Dimplex Heat Pump S1 7KS User Manual

CE  
INSTALLATION and  
OPERATING INSTRUCTIONS  
Brine-to-Water Heat Pump  
for Indoor Installation  
SI 7KS  
SI 9KS  
SI 11KS  
SI 14KS  
Order No.: 452231.67.01  
FD 8504  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLEASE READ IMMEDIATELY  
READ IMMEDIATELY  
1.1 Important Information  
CAUTION!  
The supplied strainer is to be fitted  
1
in the heat source inlet of the heat pump  
in order to protect the evaporator against  
contamination.  
CAUTION!  
The heat pump is not secured to the  
wooden pallet.  
CAUTION!  
Any work on the heat pump may  
only be performed by authorised and qualified  
customer service agents.  
The heat pump must not be tilted  
CAUTION!  
more than max. 45° (in either direction).  
1.2 Legal Provisions and Directives  
CAUTION! Do not lift unit by the holes in the  
panel assemblies!  
This heat pump conforms to all relevant DIN/VDE  
regulations and EU directives. For details refer to  
the EC Declaration of Conformity in the appendix.  
CAUTION! In the case of large-capacity heating  
circuits, the installed expansion vessel (24  
litres, 1.0 bar admission pressure) must be  
supplemented by an additional vessel.  
The electrical connection of the heat pump must be  
performed according to and conforming with all re-  
levant VDE, EN and IEC standards. Beyond that, the  
connection requirements of the local utility compa-  
nies have to be observed.  
CAUTION! The brine solution must contain at  
least 25 % of an antifreeze and corrosion  
protection agent on a monoethylene glycol or  
propylene glycol basis.  
The heat pump is to be connected to the heat source  
and heat distribution systems in accordance with all  
applicable provisions.  
CAUTION!  
On connecting the electrical load  
lines, the clockwise phase sequence must be  
observed (in the case of an incorrect phase  
sequence the heat pump will deliver no output  
and generate a lot of noise).  
1.3 Energy-Efficient Use of the Heat  
Pump  
By operating this heat pump you contribute to the  
protection of our environment. A prerequisite for an  
efficient operation is the proper design and sizing of  
the heating system and the heat source system. In  
particular, it is important to keep water flow  
temperatures as low as possible. All energy  
consumers connected should therefore be suitable  
for low flow temperatures. A 1 K higher heating water  
temperature corresponds to an increase in power  
consumption of approx. 2.5 %. Underfloor heating  
systems with flow temperatures between 30 °C and  
40 °C are optimally suited for energy-efficient  
operation.  
Commissioning of the heat pump  
CAUTION!  
must be performed in accordance with the  
installation and operating manual of the heat  
pump controller.  
Caution - Heating Contractors !  
CAUTION!  
Depending on the filling water quality and  
quantity, in particular in the case of mixed  
installations and plastic pipes, mineral deposits  
(rust sludge, lime) may form, impairing the pro-  
per functioning of the heating installation. A  
reason for this is the water hardness and  
oxygen dissolved in the filling water as well as  
additional oxygen from the air, which may  
penetrate via valves, fittings and plastic pipes  
(oxygen diffusion). As a preventive measure it  
is recommended that a physical water conditio-  
ner such as ELYSATOR be used.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PURPOSE OF HEAT PUMP  
BASELINE UNIT  
PURPOSE OF THE HEAT  
BASELINE UNIT  
PUMP  
2 3  
The baseline unit consists of a heat pump of  
compact design, ready for connection. In addition to  
the control panel with integrated controller, the unit  
also contains essential components of the heating  
and brine circuits:  
2.1Application  
The brine-to-water heat pump is designed for use  
in existing or newly built heating systems. Brine is  
used as the heat carrier in the heat source system.  
Ground coils, ground collectors or similar systems  
can be used as the heat source.  
- expansion vessels  
- circulating pumps  
- pressure relief valves  
- pressure gauges  
- overflow valve (heating circuit)  
2.2 Principle of Operation  
The refrigeration cycle contains the refrigerant  
R407C. Refrigerant R407C is CFC-free, non-ozone  
depleting and non-combustible.  
The heat generated by the sun, wind and rain is  
stored in the ground. This heat stored in the ground  
is collected at low temperature by the brine circulating  
in the ground collector, ground coil or similar device.  
