Fujimoto Satellite Radio FKK 4 User Manual

Instruction Manual  
FCX-CII SERIES TRANSMITTERS  
Differentiel pressure Transmitter (FKK ...4)  
Pressure Transmitter (FKP...4)  
Pressure Transmitter with remote seal (FKP...E)  
Absolute Pressure Transmitter (FKH...E)  
Fuji Electric France S.A.  
INF-TN3FCXC2b-E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION ON SAFETY  
First of all, read this “Caution on Safety” to ensure correct operation of the  
transmitter.  
• The cautionary descriptions listed here contain important information about safety, so they should be  
observed without fail. Those safety precautions are classified into ranks “DANGER” and “CAUTION”.  
Wrong handling may cause a dangerous situation, in which there is a  
DANGER  
risk of death or heavy injury.  
Wrong handling may invite a dangerous situation, in which there is a  
possibility of medium-level trouble or slight injury or only physical  
CAUTION  
damage is predictable.  
On items listed under “  
stances, and must be fully observed.  
”, they may also lead to serious accidents depending on circum-  
CAUTION  
• The signs of prohibition and indication are explained in the following.  
General items which pertain to prohibition (DO NOT)  
PROHIBITION  
INDICATION  
General items which pertain to user’s action  
Installation and Piping  
DANGER  
• Non-explosion-proof transmitter must not be used in a place with explosive gases to prevent  
serious accidents such as explosion, fire, etc.  
CAUTION  
• The transmitter is heavy. Be careful when handling it.  
• The transmitter should be installed in a place that meets the operating conditions shown in DS  
sheet or this instruction manual.  
• Install the transmitter according to the instruction manual. Improper installation may lead to the  
cause of fall, trouble or incorrect operation.  
• When installing, make sure that the transmitter interior is free from cable chips and other foreign  
objects to prevent fire, trouble, or incorrect operation.  
• When power is ON, do not change the position of the field indicator in an explosion-proof area.  
• When power is ON, do not change the position of the transmission unit in an explosion-proof area.  
• When power is ON, do not change the angle of the indicator.  
• Main valve used for piping should be selected with the maximum pressure of the process taken  
into account (piping parts such as main valve, etc. should be furnished by user). If the main valve  
and other parts do not meet the rating, it may result in leakage of gas or liquid which could lead to  
hazard.  
• Pressure pipes to be used must meet the temperature/pressure rating.  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
DANGER  
• On explosion-proof type transmitter, its wiring work must be performed according to the required  
laws and regulations. Incorrect wiring may cause explosion, fire or other serious accidents.  
CAUTION  
• Before making wiring work, be sure to turn OFF the main power to prevent electric shocks.  
• Use wiring materials of correct rating to prevent fire accidents.  
• Connect a power source of correct rating to prevent fire accidents.  
• The transmitter should be grounded as specified to prevent electric shocks or incorrect operation.  
• After installing the transmitter, firmly close the covers of the transmission unit and terminal box.  
If not, rain water enter the transmitter which may result in trouble or incorrect operation.  
Adjustment of Smart Type  
DANGER  
• When using a flame-proof transmitter, do not connect HHC to the transmitter terminals and junc-  
tion terminals.  
Replacement of Maintenance Parts  
DANGER  
• When removing an explosion-proof transmitter, turn OFF the main power, then disconnect the  
piping and wiring. Do not remove it when the power is ON to prevent serious accident such as  
explosion, fire, etc.  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION ON USE  
Be sure to observe the following Instructions  
Storage for a long period  
Store the transmitter in a dry room at normal temperature and humidity.  
Keep protection caps in place at the conduit connection and process connection.  
For installation, select an appropriate place  
Site at location with minimal vibration, dust and corrosive gas  
At a place allowing an adequate space for checkup  
Site at location large enough to allow maintenance and checking.  
Mounting angle  
Mount to a pipe horizontally or vertically.  
Attention to overload  
Do not apply a pressure outside the specified range.  
Other  
Besides the above, be sure to observe the cautions given in this manual.  
CONFIRMATION OF YOUR SPECIFICATION  
The instrument nameplate as shown below is attached at the transmission unit of this transmitter. Before  
use, make sure the contents of the nameplate agree exactly with your specifications.  
Tag No.  
Series  
Type  
Range  
M.W.P.  
Ser.No.  
Power Supply  
Output  
...  
4
20mADC  
Mfd.  
Fuji Electric Co., Ltd.  
Made in Japan  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTENTS  
INTRODUCTION ................................................................................................................................. i  
CAUTION ON SAFETY ...................................................................................................................... ii  
CAUTION ON USE ............................................................................................................................. iv  
CONFIRMATION OF YOUR SPECIFICATION .............................................................................. iv  
1
2
3
OUTLINE ....................................................................................................................................... 1  
OPERATING PARTS AND THEIR FUNCTIONS...................................................................... 2  
OPERATION AND SHUTDOWN ................................................................................................ 4  
3.1 Preparation for operation ............................................................................................................. 4  
3.2 Operation ...................................................................................................................................... 6  
3.3 Shutdown...................................................................................................................................... 7  
4
5
ADJUSTMENT OF SMART LINE ............................................................................................... 9  
4.1 Adjustment with HHC ................................................................................................................. 9  
4.2 Zero adjustment by the external screw ..................................................................................... 29  
4.3 Span adjustment by the external screw ..................................................................................... 30  
4.4 Local adjustment unit with LCD display .................................................................................. 31  
MAINTENANCE ......................................................................................................................... 34  
5.1 Periodique inspection ................................................................................................................ 34  
5.2 Troubleshooting ......................................................................................................................... 35  
5.3 Replacement of parts ................................................................................................................. 36  
5.4 Adjustment after replacement unit ............................................................................................ 41  
6
7
INSTALLATION AND PIPING ................................................................................................. 42  
6.1 Installation .................................................................................................................................. 42  
6.2 Piping ......................................................................................................................................... 46  
WIRING ........................................................................................................................................ 54  
7.1 Wiring procedure ....................................................................................................................... 54  
7.2 Power voltage and load resistance ............................................................................................ 53  
7.3 Grounding .................................................................................................................................. 57  
8
SPARE PARTS ............................................................................................................................. 58  
A1 BUILT-IN ARRESTER ............................................................................................................... 61  
A2 CALIBRATION ........................................................................................................................... 63  
A3 PARAMETER SETTING PRIOR TO DELIVERY.................................................................... 65  
A4 HAZARDOUS LOCATION INSTALLATION INFORMATION ............................................ 66  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
OUTLINE  
The FCX-CII series transmitter detects the differential pressure or pressure of various  
fluids, converts it into a current signal of 4 to 20 mA DC and transmits it.  
All the adjustment functions are incorporated in the transmission unit for making  
adjustments easily and exactly.  
Transmitter settings (such as range and damping time constant, etc.) can be changed from  
an HHC (Hand Held Communicator).  
Principle  
The operating principle of the FCX-CII series transmitter is shown in the block  
diagram below.  
The input pressure is changed into an electrostatic capacitance in the detecting unit.  
The change proportional to the pressure undergoes conditioning and amplification in  
the transmission unit, and is then output as a current of 4 to 20mA DC.  
Capacitance  
change  
Displacement  
Diaphragm Sensor  
Input  
differential  
pressure  
Detecting unit  
Operational  
amplification  
circuit  
Output  
current  
Measuring  
circuit  
Transmission unit  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
2
OPERATING PARTS AND THEIR FUNCTIONS  
FCX-CII Series transmitter  
Transmission unit  
Process connection  
Detecting unit  
Analog indicator  
connector  
Transmission unit  
Digital indicator  
connector  
Vent/drain  
plug  
Conduit  
connection  
Zero/span  
adjustment  
screw  
Indicator  
(Digital)  
(Analog)  
Terminal unit  
Terminal unit  
OUT  
DISP  
0
%
FIX  
%
100  
20  
80  
40  
ZERO  
abs  
60  
+
Description of FCX-CII Series transmitter  
Part name  
Description  
Detecting unit  
Detects pressure, differential pressure or level of fluid.  
Converts the detected signal into an output signal.  
Transmission unit  
Vent/drain plug  
Used for gas discharge or draining. (Attention should be paid  
under a high pressure.)  
Process connection  
Conduit connection  
Zero adjustment screw  
Connects impulse pipes from the process.  
Connects the output cable.  
Adjusts zero. (For analog type, refer to Section 7.)  
Transmission unit  
Part name  
Description  
Analog indicator connector  
Digital indicator connector  
Indicator (option)  
Used for connecting an analog indicator.  
Used for connecting a digital indicator.  
Analog or digital indicator, available.  
Terminals  
Symbol  
+, -  
Description  
Connects the output cable.  
CK+, CK-  
Used for checking the output or connecting an indicator.  
An external terminal used for grounding  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mode indicating function of digital indicator  
OUT  
DISP  
FIX  
%
ZERO  
abs  
Mode indication  
Mode  
When indicated  
When not indicated  
%
% output  
External zero adjustment possible  
Actual scale  
ZERO  
External zero adjustment impossible  
Digital indicator proportional display  
Proportional output  
DISP  
OUT  
FIX  
Digital indicator  
output  
display  
Fixed current mode  
Measurement mode  
Sampling status (Flicker)  
abs  
Absolute pressure  
Gage pressure  
Output value < Zero  
Output value Zero  
N
(a part of unit indicator)  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
OPERATION AND SHUTDOWN  
3.1 Preparation for operation  
Before operating the transmitter, be sure to perform the following checks and procedures. Note  
that adjustment is required in a non-hazardous area for zero point check of intrinsically safe  
explosionproof and flameproof transmitters, do not open terminal cover and do not use HHC.  
Use the transmitter indicator and the external adjustment screw.  
Preparation procedure  
(1) Check for liquid or gas leakagefrom the process  
connection, etc. by applying soapy water or the  
like.  
(2) Check the signal wiring according to the “Terminal block connection diagram” shown in 4.1  
(Page 16).  
(3) Vent gas from the transmitter.  
When the plant requires chemical cleaning at the start of operation, be sure to  
close the valve of the transmitter to prevent entry of cleaning liquid into the  
pressure receiving unit.  
Important  
(4) Perform zero point adjustment.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zero point check  
Turn on the power to the transmitter.  
Check the output signal of the transmitter by connecting a DC ammeter across CK+ and CK– of  
the terminal block.  
After ten minutes or longer, adjust the transmitter output current to 4 mA (zero adjustment). (See  
below.)  
(1) Zero adjustment  
Zero point of the transmitter is adjustable by the zero screw on the electronics housing with  
the zero adjustment screw.  
• If the transmitter is locked (see section  
Decrease  
“Operating procedure”, Lock of adjustment  
function), it is not possible to adjust with the  
external adjustment screw.  
Increase  
• When a digital indicator is attached to the  
transmitter, make sure that the LCD lamp  
“ZERO” is ON.  
(2) Adjustment by HHC  
Refer “zero adjustment” explained in section 7.1.  
When all the checks and preparatory operations are finished, tighten the cover securely. (Tighten-  
ing torque 20 N•m {2 kgf•m} <14ft-lb>)  
1. After adjustment of the transmitter, it should be kept energized for about 10  
Important  
seconds to write the adjustment result into memory.  
2. Use a blade-edge screwdriver for adjusting the zero/span adjustment screw.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2 Operation  
(1) Operation of pressure transmitter  
Open the valve slowly to apply a pressure. When a pressure is applied, the transmitter is set  
in the operating status.  
Open  
(2) Operation of differential pressure transmitter  
Set the operating status by manipulating the manifold valve.  
Stop valve  
on the low  
pressure side  
Make sure the equalizing valve is open.  
Open  
Stop valve  
on the high  
pressure side  
Equalizing  
valve  
Open the stop valve on the high pressure side slowly.  
Open  
Close the equalizing valve.  
Close  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Open  
Finally, open the stop valve on the low pressure side  
slowly.  
Check of operating status  
Use a field indicator, receiving instrument or HHC to check the operating status.  
3.3 Shutdown  
(1) Shutdown of pressure transmitter  
Close the valve slowly to stop applying a pressure. The transmitter is set in the measurement  
stop status.  
Close  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
(2) Shutdown of differential pressure transmitter  
Set the shutdown status by manipulating the manifold valve.  
Turn off power supply.  
Close the stop valve on the high pressure side (H side)  
slowly.  
Close  
Open  
Open the equalizing valve.  
Close  
Close the stop valve on the low pressure side (L side)  
slowly.  
Before a long shutdown, discharge the process fluid and drain completely from  
the transmitter.  
Important  
This is to protect the transmitter from freezing, corrosion, etc.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
ADJUSTMENT OF SMART TYPE  
To operate the FCX-CII series transmitter, the HHC is used for each adjustment.  
4.1 Adjustment with HHC  
Startup and usage of the Hand Held Communicator (HHC) are detailed in the instruction manual  
for HHC. Please refer to this manual before commencing adjustment.  
After adjustment of the transmitter, it should be kept energized for about 10 sec-  
onds to write the adjustment results into memory.  
Important  
4.1.1 Connection of HHC  
The HHC can be connected to the transmitter, junction terminal or the terminals in the instrument  
room.  
+
To junction  
terminal or  
instrument  
Field device  
To HHC  
room  
Instrument room  
Junction terminal Zener barrier  
Terminal block  
DC power supply  
DC16.1 ~ 45V  
Load resistor  
In the case of a flameproof transmitter, never connect the HHC to the terminal block  
of the transmitter in hazardous area installations.  
DANGER  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.1.2 Outline of HHC operation  
The following shows the flow of the key, explained for FXW Version 6.0  
(FXW  
1- A3).  
FXW prior to Version 6.0 are not available of operation of FCX-CII series transmitter.  
In this case, the user is requested to contract our office for ROM version up.  
Referential  
page  
Display symbol  
1: TAG No  
Key symbol  
Classification  
TAG No.  
MENU  
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
G
H
I
11  
INC  
INC  
Type  
2: TYPE  
12  
12  
13  
14  
14  
15  
16  
17  
18  
19  
20  
20  
21  
22  
23  
26  
28  
MENU  
INC  
Display of serial No.  
