THE HOTTEST MACHINES ON ICET
I" Series
Ice Cube Machine
SERVICE MANUAL & MAINTENANCE GUIDE
(Includes Installation Instructions)
166240004
12/1/94
Revised: 3/4/96
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS (cont’d)
Page
26
26
27
27
27
28
28
28
28
28
28
29
29
29
31
31
51
FLOODING TXV - PRODUCT SYMPTOMS . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER REGULATING VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE STEM VALVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MOISTURE CONTAMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR CONTACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR & STARTING COMPONENT CHECK-OUT PROCEDURE . . . .
RELAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
POTENTIAL – . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CURRENT – . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAPACITORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LEAK DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYSTEM EVACUATION & RECHARGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SELF-CONTAINED PRODUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HIGH PRESSURE SAFETY SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR RUN-ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUBER NOT OPERATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUBER NOT OPERATING, INDICATOR LIGHTS “OFF”, NO POWER
TO CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
51
51
51
CUBER NOT OPERATING,
INDICATOR LIGHTS “OFF”, POWER TO THE CIRCUIT BOARD . . . . . . . . . . . .
COMPRESSOR DOES NOT RUN, CIRCUIT BOARD
INDICATOR LIGHTS “ON” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR RUNS BUT DOES NOT COOL, CIRCUIT
BOARD INDICATOR LIGHTS “ON” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
52
52
52
52
52
52
53
53
53
54
54
71
73
77
78
CUBER REMAINS IN THE FREEZE CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUBER REMAINS IN THE HARVEST CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SUCTION LINE THERMISTOR OPEN (STARTS IN HARVEST) . . . . . . . . . . . . . .
PROXIMITY SWITCH LIGHT “OUT” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROXIMITY SWITCH LIGHT “ON” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LONG FREEZE CYCLE WATER FLOW ASSOCIATED . . . . . . . . . . . . . . . . . . . . .
LONG FREEZE CYCLE GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LONG HARVEST CYCLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ICE WEIGHT LIGHT AT TOP OF PLATE AND HEAVY AT THE BOTTOM . . . . .
SOFT WHITE ICE OR WATER PUMP NOT PUMPING . . . . . . . . . . . . . . . . . . . . .
INSTALLATION INSTRUCTIONS REMOTE CONDENSERS . . . . . . . . . . . . . . . .
REMOTE CONDENSER LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HEAD PRESSURE CONTROL [HEADMASTER] . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE SYSTEM EVACUATION/RE-CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF FIGURES
LIST OF TABLES
ii
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
MODEL AND SERIAL LOCATION
“I” SERIES CUBER
Condenser Discharge Air
Deflector (as required)*
Bin Adapter (as required)*
Model/Serial
Number Location
*Bin adapters and condenser discharge air deflector may be equipped depending on your location or the size of
the storage bin.
Record the model number and the serial number of your ice equipment. These numbers are required when re-
questing information from your local dealer/distributor/service company.
Model Number –
Serial Number –
Date Installed –
Purchased From -
SERIAL NUMBER EXPLANATION
AA 95 01 BC 0001
Number – 4 digit number, 0001 – 9999
Product Code – 2 digit alpha
Month – 2 digit numerical month designation
Year – 2 digit year designation
Engineering Change Level – 1 or 2 alpha designation
12/1/94
Rev 3/4/96
1
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
REMOTE CONDENSER SPECIFICATION
MODEL
CR800
208/230
1
CR1200
208/230
1
CR1400
208/230
1
Volts
Phase
Hertz
60
60
60
Amps
1.0
1.0
1.0
Output, HP
1/6
1/6
1/6
Max. fuse size, Amps (HVAC circuit breaker
required)
20
20
20
ICE CUBER SPECIFICATION
IAC322/330
IWC322/330
IWCS227
MODEL
IAC522/530
IWC522/530
IAC227
UNIT
Volts
115
115
115
115
Phase
Hertz
1
60
1
60
1
60
1
60
No. Wires
MIN. CIRCUIT
Amps
2+ground
2+ground
2+ground
2+ground
20
20
20
20
20
20
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
20
20
R404A (HP62)
R404A (HP62)
R404A (HP62)
R404A (HP 62)
Weight (oz)
Weight (g)
COMPRESSOR
Volts
17
15
26
23
482
425
737
652
115
1
115
1
115
1
115
1
Phase
Hertz
60
60
60
60
LRA
51
51
59
59
RLA
11.5
11.5
11.6
11.6
CONDENSER FAN MOTOR (Air-Cooled Systems only) of
AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts
115
1
115
1
115
1
115
1
Phase
Hertz
60
1.7
50
60
0.38
6
60
60
0.38
6
Amps Running
Watts
1.75
50
WATER PUMP
Volts
115
1
115
1
115
1
115
1
Phase
Hertz
60
60
60
60
Amps Running
HP
0.88
1/40
0.88
1/40
0.76
1/40
0.88
1/40
12/1/94
Rev 3/4/96
166240004
2
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS – 60 HZ
ICE CUBER SPECIFICATION
IAC522E60
IWC522E60
IWC522E60L
IWC530E60
IWC530E60L
IAC322E60
IAC330E60
IACS227E60
IWC322E60
IWC330E60
IWCS227E60
IAC522E60L
IAC530E60
IAC530E60L
MODEL
UNIT
Volts
230
230
230
230
Phase
Hertz
1
60
1
60
1
60
1
60
No. Wires
MIN. CIRCUIT
Amps
2+ground
2+ground
2+ground
2+ground
15
15
15
15
15
15
15
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
15
R404A(HP62)
R404A(HP62)
R404A(HP62)
R404A(HP 62)
Weight (oz)
Weight (g)
COMPRESSOR
Volts
17
15
26
23
482
425
737
652
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
60
45
9.2
60
45
9.2
LRA
24.1
5.7
24.1
5.7
RLA
CONDENSER FAN MOTOR (Air-Cooled Systems only) or
AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
0.36
6
60
60
.036
6
Amps Running
Watts
0.89
50
0.89
50
WATER PUMP
Volts
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
60
60
Amps Running
HP
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS – 60 HZ
ICE CUBER SPECIFICATION
MODEL
IAC630
IWC630
IRC630
IAC830
IWC830
IRC830
UNIT
Volts
230
230
230
230
230
230
Phase
Hertz
1
60
1
60
1
60
1
60
1
60
1
60
No. Wires
MIN. CIRCUIT
Amps
2+ground
2+ground
2+ground
2+ground
2+ground
2+ground
20
20
20
20
20
20
20
20
20
20
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
20
20
R404A(HP62)
R404A(HP62)
R404A(HP62)
170
R404A(HP62)
R404A(HP62)
R404A(HP62)
170
Weight (oz)
Weight (g)
COMPRESSOR
Volts
43
35
55
33
1219
992
4820
1559
936
4820
230
1
230
1
230
1
230
1
230
1
230
1
Phase
Hertz
60
69
8.8
60
69
8.8
60
69
8.8
60
60
60
LRA
61
61
61
RLA
12.5
12.5
12.5
CONDENSER FAN MOTOR (Air-Cooled Systems only) or
AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts
230
1
230
1
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
0.36
6
60
0.36
6
60
60
0.36
6
60
0.36
6
Amps Running
Watts
1.09
75
1.09
75
WATER PUMP
Volts
230
1
230
1
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
60
60
60
60
Amps Running
HP
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS – 60 HZ
ICE CUBER SPECIFICATION
IAC1030
IWC1030
IRC1030
IRC1030L
MODEL
IAC1030L
IWC1030L
UNIT
Volts
230
230
230
Phase
Hertz
1
60
1
60
1
60
No. Wires
MIN. CIRCUIT
Amps
2+Ground
2+Ground
2+Ground
20
20
20
20
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
20
20
R404a(HP62)
R404a(HP62)
R404a(HP62)
210
Weight (oz)
Weight (g)
COMPRESSOR
Volts
60
42
1701
1191
5954
230
1
230
1
230
1
Phase
Hertz
60
60
60
LRA
82
82
82
RLA
13.0
13.0
13.0
CONDENSER FAN MOTOR (Air-Cooled Systems only) or
AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts
230
1
230
1
230
1
Phase
Hertz
60
60
60
Amps Running
Watts
0.89ꢀ2
50Wꢀ2
0.36
6W
0.36
6W
WATER PUMP
Volts
230
1
230
1
230
1
Phase
Hertz
60
60
60
Amps Running
HP
0.5
1/30
0.5
1/30
0.5
1/30
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS – 60 HZ
ICE CUBER SPECIFICATION
MODEL
IAC1230
IWC1230
IRC1230
IAC1448
IWC1448
IRC1448
UNIT
Volts
230
230
230
230
230
230
Phase
Hertz
1
60
1
60
1
60
1
60
1
60
1
60
No. Wires
MIN. CIRCUIT
Amps
2+ground
2+ground
2+ground
2+ground
2+ground
2+ground
20
20
20
20
25
25
25
25
25
25
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
20
20
R404A(HP62)
R404A(HP62)
R404A(HP62)
210
R404A(HP 62)
R404A(HP 62)
R404A(HP 62)
250
Weight (oz)
Weight (g)
COMPRESSOR
Volts
49
45
92
44
1389
1276
5954
2608
1247
7088
230
1
230
1
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
60
60
60
60
LRA
96
96
96
95.6
23.9
95.6
23.9
95.6
23.9
RLA
13.5
13.5
13.5
CONDENSER FAN MOTOR (Air-Cooled Systems only) or
AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts
230
1
230
1
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
60
60
60
60
Amps Running
Watts
0.89 X 2
50 W X 2
0.36
6 W
0.36
6 W
0.4
0.36
6 W
0.36
6 W
1/15 HP
WATER PUMP
Volts
230
1
230
1
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
60
60
60
60
Amps Running
HP
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS – 50 HZ
IAC522E50
IWC522E50
IWC522E50L
IWC530E50
IWC530E50L
IAC322E50
IAC330E50
IACS277E50
IWC322E50
IWC330E50
IWCS227E50
IAC522E50L
IAC530E50
IAC530E50L
MODEL
UNIT
Volts
220
220
220
220
Phase
Hertz
1
50
1
50
1
50
1
50
No. Wires
MIN. CIRCUIT
Amps
2+ground
2+ground
2+ground
2+ground
15
15
15
15
15
15
15
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
15
R404A(HP62)
R404A(HP62)
R404A(HP62)
R404A(HP 62)
Weight (oz)
Weight (g)
COMPRESSOR
Volts
17
15
26
23
482
425
737
652
220
1
220
1
220
1
220
1
Phase
Hertz
50
26
5.3
50
26
5.3
50
33
8.2
50
33
8.2
LRA
RLA
CONDENSER FAN MOTOR (Air-Cooled Systems only) or
AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts
220
1
220
1
220
1
220
1
Phase
Hertz
50
50
0.3
6
50
50
0.3
6
Amps Running
Watts
0.75
50
0.75
50
WATER PUMP
Volts
220
1
220
1
220
1
220
1
Phase
Hertz
50
50
50
50
Amps Running
HP
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS – 50 HZ
IAC630E50
IAC630E50L
IWC630E50
IWC630E50L
IRC630E50
IRC63050L
IAC830E50
IAC830E50L
IWC830E50
IWC830E50L
IRC830E50
IRC830E50L
MODEL
UNIT
Volts
220
220
220
220
220
220
Phase
Hertz
1
50
1
50
1
50
1
50
1
50
1
50
No. Wires
MIN. CIRCUIT
Amps
2+ground
2+ground
2+ground
2+ground
2+ground
2+ground
20
20
20
20
20
20
20
20
20
20
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
20
20
R404A(HP62)
R404A(HP62)
R404A(HP62)
170
R404A(HP 62)
R404A(HP 62)
R404A(HP 62)
170
Weight (oz)
Weight (g)
COMPRESSOR
Volts
43
35
55
33
1219
992
4820
1559
936
4820
220
1
220
1
220
1
220
1
220
1
220
1
Phase
Hertz
50
53
8
50
53
8
50
53
8
50
58
12
50
58
12
50
58
12
LRA
RLA
CONDENSER FAN MOTOR (Air-Cooled Systems only) or
AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts
220
1
220
1
220
1
220
1
220
1
220
1
Phase
Hertz
50
50
0.3
6
50
0.3
6
50
50
0.3
6
50
0.3
6
Amps Running
Watts
1.06
75
1.06
75
WATER PUMP
Volts
220
1
220
1
220
1
220
1
220
1
220
1
Phase
Hertz
50
50
50
50
50
50
Amps Running
HP
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS – 50 HZ
IAC1030E50
IAC1030E50L
IWC1030E50
IWC1030E50L
IRC1030E50
IRC103050L
IAC1230E50
IAC1230E50L
IWC1230E50
IWC1230E50L
IRC1230E50
IRC1230E50L
MODEL
UNIT
Volts
220
220
220
220
220
220
Phase
Hertz
1
50
1
50
1
50
1
50
1
50
1
50
No. Wires
MIN. CIRCUIT
Amps
2+ground
2+ground
2+ground
2+ground
2+ground
2+ground
20
20
20
20
25
25
25
25
25
25
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
20
20
R404A(HP62)
R404A(HP62)
R404A(HP62)
210
R404A(HP 62)
R404A(HP 62)
R404A(HP 62)
250
Weight (oz)
Weight (g)
COMPRESSOR
Volts
49
45
92
44
1389
1276
5954
2608
1247
7088
220
1
220
1
220
1
220
1
220
1
220
1
Phase
Hertz
50
50
50
50
50
50
LRA
64
64
64
75.9
13
75.9
13
75.9
13
RLA
12.5
12.5
12.5
CONDENSER FAN MOTOR (Air-Cooled Systems only) or
AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts
220
1
220
1
220
1
220
1
220
1
220
1
Phase
Hertz
50
50
50
50
50
50
Amps Running
Watts
0.75ꢀ2
0.50Wꢀ2
0.3
6W
0.3
6W
0.75ꢀ2
0.75Wꢀ2
0.3
6W
0.3
6W
WATER PUMP
Volts
220
1
220
1
220
1
220
1
220
1
220
1
Phase
Hertz
50
50
50
50
50
50
Amps Running
HP
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS – 50 HZ, REMOTE CONDENSER
MODEL
CR800E50
CR1200E50
CR1400E50
UNIT
Volts
220
1
50
1.1
1/6
20
220
1
50
1.1
1/6
20
220
1
50
1.1
1/6
20
Phase
Hertz
Amps
Output H.P.
