Frigidaire Air Conditioner FRS093LC1 User Manual

AIll nabosuttthae llation  
of your  
Split Type Room Air Conditioner  
Model(indoor/outdoor):  
FRS093LW1/FRS093LC1  
FRS123LW1/FRS123LC1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To prevent injury to the user or other people and property damage, the  
following instructions must be followed.  
Incorrect operation due to ignoring of instructions may cause harm or  
damage. The seriousness is classified by the following indications.  
1. Connect with the power properly.  
Otherwise, it may cause electric  
shock or fire due to excess heat  
generation.  
2. Always ensure effective grounding.  
No grounding may cause electric  
shock.  
3. Disconnect the power if strange  
sounds, smell, or smoke comes  
from it. It may cause fire and  
electric shock.  
4. Do not operate or stop the unit by  
switching on or off the power. It  
may cause electric shock or fire due  
to heat generation.  
5. Do not operate with wet hands or in  
damp environment. It may cause  
electric shock.  
6. Do not allow water to run into  
electric parts. It may cause failure of  
machine, electric shock or fire.  
7. Do not use the power cord near  
flammable gas or combustibles,  
such as gasoline, benzene, thinner,  
etc. It may cause an explosion or fire.  
9.Do not damage or use an  
unspecified power cord. It may  
cause electric shock or fire.  
10.Do not place heavy object on the  
power cord and ensure that the  
cord will not be compressed. There  
is danger of fire or electric shock.  
8. Do not use the power cord close to  
heating appliances. It may cause  
fire and electric shock.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety precautions  
05  
11.Do not open the unit during  
operation. It may cause electric  
shock or injury.  
12.Do not drink water drained  
from air conditioner. It contains  
contaminants and could make  
you sick.  
13.Do not disassemble or modify unit.  
It may cause failure of appliance  
and electric shock.  
14.When the air filter is to be  
removed, do not touch the metal  
parts of the unit. It may cause an  
injury.  
15.When the unit is to be cleaned,  
switch off, and turn off the circuit  
breaker. Do not clean unit when  
power is on as it may cause fire,  
electric shock or injury.  
16.Avoid direct exposure of occupants  
to air flow.  
17.Turn off the main power switch when  
not using the unit for a long time.  
18.The air conditioner may be dusted  
with an oil free cloth, or washed  
with a cloth dampened in a solution  
of warm water and mild dishwashing  
detergent. Rinse thoroughly and wipe  
dry. Wring excess water from cloth  
before wiping around controls.  
20.Always insert the filters securely.  
Clean filter once every two weeks.  
Operation without filters may  
cause failure.  
21.Always install circuit breaker and a  
dedicated power circuit. No  
installation may cause fire and  
electric shock.  
19.Ensure that the installation bracket of  
the outdoor unit will not damage  
due to prolonged exposure. If  
bracket damages, there will be  
concern of damage due to falling  
of unit.  
22.Do not place obstacles around air-  
inlets or inside of air-outlet. It may  
cause failure of appliance or  
accident.  
Download from Www.Somanuals.com. All ManualsSSeaarcfheAtnyd Dpowrneloacd.autions 06  
Choosing the installation site  
Installation Warnings  
1. Carefully read the installation manual before beginning.  
2. Follow each step as shown.  
3. Observe all local, state and national electric codes. This appliance must be  
installed by a qualified licensed HVAC technician in accordance with all  
applicable codes. All electrical connections should be performed by a licensed  
electrician.  
4. Pay attention to danger and safety notices  
Precautions for Installation  
Installation at the following sites may cause problems. If you must inevitably install  
the unit at one of these sites, please consult your local distributor beforehand:  
1. Sites with machine oil.  
2. Sites with a high concentration of salinity, such as coastal areas.  
3. Sites with sulfuric gas, such as hot water springs.  
4. Sites with high frequency equipment, such as wireless equipment, welding  
machines and medical installations.  
5. Sites with flammable gases or volatile material.  
6. Sites with special environmental conditions.  
7. Laundry rooms.  
Indoor Unit  
flammable gases.  
