POWERPATH™ NAC POWER SUPPLIES
PS-EXP
PS-8
PS-6
Description
The Wheelock Series PS-6 and PS-8 are 24VDC, filtered and
regulated, supervised remote power supply/battery chargers are
used for supervision and expanded power driving capability of Fire
Alarm Notification Appliance Circuits. The PS-6 provides 6 amps of
power distributed across 4 outputs, while the PS-8 provides 8 Amps
across 4 output. In addition the PS-8 provides additional room in
the chassis for accessories like an Addressable Control Module, with
mounting studs.
The PS-6 and PS-8 Power Supplies are UL Listed under UL
Standard 864, 9th Edition to be used with any 24 volt Listed
Regulated notification appliances. They include the capability
to synchronize Wheelock strobes and horns and to silence the
horn signal when horn/strobes are operating on two wires.
Approvals
• Approvals Include: UL Standard 864, 1481, California State
Fire Marshal (CSFM), Factory Mutual (FM)
• Compliant with NFPA 72
The Power Supplies may be connected to any 12V or 24V (FWR or
DC) Fire Alarm Control Panel (FACP) by using a Notification Appliance
Circuit (NAC) or a “Dry Contact”. Primary applications include NAC
expansion (supports ADA requirements) and auxiliary power to
support system accessories. This unit provides filtered and regulated
24VDC, up to four (4) Class “B”, two (2) Class “A”, or two (2) Class
“B” and one (1) Class “A” Notification Appliance Circuits. With the
optional plug-in PS-EXP module the unit supports (8) Class “B” or
(4) Class “A” Notification Appliance Circuits. Additionally, an auxiliary
power output of 2.5 Amps (disconnected upon AC power loss or an
alarm condition) or up to 0.240 A of constant power on the PS-8 and
0.075 A of constant power on the PS-6.
Inputs
• 120VAC, 50/60Hz, 4.25 Amps (PS-6/8) and 5.32 Amps
(PS-8) Operating Power in Alarm
• 240VAC, 60Hz, 2.42 Amps (PS-6E and 3.22 Amps (PS-8E) ‘
Operating Power in Alarm
• 24VDC Battery Backup Connection
• Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA)
FWR or DC
The Wheelock Power Supplies can accommodate 7 or 12 AH batteries
inside its lockable chassis. Using an external battery cabinet it can
charge up to 33 AH batteries (pending UL testing). Two FACP NAC
circuits or two “Dry” contact initiating circuits can be connected to the
inputs. These inputs can then be directed to control supervision and
power delivery to any combination of the four (4) outputs. Each output
is rated at 3.0 Amps (Class “B”) or (Class “A”) and can be programmed
to generate a steady or Code 3 Temporal Horn sound and a strobe
output under alarm condition. Total load for the PS-6 and PS-8 NAC
circuits must not exceed the power supplies rated output.
• Two (2) “Dry”Contact initiating Circuits
• Accepts two (2) Class “A”or two (2) Class “B”circuit inputs
• Built in battery charger for sealed lead acid or gel type
batteries
Outputs
• NAC outputs are 24VDC, 3.0 Amps each, power limited
• 8 Amps on PS-8 and 6 Amps on the PS-6 total alarm current
The Power Suppliesunder non-alarm condition provides independent
supervision for Class “A” and Class “B” FACP NAC circuits. In the
event of circuit trouble, the FACP will be notified via the POWERPATH
steered input (IN1 or IN2). In addition there are two sets of trouble
reporting terminals, one used for AC power loss reporting and the
other for all troubles. The AC power loss reporting, on the common
trouble terminals and on IN1 or IN2, can be delayed for either 30
seconds or 170 minutes. The AC power loss terminals will always
report the trouble within 1 second after loss of AC power.
U
L
®
...Features continued on next page
Download from Www.Somanuals.com. All Manuals Search And Download.
POWERPATH™ Operating Modes (refer to Installation Manual):
Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening
on DRY1 or DRY2. The unit returns to standby mode when the input is deactivated.
Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock audible and strobe notification
appliances. Audibles can also be silenced in this mode while the strobes continue to flash.
In>Out Sync Mode: Accepts a synchronization signal on the input to provide a coded output or synchronized output. This signal
may come from a FACP, another POWERPATH or aWheelock DSM synchronization module. Caution: Do not use strobes on coded
output circuits.
True Input Follower Mode: Accepts a coded signal on the input to provide a coded output with the same timing as the
input. The signal may come from a FACP, another POWERPATH or other coded source. Caution: Do not use strobes
on coded output circuits.
Temporal Mode: Codes the output voltage in a code-3 temporal pattern to drive audible appliances such as horns,
bells or chimes. Caution: Do not use strobes on coded output circuits.