MAX fuse size, Amps
(HVAC circuit breaker required
Download from Www.Somanuals.com. All Manuals Search And Download.
GENERAL
FREIGHT DAMAGE CLAIMS PROCEDURE
The deliverer of your equipment (freight company, distributor or dealer) is responsible for loss or damage of your
shipment. All claims must be filed with the deliverer of your equipment. Please follow the steps below to deter-
mine if your shipment is satisfactory or if a claim must be filed:
1. Check the number of products delivered against the number of products listed on the delivery receipt.
Should the totals not match, have the driver note all errors on both copies and both you and the driver sign
and date said notation.
2. Inspect all cartons for visible damage. Open and inspect as required before the driver leaves and have him
or her note any damage on the receipts. All damaged claims must be inspected within 15 days of delivery.
Notify your carrier immediately if concealed damage is found after delivery.
3. Should concealed damage be found when product is unpacked, retain the packing material and the product
and request an inspection from the deliverer.
4. All claims for loss or damage should be filed at once. Delays in filing will reduce the chance of achieving a
satisfactory resolution to the claim.
12/1/94
Rev 3/4/96
11
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
Installation and start-up of the equipment should be performed by the distributor or the dealer’s professional
staff.
LOCATION OF EQUIPMENT
For maximum performance the location should be away from heat sources such as ovens, direct sunlight, hot
air discharge, etc.
To reduce cost of maintenance and loss of efficiency, avoid placing air-cooled equipment in areas where grease,
flour and other airborne contaminants are present. Allow a minimum of 6I (15.24 cm) clearance on all sides and
top for proper air circulation. Restricted air circulation will affect the efficiency and required maintenance of the
product.
IMPORTANT: Never operate your equipment in room temperature below 50_F (10_) or above 100_F
(38_C). Should the location of your product ever be exposed to freezing temperatures, it must be shut
down and winterized.
EQUIPMENT SET-UP
The following steps refer to the set-up of the ice bin and the cuber:
1. Remove the bin from its carton, place it on its back and install the legs into the bottom of the bin. Bins must
be installed on legs or sealed to the floor with RTV-732 sealant.
2. Set the bin up on its legs. Place the bin in its final location and level it with the adjustable feet in the legs.
3. Unpack the cuber from its carton, and set in place on the bin and adjust as required. Leave all panels on
the cuber until it is set in place on the dispenser or bin.
4. Remove all internal packing from the cuber.
THREAD LEVELING
LEG INTO BASE
NOTE: Bin adapter andcondenser air baffles may be required in certain installations.
DISPENSER INSTALLATION
The proper cuber/dispenser installation package should be ordered. This package will include gasket material
and hold-down bracket.
12/1/94
Rev 3/4/96
166240004
12
Download from Www.Somanuals.com. All Manuals Search And Download.
IACS/IWCS 227
C
15.25
A
A ELECTRICAL CORD ATTACHED (20
B 3/4 DRAIN – TUBING SIZE 5/8 I.D.
C 3/8 WATER INLET (SEA MALE FLAR
D 3/4 BIN DRAIN – STD PIPE SAE
27.00
31.38
21.38
B
7.06
D
2.25
8.75
1.00(3)
33.00
IACS 227
REAR VIEW
25.06
C
A
A ELECTRICAL CORD ATTACHED (20
B 3/4 DRAIN – TUBING SIZE 5/8 I.D.
C 3/8 RESERVOIR WATER INLET (SAE
D 3/4 BIN DRAIN – STD PIPE SAE
31.38
21.38
6.0 MIN
E 5/8 CONDENSER WATER OUTLET (
F 5/8 CONDENSER WATER INLET (MA
28.00
B
E
F
7.06
D
2.25
2.06
8.75
1.00(5)
IWCS 227
REAR VIEW
INSTRUCTIONS FOR ATTACHING SUPPORT LEGS
1. LAY CABINET ON BACK OR SIDE USING BLANKET OR
PADDING TO AVOID MARRING.
2. REMOVE CRATE SKID FROM UNIT BOTTOM.
3. SCREW ADJUSTABLE LEGS INTO RECESSED THREAD
4. LEVEL UNIT USING FEET FOR ADJUSTMENT.
LEGS (4)
BLANKET
12/1/94
Rev 3/4/96
13
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Service
Line
Electrical Service
Line
Manual Disconnect
Switch
Manual Disconnect
Switch
Shut-Off
Valve
Shut-Off Valve
Water Filter
Water Filter
STRAIN RE-
LIEF
MUST BE
USED
Dump
Valve
Drain Tube
Shut-Off Valve
Condenser Water Inlet
Strain Relief
must be used
Dump Valve
Drain Tube
Condenser Water
Drain Tube
Floor
Drain
Floor
Drain
Bin Drain
Tube
Bin Drain
Tube
WATER-COOLED MODELS
AIR-COOLED MODELS
Note: Leave all panels on the cuber until it is in place on the bin.
PLUMBING CONNECTIONS
1. All plumbing lines and connections must conform to local and
national plumbing codes.
2. Line shut-off valves must be located in supply water lines for cuber and condenser if product is water-
cooled. Water supply to water-cooled condenser must include a stand-pipe to prevent “water
hammer”.
3. Should your local water supply quality require the installation of a water filter system, consult your local dis-
tributor or dealer for proper size required.
4. Water supply pressure must not be lower than 20 PSI (1.37 BAR), nor should it exceed 120 PSI (8.16
BAR).
NOTE: Water filters larger then 5 microns do not give proper protection. Water pressures above 80
PSI (5.44 BAR) will destroy the filter.
DRAIN LINES: Bin and cuber drain lines must never be connected together and must be vented.
NOTE: All HP-62 (R404A) ice machines have a voltage range of –5%, +10% from the serial palte rating.
ELECTRICAL
1. All wiring and connections must conform to national and local electrical codes.
2. Wire size and circuit protection must conform to specifications and cuber must be on a separate electrical
circuit.
3. Strain relief connectors must be used at the junctions box of the control box and the cuber.
4. Cuber must be grounded by the control box ground screw or other method for intentional safety grounding
that meets code requirements.
5. A manual disconnect in a convenient location to the cuber must be installed.
INSTALLATION CHECK POINTS
1. Has bin and cuber been leveled and sanitized?
2. Does electrical and plumbing meet code requirements?
3. Check correct operating water level in the water pan.
12/1/94
Rev 3/4/96
166240004
14
Download from Www.Somanuals.com. All Manuals Search And Download.
operating water level
Single Evaporator Units
3/8I
operating water level
Dual Evaporator Units
WATER PAN
RIGHT SIDE VIEW
4. If water-cooled, are inlet and drain connections to condenser correct to prevent “water hammer”?
5. Are drain lines separate and vented?
6. Is there 6I clearance on all sides and top for proper air circulation?
7. Does the water curtain move freely, and does the float valve shut off incoming water to the water pan?
START-UP AND CHECK OUT
1. Turn the Cuber’s power switch to the clean (pump only) position. The water pump only should be opera-
tional. Wipe the top extrusion briskly with a ScotchBrite pad. Check for an even, steady flow of water over
evaporator top extrusion and down over evaporator surface. Check that all ports of the water distribution
tube are open for even water discharge. The water pan should refill and the float should stop the incoming
water sup-
ply.
Power Switch
NOTE: On the IACS222/IWCS227 to service the float valve:
1. Compress the John Guess fitting remove the 1/4” tubing.
2. Remove the screws that hold the float bracket to the liner wall.
3. Carefully remove float strainer and bracket as one assembly.
4. Reverse procedure to reinstall.
Should service be required on the float valve or strainer, turn the water supply off, loosen the float,
hold down nut and remove the float and strainer as an assembly for ease of service.
2. Place the Cuber’s power switch in the ON position. After a 2-second delay the compressor will start. The
condenser fan will operate when the condenser sensor signals the circuit board its temperature is 100_F
(38_C). The water pump will operate when the evaporator cools to 25_F (–3.9_C). Depress the manual
harvest switch (on the circuit board). The fan motor will stop and the water dump valve will open. In 3 se-
conds the hot gas solenoid will open and 15 seconds after depressing the manual harvest switch, the water
pump and dump valve will close terminating the dump cycle.
3. Hold the water curtain open for a maximum of 30 seconds; the Cuber should shut down. Release the water
curtain(s). When the curtain(s) closes, there will be a 2-second delay, then the compressor will start and
the start-up process should begin for the next ice-making mode.
4. If all Cuber operation is as stated, allow product to operate and produce one slab of ice, then discard the
ice. Allow the Cuber to continue operation to fill the storage bin.
12/1/94
Rev 3/4/96
15
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER -OPERATOR
The installation is not complete until you are sure the owner-operator understands the cuber operation and his
or her responsibility of preventative maintenance.
Does the owner-operator know:
1. Location of electrical disconnect switch and water shut-off valves?
2. How to start and/or shut down the product, clean and sanitize it?
3. Bin full operation and reset operation of high pressure cutout (water-cooled and remote products only)?
4. How to clean the condenser and fan blade?
5. Whom to call for product information and/or service?
CLEANING PROCEDURES
Approved ice machine cleaners by brand names:
S Lime–A–Way
S Calgon Nickel Safe (green color only)
NOTE: All ice machine cleaners labeled safe for nickel ARE NOT the brand CALGON NICKEL SAFE.
CAUTION: Ice machine cleaners are acidic-based chemicals. Before beginning any
cleaning of the cuber, the ice in the storage bin or dispenser must be removed.
WARNING: When using any chemical, rubber gloves and eye protection should be worn.
PREP – CLEANING
Use full-strength ice machine cleaner on a coarse-surface cloth material (such as terry cloth) and wipe down the
inside wall of the evaporator area, the water pan, the water curtain and evaporator plastic extrusions. If the wa-
ter distributor tube has heavy scale build-up, remove and soak it in full-strength ice machine cleaner (or ex-
change the tube and clean the scaled tube at a later date).
Cleaning the Water System and Evaporator
1. Set the switch to Clean and allow any ice on the evaporator to release and melt away.
2. Remove all ice from the storage bin.
3. Remove the water curtain(s), pour 1/2 oz. of ice machine cleaner down the rear key-slot openings. The
cleaner will drain into the water pan.
4. Return the water curtain(s) to their proper operating positions.
5. Add 3 oz. for a single evaporator, or 5 oz. for a dual evaporator of “Calgon Nickel Safe” or “Lime-A-Way”
ice machine cleaner directly into the water pan. The float will balance with inlet water. Set switch to
CLEAN, circulate for a maximum of 15 minutes.
6. Depress and hold the dump switch to allow the cleaner to drain away.
7. Fill the water pan with clean fresh water, circulate for approximately 3 minutes. Depress and hold the
DUMP switch and allow the water to drain away. Repeat the procedure 3 times.
8. After third rinse cycle, place product power switch in ice position. Allow Cuber to produce one slab of ice –
DISCARD THE ICE.
9. When the clean cycle is complete, return cuber to normal operating mode.
NOTE: Please Take Note of the Following:
S Ice machines should only be cleaned when needed, not by a timed schedule of every 60 days, etc.
S Should your ice machine require cleaning more than twice a year, consult your distributor or dealer about
proper water treatment.
166240004
12/1/94
Rev 3/4/96
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Power Switch
SANITIZING PROCEDURES
NOTE: To be performed only after cleaning the ice machine:
1. Add 1/4 ounce (7.08 g) sodium hypochlorite solution (common liquid laundry bleach) to the water pan and
allow the pump to circulate the solution for 5 minutes. You may also use a commercial sanitizer such as
Calgon Ice Machine Sanitizer following the directions on the product label.
2. Turn the Cuber power switch off and depress and hold the dump switch to drain the water pan.
3. To sanitize the bin and other surface areas, use 1 ounce of liquid bleach per gallon of water and wipe all
areas with the solution. Or use a commercial sanitizer.
4. Place the Cuber power switch in the ice position. Discard the first batch of ice produced.
5. Cleaning and sanitizing are now complete. Cuber may be returned to normal service.
DUMP CYCLE
OPERATING WATER LEVEL
SINGLE EVAPORATOR UNITS
3/8I
OPERATING WATER LEVEL
DUAL EVAPORATOR UNITS
WATER PAN
RIGHT SIDE VIEW
1. With the proper water level in the water pan, start the water pump to circulate the water. Check that the
float will return water level to original setting and stop inlet water.
2. There is a flow washer in the inlet side of the float assembly that will control inlet water pressure from
20/120 PSI (3.4/8.16 Bars). This will prevent float flutter. In low water pressure conditions, 20 PSI (1.37
Bars) or less, the flow washer may have to be removed from the float assembly for proper volume.
FLOW CONTROL WASHER FLAT SIDE UP
3. Push the manual dump switch – allow dump action to drain the water pan. When you release the momen-
tary switch, the pump will stop and the float will return the water level back to its original setting and shut off
the water supply.
12/1/94
Rev 3/4/96
17
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
4. You have the option of selecting dump cycle intervals of:
S every cycle; (Standard setting from factory)
S every 3rd cycle;
S every 5th cycle;
S every 7th cycle.
Remember, the higher the mineral content in the water supply the more often it will be required to dump the wa-
ter and/or clean the product if proper water treatment is not used.
Water
Dump
Valve
DĆ15
DĆ13
YL
RH Evap.
Switch
DĆ14
N
S
Contactor
7
5
3
8
RH Evap.
6
Water
Pump
4
2
YL
DĆ10
LH Evap. Switch
DĆ12
1
N
S
LH Evap.
Hot Gas
GR
Condenser Sensor
Condenser
plug
DĆ11
White
Suction Line Sensor
230v
neutral
115v
Suction plug
Voltage
Selector
Switch
Fan
Options Plug
Brown
DĆ6
Sleeve Connector
Test
Plug
RD
GR
DĆ5
Error
Options
Plug
Adjustable Ice
Thickness Pot.
Transformer
Dump
Every
Cycle
Dump
Every
3rd
Dump
Dump
Every
7th
Every
5th
Cycle
Micro Processor
Cycle
Cycle
Stacking
Cable
Plug
Manual
Harvest
Switch
To Stacked
Unit
(if required)
12/1/94
Rev 3/4/96
166240004
18
Download from Www.Somanuals.com. All Manuals Search And Download.
ADJUSTING BRIDGE THICKNESS
TOP ROW
3/8I - 5/8I DIMPLE
For optimum ice production and maximum cube separation, the ice
connecting the individual cubes should be a minimum of 1/8I (.32cm)
thick at the center area of the ice waffle.