Industrial value unit  
Range limit  
3: SERIAL No.  
MENU  
INC  
INC  
INC  
INC 4: UNIT  
UNIT  
5: RANGE LIMIT  
UNIT  
INC  
INC  
INC  
Range change  
(LRV, URV)  
6: RANGE  
RANG  
DAMP  
Damping adjustment  
Output mode  
INC 7: DAMPING  
LIN  
/
8: OUTPUT MODE  
INC  
LIN  
/
INC  
INC  
Burnout direction  
Zero/span adjustment  
9: BURNOUT  
A: CALIBRATE  
B: OUTPUT ADJ  
C: DATA  
INC  
CALB  
Calibration of  
output circuit  
INC  
INC  
OUT  
Indication of  
measured data  
DATA  
DATA  
INC  
Self-diagnosis  
Printer function  
D: SELF CHECK  
E: PRINT  
INC  
INC  
DATA  
INC  
INC  
Lock of adjustment  
functions  
DATA  
INC  
INC  
INC  
F: XMTR EXT.SW  
G: XMTR DISPLAY  
H: LINEARIZE  
I: RERANGE  
INC  
INC  
Indication of digital  
indicator  
DATA  
INC  
INC  
INC  
INC  
Programmable lineari-  
zation function  
DATA  
INC  
INC  
INC  
INC  
INC  
INC  
INC  
Rerange (Set LRV/URV  
calibration)  
DATA  
INC  
INC  
INC  
INC  
INC  
INC  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.1.3 Operating procedure  
In case of a flameproof transmitter, never connect the HHC to the terminal block of  
transmitter in hazardous area installations.  
TAG N°.  
0:  
PUSH MENU KEY  
To set the TAG N°. of each field de-  
vice, use the procedures shown in  
the following diagram. TAG N°.  
can be inputted up to 26 characters  
of alphanumeric codes.  
• After PUSH MENU KEY is  
displayed, press the <MENU> key  
to display TAG N°.  
• To make changes press the  
<CHNG> key and the cursor will be  
displayed under display 1 .  
• Set the alphanumeric keys as  
necessary under display 2 . To set  
the alphabet, press the <CHNG  
ALHA> key first.  
MENU  
1:  
TAG No  
1-1: TAG CHANGE  
CL  
CL  
CHNG  
FICRA-1234 xxxxxxxxx  
xxxxxxxxxxxxxxxxxxx  
< INC > < CHANGE >  
FICRA-1234 xxxxxxxxx  
xxxxxxxxxxxxxxxxxxx  
< ENT > < CL >  
1
2
3
4
INC  
ENT  
1-1: TAG CHANGE  
To menu  
2 : TYPE  
FICRA-4321 xxxxxxxxx  
xxxxxxxxxxxxxxxxxxx  
CHNG OK?< ENT/CL >  
after setting  
ENT  
1-2: TAG WRITE  
FICRA-4321 xxxxxxxxx  
xxxxxxxxxxxxxxxxxxx  
Using <  
>< > keys, cursor po-  
sition can be moved.  
• At the completion of setting, press  
the <ENT> key and a prompt is  
displayed check entry under display  
2 .  
• If the entry is correct, press the  
<ENT> key to input it to the field  
device under display 3 and 4 and  
the initial image 1 is displayed.  
• To display TYPE display, press the  
<INC> key under display 1 .  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPE  
Menu 1 : TAG N°  
Type of field device is displayed and  
changed (ex. of differential pressure  
transmitter).  
INC  
• After TAG N°. is displayed, press  
the <INC> key to display TYPE  
image.  
• To make changes press the  
<CHNG> key under display 1 and  
the cursor will be displayed under  
display 2 .  
• Set the alphanumeric keys as  
necessary under display 2 . To set  
the alphabet, press the <CHNG  
ALHA> key first. Using < >< >  
keys, cursor position can be moved.  
• At the completion of setting, press  
the <ENT> key and a prompt is  
displayed check entry under  
display 2 .  
2-1: TYPE CHANGE  
FKCXXXXX-XXXXX  
2:  
TYPE  
FKCXXXXX-XXXXX  
CL  
CL  
CHNG  
< ENT > < CL >  
ENT  
< INC > < CHANGE >  
INC  
2
3
4
1
2-1: TYPE CHANGE  
FKCXXXXX-XXXXX  
CHNG OK?< ENT/CL >  
after setting  
ENT  
To Menu  
3 : SERIAL N°  
2-2: TYPE WRITE  
FKCXXXXX-XXXXX  
• If the entry is correct, press the  
<ENT> key to input it to the field  
device under display 3 and 4 and  
the initial image 1 is displayed.  
• To display SERIAL NO., press the  
<INC> key under display 1 .  
Display of SERIAL N°.  
2 : TYPE  
INC  
SERIAL N°. and transmitters  
software version are displayed.  
3:  
SERIAL No.  
N8G07131  
VERSION 1.1  
< INC >  
• After setting TYPE, press the  
<INC> key to display SERIAL  
NO. and software version of  
transmitter.  
INC  
• By pressing the <INC> key,  
UNIT setting image is  
displayed.  
4 : UNIT  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Industrial value unit  
Available unit for FCX-C2  
Menu N°3 :  
SERIAL N°  
mmH2  
cmH  
O
O
2
INC  
mH2  
O
g/cm2  
kg/cm2  
Pa  
4:  
UNIT  
kPa  
< INC > < CHNG >  
INC  
1
hPa  
kPa  
CHNG  
MPa  
mbar  
bar  
4-1: UNIT CHANGE  
kPa  
(NEXT MPa)  
< INC > < ENT > < CL >  
psi  
2
3
4
INC  
< UNIT CHANG >  
ENT  
CL  
inH2  
ftH2  
O
O
mmAq  
cmAq  
mAq  
4-1: UNIT CHANGE  
kPa  
(NEXT MPa)  
CHNG OK? < ENT/CL >  
mmWC  
cmWC  
mWC  
CL  
ENT  
mmHg  
cmHg  
mHg  
inHg  
< Torr >  
< atm >  
4-1: UNIT WRITE  
kPa  
DEC  
INC  
Not suitable unit display  
4-1: UNIT WRITE  
Pa  
To menu N° 5 :  
RANGE LIMIT  
Note: The mark < > is settable for abso-  
lute pressure transmitter only.  
• When pressing <CHNG>  
under display 1 , the display  
for changing the unit of  
industrial value 2 appears.  
• The desired unit of industrial  
value is selectable by using  
<INC> or <DEC> under  
display 2 .  
NOT SUITABLE  
UNIT < CL >  
CL  
• Display 3 is provided for con-  
firming your change.  
• Display 4 is for registering the  
unit of industrial value.  
Important  
The unit of industrial value is set according to the range as ordered, but the display  
resolution lowers depending on the unit being set.  
When  
4-1:UNIT CHANGE  
Pa  
NOT SUITABLE  
UNIT <CL>  
is displayed upon changing the unit of industrial value, output cannot be displayed in the  
engineering unit selected.  
In this case, press the CL key and change the engineering unit to a different one.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Range limit  
Menu N°4 :  
UNIT  
INC  
Indicates the maximum measuring  
range of this transmitter.  
5: RANGE LIMIT  
× × × kPa  
Range change (LRV, URV)  
< INC >  
INC  
LRV: Lower range value (0%  
point)  
CHNG  
CL  
URV: Upper range value (100%  
point)  
6:  
RANGE  
6-1: RANGE CHANGE  
LRV  
URV  
< INC > < CHANGE >  
±
× × × . × kPa  
× × × . × kPa  
LRV  
URV  
< LRV > < URV > < CL >  
±
±
× × × . × kPa  
× × × . × kPa  
±
• When pressing <CHNG> under  
display 1 , display changes to the  
LRV and URV selection screen.  
1
2
INC  
CL  
LRV  
6-2: RANGE CHANGE  
LRV  
URV  
< LRV > < URV > < CL >  
±
±
× × × . × kPa  
× × × . × kPa  
Press <LRV> for presenting the  
display for setting the zero point  
range (display 3 ), or <URV> for  
presenting the display for setting  
the span range (display 4 ).  
3
CL  
URV  
6-2: RANGE CHANGE  
LRV  
URV  
< LRV > < URV > < CL >  
±
±
× × × . × kPa  
× × × . × kPa  
4
• Under displays 3 and 4 , input  
CL  
6-2: RANGE CHANGE  
ENT  
zero point and span values.  
To menu N°7 :  
DAMPING  
LRV  
URV  
CHNG OK? < ENT/CL >  
±
× × × . × kPa  
±× × × . × kPa  
* Press <ENT> after setting LRV  
and URV.  
5
ENT  
6-3: RANGE WRITE  
• When pressing <+/–> under  
display 3 , 4 , negative value is  
available.  
LRV  
URV  
±
±
× × × . × kPa  
× × × . × kPa  
6
Selectable setting range  
Output (mA)  
20  
Reverse  
action  
Normal  
Input  
action  
URV  
Maximum measuring range  
4
URV LRV LRV  
Important  
In case of the actual scale specification with a digital indicator  
provided, if the range is changed, indicator display does not match.  
So, setting is required again in response to the display in the digital  
indicator (G: XMTR DISPLAY). In case of the actual scale  
specification with an analog indicator provided, if the range is  
changed, indicator display does not match. So, replacement of the  
analog indicator is required.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Damping adjustment  
When process input changes exces-  
sively, an appropriate damping time  
constant should be set.  
Menu N°6 :  
RANGE  
CHNG  
7:  
DAMPING  
0.3SEC  
7-1: DAMP CHANGE  
0.3SEC  
Input time constant value under  
display 2 , time constant can be  
changed.  
< INC > < CHANGE >  
INC  
< ENT > < CL >  
CL  
after  
setting  
CL  
2
3
4
1
ENT  
7-1: DAMP CHANGE  
1.2SEC  
CHNG OK? < ENT/CL >  
Selectable time constant value  
No damping ( = measuring period) to  
32 sec  
ENT  
7-2: DAMP WRITE  
1.2SEC  
Note)  
To menu N°8 :  
The above damping constants are  
used only for the electronics unit.  
The detecting unit has its own con-  
stants independent of the  
electronics unit (for details, refer to  
the data sheet).  
OUTPUT MODE  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Output mode  
(a)  
D
LIN/  
(DP)  
The output mode is used to select the  
proportional mode (proportional to in-  
put differential pressure) or square  
root extraction mode (proportinal to  
flow rate) for output signal (4 to 20  
mA). In case of square root extraction  
mode, the cut point and the mode  
below the cut point can be set. Under  
display 2 , press <INC> or <DEC> for  
selection of the square root extraction  
mode or proportional mode.  
GP, AP, LL (Liquid Level)  
8:  
OUTPUT MODE  
XMTR:DP  
OUT=LIN  
8
: OUTPUT MODE  
XMTR:GP  
OUT=LIN  
< INC > < CHANGE >  
< INC > < CHANGE >  
1
CHNG  
CHNG  
INC  
1
INC  
8-1: MODE CHANGE  
XMTR : DP  
8-1: MODE CHANGE  
XMTR : GP  
Menu No.9  
OUT=LIN  
< INC > < ENT > < CL >  
OUT=LIN  
< ENT > < CL >  
2
ENT  
CL  
CL  
*1  
<OUTPUT MODE  
CHANGE>  
In case of OUT=LIN  
In case of OUT= SQR  
8-1: MODE CHANGE  
XMTR:DP  
8-1: MODE CHANGE  
XMTR:DP  
OUT=LIN  
CHNG OK? < ENT/CL >  
OUT=SQR  
CHNG OK? < ENT/CL >  
3
4
5
6
CL  
ENT  
CL  
ENT  
8-2: MODE WRITE  
XMTR:DP  
8-2: MODE WRITE  
XMTR:DP  
Change of output mode  
<INC> <DEC>  
OUT=SQR  
OUT=LIN  
ENT  
a OUT=LIN  
8-3: LOW CUT  
b OUT=SQR  
POINT=××.××%FLOW  
MODE=ꢀꢀꢀꢀꢀꢀ  
< CHANGE > < CL >  
ꢀꢀꢀꢀꢀꢀ = LINEAR or ZERO  
7
CL  
CHNG  
Since display 7 is presented when the  
square root extraction mode is  
selected, the low flow cut point should  
be set.  
(a)  
8-4: POINT CHANGE  
×× ××%FLOW  
.
*2  
< ENT > < CL >  
ENT  
*1 < INC > < DEC > Available Mode  
8
9
CL  
Cut point is adjustable within the range  
of 0.00 to 20.00%. The cut point is  
used for stabilizing output near 0%  
when the square root extraction mode  
is selected for output signal. There are  
two modes; in one mode, proportional  
output is selected for output below a  
cut point (Fig. A) and in the other  
mode, output is forcibly reduced to 0%  
for output below a cut point (Fig. B).  
8-4: POINT CHANGE  
1
2
OUT=LIN  
××.××%FLOW  
OUT=SQR  
CHNG OK? < ENT/CL >  
CL  
Note) GP, AP, LL : OUT = LIN only  
ENT  
*2 0.00% Cut Point 20.00% FLOW  
8-5: POINT WRITE  
×× ××%FLOW  
.
10  
11  
13  
14  
15  
8-6: LOW CUT MODE  
LINEAR  
8-6: LOW CUT MODE  
ZERO  
< CHANGE > < CL >  
< CHANGE > < CL >  
CL  
CHNG  
12  
CL  
CHNG  
8-7: LOW CUT MODE  
< 1 > LINEAR  
Output  
Output  
< 2 > ZERO  
< 1 > < 2 > <CL >  
1
2
CL  
8-7: MODE CHANGE  
LINEAR  
8-7: MODE CHANGE  
ZERO  
CHNG OK? < ENT/CL >  
CHNG OK? < ENT/CL >  
Differential  
input  
Differential  
input  
ENT  
CL  
16  
CL  
ENT  
8-8: MODE WRITE  
LINEAR  
8-8: MODE WRITE  
ZERO  
Fig. B: With zero  
output selected in  
low cut mode  
Fig. A: With linear  
output selected in  
low cut mode  
17  
Under display 13 , linear or zero out-  
put is selectable for output below the  
cut point.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Burnout direction  
Used for selecting output at occur-  
rence of a fault in the detecting unit.  
