Portable Chillers
Series 1 Water-Cooled (W1) and
Air-Cooled Models (A1) withTIC Control
Installation
Operation
Maintenance
Troubleshooting
The Conair Group, Inc.
One Conair Drive
Pittsburgh, PA 15202
Phone: (412) 312-6000
Fax: (412) 312-6227
Instant Access
Parts and Service
(800) 458-1960
(814) 437-6861
UGH016/0500
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION . . . . . . . . . . . . . . . . . . .1-1
TABLE OF
CONTENTS
Purpose of the User Guide . . . . . . . . . . . . . . . . . . . . . . . . .1-2
How the Guide is Organized . . . . . . . . . . . . . . . . . . . . . . .1-2
Your Responsibilities as a User . . . . . . . . . . . . . . . . . . . . .1-2
ATTENTION: Read this so no one gets hurt . . . . . . . . . . .1-3
DESCRIPTION . . . . . . . . . . . . . . . . . . . .2-1
What is the Portable Chiller? . . . . . . . . . . . . . . . . . . . . . . .2-2
Typical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
How it Works: Water-cooled Portable Chiller . . . . . . . . . .2-4
How it Works: Air-cooled Portable Chiller . . . . . . . . . . . .2-6
Portable Chiller Features . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
Pump Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-12
INSTALLATION . . . . . . . . . . . . . . . . . . . .3-1
Unpacking the Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Warnings and Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
Preparing for Installation . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
Making Process Plumbing Connections . . . . . . . . . . . . . . .3-5
Filling the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
Checking Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . .3-8
Connecting the Main Power Source . . . . . . . . . . . . . . . . . .3-9
Checking Electrical Connections . . . . . . . . . . . . . . . . . . .3-10
Initially Starting the Chiller . . . . . . . . . . . . . . . . . . . . . . .3-11
Stopping the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-12
OPERATION . . . . . . . . . . . . . . . . . . . . . .4-1
TIC Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-2
Before Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-3
Starting/Stopping the Chiller . . . . . . . . . . . . . . . . . . . . . . .4-4
Changing Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5
Changing the Setpoint Temperature . . . . . . . . . . . . . . . . . .4-6
Changing Temperature Scale . . . . . . . . . . . . . . . . . . . . . . .4-7
Changing to Auto Tune Mode . . . . . . . . . . . . . . . . . . . . . .4-7
Setting the To Process Low Limit . . . . . . . . . . . . . . . . . . .4-8
UGH016/0500
Series 1 Portable Chillers, TIC Control
i
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE . . . . . . . . . . . . . . . . . . . .5-1
Maintenance Features . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-2
Warnings and Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3
Preventative Maintenance Schedule . . . . . . . . . . . . . . . . . .5-4
Checking the Refrigerant Charge . . . . . . . . . . . . . . . . . . . .5-6
Cleaning the Evaporator or Water-cooled Condenser . . . . .5-7
Cleaning the Air-cooled Condenser . . . . . . . . . . . . . . . . . .5-8
Checking Electrical Connections . . . . . . . . . . . . . . . . . . . .5-9
Checking Reservoir Level . . . . . . . . . . . . . . . . . . . . . . . .5-10
TABLE OF
CONTENTS
TROUBLESHOOTING . . . . . . . . . . . . . . . .6-1
Before Beginning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-2
A Few Words of Caution . . . . . . . . . . . . . . . . . . . . . . . . . .6-2
Identifying the Cause of a Problem . . . . . . . . . . . . . . . . . .6-3
Answering an Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-4
Control Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-5
Mechanical Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Checking and Replacing Switches . . . . . . . . . . . . . . . . . .6-15
Replacing the Contactor . . . . . . . . . . . . . . . . . . . . . . . . . .6-16
Checking and Replacing the RTD . . . . . . . . . . . . . . . . . .6-17
Replacing the Temperature Controller (TIC) . . . . . . . . . .6-18
Replacing Overload Modules . . . . . . . . . . . . . . . . . . . . . .6-19
Replacing Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-20
Removing Pump Components . . . . . . . . . . . . . . . . . . . . .5-21
Checking the Pressure Switches . . . . . . . . . . . . . . . . . . . .6-22
APPENDIX . . . . . . . . . . . . . . . . . . . . . .A-1
Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-2
Maintenance Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1
Pressure Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-1
PARTS AND DIAGRAMS . . . . . . . . . . . .P/D-1
Series 1 Portable Chillers, TIC Control
UGH016/0500
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
ꢀ
ꢀ
ꢀ
ꢀ
Purpose of the User Guide . . . .1-2
How the guide is organized . . . .1-2
Your responsibilities as a user .1-2
ATTENTION: Read this so
no one gets hurt . . . . . . . . . . .1-3
Series 1 Portable Chillers, TIC Control
UGH016/0500
1-1
Download from Www.Somanuals.com. All Manuals Search And Download.
This User Guide describes Conair’s Series 1 Water-cooled and
Air-cooled Portable Chillers and explains step-by-step how to
install, operate, maintain and repair this equipment.
PURPOSE OF
THE USER
GUIDE
Before installing this product, please take a few moments to
read the User Guide and review the diagrams and safety infor-
mation in the instruction packet. You also should review man-
uals covering associated equipment in your system. This
review won’t take long, and it could save you valuable instal-
lation and operating time later.
Symbols have been used to help organize the User Guide and
call your attention to important information regarding safe
installation and operation.
HOW THE
GUIDE IS
ORGANIZED
Symbols within triangles warn of conditions that could
be hazardous to users or could damage equipment.
Read and take precautions before proceeding.
Numbers within shaded squares indicate tasks or steps
to be performed by the user.
1
A diamond indicates the equipment’s response to an
action performed by the user.
ꢀ
ꢀ
ꢀ
An open box marks items in a checklist.
A shaded circle marks items in a list.
You must be familiar with all safety procedures concerning
installation, operation and maintenance of this equipment.
Responsible safety procedures include:
YOUR
RESPONSIBILITY
AS A USER
ꢀ Thorough review of this User Guide, paying particular
attention to hazard warnings, appendices and related dia-
grams.
ꢀ Thorough review of the equipment itself, with careful
attention to voltage sources, intended use and warning
labels.
ꢀ Thorough review of instruction manuals for associated
equipment.
ꢀ Step-by-step adherence to instructions outlined in this
User Guide.
Series 1 Portable Chillers, TIC Control
UGH016/0500
1-2
INTRODUCTION
Download from Www.Somanuals.com. All Manuals Search And Download.
We design equipment with the user’s safety in mind. You can
avoid the potential hazards identified on this machine by fol-
lowing the procedures outlined below and elsewhere in the
User Guide.
ATTENTION:
READ THIS SO NO
ONE GETS HURT
WARNING: Improper installation, oper-
ation, or servicing may result in equip-
ment damage or personal injury.
This equipment should only be installed, adjust-
ed, and serviced by qualified technical person-
nel who are familiar with the construction, oper-
ation, and potential hazards of this type of
machine.
All wiring, disconnects and fuses should be
installed by qualified electrical technicians in
accordance with electrical codes in your region.
Always maintain a safe ground. Do not operate
the equipment at power levels other than what
is specified on the machine serial tag and data
plate.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when
working on the Portable Chiller, especially when
working on or around the compressor and con-
denser. These devices can reach up to 160 °F
(71 °C). Allow these devices to cool before per-
forming any maintenance or troubleshooting.
CAUTION: Ventilation hazard
The unit requires a clean and well ventilated
operating environment. Do not place anything
on top of the unit while operating. Units with
fans require unrestricted outlet air flow.
Water-cooled units require a minimum of one
foot clearance around the perimeter for service-
ability. Air-cooled units require a minimum of two
feet clearance around the perimeter for service-
ability and proper air flow.
UGH016/0500
Series 1 Portable Chillers, TIC Control
INTRODUCTION 1-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
DESCRIPTION
ꢀ
ꢀ
ꢀ
ꢀ
What is the Portable Chiller? . . .2-2
Typical Applications . . . . . . . . . .2-3
Limitations . . . . . . . . . . . . . . . . .2-3
How it Works: Water-cooled
Portable Chiller . . . . . . . . . . . .2-4
How it Works: Air-cooled
ꢀ
Portable Chiller . . . . . . . . . . . .2-6
Portable Chiller Features . . . . . .2-8
Specifications . . . . . . . . . . . . .2-10
Pump Curves . . . . . . . . . . . . . .2-12
ꢀ
ꢀ
ꢀ
Series 1 Portable Chillers, TIC Control
UGH016/0500
2-1
Download from Www.Somanuals.com. All Manuals Search And Download.
The Conair Series 1 Portable Chillers provide self-contained
sources of chilled water and are available in either water- or
air-cooled models, ranging in sizes from 3.5 Hp to 40 Hp
(approximate capacities of 3.5 tons of refrigeration to 40 tons
of refrigeration). Pump selections are available to match most
process flow and pressure requirements.
WHAT IS THE
PORTABLE
CHILLER?
The normal temperature range of discharge chilled water is
20 °F to 70 °F. For applications requiring 40 °F and lower
mix glycol with the water to the correct percentage.
The Air-cooled Portable Chiller A1 Models and Water-cooled
Portable Chiller W1 Models are designed to provide chilled
water for industrial applications requiring 24-hour-a-day per-
formance. Units are totally self-contained for easy, economical
installation. All parts wetted by the process are non-ferrous.
To operate, simply connect the power source, process piping
and fill with water or ethylene or propylene glycol (but not
automotive antifreeze).
These chillers are ideal for machine-side cooling to maintain
process temperatures in an injection molding machine or
extruder and wherever you need a small, moveable cooling
unit. Nominal capacities range from 1.44 to 14.68 tons for the
water-cooled models and from 1.18 to 10.95 tons for the air-
cooled models. Capacities are based on standard pump sizes
and delivering 50 °F water.
Operation of these units differ only in the medium used to
remove heat from the refrigerant in the condensers. Water-
cooled models use 85 °F (29 °C) or lower cooling water from
a tower, well, or city service; air-cooled models use 95 °F
(35 °C) maximum ambient air.
Choose water-cooled portable chillers where tower water or
another inexpensive water source is available. Choose air-
cooled models for maximum portability of the unit. Water-
cooled models are equipped with brazed plate or tube-in-tube
condensers. Air-cooled models use aluminum-fin, copper-tube
condensers.
All standard voltages are available.
Series 1 Portable Chillers, TIC Control
UGH016/0500
2-2
DESCRIPTION
Download from Www.Somanuals.com. All Manuals Search And Download.
The Conair A1 and W1 Portable Chillers can be used any-
where a reliable source of process cooling water - with stable
temperature control - is required.
TYPICAL
APPLICATIONS
These portable chillers are available for cooling injection
molding, blow molding, thermoforming, extrusion, air com-
pressors, metal plating, anodizing, degreasing, heatset/web
offset printing presses, and dryer after-coolers.
Roll the air-cooled condenser models next to the heat source
connect it and plug it in. They can operate almost anywhere.
The water-cooled condenser models require a source of con-
denser water. Normally used in conjunction with a recirculat-
ing evaporative cooling tower system, the units have slightly
better operating energy efficiencies.
Conair Series 1 Portable Chillers are designed to provide
chilled water for industrial applications requiring 24-hour-a-
day performance. Units are self-contained and easy to install
and maintain. Choose the Conair Series 1 Portable Chillers
based on the cooling load and the capacity of the unit. Pick
your Conair Series 1 Portable Chillers based on:
LIMITATIONS
ꢀꢀCooling load
Choose a portable chiller that has 20% more capacity than
the process load.
ꢀꢀLocation
Choose a water-cooled model if the unit will be located in
an air-conditioned area. Choose the water-cooled model if
a source of condenser water is readily available (i.e. cool-
ing tower water). Do not locate the portable chiller out-
side unless the unit is specially modified.
ꢀꢀTemperature
The portable chiller needs to provide a cooling tempera-
ture less than 70 °F (21°C).
Use this information as a general guide. Consult your Conair
representative for assistance when choosing a Conair Portable
Chiller.
UGH016/0500
Series 1 Portable Chillers, TIC Control
DESCRIPTION 2-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Process circulation
HOW IT WORKS:
WATER-COOLED
PORTABLE
CHILLER
Hot fluid from the
1
process enters the
chiller through the From
Process valve into the
pump reservoir.
Fluid is chilled in the
Pump draws water
from pump reservoir
and moves it through the
strainer and flow switch to
the evaporator.
3 evaporator and exits
2
through the to Process
valve and tube, returning to
the process.
Series 1 Portable Chillers, TIC Control
UGH016/0500
2-4
DESCRIPTION
Download from Www.Somanuals.com. All Manuals Search And Download.
