Compaq Personal Computer UPS R3000 XR User Manual

UPS R3000 XR  
Maintenance and Service Guide  
First Edition (September 2000)  
Part Number 221891-001  
Spare Part Number 223932-001  
Compaq Computer Corporation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
About This Guide  
Symbols in Text ..........................................................................................................v  
Compaq Technician Notes .........................................................................................vi  
Where to Go for Additional Help...............................................................................vi  
Telephone Numbers ...........................................................................................vii  
Chapter 1  
Before You Begin  
Safety and Product Information................................................................................1-1  
Symbols on Equipment .....................................................................................1-1  
Technician Notes...............................................................................................1-2  
Rack ..................................................................................................................1-2  
Weight...............................................................................................................1-2  
Communication Ports........................................................................................1-3  
Extended Runtime Modules and Batteries ........................................................1-3  
Remote Emergency Power Off (REPO)............................................................1-4  
Chapter 2  
Illustrated Parts List  
Exploded View.........................................................................................................2-2  
Chapter 3  
Removal and Replacement Procedures  
Before You Begin.....................................................................................................3-1  
Replaceable Parts ..............................................................................................3-1  
Tools Required..................................................................................................3-2  
Identifying Components...........................................................................................3-2  
Front Panel ........................................................................................................3-2  
Front Panel Controls and LED Display.............................................................3-3  
Rear Panel Components ....................................................................................3-4  
Modes of Operation..................................................................................................3-6  
Standby Mode ...................................................................................................3-6  
Operate Mode....................................................................................................3-6  
Configure Mode ................................................................................................3-6  
Auto-Bypass Mode............................................................................................3-6  
Powering Down the UPS..........................................................................................3-7  
Emergency Shutdown .......................................................................................3-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iv Compaq UPS R3000 XR Maintenance and Service Guide  
Removal and Replacement Procedures  
continued  
Replacing the UPS Battery Pack ..............................................................................3-8  
Disposing of Used Batteries............................................................................3-10  
Replacing the Electronics Module..........................................................................3-11  
Replacing an Option or Communication Board .....................................................3-14  
Replacing the UPS Unit..........................................................................................3-16  
Extended Runtime Modules ...................................................................................3-17  
Replacing ERM Battery Packs........................................................................3-17  
Replacing an ERM ..........................................................................................3-20  
Chapter 4  
Troubleshooting  
Troubleshooting During Start...................................................................................4-1  
Troubleshooting After Start......................................................................................4-2  
Chapter 5  
Specifications  
Physical Specifications.............................................................................................5-1  
Input Specifications..................................................................................................5-2  
Output Specifications ...............................................................................................5-3  
Overcurrent Protection .............................................................................................5-5  
Battery Specifications...............................................................................................5-5  
Battery Runtime .......................................................................................................5-5  
Environmental Specifications...................................................................................5-6  
Index  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About This Guide  
This Maintenance and Service Guide is a troubleshooting guide that can be used for reference  
when servicing Compaq R3000 XR series of Uninterruptible Power Systems (UPSs).  
WARNING: To reduce the risk of personal injury from electrical shock and hazardous energy  
levels, only authorized service technicians should attempt to repair this equipment. Improper  
repairs could create conditions that are hazardous.  
IMPORTANT: The installation of options and servicing of this product shall be performed by individuals  
who are knowledgeable of the procedures, precautions, and hazards associated with equipment  
containing hazardous energy circuits.  
Symbols in Text  
These symbols may be found in the text of this guide. They have the following meanings:  
WARNING: Text set off in this manner indicates that failure to follow directions in the warning  
could result in bodily harm or loss of life.  
CAUTION: Text set off in this manner indicates that failure to follow directions could result in  
damage to equipment or loss of information.  
IMPORTANT: Text set off in this manner presents clarifying information or specific instructions.  
NOTE: Text set off in this manner presents commentary, sidelights, or interesting points of information.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
vi Compaq UPS R3000 XR Maintenance and Service Guide  
Compaq Technician Notes  
WARNING: Only authorized technicians trained by Compaq should attempt to repair this  
equipment. All troubleshooting and repair procedures are detailed to allow only  
subassembly/module level repair. Because of the complexity of the individual boards and  
subassemblies, no one should attempt to make repairs at the component level or to make  
modifications to any printed wiring board. Improper repairs can create a safety hazard. Any  
indications of component replacement or printed wiring board modifications may void any  
warranty.  
WARNING: To reduce the risk of personal injury from electrical shock and hazardous energy  
levels, do not exceed the level of repair specified in these procedures. Because of the  
complexity of the individual boards and subassemblies, do not attempt to make repairs at the  
component level or to make modifications to any printed wiring board. Improper repairs could  
create conditions that are hazardous.  
WARNING: To reduce the risk of electric shock or damage to the equipment:  
If the system has multiple power supplies, disconnect power from the system by  
unplugging all power cords from the power supplies.  
Do not disable the power cord grounding plug. The grounding plug is an important safety  
feature.  
Plug the power cord into a grounded (earthed) electrical outlet that is easily accessible at  
all times.  
CAUTION: To properly ventilate your system, you must provide at least 12 inches (30.5 cm) of  
clearance at the front and back of the UPS.  
CAUTION: The UPS is designed to be electrically grounded. To ensure proper operation, plug  
the AC power cord into a properly grounded AC outlet only.  
Where to Go for Additional Help  
In addition to this guide, the following information sources are available:  
User Documentation  
Compaq Service Quick Reference Guide  
Service Training Guides  
Compaq Service Advisories and Bulletins  
Compaq QuickFind  
Compaq Insight ManagerTM  
Compaq Download Facility: Call 1-281-518-1418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About This Guide vii  
Telephone Numbers  
For the name of your nearest Compaq Authorized Reseller:  
In the United States, call 1-800-345-1518  
In Canada, call 1-800-263-5868  
For Compaq technical support:  
In the United States and Canada, call 1-800-386-2172  
For Compaq technical support phone numbers outside the United States and Canada, visit  
the Compaq website at  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter  
1
Before You Begin  
Safety and Product Information  
WARNING: The Compaq Uninterruptible Power System (UPS) R3000 XR contains  
hazardous voltage levels and energy circuits. There is a risk of personal injury from  
electrical shock and hazardous energy levels. Persons performing installation or service  
procedures must be Trained Service Technicians, knowledgeable about the procedures,  
precautions, and hazards associated with AC Power Products.  
