GE Monogram Switch Zenith Controls User Manual

ZTX SERIES  
40-400 Amps  
g
GE Zenith Controls  
62R-2000C  
7/02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation and Maintenance Manual  
How to Remove the Cover  
Loosen but do not remove four cover screws. Lift cover  
off the four screws and hang on two screws (2 bottom  
or 2 right-hand). See Figure i and ii.  
This will prevent damage to the cable. The cable may  
also be disconnected at the controller or keypad.  
NOTE: Reattach cable before installing cover.  
DANGER  
HAZARDOUS VOLTAGE  
Will shock, burn or cause death.  
Do not remove cover until ALL  
power is disconnected.  
Re-installation of cover is required  
after maintenance or service.  
Figure i  
Figure ii  
GE Zenith Controls  
1
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
The safe operation of your switch is GE Zenith’s focus.  
The proper storage, installation, operation and mainte-  
nance will help increase the life of the switch.  
NOTE:  
Lug torque values are specified  
in the power panel manual.  
5. Make sure that all covers and barriers are  
installed and properly fastened.  
CAUTION  
Due to hazardous voltage and current, GE Zenith rec-  
ommends that a GE Zenith Certified technician or a  
qualified electrician must perform the  
NOTE:  
Power panels ship from GE Zenith  
in the Normal Position.  
Each GE Zenith transfer switch is factory wired and  
tested. A complete information package is furnished  
with each switch which includes:  
a. Sequence of operation.  
installation and maintenance of the switch.  
b. Description and operation of  
all accessories supplied.  
c. Power panel connection diagram  
and schematic.  
d. Description and identification of  
all customer field connections.  
Equipment Inspection  
and Storage  
Once you have received the transfer switch, inspect  
it for any damage. This includes damage to the enclo-  
sure, power panel, control panel and wiring harness. If  
any damage is found or suspected, file a claim as soon as  
possible with the carrier and notify the nearest GE Zenith  
representative.  
Installation of GE Zenith transfer switches includes:  
a. Mounting the transfer switch cabinet.  
b. Connection of all Normal, Emergency,  
and Load cables or bus bars.  
Before installation, it is necessary to store the transfer  
switch in a clean dry place, protected from dirt and  
water. Provide ample air circulation and heat, if neces-  
sary, to prevent condensation.  
c. Connection of external control  
circuits as required.  
Mounting  
Adequate lifting means must be used to mount the transfer  
switch into place. The recommended method for moving  
the transfer switch using the lifting eyes, where supplied,  
and a spreader bar is  
Operating  
Storage  
Temperature  
Temperature (Ambient):  
Humidity  
illustrated here.  
-30°C to  
+75°C  
-20°C to +65°C  
(-4°F to +149°F)  
5% to 95%  
(non-con-  
densing)  
SPREADER BAR  
45°  
Enough room should  
H
be allowed to open  
(-22°F to  
+167°F)  
the cabinet doors  
fully for inspection  
and servicing of the  
LIFTING EYES  
switch per NEC and  
local codes.  
Final Equipment Inspection  
Prior to energizing the transfer switch:  
1. Remove any debris incurred, with a vacuum,  
due to shipment or installation.  
CABINET  
D
NOTE:  
When lifting the switch using a spreader bar,  
height H must be equal to half of distance D.  
WARNING  
CAUTION  
Before drilling conduit entry holes or any  
accessory mounting holes, cover and protect  
the switch and control panel to prevent dirt  
and metal fragments from entering the  
mechanical and electrical components.  
Do not use a blower since debris may  
become lodged in the electrical and  
mechanical components and cause damage.  
2. Verify that all cabled connections are correct.  
3. Check engine start connections and verify  
the correct connection of all control wires.  
4. Check the lug torque values of the power  
connections.  
Failure to do so may result in  
damage and malfunction of the switch.  
2
GE Zenith Controls  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
(contd)  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
Connect the Normal, Emergency, and Load conductors  
Power Connections  
to the clearly marked terminals on the transfer switch.  
