®
Chromalox
DIVISION
SALES
SECTION
4
VTS
(Supersedes PG436-1)
PG436-2
REFERENCE
161-304901-004
DATE
JUNE, 2010
DS-50600, STAR-GF, STAR-TIP and STAR-TG Kits
For Adding Optional Kits to STAR Radiant Heaters
Model STAR-TIP
STAR-TG
STAR-GF
Model DS50600
Always check to make certain the voltage rating of the kit
matches the voltage rating of the heater (See Nameplates).
ELECTRIC SHOCK HAZARD. Disconnect all power
to heater before installing or servicing kit(s).
Failure to do so could result in personal injury or
property damage. Kit(s) must be installed by a
qualified person in accordance with the National
Electrical Code, NFPA 70.
GENERAL
To use this instruction sheet from Table 1 select the Installation
Instructions by matching the Kit Model to the Heater Model. If a
match does not exist consult Factory.
The kits are add-on options to STAR Radiant Heaters. The
installation and renewal parts identification for the heater is cov-
ered in the instruction sheet provided with the heater. SAVE
BOTH COPIES OF THE INSTRUCTION SHEET.
Table 1
Kit Model
DS-50600
DS-50600
STAR-GF
STAR-TIP
STAR-TG
Used with Heater Model
Fixed STAR-06A and STAR-14A
Portable STAR-06A and STAR-14A
All Fixed STAR
Kit Function
Installation Instructions Wiring Diagram
Adds Integral Disconnect Switch
Adds Integral Disconnect Switch
See Page 2
See Page 3
Fig. 1
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Adds Wall Mounted Ground Fault Sensor
Adds Tip Over Shut Down
See Page 4
Portable STAR-06A and STAR-14A
Portable STAR-06A and STAR-14A
See Page 5
Adds Tip Over Shut Down with Ground Fault Sensor
See Pages 5 and 6
© 2008 Chromalox, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
Cover
(Step 5)
3 Pole Disconnect Switch
3 Pole Terminal Block w/Ground (Step 11)
Chase Nipple and Gasket
(Step 6)
Self Tapping Screw
(Step 8)
On-Off Handle
Opening for 1" Cord Fitting
(Step 11)
Cover
(Step 3)
Mounting Bracket
(Step 4)
3/8" Lockwasher and Nut
(Step 4)
Drawing shows 6 kW heater.
13.5 kW heater steps are identical.
INSTRUCTIONS FOR INSTALLING DISCONNECT SWITCH ON
6 AND 13.5 KW PORTABLE RADIANT HEATERS
1. Addition of the disconnect switch assy must be done by a qualified electrician.
2. The disconnect switch kit includes the following parts.
Verify that all parts are included, if not, contact the Chromalox Service Dept.
(1)Disconnect Switch Assy
(2)Mounting Bracket
(3)Hardware Kit:
Two 3/8” Lockwashers
Two 3/8” Nuts
One Self Tapping Screw
One Gasket for Cord Fitting (Supplied Separately)
3. Remove the screws in the heater terminal box. Remove cover.
4. Place mounting bracket over 3/8” studs as shown. Place lockwashers on studs and secure in place
with 3/8” nuts.
5. Remove cover from disconnect switch assy using same method as Step 3.
6. Remove Chase nipple and gasket from opening end of disconnect switch assy. Slide Chase nipple
through hole in heater terminal box and then gasket over threads.
7. Thread Chase nipple into threaded coupling. Hand tighten only.
8. LIne up hole in bottom of disconnect switch housing with hole in mounting bracket. Tap 10-32 x
1/2” long screw into mounting bracket.
9. Wrench tighten Chase nipple installed in Step 6.
10.Uncoil three (3) leads marked “1”, “2”, and “3” located in disconnect switch housing. Thread these
three (3) leads through the nipple. Attach leads to the terminals indicated on the heater wiring label
located on the cover of the heater. If using for single phase, cap off lead marked “3”.
11.Attach cord assy to the opening in the disconnect switch housing. Connect leads of cord to termi-
nal block.
12.Inspect all wiring to make sure all connections are tight, adequate electrical clearances exist, and
all electrical practices are met.
13.Install both covers.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTRUCTIONS FOR INSTALLING WALL MOUNTED STAR-GF
STAR-GF Mounting Dimensions
1. Check voltage on heater nameplate and STAR-GF to make cer-
tain voltages are the same. If voltages do not match, consult
factory.