A circulating pump then conveys the warmed brine  
to the evaporator of the heat pump. There, the heat  
is given off to the refrigerant in the refrigeration cycle.  
When so doing, the brine cools so that it can again  
take up heat energy in the brine circuit.  
All components required for the operation of the heat  
pump are provided on the control panel. The power  
feed for load and control current must be field-  
installed by the customer.  
The collector loops including brine manifold must  
be provided by the customer.  
1
2
The refrigerant, however, is drawn in by the electrically  
driven compressor, is compressed and "pumped"  
to a higher temperature level. The electrical power  
needed to run the compressor is not lost in this  
process, but most of the generated heat is trans-  
ferred to the refrigerant as well.  
Subsequently, the refrigerant is passed through the  
condenser where it transfers its heat energy to the  
heating water. Based on the thermostat setting, the  
heating water is thus heated to up to 55 °C.  
3
4
5
6
1) Control panel  
2) Circulating pumps  
3) Condenser  
4) Compressor  
5) Evaporator  
6) Expansion vessel  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
TRANSPORT  
ACCESSORIES  
TRANSPORT  
4 5  
4.1 Brine Manifold  
A lift truck is suited for transporting the unit on a level  
surface. If the heat pump needs to be transported  
on an uneven surface or carried up or down stairs,  
carrying straps may be used for this type of transport.  
These straps may be passed directly underneath  
the wooden pallet.  
The brine manifold ties the individual collector loops  
of the heat source system into a single main line  
which is connected to the heat pump. Integrated ball  
valves allow individual brine circuits to be shut off for  
venting purposes.  
The heat pump is not secured to the  
CAUTION!  
wooden pallet.  
The heat pump must not be tilted  
CAUTION!  
4.2 Brine Pressostat  
more than max. 45° (in either direction).  
Where this is a legal requirement, a low-pressure  
brine pressostat may be installed in the unit. In this  
case, the connection provided above the brine  
expansion vessel should be used.  
For lifting the unit without pallet, the holes provided  
in the sides of the frame should be used. The side  
panel assemblies must be removed for this  
purpose. A commercially available pipe can be used  
as a carrying aid.  
Do not use the holes in the panel  
CAUTION!  
assemblies for lifting the unit!  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
MOUNTING  
INSTALLATION  
6.1 General Information  
MOUNTING  
6 7  
7.1 General  
As a rule, the unit must be installed indoors on a  
level, smooth and horizontal surface. The entire base  
frame should thereby make close contact with the  
surface in order to ensure adequate sound  
insulation. Failing this, additional sound insulation  
measures may become necessary.  
The following connections need to be established on  
the heat pump:  
- supply/return flow of the brine system  
- supply/return flow of the space heating and  
water heating system  
- common return of space heating and water  
heating system  
The heat pump should be located to allow safe and  
easy maintenance/service access. This is ensured  
if a clearance of approx. 1 m in front of and to each  
side of the heat pump is maintained.  
- return, overflow valve  
- connection for additional expansion vessel  
(as required)  
- drain lines of overflow valves  
- condensate drain  
- power supply  
7.2 Heating-Side Connection  
The heat pump features separate outlets for the space  
heating and water heating circuit.  
In cases where the heat pump has no water heating  
mode, the hot water outlet has to be permanently  
sealed.  
Prior to establishing the heat pump connections on  
the heating water side, the heating installation must  
be flushed in order to remove any impurities that  
may be present , as well as residues of sealing  
material, or the like. Any accumulation of deposits in  
the condenser may result in a total failure of the heat  
pump.  
6.2 Sound Emissions  
The heat pump offers silent operation due to efficient  
sound insulation. Noise transmission to the  
foundation or the heating system is largely prevented  
by internal decoupling measures.  
In systems equipped with heating water flow shut-  
off devices such as radiator or thermostat valves, an  
overflow valve is installed. This assures a minimum  
heating water flow through the heat pump and  
prevents any malfunctions for occurring.  
Once the installation on the heating side has been  
completed, the heating system must be filled,  
deaerated and pressure-tested.  
Frost Protection for Installations Prone to Frost  
Provided the controller and the heating circulating  
pumps are ready for operation, the frost protection  
function of the controller is always activated. If the  
heat pump is taken out of service or in the event of a  
power failure, the system must be drained. In heat  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
MOUNTING  
pump installations where a power failure cannot  
readily be detected (e.g. holiday houses), the heating  
circuit must contain a suitable antifreeze product.  
