The Network Management Card & Modbus/Jbus (66103) is recommended for central UPSs
protecting entire networks or for UPS units backing up critical loads. With the card installed, the UPS
has its own IP address and uses the local computer capabilities to:
● Supply web pages (http or https (SSL)) with information on status conditions and measurements/
settings/alarms,
● Integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli Netview and Computer Associates
Unicenter,
● Communicate with shutdown modules installed on the protected servers (Network Shutdown
Module),
● Send e-mail and SMS messages,
● Control the ON/OFF function of the UPS and the outlets,
● Monitor the Environment Sensor (optional, cat. no. 66846).
UNPACKING AND CHECKS
● One Network Management Card & Modbus/Jbus (66103)
● One serial cable for configuration (34003918),
● One installation manual (34003906).
CHECK ON UPS VERSION
The Network Management Card & Modbus/Jbus (66103) is compatible with the Pulsar range UPSs
available since 2006.Note.
Important. Before installing the card, check that the UPS technical level (NT) is at least
equal to that indicated in the table below.
UPS
Type
Technical level (NT)
02
Pulsar
700/1000/1500
Pulsar M
2200/3000
03
04
01
Pulsar MX
4000/5000/10000
15/20 kVA
Pulsar MX Frame
● If the technical level of the UPS is lower than that indicated in the table, contact EATON.
34003906EN/AE - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
.
OVERVIEW
Jbus/modbus port
MAC address
ETHERNET 10/100BT port
Service port (Settings/Sensor)
Orange LED: RS232 activity
Settings/Sensor
1
00M
10
Green LED: communication
with the UPS
M
U
P
S
dat
a
R
S
232
6
6
1
0
3
Catalogue number
Orange LED: 10/100M
Green LED: connection +
activity
INDICATIONS
ETHERNET port
LED
Colour
Green
Status
Description
ACT
● OFF
● ON
● Card not connected to network
● Card connected to network, but no activity
● Port is sending/receiving
● Flashing
100M
Orange
● OFF
● ON
● Port operating at 10 Mbits/s
● Port operating at 100 Mbits/s
Service port (Settings/Sensor)
LED
Colour
Green
Status
Description
UPS Data
● OFF
● Card starting
● ON
● Flashing
● Communicating with UPS
● Normal operation
Communication with UPS is operational
RS232
Orange
● OFF
● ON
● Configuration menu activated
● Normal operation
Configuration menu not activated
● Communication with Environment Sensor (option)
● Flashing
4 - 34003906EN/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
The Network Management Card & Modbus/Jbus (66103) can be hot-plugged on all UPSs from
EATON equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart
the UPS.
● Remove the plastic cover of the Minislot.
● Note the MAC address of the card before inserting it.
S
et
ti
n
g
s/
S
en
so
r
ASI
10
0M
10
M
UP
S
d
ata
RS
6
23
2
6
1
0
3
ETHERNET
● Insert and secure the card with the screws.
● Connect the ETHERNET cable.
● Check the ETHERNET port indications.
● Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-up has
terminated correctly.
Note. Connection detection continues until the card has been connected to the network. Once
connection is made, card start-up continues.
IP SETTINGS
Once the card has started, proceed as indicated below.
● Connect the serial cable to card’s service port and PC’s COM port
TM
● Use a terminal emulator such as HyperTerminal
with these settings
Bits per second
9600
Data bits
8
Stop bits
1
Parity
none
Flow control
none
"Echo typed characters locally" option: disabled
● Type EATON (or eaton).
The main configuration menu is displayed:
EATON
NETWORK MANAGEMENT CARD
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit
34003906EN/AE - 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Your network is equipped with a BOOTP/DHCP server (default)
The card is configured by default with this service enabled. No manual configuration is required.The IP
parameters are automatically collected by the card.
From the main configuration menu: (see above)
● Press the 2 key (Network configuration).
● Press the 1 key(Read Network settings).
The settings supplied by the server are displayed:
Network configuration :
MAC address : 00:06:23:00:1C:07
Mode : DHCP
IP address : 172.17.23.18
Subnet mask : 255.255.248.0
Gateway : 172.17.17
● Note the IP address.
● Press the 0 key (Exit).
● Press the 0 key (Exit).
You can also use NMC Tool software utility to view the card IP adress
connected PC.
Your network is not equipped with a BOOTP/DHCP server
Manual configuration is required.
To set the network configuration, use terminal emulation (see above)
From the main configuration menu:
●
●
●
Press the 2 key (Network configuration).
Press the 2 key (Modify Network settings).
Follow the instructions and enter the IP parameters:
1 : Read Network settings
2 : Modify Network settings
3 : Set ethernet speed
0 : Exit
For each of the following questions, you can press "Return" to
select
the value shown in braces, or you can enter a new value
Should this target obtain IP settings from the network?[N] N
Static IP address [172.17.16.16]?172.16.1.82
Subnet mask IP address [255.255.0.0]? 255.255.255.0
Gateway address IP address [0.0.0.0]? 172.17.17.1
Done
Wait until "Done" is displayed, indicating that the IP parameters have been saved.
