DIRECT-VENT FIREplaCE
OWNER’S OpERaTION aND INSTallaTION MaNUal
PFS
®
NaTURal GaS “TUDOR” MODElS (V)T32N-a SERIES,
CGDV32NR aND CTDV32NR-Ha
pROpaNE/lp GaS “TUDOR” MODElS (V)T32p-a SERIES
aND CGDV32pR
WARNING: If the information in this manual is not
followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediatelycallyourgassupplierfromaneighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installationandservicemustbeperformedbyaquali-
fied installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
Download from Www.Somanuals.com. All Manuals Search And Download.
SaFETy
Continued
Carbon Monoxide Poisoning: Early signs of
Keep the appliance area clear
and free from combustible ma-
terials, gasoline and other flam-
mable vapors and liquids.
carbon monoxide poisoning resemble the flu,
with headaches, dizziness or nausea. If you
have these signs, the fireplace may not be
working properly. Get fresh air at once! Have
fireplace serviced. Some people are more af-
fected by carbon monoxide than others. These
include pregnant women, people with heart or
lung disease or anemia, those under the influ-
ence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odor-
making agent is added to the gas. The odor
helps you detect a gas leak. However, the
odor added to the gas can fade. Gas may be
present even though no odor exists.
Do not place clothing or other
flammable material on or near
fireplace. Never place any ob-
jects on fireplace.
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases unless a certified kit is used.
2. For propane/LP fireplace, do not place
propane/LP supply tank(s) inside any
structure. Locate propane/LP supply
tank(s) outdoors. To prevent performance
problems, do not use propane/LPfuel tank
of less than 100 lbs. capacity.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this fireplace.
WARNING: Any change to
this fireplace or its controls can
be dangerous.
3. If you smell gas
•
•
•
shut off gas supply
do not try to light any appliance
do not touch any electrical switch; do
not use any phone in your building
immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions
WARNING:Donotuseablow-
er insert, heat exchanger insert
orotheraccessorynotapproved
for use with this fireplace.
•
•
if you cannot reach your gas supplier,
call the fire department
4. Never install the fireplace
Do not use any solid fuels (wood,
coal,paper,cardboard,etc.)inthis
fireplace. Use only the gas type in-
dicated on fireplace name plate.
•
•
in a recreational vehicle
in windy or drafty areas where curtains
or other combustible (flammable)
objects can make contact with the
fireplace front
Carefully supervise young chil-
dren when they are in the room
with fireplace.
•
in high traffic areas
5. Do not modify this fireplace under any
circumstances. Any parts removed for
servicing must be replaced prior to operat-
ing fireplace.
6. Turn fireplace off and let cool before
servicing, installing or repairing. Only a
qualified service person should install,
service or repair this fireplace. Have fire-
place inspected annually by a qualified
service person.
7. You must keep control compartments,
burners and circulating air passages clean.
More frequent cleaning may be needed due
to excessive lint and dust from carpeting,
beddingmaterial, etc.Turnoffthegasvalve
and pilot light before cleaning fireplace.
This fireplace reaches high tem-
peratures. Keep children and
adultsawayfromhotsurfacesto
avoid burns or clothing ignition.
Fireplace will remain hot for a
time after shutdown. Allow sur-
faces to cool before touching.
Do not operate fireplace with
glass door removed, cracked
or broken.
116646-01J
3
Download from Www.Somanuals.com. All Manuals Search And Download.
SaFETy Continued
8. Haveventingsysteminspectedannuallyby
codes, with the National Electrical Code,
ANSI/NFPA 70.
11. Do not use fireplace if any part has been
under water. Immediately call a qualified
service person to arrange for replacement
of the unit.
a qualified service person. If needed, have
venting system cleaned or repaired. See
Cleaning and Maintenance, page 30.
9. Do not use this fireplace to cook food or
burn paper or other objects.
10. This appliance, when installed, must be
electrically grounded in accordance with
local codes or, in the absence of local
12. Do not operate fireplace if log is broken.
13. Provide adequate clearances around air
openings.
pRODUCT IDENTIFICaTION
Upper Louver Panel
Flue Collar
Nailing Flange
Glass Door Assembly
Log Set
Piezo Ignitor
Control Valve
Lower Louver Panel
Lava Rock
Glowing
Embers
Grate Assembly
ON/OFF/REMOTE Switch
(Optional Installation)
Blower Switch (Optional Installation)
Figure 1 - Direct-Vent Fireplace with Millivolt Ignition
lOCal CODES
Install and use fireplace with care. Follow all
American National Standards Institute, Inc.
local codes. In the absence to local codes,
use the current National Fuel Gas CodeANSI
Z223.1/NFPA 54*.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
*Available from:
Quincy, MA 02269
pRODUCT FEaTURES
These are a few facts that can help you under- • Only the blower requires electricity if
stand and enjoy your direct-vent fireplace:
• The venting system may be routed to the
outside of your home in several ways. It may
installed. If you plan to install the blower
at a later date, outlet must be wired at the
bottom of the fireplace when framing.
vent through the roof (vertical) or it may vent • Apiezo ignitor and ceramic electrode create
to an outside/exterior wall (horizontal). The
vent pipe installation is very important to
allow for proper operation. You must follow
sparks to ignite the pilot light. It does not
require any matches, batteries or any other
sources of ignition to light the pilot.
the venting instructions very carefully for • Each time you turn on your fireplace, you
either vertical or horizontal applications.
• This fireplace may be installed in any room
of your house provided all local codes and
these installation instructions are followed.
may notice some amount of condensation
on the inside of the fireplace glass. This
is normal and will disappear after 10-20
minutes of operation.
• This fireplace does not require electricity • Your direct-vent gas fireplace system
to operate.
(fireplace and venting) is a balanced and
4
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
pRODUCT FEaTURES Continued
sealed gas operating unit. It requires ap- • Fireplaces with the suffix of -HAhave been
proximately 10-20 minutes of operating
time before the flame pattern stabilizes.
designed to operate at altitudes of 4000
feet and above.
pRE-INSTallaTION pREpaRaTION
of the termination cap.
LOCATION AND SpACE REqUIREMENTS
• Do not locate termination cap where exces-
sive snow or ice build up may occur. Be sure
toclearventterminationareaaftersnowfalls
to prevent accidental blockage of venting
system. When using snow blowers, do not
direct snow towards vent termination area.
• For horizontal installations above 2,000
feet, it is recommended that a 12" extension
pipe be added before starter elbow and a
round horizontal termination be used (see
High Altitude Installation, page 16).
Determine the safest and most efficient location
for your FMI PRODUCTS, LLC direct-vent fire-
place. Make sure that rafters and wall studs are
not in the way of the venting system. Choose a
location where the heat output is not affected by
drafts, air conditioning ducts, windows or doors.
Figure 2 shows some common locations. Be
aware of all restrictions and precautions before
deciding the exact location for your fireplace and
termination cap.
When deciding the location of your fireplace,
follow these rules:
• Do not connect this fireplace venting to a
chimney flue serving a separate solid-fuel
burning fireplace or appliance.
• Due to high temperatures, do not locate this
fireplace in high traffic areas, windy or drafty
areas or near furniture or draperies.
Flush with a wall
Through exterior wall
enclosed in a chase
• Proper clearances must be maintained.
• If your fireplace is to be installed directly on
carpeting, vinyl tile or any combustible mate-
rial other than wood, it must be installed on a
metal or wood panel extending the full width
and depth of the fireplace. See Figure 3.
• Your fireplace is designed to be used in
zero clearance installations. Wall or framing
material can be placed directly against any
exterior surface on the back, sides or top of
your fireplace, except where standoff spacers
are integrally attached. If standoff spacers
are attached to your fireplace, these spacers
canbeplaceddirectlyagainstwallorframing
material. See framing details on page 6.
• If you plan on installing a television or enter-
tainment center recessed above your fire-
place, itisrecommendedthatyoumaintaina
minimum 18" above top of louver opening.
• When locating termination cap, it is impor-
tant to observe the minimum clearances
shown in Figure 7, page 7.
• If recessing into a wall, you can avoid extra
framing by positioning your fireplace against
an already existing framing member.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with
450º F heat-resistant paint to coordinate
with the exterior finish.
• There must not be any obstruction such
as bushes, garden sheds, fences, decks
or utility buildings within 24" from the front
Corner
installation
Figure 2 - Common Fireplace Locations
1
2
22 / "
16 5/8"
3
8
34 / "
Figure 3 - Fireplace Bottom Dimensions
CLEARANCES
Minimum clearances to combustibles for the
fireplace are as follows:
*Back and sides
Perpendicular walls
0"
6"
0"
42"
36"
0"
Floor
Ceiling to louver opening
Front
Top
Vent
(See venting instructions for
specific venting clearances.)
Combustiblematerialwithamaximumthickness
of 5/8" may be flush with top front of fireplace.
* For back and sides of fireplace, do not pack with
insulation or other materials. 0" clearance to com-
bustible materials are for framing purpose only.
116646-01J
5
Download from Www.Somanuals.com. All Manuals Search And Download.
pRE-INSTallaTION pREpaRaTION
Continued
NOTICE: This fireplace is in-
tended for use as supplemental
heat. Use this fireplace along
with your primary heating sys-
tem. Do not install this fireplace
as your primary heat source.
If you have a central heating
system, you may run system’s
circulating blower while using
fireplace.Thiswillhelpcirculate
the heat throughout the house.
In the event of a power outage,
you can use this fireplace as a
heat source.
39 3/ "
13 5
/8"
9 /"
1
8
2
1
28 /2"
97/8"
343/8"
3
45/8"
541/8"
Nailing
Tabs
Figure 5 - Framing Clearances for Corner
Installation
1
2
3
A
4
FRAMING AND FINISHING
Wall
B
5
6
7
Figure 4 shows typical framing of this fireplace.
Figure 5 shows framing for corner installation.
All minimum clearances must be met.
C
D
E
For available accessories for this fireplace,
see Accessories on page 37. If you are using
a separate combustible mantel piece, refer to
Figure 6 for proper installation height. You can
install noncombustible mantels at any height
above the fireplace. Note: Noncombustible
mantels may discolor!
F
G
T o p of Louver
Opening
Mantel from
Mantel
Top of Louver
Ref. Depth Ref.
Opening
16"
14"
12"
10"
8"
1
2
3
4
5
6
7
14"
12"
10"
8"
6"
4"
A
B
C
D
E
F
323/8"
345/8"
6"
4"
2"
G
17" Horiz. Vent
20" Vert. Vent
Figure 6 - Clearances for Combustible
Mantels
Figure 4 - Framing Clearances for
Installation Against an Exterior Wall
6
Download from Www.Somanuals.com. All Manuals Search And Download.