GE Zenith transfer switches are supplied with UL listed  
Remove surface oxides from cables by cleaning with a  
solderless screw type terminals as standard for the  
wire brush. Verify that all connections are correct before  
Normal, Emergency and Load power connections.  
tightening the lugs. All cable lug connections must be  
Table 1 lists the number and sizes of cable lugs supplied  
tightened to the proper torque values as shown in Table 2.  
as standard for each switch amp rating.  
NOTE:  
Do not run cables or wiring behind  
front-connected transfer switches.  
ScrewTypeTerminals for External Power Connections  
Fully Rated Neutral Bar (When Required)  
Switch Size  
(Amps)  
Utility, Generator and Load Terminals  
Cable Per Pole  
Range of Wire Sizes  
#8 to 3/0 AWG  
No. of Cables  
Range of Wire Sizes  
#8 to 1/0 AWG  
40  
1
1
1
1
1
1
3
3
3
3
3
3
80  
100  
#8 to 3/0 AWG  
#8 to 1/0 AWG  
#8 to 3/0 AWG  
#8 to 1/0 AWG  
150  
#8 to 3/0 AWG  
#8 AWG to 300 MCM  
#6 AWG to 300 MCM  
#4 AWG to 300 MCM  
200, 225, 250*  
#6 AWG to 250 MCM  
#4 AWG to 600 MCM  
300, 400  
Table 1  
LOAD  
TERMINALS  
* IEC Rating Only  
T1  
T2  
T3  
UTILITY  
TERMINALS  
Tip!  
Install  
load  
OPTIONAL A4 CONTACT  
OPERATESWHEN IN  
UTILITY POSITION  
N1  
N2  
N3  
BR  
cables  
first.  
JP  
Exerciser  
CONTROLLER  
OPTIONAL ENGINE CONTROLS  
OR AIR CONDITION DISCONNECT  
OR 3 PHASE BOARD  
3 AND 4 POLE ONLY  
ENGINE  
START  
SWITCH  
POSITION  
INDICATOR  
N
E3  
E1  
E2  
OPTIONAL A3 CONTACT  
OPERATESWHEN IN  
GENERATOR POSITION  
GENERATOR  
TERMINALS  
T = Load  
N = Utility  
E = Generator  
Figure 2 - Power Panel  
GE Zenith Controls  
3
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
(contd)  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
Control Connections  
Note:  
N = Utility Position  
E = Generator Position  
Connecting Engine Start may cause Generator to  
start. Before connecting, turn Generator OFF.  
With the Generator breaker open and the Generator  
control switch off, install the Generator start connections.  
JP  
Figure 4  
6
5
4
B
A
Exerciser  
Manual operation is possible for maintenance purposes only.  
Manual operation of the switch can be checked before it  
is operated electrically.  
CONTROLLER  
Close to Start  
Opens to Stop  
With all power off, insert a Phillips screwdriver or equivalent  
size tool into the manual operator socket and operate  
the transfer switch between the Utility and Generator  
positions. The transfer switch should operate smoothly  
without binding. Return the switch to the Utility position,  
remove the screwdriver.  
Contact Rating  
28Vdc @ 5 amps  
Figure 3  
Engine Start  
Contact Output  
The engine-start terminals are clearly identified by a  
label on the microcontroller backplate. In the case of  
manual transfer switches, or in other applications not  
requiring the microprocessor, clearly marked terminal  
blocks are provided in the upper left corner of the control  
panel for the engine start control wires.  
TighteningTorque for Lugs  
Torque  
Socket Size  
Across Flats  
Lb. - In.  
Lb. - Ft.  
1/8  
5/32  
3/16  
45  
4
Terminals for field connections to the A3 Emergency  
auxiliary contacts and the A4 Normal auxiliary contacts  
are also provided. These terminals are clearly marked  
and appear on the side of the power panel. On 400 amp  
metal frame units these terminals appear on the bracket  
above the operator handle.  