Burnout direction is selectable un-  
der display 2 .  
CHNG  
9:BURNOUT  
NOT USED  
(HOLD)  
9-1: BURNOUT  
< 1 > NOT USED  
< 2 > OVER SCALE  
< 3 > UNDER SCALE  
< INC > < CHANGE >  
2
• For selection of NOT USED, press  
1
INC  
1
2
3
<1>.  
or  
or  
Selection of  
burnout direction  
• For selection of OVER SCALE,  
press <2>.  
(ex)  
3
• For selection of UNDER SCALE,  
press <3>.  
9-2: BURNOUT  
CHANGE  
UNDER SCALE  
< ENT > < CL >  
The meaning of each condition  
above is as follows.  
A : CALIBRATE  
CL  
3
• NOT USED  
(Output hold)  
Not used  
CL  
ENT  
9-2: BURNOUT  
Saturation current = 3.8, 20.8mA  
Note) Output value just before the occur-  
rence of trouble is given in the out-  
put hold mode.  
CHANGE  
UNDER SCALE  
CHNG OK? < ENT/CL >  
4
ENT  
• OVER SCALE  
Over scale  
CL  
9-5: BURNOUT  
Saturate Current  
3.8-20.8mA  
9-4: BURNOUT  
UNDER SCALE  
Y.YmA  
< CHANGE > < CL >  
(Output 20.8 to 21.6mA)  
Saturation current = 3.8, 20.8mA  
< CL >  
5
6
CL  
CHNG  
• UNDER SCALE  
Under scale  
CL  
(Output 3.2 to 3.8 mA)  
9-5: BURNOUT CHNG  
UNDER SCALE  
Y.YmA  
Saturation current = 3.8, 20.8mA  
Burnout Current of FCX-CII series  
transmitter  
< DEC > <ENT > < CL >  
7
UNDER SCALE (burnout current)  
Y.YmA  
Over scale burnout current = 20.8 to  
21.6mA  
Under scale burnout current=3.2 to  
3.8mA  
3.8mA  
3.7mA  
3.6mA  
CL  
ENT  
9-5: BURNOUT CHNG  
UNDER SCALE  
Y.YmA  
INC  
DEC  
3.5mA  
3.4mA  
3.3mA  
3.2mA  
CHNG OK? < ENT/CL >  
Saturation current=3.8, 20.8mA  
8
ENT  
Change of Over scale current  
21.6mA  
21.5mA  
21.4mA  
21.3mA  
9-7: BURNOUT  
Saturate Current  
3.8-20.8mA  
Upon pressing <DEC> or <INC>  
burnout current can be changed.  
(See above.)  
< CL >  
INC  
DEC  
21.2mA  
21.1mA  
21.0mA  
20.9mA  
20.8mA  
9
CL  
9: BURNOUT  
UNDER SCALE  
Y.YmA  
< INC >  
< CHANGE >  
10  
INC  
CHNG  
A : CALIBRATE  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zero/span adjustment  
LRV  
CL  
< Zero adjustment >  
A-1: CALIBRATE  
A:  
CALIBRATE  
Zero and span are adjustable by apply-  
ing an actual pressure.  
When pressing <LRV> under display 1  
the screen for zero adjustment 2  
appears, and that for span adjustment 5  
appears when pressing <URV>.  
Under display 2 , after applying actual  
pressure equal to zero point, press  
<ENT> two times. Zero adjustment will  
be over.  
LRV ×××  
××× kPa  
< ENT > < CL >  
.××%  
×
.
< INC > < LRV > < URV >  
1
2
INC  
CL  
ENT  
A-1: CALIBRATE  
LRV ×××  
.
.
××%  
kPa  
URV  
×××  
×
CHNG OK? < ENT/CL >  
3
ENT  
A-2: CALIBRATING  
LRV ×××  
××× kPa  
.
××%  
.
×
When adjustment is made at any point  
other than zero, input the pressure value  
at that point at the display of 2 , then  
press the <ENT> key at the display of 3  
while applying a corresponding pres-  
sure to the transmitter.  
4
< Span adjustment >  
A-3: CALIBRATE  
URV ×××  
××× ×  
< ENT > < CL >  
.××%  
.
kPa  
5
CL  
CL  
ENT  
Under display 5 , after applying actual  
pressure equal to desired span, press  
<ENT> two times. Span adjustment  
will be over.  
A-3: CALIBRATE  
URV ×××  
.××%  
×××  
.×  
kPa  
CHNG OK? < ENT/CL >  
6
ENT  
When adjustment is made at any point  
other than span, input the pressure value  
at that point at the display of 5 , then  
press the <ENT> key at the display of 6  
while applying a corresponding pres-  
sure to the transmitter.  
A-4: CALIBRATING  
URV ×××  
××× kPa  
.
××%  
B : OUTPUT ADJ  
.
×
7
Important  
Press LRV or URV at display of 1 .  
When the following is displayed, it means that calibration can not be made because  
Menu No. H: LINEARIZE is effective. In this case, set INVALID on the panel of  
No. H: LINEARIZE.  
A-1:CALIBRATE  
Can’t proceed.  
Set Linearize  
invalid  
<CL>  
1. Span adjustment should be performed after zero adjustment is completed.  
2. When the actual input exceeds the adjustable range, [NOT CALB <CL>] is  
displayed.  
In this case, adjustment is required again.  
Adjustable range  
Zero adjustment: Within ±40% of maximum span  
Span adjustment: Within ±20% of calibrated span  
3. When the adjustment point does not meet the following condition,  
[SETTING ERR<CL>] is displayed. In this case, adjustment is required again.  
Adjustment point setting condition  
–1.000%CS (*) PL 100.000%CS(*) 0.000%CS(*) PH 110.000%CS(*)  
(Lower adjustment point)  
URV LRV  
(Higher adjustment point)  
URV LRV  
-
LRV  
PL =  
PH =  
× 100  
× 100  
-
-
LRV  
-
(*) : CS (Calibrated Span) is equal to measuring range.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Calibration of output circuit (D/A)  
The output circuit (D/A) should be  
calibrated by the following procedure  
when necessary.  
G
OUT  
B:  
OUTPUT ADJ  
< INC > < CHANGE >  
CHNG  
INC  
Make calibration wiring transmitter  
according to "Calibration" in Appen-  
dix A2, and calibrate the output cir-  
cuit with the HHC using the follow-  
ing procedure.  
B-1: OUTPUT SET  
0mA  
< LRV/URV/ENT/CL >  
1
CL  
LRV URV ENT  
(Input of XX.XXXmA at  
)
1
B-1: OUTPUT SET  
4.000mA  
B-1: OUTPUT SET  
20.000mA  
B-1: OUTPUT SET  
XX.XXXmA  
When the <LRV> key is pressed at  
the display of 1 , the display 2 for  
4mA current output and its  
calibration will appear on the screen.  
When the <URV> key is pressed, the  
display 7 for 20mA current output  
and its calibration will appear on the  
screen.  
CHANGE OK? < ENT/CL > CHANGE OK? < ENT/CL > CHANGE OK? < ENT/CL >  
2
7
CL  
8
CL  
ENT  
ENT  
CL  
ENT  
(OTHERS)  
(4 , 20mA)  
< OTHERS >  
B-2: OUTPUT MODE  
XX.XXXmA  
B-2: OUTPUT MODE  
XX.XXXmA  
CURRENT CONST.  
CURRENT CONST.  
< CHANGE > < CL >  
< CALB > < CHNG > < CL >  
3
9
CL  
CL  
CALB  
CHNG  
CHNG  
Under display 1 , input a desired  
value within a range of 3.8 to 20.8mA  
and then press <ENT> two times.  
At this input value, a regulated cur-  
rent output is available.  
B-3: OUTPUT CALIB  
XX.XXXmA CONST.  
0mA (EXT.mA)  
< ENT > < CL >  
4
5
6
CL  
ENT  
Under display 4 , input digital values  
measured by digital voltmeter.  
B-3: OUTPUT CALIB  
XX.XXXmA CONST.  
YY.YYYmA (EXT.mA)  
CHANGE OK? < ENT/CL >  
Under display 4 , the output circuit is  
calibrated when pressing <ENT>.  
CL  
ENT  
B-4: OUTPUT  
Important  
XX.XXXmA CONST.  
YY.YYYmA (EXT.mA)  
CALIBRATING  
After setting and calibrating the con-  
stant current output, be sure to reset  
the HHC display to the initial display.  
Calibration  
impossible  
B:  
OUTPUT ADJ  
B-4: OUTPUT  
10  
appears when the  
adjustable range is  
exceeded.  
XX.XXXmA CONST.  
YY.YYYmA (EXT.mA)  
NOT CAL1B. < CL >  
<INC> <CHANGE>  
10  
CL  
In this way, the transmitter output is  
reset to the measurement output. It  
should be noted that if HHC is  
removed from the transmitter loop or  
the HHC power is turned OFF when  
the constant current output has been  
set, the transmitter output is retained  
at the constant current output.  
C:  
DATA  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indication of measured data  
B
DATA  
The measured value can be indi-  
cated.  
For more information about  
operating procedure, refer to the in-  
struction manual of HHC.  
C:  
DATA  
C-1: DATA  
XXX. X %FLOW  
XXXXX kPa  
< CHANGE > < CL >  
< INC > < ENT >  
ENT  
CHNG  
CL  
INC  
:
"FLOW" is displayed  
C-1: DATA  
when output mode is  
square root extraction  
mode.  
XXX. XX %FLOW  
XXXXX kPa  
< CHANGE > < CL >  
CHNG  
CL  
:
"
flicker" is displayed  
when the communica-  
tion between transmitter  
and HHC is normal.  
(HHC is not used for 10 minutes)  
STANDBY  
PUSH CL KEY  
Self-diagnosis  
CL  
Use for displaying the measured  
temperature in the transmitter and  
the alarm information.  
ENT  
D:  
SELF CHECK  
D-1: SELF CHECK  
< 1 > AMP TEMP  
< 2 > ALM CHECK  
< 1 > < 2 > <CL >  
< INC > < ENT >  
When pressing <1> on display 2 ,  
the temperature in the amplifier  
(AMP TEMP) is displayed. When  
pressing <2>, result of self-  
diagnosis about transmitter (ALM  
CHECK) is displayed.  
1
2
INC  
1
2
CL  
D-2: SELF CHECK  
TEMP=XXX.X °C  
(YYY.Y °F)  
< CL > <INC>  
3
CL  
D-2: SELF CHECK  
ALM CHECK  
GOOD  
Result of diagnosis  
< CL >  
When the temperature in the ampli-  
fier is normal:  
4
CL  
(Temperature alarm is displayed)  
D-2: SELF CHECK  
D-2: SELF CHECK  
TEMP=XXX.X °C  
TEMP.ALARM  
TEMP= ×××.×ûC  
<CL>  
5
INC  
Temperature is displayed in °C and °F  
When temperature alarm is detected:  
alternately at each press of the <INC> key.  
D-2: SELF CHECK  
TEMP= ×××.×ûC  
TEMP. ALARM  
<CL>  
(Trouble in transmitter)  
D-2: SELF CHECK  
CELL FAULT (C1)  
E:  
PRINT  
When no error has occurred:  
< CL > < INC >  
6
CL  
D-2: SELFCHECK  
ALM CHECK  
GOOD  
<CL>  
When an error has occurred:  
D-2: SELF CHECK  
CELL FAULT (C1)  
<CL> <INC>  
For contents of error, refer to "Con-  
tents of message" on the next page.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
[Contents of message]  
As a result of self-diagnosis, the message below is appeared on the LCD display of HHC,  
when there are trouble in the transmitter. For each error, its cause and remedy are suggested.  
Indication on  
digital indicator  
Message  
Cause  
Remedy  
CELL FAULT (C1)  
FL-1  
Error of detecting unit  
Replacement of detecting unit  
CELL FAULT (C9)(*1)  
EEPROM (AMP) FLT  
EEPROM (CELL) FLT  
TEMP. ALARM  
FL-2  
FL-3  
EEPROM error on amplifier side Replacement of amplifier  
EEPROM error on cell side  
Replacement of detecting unit  
T.ALM  
Transmitter temperature is not  
within the allowable range (–45  
to 90°C).  
Transmitter temperature is  
normalized.  
(*2)  
ZERO  
XMTR FAULT  
FL-1  
Amplifier error  
Replacement of amplifier  
Properly controlled.  
OVER  
Input pressure is 105% or higher  
of setting range.  
(*2)  
ZERO  
Under  
Input pressure is –1.25% or  
lower of setting range.  
(*2)  
Properly controlled.  
ZERO  
(*1) CELL FALUT (C5) to (C9) are appeared in case of “9” in 6th digit code of FKC.  
(*2) Real indication  
With Printer Unit  
E:  
PRINT  
Printer function  
< INC > < ENT >  
ENT  
INC  
Set Year/Month/Date  
Time (Hour, Minute)  
Usable only when a printer is con-  
E-1: PRINT  
DATE YY : MM : DD  
TIME HH : MM  
< ENT > < CL >  
nected.  
Refer to the instruction manual of  
HHC.  
CL  
(Indicated when the printer unit is active)  
E-2: PRINT OUT  
ENT  
E-3: PRINT OUT  
PRINT OUT END  
< INC >PAPER FEED  
< CL >  
INC  
CL  
Paper Feed (Printer)  
Without Printer Unit  
PRINT  
NO CONNECTION  
E:  
< INC >  
INC  
F : XMTR EXT.SW  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lock of adjustment function  
CHNG  
The zero adjustment function can be  
locked by the transmitter adjust  
screw.  
F:  
XMTR EXT. SW  
F-1: XMTR EXT. SW  
< 1 > INHIBIT  
< 2 > ENABLE  
ENABLE  
< INC > < CHANGE >  
< 1 > < 2 > < CL >  
2
3
4
5
CL  
1
INC  
CL  
1
When pressing <1> (INHIBIT) un-  
der display 2 , the external switch  
lock function is activated, and it is  
released when pressing <2> (EN-  
ABLE).  
