-1, 5-7  
Exciter AC Feedback 3-5, 3-7, 3-11, 4-1, 4-7, 4-8  
Exciter DC Feedback 3-5, 3-6, 3-11, 4-1, 4-8  
Field Current Feedback 4-9  
Editing Parameters 5-1, 5-10, 5-15  
Faults 5-1, 5-9  
Keypad 2-10, 5-1  
Field Voltage Feedback 4-9  
Exciter ISBus Board 2-11, 3-1, 3-2, 3-4, 3-6, 3-8, 4-8  
Exciter Main I/O Board 2-11, 3-1, 3-2, 3-4 – 3-6, 4-3,  
4-4, 4-16, 4-17  
Protecting the Keypad 5-1, 5-14  
Reading the Display 5-1, 5-5, 5-9  
Reading the Meters 5-1, 5-8  
Exciter Power Backplane 2-14 – 2-16, 3-1, 3-8, 3-9,  
3-11  
Status Screen 5-1, 5-3, 5-5, 5-8  
Using the Menus 5-1, 5-9  
Exciter Power Distribution Module 2-14, 2-16, 3-1, 3-7,  
3-9, 3-11, 4-6  
Using the Pushbuttons 5-1, 5-2  
Exciter Power Supply Module 2-12, 2-14, 3-1, 3-9,  
3-11  
Exciter PT/CT Board 2-13, 2-17, 3-1, 3-4, 3-5, 4-3  
Exciter Selector Board 2-6, 2-11, 2-14, 3-1, 3-2, 3-4,  
3-5, 3-7  
Diagnostic Interface (keypad) 1-1, 2-1, 2-2, 2-10, 3-2,  
3-4, 5-1, 5-2, 5-5, 5-6, 5-8, 5-9, 5-10, 5-13 – 5-15  
Digital Signal Processor Control Board 1-6, 2-11, 3-1,  
3-2, 3-4, 3-8, 4-14, 4-20, 5-13  
Document Distribution 1-1, 1-8  
Exciter Software  
DSPX (see Digital Signal Processor Control Board)  
Dual Control System Configurations 2-4  
Auto Reference 2-1, 2-20  
Automatic Voltage Regulator 2-1, 2-20, 2-21, 3-4, 5-4  
AVR Setpoint 2-1, 2-20  
Field Current Regulator 2-1, 2-21, 3-2  
Field Voltage Regulator 2-1, 2-20, 2-21, 3-2, 5-4, 5-8  
Manual Reference 2-1, 2-21  
Power System Stabilizer 2-1, 2-17, 2-20, 3-4  
Under Excitation Limiter 2-1, 2-20, 3-4, 5-6, B-2  
Exciter Terminal Board 2-7, 2-14, 2-15, 3-1, 3-4 – 3-6,  
3-8 – 3-11, 4-11, 4-16, 4-17  
E
EACF (see Exciter AC Feedback Board)  
EBKP (see Exciter Backplane)  
ECTB (see Exciter Contact Terminal Board)  
EDCF (see Exciter DC Feedback Board)  
EDEX (see De-excitation Module)  
EDEX (see Exciter De-excitation Board)  
EGDM (see Exciter Field Ground Detector Module)  
EGPA (see Exciter Gate Pulse Amplifier Board)  
EISB (see Exciter ISBus Board)  
EMIO (see Exciter Main I/O Board)  
EPBP (see Exciter Power Backplane)  
EPCT (see Exciter PT/CT Board)  
EXCS (see Exciter Conduction Sensor Board)  
EXTB (see Exciter Terminal Board)  
F
FCR (see Field Current Regulator)  
Field Current Feedback 4-9  
EPDM (see Exciter Power Distribution Module)  
EPSM (see Exciter Power Supply Module)  
ESEL (see Exciter Selector Board)  
Field Current Regulator 2-1, 2-21, 3-2  
field flashing 1-5, 2-8, 2-9, 3-4, 3-6, 4-16  
Field flashing module 2-2  
Ethernet 1-2, 2-11, 2-13, 3-4, 3-10, 4-19, 4-20  
EXAM (see Exciter Attenuator Module)  
EXASP (see AVR Setpoint)  
Exciter AC Feedback 3-5, 3-7, 3-11, 4-1, 4-7, 4-8  
Exciter AC Feedback Board 2-9, 3-1, 3-4, 3-5, 3-7, 4-3,  
4-8  
Field Flashing Module 2-1, 2-9  
Field Ground Detector 2-1, 2-9, 3-7, 4-1, 4-14, 4-15  
Field Ground Detector Module 2-1, 2-9, 2-15, 3-1, 3-4,  
3-7 – 3-11, 4-14  
Field Voltage Feedback 4-9  
Field Voltage Regulator 2-1, 2-20, 2-21, 3-2, 5-4, 5-8  
Flashing Control 4-1, 4-16  
Exciter Attenuator Module 2-1, 2-9, 2-15, 3-1, 3-7 –  
3-9, 3-10  
Free Wheeling Diode 2-1, 2-7  
Exciter Backplane 3-1, 3-2, 3-6, 3-11, 4-8  
Exciter Conduction Sensor Board 3-1, 3-7  
Exciter Configurations 2-1, 2-3  
FVR (see Field Voltage Regulator)  
ii Index  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G
O
Gate Pulse Amplifiers 2-1, 2-6  
operator interface 1-2, 2-10  
Generator Current Measurement 4-3  
Generator Voltage Measurement 4-3  
P
PCM (see Power Conversion Module)  
Potential transformers 1-7, B-2  
Power Connections 4-1, 4-2  
H
Hardware  
Overview 1-1, 1-5  