CENTER
1/8I BRIDGE
BRIDGE 1/8I (0.32 cm)
It is normal for the ice slab to be slightly thicker at the bottom and taper
off in a slight wedge pattern at the top. The top row of cubes must have
a complete pattern of ice on all four sides and the back wall. Remem-
ber, when you operate the product with the panels off during testing the
additional heat at the top of the evaporator will cause thinner ice at the
top than when the panels are in place.
Should a different thickness of the bridge be desired, it will be required
to adjust the ice thickness “POT”, located on the circuit board, as fol-
lows:
BOTTOM 2 ROWS
3/16I - 1/4I BRIDGE
1. Thinner Bridge – turn the ice thickness “pot” adjustment screw
CW one full turn. Allow two cycles before determining if
additional adjustments are required.
2. Thicker Bridge – turn the ice thickness “pot” adjusting screw CCW
one full turn. Allow two cycles before determining if additional ad-
justments are required.
NOTE: Never judge the thickness of the ice from the first batch of the ice produced – the first cycle is
a balance cycle. Always wait for the second cycle before making any adjustments.
TOTAL ICE CAPACITY
Ice capacity of any ice maker is affected by many operating conditions, such as water and air temperature and
location factors. Please review the capacity tables in this manual for average 24-hour capacity under various
conditions.
NOTE: All printed capacity ratings are ꢁ 10% except 50 HZ units. These products have 12% increase
in cycle time and capacity decrease of approximately 17%.
ICE PRODUCTION CHECK
If air cooled, take air temperature at the intake of the condenser, 2I from the condenser fins, and Incoming wa-
ter temperature at the outlet of the “float” valve.*
Cycle time (CT) = freeze time plus harvest time, in minutes and seconds. 1440 divided by CT = number of
cycles per 24 hours.
Measure weight of ice from one cycle in pounds and fractions of a pound.
EXAMPLE: Weight/cycle x cycles/day = total production/24 hrs. Compare to the production tables.
* If water cooled, be certain water regulator valve is set to maintain 300/310 PSI head pressure.
12/1/94
Rev 3/4/96
19
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
Water
Dump
Valve
DĆ15
DĆ14
DĆ13
YL
RH Evap. Switch
N
S
Contactor
7
5
3
8
RH Evap.
6
Water
Pump
4
YL
DĆ10
LH Evap. Switch
DĆ12
2
1
N
S
LH Evap.
Hot Gas
GR
Condenser Sensor
Condenser
plug
DĆ11
White
230v
neutral
115v
Suction Line Sensor
Suction plug
Voltage
Selector
Switch
Fan
Brown
DĆ6
Test
Plug
RD
GR
DĆ5
Error
Options
Plug
Adjustable Ice
Thickness Pot.
Transformer
Micro Processor
Stacking
Cable
Plug
Manual
Harvest
Switch
To Stacked Unit
(if required)
LED INDICATORS
The LEDs are board circuit indicators. If the LED in the functional board circuit is complete, check component.
Example: Contactor does not energize and LED is “ON”, board circuit is OK. Check contactor, coil, leads, &
connections.
Yellow:
S Evaporator switch(s) (proximity)
Green:
S Water dump valve
S Compressor contactor
S Water Pump
S Hot Gas Valve
S Condenser Fan (cycles on & off with fan)
Red:
Error in system operation. Product shut down.
12/1/94
Rev 3/4/96
166240004
20
Download from Www.Somanuals.com. All Manuals Search And Download.
STATUS INDICATOR
Condenser Fan
Left Water Curtain
Hot Gas Valve
D6
Green LED
Yellow LED
Green LED
Green LED
Yellow LED
Green LED
Red LED
D10
D11
D12
D13
D14
D5
Water Pump
Right Water Curtain
Compressor Contactor
Error
D15
Green LED
Dump Valve
Curtain Open
D13
D10
Yellow LED off
Right evaporator curtain open.
Yellow LED off
Left evaporator curtain open.
Pre-Chill Mode
D6
Green LED (on or off)
Green LED (on)
Yellow LED (on)
Yellow LED (on)
Condenser fan cycles on & off depending upon condenser temperature.
Compressor contactor active - Compressor running.
Right evaporator curtain closed.
D14
D13
D10
Left evaporator curtain closed (only if unit has two evaporators).
Ice-Making Mode
Condenser fan cycles on and off depending upon condenser temperature.
D6
Green LED (on or off)
Green LED (on)
Green LED (on)
Yellow LED (on)
Yellow LED (on)
D12
D14
D13
D10
Water pump active.
Compressor contactor active - compressor running.
Right evaporator curtain closed.
Left evaporator curtain closed (only if unit has two evaporators).
Harvest Mode
D11
D12
D14
D15
Green LED (on)
Three seconds after water dump valve becomes active, the hot gas valve becomes active.
Fifteen seconds after water dump valve becomes active, the water pump deactivates.
Compressor contactor active - compressor running.
Green LED (on) 15 sec.
Green LED (on)
Green LED (on) 15 sec.
Water dump valve becomes active at the start of harvest. Water dump valve is active for
15 seconds.
D13
D10
Yellow LED (on)
Yellow LED (on)
Right evaporator curtain closed. When the ice falls and the curtain opens, the LED will turn off.
Same as D13 if there is a second (left) evaporator.
Error LED
D5
D5
Red LED
Red LED
(on)
(on)
(on)
EVAPORATOR OPEN THERMISTOR CIRCUIT Ć thermistor open / broken wire / poor connection.
Ice maker is SHUT DOWN. Consult service manual (Diagnostic Section) for troubleshooting
guide.
EVAPORATOR HIGH TEMP. ERROR: Six minutes into the Freeze cycle the suction line temperaĆ
ture failed to reach 40°F or below. Ice Maker is SHUT DOWN. Consult service manual (Diagnostic
Section) for troubleshooting guide.
D5
D5
Red LED
Red LED
TWO REPEATED FAILED HARVEST CYCLES Ć No ice drop.
Flashing, 1/sec CONDENSER OPEN THERMISTOR CIRCUIT (Air Cooled only) Ć Thermistor open / broken wire /
poor connection. Ice Maker is SHUT DOWN. Consult service manual (Diagnostic Section) for
troubleshooting guide.
D5
D5
Red LED
Red LED
Flashing, 1/sec CONDENSER LOW TEMPERATURE CONDITION. Ć Condenser midpoint reaches 36°F Ć Ice
Maker is SHUT DOWN.
Flashing, 1/sec CONDENSER HIGH TEMPERATURE SAFETY SHUT DOWN.
12/1/94
Rev 3/4/96
21
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
CIRCUIT BOARD DIAGNOSTIC PROCEDURE
Turn the power switch to the “ON” position. The D-5 red LED (error indicator) will be illuminated for 2 seconds.
After the D-5 red LED goes out, short across the bottom two terminals of the Test Plug with a jumper wire or a
pocket screwdriver and then remove the jumper. The circuit board is now in the test mode.
One of these two conditions will exist:
S If the Ice Thickness Potentiometer is within the factory setting the D-5, red LED will flash continiously.
S If the Ice Thickness Potentiomater is not within the factory setting, the D-5 red LED will not be illuminated.
In either case the Green LED indicators will illuminate for 2 seconds each in the sequence shown below. They
will continue to sequence until you turn the power off and stop the procedure.
D-11
D-12
D-14
D-6
Green
Green
Green
Green
Green
Hot Gas
Water Pump
Contactor
Fan
D-15
Dump Valve
Failure of the green LED’s to cycle in this sequence indicates a defect in the circuit board.
Water
Dump
Valve
DĆ15
DĆ13
YL
RH Evap. Switch
N
S
DĆ14
Contactor
7
5
3
8
RH Evap.
6
LED Indicators
Water
Pump
4
2
YL
DĆ10
LH Evap. Switch
DĆ12
1
N
LH Evap.
S
Condenser Sensor
Hot Gas
GR
Condenser
plug
DĆ11
White
Brown
Suction plug
Voltage
Selector
Switch
Fan
Suction Line
Sensor
DĆ6
Test
Plug
RD
GR
Test
Plug
DĆ5
Error
Options
Plug
Adjustable Ice
Thickness Pot.
Transformer
Micro Processor
Stacking
Cable
Plug
Manual
Harvest
Switch
To Stacked
Unit
(if required)
12/1/94
Rev 3/4/96
166240004
22
Download from Www.Somanuals.com. All Manuals Search And Download.
RESTORING ICE THICKNESS POTENTIOMETER TO FACTORY SETTING
1. Turn cuber power switch to the OFF (center) position.
2. Unplug the proximity switch(es) and the thermistor(s) from the circuit board.
3. Turn the cuber power switch to the ON position. The red LED D-5 will illuminate for 2 seconds and then go
out.
4. Short across the bottom 2 pins of the Test Plug using a wire jumper or a pocket screwdriver. Immediately
remove the jumper.
One of these two conditions will exist:
S If the Ice Thickness Potentiometer is within the factory setting the D-5, red LED will flash continiously.
S If the Ice Thickness Potentiomater is not within the factory setting, the D-5 red LED will not be illuminated.
In either case the Green LED indicators will illuminate for 2 seconds each in the sequence shown below. They
will continue to sequence until you turn the power off and stop the procedure.
D-11
D-12
D-14
D-6
Green
Green
Green
Green
Green
Hot Gas
Water Pump
Contactor
Fan
D-15
Dump Valve
Making Adjustments
When making adjustments, turn the Ice Thickness Potentiometer screw slowly to allow the circuit board time to
react. Always turn the screw one full 360_ turn, rest several seconds, then adjust another 360_ turn.
Turn the Ice Thickness Potentiometer screw 10 (ten) turns clockwise or until the red LED D-5 starts to flash –
should the LED not start to flash after 10 (ten) turns clockwise – reverse the direction and turn the screw slowly
counterclockwise until the red LED D-5 starts to flash.
When the LED starts to flash, stop turning. You have reached the original factory setting.
Important: Erratic component operation (water pump, condenser fan, hot gas valves, etc.) are usually a
result of a poor connection at the 8-pin connector. Before doing any diagnostic test on the control
board, be sure to check the 8-pin connector to ensure that all wires are properly installed and the
connector is securely in place.
12/1/94
Rev 3/4/96
23
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
COMPONENT FUNCTION (CIRCUIT BOARD ETC.)
TEST PLUG
Board manufactures check point. DO NOT ATTEMPT ANY VOLTAGE CHECKS AT THESE PINS.
SENSORS
Condenser sensor (WHITE) and suction line sensor (BROWN) are thermistors rated 1k ohm at room tempera-
ture.
S Condenser sensor signals the circuit board for fan cycling and also serves as the high temperature safety
shut down. The red “Error LED” will flash on and off every second, during high temperature safety shut
down. Product is functionally shut down. Reset procedure must be performed to restart product operation.
S Suction line sensor signals the circuit board the suction line temperature, to control ice bridge thickness.
Also the sensor serves as suction line high temperature signal (Cuber has 6 minutes to reduce suction line
temperature to 40°F (4.4°C) in the freeze mode). The red “Error LED” will be steady on. Should this time
frame not be met, product is functionally inoperative during this safety shut down. Reset procedure must be
performed to restart product operation.
RESET OPERATION
When Cuber is functionally shut down and red “Error LED” is operational, the Cuber power switch must be
turned off for 5 seconds and returned to the ON position to reset the circuit board and allow the Cuber to restart
operation.
Evaporator Switches
Proximity Switches are half mounted to the water curtain, and the other half mounted to the evaporator side rail.
Switch Notes
1. Manually holding the curtain open during freeze mode will shut the Cuber down in 5 seconds.
2. During harvest cycle, if curtain is open for 10 seconds, the water pump will stop. The compressor will oper-
ate for 20 additional seconds before Cuber shut down takes place. When the water curtain is closed, the
Cuber will begin the normal start-up process.
3. In single evaporator machines, the proximity switch connection must be on the top (RH) connection on the
circuit board.
4. In dual evaporator machines, both RH and LH switches must open and reset to start the next freeze mode.
Harvest Safety Termination
After 4 minutes in the harvest mode, the safety timer in the circuit board will terminate the harvest mode and
place the Cuber back into a freeze mode. This safety cycle will protect the evaporator, etc. should the product
fail to terminate the harvest mode for any reason.
VOLTAGE CHECKS
Evaporator Proximity Switch
Turn Cuber power switch OFF. Disconnect proximity switch plug(s) from the circuit board. Use a digital multime-
ter set for D.C. Voltage; turn power switch ON, connect leads of meter across the top two terminal pins on the
board, (for the switch being tested), meter should read 5VDC 0.2 output voltage. If not, replace the circuit
board.
NOTE: The proximity switch on the IACS 227 or the IWCS 227 is mounted inside the right hand evaporator
side rail. To test the switch, make the voltage test at the circuit board. To replace the switch, remove the upper
right hand side service panel. Carefully remove the Mylar shield to gain access to the two nylon screws that
hold the proximity switch. Remove the screws and the switch through the service opening. After installing the
new switch, replace the Mylar shield and seal with a bead of silicone sealant.
12/1/94
Rev 3/4/96
166240004
24
Download from Www.Somanuals.com. All Manuals Search And Download.
VOLTAGE SELECTOR SWITCH
1. Selector bar in center position, switch is open. Product is inoperative.
2. Selector bar in down position, selection is for 115 VAC.
3. Selector bar in up position, selection is for 230 VAC.
STACKING CABLE
When stacking the “I” series cuber the connecting cable (connecting the two (2) circuit boards) will allow: the
bottom Unit to shut off on the full bin signal (or any error code), the top Unit will then finish the cycle it is in and
shut down. The “I” series should never be stacked more than two high.
Sensor [Thermistor] Diagnosis
Sensors
Condenser or suction line – Turn Cuber power switch OFF. Disconnect sensor plug from board. Use digital
multimeter set for D.C. Voltage. Turn power switch ON. Connect leads of meter across the two pins of the sen-
sor being checked. Meter should read 2.5 VDCꢁ0.2 output voltage from the board. If voltage is not correct, re-
place the circuit board.
Should the cuber operation indicate there may be a fault in the sensor [thermistor] or the control board cir-
cuit proceed as follows.