Symbols on Equipment  
These icons may be located on equipment in areas where hazardous conditions may exist.  
Any surface or area of the equipment marked with these symbols indicates the  
presence of electrical shock hazards. Enclosed area contains no operator  
serviceable parts.  
WARNING: To reduce risk of injury from electrical shock hazards, do not open this  
enclosure.  
Any surface or area of the equipment marked with these symbols indicates the  
presence of a hot surface or hot component. If this surface is contacted, the  
potential for injury exists.  
WARNING: To reduce the risk of injury from a hot component, allow the surface to  
cool before touching.  
Any product or assembly marked with these symbols indicates that the component  
exceeds the recommended weight for one individual to handle safely.  
WARNING: To reduce the risk of personal injury or damage to the equipment,  
weight kg  
observe local health and safety requirements and guidelines for manual material  
weight lb  
handling.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1-2 Compaq UPS R3000 XR Maintenance and Service Guide  
Technician Notes  
WARNING: To reduce the risk of personal injury from electrical shock and hazardous energy  
levels:  
Only authorized technicians trained by Compaq should attempt to repair this equipment.  
The installation of options and routine maintenance and service of this product must be  
performed by Trained Service Technicians who are knowledgeable about the procedures,  
precautions, and hazards associated with AC Power Products.  
Do not exceed the level of repair specified in these procedures. All troubleshooting and  
repair procedures are detailed to allow only subassembly/module level repair. Because of  
the complexity of the individual boards and subassemblies, no one should attempt to make  
repairs at the component level or to make modifications to any printed wiring board.  
Improper repairs can create a safety hazard.  
Remove all watches, rings, and any other metal or loose-fitting jewelry.  
Avoid the use of conductive tools that could bridge live parts.  
Rack  
WARNING: To reduce the risk of personal injury or damage to the equipment, ensure that:  
The leveling jacks are extended to the floor.  
The full weight of the rack rests on the leveling jacks.  
The stabilizing feet are attached to the rack for a single rack installation.  
The racks are coupled in multiple rack installations.  
You extend only one component at a time. A rack may become unstable if more than one  
component is extended for any reason.  
Weight  
WARNING: The UPS R3000 XR weighs 82 lb (37 kg) when fully assembled. The  
battery pack weighs 42 lb (19 kg). To reduce the risk of personal injury or  
damage to the equipment:  
82 lb  
37 kg  
Observe local health and safety requirements and guidelines for manual  
material handling.  
Obtain adequate assistance to lift and stabilize the product during  
installation or removal.  
Remove all pluggable options and batteries to reduce the overall weight of  
the product.  
Install the UPS R3000 XR and the Extended Runtime Modules (ERMs) only at  
the bottom of the rack. If placed in a rack with existing equipment, the rack  
must be reconfigured to allow installation of the UPS at the bottom of the  
rack.  
Mount the UPS R3000 XR only on the fixed rails included in the UPS  
package. Refer to the appropriate installation card and rack template,  
shipped with the UPS R3000 XR kit, for instructions on rack-mounting the  
UPS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Before You Begin 1-3  
Communication Ports  
CAUTION: To reduce the risk of damage to the equipment, only use the DE9 UPS/Computer  
Interface cable supplied by Compaq (part number 201092-00X) to connect the communications  
port to the host computer. Do not use standard RS-232 cables.  
This UPS/Computer Interface Cable carries power and is specifically designed for UPS  
communications.  
Extended Runtime Modules and Batteries  
Observe these precautions when handling or connecting batteries and Extended Runtime  
Modules.  
WARNING: To reduce risk of personal injury from electric shock or damage to equipment:  
A Trained Service Technician must install all batteries and the Extended Runtime Modules  
(ERMs).  
Do not attempt to replace batteries unless all battery circuit breakers on any connected  
ERMs are in the OFF (down) position. There is a 120-volt potential across the batteries.  
WARNING: To reduce the risk of personal injury or equipment damage, adhere to the following  
precautions when handling batteries:  
Make sure that only qualified personnel handle or connect the batteries.  
Remove watches, rings, or other metal objects prior to working with the equipment.  
Use tools with insulated handles.  
Do not attempt to replace batteries unless all battery circuit breakers on any connected  
ERMs are in the OFF (down) position. There is a 120-volt potential across the batteries.  
This UPS contains sealed lead-acid batteries. To reduce the risk of fire or chemical burns,  
adhere to the following precautions:  
Do not attempt to recharge batteries after removal from the UPS.  
Do not disassemble, crush, or puncture the batteries.  
Do not short the external contacts of the batteries.  
Do not immerse the batteries in water.  
Do not expose the batteries to temperatures higher than 60°C or dispose of in fire.  
Use only the Compaq battery spare designated for this UPS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1-4 Compaq UPS R3000 XR Maintenance and Service Guide  
THIS PRODUCT CONTAINS  
A NONSPILLABLE BATTERY  
Next Recharge Date:  
14-DEC-01  
Please refer to Maintenance Section  
of Owner's Manual enclosed inside  
Figure 1-1. Checking the battery recharge date label  
IMPORTANT: Do not use the batteries if the recharge date has passed (Figure 1-1). If the date on the  
Battery Recharge Date Label has passed without the batteries being recharged, contact an Authorized  
Compaq Service Representative.  
IMPORTANT: Compaq recommends that you do not maintain an inventory of spare batteries on-site  
unless you implement a procedure to keep these batteries charged while in storage.  
Do not dispose of used batteries with general office or household waste.  
Return the used battery for proper disposal to:  
Compaq, your authorized Compaq Partners, or their agents  
A recycling center that meets all local environmental standards  
Pb  
Remote Emergency Power Off (REPO)  
If the UPS R3000 XR is to be installed in a computer equipment room, it must be connected to a  
Remote Emergency Power Off (REPO) circuit. The UPS R3000 XR REPO port is designed to  
meet the requirements stated in National Electrical Code (NFPA 70) Article 645-10 and 11 in  
North America or the equivalent local and/or national wiring regulations.  