Refrigerant circulation
HOW IT WORKS:
WATER-COOLED
CONT’D
The liquid refrigerant
4
The high pressure vapor travels from
leaves the accumula-
tor, passing through the
thermal expansion valve,
where it expands and
cools.
3
the compressor through the coiled
condenser (where it is condensed into a
liquid) and is stored in the accumulator.
Vaporized refrigerant
2
travels from evapora-
tor to the compressor,
where the low pressure
vapor is compressed into
a high pressure vapor.
Cooled refrigerant is metered
back into the exaporator for
the cycle to begin again.
5
The evaporator extracts heat
from the process fluid, caus-
ing the refrigerant to vaporize
(evaporate) into a gas.
1
UGH016/0500
Series 1 Portable Chillers, TIC Control
DESCRIPTION 2-5
Download from Www.Somanuals.com. All Manuals Search And Download.
Process circulation
HOW IT WORKS:
AIR-COOLED
PORTABLE
CHILLER
Hot fluid from the
process enters the
chiller through the From
Process valve into the
pump reservoir.
1
Pump draws fluid
from pump reservoir
and moves it through the
strainer and flow switch to
the evaporator.
Fluid is chilled in the
3 evaporator and exits
2
through the To Process
valve and tube, returning to
the process.
Series 1 Portable Chillers, TIC Control
UGH016/0500
2-6
DESCRIPTION
Download from Www.Somanuals.com. All Manuals Search And Download.
Refrigerant circulation
HOW IT WORKS:
AIR-COOLED
PORTABLE
4
The liquid refrigerant
3
The high pressure vapor
leaves the accumulator,
passing through the ther-
mal expansion valve,
where it expands and
cools.
travels from the compressor
through the condenser (where
fans cool vapor into a liquid)
and liquid is stored in the
accumulator.
CHILLER
Vaporized refrigerant
travels from evapora-
tor to the compressor,
where the low pressure
vapor is compressed into
a high pressure vapor.
2
The evaporator extracts heat
from the process fluid, caus-
ing the refrigerant to vaporize
(evaporate) into a gas.
1
Cooled refrigerant is metered
back into the exaporator for
the cycle to begin again.
5
UGH016/0500
Series 1 Portable Chillers, TIC Control
DESCRIPTION 2-7
Download from Www.Somanuals.com. All Manuals Search And Download.
Water-cooled Models
PORTABLE
CHILLER
FEATURES
Condenser
Relief valve
compresses the
refrigerant from a
high pressure vapor
into a high pressure
liquid.
acts as a safety
device for refrig-
erant pressure.
Compressor
compresses the refrig-
erant from a low pres-
sure vapor into a high
pressure vapor.
Hot Gas Bypass valve
balances the load on the
chiller to meet the needs of
the process.
Liquid line solenoid
valve
pumps down refrigerant
to the receiver.
Receiver
stores the liquid refrigerant.
Temperature trans-
mitter electrical box
Filter dryer
transmits temperature
signals to the control
cleans and dries the refrig-
erant.
TX valve
Evaporator
regulates refrigerant flow
cools the To Process fluid
Process pump
From Process valve
To Process valve
circulates fluid through
the chiller.
Pump reservoir
stores process fluid. View fluid
level on water level gauge
Options include:
ꢀꢀ60 Hz process pump
1 1/2 Hp for W1-1.5, W1-2
2 Hp for W1-3, W1-4
3 Hp for W1-5, W1-7.5, W1-10, W1-15
ꢀꢀTo Process and From Process valves
ꢀꢀProcess bypass line and valve
ꢀꢀNo reservoir/pump
ꢀꢀNo reservoir
ꢀꢀAuto fill reservoir
ꢀꢀCondenser water differential pressure switch (W1-7.5 to
W1-15 only)
ꢀꢀVisual alarm
ꢀꢀAudible alarm
ꢀꢀRemote/redundant hand control with 30 ft. cable
ꢀꢀRemote/redundant hand control with 50 ft. cable
ꢀꢀUL labeled controls
Series 1 Portable Chillers, TIC Control
UGH016/0500
2-8
DESCRIPTION
Download from Www.Somanuals.com. All Manuals Search And Download.
Air-cooled Models
PORTABLE
CHILLER
FEATURES
Condenser
Fans
compresses the refrigerant
from a high pressure vapor
into a high pressure liquid.
circulate air across the con-
denser to cool refrigerant
Compressor
compresses the refriger-
Hot Gas Bypass valve
ant from a low pressure
vapor into a high pres-
sure vapor.
balances the load on the
chiller to meet the needs of
the process.
Temperature trans-
mitter electrical box
Receiver
transmits temperature
signals to the control
stores the liquid refrigerant.
Liquid line solenoid
valve
Filter dryer
cleans and dries the refrig-
erant.
pumps down refrigerant
to the receiver.
Evaporator
TX valve
cools the To Process fluid
regulates refrigerant flow
From Process valve
To Process valve
Process pump
circulates fluid through
the chiller.
Pump reservoir
stores process fluid. View fluid
level on water level gauge
Options include:
ꢀꢀ60 Hz process pump
1 1/2 Hp for A1-1.5, A1-2.25
2 Hp for A1-3.25, A1-4
3 Hp for A1-5, A1-7.5, A1-10, A1-13
ꢀꢀTo Process and From Process valves
ꢀꢀProcess bypass line and valve
ꢀꢀCondenser air filters
ꢀꢀNo reservoir/pump
ꢀꢀNo reservoir
ꢀꢀAuto fill reservoir
ꢀꢀVisual alarm
ꢀꢀAudible alarm
ꢀꢀRemote/redundant hand control with 30 ft. cable
ꢀꢀRemote/redundant hand control with 50 ft. cable
ꢀꢀUL labeled controls
UGH016/0500
Series 1 Portable Chillers, TIC Control
DESCRIPTION 2-9
Download from Www.Somanuals.com. All Manuals Search And Download.
Water-cooled Models
SPECIFICATIONS
side
back
front
F
A
10.5 {267}
D
E
5.5 {140}
10 {254}
9 {229}
C
B
MODEL
W1-1.5
W1-2
W1-3
W1-4
W1-5
W1-7.5
W1-10
W1-15
Performance characteristics
ꢀ
Capacity tons
1.44
1.5 {1.1}
1.93
2 {1.5}
3.23
3 {2.2}
4.44
4 {3}
5.00
5 {3.7}
7.09
7.5 {5.6}
10.22
10 {7.5}
14.68
15 {11}
Compressor Hp {kW}
Pump Hp {kW}
60 Hz
0.75 {0.6}
1.5 {1.1}
6.9 {25.1}
27.8 {1.9}
8.0 {30.3}
5.0 {18.9}
0.75 {0.6}
1.5 {1.1}
4.6 {17.4}
29.9 {2.1}
15 {57}
1 {.8}
1.5 {1.1}
7.8 {29.5} 10.7 {40.5}
32.9 {2.3} 31.8 {2.2}
15 {57}
1 {.8}
2 {1.5}
1.5 {1.1}
2 {1.5}
12.0 {45.4} 17.0 {64.3}
41.6 {2.9}
15 {57}
16.7 {63.2} 24.1 {91.2}
1.5 {1.1}
2 {1.5}
1.5 {1.1}
2 {1.5}
24.5 {92.7} 35.2 {133.2}
29.3 {2.0}
25 {95}
31.7 {120} 45.4 {172}
2 {1.5}
2 {1.5}
50 Hz
‡
Chilled water flow gpm {lpm}
Chilled water pressure psi {bar}
Reservoir capacity gal {l}
Condenser water flow gpm {lpm}
Dimensions in {mm}
A-Height
§
34.8 {2.4}
25 {95}
32.3 {2.2}
25 {95}
15 {57}
6.4 {24.2}
10.3 {39.0} 14.2 {53.7}
49 {1245}
34 {864}
49 {1245}
34 {864}
61 {1549}
34 {864}
B-Width
C-Length
39.5 {1003}
45.5 {1156}
55 {1397}
D-Height to condenser out
E-Height to condenser in
F-Distance to valve
Weight lb {kg}
37 {940}
31 {787}
38.5 {978}
32.5 {826}
4 {102}
38.5 {978}
32.5 {826}
38.5 {978}
32.5 {826}
38 {965}
32 {813}
41.3 {1049}
35 {889}
4.5 {114}
41.3 {1049 41.3 {1049}
35 {889}
35 {889}
Installed
Shipped
420 {190}
550 {249}
585 {265}
755 {342}
585 {265}
755 {342}
840 {381}
1010 {458}
840 {381}
1010 {458}
1080 {490}
1250 {567}
1090 {494}
1260 {572}
1095 {497}
1265 {574}
Utility requirements
Process connections NPT in
Condenser water NPT in
Power consumption amps
230V/3 phase/60hz*
220V/3 phase/50hz
460V/3 phase/60hz*
575V/3 phase/60hz*
1
1
1.5
1.5
run full
run
9.5
13.1 19.1 13.8 19.4 17.8 27.5 22.5 33.6 24.3 38.6
full
run
full
run full
run full
run full
run
full
run full
15.3 10.2 15.6 15.1 24.4 18.7 29.4 22.5 36.3
29.2 44.7 35.0 56.0 44.8 79.0
31.3 47.4 37.4 59.1 46.8 82.1
14.2 20.2 17.1 25.3 22.0 35.7
11.4 16.2 13.7 20.2 17.6 28.5
4.5
3.6
6.9
5.5
4.9
3.9
7.1
5.7
7.3 11.1 9.1 13.3 10.9 16.4
5.8 8.9 7.3 10.7 8.7 13.1
SPECIFICATION NOTES
ꢀꢀ
Based on 50 °F (10 °C) water temperature (100% water) leaving the chiller, standard pump selections, 85 °F (27 °C) condenser water supply
@ 25 psi minimum, for the 60 Hz units. For the 50 Hz units, multiply the capacity by 0.8 Consult factory for other conditions. Capacity ratings
are (+-) 5% based on compressor manufacturer’s ratings and are subject to change without notice.
‡
§
Based on 50° F (10 °C) water temperature leaving the chiller and 60 °F (16 °C) water temperature returning to the chiller (except W1-1.5
which has 55 °F (13 °C) water temperature returning to the chiller).
Pressure at pump discharge. See Pressure Tables in the Appendix for Evaporator and Condenser pressure drops.
* Optional
Series 1 Portable Chillers, TIC Control
UGH016/0500
2-10
DESCRIPTION
Download from Www.Somanuals.com. All Manuals Search And Download.
Air-cooled Models
SPECIFICATIONS
front
back
side
A
10.5 {267}
5.5 {140}
10 {254}
9 {229}
C
B
MODEL
A1-1.5
A1-2.25
A1-3.25
A1-4
A1-5
A1-7.5
A1-10
A1-13
Performance characteristics
ꢀ
Capacity , tons
1.18
1.5 {1.1}
1.79
2.25 {1.7}
2.77
3.25 {2.4}
3.62
4 {3}
4.27
5 {3.7}
6.06
7.5 {5.6}
8.75
10 {7.5}
10.95
13 {}
Compressor Hp{kW}
Pump Hp {kW}
60 Hz
0.75 {0.6}
1.5 {1.1}
5.7 {21.6}
0.75 {0.6}
1.5 {1.1}
8.6 {32.6}
28.5 {2.0}
15 {57}
2
1 {.8}
1.5 {1.1}
6.7 {25.4}
35.9 {2.5}
15 {57}
2
1 {.8}
2 {1.5}
8.7 {32.9}
33.9 {2.3}
15 {57}
2
1.5 {1.1}
2 {1.5}
1.5 {1.1}
2 {1.5}
1.5 {1.1}
2 {1.5}
2 {1.5}
2 {1.5}
50 Hz
‡
Chilled water flow , gpm {lpm}
Chilled water pressure , psi {bar} 29.6 {2.0}
Reservoir capacity, gal {l}
Condenser fans
10.2 {38.6} 14.5 {54.9} 21.0 {79.5} 26.3 {99.6}
§
42.4 {2.9}
15 {57}
2
36.9 {2.5}
25 {95}
2
31.6 {2.2}
25 {95}
2
36.1 {2.5}
25 {95}
4
8.8 {33.3}
1
Condenser fan power Hp {kW} 0.17 {0.13}
0.17 {0.13}
1704
{48,250}
0.17 {0.13} 0.25 {0.19}
0.25 {0.19}
4237
{119,975}
0.5 {0.4}
5300
{150,075}
0.5 {0.4}
5300
{150,075}
0.5 {0.4}
9800
{277,505}
Condenser air flow
ft3/min {liters/min}
Dimensions in {mm}
A-Height
1050
{29,732}
2420
4237
{68,525}
{119,975}
49 {1245}
34 {864}
49 {1245}
34 {864}
45.5 {1156}
53.5 {1359}
71 {1524}
34 {864}
55 {1397}
75 {1905}
34 {864}
55 {1397}
B-Width
34 {864}
C-Length
39.5 {1003}
55 {1397}
Weight lb {kg}
Installed
Shipped
610 {277}
750 {340}
830 {376}
1000 {454}
830 {376}
1000 {454}
1030 {467}
1200 {544}
1030 {467}
1200 {544}
1230 {558}
1400 {635}
1230 {558} 1440 {653}
1600 {726}
1800 {816}
Utility requirements
Process connections in
Power consumption amps
230V/3 phase/60hz*
220V/3 phase/50hz*
460V/3 phase/60hz
400v/3 phase/50hz*
575V/3 phase/60hz*
1
1.5
full
run
11.0 19.6
14.7 23.6
5.3
7.7
4.2
full
run
13.3 20.8
17.1 24.8
6.5
9.0 12.4
5.2 7.5
full
run
full
18.6 32.2
21.5 35.5
run
full
run
full
run
full run
run full
23.7 33.3
27.7 37.6
11.6 15.1
14.8 18.8
9.3 12.1
27.8 40.1 38.6 47.2 47.2 62.7 57.4 76.9
29.9 42.6 41.2 50.0 50.2 66.1 60.0 79.9
13.5 18.2 18.9 21.4 23.2 28.4 28.3 34.8
16.0 21.3 22.2 25.0 27.2 33.0 32.6 40.0
10.8 14.5 15.1 17.1 18.6 22.7 22.6 27.8
8.9
11.8
7.1
9.4
9.0
11.4 17.8
7.2 11.7
14.6
SPECIFICATION NOTES
ꢀꢀ
Based on 50 °F (10 °C) water temperature (100% water) leaving the chiller, standard pump selections, 95 °F (35 °C) ambient air conditions for
the 60 Hz units. For the 50 Hz units, multiply the capacity by 0.8. Consult factory for other conditions. Capacity ratings are (+-) 5% based on
compressor manufacturer’s ratings and are subject to change without notice.