F-2: XMTR EXT. SW  
CHANGE  
INHIBIT  
< ENT > < CL >  
ENT  
F-2: XMTR EXT. SW  
CHANGE  
INHIBIT  
CHNG OK? < ENT/CL >  
CL  
ENT  
F-3: XMTR EXT. SW  
WRITE  
INHIBIT  
F : XMTR DISPLAY  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indication of digital indicator  
For digital indicator, either % dis-  
play or actual-scale display is se-  
lectable. In display on the actual  
scale, display values corresponding  
to 0% (4mA) and 100% (20mA) are  
settable.  
1
2
±
±
YYYYYY=XMTR DISPLAY  
at 4mA  
ZZZZZZ=XMTR DISPLAY  
at 20mA  
G : XMTR DISPLAY  
% DISPLAY  
X.XX-XXX.XX%YYYY  
< INC > < CHANGE >  
G
: XMTR DISPLAY  
±YYYYYY/±ZZZZZZ  
UUUUUUU  
or  
Note 1  
< INC > < CHANGE >  
UUUUUUU=XTMR DISPLAY  
UNIT  
CHNG  
CHNG  
INC  
Note1) 0.00-100.00%LIN  
0.0-100.0% LIN  
INC  
3
G-1: DISP. CHANGE  
< 1 > % DISPLAY  
< 2 >ACTUAL DISP.  
< 1 > < 2 > < CL >  
0-100%  
LIN  
0.00-100.00%FLOW  
0.0-100.0% FLOW  
H : LINEARISE  
0-100%  
FLOW  
1
2
CL  
2
In setting % display, proportional  
mode and square root extraction  
mode is selectable as shown in 4 .  
In 4 ,  
or  
1
4
A
G-2: DISP. CHANGE  
< 1 > % LIN  
< 2 > % FLOW  
< 1 > < 2 > < CL >  
<1> %LIN is displayed in % in the  
proportional mode  
<2> %FLOW is set by % in the  
square root extraction mode  
(proportional to flow)  
In case of pressure transmitter,  
absolute pressure transmitter and  
level transmitter, <2> % FLOW  
cannot be set in 4 .  
CL  
1
2
<2> % FLOW  
DP  
GP, AP, LL  
(liquid Level)  
<1> % LIN  
5
8
G-3: DISP. CHANGE  
< 1 > 0.00-100.00%  
< 2 > 0.0-100.0%  
G-3: DISP. CHANGE  
< 1 > 0.00-100.00%  
< 2 > 0.0-100.0%  
G-3: DISP. CHANGE  
Can't proceed.  
XMTR doesn't  
1
2
3
1
2
3
< 3 > 0-100% < CL >  
< 3 > 0-100% < CL >  
support.  
< CL >  
CL  
CL  
CL  
4
4
4
4
4
6
7
9
G-4: DISP. CHANGE  
X.XX-XXX.XX%LIN  
G-4: DISP. CHANGE  
X.XX-XXX.XX%FLOW  
0.00-100.00%  
or 0.0-100.0%  
or 0-100%  
CHNG OK?<ENT/CL>  
CHNG OK?<ENT/CL>  
CL  
CL  
ENT  
ENT  
10  
G-4: DISP. WRITE  
X.XX-XXX.XX%LIN  
G-4: DISP. WRITE  
X.XX-XXX.XX%FLOW  
1
B
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
When setting the actual-scale display,  
first select <2> ACTUAL DISP in 3 .  
Next, after setting the actual-scale  
display value ( 11 to 14 ), perform the  
actual-scale display unit setting  
( 16 to 19 ).  
In case of pressure transmitter,  
absolute pressure transmitter and  
level transmitter, the flow units can-  
not be set as shown in 17 .  
11  
12  
G-2 : DISP. CHANGE  
LRV: 4mA=  
URV: 20mA=  
< LRV >< URV ><CL>  
LRV URV CL  
±
YYYYYY  
Already set value  
of transmitter  
±
ZZZZZZ  
3
13  
G-2 : DISP. CHANGE  
LRV: 4mA= YYYYYY  
URV: 20mA= ZZZZZZ  
< ENT >< URV ><CL>  
G-2 : DISP. CHANGE  
LRV: 4mA= YYYYYY  
URV: 20mA= ZZZZZZ  
< ENT >< URV ><CL>  
±
±
±
±
ENT  
URV  
CL  
13  
ENT URV  
CL  
12  
11  
15  
11  
14  
16  
After making sure of the setting of the  
actual scale display 20 , enter the  
[ENT] and then data is written in the  
transmitter.  
G-2 : DISP. CHANGE  
LRV: 4mA= YYYYYY  
URV: 20mA= ZZZZZZ  
SET OK?< ENT ><CL>  
ENT CL  
G-2 : DISP. CHANGE  
LRV: 4mA= YYYYYY  
URV: 20mA= ZZZZZZ  
±
±
±
±
SETTING ERR <CL>  
CL  
11  
11  
G-3 : DISP. CHANGE  
DispUNIT=UUUUUUU  
Already set value of transmitter  
= PRESS./LEVEL/FLOW  
(
<CHNG><ENT><CL>  
)
CHNG  
ENT  
CL  
19  
40  
GP, AP, LL  
(liquid Level)  
11  
17  
G-2: DISP. CHANGE  
Can’t proceed.  
XMTR doesn't  
G-4 : DISP. CHANGE  
<1>PRESS.<3>FLOW  
<2>LEVEL  
support.  
< CL >  
<1><2><3><CL>  
CL  
CL  
1
2
3
17  
16  
18  
<3>FLOW  
DP  
40  
<1>PRESS  
<2>LEVEL  
18  
18  
17  
G-5 : DISP. CHANGE  
DispUNIT=UUUUUUU  
(NEXT XXXXXXX)  
<INC><ENT><CL>  
G-5 : DISP. CHANGE  
DispUNIT=UUUUUUU  
(NEXT XXXXXXX)  
<INC><ENT><CL>  
G-5 : DISP. CHANGE  
DispUNIT=UUUUUUU  
(NEXT XXXXXXX)  
<INC><ENT><CL>  
INC  
ENT CL  
INC  
ENT CL  
INC  
ENT CL  
17  
17  
(b)  
(c)  
(a)  
19  
19  
G-5 : DISP. CHANGE  
DispUNIT=UUUUUUU  
G-5 : DISP. CHANGE  
DispUNIT=UUUUUUU  
<DISP. UNIT CHANGE>  
(a) (b) (c)  
mmH2O mm Nm3/s  
cmH2  
cm Nm3/min  
mH2  
SET OK?<ENT><CL>  
ENT CL  
SET OK?<ENT><CL>  
ENT CL  
O
O
g/cm2 in  
kg/cm2 ft  
Pa  
m
Nm3/h  
Nm3/d  
m3/s  
m3/min  
m3/h  
m3/d  
t/s  
17  
11  
17  
11  
20  
G-6 : DISP. CHANGE  
YYYYYY/ ZZZZZZ  
UUUUUUU  
20  
G-6 : DISP. CHANGE  
YYYYYY/ ZZZZZZ  
UUUUUUU  
±
±
±
±
hPa  
kPa  
MPa  
CHNG OK?<ENT/CL>  
CHNG OK?<ENT/CL>  
ENT CL  
ENT CL  
mbar  
bar  
psi  
t/min  
t/h  
t/d  
21  
G-7 : DISP. CHANGE  
YYYYYY/ ZZZZZZ  
UUUUUUU  
21  
G-7 : DISP. CHANGE  
YYYYYY/ ZZZZZZ  
UUUUUUU  
NC DEC  
inH2O  
l/s  
±
±
±
±
ftH2  
O
l/min  
l/h  
l/d  
mmAq  
cmAq  
mAq  
mmWC  
cmWC  
mWC  
mmHg  
cmHg  
mHg  
gal/s  
gal/min  
gal/h  
gal/d  
ft3/s  
ft3/min  
ft3/h  
ft3/d  
bbl/s  
bbl/min  
bbl/h  
bbl/d  
2
(UNIT=PRESS. LEVEL)  
B
(UNIT=FLOW)  
inHg  
(Torr)  
(atm)  
( ) is available  
for GP and AP.  
(C) is available for DP.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When setting of % Flow in %display or  
Flow unit in actual scale display, low  
flow cut point and low flow cut mode  
are displayed ( 22 or 23 ).  
When, in the OUTPUT MODE (Menu  
No. 8), OUT = SQR is set, already set  
low flow cut point and low flow cut  
mode are displayed ( 23 ).  
With OUT = LIN set, the present low  
flow cut point and low flow cut mode  
are displayed ( 22 ). Then, enter  
<CHANGE>, and the setting can be re-  
newed.  
B
OUT=SQR at Menu No.8  
OUT=LIN at  
Menu No.8  
22  
23  
G-8 : LOW CUT  
G-8 : LOW CUT  
POINT=XX.XX%FLOW  
MODE=YYYYYY  
<CHANGE><CL>  
POINT=XX.XX%FLOW  
MODE=YYYYYY  
<CL>  
CL  
CL  
CHNG  
or  
2
or  
2
1
1
24  
Note2) CUT POINT  
and  
CUT MODE  
are set at Menu No.8  
YYYYYY=LINEAR or ZERO  
G-9 : POINT CHANGE  
XX.XX%FLOW  
<ENT><CL>  
CL  
ENT  
22  
25  
26  
27  
G-9 : POINT CHANGE  
XX.XX%FLOW  
CHNG OK?<ENT/CL>  
CL  
ENT  
24  
G-A : POINT WRITE  
XX.XX%FLOW  
27  
G-B : LOW CUT MODE  
LINEAR  
G-B : LOW CUT MODE  
ZERO  
<CHANGE><CL>  
<CHANGE><CL>  
CL  
CL  
CHNG  
CHNG  
or  
2
or 2  
1
1
28  
G-C : MODE CHANGE  
<1>LINEAR  
<2>ZERO  
<1><2><CL>  
CL  
1
2
27  
29  
29  
G-D : MODE CHANGE  
LINEAR  
G-B : MODE CHANGE  
ZERO  
CHNG OK?<ENT/CL>  
CHNG OK?<ENT/CL>  
ENT  
ENT  
CL  
CL  
28  
28  
30  
30  
G-D : MODE WRITE  
LINEAR  
G-B : MODE WRITE  
ZERO  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programmable linearization function  
User can set output compensation  
against the input using 14  
compensation points, (X1, Y1), (X2,  
Y2)…(X14, Y14). Each compensation  
value between (Xn, Yn) and (Xn+1,  
Yn+1) is connected by first order  
approximate formula.  
This linearization function is useful to  
compensate the tank figure in level  
measurement application and the flow  
rate of steam or gas in flow measure-  
ment application .  
H:  
LINEARIZE  
INVALID  
< INC > < CHNG >  
CHNG  
1
INC  
CL  
CHNG  
CL  
H-1:  
LINEARIZE  
H-2:  
< 1 > INVALID  
< 2 > EFFECTIVE  
< 1 > < 2 > < CL >  
LINEARIZE  
INVALID  
< INC > < CHNG > < CL >  
INC  
2
19  
2
CL  
CL  
H-2: LINEARIZE  
H-3: LINEARIZE  
CHANGE  
EFFECTIVE  
POINT 0  
< INC > < CHNG > < CL >  
CHNG OK? < ENT/CL >  
Functions for LINEARIZE are  
available for FXW Version 6.0 and  
upward.  
3
20  
ENT  
CHNG  
H-3: LINEARIZE  
CHANGE  
POINT 0  
For DP  
H-3: LINEARIZE  
Set Output Mode  
< ENT > < CL >  
By pressing INC at display of 2 , the  
display is shifted to the setting of LIN-  
EARIZE POINT 3 . Press CHNG at  
display of 3 and input POINT XX to  
be compensated. Then press ENT and  
the display will be shifted to 5 .  
Press INC at display of 5 and the dis-  
play will be shifted to y for selection of  
<1> Lin. point: LP and <2> Comp.  
value : CV.  
LIN-LIN or SQR-SQR  
< CL >  
4
CL  
Input the value of  
point and press  
ENT (POINT XX)  
21  
CL  
CHNG  
ENT  
INC  
H-2: LINEARIZE  
In the case  
where POINT  
XX has been  
set  
POINT XX  
< INC > < CHNG > < CL >  
5
CL  
INC  
H-3: LINEARIZE  
< 1 >Lin. point:LP  
< 2 >Comp value:CV  
< 1 > < 2 > < CL >  
CL  
6
CL  
Select <1> Lin. point: LP at display of  
6 and input XXX.XX% to each point  
(LP1-LP ).  
2
1
H-4: LINEARIZE  
H-4: LINEARIZE  
LP1 XXX.XX%  
< INC > < CNG/ENT/CL >  
LP3 XXX.XX%  
< INC > < CNG/ENT/CL >  
At the completion of input to all the  
compensated points, press ENT twice  
and the write of LP will be finished.  
At this time, the display is shifted to 6 .  
Select <2> Comp. point: CV at display  
of 6 and input XXX. XX% to each  
point (CV1-CV ) in the same manner  
as noted in <1> LP. At the completion  
of input to all the compensated points,  
press ENT twice and the write of CV  
will be finished.  
7
9
CL  
INC  
Next  
parameter  
INC  
CL  
15  
16  
15  
16  
H-4: LINEARIZE  
H-4: LINEARIZE  
LP2 XXX.XX%  
< INC > < CNG/ENT/CL >  
LP14 XXX.XX%  
< INC > < CNG/ENT/CL >  
CL  
8
10  
INC  
INC  
CL  
for display  
for display  
15 16  
7
15  
16  
for display  
11  
I : Rerange  
At the completion of write of compen-  
sated program for LP/CV, press CL  
twice at the display of 6 for shifting to  
2 . Then, press CHNG for selection of  
<1> INVALID and <2> EFFECTIVE  
of 19 . At display of 19 , press <2>  
and the display will be changed to  
Important  
Note) In the key stroke for Linearization, please set  
each parameter in the below sequence.  
1. Set the number of compensation points in the  
range of 2 to 14.  
2. Set each linearization option point (LP*) correctly,  
and write them.  
EFFECTIVE.  