116646-01J
lOCaTION OF TERMINaTION Cap
N
N
D
L
H
E
V
B
C
I
B
Fixed
Closed
V
V
Fixed
Closed
Openable
Openable
G
G
B
F
V
V
G
J
V
X
B
B
M
A
V
A
V
X
K
TERMINATION CAP
G
GAS METER
RESTRICTED AREA
(TERMINATION PROHIBITED)
V
AIR SUPPLY INLET
X
A
B
=
clearance above grade, veranda, porch, deck, or
balcony [*12" (30.5 cm) minimum]
I
=
=
clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
=
clearance to window or door that may be opened
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
clearance to permanently closed window
[minimum 12" (30.5 cm) recommended to prevent
condensation on window]
J
clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other fireplace
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
clearance to a mechanical air supply inlet [*In Canada,
6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within
10 ft. (3 m) horizontally]
C
D
=
=
K
=
=
vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 24" (61 cm) from L
the center-line of the terminal [18" (45.7 cm) minimum]
† clearance above paved side-walk or a paved driveway
located on public property [*84" (213.3 cm) minimum]
E
F
=
=
clearance to unventilated soffit [12" (30.5 cm) minimum] M = clearance under veranda, porch, deck
clearance to outside corner (see below)
[*12" (30.5 cm) minimum ‡]
G = clearance to inside corner (see below)
N = clearance above a roof shall extend a minimum of
24" (61 cm) above the highest point when it passes
through the roof surface and any other obstruction within
a horizontal distance of 18" (45.7 cm)
H
=
*not to be installed above a meter/regulator assembly
within 36" (91.4 cm) horizontally from the center line
of the regulator
†
vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
‡
*
only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
Outside Corner
Recessed Location
D
C
C
E
A
A = 6" (15.2 cm)
V
V
V
B = 6" (15.2 cm)
B
Balcony with No Side Wall
Balcony with Perpendicular Side Wall
C = Maximum depth of 48" (121.9 cm)
for recessed location
D = Minimum width for back wall of
recessed location -
Combustible - 38" (965 mm)
Noncombustible - 24" (61 cm)
E = Clearance from corner in
recessed location-
H
V
J
G
V
Combustible &
Noncombustible
H = 24" (61 cm)
J = 20" (50.8 cm)
Combustible - 6" (15.2 cm)
Noncombustible - 2" (5.1 cm)
G = 12" (30.5 cm) minimum clearance
Figure 7 - Minimum Clearances for Termination Cap
116646-01J
7
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTallaTION
NOTICE: Read these instruc-
tionscompletelybeforeattempt-
ing installation.
WARNING: Read all instruc-
tionscompletelyandthoroughly
before attempting installation.
Failure to do so could result in
seriousinjury,propertydamage
or loss of life.
These models are tested and approved for
use with FMI PRODUCTS, LLC (direct-vent)
pipe components and terminations.
The venting system must terminate on the
outside of the structure and can not be at-
tached to a chimney or flue system serving a
separate solid fuel or gas burning appliance.
A direct-vent appliance must have its own
venting system. DO NOT common vent this
appliance.
NOTICE:Failuretofollowthesein-
structions will void the warranty.
NOTICE: Do not seal vent cap
to pipe. Cap must be removable
for service.
These models are approved to be vented
either horizontally through an outside wall or
vertically through a roof or chase enclosure
using the following guidelines:
• When venting system terminates horizon-
tally on an outside wall, you may install
a standoff if the termination cap is to be
installed directly on a combustible finish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which could
cause a fire.
• Vent pipe air space clearances to com-
bustibles are 1" on all sides except on the
horizontal sections, which requires 2" clear-
ance from the top of the pipe. Where the
termination cap penetrates a combustible
wall, 1" air space clearance is required.
• Snorkel terminations are required when
minimum clearance to grade cannot be
met (see Figure 16 on page 12).
• Have fireplace and selected vent compo-
nents on hand to help determine the exact
measurements when elbowing or offsetting.
Always use wall firestops when penetrating
walls and firestops when penetrating ceil-
ings or attic spaces.
INSTALLATION pRECAUTIONS
Wear gloves and safety glasses for protection
• Use extreme caution when using ladders
or when on roof tops
• Be aware of electrical wiring locations in
walls and ceilings
The following actions will void the warranty
on your venting system:
• Installation of any damaged venting com-
ponent
• Unauthorizedmodificationoftheventingsys-
tem (Do not cut or alter vent components)
• Installation of any component part not
manufactured or approved by FMI PROD-
UCTS, LLC
•
• Installation other than as instructed by
these instructions
WARNING: This gas fireplace
andventassemblymustbevented
directlytotheoutside.Theventing
system must NEVER be attached
to a chimney serving a separate
solid fuel burning appliance. Each
direct-ventgasappliancemustuse
aseparateventsystem.Donotuse
common vent systems.
• If using a venting configuration of only
horizontal venting with no vertical run, a
1/4" rise for every 12" of run toward the
termination is required.
WARNING:Ventpipeairspace
clearances to combustibles are
1" on all sides except on the hori-
zontal sections, which require 2"
clearances from the top of the
pipe. Where the termination cap
penetrates a combustible wall, 1"
air space clearance is required.
• For installation of fireplace at elevations of
4000 feet or greater, pay special attention
to venting requirement recommendations.
8
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTallaTION
Continued
5. Carefully determine location where vent
INSTALLATION pLANNING
pipe assembly will penetrate the outside
wall. The center of hole should line up with
center line of horizontal vent pipe. Mark
There are two basic types of direct-vent
installation:
• Horizontal Termination
• Vertical Termination
1
1
2
2
wall for a 11 / " x 11 / " square hole. Cut
and frame the square hole in exterior wall
where vent will be terminated. If wall being
penetrated is constructed of noncombus-
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall firestop.
Horizontal installations using round termina-
tion require exterior portion of wall firestop
available only in vent kit HTK (see Figure
14, page 11).
tible material, such as masonry block or
1
2
concrete, a 8 / " hole with zero clearance
is acceptable (see Figure 9).
WARNING: Do not recess
vent termination into any wall.
This will cause a fire hazard.
1. Set fireplace in its desired location and
determine the route your horizontal venting
will take. Do not secure fireplace until all
venting has been installed. Some installa-
tions require sliding fireplace in and out of
position to make final venting connections.
Figures 14 through 18 on pages 11 through
13 show different configurations for venting
with horizontal termination that will help you
decide which application best suits your
installation. Check to see if wall studs or
roof rafters are in the path of your desired
venting route. If they are, you may want to
adjust the location of the fireplace.
Female Locking Lugs
Male
Slots
2. Direct vent pipe sections and components
are designed with special twist-lock con-
nections.
Figure 8 - Vent Pipe Connections
Vent Opening
Combustible Wall
11 1
/2" Inside Framing
Twist-Lock procedure: Female ends of
pipes have locking lugs (indentations).
These lugs will slide straight into match-
ing slots on male ends of adjacent pipes.
Push pipe sections together and twist
one section clockwise approximately one-
quarter turn until sections are fully locked
(see Figure 8). Note: Horizontal runs of
vent must be supported every three feet.
Use wall straps for this purpose.
11 1
/2"
11 1
/2"
(Framing
Detail)
Vent Opening
Noncombustible Wall
3. Use a 45° elbow to connect venting sys-
tem to fireplace flue collar. The elbow is
designed to be twist-locked onto flue collar
as described in step 2. IMPORTANT: Do
not attempt to alter configuration of elbow
by cutting, twisting, bending, etc.
8 1
/2"
Center
of Hole
4. Assemble desired combination of pipe
and elbows to fireplace flue collar. If there
are long portions of venting run, preas-
sembled pipe sections may be installed
as subassemblies for convenience.
Figure 9 - Vent Opening Requirements
116646-01J
9
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTallaTION
Continued
6. Noncombustible Exterior Wall: Position
Slide wall firestop against interior wall
1
horizontal vent cap in center of the 8 /2"
surface and attach with screws provided
(see Figure 12). See Figure 13, page 11,
for horizontal termination details.
round hole and attach to exterior wall with
four screws (see Figure 10). Note: The four
wood screws provided should be replaced
with appropriate fasteners for stucco, brick,
concrete or other types of sidings. Before
attaching vent cap to exterior wall, run
a bead of non-hardening mastic (pliable
sealant) around outside edges to make a
seal between it and outside wall.
Place fireplace into position and shim with
noncombustible material if needed. Nail or
screw side flanges to framing to secure
unit in place. IMPORTANT: Make sure fire-
place is level before securing. If fireplace
is not level it will not work properly.
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding
standoff may be installed between vent
cap and exterior wall. Siding standoff
prevents excessive heat from damaging
siding materials. Siding material must be
cut to accommodate standoff. Bolt vent
cap to standoff. Apply non-hardening
mastic around outside edge of standoff.
Position standoff/cap assembly in center
Cut Siding Away to
Fit Standoff
Standoff
Wood Screw
Vent Cap
1
of the 11 /2" square hole and attach to
exterior wall with wood screws provided
(see Figure 11). Siding standoff must sit
flush against exterior fascia material.
Screws
7. Connecting Vent Cap with Horizontal
Vent Pipe: Slide wall firestop over vent
pipe before connecting horizontal run to
vent cap (see Figure 12).
Apply Mastic
to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior)
Carefully move fireplace, with vent as-
sembly attached, toward wall and insert
vent pipe into horizontal termination. The
pipe overlap should be a minimum of 1 1/4"
(see Figure 13, page 11).
Interior Wall
Surface
Wall
Firestop
Apply Mastic to
All Four Sides
Vent
Cap
Wood
Screw
Vent Cap
(Horizontal
Termination)
Screw
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
Horizontal
Vent Pipe
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
10
Download from Www.Somanuals.com. All Manuals Search And Download.
116646-01J
VENTING INSTallaTION
Continued
GROUND FLOOR INSTALLATION
Siding
Standoff
Recommended Applications:
• Installation using cabinet surrounds
Minimum Pipe
• Through the wall using round or square
termination (up to 12") adjustable pipe)
Screws
Overlap 1 1/4"
• NOT FOR CORNER INSTALLATION
Wall
45° Elbow
Horizontal High
Wind Square
Firestop
Termination
Adjustable
Pipe 12"
Max.
Direct Vent
Pipe
High Wind
Termination
Wall
Maintain 1"
Firestop
Minimum Air Space
Around Outer Pipe
When Penetrating
a Wall
Apply Mastic
to Outside
Edge of
Square Termination
Vertical (V) Horizontal (H)
Standoff
3
4
11 1/2" x 11 1/2"
29 / "
17" max.
Exterior Wall
with Vinyl Siding
Figure 13 - Typical Horizontal
Framed Opening
Exterior
Portion of Wall
Firestop (Round
Termination Only)
45° Elbow
Wall
Firestop
Termination Cap Mounting with
Additional Siding Standoff Installed
Horizontal Termination Configurations
Figures 14 through 18 show different configura-
tionsandalternativesforventingwithhorizontal
termination. Each figure includes a chart with
critical minimum and maximum dimensions
which MUST be met. IMPORTANT: If using a
venting configuration of only horizontal venting
with no vertical run, a 1/4" rise for every 12" of
run toward termination is required.
