2HP13 & 2HP14 SPLIT SYSTEM HEAT PUMP
INSTALLATION / START-UP INSTRUCTIONS
/HOMEOWNERS INFORMATION MANUAL
These instructions must be read and understood completely before attempting installation.
Issue 0733
TABLE OF CONTENTS
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Location & Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rooftop Installation & Recommendations . . . . . . . . . . . . . . . . . . . .
Indoor Coil Piston Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigeration Line Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation of Line Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating & Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Opening Service Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2
3
3
3
4
4
4
5
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single Phase Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
5
6
6
7
9
3 Phase Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Homeowner's Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
These units are designed for use in residential and light commercial type buildings. Heat Pumps may only be
installed with indoor combinations listed in the Air-Conditioning and Refrigeration Institute (ARI) Directory of
Inspect the unit for any damage before installation. If damage is found, notify the transportation company
immediately and file a concealed damage claim.
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation
MUST conform with local building codes and with the National Electrical Code NFPA 70/ANSI C1-1993 or
current edition and Canadian Electrical Code Part 1 CSA C22.1.
Improper installation, adjustment, alteration, service or maintenance will void the warranty. The qualified installer or
agency must use factory-authorized kits or accessories when added to this products. Refer to the individual instructions
included with the specific accessory kit.
NOTE
These instructions are intended as a general guide and do not supersede national, state or local codes in any way.
These instructions must be left with the property owner.
100402-07
Issue 0733
Page 1 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
Elevate Unit
DO LOCATE THE UNIT:
!
!
!
With proper clearances on sides and top of unit
On a solid, level foundation or pad
To minimize refrigerant line lengths
Accumulation of water and ice in base pan may
cause equipment damage.
Elevate unit per local climate and code requirements to
provide clearance above estimated snowfall level and
ensure adequate drainage of unit. Use snow stand in
areas where prolonged freezing temperatures are
encountered.
DO NOT LOCATE THE UNIT:
!
!
!
!
On brick, concrete blocks or unstable surfaces
Near clothes dryer exhaust vents
Near sleeping area or near windows
Under eaves where water, snow or ice can fall
directly on the unit
If conditions or local codes require the unit be attached
to pad or mounting frame, tie down bolts should be used
and fastened through knockouts provided in unit base pan.
!
!
with clearance less than 2 ft. from a second unit
with clearance less than 4 ft. on top of unit
Operating Ambient
The minimum outdoor operating ambient in cooling
modeis55/F, andthemaximumoutdooroperatingambient
in cooling mode is 125/F. The maximum outdoor operating
ambient in heating mode is 66/F.
Roof Top Installations
Mount on level platform or frame 6 inches above roof
surface. Place unit above a load-bearing wall and isolate
unit and tubing set from structure. Arrange supporting
members to adequately support unit and minimize
transmission of vibration to building. Ensure roof structure
and anchoring method is adequate for location. Consult
local codes governing rooftop applications.
Indoor Coil Piston Selection
The outdoor heat pump section must be matched to a
factory approved indoor section. It is mandatory that the
installer ensure that the correct piston is installed in the
indoor section. If necessary remove the existing piston and
replace it with the correct piston See indoor unit
instructions for details of changing the piston. Contact
your distributor for accessory piston kits.
Roof mounted units exposed to winds above 5 mph
may require wind baffles to achieve adequate defrost. A
sheet metal baffle should be spaced 6-1/2" from the fall of
the coil. The height should cover the face of the coil and
the length should be 6" from the access panel.
Indoor (Cooling) Piston Size
13 SEER Heat Pump Indoor Piston Sizes
NOTE: Unit must be level to within ± 2/ (± 3/8 in./ft) per
compressor manufacturer specifications.
Unit Size
18
Piston Size
.055
24
.063
30
.068
Clearance Requirements
36
.076
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping, and service. For
proper airflow, quiet operation and maximum efficiency.
Position so water, snow, or ice from roof or eaves cannot
fall directly on unit.
42
48
60
.076
.082
.098
The evaporator coil may use an expansion valve (TXV) in place of piston.
14 SEER Heat Pump Models
All 14 SEER heat pump models are only rated with TXV on
the indoor side.
14 SEER Heat Pump Indoor TXV
Unit Size
18 thru 36
42 thru 48
TXV Kit
TXV3
TXV5
Refrigeration Line Sets
Use only refrigerant grade copper tubes. Split
systems may be installed with up to 50 feet of line set (no
more than 20 feet vertical) without special consideration
(see long line set guidelines).
100402-07
Issue 0733
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 3 of 18
The following is the recommended method for making
braze connections at the refrigerant line connections:
1. Debur and clean refrigerant tube end with emery
cloth or steel brush.
2. Insert tubing into swage fitting connection.
3. Wrap wet rags over valves to protect from heat.
4. Allow dry nitrogen to flow through refrigerant lines.
5. Braze joint, using a suitable brazing alloy for copper
to copper joints.
Recommended Liquid & Vapor Tube Diameters (In.)
LIQUID
VAPOR
Unit Size
Connection Dia. Tube Dia. Connection Dia. Tube Dia.
018
024
030
036
042
048
060
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/4
3/4
3/4
3/4
7/8
7/8
7/8
3/4
3/4
3/4
3/4
7/8
7/8
*1-1/8
*FIELD SUPPLIED 7/8 X 1-1/8 CONNECTOR REQUIRED ON BOTH
ENDS OF VAPOR TUBING.
6. Quench the joint and tubing with water using a wet
rag. Leave rag on fitting body and re-wet with water
to help cool area.