WARNING: To reduce risk of personal injury or damage to equipment:  
Only a licensed electrician can wire the REPO port.  
Verify that the main breaker switch is in the OFF position before wiring the REPO port.  
In North America, the REPO circuit must comply with the NEC (NFPA 70, Article 725) for a  
Class 2 circuit. The REPO port wiring must also meet all other national and local standards  
in the area in which it is installed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter  
2
Illustrated Parts List  
This chapter provides the illustrated parts breakdown and a spare parts list for the Compaq UPS  
R3000 XR. See Table 2-1 for the names of referenced spare parts.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-2 Compaq UPS R3000 XR Maintenance and Service Guide  
Exploded View  
6
5
2
1
3
4
Figure 2-1. Exploded view, Compaq UPS R3000 XR  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Illustrated Parts List 2-3  
Table 2-1  
UPS Spares Parts List  
Ref  
1
Description  
UPS Chassis  
Front Bezel  
Spares Part #  
**  
2
204507-001  
204506-001  
216097-001*  
204503-001  
**  
3
Electronics Module (low voltage)  
Electronics Module (high voltage)  
UPS Battery Pack  
4
5
6
7
Battery Bracket  
X-Slot Serial Board  
204514-001  
UPS L530-NA  
222383-001*  
222383-291*  
222384-001*  
222385-002*  
222386-021*  
204505-001*  
204504-001*  
322578-002*  
UPS L530-JP  
UPS 620H-NA  
UPS DTC-INTL  
UPS 309-EURO  
8
Cord Retention Clip  
Front and Rear Mounting Brackets  
Mounting Rail  
9
-
q
Maintenance and Service Guide  
223932-001*  
Cables  
w
UPS to server interface cable  
UPS to UPS interface cable  
204508-001*  
204509-001*  
e
* Not shown  
** No spare available  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-4 Compaq UPS R3000 XR Maintenance and Service Guide  
15  
15  
16  
17  
14  
14  
Figure 2-2. Exploded view, Extended Runtime Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Illustrated Parts List 2-5  
Table 2-2  
Extended Runtime Module Spares Parts List  
Ref  
r
Description  
Spares Part #  
204503-001  
**  
Battery Packs  
t
Battery Brackets  
y
Front Bezel  
204511-001  
**  
u
Chassis for Extended Runtime Module  
Extended Runtime Module  
Front and Rear Mounting Brackets  
Mounting Rail  
i
204510-001*  
204504-001*  
322578-002*  
o
p
Cables  
a
ERM to UPS Cable  
216092-001*  
* Not shown  
** No spare available  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter  
3
Removal and Replacement Procedures  
This chapter provides guidance for removing and replacing spare parts in the Compaq UPS  
R3000 XR.  
Before You Begin  
WARNING: The Compaq UPS R3000 XR is a high-energy product. There is a risk of personal  
injury from electrical shock and hazardous energy levels. Persons performing installation or  
service procedures must be Trained Service Technicians, knowledgeable about the procedures,  
precautions, and hazards associated with high-energy AC Power Products.  
Before beginning any of the procedures in this chapter, read and understand the cautions and  
warnings in Chapter 1, “Before You Begin.”  
Replaceable Parts  
The UPS R3000 XR contains the following replaceable parts:  
! Front bezel  
! UPS battery pack  
! Electronics module  
! Option or communication board  
! UPS unit  
! ERM battery packs  
! Extended Runtime Modules (ERMs)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-2 Compaq UPS R3000 XR Maintenance and Service Guide  
Tools Required  
To service a UPS R3000 XR, you need one or more of the following:  
#2 Phillips screwdriver  
¼-inch driver  
Compaq Power Management Utility (from the Compaq SmartStartTM and Support  
Software CD)  
Voltmeter to verify the nominal voltages to ensure proper configuration  
Identifying Components  
Use the following illustrations to locate and identify the components of the UPS R3000 XR.  
Front Panel  
1
2
3
Figure 3-1. Front panel  
Table 3-1  
Front Panel Component Identification  
Item  
1
Description  
Battery compartment  
Control buttons  
LED display  
2
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-3  
Front Panel Controls and LED Display  
The UPS front panel contains four control buttons and ten LEDs that create the interface for  
setup, configuration, load control, and status monitoring.  
1
2
3
4
5
15  
6
7
8
9
14  
10  
13  
12  
11  
Figure 3-2. Front panel controls and LED display with front bezel removed  
Table 3-2  
Front Panel Controls and LED Display  
Item  
1
Name  
Function  
General Alarm  
On Battery  
Indicates a general alarm when red  
Indicates that the battery is on when red  
Indicates that the battery is bad or low when red  
2
Bad Battery/Low  
Battery  
3
Site Wiring Fault  
Indicator  
Indicates a wiring fault when red  
4
5
Utility LED  
Indicates that:  
The unit is in Auto-Bypass mode when red  
The utility voltage is present and output is on when green  
The utility input voltage is outside nominal range when flashing red  
The utility voltage is present and the UPS is in Standby mode when  
flashing green  
6
7
Overload LED  
Indicates that the UPS exceeds maximum power available when red  
76% to 100% load  
Indicates that the UPS is approximately 76% to 100% of the maximum  
power available when green  
continued  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-4 Compaq UPS R3000 XR Maintenance and Service Guide  
Table 3-2  
Front Panel Controls and LED Display continued  
Item  
Name  
Function  
8
51% to 75% load  
Indicates that the UPS is approximately 51% to 75% of the maximum  
power available when green  
9
-
q
26% to 50% load  
0% to 25% load  
Indicates that the UPS is approximately 26% to 50% of the maximum  
power available when green  
Indicates that the UPS is approximately 0% to 25% of the maximum  
power available when green  
Configure mode  
on LED  
Indicates that the UPS is in Configure mode  
w
e
Configure button  
Places the UPS in Configure mode  
TEST/ALARM  
RESET button  
Initiates a self-test and silences audio alarms  
r
t
STANDBY button  
ON button  
Places the UPS in Standby mode  
Places the UPS in Operate mode  
Rear Panel Components  
1
2
3
4
5
6
7
11  
10  
8
9
Figure 3-3. Low voltage unit rear panel components  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-5  
1
2
3
4
5
6
7
11  
10  
9
8
Figure 3-4. High voltage unit rear panel components  
Table 3-3  
Rear Panel Components  
Item  
1
2
3
4
5
6
7
8
9
:
;
Description  
REPO port  
ERM connector  
Communications port/Options slot  
Load segment 1  
Load segment 2  
Load segment 3  
Load segment circuit protectors  
Compaq PDU output receptacle (Load segment 1)  
Cord retention clip attachment locations  
Ground bonding screw  
Power cord with plug  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-6 Compaq UPS R3000 XR Maintenance and Service Guide  
Modes of Operation  
The UPS has four modes of operation: Standby, Operate, Configure, and Auto-Bypass.  