7.4 Electrical Connection  
The following electrical connections must be  
established on the heat pump.  
The integrated expansion vessel has a capacity of  
-
Connection of the load wire to the control panel  
24 litres.This capacity is appropriate for buildings  
of the heat pump.  
2
with a heated living space floor area of up to 200 m .  
-
Connection of the control voltage wire to the  
control panel of the heat pump.  
The planner of the heating system should verify that  
the capacity of the expansion vessel is adequate. An  
additional expansion vessel may have to be  
installed, if required (as per DIN 4751 Part 1). Charts  
in manufacturer catalogues facilitate the proper  
selection of the proper size according to the amount  
of water in the system.  
All electrical components required for the operation  
of the heat pump are located on the control panel..  
For detailed instructions concerning the connection  
of external components and the operation of the heat  
pump controller refer to the heat pump terminal dia-  
gram and the operating manual of the controller.  
With large-capacity heating circuits,  
CAUTION!  
Connection of the load wire to the control panel via  
the installed expansion vessel (24 litres, 1.0 bar  
admission pressure) must be supplemented by  
an additional vessel.  
terminals X1: L1/L2/L3/PE.  
An all-pole disconnecting device with a contact gap  
of at least 3 mm (e.g. utility company disable contac-  
tor or power contactor) as well as a 3-pole circuit  
breaker with simultaneous tripping of all external  
conductors must be provided . The required cross-  
sectional area of the conductor is to be selected  
according to the power consumption of the heat  
pump, the technical connection requirements of the  
relevant utility company and all applicable regula-  
tions. Power consumption data of the heat pump is  
provided in the product literature and on the  
nameplate. The terminals are designed for a max.  
conductor cross-section of 10 mm˝.  
7.3 Connection on Heat Source Side  
The following procedure must be observed when  
making the connection:  
Connect the brine line to the flow and return pipe  
of the heat pump. The supplied strainer and vent  
must be field-installed in the brine inlet of the heat  
pump.  
The powerful vent must be installed at the highest  
point of the heat source system  
The hydraulic block schematic must be taken into  
account when so doing.  
CAUTION!  
The clockwise phase sequence  
must be observed when connecting the electric  
load lines (in the case of an incorrect phase  
sequence the heat pump will deliver no output  
and generate a lot of noise).  
The brine liquid must be produced prior to charging  
the system. The brine concentration must be at least  
25 %. Freeze protection down to -14 °C can thus be  
ensured.  
Connection of the control voltage wire is effected via  
Only antifreeze agents on a monoethylene glycol or  
terminals X1: L/N/PE.  
propylene glycol basis are to be used.  
If a more powerful brine pump is required than the  
one integrated, a motor contactor and an appropriate  
motor protecting switch need to be installed. The  
contactor must be connected to the terminals of the  
internal brine pump (controller terminals J12/N03  
and X1-N). The power supply of the larger pump  
must be provided by the mains supply.  
The heat source system has to be vented and leak-  
tested.  
CAUTION!  
The brine solution must contain at  
least 25 % of an antifreeze and corrosion protection  
agent on a monoethylene glycol or propylene glycol  
basis.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMISSIONING  
CARE/CLEANING  
Close all of the heating circuits that may also be  
closed during operation (depending on the type  
of heat pump usage) so that the least favourable  
operating state - with respect to the water flow  
COMMISSIONING  
8
8.1 General  
rate - is achieved. Normally, these are the heating  
circuits of the rooms located on the south and  
west sides of buildings. At least one heating circuit  
To ensure proper commissioning it should be  
carried out by an after-sales service authorised by  
the manufacturer. Only then can an extended  
warranty period of 3 years in total be granted (cf.  
Warranty service).  
must remain open (e.g. bathroom).  