100  
120  
150  
200  
275  
375  
500  
600  
8
10  
12  
17  
23  
31  
42  
50  
7/32  
1/4  
5/16  
3/8  
1/2  
g
GE Zenith Controls  
9/16  
Table 2  
SERIAL NUMBER:  
RATING:  
VOLTS -  
AMPS -  
HZ -  
PHASE -  
SYSTEM VOLTS:  
MODEL NUMBER:  
Figure 3  
4
GE Zenith Controls  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
(contd)  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
ATTENTION!  
This applies only to the switches with the RM4-CAT  
exerciser option:  
installed and/or replaced as recommended, the  
exerciser clock will lose its settings and the exerciser  
Upon installation, connect the MX50/90 controller to a  
will not work.  
9V battery (not supplied) via the harness that is con-  
nected to the controller. The battery should be placed  
Should the harness become disconnected in shipping,  
in the holder installed just above the controller. This is  
take the controller cover off and plug the harness in the  
to ensure that the setting in the exercisor clock are  
receptacle in the top right corner of the MX controller.  
Reinstall the cover and connect the battery.  
retained in the event of power outage. The battery  
should be replaced once a year. If the battery is not  
Battery and Holder  
Battery Harness  
MX50/90 Controller  
GE Zenith Controls  
5
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
(contd)  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
Functional Test  
FunctionalTest  
Initiate the electrical transfer test by opening the Utility  
side breaker. The delay to engine start timer (P) begins  
its timing cycle. After the P timer has completed its timing  
cycle, the engine start contacts close to start the generator.  
The functional testing of the transfer switch consists of  
electrical tests described in this section. Before proceed-  
ing, read and understand all instructions and review the  
operation of all accessories provided.  
When Generator voltage and frequency reach preset pickup  
points the optional Generator Available LED illuminates.  
Simultaneously, the delay to Generator timer (W) begins  
its timing cycle. When the W time delay is completed the  
switch will transfer to Generator. The optional Utility  
Position LED goes off, and the optional Generator  
Position LED illuminates.  
To begin the test, close the Utility source circuit breaker.  
The controller will illuminate the optional Utility Available  
LED when proper voltage is sensed. Verify the phase to  
phase voltages at the Utility line terminals.  
Next, close the Generator source breaker and start the  
engine generator. The optional Generator Available  
LED will illuminate when proper voltage and frequency  
levels is sensed. If Generator LED is flashing, use the Reset  
button to clear. Check the phase to phase voltages at the  
Generator line terminals. On three phase units, verify  
that the phase rotation of the Generator source is same  
as Utility source.  
Reclose the Utility breaker to retransfer to Utility. The  
delay to Utility timer (T) begins its timing cycle. When  
the T timer has completed its timing cycle, the switch will  
transfer into Utility. The optional Generator Position  
LEDs go off, and the Utility Position LED illuminates.  
The delay engine stop timer (U) begins its timing cycle.  
The generator runs unloaded for the duration of the U  
timing cycle. When the timer completes its timing cycle,  
the generator will stop. The optional Generator Available  
LED goes off.  
After the sources have been verified, shut down the engine  
generator, and put the starting control in the automatic posi-  
tion. Complete the visual inspection of the transfer switch,  
and replace the cabinet cover (or close the cabinet door).  
Factory Settings  
Factory Settings  
90% Nominal  
Utility Pickup Voltage  
90% Nominal  
Generator Pickup Voltage  
Line Voltage  
Line Voltage  
80% Nominal  
Utility Dropout Voltage  
80% Nominal  
Generator Dropout Voltage  
Line Voltage  
Line Voltage  
90% Nominal  
Utility Pickup Frequency  
95% Nominal  
Generator Pickup Frequency  
Line Frequency  
Line Frequency  
(T) Timer/Delay to Utility  
5 minutes*  
5 minutes*  
(P)Timer/Engine Start  
5 seconds*  
(U) Timer/Engine  
Cool Down  
(W) Timer/Delay to Generator  
20 seconds*  
Table 3  
* Factory default settings — customer time settings may vary due to specifications from the generator supplier.  