Standby Mode  
Place the UPS in Standby mode by pressing the STANDBY button on the front panel. During  
Standby mode:  
No power is available at the UPS output receptacles.  
The UPS charges the batteries as necessary.  
Operate Mode  
Place the UPS in Operate mode by pressing the ON button on the front panel. During  
Operate mode:  
Power is available at the UPS output receptacles.  
The UPS charges the batteries as necessary.  
Configure Mode  
Place the UPS in Configure mode by removing the front bezel and pressing and holding the  
Configure button on the front panel until the Configure mode on LED turns solid green. In the  
Configure mode, the front panel LED display changes function. The LED display and control  
buttons let you monitor and change the UPS configuration parameters.  
In the Configure mode:  
Press the ON button to advance to the next configuration mode.  
Press the TEST/ALARM RESET button to accept the select configuration.  
Press the STANDBY button to turn the LED configuration on or off.  
While the UPS is in Configure mode:  
Power is available at the UPS output receptacles.  
The UPS charges the batteries as necessary.  
The configuration of the UPS can be updated.  
Auto-Bypass Mode  
The UPS automatically switches to Auto-Bypass mode if the following conditions occur:  
The power (wattage) to the unit reaches a percentage greater than 110 percent for 10  
cycles or 103 percent for 30 seconds.  
The UPS power module fails or is removed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-7  
Powering Down the UPS  
To completely remove power from the UPS:  
1. Power down all equipment being supported by the UPS (attached loads).  
2. Place the UPS in Standby mode by pressing the STANDBY button on the front panel.  
3. Disconnect the UPS from utility power.  
4. Wait at least 60 seconds for the UPS internal circuitry to discharge.  
Emergency Shutdown  
Compaq UPS R3000 XR models include a Remote Emergency Power Off (REPO) port as  
required by the National Electric Code (NFPA 70). The REPO port allows you to shut the UPS  
down from a remote location. You can connect the REPO ports of multiple UPSs to a single  
switch or circuit to shut down your entire system in an emergency.  
IMPORTANT:  
The REPO feature shuts down protected devices immediately and does not follow the orderly  
shutdown procedure initiated by Compaq Power Management Software.  
The REPO feature shuts down devices that are operating under either utility or battery power.  
If the UPS was operating on battery power when the remote switch was closed, no power will be  
available to the devices until utility power is restored and the devices are manually powered up.  
The UPS R3000 XR REPO circuit is an IEC950 Secondary Extra Low Voltage (SELV) circuit.  
The computer room Emergency Power shutdown circuit conductors that connect to the REPO  
terminals must:  
Meet the requirements of an NEC Class 2 circuit or IEC950 Secondary Extra Low Voltage  
(SELV) circuit  
Be separated from any hazardous voltage circuits or conductors by reinforced insulation  
Short the UPS R3000 XR REPO terminals.  
Disconnect the UPS R3000 XR AC input source.  
To shut down the system:  
1. Place the UPS on Standby.  
2. Disconnect the mains by opening the switch or circuit breaker at the utility panel.  
WARNING: To reduce the risk of electrical shock and/or equipment damage, use a  
Lockout/Tagout procedure to isolate the UPS R3000 XR from AC power before wiring the  
product or replacing a non-hot-plug component.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-8 Compaq UPS R3000 XR Maintenance and Service Guide  
Replacing the UPS Battery Pack  
When the Bad Battery/Low Battery LED 1 turns red, the battery pack will need to be replaced  
within 30 to 60 days.  
1
100%  
25%  
1
Figure 3-5. Bad Battery/Low Battery LED  
Verify that battery replacement is required by initiating a UPS self-test (press the  
TEST/ALARM RESET button). If the red LED is still flashing after the test, replace the  
batteries.  
NOTE: Depending on usage and environmental conditions, the batteries should last three to six years.  
The battery packs are accessed from the front of the unit.  
NOTE: Batteries can be replaced (hot-swapped) without powering off the UPS if the UPS is not supplying  
battery power to devices (utility is present, indicating that the UPS is supplying utility power). To replace  
batteries with the UPS power off, follow the procedure in “Powering Down the UPS,” in this chapter.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-9  
To replace the battery pack:  
1. Obtain access to the battery pack by pulling on both ends of the front bezel 1 to remove  
it.  
2. Locate the two screws 2 on the metal battery bracket 3.  
3
1
2
Figure 3-6. Removing the front bezel  
3. Remove the two screws 1 and lift off the metal battery bracket 2.  
1
2
1
Figure 3-7. Removing the battery bracket  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-10 Compaq UPS R3000 XR Maintenance and Service Guide  
4. Pull out the battery pack. Set aside the used battery pack for proper disposal. See  
“Disposing of Used Batteries,” in this chapter.  
Figure 3-8. Removing the battery pack  
WARNING: The UPS R3000 XR battery pack weighs 42 lb (19 kg). Prepare the area and  
observe all materials handling procedures for removing the battery pack.  
5. Slide the new battery pack into the chassis.  
6. Replace the metal battery bracket and secure the two screws.  
7. Snap on the front bezel.  
8. Initiate a UPS self-test by pressing the TEST/ALARM RESET button.  
Disposing of Used Batteries  
The UPS uses sealed lead/acid batteries that must be disposed of in accordance with local  
environmental regulations and laws.  