LP1  
LP2  
3. Set each compensation value (CV*) correctly, and  
write them.  
Change of compensated  
point for LP  
LP3  
INC  
DEC  
4. Set linearization option into EFFECTIVE and  
write.  
LP14  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
Change of compensated  
point for CV  
CL  
2
CV1  
CV2  
H-4: LINEARIZE  
H-4: LINEARIZE  
CV3  
CV1 XXX.XX%  
< INC> < CNG/ENT/CL >  
CV3 XXX.XX%  
< INC> < CNG/ENT/CL >  
INC  
DEC  
13  
11 CL  
INC  
Next  
parameter  
CV14  
INC  
17  
17  
18  
18  
H-4: LINEARIZE  
H-4: LINEARIZE  
Important  
CL  
CV2 XXX.XX%  
< INC> < CNG/ENT/CL >  
CV14 XXX.XX%  
< INC> < CNG/ENT/CL >  
When INC is pressed at display of 3 ,  
the following is displayed,  
8
14  
CL  
INC  
INC  
for display  
11 17 18  
for display  
17 18  
H-2: LINEARIZE  
POINT  
0
SETTING ERR <CL>  
or  
H-5: LINEARIZE  
CHANGE  
H-5: LINEARIZE  
CHANGE  
LP1-14  
When ENT is pressed at display of 4 ,  
the following is displayed,  
LPM XXX.XX%  
< ENT > <CL >  
CHNG OK? < ENT/CL >  
CL  
15  
16  
H-3: LINEARIZE  
POINT 15  
ENT  
ENT  
POINT SET  
SETTING ERR <CL>  
for display  
8
for display 7 , 8 , 9 , 10  
CL  
for display 7 , 8 , 9 , 10  
POINT=2 (number of correction) 14  
setting err=00 or 01 or 15  
H-5: LINEARIZE  
CHANGE  
H-5: LINEARIZE  
CHANGE  
CV1-14  
When ENT is pressed at display of 15 ,  
the following is displayed,  
CVM XXX.XX%  
< ENT > <CL >  
CHNG OK? < ENT/CL >  
H-5: LINEARIZE  
CHANGE  
17  
18  
CL  
ENT  
ENT  
LPM  
150.01%  
SETTING ERR <CL>  
for display 11, 12 , 13, 14  
for display  
8
CL  
Requirement of setting  
-1.25% LP1 < LP2… <  
LP14 +110%  
for display 11, 12 , 13, 14  
When ENT is pressed at display of 17 ,  
Important  
When ENT is pressed at display  
the following is displayed,  
H-5: LINEARIZE  
CHANGE  
of 20 , the following is displayed,  
CVM  
100.01%  
H-3: LINEARIZE  
Set LINEARIZE  
Point, LP and CV  
SETTING ERR <CL>  
Requirement of setting  
-100% CV1 < CV2… <  
CV14 +100%  
correctly.  
<CL>  
Requirement of setting  
1. LP LP2 LP3…LP8 LP9…LP13 LP14 (In the  
case that LP1-LP14=All Zero, it is inhibited to be  
set enable)  
Before performing the LINEARIZE  
setting, set either of the following  
equations in the OUTPUT mode  
(Menu No. 8) and XMTR DISPLAY  
(Menu No. G):  
OUT = LIN SMTR DISP = LIN or  
OUT =SQR XMTR DISP = FLOW  
(Note 1)  
2. If CVaπCVb, then it must be LPa < LPb. (Note1)  
3. If LPa =LPb, then it must be CVa= CVb. (Note 1)  
Note 1) a, b show next numeral such as a=1 b=2  
or a=2 b=3 or ………a=13 b=14.  
or  
Note 1) XMTR DISP = FLOW means the  
settings of % FLOW in %display  
or of FLOW units in actual-scale  
display.  
the following is displayed.  
H-3: LINEARIZE  
Set OUTPUT MODE  
LIN-LIN or  
SQR-SQR <CL>  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Rerange (Set LRV/URV calibration)  
I:  
RERANGE  
< INC > < CHNG >  
CHNG  
RERANGE  
(application to level measurement) at  
change of level (LRV/URV)  
1
I-1:  
INC  
Functions of RERANGE can be made  
with FXW Version 6.0 or upward.  
< LRV >< URV > < CL >  
CL  
CL  
URV  
2
CL  
LRV  
When the lower range value (LRV) and  
uppeer range value (URV) need to be  
adjusted again during measurement of  
tank level, the measurement levels can  
be changed at the same time by setting  
the LRV or URV to be adjusted from  
FXW.  
I-2: RERANGE  
I-2: RERANGE  
LRV 0.00%  
< ENT > < CL >  
URV 100.00%  
< ENT > < CL >  
3
CL  
CL  
6
ENT  
ENT  
I-3: RERANGE  
CHANGE  
I-3: RERANGE  
CHANGE  
URV %  
CHNG OK? < ENT/CL >  
LRV  
.
CHNG OK? < ENT/CL >  
%
4
7
ENT  
ENT  
I-5: RERANGE  
I-5: RERANGE  
±
LRV  
URV  
kPa  
kPa  
LRV  
LRV  
±
±
kPa  
kPa  
±
Apply an input pressure required for  
rerange of LRV at display of 3 and  
press ENT twice.  
< CL >  
< CL >  
5
8
CL  
CL  
1: TAG N°  
In this way, the rerange of LRV is com-  
pleted, then the new measurement  
range LRV and URV, which conforms  
to the actual input pressure, is dis-  
played.  
Important  
When rerange is made at a point other  
than 0%, input the set value (PV%) of  
that point at display of 3 , and press  
ENT at display of 4 while applying a  
corresponding pressure. In this way,  
the measurement range can be changed  
to the input corresponding to that pres-  
sure.  
Adjustment point setting condition  
-1.00% LRV 100.00% 0.00% URV 110.00%  
In the case that point is out of setting limit.  
(Ex)  
1-2: RERANGE  
LRV  
100.01%  
SETTING ERR <CL>  
In case of the actual scale specification with a digital  
indicator provided, if the range is changed, indicator  
display might not match. So, setting is required again  
in response to the display in the digital indicator  
(G:XMTR DISPLAY).  
In case of the actual scale specification with an analog  
indicator provided, if the range is changed, the scale  
for indicator might not ensure exact reading.  
Apply an input pressure required for  
rerange of URV at display of 6 and  
press ENT twice. The rerange of URV  
is completed, then the new  
measurement range LRV and URV  
corresponding to the actual input pres-  
sure is displayed. When rerange is  
made at a point other than 100%, input  
the set value (PV%) of that point at dis-  
play of 6 and press ENT at display of  
7 while applying a corresponding pres-  
sure. In this way, the measurement  
range can be changed to the input cor-  
responding to that pressure.  
When CHNG is pressed at display of 1, the following  
is displayed.  
1-1: RERANGE  
Can’t proceed.  
Set Linearize  
invalid.  
<CL>  
This means that RERANGE cannot be made because  
MENU No. H: LINEARIZE is set in EFFECTIVE.  
In this case, press the CL key and set in INVALID on  
the panel of No. H: LINEARIZE.  
Note)The unit of LRV/URV at 5 and 8 are  
displayed in theunit selected by Menu No.  
4:UNIT.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2 Zero Adjustment by the external screw  
Zero point of the transmitter is adjustable by the outside screw with the mode setting switch in  
the housing set at zero position. The figure shown below is an example of “Mode setting  
switch” is attached.  
(1) Set the mode setting switch to zero position.  
Mode setting switch  
Set switch to “zero”  
for zero calibration  
(2) Apply standard input pressure corresponding to new Lower Range Value  
(3) Adjust output to 4mA by turning the outside screw  
Decrease  
Increase  
For zero suppression or elevation, apply the  
specified input pressure in advance and adjust the  
output to 4mA using the outside screw.  
Note 1) If the transmitter is locked, it cannot be adjusted by the external adjustment screw.  
Note 2) When a digital indicator is attached to the transmitter, make sure that the LCD lamp  
“ZERO” is ON.  
After adjustment, the transmitter should be kept energized at about 10 seconds to  
write the adjustment results into memory.  
Important  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3 Span adjustment by the external screw  
The measuring range for each transmitter is determinated according to its type.  
Span is changed by the outside screw with the mode setting switch in the housing set at span  
position. The figure shown below is an example of “Mode setting switch” is attached.  
(1) Set the mode setting switch to span position.  
Mode setting switch  
Set switch to “zero”  
for zero calibration  
(2) Apply standard input pressure corresponding to new Upper Range Value.  
(3) Adjust output to 20mA by turning the outside screw  
Decrease  
Increase  
(4) Then return to applying input pressure of zero again and make sure output is 4mA.  
Note 1) If the transmitter is locked, it cannot be adjusted by the external adjustment screw.  
Note 2) When a digital indicator is attached to the transmitter, make sure that the LCD lamp “ZERO” is  
ON.  
After adjustment, the transmitter should be kept energized at about 10 seconds to  
write the adjustment results into memory.  
Important  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4 Local adjustment unit with LCD display  
1. Outline  
When local adjustment unit with LCD display (Parts number is *ZZPFCX4-A055) is installed in the  
FCX-CII transmitter, some functions are available without HHC (Hand Held Communicator).  
Name of each part in local adjustment unit with LCD display and their functions are indicated  
below.  
Mode setting  
Damping setting  
switch  
switch  
LOCAL/COMM.  
changing switch  
LCD display  
Table 1.Functions of Mode setting switch  
Positions of  
switch  
Functions of external  
adjustment screw  
Output  
Difference pressure & Flow transmitter  
Pressure and Absolute pressure  
transmitter (Model:FKG,FKA)  
(Model:FKC)  
0
1
2
3
4
5
6
7
Zero adjustment  
Span adjustment  
Locking of function  
Adj. fixed current  
Adj. fixed current  
Adj. fixed current  
Span adjustment  
Locking of function  
Proportional to differential pressure  
Proportional to differential pressure  
Proportional to differential pressure  
4mA fixed current  
Proportional to pressure  
Proportional to pressure  
Proportional to pressure  
4mA fixed current  
12mA fixed current  
12mA fixed current  
20mA fixed current  
20mA fixed current  
Proportional to flow  
Proportional to pressure  
Proportional to pressure  
Proportional to flow  
Table 2.Functions of Damping setting switch  
Positions of  
Time constant (sec.)  
switch  
0
1
2
3
4
5
6
7
0
0,3  
0,6  
1,2  
2,4  
4,8  
9,6  
19,2  
Table 3. LOCAL/COMM. Changing switch  
Positions of switch  
Adjustment methods  
Adjustments of transmitter are carried  
out by Mode setting switch and Damping  
setting switch.  
LOCAL  
Adjustments of transmitter are carried  
out by HHC.  
COMM.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.Selection of transmitter adjustment method  
LOCAL/COMM. Changing switch decides the method of FCX-CII transmitter adjustment. If switch  
is set to “COMM.” side, adjustment of transmitter is carried out by HHC. This method is explained  
in instruction manual.  
If switch is set to “LOCAL” side, adjustment of transmitter is carried out by Mode setting switch  
and Damping setting switch.  
This method is explain below.  
3.Range change procedure  
For changing the measuring range, carry out zero adjustment first, and span adjustment next. (If  
zero adjustment is performed after span adjustment, the 100% point may not be adjusted correctly.).  
There is no interference between zero adjustment and span adjustment.  
3.1 Zero adjustment(Change Lower Range Value)  
Zero point of the transmitter is adjustable by the external adj. screw with the mode setting  
switch set at “0” position.  
(1) Check if “ZERO” is lit on the LCD indicator.  
If not lit, set the mode setting switch to “0” position.  
(2) Apply standard input pressure corresponding to new Lower Range Value  
(3) Adjust output signal to 4.00mA by turning the external adj. screw  
Decrease  
Increase  
For zero suppression or elevation ranges, apply the specified LRV pressure in advance and adjust  
the output signal to 4.00mA using the external adj. screw.  
Output  
signal  
Max zero elevation with :  
max span  
min span  
Max Zero suppression with :  
min span  
max span  
100% (20mA)  
Input signal  
%URL  
0%  
(4mA)  
0%  
+100%  
Zero suppression  
Zero elevation  
-100%  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2 Span adjustment (Change Upper Range Value)  
The measuring range for each transmitter is determined according to its type.  
The span is changed by the external adj. screw when the mode setting switch is set at “1” or ”6"  
position.  
(1) Set the mode setting switch to “1” or ”6” position.  
(2) Apply standard input pressure corresponding to new Upper Range Value.  
(3) Adjust output to 20.00mA by turning the external adj. screw.  
Decrease  
Increase  
(4) Then, apply input pressure corresponding to new Lower Range Value again and make sure  
output is 4mA.  
(5) After span adjustment according to above procedure from 3.2-(1) to (4), please set mode  
setting switch to appropriate position  
After adjustment, the transmitter should be kept energized at about 10 seconds to write  
the adjustment parameter into memory.  
Important  
4. Damping adjustment  
If a pulsation of the output current is caused due to flow noise etc., it can be attenuated by performing  
damping adjustment.  
Damping is adjustable in 8 steps. The damping constant becomes lager in the order of 0,1,2,3and 4.  
These damping constant correspond to time constant 0, 0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2 seconds for the  
transmission unit regardless of span.  
The relationship between position of switch and time constant are indicated in table 2.  
Note)  
The damping constant above is a time constant applied to the transmission unit only. The  
detecting unit has additional time constant  
(Please see data sheet about details)  
When the transmitter respose speed is changed, the time constant of the control system  
is also changed. Be sure to check the controllability again.  
Important  
5. Fixed current output and its adjustment  
Output of fixed current regardless of input is available.  
Output of fixed current is convenient for loop check.  
When the output(4 or 20mA)is in error, it can be adjusted by the external adjustment screw.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
MAINTENANCE  
5.1 Periodic inspection  
In order to ensure the measurement accuracy and long life of the transmitter, it is  
essential to inspect the transmitter periodically according to the operating conditions.  
Visual inspection  
Visually inspect each part of the transmitter for damage, corrosion, etc.  
If you detect any material which may cause corrosion, it should be cleaned off.  
