Intelligent Technologies (IT.)
D77A I/O Module Products
Installation and User Manual
November 2006
Supersedes October 2005
Part Numbers
D77A-DI8
D77A-RQ8
D77A-DI16
D77A-DQ8
D77A-DQ16
D77A-AI8
D77A-RQ16
D77A-DI8DQ8
D77A-DI8RQ8
D77A-AI8AQ8
D77A-AI8RQ8
D77A-NI4
D77A-AI16
D77A-AQ8
D77A-AQ16
D77A-NQ2
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Important Notice — Please Read
The product discussed in this literature is subject to terms and conditions outlined in Eaton Electrical Inc. selling policies. The sole
source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton Electrical Inc. selling policy.
NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE
INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton Electrical Inc. be responsible
to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or
consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system,
cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its
customers resulting from the use of the information, recommendations and descriptions contained herein.
The information contained in this manual is subject to change without notice.
®
Cover Photo: Eaton’s Cutler-Hammer Intelligent Technologies (IT.) D77A I/O Module Products
MN05002001E
i
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table of Contents
LIST OF FIGURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
LIST OF TABLES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v
Definitions and Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v
Hazardous High Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v
General Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Component Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Catalog Numbering System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Physical Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Surge Suppression. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Environmental Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Device Default I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
I/O Module Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Output Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Special I/O Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
THEORY OF OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Out-of-box Default Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Typical Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
I/O Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Setting Group ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
QCPort Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
TROUBLESHOOTING AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Renewal Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Communication Troubleshooting Hints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
APPENDIX A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Analog Data Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
IT. PUBLICATIONS AND SUPPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
ii
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
List of Figures
Figure 1: I/O Module Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 2: Module Physical Dimensions, mm [in] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 6: Analog Input Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 7: AC Output Module Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 8: DC Output Module Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 9: Relay Output Module Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 11: Analog Output Curves for 14 Bit Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 17: Discrete Input Module Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 19: Discrete Combination Module Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 22: Group ID Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 25: Lock DIN Rail Locking Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 29: Lock DIN Rail Locking Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 31: QCPort Backplane Interconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 32: QCPort Interconnect Backplane Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 34: I/O Property Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 38: AC Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 39: DC Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 40: Relay Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 41: Analog Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
List of Tables
Table 1: Approvals/Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 2: Catalog Numbering System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 3: Environmental Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 11: 2 Channel Analog Output Module (Consumed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 15: D77A-NI4 Analog Input Module Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
MN05002001E
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 19: D77A-NQ2 Analog Output Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 24: Analog Input Signal Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 26: Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 27: Analog 10 Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 28: Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 30: Explanation of LED Duty Cycle States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 31: Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Table 41: 0x006F (111) 16 bit Signed Analog Input Data (Available in I/O As Control Elements). . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 43: 0x8001 (32769) Device Identity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 46: 0x8004 (32772) Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 47: 0x8005 (32773) QCPort Baud Rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 51: 0x8009 (32777) Production Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 57: 0x800F (32783) Language Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 61: 0x804D (32845) Physical Node ID Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 62: 0x80CF (32975) Analog Output Communication Loss Behavior. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 66: Register 1; Serial Number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 69: IT. Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
iv
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Safety
Servicing and operating this I/O system, like all industrial control components and systems, involves significant hazards. The most
obvious hazard is that of electrical shock. These hazards are not limited to electrical shock. They also involve hazards related to
managing energy that is converted from electricity into mechanical energy as motors, solenoids controlled valves and other
equipment perform work. Every effort is made to provide the safest equipment possible. Every effort is made to provide the safest
operating and servicing procedures possible. It is, however, the user’s responsibility to ensure that the design and application are safe
and appropriate.
Throughout this document are found various safety warnings. Observe these messages carefully. Each is described as follows:
Definitions and Symbols
WARNING
AVERTISSEMENT
ADVERTENCIA
This symbol indicates high voltage. It calls
your attention to items or operations that
could be dangerous to you and other
Ce symbole indique la haute tension. Il sert à Este símbolo indica alto voltaje. Le llama su
attirer votre attention aux articles et
opérations qui pourraient vous être
atención en cuanto a artículos u operaciones
que pueden ser peligrosas para usted y
otras personas que operan este equipo. Lea
el mensaje y siga cuidadosamente las
instrucciones.
persons operating this equipment. Read the dangereux, ainsi qu’à tout autre personne
message and follow the instructions
carefully.
utilisant cet équipement. Lisez ce message
et suivez prudemment les instructions.
.
CAUTION
PRÉCAUTION
PRECAUCIÓN
Indicates a potentially hazardous situation
Indique une situation potentiellement
Indica que existe una situación
which, if not avoided, can result in minor to dangereuse qui, si elle n’est pas évitée, peut potencialmente peligrosa, que si no es
moderate injury, or serious damage to the
product. The situation described in the
CAUTION may, if not avoided, lead to
serious results. Important safety measures
are described in CAUTION (as well as
WARNING).
entraîner des blessures mineures à
evitada, podrá resultar en heridas
corporales menores o moderadas, o en
serios daños al producto. La situación
descrita en la PRECAUCIÓN podrá causar
serios resultados si no es evitada. Medidas
importantes de seguridad son descritas en la
PRECAUCIÓN (como también en la
ADVERTENCIA).
modérées ou de graves dégâts au produit.
La situation décrite dans l’article intitulé
PRÉCAUTION peut, si elle n’est pas évitée,
mener à de sérieux résultats. Les mesures
de sécurité importantes sont décrites dans
les articles intitulés PRÉCAUTION (aussi
bien que AVERTISSEMENT).
Hazardous High Voltage
WARNING
AVERTISSEMENT
ADVERTENCIA
Some control equipment and electronic
Des commandes électroniques et
Algunos equipos de control y controladores
controllers are connected to hazardous line équipement de commande sont connectés à electrónicos están conectados a tensiones
voltages. When servicing the I/O system,
related starters and other electronic
controllers, there may be exposure to
des lignes de tension dangereuse. Lors de
l’entretien du système I/O, des démarreurs
et des commandes électroniques connexes, otros controladores electrónicos, pueda que
de línea peligrosas. Al darle servicio al
sistema de I/O, arranques relacionados y
components with housings or protrusions at vous pourrez être exposé à des composants hayan componentes expuestos con carcasas
or above line potential. Extreme care should dont le boîtier et les protubérances
be taken to protect against shock. Stand on conduisent la tension de la ligne, voire
an insulating pad and make it a habit to use même supérieure. Vous devriez faire
only one hand when checking components. extrêmement attention à vous protéger
Always work with another person in case an contre les électrochocs. Tenez-vous sur un
emergency occurs. Disconnect power before tapis isolant et habituez-vous à n’utiliser
o protuberancias en el potencial de línea o
más altos. Se deberá tener extremo cuidado
para protegerse contra electrochoque.
Párese sobre un tapete aislante y habitúese
a usar sólo una mano al comprobar
componentes. Siempre trabaje con otra
persona en caso que ocurra una
checking controllers or performing
qu’une main quand vous contrôlez des
maintenance. Be sure equipment is properly composants. Travaillez toujours en
emergencia. Desconecte la energía antes de
comprobar controladores o efectuar
mantenimiento. Asegúrese de que el equipo
esté conectado apropiadamente a tierra. Use
grounded. Wear safety glasses whenever
working on electronic components or
industrial machinery.
compagnie d’une autre personne en cas
d’urgence. Coupez le courant avant de
vérifier les commandes ou de réaliser
l’entretien. Assurez-vous que l’équipement gafas de seguridad cuando trabaje en
est correctement mis à la terre. Portez des
lunettes de sécurité quand vous travaillez
sur des composants électroniques ou la
machinerie industrielle.
componentes electrónicos o en maquinas
industriales.
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
v
Intelligent Technologies (IT.) D77A I/O Module Products
General Safety
Notice
Avis
Aviso
Make sure you read and understand the
installation procedures in this manual
Assurez-vous de lire et comprendre les
Asegúrese de leer y comprender los
procédures d’installation comprises dans ce procedimientos de instalación dados en este
before you attempt to operate or set up the manuel avant d’essayer d’utiliser ou
manual antes de intentar operar o
configurar el equipo.
equipment.
d’installer l’équipement.
WARNING
AVERTISSEMENT
ADVERTENCIA
This instruction manual should be used for Ce mode d’emploi devrait être utilisé pour
Este manual de instrucciones deberá ser
usado para instalar, configurar y operar
apropiadamente el IT. Módulos I/O D77A El
instalar y mantener impropiamente este
producto podrá resultar en serias heridas
corporales o en daños a la propiedad. Antes
proper installation, setup and operation of
installer ou opérer correctement les
the IT. D77A I/O modules. Improperly
modules IT. D77A I/O. Mal installer et
installing and maintaining this product can maintenir ce produit peut entraîner de
result in serious personal injury or property graves blessures corporelles ou de grands
damage. Before attempting installation,
setup or operation, read and understand this l’installer ou de l’utiliser, lisez et comprenez de comenzar la instalación, configuración o
dégâts matériels. Avant d’essayer de
entire manual.
ce manuel dans son intégralité.
la operación, lea y comprenda el manual
completo.
WARNING
AVERTISSEMENT
ADVERTENCIA
Hazardous voltage can cause electric shock La tension dangereuse peut causer des
and burns. Always disconnect power before électrochocs et des brûlures. Coupez
Los voltajes peligrosos pueden causar
electrochoque y quemaduras. Siempre
desconecte la energía antes de proceder con
cualquier trabajo en este producto.
proceeding with any work on this product.
toujours le courant avant d’entreprendre
tout travail sur ce produit.
WARNING
AVERTISSEMENT
ADVERTENCIA
Only apply 24V DC to the I/O module power N’appliquez que du courant continu de 24 V Sólo aplique 24V CD a los terminales de
terminals. Use of any other voltage may
result in personal injury, property damage
and damage to the IT. D77A I/O module.
aux bornes de courant des modules I/O.
L’emploi de toute autre tension peut
entraîner des blessures corporelles, des
dégâts matériels et des dégâts au module
IT. D77A I/O.
energía del módulo I/O. El uso de cualquier
otro voltaje podrá resultar en heridas
corporales, daños a la propiedad o daños al
IT. Módulo I/O D77A.
WARNING
AVERTISSEMENT
ADVERTENCIA
To provide continued protection against fire Pour fournir une protection continue contre Con el fin de suministrar protección
or shock hazard, the complete IT. D77A I/O
modules must be replaced if they become
inoperative.
le risque d’incendie ou d’électrochoc, les
continua contra peligro de fuego o
modules IT. D77A I/O complets doivent être electrochoque, los módulos I/O D77A
remplacés s’ils deviennent inopérables.
completos del IT. tendrán que ser
reemplazados si se tornan inoperantes.
vi
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Introduction
Description
®
®
Cutler-Hammer Intelligent Technologies (IT.) D77A I/O Modules from Eaton Corporation are part of the IT. family of products that
are best by design. These modules are designed and built for industrial applications with standard features including removable
locking terminal blocks and connectivity to IT. motor control. The size and features are a substantive engineering and marketing effort,
involving extensive customer input. For more information on the IT. family of products, visit our website:
IT. D77A I/O discrete modules are available in 8 and 16 point densities, and in AC or DC voltage configurations. Input modules have
two points per isolated common. Output modules are available in relay and solid-state configurations with two points per isolated
common.