If a local approved recycle/disposal site is not available, your replacement battery kit includes  
the instructions and packaging required to return used batteries to an appropriate location for  
disposal.  
Do not dispose of used batteries with general office or household waste.  
Return the used battery for proper disposal to:  
!
!
Compaq, your authorized Compaq Partners, or their agents  
A recycling center that meets all local environmental standards  
Pb  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-11  
Replacing the Electronics Module  
NOTE: The electronics module can be replaced (hot-swapped) without powering off the UPS. To replace  
the electronics module with the UPS power off, follow the procedure in “Powering Down the UPS,” in this  
chapter.  
CAUTION: To avoid dropping the load while hot-swapping the electronics module, hold down  
the TEST/ALARM RESET button while sliding the new electronics module into the chassis. The  
TEST/ALARM RESET button is located on the UPS front panel.  
To replace the electronics module:  
1. Disconnect the communications cable.  
Figure 3-9. Disconnecting the communications cable  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-12 Compaq UPS R3000 XR Maintenance and Service Guide  
2. Obtain access to the electronics module by pulling on both ends of the front bezel 1 to  
remove it.  
3. Locate the two screws 2 on the electronics module 3.  
2
3
1
Figure 3-10. Removing the front bezel  
4. Remove the two screws 1 and pull out the electronics module 2.  
2
1
Figure 3-11. Removing the electronics module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-13  
CAUTION: To avoid dropping the load while hot-swapping the electronics module, hold down  
the TEST/ALARM RESET button while sliding the new electronics module into the chassis.  
3. Hold down the TEST/ALARM RESET button 1 on the front panel of the new electronics  
module and slide the electronics module into the chassis 2. Do not release the  
TEST/ALARM RESET button until the electronics module is firmly seated in the  
connector, the Configure mode on LED flashes green, and a UPS self-test begins (about  
four seconds).  
1
2
Figure 3-12. Inserting the electronics module  
5. Secure the two screws.  
6. Snap on the front bezel.  
7. Attach the communications cable.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-14 Compaq UPS R3000 XR Maintenance and Service Guide  
Replacing an Option or Communication Board  
NOTE: The option or communication board can be replaced (hot-swapped) without powering off the UPS.  
To replace the option or communication board with the UPS power off, follow the procedure in “Powering  
Down the UPS,” in this chapter.  
To remove an option or communication board:  
1. Disconnect the external cable from the board.  
Figure 3-13. Disconnecting option board cables  
2. If the UPS is powered down, proceed to step 3.  
If hot-swapping the board, remove the electronics module. See steps 2 through 4 in  
“Replacing the Electronics Module.” The UPS switches to Auto-Bypass mode.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-15  
3. Remove the screws securing the board to the UPS.  
4. Pull the board out of the unit.  
Figure 3-14. Removing an option board  
5. Slide the new board into the UPS.  
6. Tighten the screws that secure the board to the UPS.  
7. If the UPS is powered down, proceed to step 8.  
If hot-swapping the board, replace the electronics module. See steps 5 through 7 in  
“Replacing the Electronics Module.”  
CAUTION: To avoid dropping the load, hold down the TEST/ALARM RESET button while sliding  
the new electronics module into the chassis.  
8. Reconnect the external cable.  
NOTE: Replacing the communication board resets the timer and schedules.  
NOTE: The power management software may need to be rebooted after hot-swapping the board.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-16 Compaq UPS R3000 XR Maintenance and Service Guide  
Replacing the UPS Unit  
To replace the UPS:  
1. Power down the UPS. Follow the procedure in “Powering Down the UPS,” in this chapter.  
2. Turn all battery circuit breakers on the ERMs (one circuit breaker each) to the Off  
position.  
Figure 3-15. Switching the circuit breaker to the Off position  
3. Unplug the UPS power cable.  
4. Unplug connected devices and remove the retention clips that secure device cables to the  
UPS.  
5. Unplug an attached ERM from the back of the UPS.  
Figure 3-16. Unplugging the Extended Runtime Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-17  
6. Remove the UPS front bezel.  
7. Remove the screws that secure the UPS to the front of the rack.  
8. Remove the UPS from the rack.  
9. To replace the UPS, place the new unit in the rack and reverse steps 1 through 7.  
Extended Runtime Modules  
Extended Runtime Modules (ERMs) are supported by the Compaq UPS R3000 XR. The UPS  
rear panel provides a power receptacle where the module is attached. The UPS R3000 XR ERM  
contains two battery packs in a 2U chassis and extends the available UPS runtime up to 30  
minutes.  
NOTE: These figures were derived using the Compaq-recommended 80 percent load.  
Replacing ERM Battery Packs  
NOTE: The battery packs can be replaced (hot-swapped) without powering down the UPS.  
To remove battery packs from an ERM:  
1. Switch the circuit breaker on the rear of the ERM to the Off position.  
Figure 3-17. Switching the circuit breaker to the Off position  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-18 Compaq UPS R3000 XR Maintenance and Service Guide  
2. Obtain access to the battery packs by pulling on both ends of the ERM front bezel to  
remove it.  
Figure 3-18. Removing the ERM front bezel  
3. Remove two screws 1 from each metal battery bracket and lift off the battery brackets 2.  
1
2
1
Figure 3-19. Removing the battery bracket  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal and Replacement Procedures 3-19  
4. Pull out the battery packs. Set aside the used battery packs for proper disposal. See  
“Disposing of Used Batteries,” in this chapter.  
Figure 3-20. Removing the battery packs  
5. To replace the battery packs, reverse steps 1 through 4.  
NOTE: The right battery pack is inserted upside down.  
NOTE: To increase the useful life of the replacement battery, replace all batteries in the UPS and  
connected ERMs at the same time.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-20 Compaq UPS R3000 XR Maintenance and Service Guide  
Replacing an ERM  
To replace an ERM:  
1. Turn all battery circuit breakers on all attached ERMs (one circuit breaker each) to the Off  
position.  