8-1/2"
6"
2. The STAR-GF will provide ground fault protection for STAR
Radiant heaters. The number of heaters serviced by one (1)
STAR-GF is dependent on the number and length of the heat-
ing elements. See Table 2.
3/4
Table 2
3. See Instruction Sheet PG434 (provided with heater) for
Heater Model
Max. No. of Heaters
IMPORTANT INSTRUCTIONS and WIRING.
STAR-02A
STAR-05A
STAR-06A
STAR-14A
6
3
2
1
4. Using the STAR-GF as a template mark mounting holes on
wall. Use an anchoring method adequate to support the weight.
5. Wire between STAR-GF and heater, wire to terminal block.
Service entrance wiring to be made to contactor connectors.
For wire gage see Table 1 of PG434.
10-3/4"
10"
6. The ground fault sensor has been factory set at .03 Amps, DO
NOT CHANGE THE SETTING.
3/4
5/16 Dia.
6"
MAINTENANCE
The Chromalox STAR-GF ground fault sensor provides a reli-
able and cost effective method for sensing ground faults. The pur-
pose is to monitor for ground faults, sense potential heater failure
symptoms and to protect equipment.
Failure to do so could result in personal injury or
property damage. Kit(s) must be installed by a
qualified person in accordance with the National
Electrical Code, NFPA 70.
The current-carrying wires are routed through the current
transformer on the control. When ground current reaches the level
set by the trip point adjustment, (.03 Amps), the relay trips, illu-
minates the tripped LED and provides an output signal which de-
energizes the magnetic contactor.
If heating element(s) fail to operate:
1. Open door of enclosure. DANGER: Hazard of Electric
Shock. If "Tripped" indicator is on, this indicates one or more
heating elements are about to fail. Disconnect power and fol-
low the GF Troubleshooting Diagram below.
2. If the "Tripped" indicator is not on, check for blown fuses or
failed components within the heater's electrical system.
ELECTRIC SHOCK HAZARD. Disconnect all power
to heater before installing or servicing kit(s).
GF TROUBLESHOOTING DIAGRAM
START
Tripped Indicator
Light is On
Is this the
initial
No
Yes
This condition indicates
at least one element is
about to fail.
installation?
Did the problem
Is this the first
time heater is
used for the
season?
occur after
Is the set point of
the GF sensor set
at a value less than
.03 amps?
No
Call Chromalox
Service Dept.
1 800-368-2493
No
working properly
during part of this
heating season?
Yes
Unbuss wiring, check insulation resistance
Yes
Yes
on each element.
Unbuss wiring, check insulation resistance
on each element.
1. Each element to have at least 10 Meg
terminal to sheath.
2. If element does not have at least 10 Meg.
dry out element by applying half of the
rated voltage for one hour.
3. Rebuss elements, re-energize heater, flip
toggle switch back and forth, one time
to reset GF sensor.
1. Each element to have at least 10 Meg
terminal to sheath.
2. If element does not have at least 10 Meg.
dry out element by applying half of the
rated voltage for one hour.
3. Rebuss elements, re-energize heater, flip
toggle switch back and forth, one time
to reset GF sensor.
1. Turn set point dial
clockwise to .03 amps.
2. Flip toggle switch mounted ontop
of enclosure back and forth one
time, (this resets the GF sensor).
Do you want to
reduce future
down time and
maintenance
costs?
No
Yes
No
Does the heater
operate?
1. Replace all elements.
2. Flip toggle switch back
and forth, one time to
reset GF sensor.
Does the
heater
operate?
No
Yes
Does the
heater
operate?
No
Close cover.
Call Chromalox
Service Dept.
1 800-368-2493
Yes
No
Does the heater
operate?
Yes
Close cover.
Close cover.
Yes
Close cover.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
3 POLE CONTACTOR
SELF TAPPING SCREW (STEP 8)
HEAT/NO HEAT
OPENING FOR 1" CORD FITTING (STEP 11)
CHASE NIPPLE AND GASKET (STEP 6)
MOUNTING BRACKET
(STEP 4)
COVER (STEP 3)
3/8" LOCKWASHER AND NUT (STEP 4)
VIEW SHOWN WITH TIP OVER SWITCH ASSY COVER REMOVED
Drawing shows 6 kW heater.
13.5 kW heater steps are identical.
INSTRUCTIONS FOR INSTALLING “STAR-TIP” AND “STAR-TG” ON
6 AND 13.5 KW PORTABLE RADIANT HEATERS
1. Addition of the tip over switch assy must be done by a qualified electrician.
2. The tip over switch assy includes the following parts.
Verify that all parts are included, if not, contact the Chromalox Service Dept.