1. Using a good multimeter, check the control board sensor output voltage.
2. If voltage checks are correct do the following:
A. Disconnect the suction line sensor (brown lead) from the control board.
B. Install the special test cord* to the control board and reinstall the sensor to the test cord terminals.
C. Connect the multimeter (set on VDC - milli-volts) to the test cord leads.
D. Operate the cuber in the freeze cycle.
3. As the suction line temperature decreases the milli-volt reading will increase.
4. Sensor Shorted – milli-volt reading will cease to increase and will remain steady indicating a shorted sen-
sor.
5. Sensor Open – The voltage reading will indicate the control board output voltage of 2.5 VDC.
6. Should step 4 or 5 occur during this test, the sensor will require replacement.
* Special test cord, part # 164984009, may be ordered through the Service Department.
7. Condenser Sensor (white leads) – self-contained air-cooled only – water cooled and remote systems
use a resistor plug on the control board.
Complete the sensor and multimeter connections as described in
2- B, C, D
8. Shorted sensor – a steady low milli-volt reading will be recorded. The reading will not change.
9. Open sensor – the multimeter will record control board output voltage of 2.5 VDC.
10. Should sensor (thermistor) pass the voltage test proceed to the control board diagnosis for LED sequence
(see page 22).
NOTE: The sensor controls the condenser fan cycling from 88/100 degree Fahrenheit. Thus any de-
fects in the condenser circuit will effect the fan cycling rate.
CONDENSER FAN CYCLING CONTROL
The condenser fan on air-cooled cubers is cycled by the circuit board. The condenser sensor signals the circuit
board when the condenser temperature reaches 100°F (38°C) the fan starts and continues to run until the tem-
perature is reduced to 88°F (31°C).
NOTE: There is no pressure control used to cycle the fan motor on intergal condensor unit.
THERMOSTATIC EXPANSION VALVES
The following suggestions for diagnosis of automatic Thermostatic Expansion Valve (TXV) are given with the
understanding that the following have been checked and are correct and/or have been corrected prior to pro-
ceeding.
1. The condenser and fan blade are clean and have proper operating conditions.
12/1/94
Rev 3/4/96
25
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Water supply to the product is correct and flow over the evaporator is correct.
3. Cuber refrigerant charge is correct.
4. TXV sensing bulb is properly located and secured to the suction line and correctly insulated.
5. Hot gas valve(s) are not leaking and/or seeping through.
Starving TXV - Product Symptoms
1. Suction pressure lower than normal for the operating conditions.
2. Ice production lower than normal and/or none.
3. Ice pattern on evaporator (if any) thin at top and thick at bottom.
Flooding TXV - Product Symptoms
1. Ice production lower than normal and/or none.
2. Suction pressure stabilizes at higher than normal pressure for operating conditions. Suction pressure does
not modulate and may start to slowly rise.
3. Ice pattern will be very heavy at the bottom and thin at the top of the evaporator. Product may not enter
harvest cycle because of higher than normal suction line temperature.
IMPORTANT: Frost on the suction line may be normal on medium temperature refrigeration equipment.
Frost should be considered a red flag, long run times will normally produce some type of frost pattern.
Before checking the sealed refrigeration system, the external conditions that could lead to frost follow:
1. Dirty condenser
2. Dirty condenser fan blade
3. Improper air clearance around Cuber
4. Loose TXV bulb mount
5. Poor water flow over evaporator
6. Ventilation problems
The expansion valves used on Cornelius “I” series ice equipment have special super heat settings and bulb
charge designed for the product load and HP 62 refrigerant. Should the need arise to replace this or any refrig-
erant components, be certain to use only components recommended by Cornelius for the model of the Cuber
being serviced. Use of nonapproved components will compound system difficulties and may void product war-
ranty.
WATER REGULATING VALVE
The water regulating valve is used on water-cooled cubers only. The valve is installed in the condenser outlet
water line. It’s function is to control the proper operating head pressure by regulating the amount of water flow-
ing through the condenser. The valve is adjustable and factory set to maintain condenser discharge water tem-
perature @ 108/112_F (42-44_C). Setting the water regulating valve to maintain discharge water temperature
eliminates the need to enter the sealed refrigeration system. When checking the valve, the water temperature
should be taken as close to the condenser discharged as possible. The water temperature will equate to operat-
ing head pressure of approximately 310 PSI (21.1 BAR).
Should adjustment be required, the valve has an adjustment stem on the top of the valve. After allowing the
cuber to operate for 10 minutes in the ice– making mode to balance the system, turning the adjusting stem CW
will increase the discharge water temperature, and CCW
will decrease the discharge water temperature.
The water regulating valve must close off condenser water flow completely during the “hot gas” harvest cycle.
There should be no discharge water flowing out of the condenser during the harvest cycle. Should the valve fail
to close during the harvest mode, the condenser will continue to condense the compressor discharge vapor
needed for the harvest cycle and this will result in long harvest times.
Also discharge water temperature below 108_F /112_F will result in long harvest times.
Leaking (bypassing) water regulating valves are normally the result of scale build-up on the valve diaphragm
and the valve should be flushed, not replaced. To flush the valve, open the adjusting stem wide open CCW (or
force the valve spring up with a screwdriver), open and close the water supply to the condenser resulting in the
flushing action. Should this not correct the problem, replace the valve diaphragm. This can be done without en-
tering the sealed refrigeration system.
Damage to the water regulating valve may also be caused by water hammer. Water hammer will result from the
condenser inlet and outlet water lines being reversed or defective valve stops in the water supply line. Proper
installation of water–cooled equipment should always include an anti-water hammer standpipe in the supply inlet
line as close to the cuber as possible.
166240004
12/1/94
Rev 3/4/96
26
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE STEM VALVES
When closing the service stem valves to remove your gauge and manifold set always close the high side stem
valve first. Following this procedure will allow the system to “PULL” the refrigerant vapor from your manifold set
to reduce refrigerant loss. When the pressure has been reduced, close the low side stem valve.
MOISTURE CONTAMINATION
With the major changes in refrigerants in today’s marketplace and the use of hydroscopic oils the control of
moisture and contaminates have become more critical to safeguard against than ever before in the history of
mechanical refrigeration.
Contaminates are also the most difficult of all problems to determine. A Meg-Ohm meter “Megger” can be a
valuable tool to aid in the analysis of this problem. A Meg-Ohm reading log may be started any time after 90
days of operation of the product. To perform the test, proceed as listed.
Disconnect all three (3) compressor leads, take a Meg-Ohm meter reading from each compressor terminal to a
good chassis ground. Compare reading to chart below:
Meter Reading
MegĆOhm
Compressor Condition
Maintenance Required
Okay
None needed.
100 Ć ∞
50 to 100
Moisture present
Replace drier.
20 to 50
Severe moisture & possible contaminated oil
with acid present
Replace drier with acid hold type. Run 24
hours, change to regular drier.
.5 to 20
System has severe contamination
Remove compressor oil and refrigerant charge.
Evacuate, install liquid and suction line driers
(acid hold type). Recharge with new oil and reĆ
frigerant. Run 24 hours. Discharge system, disĆ
card suction line drier, replace the liquid line
drier. Evacuate and recharge.
Readings in the range listed below 100 Meg-Ohm would be an indicator that the system being tested may have
a contamination problem. Where does the problem come from? As an example, the filter drier may become sat-
urated and hold large percentages of moisture and the system function without a problem until such time as the
product operating conditions change. Should the room temperature increase, or the condenser plug-up etc., the
higher operating pressures and temperatures may cause the drier filter to release a portion of it’s held moisture.
It is also imperative to avoid opening the sealed refrigeration system whenever possible and when it is done to
be certain the true problem is correctly diagnosed and repaired. Remember, service gauge sets should only be
installed after all external checks have been performed.
CAUTION: Megger checks should NEVER be performed on any compressor that is under a
vacuum.
COMPRESSOR CONTACTOR
The contactor serves as the voltage supply switch for the compressor circuit. Voltage to the coil of the contactor
is supplied by the circuit board.
Check Out:
The two (2)* line supply screws of the contactor should always have supply voltage present when voltage is on
to the product.
The other two (2)* screws (load) should have line voltage when the contactor is energized. The contactor coil
receives its supply voltage from the circuit board. Should the contactor fail to energize:
12/1/94
Rev 3/4/96
27
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
Check for supply voltage from circuit board, lead connections to contactor coil, and ohms value of coil.
* (3) if the product is 3 phase
Note: See compressor run-on condition check procedure on page 31.
COMPRESSOR & STARTING COMPONENT CHECK-OUT PROCEDURE
When compressors fail to start or run properly, it is normally the external electrical supply or the compressor
start components that are defective – the overload protector, start and/or run capacitor, relay, circuit board,
safety controls, etc.
1. Check voltage at compressor terminals. NO voltage will require checking the electrical circuit working back
from the compressor to determine where the voltage supply is interrupted and correct as required. The
load voltage, while compressor is trying to start, should not be less than 90% of rated required voltage.
Line voltage and wire size effect the life expectancy of the electrical components, compressor, motor winding,
solenoid coils, etc.
Poor line quality voltage will cause many erratic electrical problems. Remember every electrical product, ice ma-
chine, dispenser, walk-in, reach-in, air conditioner, etc. required proper power supply to operate. Be certain
when voltage checks are performed that you are measuring load voltage, not line voltage.
2. A defective capacitor or start relay may prevent the compressor from starting. Should the compressor at-
tempt to start, but is unable to do so, or if the compressor hums or trips off on the over protector, check the
following:
NOTE: For 50 HZ application on dual rated 50/60 HZ models, load voltage while compressor is start-
ing must not be less than 90% of 50 HZ rating.
Relay
Potential –
For the potential type, contacts are normally closed. The start contacts open by C.E.M.F. generated by the com-
pressor at approximately 80% of the normal operating speed. As the contacts open, only the start capacitor is
removed from the start circuit. Both the start and run winding and the run capacitor remain in the circuit. This
relay may or may not be directional in mounting.
Current –
For the current type, contacts are normally open. The start contacts close by the high current draw from the
locked rotor condition with only the run winding in the circuit. As the contacts close, the start capacitor and the
start winding is energized and the compressor starts. At approximately 80% of its operating speed the current
draw drops off, the relay contacts open removing the start winding and start capacitor from the circuit. (Remem-
ber, current relays are directional in their mounting to allow contacts to lift and close).
Capacitors
A quick check is to replace suspected defective capacitors with known good capacitors being careful to stay
within the range for substitute values. Should those values be unknown, a basic rule for capacity is: for start ca-
pacitors ꢁ10% and run capacitors ꢁ5% of the rating on the defective original capacitor being replaced. Voltage
should always try and be matched; if it cannot be, it is acceptable to increase up to 10% higher than the voltage
listed on the capacitor being replaced. NEVER put a capacitor on a product with a voltage rating lower than the
original being replaced. If a capacitor analyzer is not available, an ohm meter may be used to check a capacitor
for short or open circuits. Set the ohm meter to its highest scale and connect its leads to the capacitor terminals.
1. With a capacitor, without plate defect, the indicator should first move to zero (0) and then gradually in-
crease to infinity.
2. If there is no movement of the ohm meter indicator, an open circuit is indicated.
3. If the ohm meter indicator moves to zero (0) and remains there, or on a low resistance reading, a short cir-
cuit is indicated.
4. Please note this check does not determine if the capacitor will deliver the proper rated MFD/UFD required,
it only shows if the capacitor has shorted or open circuits.
5. Capacitors that show any signs of leakage of electrolyte, or damage of the can, should be replaced. DO
NOT TEST!
Compressor
1. Using an ohm meter, check for continuity from compressor terminal C to R and C to S. If the compressor is
hot, wait one (1) hour for compressor to cool and recheck. An open internal overload protector can cause a
lack of continuity. If continuity cannot be measured through all windings, the compressor must be replaced.
12/1/94
Rev 3/4/96
166240004
28
Download from Www.Somanuals.com. All Manuals Search And Download.
2. To check the compressor motor for accidental ground, perform a continuity check between terminals C, R
and S to the compressor shell or a copper line of the refrigeration system (do not use a painted surface).
Continuity present, the compressor windings are grounded and the compressor must be replaced.
If the compressor starts, but trips repeatedly on the overload protector, remember that the overload is both tem-
perature and current activated. Be sure to check:
S Low voltage
S Undersized supply lines
S High head pressure
S High suction pressure
S Defective capacitors
S Compressor mechanical problems
S Low refrigerant charge
LEAK DETECTION
The new non-chlorine based refrigerants such as [HP - 62/R 404A] require special leak detection devices other
than what has been standard for the CFC’s.
While the instruments for leak detection are different, the processes have not changed.
Basics to remember:
1. Look for signs of oil when you visually start your leak check process. Oil is carried with the refrigerant. If
the oil has leaked out so will the refrigerant.
2. Refrigerant vapor is heavier than air. When leak checking suspect areas, probe below the joints or connec-
tions.
A. Always check the high-side of the system with the compressor operational.
B. Check the low-side of the system, with the system idle.
C. Following a & b will normally allow the highest pressure on each portion of the system for the best
detection.
3. Systems short of refrigerant will show improper operational results in both the freeze and harvest cycles.
Many systems will appear normal in higher operating temperatures and change drastically in cooler con-
denser temperatures.
4. Many new and reworked leak detection instruments have the ability to detect CFC’s, HCFC’s and the new
HFC’s by making a simple switch selection. This type of detector will be more sensitive on one setting than
the other. This results in finding some leaks that are so small it may take years before the actual leak rate
would create adverse operating conditions in the product.
A bubble test and/or additives with UV lamp may be the best team for the most positive leak testing results.
5. Never pressurize a system with oxygen or a mixture of refrigerant and air. Either of these methods may
cause a system explosion to occur.
6. Pressurizing systems to leak test should only be done with dry nitrogen. Be sure the regulator setting does
not exceed the recommended system pressure.
CAUTION: A full cylinder of nitrogen will have pressure of approximately 2700 PSI.
7. Failure to correct leaks will also cause shorter compressor life as a result of the higher operating tempera-
tures. Always leak check the total system as one located leak may not be the only leak.
SYSTEM EVACUATION & RECHARGING
Should service work ever be required on a product where the sealed refrigeration is opened for any reason, the
refrigerant must be recovered, drier/filter replaced, evacuated and recharged. The old method of “purging” is
NOT ACCEPTABLE. Always evacuate the system through both the high and low side service valves. Be certain
both valves are completely open when evacuating and the drier/filter has been replaced.
SELF-CONTAINED PRODUCTS
With the new POE [Polyol Ester] oils, the refrigeration system is more prone to moisture problems than the CFC
systems. Every effort should be made to never have the system open to the atmosphere for longer than 15 min-
utes, and the replacement of the drier/filter is no longer an option, [IT IS MANDATORY].