The IT. D77A I/O analog modules are available in variable voltage and current loop modules. Input modules support four analog
channels and output modules support two analog channels.
D77A I/O products are designed for industrial applications, installed in a manner consistent with the guidelines outlined in this
document. They are designed for Pollution Degree 2 environments (clean and dry).
Component Characteristics
This section identifies special features engineered into the Cutler-Hammer IT. D77A I/O modules.
All Modules
The IT. D77A I/O modules have the following common features:
• LED Status — When the LED is illuminated the proper ON state signal is received at the input or at the output point.
• Removable Lockable Terminals — Terminals are easily removable for I/O module replacement and are lockable so they will not
vibrate loose. Terminals are available in screw type, cage clamp and insulation displacement.
• Terminal Identification — Each terminal is marked for ease of wiring and troubleshooting.
• Isolation — Each module is optically isolated between the field I/O and the backplane communication.
• Securing Tabs — Each I/O module has a locking mechanism to secure it to the DIN rail.
• Barrier Type Terminals — Each terminal has a barrier to minimize shorting of field wiring.
Discrete Input Modules
The IT. D77A Input modules have the following common feature:
• Adjustable Debounce — Each point has adjustable debounce from 1 to 65 ms.
• Sink/source — Each DC input module has back-to-back LEDs in the optical isolating circuit that can accept sinking or sourcing
signals.
Discrete Output Modules
The IT. D77A I/O Output modules have the following common features:
• Configurable Safe State — Each output point has a loss of communication safe state setting.
• Configurable Power ON State — Each output point has a power-up setting.
MN05002001E
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Discrete Combination Modules
The input and output features found in the input and output modules are also found in the combination modules.
Analog Input Modules
• Four Analog Channels — Each module has four analog input channels.
• Adjustable Input Filter — Each analog channel can be set for frequencies between 50 and 500 Hz.
• Type Selection — Each analog channel can be set as a voltage input or a current loop input.
Analog Output Modules
• Two Analog Channels — Each analog channel has two analog output channels.
• Type Selection — Each module can be set as a voltage output or a current loop output.
Approval Certifications
Table 1: Approvals/Certifications
Standard
Approval/Certifications
Agency Certifications
UL 508
CE (Low Voltage Directive, ATEX Directive)
CUL (CSA C22.2 No. 14)
Radiated and Conducted Emissions
Electrical/EMC
EN 5011 Class A
ESD Immunity (IEC 61000-4-2)
Radiated Immunity (IEC 61000-4-3)
Fast Transient (IEC 61000-4-4)
8 kV air, 4 kV contact
10 V/m 80 – 1000 MHz, 80% amplitude modulation @ 1 kHz
2 kV supply and control
1 kV communications
Surge (IEC 61000-4-5)
1 kV line-to-line
2 kV line-to-ground
RF Conducted (IEC 61000-4-6)
Magnetic Field (IEC 61000-4-8)
Ingress Protection Code
10V, 0.15 – 80 MHz
30 A/m, 50 Hz
IP20
MN05002001E
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Catalog Numbering System
Catalog numbers have three or five groups of characters, depending on the kind of module the catalog number represents. The
catalog numbering system used for IT. D77A I/O modules is illustrated as follows:
For discrete digital and analog I/O, the first four positions in the first group indicate the product family. The next two places in the
second group indicate the I/O type. The third group uses one or two places to indicate the number of points in the module. The last
group is used only for combination modules.
Table 2: Catalog Numbering System
D77A
-
A Q 16 XX
Product Line Prefix
D77A = I/O Module Products
Expansion Module
DQ8 (DC Output, 8 Points)
RQ8 (Relay Output, 8 Points)
AQ8 (AC Output, 8 Points)
I/O Type
A = AC
Number of Points
2 = 2 Points
4 = 4 Points
D = DC
R = Relay
N = Analog
8 = 8 Points
16 = 16 Points
Input or Output
I = Input
Q = Output
MN05002001E
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Specifications
Physical Description
a
j
b
I
24V 8Pt
I
24V 8Pt
i
0
2 IT.
14
0
2 IT.
14
12
4
12
4
6
6
10
10
8
8
h
g
0
1
0
0
1
1
C0
C0
C0
2
3
2
3
2
3
c
f
C1
C1
C1
4
5
4
5
4
5
e
d
D
I
C2
6
C2
6
C2
8
6
7
7
7
C3
C3
C3
D77A-001
Figure 1: I/O Module Component Location
a) Number of points
b) Terminal Blocks (Removable)
c) DIN Rail Locking Tab
d) D77 Part Number
e) QC Port, Backplane Connector
f) I/O Status LED
g) Group ID Selector Switch (Address)
h) Status LED
i) I/O Type (“I” for Input, “Q” for Output)
j) Voltage (AC, DC, Relay, Analog)
MN05002001E
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Dimensional Data
90
[3.5]
90
[3.5]
22.5
[0.9]
45
[1.8]
68
[2.7]
12
[0.5]
a
b
D77A-002
Figure 2: Module Physical Dimensions, mm [in]
a) Single Wide Module
b) Double Wide Module
Note: Ventilation requirements necessitate a minimum of 50 mm (2 in) on the top and bottom of each module and to each side of a
module grouping.
Power Requirements
The current draw for the IT. D77A I/O modules can be found in the module specification table for each specific module type. When
specifying the 24 volt DC power supply, the power rating must support the sum of all the modules’ current draw added to the system
power requirements.
For more information on the sizing of power supplies, refer to the IT. QCPort System Install and Planning Guide (Publication No.
MN05001002E).
Surge Suppression
IT. D77A Discrete I/O output modules have built-in surge suppression (snubbers) to reduce the effects of transient voltages. When
connecting output devices that have inductive loads (e.g., solenoids, relays, motor starters, etc.) additional surge suppression is
recommended and should be added across the load. The addition of customer-supplied surge suppression for inductive loads
prolongs the D77A output life.
MN05002001E
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Environmental Specifications
Table 3: Environmental Ratings
Category
Description
Specification
Transportation
and Storage
Temperature
Humidity
-50°C to 80°C [-58°F to 176°F]
5 – 95% non-condensing
Operating
Temperature
-25°C to 55°C [-13°F to 131°F]
0°C to 55°C [32°F to 131°F] (analog I/O only)
Humidity
Altitude
5% – 95% non-condensing
Above 2000 meters [6600 feet] consult factory
Shock
(IEC 68-2-27)
15G any direction for 11 milliseconds
Relay Operation 8G any direction
Vibration
(IEC 68-2-6)
5 – 150 Hz, 5G, 0.7 mm maximum peak-to-peak
Relay Operation 10 – 55 Hz, 3G, 0.7 mm maximum peak-to-peak
Pollution Degree
Devices are intended to be installed in a pollution degree 2
environment.
Device Default I/O Data
The following tables display the device default data mapping for D77A I/O modules as the data would appear on a network.
Table 4: 8 Point Discrete Input Module (Produced)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte
I7
I6
I5
I4
I3
I2
I1
I0
0
Table 5: 8 Point Discrete Output Module (Consumed)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte
Q7
Q6
Q5
Q4
Q3
Q2
Q1
Q0
0
Table 6: 16 Point Discrete Input Module (Produced)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte
I7
I6
I5
I4
I3
I2
I1
I9
I0
I8
0
1
I15
I14
I13
I12
I11
I10
Table 7: 16 Point Discrete Output Module (Consumed)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte
Q7
Q6
Q5
Q4
Q3
Q2
Q1
Q9
Q0
Q8
0
1
Q15
Q14
Q13
Q12
Q11
Q10
Table 8: 16 Point Discrete Combination Module (Produced)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte
I7
I6
I5
I4
I3
I2
I1
I0
0
Table 9: 16 Point Discrete Combination Module (Consumed)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte
Q7
Q6
Q5
Q4
Q3
Q2
Q1
Q0
1
Table 10: 4 Channel Analog Input Module (Produced)
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
WORD
SB *
SB *
SB *
SB *
Analog Input Data/Channel 0
Analog Input Data/Channel 1
Analog Input Data/Channel 2
Analog Input Data/Channel 3
N/A**
N/A**
N/A**
N/A**
0
1
2
3
*Sign Bit
1 = True (-)
0 = False (+)
**Not Used
MN05002001E
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 11: 2 Channel Analog Output Module (Consumed)
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
WORD
SB *
SB *
Analog Output Data/Channel 0
Analog Output Data/Channel 1
N/A**
N/A**
0
1
*Sign Bit
1 = True (-)
0 = False (+)
**Not Used
I/O Module Summary
Table 12: I/O Devices
Voltage
(Current)
Part Number
Type (I/O)
Description
Page
AC
DC
D77A-AI8
D77A-AI16
D77A-AQ8
D77A-AQ16
D77A-DI8
D77A-DI16
D77A-DQ8
120V AC
120V AC
120V AC
120V AC
24V DC
24V DC
24V DC
Input
AC Input Module
AC Input Module
AC Output Module
AC Output Module
DC Input Module
DC Input Module
Input
Output
Output
Input
Input
Output
DC Sink Output
Module
D77A-DQ16
D77A-RQ8
24V DC
Output
Output
DC Sink Output
Module
Relay
0 – 30V DC
0 – 125V AC
0 – 30V DC
0 – 125V AC
24V DC
D77A-RQ16
D77A-DI8DQ8
D77A-DI8RQ8
D77A-AI8AQ8
D77A-AI8RQ8
D77A-NI4
Output
Combo
Input
24V DC
Output
Input
24V DC
Relay
Output
Input
120V AC
120V AC
120V AC
Relay
Output
Input
Output
Input
Analog
0 – 5V
Analog Module
1 – 5V
0 – 10V
0 – 20 mA
4 – 20 mA
0 – 5V
D77A-NQ2
Output
Analog Module
1 – 5V
0 – 10V
0 – 20 mA
4 – 20 mA
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Intelligent Technologies (IT.) D77A I/O Module Products
Input Specifications
AC Input Module Specifications
Table 13: AC Input Module Specifications
Catalog Number
D77A-AI8
D77A-AI16
Nominal Input Voltage
Operating Voltage
Number of Inputs
Points per Common
OFF State Voltage
ON State Voltage
Nominal Input Current
Signal Delay
120V AC, 50/60 Hz
120V AC, 50/60 Hz
80 – 140V AC, 50/60 Hz
80 – 140V AC, 50/60 Hz
8
16
2
2
0 – 30V AC *
0 – 30V AC *
80V AC – 140V AC
80V AC – 140V AC
15 mA
15 mA
8.33 ms @ 60 Hz / 10 ms @ 50 Hz
8.33 ms @ 60 Hz / 10 ms @ 50 Hz
QCPort Current Draw
Isolation
33 mA
1.5kV
46 mA
1.5kV
Terminal Screw Torque
4.5 inch-pounds
(0.51 Newton-meters)
4.5 inch-pounds
(0.51 Newton-meters)
* A 50V transition range exists between 30V and 80V.