6
GE Zenith Controls  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RM4 Control Interface (Optional)  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
Optional Indicator LEDs  
Utility available Green LED. When on, indicates the  
utility source is acceptable.  
A
B
C
D
Utility position Green LED. When on, indicates that  
the transfer switch is connected to the utility.  
Generator available Red LED. When on, indicates  
the generator source is acceptable.  
Generator position Red LED. When on, indicates that  
the transfer switch is connected to the generator.  
C
Load Amber LED. When on, indicates that the load  
is connected to an acceptable source.  
E
D
F
A
H
B
I
Figure 5  
E
G
Optional Pushbuttons  
Generator Start/Stop push button. Pressing and  
F
holding this button for approximately 5 seconds  
will cause the generator to start. Pressing this button  
a second time will stop the generator.  
G
Exerciser Start/Stop push button. When this button  
is depressed it will enable the automatic exerciser  
mode. Pressing this button a second time will cancel  
the automatic exerciser mode.  
H
Reset push button. Pressing this button will clear the  
fault indications.  
I
Transfer push button. Pressing this button will force  
the unit to transfer from one position to another when  
both sources are available.  
GE Zenith Controls  
7
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RM4 Control Interface (Optional)  
(contd)  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
AutomaticTransfer Generator  
Testing (OneTimeTest)  
Transfer GeneratorTesting  
(Forcing Operation with Keypad)  
Verify that the transfer switch UTILITY available and  
Verify that the transfer switch UTILITY available and posi-  
position LEDs are illuminated.  
A
B
tion LEDs are illuminated.  
A
B
+
+
Press and hold the GENERATOR START/STOP button  
F
Press and hold the GENERATOR START/STOP button for 5  
seconds. This will start the generator.  
I
and the TRANSFER button  
for 5 seconds. This will  
F
cause the generator to start. Once the generaCor has  
started, the Generator LED will illuminate.  
Verify that the GENERATOR available LED  
has illuminated.  
C
C
Once the GENERATOR power LED  
has come on, the  
transfer switch will now switch the load to the Generator.  
D
The GENERATOR position LED will illuminate.  
I
Press the TRANSFER button.  
to the Generator source position. The GENERATOR  
position LED will now be illuminated.  
The switch will transfer  
D
The transfer switch will be connected to the generator  
for 5 minutes.* Then the switch will automatically return to  
B
the utility and the UTILITY Position LED will illuminate.  
Pressing the TRANSFER button  
unit to transfer to the utility power source. The UTILITY  
position LED will illuminate.  
again will cause the  
I
B
The generator will cool down for 5 minutes (U Timer)  
and then shut down. The GENERATOR LED will go off.  
C
Pressing the GENERATOR START/STOP button will stop  
the generator.  
This completes the automatic test.  
F
* Pressing and releasing the generator Start/Stop button  
NOTE: Transfer will cause short interruption of power.  
will cancel current test.  
LED Diagnostic Flash Codes  
Rapidly Flashing Generator  
Rapidly Flashing Generator  
D
Availability LED  
Position LED  
C
Generator failed to start.  
Switch did not transfer to Generator position.  
Generator starts but failed to reach proper  
operating parameters.  
B
Rapidly Flashing Utility  
Position LED  
Generator became over loaded for an extended  
period of time.  
Switch did not transfer to Utility position.  
NOTE: All fault alarms can be cleared by  
depressing the reset button.  
Optional generator crank board (see generator  
fault flash table on page 14)  
8
GE Zenith Controls  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RM4 Control Interface (Optional)  
(contd)  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
Automatic Generator Exerciser  
DANGER  
Turn OFF all power before selecting.  
The automatic generator exerciser comes preset with  
a 28-day exerciser schedule (the customer unit’s preset day  
cycle may vary due to specifications from the generator supplier).  
The exerciser, when enabled, will automatically start the  
generator every twenty-eighth day and run the unit loaded  
JP (CDT SELECT)  
or unloaded for 10 minutes. The exerciser interval is  
selectable through (JP) jumper selection on the con-  
See Figure 3, Page 4  
troller board. The selections are 7, 14, 21 or 28 day.  