The overflow valve is to be opened to such an  
extent that based on the current heat source tem-  
perature the maximum temperature difference  
between heating supply and return flow tem-  
perature is obtained, as indicated in the table  
below. The temperature difference should be  
measured as closely to the heat pump as  
possible. In mono-energetic systems, the electric  
8.2 Preparatory Steps  
Prior to commissioning, the following items need to  
heating element is to be deactivated.  
be checked:  
Heat source temperature max. difference between heating  
-
-
-
-
-
All connections of the heat pump must have been  
made as described in Chapter 7.  
from  
-5 °C  
1 °C  
to  
0 °C  
5 °C  
9 °C  
14 °C  
20 °C  
25 °C  
supply and return temperature  
10 K  
11 K  
12 K  
13 K  
14 K  
15 K  
6 °C  
The heat source system and the heating circuit  
10 °C  
15 °C  
21 °C  
must be filled and tested.  
Strainer and vent must be fitted in the brine inlet  
of the heat pump.  
Any malfunctions occurring during operation are  
indicated on the display of the heat pump controller  
and can be corrected as described in the operating  
manual of the heat pump controller.  
All valves that could impair the proper water flow  
must be open in the brine and heating circuits.  
The heat pump controller must be adapted to the  
heating installation in accordance with the  
instructions contained in its operating manual.  
CARE/CLEANING  
99.1 Care  
-
-
Proper condensate drainage must be ensured.  
Drainage of the liquid emerging from the brine  
and heating water overflow valves must be  
ensured.  
The heat pump is designed for maintenance-free  
operation. To prevent operating malfunctions caused  
by dirt deposits in the heat exchangers, care must be  
taken that no contamination whatsoever can enter the  
heat source and heating systems. In the event that  
operating malfunctions due to contamination occur  
nevertheless, the system should be cleaned as  
described below.  
8.3 Commissioning Procedure  
The start-up of the heat pump is effected via the heat  
pump controller.  
9.2 Cleaning of Heating Side  
Commissioning of the heat pump  
CAUTION!  
must be carried out in accordance with the  
The ingress of oxygen into the heating water circuit  
may result in the formation of oxidation products (rust).  
It is therefore important - in particular with respect to  
the piping of the underfloor heating systems - that  
the installation is executed in a diffusion-proof manner.  
installation and operating manual of the heat  
pump controller.  
The delivery rate of the circulating pump must be  
adapted to the heating system.  
Also residues of lubricating and sealing agents may  
The setting of the overflow valve must be adapted to  
the requirements of the heating system. An incorrect  
setting may result in various error symptoms and an  
increased electric power consumption. To correctly  
set the overflow valve, the following procedure is  
recommended:  
contaminate the heating water.  
In the case of severe contamination leading to a  
reduction in the performance of the condenser in the  
heat pump, the system must be cleaned by a heating  
technician.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
CARE/CLEANING  
MALFUNCTIONS/TROUBLESHOOTING  
DECOMMISSIONING  
According to current knowledge, we recommend  
cleaning with a 5% phosphoric acid solution or, in  
the case that cleaning needs to be performed more  
MALFUNCTIONS/  
TROUBLESHOOTING  
10  
frequently, with a 5% formic acid solution.  
In either case, the cleaning fluid should be at room  
temperature. It is recommended that the heat  
exchanger be cleaned in the direction opposite to  
This heat pump is a quality product and is designed  
for trouble-free operation. In the event that a  
malfunction occurs nevertheless, you will be able to  
correct the problem yourself in most of the cases.  
Simply consult the Malfunctions and Trouble-  
shooting table contained in the operating manual of  
the heat pump controller.  
the normal flow direction.  
To prevent acidic cleaning agents from entering  
the circuit of the heating installation we recom-  
mend that the flushing device be fitted directly to  
the supply and return lines of the condenser. To  
prevent any damage caused by cleaning agent  
residues that may be present in the system it is  
important that the system be thoroughly flushed  
Additional malfunctions can be interrogated at the  
heat pump controller.  
using appropriate neutralising agents.  
If you cannot correct the malfunction yourself, please  
contact the after-sales service agent in charge (see  
Warranty Certificate).  
The acids must be used with great care, all rele-  
vant regulations of the employers' liability  
insurance associations must be adhered to.  
If in doubt, contact the manufacturer of the chemicals!  
CAUTION! All work on the heat pump may only  
be performed by an authorised and qualified  
after-sales service.  
CAUTION!  
Caution - Heating Technicians !  