‡
§
Based on 50 °F (10 °C) water temperature leaving the chiller and 60 °F (16 °C) water temperature returning to the chiller (except A1-1.5 and
A1-2.25 which have 55 °F (13 °C) water temperature returning to the chiller).
Pressure at pump discharge. See Pressure Tables in the Appendix for Evaporator and Condenser pressure drops.
* Optional
UGH016/0500
Series 1 Portable Chillers, TIC Control
DESCRIPTION 2-11
Download from Www.Somanuals.com. All Manuals Search And Download.
PUMP CURVES
60 HZ PUMP PERFORMANCE CURVES
Flow Rate (gpm)
50 HZ PUMP PERFORMANCE CURVES
Flow Rate (gpm)
Series 1 Portable Chillers, TIC Control
UGH016/0500
2-12
DESCRIPTION
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
ꢀ
ꢀ
ꢀ
ꢀ
Unpacking the Boxes . . . . . . . . . .3-2
Warnings and Cautions . . . . . . . . .3-3
Preparing for Installation . . . . . . .3-4
Making Process Plumbing
Connections . . . . . . . . . . . . . . . .3-5
Filling the Chiller . . . . . . . . . . . . . .3-6
Checking Refrigerant Charge . . . .3-8
Connecting the Main
Power Source . . . . . . . . . . . . . . .3-9
Checking Electrical
ꢀ
ꢀ
ꢀ
ꢀ
Connections . . . . . . . . . . . . . . .3-10
Initially Starting the Chiller . . . . .3-11
Stopping the Chiller . . . . . . . . . .3-12
ꢀ
ꢀ
Series 1 Portable Chillers, TIC Control
UGH016/0500
3-1
Download from Www.Somanuals.com. All Manuals Search And Download.
The portable chiller comes fully assembled in a single crate.
UNPACKING THE
BOXES
CAUTION: Lifting hazard
The Series 1 Portable Chillers are designed to
easily roll on casters. If, for some reason you
need to lift the chiller, take all precautions to
avoid personal injury or damage to the chiller.
Lift the chiller using a forklift or hoist with straps
that have peen positioned at the chillers’ center
of gravity. Do not try to lift the unit manually.
Carefully uncrate the chiller
and its components.
1
2 Remove all packing material, protective paper,
tape, and plastic. compare contents to the shipping papers
to ensure that you have all the parts.
3 Carefully inspect all components to make sure
no damage occurred during shipping. If any damage is
found, notify the shipping agent immediately. Check all
wire terminal connections, bolts, and any other electrical
connections, which may have come loose during ship-
ping. Check for pinched wires and kinked hoses.
3 Record serial numbers and specifications
in the blanks provided on the back of the User Guide’s
title page. This information will be helpful if you ever
need service or parts.
Series 1 Portable Chillers, TIC Control
UGH016/0500
3-2
INSTALLATION
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Improper installation, oper-
ation, or servicing may result in equip-
ment damage or personal injury.
This equipment should only be installed, adjust-
ed, and serviced by qualified technical person-
nel who are familiar with the construction, oper-
ation, and potential hazards of this type of
machine.
WARNINGS AND
CAUTIONS
All wiring, disconnects and fuses should be
installed by qualified electrical technicians in
accordance with electrical codes in your region.
Always maintain a safe ground. Do not operate
the equipment at power levels other than what
is specified on the machine serial tag and data
plate.
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when
working on the Portable Chiller, especially when
working on or around the compressor and con-
denser. These devices can reach up to 160 °F
(71 °C). Allow these devices to cool before per-
forming any maintenance or troubleshooting.
CAUTION: Ventilation hazard
The unit requires a clean and well ventilated
operating environment. Do not place anything
on top of the unit while operating. Units with
fans require unrestricted outlet air flow.
Water-cooled units require a minimum of one
foot clearance around the perimeter for service-
ability. Air-cooled units require a minimum of two
feet clearance around the perimeter for service-
ability and proper air flow.
UGH016/0500
Series 1 Portable Chillers, TIC Control
INSTALLATION 3-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Plan the location for the chiller and prepare the area properly.
PREPARING FOR
INSTALLATION
Position the Chiller as close to the process machine as possi-
ble. Place the chiller in position near the process machine so
that fluid lines can be connected from the process machine to
the chiller and back.
Chiller
Process machine
Alternate
locations
Make sure the area where the chiller is installed has:
ꢀꢀA grounded power source.
Check the chiller’s serial tag for the correct amps, volt-
age, phase, and cycle. All wiring should be completed by
qualified personnel and comply with your region’s elec-
trical codes.
ꢀꢀClearance for safe operation and maintenance.
Make sure there is two feet clearance around the chiller
for proper operation, maintenance, and servicing. After
positioning, lock casters to prevent chiller from moving.
24 inches
24 inches
(610 mm)
(610 mm)
24 inches
(610 mm)
24 inches
(610 mm)
ꢀꢀAvailable water source.
If installing a water-cooled unit, makes sure water source
is plumbed to chiller installation location. High points in
plumbing require vent valves; low points require drain
valves.
Series 1 Portable Chillers, TIC Control
UGH016/0500
3-4
INSTALLATION
Download from Www.Somanuals.com. All Manuals Search And Download.
Warm fluid from your process enters the chiller at the From
Process valve and chilled fluid returns to the process equip-
ment through the To Process valve.
MAKING
PROCESS
Remove the shipping plastic pipe plug from
the female connections on the back of the portable chiller.
1
PLUMBING
CONNECTIONS
Make sure the male pipe threads are clean
and new.
2
3 Wrap threads with Mylar or Teflon tape.
Connect the From Process valve and tubing
on the back of the chiller to the From Process tubing.
Start by hand until the threads engage and then tighten
with a pipe wrench. Tighten only enough to prevent leaks;
do not over-tighten!
4
Connect the To Process valve and tubing on
the back of the chiller to the return tubing. Start by hand
until the threads engage and then tighten with a pipe
wrench. Tighten only enough to prevent leaks; do not
over-tighten!
5
For the Water-cooled Chillers connect the water source for
cooling to the Condenser Water inlet on the back of the chiller.
Connect the Condenser Water outlet for returning water.
back view
Condenser
Water Outlet
(water-cooled only)
Condenser
Water Inlet
(water-cooled only)
From Process valve
To Process valve
UGH016/0500
Series 1 Portable Chillers, TIC Control
INSTALLATION 3-5
Download from Www.Somanuals.com. All Manuals Search And Download.
The Chiller is shipped without coolant. The chiller is filled
manually during installation. Use water as the coolant down to
40 °F (4 °C). Below 40 °F and down to 20 °F (-7 °C), use an
ethylene glycol or propylene glycol solution.
FILLING THE
CHILLER
To fill with water:
1
2
3
Attach water hose to Fill/Drain valve.
Close the To Process and From Process valves.
Open the Fill/Drain valve and fill chiller
to the fill mark on the Water Level sight glass. If the
chiller is overfilled, the excess water spills out the vent
tube. DO NOT OVERFILL.
Close the Fill/Drain valve.
4
5
Disconnect water hose from Fill/Drain valve.
From Process valve
To Process valve
Water Level
sight glass
Fill/Drain valve
To fill with glycol solution:
Mix the glycol to the proper percentage.
1
Use the table to determine the percentage (by volume) of
glycol needed for the process temperature (in °F) you
require. Do not choose a temperature below 15 °F (-9 °C).
Mix the proper percentage of glycol with water.
WARNING: Refrigerant hazard
Only certified refrigerant technicians should
examine and correct problems involving the
refrigerant circuit.
Series 1 Portable Chillers, TIC Control
UGH016/0500
3-6
INSTALLATION
Download from Www.Somanuals.com. All Manuals Search And Download.
FILLING THE
CHILLER
CONT’D
Temperature of Process Fluid °F
2 Close the To Process and From Process valves.
3
Open the Fill/Drain valve and fill chiller
to the fill mark on the Water Level gauge. If the chiller is
overfilled, the excess fluid spills out the vent tube. DO
NOT OVERFILL.
4 Close the Fill/Drain valve.
5
6
Check the coolant level.
Once the chiller is turned on, the coolant level may drop
as the coolant begins to circulate, filling the connected
plumbing. Check the coolant level on the back of the
chiller. The water level shows on the water level gauge.
Make sure water level is filled to the mark on the gauge.
Change the minimum operating temperature
range to the correct setting for the percent glycol used.
See Setting the To Process Low Limit, in the Operations
section.
UGH016/0500
Series 1 Portable Chillers, TIC Control
INSTALLATION 3-7
Download from Www.Somanuals.com. All Manuals Search And Download.
All chillers are fully charged with refrigerant at the factory.
Your chiller’s model nameplate identifies the type and amount
of total refrigerant charge required.
CHECKING
REFRIGERANT
CHARGE
Check refrigerant charge while the chiller is running. Check
the refrigerant charge through the sight glass. Open the side
door of the Chiller. Use a flashlight, if necessary, and check
the liquid-line sight glass:
ꢀꢀUnder normal load conditions, the refrigerant should
be clear.
ꢀꢀUnder low load conditions, when the hot-gas bypass
valves are operating, bubbles may be visible in the
sight glass. This is normal.
If the charge is low contact Conair service or have a local, cer-
tified refrigeration technician add refrigerant to the system.
WARNING: Refrigerant hazard
Only certified refrigerant technicians should
examine and correct problems involving the
refrigerant circuit.
Sight glass
Series 1 Portable Chillers, TIC Control
UGH016/0500
3-8
INSTALLATION
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Improper installation, oper-
ation, or servicing may result in equip-
ment damage or personal injury.
This equipment should only be installed, adjust-
ed, and serviced by qualified technical person-
nel who are familiar with the construction, oper-
ation, and potential hazards of this equipment
CONNECTING
THE MAIN
POWER SOURCE
All wiring, disconnects and fuses should be
installed by qualified electrical technicians in
accordance with electrical codes in your region.
Always maintain a safe ground. Do not operate
the equipment at power levels other than what
is specified on the machine serial tag and data
plate.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
1
2
Open the chiller’s electrical enclosure.
The 575V, 1 1/2 - 4 Hp
units utilize a transformer;
power wires must be con-
nected to the line side of
the transformer.
Connect the power wires to the terminals
as indicated on the wiring diagrams
that came with your machine. Route
the power cable through the hole in
the side of the chiller to the electrical
enclosure.
3
4
Check terminal screws to
make sure wires are secure. Gently
tug each wire; if wire is loose, use a
screwdriver to tighten the terminal.
Grounding lug
Connect the ground wire to grounding lug.
UGH016/0500
Series 1 Portable Chillers, TIC Control
INSTALLATION 3-9
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
CHECKING
ELECTRICAL
CONNECTIONS
1 Open electrical enclosure.
Connect the power cable
to the main line connection.
2
Check the short-to-ground with an ohm meter.