1. The unit must be installed at a site  
that does not obstruct the flow of  
air.  
7. The indoor unit must be at least 7.5  
feet (2.3 meters) from the ground.  
8. The site must allow for the easy  
removal of the connector pipe and  
drain hose.  
2. The site must support the weight of  
the indoor unit.  
3. The site must be easily accessible  
for maintenance and replacement  
of the air filter.  
9. The unit must be installed at a site  
protected from direct sunlight.  
4. The site must allow for the  
necessary space around the indoor  
unit, as shown in the sideward  
figure.  
More  
than 6"  
More  
than 5"  
5. There should be at least 3 feet (1  
meter) between the unit and radio  
or television devices. It is ideal  
that the unit be installed at the  
center.  
More  
than 5"  
More  
than 7.5'  
6. It must be far from fire, smoke or  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Choosing the installation site  
07  
More  
Outdoor Unit  
More  
More  
than 2 feet  
than 1 feet  
than 1 feet  
1. The outdoor unit must be  
installed at a convenient site  
that is not exposed to strong  
winds. The site should be dry  
and well ventilated.  
2. The site must support the weight  
of the outdoor unit and allow  
for vertical installation.  
More  
3. There must not be the possibility  
of increased noise and vibration  
at the site.  
More  
than 6.6 feet  
than 2 feet  
4. The unit must be installed at a  
site where the noise produced  
by its operation and air  
discharge does not disturb the  
neighbors or animals.  
5. The site cannot have any  
leakage of flammable gases.  
6. The site must provide enough  
space around the unit, as shown  
in the figure.  
7. Children must not be able to  
access the installation site.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Choosing the installation site 08  
Parts list  
NUMBER  
PART NAME  
QTY.  
1
1
2
3
4
5
6
Installation plate  
Clip anchor  
10  
8
Self-tapping screw A #7 X 1"  
Seal  
1
1
Drain Joint  
1
Connecting cable  
(capacity < 12000 Btu's)  
(capacity > 12000 Btu's)  
Ø1/4"  
Liquid side  
Ø3/8"  
Ø3/8"  
Ø1/2"  
Ø5/8"  
Connecting  
pipe  
assembly  
(capacity < 9000 Btu's)  
7
1
Gas side  
(capacity < 12000 Btu's)  
(capacity > 12000 Btu’s)  
8
9
1
2
1
Remote controller  
Self-tapping screw B #7X 3/4"  
10  
Remote Controller holder  
10 10  
9 9  
8 8  
Indoor unit  
4
5
1
3
2
Outdoor unit  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts list  
09  
1
More than 6"  
Indoor unit  
2
3
More than 5"  
6
6
7
More than 5"  
Air filter  
8
More than 2 feet  
More than 1 feet  
A
More  
than 2 feet  
4
10  
9
5
B
C
Outdoor  
More than 6.6 feet  
unit  
Attention  
1. This illustration is for explanation purposes only.  
2. Copper tubes must be insulated independently  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts list 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
6" or more from  
the ceiling  
Installation plate  
Indoor unit outline  
5" or more  
from the wall  
5" or more  
from the wall  
1.77"  
3.55"  
Refrigerant pipe  
hole (right) Ø 2.56"  
Refrigerant pipe  
hole (left) Ø 2.56"  
3.15  
19.27"  
36.25"  
(B)  
Capacity < 12000 Btu's  
Fixing the Installation Plate  
1. Install the installation plate  
horizontally over the structural  
parts on the wall using the spaces  
indicated on the plate, as shown  
in the figures above.  
Attention  
Fit the Installation Plate and drill holes  
in the wall according to the wall  
structure and corresponding mounting  
points on the installation plate  
(Dimensions are in “mm” unless  
otherwise stated).  
2. In the case of tiled, concrete or  
similar walls, create 0.2 inch  
diameter holes. Place anchorage  
supports for the appropriate  
assembly screws.  
Installation plate  
3. Fix the installation plate to the  
wall with eight A type screws.  