Depending on the filling water quality and  
quantity, in particular in the case of mixed  
installations and plastic pipes, mineral deposits  
(rust sludge, lime) may form, impairing the pro-  
per functioning of the heating installation. A  
reason for this is the water hardness and  
oxygen dissolved in the filling waters as well  
as additional oxygen from the air, which may  
penetrate via valves, fittings and plastic pipes  
(oxygen diffusion). As a preventive measure it  
is recommended that a physical water conditio-  
ner such as ELYSATOR be used.  
DECOMMISSIONING  
11  
11.1 Shutdown in Summer  
Shutting down the heating system in summer is  
effected by switching the heat pump controller to the  
"Summer" operating mode.  
11.2 End-of-Life Decommissioning/  
Disposal  
9.3 Cleaning of Heat Source Side  
Before removing the heat pump, disconnect the  
machine from the power source and close all valves.  
Environment-relevant requirements regarding the  
recovery, recycling and disposal of service fuels and  
components in accordance with all relevant  
standards must be adhered to. Particular attention  
must hereby be paid to the proper disposal of  
refrigerants and refrigeration oils.  
The supplied strainer is to be install-  
CAUTION!  
ed in the heat source inlet of the heat pump in  
order to protect the evaporator against conta-  
mination.  
The filter screen of the strainer should be cleaned  
one day after commissioning, thereafter every week.  
If no more contamination can be noticed any more,  
the strainer filter can be removed in order to reduce  
pressure losses.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX  
APPENDIX  
12  
12.1  
DIMENSIONED DRAW-  
ING  
11  
12  
12.2 EQUIPMENT DATA  
12.3 SCHEMATICS  
12.3.1  
12.3.2  
12.3.3  
12.3.4  
Characteristics .. 7KS  
Characteristics .. 9KS  
Characteristics .. 11KS  
Characteristics .. 14KS  
13  
14  
15  
16  
12.4 WIRING DIAGRAMS  
12.4.1  
12.4.2  
12.4.3  
Control .. 7KS to .. 14KS  
Load .. 7KS to .. 14KS  
Terminal Diagram  
17  
18  
.. 7KS to .. 14KS  
19  
12.4.4  
12.5  
12.6  
Legend .. 7KS to .. 14KS  
20  
HYDR. BLOCK DIAGRAM 21  
EC DECLARATION OF  
CONFORMITY  
22  
23  
12.7  
WARRANTY CERTIFICATE/  
AFTER-SALES SERVICE  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                          
                          
                            
                            
                              
                              
                               
                               
                                  
                                  
                                    
                                     
                                      
                                      
                                        
                                        
                                          
                                          
                                           
                                           
                                            
                                            
                                              
                                              
                                                
                                                
APPENDIX: 12.1 DIMENSIONED DRAWING  
12. 1Maßbilder  
Dimensioned Drawing  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.2 EQUIPMENT DATA  
Equipment Data  
EQUIPMENT DATA for Brine-to-Water Heat Pumps for Heating  
1
TYPE AND COMMERCIAL DESCRIPTION  
MODEL  
..7KS  
..9KS  
..11KS  
..14KS  
2
2.1  
2.2  
2.3  
3
Type  
compact  
IP 20  
compact  
IP 20  
compact  
IP 20  
compact  
IP 20  
Enclosure type acc. to EN 60 529  
Installation site  
indoors  
indoors  
indoors  
indoors  
PERFORMANCE DATA  
Operating temperature limits:  
Heating water supply  
Brine (heat source)  
3.1  
°C  
°C  
max. 55  
max. 55  
max. 55  
max. 55  
-5 to +25  
-5 to +25  
-5 to +25  
-5 to +25  
monoethylene glycol  
monoethylene glycol monoethylene glycol monoethylene glycol  
Antifreeze agent  
Minimum brine concentration (-13°C freezing temperature)  
Heating water temperature difference at B0 / W35  
25%  
9,9  
25%  
10,5  
25%  
10,1  
25%  
9,6  
3.2  
3.3  
K
Heating capacity / coeff.of perform.  