Connect the ohm meter to each of the three terminal
screws and to the grounding lug. Test all three for resis-
tance. The minimum resistance to ground should be
1megohm. If it resistance is less that 1 megohm, there is a
leak in the system.
3
Test each for
resistance
Grounding lug
4 Close the electrical enclosure.
5
Turn on main power source.
Series 1 Portable Chillers, TIC Control
UGH016/0500
3-10
INSTALLATION
Download from Www.Somanuals.com. All Manuals Search And Download.
1 Turn on main power source.
INITIALLY
STARTING THE
CHILLER
The control boots up and the screen displays the tempera-
ture of the fluid going to the process.
WARNING: Initial startup
Do not press any buttons after initially applying
power to the Chiller. Let the Chiller set, undis-
turbed, for a minimum of 8 hours before starting
the Chiller. This is necessary to allow the
crankcase heater to warm properly, and to pre-
vent the refrigerant from pooling in the com-
pressor.
After the initial 8-hour minimum warmup, continue with start-
up:
Press the Start Chiller button.
2
Check the Pump and Compressor lights on the control
panel; they should turn on and off as the pump and com-
pressor cycle on and off. The To Process temperature dis-
plays on the control. The To Process temperature is real-
time temperature. It should change as the chiller runs and
cools the fluid.
Check the rotation of the pump.
3
4
If pump is not turning, disconnect main power to chiller,
swap any two incoming power wires; reapply main power.
Check for leaks inside the chiller cabinet; fix any leaks
and dry the inside of the chiller before proceeding.
Check the compressor.
If the compressor is running backwards, disconnect the
Chiller from the main power supply, switch any two
incoming main power leads, and reapply main power sup-
ply. Wait three minutes. The compressor should now be
running in the proper direction.
When the compressor is shut
off it cannot be turned on
again for three minutes. This
allows temperatures and
pressure in the chiller to
equalize, making restart easi-
er, and prolonging the life of
the chiller.
Check the sight glass on the back of the chiller.
If the fluid level is low, follow the steps to add fluid. See
Filling the Chiller in the Installation section.
5
If the chiller is not working properly at any time, press the red
Stop button to turn off the chiller.
UGH016/1200
Series 1 Portable Chillers, TIC Control
INSTALLATION 3-11
Download from Www.Somanuals.com. All Manuals Search And Download.
To stop the chiller, press the Stop Chiller button on the control
panel.
STOPPING THE
CHILLER
NOTE: When you press the Stop Chiller button, the pump and
compressor both stop. If you want to restart immediately by
pressing the Start Chiller button, the pump will turn on but the
compressor will not turn on for three minutes. The Process
Pump light on the control panel will light immediately. After
three minutes the compressor turns on and the Compressor
light on the control panel lights. This allows temperatures and
pressure to equalize, making restart easier, and prolonging the
life of the chiller.
If the chiller is not working properly at any time, stop the
chiller and refer to the Troubleshooting section. If you do not
encounter any problems, proceed to the Operation section.
Series 1 Portable Chillers, TIC Control
UGH016/0500
3-12
INSTALLATION
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
TIC Control Features . . . . . . . . .4-2
Before Starting . . . . . . . . . . . . . .4-3
Starting/Stopping the Chiller . . .4-4
Changing Settings . . . . . . . . . . .4-5
Changing the Setpoint
Temperature . . . . . . . . . . . . . .4-6
ꢀ
ꢀ
ꢀ
Changing Temperature Scale . .4-7
Changing Auto Tune Mode . . . .4-7
Setting the To Process
Low Limit . . . . . . . . . . . . . . . . .4-8
Series 1 Portable Chillers, TIC Control
UGH016/0500
4-1
Download from Www.Somanuals.com. All Manuals Search And Download.
The TIC control lets you view the status of the chiller and
change settings.
TIC CONTROL
FEATURES
Display
System lights
4-digit LED screen shows To Process tem-
perature, new settings and run modes.
Indicator light shows hot gas unloading.
Light when compressor,
pump or alarm activates
System buttons
Quick text
Control buttons
Press to start and stop
chiller and to silence
optional audible alarm
Follow steps to
change setpoints
Press to access menus,
enter data, and to scroll
4-Digit LED display
Unloading indicator
Shows status, settings
and run modes.
Lights when the hot gas
bypass is unloading.
Menu Access button
Mode/Enter button
Press to enter or change
setpoint, to exit the menu,
and to index to the next
menu.
Press to enter parameter selec-
tions, access operating modes,
silence alarms, and index
through menu items.
Raise button
Increases values, hold for
fast-step progression.
Lower button
Decreases values; hold
for fast-step progression.
Series 1 Portable Chillers, TIC Control
UGH016/0500
4-2
OPERATION
Download from Www.Somanuals.com. All Manuals Search And Download.
Before you start daily operation of the chiller, you need to
perform scheduled preventative maintenance. Necessary main-
tenance is describe in the Maintenance section of this Users
Guide.
BEFORE
STARTING
WARNING: Electrical hazard
Be sure that power to the chiller is OFF when
doing any maintenance on the chiller. Follow all
safety rules when performing any maintenance
on this equipment.
Daily maintenance includes:
ꢀꢀChecking electrical connections
ꢀꢀChecking process fluid level in the pump tank
ꢀꢀChecking the condenser coil for debris
ꢀꢀVerifying pump discharge pressure
ꢀꢀInspecting piping for leaks
NOTE: The daily, weekly, monthly, and semi-annual mainte-
nance procedures are detailed in the Maintenance section. Go
there for detailed preventative maintenance.
Before starting the Chiller be sure to:
ꢀꢀOpen the To Process valve
to the full open position.
ꢀꢀOpen the From Process valve
to the 3/4 open position. You will need to adjust this
valve when the chiller is running to obtain the desired
pump discharge pressure. To find the approximate
water flow, refer to the Pump Curves in Description
section.
From Process valve
To Process valve
ꢀꢀCheck that the casters are locked.
UGH016/0500
Series 1 Portable Chillers, TIC Control
OPERATION 4-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Plug in the power cord to restore power after any required
maintenance.
STARTING/
STOPPING THE
CHILLER
The chiller control automatically performs its bootup routine.
When bootup is complete, the screen displays the To Process
temperature. The chiller is ready to run.
Press the Start Chiller button.
Check the Pump and Compressor lights on the control
panel; they should turn on and off as the pump and com-
pressor cycle on and off. The To Process temperature dis-
plays on the control. The To Process temperature is real-
time temperature. It should change as the chiller runs and
cools the fluid.
If you disconnect the Chiller
from the main power supply
and reconnect it, the Chiller
needs 15 minutes for the
crankcase heater to warm
up. You can not use the
To safely stop the chiller at any time, press the red Stop
Chiller button on the control panel.
Chiller during this time.
The chiller remains on, but stopped. The display screen on
the control remains on.
NOTE: When you press the Stop Chiller button, the pump and
compressor both stop. If you want to restart immediately by
pressing the Start Chiller button, the pump will turn on but the
compressor will not turn on for three minutes. The Process
Pump light on the control panel will light immediately. After
three minutes the compressor turns on and the Compressor
light on the control panel lights.
Series 1 Portable Chillers, TIC Control
UGH016/0500
4-4
OPERATION
Download from Www.Somanuals.com. All Manuals Search And Download.
The control allows you to change four settings:
CHANGING
SETTINGS
ꢀꢀTemperature Setpoint
The temperature you want the To Process liquid
ꢀꢀTemperature Scale
Choose to display temperature in degrees Fahrenheit or
Celsius.
ꢀꢀAuto Tune
Helps maintain the temperature setpoint without over-
shooting.
ꢀꢀTo Process Low Limit
Set when need to chill fluid below 40 °F (4 °C) and
down to 20 °F (-7 °C). Set this limit when using glycol
to chill.
All other settings are set at the factory. You should not change
any other settings. If you accidentally change any other set-
ting, refer to the control manual that you received with your
chiller and see Control Settings, in the Appendix. If you have
any problems or questions, call your Conair Service represen-
tative.
The current To Process temperature displays on the screen
when the chiller is turned on. As the temperature changes, the
number on the display changes.
CHANGING THE
SETPOINT
TEMPERATURE
The setpoint temperature is the temperature you want the
water to be exiting the chiller at the To Process valve.
To set the temperature setpoint:
1
Press Menu button once.
The display flashes SP, and the current setpoint
temperature.
2
Press the Up/Down arrows
to raise and lower the setpoint temperature. Each
time you press the arrow the temperature
changes one unit. Stop when you reach the tem-
perature you want.
To return to the To Process
Temperature screen from
any other screen, press and
hold the
least 5 seconds until the
temperature displays.
button for at
Press the Mode/Enter button
to accept the new setpoint temperature. The dis-
play returns to the actual process temperature.
3
UGH016/0500
Series 1 Portable Chillers, TIC Control
OPERATION 4-5
Download from Www.Somanuals.com. All Manuals Search And Download.
The default temperature scale for the control is Fahrenheit (F).
You can change the scale to Celsius (C):
CHANGING
TEMPERATURE
SCALE
1
2
Press Menu button until DISP shows
on the screen.
Press the Enter button.
The current temperature scale displays (F or C)
and is flashing.
Press the Up/Down arrows
3
4
to move to the other scale. If the current temper-
ature scale is Fahrenheit, pressing the arrow
moves you to C; if the current temperature scale
is Celsius, pressing the arrow moves you to F.
Press the Menu button
to accept the new temperature scale and displays
the process temperature.
Use the Auto Tune Mode to maintain the temperature setpoint
without overshooting it. When initiating Auto Tune Mode the
actual temperature (temperature of the water exiting the
Chiller) must at least 20° warmer than the current setpoint
temperature. In order to guarantee this, run the chiller for sev-
eral minutes until the To Process temperature is 40 °F with no
load on the Chiller.
CHANGING TO
AUTO TUNE
MODE
To initiate the Auto Tune mode:
Press Enter button and hold
for 3 seconds. FOP displays on the screen.
1
Use the Up/Down arrows to scroll
until STBY (standby) displays.
To return to the To Process
Temperature screen from
any other screen, press and
2
hold the
button for at
least 5 seconds until the
temperature displays.
Press the Enter button.
3
STBY flashes on the screen alternately with the
current To Process temperature.
Series 1 Portable Chillers, TIC Control
UGH016/0500
4-6
OPERATION
Download from Www.Somanuals.com. All Manuals Search And Download.
4 Press the Menu button.
SP displays, flashing alternately with the cur-
rent setpoint temperature.
CHANGING
AUTO TUNE
MODE
5
Use the Up/Down arrows to change
the setpoint temperature. Each time you press
an arrow, the displayed number changes one
unit.
CONT’D
6 Press Enter button.
The screen displays STBY and the new number.
7 Press Enter button and hold
for 3 at least seconds until FOP displays on the
screen.
8
9
Apply a load to the Chiller.
To return to the To Process
Temperature screen from
any other screen, press and
Use the Up/Down arrows to scroll
until ATUN displays on the screen.
hold the
button for at
least 5 seconds until the
temperature displays.
10 Press the Enter/Mode button once.
The screen flashes ATUN. When auto tuning is
done the screen displays STBY.
Press Enter button and hold
for 3 at least seconds until FOP displays on the
screen.
11
12
Use the Up/Down arrows to scroll
to NOR on the screen.
13 Press Enter button.
Initiating Auto Tune is complete.
UGH016/0500
Series 1 Portable Chillers, TIC Control
OPERATION 4-7
Download from Www.Somanuals.com. All Manuals Search And Download.
The default low temperature limit for the To Process fluid is
set at the factory at 40 °F. This temperature limit is the lowest
temperature for the chilled fluid leaving the Chiller. If you
want to cool fluid below 40 °F (4 °C) and down to 20 °F
(-7 °C), you need to fill the chiller with the proper percentage
of glycol solution. See Filling the Chiller, in the Installation
section.
SETTING THE TO
PROCESS LOW
LIMIT
After the Chiller is filled with the proper percentage of glycol
solution, you need to set the minimum operating temperature
on the control. Use the temperature you chose when selecting
the percent glycol.
To set the To Process low limit on the control:
1
2
Press Menu button until INP shows
on the screen.
Press the Enter button until SPLL
displays on the screen. SPLL flashes, along with
the current low limit temperature.
To return to the To Process
Temperature screen from
any other screen, press and
Press the Up/Down arrows
to change the temperature to the required num-
ber.
3
4
hold the
button for at
least 5 seconds until the
temperature displays.
Press the Menu button
to accept the new temperature.
If you want to change from using a glycol solution back
to using water in your chiller, you need to change the low
limit temperature to 40 °F (4 °C). Follow the steps listed
here to set the To Process low limit to 40.