4. At all times securing to the wall  
studs is recommended.  
Drilling the Hole  
Wall  
1. Determine the position of the  
hole for the pipes using the  
installation plate and drill the  
pipe hole so that it is tilted slightly  
downward.  
Indoor unit  
Outdoor unit  
2. Always use a pipe cover with an  
opening when drilling.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit installation 12  
Connective pipe and drainage installation  
Connective pipe  
Pipe cover  
(right)  
Pipe  
holder  
Pipe cover  
(left)  
1. For the left-hand and right-hand  
piping, remove the pipe cover from  
the side panel. The pipe cover  
must be kept as it may be used  
when relocating the air conditioner  
to any other place.  
Left piping  
Rear left  
piping  
Rear right  
piping  
Right piping  
2. For the rear-right-hand and rear-left-  
hand piping, install the piping as  
shown in the sideward figure. Bend  
the connective pipe to be laid at  
a height of 1.69 inches or less from  
Connective  
pipe  
Indoor unit  
outline  
Fix the end of the  
the wall.  
connective pipe.  
Drainage  
Do not block  
water flow  
by a rise.  
Do not block  
water flow  
by a rise.  
1. Run the drain hose sloping  
downward. Do not install the drain  
hose as illustrated sideward.  
2. When connecting extension drain  
hose, insulate the connecting part  
of extension drain hose with a  
shield pipe, do not let the drain  
hose slack.  
Do not put the end  
of drain hose into water.  
Fastening the Indoor Unit  
Upper hook  
1. Pass the piping through the hole in  
the wall.  
2. Put the upper claw at the back of  
the indoor unit on the upper hook of  
the installation plate, move the  
indoor unit from side to side to see  
that it is securely hooked.  
Lower hook  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit installation  
13  
3. Piping can easily be made by  
lifting the indoor unit with a  
cushioning material between the  
indoor unit and the wall. Get it  
out after finish piping.  
4. Push the lower part of the indoor  
unit up on the wall, Then move  
the indoor unit from side to side,  
up and down to check if it is  
hooked securely.  
Cushioning  
material  
Piping and wrapping  
Ponding  
box  
1. Bundle the tubing, connecting  
cable, and drain hose with tape  
securely and evenly as shown  
in the sideward figure.  
Indoor unit  
Cable  
connection  
Pipe room  
2. Because the condensed water  
from rear of the indoor unit is  
gathered in ponding box and is  
piped out of room, do not put  
anything else in the box.  
Connective  
pipe  
Wrapping  
belt  
Drain hose  
Attention  
1. Connect the indoor unit first, then the outdoor unit.  
2. Do not allow the piping to let out from the back of the indoor unit.  
3. Be careful not to let the drain hose slack.  
4. Both of the auxiliary piping should be heat insulation.  
5. Be sure that the drain hose is located at the lowest side of the bundle. Locating  
at the upper side may cause drain pan to overflow inside the unit.  
6. Never intercross nor intertwist the power wire with any other wiring.  
7. Run the drain hose sloped downward to drain out the condensed water  
smoothly.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit installation 14  
Outdoor unit installation  
1. Install the outdoor part of the unit  
on a rigid surface to avoid excess  
noise and vibration.  
2. Direct the air vent toward an area  
without obstacles.  
3. Install the unit at the site where it is  
to as little wind as possible,  
exposed  
especially in areas where it is  
frequently windy.  
4. If the installation site is exposed to  
heavy winds, such as in coastal  
areas, place the unit along the  
widest part of the wall or use  
protective plates.  
5. Be sure there is no obstacle which  
blocks radiating air, including  
schrubs or bushes.  
Strong wind  
OutdooDrowunlnoaidtfroimnWswtwa.Slolmaatnuiaolsn.com. All Manuals Search And Download.  
15  
A
Air inlet  
Settlement of outdoor unit  
Anchor the outdoor unit tightly and  
horizontally on a concrete or rigid  
mount with a bolt and nut 0.39 inch  
or 0.32 inch diameter (Purchasedy  
separately).  
