7 Testing the library and resuming operation
7 Testing the library and resuming operation
Before resuming operation, use the Demo Menu from the operator panel to
ensure that the robot and the newly installed tape drive are
communicating correctly. The Demo Menu causes the robot to randomly
move cartridges from slot to slot, including the fixed cartridge slots.
To test the library operation using the Demo Menu, follow these steps:
1. Insert a cartridge in the entry/exit port.
Note: All other cartridges in the library can remain where they are.
The testing can also be performed without any cartridges other
than the one in the entry/exit port.
2. If necessary, disable security as follows:
a. Press the [MENU] key to display the menus. Press the down arrow key
until “Security” appears on the screen, as shown below. If security
is enabled, “LCD Password” appears on this screen.
! S e c u r i t y
L C D P a s s w o r d
b. Press [ENTER]. The following screen appears.
P a s s w o r d ?
0 0 0
↕
c. Use the left and right arrow keys to move across the columns. Enter
your password using the up and down arrow keys to select a
number. Press [ENTER]. Security is then disabled.
3. Change the control mode to LCD as follows:
a. Press [MENU] to display the menus, then press the down arrow key
until “Robot Mode” appears. The Robot Mode screen shows the
currently activated mode.
! R o b o t
M o d e
S C S I
March 2002
Page 9 of 12