Series 1 Portable Chillers, TIC Control
UGH016/0500
4-8
OPERATION
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
ꢀ
ꢀ
ꢀ
Maintenance Features . . . . . . . .5-2
Warnings and Cautions . . . . . . .5-3
Preventative Maintenance
Schedule . . . . . . . . . . . . . . . . .5-4
Checking the Refrigerant
Charge . . . . . . . . . . . . . . . . . . .5-6
Cleaning the Evaporator or
ꢀ
ꢀ
ꢀ
Water-cooled Condenser . . . .5-7
Cleaning the Air-cooled
Condenser . . . . . . . . . . . . . . . .5-8
ꢀ
ꢀ
Checking Electrical
Connections . . . . . . . . . . . . . .5-9
Checking Reservoir Level . . . .5-10
Series 1 Portable Chillers, TIC Control
UGH016/0500
5-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Conair Series 1 Portable Chillers need regular, scheduled
maintenance for peak performance.
MAINTENANCE
FEATURES
To maintain the best performance of the chiller, it must be
cleaned and inspected regularly. Maintenance includes a daily,
monthly, and semi-annual schedule.
Use this maintenance schedule as a guide. You may need to
shorten the time of the maintenance schedule, depending on
how often you use the chiller. Among the features that require
preventative maintenance are:
ꢀꢀthe refrigerant system
ꢀꢀelectrical cables, terminals, and control lights
ꢀꢀthe condenser
ꢀꢀprocess fluid level
ꢀꢀevaporator
ꢀꢀCooling water treatment system (if used)
Series 1 Portable Chillers, TIC Control
UGH016/0500
5-2
MAINTENANCE
Download from Www.Somanuals.com. All Manuals Search And Download.
Follow all cautions and warnings when working on the equip-
ment.
WARNING AND
CAUTIONS
WARNING: Improper installation, oper-
ation, or servicing may result in equip-
ment damage or personal injury.
This equipment should only be installed, adjust-
ed, and serviced by qualified technical person-
nel who are familiar with the construction, oper-
ation, and potential hazards of this type of
machine.
All wiring, disconnects, and fuses should be
installed by qualified electrical technicians in
accordance with electrical codes in your region.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup. Be sure that power to the chiller is OFF
when doing any maintenance on the chiller.
Follow all safety rules when performing any
maintenance on this equipment.
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when
working on the Portable Chiller, especially when
working on or around the compressor and con-
denser. These devices can reach up to 160 °F
(71 °C). Allow these devices to cool before per-
forming any maintenance or troubleshooting.
WARNING: Refrigerant hazard
Only certified refrigerant technicians should
examine and correct problems involving the
refrigerant circuit.
UGH016/0500
Series 1 Portable Chillers, TIC Control
MAINTENANCE 5-3
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢀ
Daily, or as often as needed
PREVENTATIVE
MAINTENANCE
SCHEDULE
ꢀꢀꢀ
Checking electrical connections
Make sure electrical connections are properly seated.
See Checking Electrical Connections, in the
Maintenance section.
ꢀꢀꢀ
Checking process fluid level in the pump tank
Check the process fluid level in the water level gauge
on the back of the chiller. If low, see Filling the
Chiller, in the Installation section.
ꢀꢀꢀ
Verifying pump discharge pressure
To maintain the best perfor-
mance, follow the mainte-
nance schedule and record
information in the
While the pump is running, check that the pump pres-
sure gauges are within range. To change the pressure
open or close the From Process valve.
Maintenance Log in the
Appendix.
ꢀꢀꢀ
Inspecting piping for leaks
Check to see that pipes are not leaking. Look for
standing water on the floor or inside the chiller cabi-
net.
ꢀꢀꢀ
Inspecting the condenser coil for debris
(air-cooled models only) Remove the wire mesh side
panel in front of the condenser coil. Remove any
debris from the coils.
ꢀ
Weekly, or as often as needed
ꢀꢀꢀ
Checking temperature and pressure readings
Check that the temperature and pressure display on the
control screen, and that the pressure gauge indicates
normal operation.
ꢀꢀꢀ
Checking efficiency
Review the performance data on the Maintenance Log
found in the Appendix. If you notice a decrease in effi-
ciency over time, check all heat transfer surfaces of the
evaporator and condenser for fouling. Clean as needed.
ꢀꢀꢀ
Checking refrigerant site glass
There should not be any bubbles. See Checking
Refrigerant Charge, in the Maintenance section.
ꢀꢀꢀ
Checking reservoir level
Check the water level gauge on the back of the chiller.
If fluid level is low, fill. See Checking Reservoir Level,
in the Maintenance section.
Series 1 Portable Chillers, TIC Control
UGH016/0500
5-4
MAINTENANCE
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢀ
Monthly
PREVENTATIVE
MAINTENANCE
SCHEDULE
ꢀꢀꢀ
Inspecting cooling water treatment system
If your chiller uses a cooling water treatment system,
maintain proper chemical levels and follow the recom-
mendations of your water treatment specialist. Change
water in the reservoir tank monthly.
ꢀꢀꢀ
Cleaning
Wipe all external surfaces to maintain performance.
ꢀꢀꢀ
Inspecting condenser
Check the condenser for adequate air flow or water
flow. Check the condenser face for dirt and clogging.
If dirt or clogs are present, clean the condenser. See
Cleaning the Evaporator or Water-cooled Condenser,
and Cleaning the Air-cooled Condenser, in the
Maintenance section. If your unit has an optional filter
at the air inlet of the Air-cooled condenser coil, check,
clean, and replace as needed.
To maintain the best perfor-
mance, follow the mainte-
nance schedule and record
information in the
Maintenance Log in the
Appendix.
ꢀꢀꢀ
Inspecting the control panel
Check for loose wires, burned contacts, and signs of
overheated wires. Check that all panel lights illumi-
nate. See Checking Electrical Connections in the
Maintenance section.
ꢀꢀꢀ
Checking refrigerant charge
Check the sight glass between the receiver and evapo-
rator for proper refrigerant pressure. See Checking
Refrigerant Charge, in the Maintenance section.
ꢀꢀꢀ
Cleaning process fluid strainer
Remove cap and clean any debris out of strainer.
Replace cap.
ꢀ
Semi-annual (every 6 months)
ꢀꢀꢀ
Cleaning the evaporator or water-cooled condenser
See Cleaning the Evaporator or Water-cooled
Condenser, in the Maintenance section.
ꢀꢀꢀ
Cleaning the tank and float switch
Drain the reservoir. Disconnect all piping from tank
reservoir. Remove the float switch by loosening the nut
on the float switch. Remove switch and clean. Unbolt
the tank from the chiller base. Take off the tank cover
and clean the reservoir. Reinstall the tank cover; rein-
stall tank. Reinsert float switch, holding firmly against
reservoir and tighten nut. Fill reservoir and check for
leaks.
UGH016/0500
Series 1 Portable Chillers, TIC Control
MAINTENANCE 5-5
Download from Www.Somanuals.com. All Manuals Search And Download.
All chillers are fully charged with refrigerant at the factory.
Your chiller’s model nameplate identifies the type and amount
of total refrigerant charge required.
CHECKING THE
REFRIGERANT
CHARGE
WARNING: Refrigerant hazard
Only certified refrigerant technicians should
examine and correct problems involving the
refrigerant circuit.
Check refrigerant charge while the chiller is running:
Check the refrigerant charge through the sight
glass.
Use a flashlight, if necessary, and check the liquid-line
sight glass:
ꢀꢀUnder full load conditions, the refrigerant should be
clear (no bubbles).
ꢀꢀUnder low load conditions, when the hot-gas bypass
valves are operating, bubbles may be visible in the
sight glass. This is normal.
If the charge is low contact Conair service or have a local, cer-
tified refrigeration technician to add refrigerant to the system.
Sight
glass
Series 1 Portable Chillers, TIC Control
UGH016/0500
5-6
MAINTENANCE
Download from Www.Somanuals.com. All Manuals Search And Download.
Minerals and other contaminants produce deposits, scales,
slime, or algae on the heat transfer surfaces exposed to water.
Fouled surfaces result in decreased cooling capacity.
Implement a water treatment program to slow the fouling.
CLEANING THE
EVAPORATOR OR
WATER-COOLED
CONDENSER
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when
working on the Portable Chiller, especially when
working on or around the compressor and con-
denser. These devices can reach up to 160 °F
(71 °C). Allow these devices to cool before per-
forming any maintenance or troubleshooting.
Water quality should be maintained at a pH of 7.4, but not less
that 6.0 for proper heat exchanger life.
To clean:
1
Prepare a 5% solution of Phosphoric acid
or Oxalic acid. Do not heat the acid solution.
2
3
Shut the From Process valve.
Disconnect the pump from the heat exchanger.
Install a cap in the opening of the heat exchanger where
the pump was connected.
4
5
6
7
Connect 1/2-inch tubing to the 1/2-inch
connections of the heat exchanger.
Back-flush the solution through the
heat exchanger and the chiller.
Flush the heat exchanger and the chiller
piping with fresh water after cleaning.
Out
In
Reconnect the chiller pump to the
heat exchanger. Remove the cap in the heat exchanger
and reconnect the hose from the pump.
Out
In
1/2 inch connection on
outside of chiller cabinet
Heat
Exchanger
Fluid circuit
Acid solution
To Process connection
UGH016/0500
Series 1 Portable Chillers, TIC Control
MAINTENANCE 5-7
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
CLEANING THE
AIR-COOLED
CONDENSER
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when
working on the Portable Chiller, especially when
working on or around the compressor and con-
denser. These devices can reach up to 160 °F
(71 °C). Allow these devices to cool before per-
forming any maintenance or troubleshooting.
The air-cooled condenser can accumulate dirt and clog quick-
ly if it is run in a dusty or dirty environment. A clogged con-
denser increases refrigerant discharge pressure, lowers perfor-
mance, and may cause the fan motors and compressor to over-
heat.
Inspect the coils.
Use a flashlight to check between coil surfaces.
1
2 Clean the dirty coils with a soft brush.
Flush with cool water or a commercial
coil cleaner.
3
If your unit has the optional air filter supplied by Conair, clean
it using water or air. Replace as needed.
Series 1 Portable Chillers, TIC Control
UGH016/0500
5-8
MAINTENANCE
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
CHECKING
ELECTRICAL
CONNECTIONS
WARNING: Improper installation, oper-
ation, or servicing may result in
equipment damage or personal injury.
This equipment should only be installed, adjust-
ed, and serviced by qualified technical person-
nel who are familiar with the construction, oper-
ation, and potential hazards of this type of
machine.
All wiring, disconnects, and fuses should be
installed by qualified electrical technicians in
accordance with electrical codes in your region.
1 Be sure the main power is disconnected
and the chiller is locked out. Always disconnect and lock-
out the main power source before opening the unit for
servicing.
2
Open the electrical enclosure.
3 Inspect all wires and connections.
Always refer to the wiring
diagrams you received with
your chiller to locate specif-
ic electrical components.
Look for loose wires, burned contacts, and signs of over-
heated wires. Compare the control wiring to the wiring
diagrams you received with your chiller. Have a qualified
electrician make any necessary repairs or replacements.
4
Close the electrical enclosure door.
5 Inspect the exterior power cords.
Cords should not be crimped, exposed, or rubbing against
the frame. If the main power cord runs along the floor,
make sure it is not positioned where it could rest in pool-
ing water or could be run over and cut by wheels or cast-
ers.
UGH016/0500
Series 1 Portable Chillers, TIC Control
MAINTENANCE 5-9
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
CHECKING
RESERVOIR
LEVEL
Check the fluid level in the reservoir. The meniscus in the
sight glass on the back of the chiller should be in line with the
mark on the sight glass.
To manually fill the reservoir:
Disconnect and lockout power to the chiller.
1
Locate the fill port on the back of the chiller.
2
3
Refill the reservoir.
Monitor the level using the water level gauge on the back
of the chiller. Because the Portable Chiller can use either
pure water or a glycol solution, make sure your are
adding the correct fluid for your application.
Fill port
Fill/Drain valve
Water level gauge
If you have the optional make-up water level float switch, it
will automatically control the fluid level.