12/1/94
29
166240004
Rev 3/4/96
Download from Www.Somanuals.com. All Manuals Search And Download.
A good vacuum is not always easy to measure, however the goal is to have less then 1% non-condensible va-
pors in the system at the completion of the evacuation. Basic guidelines with a good pump would be to evacu-
ate a selfcontained product 30 to 45 minutes and a remote product no less than 60 minutes.
The system should be evacuated to approximately 200/250 microns. Then perform a 5 minute holding test. You
may expect a low grade loss of the vacuum as normal. However, a rapid rise to normal atmospheric pressure
would signal a system leak is present and must be located and repaired before recharging the product. A slower
pressure rise to approximately 1500 microns would signal moisture still present in the refrigeration system.
On a “WET” system, it would be beneficial to use heat lamps to raise the temperature of the compressor dome
and evaporator surface area during the evacuation.
To assure a properly recharged product, the refrigerant charge must be weighed into the product using an elec-
tronic charging scale or dial-a-charge. On air- and water-cooled products the charge should be introduced into
the high side service valve. On remote systems, the charge should be introduced into the product receiver.
MANIFOLD SET
MANIFOLD SET
CLOSED
OPEN
OPEN
OPEN
OPEN
HIGH SIDE
SERVICE
VALVE
CLOSED
HIGH SIDE
SERVICE
VALVE
LOW SIDE
SERVICE
VALVE
LOW SIDE
SERVICE
VALVE
CLOSED
OPEN
CHARGING
CYLINDER
CHARGING
CYLINDER
OPEN
CLOSED
VACUUM
PUMP
VACUUM
PUMP
OPEN
CLOSED
ELECTRONIC
SCALE
ELECTRONIC
SCALE
IMPORTANT: Service personnel are held responsible for ALL ASPECTS OF THE CLEAN AIR ACT OF
JULY, 1992.
REFRIGERANT DEFINITIONS
(ASHRAE 3-1990)
RECOVERY
To remove refrigerant in any condition from a system and store it in an external container without necessarily
testing or processing it in any way.
RECYCLING
To clean refrigerant for reuse by oil separation and single or multiple passes through devices, such as replace-
able core filter-driers, which reduce moisture, acidity, and particulate matter. This term usually applies to proce-
dures implemented at the field job site or at a local service shop.
RECLAIM
To reprocess refrigerant to new product specifications by means which may include distillation. Will require
chemical analysis of the refrigerant to determine that appropriate product specifications are met. This term usu-
ally implies the use of processes or procedures available only at a reprocessing or manufacturing facility.
NOTES REGARDING RECLAIM:
“New product specifications” currently means ARI standard 700-88. Note that chemical analysis is required to
assure that this standard is met.
166240004
12/1/94
Rev 3/4/96
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Chemical analysis is the key requirement to the definition of “Reclaim”. Regardless of the purity levels reached
by a re-processing method, the refrigerant is not “reclaimed” unless it has been chemically analyzed and meets
ARI Standard.
HIGH PRESSURE SAFETY SWITCH
All water-cooled and remote products contain a high pressure safety cut-out switch. The function of this switch
is to shut down the cuber should excessive pressure develop in the high side of the refrigeration system. This
switch will open the power supply at 450 PSI (30.61 BAR) high side pressure. Should this control open, it must
be reset manually and the cause for the increase in pressure determined.
COMPRESSOR RUN-ON
Contactor remains energized when curtains are in a full bin condition – compressor runs but water pump and
condenser fan (AC) are off.
1. Check VAC at contactor coil with an analog voltmeter (dial type, not digital).
A. Voltage at the contactor coil 12 VAC or higher may hold the coil energized. Turn the power switch
OFF, if contactor de-energizes, replace the circuit board, the snubber circuit is leaking.
B. Should you find 1/2 normal line voltage, replace the circuit board, the triac is shorted.
C. If no voltage or very low voltage (6 VAC or less) is present and plunger is still closed, replace the con-
tactor.
12/1/94
Rev 3/4/96
31
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IACS227/IAC322/IAC330
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Day
AVERAGE
ICE
WEIGHT
lb/Cycle
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
200
228
267
270
299
39
42
44
45
47
9:5
150
160
183
181
199
105
110
133
130
142
1:1
0:9
0:7
0.7
0:6
2.4
2.4
2.5
2.4
2.8
325
260
240
220
200
80
12:4
14:3
15.1
19:8
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1379
1572
1841
1862
2062
269
290
303
310
324
9:5
1034
1103
1262
1248
1372
724
758
917
896
979
1:1
0:9
0:7
0.7
0:6
1.1
1.1
1.1
1.1
1.3
147
118
109
100
91
12:4
14:3
15.1
19:8
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IWCS227/IWC322/IWC330
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
300
300
300
303
300
40
42
43
44
44
12:1
15:3
16:2
16.4
16:3
143
160
160
173
160
103
116
118
120
117
0:9
1:1
1:2
1.1
1:3
2.8
2.8
2.9
2.8
2.6
310
245
240
230
215
80
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
2068
2068
2068
2089
2068
276
290
296
303
303
12:1
15:3
16:2
16.4
16:3
986
710
800
814
827
807
0:9
1:1
1:2
1.1
1:3
1.3
1.3
1.3
1.3
1.2
141
111
109
104
98
1103
1103
1193
1103
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IAC522/IAC530
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
220
250
275
290
320
38
42
41
45
46
12:5
14:6
17:4
17.9
20:9
155
175
195
200
220
95
1.0
0:9
0:7
0.6
0:6
5.1
4.8
5.1
5.0
5.2
540
450
405
387
350
80
111
120
120
120
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1517
1724
1896
1999
2206
262
290
283
310
317
12.5
14.6
17.4
17.9
20.9
1069
1207
1344
1379
1517
655
765
827
827
827
1:0
0.9
0.7
0.6
0.6
2.3
2.2
2.3
2.3
2.4
245
204
184
176
159
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IWC522/IWC530
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
323
327
326
328
327
44
45
45
47
45
11:3
13:7
13:8
15.2
13:9
156
168
173
184
175
106
115
117
127
119
1:3
1.2
1:1
1:1
1:1
4.3
4.4
4.3
4.3
4.3
490
425
420
384
415
80
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
2227
2255
2248
2261
2255
303
310
310
324
310
11:3
13:7
13:8
15:2
13:9
1076
1158
1193
1269
1207
731
793
807
876
820
1:3
1:2
1:1
1:1
1:1
1.9
2.0
2.0
2.0
2.0
222
193
191
174
188
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IAC630
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
225
261
296
297
333
34
37
40
40
43
8:4
148
166
183
184
200
88
1:5
1.2
1:1
1:0
1:1
5.4
5.6
5.6
5.5
6.0
755
640
590
560
475
80
11:3
12:6
13:2
17:1
101
113
113
125
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1551
1800
2041
2048
2296
234
255
276
276
296
8:4
1020
1145
1262
1269
1379
607
696
779
779
862
1:5
1:2
1:1
1:0
1:1
2.4
2.5
2.6
2.5
2.7
342
290
268
254
215
11:3
12:6
13:2
17:1
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IWC630
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
299
299
300
304
300
35
38
38
39
38
10:1
12:4
12:3
14:0
12:2
143
152
153
166
152
86
92
1:6
1.4
1:4
1:2
1:4
5.8
6.0
5.9
6.0
5.8
715
622
620
570
615
80
90
93
90
100
93
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
2062
2062
2068
2096
2068
241
262
262
269
262
10:1
12:4
12:3
14:0
12:2
986
593
634
641
689
641
1:6
1:4
1:4
1:2
1:4
2.6
2.7
2.7
2.7
2.6
324
282
281
259
279
1048
1055
1145
1048
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IRC630
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
225
261
296
297
333
34
37
40
40
43
8:4
148
166
183
184
200
88
1:5
1.2
1:1
1:0
1:1
5.2
5.6
5.6
5.5
6.0
755
640
590
560
475
80
11:3
12:6
13:2
17:1
101
113
113
125
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1551
1800
2041
2048
2296
234
255
276
276
296
8:4
1020
1145
1262
1269
1379
607
696
779
779
862
1:5
1:2
1:1
1:0
1:1
2.4
2.5
2.6
2.5
2.7
342
290
268
254
215
11:3
12:6
13:2
17:1
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IAC830
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
253
293
335
339
379
29
33
36
37
40
7:6
9:0
163
187
210
209
232
83
97
1:5
1.0
0:9
0:9
0:8
5.3
5.2
5.8
5.8
6.0
840
745
680
645
595
80
90
11:5
12:0
13:8
111
111
126
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1744
2020
2310
2337
2613
200
228
248
255
276
7:6
9:0
1124
1289
1448
1441
1600
572
669
765
765
869
1:5
1:0
0:9
0:9
0:8
2.4
2.3
2.7
2.6
2.7
381
338
308
293
270
11:5
12:0
13:8
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IWC830
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
298
296
295
298
295
32
34
34
37
34
8:6
154
163
164
166
175
81
86
87
88
93
1:5
1.3
1:3
1:2
1:3
5.6
5.7
5.9
6.0
5.9
795
715
710
650
690
80
10:2
10:7
12:1
11:1
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
2055
2041
2034
2055
2034
221
234
234
255
234
8:6
1062
1124
1131
1145
1207
558
593
600
607
641
1:5
1:3
1:3
1:2
1:3
2.5
2.6
2.7
2.6
2.7
361
324
322
295
313
10:2
10:7
12:1
11:1
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IRC830
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
253
293
335
339
379
29
33
36
37
40
7:6
9:0
163
187
210
209
232
83
97
1:5
1.0
0:9
0:9
0:8
5.3
5.2
5.8
5.8
6.0
840
745
680
645
595
80
90
11:5
12:0
13:8
111
111
126
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1744
2020
2310
2337
2613
200
228
248
255
276
7:6
9:0
1124
1289
1448
1441
1600
572
669
765
765
869
1:5
1:0
0:9
0:9
0:8
2.4
2.3
2.7
2.6
2.7
381
338
308
293
270
11:5
12:0
13:8
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IAC1030
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
240
276
312
313
349
33
36
38
38
41
13:5
14:2
15:9
16:8
18:7
164
177
196
198
215
75
83
1:7
1.4
1:1
1:1
1:0
11.6
10.5
10.5
10.5
10.8
1101
969
890
840
793
80
90
91
90
91
100
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1655
1903
2151
2158
2406
228
248
262
262
283
13:5
14:2
15:9
16:8
18:7
1131
1220
1351
1365
1482
517
572
627
627
689
1:7
1:4
1:1
1:1
1:0
5.3
4.8
4.8
4.7
4.9
499
440
404
381
360
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IWC1030
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
296
297
297
300
297
34
35
36
36
36
13:0
15:3
15:7
17:9
15:8
155
161
161
175
164
73
75
77
81
77
1:8
1.7
1:5
1:4
1:5
10.7
10.9
11.0
11.0
11.0
1046
925
920
823
915
80
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
2041
2048
2048
2068
2048
234
241
248
248
248
13:0
15:3
15:7
17:9
15:8
1069
1110
1110
1207
1131
503
517
531
558
531
1:8
1:7
1:5
1:4
1:5
4.9
4.9
5.0
5.0
5.0
474
420
417
373
415
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IRC1030
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
240
276
312
313
349
33
36
38
38
41
13:5
14:2
15:9
16:8
18:7
164
177
196
198
215
75
83
1:7
1.4
1:1
1:1
1:0
11.6
10.5
10.5
10.5
10.8
1101
969
890
840
793
80
90
91
90
91
100
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1655
1903
2151
2158
2406
228
248
262
262
283
13:5
14:2
15:9
16:8
18:7
1131
1220
1351
1365
1482
517
572
627
627
689
1:7
1:4
1:1
1:1
1:0
5.3
4.8
4.8
4.7
4.9
499
440
404
381
360
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IAC1230
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
231
266
296
295
331
30
33
35
36
38
8:8
175
191
211
211
232
75
84
1:5
1.1
1:0
0:9
0:9
8.9
9.5
1249
1090
1000
948
80
11:4
13:6
14:5
16:3
90
95
10.1
10.1
10.3
90
93
100
105
865
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1593
21834
2041
2034
2282
207
228
241
248
262
8:8
1207
1317
1455
1455
1600
517
579
655
641
724
1:5
1:1
1:0
0:9
0:9
4.1
4.3
4.6
4.6
4.7
567
494
454
430
392
11:4
13:6
14:5
16:3
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IWC1230
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
336
324
330
323
324
30
30
33
32
30
10:1
13:2
14:0
14:8
14:0
187
177
180
180
180
73
76
76
78
76
1:4
1.3
1:3
1:3
1:3
9.8
1221
1065
1030
973
80
10.7
10.9
10.9
10.9
90
90
100
1025
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
2317
2234
2275
2227
2234
207
207
228
221
207
10:1
13:2
14:0
14:8
14:0
1289
1220
1241
1241
1241
503
524
524
538
524
1:4
1:3
1:3
1:3
1:3
4.4
4.9
5.0
4.9
4.9
554
483
467
441
465
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IRC1230
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
231
266
296
295
331
30
33
35
36
38
8:8
175
191
211
211
232
75
84
1:5
1.1
1:0
0:9
0:9
8.9
9.5
1249
1090
1000
948
80
11:4
13:6
14:5
16:3
90
95
10.1
10.1
10.3
90
93
100
105
865
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1593
1834
2041
2034
2282
207
228
241
248
262
8:8
1207
1317
1455
1455
1600
517
579
655
641
724
1:5
1:1
1:0
0:9
0:9
4.1
4.3
4.6
4.6
4.7
567
494
454
430
392
11:4
13:6
14:5
16:3
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IAC1448
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
246
280
315
317
352
31
34
35
37
38
10:1
11:8
13:2
13:7
15:8
185
201
220
222
242
79
88
1:3
1.3
1:1
1:1
0:8
12.1
12.3
12.6
12.4
13.1
1525
1355
1275
1205
1140
80
90
97
90
98
100
106
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1696
1931
2172
2186
2427
214
234
241
255
262
10:1
11:8
13:2
13:7
15:8
1276
1386
1517
1531
1669
545
607
669
676
731
1:3
1:3
1:1
1:1
0:8
5.5
5.6
5.7
5.6
6.0
692
615
578
547
517
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IWC1448
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
316
318
318
317
316
32
35
36
37
36
9:9
180
188
190
194
189
73
77
78
80
77
1:7
1.4
1:3
1:3
1:4
12.1
12.7
12.8
12.6
13.1
1505
1370
1360
1270
1335
80
11:9
12:2
13:0
12:7
90
90
100
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
2179
2193
2193
2186
2179
221
241
248
255
248
9:9
1241
1296
1310
1338
1303
503
531
538
552
531
1:7
1:4
1:3
1:3
1:4
5.5
5.8
5.8
5.7
5.9
683
621
617
576
606
11:9
12:2
13:0
12:7
Download from Www.Somanuals.com. All Manuals Search And Download.