21 Day  
28 Day  
7 Day  
Selecting Exerciser WithoutTransfer  
To start the automatic exerciser without transfer, depress  
the Exerciser Start/Stop button. The generator will start  
and run for 10 minutes.*Once this first exercise is com-  
plete, the generator LED will flash at a 1-second interval  
indicating the exerciser is enabled. Once the exerciser  
times out (7, 14, 21 or 28 day interval), the generator  
will start and run again for 10 minutes. This will repeat  
until the exerciser is disabled. To stop the exerciser mode,  
depress the exerciser Start/Stop again and the generator  
light will stop flashing, indicating the exerciser mode  
has been canceled.  
B
B
A
A
B
B
A
A
14 Day  
JP (VOLTAGE/FREQUENCY SELECT)  
Selecting Exerciser WithTransfer  
To enable the automatic exerciser with transfer, depress  
the Exerciser Start/Stop button and the transfer button.  
The generator will start and the load will be transferred to  
the generator. After 10 minutes*, the load will be transferred  
back to the utility. Once this first exercise is complete, the  
generator LED and the Generator position LED will flash  
at a 1-second interval indicating the exerciser is enabled.  
Once the exerciser has timed out (7, 14, 21 or 28 day  
interval), the generator will start and transfer the load  
to Generator power for 10 minutes. At the end of this  
10-minute period, the unit will transfer the load back to  
the utility and the generator will shut off. This will repeat  
until the exerciser is disabled. To stop the exerciser  
mode, depress the exerciser Start/Stop again and the  
generator light will stop flashing, indicating the exerciser  
mode has been canceled.  
See Figure 3, Page 4  
Do not adjust the jumper positions.  
This service to be performed by qualified personnel only.  
208 V  
220 V  
240 V  
50 Hz  
60 Hz  
* Pressing and releasing the generator Start/Stop button will cancel  
the current test. The exerciser will go off at approximately the same  
time it was started (7, 14, 21 or 28 days) later.  
NOTE: Transfer will cause short interruption of power.  
Figure 6  
GE Zenith Controls  
9
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Engine Controller Accessory Board (Optional)  
Oil Pressure Sensor Input  
Fuel/Run Contact Output  
(Oil pressure contact to be normally open, held closed  
by adequate oil pressure)  
This output is activated closed whenever the engine is  
running. This will keep the fuel valve open as needed,  
and will cut fuel supply during the above mentioned  
lockouts or when the engine is no longer called to run.  
Approximately five seconds after emngine starter signal  
is sent, if terminal X3 is open to ground or returns to  
open state thereafter the generator Starter and Fuel/Run  
outputs are opened and locked out. After cause is deter-  
mined and corrective action is taken and verified by quali-  
fied technician, controller can be reset via reset button.  
Start Contact Output  
This output is activated closed during cranking of the  
engine. Output will deactivate once the controller senses  
that the generator output has reached 33% of frequency  
indicating engine has reached running RPM.  
Temperature Sensor Input  
(Temperature sensor contact to be normally open,  
closed by over-temperature condition)  
Approximately five seconds after the engine starter signal  
is sent, if terminal X1 is connected to ground Starter and  
Fuel/Run outputs are opened and locked out. After  
cause is determined and corrective action is taken and  
verified by a qualified technician, the controller can be  
reset via the reset button.  
Generator Battery Input  
This input is required to support the controller’s operation.  