at B-5 / W55 1)  
at B0 / W50 1)  
at B0 / W35 1)  
kW / ---  
kW / ---  
kW / ---  
dB(A)  
m³/h / Pa  
Pa  
5,6 / 2,2  
6,7 / 2,9  
6,9 / 4,3  
51  
7,7 / 2,3  
9,0 / 3,1  
9,2 / 4,4  
51  
9,4 / 2,4  
11,3 / 3,0  
11,8 / 4,4  
51  
12,5 / 2,6  
14,2 / 3,4  
14,5 / 4,5  
51  
3.4  
3.5  
3.6  
3.7  
3.8  
3.9  
4
Sound power level  
Heating water flow rate at internal pressure difference  
Free presssure, heating circulating pump (stage 3)  
Brine flow rate at internal pressure difference (heat source)  
Free pressure, brine pump (stage 3)  
0,6 / 2500  
47500  
0,75 / 4500  
43500  
1,0 / 3500  
65500  
1,3 / 3500  
64500  
m³/h / Pa  
Pa  
1,7 / 10000  
55000  
2,3 / 16000  
44000  
3,0 / 13000  
40000  
3,5 / 13000  
34000  
Refrigerant; total charge weight  
type / kg  
R407C / 1,5  
R407C / 1,8  
R407C / 2,0  
R407C / 2,3  
DIMENSIONS, CONNECTIONS AND WEIGHT  
Equipment dimensions without connections 4)  
Equipment connections for heating system  
Equipment connections for heat source  
Weight of transport unit(s) incl. packaging  
ELECTRICAL CONNECTION  
4.1  
4.2  
4.3  
4.4  
5
H x W x L mm  
inches  
1110 × 652 × 653  
R 1¼" ext.  
R 1¼" ext.  
179  
1110 × 652 × 653  
R 1¼" ext.  
R 1¼" ext.  
180  
1110 × 652 × 653  
R 1¼" ext.  
R 1¼" ext.  
191  
1110 × 652 × 653  
R 1¼" ext.  
R 1¼" ext.  
203  
inches  
kg  
5.1  
5.2  
5.3  
5.4  
6
Nominal voltage; fusing  
V / A  
kW  
400 / 16  
400 / 16  
2,07  
15  
400 / 16  
2,66  
26  
400 / 16  
3,22  
26  
Nominal power consumption 1) B0 W35  
Starting current with soft starter  
1,6  
A
30 (no soft starter)  
A / ---  
2,89  
3)  
3,77  
3)  
4,84  
3)  
5,81  
3)  
Nominal current B0 W35 / cosϕ  
COMPLIES WITH EUROPEAN SAFETY REGULATIONS  
OTHER DESIGN CHARACTERISTICS  
Water inside equipment protected against freezing 2)  
Performance settings  
7
7.1  
7.2  
7.3  
yes  
yes  
yes  
yes  
1
1
1
1
Controller internal / external  
internal  
internal  
internal  
internal  
These data characterize the size and performance capability of the system. For economic and energetic reasons, additional  
factors such as balance point and control need to be taken into consideration. Abbreviations have the following meaning, e.g. B10 /  
W55: heat source temperature 10 °C and heating water supply temperature 55 °C.  
1)  
2)  
3)  
4)  
The heating circulating pump and the controller of the heat pump must be ready for operation at all times.  
s. EC Declaration of Conformity  
Please keep in mind that more space is required for pipe connection, operation and maintenanc.  
Subject to technical modifications  
Issued: 23.04.2004  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.3 SCHEMATICS  
12.3.1 Characteristics .. 7KS  
Water outlet temperature in [°C]  
Heating capacity in [kW]  
12  
35  
50  
Conditions:  
10  
8
Heating water flow rate  
Brine flow rate  
0,6 m³/h  
1,7 m³/h  
6
4
2
0
-10  
-5  
0
5
10  
15  
20  
25  
30  
Brine inlet temperature in [°C]  
Power consumption (incl. power input to pump)  
Pressure loss in [Pa]  
40000  
35000  
30000  
25000  
20000  
15000  
10000  
5000  
2,5  
50  
35  
Evaporator  
2
1,5  
1
0,5  
0
0
0
1
2
3
4
-10  
-5  
0
5
10  
15  
20  
25  
30  
Brine inlet temperature in [°C]  
Brine flow rate in [m³/h]  
Coefficient of performance (incl. power input to pump)  
Pressure loss in [Pa]  
Condenser  
25000  
20000  
15000  
10000  
5000  
0
8
7
6
5
4
3
2
1
0
35  
50  
0
0,5  
1
1,5  
2
-10  
-5  
0
5
10  
15  
20  
25  
30  
[m³/h]  
Heating water flow rate in  
Brine inlet temperature in [°C]  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.3 SCHEMATICS  