Air  
inlet  
B
Air outlet  
A (inch)  
B (inch)  
Outdoor unit dimension inch(WxHxD)  
2.30'x1.76'x0.77'  
1.50'  
1.51'  
1.80'  
1.74'  
1.84'  
0.82'  
0.91'  
0.91'  
0.95'  
1.10'  
2.25'x1.41'x0.85'  
2.56'x1.77'x0.82'  
2.49'x1.94'x0.94'  
2.77'x2.28'x1.10'  
Drain joint installation  
Fit the seal into the drain elbow, then  
insert the drain joint into the base  
pan hole of outdoor unit, rotate 90o to  
securely assemble them. Connect  
the drain joint with an extension  
drain hose (Locally purchased), in  
case of the water draining off the  
outdoor unit during the heating  
mode or rainy season.  
Base pan hole  
of outdoor unit  
Seal  
+
=
Seal  
Drain joint  
Drain pipe  
Download from Www.Somanuals.com.OAll Muatnduaols SoearrchuAnndiDtoiwnnlosatd.allation 16  
Refrigerant piping connection  
Unit comes with 16.4 feet tubing bundle. It is not recommended to cut. If too  
long, loop for excess.  
Note: Keep original bend so not kinking of the tube occurs.  
Flaring work  
Main cause for refrigerant leakage is  
due to defect in the flaring work.  
Pipe  
Carry out correct flaring work using the  
following procedure:  
1. Cut the pipes and the cable.  
A) Use the piping kit accessory or  
pipes purchased locally.  
Correct  
Wrong  
Oblique Roughness Burr  
B) Measure the distance between the  
indoor and the outdoor unit.  
C) Cut the pipes a little longer than the  
measured distance.  
D) Cut the cable 4.92 feet longer than  
the pipe length.  
2. Burr removal  
Pipe  
A) Completely remove all burrs from  
the cut cross section of pipe/tube.  
Reamer  
Point  
down  
B) Put the end of the copper  
tube/pipe in a downward direction  
as you remove burrs in order to  
avoid dropping burrs into the  
tubing.  
Flare nut  
3. Put nut on.  
Remove flare nuts attached to  
indoor and outdoor unit, then put  
them on pipe/tube having  
completed burr removal.(It is not  
possible to put them on after flaring  
work)  
Cooper tube  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant piping connection  
17  
4. Flaring work.  
Firmly hold copper pipe in a  
die in the dimension shown in  
the table below.  
Bar  
Copper  
pipe  
Handle  
A (inch)  
OUTER  
Yoke  
Red arrow mark  
DIAMETER (inch)  
Min.  
Max.  
0.051  
0.063  
0.071  
0.095  
0.028  
0.039  
0.039  
0.087  
1/4  
3/8  
1/2  
5/8  
Clamp  
handle  
Connection Adjustment  
1. Align the pipes to be connected.  
Caution: Excessive twisting may  
break the nut, depending on the  
installation conditions.  
2. Screw the flare nut with your  
fingers, and then tighten it with  
a spanner and torque wrench,  
as shown in the following figure.  
Pipings  
Indoor unit  
tubing  
Flare  
nut  
OUTER  
TIGHTENING  
.
TORQUE (lbf in)  
ADDITIONAL TIGHTENING  
.
TORQUE (lbf in)  
DIAMETER (inch)  
1/4  
3/8  
1/2  
5/8  
139  
260  
434  
651  
174  
304  
477  
694  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant piping connection 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect the cable to the indoor unit  
Electrical box  
cover  
1. The inside and outside connecting  
cable can be connected without  
removing the front grille.  
2. Connecting cable between indoor  
unit and outdoor unit shall be  
approved polychloroprene  
sheathed flexible cord, type  
designation 16AWG or heavier  
cord.  
3. Lift the indoor unit panel up,  
remove the electrical box cover by  
loosening the screw.  
4. Ensure the colour of wires of  
outdoor unit and the terminal Nos.  
are the same to the indoors  
respectively.  