It is important that no tubing be cut or seals broken
until you are ready to actually make connections to the
evaporator and to the condenser section. DO NOT remove
rubber plugs or copper caps from the tube ends until ready
to make connections at evaporator and condenser. Under
no circumstances leave the lines open to the atmosphere
for any period of time, if so unit requires additional
evacuation to remove moisture.
Leak Check
Refrigeration lines and indoor coil must be checked for
leaks after brazing and before evacuation.
The
recommended procedure is to apply a trace amount of
vapor refrigerant (approximately two ounces or 3 psig) into
the line set and indoor coil, then pressurize with 150 psig
of dry nitrogen. Use a refrigerant leak detector to check all
joints. The system may also be checked for leaks using a
halide torch or pressure and soapy solution. After
completion of leak check, relieve all pressure from system
before evacuation.
Be extra careful with sharp bends. Tubing can "kink"
very easily, and if this occurs, the entire tube length will
have to be replaced. Extra care at this time will eliminate
future service problems.
It is recommended that vertical suction risers not be
up-sized. Proper oil return to the compressor should be
maintained with suction gas velocity.
Evacuating And Charging Instructions
NOTE: Intentional release of CFC or HCFC refrigerant
to the atmosphere violates Federal Law. It may
also violate State and Local Codes. Check all
Federal, State and Local Codes before
proceeding.
Installation of Line Sets
DO NOT fasten liquid or suction lines in direct contact
with the floor or ceiling joist. Use an insulated or
suspension type of hanger. Keep both lines separate, and
always insulate the suction line. Long liquid line runs (30
feet or more) in an attic will require insulation. Route
refrigeration line sets to minimize length.
These outdoor units are pre-charged at the factory with
adequate refrigerant to handle 15 feet of refrigerant tubing.
DO NOT let refrigerant lines come in direct contact with
foundation. When running refrigerant lines through the
foundation or wall, openings should allow for a sound and
vibration absorbing material to be placed or installed
between tubing and foundation. Any gap between
foundation or wall and refrigerant lines should be filled with
a vibration damping material.
NOTE: DO NOT use any portion of the charge for purging
or leak testing. It is mandatory that a thorough
evacuation of the refrigeration lines and indoor coil
be performed.
The liquid line and suction line service valves have been
closed after final testing at the factory. DO NOT disturb
these valves until the lines have been leak checked and
evacuated or the charge in the unit may be lost.
If ANY refrigerant tubing is buried, provide a 6 inch
vertical rise at service valve. Refrigerant tubing
lengths up to 36 inches may be buried without further
special consideration. For lengths above 36 inches,
consult your local distributor.
1. Connect the vacuum pump to the center hose of the
manifoldgaugeset, thelow-pressuremanifoldgauge
to the vapor service valve and the high pressure
manifold gauge to the liquid service valve.
NOTE: Unnecessary switching of hoses can be avoided
and complete evacuation of all lines can be
achieved by also connecting a branch hose from
the manifold gauge center port to a cylinder of R-
22. Provide a separate shut-off valve to vacuum
pump to avoid contaminating vacuum pump oil
with refrigerant.
Before making braze connections, be sure all joints are
clean. Before heat is applied for brazing, dry nitrogen
should be flowing through the tubing to prevent oxidation
and scale formation on the inside of the tubing.
100402-07
Issue 0733
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 4 of 18
2. The valves should be kept in the "front seated"
(closed) position. This will allow evacuation of the
refrigeration lines and the indoor coil, without
disturbing the factory charge in the outdoor unit.
3. Follow the vacuum pump manufacturer's
instructions. Allow the pump to operate until the
system has been evacuated down to 300 microns.
Allow the pump to continue running for an additional
15 minutes. Turn OFF the pump and leave the
connections secured to the two (2) service valves.
After 5 minutes, if the system fails to hold 500
microns or less, check all connections for tight fit and
repeat the evacuation procedure.
Provide line voltage power supply to unit from a properly
sized disconnect switch. Route power and ground wires
from disconnect switch to unit. Line voltage connections
are made at the line side of the contactor in the control box
of the outdoor unit. Follow the appropriate wiring diagram
attached to inside of the access panel.
Proper circuit protection recommendations are indicated
on Unit Rating Plate. Time delay fuses are required to
prevent blowing due to starting current (the current in rush
when equipment starts is referred to as the Locked Rotor
Amps or (LRA). A fuse of this kind properly sized will give
maximum equipment protection.
4. Isolate the vacuum pump from the system by closing
the shutoff valves on the gauge-set. Disconnect the
vacuum pump.
Use copper wire only between disconnect switch and
unit.
Remove access panel to gain access to unit wiring.
Extend wires from disconnect through power wiring hole
provided and into unit control box. Flexible conduit is
required for the swing out control box feature.
Opening Service Valves
After evacuation of the connecting lines, remove the
service valve cap and fully insert the hex wrench into the
stem. A back-up wrench is required on the valve body to
open the valve stem. Back-out counterclockwise until the
valve stem just touches the coined edge.
The unit cabinet must have an uninterrupted or
unbroken ground to minimize personal injury if
an electrical fault should occur. The ground
may consist of electrical wire or metal conduit
when installed in accordance with existing
electrical codes. Failure to follow this warning
can result in an electric shock, fire, or death.
Wrench sizes:
3/8 service valve: 3/16" Hex wrench
3/4 service valve: 5/16" Hex wrench
7/8 service valve: 5/16" Hex wrench
Replace service valve cap and torque to 8-11 ft-lb on 3/8"
valves; 12-15 ft-lb on 3/4" valves; 15-20 ft-lb on 7/8" valves.
Use backup wrench on valve body when torqueing valve
cap.
Connect ground wire to ground connection in control box
for safety. Connect power wiring to contactor.
High voltage power connections to 3-phase models is
made to "Pig Tail" leads with field supplied splice
connectors.