12.3.2 Characteristics .. 9KS  
Water outlet temperature in [°C]  
Heating capacity in [kW]  
18  
16  
14  
12  
10  
8
Conditions:  
Heating water flow rate 0,75 m³/h  
Brine flow rate  
35  
50  
2,3 m³/h  
6
4
2
0
-10  
-5  
0
5
10  
15  
20  
25  
30  
Brine inlet temperature in [°C]  
Power consumption (incl. power input to pump)  
Pressure loss in [Pa]  
50000  
40000  
30000  
20000  
10000  
0
3,5  
3
2,5  
2
Evaporator  
50  
35  
1,5  
1
0,5  
0
0
1
2
3
4
-10  
-5  
0
5
10  
15  
20  
25  
30  
Brine inlet temperature in [°C]  
[m³/h]  
Brine flow rate in  
Coefficient of performance (incl. power input to pump)  
Pressure loss in [Pa]  
Condenser  
25000  
20000  
15000  
10000  
5000  
0
8
7
6
5
4
3
2
1
0
35  
50  
0
0,5  
1
1,5  
2
-10  
-5  
0
5
10  
15  
20  
25  
30  
Heating water flow rate in [m³/h]  
Brine inlet temperature in [°C]  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.3 SCHEMATICS  
12.3.3 Characteristics .. 11KS  
Water outlet temperature in [°C]  
Heating capacity in [kW]  
20  
35  
50  
18  
Conditions:  
Heating water flow rate  
Brine flow rate  
1,0 m³/h  
3,0 m³/h  
16  
14  
12  
10  
8
6
4
2
0
-10  
-5  
0
5
10  
15  
20  
25  
30  
Brine inlet temperature in [°C]  
Power consumption (incl. power input to pump)  
Pressure loss in [Pa]  
Evaporator  
40000  
30000  
20000  
10000  
0
4
50  
35  
3,5  
3
2,5  
2
1,5  
1
0,5  
0
0
1
2
3
4
5
-10  
-5  
0
5
10  
15  
20  
25  
30  
Brine inlet temperature in [°C]  
[m³/h]  
Brine flow rate in  
Coefficient of performance (incl. power input to pump)  
Pressure loss in [Pa]  
Condenser  
16000  
14000  
12000  
10000  
8000  
6000  
4000  
2000  
0
8
7
6
5
4
3
2
1
0
35  
50  
0
0,5  
1
1,5  
2
-10  
-5  
0
5
10  
15  
20  
25  
30  
[m³/h]  
Heating water flow rate in  
Brine inlet temperature in [°C]  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.3 SCHEMATICS  
12.3.4 Characteristics .. 14KS  
Water outlet temperature in [°C]  
Heating capacity in [kW]  
25  
35  
50  
20  
15  
10  
5
Conditions:  
Heating water flow rate  
Brine flow rate  
1,3 m³/h  
3,5 m³/h  
0
-10  
-5  
0
5
10  
15  
20  
25  
30  
Brine inlet temperature in [°C]  
Power consumption (incl. power input to pump)  
Pressure loss in [Pa]  
Evaporator  
40000  
30000  
20000  
10000  
0
5
4
3
2
1
0
50  
35  
0
1
2
3
4
5
-10  
-5  
0
5
10  
15  
20  
25  
30  
Brine inlet temperature in [°C]  
[m³/h]  
Brine flow rate in  
Coefficient of performance (incl. power input to pump)  
Pressure loss in [Pa]  
Condenser  
14000  
12000  
10000  
8000  
6000  
4000  
2000  
0
8
7
6
5
4
3
2
1
0
35  
50  
0
0,5  
1
1,5  
2
2,5  
[m³/h]  
-10  
-5  
0
5
10  
15  
20  
25  
30  
Heating water flow rate in  
Brine inlet temperature in [°C]  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.4 WIRING DIAGRAMS  
12.4.1 Control .. 7KS to .. 14KS  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.4 WIRING DIAGRAMS  
12.4.2 Load .. 7KS to .. 14KS  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.4 WIRING DIAGRAMS  
12.4.3 Terminal Diagram .. 7KS to .. 14KS  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.4 WIRING DIAGRAMS  
12.4.4 Legend .. 7KS to .. 14KS  
A1  
Wire jumper, must be inserted if no utility company disable contactor is required  
A2  
Wire jumper, must be removed if 2nd disable input is used  
B3*  
B4*  
Thermostat, hot water  
Thermostat, swimming pool water  
E9*  
Electric immersion heater, hot water  
E10*  
Back-up heater (boiler or electric heating element)  
F2  
F3  
F4  
F5  
