RENEWAL PARTS IDENTIFICATION
161-304509-001
JANUARY, 2003
Industrial Wall Mounted Natural Convection
Space Heater - Type H
Specifications
Dimensions (In.)
Output
(kW)
Voltage
(Vac)
Output
(BTUH)
Wt.
Lbs.
Model
Width
Height
Depth
H-1801
H-1801
1.0
1.0
120
240
2
2
20-3/4
20-3/4
7-1/2
7-1/2
4-1/2
4-1/2
28
28
H-2405
H-2405
H-2405
1.5
1.5
1.5
120
240
480
2
2
2
26-1/2
26-1/2
26-1/2
7-1/2
7-1/2
7-1/2
4-1/2
4-1/2
4-1/2
30
30
30
H-2406
H-2406
H-2406
2.0
2.0
2.0
120
240
480
4
4
4
26-1/2
26-1/2
26-1/2
11-1/4
11-1/4
11-1/4
4-1/2
4-1/2
4-1/2
32
32
32
H-2407
H-2407
3.0
3.0
240
480
4
4
26-1/2
26-1/2
11-1/4
11-1/4
4-1/2
4-1/2
32
32
GENERAL INFORMATION
5. Heaters are mounted directly on any type of noncombustible sur-
face—masonry, concrete, block, plastered walls, metal framework,
etc.— using appropriate hardware.
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do
so could result in personal injury or property dam-
age. Heater must be installed by a qualified person
in accordance with the National Electrical Code,
NFPA 70.
6. Standard heaters are mounted in a horizontal position with the ter-
minal end on the left.
The system designer is responsible for the safety
of this equipment and should install adequate
back-up controls and safety devices with their
electric heating equipment. Where the conse-
quences of failure could result in personal injury or
property damage, back-up controls are essential.
1. All wiring should be done in accordance with local codes and the
National Electrical Code by a qualified person.
2. Connect air heaters to same line voltage as on heater nameplate.
3. Check possibility of corrosion if heaters are operated in atmos-
pheres other than air.
4. In general, locate heater approximately 1 foot from the floor, but
not less than 6 inches, for best overall results. Heater, however, can
be located anywhere to meet unique requirements of any particu-
lar application.
© 2010 Chromalox, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING
Note: All wiring should be done in accordance with local codes
and the National Electrical Code by a qualified person.
1. Electrical wiring enters heater case through 7/8” opening in end of
heater.
ELECTRIC SHOCK HAZARD. Any installation involv-
ing electric heaters must be performed by a quali-
fied person and must be effectively grounded in
accordance with the National Electrical Code to
eliminate shock hazard.
2. Grounding conductor, with green insulation, should be secured to
grounding screw located on case.
RENEWAL PARTS IDENTIFICATION
Reflector
Air Space Between Wall and Heat
Wall
1
3
4
5
Insulating
Bushing
Insulating
Bushing
Heater
Cover
Element
Model Volts Watts
Heating Element
120
240
480
1000
1000
1000
SE-1850 – 120V - 500W (2) 032-010978-001 (4) 032-010978-002 (4) 152-108257-001
SE-1850 – 240V - 500W (2) 032-010978-001 (4) 032-010978-002 (4) 152-108257-001
SE-1850 – 240V - 500W (2) 032-010978-001 (4) 032-010978-002 (4) 152-108257-001
H-1801
H-2405
H-2406
H-2407
120
240
480
1500
1500
1500
SE-2475 – 120V - 750W (2) 032-010978-001 (4) 032-010978-002 (4) 152-108257-002
SE-2475 – 240V - 750W (2) 032-010978-001 (4) 032-010978-002 (4) 152-108257-002
SE-2475 – 240V - 750W (2) 032-010978-001 (4) 032-010978-002 (4) 152-108257-002
120
240
480
2000
2000
2000
SE-2450 – 120V - 500W (4) 032-010978-001 (8) 032-010978-002 (8) 152-108257-003
SE-2450 – 240V - 500W (4) 032-010978-001 (8) 032-010978-002 (8) 152-108257-003
SE-2450 – 240V - 500W (4) 032-010978-001 (8) 032-010978-002 (8) 152-108257-003
120
240
480
3000
3000
3000
SE-2475 – 120V - 750W (4) 032-010978-001 (8) 032-010978-002 (8) 152-108257-003
SE-2475 – 240V - 750W (4) 032-010978-001 (8) 032-010978-002 (8) 152-108257-003
SE-2475 – 240V - 750W (4) 032-010978-001 (8) 032-010978-002 (8) 152-108257-003
OPERATION
HAZARD OF FIRE OR DISCOLORATION OF TEM-
PERATURE SENSITIVE FABRICS. Keep combustible
materials and such fabrics at least 4” away from
front of cover or above cover.
FIRE HAZARD. This heater is not intended for use in
hazardous atmospheres where flammable vapors,
gases, liquids or other combustible atmospheres are
present as defined in the National Electrical Code.
Failure to comply can result in explosion or fire.
MAINTENANCE
which will incinerate causing smoking and consequent wall dis-
coloration.
2. If heater is located in areas of heavy traffic, furnish suitable heater
guard (wall mounted pipe rail in front of case, for example) to pre-
vent damage to heater.
ELECTRIC SHOCK HAZARD. Disconnect all power
before attempting to service this heater.
1. Following long periods of idleness, heater should be vacuumed
before start-up to remove accumulated combustible particles