Check of cover and O-ring  
The transmitter has a water and dust-proof construction.  
Make sure the O-ring of the case cover is not damaged or deteriorated.  
Carefully prevent foreign materials from sticking to threads.  
Piping leakage check  
Using soapy water or the like, check the all process connections for leakage of  
process fluid. If necessary, drain the moisture which has accumulated in  
the transmitter and process pipe.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.2 Troubleshooting  
If an abnormality occurred in the process or transmitter, action should be taken with reference to the  
table below.  
Symptom  
Cause  
Remedy  
Repair the valve so that it opens/closes normally.  
(1) The manifold valve does  
not open/close normally.  
(2) Pressure leak is occurring.  
(3) Process piping is improper.  
(4) Process pipe is clogged.  
(5) Power supply voltage  
and/or load resistance is  
improper.  
Repair a leak.  
Make correct piping.  
Eliminate the cause of clogging.  
Make arrangement to obtain proper values.  
(For power supply voltage and load resistance,  
refer to “7.2” (page 50).)  
(For intrinsically safe installations, the power  
supply voltage should be 10.5 to 26V DC for  
smart type.)  
Check for faulty cable, insulation, etc. and repair  
as needed.  
Output  
current  
overshoots  
scale  
(exceeds  
20mA).  
(6) Voltage between the  
external connection  
terminals of transmission  
unit is wrong.  
(For power supply voltage and load resistance,  
refer to “7.2” (page 50).)  
(For intrinsically safe installations, the power  
supply voltage should be 10.5 to 26V DC for  
smart type.)  
Readjust according to sections 4 (page 9).  
(7) Zero and span are not  
adjusted.  
Replace the electronics unit according to 5.3 (page  
32).  
(8) Electronics unit is faulty.  
Correct wiring (according to 7.1 (page 48)).  
(1) Same as (1) to (4) above  
(2) Power supply polarity is  
wrong.  
Make arrangement to obtain proper values.  
(For power supply voltage and load resistance,  
refer to “7.2” (page 50).)  
(For intrinsically safe installations, the power  
supply voltage should be 10.5 to 26V DC for  
smart type.)  
(3) Power supply voltage and/  
or load resistance is  
improper.  
No output  
current (less  
than 3.8 mA).  
Check for faulty cable, insulation, etc. and repair  
as needed.  
(For power supply voltage and load resistance,  
(4) Voltage between the  
external connection  
terminals is wrong.  
refer to "7.2" (page 50).)  
(For intrinsically safe installations, the power  
supply voltage should be 10.5 to 26V DC for  
smart type.)  
Replace the electronics unit according to 5.3 (page  
32).  
(5) Electronics unit is faulty.  
(1) Process piping is improper.  
(2) Gas or solution is mixed in.  
(3) Liquid density changes.  
(4) Ambient temperature  
changes widely.  
Correct the piping.  
Output current  
error  
Vent or drain the transmitter.  
Perform density compensation.  
Minimize the temperature change.  
(5) Zero or span has deviated.  
(6) Electronics unit is faulty.  
Readjust zero or span.  
Replace the electronics unit according to 5.3 (page  
32).  
If remedy is impossible, contact Fuji Electric’s service department.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.3 Replacement of parts  
If the transmitter requires a replacement part, drain process fluid from the transmitter,  
disconnect it from the process and carry out replacement in an instrument room.  
When removing an explosion-proof transmitter, turn OFF the main power, then dis-  
connect the piping and wiring. Do not remove it when the power is ON to prevent  
serious accident such as explosion, fire, etc.  
DANGER  
To identify faulty part  
Replace the transmission unit with a spare one in order to determine whether it is the  
detecting unit or transmission unit which is faulty.  
When the faulty unit is identified, it should be replaced with a new one.  
Replacement of electronics unit  
Replacing procedure  
Electronics unit  
(1) Turn off the power supply.  
(2) Remove the indicator.  
Indicator  
(3) Remove the electronics unit.  
Unplug each connector.  
(4) Remove the stud bolts which fastens  
Connection at rear  
of electronics unit  
the indicator.  
(5) Replace the electronics unit with a  
new one and assemble it by  
reversing the above procedure from  
(4) to (1).  
When installing the electronics unit, make sure that the  
zero adjust screw and the volume control are posi-  
Important  
Volume control  
Zero/span  
tioned as shown the right.  
adjustment screw  
(6) After completion of replacement, perform zero and span adjustments.  
The electronics unit should be removed carefully so as not to damage the internal  
wiring.  
Important  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replacement of detecting unit  
Transmission unit  
Detecting unit  
Flexible printed circuit board  
Hexagonal socket bolt  
Replacing procedure  
(1) Remove the electronics unit according to “Replacement of electronics unit”.  
(2) Remove the hex. socket bolts from the electronic housing.  
Pull the electronics housing straight forward and away from the detecting unit.  
(3) Replace the detecting unit with a new one of the same type.  
(4) Fit the transmission unit to the detecting unit and tighten it.  
(5) Connect each connector of the electronics unit and attach it to the transmission  
unit.  
(6) After reassembly, carry out zero and span adjustments.  
• Ensure that replacement detector unit is the same specification as the original  
by comparing dataplates.  
Important  
• When removing the transmitter case, pay attention not to damage the flexible  
printed circuit board.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replacement of the internal parts of detecting unit  
In case of differential transmitter (code symbol : FKK/FDK) :  
Nut  
Seal diaphragm  
O-ring  
Measurement  
chamber  
detecting cover  
Seal tape  
Bolt  
Seal tape  
Replacing procedure  
(1) Remove four hexagon socket head bolts with a torque wrench, etc..  
(2) Disassembly gives access to the casing covers, O-rings, hexagon socket head bolts and nuts.  
(3) After disassembly, replace the faulty part with a new one.  
(4) Before reassembly, clean the O-ring face of casing cover with the soft cloth immersed in  
water, alcohol, or similar detergent.  
(5) Reassemble the detecting unit by reversing the disassembling procedure. The casing covers  
should be assembled so as to be symmetrical with each other in the left-right direction and  
carefully so as not to damage the seal diaphragm. Tightening torque should follow the table  
below.  
Tightening Maximum working  
torque  
Bolt size Bolt material [N•m]  
(kgf•m)  
pressure  
[MPa]  
{bar}  
Application  
<ft-lb>  
<psi>  
50  
42  
M10  
M10  
M10  
Cr-Mo steel  
(5)  
<36>  
{420}  
<6000>  
Working pressure 42 MPa {420 bar} <6000 psi> or less  
Working pressure 10MPa {100 bar} <1400 psi> or less  
Working pressure 42 MPa {420 bar} <6000 psi> or less  
SUS304  
ASTMB7M  
ASTML7M  
30  
(3)  
<22>  
10  
{100}  
<1400>  
50  
(5)  
<36>  
42  
{420}  
<6000>  
SUS630  
(6) After assembly, carry out a pressure test. Apply a pressure equal to 150% of the maximum  
working pressure to both high pressure (H) and low pressure (L) measurement chambers of  
the transmitter simultaneously for 15 minutes, and make sure there is no leakage.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replacement of field indicator  
1. Replacement of analog indicator  
Analog indicator  
Transmitter cover  
Replacing procedure  
(1) Detach the transmitter cover.  
(2) Remove the analog indicator.  
(3) Pull out the connector extending from the analog indicator.  
(4) Connect the connector of a new analog indicator to the electronics section. (See the figure  
below.)  
(5) Then, mount the analog indicator at the electronics section.  
(6) Attach the transmitter cover.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Replacement of digital indicator  
Digital indicator  
Transmitter cover  
Digital indicator mounting board  
Replacing procedure  
(1) Detach the transmitter cover.  
(2) Remove two fixing screws which fasten the digital indicator and separate the indicator.  
(3) Pull out the leading end of the flexible PC board extending from the digital indicator after  
raising the slider (white knob) in the electronics section. (See the figure below.)  
(4) Insert the leading end of the flexible PC board of a new digital indicator into the connector  
plug-in port of the electronics section and fix it by pushing in the slider. Before inserting the  
flexible PC board, confirm its correct orientation.  
Digital indicator  
plugin port  
Pin Plug  
(5) Fasten the digital indicator to the electronics section by tightening two fixing screws.  
Before tightening, make sure a small recess on the surface is positioned at the top as shown  
below.  
When twisting the flexible PC board for mounting, adequate attention should be paid not to  
damage the board.  
(6) Attach the transmitter cover.  
Fixing screw  
Small recess  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.4 Adjustment after replacement of unit  
Adjustment  
After completion of the assembly work mentioned above, use the following procedures for adjust-  
ment and setting. Adjustment should be performed using the HHC.  
(1) After replacement of electronics unit (including replacement of internal parts)  
Step  
1
Adjustment item  
Constant current output (output circuit)  
TAG. No.  
Relevant page  
P19  
2
P11  
3
Type  
P12  
4
Industrial value unit  
Range (zero/span)  
Zero/span adjustment  
Damping  
P13  
5
P14  
6
P18  
7
P15  
8
Output mode (LIN/  
Burnout direction  
selection)  
P16  
9
P17  
10 Lock of adjustment function  
P22  
(2) After replacement of detecting unit (including replacement of internal parts)  
Step  
1
Adjustment item  
Range (zero/span)  
Relevant page  
P14  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
INSTALLATION AND PIPING  
6.1 Installation  
After unpacking, check the delivered items.  
This transmitter can be mounted on a pipe or on a wall.  
Note that the bolts (M8) for wall mounting should be supplied by the customer.  
• The transmitter is heavy. Be careful when handling it.  
• The transmitter should be installed in a place that meets the operating conditions  
shown in DS sheet or instruction manual.  
• Install the transmitter according to the instruction manual. Improper installation  
CAUTION  
may lead to the cause of fall, trouble or incorrect operation.  
• When installing, make sure that the transmitter interior is free from cable chips  
and other foreign objects to prevent fire, trouble or incorrect operation.  
• Non-explosion-proof transmitter must not be used in a place with explosive gas to  
prevent serious accidents such as explosion, fire, etc.  
DANGER  
If the transmitter is not used soon after delivery, then leave it packed and store it in a  
room at the normal temperature and humidity (25°C <77°F>, 60%RH).  
Important  
Bracket mounting  
Mount the bracket to the transmitter.  
The bracket should be mounted to the process cover as shown below.  
(Pressure and absolute transmitter, types : FKP & FKH)  
(Differential pressure transmitter,  
type FKK)  
Mount to a horizontal pipe  
Mount to a vertical pipe  
Transmitter  
Transmitter  
Transmitter  
Measuring chamber  
detector cover  
Bracket  
Bracket  
Bracket  
Plain washer  
Plain washer  
Plain washer  
Spring washer  
Spring washer  
Spring washer  
Mounting bolt  
(M8 × 12)  
Mounting bolt  
(M4 × 10)  
Mounting bolt  
(M4 × 10)  
Adaptor (Option)  
Adaptor (Option)  
Mounting  
Pipe mounting  
(Differential pressure transmitter)  
(Pressure and absolute pressure transmitters transmitter)  
Mount to a horizontal pipe Mount to a vertical pipe  
U-bolt  
(1) Fasten the transmitter to a vertical or horizontal pipe using the supplied U-bolt (tightening torque  
approximately 15 N•m (1.5 kgf•m) <11ft-lb>).  
(2) Use a pipe of outer diameter ø60.5 <2.38">mm.  
Wall mounting  
(1) Fasten to wall face by M8 bolt utilizing the U-bolt holes.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Change of field indicator position  
Avoid the following procedure in an explosionproof area.  
CAUTION  
It is sometimes preferable to mount the indicator on the terminal block side due to  
installation location.  
In such a case, the following mounting procedure should be followed for analog indicator.  
Digital indicator cannot be mounted on the terminal block side.  
Indicator attached  
to transmission  
unit side.  
Remove the terminal  
unit side cover.  
Remove the transmission  
unit side cover with  
window and indicator.  
Attach the cover.  
Remove pin  
plug fitted to  
indicator.  
Mount the supplied  
attachment on  
indicator.  
Pin plug  
Attachment  
Mount the studs  
supplied with the  
attachment on  
the terminal  
Connect the red wire (+)  
of the indicator to CK+  
and the black wire (-) of  
the indicator to CK-, then  
attach the cover with  
window.  
block.  
Studs  
Indicator attached to  
terminal board side.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Change of transmission unit position  
Avoid the following procedure in an explosionproof area.  
CAUTION  
Wiring is sometimes difficult depending on the installation loca-  
tion. In such a case, it is convenient to carry out the following.  
Before turning the transmission unit, remove the electronics  
unit.  
The transmission unit is secured by 2 hexagonal socket bolts.  
Loosen the bolts, turn the transmission unit at 90˚ or 180˚ in the  
clockwise or counterclockwise direction and fix it by the screws.  
Then, carry out wiring.  
Hex.  
socket bolt  
If the transmission unit has been turned  
excessively without removing the  
Important  
electronics unit, straighten the ribbon  
cable which connects the electronics unit  
in the transmission unit and the detecting  
unit, and set the transmission unit again.  
Turn at 90°  
in the counter-  
clockwise.  
Turn at 90°  
in the clockwise.  
Change of indicator angle  
Avoid the following procedure in an  
explosionproof area.  
CAUTION  
In case of an analog indicator, it can be turned ±180˚ in 90˚  
increments because it is connected with a pin plug.  
Digital indicator does not allow change of its mounting  
direction.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Change of vent/drain plug position  
Hold the hexagonal area of the vent/drain plug  
with a wrench and remove it by turning slowly.  
Peel the existing seal tape and wind a new seal  
type. Then, screw the vent/drain plug into the  
process connection for changing.  
Process connection  
Tightening torque: 25N•m (2.5kgf•m) <18ft-lb>  
Check space  
Ensure a space of about 500mm against the cover in order to facilitate check, adjustment, etc.  
500  
500  
500  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.2 Piping  
It is generally recognized that there are appropriate positioning relationship between the  
transmitter and main process piping for accurate measurement to avoid harmful gas or liquid  
accumulation.  
General recognizations are;  
1- Mount transmitter below main process piping for liquid or steam measurement.  