Slide Ring
Over Elbow
to Complete
Connection
NOTICE:Donotsealtermination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
Horizontal Round
Termination
Round Termination
(Kit HTK Shown)
Figure 14 - Horizontal Termination
Configuration for Square or Round
Termination
WARNING: Never run vent
downward as this may cause
excessive temperatures which
could cause a fire. Operation of
improperly installed and main-
tained venting system could
resultinseriousinjury, property
damage or loss of life.
116646-01J
11
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTallaTION
Continued
CORNER INSTALLATION
Recommended Applications:
• Corner ground floor installation
• Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
• Basement installation where one foot clearance from ground to termination is possible
Not to Exceed
(H) Limits
Square
Termination
90° Elbow
Not to Exceed
(H) Limits
90°
Elbow
Square
Termination
As Required
for (V), See
Chart for
Pipe Section
Required
Wall
12" Min.
Firestop
Wall
Firestop
45°
Elbow
45°
Elbow
Vertical (V)
Required
Vertical (V) Vertical Pipe Horizontal (H)
*43 3/4" min.
None
1 ft.
2 ft.
3 ft.
4 ft.
30" max.
48" max.
60" max.
84" max.
20' max.
53 3/4" min.
65 3/4" min.
77 3/4" min.
89 3/4" min.
* Ground Floor Corner Venting
Figure 15 - Horizontal Termination Configuration for Corner Installation Using One
90° Elbow
SNORKEL TERMINATION INSTALLATION
Snorkel terminations are available for instal-
lations requiring a vertical rise on exterior of
building. If installing snorkel termination below
grade, you must provide proper drainage to
prevent water from entering snorkel termina-
tion (see Figure 16). Do not back fill around
Recommended Applications:
• Installations requiring a vertical rise on
building exterior
• Any installation using snorkel termination
to achieve one foot above ground
snorkel termination.
Snorkel
Termination
Snorkel
Termination
Wall
Snorkel
Termination
Firestop
90° Elbow
12" Min.
12" Min.
12" Min.
Adequate
Drainage
Figure 16 - Snorkel Termination Configurations for Below Ground Installation
12
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTallaTION
Continued
HORIZONTAL SYSTEM INSTALLATION USING TWO 90° ELBOWS
The following configurations show the minimum vertical rise requirements for a horizontal
system using two 90° elbows.
Venting with Two 90° Elbows
Horizontal (H1) +
Vertical (V) Horizontal (H1) Horizontal (H2)
5' min.
6' min.
7' min.
8' min.
20' max.
2' max.
4' max.
6' max.
8' max.
8' max.
6' max.
12' max.
18' max.
20' max.
20' max.
45° Elbow
Figure 17 - Horizontal Termination Configuration for Venting Using Two 90° Elbows
Venting with Two 90° Elbows
Horizontal (H1) +
Vertical (V) Horizontal (H2)
5' min.
6' min.
7' min.
8' min.
20' max.
6' max.
12' max.
18' max.
20' max.
20' max.
45° Elbow
Figure 18 - Horizontal Termination Configuration for Venting Using Two 90° Elbows
with Termination at 90° with Fireplace
116646-01J
13
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTallaTION
Continued
Flat Ceiling Installation
INSTALLATION FOR vERTICAL
TERMINATION
Note: Vertical restrictor must be installed in
all vertical installations.
1
2
1. Cut a 11 / " square hole in ceiling using locat-
ing hole as a center point. Opening should be
1
1
2
2
framed to 11 / " x 11 / " inside dimensions,
as shown in Figure 9 on page 9 using framing
lumber the same size as ceiling joists. If area
above the ceiling is an insulated ceiling or an
attic, nail firestop from top side. This prevents
loose insulation from falling into required
clearance space. If area above ceiling is a
living space, install firestop below framed
hole. Firestop should be installed with no less
than 3 nails per side (see Figure 20).
1. Determine route your vertical venting
will take. If ceiling joists, roof rafters or
other framing will obstruct venting system,
consider an offset (see Figure 19) to avoid
cutting load bearing members. Note: Pay
special attention to these installation
instructions for required clearances (air
space) to combustibles when passing
through ceilings, walls, roofs, enclosures,
attic rafters, etc. Do not pack air spaces
with insulation. Also note maximum
vertical rise of venting system and any
maximum horizontal offset limitations.
2. Set fireplace in desired location. Drop a
plumb line down from ceiling to position
of fireplace exit flue. Mark center point
where vent will penetrate ceiling. Drill a
small locating hole at this point.
2. Assemble desired lengths of pipe and
elbows necessary to reach from fireplace
flue up through firestop. Be sure all pipe
and elbow connections are fully twist-
locked (see Figure 8, page 9).
3. Cut a hole in roof using locating hole as
a center point. (Cover any exposed open
vent pipes before cutting hole in roof.) The
1
1
2
2
11 / " x 11 / " hole must be measured
on the horizontal; actual length may be
larger depending on pitch of roof. There
must be a 1" clearance from vent pipe to
combustible materials. Frame opening as
shown in Figure 9, page 9.
Drop a plumb line from inside of roof to
locating hole in ceiling. Mark center point
where vent will penetrate roof. Drill a small
locating hole at this point.
4. Connect a section of pipe and extend up
through hole.
Note: If an offset is needed to avoid
obstructions, you must support vent pipe
every 3 feet. Use wall straps for this pur-
pose (see Figure 19). Whenever possible,
use 45° elbows instead of 90° elbows. The
45° elbow offers less restriction to the flow
of flue gases and intake air.
Roof
Flashing
Wall Strap
5. Place flashing over pipe section(s) ex-
tending through roof. Secure base of
flashing to roof and framing with roofing
nails. Be sure roofing material overlaps
top edge of flashing as shown in Figure
19. There must be a 1" clearance from
vent pipe to combustible materials.
45° Elbow
If area above is an
attic or insulated
If area above is a
living space, install
area, install firestop firestop below framed
above framed hole. hole.
Ceiling
Firestop
Figure 19 - Offset with Wall Strap and 45°
Elbows
Figure 20 - Installing Firestop
14
Download from Www.Somanuals.com. All Manuals Search And Download.
116646-01J
Venting with One 90° Elbow
Vertical (V) Horizontal (H)
VENTING INSTallaTION
Continued
5' min.
6' min.
7' min.
8' min.
20' max.
2' max.
4' max.
6' max.
8' max.
8' max.
6. Continue to add pipe sections until height
of vent cap meets the minimum building
code requirements described in Figure
7 on page 7. Note: You must increase
vent height for steep roof pitches. Nearby
trees, adjoining rooflines, steep pitched
roofs and other similar factors may cause
poor draft or down-drafting in high winds.
Increasing vent height may solve this
problem.
45° Elbow
7. Twist-lock vent cap onto last section of
vent pipe.
Note: If vent pipe passes through any occu-
pied areas above first floor, including storage
spaces and closets, you must enclose pipe.
You may frame and sheetrock enclosure with
standard construction material. Make sure
and meet minimum allowable clearances
to combustibles. Do not fill any required air
spaces with insulation.
Note: Install restrictor
into inner collar of
fireplace as shown.
Figure 22 - Vertical Venting Configuration
Using One 90° Elbow (Vertical Round
High Wind Termination Shown)
Vertical Termination Configurations
Figures 21 through 24 show four different
configurations for vertical termination.
Venting with Two 90° Elbows
Horizontal (H1) +
Vertical (V) Horizontal (H2)
5' min.
6' min.
7' min.
8' min.
20' max.
2' max.
4' max.
6' max.
8' max.
8' max.
Note: Install
restrictor into inner
collar of fireplace
as shown.
45° Elbow
45° Elbow
Note: Install
restrictor into
inner collar of
fireplace as
shown.
Venting with Two 90° Elbows
vertical (v1) Horizontal (H)
5' min.
6' min.
7' min.
8' min.
6' max.
12' max.
18' max.
20' max.
Figure 21 - Vertical Venting
Configuration Using Two 90° Elbows
with Two Horizontal Runs (Vertical
Round High Wind Termination Shown)
Note: Vertical (V1) + Vertical (V2) = 40' max.
Figure 23 - Vertical Venting Configuration
Using Two 90° Elbows (Vertical Round
High Wind Termination Shown)
116646-01J
15
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTallaTION
Continued
starter elbow (see Figure 25) and a round
horizontal termination be used.
45° Starter
Elbow
12"
Extension
Vertical Venting
V = 40' max.
Figure 25 - Recommended 12" Extension
for High Altitude Installation
Note: Install
restrictor into inner
collar of fireplace
as shown.
PARTS LIST FOR VENTING KITS
AND COMpONENTS
FMI PRODUCTS, LLC (5"/8") Pipe & Vent Kits
Number Description
P58-6
6" Section Double Wall Pipe,
Galvanized
P58-12 12" Section Double Wall Pipe,
Galvanized
45° Elbow
P58-24 24" Section Double Wall Pipe,
Galvanized
P58-36 36" Section Double Wall Pipe,
Galvanized
P58-48 48" Section Double Wall Pipe,
Galvanized
PA58-712 Adjustable 7"-12" Section Double
Wall Pipe, Galvanized
Figure 24 - Vertical Venting Configuration
With No Horizontal Run (Vertical Round
High Wind Termination Shown)
E58-45 45° Elbow, Galvanized
E58-90 90° Elbow, Galvanized
VKG-58 Ground Floor Vent Kit, Galvanized
(Includes: 45° Elbow, 7"-12" Adjust-
able Pipe, Wall Firestop, Horizontal
Square Termination, 16 Screws)
VKB-58 Basement Vent Kit, Galvanized
(Includes: 45° Elbow, 7"-12"
HIGH ALTITUDE INSTALLATION
Your FMI PRODUCTS, LLC direct-vent
fireplace has been tested and approved for
elevations from 0-2000 feet (USA).
Fireplaces for High Altitude (models ending
in -HA) are for installation above 4000 feet
only. These fireplaces are equipped with parts
specific for higher altitudes.
Adjustable Pipe, Wall Firestop,
Horizontal Square Termination, 4'
Pipe, 90° Elbow, 20 Screws)
When installing a non-high altitude fireplace
at an elevation above 2000 feet (in the USA),
you may need to decrease the input rating
by changing the existing burner orifice to a
smaller size. Reduce input 4% for each 1000
feet above sea level. Check with your local gas
company for proper orifice size identification.