(1)Tip Over Switch Assy
(2)Mounting Bracket
(3)Hardware Kit:
Two 3/8” Lockwashers
Two 3/8” Nuts
Two Self Tapping Screw
One Gasket for Cord Fitting (Supplied Separately)
3. Remove the screws in the heater terminal box. Remove cover.
4. Place mounting bracket over 3/8” studs as shown. Place lockwashers on studs and secure in place
with 3/8” nuts.
5. Remove cover from tip over switch assy using same method as Step 3.
6. Remove Chase nipple and gasket from open end of tip over switch assy. Slide Chase nipple through
hole in heater terminal box and then gasket over threads.
7. Thread Chase nipple into threaded coupling. Hand tighten nipple.
8. Line up hole in bottom of tip over switch with hole in mounting bracket. Tap 10-32 x 1/2” long
screws into mounting bracket.
9. Wrench tightened Chase nipple installed in Step 6.
10.Uncoil three (3) leads marked “1”, “2”, and “3” located in disconnect switch housing. Thread these
three (3) leads through the nipple. Wire nut leads of tip over switch to leads of heater. If using for
single phase, cap off lead marked “3”.
11.Attach cord assembly to the opening in the tip over switch housing. Connect leads of cord to the
contactor.
12.Inspect all wiring to make sure all connections are tight, adequate electrical clearances exist, and
all electrical practices are met.
13.Install both covers.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
The Chromalox STAR-TG tip over cutout with ground fault
Failure to do so could result in personal injury or
property damage. Kit(s) must be installed by a
qualified person in accordance with the National
Electrical Code, NFPA 70.
sensor provides a reliable and cost effective method for sensing
ground faults and to shut off the heater in case of tip-over. The pur-
pose of the ground fault control is to monitor for ground faults,
sense potential heater failure symptoms and to protect equipment.
The current-carrying wires are routed through the current
transformer on the control. When ground current reaches the level
set by the trip point adjustment, (.03 amps), the relay trips, illumi-
nates the tripped LED and provides an output signal which de-
energizes the magnetic contactor.
If heating element(s) fail to operate:
1. Open door of enclosure. DANGER: Hazard of Electric
Shock.
2. If "Tripped" indicator is not on, check for blown fuses or failed
electrical components in the heater’s electrical system includ-
ing the tip over trip mechanism.then this indicates one or more
heating elements are about to fail.
3. Check pendulums on the tip over switch mechanisms to be sure
they are not blocked.
4. If the "Tripped" indicator is on, then this indicates one or more
heating elements are about to fail. Disconnect power and fol-
low the GF Troubleshooting Diagram below.
ELECTRIC SHOCK HAZARD. Disconnect all power
to heater before installing or servicing kit(s).
TG TROUBLESHOOTING DIAGRAM
START
Tripped Indicator
Light is On
Is this the
initial
No
Yes
This condition indicates
at least one element is
about to fail.
installation?
Did the problem
Is this the first
time heater is
used for the
season?
occur after
Is the set point of
the GF sensor set
at a value less than
.03 amps?
No
Call Chromalox
Service Dept.
1 800-368-2493
No
working properly
during part of this
heating season?
Yes
Unbuss wiring, check insulation resistance
Yes
Yes
on each element.
Unbuss wiring, check insulation resistance
on each element.
1. Each element to have at least 10 Meg
terminal to sheath.
2. If element does not have at least 10 Meg.
dry out element by applying half of the
rated voltage for one hour.
3. Rebuss elements, re-energize heater, flip
toggle switch back and forth, one time
to reset GF sensor.
1. Each element to have at least 10 Meg
terminal to sheath.
2. If element does not have at least 10 Meg.
dry out element by applying half of the
rated voltage for one hour.
3. Rebuss elements, re-energize heater, flip
toggle switch back and forth, one time
to reset GF sensor.
1. Turn set point dial
clockwise to .03 amps.
2. Flip toggle switch mounted ontop
of enclosure back and forth one
time, (this resets the GF sensor).
Do you want to
reduce future
down time and
maintenance
costs?
No
Yes
No
Does the heater
operate?
1. Replace all elements.
2. Flip toggle switch back
and forth, one time to
reset GF sensor.
Does the
heater
operate?
No
Yes
Does the
heater
operate?
No
Close cover.
Call Chromalox
Service Dept.
1 800-368-2493
Yes
No
Does the heater
operate?
Yes
Close all covers.
Close all covers.