Ø
1
Ø
1
8
9
CØ
2
V A C
V A C
CØ
2
C4
10
11
C5
12
13
C6
14
15
C7
V A C
V A C
V A C
V A C
COM
IN
3
3
C1
4
C1
4
5
5
IN
C2
6
V A C
C2
6
V A C
V A C
V A C
V A C
c
7
7
V A C
C3
C3
D77A-006
a
b
Figure 3: AC Input Module Diagrams
a) D77A-AI8, Eight-Point Module
b) D77A-AI16, Sixteen-Point Module
c) Internal Circuit
MN05002001E
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
DC Input Module Specifications
Table 14: DC Input Module Specifications
Catalog Number
D77A-DI8
D77A-DI16
Type
Sink/Source
24V DC
18 – 30V DC
8
Sink/Source
24V DC
18 – 30V DC
16
Nominal Input Voltage
Operating Voltage
Number of Inputs
Points per Common
Signal Delay
2
2
5 ms
5 ms
OFF State Voltage
ON State Voltage
Nominal Input Current
QCPort Current Draw
Isolation
0 – 6V DC *
18V – 30V DC
5 mA
0 – 6V DC *
18V – 30V DC
5 mA
35 mA
63 mA
1.5kV
1.5kV
Terminal Screw Torque
4.5 inch-pounds
(0.51 Newton-meters)
4.5 inch-pounds
(0.51 Newton-meters)
* A 12V transition range exists between 6V and 18V.
Ø
1
Ø
1
8
9
CØ
2
CØ
2
C4
1 0
11
V DC
V DC
V DC
IN
3
3
V DC C1
V DC C1
V DC C5
IN
4
5
4
5
1 2
1 3
COM
C2
6
C2
C6
V DC
V DC
V DC
V DC
6
7
1 4
1 5
c
7
C3
V DC C3
V DC C7
D77A-008
a
b
Figure 4: DC Input Module Diagrams
a) D77A-DI8, Eight-point Module
b) D77A-DI16, Sixteen-point Module
c) Internal Circuit
MN05002001E
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Analog Input Module Specifications
Table 15: D77A-NI4 Analog Input Module Specifications
D77A-NI4
Catalog Number
Voltage Input
Current Loop Input
Voltage Input
Current Input
Input Type
0 – 5V, 1 – 5V, 0 – 10V DC
—
—
4 – 20 mA, 0 – 20 mA
Single End, Uni-polar
Resolution
Voltage
0-5VDC
0-10VDC
1-5VDC
0-5VDC
0-10VDC
1-5VDC
0-5VDC
0-10VDC
1-5VDC
0-5VDC
0-10VDC
1-5VDC
Resolution
14 bit
14 bit
14 bit
14 bit
14 bit
14 bit
14 bit
13 bit
12 bit
9 bit
Current
0-20mA
4-20mA
Resolution
50Hz
14 bit
14 bit
Note: Input filter settings affect the
effective resolution of the channels.
60Hz
0-20mA
4-20mA
14 bit
14 bit
250Hz
500Hz
0-20mA
4-20mA
12 bit
12 bit
0-20mA
4-20mA
9 bit
9 bit
10 bit
9 bit
Input Full Scale Range
0 – 10.5V or 0 – 5.25V
30VDC
0 – 21 mA
32 mA
Maximum Overload at Input Terminal
Number of Channels
4
Selectable Input Filter Frequency
Input Group-to-Bus Isolation
Common Mode Rejection
Normal Mode Rejection ratio
Accuracy
50Hz, 60Hz, 250Hz, 500Hz
500 VAC for 60 seconds
Greater than 60 db @ 50/60 Hz
-50 db @ 50/60 Hz
+/– 0.3% Full Scale @ 25°C
+/– 0.4% Full Scale @ 0-55°C
+/– 0.45% Full Scale @ 25°C
+/– 0.5% Full Scale @ 0-55°C
Input Impedance
15M ohm
250 ohm
Operating Temperature
Status LED Indication
QCPort Current Draw
Terminal Screw Torque
0–55°C
Module Status
60 mA
4.5 inch-pounds (0.51 Newton-meters)
MN05002001E
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
V0
I0
+
V0
(I)
(I)
(I)
(V)
NC
NC
NC
NC
I0
C0
V1
I1
-
C0
V1
I1
+
(V)
-
C1
V2
I2
C1
V2
I2
+
(V)
-
C2
V3
I3
C2
V3
I3
+
(I)
(V)
-
C3
C3
a
b
JIC-0013
Figure 5: D77A-NI4 Analog Input Module Diagrams
a) D77A-NI4 Voltage Input Channels
b) D77A-NI4 Current Input Channels
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Intelligent Technologies (IT.) D77A I/O Module Products
32766
31206
32766
31206
32766
31206
6242
3120
0
0
0
0V
0V
0V
5V 5.25V
1V
0.5V
5V 5.25V
10V 10.5V
(A)
(B)
(C)
32766
31206
32766
31206
6242
4992
0
0
0mA
20mA 21mA
0mA 4mA
3.2mA
20mA 21mA
(D)
D77A-031
(E)
Figure 6: Analog Input Curves
a) 0-5V Range Setting
b) 1-5V Range Setting
c) 0-10V Range Setting
d) 0-20mA Range Setting
e) 4-20mA Range Setting
14 Bit Resolution Equations
Vdc = Voltage input value
mA = Current input value
N = Decimal value
0-5 Vdc, 1-5 Vdc
• Vdc = (1/6241.2) x N
0-10 Vdc
• Vdc = (1/3120.6) x N
4-20 mA, 0-20 mA
• mA = (1/1560.2) x N
MN05002001E
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Output Specifications
AC Output Module Specifications
Table 16: AC Output Module Specifications
Catalog Number
D77A-AQ8
D77A-AQ16
Nominal Output Voltage
Operating Voltage
120V AC, 50/60 Hz
120V AC, 50/60 Hz
80 – 140V AC, 50/60 Hz
80 – 140V AC, 50/60 Hz
Number of Outputs
8
16
Points per Common
2
2
Minimum Load Current (Resistive)
Max. Current/Point (Resistive)
15 mA
15 mA
.5A @ 30°C
.1A @ 55°C
.5A @ 30°C
.1A @ 55°C
Max. Current/Module (Resistive)
.4A @ 30°C
.8A @ 0-55°C
8A @ 30°C
1.6A @ 0-55°C
Surge Current (10 ms)
OFF State Leakage
Signal Delay
10A
10A
2 mA
2 mA
8.33 ms @ 60 Hz
10 ms @ 50 Hz
8.33 ms @ 60 Hz
10 ms @ 50 Hz
QCPort Current Draw
Isolation
120 mA
1.5kV
220 mA
1.5kV
Terminal Screw Torque
4.5 inch-pounds
(0.51 Newton-meters)
4.5 inch-pounds
(0.51 Newton-meters)
Ø
1
1
2
8
9
CR
CR
CR
CR
CR
CR
V AC
V AC
V AC
CØ
2
CØ
2
C4
10
11
CR
CR
CR
CR
CR
CR
L2
3
3
V AC C1
V AC C1
V AC C5
OUT
4
5
4
5
1 2
1 3
CR
CR
CR
CR
CR
CR
V AC C2
V AC C2
V AC C6
6
7
6
1 4
CR
CR
CR
CR
OUT
7
1 5
C7
CR
CR
C3
C3
V AC
V AC
V AC
c
D77A-007
a
b
Figure 7: AC Output Module Diagrams
a) D77A-AQ8, Eight-Point Module
b) D77A-AQ16, Sixteen-Point Module
c) Internal Circuit
MN05002001E
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
DC Output Module Specifications
Table 17: DC Output Module Specifications
Catalog Number
D77A-DQ8
D77A-DQ16
Type
MOSFET Sink
MOSFET Sink
24V DC
18 – 30V DC
16
Nominal Output Voltage
Operating Voltage
Number of Inputs
Points per Common
Signal Delay
24V DC
18 – 30V DC
8
4
4
1 ms
0.75A
6A
1 ms
Max. Current/Point
Max. Current/Module (Resistive)
Surge Current (10 ms)
OFF State Leakage
QCPort Current Draw
Isolation
0.75A
12A
4A
4A
1 mA
85 mA
1.5kV
1 mA
126 mA
1.5kV
Terminal Screw Torque
4.5 inch-pounds
(0.51 Newton-meters)
4.5 inch-pounds
(0.51 Newton-meters)
Ø
1
2
3
-
CR
CR
CR
CR
Ø
1
2
3
-
CR
CR
CR
CR
8
9
CR
CR
CR
10
11
-
+24
CR
OUT
COM
COM
COM
+
4
5
6
7
-
+
4
5
6
7
-
+
V D C
CR
V D C
CR
V D C
CR
1 2
1 3
1 4
1 5
-
OUT
C
CR
CR
CR
CR
CR
CR
CR
CR
CR
COM
COM
V D C
COM
V D C
c
+
+
+
V D C
D77A-009
a
b
Figure 8: DC Output Module Diagrams
a) D77A-DQ8, Eight-Point Module
b) D77A-DQ16, Sixteen-Point Module
c) Internal Circuit
MN05002001E
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Relay Output Module Specifications
Table 18: Relay Output Module Specifications
Catalog Number
D77A-RQ8
D77A-RQ16
Nominal Output Voltage
0 – 140V AC
0 – 30V DC
0 – 140V AC
0 – 30V DC
Number of Outputs
Points per Common
Relay OFF Time
8
16
2
2
6 ms
6 ms
Relay ON Time
3 ms
3 ms
Max. Current/Point (Resistive)
Max. Current/Module (Resistive)
Electrical Life
3 A
3 A
24 A
48 A
100,000 Cycles
1,000,000 Cycles
92 mA
100,000 Cycles
1,000,000 Cycles
164 mA
1.5 kV
Mechanical Life
QCPort Current Draw
Isolation
1.5 kV
Terminal Screw Torque
4.5 inch-pounds
(0.51 Newton-meters)
4.5 inch-pounds
(0.51 Newton-meters)
CR
Ø
1
CR
CR
Ø
1
8
CR
CR
CR
9
V A C/DC
V A C/DC
V A C/DC
CØ
2
CØ
2
C4
10
11
C5
1 2
1 3
C6
1 4
1 5
C7
CR
CR
CR
CR
CR
OUT
3
3
CR
V A C/DC
C1
4
V A C/DC
V A C/DC
C1
4
CR
CR
CR
5
5
CR
CR
CR
OUT
C
V A C/DC
V A C/DC
V A C/DC
C2
6
C2
6
CR
CR
CR
CR
7
7
CR
CR
V A C/DC C3
V A C/DC
V A C/DC
C3
c
D77A-010
a
b
Figure 9: Relay Output Module Diagrams
a) D77A-RQ8, Eight-point Module
b) D77A-RQ16, Sixteen-point Module
c) Internal Circuit
MN05002001E
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Analog Output Module Specifications
Table 19: D77A-NQ2 Analog Output Module Specifications
D77A-NI4
Catalog Number
Voltage Output
Current Loop Output
Voltage Output
Current Output
Output Type
Resolution
0 – 5V, 1 – 5V, 0 – 10V DC
—
—
4 – 20 mA, 0 – 20 mA
Single End, Uni-polar
Voltage
0-5VDC
0-10VDC
1-5VDC
Resolution
13bit
Current
0-20mA
4-20mA
Resolution
14 bit
14 bit
14 bit
13 bit
Output Full Scale Range
Maximum Overload at Input Terminal
Number of Channels
Resistive Load
0 – 10.5V or 0 – 5.25V
0 – 21 mA
36V DC
2
—
Less than 500 ohms
Load Range
Greater than 1k ohm
—
Maximum Inductive Load
Maximum Capacitive Load
Accuracy
—
0.1 mH
—
1 µF
+/– 0.8% Full Scale @ 25°C
+/– 1.0% Full Scale @ 0-55°C
Update Rate
350 NS
Output Impedance
Output Ripple (0-50 Hz)
Operating Temperature
Status LED Indication
QCPort Current Draw
External Power
10 ohm
+/-0.1%
0–55°C
Module Status
40 mA
24 VDC, 60 mA Maximum
1.5kV for 60 Sec.