Load fuse for N1 relay outputs across J12 and J13  
Load fuse for N1 relay outputs across J15 to J18  
Pressostat, high pressure  
4,0ATr  
4,0ATr  
Pressostat, low pressure  
H5*  
Lamp, remote fault indicator  
Terminal connectors at N1  
J1...J18  
K1  
Contactor, compressor  
K11*  
K12*  
K20*  
K21*  
K22*  
K23*  
Electron. relay for remote fault indicator (on relay module)  
Electron. relay for swimming pool water circulating pump (on relay module)  
Contactor, back-up heater  
Contactor, electr. immersion heater, hot water  
Utility company disable contactor  
SPR auxiliary relay  
M1  
Compressor  
M11  
Primary circulating pump (brine)  
Heating circulating pump  
Heating circulating pump, heating circuit 2  
Suppl. circulating pump  
M13  
M15*  
M16*  
M18*  
M19*  
M21*  
M22*  
Hot water circulating pump  
Swimming pool water circulating pump  
Mixer, primary circuit  
Mixer, heating circuit 2  
N1  
Heat pump controller  
Soft starter  
N7  
N10*  
Remote control station  
Relay module  
N11*  
R1  
R2  
R3  
R5  
R6  
R7  
External sensor  
Return sensor  
Hot water sensor (as an alternative to the hot water thermostat)  
Sensor for heating circuit 2  
Freeze protection sensor  
Coding resistor 8.2 kOhm  
T1  
Safety isolating transformer 230/24 VAC-28VA  
X1  
Terminal strip, mains-load 3L/PE-400 VAC-50 Hz/  
Mains-control L/N/PE-230 VAC-50Hz / fuses/N- and PE-terminal block  
Terminal strip 24 VAC-terminal block  
X2  
X3  
Terminal strip GND terminal block for analog inputs at J2 and J6  
Abbreviations:  
EVS  
Utility company disable input  
SPR  
Supplementary disable input, configurable  
Mixer OPEN  
MA*  
MZ  
Mixer CLOSED  
* Components to be supplied by the customer  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAM  
Hydraulic Block Diagram  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 12.6 EC DECLARATION OF CONFORMITY  
EC Declaration of Conformity  
Declaration of Conformity  
The undersigned  
Glen Dimplex Deutschland GmbH  
Division Dimplex  
Am Goldenen Feld 18  
D-95326 Kulmbach  
hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed  
on the market by us, conform to the relevant requirements of the applicable EC directives.  
This declaration becomes invalidated if any modifications are made to the product(s) without our  
prior authorization.  
Designation of the product(s):  
EC Directives:  
Brine-to-water heat pumps  
for indoor installation,  
containing R407C  
EC Low Voltage Directive  
(73/23/EEC)  
EC EMC Directive  
(89/336/EEC)  
Pressure Equipment Directive  
(97/23/EEC)  
Type(s):  
SI 7KS  
Harmonized EN Standards:  
SI 9KS  
SI 11KS  
SI 14KS  
Requirements of category II  
Order No.:  
National Standard/Directives:  
341 860  
341 870  
341 880  
341 890  
Kulmbach, 25.04.2005  
CE09W09G.doc  
General Manager  
Technical Director  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glen Dimplex Deutschland GmbH  
Division Dimplex  
Subject to technical modifications  
Fax +49 92 21/709-589  
Am Goldenen Feld 18  
D-95326 Kulmbach  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Cisco Systems Network Hardware WAP561AK9 User Manual
Conair Styling Iron CS3CS User Manual
Contec Computer Hardware SPI 8450 LLVA User Manual
Cooper Lighting Indoor Furnishings BA SERIES User Manual
Cornelius Beverage Dispenser CCM1448 User Manual
Cuisinart Coffeemaker DCC1200E User Manual
Delta Electronics Power Supply PMC 24V050W1AA User Manual
Field Controls Range Oil Venting Systems User Manual
Gefen Switch 4x4 DVI Matrix User Manual
GE Monogram Refrigerator ZDBT210 User Manual