Install Electrical Accessories
Refer to the instructions packaged with the accessories.
Control Wiring
The control voltage is 24 Vac. NEC Class I insulated 18
AWG is required for control wiring. For lengths longer than
150 feet, contact your local distributor for technical service.
Electrical Connections
. . . .
ELECTRICAL SHOCK HAZARD!
Ensure the room thermostat is properly installed per
instructions shipped with room thermostat. Generally the
thermostat should not be exposed to sunlight, drafts or
vibration and should not be mounted on exterior walls.
Turn OFF electric power before connecting unit,
performing any maintenance or removing
panels or doors. More than one disconnect
may be required to turn off all power.
Low voltage control wire connections should be made to
the screw connection terminal board mounted on the
defrost control as shown. All low voltage control wiring
must be separated from incoming power leads.
FAILURE TO DO SO COULD RESULT IN BODILY
INJURY OR DEATH.
Be sure to check all local codes to determine that the unit
is installed accordance with local requirements. Consult
the National Electric Code for wire size requirements. Use
60/ C wire or higher. Always provide ground connections
to the outdoor unit. Power supply must agree with rating
on unit nameplate.
100402-07
Issue 0733
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 5 of 18
Adjusting Charge
Factory charge is shown on the rating label located on
the access panel.
All split system heat pumps are factory charged for
15 feet of connecting line set and matched indoor fan
coil. Nameplate refrigerant charge should initially be
adjusted for line set lengths other than 15 feet. For line
sets shorter than 15 feet in length, remove charge. For line
sets longer than 15 feet, add charge. Oil charge is
sufficient for all line lengths.
Refrigeration Charge Adjustment
Liquid Line Diameter
3/8"
Oz. Per Linear Foot *
.6
* Factory charge for series is for 15' (ft.) line sets and matched fan
coil.
Before final adjustment is made to the refrigerant charge,
it is imperative that proper indoor airflow be established.
Airflow will be higher across a dry coil versus a wet coil.
Blower charts are calculated with a dry or wet coil basis.
Recommended airflow is 350-450 CFM per ton (12,000
Btuh) through a wet coil. Refer to indoor unit instructions
for methods of determining air flow and blower
performance.
Heat Pump Application with Electric Heat
Emergency Heat (heating heat pump)
If selector switch on thermostat is set to the emergency
heat position, the heat pump will be locked out of the
heating circuit, and all heating will be electric heat ( if
applicable). A jumper should be placed between W and E
on the thermostat so that the electric heat control will
transfer to the first stage heat on the thermostat. This will
allow the indoor blower to cycle on and off with the electric
heat when the fan switch is in the AUTO position.
Cooling Cycle Charge Adjustment
The optimum method for checking the charge is by
weight. However the following methods may be used
to confirm the proper charge:
Units with Indoor Pistons
Units installed with indoor pistons require charging with
the superheat method.
* Add Jumper on Subbase (Optional)
The following procedure is valid when indoor airflow is
within ± 20% of its rated CFM.
Start-Up Procedure
1. Check to ensure:
1. Operate unit a minimum of 10 minutes before
checking charge.
2. Measure suction pressure by attaching a gage to
suction valve service port. Do not use compressor
suction port. Determine saturation temp from T/P
chart.
3. Measure suction temperature by attaching an
accurate thermistor type or electronic thermometer
to suction line at service valve.
4. Calculate superheat (measured temp. — saturation
temp.).
5. Measure outdoor air dry-bulb temperature with
thermometer.
6. Measure indoor air (entering indoor coil) wet-bulb
temperature with a sling psychrometer.
7. Compare superheat reading at service valve with the
chart located on control box cover.
8. If unit has a higher suction line temperature than
charted temperature, add refrigerant until charted
temperature is reached.
9. If unit has a lower suction line temperature than
chartedtemperature, reclaimrefrigerantuntilcharted
temperature is reached.
!
!
!
!
Service valve and gage port caps are installed and
tightened.
Voltage supply at unit agrees with nameplate
rating.
Field wiring connections are tight and factory
wiring has not been disturbed and are tight.
Indoor fan motor is on correct speed tap.
2. Set thermostat selector switch to OFF and fan control
switch to "Auto" is so equipped.
3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure
set point is below indoor ambient temperature.
5. Set the system switch of the thermostat on COOL (or
HEAT if applicable) and fan switch for continuous
operation (ON) or AUTO, as desired. There will be a
5 minute short cycle compressor delay on startup.
Operate unit for 15-20 minutes, then check the system
refrigerant charge.
6. Adjust refrigerant charge per "Adjusting Charge"
section.
100402-07
Issue 0733
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 6 of 18
10. Remove charge if superheat is low and add charge
if superheat is high.
SYSTEM OPERATION
The outdoor unit and indoor blower cycle on demand
from the room thermostat. When the thermostat blower
switch is in the ON position, the indoor blower operates
continuously.
Model
Required Subcooling
(± I/F)
HP 13
14
HP 14
10
Filter Drier
18
24
30
36
42
48
60
The outdoor unit is equipped with a bi-flow filter drier. If
replacementisnecessary, ordernewdryer accordingtothe
service parts manual.
9
13
9
3
8
14
3
11
8
9
Emergency Heat Function (Room Thermostat)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of
outdoor unit is required or when auxiliary electric heat is
staged by outdoor thermostats. When the room thermostat
is placed in the emergency heat position, the outdoor unit
control circuit is isolated from power and field-provided
relays bypass the outdoor thermostats. An amber
indicating light simultaneously comes on to remind the
homeowner that he is operating in the emergency heat
mode.
12
-
Units with Indoor TXV
Units installed with TXV on indoor side, require charging
with the subcooling method.