12 Pins (Pitch, 5.2 mm)
4.5 inch-pounds (0.51 Newton-meters)
Output group-to-bus Isolation
Terminal
Terminal Screw Torque
V0
I0
V0
+
(V)
I0
C0
V1
I1
(I)
-
C0
V1
I1
+
(V)
-
(I)
C1
NC
C1
NC
NC
NC
NC
-
NC
NC
NC
-
24VDC
24VDC
+
-
+
-
+
+
a
b
JIC-0014
Figure 10: D77A-NQ2 Combination Module Diagrams
a) D77A-NQ2 Module, Voltage Output Channels
b) D77A-NQ2 Module Current Output Channels
Download from Www.Somanuals.com. All Manuals Search And Download.
MN05002001E
Intelligent Technologies (IT.) D77A I/O Module Products
32766
31206
32766
31206
32766
31206
6242
3120
0
0
0
0V
0V
0V
5V 5.25V
1V
0.5V
5V 5.25V
10V 10.5V
(A)
(B)
(C)
32766
31206
32766
31206
6242
4992
0
0
0mA
20mA 21mA
0mA 4mA
3.2mA
20mA 21mA
(D)
D77A-031
(E)
Figure 11: Analog Output Curves for 14 Bit Resolution
a) 0-5V Range Setting
b) 1-5V Range Setting
c) 0-10V Range Setting
d) 0-20mA Range Setting
e) 4-20mA Range Setting
14 Bit Resolution Equations
Vdc = Voltage input value
mA = Current input value
N = Decimal value
0-5 Vdc, 1-5 Vdc
• Vdc = (1/6241.2) x N
0-10 Vdc
• Vdc = (1/3120.6) x N
4-20 mA, 0-20 mA
• mA = (1/1560.2) x N
MN05002001E
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Special I/O Specifications
Combination Module Specifications
Table 20: D77A-DI8DQ8 Combination Module Specifications
D77A-DI8DQ8
Catalog Number
DC Sink/Source Input
DC MOSFET Sink Output
Nominal Voltage
24V DC
24V DC
Operating Voltage
Number of Points
Points per Common
Signal Delay
18 – 30V DC
18 – 30V DC
8
8
2
2
5 ms
—
OFF State Voltage
ON State Voltage
0 – 6V DC *
—
18V – 30V DC
—
Nominal Current
5 mA
—
Signal Delay
—
1 ms
0.75A
6A
4A
1 mA
Max. Current/Point (Resistive)
Max. Current/Module (Resistive)
Surge Current (10 ms)
OFF State Leakage
QCPort Current Draw
Isolation
—
—
—
—
99 mA
1.5kV
Terminal Screw Torque
4.5 inch-pounds (0.51 Newton-meters)
* A 12V transition range exists between 6V and 18V.
Ø
1
Ø
1
CR
CR
CR
+24
V D C
V D C
2
3
-
CØ
2
OUT
CR
IN
COM
3
+
C1
4
V D C
CR
4
IN
OUT
C
5
5
6
7
-
CR
CR
V D C
V D C
C2
6
COM
CR
7
COM
c
b
+
C3
V D C
D77A-011
a
Figure 12: D77A-DI8DQ8 Combination Module Diagrams
a) D77A-DI8DQ8 Module
b) Internal DC Input Circuit
c) Internal DC Output Circuit
MN05002001E
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 21: D77A-DI8RQ8 Combination Module Specifications
D77A-DI8RQ8
Catalog Number
DC Sink/Source Input
Relay Output
Nominal Voltage
Operating Voltage
24V DC
—
18-30V DC
0-140V AC
0-30V DC
Number of Points
Points per Common
Signal Delay
8
8
2
2
5 ms
—
—
—
—
OFF State Voltage
ON State Voltage
Nominal Current
Signal Delay
0-6V DC *
18V-30V DC
5 mA
—
Relay ON Time 3 ms
Relay OFF Time 6 ms
Max. Current/Point (Resistive)
Max. Current/Module (Resistive)
Mechanical Life
—
3A
—
24A
—
1,000,000 Operations
100,000 Operations
Electrical Life
—
QCPort Current Draw
Isolation
121 mA
1.5kV
Terminal Screw Torque
4.5 inch-pounds (0.51 Newton-meters)
* A 12V transition range exists between 6V and 18V.
CR
Ø
1
Ø
1
CR
V A C/DC
C4
2
V D C
V D C
CØ
2
OUT
CR
IN
3
3
CR
V A C/DC
C1
4
C5
4
CR
IN
OUT
C
5
5
CR
V A C/DC
C6
6
C2
6
COM
V D C
V D C
CR
CR
7
7
c
b
V A C/DC C7
C3
D77A-028
a
Figure 13: D77A-DI8RQ8 Combination Module Diagrams
a) D77A-DI8RQ8 Module
b) Internal DC Input Circuit
c) Internal Relay Output Circuit
MN05002001E
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 22: D77A-AI8AQ8 Combination Module Specifications
D77A-AI8AQ8
AC Input
Catalog Number
AC Output
Nominal Voltage
120V AC, 50/60 Hz
120V AC, 50/60 Hz
Operating Voltage
Number of Points
Points per Common
OFF State Voltage
ON State Voltage
80-140V AC
8
80-140 V AC
8
2
2
0-30V AC *
80V-140V AC
15 mA
—
—
—
Minimal Load Current (Resistive)
Signal Delay
8.33 ms @ 60 Hz
10 ms @ 50 Hz
Max. Current/Point (Resistive)
Max. Current/Module (Resistive)
—
—
—
0.5A @ 30°C
0.1A @ 55°C
4A @ 30°C
0.8A @ 55°C
Surge Current (10 ms)
OFF State Leakage
QCPort Current Draw
Isolation
10A
2 mA
132 mA
1.5kV
Terminal Screw Torque
4.5 inch-pounds (0.51 Newton-meters)
* A 50V transition range exists between 30V and 80V.
CR
Ø
1
Ø
1
CR
V A C
C4
2
V A C
V A C
CØ
2
COM
IN
L2
CR
CR
3
3
OUT
V A C
C1
4
C5
4
CR
5
5
CR
OUT
V A C
C6
6
V A C
V A C
C2
6
IN
CR
7
7
CR
c
b
V A C
C3
C7
D77A-029
a
Figure 14: D77A-AI8AQ8 Combination Module Diagrams
a) D77A-AI8AQ8 Module
b) Internal AC Input Circuit
c) Internal AC Output Circuit
MN05002001E
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 23: D77A-AI8RQ8 Combination Module Specifications
D77A-AI8RQ8
AC Input
Catalog Number
Relay Output
Nominal Voltage
Operating Voltage
120V AC, 50/60 Hz
80-140V AC
—
0-140V AC
0-30V DC
Number of Points
Points per Common
Signal Delay
8
8
2
2
5 ms
—
—
—
—
OFF State Voltage
ON State Voltage
0-80V AC*
180V-140V AC
15 mA
Maximum Load Current (Resistive)
Signal Delay
8.33 ms @ 60 Hz
10 ms @ 50 Hz
Relay ON Time 3 ms
Relay OFF Time 6 ms
Max. Current/Point (Resistive)
Max. Current/Module (Resistive)
Mechanical Life
—
3A
—
24A
—
1,000,000 Operations
100,000 Operations
Electrical Life
—
QCPort Current Draw
Isolation
104 mA
1.5kV
Terminal Screw Torque
4.5 inch-pounds (0.51 Newton-meters)
* A 60V transition range exists between 80V and 140V.
Ø
1
Ø
1
CR
CR
V A C/DC
C4
2
COM
IN
AC
AC
CØ
2
OUT
CR
3
3
CR
V A C/DC
C1
4
C5
4
OUT
C
CR
5
5
CR
V A C/DC
C6
6
IN
AC
AC
C2
6
CR
CR
7
7
c
b
V A C/DC C7
C3
D77A-030
a
Figure 15: D77A-AI8RQ8 Combination Module Diagrams
a) D77A-AI8RQ8 Module
b) Internal DC Input Circuit
c) Internal Relay Output Circuit
MN05002001E
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Theory of Operation
The IT. D77A I/O system consists of a collection of input and output modules connected together by QCPort to a network adapter. The
network adapter connects to the industrial network where the controller usually is a PLC or DCS. The input modules collect digital or
linear signals from sensors (limit switches, proximity sensors, temperature transmitters, etc.) and deliver these data to the control
device. In the control device, input data values are placed in data registers. Based on the input data, the control algorithm manipulates
values in the output registers. With each scan of the network, the input and output data registers are updated. With this update, the
output modules have their digital or linear data changed to reflect the control algorithm found in the control device software. The
output devices (solenoid valves, motor starters, temperature gauges, etc.) effect changes to the machinery being controlled.