IMPORTANT: For horizontal installations
above 2,000 feet, it is recommended that
a 12" extension pipe be added before
VKS-58 Snorkel Vent Kit, Galvanized (Includes:
45° Elbow, 7"-12" Adjustable Pipe,
Wall Firestop, 36" Snorkel Termination,
4' Pipe, 1' Pipe, 90° Elbow, 26 Screws)
VKR-58 Roof Vent Kit, Galvanized (Includes:
45° Elbow, 7"-12" Adjustable Pipe,
Flue Restrictor, Vertical High Wind
Termination, 2' Pipe, 4' Pipe, Wall
Firestop, Storm Collar, Roof Flash-
ing [0/12 - 6/12], 26 Screws)
16
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTallaTION
Continued
Number Description
Number Description
VKC-58 Corner Vent Kit, Galvanized
(Includes 45° Elbow, 7"-12"
ST-58-14 14" Snorkel Termination, Galva-
nized
Adjustable Pipe, Wall Firestop,
Horizontal Termination, 6" Pipe,
90° Elbow, 18 Screws)
ST-58-36 36" Snorkel Termination, Galvanized
SC-58
WF-58
Storm Collar, Galvanized
Wall Firestop, Galvanized
HHTK-58 High Wind Round Horizontal Termi-
nation Kit (Includes Round Termina-
tion, Wall Firestop, 45° Elbow)
RF-58-6 Roof Flashing - 0 to 6/12 Pitch,
Galvanized
RF-58-12 Roof Flashing - 6/12 to 12/12
Pitch, Galvanized
HHT-58
High Wind Round Termination
Kit, Galvanized
VR-58
S-58
Vertical Restrictor, Galvanized
Vinyl Siding Standoff, Galvanized
Wall Strap
HTK-58
Horizontal Round Termination
Kit (Includes Round Termination, WS-58
Wall Firestop, 45° Elbow)
Horizontal Round Termination,
Galvanized
Horizontal Square Termination,
Galvanized
CS-58
FP-58
SF-58
Cathedral Ceiling Support
Firestop Plate
Stucco Flashing - For use with
HTS-58
HT-58
HTS-58
RF-58
Flat Roof Flashing
HTKS-58 Horizontal Square Termination
Kit (Includes: Square Termina-
PF58-927 Flex Pipe Section 9" to 24"
PF58-1236 Flex Pipe Section 12" to 36"
PF58-1854 Flex Pipe Section 18" to 54"
tion, Wall Firestop, 45° Elbow)
HTS-58
VT-58
Horizontal Square Termination,
Galvanized
Vertical Round Termination,
Galvanized
VKF58-927 Flex Kit (Includes Flex Pipe Wall
Section 9" to 27", Firestop and
Horizontal Square Termination)
FIREplaCE INSTallaTION
Model BK Installation
CHECK GAS TYPE
Follow all instructions provided in blower
accessory kit.
Use proper gas type for fireplace unit you are
installing. If your gas supply is not correct, do
not install fireplace. See retailer where you
purchased fireplace for proper fireplace ac-
cording to your gas type or to purchase gas
conversion kit (see Accessories, page 37).
1. Attach power cord to blower motor by
firmly pushing two female terminals at end
of power cord onto two spade terminals
on blower motor (see Figure 26).
2. Attach green ground wire from power cord
to blower housing using screw provided
(see Figure 26). Tighten screws securely.
INSTALLING OpTIONAL bLOWER
ACCESSORY
3. Place blower against lower rear wall of
firebox outer wrapper with exhaust port
directed upward. Blower will fit inside back
opening and be held in position against
back wall by magnets (see Figure 26).
NOTICE: If installing blower in
an existing fireplace with gas
connections, shut off gas sup-
ply and disconnect heater from
gas supply. Contact a qualified
service person to do this.
Blower
Location
Side View
Lower Firebox
Magnetic
Strips
Cavity
WARNING: If there is a duplex
electrical outlet installed in the
right side of the bottom of the
fireplace base area, be sure that
theelectricalpowertotheoutletis
turnedoffbeforeproceedingwith
blower installation. Failure to do
this may result in serious injury.
Spade
Terminals
Green
Ground
Wire
Screw
Exhaust
Port
Figure 26 - Blower Model BK
116646-01J
17
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREplaCE INSTallaTION
Continued
4. Be certain that all wire terminals are 9. Check to make sure that power cord is
securely attached to terminals on blower
motor and that screw retaining green
ground wire is tight.
completely clear of blower wheel and
that there are no other foreign objects in
blower wheel. Turn blower on and check
for operation. Turn blower off by turning
knob fully counterclockwise before con-
tinuing.
5. Mount speed control box to switch bracket
by placing plastic control shaft forward
through opening in switch bracket (see
Figure 27).
10. Peel off backing paper and stick supplied
wiring diagram decal on firebox bottom
approximately 12" in front of blower (see
Figure 28).
6. While supporting speed control, secure
control shaft with lock nut by pushing
and turning lock nut with pliers clockwise
until it is tight against front panel. Place
provided control knob on shaft.
7. Turn on power to duplex outlet if previ-
ously turned off per warning in column 2,
page 17.
8. Plug in blower power cord.
a. If your firebox is installed as a free-
standing unit with an accessory man-
tel, determine whether power cord will
exit left side or right side of firebox.
Route power cord through exit hole
and plug power cord into a wall recep-
tacle near firebox.
Wiring Diagram
Decal 12" in Front
of Blower
Figure 28 - Location of Wiring Diagram
Decal (Model May Vary From Illustration)
b. If your firebox installation is recessed
and/or prewired, plug power cord into
duplex outlet provided. Refer to your
firebox owner’s manual for instructions
on wiring duplex outlet.
Model BKT Installation
Note: When installing BKT thermostati-
cally controlled blower, you must first secure
thermal switch bracket to blower if it has not
already been factory installed.
1. Place green ground wire with ring ter-
minal between bottom hole on thermal
switch bracket and top ear hole on blower
assembly. Insert Phillips screw into all
three pieces and tighten securely (see
Figure 29, page 19).
CAUTION:Nevertouchblow-
er wheel while in operation.
Duplex Outlet
(Located underneath
firebox floor against
lower right outside wall)
Speed
Control
Switch
Bracket
2. Connect wire harness and power cord ter-
minals. Connect blue jumper wire to blower
motor terminal and right side terminal of
thermal switch. Connect black wire to left
side of thermal switch and white wire to
other remaining blower motor terminal.
Note: The power cord outer insulation sleeve
may have to be stripped slightly to allow
enough wire length to reach and make all
connections. DO NOT trim excessive length
away. Enable just enough to make all con-
nections securely.
Blower
Plug-In
Control
Shaft
Locknut
Control
Knob
Figure 27 - Attaching Speed Control to
Firebox
18
Download from Www.Somanuals.com. All Manuals Search And Download.
116646-01J
FIREplaCE INSTallaTION
Continued
3. Place blower against lower rear wall of 7. Check to make sure that power cord is
firebox outer wrapper with exhaust port di-
rected upward and thermodisc positioned
up near fireplace bottom. Thermodisc
must be oriented near fireplace bottom
as shown in Figure 29, in order to sense
temperature and properly operate. Blower
will be held in position against back wall
by magnets incorporated onto blower
housing (see Figure 29).
completely clear of blower wheel and
that there are no other foreign objects in
blower wheel. Also double check all wire
leads and make sure wire routing is not
pinched or in a precarious position. Cor-
rect accordingly.
8. Turn on power to duplex outlet if previ-
ously turned off per warning in column 2,
page 17.
4. Be certain that all wire terminals are
securely attached to terminals on blower
motor and thermal switch and that screw
for thermodisc bracket and green ground
wire is tight.
9. Plug in blower power cord to duplex
outlet.
10. Blower will only run when speed control
knob is in the ON position and thermal
switch senses temperature after fireplace
begins to heat up. Blower speed can be
adjusted by rotating control knob. To turn
off, turn knob fully counterclockwise until
it clicks off. If blower is ON and has been
running with fireplace operating, blower
will continue to run for a short time after
fireplace has been turned off. As thermal
switch cools down, blower shuts down
automatically.
5. Mount speed control box against mount-
ing plate provided in lower fireplace
cavity by placing plastic control shaft
forward through round hole (see Figure
27, page 18).
6. While supporting speed control, secure
control shaft with lock nut by pushing and
turning lock nut with pliers clockwise until
it is tight against mounting plate. Place
control knob provided on shaft (see Figure
27, page 18).
11. Peel off the backing paper and stick the
supplied wiring diagram decal on the
firebox bottom approximately 12" in front
of the blower (see Figure 28, page 18).
Power Cord White
Blue
Wire
Wire
Blower Wiring Diagram
Black
Magnetic
Strips
Air Flow
Direction
Wire
Thermal
Switch
CAUTION: Label all wires
prior to disconnection when
servicingcontrols.Wiringerrors
can cause improper and dan-
gerous operation. Verify proper
operation after servicing.
Thermal
Switch
Bracket
Ring
Terminal on
Green Wire
Phillips
Screw
Variable
Fan Switch
(N.O.)
Fan Switch
1
Air Flow
Direction
Route BKT Blower
Through This Area
Off
Black
2
On
110/115
V. A.C.
Blue
Black
White
Green
Thermodisc
Side View Firebox Bottom
Blower
Blower
Motor
Magnets
Figure 30 - Blower Wiring Diagram for
Thermostat-Controlled Models
Location
Figure 29 - Blower Model BKT
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
19
FIREplaCE INSTallaTION
Continued
fireplace regulator damage could occur. Install
INSTALLING GAS pIpING TO
FIREpLACE LOCATION
external regulator with the vent pointing down
as shown in Figure 31. Pointing the vent down
protects it from freezing rain or sleet.
WARNING: A qualified
service person must connect
fireplace to gas supply. Follow
all local codes.
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2"insidediameterorgreaterto
allow proper gas volume to fire-
place. If pipe is too small, undue
loss of volume will occur.
CAUTION: For propane/LP
units,neverconnectfireplacedi-
rectly to the propane/LP supply.
This heater requires an external
regulator (not supplied). Install
the external regulator between
the fireplace and propane/LP
supply.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPTtap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from fireplace (see
Figure 32, page 21).
WARNING: For natural
gas, never connect heater to
private (non-utility) gas wells.
This gas is commonly known
as wellhead gas.
IMPORTANT: Install main gas valve (equip-
ment shutoff valve) in an accessible location.
The main gas valve is for turning on or shutting
off the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to fireplaces.
Installation Items Needed
Before installing fireplace, make sure you
have the items listed below.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged fireplace valves.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
• tee joint
• pipe wrench
Propane/LP
Supply Tank
External
• approved flexible gas line with gas connec-
Regulator
with Vent
Pointing
Down
tor (if allowed by local codes)
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the equipment shutoff
valve from your retailer.
For propane/LP connection only, the installer
must supply an external regulator. The ex-
ternal regulator will reduce incoming gas
pressure. You must reduce incoming gas
pressure to between 11" and 14" of water. If
you do not reduce incoming gas pressure,
Figure 31 - External Regulator with Vent
Pointing Down (Propane/LP Only)
20
Download from Www.Somanuals.com. All Manuals Search And Download.
116646-01J
FIREplaCE INSTallaTION
Continued
We recommend that you install a sediment
To Gas Supply
(Natural)
trap/drip leg in supply line as shown in Figure
32. Locate sediment trap/drip leg where it is
within reach for cleaning. Install in piping sys-
tem between fuel supply and fireplace. Locate
sediment trap/drip leg where trapped matter
is not likely to freeze. A sediment trap traps
moisture and contaminants. This keeps them
from going into fireplace gas controls. If sedi-
ment trap/drip leg is not installed or is installed
wrong, fireplace may not run properly.