2. Unplug the ERM from the back of the UPS.  
Figure 3-21. Unplugging the Extended Runtime Module  
4. Remove the front bezel from the ERM you want to replace.  
5. Remove the screws that secure the ERM to the front of the rack.  
6. Remove the ERM from the rack.  
7. To replace the ERM, place the new ERM in the rack and reverse steps 1 through 4.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter  
4
Troubleshooting  
This chapter provides information on the following topics:  
Troubleshooting problems that occur during UPS start  
Troubleshooting problems that occur after UPS start  
Troubleshooting During Start  
If problems occur when starting the Compaq UPS R3000 XR models, select the appropriate  
symptom for possible causes and suggested actions.  
Table 4-1  
Troubleshooting Guide (UPS Start)  
Symptom  
Possible Cause  
Suggested Action  
UPS will not start  
There is no utility power and the  
batteries are not charged.  
Check the power at the utility  
power receptacle or contact a  
qualified electrician.  
The UPS power cord is  
disconnected.  
Connect the power cord.  
Site Wiring Fault LED is red  
The utility power receptacle is  
ungrounded or there is no ground  
wire in the UPS power cord.  
Contact a qualified electrician to  
correct the condition.  
Line and neutral wires are  
reversed in the utility power  
receptacle or in the UPS power  
cord.  
For units factory-configured for  
200V or 208V, the Site Wiring  
Fault function has been disabled.  
If reconfiguring a 230V unit to  
operate at 208V, the Site Wiring  
Fault function must be manually  
disabled.  
(high voltage models only)  
continued  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-2 Compaq UPS R3000 XR Maintenance and Service Guide  
Table 4-1  
Troubleshooting Guide (UPS Start) continued  
Symptom  
Possible Cause  
Suggested Action  
Bad Battery/Low Battery LED is  
flashing red  
Battery voltage is low because the  
UPS has been out-of-service for a  
long period.  
Allow the UPS to charge the  
batteries for 24 hours. Initiate a  
self-test. If the LED does not turn  
off, replace the batteries.  
The battery test failed.  
Allow the UPS to charge the  
batteries for 24 hours. Initiate a  
self-test. If the LED does not turn  
off, replace the batteries.  
The battery is disconnected.  
Install the battery pack. If the  
battery pack is installed, remove it  
and then insert it again.  
Troubleshooting After Start  
For problems that occur after the UPS has gone through the startup self-test sequence, these  
suggested actions address possible causes.  
Table 4-2  
Troubleshooting Guide (After Start)  
Symptom  
Possible Cause  
Suggested Action  
Audio Alarm sounds  
An alarm condition exists.  
Identify the red LED associated  
with the alarm condition. Check  
this troubleshooting guide to  
determine the cause of the alarm.  
Utility LED and On Battery LED are  
flashing red  
The utility voltage is too high.  
The utility voltage is higher than  
the UPS operating range. The UPS  
switches to battery power. If this  
happens repeatedly, update the  
configuration.  
Contact a qualified electrician to  
ensure that utility power is  
suitable for the UPS.  
Utility LED and On Battery LED are  
flashing red  
The utility voltage is too low.  
The utility voltage is lower than  
the UPS operating range. The UPS  
switches to battery power. If this  
happens repeatedly, update the  
configuration.  
Contact a qualified electrician to  
ensure that utility power is  
suitable for the UPS.  
continued  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting 4-3  
Table 4-2  
Troubleshooting Guide (After Start) continued  
Symptom  
Possible Cause  
Suggested Action  
Utility LED and On Battery LED are  
flashing red  
The utility frequency is out of  
tolerance.  
Contact a qualified electrician to  
ensure that utility power is  
suitable for the UPS.  
Utility LED is flashing red  
The utility input voltage is outside  
the ±12% nominal range.  
If this happens repeatedly, check  
the input voltage and reconfigure  
the unit.  
Contact a qualified electrician to  
ensure that utility power is  
suitable for the UPS.  
Utility LED is flashing green  
The utility power is within the  
acceptable range, but the output  
is off.  
Press the ON button.  
UPS frequently switches between  
utility and battery power  
There are utility power variations.  
The utility voltage is frequently  
outside the UPS operating range.  
Update the configuration.  
Contact a qualified electrician to  
ensure that utility power is  
suitable for the UPS.  
Overload LED is red  
Protected devices are exceeding  
the UPS power rating.  
Remove one or more devices to  
reduce the power requirements.  
(UPS may switch from utility to  
Auto-Bypass.)  
Make sure that the devices are  
not defective.  
On Battery LED is flashing red  
There is low battery voltage.  
If the UPS is supplying battery  
power, save current work and  
shut down the system. Allow the  
batteries to charge.  
If the UPS is supplying utility  
power, no intervention is required.  
Allow the batteries to charge.  
Insufficient warning of low  
batteries  
Battery service is required.  
Allow the batteries to charge for  
24 hours, then initiate a self-test.  
If the LED is red, replace the  
batteries.  
The Shutdown Delay configuration  
is inappropriate.  
Use the Compaq power  
management software to specify  
a suitable delay.  
continued  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-4 Compaq UPS R3000 XR Maintenance and Service Guide  
Table 4-2  
Troubleshooting Guide (After Start) continued  
Symptom  
Possible Cause  
Suggested Action  
Utility LED is flashing red and the  
unit is in Auto-Bypass mode  
A potential for overload exists.  
Reduce the load.  
An over-temperature condition  
may exist.  
Ensure that there is no blockage  
of airflow to the front bezel and  
rear panel.  
The electronics module may have  
failed.  
Replace the electronics module.  
Bad Battery/Low Battery LED is  
flashing red  
A potential battery failure has  
been detected.  
Allow the batteries to charge for  
24 hours, then initiate a self-test.  
If the LED is red, replace the  
batteries.  
New batteries are improperly  
connected.  
Reinsert the battery pack.  
All LEDs are flashing red and the  
audio alarm cannot be silenced  
An internal UPS fault condition  
exists.  
Replace the electronics module.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter  
5
Specifications  
This chapter provides specifications that apply to all Compaq UPS R3000 XR models:  
! Physical specifications  
! Input specifications  
! Output specifications  
! Overcurrent protection  
! Battery specifications  
! Battery runtime  
! Environmental specifications  
Physical Specifications  
Table 5-1  
Physical Characteristics  
Feature  
U.S.  