Yes
Close all covers.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING
For applicable wiring diagram see Table 1
TERMINAL BLOCK
TOGGLE
SWITCH
TIPOVER
SWITCH
NOTES:
GRN L1 L2
L3
1. USE 90 DEG. C. MIN. WIRING.
TIPOVER
SWITCH
4
3
6
5
2. USE COPPER CONDUCTORS ONLY.
3. TO MAINTAIN THE ENVIRONMENTAL
RATING OF THIS ENCLOSURE, USE
ONLY UL LISTED OR RECOGNIZED
LIQUID TIGHT CONDUIT HUBS.
2
CONTACTOR
1
3
2
1
L3
L2
L1
NOTES:
1. USE 90 DEG. C. MIN. WIRING.
DISCONNECT
SWITCH
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TIP"
MATCHES VOLTAGE OF HEATER.
3
2
1
TO TERMINALS
INSIDE HEATER
JUNCTION BOX
TO TERMINALS
INSIDE HEATER
JUNCTION BOX
PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
Fig. 1
240V = BLK AND ORG
277V = BLK AND BRN
BLACK
WHITE
380V = BLK AND VIOLET
480V = BLK AND BLK/RED
600V = BLK AND GRAY
TRANSFORMER
UNUSED LEADS CAPPED OFF.
Fig. 3
GROUND FAULT
MONITOR
TOGGLE SWITCH
SUPPLY
G
3
2
1
NC
CO
TO TERMINALS
INSIDE HEATER
JUNCTION BOX
NO
CONTACTOR
L3
L2
L1
SEE NOTES
POWER LEADS MUST
PASS THROUGH CURRENT
TRANSFORMER POSITION
OF GROUND FAULT
MONITOR
ATTACHED TO
AUXILLARY TERMINALS
PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
240V = BLK AND ORG
NOTES:
1. USE 90 DEG. C. MIN. WIRING.
277V = BLK AND BRN
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TG"
MATCHES VOLTAGE OF HEATER.
380V = BLK AND VIOLET
480V = BLK AND BLK/RED
600V = BLK AND GRAY
UNUSED LEADS CAPPED OFF.
WHITE
BLACK
TRANSFORMER
Fig. 2
GROUND FAULT
MONITOR
TOGGLE
SWITCH
TIPOVER
SWITCH
TIPOVER
SWITCH
3
2
1
SUPPLY
NC
NO
CO
TO TERMINALS
INSIDE HEATER
JUNCTION BOX
CONTACTOR
L3
L2
L1
POWER LEADS MUST
PASS THROUGH CURRENT
TRANSFORMER POSITION
OF GROUND FAULT
MONITOR
SEE NOTES
ATTACHED TO
AUXILLARY
TERMINALS
PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
240V = BLK AND ORG
277V = BLK AND BRN
NOTES:
1. USE 90 DEG. C. MIN. WIRING.
480V = BLK AND BLK/RED
380V = BLK AND VIOLET
600V = BLK AND GRAY
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TG"
MATCHES VOLTAGE OF HEATER.
UNUSED LEADS CAPPED OFF.
WHITE
BLACK
TRANSFORMER
Fig. 4
7
Download from Www.Somanuals.com. All Manuals Search And Download.
RENEWAL PARTS IDENTIFICATION
Kit
Model
Disconnect
Switch
DS Shaft
Gasket
Cover
Gasket
“U” Shaped
Clamp
Term. Block
Cont. Sect.
Term. Block
End. Sect.
Toggle
Switch
Toggle Switch
Boot
Ground Fault
Sensor
Tip Over
Switch
Contactor
DS-506008 292-303472-007 132-304689-001 132-304879-002 056-304884-004
NA
NA
NA
NA
NA
STAR-GF-8
STAR-GF-3
STAR-GF-4
STAR-GF-7
STAR-GF-6
STAR-TIP-8
STAR-TIP-2
072-121651-062
STAR-TIP-3
STAR-TIP-4
STAR-TIP-7
STAR-TIP-6
STAR-TG-8
STAR-TG-2
STAR-TG-3
STAR-TG-4
STAR-TG-7
STAR-TG-6
NA
NA
NA
NA
303-052241-002 303-052241-001 292-046123-001 024-052539-001 072-306110-008
N/A
292-304695-001
072-121651-062
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
2150 N. RULON WHITE BLVD., OGDEN, UT 84404
TA - T0 - EF
Litho in U.S.A.
Phone: 1-800-368-2493
Download from Www.Somanuals.com. All Manuals Search And Download.
|