2- Mount transmitter above main process piping for gas measurement.  
The standard style of FCX-CII series transmitter except gauge pressure transmitter correspond to  
the piping procedure 1 mentioned above. Change the vent/drain plug to correspond to the piping  
procedure 2.  
Main valve used for piping should be selected with the maximum pressure of the pro-  
cess taken into account (piping parts such as main valve, etc. should be furnished by  
user). If the main valve and other parts do not meet the rating, it may result in leakage  
CAUTION  
of gas or liquid which could lead to a hazard.  
6.2.1 Piping of differential pressure transmitters  
Check of high/low pressure sides of transmitter  
The detecting unit of the differential pressure transmitter bears  
symbols H and L which represent high and low pressure sides,  
respectively.  
L H  
Also, vent/drain plugs are provided at the lower process connection,  
while impulse pipes are connected at the upper process connections.  
Removal of protective cap  
The process connection ports of the transmitter and manifold (equalizer) valve are fitted with  
protective caps. Before piping, be sure to remove the caps. When removing the caps, care-  
fully protect the threaded portion and sealing face from damage.  
Connection of transmitter and impulse pipes  
(1) When using the manifold valve, it should be fixed to the transmitter by tightening four oval  
flange setbolts (7/16-20UNF), and then the impulse pipe should be connected to the manifold  
valve. Tightening torque of 7/16-20UNF mounting bolt should be 30 to 40 N•m (3 to 4  
kgf•m).  
(2) If a manifold valve is not used, the impulse pipes can directly be screwed into the transmit-  
ter. If thread size does not match between the transmitter and impulse pipes, an oval flange  
should be used. Tightening torque of 7/16-20UNF mounting bolt in an oval flange should  
be 30 to 40 N•m (3 to 4 kgf•m).  
Position of process taps (Horizontal main process piping)  
The position of the process tap is determined by the relationship between the condition, char-  
acteristics and measuring point of the process fluid.  
Note the following figures when planning and installing the piping.  
Gas measurement  
Liquid measurement  
Main process piping  
Steam measurement  
Differential pressure source  
45°  
45°  
Upper  
Lower  
Upper  
45°  
45°  
Lower  
Differential pressure  
source is located upper  
side of main process piping  
Differential pressure  
source is located lower  
side of main process piping  
Differential pressure  
source is located upper  
side of main process piping  
Within 45°upward from  
vertical direction  
Within 45° downward  
from horizontal direction  
Within 45° upward from  
horizontal direction  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical examples of piping  
Manifold valve  
Impulse pipe  
Stop valve  
1
Flow measurement (in case of gas)  
Place the transmitter above the differential pres-  
sure source.  
Process pipe  
Differencial pressure source (orifice)  
Differencial pressure source (orifice)  
Flow measurement (in case of liquid)  
2
Process pipe  
Stop valve  
Place the transmitter below the differential pres-  
sure source.  
Impulse pipe  
Make piping so that gas in the impulse pipe is not  
delivered to the transmitter, and incorporate gas  
reservoirs as required.  
Manifold valve  
Process pipe  
Stop valve  
Flow measurement (in case of steam)  
3
Condenser  
Set two condensers at the same height near the  
process tap. Fill the line between the condensers  
and transmitter with condensed water.  
Install a drain port as required.  
Impulse pipe  
Manifold valve  
Process pipe  
Pressure measurement (in case of liquid)  
4
Pressure source  
Zero point can be checked with a manifold valve  
installed.  
Atmospheric air inlet  
Stop valve  
Manifold valve  
Impulse pipe  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(1) Protection is required to prevent dust from entering through the atmospheric  
air inlet after installation of the manifold valve.  
Important  
(2) If process pressure range is narrow (below 10kPa (1000mmH2O)), the follow-  
ing should be considered.  
• Pressure variation due to wind around atmospheric air inlet  
• Temperature variation near process taps  
• Difference in atmospheric pressure between process tap and transmitter  
location.  
To overcome this, provide atmospheric pressure-side pipe with a proper orifice  
and consider accommodating the transmitter and atmospheric air inlet in a box.  
5
6
Pressure measurement (in case of gas)  
Mount the transmitter above the process pipes to  
preventing moisture from entering the inside of  
transmitter.  
Manifold valve  
Impulse pipe  
Stop valve  
Atmospheric  
air inlet  
Process pipe  
Pressure source  
Level measurement  
(1) In case of wet leg:  
For measurement, connect the highest liquid level tapping of tank with the low pres-  
sure side of transmitter, and the lowest liquid level tapping of tank with the high  
pressure side of transmitter.  
ρ1  
Condensor  
Max. liquid  
level  
< Level calculation formula >  
LRV: rH2 - r0H1  
h
Min. liquid  
level  
ρ
URV: rH2 + r1h - r0H1  
Span (DP): r1h  
ρ0  
Manifold  
valve  
H2  
LRV: Low limit of measurement (0% point)  
URV: High limit of measurement (100% point)H  
r0,r,r1: Density  
1
High  
pressure  
side  
Low  
pressure  
side  
H1, H2: Liquid level, h: Liquid level change  
(2) In case of dry leg:  
For an open tank, leave the low pressure side of transmitter open to atmosphere.  
Max. liquid  
level  
< Level calculation formula >  
LRV: rH1  
ρ1  
h
Min. liquid  
level  
URV: rH1 + r1h  
Span (DP): r1h  
ρ
Atomospheric  
LRV: Low limit of measurement (0% poinat)ir inlet  
URV: High limit of measurement (100% point)  
r,r1: Density  
Manifold  
valve  
H1  
High  
pressure  
side  
Low  
pressure  
side  
H1: Liquid level, h: Liquid level change  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cautions on impulse piping  
• For liquid, the impulse pipes should have an upward slope of 1/10 or more between the  
process connection and the transmitter to prevent accumulation of gas, etc. in the detect-  
ing unit.  
• For gas, the impulse pipes should have a downward slope of 1/10 or more between the  
process connection and transmitter to prevent accumulation of moisture, etc. in the de-  
tecting unit.  
• Do not bent the impulse pipes acutely near the pressure outlet port, to prevent gas or drain  
from staying in the pipe.  
• Take care not to apply an excessive force to the transmitter during connection.  
• In order to prevent vibration of the transmitter body and capillary from interfering with  
output, the transmitter body should be installed at a vibration-free place and the capillary  
should be fixed to a stable support.  
• The impulse pipes used should be suitable for the working temperature, pressure, etc.  
• When the measuring fluid is likely to freeze in the cover of the measurement chamber,  
the cover needs to be warmed up with steam or a heater.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.2.2 Piping of pressure transmitter type : FKP  
Removal of protective cap  
The process connection port of the transmitter is fitted with a protective cap. Before piping,  
remove the cap carefully. When removing the cap, carefully protect the threaded portion and  
sealing face from damage.  
Connection of transmitter and impulse pipe  
• Impulse pipe should directly be screwed into the transmitter.  
• After connection, close the stop valve of transmitter in order to prevent foreign materials  
from entering the inside.  
Position of process taps (Horizontal main process piping)  
The position of the process tap is determined by the relationship between condition, charac-  
teristics and measurement point of process fluid. Note the following figures when planning  
and installing the piping.  
Gas measurement  
Liquid measurement  
Main process piping  
Steam measurement  
Pressure source  
45°  
45°  
Upper  
Lower  
Upper  
45°  
45°  
Pressure source is  
Lower  
Pressure source is  
located upper side of  
main process piping  
Pressure source is  
located upper side of  
main process piping  
located lower side of  
main process piping  
Within 45° upward from  
Within 45° downward  
Within 45° upward from  
vertical direction  
from horizontal direction  
horizontal direction  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical examples of piping  
1
Gas measurement  
Manual valve  
Impulse pipe  
Place the transmitter above the pressure source.  
Stop valve  
Pressure source  
Pressure source  
Process pipe  
2
Liquid measurement  
Process pipe  
Place the transmitter below the pressure source.  
Make piping so that gas in the process pipe is not  
delivered to the transmitter, and incorporate gas  
reservoirs as required.  
Stop valve  
Impulse pipe  
This is required for preventing gas from remain-  
ing in the impulse pipe and transmitter.  
Manual valve  
Pressure source  
Stop valve  
Impulse pipe  
Steam measurement  
3
Place the transmitter below the pressure source.  
Manual valve  
Cautions on impulse piping  
• For liquid, the impulse pipe should have an upward slope of 1/10 or more between the  
process connection and transmitter to prevent accumulation of gas, etc. in the detecting  
unit.  
• For gas, the impulse pipe should have a downward slope of 1/10 or more between process  
connection and transmitter to prevent accumulation of moisture, etc. in the detecting unit.  
• Avoid any sharp bends in impulse pipe which may cause gas or moisture to accumulate in  
the impulse pipe.  
The impulse pipe used should be suitable for the working temperature, pressure,  
etc.  
CAUTION  
• Take care not to apply an excessive force to the transmitter during its connection.  
• When the measurement fluid is likely to freeze in the cover of measurement chamber, the  
cover needs to be warmed up with steam or a heater.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.2.3 Piping of level transmitter type : FKP for open tank  
Seal on mounting flange face  
When mounting the flange on the pressure side, a gasket should be inserted as  
follows.  
Transmitter flange  
Process side flange  
Gasket  
On the projection type, be sure to use a gasket with an internal diameter larger  
Important  
than the flange to prevent the gasket form touching the seal diaphragm.  
Connecting method of the mounting flange  
Thighten bolts of mounting flange and process flange in a diagonal order and  
about three cycles.  
Removal of protective cap from process connection port  
The process connection port on the low pressure side is fitted with a protective  
cap. Before piping, remove the cap carefully. When removing the cap,  
carrefully protect the threaded portion and sealing face from damage.  
Connection of transmitter and impulse pipe  
After connection, close the stop valve of the transmitter in order to prevent  
foreign materials from entering the inside.  
Typical example of piping  
Level measurement of open tank  
Leave the below pressure side of the transmitter open to atmosphere.  
Level circulation formula  
LRV = ρ.H1  
ρ
URV = ρ.(H1+h)  
LRV = low limit of measurement (0%)  
h
URV = high limit of measurement (100%)  
ρ = measuring liquid density  
H
1
H1 = Liquid level  
h = liquid level change  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Caution of installation  
• Restriction on H1  
Liquid level is not proportional to the transmitter output at some points inside  
the seal diaphragm.  
Therefore, H1 should be set higher than the value shown in the table below.  
• In order to prevent vibration, the transmitter body should be installed at a  
vibration-free place.  
• Do not shock the seal diaphragm by hitting hard object against it, for example.  
• Take care not to apply an excessive force to the flange during connection.  
Minimum value of H1  
Flange size  
DN40 / 1 1/2”  
DN50 / 2”  
DN80 / 3”  
DN100 / 4”  
Non projection type  
30mm  
Projection type  
30mm  
55mm  
55mm  
30mm  
40mm  
55mm  
It should be noted that leakage of fluid from the wetted parts would affect  
the performance due to the progress of corrosion.  
Important  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
WIRING  
Cautions on wiring  
(1) Application of a voltage exceeding 60 V DC or 40 V AC (exceeding 32 V DC or 23 V AC  
when arrester equipped) between “+” and “–” terminals may result in damage to the transmitter.  
(2) Use a shielded cable for the transmission line where possible.  
(3) Avoid installation of signal cable and power cable in same conduit or cable tray in order to  
prevent increased noise. Also, do not bring the signal cable close to large electrical equip-  
ment.  
In case of an explosionproof arrangement, wiring shall be made in accordance with  
the relevant regulations to ensure the explosionproofing.  
DANGER  
7.1 Wiring procedure  
• Before making wiring work, be sure to turn OFF the main power to prevent  
electric shocks.  
• Use wiring materials of correct rating to prevent fire accidents.  
• After installing the transmitter, firmly close the covers of the transmission unit  
and terminal box. If not, rain water enter the transmitter which may result in  
trouble or incorrect operation.  
CAUTION  
Sealing of conduit connection  
Use sealing tape, if using metal pipe screw coupling or rubber gasket and fastening gland in the  
case of cable (OD ø11) <0.43"> to ensure airtightness of the connection box.  
1. If the connection box is located above the transmitter when using a protec-  
Important  
tive tube for the wiring, then moisture may enter the protective tube and have  
an adverse effect on the transmitter. So maintaining airtightness of the  
connection box is an important practice.  
2. The thread of conduit tube should meet the selected size and a seal fixture  
should be used.  
Cable  
Metal  
pipe  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Terminal block connection diagram  
Tighten the terminal screws (M4 x10) to a torque of approximately 1.5 N•m (15 kgf•cm) <11ft-  
lb> so that the wires will not loosen.  
After connection, fasten the cover until it does not turn.  
Terminal  
CK–  
CK+  
+
10.5 ~ 45 V DC (Analog type)  
16.1 ~ 45 V DC (Smart type)  
Conveter  
Output DC4 ~ 20mA  
When using an external field indicator  
For direct connection to an external field indicator, connect the “+” and “–” sides of the field  
indicator to CK+ and CK– of the transmitter as shown below.  
Use an external field indicator with internal resistance of 12W or less.  
+
4 ~ 20mA DC  
CK–  
CK+  
+
10.5 ~ 45 V DC (Analog type)  
16.1 ~ 45 V DC (Smart type)  
Converter  
Output DC4 ~ 20mA  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Things convenient to know beforehand  
When using conduit connection at the top  
For wiring from the top conduit connection, use the following procedure.  
(1)  
(2)  
(3)  
Remove the screw plug of the top conduit connection.  
Screw the removed screw plug into the bottom conduit connection.  
Insert the cable from the top and connect it.  
Hexagon key  
wrench  
Flash screw  
• The unused conduit connection is of great importance to flameproofing and  
moisture prevention. So be sure to tighten the flush screw and packing into  
the connection.  
Important  
• When performing an insulation check after wiring, use a Megger (insulation  
resistance meter) of 250 V DC or less and avoid applying a high voltage. If an  
arrester is equipped, avoid the insulation resistance test and the dielectric  
strength measurement.  
7.2 Power voltage and load resistance  
Make sure the load resistance of the wiring connected to the loop is within the range shown below.  