1. Operate unit a minimum of 10 minutes before
checking charge.
2. Measure liquid service valve pressure by attaching
an accurate gage to service port. Determine
saturation temp. from T/P chart.
3. Measure liquid line temperature by attaching an
accurate thermistor type or electronic thermometer
to liquid line near outdoor coil.
4. Calculate subcooling (saturation temp.— measured
temp.).
5. Find the point where required subcooling
temperatureintersectsmeasuredliquidservicevalve
pressure.
Emergency heat is usually used during an outdoor unit
shutdown, but it should also be used following a power
outage. If power has been off for over an hour and the
outdoor temperature is below 50/F (10/C). System should
be left in the emergency heat mode at least six hours to
allow the crankcase heater sufficient time to prevent
compressor slugging. This applies only to systems with
crank case heaters.
Defrost System
The defrost system includes two (2) components: a
defrost thermostat and a defrost control.
6. Add refrigerant if subcooling is lower than table
below. Recover refrigerant if subcooling is high.
Defrost Thermostat
Heating Check Chart Procedure
The defrost thermostat is located on the liquid line
between the check/expansion valve and the distributor.
When defrost thermostat senses 29/F or cooler, the
thermostat contacts close and send a signal to the defrost
control board to start the defrost timing. It also terminates
defrost when the liquid line warms up to 60/F.
To check system operation during heating cycle, refer to
the Heating Check Chart located on back of control box
cover. This chart indicates whether a correct relationship
exists between system operating pressure and air
temperature entering indoor and outdoor units. If pressure
and temperature do not match on chart, system refrigerant
charge may not be correct. Do not use chart to adjust
refrigerant charge.
Defrost Control
The defrost control board includes the combined
functions of a time/temperature defrost control, defrost
relay, diagnostic LEDs and terminal strip for field wiring
connections.
Charge must be rechecked again during the cooling
season.
The control provides automatic switching from normal
heating operation to defrost mode and back. During
compressor cycle, the control accumulates compressor
run times at 30-, 60-, or 90-minute field-adjustable
intervals. If the defrost thermostat is closed when the
selected compressor run time interval ends (call for
Cold Weather Application
A cold weather accessory kit may be required for heat
pumps operating at ambient conditions below 25/ F.
Supplemental heat should be provided for these conditions
due to the expected performance degeneration.
100402-07
Issue 0733
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 7 of 18
defrost), the defrost relay is energized and defrost begins.
The factory setting is 60 minutes. However, if frost
accumulation is easily cleared, the optimum efficiency
setting is 90 minutes.
removed.
NOTE: The 30 second "off" cycle is not functional when
jumpering the TEST pins.
Time Delay
The timed-off delay is 5 minutes long. The delay help to
protect the compressor from short-cycling in case the
power to the unit is interrupted or a pressure switch opens.
The delay is bypassed by placing the timer select jumper
across the TEST pins for 0.5 seconds.
Pressure Switch Circuit
The defrost control incorporates 2 pressure switch
circuits. The optional high pressure switch connects to the
boards HI PS terminals. The low pressure switch is factory
installed.
During a single demand cycle, the defrost control will lock
out the unit after the fifth time that the circuit is interrupted
by any pressure switch wired to the control board. In
addition, the diagnostic LEDs will indicate a locked-out
pressure switch after the fifth occurrence of an open
pressure switch. The unit will remain locked out until power
to the board is interrupted, then re-established or until the
jumper is applied to the TEST pins for 0.5 seconds.
Outdoor Unit Defrost Control Board
Defrost Control Timing Pins
NOTE: The defrost control board ignores input from the
low-pressure switch terminals as follows:
Each timing pin selection provides
a
different
!
!
!
!
During the TEST mode,
During the defrost cycle,
During the 90 second start-up period,
and for the first 90 seconds each time the reversing
valve switches heat/cool modes. If the TEST pins
are jumpered and the 5 minute delay is being by-
passed, the LO PS terminal signal is not ignored
during the 90 second start-up period.
accumulated compressor run time period for one defrost
cycle. This time period must occur before a defrost cycle
is initiated. The defrost interval can be adjusted to 30 (/T1),
60 (T2), or 90 (T3) minutes. The defrost timing jumper is
factory-installed to provided a 90-minute defrost interval.
If the timing selector jumper is not in place the control
defaults to a 90-minute defrost interval. The maximum
defrost period is 14 minutes and cannot be adjusted.
A TEST option is provided for troubleshooting. The
TEST mode may be started any time the unit is in the
heating mode and the defrost thermostat is closed or
jumpered. If the jumper is in the TEST position at power-
up, the control will ignore the test pins. When the jumper
is placed across the TEST pins for 2 seconds, the control
will enter the defrost mode. If the jumper is removed
before an additional 5 second period has elapsed ( 7
seconds total), the unit will remain in defrost mode until the
defrost thermostat opens or 14 minutes have passed. If
the jumper is not removed until after the additional 5
second period has elapsed, the defrost will terminate and
the test option will not function again until the jumper is
removed and re-applied.
Diagnostic LEDS
The defrost board uses 2 LEDs for diagnostics. The
LEDs flash a specific sequence according to the condition.