AVERAGE OPERATING CHARACTERISTICS
IRC1448
IP Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_F
WATER
TEMP
_F
70
50
70
70
80
70
246
280
315
317
352
31
34
35
37
38
10:1
11:8
13:2
13:7
15:8
185
201
220
222
242
79
88
1:3
1.3
1:1
1:1
0:8
12.1
12.4
12.7
12.5
13.3
1535
1365
1285
1215
1150
80
90
97
90
98
100
106
SI Units
FREEZE CYCLE
HARVEST CYCLE
AVERAGE
ICE
WEIGHT
kg/Cycle
AVERAGE
ICE
WEIGHT
kg/Day
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
AMBIENT
TEMP
_C
WATER
TEMP
_C
21
27
32
32
38
10
21
21
27
21
1696
1931
2172
2186
2427
214
234
241
255
262
10:1
11:8
13:2
13:7
15:8
1276
1386
1517
1531
1669
545
607
669
676
731
1:3
1:3
1:1
1:1
0:8
5.5
5.6
5.8
5.7
6.0
696
619
583
551
522
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
IMPORTANT: Only qualified personnel should service internal components or electrical wiring.
Trouble
Probable Cause
Remedy
CUBER NOT OPERATING
A. Power switch in center “OFF”
A. Place switch in “ON” position.
position.
CUBER NOT OPERATING,
INDICATOR LIGHTS “OFF”,
NO POWER TO CIRCUIT
BOARD
A. Test power switch and leads.
A. If defective, replace.
B. High pressure cut-out open.
(water cooled or remote
systems)
B. Press manual reset.
Determine cause:
Water supply shut off; water
pressure too low; water valve
defective or out of adjustment;
water condenser dirty or
corroded; unit overcharged; water
inlet pressure too high. Replace
defective component as needed.
CUBER NOT OPERATING,
INDICATOR LIGHTS “OFF”,
POWER TO THE CIRCUIT
BOARD
A. Magnet not in proximity switch A. Water curtain drifting out of switch
field.
range. Reduce clearance between
curtain and proximity switch.
B. No curtain movement.
C. Faulty proximity switch.
D. Unit “OFF” due to bin full.
B. Adjust proximity switch.
C. Replace proximity switch.
D. Remove ice from curtain.
Eliminate curtain restriction.
COMPRESSOR DOES NOT
RUN, CIRCUIT BOARD
A. Check contactor and leads.
A. Replace if defective.
INDICATOR LIGHTS “ON”
B. Compressor overload “open”.
B. Permit overload to cool and reset
or replace.
C. Check compressor and start
components.
C. Replace as needed.
12/1/94
Rev 3/4/96
51
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
Trouble
Probable Cause
A. Low charge.
Remedy
COMPRESSOR RUNS BUT
DOES NOT COOL, CIRCUIT
BOARD INDICATOR LIGHTS
“ON”
A. Leak check – Recharge.
B. Hot gas solenoid leaking.
C. Defective expansion valve.
D. Inefficient compressor.
B. Replace.
C. Replace.
D. Replace.
E. Internal by-pass open,
compressor noisy.
E. Permit pressures to equalize.
CUBER REMAINS IN THE
FREEZE CYCLE
A. Check suction line thermistor
(sensor) lead wire connection
at the circuit board.
A. Tighten, reattach.
B. Evaporator thermistor shorted. B. Replace.
C. Check thermistor (1K ohm).
D. Ice bridge setting too low.
C. Replace if out of range.
D. Adjust per bridge adjustment
instructions.
E. Expansion valve failure (will
not pull down).
E. Tighten bulb, replace as needed.
See check-out procedure.
CUBER REMAINS IN THE
HARVEST CYCLE
SUCTION LINE THERMISTOR
OPEN (STARTS IN HARVEST)
A. Loose connection at the circuit A. Tighten or reconnect.
board.
B. Test thermistor.
B. Replace if out of range.
PROXIMITY SWITCH LIGHT
“OUT”
C. Loose wire connection at
circuit board.
C. Tighten, reattach wire.
D. Proximity switch defective, see D. Replace as needed.
check-out procedure.
E. Water curtain stuck, curtain
frozen to ice on evaporator.
Curtain hung on water pan,
proximity switch out of range.
E. Check and adjust as needed.
PROXIMITY SWITCH LIGHT “ON”
F. Circuit board failure. Check
voltage output.
F. Replace as needed.
G. Ice weight too light.
G. Adjust bridge per Bridge
Adjustment instructions.
H. Potentiometer set too high.
H. Adjust bridge per Bridge
Adjustment instructions.
I.
Water curtain stuck, curtain
frozen to ice on evaporator.
Curtain hung on water pan,
proximity switch out of range.
I.
Check and adjust as needed.
12/1/94
Rev 3/4/96
166240004
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Trouble
Probable Cause
A. Float set too high.
B. Float stuck.
Remedy
LONG FREEZE CYCLE
WATER FLOW ASSOCIATED
A. Adjust.
B. Clean or replace.
C. Flow control washer missing or C. Replace or re-install.
upside down (number must be
facing up).
LONG FREEZE CYCLE
GENERAL
A. Water leaking around pan or
curtain.
A. Adjust as needed.
B. Dirty condenser or fan blade.
B. Clean as required.
C. Remove obstruction.
C. Louvers at condenser
obstructed.
D. Ambient air or water
temperature too high.
D. Advise customer.
E. Condenser discharge air
re-circulating.
E. Install condenser baffle.
F. Low charge.
F. Check for leak, correct, evacuate
and recharge.
G. Hot gas solenoid valve leaking G. Replace.
(not seating).
H. Water regulator valve set too
high or stuck (water cooled
units only).
H. Adjust, clean or replace (setting to
be 300 to 310 PSI).
LONG HARVEST CYCLES
A. Ice weight set too light.
A. Adjust bridge per adjustment
instructions.
B. Unit not level.
B. Level the unit.
C. Water curtain movement
restricted.
C. Remove restriction.
D. Low head pressure: ambient
too low.
D. Minimum ambient temperature
50_F (10_C).
E. Adjust water regulator valve or
replace (300 to 310 PSI).
E. Low head pressure; water
valve set too low (water cooled
units only) or leaking during
harvest.
F. Scale build-up on evaporator.
F. Clean per instructions.
G. Replace valve.
G. Hot gas solenoid valve not
opening. Slow rise of low side
pressure.
H. Expansion valve leaking.
H. Replace valve.
12/1/94
Rev 3/4/96
53
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
Trouble
Probable Cause
Remedy
ICE WEIGHT LIGHT AT TOP
OF PLATE AND HEAVY AT
THE BOTTOM
A. Float stuck open.
A. Replace the float valve.
NOTE: REVIEW DRAWING
ON PAGE 19 OF THIS
MANUAL FOR NORMAL ICE
SLAB.
B. Flow control washer missing
from the float or installed
upside-down (numbers must
be facing up).
B. Replace or re-install as needed.
C. Water flow rate over the
evaporator too fast.
C. Check position of distribution tube
(inner & outer).
D. Water leaking around curtain
and pan; curtain frozen in the
ice.
D. Correct.
E. Expansion valve flooding.
E. Tighten and seal bulb. Replace
TXV if required.
F. Condenser air re-circulating.
G. Low charge.
F. Install baffle.
G. Leak check, evacuate & recharge.
H. Hot gas solenoid valve leaking. H. Replace.
I.
Evaporator wall gasket torn or I.
missing, allowing condenser
air to reach top of evaporator.
Replace.
SOFT WHITE ICE OR WATER A. Distribution tube or water
A. Clean distribution system as
required.
PUMP NOT PUMPING
system scaled.
B. Water temperature too cold.
B. 50_F (10_C) minimum.
C. Correct.
C. Inadequate water system;
water pressure too low (below
20 PSI).
D. Inadequate water system; float D. Replace.
plugged or damaged.
E. Distributor tubes – old style
E. Replace with new style, 47 hole,
distributor tube. High flow tubes
require new style water curtains to
contain water.
12/1/94
Rev 3/4/96
166240004
54
Download from Www.Somanuals.com. All Manuals Search And Download.
WH
BR
COMPRESSOR
START
CAPACITOR
GR
COMPRESSOR
R
CONTACTOR
RD
YL
BK
243-292 mfd
115 VAC
C
S
BK
BK
EXTERNAL
COMPRESSOR
OVERLOAD
OR
WH
M
UNIT
SWITCH
2
BR
5
BK
CURRENT
START RELAY
CONDENSATION
FAN (W/C ONLY)
BL
1
1
WH
2
3
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C ONLY)
WH
WATER DUMP
VALVE
BR
CO
450 PSIG
WH
BK
BL
BL
WATER DUMP
SWITCH
1
BR
3
2
CONDENSER
FAN MOTOR
(A/C ONLY)
YL
BK
M
Water
Dump
Valve
D-15
BK
GR
D-13
YL
D-14
GR
WH
RH Evap.
Switc
h
7
8
6
Relay
RH Evap.
5
N
S
BL
Water
Pump
4
2
3
1
GR
WH
D-12
YL
D-10
D-11
GR
Hot Gas
Valve
(White Lead)
Condenser
Sensor
LH Evap.
WH
230V
WH
RD
Condenser
Plug
Voltage
Selector
Switch
See note 1
PUMP
CORD
Suction
Plug
D-6
GR
Condenser
Fan
Suction Line
Sensor
(Brown Lead)
115V
HOT GAS
SOLENOID
Test
Plug
RD
D-5
Error
Options
Plug
M
Adjustable
Ice
Transformer
BL
BL
Thickness Pot.
WATER PUMP
Micro
Processor
To Stacked
Unit
(if required)
Stacking
Cable
Plug
Manual
Harvest
Switch
IAC 322 & IWC 322
IAC 330 & IWC 330
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C UNITS.
12/1/94
Rev 3/4/96
55
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
WH
BR
COMPRESSOR
START
GR
POWER
CORD
COMPRESSOR
R
CAPACITOR
CONTACTOR
RD
YL
BK
243-292 mfd
115 VAC
C
S
BK
BK
EXTERNAL
COMPRESSOR
OVERLOAD
M
OR
WH
UNIT
2
BR
CONDENSATION
FAN (W/C ONLY)
5
SWITCH
BK
POTENTIAL
BL
1
1
3
START RELAY
WH
2
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C ONLY)
WH
WATER DUMP
VALVE
BR
CO
450 PSIG
WH
BK
BL
BL
WATER DUMP
SWITCH
1
BR
3
2
CONDENSER
FAN MOTOR
(A/C ONLY)
YL
BK
M
Water
Dump
Valve
D-15
BK
GR
D-13
YL
D-14
GR
WH
RH Evap.
Switch
7
8
6
Relay
RH Evap.
5
N
S
BL
Water
Pump
4
2
3
1
GR
WH
D-12
YL
D-10
D-11
GR
Hot Gas
Valve
(White Lead)
Condenser
Sensor
LH Evap.
BK
230V
RD
WH
Condenser
Plug
Voltage
Selector
Switch
See note 1
PUMP
CORD
Suction
Plug
D-6
GR
Condenser
Fan
Suction Line
Sensor
(Brown Lead)
115V
HOT GAS
SOLENOID
Test
Plug
RD
D-5
Error
Options
Plug
M
Transformer
Adjustable Ice
Thickness Pot.
BL
WATER PUMP
Micro
Processor
To Stacked
Unit
(if required)
Stacking
Cable
Plug
Manual
Harvest
Switch
BL
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C UNITS.
IACS 227 & IWCS 227
115 Volts 60 HZ
ILL339
12/1/94
Rev 3/4/96
56
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
RD
RD
RD
COMPRESSOR
START
CAPACITOR
CURRENT
RELAY
GR
BK
POWER
CORD
CONTACTOR
COMPRESSOR
R
L
RD
BR
WH
C
S
S
M
YL
EXTERNAL
BK
43-52 mfd 220 VAC
BK
COMPRESSOR
OVERLOAD
RD
RD
BL
M
RD
BK
CONDENSATION FAN
(W/C ONLY)
BR
MANUAL RESET
HIGH PRESSURE CONTROL
(W/C ONLY)
RD
WATER DUMP
VALVE
CO
450 PSIG
BR
WH
BK
RD
BL
WATER DUMP
SWITCH
UNIT
1
BR
SWITCH
3
2
BL
M
BK
YL
BK
CONDENSOR
FAN MOTOR
(A/C ONLY)
Water
Dump
Valve
WH
D-15
GR
D-13
YL
D-14
GR
RH Evap.
Switch
8
6
7
5
Relay
BL
RH Evap.
N
S
Water
Pump
4
2
3
1
GR
D-12
RD
RD
D-10
YL
LH Evap.
Switch
WH
WH
D-11
GR
N
S
LH Evap.
Hot Gas
Valve
230V
Voltage
Selector
Switch
PUMP
CORD
(White Lead)
Condenser Sensor
Condenser
Plug
See note 1
D-6
GR
Suction
Plug
Condenser
Fan
HOT GAS
SOLENOID
Suction Line
Sensor
(Brown Lead)
115V
Test
Plug
RD
M
WATER PUMP
D-5
Error
BL
Options
Plug
Transformer
Adjustable Ice
Thickness Pot.
Micro
Processor
To Stacked
Unit
(if required)
Stacking
Cable
Plug
Manual
Harvest
Switch
BL
IACS227E60, IWCS227E60,
208/230V 60HZ
Artwork 50910
12/1/94
Rev 3/4/96
57
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
WH
BR
COMPRESSOR
RUN
COMPRESSOR
START
GR
COMPRESSOR
R
CAPACITOR
CAPACITOR
CONTACTOR
RD
RD
BK
30 mfd
440 VAC
C
S
YL
72-86 mfd
330 VAC
BK
BK
EXTERNAL
YL
COMPRESSOR
OVERLOAD
OR
WH
M
UNIT
2
BR
CONDENSATION
FAN (W/C ONLY)
5
SWITCH
BK
POTENTIAL
BL
1
1
3
START RELAY
WH
2
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C ONLY)
WH
WATER DUMP
VALVE
BR
CO
450 PSIG
WH
BK
BL
BL
WATER DUMP
SWITCH
1
BR
3
2
CONDENSER
FAN MOTOR
(A/C ONLY)
YL
BK
M
Water
Dump
Valve
D-15
BK
GR
D-13
YL
D-14
GR
WH
RH Evap.