Metric  
483 mm  
89 mm  
622 mm  
37 kg  
Dimensions  
Width  
19.0 in  
3.5 in  
24.5 in  
82 lb  
Height  
Depth  
Weight  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5-2 Compaq UPS R3000 XR Maintenance and Service Guide  
Input Specifications  
Table 5-2  
Input Specifications  
UPS Model  
Utility Voltage Default Settings Available Settings Power Cord Supplied  
Frequency Nominal Voltage Utility Voltage (VAC)  
(Hz)  
(VAC)  
R3000 XR-NA  
50/60  
120  
100, 110, 120, 127 Non-detachable power cord with  
NEMA L5-30 plug  
R3000j XR-JPN  
R3000h XR-NA  
R3000h XR-JPN  
R3000e XR-INT  
R3000i XR-EURO  
R3000i XR-SCHUKO  
R3000i XR-SA  
50/60  
50/60  
50/60  
50/60  
50/60  
50/60  
50/60  
100  
208  
208  
208  
230  
230  
230  
100, 110, 120, 127 Non-detachable power cord with  
NEMA L5-30 plug  
200, 220, 230, 240 Non-detachable power cord with  
NEMA L6-20 plug  
200, 220, 230, 240 Non-detachable power cord with  
NEMA L6-20 plug  
200, 220, 230, 240 Detachable power cord with  
country-specific plug  
200, 208, 220, 240 Non-detachable power cord with  
16A IEC-309 plug  
200, 208, 220, 240 Non-detachable power cord with  
16A CEE 7/7 SCHUKO plug  
200, 208, 220, 240 Non-detachable power cord with  
16A BS-546 plug  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications 5-3  
Output Specifications  
Table 5-3  
Output Specifications  
UPS Model  
Effective VA  
Nominal Power  
Rating (W)  
Load Segment #  
Output  
Receptacles  
R3000 XR-NA  
2880  
2700  
2250  
2700  
2700  
2700  
2700  
1
2 x 5-15R  
1 x L5-30R  
2
3
1
2 x 5-15R  
2 x 5-15R  
R3000j XR-JPN  
R3000h XR-NA  
R3000h XR-JPN  
R3000e XR-INT  
2400  
3000  
3000  
3000  
3000  
2 x 5-15R  
1 x L5-30R  
2
3
1
2 x 5-15R  
2 x 5-15R  
3 x IEC-320, C13  
1 x L6-20R  
2
3
1
3 x IEC-320, C13  
3 x IEC-320, C13  
3 x IEC-320, C13  
1 x L6-20R  
2
3
1
3 x IEC-320, C13  
3 x IEC-320, C13  
3 x IEC-320, C13  
1 x IEC-320, C19  
2
3
1
3 x IEC-320, C19  
3 x IEC-320, C13  
R3000i XR-EURO;  
R3000i XR-SCHUKO;  
R3000i XR-SA  
3 x IEC-320, C13  
1 x IEC-320, C19  
2
3
3 x IEC-320, C13  
3 x IEC-320, C13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5-4 Compaq UPS R3000 XR Maintenance and Service Guide  
Table 5-4  
Output Specifications  
Characteristics  
Configuration Setting (VAC)  
Available Nominal  
Output Voltage (VAC)  
Voltage  
100  
100  
110  
110  
120  
120  
127  
127  
200  
200  
208  
230  
208  
230  
240  
240  
Source of Power  
Regulation  
Output  
Utility power  
(normal range)  
-10% to +6% of nominal output voltage  
rating (within the guidelines of the  
Computer Business Equipment  
Manufacturers Association)  
Battery power  
±5% of nominal output voltage rating  
Feature  
Specification  
Other features  
On-line efficiency  
Voltage wave shape  
94%  
Sine wave; 5% THD with typical PFC  
load  
Surge suppression  
Noise filtering  
High energy 6500A peak  
MOVs and line filter for normal and  
common mode use  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications 5-5  
Overcurrent Protection  
Table 5-5  
Overcurrent Protection Per Model  
UPS Model  
Input Protection  
R3000 XR-NA  
Circuit protector for each load segment  
R3000j XR-JPN  
R3000h XR-NA  
R3000h XR-JPN  
R3000e XR-INT  
R3000i XR-EURO  
R3000i XR-SCHUKO  
R3000i XR-SA  
Circuit protector for each load segment  
Circuit protector for each load segment  
Circuit protector for each load segment  
Circuit protector for each load segment  
Circuit protector for each load segment  
Circuit protector for each load segment  
Circuit protector for each load segment  
Battery Specifications  
Table 5-6  
Battery Specifications  
Feature  
Type  
Specification  
Sealed lead-acid; maintenance-free  
120V battery string  
Voltage  
Charging  
24 hours to full charge  
4 hours to 90% capacity at default nominal utility voltage and no load  
Battery Runtime  
Table 5-7  
Estimated Battery Runtime  
Load  
(Percent)  
Estimated Battery Runtime  
(Minutes)  
UPS with ERM  
Runtime (Minutes)  
20  
50  
40  
12  
6.5  
5
120  
45  
80  
30  
100  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5-6 Compaq UPS R3000 XR Maintenance and Service Guide  
Environmental Specifications  
Table 5-8  
Environmental Specifications  
Feature  
Specification  
Operating temperature  
10oC to 40oC (50oF to 104oF)  
UL-tested at 25oC (77oF)  
Relative humidity  
Operating altitude  
Audible noise  
0% to 95%; non-condensing  
Up to 2,000 m (6,562 ft) above sea level*  
Less than 45 dBA  
Transit temperature  
Transit altitude  
-25oC to +55oC (-13oF to 131oF)  
15,000 m (49,212 ft) above sea level  
*Due to thermal limitations, the UPS will be derated above 2,000 m (6,561 ft).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
buttons  
Configure 3-4  
A
front panel 3-2, 3-3  
On 3-4, 3-6  
Standby 3-4  
adapters, removing 3-14  
alarms  
general 3-3  
Test/Alarm Reset 3-4  
responding to 4-2  
silencing 3-4  
troubleshooting 4-1  