● Press the 0 key (Exit).
● Press the 1 key (Reset).
● Press the 2 key (Restart).
The card restarts with the new IP settings (after approx. one minute).
6 - 34003906EN/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
ACCESS TO SUPERVISION
To check whether the Network Management Card & Modbus/Jbus (66103) is operational after
installation and configuration, proceed as follows.
● Run a browser
● Enter in the address bar:
http://IP address/ (e.g. http://172.16.1.82/)
● The home page is displayed
● Set the time by clicking the Time command.
● Continue configuration via the sections in the Settings menu.
USER MANUAL
This manual provides all the information required to install and configure the Network Management
Card & Modbus/Jbus (66103).
For more information on the supervision, control and configuration functions offered by the Network
Management Card & Modbus/Jbus (66103), see the user manual on the Solution-Pac 2 CD-ROM or
34003906EN/AE - 7
Download from Www.Somanuals.com. All Manuals Search And Download.
SENSOR CONNECTION (option)
The Environment sensor is a Network Management Card & Modbus/Jbus option. It is available
from EATON (cat. no 66846).
The sensor remotely monitors the UPS environment by regularly measuring the temperature and
humidity, and checking the states of two external contacts. It can also send alarms (e-mail, SNMP trap)
tripped by pre-set thresholds.
Connection is made via the Service port (Settings/Sensor) on the Network Management Card &
Modbus/Jbus. The sensor is detected automatically. Configuration and supervision use a menu that
may be accessed directly from the home page. For more information, see the user manual of the
Network Management Card & Modbus/Jbus.
10
0M
10
M
UP
S
d
lin
k
a
ta
R
S
23
2
6
6
1
0
3
8 - 34003906EN/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
J BUS/ MODBUS
RS232 link configuration and connection
SA1
SA2
Pin Function
SA2
1
8
1
2
3
4
5
Received data (input)
Not connected
5
4
3
2
1
Transmitted data (output)
Not connected
Signal ground
SG
Txd
Rxd
RS485 link configuration and connection
For proper operation, the polarity of EIA RS485 2-wire and 4-wire lines must be set at only one point
and the lines terminated at the end.
Polarity
Normally, the master of the network sets the polarity of the line. The receiver inputs have a true failsafe
feature wich eliminates the need for external bias resistors and ensures a logic high output level when
the inputs are open or shorted. This guarantees that the receiver outputs are in a known state before
communication begins and when communication ceases.
Termination
Termination is used to match impedance of a node to the impedance of the transmission line being
used. When impedance are mismatched, the transmitted signal is not completely absorbed by the load
and a portion is reflected back into the transmission line. The termination line is not necessary if the
speed on the line is much less than 115Kbauds
RS485
SA1
SA2
RD = (B')
1
2
3
4
5
R-
R+
T-
RD = (A')
TD = (B)
TD = (A)
SA2
SA1
1
8
1
8
T+
0 V
0 V
The default setting of the RS485 is a 4 wires configuration without polarity and without termination.
SA1 switches are used to make the termination and the topology of the line (2 or 4 wires). The
termination resistance value is 166 Ω.
SA1 description:
1 : reserved
2 : reserved
3 : link termination between T- to R- (2 wires configuration) if set to ON
4 : connection T- to R- (2 wires configuration ) if set to ON
5 : connection T+ to R+ (2 wires configuration ) if set to ON
6 : reserved
7 : reserved
8 : link termination between R+ and R- if set to ON
34003906EN/AE - 9
Download from Www.Somanuals.com. All Manuals Search And Download.
2 wires connection
SA1
SA2
SA2
SA1
1
8
1
8
5
4
3
2
1
L - L +
5V
3V3
3V3
Rp
polarity
L-
L-
L-
L-
connection
if end
3
1
3
1
3
termination
of the line
Ra
Ra
7
Ra
connection
if end
of the line
termination
SA1-3
SA1-3
L+
L+
L+
L+
2
4
2
4
polarity
Rp
0V
0V
0V
transmit/receive
data
transmit/receive
data
transmit/receive
data
Card of an intermediate cubicle
Master unit
Card of an end-of-line cubicle
Card settings of an intermediate cubicle
SA1
SA1
SA2
Link without polarity and without termination.
Others settings
SA1
SA1
SA2
Link with termination.
10 - 34003906EN/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
4 wires connection
SA1
SA2
SA2
SA1
1
8
1
8
5
4
3
2
1
T + T - R + R-
master
transmitt
slave
receiver
slave
receiver
5V
Rp
polarity
T-
R-
R-
R-
1
termination
termination
1
Ra
Ra
T+
R+
R+
R+
2
2
polarity
Rp
0V
5V
transmit data
receive data
receive data
Rp
Ra
slave
slave
slave
receiver
transmitt
transmitt
R-
T-
T-
T-
connection if
end of the line
3
3
connection if
end of the line
R+
T+
T+
T+
4
4
Rp
0V
receive data
transmit data
transmit data
Master unit
Card of an intermediate cubicle
Card of an end-of-line cubicle
Card settings of an intermediate cubicle
SA1
SA1
SA2
Link without polarity and without termination.