Specifications and Ordering Information
Order
Code
Approvals
CSFM FM
Model Number
Input Voltage/Current
UL
X
PS-6
105530
100257
105531
105830
105083
105084
105534
105527
6 amp, red enclosure
6 amp, black enclosure
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PS-6B
X
X
X
X
X
X
X
PS-8
8 amp, red enclosure
PS-8B
8 amp, black enclosure
PS-6EXP
6 amp power supply with preinstalled expansion module
8 amp power supply with preinstalled expansion module
4 class B or 2 class A expansion module
Field upgrade kit for models prior to January 2010#
Input Voltage and Current
PS-8EXP
PS-EXP
PS-EXP-RETRO
Input Circuit
Input voltage Range
Input Current @ 12 VDC
X= Approved
*= Pending
#=Contact Technical
Support for additional
inforamation on upgrade
options
8 to 33 VDC
0.005 amps
Input Current @ 24 VDC
0.005 amps
Output Circuit
Output Voltage and Current
Four (4) Class B or
Two (2) Class A or
24 VDC @ up to 3 amps per curcuit
One (1) Class A and Two (2) Class “B”or
8 Class B or 4 Class A
(optional PS-EXP module necessary)
Continuous duty up to 3 Amps per circuit, up to 4 Amps maximum per panel
Standby Current
Alarm Current
0.129 Amps
0.129 Amps
Primary PS-6 (120 VAC models)
Primary PS-8 (120VAC models)
Primary PS-6E (240 VAC models)
Primary PS-8E (240 VAC models)
Secondary Power Charging Capacity
105 to 130 VAC, 50/60 Hz @ 4.25 Amps
105 to 130 VAC 50/60 Hz @ 5.32 Amps
210 to 260 VAC, 50/60 Hz @ 2.42 Amps
210 to 260 VAC 50/60 Hz @ 3.22 Amps
32 Amp hours @ 0.750 Amps per hour
Enclosure can house up to two 12 AH batteries
Aux Output
CP Mode
PS-6 up to 75 mA
PS-8 up to 250 mA
Comments
MP Mode
Model
2.5A during non alarm
Dimensions
Weight
PS-6/PS-6B
17”H x 13”W x 3.5”D
11.5lbs. (Ship) 9.4lbs (Unit)
Small profile
PS-8/PS-8B
17”H x 15”W x 5.5”D
17.7lbs (Ship) 15.6lbs (Unit) Additional room for modules
Plugs into main pcb on all
PS-EXP
4.3”H x 3.7”W x 1”D
1lb. (Ship & Unit)
models
Download from Www.Somanuals.com. All Manuals Search And Download.
Architects and Engineers Specifications
The power supply shall be Wheelock POWERPATH™ Series PS-8, or equivalent. The unit shall be stand alone power supply intended
for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC). The unit shall be UL 864 Listed for
power limited operation of outputs and comply with NFPA 70 (NEC), article 760.
The power supply shall support a full 8A of notification power even if the battery is in a degraded mode and only AC power is
connected.
The power supply shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a
“Dry contact” opening. The units shall be 8 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall
operate over the voltage range of 8 to 33 VDC or FWR. The primary application of the unit shall be able to expand fire alarm system
capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories
or functions. The power supply shall provide four Class “B”, two Class “A”, or two Class “B” and one Class “A” NAC circuit(s). Eight
Class “B” or Four Class “A” circuits shall be available with an optional PS-EXP module. The PS-8 unit shall supply up to 240 mA of
auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm.
The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at maximum rate of 0.750 Amps per
hour.
Input activation options shall be from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability of
being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class “B”
applications or 3 amperes each for Class “A”. The outputs shall be programmable to generate a steady or Temporal (Code 3) output
and or a synchronized strobe or horn output. The power supply shall provide independent loop supervision for either Class “A” or Class
“B” FACP NAC circuits and shall have the capability to “steer” all alarm or trouble conditions to either incoming NAC circuit. The units
shall have common trouble terminals. The power supply shall be powered from a 120 VAC source with a current consumption of xx
amperes max. The unit shall incorporate short circuit protection with auto reset. The power supply shall incorporate a built in battery
charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure. The charger
shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby
current for battery back up shall be 0.129 Amps max. The power supply shall have the ability to latch trouble LED’s so the circuit in
trouble can be identified. The cabinet dimensions shall be 17”H x 15”W x 5.5”D.
The power supply shall be Wheelock POWERPATH™ Series PS-6, or equivalent. The unit shall be stand alone power supply intended
for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC). The unit shall be UL 864 Listed for
power limited operation of outputs and comply with NFPA 70 (NEC), article 760.
The power supply shall support a full 6A of notification power even if the battery is in a degraded mode and only AC power is
connected.
The power supply shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a
“Dry contact” opening. The units shall be 6 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall
operate over the voltage range of 8 to 33 VDC or FWR. The primary application of the unit shall be able to expand fire alarm system
capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories
or functions. The power supply shall provide four Class “B”, two Class “A”, or two Class “B” and one Class “A” NAC circuit(s). Eight
Class “B” or Four Class “A” circuits shall be available with an optional PS-EXP module. The PS-6 unit shall supply up to 200 mA of
auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm.
The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at a maximum rate of 0.750 Amps
per hour.
Input activation options shall be from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability of
being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class “B”
applications or 3 amperes each for Class “A”. The outputs shall be programmable to generate a steady or Temporal (Code 3) output
and or a synchronized strobe or horn output. The power supply shall provide independent loop supervision for either Class “A” or Class
“B” FACP NAC circuits and shall have the capability to “steer” all alarm or trouble conditions to either incoming NAC circuit. The units
shall have common trouble terminals. The power supply shall be powered from a 120 VAC source with a current consumption of xx
amperes max. The unit shall incorporate short circuit protection with auto reset. The power supply shall incorporate a built in battery
charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure. The charger
shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby
current for battery back up shall be 0.130 Amps max. The power supply shall have the ability to latch trouble LED’s so the circuit in
trouble can be identified. The cabinet dimensions shall be 17”H x 13”W x 3.5”D.
WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS
PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLA-
TION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accor-
dance with Wheelock Inc. standard terms and conditions.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
1 YEAR WARRANTY