Defrost Control board Diagnostic LED
Mode
Green LED (DS2)
OFF
Red LED (DS1)
OFF
No power to control
Normal operation/
power to control
Anti-short cycle
lockout
Low pressure switch
fault (Optional)
Low pressure switch
lockout (Optional)
High pressure switch
fault (Optional)
Simultaneous Slow FLASH
Alternating Slow FLASH
OFF
Slow FLASH
OFF
ON
Slow FLASH
ON
OFF
OFF
High pressure Switch
lockout (Optional)
Compressor Delay
The defrost board has a field-selectable function to
reduce occasional sounds that may occur while the unit is
cycling in and out of the defrost mode. The compressor will
be cycled "off" for 30 seconds going in and out of the
defrost mode when the compressor delay jumper is
100402-07
Issue 0733
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 8 of 18
H/P SINGLE PHASE WIRING DIAGRAM
100402-07
Issue 0733
Page 9 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
H/P 3 PHASE WIRING DIAGRAM
100402-07
Issue 0733
Page 10 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
SUPERHEAT TABLES FOR CHARGING SYSTEMS WITH PISTON COILS
Required Superheat for 2HP13 (B,L)18P-1A
OUTDOOR DRY BULB TEMPERATURE (/F)
INDOOR
WET-BULB (/F)
60
6
65
--
70
--
75
--
80
--
85
--
90
--
95
--
100
--
105
--
110
--
115
--
53
55
57
59
61
63
65
67
69
71
73
75
9
1
--
--
--
--
--
--
--
--
--
--
12
15
18
18
24
27
30
34
37
40
4
--
--
--
--
--
--
--
--
--
--
8
1
--
--
--
--
--
--
--
--
--
12
15
20
24
28
32
36
40
6
1
--
--
--
--
--
--
--
--
12
16
20
25
30
35
39
9
3
--
--
--
--
--
--
--
12
17
23
28
34
39
6
3
--
--
--
--
--
--
13
19
26
32
39
10
13
16
27
38
6
3
--
--
--
--
7
5
--
--
--
--
8
7
3
--
--
--
22
37
15
36
10
34
--
--
--
32
31
30
Heating Mode Pressures 2HP13(B,L)18P-1A
Press. (psig)
High Low
Press. (psig)
OUTDOOR
OUTDOOR
(/F)
(/F)
High
168
Low
42
70
65
60
55
50
45
40
35
234 85
30
25
20
15
10
225
216
208
199
190
183
176
79
73
69
63
57
53
47
161
154
148
142
38
33
30
25
Required Superheat for 2HP13 (B,L)24P-1A
OUTDOOR DRY BULB TEMPERATURE (/F)
INDOOR
WET-BULB (/F)
60
6
9
65
--
1
5
9
70
--
--
--
1
75
--
--
--
--
80
--
--
--
--
85
--
--
--
--
90
--
--
--
--
95
--
--
--
--
100
--
--
--
--
105
--
--
--
--
110
--
--
--
--
115
--
--
--
--
53
55
57
59
61
63
65
67
69
71
73
75
13
17
20
20
27
30
33
37
40
43
13
17
22
26
30
35
39
43
6
0
--
--
--
--
--
--
--
--
13
17
22
28
33
38
43
10
13
18
25
31
37
43
3
--
--
--
--
--
--
--
6
3
--
--
--
--
--
--
15
21
29
36
44
11
13
19
32
44
7
7
10
27
44
3
5
7
--
--
3
--
--
--
--
--
--
--
--
--
21
45
10
45
--
--
--
46
46
47
Heating Mode Pressures 2HP13(B,L)24P-1A
Press. (psig)
Press. (psig)
High Low
OUTDOOR
OUTDOOR
(/F)
(/F)
High Low
70
65
60
55
50
45
40
35
228 73
30
25
20
15
10
164 36
220
211
202
194
185
178
171
68
63
59
54
49
45
40
156
150
144
139
32
28
26
22
100402-07
Issue 0733
Page 11 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
Required Superheat for 2HP13 (B,L)30P-1A
OUTDOOR DRY BULB TEMPERATURE (/F)
INDOOR
WET-BULB (/F)
60
6
65
--
70
--
75
--
80
--
85
--
90
--
95
--
--
--
--
--
--
--
3
100
--
105
--
110
--
115
--
53
55
57
59
61
63
65
67
69
71
73
75
9
1
--
--
--
--
--
--
--
--
--
9
3
--
--
--
--
--
--
--
--
--
11
14
15
19
22
25
27
30
33
6
2
--
--
--
--
--
--
--
--
10
12
16
19
22
26
29
32
5
1
--
--
--
--
--
--
--
10
13
16
20
24
28
31
8
3
--
--
--
--
--
--
10
14
18
22
27
31
5
3
--
--
--
--
--
11
15
20
25
30
8
6
--
--
--
--
13
12
20
28
7
5
--
--
--
--
5
7
3
--
--
--
15
26
7
10
18
--
--
--
23
13
11
8
Heating Mode Pressures 2HP13(B,L)30P-1A
Press. (psig)
High Low
252 84
Press. (psig)
OUTDOOR
OUTDOOR
(/F)
(/F)
High
181
Low
42
70
65
60
55
50
45
40
35
30
25
20
15
10
243
233
224
214
205
197
189
78
73
68
62
57
52
46
173
160
159
153
37
33
30
25
Required Superheat for 2HP13 (B,L)36P-1A
OUTDOOR DRY BULB TEMPERATURE (/F)
INDOOR
WET-BULB (/F)
60
6
65
--
70
--
75
--
80
--
85
--
90
--
95
--
100
--
105
--
110
--
115
--
53
55
57
59
61
63
65
67
69
71
73
75
9
1
--
--
--
--
--
--
--
--
--
--
12
15
18
18
24
27
30
34
37
40
4
--
--
--
--
--
--
--
--
--
--
8
1
--
--
--
--
--
--
--
--
--
12
15
20
24
28
32
36
40
6
1
--
--
--
--
--
--
--
--
12
16
20
25
30
35
39
9
3
--
--
--
--
--
--
--
12
17
23
28
34
39
6
3
--
--
--
--