Out-of-box Default Operation
When the IT. D77A I/O modules are properly installed and each has a properly configured Group ID (address), no additional
configuration is needed for standard operation. To customize the configuration, refer to Configuration on page 34. After customizing
the configuration, the system can be restored to the default out-of-box configuration without a software tool such as CH Studio by
following these steps.
1. Using a screwdriver, rotate the Group ID Switch from the “0” position to the “1” position.
2. Repeat this action five times.
The status LED rapid flashes, signaling that the system is reset to the out-of-box default settings.
Typical Application
Figure 16 illustrates a typical D77A I/O module application this is integrated with a number of IT. starters with QSNAPs. In this
example, a D77A I/O is part of a larger system where motor control and I/O are required within a single panel. On the same QCPort
connection, both the I/O and the motor control are connected to a single network Adapter. The network adapter then represents the
D77A I/O and motor control as remote I/O, allowing for control and monitoring of the QCPort devices.
b
e
d
a
f
c
D77A-003
Figure 16: Panel Layout: Adapter, I/O and QSNAP
a) PC or PLC Connection
b) I/O Modules
c) QCPort Connection
d) IT. Starters with QSNAPs
e) Power Tap/Terminator Resistor
f) 24 V DC Power Supply
MN05002001E
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
I/O Function
Discrete Input Modules
Figure 17 illustrates the basic signal processing operation. When a signal is present at the input point, the module responds with the
following sequence:
1. Optical Isolation — Optical isolation protects the I/O circuits and communication circuits from possible damage due to
transients and over-voltage.
2. Debounce Logic/Control — A debounce circuit and software limits the effects of transients and electrical noise by requiring the
input to be true for a certain period of time before the logic acknowledges a true signal. Once a true signal is achieved, the logic
turns on the LED.
3. QCPort Com./Logic — The logic updates the QCPort communication on a regular, scheduled basis as to the status of the input
point.
Optical
Isolation
Debounce
Logic/Control
QCPort
Com.
Input
LED
Indication
D77A-004
Figure 17: Discrete Input Module Operation
Discrete Output Modules
Figure 18 illustrates the basic logic processing operation. When the processor activates an output point, the module responds with
the following sequence:
1. QCPort Com./Logic — QCPort communication updates the logic circuit on a regular, scheduled basis as to the status of the
output points.
2. Optical Isolation — Optical isolation protects the I/O circuits and communication circuits from possible damage due to
transients and over-voltage. Once an active signal is transmitted to the optical isolation circuit, the LED is forward-biased.
3. Output Drivers — The driver activates the output point.
QCPort
Com.
Optical
Isolation
Output
Drivers
Output
LED
Indication
D77A-005
Figure 18: Discrete Output Module Operation
MN05002001E
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Discrete Combination Modules
Combination modules have the properties of both input and output points in a single module. The behavior of the combination
module’s input and output points are the same as those found in discrete input and output modules.
QCPort
Comm
Optical
Isolation
Debounce
Logic/Control
Input
LED
Indication
Output
Drivers
Optical Isolation
Output
D77A-032
Figure 19: Discrete Combination Module Operation
MN05002001E
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Analog Input Modules
Figure 20 illustrates the basic signal processing operation. Analog signals from four separate channels are received by a multiplexer
(MUX). The MUX sequentially transfers this data to an analog-to-digital converter (ADC). The ADC measures the analog signal and
converts it to a digital value. This digital value is presented to the controller’s central processes unit (CPU). This data is then presented
to the QCPort for external processing.
V0
I0
V1
M
U
X
I1
V2
I2
ADC
CPU
QC Port
V3
I3
C0
C1
C2
C3
V1
+V2 -V2
SCHEM-001
Figure 20: Analog Input Module Operation
Analog input signal delays are associated with multiplexer switching, channel updating and channel reconfiguration. These delays are
all influenced by analog input filter frequency selection.
Table 24: Analog Input Signal Delays
Filter Setting
Total Update Time
50 Hz
60Hz
336 ms
283.2 ms
80 ms
250 Hz
500 Hz
44 ms
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
25
Intelligent Technologies (IT.) D77A I/O Module Products
Analog Output Modules
Figure 21 illustrates the basic signal processing operation. Digital data from external sources are extracted from the QCPort and
transferred to the controller’s central processor unit (CPU). The digital data from the CPU is transferred to the digital-to-analog
converters (DAC). The DAC system converts the digital values to linear signals and provides them to the output terminals.
QC Port
CPU
DAC
DAC
V0
I0
V1
I1
C0
C1
+24V
G
P. S.
SCHEM-002
Figure 21: Analog Output Module Operation
MN05002001E
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Installation
WARNING
AVERTISSEMENT
ADVERTENCIA
Indicates a potentially hazardous situation
which, if not avoided, can result in serious
injury or death.
Indique une situation potentiellement
Indica que existe una situación
dangereuse qui, si elle n’est pas évitée, peut potencialmente peligrosa, que si no es
entraîner de graves blessures, voire la mort. evitada, podrá resultar en serias heridas
corporales o en la muerte.
Setting Group ID
A unique Group ID must be assigned to each module. The modules are shipped with a factory-set default setting of zero.
To set the Group ID, use a screwdriver to rotate the rotary switch located on the top of the module.
0
0
0
0
14
10
14
10
14
10
14
10
2
6
2
6
2
6
2
6
12
4
12
4
12
4
12
4
8
8
8
8
a
c
b
d
D77A-015
Figure 22: Group ID Switch
a) Discrete I/O Group ID Three
b) Discrete I/O Group ID Ten
c) Analog I/O Group ID Three
d) Analog I/O Group ID Ten
Notice
Avis
Aviso
In the examples above, the left module has a Dans les exemples ci-dessus, le module de En los ejemplos de arriba, el módulo
Group ID of 3 and the right a Group ID of 10. gauche porte un numéro d’identification de izquierdo tiene una identificación de Grupo
The arrow indicates the Group ID setting
groupe n° 3 et celui de droite un de 10. La
3 y el de la derecha una identificación de
Grupo 10. La fecha indica la configuración de
(not the line). Refer to the IT. QCPort System flèche indique le réglage du numéro
Install and Planning Guide (Publication No. d’identification de groupe (non pas la ligne). identificación de Grupo (no la línea).
MN05001002E) for more information on
setting the Group ID.
Reportez-vous au Guide de planification et
d’installation du système bâbord IT. QCPort Instalación del Sistema QCPort del IT. (
Refiérase a la Guía de Planificación e
(publication no. MN05001002E) pour plus
d’information sur les réglages du numéro
d’identification de groupe.
Publicación No. MN05001002E) para obtener
más información de cómo configurar la
identificación de Grupo.
DIN rail installation requires one of two procedures:
• DIN Rail installation without Backplane
• DIN Rail installation with Backplane
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
27
Intelligent Technologies (IT.) D77A I/O Module Products
Installation Without Backplane
Module Preparation
The DIN rail locking tab is located under the removable terminal on the front of the device. Remove the terminal to gain access to the
locking tab.
1. Remove the terminal by unlocking the terminal tabs.
1
4
0
8
12
2
6
10
4
D77A-016
Figure 23: Removable Terminal Locking Tabs
2. Remove the terminal strip from the module.
3. Insert a screwdriver under the DIN rail locking tab and lift up to unlock the locking tab.
a
b
c
D77A-017
Figure 24: Unlock DIN Rail Locking Tab
a) Tab
b) Locking Tab Captured
c) Locking Tab Released
MN05002001E
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Installing the Module
The module is now ready for installation on the DIN rail.
CAUTION
PRÉCAUTION
PRECAUCIÓN
Do no “rock” the module onto the DIN rail.
The rocking action could damage the
module.
Ne « basculez » pas le module sur le rail DIN. No “meza” el módulo sobre el riel DIN. El
L’action de basculement pourrait
endommager le module.
mecerlo podrá dañar el módulo.
1. The module must always be inserted perpendicular onto the DIN rail. Push the module straight back onto the DIN rail.
2. Depress the locking tab to secure the module to the DIN rail.
a
b
D77A-018
Figure 25: Lock DIN Rail Locking Tab
a) Locking Tab
b) Locking Tab Captured
3. Install the terminal strip on the front of the module.
4. Lock the terminal strip into place using the locking tabs.
14
0
12
2
10
4
8
6
D77A-019
Figure 26: Removable Terminal Locking Tab
Notice
Avis
Aviso
After the strip is installed, install
Après avoir installé la bande, installez les
Después de instalada la banda, instale los
interconectadores, vea la Guía de
Planificación e Instalación del Sistema
QCPort del IT. ( Publicación No.
MN05001002E) para obtener más
información.
interconnects; see the IT. QCPort System
interconnecteurs ; voyez le Guide de
Install and Planning Guide (Publication No. planification et d’installation du système
MN05001002E) for more information.
bâbord IT. QCPort (publication no.
MN05001002E) pour plus d’information.
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
29
Intelligent Technologies (IT.) D77A I/O Module Products
Installation With Backplane
Module Preparation
The DIN rail locking tab is underneath the removable terminal (on the front of the device). The terminal must be removed to gain
access to the locking tab.
1. To remove the terminal, unlock the terminal tabs.
14
0
12
2
10
4
8
6
D77A-016
Figure 27: Removable Terminal Locking Tabs
2. Remove the terminal strip from the module.
3. Insert a screwdriver under the DIN rail locking tab and lift up to unlock the locking tab.
a
b
c
D77A-017
Figure 28: Unlock DIN Rail Locking Tab
a) Tab
b) Locking Tab Captured
c) Locking Tab Released
MN05002001E
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Installing the Module
The module is now ready for installation on the DIN rail.
CAUTION
PRÉCAUTION
PRECAUCIÓN
Do not “rock” the module onto the DIN rail. Ne « basculez » pas le module sur le rail DIN. No “meza” el módulo sobre el riel DIN. El
The rocking action could damage the
module.
L’action de basculement pourrait
endommager le module.
mecerlo podrá dañar el módulo.
1. Line the center of the module up with the backplane connector on the DIN rail. Ensure the backplane connector is installed with
the arrows up. The module must always be inserted perpendicular onto the DIN rail.
2. Push the module straight back onto the DIN rail and backplane connector.
3. Depress the locking tab to secure the module to the DIN rail.
a
b
D77A-018
Figure 29: Lock DIN Rail Locking Tab
a) Locking Tab
b) Locking Tab Captured
4. Install the terminal strip on the front of the module.
5. Lock the terminal strip into place using the locking tabs.
14
0
12
2
10
4
8
6
D77A-019
Figure 30: Removable Terminal Locking Tab
MN05002001E
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
QCPort Connections
WARNING
AVERTISSEMENT
ADVERTENCIA
Hazardous voltage can cause electric shock La tension dangereuse peut causer des
and burns. Always disconnect power before électrochocs et des brûlures. Coupez
Los voltajes peligrosos pueden causar
electrochoque y quemaduras. Siempre
desconecte la energía antes de proceder con
cualquier trabajo en este producto.
proceeding with any work on this product.
toujours le courant avant d’entreprendre
tout travail sur ce produit.