Equipment
Shutoff
Valve
Control Valve
To External
Regulator
(Propane/LP)
Flexible Gas Line
Do NOT Kink
Equipment Shutoff Valve with
Figure 33 - Connecting Flexible Gas Line
1/8" NPT Tap*
Natural - From
to Millivolt Valve
Gas Meter (5.5"
W.C. to 10.5"
W.C. Pressure)
Propane/LP
From External
Regulator (11"
W.C. to 14"
CHECKING GAS CONNECTIONS
WARNING:Testallgaspiping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
Approved
Flexible Gas
Line
W.C. Pressure)
3" Minimum
WARNING:Neveruseanopen
flame to check for a leak. Apply
noncorrosive leak detection fluid
toalljoints.Bubblesformingshow
a leak. Correct all leaks at once.
Cap Pipe Nipple Tee Joint
Sediment Trap/Drip Leg
Figure 32 - Gas Connection
* The equipment shutoff valve may be sup-
plied with the appliance or you can purchase
it from your retailer.
pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
CONNECTING FIREpLACE TO GAS
SUppLY
1. Disconnect fireplace and its individual equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig (3.5
kPa) will damage fireplace gas regulator.
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LPgas fireplace or opening main gas
valve located on or near gas meter for natural
gas fireplace or using compressed air.
4. Check all joints of gas supply piping sys-
tem. Apply noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not
provided)
1. Open lower louver door panel by gently
pulling forward.
2. Route flexible gas line (provided by in-
staller) from equipment shutoff valve to
fireplace. Route flexible gas supply line
through one of the access holes on side
of fireplace.
3. Attach flexible gas line from gas supply to
control valve (see Figure 33).
5. Reconnect fireplace and equipment
shutoff valve to gas supply. Check recon-
nected fittings for leaks.
4. Check all gas connections for leaks. See
Checking Gas Connections.
116646-01J
21
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREplaCE INSTallaTION
Continued
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig- 1. Open equipment shutoff valve (see Fig-
ure 34). ure 34).
2. Pressurize supply piping system by either 2. Open main gas valve located on or near
pRESSURE TESTING FIREpLACE GAS
CONNECTIONS
opening propane/LP supply tank valve for
propane/LPgas fireplace or opening main gas
valve located on or near gas meter for natural
gas fireplace or using compressed air.
gas meter for natural gas or open supply
tank valve for propane/LP gas.
3. Make sure control knob of fireplace is in
the OFF position.
3. Check all joints from propane/LP supply
tank for propane/LP or gas meter for
natural gas to equipment shutoff valve
(see Figure 35 or Figure 36). Apply non-
corrosive leak detection fluid to all joints.
Bubbles forming show a leak. Correct all
leaks at once.
4. Check all joints from equipment shutoff
valve to gas valve (see Figure 35 or Figure
36). Apply noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Light fireplace (see Operation, page 26).
Check all other internal joints for leaks.
6. Turn off fireplace (see To Turn Off Gas to
Appliance, page 27).
Equipment
Shutoff Valve
Open
INSTALLING OpTIONAL WALL
MOUNT SWITCH - GWMS2
1. Connect one terminal of 25 ft. wire for
wall switch to TPTH terminal on valve.
Connect remaining wire terminal to TH
terminal on valve. Make sure that wire ter-
minals are in positions on unit as pictured
in Figure 37. If wires are not connected as
shown the switch will not work.
Closed
Figure 34 - Equipment Shutoff Valve
Equipment Shutoff Valve
Propane/LP
Supply Tank
2. Route 25 ft. wire through openings pro-
vided on sides of burner system to a con-
venient location to mount your switch.
3. Connect one bare wire end to each of the
terminals of the GWMS2 wall switch.
4. Install wall switch and cover in wall.
Gas Valve
To Wall
Switch
Accessory
Figure 35 - Checking Gas Joints for
Propane/LP Gas Fireplace
Equipment Shutoff Valve
Figure 37 - Connecting Wall Switch to
Control Valve
Gas
Meter
Gas Valve
Figure 36 - Checking Gas Joints for
Natural Gas Fireplace
22
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
Battery Cover
Remote Control Unit
FIREplaCE
INSTallaTION
Continued
INSTALLING OpTIONAL WIRELESS
HAND-HELD REMOTE CONTROL
HRC100 AND HRC200 SERIES
Terminal
Wires
Battery
Housing
9-Volt
Battery
NOTICE: Use only alkaline bat-
teries (not included).
Figure 40 - Installing Battery in Hand-
Installing Remote Receiver
1. Open bottom louver and locate switch
bracket on the left.
Held Remote Control Unit
REMOvING/REpLACING GLASS
DOOR
2. Unscrew switch bracket. Lean bracket
forward so you are able to access the
back of remote receiver.
CAUTION: Do not operate
thisfireplacewithabrokenglass
door panel or without the glass
doorpanelsecurelyinplace. For
replacementpartinformationsee
Replacement Parts, page 36.
3. Locate battery clip mounted on back of
receiver. Slide a 9-volt alkaline battery (not
included) through the clip (see Figure 38).
4. Attach terminal wires to battery.
5. Connect wires from receiver to TH and
TPTH to control valve (see Figure 39).
6. Replace switch bracket.
CAUTION: Wear gloves and
safety glasses while handling or
removingbrokenglass.Donotre-
moveifglassishot.Keepchildren
and pets away from glass.
Receiver
9-Volt
Alkaline
Battery
Terminal
Wires
WARNING: If fireplace has
been running, turn off and un-
plugfireplace.Letcoolbeforere-
moving glass door or louvers.
Battery Clip
Figure 38 - Attaching Alkaline Battery to
Receiver
Removing Louver Panels
Remove top and bottom louver panels by
simultaneously pulling both top end spring
latches towards center of appliance until
they are disengaged from locating holes
(see Figure 41). Repeat for bottom spring
latches and pull louvers outward. To install
or replace items removed, simply reverse
procedures above.
To Optional
Remote
Accessory
Figure 39 - Control Valve Terminals
Installing 9-Volt Alkaline Battery in Hand-
Held Remote Control Unit
1. Remove battery cover on back of remote
control unit (see Figure 40).
2. Attach terminal wires to battery. Place
battery into battery housing.
Spring Latch
3. Replace battery cover onto remote control
unit.
Louver Panel
Figure 41 - Removing Louver Panel
116646-01J
23
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREplaCE INSTallaTION
Continued
Removing Glass Door
INSTALLING OPTIONAL BRICK
LINER MODEL BL32D
If replacement of glass is necessary, the
entire assembly, glass and frame, must be
replaced. If glass is broken, wear gloves and
tape remaining fragments onto frame.
WARNING: If fireplace has
been running, turn off and un-
plug fireplace. Let cool before
installing brick liner.
1. Remove screen/rod assembly from fire-
box, push rod either left or right and then
down and forward. Set assembly aside.
2. Lift up on latches to unlock. There are
two on top of firebox and two below
firebox that hold glass door in place (see
Figure 42).
This brick liner kit is optional. You may pur-
chase brick liner from your local retailer or
see page 37.
3. While holding glass door to prevent it from
falling and causing injury, remove the five
screws from hinge located on left side of
door frame assembly (see Figure 42).
CAUTION: Always handle
brick panels with two hands.
Do not force brick panels into
place.Excessiveforcewillbreak
brick panels.
4. Remount new frame at hinge with five
new screws before closing door. This will
ensure seating of gasket.
1. Remove top and bottom louvers to allow
access to door latches.
5. Close glass door frame. Lock latches by
placing bar under tab on door and pushing
down and back on latch (see Figure 42).
2. Unlock door latches and open glass door.
See steps 1 and 2 of Removing/Replacing
Glass Door, page 23.
6. Replace screen/rod assembly by revers-
ing step 1.
3. If installing brick liner in new fireplace,
go to step 4. If installing brick liner in an
existing fireplace, carefully remove logs,
lava rock and ember material.
7. Replace louvers by reversing procedure
under Removing Louver Panels, page 23.
Unlock
Lock
4. Remove three screws from deflector
shield on the inside top of firebox. Set
shield and screws aside.
Latch
Screw
5. Install rear brick panel first. Rest bottom
edge of panel on back edge of grate (see
Figure 43).
6. Install left side brick panel by sliding it
between grate and side of firebox (see
Figure 43).
Rear Brick
Panel
Hinge
Glass Frame
Assembly
Figure 42 - Removing/Replacing Glass
Door
Cleaning Glass Door
See Cleaning and Maintenance on page 31.
Figure 43 - Installing Rear Brick Panel
24
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREplaCE INSTallaTION
Continued
7. Install right brick panel using the same 5. Place log #5 (base log) onto front left part of
method described in step 5 for left brick
panel.
grate making sure notches fit over prongs
of grate). See Figure 49, page 26.
8. Replace deflector shield using screws
removed in step 4.
9. Follow instructions below to install logs,
lava rock and ember material.
1
10. Close glass door, lock latches on top and
bottom of door and replace screen (see
steps 5 and 6 of Removing Glass Door,
page 24).
11. Close top and bottom louvers.
Figure 45 - Installing Log No. 1
Left Side
Brick Panel
2
Figure 44 - Installing Side Brick Panels
INSTALLING LOGS, LAVA ROCK
AND GLOWING EMbERS
Each log is marked with a number. These
numbers will help you identify the log when
installing. It is very important to install these
logs exactly as instructed. Do not modify logs.
Only use logs supplied with fireplace.
Figure 46 - Installing Log No. 2
Open louvers, remove screen, unlock door
latches and open glass door. See steps 1 and
2 of Removing Glass Door, page 24. Install
logs according to instructions for fireplace
model numbers.
3
1. Place log #1 (rear log) on top of grate.
Make sure notches in bottom of log fit
over grate (see Figure 45).
2. Rest log #2 (large front log) on pins on
front part of grate (see Figure 46).
3. Place log #3 (crossover log) onto rear and
front logs. Make sure it is seated properly
on smooth surface on front log and on pin
on back log as shown in Figure 47.
4. Placelog#4(rightlog)onpinonrightsideof
front log as shown in Figure 48, page 26.
Figure 47 - Installing Log No. 3
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
25
FIREplaCE INSTallaTION
Continued
6. Place log #6 (left log) onto two pins
in one area. Do not block pilot ports with
embers. It is not necessary to use all of
the ember material provided.
on left side of back and front log. See
Figure 49.
7. Place lava rock along sides and front of 9. Close glass door, lock door latches,
firebox bottom in areas that are visible
only. It is not necessary to use all of the
lava rock provided.
replace screen and close louvers (see
steps 5 and 7 of Removing Glass Door,
page 24).