5. Wrap those cables not connected  
with terminals with insulation  
tapes, so that they will not touch  
any electrical components. Secure  
the cable onto the control board  
with the cord clamp.  
< 12000 btu's CABLE  
(Heating and cooling model)  
or  
"Cable A"  
Code wire  
"Cable B"  
Code wire  
1.57"  
1.57"  
< 12000 btu's CABLE (Cooling model)  
0.39"  
0.39"  
Code wire  
> 12000 btu's CABLE  
1.57"  
0.39"  
(Heating and cooling model)  
"Cable C”  
Code wire  
1.57"  
0.39"  
Download from Www.Somanuals.com. All Manuals SearchEAnldeDcotwrnliocada. l work 20  
9000 and 12000 Btu's  
COOLING MODEL  
9000 and 12000 Btu's  
HEATING AND COOLING MODEL  
Terminal block of indoor unit  
"Connector A" or "Connector B"  
Terminal block of indoor unit  
1
2
3
4
1
2(N)  
3
4
1
2(N)  
3
4
or  
To Outdoor Unit  
To outdoor  
unit  
To outdoor  
unit  
18000 Btu's  
HEATING AND COOLING MODE  
"Connector A"  
Terminal block of indoor unit  
To outdoor  
unit  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical work  
21  
Connect the cable to the outdoor unit  
1. Remove the electrical control  
board cover from the outdoor unit  
by loosening the screw.  
2. Connect the connective cables to  
the terminals as identified with  
their respective matched numbers  
on the terminal block of indoor  
and outdoor units. The connective  
cable to power supply shall be  
approved polychloroprene  
Cover  
Screw  
sheathed flexible cord.  
3. Secure the cable onto the control  
board with the cord clamp.  
4. To prevent the ingress of water,  
form a loop of the connective  
cable as illustrated in the  
installation diagram of indoor and  
outdoor units.  
5. Insulate unused cords (conductors)  
with PVC-tape. Process them so  
they could not touch any electrical  
or metal parts.  
< 12000 btu's CABLE  
(Heating and cooling model)  
or  
"Cable D”  
"Cable E”  
Code wire  
Code wire  
1.57"  
1.57"  
0.39"  
0.39"  
< 12000 btu's CABLE (Cooling model)  
Code wire  
> 12000 btu's CABLE  
(Heating and cooling model)  
"Cable F”  
Code wire  
1.57"  
0.39"  
1.57"  
0.39"  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical work 22  
9000 and 12000 Btu's  
COOLING MODEL  
9000 and 12000 Btu's  
HEATING AND COOLING MODEL  
"Conector A" or "Conector B"  
Terminal block of outdoor unit  
Terminal block of outdoor unit  
N
1
2
3
4
L
G
1
2(N)  
3
4
1
2(N)  
3
4
Cables  
board  
Cables  
board  
Cord clamp  
"Conector C” or "Conector D”  
Terminal block of outdoor unit  
To power supply  
To indoor unit  
2(N)  
3
1
4
2(N)  
3
1
4
Cables  
board  
Cables  
board  
18000 Btu's  
HEATING AND COOLING MODEL  
"Conector A" or "Conector B"  
Terminal block of outdoor unit  
2(N)  
1
S
N
L
o
Cables  
board  
Cables  
board  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical work  
23  
Caution  
After the confirmation of the above conditions, prepare the wiring as follows:  
1. Never fail to have an individual power circuit specifically for the air  
conditioner. As for the method of wiring, be guided by the circuit diagram  
posted on the inside of control cover.  
2. The screws which fasten the wiring in the casing of electrical fittings are  
liable to come loose from vibrations to which the unit is subjected during  
the course of transportation. Check them and make sure that they are all  
tightly fastened. (If they are loose, it could cause burn-out of the wires.)  
3. Specification of power source.  
4. Confirm that electrical capacity is sufficient.  
5. See to that the starting voltage is maintained at more than 90 percent of  
the rated voltage marked on the name plate.  