Connect power source of correct rating. Use of power source in excess of the  
rating may cause a fire.  
CAUTION  
1533  
Note  
600  
Operating  
zone  
250  
0
10.5 16.1  
24  
45  
Power voltage (Vdc)  
Note) For communication with HHC, the smart type requires load resistance 250 as  
minimum.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.3 Grounding  
The transmitter must be grounded. Otherwise, it may cause electric shocks or  
incorrect operation.  
CAUTION  
Grounding terminals are provided at two places (at the inside of terminal box and on the side of  
conduit connection).  
By any of the methods given below, ground the transmitter in compliance with the relevant stipu-  
lation in the standard on explosionproof installation (for example, grounding resistance 100 or  
less by one of the methods given below). In case of intrinsically safe and flameproof installation,  
be sure to use the ground terminal for grounding.  
Grounding of transmitter casing  
Grounding from ground terminal  
External grounding terminal  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
SPARE PARTS  
This diagram shows main parts of the differential pressure transmitter, pressure transmitter.  
For details, contact our office.  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No.  
A-1  
Parts No.  
Part Name  
Q’ty  
1
Material  
Remarks  
* ZZPFCX4-A010 Cover  
Aluminium alloy Blue  
ADC12  
A-2  
A-3  
A-5  
* ZZPFCX4-A020 Cover  
1
1
Aluminium alloy Blue  
ADC12  
* ZZPFCX4-A030 Cover ass'y  
Aluminium alloy With indicator  
ADC12  
* ZZPFCX4-A050 Indicator  
* ZZPFCX4-A051 Indicator  
* ZZPFCX4-A052 Indicator  
* ZZPFCX4-A053 Indicator  
* ZZPFCX4-A054 Indicator  
* ZZPFCX4-A054A Indicator kit  
1
1
1
1
1
1
1
1
1
1
Analog, 0 to 100% linear  
Analog, 0 to 100% square-root  
Analog, dual scale  
Analog, actual scale  
LCD Meter  
A-5A * ZZPFCX4-A05A Unit name plate  
LCD Indicator type  
A-6  
A-9  
* ZZPFCX4-A061 Amplifier unit  
* ZZPFCX1-A091 Switch over plug  
Normal/Reverse action switch over plug.  
A-10 * ZZPFKK1-A101 Electronics housing  
* ZZPFKK1-A102 Electronics housing  
* ZZPFKK1-A103 Electronics housing  
Aluminium alloy With Pg13.5 connection  
ADC12  
1
1
Aluminium alloy With NPT1/2 connection  
ADC12  
Aluminium alloy With M20 x 1.5 connection  
ADC12  
A-12A * ZZPFCX4-A121A Plug kit  
* ZZPFCX4-A123A Plug  
1
1
1
1
Plug for Pg13.5 connection.  
Plug for M20 x 1.5 connection.  
A-12 * ZZPFCX1-A122 Plug  
* ZZPFCX4-A121 Plug  
Stainless steel Plug for NPT1/2 connection.  
Aluminium alloy Plug for Pg13.5 connection.  
ADC12  
* ZZPFCX4-A123 Plug  
1
Aluminium alloy Plug for M20 x 1.5 connection.  
ADC12  
A-13A * ZZPFCX4-A132 Terminal block unit  
* ZZPFCX4-A133 Terminal block unit  
* ZZPFCX4-A134 Terminal block unit  
* ZZPFCX4-A135 Terminal block unit  
A-20A * ZZPFCX1-A200A Cable gland kit  
A-24A * ZZPFKK1-A240A Fastener kit  
A-31A * ZZPFCX1-A310A Hex. socket screw kit  
A-39 * ZZPFCX2-A390 Blank name plate  
A-40 * ZZPFCX1-A400 Rivet  
1
1
1
1
1
1
2
1
4
Round washer type.  
Wire retaining washer type.  
Round washer type with arrester.  
Wire retaining washer type with arrester.  
Minimum order q’ty 10 pcs.  
Standard (Minimum order q’ty 5 pcs.)  
Minimum order q’ty 50 pcs.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No.  
Parts No.  
––––––––  
Part Name  
Detecting unit  
Q’ty  
1
Material  
Remarks  
B-1~5  
Contact our office for inquiry  
(Differential pressure and Flow)  
B-8  
B-9  
* ZZPFCX4-B080  
* ZZPFCX4-B081  
O-ring  
2
2
Viton  
Minimum order q’ty 10 pcs.  
Square section gasket  
Teflon  
4th digit of  
type code  
* ZZPFCX4-B091  
* ZZPFCX4-B093  
* ZZPFCX4-B095  
Cover  
2
2
2
2
4
4
4
1
1
1
SCS14  
SCS14  
SCS14  
S
T,X  
V,W  
Cover  
Cover  
B-12A * ZZPFHC1-B122  
B-14 * ZZPFHC1-B143  
* ZZPFHC1-B144  
Vent/drain kit  
Bolt/Nut kit  
Bolt/Nut kit  
Bolt/Nut kit  
O-ring  
NPT1/4  
C.S.  
Stainless steel Up to 10MPa {100kgf/cm2}  
Stainless steel Up to 14MPa {140kgf/cm2}  
* ZZPFHC1-B145  
B-16 * ZZPFHC1-B160  
Chloroprene  
Minimum order q’ty 10 pcs.  
B-17 * ZZPFHK1-B171 Mounting bracket kit  
Stainless steel  
C-1~4  
––––––––  
Detecting unit  
(Pressure)  
Contact our office for inquiry  
C-7  
* ZZPFHP1-C071  
* ZZPFHP1-C072  
Adapter  
1
1
1
Stainless steel Rc1/2  
Stainless steel NPT1/4  
Stainless steel  
Adapter  
C-17 * ZZPFHP1-C171  
Mounting bracket kit  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A1  
BUILT-IN ARRESTER  
General  
An arrester is used to protect a transmitter or receiver from an abnormal voltage such as lightning  
surges induced into signal lines. A built-in type arrester is mounted behind the terminal unit. A  
nameplate marked “with arrester” is attached to the terminal unit of transmitter with a built-in  
arrester.  
Installation  
The built-in arrester should be used in combination with panel mounting type arrester (type PXC)  
for distributor protection.  
+
1–  
1+  
1
5
2
6
PXC  
E
PWM  
E
Distributor  
Transmitter  
(with arrester)  
Panel mounting  
type arrester  
Grounding  
Since transmitter and arrester groundings are internally connected together, user have only to  
connect the external grounding terminals to ground.  
Grounding terminal must be used, in case of the explosionproof or intrinsic safety type  
transmitter.  
FCX-C series transmitter  
Grounding terminal  
External grounding terminal  
External grounding terminal  
1. Grounding resistance should be 100W or less.  
2. Avoid common grounding with a lightning rod.  
Important  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Check of arrester  
• Measure output current from the transmitter check terminals and output current to flow into  
transmitter (see figures below).  
When current is measured with an ammeter connected to CK+ and CK- terminals, the  
internal resistance of the ammeter should be 12or less.  
• If the measured two output current are the same, the arrester is normal.  
• In case the measured values have a difference of 0.1% (0.016mA) or more, the arrester is  
not functioning.  
• In the above case, the arrester unit (terminal unit) should be replaced with a new one.  
Limitation of insulation resistance and dielectric strength test  
An insulation resistance and dielectric strength test should be avoided as a rule, since it  
may damage the arrester.  
Output measurement at check terminals  
Digital voltmeter  
To CK +  
To CK –  
Standard resistor  
(1 or 10)  
Output measurement outside transmitter  
* Disconnect the wire from the - (minus)  
terminal and connect the measurement device a  
shown below.  
To (–) terminal  
To (+) terminal  
Digital voltmeter  
To (+) side wiring  
DC power  
supply  
To (–) side  
wiring  
Standard resistance  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A2  
CALIBRATION  
Preparation for calibration  
The transmitter should be calibrated in a calibration room. For calibration of each transmitter, the  
following devices are required.  
o Pressure source and pressure measuring equipment (should have as high an accuracy as pos-  
sible)  
* Measurable ranges are listed in the table below.  
o Power supply : DC power supply (24 V DC) or Fuji Electric FC series power supply unit  
(type PXJ or PXL)  
o Load resistor : Standard resistor 250 (within ±0.0125 )  
o Measuring device : Digital voltmeter (capable of measuring transmitter output with an  
accuracy better than 0.1%)  
* Use meter having a 5-digit display.  
o Hand Held Communicator (HHC) type FXW  
* For use with smart type  
Differential pressure range of FKK  
Smart type  
Differential pressure range  
[kPa] {mmH2O} <inH2O>  
0.375~6 {37.5~600} <1.5~24>  
2~32 {200~3200} <8~125>  
8.125~130 {812.5~13000} <32.5~520>  
31.25~500 {3125~50000} <4.375~70psi>  
125~2000 {12500~200000} <17.5~280psi>  
Pressure range of FKP  
Smart type  
Pressure range  
[kPa] {bar} <psi>  
8.125~130 {0.08125~1.3} <1.188~19>  
31.25~500 {0.3125~5} <4.375~70>  
187.5~3000 {1.875~30} <26.875~430>  
625~10000 {6.25~100} <93.75~1500>  
Pressure range of FKH  
Smart type  
Pressure range  
[kPa] {bar} <psi>  
8.125~130 {0.08125~1.3} <1.188~19>  
31.25~500 {0.3125~5} <4.375~70>  
187.5~3000 {1.875~30} <26.875~430>  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Calibration procedure  
(1) Make wiring according to the diagram below.  
Connect DC power supply (power source), digital voltmeter (measuring device), standard  
resistance and HHC (Hand Held Communicator):  
When current is measured with an ammeter connected to CK+ and CK- terminals, the internal  
resistance of the ammeter should be 12or less.  
HHC  
Digital voltmeter  
DC power supply  
Load resistance  
Standard resistance  
Important  
For communication with the HHC, a load resistor of 250is necessary.  
(2) Calibration of output circuit (D/A)  
Calibrate the output circuit with reference to “Calibration of output circuit” (page 20) in “AD-  
JUSTMENT ”.  
(3) Zero/span adjustment  
Refer to “Zero/span adjustment” (page 35) in Section 7.  
(4) Accuracy test  
Apply input pressures in the order of 0%, 25%, 50%, 75%, 100%, 75%, 50%, 25% and 0%,  
and read output at each input pressure.  
Make sure the difference between each output value and input pressure (%) is within the  
accuracy rating listed in the table below.  
The voltage values in the table are dependent on use of “DC power supply + standard resistor  
250+ digital voltmeter (measuring device).  
Accuracy  
Measurement category  
Reference value  
Accuracy:0.1% Accuracy:0.2%  
Percent display (%)  
Current measurement (mA)  
Voltage measurement (V)  
0, 25, 50, 75, 100  
4, 8, 12, 16, 20  
1, 2, 3, 4, 5  
±0.1  
±0.2  
±0.016  
±0.004  
±0.032  
±0.008  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A3  
PARAMETER SETTING PRIOR TO DELIVERY  
The damping value (time constant), function of zero/span adjust screw, output current mode, indicator  
scale, cut point, mode below cut point and burnout, have been set prior to delivery as shown in the  
following.  
No.  
1
Item  
Contents of parameter  
No Damping  
Damping value  
(time constant)  
(= measuring period)  
Zero adjust  
2
3
Zero point adjustment possible  
screw function  
To be set by designation  
when ordering (Note 2)  
Current output mode  
Digital indicator scale  
To be set by designating type  
when ordering  
(9th digit of code  
symbols)  
Cut point  
4
5
7.07%  
Linear  
(square-root extraction  
mode setting)  
Mode below cut point  
(square-root setting)  
To be set by designation  
when ordering ( Note 3)  
6
7
Burnout  
Invalid  
Linearization function  
Note 1: For span adjustment, HHC should be used. HHC can also be used for zero adjustment.  
Note 2: In both the differential pressure transmitter and remote seal type, the output current mode is  
set in linear unless it is designated.  
Note 3: Burnout direction is selectable from HHC, Hold, Over scale (20.8 to 21.6), under scale (3.2 to  
3.8mA).  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A4 HAZARDOUS LOCATION INSTALLATION INFORMATION  
This appendix contains one table and four drawings that present installation instruction for the FCX-A/C  
Series Transmitter in a hazardous location. Refer to these figures when installing or servicing a  
transmitter mounted in a hazardous location.  
When installed the apparatus MUST be provided with a voltage limiting device which will prevent the  
rated voltage of 45V being exceeded.  
Table 1 BASEEFA Certificate numbers of FCX-A/C series transmitter  
Item  
Certificate number  
Ex95D2444  
Transmitter  
Intrinsically Safety  
Transmitter  
Type N  
Ex95Y4446X  
Ex90C2370X  
Ex93C2154  
Ex95D2445  
FXW  
Intrinsically Safety  
FXE  
Intrinsically Safety  
System  
Intrinsically safety  
Transmitter  
Flameproof  
FCX-A:  
Ex96Y1003  
FCX-C:  
Ex96Y1002  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fuji Electric France S.A.  
46, Rue Georges Besse - Z I du Brézet  
63 039 Clermont-Ferrand cedex 2 — FRANCE  
France : Tél. 04 73 98 26 98 - Fax 04 73 98 26 99  
International : Tél. (33) 4 7398 2698 - Fax. (33) 4 7398 2699  
E-mail : [email protected]  
Fuji Electric can accept no responsibility for possible errors in catalogues, brochures and other printed material. Fuji Electric reserves the right to alter  
its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes  
being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. All rights reseved.  
Printed in FRANCE : 2002  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Electro Voice Portable Speaker MTL 4B User Manual
Electro Voice Portable Speaker SH 1810 User Manual
Exmark Lawn Mower 4500 358 User Manual
FieldServer Computer Drive FS 8700 86 User Manual
Fisher Price Baby Toy 74123 User Manual
Focal Car Speaker 130 KRC User Manual
Frigidaire Refrigerator 242063600 User Manual
GE Cordless Telephone TC28031 Series User Manual
Gianni Industries Door L NH2300 User Manual
Gianni Industries Switch CP 22 Series User Manual