Series 1 Portable Chillers, TIC Control
UGH016/0500
5-10
MAINTENANCE
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
ꢀ
ꢀ
ꢀ
Before Beginning . . . . . . . . . . . .6-2
A Few Words of Caution . . . . . .6-2
Identifying the Cause
of a Problem . . . . . . . . . . . . . .6-3
ꢀ
ꢀ
ꢀ
ꢀ
Answering an Alarm . . . . . . . . .6-4
Control Problems . . . . . . . . . . . .6-5
Mechanical Conditions . . . . . . .6-6
Checking and Replacing
Switches . . . . . . . . . . . . . . . .6-15
Replacing the Contactor . . . . .6-16
Checking and Replacing
ꢀ
ꢀ
the RTD . . . . . . . . . . . . . . . . .6-17
Replacing the Temperature
Controller (TIC) . . . . . . . . . . .6-18
Replacing Overload Modules .6-19
ꢀ
ꢀ
ꢀ
ꢀ
Replacing Fuses . . . . . . . . . . .6-20
Removing Pump
Components . . . . . . . . . . . . .6-21
ꢀ
Checking the Pressure
Switches . . . . . . . . . . . . . . . .6-22
Series 1 Portable Chillers, TIC Control
UGH016/0500
6-1
Download from Www.Somanuals.com. All Manuals Search And Download.
You can avoid most problems by following the recommended
installation, operation and maintenance procedures outlined in
this User Guide. If you have a problem, this section will help
you determine the cause and tell you how to fix it.
BEFORE
BEGINNING
Before you begin troubleshooting:
ꢀ Find any wiring, piping, and assembly diagrams that
were shipped with your equipment. These are the best
reference for correcting a problem. The diagrams will
note any custom features or options not covered in this
User Guide.
ꢀ Verify that you have all instructional materials related
to the chiller. Additional details about troubleshooting
and repairing specific components are found in these
materials.
ꢀ Check that you have manual for other equipment con-
nected in the system. Troubleshooting may require
investigating other equipment attached to, or connected
with the chiller.
WARNING: Improper installation, oper-
ation, or servicing may result in equip-
ment damage or personal injury.
A FEW WORDS
OF CAUTION
This equipment should only be installed, adjust-
ed, and serviced by qualified technical person-
nel who are familiar with the construction, oper-
ation, and potential hazards of this type of
machine.
All wiring, disconnects, and fuses should be
installed by qualified electrical technicians in
accordance with electrical codes in your region.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
WARNING: Refrigerant hazard
Only certified refrigerant technicians should
examine and correct problems involving the
refrigerant circuit.
Series 1 Portable Chillers, TIC Control
UGH016/0500
6-2
TROUBLESHOOTING
Download from Www.Somanuals.com. All Manuals Search And Download.
The Troubleshooting section covers problems directly related
to the operation and maintenance of the portable chiller. This
section does not provide solutions to problems that originate
with other equipment. Additional troubleshooting help can be
found in manual supplied with the other equipment.
IDENTIFYING
THE CAUSE OF
A PROBLEM
Conditions you may see are:
ꢀꢀelectrical - a fuse is out, a switch has tripped
ꢀꢀmechanical - pump, condenser not working
ꢀꢀphysical - water flow incorrect
Always refer to the wiring
diagrams you received
with your chiller to locate
specific electrical compo-
nents.
As part of troubleshooting you need to know the status of the
inputs and outputs. Open the electrical enclosure and check
the status of the inputs and outputs. When they are in normal
range, the numbers are highlighted. If the number is not high-
lighted, it is out of range.
I
1 2 3 4
5
6
7
8
9 10 11 12
Inputs
DAY
TIME
O
1
2
3
4
5
6
7
8
Outputs
In this example, inputs 7 and 8 are highlighted; they are in
normal position. The unhighlighted numbers are out of range.
Refer to the wiring diagram and the following table for the
switch status:
Input
Description
Output Description
1
2
3
4
5
6
7
8
9
Chiller Stop
Chiller Start
Level Switch
Flow Switch
Compressor Running
Pump Running
Suction Pressure Switch
Discharge Pressure Switch
Low Temperature Deviation
Optional Auto-Fill Level Switch
Pressure Differential Switch
(7.5, 10, 15 ton only)
Optional Alarm Silence
1
Compressor Starter
Compressor Run Lamp
Pump Starter
Pump Run Lamp
Alarm Lamp
Optional Auto-Fill Solenoid
Optional Alarm Bell
Optional Alarm Strobe
2
3
4
5
6
7
8
10
11
12
UGH016/0500
Series 1 Portable Chillers, TIC Control
TROUBLESHOOTING 6-3
Download from Www.Somanuals.com. All Manuals Search And Download.
When an alarm condition occurs, the alarm light on the con-
trol panel lights. It stays lit until the alarm condition is cor-
rected. If you have the optional audible alarm, pressing the
Enter button silences the audible alarm.
ANSWERING AN
ALARM
To find out what is causing the alarm, check the indicator
lights on the control panel for the pump and compressor sta-
tus. If the pump and compressor are both off, check the water
tank level, flow valves, and the pump. If the pump is on and
the compressor is off, check the compressor, suction pressure
and discharge pressure.
Pump
Compressor
Status
Alarm Condition
Description
Status
Low Water Tank Level
Flow Fault
The water level in the pump tank is low.
OFF
OFF
OFF
OFF
There is no flow of the process fluid at the
pump discharge.
Pump Overload
There is a high amperage condition; the
pump is drawing too much current.
OFF
ON
OFF
OFF
OFF
OFF
Compressor Overload
High Discharge Pressure
Low Suction Pressure
There is a high amperage condition; the
compressor is drawing too much current.
The refrigerant pressure, as measured at the ON
compressor outlet is high.
The refrigerant pressure, as measured at the ON
inlet of the compressor is low.
Refer to the Troubleshooting tables and the wiring diagrams to
correct the alarm condition.
Series 1 Portable Chillers, TIC Control
UGH016/0500
6-4
TROUBLESHOOTING
Download from Www.Somanuals.com. All Manuals Search And Download.
Look here if the control panel is not lit, or if the power is on
and the Portable Chiller will not run.
CONTROL
PROBLEMS
Solution
Possible cause
Symptom
ꢀꢀCheck the power cord and
plug. Make sure the cord and
plug are properly connected.
Power is not reaching the
chiller.
The control is not lit
and the chiller is not
working.
ꢀꢀMake sure the main discon-
nect switch is on.
ꢀꢀCheck fuses and breakers.
Replace or reset as required.
Check the voltage specification
on the chiller nameplate.
The correct power is not
reaching the unit
ꢀꢀCheck fuses and replace as
needed.
There is a problem with
the TIC control.
ꢀꢀCheck the power to the tem-
perature controller. Reconnect
or replace as needed.
ꢀꢀCheck the TIC indicator
lights and replace as needed.
The control panel may have
failed. Contact Conair Service.
There is a problem with
the control panel.
UGH016/0500
Series 1 Portable Chillers, TIC Control
TROUBLESHOOTING 6-5
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROL
PROBLEMS
CONT’D
Solution
Possible cause
Symptom
Check the main supply volt-
age. It must be within 10% of
the nameplate rating.
The input voltage is
incorrect
The control is lit and
there is no alarm
condition. The com-
pressor hums, but
does not run.
ꢀꢀCheck the fuses on the main
power supply.
There is a phase loss.
ꢀꢀCheck the phase-to-phase
voltages.
ꢀꢀCheck phase continuity
through the compressor con-
tactor.
ꢀꢀCheck the wiring at the
compressor.
Replace or repair as needed.
6-6
TROUBLESHOOTING
Series 1 Portable Chillers, TIC Control
UGH016/0500
Download from Www.Somanuals.com. All Manuals Search And Download.
Look here when the Alarm/Shutdown light on the control
panel is lit. See Answering an Alarm, in the Troubleshooting
section before going to these tables.
MECHANICAL
CONDITIONS
Solution
Possible cause
Alarm
Fill tank to proper level. See
Water level in tank is low.
Low Water Tank
Level (pump and
compressor are off)
Checking Reservoir Level, in
the Maintenance section.
Inspect for leaks in the process
piping. Repair as necessary.
See Making Plumbing
Connections, in the Installation
section.
Check level gauge and com-
pare it to status of the level
switch by checking continuity
of switch in electrical enclo-
sure. Refer to wiring diagrams.
Failed Level switch.
TROUBLESHOOTING 6-7
UGH016/0500
Series 1 Portable Chillers, TIC Control
Download from Www.Somanuals.com. All Manuals Search And Download.
MECHANICAL
CONDITIONS
Solution
Possible cause
Alarm
Open valve(s).
The To Process and From
Process valves are closed.
Flow fault (pump
and compressor are
off)
Clean the strainer.
The Process Fluid strain-
er is clogged.
Fill the reservoir. See Making
Process Plumbing
Water level in reservoir is
low.
Connections, in the Installation
section.
Clean Evaporator. See
The evaporator is fouled.
Pump is not running.
Cleaning the Evaporator or
Water-cooled Condenser, in the
Maintenance section.
Check overload module.
Replace as needed. See
Replacing Overload Modules,
in the Troubleshooting section.
Switch any two of the three
main power leads to the pump.
Pump is running back-
wards.
6-8
TROUBLESHOOTING
Series 1 Portable Chillers, TIC Control
UGH016/0500
Download from Www.Somanuals.com. All Manuals Search And Download.
MECHANICAL
CONDITIONS
CONT’D
Alarm
Solution
Possible cause
Pump Overload
(pump and compres-
sor are off)
Check table on wiring diagram
for correct amperage. Adjust
overload accordingly.
Overload set incorrectly.
ꢀꢀCheck supply voltage.
Supply voltage to contactor
should be +- 10% of name-
plate voltage.
Low supply voltage.
ꢀꢀCheck wire terminations
and connections. Tighten if
loose.
Check line and load side of
contactor. It should be less
than 5 volt drop across the
contactor. If it is not, replace
the contactor. See Replacing
the Contactor in the
Faulty contactor
Troubleshooting section.
Check amp draw of circuit. If
it is under the rated setting,
replace the overload module.
See Replacing Overload
Modules, in the
Faulty overload module.
Troubleshooting section.
TROUBLESHOOTING 6-9
UGH016/0500
Series 1 Portable Chillers, TIC Control
Download from Www.Somanuals.com. All Manuals Search And Download.
MECHANICAL
CONDITIONS
CONT’D
SOLUTION
Alarm
Possible cause
Check table on wiring diagram
for correct amperage. Adjust
overload accordingly.
Compressor
Overload (pump is
running and com-
pressor is off)
Overload set incorrectly.
ꢀꢀCheck supply voltage.
Supply voltage to contactor
should be +- 10% of name-
plate voltage.
Low supply voltage.
ꢀꢀCheck wire terminations
and connections. Tighten if
loose.
Check line and load side of
contactor. It should be less
than 5 volt drop across the
contactor. If it is not, replace
the contactor. See Replacing
the Contactor in the
Faulty contactor.
Troubleshooting section.
Check amp draw of circuit. If
it is under the rated setting,
replace the overload module.
See Replacing Overload
Modules, in the
Faulty overload module.
Troubleshooting section.
6-10 TROUBLESHOOTING
Series 1 Portable Chillers, TIC Control
UGH016/0500
Download from Www.Somanuals.com. All Manuals Search And Download.
MECHANICAL
CONDITIONS
CONT’D
Solution
Possible cause
Alarm
Clean the coil. See Cleaning
the Air-cooled Condenser, in
the Maintenance section.
Clogged/dirty air-cooled
condenser.
High Discharge
Pressure (pump is
running, compressor
is off)
Move chiller or unblock air
passageway.
Blocked air flow to air-
cooled condenser.
Check required flow; see
Specifications in the
Description section.
Low condenser water
flow or water too warm
to water-cooled con-
denser.
Unblock line; open valve.
Blocked condenser water
line or valve closed.
Clean the condenser. See
Cleaning the Air-cooled
Condenser, and Cleaning the
Evaporator or Water-cooled
Condenser, in the Maintenance
section.
Water-cooled condenser
fouled.
TROUBLESHOOTING 6-11
UGH016/0500
Series 1 Portable Chillers, TIC Control
Download from Www.Somanuals.com. All Manuals Search And Download.
MECHANICAL
CONDITIONS
CONT’D
Possible cause
Solution
Alarm
Open valve.
Compressor discharge
valve closed.
High Discharge
Pressure, cont’d
See Checking the Refrigerant
Charge in the Maintenance
section.
Overcharged with refrig-
erant.
Repair or replace the valve.
Faulty water regulating
valve.
See Checking the Pressure
Switches, in the
Faulty pressure switch.
Troubleshooting section.
6-12 TROUBLESHOOTING
Series 1 Portable Chillers, TIC Control
UGH016/0500
Download from Www.Somanuals.com. All Manuals Search And Download.
MECHANICAL
CONDITIONS
CONT’D
Possible cause
Solution
Alarm
No or low flow with a
failed flow switch and
RTD.
ꢀꢀCheck To Process and From
Process valves to see if they
are open.
Low Suction
Pressure (pump is
running and com-
pressor is off)
ꢀꢀCheck Flow switch and
RTD. Replace as needed.
Compressor suction valve Open valve.
is closed.
No load on the Chiller.
Check process load for
required load. Chiller may be
oversized.