altitude, operating 5-6  
audible noise specifications 5-6  
Auto-Bypass mode 3-6  
C
cables  
cautions 1-3  
part numbers 2-3, 2-5  
charging time, battery 5-5  
circuit protectors 3-5  
communications cable 1-3  
communications port 3-5  
Compaq Download Facility vi  
Compaq Power Management  
Utility 3-2  
B
backup time 5-5  
Bad Battery/Low Battery LED 3-3,  
4-4  
batteries  
accessing 3-8  
components  
charging 5-5  
identifying 3-2  
disposing of 3-10  
estimated backup time 5-5  
part numbers 2-3, 2-5  
precautions 1-3  
replacing 3-8, 3-17  
specifications 5-5  
storing 1-4  
repair warnings vi, 1-2  
Configure button 3-4, 3-6  
Configure LED 3-4  
Configure mode 3-4, 3-6  
connector, ERM 3-5  
control buttons 3-2, 3-3  
cords  
testing 3-8  
power 3-5  
type supported 5-5  
weight warning 1-2  
when to change 3-8  
battery compartment 3-2  
bezels, front  
retention clip 2-3, 3-5  
D
dimensions, UPS 5-1  
part numbers 2-3, 2-5  
removing 3-9, 3-18  
boards, removing 3-14  
E
electrical shock v, vi, 1-1, 3-1  
electronics module  
part number 2-3  
replacing 3-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2
Compaq UPS R3000 XR Maintenance and Service Guide  
emergency shutdown procedures 3-7  
environmental specifications 5-6  
ERM  
L
LED display 3-2, 3-3  
leveling jacks, warning 1-2  
load  
batteries  
part number 2-5  
replacing 3-17  
description 3-17  
exploded view 2-4  
front bezel  
effect on backup time 5-5  
indicators of 3-3  
recommended 3-17  
segments 3-5  
part number 2-5  
removing 3-18  
part number 2-5  
replacing 3-20  
unplugging 3-16  
warnings 1-2, 1-3  
exploded view  
M
modes  
Auto-Bypass 3-6  
Configure 3-4, 3-6  
Operate 3-4, 3-6  
Standby 3-4, 3-6  
ERM 2-4  
UPS 2-2  
Extended Runtime Module See  
ERM  
N
noise specifications 5-6  
nominal utility voltage  
specification 5-2  
F
frequency, input 5-2  
front bezels  
part numbers 2-3, 2-5  
removing 3-9, 3-18  
front panel  
O
On Battery LED 3-3, 4-2, 4-3  
On button 3-4, 3-6  
Operate mode 3-4, 3-6  
operating altitude 5-6  
operating temperature 5-6  
Options slot 3-5  
buttons 3-2, 3-3  
components 3-2  
LEDs 3-2, 3-3  
output specifications 5-3  
overcurrent protection 5-5  
overheating, caution vi  
Overload LED 3-3, 4-3  
G
general alarm 3-3  
ground bonding screw 3-5  
grounding plug vi  
grounding, caution vi  
P
panels  
H
front 3-2, 3-3  
rear 3-4  
hazardous energy levels vi, 3-1  
help  
part numbers 2-3, 2-5  
parts, replaceable 3-1  
personal injury v, vi, 1-1, 3-1  
physical specifications, UPS 5-1  
ports 3-5  
power cord, input 5-2  
powering down UPS 3-7  
problems See troubleshooting  
additional sources vi  
Compaq Authorized  
Resellers vii  
Compaq website vii  
technical support vii  
hot surfaces 1-1  
R
I
rack components, extending 1-2  
rear panel 3-4  
input specifications 5-2  
relative humidity 5-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
3
removing  
front bezels 3-9, 3-18  
UPS power 3-7  
replacing  
technician notes vi, 1-2  
telephone numbers  
Compaq Authorized  
Resellers vii  
adapters 3-14  
batteries 3-8, 3-17  
electronics modules 3-11  
ERM 3-20  
option boards 3-14  
UPS 3-16  
Compaq Download Facility vi  
technical support vii  
temperature, operating 5-6  
Test/Alarm Reset button 3-4  
tools, service 1-2, 3-2  
troubleshooting  
REPO port 3-5, 3-7  
retention clip, cord 2-3, 3-5  
after start 4-2  
alarm condition 4-1  
during start 4-1  
S
U
safety 1-1, 3-1  
self-test, initiating 3-4, 3-8  
servicable parts list 3-1  
silencing alarms 3-4  
Site Wiring Fault Indicator 3-3  
SmartStart and Support Software  
CD 3-2  
Uninterruptible Power System See  
UPS  
UPS  
components 3-2  
exploded view 2-2  
modes 3-6  
spare parts list 2-3, 2-5  
specifications  
part numbers 2-3  
powering down 3-7  
recommended load 3-17  
replacing 3-16  
battery 5-5  
environmental 5-6  
input 5-2  
overcurrent protection 5-5  
overview 5-1  
specifications 5-1  
used batteries 3-10  
Utility LED 3-3, 4-2, 4-3, 4-4  
UPS  
audible noise 5-6  
dimensions 5-1  
V
operating altitude 5-6  
operating temperature 5-6  
output 5-3  
ventilation clearances vi  
voltage  
battery 5-5  
physical 5-1  
nominal utility 5-2  
specifications 5-5  
relative humidity 5-6  
Standby button 3-4, 3-6  
Standby mode 3-4, 3-6  
symbols in text v  
W
warranty, voiding vi, 1-2  
weight  
T
battery assembly 5-5  
UPS 5-1  
technical support  
Compaq website vii  
telephone numbers vii  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Coleman Camping Equipment 214C700 User Manual
Cooper Lighting Indoor Furnishings YIxx User Manual
Curtis MP3 Player MPK7836 User Manual
Delhi Industries Blower DSQ D 10 User Manual
Delta Electronics Power Supply F48SA User Manual
Durst Printer Rho 800 User Manual
Electro Voice Speaker System DH2T 16 User Manual
Everpure Water System SSFM 50CC User Manual
Excalibur electronic Video Games 908 EFG User Manual
Generac Pressure Washer 6412 User Manual