6. Confirm that the cable thickness is as specified in the power source  
specification.  
7. Always install an earth leakage circuit breaker in a wet or moist area.  
8. The following would be caused by voltage drop: vibration of a magnetic  
switch, which will damage the contact point, fuse breaking, disturbance of  
the normal function of the overload protector.  
9. The means for disconnection from a power supply shall be incorporated  
in the fixed wiring and have an air gap contact separation of at least 0.12  
inch in each active (phase) conductors.  
Air purging  
Air and moisture in the refrigeration system have undesirable effects as indicated  
below:  
1. Pressure in the system rises.  
2. Operating current rises.  
5. Water may lead to corrosion of  
parts in the refrigeration system.  
Therefore, the indoor unit and tubing  
between the indoor and outdoor unit  
must apply leakage test and be evacuated  
to remove any noncondensables and  
moisture from the system.  
3. Cooling or heating(only for  
models with heating function)  
efficiency drops.  
4. Moisture in the refrigerant circuit  
may freeze and block capillary  
tubing.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical work and air purging 24  
Air purging with vacuum pump  
1. Check that each tube(both liquid and gas side tubes) between the indoor and  
outdoor units have been properly connected and all wiring for the test run has  
been completed. Remove the service valve caps from both the gas and the  
liquid side on the outdoor unit. Note that both the liquid and the gas side  
service valves on the outdoor unit are kept closed at this stage.  
2. When relocating the unit to another place, perform evacuation using vacuum  
pump.  
3. Pipe length and refrigerant amount:  
Air  
purging  
Additional amount of  
Connective  
pipe length  
refrigerant to be charged  
Less than 16.4' Use vacuum pump.  
16.4'~32.8'  
Use vacuum pump.  
R410A: 0.71ozs/ft (Pipe length-16.4')  
Caution in handling the packed valve integrated in the outlets of  
outdoor unit.  
1. Operation of opening packed valve: Open the valve stem until it hits against  
the stopper. Do not try to open it further.  
2. Operation of closing packed valve: Securely tighten the valve stem with a special  
tool. Then securely tighten the valve stem cap with a spanner or the like. Refer to  
tightening torque table in page 17 for valve stem cap tightening torque  
Note: There is a charging port integrated in the low side outlet, but not in the  
high side outlet. The low side outlet is shown in the sketch map below.  
Flare nut  
Refrigerant  
Valve body  
Outdoor unit  
Indoor unit  
Gas  
A
C
Cap  
D
Charge port  
B
Packed valve  
Valve stem  
Stopper  
Half union  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air purging  
25  
When using the vacuum pump  
For method of using a manifold valve, refer to its operation manual.  
Indoor unit  
1. Completely tighten the flare nuts at  
connection point A, B, C and D.  
Connect valve core removal tool to  
the charging port, then connect  
vacuum hose to valve core tool.  
Open the schrader valve.  
Outdoor unit  
Note: The schrader valve is inside  
the charging port.  
2. Connect the other charge hose of  
manifold valve to the vacuum pump.  
3. Fully open the handle Lo of the  
manifold valve.  
Manifold valve  
-76cm/Hg  
Charge  
hose  
4. Operate the vacuum pump to  
evacuate. After starting evacuation,  
slightly loose the flare nut of the  
Lo valve on the gas pipe side and  
check if the air is entering (Operation  
noise of the vacuum pump changes  
and a compound meter indicates  
0 instead of minus), then tighten  
the flare nut. The procedure verifies  
if there are blocks inside the tubes.  
Handle Hi  
Handle Lo  
Charge hose  
Vacuum pump  
5. Make evacuation for 15 minutes  
or more and check that the  
compound meter indicates  
display in the pressure indicator is  
a little higher than the atmosphere  
pressure. This procedure verifies if  
the refrigerant goes through the  
tubes correctly.  
5
5
-7.6 x 10 μmHg (-1x10 Pa).  
After the evacuation is completed,  
fully close the handle Lo of the  
manifold valve and stop the  
operation of the vacuum pump.  