6
8. Pull ember material apart into pieces no
larger than a dime. Place these pieces
loosely and sparingly directly onto ex-
posed section of front burner and along
space between burner and grate prongs
(see Figure 50). This will create the
glowing ember appearance as the flame
touches the ember material. Do not block
air slots by using too much ember material
5
4
Figure 49 - Installing Logs No. 5 and No. 6
Ember Material
Figure 50 - Placing Ember Material on
Burner
Figure 48 - Installing Log No. 4
OpERaTION
WHAT TO DO IF YOU SMELL GAS
FOR YOUR SAFETY
•
•
•
•
Do not try to light any appliance.
Do not touch any electric switch.
Do not use any phone in your building.
Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
READ bEFORE LIGHTING
WARNING: If you do not fol-
low these instructions exactly,
a fire or explosion may result
causing property damage, per-
sonal injury or loss of life.
•
If you cannot reach your gas sup-
plier, call the fire department.
C. Use only your hand to push in or turn
the gas control knob. Never use tools.
If the knob will not push in or turn by
hand, don'ttrytorepairit, callaqualified
service technician. Force or attempted
repair may result in a fire or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call
a qualified service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
A. This appliance is equipped with an
ignition device which automatically
lights the pilot. Do not try to light the
pilot by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the floor because some
gas is heavier than air and will settle
on the floor.
26
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
OpERaTION
Continued
LIGHTING
INSTRUCTIONS
TO TURN OFF GAS
TO AppLIANCE
1. STOP! Read the safety information on 1. Open lower louver panel.
page 26.
2. Set selector switch in the OFF position to
prevent draining battery.
2. Open lower louver panel.
3. Turn off all electric power to fireplace.
4. Push in gas control knob slightly and turn
3. Turn off all electrical power to appliance
if service is to be performed.
clockwise
to OFF.
4. Push in gas control knob slightly and turn
clockwise
to OFF.
5. Wait five (5) minutes to clear out any gas.
Then smell for gas, including near the 5. Close lower louver panel.
floor. If you smell gas, STOP! Follow “B”
MANUAL LIGHTING
in the safety information on page 26. If
you don't smell gas, go to the next step.
pROCEDURE
1. Remove glass door (see Removing/Re-
placing Glass Door, page 24).
6. The pilot is located by the main burner and
should not require accessing for lighting.
2. Follow steps 1 through 8 under Lighting
Instructions.
7. Turn gas control knob counterclockwise
to PILOT (see Figure 51).
3. Press gas control knob and light pilot with
match.
8. Push in gas control knob all the way and
hold. Immediately light the pilot by repeat-
edly pressing the piezo spark ignitor until
a flame appears. Continue to hold for
about 1 minute after pilot is lit. Release
gas control knob and it will pop back. Pilot
should remain lit. If it goes out, repeat
steps 4 through 8.
4. Keep gas control knob pressed in for
30 seconds after lighting pilot. After 30
seconds, release gas control knob. Fol-
low steps 10 through 13 under Lighting
Instructions.
5. Replace glass door (see Removing/Re-
placing Glass Door, page 23).
•
Ifgascontrolknobdoesnotpopupwhen
released, stop and immediately call your
service technician or gas supplier.
OpTIONAL HAND-HELD
REMOTE OpERATION
Note: All remote control accessories must
be purchased separately (see Accessories,
page 37). Follow instructions included with
the remote control.
•
If pilot will not stay lit after several tries,
turn gas control knob to OFF and call
your service technician or gas supplier.
9. Turn on all electric power to fireplace.
10. Turn gas control knob counterclockwise
to ON.
NOTICE:Youmustlightthepilot
before using the hand-held re-
mote control unit. See Lighting
Instructions.
11. This valve is equipped with a HI/LO fea-
ture. Set fireplace input as desired.
12. To leave pilot lit and shut off burners only,
turn control knob clockwise
to the
PILOT position or set selector switch in
the OFF position.
After lighting, let pilot flame burn for about
one minute. Turn control knob to ON posi-
tion. Adjust flame adjustment knob anywhere
between HI and LO. Slide selector switch to
the REMOTE position (see Figure 52, page
28). Note: The burner may light if hand-held
remote was on when selector switch was last
turned off. You can now turn the burner on and
off with the hand-held remote control unit.
13. Close lower louver panel.
Gas Control
Knob
Variable Control Knob
H
T
IMPORTANT: Do not leave selector switch in
the REMOTE or ON position when the pilot
is not lit. This will drain the battery.
Piezo Ignitor
Figure 51 - Control Valve
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
27
OpERaTION
Continued
Blower Control Knob
(Optional Accessory)
Manual Mode
1. Press the POWER and LOCK buttons
together to turn on the hand-held remote
control.
Variable
Control Knob
OFF
ON
2. Press the MANU button to turn on the
fireplace.
H
P
3. Press the POWER and LOCK buttons
together to turn off the fireplace.
Gas Control Knob
in ON Position
Auto (Thermostatic) Mode
1. Press the POWER and LOCK buttons
together to turn on the hand-held remote
control.
Selector Switch in
Remote Position
Figure 52 - Setting Selector Switch, Gas
Control Knob and Variable Control Knob
for Remote Operation
2. Press AUTO button to select this mode.
3. Set the desired room temperature by
pressing the TEMP + or - buttons.
ON/OFF SERIES
4. Press the POWER and LOCK buttons
together to turn off the fireplace.
(Model HRC100 and HRC101)
Hold control button on hand-held remote until
burner turns on. Hold control button again until
burner turns off (see Figure 53).
Note: Do not leave the hand-held remote in
the AUTO mode close to the fireplace. The
radiant heat from the fireplace will turn off the
fireplace. Ideally, place the hand-held remote
in the center of the room facing towards the
fireplace.
TO LOCK press both buttons on hand-held
remote control until light stops flashing. Hand-
held remote control is now locked. If the fire
is on it will be turned off automatically. In the
locked state, the light will not light up when
any button is pressed.
Note: Do not hold the hand-held remote for
a long time. Body temperature will affect its
operation in the AUTO mode.
TO UNLOCK press both buttons together
on hand-held remote control until the light
stops flashing. The hand-held remote is now
unlocked.
Safety Features
When away from home for an extended period
of time or as a child safety feature to prevent
accidental ignition of the fireplace, the receiver
ON/OFF/REMOTE switch should be in the
Indicator
Light
OFF position.
Control
Button
Digital Display Shows
Temperature and Settings
Locks
System to
Turns
AUTO
SET
TEMP
Prevent
Accidental
Ignition
ROOM
TEMP
Hand-Held
Remote On
or Off and
Allows You
to Choose
the Manual
Setting
TEMP
ºC/ºF
LOCK
POWER
Figure 53 - On/Off Hand-Held Remote
Turns
Burners
On or Off
Control Unit (HRC100/HRC101)
MANU
AUTO
THERMOSTAT SERIES
(Model HRC200 and HRC201)
Increases or
Decreases
Room
Temperature
in AUTO
Selects
AUTO
Mode
The hand-held remote can be operated using
either the manual mode (MANU) or thermo-
static mode (AUTO) (see Figure 54). To select
Fahrenheit/Centigrade mode display, carefully
press the ˚C/˚F mode button with the end of a
paper clip or similar blunt object.
Mode
°C/°F Mode Button
Figure 54 - Thermostat Hand-Held
Remote Control Unit (HRC200/HRC201)
28
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
OpERaTION
Continued
Auto Shutoff Feature
This thermostat has been electronically cali-
1. If the average room temperature reaches brated at the factory and requires no adjust-
a range of 82° F (28° C) to 92° F (33° C), ment or leveling.
the hand-held remote control will perform
a safety override and shut the fireplace off.
This feature is not available in the MANU
mode.
Upon installation, thermostat must be allowed
to stabilize at room temperature for a mini-
mum of 30 minutes for proper operation.
To turn fireplace off, adjust thermostat to the
lowest setting and turn gas control knob back
to PILOT. The pilot will remain lit.
2. The receiver continuously receives sig-
nals from the hand-held remote to control
the room temperature. If the hand-held
remote is misplaced, obstructed or for any
reason cannot transmit to the receiver, the
receiver will shut off the fireplace. This will
occur in 8 or more minutes depending
upon location of remote transmitter and
strength of batteries.
IMPORTANT: To turn pilot off, turn gas control
knob on heater to the OFF position.
OpERATING OpTIONAL
bLOWER ACCESSORY
Locate blower controls by opening lower
louver panel on fireplace. Blower controls are
located on the right side of switch bracket to
the left just inside louver panel.
Key Pad Lock Feature
This feature allows the user to lock/unlock the
keypad on the hand-held remote in the MANU
or AUTO mode to prevent inadvertent op-
eration (i.e. children operating the hand-held
remote control, etc.). The keypad is locked in
either on or off. Press the POWER and LOCK
buttons together to turn the unit on or off.
The BK manual blower and BKT thermostati-
cally-controlled blower have an ON setting
and an OFF setting. Blower will only run when
the switch is in the ON position. In the OFF
position, blower will not operate.
Note for BKT Only: If you are using BKT
blower with optional thermostat (wall mounted
or remote control) for the fireplace, your fire-
place and blower will not turn on and off at
the same time. Fireplace may run for several
minutes before blower turns on. After heater
modulates to the pilot position, blower will
continue to run. Blower will shut off after
firebox temperature decreases.
OpERATING OpTIONAL
GWMT1 WALL MOUNTED
THERMOSTAT
WARNING: Do not con-
nect the thermostat to a power
source. Electrical shock and/or
a fire hazard will occur.
The blower helps distribute heated air from the
fireplace. Periodically check louvers of firebox
and remove any dust, dirt or other obstruc-
tions that will hinder the flow of air.
Light the fireplace as instructed in Lighting
Instructions on page 27. Set wall thermostat
to desired temperature.
INSpECTING bURNERS
Check pilot flame pattern and burner flame pilot burner must extend beyond both the
patterns often.
thermocouple and thermopile.
pILOT ASSEMbLY
Pilot
Burner
Thermopile
3/8" to 1/2"
The pilot assembly is factory preset for the
proper flame height. Alterations may have
occurred during shipping and handling. Call
a qualified service person to readjust the pilot
if necessary.
1/8"
Piezo
Ignitor
Thermocouple
The height of the thermopile must be 3/8"
to 1/2" above pilot flame as shown in Figure
55. The thermocouple must be at a height of
about 1/8" above pilot flame. The flame from
Figure 55 - Pilot Assembly
116646-01J
29
Download from Www.Somanuals.com. All Manuals Search And Download.
INSpECTING bURNERS
Continued
If you pilot assembly does not meet these Figure 56 shows a typical flame pattern.
requirements:
If burner flame pattern differs from that de-
• turn fireplace off (see To Turn Off Gas to scribed:
Appliance, page 27)
• turn fireplace off (see To Turn Off Gas to
Appliance, page 27)
• see Troubleshooting, page 32
• see Troubleshooting, page 32
bURNER FLAME pATTERN
Burner flames will be steady, not lifting or float-
ing. Flame patterns will be different from unit
to unit and will vary depending on installation
type and weather conditions.