The Evaporator is fouled. Clean Evaporator. See
Cleaning the Evaporator or
Water-cooled Condenser, in the
Maintenance section.
The Evaporator is frozen. ꢀꢀCheck RTD; Replace as
needed.
ꢀꢀCheck minimum allowable
setpoint for percent glycol
used.
There is a refrigerant
leak.
Check for oil in chiller cabinet
and bubbles in refrigerant site
glass. Consult Conair Service
for repair.
See Checking Pressure
Switches, in the
Troubleshooting section.
The pressure switch is
faulty.
TROUBLESHOOTING 6-13
UGH016/0500
Series 1 Portable Chillers, TIC Control
Download from Www.Somanuals.com. All Manuals Search And Download.
MECHANICAL
CONDITIONS
CONT’D
Solution
Possible cause
Symptom
Swap any two of the three
main power leads to the com-
pressor.
Leads are backwards.
Compressor fault.
Contact Conair Service.
The compressor failed.
6-14 TROUBLESHOOTING
Series 1 Portable Chillers, TIC Control
UGH016/0500
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this unit, discon-
nect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
CHECKING AND
REPLACING
SWITCHES
The pump tank has one or two float switches. The float switch
(low level cutout) activates an alarm. There is also a flow
switch in the process fluid line to verify flow.
To replace a switch:
Disconnect and lockout power to the chiller.
1
2 Open the electrical enclosure and locate the
connection for the correct switch on the terminal switch.
Refer to the wiring diagrams you received with your
chiller to find the correct terminals.
3
Check the switch.
Check continuity within the switch and make sure it cor-
responds to the condition of the switch. Clean the switch
if needed.
Replace the switches as needed.
Drain the tank to replace the switch(es).
4
To check a flow switch:
Always refer to the wiring
diagrams that came with
your chiller to locate specific
electrical components.
Remove the electrical cover on the flow switch.
1
2
Slide the top of the switch housing over until
the N.O. (normally open) shows when electrical cover is
placed back on.
3 Replace electrical cover on flow switch.
Flow switch
Level switch
TROUBLESHOOTING 6-15
UGH016/0500
Series 1 Portable Chillers, TIC Control
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this unit, discon-
nect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
REPLACING THE
CONTACTOR
To replace contactor for the pump or compressor:
Disconnect and lockout power to the chiller.
1
2 Open the electrical enclosure and locate
the correct contactor. Refer to the wiring diagrams you
received with your chiller.
Always refer th the wiring
diagrams that came with
your chiller to locate specific
electrical components.
3
Disconnect the wiring from the contactor.
Make sure you label each wire so you can correctly install
the new unit.
4
Remove the contactor by snapping off
the DIN rail mounting.
5
6
Snap in the new contactor.
Reconnect the wiring and reconnect power
to the chiller.
Pump contactor
Compressor
contactor
6-16 TROUBLESHOOTING
Series 1 Portable Chillers, TIC Control
UGH016/0500
Download from Www.Somanuals.com. All Manuals Search And Download.
The Conair Portable Chiller uses a standard 100 ohm RTD to
monitor process temperature. Disconnect the RTD leads and
measure the resistance through the RTD. It should read 95 -
110 ohms. If it does not, the RTD is bad and needs replaced.
CHECKING AND
REPLACING THE
RTD
To replace the RTD:
Disconnect and lockout power to the chiller.
1
2 Disconnect the To Process tubing from the
To Process connection.
Fill/Drain valve
To Process
connection
3
Open the Drain/Fill valve and drain water
Always refer th the wiring
diagrams that came with
your chiller to locate specific
electrical components.
from the unit so the water level is lower that the RTD.
4 Open the side of the chiller.
5
Disconnect the RTD wiring from the
temperature controller in the top electrical panel. Refer to
the wiring diagram.
Remove the RTD.
Loosen the compression nut to slide the RTD out of the
evaporator.
6
7 Install the new RTD.
The new RTD should be inserted in the evaporator so that
the tip is extended completely through the evaporator.
8
Wire the RTD to the controller
in the top electrical enclosure.
RTD
TROUBLESHOOTING 6-17
UGH016/0500
Series 1 Portable Chillers, TIC Control
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this unit, discon-
nect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
REPLACING THE
TEMPERATURE
CONTROLLER
(TIC)
Disconnect and lockout power to the chiller.
1
2
Snap the Temperature Controller board out
of the mounting case by pressing the snaps on both sides
of the controller, and pulling outward at the same time.
Always refer to the wiring dia-
grams you received with your
chiller to locate specific elec-
trical components.
Slide the new controller in until
3
4
it snaps into place.
Contact Conair Service for the temperature
setup list. This list tells you the correct settings for the
controller parameters.
Series 1 Portable Chillers, TIC Control
UGH016/0500
6-18 TROUBLESHOOTING
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this unit, discon-
nect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
REPLACING
OVERLOAD
MODULES
Normally if the overload trips, resetting the overload and cor-
recting the cause is typically all that is needed. However, if the
overload continues to trip, it may be necessary to replace the
overload module.
To replace the overload module:
Always refer to the wiring dia-
grams you received with your
chiller to locate specific elec-
trical components.
Disconnect and lockout power to the chiller.
Open the electrical enclosure.
1
2
3
Locate the overload module and disconnect
the power leads from the module to the device. Refer to
the wiring diagram for the exact location. Note the place-
ment of each lead and label as needed.
Disconnect auxiliary wiring to the module.
Loosen the screws and remove the module.
4
5
6
Install the new module
and tighten in place with the screws.
Reconnect wires and leads.
7
8
Adjust setting to correct Full Load Amps
rating of compressor, fan or pump.
9
Restore power to the chiller.
Pump overload
module
Compressor over-
load module
UGH016/0500
Series 1 Portable Chillers, TIC Control
TROUBLESHOOTING 6-19
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Electrical hazard
Before performing any work on this unit, discon-
nect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
REPLACING
FUSES
To replace fuses:
Disconnect and lockout power to the chiller.
1
2
Open the electrical enclosure and locate
the fuses. Refer to the wiring diagram for the exact loca-
tion.
3 Remove and replace fuses.
Always refer to the wiring dia-
grams you received with your
chiller to locate specific elec-
trical components.
Restore power to the chiller.
4
Control transformer
primary fuses
Control transformer
secondary fuse
Series 1 Portable Chillers, TIC Control
UGH016/0500
6-20 TROUBLESHOOTING
Download from Www.Somanuals.com. All Manuals Search And Download.
The pump’s wet end (impeller, motor, and seal assembly) can
be removed for service.
REMOVING
PUMP
COMPONENTS
1
2
Disconnect and lockout power to the chiller.
Open the drain/fill valve.
Drain the water from the chiller.
Open
this
side
Fill/Drain valve
3 Open the side of the chiller.
4 Remove the bolts connecting the pump
assembly to the pump housing.
Remove the pump assembly.
5 Carefully slide it sideways away from the pump tank to
avoid damage.
Inspect, clean, and replace pump parts
6
as needed. Separate the pump assembly form the pump
volute (casing) by prying the flanges and pulling apart.
Follow the disassembly and reassembly procedures in the
pump manufacturer’s manual that accompanies this User
Guide.
UGH016/0500
Series 1 Portable Chillers, TIC Control
TROUBLESHOOTING 6-21
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Coolant hazard
CHECKING
PRESSURE
SWITCHES
Coolant can cause freezing of skin. All proper
precautions should be taken any time the cool-
ing system is worked on. Any adjustment that
involves the coolant should only be performed
by a certified refrigeration technician.
The pressure switch is a non-adjustable switch. To check the
pressure switch:
Locate the pressure switch.
Use the wiring diagrams that came with your chiller for
exact location. Location varies depending on size of unit.
1
Always refer to the wiring dia-
grams you received with your
chiller to locate specific elec-
trical components.
Check the connections.
2
3
Make sure all connections to the switch are secure.
Tighten as needed.
Check the control signal in the electrical panel.
Refer to the wiring diagram and the following table for
the switch status:
Inputs
I
1 2 3 4
5
6
7
8
9 10 11 12
DAY
TIME
Outputs
O
1
2
3
4
5
6
7
8
In this example, inputs 7 and 8 are highlighted; they are in
normal position. If they are not highlighted the input is out of
range.
Input
Description
Output Description
1
2
3
4
5
6
7
8
9
Chiller Stop
Chiller Start
Level Switch
Flow Switch
Compressor Running
Pump Running
Suction Pressure Switch
Discharge Pressure Switch
Low Temperature Deviation
Optional Auto-Fill Level Switch
Pressure Differential Switch
(7.5, 10, 15 ton only)
Optional Alarm Silence
1
2
3
4
5
6
7
8
Compressor Starter
Compressor Run Lamp
Pump Starter
Pump Run Lamp
Alarm Lamp
Optional Auto-Fill Solenoid
Optional Alarm Bell
Optional Alarm Strobe
10
11
12
Series 1 Portable Chillers, TIC Control
UGH016/0500
6-22 TROUBLESHOOTING
Download from Www.Somanuals.com. All Manuals Search And Download.
CHECKING
PRESSURE
SWITCHES
CONT’D
Check the continuity within the switch
4
and make sure it corresponds to the following conditions:
Item
Description
High Pressure Switches (PS-2)
Low Pressure Switches (PS-1)
Cut out @ 300 PSIG on rise
Cut out at 28 PSIG on fall
Cut in at 43 PSIG on rise
If required, check the switch with a refrigeration gauge. If
the switch does not change, as listed in this table, when
compared to a refrigeration pressure gauge, the switch is
faulty. Replace the switch.
UGH016/0500
Series 1 Portable Chillers, TIC Control
TROUBLESHOOTING 6-23
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Conair has made the largest investment in customer support in
the plastics industry. Our service experts are available to help
with any problem you might have installing and operating
your equipment. Your Conair sales representative also can help
analyze the nature of your problem, assuring that it did not
result from misapplication or improper use.
WE’RE HERE
TO HELP
To contact Customer Service personnel, call:
HOW TO CONTACT
CUSTOMER
SERVICE
From outside the United States, call: 814-437-6861
You can commission Conair service personnel to provide on-
site service by contacting the Customer Service Department.
Standard rates include an on-site hourly rate, with a one-day
minimum plus expenses.
If you do have a problem, please complete the
following checklist before calling Conair:
BEFORE YOU
CALL ...
ꢀꢀ Make sure you have all model, serial and parts list
numbers for your particular equipment. Service
personnel will need this information to assist you.
ꢀꢀꢀMake sure power is supplied to the equipment.
ꢀꢀꢀMake sure that all connectors and wires within
and between control systems and related
components have been installed correctly.
ꢀꢀ Check the troubleshooting guide of this manual
for a solution.
ꢀꢀꢀThoroughly examine the instruction manual(s)
for associated equipment, especially controls.
Each manual may have its own troubleshooting
guide to help you.
Additional manuals and
prints for your Conair
equipment may be
ordered through the
Customer Service or
Parts Departments for
a nominal fee.
ꢀꢀꢀCheck that the equipment has been operated as
described in this manual.
ꢀꢀꢀCheck accompanying schematic drawings for
information on special considerations.
IMS0002/0296
SERVICE INFORMATION
APPENDIX A-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Conair guarantees the machinery and equipment on this
order, for a period as defined in the quotation from date of
shipment, against defects in material and workmanship
under the normal use and service for which it was recom-
mended (except for parts that are typically replaced after
normal usage, such as filters, liner plates, etc.). Conair’s
guarantee is limited to replacing, at our option, the part or
parts determined by us to be defective after examination.
The customer assumes the cost of transportation of the
part or parts to and from the factory.
EQUIPMENT
GUARANTEE
Conair warrants that this equipment will perform at or
above the ratings stated in specific quotations covering the
equipment or as detailed in engineering specifications,
provided the equipment is applied, installed, operated and
maintained in the recommended manner as outlined in our
quotation or specifications.
PERFORMANCE
WARRANTY
Should performance not meet warranted levels, Conair at
its discretion will exercise one of the following options:
ꢀꢀꢀInspect the equipment and perform alterations or
adjustments to satisfy performance claims. (Charges
for such inspections and corrections will be waived
unless failure to meet warranty is due to misapplica-
tion, improper installation, poor maintenance practices
or improper operation.)
ꢀꢀꢀReplace the original equipment with other Conair
equipment that will meet original performance claims
at no extra cost to the customer.
ꢀꢀꢀRefund the invoiced cost to the customer. Credit is
subject to prior notice by the customer at which time a
Return Goods Authorization Number (RGA) will be
issued by Conair’s Service Department. Returned
equipment must be well crated and in proper operating
condition, including all parts. Returns must be prepaid.
Purchaser must notify Conair in writing of any claim and
provide a customer receipt and other evidence that a claim
is being made.