7. Close the schrader valve, then  
remove the valve core tool.  
Replace the charging port cap.  
8. Fully open the packed valve  
stems B and A.  
6. Turn the stem of the packed  
valve B about 45o  
counterclockwise for 6~7  
seconds after the gas comes  
out, then tighten the flare nut  
again. Make sure the pressure  
9. Securely tighten the cap of the  
packed valve.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air purging 26  
Electrical safety  
Perform the electric safety check after completing installation:  
1. Insulated resistance: The insulated resistance must be more than 2M  
.
2. Grounding work: After finishing grounding work, measure the grounding  
resistance by visual detection and grounding resistance tester. Make sure the  
grounding resistance is less than 4  
.
3. Electrical leakage check (performing during test running): During test operation  
after finishing installation, the serviceman can use the electric probe and  
multimeter to perform the electrical leakage check. Turn off the unit  
immediately if electrical leakage happens. Check and find out the solution  
ways till the unit operates properly.  
Gas leak check  
Soap water method  
indoor unit  
Apply a soap water or a liquid neutral  
check point  
detergent on the indoor unit  
connection or outdoor unit connections  
by a soft brush to check for leakage of  
the connecting points of the piping. If  
bubbles come out, the pipes have  
leakage point.  
Cover  
Outdoor unit  
check point  
Leak detector  
Use the leak detector to check for  
leakage.  
Caution  
A: Lo packed valve, B: Hi packed valve  
C and D are ends of indoor unit  
connection.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical safety and gas leak check  
27  
Test running  
Perform test operation after completing gas leak check at the flare nut  
connections and electrical safety check.  
1. Connect the power, press the ON/OFF button on the remote controller to  
turn the unit on.  
2. Use the MODE button to select COOL, HEAT(Only for models with heating  
function), AUTO and FAN to check if all the functions work well.  
3. When the ambient temperature is too low(lower than 63oF), the unit  
cannot be controlled by the remote controller to run in cooling mode,  
manual operation can be taken. Manual operation is used only when the  
remote controller is disable or maintenance necessary.  
Auto/Cool  
Manual control button  
or  
Manual control  
button  
Auto  
Cool  
Download from Www.Somanuals.com. All Manuals Search And TDoewsnltoadr.unning 28  
Preparing the device for operation  
1. Contact a specialist to install the device.  
2. Guarantee that the unit is appropriately fastened and complies with all of  
the aforementioned safety norms.  
3. Before operating the air conditioner, ensure that the air filter is installed  
correctly.  
4. If the unit has been out of use for a long period of time, it is recommended  
that the air filter be cleaned before use. During continuous use, clean the air  
filter every two weeks.  
5. This air conditioner was designed for use under the following conditions:  
MODE  
*
Cool  
Heat  
Temperature  
Indoor Outdoor  
Dehumidifier  
Temperature  
Temperature  
Indoor  
Outdoor  
Indoor  
Outdoor  
63°F~90°F 64°F~109°F 63°F~86°F 19°F~75°F 63°F~90°F 52°F~109°F  
only for models with heating function  
*
Attention  
If air conditioner is used outside of the above conditions, certain safety protection  
features may come into operation and cause the unit to function abnormally.  
Room relative humidity should be less than 80%. If the air conditioner operates in  
excess of this figure, the surface of the air conditioner may attract condensation.  
Please set the horizontal louver to its maximum angle (vertically to the floor), and  
set HIGH fan mode.  
Optimum performance will be achieved within these operating temperature.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preparing the device for operation  
29  

Cortelco Telephone 2740 User Manual
Craftsman Air Compressor 92116638 User Manual
Crown Audio Microphone CM 31 User Manual
Curtis Stereo System IP1490UK User Manual
Desa Thermostat RM200T User Manual
Everpure Water System EV9273 69 User Manual
Fisher Price Crib J6982 User Manual
Fujitsu VCR MB2198 01 User Manual
Garland Range C0836 10 User Manual
GE Washer 175D1807P270 User Manual