Others settings
SA1
SA1
SA2
Link with termination.
34003906EN/AE - 11
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the JBUS/MODBUS communication parameters
Through settings port
ETERNET
/Sensor
100M
1
0M
n
=
UP
L
Bl
S
in
dat
a
k
a
R
S2
32
6
6
1
0
3
Connect the RS232 link to a
terminal
(Microsoft Hyper terminal)
● Use the cord supplied with the card
● Connect the card to a computer
● Use a terminal emulator such as HyperTerminal
TM
with these settings
Bits per second
9600
Data bits
8
Stop bits
1
Parity
none
Flow control
none
"Echo typed characters locally" option: disabled
● Check that UPS power is on.
● Type EATON (or eaton).
The main configuration menu is displayed:
EATON
NETWORK MANAGEMENT CARD
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit
● Press the 5 key (Jbus configuration).
The Jbus configuration menu is displayed:
Jbus settings
1 : Display Jbus settings
2 : Modify Jbus settings
3 : Display Jbus diagnostics
4 : Reset Jbus diagnostics
5 : Return to Jbus Default Configuration
6 : Display Jbus frames
0 : Exit
12 - 34003906EN/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
● Press the 2 key (Modifiy Jbus settings)
● Press «Return» key to modify the Jbus settings
Setting Jbus configutration
Set Slave number : 0x1*
Set the Baud Rate [1:38400,2: 19200, 3:9600, 4: 4800, 5: 2400,
6: 1200] :3
Set data format[1: 8 bits, 2: 7 bits] :1
Set stop bit[1: 1 bits, 2: 2 bits] :1
Set parity [1: None, 2: Even, 3: Odd] :1
Wait during the new setting is saved ...
TLS/Slave JBUS initialized
The Jbus configuration is now updated.
* Hex format.
● Press the 0 key (Exit).
● Press the 0 key (Exit).
Through a web browser
● Run a browser
● Enter in the address bar:
http://IP address/ (e.g. http://172.16.1.82/)
● The home page is displayed
● Select the setting menu
● Set the parameters.
● Select the «Save» button to save the new parameters.
34003906EN/AE - 13
Download from Www.Somanuals.com. All Manuals Search And Download.
TECHNICAL CHARACTERISTICS
Physical characteristics
Dimensions (W x D x H)
Weight
132 x 66 x 42 mm
70 g
RoHS
100% compatible
Storage
Storage temperature range
Ambient conditions
Operating temperature range
Relative humidity
Card performance
Supply voltage
-10°C to 70°C
0°C to 40°C
90% RH max. without condensation
5V ±5%
Supply current (all LEDs ON and
Environment Sensor connected)
300 mA max.
Functions
Web supervision
5 browsers max. (http),
3 browsers max. (https)
Languages
Alarms
English, French, German, Italian, Spanish
E-mail, SNMP TRAP, Web page
400 measurements or events
Log
Server protection
Network
Up to 100 servers protected
Fast ETHERNET, 10/100 Mbits, auto-negotiation
HTTP 1.1, SNMP V1, NTP, TFTP, SMTP, BOOTP/DHCP
Identification
Security
Browsers
NMS
User name and password
SSL 3.0, TLS 1.0
Microsoft Internet Explorer 6.x or higher
Enterprise Power Manager (EPM)
Management-Pac 2
MIB
MIB II standard - UPS EATON MIB V1.7
Settings (default values)
IP network
BOOTP/DHCP enabled
IP address: 172.17.16.16 (manual configuration)
Subnet mask: 255.255.0.0
Gateway: 0.0.0.0
NTP server: pool.ntp.org
Web-page access control
User name: EATON
Password: EATON
Service-port menu access control
Date and time
Password: EATON or eaton (not modifiable)
Synchronise with an NTP server (GMT)
Service port
9600 bits/s, 8 bits, 1 bit stop, no parity
RS485 port
Slave nb:0x01, 9600 bits/s, 8 bits, 1 bit stop, no parity
14 - 34003906EN/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTROMAGNETIC COMPATIBILITY
When correctly installed and used in accordance with manufacturer instructions, the card complies with
the following standards:
● ITE (Information Technology Equipment) safety: IEC/EN 60950-1 2002
● EMC: EN 61000-6-2 (2002), EN 61000-6-3 (2002), IEC/EN 62040-2 (2002)
In compliance with European directives:
● Low voltage: 73/23/EEC and 93/68/EEC.
● EMC: 89/336/EEC and 93/68/EEC.
Federal Communication Commission (FCC) statement
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment.
WEB SITE
The information presented in this manual is also available in other languages in the download section
of the EATON site (www.eaton.com/powerquality).
34003906EN/AE - 15