High Voltage Interface 2-1, 2-9  
HMI  
power conversion cabinet 1-5, 2-8  
Power Conversion Cabinet 2-1, 2-5, 4-11  
Free Wheeling Diode 2-1, 2-7  
Mark VI 2-1  
Gate Pulse Amplifiers 2-1, 2-6  
Toolbox 2-1, 4-20  
Main Dc Contactors 2-1, 2-7  
HMI (see Human Machine Interface)  
How to Get Help 1-1, 1-8  
Human Machine Interface 1-2, 2-1, 2-20, 2-21, 3-4,  
4-19  
Manual Ac Disconnect 2-1, 2-5  
Power Converter Module 1-6, 2-1, 2-5  
power conversion module 1-2, 1-6, 1-7, 2-1, 2-2, 2-5,  
3-5, 3-7, 4-14, B-1 – B-3  
Mark VI 2-1  
Toolbox 2-1, 4-20  
Power Conversion Module 1-2, 1-6, 1-7, 2-1, 2-2, 2-5,  
3-5, 3-7, 4-14, B-1, B-2, B-3  
HVI (see High Voltage Interface)  
Power Converter Module 1-6, 2-1, 2-5  
Power potential transformer 1-2, 2-2, 2-5, 2-9, 3-7, 4-3,  
4-14  
Power Potential Transformer 4-1, 4-3  
power source 1-2, 3-7  
I
I/O 1-1, 1-5, 1-6, 2-2, 2-10, 2-11, 3-1, 3-2, 3-4, 3-5, 3-9,  
3-11, 4-1, 4-5, 5-1, 5-8  
Power Supply Boards  
I/O Terminal Boards  
DACA 1-6, 2-14, 3-1, 3-9, 3-11, B-1  
EPBP 2-14 – 2-16, 3-1, 3-8, 3-9, 3-11  
EPDM 2-14, 2-16, 3-1, 3-7, 3-9, 3-11, 4-6  
EPSM 2-12, 2-14, 3-1, 3-9, 3-11  
Power Supply Inputs 4-1, 4-6  
Power System Stabilizer 2-1, 2-17, 3-4  
PPT (see Power potential transformer)  
PPT (see Power Potential Transformer)  
PSS (see Power System Stabilizer)  
EACF 2-9, 3-1, 3-4, 3-5, 3-7, 4-3, 4-8  
ECTB 1-7, 2-15, 3-1, 3-4 – 3-6, 3-10, 3-11, 4-4, B-2  
EDCF 2-6, 2-9, 2-13, 3-1, 3-4 – 3-6, 3-10, 3-11, 4-8  
EPCT 2-13, 2-17, 3-1, 3-4, 3-5, 4-3  
EXTB 2-7, 2-14, 2-15, 3-1, 3-4 – 3-6, 3-8 – 3-11,  
4-11, 4-16, 4-17  
K
Keypad 1-1, 2-10, 5-2, 5-7, 5-14, 5-15  
R
RAM 1-6  
L
Ratings and Specifications 1-1  
Redundant ac source 2-2  
Redundant Control System 2-1, 2-13  
Related Documents 1-1, 1-8  
Leg Reactors 2-5  
Line Filter Connections 4-1, 4-7  
Line-to-line filters 2-2  
M
S
Main Dc Contactors 2-1, 2-7  
Manual Ac Disconnect 2-1, 2-5  
MANUAL REF (see Manual Reference)  
Manual Reference 2-1, 2-21  
Mark VI HMI 2-1  
Microprocessor-based controllers  
ACLA 1-6, 2-11, 2-13, 2-14, 3-1, 3-2, 3-4, 4-19, 4-20  
DSPX 1-6, 2-11, 3-1, 3-2, 3-4, 3-8, 4-14, 4-20, 5-13  
Multibridge configuration 2-2  
SCR 1-2, 1-5, 2-5 – 2-8, 3-2, 3-5 – 3-8, 4-8, 4-9, 4-11  
SCR De-excitation Module 2-8  
shaft voltage suppression 1-5, 2-8  
Shaft voltage suppressor 2-2  
Shaft Voltage Suppressor 2-1, 2-9, 4-1, 4-18  
Simplex Control Configurations 2-3  
Simplex Control System 2-1, 2-12  
Software  
Overview 1-1, 1-6  
Status Screen 5-1, 5-3, 5-5, 5-8  
EX2100 User’s Guide GEH-6632  
Index iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T
Technical Characteristics 1-1, 1-6  
Thyrite 2-8, 4-18  
TMR (see Triple Modular Redundant)  
Toolbox (see Control System Toolbox)  
Triple Modular Redundant 2-2, 2-14  
U
UDH (see Unit Data Highway)  
UEL (see Under Excitation Limiter)  
Under Excitation Limiter 2-1, B-2  
Unit Data Highway 1-2, 4-19  
W
Warm backup bridge configuration 2-2  
Warranty and Renewal Parts 1-1, A-1  
iv Index  
GEH-6632 EX2100 User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*(ꢀ,QGXVWULDOꢀ6\VWHPV  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Euro Pro Lawn Sweeper V1925 User Manual
Extron electronic Switch System 4LQ xi User Manual
Extron electronic TV Converter Box DVI RGB 100 User Manual
Fisher Paykel Ventilation Hood 87641 User Manual
Fitness Quest Exercise Bike 475u User Manual
Frigidaire Washer Dryer 134126300B User Manual
FujiFilm Camcorder 16229490 User Manual
Fujitsu Power Supply FLASH CAN 100 User Manual
FUNAI CRT Television DWT1304 User Manual
Furuno Marine RADAR FAR FR 2815 2825 User Manual