--
--
13
19
26
32
39
10
13
16
27
38
6
3
--
--
--
--
7
5
--
--
--
--
8
7
3
--
--
--
22
37
15
36
10
34
--
--
--
32
31
30
Heating Mode Pressures 2HP13(B,L)36P-1A
Press. (psig)
High Low
269 84
Press. (psig)
High Low
193 42
OUTDOOR
OUTDOOR
(/F)
(/F)
70
65
60
55
50
45
40
35
30
25
20
15
10
259
248
239
228
219
210
202
78
73
68
62
57
52
46
185
177
170
163
37
33
30
25
100402-07
Issue 0733
Page 12 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
Required Superheat for 2HP13 (B,L)42P-1A
OUTDOOR DRY BULB TEMPERATURE (/F)
INDOOR
WET-BULB (/F)
60
6
65
--
70
--
75
--
80
--
85
--
90
--
95
--
100
--
105
--
110
--
115
--
53
55
57
59
61
63
65
67
69
71
73
75
9
1
--
--
--
--
--
--
--
--
--
--
12
15
18
18
24
27
30
34
37
40
4
--
--
--
--
--
--
--
--
--
--
8
1
--
--
--
--
--
--
--
--
--
12
15
20
24
28
32
36
40
6
1
--
--
--
--
--
--
--
--
12
16
20
25
30
35
39
9
3
--
--
--
--
--
--
--
12
17
23
28
34
39
6
3
--
--
--
--
--
--
13
19
26
32
39
10
13
16
27
38
6
3
--
--
--
--
7
5
--
--
--
--
8
7
3
--
--
--
22
37
15
36
10
34
--
--
--
32
31
30
Heating Mode Pressures 2HP13(B,L)42P-1A
Press. (psig)
High Low
266 87
Press. (psig)
OUTDOOR
OUTDOOR
(/F)
(/F)
High
192
Low
43
70
65
60
55
50
45
40
35
30
25
20
15
10
257
246
237
226
217
208
200
81
75
70
65
59
54
48
183
176
168
162
39
34
31
26
Required Superheat for 2HP13 (B,L)48P-1A
OUTDOOR DRY BULB TEMPERATURE (/F)
INDOOR
WET-BULB (/F)
60
6
65
--
70
--
75
--
80
--
85
--
90
--
95
--
100
--
105
--
110
--
115
--
53
55
57
59
61
63
65
67
69
71
73
75
9
1
--
--
--
--
--
--
--
--
--
--
15
19
22
22
29
33
36
40
43
47
5
--
--
--
--
--
--
--
--
--
--
10
14
18
24
28
33
38
42
47
1
--
--
--
--
--
--
--
--
--
7
0
--
--
--
--
--
--
--
--
14
18
24
30
36
42
48
10
13
20
27
34
41
48
3
--
--
--
--
--
--
--
6
3
--
--
--
--
--
--
16
23
32
40
48
11
13
22
37
50
7
3
--
--
--
--
7
5
--
--
--
--
14
33
52
7
3
--
--
--
29
55
10
59
--
--
--
64
65
68
Heating Mode Pressures 2HP13(B,L)48P-1A
Press. (psig)
High Low
281 84
Press. (psig)
High Low
202 42
OUTDOOR
OUTDOOR
(/F)
(/F)
70
65
60
55
50
45
40
35
30
25
20
15
10
271
260
250
239
229
220
211
78
73
68
62
57
52
46
193
185
178
171
37
33
30
25
100402-07
Issue 0733
Page 13 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
Required Superheat for 2HP13 (B,L)60P-1A
OUTDOOR DRY BULB TEMPERATURE (/F)
INDOOR
WET-BULB (/F)
60
6
65
--
70
--
75
--
80
--
85
--
90
--
95
--
100
--
105
--
110
--
115
--
53
55
57
59
61
63
65
67
69
71
73
75
9
1
--
--
--
--
--
--
--
--
--
--
12
15
18
18
24
27
30
34
37
40
4
--
--
--
--
--
--
--
--
--
--
8
1
--
--
--
--
--
--
--
--
--
12
15
20
24
28
32
36
40
6
1
--
--
--
--
--
--
--
--
12
16
20
25
30
35
39
9
3
--
--
--
--
--
--
--
12
17
23
28
34
39
6
3
--
--
--
--
--
--
13
19
26
32
39
10
13
16
27
38
6
3
--
--
--
--
7
5
--
--
--
--
8
7
3
--
--
--
22
37
15
36
10
34
--
--
--
32
31
30
Heating Mode Pressures 2HP13(B,L)60P-1A
. . . . . . . . . . . . . . . . . . . . . . . . .
Press. (psig)
High Low
292 74
Press. (psig)
OUTDOOR
OUTDOOR
(/F)
(/F)
High
210
Low
37
70
65
60
55
50
45
40
35
30
25
20
15
10
281
270
259
248
237
228
219
69
64
60
55
50
46
41
200
192
184
177
33
29
26
22
100402-07
Issue 0733
Page 14 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
Homeowner's Information
information below is typical for most thermostats. Ask your
dealer for specific information regarding the model of
thermostat installed.
ELECTRICAL SHOCK HAZARD!
Turn OFF electric power to unit before performing
any maintenance or removing panels or doors.
Temperature Setting Levers
Mostheatpumpthermostats have 2 temperature selector
levers: one for heating and one for cooling. Set the levers
or dials to the desired temperature set points for both
FAILURE TO DO SO COULD RESULT IN BODILY
INJURY OR DEATH.
heating and cooling.
Avoid frequent temperature
adjustment; turning the unit off and back on before
pressures equalize puts stress on the unit compressor.
Heat Pump Operation
Your new heat pump has several characteristics that you
should be aware of:
On heat pump systems, increasing your thermostat
setting by more than 2 degrees may cause supplemental
heaters to turn on, reducing potential energy savings.