Switch
7
5
8
6
Relay
RH Evap.
N
S
BL
Water
Pump
4
2
3
1
GR
WH
D-12
YL
D-10
D-11
GR
Hot Gas
Valve
(White Lead)
Condenser
Sensor
LH Evap.
WH
230V
WH
RD
Condenser
Plug
Voltage
Selector
Switch
See note 1
PUMP
CORD
Suction
Plug
D-6
GR
Condenser
Fan
Suction Line
Sensor
(Brown Lead)
115V
HOT GAS
SOLENOID
Test
Plug
RD
D-5
Error
Options
Plug
M
Transformer
Adjustable Ice
Thickness Pot.
BL
WATER PUMP
Micro
Processor
To Stacked
Unit
(if required)
Stacking
Cable
Plug
Manual
Harvest
Switch
IAC 522 & IWC 522
IAC 530 & IWC 530
BL
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C UNITS.
12/1/94
Rev 3/4/96
58
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
RD
LIQUID LINE
SOLENOID
(R/C ONLY)
RD
RD
COMPRESSOR
RUN
COMPRESSOR
START
GR
BK
BK
RD
CONTACTOR
COMPRESSOR
R
CAPACITOR
CAPACITOR
RD
See note 2
RD
BR
C
S
35 mfd
370 VAC
YL
EXTERNAL
COMPRESSOR
OVERLOAD
145-174 mfd
250 VAC
BK
BK
BK
YL
BK
RD
OR
RD
M
CRANKCASE
HEATER
(RC ONLY)
RD
2
BR
5
BK
BL
CONDENSATION FAN
(W/C & R/C ONLY)
POTENTIAL
1
START RELAY
BR
MANUAL RESET
HIGH PRESSURE CONTROL
(W/C & RC ONLY)
RD
WATER DUMP
VALVE
CO
450 PSIG
BR
WH
BK
RD
BL
UNIT
SWITCH
WATER DUMP
SWITCH
1
BR
3
2
BL
M
BK
YL
BK
CONDENSOR
FAN MOTOR
(A/C ONLY)
Water
Dump
Valve
WH
D-15
GR
D-13
YL
D-14
GR
RH Evap.
Switch
7
5
8
6
Relay
BL
RH Evap.
N
S
Water
Pump
4
2
3
1
GR
RD
RD
D-10
YL
D-12
LH Evap.
Switch
WH
WH
D-11
GR
N
S
LH Evap.
Hot Gas
Valve
230V
Voltage
PUMP
CORD
(White Lead)
Condenser Sensor
Condenser
Plug
See note 1
Selector
Switch
D-6
GR
Suction
Plug
Condenser
Fan
HOT GAS
SOLENOID
Suction Line
Sensor
(Brown Lead)
115V
Test
Plug
RD
D-5
M
WATER PUMP
Error
BL
Options
Plug
Transformer
Adjustable Ice
Thickness Pot.
Micro
Processor
To Stacked
Unit
(if required)
Stacking
Cable
Plug
Manual
Harvest
Switch
IAC 830, IWC 830 & IRC 830
IAC 630, IWC 630 & IRC 630
BL
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTER USED ONLY ON W/C & R/C UNITS.
NOTE 2: CAPACITORS USED ON 630 BRISTOL COMPRESSOR:
RUN CAP, 25mfd 440 VAC
START CAP. 161-193mfd 250 VAC
12/1/94
Rev 3/4/96
59
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
RD
LIQUID LINE
SOLENOID
(R/C ONLY)
RD
RD
COMPRESSOR
RUN
CAPACITOR
COMPRESSOR
START
CAPACITOR
GR
BK
BK
RD
CONTACTOR
COMPRESSOR
R
RD
SEE NOTE 2
RD
BR
C
S
40 mfd
370 VAC
YL
EXTERNAL
COMPRESSOR
BK
189-227 mfd
330 VAC
BK
YL
RD
RD
BK
OVERLOAD
OR
RD
M
2
BR
5
BK
CRANKCASE
HEATER
(RC ONLY)
CONDENSATION
FAN (W/C & R/C)
POTENTIAL
START RELAY
BL
1
BK
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C & R\C)
BK
RD
WATER DUMP
VALVE
CO
450 PSIG
WH
BK
BL
CONDENSER
FAN MOTORS
(A/C ONLY)
WATER DUMP
SWITCH
1
BR
BR
3
2
UNIT
SWITCH
RD
M
M
YL
BK
BK
BK
Water
Dump
Valve
BL
WH
D-15
GR
D-13
YL
D-14
GR
RH Evap.
Switch
7
5
8
Relay
BL
RH Evap.
6
N
S
Water
Pump
4
2
3
1
GR
D-10
YL
RD
RD
D-12
LH Evap.
Switch
WH
WH
N
S
D-11
GR
LH Evap.
Hot Gas
Valve
230V
Voltage
PUMP
CORD
(White Lead)
Condenser Sensor
Condenser
Plug
See note 1
Selector
Switch
Suction
Plug
D-6
GR
Condenser
Fan
HOT GAS
SOLENOID
Suction Line
Sensor
(Brown Lead)
115V
Test
Plug
RD
M
D-5
Error
BL
Options
Plug
WATER PUMP
Transformer
Adjustable Ice
Thickness Pot.
Micro
Processor
To Stacked
Unit
(if required)
Stacking
Cable
Plug
Manual
Harvest
Switch
IAC 1230, IWC 1230 & IRC 1230
IAC 1030, IWC 1030 & IRC 1030
BL
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C & R/C UNITS.
2: CAPACITORS USED ON 1030 COMPRESSOR
RUN CAP. 37MFD 370V
START CAP. 145 - 174 MFD 250V
12/1/94
Rev 3/4/96
60
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
RD
LIQUID LINE
SOLENOID
(R/C ONLY)
RD
RD
COMPRESSOR COMPRESSOR
RUN
CAPACITOR
GR
BK
START
CAPACITOR
RD
CONTACTOR
COMPRESSOR
R
RD
RD
YL
BK
BK
BR
C
S
189-227 mfd
330 VAC
40 mfd
440 VAC
BK
EXTERNAL
COMPRESSOR
OVERLOAD
YL
2
RD
RD
M
UNIT
SWITCH
OR
RD
BR
CONDENSATION
FAN (W/C & R/C)
5
BK
BK
POTENTIAL
START RELAY
BL
1
BK
BR
CRANKCASE HEATER
(A/C & R/C ONLY)
RD
WATER DUMP
VALVE
RD
WH
BK
BL
WATER DUMP
SWITCH
1
BR
CO
450 PSIG
3
2
BL
M
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C & R/C)
BK
WH
YL
BK
CONDENSER
FAN MOTOR
(A/C ONLY)
BR
Water
Dump
Valve
D-15
WH
GR
D-13
YL
D-14
GR
RH Evap.
Switch
7
5
8
Relay
BL
RH Evap.
6
N
S
Water
Pump
4
2
3
1
GR
RD
RD
D-12
YL
D-10
LH Evap.
Switch
WH
WH
D-11
GR
N
S
LH Evap.
Hot Gas
Valve
230V
Voltage
PUMP
CORD
(White Lead)
Condenser Sensor
Condenser
Plug
See note 1
Selector
Switch
D-6
GR
Suction
Plug
HOT GAS
SOLENOID
Condenser
Fan
Suction Line
Sensor
(Brown Lead)
115V
Test
Plug
RD
D-5
M
Error
BL
Options
Plug
WATER PUMP
Transformer
Adjustable Ice
Thickness Pot.
Micro
Processor
To Stacked
Unit
(if required)
Stacking
Cable
Plug
Manual
Harvest
Switch
IAC 1448, IWC 1448 & IRC 1448
BL
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C & R/C UNITS.
12/1/94
Rev 3/4/96
61
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
CAPACITOR
2 mfd 440 VAC
RED
COLORED
BAND
M
BK
BK
CONDENSER
FAN MOTOR
GR
HEAT SHRINK TAPE
HEAT SHRINK
TAPE
FAN CYCLING
SWITCH
BK
RD
GR
HEAT SHRINK TAPE
CR800, CR1200, & CR1400 REMOTE CONDENSERS
208/230 VOLTS 60 HZ
12/1/94
Rev 3/4/96
62
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
AIR COOLED CONDENSER
FAN BLADES
FAN MOTOR
EVAPORATOR
HEAT EXCHANGER
WATER
FLOAT
VALVE
THERMOSTATIC
EXPANSION VALVE
WATER
DUMP VALVE
HOT GAS
SOLENOID
VALVE
FILTER/DRIER
WATER PUMP
S
HIGH SIDE
SERVICE
VALVE
LOW SIDE
SERVICE
VALVE
COMPRESSOR
REFRIGERATION AND WATER SYSTEMS
MODELS IAC227, IAC322, IAC330, IAC522, AND IAC530
MODELS IAC630, AND IAC830
MODEL IWCS227
Download from Www.Somanuals.com. All Manuals Search And Download.
AIR COOLED CONDENSER
FAN BLADES
EVAPORATOR
THERMOSTATIC
EXPANSION
VALVE
FAN MOTOR
FILTER/DRIER
HEAT EXCHANGER
WATER
DUMP VALVE
WATER PUMP
WATER
FLOAT VALVE
HOT GAS
SOLENOID VALVE
HIGH SIDE
SERVICE
VALVE
LOW SIDE
SERVICE
VALVE
COMPRESSOR
THERMOSTATIC
EXPANSION
VALVE
EVAPORATOR
Refrigeration and water system
Models IAC1030, IAC1230, and IAC1448
August 3, 1994
Download from Www.Somanuals.com. All Manuals Search And Download.
WATER REGULATING
VALVE
WATER-COOLED CONDENSER
WATER INLET
EVAPORATOR
HEAT EXCHANGER
WATER
FLOAT
VALVE
S
THERMOSTATIC
EXPANSION VALVE
WATER
DUMP VALVE
HOT GAS
SOLENOID
VALVE
FILTER/DRIER
WATER PUMP
PRESSURE SWITCH
S
HIGH SIDE
SERVICE
VALVE
LOW SIDE
SERVICE
VALVE
Refrigeration and Water Systems
Models IWC322, IWC330, IWC522, and IWC530
Models IWC603, and IWC830
Model IWCS227
COMPRESSOR
August 3, 1994
Download from Www.Somanuals.com. All Manuals Search And Download.
WATER REGULATING
VALVE
W
WATER INLET
EVAPORATOR
THERMOSTATIC
EXPANSION VALVE
WATER-COOLED CONDENSER
S
HEAT EXCHANGER
WATER
DUMP VALVE
HOT GAS
SOLENOID
VALVE
WATER
FLOAT
VAVLE
WATER PUMP
FILTER/DRIER
S
HIGH SIDE
SERVICE
VALVE
LOW SIDE
SERVICE
VALVE
PRESSURE
SWITCH
COMPRESSOR
THERMOSTATIC
EXPANSION VALVE
EVAPORATOR
REFRIGERATION AND WATER SYSTEM
MODELS IWC1030, IWC1230 AND 1WC1448
AUGUST 3, 1994
Download from Www.Somanuals.com. All Manuals Search And Download.
PRESSURE SWITCH
FAN BLADES
HEAD
PRESSURE
CONTROL
EVAPORATOR
THERMOSTATIC
EXPANSION VALVE
FAN MOTOR
S
COUPLINGS
VALVES
REMOTE CONDENSER
HOT GAS
WATER
SOLENOID
VALVE
RECEIVER
LIQUID SOLENOID
VALVE
FILTER/DRIER
DUMP VALVE
S
WATER
FLOAT
VALVE
WATER PUMP
S
PRESSURE SWITCH
HEAT EXCHANGER
SERVICE VALVE
HIGH SIDE
SERVICE
VALVE
LOW SIDE
SERVICE
VALVE
CHECK
VALVE
COMPRESSOR
REFRIGERATION AND WATER SYSTEMS
MODELS IRC630 AND IRC830
AUGUST 3, 1994
Download from Www.Somanuals.com. All Manuals Search And Download.
PRESSURE SWITCH
FAN BLADES
HEAD
PRESSURE
CONTROL
EVAPORATOR
THERMOSTATIC
EXPANSION VALVE
FAN MOTOR
COUPLINGS
VALVES
REMOTE CONDENSER
FILTER/DRIER
WATER
DUMP
HOT GAS
SOLENOID
VALVE
RECEIVER
LIQUID SOLENOID
VALVE
VALVE
WATER
FLOAT
VALVE
WATER PUMP
PRESSURE SWITCH
HEAT EXCHANGER
SERVICE VALVE
HIGH SIDE
SERVICE
VALVE
LOW SIDE
SERVICE
VALVE
CHECK
VALVE
EVAPORATOR
COMPRESSOR
THERMOSTATIC
EXPANSION VALVE
REFRIGERATION AND WATER SYSTEM
MODELS IRC1030, IRC1230 AND IRD1448
AUGUST 3, 1994
Download from Www.Somanuals.com. All Manuals Search And Download.
PRESSURE SWITCH
FAN BLADES
HEAD PRESSURE
CONTROL
FAN MOTOR
COUPLINGS
VALVES
REMOTE CONDENSER
MODELS CR800, CR1200, AND CR1400
AUGUST 5, 1994
Download from Www.Somanuals.com. All Manuals Search And Download.
“I” Series “Remote”
Ice Machine
12/1/94
Rev 3/4/96
166240004
70
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS REMOTE CONDENSERS
1/4-20 SCREW
UNIT
LEG
BRACE
LEG
1. Follow the standard installation instructions supplied with cuber. Do not hook cuber into the power source
until the remote condenser and line set installation is complete.
2. Assembly of remote condenser (see drawing):
A. Assemble legs to base panel. Install leg supports on legs.
B. Locate the remote condenser in a well–ventilated area on the roof away from other refrigeration equip-
ment’s condenser discharge air flow.
C. Use the mounting holes provided to secure the remote condenser to the roof. Seal over heads of bolts
or fasteners with tar or pitch to prevent entrance of moisture.