Interconnects/Connections
Connecting the I/O modules together and to other IT. family products involves using one or more of the interconnect connectors. The
I/O product family uses two types of connectors:
• The backplane interconnect
• The short run interconnect
These interconnects provide the I/O module with power and communications.
For more information on making interconnects, the use of interconnects and the restrictions placed upon interconnects, refer to the IT.
QCPort System Install and Planning Guide (Publication No. MN05001002E).
QCPort Backplane Interconnect
The QCPort backplane interconnect is used when connecting the Adapter and I/O modules on a DIN rail. The interconnect fits inside
the channel of the DIN rail and provides for connection to power and communication to the Adapter and I/O products (Figure 31 and
6
GND
B
A
+24
1
D77A-020
Figure 31: QCPort Backplane Interconnect
6
GND
B
a
b
A
+24
1
D77A-021
Figure 32: QCPort Interconnect Backplane Connectors
a) Module Side
b) Backplane Side
MN05002001E
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Pre-manufactured QCPort Interconnect Cables
To connect the D77A I/O modules together without using a QCPort backplane, use the QCPort connectors that are located at the bottom
of the D77A I/O module. There are two QCPort connections next to each other. They are configured parallel with each other so that
they can be daisy chained together using QCPort Interconnect cables. There are standard sizes for the QCPort Interconnect cables.
These sizes are listed in the “Renewal Parts” portion of “Troubleshooting and Maintenance.”
Note: The maximum current allowed through a QCPort interconnect cable is 1 Amp. The maximum number of modules that may be
daisy chained together using QCPort interconnect cables is calculated by adding the current rating of each device and keeping
the total less than 1 Amp.
When making this interconnect, refer to the IT. QCPort System Install and Planning Guide (Publication No. MN05001002E) for the
recommended cable and connections.
1 – +24
a
2 – GND
3 –
4 –
B
1
A
5 – +24
6 – GND
b
1
D77A-022
Figure 33: QCPort Connector
a) Connector Half
b) Keyed Insert
MN05002001E
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Configuration
There are parameters associated with the D77A I/O products that can be set using a software tool such as CH Studio for enhanced
functionality.
All of the enhanced features are selectable through CH Studio either in the Property Window or the Property Pages of the device.
Figure 34: I/O Property Page
MN05002001E
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Field Wiring
Notice
Avis
Aviso
Install all field wiring on the modules in
compliance with all applicable regularity
codes.
Installez tout le câblage de terrain sur les
modules en accord avec tous les codes de
réglementation applicables.
Instale todo el cableado del inductor en los
módulos cumpliendo con todos los códigos
de regularidad que apliquen.
WARNING
AVERTISSEMENT
ADVERTENCIA
Hazardous voltage can cause electric shock La tension dangereuse peut causer des
and burns. Always disconnect power before électrochocs et des brûlures. Coupez
Los voltajes peligrosos pueden causar
electrochoque y quemaduras. Siempre
desconecte la energía antes de proceder con
cualquier trabajo en este producto.
proceeding with any work on this product.
toujours le courant avant d’entreprendre
tout travail sur ce produit.
WARNING
AVERTISSEMENT
ADVERTENCIA
Only apply 24V DC to the I/O module power N’appliquez que du courant continu de 24 V Sólo aplique 24V CD a los terminales de
terminals. Use of any other voltage may
result in personal injury, property damage
and damage to the IT. D77A I/O module.
aux bornes de courant des modules I/O.
L’emploi de toute autre tension peut
entraîner des blessures corporelles, des
dégâts matériels et des dégâts au module
IT. D77A I/O.
energía del módulo I/O. El uso de cualquier
otro voltaje podrá resultar en heridas
corporales, daños a la propiedad o daños al
IT. Módulo I/O D77A.
Table 25: Symbol Definitions
Symbol
Definition
MOSFET
D
S
G
Selector Switch
Push Button
Contact (normally closed)
Pilot Light
G
Overload
Capacitor
MN05002001E
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Symbol
Definition
Earth Ground
Chassis Ground
Fuse
Control Relay
CR
Limit Switch
Resistor
Diode
Contact (normally open)
MOV
Relay Module Output Point
Optical Isolator AC Output Point
Solenoid
Control Transformer
MN05002001E
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
AC Inputs
AC power is typically used to energize loads related to machinery function such as solenoid valves and motor starters. The same AC
power source is often used as signal power for inputs as illustrated in Figure 35. The input devices to which AC inputs are wired are
typically two-lead devices like push buttons, limit switches and selector switches. One side of the input device is wired to an AC power
source while the other is wired to the input terminal. Another input terminal is wired to a grounded neutral wire. Refer to AC Output
Module Specifications on page 13 for module details.
L1
L2
L3
1FU
2FU
3FU
a
H1
H4
H3
H2
g
L1
L2
X1
X2
b
c
f
0
1
C0
C1
e
d
2
3
N/C
JIC-0002
Figure 35: AC Input Wiring
a) Three-phase Motor Circuits
b) First Point of Input Module
c) Second Point of Module
d) Selector Switch
e) Push Button
f) Limit Switch
g) Control Transformer
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
37
Intelligent Technologies (IT.) D77A I/O Module Products
DC Inputs
DC Input modules are designed to operate with either sinking or sourcing devices. They are typically used with proximity sensors and
other solid-state devices. (Figure 36) Input modules may need to be installed relatively close to the sensor location. Refer to DC Input
H1
H4
H3
H2
a
b
X1
X2
24VDC
NEU
120VAC
+
-
-
+
c
0
1
e
C0
-
+
d
JIC-0007
Figure 36: DC Input Wiring
a) Control Transformer
b) 24 VDC Power Supply
c) DC Input Module
d) Sinking Input Device
e) DC Sourcing Device
MN05002001E
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Analog Inputs
Analog signals are typically used to transmit or indicate linear data like temperature, pressure or flow, as illustrated in Figure 37. The
analog input devices to which analog inputs are wired are typically current loop or voltage range devices like 4-20 mA transmitters or
Note: Ground the shield on one end only. It is recommended to limit the cable impedance by keeping the cable length as short as
TM
possible. Limiting the distance from ground to the shield is also recommended. The recommended cable is a Belden
equivalent.
8761 or
Wire Type
Solid Cu-90°C
Stranded Cu-90°C
Wire Size
#14 - # 22 AWG
#16 - # 22 AWG
Terminal Torque
4.5 in-lbs
4.5 in-lbs
Note: When an input channel in not used, jumper from V to C eliminating noise from causing erroneous readings for that channel.
e
f
a
V
-
+
V0
I0
1
2
3
C0
d
I
V1
I1
4
5
6
C1
V2
I2
7
8
9
c
C2
b
V3
I3
10
11
12
C3
JIC-0012
Figure 37: Analog Input Wiring
a) Input Module
b) Jumper
c) Shield (Ground One End Only)
d) Current Input Device
e) Voltage Input Device
f) Shield (Ground One End Only)
MN05002001E
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
AC Outputs
AC power is typically used to energize loads related to machinery function such as solenoid valves and motor starters. These devices
are generally two-lead devices as illustrated in Figure 38. One side is wired to a grounded neutral wire while the other is wired to the
M1
M2
OLDS
M1
OLDS
M2
L1
L2
L3
1FU
2FU
3FU
H1
H4
H3
H2
a
L1
L2
X1
X2
b
OLDS
OLDS
M1
C0
C1
0
1
SOL1
M2
g
f
c
d
2
3
G
PL1
e
JIC-0001
Figure 38: AC Output Wiring
a) Control Transformer
b) M1 Motor Starter Coil
c) Solenoid Valve
d) M2 Motor Starter Coil
e) Pilot Light
f) Second Point of Module
g) First Point of Module
MN05002001E
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
DC Outputs
DC power is typically used for instrumentation or light control circuits. Examples might be solenoid valves, indicator lamps or sinking
or sourcing signals to other equipment. These devices are generally two-lead devices as illustrated in Figure 39. Refer to DC Output
Module Specifications on page 14 for module details.
H1
H4
H3
H2
a
X1
X2
b
24VDC
NEU
120VAC
+
-
+
-
0
1
c
d
e
f
SOL1
C0
PL1
G
2
3
CR
CR
g
JIC-0015
Figure 39: DC Output Wiring
a) Control Transformer
b) 24 VDC Power Supply
c) Solenoid
d) Pilot Light
e) Control Relay 1
f) Control Relay 2
g) DC Output Module Points 2 and 3
h) DC Output Module Points 0 and 1
MN05002001E
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Relay Outputs
Relay outputs can be used to control a variety of different loads. They can be used in AC or DC circuits or they can be used to provide
a dry contact to other equipment. (Figure 40) Refer to Relay Output Module Specifications on page 15 for module details.
H1
H4
H3
H2
a
X1
X2
b
24VDC
NEU
120VAC
c
+
-
0
SOL1
C0
PL1
G
1
j
i
2
3
C1
d
e
f
4
5
SOL2
C2
CR
JIC-0011
h
g
Figure 40: Relay Output Wiring
a) Control Transformer
b) 24 VDC Power Supply
c) DC Solenoid
d) DC Pilot Light
e) AC Solenoid
f) Dry Contact to Other Equipment
g) AC Control Relay
h) Relay Output Points 4 and 5
i) Relay Output Points 2 and 3
j) Relay Output Points 0 and 1
MN05002001E
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Analog Outputs
Analog signals are typically used to transmit or indicate linear data like pressure or linear actuation, as illustrated in Figure 41. The
analog output devices to which analog outputs are wired are typically current loop or voltage range devices like 4-20 mA signals or
Note: Ground the shield on one end only. It is recommended to limit the cable impedance by keeping the cable length as short as
TM
possible. Limiting the distance from ground to the shield is also recommended. The recommended cable is a Belden
equivalent.
8761 or
Wire Type
Solid Cu-90°C
Stranded Cu-90°C
Wire Size
#14 - # 22 AWG
#16 - # 22 AWG
Terminal Torque
4.5 in-lbs.
4.5 in-lbs.