!
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This
is quite different from gas-or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
Fan Switch
!
Do Not be alarmed if you notice frost on the outdoor
coil in the winter months. Frost develops on the
outdoor coil during the heating cycle when
temperatures are below 45/F. An electronic control
activates a defrost cycle lasting 5 to 15 minutes at
preset intervals to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence.
The thermostat may engage auxiliaryheat during the
defrost cycle to satisfy a heating demand; however.,
the unit will run to normal operation at the conclusion
of the defrost cycle.
In AUTO or INT (intermittent ) mode, the blower operates
only when the thermostat calls for heating or cooling. This
mode is generally preferred when humidity control is a
priority. The ON or CONT mode provides continuous
indoor blower operation, regardless of whether the
compressor or auxiliary heat are operating. This mode is
required when constant air circulation or filtering is desired.
!
System Switch
Set the system switch for heating, cooling or auto
operation. The auto mode allows the heat pump to
automatically switch from heating mode to cooling mode to
maintain predetermined comfort settings. Many heat pump
thermostats are also equipped with an emergency heat
mode which locks out heat pump operation and provides
temporary heat supplied by the auxiliary heat.
In case of extended power outage...
If the outdoor temperature is below 50/F and power to
your outdoor unit has been interrupted for 6 hours or
longer, observe the following when restoring power to your
heat pump system.
!
!
!
Set the room thermostat selector to the "Emergency
Heat" setting to obtain temporary heat for a minimum
of 6 hours. This will allow system refrigerant
pressures and temperatures enough time to return to
a stabilized condition.
In Emergency Heat mode, all heating demand is
satisfied by auxiliary heat; heat pump operation is
locked out. After a 6 hour "warm-up" period, the
thermostat can then be switched to the "Heat" setting
and normal heat pump operation my resume.
Heat pumps (in the cooling mode) remove humidity
from your home. Depending on the amount of
moisture in the air inside your home, water will trickle
from the condensate drain of the cooling coil.
Indicating Light
Most heat pump thermostats have an amber light which
indicates when the heat pump is operating in the
emergency heat mode.
Temperature Indicator
The temperature indicator displays the actual room
temperature.
Fan Control
For fan control your thermostat may have a Fan
Selection Switch that allows you to run the fan continuously
or cycle it automatically with the heating or cooling system.
Switch the lever to ON for continuous operation and to
AUTO for automatic cycling.
Thermostat Operation
The wall-mounted thermostat controls your air
conditioner. The thermostat is available in various
configurations from different manufacturers. The
For maximum comfort satisfaction and continual air
cleaning/filtering, constant fan operation is recommended.
100402-07
Issue 0733
Page 15 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
On models without a fan Selection Switch, the fan will
cycle with the outdoor unit.
of your unit and could cause damage to the condenser.
Periodically, debris should be brushed from the condenser
coils.
Important System Information
!
Your system should never be operated without a
clean air filter properly installed.
Return air and supply air registers should be free
from restrictions or obstructions to allow full flow of
air.
. . . . .
SHARP OBJECT HAZARD!
!
Condenser coils have sharp edges. Wear adequate
body protection on body extremities (e.g. gloves).
FAILURE TO FOLLOW THIS WARNING COULD
RESULT IN BODILY INJURY.
Regular Maintenance Requirements
Your system should be regularly inspected by a qualified
service technician. These regular visits may include
(among other things) checks for:
Use a soft bristle brush with light pressure only. DO NOT
damage or bend condenser coil fins. Damaged or bent fins
may affect unit operation.
!
!
!
!
!
!
!
!
!
!
!
Motor operation
Ductwork air leaks
Coil & drainpan cleanliness (indoor & outdoor)
Electrical component operation & wiring check
Proper refrigerant level & refrigerant leaks
Proper airflow
Drainage of condensate
Air filter(s) performance
Blower wheel alignment, balance & cleaning
Primary & secondary drain line cleanliness
Proper defrost operation (heat pumps)
Painted Surfaces
For maximum protection of the unit's finish, a good grade
of automobile wax should be applied every year. In
geographical areas where water has a high concentration
of minerals (calcium, iron, sulfur, etc.). It is recommended
that lawn sprinklers not be allowed to spray the unit. In
such applications, the sprinklers should be directed away
from the unit. Failure to follow this precaution may result in
premature deterioration of the unit finish and metal
components.
In sea coast areas, special maintenance is required due
to the corrosive atmosphere provided by the high salt
concentration in ocean mists and the air. Periodic washing
of all exposed surfaces and coil will add additional life to
your unit. Please consult your installing dealer for proper
procedures in your geographic area.
There is some routine maintenance procedures you can
do to help keep your system operating at peak
performance between visits.
Air Filter
Inspect air filters at least monthly and replace or clean as
required. Disposable filters should be replaced. Washable
filters may be cleaned by soaking in mild detergent and
rinsing with cold water. Replace filters with the arrows
pointing in the direction of airflow. Dirty filters are the most
common cause of poor heating / cooling performance and
compressor failures.
IF YOUR SYSTEM DOES NOT WORK,
BEFORE REQUESTING A SERVICE CALL:
1. Ensure thermostat is set below (cooling) or above
(heating) room temperature and that the system lever
is in the "COOL", "HEAT" or "AUTO" position.
2. Inspect your return air filter: If it is dirty your air
conditioner may not function properly.
Indoor Coil
If the system has been operated with a clean filter in
place, it should require minimal cleaning. Use a vacuum
cleaner and soft brush attachment to remove any
accumulation of dust from the top and underside of the
finned coil surface. However, perform this maintenance
only when the coil is completely dry.