If the vent configuration is installed incorrectly,
flames will lift or "ghost". This can be danger-
ous. Inspect flames after installation to ensure
proper installation and performance.
Figure 56 - Typical Flame Pattern
ClEaNING aND MaINTENaNCE
WARNING: Do not use
abrasive cleaners as this may
damage glass. Use a nonabra-
sive household glass cleaner to
clean glass. Do not clean glass
when hot.
WARNING:Turnofffireplace
and let cool before cleaning.
CAUTION: You must keep
control areas, burners and
circulating air passageways of
fireplace clean. Inspect these
areas of fireplace before each
use. Have fireplace inspected
yearly by a qualified service
person. Fireplace may need
more frequent cleaning due to
excessive lint from carpeting,
bedding material, pet hair, etc.
Glass must be cleaned periodically. Dur-
ing start up it is normal for condensation to
form on the inside of glass causing lint, dust
and other airborne particles to cling to glass
surface. During initial start up a slight film
may form on glass due to paint curing. Glass
should be cleaned several times with a non-
ammonia, nonabrasive household cleaner
and warm water after the first two weeks of
operation.Afterwards, clean glass two or three
times during each heating season, depend-
ing on the usage and circumstances present.
Refer to Removing/Replacing Glass Door on
page 24 of this manual when removing glass
door for cleaning.
GLASS DOOR
WARNING: Handle glass
door panel with care. Do not
strike, slam or otherwise abuse
glass. Do not operate fireplace
with the glass door unlatched,
removed, cracked or broken.
WARNING: Only parts sup-
pliedbythemanufacturershould
be used when replacing broken
or damaged glass door panel
(see Replacement Parts, page
36). This glass door panel is
a complete unit. No substitute
materials may be used.
30
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
ClEaNING aND MaINTENaNCE
Continued
LOGS
CAUTION: Wear gloves and
safety glasses while handling
or removing broken glass. Do
not remove if glass is hot. Keep
children and pets away from
glass.
• If you remove logs for cleaning, refer to
Installing Logs, Lava Rock and Glowing
Embers, page 25, to properly replace logs.
• Use a vacuum cleaner to remove any
carbon buildup on logs.
• Replace log(s) if broken. See Replacement
Parts on page 36.
•
Replace ember material periodically
as needed. See Replacement Parts on
page 36.
If glass has been broken, carefully remove
glass door (see Removing/Replacing Glass
Door, page 23). Vacuum all glass pieces with
a shop vac.
vENTING SYSTEM
Conduct annual inspection of venting system
following these guidelines:
CAUTION: Do not vacuum if
pieces are hot.
1. Check areas of venting system that are
exposed to the weather for corrosion (rust
spots or streaks and, in extreme cases,
holes). Have these items replaced im-
mediately by a qualified service person.
Use only the tempered glass door replace-
ment intended for this fireplace (see Replace-
ment Parts, page 36 for detail on ordering).
No substitutions may be made. See Remov-
ing/Replacing Glass Door, page 23 for instruc-
tions for replacing glass door.
2. Remove the vent cap and shine a flash-
light into the vent. Remove any foreign
material.
WARNING: Do not operate
fireplace with the glass door
unlatched, removed, cracked
or broken.
3. Check for evidence of excessive con-
densation. Continuous condensation can
cause corrosion of caps, pipes and fittings
and can be caused by having excessive
lateral runs, too many elbows or exterior
portions of the system being exposed to
cold weather.
pILOT AND bURNERS
• Remove ember material before cleaning
burners and replace when cleaning is
complete.
4. Inspect joints to verify that no pipe section
or fitting has been disturbed and loos-
ened. Check mechanical supports such
as wall straps for rigidity.
• Burner and controls should be cleaned
with compressed air to remove dust, dirt
or lint.
• Use a vacuum cleaner or small, soft bristled
brush to remove excess dust, dirt or lint.
116646-01J
31
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUblESHOOTING
WARNING: Turn off heater and let cool before servicing. Only a
qualified service person should service and repair heater.
CAUTION: Never use a wire, needle or similar object to clean
pilot. This can damage pilot unit.
Note: All troubleshooting items are listed in order of operation.
ObSERvED pRObLEM pOSSIbLE CAUSE
REMEDY
Whenignitorbuttonispressed, 1. Ignitor electrode not con- 1. Reconnect ignitor cable
there is no spark at pilot
nected to ignitor cable
2. Ignitor cable pinched or 2. Free ignitor cable if pinched
wet
by any metal or tubing.
Keep ignitor cable dry
3. Piezo ignitor nut is loose
3. Tighten nut holding piezo
ignitor. Nut is located be-
hind the mounting bracket
4. Replace ignitor cable
5. Replace piezo ignitor
6. Replace pilot assembly
4. Broken ignitor cable
5. Bad piezo ignitor
6. Ignitor electrode broken
7. Ignitor electrode positioned 7. Tighten electrode. Replace
wrong if necessary
Whenignitorbuttonispressed, 1. Gas supply turned off or 1. Turn on gas supply or open
there is spark at pilot but no
ignition
equipment shutoff valve
closed
equipment shutoff valve
2. Gas control knob not in 2. Turn gas control knob to
PILOT position PILOT position
3. Gas control knob not 3. Press in gas control knob
pressed in while in PILOT
position
while in PILOT position
4. Air in gas lines when in- 4. Continue holding down
stalled
control knob. Repeat ignit-
ing operation until air is
removed
5. Depleted gas supply (pro- 5. Contact local propane/LP
pane/LP models only)
6. Pilot is clogged
gas company
6. Clean pilot (see Cleaning
and Maintenance, page 30)
or replace pilot assembly
7. Gas regulator setting is not 7. Replace gas regulator
correct
32
Download from Www.Somanuals.com. All Manuals Search And Download.
116646-01J
TROUblESHOOTING
Continued
ObSERvED pRObLEM pOSSIbLE CAUSE
REMEDY
Pilot lights but flame goes 1. Gas control knob not fully 1. Press in gas control knob
out when control knob is
released
pressed in
fully
2. Gas control knob not 2. After pilot lights, keep gas
pressed in long enough
control knob pressed in 30
seconds
3. Equipment shutoff valve not 3. Fully open equipment shut-
fully open off valve
4. Pilot flame not touching 4. A) Contact local natural or
thermocouple, which allows
thermocouple to cool, caus-
ingpilotflametogoout.This
problem could be caused by
one or both of the following:
A) Low gas pressure
propane/LP gas company
B) Clean pilot (see Cleaning
and Maintenance, page 30)
or replace pilot assembly
B) Dirty or partially clogged
pilot
5. Thermocouple connection 5. Hand tighten until snug,
loose at control valve
6. Thermocouple damaged
7. Control valve damaged
then tighten 1/4 turn more
6. Replace pilot assembly
7. Replace control valve
Burner does not light after 1. Burner orifice clogged
pilot is lit
1. Clean burner (see Cleaning
and Maintenance, page 30)
or replace burner orifice
2. Inlet gas pressure is too 2. Contact local propane/LPor
low natural gas company
3. Thermopile leads discon- 3. Reconnect leads
nected or improperly con-
nected
4. Thermopile is defective
4. Replace thermopile
Delayed ignition burner
1. Manifold pressure is too 1. Contact local propane/LPor
low natural gas company
2. Burner porting or orifice 2. Clean burner (see Cleaning
clogged
and Maintenance, page 30)
or replace burner orifice
Burner backfiring during com- 1. Burner orifice is clogged or 1. Clean burner (see Cleaning
bustion
damaged
and Maintenance, page 30)
or replace burner orifice
2. Replace damaged burner
3. Replace gas control
2. Damaged burner
3. Gas regulator defective
Slight smoke or odor during 1. Residues from manufac- 1. Problem will stop after a few
initial operation
turing processes and logs
curing
hours of operation
116646-01J
33
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUblESHOOTING
Continued
pOSSIbLE CAUSE
ObSERvED pRObLEM
REMEDY
1. Turning gas control knob
to HI position when burner
is cold
Heater produces a whistling
noise when burner is lit
1. Turn gas control knob to LO
position and let warm up for
a minute
2. Air in gas line
2. Operate burner until air is
removed from line. Have
gas line checked by local
propane/LP or natural gas
company
3. Dirty or partially clogged
burner orifice
3. Clean burner (see Cleaning
and Maintenance, page 30)
or replace burner orifice
1. Flame impingement on
logs
Glass soots
1. Adjust log set so that the
flame does not excessively
impinge in it
2. Inspect the opening at the
base of the burner to see
that it is NOT packed with
any type of material
2. Debris around burner air
mixer
1. Metal expanding while
heating or contracting
while cooling
Fireplace produces a clicking/
ticking noise just after burners
are lit or shut off
1. This is normal. If noise is
excessive, contact qualified
service person
1. Battery is not installed or
battery power is low
Remote does not function
Fireplace shuts off in use
1. Replace 9-volt batteries in
receiver and remote control
1. High or gusting winds
1. Fireplace has been tested
for up to 40 mph winds.
However, extreme condi-
tions may occur. See Light-
ing Instructions on page 27
2. Contact local propane/LPor
natural gas company
2. Low line pressure
3. Pilot is partially clogged
3. Clean pilot (see Cleaning
and Maintenance, page 30)
4. Locate and correct all leaks
(see Checking Gas Con-
nections, page 21)
4. Inner vent pipe leaking ex-
haust gasses into system
5. Glass too loose and air
tight gasket leaks in cor-
ners after usage
5. Tighten glass
6. Bad thermopile or thermo-
couple
6. Replace faulty component
7. Improper vent cap installa-
tion
7. Check for proper installation
and freedom from debris or
blockage
34
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUblESHOOTING Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Fol-
low the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
ObSERvED pRObLEM pOSSIbLE CAUSE
REMEDY
Fireplace produces unwant- 1. Gas leak. See Warning 1. Locate and correct all leaks
ed odors
statement above
(see Checking Gas Con-
nections, page 21)
Gas odor even when control 1. Gas leak. See Warning 1. Locate and correct all leaks
knob is in OFF position
statement above
(see Checking Gas Con-
nections, page 21)
2. Control valve defective
2. Replace control valve
Gas odor during combustion 1. Gas leak. See Warning 1. Locate and correct all leaks
statement above
(see Checking Gas Con-
nections, page 21)
Darkresidueonlogsorinside 1. Improper log placement
of fireplace
1. Properly locate logs (see
Installing Logs, Lava Rock
and Glowing Embers,
page 25)
2. Air holes at burner inlet 2. Clean out air holes at burn-
blocked
er inlets. Periodically repeat
as needed
3. Burner flame holes 3. Remove blockage or re-
blocked place burner
4. Improper venting or exces- 4. Have the vent system in-
sive blockage
spected, including the ter-
mination cap. Remove any
restrictions or obstruction
5. Excessive amounts of em- 5. Clear excess embers until
bers and pan material
a minimum gap of 1/2"
remains under the grate
116646-01J
35
Download from Www.Somanuals.com. All Manuals Search And Download.