Except for the Equipment Guarantee and Performance
Warranty stated above, Conair disclaims all other war-
ranties with respect to the equipment, express or
implied, arising by operation of law, course of dealing,
usage of trade or otherwise, including but not limited to
the implied warranties of merchantability and fitness for
a particular purpose.
WARRANTY
LIMITATIONS
A-2 SERVICE INFORMATION
WARRANTY INFORMATION
IMS0003/0796
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
LOG
Reading
Date
Maintenance Item
Compressor Amps,
100% loaded
Discharge Pressure
Suction pressure
Evaporator water out
temperature
Process Water Pressure,
In/Out
Condenser Water
Temperature, In/Out
Condenser Water
Pressure, In/Out
Condenser Fan Amps (1)
Condenser Fan Amps (2)
Pump Amps
UGH016/0500
Series 1 Portable Chillers, TIC Control
APPENDIX B-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Evaporator and Piping
Pressure Drops
PRESSURE
TABLES
A1/W1-7.5
A1/W1-2
A1/W1-3
A1/W1-10, A1-13
A1/W1-5
A1/W1-1.5
A1/W1-4
W1-15
Flow Rate, GPM
UGH016/0500
Series 1 Portable Chillers, TIC Control
APPENDIX C-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Condenser and Piping
Pressure Drops
PRESSURE
TABLES
80
70
60
50
40
30
20
10
0
W1-1.5
W1-2 W1-3
W1-7.5
W1-5
W1-4
W1-10
W1-15
0
5
10
15
20
25
30
35
40
45
50
55
Flow Rate, GPM
Series 1 Portable Chillers, TIC Control
UGH016/0500
APPENDIX C-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Use this table when configuring the temperature controller.
Refer to the manufacturer’s manual that accompanies this
User Guide for detailed information.
CONTROL
SETTINGS
When the control displays the text listed in the Display col-
umn, you can scroll to, and change, the settings listed in the
Parameter column.
Display Parameter Description
Setting
Units
InP
SP.LL
SP.HL
TyPE
Lower Setpoint limit
Upper Setpoint Limit
Input sensor type
40
70
rtd
°F
°F
100 ohm rtd
DSPL
OutP
dspl
Unit
Display menu
Temperature units
----
F
-----
°F or °C
O1.ty
O1.ac
O1.cy
O1.hl
O2.ty
O2.aa
O2.ao
O2.ih
O2.SP
Output 1 Type
Output 1 action
PID
re
5
80%
ALr
nor
DE.L
En
-----
Reverse action
Seconds
% time HGV is on
-----
-----
Alarm set to low deviation
Enabled
°F Low deviation
Output 1 cycle type
Output 1 High limit
Output 2 Control Type
Output 2 Alarm 1 Action
Output 2 process
Output 2 alarm inhibit
Output 2 alarm setpoint
4
Cnrl
Pb1
der
OFFS
Int
Proportional Band-gain
Derivative Action - rate
Manual reset
1
0
OFF
0
-----
-----
-----
-----
Integral Action - reset
UGH016/0601
Series 1 Portable Chillers, TIC Control
APPENDIX D-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS & DIAGRAMS
ꢀ
Spare Parts Lists . . . . . . . . . .P/D-2
UGH016/0500
Series 1 Portable Chillers, TIC Control
P/D-1
Download from Www.Somanuals.com. All Manuals Search And Download.
RECOMMENDED
SPARE PARTS
Part
Number Description
Athena 1/32 DIN Temperature Controller
120VAC LOGO! Long
120VAC 4” Alarm Bell
20VAC White Strobe
22 mm Red extended pushbutton operator
22 mm Green flush pushbutton operator
120VAC Green Indicator light
120VAC Red indicator light
MSP-to-Contactor connecting module, 3RA1921-1A
MSP-to-Contactor connecting module, 3RA1921-1B
MSP-to-Contactor connecting module, 3RA1921-1D
MSP-to-Contactor connecting module, 3RA1931-1A
MSP-to-Contactor connecting module, 3RA1931-1B
MSP-to-Contactor connecting module, 3RA1941-1A
MSP-to-Contactor connecting module, 3RA1941-1B
3 Pole Contactor w/ 120VAC coil, 7A (AC-3)
3 Pole Contactor w/ 120VAC coil, 9A (AC-3)
3 Pole Contactor w/ 120VAC coil 12A (AC-3)
3 Pole Contactor w/ 120VAC coil, 17A (AC-3)
3 Pole Contactor w/ 120VAC coil, 25A (AC-3)
3 Pole Contactor w/ 120VAC coil, 28A (AC-3)
3 Pole Contactor w/ 120VAC coil, 32A (AC-3)
3 Pole Contactor w/ 120VAC coil, 40A (AC-3)
3 Pole Contactor w/ 120VAC coil, 50A (AC-3)
3 Pole Contactor w/ 120VAC coil, 65A (AC-3)
Motor Starter Protector (1.8-2.5A)
Motor Starter Protector (2.2-3.2A)
Motor Starter Protector (3.5-5.0A)
Motor Starter Protector (4.5-6.3A)
Motor Starter Protector (5.5-8.0A)
Motor Starter Protector (7.0-10.0A)
Motor Starter Protector (9.0-12.5A)
Motor Starter Protector (11.0-16.0A)
Motor Starter Protector (14.0-20.0A)
Motor Starter Protector (17.0-22.0A)
Series 1 Portable Chillers, TIC Control
UGH016/0500
P/D-2
SPARE PARTS
Download from Www.Somanuals.com. All Manuals Search And Download.
RECOMMENDED
SPARE PARTS
Part
Number Description
Motor Starter Protector (20.0-25.0A)
Motor Starter Protector (18.0-25.0A)
Motor Starter Protector (22.0-32.0A)
Motor Starter Protector (28.0-40.0A)
Motor Starter Protector (40.0-50.0A)
Motor Starter Protector (45.0-63.0A)
Motor Starter Protector (57.0-75.0A)
MSP Auxiliary Contact Block (2 N.O.)
MSP Line Side Feeder
MSP Feeder Lug (3RV101, 3RV102)
MSP Feeder Lug (3RV103)
Normally Open contact block
Normally Closed contact block
Control Terminal Block, Size 4
Terminal Block End Bracket
Terminal Block Barrier
Littlefuse 0.5A Fuse, 250VAC
Littlefuse 3.0A Fuse, 250VAC
Littlefuse 5.0A Fuse, 250VAC
Littlefuse 0.25A Fuse, 600VAC
Littlefuse 2.0A Fuse, 600VAC
1 Pole Fuseblock Cover Lit
Transformer Touch Safe Cover Lit
1 Pole Secondary Fuseblock
2 Pole Primary Fuseblock
Littlefuse 2 Pole Ultrasafe Fuseblock
Motorola 5 VDC Voltage Regulator
250VA Control Transformer 230x460, 110/115/120
250VA Control Transformer 550/575/600, 110/115/120
250VA Control Transformer 380/400/415, 110x120
250VA Control Transformer 208/230/460, 24/115
Pump Seal Kit, pump type 231
Pump Seal Kit, Pump type 233, 3HP
Pump Seal Kit, Pump type 233, 5HP
Pump Seal Kit, Pump type 234, 7.5HP
UGH016/0500
Series 1 Portable Chillers, TIC Control
SPARE PARTS P/D-3
Download from Www.Somanuals.com. All Manuals Search And Download.
RECOMMENDED
SPARE PARTS
Part
Number
Description
Pump Seal Kit, Pump type 233, 7.5HP and 10HP
Pump Seal Kit, Pump type 234, 10HP and 15HP
Flowtect, Flow Switch, Evap Circuit
Gems, Float Switch, Process Tank
Pressure Gauge, Dual Scale, 0-160PSIG
20973003
26636101
26629901
26638902
26638901
26638903
2663890
Discharge pressure switch, cut out at 300 PSIG on
rise, cut in at 275 PSIG on fall, 1/4” with Schreader
depressor
Suction pressure cut out at 28 PSIG on fall, cut in at
43 PSIG on rise, 1/4” with Schreader depressor
Fan Cycling Switch #1, Air-cooled Chiller, cut out at
190 PSIG on fall, Cut in at 250 PSIG on rise, 1/4”
with Schreader depressor
Fan Cycling Switch #2, Air-cooled Chiller, cut out at
200 PSIG on fall, Cut in at 270 PSIG on rise, 1/4
with Schreader depressor
20966802
331021051
8”x14’ 100ohm RTD
Differential Pressure Switch, 0-45 PSID
2920580201 Refrigerant Pressure Relief Valve, 400PSIG, Air-
cooled Chiller (1-4 ton)
2920581001 Refrigerant Pressure Relief Valve, 400PSIG, Air-
cooled Chiller (5-7.5 ton)
2920581301 Refrigerant Pressure Relief Valve, 400PSIG, Air-
cooled Chiller (10 and 13 ton)
2920580202 Refrigerant Pressure Relief Valve, 350PSIG, Water-
cooled Chiller (1.5-5 ton)
2920581302 Refrigerant Pressure Relief Valve, 350PSIG, Water-
cooled Chiller (7.5-15 ton)
2920940902 Filter Dryer, 1.5-3 ton
2920941302 Filter Dryer, 4-7.5 ton
2920941802 Filter Dryer, 10-15 ton
29213103
29213104
TXV 1.5 ton Water-cooled
TXV 1.5 ton Air-cooled, 2 ton Water- and Air-cooled
Series 1 Portable Chillers, TIC Control
UGH016/0500
P/D-4
SPARE PARTS
Download from Www.Somanuals.com. All Manuals Search And Download.
RECOMMENDED
SPARE PARTS
Part
Number Description
29213105
29213106
29213107
29213108
29213109
TXV 2 ton Water- and Air-cooled
TXV 3 ton Water- and Air-cooled
TXV 5 ton Water- and Air-cooled
TXV 7.5 ton Water- and Air-cooled
TXV 10 ton Water- and Air-cooled
292131110 TXV 13 ton Water-cooled and 15 ton Air-cooled
20958401
20958402
20958403
20958404
Liquid Line Solenoid Valve, 1-5 ton
Liquid Line Solenoid Valve, 7.5-10 ton
Liquid Line Solenoid Valve, 13-15 ton
Hot Gas Bypass Solenoid, 1.5-4 ton
20958405
20958406
Hot Gas Bypass Solenoid, 5-10 ton
Hot Gas Bypass Solenoid, 13 and 15 ton
3331302204 Air Filter, 1.5 ton Air-cooled
3331302202 Air Filter, 2 and 3 ton Air-cooled
3331302201 Air Filter, 4 and 5 ton Air-cooled
3331302203 Air Filter, 7.5-10 ton Air-cooled
3331302
Air Filter, 13 ton Air-cooled
Condenser Fan Motor, 50 watts, 400/460V, 50/60Hz, for
A1-2.25 unit
Condenser Fan Motor, 0.166HP, 400/460V, 50/60Hz, for
A1-1.5 and A1-3 units
Condenser Fan Motor, 1/4HP, 400/460V, 50/60Hz, for
A1-4 and A1-5 units
Condenser Fan Motor, 1/2HP, 400/460V, 50/60Hz, for
A1-7.5, A1-10 and A1-13 units
Condenser Fan Motor, 50 watts, 200/230V, 50/60Hz, for
A1-2.25 unit
Condenser Fan Motor, 0.166HP, 200/230V, and 575V,
50/60Hz, for A1-1.5 and A1-3 units
Condenser Fan Motor, 1/4HP, 200/230V, 50/60Hz, for
A1-4 and A1-5 units, and 575V, for A1-4 unit
Condenser Fan Motor, 1/2HP, 200/230V, 50/60Hz, for
A1-7.5, A1-10 and A1-13 units
UGH016/0500
Series 1 Portable Chillers, TIC Control
SPARE PARTS P/D-5
Download from Www.Somanuals.com. All Manuals Search And Download.
RECOMMENDED
SPARE PARTS
Part
Number
Description
Condenser Fan Motor, 1/4HP, 575V, 60 Hz for A1-5 unit
Condenser Fan Motor, 1/2HP, 575V, 60Hz, for A1-7.5,
A1-10 and A1-13 units
Condenser Fan Blade, A1-1.5
Condenser Fan Blade, A1-2.25
Condenser Fan Blade, A1-3.25
Condenser Fan Blade, A1-4 and A1-5
Condenser Fan Blade, A1-7.5, A1-10, A1-13
Water Regulating Valve, W1-1.5, W1-2, W1-3
Water Regulating Valve, W1-4, W1-5
26642001
26642002
26642102
Water Regulating 1 1/4” Control Ball Valve, W1-7.5, W1-
10, W1-15 units
Series 1 Portable Chillers, TIC Control
UGH016/0500
P/D-6
SPARE PARTS