3. Check indoor and outdoor disconnect switches.
Confirm circuit breakers are ON or that fuses have not
blown. Reset breakers/replace fuses as necessary.
4. Inspect the outdoor unit for clogged condenser coils,
(grass cuttings, leaves, dirt, dust or lint). Ensure that
branches, twigs or other debris are not obstructing the
condenser fan.
If the coil cannot be cleaned by this method, call your
dealer for service. It may need a detergent solution and
rinsing with water for cleaning, which may require coil
removal. You should not attempt this yourself.
IF YOUR SYSTEM STILL DOES NOT OPERATE,
CONTACT YOU SERVICING DEALER.
Condensate Drain
During cooling season check at least monthly for free
flow of drainage and clean if necessary.
Be sure to describe the problem, and have the model
and serial numbers of the equipment available.
Condenser Coils
If warranted replacements parts are required, the
warrantymustbeprocessedthroughaqualifieddistribution
location.
Grass cuttings, leaves, dirt, dust, lint from clothes dryers,
and fall off from trees can be drawn into coils by movement
of the air. Clogged condenser coils will lower the efficiency
100402-07
Issue 0733
Page 16 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
OUTDOOR EQUIPMENT LIMITED WARRANTY
(Not applicable outside the U.S.A. and Canada.)
Warrantor: Allied Air Enterprises Inc., 215 Metropolitan Drive, West Columbia, SC 29170
These Allied Air Enterprises, Inc. Products are available under the following names: Ducane, Concord
GENERAL FIVE YEAR PART WARRANTY - (hereinafter referred to as the company) warrants the product to be free from
defects in material and workmanship under normal use and maintenance for a period of five (5) years in residential applications (one
(1) year for commercial) on all components, except compressors as noted below. The warranty period begins on the date of original
installation whether or not actual use begins on that date. If the date of original installation cannot be verified, the warranty begins
on the date of manufacture plus six (6) months. At the Company's sole option, a new or re-manufactured part to replace any defective
part will be provided without charge for the part itself; PROVIDED the defective part is returned to our distributor through a qualified
servicing dealer or contractor. All warranty claims must be processed through a qualified distribution point. The replacement part
assumes the unused portion of the factory warranty. Residential application is defined as a single family or multi-family dwelling.
COVERED PARTS INCLUDE - accumulator, capacitor, condenser coil, contactor, expansions device, fan blade, fan motor,
muffler, reversing valve, service valve, solenoid valve, unit mounted sensors and switches, if present.
COMPRESSOR WARRANTY - The compressor in the above listed product is warranted to be free from defects in material and
workmanship under normal use and maintenance for a period of five (5) years for 13 SEER models (2AC13, 2HP13) and ten (10)
years for 14 SEER models (2AC14, 2HP14). The compressor will be provided without charge for the compressor itself; PROVIDED
the defective compressor is returned to our distributor through a qualified servicing dealer or contractor. The replacement compressor
assumes the unused portion of the factory warranty.
THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS - incurred for diagnosing, repairing, removing,
installing, shipping, servicing, or handling of either defective parts or replacement parts or complete unit. Other costs not covered
include items such as any materials not listed above, refrigerant and refrigerant reclaiming. Such costs may be covered by a separate
warranty provided by the installing dealer or contractor.
THESE WARRANTIES APPLY ONLY:
-
-
To products in their original installation location and become void upon re-installation.
To units installed with indoor coil combinations listed in the Air-Conditioning and Refrigeration Institute (ARI) Directory of Certified
EXCEPTIONS TO LIMITED WARRANTY - When the outdoor unit is installed in non-residential applications; in these cases the
compressor is warranted for five (5) years.
LIMITATIONS OF WARRANTIES - All implied warranties (including implied warranties of merchantability) are hereby limited in
duration to the period for which the limited warranty is given. Some states do not allow limitations on how long an implied warranty
lasts, so the above may not apply to you. The expressed warranties made in this warranty are exclusive and may not be altered,
enlarged, or changed by any distributor, dealer, contractor or other person whatsoever.
THE COMPANY WILL NOT BE RESPONSIBLE FOR:
1. Failure to start due to voltage conditions, blown fuses, open circuit breakers or other damages due to the inadequacy or
interruption of electrical service;
2. Damage as a result of floods, winds, fires, lightning, accidents, corrosive environments or other conditions beyond the control
of the Company;
3. Damage or repairs required as a consequence of faulty installation, misapplication, abuse, improper servicing, unauthorized
alteration or improper operation;
4. Normal maintenance as outlined in the installation and servicing instructions or owner's manual including coil cleaning, filter
cleaning and/or replacement and lubrication;
5. Parts not supplied or designated by the Company, or damages resulting from their use;
6. The Company products installed outside the United States of America and Canada;
7. Electricity or fuel costs or increases in electricity or fuel costs for any reason whatsoever including additional or unusual use of
supplemental electric heat;
8. ANY SPECIAL INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE OF ANY NATURE
WHATSOEVER. Some states do not allow the exclusion of incidental or consequential damages, so the above limitation may
not apply to you.
This warranty gives you specific rights, and you may also have other rights that vary from state to state.
100402-07
Issue 0733
Page 17 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
Keep this book and your sales slip together for future reference. You must provide proof of purchase or installation
date for in-warranty service.
Write down the following information about your unit to better help you obtain assistance or service if you ever need it. You
will need to know the complete model and serial number. You can find this information on the unit rating plate.
Dealer Name:
Address:
Phone Number:
Indoor Model Number:
Indoor Model Number:
Installation Date:
Serial Number:
Serial Number:
100402-07
Issue 0733
Page 18 of 18
Download from Www.Somanuals.com. All Manuals Search And Download.
|