H1
H3
H4
H2
a
b
X1
X2
24VDC
NEU
120VAC
+
-
V0
+
1
I0
V
2
3
C0
-
c
V1
I1
4
5
I
C1
NC
NC
NC
NC
-
6
d
7
8
9
10
11
12
+
e
JIC-0008
Figure 41: Analog Output Wiring
a) Control Transformer
b) 24 VDC Power Supply
c) Voltage Output Device
d) Current Output Device
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
43
Intelligent Technologies (IT.) D77A I/O Module Products
Combination I/O
Combination I/O modules incorporate the features of input points and output points into a single module. Figure 42 illustrates a
typical dual purpose module application. The advantage is improved I/O density and greater flexibility for many applications. Refer to
Combination Module Specifications on page 18 for module details.
H1
H4
H3
H2
a
X1
X2
24VDC
120VAC
NEU
+
-
e
R
G
A
B
PLT1
0
1
2
PLT2
PLT3
PLT4
b
3
+
-
c
JIC-0003
d
LS1
PB1
0
1
C0
Figure 42: Combination I/O Wiring
a) Control Transformer
b) DC Loads
c) Output Points
d) Inputs
e) 24 VDC Power Supply
MN05002001E
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Troubleshooting and Maintenance
Status LED
Table 26: Status LED
State
LED Behavior
No Power
OFF
Power-Up Routine
Off-Line, OK (mostly off)
OFF – CRC corrupt
On-Line (mostly on)
Faulted (50%)
Identify device (burst)
Undiscovered
Fault Codes
Table 27: Analog 10 Fault Codes
0 x 41 (65)
0 x 42 (66)
0 x 44 (68)
0 x 45 (69)
Analog input over range.
Analog input under range.
Analog input open.
Analog input shorted.
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
45
Intelligent Technologies (IT.) D77A I/O Module Products
Troubleshooting
Table 28: Troubleshooting
Observation
Possible Cause/Corrective Action
The input LED will not illuminate.
Verify that the module is powered; the LED is controlled by the micro controller
in the device.
The power for the input itself may not be applied. Verify that there is a valid
signal on the input point.
The screws on the terminal may be loose; tighten the screws.
Replace the device.
The output LED is illuminated but the output is not on.
Check that the switch closes on the output using a multi meter.
The screws on the terminal may be loose; tighten the screws.
Replace the device.
The status LED has a “fast blink” while all other device’s
status LEDs are “mostly on.” See Table 26 Status LED.
The “fast blink” device may have the same Group ID as another device. Verify
that all devices have unique Group IDs.
The “fast blink” device was not accepted into the scan list. Reasons include it
was replaced and the device is not the same as the original device (parameters
are different or the product is different).
An out-of-box device was inserted into an actively scanning QCPort; power will
need to be cycled on QCPort to be accepted.
While On-Line with CH Studio the I/O Module disappears.
It may be that the controller is not allowing enough time for the CH Studio
messages and the connection between CH Studio and the Network Adapter is
timing out. You may have to take the system controller off-line to continue or
add an interscan delay to the industrial network scan.
While looking at the I/O Module it is noticed that the status If no other LED’s are on it is possible the I/O Module was placed into a firmware
LED is solid on.
download mode, cycle power to the I/O Module and see if the LED behaves
properly.
The module may have corrupt memory or damage to the circuit board and the
module will need to be replaced.
Renewal Parts
Table 29: I/O Module Renewal Parts
Description
Part Number
7-Position QCPort Backplane
12-Position QCPort Backplane
25-Position QCPort Backplane
QCPort RJ Terminator
D77E-BP7
D77E-BP12
D77E-BP20
D77E-TERRJ
D77E-QPIP25
D77E-QPIP100
D77E-QPIP200
D77E-QPIP300
D77E-QPLR
25 cm Powered QCPort Interconnect
1 Meter QCPort Interconnect
2 Meter QCPort Interconnect
3 Meter QCPort Interconnect
QCPort Terminator and Power Tap
Communication Troubleshooting Hints
Explanation of LED Duty Cycle States
Table 30: Explanation of LED Duty Cycle States
LED Duty Cycle State
Explanation
Mostly Off
Mostly On
50%
One short blink ON every 2 seconds
One short blink OFF every 2 seconds
ON and OFF blinking same amount of time; 1/2 second cycle
Strobe
Rapid Flash
MN05002001E
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 31: Status LED
Status LED
Description
Explanation
Mostly Off
Offline
Everything is OK with in the I/O Module and the I/O Module is not being scanned.
Check that the Network Adapter is commanded to scan QCPort. This is generally done by setting bit 0 of byte
0, for channel A, in the output assembly.
Mostly On
50%
Online
Everything is OK with in the I/O Module and the I/O Module is being scanned.
Internal memory fault (cycle power).
Faulted
Verify that there are not any duplicate Group ID’s (address). Check that the address is unique for the QCPort
system.
The Group ID was changed and a reset is required.
Buss fault. All the devices on the QCPort will have the same status LED behavior. A buss fault is caused by an
open or QCPort shorted buss.
Rapid Flash
Unacquired
The I/O Module has not been discovered/acquired by the Network Adapter, verify that the node ID is set
correctly for the system.
The Network Adapter has not auto configured the QCPort system. In this case all the I/O Module’s will have
the same behavior of the status LED. Perform an auto configuration.
CH Studio is identifying that device. When the device is highlighted in CH Studio this is a way to identify in
the field which device is being highlighted. Remove the highlight from CH Studio and verify that the Rapid
Flash disappears.
Solid On
Off
It is possible the I/O Module is in firmware download mode, cycle power to exit that mode. If the LED stays
solid On after the power cycle, it is possible that the I/O Module has in internal failure and will need to be
replaced.
No Power
The I/O Module is not powered or a memory fault in NV RAM has occurred that will require the I/O Module to
be replaced.
Communication Hints
Table 32: Communication Hints
Problem
Solution
Are all the QCPort devices
connected to one Network
Gateway are not
communicating? Are all the
Status LED’s either Rapid
Flash or 50% On
Check the Network Adapter, is the ST LED Green? – If the LED is green, then perform an auto configuration of
the Network Adapter and see if the problem goes away.
There may be a damaged I/O Module or a shorted QCPort communication wire that is prohibiting QCPort
communications. Remove all the I/O Modules from the QCPort system.
Unplug the Network Adapter from the industrial network.
Cycle power to the Network Adapter.
One by one plug the I/O Modules back in and verify that the status LED is mostly off as they are plugged back in.
When the I/O Module the causes the system to fail is plugged in, the I/O Module’s status LED will rapid flash or
50% flash only.
Remove the I/O Module and check the QCPort connections for shorted or damaged wires or connections.
When all the I/O Modules are online, plug the Network Adapter into the industrial Network.
It is possible that the terminating resistors are damaged, replace the terminating resistors.
Is there a single I/O Module
in the system that is not
communicating?
The problem may be that the I/O Module has a fixable internal communication failure. Perform a reset by
toggling the rotary switch from 0 to 1 five times, reset the rotary switch to the correct group ID (address).
It is also possible the Group ID rotary switch was changed after auto configuration. Check the rotary switch and
verify that they are in the correct position for that address. Physically move the rotary switch from one position
to another to verify that it is in the correct position (there will be a “snap” when it reaches the next state).
Unplug and replug the device and check that the problem disappears.
It is possible that the communication connections are damaged or unplugged.
It is possible that the terminating resistors are damaged, replace the terminating resistors.
Check the status LEDs on the I/O Module units, if the LEDs are rapid flashing or 50% On refer to the above
During auto configuration
the Network Adapter will not problem for a solution.
detect any of the I/O
If the status LEDs on the I/O Module units are all slow flashing, the Network Adapter has already connected to
the I/O Module units and the problem is that the CH Studio software is not displaying the I/O Module units. This
can be because the scanner is not allowing CH Studio to send long messages.
Modules.
The Network Adapter cannot perform an auto configuration if the system controller is scanning the Network
Adapter. Disconnect the Network Adapter from the industrial network and reattempt the auto configuration.
MN05002001E
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Appendix A
Data Parameters
Table 33: 0x0001 (1) Production Data
Size
Description
Varies
This list contains the concatenated values of QCPort Parameters specified in QCPort Configuration Parameter
0x800C, Production List.
Table 34: 0x0002 (2) Consumption Data
Size
Description
Varies
This list contains the concatenated values of QCPort Parameters specified in QCPort Configuration Parameter
0x800D, Consumption List.
Table 35: 0x0003 (3) QCPort Status
Size
Description
1 Byte
This parameter indicates the QCPort fault condition that caused a device to enter the Fault Mode, as indicated
below:
0x00 — No QCPort Fault
0x01 — Node ID Conflict
0x02 — Invalid Node ID in Master/Slave
0x03 — Physical Node ID does not match actual ID
0x04 — Duplicate configured nodes online
0x05 — Dynamic Node ID overflow
0x06 — Invalid baud rate selected
0x07 — Errant Device fault
0x08 — Problem with data in non-volatile memory
Table 36: 0x0004 (4) Application Status (Available in I/O As Control Elements)
Size
Description
2 Bytes
This parameter indicates the application status of the QCPort device. It reports the most recent fault or warning.
If there have been no faults or warnings, it reports 0. Reset clears this parameter.
Table 37: 0x0005 (5) Discrete Data Input (Available in I/O As Control Elements)
Size
Description
n Bytes
A series of BYTES that represent discrete digital inputs on a device. This parameter is used in any input module
having discrete inputs.
The least significant bit of byte 0 corresponds to input point 0.
Table 38: 0x0006 (6) Discrete Data Output (Available in I/O As Control Elements)
Size
Description
n Bytes
A series of BYTES representing the state of the outputs of a discrete output device. This parameter is used in
any module having discrete outputs. The least significant bit of byte 0 corresponds to output point 0.
Parameter 0x8023, “Output Comm Loss Behavior” is used in conjunction with this parameter.
Table 39: 0x006B (107) Analog Input Status (Available in I/O As Control Elements)
Size
Description
n Bytes
This provides channel status for the analog inputs.
U = Under Range
O = Over Range
Byte
Bit 7
Bit 6
Bit 5 *
O1
Bit 4 *
U1
Bit 3
Bit 2
Bit 1 *
O0
Bit 0 *
U0
0
1
O3
U3
O2
U2
* Setting the bit from “0” to “1” indicates that the condition is true.
MN05002001E
48
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 40: 0x006C (108) Analog Output Status (Available in I/O As Control Elements)
Size
Description
n Bytes
This provides channel status for the analog outputs.
U = Under Range
O = Over Range
Byte
Bit 7
Bit 6
Bit 5 *
Bit 4 *
Bit 3
Bit 2
Bit 1 *
Bit 0 *
0
O1
U1
O0
U0
Table 41: 0x006F (111) 16 bit Signed Analog Input Data (Available in I/O As Control Elements)
Size
Description
Word
This provides the 16 bit signed analog input data for the module.