REplaCEMENT paRTS
Note: Use only original replacement parts. When calling, have ready:
This will protect your warranty coverage for
parts replaced under warranty.
• your name
• your address
Contact authorized dealers of this product.
If they can’t supply original replacement
part(s), call FMI PRODUCTS, LLC at
1-866-328-4537.
• model and serial numbers of your heater
• how heater was malfunctioning
• purchase date
Usually, we will ask you to return the part to
the factory.
SERVICE HINTS
TECHNICal SERVICE
When Gas pressure Is Too Low
You may have further questions about
installation, operation, or troubleshooting.
If so, contact FMI PRODUCTS, LLC at
1-866-328-4537. When calling please have
your model and serial numbers of your
heater ready.
• pilot will not stay lit
• burners will have delayed ignition
• fireplace will not produce specified heat
• propane/LP gas supply might be low (pro-
pane/LP units only)
You can also visit FMI PRODUCTS, LLC’s
You may feel your gas pressure is too low. If
so, contact your local gas supplier.
SpECIFICaTIONS
(V)T32N-A Series, (V)T32N-A-HA Series,
CGDV32NR and CTDV32NR-HA
• Rating: 12,000/18,000 Btu/Hr
(V)T32P-A Series and CGDV32PR
• Rating: 11,000/17,000 Btu/Hr
• Type Gas: Propane/LP Gas Only
• Ignition: Piezo
• Type Gas: Natural Gas Only
• Ignition: Piezo
• Manifold Pressure: 10" W.C.
• Minimum Inlet Gas Pressure (W.C.): 11"
• Manifold Pressure:
Models (V)T32N-A Series and CGDV32NR
3.5" W.C.
• Dimensions (H x W x D) (Firebox only. Does
not include nailing flanges or standoffs):
32 1/4" x 34 1/2" x 16 5/8"
Models (V)T32N-A-HA series and
CTDV32NR-HA
3.8" W.C.
• Fireplace Weight*: 80 lb
• Minimum Inlet Gas Pressure (W.C.): 5.5"
• Shipping Weight*: 83 lb
• Dimensions (H x W x D) (Firebox only. Does
not include nailing flanges or standoffs):
32 1/4" x 34 1/2" x 16 5/8"
*For refractory lined models add 45 lb
• Fireplace Weight*: 80 lb
• Shipping Weight*: 83 lb
*For refractory lined models add 45 lb
36
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
aCCESSORIES
NOTICE: All accessories may
not be available for all fireplace
models.
Purchase these accessories from your local
dealer. If they can not supply these accessories
call FMI PRODUCTS, LLC at 1-866-328-4537
for information. You can also write to the ad-
dress listed on the back page of this manual.
THERMOSTATICALLY-
CONTROLLED BLOWER KIT - BKT
Provides better heat distribution. Blower turns
off and on automatically, as needed. Com-
plete installation and operation instructions
included in this manual.
REFRACTORY BRICK LINER KIT
BL32DS
This brick liner adds a touch of style to your
direct-vent fireplace. Complete installation
instructions included in this manual.
pROpANE/NATURAL GAS
CONVERSION KIT
PCDM-32T - Propane/LP Gas Conversion Kit
NCDM-32T - Natural Gas Conversion Kit
RECEIvER AND HAND-HELD
THERMOSTAT REMOTE CONTROL
KIT - TLCR
FACE/LOUVER PANEL KIT
RLD32 - Rolled Louver Panels, Black
For all Remote-Ready Models. Allows
the fireplace to be operated in a manually
or thermostatically-controlled mode. You
can adjust your heat settings and turn the
fireplace on or off without leaving the comfort
of your easy chair.
LOUVER TRIM KIT (Rolled Louvers
Only)
LT32B - Brushed Brass
LT32P - Platinum
DEFLECTION HOOD
HD32 - Hood - Black (2" Brow)
PERIMETER TRIM KIT
PT32 - Black
PT32B - Brushed Brass
PT32P - Platinum
RECEIvER AND HAND-HELD ON/OFF
REMOTE CONTROL KIT - MLCR
For all Remote-Ready Models. Allows
the fireplace to be turned on and off
conveniently.
WALL MOUNTED THERMOSTAT
CONTROL KIT - GWMT1
Allows easy wall access for thermostatic opera-
tion of your fireplace.
MANUAL BLOWER KIT - BK
Manual variable control blower accessory
provides better heat distribution. Complete in-
stallation and operation instructions included
in this manual.
WALL MOUNTED ON/OFF SWITCH
GWMS2
Allows burner system to be turned on and off
with a wall switch.
116646-01J
37
Download from Www.Somanuals.com. All Manuals Search And Download.
paRTS
MODELS (V)T32N-A, (V)T32NB-A, (V)T32NR-A, (V)T32NRB-A, (V)T32P-A,
(V)T32PB-A, (V)T32PR-A, (V)T32PRB-A, CGDV32NR, CGDV32PR AND
CTDV32NR-HA
22-3
6
22-5
22-4
22-6
7
8
22-2
22-1
1
4
11
9
14
21
19
18
20
12
13
10
17
3
15
5
2
16
38
Download from Www.Somanuals.com. All Manuals Search And Download.
116646-01J
paRTS
This list contains replaceable parts used in your fireplace. When ordering parts, follow the
instructions listed under Replacement Parts on page 36 of this manual.
pART NUMbER
CGDV32NR
CGDV32PR
CTDV32NR-HA
(V)T32N-A
(V)T32P-A
(V)T32NR-A
(V)T32PR-A
KEY (V)T32NB-A (V)T32NRB-A
NO. (V)T32PB-A (V)T32PRB-A DESCRIpTION
QTY.
1
2
3
**
**
**
**
Firebox Assembly
Face Weldment
1
1
1
1
108892-01 108892-01
108892-02 108892-02
109155-01 108903-01
109155-02 108903-02
Door Assembly (T & CGDV Models Only)
Door Assembly (VT Models Only)
Top Louver/Panel Assembly
Bottom Louver/Panel Assembly
Fireplace Top
Fireplace Top Insulation
Fireplace Surround
Burner Assembly (Natural Gas)
Burner Assembly (Propane/LP Gas)
(See page 40 & 41)
4
5
6
7
8
9
1
1
1
1
1
1
**
**
**
**
**
**
108885-01 108885-01
108885-02 108885-02
10
11
12
13
14
15
16
17
18
19
20
21
22
108890-01 108890-01
109082-03 109082-03
108897-01 108897-01
108901-01 108901-01
108901-02 108901-02
Burner Base Gasket
Heat Shield
Rear Refractory Brick Panel (B Models Only)
Right Refractory Brick Panel (B Models Only)
Left Refractory Brick Panel (B Models Only)
Push-On Nut
Screen
Screen Rod
Strain Relief
Gas Knock-Out Cover
Handy Box Assembly
Gas Conduit Assembly
Log Set
Front Log (No. 1)
Rear Log (No. 2)
Base Log (No. 3)
Crossover Log (No. 4)
Left Top Log (No. 5)
1
1
1
1
1
2
2
1
1
2
1
1
1
1
1
1
1
1
1
11418
12125
11418
12125
109479-01 109479-01
14123
21171
24353
24460
14123
21171
24353
24460
109222-01 109222-01
22-1 109403-01 109403-01
22-2 109404-01 109404-01
22-3 109407-01 109407-01
22-4 109406-01 109406-01
22-5 109405-01 109405-01
22-6 109408-01 109408-01
Right Top Log (No. 6)
PARTS AVAILABLE - NOT SHOWN
25487
25487
Lava Rock/Bag Assembly
1
1
PCDM-32T Propane/LP Gas Conversion Kit (model
CTDV32NR-HA only)
** Not a field replaceable part.
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
39
paRTS
BURNER ASSEMBLY MODELS (V)T32N-A, (V)T32NB-A, (V)T32NR-A, (V)
T32NRB-A, (V)T32P-A, (V)T32PB-A, (V)T32PR-A, (V)T32PRB-A, CGDV32NR,
CGDV32PR AND CTDV32NR-HA
17
19
16
15
1
2
13
8
3
7
18
9
14
11
6
12
4
5
10
40
Download from Www.Somanuals.com. All Manuals Search And Download.
116646-01J
paRTS
BURNER ASSEMBLY MODELS (V)T32N-A, (V)T32NB-A, (V)T32NR-A, (V)
T32NRB-A, (V)T32P-A, (V)T32PB-A, (V)T32PR-A, (V)T32PRB-A, CGDV32NR,
CGDV32PR AND CTDV32NR-HA
This list contains replaceable parts used in your fireplace. When ordering parts, follow the
instructions listed under Replacement Parts on page 36 of this manual.
KEY
NO. PART NO.
DESCRIpTION
QTY.
2
9
4
1
1
2
3
4
5
11102
11105
11179
11237
14389
14390
Screw #8-32 x 3/8 PPH Zinc
Screw #10 x 1/2 Zinc
Screw #10-24 x 1/4 Zinc
Screw, Trilab M4 x 8 mm
Millivolt Valve (Natural Gas)
Millivolt Valve (Propane/LP Gas)
1
1
117370-01 Millivolt Valve (NG-High Altitude)
1
6
7
8
9
14492
14500
14253
14511
Piezo Ignitor
Brass Fitting
Flexible Connector
Ignitor Bracket
Brass Elbow Fitting
1
2
1
1
10 14528
1
11 104506-25 Orifice (Natural #47)
104506-02 Orifice (Propane/LP #55)
12 104509-02 Aluminum Tubing Assy
1
1
1
13 26808
14 26827
Valve Bracket
Switch Bracket
1
1
15 108886-01 Base Grate Assembly
16 108891-01 Burner
1
1
17 108084-02 Pilot Assembly (Natural)
108084-03 Pilot Assembly (Propane/LP)
108084-05 Pilot Assembly (NG-High Altitude)
1
1
1
18
**
Burner Base Assembly
1
19 27113
Air Deflector
1
** Not a field replaceable part.
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
41
NOTES
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
42
116646-01J
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
116646-01J
43
Download from Www.Somanuals.com. All Manuals Search And Download.
WaRRaNTy
KEEp THIS WaRRaNTy
Model (located on product or identification tag)_____________________________
Serial No. (located on product or identification tag)__________________________
Date Purchased __________________________
Keep receipt for warranty verification.
FMI pRODUCTS, llC lIMITED WaRRaNTIES
New products
Standard Warranty: FMIPRODUCTS, LLCwarrantsthisnewproductandanypartsthereoftobefreefromdefects
in material and workmanship for a period of four (4) years from the date of first purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date
of first purchase.
Factory Reconditioned products
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be
free from defects in material and workmanship for 30 days from the date of first purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
Terms Common to All Warranties
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this
warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only
when installed by a qualified installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allow-
ance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by
FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI
PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement
parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs,
unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of
the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty
excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all
implied warranties, including warranties of merchantability and fitness for a particular purpose to four (4) years on
new products and 30 days on factory reconditioned products from the date of first purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not
be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.