Controller  
Generator Battery Input  
(12Vdc)  
X9  
X10  
Engine  
Controller  
+ –  
+ – + –  
X1  
X2  
X3  
X4  
X5  
X6  
Start Contact Output  
(28Vdc @ 5 amps)  
Input  
Input  
Fuel/Run Contact Output  
Temperature  
Sensor  
Oil Pressure  
Sensor  
(28Vdc @ 5 amps)  
(12Vdc)  
(12Vdc)  
10  
GE Zenith Controls  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example Systems  
Partial Coverage System  
Transfer Switch  
Loads  
Utility  
Source  
Generator  
Source  
Circuit  
Breaker  
Utility Panel  
Loads  
Distribution Panel  
Total Coverage System  
Transfer Switch  
Generator  
Source  
Utility  
Source  
Circuit  
Breaker  
Circuit  
Breaker  
Main  
Breaker  
Panel  
All Loads  
GE Zenith Controls  
11  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical Diagrams  
Power Circuit Schematic  
Power Panel Layout  
Interconnect Plug  
5
10  
6
CCN  
SN  
SCOM  
SE  
N1  
N2  
CCE  
E1  
E2  
1
OPTIONAL 3  
4
3
N2 E3  
N3 E2  
2
1
12  
GE Zenith Controls  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
Service must be performed by qualified personnel.  
Symptom  
Possible Cause  
Corrective Action  
P timer has not lapsed  
See factory settings on Page 6  
Generator control switch not in Auto  
Refer to generator instruction manual  
See Figure 3, Page 4  
Engine Start contact not wired  
to generator  
Generator will not start  
Starter battery is dead  
No fuel  
Refer to generator instruction manual  
Refer to generator instruction manual  
T timer has not lapsed  
Exercise in progress  
See factory settings on Page 6  
See Page 9  
Utility breaker open or tripped  
Clear fault and reset  
Transfer switch does not  
transfer to Utility  
Wait for utility to return to acceptable  
level. See factory settings on Page 6.  
Utility voltage out of range  
Control harness unplugged  
With all power disconnected,  
reconnect harness  
W timer has not lapsed  
See factory settings on Page 6  
Generator breaker open or tripped  
Generator voltage out of range  
Refer to generator instruction manual  
Refer to generator instruction manual  
Transfer switch does not  
transfer to Generator  
With all power disconnected,  
reconnect harness  
Control harness unplugged  
U timer has not lapsed  
See factory settings on Page 6  
See page 9  
Exercise in progress  
Generator will not stop  
Engine control switch in run position  
Refer to generator instruction manual  
With all power disconnected,  
reconnect harness  
Keypad cable unplugged  
All LEDs off  
Sources unavailable and/or source  
breakers tripped or open  
Clear fault and reset breakers and/or  
check source availability  
GE Zenith Controls  
13  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
(contd)  
DANGER  
HAZARDOUS VOLTAGE  
(Can Cause Severe Injury or Death)  
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.  
Service must be performed by qualified personnel.  
Generator Fault FlashTable  
Generator Failed to Start (GFSTimeout)  
Generator Under-Speed Fault  
2 Flashes + 2 Missing  
3 Flashes + 2 Missing  
4 Flashes + 2 Missing  
5 Flashes + 2 Missing  
6 Flashes + 2 Missing  
Generator Over-Speed Fault  
Generator Over-Temperature Fault  
Generator Low-Oil-Pressure Fault  
NOTE: Faults that trigger the “original” SAG timer (emergency source not available for longer than the GS timer interval)  
will continue to be indicated on the “Emergency Source” LED at the original continuous 5 Hz rate.  
14  
GE Zenith Controls  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GE Zenith Controls  
15  
ZTX Operation and Maintenance Manual (62R-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
g
GE Zenith Controls  
GE Industrial Systems –  
Power Equipment Business  
830 W. 40th Street, Chicago, IL 60609 USA  
773 299-6600, Fax: 630 850-6899  
Download from Www.Somanuals.com. All Manuals Search And Download.  

CNET Network Router CNWR 811P User Manual
Coleman Air Conditioner 100 RANG User Manual
Cooper Lighting Indoor Furnishings CM2B User Manual
Country Home Products Outdoor Cart Garden Cart User Manual
Cuisinart Blender CSB 76 User Manual
Fisher Price Riding Toy M0411 User Manual
GE Air Conditioner AEV24DK User Manual
Gefen Switch EXT DVI 16416 User Manual
Generac Power Systems Portable Generator 004988 2 User Manual
Gitzo Camcorder Accessories G1297 User Manual