Bit Position
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
1
2
3
SB*
SB*
SB*
SB*
Analog Input Data Channel 0
Analog Input Data Channel 1
Analog Input Data Channel 2
Analog Input Data Channel 3
Sign Bit*
1 = True (-)
0 = False (+)
Table 42: 0x0070 (112) 16 bit Signed Analog Output Data (Available in I/O As Control Elements)
Size
Description
Word
This provides the 16 bit signed analog output data for the module.
Bit Position
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
1
SB*
SB*
Analog Input Data Channel 0
Analog Input Data Channel 1
Sign Bit*
1 = True (-)
0 = False (+)
MN05002001E
Download from Www.Somanuals.com. All Manuals Search And Download.
49
Intelligent Technologies (IT.) D77A I/O Module Products
Configuration Parameters
None of the Configuration Parameters support I/O data.
Table 43: 0x8001 (32769) Device Identity
Size
Description
14 bytes
This read-only parameter contains information that uniquely identifies a device, including the following elements:
Product Code
(2 bytes)
A device’s unique product code must be reported. Each
vendor must maintain its own list of product codes.
Vendor ID
(2 bytes)
Each QCPort vendor must use their unique ID as assigned
by Eaton Electrical.
Serial Number
(4 bytes)
A device’s serial number must be reported. This value must
be unique for a particular manufacturer across all device
types.
Hardware Revision
(2 bytes)
Major revision must be reported in the MSB. Minor revision
must be reported in the LSB.
Firmware Revision
(2 bytes)
Major revision must be reported in the MSB. Minor revision
must be reported in the LSB.
QCPort Revision
(2 bytes)
Major revision must be reported in the MSB. Minor revision
must be reported in the LSB.
Table 44: 0x8002 (32770) Configuration CRC
Size
Description
2 bytes
Used for confirmation of a device’s configuration. Normally, the initial values of selected configuration
parameters would be included in the calculation. The product instruction leaflet should describe which
parameters are actually included. To facilitate node replacement, Device Identity information should not be
included in this calculation.
Table 45: 0x8003 (32771) Node ID
Size
Description
2 bytes
This parameter specifies a device’s Node ID. The Group ID is the Most Significant Byte and the Member ID is the
Least Significant Byte.
An Initial Value of 0x0000 indicates an unconfigured state. In this state, a device assumes a current value based
on the level of switch support implemented in hardware.
Table 46: 0x8004 (32772) Operating Mode
Size
Description
1 byte
This parameter specifies a device’s operating mode, as follows:
Mode
Description
Active/Passive
0x00
0x01
0x02
0x03
0x04
Unconfigured
Simple System
Master/Slave
Wire Replacer
Faulted
Passive
Passive
Active
Passive
Passive
Table 47: 0x8005 (32773) QCPort Baud Rate
Size
Description
1 byte
This parameter specifies the QCPort baud rate for a device as indicated below:
0x00 — 9,600
0x01 — 19,200
0x02 — 38,400
0x03 — 57,600
0x04 — 115,200
0x05 — 230,400
0x06 — 460,800
Note that the current value of the baud rate cannot be directly modified. The current value is set to the initial
value upon reset. Therefore, writing to the initial value and resetting the device sets a new current value.
MN05002001E
50
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 48: 0x8006 (32774) Slave Address
Size
Description
1 byte
This parameter specifies the address used by a Master for data transfers in the Master/Slave Data Protocol.
The default value must be 0x00 (unconfigured), requiring a Master to set this value prior to using the Master/
Slave Data Protocol.
Table 49: 0x8007 (32775) Production Destination
Size
Description
2 bytes
This parameter specifies the destination Node ID to be used by a device in either the Simple System or Wire
Replacer Data Protocols. The MSB indicates the Group ID; the LSB indicates the Member ID.
An Initial Value of 0x0000 indicates an unconfigured state. In this state, a device assumes a current value equal
to its Group ID and a Member ID of 0x00. This results in its Production Data being targeted at all members of its
Group.
Table 50: 0x8008 (32776) Device ID Tag
Size
Description
32 bytes
This parameter specifies the 32-character ASCII string ID tag assigned to a device, pre-assigned at the factory
but can be set by the user.
Table 51: 0x8009 (32777) Production Interval
Size
Description
2 bytes
This parameter specifies the rate, in milliseconds, at which a producing device generates a Data Protocol
message in either Simple System or Wire Replacer mode.
A value of 0 disables this timer.
Table 52: 0x800A (32778) Consumption Interval
Size
Description
2 bytes
This parameter is the value to which the consumption timer is set whenever there is a set of the current value of
any parameter on the consumption list.
Expiration of this interval causes the module to execute communications loss behavior.
A value of 0 disables this timer.
Table 53: 0x800B (32779) Parameter List
Size
Description
92 bytes
This read-only list specifies the n QCPort Parameters that a device supports.
Table 54: 0x800C (32780) Production List
Size
Description
2 bytes
This 2n-byte read-only list specifies the n QCPort Parameters included in a device’s QCPort Data Parameter
0x0001, Production Data.
Setting Parameter Attribute 0x09, “Production List Member,” to TRUE, designates a Parameter’s membership in
this list. Only Parameters supporting Attribute 0x09 are eligible for inclusion in this list.
Ordering of Parameter IDs in the Production List is based first on Parameter data size and then sequentially
within Parameters of like size. For example, all Parameters with an even number of bytes would appear first
sequentially, followed by Parameters with an odd number of bytes.
Table 55: 0x800D (32781) Consumption List
Size
Description
2 bytes
This 2n-byte read-only list specifies the n QCPort Parameters included in a device’s QCPort Data Parameter
0x0002, Consumption Data.
Setting Parameter Attribute 0x0A, “Consumption List Member,” to TRUE, designates a Parameter’s membership
in this list. Only Parameters supporting Attribute 0x0A are eligible for inclusion in this list.
Ordering of Parameter IDs in the Consumption List is based first on Parameter data size and then sequentially
within Parameters of like size. For example, Parameters with an even number of bytes would appear first
sequentially, followed by Parameters with an odd number of bytes.
Table 56: 0x800E (32782) Languages Supported
Size
Description
n bytes
This is a list of languages supported in the product. It consists of a list of bytes, each representing a different
language.
0x00 — English
0x01 — Spanish
0x02 — French
0x03 — German
0x04 — Italian
MN05002001E
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Table 57: 0x800F (32783) Language Selection
Size
Description
1 byte
Holds the currently selected language from the list in parameter 800E.
Table 58: 0x8010 (32784) Device Semaphore
Size
Description
4 bytes
The purpose of this parameter is to provide a method for tools to access a QCPort node in a non-conflicting
manner.
This parameter consists of a field of 2 UNITs organized as follows:
Byte
Node ID Low byte
Node ID High byte
Lockout Time in tenths of seconds Low byte
Lockout Time in tenths of seconds High byte
If the above 4 bytes are 0, anyone can write to this parameter. This parameter is cleared by the Clear Semaphore
command that can be sent by anyone. If all 4 bytes are not 0 and a write (other than a clear) to this parameter is
attempted, an error message will be returned. The parameter will be cleared when the timer counts down to 0.
If the node ID field is 0, all set parameters to the node will be accepted. If the node ID field is not 0, set parameter
commands to the node will only be accepted from the device having the same node ID as that contained in this
parameter. Note that if the node ID is set to zero at the same time that a non-zero value is loaded to the timer, the
timer will not decrement.
Table 59: 0x8023 (32803) Output Comm Loss Action
Size
Description
The n bytes
Used in discrete output modules. Each bit of this parameter is associated with an output bit and defines the
behavior of that output upon detection of communications loss.
If a bit in this parameter is 1, the output bit holds the last state.
If a bit is 0, the output bit is determined by the initial value.
Table 60: 0x8024 (32804) Input Debounce
Size
Description
The n bytes
Used with discrete input devices. This parameter consists of a series of UNITs, two bytes for each discrete input
and holds the debounce time for that input.
Table 61: 0x804D (32845) Physical Node ID Setting
Size
Description
2 bytes
This parameter may be used with modules having a hardware node ID switch and represents the actual setting
of that switch.
Table 62: 0x80CF (32975) Analog Output Communication Loss Behavior
Size
Description
n Bytes
Determines the communication loss behavior of the output module.
0 = Hold last state
1 = Use Communication Loss Value
2 = Use Initial Value
Table 63: 0x80D0 (32976) Analog Output Communication Loss Value
Size
Description
Word
Value that the output channel will go to if selected using the communication loss behavior.
1-32767
Table 64: 0x80D1 (32977) Input Range Setting
Size
Description
1 Word
Determines analog input data range:
0 = 0 - 10V
1 = 0 - 5V
2 = 1 - 5v
3 = 0 - 20mA
4 = 4 - 20mA
Table 65: 0x80D2 (32978) Analog Output Range
Size
Description
1 Word
Determines analog output data range.
0 = 0 - 10V
1 = 0 - 5V
2 = 1 - 5v
3 = 0 - 20mA
4 = 4 - 20mA
MN05002001E
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Intelligent Technologies (IT.) D77A I/O Module Products
Analog Data Registers
Table 66: Register 1; Serial Number
Size
Description
4 bytes, read only
Serial number of module
Table 67: Register 2; Hardware Revision
Size
Description
2 bytes, read only
Hardware version of module
Table 68: Register 3; Analog Filter Setting
Size
Description
2 bytes, read only
Filter setting of analog input channel
0 = 50 Hz
1 = 60 Hz
2 = 250 Hz
3 = 500 Hz
IT. Publications and Support
Publications
Table 69: IT. Publications
Publication
Description
MN05002001E
MN05001002E
MN05004002E
IT. D77A I/O Module Products Installation and Users Manual
IT. QCPort System Install and Planning Guide
IT. DeviceNet Adapter Installation and User Manual
MN05002001E
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Company Information
Eaton’s electrical business is a global leader in electrical control, power distribution, and industrial automation products and services.
Through advanced product development, world-class manufacturing methods, and global engineering services and support, Eaton’s
electrical business provides customer-driven solutions under brand names such as Cutler-Hammer®, Powerware®, Durant®,
Heinemann®, Holec® and MEM®, which globally serve the changing needs of the industrial, utility, light commercial, residential, and OEM
Eaton Corporation is a diversified industrial manufacturer with 2004 sales of $9.8 billion. Eaton is a global leader in electrical systems and
components for power quality, distribution and control; fluid power systems and services for industrial, mobile and aircraft equipment;
intelligent truck drivetrain systems for safety and fuel economy; and automotive engine air management systems, powertrain solutions
and specialty controls for performance, fuel economy and safety. Eaton has 56,000 employees and sells products to customers in more
Eaton Electrical Inc.
1000 Cherrington Parkway
Moon Township, PA 15108-4312
USA
tel: 1-800-525-2000
© 2005 Eaton Corporation
All Rights Reserved
Publication No. MN05002001E
Revision 4/ November 2006