REMOTE CONDENSER
LEG
LEG SUPPORT
3. Remote condenser electrical hook-up:
A. Connect remote condenser to a power source (208/230VAC, 60 HZ) separate from the cuber. An ex-
ternal disconnect switch must be used.
B. Make sure the electrical connections follow all local and
national codes.
C. DO NOT turn condenser on until cuber install and refrigerant line connections are complete!
D. Never wire condenser into cuber section. The condenser is an independent electrical connection.
E. Fan motor will not start until pressure rises to 205 PSIG [14.07 Bars] closing fan cycling switch.
12/1/94
Rev 3/4/96
71
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
F. The condenser fan may cycle off during the harvest cycle – this would be normal.
NOTE: Installing an IMI Cornelius remote cuber with other than an IMI Cornelius remote condenser
and line set may be reason to void the cuber warranty.
LIQUID
REFRIGERANT
LINE
DISCHARGE
LINE
CORRECT
4. Each condenser and cuber is connected with two (2) *pre-charged lines.
A. The pre-charged lines are ordered separately from the condenser to suit each individual application.
B. The pre-charged line lengths are 20 feet [6.096 meters], 35 feet [10.66 meters] and 55 feet [16.76 me-
ters].
NOTE
(Pre-charged is defined as a vapor holding charge – not a portion of the system charge.)
5. Installation of line kits (see drawing). Remove the tubing from the carton. Carefully uncoil the lines so the
tubing doesn’t become kinked, and route lines to cuber and condenser.
6. Keep line-set as short as possible. Place a 3-foot service loop behind cuber to allow for rear service
should it ever be required.
12/1/94
Rev 3/4/96
166240004
72
Download from Www.Somanuals.com. All Manuals Search And Download.
REMOTE CONDENSER LOCATION
1. Physical Line-Set Length: 55 Ft. Maximum [16.764 meters]
The ice machine compressor must have the proper oil return. Line-set rises, drop, or horizontal runs great-
er than the maximum distance allowed will exceed the compressor start-up and pumping design limits, and
will result in poor oil return to the compressor.
Line-Set Rise: 35 Ft. Maximum [10.66 meters]
Line-Set Drop: 15 Ft. Maximum [4.57 meters]
2. Calculated Line-Set Distance: 100 Ft. [30.48 meters]
To prevent the combination of rises, drops and horizontal runs exceeding the compressor start-up and
pumping design limit, the following calculations should be made:
NOTE: Max. line–set for IMI Cornelius cubers is 55 ft. Do not confuse line length with calculated line
distance
B
A
C
B
B - LINE LENGTH 35 FT.: EXAMPLE
C - (DROP) CONDENSER LOWER THAN EVAP. 15 FT.: MAX.
A - (RISE) CONDENSER HIGHER THAN EVAP.
MAX. 35 FT.
B - LINE LENGTH 15 FT.: EXAMPLE
Maximum Line-Set Distance Formula
A. Measured rise
B. Measured drop
x 1.7=
x 6.6=
Calculated Rise 35 ft. Max) [10.66 meters]
Calculated Drop 15 ft. Max) [4.57 meters]
C. Measured Horizontal Distance = actual measurement.
D. Total Calculated Distance (A+B+C)=Total Calculated Distance (100 ft. Max.) [30.48 meters]
Examples:
a. Insert measured rise (R) into the formula and multiply it by 1.7 to get a calculated rise.
example: A condenser located 15 ft. [4.572 meters] above the ice machine has a 25.5 ft. [8.874
meters] calculated total (15 ft. x 1.7 = 25.5).
H
AIR
FLOW
R
b. Insert measured drop (D) into formula and multiply by 6.6 to get a calculated drop.
example: A condenser located 8 ft. [2.438 meters] below the ice machine has a 52.8 ft. [16.093
meters] calculated total (8 ft. x 6.6 = 52.8 ft.).
12/1/94
Rev 3/4/96
73
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
COMBINATION OF
DROP(S)
WITH HORIZONTAL
H
D
AIR
FLOW
c. Insert measured horizontal distance into formula. No calculation is necessary. (6 ft.) [1.828 me-
ters].
d. Add the calculated rise, calculated drop, and horizontal distance together to get the total calcu-
lated distance (25.5 + 52.8 + 6) equals 84.3 ft. [25.694 meters]. If 100 ft. [30.48 meters] total cal-
culated distance is exceeded, the condenser must be moved to a new location which permits
proper equipment operation.
COMBINATION OF RISE AND
DROP(S)WITH HORIZONTAL
H
R
D
AIR
FLOW
CAUTION: If a line-set rise is followed by a line-set drop, a second line-set rise cannot be
made. Or If a line-set drop is followed by a line-set rise, a second line-set drop cannot be
made.
3. Lengthening or Reducing the Line-Set Lengths
In most cases, by routing the line-set properly, shortening will not be necessary (refer to illustration). How-
ever, when shortening or lengthening is required, do so before connecting the line-set to the ice machine or
the remote condenser. This prevents the loss of refrigerant from the ice machine or the condenser.
The quick connect fittings on the line-sets are equipped with Schrader Valves. Use these valves to recover
any vapor charge from the line-set. When lengthening or shortening lines, apply good refrigeration practic-
es and insulate new tubing. Do not change the tube sizes. Evacuate the lines and place approximately 5
oz. of
vapor refrigerant charge in each line.
SCHRADER
VALVE
PARENT
METAL
SEAL
INTERMEDIATE
SEAL
4. Connection of Line-Set
A. Remove the plastic caps from the line-set, the condenser, and the ice machine.
B. Apply refrigeration oil to the threads on the quick connect couplers before connecting them to the con-
denser.
C. Carefully thread the female fitting onto the condenser or ice machine by hand.
D. Using the proper size wrench, tighten the couplings until they bottom out. Turn an additional 1/4 turn
to ensure proper brass-to-brass seating.
12/1/94
Rev 3/4/96
166240004
74
Download from Www.Somanuals.com. All Manuals Search And Download.
E. Check all fittings for leaks.
5. Final Installation:
A. Remove grill from the right-hand side panel of cuber.
B. Turn service port on receiver tank to open position releasing refrigerant to the balance of the system.
C. Leak check line-set connections at cuber and condenser.
D. Replace grill.
E. Connect cuber to power source.
F. Make sure electrical connections follow all local and national codes.
6. Start Up:
A. Use standard procedures from cuber installation instructions.
B. After the cuber is running, check the remote condenser and verify that the condenser fan is running.
CAUTION: Once the refrigerant lines are connected, the seal is broken in the fittings. If the
lines are removed or loosened from the cuber or remote condenser, the refrigerant charge
will be discharged to the atmosphere. DISCHARGING TO THE ATMOSPHERE IS IN
VIOLATION OF THE CLEAN AIR ACT OF JULY, 1992.
12/1/94
Rev 3/4/96
75
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
ICE CUBER SPECIFICATION
MODEL
IRC630
IRC830
IRC1230
IRC1448
UNIT
Volts
Phase
208/230 + 10%, –5% 208/230 +10%, –5%
208/230 +10%, –5%
208/230 +10%, –5%
1
60
1
60
1
60
1
60
Hertz
No. Wires
MIN. CIRCUIT
Amps
2+ground
2+ground
2+ground
2+ground
20
20
20
20
25
25
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps
REFRIGERANT
Type
20
20
R404a(HP62)
170
R404a(HP62)
170
R404a(HP62)
210
R404a(HP 62)
250
Weight (oz)
Weight (g)
COMPRESSOR
Volts
4820
4820
5954
7088
230
1
230
1
230
1
230
1
Phase
Hertz
60
69
8.8
60
60
60
LRA
61
96
95.6
23.9
RLA
12.5
13.5
AIR CIRCULATION FAN MOTOR
Volts
Phase
230
1
230
1
230
1
230
1
Hertz
60
0.36
6
60
0.36
6
60
0.36
6
60
0.36
6
Amps Running
Watts
WATER PUMP
Volts
230
1
230
1
230
1
230
1
Phase
Hertz
60
60
60
60
Amps Running
HP
0.5
1/30
0.5
1/30
0.5
1/30
0.5
1/30
REMOTE CONDENSER SPECIFICATION
MODEL
CR800
230
1
CR1200
CR1400
Volts
230
1
230
1
Phase
Hertz
60
1.0
1/6
60
1.0
1/6
60
1.0
1/6
Amps
Output, HP
Max. fuse size, Amps (HVAC circuit breaker
required)
20
20
20
12/1/94
Rev 3/4/96
166240004
76
Download from Www.Somanuals.com. All Manuals Search And Download.
HEAD PRESSURE CONTROL [HEADMASTER]
receiver
receiver
discharge
discharge
condenser
condenser
above 70°F
normal
below 70°F by-pass
The Cornelius “I” series remote systems use an Alco Head Pressure Control, normally referred to as a head-
master. This control is mounted in the remote condenser with a fan cycling control switch. Using both these
controls gives the system positive operation under a wide range of condensing temperatures.
The cycling control starts the fan at 270 PSI and stops it at 205 PSI allowing a positive efficient operation at the
high temperature operating ranges.
The headmaster controls the operation when the condensing temperature drops below 70°F. The “I” series re-
frigerant charge is HP - 62 [R - 404A] and the headmaster dome charge setting is 200 PSI of nitrogen pressure
making it stable under the low temperature operating range down to - 20°F.
The normal flow pattern through the headmaster is from the condenser port to the receiver port. When this flow
pattern is unable to maintain a receiver outlet pressure equal to or above the dome pressure setting of the
valve, the dome pressure will force the valve portage to change closing the condenser port and opening the by-
pass port from the compressor discharge line. This allows the high pressure vapor from the discharge port to
“buck” the receiver pressure back up. With the condenser port closed, the refrigerant is backed up in the con-
denser, basically reducing the condenser size, assisting in maintaining the discharge portage flow and increas-
ing the head pressure.
Remember, sense of touch to the lines of the headmaster will determine the flow path the headmaster is in,
condenser to receive, or bypass to receiver.
High side gauge installed at the receiver outlet valve will determine if the headmaster is functioning to maintain
the proper operating pressure.
In the event the control appears to be “stuck in bypass”, the pressure drop across the headmaster must be
measured. With a gauge installed at the receiver outlet valve and the high side service valve, the pressure dif-
ference at these two points must be less than the 15 PSI. The three most common causes of an excessive
pressure drop are shortage of refrigerant, kinked remote lines, and excessive line length.
Eliminate refrigerant shortage first. Add refrigerant in two-pound increments (not to exceed six pounds) to
determine if it corrects the pressure drop. If pressure drop is not corrected, inspect line set for sharp bends or
kinks and correct as required. If adding refrigerant does not correct continued (bypass) condition and line set is
not damaged, replace headmaster.
12/1/94
Rev 3/4/96
77
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
REMOTE SYSTEM EVACUATION/RE-CHARGE
All field repairs to the sealed system must start with a total discharge of the system following the requirements
of the Clean Air Act of July, 1992.
Proper evacuation of the total remote system will require a three (3) point hook-up of your manifold and hose
set, (see drawing):
Point #1 - Cuber receiver outlet valve
Point #2 - Cuber high side service valve
Point #3 - Cuber low side service valve
Evacuation:
1. With cuber power supply turned “OFF” disconnect and insulate all 3 compressor leads at the compressor.
Turn power supply on, place power switch in the “on” position. This will energize (open) the Liquid Line so-
lenoid allowing evacuation of the Liquid Line between the solenoid and the expansion valve(s).
2. Evacuate system to 200/250 microns or less. At this point, there should be a holding test of five(5) minutes.
You may expect a slight loss of vacuum as normal. A rapid rise to normal atmospheric pressure indicates
moisture still present in the system. On a “wet” system, it will prove beneficial to use heat lamps to warm
the compressor dome and evaporator surface during evacuation.
3. Turn cuber power switch OFF. Reconnect compressor leads.
4. *After proper evacuation hold test has been performed, the refrigerant charge should be “dumped” into the
receiver until the pressure equalizes, stopping the flow. Do not try to throttle the refrigerant flow. Doing so
will allow system pressure to balance too soon. The high-side service valve should be closed and the bal-
ance of the charge fed slowly through the suction side service valve with the compressor operational. Con-
trol the feed rate at no faster than four (4) ounces [113.g] per minute to ensure the compressor oil does not
become too saturated with refrigerant resulting in a loss of compressor lubrication.
5. All refrigerant re-charging must be weighed into the system, utilizing an electronic charging scale. DO NOT
attempt to recharge the system by sight glass, system pressure, amperage, frost line or sweat patterns.
6. Always leak check entire system after recharge.
CAUTION: Before programming the electronic scales to “dump” the charge, de-energize
the liquid line solenoid, close the shut-off valve on vacuum pump and low side of the
manifold set.
2ND STAGE CHARGING
1ST STAGE CHARGING
MANIFOLD SET
EVACUATION
MANIFOLD SET
COMPRESSOR OPERATING
OPEN
OPEN
MANIFOLD SET
OPEN
CLOSED
CLOSED
OPEN
OPEN
CLOSED
CLOSED
RECEIVER
RECEIVER
HIGH SIDE
SERVICE
VALVE
HIGH SIDE
SERVICE
VALVE
RECEIVER
HIGH SIDE
SERVICE
VALVE
OPEN
OPEN
CLOSED
LOW
SIDE
SERVICE
VALVE
LOW
SIDE
SERVICE
VALVE
LOW
SIDE
SERVICE
VALVE
RECEIVER
OUTLET
VALVE
RECEIVER
OUTLET
VALVE
RECEIVER
OUTLET
VALVE
OPEN
CHARGING
CLOSED
OPEN
CHARGING
CYLINDER
CHARGING
CYLINDER
CYLINDER
OPEN
CLOSED
CLOSED
VACUUM
PUMP
VACUUM
PUMP
VACUUM
PUMP
OPEN
CLOSED
OPEN
ELECTRONIC
ELECTRONIC
SCALE
ELECTRONIC
SCALE
SCALE
12/1/94
Rev 3/4/96
166240004
78
Download from Www.Somanuals.com. All Manuals Search And Download.
THIS PAGE LEFT BLANK INTENTIONALLY
79
166240004
Download from Www.Somanuals.com. All Manuals Search And Download.
IMI CORNELIUS INC.
CORPORATE HEADQUARTERS:
One Cornelius Place
Anoka, Minnesota 55303-6234
(763) 421-6120
(800) 238-3600
12/1/94
Rev 3/4/96
166240004
80
Download from Www.Somanuals.com. All Manuals Search And Download.
|